Loading...
HomeMy WebLinkAboutFS REVIEW - 23-00170 - Rexburg 10th Ward LDS Meetinghouse Rexburg 10 Meetinghouse – Rexburg 1 of 1 STATE FIRE MARSHAL IDAHO DEPARTMENT OF INSURANCE 700 W. State Street, 3rd Floor P.O. Box 83720 Boise, ID 83720-0043 (208) 334-4370 | www.doi.idaho.gov/sfm PLAN REVIEW FOR FIRE SPRINKLER SYSTEMS PLANS RECEIVED: October 5, 2023 APPROVED: October 12, 2023 REVIEWED BY: Rory Winch, Fire Plans Examiner PROJECT: Rexburg 10 Meetinghouse STREET ADDRESS: 411 University Blvd. CITY: Rexburg AHJ: Madison Fire Department SPRINKLER CONTRACTOR: Intermountain Fire Systems 5768 South 650 West Spanish Fork, Utah 84660 IDAHO LICENSE: FPSC-184 CONTACT NAME: Lee Anderson landerson952@gmail.com PHONE NO: (801) 471-7568 SYSTEM DESIGNED BY: Lee Anderson landerson952@gmail.com PHONE NO: (801) 471-7568 TYPE OF SYSTEM: NFPA 13/Dry HEAD COUNT: 394 TOTAL SYSTEMS: 1 OCCUPANCY CLASSIFICATION: A3 CONSTRUCTION TYPE: III-B AREA SQUARE FOOTAGE: 31,338 SCOPE OF WORK: This is a new dry system with a nitrogen generator protecting a LDS church. PLAN REVIEW COMMENTS: Approved with comments 1. Provide the owner with a copy of NFPA 25. (NFPA 13, 28.4(2) 2. General information sign per NFPA 13, 28.6.1. 3. Hydraulic info sign per NFPA 13, 28.5.1 4. Hydraulic calculations shall be prepared on form sheets that include a summary sheet, a graph sheet, a water supply analysis, a node analysis, and detailed worksheets. (NFPA13, 27.4.5.1.1) 5. The 2019 edition of NFPA 13 is adopted. Approval of shop drawings is not intended to imply waiver or modification of any requirements of the Idaho State Statutes or Rules, International Fire Code, NFPA Standards or any other applicable criteria. It is acknowledged that backflow preventer is installed per the demand of the local water purveyor. The State Fire Marshal’s Office and its personnel does not take any responsibility for the back flow device.