HomeMy WebLinkAboutCRAPO BUILDING 156-Reviewed-Corrections-RequiredAuthor Name Author Email Author Phone No.:
Cody Jones Cody.Jones@rexburg.org 208-372-2173
Kyle Baldwin Kyle.Baldwin@rexburg.org 208-372-2164
Don Allen Don.Allen@rexburg.org 208-372-2174
Alex Owens Alex.Owens@rexburg.org 208-372-2172
Description : Crapo 3 Plex - Remodel
Address : 156 E 2nd S
Application Type :
Document Filename : CRAPO BUILDING 156.pdf Array
Comment Author Contact Information:
Corrections in the following table need to be applied before a permit can be issued
Review Report
Revisions Required
Page Reference Annotation
Type
Author : Department Status Page Review Comments Applicant Response Comments
A000 Free Text Cody Jones : Building Open 1 R2 occupancy type
VB construction?
Need to have site plan
Need Envelope COMM check
Stamped architectural plans
Listed horizontal and vertical assemblies need to be noted
Landings at doors and cross slope of sidewalk not to exceed
2%.
Dwelling units to not have a sound transmission of less than
50
Stairways to comply with IBC 2018
A000 Note Cody Jones : Building Open 1 Concealed spaces are fireblocked/draftstopped per Section
718
A000 Note Cody Jones : Building Open 1 Ventilation is provided as per IBC Section 1203
A000 Note Cody Jones : Building Open 1 Site Grading meets the requirements of IBC Section 1804.4
A000 Note Cody Jones : Building Open 1 Dampproofing/Waterproofing comply with IBC Section 1805
A000 Note Cody Jones : Building Open 1 Glass and Glazing meets the requirements of IBC Chapter 24
# 23-00766
Multi-Family - Remodel
Please digitally re-submit all pages of the plan set in response to requested revisions
for our next review cycle, with noted items resolved.
Report Date: 10.31.2023
Approval of plans does not constitute approval of variance from code
Page 1 of 2
Page Reference Annotation
Type
Author : Department Status Page Review Comments Applicant Response Comments
S1.0 Free Text Cody Jones : Building Open 5 36"
S1.0 Free Text Cody Jones : Building Open 5 35
50
A000 Free Text Alex Owens : Electrical Open 1 No electrical plans provided. All electrical work must comply
with 2017 NEC.
A000 Free Text Kyle Baldwin : P&Z Open 1 Please submit full Site plan and show parcel lines, any
landscaping and parking stalls. Remember to label streets and
include North indicator.
Report Date: 10.31.2023
Approval of plans does not constitute approval of variance from code
Page 2 of 2
Powered by TCPDF (www.tcpdf.org)
1 2 3 4 5
AL
E
X
V
A
L
E
N
C
I
A
D
E
S
I
G
N
ph
o
n
e
:
9
3
7
.
2
3
2
.
0
0
3
7
av
b
a
l
l
8
@
g
a
m
i
l
.
c
o
m
RE
V
.
DA
T
E
BY
DE
S
C
R
I
P
T
I
O
N
PR
O
J
E
C
T
M
A
N
A
G
E
R
:
CA
D
O
P
E
R
A
T
O
R
:
DATE:
JO
B
N
O
.
:
ST
R
U
C
T
U
R
A
L
E
N
G
I
N
E
E
R
S
S
E
A
L
:
PR
O
J
E
C
T
:
CL
I
E
N
T
:
CURRENT REV.
A000
Pr
o
j
e
c
t
N
u
m
b
e
r
CO
V
E
R
S
H
E
E
T
Au
t
h
o
r
B
U
I
L
D
I
N
G
1
5
6
15
6
E
2
N
D
S
,
R
E
X
B
U
R
G
,
I
D
8
3
4
4
0
CR
A
P
O
BUILDING 156
• SCALE: 1/4" = 1'-0"
• SQFT: 3,091
• REMODEL & REPAIR
• REPLACE DAMAGED AND
EXISTING ADD-ON, REMODEL
INTERIOR INTO THREE
APARTMENTS
SHEET INDEX
SHEET DESCRIPTION DETAILS
A000 COVER SHEET
A100 SITE PLAN
A101 FLOOR PLANS
A102 ELEVATIONS
No electrical plans provided. All
electrical work must comply with
2017 NEC.
R 2 occupancy type
V B construction?
Need to have site plan
Need Envelope CO M M check
S tamped architectural plans
L isted horiz ontal and vertical assemb lies need to b e noted
L anding s at doors and cross slope of sidewalk not to ex ceed 2% .
D welling units to not have a sound transmission of less than 5 0
S tairways to comply with IB C 2018
P lease sub mit full S ite plan and show parcel
lines, any landscaping and parking stalls.
R ememb er to lab el streets and include North
indicator.
E 2ND S
41
'
-
0
"
41' - 0"
13
0
'
-
0
"
44
'
-
1
1
5
/
8
"
72
'
-
0
3
/
8
"
13
'
-
0
"
7' - 2"27' - 10"6' - 0"
1 2 3 4 5
AL
E
X
V
A
L
E
N
C
I
A
D
E
S
I
G
N
ph
o
n
e
:
9
3
7
.
2
3
2
.
0
0
3
7
av
b
a
l
l
8
@
g
a
m
i
l
.
c
o
m
RE
V
.
DA
T
E
B
Y
D
E
S
C
R
I
P
T
I
O
N
PR
O
J
E
C
T
M
A
N
A
G
E
R
:
C
A
D
O
P
E
R
A
T
O
R
:
DATE:
JO
B
N
O
.
:
ST
R
U
C
T
U
R
A
L
E
N
G
I
N
E
E
R
S
S
E
A
L
:
PR
O
J
E
C
T
:
CL
I
E
N
T
:
CURRENT REV.
A100
Pr
o
j
e
c
t
N
u
m
b
e
r
SI
T
E
P
L
A
N
Au
t
h
o
r
B
U
I
L
D
I
N
G
1
5
6
15
6
E
2
N
D
S
,
R
E
X
B
U
R
G
,
I
D
8
3
4
4
0
CR
A
P
O
1/8" = 1'-0"1 Site
NORTH
27' - 4 1/4"
38
'
-
8
1
/
4
"
9'
-
3
1
/
8
"
24
'
-
1
"
11' - 1"5' - 7"11' - 2"
27' - 10"
72
'
-
0
3
/
8
"
15
'
-
0
"
5'
-
7
3
/
8
"
12
'
-
0
"
15
'
-
1
0
"
15' - 3 1/4"
15
'
-
6
"
15
'
-
9
"
5'
-
0
"
9' - 3"
13' - 7"
10
'
-
7
3
/
8
"
BEDROOM
FAMILY
KITCHEN
BATH
BEDROOM
BEDROOM BEDROOM
FAMILY
KITCHEN
BATH
LAUNDRY
EXISTING
STAIR
8' - 10"
2'
-
7
"
5'
-
3
"
12
'
-
4
"
11' - 4 5/8"
3' - 6"
5' - 0"
21' - 3 3/4"
LAUNDRY
3'
-
6
"
2'
-
0
"
7'
-
9
"
2'
-
0
"
5'
-
1
0
"
2'
-
0
"
0'
-
8
"
3'
-
2
"
4'
-
6
"
4'
-
0
"
9'
-
9
1
/
4
"
2'
-
0
"
3'
-
0
"
5'
-
8
"
2'
-
0
"
10
'
-
6
"
5'
-
6
"
7'
-
9
"
5'
-
0
"
4'
-
2
"
5'
-
4
"
1'
-
1
"
0'
-
2
"
4' - 4 1/2"
8'
-
0
3
/
8
"
12
'
-
0
"
9' - 10 5/8"
2'
-
0
"
CLOSET
9' - 7"7' - 1"9' - 8"
0'
-
1
1
"
4'
-
0
"
3'
-
6
3
/
8
"
15
'
-
1
0
"
12
'
-
7
"
1' - 10 1/2"4' - 6"1' - 10 1/2"
2'
-
6
"
1' - 0"2' - 6"1' - 8 1/2"3' - 0"4' - 0"4' - 8"2' - 6"2' - 11 3/4"4' - 0"1' - 0"
11
22
33
44
55
8'
-
1
1
"
38
'
-
8
1
/
2
"
8'
-
2
7
/
8
"
15
'
-
1
0
"
A
A
B
B
C
C
D
D
10' - 5"3' - 7"13' - 4 1/4"
SD
SD
SD SD
SDSD
SD
SD
3'
-
6
"
4' - 0"7' - 2 3/4"
STAIR
4
5 TYP
TYP
9' - 2"
6'
-
9
"
16' - 6 3/4"
13
'
-
2
"
25
'
-
6
1
/
2
"
12' - 8 7/8"12' - 9 3/8"10
'
-
1
1
/
2
"
2'
-
1
1
"
8' - 7"
6'
-
8
7
/
8
"
11' - 4 3/4"
5'
-
4
1
/
2
"
10' - 2 3/4"
8'
-
1
"
10' - 1 1/4"15' - 11 1/2"
8'
-
1
"
11
'
-
0
3
/
8
"
15' - 5 1/2"
26' - 11 3/4"
27
'
-
5
1
/
2
"
20
'
-
2
3
/
8
"
47
'
-
7
7
/
8
"
33
'
-
6
3
/
8
"
14
'
-
3
1
/
2
"
2' - 8 3/4"3' - 9"20' - 10"
27' - 3 3/4"
4' - 2 3/8"4' - 8 5/8"
8' - 0 1/4"
BATH
FAMILY
KITCHEN
BEDROOM
BEDROOM
PANTRY
STORAGE
MECH
STAIR
6'
-
0
"
5' - 8"
LAUNDRY
4'
-
6
"
5'
-
1
"
3'
-
0
"
8'
-
2
"
2'
-
5
"
11
22
33
44
5
A
A
B
B
C
C
D
D
SD
SD
SD
SD
5 TYP
4 TYP
1 2 3 4 5
AL
E
X
V
A
L
E
N
C
I
A
D
E
S
I
G
N
ph
o
n
e
:
9
3
7
.
2
3
2
.
0
0
3
7
av
b
a
l
l
8
@
g
a
m
i
l
.
c
o
m
RE
V
.
DA
T
E
B
Y
D
E
S
C
R
I
P
T
I
O
N
PR
O
J
E
C
T
M
A
N
A
G
E
R
:
C
A
D
O
P
E
R
A
T
O
R
:
DATE:
JO
B
N
O
.
:
ST
R
U
C
T
U
R
A
L
E
N
G
I
N
E
E
R
S
S
E
A
L
:
PR
O
J
E
C
T
:
CL
I
E
N
T
:
CURRENT REV.
A101
Pr
o
j
e
c
t
N
u
m
b
e
r
FL
O
O
R
P
L
A
N
S
AV
B
U
I
L
D
I
N
G
1
5
6
15
6
E
2
N
D
S
,
R
E
X
B
U
R
G
,
I
D
8
3
4
4
0
CR
A
P
O
1/4" = 1'-0"2 MAIN LEVEL
1/4" = 1'-0"1 BASEMENT
NORTH
KEYNOTES
1 AUTOMATIC SPRINKLER SYSTEM SHALL BE PROVIDED
PER ICC SECTION 903.3
2 NEW EXTERIOR WALLS TO BE CLAD IN VINYL SIDING
3 EXISTING EXTERIOR WALLS CLAD IN BRICK
4 BOLD WALLS ARE NEW CONSTRUCTION
5 THIN WALLS ARE EXISTING STRUCTURE
BASEMENT
0' -0"
MAIN LEVEL
9' -0"
ROOF
18' -0"
2
BASEMENT
0' -0"
MAIN LEVEL
9' -0"
ROOF
18' -0"
3
BASEMENT
0' -0"
MAIN LEVEL
9' -0"
ROOF
18' -0"
3
2
BASEMENT
0' -0"
MAIN LEVEL
9' -0"
ROOF
18' -0"
2
3
1 2 3 4 5
AL
E
X
V
A
L
E
N
C
I
A
D
E
S
I
G
N
ph
o
n
e
:
9
3
7
.
2
3
2
.
0
0
3
7
av
b
a
l
l
8
@
g
a
m
i
l
.
c
o
m
RE
V
.
DA
T
E
B
Y
D
E
S
C
R
I
P
T
I
O
N
PR
O
J
E
C
T
M
A
N
A
G
E
R
:
C
A
D
O
P
E
R
A
T
O
R
:
DATE:
JO
B
N
O
.
:
ST
R
U
C
T
U
R
A
L
E
N
G
I
N
E
E
R
S
S
E
A
L
:
PR
O
J
E
C
T
:
CL
I
E
N
T
:
CURRENT REV.
A102
Pr
o
j
e
c
t
N
u
m
b
e
r
EL
E
V
A
T
I
O
N
S
AV
B
U
I
L
D
I
N
G
1
5
6
15
6
E
2
N
D
S
,
R
E
X
B
U
R
G
,
I
D
8
3
4
4
0
CR
A
P
O
1/4" = 1'-0"1 South
1/4" = 1'-0"2 North
1/4" = 1'-0"3 West
1/4" = 1'-0"4 East
KEYNOTES
1 AUTOMATIC SPRINKLER SYSTEM SHALL BE PROVIDED
PER ICC SECTION 903.3
2 NEW EXTERIOR WALLS TO BE CLAD IN VINYL SIDING
3 EXISTING EXTERIOR WALLS CLAD IN BRICK
4 BOLD WALLS ARE NEW CONSTRUCTION
5 THIN WALLS ARE EXISTING STRUCTURE
CAST IN PLACE
CENTERLINE
CENTERLINE OF BEAM
CENTERLINE OF COLUMN
CENTERLINE OF WALL
CLEAR
CONCRETE
CONCRETE CONTROL JOINT
CONCRETE SAWCUT JOINT
CONCRETE MASONRY UNIT
CONNECTION
CONTINUOUS
DEAD LOAD
DOWN
DRAWING(S)
EQUAL
EQUIPMENT
EXPANSION JOINT
EACH WAY
FINISHED FLOOR
FACE OF STEEL
FACE OF WALL
GAUGE
GALVANIZED
GENERAL STRUCTURAL NOTES
CENTERLINE OF FOOTING
FACE OF MEMBER
EXPANSION BOLT
EDGE OF SLAB
DIAMETER
GALV.
GSN
DN.
DWG(S)
EQ.
EQUIP.
EXP. JT (E.J.)
E.W.
F.F.
F.O.S.
F.O.W.
GA.
F.O.M.
EXP. BOLT
E.O.S.
o OR DIA.
C.I.P.
C.L.
C.L.B.
C.L.C.
C.L.W.
CLR
CONC
C.C.J.
C.S.J.
C.M.U.
CONN.
CONT.
D.L.
C.L.F.
W/ WITH
W/O WITHOUT
T.O.P.
U.N.O.
W.W.F.
TYP.
VERT
T.O.S.
T.O.W.
T.O.D.
T.O.F.
T.O.L.
T.O.M.
STD
T.O.B.
T.L.
SLH
SLV
SIM.
SQ.
PSF
PSI
REINF.
PREFAB
OPP.
P.C.
PLF
N.T.S.
O.C.
O.F.W.
TOP OF FOOTING
UNLESS NOTED OTHERWISE
WELDED WIRE FABRIC
TOP OF MASONRY
TOP OF PLATE
TOP OF STEEL
TOP OF WALL
TYPICAL
VERTICAL
STANDARD
TOP OF BEAM
TOP OF DECK
TOP OF LEDGER
TOTAL LOAD
OUTSIDE FACE OF WALL
PRECAST CONCRETE
POUNDS PER LINEAR FOOT
POUNDS PER SQUARE FOOT
POUNDS PER SQUARE INCH
SHORT LEG VERTICAL
SHORT LEG HORIZONTAL
REINFORCING
SIMILAR
SQUARE
NOT TO SCALE
ON CENTER
OPPOSITE
PREFABRICATED
AGGREGATE BASE COURSE
AIR CONDITIONER
ABOVE FINISHED FLOOR
ALTERNATE
ANCHOR BOLT
AT (MEASUREMENT)
BEAM
BOTTOM OF BEAM
BOTTOM OF DECK
BEARING
BELOW FINISHED FLOOR
BOTTOM OF FOOTING
A.B.C.
A/C
A.F.F.
ALT.
A.B.
@
BM
B.O.B.
B.O.D.
BRG
B.F.F
B.O.F.
ABBREVIATIONS
LBS (#)
MFR('S)
M.C.J.
MECH'L.
N/A
LLV
LLH
HORIZ.
K(KIP)
GLB (GLULAM)
I.F.W.
L.L.
LONG LEG VERTICAL
MANUFACTURER('S)
MASONRY CONTROL JOINT
NOT APPLICABLE
LONG LEG HORIZONTAL
GLUED-LAMINATED BEAM
INSIDE FACE OF WALL
POUNDS
MECHANICAL
HORIZONTAL
1000 POUNDS
LIVE LOAD
EXISTING(E)
MIN. MINIMUM
MAX. MAXIMUM
SYMBOLS LEGEND
WALLS WITH SOLID LINES DESIGNATE STRUCTURAL (BEARING) WALLS.
WALLS WITH DASHED LINES DESIGNATE NON-STRUCTURAL (NON-BEARING)
WALLS.
WALLS WITH HATCH DESIGNATE MASONRY WALLS.
, , , -AS SHOWN ON PLAN INDICATES A SHEARWALL; HATCHING IN WALL
DESIGNATES SHEARWALL LENGTH.
5 6 7
, , - AS SHOWN ON PLAN INDICATES A SHEARWALL HOLDOWN. SEE HOLDOWN
SCHEDULES AND DETAILS FOR ADDITIONAL INFORMATION.
A B
INDICATES HVAC EQUIPMENT ON ROOF OR IN ATTIC SPACE. SEE TYPICAL
DETAILS FOR FRAMING INFORMATION.
- AS SHOWN ON PLAN INDICATES A HELICAL PIER.
XXXX CS16, CMSTC16, ECT. - AS SHOWN AT WALL OPENINGS INDICATE STRAPPING,
PROVIDE STRAPPING PER "TYPICAL STRAP AT OPENING" DETAIL.
D=xxx# INDICATES DRAG LOAD (ASD) THAT TRUSS MANUFACTURER IS TO DESIGN
TRUSS FOR IN BOTH TENSION AND COMPRESSION.
STEP INDICATES STEPPED OR DEPRESSED SLAB.
C=X" INDICATES CAMBER IN BEAM.
INDICATES RIDGID CONNECTION.
(NOT ALL SYMBOLS NECESSARILY APPLY TO THIS PROJECT)
P1, P2, ETC. AS SHOWN ON PLAN INDICATES A WOOD POST. SEE POST
SCHEDULE FOR MORE INFORMATION.
SC1, SC2, ETC. - AS SHOWN ON PLAN INDICATES A STEEL COLUMN. SEE
STEEL COLUMN SCHEDULE FOR ADDITIONAL INFORMATION. COLUMNS START
AT THE LEVEL THEY ARE CALLED OUT ON.
PX
SCX
RME
XXX#
1 2 3 4 5
RE
V
.
DA
T
E
BY
DE
S
C
R
I
P
T
I
O
N
Th
i
s
d
r
a
w
i
n
g
i
s
t
h
e
p
r
o
p
e
r
t
y
o
f
F
R
O
S
T
S
t
r
u
c
t
u
r
a
l
E
n
gi
n
e
e
r
i
n
g
,
I
n
c
.
Le
g
a
l
l
y
,
t
h
e
d
r
a
w
i
n
g
c
a
n
N
O
T
b
e
c
o
p
i
e
d
i
n
w
h
o
l
e
o
r
in
p
i
e
c
e
s
.
I
t
is
o
n
l
y
t
o
b
e
u
s
e
d
f
o
r
t
h
e
p
r
o
j
e
c
t
a
n
d
s
i
t
e
s
p
e
c
i
f
i
ca
l
l
y
i
d
e
n
t
i
f
i
e
d
he
r
e
o
n
a
n
d
i
s
n
o
t
t
o
b
e
u
s
e
d
o
n
a
n
y
o
t
h
e
r
p
r
o
j
e
c
t
.
Co
n
t
r
a
c
t
o
r
sh
a
l
l
c
a
r
e
f
u
l
l
y
r
e
v
i
e
w
a
l
l
d
i
m
e
n
s
i
o
n
s
,
d
e
t
a
i
l
s
,
a
n
d
c
o
n
d
i
t
i
o
n
s
a
n
d
re
p
o
r
t
a
t
o
n
c
e
a
n
y
e
r
r
o
r
,
i
n
c
o
n
s
i
s
t
e
n
c
y
o
r
o
m
i
s
s
i
o
n
d
i
s
c
o
v
e
r
e
d
be
f
o
r
e
c
o
n
s
t
r
u
c
t
i
o
n
.
Th
e
c
o
n
t
r
a
c
t
o
r
a
s
s
u
m
e
s
f
u
l
l
l
i
a
b
i
l
i
t
y
f
o
r
d
e
v
i
a
t
i
o
n
s
f
r
o
m
t
h
e
in
t
e
n
t
o
f
t
h
e
s
e
p
l
a
n
s
.
PR
O
J
E
C
T
M
A
N
A
G
E
R
:
CA
D
O
P
E
R
A
T
O
R
:
DATE:
JO
B
N
O
.
:
ST
R
U
C
T
U
R
A
L
E
N
G
I
N
E
E
R
S
S
E
A
L
:
PR
O
J
E
C
T
:
CL
I
E
N
T
:
CURRENT REV.
S1.0
GE
N
E
R
A
L
S
T
R
U
C
T
U
R
A
L
N
O
T
E
S
AV
C
R
A
P
O
1
5
6
15
6
E
2
n
d
S
RE
X
B
U
R
G
,
I
D
83
4
4
0
CR
A
P
O
SHEET INDEX
SHEET DESCRIPTION DETAILS
S1.0 GENERAL STRUCTURAL NOTES ---
S2.0 FOUNDATION PLAN ---
S2.1 FIRST FLOOR FRAMING PLAN ---
S2.2 ROOF FRAMING PLAN ---
LOCATION LIVE / SNOW
LOAD DEAD LOAD
ELEMENTS LIVE LOAD TOTAL LOAD
LOCATION:MINIMUM
COVER TOLERANCE
USE:CONCRETE
STRENGTH:
MAX W/C
RATIO
AIR
ENTRAINMENT
USE:MATERIAL:
GENERAL REQUIREMENTS:
BASIS FOR DESIGN:
FOUNDATION NOTES:CONCRETE:WOOD:DEFERRED SUBMITTAL ITEMS:
1.THE STRUCTURAL SYSTEMS AND MEMBERS DEPICTED HEREIN HAVE BEEN
DESIGNED PRIMARILY TO SAFEGUARD AGAINST MAJOR STRUCTURAL DAMAGE AND
LOSS OF LIFE, NOT TO LIMIT DAMAGE OR MAINTAIN FUNCTION (IBC SECTION 101.3).
2.THESE DRAWINGS, AND THEIR ASSOCIATED STRUCTURAL CALCULATIONS, HAVE
BEEN PERFORMED USING STANDARDS OF PROFESSIONAL CARE AND
COMPLETENESS NORMALLY EXERCISED UNDER SIMILAR CIRCUMSTANCES BY
REPUTABLE STRUCTURAL ENGINEER'S IN THIS OR SIMILAR LOCALITIES. THEY
NECESSARILY ASSUME THAT THE WORK DEPICTED WILL BE PERFORMED BY AN
EXPERIENCED CONTRACTOR AND/OR WORKMEN WHO HAVE A WORKING
KNOWLEDGE OF THE INTERNATIONAL BUILDING CODE CONVENTIONAL FRAMING
REQUIREMENTS AND OF INDUSTRY ACCEPTED STANDARD GOOD PRACTICE. AS NOT
EVERY CONDITION OR FRAMING ELEMENT IS (OR CAN BE) EXPLICITLY SHOWN ON
THESE DRAWINGS, IT IS UNDERSTOOD THAT THE CONTRACTOR WILL USE INDUSTRY
ACCEPTED STANDARD GOOD PRACTICE FOR ALL MISCELLANEOUS WORK NOT
EXPLICITLY SHOWN.
3.THESE DRAWINGS REPRESENT THE FINISHED STRUCTURE. THEY DO NOT INDICATE
THE METHOD OF CONSTRUCTION. THE CONTRACTOR SHALL BE SOLELY
RESPONSIBLE FOR CONSTRUCTION MEANS, METHODS, TECHNIQUES, SEQUENCES
AND PROCEDURES. CONSTRUCTION MATERIALS SHALL BE SPREAD OUT IF PLACED
ON FRAMED CONSTRUCTION SUCH THAT DESIGN LIVE LOAD PER SQUARE FOOT AS
STATED HEREIN IS NOT EXCEEDED. OPTIONS ARE FOR CONTRACTOR'S
CONVENIENCE. IF AN OPTION IS USED, THE CONTRACTOR SHALL BE RESPONSIBLE
FOR ALL NECESSARY CHANGES, AND SHALL COORDINATE ALL DETAILS.
4.WHERE DISCREPANCIES OCCUR BETWEEN PLANS, DETAILS, GENERAL STRUCTURAL
NOTES AND SPECIFICATIONS, THE GREATER REQUIREMENTS SHALL GOVERN.
TYPICAL DETAILS AND NOTES ARE NOT NECESSARILY INDICATED ON THE PLANS,
BUT SHALL APPLY NONE-THE-LESS. WHERE NO DETAILS ARE SHOWN,
CONSTRUCTION SHALL CONFORM TO SIMILAR WORK ON THE PROJECT. DETAILS
MAY SHOW ONLY ONE SIDE OF CONNECTION OR MAY OMIT INFORMATION FOR
CLARITY.
5.ESTABLISH AND VERIFY ALL OPENINGS AND INSERTS FOR ARCHITECTURAL,
MECHANICAL, PLUMBING AND ELECTRICAL WITH APPROPRIATE TRADES, DRAWINGS
AND SUBCONTRACTORS PRIOR TO CONSTRUCTION. CONTRACTOR SHALL BE
RESPONSIBLE FOR VERIFICATION OF ALL DIMENSIONS WITH ARCHITECTURAL
DRAWINGS PRIOR TO START OF CONSTRUCTION. RESOLVE ANY DISCREPANCY WITH
THE ARCHITECT AND STRUCTURAL ENGINEER.
6.ANY INSPECTIONS, SPECIAL (IBC CHAPTER 17) OR OTHERWISE THAT ARE REQUIRED
BY THE BUILDING CODES, LOCAL BUILDING DEPARTMENTS, OR BY THESE PLANS
SHALL BE DONE BY AN INDEPENDENT INSPECTION COMPANY OR THE BUILDING
DEPARTMENT, SITE VISITS BY THE STRUCTURAL ENGINEER DO NOT CONSTITUTE AN
OFFICIAL INSPECTION, UNLESS SPECIFICALLY CONTRACTED FOR.
1.BUILDING CODE: 2018 EDITION OF THE IBC WITH CITY/COUNTY AMENDMENTS.
RISK CATEGORY = II
4. SEISMIC DESIGN PARAMETERS:
ANALYSIS PROCEDURE EQUIVALENT LATERAL FORCE
PROCEDURE
IMPORTANCE FACTOR Ie = 1.00
SITE CLASS D
SEISMIC DESIGN CATEGORY D
MAPPED SPECTRAL RESPONSE
ACCELERATIONS S1 = 0.143, SS = 0.371
DESIGN SPECTRAL RESPONSE
ACCELERATIONS
PERCENT SNOW INCLUDED WITH
SEISMIC LOADS 20
VERTICAL SHEAR TRANSFER ELEMENTS:
PLYWOOD SHEARWALL(S)R = 6.5, CS = 0.057
5. WIND DESIGN PARAMETERS (STRENGTH):
ULTIMATE WIND SPEED 115 MPH (3 SECOND GUST)
WIND EXPOSURE C
IMPORTANCE FACTOR Iw = 1.00
INTERNAL PRESSURE COEFFICIENT -0.18
COMPONENT AND CLADDING PRESSURE 30.2 PSF
NET UPLIFT ON ROOF 19.9 PSF
2. VERTICAL LOADS:
ROOF ROOF = 30 PSF
GROUND = 40 PSF 15 PSF
FLOOR 40 PSF 20 PSF
3. DEFLECTION LIMITS:
ROOF TRUSSES/JOISTS L/360 L/240
FLOOR TRUSSES/JOISTS L/720 L/240
BEAMS L/360 L/240
1.IN LIEU OF A GEOTECHNICAL REPORT: THE FOUNDATION HAS BEEN DESIGNED
ACCORDING TO THE RECOMMENDATIONS OF CHAPTER 18 OF THE IBC.
2.THE SOIL DESIGN VALUES LISTED BELOW HAVE BEEN APPROVED BY THE
CITY/COUNTY BUILDING DEPARTMENT, CONTINGENT THAT THE SOIL ON THE SITE
PREDOMINATELY CONSISTS OF SAND AND/OR GRAVEL.
SPECIFIC SOIL CLASSIFICATIONS SHOULD BE ONE OF THE FOLLOWING: SANDY
GRAVEL OR GRAVEL(GW OR GP), SAND(SW AND SP), SILTY SAND(SM), CLAYEY
SAND(SC), SILTY GRAVEL(GM), OR CLAYEY GRAVEL(GC). THESE SOIL
CLASSIFICATIONS CAN BE FOUND IN TABLE 1806.2 OF CHAPTER 18 OF THE IBC.
VERIFICATION OF SOIL CLASSIFICATION IS THE RESPONSIBILITY OF THE
CONTRACTOR.
3.A ONE-THIRD INCREASE IN BEARING PRESSURES IS ALLOWED WITH SEISMIC OR
WIND LOAD COMBINATIONS. LATERAL BEARING AND LATERAL SLIDING RESISTANCE
MAY BE COMBINED.
4.ALL FOUNDATIONS SHALL BEAR ON COMPACTED ENGINEERED FILL OR COMPETENT
NATIVE SOIL SUBBASE COMPACTED TO 95% DRY DENSITY (STANDARD PROCTOR).
GRADE IS DEFINED AS LOWEST ADJACENT GRADE WITHIN 5 FEET OF THE BUILDING
FOR PERIMETER FOOTINGS. WHERE EXTERIOR PAVING OR CONCRETE IS DIRECTLY
ADJACENT TO BUILDING, GRADE IS DEFINED AS TOP OF EXTERIOR PAVING AT LEAST
5 FEET FROM BUILDING. CONCRETE FOOTING EXCAVATIONS SHALL BE CLEAN AND
FREE OF LOOSE DEBRIS OR UN-COMPACTED MATERIAL AT TIME OF CONCRETE
PLACEMENT.
5.CONCRETE SLABS ON GRADE SHALL BE SUPPORTED ON A 4 INCH (MIN) LAYER OF
FREE-DRAINING GRANULAR MAT (DRAINAGE FILL COURSE). THE MAT SHOULD
CONSIST OF A WELL GRADED SAND AND GRAVEL MIXTURE WITH MAXIMUM 3/4-INCH
CRUSHED AGGREGATE. THE GRANULAR MAT SHOULD BE COMPACTED TO NO LESS
THAN 95% OF THE MAXIMUM DRY DENSITY AS DETERMINED BY ASTM D1557.
6.BACKFILL AGAINST RESTRAINED WALLS SHALL NOT BE PLACED UNTIL AFTER THE
WALLS ARE SUPPORTED BY THE COMPLETION OF INTERIOR FLOOR SYSTEMS AND
CONCRETE OR GROUT STRENGTH HAS REACHED THE 28 DAY STRENGTH LISTED
BELOW.
THE SOIL DESIGN VALUES FOR THE FOUNDATION ARE:
ALLOWABLE BEARING PRESSURE 1500 PSF
ALLOWABLE LATERAL BEARING PRESSURE 150 PSF/FT
ALLOWABLE LATERAL SLIDING COEFFICIENT 0.25
LATERAL BACKFILL PRESSURE (UNRESTRAINED) 45 PSF/FT
LATERAL BACKFILL PRESSURE (RESTRAINED) 60 PSF/FT
FOUNDATION BEARING DEPTH
30" BELOW FINISHED GRADE
2.ALL NORMAL WEIGHT CONCRETE SHALL BE REGULAR WEIGHT OF 150 POUNDS PER
CUBIC FOOT USING HARD ROCK AGGREGATES. AGGREGATE USED IN CONCRETE
SHALL CONFORM TO ASTM C33. .
3.LAP SPLICES FOR BEAMS AND FLOOR SLABS SLABS SHALL BE ACCORDING TO
CHAPTER 12 OF ACI 318 OR LAP SCHEDULE ON THESE DRAWINGS.
STAGGER SPLICES A MINIMUM OF ONE LAP LENGTH. NO TACK WELDING OF
REINFORCING BARS ALLOWED WITHOUT PRIOR REVIEW OF PROCEDURE WITH THE
STRUCTURAL ENGINEER. LATEST ACI CODE AND DETAILING MANUAL APPLY.
PROVIDE BENT CORNER BARS TO MATCH AND LAP WITH HORIZONTAL BARS AT ALL
CORNERS AND INTERSECTIONS PER TYPICAL DETAILS. VERTICAL WALL BARS SHALL
BE SPLICED AT OR NEAR FLOOR LINES.
4.ALL DIMENSIONS SHOWING THE LOCATION OF REINFORCING STEEL NOT NOTED AS
"CLEAR" OR "CLR" ARE TO CENTER OF STEEL. MINIMUM COVER FOR
NON-PRESTRESSED CONCRETE REINFORCING SHALL BE AS FOLLOWS:
5.MAXIMUM SLUMP FOR ALL CONCRETE SHALL BE 6". PORTLAND CEMENT SHALL
CONFORM TO ASTM C150. TYPE V CEMENT SHALL BE USED FOR CONCRETE IN
CONTACT WITH ALKALINE SOIL, AND TYPE II ELSEWHERE.
6. NO MORE THAN 90 MINUTES SHALL ELAPSE BETWEEN CONCRETE BATCHING AND
CONCRETE PLACEMENT UNLESS APPROVED BY THE TESTING AGENCY.
7.CONCRETE PLACEMENT AND QUALITY SHALL BE PER RECOMMENDATIONS IN ACI
614, ACI 301 AND ACI 318. MECHANICALLY VIBRATE ALL CONCRETE WHEN PLACED,
EXCEPT THAT SLABS ON GRADE NEED BE VIBRATED ONLY AROUND AND UNDER
FLOOR DUCTS, ETC. CAST CLOSURE POUR, WHERE SHOWN ON PLANS AROUND
COLUMNS AFTER COLUMN DEAD LOAD IS APPLIED. REMOVE ALL DEBRIS FROM
FORMS BEFORE PLACING CONCRETE.
ALL ITEMS TO BE CAST IN CONCRETE SUCH AS REINFORCING, DOWELS, BOLTS,
ANCHORS, PIPES, SLEEVES, ETC., SHALL BE SECURELY POSITIONED IN THE FORMS
BEFORE PLACING THE CONCRETE.
8.ALL CONCRETE SLABS ON GRADE SHALL BE DIVIDED INTO AREAS BY CONTROL
JOINTS (KEYED OR SAW CUT) SUCH THAT ONE SLAB AREA DOES NOT EXCEED A
MAXIMUM LENGTH OF 24 TIMES THE SLAB THICKNESS IN BOTH DIRECTIONS
(EXAMPLE: 4" SLAB = 8'-0" LENGTH). SQUARE LAYOUTS ARE PREFERRED, BUT THE
SLAB GEOMETRY MAY DICTATE OTHERWISE. THE RATIO OF THE LONG TO SHORT
DISTANCE SHALL NOT EXCEED 1.3. IT IS RECOMMENDED THAT SAW CUTS BE MADE
WITHIN 16 HOURS OF CONCRETE BATCHING.
KEYED CONTROL JOINTS NEED ONLY OCCUR AT EXPOSED EDGES DURING
POURING, ALL OTHER JOINTS MAY BE SAW CUT.
9.HORIZONTAL PIPES AND ELECTRICAL CONDUITS SHALL NOT BE EMBEDDED IN
STRUCTURAL CONCRETE AND SLABS ON GRADE EXCEPT WHERE SPECIFICALLY
APPROVED OR NOTED BY THE STRUCTURAL ENGINEER. PIPES AND CONDUITS
SHALL NOT IMPAIR THE STRENGTH OF THE WORK.
10.FLY ASH MAY BE USED ONLY IF PERMITTED BY ARCHITECTURAL SPECIFICATIONS
AND SHALL BE LIMITED TO 18 PERCENT OF CEMENTITIOUS MATERIALS AND SHALL
HAVE A REPLACEMENT FACTOR OF 1.2 RELATIVE TO CEMENT REPLACED. NO FLY
ASH ADDITIVES SHALL BE USED IN FLATWORK OR ARCHITECTURALLY EXPOSED
CONCRETE.
11. COLD/HOT WEATHER CONCRETE CONSTRUCTION: PROTECT CONCRETE FROM
DAMAGE OR REDUCED STRENGTH IN COMPLIANCE WITH ACI 305 AND 306.
12.CONCRETE MIXES SHALL BE DESIGNED BY A CERTIFIED LABORATORY AND
APPROVED BY THE STRUCTURAL ENGINEER.
13.LIMIT ALKALI-SILICA REACTION (ASR) TO 0.1% EXPANSION AT 28 DAYS IN CONCRETE
MIX AT ALL EXTERIOR CONCRETE AND INTERIOR CONCRETE EXPOSED TO
MOISTURE.
CAST AGAINST EARTH (FOOTINGS)3"± 3/8"
SLABS ON GRADE 1 1/2"
EXPOSED TO EARTH OR WEATHER - #5 AND SMALLER
EXPOSED TO EARTH OR WEATHER - #6 AND LARGER 2"
NOT EXPOSED TO WEATHER OR IN CONTACT WITH THE
GROUND ROOF SLAB 1"
STRUCTURAL SLABS AND WALLS
BEAMS AND COLUMNS (PRIMARY) REINFORCEMENT,
TIES, STIRRUPS AND SPIRALS
1. MINIMUM 28 DAY CONCRETE STRENGTH SHALL BE AS FOLLOWS:
FOOTINGS 3500 PSI 0.50 5.5% ± 1%
FOUNDATION WALLS 4500 PSI 0.45 5.5% ± 1%
INTERIOR CONCRETE
SLABS ON GRADE 3500 PSI 0.45 N/A
BEAMS, COLUMNS,
ELEVATED SLABS, WALLS 4500 PSI 0.45 5.5% ± 1%
1.GENERAL: DO NOT NOTCH OR DRILL JOISTS, BEAMS, OR LOAD BEARING STUDS
WITHOUT PRIOR APPROVAL OF THE STRUCTURAL ENGINEER THROUGH THE
ARCHITECT. DOUBLE UP JOISTS AND BLOCKING UNDER PARTITIONS. PROVIDE 2"
(NOMINAL) SOLID BLOCKING AT SUPPORTS OF ALL JOISTS. UNLESS NOTED
OTHERWISE ON PLANS/DETAILS PROVIDE 2x SOLID BLOCKING AT MID-HEIGHT OF
BEARING STUD WALLS. ALL NAILING NOT NOTED SHALL BE ACCORDING TO IBC
TABLE 2304.10.1. JOIST HANGERS AND OTHER MISC. FRAMING ANCHORS SHALL BE
SIMPSON STRONG-TIE COMPANY, INC. OR OTHER MANUFACTURER WITH CURRENT
ICC-ES APPROVAL.
2.SAWN LUMBER: FRAMING LUMBER SHALL COMPLY WITH THE LATEST EDITION OF
THE GRADING RULES OF THE WESTERN WOOD PRODUCTS ASSOCIATION (WWPA) OR
THE WEST COAST LUMBER INSPECTION BUREAU (WCLIB). ALL SAWN LUMBER SHALL
BE STAMPED WITH THE GRADE MARK OF AN APPROVED LUMBER GRADING AGENCY.
SAWN LUMBER SHALL HAVE THE FOLLOWING MINIMUM GRADE UNLESS NOTED
OTHERWISE IN SCHEDULES:
2x4 STUDS DOUGLAS-FIR NO. 2, MINIMUM (U.N.O.)
2x6 STUDS DOUGLAS-FIR NO. 2, MINIMUM (U.N.O.)
JOISTS, TOP PLATES AND ALL OTHER
SAWN LUMBER DOUGLAS-FIR NO. 2, MINIMUM (U.N.O.)
BEAMS AND POSTS DOUGLAS-FIR NO. 2, MINIMUM (U.N.O.)
LOCATION:NOMINAL
THICKNESS:
SPAN
INDEX
RATING:
EDGE
ATTACHMENT:
FIELD
ATTACHMENT:
WALL 8d AT 6" O.C. 8d AT 12" O.C.
ROOF 8d AT 6" O.C. 8d AT 12" O.C.
ROOF 8d AT 6" O.C. 8d AT 12" O.C.
ROOF 10d AT 6" O.C.10d AT 12" O.C.
ROOF 10d AT 6" O.C. 10d AT 12" O.C.
ROOF 10d AT 6" O.C. 10d AT 12" O.C.
FLOOR 10d AT 6" O.C. OR
#8 SCREWS AT 6" O.C.
10d AT 6" O.C. OR
#8 SCREWS AT 12" O.C.
FLOOR 10d AT 6" O.C. OR
#8 SCREWS AT 6" O.C.
10d AT 6" O.C. OR
#8 SCREWS AT 12" O.C.
FLOOR 10d AT 6" O.C. OR
#8 SCREWS AT 6" O.C.
10d AT 6" O.C. OR
#8 SCREWS AT 12" O.C.
3.PLYWOOD: ALL PLYWOOD SHALL BE C-D OR C-C SHEATHING CONFORMING TO
STANDARD PS 1-95. LAY UP PLYWOOD WITH FACE GRAIN IN PERPENDICULAR TO
SUPPORTS (ON ROOFS WHERE PLYWOOD IS LAID UP WITH FACE GRAIN PARALLEL
TO SUPPORTS, USE A MINIMUM OF 5-PLY PLYWOOD, STAGGER JOINTS). ALL NAILING,
COMMON NAILS. BLOCKING AT PANEL EDGES WHERE INDICATED ON PLANS. ALL
PLYWOOD SHALL BE OF THE FOLLOWING NOMINAL THICKNESS, SPAN/INDEX RATING
AND SHALL BE NAILED AS FOLLOWS UNLESS NOTED OTHERWISE ON THE PLANS:
SCREWS AT FLOOR SHEATHING SHALL BE #8 SCREWS AND SHALL PENETRATE AT
LEAST 1 1/2" INTO THE SUPPORTING MEMBER. ALL FLOOR SHEATHING SHALL BE
GLUED TO SUPPORTING MEMBERS WITH AN APA AFG-01 QUALIFIED ADHESIVE.
PLYWOOD ALTERNATE: AMERICAN PLYWOOD ASSOCIATION PERFORMANCE RATED
SHEATHING MAY BE USED AS AN ALTERNATE TO PLYWOOD WITH PRIOR APPROVAL
OF OWNER, ARCHITECT AND ROOFER. IT MAY NOT BEUSED ON ROOFS WHERE BUILT
UP ROOF SYSTEM IS TO BE GUARANTEED BY ROOFER. RATED SHEATHING SHALL
COMPLY WITH CURRENT ICC-ES REPORTS AND SHALL HAVE A SPAN RATING
EQUIVALENT TO OR BETTER THAN THE PLYWOOD IT REPLACES. ATTACHMENT AND
THICKNESS (WITHIN 1/32") SHALL BE THE SAME AS THE PLYWOOD IT REPLACES.
INSTALL PER MANUFACTURER'S RECOMMENDATIONS.
4.NOMINAL 2x AND 3x DECKING. TONGUE AND GROOVE TYPE. MINIMUM Fb = 1,600 PSI,
MINIMUM E = 1,300,000 PSI. INSTALL WITH TONGUES UP SLOPE ON PITCHED ROOFS,
AND OUTWARD IN THE DIRECTION OF LAYING ON FLAT ROOFS. NAIL EACH PLANK
WITH 16d TOENAIL (THRU THE TONGUE) AND 16d FACE NAIL AT EACH SUPPORT.
DECK SHALL BE INSTALLED AS SIMPLE SPAN WITH ALL PLANKS BEARING ON TWO
SUPPORTS. FOR REFERENCE AND/OR ADDITIONAL INFORMATION SEE AITC 117-2010.
5.GLUED-LAMINATED BEAMS (GLB): GLUED-LAMINATED BEAMS SHALL BE DOUGLAS FIR
COMBINATION AT 24F-V4 AT SIMPLE SPAN BEAMS AND 24F-V8 AT MULTI-SPAN AND
CANTILEVERED BEAMS WITH THE FOLLOWING MINIMUM PROPERTIES: FB = 2,400 PSI,
FV = 190 PSI, FC (PERPENDICULAR) = 650 PSI, E =1,800 KSI. ALL BEAMS SHALL BE
FABRICATED USING WATERPROOF GLUE. FABRICATION AND HANDLING PER LATEST
AITC AND WCLA STANDARDS. BEAMS TO BEAR GRADE STAMP AND AITC STAMP AND
CERTIFICATE. CAMBER AS SHOWN ON DRAWINGS. STANDARD CAMBER IS BASED ON
A RADIUS OF CURVATURE OF 2000 FEET.
6.GLUED-LAMINATED COLUMNS: GLUED-LAMINATED COLUMNS SHALL BE DOUGLAS FIR
COMBINATION 3 WITH THE FOLLOWING MINIMUM PROPERTIES: FBY = 2,100 PSI, FBX =
2000 PSI, FVY = 230 PSI, FVX = 265 PSI, FC (PERPENDICULAR) = 650 PSI, E =1,900 KSI.
ALL COLUMNS SHALL BE FABRICATED USING WATERPROOF GLUE. FABRICATION AND
HANDLING PER LATEST AITC AND WCLA STANDARDS. COLUMNS TO BEAR GRADE
STAMP AND AITC STAMP AND CERTIFICATE.
7. LAMINATED VENEER LUMBER (LVL): DESIGN, FABRICATION AND ERECTION IN
ACCORDANCE WITH THE LATEST ICC-ES REPORT. MINIMUM PROPERTIES FOR LVLs
SHALL BE: FB = 2,600 PSI, FV = 285 PSI, E = 2,000 KSI.
8.PARALLEL STRAND LUMBER (PSL): DESIGN, FABRICATION AND ERECTION IN
ACCORDANCE WITH THE LATEST ICC-ES REPORT. MINIMUM PROPERTIES FOR PSLs
SHALL BE: FB = 2,900 PSI, FV = 290 PSI, E = 2,000 KSI.
9.LAMINATED STRAND LUMBER (LSL): DESIGN, FABRICATION AND ERECTION IN
ACCORDANCE WITH THE LATEST ICC-ES REPORT. MINIMUM PROPERTIES FOR LSLs
SHALL BE: FB = 2,325 PSI, FV = 310 PSI, E = 1,550 KSI.
10.SILL PLATES RESTING ON CONCRETE OR MASONRY SHALL BE OF TREATED FIR.
SHEAR WALLS AND EXTERIOR WALL SILLS AT CONCRETE SLAB SHALL HAVE A
MINIMUM OF (2) ANCHOR BOLTS PER PIECE. PROVIDE ANCHOR BOLT AT 9" MAXIMUM,
4" MINIMUM FROM THE END OF EACH PIECE AT SPLICE OR END OF WALL. MAXIMUM
ANCHOR BOLT SPACING SHALL BE 72" ON CENTER UNLESS NOTED OTHERWISE ON
PLANS OR DETAILS. ALL ANCHOR BOLTS (OTHER THAN BOLTS FOR HOLDOWNS)
SHALL EMBED 7" INTO CONCRETE. ANCHOR BOLTS FOR HOLDOWNS SHALL NOT BE
CONSIDERED AS PART OF REQUIRED ANCHOR BOLTS ON SHEAR WALLS. ALL
EXTERIOR WALLS SHALL BE SECURED WITH MINIMUM ANCHOR BOLTS. INTERIOR
WALLS MAY BE SECURED TO CONCRETE WITH EITHER ANCHOR BOLTS OR POWER
DRIVEN SHOT PINS UNLESS NOTED OTHERWISE ON PLANS.
11. BOLTING: ALL BOLTS IN WOOD CONNECTIONS SHALL CONFORM TO ASTM A307.
BOLTS SHALL BE INSTALLED IN HOLES BORED WITH A BIT 1/16" LARGER THAN THE Ø
(DIAMETER) OF THE BOLT. BOLTS AND NUTS SEATING ON WOOD SHALL HAVE CUT
STEEL WASHERS UNDER HEADS AND NUTS. NICK THREADS TO PREVENT
LOOSENING.
12.
PREFABRICATED WOOD ROOF TRUSSES
SD1 = 0.221, SDS = 0.372
GENERAL STRUCTURAL NOTES
(APPLY UNLESS NOTED OTHERWISE ON PLANS/DETAILS)
± 1/4"
1 1/2" ± 3/8"
± 3/8"
1/8"
3/4"1/8"
1 1/2" 3/8"
PREFABRICATED WOOD TRUSSES: PREFABRICATED WOOD TRUSSES SHALL BE
DESIGNED TO SUPPORT SELF WEIGHT PLUS LIVE LOAD AND SUPERIMPOSED DEAD
LOADS. WHERE UNINHABITABLE ATTIC SPACE CAN BE USED FOR STORAGE, A 20
PSF LIVE LOAD ON THE BOTTOM CHORD SHALL BE INCLUDED IN THE ANALYSIS.
BRIDGING SIZE AND SPACING BY TRUSS MANUFACTURER UNLESS NOTED
OTHERWISE. CONTRACTOR SHALL SUBMIT SHOP DRAWINGS WITH DESIGN
CALCULATIONS SEALED BY A REGISTERED ENGINEER FOR REVIEW PRIOR TO
MANUFACTURE FOR BOTH ROOF AND FLOOR TRUSSES WHEN USED.
SHOP DRAWINGS SHALL SHOW ANY SPECIAL DETAILS REQUIRED AT BEARING
POINTS. ALL CONNECTORS SHALL HAVE CURRENT ICC-ES APPROVAL. ADDITIONAL
TRUSSES SHALL BE SUPPLIED AS REQUIRED TO SUPPORT MECHANICAL
EQUIPMENT. PER IBC SECTION 2303.4 AND TPI-1: EACH TRUSS SHALL BE LEGIBLY
BRANDED, MARKED OR OTHERWISE HAVE PERMANENTLY AFFIXED THERETO THE
IDENTITY OF THE COMPANY MANUFACTURING THE TRUSS, THE DESIGN LOADS, AND
THE TRUSS SPACING - WITHIN TWO FEET OF THE CENTER OF THE SPAN ON THE
FACE OF THE BOTTOM CHORD.
PREFABRICATED WOOD/STEEL WEB JOIST/PURLINS (TJI/TJL SERIES OR EQUAL):
DESIGN, FABRICATION AND ERECTION IN ACCORDANCE WITH THE LATEST EDITION
ICC-ES REPORT. CONNECTIONS AND BEARING MATERIAL TO BE DESIGNED AND
FURNISHED BY JOIST FABRICATOR. CONTRACTOR SHALL SUBMIT SHOP DRAWINGS
WITH DESIGN CALCULATIONS SEALED BY A REGISTERED STRUCTURAL ENGINEER
FOR REVIEW PRIOR TO MANUFACTURE. ADDITIONAL JOISTS SHALL BE SUPPLIED AS
REQUIRED TO SUPPORT MECHANICAL EQUIPMENT.
7/16" OR 1/2"
7/16" OR 1/2"
15/32" OR 1/2"
19/32" OR 5/8"
23/32" OR 3/4"
7/8"
3/4" T&G
7/8" T&G
1 1/8" T&G
24/16
24/16
32/16
40/20
48/24
60/32
48/24
60/32
60/48REINFORCING STEEL:
1.ASTM A615 GRADE 60 (FY = 60 KSI) DEFORMED BARS FOR ALL BARS #4 AND LARGER.
ASTM A615 GRADE 40 (FY = 40 KSI) DEFORMED BARS FOR ALL BARS #3 AND
SMALLER. GRADE 60 DEFORMED BARS SHALL BE USED FOR CONCRETE WALLS,
BEAMS, AND ELEVATED SLAB REINFORCING.
2.WELDING OF REINFORCING BARS SHALL BE MADE ONLY TO ASTM A706 GRADE 60
BARS AND ONLY USING E90 SERIES RODS. WELDING OF REINFORCING BARS SHALL
BE MADE ONLY AT LOCATIONS SHOWN ON PLANS OR DETAILS.
3.REINFORCING BAR SPACING GIVEN ARE MAXIMUM ON CENTERS. ALL BARS PER CRSI
SPECIFICATIONS AND HANDBOOK. DOWEL ALL VERTICAL REINFORCING TO
FOUNDATION. SECURELY TIE ALL BARS IN LOCATION BEFORE PLACING CONCRETE.
7.SHOP DRAWINGS SHALL BE SUBMITTED FOR ALL STRUCTURAL ITEMS IN ADDITION
TO ITEMS REQUIRED BY ARCHITECTURAL SPECIFICATIONS, THE CONTRACTOR
SHALL REVIEW ALL SHOP DRAWINGS PRIOR TO SUBMITTAL. ITEMS NOT IN
ACCORDANCE WITH CONTRACT DRAWINGS SHALL BE FLAGGED UPON HIS REVIEW.
VERIFY ALL DIMENSIONS WITH ARCHITECT. ANY CHANGES, SUBSTITUTIONS, OR
DEVIATIONS FROM ORIGINAL CONTRACT DRAWINGS SHALL BE CLOUDED. ANY OF
THE AFOREMENTIONED WHICH ARE NOT CLOUDED OR FLAGGED BY SUBMITTING
PARTIES, SHALL NOT BE CONSIDERED APPROVED AFTER THE STRUCTURAL
ENGINEER'S REVIEW, UNLESS NOTED ACCORDINGLY. ANY ENGINEERING PROVIDED
BY OTHERS AND SUBMITTED FOR REVIEW, SHALL BEAR THE SEAL OF A
STRUCTURAL ENGINEER REGISTERED IN THE APPROPRIATE STATE. THE SHOP
DRAWINGS DO NOT REPLACE THE ORIGINAL CONTRACT DRAWINGS. ITEMS OMITTED
OR SHOWN INCORRECTLY AND ARE NOT FLAGGED BY THE STRUCTURAL ENGINEER
ARE NOT TO BE CONSIDERED CHANGES TO ORIGINAL DRAWINGS. THE ADEQUACY
OF ENGINEERING DESIGNS AND LAYOUT PERFORMED BY THE OTHERS RESTS WITH
THE DESIGNING OR SUBMITTING AUTHORITY. REVIEWING IS INTENDED ONLY AS AN
AID TO THE CONTRACTOR IN OBTAINING CORRECT SHOP DRAWINGS.
RESPONSIBILITY FOR CORRECTNESS SHALL REST WITH THE CONTRACTOR. ALLOW
(5) WORKING DAYS FOR THE STRUCTURAL ENGINEER'S REVIEW. ONE COPY OF EACH
SUBMITTAL WILL BE RETAINED FOR THE STRUCTURAL ENGINEER'S RECORDS.
3 6 "
3 5
5 0
KEYNOTES:
NOTES:
1.WOOD STUD WALL, SEE PLAN
2.CONT 2x BOTTOM PLATE, ATTACH PER
SHEARWALL SCHEDULE
3.BOUNDARY NAILING, SEE PLAN
4. FLOOR SHEATHING, SEE PLAN
5.WOOD JOIST W/ (2) 16d NAILS EACH JOIST
INTO SOLE PLATE
6. CONT RIM BOARD
7.CONT 2x PT SOLE PLATE W/ ANCHOR
BOLTS PER SHEARWALL SCHEDULE
8.CONCRETE WALL, SEE PLAN
9.CONCRETE FOOTING, SEE PLAN
10. SIDEWALK, PAVEMENT, OR FINISH GRADE
PER ARCH
11. COMPACTED SUB-GRADE BELOW
FOOTING, SEE PLAN
12. MINIMUM FOOTING DEPTH, SEE GSN
13.EDGE NAILING, SEE SHEARWALL
SCHEDULE
14.WALL SHEATHING AS OCCURS, SEE PLAN
3"
CLR
3"
CL
R
10
14
12
13
11
10
5
9
10
4
1
2 3
6
7
8
6"
MI
N
A. EXTEND WALL SHEATHING TO SOLE
PLATE, NO SPLICE IN WALL SHEATHING
BELOW BOTTOM PLATE
B.WATERPROOF ANY EXTERIOR WOOD
FRAMING WITHIN 8" OF GRADE PER ARCH
DRAWINGS
13
CONCRETE SLAB ON GRADE
CONCRETE SLAB ON GRADE W/
EACH WAY CENTERED IN SLAB THICKNESS
OVER COMPACTED FILL.
(SEE GSN)
4"4 AT 24" O.C.
WF
1
8
A
WF
1
8
A
WF
1
8
A
WF
1
8
A
WF
1
8
A
WF
1
8
A
WF
1
8
WF
1
8
WF18
F30
F30
F30
EWF18
EWF18
EWF18
EW
F
1
8
EW
F
1
8
EW
F
1
8
EW
F
1
8
27'-1 3/4"
8'
-
3
"
27
'
-
8
1
/
2
"
20
'
-
5
1
/
2
"
15
'
-
3
1
/
2
"
71
'
-
8
1
/
2
"
7'
-
7
1
/
2
"
1'
-
1
"
5'
-
4
"
13
'
-
1
0
"
10
'
-
1
1
1
/
2
"
3'
-
1
1
/
2
"
5'
-
8
"
5'
-
9
1
/
2
"
8'
-
1
1
"
27'-4 1/4"
1'-9 1/2"
1
2
3
4
5
A B C D
W1
EW1
EW1
EW1
W1
W1
EW
1
EW
F
1
8
E
W
1
EW
1
EW
1
EW
1
5
6.6.
5
5
NEW WALL ELEVATION
TO MATCH FINISHED
FLOOR WITH EXISTING
FINISHED FLOOR
1
1
A A A A
1
101
S2.0
________________________
101
S2.0
________________________
1 2 3 4 5
RE
V
.
DA
T
E
B
Y
D
E
S
C
R
I
P
T
I
O
N
Th
i
s
d
r
a
w
i
n
g
i
s
t
h
e
p
r
o
p
e
r
t
y
o
f
F
R
O
S
T
S
t
r
u
c
t
u
r
a
l
E
n
gi
n
e
e
r
i
n
g
,
I
n
c
.
Le
g
a
l
l
y
,
t
h
e
d
r
a
w
i
n
g
c
a
n
N
O
T
b
e
c
o
p
i
e
d
i
n
w
h
o
l
e
o
r
in
p
i
e
c
e
s
.
I
t
is
o
n
l
y
t
o
b
e
u
s
e
d
f
o
r
t
h
e
p
r
o
j
e
c
t
a
n
d
s
i
t
e
s
p
e
c
i
f
i
ca
l
l
y
i
d
e
n
t
i
f
i
e
d
he
r
e
o
n
a
n
d
i
s
n
o
t
t
o
b
e
u
s
e
d
o
n
a
n
y
o
t
h
e
r
p
r
o
j
e
c
t
.
Co
n
t
r
a
c
t
o
r
sh
a
l
l
c
a
r
e
f
u
l
l
y
r
e
v
i
e
w
a
l
l
d
i
m
e
n
s
i
o
n
s
,
d
e
t
a
i
l
s
,
a
n
d
c
o
n
d
i
t
i
o
n
s
a
n
d
re
p
o
r
t
a
t
o
n
c
e
a
n
y
e
r
r
o
r
,
i
n
c
o
n
s
i
s
t
e
n
c
y
o
r
o
m
i
s
s
i
o
n
d
i
s
c
o
v
e
r
e
d
be
f
o
r
e
c
o
n
s
t
r
u
c
t
i
o
n
.
Th
e
c
o
n
t
r
a
c
t
o
r
a
s
s
u
m
e
s
f
u
l
l
l
i
a
b
i
l
i
t
y
f
o
r
d
e
v
i
a
t
i
o
n
s
f
r
o
m
t
h
e
in
t
e
n
t
o
f
t
h
e
s
e
p
l
a
n
s
.
PR
O
J
E
C
T
M
A
N
A
G
E
R
:
C
A
D
O
P
E
R
A
T
O
R
:
DATE:
JO
B
N
O
.
:
ST
R
U
C
T
U
R
A
L
E
N
G
I
N
E
E
R
S
S
E
A
L
:
PR
O
J
E
C
T
:
CL
I
E
N
T
:
CURRENT REV.
S2.0
FO
U
N
D
A
T
I
O
N
P
L
A
N
Au
t
h
o
r
C
R
A
P
O
1
5
6
15
6
E
2
n
d
S
RE
X
B
U
R
G
,
I
D
83
4
4
0
CR
A
P
O
NORTH
WALL (W) SCHEDULE
TYPE MATERIAL THICKNESS VERTICAL REINFORCING HORIZONTAL REINFORCING REMARKS
EW1 CONCRETE 8" #4 AT 18" O.C. #4 AT 12" O.C. ---
W1 CONCRETE 8" #4 AT 18" O.C. #4 AT 18" O.C. ---
FOOTING SCHEDULE
MARK LENGTH WIDTH THICKNESS REINFORCING REMARKS
F30 30" 30" 10" (3) #4 EACH WAY BOTTOM ---
EWF18 CONT 18" 10" (2) #4 CONT BOTTOM STRIP FOOTING
WF18 CONT 18" 10" (2) #4 CONT BOTTOM STRIP FOOTING
WF18A CONT 18" 10" (2) #4 CONT TOP & BOTTOM STRIP FOOTING
KEYNOTES
1 DRILL AND EPOXY REBAR INTO EXISTING FOOTING W/
6" MIN INTO EXISTING FOUNDATION W/ (2) DOWELS
INTO FOOTING AND (1) INTO TOP OF WALL
2 SOLID BLOCK BETWEEN FLOOR BELOW POST ABOVE
TO POST BELOW
3 ALIGN TRUSS W/ SHEARWALL AND ATTACH W/ A35 CLIP
AT 16" O.C.
4 ATTACH EXISTING ROOF TO NEW ROOF W/ CONT 2x
LEDGER W/ (2)16d NAILS AT 6" O.C.
FOUNDATION PLAN NOTES
A. VERIFY ALL DIMENSIONS WITH ALL ARCHITECTURAL
DRAWINGS.
B. ALL SCHEDULED MARK DESIGNATIONS MAY NOT
NECESSARILY BE FOUND ON THIS PLAN. SCHEDULES
ARE TYPICAL TO THIS PROJECT.
C. THE DEPTH OF FOOTING DIMENSION INDICATED IN THE
G.S.N. IS A MINIMUM. FOUNDATION CONTRACTOR SHALL
COORDINATE WITH THE SOILS REPORT AND OTHER
TRADES TO INSURE THAT THESE MINIMUMS ARE
SUFFICIENT FOR THE WORK. SEE TYPICAL DETAILS FOR
ADDITIONAL REQUIREMENTS.
D. W1, W2, ETC. - AS SHOWN ON PLAN INDICATES
CONCRETE OR MASONRY WALLS. SEE WALL SCHEDULE
FOR ADDITIONAL INFORMATION.
E. WF18, WF24, ETC. - AS SHOWN ON PLAN INDICATES A
CONTINUOUS WALL FOOTING. SEE FOOTING SCHEDULE
FOR ADDITIONAL INFORMATION.
F. F36, F48, ETC. - AS SHOWN ON PLAN INDICATES A
CONCRETE FOOTING. SEE FOOTING SCHEDULE FOR
ADDITIONAL INFORMATION.
G. RWF36, RWF42, ETC. - AS SHOWN ON PLAN INDICATES A
CONTINUOUS RETAINING WALL FOOTING. SEE FOOTING
SCHEDULE FOR ADDITIONAL INFORMATION.
H. P1, P2, ETC. AS SHOWN ON PLAN INDICATES A WOOD
POST. SEE POST SCHEDULE FOR MORE INFORMATION.
I. PROVIDE CONTINUOUS BEARING FOR ALL POSTS AND
BUILT-UP STUDS TO THE FOUNDATION PER TYPICAL
"SOLID BLOCKING BETWEEN FLOORS" DETAIL.
J. ALL EXTERIOR WALLS SHALL BE CONSTRUCTED WITH
TYPE "5" SHEARWALLS, UNO.
K. FOR SIDEWALK AND LANDING LOCATIONS, SEE
ARCHITECTURAL DRAWINGS.
SCALE: 1/4" = 1'-0"
FOUNDATION
7. BLOCK ALL PANEL EDGES. EDGE NAIL SHEATHING AT BLOCKED EDGES.
6. PROVIDE FULL HEIGHT DOUBLE STUDS AT ENDS OF SHEARWALLS UNLESS NOTED OTHERWISE ON PLANS OR DETAILS.
5. PROVIDE CONTINUOUS DOUBLE 2x TOP PLATE AT ALL SHEARWALLS AND EXTERIOR WALL. UNLESS NOTED OTHERWISE
(U.N.O.), LAP SPLICE TOP PLATE A MINIMUM 4'-0" WITH 16d NAILS STAGGERED AT 2" ON CENTER (O.C.) ((24) 16d NAILS TOTAL
BETWEEN SPLICE JOINTS.)
4. A MINIMUM OF (2) ANCHOR BOLTS SHALL BE USED ON EACH BASE PLATE PIECE. PROVIDE (1) ANCHOR BOLT MINIMUM WITHIN
9" OF EACH END PIECE.
3. ANCHOR BOLTS TO FOUNDATION SHALL BE 10" LONG AND SHALL BE EMBED 7" INTO CONCRETE. EXPANSION BOLTS OR SHOT
PINS MAY BE USED AT INTERIOR WALLS (AWAY FROM EDGE OF SLAB OR SLAB STEP-DOWN) PER SUPPLEMENTAL INSTRUCTIONS.
2. FRAMING MEMBER SUPPORTING MATERIAL SHALL BE SPACED AT 16" ON CENTER (O.C.) MAXIMUM.
1. SHEARWALL TYPES LISTED BELOW ARE NOT JOB SPECIFIC. SOME TYPES MAY NOT BE USED ON THE PLANS.
NOTES:
SHEARWALL TYPE SCHEDULE
MARK SHEATHING MATERIAL EDGE NAILING FIELD NAILING BOTTOM PLATE ATTACHMENT
5 7/16" APA RATED
SHEATHING (BLOCKED)
ONE SIDE OF WALL
8d COMMON
AT 6" O.C.
8d COMMON
AT 12" O.C.
CONCRETE: 1/2" Ø A.B. W/ 1/4"x3"x3" PLATE WASHERS AT 36" O.C.
CONCRETE: 5/8" Ø A.B. W/ 1/4"x3"x3" PLATE WASHERS AT 48" O.C.
WOOD: 16d STAGGERED AT 6" O.C.
6. 7/16" APA RATED
SHEATHING (BLOCKED)
ONE SIDE OF WALL
8d COMMON
AT 4" O.C.
8d COMMON
AT 12" O.C.
CONCRETE: 1/2" Ø A.B. W/ 1/4"x3"x3" PLATE WASHERS AT 24" O.C.
CONCRETE: 5/8" Ø A.B. W/ 1/4"x3"x3" PLATE WASHERS AT 32" O.C.
WOOD: 16d STAGGERED AT 4" O.C.
HOLDOWN SCHEDULE
MARK HOLDOWN
SHEARWALL
END POST UNO
ON PLAN ALTERNATE HOLDOWN
ANCHOR
BOLT DIA.
A SIMPSON STHD10RJ (2) 2x STUDS HTT4 W/ (18) 0.148x1.5"
NAILS
5/8" (FOR
ALTERNATE)
SCALE: NTS101WOOD JOIST AT FOUNDATION
1
2
3
4
5
A B C D
B2
B2
B2
P1
1
2
3
4
5
A B C D
EW
J
1
WJ1WJ
1
5
6.6.
5
5
EX
I
S
T
I
N
G
B
E
A
M
A A A A
B2
P1
P1
P1
P2
P1
P1
P1
2
2
TYP
TYP
TYPICAL FLOOR SHEATHING
APA RATED ROOF SHEATHING W/
NAILS AT O.C. AT PANEL EDGES AND
BOUNDARY AND AT O.C. IN THE FIELD.
3/4"10d
6"
12"
P2
1 2 3 4 5
RE
V
.
DA
T
E
B
Y
D
E
S
C
R
I
P
T
I
O
N
Th
i
s
d
r
a
w
i
n
g
i
s
t
h
e
p
r
o
p
e
r
t
y
o
f
F
R
O
S
T
S
t
r
u
c
t
u
r
a
l
E
n
gi
n
e
e
r
i
n
g
,
I
n
c
.
Le
g
a
l
l
y
,
t
h
e
d
r
a
w
i
n
g
c
a
n
N
O
T
b
e
c
o
p
i
e
d
i
n
w
h
o
l
e
o
r
in
p
i
e
c
e
s
.
I
t
is
o
n
l
y
t
o
b
e
u
s
e
d
f
o
r
t
h
e
p
r
o
j
e
c
t
a
n
d
s
i
t
e
s
p
e
c
i
f
i
ca
l
l
y
i
d
e
n
t
i
f
i
e
d
he
r
e
o
n
a
n
d
i
s
n
o
t
t
o
b
e
u
s
e
d
o
n
a
n
y
o
t
h
e
r
p
r
o
j
e
c
t
.
Co
n
t
r
a
c
t
o
r
sh
a
l
l
c
a
r
e
f
u
l
l
y
r
e
v
i
e
w
a
l
l
d
i
m
e
n
s
i
o
n
s
,
d
e
t
a
i
l
s
,
a
n
d
c
o
n
d
i
t
i
o
n
s
a
n
d
re
p
o
r
t
a
t
o
n
c
e
a
n
y
e
r
r
o
r
,
i
n
c
o
n
s
i
s
t
e
n
c
y
o
r
o
m
i
s
s
i
o
n
d
i
s
c
o
v
e
r
e
d
be
f
o
r
e
c
o
n
s
t
r
u
c
t
i
o
n
.
Th
e
c
o
n
t
r
a
c
t
o
r
a
s
s
u
m
e
s
f
u
l
l
l
i
a
b
i
l
i
t
y
f
o
r
d
e
v
i
a
t
i
o
n
s
f
r
o
m
t
h
e
in
t
e
n
t
o
f
t
h
e
s
e
p
l
a
n
s
.
PR
O
J
E
C
T
M
A
N
A
G
E
R
:
C
A
D
O
P
E
R
A
T
O
R
:
DATE:
JO
B
N
O
.
:
ST
R
U
C
T
U
R
A
L
E
N
G
I
N
E
E
R
S
S
E
A
L
:
PR
O
J
E
C
T
:
CL
I
E
N
T
:
CURRENT REV.
S2.1
FI
R
S
T
F
L
O
O
R
F
R
A
M
I
N
G
P
L
A
N
Au
t
h
o
r
C
R
A
P
O
1
5
6
15
6
E
2
n
d
S
RE
X
B
U
R
G
,
I
D
83
4
4
0
CR
A
P
O
NORTH
FLOOR FRAMING PLAN NOTES
A. VERIFY ALL DIMENSIONS WITH ALL ARCHITECTURAL
DRAWINGS.
B. ALL SCHEDULED MARK DESIGNATIONS MAY NOT
NECESSARILY BE FOUND ON THIS PLAN. SCHEDULES
ARE TYPICAL TO THIS PROJECT.
C. IF DOUBLE TOP PLATE IS NOTCHED, STEPPED OR
BROKEN, PROVIDE A SIMPSON MSTC40 STRAP AT
DISCONTINUITY.
D. TYPICAL BEARING WALL FRAMING SHALL BE 2x6 STUDS
AT 16" O.C. UNO.
E. PROVIDE TRIMMER STUDS (TS) AND KING STUDS (KS) AT
OPENINGS AS FOLLOWS, U.N.O.: OPENINGS 6'-0" OR
LESS, (1) TS & (1) KS, OPENINGS 6'-1" TO 9'-0", (1) TS & (2)
KS, 9'-1" TO 12-0", (2) TS & (3) KS. FOR ATTACHMENT, SEE
"TYPICAL HEADER CONNECTION" DETAIL.
F. B1, B2, ETC. - AS SHOWN ON PLAN INDICATES A BEAM OR
HEADER. SEE BEAM SCHEDULE FOR ADDITIONAL
INFORMATION.
G. WJ1, WJ2, ETC. - AS SHOWN ON PLAN INDICATES A WOOD
JOIST. SEE WOOD JOIST SCHEDULE FOR ADDITIONAL
INFORMATION.
H. P1, P2, ETC. AS SHOWN ON PLAN INDICATES A WOOD
POST. SEE POST SCHEDULE FOR MORE INFORMATION.
I. PROVIDE CONTINUOUS BEARING FOR ALL POSTS AND
BUILT-UP STUDS TO THE FOUNDATION PER TYPICAL
"SOLID BLOCKING BETWEEN FLOORS" DETAIL.
J. FOR CLARITY, DETAILS MAY SHOW ONLY ONE SIDE OF
FRAMING CONDITION.
K. ALL EXTERIOR WALLS SHALL BE CONSTRUCTED WITH
TYPE "5" SHEARWALLS, UNO.
7. BLOCK ALL PANEL EDGES. EDGE NAIL SHEATHING AT BLOCKED EDGES.
6. PROVIDE FULL HEIGHT DOUBLE STUDS AT ENDS OF SHEARWALLS UNLESS NOTED OTHERWISE ON PLANS OR DETAILS.
5. PROVIDE CONTINUOUS DOUBLE 2x TOP PLATE AT ALL SHEARWALLS AND EXTERIOR WALL. UNLESS NOTED OTHERWISE
(U.N.O.), LAP SPLICE TOP PLATE A MINIMUM 4'-0" WITH 16d NAILS STAGGERED AT 2" ON CENTER (O.C.) ((24) 16d NAILS TOTAL
BETWEEN SPLICE JOINTS.)
4. A MINIMUM OF (2) ANCHOR BOLTS SHALL BE USED ON EACH BASE PLATE PIECE. PROVIDE (1) ANCHOR BOLT MINIMUM WITHIN
9" OF EACH END PIECE.
3. ANCHOR BOLTS TO FOUNDATION SHALL BE 10" LONG AND SHALL BE EMBED 7" INTO CONCRETE. EXPANSION BOLTS OR SHOT
PINS MAY BE USED AT INTERIOR WALLS (AWAY FROM EDGE OF SLAB OR SLAB STEP-DOWN) PER SUPPLEMENTAL INSTRUCTIONS.
2. FRAMING MEMBER SUPPORTING MATERIAL SHALL BE SPACED AT 16" ON CENTER (O.C.) MAXIMUM.
1. SHEARWALL TYPES LISTED BELOW ARE NOT JOB SPECIFIC. SOME TYPES MAY NOT BE USED ON THE PLANS.
NOTES:
SHEARWALL TYPE SCHEDULE
MARK SHEATHING MATERIAL EDGE NAILING FIELD NAILING BOTTOM PLATE ATTACHMENT
5 7/16" APA RATED
SHEATHING (BLOCKED)
ONE SIDE OF WALL
8d COMMON
AT 6" O.C.
8d COMMON
AT 12" O.C.
CONCRETE: 1/2" Ø A.B. W/ 1/4"x3"x3" PLATE WASHERS AT 36" O.C.
CONCRETE: 5/8" Ø A.B. W/ 1/4"x3"x3" PLATE WASHERS AT 48" O.C.
WOOD: 16d STAGGERED AT 6" O.C.
6. 7/16" APA RATED
SHEATHING (BLOCKED)
ONE SIDE OF WALL
8d COMMON
AT 4" O.C.
8d COMMON
AT 12" O.C.
CONCRETE: 1/2" Ø A.B. W/ 1/4"x3"x3" PLATE WASHERS AT 24" O.C.
CONCRETE: 5/8" Ø A.B. W/ 1/4"x3"x3" PLATE WASHERS AT 32" O.C.
WOOD: 16d STAGGERED AT 4" O.C.
BEAM (B) SCHEDULE
MARK SIZE
B2 (2) 2x8 OR 4x8 OR (2) 1 3/4x5 1/2 LVL
B3 (3) 1 3/4x11 7/8 LVL OR 3 1/2x11 7/8 LVL OR 5 1/8x13 1/2 GLB
POST (P) SCHEDULE
MARK SIZE SPECIES AND GRADE CONNECTION
P1 (2) 2x4 DOUG FIR NO. 2 SEE TYPICAL DETAIL
P2 (3) 2x4 DOUG FIR NO. 2 SEE TYPICAL DETAIL
P3 (2) 2x6 DOUG FIR NO. 2 SEE TYPICAL DETAIL
KEYNOTES
1 DRILL AND EPOXY REBAR INTO EXISTING FOOTING W/
6" MIN INTO EXISTING FOUNDATION W/ (2) DOWELS
INTO FOOTING AND (1) INTO TOP OF WALL
2 SOLID BLOCK BETWEEN FLOOR BELOW POST ABOVE
TO POST BELOW
3 ALIGN TRUSS W/ SHEARWALL AND ATTACH W/ A35 CLIP
AT 16" O.C.
4 ATTACH EXISTING ROOF TO NEW ROOF W/ CONT 2x
LEDGER W/ (2)16d NAILS AT 6" O.C.
SCALE: 1/4" = 1'-0"
FIRST FLOOR
WOOD JOIST (WJ) SCHEDULE
MARK WOOD JOIST
JOIST SPACING
(O.C.)
FACE MOUNT
HANGER
TOP FLANGE
HANGER
EWJ1 2x8 1'-4"
WJ1 11 7/8" TJI 110 1'-4"
KEYNOTES:
NOTES:
1. WOOD TRUSS W/ CLIP, SEE PLAN
2.CONT DBL 2x TOP PLATE W/ LAP SPLICE,
SEE TYPICAL DETAIL
3.WOOD STUD WALL, SEE PLAN
4. WALL SHEATHING AS OCCURS, SEE PLAN
5.EDGE NAILING, SEE SHEARWALL
SCHEDULE
6. FULL-HEIGHT TIMBER STRAND BLOCKING
BETWEEN EACH TRUSS, SEE TYPICAL
"ELEVATION - TYPICAL SOLID 2x
BLOCKING" DETAIL FOR VENTILATION
HOLES IN BLOCKING
7.ROOF SHEATHING, SEE PLAN
8.BOUNDARY NAILING, SEE PLAN
1
2
3
55
4
8
6
7
A.NO WALL SHEATHING SPLICE BETWEEN
BLOCKING AND TOP PLATE, IF
SHEATHING BREAKS PROVIDE A35 CLIP
AT EACH BLOCK
B.COORDINATE ROOF VENTILATION
C. FASCIA PER ARCHITECTURAL DETAILS
1
2
3
4
5
A B C D
1
2
3
4
5
A B C D
5
6.6.
5
5
P2
B3
B2
B2
B2 B2B2B2
B2
B2
NEW ROOF OVERBUILD
EX
I
S
T
I
N
G
R
O
O
F
F
R
A
M
I
N
G
NE
W
P
R
E
F
A
B
R
O
O
F
T
R
U
S
S
E
S
P1
P1
P1
P1
P2
P3 P3
6.
G
T G T
3
4
201
S2.2
________________________
201
S2.2
________________________
201
S2.2
________________________
TYPICAL ROOF SHEATHING
APA RATED ROOF SHEATHING W/
NAILS AT O.C. AT PANEL EDGES AND
BOUNDARY AND AT O.C. IN THE FIELD.
7/16"8d
6"
12"
GT
1 2 3 4 5
RE
V
.
DA
T
E
B
Y
D
E
S
C
R
I
P
T
I
O
N
Th
i
s
d
r
a
w
i
n
g
i
s
t
h
e
p
r
o
p
e
r
t
y
o
f
F
R
O
S
T
S
t
r
u
c
t
u
r
a
l
E
n
gi
n
e
e
r
i
n
g
,
I
n
c
.
Le
g
a
l
l
y
,
t
h
e
d
r
a
w
i
n
g
c
a
n
N
O
T
b
e
c
o
p
i
e
d
i
n
w
h
o
l
e
o
r
in
p
i
e
c
e
s
.
I
t
is
o
n
l
y
t
o
b
e
u
s
e
d
f
o
r
t
h
e
p
r
o
j
e
c
t
a
n
d
s
i
t
e
s
p
e
c
i
f
i
ca
l
l
y
i
d
e
n
t
i
f
i
e
d
he
r
e
o
n
a
n
d
i
s
n
o
t
t
o
b
e
u
s
e
d
o
n
a
n
y
o
t
h
e
r
p
r
o
j
e
c
t
.
Co
n
t
r
a
c
t
o
r
sh
a
l
l
c
a
r
e
f
u
l
l
y
r
e
v
i
e
w
a
l
l
d
i
m
e
n
s
i
o
n
s
,
d
e
t
a
i
l
s
,
a
n
d
c
o
n
d
i
t
i
o
n
s
a
n
d
re
p
o
r
t
a
t
o
n
c
e
a
n
y
e
r
r
o
r
,
i
n
c
o
n
s
i
s
t
e
n
c
y
o
r
o
m
i
s
s
i
o
n
d
i
s
c
o
v
e
r
e
d
be
f
o
r
e
c
o
n
s
t
r
u
c
t
i
o
n
.
Th
e
c
o
n
t
r
a
c
t
o
r
a
s
s
u
m
e
s
f
u
l
l
l
i
a
b
i
l
i
t
y
f
o
r
d
e
v
i
a
t
i
o
n
s
f
r
o
m
t
h
e
in
t
e
n
t
o
f
t
h
e
s
e
p
l
a
n
s
.
PR
O
J
E
C
T
M
A
N
A
G
E
R
:
C
A
D
O
P
E
R
A
T
O
R
:
DATE:
JO
B
N
O
.
:
ST
R
U
C
T
U
R
A
L
E
N
G
I
N
E
E
R
S
S
E
A
L
:
PR
O
J
E
C
T
:
CL
I
E
N
T
:
CURRENT REV.
S2.2
RO
O
F
F
R
A
M
I
N
G
P
L
A
N
Au
t
h
o
r
C
R
A
P
O
1
5
6
15
6
E
2
n
d
S
RE
X
B
U
R
G
,
I
D
83
4
4
0
CR
A
P
O
NORTH
POST (P) SCHEDULE
MARK SIZE SPECIES AND GRADE CONNECTION
P1 (2) 2x4 DOUG FIR NO. 2 SEE TYPICAL DETAIL
P2 (3) 2x4 DOUG FIR NO. 2 SEE TYPICAL DETAIL
P3 (2) 2x6 DOUG FIR NO. 2 SEE TYPICAL DETAIL
BEAM (B) SCHEDULE
MARK SIZE
B2 (2) 2x8 OR 4x8 OR (2) 1 3/4x5 1/2 LVL
B3 (3) 1 3/4x11 7/8 LVL OR 3 1/2x11 7/8 LVL OR 5 1/8x13 1/2 GLB
KEYNOTES
1 DRILL AND EPOXY REBAR INTO EXISTING FOOTING W/
6" MIN INTO EXISTING FOUNDATION W/ (2) DOWELS
INTO FOOTING AND (1) INTO TOP OF WALL
2 SOLID BLOCK BETWEEN FLOOR BELOW POST ABOVE
TO POST BELOW
3 ALIGN TRUSS W/ SHEARWALL AND ATTACH W/ A35 CLIP
AT 16" O.C.
4 ATTACH EXISTING ROOF TO NEW ROOF W/ CONT 2x
LEDGER W/ (2)16d NAILS AT 6" O.C.
ROOF FRAMING PLAN NOTES
A. VERIFY ALL DIMENSIONS WITH ALL ARCHITECTURAL
DRAWINGS.
B. ALL SCHEDULED MARK DESIGNATIONS MAY NOT
NECESSARILY BE FOUND ON THIS PLAN. SCHEDULES
ARE TYPICAL TO THIS PROJECT.
C. IF DOUBLE TOP PLATE IS NOTCHED, STEPPED OR
BROKEN, PROVIDE A SIMPSON MSTC40 STRAP AT
DISCONTINUITY.
D. TYPICAL BEARING WALL FRAMING SHALL BE 2x6 STUDS
AT 16" O.C. UNO. WHERE ROOF TRUSSES OR JOISTS
SPANS EXCEED 20'-0" ALIGN ADDITIONAL STUD BELOW
ROOF FRAMING MEMBER.
E. PROVIDE TRIMMER STUDS (TS) AND KING STUDS (KS) AT
OPENINGS AS FOLLOWS, U.N.O.: OPENINGS 6'-0" OR
LESS, (1) TS & (1) KS, OPENINGS 6'-1" TO 9'-0", (1) TS & (2)
KS, 9'-1" TO 12-0", (2) TS & (3) KS. FOR ATTACHMENT, SEE
"TYPICAL HEADER CONNECTION" DETAIL.
F. B1, B2, ETC. - AS SHOWN ON PLAN INDICATES A BEAM OR
HEADER. SEE BEAM SCHEDULE FOR ADDITIONAL
INFORMATION.
G. P1, P2, ETC. AS SHOWN ON PLAN INDICATES A WOOD
POST. SEE POST SCHEDULE FOR MORE INFORMATION.
H. TIE EACH ROOF TRUSS AT BEARING LOCATIONS WITH (1)
H2.5A OR (1) H1 CLIP, AND EACH GIRDER TRUSS WITH (2)
H2.5A CLIPS, UNO.
I. TIE EACH ROOF JOIST AT BEARING LOCATIONS WITH (1)
H2.5A CLIP, UNO.
J. PROVIDE BUILT-UP 2x POSTS BELOW EACH GIRDER
TRUSS, MATCH GIRDER TRUSS WIDTH, U.N.O.
K. OVERBUILD PONY WALLS (MAX 6'-0" SPACING FOR 2x6
OVERBUILD FRAMING AT 24" O.C. W/ SIMPSON LUS__
HANGER) PER "TYPICAL OVERBUILD" DETAIL.
L. CS16, CS18, ETC. - AS SHOWN AT WALL OPENINGS,
PROVIDE STRAPPING PER "TYPICAL STRAP AT OPENING"
DETAIL.
M. PROVIDE CONTINUOUS BEARING FOR ALL POSTS AND
BUILT-UP STUDS TO THE FOUNDATION PER TYPICAL
"SOLID BLOCKING BETWEEN FLOORS" DETAIL.
N. FOR CLARITY, DETAILS MAY SHOW ONLY ONE SIDE OF
FRAMING CONDITION.
O. ALL EXTERIOR WALLS SHALL BE CONSTRUCTED WITH
TYPE "5" SHEARWALLS, UNO.
7. BLOCK ALL PANEL EDGES. EDGE NAIL SHEATHING AT BLOCKED EDGES.
6. PROVIDE FULL HEIGHT DOUBLE STUDS AT ENDS OF SHEARWALLS UNLESS NOTED OTHERWISE ON PLANS OR DETAILS.
5. PROVIDE CONTINUOUS DOUBLE 2x TOP PLATE AT ALL SHEARWALLS AND EXTERIOR WALL. UNLESS NOTED OTHERWISE
(U.N.O.), LAP SPLICE TOP PLATE A MINIMUM 4'-0" WITH 16d NAILS STAGGERED AT 2" ON CENTER (O.C.) ((24) 16d NAILS TOTAL
BETWEEN SPLICE JOINTS.)
4. A MINIMUM OF (2) ANCHOR BOLTS SHALL BE USED ON EACH BASE PLATE PIECE. PROVIDE (1) ANCHOR BOLT MINIMUM WITHIN
9" OF EACH END PIECE.
3. ANCHOR BOLTS TO FOUNDATION SHALL BE 10" LONG AND SHALL BE EMBED 7" INTO CONCRETE. EXPANSION BOLTS OR SHOT
PINS MAY BE USED AT INTERIOR WALLS (AWAY FROM EDGE OF SLAB OR SLAB STEP-DOWN) PER SUPPLEMENTAL INSTRUCTIONS.
2. FRAMING MEMBER SUPPORTING MATERIAL SHALL BE SPACED AT 16" ON CENTER (O.C.) MAXIMUM.
1. SHEARWALL TYPES LISTED BELOW ARE NOT JOB SPECIFIC. SOME TYPES MAY NOT BE USED ON THE PLANS.
NOTES:
SHEARWALL TYPE SCHEDULE
MARK SHEATHING MATERIAL EDGE NAILING FIELD NAILING BOTTOM PLATE ATTACHMENT
5 7/16" APA RATED
SHEATHING (BLOCKED)
ONE SIDE OF WALL
8d COMMON
AT 6" O.C.
8d COMMON
AT 12" O.C.
CONCRETE: 1/2" Ø A.B. W/ 1/4"x3"x3" PLATE WASHERS AT 36" O.C.
CONCRETE: 5/8" Ø A.B. W/ 1/4"x3"x3" PLATE WASHERS AT 48" O.C.
WOOD: 16d STAGGERED AT 6" O.C.
6. 7/16" APA RATED
SHEATHING (BLOCKED)
ONE SIDE OF WALL
8d COMMON
AT 4" O.C.
8d COMMON
AT 12" O.C.
CONCRETE: 1/2" Ø A.B. W/ 1/4"x3"x3" PLATE WASHERS AT 24" O.C.
CONCRETE: 5/8" Ø A.B. W/ 1/4"x3"x3" PLATE WASHERS AT 32" O.C.
WOOD: 16d STAGGERED AT 4" O.C.
SCALE: 1/4" = 1'-0"
FIRST FLOOR FRAMING PLAN
SCALE: NTS201WOOD TTRUSS AT WOOD STUD WALL