Description : Herndon Apartments - Walsh - 4-plex
Address : 263 S 4th W
Application Type :
Document Filename : INFRASTRUCTURE PLAN 7.28.22 - 22-00457 - Herndon Apartments - Walsh - 4-plex - 263 S 4th W.pdf Array
Comment Author Contact Information:
Corrections in the following table need to be applied before a permit can be issued
Review Report
Revisions Required
Page Reference Annotation
Type
Author : Department Status Page Review Comments Applicant Response Comments
PG1 of 1 Free text Todd Smith : Broadband Open 1 As per Resolution 2022-07, adopted April 6, 2022, new
development is required to follow standards for the
installation of fiber conduit and distribution boxes. Location
of conduit and distribution boxes need to be identified and
shown on plans.
PG1 of 1 Free text Stan Crittenden : Fire Open 1 Need to show all access points for driveway
access, widths of driveway, and turning radius
fire department access.
PG1 of 1 Free text Stan Crittenden : Fire Open 1 Need to be able to park the fire truck and reach
anywhere on the structure with a 150 ft. hose.
PG1 of 1 Free text Stan Crittenden : Fire Open 1 Fire Department connection
to the Fire Sprinkler system
will need to be located on
the addressing side of the
building.
# 22-00457
New Multi-Family Residence
Please digitally re-submit all pages of the plan set in response to requested revisions
for our next review cycle, with noted items resolved.
Report Date: 08.15.2022
Approval of plans does not constitute approval of variance from code
Page 1 of 2
Added to drawing.
Added to drawing. Turning
radius not required
Truck would need to pull in driveway 24 feet to reach anywhere on
structure w/in 150'
Sprinkler system not required.
Units are townhouse style.
Page Reference Annotation
Type
Author : Department Status Page Review Comments Applicant Response Comments
PG1 of 1 Free text Stan Crittenden : Fire Open 1 Will need to verify that the
closest fire hydrant is within
150 ft. of the Fire Department
connection on the building.
PG1 of 1 Callout Kyle Baldwin : P&Z Open 1 This setback can be 10' because surrounding parcels are
zoned same (HDR1)
PG1 of 1 Callout Kyle Baldwin : P&Z Open 1 Sidewalk connectivity must be provided from internal
sidewalks to sidewalk in right-of-way.
PG1 of 1 Callout Kyle Baldwin : P&Z Open 1 10' setback required along West Property Line
PG1 of 1 Callout Kyle Baldwin : P&Z Open 1 How many units are in the existing building?
PG1 of 1 Free text Kyle Baldwin : P&Z Open 1 Please show permeable and non-permeable areas for
determination of permissible lot coverage requirement
PG1 of 1 Callout Kyle Baldwin : P&Z Open 1 Please show sidewalk location
PG1 of 1 Callout Kyle Baldwin : P&Z Open 1 Driveway edges and dimensions must be shown
PG1 of 1 Free text Joel Gray : PW Open 1 What area is to be paved?
Where is runoff going from pavement?
Water and sewer services must connect to City main lines.
Report Date: 08.15.2022
Approval of plans does not constitute approval of variance from code
Page 2 of 2
Powered by TCPDF (www.tcpdf.org)
Sprinkler system not required as
noted above. Hydrant locations
noted on plan.
Thanks for letting us know. We moved
4plex back 2' for more space between
buildings.Updated on plan.
Existing building is for one household
See Note B below.
Plan updated
Plan updated
Plan updated
See Note A Below.
Note A. In earlier meetings with the city when we
discussed the lot split Stephen Zollinger required we sign
a document that stated even though the lots are legally
separated they are considered one lot for zoning
requirements. It was filed with the city before the lot was
allowed to be split. This removes the 10' setback
required on the West property line.
Note B. The plan is updated and exceeds the 20% permeable area,
it's 27%. Since we were well above the lower limit we added a pad
for a future shed to hold lawnmower, snow shovels, and other
items.
4T
H
W
E
S
T
SE
T
B
A
C
K
10
'
-
0
"
SETBACK
20' - 0"
SE
T
B
A
C
K
10
'
-
0
"
165' - 0"
80
'
-
0
"
165' - 0"
80
'
-
0
"
75' - 0"90' - 0"
30' - 0"24' - 6"
40
'
-
0
"
12
'
-
0
"
22' - 6"
LO
T
S
P
L
I
T
40
'
-
0
"
4' - 0"9' - 0"9' - 6"
20
'
-
0
"
20
'
-
0
"
24
'
-
0
"
EXISTING
GARAGE TO BE
REMOVED
8' - 0"9' - 0"8' - 0"9' - 0"9' - 0"9' - 0"9' - 0"9' - 0"
1'
-
0
"
23
'
-
0
"
16
'
-
0
"
1A
2A
1W 2W 1X 2X 1Y 2Y 1Z 2Z
17' - 10 1/2"
SIDEWALK
5' - 0"
SIDEWALK
5' - 0"
5' - 0"
14
'
-
0
"
27' - 0"
EXISTING WATER
WATER METER
20
'
-
0
"
EXISTING SEWER LINE
E L E C T R I C A L L I N E
1
1
1
NE
W
S
E
W
E
R
L
I
N
E
NE
W
S
E
W
E
R
L
I
N
E
NEW WATER
1
1
801.455.2080
devin@dswdrafting.com
D
S
W
DRAFTING
Let's create something together
Date
Drawn by
Designed for
Sheet
OF
CCopyright DSW Drafting All rights reserved.
The use of these plans is expressly limited to DSW
Drafting and those who have purchased plans
with a letter of usage. Reproduction,re-use, or publication
by any method, in whole or in part, is prohibited.
REVISED:
7/27/2022 6:00:05 PM
S
I
T
E
P
L
A
N
(slab on grade)
May 2022
DSW
Patrick Walsh
A1.1
20
4-Plex
NOTE:
ADD FENCING AND WATER RETENTION
METHODS TO PREVENT DIRT & DEBRIS FROM
ENTERING STORM DRAINS DURING
CONSTRUCTION
NOTE:
ALL STORM WATER AND DIRT WILL BE KEPT ON SITE DURING
CONSTRUCTION UNTIL FINAL LANDSCAPING IS DONE.
GENERAL CONTRACTOR WILL BE HELD RESPONSIBLE FOR
KEEPING DIRT/MUD ON SITE DURING BAD WEATHER AND FOR
CLEANING UP AFTER SUBCONTRACTORS
THE GRADE AWAY FROM FOUNDATION WALLS SHALL FALL A
MINIMUM OF 6" WITHIN THE FIRST 10 FEET (5%)
STREET, CURB AND GUTTER WILL BE INSPECTED AND
CLEANED OF ALL MUD AND DIRT AT THE END OF EVERY DAY
GRAVEL BAGS TO BE PLACED AND MAINTAINED AROUND
ANY STORM DRAIN INLET ADJACENT TO OR IMMEDIATELY
DOWNSTREAM FROM SITE DURING CONSTRUCTION
SILT FENCES OR BERMS ARE REQUIRED ALONG PROPERTY
LINES TO PREVENT STORM WATER FLOW ONTO ADJACENT
LOTS
ADD EXTERNAL ACCESSIBLE INTERSYSTEM BONDING
TERMINAL FOR THE GROUNDING AND BONDING OF
COMMUNICATIONS SYSTEMS. THIS IS A GROUNDING BUS ON
THE OUTSIDE OF THE ELECTRICAL SERVICE, NOT A UFER
A LINED CONCRETE WASHOUT AREA MUST BE PROVIDED AT
THE SITE FOR ALL CONCRETE WORK. WASHOUT INTO
FOUNDATION OR ON THE GROUND IS PROHIBITED
NOTE:
WINDOW WELLS TO BE A MIN. OF 3" ABOVE
FINISHED GRADE
EXCAVATION-FOUNDATION
VERIFY SEWER DEPTH @ MANHOLE BEFORE
EXCAVATION TO DETERMINE DRIVEWAY SLOPE
REVISION SCHEDULE
No. Description Date
1 ADDED UTILITIES 7.26.22
ADDRESS: 263 S. 4TH WEST
REXBURG, IDAHO
83440
DATE: MAY, 2022
SQUARE FEET: 13,200
NOTE:
GRADE LOT SO SURFACE WATER
IS PREVENTED FROM CROSSING
PROPERTY LINES.
SCALE:1/8" = 1'-0"1 SITE PLAN
Will need to verify that the
closest fire hydrant is within
150 ft. of the Fire Department
connection on the building.
This setback can be 10' because
surrounding parcels are zoned same
(HDR1)
10' setback required along West
Property Line
Need to show all access points for driveway
access, widths of driveway, and turning radius
fire department access.
Please show permeable and non-permeable
areas for determination of permissible lot
coverage requirement
Please show sidewalk location
As per Resolution 2022-07,
adopted April 6, 2022, new
development is required to follow
standards for the installation of
fiber conduit and distribution
boxes. Location of conduit and
distribution boxes need to be
identified and shown on plans.
How many units are in the existing
building?
Driveway edges and dimensions
must be shown
Fire Department connection
to the Fire Sprinkler system
will need to be located on
the addressing side of the
building.
What area is to be paved?
Where is runoff going from pavement?
Water and sewer services must connect to City main lines.
Sidewalk connectivity must be
provided from internal sidewalks to
sidewalk in right-of-way.
Need to be able to park the fire truck and reach
anywhere on the structure with a 150 ft. hose.