Electrical inspector Comments
August 15, 2024
Jeremy Bradley Author
ATTENTION: City of Rexburg electrical inspector
RE: Manufab Review Comments
1. The owner did have a Ufer ground installed when the slab was poured. A grounding detail has been added to
drawing E4.1 showing connection of the Ufer ground to the building grounding system.
2. The owner has requested the change also from fused disconnects to standard disconnects on all rooftop units and
the office condensing unit. Musgrove Engineering always designs to this level with fused disconnects for an extra
level of protection and for fault current ratings at the devices.
3. The powder coat booth is an item that will be installed in the future. At this time the owner has requested that only
the circuit breaker be provided in the electrical panel for the future device.
4. There are other future devices now shown on the drawings that are clouded. At this time all future devices will only
have circuit breakers mounted in the panel. All conduit work, conductors and disconnects to future devices to be
installed at a later date.