HomeMy WebLinkAboutREDLINED REVIEW RESPONSE - 22-00821 - Shelfology - AdditionDescription : Shelfology - Addition Address : 156 N 2nd E Application Type : Document Filename : 22-00821 Review Comments Responses, 221208 (1).pdf Array Comment Author Contact Information: Corrections in the following table need to be applied before a permit can be issued Review Report Revisions Required # 22-00821 Commercial - Addition Please digitally re-submit all pages of the plan set in response to requested revisions for our next review cycle, with noted items resolved. Report Date: 12.14.2022 Approval of plans does not constitute approval of variance from code Page 1 of 1 Powered by TCPDF (www.tcpdf.org) Author Name Author Email Author Phone No.: Alex Owens Alex.Owens@rexburg.org 208-372-2172 Description : Shelfology - Addition Address : 156 N 2nd E Application Type : Document Filename : 2022_03_SHELFOLOGY SHOP EXPANSION_ELEC.pdf Array Comment Author Contact Information: Corrections in the following table need to be applied before a permit can be issued Review Report Revisions Required Page Reference Annotation Type Author : Department Status Page Review Comments Applicant Response Comments E00 - ELECTRICAL SYMBOLS & ABBREV- Callout Alex Owens : Electrical Open 1 For verification: Notes Q,R,S are above and beyond NEC requirements. Please verify this is as the engineer requires and it will be inspected accordingly. E00 - ELECTRICAL SYMBOLS & ABBREV- Free Text Alex Owens : Electrical Open 1 All electrical work to comply with 2017 NEC. # 22-00821 Commercial - Addition Please digitally re-submit all pages of the plan set in response to requested revisions for our next review cycle, with noted items resolved. Report Date: 11.08.2022 Approval of plans does not constitute approval of variance from code Page 1 of 1 Powered by TCPDF (www.tcpdf.org) 1. We recognize these requirement exceed NEC requirements but are considered good practices. Project to comply with Notes Q, R, & S as specified. 2. A GENERAL NOTE will be included to require compliance with 2017 NEC. J PC DS M F CONDUIT CONTINUATION CONDUIT CONCEALED IN WALL OR CEILING CONDUIT EXISTING CONDUIT CONCEALED UNDERGROUND CONDUIT STUB DOWN STUB THROUGH CONDUIT STUB UP JUNCTION BOX (NEW, EXISTING, DEMO) ELECTRICAL DISTRIBUTION PANELBOARD EQUIPMENT ENCLOSURE AS NOTED SIMPLEX RECEPTACLE DUPLEX RECEPTACLE (NEW, EXISTING, DEMO) DOUBLE DUPLEX RECEPTACLE OVER-COUNTER RECEPTACLE CONTROLLED RECEPTACLE EMERGENCY EXIT SIGN WITH BATTERY BACKUP: SHADED QUARTER OF SYMBOL INDICATES LIGHTED 'EXIT' ON THAT FACE ARROWS INDICATE LIGHTED DIRECTIONAL ARROW ON THAT FACE. CONNECT TO UNSWITCHED LOCAL LIGHTING CIRCUIT EMERGENCY LIGHTING (SURFACE, RECESSED) CONNECT TO UNSWITCHED LOCAL LIGHTING CIRCUIT FIXTURES WITH HALF-SHADING ARE EMERGENCY LIGHTS WITH BATTERY BACKUP. BATTERY BACKUP SHALL PROVIDE MINIMUM 1100 LUMENS PER FIXTURE FOR 90 MINUTES. EMERGENCY BATTERY UNIT SHALL BE CONNECTED TO UNSWITCHED LOCAL LIGHTING CIRCUIT. FIXTURES SHALL BE SWITCHED WITH ROOM LIGHTS. FIXTURES TO REMAIN ON AT LOSS OF POWER. FIXTURES WITH 'NL' SHALL BE EMERGENCY/NIGHT LIGHTS CONNECTED FOR 24 HOUR OPERATION. 2X4 LIGHT FIXTURE PENDANT FIXTURE RECESSED DOWNLIGHT FIXTURE WALL MOUNTED FIXTURE LIGHT FIXTURE CALLOUT E J XX SWITCH X =2 -DOUBLE POLE-DOUBLE THROW 3 -THREE-WAY 3 -FOUR-WAY D -DIMMER HP -HORSEPOWER RATED SWITCH WITH THERMAL OVERLOADS SIZED AS REQUIRED BY EQUIPMENT LABEL RATING K -KEY OPERATED OV -LOW VOLTAGE MOMENTARY OVERRIDE SWITCH OS -OCCUPANCY SENSOR PASSIVE INFRARED WALL SWITCH, WITH A 30 MINUTE TIME DELAY, PROVIDE WITH STAINLESS STEEL FACEPLATE P -NEON PILOT LIGHT L -LIGHTED SWITCH T -TIMER AS NOTED W -WIRELESS SWITCH WP -WEATHERPROOF SHEET NOTE CALLOUT REVISION DELTA X ## ##-## 1 SPECIAL ELECTRICAL CONNECTION: COORDINATE REQUIREMENTS WITH EQUIPMENT BEING SERVED MOTOR CONNECTION STARTER OR CONTACTOR: SIZE AS REQUIRED BY EQUIPMENT MANUFACTURER COMBINATION MOTOR STARTER/DISCONNECT: SIZE AS REQUIRED BY EQUIPMENT MANUFACTURER DISCONNECT SWITCH: SIZE AS REQUIRED BY EQUIPMENT MANUFACTURER F=FUSED, BLANK=UNFUSED SWITCH/DISCONNECT CONFIGURATION DESIGNATION NUMBER OF POLES AMPERE RATING OF THE SWITCH NEMA CLASSIFICATION THERMOSTAT OR TEMPERATURE SENSOR: SEE MECHANICAL DRAWINGS FOR LOCATIONS FURNISH AND INSTALL BACKBOX AND 1"C TO ABOVE ACCESSIBLE CEILING. COORDINATE INSTALLATION WITH MECHANICAL SMOKE DAMPER: SEE MECHANICAL DRAWINGS FOR LOCATIONS VERIFY REQUIREMENTS WITH MECHANICAL AND FIRE PROTECTION FURNISH AND INSTALL ALL ELECTRICAL REQUIRED FOR COMPLETE OPERATIONAL SYSTEM DUCT TYPE SMOKE DETECTOR: SEE MECHANICAL DRAWINGS FOR LOCATIONS VERIFY REQUIREMENTS WITH MECHANICAL AND FIRE PROTECTION FURNISH AND INSTALL ALL ELECTRICAL REQUIRED FOR COMPLETE OPERATIONAL SYSTEM MECHANICAL EQUIPMENT CALLOUT 1 / 30 / 3 XX XX T TS D SD J J A/V GFCI RECEPTACLE GFCI OVER-COUNTER RECEPTACLE GFCI CONTROLLED RECEPTACLE WEATHERPROOF GFCI RECEPTACLE ISOLATED GROUND RECEPTACLE USB CHARGER/DUPLEX RECEPTACLE OVER-COUNTER USB CHARGER/DUPLEX RECEPTACLE CONTROLLED USB CHARGER/DUPLEX RECEPTACLE FLOOR RECEPTCLES: FLUSH WITH COVER FLUSH FLOOR BOX DUPLEX RECEPTACLE, COMM/DATA, A/V CEILING RECEPTACLE: FLUSH WITH CEILING HOMERUN 2X2 LIGHT FIXTURE STRIP LIGHT FIXTURE WALL SCONCE RECESSED STEP FIXTURE BOLLARD FIXTURE POST TOP LIGHT FIXTURE, POLE, AND BASE SWITCH 120/277 VOLT, 20 AMP CEILING OCCUPANCY SENSOR OS INTERIOR DAYLIGHT SENSOR EXTERIOR PHOTOCELL TELEPHONE TERMINAL BOARD (PLAN VIEW) SIGNAL OUTLETS SYSTEM NOTES: SYSTEMS ARE RACEWAY ONLY FOR THIS CONTRACTOR UON. 4" SQUARE BOX MINIMUM WITH SINGLE GANG MUD RING UON. 1" MINIMUM CONDUIT SIZE FROM BOX TO NEAREST ACCESSIBLE CEILING. TELEPHONE-DATA OUTLET WEATHERPROOF GFCI RECEPTACLE OVER-COUNTER WEATHERPROOF GFCI RECEPTACLE HORIZONTAL FACEPLATE SMOKE/CO DETECTOR: KIDDE i12010SCO (OR APPROVED EQUIVALENT) SD 7 A 8 B 65 7 C D 865 243 1 A B 243 C DWG‐ EFFECTIVE DATE: REV DATE:DESIGN: APPROVED: NAME AND DATE FOR  CURRENT RELEASE ONLY 1 D XL E N G I N E E R I N G ID A H O F A L L S , I D A H O XL ENGINEERING 5257 WILD DUNES LN IDAHO FALLS, ID 83404 ELECTRICAL ENGINEER MARK OWENS (208) 709-3111 MOWENS@XLENGINEERING.NET MECHANICAL ENGINEER JOHN GODAK (208) 339-4907 JGODAK@XLENGINEERING.NET M. Owens M. Owens E00 Sh e l f o l o g y S h o p E x p a n s i o n 15 6 N 2 n d E Re x b u r g , I D 8 3 4 4 0 EL E C T R I C A L S Y M B O L S & A B B R E V . 10/15/22 10/15/22 ELECTRICAL ABBREVIATIONS SYMBOLS____________________________________________________________________________GENERAL NOTES:DRAWING INDEX ELECTRICAL E00 ELECTRICAL SYMBOLS & ABBREV. E01 ENERGY COMPLIANCE FORMS E11 LIGHTING & POWER PLANS - FULFILLMENT E12 LIGHTING PLAN LEVEL 2 E21 POWER PLAN - LEVEL 1 FULFILLMENT E22 POWER PLAN LEVEL 2 E23 POWER PLAN ROOF E31 MECHANICAL POWER PLAN LEVEL 1 E32 MECHANICAL POWER PLAN LEVEL 2 E71 DETAILS E72 DETAILS #"C SIZE OF TRADE SIZE CONDUIT. # = 1/2"C, 2"C. #P NUMBER OF POLES. # = 1P, 2P, ETC. #W NUMBER OF WIRES, # = 3W, 4W, ETC. A AMPERE AC ALTERNATING CURRENT ADA AMERICANS WITH DISABILITIES ACT AFF ABOVE FINISHED FLOOR AFG ABOVE FINISHED GRADE AHJ AUTHORITY HAVING JURISDICTION AIC AMPERE INTERRUPTING CAPACITY AL ALUMINUM ANN ANNUNCIATOR AUX AUXILIARY AWG AMERICAN WIRE GAUGE C CONDUIT CB CIRCUIT BREAKER CD CANDELLA CLG CEILING CT CURRENT TRANSFORMER CU COPPER DC DIRECT CURRENT DPDT DOUBLE POLE, DOUBLE THROW DPST DOUBLE POLE, SINGLE THROW EMT ELECTRICAL METALLIC TUBING EP EXPLOSION PROOF EWH ELECTRIC WATER HEATER FFUSE FACP FIRE ALARM CONTROL PANEL GFCI GROUND FAULT CIRCUIT INTERRUPTER GFI GROUND FAULT INTERRUPTER GND GROUND HOA HAND-OFF-AUTO HP HORSE POWER HVAC HEATING VENTILATION AND AIR CONDITIONING I/O INPUT / OUTPUT IG ISOLATED GROUND INC INCANDESCENT J-BOX JUNCTION BOX KCMIL THOUSAND CIRCULAR MIL KO KNOCK OUT KV KILOVOLT KVA KILOVOLT AMPERE KW KILOWATT KWH KILOWATT HOUR LV LOW VOLTAGE MCC MOTOR CONTROL CENTER MDSB MAIN DISTRIBUTION SWITCHBOARD A. ALL WORK SHALL BE IN ACCORDANCE WITH THE LATEST EDITION OF THE LOCALLY ADOPTED ELECTRICAL CODE, ALL LOCAL CODES, AND TO THE FULL ACCEPTANCE OF THE AUTHORITY HAVING JURISDICTION. WHENEVER THE REQUIREMENTS OF THE ELECTRICAL SPECIFICATIONS OR DRAWINGS EXCEED THOSE OF THE APPLICABLE CODES OR STANDARDS, THE REQUIREMENTS OF THE SPECIFICATIONS AND DRAWINGS SHALL GOVERN. B. BIDDERS SHALL VIEW THE SITE AND SHALL INCLUDE ALL COSTS INCURRED BY EXISTING CONDITIONS IN THE BID PROPOSAL. THE CONTRACTOR SHALL FAMILIARIZE THEMSELVES WTIH ALL RELEVANT BID DOCUMENTS, BID FORMS AND SPECIFICATIONS. ANY INCREASED COST INCURRED DUE TO FAILURE TO BECOME FAMILIAR WITH THESE DOCUMENTS SHALL BE BORNE BY THE CONTRACTOR. WORK SHALL INCLUDE ALL LABOR, EQUIPMENT, APPLIANCES, MATERIALS, TRANSPORTATION, FACILITIES AND SERVICES NECESSARY FOR AND/OR REASONABLY INCIDENTAL TO THE COMPLETION OF ALL ELECTRICAL WORK IN STRICT COMPLIANCE WITH THE DRAWINGS AND OTHER CONTRACT DOCUMENTS. WORK SHALL INCLUDE, BUT NOT BE NECESSARILY LIMITED TO, THE WORK SPECIFIED AND INDICATED ON DRAWINGS. C. OBTAIN ALL PERMITS, COORDINATE, FURNISH, INSTALL, CONNECT AND TEST ALL ELECTRICAL EQUIPMENT REQUIRED FOR ALL THE SYSTEMS INSTALLED UNDER THIS CONTRACT TO INSURE COMPLETE AND FULLY OPERATIONAL SYSTEMS. D. CONTRACTOR SHALL MAINTAIN A COMPLETE SET OF AS-BUILT DRAWINGS. AS-BUILT SET OF DRAWINGS SHALL BE UPDATED DAILY AND SHALL DOCUMENT THE ACTUAL INSTALLED CONDITION OF THE ENTIRE ELECTRICAL INSTALLATION. AS-BUILT SET OF DRAWINGS SHALL BE AVAILABLE AT ALL TIMES ON THE SITE FOR INSPECTION BY CODE OFFICIALS, OWNER, ARCHITECT, AND ENGINEER. E. PROPOSED MODIFICATIONS OF ENGINEERED ELECTRICAL DRAWINGS SHALL BE APPROVED BY ENGINEER OF RECORD PRIOR TO PROCEEDING WITH WORK. PROPOSED CHANGES SHALL COMPLY WITH ALL APPLICABLE CODES/JURISDICTION REQUIREMENTS. COST OF ANY ENGINEERING/REVIEW REQUIRED BY PROPOSED CHANGES SHALL BE BORNE BY ENTITY PROPOSING CHANGE. F. DESIGN IS BASED ON BEST AVAILABLE INFORMATION. CONTRACTOR SHALL FIELD VERIFY EXISTING CONDITIONS TO DETERMINE STATUS OF ACTUAL CONDITIONS AS THEY RELATE TO THE SCOPE OF WORK AS SHOWN ON THESE PLANS. G. COORDINATE ALL ELECTRICAL WORK WITH ALL OTHER TRADES. H. COORDINATE EXACT LOCATION AND MOUNTING HEIGHTS OF ALL ELECTRICAL EQUIPMENT AND DEVICES WITH THE ARCHITECTURAL ELEVATIONS AND DETAILS PRIOR TO ROUGH-IN. I. CONTRACTOR SHALL COORDINATE WITH WALL TYPES AND FURNISH AND INSTALL EXTENSION RINGS AS REQUIRED. (I.E. WALLS WITH TWO LAYERS OF GYP BOARD). J. ALL MATERIALS AND EQUIPMENT FURNISHED TO THE PROJECT SHALL BE NEW AND SHALL BEAR THE LISTING LABEL OF A NATIONALLY RECOGNIZED TESTING LABORATORY (NRTL), WHERE APPLICABLE. K. ALL ELECTRICAL BOXES, FITTINGS AND CABINETS SHALL BE OF STEEL CONSTRUCTION, GALVANIZED OR POWDER COATED, NEMA 1 TYPE, UON. L. ALL DEVICES (SWITCHES/RECEPTACLES/TELECOMMUNICATIONS) SHALL BE WHITE AND COVERPLATES SHALL BE BRUSHED STAINLESS STEEL, UON. M. ALL CIRCUIT BREAKERS SUPPLYING MOTOR LOADS SHALL BE HACR RATED. N. ALL ELECTRICAL DEVICES AND TERMINALS SHALL BE RATED 75°C MINIMUM. O. ALL CONDUCTORS SHALL BE STRANDED COPPER, 600 VOLT RATED. INSULATION TYPE SHALL BE THHN/THWN, FULLY COLOR CODED WITH GAUGE, TYPE AND MANUFACTURER MARKED EVERY 24" ALONG. CONDUCTOR COLOR CODE SHALL BE AS FOLLOWS: 208Y/120 VOLT SYSTEM 480Y/277 VOLT SYSTEM PHASE A -BLACK PHASE A -BROWN PHASE B -RED PHASE B -ORANGE PHASE C -BLUE PHASE C -YELLOW NEUTRAL -WHITE NEUTRAL -GRAY GROUND -GREEN GROUND -GREEN P. MINIMUM SIZE WIRE FOR POWER AND LIGHTING CIRCUITS SHALL BE #12 AWG, UON. CONDUCTOR SIZE SHALL BE CONTINUOUS THROUGHOUT THE ENTIRE LENGTH OF THE CIRCUIT. Q. ALL CIRCUITS SHALL HAVE AN INDEPENDENT NEUTRAL CONDUCTOR. NO EDISON STYLE SHARED NEUTRAL CONDUCTORS ARE ALLOWED. R. ALL CONDUITS SHALL CONTAIN A GROUND CONDUCTOR SIZED PER NEC. S. ALL POWER AND LIGHTING CONDUCTORS SHALL BE ROUTED IN 3/4" CONDUIT MINIMUM. NO MC TYPE CABLE IS ALLOWED WITH THE EXCEPTION OF CEILING WHIPS 6' OR LESS. T. CONDUIT AND WIRE FOR FEEDER OR BRANCH CIRCUITS SHALL NOT BE RUN ON OR ABOVE THE ROOF. ELECTRICAL SERVICES FOR ROOF MOUNTED EQUIPMENT ARE TO BE RUN IN A STRAIGHT LINE FROM THE ROOF PENETRATION TO THE ELECTRICAL CONNECTION FOR THE UNIT SERVED. U. ROUTE ALL CONDUIT HOME RUNS TO PANELS OVERHEAD AND ABOVE ACCESSIBLE CEILINGS WHERE AVAILABLE. V. INSTALL CONDUIT A MINIMUM OF 4" BELOW BOTTOM OF CONCRETE SLAB WHERE RUNNING UNDER FLOOR. ALL ELBOWS SHALL BE RIGID METAL CONDUIT OR INTERMEDIATE METAL CONDUIT. W. ALL EQUIPMENT, SWITCHING DEVICES AND PANELS SHALL BE MOUNTED SO AS TO BE ACCESSIBLE AND SHALL BE MOUNTED PLUMB AND SQUARE WITH WALLS. X. BOXES MOUNTED IN A COMMON WALL SHALL BE OFFSET A MINIMUM OF 12" OR MOUNTED IN ADJACENT STUD SPACES. BOXES MOUNTED BACK-TO-BACK ARE NOT ALLOWED. Y. ALL ELECTRICAL EQUIPMENT, RACEWAY, FIXTURE AND DEVICE SUPPORTS SHALL BE CAPABLE OF SUSTAINING NOT LESS THAN FOUR (4) TIMES THE ULTIMATE WEIGHT OF THE OBJECT OR OBJECTS. FASTEN SUPPORTS TO THE BUILDING STRUCTURE. CONDUIT IS NOT PERMITTED TO BE SUPPORTED FROM THE CEILING FIXTURE WIRES. Z. FURNISH AND INSTALL SAFETY WIRES AT ALL LIGHT FIXTURES INSTALLED IN A SUSPENDED CEILING. AA. MOUNTING METHODS INDICATED AND REFERRED TO ARE MINIMUM CODE REQUIREMENTS. COMPLY WITH LOCAL CODES FOR ADDITIONAL SEISMIC RESTRAINTS. BB. DEVICES AND RACEWAYS PENETRATING FIRE RATED WALLS AND FLOORS SHALL BE SEALED WITH FIRE RESISTIVE MATERIAL, COMPATIBLE WITH CONSTRUCTION PENETRATED, TO MAINTAIN RATING OF THE WALL. SEALANT SYSTEM SHALL BE A NRTL APPROVED SYSTEM AND INSTALLED PER MANUFACTURER'S INSTRUCTIONS. CC. FURNISH AND INSTALL A PULL CORD IN ALL EMPTY CONDUITS. DD. MAKE ALL CONNECTIONS TO EQUIPMENT PER MANUFACTURER'S REQUIREMENTS. EE. ALL CONDUCTORS IN ELECTRICAL PANELS, CABINETS AND EQUIPMENT SHALL BE NEATLY TRAINED AND LACED. FF. CLEARLY LABEL ALL ACCESSIBLE CONDUIT STUBS WITH SYSTEM NAME AND LOCATION (ROOM NUMBER) WHERE THE OTHER END OF THE CONDUIT TERMINATES. USE INDELIBLE INK. THE LABELS SHALL BE LOCATED ON THE CONDUIT IN A POSITION THAT CAN BE EASILY READ BY THE OWNER IN THE FUTURE. GG. ALL JUNCTION BOX COVERS WITH POWER WIRING SHALL HAVE THE PANEL AND CIRCUIT LABELED ON THE OUTSIDE SURFACE. ALL LABELS FOR EXPOSED JUNCTION BOXES IN "FINISHED AREAS" SHALL BE LABELED UTILIZING CLEAR SELF ADHESIVE LABELS PRODUCED BY A MECHANICAL LABELING MACHINE. LABELS FOR JUNCTION BOX COVERS IN CONCEALED LOCATIONS SHALL CONSIST OF THE INFORMATION BEING NEATLY HANDWRITTEN ON THE OUTSIDE SURFACE OF THE COVER WITH A PERMANENT STYLE MARKER. JUNCTION BOX COVERS FOR FIRE ALARM AND EMERGENCY SYSTEMS SHALL BE PAINTED RED AND LABELED "FA" FOR FIRE ALARM AND "E" FOR EMERGENCY. HH. THE CONTRACTOR SHALL PROVIDE TYPED CIRCUIT PANEL DIRECTORIES FOR ALL PANELS THAT CONTAIN CIRCUITS IMPACTED BY THIS PROJECT. OLD DIRECTORIES SHALL BE RETAINED BEHIND THE NEW. AI.THE CONTRACTOR SHALL PROVIDE SUBMITTALS TO THE GENERAL CONTRACTOR FOR APPROVAL BY ARCHITECT AND ENGINEER PRIOR TO ORDERING EQUIPMENT. SUBMITTALS SHALL CONSIST OF CATALOG CUT DESIGNATING PART NUMBERS TO BE SUPPLIED FOR EACH TYPE OF THE FOLLOWING: ELECTRICAL GEAR, LIGHT FIXTURES, BALLASTS, DRIVERS, LAMPS, DEVICES AND COVERPLATES. MFR MANUFACTURER MLO MAIN LUG ONLY N/A NOT APPLICABLE NC NORMALLY CLOSED NEC NATIONAL ELECTRICAL CODE NEMA NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION NESC NATIONAL ELECTRICAL SAFETY CODE NO NORMALLY OPEN NO. NUMBER NRTL NATIONALLY RECOGNIZED TESTING LABORATORY - AS DEFINED BY OSHA O.H. OPPOSITE HAND - MIRRORED OR ROTATED LAYOUT OC OVER COUNTER TOP BACKSPLASH - COORDINATE INSTALLATION OSHA OCCUPATIONAL SAFETY AND HEALTH ADMINISTRATION PF POWER FACTOR PH PHASE REV REVISION RTU ROOF TOP UNIT SPDT SINGLE POLE, DOUBLE THROW SPST SINGLE POLE, SINGLE THROW SST SOFT START/STOP MOTOR STARTER TTB TELEPHONE TERMINAL BOARD TVSS TRANSIENT VOLTAGE SURGE SUPPRESSOR TYP TYPICAL UON UNLESS OTHERWISE NOTED UPS UNINTERRUPTABLE POWER SUPPLY USB UNIVERSAL SERIAL BUS V VOLTAGE VA VOLT-AMPERE VFD VARIABLE FREQUENCY MOTOR DRIVE WP WEATHERPROOF XFMR TRANSFORMER XFR TRANSFER SWITCH REVISION HISTORY REV DATE DESCRIPTION 0 10 / 1 5 / 2 2 RE L E A S E D F O R C O N S T R U C T I O N 10/15/2022 7 A 8 B 65 7 C D 865 243 1 A B 243 C DWG‐ EFFECTIVE DATE: REV DATE:DESIGN: APPROVED: NAME AND DATE FOR  CURRENT RELEASE ONLY 1 D XL E N G I N E E R I N G ID A H O F A L L S , I D A H O XL ENGINEERING 5257 WILD DUNES LN IDAHO FALLS, ID 83404 ELECTRICAL ENGINEER MARK OWENS (208) 709-3111 MOWENS@XLENGINEERING.NET MECHANICAL ENGINEER JOHN GODAK (208) 339-4907 JGODAK@XLENGINEERING.NET M. Owens M. Owens E01 Sh e l f o l o g y S h o p E x p a n s i o n 15 6 N 2 n d E Re x b u r g , I D 8 3 4 4 0 EN E R G Y C O M P L I A N C E F O R M S 10/15/22 10/15/22 REVISION HISTORY REV DATE DESCRIPTION 0 10 / 1 5 / 2 2 RE L E A S E D F O R C O N S T R U C T I O N 10/15/2022 PC F F F F OWNER FURNISHED LIGHTING FIXTURES ENVISION -LED-LHB-2FT-3M165-WH-F-50K 165W, 120V (TYPICAL OF 8) CIRCUIT ALL HOME RUNS TO EXISTING PANEL WITH AVAILABLE CAPACITY USE SPARE CIRCUIT BREAKERS OR SUPPLY COMPATIBLE CIRCUIT BREAKER(S) IN AVAILABLE SPACE(S) (TYPICAL OF ALL) LITHONIA -DSXW1 LED 20C 1000 40K T3M MVOLT PE DDBXD MULE -MERU LED ACEM DB CW LITHONIA -ECBG LED M6LITHONIA -EU2LM12 FUSED DISCONNECT SWITCH FOR AIR COMPRESSOR QUINCY -QGD 40 40HP, 52A (153.5A MAX), 480V, 3-PHASE (TYPICAL OF 4) CIRCUIT ALL HOME RUNS TO EXISTING PANEL WITH AVAILABLE CAPACITY USE SPARE CIRCUIT BREAKERS OR SUPPLY COMPATIBLE CIRCUIT BREAKER(S) IN AVAILABLE SPACE(S) (TYPICAL OF ALL) 7 A 8 B 65 7 C D 865 243 1 A B 243 C DWG‐ EFFECTIVE DATE: REV DATE:DESIGN: APPROVED: NAME AND DATE FOR  CURRENT RELEASE ONLY 1 D XL E N G I N E E R I N G ID A H O F A L L S , I D A H O XL ENGINEERING 5257 WILD DUNES LN IDAHO FALLS, ID 83404 ELECTRICAL ENGINEER MARK OWENS (208) 709-3111 MOWENS@XLENGINEERING.NET MECHANICAL ENGINEER JOHN GODAK (208) 339-4907 JGODAK@XLENGINEERING.NET M. Owens M. Owens E11 Sh e l f o l o g y S h o p E x p a n s i o n 15 6 N 2 n d E Re x b u r g , I D 8 3 4 4 0 LI G H T I N G & P O W E R P L A N S - FU L F I L L M E N T 10/15/22 10/15/22 NORTH GENERAL NOTES: SHEET NOTES:## ##-## NORTH A. ALL CONDUITS WITH CIRCUIT CONDUCTORS SHALL HAVE A COPPER EQUIPMENT GROUNDING CONDUCTOR SIZED IN ACCORDANCE WITH NEC 250. B. CONTRACTOR TO VERIFY EQUIPMENT ELECTRICAL REQUIREMENTS PRIOR TO INSTALLATION OF RELATED CIRCUIT. CIRCUIT(S) ARE TO BE SIZED AS REQUIRED BY LABEL RATING. C. ELECTRICAL DEVICES NOTED WITH AN 'OC' SUBSCRIPT ARE TO BE MOUNTED ABOVE THE COUNTER BACK SPLASH. THE BOTTOM OF THE DEVICE COVERPLATE SHALL CLEAR THE TOP OF THE BACK SPLASH. COORDINATE THE MOUNTING HEIGHT WITH THE MILLWORK BEING INSTALLED. D. COORDINATE HOMERUN CIRCUIT NUMBERS WITH PANEL SCHEDULES. RE: SHEET E01. E. THIS PLAN DOES NOT REFLECT COMMUNICATION EQUIPMENT. COORDINATE WITH ARCHITECT FOR THE QUANTITY AND LOCATION OF RJ-45 PORTS. THE SERVER SHALL BE LOCATED NEAR THE ELECTRICAL SERVICE ENTRANCE. ALL RJ-45 PORTS SHALL BE CONNECTED TO THE SERVER VIA DEDICATED CAT. 6A ETHERNET CABLE. CONFIRM WITH THE ARCHITECT THAT TELEPHONE AND TV WILL BE INTERNET BASED AND THAT NO COAXIAL OR COPPER TELEPHONE WIRE IS NECESSARY. F. ELECTRICAL CONTRACTOR IS RESPONSIBLE TO FURNISH AND INSTALL TAMPER- RESISTANT (TR) RECEPTACLES IN ALL 15A AND 20A LOCATIONS PER NEC 406.12(1). G. ELECTRICAL CONTRACTOR IS RESPONSIBLE TO FURNISH AND INSTALL ARC- FAULT CIRCUIT-INTERRUPTER (AFCI) PROTECTION PER IN ALL 15A AND 20A LOCATIONS PER NEC 210.12(A). H. ELECTRICAL CONTRACTOR IS RESPONSIBLE TO FURNISH AND INSTALL GROUND- FAULT CIRCUIT-INTERRUPTER (GFCI OR GFI) PROTECTION PER NEC 210.08(A). ALL SINGLE-PHASE RECEPTACLES RATED 125-VOLT, 50 AMPS OR LESS AND THREE- PHASE RECEPACLES RATED 125-VOLT, 100 AMPS OR LESS SHALL BE GFCI PROTECTED. RECEPTACLES THAT ARE INACCESSIBLE ABOVE OR BEHIND APPLIANCES SHALL BE PROTECTED WITH GFCI PROTECTED CIRCUIT BREAKERS AT THE SOURCE PANEL. I. PROVIDE COMBINATION EXIT/EGRESS LIGHTING AS SHOWN. LIGHT BARS SHALL BE AIMED TO ILLUMINATE THE EGRESS PATH WITH ARROW/CHEVRON INDICATING THE DIRECTION TO THE EXIT. J. DAYLIGHT ZONE(S) ARE NOT REQUIRED TO HAVE DAYLIGHT-RESPONSIVE CONTROLS DUE TO AREA CONTAINING LESS THAN 150 TOTAL WATTS OF GENERAL LIGHTING PER IECC C405.2.3. K. INTERIOR LIGHTING IS CONTROLLED BY OCCUPANCY SENSOR OR DAYLIGHT SENSOR CONTROLS (SOME CEILING MOUNTED WIDE-AREA CONTROLS AND OTHERS WALL MOUNTED CONTROLS). A LOWER CASE LETTER "x" INDICATES THE ZONE OF CONTROL WHEN MORE THAN ONE CONTROLLER IS PRESENT IN A COMMON SPACE. L. OCCUPANT SENSOR CONTROL FUNCTION: a. AUTOMATICALLY TURN OFF LIGHTS WITHIN 30 MINUTES OF ALL OCCUPANTS LEAVING THE SPACE. b. BE MANUAL ON OR CONTROLLED TO AUTOMATICALLY TURN THE LIGHTING ON TO NOT MORE THAN 50 PERCENT POWER. c. SHALL INCORPORATE MANUAL CONTROL TO ALLOW OCCUPANTS TO TURN LIGHTS OFF. 1/4" = 1'-0"1E11 - LIGHTING PLAN - LEVEL 1 FULFILLMENT 1/4" = 1'-0"2E21 - POWER PLAN - LEVEL 1 FULFILLMENT REVISION HISTORY REV DATE DESCRIPTION 0 10 / 1 5 / 2 2 RE L E A S E D F O R C O N S T R U C T I O N 10/15/2022