HomeMy WebLinkAboutPLAN REVIEW NOTES 2 - 22-00839 - Teton Lakes Golf Course - Fiber Hut - Bldg 1 MO DULAR / C OMME RC IAL PL AN RE VIE W NOT E S T h ese n o tes s hall b e attach ed to th e ID O PL s tamp ed ap p roved p lan s an d documents. M OD2 21 1 -00018 The mo dular building unit when assembled in the facto ry meets the code requirements for the mo dular building unit o nly, as the p lans were submitted to the Idaho Divisio n o f Occupatio nal and Professio nal Licenses (IDOP L). S ectio n 1 1 0.5 , 20 1 8 IB C. Inspection requests. It shall be the duty of the holder o f the building p ermit o r their duly authorized agent to no tify the building o ffici al when work is ready for inspection. It shall be the duty o f the permit ho lder to provide access to and means fo r insp ectio ns o f such wo rk that are required by this code. (see sectio n 1 1 0.3 201 8 IBC. for required inspectio ns) The Notice to Local Enforcement Agency (N.L.E.A.) fo rm o utlines possible code required/permitted wo rk that requires site comp letio n. The N.L.E.A. fo rm is a comp o nent o f the Idaho app roved mo dular building plan submittal. The N.L.E.A. fo rm sho uld be reviewed by the local jurisdiction fo r info rmatio n regarding the installatio n of the mo dular building o n-site. 2 0 1 8 IB C - Amended co nstruction do cuments. Wo rk sh all be insta lled in acco rdan ce with th e approved con struction docum ents, and an y chan ges m ade during constructio n that are no t in co mplian ce with the approved con struction docum ents sh all be resubmitted for appro val as an am ended set of construction documents. Resubmittal may be required fo r any reaso n at the inspector’s discretion. S ectio n 1 1 0.1 , 20 1 8 IB C. Appro val as a result o f an insp ectio n shall not be construed to be an ap p ro val o f a violation of the p rovisions o f the code o r o f o ther ordinances of the jurisdiction. Inspectio ns p resuming to give autho rity to violate o r cancel the p rovisio ns o f this code o r o f other o rdinances o f the jurisdictio n shall not be valid. The lo cal jurisdiction may reques t an IDOP L ap p roved set of the modular p lans for verific ation o f any jurisdictio nal codes and regulation requirements. It is up to the lo cal jurisdictio n to ensure co mp lete co de co mp liance and app roval fo r lo cal site installatio ns, to include but not limited to ; all site wo rk, exact location fro m lo t lines and sep aration distances fro m o ther structures, structural stability and any fire assembly requirements that may be required by the 201 8 IB C. for the co mplete project. "P lanning and Zoning" is no t part o f the modular building plan review. Co de required insp ections for the constructio n o f the modular building in the facto ry shall be perfo rmed by the applicable insp ector(s) and in accordance with the IDOP L app roved plan submittal and all Idaho ado p ted codes. It is the responsibility of the owner the design p rofessionals and the co ntracto r to ensure co mplete code co mpliance fo r this pro ject. Any lack of informatio n, questio ns o r deviations shall be bro ught to the attention of the registered design pro fessio nal o f record fo r appro val. F inal ap p ro val o f all code co mpliance fo r this project will be based upo n the 201 8 IBC through field inspections, verifications and appro val by the field insp ecto rs. These plans have been reviewed for code compliance by the Division of Occupational and Professional Licenses. This review shall not be construed to be an approval of any violation, or variance, from Idaho's adopted codes, standards, laws or rules applicable to this project. Corrections will be required for any code violations found during the inspection process. This is not a building permit Plan Approval #: Date: MOD2211-00018 11/30/22 Date Mfg NOTIFICATION TO LOCAL ENFORCEMENT AGENCY The Factory-Built unit identified below requires completion work at the site as specified. Owner's name Installation address City County State ZIP+4 Mfgr's serial no. Dept insignia no. Type of construction Occupancy ETA at site DESCRIBE ITEMS REQUIRING COMPLETION WORK AT THE SITE To: Inspector's name (print/type) Office location Phone: (8 am to 5 pm) Manufacturer's signatureDate Installation site is in: City County Phone number Manufacturer's name (print/type) INSERT NAME AND ADDRESS IN SHADED AREA LOCAL BUILDING DEPARTMENT 9/26/22 Thermo Bond Buildings City of Rexburg TBB1574 293 East 7th North U S2 12/2022 Rexburg ID 83440 Madison 208-229-6100 4 Shauna Eaton 35 N 1st East Rexburg, ID 83440 208-372-2166 1. Modular building installation to concrete foundation 3. Utility service connection 120/240V, 200A, 1PH Jim Brinkmann 9/26/22 RESET These plans have been reviewed for code compliance by the Division of Occupational and Professional Licenses. This review shall not be construed to be an approval of any violation, or variance, from Idaho's adopted codes, standards, laws or rules applicable to this project. Corrections will be required for any code violations found during the inspection process. This is not a building permit Plan Approval #: Date: MOD2211-00018 11/30/22 BUILDING EXTERIOR OZARK GREY OTHER PROJECT CITY OF REXBURG JOB NO. 2112-534B-1 SITE NAME NORTH WELL REXBURG, ID SIZE 1 2'W. OD X 20'L. OD X 9'H. ID REVISION NUMBER:LAST REVISED: 19/26/22 FOR SIGNATURE OR STAMPED APPROVAL: NO N E CI T Y OF REXBURG TH I S DO C U M E N T AN D AL L IN F O R M A T I O N CO N T A I N E D HE R E I N AR E TH E PROPRIETARY DA T A AN D TR A D E SE C R E T S OF TH E R M O B O N D . TH I S DO C U M E N T AN D TH E IN F O R M A T I O N CO N T A I N E D HE R E I N MA Y NO T BE REPRODUCED, US E D OR DI S C L O S E D IN AN Y MANNER OR TO AN Y EX T E N T (E X C E P T BY OR TO TH E R M O B O N D ) WIT H O U T TH E PR I O R WR I T T E N AUTHORIZATION OF TH E R M O B O N D . DR A W N : 9/ 7 / 2 2 RE V I S E D : 9/ 2 6 / 2 2 DR A W N BY : NR S PR O J E C T NU M B E R : 21 1 2 - 5 3 4 B - 1 SC A L E ~ 11 X 1 7 : SH E E T : PR O J E C T NA M E : DR A W I N G NU M B E R : TB B 1 5 7 4 REXBURG, ID 12 ' W . OD x 20 ' L . OD x 9' H . ID SH E L T E R A1 . 0 Dr a w i n g In d e x DRAWING TITLE DRAWING INDEX_______________________________ REVISIONS & NOTES SHEET_____________________ BILL OF MATERIALS____________________________ INTERIOR LAYOUTS____________________________ FLOOR & CEILING LAYOUT_____________________ ELEVATION VIEWS_____________________________ DOOR DETAIL__________________________________ ELECTRICAL PANEL____________________________ CORNER CONSTRUCTION DETAILS______________ ROOF CONSTRUCTION DETAILS_________________ FASTENER SCHEDULE__________________________ BUILDING SKID ASSEMBLY_____________________ DRAWING NUMBER A1.0 A2.0 B1.0 C1.0 C1.1 C2.0 C3.0 E1.0 D1.0 D1.1 D2.0 S1.0 USAGE_________________ CONSTRUCTION TYPE___ OCCUPANCY GROUP____ STORIES________________ ULTIMATE WIND SPEED_____ FLOOR LOAD___________ ROOF LOAD____________ FLOOR AREA___________ BUILDING HEIGHT______ SEISMIC DESIGN________ WIND EXPOSURE_______ ________UNMANNED SHELTER _______________________VB ________________________U ___________________________1 ___________115 VULT _______________________200 PSF __________________________70 PSF ___________________240 SQ.FT. ______________________11'-2" ______________________CAT D ________________________CAT C CODES: 2018 INTERNATIONAL BUILDING CODE (IBC) 2018 INTERNATIONAL MECHANICAL CODE (IMC) 2018 INTERNATIONAL ENERGY CONSERVATION CODE (IECC) 2018 NATIONAL ELECTRICAL CODE (NEC) NOTES: AGENCY LABEL AND DATA PLATE TO BE PLACED ON A PLATE LOCATED ON THE INSIDE LEFT OR RIGHT OF THE DOOR. STATE INSIGNIA TO BE LOCATED ON OUTSIDE OF DOOR ABOVE PASSAGE. SPECIAL CONDITIONS/LIMITATIONS: · IF A BATTERY STORAGE SYSTEM IS INSTALLED IN THIS BUILDING, THE SYSTEM SHALL BE INSTALLED PER 2018 IFC SECTION 1206.2 · THIS BUILDING WILL NOT BE LOCATED IN A FLOOD PLAIN. · ROOF SYSTEM DESIGNED PER ICC-ESR 1463 TABLE 5 SYSTEM NO. 1 · SURE-WELD WHITE TPO MEMBRANE SOLAR REFLECTANCE AFTER 3 YEARS IS 0.70, THERMAL EMITTANCE AFTER 3 YEARS IS 0.86 AND SOLAR REFLECTANCE INDEX AFTER 3 YEARS IS 85. 9/26/22 See Plan Review notes: The plan review notes shall always be attached to the stamped approved plans and documents. are part of the plans and shall be a permanent record with the plans. Inspection shall not take place without a complete set of the Idaho Division of Occupational and Professional Licenses (IDOPL) plan review notes and approved, stamped plans on site. These documents have been reviewed for code compliance by the Division of Occupational and Professional Licenses. This approval shall not be construed to be an approval of any violation of, or variance from, Idaho's adopted codes, standards, rules or laws applicable to this project. Corrections will be required for any code violations found during the inspection process. This is not a building permit Plan Approval #: Date: MOD2211-00018 11/30/22 1. HOLD DOWN PLATES, WASHERS, AND NUTS (14) 699-982-BRNZ HOLD DOWN PLATE (14) 299-0007 HEX NUT (14) 299-0016 FLAT WASHER (14) 299-0018 LOCK WASHER 2. (1) 102-0072 FLOOR INSERT ITEMS SHIPPED LOOSE CONSTRUCTION NOTES DATE DRAFTER REVISION 9/22/22 NRS UPDATED SKID AND INTERIOR LIGHT WATTAGE REVISION LOG ON 16" CENTERS3. WALLS TO HAVE 2X4 STUDS 7. ROOF TO BE FR DECK PANEL A 6. ROOF TO HAVE R-38 SPRAY IN FOAM INSULATION APPLIED TO UNDERSIDE OF FR DECK PANEL A ON 12" CENTERS5. ROOF TO HAVE 2X12 JOISTS 10. 10 1/2" X 1 1/2" 18 GAUGE GALVANIZED STRAPS TO BE INSTALLED ON ALL ROOF RIM JOISTS AND WHERE INDICATED ON FLOOR RIM JOISTS (SEE SKID). STRAPS ARE TO BE FASTENED WITH 1 1/2" X .100 KNURLED MG NAILS. 11. DOUBLE FLOOR JOISTS TO BE INSTALLED EVERY 4' 2. FLOOR TO HAVE R-21 FIBERGLASS INSULATION ELECTRICAL NOTES INTEGRATION NOTES 10. ELECTRICAL CONDUIT COUPLERS WILL BE STANDARD SCREW TYPE FITTINGS. 1. CABLE LADDER TO BE MOUNTED AT 7'-2" A.F.F. 2. NO GROUNDING/BONDING TO BE INSTALLED. 3. NO GROUND PENETRATION TO BE INSTALLED. GROUND WILL COME UP THROUGH FLOOR ENTRANCE. 1. ALL WIRING SHALL BE IN ACCORDANCE WITH THE 2018 NATIONAL ELECTRIC CODE. 2. ALL ELECTRICAL MATERIALS SHALL BE U.L. LISTED AND CLASSIFIED AS SUITABLE FOR THE PURPOSE SPECIFIED. 3. ALL WIRING SHALL BE SURFACE MOUNTED IN A RACEWAY OR EMT CONDUIT USING APPROVED CONNECTORS, COUPLINGS, AND CLAMPS, ALL CONDUIT SHALL BE ANCHORED IN PLACE AT APPROXIMATELY EVERY 4 FT ON CONDUIT RUNS. ANCHORED IN PLACE 3' FROM EVERY ELECTRICAL BOX. 4. ALL WIRING SHALL BE STRANDED CONDUCTOR. 5. ALL WIRE RUNS SHALL BE CONTINUOUS. 6. LOW VOLTAGE WIRE MAY BE STRANDED. 7. ALL WIRING SHALL BE TESTED AND INSPECTED PRIOR TO SHIPMENT. 8. GREEN GROUND CONDUCTORS SHALL BE RUN TO ALL OF THE BUILDINGS A/C POWERED DEVICES. CONDUIT SHALL NOT BE USED AS THE SOLE SOURCE OF GROUND. 9. ALL ALARM DEVICES WIRING SHALL BE RUN IN ITS OWN CONDUIT TO THE ALARM CABINET. 11. MINIMUM EMT CONDUIT SIZE SHALL BE TRADE SIZE 16 (1/2") ON 12" CENTERS1. FLOOR TO HAVE 2X6 JOISTS 8. PERIMETER SKID TO BE PAINTED WITH DARK BRONZE RUST PREVENTATIVE PAINT 9. ALL EDGING AND TRIM TO BE DARK BRONZE IN COLOR WALLS TO HAVE R-15 FIBERGLASS INSULATION4. WITH R-5 RIGID FOAM NO N E CI T Y OF RE X B U R G TH I S DO C U M E N T AN D AL L IN F O R M A T I O N CO N T A I N E D HE R E I N AR E TH E PROPRIETARY DA T A AN D TR A D E SE C R E T S OF TH E R M O B O N D . TH I S DO C U M E N T AN D TH E IN F O R M A T I O N CO N T A I N E D HE R E I N MA Y NO T BE RE P R O D U C E D , US E D OR DI S C L O S E D IN AN Y MA N N E R OR TO AN Y EX T E N T (E X C E P T BY OR TO TH E R M O B O N D ) WIT H O U T TH E PR I O R WR I T T E N AU T H O R I Z A T I O N OF TH E R M O B O N D . DR A W N : 9/ 7 / 2 2 RE V I S E D : 9/ 2 6 / 2 2 DR A W N BY : NR S PR O J E C T NU M B E R : 21 1 2 - 5 3 4 B - 1 SC A L E ~ 11 X 1 7 : SH E E T : PR O J E C T NA M E : DR A W I N G NU M B E R : TB B 1 5 7 4 RE X B U R G , ID 12 ' W . OD x 2 0 ' L . OD x 9' H . ID SH E L T E R A2 . 0 Re v i s i o n s & No t e s These documents have been reviewed for code compliance by the Division of Occupational and Professional Licenses. This approval shall not be construed to be an approval of any violation of, or variance from, Idaho's adopted codes, standards, rules or laws applicable to this project. Corrections will be required for any code violations found during the inspection process. This is not a building permit Plan Approval #: Date: MOD2211-00018 11/30/22 HYDRAULIC CLOSER099-0861 HYDRAULIC CLOSER HOLD OPEN099-0892 900-186 A/R 12. 12" CABLE LADDER RACKCLR-12-2 1 7. 20" MASTER GROUND BAR915-054 GBI14420TBI 4', 2 BULB LED LIGHT FIXTURE, 32W500-0130 9. 3. LIGHT SWITCH, SINGLE500-103 10. 500-085 EXTERIOR LED LIGHT WITH PHOTOCELL BARD HVAC THERMOSTATMC4002-A 100-0084 5. 4.200A. 120/240V. SINGLE PHASE, 40 POSITIONQO140M200200-152 DISTRIBUTION PANEL W/ 200A. MAIN BREAKER 4" WIRE RACEWAYA/R A/R 13. BILL OF MATERIALS DESCRIPTIONMFG PART #TBB PART # QTY.NO. METAL WALL FILE001-2048 1 14. 3' X 7' STEEL INSULATED DOOR AND FRAME W/ BAKED ON ENAMEL PAINT W/S.S. BALL BEARING HINGES W/ NON REMOVABLE PINS, LEFT HAND REVERSE W/ TELL 099-0834 1 1. LEVER PASSAGE & DEADBOLT, ADJUSTABLE FRAME GFI RECEPTACLE 20A. W/WEATHERPROOF COVER800-100 2. DUPLEX RECEPTACLES 20A.800-101 11. 200A. SINGLE PHASE MAIN DISCONNECT INTERIORQ22200NS 200-171 1 15. 4 1 1 1 1 1 8 BARD 2 TON AC W/5KW HEAT, 11 EERW24AB-A05BPXXXJ 899-707 6. 2 UNISTRUT, 1 5/8" X 1 5/8" X 16"915-211-GRY 2 17. TWISTLOCK RECEPTACLES 20A.L5-20 800-106 8. 2 FLOOR INSERT, A=8", B=12", C=13"102-0072 1 16. NO N E CI T Y OF RE X B U R G TH I S DO C U M E N T AN D AL L IN F O R M A T I O N CO N T A I N E D HE R E I N AR E TH E PROPRIETARY DA T A AN D TR A D E SE C R E T S OF TH E R M O B O N D . TH I S DO C U M E N T AN D TH E IN F O R M A T I O N CO N T A I N E D HE R E I N MA Y NO T BE RE P R O D U C E D , US E D OR DI S C L O S E D IN AN Y MA N N E R OR TO AN Y EX T E N T (E X C E P T BY OR TO TH E R M O B O N D ) WIT H O U T TH E PR I O R WR I T T E N AUTHORIZATION OF TH E R M O B O N D . DR A W N : 9/ 7 / 2 2 RE V I S E D : 9/ 2 6 / 2 2 DR A W N BY : NR S PR O J E C T NU M B E R : 21 1 2 - 5 3 4 B - 1 SC A L E ~ 11 X 1 7 : SH E E T : PR O J E C T NA M E : DR A W I N G NU M B E R : TB B 1 5 7 4 RE X B U R G , ID 12 ' W . OD x 2 0 ' L . OD x 9' H . ID SH E L T E R B1 . 0 Bi l l of Ma t e r i a l s These documents have been reviewed for code compliance by the Division of Occupational and Professional Licenses. This approval shall not be construed to be an approval of any violation of, or variance from, Idaho's adopted codes, standards, rules or laws applicable to this project. Corrections will be required for any code violations found during the inspection process. This is not a building permit Plan Approval #: Date: MOD2211-00018 11/30/22 BA R D WALL "A" WALL "D" WALL "C" WALL "B" 18'-11 3/4" 9' - 0 1/ 4 " 10 ' - 1 1 3/ 4 " SU P P L Y RE T U R N 1 3 14 SU P P L Y RE T U R N 5 6 6 4' 2' 2' 4' 8'-1" 1'-4" 4 15 6' 1' - 6 " 3'-9" 7 1111 11 1' - 6 " 4' 6' 4' TY P . 11 11 11 11 9 16 9 9 9 1717 8 13 8 3' 9'-5" 11 NOTES: 1. ALL CONDUIT SHOWN IS APPROXIMATE AND MAY NOT REFLECT ACTUAL RUNS IN BUILDING 1/ 4 " = 1' - 0 " CI T Y OF RE X B U R G TH I S DO C U M E N T AN D AL L IN F O R M A T I O N CO N T A I N E D HE R E I N AR E TH E PR O P R I E T A R Y DA T A AN D TR A D E SE C R E T S OF TH E R M O B O N D . TH I S DO C U M E N T AN D TH E IN F O R M A T I O N CO N T A I N E D HE R E I N MA Y NO T BE RE P R O D U C E D , US E D OR DI S C L O S E D IN AN Y MA N N E R OR TO AN Y EX T E N T (E X C E P T BY OR TO TH E R M O B O N D ) WIT H O U T TH E PR I O R WR I T T E N AU T H O R I Z A T I O N OF TH E R M O B O N D . DR A W N : 9/ 7 / 2 2 RE V I S E D : 9/ 2 6 / 2 2 DR A W N BY : NR S PR O J E C T NU M B E R : 21 1 2 - 5 3 4 B - 1 SC A L E ~ 11 X 1 7 : SH E E T : PR O J E C T NA M E : DR A W I N G NU M B E R : TB B 1 5 7 4 RE X B U R G , ID 12 ' W . OD x 20 ' L . OD x 9' H . ID SH E L T E R C1 . 0 In t e r i o r La y o u t 9/26/22 These documents have been reviewed for code compliance by the Division of Occupational and Professional Licenses. This approval shall not be construed to be an approval of any violation of, or variance from, Idaho's adopted codes, standards, rules or laws applicable to this project. Corrections will be required for any code violations found during the inspection process. This is not a building permit Plan Approval #: Date: MOD2211-00018 11/30/22 16 WALL "B" WALL "A" WALL "C" WALL "D" FLOOR LAYOUT 2'-2" 2" 1717 WALL "B" WALL "A" WALL "C" WALL "D" CABLE LADDER LAYOUT 5' - 5 7/ 8 " 6' 6' 6' 9 9 9 9 8 13 8 WALL "B" WALL "A" WALL "C" WALL "D" ELECTRICAL LAYOUT 4' - 6 " 3'2'-4" NOTES: 1. ALL CONDUIT SHOWN IS APPROXIMATE AND MAY NOT REFLECT ACTUAL RUNS IN BUILDING 1/ 4 " = 1' - 0 " CI T Y OF RE X B U R G TH I S DO C U M E N T AN D AL L IN F O R M A T I O N CO N T A I N E D HE R E I N AR E TH E PROPRIETARY DA T A AN D TR A D E SE C R E T S OF TH E R M O B O N D . TH I S DO C U M E N T AN D TH E IN F O R M A T I O N CO N T A I N E D HE R E I N MA Y NO T BE RE P R O D U C E D , US E D OR DI S C L O S E D IN AN Y MA N N E R OR TO AN Y EX T E N T (E X C E P T BY OR TO TH E R M O B O N D ) WIT H O U T TH E PR I O R WR I T T E N AU T H O R I Z A T I O N OF TH E R M O B O N D . DR A W N : 9/ 7 / 2 2 RE V I S E D : 9/ 2 6 / 2 2 DR A W N BY : NR S PR O J E C T NU M B E R : 21 1 2 - 5 3 4 B - 1 SC A L E ~ 11 X 1 7 : SH E E T : PR O J E C T NA M E : DR A W I N G NU M B E R : TB B 1 5 7 4 RE X B U R G , ID 12 ' W . OD x 20 ' L . OD x 9' H . ID SH E L T E R C1 . 1 Fl o o r & Ce i l i n g La y o u t These documents have been reviewed for code compliance by the Division of Occupational and Professional Licenses. This approval shall not be construed to be an approval of any violation of, or variance from, Idaho's adopted codes, standards, rules or laws applicable to this project. Corrections will be required for any code violations found during the inspection process. This is not a building permit Plan Approval #: Date: MOD2211-00018 11/30/22 WALL "B" WALL "A" WALL "C"WALL "D" 2" ELECTRICAL ENTRANCE METAL ROOF EDGE AGGREGATE EXTERIOR PANEL METAL ROOF EDGE AGGREGATE EXTERIOR PANEL METAL ROOF EDGE AGGREGATE EXTERIOR PANEL METAL ROOF EDGE AGGREGATE EXTERIOR PANEL BARD 1 10 BARD 66 2 6 6 3 / 1 6 " = 1' - 0 " CI T Y OF RE X B U R G TH I S DO C U M E N T AN D AL L IN F O R M A T I O N CO N T A I N E D HE R E I N AR E TH E PR O P R I E T A R Y DA T A AN D TR A D E SE C R E T S OF TH E R M O B O N D . TH I S DO C U M E N T AN D TH E IN F O R M A T I O N CO N T A I N E D HE R E I N MA Y NO T BE RE P R O D U C E D , US E D OR DI S C L O S E D IN AN Y MA N N E R OR TO AN Y EX T E N T (E X C E P T BY OR TO TH E R M O B O N D ) WIT H O U T TH E PR I O R WR I T T E N AU T H O R I Z A T I O N OF TH E R M O B O N D . DR A W N : 9/ 7 / 2 2 RE V I S E D : 9/ 2 6 / 2 2 DR A W N BY : NR S PR O J E C T NU M B E R : 21 1 2 - 5 3 4 B - 1 SC A L E ~ 11 X 1 7 : SH E E T : PR O J E C T NA M E : DR A W I N G NU M B E R : TB B 1 5 7 4 RE X B U R G , ID 12 ' W . OD x 2 0 ' L . OD x 9' H . ID SH E L T E R C2 . 0 El e v a t i o n Vi e w s 9/26/22 These documents have been reviewed for code compliance by the Division of Occupational and Professional Licenses. This approval shall not be construed to be an approval of any violation of, or variance from, Idaho's adopted codes, standards, rules or laws applicable to this project. Corrections will be required for any code violations found during the inspection process. This is not a building permit Plan Approval #: Date: MOD2211-00018 11/30/22 HEAVY DUTY HOLD OPEN HOLD BACK BALL BEARING HINGES WITH NON REMOVABLE PINS PASSAGE DEADBOLT 3' 1/ 2 " 7' 134" BALL BEARING HINGES WITH NON REMOVABLE PINS NOTES: · DOOR FRAME 16 GAUGE PRIMED AND PAINTED STEEL. · DOOR SLAB 18 GAUGE PRIMED AND PAINTED STEEL. · WEATHER STRIPPING AROUND DOOR OPENING. · THRESHOLD BELOW DOOR. · DRIP CAP ABOVE DOOR FRAME. · PASSAGE AND DEADBOLT. NT S CI T Y OF RE X B U R G TH I S DO C U M E N T AN D AL L IN F O R M A T I O N CO N T A I N E D HE R E I N AR E TH E PR O P R I E T A R Y DA T A AN D TR A D E SE C R E T S OF TH E R M O B O N D . TH I S DO C U M E N T AN D TH E IN F O R M A T I O N CO N T A I N E D HE R E I N MA Y NO T BE RE P R O D U C E D , US E D OR DI S C L O S E D IN AN Y MA N N E R OR TO AN Y EX T E N T (E X C E P T BY OR TO TH E R M O B O N D ) WIT H O U T TH E PR I O R WR I T T E N AUTHORIZATION OF TH E R M O B O N D . DR A W N : 9/ 7 / 2 2 RE V I S E D : 9/ 2 6 / 2 2 DR A W N BY : NR S PR O J E C T NU M B E R : 21 1 2 - 5 3 4 B - 1 SC A L E ~ 11 X 1 7 : SH E E T : PR O J E C T NA M E : DR A W I N G NU M B E R : TB B 1 5 7 4 RE X B U R G , ID 12 ' W . OD x 2 0 ' L . OD x 9' H . ID SH E L T E R C3 . 0 Do o r De t a i l These documents have been reviewed for code compliance by the Division of Occupational and Professional Licenses. This approval shall not be construed to be an approval of any violation of, or variance from, Idaho's adopted codes, standards, rules or laws applicable to this project. Corrections will be required for any code violations found during the inspection process. This is not a building permit Plan Approval #: Date: MOD2211-00018 11/30/22 COVE INTERIOR WALL AND CEILING TO BE FINISHED WITH 3/4" PRE-FINISHED FRP/OSB BOARD FRP IS RATED FIRE CLASS C 1/4" AGGREGATE PANEL METAL ROOF EDGE 23/32" FR DECK PANEL 45 MIL REINFORCED MULE HIDE WHITE TPO ROOFING MEMBRANE FULLY ADHERED WITH AQUA BASE 120 BONDING ADHESIVE TO FR DECK PANEL HOUSE WRAP DOUBLE TOP PLATES 1/2" EXTERIOR RATED WALL SHEATHING PANEL TOP PLATE TO WALL STUD ROOF FASTENED TO WALL R-5 RIGID FOAM 2 X 12'S @ 12" O.C. TAPERED TO FORM ROOF PITCH R-38 SPRAY-IN FOAM APPLIED TO UNDERSIDE OF FR DECK PANEL INTERIOR WALLS TO BE FINISHED WITH 3/4" PRE-FINISHED FRP/OSB BOARD FRP IS RATED FIRE CLASS C COVE R-5 RIGID FOAM HOUSE WRAP 1/2" EXTERIOR RATED WALL SHEATHING PANEL WALLS FASTENED IN CORNERS @ 16 O.C.2 X 4's R-15 FIBERGLASS R-15 FIBER- GLASS R-15 FIBER- GLASS 1/4" AGGREGATE PANEL PVC CORNER PIECE PVC TRIM STRIP 1/4" GAP BETWEEN AGGREGATE PANELS WALL FASTENED TO FLOOR 3/4" T & G STURD-I-FLOOR BOTTOM OF WALL SEALED WITH CONSTRUCTION ADHESIVE SEALANT R-5 RIGID FOAM 6" X #9 BEAM 3/8" x 4" LAG BOLT @ 12" O.C. 1/8" COMMERCIAL GRADE TILE 4" BASEBOARD INTERIOR OF WALL TO BE FINISHED WITH PRE-FINISHED FRP/OSB BOARD FRP IS RATED FIRE CLASS C 2 X 6's @12" O.C. HOUSE WRAP 1/2" EXTERIOR RATED WALL SHEATHING PANEL BOTTOM OF FLOOR IS 3/4" CDX PLYWOOD SEALING WITH AN ASPHALT UNDERCOATING AND A 18 X 16 X .011 WIRE MESH FOR RODENT PROTECTION 1/4" AGGREGATE PANEL R-21 FIBERGLASS INSULATION GALV. "L" FLASHING WRAP BOTTOM OF EXTERIOR SHEATHING WITH HOUSE WRAP 6" UP EACH SIDE WALL TO FLOOR DETAIL WALL TO ROOF DETAIL WALL CORNER DETAIL NOTES: 1. SEE FASTENER SCHEDULE FOR FASTENER INFORMATION. 2. HOUSE WRAP TO BE INSTALLED 1/8" BELOW SHEETING AND EXTEND TO TOP OF TOP PLATE. ALL SEAMS TO BE LAPPED 6" AND TAPED W/SEAM TAPE. 3. ALL SCREW HOLES THROUGH PANELS FILLED WITH POLYURETHANE CAULK PRIOR TO SCREW BEING INSTALLED. 4. ALL STRUCTURAL LUMBER SHALL BE SPF #1 OR #2. 5. ALL CDX, EXTERIOR SHEATHING & T&G GLUED TO STUDS WITH ENERBOND SF GLUE (COMPLIES WITH ASTM D3498) TO ALL STUDS BEFORE NAILING. SEE FASTENER SCHEDULE NT S CI T Y OF RE X B U R G TH I S DO C U M E N T AN D AL L IN F O R M A T I O N CO N T A I N E D HE R E I N AR E TH E PROPRIETARY DA T A AN D TR A D E SE C R E T S OF TH E R M O B O N D . TH I S DO C U M E N T AN D TH E IN F O R M A T I O N CO N T A I N E D HE R E I N MA Y NO T BE RE P R O D U C E D , US E D OR DI S C L O S E D IN AN Y MA N N E R OR TO AN Y EX T E N T (E X C E P T BY OR TO TH E R M O B O N D ) WIT H O U T TH E PR I O R WR I T T E N AU T H O R I Z A T I O N OF TH E R M O B O N D . DR A W N : 9/ 7 / 2 2 RE V I S E D : 9/ 2 6 / 2 2 DR A W N BY : NR S PR O J E C T NU M B E R : 21 1 2 - 5 3 4 B - 1 SC A L E ~ 11 X 1 7 : SH E E T : PR O J E C T NA M E : DR A W I N G NU M B E R : TB B 1 5 7 4 RE X B U R G , ID 12 ' W . OD x 20 ' L . OD x 9' H . ID SH E L T E R D1 . 0 Co r n e r Construction INSULATION REQUIREMENT NOTES: 1. RIGID FOAM BOARD TO BE OWENS-CORNING FOAMULAR 150 PER UL ER811-01): R-3 - 1/2" THICK R-5 - 1" THICK R-7.5 - 1 1/2" THICK SPRAY-IN FOAM REQUIREMENT NOTES: 1. SPRAY-IN FOAM TO BE BASF SPRAYTITE 178 APPLIED AT THE FOLLOWING THICKNESS (INTEK REPORT CCRR-1031): R-21 3-1/2" THICK R-25 4" THICK R-30 5" THICK R-35 6" THICK R-38 6" THICK CONSTRUCTION NOTES: FR DECK PANEL A AND TPO MEMBRANE MUST BE INSTALLED PER ICC-ESR 1365. 1. MULE-HIDE FR DECK PANEL A ROOF DECK MUST BE INSTALLED WITH PYROTITE LAMINATE FACING UP. 2. ALL DECK JOINTS MUST BE BLOCKED WITH 2X4 BLOCKING OR INSTALLED OVER A ROOF JOIST. 3. GAPS IN THE DECK PANELS MUST BE CAULKED WITH RECTORSEAL FLAMESAFE FS9000+. 9/26/22 These documents have been reviewed for code compliance by the Division of Occupational and Professional Licenses. This approval shall not be construed to be an approval of any violation of, or variance from, Idaho's adopted codes, standards, rules or laws applicable to this project. Corrections will be required for any code violations found during the inspection process. This is not a building permit Plan Approval #: Date: MOD2211-00018 11/30/22 11 1 4" 714" 10 1/2" X 1 1/2" 18 GAUGE STRAPPING, QTY 2 (EACH END OF TRUSS) TAPERED 23/32" FR DECK PANEL NAILED TO JOIST SPACED 12" O.C. 2 X 12 ROOF JOIST INTERIOR PRE-FINISH FRP/OSB TO FASTENED TO JOIST 23/32" FR DECK PANEL NAILED TO JOIST DOUBLE TOP PLATE SPACED 12" O.C. 1/ 2 " - 12 " PI T C H 2 X 12 ROOF JOIST ROOF STRUCTURE SIDE DETAIL ROOF STRUCTURE END DETAIL NOTES: 1. SEE FASTENER SCHEDULE FOR FASTENER INFORMATION. 2. HOUSE WRAP TO BE INSTALLED 1/8" BELOW SHEETING AND EXTEND TO TOP OF TOP PLATE. ALL SEAMS TO BE LAPPED 6" AND TAPED W/SEAM TAPE. 3. ALL SCREW HOLES THROUGH PANELS FILLED WITH POLYURETHANE CAULK PRIOR TO SCREW BEING INSTALLED. 4. ALL STRUCTURAL LUMBER SHALL BE SPF #1 OR #2. 5. ALL CDX, EXTERIOR SHEATHING & T&G GLUED TO STUDS WITH ENERBOND SF GLUE (COMPLIES WITH ASTM D3498) TO ALL STUDS BEFORE NAILING. NT S CI T Y OF RE X B U R G TH I S DO C U M E N T AN D AL L IN F O R M A T I O N CO N T A I N E D HE R E I N AR E TH E PR O P R I E T A R Y DA T A AN D TR A D E SE C R E T S OF TH E R M O B O N D . TH I S DO C U M E N T AN D TH E IN F O R M A T I O N CO N T A I N E D HE R E I N MA Y NO T BE RE P R O D U C E D , US E D OR DI S C L O S E D IN AN Y MA N N E R OR TO AN Y EX T E N T (E X C E P T BY OR TO TH E R M O B O N D ) WIT H O U T TH E PR I O R WR I T T E N AU T H O R I Z A T I O N OF TH E R M O B O N D . DR A W N : 9/ 7 / 2 2 RE V I S E D : 9/ 2 6 / 2 2 DR A W N BY : NR S PR O J E C T NU M B E R : 21 1 2 - 5 3 4 B - 1 SC A L E ~ 11 X 1 7 : SH E E T : PR O J E C T NA M E : DR A W I N G NU M B E R : TB B 1 5 7 4 RE X B U R G , ID 12 ' W . OD x 20 ' L . OD x 9' H . ID SH E L T E R D1 . 1 Ro o f Co n s t r u c t i o n 9/26/22 These documents have been reviewed for code compliance by the Division of Occupational and Professional Licenses. This approval shall not be construed to be an approval of any violation of, or variance from, Idaho's adopted codes, standards, rules or laws applicable to this project. Corrections will be required for any code violations found during the inspection process. This is not a building permit Plan Approval #: Date: MOD2211-00018 11/30/22 SPAN RATINGS FOR CONSTRUCTION MATERIALS: FLOOR 23/32" T&G: 24 OC WALL 15/32" OSB: 32/16 ROOF 23/32" PLYWOOD: 48/24 NO N E CI T Y OF RE X B U R G TH I S DO C U M E N T AN D AL L IN F O R M A T I O N CO N T A I N E D HE R E I N AR E TH E PROPRIETARY DA T A AN D TR A D E SE C R E T S OF TH E R M O B O N D . TH I S DO C U M E N T AN D TH E IN F O R M A T I O N CO N T A I N E D HE R E I N MA Y NO T BE RE P R O D U C E D , US E D OR DI S C L O S E D IN AN Y MA N N E R OR TO AN Y EX T E N T (E X C E P T BY OR TO TH E R M O B O N D ) WIT H O U T TH E PR I O R WR I T T E N AUTHORIZATION OF TH E R M O B O N D . DR A W N : 9/ 7 / 2 2 RE V I S E D : 9/ 2 6 / 2 2 DR A W N BY : NR S PR O J E C T NU M B E R : 21 1 2 - 5 3 4 B - 1 SC A L E ~ 11 X 1 7 : SH E E T : PR O J E C T NA M E : DR A W I N G NU M B E R : TB B 1 5 7 4 RE X B U R G , ID 12 ' W . OD x 2 0 ' L . OD x 9' H . ID SH E L T E R D2 . 0 Fa s t e n e r Sc h e d u l e FASTENER SCHEDULE CHART ITEM SIZE TYPE SPACING TOLERANCE MINIMUM INTERIOR OSB/FRP TO ASSEMBLY FRAMEWORK 15GA X 2 1/2" FINISH NAIL 6" AROUND PERIMETER, 12" IN FIELD +/- 1/4" 36 ALL OSB, CDX & T&G TO ASSEMBLY FRAMEWORK .113 X 2 1/2" SPIRAL SHANK 4" AROUND PERIMETER, 12" IN FIELD +/- 1/4" 36 SHEATHING TO RIM JOIST .099 X 2 1/2" SPIRAL SHANK 4" ON CENTER +/- 1/4" VARIES CORNER WALL TO WALL 3/8" X 6" LAG 3/4" FROM OUTER EDGE, 24" OC IN FIELD +/- 3/4" VARIES FLOOR TO SKID 3/8" X 4" LAG 12" OC STAGGERED VARIES WALL TO FLOOR 3/8" X 4" LAG 2" FROM FLUSH OUTER EDGE, EVERY 24" +/- 3/4" VARIES ROOF TO WALL 3/8" X 6" LAG 12" OC +/- 3/4" VARIES TOP PLATE TO STUD 2X4 .131 X 3" COMMON NAIL 2 END NAILED 2 STUD TO SOLE PLATE .131 X 3" COMMON NAIL 2 END NAILED 2 DOUBLE TOP PLATES .131 X 3" COMMON NAIL 16" OC TYPICAL FACE NAIL +/- 3/4" VARIES TOP PLATES LAP & INTERSECTIONS .131 X 3" COMMON NAIL 2 FACE NAILED 2 CONTINUOUS HEADER, TWO PIECES .131 X 3" COMMON NAIL 16" OC ALONG EDGE +/- 3/4" VARIES CONTINUOUS HEADER TO STUD .131 X 3" COMMON NAIL 4 END NAILED 4 RAFTER TO PLATE 2 X 6 .131 X 3" COMMON NAIL 3 FACE NAILED 3 RAFTER TO PLATE 2 X 8 .131 X 3" COMMON NAIL 4 FACE NAILED 4 RAFTER TO PLATE 2 X 10 .131 X 3" COMMON NAIL 5 FACE NAILED 5 RAFTER TO PLATE 2 X 12 .131 X 3" COMMON NAIL 6 FACE NAILED 6 ROOF DECK .113 X 2 1/2" SPIRAL SHANK 6" AROUND PERIMETER, 12" IN FIELD +/- 1/4" 36 END WALL SHEATHING .113 X 2 1/2" COMMON NAIL 4" AROUND PERIMETER, 12" IN FIELD +/- 1/4" VARIES SIDE WALL SHEATHING .113 X 2 1/2" COMMON NAIL 6" AROUND PERIMETER, 12" IN FIELD +/- 1/4" VARIES ROOF FACE TO ROOF BASE #8 X 3/4" TEK SCREW 12" O.C. VARIES EXTERIOR AGGREGATE PANEL WITH R3 OR R5 RIGID INSULATION #10 X 2 1/2" SS SCREW 1" FROM EDGE, 1 EVERY 2' IN FIELD; PREDRILLED 3/16" HOLES +/- 1/4" VARIES 18 GA STRAPPING OF DOUBLE STUDS TO RIM JOIST .148 X 2 1/2" COMMON NAIL 16 NAILS MIN., 8 INTO DOUBLE STUDS AND 8 INTO RIM JOISTS (BOTH STRAPS)16 9/26/22 These documents have been reviewed for code compliance by the Division of Occupational and Professional Licenses. This approval shall not be construed to be an approval of any violation of, or variance from, Idaho's adopted codes, standards, rules or laws applicable to this project. Corrections will be required for any code violations found during the inspection process. This is not a building permit Plan Approval #: Date: MOD2211-00018 11/30/22 1 3 5 7 9 11 13 15 17 19 21 35 39 37 33 31 29 27 25 23 DESCRIPTION QT Y . UNIT V.A. A B PHASE TR I P PO L E S WI R E SI Z E A. I . C . LOAD LOAD PER PHASE PANEL CIRCUIT (VA) AND LOAD PER PHASE LOAD SCHEDULE (VA) 41 34 38 40 36 30 32 28 PHASE V.A.QT Y . 20 24 26 22 16 18 14 6 10 12 8 4 2 AB LOAD DESCRIPTIONUNIT WI R E SI Z E A. I . C . PO L E S TR I P LOCATION: DESIGNATION: SERVICE: S/NS/G 42 200 LIGHTS 4 10k1212032 20128 10k DUPLEXES412 1 20 720 180 20 1 2 10k 2592 2 TON BARD HVAC5184 2592 30 10 30 1 2 10k 2592 2 TON BARD HVAC 5184 2592 30 10 30 SUBTOTAL MANUFACTURER: CATALOG NUMBERS: TOTAL KVA PHASE A TOTAL KVA PHASE B TOTAL AMPS PHASE A TOTAL AMPS PHASE B CONTINUOUS NO EQUAL: APPROVED EQUAL: FLUSHSURFACE MOUNTING: SUBTOTAL VOLTAGE: NEUTRAL: MAIN BREAKER: MAIN LUGS: MAINS: TOP BOTTOM MAIN COPPER BUS: CYCLE: PHASE: WIRES: TRIP: A/C: 6.0 6.1 50.4 50.7 3312 3312 27722732 X QO140M200 200 AMP 200 AMP 200 AMP FRAME X X 360 1 22 KA SQUARE D120/240V. 2" EMT (2) 3/0 WIRE (1) #6 WIRE WIRING SCHEMATIC UTILITY MAIN BREAKER W/ BONDING BUSHING MAIN PANEL NO N E CI T Y OF RE X B U R G TH I S DO C U M E N T AN D AL L IN F O R M A T I O N CO N T A I N E D HE R E I N AR E TH E PROPRIETARY DA T A AN D TR A D E SE C R E T S OF TH E R M O B O N D . TH I S DO C U M E N T AN D TH E IN F O R M A T I O N CO N T A I N E D HE R E I N MA Y NO T BE RE P R O D U C E D , US E D OR DI S C L O S E D IN AN Y MA N N E R OR TO AN Y EX T E N T (E X C E P T BY OR TO TH E R M O B O N D ) WIT H O U T TH E PR I O R WR I T T E N AU T H O R I Z A T I O N OF TH E R M O B O N D . DR A W N : 9/ 7 / 2 2 RE V I S E D : 9/ 2 6 / 2 2 DR A W N BY : NR S PR O J E C T NU M B E R : 2112-53 4B-1 SC A L E ~ 11 X 1 7 : SH E E T : PR O J E C T NA M E : DR A W I N G NU M B E R : TB B 1 5 7 4 RE X B U R G , ID 12 ' W . OD x 2 0 ' L . OD x 9' H . ID SH E L T E R E1 . 0 El e c t r i c a l Pa n e l 10kGFI 1 12120180 180 20 10kEXTERIOR LIGHT 1 1212012 12 20 10k DUPLEXES412 1 20 720 180 20 10k TWISTLOCK112 1 20 20 10k TWISTLOCK1 12 1 2020 These documents have been reviewed for code compliance by the Division of Occupational and Professional Licenses. This approval shall not be construed to be an approval of any violation of, or variance from, Idaho's adopted codes, standards, rules or laws applicable to this project. Corrections will be required for any code violations found during the inspection process. This is not a building permit Plan Approval #: Date: MOD2211-00018 11/30/22 10 1/2" X 1 1/2" 18 GAUGE STRAPPING LOCATION 8'-1" 16'-1" 1'-6" 19'-8 1/4" 11 ' - 8 1/ 4 " 5' - 8 1/ 8 " 2' - 9 1/ 8 " 18'-2 1/4" 12'-1" 4'-1" 1* 3 1* 1* 2 2 1* 1* 1* 3 3 2' - 5 1/ 8 " 2' - 7 " 2' - 5 1/ 8 " A A B B 1" TYP 9 3 / 4 " 1' TYP 3 2' - 7 " 8' - 7 1/ 4 " 10 1/2" X 1 1/2" 18 GAUGE STRAPPING LOCATION 10 1/2" X 1 1/2" 18 GAUGE STRAPPING LOCATION 9 3 / 4 " 10 3 / 8 " 10 3 / 8 " 10 3 / 8 " 10 3 / 8 " 9 3/ 4 " 9 3/ 4 " 4' TYP3'-8" 3 3/16" 3/16"TYP. 1 1 2 3/16" 3/16" TYP. 1/ 4 " 1/ 4 " 2" 3/8" x 45° CHAMFER LIST OF MATERIAL NO. QTY.DESCRIPTION 1. 7 2. 163. BEAM SUPPORT (W6 X 9#) GRADE 50 GRADE A992 WEIGHT 1066.3# 2 177.2# 127.9#A36 ANGLE, SUPPORT (2 X 2 X 1/4) PIPE SUPPORT (3" NOM. SCH 40) 1371.4#TOTAL BLACK STEEL WEIGHT A500B NOTES: UNLESS OTHERWISE SPECIFIED ALL DIMENSIONS SHOWN ON THIS DRAWING SHALL HAVE THE FOLLOWING TOLERANCE: FRACTION ANGLE WELDED ASSEMBLY TOP VIEW 1 1/2" = 1' SCALE SECTION "B-B" 3/8" = 1' SCALE 1 1/2" = 1' SCALE SECTION "A-A" 1. FINISH: PAINTED WITH BRONZE RUST PREVENTATIVE PAINT. AS NO T E D CI T Y OF RE X B U R G TH I S DO C U M E N T AN D AL L IN F O R M A T I O N CO N T A I N E D HE R E I N AR E TH E PROPRIETARY DA T A AN D TR A D E SE C R E T S OF TH E R M O B O N D . TH I S DO C U M E N T AN D TH E IN F O R M A T I O N CO N T A I N E D HE R E I N MA Y NO T BE RE P R O D U C E D , US E D OR DI S C L O S E D IN AN Y MA N N E R OR TO AN Y EX T E N T (E X C E P T BY OR TO TH E R M O B O N D ) WIT H O U T TH E PR I O R WR I T T E N AU T H O R I Z A T I O N OF TH E R M O B O N D . DR A W N : 9/ 7 / 2 2 RE V I S E D : 9/ 2 6 / 2 2 DR A W N BY : NR S PR O J E C T NU M B E R : 21 1 2 - 5 3 4 B - 1 SC A L E ~ 11 X 1 7 : SH E E T : PR O J E C T NA M E : DR A W I N G NU M B E R : TB B 1 5 7 4 RE X B U R G , ID 12 ' W . OD x 2 0 ' L . OD x 9' H . ID SH E L T E R S1 . 0 Sk i d 1 1/2" = 1' SCALE BEAM COPING DETAIL *2. BOTH ENDS OF THIS BEAM ARE COPED, SEE BEAM COPING DETAIL 3. STRAPPING TO BE ATTACHED TO KING STUDS ON OPENINGS MARKED 9/26/22 These documents have been reviewed for code compliance by the Division of Occupational and Professional Licenses. This approval shall not be construed to be an approval of any violation of, or variance from, Idaho's adopted codes, standards, rules or laws applicable to this project. Corrections will be required for any code violations found during the inspection process. This is not a building permit Plan Approval #: Date: MOD2211-00018 11/30/22