HomeMy WebLinkAboutREDLINED ELECTRICAL PLANS - 23-00089 - Manufab - New Commercial ShopAuthor Name Author Email Author Phone No.: Alex Owens Alex.Owens@rexburg.org 208-372-2172 Description : Address : 2959 Grizzly Ln Application Type : Document Filename : 240802 Manufab Elect Permit.pdf Array Comment Author Contact Information: Corrections in the following table need to be applied before a permit can be issued Review Report Revisions Required Page Reference Annotation Type Author : Department Status Page Review Comments Applicant Response Comments E2.0 MAIN LEVEL POWER Callout Alex Owens : Electrical Open 4 Powder coat booth must comply with article 516 E3.0 MAIN LEVEL MPOWER Callout Alex Owens : Electrical Open 6 Disconnects are not required to be fused as per NEC. Pleas verify E4.1 SCHEDULES Callout Alex Owens : Electrical Open 9 For verification: NEC requires a maximum #4 copper concrete encased electrode # 23-00089 Madison County - Commercial Please digitally re-submit all pages of the plan set in response to requested revisions for our next review cycle, with noted items resolved. Report Date: 08.08.2024 Approval of plans does not constitute approval of variance from code Page 1 of 1 7/24/2024 7/24/2024 7/24/2024 7/24/2024 Powder coat booth must comply with article 516 7/24/2024 7/24/2024 Disconnects are not required to be fused as per NEC. Pleas verify 7/24/2024 7/24/2024 7/24/2024 For verification: NEC requires a maximum #4 copper concrete encased electrode