HomeMy WebLinkAboutFIRE DETECTION ALARM - 23-00170 - Rexburg 10th Ward LDS MeetinghouseHW Job No. REXBURG LDS MEETINGHOUSE Submittal Review: 283100 - 01 223015 411 UNIVERSITY BOULEVARD, REXBURG, ID 83440 65 EAST WADSWORTH PARK DRIVE SUITE 20 DRAPER, UT 84020 LAFE HARRIS To:BHD ARCHITECTS Specification Section Date: 9/12/2023 283100 FIRE DETECTION & ALARM Transmit By:Internet This Submittal includes the following: Transmitted for: Shop Drawings Product Data Samples Copy of Letter Other For Approval For Your Use For Review and Comment Other Comments: PLEASE SEE ATTACHED. Reply Due Date: 9/19/2023 Signed:Alma HaleAttn: Phone:(801) 571-0010 From:Headwaters Construction Company 900 JET STREAM DRIVE REXBURG, ID 83440 Phone:(866) 496-9869Cell:(801) 367-0608 lafe@bhdarchitects.comEmail: Cell:(208) 270-5231 ahale@headwaterscc.comEmail: Description:FIRE DETECTION & ALARM Contractor Review: A/E Review: Reviewed Comments Noted Other This shop drawing/submittal is submitted for the purposes of fabrication/installation of the materials identified. Contractor has reviewed the submittal for general compliance with the contract documents. Any deviations from the contract documents observed by contractor have been noted. The party supplying the material remains responsible for: (1) Compliance with the contract documents, (2) the accuracy and completeness of details such as dimensions and quantities, (3) field measurements as required, and (4) construction of a complete and workable installation satisfactory for the work included. Contractor is not a design professional and renders no opinion about the structural integrity or suitability of the materials for the project. 900 JET STREAM DRIVE, REXBURG, ID 83440 P: (866) 496-9869 F: (866) 496-0209 www.HeadwatersCC.com Page 1 of 1 If Enclosures Are Not As Noted, Please Notify Us Immediatley FIRE-ALARM ANNUNCIATOR CA L C U L A T I O N , L E G E N D , N O T E S , & D E T A I L S RE V I S I O N DE S C R I P T I O N DA T E RE X B U R G 1 0 T H W A R D 41 1 U N I V E R S I T Y B O U L E V A R D RE X B U R G , I D A H O 8 3 4 4 0 shop drawings created by: 5794 W. 4600 So. Hooper, UT 84315 Office: 801.985.0410 om n i FA-1 COM TELGAURD EMERGENCY COMMAND CENTER By Honeywell FIRE-LITE ALARMS EC C - C E 6 By Honeywell ANN-80 FIRE-ALARM ANNUNCIATOR FIRE-LITE ALARMS TG-7FLV FI R E A L A R M R I S E R D I A G R A M RE V I S I O N DE S C R I P T I O N DA T E RE X B U R G 1 0 T H W A R D 41 1 U N I V E R S I T Y B O U L E V A R D RE X B U R G , I D A H O 8 3 4 4 0 shop drawings created by: 5794 W. 4600 So. Hooper, UT 84315 Office: 801.985.0410 om n i FA-2 Hallway [171] Bishop [103] Interview [101] Bishop [104] Interview [102] Clerk [106] Waiting [105] Storage [148] Storage [149] Storage [123] Interview [126] Interview [127] Waiting [128] Clerk [124] Stake Pres [125] High Council [129] Vest [130] Custodial [116] Tech [154] Men [158] Women [157] Mothers [159] Vest [191] Clerk [192] Bishop [193] Bishop [189] Waiting [190] Interview [188] Interview [187] Clerk [164] Bishop [165] Bishop [166] Waiting [163] Interview [162] Interview [161] Vest [160] Vest [131] Chapel [146] Cultural Center [147] Cultural Center [150] Chapel [151] Rostrum [152] Hallway [140] Hallway [119] Hallway [155] Room [185] Room [186]Women [167] Men [168] Women [107] Men [108] Family RR [142] Sac Prep [141] Materials Center [143] Rostrum [145] Room [121] Room [120] Room [117] Room [118] Room [169] Room [170] Room [173] Room [172] Room [133] Room [132] Clerk [139] Bishop [138] Bishop [134] Waiting [137] Interview [135] Interview [136] Vest [112] Foyer [111] Fire Riser [176]Bishop [182] Bishop [177] Clerk [181] Interview [178] Waiting [180] Foyer [183] Vest [184] Interview [179] Serving Area [174] Room [156] Electrical [114] Serving Area [115] Table/Chair Storage [113] Room [109] Room [110] Stair [122] Mothers [144] Custodial [175] Sac Prep [153] FI R S T F L O O R F I R E A L A R M P L A N RE V I S I O N DE S C R I P T I O N DA T E RE X B U R G 1 0 T H W A R D 41 1 U N I V E R S I T Y B O U L E V A R D RE X B U R G , I D A H O 8 3 4 4 0 shop drawings created by: 5794 W. 4600 So. Hooper, UT 84315 Office: 801.985.0410 om n i FA-3 CA T W A L K F L O O R F I R E A L A R M P L A N RE V I S I O N DE S C R I P T I O N DA T E RE X B U R G 1 0 T H W A R D 41 1 U N I V E R S I T Y B O U L E V A R D RE X B U R G , I D A H O 8 3 4 4 0 shop drawings created by: 5794 W. 4600 So. Hooper, UT 84315 Office: 801.985.0410 om n i FA-4 For more information, call 248-673-9898 or visit www.sti-usa.com. WIRE GUARDS KEY FEATURES General Information · Offers protection against vandalism and accidental damage. · Simple removal for maintenance. · For use in controlled environment (not intended for outdoor use). · Three year guarantee against breakage in normal use. Construction · Constructed of tough 9-gauge steel wire. · Coated with corrosion resistant polyester. Installation · Installation is fast and simple with screws and anchors provided. Options · STI-9705, STI-9708, STI-9711 and STI-9714 protect SpectrAlert® strobe units. · STI-9717 and STI-9720 fit over System Sensor notification appliances P2R1224MC and SP2W1224MC. HORN/STROBE/SPEAKER DAMAGE STOPPERS ® PRODUCT OVERVIEW Here are excellent ways to protect strobe units against both vandalism and accidental damage. Constructed of tough, 9-gauge steel wire coated with corrosion resistant red or white polyester, these guards can take hard knocks in stride. STI-9705, STI-9708, STI-9711 and STI-9714 wire guards provide maximum protection for System Sensor SpectrAlert ® Advance series strobe notification appliances. BACKED BY A THREE YEAR GUARANTEE As all STI protective covers, these guards are backed by a three year guarantee against breakage in normal use. Installation and servicing is easy with all screws and anchors provided. This Stopper is highly recommended for areas where abuse is severe or it is imperative that strobe units continue to operate. STI-9717 and STI-9720 fit over System Sensor notification appliances SP2R1224MC and SP2W1224MC. STI-9705-R STI-9711 STI-9720 © 2010-2022 Safety Technology International, Inc.Subject to change without notice. 02/22 2306 Airport Road Waterford, Michigan 48327, USA Tel: 248-673-9898 Fax: 248-673-1246 Toll-free: 800-888-4784 info@sti-usa.com www.sti-usa.com Unit 49G Pipers Road Park Farm Industrial Estate Redditch, Worcestershire B98 OHU England Tel: 44 (0) 1527 520 999 Fax: 44 (0) 1527 501 999 Free: 0800 085 1678 (UK) www.sti-europe.com 2306 Airport Road info@sti-usa.com Waterford, MI www.sti-usa.com 48327, USA Te l:248-673-9898 Ta ylor House info@sti-emea.com 34 Sherwood Rd., Bromsgrove, www.sti-emea.com Worcs., B60 3DR, England Te l: +44 (0) 1527 520 999 Unit 7A Lockheed Avenue Airport Business Park Waterford X91 HWF2 Ireland APPROVALS & WARRANTY TESTING STI-9705, STI-9708, STI-9711 and STI-9714 have been tested and approved or listed by:· Underwriter Laboratories and Canadian UL File S7025 WARRANTY Three year guarantee against breakage in normal use. Horn/Strobe/Speaker Damage Stoppers® Dimensions and Technical Information MODELS AVAILABLE STI-9705 Damage Stopper, Flush Mount - White STI-9705-R Damage Stopper, Flush Mount - Red STI-9708 Damage Stopper, Surface Mount - White STI-9708-R Damage Stopper, Surface Mount - Red STI-9711 Damage Stopper, Flush Mount - White STI-9714 Damage Stopper, Surface Mount - White STI-9717 Speaker/Strobe Damage Stopper - Flush Mount (not UL Listed) STI-9720 Speaker/Strobe Damage Stopper - Surface Mount (not UL Listed) MODEL HEIGHT WIDTH DEPTH STI-9705 STI-9705-R 7.40 in. (188mm) 6.15 in. (156mm) 3.39 in. (84mm) STI-9708 STI-9708-R 7.49 in. (190mm) 6.74 in. (171mm) 6.09 in. (155mm) STI-9711 8.26 in. (210mm) 8.26 in. (210mm) 3.54 in. (90mm) STI-9714 8.55 in. (271mm) 8.55 in. (271mm) 6.23 in. (158mm) STI-9717 6.1 in. (155mm) 9.3 in. (238mm) 2.4 in. (61mm) STI-9720 6.1 in. (155mm) 9.3 in. (238mm) 4.9 in. (125mm) Light De-Rating Factor STI-9705 and STI-9708 System Sensor (SR,SW, SW-ALERT, SW-CLR-ALERT, SRK, SWK, P2R, P2W, P4R, P4W, CHSR, CHSW, P2RK, P2WK, P4RK, P4WK, SPSR, SPSR-SP, SPSR-PG, SPSW, SPSW-CLR-ALERT, SPSW-SP, SPSW-PG, SPSRV, SPSRV-SP, SPSRV-PG, SPSWV, SPSWV-SP and SPSWV-PG, SPSWK, SPSRK, SPSW-ALERT) System Sensor (SRH, SWH, SRHK, SWH-ALERT, SWHK, P2RH, P2WH, P4RH, P2RHK, P2WHK, P2RHK-120, SPSRH, SPSRH-SP, SPSRH-PG, SPSWH, SPSWH-SP and SPSWH-PG, SPSRHK) STI-9711 and STI-9714 System Sensor (SCR, SCW, SCRK, SCWK, SCW-CLR-ALERT, PC2R, PC2W, PC4R, PC4W, PC2RK, PC2WK, PC4WK, SPSCWV, SPSCR, SPSCR-SP, SPSCR-PG, SPSCW, SPSCW-SP, SPSCW-PG, SPSCRV, SPSCRV-PG, SPSCWV, SPSCWV-SP and SPSCWV-PG, SPSCWK, SPSCW-CLR-ALERT) System Sensor (SCRH, SCWH, SCRHK, SCWHK, PC2RH, PC2WH, PC4RH, PC2RHK, PC2WHK, PC4WHK, SPSCWHV, SPSCRH, SPSCRH-SP, SPSCRH-PG, SPSCWH, SPSCWH-SP, SPSCWH-PG, SPSCRVH, SPSCRVH-SP, SPSCRVH-PG, SPSCWHV-SP SPSCWHV-PG, SPSCWHK) Light Loss % 13% 0% 0% 0% STI-9705 ANCHOR (4) PROVIDED H19020 CLAMP (4) PROVIDED #10 x 1-1/2 in. PHILLIPS PAN HEAD SCREW (4) PROVIDED 7.40 in.(188mm) 3.39 in. (86mm) 6.15 in. (156mm)6.74 in. (171mm) 7.49 in. (190mm) 6.09 in. (155mm) 3.1 in. (79mm) 3.15 in. (80mm) 1.63 in. (41mm) SPEAKER/STROBE MOUNTING PLATE STI-9705 WIRE GUARD SPEAKER/STROBE STI-1285 BACKPLATE 4” SQUARE ELECTRICAL BOX STI-9708 CEILING STROBE ANCHOR (4) PROVIDED #10 x 1-1/2 in. PHILLIPS PAN HEAD SCREW (4) PROVIDED H19020 CLAMP (4) PROVIDED STROBE AND BACKBOX 22.5° 3.54 in. (90mm) 8.26 in. (210mm) STI-9711 STI-9714 6.23 in. (158mm) 8.55 in. (271mm) CEILIING SPEAKER/STROBE 4” SQUARE ELECTRICAL BOX STI-1286 BACKPLATE CEILING SPEAKER/STROBE MOUNTING PLATEWIRE GUARD CLAMPS ANCHOR (4) PROVIDED H19020 CLAMP (4) PROVIDED #10 x 1-1/2 in. PHILLIPS PAN HEAD SCREW (4) PROVIDED 7.40 in.(188mm) 3.39 in. (86mm) 6.15 in. (156mm)6.74 in. (171mm) 7.49 in. (190mm) 6.09 in. (155mm) 3.1 in. (79mm) 3.15 in. (80mm) 1.63 in. (41mm) SPEAKER/STROBE MOUNTING PLATE STI-9705 WIRE GUARD SPEAKER/STROBE STI-1285 BACKPLATE 4” SQUARE ELECTRICAL BOX CEILING STROBE ANCHOR (4) PROVIDED #10 x 1-1/2 in. PHILLIPS PAN HEAD SCREW (4) PROVIDED H19020 CLAMP (4) PROVIDED STROBE AND BACKBOX 22.5° 3.54 in. (90mm) 8.26 in. (210mm) STI-9711 STI-9714 6.23 in. (158mm) 8.55 in. (271mm) CEILIING SPEAKER/STROBE 4” SQUARE ELECTRICAL BOX STI-1286 BACKPLATE CEILING SPEAKER/STROBEMOUNTING PLATEWIRE GUARD CLAMPS CEILING STROBE ANCHOR (4) PROVIDED #10 x 1-1/2 in. PHILLIPS PAN HEAD SCREW (4) PROVIDED H19020 CLAMP (4) PROVIDED STROBE AND BACKBOX 22.5° 3.54 in. (90mm) 8.26 in. (210mm) STI-9711 STI-9714 6.23 in. (158mm) 8.55 in. (271mm) CEILIING SPEAKER/STROBE 4” SQUARE ELECTRICAL BOX STI-1286 BACKPLATE CEILING SPEAKER/STROBE MOUNTING PLATEWIRE GUARD CLAMPS STI-9711 EXISTING SYSTEM SENSOR WALL SPEAKER/STROBE SIGNAL DEVICE SHOWN WITH ACCESSORY BACK BOX SKIRT. STI-9720 SURFACE MOUNT STI-9717 FLUSH MOUNT PHILLIPS PAN HEAD SCREW #10 x 1 1/2 in. (4) PROVIDED H19020 CLAMP (4) PROVIDED ANCHOR (4) PROVIDEDDRILL (4) .25 in.(6.3mm) HOLES EXISTING SYSTEM SENSOR WALL SPEAKER/STROBE SIGNAL DEVICE CLAMPS MAY BE INSTALLED VERTICALLY OR HORIZONTALLY AS SHOWN 3.7 in. (94mm)4.9 in. (125mm) STI-9720 TOP VIEW 1.2 in. (31mm)2.4 in. (61mm) STI-9717 TOP VIEW 9.3 in.(238mm) 6.1 in. (155mm) STI-9717 and STI-9720 FRONT VIEW STI-9717 SIDE VIEW DF-52013:D • 4/13/2012 — Page 1 of 2 BG-12LX Addressable Manual Pull Station Addressable Devices DF-52013:D • E-100 FL P u l l S t a t i o n . j p g General The Fire·Lite BG-12LX is a state-of-the-art, dual-action (i.e., requires two motions to activate the station) pull station that includes an addressable interface (mounted inside) for Fire·Lite’s addressable fire alarm control panels (FACPs) Because the BG-12LX is addressable, the control panel can display the exact location of the activated manual station. This leads fire personnel quickly to the location of the alarm. Features • Maintenance personnel can open station for inspection and address setting without causing an alarm condition. • Built-in bicolor LED, which is visible through the handle of the station, flashes in normal operation and latches steady red when in alarm. • Handle latches in down position and the word “ACTIVATED” appears to clearly indicate the station has been operated. • Captive screw terminals wire-ready for easy connection to SLC loop (accepts up to 12 AWG/3.25 mm² wire). • Can be surface mounted (with SB-10 or SB-I/O) or semi- flush mounted. Semi-flush mount to a standard single- gang, double-gang, or 4" (10.16 cm) square electrical box. • Smooth dual-action design. • Meets ADAAG controls and operating mechanisms guide- lines (Section 4.1.3[13]); meets ADA requirement for 5 lb. maximum activation force. • Highly visible. • Attractive shape and textured finish. • Key reset. • Includes Braille text on station handle. • Optional trim ring (BG12TR). • Meets UL 38, Standard for Manually Actuated Signaling Boxes. Construction Shell, door, and handle are molded of durable polycarbonate material with a textured finish. Specifications •Shipping Weight: 9.6 oz. (272.15 g) •Normal operating voltage: 24 VDC. •Maximum SLC loop voltage: 28.0 VDC. •Maximum SLC standby current: 375 μA. •Maximum SLC alarm current: 5 mA. •Temperature Range: 32°F to 120°F (0°C to 49°C) •Relative Humidity: 10% to 93% (noncondensing) •For use indoors in a dry location Installation The BG-12LX will mount semi-flush into a single-gang, double- gang, or standard 4" (10.16 cm) square electrical outlet box, or will surface mount to the model SB-10 or SB-I/O surface back- box. If the BG-12LX is being semi-flush mounted, then the optional trim ring (BG12TR) may be used. The BG12TR is usually needed for semi-flush mounting with 4" (10.16 cm) or double-gang boxes (not with single-gang boxes). Operation Pushing in, then pulling down on the handle causes it to latch in the down/activated position. Once latched, the word “ACTI- VATED” (in bright yellow) appears at the top of the handle, while a portion of the handle protrudes from the bottom of the station. To reset the station, simply unlock the station with the key and pull the door open. This action resets the handle; clos- ing the door automatically resets the switch. Each manual station, on command from the control panel, sends data to the panel representing the state of the manual switch. Two rotary decimal switches allow address settings (1 – 159 with Breakaway Tab removed for MS-9600 Series, 1 – 99 and MS-9200UDLS, 1 – 50 for MS-9050UD). Architectural/Engineering Specifications Manual Fire Alarm Stations shall be non-coded, with a key- operated reset lock in order that they may be tested, and so designed that after actual Emergency Operation, they cannot be restored to normal except by use of a key. An operated sta- tion shall automatically condition itself so as to be visually detected as activated. Manual stations shall be constructed of red-colored polycarbonate material with clearly visible operat- ing instructions provided on the cover. The word FIRE shall appear on the front of the stations in white letters, 1.00 inches (2.54 cm) or larger. Stations shall be suitable for surface mounting on matching backbox SB-10 or SB-I/O; or semi-flush mounting on a standard single-gang, double-gang, or 4" (10.16 cm) square electrical box, and shall be installed Page 2 of 2 — DF-52013:D • 4/13/2012 This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice. For more information, contact Fire•Lite Alarms. Phone: (800) 627-3473, FAX: (877) 699-4105. www.firelite.com FireLite® Alarms® is a registered trademark of Honeywell International Inc. ©2012 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited. Made in the U.S. A. within the limits defined by the Americans with Disabilities Act (ADA) or per national/local requirements. Manual Stations shall be Underwriters Laboratories listed. Manual stations shall connect with two wires to one of the con- trol panel SLC loops. The manual station shall, on command from the control panel, send data to the panel representing the state of the manual switch. Manual stations shall provide address setting by use of rotary decimal switches. Product Line Information BG-12LX: Dual-action addressable pull station. Includes key locking feature. (Listed for Canadian and non-Canadian appli- cations.) SB-10: Surface backbox; metal. SB-I/O: Surface backbox; plastic. BG12TR: Optional trim ring. 17003: Keys, set of two. Agency Listings and Approvals In some cases, certain modules or applications may not be listed by certain approval agencies, or listing may be in pro- cess. Consult factory for latest listing status. •UL/ULC Listed: S711 (listed for Canadian and non-Cana- dian applications). •MEA: 67-02-E. •CSFM: 7150-0075:0184. • FM Approved. Patented: U.S. Patent No. D428,351; 6,380,846; 6,314,772; 6,632,108. df-60379:A1 • 08/04/09 — Page 1 of 2 CRF-300(A) Relay Module Addressable Devices df-60379:A1 • E-400 General The CRF-300(A) Addressable Relay Module provides the sys- tem with a dry-contact output for activating a variety of auxil- iary devices, such as fans, door holders, dampers, control equipment, etc. Addressability allows the dry contact to be activated through panel programming, on a select basis. LiteSpeed™ is a communication protocol developed by Fire•Lite Engineering that greatly enhances the speed of com- munication between analog intelligent devices. Intelligent devices communicate in a grouped fashion. If one of the devices within the group has new information, the panel CPU stops the group poll and concentrates on single points. The net effect is response speed greater than five times that of other designs. Features • Built-in type identification automatically identifies these devices to the control panel. • Internal circuitry and relay powered directly by two-wire SLC loop. • Integral LED “blinks” green each time a communication is received from the control panel and turns on in steady red when activated. • High noise immunity (EMF/RFI). • Wide viewing angle of LED. • SEMS screws with clamping plates for wiring ease. • Direct-dial entry of address: 01– 159 for MS-9600(A) series panels, 01 – 99 on MS-9200UDLS(A) and MS-9050UD(A). Applications The CRF-300(A) may be programmed to operate dry contacts for door holders, Air Handling Unit shutdown, etc., and to reset four-wire smoke detector power. Construction • The face plate is made of off-white heat-resistant plastic. • Controls include two rotary switches for direct-dial entry of address setting. • The CRF-300(A) is configured for a single Class B (Style Y) or Class A (Style Z) Notification Appliance Circuit. • The CRF-300(A) provides two Form-C dry contacts that switch together. Operation Each CRF-300(A) uses one of the addresses on a SLC loop. It responds to regular polls from the control panel and reports its type and status, including the open/normal/short status of its Notification Appliance Circuit (NAC). The LED blinks with each poll received. On command, it activates its internal relay. NOTE: Open/short supervision is suspended with the CRF-300. Rotary switches set a unique address for each module. The address may be set before or after mounting. The built-in TYPE CODE (not settable) will identify the module to the con- trol panel, so as to differentiate between a control module and a relay module. Specifications Normal operating voltage: 15 to 32 VDC. Maximum SLC current draw: 6.5 mA (LED on). Average operating current: 230 μA direct poll (CLIP mode), 255 μA group poll (LiteSpeed mode) with LED flashing. EOL resistance: not used. Temperature range: 32°F to 120°F (0°C to 49°C). Humidity range: 10% to 93% non-condensing. Dimensions: 4.5" (11.43 cm) high x 4" (10.16 cm) wide x 1.25" (3.175 cm) deep. Mounts to a 4" (10.16 cm) square x 2.125" (5.398 mm) deep box. Relay Contact Ratings Load Description Application Maximum Voltage Current Rating Resistive Non-Coded 30 VDC 3.0 A Resistive Coded 30 VDC 2.0 A Resistive Non-Coded 110 VDC 0.9 A Resistive Non-Coded 125 VAC 0.9 A Inductive (L/R=5ms) Coded 30 VDC 0.5 A Inductive (L/R=2ms) Coded 30 VDC 1.0 A Inductive (PF=0.35) Non-Coded 125 VAC 0.5 A CRF-300(A) 60 3 7 9 c o v . j p g Page 2 of 2 — df-60379:A1 • 08/04/09 This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice. For more information, contact Fire•Lite Alarms. Phone: (800) 627-3473, FAX: (877) 699-4105. www.firelite.com LiteSpeed™ is a trademark and Fire•Lite® Alarms is a registered trademark of Honeywell International Inc. ©2009 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited. Made in the U.S. A. Agency Listings and Approvals In some cases, certain modules may not be listed by certain approval agencies, or listing may be in process. Consult fac- tory for latest listing status. •UL: S2424 •ULC: S2424 • FM approved •CSFM: 7300-0075:185 •MEA: 72-01-E Product Line Information CRF-300(A): Intelligent addressable relay module. : Intelligent addressable relay module, ULC listed model. SMB500: Optional surface-mount backbox. NOTE: For installation instructions, see document I56-1190-005 and refer to the SLC Wiring Manual, document 51309. GAMEWELL-FCI 12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118 Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use. ©2013 by Honeywell International Inc. All rights reserved. www.gamewell-fci.com 9021-60470 Rev. C page 1 of 4 InnovairFlex™ Series D4120 Duct Smoke Detector 4-Wire Photoelectric Duct Smoke Detector FM 3029700 APPROVED SIGNALING S911 MSFM 2202 2207 3242-1653:0207 S911 Description The InnovairFlex™ Series, D4120, 4-wire photoelectric duct smoke detector features a pivoting housing that fits both square and rectangular footprints and mounts to round or rectangular ductwork. This unit senses smoke in the most challenging conditions, operating in airflow speeds from 100 to 4,000 feet per minute, temperatures of –4°F to 158°F, and a humidity range of 0 to 95 percent (non-condensing). A plug-in sensor head offers improved false alarm immunity and simple installation, testing, and maintenance. The improved cover design isolates the sen- sor head from the low-flow feature for simple maintenance. The InnovairFlex housing provides ample wiring space, a ¾-inch conduit knockout, and a built-in short circuit protec- tion to prevent damage to sensitive components during installation. The high contrast terminal designations make wiring easy. With a 2:1 sensor-to-power capability, the power board of the D4120 may be used to simultaneously monitor a second D4S sensor (i.e., supply and return side). Up to 50 InnovairFlex detectors can be interconnected. When one unit senses smoke, all interconnected detectors will switch the relays, and only the detector sensing smoke will go into alarm, thus pinpointing the fire source. An easy-access Test/Reset button makes it possible to test the unit with the cover on. Three DIP switches can be used to configure the following field selectable settings: • cover tamper delay • number of sensors to be controlled • shut down on trouble option Each power board has two LEDs that can be used to indi- cate the status of connected sensors. A quick reference label imprinted on the cover displays the LED status indi- cations (Standby, Maintenance, Trouble, and Alarm). The InnovairFlex duct smoke detector can be customized to meet local codes and specifications without additional wir- ing. The new InnovairFlex product line is compatible with all previous Innovair models, including the remote test accessories. WARNING: Duct smoke detectors are NOT a substitute for open area smoke detectors; NOT a substitute for early warning detection; NOT a replacement for a building’s regular fire detection system. Refer to NFPA 72 and 90A for additional information. InnovairFlex™ is a trademark of Honeywell International Inc. Features • Photoelectric, integrated low-flow technology. • Air velocity rating from 100 ft/min to 4,000 ft/min (0.5 m/s to 20.32 m/sec). • Versatile mounting options: square or rectangular configuration. • Plug-in sensor offers superb false alarm immunity and the latest sensor technology. • Broad ranges for operating temperature (–4°F to 158°F) and humidity (0% to 95% non-condensing). • Patented sampling tube installs from front or back of the detector with no tools required. • Increased wiring space with a newly added ¾-inch conduit knockout. • One easy-access Test/Reset button and improved LED status. • Patented interconnect feature for multi-fan shutdown. • New high contrast terminal designations. • Built-in short circuit protection from operator wiring errors. • Field selectable settings for configuring the detector. • Two DPDT Form-C relay contacts, 24 VAC/DC or 120VAC. InnovairFlex-D4120 GAMEWELL-FCI 12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118 9021-60470 Rev. C page 2 of 4 www.gamewell-fci.com Architectural/Engineering Specifications The air duct smoke detector shall be a System Sensor InnovairFlex™ D4120 Photoelectric Duct Smoke Detector. The detector housing shall be UL Listed per UL 268A specifically for use in air handling systems. The flexible housing of the duct smoke detector fits multiple footprints from square to rectangular. The detector shall operate at air velocities of 100 feet per minute to 4,000 feet per minute (0.5 to 20.32 meters/second). The unit shall be capable of controlling up to 50 air handling systems when interconnected with other detectors. The detector shall be capable of providing a trouble signal in the event that the front cover is removed. It shall be capable of local testing via magnetic switch, test button on the cover, or remote testing using the RTS2-AOS Multi-Signaling Accessory or the RTS151KEY Remote Test Station. Terminal connections shall be of the strip and clamp method suitable for 12–18 AWG wiring. Physical Specifications Size: Rectangular Dimensions:14.38 in (37 cm) Length; 5 in (12.74 cm) Width; 2.5 in (6.36 cm) Depth Square Dimensions:7.75 in (19.7 cm) Length; 9 in (22.9 cm) Width; 2.5 in (6.35 cm) Depth Weight:2.5 lbs (1.14 kg) Operating Temperature Range:D4120 & D4S: –4° to 158°F (–20° to 70°C); D4P120: –40° to 158°F (–40° to 70°C) Storage Temperature Range:D4120 & D4S: –22° to 158°F (–30° to 70°C); D4P120: –40° to 158°F (–40° to 70°C) Operating Humidity Range:0% to 95% relative humidity non-condensing Air Duct Velocity:100 to 4,000 ft/min (0.5 to 20.32 m/sec) Electrical Ratings Power supply voltage:20–29 VDC 24 VAC 50–60 Hz 120 VAC 50–60 Hz Input capacitance:270 µF max. 270 µF max. N/A Reset voltage:3.0 VDC min. 2.0 VAC min. 10 VAC min. Reset time: (with RTS151).03 to 0.3 sec. .03 to 0.3 sec. .03 to 0.3 sec. Reset time: (by power down)0.6 sec. max. 0.6 sec. max. 0.6 sec. max. Power up time:35 sec. max. 35 sec. max. 35 sec. max. Alarm response time:15 sec. 15 sec. 15 sec. Sensitivity Test:See detector label See detector label See detector label Current Requirements: (Using No Accessories) Max. standby current:21 mA @ 24VDC 65 mA RMS @ 24VAC 60Hz 20 mA RMS @ 120VAC 60Hz Max. alarm current:65 mA @ 24VDC 135 mA RMS @ 24VAC 60Hz 35 mA RMS @ 120VAC 60Hz Contact Ratings Alarm initiation contacts: (SPST)2.0A @ 30 VDC (resistive) Alarm auxiliary contacts: (DPDT)10A @ 30 VDC (resistive); 10A @ 250 VAC (resistive); ½ HP @ 240 VAC; ¼ HP @ 120 VAC Note: Alarm auxiliary contacts shall not be connected to initiating circuits of control panels. Use the alarm initiation contact for this purpose. Supervisory contacts: (SPDT)2.0A @ 30 VDC (resistive); 2.0A @ 125 VAC (resistive) Accessory Current Loads at 24 VDC Device Standby Trouble Alarm APA151/APA151 12.5 mA n/a 30 mA Max. MHR/MHW 0 mA n/a 29 mA Max. RA100Z 0 mA n/a 12 mA Max. RTS151/RTS151KEY 0 mA/12 mA n/a 12 mA Max. RTS2-AOS 8 mA Max. 16 mA Max.40 mA Max. Note: Any combination of accessories may be used such that the given accessory loads are: 110 mA or less at the Aux output, and 50 mA or less at the Alarm output. GAMEWELL-FCI 12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118 www.gamewell-fci.com 9021-60470 Rev. C page 3 of 4 Installing the InnovairFlex Sampling Tube The InnovairFlex sampling tube may be installed from the front or back of the detector. The tube locks securely into place and can be removed by releasing the front or rear locking tab. (Figure 3 illustrates the front locking tab). Figure 1 Figure 2 Figure 3 Wiring for 4-wire Duct Smoke Detector and Accessories Figure 4 Wiring for 4-Wire Duct Smoke Detector and Accessories NOTE 1: 24V Power Inputs accept a non-polarized 24VDC or 24VAC 50-60Hz. 120VAC Power Inputs accept only 120VAC 50- 60Hz. Connect power source to appropriate terminals of each detector. See specifications for additional power supply information. NOTE 2: Auxiliary contacts shown in standby position. Contacts switch during alarm as indicated by arrows. Auxiliary contacts are not to be used for connection to the control panel. See specifications for contact ratings. NOTE 3: Supervisory contacts shown in standby position. Open contacts indicate a trouble condition to the panel. See specifica- tions for contact ratings. NOTE 4: Alarm Initiation contacts shown in standby position. Closed contacts indicate an alarm condition to the panel. See specifi- cations for contact ratings. NOTE 5: For additional information, refer to the InnovairFlex D4120 Duct Smoke Detector Installation Instructions, P/N I56-2967-002R and the Duct Application Smoke Detectors Application Guide. Important Notes on 2:1 Sensor-to-Power Capability • 2:1 sensor-to-power capability is only available on the D4120 4-wire conventional models. • 2:1 sensor-to-power capability can be enabled using one D4120 and one D4S, or two D4S and one D4P120. Important Interconnect Notes • When using the interconnect feature, all interconnected units must be powered using the same independent supply. • Polarity must be maintained throughout the interconnect wiring. Connect the INT+ terminal on unit 1 to the INT+ terminal on unit 2 and so on. Similarly, connect the INT/AUX– terminal on unit 1 to the INT/AUX- terminal on unit 2 and so on. • Up to 50 D4120 units, 50 D4P120 units, or 50 units of combination may be interconnected. • Up to 10 DH100ACDC units may be interconnected. Please note that each of the 9 DH100ACDC units interconnected may be replaced by three D4P120 units. Therefore, when using the interconnect feature a single DH100ACDC can drive either 9 DH100ACDCs or 27 D4120 units. NOTE: The alarm can be reset only at the initiating device and not at the devices interconnected. GAMEWELL-FCI 12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118 9021-60470 Rev. C page 4 of 4 www.gamewell-fci.com Accessories System Sensor provides system flexibility with a variety of accessories, including two remote test stations and several different means of visible and audible system annunciation. As with our duct smoke detectors, all duct smoke detector accessories are UL listed. Figure 5 RTS151 UL S2522 Figure 6 RTS151KEY UL S2522 Figure 7 APA151 UL S4011 Figure 8 RTS2-AOS UL S2522 Figure 9 RA100Z UL S2522 Figure 10 MHW UL S4011 Figure 11 MHR UL S4011 Figure 12 RTS2-AOS with PS24LOW Strobe and PS12/24 LENSW lens Ordering Information Part Number Description D4120 4-wire photoelectric low-flow duct smoke detector Accessories Part Number Description Part Number Description D4S 4-wire photoelectric sensor component only MHR Mini Horn, Red D4P120 4-wire photoelectric power board component only, 24 VAC/DC, 120 VAC MHW Mini Horn, White 2D51 4-wire conventional photoelectric sensor head P48-21-00 End cap for metal sampling tubes DST1 Metal sampling tube duct width up to 1ft (0.3m)PS12/24SLENSC Ceiling-mount “SMOKE” lens DST1.5 Metal sampling tube duct widths 1 ft to 2 ft (0.3 to 0.6 m) PS12/24SLENSW Wall-mount “SMOKE” lens DST3 Metal sampling tube duct widths 2 ft to 4 ft (0.6 to 1.2 m) PS24LO Mini-Alert add-on strobe (red) DST5 Metal sampling tube duct widths 4 ft to 8 ft (1.2 to 2.4 m)RA100Z/RA100ZA Remote annunciator alarm LED DST10 Metal sampling tube duct widths 8 ft to 12 ft (2.4 to 3.7 m) RTS151 Remote test station APA151 Remote annunciator with piezo alarm RTS151KEY Remote test station with key lock DH400 OE-1 Weatherproof enclosure RTS2 Multi-signaling accessory ETX Metal exhaust tube duct width 1ft (0.3m)AOS Add-On Strobe M02-04-00 Test magnet RTS2-AOS Multi-signaling accessory DF-60734:B1 • 8/15/2018 — Page 1 of 6 ECC-50/100(E) Emergency Command Center Emergency Communications DF-60734:B1 • C-200 General Fire•Lite’s ECC-50/100 and ECC-50/100E are multipurpose emer- gency voice evacuation panels for fire applications, mass notification applications, or both. The Primary Operating Consoles (POCs) deliver 50 or 100 watts of audio power for distribution to up to eight speaker circuits (i.e. zones). The ECC-50/100(E) comes standard with a single speaker circuit and a built-in 25Vrms, 50 watt amplifier. A secondary 50 watt amplifier (ECC-50W-25/70V) can be added for single speaker circuit backup or to increase system capacity to two speaker circuits and an additional 50 watts of audio power. An optional ECC-CE6 module added to the ECC-50/100(E) will upgrade the system to a maximum of eight speaker circuit outputs. All speaker output circuits can be wired in either Style Y (Class B) or Style Z (Class A) configuration. The ECC-50/100(E) has fourteen field programmable messages (up to 60 seconds each), built-in field configurable pre- and post-announce tone generators and a fully supervised Notification Appliance Circuit (NAC) with 2.0 amps of synchronized NAC power. The ECC-50/100(E) includes three built- in Form-C relay contacts, (AC power, trouble and MNS active) a NAC follower input for triggering the on board NAC circuit and 500mA special application power. A built-in power supply with switch mode technology delivers operational power to the panel and an onboard battery charger supports charging up to 26AH batteries (ECC cabinet holds up to 18AH batteries). For fire protection applications, the ECC-50/100(E) is an adjunct (slave) to any UL listed FACP, providing reverse polarity or contact closure; can be used as a stand-alone unit for non-fire applications. For seamless integration between fire and mass notification, the ECC-50/100(E) can be directly activated via serial communication between the ES-200X, MS-9600(UD)LS, or MS-9200UDLS. Activa- tion of the ECC-50/100(E) via other FACPs uses the eight on board Command Input Circuits (CMDs). Two of the eight CMD circuits (CMD 1 & CMD 2) can be individually field programmed for activa- tion by an FACP Notification Appliance Circuit reverse polarity and all eight can be activated by a contact closure. In addition, the ECC- 50/100(E) can be activated from a building's Private Branch Exchange (PBX) with the integral night ring feature. All ECC-50/100(E) programming is done by using a simple, built-in programming utility accessed from any laptop. For added flexibility, the ECC-50/100(E) supports both 25Vrms and 70.7Vrms speaker output operation. By adding a 70V transformer conversion module (ECC-XRM-70V) or an additional 70.7 volt secondary amplifier (ECC-50W-25/70V) the system supports 70.7 volt speaker devices. The ECC-50/100(E) can expand in order to accommodate larger or more complex installations. To add more control and increase sys- tem capacity, any combination of up to eight external remote con- soles (including the ECC-LOC, ECC-RPU, and ECC-RM) and up to eight distributed audio amplifiers (including the ECC-50DA(E), ECC- 50BDA and ECC-125-DA(E) can be connected on the external data bus and audio riser data bus to create a fully integrated command center. A fully loaded system supports up to 1100 watts of total audio power and up to 24 speaker circuit outputs. TYPICAL APPLICATIONS Features • UL Listed to UL 2572 Communication (Control Units Mass Notifi- cation Systems) and UL 864 (emergency voice evacuation for fire) • Modular design for system flexibility and easy expansion • Removable terminal blocks for ease of servicing and module replacement • 50 watts of 25V audio power (expandable to 100 watts) RMS • 2 amp Notification Appliance Circuit (NAC) output, sync genera- tor, or follower for System Sensor, Wheelock or Gentex protocols • Optional 70.7VRMS conversion transformer available for the pri- mary amplifier. (Note that speaker wiring continues to be super- vised in standby, alarm and when background music is playing with this optional transformer installed) • Eight Command Input Circuits to activate messages 1 to 8: –CMD1 and CMD2 are field selectable to be activated from 12 or 24 VDC Notification Appliance Circuits (reverse polarity) or con- tact closures –CMD3-CMD8 are activated by contact closures • Speaker Circuits –Single Style Y (Class B) or Style Z (Class A) speaker Circuit –Two Style Y (Class B) or Style Z (Class A) speaker circuits (with optional ECC-50W-25/70V Audio Amplifier installed) –Eight Style Y (Class B) or Style Z (Class A) speaker circuits (with optional ECC-50W-25/70V and ECC-CE6 installed) • 520Hz square wave tones available, which can be uploaded to the ECC-50/100 to meet NFPA Low Frequency requirements (Refer to the Device Compatibility Document 15384 for listed compatible speakers.) • ECC-50/100(E) can be controlled by an FACP via the ANN/ACS (EIA-485) link. Compatible FACPs include the ES-200X, MS- 9600(UD)LS, and MS-9200UDLS • Schools • Healthcare Facilities • Factories • Theaters • Military facilities • Restaurants • Auditoriums • Places of Worship • Office Buildings • Dormitories Page 2 of 6 — DF-60734:B1 • 8/15/2018 • Certified for seismic applications when used with the appropriate seismic mounting kit • Integral supervised microphone • Microphone time-out feature which reverts back to prerecorded message if emergency page exceeds the programmed time • 14 recorded messages • Field-selectable message and custom message recording capa- bility using the local microphone, a USB port, or an external audio input • External Audio Input can be used for background music • Up to 60 second message duration for all messages • Integral tone generators field selectable for multiple tone types • Powered by integral AC power supply or batteries during AC fail • Programmable delay of immediate, 2 hours or 6 hours reporting of AC Loss • Piezo sounder for local trouble • 100 event history log • Three Form-C relays: –AC Power Loss Relay - TB1 –System Trouble Relay - TB2 –MNS Active - TB3 • 500mA (0.5A) Special Application (auxiliary power) output for addressable modules when interfaced with compatible address- able FACPs and End-of-Line power supervision relays • System Status LEDs (Refer to “Controls and Indicators” in prod- uct manual LS10001-000FL-E.) • Integral Dress Panel • Optional TR-CE semi-flush trim ring • Any combination of up to eight (8) external remote consoles: –Optional ECC-RM Remote Microphone (includes cabinet) See DF-60760. –Optional ECC-RPU Remote Page Unit (includes cabinet) See DF-60761. –Optional ECC-LOC Local operator console (includes cabinet) See DF-60762. • Any combination of up to eight (8) distributed audio amplifiers: –Optional ECC-50DA(E) distributed amplifier, 50 watts. See DF- 60763. –Optional ECC-125DA(E) distributed amplifier, 125 watts. See DF-60763. –Optional ECC-50BDA distributed amplifier with backup, 100 watts.See DF-60760. Optional Internal Expansion Modules ECC-CE6: Circuit Expander Module provides connections for up to six Style Z (Class A) or Style Y (Class B) speaker circuits. Circuits are configured through the web-based programming utility. ECC-50W-25V: 25V, 50 watt audio amplifier module. Adding a sec- ond speaker circuit increases the total ECC-50/100 power output to 100 watts or can also be used as a backup amplifier. ECC-50W-70V: 70V, 50 watt audio amplifier module. Adding a sec- ond speaker circuit increases the total ECC-50/100 power output to 100 watts or can also be used as a backup amplifier. ECC-XRM-70V: 70V Transformer Conversion Module. Converts the ECC-50/100(E) primary amplifier to a 70V output. This transformer mounts directly to the ECC-50/100(E) main control board by two metal brackets. Control and Indicators PUSH BUTTON CONTROLS LED Status Indicators (visible with door closed) LED Indicators (visible with door and dress panel open) • Speaker Volume Control Fault (yellow) • Option Card Fault (yellow) • Amplifier Over Current Fault (yellow) • All Call • Message Select 1-14 • MNS Control • Diagnostic Select • System Control • Trouble Silence • Speaker Select 1-24 • Console Lamp Test • Fire System Active (green) • LOC/RPU/RM 1-8 Active (green) • MNS Control (green) • Main Console Fault (yellow) • System Control (green) • AC Power (green) • System in Use (green) • Ground Fault (yellow) • Speaker Zone 1-24 Active (green) • Charger Fault (yellow) • Speaker Zone 1-24 Fault (yellow) • Battery Fault (yellow) • OK to Page (green) • Data Bus Fault (yellow) • Microphone Trouble (yellow) • NAC Fault (yellow) • Message 1-8 Active (red)• NAC Active (green) • Message 1-8 Fault (yellow) • System Trouble (yellow) • Remote Amplifier 1-8 Fault (yellow) • Audio Riser Fault (yellow) • LOC/RPU/RM 1-8 Fault (yellow) DF-60734:B1 • 8/15/2018— Page 3 of 6 horns/strobes Speaker Circuits TB20 & TB21 NAC Circuit TB19 Internal options -CE6 circuit expander -25/70V optional amplifier -FFT firefighter telephone remote consoles -LOC local operator console -RPU remote paging unit -RM remote microphone TB4 TB12 TB22 distributed audio external battery charger - J7 -50DA 50W remote amplifier -125DA 125W remote amplifier CHG-120 charger CHG-75 charger -50BDA 50W remote amplifier Page 4 of 6 — DF-60734:B1 • 8/15/2018 Product Line Information ECC-50/100: (Primary Operating Console) 50 Watt, 25VRMS single speaker zone emergency voice evacuation system, integral micro- phone, built in tone generator and 14 recordable messages. ECC-50/100E: Export version (Primary Operating Console) 50 Watt, 25VRMS single speaker zone emergency voice evacuation system, integral microphone, built in tone generator and 14 recordable mes- sages. (240 VAC, 50Hz). ECC-CE6: Speaker Circuit/Zone Expander Module. ECC-50W-25V: 25V, 50 watt audio amplifier module. Adding a sec- ond speaker circuit increases the total ECC-50/100 power output to 100 watts or can also be used as a backup amplifier. ECC-50W-70V: 70V, 50 watt audio amplifier module. Adding a sec- ond speaker circuit increases the total ECC-50/100 power output to 100 watts or can also be used as a backup amplifier. ECC-XRM-70V: 70V Transformer Conversion Module. Converts the ECC-50/100(E) primary amplifier to a 70V output. This transformer mounts directly to the ECC-50/100(E) main control board by two metal brackets. ECC-LOC: Local Operator Console (Complete user interface), Please refer to the data sheet DF-60762 for more information. ECC-RPU: Remote Page Unit Hand held microphone, 14 message buttons. Please refer to the data sheet DF-60761 for more informa- tion. ECC-RM: Remote Microphone only. Please refer to the data sheet DF-60760 for more information. ECC-50DA: Distributed (Remote) Audio Amplifier, 50 watts. Please refer to the data sheet DF-60763 for more information. ECC-50DAE: Export version. Distributed (Remote) Audio Amplifier, 50 watts. (240 VAC, 50Hz). Please refer to the data sheet DF-60763 for more information. ECC-125DA: Distributed (Remote) Audio Amplifier, 125 watts. Please refer to the data sheet DF-60763 for more information. ECC-125DAE: Export version. Distributed (Remote) Audio Amplifier, 125 watts. (240 VAC, 50Hz). Please refer to the data sheet DF- 60763 for more information. ECC-50BDA: Distributed (Remote) Audio Amplifier with back up, 50 watts/100 watts at 25Vrms or 70Vrms. Please refer to the data sheet DF-60763 for more information. ECC-50WBU: Expander card for ECC-50BDA remote amplifier for 100 watt primary / 50 watt back up operation.Please refer to the data sheet DF-60763 for more information. ECC-CE4: Distributed Audio Speaker Circuit/Zone expander mod- ule. ECC-FFT: Fire Fighter Telephone System. Please refer to the data sheet DF-60765 for more information. ECC-RTZM: Remote Telephone Zone Module. Allows for secure access to the ECC via cell phone or remote telephone means; not UL listed.Please refer to the data sheet DF-60785 for more informa- tion. SEISKIT-COMMENC: Seismic kit for the ECC-50/100. Includes bat- tery bracket for two 12 AH or 18 AH batteries. FPJ-F: Remote Phone Jack. FHS-F: Fire Fighters Remote Handset. FHSC-RF: Fire Fighters Handset Cabinet Recessed. FHSC-SF: Fire Fighters Handset Cabinet Surface Mount. MMF-301: Addressable Mini-Monitor Module. I300: SLC Line Isolation Module. TR-CE: Optional Trim Ring. THUMBLTCH: Optional Thumb Latch. (Non UL-Listed). CHG-75: 25 to 75 ampere-hours (AH) External Battery Charger. CHG-120F: 25-120 ampere-hours (AH) External Battery Charger. ECC-MICROPHONE: Replacement Microphone only. BAT-1270: Battery,12 volt,7.0 AH (Two required). BAT-12120: Battery,12 volt,12.0 AH (Two required). BAT-12180: Battery,12 volt, 18.0 AH (Two required). Wiring Requirements See product manual, part number LS10001-000FL-E for detailed wiring requirements. Total System Capacity: (ECC-50/100(E) only) • Total Built-in Audio Power: 50 Watts. • Total Expandable Audio Power: 100 Watts. • Total Built-in Speaker Circuits: 2. • Total Expandable Speaker Circuits: 8. • Audio Message Max Time Duration: 60 seconds. • External Audio Input: 1. Total System Capacity: (Fully Loaded Sys- tem) • Total Distributed Audio Power: 1100 Watts. • Total Speaker Circuits Per System: 24. • Total Remote Consoles Supported: 8. • Total Distributed Audio Amplifiers Supported: 8. Electrical Specifications PRIMARY (AC) POWER (TB15) ECC-50/100: 120 VAC, 60 Hz, 3.5 amps. ECC-50/100E: 240 VAC, 50 Hz, 2.0 amps. Wire size: minimum #14 AWG (2.00mm2) with 600 V insulation. SECONDARY POWER (BATTERY) CHARGING CIRCUIT (J7) • Supports lead-acid batteries only. • Float charge voltage at 27.3V • Maximum charge current: 1.0 Amp • Maximum battery charge capability: 2.8 Amps, 26AH (ECC cabi- net holds max. 18AH battery). • Minimum Battery size:12 Amp Hour. AC LOSS RELAY CONTACT RATING (TB3) • 2.0 amps @ 30 VDC (resistive), 0.5 amps @ 30 VAC (resistive). FORM C - TROUBLE RELAY CONTACT RATING (TB2) • 2.0 amps @ 30 VDC (resistive), 0.5 amp @ 30 VAC (resistive). MNS ACTIVE RELAY CONTACT RATING (TB1) • 2.0 amps @ 30 VDC (resistive), 0.5 amps @ 30 VAC (resistive). NOTIFICATION APPLIANCE CIRCUIT (NAC) OUTPUT RAT- ING (TB19) • One (1) Style Y (Class B) or Style Z (Class A) circuit. • Power-limited circuitry, (Class 2) supervised. • Nominal operating voltage: 24 VDC. • Maximum signaling current for special application power: 2.0A. • Maximum signaling current for regulated power: 200mA. • Maximum wiring impedance: 1Ω. • Current limit: fuse-less, electronic, power-limited. DF-60734:B1 • 8/15/2018— Page 5 of 6 • End-Of-Line Resistor: 4.7 KΩ, ½ watt, (P/N 71252) required for Style Y (Class B) operation. Refer to the Device Compatibility Document 15384 for listed com- patible devices. NAC FOLLOWER OUTPUT REMOTE SYNC (TB18) • Connections for FACP NAC synchronization trigger signal. • Output terminals: pass-through to other system components. • Trigger input voltage: 9 to 32 VDC, 24 VDC rated. • Input current draw in Alarm condition: 10 mA at rated voltage. SPECIAL APPLICATION POWER (AUX. POWER) (TB17) • 500 mA @ 24 VDC. • Used for powering addressable modules and associated End-of- Line power supervision relays. Power-limited circuitry. Refer to the Device Compatibility Document 15384 for a list of compatible devices. SPEAKER VOLUME CONTROL OVERRIDE (TB23) • Style Y (Class B) or Style Z (Class A) circuit. • Special application power. • Power-limited circuitry, supervised. • Nominal operating voltage: 24 VDC. • Maximum signaling current: 0.25 amps. • Current limit: fuse-less, electronic, power-limited. • End-Of-Line Resistor: 4.7 KΩ, ½ watt, (P/N 71252) required for Style Y (Class B) operation. SPEAKER CIRCUITS • Primary Speaker Circuit (TB20) • Secondary Speaker Circuit (TB21) (with optional amplifier only). –Circuit can be wired Style Y (Class B) or Style Z (Class A). –Power-limited circuitry. –Normal Operating Voltage: 25 VRMS @ 2 amps max and maxi- mum Load Impedance of 12.5Ω (70.7 VRMS @ 700 mA max. with maximum load Impedance of 100Ω operation possible by plugging optional ECC-XRM-70V conversion transformer into J12 of the main control board). –Output Power: 50 watts (10 watts when background music is employed). –Frequency Range: 400Hz - 4,000Hz. –Maximum total capacitance for each speaker circuit: 250 µF. –End-of-Line Resistor required for Style Y circuit: 15 KΩ, 1 watt (P/N: ELR-15K). COMMAND INPUT CIRCUITS (ALARM POLARITIES SHOWN) CMD1 - TB4 Terminals 3(+) & 4(-) are input terminals and Terminals 1(-) and 2(+) are output terminals which provide feed through of the NAC circuits to NAC devices down stream. CMD2 - TB5 Terminals 3(+) & 4(-) are input terminals and Terminals 1(-) and 2(+) are output terminals which provide feed through of the NAC circuits to NAC devices downstream. CMD3 - TB6 Terminals 1(+) & 2(-) are input terminals for contact clo- sure only. CMD4 - TB6 Terminals 3(+) & 4(-) are input terminals for contact clo- sure only. CMD5 - TB7 Terminals 1(+) & 2(-) are input terminals for contact clo- sure only. CMD6 - TB7 Terminals 3(+) & 4(-) are input terminals for contact clo- sure only. CMD7 - TB8 Terminals 1(+) & 2(-) are input terminals for contact clo- sure only. CMD8 - TB8 Terminals 3(+) & 4(-) are input terminals for contact clo- sure only. • Power-limited and supervised circuitry. • Normal Operating Voltage Range: 10.5 VDC - 29 VDC; (Maxi- mum Voltage: 29 VDC). • NAC Reverse Polarity Current (requires End-of-Line Resistor from NAC): 1.6 mA maximum. • Contact Closure Operation Current (requires 4.7KΩ, ½ watt End- of-Line Resistor P/N 27072): 6.6 mA maximum. • Maximum Wiring Impedance CMD1 - CMD8 (Contact Closure Operation): 200Ω. NOTE: When the system is programmed for Mass Notification, CMD1and CMD2 will be programmed for Reverse Polarity only. See manual P/N LS10001-000FL-E for more details. MAXIMUM INPUT IMPEDANCE: • CMD1 & CMD2 (Reverse Polarity Operation): 20KΩ. • CMD1 - CMD8 (Contact Closure Operation): 4.75KΩ. NIGHT RING INPUT - TB16, TERMINALS 1 (+) & 2 (-) • Contact closure input. • Isolated, non-supervised. • Operation current: 3.8 mA, maximum. • Maximum wiring impedance: 30KΩ. • Minimum isolation withstand voltage: 1500 VRMS. EXTERNAL OPERATOR INTERFACE POWER OUTPUT (TB24) • Non-resettable power for external operator interface components. • Power-limited circuitry, non-supervised. • Nominal operating voltage: 24 VDC. • Maximum output current: 0.80 amps. • Current limit: fuse-less, electronic, power-limited circuit. EXTERNAL DATA BUS (EIA-485) (TB12) • Data connections for external operator interface components. • Redundant transceiver circuitry for Class A operability. • Power-limited circuitry, supervised. • Maximum wiring impedance: 13.2Ω FACP DATA BUS (EIA-485) (TB13) • Dedicated connection to FACP serial bus. • Output terminals: pass-through to other system components. • Isolated, supervised. • Minimum isolation withstand voltage: 1500 VRMS. • Maximum wiring impedance: 40Ω (ANN-BUS), 26Ω (ACS-BUS). • External Audio Riser (TB22). • Style Y (Class B) or Style Z (Class A) audio connections to exter- nal operator interface components. • Power-limited circuitry, supervised. • Audio signal level: 3.85 V, maximum. • Frequency range: 400 Hz - 4 KHz RMS. • Frequency range (ECC-50/125DA): 800Hz - 2KHz RMS. Fire-Lite® Alarms is a registered trademark of Honeywell International Inc. ©2018 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited. Page 6 of 6 — DF-60734:B1 • 8/15/2018 This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice. For more information, contact Fire•Lite Alarms. Phone: (800) 627-3473, FAX: (877) 699-4105. www.firelite.com Country of Origin: USA Electrical Specifications Display Board EXTERNAL AUDIO INPUT (TB5) • Input Impedance: 8.5KΩ nominal @1KHz • Input Voltage: 700 mV rms maximum • Input Current: 0.1 mA maximum @ 700 mV NOTE: Some laptops/personal computers only provide an audio output for headphones. It may be necessary to adjust the headphone output level for proper recording of voice messages. ECC-CE6 Circuit Expander Module Specifi- cations • Power-limited circuitry. • Up to six (6) circuits on the ECC-CE6 can be wired as Style Y (Class B) or Style Z (Class A). • Normal Operating Voltage for Speaker Circuits: 25 VRMS @ 2.0 amps max. (Maximum Load Impedance of 12.5Ω). • 70.0 VRMS @ 700 mA max. with maximum Load Impedance of 100Ω operation possible for the primary circuit by plugging in an optional ECC-XRM-70V conversion transformer into J12 of the main control board. The same operation is possible for the optional 50W amplifier by selecting the ECC-50W-70V model. • Speaker circuit wiring is supervised during standby, background music, and alarm. • Output Power: 50 watts total; Frequency Range: 400Hz - 4,000Hz. • Maximum total capacitance: 250 µF. (Note that the total capaci- tance for the speaker outputs must not exceed the maximum of 250 µF.) • End-of-Line Resistor required for Style Y (Class B) speaker cir- cuit: 15 KΩ, 1 watt (P/N: ELR-15K) TB13 on the main control board: ACS/ANN (EIA-485) electrically isolated link to FACP pro- vides programmed speaker control. Cabinet Specifications • Backbox: 19.0"(48.26 cm) high x 16.65"(42.29 cm) wide x 5.20"(13.23 cm) deep. • Door: 19.26” (48.92 cm) high x 16.82”(42.73 cm) wide x 0.12”(0.30 cm) deep. • Trim Ring (TR-CE): 22.00” (55.88 cm) high x 19.65” (49.91 cm) wide. Shipping Specifications Base Unit Weight: 27.85 lbs (12.63 kg). Temperature and Humidity ranges This system meets NFPA requirements for operation at 0 – 49°C/32 – 120°F and at a relative humidity 93% ± 2% RH (noncondensing) at 32°C ± 2°C (90°F ± 3°F). However, the useful life of the system's standby batteries and the electronic components may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and its peripherals be installed in an environment with a normal room temperature of 15 – 27°C/60 – 80°F. Agency Listings and Approvals The listings and approvals below apply to the basic ECC-50/100(E) control panel. In some cases, certain modules may not be listed by certain approval agencies or listing may be in process. Consult fac- tory for latest listing status. • UL/ULC Listed: S2424 • CSFM: 6911-0075:0226 • NYC Fire Dept. Certificate of Approval: #6152 • FM Approved Standards and Codes The ECC-50/100(E) complies with the following UL Standards, NFPA 72, International Building Codes, and California Building Codes. • UL 864 • UL 2572 • UFC 4-021-01 • IBC 2012, IBC 2009, IBC 2006, IBC 2003, IBC 2000 (Seismic) • CBC 2007 (Seismic) DF-60957:C • 7/16/2018 — Page 1 of 4 ES-200X Intelligent Addressable FACP with Communicator Addressable Fire Alarm Control Panels DF-60957:C General The ES-200X is the latest intelligent addressable Fire Alarm Control Panel (FACP) from Fire•Lite Alarms and is a direct replacement for the MS-9200UDLS. The ES-200X comes with a pre-installed com- municator and supports up to 198 addressable devices (99 detec- tors and 99 modules). With an extensive list of powerful features, the ES-200X programs just like Fire•Lite’s other addressable products, yet fits into applications previously served only by conventional pan- els. The pre-installed IPOTS-COM is a dual technology (POTS and IP) communicator. The POTS transmits system status (alarms, troubles, AC loss, etc.) to a Central Station via the public switched telephone network. The IP communicator’s internet monitoring capability sends alarm signals over the Internet saving the monthly cost of two dedi- cated business telephone lines. Although not required, the second- ary telephone line may be retained providing backup communication over the public switched telephone line. Optional cellular reporting is available using the CELL-MOD or CELL-CAB-FL. Remote and local programming of the control panel is possible using the FS-Tools Upload/Download utility. Programming databases can be uploaded/downloaded via the panel’s USB port (and USB cable) or via an ethernet connection using the IPOTS-COM communicator. The USB port also allows for the download or upload of the entire program, history file, walk-test data, current status and system volt- ages by means of a USB flash drive. The power supply and all electronics are contained on a circuit board supported on a new quick install chassis and housed in a metal cabinet. Available accessories include local and remote upload/download software, remote annunciators, and reverse polar- ity/city box transmitter (4XTMF). Features • Listed to UL Standard 864, 10th edition • Pre-installed IPOTS-COM Ethernet IP and POTS (Plain Old Tele- phone Service) Central Station Communicator over AlarmNet • Optional CELL-MOD or CELL-CAB-FL GSM Central Station Communicator over AlarmNet® • Automated activation of the ECC-50/100 Emergency Command Center • ECC-FFT Firefighter Telephone option • Compatible with SWIFT® wireless devices • Auto-programming (learn mode) reduces installation time. Reports two devices set to the same address • Four built-in, independently programmable Style Z (Class A) or Style Y (Class B) NAC circuits • Selectable strobe synchronization for System Sensor, Wheelock, and Gentex devices • Notification Appliance Circuit End of Line resistor matching • Four programmable function keys for ease of maintenance • Two programmable relays and one fixed trouble relay • Built-in Programmer • Integral 80-character LCD display with backlighting • Real-time clock/calendar with automatic daylight savings control • History file with 1,000 event capacity • Addressable sounder base compatibility • Multi-criteria detector (smoke, heat, CO) with programmable response • Control module delay timer • Automatic detector sensitivity testing (NFPA 72 compliant) • Automatic device type-code verification • Point trouble identification • Waterflow selection per module point • Alarm verification selection per detector point • Maintenance alert warns when smoke detector dust accumula- tion is excessive • One-person audible or silent walk test with walk-test log and printout • System alarm verification selection per detector point • PAS (Positive Alarm Sequence) and Pre-signal per point (NFPA 72 compliant) • Up to 16 ANN-BUS annunciators- 8 per each ANN-Bus • Remote Acknowledge, Alarm Silence, Reset and Drill via addressable modules or remote annunciator • Upload/Download of program and data via USB with optional FS- Tools Programming Utility SLC COMMUNICATION LOOP • Supports LiteSpeed™ and CLIP protocols • SLC operates up to 10,000 ft. (3,000 m) in LiteSpeed mode with twisted, unshielded wire • Single addressable SLC loop which meets NFPA Class B and Class A requirements • 198 addressable device capacity (99 addressable detectors and 99 modules) • Compatible with Fire•Lite’s addressable devices (refer to the SLC Wiring Manual) NOTIFICATION APPLIANCE CIRCUITS (NACS) • Four independently programmable output circuits. Circuits can be configured for the following outputs: –Style Y (Class B) –Style Z (Class A) • Silence Inhibit and Autosilence timer options • Continuous, March Time, Temporal, or California code for main circuit board NACs with two-stage capability • Selectable strobe synchronization per NAC • 2.5 A special application, 250mA regulated, total power for NACs NOTE: Maximum or total 24VDC system power shared between all NAC circuits and the ANN-BUS is 2.7 A Page 2 of 4 — DF-60957:C • 7/16/2018 PROGRAMMING AND SOFTWARE • Autoprogramming (learn mode) reduces installation time • Custom English labels (per point) may be manually entered or selected from an internal library file • Two programmable Form-C relay outputs • 99 software zones • Continuous fire protection during online programming • Program Check automatically catches common errors not linked to any zone or input point •OFFLINE PROGRAMMING: Create the entire program in your office using FS-Tools, a Windows®-based software package, and upload/download system programming locally. Offline program- ming requires an ethernet connection. FS-Tools is available on www.firelite.com. User interface LED INDICATORS • Fire Alarm (red) • CO Alarm (red) • AC Power (green) • Supervisory (yellow) • Trouble (yellow) • Ground fault (yellow) • Battery fault (yellow) • Disabled (yellow) • Maintenance (yellow) • Communication (yellow) • Alarm Silenced (yellow) • F1-F4 Programmable Function Keys (yellow) KEYPAD • 16 key alpha-numeric pad • Acknowledge • Alarm Silence • Drill (Manual Evacuate) • Four (4) programmable function keys • Reset (lamp test) PRODUCT LINE INFORMATION ES-200X: Addressable Fire Alarm Control Panel with one SLC loop. Includes main circuit board with display, pre-installed communicator, chassis with transformer, backbox with door, plastic bag containing screws, cables, key, etc. (For ES-200XC, refer to DF-60958.) FS-Tools: Programming software for Windows®-based PC com- puter. Available for download at www.firelite.com. CELL-CAB-FL/CELL-MOD: Optional GSM communicators. IPOTS-COM: Dual technology (POTS and IP) communicator. (replacement board) DP-ES-R: Optional dress panel for the ES-200X. TR-CE: Optional trim ring for semi-flush mounting. BB-2F: Optional cabinet for one or two modules. BB-6F: Optional cabinet for up to six modules mounted on CHS-6 chassis. BB-26: Battery backbox, holds up to two 25 AH batteries and CHG- 75. BB-55F: Battery box, houses two 55 AH batteries CHS-6: Chassis, mounts up to six multi-modules in a BB-6F cabinet. CHG-75: Battery charger for lead-acid batteries with a rating of 25 to 75 AH. CHG-120F: Remote battery charging system for lead-acid batteries with a rating of 55 to 120 AH. Requires additional BB-55F for mount- ing. BAT Series: Batteries, see data sheet DF-52397. PRN Series: UL listed compatible event printer. Uses tractor-fed paper. OPTIONAL MODULES 4XTMF Reverse Polarity Transmitter Module: Provides a super- vised output for local energy municipal box transmitter, alarm and trouble. Includes a disable switch and disable trouble LED. PWRMOD24 Power Expander Module: Optional power module. Increases alarm power output to 6 amps. COMPATIBLE ANNUNCIATORS ANN-80: Remote LCD annunciator mimics the information dis- played on the FACP LCD display. Recommended wire type is un- shielded. ANN-100: Remote LCD annunciator mimics the information dis- played on the FACP LCD display. Recommended wire type is un- shielded. For use in FM applications only. ANN-I/O: LED Driver Module provides connections to a user sup- plied graphic annunciator. (See DF-52430.) ANN-LED: Annunciator Module provides three LEDs for each zone: Alarm, Trouble, and Supervisory. Ships with red enclosure. (See DF- 60241.) ANN-RLED: Provides alarm (red) indicators for up to 30 input zones or addressable points. (See DF-60241.) ANN-RLY: Relay Module provides 10 programmable Form-C relays. Can be mounted inside the cabinet. (See DF-52431.) ANN-S/PG: Serial/Parallel Printer Gateway module provides a con- nection for a serial or parallel printer. (See DF-52429.) ADDRESSABLE DEVICES All feature a polling LED and rotary switches for addressing. SD365: Addressable low-profile photoelectric smoke detector. Lite- Speed only. SD365-IV: Addressable low-profile photoelectric smoke detector. Ivory. LiteSpeed and CLIP mode. SD365T: Addressable low-profile photoelectric smoke detector with thermal sensor. LiteSpeed only. SD365T-IV: Addressable low-profile photoelectric smoke detector with thermal sensor. Ivory. LiteSpeed and CLIP mode. SD365R: Remote test capable addressable photoelectric smoke detector for use with DNR(W) duct detector housing. LiteSpeed only. SD365R-IV: Remote test capable addressable photoelectric smoke detector for use with DNR(W) duct detector housing. Ivory. Lite- Speed and CLIP mode. H365: Low-profile 135°F fixed thermal sensor. LiteSpeed only. H365-IV: Low-profile 135°F fixed thermal sensor. Ivory. LiteSpeed and CLIP mode. H365R: Low-profile, intelligent, rate-of-rise thermal sensor. Lite- Speed only. H365R-IV: Low-profile, intelligent, rate-of-rise thermal sensor. Ivory. LiteSpeed and CLIP mode. H365HT: Low-profile intelligent 190°F/88°C fixed thermal sensor. LiteSpeed only. H365HT-IV: Low-profile intelligent 190°F/88°C fixed thermal sensor. Ivory. LiteSpeed and CLIP mode. Legacy Devices CP355: Addressable low-profile ionization smoke detector. SD355: Addressable low-profile photoelectric smoke detector. SD355T: Addressable low-profile photoelectric smoke detector with thermal sensor. SD355R: Remote test capable addressable photoelectric smoke detector for use with DNR(W) duct detector housing. SD355CO: Addressable, low-profile device that provides fire, heat, and carbon monoxide (CO) detection. H355: Fast-response, low-profile heat detector. DF-60957:C • 7/16/2018— Page 3 of 4 H355R: Fast-response, low-profile heat detector with rate-of-rise option. H355HT: Fast-response, low-profile heat detector that activates at 190°F/88°C. AD355: Low-profile, intelligent, “Adapt” multi-sensor detector (B350LP base included). B200S: Programmable, addressable sounder base. B200SR: Addressable sounder base. BEAM355: Intelligent beam smoke detector. BEAM355S: Intelligent beam smoke detector with integral sensitiv- ity test. D355PL: InnovairFlex low-flow non-relay duct-detector housing; includes SD355R. DNR: InnovairFlex low-flow non-relay duct-detector housing. (Order SD355R/SD365R separately.) DNRW: InnovairFlex low-flow non-relay duct-detector housing, with NEMA-4 rating. Watertight. (Order SD355R/SD365R separately.) Addressable Modules MMF-300: Addressable Monitor Module for one zone of normally- open dry-contact initiating devices. Mounts in standard 4.0" (10.16 cm.) box. Includes plastic cover plate and end-of-line resistor. Mod- ule may be configured for either a Style B (Class B) or Style D (Class A) IDC. MDF-300: Dual Monitor Module. Same as MMF-300 except it pro- vides two Style B (Class B) only IDCs. MMF-301: Miniature version of MMF-300. Excludes LED and Style D option. Connects with wire pigtails. May mount in device backbox. MMF-302: Similar to MMF-300. Addressable Monitor Module for one zone of conventional two-wire detectors. Requires resettable 24 VDC power. Refer to the Device Compatibility Document for listed compatible devices and quantity limitation. CMF-300: Addressable Control Module for one Style Y/Z (Class B/ A) zone of supervised polarized Notification Appliances. Mounts directly to a 4.0" (10.16 cm.) electrical box. NAC option requires external 24 VDC to power notification appliances. CRF-300: Addressable relay module containing two isolated sets of Form-C contacts, which operate as a DPDT switch. Mounts directly to a 4.0" (10.16 cm.) box, surface mount using the SMB500. BG-12LX: Addressable manual pull station with interface module mounted inside. I300: This module isolates the SLC loop from short circuit conditions (required for Style 6 or 7 operation). ISO-6: Six-fault isolator module. Mount one or two modules in a BB-2F cabinet (optional). Mount up to six modules on a CHS-6 chassis in a BB-6F cabinet. SMB500: Used to mount all modules except the MMF-301 and M301. MMF-300-10: Ten-input monitor module. Mount one or two modules in a BB-2F cabinet (optional). Mount up to six modules on a CHS-6 chassis in a BB-6F cabinet. MMF-302-6: Six-zone interface module. Mount one or two modules in a BB-2F cabinet (optional). Mount up to six modules on a CHS-6 chassis in a BB-6F cabinet. CMF-300-6: Six-circuit supervised control module. Mount one or two modules in a BB-2F cabinet (optional). Mount up to six modules on a CHS-6 chassis in a BB-6F cabinet. CRF-300-6: Six-relay control module (Form-C relays). Mount one or two modules in a BB-2F cabinet (optional). Mount up to six modules on a CHS-6 chassis in a BB-6F cabinet. SWIFT Wireless Devices W-GATE: LiteSpeed Wireless Gateway W-SD355: LiteSpeed intelligent, wireless photo detector. W-H355R: LiteSpeed intelligent wireless rate of rise (135°) heat detector. W-SD355T: Intelligent wireless photo/heat detector. W-H355: LiteSpeed intelligent wireless fixed-temperature (135°) heat detector. W-MMF: LiteSpeed Intelligent wireless monitor module. W-CRF: LiteSpeed Intelligent wireless relay module. W-BG12LX: LiteSpeed Intelligent wireless pull station. WAV-RL, WAV-WL,WAV-CRL,WAV-CWL: LiteSpeed Intelligent AV bases. W-USB: Wireless USB radio/antenna dongle that plugs into the USB port of a PC running SWIFT Tools. SWIFT Tools: Programming and diagnostic utility for the Wireless Gateway and devices. Available for download from firelite.com. NOTE: For more information on Compatible Addressable Devices for use with the ES-200X, see the following data sheets (document num- bers): SD365 Series (DF-61010), H365 Series (DF-61011), AD355 (DF-52386), BG-12LX (DF-52013), CMF-300-6 (DF-52365), CRF-300-6 (DF-52374), CMF/CRF Series (DF-52130), CP355 (DF-52383), H355 Series (DF-52385), I300 (DF-52389), ISO-6 (DF-60485), MMF-300 Series/MDF-300 (DF-52121), MMF-300-10 (DF-52347), MMF-302-6 (DF-52356), SD355/SD355T (DF-52384), and SLC Wiring Manual (51309). NOTE: Legacy 300 Series detection devices such as the CP300/CP350, SD300(T)/SD350(T) and older modules such as the M300, M301, M302, C304, and BG-10LX are not compatible with LiteSpeed polling. If the SLC contains one of these devices, polling must be set for standard CLIP protocol. Please consult factory for further information on previous 300 Series devices. ADDRESSABLE DEVICE ACCESSORIES End-of-Line Resistor Assembly (R-47K and R-3.9K): The 47k ohm assembly supervises the MMF-300, MDF-300, MMF-301, and CMF-300 module circuits. The 3.9k ohm assembly supervises the MMF-302 module circuit. These resistors are included with each module. Power Supervision Relay: Supervises the power to 4-wire smoke detectors and notification appliances. Wiring Requirements While shielded wire is not required, it is recommended that all SLC wiring be twisted-pair to minimize the effects of electrical interfer- ence. Refer to the panel manual for wiring details. AlarmNet®, Fire-Lite® Alarms, SWIFT®, and System Sensor® are registered trademarks of Honeywell International Inc. Microsoft® and Windows® are registered trademarks of the Microsoft Corporation. ©2018 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited. Page 4 of 4 — DF-60957:C • 7/16/2018 This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice. For more information, contact Fire•Lite Alarms. Phone: (800) 627-3473, FAX: (877) 699-4105. www.firelite.com Country of Origin: USA SYSTEM SPECIFICATIONS System Capacity • Intelligent Signaling Line Circuits................................................1 • Addressable device capacity..................................................198 • Programmable software zones.................................................99 • Annunciators.............................................................................16 Electrical Specifications AC Power: Operates in either 120 or 240 VAC, 50/60 Hz, 3.25 A, auto-sensing- no switch required. Wire size: minimum 14 AWG (2.00 mm2) with 600 V insulation. Nonpower-limited, supervised. Battery: Two 12 V 18 AH lead-acid batteries. Battery Charger Capacity: 7-18 AH (ES-200X cabinet holds maximum of two 18 AH batteries.) Communication Loop: Supervised and power-limited. Notification Appliance Circuits: Terminal Block provides connec- tions for four NACs, Style Y (Class B) or Style Z (Class A). Special Application power. Power-limited, supervised circuitry. Maximum signaling current per circuit: 2.5 amps special application, 250mA regulated. End-of-Line Resistor: 4.7k ohm, ½ watt (P/N 71252 UL listed) for Style Y (Class B) NAC; system capable of 1.9 kΩ - 22 kΩ ELR range. Refer to the Fire•Lite Device Compatibility Document for listed compatible devices. Two Programmable Relays and One Fixed Trouble Relay: Con- tact rating: 2.0 A @ 30 VDC (resistive), 0.5 A @ 30 VAC (resistive). Form-C relays, non-power-limited, non-supervised. Cabinet Specifications Door: 19.26" (48.92 cm.) high x 16.82" (42.73 cm.) wide x 0.72" (1.82 cm.) deep. Backbox: 19.00" (48.26 cm.) high x 16.65" (42.29 cm.) wide x 5.25" (13.34 cm.) deep. Trim Ring (TR-CE): 22.00" (55.88 cm.) high x 19.65" (49.91 cm.) wide. Shipping Specifications Weight: 26.9 lbs. (12.20 kg.) Dimensions: 20.00” (50.80 cm.) high x 22.5” (57.15 cm.) wide x 8.5” (21.59 cm.) deep. Temperature and Humidity Ranges This system meets NFPA requirements for operation at 0 – 49°C/32 – 120°F and at a relative humidity 93% ± 2% RH (noncondensing) at 32°C ± 2°C (90°F ± 3°F). However, the useful life of the system's standby batteries and the electronic components may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and its peripherals be installed in an environment with a normal room temperature of 15 – 27°C/60 – 80°F. NFPA Standards The ES-200X complies with the following NFPA 72 Fire Alarm Sys- tems requirements: – LOCAL (Automatic, Manual, Waterflow and Sprinkler Supervi- sory). – AUXILIARY (Automatic, Manual and Waterflow) (requires 4XTMF). – REMOTE STATION (Automatic, Manual and Waterflow) (Where a DACT is not accepted, the alarm, trouble and supervi- sory relays may be connected to UL 864 listed transmitters. For reverse polarity signaling of alarm and trouble, 4XTMF is required.) – PROPRIETARY (Automatic, Manual and Waterflow). – CENTRAL STATION (Automatic, Manual and Waterflow, and Sprinkler Supervised). –OT, PSDN (Other Technologies, Packet-switched Data Net- work) – IBC 2012, IBC 2009, IBC 2006, IBC 2003, IBC 2000 (Seismic). – CBC 2007 (Seismic) Agency Listings and Approvals The listings and approvals below apply to the basic ES-200X control panel. In some cases, certain modules may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status. •UL: S624 •FM approved •CSFM: 7165-0075:500 •FDNY: COA #6261 NOTE: See DF-60958 for ULC-listed model. DF-52121:E • 07/30/2015 — Page 1 of 4 MMF-300(A) Series, MDF-300 Addressable Monitor Modules Addressable Devices DF-52121:E • E-325 General Four different monitor modules are available for Fire•Lite’s intelligent control panels to suit a variety of applications. Moni- tor modules are used to supervise a circuit of dry-contact input devices, such as conventional heat detectors and pull stations, or monitor and power a circuit of two-wire smoke detectors (MMF-302(A)). MMF-300(A) is a standard-sized module (typically mounts to a 4" [10.16 cm] square box) that supervises either a Style D (Class A) or Style B (Class B) circuit of dry-contact input devices. MMF-301(A) is a miniature monitor module a mere 1.3" (3.302 cm) H x 2.75" (6.985 cm) W x 0.65" (1.651 cm) D that super- vises a Style B (Class B) circuit of dry-contact input devices. Its compact design allows the MMF-301(A) to be mounted in a single-gang box behind the device it monitors. MMF-302(A) is a standard-sized module used to monitor and supervise compatible two-wire, 24 volt, smoke detectors on a Style D (Class A) or Style B (Class B) circuit. MDF-300(A) is a standard-sized dual monitor module used to monitor and supervise two independent two-wire Style B (Class B) dry-contact initiating device circuits (IDCs) at two separate, consecutive addresses in intelligent, two-wire sys- tems. LiteSpeed™ is a communication protocol developed by Fire•Lite Engineering that greatly increases the speed of com- munication between analog intelligent devices. Intelligent devices communicate in a grouped fashion. If one of the devices within the group has new information, the panel CPU stops the group poll and concentrates on single points. The net effect is response speed greater than five times that of other communication protocols. MMF-300(A) Monitor Module • Built-in type identification automatically identifies this device as a monitor module to the control panel. • Powered directly by two-wire SLC loop. No additional power required. • High noise (EMF/RFI) immunity. • SEMS screws with clamping plates for ease of wiring. • Direct-dial entry of address: 01 – 159 on MS-9600 series panels, 01 – 99 on other compatible systems. • LED flashes during normal operation and latches on steady to indicate alarm. The MMF-300(A) Monitor Module is intended for use in intelli- gent, two-wire systems, where the individual address of each module is selected using the built-in rotary switches. It pro- vides either a two-wire or four-wire fault-tolerant Initiating Device Circuit (IDC) for normally-open-contact fire alarm and supervisory devices. The module has a panel-controlled LED indicator. The MMF-300(A) can be used to replace M300(A) modules in existing systems. MMF-300(A) APPLICATIONS Use to monitor a zone of four-wire smoke detectors, manual fire alarm pull stations, waterflow devices, or other normally- open dry-contact alarm activation devices. May also be used to monitor normally-open supervisory devices with special supervisory indication at the control panel. Monitored circuit may be wired as an NFPA Style B (Class B) or Style D (Class A) Initiating Device Circuit. A 47K Ohm End-of-Line Resistor (provided) terminates the Style B circuit. No resistor is required for supervision of the Style D circuit. MMF-300(A) OPERATION Each MMF-300(A) uses one of the available module addresses on an SLC loop. It responds to regular polls from the control panel and reports its type and the status (open/nor- mal/short) of its Initiating Device Circuit (IDC). A flashing LED indicates that the module is in communication with the control panel. The LED latches steady on alarm (subject to current limitations on the loop). MMF-300(A) SPECIFICATIONS Nominal operating voltage: 15 to 32 VDC. Maximum current draw: 5.0 mA (LED on). Average operating current: 375 µA (LED flashing), 1 com- munication every 5 seconds, 47k EOL. Maximum IDC wiring resistance: 1500 Ohms. Maximum IDC Voltage: 11 Volts. EOL resistance: 47K Ohms. Temperature range: 32°F to 120°F (0°C to 49°C). Humidity range: 10% to 93% noncondensing. Dimensions: 4.5" (11.43 cm) high x 4" (10.16 cm) wide x 1.25" (3.175 cm) deep. Mounts to a 4" (10.16 cm) square x 2.125" (5.398 cm) deep box. MMF-301(A) Mini Monitor Module • Built-in type identification automatically identifies this device as a monitor module to the panel. • Powered directly by two-wire SLC loop. No additional power required. • High noise (EMF/RFI) immunity. MMF-300(A) (Type H) 69 9 9 c o v . j p g Page 2 of 4 — DF-52121:E • 07/30/2015 • Tinned, stripped leads for ease of wiring. • Direct-dial entry of address: 01 – 159 on MS-9600 series panels, 01 – 99 on other compatible systems The MMF-301(A) Mini Monitor Module can be installed in a single-gang junction directly behind the monitored unit. Its small size and light weight allow it to be installed without rigid mounting. The MMF-301(A) is intended for use in intelligent, two-wire systems where the individual address of each module is selected using rotary switches. It provides a two-wire initiat- ing device circuit for normally-open-contact fire alarm devices. The MMF-301(A) can be used to replace M301(A) modules in existing systems. MMF-301(A) APPLICATIONS Use to monitor a single device or a zone of four-wire smoke detectors, manual fire alarm pull stations, waterflow devices, or other normally-open dry-contact devices. May also be used to monitor normally-open supervisory devices with special supervisory indication at the control panel. Monitored circuit/ device is wired as an NFPA Style B (Class B) Initiating Device Circuit. A 47K Ohm End-of-Line Resistor (provided) terminates the circuit. MMF-301(A) OPERATION Each MMF-301(A) uses one of the available module addresses on an SLC loop. It responds to regular polls from the control panel and reports its type and the status (open/nor- mal/short) of its Initiating Device Circuit (IDC). MMF-301(A) SPECIFICATIONS Nominal operating voltage: 15 to 32 VDC. Average operating current: 350 µA, 1 communication every 5 seconds, 47k EOL; 600 µA Max. (Communicating, IDC Shorted). Maximum IDC wiring resistance: 1500 Ohms. Maximum IDC Voltage: 11 Volts. Maximum IDC Current: 450 µA. EOL resistance: 47K Ohms. Temperature range: 32°F to 120°F (0°C to 49°C). Humidity range: 10% to 93% noncondensing. Dimensions: 1.3" (3.302 cm) high x 2.75" (6.985 cm) wide x 0.65" (1.651 cm) deep. Wire length: 6" (15.24 cm) minimum. MMF-302(A) Interface Module • Supports compatible two-wire smoke detectors. • Supervises IDC wiring and connection of external power source. • High noise (EMF/RFI) immunity. • SEMS screws with clamping plates for ease of wiring. • Direct-dial entry entry of address: 01 – 159 on MS-9600 series panels, 01 – 99 on other compatible systems. • LED flashes during normal operation. • LED latches steady to indicate alarm on command from control panel. The MMF-302(A) Interface Module is intended for use in intelli- gent, addressable systems, where the individual address of each module is selected using built-in rotary switches. This module allows intelligent panels to interface and monitor two- wire conventional smoke detectors. It transmits the status (normal, open, or alarm) of one full zone of conventional detectors back to the control panel. All two-wire detectors being monitored must be UL compatible with the module. The MMF-302(A) can be used to replace M302(A) modules in existing systems. MMF-302 (A) APPLICATIONS Use the MMF-302(A) to monitor a zone of two-wire smoke detectors. The monitored circuit may be wired as an NFPA Style B (Class B) or Style D (Class A) Initiating Device Circuit. A 3.9 K Ohm End-of-Line Resistor (provided) terminates the end of the Style B or D (class B or A) circuit (maximum IDC loop resistance is 25 Ohms). Install ELR across terminals 8 and 9 for Style D application. MMF-302(A) OPERATION Each MMF-302(A) uses one of the available module addresses on an SLC loop. It responds to regular polls from the control panel and reports its type and the status (open/nor- mal/short) of its Initiating Device Circuit (IDC). A flashing LED indicates that the module is in communication with the control panel. The LED latches steady on alarm (subject to current limitations on the loop). MMF-302(A) SPECIFICATIONS Nominal operating voltage: 15 to 32 VDC. Maximum current draw: 5.1 mA (LED on). Maximum IDC wiring resistance: 25 Ohms. Average operating current: 270 µA, 1 communication and 1 LED flash every 5 seconds, 3.9k eol. EOL resistance: 3.9K Ohms. External supply voltage (between Terminals T10 and T11): • DC voltage: 24 volts power limited. • Ripple voltage: 0.1 Vrms maximum. • Current: 90 mA per module maximum. Temperature range: 32°F to 120°F (0°C to 49°C). Humidity range: 10% to 93% noncondensing. Dimensions: 4.5" (11.43 cm) high x 4" (10.16 cm) wide x 1.25" (3.175 cm) deep. Mounts to a 4" (10.16 cm) square x 2.125" (5.398 cm) deep box. MDF-300(A) Dual Monitor Module The MDF-300(A) Dual Monitor Module is intended for use in intelligent, two-wire systems. It provides two independent two- wire initiating device circuits (IDCs) at two separate, consecutive addresses. It is capable of monitoring normally open contact fire alarm and supervisory devices. The module has a single panel- controlled LED. 67 2 0 m 1 0 1 . w m f DF-52121:E • 07/30/2015 — Page 3 of 4 NOTE: The MDF-300(A) provides two Style B (Class B) IDC cir- cuits ONLY. Style D (Class A) IDC circuits are NOT supported in any application. MDF-300(A) SPECIFICATIONS Normal operating voltage range: 15 to 32 VDC. Maximum current draw: 6.4 mA (LED on). Average operating current: 750 µA (LED flashing). Maximum IDC wiring resistance: 1,500 Ohms. Maximum IDC Voltage: 11 Volts. Maximum IDC Current: 240 µA EOL resistance: 47K Ohms. Temperature range: 32° to 120°F (0° to 49°C). Humidity range: 10% to 93% (non-condensing). Dimensions: 4.5" (11.43 cm) high x 4" (10.16 cm) wide x 1.25" (3.175 cm) deep. Mounts to a 4" (10.16 cm) square x 2.125" (5.398 cm) deep box. MDF-300(A) AUTOMATIC ADDRESSING The MDF-300(A) automatically assigns itself to two address- able points, starting with the original address. For example, if the MDF-300(A) is set to address “26”, then it will automati- cally assign itself to addresses “26” and “27”. NOTE: “Ones” addresses on the MDF-300(A) are 0, 2, 4, 6, or 8 only. Terminals 6 and 7 use the first address, and terminals 8 and 9 use the second address. Installation MMF-300(A), MMF-302(A), and MDF-300(A) modules mount directly to a standard 4" (10.16 cm) square, 2.125" (5.398 cm) deep, electrical box. They may also be mounted to the SMB500 surface-mount box. Mounting hardware and installa- tion instructions are provided with each module. All wiring must conform to applicable local codes, ordinances, and regu- lations. These modules are intended for power-limited wiring only. The MMF-301(A) module is intended to be wired and mounted without rigid connections inside a standard electrical box. All wiring must conform to applicable local codes, ordinances, and regulations. Agency Listings and Approvals In some cases, certain modules may not be listed by certain approval agencies, or listing may be in process. Consult fac- tory for latest listing status. •UL: S2424. •ULC: S2424. •FM Approved. •CSFM: 7300-0075:0185. •MEA: 72-01-E. Product Line Information NOTE: “A” suffix indicates ULC-listed model. MMF-300(A): Monitor module. MMF-301(A): Monitor module, miniature. MMF-302(A): Monitor module, two-wire detectors. MDF-300(A): Monitor module, dual, two independent Class B circuits. SMB500: Optional surface-mount backbox. NOTE: See installation instructions and refer to the SLC Wiring Manual, PN 51309. Architects’/Engineers’ Specifications Specifications of these devices and all FireLite products are available from FireLite. CAUTION: Avoid duplicating addresses on the system. Page 4 of 4 — DF-52121:E • 07/30/2015 This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice. For more information, contact Fire•Lite Alarms. Phone: (800) 627-3473, FAX: (877) 699-4105. www.firelite.com Fire·Lite® is a registered trademark and LiteSpeed™ and FireWatch™ are trademarks of Honeywell International Inc. ©2015 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited. Agency Listings AVDS115-02 • 12/3/2019 • Page 1 MEA452-05-E3023572 7300-1653:187 (outdoor strobes) 7125-1653:188 (horn strobes, chime strobes) 7135-1653:189 (horns, chimes) S4011 (chimes, horn strobes, horns) S3593 (outdoor and alert strobes) Features • Weatherproof per NEMA 4X, IP56 • Listed to UL 1638 (strobe) and UL 464 (horn) • Compatible with System Sensor synchronization protocol and legacy SpectrAlert products • Field-selectable candela settings: 15, 15/75, 30, 75, 95, 110, 115, 135, 150, 177, and 185 • Automatic selection of 12- or 24-volt operation at 15 and 15/75 candela • Rotary switch for horn tone and three volume selections • Horn rated at 88+ dBA at 16 volts • Rated from –40°F to 151°F • Universal mounting plate with an onboard shorting spring that tests wiring continuity before devices are installed • Plug-in design with minimal intrusion into the back box • Tamper-resistant construction • Listed for ceiling or wall mounting SpectrAlert Advance offers the broadest line of outdoor horns, strobes, and horn strobes in the industry. With white or red plastic housings, wall or ceiling mounting options, and plain or FIRE-printed devices, SpectrAlert Advance can meet virtually any application requirement, including indoor, outdoor, wet, and dry applications in temperatures from −40°F to 151°F. Like the entire SpectrAlert Advance line, outdoor horns, strobes, and horn strobes for wall applications include a variety of features that increase application flexibility and simplify installation. First, field-selectable settings, including candela, automatic selection of 12- or 24-volt operation, horn tones, and three volume options enable installers to easily adapt devices to meet requirements. Next, SpectrAlert Advance devices use a universal mounting plate for both wall and ceiling applications. This mounting plate includes an onboard shorting spring that ensures wiring continuity before devices are installed, so installers can verify proper wiring without mounting the devices and exposing them to potential construction damage. Once the plates are mounted, all SpectrAlert Advance devices utilize a plug-in design with a single captured screw to speed installation and virtually eliminate costly ground faults. Outdoor devices ship with weatherproof plastic back boxes (metal back boxes are available separately) that accommodate in-and- out wiring for daisy chaining devices. Plastic back boxes feature removable side flanges and improved resistance to saltwater corrosion. Knock-outs located on the back eliminate the need to drill holes for screw-in mounting. Plastic and metal weatherproof back boxes come with ¾-inch top and bottom conduit entries and ¾-inch knock-outs at the back. A screw-in NPT plug with an O-ring gasket for a watertight seal is included with each back box. Outdoor Selectable- Output Horns, Strobes, and Horn Strobes for Wall Applications SpectrAlert® Advance outdoor audible visible products are rich with features that cut installation times and maximize profits. AVDS115-02 • 12/3/2019 • Page 2 SpectrAlert Advance Outdoor Horn, Strobe, and Horn StrobeSpecifications Architect/Engineer Specifications General SpectrAlert Advance outdoor horns, strobes, and horn strobes shall mount to a weatherproof back box. A universal mounting plate shall be used for mounting ceiling and wall products. The notification appliance circuit wiring shall terminate at the universal mounting plate. Also, SpectrAlert Advance products, when used with the Sync•Circuit™ Module accessory, shall be powered from a non-coded notification appliance circuit output and shall operate on a nominal 12 or 24 volts. When used with the Sync•Circuit Module, 12-volt-rated notification appliance circuit outputs shall operate between 8.5 and 17.5 volts; 24-volt-rated notification appliance circuit outputs shall operate between 16.5 and 33 volts. Outdoor SpectrAlert Advance products shall operate between −40 and 151 degrees Fahrenheit from a regulated DC or full- wave rectified unfiltered power supply. Strobes and horn strobes shall have field-selectable candela settings including 15, 15/75, 30, 75, 95, 110, 115, 135, 150, 177, and 185. Strobe The strobe shall be a System Sensor SpectrAlert Advance Model _______ listed to UL 1971 and shall be approved for fire protective service. The strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances, flashing at 1 Hz over the strobe’s entire operating voltage range. The strobe light shall consist of a xenon flash tube and associated lens/reflector system. The strobe must be installed with its weatherproof back box in order to remain outdoor approved per UL. The strobe shall be suitable for use in wet environments. Horn Strobe Combination The horn strobe shall be a System Sensor SpectrAlert Advance Model _______ listed to UL 1971 and UL 464 and shall be approved for fire protective service. The horn strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances, flashing at 1 Hz over the strobe’s entire operating voltage range. The strobe light shall consist of a xenon flash tube and associated lens/reflector system. The horn shall have three audibility options and an option to switch between a temporal three pattern and a non-temporal (continuous) pattern. These options shall be set by a multiple position switch. On four-wire products, the strobe shall be powered independently of the sounder. The horn or horn strobe models shall operate on a coded or non-coded power supply. The horn strobe must be installed with its weatherproof back box in order to remain outdoor approved per UL. The horn strobe shall be suitable for use in wet environments. Physical/Electrical Specifications Operating Temperature –40°F to 151°F (–40°C to 66°C) Strobe Flash Rate 1 flash per second Nominal Voltage Regulated 12 DC/FWR or regulated 24 DC/FWR1 Operating Voltage Range2 8 to 17.5 V (12 V nominal) or 16 to 33 V (24 V nominal) Operating Voltage with MLD3 Sync Module 8.5 to 17.5 V (12 V nominal) or 16.5 to 33 V (24 V nominal) Input Terminal Wire Gauge 12 to 18 AWG Wall-Mount Dimensions (including lens)5.6˝ L × 4.7˝ W × 2.5˝ D (142 mm L × 119 mm W × 64 mm D) Horn Dimensions 5.6˝ L × 4.7˝ W × 1.3˝ D (142 mm L × 119 mm W × 33 mm D) Wall-Mount Weatherproof Back Box Dimensions (SA-WBB)5.7˝ L × 5.1˝ W × 2.0˝ D (145 mm L × 130 mm W × 51 mm D) Notes: 1. Full Wave Rectified (FWR) voltage is a non-regulated, time-varying power source that is used on some power supply and panel outputs. 2. 2. P, S, PC, and SC products will operate at 12 V nominal only for 15 and 15/75 cd. UL Max. Strobe Current Draw (mA RMS) Candela 8–17.5 Volts 16–33 Volts DC FWR DC FWR Standard Candela Range 15 123 128 66 71 15/75 142 148 77 81 30 NA NA 94 96 75 NA NA 158 153 95 NA NA 181 176 110 NA NA 202 195 115 NA NA 210 205 High Candela Range 135 NA NA 228 207 150 NA NA 246 220 177 NA NA 281 251 185 NA NA 286 258 UL Max. Current Draw (mA RMS), 2-Wire Horn Strobe, Standard Candela Range (15–115 cd) DC Input 8–17.5 Volts 16–33 Volts 15 15/75 15 15/75 30 75 95 110 115 Temporal High 137 147 79 90 107 176 194 212 218 Temporal Medium 132 144 69 80 97 157 182 201 210 Temporal Low 132 143 66 77 93 154 179 198 207 Non-Temporal High 141 152 91 100 116 176 201 221 229 Non-Temporal Medium 133 145 75 85 102 163 187 207 216 Non-Temporal Low 131 144 68 79 96 156 182 201 210 FWR Input Temporal High 136 155 88 97 112 168 190 210 218 Temporal Medium 129 152 78 88 103 160 184 202 206 Temporal Low 129 151 76 86 101 160 184 194 201 Non-Temporal High 142 161 103 112 126 181 203 221 229 Non-Temporal Medium 134 155 85 95 110 166 189 208 216 Non-Temporal Low 132 154 80 90 105 161 184 202 211 UL Max. Current Draw (mA RMS), 2-Wire Horn Strobe, High Candela Range (135–185 cd) DC Input 16–33 Volts FWR Input 16–33 Volts 135 150 177 185 135 150 177 185 Temporal High 245 259 290 297 Temporal High 215 231 258 265 Temporal Medium 235 253 288 297 Temporal Medium 209 224 250 258 Temporal Low 232 251 282 292 Temporal Low 207 221 248 256 Non-Temporal High 255 270 303 309 Non-Temporal High 233 248 275 281 Non-Temporal Medium 242 259 293 299 Non-Temporal Medium 219 232 262 267 Non-Temporal Low 238 254 291 295 Non-Temporal Low 214 229 256 262 UL Max. Horn Current Draw (mA RMS) Sound Pattern dB 8–17.5 Volts 16–33 Volts DC FWR DC FWR Temporal High 57 55 69 75 Temporal Medium 44 49 58 69 Temporal Low 38 44 44 48 Non-Temporal High 57 56 69 75 Non-Temporal Medium 42 50 60 69 Non-Temporal Low 41 44 50 50 Coded High 57 55 69 75 Coded Medium 44 51 56 69 Coded Low 40 46 52 50 UL Current Draw Data Horn Tones and Sound Output DataCandela Derating For K series products used at low temperatures, listed candela ratings must be reduced in accordance with this table. Strobe Output (cd) Listed Candela Candela rating at –40°F 15 Do not use below 32°F15/75 30 75 44 95 70 110 110 115 115 135 135 150 150 177 177 185 185 Horn and Horn Strobe Output (dBA) Switch Position Sound Pattern dB 8–17.5 Volts 16–33 Volts 24-Volt Nominal Reverberant Anechoic DC FWR DC FWR DC FWR DC FWR 1 Temporal High 78 78 84 84 88 88 99 98 2 Temporal Medium 74 74 80 80 86 86 96 96 3 Temporal Low 71 73 76 76 83 80 94 89 4 Non- Temporal High 82 82 88 88 93 92 100 100 5 Non- Temporal Medium 78 78 85 85 90 90 98 98 6 Non- Temporal Low 75 75 81 81 88 84 96 92 7†Coded High 82 82 88 88 93 92 101 101 8†Coded Medium 78 78 85 85 90 90 97 98 9†Coded Low 75 75 81 81 88 85 96 92 †Settings 7, 8, and 9 are not available on 2-wire horn strobe. 3825 Ohio Avenue • St. Charles, IL 60174 Phone: 800-SENSOR2 • Fax: 630-377-6495 www.systemsensor.com ©2019 System Sensor. Product specifications subject to change without notice. Visit systemsensor.com for current product information, including the latest version of this data sheet. AVDS115-02 • 12/3/2019 SpectrAlert Advance Diagrams Model Description Red White Wall Horn Strobes P2RK P2WK 2-Wire Horn Strobe, Standard cd, Outdoor (includes plastic weatherproof back box) P2RK-P P2WK-P 2-Wire Horn Strobe, Standard cd, Outdoor, Plain (includes plastic weatherproof back box) P2RK-R P2WK-R 2-Wire Horn Strobe, Standard cd, Outdoor (does not include plastic weatherproof back box) P2RHK P2WHK 2-Wire Horn Strobe, High cd, Outdoor (includes plastic weatherproof back box) P2RHK-P P2WHK-P 2-Wire Horn Strobe, High cd, Outdoor, Plain (includes plastic weatherproof back box) P2RHK-R P2WHK-R 2-Wire Horn Strobe, High cd, Outdoor (does not include plastic weatherproof back box) P4RK P4WK 4-Wire Horn Strobe, Standard cd, Outdoor (includes plastic weatherproof back box) P4RK-R —4-Wire Horn Strobe, Standard cd, Outdoor (does not include plastic weatherproof back box) P2RHK-120 —2-Wire Horn Strobe, High cd, Outdoor, 120 V (includes plastic weatherproof back box) Wall Strobes SRK SWK Strobe, Standard cd, Outdoor (includes plastic weatherproof back box) SRK-P SWK-P Strobe, Standard cd, Outdoor, Plain (includes plastic weatherproof back box) SRK-R SWK-R Strobe, Standard cd, Outdoor (does not include plastic weatherproof back box) SRHK SWHK Strobe, High cd, Outdoor (includes plastic weatherproof back box) SRHK-P SWHK-P Strobe, High cd, Outdoor, Plain (includes plastic weatherproof back box) SRHK-R SWHK-R Strobe, High cd, Outdoor (does not include plastic weatherproof back box) Horns HRK —Horn, Red, Outdoor (includes plastic weatherproof back box) HRK-R —Horn, Red, Outdoor (does not include plastic weatherproof back box) Accessories SA-WBB SA-WBBW Metal Weatherproof Back Box WTP WTPW Metal Weatherproof Outdoor Flush-mounting Plate SpectrAlert Advance Ordering Information Notes: All -P models have a plain housing (no “FIRE” marking on cover). All -R models require metal weatherproof outdoor flush mounting plate or a metal weatherproof outdoor back box (order separately). “Standard cd” refers to strobes that include 15, 15/75, 30, 75, 95, 110, and 115 candela settings. “High cd” refers to strobes that include 135, 150, 177, and 185 candela settings. When replacing standard outdoor units both the device and back box must be replaced. 4.7˝ 5.6˝ 6.8˝Dia. 2.5˝ 2.5˝ 64mm119mm 142mm Wall-Mount Horn Strobes Wall Plastic Weatherproof Back Box Wall-Mount Horn Strobe with Plastic Weatherproof Back Box PS SERIES 6 Amp and 10 Amp, 24 Volt Power Supplies product caption HPF-PS6/10 HPF-PS6/10B The PS Series is a remote power supply line from Gamewell-FCI. The HPF-PS6 is a 6 amp and the HPF-PS10 is a 10 amp, remote power supply with battery charger that may be connected to any 12 or 24 volt fire alarm control panel (FACP) or used as a standalone power supply. The PS Series provides 24 VDC power for NACs (notification appliance circuits) configured as either Class B or Class A (requires the ZNAC-PS option card) with multiple sync protocol options. The PS Series also provides auxiliary power, constant or resettable, suited for detectors, annunciators, door holders, and other fire alarm system peripherals. The PS Series cabinet can hold two 7 AH or 18 AH batteries and can charge up to 33 AH batteries in a separate cabinet. FEATURES AND BENEFITS • Up to five (6 amp model) or seven (10 amp model) independently-configurable, power- limited output circuits for: –Class B and/or Class A NACs –Class B and/or Class A resettable or non- resettable 24V auxiliary power –door holder power • Converts from Class B to Class A wiring without losing any outputs using the ZNAC- PS converter card (sold separately) • Optimal for powering four-wire smoke detectors, annunciators, and other system peripherals requiring regulated power • Optional addressable control, monitor, and relay modules and power-supervision relay (EOLR-1) • Configurable for ANSI® Temporal 3 or Temporal 4 coded output • UL-Listed NAC synchronization using System Sensor®, Wheelock®, Gentex®, or AMSECO® appliances • Synchronization can be triggered from FACP NAC/remote sync outputs, cascaded power supply, or a control module, single or multi, which may be housed within the power supply cabinet • Ability to cascade up to four power supplies • Two (6 amp model) or three (10 amp model) fully-isolated input/control circuits which can be programmed to any output • Two Form C normally-closed trouble relays for AC Trouble and General Trouble • 6 or 10 amp full load output, respectively, with 3 A maximum/circuit • Individual NAC power and trouble LEDs for diagnostic efficiency • Trouble history mode for diagnostic support • Wide range end-of-line supervision value (normal: 2-27K ohms) • Selectable earth fault detection (enable or disable) • AC trouble report delay timer • Completely configurable via onboard DIP switches, no extra software required • Self-contained in compact, locking cabinet constructed of heavy gauge steel with a corrosion-resistant powder coat chip and scratch-resistant finish • Cabinet designed with ten double knockouts and a removable door for ease of installation and wiring • Includes integral battery charger capable of charging up to 33 AH batteries • Cabinet can house two 7 AH or 18 AH batteries • Battery charger may be disabled via DIP switch for applications requiring larger batteries and external battery charger • Removable terminal blocks accommodate up to 12 AWG (3.1mm2) wire • Works with any UL 864 FACP which utilizes an industry-standard reverse-polarity notification circuit • HPF-PS6/10 include the - Honeywell Power Products lock set (PN: 17059) and key (PN: 17051) The PS Series are independently configurable power supplies, allowing you to pair any input with any output, and feature LED diagnostics for troubleshooting. ORDERING INFORMATION HPF-PS6: 6.0 A, 120 VAC remote charger power supply in a lockable, metal enclosure, red HPF-PS6B: 6.0 A, 120 VAC remote charger power supply in a lockable, metal enclosure, black HPF-PS10: 10.0 A, 120 VAC remote charger power supply in a lockable, metal enclosure, red HPF-PS10B: 10.0 A, 120 VAC remote charger power supply in a lockable, metal enclosure, black ZNAC-PS: Optional Class A converter card, sold separately AOM-2SF: Addressable Control Module for one Class B or Class A zone of supervised, polarized Notification Appliances. Notification Appliance Circuit option requires external 24 VDC to power notification appliances. AOM-2RF: Addressable relay module containing two isolated sets of Form-C contacts, which operate as a DPDT switch AMM-4F: Addressable Monitor Module for one zone of normally open dry-contact initiating devices. Includes plastic cover plate and end-of-line resistor. Module may be configured for either a Class B or Class A AMM-2IF: Dual Monitor Module. Same as AMM-4F except it provides two inputs for Class B wiring only AMM-2RIF: Provides two monitored inputs and two Form-C relays. Functions in Class B wiring only MMO-6SF: Six-circuit supervised control module MMO-6RF: Six Form-C relay control module EOLR-1: 12/24 VDC end-of-line relay for monitoring four-wire smoke detector power BAT-1270-BP: Battery, 12 volt, 7.0 AH, 5-pack (two required) BAT-12180-BP: Battery, 12 volt, 18AH, 2-pack BAT-12330: Battery, 12 volt, 33AH SEISKIT-MULTI-1: Seismic kit for the PS Series. Includes bracket and hardware for two 7AH or two 18AH batteries. 17070: Alternate Honeywell Gamewell-FCI lock set, PK-625, 3/8" cam Page 2 of 3 — 9021-61096:B • 1/25/2021 HPS SERIES TECHNICAL SPECIFICATIONS 9021-61096 | B | 01/21 ©2021 Honeywell International Inc. Honeywell Gamewell-FCI 12 Clintonville Road Northford, CT 06472-1610 203.484.7161 www.gamewell-fci.com Gamewell-FCI® and System Sensor® are trademark of Honeywell International, Inc. Wheelock® is a registered trademark of Cooper Technologies Company. Gentex® is a registered trademark of Gentex Corporation. AMSECO® is a registered trademark of Potter Electric Signal Company, LLC. ANSI® is a registered trademark of the American National Standards Institute, Inc. ©2021 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited. This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice. Country of origin: USA PRIMARY (AC) POWER HPF-PS6(B): 120 VAC, 50/60 Hz, 5.0A maximum HPF-PS10(B): 120VAC, 50/60 Hz, 6.2 A maximum Wire Size: #12-14 AWG with 600 V insulation COMMAND INPUT CIRCUIT Trigger Input Voltage: 9 to 32 VDC Trigger Current: 2.0 mA (16 - 32 V); Per Input: 1.0 mA (9 - 16 V) RELAY CIRCUITS Trouble Contact Rating: 4 A at 24 VDC OUTPUT CIRCUITS • 24 VDC filtered • HPF-PS6B: TB8-TB9 – 1A Regulated, 3A special applications; TB10-TB12 – 0.3A Regulated, 3A special applications • HPF-PS10B: TB8-TB11 – 1.5A Regulated, 3A special applications; TB12-TB14 – 0.3A Regulated, 3A special applications • 6.0 A (HPF-PS6B) or 10.0 (HPF-PS10B) maximum total continuous current for all outputs SECONDARY POWER (BATTERY) CHARGING CIRCUIT • Supports lead-acid batteries only • Float-charge voltage: 27.6 VDC • Maximum current charge: 1.5 A • Maximum battery capacity: 18 AH (inside cabinet) • Maximum battery charging capacity: 33 AH (external cabinet) PHYSICAL Dimensions: 20.0”H x 14.5”W x 3.5”D (cm: 50.8H x 36.83W x 8.9D) Weight: with two 7Ah batteries is 24 pounds (10.9 kg), with two 18 AH batteries is 39 pounds (17.7 kg) STANDARDS AND CODES The HPF-PS complies with the following standards: NFPA 72: National Fire Alarm Code UL 864: Standard for Control Units for Fire Alarm Systems (NAC expander mode) UL 1481: Power Supplies for Fire Alarm Systems AGENCY LISTINGS AND APPROVALS These listings and approvals apply to the modules specified in this document. In some cases, certain modules or applications may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status. UL Listed: S24562 CSFM: 7315-1637:0505 FDNY Approved FM Approved DF-61010:C • 5/28/2020 — Page 1 of 3 SD365 Series Addressable Photoelectric Smoke Detectors Addressable Devices DF-61010:C The Fire•Lite® Alarms SD365(A), SD365R(A), and SD365HT(A) intelligent plug-in smoke detectors are designed for both perfor- mance and aesthetics, and are direct replacements for the SD355 Series. A new modern, sleek, contemporary design and enhanced optical sensing chamber is engineered to sense smoke produced by a wide range of combustion sources in accordance with more strin- gent code standards. Exclusively for use with Fire•Lite’s addressable fire alarm control panels, the SD365(A) Series point ID capability allows each detec- tor’s address to be set with rotary, decimal address switches, provid- ing exact detector location for emergency personnel to quickly locate a fire during its early stages, potentially saving precious rescue time while also reducing property damage. Two LEDs on each sensor light to provide a local, visible sensor indication. The SD365(A) Series also offers 135°F (57°C) fixed temperature thermal sensing on the SD365T(A) and a remote test capable detec- tor on the SD365R(A) for use with DNR(A)/DNRW duct smoke detector housings. Features SLC LOOP: • Two-wire SLC loop connection • Unit uses base for wiring • Compatible with LiteSpeed™ and CLIP protocol systems • Stable communication technique with noise immunity ADDRESSING: • Addressable by device • Rotary, decimal addressing (Refer to the Fire•Lite panel manuals for device capacity.) ARCHITECTURE: • Sleek, low-profile, stylish design • Unique single-source design to respond quickly and dependably to a broad range of fires • Integral communications and built-in device-type identification • Built-in tamper resistant feature • Remote test feature from the panel • Walk test with address display (an address on 121 will blink the detector LED: 12-[pause]-1(LiteSpeed systems only) • Built-in functional test switch activated by external magnet • Removable cover and insect-resistant screen for simple field cleaning • Expanded color options OPERATION: • Designed to meet UL 268 7th Edition • Factory preset at 1.5% nominal sensitivity for panel alarm thresh- old level • LED “blinks” when the unit is polled (communicating with the fire panel) and latches in alarm. • Low standby current MECHANICALS: • Sealed against back pressure • SEMS screws for wiring of the separate base • Designed for direct-surface or electrical-box mounting • Plugs into separate base for ease of installation and maintenance • Separate base allows interchange of photoelectric, ionization and thermal sensors OPTIONS: • Optional relay, isolator, and sounder bases Installation SD365 Series plug-in intelligent smoke detectors use a detachable base to simplify installation, service and maintenance. Installation instructions are shipped with each detector. Mount detector base (all base types) on an electrical backbox which is at least 1.5" (3.81 cm) deep. For a chart of compatible junction boxes, see DF-60059. NOTE: Because of the inherent supervision provided by the SLC loop, end-of-line resistors are not required. Wiring “T-taps” or branches are permitted for Class “B” wiring only. When using relay or sounder bases, consult the I300(A) installation sheet I56-3626 for device limitations between isolator modules and isola- tor bases. Construction These detectors are constructed of fire-resistant plastic. The SD365 Series plug-in intelligent smoke detectors are designed to commer- cial standards and offer an attractive appearance. Operation Each SD365 Series detector uses one of the panel’s addresses (total limit is panel dependent) on the Fire•Lite Signaling Line Circuit (SLC). It responds to regular polls from the control panel and reports its type and the status. If it receives a test command from the panel (or a local magnet test), it stimulates its electronics and reports an alarm. It blinks its LEDs when polled and turns the LEDs on when commanded by the panel. The SD365 Series offers features and performance that represent the latest in smoke detector technology. Detector Sensitivity Test Each detector can have its sensitivity tested (required per NFPA 72, Chapter 14 on Inspection, Testing and Maintenance) when installed/ connected to an Fire•Lite addressable fire alarm control panel. The results of the sensitivity test can be printed for record keeping. Page 2 of 3 — DF-61010:C • 5/28/2020 Product Line Information NOTE: “-IV” suffix indicates CLIP and LiteSpeed device. NOTE: “A” suffix indicates Canadian version. SD365: White, low-profile intelligent photoelectric sensor, LiteSpeed only SD365A: Same as SD365 but with ULC listing SD365-IV: Ivory, low-profile intelligent photoelectric sensor SD365A-IV: Same as SD365-IV but with ULC listing SD365T: White, same as SD365 but includes a built-in 135°F (57°C) fixed-temperature thermal device, LiteSpeed only SD365TA: Same as SD365T but with ULC listing SD365T-IV: Ivory, same as SD365T but includes a built-in 135°F (57°C) fixed-temperature thermal device SD365TA-IV: Same as SD365T-IV but with ULC listing SD365R: White, low-profile intelligent photoelectric sensor, remote test capable, for use with DNR/DNRW, LiteSpeed only SD365RA: Same as SD365R but with ULC listing, for use with DNRA SD365R-IV: Ivory, low-profile intelligent photoelectric sensor, remote test capable, for use with DNR/DNRW SD365RA-IV: Same as SD365R-IV but with ULC listing, for use with DNRA INTELLIGENT BASES NOTE: For details on intelligent bases, see DF-60059. B300-6: White, 6” base, standard flanged low-profile mounting base (CSFM: 7300-1653:0109) B300-6-IV: Ivory,6” base, standard flanged low-profile mounting base (CSFM: 7300-1653:0109) B300A-6: Same as B300-6, ULC listed B300A-6-IV: Ivory, 6” standard flanged low-profile mounting base, ULC listed B300-6-BP: Bulk pack of B300-6, package contains 10 B501-WHITE: White, 4” standard European flangeless mounting base. UL/ULC listed (CSFM: 7300-1653:0109) B501-BL: Black, 4” standard European flangeless mounting base. UL/ULC listed (CSFM: 7300-1653:0109) B501-IV: Ivory color, 4” standard European flangeless mounting base. UL/ULC listed (CSFM: 7300-1653:0109) B501-WHITE-BP: Bulk pack of B501-WHITE contains 10 B224RB-WH: White, relay base (CSFM: 7300-1653:0216) B224RB-IV: Ivory, relay base (CSFM: 7300-1653:0216) B224RBA-WH: White, relay base, ULC listing B224RBA-IV: Ivory, relay base, ULC listing B224BI-WH: White, isolator detector base (CSFM: 7300-1653:0216) B224BI-IV: Ivory isolator detector base (CSFM: 7300-1653:0216) B224BIA-WH: White, isolator detector base, ULC listing B224BIA-IV: Ivory isolator detector base, ULC listing B200S-WH: White, Intelligent addressable sounder base capable of producing sound output in high or low volume with ANSI Temporal 3, ANSI Temporal 4, continuous tone, marching tone, and custom tone. Uses LiteSpeed protocol. (CSFM: 7300-1653:0213) B200S-IV: Ivory, Intelligent addressable sounder base capable of producing sound output in high or low volume with ANSI Temporal 3, ANSI Temporal 4, continuous tone, marching tone, and custom tone. Uses LiteSpeed protocol. (CSFM: 7300-1653:0213) B200SA-WH: Same as B200S-WH, ULC listing B200SA-IV: Same as B200S-IV, ULC listing B200SCOA-WH: White, Intelligent, programmable sounder base in English/French (required in Canada for ULC applications with CO Series detector applications B200SCOA-IV: Ivory Intelligent, programmable sounder base in English/French (required in Canada for ULC applications with CO Series detector applications, ULC listing B200S-LF-WH: White, Low Frequency Intelligent, programmable sounder base. Produces a fundamental frequency of 520 Hz +/- 10% with a square wave or its equivalent; designed to meet the NFPA 72 sleeping space requirement. (CSFM: 7300-1653:0238) B200S-LF-IV: Ivory, Low Frequency Intelligent, programmable sounder base. Produces a fundamental frequency of 520 Hz +/- 10% with a square wave or its equivalent; designed to meet the NFPA 72 sleeping space requirement. (CSFM: 7300-1653:0238) B200SR-WH: White, Intelligent sounder base capable of producing sound output with ANSI Temporal 3 or continuous tone. Intended for retrofit applications. (CSFM: 7300-1653:0213) B200SR-IV: Ivory, Intelligent sounder base capable of producing sound output with ANSI Temporal 3 or continuous tone. Intended for retrofit applications. (CSFM: 7300-1653:0213) B200SRA-WH: Same as B200SR-WH with, ULC listing B200SRA-IV: Same as B200SR-IV in Ivory color, ULC listing B200SR-LF-WH: White, Low Frequency Intelligent, programmable sounder base. Produces a fundamental frequency of 520 Hz +/- 10% with a square wave or its equivalent; designed to meet the NFPA 72 sleeping space requirement. Intended for retrofit applica- tions. (CSFM: 7300-1653:0238) B200SR-LF-IV: Ivory, Low Frequency Intelligent, programmable sounder base. Produces a fundamental frequency of 520 Hz +/- 10% with a square wave or its equivalent; designed to meet the NFPA 72 sleeping space requirement. Intended for retrofit applica- tions. (CSFM: 7300-1653:0238) MOUNTING KITS AND ACCESSORIES TR300: White, replacement flange for B210LP(A) base TR300-IV: Ivory, replacement flange for B210LP(A) base RA100Z(A): Remote LED annunciator. 3-32 VDC. Mounts to a U.S. single-gang electrical box. For use with B501(A) and B300-6(A). M02-04-00: Test magnet M02-09-00: Test magnet with telescoping handle CK300: Color Kit (includes cover and trim ring), white, 10-pack CK300-IV: Color Kit (includes cover and trim ring), ivory, 10-pack CK300-BL: Color Kit (includes cover and trim ring), black, 10-pack LiteSpeed™ is a trademark, and Fire•Lite® Alarms and System Sensor® are registered trademarks of Honeywell International Inc. ©2020 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited. Page 3 of 3 — DF-61010:C • 5/28/2020 This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice. For more information, contact Fire•Lite Alarms. Phone: (800) 627-3473, FAX:(877) 699-4105. www.firelite.com Country of Origin: Mexico SYSTEM SPECIFICATIONS Sensitivity: • UL Applications: 0.5% to 4.0% per foot obscuration. • ULC Applications: 0.5% to 3.5% per foot obscuration Size: 2.0" (51mm) high; base determines diameter – B300-6: 6.1" (15.6 cm) diameter – B501: 4" (10.2 cm) diameter For a complete list of detector bases see DF-60983 Shipping weight: 3.4 oz. (95 g) Operating temperature range: • SD365: 32°F to 122°F (0°C to 50°C) • SD365T Series: 32°F to 100°F(0°C to 38°C) • SD365R Series installed in a DNR/DNRW, -4°F to 158°F (-20°C to 70°C) UL/ULC Listed Velocity Range: 0-4000 ft/min. (1219.2 m/min.), suitable for installation in ducts Relative humidity: 10% – 93% non-condensing Thermal ratings: fixed-temperature set point 135°F (57°C), rate-of- rise detection 15°F (8.3°C) per minute, high temperature heat 190°F (88°C) ELECTRICAL SPECIFICATIONS Voltage range: 15 - 32 volts DC peak Standby current (max. avg.): 200µA @ 24 VDC (o ne communica- tion every 5 seconds with LED enabled) Max current: 4.5 mA @ 24 VDC (“ON”) DETECTOR SPACING AND APPLICATIONS Fire•Lite recommends spacing detectors in compliance with NFPA 72. In low airflow applications with smooth ceiling, space detectors 30 feet (9.1m). For specific information regarding detector spacing, placement, and special applications refer to NFPA 72. A System Smoke Detector Application Guide, document SPAG91, is available at www.systemsensor.com. Listings and Approvals Listings and approvals below apply to the SD365 Series detectors. In some cases, certain modules may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status. • UL/ULC Listing: S1059 • FM Approved • CSFM: 7272-0075:0502 Ceiling Speaker Strobes L Series, Indoor Ceiling Strobes and Dual Speakers Indoor Output Speaker Strobes and Dual Speakers for Ceiling Applications Notification Appliances General The L-Series indoor selectable-output speaker strobes and dual-voltage evacuation speakers offer a modern, aesthetic plug-in design that reduce costly ground faults. The universal mounting plate can be used in ceiling applications and its flexible design enables the Installer to easily perform the following: • Pre-wire mounting plates •Dress the wires Confirm wiring continuity before the Installer plugs-in the speakers. In addition, this product includes a protective plastic cover which shields exposed speaker components and prevents nicked wires. These devices enable faster installations by providing instant feedback to the Installer to ensure the following: • The wiring is properly connected. • The rotary switches are set to the selected voltage and power settings. • The 7 field-selectable candela settings are configured for wall speaker strobes. • The low total harmonic distortion of the SP speaker offers both high-fidelity and high-volume sound output so that it can be used in high ambient noise applications. L-Series makes installation easy to install the L-Series speakers or speaker strobe, do the following: 1. Attach a universal mounting plate to a 4 x 4 x 2 1/8 inch backbox. Flush- mount applications do not require an extension ring. 2. Connect the notification appliance circuit or speaker wiring to the terminals on the mounting plate. 3. To attach the speaker or speaker strobe to the mounting plate, insert the product tabs into the mounting plate grooves. 4. Hinge the device into position to lock the product pins into the mounting plate terminals. 5. A catch temporarily holds the device in place until you secure the device with a captured mounting screw. FEATURES & BENEFITS • Includes a plug-in feature and protective cover to reduce ground faults • Contains a universal mounting plate with an on-board shorting spring that is used to test the wiring continuity before an installation • No extension ring required • Field-selectable candela settings on ceiling units: - 15 - 30 - 75 - 95 - 115 - 150 - 177 • Uses an automatic selection of 12- or 24- volt operation at 15 and 30 candela • Provides a rotary switch that simplifies the field selection of speaker voltage (25) and 70.7 VRMS) and the following power settings: - 1/4 watt - 1/2 watt - 1 watt - 2 watts • Offers speakers with both high-fidelity and high-volume sound output • Compatible with the System Sensor synchronization protocol • Supports electrical compatibility with the existing SpectrAlert and the SpectrAlert Advance products •Designed with a tamper-resistant construction • Built with an updated modern design 2 L-Series Speaker and Speaker Strobe Specifications Architectural/Engineering Specifications General The L-Series speaker and speaker strobes shall mount to a 4 x 4 x 2 1/8-inch backbox. A universal mounting plate shall be used for the mounting ceiling and wall products. The notification appliance circuit and amplifier wiring shall terminate at the universal mounting plate. Also, the L-Series speaker strobes, when used with the Sync•Circuit. Module accessory, shall be powered from a non-coded notification appliance circuit output and shall operate on a nominal 12 or 24 volts. When these devices are used with the Sync•Circuit Module, either of the following may occur. • 12-volt rated notification appliance circuit outputs shall operate between 8.5 and 17.5 volts. • 24-volt rated notification appliance circuit outputs shall operate between 16.5 and 33 volts. The Indoor L-Series products shall operate between 32° F and 120°F from a regulated DC, or full-wave rectified, unfiltered power supply. Speaker strobes shall have the following field-selectable candela settings: Speaker The speaker shall be an L-Series model _______ dual- voltage transformer speaker capable of operating at 25.0 or 70.7 nominal VRMS. It should be listed to UL Standard 1480 and shall be approved for fire protective service. The speaker shall have a frequency range of 400 to 4,000 Hz and shall have an operating temperature between 32°F and 120°F. The speaker shall have power taps and voltage that are selected by rotary switches. Speaker Strobe Combination The speaker strobe shall be an L-Series model __________ listed to UL Standard 1480 and UL Standard 1971 and be approved for fire protective signaling systems. The speaker shall be capable of operating at 25.0 or 70.7 nominal VRMS selected via rotary switch, and shall have a frequency range of 400 to 4,000 Hz. The speaker shall have power taps that are selected by rotary switch. The strobe shall comply with the NFPA 72 requirements for visible signaling appliances, flashing at 1 Hz over the strobe’s entire operating voltage range. The strobe light shall consist of a xenon flash tube and associated lens/reflector system. Synchronization Module The module shall be a Sync•Circuit model MDL3 listed to UL Standard 464 and shall be approved for fire protective service. The module shall synchronize SpectrAlert strobes at 1 Hz. The module shall mount to a 4 11/16 x 4 11/16 x 2 1/8-inch back box. The module shall also control two Style Y (Class B) circuits or one Style Z (Class A) circuit. The module shall synchronize multiple zones. Daisy chaining two or more synchronization modules together will synchronize all the zones they control. The module shall not operate on a coded power supply. UL Current Draw Data Table 1 lists the UL maximum strobe current draw. Table 2 lists the ceiling mount speaker sound outputs. Table 3 lists the ceiling-mount speaker strobe sound outputs. •15 •30 •75 •95 •115 •150 •177 8-17.5 Volts 16-33 Volts Candela DC DC FWR 15 87 41 60 30 153 63 86 75 NA 111 142 95 NA 134 164 115 NA 158 191 150 NA 189 228 177 NA 226 264 Table 1 UL Max. Strobe Current Draw (mA RMS) Setting UL Reverberant (dBA @10 ft) UL Anechoic (dBA @10 ft) 1/4 W 79 79 1/2 W 82 82 1 W 85 85 2 W 88 88 Table 2 Ceiling Speaker Sound Outputs Setting UL Reverberant (dBA @10 ft) UL Anechoic (dBA @10 ft) 1/4 W 77 77 1/2 W 80 80 1 W 83 83 2 W 86 86 Table 3 Ceiling-Mount Speaker Strobe Sound Output 3 Dimensions Figure 1 shows the speaker dimensions. Figure 2 shows the speaker dimensions. Surface Mounting Figure 3 illustrates the ceiling-mount speaker and speaker strobes with the SBBCR/SBBCWL surface mount backbox. L-Series Ordering Information SpectrAlert Speakers and Strobes: Ceiling Mount: SPCWL: White Speaker only SPCRL: Red Speaker only SPSCWL: White Speaker Strobe SPSCRL: Red Speaker Strobe SPSCWL-P: Plain, Speaker Strobe SPSCWL-SP: Fuego, Speaker Strobe SPSCWL-CLR-ALERT : Alert, Speaker Strobe,Clear Lens Accessories: SBBCWL: White, Universal Ceiling Surface Mount Back Box SBBCRL: Red, Universal Ceiling Surface Mount Back Box TRC-2W: White, Universal Ceiling Trim Ring TRC-2: Red, Universal Ceiling Trim Ring Figure 1 Speaker Dimensions Figure 2 Speaker Dimensions Figure 3 Ceiling-Mount Speaker and Speaker Strobe with SBBCRL/SBBCWL Surface Mount Backbox L Series, Indoor Ceiling Strobes and Dual Speakers Technical Specifications 9021-60930 | C | 03/18 ©2018 Honeywell International Inc. For a complete listing of all compliance approvals and certifications, please visit: http://www.gamewell- fci.com/en-US/ documentation/Pages/ Listings.aspx E3 Series® and Gamewell-FCI® are registered trademarks of Honeywell International Inc. UL® is a registered trademark of Underwriter’s Laboratories Inc. This document is not intended to be used for installation purposes. We try to keep our product information up-to- date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice. Honeywell Gamewell-FCI 12 Clintonville Road Northford, CT 06472-1610 203.484.7161 www.honeywell.com For more information Learn more about Gamewell-FCI’s L Series, Indoor Ceiling Strobes and Dual Speakers and other products available by visiting www.Gamewell-FCI.com SYSTEM Electrical/Operating Specifications: Nominal Voltage (speakers): 25 Volts or 70.7 Volts (nominal) Maximum Supervisory Voltage (speakers): 50 VDC Strobe Flash Rate: 1 flash per second Nominal Voltage (strobes): Regulated 12 VDC or Regulated 24 VDC/FWR Operating Voltage Range (includes fire alarm panels with built-in sync): 8 to 17.5 V (12 V nominal) or 16 to 33 V (24 V nominal) Operating Voltage with MDL3 Sync Module: 8.5 to 17.5 V (12 V nominal) or 16.5 to 33 V (24 V nominal) Frequency Range: Frequency Range: 400 to 4,000 Hz Power: ¼, ½, 1, 2 watts STANDARDS The L-Series, Indoor Ceiling Strobes and Horn Strobes are designed to comply with the following standard: UL Standard: UL 1971 and UL 464 AGENCY LISTINGS AND APPROVALS These listings and approvals apply to the modules specified in this document. In some cases, certain modules or applications may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status. UL: S5512, S4011 CSFM: 7320-1653:0505 ISO 9001 Certification Physical Specifications: Operating Temperature:32°F to 120°F (0°C to 49°C) Humidity Range:10 to 93% non-condensing Dimensions,Ceiling-Mount:Diameter Depth SPC Speaker 6.8 in, 173 mm 1.0 in, 25 mm With Surface Mount BacKbox 6.9 in, 176 mm 3.5 in, 89 mm SPSC Speaker Strobe 6.8 in, 173 mm 2.8 in, 73 mm With Surface Mount Backbox 6.9 in, 176 mm 5.37 in,136 mm Wall Horn, Horn Strobe L-Series, Indoor Strobes and Horn Strobes Indoor Selectable-Output Horns, Strobes and Horn Strobes for Wall Applications Notification Appliances General The L-Series audible visible notification products offer the most versatile and easy-to- use line of horns, strobes, and horn strobes in the industry. In addition, this product includes lower current draws and a modern aesthetic design which reduce installation times and maximize profits. The following devices offer a variety of design options, so that the L-Series can be used for any application requirement. • White and red plastic housings • Standard and small footprint devices • Plain, FIRE, and FUEGO-printed devices Similar to the entire L-Series product line, the wall-mount horns, strobes, and horn strobes include a variety of features that increase their application versatility while simplifying the installation. All devices offer a plug-in design so that there is minimal intrusion into the backbox. These features make installations fast and foolproof while eliminating costly and time-consuming ground faults. To further simplify the installation and protect devices from construction damage, the L-Series uses a mounting plate for all standard and compact models that include an onboard shorting spring. This feature allows Installers to test wiring continuity before the device is installed. Installers can also easily adapt devices to suit a wide range of application requirements using the following features: • Field-selectable candela settings • Automatic selection of 12- or 24-volt operation • Rotary switch for horn tones with two volume selections FEATURES & BENEFITS • Listed for wall mounting only • Offers small profile devices for horns and horn strobes • Provides an automatic selection of 12- or 24- volt operation at 15 and 30 candela • Produces horn rated at 88+ dBA at 16 volts • Uses field-selectable candela settings on wall units: - 15 - 30 - 75 - 95 - 110 - 135 - 185 • Includes a mounting plate for all standard and all compact wall units • Contains a mounting plate with a shorting spring that checks the wiring continuity before device installation • Features a plug-in design with minimal intrusion into the backbox •Designed with a tamper-resistant construction • Supports a rotary switch for horn tone and two volume selections 2 Architect/Engineer Specifications General When it is used with the Sync•Circuit Module, the following occur: • 12-volt-rated notification appliance circuit outputs shall operate between 8.5 and 17.5 volts • 24-volt-rated notification appliance circuit outputs shall operate between 16.5 and 33 volts The Indoor L-Series products shall operate between 32 and 120 degrees Fahrenheit from a regulated DC or full-wave rectified unfiltered power supply. Strobes and horn strobes shall have the following field-selectable candela settings: Strobe The strobe shall be an L-Series Model _______ listed to UL Standard 1971 and shall be approved for fire protective service. The strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances, flashing at 1 Hz over the strobe’s entire operating voltage range. The strobe light shall consist of a xenon flash tube and associated lens/ reflector system. Horn Strobe Combination The horn strobe shall be an L-Series Model _______ listed to UL Standard 1971 and UL Standard 464 and shall be approved for fire protective service. The horn strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances, flashing at 1 Hz over the strobe’s entire operating voltage range. The strobe light shall consist of a xenon flash tube and associated lens/reflector system. The horn shall have two audible options and an option to switch between a temporal three pattern and a non-temporal (continuous) pattern. These options are set by a multiple position switch. The horn on horn strobe models shall operate on a coded or non-coded power supply. Synchronization Module The module shall be a Sync•Circuit model MDL3 listed to UL Standard 464 and shall be approved for fire protective service. The module shall synchronize SpectrAlert strobes at 1 Hz and horns at temporal three. Also, while operating the strobes, the module shall silence the horns on horn strobe models over a single pair of wires. The module shall mount to a 4 11/16 x 4 11/16 x 2 1/8-inch backbox. The module shall also control two Style Y (Class B) circuits or one Style Z (Class A) circuit. The module shall synchronize multiple zones. Daisy-chaining two or more synchronization modules together will synchronize all the zones they control. The module shall not operate on a coded power supply UL Current Draw Table 1 lists the UL maximum strobe current draw. Table 2 lists the UL maximum Horn current draw.•15 •30 •75 •95 • 115 • 150 • 177 Candela 8-17.5 Volts 16-33 Volts FWRDC DC Candela Range 15 88 43 60 30 143 63 83 75 N/A 107 136 95 N/A 121 155 110 N/A 148 179 135 N/A 172 209 185 N/A 222 257 Table 1: UL Maximum Strobe Current Draw (mA RMS) Sound Pattern dB 8-17.5 Volts 16-33 Volts DC DC FWR Temporal High 39 44 54 Temporal Low 28 32 54 Non-Temporal High 43 47 54 Non-Temporal Low 29 32 54 3.1 KHz Temporal High 39 41 54 3.1 KHz Temporal Low 29 32 54 3.1 KHz Non-Temporal High 42 43 54 3.1 KHz Non-Temporal Low 28 29 54 Coded High 43 47 54 3.1 KHz Coded High 42 43 54 Table 2: UL Max. Horn Current Draw (mA RMS) 3 UL Current Draw Data Table 3 lists the maximum UL Current Draw (mA RMS) allowed for Wall Horn Strobes. Horn Strobe Tones and Sound Output Data Table 4 lists the horn strobe tones and sound output date. DC 8-17.5 Volts 16-33 Volts 15cd 30cd 15cd 30cd 75cd 95cd 110cd 135cd 185cd EM Temp Hi 98 158 54 74 121 142 162 196 245 EM Temp Low 93 154 44 65 111 133 157 164 235 EM Cont Hi 106 166 73 94 139 160 182 21 262 EM Cont Low 93 156 51 71 119 139 162 190 239 3.1K Temp Hi 93 156 53 73 119 140 164 190 242 3.1K Temp Low 91 154 45 66 112 133 160 185 235 3.1K Cont Hi 99 162 69 90 135 157 175 208 261 3.1K Cont Low 93 156 52 72 119 138 162 192 242 16V FWR FWR Input 15cd 30cd 75cd 95cd 110cd 135cd 185cd EM Temp Hi 83 107 156 177 198 234 287 EM Temp Low 68 91 145 165 185 223 271 EM Cont Hi 111 135 185 207 230 264 316 EM Cont Low 79 104 157 175 197 235 283 3.1K Temp Hi 81 105 155 177 196 234 284 3.1K Temp Low 68 90 145 166 186 222 276 3.1K Cont Hi 104 131 177 204 230 264 326 3.1K Cont Low 77 102 156 177 199 234 291 Table 3 UL Max. Current Draw (mA RMS), Wall Horn Strobe, Horn Strobe, Candela Range (15-115 cd) Switch Position Sound Pattern dB 8–17.5 Volts 16–33 Volts FWR DC DC 1 Temporal High 84 89 89 2 Temporal Low 75 83 83 3 Non-Temporal High 85 90 90 4 Non-Temporal Low 76 84 84 5 3.1 KHz Temporal High 83 88 88 6 3.1 KHz Temporal Low 76 82 82 7 3.1 KHz Non-Temporal High 84 89 89 8 3.1 KHz Non-Temporal Low 77 83 83 9* (See Note)Coded High 85 90 90 10* (See Note)3.1 KHz Coded High 84 89 89 Note: Settings 9 and 10 are not available on 2-Wire horns and strobes. Temporal coding must be provided by the NAC. If the NAC voltage is held constant, the horn output remains constantly on. Table 4: Horn Strobe Tones and Sound Output Data 4 L-Series Ordering Information Ceiling Horn Strobes: PC2RL : 2-Wire, Standard Horn Strobe, Red PC2WL: 2-Wire, Standard Horn Strobe, White P2GRL: 2-Wire, Compact Horn Strove, White P2RL-P: 2-Wire, Horn Strove, Red, Plain P2WL-P: 2-Wire, Horn Strobe, White, Plain P2RL-SP: 2-Wire, Horn Strobe, Red, FUEGO P2WL-SP: 2-Wire, Horn Strobe, White, FUEGO P4WL: 4-Wire, Horn Strobe, Red P4WLA: 4-Wire, Horn Strobe, White Wall Strobes: SRL: Strobe, Red SWL: Strobe, White SGRL: Compact Strobe, Red SGWL: Compact Strobe, White SRL-P: Strobe, Red, Plain SWL-P: Strobe, White, Plain SWL-CLR-ALERT: Strobe, White, ALERT L-Series Ordering Information HRL*: Horn, Red HWL*: Horn, White HGRL*: Compact Horn, Red HGWL*: Compact Horn, White Note: Horn-only models are listed for wall or ceiling use. Accessories: TR-2: Universal Wall Trim Ring Red TR-2W: Universal Wall Trim Ring White SBBRL: Ceiling Surface Mount Back Box, Red SBBWL: Ceiling Surface Mount Back Box, White SBBGRL: Compact Wall Surface Mount Backbox, Red SBBGWL: Compact Wall Surface Mount Backbox, White L-Series Dimensions Figure 1 Compact Strobe, Horn Strobe Figure 2 Compact Horn Figure 3 Compact Wall Surface Mount Backbox (SBBGRL, SBBGWL) Figure 4 Strobe, Horn Strobe Figure 5 Horn Figure 6 Wall Surface Mount Backbox (SBBRL/SBBWL) 3.46" 88 mm 5.27" 133.9 mm 1.91" 48.5 mm 1.25" 32 mm 3.46" 88 mm 5.27" 133.9 mm 1.25" 32 mm 3.57" (9.1 cm) 1.55" (3.9 cm) 5.38" (13.7 cm) 4.70" (11.94 cm) 1.91" (4.85 cm) 1.25" (3.18 mm) 5.67" (14.4 cm) 5.67" (144 mm) 1.25" (32 mm) 4.7" (119 mm) 4.82" (12.24 cm) 1.85" (4.69 cm) 5.78" (14.68 cm) L-Series, Indoor Strobes and Horn Strobes Technical Specifications 9021-60929 | C | 03/18 ©2018 Honeywell International Inc. For a complete listing of all compliance approvals and certifications, please visit: http://www.gamewell- fci.com/en-US/ documentation/Pages/ Listings.aspx E3 Series® and Gamewell-FCI® are registered trademarks of Honeywell International Inc. UL® is a registered trademark of Underwriter’s Laboratories Inc. This document is not intended to be used for installation purposes. We try to keep our product information up-to- date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice. Honeywell Gamewell-FCI 12 Clintonville Road Northford, CT 06472-1610 203.484.7161 www.honeywell.com For more information Learn more about Gamewell-FCI’s L-Series, Indoor Strobes and Horn Strobes and other products available by visiting www.Gamewell-FCI.com SYSTEMS Temperature Ranges: Standard Operating Temperature: 32°F to 120°F (0°C to 49°C) Humidity Range: 10 to 93% non-condensing Voltages: Strobe Flash Rate: 1 flash per second Nominal Voltage: Regulated 12 VDC or regulated 24 DC/FWR1 Operating Voltage Range2: 8 to 17.5 V (12 V nominal) or 16 to 33 V (24 V nominal) Operating Voltage Range (MDL3): 8.5 to 17.5V(12 V nominal) or 16.5 to 33 V(24V nominal) Wire Gage: Input Terminal Wire Gauge: 12 to 18 AWG Dimensions: Ceiling-Mount Dimensions (including lens): 6.8" diameter × 2.5" high (173 mm diameter × 64 mm high) Ceiling-Mount Surface Mount Backbox Skirt Dimensions (SBBCR, SBBCW): 6.9" diameter x 3.4" high (175 mm diameter x 86 mm high) Notes: 1. Full Wave Rectified (FWR) voltage is a non- regulated, time-varying power source that is used on some power supply and panel outputs. 2. P, S, PC, and SC products will operate at 12 V nominal only for 15 and 30 cd. TEMPERATURE AND HUMIDITY RANGES This system meets NFPA requirements for operation at 0 – 49°C/32 – 120°F and at a relative humidity 93% ± 2% RH (noncondensing) at 32°C ± 2°C (90°F ± 3°F). However, the useful life of the system's standby batteries and the electronic components may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and its peripherals be installed in an environment with a normal room temperature of 15 – 27°C/60 – 80°F. STANDARDS The L-Series, Ceiling Strobes and Horn Strobes are designed to comply with the following standard: UL Standard: UL 1971 and UL 464 AGENCY LISTINGS AND APPROVALS These listings and approvals apply to the modules specified in this document. In some cases, certain modules or applications may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status. UL: S5512, S4011 CSFM: 7135-1653:0503 7125-1653:0504 ISO 9001 Certification Brady B Haws Fire Alarm Systems Level IV 138751 2025-05-01