File Name:
24004D08152024TH
In Place Density of Soils ASTM D2922 & D3017
Date:
08/15/2024
Project Number:
24004
Project Name:
Teton River Temple
Client:
The Church of Jesus Christ of Latter-day Saints
Time Start:
09:00 AM
Contractor:
Depatco
Total Time on Project:
6 hrs
Current Weather Conditions:
Sunny/Clear
Wind:
5-15 mph
Instrument ID
78653
MS:
646
Ambient Temperature (°F):
63
DS:
2660
Results
Test
#:
Location:Elevation: Depth:Material:Wet:Dry:% M:Proctor
#:
%
Proctor:
Result
1 Teton River
St, STA:
64+00 4'
RCL
16"
below
FG
4 Pit Run 135.0 129.7 4.1 134.8 96 Pass
2 Teton River
St, STA:
63+00 6'
LCL
16"
below
FG
4 Pit Run 140.8 132.9 6.0 134.8 99 Pass
3 Teton River
St, STA:
62+00 5'
RCL
16"
below
FG
4 Pit Run 138.4 131.8 5.0 134.8 98 Pass
4 Teton River 16" 4 Pit Run 131.2 127.5 2.9 134.8 95 Pass
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
19884116872ae642-1723733967219 2
Test
#:
Location:Elevation: Depth:Material:Wet:Dry:% M:Proctor
#:
%
Proctor:
Result
St, STA:
65+75 7'
LCL
below
FG
5 West
Church Dr,
STA:
106+00 3'
RCL
16"
below
FG
4 Pit Run 131.7 128.1 2.8 134.8 95 Pass
6 West
Church Dr,
STA:
102+50 6'
LCL
16"
below
FG
4 Pit Run 142.7 137.5 3.8 134.8 102 Pass
7 West
Church Dr,
STA:
109+50 7'
RCL
16"
below
FG
4 Pit Run 135.0 131.3 2.8 134.8 97 Pass
Field Technician Information
Truck
STARLORD
Mileage from Lab to Project (One Way)
13
Total Mileage
57686.00
Tested By:
Travis Hutmacher
Signature:
Items observed are in general conformance with approved project documents and jurisdictional requirements.
Items observed are NOT in general conformance with approved project documents and jurisdictional requirements.
Observations/Remarks:
Arrived on site at 9:00 am. Unpacked the gauge and standardized it. Observed as dump trucks delivered
material, a dozer spread the material and a roller compacted.
Took multiple passing shots and coordinated with the roller operator. Continued to observe workers.
Transitioned to the pile driving pit and made a set of 5 cylinders.
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
19884116872ae642-1723733967219 3
Transitioned back to testing West Church Dr. Observed workers and took multiple passing shots.
Reviewed By:
E. Vail
Signature:
Inspection Images:
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
19884116872ae642-1723733967219 4
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
19884116872ae642-1723733967219 5
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
19884116872ae642-1723733967219 6
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
19884116872ae642-1723733967219 7