In Place Density of Soils ASTM D2922 & D3017
Date:
06/19/2024
Project Number:
23-289
Project Name:
Good to Go Rexburg
Client:
Uncommon Builders
Time Start:
01:00 PM
Contractor:
HK Contractors
Total Time on Project:
3.5
Current Weather Conditions:
Sunny/Clear
Wind:
Calm
Instrument ID
76560
MS:
624
Ambient Temperature (°F):
67
DS:
2355
Results
Test
#:
Location:Elevation: Depth:Material:Wet:Dry:% M:Proctor
#:
%
Proctor:
Result
1 South
shoulder of
University
Blvd. East of
S 12th West
approximately
650’
Approximately
1’
above
bottom
of
excavation
6 Pit Run 136.6 126.5 8.0 131.8 96 Pass
2 South
shoulder of
University
Blvd. East of
S 12th West
approximately
Approximately
1’
above
bottom
of
excavation
6 Pit Run 137.4 127.9 7.4 131.8 97 Pass
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
2C79AA9E-2834-4540-B1D6-522BC0FA4ACA 2
Test
#:
Location:Elevation: Depth:Material:Wet:Dry:% M:Proctor
#:
%
Proctor:
Result
575’
3 South
shoulder of
University
Blvd. East of
S 12th West
approximately
500’
Approximately
1’
above
bottom
of
excavation
6 Pit Run 137.0 130.7 4.8 131.8 99 Pass
4 North side
of wash bay
drain
approximately
425’ from
the east end.
Approximately
1’
above
bottom
of
excavation
6 Pit Run 134.2 129.6 3.5 131.8 98 Pass
5 North side
of wash bay
drain
approximately
350’ from
the east end.
Approximately
1’
above
bottom
of
excavation
6 Pit Run 141.9 133.5 6.3 131.8 101 Pass
6 North side
of wash bay
drain
approximately
275’ from
the east end.
Approximately
1’
above
bottom
of
excavation
6 Pit Run 132.9 126.3 5.3 131.8 96 Pass
7 South
shoulder of
University
Blvd. East of
S 12th West
approximately
200’ from
the east end.
Approximately
1’
above
bottom
of
excavation
6 Pit Run 137.6 125.7 5.4 131.8 95 Pass
8 South
shoulder of
University
Blvd. East of
S 12th West
approximately
125’ from
the east end.
Approximately
1’
above
bottom
of
excavation
6 Pit Run 131.1 125.8 4.1 131.8 95 Pass
9 South Approximately 6 Pit Run 134.9 127.2 6.0 131.8 97 Pass
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
2C79AA9E-2834-4540-B1D6-522BC0FA4ACA 3
Test
#:
Location:Elevation: Depth:Material:Wet:Dry:% M:Proctor
#:
%
Proctor:
Result
shoulder of
University
Blvd. East of
S 12th West
approximately
50’ from the
east end.
1’
above
bottom
of
excavation
Field Technician Information
Truck
PUNISHER
Mileage from Lab to Project (One Way)
8
Total Mileage
63050.00
Tested By:
Ben E Ball
Signature:
Items observed are in general conformance with approved project documents and jurisdictional requirements.
Items observed are NOT in general conformance with approved project documents and jurisdictional requirements.
Observations/Remarks:
Arrived on site at 1:20 PM and met Leon from HK Contractors. He directed me to the South shoulder of
University Blvd, from S 12th West Street, approximately 700’ east. The contractor was still installing the first lift
on the west end, so I began testing on the east end. After testing approximately 600’, I caught up to them. I
informed Leon that I had another job to attend to and would return later. Left the site at 2:30 PM and returned
at 3:50 PM to finish testing. I informed Leon of my results before leaving the site at 4:55 PM.
Reviewed By:
Luke Hammar
Signature: