HomeMy WebLinkAboutPLANS - 22-00429 - jacqueline Klingler - Solar roof installADDITIONAL NOTES PLAN SET LEGEND
SHEET INDEX
VICINITY MAP APPLICABLE CODES
ABBREVIATIONS PROJECT INFORMATION
1.ALL MODULES WILL BE GROUNDED IN ACCORDANCE WITH
THE CODE AND THE MANUFACTURES INSTALLATION
INSTRUCTIONS.
2.ALL PLACARDS REQUIRED BY NEC 2017 CODE MACHINE
PRINTED LETTERS IN A CONTRASTING COLOR TO THE
PLACARD.
3.LIQUID TIGHT FLEXIBLE CONDUIT SHALL BE SUNLIGHT
RESISTANT.
4.ELECTRICAL INSTALLATION WILL COMPLY WITH NEC 2017
CODE.
5.ALL SOLAR MODULES EQUIPMENT AND METALLIC
COMPONENTS ARE TO BE BONDED.
6.ALL PLUMBING AND MECHANICAL ROOF VENTS TO CLEAR
FROM PHOTOVOLTAIC ARRAY, OR EXTEND ABOVE SOLAR
PANELS.
7.SOLAR PHOTOVOLTAIC SYSTEM TO BE INSTALLED ON
RESIDENTIAL STRUCTURE.
8.DESIGN COMPLYING WITH THE IBC 2018 CODE AND ALL
LOCAL ORDINANCES AND POLICIES.
9.THE PROJECT HAS BEEN DESIGNED TO WITHSTAND A
MINIMUM 110 MPH WIND LOAD.
10.THE SYSTEM WILL NOT BE INTERCONNECTED UNTIL
APPROVAL FROM THE LOCAL JURISDICTION AND A UTILITY
IS OBTAINED.
11.IF THE MAIN SERVICE PANEL DOES NOT HAVE VERIFIABLE
GROUNDING ELECTRODE, IT IS THE CONTRACTORS
RESPONSIBILITY TO INSTALL SUPPLEMENTAL GROUNDING
ELECTRODE.
12.EACH MODULE WILL BE GROUNDED USING THE SUPPLIED
CONNECTION POINTS IDENTIFIED ON THE MODULE AND
THE MANUFACTURERS INSTALLATION INSTRUCTIONS.
13.A LADDER SHALL BE IN PLACE FOR INSPECTION IN
COMPLIANCE WITH OSHA REGULATIONS.
14.PROPER ACCESS AND WORKING CLEARANCE WILL BE
PROVIDED "WARNING: PV POWER SOURCE" TO BE PLACED
EVERY 10 FT.
15.GFCI PROTECTION IN INVERTER.
OCCUPANCY: R-3
CONSTRUCTION TYPE: V-B
UNSPRINKLERED
ALL CONDUIT TO RUN ON EXTERIOR OF HOUSE UNLESS
OTHERWISE NOTED
PV-1 PROJECT INFORMATION,
VICINITY MAP
PV-2 SITE PLAN, AERIAL VIEW
PV-3 ELECTRICAL LINE DIAGRAM
AND NOTES
PV-4 REQUIRED SIGNAGE
ALL WORK TO COMPLY WITH THE
FOLLOWING CODE:
NEC 2017 CODE
IBC/IRC/IFC 2018 CODE
PR
O
J
E
C
T
I
N
F
O
R
M
A
T
I
O
N
,
VI
C
I
N
I
T
Y
M
A
P
IS
S
U
E
D
F
O
R
:
P
E
R
M
I
T
DA
T
E
06
/
1
4
/
2
0
2
2
SC
A
L
E
:
N
T
S
JO
B
#
:
ww
w
.
b
i
g
d
o
g
e
n
e
r
g
y
.
c
o
m
SO
L
A
R
P
H
O
T
O
V
O
L
T
A
I
C
S
Y
S
T
E
M
JA
C
Q
U
E
L
I
N
E
D
A
V
E
K
L
I
N
G
L
E
R
DE
S
I
G
N
E
D
B
Y
CO
N
T
R
A
C
T
O
R
I
N
F
O
R
M
A
T
I
O
N
PV-1
25
,
E
M
O
R
A
N
V
I
E
W
R
D
,
RE
X
B
U
R
G
,
ID
83
4
4
0
BI
G
D
O
G
R
E
N
E
W
A
B
L
E
E
N
E
R
G
Y
CO
N
T
R
A
C
T
O
R
L
I
C
#
:
ID
A
H
O
0
1
7
9
1
6
62
0
P
H
E
A
S
A
N
T
R
I
D
G
E
D
R
CH
U
B
B
U
C
K
,
I
D
8
3
2
0
2
20
8
-
2
4
2
-
3
3
5
2
T
20
8
-
2
3
2
-
5
9
3
5
F
X
_
_
_
_
_
_
_
_
_
_
_
_
_
_
_
_
_
_
(E) EXISTING
(N) NEW
EXT EXTERIOR
INT INTERIOR
EMT ELECTRICAL METALLIC TUBING
RMT RIGID METALLIC TUBING
FMC FLEXIBLE METALLIC CONDUIT
VOC VOLTAGE OPEN CIRCUIT
VMP VOLTAGE AT MAX. POWER
ISC SHORT CIRCUIT CURRENT
IMP CURRENT AT MAX. POWER
NTS NOT TO SCALE
MSP
SUB
AC
DC
SLC
M
INV
JB
CB
BAT
MAIN SERVICE PANEL
SUB SERVICE PANEL
AC DISCONNECT
DC DISCONNECT
SOLAR LOAD CENTER
MONITORING METER
INVERTER
JUNCTION BOX
COMBINER BOX
BATTERY
PV PRODUCTION METER
RAPID SHUTDOWN DISCONNECT
PM
RSD
JACQUELINE DAVE KLINGLER
25 E MORAN VIEW RD,
REXBURG, ID 83440
34 - URE FBM400MFG-BB (400W)
PHOTOVOLTAIC MODULES
2 - SOLAREDGE SE6000H-US (6000W)
INVERTER(S)
SYSTEM SIZE: 13.600 KW DC STC
ARRAY AREA:715.51 SF
M
S
P
M
T
R
I
N
V
A
C
A
C
I
N
V
SCALE: NTS AERIAL VIEW SCALE: NTS
SI
T
E
P
L
A
N
,
A
E
R
I
A
L
V
I
E
W
N IS
S
U
E
D
F
O
R
:
P
E
R
M
I
T
DA
T
E
06
/
1
4
/
2
0
2
2
SC
A
L
E
:
N
T
S
JO
B
#
:
ww
w
.
b
i
g
d
o
g
e
n
e
r
g
y
.
c
o
m
SO
L
A
R
P
H
O
T
O
V
O
L
T
A
I
C
S
Y
S
T
E
M
JA
C
Q
U
E
L
I
N
E
D
A
V
E
K
L
I
N
G
L
E
R
DE
S
I
G
N
E
D
B
Y
CO
N
T
R
A
C
T
O
R
I
N
F
O
R
M
A
T
I
O
N
PV-2
25
,
E
M
O
R
A
N
V
I
E
W
R
D
,
RE
X
B
U
R
G
,
ID
83
4
4
0
BI
G
D
O
G
R
E
N
E
W
A
B
L
E
E
N
E
R
G
Y
CO
N
T
R
A
C
T
O
R
L
I
C
#
:
ID
A
H
O
0
1
7
9
1
6
62
0
P
H
E
A
S
A
N
T
R
I
D
G
E
D
R
CH
U
B
B
U
C
K
,
I
D
8
3
2
0
2
20
8
-
2
4
2
-
3
3
5
2
T
20
8
-
2
3
2
-
5
9
3
5
F
X
_
_
_
_
_
_
_
_
_
_
_
_
_
_
_
_
_
_
ROOF DESCRIPTION
ROOF ARRAY PITCH AZIMUTH
#1 15°136°
SITE PLAN
ABBREVIATIONS
INV INVERTER
MSP MAIN SERVICE PANEL
AC AC DISCONNECT
MTR METER
ROOF #1
TOTAL # OF PANELS:
34
ROOF TYPE:
SHINGLE
3'
PATHWAY
S
H
E
D
E M
O
R
A
N
V
I
E
W
R
D
BOTH AC DISCONNECTS WITHIN
3’ FROM UTILITY METER
3'
PATHWAY
3'
PATHWAY
ELECTRICAL SINGLE LINE DIAGRAM
1.PV ARRAYS ARE PER SINGLE LINE.
2.PV ARRAY WIRING TO JUNCTION IS #10 AWG USE 2 W/
FIELD INSTALLED MC CONNECTORS TO INTERFACE W/
MODULES.
3.PV ARRAY COMBINER/JUNCTION BOX PROVIDES
TRANSITION FROM ARRAY WIRING TO CONDUIT
WIRING.
4.USE UFER GROUND ELECTRODE SYSTEM FROM
INVERTER TO EXISTING MAIN SERVICE GROUND
ELECTRODE PER N.E.C. 250.58.
5.GROUND ELECTRODE CONDUCTOR FROM INVERTER
TO GROUND ELECTRODE TO BE MINIMUM
PROTECTION OF BARE ARMOR SHEATHED CABLE FOR
ALL CONDUCTOR SIZES.
6.ALL GROUND CONNECTED TO MAIN SERVICE GROUND
IN MAIN SERVICE PANEL.
7.CONNECTORS SHALL BE POLARIS OR EUROSTRIP IT
CONNECTORS.
8.INVERTER SHALL BE PER SINGLE LINE, SEE ATTACHED
CUT SHEET.
9.INVERTER IS PER SINGLE LINE.
10.AC DISCONNECT SHALL BE PER SINGLE LINE.
11.EQUIPMENT GROUNDING CONDUCTORS ON AC AND
DC SIDE SIZED ACCORDING TO N.E.C. 690.
12.POLE OF PV ARRAY REFERENCED TO GROUND AT THE
INVERTER IN SINGLE LINE.
13.ALL CONDUCTORS SHALL BE 600V, 90C STANDARD
COPPER. ALL CONDUCTORS IN CONDUIT SHALL BE
THWN-2.
14.MAXIMUM DC VOLTAGE DROP SHALL BE 2.5%
15.ALL CONDUCTORS SHALL BE IN CONDUIT UNLESS
OTHERWISE NOTED.
16.ALL WORK TO COMPLY WITH NEC 2017 CODE.
17.DC ARRAY CONDUCTORS ARE TO REMAIN OUTSIDE OF
BUILDING PRIOR TO FUSIBLE COMBINER BOX OR
FUSIBLE DC DISCONNECT MEANS.
18.EXACT CONDUIT RUN LOCATIONS SUBJECT TO
CHANGE.
19.3.0 PSF MAX (.5 PSF FROM RACKING, 2.5 PSF FROM
MODULES) DEAD LOAD CONTRIBUTED FROM SOLAR
ARRAY.
20.ARC FAULT INSTALLED AT INVERTER OR IN COMBINER
BOX.
21.DC GROUND FAULT PROTECTION INTEGRATED IN
INVERTER.
22.POINT OF CONNECTION BREAKER TO BE LOCATED
OPPOSITE END OF BUSBAR FROM MAIN UNLESS
OTHERWISE NOTED.
23.ANY UNDERGROUND WIRING METHODS WILL COMPLY
WITH NEC 300.5(J), 300.7(B), 352.44, AND OTHER
SECTIONS OF CHAPTER 3 AS APPLICABLE.
24.ANY EXPOSED PVC CONDUIT SHALL COMPLY WITH
NEC 352.10
25.ALL PV SYSTEM DC CIRCUITS RUN INSIDE A BUILDING
SHALL BE CONTAINED IN A METAL RACEWAY IN
ACCORDANCE TO NEC 690.31(G)
26.COMPLIES WITH 705.12(B)(2)(3)(B)
27.SUPPLY SIDE CONNECTION WITH LISTED INSULATION
PIERCING CONNECTORS IN ACCORDANCE WITH
705.12(A) AND 230.82
28.CONNECTION AT PANEL SECONDARY SERVICE
LOCATION
29.COMPLIES WITH 705.12(B)(2)(1)(B)
ELECTRICAL NOTESSCALE: NTS
SI
N
G
L
E
L
I
N
E
D
I
A
G
R
A
M
RACKING & MODULES ARE GROUNDED VIA A
CONTINUOUS #6AWG COPPER CONDUCTOR
CONNECTED W/ WEEBS - MODULES ARE FACTORY
PROVIDED W/ 2 THREADED HOLES TO FACILITATE
LANDING OF THE LUGS
ALL EQUIPMENT SHALL BE PROPERLY GROUNDED AND
BONDED IN ACCORDANCE WITH ARTICLE 250. ALL
CIRCUITS CONNECTED TO MORE THAN ONE SOURCE
SHALL HAVE OVERCURRENT DEVICES LOCATED SO AS
TO PROVIDE OVERCURRENT PROTECTION FROM ALL
SOURCES 690.9 (A)
IS
S
U
E
D
F
O
R
:
P
E
R
M
I
T
DA
T
E
06
/
1
4
/
2
0
2
2
SC
A
L
E
:
N
T
S
JO
B
#
:
ww
w
.
b
i
g
d
o
g
e
n
e
r
g
y
.
c
o
m
SO
L
A
R
P
H
O
T
O
V
O
L
T
A
I
C
S
Y
S
T
E
M
JA
C
Q
U
E
L
I
N
E
D
A
V
E
K
L
I
N
G
L
E
R
DE
S
I
G
N
E
D
B
Y
CO
N
T
R
A
C
T
O
R
I
N
F
O
R
M
A
T
I
O
N
PV-3
25
,
E
M
O
R
A
N
V
I
E
W
R
D
,
RE
X
B
U
R
G
,
ID
83
4
4
0
BI
G
D
O
G
R
E
N
E
W
A
B
L
E
E
N
E
R
G
Y
CO
N
T
R
A
C
T
O
R
L
I
C
#
:
ID
A
H
O
0
1
7
9
1
6
62
0
P
H
E
A
S
A
N
T
R
I
D
G
E
D
R
CH
U
B
B
U
C
K
,
I
D
8
3
2
0
2
20
8
-
2
4
2
-
3
3
5
2
T
20
8
-
2
3
2
-
5
9
3
5
F
X
_
_
_
_
_
_
_
_
_
_
_
_
_
_
_
_
_
_
ALL MODULES WILL BE GROUNDED IN ACCORDANCE
WITH CODE AND THE MANUFACTURER'S
INSTALLATION INSTRUCTIONS.
1 ELECTRICAL LINE DIAGRAM
PV-3 SCALE: NTS
ELECTRICAL EQUIPMENT CALLOUTS13,600W TOTAL SOLAR ARRAY
34 URE FBM400MFG-BB (400W) PANELS
1 STRING OF 9 MODULES CONNECTED IN SERIES @ INVERTER-1
WIRE AND CONDUIT CALLOUTS
SOLADECK MODEL 0783-41 JUNCTION
BOX/ROOF PENETRATION, 600V
6.0kW INVERTER UNGROUNDED
SOLAREDGE SE6000H-US (240V) INVERTER
240VAC, 25A, NEMA 3R, UL LISTED,
(W/ INTEGRATED DC DISCONNECT)
WITH INTEGRATED GFP, W/ INTEGRATED AFP
(2) #10 AWG PV/RHW-2 IN FREE AIR
(1) #6 AWG BARE COPPER GND IN FREE AIR
(2) #10 AWG THWN-2
(1) #10 AWG THWN-2 GND IN 3/4" EMT/FMC
SOLAREDGE S440 OPTIMIZER ONE PER PANELA
B
C
D
E
SQUARE D SAFETY SWITCH, #D222NRB
250 VAC, 60A, NEMA 3R, FUSED, UL, NEMA,
CSA, NOM CERTIFIED W/ 40A FUSES
_
~
MPPT 1
MPPT 2
3 C
8 MODULES IN SERIES
9 MODULES IN SERIES
B A
AB ONE PER PANEL
2 1
STRING 1
STRING 2
ONE PER PANEL
2 1
_
~
MPPT 1
MPPT 2
3 C
8 MODULES IN SERIES
9 MODULES IN SERIES
B A
AB ONE PER PANEL
2 1
STRING 1
STRING 2
ONE PER PANEL
2 1
L1
L2
N
G
D3
L1
L2
N
G
E
N G
40A
BREAKER 28
200A
40A
BACKFEED 26
F
(2) #8 AWG THWN-2
(1) #10 AWG THWN-2 GND IN 3/4" EMT
1 STRING OF 8 MODULES CONNECTED IN SERIES @ INVERTER-1
1 STRING OF 9 MODULES CONNECTED IN SERIES @ INVERTER-2
1 STRING OF 8 MODULES CONNECTED IN SERIES @ INVERTER-2
LABEL TO BE INSTALLED
"MANUAL DISCONNECT FOR
PARALLEL GENERATION 2 OF 2"
LABEL TO BE INSTALLED
"MANUAL DISCONNECT FOR
PARALLEL GENERATION 1 OF 2"
250A (E) MAIN SERVICE PANEL SPLIT BUS
(W/ 200A MAIN BREAKER AT LOCALIZED BUSBAR
CENTER FED & 50A MAX RATED PARALLEL
DISTRIBUTION BREAKER ONLY SLOT)
1
2
3
L1
L2
N
G
D3
L1
L2
N
G
BI-DIRECTIONAL UTILITY METERF
BOTH AC DISCONNECTS WITHIN
3’ FROM UTILITY METER
MODULE:
URE FBM400MFG-BB (400W)
Voc= 37.20V Isc= 13.68A
Vmp= 31.17V Imp= 12.84A
REQUIRED SIGNAGE
IS
S
U
E
D
F
O
R
:
P
E
R
M
I
T
DA
T
E
06
/
1
4
/
2
0
2
2
SC
A
L
E
:
N
T
S
JO
B
#
:
ww
w
.
b
i
g
d
o
g
e
n
e
r
g
y
.
c
o
m
SO
L
A
R
P
H
O
T
O
V
O
L
T
A
I
C
S
Y
S
T
E
M
JA
C
Q
U
E
L
I
N
E
D
A
V
E
K
L
I
N
G
L
E
R
DE
S
I
G
N
E
D
B
Y
CO
N
T
R
A
C
T
O
R
I
N
F
O
R
M
A
T
I
O
N
PV-4
25
,
E
M
O
R
A
N
V
I
E
W
R
D
,
RE
X
B
U
R
G
,
ID
83
4
4
0
BI
G
D
O
G
R
E
N
E
W
A
B
L
E
E
N
E
R
G
Y
CO
N
T
R
A
C
T
O
R
L
I
C
#
:
ID
A
H
O
0
1
7
9
1
6
62
0
P
H
E
A
S
A
N
T
R
I
D
G
E
D
R
CH
U
B
B
U
C
K
,
I
D
8
3
2
0
2
20
8
-
2
4
2
-
3
3
5
2
T
20
8
-
2
3
2
-
5
9
3
5
F
X
_
_
_
_
_
_
_
_
_
_
_
_
_
_
_
_
_
_
RE
Q
U
I
R
E
D
S
I
G
N
A
G
E
WARNING
DUAL POWER SUPPLY
SOURCES: UTILITY GRID AND
PV SOLAR ELECTRIC SYSTEM
2. LABEL FOR SOLAR AC DISCONNECT:
SYSTEM AC VOLTAGE: 240V
TOTAL RATED AC AMPS: 40A
SYSTEM AC VOLTAGE: 240V
3. THE FOLLOWING SIGNAGE MUST HAVE A MINIMUM OF 3/8"
HIGH LETTERING, IN ARIAL FONT (NON-BOLD), WITH CAPITAL
LETTERS, WHITE ON RED BACKGROUND AND A REFLECTIVE,
WEATHER RESISTANT MATERIAL.
1. PROVIDE A PLACARD WITH THE FOLLOWING WORKING IN 1/4"
HIGH LETTERING PER NEC 690-17.
AT THE MAIN SERVICE DISCONNECT PROVIDE A SIGN WITH THE
FOLLOWING WORDING: FOLLOWING WORDING:
THE SIGN SHOULD BE PLACED ON THE OUTSIDE COVER IF THE MAIN
SERVICE DISCONNECT IS OPERABLE WITH THE SERVICE PANEL CLOSED.
CUSTOMER OWNED
ON SITE POWER GENERATION
SYSTEM DISCONNECT
8. THE FOLLOWING SIGN MUST BE PROVIDED ON THE
OUTSIDE (OR WITHIN 3' OF) THE SERVICE
PANELBOARD, AS REQUIRED PER NEC 690.56(C)(1):
RAPID SHUTDOWN SWITCH
FOR SOLAR PV SYSTEM
PHOTOVOLTAIC SYSTEM
EQUIPPED WITH RAPID
SHUTDOWN
ALL SIGNAGE MUST BE PERMANENTLY ATTACHED AND
BE WEATHER RESISTANT/SUNLIGHT RESISTANT AND CANNOT BE
HAND-WRITTEN.
NEC 110.21(B)
FIRE DEPARTMENT REQUIRED SIGNAGE
4. LABELS TO BE INSTALLED ON FACE OF THE UTILITY AC DISCONNECT:
5. LABEL INSTALLATION AT INTERCONNECT BREAKER:
9. SIGNAGE REQUIRED AT SERVICE PANELBOARD PER NEC 690.54:
7. AT PV DISCONNECT SWITCH AS REQUIRED PER NEC 690.56(C)(3):
6. REFLECTIVE PLACARD AT SERVICE STATING:
"SOLAR AC DISCONNECT"
WARNING:
ELECTRICAL SHOCK HAZARD.
DO NOT TOUCH TERMINALS. TERMINALS
ON BOTH THE LINE AND LOAD SIDES MAY
BE ENERGIZED IN THE OPEN POSITION.
WARNING:
INVERTER CONNECTION.
DO NOT RELOCATE THIS
OVERCURRENT DEVICE.
DIRECT CURRENT PHOTOVOLTAIC SOURCE
SYSTEM AC VOLTAGE: 240V
MAX AC CIRCUIT CURRENT: 25A
MAX DC CURRENT PER OPTIMIZER: 15A
10. SIGNAGE REQUIRED AT STRING INVERTER PER NEC 690.53:
DIRECT CURRENT PHOTOVOLTAIC SOURCE
SYSTEM AC VOLTAGE: 240V
MAX AC CIRCUIT CURRENT: 25A
MAX DC CURRENT PER OPTIMIZER: 15A
MANUAL DISCONNECT
FOR PARALLEL
GENERATION 1 OF 2
11. LABELS TO BE INSTALLED ON FACE OF AC DISCONNECTS:
MANUAL DISCONNECT
FOR PARALLEL
GENERATION 2 OF 2