HomeMy WebLinkAboutHV1529 HIBBARD FINAL CDs_ELECT_06.09.25-Reviewed-ApprovedAuthor Name Author Email Author Phone No.: Alex Owens Alex.Owens@rexburg.org 208-372-2172 Description : Address : Record Type : Cell Tower Document Filename : HV1529 HIBBARD FINAL CDs_ELECT_06.09.25.pdf Comment Author Contact Information: Corrections in the following table need to be applied before a permit can be issued Review Report Approved # 25-00003 Page Reference Annotation Type Author : Department Status Page Review Comments Applicant Response Comments E-1 Stamp Alex Owens : Electrical Open 1 Approved - Electrical Inspector E-4 Callout Alex Owens : Electrical Open 4 Because this generator provides 150 amps but the calculated load is 188 amps, load shed devices will be required. E-4 Stamp Alex Owens : Electrical Open 4 Approved - Electrical Inspector Cell Tower Approval of plans does not constitute approval of variance from code EEEEEE E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E F F F F F F F F F E-1 IT IS A VIOLATION OF LAW FOR ANY PERSON, UNLESS THEY ARE ACTING UNDER THE DIRECTION OF A LICENSED PROFESSIONAL ENGINEER, TO ALTER THIS DOCUMENT. SHEET NUMBER: ISSUED FOR: SHEET NAME: SITE NAME: HIBBARD SITE NUMBER: HV1529 SITE ADDRESS: 2525 W. 4000 N REXBURG, ID 83440 JURISDICTION: MADISON COUNTY 10000 PARK MEADOWS DR, SUITE 300 LONE TREE, CO 80124 ORIGINAL DRAWING SIZE: ANSI B, 11.00" X 17.00" DRWNREV DESCRIPTION QADATE OAM 90% COMPLETE CD SET PM05/07/2024 OAM 100% COMPLETE CD SET PM11/15/2024 A 0 1065 POPLAR STREET JOHNSTOWN, CO 80534 UTILITY SITE PLAN SCALE:PAGE1PLAN: UTILITY SITE 1/128" = 1'-0”E-1 DISCLAIMER: THESE DRAWINGS WERE PRODUCED WITHOUT THE BENEFIT OF A CURRENT LAND SURVEY. ALL PROPERTY LINES, EASEMENTS, SETBACKS, AND DIMENSIONS SHOWN SHALL BE VERIFIED PRIOR TO START OF CONSTRUCTION. TOTAL SITE SERVICES DOES NOT GUARANTEE THE ACCURACY OF SAID PROPERTY LINES, EASEMENTS, SETBACKS, AND DIMENSIONS SHOWN. N EW S (E) UTILITY POLE WITH TRANSFORMER AND METER (E) RAW LAND (E) RAW LAND (E) OVERHEAD POWER (P) HORVATH H-FRAME WITH METER BANK AND FIBER ENCLOSURE (P) HORVATH 6'-0" CHAINLINK FENCE (P) HORVATH LEASE AREA,100'-0" X 100'-0" (P) HORVATH COMPOUND, 55'-0" X 55'-0" (E) UNDERGROUND FIBER ROUTE (N) UNDERGROUND PRIMARY POWER ROUTE (P) HORVATH 14'-0" ACCESS GATE (P) HORVATH 12'-0" EASEMENT (E) BUILDING, TYP. 2 E-2 E E E FF E E E E E E E E E E F F F F F F F F F F F F E E E E E E E E E E E E E E E EEEE E F F F F F F F F F F F F F F F X XXXXXXXXXXXXX X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X E-2 IT IS A VIOLATION OF LAW FOR ANY PERSON, UNLESS THEY ARE ACTING UNDER THE DIRECTION OF A LICENSED PROFESSIONAL ENGINEER, TO ALTER THIS DOCUMENT. SHEET NUMBER: ISSUED FOR: SHEET NAME: SITE NAME: HIBBARD SITE NUMBER: HV1529 SITE ADDRESS: 2525 W. 4000 N REXBURG, ID 83440 JURISDICTION: MADISON COUNTY 10000 PARK MEADOWS DR, SUITE 300 LONE TREE, CO 80124 ORIGINAL DRAWING SIZE: ANSI B, 11.00" X 17.00" DRWNREV DESCRIPTION QADATE OAM 90% COMPLETE CD SET PM05/07/2024 OAM 100% COMPLETE CD SET PM11/15/2024 A 0 1065 POPLAR STREET JOHNSTOWN, CO 80534 ELECTRICAL SITE PLAN SCALE:PAGE2PLAN: ELECTRICAL SITE 1/16” = 1’-0”E-2 N EW S PROPOSED HORVATH LEASE AREA, 100'-0" X 100'-0" PROPOSED VERIZON 30KW KOHLER GENERATOR WITH 300GAL DIESEL BELLY TANK (N) (3) PROPOSED UG CONDUITS, (1) 1/2", (1) 1", (1) 2",(±15) PROPOSED 200A ILC/ATS PROPOSED VERIZON EQUIPMENT SHELTER (N) FIBER ENCLOSURE, 24.00" X 24.00" X 12.00" PROPOSED VERIZON ICE BRIDGE (N) (1) PROPOSED 4" UG CONDUIT WITH (N) (3) 1.25" INNERDUCTS PROPOSED HORVATH H-FRAME WITH METER BANK AND FIBER ENCLOSURE PROPOSED HORVATH 110'-0" SELF-SUPPORT TOWER WITH 10' LIGHTNING ARRESTOR PROPOSED HORVATH 14'-0" ACCESS GATE PROPOSED HORVATH 12'-0" ACCESS ROAD WITHIN 20'-0" EASEMENT (E) UG FIBER ROUTE (N) VERIZON FIBER PULL BOX (N) FIBER ROUTE FROM (N) FIBER PULL BOX TO PROPOSED H-FRAME PROPOSED HORVATH 6'-0" CHAINLINK FENCE 12'-0" DIRT ROAD (N) UG PRIMARY POWER ROUTE (N) UTILITY PAD MOUNTED TRANSFORMER PROPOSED VERIZON GPS ANTENNA 3 E-3 (N) 2" SCH 40 PVC UG POWER ROUTE FROM (N) TRANSFORMER TO (N) METERBANK ON PROPOSED H-FRAME (±15) (N) (1) PROPOSED 2" SCH. 40 PVC UG CONDUIT FROM (N) METERBANK TO (N) 200A ILC (±50) E E E E E E E E E E E E E E E EEEE E F F F F F F F F F F F F F F F E-3 IT IS A VIOLATION OF LAW FOR ANY PERSON, UNLESS THEY ARE ACTING UNDER THE DIRECTION OF A LICENSED PROFESSIONAL ENGINEER, TO ALTER THIS DOCUMENT. SHEET NUMBER: ISSUED FOR: SHEET NAME: SITE NAME: HIBBARD SITE NUMBER: HV1529 SITE ADDRESS: 2525 W. 4000 N REXBURG, ID 83440 JURISDICTION: MADISON COUNTY 10000 PARK MEADOWS DR, SUITE 300 LONE TREE, CO 80124 ORIGINAL DRAWING SIZE: ANSI B, 11.00" X 17.00" DRWNREV DESCRIPTION QADATE OAM 90% COMPLETE CD SET PM05/07/2024 OAM 100% COMPLETE CD SET PM11/15/2024 A 0 1065 POPLAR STREET JOHNSTOWN, CO 80534 ELECTRICAL PLAN SCALE:PAGE3PLAN: ELECTRICAL 3/16” = 1’-0”E-3 N EW S PROPOSED VERIZON 30KW KOHLER GENERATOR WITH 300GAL DIESEL BELLY TANK (N) (3) PROPOSED UG CONDUITS, (1) 1/2", (1) 1", (1) 2",(±15) PROPOSED 200A ILC/ATS PROPOSED VERIZON EQUIPMENT SHELTER (N) (1) PROPOSED 2" SCH. 40 PVC UG CONDUIT FROM (N) METERBANK TO (N) 200A ILC (±50) (N) (1) PROPOSED 4" UG CONDUIT WITH (N) (3) 1.25" INNERDUCTS PROPOSED HORVATH 110'-0" SELF-SUPPORT TOWER WITH 10' LIGHTNING ARRESTOR PROPOSED VERIZON GPS ANTENNA (N) TRANSPORT RACK (N) (1) GMT FUSE PANEL (N) (1) ROUTER (N) (1) BBU (N) RAYCAP RACK (N) (1) 4520 RAYCAP (N) (1) JMA UPCONVERTER (N) (1) PDF RACK (N) (1) -48V PDF (N) (7) 50A RECTIFIERS (N) (2) -48V STRINGS OF SAFT TLX180s TO BE INSTALLED UNDER (N) PDF. NOTE: VERIZON TO PROVIDE BATTERY SHELVES (N) HVAC UNIT (N) VERIZON ALARM BOARD PROPOSED VERIZON ICE BRIDGE PROPOSED (N) (2) 6X12 HYBRID CABLES (N) FIBER ENCLOSURE, 24.00" X 24.00" X 12.00" E-4 IT IS A VIOLATION OF LAW FOR ANY PERSON, UNLESS THEY ARE ACTING UNDER THE DIRECTION OF A LICENSED PROFESSIONAL ENGINEER, TO ALTER THIS DOCUMENT. SHEET NUMBER: ISSUED FOR: SHEET NAME: SITE NAME: HIBBARD SITE NUMBER: HV1529 SITE ADDRESS: 2525 W. 4000 N REXBURG, ID 83440 JURISDICTION: MADISON COUNTY 10000 PARK MEADOWS DR, SUITE 300 LONE TREE, CO 80124 ORIGINAL DRAWING SIZE: ANSI B, 11.00" X 17.00" DRWNREV DESCRIPTION QADATE OAM 90% COMPLETE CD SET PM05/07/2024 OAM 100% COMPLETE CD SET PM11/15/2024 A 0 1065 POPLAR STREET JOHNSTOWN, CO 80534 ONE-LINE DIAGRAM 1PANEL SCHEDULE PANEL NAME PANEL 'G1A'ENCL. TYPE NEMA 3R NOTES: VOLTAGE RATING 120/240 VAC MOUNTING TYPE SURFACE CONN. LINE VOLTAGE 240 VAC LOCKABLE CABINET?YES PHASE 1 WIRE 3 DOOR-IN-DOOR?YES BUS TYPE MAIN BREAKER MFR. BUS RATING 200 AMPS MODEL MAIN BREAKER 200 AMPS CAT. NO. BREAKER TYPE PLUG-IN SERIES RATED BY MFR?YES INTERRUPTING RATING 65/10 KAIC FUSE TYPE NA LOAD POS CB A B CB POS LOAD 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 19,040 18,880 LOAD TYPE CONN. LOAD NEC D.F.NEC LOAD TOTAL LOAD RECEPTACLES < 10 KVA 1080 x 100%=1080 45.3 KVA LIGHTING x 125%=94.4 % LARGEST MOTOR 10000 x 125%=12500 188.9 AMPS UNITARY HVAC EQUIPMENT x 100%= DC RECTIFIERS 14400 x 100%=14400 OTHER 2000 x 100%=2000 TOTAL 42,720 VA VA 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 BLANK 45,330 440 550 1P20 BLANK -48V RECTIFIER #3 -48V RECTIFIER #2 1200 1200 GFCI RECEPTACLE 1200 1200 BLANK BLANK BLANK BLANK BLANK BLANK BLANK BLANK 1P15 -48V RECTIFIER #12P30 -48V RECTIFIER #4 -48V RECTIFIER #5 -48V RECTIFIER #6 2P30 2P30 2P30 2P30 2P30 1200 1200 1200 1200 1200 1200 1200 1200 1P20 1P20 GENERAC ILC - GEN. BLOCK HEATER GEN. BATTERY CHARGER 440 1500 500 180 10000 10000 SPARE2P30 SPARE2P30 SHELTER LIGHTING BLANK BLANK BLANK BLANK SHORT CIRCUIT CALCULATIONS SHORT CIRCUIT CALCULATIONS BASED UPON POINT METHOD AS ILLUSTRATED IN BUSSMAN PUBLICATION SPD-90. FAULT VALUES SHOWN ARE FOR 3Φ FAULTS ON 3Φ CIRCUITS AND FOR LINE-TO-LINE FAULTS ON 1Φ CIRCUITS. FAULT CURRENT AT NEW TRANSFORMER SECONDARY : ISC1 =14,880 A f1 = 2 x L x ISC1(L-L) = 2 x 15 x 14,880 =0.0348 C1 x n x VL-L 26706 x 2 x 240 M1 = 1 = 1 =0.9663 1 + f1 1 + 0.0348 =M1 x ISC1 =0.9663 x 14,880 =14,379 A FAULT CURRENT AT NEW 800A METERBANK: 2 ONE LINE DIAGRAM 3 M M M 900SHELTER RECEPTACLES 1P20 HVAC UNIT #1 1P60 5000 5000 HVAC UNIT #2 1P60 5000 5000 BLANK G f2 = 2 x L x ISC2(L-L) = 2 x 50 x 14,379 =0.4303 C2 x n x VL-L 13923 x 1 x 240 M2 = 1 = 1 =0.6991 1 + f2 1 + 0.4303 =M2 x ISC2 =0.6991 x 14,379 =10,053 A FAULT CURRENT AT NEW 200A ILC PANEL 'G1A': ISC2 ISC3 M :86LJ:ÑK=>JÑ<:E:I6KFIÑ GIFM>9:JѤ ŽÑ6CGJÑ7LKÑK=:Ñ 86B8LB6K:9ÑBF69Ñ>JѤ Ñ6CGJÑ BF69ÑJ=:9Ñ9:M>8:JÑO>BBÑ7:Ñ I:HL>I:9• G-1 IT IS A VIOLATION OF LAW FOR ANY PERSON, UNLESS THEY ARE ACTING UNDER THE DIRECTION OF A LICENSED PROFESSIONAL ENGINEER, TO ALTER THIS DOCUMENT. SHEET NUMBER: ISSUED FOR: SHEET NAME: SITE NAME: HIBBARD SITE NUMBER: HV1529 SITE ADDRESS: 2525 W. 4000 N REXBURG, ID 83440 JURISDICTION: MADISON COUNTY 10000 PARK MEADOWS DR, SUITE 300 LONE TREE, CO 80124 ORIGINAL DRAWING SIZE: ANSI B, 11.00" X 17.00" DRWNREV DESCRIPTION QADATE OAM 90% COMPLETE CD SET PM05/07/2024 OAM 100% COMPLETE CD SET PM11/15/2024 A 0 1065 POPLAR STREET JOHNSTOWN, CO 80534 GROUNDING PLAN SCALE:PAGE1PLAN: GROUNDING 3/16” = 1’-0”G-1 N EW S NOTES: 1.EXOTHERMIC WELDS SHALL BE USED FOR ALL GROUNDING CONNECTIONS BELOW GRADE. 2.APPROVED ANTIOXIDANT COATINGS (I.E., CONDUCTIVE GEL OR PASTE) SHALL BE USED ON ALL COMPRESSION AND BOLTED GROUND CONNECTIONS. 3.MISCELLANEOUS ELECTRICAL AND NON-ELECTRICAL METAL BOXES, FRAMES AND SUPPORTS SHALL BE BONDED TO THE GROUND RING, IN ACCORDANCE WITH THE NEC. 4.METAL CONDUIT AND TRAY SHALL BE GROUNDED AND MADE ELECTRICALLY CONTINUOUS WITH LISTED BONDING FITTINGS OR BY BONDING ACROSS THE DISCONTINUITY WITH 6 AWG COPPER WIRE AND UL APPROVED GROUNDING TYPE CONDUIT CLAMPS. 5.GROUND CONDUCTORS USED IN THE FACILITY GROUND AND LIGHTNING PROTECTION SYSTEMS SHALL NOT BE ROUTED THROUGH METALLIC OBJECTS THAT FORM A RING AROUND THE CONDUCTOR, SUCH AS METALLIC CONDUITS, METAL SUPPORT CLIPS OR SLEEVES THROUGH WALLS OR FLOORS. WHEN IT IS REQUIRED TO BE HOUSED IN CONDUIT TO MEET CODE REQUIREMENTS OR LOCAL CONDITIONS, NON-METALLIC MATERIAL SUCH AS PVC PLASTIC CONDUIT SHALL BE USED. WHERE USE OF METAL CONDUIT IS UNAVOIDABLE (E.G., NON-METALLIC CONDUIT PROHIBITED BY LOCAL CODE) THE GROUND CONDUCTOR SHALL BE BONDED TO EACH END OF THE METAL CONDUIT. 6.ANY EQUIPMENT, BOX, SKID TO BE GROUNDED AND DOES NOT HAVE A DESIGNATED GROUND CONNECTION SHALL BE DRILLED AS NECESSARY TO CONNECT A GROUND WIRE. REMOVE PAINT IN AREA UNDER LUG. APPLY ANTI-OXIDANT COMPOUND AND CONNECT WITH TWO-HOLE, COMPRESSION LUG. 7.GROUND BARS SHALL BE TINNED COPPER AND SHALL BE ENGRAVED OR IMPRESSED "STOLEN-DO NOT RECYCLE" AND/OR "PROPERTY OF AT&T", ETCHED OR STAMPED WITH SITE FA LOCATION AND SECURED WITH ANTI-THEFT HARDWARE. 8.THE SUBCONTRACTOR SHALL PERFORM IEEE FALL-OF-POTENTIAL RESISTANCE TO EARTH TESTING FOR GROUND ELECTRODE SYSTEMS. TESTING SHALL BE IN ACCORDANCE WITH IEEE STD 81. 9. THE SUBCONTRACTOR SHALL FURNISH AND INSTALL SUPPLEMENTAL GROUND ELECTRODES AS NEEDED TO ACHIEVE A TEST RESULT OF 5 OHMS OR LESS. WHEN ADDING ELECTRODES, CONTRACTOR SHALL MAINTAIN A MINIMUM DISTANCE BETWEEN THE ADDED ELECTRODE AND ANY OTHER EXISTING ELECTRODE EQUAL TO THE BURIED LENGTH OF THE ROD. IDEALLY, CONTRACTOR SHALL STRIVE TO KEEP THE SEPARATION DISTANCE EQUAL TO OR LESS THAN TWICE THE BURIED LENGTH OF THE RODS. 10. METAL RACEWAY SHALL NOT BE USED AS THE NEC REQUIRED EQUIPMENT GROUND CONDUCTOR. STRANDED COPPER CONDUCTORS WITH GREEN INSULATION, SIZED IN ACCORDANCE WITH THE NEC, SHALL BE FURNISHED AND INSTALLED WITH THE POWER CIRCUITS TO BTS EQUIPMENT. 11. ALUMINUM CONDUCTOR OR COPPER CLAD STEEL CONDUCTOR SHALL NOT BE USED FOR GROUNDING CONNECTIONS. 12. EACH INTERIOR COMMUNICATION CABINET FRAME/PLINTH SHALL BE ELECTRICALLY ISOLATED FROM GROUNDS AND SHALL BE DIRECTLY CONNECTED TO THE CELL REFERENCE GROUND BAR WITH 6 AWG OR LARGER STRANDED, GREEN INSULATED GROUND WIRES. 13. GROUND WIRING INSTALLED OUTDOOR EXPOSED SHALL BE 600V, GREEN SUNLIGHT RESISTANT UL LISTED TYPE THW OR THWN OR XHHW, ANNEALED, TINNED, OR UN-TUNNED CLASS B OR CLASS I STRANDED COPPER, SIZE 6 UNLESS OTHERWISE SPECIFIED. 14. GROUND RODS SHOULD BE SPACED AT APPROXIMATELY TWICE THEIR LENGTH AS PER ATT-TP-76416 SPECIFICATIONS. MECHANICAL CONNECTION GROUNDING LEGEND EXOTHERMIC CONNECTION GROUND BAR GROUND WIRE GROUND ROD W/ 5/8"Ø x 8'-0" LONG; MAX. SPACING 16' GROUND ROD W/ TEST WELL (TYP. OF 2) NEW TOWER GROUND BAR SEE DETAILS GROUND GENERATOR FRAME (TYP. OF 2) ICE BRIDGE GROUNDING INTERIOR HALO GROUND RING (X2) ANTENNA, COMMSCOPE NHH-65C-R2B (X1) ANTENNA, ERICSSON AIR6419 B77D (X1) OVP ENCLOSURE, RAYCAP RVZDC-6627-PF-48 (X2) ANTENNA, COMMSCOPE NHH-65C-R2B (X1) ANTENNA/RADIO ERICSSON AIR6419 B77D (X2) ANTENNA, COMMSCOPE NHH-65C-R2B (X1) ANTENNA, ERICSSON AIR6419 B77D (X1) DUAL BAND RADIO, ERICSSON 4490 B5/B13 (X1) DUAL BAND RADIO, ERICSSON 4890 B2/B66 (X1) DUAL BAND RADIO, ERICSSON 4490 B5/B13 (X1) DUAL BAND RADIO, ERICSSON 4890 B2/B66 (X1) DUAL BAND RADIO, ERICSSON 4490 B5/B13 (X1) DUAL BAND RADIO, ERICSSON 4890 B2/B66 SCALE:PAGE2PLAN: ANTENNA GROUNDING 3/16” = 1’-0”G-2 G-2 IT IS A VIOLATION OF LAW FOR ANY PERSON, UNLESS THEY ARE ACTING UNDER THE DIRECTION OF A LICENSED PROFESSIONAL ENGINEER, TO ALTER THIS DOCUMENT. SHEET NUMBER: ISSUED FOR: SHEET NAME: SITE NAME: HIBBARD SITE NUMBER: HV1529 SITE ADDRESS: 2525 W. 4000 N REXBURG, ID 83440 JURISDICTION: MADISON COUNTY 10000 PARK MEADOWS DR, SUITE 300 LONE TREE, CO 80124 ORIGINAL DRAWING SIZE: ANSI B, 11.00" X 17.00" DRWNREV DESCRIPTION QADATE OAM 90% COMPLETE CD SET PM05/07/2024 OAM 100% COMPLETE CD SET PM11/15/2024 A 0 1065 POPLAR STREET JOHNSTOWN, CO 80534 PROPOSED VZW RAD CENTER PLAN & SECTOR ELEVATIONS MECHANICAL CONNECTION GROUNDING LEGEND EXOTHERMIC CONNECTION GROUND BAR GROUND WIRE #6 AWG GROUND CONDUCTOR (TO ANTENNA TYPICAL) (ATTACH PER MANUF. SPECS) SECTOR GROUND BAR (TYP. PER SECTOR), FIELD VERIFY LOCATIONS #6 AWG GROUND CONDUCTOR FROM RRH'S (TYP. EACH UNIT) (ATTACH PER MANUF. SPECS) #2 AWG GROUND CONDUCTOR EXOTHERMICALLY BONDED TO RAYCAP SUPPORT PIPE GROUND BAR, MOUNTED NEAR/BELOW ANTENNA BONDED TO TOWER STEEL OR MONOPOLE. DOWN CONDUCTOR TO GROUND NOT REQUIRED. JUMPER REQUIRED ONLY FOR EASE OF CONNECTION (TYP) AND STRESS REDUCTION ON ANTENNA CONNECTORS CONNECTOR WEATHERPROOFING KIT (TYP) WEATHERPROOFING KIT (TYP) STANDARD GROUND KIT (TYP) (NOTE: 1) ANTENNA CABLE TO BTS (TYP) CONNECTION OF HYBIRD CABLE GROUND WIRE TO GROUND BAR (TOWER/MONOPOLE/ROOFTOP) FROM TMA AND OTHER EQUIPMENT (WHERE APPLICABLE) TO TOWER MOUNTED AMPLIFIER UNITS (TMA) (WHERE APPLICABLE) AND RECEIVE ANTENNA PORTS TO TRANSMIT ANTENNA PORT 6 AWG STRANDED Cu WIRE SUPPLIED WITH KIT OR WITH GREEN, 600V, SUN RESISTANT INSULATION 2 AWG Cu STRANDED WIRE WITH GREEN, 600V, SUN RESISTANT INSULATION TO SITE GROUND (ROOFTOP SITES) NOTES: 1.DO NOT INSTALL CABLE GROUND KIT AT A BEND AND ALWAYS DIRECT GROUND WIRE DOWNWARD. 3/8"-20 HEX BOLT 3/8" FLAT WASHER 3/8" FLAT WASHER 3/8" EXTERNAL TOOTH LOCK WASHER 3/8"-20 HEX NUT 2- HOLE LUG WITH INSPECTION WINDOW #6 GROUND CONDUCTOR INSTALLATION NOTES: 1.SELECT BOLT LENGTHS TO PROVIDE MINIMUM OF 3 EXPOSED THREADS 2.BURNISH MOUNTING SURFACE TO REMOVE PAINT IN THE AREA OF LUG CONTACT 3.APPLY ANTI-OXIDANT COMPOUND TO MATING SURFACE OF LUG AND WIPE CLEAN EXCESS COMPOUND 4.ALL BUSS BARS TO BE CADWELDED, MECHANICAL LUGS ARE PROHIBITED HEAT-SHRINK TUBING, BLACK HARDWARE SCHEDULE CONDUCTOR SIZE BURNDY LUG FASTENER SIZE #6 AWG, GREEN INSULATED YA6C-2TC38 3/8"-16 NC SS, 2 BOLT #2 AWG, SOLD TINNED YA3C-2TC38 3/8"-16 NC SS, 2 BOLT #2 AWG, STRANDED YA2C-2TC38 3/8"-16 NC SS, 2 BOLT #2/0 AWG, STRANDED YA26-2TC38 3/8"-16 NC SS, 2 BOLT #4/0 AWG, STRANDED TA28-2N 1/2"-16 NC SS, 2 BOLT 3/8"-20 HEX BOLT 3/8" FLAT WASHER 3/8" FLAT WASHER 3/8" EXTERNAL TOOTH LOCK WASHER 3/8"-20 HEX NUT 2- HOLE LUG WITH INSPECTION WINDOW HEAT-SHRINK TUBING, CLEAR HARDWARE SCHEDULE CONDUCTOR SIZE BURNDY LUG FASTENER SIZE #6 AWG, GREEN INSULATED YA6C-2TC38 3/8"-16 NC SS, 2 BOLT #2 AWG, SOLD TINNED YA3C-2TC38 3/8"-16 NC SS, 2 BOLT #2 AWG, STRANDED YA2C-2TC38 3/8"-16 NC SS, 2 BOLT #2/0 AWG, STRANDED YA26-2TC38 3/8"-16 NC SS, 2 BOLT #4/0 AWG, STRANDED TA28-2N 1/2"-16 NC SS, 2 BOLT INSTALLATION NOTES: 1.SELECT BOLT LENGTHS TO PROVIDE MINIMUM OF 3 EXPOSED THREADS 2.BURNISH MOUNTING SURFACE TO REMOVE PAINT IN THE AREA OF LUG CONTACT 3.APPLY ANTI-OXIDANT COMPOUND TO MATING SURFACE OF LUG AND WIPE CLEAN EXCESS COMPOUND 4.ALL BUSS BARS TO BE CADWELDED, MECHANICAL LUGS ARE PROHIBITED #6 GROUND CONDUCTOR GROUND BAR SCHEDULE TYPE NC TYPE GT TYPE HATYPE GL LUG TYPE VSTYPE GR TYPE SSTYPE HS TYPE XA TYPE PT TYPE VB TYPE VBC EXTERIOR GROUND RING, 3 AWG SOLID, BARE, TINNED COPPER GROUNDING CONDUCTOR NO SLAG OR DEFORMITIES ALLOWED PARALLEL EXOTHERMIC WELD (CADWELD, THERMOWELD, OR EQUIVALENT) MINIMUM BENDING RADIUS 6 INCHES, (12 INCHES PREFERRED), TYPICAL BRANCH, 2 AWG SOLID, BARE, TINNED COPPER GROUNDING CONDUCTOR G-3 IT IS A VIOLATION OF LAW FOR ANY PERSON, UNLESS THEY ARE ACTING UNDER THE DIRECTION OF A LICENSED PROFESSIONAL ENGINEER, TO ALTER THIS DOCUMENT. SHEET NUMBER: ISSUED FOR: SHEET NAME: SITE NAME: HIBBARD SITE NUMBER: HV1529 SITE ADDRESS: 2525 W. 4000 N REXBURG, ID 83440 JURISDICTION: MADISON COUNTY 10000 PARK MEADOWS DR, SUITE 300 LONE TREE, CO 80124 ORIGINAL DRAWING SIZE: ANSI B, 11.00" X 17.00" DRWNREV DESCRIPTION QADATE OAM 90% COMPLETE CD SET PM05/07/2024 OAM 100% COMPLETE CD SET PM11/15/2024 A 0 1065 POPLAR STREET JOHNSTOWN, CO 80534 GROUNDING DETAILS CADWELD GROUNDING CONNECTIONS 4 INTERIOR GROUND BAR LUG 5 EXTERIOR GROUND BAR LUG 6 NOTE: 1.ERICO EXOTHERMIC "MOLD TYPES" SHOWN HERE ARE EXAMPLES. CONSULT WITH CONSTRUCTION MANAGER FOR SPECIFIC MOLDS TO BE USED FOR THIS PROJECT. 2.MOLD TYPE ONLY TO BE USED BELOW GRADE WHEN C0NNECTING GROUND RING TO GROUND ROD. 6" 1'-0" 1'-0" 3" 2'-0" 2'-6" 3'-0" MIN. 3" CIVIL CONTRACTOR TO COMPLETE FINAL COMPACTION (N) (2) 4" CONDUIT WITH INNERDUCT & (2) PULL STRINGS PER (4 TOTAL) FOR FIBER/TELCO SERVICE (N) CONDUIT FOR POWER, SAND COMPACTED BACKFILL WARNING TAPE 500X MARIFI WEED BARRIER OR EQUIVALENT EXISTING EARTH EXISTING EARTH NEW CRUSHED LIMESTONE PAVING CAD WELD FINAL GRADE FROST LINE GROUNDING ELECTRODE CONDUCTOR LOOP. REFER TO GROUND PLAN FRO NUMBER AND SIZE OF CONNECTIONS. Ø5/8" X 8" LONG MINIMUM GROUND ROD. CONTRACTOR TO COMPLY WITH TOWER GROUNDING REQUIREMENTS FOR SPECIFIC GROUND ROD LENGTH. G-4 IT IS A VIOLATION OF LAW FOR ANY PERSON, UNLESS THEY ARE ACTING UNDER THE DIRECTION OF A LICENSED PROFESSIONAL ENGINEER, TO ALTER THIS DOCUMENT. SHEET NUMBER: ISSUED FOR: SHEET NAME: SITE NAME: HIBBARD SITE NUMBER: HV1529 SITE ADDRESS: 2525 W. 4000 N REXBURG, ID 83440 JURISDICTION: MADISON COUNTY 10000 PARK MEADOWS DR, SUITE 300 LONE TREE, CO 80124 ORIGINAL DRAWING SIZE: ANSI B, 11.00" X 17.00" DRWNREV DESCRIPTION QADATE OAM 90% COMPLETE CD SET PM05/07/2024 OAM 100% COMPLETE CD SET PM11/15/2024 A 0 1065 POPLAR STREET JOHNSTOWN, CO 80534 GROUNDING DETAILS GROUND ROD 1 GROUND ROD WITH TEST WELL 2 LUG DETAIL 3 TYPICAL ANTENNA CABLE GROUNDING 4 TRENCH DETAILS 5 NOT USED 6 NOTE: 1.GROUND ROD TO BE DRIVEN VERTICALLY, NOT TO EXCEED 45 DEGREES FROM VERTICAL 2.GROUND WIRE SHALL BE MIN. 30" BELOW GRADE OR 6" BELOW FROST LINE, WHICH EVER IS GREATER, AS PER NEC ARTICLE 250-50(D) CHERRY INSULATOR INSTALLED IF REQUIRED NOTE: MINIMUM OF 3 THREADS TO BE VISIBLE (TYP) S/S SPLIT WASHER (TYP) S/S FLAT WASHER (TYP) S/S FLAT WASHER (TYP) 2 HOLE LONG BARREL TINNED SOLID COPPER LUG (TYP) S/S NUT (TYP) TIN COATED SOLID COPPER BUS BAR S/S BOLT (TYP) NOTES: 1.NUMBER OF GROUNDING BARS MAY VARY DEPENDING ON THE TYPE OF TOWER, ANTENNA LOCATIONS AND CONNECTION ORIENTATION. COAXIAL CABLES EXCEEDING 200 FEET ON THE TOWER SHALL HAVE GROUND KITS AT THE MIDPOINT. PROVIDE AS REQUIRED. 2.ONLY MECHANICAL CONNECTIONS ARE ALLOWED TO BE MADE TO CROWN CASTLE TOWERS. ALL MECHANICAL CONNECTIONS SHALL BE TREATED WITH AN ANTI-OXIDANT COATING. 3.ALL TOWER GR0UNDING SYSTEMS SHALL COMPLY WITH THE REQUIREMENTS OF ANSI/TIA 222 AND NFPA 780. FOR TOWERS BEING BUILT TO REV G 0F THE STANDARD THE WIRE SIZE OF THE BURIED GROUND RING AND CONNECTIONS BETWEEN THE TOWER AND THE BURIED GROUND RING SHALL BE #2 STRANDED IN ADDITION, THE MINIMUM LENGTH OF THE GROUND RODS SHALL BE INCREASED FROM 8 FEET TO 10 FEET. TO TOWER MOUNTED EQUIPMENT (TYP.) ANTENNA GROUND BAR LOCATED AT MCL (BONDED TO TOWER STEEL) ANTENNA GROUND BAR W/O INSULATORS, BONDED DIRECTLY TO THE BOTTOM OF TOWER WITH STAINLESS STEEL HARDWARE. SEE NOTE 1. MECHANICAL CONNECTION (TYP.) #2 SOLID TINNED BARE COPPER WIRE GROUND RING TO ANTENNA STANDARD COAX CABLE GROUND KIT (TYP.) 6 AWG STRANDED CU WITH GREEN, 600V THWN INSULATION (OR AS PROVIDED WITH GROUNDING KIT, TYP.) COAX CABLE (TYP. FOR ALL) 6 AWG 2 HOLE LUG (TYP.) TO BTS EQUIPMENT VIA TRAY OR ICE BRIDGE GROUND WIRE (NOTE 3) GRADE EXOTHERMIC WELD (TYP.)