Corrections in the following table need to be applied before a permit can be issued
Review Report
Revisions Required
Page Reference Annotation
Type
Author : Department Status Page Review Comments Applicant Response Comments
G002 Free Text Cody Jones : Building Open 3 Penetrations comply with IBC Section 714 for rated assemblies
G002 Free Text Cody Jones : Building Open 3 Ducts and dampers meet the requirements of IBC Section 717
G002 Free Text Cody Jones : Building Open 3 Concealed spaces are fireblocked/draftstopped per Section
718
G002 Free Text Cody Jones : Building Open 3 Accessible Means of Egress complies with IBC Section 1009
G002 Note Cody Jones : Building Open 3 Recreational Facilities comply with IBC Section 1110
G002 Note Cody Jones : Building Open 3 Electrical: Exit Signs/Emergency Lighting
G003 Free Text Cody Jones : Building Open 4 Fire barrier to comply with Section 707 and continuity of 707.5.
A0.00 Free Text Cody Jones : Building Open 5 86 parking stalls would require 4 ADA accessible stalls with at
least one of those being van accessible. 1106.1, 1106.5.
A1.1 Free Text Cody Jones : Building Open 9 2 hour rated wall to have listed assembly specified.
A1.1 Free Text Cody Jones : Building Open 10 Egress width 68"
A5.1 Free Text Cody Jones : Building Open 42 As per section 1003.1 a barrier shall be provided where the
vertical clearance above a circulation path is less than 80" high
above finished floor.
# 23-00172
New Commercial Building
Please digitally re-submit all pages of the plan set in response to requested revisions
for our next review cycle, with noted items resolved.
Report Date: 04.26.2023
Approval of plans does not constitute approval of variance from code
Page 1 of 2
Page Reference Annotation
Type
Author : Department Status Page Review Comments Applicant Response Comments
A7.1 Note Cody Jones : Building Open 56 Panic Hardware shall be installed as per IBC Section 1010.1.10
A8.2 Free Text Cody Jones : Building Open 60 Suspended ceiling to be installed to manufacturers
specifications.
S1.0 Note Cody Jones : Building Open 62 Roof and Roof Fire Classification comply with IBC Chapter 15
S1.1 Free Text Cody Jones : Building Open 63 Special inspector needs to be identified as per Chapter 17.
S1.2 Note Cody Jones : Building Open 64 Rebar: 8' Wall-Horizontal & Vertical 24" O.C. with 2 in Top 12"
Rebar: 4' Wall-Horizontal & Vertical 24" O.C. with 1 in Top 6"
E-5.1 Callout Alex Owens : Electrical Open 121 Available fault current calculation needed
E-5.1 Callout Alex Owens : Electrical Open 121 Available fault current calculations needed for service and
panels
E-5.1 Callout Alex Owens : Electrical Open 121 2 runs parallel 350 aluminum conductors is not adequate
feeder size for 600 amps.
Report Date: 04.26.2023
Approval of plans does not constitute approval of variance from code
Page 2 of 2