Loading...
HomeMy WebLinkAboutFwd_ Manufab ---------- Forwarded message --------- From: Jeremy B. Bradley <jeremyb@musgrovepa.com <mailto:jeremyb@musgrovepa.com> > Date: Tue, Nov 19, 2024 at 2:26 PM Subject: Manufab To: elkridgeelectric@gmail.com <mailto:elkridgeelectric@gmail.com> <elkridgeelectric@gmail.com <mailto:elkridgeelectric@gmail.com> > Gary, As we discussed the grounding detail that I had placed on the Manufab drawings was our grounding detail that we use in the Jackson Wyoming area and that jurisdiction has a different requirement that has been adopted which uses a #3/0 wire to tie into the Ufer ground. This is above and beyond what we need in Idaho. The way you have installed with a #4 bare copper wire is accepted to tie into the rebar. Thank you. Jeremy Bradley Project Manager MUSGROVE ENGINEERING, P.A. Web: www.musgrovepa.com <http://www.musgrovepa.com/> 645 W. 25 <https://www.google.com/maps/search/645+W.+25?entry=gmail&source=g> th St. Idaho Falls, ID 83402 Ph: 208.523.2862 C: 208.589.0049 Over 40 Years of Engineering Excellence