HomeMy WebLinkAboutSTRUCTURAL ENGINEERING - 23-00089 - Manufab - New Commercial ShopFROST Structural Engineering 1020 Lincoln Road Phone: 208.227.8404 Idaho Falls, ID 83401 Fax: 208.227.8405 www.frost-structural.com Report No. : Project : Visit Date: Report Date: To : By : Reference:Observation: It was noted that the Titen HD anchors specified for the steel columns in detail 108 were either cast in place or drilled and epoxied with Simpson Set 3G epoxy with 10" embedment into concrete. We receommend protecting all anchors installed with Simpson Set 3G epoxy from moisture, as moisture can release the bond between the epoxy and the concrete, subjecting the anchor to pulling out. S3.0 No wire rope bracing was observed as noted by keynote 1, see attached photo #1. All wire rope bracing must be installed as noted on plans and shown in details. S2.2 The wood stud wall on the west side of the second floor was observed to have a break approximately midspan of wall with (2) 2x6 plates spanning from the ICF concrete wall to the first steel column, see photo #2. We recommend adding (2) additional 2x6 plates to the existing (2) 2x6 plates and attaching all plys together with 16d nails at 6" on center staggered. We recommend attaching the (4) plates at the ICF wall and at the steel column with (2) Simpson A35 clips per the attached figure #1. It was also observed on the same wall that the several of the studs were broken and spliced together, see photo #2. We recommend replacing these studs with studs spanning from bottom plate to the (4) 2x6 plates at midwall height. S2.2 September 18, 2024 Justin Rasmussen Cody Brian SITE OBSERVATION REPORT 1 (Site Visit) Manufab Building January 1, 2015 102 LincolRLa 102 Linco2dca Phedca :lnLca 8.LLnca 74I FSEFs,D3,x5wfxxrD3t-lhuml%cIu&'(&he 1 of 5 September 17, 2024 FROST Structural Engineering No steel angle bracing as noted in detail 306 was observed. All angle braced must be installed per detail 306 or as otherwise noted previously. S5.0 Provide Simpson DTT2Z holdown as noted in previous observation and per Figure #2 on detail 303, where roof joists attach to ICF concrete wall. S5.0 Note: Many of the items noted here-in may not have been completed at the time of observation due to phase of construction. These items are solely observations made and do not supersede the intent of the original construction documents, unless specifically noted above. No HGA10 clip was observered on joists per detail 201. We recommend ommitting the HGA10 clips noted and replace with a Simpson DTT2Z holdown with a 1/2" diameter anchor rod, drilled and epoxied into ICF concrete wall with Simpson Set 3G epoxy and 6" emebedment into concrete. See the attached Figure #2 or updated detail 201 S4.0 Project Name:Project No. : Eng. : Date : Sheet : CJB FSE09/18/24IF22-187Manufab Building 2 of 5 FROST Structural Engineering Project Name:Project No. : Eng. : Date : Sheet : CJB FSE09/18/24IF22-187Manufab Building Photo #1 - Interior view of roof framing 3 of 5 FROST Structural Engineering Project Name:Project No. : Eng. : Date : Sheet : CJB FSE09/18/24IF22-187Manufab Building Photo #2 - Broken wood stud wall 4 of 5 FROST Structural Engineering Project Name:Project No. : Eng. : Date : Sheet : CJB FSE09/18/24IF22-187Manufab Building KEYNOTES: 1.WOOD JOIST W/ HANGER, SEE PLAN 2.CONT 13 4x117 8 LVL LEDGER W/ SIMPSON ICFVL-CW LEDGER CONNECTOR SYSTEM AT 30" O.C. 3.ICF CONCRETE WALL, SEE PLAN 4.BOUNDARY NAILING, SEE PLAN 5.FLOOR SHEATHING, SEE PLAN 6.SIMPSON HGA10 CLIP AT 48" O.C.. INSTALL PER MANUFACTURER'S INSTRUCTIONS 7.PROVIDE WEB STIFFENER EACH SIDE OF JOIST AT EACH HGA10 CLIP. SEE "TYPICAL WEB STIFFENER REQUIREMENTS" DETAIL 1 2 3 5 201 WOOD JOIST AT ICF CONCRETE WALL NO SCALE 4 6 7 Figure #1 - (4) 2x6 midwall plates at steel column and ICF wall (4) 2x6 PLATES TO SPAN FULL LENGTH FROM STEEL COLUMN TO ICF CONCRETE WALL. ATTACH TOGEHTER W/ 16d NAILS AT 6" O.C. STAGGERED MOUNTING PLATE (EITHER NAILER AT HSS STEEL COLUMN OR ATTACHMENT PLATE AT ICF CONCRETE WALL) ATTACH (4) 2x6 PLATES TO MOUNTING PLATE W/ A35 CLIP TOP AND BOTTOM ((2) CLIPS TOTAL) AT EACH END NO HGA10 REQUIRED EXTEND WEB STIFFENER TO RECEIVE HOLDOWN ATTACHMENT SIMPSON DTT2Z HOLDOWN AT 48" O.C. 1/2"ø THREADED ROD. DRILL AND EPOXY INTO ICF CONCRETE WALL W/ SIMPSON SET 3G EPOXY AND 6" EMBEDMENT INTO CONCRETE 6" PLACE HOLDOWN SO BOTTOM OF HOLDOWN IS 2" MIN AWAY FROM LEDGER (FIGURE #2) 5 of 5