Compressive Strength of Concrete Test Specimens
Project Number:
23-255
Cumulative Test Load Amount:
11.0
Project Name:
Married Student Second Stake
Test Location:
Footings on North edge of building
Client:
The Church of Jesus Christ of Latter-day Saints
Admixtures:
MP 322
Contractor:
Alpha Concrete Construction
Supplier:
Walters Ready Mix, Inc.
Mix Number:
W170-F 35
Date:
8/8/2023
Cylinder Log #:
445
Set #:
1
Entrained Air (%):
3.0
Concrete Temperature (°F):
72
Ambient Temperature (°F):
71
Unit Weight (PCF):
147.0
Tested By:
Leland Stiener
Date:
8/8/2023
Picked Up By:
Jense Christensen
Pick Up Date:
8/9/2023
Pick Up Time:
1:45 PM
Max, Min Temperature:
80,60
Compressive Strength Data
Previous Test Results:
Cylinder ID:Break Age:Break Date:Area (in^2):Maximum Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
A 7 8/15/2023 12.57 39360 3131 3,000.00 Type 1
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
7F53AC33-A7B0-485F-95D3-52DBC693CE1F 2
Current Break Testing:
Cylinder
ID:
Break
Age:
Break
Date:
Diameter
(in):
Area
(in^2):
Maximum
Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
B 28 9/5/2023 4.000 12.57 55195.0 4391 3000.0 Type 6
C 28 9/5/2023 4.000 12.57 54470.0 4333 3000.0 Type 3
D 28 9/5/2023 4.000 12.57 55995.0 4455 3000.0 Type 3
Second Break Average:
4393
Date:
09/05/2023
Reviewed By:
Luke Hammar
Signature:
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
F39E3D37-D651-48D9-AA81-B8618D133D91 1
4103 E 605 N Suite 1
Rigby, ID 83442
208.932.4428
File name:
23255SB07032024MS
Compressive Strength of Concrete Test Specimens
Project Number:
23-255
Cumulative Test Load Amount:
9
Project Name:
Married Student Second Stake
Test Location:
Northeast corner of northeast utility pad.
Client:
The Church of Jesus Christ of Latter-day Saints
Admixtures:
N/A
Contractor:
Okland Construction
Supplier:
Walters Ready Mix, Inc.
Mix Number:
4500AF
Date:
6/4/2024
Cylinder Log #:
351
Set #:
1
Entrained Air (%):
4.9
Concrete Temperature (°F):
69
Ambient Temperature (°F):
71
Unit Weight (PCF):
140.6
Tested By:
Tyler Jones
Date:
6/4/2024
Picked Up By:
Michelle S.
Pick Up Date:
6/6/2024
Pick Up Time:
1:52 PM
Max, Min Temperature:
75,63
Compressive Strength Data
Previous Test Results:
Cylinder ID:Break Age:Break Date:Area (in^2):Maximum Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
A 7 6/12/2024 12.57 47595 3786 3,000.00 1
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
F39E3D37-D651-48D9-AA81-B8618D133D91 2
Current Break Testing:
Cylinder
ID:
Break
Age:
Break
Date:
Diameter
(in):
Area
(in^2):
Maximum
Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
B 28 7/3/2024 4.000 12.57 61,975.0 4930 3,000.0 Type 1
C 28 7/3/2024 4.000 12.57 62,905.0 5004 3,000.0 Type 1
D 28 7/3/2024 4.000 12.57 62,770.0 4994 3,000.0 Type 1
Second Break Average:
4976
Date:
07/10/2024
Reviewed By:
Luke Hammar
Signature:
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
7277D0EA-A23F-4703-AE64-016DC631A399 1
4103 E 605 N Suite 1
Rigby, ID 83442
208.932.4428
File name:
23255SB07092024LSH
Compressive Strength of Concrete Test Specimens
Project Number:
23-255
Cumulative Test Load Amount:
9
Project Name:
Married Student Second Stake
Test Location:
Curb on south west corner of building
Client:
The Church of Jesus Christ of Latter-day Saints
Admixtures:
Air entrainment
Contractor:
Rad Crete
Supplier:
Walters Ready Mix
Mix Number:
4500AF
Date:
7/2/2024
Cylinder Log #:
474
Set #:
1
Entrained Air (%):
5.0
Concrete Temperature (°F):
70
Ambient Temperature (°F):
61
Unit Weight (PCF):
141.6
Tested By:
Leland Steiner
Date:
7/2/2024
Picked Up By:
Michelle S.
Pick Up Date:
7/3/2024
Pick Up Time:
3:54 PM
Max, Min Temperature:
74,60
Compressive Strength Data
Previous Test Results:
Cylinder ID:Break Age:Break Date:Area (in^2):Maximum Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
B 5 7/7/2024 12.57 50035 3981 3,000.00 2
C 6 7/8/2024 12.57 53395 4248 3,000.00 2
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
7277D0EA-A23F-4703-AE64-016DC631A399 2
Current Break Testing:
Cylinder
ID:
Break
Age:
Break
Date:
Diameter
(in):
Area
(in^2):
Maximum
Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
D 7 7/9/2024 4.000 12.57 54,965.0 4373 3,000.0 Type 1
Second Break Average:
4373
Date:
07/10/2024
Reviewed By:
Luke Hammar
Signature:
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
FC40CD35-A38D-49A8-AF58-819AD79BAA87 1
4103 E 605 N Suite 1
Rigby, ID 83442
208.932.4428
File name:
23255SB07232024MS
Compressive Strength of Concrete Test Specimens
Project Number:
23-255
Cumulative Test Load Amount:
10
Project Name:
Married Student Second Stake
Test Location:
SE corner of lot curb
Client:
The Church of Jesus Christ of Latter-day Saints
Admixtures:
AE-90, 322 N
Contractor:
Radcrete
Supplier:
Walters Ready Mix
Mix Number:
4500AF 10WC51
Date:
6/25/2024
Cylinder Log #:
443
Set #:
1
Entrained Air (%):
4.5
Concrete Temperature (°F):
72
Ambient Temperature (°F):
57
Unit Weight (PCF):
141.6
Tested By:
James Russo
Date:
6/25/2024
Picked Up By:
Michelle S.
Pick Up Date:
6/26/2024
Pick Up Time:
11:54 AM
Max, Min Temperature:
75,61
Compressive Strength Data
Previous Test Results:
Cylinder ID:Break Age:Break Date:Area (in^2):Maximum Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
A 7 7/2/2024 12.57 63855 5080 3,000.00 1
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
FC40CD35-A38D-49A8-AF58-819AD79BAA87 2
Current Break Testing:
Cylinder
ID:
Break
Age:
Break
Date:
Diameter
(in):
Area
(in^2):
Maximum
Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
B 28 7/23/2024 4.000 12.57 77,960.0 6202 3,000.0 Type 3
C 28 7/23/2024 4.000 12.57 80,005.0 6365 3,000.0 Type 2
D 28 7/23/2024 4.000 12.57 78,065.0 6210 3,000.0 Type 2
Second Break Average:
6259
Date:
07/23/2024
Reviewed By:
Luke Hammar
Signature:
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
90C33423-3580-4AEC-8874-BE9C3A9B926E 1
4103 E 605 N Suite 1
Rigby, ID 83442
208.932.4428
File name:
23255SB07242024MS
Compressive Strength of Concrete Test Specimens
Project Number:
23-255
Cumulative Test Load Amount:
10
Project Name:
Married Student Second Stake
Test Location:
Sidewalk curb 50 ft E of NE corner of bullding
Client:
The Church of Jesus Christ of Latter-day Saints
Admixtures:
Air
Contractor:
Alpha Concrete Construction
Supplier:
Walters Ready Mix
Mix Number:
4500AF 10WC187
Date:
6/26/2024
Cylinder Log #:
451
Set #:
1
Entrained Air (%):
6.4
Concrete Temperature (°F):
77
Ambient Temperature (°F):
62
Unit Weight (PCF):
138
Tested By:
James Russo
Date:
6/26/2024
Picked Up By:
Michelle S.
Pick Up Date:
6/27/2024
Pick Up Time:
10:21 AM
Max, Min Temperature:
78,62
Compressive Strength Data
Previous Test Results:
Cylinder ID:Break Age:Break Date:Area (in^2):Maximum Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
A 7 7/3/2024 12.57 50525 4019 4,000.00 1
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
90C33423-3580-4AEC-8874-BE9C3A9B926E 2
Current Break Testing:
Cylinder
ID:
Break
Age:
Break
Date:
Diameter
(in):
Area
(in^2):
Maximum
Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
B 28 7/24/2024 4.000 12.57 55,500.0 4415 4,000.0 Type 2
C 28 7/24/2024 4.000 12.57 54,750.0 4356 4,000.0 Type 1
D 28 7/24/2024 4.000 12.57 56,915.0 4528 4,000.0 Type 5
Second Break Average:
4279
Date:
07/24/2024
Reviewed By:
Luke Hammar
Signature:
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
CEA3EDE2-7F27-45BC-9A38-63AE187928D0 1
4103 E 605 N Suite 1
Rigby, ID 83442
208.932.4428
File name:
23255SB07302024MS
Compressive Strength of Concrete Test Specimens
Project Number:
23-255
Cumulative Test Load Amount:
9
Project Name:
Married Student Second Stake
Test Location:
Curb on south west corner of building
Client:
The Church of Jesus Christ of Latter-day Saints
Admixtures:
Air entrainment
Contractor:
Rad Crete
Supplier:
Walters Ready Mix
Mix Number:
4500AF
Date:
7/2/2024
Cylinder Log #:
474
Set #:
1
Entrained Air (%):
5.0
Concrete Temperature (°F):
70
Ambient Temperature (°F):
61
Unit Weight (PCF):
141.6
Tested By:
Leland Steiner
Date:
7/2/2024
Picked Up By:
Michelle S.
Pick Up Date:
7/3/2024
Pick Up Time:
3:54 PM
Max, Min Temperature:
74,60
Compressive Strength Data
Previous Test Results:
Cylinder ID:Break Age:Break Date:Area (in^2):Maximum Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
B 5 7/7/2024 12.57 50035 3981 3,000.00 2
C 6 7/8/2024 12.57 53395 4248 3,000.00 2
D 7 7/9/2024 12.57 54965 4373 3,000.00 1
A 4 7/6/2024 12.57 0 3,000.00
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
CEA3EDE2-7F27-45BC-9A38-63AE187928D0 2
Current Break Testing:
Cylinder
ID:
Break
Age:
Break
Date:
Diameter
(in):
Area
(in^2):
Maximum
Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
E 28 7/30/2024 4.000 12.57 68,080.0 5416 3,000.0 Type 1
F 28 7/30/2024 4.000 12.57 61,295.0 4876 3,000.0 Type 5
G 28 7/30/2024 4.000 12.57 64,585.0 5138 3,000.0 Type 2
Second Break Average:
5143
Date:
07/30/2024
Reviewed By:
Luke Hammar
Signature:
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
FF2D923C-DC97-48C9-8215-2E74B7DD7927 1
4103 E 605 N Suite 1
Rigby, ID 83442
208.932.4428
File name:
23255SB08072023JPC
Compressive Strength of Concrete Test Specimens
Project Number:
23-255
Cumulative Test Load Amount:
10
Project Name:
Married Student Second Stake
Test Location:
Southern foundation walls
Client:
The Church of Jesus Christ of Latter-day Saints
Admixtures:
DELVO, MP322, MA AE 90
Contractor:
Headwaters Construction
Supplier:
Walters Concrete
Mix Number:
4500AF-45
Date:
8/1/2023
Cylinder Log #:
432
Set #:
1
Entrained Air (%):
5.0
Concrete Temperature (°F):
73
Ambient Temperature (°F):
87
Unit Weight (PCF):
140.6
Tested By:
Mark Mansfield
Date:
8/1/2023
Picked Up By:
Pick Up Date:
Pick Up Time:
Max, Min Temperature:
Compressive Strength Data
Previous Test Results:
Cylinder ID:Break Age:Break Date:Area (in^2):Maximum Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
A 3 8/4/2023 12.57 57040 4538 4,500.00 Type 1
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
FF2D923C-DC97-48C9-8215-2E74B7DD7927 2
Current Break Testing:
Cylinder
ID:
Break
Age:
Break
Date:
Diameter
(in):
Area
(in^2):
Maximum
Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
B 6 8/7/2023 4.000 12.57 66,285.0 5273 4,500.0 Type 3
Second Break Average:
5273
Date:
08/08/2023
Reviewed By:
Luke Hammar
Signature:
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
612B66D8-5C11-4342-AFAA-1571F2451939 1
4103 E 605 N Suite 1
Rigby, ID 83442
208.932.4428
File name:
23255SB08082023JPC
Compressive Strength of Concrete Test Specimens
Project Number:
23-255
Cumulative Test Load Amount:
10
Project Name:
Married Student Second Stake
Test Location:
Southern foundation walls
Client:
The Church of Jesus Christ of Latter-day Saints
Admixtures:
DELVO, MP322, MA AE 90
Contractor:
Headwaters Construction
Supplier:
Walters Concrete
Mix Number:
4500AF-45
Date:
8/1/2023
Cylinder Log #:
432
Set #:
1
Entrained Air (%):
5.0
Concrete Temperature (°F):
73
Ambient Temperature (°F):
87
Unit Weight (PCF):
140.6
Tested By:
Mark Mansfield
Date:
8/1/2023
Picked Up By:
Luke Hammar
Pick Up Date:
8/2/2023
Pick Up Time:
8:19 AM
Max, Min Temperature:
80,60
Compressive Strength Data
Previous Test Results:
Cylinder ID:Break Age:Break Date:Area (in^2):Maximum Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
A 3 8/4/2023 12.57 57040 4538 4,500.00 Type 1
B 6 8/7/2023 12.57 66285 5273 4,500.00 Type 3
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
612B66D8-5C11-4342-AFAA-1571F2451939 2
Current Break Testing:
Cylinder
ID:
Break
Age:
Break
Date:
Diameter
(in):
Area
(in^2):
Maximum
Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
C 7 8/8/2023 4.000 12.57 70,860.0 5637 4,500.0 Type 1
Second Break Average:
5637
Date:
08/09/2023
Reviewed By:
Luke Hammar
Signature:
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
8646AB0D-50FE-423A-861B-F59D79264536 1
4103 E 605 N Suite 1
Rigby, ID 83442
208.932.4428
File name:
23255SB08152023JPC
Compressive Strength of Concrete Test Specimens
Project Number:
23-255
Cumulative Test Load Amount:
10.0
Project Name:
Married Student Second Stake
Test Location:
Southern foundation walls
Client:
The Church of Jesus Christ of Latter-day Saints
Admixtures:
DELVO, MP322, MA AE 90
Contractor:
Headwaters Construction
Supplier:
Walters Concrete
Mix Number:
4500AF-45
Date:
8/1/2023
Cylinder Log #:
432
Set #:
1
Entrained Air (%):
5.0
Concrete Temperature (°F):
73
Ambient Temperature (°F):
87
Unit Weight (PCF):
140.6
Tested By:
Mark Mansfield
Date:
8/1/2023
Picked Up By:
Luke Hammar
Pick Up Date:
8/2/2023
Pick Up Time:
8:19 AM
Max, Min Temperature:
80,60
Compressive Strength Data
Previous Test Results:
Cylinder ID:Break Age:Break Date:Area (in^2):Maximum Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
A 3 8/4/2023 12.57 57040 4538 4,500.00 Type 1
B 6 8/7/2023 12.57 66285 5273 4,500.00 Type 3
C 7 8/8/2023 12.57 70860 5637 4,500.00 Type 1
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
8646AB0D-50FE-423A-861B-F59D79264536 2
Current Break Testing:
Cylinder
ID:
Break
Age:
Break
Date:
Diameter
(in):
Area
(in^2):
Maximum
Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
D 14 8/15/2023 4.000 12.57 75,180.0 5981 4,500.0 Type 1
Second Break Average:
5981
Date:
08/16/2023
Reviewed By:
E. Vail
Signature:
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
42B23C25-95B2-4F4D-9A84-1B95F94A2881 1
4103 E 605 N Suite 1
Rigby, ID 83442
208.932.4428
File name:
23255SB08222023MDH
Compressive Strength of Concrete Test Specimens
Project Number:
23-255
Cumulative Test Load Amount:
8.5
Project Name:
Married Student Second Stake
Test Location:
F-1
Client:
The Church of Jesus Christ of Latter-day Saints
Admixtures:
MP 322
Contractor:
Alpha Concrete Construction
Supplier:
Walters Ready Mix
Mix Number:
W170-F 35
Date:
7/25/2023
Cylinder Log #:
418
Set #:
1
Entrained Air (%):
2.0
Concrete Temperature (°F):
80
Ambient Temperature (°F):
86
Unit Weight (PCF):
139.8
Tested By:
Bryce Choffin
Date:
7/25/2023
Picked Up By:
B. Choffin
Pick Up Date:
7/26/2023
Pick Up Time:
8:10 AM
Max, Min Temperature:
80, 60
Compressive Strength Data
Previous Test Results:
Cylinder ID:Break Age:Break Date:Area (in^2):Maximum Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
A 7 8/1/2023 12.57 44105 3509 3,000.00 Type 2
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
42B23C25-95B2-4F4D-9A84-1B95F94A2881 2
Current Break Testing:
Cylinder
ID:
Break
Age:
Break
Date:
Diameter
(in):
Area
(in^2):
Maximum
Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
B 28 8/22/2023 4.000 12.57 51085.0 4064 3000.0 Type 1
C 28 8/22/2023 4.000 12.57 50185.0 3992 3000.0 Type 1
D 28 8/22/2023 4.000 12.57 52610.0 4185 3000.0 Type 2
Second Break Average:
4080
Date:
08/23/2023
Reviewed By:
Luke Hammar
Signature:
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
EE41CFF8-50CB-400D-A902-F589695D4B79 1
4103 E 605 N Suite 1
Rigby, ID 83442
208.932.4428
File name:
23255SB08292023LSH
Compressive Strength of Concrete Test Specimens
Project Number:
23-255
Cumulative Test Load Amount:
10.0
Project Name:
Married Student Second Stake
Test Location:
Southern foundation walls
Client:
The Church of Jesus Christ of Latter-day Saints
Admixtures:
DELVO, MP322, MA AE 90
Contractor:
Headwaters Construction
Supplier:
Walters Concrete
Mix Number:
4500AF-45
Date:
8/1/2023
Cylinder Log #:
432
Set #:
1
Entrained Air (%):
5.0
Concrete Temperature (°F):
73
Ambient Temperature (°F):
87
Unit Weight (PCF):
140.6
Tested By:
Mark Mansfield
Date:
8/1/2023
Picked Up By:
Luke Hammar
Pick Up Date:
8/2/2023
Pick Up Time:
8:19 AM
Max, Min Temperature:
80,60
Compressive Strength Data
Previous Test Results:
Cylinder ID:Break Age:Break Date:Area (in^2):Maximum Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
A 3 8/4/2023 12.57 57040 4538 4,500.00 Type 1
B 6 8/7/2023 12.57 66285 5273 4,500.00 Type 3
C 7 8/8/2023 12.57 70860 5637 4,500.00 Type 1
D 14 8/15/2023 12.57 75180 5981 4,500.00 Type 1
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
EE41CFF8-50CB-400D-A902-F589695D4B79 2
Current Break Testing:
Cylinder
ID:
Break
Age:
Break
Date:
Diameter
(in):
Area
(in^2):
Maximum
Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
E 28 8/29/2023 4.000 12.57 77060.0 6130 4500.0 Type 1
F 28 8/29/2023 4.000 12.57 80380.0 6395 4500.0 Type 1
G 28 8/29/2023 4.000 12.57 77800.0 6189 4500.0 Type 1
Second Break Average:
6238
Date:
08/30/2023
Reviewed By:
Luke Hammar
Signature:
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
0E4C995A-5AEB-4351-A237-07310BAF7332 1
4103 E 605 N Suite 1
Rigby, ID 83442
208.932.4428
File name:
23255SB08312023MDH
Compressive Strength of Concrete Test Specimens
Project Number:
23-255
Cumulative Test Load Amount:
9.8
Project Name:
Married Student Second Stake
Test Location:
Southwest corner of building, foundation walls
Client:
The Church of Jesus Christ of Latter-day Saints
Admixtures:
DELVO, MP 322, MA AE 90
Contractor:
Alpha Concrete Construction
Supplier:
Walters Ready Mix, Inc.
Mix Number:
4500AF-45
Date:
8/3/2023
Cylinder Log #:
434
Set #:
1
Entrained Air (%):
5.5
Concrete Temperature (°F):
80
Ambient Temperature (°F):
70
Unit Weight (PCF):
138.6
Tested By:
Michael Hammar
Date:
8/3/2023
Picked Up By:
L. Steiner
Pick Up Date:
8/4/2023
Pick Up Time:
11:31 AM
Max, Min Temperature:
79.6,60
Compressive Strength Data
Previous Test Results:
Cylinder ID:Break Age:Break Date:Area (in^2):Maximum Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
A 7 8/10/2023 12.57 46130 3670 4,500.00 Type 3
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
0E4C995A-5AEB-4351-A237-07310BAF7332 2
Current Break Testing:
Cylinder
ID:
Break
Age:
Break
Date:
Diameter
(in):
Area
(in^2):
Maximum
Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
B 28 8/31/2023 4.000 12.57 58115.0 4623 4500.0 Type 3
C 28 8/31/2023 4.000 12.57 57965.0 4611 4500.0 Type 1
D 28 8/31/2023 4.000 12.57 57445.0 4570 4500.0 Type 3
Second Break Average:
4601
Date:
09/01/2023
Reviewed By:
Luke Hammar
Signature:
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
83C84CDD-086F-4776-B4F3-A9082F4D48BD 1
4103 E 605 N Suite 1
Rigby, ID 83442
208.932.4428
File name:
23255SB09192023MDH
Compressive Strength of Concrete Test Specimens
Project Number:
23-255
Cumulative Test Load Amount:
10.0
Project Name:
Married Student Second Stake
Test Location:
Footings for interior of building on south half
Client:
The Church of Jesus Christ of Latter-day Saints
Admixtures:
MP 322
Contractor:
Alpha Concrete
Supplier:
Walters Ready Mix, Inc.
Mix Number:
W170-F 35
Date:
8/22/2023
Cylinder Log #:
488
Set #:
1
Entrained Air (%):
1.4
Concrete Temperature (°F):
71
Ambient Temperature (°F):
80
Unit Weight (PCF):
145.0
Tested By:
Leland Stiener
Date:
8/22/2023
Picked Up By:
Matthew Hammar
Pick Up Date:
8/23/2023
Pick Up Time:
11:17 AM
Max, Min Temperature:
80, 60
Compressive Strength Data
Previous Test Results:
Cylinder ID:Break Age:Break Date:Area (in^2):Maximum Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
A 7 8/29/2023 12.57 41770 3323 3000 Type 1
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
83C84CDD-086F-4776-B4F3-A9082F4D48BD 2
Current Break Testing:
Cylinder
ID:
Break
Age:
Break
Date:
Diameter
(in):
Area
(in^2):
Maximum
Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
B 28 9/19/2023 4.000 12.57 54910.0 4368 3000.0 Type 1
C 28 9/19/2023 4.000 12.57 55840.0 4442 3000.0 Type 1
D 28 9/19/2023 4.000 12.57 56045.0 4459 3000.0 Type 6
Second Break Average:
4423
Date:
09/22/2023
Reviewed By:
Luke Hammar
Signature:
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
EFA7DA78-DBB8-425B-9BA2-0BF168AC6554 1
4103 E 605 N Suite 1
Rigby, ID 83442
208.932.4428
File name:
23255SB09192024MS
Compressive Strength of Concrete Test Specimens
Project Number:
23-255
Cumulative Test Load Amount:
10
Project Name:
Married Student Second Stake
Test Location:
43.8032400, -111.7970208
Client:
The Church of Jesus Christ of Latter-day Saints
Admixtures:
AE-90 171.0, 322 N 328.0
Contractor:
Rad Crete
Supplier:
Walters Ready Mix, Inc.
Mix Number:
4500AF
Date:
8/22/2024
Cylinder Log #:
657
Set #:
1
Entrained Air (%):
5.0
Concrete Temperature (°F):
67
Ambient Temperature (°F):
58
Unit Weight (PCF):
142
Tested By:
Nathaniel Speas
Date:
8/22/2024
Picked Up By:
Michelle S.
Pick Up Date:
8/23/2024
Pick Up Time:
1:46 PM
Max, Min Temperature:
75,62
Compressive Strength Data
Previous Test Results:
Cylinder ID:Break Age:Break Date:Area (in^2):Maximum Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
A 7 8/29/2024 12.57 63150 5024 3,000.00 1
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
EFA7DA78-DBB8-425B-9BA2-0BF168AC6554 2
Current Break Testing:
Cylinder
ID:
Break
Age:
Break
Date:
Diameter
(in):
Area
(in^2):
Maximum
Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
B 28 9/19/2024 4.000 12.57 76,060.0 6051 3,000.0 Type 2
C 28 9/19/2024 4.000 12.57 71,585.0 5695 3,000.0 Type 2
D 28 9/19/2024 4.000 12.57 74,660.0 5940 3,000.0 Type 1
Second Break Average:
5895
Date:
09/20/2024
Reviewed By:
Luke Hammar
Signature:
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
DD1D6409-2C8B-4187-90DC-425C09BC7EF6 1
4103 E 605 N Suite 1
Rigby, ID 83442
208.932.4428
File name:
23255SB09212023MDH
Compressive Strength of Concrete Test Specimens
Project Number:
23-255
Cumulative Test Load Amount:
22.0
Project Name:
Married Student Second Stake
Test Location:
Interior footing on west side of building
Client:
The Church of Jesus Christ of Latter-day Saints
Admixtures:
MP 322
Contractor:
Alpha Concrete
Supplier:
Walters Ready Mix, Inc
Mix Number:
W170-F 35
Date:
8/24/2023
Cylinder Log #:
498
Set #:
1
Entrained Air (%):
1.8
Concrete Temperature (°F):
76
Ambient Temperature (°F):
99
Unit Weight (PCF):
146.0
Tested By:
Leland Steiner
Date:
8/24/2023
Picked Up By:
L. Steiner
Pick Up Date:
8/25/2023
Pick Up Time:
10:41 AM
Max, Min Temperature:
70,60
Compressive Strength Data
Previous Test Results:
Cylinder ID:Break Age:Break Date:Area (in^2):Maximum Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
A 7 8/31/2023 12.57 47570 3784 3000 Type 1
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
DD1D6409-2C8B-4187-90DC-425C09BC7EF6 2
Current Break Testing:
Cylinder
ID:
Break
Age:
Break
Date:
Diameter
(in):
Area
(in^2):
Maximum
Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
B 28 9/21/2023 4.000 12.57 53565.0 4261 3000.0 Type 3
C 28 9/21/2023 4.000 12.57 56130.0 4465 3000.0 Type 3
D 28 9/21/2023 4.000 12.57 56780.0 4517 3000.0 Type 3
Second Break Average:
4414
Date:
09/22/2023
Reviewed By:
Luke Hammar
Signature:
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
A46BE1FB-EBC2-4576-B746-DD5B8CB44140 1
4103 E 605 N Suite 1
Rigby, ID 83442
208.932.4428
File name:
23255SB09252023MDH
Compressive Strength of Concrete Test Specimens
Project Number:
23-255
Cumulative Test Load Amount:
8.0
Project Name:
Married Student Second Stake
Test Location:
Footings, north side of building
Client:
The Church of Jesus Christ of Latter-day Saints
Admixtures:
MP 322
Contractor:
Alpha Concrete Construction
Supplier:
Walter's Ready Mix, Inc.
Mix Number:
W170-F 35
Date:
8/28/2023
Cylinder Log #:
504
Set #:
1
Entrained Air (%):
1.2
Concrete Temperature (°F):
77
Ambient Temperature (°F):
80
Unit Weight (PCF):
148.6
Tested By:
Michael Hammar
Date:
8/28/2023
Picked Up By:
L. Steiner
Pick Up Date:
8/29/2023
Pick Up Time:
4:17 PM
Max, Min Temperature:
77,60
Compressive Strength Data
Previous Test Results:
Cylinder ID:Break Age:Break Date:Area (in^2):Maximum Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
A 7 9/4/2023 12.57 44460 3537 3000 Type 6
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
A46BE1FB-EBC2-4576-B746-DD5B8CB44140 2
Current Break Testing:
Cylinder
ID:
Break
Age:
Break
Date:
Diameter
(in):
Area
(in^2):
Maximum
Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
B 28 9/25/2023 4.000 12.57 56180.0 4469 3000.0 Type 3
C 28 9/25/2023 4.000 12.57 54750.0 4356 3000.0 Type 6
D 28 9/25/2023 4.000 12.57 55350.0 4403 3000.0 Type 6
Second Break Average:
4409
Date:
09/28/2023
Reviewed By:
Luke Hammar
Signature:
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
72452B4E-FA8D-4270-AEC6-68F7FDEBB5E5 1
4103 E 605 N Suite 1
Rigby, ID 83442
208.932.4428
File name:
23255SB10042023MDH
Compressive Strength of Concrete Test Specimens
Project Number:
23-255
Cumulative Test Load Amount:
33.0
Project Name:
Married Student Second Stake
Test Location:
Interior subfloor
Client:
The Church of Jesus Christ of Latter-day Saints
Admixtures:
MP 322
Contractor:
Alpha Concrete
Supplier:
Walters Ready Mix, Inc
Mix Number:
170-3500
Date:
9/6/2023
Cylinder Log #:
523
Set #:
2
Entrained Air (%):
1.1
Concrete Temperature (°F):
67
Ambient Temperature (°F):
41
Unit Weight (PCF):
148.3
Tested By:
Leland Steiner
Date:
9/6/2023
Picked Up By:
Matthew Hammar
Pick Up Date:
9/7/2023
Pick Up Time:
11:01 AM
Max, Min Temperature:
80, 60
Compressive Strength Data
Previous Test Results:
Cylinder ID:Break Age:Break Date:Area (in^2):Maximum Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
A 7 9/13/2023 12.57 60895 4844 3500 Type 6
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
72452B4E-FA8D-4270-AEC6-68F7FDEBB5E5 2
Current Break Testing:
Cylinder
ID:
Break
Age:
Break
Date:
Diameter
(in):
Area
(in^2):
Maximum
Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
B 28 10/4/2023 4.000 12.57 71630.0 5698 3500.0 Type 2
C 28 10/4/2023 4.000 12.57 73265.0 5829 3500.0 Type 3
D 28 10/4/2023 4.000 12.57 72290.0 5751 3500.0 Type 3
Second Break Average:
5759
Date:
10/05/2023
Reviewed By:
Luke Hammar
Signature:
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
A8491DD5-3D79-4659-A935-18BD5850DD43 1
4103 E 605 N Suite 1
Rigby, ID 83442
208.932.4428
File name:
23255SB10062023MDH
Compressive Strength of Concrete Test Specimens
Project Number:
23-255
Cumulative Test Load Amount:
66
Project Name:
Married Student Second Stake
Test Location:
But. Slab on grade
Client:
The Church of Jesus Christ of Latter-day Saints
Admixtures:
N/A
Contractor:
Headwaters Construction
Supplier:
Walters
Mix Number:
170-3500
Date:
9/8/2023
Cylinder Log #:
535
Set #:
2
Entrained Air (%):
1.5
Concrete Temperature (°F):
72
Ambient Temperature (°F):
69
Unit Weight (PCF):
148.2
Tested By:
Bryton Ferguson
Date:
9/8/2023
Picked Up By:
Matthew Hammar
Pick Up Date:
9/9/2023
Pick Up Time:
12:46 PM
Max, Min Temperature:
80, 60
Compressive Strength Data
Previous Test Results:
Cylinder ID:Break Age:Break Date:Area (in^2):Maximum Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
A 7 9/15/2023 12.57 61320 4878 3,500.00 Type 3
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
A8491DD5-3D79-4659-A935-18BD5850DD43 2
Current Break Testing:
Cylinder
ID:
Break
Age:
Break
Date:
Diameter
(in):
Area
(in^2):
Maximum
Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
B 28 10/6/2023 4.000 12.57 71,890.0 5719 3,500.0 Type 1
C 28 10/6/2023 4.000 12.57 72,105.0 5736 3,500.0 Type 1
D 28 10/6/2023 4.000 12.57 72,475.0 5766 3,500.0 Type 3
Second Break Average:
5740
Date:
10/09/2023
Reviewed By:
Luke Hammar
Signature:
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
A8491DD5-3D79-4659-A935-18BD5850DD43 1
4103 E 605 N Suite 1
Rigby, ID 83442
208.932.4428
File name:
23255SB10062023MDH
Compressive Strength of Concrete Test Specimens
Project Number:
23-255
Cumulative Test Load Amount:
66
Project Name:
Married Student Second Stake
Test Location:
But. Slab on grade
Client:
The Church of Jesus Christ of Latter-day Saints
Admixtures:
N/A
Contractor:
Headwaters Construction
Supplier:
Walters
Mix Number:
170-3500
Date:
9/8/2023
Cylinder Log #:
535
Set #:
2
Entrained Air (%):
1.5
Concrete Temperature (°F):
72
Ambient Temperature (°F):
69
Unit Weight (PCF):
148.2
Tested By:
Bryton Ferguson
Date:
9/8/2023
Picked Up By:
Matthew Hammar
Pick Up Date:
9/9/2023
Pick Up Time:
12:46 PM
Max, Min Temperature:
80, 60
Compressive Strength Data
Previous Test Results:
Cylinder ID:Break Age:Break Date:Area (in^2):Maximum Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
A 7 9/15/2023 12.57 61320 4878 3,500.00 Type 3
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
A8491DD5-3D79-4659-A935-18BD5850DD43 2
Current Break Testing:
Cylinder
ID:
Break
Age:
Break
Date:
Diameter
(in):
Area
(in^2):
Maximum
Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
B 28 10/6/2023 4.000 12.57 71,890.0 5719 3,500.0 Type 1
C 28 10/6/2023 4.000 12.57 72,105.0 5736 3,500.0 Type 1
D 28 10/6/2023 4.000 12.57 72,475.0 5766 3,500.0 Type 3
Second Break Average:
5740
Date:
10/09/2023
Reviewed By:
Luke Hammar
Signature:
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
A8491DD5-3D79-4659-A935-18BD5850DD43 1
4103 E 605 N Suite 1
Rigby, ID 83442
208.932.4428
File name:
23255SB10062023MDH
Compressive Strength of Concrete Test Specimens
Project Number:
23-255
Cumulative Test Load Amount:
66
Project Name:
Married Student Second Stake
Test Location:
But. Slab on grade
Client:
The Church of Jesus Christ of Latter-day Saints
Admixtures:
N/A
Contractor:
Headwaters Construction
Supplier:
Walters
Mix Number:
170-3500
Date:
9/8/2023
Cylinder Log #:
535
Set #:
2
Entrained Air (%):
1.5
Concrete Temperature (°F):
72
Ambient Temperature (°F):
69
Unit Weight (PCF):
148.2
Tested By:
Bryton Ferguson
Date:
9/8/2023
Picked Up By:
Matthew Hammar
Pick Up Date:
9/9/2023
Pick Up Time:
12:46 PM
Max, Min Temperature:
80, 60
Compressive Strength Data
Previous Test Results:
Cylinder ID:Break Age:Break Date:Area (in^2):Maximum Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
A 7 9/15/2023 12.57 61320 4878 3,500.00 Type 3
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
A8491DD5-3D79-4659-A935-18BD5850DD43 2
Current Break Testing:
Cylinder
ID:
Break
Age:
Break
Date:
Diameter
(in):
Area
(in^2):
Maximum
Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
B 28 10/6/2023 4.000 12.57 71,890.0 5719 3,500.0 Type 1
C 28 10/6/2023 4.000 12.57 72,105.0 5736 3,500.0 Type 1
D 28 10/6/2023 4.000 12.57 72,475.0 5766 3,500.0 Type 3
Second Break Average:
5740
Date:
10/09/2023
Reviewed By:
Luke Hammar
Signature:
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
9973F820-9B3B-4C1E-838C-9ED81E03FC72 1
4103 E 605 N Suite 1
Rigby, ID 83442
208.932.4428
File name:
23255SB10102023MDH
Compressive Strength of Concrete Test Specimens
Project Number:
23-255
Cumulative Test Load Amount:
65
Project Name:
Married Student Second Stake
Test Location:
Slab on grade: A-B:1-2
Client:
The Church of Jesus Christ of Latter-day Saints
Admixtures:
MP 322
Contractor:
Headwaters
Supplier:
Walters
Mix Number:
170-3500
Date:
9/12/2023
Cylinder Log #:
550
Set #:
2
Entrained Air (%):
1.5
Concrete Temperature (°F):
69
Ambient Temperature (°F):
68
Unit Weight (PCF):
146.6
Tested By:
Bryton Ferguson
Date:
9/12/2023
Picked Up By:
Matthew Hammar
Pick Up Date:
9/13/2023
Pick Up Time:
1:26 PM
Max, Min Temperature:
80, 60
Compressive Strength Data
Previous Test Results:
Cylinder ID:Break Age:Break Date:Area (in^2):Maximum Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
A 7 9/19/2023 12.57 56275 4477 3500 Type 1
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
9973F820-9B3B-4C1E-838C-9ED81E03FC72 2
Current Break Testing:
Cylinder
ID:
Break
Age:
Break
Date:
Diameter
(in):
Area
(in^2):
Maximum
Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
B 28 10/10/2023 4.000 12.57 69,455.0 5525 3,500.0 Type 1
C 28 10/10/2023 4.000 12.57 68,910.0 5482 3,500.0 Type 1
D 28 10/10/2023 4.000 12.57 69,080.0 5496 3,500.0 Type 1
Second Break Average:
5501
Date:
10/14/2023
Reviewed By:
Luke Hammar
Signature:
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
9973F820-9B3B-4C1E-838C-9ED81E03FC72 1
4103 E 605 N Suite 1
Rigby, ID 83442
208.932.4428
File name:
23255SB10102023MDH
Compressive Strength of Concrete Test Specimens
Project Number:
23-255
Cumulative Test Load Amount:
65
Project Name:
Married Student Second Stake
Test Location:
Slab on grade: A-B:1-2
Client:
The Church of Jesus Christ of Latter-day Saints
Admixtures:
MP 322
Contractor:
Headwaters
Supplier:
Walters
Mix Number:
170-3500
Date:
9/12/2023
Cylinder Log #:
550
Set #:
2
Entrained Air (%):
1.5
Concrete Temperature (°F):
69
Ambient Temperature (°F):
68
Unit Weight (PCF):
146.6
Tested By:
Bryton Ferguson
Date:
9/12/2023
Picked Up By:
Matthew Hammar
Pick Up Date:
9/13/2023
Pick Up Time:
1:26 PM
Max, Min Temperature:
80, 60
Compressive Strength Data
Previous Test Results:
Cylinder ID:Break Age:Break Date:Area (in^2):Maximum Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
A 7 9/19/2023 12.57 56275 4477 3500 Type 1
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
9973F820-9B3B-4C1E-838C-9ED81E03FC72 2
Current Break Testing:
Cylinder
ID:
Break
Age:
Break
Date:
Diameter
(in):
Area
(in^2):
Maximum
Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
B 28 10/10/2023 4.000 12.57 69,455.0 5525 3,500.0 Type 1
C 28 10/10/2023 4.000 12.57 68,910.0 5482 3,500.0 Type 1
D 28 10/10/2023 4.000 12.57 69,080.0 5496 3,500.0 Type 1
Second Break Average:
5501
Date:
10/14/2023
Reviewed By:
Luke Hammar
Signature:
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
CEB2FAAB-73CE-45BC-97DF-2245EE977927 1
4103 E 605 N Suite 1
Rigby, ID 83442
208.932.4428
File name:
23255SB10102023MDH
Compressive Strength of Concrete Test Specimens
Project Number:
23-255
Cumulative Test Load Amount:
11
Project Name:
Married Student Second Stake
Test Location:
Slab on grade: A-B:1-2
Client:
The Church of Jesus Christ of Latter-day Saints
Admixtures:
MP 322
Contractor:
Headwaters
Supplier:
Walters
Mix Number:
170-3500
Date:
9/12/2023
Cylinder Log #:
549
Set #:
1
Entrained Air (%):
1.5
Concrete Temperature (°F):
73
Ambient Temperature (°F):
65
Unit Weight (PCF):
148.3
Tested By:
Bryton Ferguson
Date:
9/12/2023
Picked Up By:
Matthew Hammar
Pick Up Date:
9/13/2023
Pick Up Time:
1:12 PM
Max, Min Temperature:
80, 60
Compressive Strength Data
Previous Test Results:
Cylinder ID:Break Age:Break Date:Area (in^2):Maximum Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
A 7 9/19/2023 12.57 55900 4447 3500 Type 6
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
CEB2FAAB-73CE-45BC-97DF-2245EE977927 2
Current Break Testing:
Cylinder
ID:
Break
Age:
Break
Date:
Diameter
(in):
Area
(in^2):
Maximum
Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
B 28 10/10/2023 4.000 12.57 62,880.0 5002 3,500.0 Type 1
C 28 10/10/2023 4.000 12.57 67,285.0 5353 3,500.0 Type 3
D 28 10/10/2023 4.000 12.57 68,430.0 5444 3,500.0 Type 1
Second Break Average:
5266
Date:
10/14/2023
Reviewed By:
Luke Hammar
Signature:
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
FB16B15A-53EA-456E-B576-681B76ADF7E8 1
4103 E 605 N Suite 1
Rigby, ID 83442
208.932.4428
File name:
23255SB10122023MDH
Compressive Strength of Concrete Test Specimens
Project Number:
23-255
Cumulative Test Load Amount:
11.0
Project Name:
Married Student Second Stake
Test Location:
Referencing plans page S103. 11.5 - A6
Client:
The Church of Jesus Christ of Latter-day Saints
Admixtures:
MP322
Contractor:
ALPHA CONCRETE CONSTRUCTION
Supplier:
WALTERS READY MIX
INC.
Mix Number:
170-3500
Date:
9/14/2023
Cylinder Log #:
558
Set #:
1
Entrained Air (%):
2.0
Concrete Temperature (°F):
69
Ambient Temperature (°F):
42
Unit Weight (PCF):
147
Tested By:
Matthew Hammar
Date:
9/14/2023
Picked Up By:
Matthew Hammar
Pick Up Date:
9/15/2023
Pick Up Time:
5:39 PM
Max, Min Temperature:
80, 60
Compressive Strength Data
Previous Test Results:
Cylinder ID:Break Age:Break Date:Area (in^2):Maximum Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
A 7 9/21/2023 12.57 0 3500
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
FB16B15A-53EA-456E-B576-681B76ADF7E8 2
Current Break Testing:
Cylinder
ID:
Break
Age:
Break
Date:
Diameter
(in):
Area
(in^2):
Maximum
Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
B 28 10/12/2023 4.000 12.57 69,135.0 5500 3,500.0 Type 3
C 28 10/12/2023 4.000 12.57 68,290.0 5433 3,500.0 Type 3
D 28 10/12/2023 4.000 12.57 68,365.0 5439 3,500.0 Type 1
Second Break Average:
5457
Date:
10/14/2023
Reviewed By:
Luke Hammar
Signature:
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
7926E6CB-76E1-44F8-8A21-60922D7B5046 1
4103 E 605 N Suite 1
Rigby, ID 83442
208.932.4428
File name:
23255SB10122023MDH
Compressive Strength of Concrete Test Specimens
Project Number:
23-255
Cumulative Test Load Amount:
66
Project Name:
Married Student Second Stake
Test Location:
Referencing plans page S103. 8.5 - A6
Client:
The Church of Jesus Christ of Latter-day Saints
Admixtures:
MP322
Contractor:
ALPHA CONCRETE CONSTRUCTION
Supplier:
WALTERS READY MIX
INC.
Mix Number:
170-3500
Date:
9/14/2023
Cylinder Log #:
559
Set #:
2
Entrained Air (%):
2.0
Concrete Temperature (°F):
67
Ambient Temperature (°F):
45
Unit Weight (PCF):
147.4
Tested By:
Matthew Hammar
Date:
9/14/2023
Picked Up By:
Matthew Hammar
Pick Up Date:
9/15/2023
Pick Up Time:
5:45 PM
Max, Min Temperature:
80, 60
Compressive Strength Data
Previous Test Results:
Cylinder ID:Break Age:Break Date:Area (in^2):Maximum Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
A 7 9/21/2023 12.57 58330 4640 3500 Type 6
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
7926E6CB-76E1-44F8-8A21-60922D7B5046 2
Current Break Testing:
Cylinder
ID:
Break
Age:
Break
Date:
Diameter
(in):
Area
(in^2):
Maximum
Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
B 28 10/12/2023 4.000 12.57 71,470.0 5686 3,500.0 Type 3
C 28 10/12/2023 4.000 12.57 71,670.0 5702 3,500.0 Type 3
D 28 10/12/2023 4.000 12.57 71,395.0 5680 3,500.0 Type 3
Second Break Average:
5689
Date:
10/14/2023
Reviewed By:
Luke Hammar
Signature:
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
CA3BC67C-D617-49A3-9933-DF527CD78E21 1
4103 E 605 N Suite 1
Rigby, ID 83442
208.932.4428
File name:
23255SB10172023EV
Compressive Strength of Concrete Test Specimens
Project Number:
23-255
Cumulative Test Load Amount:
11.0
Project Name:
Married Student Second Stake
Test Location:
Gridlines: 1.5-2:A-B. Reference plans Pg. S101
Client:
The Church of Jesus Christ of Latter-day Saints
Admixtures:
Plasticizer
Contractor:
Headwaters Construction
Supplier:
Walters Ready Mix, Inc.
Mix Number:
170-3500
Date:
9/19/2023
Cylinder Log #:
578
Set #:
1
Entrained Air (%):
2.0
Concrete Temperature (°F):
70
Ambient Temperature (°F):
55
Unit Weight (PCF):
146.6
Tested By:
Bryton Ferguson
Date:
9/19/2023
Picked Up By:
Matthew Hammar
Pick Up Date:
9/20/2023
Pick Up Time:
1:07 PM
Max, Min Temperature:
80, 60
Compressive Strength Data
Previous Test Results:
Cylinder ID:Break Age:Break Date:Area (in^2):Maximum Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
A 7 9/26/2023 12.57 62010 4933 3,500.00 Type 3
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
CA3BC67C-D617-49A3-9933-DF527CD78E21 2
Current Break Testing:
Cylinder
ID:
Break
Age:
Break
Date:
Diameter
(in):
Area
(in^2):
Maximum
Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
B 28 10/17/2023 4.000 12.57 71,550.0 5692 3,500.0 Type 1
C 28 10/17/2023 4.000 12.57 73,650.0 5859 3,500.0 Type 2
D 28 10/17/2023 4.000 12.57 71,605.0 5696 3,500.0 Type 2
Second Break Average:
5749
Date:
10/18/2023
Reviewed By:
E. Vail
Signature:
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
805F104C-0EF3-41C2-AAE2-87808A8857F5 1
4103 E 605 N Suite 1
Rigby, ID 83442
208.932.4428
File name:
23255SB11092023MDH
Compressive Strength of Concrete Test Specimens
Project Number:
23-255
Cumulative Test Load Amount:
10
Project Name:
Married Student Second Stake
Test Location:
Dumpster enclosure approximately south west corner
of parking lot
Client:
The Church of Jesus Christ of Latter-day Saints
Admixtures:
HP 322, MA AE 90
Contractor:
Alpha
Supplier:
Walters
Mix Number:
4500-AF
Date:
10/12/2023
Cylinder Log #:
649
Set #:
1
Entrained Air (%):
5.5
Concrete Temperature (°F):
63
Ambient Temperature (°F):
46
Unit Weight (PCF):
138.5
Tested By:
Bryton Ferguson
Date:
10/12/2023
Picked Up By:
Matthew Hammar
Pick Up Date:
10/13/2023
Pick Up Time:
4:41 PM
Max, Min Temperature:
80, 60
Compressive Strength Data
Previous Test Results:
Cylinder ID:Break Age:Break Date:Area (in^2):Maximum Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
A 7 10/19/2023 12.57 47495 3778 3,000.00 Type 1
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
805F104C-0EF3-41C2-AAE2-87808A8857F5 2
Current Break Testing:
Cylinder
ID:
Break
Age:
Break
Date:
Diameter
(in):
Area
(in^2):
Maximum
Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
B 28 11/9/2023 4.000 12.57 61,700.0 4909 3,000.0 Type 3
C 28 11/9/2023 4.000 12.57 55,500.0 4415 3,000.0 Type 1
D 28 11/9/2023 4.000 12.57 63,490.0 5051 3,000.0 Type 3
Second Break Average:
4792
Date:
11/13/2023
Reviewed By:
Luke Hammar
Signature: