Loading...
HomeMy WebLinkAboutENGINEER LETTER - 23-00089 - Manufab - New Commercial Shop MUSGROVE ENGINEERING, P.A. 234 S. Whisperwood Way 645 West 25th Street Boise, Idaho 8379 Idaho Falls, Idaho 83402 (208) 384.0585 (208) 523.2862 www.musgrovepa.com OVER 45 YEARS OF ENGINEERING EXCELLENCE Manufab Electrical inspector Comments August 15, 2024 Jeremy Bradley Author ATTENTION: City of Rexburg electrical inspector RE: Manufab Review Comments 1. The owner did have a Ufer ground installed when the slab was poured. A grounding detail has been added to drawing E4.1 showing connection of the Ufer ground to the building grounding system. 2. The owner has requested the change also from fused disconnects to standard disconnects on all rooftop units and the office condensing unit. Musgrove Engineering always designs to this level with fused disconnects for an extra level of protection and for fault current ratings at the devices. 3. The powder coat booth is an item that will be installed in the future. At this time the owner has requested that only the circuit breaker be provided in the electrical panel for the future device. 4. There are other future devices now shown on the drawings that are clouded. At this time all future devices will only have circuit breakers mounted in the panel. All conduit work, conductors and disconnects to future devices to be installed at a later date.