Corrections in the following table need to be applied before a permit can be issued
Review Report
Approved
# 25-00003
Page Reference Annotation
Type
Author : Department Status Page Review Comments Applicant Response Comments
E-1 Stamp Alex Owens : Electrical Open 1 Approved - Electrical Inspector
E-4 Callout Alex Owens : Electrical Open 4 Because this generator provides 150 amps but the calculated
load is 188 amps, load shed devices will be required.
E-4 Stamp Alex Owens : Electrical Open 4 Approved - Electrical Inspector
Cell Tower
Approval of plans does not constitute approval of variance from code
EEEEEE
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
F
F
F
F
F
F
F
F
F
E-1
IT IS A VIOLATION OF LAW FOR ANY PERSON,
UNLESS THEY ARE ACTING UNDER THE DIRECTION
OF A LICENSED PROFESSIONAL ENGINEER,
TO ALTER THIS DOCUMENT.
SHEET NUMBER:
ISSUED FOR:
SHEET NAME:
SITE NAME:
HIBBARD
SITE NUMBER:
HV1529
SITE ADDRESS:
2525 W. 4000 N
REXBURG, ID 83440
JURISDICTION:
MADISON COUNTY
10000 PARK MEADOWS DR, SUITE 300
LONE TREE, CO 80124
ORIGINAL DRAWING SIZE: ANSI B, 11.00" X 17.00"
DRWNREV DESCRIPTION QADATE
OAM 90% COMPLETE CD SET PM05/07/2024
OAM 100% COMPLETE CD SET PM11/15/2024
A
0
1065 POPLAR STREET
JOHNSTOWN, CO 80534
UTILITY SITE PLAN
SCALE:PAGE1PLAN: UTILITY SITE
1/128" = 1'-0”E-1
DISCLAIMER:
THESE DRAWINGS WERE PRODUCED WITHOUT THE BENEFIT OF A CURRENT LAND SURVEY. ALL
PROPERTY LINES, EASEMENTS, SETBACKS, AND DIMENSIONS SHOWN SHALL BE VERIFIED
PRIOR TO START OF CONSTRUCTION. TOTAL SITE SERVICES DOES NOT GUARANTEE THE
ACCURACY OF SAID PROPERTY LINES, EASEMENTS, SETBACKS, AND DIMENSIONS SHOWN.
N
EW
S
(E) UTILITY POLE WITH TRANSFORMER AND METER
(E) RAW LAND (E) RAW LAND
(E) OVERHEAD POWER
(P) HORVATH H-FRAME WITH METER
BANK AND FIBER ENCLOSURE
(P) HORVATH 6'-0" CHAINLINK FENCE
(P) HORVATH LEASE AREA,100'-0" X 100'-0"
(P) HORVATH COMPOUND, 55'-0" X 55'-0"
(E) UNDERGROUND FIBER ROUTE
(N) UNDERGROUND PRIMARY
POWER ROUTE
(P) HORVATH 14'-0" ACCESS GATE
(P) HORVATH 12'-0" EASEMENT
(E) BUILDING, TYP.
2
E-2
E
E
E
FF
E
E
E
E
E
E
E
E
E
E
F
F
F
F
F
F
F
F
F
F
F
F
E
E
E
E
E
E
E
E
E
E
E
E E E E
EEEE
E
F
F
F
F
F
F
F
F
F
F
F
F F F F
X
XXXXXXXXXXXXX
X
X
X
X
X
X
X
X
X
X
X
X
X
X X X X X X X X X X X X X
X
X
X
X
X
X
X
X
X
X
X
E-2
IT IS A VIOLATION OF LAW FOR ANY PERSON,
UNLESS THEY ARE ACTING UNDER THE DIRECTION
OF A LICENSED PROFESSIONAL ENGINEER,
TO ALTER THIS DOCUMENT.
SHEET NUMBER:
ISSUED FOR:
SHEET NAME:
SITE NAME:
HIBBARD
SITE NUMBER:
HV1529
SITE ADDRESS:
2525 W. 4000 N
REXBURG, ID 83440
JURISDICTION:
MADISON COUNTY
10000 PARK MEADOWS DR, SUITE 300
LONE TREE, CO 80124
ORIGINAL DRAWING SIZE: ANSI B, 11.00" X 17.00"
DRWNREV DESCRIPTION QADATE
OAM 90% COMPLETE CD SET PM05/07/2024
OAM 100% COMPLETE CD SET PM11/15/2024
A
0
1065 POPLAR STREET
JOHNSTOWN, CO 80534
ELECTRICAL SITE PLAN
SCALE:PAGE2PLAN: ELECTRICAL SITE
1/16” = 1’-0”E-2
N
EW
S
PROPOSED HORVATH LEASE AREA,
100'-0" X 100'-0"
PROPOSED VERIZON 30KW
KOHLER GENERATOR WITH
300GAL DIESEL BELLY TANK
(N) (3) PROPOSED UG CONDUITS,
(1) 1/2", (1) 1", (1) 2",(±15)
PROPOSED 200A ILC/ATS
PROPOSED VERIZON
EQUIPMENT SHELTER
(N) FIBER ENCLOSURE,
24.00" X 24.00" X 12.00"
PROPOSED VERIZON
ICE BRIDGE
(N) (1) PROPOSED 4" UG CONDUIT
WITH (N) (3) 1.25" INNERDUCTS
PROPOSED HORVATH H-FRAME WITH
METER BANK AND FIBER ENCLOSURE
PROPOSED HORVATH 110'-0"
SELF-SUPPORT TOWER WITH
10' LIGHTNING ARRESTOR
PROPOSED HORVATH
14'-0" ACCESS GATE
PROPOSED HORVATH
12'-0" ACCESS ROAD
WITHIN 20'-0" EASEMENT
(E) UG FIBER ROUTE
(N) VERIZON FIBER PULL BOX
(N) FIBER ROUTE FROM (N) FIBER
PULL BOX TO PROPOSED H-FRAME
PROPOSED HORVATH 6'-0"
CHAINLINK FENCE
12'-0"
DIRT ROAD
(N) UG PRIMARY POWER ROUTE
(N) UTILITY PAD MOUNTED TRANSFORMER
PROPOSED VERIZON GPS ANTENNA
3
E-3
(N) 2" SCH 40 PVC UG POWER ROUTE FROM
(N) TRANSFORMER TO (N) METERBANK ON
PROPOSED H-FRAME (±15)
(N) (1) PROPOSED 2" SCH. 40 PVC
UG CONDUIT FROM (N)
METERBANK TO (N) 200A ILC (±50)
E
E
E
E
E
E
E
E
E
E
E
E E E E
EEEE
E
F
F
F
F
F
F
F
F
F
F
F
F F F F
E-3
IT IS A VIOLATION OF LAW FOR ANY PERSON,
UNLESS THEY ARE ACTING UNDER THE DIRECTION
OF A LICENSED PROFESSIONAL ENGINEER,
TO ALTER THIS DOCUMENT.
SHEET NUMBER:
ISSUED FOR:
SHEET NAME:
SITE NAME:
HIBBARD
SITE NUMBER:
HV1529
SITE ADDRESS:
2525 W. 4000 N
REXBURG, ID 83440
JURISDICTION:
MADISON COUNTY
10000 PARK MEADOWS DR, SUITE 300
LONE TREE, CO 80124
ORIGINAL DRAWING SIZE: ANSI B, 11.00" X 17.00"
DRWNREV DESCRIPTION QADATE
OAM 90% COMPLETE CD SET PM05/07/2024
OAM 100% COMPLETE CD SET PM11/15/2024
A
0
1065 POPLAR STREET
JOHNSTOWN, CO 80534
ELECTRICAL PLAN
SCALE:PAGE3PLAN: ELECTRICAL
3/16” = 1’-0”E-3
N
EW
S
PROPOSED VERIZON 30KW
KOHLER GENERATOR WITH
300GAL DIESEL BELLY TANK
(N) (3) PROPOSED UG CONDUITS,
(1) 1/2", (1) 1", (1) 2",(±15)
PROPOSED 200A ILC/ATS
PROPOSED VERIZON EQUIPMENT SHELTER
(N) (1) PROPOSED 2" SCH. 40 PVC
UG CONDUIT FROM (N)
METERBANK TO (N) 200A ILC (±50)
(N) (1) PROPOSED 4" UG CONDUIT
WITH (N) (3) 1.25" INNERDUCTS
PROPOSED HORVATH 110'-0"
SELF-SUPPORT TOWER WITH
10' LIGHTNING ARRESTOR
PROPOSED VERIZON GPS ANTENNA
(N) TRANSPORT RACK
(N) (1) GMT FUSE PANEL
(N) (1) ROUTER
(N) (1) BBU
(N) RAYCAP RACK
(N) (1) 4520 RAYCAP
(N) (1) JMA UPCONVERTER
(N) (1) PDF RACK
(N) (1) -48V PDF
(N) (7) 50A RECTIFIERS
(N) (2) -48V STRINGS OF SAFT TLX180s TO
BE INSTALLED UNDER (N) PDF.
NOTE: VERIZON TO PROVIDE
BATTERY SHELVES
(N) HVAC UNIT
(N) VERIZON ALARM BOARD
PROPOSED VERIZON ICE BRIDGE
PROPOSED (N) (2) 6X12
HYBRID CABLES
(N) FIBER ENCLOSURE,
24.00" X 24.00" X 12.00"
E-4
IT IS A VIOLATION OF LAW FOR ANY PERSON,
UNLESS THEY ARE ACTING UNDER THE DIRECTION
OF A LICENSED PROFESSIONAL ENGINEER,
TO ALTER THIS DOCUMENT.
SHEET NUMBER:
ISSUED FOR:
SHEET NAME:
SITE NAME:
HIBBARD
SITE NUMBER:
HV1529
SITE ADDRESS:
2525 W. 4000 N
REXBURG, ID 83440
JURISDICTION:
MADISON COUNTY
10000 PARK MEADOWS DR, SUITE 300
LONE TREE, CO 80124
ORIGINAL DRAWING SIZE: ANSI B, 11.00" X 17.00"
DRWNREV DESCRIPTION QADATE
OAM 90% COMPLETE CD SET PM05/07/2024
OAM 100% COMPLETE CD SET PM11/15/2024
A
0
1065 POPLAR STREET
JOHNSTOWN, CO 80534
ONE-LINE DIAGRAM
1PANEL SCHEDULE
PANEL NAME PANEL 'G1A'ENCL. TYPE NEMA 3R NOTES:
VOLTAGE RATING 120/240 VAC MOUNTING TYPE SURFACE
CONN. LINE VOLTAGE 240 VAC LOCKABLE CABINET?YES
PHASE 1 WIRE 3 DOOR-IN-DOOR?YES
BUS TYPE MAIN BREAKER MFR.
BUS RATING 200 AMPS MODEL
MAIN BREAKER 200 AMPS CAT. NO.
BREAKER TYPE PLUG-IN SERIES RATED BY MFR?YES
INTERRUPTING RATING 65/10 KAIC FUSE TYPE NA
LOAD POS CB A B CB POS LOAD
1 2
3 4
5 6
7 8
9 10
11 12
13 14
15 16
17 18
19 20
21 22
23 24
19,040 18,880
LOAD TYPE CONN. LOAD NEC D.F.NEC LOAD TOTAL LOAD
RECEPTACLES < 10 KVA 1080 x 100%=1080 45.3 KVA
LIGHTING x 125%=94.4 %
LARGEST MOTOR 10000 x 125%=12500 188.9 AMPS
UNITARY HVAC EQUIPMENT x 100%=
DC RECTIFIERS 14400 x 100%=14400
OTHER 2000 x 100%=2000
TOTAL 42,720 VA VA
25 26
27 28
29 30
31 32
33 34
35 36
37 38
39 40
BLANK
45,330
440 550
1P20
BLANK
-48V RECTIFIER #3
-48V RECTIFIER #2
1200
1200
GFCI RECEPTACLE
1200
1200
BLANK
BLANK
BLANK
BLANK
BLANK
BLANK
BLANK
BLANK
1P15
-48V RECTIFIER #12P30
-48V RECTIFIER #4
-48V RECTIFIER #5
-48V RECTIFIER #6
2P30
2P30
2P30
2P30
2P30
1200
1200
1200
1200
1200
1200
1200
1200
1P20
1P20
GENERAC
ILC
-
GEN. BLOCK HEATER
GEN. BATTERY CHARGER
440
1500
500
180
10000 10000
SPARE2P30
SPARE2P30
SHELTER LIGHTING
BLANK
BLANK
BLANK
BLANK
SHORT CIRCUIT CALCULATIONS
SHORT CIRCUIT CALCULATIONS BASED UPON POINT METHOD AS ILLUSTRATED IN BUSSMAN PUBLICATION SPD-90. FAULT VALUES
SHOWN ARE FOR 3Φ FAULTS ON 3Φ CIRCUITS AND FOR LINE-TO-LINE FAULTS ON 1Φ CIRCUITS.
FAULT CURRENT AT NEW TRANSFORMER SECONDARY :
ISC1 =14,880 A
f1 =
2 x L x ISC1(L-L)
=
2 x 15 x 14,880
=0.0348
C1 x n x VL-L 26706 x 2 x 240
M1 =
1
=
1
=0.9663
1 + f1 1 + 0.0348
=M1 x ISC1 =0.9663 x 14,880 =14,379 A
FAULT CURRENT AT NEW 800A METERBANK:
2
ONE LINE DIAGRAM 3
M M M
900SHELTER RECEPTACLES 1P20
HVAC UNIT #1 1P60 5000
5000
HVAC UNIT #2 1P60 5000
5000
BLANK
G
f2 =
2 x L x ISC2(L-L)
=
2 x 50 x 14,379
=0.4303
C2 x n x VL-L 13923 x 1 x 240
M2 =
1
=
1
=0.6991
1 + f2 1 + 0.4303
=M2 x ISC2 =0.6991 x 14,379 =10,053 A
FAULT CURRENT AT NEW 200A ILC PANEL 'G1A':
ISC2
ISC3
M
:86LJ:ÑK=>JÑ<:E:I6KFIÑ
GIFM>9:JѤÑ6CGJÑ7LKÑK=:Ñ
86B8LB6K:9ÑBF69Ñ>JѤÑ6CGJÑ
BF69ÑJ=:9Ñ9:M>8:JÑO>BBÑ7:Ñ
I:HL>I:9
G-1
IT IS A VIOLATION OF LAW FOR ANY PERSON,
UNLESS THEY ARE ACTING UNDER THE DIRECTION
OF A LICENSED PROFESSIONAL ENGINEER,
TO ALTER THIS DOCUMENT.
SHEET NUMBER:
ISSUED FOR:
SHEET NAME:
SITE NAME:
HIBBARD
SITE NUMBER:
HV1529
SITE ADDRESS:
2525 W. 4000 N
REXBURG, ID 83440
JURISDICTION:
MADISON COUNTY
10000 PARK MEADOWS DR, SUITE 300
LONE TREE, CO 80124
ORIGINAL DRAWING SIZE: ANSI B, 11.00" X 17.00"
DRWNREV DESCRIPTION QADATE
OAM 90% COMPLETE CD SET PM05/07/2024
OAM 100% COMPLETE CD SET PM11/15/2024
A
0
1065 POPLAR STREET
JOHNSTOWN, CO 80534
GROUNDING PLAN
SCALE:PAGE1PLAN: GROUNDING
3/16” = 1’-0”G-1
N
EW
S
NOTES:
1.EXOTHERMIC WELDS SHALL BE USED FOR ALL GROUNDING
CONNECTIONS BELOW GRADE.
2.APPROVED ANTIOXIDANT COATINGS (I.E., CONDUCTIVE GEL OR
PASTE) SHALL BE USED ON ALL COMPRESSION AND BOLTED
GROUND CONNECTIONS.
3.MISCELLANEOUS ELECTRICAL AND NON-ELECTRICAL METAL BOXES,
FRAMES AND SUPPORTS SHALL BE BONDED TO THE GROUND RING,
IN ACCORDANCE WITH THE NEC.
4.METAL CONDUIT AND TRAY SHALL BE GROUNDED AND MADE
ELECTRICALLY CONTINUOUS WITH LISTED BONDING FITTINGS OR
BY BONDING ACROSS THE DISCONTINUITY WITH 6 AWG COPPER
WIRE AND UL APPROVED GROUNDING TYPE CONDUIT CLAMPS.
5.GROUND CONDUCTORS USED IN THE FACILITY GROUND AND
LIGHTNING PROTECTION SYSTEMS SHALL NOT BE ROUTED
THROUGH METALLIC OBJECTS THAT FORM A RING AROUND THE
CONDUCTOR, SUCH AS METALLIC CONDUITS, METAL SUPPORT
CLIPS OR SLEEVES THROUGH WALLS OR FLOORS. WHEN IT IS
REQUIRED TO BE HOUSED IN CONDUIT TO MEET CODE
REQUIREMENTS OR LOCAL CONDITIONS, NON-METALLIC MATERIAL
SUCH AS PVC PLASTIC CONDUIT SHALL BE USED. WHERE USE OF
METAL CONDUIT IS UNAVOIDABLE (E.G., NON-METALLIC CONDUIT
PROHIBITED BY LOCAL CODE) THE GROUND CONDUCTOR SHALL BE
BONDED TO EACH END OF THE METAL CONDUIT.
6.ANY EQUIPMENT, BOX, SKID TO BE GROUNDED AND DOES NOT HAVE
A DESIGNATED GROUND CONNECTION SHALL BE DRILLED AS
NECESSARY TO CONNECT A GROUND WIRE. REMOVE PAINT IN AREA
UNDER LUG. APPLY ANTI-OXIDANT COMPOUND AND CONNECT WITH
TWO-HOLE, COMPRESSION LUG.
7.GROUND BARS SHALL BE TINNED COPPER AND SHALL BE
ENGRAVED OR IMPRESSED "STOLEN-DO NOT RECYCLE" AND/OR
"PROPERTY OF AT&T", ETCHED OR STAMPED WITH SITE FA
LOCATION AND SECURED WITH ANTI-THEFT HARDWARE.
8.THE SUBCONTRACTOR SHALL PERFORM IEEE FALL-OF-POTENTIAL
RESISTANCE TO EARTH TESTING FOR GROUND ELECTRODE
SYSTEMS. TESTING SHALL BE IN ACCORDANCE WITH IEEE STD 81.
9. THE SUBCONTRACTOR SHALL FURNISH AND INSTALL SUPPLEMENTAL
GROUND ELECTRODES AS NEEDED TO ACHIEVE A TEST RESULT OF 5
OHMS OR LESS. WHEN ADDING ELECTRODES, CONTRACTOR SHALL
MAINTAIN A MINIMUM DISTANCE BETWEEN THE ADDED ELECTRODE
AND ANY OTHER EXISTING ELECTRODE EQUAL TO THE BURIED
LENGTH OF THE ROD. IDEALLY, CONTRACTOR SHALL STRIVE TO
KEEP THE SEPARATION DISTANCE EQUAL TO OR LESS THAN TWICE
THE BURIED LENGTH OF THE RODS.
10. METAL RACEWAY SHALL NOT BE USED AS THE NEC REQUIRED
EQUIPMENT GROUND CONDUCTOR. STRANDED COPPER
CONDUCTORS WITH GREEN INSULATION, SIZED IN ACCORDANCE
WITH THE NEC, SHALL BE FURNISHED AND INSTALLED WITH THE
POWER CIRCUITS TO BTS EQUIPMENT.
11. ALUMINUM CONDUCTOR OR COPPER CLAD STEEL CONDUCTOR
SHALL NOT BE USED FOR GROUNDING CONNECTIONS.
12. EACH INTERIOR COMMUNICATION CABINET FRAME/PLINTH SHALL BE
ELECTRICALLY ISOLATED FROM GROUNDS AND SHALL BE DIRECTLY
CONNECTED TO THE CELL REFERENCE GROUND BAR WITH 6 AWG
OR LARGER STRANDED, GREEN INSULATED GROUND WIRES.
13. GROUND WIRING INSTALLED OUTDOOR EXPOSED SHALL BE 600V,
GREEN SUNLIGHT RESISTANT UL LISTED TYPE THW OR THWN OR
XHHW, ANNEALED, TINNED, OR UN-TUNNED CLASS B OR CLASS I
STRANDED COPPER, SIZE 6 UNLESS OTHERWISE SPECIFIED.
14. GROUND RODS SHOULD BE SPACED AT APPROXIMATELY TWICE
THEIR LENGTH AS PER ATT-TP-76416 SPECIFICATIONS.
MECHANICAL CONNECTION
GROUNDING LEGEND
EXOTHERMIC CONNECTION
GROUND BAR
GROUND WIRE
GROUND ROD W/ 5/8"Ø
x 8'-0" LONG; MAX.
SPACING 16'
GROUND ROD W/ TEST
WELL (TYP. OF 2)
NEW TOWER GROUND
BAR SEE DETAILS
GROUND GENERATOR
FRAME (TYP. OF 2)
ICE BRIDGE GROUNDING
INTERIOR HALO
GROUND RING
(X2) ANTENNA,
COMMSCOPE NHH-65C-R2B
(X1) ANTENNA,
ERICSSON AIR6419 B77D
(X1) OVP ENCLOSURE,
RAYCAP RVZDC-6627-PF-48
(X2) ANTENNA,
COMMSCOPE NHH-65C-R2B
(X1) ANTENNA/RADIO
ERICSSON AIR6419 B77D
(X2) ANTENNA,
COMMSCOPE NHH-65C-R2B
(X1) ANTENNA,
ERICSSON AIR6419 B77D
(X1) DUAL BAND RADIO,
ERICSSON 4490 B5/B13
(X1) DUAL BAND RADIO,
ERICSSON 4890 B2/B66
(X1) DUAL BAND RADIO,
ERICSSON 4490 B5/B13
(X1) DUAL BAND RADIO,
ERICSSON 4890 B2/B66
(X1) DUAL BAND RADIO,
ERICSSON 4490 B5/B13
(X1) DUAL BAND RADIO,
ERICSSON 4890 B2/B66
SCALE:PAGE2PLAN: ANTENNA GROUNDING
3/16” = 1’-0”G-2
G-2
IT IS A VIOLATION OF LAW FOR ANY PERSON,
UNLESS THEY ARE ACTING UNDER THE DIRECTION
OF A LICENSED PROFESSIONAL ENGINEER,
TO ALTER THIS DOCUMENT.
SHEET NUMBER:
ISSUED FOR:
SHEET NAME:
SITE NAME:
HIBBARD
SITE NUMBER:
HV1529
SITE ADDRESS:
2525 W. 4000 N
REXBURG, ID 83440
JURISDICTION:
MADISON COUNTY
10000 PARK MEADOWS DR, SUITE 300
LONE TREE, CO 80124
ORIGINAL DRAWING SIZE: ANSI B, 11.00" X 17.00"
DRWNREV DESCRIPTION QADATE
OAM 90% COMPLETE CD SET PM05/07/2024
OAM 100% COMPLETE CD SET PM11/15/2024
A
0
1065 POPLAR STREET
JOHNSTOWN, CO 80534
PROPOSED VZW RAD CENTER
PLAN & SECTOR ELEVATIONS
MECHANICAL CONNECTION
GROUNDING LEGEND
EXOTHERMIC CONNECTION
GROUND BAR
GROUND WIRE
#6 AWG GROUND
CONDUCTOR (TO ANTENNA
TYPICAL)
(ATTACH PER MANUF.
SPECS)
SECTOR GROUND
BAR (TYP. PER
SECTOR), FIELD
VERIFY LOCATIONS
#6 AWG GROUND
CONDUCTOR FROM RRH'S
(TYP. EACH UNIT)
(ATTACH PER MANUF. SPECS)
#2 AWG GROUND
CONDUCTOR
EXOTHERMICALLY BONDED
TO RAYCAP SUPPORT PIPE
GROUND BAR, MOUNTED
NEAR/BELOW ANTENNA BONDED
TO TOWER STEEL OR
MONOPOLE. DOWN CONDUCTOR
TO GROUND NOT REQUIRED.
JUMPER REQUIRED ONLY FOR
EASE OF CONNECTION (TYP)
AND STRESS REDUCTION ON
ANTENNA CONNECTORS
CONNECTOR
WEATHERPROOFING
KIT (TYP)
WEATHERPROOFING KIT (TYP)
STANDARD GROUND KIT (TYP)
(NOTE: 1)
ANTENNA CABLE TO BTS (TYP)
CONNECTION OF HYBIRD CABLE
GROUND WIRE TO GROUND BAR
(TOWER/MONOPOLE/ROOFTOP)
FROM TMA AND OTHER
EQUIPMENT (WHERE APPLICABLE)
TO TOWER MOUNTED
AMPLIFIER UNITS (TMA)
(WHERE APPLICABLE) AND
RECEIVE ANTENNA PORTS
TO TRANSMIT
ANTENNA PORT
6 AWG STRANDED Cu WIRE
SUPPLIED WITH KIT OR WITH
GREEN, 600V, SUN RESISTANT
INSULATION
2 AWG Cu STRANDED WIRE WITH
GREEN, 600V, SUN RESISTANT
INSULATION TO SITE GROUND
(ROOFTOP SITES)
NOTES:
1.DO NOT INSTALL CABLE GROUND
KIT AT A BEND AND ALWAYS DIRECT
GROUND WIRE DOWNWARD.
3/8"-20 HEX BOLT
3/8" FLAT WASHER
3/8" FLAT WASHER
3/8" EXTERNAL TOOTH
LOCK WASHER
3/8"-20 HEX NUT
2- HOLE LUG WITH
INSPECTION WINDOW
#6 GROUND CONDUCTOR
INSTALLATION NOTES:
1.SELECT BOLT LENGTHS TO PROVIDE MINIMUM OF 3
EXPOSED THREADS
2.BURNISH MOUNTING SURFACE TO REMOVE PAINT IN
THE AREA OF LUG CONTACT
3.APPLY ANTI-OXIDANT COMPOUND TO MATING SURFACE
OF LUG AND WIPE CLEAN EXCESS COMPOUND
4.ALL BUSS BARS TO BE CADWELDED, MECHANICAL LUGS
ARE PROHIBITED
HEAT-SHRINK TUBING, BLACK
HARDWARE SCHEDULE
CONDUCTOR SIZE BURNDY LUG FASTENER SIZE
#6 AWG, GREEN INSULATED YA6C-2TC38 3/8"-16 NC SS, 2 BOLT
#2 AWG, SOLD TINNED YA3C-2TC38 3/8"-16 NC SS, 2 BOLT
#2 AWG, STRANDED YA2C-2TC38 3/8"-16 NC SS, 2 BOLT
#2/0 AWG, STRANDED YA26-2TC38 3/8"-16 NC SS, 2 BOLT
#4/0 AWG, STRANDED TA28-2N 1/2"-16 NC SS, 2 BOLT
3/8"-20 HEX BOLT
3/8" FLAT WASHER
3/8" FLAT WASHER
3/8" EXTERNAL TOOTH
LOCK WASHER
3/8"-20 HEX NUT
2- HOLE LUG WITH
INSPECTION WINDOW
HEAT-SHRINK TUBING, CLEAR
HARDWARE SCHEDULE
CONDUCTOR SIZE BURNDY LUG FASTENER SIZE
#6 AWG, GREEN INSULATED YA6C-2TC38 3/8"-16 NC SS, 2 BOLT
#2 AWG, SOLD TINNED YA3C-2TC38 3/8"-16 NC SS, 2 BOLT
#2 AWG, STRANDED YA2C-2TC38 3/8"-16 NC SS, 2 BOLT
#2/0 AWG, STRANDED YA26-2TC38 3/8"-16 NC SS, 2 BOLT
#4/0 AWG, STRANDED TA28-2N 1/2"-16 NC SS, 2 BOLT
INSTALLATION NOTES:
1.SELECT BOLT LENGTHS TO PROVIDE MINIMUM OF 3
EXPOSED THREADS
2.BURNISH MOUNTING SURFACE TO REMOVE PAINT IN
THE AREA OF LUG CONTACT
3.APPLY ANTI-OXIDANT COMPOUND TO MATING SURFACE
OF LUG AND WIPE CLEAN EXCESS COMPOUND
4.ALL BUSS BARS TO BE CADWELDED, MECHANICAL LUGS
ARE PROHIBITED
#6 GROUND CONDUCTOR
GROUND BAR SCHEDULE
TYPE NC
TYPE GT
TYPE HATYPE GL LUG
TYPE VSTYPE GR
TYPE SSTYPE HS
TYPE XA
TYPE PT
TYPE VB
TYPE VBC
EXTERIOR GROUND RING, 3 AWG
SOLID, BARE, TINNED COPPER
GROUNDING CONDUCTOR NO SLAG OR
DEFORMITIES ALLOWED
PARALLEL EXOTHERMIC WELD
(CADWELD, THERMOWELD, OR
EQUIVALENT)
MINIMUM BENDING RADIUS 6 INCHES,
(12 INCHES PREFERRED), TYPICAL
BRANCH, 2 AWG SOLID, BARE, TINNED
COPPER GROUNDING CONDUCTOR
G-3
IT IS A VIOLATION OF LAW FOR ANY PERSON,
UNLESS THEY ARE ACTING UNDER THE DIRECTION
OF A LICENSED PROFESSIONAL ENGINEER,
TO ALTER THIS DOCUMENT.
SHEET NUMBER:
ISSUED FOR:
SHEET NAME:
SITE NAME:
HIBBARD
SITE NUMBER:
HV1529
SITE ADDRESS:
2525 W. 4000 N
REXBURG, ID 83440
JURISDICTION:
MADISON COUNTY
10000 PARK MEADOWS DR, SUITE 300
LONE TREE, CO 80124
ORIGINAL DRAWING SIZE: ANSI B, 11.00" X 17.00"
DRWNREV DESCRIPTION QADATE
OAM 90% COMPLETE CD SET PM05/07/2024
OAM 100% COMPLETE CD SET PM11/15/2024
A
0
1065 POPLAR STREET
JOHNSTOWN, CO 80534
GROUNDING DETAILS
CADWELD GROUNDING CONNECTIONS 4 INTERIOR GROUND BAR LUG 5 EXTERIOR GROUND BAR LUG 6
NOTE:
1.ERICO EXOTHERMIC "MOLD TYPES" SHOWN HERE ARE EXAMPLES. CONSULT WITH
CONSTRUCTION MANAGER FOR SPECIFIC MOLDS TO BE USED FOR THIS PROJECT.
2.MOLD TYPE ONLY TO BE USED BELOW GRADE WHEN C0NNECTING GROUND RING
TO GROUND ROD.
6"
1'-0"
1'-0"
3"
2'-0"
2'-6"
3'-0"
MIN.
3"
CIVIL CONTRACTOR TO
COMPLETE FINAL COMPACTION
(N) (2) 4" CONDUIT WITH INNERDUCT
& (2) PULL STRINGS PER (4 TOTAL)
FOR FIBER/TELCO SERVICE
(N) CONDUIT FOR POWER,
SAND
COMPACTED
BACKFILL
WARNING TAPE
500X MARIFI WEED
BARRIER OR EQUIVALENT
EXISTING
EARTH
EXISTING
EARTH
NEW CRUSHED
LIMESTONE PAVING
CAD WELD
FINAL GRADE
FROST LINE
GROUNDING ELECTRODE
CONDUCTOR LOOP. REFER TO
GROUND PLAN FRO NUMBER
AND SIZE OF CONNECTIONS.
Ø5/8" X 8" LONG MINIMUM GROUND
ROD. CONTRACTOR TO COMPLY WITH
TOWER GROUNDING REQUIREMENTS
FOR SPECIFIC GROUND ROD LENGTH.
G-4
IT IS A VIOLATION OF LAW FOR ANY PERSON,
UNLESS THEY ARE ACTING UNDER THE DIRECTION
OF A LICENSED PROFESSIONAL ENGINEER,
TO ALTER THIS DOCUMENT.
SHEET NUMBER:
ISSUED FOR:
SHEET NAME:
SITE NAME:
HIBBARD
SITE NUMBER:
HV1529
SITE ADDRESS:
2525 W. 4000 N
REXBURG, ID 83440
JURISDICTION:
MADISON COUNTY
10000 PARK MEADOWS DR, SUITE 300
LONE TREE, CO 80124
ORIGINAL DRAWING SIZE: ANSI B, 11.00" X 17.00"
DRWNREV DESCRIPTION QADATE
OAM 90% COMPLETE CD SET PM05/07/2024
OAM 100% COMPLETE CD SET PM11/15/2024
A
0
1065 POPLAR STREET
JOHNSTOWN, CO 80534
GROUNDING DETAILS
GROUND ROD 1 GROUND ROD WITH TEST WELL 2 LUG DETAIL 3
TYPICAL ANTENNA CABLE GROUNDING 4 TRENCH DETAILS 5 NOT USED 6
NOTE:
1.GROUND ROD TO BE DRIVEN VERTICALLY, NOT TO EXCEED 45 DEGREES FROM
VERTICAL
2.GROUND WIRE SHALL BE MIN. 30" BELOW GRADE OR 6" BELOW FROST LINE, WHICH
EVER IS GREATER, AS PER NEC ARTICLE 250-50(D)
CHERRY INSULATOR
INSTALLED IF REQUIRED
NOTE: MINIMUM OF
3 THREADS TO BE
VISIBLE (TYP)
S/S SPLIT
WASHER (TYP)
S/S FLAT
WASHER
(TYP)
S/S FLAT
WASHER
(TYP)
2 HOLE LONG
BARREL TINNED
SOLID COPPER
LUG (TYP)
S/S NUT
(TYP)
TIN COATED SOLID
COPPER BUS BAR
S/S BOLT
(TYP)
NOTES:
1.NUMBER OF GROUNDING BARS MAY VARY DEPENDING ON THE TYPE OF TOWER, ANTENNA
LOCATIONS AND CONNECTION ORIENTATION. COAXIAL CABLES EXCEEDING 200 FEET ON
THE TOWER SHALL HAVE GROUND KITS AT THE MIDPOINT. PROVIDE AS REQUIRED.
2.ONLY MECHANICAL CONNECTIONS ARE ALLOWED TO BE MADE TO CROWN CASTLE TOWERS.
ALL MECHANICAL CONNECTIONS SHALL BE TREATED WITH AN ANTI-OXIDANT COATING.
3.ALL TOWER GR0UNDING SYSTEMS SHALL COMPLY WITH THE REQUIREMENTS OF ANSI/TIA
222 AND NFPA 780. FOR TOWERS BEING BUILT TO REV G 0F THE STANDARD THE WIRE SIZE
OF THE BURIED GROUND RING AND CONNECTIONS BETWEEN THE TOWER AND THE BURIED
GROUND RING SHALL BE #2 STRANDED IN ADDITION, THE MINIMUM LENGTH OF THE GROUND
RODS SHALL BE INCREASED FROM 8 FEET TO 10 FEET.
TO TOWER MOUNTED
EQUIPMENT (TYP.)
ANTENNA GROUND BAR
LOCATED AT MCL
(BONDED TO TOWER STEEL)
ANTENNA GROUND BAR W/O
INSULATORS, BONDED DIRECTLY
TO THE BOTTOM OF TOWER WITH
STAINLESS STEEL HARDWARE.
SEE NOTE 1.
MECHANICAL CONNECTION
(TYP.)
#2 SOLID TINNED
BARE COPPER WIRE
GROUND RING
TO ANTENNA
STANDARD COAX CABLE
GROUND KIT (TYP.)
6 AWG STRANDED CU WITH GREEN,
600V THWN INSULATION (OR AS
PROVIDED WITH GROUNDING KIT, TYP.)
COAX CABLE (TYP. FOR ALL)
6 AWG 2 HOLE LUG (TYP.)
TO BTS EQUIPMENT VIA
TRAY OR ICE BRIDGE
GROUND WIRE
(NOTE 3)
GRADE
EXOTHERMIC WELD (TYP.)