IDAHO STATE FIRE MARSHAL'S OFFICE
FIRE SPRINKLER PLAN REVIEW
ACCEPTED
05/29/2024
8 6 24 0 8 16 24
S101
S102
S103
S104
S105
S106
S107
S108S109
S110
019
009 008 236
S201
S202
S203S204
S205
S206S207
S208
S209
004 055 056
016
8 6 24 0 8 16 24
Design Area Density:
Calculations using Method
Occupancy Classification:
Design Area System
Additional Outside Hose:
Design Area Size:
Notes:
1 Wet
Fab Floor
Demand Hazen-Williams
OGII
0.2
250
1008
QR Modified
This system as shown on company print no dated
for at
contract no is designed to discharge at a rate of
a maximum area of when supplied with water at a rate of
Occupancy classification:
Commodity classification:
Maximum storage height:
Storage arrangement:
Number of heads flowing:
System Type:
Maximum velocity:
Flow from In-Rack sprinklers:
Flow from Overhead sprinklers:
Flow from Inside Hoses:
Flow from Outside Hoses:
Other fixed flows:
Total flow in system piping:
Additional flow at/beyond source:
Total of all flows:
Calculation results for Design Area
gpm/ft² (L/min/m²) of floor area over
-
Surplus Pressure at Source:
Pressure Required at Source:
Pressure Available at Source:
at at the base of the riser.
Hose stream allowance of is included in the above.
1 Fab Floor
Shelfology 5.1.2024
Shelfology 156 N 2nd E, Rexburg, ID 83440
24-201 0.2
1008 ft²307.9 gpm 67.9 psi
OGII 10
Wet
22.31 ft/s
0 gpm
307.9 gpm
0 gpm
0 gpm
0 gpm
307.9 gpm
250 gpm
557.9 gpm
67.9 psi
77.6 psi
9.7 psi
Design Area Density:
Calculations using Method
Occupancy Classification:
Design Area System
Additional Outside Hose:
Design Area Size:
Notes:
2 Wet
Fab Floor
Demand Hazen-Williams
OGII
0.2
250
963
QR Modified
This system as shown on company print no dated
for at
contract no is designed to discharge at a rate of
a maximum area of when supplied with water at a rate of
Occupancy classification:
Commodity classification:
Maximum storage height:
Storage arrangement:
Number of heads flowing:
System Type:
Maximum velocity:
Flow from In-Rack sprinklers:
Flow from Overhead sprinklers:
Flow from Inside Hoses:
Flow from Outside Hoses:
Other fixed flows:
Total flow in system piping:
Additional flow at/beyond source:
Total of all flows:
Calculation results for Design Area
gpm/ft² (L/min/m²) of floor area over
-
Surplus Pressure at Source:
Pressure Required at Source:
Pressure Available at Source:
at at the base of the riser.
Hose stream allowance of is included in the above.
2 Fab Floor
Shelfology 5.1.2024
Shelfology 156 N 2nd E, Rexburg, ID 83440
24-201 0.2
963 ft²246.7 gpm 40.1 psi
OGII 9
Wet
16.17 ft/s
0 gpm
246.7 gpm
0 gpm
0 gpm
0 gpm
246.7 gpm
250 gpm
496.7 gpm
40.1 psi
78.1 psi
38 psi
IDAHO STATE FIRE MARSHAL'S OFFICE
FIRE SPRINKLER PLAN REVIEW
ACCEPTED
05/29/2024