HomeMy WebLinkAboutREDLINED REVIEW RESPONSE - 22-00821 - Shelfology - AdditionDescription : Shelfology - Addition
Address : 156 N 2nd E
Application Type :
Document Filename : 22-00821 Review Comments Responses, 221208 (1).pdf Array
Comment Author Contact Information:
Corrections in the following table need to be applied before a permit can be issued
Review Report
Revisions Required
# 22-00821
Commercial - Addition
Please digitally re-submit all pages of the plan set in response to requested revisions
for our next review cycle, with noted items resolved.
Report Date: 12.14.2022
Approval of plans does not constitute approval of variance from code
Page 1 of 1
Powered by TCPDF (www.tcpdf.org)
Author Name Author Email Author Phone No.:
Alex Owens Alex.Owens@rexburg.org 208-372-2172
Description : Shelfology - Addition
Address : 156 N 2nd E
Application Type :
Document Filename : 2022_03_SHELFOLOGY SHOP EXPANSION_ELEC.pdf Array
Comment Author Contact Information:
Corrections in the following table need to be applied before a permit can be issued
Review Report
Revisions Required
Page Reference Annotation
Type
Author : Department Status Page Review Comments Applicant Response Comments
E00 - ELECTRICAL
SYMBOLS &
ABBREV-
Callout Alex Owens : Electrical Open 1 For verification: Notes Q,R,S are above and beyond NEC
requirements. Please verify this is as the engineer requires
and it will be inspected accordingly.
E00 - ELECTRICAL
SYMBOLS &
ABBREV-
Free Text Alex Owens : Electrical Open 1 All electrical work to comply with 2017 NEC.
# 22-00821
Commercial - Addition
Please digitally re-submit all pages of the plan set in response to requested revisions
for our next review cycle, with noted items resolved.
Report Date: 11.08.2022
Approval of plans does not constitute approval of variance from code
Page 1 of 1
Powered by TCPDF (www.tcpdf.org)
1. We recognize these requirement exceed NEC requirements but are considered good practices. Project
to comply with Notes Q, R, & S as specified.
2. A GENERAL NOTE will be included to require compliance with 2017 NEC.
J
PC
DS
M
F
CONDUIT CONTINUATION
CONDUIT CONCEALED IN WALL OR CEILING
CONDUIT EXISTING
CONDUIT CONCEALED UNDERGROUND
CONDUIT STUB DOWN
STUB THROUGH
CONDUIT STUB UP
JUNCTION BOX (NEW, EXISTING, DEMO)
ELECTRICAL DISTRIBUTION PANELBOARD
EQUIPMENT ENCLOSURE AS NOTED
SIMPLEX RECEPTACLE
DUPLEX RECEPTACLE (NEW, EXISTING, DEMO)
DOUBLE DUPLEX RECEPTACLE
OVER-COUNTER RECEPTACLE
CONTROLLED RECEPTACLE
EMERGENCY EXIT SIGN WITH BATTERY BACKUP: SHADED
QUARTER OF SYMBOL INDICATES LIGHTED 'EXIT' ON THAT
FACE ARROWS INDICATE LIGHTED DIRECTIONAL ARROW
ON THAT FACE. CONNECT TO UNSWITCHED LOCAL
LIGHTING CIRCUIT
EMERGENCY LIGHTING (SURFACE, RECESSED)
CONNECT TO UNSWITCHED LOCAL LIGHTING CIRCUIT
FIXTURES WITH HALF-SHADING ARE EMERGENCY LIGHTS WITH
BATTERY BACKUP. BATTERY BACKUP SHALL PROVIDE
MINIMUM 1100 LUMENS PER FIXTURE FOR 90 MINUTES.
EMERGENCY BATTERY UNIT SHALL BE CONNECTED TO
UNSWITCHED LOCAL LIGHTING CIRCUIT. FIXTURES SHALL BE
SWITCHED WITH ROOM LIGHTS. FIXTURES TO REMAIN ON AT
LOSS OF POWER. FIXTURES WITH 'NL' SHALL BE
EMERGENCY/NIGHT LIGHTS CONNECTED FOR 24 HOUR
OPERATION.
2X4 LIGHT FIXTURE
PENDANT FIXTURE
RECESSED DOWNLIGHT FIXTURE
WALL MOUNTED FIXTURE
LIGHT FIXTURE CALLOUT
E
J
XX
SWITCH
X =2 -DOUBLE POLE-DOUBLE THROW
3 -THREE-WAY
3 -FOUR-WAY
D -DIMMER
HP -HORSEPOWER RATED SWITCH WITH THERMAL
OVERLOADS SIZED AS REQUIRED BY EQUIPMENT
LABEL RATING
K -KEY OPERATED
OV -LOW VOLTAGE MOMENTARY OVERRIDE SWITCH
OS -OCCUPANCY SENSOR PASSIVE INFRARED WALL
SWITCH, WITH A 30 MINUTE TIME DELAY, PROVIDE
WITH STAINLESS STEEL FACEPLATE
P -NEON PILOT LIGHT
L -LIGHTED SWITCH
T -TIMER AS NOTED
W -WIRELESS SWITCH
WP -WEATHERPROOF SHEET NOTE CALLOUT
REVISION DELTA
X
## ##-##
1
SPECIAL ELECTRICAL CONNECTION:
COORDINATE REQUIREMENTS WITH EQUIPMENT BEING SERVED
MOTOR CONNECTION
STARTER OR CONTACTOR:
SIZE AS REQUIRED BY EQUIPMENT MANUFACTURER
COMBINATION MOTOR STARTER/DISCONNECT:
SIZE AS REQUIRED BY EQUIPMENT MANUFACTURER
DISCONNECT SWITCH:
SIZE AS REQUIRED BY EQUIPMENT MANUFACTURER
F=FUSED, BLANK=UNFUSED
SWITCH/DISCONNECT CONFIGURATION DESIGNATION
NUMBER OF POLES
AMPERE RATING OF THE SWITCH
NEMA CLASSIFICATION
THERMOSTAT OR TEMPERATURE SENSOR: SEE
MECHANICAL DRAWINGS FOR LOCATIONS FURNISH AND
INSTALL BACKBOX AND 1"C TO ABOVE ACCESSIBLE CEILING.
COORDINATE INSTALLATION WITH MECHANICAL
SMOKE DAMPER: SEE MECHANICAL DRAWINGS FOR
LOCATIONS VERIFY REQUIREMENTS WITH MECHANICAL
AND FIRE PROTECTION FURNISH AND INSTALL ALL
ELECTRICAL REQUIRED FOR COMPLETE OPERATIONAL
SYSTEM
DUCT TYPE SMOKE DETECTOR: SEE MECHANICAL
DRAWINGS FOR LOCATIONS VERIFY REQUIREMENTS WITH
MECHANICAL AND FIRE PROTECTION FURNISH AND
INSTALL ALL ELECTRICAL REQUIRED FOR COMPLETE
OPERATIONAL SYSTEM
MECHANICAL EQUIPMENT CALLOUT
1 / 30 / 3
XX
XX
T TS
D
SD
J J
A/V
GFCI RECEPTACLE
GFCI OVER-COUNTER RECEPTACLE
GFCI CONTROLLED RECEPTACLE
WEATHERPROOF GFCI RECEPTACLE
ISOLATED GROUND RECEPTACLE
USB CHARGER/DUPLEX RECEPTACLE
OVER-COUNTER USB CHARGER/DUPLEX RECEPTACLE
CONTROLLED USB CHARGER/DUPLEX RECEPTACLE
FLOOR RECEPTCLES:
FLUSH WITH COVER
FLUSH FLOOR BOX
DUPLEX RECEPTACLE, COMM/DATA, A/V
CEILING RECEPTACLE:
FLUSH WITH CEILING
HOMERUN
2X2 LIGHT FIXTURE
STRIP LIGHT FIXTURE
WALL SCONCE
RECESSED STEP FIXTURE
BOLLARD FIXTURE
POST TOP LIGHT FIXTURE, POLE, AND BASE
SWITCH 120/277 VOLT, 20 AMP
CEILING OCCUPANCY SENSOR OS
INTERIOR DAYLIGHT SENSOR
EXTERIOR PHOTOCELL
TELEPHONE TERMINAL BOARD (PLAN VIEW)
SIGNAL OUTLETS SYSTEM NOTES: SYSTEMS ARE
RACEWAY ONLY FOR THIS CONTRACTOR UON. 4" SQUARE
BOX MINIMUM WITH SINGLE GANG MUD RING UON. 1"
MINIMUM CONDUIT SIZE FROM BOX TO NEAREST
ACCESSIBLE CEILING.
TELEPHONE-DATA OUTLET
WEATHERPROOF GFCI RECEPTACLE
OVER-COUNTER WEATHERPROOF GFCI RECEPTACLE
HORIZONTAL FACEPLATE
SMOKE/CO DETECTOR: KIDDE i12010SCO (OR APPROVED EQUIVALENT) SD
7
A
8
B
65
7
C
D
865
243 1
A
B
243
C
DWG‐
EFFECTIVE DATE:
REV
DATE:DESIGN:
APPROVED:
NAME AND DATE FOR
CURRENT RELEASE ONLY
1
D
XL
E
N
G
I
N
E
E
R
I
N
G
ID
A
H
O
F
A
L
L
S
,
I
D
A
H
O
XL ENGINEERING
5257 WILD DUNES LN
IDAHO FALLS, ID 83404
ELECTRICAL ENGINEER
MARK OWENS
(208) 709-3111
MOWENS@XLENGINEERING.NET
MECHANICAL ENGINEER
JOHN GODAK
(208) 339-4907
JGODAK@XLENGINEERING.NET
M. Owens
M. Owens
E00
Sh
e
l
f
o
l
o
g
y
S
h
o
p
E
x
p
a
n
s
i
o
n
15
6
N
2
n
d
E
Re
x
b
u
r
g
,
I
D
8
3
4
4
0
EL
E
C
T
R
I
C
A
L
S
Y
M
B
O
L
S
&
A
B
B
R
E
V
.
10/15/22
10/15/22
ELECTRICAL ABBREVIATIONS
SYMBOLS____________________________________________________________________________GENERAL NOTES:DRAWING INDEX
ELECTRICAL
E00 ELECTRICAL SYMBOLS & ABBREV.
E01 ENERGY COMPLIANCE FORMS
E11 LIGHTING & POWER PLANS - FULFILLMENT
E12 LIGHTING PLAN LEVEL 2
E21 POWER PLAN - LEVEL 1 FULFILLMENT
E22 POWER PLAN LEVEL 2
E23 POWER PLAN ROOF
E31 MECHANICAL POWER PLAN LEVEL 1
E32 MECHANICAL POWER PLAN LEVEL 2
E71 DETAILS
E72 DETAILS
#"C SIZE OF TRADE SIZE CONDUIT. # = 1/2"C,
2"C.
#P NUMBER OF POLES. # = 1P, 2P, ETC.
#W NUMBER OF WIRES, # = 3W, 4W, ETC.
A AMPERE
AC ALTERNATING CURRENT
ADA AMERICANS WITH DISABILITIES ACT
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AHJ AUTHORITY HAVING JURISDICTION
AIC AMPERE INTERRUPTING CAPACITY
AL ALUMINUM
ANN ANNUNCIATOR
AUX AUXILIARY
AWG AMERICAN WIRE GAUGE
C CONDUIT
CB CIRCUIT BREAKER
CD CANDELLA
CLG CEILING
CT CURRENT TRANSFORMER
CU COPPER
DC DIRECT CURRENT
DPDT DOUBLE POLE, DOUBLE THROW
DPST DOUBLE POLE, SINGLE THROW
EMT ELECTRICAL METALLIC TUBING
EP EXPLOSION PROOF
EWH ELECTRIC WATER HEATER
FFUSE
FACP FIRE ALARM CONTROL PANEL
GFCI GROUND FAULT CIRCUIT INTERRUPTER
GFI GROUND FAULT INTERRUPTER
GND GROUND
HOA HAND-OFF-AUTO
HP HORSE POWER
HVAC HEATING VENTILATION AND AIR
CONDITIONING
I/O INPUT / OUTPUT
IG ISOLATED GROUND
INC INCANDESCENT
J-BOX JUNCTION BOX
KCMIL THOUSAND CIRCULAR MIL
KO KNOCK OUT
KV KILOVOLT
KVA KILOVOLT AMPERE
KW KILOWATT
KWH KILOWATT HOUR
LV LOW VOLTAGE
MCC MOTOR CONTROL CENTER
MDSB MAIN DISTRIBUTION SWITCHBOARD
A. ALL WORK SHALL BE IN ACCORDANCE WITH THE LATEST EDITION OF THE LOCALLY ADOPTED
ELECTRICAL CODE, ALL LOCAL CODES, AND TO THE FULL ACCEPTANCE OF THE AUTHORITY HAVING
JURISDICTION. WHENEVER THE REQUIREMENTS OF THE ELECTRICAL SPECIFICATIONS OR DRAWINGS
EXCEED THOSE OF THE APPLICABLE CODES OR STANDARDS, THE REQUIREMENTS OF THE
SPECIFICATIONS AND DRAWINGS SHALL GOVERN.
B. BIDDERS SHALL VIEW THE SITE AND SHALL INCLUDE ALL COSTS INCURRED BY EXISTING CONDITIONS
IN THE BID PROPOSAL. THE CONTRACTOR SHALL FAMILIARIZE THEMSELVES WTIH ALL RELEVANT BID
DOCUMENTS, BID FORMS AND SPECIFICATIONS. ANY INCREASED COST INCURRED DUE TO FAILURE TO
BECOME FAMILIAR WITH THESE DOCUMENTS SHALL BE BORNE BY THE CONTRACTOR. WORK SHALL
INCLUDE ALL LABOR, EQUIPMENT, APPLIANCES, MATERIALS, TRANSPORTATION, FACILITIES AND
SERVICES NECESSARY FOR AND/OR REASONABLY INCIDENTAL TO THE COMPLETION OF ALL
ELECTRICAL WORK IN STRICT COMPLIANCE WITH THE DRAWINGS AND OTHER CONTRACT
DOCUMENTS. WORK SHALL INCLUDE, BUT NOT BE NECESSARILY LIMITED TO, THE WORK SPECIFIED
AND INDICATED ON DRAWINGS.
C. OBTAIN ALL PERMITS, COORDINATE, FURNISH, INSTALL, CONNECT AND TEST ALL ELECTRICAL
EQUIPMENT REQUIRED FOR ALL THE SYSTEMS INSTALLED UNDER THIS CONTRACT TO INSURE
COMPLETE AND FULLY OPERATIONAL SYSTEMS.
D. CONTRACTOR SHALL MAINTAIN A COMPLETE SET OF AS-BUILT DRAWINGS. AS-BUILT SET OF
DRAWINGS SHALL BE UPDATED DAILY AND SHALL DOCUMENT THE ACTUAL INSTALLED CONDITION OF
THE ENTIRE ELECTRICAL INSTALLATION. AS-BUILT SET OF DRAWINGS SHALL BE AVAILABLE AT ALL
TIMES ON THE SITE FOR INSPECTION BY CODE OFFICIALS, OWNER, ARCHITECT, AND ENGINEER.
E. PROPOSED MODIFICATIONS OF ENGINEERED ELECTRICAL DRAWINGS SHALL BE APPROVED BY
ENGINEER OF RECORD PRIOR TO PROCEEDING WITH WORK. PROPOSED CHANGES SHALL COMPLY
WITH ALL APPLICABLE CODES/JURISDICTION REQUIREMENTS. COST OF ANY ENGINEERING/REVIEW
REQUIRED BY PROPOSED CHANGES SHALL BE BORNE BY ENTITY PROPOSING CHANGE.
F. DESIGN IS BASED ON BEST AVAILABLE INFORMATION. CONTRACTOR SHALL FIELD VERIFY EXISTING
CONDITIONS TO DETERMINE STATUS OF ACTUAL CONDITIONS AS THEY RELATE TO THE SCOPE OF
WORK AS SHOWN ON THESE PLANS.
G. COORDINATE ALL ELECTRICAL WORK WITH ALL OTHER TRADES.
H. COORDINATE EXACT LOCATION AND MOUNTING HEIGHTS OF ALL ELECTRICAL EQUIPMENT AND
DEVICES WITH THE ARCHITECTURAL ELEVATIONS AND DETAILS PRIOR TO ROUGH-IN.
I. CONTRACTOR SHALL COORDINATE WITH WALL TYPES AND FURNISH AND INSTALL EXTENSION RINGS
AS REQUIRED. (I.E. WALLS WITH TWO LAYERS OF GYP BOARD).
J. ALL MATERIALS AND EQUIPMENT FURNISHED TO THE PROJECT SHALL BE NEW AND SHALL BEAR THE
LISTING LABEL OF A NATIONALLY RECOGNIZED TESTING LABORATORY (NRTL), WHERE APPLICABLE.
K. ALL ELECTRICAL BOXES, FITTINGS AND CABINETS SHALL BE OF STEEL CONSTRUCTION, GALVANIZED
OR POWDER COATED, NEMA 1 TYPE, UON.
L. ALL DEVICES (SWITCHES/RECEPTACLES/TELECOMMUNICATIONS) SHALL BE WHITE AND
COVERPLATES SHALL BE BRUSHED STAINLESS STEEL, UON.
M. ALL CIRCUIT BREAKERS SUPPLYING MOTOR LOADS SHALL BE HACR RATED.
N. ALL ELECTRICAL DEVICES AND TERMINALS SHALL BE RATED 75°C MINIMUM.
O. ALL CONDUCTORS SHALL BE STRANDED COPPER, 600 VOLT RATED. INSULATION TYPE SHALL BE
THHN/THWN, FULLY COLOR CODED WITH GAUGE, TYPE AND MANUFACTURER MARKED EVERY 24"
ALONG. CONDUCTOR COLOR CODE SHALL BE AS FOLLOWS:
208Y/120 VOLT SYSTEM 480Y/277 VOLT SYSTEM
PHASE A -BLACK PHASE A -BROWN
PHASE B -RED PHASE B -ORANGE
PHASE C -BLUE PHASE C -YELLOW
NEUTRAL -WHITE NEUTRAL -GRAY
GROUND -GREEN GROUND -GREEN
P. MINIMUM SIZE WIRE FOR POWER AND LIGHTING CIRCUITS SHALL BE #12 AWG, UON. CONDUCTOR SIZE
SHALL BE CONTINUOUS THROUGHOUT THE ENTIRE LENGTH OF THE CIRCUIT.
Q. ALL CIRCUITS SHALL HAVE AN INDEPENDENT NEUTRAL CONDUCTOR. NO EDISON STYLE SHARED
NEUTRAL CONDUCTORS ARE ALLOWED.
R. ALL CONDUITS SHALL CONTAIN A GROUND CONDUCTOR SIZED PER NEC.
S. ALL POWER AND LIGHTING CONDUCTORS SHALL BE ROUTED IN 3/4" CONDUIT MINIMUM. NO MC TYPE
CABLE IS ALLOWED WITH THE EXCEPTION OF CEILING WHIPS 6' OR LESS.
T. CONDUIT AND WIRE FOR FEEDER OR BRANCH CIRCUITS SHALL NOT BE RUN ON OR ABOVE THE ROOF.
ELECTRICAL SERVICES FOR ROOF MOUNTED EQUIPMENT ARE TO BE RUN IN A STRAIGHT LINE FROM
THE ROOF PENETRATION TO THE ELECTRICAL CONNECTION FOR THE UNIT SERVED.
U. ROUTE ALL CONDUIT HOME RUNS TO PANELS OVERHEAD AND ABOVE ACCESSIBLE CEILINGS WHERE
AVAILABLE.
V. INSTALL CONDUIT A MINIMUM OF 4" BELOW BOTTOM OF CONCRETE SLAB WHERE RUNNING UNDER
FLOOR. ALL ELBOWS SHALL BE RIGID METAL CONDUIT OR INTERMEDIATE METAL CONDUIT.
W. ALL EQUIPMENT, SWITCHING DEVICES AND PANELS SHALL BE MOUNTED SO AS TO BE ACCESSIBLE
AND SHALL BE MOUNTED PLUMB AND SQUARE WITH WALLS.
X. BOXES MOUNTED IN A COMMON WALL SHALL BE OFFSET A MINIMUM OF 12" OR MOUNTED IN
ADJACENT STUD SPACES. BOXES MOUNTED BACK-TO-BACK ARE NOT ALLOWED.
Y. ALL ELECTRICAL EQUIPMENT, RACEWAY, FIXTURE AND DEVICE SUPPORTS SHALL BE CAPABLE OF
SUSTAINING NOT LESS THAN FOUR (4) TIMES THE ULTIMATE WEIGHT OF THE OBJECT OR OBJECTS.
FASTEN SUPPORTS TO THE BUILDING STRUCTURE. CONDUIT IS NOT PERMITTED TO BE SUPPORTED
FROM THE CEILING FIXTURE WIRES.
Z. FURNISH AND INSTALL SAFETY WIRES AT ALL LIGHT FIXTURES INSTALLED IN A SUSPENDED CEILING.
AA. MOUNTING METHODS INDICATED AND REFERRED TO ARE MINIMUM CODE REQUIREMENTS. COMPLY
WITH LOCAL CODES FOR ADDITIONAL SEISMIC RESTRAINTS.
BB. DEVICES AND RACEWAYS PENETRATING FIRE RATED WALLS AND FLOORS SHALL BE SEALED WITH
FIRE RESISTIVE MATERIAL, COMPATIBLE WITH CONSTRUCTION PENETRATED, TO MAINTAIN RATING OF
THE WALL. SEALANT SYSTEM SHALL BE A NRTL APPROVED SYSTEM AND INSTALLED PER
MANUFACTURER'S INSTRUCTIONS.
CC. FURNISH AND INSTALL A PULL CORD IN ALL EMPTY CONDUITS.
DD. MAKE ALL CONNECTIONS TO EQUIPMENT PER MANUFACTURER'S REQUIREMENTS.
EE. ALL CONDUCTORS IN ELECTRICAL PANELS, CABINETS AND EQUIPMENT SHALL BE NEATLY TRAINED
AND LACED.
FF. CLEARLY LABEL ALL ACCESSIBLE CONDUIT STUBS WITH SYSTEM NAME AND LOCATION (ROOM
NUMBER) WHERE THE OTHER END OF THE CONDUIT TERMINATES. USE INDELIBLE INK. THE LABELS
SHALL BE LOCATED ON THE CONDUIT IN A POSITION THAT CAN BE EASILY READ BY THE OWNER IN THE
FUTURE.
GG. ALL JUNCTION BOX COVERS WITH POWER WIRING SHALL HAVE THE PANEL AND CIRCUIT LABELED ON
THE OUTSIDE SURFACE. ALL LABELS FOR EXPOSED JUNCTION BOXES IN "FINISHED AREAS" SHALL BE
LABELED UTILIZING CLEAR SELF ADHESIVE LABELS PRODUCED BY A MECHANICAL LABELING MACHINE.
LABELS FOR JUNCTION BOX COVERS IN CONCEALED LOCATIONS SHALL CONSIST OF THE
INFORMATION BEING NEATLY HANDWRITTEN ON THE OUTSIDE SURFACE OF THE COVER WITH A
PERMANENT STYLE MARKER. JUNCTION BOX COVERS FOR FIRE ALARM AND EMERGENCY SYSTEMS
SHALL BE PAINTED RED AND LABELED "FA" FOR FIRE ALARM AND "E" FOR EMERGENCY.
HH. THE CONTRACTOR SHALL PROVIDE TYPED CIRCUIT PANEL DIRECTORIES FOR ALL PANELS THAT
CONTAIN CIRCUITS IMPACTED BY THIS PROJECT. OLD DIRECTORIES SHALL BE RETAINED BEHIND THE
NEW.
AI.THE CONTRACTOR SHALL PROVIDE SUBMITTALS TO THE GENERAL CONTRACTOR FOR APPROVAL BY
ARCHITECT AND ENGINEER PRIOR TO ORDERING EQUIPMENT. SUBMITTALS SHALL CONSIST OF
CATALOG CUT DESIGNATING PART NUMBERS TO BE SUPPLIED FOR EACH TYPE OF THE FOLLOWING:
ELECTRICAL GEAR, LIGHT FIXTURES, BALLASTS, DRIVERS, LAMPS, DEVICES AND COVERPLATES.
MFR MANUFACTURER
MLO MAIN LUG ONLY
N/A NOT APPLICABLE
NC NORMALLY CLOSED
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECTRICAL MANUFACTURERS
ASSOCIATION
NESC NATIONAL ELECTRICAL SAFETY CODE
NO NORMALLY OPEN
NO. NUMBER
NRTL NATIONALLY RECOGNIZED TESTING
LABORATORY - AS DEFINED BY OSHA
O.H. OPPOSITE HAND - MIRRORED OR ROTATED
LAYOUT
OC OVER COUNTER TOP BACKSPLASH -
COORDINATE INSTALLATION
OSHA OCCUPATIONAL SAFETY AND HEALTH
ADMINISTRATION
PF POWER FACTOR
PH PHASE
REV REVISION
RTU ROOF TOP UNIT
SPDT SINGLE POLE, DOUBLE THROW
SPST SINGLE POLE, SINGLE THROW
SST SOFT START/STOP MOTOR STARTER
TTB TELEPHONE TERMINAL BOARD
TVSS TRANSIENT VOLTAGE SURGE SUPPRESSOR
TYP TYPICAL
UON UNLESS OTHERWISE NOTED
UPS UNINTERRUPTABLE POWER SUPPLY
USB UNIVERSAL SERIAL BUS
V VOLTAGE
VA VOLT-AMPERE
VFD VARIABLE FREQUENCY MOTOR DRIVE
WP WEATHERPROOF
XFMR TRANSFORMER
XFR TRANSFER SWITCH
REVISION HISTORY
REV
DATE
DESCRIPTION
0
10
/
1
5
/
2
2
RE
L
E
A
S
E
D
F
O
R
C
O
N
S
T
R
U
C
T
I
O
N
10/15/2022
7
A
8
B
65
7
C
D
865
243 1
A
B
243
C
DWG‐
EFFECTIVE DATE:
REV
DATE:DESIGN:
APPROVED:
NAME AND DATE FOR
CURRENT RELEASE ONLY
1
D
XL
E
N
G
I
N
E
E
R
I
N
G
ID
A
H
O
F
A
L
L
S
,
I
D
A
H
O
XL ENGINEERING
5257 WILD DUNES LN
IDAHO FALLS, ID 83404
ELECTRICAL ENGINEER
MARK OWENS
(208) 709-3111
MOWENS@XLENGINEERING.NET
MECHANICAL ENGINEER
JOHN GODAK
(208) 339-4907
JGODAK@XLENGINEERING.NET
M. Owens
M. Owens
E01
Sh
e
l
f
o
l
o
g
y
S
h
o
p
E
x
p
a
n
s
i
o
n
15
6
N
2
n
d
E
Re
x
b
u
r
g
,
I
D
8
3
4
4
0
EN
E
R
G
Y
C
O
M
P
L
I
A
N
C
E
F
O
R
M
S
10/15/22
10/15/22
REVISION HISTORY
REV
DATE
DESCRIPTION
0
10
/
1
5
/
2
2
RE
L
E
A
S
E
D
F
O
R
C
O
N
S
T
R
U
C
T
I
O
N
10/15/2022
PC
F
F
F
F
OWNER FURNISHED LIGHTING FIXTURES
ENVISION -LED-LHB-2FT-3M165-WH-F-50K
165W, 120V (TYPICAL OF 8)
CIRCUIT ALL HOME RUNS TO EXISTING PANEL WITH AVAILABLE CAPACITY
USE SPARE CIRCUIT BREAKERS OR SUPPLY COMPATIBLE CIRCUIT BREAKER(S) IN AVAILABLE SPACE(S)
(TYPICAL OF ALL)
LITHONIA -DSXW1 LED 20C 1000 40K T3M MVOLT PE DDBXD
MULE -MERU LED ACEM DB CW
LITHONIA -ECBG LED M6LITHONIA -EU2LM12
FUSED DISCONNECT SWITCH FOR AIR COMPRESSOR
QUINCY -QGD 40
40HP, 52A (153.5A MAX), 480V, 3-PHASE
(TYPICAL OF 4)
CIRCUIT ALL HOME RUNS TO EXISTING PANEL WITH AVAILABLE CAPACITY
USE SPARE CIRCUIT BREAKERS OR SUPPLY COMPATIBLE CIRCUIT BREAKER(S) IN AVAILABLE SPACE(S)
(TYPICAL OF ALL)
7
A
8
B
65
7
C
D
865
243 1
A
B
243
C
DWG‐
EFFECTIVE DATE:
REV
DATE:DESIGN:
APPROVED:
NAME AND DATE FOR
CURRENT RELEASE ONLY
1
D
XL
E
N
G
I
N
E
E
R
I
N
G
ID
A
H
O
F
A
L
L
S
,
I
D
A
H
O
XL ENGINEERING
5257 WILD DUNES LN
IDAHO FALLS, ID 83404
ELECTRICAL ENGINEER
MARK OWENS
(208) 709-3111
MOWENS@XLENGINEERING.NET
MECHANICAL ENGINEER
JOHN GODAK
(208) 339-4907
JGODAK@XLENGINEERING.NET
M. Owens
M. Owens
E11
Sh
e
l
f
o
l
o
g
y
S
h
o
p
E
x
p
a
n
s
i
o
n
15
6
N
2
n
d
E
Re
x
b
u
r
g
,
I
D
8
3
4
4
0
LI
G
H
T
I
N
G
&
P
O
W
E
R
P
L
A
N
S
-
FU
L
F
I
L
L
M
E
N
T
10/15/22
10/15/22
NORTH
GENERAL NOTES:
SHEET NOTES:## ##-##
NORTH
A. ALL CONDUITS WITH CIRCUIT CONDUCTORS SHALL HAVE A COPPER EQUIPMENT
GROUNDING CONDUCTOR SIZED IN ACCORDANCE WITH NEC 250.
B. CONTRACTOR TO VERIFY EQUIPMENT ELECTRICAL REQUIREMENTS PRIOR TO
INSTALLATION OF RELATED CIRCUIT. CIRCUIT(S) ARE TO BE SIZED AS REQUIRED
BY LABEL RATING.
C. ELECTRICAL DEVICES NOTED WITH AN 'OC' SUBSCRIPT ARE TO BE MOUNTED
ABOVE THE COUNTER BACK SPLASH. THE BOTTOM OF THE DEVICE COVERPLATE
SHALL CLEAR THE TOP OF THE BACK SPLASH. COORDINATE THE MOUNTING
HEIGHT WITH THE MILLWORK BEING INSTALLED.
D. COORDINATE HOMERUN CIRCUIT NUMBERS WITH PANEL SCHEDULES. RE: SHEET
E01.
E. THIS PLAN DOES NOT REFLECT COMMUNICATION EQUIPMENT. COORDINATE
WITH ARCHITECT FOR THE QUANTITY AND LOCATION OF RJ-45 PORTS. THE
SERVER SHALL BE LOCATED NEAR THE ELECTRICAL SERVICE ENTRANCE. ALL
RJ-45 PORTS SHALL BE CONNECTED TO THE SERVER VIA DEDICATED CAT. 6A
ETHERNET CABLE. CONFIRM WITH THE ARCHITECT THAT TELEPHONE AND TV
WILL BE INTERNET BASED AND THAT NO COAXIAL OR COPPER TELEPHONE WIRE
IS NECESSARY.
F. ELECTRICAL CONTRACTOR IS RESPONSIBLE TO FURNISH AND INSTALL TAMPER-
RESISTANT (TR) RECEPTACLES IN ALL 15A AND 20A LOCATIONS PER NEC
406.12(1).
G. ELECTRICAL CONTRACTOR IS RESPONSIBLE TO FURNISH AND INSTALL ARC-
FAULT CIRCUIT-INTERRUPTER (AFCI) PROTECTION PER IN ALL 15A AND 20A
LOCATIONS PER NEC 210.12(A).
H. ELECTRICAL CONTRACTOR IS RESPONSIBLE TO FURNISH AND INSTALL GROUND-
FAULT CIRCUIT-INTERRUPTER (GFCI OR GFI) PROTECTION PER NEC 210.08(A). ALL
SINGLE-PHASE RECEPTACLES RATED 125-VOLT, 50 AMPS OR LESS AND THREE-
PHASE RECEPACLES RATED 125-VOLT, 100 AMPS OR LESS SHALL BE GFCI
PROTECTED. RECEPTACLES THAT ARE INACCESSIBLE ABOVE OR BEHIND
APPLIANCES SHALL BE PROTECTED WITH GFCI PROTECTED CIRCUIT BREAKERS
AT THE SOURCE PANEL.
I. PROVIDE COMBINATION EXIT/EGRESS LIGHTING AS SHOWN. LIGHT BARS SHALL
BE AIMED TO ILLUMINATE THE EGRESS PATH WITH ARROW/CHEVRON INDICATING
THE DIRECTION TO THE EXIT.
J. DAYLIGHT ZONE(S) ARE NOT REQUIRED TO HAVE DAYLIGHT-RESPONSIVE
CONTROLS DUE TO AREA CONTAINING LESS THAN 150 TOTAL WATTS OF
GENERAL LIGHTING PER IECC C405.2.3.
K. INTERIOR LIGHTING IS CONTROLLED BY OCCUPANCY SENSOR OR DAYLIGHT
SENSOR CONTROLS (SOME CEILING MOUNTED WIDE-AREA CONTROLS AND
OTHERS WALL MOUNTED CONTROLS). A LOWER CASE LETTER "x" INDICATES THE
ZONE OF CONTROL WHEN MORE THAN ONE CONTROLLER IS PRESENT IN A
COMMON SPACE.
L. OCCUPANT SENSOR CONTROL FUNCTION:
a. AUTOMATICALLY TURN OFF LIGHTS WITHIN 30 MINUTES OF ALL OCCUPANTS
LEAVING THE SPACE.
b. BE MANUAL ON OR CONTROLLED TO AUTOMATICALLY TURN THE LIGHTING ON
TO NOT MORE THAN 50 PERCENT POWER.
c. SHALL INCORPORATE MANUAL CONTROL TO ALLOW OCCUPANTS TO TURN
LIGHTS OFF.
1/4" = 1'-0"1E11 - LIGHTING PLAN - LEVEL 1 FULFILLMENT
1/4" = 1'-0"2E21 - POWER PLAN - LEVEL 1 FULFILLMENT
REVISION HISTORY
REV
DATE
DESCRIPTION
0
10
/
1
5
/
2
2
RE
L
E
A
S
E
D
F
O
R
C
O
N
S
T
R
U
C
T
I
O
N
10/15/2022