HomeMy WebLinkAboutRESUBMITTAL - 22-00034 - Nitro Car WashAuthor Name Author Email Author Phone No.:
Kyle Baldwin Kyle.Baldwin@rexburg.org 208-372-2164
Alex Owens Alex.Owens@rexburg.org 208-372-2330
Cody Jones Cody.Jones@rexburg.org 208-372-2173
Don Allen Don.Allen@rexburg.org 208-372-2174
Description : Nitro Car Wash
Address : 1371 N 2nd E
Application Type :
Document Filename : 220118 Rexburg ID Nitro - Combined.pdf Array
Comment Author Contact Information:
Corrections in the following table need to be applied before a permit can be issued
Review Report
Revisions Required
Page Reference Annotation
Type
Author : Department Status Page Review Comments Applicant Response Comments
G0.2 Free text Cody Jones : Building Open 3 This sign to be installed on both doors.
G0.2 Free text Cody Jones : Building Open 3 Any concealed spaces need fire blocked/ draft stopped as per
IBC. (concealed attic areas over 3,000sq feet.)
G0.2 Free text Cody Jones : Building Open 3 Exit lighting and exit signs to comply with section 1008 and
1013.
G0.2 Free text Cody Jones : Building Open 3 Glass and glazing to meet requirements of chapter 24.
A0.1 Free text Cody Jones : Building Open 4 Minimum of one needs to be ADA van accessible. as per
section 1106.1 and 1106.5.
A0.2 Free text Cody Jones : Building Open 5 Cross slope of sidewalk to not exceed 2% slope.
A2.5 Free text Cody Jones : Building Open 20 Suspended ceiling to be installed to manufacturers
specifications.
S1.0 Free text Cody Jones : Building Open 48 Special inspector needs to be identified.
S1.0 Free text Cody Jones : Building Open 48 Grade to slope away from building 6" in first 10'.
# 22-00034
New Commercial Building
Report Date: 02.04.2022
Approval of plans does not constitute approval of variance from code
Page 1 of 2
see updated drawing sheet G0.2
see updated drawing sheet G0.2
see updated drawing sheet G0.2
see updated drawing sheet G0.2
see updated drawing sheet A0.1
see updated drawing sheet A0.2
see updated drawing sheet A2.5
see updated drawing sheet S1.0
see updated drawing sheet S1.0
Page Reference Annotation
Type
Author : Department Status Page Review Comments Applicant Response Comments
S1.0 Free text Cody Jones : Building Open 48 Will need precast wall submittals with third party inspector
results.
E-1 Free text Alex Owens : Electrical Open 61 Verify all electrical work inside "wash tunnel" is rated for wet
location.
A0.1 Free text Kyle Baldwin : P&Z Open 4 Please show required snow storage locations, and provide
landscaping plan.
Please review Central Features and Community Spaces in
Development Code (6.00.040) and include provisions to meet
this requirement.
A0.1 Callout Kyle Baldwin : P&Z Open 4 Please show public sidewalk and internal sidewalk locations
for pedestrian connectivity requirement
Report Date: 02.04.2022
Approval of plans does not constitute approval of variance from code
Page 2 of 2
Powered by TCPDF (www.tcpdf.org)
by subsequent deferred submittal
see updated drawing sheet E-1
see updated drawing sheet C.3.1
& C.3.2
see updated drawing sheet C.3.1
STAMP:
THESE DOCUMENTS HAVE BEEN PRODUCED AS AN
INSTRUMENT OF SERVICE AND ARE INTENDED SOLELY
FOR THE PURPOSE OF CONSTRUCTING, USING AND
MAINTAINING THE PROJECT. SPOTLESS WASH
SOLUTIONS USA INC, AS THE ARCHITECT OF RECORD
FOR THE PROJECT RETAINS OWNERSHIP OF THESE
DOCUMENTS.
ANY USE OF THESE DOCUMENTS OR USE OF THIS
DESIGN, IDEAS OR CONCEPTS DESCRIBED HEREIN IN
WHOLE OR PART BY ANY MEANS WHATSOEVER IS
STRICTLY PROHIBITED EXCEPT BY WRITTEN CONSENT
OF SPOTLESS WASH SOLUTIONS USA INC.
REPRODUCTION OF THIS DOCUMENT IS STRICTLY
PROHIBITED EXCEPT BY WRITTEN CONSENT OF
SPOTLESS WASH SOLUTIONS USA INC.
COPYRIGHT 2022
SPOTLESS WASH SOLUTIONS USA INC.
CHECKED:
DATE:
JOB NUMBER:
ISSUED FOR:
SHEET NUMBER:
SP
O
T
L
E
S
S
W
A
S
H
S
O
L
U
T
I
O
N
S
PO
B
O
X
5
4
5
6
TW
I
N
F
A
L
L
S
,
I
D
A
H
O
8
3
3
0
3
PH
.
(
2
0
8
)
8
4
1
-
4
5
2
4
DRAWN:
BI
N
D
I
N
G
02/15/2022
PERMIT REVIEW SET
NOT FOR CONSTRUCTION
21005
BUILDING PERMIT - NFC
A0.0
COVER SHEET
AS
NI
T
R
O
C
A
R
W
A
S
H
RE
X
B
U
R
G
,
I
D
13
7
1
N
2
N
D
E
RE
X
B
U
R
G
,
I
D
8
3
4
4
8
5/4/22
BUILDING CODES AS ADOPTED BY THE CITY OF REXBURG, ID:
-2018 IBC / IMC / IFGC / IECC / IFC -AS ADOPTED BY THE CITY OF REXBURG, ID
-2017 NEC
-2017 IDAHO PLUMBING CODE
DESIGN CRITERIA
DEVELOPMENT TEAM
OWNER :
TETON MANAGEMENT GROUP
PO BOX 217
TETONIA, ID 83452
ZACHARY HARMAN
208.670.0344
ZACHARY@TETONMANAGEMENTGROUP.COM
GENERAL CONTRACTOR:
UNCOMMON BUILDERS
1054 N 575 E
FIRTH, ID 83236
KERRY ADOLPHSON
208.541.9823
UNCOMMONBUILDERS@GMAIL.COM
SPECIAL INSPECTOR:
ATLAS TECHNICAL CONSULTANTS
17778 E PRECISION DR
IDAHO FALLS ID 83401
208-529-8242
STRUCTURAL ENGINEER:
FROST STRUCTURAL ENGINEERING
1020 E LINCOLN RD
IDAHO FALLS, ID 83401
208.227.8404 EXT 204
BRIGHAM CHRISTENSEN
BRIGHAMC@FROSTSTRUCTURAL.COM
ARCHITECT:
SPOTLESS WASH SOLUTIONS USA
PO BOX 5456
TWIN FALLS, ID 83301
JOSHUA E HOWA
208.841.4524
JOSH@SPOTLESSWASHSOLUTIONS.COM
CIVIL ENGINEER:
HORROCKS ENGINEERS
2194 SNAKE RIVER PKWY, STE 205
IDAHO FALLS, ID 83402
208.522.1223
CADEN FUHRIMAN
CADENF@HORROCKS.COM
MECHANICAL / ELECTRICAL ENGINEER:
KARTCHENER BEAUCANNON ASSOCIATES
1301 SOUTH FIVE MILE RD
BOISE, ID 83709
208.888.7145
JUSTIN BEAUCANNON
JBEAUCANNON@KBAMEP.COM
VICINITY MAP
DEFERRED SUBMITTALS
SUBMITTAL DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE SUBMITTED TO THE ARCHITECT OR ENGINEER OF
RECORD WHO SHALL REVIEW THEM AND INDICATE BY NOTATION THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN
REVIEWED AND THAT THEY HAVE BEEN FOUND IN GENERAL CONFORMANCE WITH THE DESIGN OF THE BUILDING. DEFERRED
SUBMITTALS WILL BE RETURNED TO THE CONTRACTOR
THE DEFERRED SUBMITTAL ITEMS SHALL NOT BE INSTALLED UNTIL THEIR DESIGN AND SUBMITTAL DOCUMENTS HAVE BEEN
APPROVED BY THE AUTHORITIES HAVING JURISDICTION
ITEMS DEFERRED ARE REQUIRED TO HAVE A SEPARATE REVIEW AND APPROVAL. EVERY DEFERRED SUBMITTAL SHALL HAVE
SUFFICIENT DRAWINGS, DETAILS AND SUPPORTING DATA TO STAND ON ITS OWN WITHOUT REFERENCE TO PREVIOUSLY
APPROVED PLANS. PROVIDE A COMPLETE PACKAGE FOR SUBMISSION OF DEFERRED ITEMS
ITEMS DEFERRED ARE REQUIRED TO HAVE A SEPARATE REVIEW AND APPROVAL. EVERY DEFERRED SUBMITTAL SHALL HAVE
SUFFICIENT DRAWINGS, DETAILS AND SUPPORTING DATA TO STAND ON ITS OWN WITHOUT REFERENCE TO PREVIOUSLY
APPROVED PLANS. PROVIDE A COMPLETE PACKAGE FOR SUBMISSION OF DEFERRED ITEMS
1.PRE-CAST HOLLOW CORE ROOF PANEL SHOP DRAWINGS
2.STRUCTURAL STEEL SHOP DRAWINGS
4.ICE MELT SYSTEM DESIGN DRAWINGS
THE FOLLOWING ITEMS REQUIRE SEPARATE PLAN CHECK AND PERMIT, AND ARE NOT DEFERRED SUBMITTALS:
A.EXTERIOR SIGNAGE
A. DO NOT SCALE DRAWINGS
B. VERIFY EXISTING UTILITY LOCATIONS PRIOR TO CONSTRUCTION
C. VERIFY ALL DIMENSIONS
D. PROVIDE SOLID FRT WOOD BACKING AT ITEMS PER EQUIPMENT SCHEDULE
E. PROVIDE SEALANT AT ALL LOCATIONS WHERE GYPSUM BOARD MEETS DISSIMILAR
MATERIALS
F. PROVIDE SEALANT AT ALL CONCRETE PANEL JOINTS AND BETWEEN ALL BUILDING
CONCRETE AND SITE CAST PAVING
G. SEE CIVIL DRAWINGS FOR FINISH FLOOR ELEVATION
GENERAL NOTES
THIS PROJECT INCLUDES AN ENCLOSED BUILDING OF 4,593ft2,ON A 51,817ft2 SITE
DEVELOPMENT PLUS RIGHT OF WAY IMPROVEMENTS FOR NEW TUNNEL CAR WASH.
PROJECT INCLUDES 15 COVERED VACUUM SPACES. ALL CONSTRUCTION IS NON-
COMBUSTABLE AND STRUCTURE IS PRECAST CONCRETE CONSTRUCTION, SERVING A
TUNNEL CAR WASH.
PROJECT INFORMATION
NITRO CAR WASH
1371 N 2ND E / REXBURG, ID
BUILDING PERMIT SET - 05/05/22 - NOT FOR CONSTRUCTION
NORTH
W MOODY RD / E 2000N
N
2
N
D
E
N Y E LL O W S T O N E H W Y
H W Y 20
PROJECT
LOCATION
DRAWING INDEX
A0.0 COVER SHEET
G0.1 CODE DATA
G0.2 LIFE SAFETY
A0.1 SITE PLAN
A0.2 SITE DETAILS
A1.0 ASSEMBLIES
A1.1 FLOOR PLAN
A1.2 SLAB, TRENCH, AND PIT GRADING
A1.3 SLAB PLUMBING PLAN
A1.5 WASH EQUIPMENT PLUMBING PLAN
A1.6a EQUIPMENT SCHEDULE
A1.6b EQUIPMENT SCHEDULE CONTINUED
A1.6d EQUIPMENT PLAN / MOTOR LIST
A1.7 ROOF PLAN
A1.8 REFLECTED CEILING PLAN
A2.1 EXTERIOR ELEVATIONS
A2.3 INTERIOR ELEVATIONS
A2.4 TUNNEL EQUIPMENT EMBED PLATE LOCATIONS
A2.5 INTERIOR DETAILS
A3.1 BUILDING SECTIONS
A3.2 WALL SECTIONS
A3.3 EXTERIOR DETAILS
A4.1 POS ISLAND DETAILS
A4.2 POS ISLAND POWER & SPECIAL SYSTEMS PLANS
A5.1 DOOR AND WINDOW DETAILS
A6.1 DOOR AND FINISH SCHEDULES
A6.2 FRAME TYPES
A7.1 RECLAIM SYSTEM DETAILS
C.1.0 COVER SHEET
C.1.1 GENERAL NOTES
C.1.2 LEGEND
C.1.3 FINAL PLAT
C.2.0 EXISTING CONDITIONS & DEMO
C.3.0 OVERALL SITE PLAN & KEY MAP
C.3.1 OVERALL SITE PLAN
C.3.2 SITE PLAN DETAILS
C.4.0 OVERALL GRADING PLAN
C.5.0 OVERALL UTILITY & DRAINAGE PLAN
C.6.0 EROSION CONTROL PLAN
C.7.0 PLAN & PROFILE - MOODY STREET
C.7.1 PLAN & PROFILE - NORTH 2ND EAST
C.7.2 PLAN & PROFILE - PRIVATE DRIVE WEST
C.8.0 EROSION CONTROL
SE-1 SITE ELECTRICAL PLAN
SE-2 POS ISLAND ELECTRICAL PLAN
S1.0 GENERAL STRUCTURAL NOTES
S1.1 TYPICAL DETAILS
S2.0 FOUNDATION PLAN
S2.1 ROOF FRAMING PLAN
S3.0 FOUNDATION DETAILS
S4.0 ROOF FRAMING DETAILS
P-1 WASTE AND VENT FLOOR PLAN
P-2 WATER AND GAS FLOOR PLAN
P-3 PLUMBING DETAILS
M-1 HVAC FLOOR PLAN
M-2 HVAC ROOF PLAN
M-3 MECHANICAL SCHEDULES
M-4 MECHANICAL DETAILS
E-1 ELECTRICAL POWER FLOOR PLAN
E-2 ELECTRICAL LIGHTING FLOOR PLAN
E-3 SPECIAL SYSTEMS FLOOR PLAN
E-4 ELECTRICAL ROOF PLAN
E-5 ELECTRICAL LIGHTING SCHEDULES
E-6 ELECTRICAL PANEL SCHEDULES
E-7 ELECTRICAL SINGLE LINE DIAGRAM
W MORAN VIEW RD
WALMART
E 7TH N
N
2
N
D
E
9T
H
E
/
N
1
0
0
0
E
E 9TH N
1
REVISIONS
#DATE
1 5/4/22
NOT
F
O
R
C
O
N
S
T
R
U
C
T
I
O
N
STAMP:
THESE DOCUMENTS HAVE BEEN PRODUCED AS AN
INSTRUMENT OF SERVICE AND ARE INTENDED SOLELY
FOR THE PURPOSE OF CONSTRUCTING, USING AND
MAINTAINING THE PROJECT. SPOTLESS WASH
SOLUTIONS USA INC, AS THE ARCHITECT OF RECORD
FOR THE PROJECT RETAINS OWNERSHIP OF THESE
DOCUMENTS.
ANY USE OF THESE DOCUMENTS OR USE OF THIS
DESIGN, IDEAS OR CONCEPTS DESCRIBED HEREIN IN
WHOLE OR PART BY ANY MEANS WHATSOEVER IS
STRICTLY PROHIBITED EXCEPT BY WRITTEN CONSENT
OF SPOTLESS WASH SOLUTIONS USA INC.
REPRODUCTION OF THIS DOCUMENT IS STRICTLY
PROHIBITED EXCEPT BY WRITTEN CONSENT OF
SPOTLESS WASH SOLUTIONS USA INC.
COPYRIGHT 2022
SPOTLESS WASH SOLUTIONS USA INC.
CHECKED:
DATE:
JOB NUMBER:
ISSUED FOR:
SHEET NUMBER:
SP
O
T
L
E
S
S
W
A
S
H
S
O
L
U
T
I
O
N
S
PO
B
O
X
5
4
5
6
TW
I
N
F
A
L
L
S
,
I
D
A
H
O
8
3
3
0
3
PH
.
(
2
0
8
)
8
4
1
-
4
5
2
4
DRAWN:
BI
N
D
I
N
G
02/15/2022
PERMIT REVIEW SET
NOT FOR CONSTRUCTION
JH
21005
BUILDING PERMIT - NFC
G0.1
CODE DATA
AS
NI
T
R
O
C
A
R
W
A
S
H
RE
X
B
U
R
G
,
I
D
13
7
1
N
2
N
D
E
RE
X
B
U
R
G
,
I
D
8
3
4
4
8
5/4/22METAL DOORS: U=0.45 OR BETTER
SHGC=0.40 OR BETTER
STOREFRONT ASSEMBLIES: U=0.38 OR BETTER
EXTERIOR WALL CONTINUOUS INSULATION: 2" THICK, R-10 MINIMUM
EXTERIOR WALL FURRING: R-21 MINIMUM AT 6" STUDS; R-13 MINIMUM AT 4" STUDS
ROOF INSULATION WHERE INDICATED: R-30 MINIMUM
WHEN THERE ARE MORE STRINGENT R-VALUES AND U-FACTORS LISTED IN THE PROJECT MANUAL
SPECIFICATIONS SHALL TAKE PRECEDENCE
R-VALUES LISTED ARE MINIMUM TO BE PROVIDED BY INSULATION MATERIALS AND IS NOT THE
TOTAL R-VALUE FOR THE ASSEMBLY
ENERGY CODE NOTES
REVISIONS
#DATE
NOT
F
O
R
C
O
N
S
T
R
U
C
T
I
O
N
FE
1
1
2
2
3
3
4
4
5
5
AA
BB
CC
DD
40
'
-
0
"
137' - 0"
29
'
-10"
3 1 ' -7 "
5 9 ' -4 "
19' -6"
36"
36"
36
"
36
"
CODE AREAS
DRIVE-THRU TUNNEL
MAT WASH
MECH/EQUIP
OFFICE
USABLE:498 ft²
OFFICE
USABLE:2401 ft²
DRIVE-THRU TUNNEL
USABLE:1398 ft²
MECH/EQUIP
USABLE:58 ft²
MAT WASH
101
MANAGER
102
CONTROL
103
HALL
104
TOILET
105
CLEAN
EQUIPMENT
106
EQUIPMENT
108
MAT WASH
107
ELECTRICAL
109
WASH
TUNNEL
36"
EXIT
INSTALL SIGN AT BOTH OVERHEAD
DOORS: "TUNNEL DOORS TO REMAIN
OPEN WHEN THIS SPACE IS OCCUPIED."
EXIT
EXIT
33' - 10 1/8"
INSTALL SIGN AT BOTH OVERHEAD
DOORS: "TUNNEL DOORS TO REMAIN
OPEN WHEN THIS SPACE IS OCCUPIED."
1
1
USABLE:4557 ft²
WASH BUILDING
STAMP:
THESE DOCUMENTS HAVE BEEN PRODUCED AS AN
INSTRUMENT OF SERVICE AND ARE INTENDED SOLELY
FOR THE PURPOSE OF CONSTRUCTING, USING AND
MAINTAINING THE PROJECT. SPOTLESS WASH
SOLUTIONS USA INC, AS THE ARCHITECT OF RECORD
FOR THE PROJECT RETAINS OWNERSHIP OF THESE
DOCUMENTS.
ANY USE OF THESE DOCUMENTS OR USE OF THIS
DESIGN, IDEAS OR CONCEPTS DESCRIBED HEREIN IN
WHOLE OR PART BY ANY MEANS WHATSOEVER IS
STRICTLY PROHIBITED EXCEPT BY WRITTEN CONSENT
OF SPOTLESS WASH SOLUTIONS USA INC.
REPRODUCTION OF THIS DOCUMENT IS STRICTLY
PROHIBITED EXCEPT BY WRITTEN CONSENT OF
SPOTLESS WASH SOLUTIONS USA INC.
COPYRIGHT 2022
SPOTLESS WASH SOLUTIONS USA INC.
CHECKED:
DATE:
JOB NUMBER:
ISSUED FOR:
SHEET NUMBER:
SP
O
T
L
E
S
S
W
A
S
H
S
O
L
U
T
I
O
N
S
PO
B
O
X
5
4
5
6
TW
I
N
F
A
L
L
S
,
I
D
A
H
O
8
3
3
0
3
PH
.
(
2
0
8
)
8
4
1
-
4
5
2
4
DRAWN:
BI
N
D
I
N
G
02/15/2022
PERMIT REVIEW SET
NOT FOR CONSTRUCTION
21005
BUILDING PERMIT - NFC
G0.2
LIFE SAFETY
AS
NI
T
R
O
C
A
R
W
A
S
H
RE
X
B
U
R
G
,
I
D
13
7
1
N
2
N
D
E
RE
X
B
U
R
G
,
I
D
8
3
4
4
8
5/4/22
3/16" = 1'-0"
LIFE SAFETY PLAN1
AREA - OVERALL (NET)
NAME:AREA:
OFFICE 498 ft²
MAT WASH 58 ft²
DRIVE-THRU TUNNEL 2401 ft²
MECH/EQUIP 1398 ft²
TOTAL AREA: 4356 ft²
SINGLE MAJOR OCCUPANCY WITH INTEGRAL ACCESSORY OFFICE AREA
OCCUPANCY CLASSIFICATION (304.1):
GROUP B (CAR WASH), NOT SPRINKLERED, NO FIRE ALARM
BUILDING HEIGHTS & AREAS (503):
GROUP B / TYPE VB: 2 STORIES / 9,000 SF
PROPOSED: 1 STORY / 4,557 SF
CONSTRUCTION TYPE (601):
TYPE V:
EXTERIOR WALLS: PRECAST CONCRETE
INTERIOR WALLS: LIGHT-FRAME CONSTRUCTION
COMBUSTIBLE AND NONCOMBUSTIBLE CONSTRUCTION IS ALLOWED.
THERE ARE NO ELEVATED FLOORS THAT REQUIRE RATED SUPPORT
STRUCTURES.
OCCUPANCY SEPARATION (508):NONE REQUIRED
FIRE ALARM:NONE REQUIRED
OCCUPANT LOAD (1004):
CAR WASH TUNNEL (2401 SF): UNOCCUPIED = 0
BUSINESS AREAS (556 SF): 100 SF PER OCC (GROSS) = 6
EQUIPMENT AREAS (1398 SF): 300 SF PER OCC (GROSS) = 5
TOTAL BUILDING OCCUPANT LOAD:11
ONE EXIT (IN ROOM OR AREA)ALLOWED (1021.2):
MAX OCCUPANT LOAD:49
MAX EXIT TRAVEL DISTANCE:75'
ROOMS / AREAS REQUIRING TWO EXITS (1015.1): CAR WASH TUNNEL
TRAVEL DISTANCE (1016.2): 200' MAX TO NEAREST EXIT
CONCEALED SPACES OVER 3,000sf REQUIRING FIRE BLOCKING / DRAFT STOPPING: NONE
EXIT LIGHTING AND EXIT SIGNS TO COMPLY WITH SECTION 1008 & 1013.
GLASS AND GLAZING TO MEET REQUIREMENTS OF CHAPTER 24.
CODE ANALYSIS
AREA - OFFICE
NAME:AREA:
OFFICE 498 ft²
MAT WASH 58 ft²
TOTAL AREA: 556 ft²
AREA - DRIVE-THRU TUNNEL
NAME:AREA:
DRIVE-THRU TUNNEL 2401 ft²
TOTAL AREA: 2401 ft²
AREA - MECH/EQUIP
NAME:AREA:
MECH/EQUIP 1398 ft²
TOTAL AREA: 1398 ft²
LIFE SAFETY NOTES
A. DO NOT SCALE DRAWINGS, IF DIMENSIONAL INFORMATION IS REQUIRED & NOT FOUND,
NOTIFY ARCHITECT IMMEDIATELY FOR CLARIFICATION.
B. SEE SHEET A0.0 FOR GENERAL NOTES
BUILDING AREA (GROSS)
NAME:AREA:
WASH BUILDING 4557 ft²
TOTAL AREA: 4557 ft²
0'4'2'8'
NORTH
3/32" = 1'-0"
AREA PLAN2
PATH OF TRAVEL
FROM DISTANCE
CLEAN EQUIPMENT 105 59 ft
ELECTRICAL 107 20 ft
HALL 103 32 ft
MANAGER 101 30 ft
1
REVISIONS
#DATE
1 5/4/22
NOT
F
O
R
C
O
N
S
T
R
U
C
T
I
O
N
PAVING TYPE:
ASPHALT
CONCRETE
CONCRETE W/ ICE MELT
GEODETIC DATUM = TBD
1
2
33 36 61
A4.1
1
A0.2
C2
6
1
10
5
7
LANE 2
LANE 1
4
10
3
4,593 SF CAR WASH
BUILDING
120' CONVEYOR
15 VACUUM STALLS
MOODY ROAD
N
2
N
D
E
18 VEHICLE
STACKING
PR
I
V
A
T
E
A
C
C
E
S
S
R
O
A
D
10
10
10 10
4' - 0" 6' - 0" 2' - 9" 12' - 6" 12' - 6" 12' - 6" 12' - 6" 12' - 6" 12' - 6" 12' - 6" 12' - 6" 12' - 6" 12' - 6" 2' - 9"2' - 0" 12' - 6" 12' - 6" 12' - 6" 12' - 6" 12' - 6" 2' - 0"6' - 0"
4 PARKING STALLS
3' - 9" 9' - 0" 3' - 6" 9' - 0" 3' - 6" 9' - 0" 3' - 6" 9' - 0" 3' - 6" 9' - 0" 3' - 9" 8' - 0" 14' - 0" 10' - 0" 4' - 6"
15
'
-
0
"
9' - 0"
8' - 0"
6' - 6"
9' - 0"9' - 0"9' - 0"
10' - 0"
2
10' - 0"
7'
-
0
"
7
'
-
0
"
24
'
-
0
"
9
'
-
0
"
3
0
'
-
0
"
2
0
'
-
0
"
7
'
-
0
"
12
'
-
0
"
12
'
-
0
"
20' - 0"
9'
-
0
"
4
'
-
0
"
9
'
-
0
"
12' - 0"
14
'
-
0
"
12' - 0"
29
'
-
9
"
20
'
-
0
"
30
'
-
0
"
14' - 0"
15
'
-
0
"
6' - 0"
3' - 6"
5' - 0"
5'
-
1
"
5' - 1"
47' - 6"125' - 0"55' - 6"
20
'
-
0
"
15
'
-
0
"
7'
-
0
"
7
'
-
0
"
32 17 23.13
32 17 23.13
32 17 23.13
8'
-
6
"
7'
-
0
"
8'
-
6
"
14
'
-
0
"
6'
-
0
"
1
4
'
-
0
"
8
9
1:12
5' - 0"
6' - 0"
5' - 0" 9' - 6"
6'
-
0
"
12' - 0"
32 39 13
A7.1
2
3' - 6"
TYPICAL
9' - 0" 3' - 6"
32 39 13
32 39 13
8"
D
2
6" D3 4"
D
4
18
"
18
"
36
"
6"
R
W
2
4"
R
W
3
4' - 6"
ICE MELT
AREA
921 SF
11
1
22 14 26.19
STAMP:
THESE DOCUMENTS HAVE BEEN PRODUCED AS AN
INSTRUMENT OF SERVICE AND ARE INTENDED SOLELY
FOR THE PURPOSE OF CONSTRUCTING, USING AND
MAINTAINING THE PROJECT. SPOTLESS WASH
SOLUTIONS USA INC, AS THE ARCHITECT OF RECORD
FOR THE PROJECT RETAINS OWNERSHIP OF THESE
DOCUMENTS.
ANY USE OF THESE DOCUMENTS OR USE OF THIS
DESIGN, IDEAS OR CONCEPTS DESCRIBED HEREIN IN
WHOLE OR PART BY ANY MEANS WHATSOEVER IS
STRICTLY PROHIBITED EXCEPT BY WRITTEN CONSENT
OF SPOTLESS WASH SOLUTIONS USA INC.
REPRODUCTION OF THIS DOCUMENT IS STRICTLY
PROHIBITED EXCEPT BY WRITTEN CONSENT OF
SPOTLESS WASH SOLUTIONS USA INC.
COPYRIGHT 2022
SPOTLESS WASH SOLUTIONS USA INC.
CHECKED:
DATE:
JOB NUMBER:
ISSUED FOR:
SHEET NUMBER:
SP
O
T
L
E
S
S
W
A
S
H
S
O
L
U
T
I
O
N
S
PO
B
O
X
5
4
5
6
TW
I
N
F
A
L
L
S
,
I
D
A
H
O
8
3
3
0
3
PH
.
(
2
0
8
)
8
4
1
-
4
5
2
4
DRAWN:
BI
N
D
I
N
G
02/15/2022
PERMIT REVIEW SET
NOT FOR CONSTRUCTION
21005
BUILDING PERMIT - NFC
A0.1
SITE PLAN
AS
NI
T
R
O
C
A
R
W
A
S
H
RE
X
B
U
R
G
,
I
D
13
7
1
N
2
N
D
E
RE
X
B
U
R
G
,
I
D
8
3
4
4
8
5/4/22
SITE PLAN NOTES
A. DRAWINGS & SPECIFICATIONS ARE COMPLIMENTARY COMPONENTS OF THE CONTRACT
DOCUMENTS, REVIEW ALL DRAWINGS AND SPECIFICATIONS FOR THE COMPLETE SCOPE OF
WORK. NOTIFY ARCHITECT IMMEDIATELY FOR CLARIFICATION IF INCONSISTENCIES,
CONTRADICTIONS OR OMISSIONS ARE DISCOVERED.
B. DO NOT SCALE DRAWINGS, IF DIMENSIONAL INFORMATION IS REQUIRED & NOT FOUND,
NOTIFY ARCHITECT IMMEDIATELY FOR CLARIFICATION.
C. UNLESS NOTED OTHERWISE SLOPE GRADE MAXIMUM 2% WITHIN 10' OF BUILDING, THEN
MAXIMUM 5% TO MATCH EXISTING GRADE ELEVATIONS. SLOPE ALL WALKING SURFACES
MAXIMUM 5% IN THE DIRECTION OF TRAVEL AND MAXIMUM 2% AT LANDING, CHANGE OF
DIRECTION, AND PERPENDICULAR TO DIRECTION OF TRAVEL.
D. UNLESS NOTED OTHERWISE FOR ALL EXTERIOR CONCRETE PAVEMENT PROVIDE MINIMUM 6"
TYPE II, COMPACTED 95%.
E. SEE LANDSCAPE PLANS FOR PLANTING AND IRRIGATION INFORMATION.
F. SEE CIVIL DRAWINGS FOR GRADING, DRAINAGE AND UTILITIES.
G. ALL WORKS TAKES PLACE DURING A SINGLE AND ONLY PHASE OF THE PROJECT.
H. NOT ALL UNDERGROUND PIPING AND CONDUITS FROM BUILDING TO RECLAIM TANKS IS
IDENTIFIED ON THIS SHEET. SEE A1.3 AND A7.1 FOR ADDITIONAL REQUIREMENTS.
I. REFER TO SHEET C.3.1 OVERALL SITE PLAN FOR SNOW STORAGE LOCATIONS.
1/16" = 1'-0"
SITE PLAN1
SHEET NOTES
1 PROPERTY LINE
2 BUILDING SETBACK
3 VACUUM PRODUCER PAD
4 TRASH ENCLOSURE
5 STAINLESS STEEL ISLAND FORM, FILL WITH CONCRETE
6 ESCAPE LANE
7 TRANSFORMER PAD, SEE CIVIL/ELECTRICAL
8 RECLAIM OUTLET TO SANITARY SEWER, SEE CIVIL
9 SANITARY SEWER CLEANOUT, SEE RECLAIM A7.1
10 SIGN, POST, "DO NOT ENTER"
11 VAN ACCESSIBLE PARKING STALL & SIGN. REFER TO C.3.1 CIVIL SITE PLAN & 4/C.3.2 TYPICAL
HANDICAP SIGN DETAIL
KEYNOTES
MARK:DESCRIPTION:
22 14 26.19 PRESLOPED TRENCH DRAIN, ACO S200K WITH SLOTTED IRON 8" LOAD CLASS F GRATE
(OR APPROVED EQUAL)
32 17 23.13 PAINTED PAVEMENT MARKING, WHITE
32 39 13 METAL BOLLARDS
33 36 61 UNDERGROUND REINFORCED CONCRETE WASTEWATER RECLAIM TANKS
0'16'8'32'
NORTH
SITE ANALYSIS
ADDRESS : 1371 N 2ND E
REXBURG, ID
ZONING : COMMERCIAL
SITE AREA : 51,817 SF
BUILDING AREA:4,593 SF
BUILDING HEIGHT:28'
COMMERCIAL ZONE C:
SETBACKS:
-FRONT / SIDE: 10' (ABUTTING PUBLIC THOROUGHFARE)
-BACK: 0'' (NO DEDICATED ALLEY OR PUBLIC WAY)
-SIDES: 0' (ADJACENT COMMERCIAL OR INDUSTRIAL)
PARKING : USE -OTHER
1 SPACE PER 1,000 SF OF FLOOR AREA (4,593sf)
REQUIRED PROVIDED
5 19
MINIMUM 1 ADA VAN ACCESSIBLE SPACE PER SECTION 1106.1 & 1106.5
CITY OF REXBURG, ID DEVELOPMENT CODE
1
1
1
REVISIONS
#DATE
1 5/4/22
NOT
F
O
R
C
O
N
S
T
R
U
C
T
I
O
N
6"
3
'
-
0
"
3
'
-
0
"
1
1
/
8
"
ROUNDED CONCRETE CAP
STEEL PIPE 6" STANDARD, PRIME
WITH DTM RUST INHIBITING
PRIMER
SEAL JOINT AT CONCRETE
FOOTING
SLOPE TO 1" ABOVE PAVEMENT
CAST IN PLACE CONCRETE
FOOTING
BOLLARD COVER AS
MANUFACTURED BY POST
GUARD, BLUE DOME COVER
MIN
1219 FLUSH WITH
PAVEMENT
SL
O
P
E
1:
1
2
S L O P E
1 :1 2
SLOPE1:12
1/4" TOOLED JOINTS @ 6" O.C.
CONCRETE SIDEWALK
CONSTRUCT PER ICC/ANSI A117.1-2009
SECTION 406 OR LOCAL BUILDING
STANDARD
CONSTRUCT PER ICC/ANSI A117.1-2009
OR LOCAL BUILDING STANDARD
EXPANSION JOINT
CONCRETE WALK, BROOM FINISH
GRANULAR FILL
TRAFFIC RESISTANT CAULK OVER
TOP OF 1/2" X 4" EXPANSION JOINT
FILLER HELD DOWN 1/2"
1/4" TOOLED RADIUS
13
CONTROL JOINT
CONCRETE WALK, BROOM FINISH
GRANULAR FILL
SEALANT
SAWCUT OR TOOLED JOINT WITH 1/4"
RADIUS EDGE
6
NOTE:PROVIDE CONTROL JOINTS AT
INTERVALS TO MATCH SIDEWALK WIDTH
BUT NOT MORE THAN 8' O.C. PROVIDE
EXPANSION JOINTS AT INTERVALS NOT
MORE THAN 20' O.C. BUT NOT LESS
THAN INDICATED ON PLAN
CROSS SLOPE OF SIDEWALKS NOT TO EXCEED 2%
1
4x4 PT WOOD POSTS
2x4 EXTERIOR GRADE
WOOD STUDS, EXTEND
BETWEEN HORIZONTAL
PLATES & CENTER
BETWEEN POSTS
1x TREX STYLE FENCE
PRODUCT W/ 1/2" GAP TO
MATCH ACCENT SIDING
FINISH & SPECIES
2x8 WOOD TRIM TO
MATCH ACCENT SIDING
FINISH & SPECIES2x4 EXTERIOR GRADE
WOOD PLATE, FASTEN
W/ HANGER PLATES
BETWEEN POSTS
TOP OF CONCRETE CURB,
SEE CIVIL
6'
-
0
"
MIN6"
C3
A0.2
1' - 0" 9' - 3" 3' - 6" 9' - 3" 1' - 0"
1'
-
0
"
1
0
'
-
0
"
1
'
-
0
"
4x4 PT WOOD POSTS
2x4 EXTERIOR GRADE WOOD
STUDS, EXTEND BETWEEN
HORIZONTAL PLATES &
CENTER BETWEEN POSTS
WOOD SIDING TO MATCH
CAR WASH BUILDING
2x8 WOOD TRIM TO
MATCH SIDING
CONCRETE CURB, SEE CIVIL
32 39 1332 39 13
STAMP:
THESE DOCUMENTS HAVE BEEN PRODUCED AS AN
INSTRUMENT OF SERVICE AND ARE INTENDED SOLELY
FOR THE PURPOSE OF CONSTRUCTING, USING AND
MAINTAINING THE PROJECT. SPOTLESS WASH
SOLUTIONS USA INC, AS THE ARCHITECT OF RECORD
FOR THE PROJECT RETAINS OWNERSHIP OF THESE
DOCUMENTS.
ANY USE OF THESE DOCUMENTS OR USE OF THIS
DESIGN, IDEAS OR CONCEPTS DESCRIBED HEREIN IN
WHOLE OR PART BY ANY MEANS WHATSOEVER IS
STRICTLY PROHIBITED EXCEPT BY WRITTEN CONSENT
OF SPOTLESS WASH SOLUTIONS USA INC.
REPRODUCTION OF THIS DOCUMENT IS STRICTLY
PROHIBITED EXCEPT BY WRITTEN CONSENT OF
SPOTLESS WASH SOLUTIONS USA INC.
COPYRIGHT 2022
SPOTLESS WASH SOLUTIONS USA INC.
CHECKED:
DATE:
JOB NUMBER:
ISSUED FOR:
SHEET NUMBER:
SP
O
T
L
E
S
S
W
A
S
H
S
O
L
U
T
I
O
N
S
PO
B
O
X
5
4
5
6
TW
I
N
F
A
L
L
S
,
I
D
A
H
O
8
3
3
0
3
PH
.
(
2
0
8
)
8
4
1
-
4
5
2
4
DRAWN:
BI
N
D
I
N
G
02/15/2022
PERMIT REVIEW SET
NOT FOR CONSTRUCTION
21005
BUILDING PERMIT - NFC
A0.2
SITE DETAILS
AS
NI
T
R
O
C
A
R
W
A
S
H
RE
X
B
U
R
G
,
I
D
13
7
1
N
2
N
D
E
RE
X
B
U
R
G
,
I
D
8
3
4
4
8
5/4/22
1/2" = 1'-0"
BOLLARD DETAIL, TYPICALC1
1/2" = 1'-0"
ACCESSIBLE CURB CUTB21/2" = 1'-0"
ACCESSIBLE PARKING SIGNB3 1/2" = 1'-0"
ACCESSIBLE PARKING EMBLEMB1
1" = 1'-0"
SIDEWALK DETAILA1
GENERAL NOTES
A.SEE SHEET A2.1 FOR EXTERIOR FINISH SCHEDULE.
B.CHAMFER ALL EXPOSED CONCRETE EDGES 3/4"
C.PROVIDE TEXTURED ELASTOMERIC FINISH SYSTEM AT ALL TRASH ENCLOSURE
CONCRETE SURFACES.
D.PROVIDE JOINT SEALANT BETWEEN ALL TRASH ENCLOSURE PANEL EDGES.
ALSO PROVIDE JOINT SEALANT BETWEEN ALL SLAB OR PAVEMENT / WALL
INTERSECTIONS.
1/2" = 1'-0"
TRASH ENCLOSURE DETAILC3 1/4" = 1'-0"
TRASH ENCLOSUREC2
KEYNOTES
MARK:DESCRIPTION:
32 39 13 METAL BOLLARDS
REVISIONS
#DATE
1 5/4/22
NOT
F
O
R
C
O
N
S
T
R
U
C
T
I
O
N
ACCOUSTIC INSULATION
2x4 STUD @ 24" OC
5/8" GYPSUM BOARD
NOTE:WHERE INDICATED ON ROOM FINISH
SCHEDULE, REPLACE GYPSUM BOARD
WITH 5/8" CDX PLYWOOD SHEATHING
2x6 STUD @ 24" OC
ACCOUSTIC INSULATION
5/8" GYPSUM BOARD
NOTE:WHERE INDICATED ON ROOM FINISH
SCHEDULE, REPLACE GYPSUM BOARD
WITH 5/8" CDX PLYWOOD SHEATHING
5/8" GYPSUM BOARD
ACCOUSTIC INSULATION
PARENT WALL SIDE
ROOM SIDE
2x4 STUD @ 24" OC
(2") CONTINUOUS INSULATION
5/8" GYPSUM BOARD
ACCOUSTIC INSULATION
PARENT WALL SIDE
ROOM SIDE
2x6 STUD @ 24" OC
NOTE:WHERE INDICATED ON ROOM FINISH
SCHEDULE, REPLACE GYPSUM BOARD
WITH 5/8" CDX PLYWOOD SHEATHING
INTERIOR
EXTERIOR
5/8" EXTERIOR GRADE PLYWOOD
SHEATHING
WEATHER-RESISTIVE BARRIER
2X4 AT 16" OC
R-15 BLANKET
5/8" GYPSUM BOARD
POLYETHELENE VAPOR BARRIER, 6
MIL
INTERIOR
EXTERIOR
5/8" EXTERIOR GRADE PLYWOOD
SHEATHING
2X6 STUD @ 16" (406mm) OC
WEATHER-RESISTIVE BARRIER
R-21 BLANKET
5/8" GYPSUM BOARD
POLYETHELENE VAPOR BARRIER, 6
MIL
EXTERIOR
PROVIDE SMOOTH FORM FINISH AND
SEALANT CC-1
PAINT TWO COATS AT EXTERIOR SURFACES WHERE
VISIBLE. VISIBLE SURFACES INCLUDE THOSE ONLY
VISIBLE FROM ROOF ABOVE TERMINATION BAR.
NOTE:WHERE BOTH SIDES OF WALL
ARE INTERIOR, PROVIDE SMOOTH
FORM FINISH AND SEALANT CC-1
INTERIOR
8"
SHEET UNDERLAYMENT
METAL ROOF PANELS
STEEL STUD & SHEATHING, SEE STRUCT.
METAL SOFFIT PANEL
ICE & WATER SHIELD
PRECAST HOLLOW CORE
SLAB
APPLY PRIMER
(2) LA. 3" GLASS FACED POLYISO.
TAPERED INSULATION BOARD SEE
PLAN
SUPPORT BOARD AND BASE
SHEET WITH LAMINATED
MEMBRANE WITH COVER STRIP
AT EACH END JOINT
MEMBRANE CAP SHEET
THERMOPLASTIC POLYOLEFIN
MEMBRANE ROOFING SYSTEM
(TPO)
NOTE: PROVIDE
FULLY-ADHERED
ROOFING SYSTEM
INTERIOR
EXTERIOR
5/8" EXTERIOR GRADE PLYWOOD
SHEATHING
2X6 STUD @ 16" (406mm) OC
WEATHER-RESISTIVE BARRIER
R-21 BLANKET
5/8" EXTERIOR GRADE PLYWOOD
SHEATHING
POLYETHELENE VAPOR BARRIER, 6
MIL
ABOVE ROOF DECK ONLY
EXTERIOR
PROVIDE SMOOTH FORM
FINISH AND SEALANT CC-1INTERIOR
8"PRECAST CONCRETE
2X6 PT STUD @ 16" OC
7/8" EXTERIOR GRADE
PLYWOOD SHEATHING
WEATHER BARRIER
CORTEN STEEL WALL PANELS
W/ 4'x4' SEAM PATTERN
PROVIDE SMOOTH FORM FINISH AND
SEALANT CC-1
INTERIOR
PROVIDE SMOOTH FORM FINISH AND
SEALANT CC-1INTERIOR
6"
EXTERIOR
PROVIDE SMOOTH FORM
FINISH AND SEALANT CC-1INTERIOR
8"
PRECAST CONCRETE
SIDING PER ELEVATIONS
5/8" EXTERIOR GRADE PLYWOOD
SHEATHING
ACCOUSTIC INSULATION
PARENT WALL SIDE
ROOM SIDE
2x4 STUD @ 24" OC
ACCOUSTIC INSULATION
2x4 STUD @ 24" OC
5/8" GYPSUM BOARD
5/8" EXTERIOR GRADE PLYWOOD
SHEATHING
2x6 STUD @ 24" OC
ACCOUSTIC INSULATION
5/8" EXTERIOR GRADE PLYWOOD
SHEATHING
5/8" EXTERIOR GRADE PLYWOOD
SHEATHING
STAMP:
THESE DOCUMENTS HAVE BEEN PRODUCED AS AN
INSTRUMENT OF SERVICE AND ARE INTENDED SOLELY
FOR THE PURPOSE OF CONSTRUCTING, USING AND
MAINTAINING THE PROJECT. SPOTLESS WASH
SOLUTIONS USA INC, AS THE ARCHITECT OF RECORD
FOR THE PROJECT RETAINS OWNERSHIP OF THESE
DOCUMENTS.
ANY USE OF THESE DOCUMENTS OR USE OF THIS
DESIGN, IDEAS OR CONCEPTS DESCRIBED HEREIN IN
WHOLE OR PART BY ANY MEANS WHATSOEVER IS
STRICTLY PROHIBITED EXCEPT BY WRITTEN CONSENT
OF SPOTLESS WASH SOLUTIONS USA INC.
REPRODUCTION OF THIS DOCUMENT IS STRICTLY
PROHIBITED EXCEPT BY WRITTEN CONSENT OF
SPOTLESS WASH SOLUTIONS USA INC.
COPYRIGHT 2022
SPOTLESS WASH SOLUTIONS USA INC.
CHECKED:
DATE:
JOB NUMBER:
ISSUED FOR:
SHEET NUMBER:
SP
O
T
L
E
S
S
W
A
S
H
S
O
L
U
T
I
O
N
S
PO
B
O
X
5
4
5
6
TW
I
N
F
A
L
L
S
,
I
D
A
H
O
8
3
3
0
3
PH
.
(
2
0
8
)
8
4
1
-
4
5
2
4
DRAWN:
BI
N
D
I
N
G
02/15/2022
PERMIT REVIEW SET
NOT FOR CONSTRUCTION
21005
BUILDING PERMIT - NFC
A1.0
ASSEMBLIES
AS
NI
T
R
O
C
A
R
W
A
S
H
RE
X
B
U
R
G
,
I
D
13
7
1
N
2
N
D
E
RE
X
B
U
R
G
,
I
D
8
3
4
4
8
5/4/22
1" = 1'-0"
4" PARTITIONP4
1" = 1'-0"
6" PARTITIONP6
1" = 1'-0"
4" FURRINGF4
1" = 1'-0"
6" FURRINGF6
1" = 1'-0"
4" EXTERIORE4
1" = 1'-0"
6" EXTERIORE6a1" = 1'-0"
PRECAST CONCRETE WALLC8
1" = 1'-0"
WALL ASSEMBLIES
1" = 1'-0"
EXTERIOR METAL ROOFR21" = 1'-0"
PRECAST ROOF ASSEMBLYR1
1" = 1'-0"
ROOF ASSEMBLIES
1" = 1'-0"
6" EXTERIORE6b
NOTE: ALL WALL ASSEMBLIES ARE FULL-HEIGHT TO UNDERSIDE OF STRUCTURAL DECK UNLESS
SPECIFICALLY INDICATED OTHERWISE. PROVIDE MANUFACTURER'S STANDARD DEFLECTION JOINT
SYSTEM WHERE WALLS EXTEND TO UNDERSIDE OF STRUCTURE. IF SPECIFIED STUD SIZE DOES
NOT MEET DEFLECTION CRITERIA FOR HEIGHT INDICATED, INCREASE STUD SIZE ACCORDINGLY
1" = 1'-0"
PRECAST & FURRING WALLC8a
1" = 1'-0"
PRECAST CONCRETE WALLC6
1" = 1'-0"
PRECAST CONCRETE WALLC8b
1" = 1'-0"
4" FURRING W/ PLYWOODF5 1" = 1'-0"
4" PARTITION W/ PLYWOODP5
1" = 1'-0"
6" PARTITION W/ PLYWOODP7
REVISIONS
#DATE
NOT
F
O
R
C
O
N
S
T
R
U
C
T
I
O
N
FE
15
'
-
0
"
20
'
-
0
"
S1
S2
S3
S4S5
H4H5
H2
H3
A2.1
2
A2.1
3
A2.1 1
1
1
2
2
3
3
4
4
12' - 0"12' - 0"93' - 0"20' - 0"
5
5
0"42' - 0"14' - 6"45' - 6"3' - 0"
A2.14
1
A3.1
3
A3.1
3
A3.1
2
A3.1
101
MANAGER
102
CONTROL
103
HALL
104
TOILET
105
CLEAN
EQUIPMENT
106
EQUIPMENT
107
ELECTRICAL
109
WASH
TUNNEL
AA
BB
CC
DD
1' - 4"3' - 4"4' - 10"10' - 0"28' - 6"7' - 0"4' - 8"3' - 4"26' - 0"4' - 0"6"3' - 6"10' - 0"4' - 0"2' - 0"
CENTERLINE OF WASH SYSTEM
35
'
-
0
"
OH108
108
MAT WASH
OH106
10
6
a
105b
107
10
1
105a
5'
-
0
"
1
5
'
-
0
"
20
'
-
0
"
10
4
OH
1
0
9
b
137' - 0"
10
'
-
0
"
1
0
'
-
0
"
3'
-
1
0
"
1'
-
6
"
6'
-
0
"
2' - 0"8' - 0"2' - 0"2' - 0"8' - 0"2' - 0"
3'
-
1
0
"
11' - 2"
4'
-
4
"
P4
P4
P5
F4
F4
P6
P7
4
A3.1
4
A3.1
P7
CP8
F5
S6S7
P7
3'
-
0
"
5
'
-
8
"
4' - 7"
1'
-
0
"
8
'
-
4
"
10
3
10
2
b
10
2
a
10
6
b
1
2
3
2
A2.3
1
4'
-
1
"
5'
-
3
"
5'
-
3
"
4'
-
1
"
C8
C8
C8C8
C8C8
4'
-
6
"
10
'
-
0
"
1
0
'
-
0
"
10 44 16
CP8
3' - 9"23' - 9"1' - 0"4' - 0"41' - 0"
14
'
-
4
"
1'
-
9
"
10
'
-
1
0
"
1'
-
9
"
22 14 26.19
1' - 7"13' - 0"1' - 7"3'
-
8
"
22 14 26.19
3
A7.1
3
A7.1
4'
-
0
"
05 53 00
2 2
S7
4
2
1' - 4"
2' - 11"
2' - 8" 8' - 0" 2' - 0"
F5
F4
F4
F4
05 51 33
S6 S6
2
20' - 0"2' - 4"40' - 2"6' - 0" 14' - 0"30' - 6"12' - 0"
5
5
5
1
A1.1
1' - 0"
101' - 0"
TOP OF
CP8
OH109a
22 14 26.19
32 39 13
32 39 13
1
T/O FLOOR
100' -0"
7
8
8
6
1' - 6" CLEAR
3' - 0" MINIMUM
NOTE: PROVIDE 7"
MINIMUM TOE CLEARANCE
BETWEEN WALL AND
LADDER RUNGS
1'
-
0
"
TY
P
.
1'
-
0
"
DIMENSIONS
TO TOP OF
RUNGS
CLEAR
1' - 6"
UNDERLAY LEVEL
113' -0"
STAMP:
THESE DOCUMENTS HAVE BEEN PRODUCED AS AN
INSTRUMENT OF SERVICE AND ARE INTENDED SOLELY
FOR THE PURPOSE OF CONSTRUCTING, USING AND
MAINTAINING THE PROJECT. SPOTLESS WASH
SOLUTIONS USA INC, AS THE ARCHITECT OF RECORD
FOR THE PROJECT RETAINS OWNERSHIP OF THESE
DOCUMENTS.
ANY USE OF THESE DOCUMENTS OR USE OF THIS
DESIGN, IDEAS OR CONCEPTS DESCRIBED HEREIN IN
WHOLE OR PART BY ANY MEANS WHATSOEVER IS
STRICTLY PROHIBITED EXCEPT BY WRITTEN CONSENT
OF SPOTLESS WASH SOLUTIONS USA INC.
REPRODUCTION OF THIS DOCUMENT IS STRICTLY
PROHIBITED EXCEPT BY WRITTEN CONSENT OF
SPOTLESS WASH SOLUTIONS USA INC.
COPYRIGHT 2022
SPOTLESS WASH SOLUTIONS USA INC.
CHECKED:
DATE:
JOB NUMBER:
ISSUED FOR:
SHEET NUMBER:
SP
O
T
L
E
S
S
W
A
S
H
S
O
L
U
T
I
O
N
S
PO
B
O
X
5
4
5
6
TW
I
N
F
A
L
L
S
,
I
D
A
H
O
8
3
3
0
3
PH
.
(
2
0
8
)
8
4
1
-
4
5
2
4
DRAWN:
BI
N
D
I
N
G
02/15/2022
PERMIT REVIEW SET
NOT FOR CONSTRUCTION
JH
21005
BUILDING PERMIT - NFC
A1.1
FLOOR PLAN
AS
NI
T
R
O
C
A
R
W
A
S
H
RE
X
B
U
R
G
,
I
D
13
7
1
N
2
N
D
E
RE
X
B
U
R
G
,
I
D
8
3
4
4
8
5/4/22
GENERAL NOTES
A. DIMENSIONS ARE TO:
a. FACE OF STUD OR CONCRETE / BLOCK WALL.
b. CENTERLINE OF WINDOW OR DOOR.
B. DIMENSIONED SWING DOOR OPENINGS ARE TO OUTSIDE FACE OF FRAME. ADD 1/2" (12.7mm)
TO DIMENSION FOR ROUGH OPENINGS.
C. WALL ASSEMBLIES ON SHEET A1.0.
D. ROOM FINISH SCHEDULES ON SHEET A6.1.
E. FRAME TYPES ON SHEET A6.2.
F. PROVIDE BACKING IN FRAMED WALLS FOR WALL MOUNTED ITEMS EXCEPT AS OTHERWISE
NOTED ON EQUIPMENT AND ACCESSORIES SCHEDULES ON A1.3 SERIES SHEETS.
G. PIPING AND ELECTRICAL ROUGH-IN STUB-UPS ARE TO BE AT CENTERLINE OF WALLS AT
FRAMED WALL ASSEMBLIES.
H. PROVIDE TWO COATS OF SEVERE EXPOSURE PAINT TO PROTECT STEEL FROM MOISTURE AT
ALL STEEL EXPOSED AT THE CAR WASH TUNNEL. THIS INCLUDES ALL EXPOSED EMBED
STEEL EXCEPT STAINLESS STEEL ITEMS. DO NOT COAT CONVEYOR TRENCH ANGLE EMBEDS
OR FLAT PLATES AT THE CONVEYOR.
I. GROUT AND TEXTURE ALL PANEL PICK HARDWARE REVEALS. FINISH TO MATCH ADJACENT
PANEL SURFACE.
J. WALL TYPE "P6" IS TYPICAL AT INTERIOR FRAMED PARTITIONS AND FULL HEIGHT EXCEPT
WHERE SPECIFICALLY INDICATED OTHERWISE.
K. FOR TYPICAL ACCESSIBILITY CLEARANCES SEE SHEET A2.3.
L. ALL WALLS, PARTITIONS AND FURRING TO EXTEND TO UNDERSIDE OF DECK UNLESS
SPECIFICALLY INDICATED OTHERWISE. PROVIDE MANUFACTURER'S STANDARD DEFLECTION
TRACK.
M. ALL TRENCH AND PIT GRATINGS ARE FURNISHED AND INSTALLED BY OWNER EXCEPT THAT
EQUIPMENT ROOM TRENCH DRAIN AND EXTERIOR TRENCH DRAINS ARE PROVIDED BY
CONTRACTOR.
N. OVERHEAD PANEL DOOR: BASIS-OF-DESIGN IS AIRLIFT DOORS, INC. ALASKA EXTREME
PACKAGE WITH STAINLESS STEEL TORSION SPRINGS, ANODIZING UPGRADE, MANUAL
OPERATION, 3-PANEL WIDE POLYCARBONATE . DO NOT INCLUDE STRAPEZE
COUNTERBALANCE SYSTEM. OVERHEAD DOORS SHALL EXTEND VERTICALLY ON WALL AS
HIGH AS POSSIBLE.
O. OVERHEAD ROLLING STEEL SERVICE DOOR BASIS-OF-DESIGN IS OVERHEAD DOOR MODEL
610 -F-265, MANUAL OPERATION.
P. PROVIDE ACCESSIBLE DOOR LANDING AT APPROACH AND PULL SIDE OF ALL DOORS.
Q. PROVIDE BROOM FINISH AT ALL INTERIOR SLABS, EXCEPT PROVIDE SMOOTH TROWEL FINISH
AT CAR WASH TUNNEL AT THE PASSENGER SIDE OF THE CONVEYOR TRENCH EXTENDING 4'
BEYOND THE TRENCH (PASSENGER SIDE ONLY). PROVIDE BROOM FINISH BEGINNING 4'
FROM TRENCH TO ADJACENT WALL.
R. PROVIDE SEALANT AT ENTIRE PERIMETER OF THE CAR WASH TUNNEL AND THE EQUIPMENT
ROOM WHERE THE SLABS MEET A CONCRETE WALL. USE ISOFLEX OR APPROVED EQUAL
TEAR-OFF STRIP JOINT FILLER TO CREATE A VOID FOR THE SEALANT.
KEYNOTES
MARK:DESCRIPTION:
05 51 33 METAL LADDER
05 53 00 METAL GRATING, OWNER PROVIDED, AMD 1.5x1.5x1.5 MOLDED PROFILE NUMBER 14, YELLOW, OR
APPROVED EQUAL
10 44 16 FIRE EXTINGUISHER, 10 LB. TYPE 3A-40B:CM, PROVIDE WALL BRACKET
22 14 26.19 PRESLOPED TRENCH DRAIN, ACO S200K WITH SLOTTED IRON 8" LOAD CLASS F GRATE (OR
APPROVED EQUAL)
32 39 13 METAL BOLLARDS
SHEET NOTES
#:NOTE:
1 CONVEYOR TRENCH WITH PERIMETER ANGLE EMBEDS, SEE DETAIL 4 & 5 SHEET A1.2
2 CENTER OPENING IN PRECAST PANEL
3 CONVEYOR EQUIPMENT AND CONVEYOR GRATING BY OTHERS
4 STEEL LADDER TO ROOF. 18" MINIMUM WIDTH. PRIME AND PAINT. VERIFY EXACT LOCATION
5 EXIT DISCHARGE DOOR
6 ROOF HATCH
7 STEEL LADDER WITH 2 1/2" RAILS AND 1" DIA. RUNGS
8 STEEL BRACKET
0'4'2'8'
NORTH3/16" = 1'-0"
FLOOR PLAN
1/4" = 1'-0"
LADDER AND ROOF HATCH1
REVISIONS
#DATE
1 5/4/22
NOT
F
O
R
C
O
N
S
T
R
U
C
T
I
O
N
5
A1.2
4
A1.2
4
A1.2
3'
-
8
"
2'
-
0
"
8' - 0"
4
A1.2
4
A1.2
5
A1.2
4
A1.2
4
A1.2 5
A1.2
5
A1.2
CONVEYOR
TRENCH PLAN
NOTE: SEE FLOOR PLANS
FOR EMBED PLATE
LOCATIONS
6' - 0"
5'
-
8
"
5'
-
8
"
OVERALL LENGTH = 120'-2"
DIRECTION OF VEHICLE TRAVEL
SEE STRUCTURAL
FOR REINFORCING
VEHICLE IS
TRAVELING AWAY
FROM VIEWER OF
THIS DETAIL
1'
-
5
"
2
'
-
6
"
C
L
E
A
R
NOTE:AT HIGH ENDS OF CONVEYOR TRENCH, THE WEDGE WILL
GET SMALLER AND GRADUALLY DISAPPEAR IN ORDER TO MAINTAIN
THE 2'-6" DIMENSION FROM TOP OF CONCRETE TO TOP OF WEDGE.
UNDISTURBED SOIL OR
COMPACTED STRUCTURAL
FILL, TYPICAL
SERRATED
WATERSTOP,
TYPICAL
3' - 8"
8"
3
1
/
2
"
1' - 10 1/2"
45° M
AX
STEEL EMBED
PLATE 8"x8"x0.5"
AT 5'-0" OC WITH
(4) 1/4" x 2" WELD
STUDS
CENTERLINE OF
WASH SYSTEM
A1.2
4
A1.2
5
L1.75xL1.75x0.25 WITH 1/4"x3" HCA'S
AT 24" OC
CENTERLINE OF WASH
SYSTEM
L2.5xL2.5x0.25 WITH 1/4"x3" HCA'S AT
24" OC
1
1
2
2
3
3
4
4
5
5
AA
BB
CC
DD
100.00
99.79 T.T.109
WASH
TUNNEL
106
EQUIPMENT
105
CLEAN
EQUIPMENT
103
HALL
102
CONTROL
101
MANAGER
104
TOILET
108
MAT WASH
107
ELECTRICAL
99.83
100.00
100.00
99.63
100.25
100.25100.25
100.25
100.17
100.17
100.00
100.00100.00
100.00
3
A1.2
22 14 26.19
22 14 26.19
22 14 26.19
22 14 26.23
95.98 B.T.
97.18 T.O.W.
1
1
1.83%
1.83%
95.56 B.T.
96.19 B.T.
97.18 B.T.
96.19 B.T.
99.79 T.T.
99.27 T.T.
99.23 T.T.
99.42 B.S.
4
A7.1
2.08%
99.75
99.85
99.75
99.83 99.83
100.00
100.00
99.94
99.94
99.75
99.75
99.88 99.88
1.
93%
1.
8
3
%
99.8499.85
2.40%
1.74%
1.87%
1.88%2.83%
1.74%
100.17
1.94%
1
.
8
4
%
[No Slope]
0.43%
5.00%99.23 T.T.
99.28
99.19 T.T.
99.19 T.T.
0.50%
99.49 T.T.
99.49 T.T.
0.50%
99.46
99.41
99.61
0.50%
99.30
99.51
99.53
99.58
99.6699.79 T.T.
0.50%
0.50%
0.50%
99.92
99.7999.79
99.79
99.76 T.T.
99.81
99.76
0.50%
99.76
99.76
99.75
1.
87%
100.00
100.00
100.00
99.47
99.48
99.54
99.28
TRASH PIT WALL
L1.75xL1.75x0.25 WITH 1/4"x3" HCA'S
AT 24" OC
METAL GRATING
STAMP:
THESE DOCUMENTS HAVE BEEN PRODUCED AS AN
INSTRUMENT OF SERVICE AND ARE INTENDED SOLELY
FOR THE PURPOSE OF CONSTRUCTING, USING AND
MAINTAINING THE PROJECT. SPOTLESS WASH
SOLUTIONS USA INC, AS THE ARCHITECT OF RECORD
FOR THE PROJECT RETAINS OWNERSHIP OF THESE
DOCUMENTS.
ANY USE OF THESE DOCUMENTS OR USE OF THIS
DESIGN, IDEAS OR CONCEPTS DESCRIBED HEREIN IN
WHOLE OR PART BY ANY MEANS WHATSOEVER IS
STRICTLY PROHIBITED EXCEPT BY WRITTEN CONSENT
OF SPOTLESS WASH SOLUTIONS USA INC.
REPRODUCTION OF THIS DOCUMENT IS STRICTLY
PROHIBITED EXCEPT BY WRITTEN CONSENT OF
SPOTLESS WASH SOLUTIONS USA INC.
COPYRIGHT 2022
SPOTLESS WASH SOLUTIONS USA INC.
CHECKED:
DATE:
JOB NUMBER:
ISSUED FOR:
SHEET NUMBER:
SP
O
T
L
E
S
S
W
A
S
H
S
O
L
U
T
I
O
N
S
PO
B
O
X
5
4
5
6
TW
I
N
F
A
L
L
S
,
I
D
A
H
O
8
3
3
0
3
PH
.
(
2
0
8
)
8
4
1
-
4
5
2
4
DRAWN:
BI
N
D
I
N
G
02/15/2022
PERMIT REVIEW SET
NOT FOR CONSTRUCTION
21005
BUILDING PERMIT - NFC
A1.2
SLAB, TRENCH,
AND PIT GRADING
AS
NI
T
R
O
C
A
R
W
A
S
H
RE
X
B
U
R
G
,
I
D
13
7
1
N
2
N
D
E
RE
X
B
U
R
G
,
I
D
8
3
4
4
8
5/4/22
GENERAL NOTES
A. ABBREVIATIONS:
a. B.P. = BOTTOM OF PIT
b. B.T. = BOTTOM OF TRENCH
c. B.S. = BOTTOM OF STEP
d. C.P. = CENTER OF PIPE
e. C.I.P = CAST IN PLACE
f. I.E. = INVERT ELEVATION -FLOW LEVEL AT PIPE
g. T.T. = TOP OF TRENCH
B. ASSUMED ELEVATION 0.00 IS EQUAL TO ELEVATION TBD.
C. ALL PIPE / PIPE SLEEVE ELBOWS TO BE LONG SWEEP.
D. SEE PLUMBING PLAN FOR SANITARY PIPE LAYOUT AND CLEANOUTS.
E. PROVIDE MEDIUM BROOM CONCRETE FINISH AT ENTIRE CAR WASH TUNNEL. PROVIDE SMOOTH TROWEL
FINISH AT PASSENGER SIDE OF CONVEYOR TRENCH FOR THE FIRST 4' (1219mm) ADJACENT TO TRENCH
AND MEDIUM BROOM FINISH BEGINNING AT THE 4' MARK TO ADJACENT WALL. PROVIDE SMOOTH
TROWEL FINISH AT ALL OTHER INTERIOR CONCRETE LOCATIONS.
SHEET NOTES
#:DESCRIPTION:
1 SET TOP OF TRENCH DRAIN ASSEMBLY FLUSH WITH LOW POINT AT CONVEYOR TRENCH GUTTER
1/4" = 1'-0"
CONVEYOR TRENCH DETAIL2 1/2" = 1'-0"
CONVEYOR TRENCH SECTION3 3" = 1'-0"
FEMALE EMBED ANGLE4
3" = 1'-0"
MALE EMBED ANGLE5
NORTH
0'4'2'8'
3/16" = 1'-0"
SITE, TRENCH, AND PIT GRADING PLAN
KEYNOTES
MARK:DESCRIPTION:
22 14 26.19 PRESLOPED TRENCH DRAIN, ACO S200K WITH SLOTTED IRON 8" LOAD CLASS F GRATE
(OR APPROVED EQUAL)
22 14 26.23 TUNNEL TRENCH DRAIN ASSEMBLY, OWNER FURNISHED CONTRACTOR INSTALLED
3" = 1'-0"
GRATING SUPPORT ANGLE6
REVISIONS
#DATE
NOT
F
O
R
C
O
N
S
T
R
U
C
T
I
O
N
12
2
3
3
4
4
5
5
A
BB
CC
DD
4"
S
L
1
4"
S
L
1
4"
S
L
1
5'
-
6
"
5'
-
6
"
4' - 0"5' - 0"
4"
S
L
2
4"
S
L
2
4"
S
L
2
4' - 10"7' - 0"
7'
-
0
"
16' - 6"8' - 0"
9"1' - 5"
2' - 4"1' - 6"4' - 1"3' - 9"3' - 7"3' - 8"2' - 0"8' - 4 1/2"4' - 2"13' - 4 1/2"
4"
S
L
2
4"
S
L
2
4"
S
L
2
1' - 0"
4"
S
L
2
6"
R
W
2
4" D4
10"2' - 0"3' - 0"11' - 0"
4"
S
L
1
4" D2
4"
D
2
4" D2
WT
R
2"
D
2
22 14 26.19
22 14 26.19
6"
6"
1' - 4"
6"
6"
2' - 11"6"
8"
22 14 26.19
22 14 26.23
4"
S
L
2
6"
6" RW4
4"
S
L
1
SL
5
SL
5
4"
R
W
3
4" D6
SL
3
SL
3
SL
3
4"
4" D2
2" D2
10
"
D
1
2" D2
4" D22" D2
4" D2
4' - 10 1/2"4' - 5"
3"
17' - 1"
4"
S
L
4
6"
S
L
6
3 2 2 1 222222 2 2 2
2222
3
4"
D
2
8"
D
2
22 14 26.19 22 14 26.19
4"
R
W
3
6"
R
W
2
4"
D
4
4
5
6"
D
3
2' - 0"
2'
-
0
"
4"
D
4
2" D2
6" RW4
8"
D
2
1' - 0"6" RW4
3'
-
0
"
6
1
STAMP:
THESE DOCUMENTS HAVE BEEN PRODUCED AS AN
INSTRUMENT OF SERVICE AND ARE INTENDED SOLELY
FOR THE PURPOSE OF CONSTRUCTING, USING AND
MAINTAINING THE PROJECT. SPOTLESS WASH
SOLUTIONS USA INC, AS THE ARCHITECT OF RECORD
FOR THE PROJECT RETAINS OWNERSHIP OF THESE
DOCUMENTS.
ANY USE OF THESE DOCUMENTS OR USE OF THIS
DESIGN, IDEAS OR CONCEPTS DESCRIBED HEREIN IN
WHOLE OR PART BY ANY MEANS WHATSOEVER IS
STRICTLY PROHIBITED EXCEPT BY WRITTEN CONSENT
OF SPOTLESS WASH SOLUTIONS USA INC.
REPRODUCTION OF THIS DOCUMENT IS STRICTLY
PROHIBITED EXCEPT BY WRITTEN CONSENT OF
SPOTLESS WASH SOLUTIONS USA INC.
COPYRIGHT 2022
SPOTLESS WASH SOLUTIONS USA INC.
CHECKED:
DATE:
JOB NUMBER:
ISSUED FOR:
SHEET NUMBER:
SP
O
T
L
E
S
S
W
A
S
H
S
O
L
U
T
I
O
N
S
PO
B
O
X
5
4
5
6
TW
I
N
F
A
L
L
S
,
I
D
A
H
O
8
3
3
0
3
PH
.
(
2
0
8
)
8
4
1
-
4
5
2
4
DRAWN:
BI
N
D
I
N
G
02/15/2022
PERMIT REVIEW SET
NOT FOR CONSTRUCTION
Checker
21005
BUILDING PERMIT - NFC
A1.3
SLAB PLUMBING
PLAN
AS
NI
T
R
O
C
A
R
W
A
S
H
RE
X
B
U
R
G
,
I
D
13
7
1
N
2
N
D
E
RE
X
B
U
R
G
,
I
D
8
3
4
4
8
5/4/22
3/16" = 1'-0"
SLAB PLUMBING PLAN
PIPE SCHEDULE
#:DESCRIPTION:
D1 10" SCH40 PVC FROM TUNNEL TRENCH TO TRASH PIT
D2 SCH40 PVC DRAIN PIPE ASSEMBLY, SIZE AS INDICATED
D3 6" SCH40 PVC DRAIN FROM TUNNEL TRENCH DRAIN ASSEMBLY TO SAND/ OIL INTERCEPTOR
D4 4" SCH40 PVC DRAIN NETWORK TO SAND/ OIL INTERCEPTOR
D5 4" SCH40 PVC DRAIN FROM PRESLOPED TRENCH DRAIN TO SIDE WALL OF CONVEYOR TRENCH
D6 4" SCH40 PVC DRAIN FROM PRESLOPED TRENCH DRAIN TO SIDE WALL OF TRASH PIT
RW1 6" SCH80 PVC RECLAIM WATER HEADER PIPING FROM FILTER TO PUMPS AND TRENCH FLUSH
RW2 6" SCH80 PVC RECLAIM WATER FROM SUMP PUMP TO FILTER
RW3 4" SCH80 PVC RECLAIM WATER FROM NIGHT TIME SUMP PUMP. STUB UP AT EQUIPMENT ROOM AND CONNECT TO VERTICAL LEG OF RW4 PUMBING WITH WYE FITTING
ARRANGED FOR DOWNWARD FLOW AT 12" ABOVE SLAB
RW4 6" SCH40 PVC RECLAIM WATER TRENCH FLUSH PIPE ASSEMBLY. PROVIDE CONSTANT DOWNWARD SLOPE EACH DIRECTION FROM WYE FITTING AS ILLUSTRATED TO
SIDEWALL OF TRENCH. PIPE INVERT AT TRENCH TO BE 3" ABOVE GUTTER FLOOR OF TRENCH TO ACCOMMODATE WATERSTOP ASSEMBLIES.
RW5 8" SCH40 PVC RECLAIM WATER SANITARY TEE BETWEEN TANKS. PIPE INVERT AT EACH TANK TO BE SAME ELEVATION AS INLET PIPE RW1
SL1 4" SCH40 PVC SLEEVE STUB UP FROM EQUIPMENT ROOM TO SIDE WALL OF TRENCH
SL2 4" SCH40 PVC SLEEVE FROM SIDE WALL OF TRENCH TO STUB UP IN TUNNEL SLAB
SL3 1.5" SCH40 PVC PIPE SLEEVES FOR COMPRESSED AIR HOSE INSTALLATION BY OTHERS, PROVIDE 2 PIPES TO EACH TO LID OF RECLAIM TANKS <E013> & <E014> AS
ILLUSTRATED. SEE A7.1 RECLAIM SYSTEM DETAILS.
SL4 4" SCH40 SLEEVE FOR TIRE SHINE AIR AND CHEMICAL LINES
SL5 (2X) 1.5" SCH40 PVC SLEEVES FOR COMPRESSED AIR. STUB-UP INTO CLOSEST VACUUM ARCH STANCHION BASE AT ROW OF VACUUMS NEAREST THE BUILDING AND ALSO AT
ROW ACROSS LOT DRIVE FOR ARCHES NOTED AS FUTURE.
SL6 6" SCH40 PVC SLEEVE FROM CONVEYOR POWER PACK TO SIDE WALL OF CONVEYOR TRENCH
WTR LOCATION OF WATER SERVICE ENTERING BUILDING. SEE MECHNICAL PLANS FOR INTERIOR PIPE SIZE AND CONTINUATION INSIDE OF BUILDING AND CIVIL UTILITY PLAN FOR
EXTERIOR PIPE SIZE AND CONTINUATION ON SITE TO MUNICIPAL WATER SUPPLY SYSTEM.
B. ASSUMED ELEVATION 0.00 IS EQUAL TO ELEVATION (TO BE
DETERMINED).
C. ALL PIPE / PIPE SLEEVE ELBOWS TO BE LONG SWEEP.
D. SEE PLUMBING PLAN FOR SANITARY PIPE LAYOUT AND CLEANOUTS.
B.P. = BOTTOM OF PIT
B.T. = BOTTOM OF TRENCH
C.P. = CENTER OF PIPE
C.I.P = CAST IN PLACE
I.E. = INVERT ELEVATION (FLOW LEVEL AT PIPE)...
A. ABBREVIATIONS
GENERAL NOTES
NORTH
0'4'2'8'
SHEET NOTES
#:DESCRIPTION:
1 SET PIPE INVERT 1/2" LOWER THAN BOTTOM OF TRENCH
2 SET PIPE INVERT15" BELOW TOP OF TRENCH
3 SET PIPE INVERT 3" ABOVE BOTTOM OF TRENCH SO NO MUD WILL COLLECT
4 10" TO 6" ECCENTRIC REDUCER
5 22.5 DEGREE LONG-SWEEP ELBOW
6 ROUTE TO FRENCH DRAIN
KEYNOTES
MARK:DESCRIPTION:
22 14 26.19 PRESLOPED TRENCH DRAIN, ACO S200K WITH SLOTTED IRON 8" LOAD CLASS F
GRATE (OR APPROVED EQUAL)
22 14 26.23 TUNNEL TRENCH DRAIN ASSEMBLY, OWNER FURNISHED CONTRACTOR
INSTALLED
REVISIONS
#DATE
1 5/4/22
1
NOT
F
O
R
C
O
N
S
T
R
U
C
T
I
O
N
4'
-
3
"
(
C
O
N
F
I
R
M
W
I
T
H
O
W
N
E
R
)
GALVANIZED ANGLES AND
P1000 SHAPES AND
FASTENERS AS REQUIRED
TO SUPPORT HORIZONTAL
UNISTRUT SHELVES
VERTICAL SUPPORTS AND
CROSS MEMBERS AT 5'-0"
OC MAXIMUM SPACING
COMPLETE 1-5/8"
GLAVANIZED UNISTRUT
METAL FRAMING SYSTEM
EXPANSION
ANCHORS INTO
CONCRETE AS
REQUIRED
2' - 0"
PE
R
O
W
N
E
R
PE
R
O
W
N
E
R
2'
-
3
"
±
CA
SCW
ICW
SHW
HOTSY
PLUMBING
BY GC
4"
3
1
/
2
"
4
"
4
"
5
"
4
"
MOUNT PIPES ON OWNER
PROVIDED UNISTRUT RACK
WITH "CUSH-A-CLAMP"
CHANNEL MOUNTING
SYSTEM TO SUPPORTS AT
5'-0" ON CENTER MAX.
NOTE: OWNER INSTALLED
CEILING UNISTRUT IS FOR
SUPPORT OF OWNER
INSTALLED ITEMS ONLY AND
MAY ONLY BE UTILZED BY
CONTRACTOR WITH WRITTEN
AUTHORIZATION BY
ARCHITECT.
SHW
NOTE: REFER TO EQUIPMENT
PLAN FOR EXACT SPACING AND
LAYOUT. FAILURE TO
COORDINATE WILL BE THE
RESPONSIBILITY OF THE
CONTRACTOR TO RELOCATE
ANY AND ALL PIPING.
NOTE: DO NOT INSTALL VALVES
UNTIL EQUIPMENT IS SET IN
FINAL PLACE AND LOCATION OF
VALVE IS CONFIRMED WITH
OWNER
MOUNT PIPES ON OWNER
PROVIDED UNISTRUT RACK WITH
"CUSH-A-CLAMP"CHANNEL
MOUNTING SYSTEM TO SUPPORTS
AT 5'-0" ON CENTER MAX.
ROUTE COMPRESSED AIR
TAKE-OFFS FROM TOP OF
MAIN LINE. INSTALL BALL
VALVE AT THE END OF MAIN
LINE FOR CONDENSATE DRAIN CA
ICW
SCW
SHW
BALL VALVES TO
BE INSTALLED AT
+78" ABOVE SLAB
FEMALE THREADED BALL VALVES
FOR FUTURE CONNECTION BY
OWNER.
SEE PLAN FOR SIZING AND
PLACEMENT REQUIREMENTS
NOTE: NOT ALL PIPES
ARE SHOWN IN
ISOMETRIC SKETCH
2" SHW
1.5" ICW
1.5"1.5"1.5"
1.
5
"
R
R
1" CA
1.5" SHW
1.5" SCW
3"
I
C
W
1.
5
"
I
C
W
1.5" ICW1.5" ICW
2" SCW
2"
S
C
W
0.75" CA
0.
7
5
"
C
A
1
9 9 9
11
2348
7
56
10
1.25" SCW
1.5"0.5"0.5"
1' - 4"
1.5" SHW
A1.5
1
2"1.5"1.5"
0.75"0.75"1"1"
5
0.75" 0.75"0.75"0.5"
2"
1.5"2"1.5"
16"
1.5"
1.5" 1.5"
10
10
10
10
3" ICW
2
A1.5
T/O FLOOR
100' -0"
6" RW1
0.
5
"
C
A
0.75" CA1" CA
1"
C
A
0.
7
5
"
C
A
0.
7
5
"
C
A
0.
7
5
"
C
A
0.
7
5
"
C
A
0.
7
5
"
C
A
E410
E201
E112
E406
E402
E405 E404
E401
E403
E502 E501
E102 E103 E101
E107 E106
E020
E830
6"
R
W
1
6"
R
W
1
6"
R
W
1
6"
R
W
4
4"
S
L
1
4"
R
W
3
4"
S
L
1
4"
S
L
1
4"
S
L
1
4"
S
L
1
6"
S
L
6
4"
S
L
4
4"
D
2
1.
5
"
S
L
5
1.
5
"
S
L
5
2"
D
2
E4
2
2
E4
2
1
1.
5
"
S
H
W
1.
5
"
S
C
W
1.
5
"
S
H
W
1.
5
"
S
C
W
2"
S
C
W
1.
5
"
S
H
W
2"
S
H
W
2"
I
C
W
2"
I
C
W
1.
5
"
I
C
W
1.
5
"
I
C
W
E301E302
E201a
E840
E108
1.
5
"
R
W
1
4"
D
4
6"
R
W
2
4"
D
4
1"
C
A
7
5
6
1110
1.5" RR
106
EQUIPMENT
2
A1.5
4' - 0"
5' - 9"
6' - 6"
7' - 3"
4' - 9"
6' - 9"
T/O FLOOR
100' -0"
E930E002E001b
UH-1
E109 E110
E030b
E111
E003a
UH-2
2"
D
2
4"
D
2
1.
5
"
S
L
3
1.
5
"
S
L
3
1.
5
"
S
L
3
E003b
1.
5
"
R
R
1"
S
C
W
0.
7
5
"
S
C
W
2"
S
C
W
2"
S
H
W
2"
I
C
W
2"
I
C
W
3"
I
C
W
2"
0.
5
"
C
A
E920
4"
W
T
R
4"
D
4
4"
D
2
1.
5
"
S
H
W
1.5" SL51.5" SL54" RW36" RW2
E030
E004
OH106
106a
22 42 16.1
22 14 26.19
1
2
3
4 8
106
EQUIPMENT
105
CLEAN
EQUIPMENT
2' - 0"
6' - 0"
8' - 2"
7' - 2"
5' - 0"
6' - 6"
STAMP:
THESE DOCUMENTS HAVE BEEN PRODUCED AS AN
INSTRUMENT OF SERVICE AND ARE INTENDED SOLELY
FOR THE PURPOSE OF CONSTRUCTING, USING AND
MAINTAINING THE PROJECT. SPOTLESS WASH
SOLUTIONS USA INC, AS THE ARCHITECT OF RECORD
FOR THE PROJECT RETAINS OWNERSHIP OF THESE
DOCUMENTS.
ANY USE OF THESE DOCUMENTS OR USE OF THIS
DESIGN, IDEAS OR CONCEPTS DESCRIBED HEREIN IN
WHOLE OR PART BY ANY MEANS WHATSOEVER IS
STRICTLY PROHIBITED EXCEPT BY WRITTEN CONSENT
OF SPOTLESS WASH SOLUTIONS USA INC.
REPRODUCTION OF THIS DOCUMENT IS STRICTLY
PROHIBITED EXCEPT BY WRITTEN CONSENT OF
SPOTLESS WASH SOLUTIONS USA INC.
COPYRIGHT 2022
SPOTLESS WASH SOLUTIONS USA INC.
CHECKED:
DATE:
JOB NUMBER:
ISSUED FOR:
SHEET NUMBER:
SP
O
T
L
E
S
S
W
A
S
H
S
O
L
U
T
I
O
N
S
PO
B
O
X
5
4
5
6
TW
I
N
F
A
L
L
S
,
I
D
A
H
O
8
3
3
0
3
PH
.
(
2
0
8
)
8
4
1
-
4
5
2
4
DRAWN:
BI
N
D
I
N
G
02/15/2022
PERMIT REVIEW SET
NOT FOR CONSTRUCTION
21005
BUILDING PERMIT - NFC
A1.5
WASH EQUIPMENT
PLUMBING PLAN
AS
NI
T
R
O
C
A
R
W
A
S
H
RE
X
B
U
R
G
,
I
D
13
7
1
N
2
N
D
E
RE
X
B
U
R
G
,
I
D
8
3
4
4
8
5/4/22
GENERAL NOTES
A. SEE P-SERIES PLUMBING DRAWINGS FOR CONTINUATION AND ADDITIONAL
REQUIREMENTS.
B. SEE SLAB, TRENCH & PIT GRADING PLAN A1.2b FOR ADDITIONAL BENEATH SLAB
SLEEVES AND PIPING.
C. COORDINATE SEQUENCING AND INSTALLATION OF EQUIPMENT POWER AND
PLUMBING SYSTEMS WITH OWNER'S CONSTRUCTION FORCES.
D. PROVIDE ALL INDICATED CONDUITS AND VALVES FOR ALL EQUIPMENT INDICATED
ON EQUIPMENT SCHEDULE TO BE "FUTURE".
E. ALL PIPING TO BE GRADE L COPPER UNLESS SPECIFICALLY DESIGNATED
OTHERWISE BELOW.
F. ALL COPPER PIPE SHALL INCORPORATE BRAZED COPPER FITTINGS.
G. ALL BALL VALVES TO BE FEMALE PIPE THREAD, BRASS BODIED, FULL PORT.
H. PIPE INSULATION SHALL BE PROVIDED AT HOT WATER PIPING AND EXTERIOR
IN-GROUND PIPING THAT IS LESS THAN 36" BURIAL DEPTH OR FROST LINE.
I. PIPE INSULATION PROVIDED SHALL BE 1" FOR PIPES UP TO AND INCLUDING 2"
IN DIAMETER, AND 1.5" FOR PIPES MORE THAN 2" IN DIAMETER.
J. ABBREVIATIONS:
CA COMPRESSED AIR: RAPIDAIR FASTPIPE SYSTEM AND COMPRESSION
FITTINGS. USE MAXLINE WHEN INDICATED TO RUN IN UNDERGROUND
PVC SLEEVE.
HOTSY HOTSY PRESSURE WASHING SYSTEM: PROVIDE 1/2" 4000PSI BLACK
HIGH PRESSURE HOT WATER HOSE AND FITTINGS. PROVIDE CUSH-A-
CLAMP UNISTRUT SUPPORT
ICW INDUSTRIAL COLD WATER: GRADE L COPPER PIPE
RO REVERSE OSMOSIS WATER: GRADE L COPPER
RR RO REJECT RECOVERY WATER: GRADE L COPPER
RW RECLAIM WATER: GRADE L COPPER
SCW SOFT COLD WATER: GRADE L COPPER
SHW SOFT HOT WATER: GRADE L COPPER
SHWU SOFT HOT WATER UNDER SLAB: GRADE K COPPER
VAC VACUUM PIPING: PROVIDE SOLID CORE PVC
NPT NATIONAL PIPE THREAD
LEGEND
HOSE BIB 'HB-1'. PROVIDE & INSTALL 3/4" THREADED OUTLET BALL
VALVE. INSTALL AT 66" ABOVE SLAB UNLESS OTHERWISE NOTED ON
PLANS. ADDITIONAL HOSE BIBS ARE SPECIFIED ON SHEET PLUMBING
PLANS.
BALL VALVE. PROVIDE FEMALE PIPE THREAD UNITS -SEE DETAIL 3 FOR
VALVE WITH DROP STEM MOUNTING.
TEST & DRAIN BALL VALVE.
SHUT-OFF BALL VALVE.
ELBOW. PROVIDE QUANTITY AS REQUIRED.
TEE.
DOUBLE TEE.
MAKE PLUMBING CONNECTION.
HEAT EXCHANGER ON POWER PACK UNIT -OWNER FURNISH,
CONTRACTOR INSTALLED
MIXING VALVE
T/D
1 : 10
UNISTRUT RACK BY OWNER2
12" = 1'-0"
PIPE AND BALL VALVE MOUNTING3
3/16" = 1'-0"
WASH EQUIPMENT PLUMBING PLAN
NORTH
0'4'2'8'
3/16" = 1'-0"
PLUMBING - EQUIPMENT NORTH1
3/16" = 1'-0"
PLUMBING - EQUIPMENT SOUTH5
PIPE SCHEDULE
#:DESCRIPTION:
SCW SOFT COLD WATER
SHW SOFT HOT WATER
SL1 4" SCH40 PVC SLEEVE STUB UP FROM EQUIPMENT ROOM TO SIDE WALL OF TRENCH
SL3 1.5" SCH40 PVC PIPE SLEEVES FOR COMPRESSED AIR HOSE INSTALLATION BY OTHERS, PROVIDE 2 PIPES TO
EACH TO LID OF RECLAIM TANKS <E013> & <E014> AS ILLUSTRATED. SEE A7.1 RECLAIM SYSTEM DETAILS.
SL4 4" SCH40 SLEEVE FOR TIRE SHINE AIR AND CHEMICAL LINES
SL5 (2X) 1.5" SCH40 PVC SLEEVES FOR COMPRESSED AIR. STUB-UP INTO CLOSEST VACUUM ARCH STANCHION
BASE AT ROW OF VACUUMS NEAREST THE BUILDING AND ALSO AT ROW ACROSS LOT DRIVE FOR ARCHES
NOTED AS FUTURE.
SL6 6" SCH40 PVC SLEEVE FROM CONVEYOR POWER PACK TO SIDE WALL OF CONVEYOR TRENCH
WTR LOCATION OF WATER SERVICE ENTERING BUILDING. SEE MECHNICAL PLANS FOR INTERIOR PIPE SIZE AND
CONTINUATION INSIDE OF BUILDING AND CIVIL UTILITY PLAN FOR EXTERIOR PIPE SIZE AND CONTINUATION
ON SITE TO MUNICIPAL WATER SUPPLY SYSTEM.
PIPE SCHEDULE
#:DESCRIPTION:
CA COMPRESSED AIR
D2 SCH40 PVC DRAIN PIPE ASSEMBLY, SIZE AS INDICATED
D4 4" SCH40 PVC DRAIN NETWORK TO SAND/ OIL INTERCEPTOR
ICW INDUSTRIAL COLD WATER
RR RO REJECT RECOVERY
RW1 6" SCH80 PVC RECLAIM WATER HEADER PIPING FROM FILTER TO PUMPS AND TRENCH FLUSH
RW2 6" SCH80 PVC RECLAIM WATER FROM SUMP PUMP TO FILTER
RW3 4" SCH80 PVC RECLAIM WATER FROM NIGHT TIME SUMP PUMP. STUB UP AT EQUIPMENT ROOM AND
CONNECT TO VERTICAL LEG OF RW4 PUMBING WITH WYE FITTING ARRANGED FOR DOWNWARD FLOW AT 12"
ABOVE SLAB
RW4 6" SCH40 PVC RECLAIM WATER TRENCH FLUSH PIPE ASSEMBLY. PROVIDE CONSTANT DOWNWARD SLOPE
EACH DIRECTION FROM WYE FITTING AS ILLUSTRATED TO SIDEWALL OF TRENCH. PIPE INVERT AT TRENCH
TO BE 3" ABOVE GUTTER FLOOR OF TRENCH TO ACCOMMODATE WATERSTOP ASSEMBLIES.
SHEET NOTES
# DESCRIPTION
1 SEE P-SERIES PLUMBING DRAWINGS FOR CONTINUATION
2 SEE PLUMBING DRAWINGS FOR WATER SERVICE BACKFLOW PREVENTERS, INSTALL
PARALLEL TO WALL IN SHORTEST REASONABLE LENGTH.
3 SEE PLUMBING DRAWINGS FOR WATER SOFTENER SYSTEM (2" PRE-PLUMBED
PIPING MANIFOLD.
4 SEE PLUMBING DRAWINGS FOR BOILER DETAIL. SYSTEM INCLUDES PRE-PLUMBED
MANIFOLD & SKID.
5 SEE SHEET A1.2 FOR UNDERGROUND COMPRESSED AIR PIPING FROM AIR DRYER
TO VACUUM ARCH BASES. PROVIDE SHUT-OFF BALL VALVE TO EACH OF (2) PIPES.
6 BALL VALVE FOR EXTENSION TO FUTURE AIR VALVES AT BLOWER ROOM FANS.
7 CONNECT (2) AIR COMPRESSORS TO SINGLE AIR DRYER & PROVIDE BYPASS LOOP
AROUND AIR DRYER. SEE PLUMBING DETAIL.
8 SEE PLUMBING DRAWINGS FOR ICE MELT BOILER DETAIL. SYSTEM INCLUDES RACK
AND PRE-PLUMBED SYSTEM MANIFOLD.
9 PIPING TO TUNNEL BALL VALVES SHALL SLOPE DOWN TO VALVE, SO TUNNEL PIPING
CAN BE DRAINED EASILY, TYPICAL. INSTALL VALVES AT +48".
10 MOUNT PIPE OR GROUP OF PIPES AS OCCURS TO OWNERS UNISTRUT RACK
SYSTEM PER DETAILS 2 & 3, TYPICAL AT SOUTH WALL.
11 INSTALL AND SUPPORT OWNER FURNISHED 6" SCH80 RECLAIM DELIVERY MANIFOLD
KIT FROM RECLAIM FILTER TO 6" STUB-UP PLUMBING. SEE A1.2b FOR LOCATION OF
UNDERGROUND STUB-UP LOCATION.
REVISIONS
#DATE
NOT
F
O
R
C
O
N
S
T
R
U
C
T
I
O
N
STAMP:
THESE DOCUMENTS HAVE BEEN PRODUCED AS AN
INSTRUMENT OF SERVICE AND ARE INTENDED SOLELY
FOR THE PURPOSE OF CONSTRUCTING, USING AND
MAINTAINING THE PROJECT. SPOTLESS WASH
SOLUTIONS USA INC, AS THE ARCHITECT OF RECORD
FOR THE PROJECT RETAINS OWNERSHIP OF THESE
DOCUMENTS.
ANY USE OF THESE DOCUMENTS OR USE OF THIS
DESIGN, IDEAS OR CONCEPTS DESCRIBED HEREIN IN
WHOLE OR PART BY ANY MEANS WHATSOEVER IS
STRICTLY PROHIBITED EXCEPT BY WRITTEN CONSENT
OF SPOTLESS WASH SOLUTIONS USA INC.
REPRODUCTION OF THIS DOCUMENT IS STRICTLY
PROHIBITED EXCEPT BY WRITTEN CONSENT OF
SPOTLESS WASH SOLUTIONS USA INC.
COPYRIGHT 2022
SPOTLESS WASH SOLUTIONS USA INC.
CHECKED:
DATE:
JOB NUMBER:
ISSUED FOR:
SHEET NUMBER:
SP
O
T
L
E
S
S
W
A
S
H
S
O
L
U
T
I
O
N
S
PO
B
O
X
5
4
5
6
TW
I
N
F
A
L
L
S
,
I
D
A
H
O
8
3
3
0
3
PH
.
(
2
0
8
)
8
4
1
-
4
5
2
4
DRAWN:
BI
N
D
I
N
G
02/15/2022
PERMIT REVIEW SET
NOT FOR CONSTRUCTION
21005
BUILDING PERMIT - NFC
A1.6a
EQUIPMENT
SCHEDULE
AS
NI
T
R
O
C
A
R
W
A
S
H
RE
X
B
U
R
G
,
I
D
13
7
1
N
2
N
D
E
RE
X
B
U
R
G
,
I
D
8
3
4
4
8
5/4/22
E100 PUMPS AND MOTORS
ITEM DESCRIPTION UNLOADED FURNISHED
SET IN
PLACE INSTALLED
CONDUIT
OH / UG
POWER
VOLTAGE (V)
CONTROL
VOLTAGE
TUNNEL
CONTROL
FUNCTION
CONTROL WIRE
SPECIFICATION
CONTROL WIRE QUANTITY/
TYPE
CONTROL CONNECTION
TYPE
CONTROL FED FROM/ FEEDS
TO POWER FEED FROM/FEEDS TO HARDWIRE
PROVIDE
CONDUIT(S)
PROVIDE
VALVES PLUMBING IN
PLUMBING IN
PIPE SIZE
PLUMBING
OUT
PLUMBING
OUT PIPE SIZE
STARTUP
TEST
BALANCE MOUNTING COMMENTS
E101 PUMP HFX; HSW PUMP 1;GC O O O UG 480VAC - 0 PREWIRED PREWIRED PREWIRED PREWIRED HA/ UNIT VFD/ MOTOR GC GC O 2" O 2" O FRAME/ SLAB GRUNDFOS CRE10-10 N-GJ-A-E-HQQE
E101a PRESSURE TRANSDUCER - O - GC UG - 24VDC 0 SOUTHWIRE
MCTC-18-3S-1
1/SENSOR CABLE TERMINAL BLOCK MCC/ TRANSDUCER - GC GC - - -- - - -
E102 PUMP HFX; HSW PUMP 2;GC O O O UG 480VAC 0 PREWIRED PREWIRED PREWIRED PREWIRED HA/ UNIT VFD/ MOTOR GC GC O 2" O 2" O FRAME/ SLAB GRUNDFOS CRE10-10 N-GJ-A-E-HQQE
E102a PRESSURE TRANSDUCER - O - GC UG - 24VDC 0 SOUTHWIRE
MCTC-18-3S-1
1/SENSOR CABLE TERMINAL BLOCK MCC/ TRANSDUCER - GC GC - - -- - - - -
E103 BACK-UP PUMP; (FUTURE) NO CONNECTIONS - O O O - - - 0 - - - - - - - - - - - - - - -
E103a PRESSURE TRANSDUCER O - GC UG - 24VDC 0 SOUTHWIRE
MCTC-18-3S-1
1/SENSOR CABLE TERMINAL BLOCK MCC/ TRANSDUCER - GC GC - - -- - - - -
E104 PUMP; SUMP RECLAIM; MAIN SUPPLY GC O GC GC UG 480VAC - 0 PREWIRED PREWIRED PREWIRED PREWIRED CWMS VFD/ MOTOR GC GC - - - GC 6" O TANK MAKE SURE PUMP MOTOR ROTATES IN CORRECT DIRECTION
E104a PRESSURE TRANSDUCER O - GC UG - 24VDC 1/SENSOR CABLE TERMINAL BLOCK MCC/ TRANSDUCER - GC GC - - -- - - RECLAIM MAIN
E104a LOW LEVEL FLOAT; SUMP RECLAIM O O GC GC UG - 4-20mA 0 SOUTHWIRE
MCTC-18-3S-1
1/SENSOR CABLE TERMINAL BLOCK MCC TC CWMS/ METER GC GC - -- - - - TANK
E104b MOTOR HEAT SENSOR ON PUMP - O - - UG - - 0 - - - - - GC GC - - - - - - TANK
E105 PUMP; SUMP RECLAIM; AT NIGHT TRENCH FLUSH GC O GC GC UG 480VAC - 0 PREWIRED PREWIRED PREWIRED PREWIRED CWMS STARTER/ MOTOR GC GC - - - GC 4" O TANK
E106 PUMP; RECLAIM HIGH PRESSURE GC O GC O UG 480VAC - 1 PREWIRED PREWIRED PREWIRED PREWIRED VFD/ MOTOR GC GC 3" GC (2) 1.5" GC 1" SS O SLAB
E107 PUMP; RECLAIM HIGH PRESSURE GC O GC O UG 480VAC - 1 PREWIRED PREWIRED PREWIRED PREWIRED VFD/ MOTOR GC GC 3" GC (2) 1.5" GC 1" SS O SLAB
E108 PUMP; MUD BLAST GC O GC O UG 480VAC - 1 PREWIRED PREWIRED PREWIRED PREWIRED MCC VFD/ MOTOR GC GC 3" GC 3" GC 1.25" SS O SLAB GRUNDFOS CR 45-5-2 A-G-A-E-HQQE
E108a PRESSURE TRANSDUCER GC O - GC UG - 24VDC 0 SOUTHWIRE
MCTC-18-3S-1
1/SENSOR CABLE TERMINAL BLOCK MCC/ TRANSDUCER - GC GC - - -- - - PUMP
E109 PUMP; RO PRODUCTION - O - O UG 480VAC - 0 - - PREWIRED - - GC GC - - - - - - SKID
E109a LOW/HIGH LEVEL FLOAT - O - O OH 480VAC - 0 - - - - - - GC - - - - - - TANK
E110 PUMP; RO DELIVERY - O - O UG 480VAC - 1 - - PREWIRED - - GC GC - - - - - - SKID
E111 PUMP; RO REJECT RECOVERY - O - O UG 480VAC - 0 - - - - - GC GC - - - - - - SLAB
E111a LOW LEVEL FLOAT; RO REJECT RECOVERY - O - O OH - - 0 - - - - - - GC - - - - - - TANK
E112 PUMP; PRESSURE WASHER W/ WALL BRACKET GC O GC O UG 480VAC - 0 - - - - HA/ UNIT STARTER GC GC 1.5" HSW GC 1" TYPE K O 0.5" SS O WALL (BRACKET) AALADIN 443-SS W/ SOAP CONTAINER AND CLUTCH
E121 MOTOR, TOP BRUSH GC O O O OH 480VAC 1 PREWIRED PREWIRED PREWIRED PREWIRED MCC1 VFD/ MOTOR GC GC - - - - - O ARCH PECO ELECTRIC MOTOR IN TUNNEL
E122a MOTOR, WRAPS 1 DS GC O O O UG 480VAC - 1 PREWIRED PREWIRED PREWIRED PREWIRED MCC1 VFD/ MOTOR GC GC - - - - - O ARCH PECO ELECTRIC MOTOR IN TUNNEL
E122b MOTOR, WRAPS 1 PS GC O O O UG 480VAC - 1 PREWIRED PREWIRED PREWIRED PREWIRED MCC1 VFD/ MOTOR GC GC - - - - - O ARCH PECO ELECTRIC MOTOR IN TUNNEL
E123a MOTOR, ROCKER 1 PS GC O O O UG 480VAC - 1 PREWIRED PREWIRED PREWIRED PREWIRED MCC1 VFD/ MOTOR GC GC - - - - - O PEDESTAL PECO ELECTRIC MOTOR IN TUNNEL
E123b MOTOR, ROCKER 1 DS GC O O O UG 480 - 1 PREWIRED PREWIRED PREWIRED PREWIRED MCC1 VFD/ MOTOR GC GC - - - O PEDESTAL PECO ELECTRIC MOTOR IN TUNNEL
E124a MOTOR, ROCKER 2 PS GC O O O UG 480VAC - 1 PREWIRED PREWIRED PREWIRED PREWIRED MCC1 VFD/ MOTOR GC GC - - - - - O PEDESTAL PECO ELECTRIC MOTOR IN TUNNEL
E124b MOTOR, ROCKER 2 DS GC O O O UG 480VAC - 1 PREWIRED PREWIRED PREWIRED PREWIRED MCC1 VFD/ MOTOR GC GC - - - - - O PEDESTAL PECO ELECTRIC MOTOR IN TUNNEL
E125 MOTOR, TOP BRUSH 2 GC O O O OH 480VAC - 1 PREWIRED PREWIRED PREWIRED PREWIRED MCC1 VFD/ MOTOR GC GC - - - - - O ARCH PECO ELECTRIC MOTOR IN TUNNEL
E126a MOTOR, WRAPS 2 DS GC O O O OH 480VAC - 1 PREWIRED PREWIRED PREWIRED PREWIRED MCC1 VFD/ MOTOR GC GC - - - - - O ARCH PECO ELECTRIC MOTOR IN TUNNEL
E126b MOTOR, WRAPS 2 PS GC O O O OH 480VAC - 1 PREWIRED PREWIRED PREWIRED PREWIRED MCC1 VFD/ MOTOR GC GC - - - - - O ARCH PECO ELECTRIC MOTOR IN TUNNEL
E127a MOTOR, TIRE SHINE DS GC O O O UG 480VAC - 1 PREWIRED PREWIRED PREWIRED PREWIRED MCC1 VFD/ MOTOR GC GC - - - - - O EQUIP PECO ELECTRIC MOTOR IN TUNNEL
E127b MOTOR, TIRE SHINE PS GC O O O UG 480VAC - 1 PREWIRED PREWIRED PREWIRED PREWIRED MCC1 VFD/ MOTOR GC GC - - - - - O EQUIP PECO ELECTRIC MOTOR IN TUNNEL
E130 MOTOR; SPEED DOOR & CONTROL BOX; EXIT GC O O O UG 480VAC 1 14/3 SHIELDED 3 CONDUCTOR SHIELDED x2 MCC1 TC/ UNIT CONTROLLER HA/ UNIT VFD/ MOTOR GC GC - - - - - O WALL RYTEC PREDADOOR; VFD ON WALL NEXT TO DOOR
E000 WATER PROCESSING / BOILER SYSTEMS
ITEM DESCRIPTION UNLOADED FURNISHED
SET IN
PLACE INSTALLED
CONDUIT
OH / UG
POWER
VOLTAGE (V)
CONTROL
VOLTAGE HARDWIRE
WIRE DEVICE TO
CONTROLLER
PROVIDE
CONDUIT(S)PLUMBING IN
PLUMBING IN
PIPE SIZE
PLUMBING
OUT
PLUMBING
OUT PIPE SIZE
STARTUP
TEST
BALANCE MOUNTING COMMENTS
E001a BACKFLOW PREVENTER; 3" (PROCESS WATER) - GC GC GC -- - - - - GC 3" GC 3" - - INSTALL RPBP'S IN PARALLEL
E001b BACKFLOW PREVENTER; 1 1/2" (DOMESTIC) - GC GC GC - -- - - - GC 1.5" GC 1.5" - - INSTALL RPBP'S IN PARALLEL
E002 WATER SOFTENER SYSTEM; DU-PLEX GC O GC GC UG (2) 120VAC - GC PREWIRED GC GC 2" GC 2" GC SLAB VWW VS2-2000-210 - SKID MOUNTED
E003a BOILER: UHE; ICE MELT GC O GC GC UG 120VAC - GC PREWIRED GC GC 1.5" GC 1.5" GC SLAB 400,000 BTU
E003b ICE MELT MANIFOLDS; MULTIPLE - SEE PLAN - O - - - - -- - - - - - - - SLAB SEE VENDORS DESIGN
E003c ICE MELT SENSOR - O - - UG - 4-20mA GC GC GC - - - - - PAVING SEE VENDORS DESIGN
E003d THERMOSTAT SENSOR - O GC GC OH - 4-20mA GC GC GC - - - - - PAVING SEE VENDORS DESIGN
E004 BOILER; UHE; WATER GC O GC GC UG 120VAC - GC GC GC GC 2" GC 2" GC SLAB 400,000 BTU
E010 TRENCH TRASH COLLECTION DRAIN; SWIRLY GC O GC GC - - -- - - GC - GC 10" - TRENCH FORM IN AND POUR IN PLACE WITH TUNNEL
CONVEYOR TRENCH CONCRETE
E011 TANK 1; RECLAIM; 3,000 GA GC GC GC GC - - - - - GC 12" GC 8" - GROUND SEE SHEET A7.1
E012 TANK 2; RECLAIM; 3,000 GA GC GC GC GC - - - - - GC 8" GC 8" - GROUND SEE SHEET A7.1
E013 TANK 3; RECLAIM; 3,000 GA GC GC GC GC - - - - - GC 8" GC 8" - GROUND SEE SHEET A7.1
E014 TANK 4; SAND/ OIL INTERCEPTOR; 3,000 GA GC GC GC GC - - - - - GC 8" GC 8" - GROUND SEE SHEET A7.1
E020 RECLAIM FILTER, 115VAC; 60HZ GC O GC O UG 120VAC GC GC GC 6" GC 6" - SLAB NETAFIM; APOLLO, 5 UNIT TWIN, 4" WASTE
E030 RO UNIT SKID; 14,400 GPD GC O GC O UG - 4-20mA - - - GC 1" GC 1" SLAB -
E030a RO CARBON FILTER (GAC)- O O O UG - - - - - - - - SKID -
E030b RO PREFILTER - O O O -- - - - - - - - SKID -
E030c RO STORAGE TANK 1; 1,500 GA GC O O O -- - - GC GC - SLAB -
E030d RO REJECT TANK 2; 1,500 GA GC O O O -- - - GC GC - SLAB -
E200 HYDRAULICS
ITEM DESCRIPTION UNLOADED FURNISHED
SET IN
PLACE INSTALLED
CONDUIT
OH / UG
POWER VOLTAGE
(V)
CONTROL
VOLTAGE
TUNNEL
CONTROL
FUNCTION CONTROL WIRE SIZE/ TYPE
CONTROL WIRE QUANTITY/
TYPE CONTROL CONNECTION TYPE
CONTROL FED FROM/ FEEDS
TO POWER FEED FROM/FEEDS TO HARDWIRE
WIRE DEVICE TO
CONTROLLER
PROVIDE
CONDUIT(S)PLUMBING IN
PLUMBING
OUT
STARTUP
TEST
BALANCE MOUNTING COMMENTS
E201 PUMP, HYDRAULIC, CONVEYOR GC O GC O UG 480VAC - 1 PREWIRED PREWIRED PREWIRED PREWIRED MCC VFD/ MOTOR GC GC GC O O O SLAB
E201a LOW OIL SENSOR - O - O UG - 24VAC 1 SOUTHWIRE MCTC-18-3S-1 1/SENSOR CABLE CEE CONDUIT BODY/FLEXIBLE
CONDUIT/JBOX
TC/ JBOX-CONDULET MCC CONTROLLER/ UNIT GC GC GC - - - NEEDS A SEPARATE CONDUIT TO MCC ; MULTIPLE LOW OIL LINES CAN SHARE
CONDUIT WHEN EQUIPMENT IS ADJACENT TO ONE-ANOTHER.
E300 AIR MOVEMENT
ITEM DESCRIPTION UNLOADED FURNISHED
SET IN
PLACE INSTALLED
CONDUIT OH /
UG
POWER
VOLTAGE (V)
CONTROL
VOLTAGE
TUNNEL
CONTROL
FUNCTION CONTROL WIRE SIZE/ TYPE
CONTROL WIRE QUANTITY/
TYPE CONTROL CONNECTION TYPE
CONTROL FED FROM/ FEEDS
TO POWER FEED FROM/FEEDS TO HARDWIRE
WIRE DEVICE TO
CONTROLLER
PROVIDE
CONDUIT(S) PROVIDE VALVES PLUMBING IN
PLUMBING
OUT
STARTUP
TEST
BALANCE MOUNTING COMMENTS
E301 AIR COMPRESSOR 1 GC O GC O UG 480VAC 0 - - - - HA/ UNIT STARTER GC - GC O O O O SLAB CONNECT BOTH COMPRESSORS FROM 3/4" HOSE INTO SINGLE 1" LINE
E302 AIR COMPRESSOR 2 GC O GC O UG 480VAC 0 - - - - HA/ UNIT STARTER GC - GC O O O O SLAB CONNECT BOTH COMPRESSORS FROM 3/4" HOSE INTO SINGLE 1" LINE
E303a BLOWER 1 GC O O O OH 480VAC 1 MCC PREWIRED MCC PREWIRED MCC PREWIRED MCC PREWIRED MCC/ MOTOR GC - GC O - - - BEAM HEAD SYSTEMS
E303b BLOWER 2 GC O O O OH 480VAC 1 MCC PREWIRED MCC PREWIRED MCC PREWIRED MCC PREWIRED MCC/ MOTOR GC - GC O - - - BEAM HEAD SYSTEMS
E303c BLOWER 3 GC O O O OH 480VAC 1 MCC PREWIRED MCC PREWIRED MCC PREWIRED MCC PREWIRED MCC/ MOTOR GC - GC O - - - BEAM HEAD SYSTEMS
E303d BLOWER 4 GC O O O OH 480VAC 1 MCC PREWIRED MCC PREWIRED MCC PREWIRED MCC PREWIRED MCC/ MOTOR GC - GC O - - - BEAM HEAD SYSTEMS
E303e BLOWER 5 GC O O O OH 480VAC - 1 MCC PREWIRED MCC PREWIRED MCC PREWIRED MCC PREWIRED MCC/ MOTOR GC - GC O - - - BEAM HEAD SYSTEMS
E303f BLOWER 6 GC O O O OH 480VAC - 1 MCC PREWIRED MCC PREWIRED MCC PREWIRED MCC PREWIRED MCC/ MOTOR GC - GC O - - - BEAM HEAD SYSTEMS
E303g BLOWER 7 GC O O O OH 480VAC 1 MCC PREWIRED MCC PREWIRED MCC PREWIRED MCC PREWIRED MCC/ MOTOR GC - GC O - - - BEAM HEAD SYSTEMS
E303h BLOWER 8 GC O O O OH 480VAC 1 MCC PREWIRED MCC PREWIRED MCC PREWIRED MCC PREWIRED MCC/ MOTOR GC - GC O - - - BEAM HEAD SYSTEMS
E303i BLOWER 9 GC O O O OH 480VAC - 1 MCC PREWIRED MCC PREWIRED MCC PREWIRED MCC PREWIRED MCC/ MOTOR GC - GC O - - - BEAM HEAD SYSTEMS
E303j BLOWER 10 GC O O O OH 480VAC - 1 MCC PREWIRED MCC PREWIRED MCC PREWIRED MCC PREWIRED MCC/ MOTOR GC - GC O - - - BEAM HEAD SYSTEMS
E303k BLOWER 11 GC O O O OH 480VAC - 1 MCC PREWIRED MCC PREWIRED MCC PREWIRED MCC PREWIRED MCC/ MOTOR GC - GC O - - - BEAM HEAD SYSTEMS
E303l BLOWER 12 GC O O O OH 480VAC - 1 MCC PREWIRED MCC PREWIRED MCC PREWIRED MCC PREWIRED MCC/ MOTOR GC - GC O - - - BEAM HEAD SYSTEMS
E303m BLOWER 13 GC O O O OH 480VAC - 1 MCC PREWIRED MCC PREWIRED MCC PREWIRED MCC PREWIRED MCC/ MOTOR GC - GC O - - - BEAM HEAD SYSTEMS
E303n BLOWER 14 GC O O O OH 480VAC - 1 MCC PREWIRED MCC PREWIRED MCC PREWIRED MCC PREWIRED MCC/ MOTOR GC - GC O - - - BEAM HEAD SYSTEMS
E303o BLOWER 15 GC O O O OH 480VAC - 1 MCC PREWIRED MCC PREWIRED MCC PREWIRED MCC PREWIRED MCC/ MOTOR GC - GC O - - - BEAM HEAD SYSTEMS
E303p BLOWER 16 GC O O O OH 480VAC - 1 MCC PREWIRED MCC PREWIRED MCC PREWIRED MCC PREWIRED MCC/ MOTOR GC - GC O - - - BEAM HEAD SYSTEMS
E303q BLOWER 17 GC O O O OH 480VAC - 1 MCC PREWIRED MCC PREWIRED MCC PREWIRED MCC PREWIRED MCC/ MOTOR GC - GC O - - - BEAM HEAD SYSTEMS
E304 VAC PRODUCER GC O GC O UG 480VAC - 0 BELDEN 8618 1/BELDEN WEATHERBOX VFD/TRANSDUCER MDP/VFD; VFD/MOTOR GC - GC - O O O PAD WIRE VFD IN VACUUM ROOM;SEE VACUTECH DRAWINGS
E304a PRESSURE TRANSDUCER - O - GC UG - 24VDC 0 SOUTHWIRE MCTC-18-3S-1 1/SENSOR CABLE TERMINAL BLOCK MCC/ TRANSDUCER - GC - GC - - - - - -
E305 VAC PRODUCER GC O GC O UG 480VAC - 0 BELDEN 8618 1/BELDEN WEATHERBOX VFD/TRANSDUCER MDP/VFD; VFD/MOTOR GC - GC - O O O PAD WIRE VFD IN VACUUM ROOM;SEE VACUTECH DRAWINGS
E305A PRESSURE TRANSDUCER - O - GC UG - 24VDC 0 SOUTHWIRE MCTC-18-3S-1 1/SENSOR CABLE TERMINAL BLOCK MCC/ TRANSDUCER - GC - GC - - - - - -
SCHEDULE KEY
B- BOBRICK ACCESSORY CATOLOGUE NUMBERS
GC GENERAL CONTRACTOR
O OWNER
OC OWNERS CONSTRUCTION FORCES
NA NOT APPLICABLE
/ R RECESSED APPLICATION
V VARIES
GREY COLOR INDICATES NOT APPLICABLE
EXXX HAVE CUT SHEET(S) FOR THESE ITEMS
DEFINITIONS
FURNISHED
SET IN PLACE
INSTALLED
HARDWIRE
PROVIDE CONDUIT
PROVIDE VALVES
PLUMBING CONNECTION
SUPPLIED TO SITE AT OWNERS OR GENERAL CONTRACTORS CHOSEN LOCATION
MOVED FROM ANY LOCATION ON PROPERTY AND SET IN APPROPRIATE PLACE. THIS LOCATION
SHALL BE CONFIRMED BY THE OWNER OR OWNER'S REPRESENTATIVE
EQUIPMENT TO BE FASTENED, MOUNTED OR SECURED IN PLACE
CONNECT CONDUCTORS FROM SOURCE TO EQUIPMENT; THIS INCLUDES BOTH POWER AND
CONTROL CONDUCTORS
EXTEND APPROPRIATE CONDUIT FROM SOURCE TO EQUIPMENT AND PROVIDE BOX AS
NECESSARY. SEE SCHEDULE FOR ROUTING OVERHEAD OR UNDERGROUND RECESSED
APPLICATION
THIS INCLUDES VALVES AND ALL NECESSARY PLUMBING FITTINGS FOR COMPLETE, CODE
COMPLIANT INSTALLATION. ALL CODE REQUIRED VALVES MAY NOT BE SHOWN. IT IS THE
GENERAL CONTRACTORS
PROVIDE PIPING AND FITTINGS REQUIRED AND MAKE FINAL CONNECTION TO EQUIPMENT FOR
ALL WATER, SEWER, GAS, AND COMPRESSED AIR SYSTEMS
REVISIONS
#DATE
NOT
F
O
R
C
O
N
S
T
R
U
C
T
I
O
N
STAMP:
THESE DOCUMENTS HAVE BEEN PRODUCED AS AN
INSTRUMENT OF SERVICE AND ARE INTENDED SOLELY
FOR THE PURPOSE OF CONSTRUCTING, USING AND
MAINTAINING THE PROJECT. SPOTLESS WASH
SOLUTIONS USA INC, AS THE ARCHITECT OF RECORD
FOR THE PROJECT RETAINS OWNERSHIP OF THESE
DOCUMENTS.
ANY USE OF THESE DOCUMENTS OR USE OF THIS
DESIGN, IDEAS OR CONCEPTS DESCRIBED HEREIN IN
WHOLE OR PART BY ANY MEANS WHATSOEVER IS
STRICTLY PROHIBITED EXCEPT BY WRITTEN CONSENT
OF SPOTLESS WASH SOLUTIONS USA INC.
REPRODUCTION OF THIS DOCUMENT IS STRICTLY
PROHIBITED EXCEPT BY WRITTEN CONSENT OF
SPOTLESS WASH SOLUTIONS USA INC.
COPYRIGHT 2022
SPOTLESS WASH SOLUTIONS USA INC.
CHECKED:
DATE:
JOB NUMBER:
ISSUED FOR:
SHEET NUMBER:
SP
O
T
L
E
S
S
W
A
S
H
S
O
L
U
T
I
O
N
S
PO
B
O
X
5
4
5
6
TW
I
N
F
A
L
L
S
,
I
D
A
H
O
8
3
3
0
3
PH
.
(
2
0
8
)
8
4
1
-
4
5
2
4
DRAWN:
BI
N
D
I
N
G
02/15/2022
PERMIT REVIEW SET
NOT FOR CONSTRUCTION
21005
BUILDING PERMIT - NFC
A1.6b
EQUIPMENT
SCHEDULE
CONTINUED
AS
NI
T
R
O
C
A
R
W
A
S
H
RE
X
B
U
R
G
,
I
D
13
7
1
N
2
N
D
E
RE
X
B
U
R
G
,
I
D
8
3
4
4
8
5/4/22
E400 CHEMICAL / WATER DISPENSING
ITEM DESCRIPTION UNLOADED FURNISHED
SET IN
PLACE INSTALLED
CONDUIT
OH / UG
POWER
VOLTAGE (V)
CONTROL
VOLTAGE
TUNNEL
CONTROL
FUNCTION CONTROL WIRE SIZE/ TYPE
CONTROL WIRE QUANTITY/
TYPE CONTROL CONNECTION TYPE
CONTROL FED FROM/ FEEDS
TO POWER FEED FROM/FEEDS TO HARDWIRE
WIRE DEVICE TO
CONTROLLER
PROVIDE
CONDUIT(S)
PROVIDE
VALVES PLUMBING IN
PLUMBING
OUT
STARTUP
TEST
BALANCE MOUNTING BACKING COMMENTS
E401 HYDRAFLEX PANEL 1 - HD7/9; HOT SOFT WATER; 24VAC; 24.5W - O O O UG - - 7 #16AWG/THHN/THWN 9/7 HOTS/1 NEUTRAL/1
GROUND
YELLOW CORD; 1"CONDUIT/ JBOX TC/6X6X4 JBOX PANEL/ HYDRAFLEX PANEL GC GC GC O O O O WALL NO CONNECT YELLOW MAIN TRUNK WIRE TO J-BOX; CONNECT
GREY WIRE TO CTRL UNIT
E401a PANEL 1-1; CTA 1; ALKALINE; AIR - - - - - - - 0 - - - - - - - - O O O O - - NOT SHOWN ON PLAN, PART OF E401
E401b PANEL 1-2; CTA 2; ALKALINE; AIR - - - - - - - 0 - - - - - - - - O O O O - - NOT SHOWN ON PLAN, PART OF E401
E401c PANEL 1-3; BUG JUICE LOW; NO AIR - - - - - - - 0 - - - - - - - - O O O O - - NOT SHOWN ON PLAN, PART OF E401
E401d PANEL 1-4; BUG JUICE TOP; NO AIR - - - - - - - 0 - - - - - - - - O O O O - - NOT SHOWN ON PLAN, PART OF E401
E401e PANEL 1-5; PRESOAK PEDESTAL 1; AIR - - - - - - - 0 - - - - - - - - O O O O - - NOT SHOWN ON PLAN, PART OF E401
E401f PANEL 1-6; PRESOAK PEDESTAL 2; AIR - - - - - - - 0 - - - - - - - - O O O O - - NOT SHOWN ON PLAN, PART OF E401
E401g PANEL 1-7+; RAINBOW FOAM; NEUTRAL; AIR - - - - - - - 0 - - - - - - - - O O O O - - NOT SHOWN ON PLAN, PART OF E401
E402 HYDRAFLEX PANEL 2 - HD7/9; COLD SOFT WATER; 24VAC; 24.5W - O O O UG - - 7 #16AWG/THHN/THWN 9/7 HOTS/1 NEUTRAL/1
GROUND
YELLOW CORD; 1"CONDUIT/ JBOX TC/6X6X4 JBOX PANEL/ HYDRAFLEX PANEL GC GC GC O O O O WALL NO CONNECT YELLOW MAIN TRUNK WIRE TO J-BOX; CONNECT
GREY WIRE TO CTRL UNIT
E402a PANEL 2-1; PRESOAK 2; BANANA FOAMER; LOW PH; AIR - - - - - - - 0 - - - - - - - - O O O O - - NOT SHOWN ON PLAN, PART OF E402
E402b PANEL 2-2; CTA 3; LOW PH; AIR - - - - - - - 0 - - - - - - - - O O O O - - NOT SHOWN ON PLAN, PART OF E402
E402c PANEL 2-3+; CARNUBA WAX; LOW PH; AIR - - - - - - - 0 - - - - - - - - O O O O - - NOT SHOWN ON PLAN, PART OF E402
E402d PANEL 2-4+; TOTAL SURFACE PROTECTION CERAMIC; ICE - - - - - - - 0 - - - - - - - - O O O O - - NOT SHOWN ON PLAN, PART OF E402
E402e PANEL 2-5; CLEAR COAT; BLAZIN GLAZE - - - - - - - 0 - - - - - - - - O O O O - - NOT SHOWN ON PLAN, PART OF E402
E402f PANEL 2-6; DRYING AGENT; BLAZIN GLAZE - - - - - - - 0 - - - - - - - - O O O O - - NOT SHOWN ON PLAN, PART OF E402
E402g PANEL 2-7; RUST INHIBITOR;- - - - - - - 0 - - - - - - - - O O O O - - NOT SHOWN ON PLAN, PART OF E402
E403 ACCU-PUMP 1; 4 UNIT GROUP - O O O UG 120VAC - 1 - - - - - - - GC - O O O WALL NO
E404 ACCU-PUMP 2; 4 UNIT GROUP - O O O UG 120VAC - 1 - - - - - - - GC - O O O WALL NO
E405 ACCU-PUMP 3; 4 UNIT GROUP - O O O UG 120VAC - 1 - - - - - - - GC - O O O WALL NO
E406 ACCU-PUMP 4; 4 UNIT GROUP - O O O UG 120VAC - 1 - - - - - - - GC - O O O WALL NO
E410 TIRE SEAL CONTROL PANEL - O O O UG - 24VAC 1 #16AWG/THHN/THWN 5/3HOT/1NEUTRAL/1GROUN
D
CEE CONDUIT BODY/FLEXIBLE
CONDUIT/JBOX
TC/ JBOX-CONDULET TC/ JBOX GC GC GC - O O O WALL NO
E420 SOLENOID UNDER CARRIAGE RINSE 12VDC - O O O UG - 12VDC 1 #16AWG/THHN/THWN 3/1HOT/1NEUTRAL/1GROUN
D
CEE CONDUIT BODY/FLEXIBLE
CONDUIT/JBOX
TC/ JBOX-CONDULET TC/ JBOX GC GC GC - O O O WALL NO
E421 FRESH WATER SOLENOID MANIFOLD 1 - O O O OH - 24VAC 4 #16AWG/THHN/THWN 10/8 HOT/1 NEUTRAL/1
GROUND
CEE CONDUIT BODY/FLEXIBLE
CONDUIT/JBOX
TC/ JBOX-CONDULET TC/ JBOX GC GC GC - O O O WALL NO PECO; (4) 1/2" SOLENOIDS
E421a FRESH WATER SOLENOID 1-1 - O GEN UG - 24VDC #12AWG/THHN/THWN 3/1HOT/1NEUTRAL/1GROUN
D
JBOX/SO CORD OR FLEXIBLE
CONDUIT
MCC TC/ SOLENOID JBOX TC/ SOLENOID JBOX GEN GEN .75" CA GEN - O
E421b FRESH WATER SOLENOID 2-2 - O GEN UG - 24VDC #12AWG/THHN/THWN 3/1HOT/1NEUTRAL/1GROUN
D
JBOX/SO CORD OR FLEXIBLE
CONDUIT
MCC TC/ SOLENOID JBOX TC/ SOLENOID JBOX GEN GEN .75" CA GEN - O
E421c FRESH WATER SOLENOID 2-3 - O GEN UG - 24VDC #12AWG/THHN/THWN 3/1HOT/1NEUTRAL/1GROUN
D
JBOX/SO CORD OR FLEXIBLE
CONDUIT
MCC TC/ SOLENOID JBOX TC/ SOLENOID JBOX GEN GEN .75" CA GEN - O
E421d FRESH WATER SOLENOID 2-3 - O GEN UG - 24VDC #12AWG/THHN/THWN 3/1HOT/1NEUTRAL/1GROUN
D
JBOX/SO CORD OR FLEXIBLE
CONDUIT
MCC TC/ SOLENOID JBOX TC/ SOLENOID JBOX GEN GEN .75" CA GEN - O
E422 FRESH WATER SOLENOID MANIFOLD 2 - O O O OH - 24VAC 4 #16AWG/THHN/THWN 10/8 HOT/1 NEUTRAL/1
GROUND
CEE CONDUIT BODY/FLEXIBLE
CONDUIT/JBOX
TC/ JBOX-CONDULET TC/ JBOX GC GC GC - O O O WALL NO PECO; (4) 1/2" SOLENOIDS
E422a FRESH WATER SOLENOID 2-1 - - - - - - - 0 - - - - - - - - - GEN - O
E422b FRESH WATER SOLENOID 2-2 - - - - - - - 0 - - - - - - - - - - - O WALL -
E422c FRESH WATER SOLENOID 2-3 - - - - - - - 0 - - - - - - - - - - - O WALL -
E422d FRESH WATER SOLENOID 2-4 - - - - - - - 0 - - - - - - - - - - - O WALL -
E431 MAT WASHER 1; 110VAC; 30AMP GC O GC O UG 120VAC - 0 - - - - HOUSE PANEL/ EQUIP GC - GC .5" HSW GC GC O SLAB - RHINO OR SPOTLESS; SS ; VALVE IN GROUND;
E432 MAT WASHER 2; 110VAC; 30AMP GC O GC O UG 120VAC - 0 - - - - HOUSE PANEL/ EQUIP GC - GC .5" HSW GC GC O SLAB - RHINO OR SPOTLESS; SS ; VALVE IN GROUND;
SCHEDULE KEY
B- BOBRICK ACCESSORY CATOLOGUE NUMBERS
GC GENERAL CONTRACTOR
O OWNER
OC OWNERS CONSTRUCTION FORCES
NA NOT APPLICABLE
/ R RECESSED APPLICATION
V VARIES
GREY COLOR INDICATES NOT APPLICABLE
EXXX HAVE CUT SHEET(S) FOR THESE ITEMS
DEFINITIONS
FURNISHED
SET IN PLACE
INSTALLED
HARDWIRE
PROVIDE CONDUIT
PROVIDE VALVES
PLUMBING CONNECTION
SUPPLIED TO SITE AT OWNERS OR GENERAL CONTRACTORS CHOSEN LOCATION
MOVED FROM ANY LOCATION ON PROPERTY AND SET IN APPROPRIATE PLACE. THIS LOCATION
SHALL BE CONFIRMED BY THE OWNER OR OWNER'S REPRESENTATIVE
EQUIPMENT TO BE FASTENED, MOUNTED OR SECURED IN PLACE
CONNECT CONDUCTORS FROM SOURCE TO EQUIPMENT; THIS INCLUDES BOTH POWER AND
CONTROL CONDUCTORS
EXTEND APPROPRIATE CONDUIT FROM SOURCE TO EQUIPMENT AND PROVIDE BOX AS
NECESSARY. SEE SCHEDULE FOR ROUTING OVERHEAD OR UNDERGROUND RECESSED
APPLICATION
THIS INCLUDES VALVES AND ALL NECESSARY PLUMBING FITTINGS FOR COMPLETE, CODE
COMPLIANT INSTALLATION. ALL CODE REQUIRED VALVES MAY NOT BE SHOWN. IT IS THE
GENERAL CONTRACTORS
PROVIDE PIPING AND FITTINGS REQUIRED AND MAKE FINAL CONNECTION TO EQUIPMENT FOR
ALL WATER, SEWER, GAS, AND COMPRESSED AIR SYSTEMS
E600 SIGNS / SPECIALTY LIGHTING
ITEM DESCRIPTION UNLOADED FURNISHED
SET IN
PLACE INSTALLED
CONDUIT
OH / UG
POWER
VOLTAGE (V)
TUNNEL
CONTROL
FUNCTION CONTROL WIRE SIZE/ TYPE CONTROL WIRE QUANTITY/ TYPE CONTROL CONNECTION TYPE CONTROL FED FROM/ FEEDS TO
POWER FEED
FROM/FEEDS TO HARDWIRE
WIRE DEVICE TO
CONTROLLER
PROVIDE
CONDUIT(S) MOUNTING COMMENTS
E601 ALL BUILDING SIGNAGE; SEE SIGNAGE PACKAGE FOR LOCATIONS SC SC SC SC OH - 0 --- - LCP/ SIGN GC - GC WALL ALL BUILDING SIGNAGE; SEE SIGNAGE PACKAGE FOR
LOCATIONS
E611 ALL SITE SIGNAGE; SEE SIGNAGE PACKAGE FOR LOCATIONS SC SC SC SC UG - 0 --- - LCP/ SIGN GC - GC VARIES ALL SITE SIGNAGE; SEE SIGNAGE PACKAGE FOR
LOCATIONS
E621a SIGN; DIGITAL MENU 1; 100-240VAC; 4AMP (FUTURE)- O O O UG 120VAC 0 #16AWG/THHN/THWN 3/1SWITCH/1NEUTRAL/1GROUND SO CORD/JBOX TC/ DRIVER/ LED TC/ DRIVER/ LED GC GC GC PAD SPOTLESS DIGITAL MENU
E621b SIGN; DIGITAL MENU 2; 100-240VAC; 4AMP (FUTURE)- O O O UG 120VAC 0 #16AWG/THHN/THWN 3/1SWITCH/1NEUTRAL/1GROUND SO CORD/JBOX TC/ DRIVER/ LED TC/ DRIVER/ LED GC GC GC PAD SPOTLESS DIGITAL MENU
E631 GRAND ENTRANCE ARCH O O O O UG 120VAC 1 #16AWG/THHN/THWN 3/1SWITCH/1NEUTRAL/1GROUND SO CORD/JBOX TC/ DRIVER/ LED TC/ DRIVER/ LED GC GC GC SLAB SPOTLESS
E632a SIGN; WALL MOUNTED O O O O UG 120VAC 1 #16AWG/THHN/THWN 3/1SWITCH/1NEUTRAL/1GROUND SO CORD/JBOX TC/ DRIVER/ LED TC/ DRIVER/ LED GC GC GC WALL
E632b SIGN; WALL MOUNTED O O O O UG 120VAC 1 #16AWG/THHN/THWN 3/1SWITCH/1NEUTRAL/1GROUND SO CORD/JBOX TC/ DRIVER/ LED TC/ DRIVER/ LED GC GC GC WALL
E633 SIGN; WALL MOUNTED O O O O UG 120VAC 1 #16AWG/THHN/THWN 3/1SWITCH/1NEUTRAL/1GROUND SO CORD/JBOX TC/ DRIVER/ LED TC/ DRIVER/ LED GC GC GC WALL
E634 SIGN; WALL MOUNTED O O O O UG 120VAC 1 #16AWG/THHN/THWN 3/1SWITCH/1NEUTRAL/1GROUND SO CORD/JBOX TC/ DRIVER/ LED TC/ DRIVER/ LED GC GC GC WALL
E635 SIGN; WALL MOUNTED O O O O UG 120VAC 1 #16AWG/THHN/THWN 3/1SWITCH/1NEUTRAL/1GROUND SO CORD/JBOX TC/ DRIVER/ LED TC/ DRIVER/ LED GC GC GC WALL
E636 SIGN; WALL MOUNTED O O O O UG 120VAC 1 #16AWG/THHN/THWN 3/1SWITCH/1NEUTRAL/1GROUND SO CORD/JBOX TC/ DRIVER/ LED TC/ DRIVER/ LED GC GC GC WALL
E637 SIGN; STILL DRYING / GO - O O O UG 120VAC 2 #16AWG/THHN/THWN 3/1SWITCH/1NEUTRAL/1GROUND SO CORD/JBOX TC/ DRIVER/ LED TC/ DRIVER/ LED GC GC GC PAVEMENT SPOTLESS
E600 LED LIGHTING
ITEM DESCRIPTION FURNISHED
SET IN
PLACE INSTALLED
CONDUIT
OH / UG
POWER
VOLTAGE
(V)
TUNNEL
CONTROL
FUNCTION
CONTROL WIRE
SPECIFICATION CONTROL WIRE QUANTITY/ TYPE
CONTROL
CONNECTION TYPE
CONTROL FED FROM/
FEEDS TO HARDWIRE
WIRE DEVICE
TO
CONTROLLER
PROVIDE
CONDUIT(S) MOUNTING COMMENTS
E641 LED; PRESOAK; 6' O O O OH 120VAC 1 #16AWG/THHN/THWN 3/1SWITCH/1NEUTRAL/1GROUND SO CORD/JBOX TC/ DRIVER/ LED GC GC GC UNISTRUT G&G LED; RAINBOW MAXX
E642 LED; RAINBOW FOAM; 4' x 6' x 4' O O O OH 120VAC 1 #16AWG/THHN/THWN 3/1SWITCH/1NEUTRAL/1GROUND SO CORD/JBOX TC/ DRIVER/ LED GC GC GC UNISTRUT G&G LED; RED
E643 LED; CARNUBA WAX; 6' O O O OH 120VAC 1 #16AWG/THHN/THWN 3/1SWITCH/1NEUTRAL/1GROUND SO CORD/JBOX TC/ DRIVER/ LED GC GC GC UNISTRUT G&G LED; RAINBOW MAXX
E644 LED; RINSE; 6'O O O OH 120VAC 1 #16AWG/THHN/THWN 3/1SWITCH/1NEUTRAL/1GROUND SO CORD/JBOX TC/ DRIVER/ LED GC GC GC UNISTRUT G&G LED; AMBER MAXX
E645 LED; SURFACE PROTECTANT; 6' O O O OH 120VAC 1 #16AWG/THHN/THWN 3/1SWITCH/1NEUTRAL/1GROUND SO CORD/JBOX TC/ DRIVER/ LED GC GC GC UNISTRUT G&G LED; BLUE
E646 LED; CLEAR COAT PROTECTANT; 6' O O O OH 120VAC 1 #16AWG/THHN/THWN 3/1SWITCH/1NEUTRAL/1GROUND SO CORD/JBOX TC/ DRIVER/ LED GC GC GC UNISTRUT G&G LED; AMBER
E647 LED; DRYING AGENT; 6' O O O OH 120VAC 1 #16AWG/THHN/THWN 3/1SWITCH/1NEUTRAL/1GROUND SO CORD/JBOX TC/ DRIVER/ LED GC GC GC UNISTRUT G&G LED; RED
E648 LED; SPOT FREE RINSE; 6' O O O OH 120VAC 1 #16AWG/THHN/THWN 3/1SWITCH/1NEUTRAL/1GROUND SO CORD/JBOX TC/ DRIVER/ LED GC GC GC UNISTRUT G&G LED; RED
E649 LED; BLOWER BEAM 1; 6' O O O OH 120VAC 1 #16AWG/THHN/THWN 3/1SWITCH/1NEUTRAL/1GROUND SO CORD/JBOX TC/ DRIVER/ LED GC GC GC UNISTRUT G&G LED; RED
E650 LED; BLOWER BEAM 2; 6' O O O OH 120VAC 1 #16AWG/THHN/THWN 3/1SWITCH/1NEUTRAL/1GROUND SO CORD/JBOX TC/ DRIVER/ LED GC GC GC UNISTRUT G&G LED; RED
E651 LED; BLOWER BEAM 3; 6' O O O OH 120VAC 1 #16AWG/THHN/THWN 3/1SWITCH/1NEUTRAL/1GROUND SO CORD/JBOX TC/ DRIVER/ LED GC GC GC UNISTRUT G&G LED; RED
E652 LED; BLOWER BEAM 4; 6' O O O OH 120VAC 1 #16AWG/THHN/THWN 3/1SWITCH/1NEUTRAL/1GROUND SO CORD/JBOX TC/ DRIVER/ LED GC GC GC UNISTRUT G&G LED; RED
E653 LED; BLOWER BEAM 5; 6' O O O OH 120VAC 1 #16AWG/THHN/THWN 3/1SWITCH/1NEUTRAL/1GROUND SO CORD/JBOX TC/ DRIVER/ LED GC GC GC UNISTRUT G&G LED; RED
E500 AIR CONTROLS
ITEM DESCRIPTION FURNISHED
SET IN
PLACE INSTALLED
CONDUIT
OH / UG
CONTROL
VOLTAGE
TUNNEL
CONTROL
FUNCTION CONTROL WIRE SIZE/ TYPE CONTROL WIRE QUANTITY/ TYPE CONTROL CONNECTION TYPE
CONTROL FED FROM/ FEEDS
TO HARDWIRE
WIRE DEVICE TO
CONTROLLER
PROVIDE
CONDUIT(S) PROVIDE VALVES
STARTUP
TEST
BALANCE MOUNTING BACKING COMMENTS
E501 AIR TREE 1 SOLENOIDS (24VDC)O O O UG 24VDC 6 #16AWG/THHN/THWN 8/6HOT/1NEUTRAL/1GROUND JBOX/SO CORD TC/ SOLENOID JBOX GC GC GC .75" CA O WALL NO
E501a SOLENOID - TOP BRUSH RETRACT SINGLE - - - - - 0 --- - - - - - - - -
E501b SOLENOID - SIDE BRUSH 1 PS EXTEND SINGLE - - - - - 0 --- - - - - - -
E501c SOLENOID - SIDE BRUSH 2 DS EXTEND SINGLE - - - - - 0 --- - - - - - - - -
E501d SOLENOID - SIDE BRUSH 2 DS EXTEND SINGLE - - - - - 0 --- - - - - - -
E501e SOLENOID - WRAP 1 DRIVER EXTEND DUAL - - - - - 0 --- - - - - - - - -
E501f SOLENOID - WRAP 1 PASSENGER EXTEND DUAL - - - - - 0 --- - - - - - - - -
E502 AIR TREE 2 SOLENOIDS (24VDC)O O O UG 24VDC 7 #16AWG/THHN/THWN 11/9 HOTS/1 NEUTRAL/1 GROUND JBOX/SO CORD TC/ SOLENOID JBOX GC GC GC .75" CA O WALL NO
E502a SOLENOID - TOP BRUSH 2 RETRACT SINGLE - - - - - 0 --- - - - - - - - -
E502b SOLENOID - WRAP 1 DRIVER EXTEND DUAL - - - - - 0 --- - - - - - -
E502c SOLENOID - WRAP 1 PASSENGER EXTEND DUAL - - - - - 0 --- - - - - - -
E502d SOLENOID - SIDE BRUSH 1 DS EXTEND SINGLE - - - - - 0 --- - - - - - -
E502e SOLENOID - TIRE SHINER DRIVER EXTEND SINGLE - - - - - 0 --- - - - - - - - -
E502f SOLENOID - TIRE SHINER PASSENGER EXTEND SINGLE - - - - - 0 --- - - - - - - - -
REVISIONS
#DATE
NOT
F
O
R
C
O
N
S
T
R
U
C
T
I
O
N
STAMP:
THESE DOCUMENTS HAVE BEEN PRODUCED AS AN
INSTRUMENT OF SERVICE AND ARE INTENDED SOLELY
FOR THE PURPOSE OF CONSTRUCTING, USING AND
MAINTAINING THE PROJECT. SPOTLESS WASH
SOLUTIONS USA INC, AS THE ARCHITECT OF RECORD
FOR THE PROJECT RETAINS OWNERSHIP OF THESE
DOCUMENTS.
ANY USE OF THESE DOCUMENTS OR USE OF THIS
DESIGN, IDEAS OR CONCEPTS DESCRIBED HEREIN IN
WHOLE OR PART BY ANY MEANS WHATSOEVER IS
STRICTLY PROHIBITED EXCEPT BY WRITTEN CONSENT
OF SPOTLESS WASH SOLUTIONS USA INC.
REPRODUCTION OF THIS DOCUMENT IS STRICTLY
PROHIBITED EXCEPT BY WRITTEN CONSENT OF
SPOTLESS WASH SOLUTIONS USA INC.
COPYRIGHT 2022
SPOTLESS WASH SOLUTIONS USA INC.
CHECKED:
DATE:
JOB NUMBER:
ISSUED FOR:
SHEET NUMBER:
SP
O
T
L
E
S
S
W
A
S
H
S
O
L
U
T
I
O
N
S
PO
B
O
X
5
4
5
6
TW
I
N
F
A
L
L
S
,
I
D
A
H
O
8
3
3
0
3
PH
.
(
2
0
8
)
8
4
1
-
4
5
2
4
DRAWN:
BI
N
D
I
N
G
02/15/2022
PERMIT REVIEW SET
NOT FOR CONSTRUCTION
21005
BUILDING PERMIT - NFC
A1.6c
EQUIPMENT
SCHEDULE
CONTINUED
AS
NI
T
R
O
C
A
R
W
A
S
H
RE
X
B
U
R
G
,
I
D
13
7
1
N
2
N
D
E
RE
X
B
U
R
G
,
I
D
8
3
4
4
8
5/4/22
E800 ELECTRICAL PANELS, CONTROLLERS, POS SYSTEMS
ITEM SORTCODE DESCRIPTION UNLOADED FURNISHED
SET IN
PLACE INSTALLED
CONDUIT
OH / UG
POWER VOLTAGE
(V)
CONTROL
VOLTAGE
TUNNEL CONTROL
FUNCTION CONTROL WIRE SIZE/ TYPE
CONTROL WIRE QUANTITY/
TYPE CONTROL CONNECTION TYPE CONTROL FED FROM/ FEEDS TO
POWER FEED
FROM/FEEDS TO HARDWIRE
WIRE DEVICE TO
CONTROLLER
PROVIDE
CONDUIT(S) MOUNTING Comments
PT 21 PAD MOUNTED TRANSFORMER GC GC GC GC UG 480VAC - 0 ---- SEE ONE LINE GC - GC SLAB SPECIFIED BY POWER COMPANY / ENGINEER
MSB 22 MAIN SWITCH BOARD (MSB); 1200AMP GC GC GC GC UG 480VAC - 0 ---- SEE ONE LINE GC - GC SLAB/W SPECIFIED BY ENGINEER
MCC 23 MOTOR CONTROL CENTER; 800 AMP GC O O O UG 480VAC - 0 #16AWG/THHN/THWN 5/2HOTS/2NEUTRALS/1GROUND UG STUBS TO BOTTOM RIGHT SIDE
OF MCC
NEAREST 120VAC PANEL /MCC MSB/ MCC1 GC GC GC SLAB/W DESIGNED BY VENDOR
TC 24 TUNNEL CONTROLLER (TC); (1) 40AMP GC O O O UG 220VAC - 0 RS422 1 UG SITEWATCH SERVER/TC MCC / TC GC GC GC IN MCC DESIGNED BY VENDOR
HA 25 480Y/277 SUB-PANEL GC GC GC GC UG 480VAC - 0 ---- SEE ONE LINE GC - GC WALL SPECIFIED BY ENGINEER
LA 26 208Y/120 SUB-PANEL GC GC GC GC UG 120-208VAC - 0 ---- SEE ONE LINE GC - GC WALL SPECIFIED BY ENGINEER
LCP 27 LIGHTING CONTROL PANEL GC GC GC GC UG - - 0 ---- SEE ONE LINE GC - GC WALL SPECIFIED BY ENGINEER
TA 28 TRANSFORMER; 112.5 KVA GC GC GC GC UG - - 0 ---- SEE ONE LINE GC - GC SLAB SPECIFIED BY ENGINEER
TTB 29 TELEPHONE TERMINAL BOARD GC GC GC GC UG - - 0 ----- GC - GC WALL SPECIFIED BY ENGINEER, PAINT
IC 200 IRRIGATION CONTROLLER GC GC GC GC UG 120VAC - 0 ----- GC - GC WALL SPECIFIED BY ENGINEER
VFD1 201 VFD, VACUUM PRODUCER 1; DISCONNECT RATED GC O GC GC UG 480VAC 12VDC 0 ----- GC - GC WALL OWNER FURNISHED, CONTRACTOR INSTALLED
VFD2 202 VFD, VACUUM PRODUCER 2; DISCONNECT RATED (FUTURE)- - - - UG 480VAC 12VDC 0 ----- GC - GC WALL OWNER FURNISHED, CONTRACTOR INSTALLED
E801a 210 DRB SW; SITEWATCH SERVER - O O O UG 120VAC - 1 CAT5E 1 WALL PLATE/ PATCH CABLE DMARC/ SERVER LOCATION HOUSE PANEL/ UNIT GC - GC IN RACK LOCATED IN MANAGERS OFFICE POS RACK
E801b 210 DRB SITEWATCH SRMB - O O O UG - - 1 CAT5E 1 WALL PLATE/ PATCH CABLE DMARC/ SERVER LOCATION HOUSE PANEL/ UNIT GC - GC IN RACK SEE NON-TUNNELWATCH CONTROLLER INTERFACE WIRING IN DRB LITERATURE
E802 210 DRB TW; TUNNELWATCH COMPUTER; 120VAC - O O O UG 120VAC - 0 CAT5E 1 WALL PLATE/ PATCH CABLE SITEWATCH SERVER/ WALL JACK HOUSE PANEL/ UNIT GC - GC IN RACK LOCATED IN MANAGERS OFFICE POS RACK
E803 210 DRB MWS1; MANAGER'S WORKSTATION 1 AT CONTROL; 120VAC - O O O UG 120VAC - 0 CAT5E 1 WALL PLATE/ PATCH CABLE SITEWATCH SERVER/ WALL JACK HOUSE PANEL/ UNIT GC - GC DESK AT CONTROL
E804 210 DRB MWS2; MANAGER'S WORKSTATION 2; AT MANAGER'S OFFICE; 120VAC - O O O UG 120VAC - 0 CAT5E 1 WALL PLATE/ PATCH CABLE SITEWATCH SERVER/ WALL JACK HOUSE PANEL/ UNIT GC - GC DESK AT MANAGER'S OFFICE
E805 210 SWS LOADING TUNNEL CONTROL STATION/ LAGUNA KEYPAD O O O O UG 120VAC - 0 CAT5E/ (2) RS422 3 WALL PLATE/ PATCH CABLE SITEWATCH SERVER/ STATION HOUSE PANEL/ UNIT GC GC GC SLAB ON LOADING PEDESTAL
E806a 230 DRB XPT1; EXPRESS PAY TERMINAL; LANE 1; 120VAC; 8A - O O O UG 120VAC - 0 CAT5E 1 EQUIPMENT MOUNTED BOX SITEWATCH SERVER/ XPT HOUSE PANEL/ UNIT GC - GC ISLAND XPT STANDARD BASE FRAME; INSTALL PER PRODUCT LITERATURE
E806b 230 DRB XPT2; EXPRESS PAY TERMINAL; LANE 2; 120VAC; 8A - O O O UG 120VAC - 0 CAT5E 1 EQUIPMENT MOUNTED BOX SITEWATCH SERVER/ XPT HOUSE PANEL/ UNIT GC - GC ISLAND XPT STANDARD BASE FRAME; INSTALL PER PRODUCT LITERATURE
E807a 230 DRB FPR1; FASTPASS PROXIMITY READER; LANE 1 - O O O UG - - 0 MANUF. PREWIRED WHIP ---- GC - GC ISLAND INSTALL PER PRODUCT LITERATURE
E807b 230 DRB FPR2; FASTPASS PROXIMITY READER; LANE 2 - O O O UG - - 0 MANUF. PREWIRED WHIP ---- GC - GC ISLAND INSTALL PER PRODUCT LITERATURE
E808a 230 DRB GATE1; MAGNETIC GATE; LANE 1; 120VAC; 5A - O O O UG 120VAC - 0 CAT5E 1 EQUIPMENT MOUNTED JBOX XPT/GATE HOUSE PANEL/ UNIT GC - GC ISLAND PROVIDE 2 1/2" PVC GUIDE TUBE PER PRODUCT LITERATURE
E808b 230 DRB GATE 2; MAGNETIC GATE; LANE 2; 120VAC; 5A - O O O UG 120VAC - 0 CAT5E 1 EQUIPMENT MOUNTED JBOX XPT/GATE HOUSE PANEL/ UNIT GC - GC ISLAND PROVIDE 2 1/2" PVC GUIDE TUBE PER PRODUCT LITERATURE
E809a 230 DRB EPL1; EXTERNAL PROXIMITY LOOP; LANE 1 - O GC GC UG - - 0 SEE NOTE AT END ---- GC - GC PAVEMENT IN-PAVEMENT LOOPS; SEE DRB LITERATURE FOR LOOP SOURCING
E809b 230 DRB EPL2; EXTERNAL PROXIMITY LOOP; LANE 2 - O GC GC UG - - 0 SEE NOTE AT END ---- GC - GC PAVEMENT IN-PAVEMENT LOOPS; SEE DRB LITERATURE FOR LOOP SOURCING
E810a 230 DRB GL1; GATE LOOP; LANE 1 - O GC GC UG - - 0 SEE NOTE AT END ---- GC - GC PAVEMENT IN-PAVEMENT LOOPS; SEE DRB LITERATURE FOR LOOP SOURCING
E810b 230 DRB GL2; GATE LOOP; LANE 2 - O GC GC UG - - 0 SEE NOTE AT END ---- GC - GC PAVEMENT IN-PAVEMENT LOOPS; SEE DRB LITERATURE FOR LOOP SOURCING
E811a 230 DRB ML1; MERGE LOOP 1 GC GC GC GC UG - - 0 SEE NOTE AT END ---- GC - GC PAVEMENT 8' DISTANCE FROM GATE LOOPS; SEE LIT. FOR LOOP SOURCING
E811b 230 DRB ML2; MERGE LOOP 2 GC GC GC GC UG - - 0 SEE NOTE AT END ---- GC - GC PAVEMENT 8' DISTANCE FROM GATE LOOPS; SEE LIT. FOR LOOP SOURCING
E812a 230 POS LANE 1 PULL BOX GC GC GC GC UG - - 0 ----- - - GC SLAB
E812b 230 POS LANE 2 PULL BOX GC GC GC GC UG - - 0 ----- - - GC SLAB
E821 230 PULSE SWITCH - O O O UG - - 1 BELDEN 8618 1/ BELDEN REMOTE MOUNTED JBOX TC/ JBOX TC/ JBOX GC GC GC CONVEYOR STI
E822 230 VEHICLE DETECTION MODULE; SONAR - O O O UG - - 1 BELDEN 8618 1/ BELDEN REMOTE JBOX TO MCC TC TC/ JBOX TC/ JBOX GC GC GC SLAB SITS IN RECESS IN TUNNEL SLAB
E823a 230 AMPLIFIER; ENTER EYES - O O O UG 120VAC - 1 #16AWG/THHN/THWN 10/7HOTS/2NEUTRALS/1GROUN
D
JBOX TC/ JBOX/ UNIT PANEL/ AMPLIFIER GC GC GC IN RACK INDIVIDUAL CIRCUIT, STOP / START CIRCUIT (CONVEYOR ONLY), DO NOT ROUTE IN
TRENCH
E823b 230 ENTER EYES PAIR - O O O UG - - 1 BELDEN 8618 1/ BELDEN OTT OTT/ EYE TC/ AMPLIFIER GC GC GC SLAB
E824 230 VEHICLE PROFILE SENSOR; TRUCK BED SONAR - O O O OH - - 1 BELDEN 8102 1/ BELDEN FLEXIBLE VPS INTERFACE/SONAR SENSOR - GC GC GC WALL CONNECT TO E845 CONTROLLER
E825a 230 EMERGENCY START/ STOP; PUSH BUTTON & TWIST TO RESET GC GC GC GC UG - - 1 #14AWG/THHN/THWN SEE DRB INSTALL MANUAL CONDUIT TCS/ JBOX TC/ BUTTONS GC GC GC WALL START & STOP WITH LED STATUS INDICATOR; ALL INDIVIDUALLY HOMERUN TO WBC
E825b 230 EMERGENCY START/ STOP; PUSH BUTTON & TWIST TO RESET GC GC GC GC UG - - 1 #14AWG/THHN/THWN SEE DRB INSTALL MANUAL CONDUIT TCS/ JBOX TC/ BUTTONS GC GC GC WALL CONNECT TO E845 CONTROLLER
E825c 230 EMERGENCY START/ STOP; PUSH BUTTON & TWIST TO RESET GC GC GC GC UG - - 1 #14AWG/THHN/THWN SEE DRB INSTALL MANUAL CONDUIT TCS/ JBOX TC/ BUTTONS GC GC GC WALL CONNECT TO E845 CONTROLLER
E825d 230 EMERGENCY START/ STOP; PUSH BUTTON & TWIST TO RESET GC GC GC GC UG - - 1 #14AWG/THHN/THWN SEE DRB INSTALL MANUAL CONDUIT TCS/ JBOX TC/ BUTTONS GC GC GC WALL CONNECT TO E845 CONTROLLER
E826 230 ANTI-COLLISION LOOP; 2'-6" x 6'-0"- O GC GC UG - - 0 SEE NOTE 1 ---- GC GC GC PAVEMENT
E830 230 PETIT SYSTEM CONTROLLER; 208VAC; 3PH; 20AMP; CAT-5E & THHN - O GC GC UG - - 0 #18AWG/THHN/THWN 13/11HOTS/1NEUTRAL/1GROUN
D
--- GC GC GC IN MCC DESIGNED BY VENDOR
E840 230 WELDING OUTLET, 220VAC, 50AMP - GC GC GC UG - - 0 ---- LA/ JBOX GC - GC FRAMING
E900 OTHER EQUIPMENT
ITEM DESCRIPTION FURNISHED
SET IN
PLACE INSTALLED
CONDUIT
OH / UG
POWER
VOLTAGE
(V)
CONTROL WIRE
SPECIFICATION POWER FEED FROM/FEEDS TO HARDWIRE
WIRE DEVICE
TO
CONTROLLER
PROVIDE
CONDUIT(S)
PROVIDE
VALVES MOUNTING COMMENTS
E901a RACK FOR SECURITY SERVER O O O - - - - - - - - SLAB
E901b RACK FOR POINT OF SALE SERVER O O O - - - - - - - - SLAB
E902 SECURITY SERVER; RECEPTACLE O O O UG 120VAC - - - - GC - RACK
E903 CAMERA OR MARKETING WALL MONITORS; RECEPTACLE O O O UG 120VAC - - - - GC - WALL
E904 MODEM / ROUTER; RECEPTACLE O O O UG 120VAC - - - - GC - RACK
E905 PC; RECEPTACLE O O O UG 120VAC - - - - GC - COUNTER
E906 MULTIFUNCTION PRINTER; RECEPTACLE O O O UG 120VAC - - -- GC - COUNTER
E910 REFRIGERATOR; FULL; RECEPTACLE O O O UG 120VAC - - - - GC - WALL
E911 MICROWAVE; ON COUNTER; RECEPTACLE O O O UG 120VAC - - -- GC - SHELF LOCATED ON MILLWORK SHELF
E912 COFFEE MAKER RECEPTACLE O O O UG 120VAC - - - - GC - COUNTER
E920 WORK BENCH 8' x 2.5'O O O OH - - - - - GC .5" CA BV SLAB BALL VALVE IS FOR OWNER PROVIDED HOSE REEL AT BENCH
E930 WASHING MACHINE O O O UG 120VAC - - - - GC .75" CSW SLAB
E940 CAMERA LOCATION; ALL POE SC SC SC OH 48VDC CAT 6A SEC SERVER/ CAMERA OC OC GC - VARIES
SCHEDULE KEY
B- BOBRICK ACCESSORY CATOLOGUE NUMBERS
GC GENERAL CONTRACTOR
O OWNER
OC OWNERS CONSTRUCTION FORCES
NA NOT APPLICABLE
/ R RECESSED APPLICATION
V VARIES
GREY COLOR INDICATES NOT APPLICABLE
EXXX HAVE CUT SHEET(S) FOR THESE ITEMS
DEFINITIONS
FURNISHED
SET IN PLACE
INSTALLED
HARDWIRE
PROVIDE CONDUIT
PROVIDE VALVES
PLUMBING CONNECTION
SUPPLIED TO SITE AT OWNERS OR GENERAL CONTRACTORS CHOSEN LOCATION
MOVED FROM ANY LOCATION ON PROPERTY AND SET IN APPROPRIATE PLACE. THIS LOCATION
SHALL BE CONFIRMED BY THE OWNER OR OWNER'S REPRESENTATIVE
EQUIPMENT TO BE FASTENED, MOUNTED OR SECURED IN PLACE
CONNECT CONDUCTORS FROM SOURCE TO EQUIPMENT; THIS INCLUDES BOTH POWER AND
CONTROL CONDUCTORS
EXTEND APPROPRIATE CONDUIT FROM SOURCE TO EQUIPMENT AND PROVIDE BOX AS
NECESSARY. SEE SCHEDULE FOR ROUTING OVERHEAD OR UNDERGROUND RECESSED
APPLICATION
THIS INCLUDES VALVES AND ALL NECESSARY PLUMBING FITTINGS FOR COMPLETE, CODE
COMPLIANT INSTALLATION. ALL CODE REQUIRED VALVES MAY NOT BE SHOWN. IT IS THE
GENERAL CONTRACTORS
PROVIDE PIPING AND FITTINGS REQUIRED AND MAKE FINAL CONNECTION TO EQUIPMENT FOR
ALL WATER, SEWER, GAS, AND COMPRESSED AIR SYSTEMS
E600 APPLICATORS
ITEM DESCRIPTION FURNISHED
SET IN
PLACE INSTALLED
CONDUIT
OH / UG
TUNNEL
CONTROL
FUNCTION CONTROL WIRE SIZE/ TYPE CONTROL WIRE QUANTITY/ TYPE CONTROL CONNECTION TYPE CONTROL FED FROM/ FEEDS TO
POWER FEED
FROM/FEEDS TO HARDWARE
WIRE DEVICE TO
CONTROLLER
PROVIDE
CONDUIT(S) PLUMBING IN MOUNTING BACKING COMMENTS
E661 APPLICATOR; BUG SPRAY LOWER O O O - 0 --- - - - - - O
E662 APPLICATOR; BUG SPRAY TOP O O O - 0 --- - - - - - O
E663a APPLICATOR; PRESOAK PEDESTAL SET SIDE - BACK O O O - 0 --- - - - - - O
E663b APPLICATOR; PRESOAK PEDESTAL SET FRONT - SIDE O O O - 0 --- - - - - - O
E664a APPLICATOR; PRESOAK CTA SET 1 O O O - 0 --- - - - - - O
E665 APPLICATOR; TOP BRUSH 1 WATER; MANIFOLD (PECO SUPPLIED)O O O - 0 --- - - - - - O
E666 APPLICATOR; UNDERCARRIAGE BLAST MANIFOLD O O O - 0 --- - - - - - O
E668 APPLICATOR; MUD BLASTER SET O O O - 0 --- - - - - - O
E670 APPLICATOR; SIDE BRUSH 1 WATER; MANIFOLD (PECO SUPPLIED)O O O - 0 --- - - - - - O
E671 APPLICATOR; RANBOW FOAM RAIN BAR O O O - 0 --- - - - - - O
E672 APPLICATOR; TOP BRUSH 2 WATER; MANIFOLD (PECO SUPPLIED)O O O - 0 --- - - - - - O
E673 APPLICATOR; CARNUBA WAX RAIN BAR O O O - 0 --- - - - - - O
E674 APPLICATOR; WRAPS 1 WATER; MANIFOLDS (PECO SUPPLIED)O O O - 0 --- - - - - - O
E675 APPLICATOR; SIDE BRUSH 2 WATER; MANIFOLD (PECO SUPPLIED)O O O - 0 --- - - - - - O
E676 APPLICATOR; WRAPS 2 WATER; MANIFOLDS (PECO SUPPLIED)O O O - 0 --- - - - - - O
E680 UNDERCARRIAGE RUST INHIBITOR O O O - 0 --- - - - - - O
E681 APPLICATOR; ARCH; MEDIUM PRESSURE RINSE 1 O O O - 0 --- - - - - - O
E682 APPLICATOR; ARCH; MEDIUM PRESSURE RINSE 2 O O O - 0 --- - - - - - O VAN SIDES
E683 APPLICATOR; SURFACE PROTECTANT; RAIN BAR O O O - 0 --- - - - - - O
E684 APPLICATOR; CLEAR COAT PROTECTANT; RAIN BAR O O O - 0 --- - - - - - O VAN SIDES
E685 APPLICATOR; DRYING AGENT; ARCH O O O - 0 --- - - - - - O ARCH
E686 APPLICATOR; REVERSE OSMOSIS; ARCH O O O - 0 --- - - - - - O ARCH
E687 APPLICATOR; TIRE SHINE; MANIFOLD SET (PECO SUPPLIED)O O O - 0 --- - - - - - O ARCH PECO ARCH 18" WIDER; MODIFICATIONS BY SPOTLESS REQUIRED
REVISIONS
#DATE
NOT
F
O
R
C
O
N
S
T
R
U
C
T
I
O
N
FE
1
1
2
2
34
4
5
5
AA
BB
CC
DD
101
MANAGER
102
CONTROL
103
HALL
104
TOILET
105
CLEAN
EQUIPMENT
109
WASH
TUNNEL
107
ELECTRICAL
108
MAT WASH
106
EQUIPMENT
E902
E001aE001bE002
E004
E930E030a
E107
E301E302
E030d E030c
ICLCPLA
TAHA
MSB
E824
E107
E920E030b
E020
E112 E401E402E410
E431E432
E303h
E303g
E303lE303p
E303o E303k
E303d
E303e
E303c
E303b
E303i
E303mE303q
E303n E303j E303f
E303a E125
E126a
E126b
E122a
E122b
E121
E823b
E823b
E825a
E822
E825bE825c
E501
E420
E502
E201
UH-2
UH-1
10 44 16
E003c
E003b
E003d
E030
TTB
VFD1
VFD2
E823a
TCMCC E830
E840
E662
E421
E601 E611
E635E636
E637
E003a E111
E110 E109
E403E404E405E406
E422 E634 E633
E632a
E632b
E686
E685
E646
E645
E681
E680
E661
E683
E684
E825d
E631
E830
E666
E643
E642
E644
E682E647
E648
E649
E650
E651E652E653
E805
18' - 0"
6'
-
8
"
14' - 6"7' - 10" 4' - 2" 1' - 0" 3' - 3" 14' - 5"6' - 10" 2' - 1" 2' - 5"2' - 8" 11" 3' - 0" 1' - 8" 1' - 8" 3' - 9" 1' - 6"30' - 4"3' - 0" 4' - 0" 4' - 0" 4' - 1" 3' - 11" 2' - 8"
5' - 11" 4' - 10" 5' - 5"9' - 8" 4' - 6" 6' - 2"2' - 7" 2' - 7" 6' - 0" 4' - 9" 4' - 6" 2' - 9" 7' - 6" 9' - 0"
E663a
E663b
E664a
E665
E668
E671
E123aE124a
E124bE123b
E670
E673
E675
E674E676
E802
E903
E801a
E801b
E904
E905
E804
E906
E907
E803
E908E910E911
E201a
E108
E101
E103E102
STAMP:
THESE DOCUMENTS HAVE BEEN PRODUCED AS AN
INSTRUMENT OF SERVICE AND ARE INTENDED SOLELY
FOR THE PURPOSE OF CONSTRUCTING, USING AND
MAINTAINING THE PROJECT. SPOTLESS WASH
SOLUTIONS USA INC, AS THE ARCHITECT OF RECORD
FOR THE PROJECT RETAINS OWNERSHIP OF THESE
DOCUMENTS.
ANY USE OF THESE DOCUMENTS OR USE OF THIS
DESIGN, IDEAS OR CONCEPTS DESCRIBED HEREIN IN
WHOLE OR PART BY ANY MEANS WHATSOEVER IS
STRICTLY PROHIBITED EXCEPT BY WRITTEN CONSENT
OF SPOTLESS WASH SOLUTIONS USA INC.
REPRODUCTION OF THIS DOCUMENT IS STRICTLY
PROHIBITED EXCEPT BY WRITTEN CONSENT OF
SPOTLESS WASH SOLUTIONS USA INC.
COPYRIGHT 2022
SPOTLESS WASH SOLUTIONS USA INC.
CHECKED:
DATE:
JOB NUMBER:
ISSUED FOR:
SHEET NUMBER:
SP
O
T
L
E
S
S
W
A
S
H
S
O
L
U
T
I
O
N
S
PO
B
O
X
5
4
5
6
TW
I
N
F
A
L
L
S
,
I
D
A
H
O
8
3
3
0
3
PH
.
(
2
0
8
)
8
4
1
-
4
5
2
4
DRAWN:
BI
N
D
I
N
G
02/15/2022
PERMIT REVIEW SET
NOT FOR CONSTRUCTION
21005
BUILDING PERMIT - NFC
A1.6d
EQUIPMENT PLAN /
MOTOR LIST
AS
NI
T
R
O
C
A
R
W
A
S
H
RE
X
B
U
R
G
,
I
D
13
7
1
N
2
N
D
E
RE
X
B
U
R
G
,
I
D
8
3
4
4
8
5/4/22
E100 - E300 MOTOR LIST
ITEM DESCRIPTION HP VOLTAGE (V) PANEL
TUNNEL CONTROL
FUNCTION
VFD IN
MCC
VFD WITH
UNIT STARTER IN MCC
STARTER WITH
UNIT
PROVIDE TWIST LOCK
PLUG COMMENTS
E101 PUMP HFX; HSW PUMP 1;7.5 480 HA 0 1 0 0 0 1 TRANSDUCER
E102 PUMP HFX; HSW PUMP 2;7.5 480 HA 0 1 0 0 0 1 TRANSDUCER
E104 PUMP; SUMP RECLAIM; MAIN SUPPLY 30 480 HA 0 1 0 0 0 0 FLOAT LOW-LEVEL SHUT-OFF; HIGH-TEMP SENSOR SHUT-OFF
E105 PUMP; SUMP RECLAIM; AT NIGHT TRENCH FLUSH 3 480 HA 0 0 0 1 0 0 HYDROSONIC SENSOR LOW-LEVEL SHUT-OFF
E106 PUMP; RECLAIM HIGH PRESSURE 30 480 MCC 1 1 0 0 0 1 -
E107 PUMP; RECLAIM HIGH PRESSURE 30 480 MCC 1 1 0 0 0 1 -
E108 PUMP; MUD BLAST 30 480 MCC 1 1 0 0 0 1 -
E109 PUMP; RO PRODUCTION 3 480 HA 0 0 1 0 0 0 -
E110 PUMP; RO DELIVERY 2 480 MCC 1 1 0 0 0 0 -
E111 PUMP; RO REJECT RECOVERY 2 480 HA 0 0 1 0 0 1 -
E112 PUMP; PRESSURE WASHER W/ WALL BRACKET 7.5 208 LA 0 0 0 0 1 0 STARTER IN UNIT
E121 MOTOR, TOP BRUSH 1 480 MCC 1 1 0 0 0 0 HOMERUN VFD CABLE DIRECT FROM MOTOR TO MCC (NO SPLICING)
E122a MOTOR, WRAPS 1 DS 1 480 MCC 1 1 0 0 0 0 -
E122b MOTOR, WRAPS 1 PS 1 480 MCC 1 1 0 0 0 0 -
E123a MOTOR, ROCKER 1 PS 1 480 MCC 1 1 0 0 0 0 -
E123b MOTOR, ROCKER 1 DS 1 480 MCC 1 1 0 0 0 0 -
E124a MOTOR, ROCKER 2 PS 1 480 MCC 1 1 0 0 0 0 -
E124b MOTOR, ROCKER 2 DS 1 480 MCC 1 1 0 0 0 0 -
E125 MOTOR, TOP BRUSH 2 1 480 MCC 1 1 0 0 0 0 -
E126a MOTOR, WRAPS 2 DS 1 480 MCC 1 1 0 0 0 0 -
E126b MOTOR, WRAPS 2 PS 1 480 MCC 1 1 0 0 0 0 -
E127a MOTOR, TIRE SHINE DS 1 480 MCC 1 1 0 0 0 0 -
E127b MOTOR, TIRE SHINE PS 1 480 MCC 1 1 0 0 0 0 -
E130 MOTOR; SPEED DOOR & CONTROL BOX; EXIT 2 208 LA 1 0 1 0 0 0 -
E201 PUMP, HYDRAULIC, CONVEYOR 10 480 MCC 1 0 0 1 0 0 24VAC LOW OIL SWITCH TO TC
E301 AIR COMPRESSOR 1 10 480 HA 0 0 0 0 1 0 STARTER SUPPLIED BY VENDOR IN UNIT
E302 AIR COMPRESSOR 2 10 480 HA 0 0 0 0 1 0 STARTER SUPPLIED BY VENDOR IN UNIT
E303a BLOWER 1 15 480 MCC 1 0 0 1 0 0 AIR VALVE KIT
E303b BLOWER 2 15 480 MCC 1 0 0 1 0 0 AIR VALVE KIT
E303c BLOWER 3 15 480 MCC 1 0 0 1 0 0 AIR VALVE KIT
E303d BLOWER 4 15 480 MCC 1 0 0 1 0 0 AIR VALVE KIT
E303e BLOWER 5 15 480 MCC 1 0 0 1 0 0 AIR VALVE KIT
E303f BLOWER 6 15 480 MCC 1 0 0 1 0 0 AIR VALVE KIT
E303g BLOWER 7 15 480 MCC 1 0 0 1 0 0 AIR VALVE KIT
E303h BLOWER 8 15 480 MCC 1 0 0 1 0 0 AIR VALVE KIT
E303i BLOWER 9 15 480 MCC 1 0 0 1 0 0 AIR VALVE KIT
E303j BLOWER 10 15 480 MCC 1 0 0 1 0 0 AIR VALVE KIT
E303k BLOWER 11 15 480 MCC 1 0 0 1 0 0 AIR VALVE KIT
E303l BLOWER 12 15 480 MCC 1 0 0 1 0 0 AIR VALVE KIT
E303m BLOWER 13 15 480 MCC 1 0 0 1 0 0 AIR VALVE KIT
E303n BLOWER 14 15 480 MCC 1 0 0 1 0 0 AIR VALVE KIT
E303o BLOWER 15 15 480 MCC 1 0 0 1 0 0 AIR VALVE KIT
E303p BLOWER 16 15 480 MCC 1 0 0 1 0 0 AIR VALVE KIT
E303q BLOWER 17 15 480 MCC 1 0 0 1 0 0 AIR VALVE KIT
E304 VAC PRODUCER 50 480 MDP 0 0 1 0 0 0 VFD 1 AT ELECTRICAL ROOM, DISCONNECT BY MOTOR
E305 VAC PRODUCER 50 480 MDP 0 0 1 0 0 0 VFD 1 AT ELECTRICAL ROOM, DISCONNECT BY MOTOR
551.5 35 19 5 19 3 6
NORTH
0'4'2'8'
GENERAL NOTES
A. FOR EQUIPMENT AND ACCESSORY MOUNTING HEIGHTS, SEE SHEET A2.3.
B. WALL-MOUNTED ACCESSORIES AND EQUIPMENT TO BE ATTACHED TO STUD FRAMING,
BACKING AND / OR BLOCKING IN ACCORDANCE WITH THE EQUIPMENT SCHEDULE. WALL
MOUNTED ITEMS AT CONCRETE WALLS DO NOT REQUIRE BACKING.
C. COORDINATE SEQUENCING AND INSTALLATION OF EQUIPMENT POWER AND PLUMBING
SYSTEMS WITH OWNER'S CONSTRUCTION FORCES.
D. WHERE A SINGLE EQUIPMENT TAG IS USED TO REFERENCE A GROUP OF ITEMS THE "E" IS
SOMETIMES OMITTED.
E. PROVIDE ALL INDICATED CONDUITS AND VALVES FOR ALL EQUIPMENT INDICATED ON
EQUIPMENT SCHEDULE TO BE "FUTURE" .
3/16" = 1'-0"
EQUIPMENT PLAN
REVISIONS
#DATE
NOT
F
O
R
C
O
N
S
T
R
U
C
T
I
O
N
1' - 0" 1' - 0"
48" TYP
TAPERED RIGID INSULATION -
BEGIN INSULATION HERE AT
1/4" : 12"
NOTE: ACTUAL DEPTH OF PRECAST ROOF IS NOT SHOWN
ROOF DRAIN
TAPERED RIGID INSULATION -
BEGIN INSULATION HERE AT
1/4" : 12"
ROOF OVERFLOW
DRAIN
SECTION
1/4" : 12"
STRUCTURE SLOPE
1/4" : 12" TAPERED
INSULATION SLOPE
1/4" : 12" TAPERED
INSULATION SLOPESLOPED
RD
SECTION SECTION
PLAN
1"
INSULATION SUMP
NOTE: WATER INLET AT THE OVERFLOW ROOF DRAIN
IS TO BE 2" HIGHER THAN AT THE ROOF DRAIN
ORD7/8"2
1
/
4
"
1 1 /2 "
4 3 /8 "
1"
1"
4"
1/2"
5"
6"
4"
1 1/4"
1/2"2
1
/
8
"
1"
3"
1 1/2"
3"1/2"
CUSTOM J HIGH
SIDE AND RAKE
CUSTOM DRIP
HIGH SIDE & RAKE ANGLE TRIM
ALL SIDES
MT-26 EAVE TRIM
STANDARD
LOW SIDE
MT-61 GUTTER
STANDARD
LOW SIDE
1
1
2
2
3
3
4
4
5
5
AA
BB
CC
DD
5'
-
0
"
1
5
'
-
0
"
20
'
-
0
"
1/4" / 12"
1/4" / 12"
1/
4
"
/
1
2
"
1/
4
"
/
1
2
"
R1
22 14 26.13
03 41 13
12' - 0"12' - 0"93' - 0"20' - 0"
1
2 223
1/4" / 12"1/4" / 12"1/4" / 12"
1/4" / 12"
5
A1.7
4
A1.7A3
A3.3
3
A1.7
2
A1.7
2
A1.7
2
A1.7
07 61 13
07 62 00
07 62 00
07 42 14 *PF9
*PF9
*PF4
*PF1
1 1 1 1
1
1/4" / 12"
1
10 71 13.43
07 72 33
4
07 54 23
3
METAL GUTTER, MATCH ROOF
COLOR
STANDING SEAM METAL ROOF WITH
ROOF UNDERLAYMENT
INSIDE CLOSURE W/ 1"
(25mm) ROLL TAPE SELANT
(TOP & BOT)
ROOF UNDERLAYMENT
DRIP FLASHING
SHEATHING, SEE STRUCT.
ICE AND WATER SHIELD
PRE-FINISHED METAL SOFFIT ANGLE
METAL SOFFIT PANELS
PRE-FINISHED METAL FASCIA PANEL
SHEATHING, SEE STRUCT.
ROOF UNDERLAYMENT
ICE AND WATER SHIELD
FASTENING CLEAT
MAXIMA 2" ARCHITECTURAL
RAKE TRIM
LOW FIXED RAKE
SUPPORT ANGLE
3/32" x 1" ROLL TAPE SEALANT
(TOP AND SIDE OF ANGLE TRIM)
ICE AND WATER SHIELD
MAXIMA 2" PANEL OVER
THERMAL SPACER &
ROOF UNDERLAYMENT
FIELD CUT PANEL AND
TURN UP PANEL EDGE 2" (51mm)
43D POP RIVET
(@ 1'-0" O.C. (305mm))
3/32" x 1" ROLL TAPE SEALANT
(TOP AND SIDE OF ANGLE TRIM)
PRE-FINISHED METAL SOFFIT ANGLE
METAL SOFFIT PANELS
PRE-FINISHED METAL FASCIA PANEL
INSIDE CLOSURE W/ 1"
(25mm) ROLL TAPE SELANT
(TOP & BOT)
ICE AND WATER SHIELD
FASTENING CLEAT
SHEATHING, SEE STRUCT.
HIGH-SIDE EVE TRIM AND CUSTOM
J-TRIM
ROOF UNDERLAYMENT
ROOF UNDERLAYMENT
PRE-FINISHED METAL SOFFIT ANGLE
METAL SOFFIT PANELS
PRE-FINISHED METAL FASCIA PANEL
STAMP:
THESE DOCUMENTS HAVE BEEN PRODUCED AS AN
INSTRUMENT OF SERVICE AND ARE INTENDED SOLELY
FOR THE PURPOSE OF CONSTRUCTING, USING AND
MAINTAINING THE PROJECT. SPOTLESS WASH
SOLUTIONS USA INC, AS THE ARCHITECT OF RECORD
FOR THE PROJECT RETAINS OWNERSHIP OF THESE
DOCUMENTS.
ANY USE OF THESE DOCUMENTS OR USE OF THIS
DESIGN, IDEAS OR CONCEPTS DESCRIBED HEREIN IN
WHOLE OR PART BY ANY MEANS WHATSOEVER IS
STRICTLY PROHIBITED EXCEPT BY WRITTEN CONSENT
OF SPOTLESS WASH SOLUTIONS USA INC.
REPRODUCTION OF THIS DOCUMENT IS STRICTLY
PROHIBITED EXCEPT BY WRITTEN CONSENT OF
SPOTLESS WASH SOLUTIONS USA INC.
COPYRIGHT 2022
SPOTLESS WASH SOLUTIONS USA INC.
CHECKED:
DATE:
JOB NUMBER:
ISSUED FOR:
SHEET NUMBER:
SP
O
T
L
E
S
S
W
A
S
H
S
O
L
U
T
I
O
N
S
PO
B
O
X
5
4
5
6
TW
I
N
F
A
L
L
S
,
I
D
A
H
O
8
3
3
0
3
PH
.
(
2
0
8
)
8
4
1
-
4
5
2
4
DRAWN:
BI
N
D
I
N
G
02/15/2022
PERMIT REVIEW SET
NOT FOR CONSTRUCTION
JH
21005
BUILDING PERMIT - NFC
A1.7
ROOF PLAN
AS
NI
T
R
O
C
A
R
W
A
S
H
RE
X
B
U
R
G
,
I
D
13
7
1
N
2
N
D
E
RE
X
B
U
R
G
,
I
D
8
3
4
4
8
5/4/22
GENERAL NOTES
A. VERIFY EXISTING ROOF SLOPES FOR CONFORMANCE TO SLOPES INDICATED ON
DRAWINGS. CERTIFY THAT ENTIRE ROOF IS MAINTAINING POSITIVE DRAINAGE
B. CERTIFY THAT ALL DRAINAGE FROM ROOF IS AND WILL CONTINUE FUNCTIONING AND
DRAINING WITHOUT WATER INTRUSION.
C. PROVIDE DRAINAGE CRICKETS AT ALL MECHANICAL OR OTHER ROOF CURBS AS REQUIRED
TO PROVIDE POSITIVE DRAINAGE, EVEN IF NOT INDICATED ON DRAWINGS
D. PROVIDE GALVANIZED PRE-FINISHED (COLOR AS SELECTED BY OWNER) FLASHINGS,
COUNTER-FLASHINGS, REGLETS, DRIP-EDGES, VENTS, AND COPINGS OF MINIMUM 22
GAUGE.
E. PROVIDE MINIMUM #60 ASPHALT INFUSED ROOFING FELT BENEATH ALL NON-METAL
ROOFING SYSTEMS.
F. PROVIDE BITUMINOUS RUBBERIZED ASPHALT WATER-PROOF ICE/WATER SHIELD BENEATH
ALL METAL ROOFING SYSTEMS.
G. BASIS-OF-DESIGN MATERIALS:
a. TPO ROOF MEMBRANE SYSTEM: MULE-HIDE, 60 MIL, FULLY-ADHERED, WHITE
b. ROOF HATCH: BILCO, E-20, 36"x36", WITH LADDERUP SAFETY POST
c. STANDING SEAM METAL ROOF: MBCI, BATTENLOK HS, 12", OR EQUAL, COATED
ALUMINUM, MUST MATCH MP1 COIL COLOR, KYNAR 500
SHEET NOTES
#:DESCRIPTION:
1 DRAINAGE CRICKET
2 AFTER HOLLOW CORE SLAB ERECTION, OWNER WILL INSTALL METAL TEES BETWEEN SECTIONS
OF SLABS. COORDINATE SCHEDULE WITH OWNER FOR THOSE INSTALLATION ACTIVITES.
3 ROOFTOP MECHANICAL UNITS ARE NOT SHOWN. REFERENCE MECHANICAL PLANS. PROVIDE
INSULATED CURBS AND TAPERED INSULATION CRICKETS AT ALL UNITS.
4 ROOF ACCESS HATCH W/ INSULATED CURB. COORDINATE LOCATION W/ PRECAST ROOF SLAB
LAYOUT.
KEYNOTES
#:DESCRIPTION:
03 41 13 PRECAST CONCRETE HOLLOW CORE PLANKS
07 42 14 METAL SLAT CLADDING SYSTEM
07 54 23 THERMOPLASTIC-POLYOLEFIN (TPO) ROOFING, 60 MIL, WHITE
07 61 13 STANDING SEAM METAL ROOF
07 62 00 SHEET METAL FLASHING AND TRIM
07 72 33 ROOF HATCH, BASIS-OF-DESIGN IS BILCO E-20 OR APPROVED EQUAL
10 71 13.43 FIXED SUN SCREENS INTEGRAL WITH ALUMINUM STOREFRONT
22 14 26.13 ROOF DRAIN
1 : 10
ROOF DRAIN AND OVERFLOW DRAIN2 1 : 5
METAL ROOF FLASHING1
NORTH
0'8'4'16'
1/8" = 1'-0"
ROOF PLAN
3" = 1'-0"
LOWER FASCIA33" = 1'-0"
RAKE FASCIA43" = 1'-0"
UPPER FASCIA5
FINISH SCHEDULE
MARK:DESCRIPTION:
*PF1 PREFINISHED METAL, MBCI, SIGNATURE 200, 24GA MIN, CHARCOAL GRAY
*PF4 PRE-FINISHED STANDING SEAM METAL ROOF, 24GA MIN, MATCH MP1, RED
*PF9 PRE-FINISHED METAL, 24GA MIN, MATCH MP1, RED
REVISIONS
#DATE
NOT
F
O
R
C
O
N
S
T
R
U
C
T
I
O
N
1
1
2
2
3
3
4
4
5
5
1
A3.1
1
A3.1
3
A3.1
3
A3.1
2
A3.1
2
A3.1
AA
BB
CC
DD
106
EQUIPMENT107
ELECTRICAL
108
MAT WASH
109
WASH
TUNNEL
105
CLEAN
EQUIPMENT
103
HALL
104
TOILET
102
CONTROL
101
MANAGER
4
A3.1
4
A3.1
10' - 6"
10' - 6"
10' - 6"
2
5 4 2
8
8
8
7
6
3
07 42 93
07 62 00
10 71 13.43
07 42 14
09 51 13
09 51 13
03 41 13
26 51 00
05 12 23
E644E645E646E647E648E649E650E651E652E653 E643 E642
*PF1
*PF9
*PF9
*PF7
4
A1.7
5
A1.7
3
A1.7
905 51 33
07 72 33
26 51 00
26 51 00
26 51 00
1
A1.1
12 24 13
12 24 13
9' - 0"
UH-2 UH-1
1
2 2
6
1 1 1 1 1
6
5 5 5
5
5
5
5
26 51 00
26 51 00
26 51 00
26 51 0026 51 0026 51 00
STAMP:
THESE DOCUMENTS HAVE BEEN PRODUCED AS AN
INSTRUMENT OF SERVICE AND ARE INTENDED SOLELY
FOR THE PURPOSE OF CONSTRUCTING, USING AND
MAINTAINING THE PROJECT. SPOTLESS WASH
SOLUTIONS USA INC, AS THE ARCHITECT OF RECORD
FOR THE PROJECT RETAINS OWNERSHIP OF THESE
DOCUMENTS.
ANY USE OF THESE DOCUMENTS OR USE OF THIS
DESIGN, IDEAS OR CONCEPTS DESCRIBED HEREIN IN
WHOLE OR PART BY ANY MEANS WHATSOEVER IS
STRICTLY PROHIBITED EXCEPT BY WRITTEN CONSENT
OF SPOTLESS WASH SOLUTIONS USA INC.
REPRODUCTION OF THIS DOCUMENT IS STRICTLY
PROHIBITED EXCEPT BY WRITTEN CONSENT OF
SPOTLESS WASH SOLUTIONS USA INC.
COPYRIGHT 2022
SPOTLESS WASH SOLUTIONS USA INC.
CHECKED:
DATE:
JOB NUMBER:
ISSUED FOR:
SHEET NUMBER:
SP
O
T
L
E
S
S
W
A
S
H
S
O
L
U
T
I
O
N
S
PO
B
O
X
5
4
5
6
TW
I
N
F
A
L
L
S
,
I
D
A
H
O
8
3
3
0
3
PH
.
(
2
0
8
)
8
4
1
-
4
5
2
4
DRAWN:
BI
N
D
I
N
G
02/15/2022
PERMIT REVIEW SET
NOT FOR CONSTRUCTION
JH
21005
BUILDING PERMIT - NFC
A1.8
REFLECTED
CEILING PLAN
AS
NI
T
R
O
C
A
R
W
A
S
H
RE
X
B
U
R
G
,
I
D
13
7
1
N
2
N
D
E
RE
X
B
U
R
G
,
I
D
8
3
4
4
8
5/4/22
GENERAL NOTES
A. REFER TO ROOM FINISH SCHEDULE ON SHEET A6.1 FOR CEILING
DESIGNATIONS AND HEIGHTS.
B. ALL CEILING MOUNTED ELECTRICAL AND MECHANICAL DEVICES TO BE AT
CENTER OF CEILING PANEL AS DEFINED BY THE PANEL PATTERN.
C. HVAC DIFFUSERS SHOWN FOR COORDINATION ONLY -SEE MECHANICAL
HVAC PLANS FOR SIZES OF GRILLES, ETC.
D. LIGHTING AND ELECTRICAL DEVICES SHOWN FOR COORDINATION ONLY -
SEE ELECTRICAL PLANS FOR MORE INFORMATION ON LIGHTING.
E. NOT ALL EXPOSED STRUCTURE IS ILLUSTRATED.
F. SUSPENDED CEILINGS SHALL BE INSTALLED IN ACCORDANCE WITH 2015 IBC
SECTION 808.1, ASTM C635, ASTM C636.
G. ALL PENETRATIONS THROUGH HOLLOW CORE ROOF PLANKS REQUIRE
WRITTEN ARCHITECT APPROVAL.
H. NOT ALL CEILING AND ROOF PENETRATIONS ARE IDENTIFIED ON THIS PLAN.
SEE MECHANICAL AND ELECTRICAL DRAWINGS FOR ADDITIONAL
REQUIREMENTS.
I. PROVIDE SEALANT AT ENTIRE PERIMETER AT CAR WASH TUNNEL WHERE
PRECAST ROOF PANELS MEET CONCRETE WALL PANELS, TYPICAL.
J. SEE ROOF PLAN FOR ALL ROOF DRAIN LOCATIONS.
K. PROVIDE CORE HOLES FOR ALL BOILER VENTS AND AIR INTAKE PIPES, ROOF
DRAINS AND OTHER HOLLOW CORE DECK PENETRATIONS THE PRECASTER IS
NOT PROVIDING HOLES FOR.
REVEAL IN CEILING PANEL
WHERE APPLICABLE
OS
RCP LEGEND
CEILING / WALL MOUNTED EXIT SIGN
RETURN GRILLE
SUPPLY DIFFUSERS
OCCUPANCY SENSOR
RECESSED CAN FIXTURE
2' x 2' RECESSED FIXTURE
8' LONG LED -SURFACE MOUNTED AT UNDERSIDE OF DECK
EXHAUST FANS
2' x 4' RECESSED FIXTURE
3/16" = 1'-0"
REFLECTED CEILING PLAN 0'4'2'8'
NORTH
SHEET NOTES
# DESCRIPTION
1 BLOWER SUPPORT BEAM, SEE A2.4.
2 MANUALLY OPERATED OVERHEAD COILING DOOR AND HOOD FURNISHED BY OWNER AND INSTALLED BY CONTRACTOR.
3 BOILER VENTS AND AIR INTAKE PIPES. VENT AND AIR INTAKE PIPES AND ROOF TERMINATIONS ARE SUPPLIED AND INSTALLED BY CONTRACTOR.
SEE MANUFACTURER'S LITERATURE FOR REQUIREMENTS. FIELD CORE HOLLOW CORE PANELS AFTER PLACEMENT OF EQUIPMENT TO ENSURE VENT
PIPES ARE PLUMB WITH NO JOGS OR OFFSETS FROM UNIT THROUGH ROOF.
4 PROVIDE SEALANT AT ENTIRE PERIMETER OF TUNNEL WHERE HOLLOW CORE MEETS WALLS. SEALANT COLOR SHALL APPROXIMATE CONCRETE
COLOR.
5 MECHANICAL ROOF PENETRATION. SEE MECHANICAL FOR SIZE OF OPENINGS. COORDINATE SIZE AND EXACT PLACEMENT WITH ALL TRADES.
6 ROOF AND OVERFLOW DRAIN LEADER PIPE DECK PENETRATION.
7 SUSPENDED GYPSUM BOARD CEILING.
8 SUSPENDED ACOUSTICAL PANEL CEILING SYSTEM.
9 ROOF ACCESS HATCH LOCATION. COORDINATE LOCATION W/ PRECAST ROOF SLAB LAYOUT.
KEYNOTES
MARK:DESCRIPTION:
03 41 13 PRECAST CONCRETE HOLLOW CORE PLANKS
05 12 23 STRUCTURAL STEEL FOR BUILDINGS
05 51 33 METAL LADDER
07 42 14 METAL SLAT CLADDING SYSTEM
07 42 93 METAL SOFFIT PANEL
07 62 00 SHEET METAL FLASHING AND TRIM
07 72 33 ROOF HATCH, BASIS-OF-DESIGN IS BILCO E-20 OR APPROVED EQUAL
09 51 13 ACOUSTICAL PANEL CEILINGS
10 71 13.43 FIXED SUN SCREENS INTEGRAL WITH ALUMINUM STOREFRONT
12 24 13 ROLLER WINDOW SHADES
26 51 00 INTERIOR LIGHTING
REVISIONS
#DATE
NOT
F
O
R
C
O
N
S
T
R
U
C
T
I
O
N
T/O FLOOR
100' -0"
T/O PARAPET 1
117' -0"
T/O PARAPET 2
119' -0"
T/O Tower
123' -0"
ABCD
07 42 13.1
03 41 00
03 41 00
03 41 00
OH109b
107
C8a
C8
C8
C8
*MP1
07 62 00
10 71 13.43
07 42 14
07 62 00
03 41 00 *TP1
*MP2
*PF7
*PF1
*PF2
*TP2
07 62 00
07 61 13
*PF9
*PF4
*TP3
*TP4
*TP3
*TP1
10 14 33
*TP5
*TP1
*TP1 *TP1
R2
T/O FLOOR
100' -0"
T/O PARAPET 1
117' -0"
T/O PARAPET 2
119' -0"
1345
03 41 00
03 41 00
03 41 00*TP1
03 41 00 *TP2
C8a
C8
C8
OH108
106a OH106 104
07 42 14
10 71 13.43
08 43 13
*PF9
*PF7
*PF6
*TP103 41 00102a
S4
S5
03 41 00
07 62 00
*TP3
*TP1
*PF9
07 62 00 *PF2
C8 C8
C8
2 " / 1 2 "
*TP2
*MP1
07 62 00*MP2
*TP3
*PF1
14' - 0"
10' - 0"
07 62 00
10 14 33
10 14 33
*TP5 *TP5
28' - 1"
T/O FLOOR
100' -0"
T/O PARAPET 1
117' -0"
T/O PARAPET 2
119' -0"
T/O Tower
123' -0"
1 2 4 5
C8 C8
*TP1 *TP3
S6S6S6S7
08 43 13
10 14 33
C8
*TP2
C8C8C8
*TP1
*TP1
*TP3
07 42 14
10 71 13.43
08 42 13
07 62 00
2" / 12"
07 62 00*PF1
*PF9
*PF6
*PF7
S1 102b
*PF1
*PF6
*PF9
10 14 33 07 62 0010 14 33
S7
101' - 0"
108' - 0"
103' - 0"
128' - 1 1/4"
T/O FLOOR
100' -0"
T/O PARAPET 1
117' -0"
A C D
OH109a
S3 S2
03 41 00
08 43 13
10 71 13.43
07 42 14
07 62 00
03 41 00
07 62 00
*PF1
*PF9
*PF7
*PF6 C8
C8
*TP1 *TP3 *TP3
*PF9
07 42 93 *PF1
10 14 33
STAMP:
THESE DOCUMENTS HAVE BEEN PRODUCED AS AN
INSTRUMENT OF SERVICE AND ARE INTENDED SOLELY
FOR THE PURPOSE OF CONSTRUCTING, USING AND
MAINTAINING THE PROJECT. SPOTLESS WASH
SOLUTIONS USA INC, AS THE ARCHITECT OF RECORD
FOR THE PROJECT RETAINS OWNERSHIP OF THESE
DOCUMENTS.
ANY USE OF THESE DOCUMENTS OR USE OF THIS
DESIGN, IDEAS OR CONCEPTS DESCRIBED HEREIN IN
WHOLE OR PART BY ANY MEANS WHATSOEVER IS
STRICTLY PROHIBITED EXCEPT BY WRITTEN CONSENT
OF SPOTLESS WASH SOLUTIONS USA INC.
REPRODUCTION OF THIS DOCUMENT IS STRICTLY
PROHIBITED EXCEPT BY WRITTEN CONSENT OF
SPOTLESS WASH SOLUTIONS USA INC.
COPYRIGHT 2022
SPOTLESS WASH SOLUTIONS USA INC.
CHECKED:
DATE:
JOB NUMBER:
ISSUED FOR:
SHEET NUMBER:
SP
O
T
L
E
S
S
W
A
S
H
S
O
L
U
T
I
O
N
S
PO
B
O
X
5
4
5
6
TW
I
N
F
A
L
L
S
,
I
D
A
H
O
8
3
3
0
3
PH
.
(
2
0
8
)
8
4
1
-
4
5
2
4
DRAWN:
BI
N
D
I
N
G
02/15/2022
PERMIT REVIEW SET
NOT FOR CONSTRUCTION
JH
21005
BUILDING PERMIT - NFC
A2.1
EXTERIOR
ELEVATIONS
AS
NI
T
R
O
C
A
R
W
A
S
H
RE
X
B
U
R
G
,
I
D
13
7
1
N
2
N
D
E
RE
X
B
U
R
G
,
I
D
8
3
4
4
8
5/4/22
KEYNOTES
MARK:DESCRIPTION:
03 41 00 PRECAST CONCRETE WALL PANELS, TYPICAL.
07 42 13.1 ACM WALL PANEL, REYNOBOND, COLORWELD 500
07 42 14 METAL SLAT CLADDING SYSTEM
07 42 93 METAL SOFFIT PANEL
07 61 13 STANDING SEAM METAL ROOF
07 62 00 SHEET METAL FLASHING AND TRIM
08 42 13 ALUMINUM-FRAMED ENTRANCE
08 43 13 ALUMINUM-FRAMED STOREFRONT
10 14 33 SIGNAGE BY OTHERS REQUIRES SEPARATE PLAN REVIEW AND PERMIT
10 71 13.43 FIXED SUN SCREENS INTEGRAL WITH ALUMINUM STOREFRONT
FINISH SCHEDULE
MARK:DESCRIPTION:
*MP1 ALUMINUM COMPOSITE METAL PANEL, ALPOLIC, 4MM, BTR RED #4-BTR-50
*MP2 TRIM AT ACM PANELS, COIL TO MATCH MP1, 24GA MIN
*PF1 PREFINISHED METAL, MBCI, SIGNATURE 200, 24GA MIN, CHARCOAL GRAY
*PF2 PREFINISHED METAL, MBCI, SIGNATURE 300, 24GA MIN, SLATE GRAY
*PF4 PRE-FINISHED STANDING SEAM METAL ROOF, 24GA MIN, MATCH MP1, RED
*PF6 PREFINISHED ALUMINUM STOREFRONT SYSTEM; CLEAR, ANNODIZED
*PF7 PREFINISHED ALUMINUM FIXED SUN SCREEN; MATCH MP1, RED
*PF9 PRE-FINISHED METAL, 24GA MIN, MATCH MP1, RED
*TP1 BUILDING DARK GRAY PAINT COLOR: SPRAY APPLIED TEXTURE / PAINT - ACRYLIC TEXTURE
COATING - BM OVERCOAT #CC-544; (2) COATS ACRYLIC TEXTURE COATING; (1) COAT
EXTERIOR LATEX
*TP2 BUILDING MEDIUM GRAY PAINT COLOR: SPRAY APPLIED TEXTURE / PAINT - ACRYLIC TEXTURE
COATING - BM COBBLESTONE PATH #1606; (2) COATS ACRYLIC TEXTURE COATING; (1) COAT
EXTERIOR LATEX
*TP3 BUILDING RED PAINT COLOR: SPRAY APPLIED TEXTURE / PAINT - ACRYLIC TEXTURE COATING -
COLOR TBD; (2) COATS ACRYLIC TEXTURE COATING; (1) COAT EXTERIOR LATEX
*TP4 BUILDING WHITE: SPRAY APPLIED TEXTURE / PAINT - ACRYLIC TEXTURE COATING - COLOR
TBD; (2) COATS ACRYLIC TEXTURE COATING; (1) COAT EXTERIOR LATEX
*TP5 EXTERIOR STEEL CHARCOAL GRAY PAINT COLOR TO MATCH TP1; FACTORY PRIME STEEL AND
APPLY WEATHERSKIN 5 YEAR EXTERIOR PAINTING SYSTEM WITH PRIME-, BASE-, AND
TOPCOAT; GLOSS SHEEN
GENERAL NOTES
A. DRAWINGS & SPECIFICATIONS ARE COMPLIMENTARY COMPONENTS OF THE CONTRACT
DOCUMENTS, REVIEW ALL DRAWINGS AND SPECIFICATIONS FOR THE COMPLETE SCOPE OF WORK.
NOTIFY ARCHITECT IMMEDIATELY FOR CLARIFICATION IF INCONSISTENCIES, CONTRADICTIONS OR
OMISSIONS ARE DISCOVERED.
B. DO NOT SCALE DRAWINGS, IF DIMENSIONAL INFORMATION IS REQUIRED & NOT FOUND, NOTIFY
ARCHITECT IMMEDIATELY FOR CLARIFICATION.
C. ALL DIMENSIONS ARE TO COLUMN CENTERLINES OR TO FACE OF FRAMING, U.N.O. CLEAR
DIMENSIONS INDICATE DIMENSION BETWEEN FINISHES.
D. ALL EXPOSED FOUNDATIONS AND FOOTINGS ARE TO BE PAINTED TO MATCH ADJACENT WALL FINISH
OR COLOR AS SELECTED BY OWNER. PROVIDE NECESSARY SURFACE FILLER AS RECOMMENDED BY
MANUFACTURER FOR PARTICULAR APPLICATION.
E. PROVIDE 24 GUAGE PRE-FINISHED METAL FLASHING, DRIP EDGE, AND TRIM TO MATCH ROOFING
COLOR, AS SELECTED BY OWNER.
F. PROVIDE TEXTURED PAINT FINISH AT ALL EXTERIOR CONCRETE SURFACES INCLUDING FACES ONLY
VISIBLE FROM THE ROOF.
G. METAL SLAT CLADDING: BASIS-OF-DESIGN IS AWNEX HOLLYWOOD SUNSCREEN WALL PANELS.
PROVIDE 1"x4" SLAT WITH 4" SPACE BETWEEN SLATS. PROVIDE STANDARD 2-COAT KYNAR FINISH
COLOR MATCHED TO MP1. INSTALL SYSTEM AND ANCHORING PER MANUFACTURER'S PUBLISHED
INSTRUCTIONS.
H. SIGNAGE WHEN ILLUSTRATED IS FOR REFERENCE ONLY. SIGNAGE WILL BE SUBMITTED FOR REVIEW
UNDER SEPARATE PERMIT AND MAY VARY FROM PRELIMINARY INFORMATION PROVIDED ON THIS
DRAWING.
1/8" = 1'-0"
WEST ELEVATION11/8" = 1'-0"
SOUTH ELEVATION2
1/8" = 1'-0"
NORTH ELEVATION31/8" = 1'-0"
EAST ELEVATION4
0'8'4'16'
REVISIONS
#DATE
NOT
F
O
R
C
O
N
S
T
R
U
C
T
I
O
N
FE
F
NOTES:
1.DIMENSIONS ARE FROM FINISHED WALL
SURFACE AND FINISHED FLOOR.
2.ALL DIMENSIONS SHOWN ARE TO TOP OF
OPERATING MECHANISM FOR EACH
ACCESSORY. DIMENSION LINES WITH TWO
DIMENSIONS INDICATE THE MINIMUM AND
MAXIMUM DIMENSION.
KEYNOTES:
A. WATER CLOSET (W.C.)
B. ADJACENT WALL
C. SINK
D. ELECTRICAL RECEPTACLE
E. ELECTRICAL SWITCHES,
THERMOSTATS, F.A. PULLS
F. MINIMUM CLEARANCE
G. KNEE / TOE SPACE
H.DRINKING FOUNTAIN, DUAL
I.FIRE ALARM
J.FIRE EXTINGUISHER
K.FLUSH CONTROL AT OPEN SIDE OF
TOILET (NOT ADJACENT TO WALL)
L.ADA LAVATORY PIPE BOOT.
A K
A
F
C
L
I
E J
D C
L
G
H H
G
SPOUT OUTLET
5' - 0" MIN 4' - 8" MIN
16" - 18"1' - 3" MIN
2'
-
1
0
"
M
A
X
6'
-
8
"
3'
-
1
0
"
1'
-
6
"
U
O
N
4'
-
6
"
27
"
M
I
N
2'
-
1
0
"
M
A
X
38
"
-
4
8
"
36
"
M
A
X
1' - 3" MIN
5" MAX FORWARD
APPROACH
3 1/2" MAX PARALLEL
APPROACH
SP
O
U
T
NOTES:
1. DIMENSIONS ARE FROM FINISHED WALL SURFACE AND FINISHED FLOOR.
2.ALL DIMENSIONS SHOWN ARE TO TOP OF OPERATING MECHANISM FOR EACH ACCESSORY.
DIMENSION LINES WITH TWO DIMENSIONS INDICATE THE MINIMUM AND MAXIMUM DIMENSION.
3.REFER AND VERIFY WITH MANUFACTURER'S RECOMMENDED MOUNTING HEIGHTS.
4.NOT ALL ACCESSORIES ARE SHOWN IN MOUNTING SCHEDULE.
3'
-
6
"
PAPER TOWEL
DISPENSER
SOAP DISPENSER TOILET TISSUE
DISPENSER
SANITARY NAPKIN
DISPOSAL
SANITARY NEEDLE
DISPOSAL
SURFACE MOUNTED
WASTE RECEPTACLE
MIRROR
A1 A2
A3
W.C.
A4 A13
A5 A7
24"X36"
UNLESS
NOTED
OTHERWISE
3'
-
6
"
24" TO WALL
1-
1
/
2
"
M
I
N
.
14
"
-
1
9
"
2'
-
3
"
2'
-
3
"
2'
-
6
"
REFLECTIVE
SURFACE
3'
-
4
"
M
A
X
GRAB BAR GRAB BARS
A8
A10
A9
C.L. OF W.C.
2' - 0" MIN.
MIN.
1' - 0"
33
"
-
3
6
"
33
"
-
3
6
"
MAX
1' - 0" 3' - 6" MIN.
4' - 6" MIN.
39" - 41"
1'
-
6
"
M
I
N
.
39
"
-
4
1
"
T/O FLOOR
100' -0"
4'
-
0
"
09 30 13.1
09 21 16
A10
A9
A6
A4
A5
A12
T/O FLOOR
100' -0"
A10 A9
09 30 13.1
09 21 16
26 51 00
1
A4
A3
A8
A6
T/O FLOOR
100' -0"
A7
A8
4'
-
6
"
26 51 00
09 21 16
09 30 13.1
1
A1
A2
A9
A3
T/O FLOOR
100' -0"
4'
-
6
"
09 30 13.1
09 21 16
26 51 00
A12
A1
A5
A2
A7
T/O FLOOR
100' -0"
WC
12
18
WC
24
36
BC1
25
36
BC2
25
39
2'
-
6
"
1'
-
8
"
2'
-
1
0
"
12 36 61.16
22 42 16.16
BC2
25
39
WC
24
36
WC
24
36
E910
H2
H3
A2.3
4
104
TOILET
105
CLEAN
EQUIPMENT
102
CONTROL 101
MANAGER
103
HALL
A2.311
10
A2.3 3
2'
-
1
"
4'
-
3
"
2' - 1"3' - 11"
3' - 10"4' - 10"2' - 0"
8"
2
'
-
0
"
4
'
-
6
"
12
12 36 61.16
12 36 61.16
22 42 16.16
12 36 61.16
14' - 9"
3' - 8"
A2.3
9
A2.3
2
1'
-
6
"
3'
-
0
"
H4H5
105a
10
3
10
2
b
10
1
10
2
a
10
4
5'
-
8
1
/
2
"
4
'
-
7
1
/
2
"
4
'
-
0
"
12 36 61.1612 36 61.16
12 36 61.16
12 36 61.1612 36 61.16
CT3
A2.5
CT2
A2.5
T/O FLOOR
100' -0"
3'
-
0
"
12 36 61.16
09 65 13.1
103
GL-2GL-4
T/O FLOOR
100' -0"
10
"
2'
-
1
0
"
3'
-
1
1
/
2
"
BC4
24
18
12 32 1609 65 13.1
12 36 61.1612 36 61.16
10"
T/O FLOOR
100' -0"
12 36 61.1612 36 61.16
09 21 16
10
"
2'
-
1
0
"
09 65 13.1
GL-2
101
12 36 61.16
T/O FLOOR
100' -0"
12 36 61.16
BC4
24
18
2'
-
6
"
06 41 1809 65 13.1
3' - 6"
P4
12 36 61.16
12 36 61.16
12 36 61.16
12 24 1312 24 13
3'
-
8
"
2'
-
1
0
"
12 32 16
ADA COUNTER
3' - 2"3' - 6"
09 65 13.1
1'
-
1
"
1'
-
1
"
6"
12 36 61.16
12 36 61.16
12 32 16
base
ar
m
ar
m
Size of Turning Space
ICC/ANSI FIG 304.3
Size of Clear Floor Space
ICC/ANSI FIG 305.3
30
"
48"
ø 5' - 0"
60
"
60"
24
"
3
6
"
12" 36" 12"
A2.3
6
7
8
5
5'
-
1
7
/
8
"
10' - 2 5/8"
4'
-
0
"
2' - 6"
ø 5' - 0 "
5'
-
0
"
4' - 8"
54 ft²
104
TOILET
A9
A1
0
A8 A7
A6
A1
A2
A4
A3
A5
A1
2
A11
STAMP:
THESE DOCUMENTS HAVE BEEN PRODUCED AS AN
INSTRUMENT OF SERVICE AND ARE INTENDED SOLELY
FOR THE PURPOSE OF CONSTRUCTING, USING AND
MAINTAINING THE PROJECT. SPOTLESS WASH
SOLUTIONS USA INC, AS THE ARCHITECT OF RECORD
FOR THE PROJECT RETAINS OWNERSHIP OF THESE
DOCUMENTS.
ANY USE OF THESE DOCUMENTS OR USE OF THIS
DESIGN, IDEAS OR CONCEPTS DESCRIBED HEREIN IN
WHOLE OR PART BY ANY MEANS WHATSOEVER IS
STRICTLY PROHIBITED EXCEPT BY WRITTEN CONSENT
OF SPOTLESS WASH SOLUTIONS USA INC.
REPRODUCTION OF THIS DOCUMENT IS STRICTLY
PROHIBITED EXCEPT BY WRITTEN CONSENT OF
SPOTLESS WASH SOLUTIONS USA INC.
COPYRIGHT 2022
SPOTLESS WASH SOLUTIONS USA INC.
CHECKED:
DATE:
JOB NUMBER:
ISSUED FOR:
SHEET NUMBER:
SP
O
T
L
E
S
S
W
A
S
H
S
O
L
U
T
I
O
N
S
PO
B
O
X
5
4
5
6
TW
I
N
F
A
L
L
S
,
I
D
A
H
O
8
3
3
0
3
PH
.
(
2
0
8
)
8
4
1
-
4
5
2
4
DRAWN:
BI
N
D
I
N
G
02/15/2022
PERMIT REVIEW SET
NOT FOR CONSTRUCTION
21005
BUILDING PERMIT - NFC
A2.3
INTERIOR
ELEVATIONS
AS
NI
T
R
O
C
A
R
W
A
S
H
RE
X
B
U
R
G
,
I
D
13
7
1
N
2
N
D
E
RE
X
B
U
R
G
,
I
D
8
3
4
4
8
5/4/22
GENERAL NOTES
A. ABBREVIATIONS:
F = FILE DRAWER WITH HANGING FILE SYSTEM
B. ALL GYPSUM WALLS / SURFACES TO BE A LEVEL 4 GRADE FINISH.
C. GYPSUM BOARD CONTROL JOINTS, ARE NOT SHOWN FOR CLARITY, ALL CONTROL JOINTS ARE
TO BE EQUALLY SPACED WITHIN A ROOM/WALL/SPACE, CONFIRM ACCEPTABILITY OF LOCATION
WITH ARCHITECT.
D. ALL WALL-MOUNTED ELEMENTS ARE TO RECEIVE WALL BACKING, SEE WALL-BACKING DETAILS
AND REQUIREMENTS.
E. FIRE ALARM HORN-STROBE LOCATIONS ARE TO BE CONFIRMED AND ACCEPTABLE ARCHITECT,
CONTRACTOR TO COORDINATE PLACEMENT WITH ARCHITECT
F. PROVIDE WALL BASE AT ALL GYPSUM BOARD CLAD WALLS AND AT ALL CABINET TOE KICKS.
THIS INCLUDES ALL WALLS EVEN IF NOT INDICATED ON ROOM FINISH SCHEDULE.
G. PROVIDE 3" DEEP TOE KICK AT FRONT AND EXPOSED SIDES OF ALL CABINETS.
H. FOR TYPICAL BARRIER FREE TOILET ROOM CLEARANCES SEE 3/A2.3a.
I. FOR PLUMBING FIXTURE AND ACCESSORY MOUNTING HEIGHTS SEE A2.3a.
J. FIELD VERIFY ALL DIMENSIONS BETWEEN WALLS FOR CABINETS. CABINET DIMENSIONS
INDICATED DO NOT ACCOUNT FOR GYPSUM BOARD AND OTHER FINISHES. WHERE CABINET
DIMENSION INCLUDE " ± " USE THAT CABINET TO ACCOMMODATE NECESSARY ADJUSTMENTS
IN OVERALL WIDTH.
K. ALL VERTICAL DIMENSIONS ARE FROM TOP OF FINISHED FLOORING. ADJUST DIMENSIONS IF
CABINETS ARE INSTALLED PRIOR TO FLOORING UNDERLAYMENT.
L. PROVIDE ADJUSTABLE MELAMINE SHELVES ONLY WHERE SHELVING IS CONCEALED BEHIND
CABINET DOORS, QUANTITY AS SHOWN ON ELEVATIONS.
M. REFER TO EQUIPMENT SCHEDULE FOR WALL-MOUNTED ACCESSORIES AND EQUIPMENT TO BE
ATTACHED TO STUD FRAMING, BACKING AND / OR FRT BLOCKING.
N. OUTLETS WHEN SHOWN ARE FOR COORDINATION ONLY, SEE ELECTRICAL
O. COORDINATE LOCATIONS FOR GROMMETS AT WORK SURFACES WITH OWNER SUPPLIED
COMPUTERS, EQUIPMENT, ETC. FOR BIDDING PURPOSES ASSUME AND PROVIDE 4 GROMMETS
P. SCRIBE ALL CABINETS AND COUNTERTOPS TO WALL. PROVIDE CABINET FILLERS AT ALL
LOCATIONS WHERE GAP EXISTS BETWEEN CABINET AND ADJACENT FINISH. MAXIMUM CABINET
FILLER TO BE NO MORE THAN 2".
Q. PROVIDE SEALANT AT ALL LOCATIONS WHERE CABINETS MEET ADJACENT SURFACES.
R. FOR EQUIPMENT AND ACCESSORY TAG DESIGNATIONS SEE SCHEDULES ON A1.3 SERIES
SHEETS.
S. PROVIDE SOLID SURFACE SILLS AT ALL EXTERIOR WINDOWS EXCEPT AT TUNNEL.
T. PROVIDE WINDOW SHADES AT ALL WINDOWS TO EXTERIOR AT MANAGER #101. DO NOT
PROVIDE WINDOW SHADES AT ENTRANCE DOORS AND TRANSOM WINDOWS.
LEGEND
SYMBOL (2x SCALE)DESCRIPTION
A1
*17
24
MILLWORK DETAIL REFERENCE -SEE A2.5
WIDTH OF CABINET OR DRAWER FACE IF NOT DIMENSIONED
OVERALL DEPTH OF CABINET, COUNTERTOPS EXTEND PAST 25mm (1")
* EQ = EQUALLY SIZED CABINET FACE PANELS WHERE INDICATED
ACCESSORY SCHEDULE
#DESCRIPTION MANUFACTURER / #
A1 PAPER TOWEL DISPENSER BOBRICK B-72974
A2 SOAP DISPENSER BOBRICK B-2013
A3 TOILET TISSUE DISPENSER W/ SHELF BOBRICK B-2840
A4 SANITARY NAPKIN DISPOSAL BOBRICK B-270
A5 SURFACE MOUNTED WASTE RECEPTACLE BOBRICK B-277
A6 TOILET SEAT COVER DISPENSER SHARPS COMPLIANCE #10502
A7 MIRROR BOBRICK B-165
A8 HORIZONTAL GRAB BAR - 36" BOBRICK B-9806 x 36
A9 HORIZONTAL GRAB BAR - 42" BOBRICK B-9806 x 42
A10 VERTICAL GRAB BAR - 18" BOBRICK B-9806 x 18
A11 COAT HOOK BOBRICK B-6827
A12 HAND DRYER; ELECTRIC; HIGH-VELOCITY DYSON; V-POWER; 240VAC
3/8" = 1'-0"
FIXTURE / DEVICE MOUNTING SCHEDULE
SHEET NOTES
#:DESCRIPTION:
1 PROVIDE SOLID FRT WOOD BACKING IN WALL FOR SUPPORT OF GRAB BARS
KEYNOTES
MARK:DESCRIPTION:
06 41 18 METAL KNEE BRACE, PREFINISHED BLACK
09 21 16 GYPSUM BOARD ASSEMBLIES
09 30 13.1 PORCELAIN WALL TILE, AMERICAN OLEAN, HORIZON, GREY JOLLY, HZ04, 6x16, HORIZONTAL
09 65 13.1 RESILIENT BASE AND ACCESSORIES, 4" HEIGHT
12 24 13 ROLLER WINDOW SHADES
12 32 16 MANUFACTURED PLASTIC-LAMINATE-CLAD CASEWORK
12 36 61.16 SOLID SURFACING COUNTERTOPS
22 42 16.16 UNDERCOUNTER MOUNTED SINK
26 51 00 INTERIOR LIGHTING
3/8" = 1'-0"
ACCESSORY MOUNTING SCHEDULE
1/4" = 1'-0"
TOILET NORTH8 1/4" = 1'-0"
TOILET EAST7 1/4" = 1'-0"
TOILET SOUTH6 1/4" = 1'-0"
TOILET WEST5
1/4" = 1'-0"
BREAK4
1/4" = 1'-0"
ENLARGED OFFICE INTERIOR PLAN1
1/4" = 1'-0"
CONTROL SOUTH12 1/4" = 1'-0"
CONTROL EAST11 1/4" = 1'-0"
CONTROL NORTH10
1/4" = 1'-0"
MANAGER WEST3
1/4" = 1'-0"
ACCESSIBLE COUNTER9
1/4" = 1'-0"
TURNING AND CLEAR FLOOR SPACE
1/2" = 1'-0"
TOILET DIMENSION PLAN2
REVISIONS
#DATE
NOT
F
O
R
C
O
N
S
T
R
U
C
T
I
O
N
S.S. PL 1/2"x12"x12" W/ (4) 1/2"Øx4" HCAs
G.S. W12X19
S.S. PL 3/8"x3-1/2"x7-1/2" W/ (2)
3/4"Ø A325 BOLTS
3/16
1
1
/
4
"
3"
1
1
/
4
"
1 1/2"
T/O FLOOR
100' -0"
T/O FOOTING
97' -10"
2 3 4 5
109
WASH
TUNNEL
10' - 2 15/16" CENTERLINE OF PLATES
10
'
-
1
1
7
/
8
"
3' - 1"4' - 0"4' - 0"4' - 0"4' - 0"2' - 7"8"2' - 7"
T/O FLOOR
100' -0"
T/O FOOTING
97' -10"
2345
109
WASH
TUNNEL
10' - 2 15/16" CENTERLINE OF PLATES
11
'
-
0
"
2
2
3
3
4
4
5
5
CC
DD
109
WASH
TUNNEL
2' - 7"4' - 0"4' - 0"4' - 0"4' - 0"3' - 1"2' - 7"
CENTERLINE OF BEAM / TUNNEL
20' - 0"
3' - 9" 4' - 0" 4' - 0" 4' - 0" 4' - 0" 2' - 7" 8" 2' - 7"
3' - 10" 11" 5' - 1"
STAMP:
THESE DOCUMENTS HAVE BEEN PRODUCED AS AN
INSTRUMENT OF SERVICE AND ARE INTENDED SOLELY
FOR THE PURPOSE OF CONSTRUCTING, USING AND
MAINTAINING THE PROJECT. SPOTLESS WASH
SOLUTIONS USA INC, AS THE ARCHITECT OF RECORD
FOR THE PROJECT RETAINS OWNERSHIP OF THESE
DOCUMENTS.
ANY USE OF THESE DOCUMENTS OR USE OF THIS
DESIGN, IDEAS OR CONCEPTS DESCRIBED HEREIN IN
WHOLE OR PART BY ANY MEANS WHATSOEVER IS
STRICTLY PROHIBITED EXCEPT BY WRITTEN CONSENT
OF SPOTLESS WASH SOLUTIONS USA INC.
REPRODUCTION OF THIS DOCUMENT IS STRICTLY
PROHIBITED EXCEPT BY WRITTEN CONSENT OF
SPOTLESS WASH SOLUTIONS USA INC.
COPYRIGHT 2022
SPOTLESS WASH SOLUTIONS USA INC.
CHECKED:
DATE:
JOB NUMBER:
ISSUED FOR:
SHEET NUMBER:
SP
O
T
L
E
S
S
W
A
S
H
S
O
L
U
T
I
O
N
S
PO
B
O
X
5
4
5
6
TW
I
N
F
A
L
L
S
,
I
D
A
H
O
8
3
3
0
3
PH
.
(
2
0
8
)
8
4
1
-
4
5
2
4
DRAWN:
BI
N
D
I
N
G
02/15/2022
PERMIT REVIEW SET
NOT FOR CONSTRUCTION
21005
BUILDING PERMIT - NFC
A2.4
TUNNEL
EQUIPMENT
EMBED PLATE
LOCATIONS
AS
NI
T
R
O
C
A
R
W
A
S
H
RE
X
B
U
R
G
,
I
D
13
7
1
N
2
N
D
E
RE
X
B
U
R
G
,
I
D
8
3
4
4
8
5/4/22
3" = 1'-0"
BEAM TO EMBED PLATE4
GENERAL NOTES
A. ALL EMBED PLATES AND HCA ANCHORS ON THIS SHEET ARE STAINLESS STEEL.
B. ELEVATION TAGS AND DIMENSIONS ARE TO CENTER OF PLATE.
C. ABBREVIATIONS:
G.S. = GALVANIZED STEEL
M.S. = MILD STEEL
S.S. = STAINLESS STEEL
SHEET NOTES
3/16" = 1'-0"
EMBED PLATE LOCATIONS NORTH ELEVATION2
3/16" = 1'-0"
EMBED PLATE LOCATIONS SOUTH ELEVATION1
3/16" = 1'-0"
TUNNEL EQUIPMENT EMBED LOCATIONS3 NORTH
0'4'2'8'
REVISIONS
#DATE
NOT
F
O
R
C
O
N
S
T
R
U
C
T
I
O
N
SPACER BAR OR OTHER
COMPONENT TO KEEP
PERIMETER COMPONENTS
FROM SPREADING OUT.
PERIMETER SUPPORT WIRE PER
ASTM C636
6:1, +/-10 DEGREES
MAXIMUM
PERIMETER
ATTACHMENT
PER ASTM C636
STANDARD DUTY T-BAR
GRID SYSTEM PERIMETER
SUPPORT
PERIMETER
SUPPORTWALL ANGLE, TYP.
SUSPENDED CEILING TO BE INSTALLED TO MANUFACTURER'S SPECIFICATIONS
1
1"
HOLLOW CORE DECK
DEEP LEG DEFLECTION TRACK
METAL TRACK OR WOOD STUD
INSULATION, SEE WALL
ASSEMBLY
09 29 00.D1
05 41 0005 41 00
SEE REFLECTED
CEILING PLAN
09 29 00.D1
2' - 0"
OF
S
E
L
F
-
R
I
M
M
I
N
G
S
I
N
K
86
4
M
A
X
.
A
B
O
V
E
F
I
N
I
S
H
E
D
F
L
O
O
R
ME
A
S
U
R
E
D
T
O
T
O
P
STEEL
BRACKET
SOLID SURFACE
BACKSPLASH
SOLID SURFACFE WITH
SUB-TOP SUPPORT AS
RECOMMENDED BY
MANUFACTURER/
WARRANTY
DOOR PULL
BASE AS
SCHEDULED FOR
ROOM
2' - 0"
SOLID SURFACE
BACKSPLASH
SOLID SURFACFE WITH
SUB-TOP SUPPORT AS
RECOMMENDED BY
MANUFACTURER/
WARRANTY
DOOR PULL
BASE AS
SCHEDULED FOR
ROOM
STEEL BRACKET
DRAWER SLIDES FULL
EXTENTION
DRAWER PULL
SE
E
E
L
E
V
A
T
I
O
N
S
2' - 0"
SOLID SURFACE
BACKSPLASH
SOLID SURFACFE WITH
SUB-TOP SUPPORT AS
RECOMMENDED BY
MANUFACTURER/
WARRANTY
DOOR PULL
BASE AS
SCHEDULED FOR
ROOM
STEEL BRACKET
DRAWER SLIDES FULL
EXTENTION
DRAWER PULL
SE
E
E
L
E
V
A
T
I
O
N
S
2' - 0"
SOLID SURFACE
BACKSPLASH
SOLID SURFACFE WITH SUB-TOP
SUPPORT AS RECOMMENDED BY
MANUFACTURER/WARRANTY
BASE AS SCHEDULED FOR
ROOM
STEEL BRACKET
DRAWER SLIDES FULL
EXTENTION
SE
E
E
L
E
V
A
T
I
O
N
S
SE
E
E
L
E
V
A
T
I
O
N
S
BASE AS
SCHEDULED FOR
ROOM
METAL KNEE BRACE,
PREFINISHED BLACK
STEEL
BACKING
PLATE
SOLID SURFACE WITH
SUB-TOP
SUPPORT AS
RECOMMENDED BY
MANUFACTURER/
WARRANTY
2' - 1"
SOLID SURFACE WITH SUB-TOP
SUPPORT AS RECOMMENDED BY
MANUFACTURER/ WARRANTY
9" 2' - 1"
METAL KNEE BRACE,
PREFINISHED BLACK
REMOVABLE PANEL
BASE AS SCHEDULED FOR
ROOM
STEEL BACKING PLATE
APPLIED PANELS
13mm (1/2") ANODIZED
ALUMINUM REVEAL
BETWEEN PANELS,
CONTINUE AROUND END
PANELS OF MILLWORK
NOTE: USE FRY REGLET DRYWALL
REGLETS OR EQUAL AT REVEALS. USE
REVEAL CHANNEL SCREED BETWEEN
PANELS, F-REVEAL BETWEEN PANELS AND
COUNTERTOPS AND X-MOLDING AT
OUTSIDE CORNERS AND BOTTOM EDGE
2' - 4 1/2"
METAL KNEE BRACE,
PREFINISHED BLACK
REMOVABLE PANEL
BASE AS SCHEDULED FOR ROOM
STEEL BACKING PLATE
APPLIED PANELS
13mm (1/2") ANODIZED ALUMINUM
REVEAL BETWEEN PANELS,
CONTINUE AROUND END PANELS
OF MILLWORK
SOLID SURFACE WITH SUB-TOP
SUPPORT AS RECOMMENDED BY
MANUFACTURER/ WARRANTY
8"
2' - 10"
SE
E
E
L
E
V
A
T
I
O
N
S
SE
E
E
L
E
V
A
T
I
O
N
S
SE
E
E
L
E
V
A
T
I
O
N
S
STEEL BACKING PLATE
NOTCH ADJUSTABLE SHELVES TO
ACCOMMODATE PLUG MOLD
(2) LAYERS OF 19mm (3/4" )
PARTICLE BOARD AT FIXED
SHELF
MELAMINE
ADJUSTABLE
SHELVES
BASE AS SCHEDULED FOR ROOM
WIRE DOOR PULLS
SEE ELEVATIONS
SE
E
E
L
E
V
A
T
I
O
N
S
STEEL BACKING PLATE
CABINET EXHAUST LOUVERS AT
TOP AND BOTTOM OF DOORS BY
MILLWORK CONTRACTOR
WIRE DOOR PULLS
BOTTOM OPEN TO FLOOR
PROVIDE GAP FOR WIRING
CABINET EXHAUST LOUVERS AT
TOP AND BOTTOM OF DOORS BY
MILLWORK CONTRACTOR
2" MIN.
VARIES SEE ELEVATIONS
5/8" PLYWOOD BACK AS
REQUIRED BY UTILITY PROVIDER
SE
E
E
L
E
V
A
T
I
O
N
S
STEEL BACKING PLATE
NOTCH ADJUSTABLE SHELVES TO
ACCOMMODATE PLUG MOLD
(2) LAYERS OF 19mm (3/4" )
PARTICLE BOARD AT FIXED
SHELF
MELAMINE
ADJUSTABLE
SHELVES
WIRE DOOR PULLS
BOTTOM OPEN TO FLOOR
610 MM MIN CLEAR DEPTH
1' - 0"
SE
E
E
L
E
V
A
T
I
O
N
S
MELAMINE
SHELVES,
ADJUSTABLE
DOOR PULL
STEEL
BACKING
PLATE
STAMP:
THESE DOCUMENTS HAVE BEEN PRODUCED AS AN
INSTRUMENT OF SERVICE AND ARE INTENDED SOLELY
FOR THE PURPOSE OF CONSTRUCTING, USING AND
MAINTAINING THE PROJECT. SPOTLESS WASH
SOLUTIONS USA INC, AS THE ARCHITECT OF RECORD
FOR THE PROJECT RETAINS OWNERSHIP OF THESE
DOCUMENTS.
ANY USE OF THESE DOCUMENTS OR USE OF THIS
DESIGN, IDEAS OR CONCEPTS DESCRIBED HEREIN IN
WHOLE OR PART BY ANY MEANS WHATSOEVER IS
STRICTLY PROHIBITED EXCEPT BY WRITTEN CONSENT
OF SPOTLESS WASH SOLUTIONS USA INC.
REPRODUCTION OF THIS DOCUMENT IS STRICTLY
PROHIBITED EXCEPT BY WRITTEN CONSENT OF
SPOTLESS WASH SOLUTIONS USA INC.
COPYRIGHT 2022
SPOTLESS WASH SOLUTIONS USA INC.
CHECKED:
DATE:
JOB NUMBER:
ISSUED FOR:
SHEET NUMBER:
SP
O
T
L
E
S
S
W
A
S
H
S
O
L
U
T
I
O
N
S
PO
B
O
X
5
4
5
6
TW
I
N
F
A
L
L
S
,
I
D
A
H
O
8
3
3
0
3
PH
.
(
2
0
8
)
8
4
1
-
4
5
2
4
DRAWN:
BI
N
D
I
N
G
02/15/2022
PERMIT REVIEW SET
NOT FOR CONSTRUCTION
21005
BUILDING PERMIT - NFC
A2.5
INTERIOR DETAILS
AS
NI
T
R
O
C
A
R
W
A
S
H
RE
X
B
U
R
G
,
I
D
13
7
1
N
2
N
D
E
RE
X
B
U
R
G
,
I
D
8
3
4
4
8
5/4/22
3/4" = 1'-0"
SUSPENDED ACCOUSTICAL PANEL CEILING, TYPICAL
3/4" = 1'-0"
FULL HEIGHT WALL, TYPICAL
3/4" = 1'-0"
GYP BD CEILING, TYPICAL
3/4" = 1'-0"
BC1 - SINK CABINET
3/4" = 1'-0"
BC2 - CABINET WITH TOP DRAWER
3/4" = 1'-0"
BC3 - 2 DEEP DRAWERS AND TOP DRAWER
3/4" = 1'-0"
BC4 - 2 DEEP DRAWERS
3/4" = 1'-0"
CT1 - OPEN COUNTERTOP
3/4" = 1'-0"
CT2 - MILLWORK WALL AND COUNTERTOP
3/4" = 1'-0"
CT3 - MILLWORK WALL AND TWO TIER COUNTERTOP
3/4" = 1'-0"
TC1 - TALL CABINET
3/4" = 1'-0"
TC2 - TALL CABINET
3/4" = 1'-0"
TC3 - TALL CABINET
3/4" = 1'-0"
WC - WALL CABINET
REVISIONS
#DATE
1 5/4/22
NOT
F
O
R
C
O
N
S
T
R
U
C
T
I
O
N
T/O FLOOR
100' -0"
T/O PARAPET 2
119' -0"
T/O FOOTING
97' -10"
2 3 4 53
A3.1
4
A3.1 A3.2
6
A3.2
2
109
WASH
TUNNEL
R1
C8
C6 C6
C8
A2.4
2
3
A7.1
97.18
99.79
95.56
96.18
100.00
22 14 26.19
107.68 R.O.107.38 R.O.107.45 R.O.
3' - 0" R.O.
2' - 11" 7' - 1" 1' - 4" 7' - 5 1/2"
7' - 2 1/4" R.O.
6'
-
1
1
1
/
8
"
6' - 11 1/8"
96.18
UNDERLAY LEVEL
113' -0"
T/O FLOOR
100' -0"
T/O PARAPET 1
117' -0"
T/O FOOTING
97' -10"
1 43
A3.1
4
A3.1
107
ELECTRICAL
106
EQUIPMENT
105
CLEAN
EQUIPMENT
103
HALL
102
CONTROL
A3.2
4
A3.2
5
R1
P7 C8a
C8
C8
10' - 6"
P5 P709 51 13
108' - 0"
3
A7.1
22 14 26.19
A7.1
4
26 51 00 UNDERLAY LEVEL
113' -0"
T/O FLOOR
100' -0"
T/O PARAPET 1
117' -0"
T/O PARAPET 2
119' -0"
1
A3.1
2
A3.1
A C D
A3.2
4
A3.2
1
102
CONTROL
109
WASH
TUNNELC8
F4F409 51 13
22 14 26.13
A1.7
2
R1
A1.2
3
1/4" / 12"
14' - 0"
10' - 6"
100.00
R2
A3.2
3
C8
C8
C8
R2
UNDERLAY LEVEL
113' -0"
T/O FLOOR
100' -0"
T/O PARAPET 1
117' -0"
T/O PARAPET 2
119' -0"
1
A3.1
2
A3.1
B C D
A3.2
5
A3.2
6A3.2
7
C8
C8
C8
C8a
C8
A1.2
3
109
WASH
TUNNEL
107
ELECTRICAL
108
MAT WASH
R1
14' - 0"
F5
1' - 0"
P7
1/4" / 12"
1' - 0"
CP8
UNDERLAY LEVEL
113' -0"
STAMP:
THESE DOCUMENTS HAVE BEEN PRODUCED AS AN
INSTRUMENT OF SERVICE AND ARE INTENDED SOLELY
FOR THE PURPOSE OF CONSTRUCTING, USING AND
MAINTAINING THE PROJECT. SPOTLESS WASH
SOLUTIONS USA INC, AS THE ARCHITECT OF RECORD
FOR THE PROJECT RETAINS OWNERSHIP OF THESE
DOCUMENTS.
ANY USE OF THESE DOCUMENTS OR USE OF THIS
DESIGN, IDEAS OR CONCEPTS DESCRIBED HEREIN IN
WHOLE OR PART BY ANY MEANS WHATSOEVER IS
STRICTLY PROHIBITED EXCEPT BY WRITTEN CONSENT
OF SPOTLESS WASH SOLUTIONS USA INC.
REPRODUCTION OF THIS DOCUMENT IS STRICTLY
PROHIBITED EXCEPT BY WRITTEN CONSENT OF
SPOTLESS WASH SOLUTIONS USA INC.
COPYRIGHT 2022
SPOTLESS WASH SOLUTIONS USA INC.
CHECKED:
DATE:
JOB NUMBER:
ISSUED FOR:
SHEET NUMBER:
SP
O
T
L
E
S
S
W
A
S
H
S
O
L
U
T
I
O
N
S
PO
B
O
X
5
4
5
6
TW
I
N
F
A
L
L
S
,
I
D
A
H
O
8
3
3
0
3
PH
.
(
2
0
8
)
8
4
1
-
4
5
2
4
DRAWN:
BI
N
D
I
N
G
02/15/2022
PERMIT REVIEW SET
NOT FOR CONSTRUCTION
21005
BUILDING PERMIT - NFC
A3.1
BUILDING
SECTIONS
AS
NI
T
R
O
C
A
R
W
A
S
H
RE
X
B
U
R
G
,
I
D
13
7
1
N
2
N
D
E
RE
X
B
U
R
G
,
I
D
8
3
4
4
8
5/4/22
KEYNOTES
MARK:DESCRIPTION:
09 51 13 ACOUSTICAL PANEL CEILINGS
22 14 26.13 ROOF DRAIN
22 14 26.19 PRESLOPED TRENCH DRAIN, ACO S200K WITH SLOTTED IRON 8" LOAD CLASS F
GRATE (OR APPROVED EQUAL)
26 51 00 INTERIOR LIGHTING
3/16" = 1'-0"
WASH TUNNEL SECTION1
3/16" = 1'-0"
EQUIPMENT ROOM SECTION2
3/16" = 1'-0"
CONTROL SECTION3 3/16" = 1'-0"
ELECTRICAL & DRYING SECTION4
0'4'2'8'
REVISIONS
#DATE
NOT
F
O
R
C
O
N
S
T
R
U
C
T
I
O
N
T/O FLOOR
100' -0"
D
R1
07 21 13
03 41 13
A3.3
B3
A5.1
C1
A5.1
C1
A1.7
4
07 54 23
07 62 00
07 42 93
07 61 13
10 14 33
08 12 13 *PF6
*PF9
*PF1
*PF4
19' - 0"
UNDERLAY LEVEL
113' -0"
T/O FLOOR
100' -0"
T/O FOOTING
97' -10"
2
07 21 13
R1
03 41 13
A5.1
C1
A5.1
E4
A3.3
A3
07 54 23
A1.7
5
R22" / 12"
19' - 0"
10 14 33
10 14 33
22 14 26.19
07 62 00
07 61 13
07 42 93
*PF4
*PF9
*PF1
UNDERLAY LEVEL
113' -0"
T/O FLOOR
100' -0"
T/O PARAPET 1
117' -0"
1
03 31 00.2F4
A5.1
D3
A5.1
D1
09 21 16
05 41 00
09 51 13
ACT
R1
07 21 13
03 41 13
A3.3
D3
A3.3
A1
07 54 23
07 42 14
10 71 13.43
C8
08 42 13*PF6
07 62 00*PF1
*PF9
*PF7
UNDERLAY LEVEL
113' -0"
T/O FLOOR
100' -0"
T/O PARAPET 1
117' -0"
B
14' - 0"
C8
*TP2
*TP2
07 42 13.1
03 41 00
03 41 00*TP1
A3.3
A3
A5.1
C1
A5.1
E4
07 54 23
07 21 13
07 54 23
03 31 00.2
C8a
C8
03 41 13
R1
A3.3
A3
A3.3
B2
A3.3
C2
10' - 0"
03 41 00
UNDERLAY LEVEL
113' -0"
T/O FLOOR
100' -0"
T/O PARAPET 2
119' -0"
5
C8
R1
A5.1
C1
A5.1
E4
07 21 13
07 54 23
03 41 13
03 31 00.2
A3.3
B3
A3.3
A3
UNDERLAY LEVEL
113' -0"
T/O FLOOR
100' -0"
C
107
ELECTRICAL
109
WASH
TUNNEL
C8
R1
07 54 23
07 21 13
03 41 13 03 41 13
07 21 13
07 21 13
03 41 00
06 16 33
F5
1/4" / 12"
A3.3
D3
UNDERLAY LEVEL
113' -0"
T/O FLOOR
100' -0"
C
C8
F4
ACT
R1
C8
R2
03 31 00.2
08 11 13
03 41 13
07 62 00
07 61 13
09 51 13
06 41 17
07 54 23
A1.7
4
A3.3
B3
A3.3
D3
A5.1
A3
A5.1
A1
*PF4
*PF9
*PF1 07 42 93
07 54 23
19' - 0"
17' - 0"
UNDERLAY LEVEL
113' -0"
STAMP:
THESE DOCUMENTS HAVE BEEN PRODUCED AS AN
INSTRUMENT OF SERVICE AND ARE INTENDED SOLELY
FOR THE PURPOSE OF CONSTRUCTING, USING AND
MAINTAINING THE PROJECT. SPOTLESS WASH
SOLUTIONS USA INC, AS THE ARCHITECT OF RECORD
FOR THE PROJECT RETAINS OWNERSHIP OF THESE
DOCUMENTS.
ANY USE OF THESE DOCUMENTS OR USE OF THIS
DESIGN, IDEAS OR CONCEPTS DESCRIBED HEREIN IN
WHOLE OR PART BY ANY MEANS WHATSOEVER IS
STRICTLY PROHIBITED EXCEPT BY WRITTEN CONSENT
OF SPOTLESS WASH SOLUTIONS USA INC.
REPRODUCTION OF THIS DOCUMENT IS STRICTLY
PROHIBITED EXCEPT BY WRITTEN CONSENT OF
SPOTLESS WASH SOLUTIONS USA INC.
COPYRIGHT 2022
SPOTLESS WASH SOLUTIONS USA INC.
CHECKED:
DATE:
JOB NUMBER:
ISSUED FOR:
SHEET NUMBER:
SP
O
T
L
E
S
S
W
A
S
H
S
O
L
U
T
I
O
N
S
PO
B
O
X
5
4
5
6
TW
I
N
F
A
L
L
S
,
I
D
A
H
O
8
3
3
0
3
PH
.
(
2
0
8
)
8
4
1
-
4
5
2
4
DRAWN:
BI
N
D
I
N
G
02/15/2022
PERMIT REVIEW SET
NOT FOR CONSTRUCTION
21005
BUILDING PERMIT - NFC
A3.2
WALL SECTIONS
AS
NI
T
R
O
C
A
R
W
A
S
H
RE
X
B
U
R
G
,
I
D
13
7
1
N
2
N
D
E
RE
X
B
U
R
G
,
I
D
8
3
4
4
8
5/4/22
KEYNOTES
MARK:DESCRIPTION:
03 31 00.2 130mm (5") CONCRETE SLAB, TROWEL FINISH
03 41 00 PRECAST CONCRETE WALL PANELS, TYPICAL.
03 41 13 PRECAST CONCRETE HOLLOW CORE PLANKS
05 41 00 STRUCTURAL METAL STUD FRAMING
06 16 33 5/8" EXTERIOR GRADE PLYWOOD SHEATHING
06 41 17 SOLID SURFACE COUNTERTOP, TYPICAL
07 21 13 BOARD INSULATION
07 42 13.1 ACM WALL PANEL, REYNOBOND, COLORWELD 500
07 42 14 METAL SLAT CLADDING SYSTEM
07 42 93 METAL SOFFIT PANEL
07 54 23 THERMOPLASTIC-POLYOLEFIN (TPO) ROOFING, 60 MIL, WHITE
07 61 13 STANDING SEAM METAL ROOF
07 62 00 SHEET METAL FLASHING AND TRIM
08 11 13 HOLLOW METAL DOOR AND FRAME AS SCHEDULED. PAINT.
08 12 13 HOLLOW METAL FRAME AS SCHEDULED. PAINT.
08 42 13 ALUMINUM-FRAMED ENTRANCE
09 21 16 GYPSUM BOARD ASSEMBLIES
09 51 13 ACOUSTICAL PANEL CEILINGS
10 14 33 SIGNAGE BY OTHERS REQUIRES SEPARATE PLAN REVIEW AND PERMIT
10 71 13.43 FIXED SUN SCREENS INTEGRAL WITH ALUMINUM STOREFRONT
22 14 26.19 PRESLOPED TRENCH DRAIN, ACO S200K WITH SLOTTED IRON 8" LOAD CLASS F GRATE
(OR APPROVED EQUAL)
FINISH SCHEDULE
MARK:DESCRIPTION:
*PF1 PREFINISHED METAL, MBCI, SIGNATURE 200, 24GA MIN, CHARCOAL GRAY
*PF4 PRE-FINISHED STANDING SEAM METAL ROOF, 24GA MIN, MATCH MP1, RED
*PF6 PREFINISHED ALUMINUM STOREFRONT SYSTEM; CLEAR, ANNODIZED
*PF7 PREFINISHED ALUMINUM FIXED SUN SCREEN; MATCH MP1, RED
*PF9 PRE-FINISHED METAL, 24GA MIN, MATCH MP1, RED
*TP1 BUILDING DARK GRAY PAINT COLOR: SPRAY APPLIED TEXTURE / PAINT - ACRYLIC
TEXTURE COATING - BM OVERCOAT #CC-544; (2) COATS ACRYLIC TEXTURE COATING; (1)
COAT EXTERIOR LATEX
*TP2 BUILDING MEDIUM GRAY PAINT COLOR: SPRAY APPLIED TEXTURE / PAINT - ACRYLIC
TEXTURE COATING - BM COBBLESTONE PATH #1606; (2) COATS ACRYLIC TEXTURE
COATING; (1) COAT EXTERIOR LATEX
1/2" = 1'-0"
TUNNEL WALL11/2" = 1'-0"
TUNNEL ENTRY21/2" = 1'-0"
OFFICE WALL41/2" = 1'-0"
EQUIP. RM WALL51/2" = 1'-0"
TUNNEL EXIT61/2" = 1'-0"
EQUIP. RM / TUNNEL7 1/2" = 1'-0"
OFFICE / TUNNEL3
REVISIONS
#DATE
NOT
F
O
R
C
O
N
S
T
R
U
C
T
I
O
N
1/2" PREFORMED JOINT FILLER
EXTERIORINTERIOR
CONCRETE SLAB, REF.
STRUCTURAL. SEE A1.2
FOR ELEVATIONS &
SLOPES
CONCRETE APRON OR WALK
PER SITE PLAN
CONCRETE GRADE BEAM,
REF. STRUCTURAL
T.O. GRADE BEAM
REF. STRUCTURAL
PRECAST CONCRETE WALL
SYSTEM, REF. STRUCTURAL
CAP SHEET MEMBRANE
MEMBRANE FLASHING TO
WRAP FROM BASE TO TOP OF
WALL AND DOWN FACE OF
WALL A MINIMUM OF 102mm (4")
METAL COPING CAP
WITH CONTINUOUS
HOLD-DOWN CLEATS
1/2" SHIM
FASTENING CLEAT
4"
4"
ROOF MEMBRANE FLASHING SET IN
BONDING ADHESIVE AT PARAPET
MANUFACTURER'S BATTEN WITH
FASTENERS AT 305mm (12") OC MAXIMUM
SEAM PER MANUFACTURER
MEMBRANE FLASHING TO
WRAP FROM BASE TO TOP OF
WALL AND DOWN FACE OF
WALL A MINIMUM OF 4"
4"
4"
07 62 00.1
07 62 00
05 41 00
REF.
ELEVATION
1/2" SHIM
MEMBRANE FLASHING TO
WRAP FROM BASE TO TOP OF
WALL AND DOWN FACE OF
WALL A MINIMUM OF 4"
4"
4"
07 62 00.1
07 62 00
REF.
ELEVATION
1/2" SHIM
07 42 13.2
03 41 00
1/2" PREFORMED JOINT FILLER
EXTERIORINTERIOR
CONCRETE SLAB, REF.
STRUCTURAL. SEE A1.2
FOR ELEVATIONS &
SLOPES
CONCRETE GRADE BEAM,
REF. STRUCTURAL
PRECAST CONCRETE WALL
SYSTEM, REF. STRUCTURAL
CONCRETE APRON OR WALK PER
SITE PLAN
WEATHER-RESISTIVE BARRIER
5/8" EXTERIOR GRADE PLYWOOD
SHEATHING
RAIN DRIP AT EXTERIOR OR AT WASH
BAY
6" METAL RUNNER CHANNEL
T.O. GRADE BEAM
REF. STRUCTURAL
1/2" PREFORMED JOINT FILLER
EXTERIORINTERIOR
CONCRETE SLAB, REF.
STRUCTURAL. SEE A1.2
FOR ELEVATIONS &
SLOPES
CONCRETE GRADE BEAM,
REF. STRUCTURAL
PRECAST CONCRETE WALL
SYSTEM, REF. STRUCTURAL
CONCRETE APRON OR WALK PER
SITE PLAN
RAIN DRIP AT EXTERIOR OR AT WASH
BAY
T.O. GRADE BEAM
REF. STRUCTURAL
05 41 00
07 62 00
REF.
ELEVATION
03 41 00
07 42 13.2
07 62 00
3"
07 62 00
3"
07 62 00
07 42 13.2
06 16 00.2
07 11 00
1"
SEALANT W/ BACKER
03 41 00
REF.
ELEVATION
STAMP:
THESE DOCUMENTS HAVE BEEN PRODUCED AS AN
INSTRUMENT OF SERVICE AND ARE INTENDED SOLELY
FOR THE PURPOSE OF CONSTRUCTING, USING AND
MAINTAINING THE PROJECT. SPOTLESS WASH
SOLUTIONS USA INC, AS THE ARCHITECT OF RECORD
FOR THE PROJECT RETAINS OWNERSHIP OF THESE
DOCUMENTS.
ANY USE OF THESE DOCUMENTS OR USE OF THIS
DESIGN, IDEAS OR CONCEPTS DESCRIBED HEREIN IN
WHOLE OR PART BY ANY MEANS WHATSOEVER IS
STRICTLY PROHIBITED EXCEPT BY WRITTEN CONSENT
OF SPOTLESS WASH SOLUTIONS USA INC.
REPRODUCTION OF THIS DOCUMENT IS STRICTLY
PROHIBITED EXCEPT BY WRITTEN CONSENT OF
SPOTLESS WASH SOLUTIONS USA INC.
COPYRIGHT 2022
SPOTLESS WASH SOLUTIONS USA INC.
CHECKED:
DATE:
JOB NUMBER:
ISSUED FOR:
SHEET NUMBER:
SP
O
T
L
E
S
S
W
A
S
H
S
O
L
U
T
I
O
N
S
PO
B
O
X
5
4
5
6
TW
I
N
F
A
L
L
S
,
I
D
A
H
O
8
3
3
0
3
PH
.
(
2
0
8
)
8
4
1
-
4
5
2
4
DRAWN:
BI
N
D
I
N
G
02/15/2022
PERMIT REVIEW SET
NOT FOR CONSTRUCTION
21005
BUILDING PERMIT - NFC
A3.3
EXTERIOR DETAILS
AS
NI
T
R
O
C
A
R
W
A
S
H
RE
X
B
U
R
G
,
I
D
13
7
1
N
2
N
D
E
RE
X
B
U
R
G
,
I
D
8
3
4
4
8
5/4/22
3" = 1'-0"
WALL BASE - EXTERIOR CONC C8D3
3" = 1'-0"
PARAPET COPING - EXTERIOR CONC C8A3
3" = 1'-0"
MEMBRANE BASE TIE-INB3
3" = 1'-0"
PARAPET COPING - EXTERIOR CONC C8aA2 3" = 1'-0"
PARAPET COPING - EXTERIOR CONC C8bA1
3" = 1'-0"
WALL BASE - EXTERIOR CONC C8aD2 3" = 1'-0"
WALL BASE - EXTERIOR CONC C8bD1
3" = 1'-0"
PANEL FURRING - BOTTOM - EXTERIOR CONC C8aC2
3" = 1'-0"
PANEL FURRING - TOP - BELOW PARAPET C8aB2
REVISIONS
#DATE
NOT
F
O
R
C
O
N
S
T
R
U
C
T
I
O
N
5
34 2
DIMENSIONS AND NOTES ARE
TYPICAL AT EACH OF (2) LANES
1
LANE 2
LANE 1
20' - 0"
CENTERLINE OF
POS SYSTEM
9'
-
0
"
4'
-
0
"
9'
-
0
"
3'
-
6
"
CENTERLINE OF
POS ISLAND
6'
-
0
"
1
'
-
6
"
2
'
-
0
"
2
'
-
0
"
1
'
-
6
"
6
'
-
0
"
1
'
-
6
"
1' - 6" 2' - 6" 5' - 0" 10' - 0" 2' - 6" 4' - 0"20' - 0"
3
A4.1
3
A4.1
5 8769
10
11
12
10
CENTERLINE OF
POS SYSTEM
6"
1'
-
6
"
9"
1
'
-
3
"
1'
-
6
"
6
"
6"
1
'
-
6
"
1
'
-
6
"
6
"
6"1'
-
6
"
2'
-
0
"
9"2'
-
0
"
1'
-
6
"
3' - 3" 3' - 0" 3' - 0" 3' - 2" 2' - 10"
3' - 3" 3' - 0" 3' - 0" 3' - 2" 2' - 10"
32 39 13
DIMENSIONS AND NOTES ARE
TYPICAL AT EACH OF (2) LANES
32 39 13
5 876912
T.O. POS ISLAND
100' -0"
UNDERLAY LEVEL
113' -0"
STAMP:
THESE DOCUMENTS HAVE BEEN PRODUCED AS AN
INSTRUMENT OF SERVICE AND ARE INTENDED SOLELY
FOR THE PURPOSE OF CONSTRUCTING, USING AND
MAINTAINING THE PROJECT. SPOTLESS WASH
SOLUTIONS USA INC, AS THE ARCHITECT OF RECORD
FOR THE PROJECT RETAINS OWNERSHIP OF THESE
DOCUMENTS.
ANY USE OF THESE DOCUMENTS OR USE OF THIS
DESIGN, IDEAS OR CONCEPTS DESCRIBED HEREIN IN
WHOLE OR PART BY ANY MEANS WHATSOEVER IS
STRICTLY PROHIBITED EXCEPT BY WRITTEN CONSENT
OF SPOTLESS WASH SOLUTIONS USA INC.
REPRODUCTION OF THIS DOCUMENT IS STRICTLY
PROHIBITED EXCEPT BY WRITTEN CONSENT OF
SPOTLESS WASH SOLUTIONS USA INC.
COPYRIGHT 2022
SPOTLESS WASH SOLUTIONS USA INC.
CHECKED:
DATE:
JOB NUMBER:
ISSUED FOR:
SHEET NUMBER:
SP
O
T
L
E
S
S
W
A
S
H
S
O
L
U
T
I
O
N
S
PO
B
O
X
5
4
5
6
TW
I
N
F
A
L
L
S
,
I
D
A
H
O
8
3
3
0
3
PH
.
(
2
0
8
)
8
4
1
-
4
5
2
4
DRAWN:
BI
N
D
I
N
G
02/15/2022
PERMIT REVIEW SET
NOT FOR CONSTRUCTION
21005
BUILDING PERMIT - NFC
A4.1
POS ISLAND
DETAILS
AS
NI
T
R
O
C
A
R
W
A
S
H
RE
X
B
U
R
G
,
I
D
13
7
1
N
2
N
D
E
RE
X
B
U
R
G
,
I
D
8
3
4
4
8
5/4/22
1/4" = 1'-0"
POS HORIZONTAL CONTROL11/4" = 1'-0"
POS EQUIPMENT LOCATION PLAN2
SHEET NOTES
1 6" Ø CONCRETE FILLED PIPE BOLLARD, PAINT WITH RUST INHIBITOR AND PROVIDE BOLLARD COVER.
2 CONCRETE ISLAND, TYPICAL. FORM AND FILL ISLAND WITH CONCRETE TO AN OVERALL DEPTH OF 12"
MINIMUM. PROVIDE #3 BARS @ 12" O.C. EACH WAY AT TOP AND PROVIDE #3 CONTINUOUS AROUND
THE BOTTOM PERIMETER. PROVIDE 3" MINIMUM COVERAGE. PROVIDE BROOM FINISH.
3 6" HIGH x 1" CHAMFER EDGE AT PERIMETER OF PAY ISLAND.
4 PREFORMED JOINT MATERIAL AND POLYEURETHANE SEALANT FS-TT-S-00227, TYPE II, NON SAG AND
I-SELF LEVELING, CLASS A, ALL AROUND, TYPICAL.
5 PROVIDE DIVIDED PULL-BOX FOR ISLAND POWER AND CONTROLS CONDUCTORS.
6 DRB XPT - EXPRESS PAY TERMINAL.
7 DRB FASTPASS READER PEDESTAL.
8 DRB MAGNETIC GATE.
9 MENU SIGN LOCATION.
10 IN PAVEMENT SENSOR LOOP. DIVISION 16 TO SET LOOP IN LOCATION ILLUSTRATED AND SET ON
CHAIRS SO THAT THE LOOP CONDUCTORS ARE 2" BELOW TOP OF PAVEMENT, TYPICAL.
11 IN PAVEMENT MERGE LOOP LEAD-IN WIRES, CONDUITS AND SENSING CONDUCTORS PROVIDED BY
DIVISION 16 CONTRACTOR. REFER TO DRB LITERATURE FOR ADDITIONAL REQUIREMENTS AND LOOP
SOURCING. ROUTE CONDUCTORS TO MAGNETIC GATE BASES AS ILLUSTRATED.
12 3" SLEEVE FOR BUG JUICE LINE. STUB UP AT TWO LOCATIONS AT ISLANDS. EXTEND LINE TO BUG
JUICE PUMP E404 IN EQUIPMENT ROOM.
GENERAL NOTES
A. IN ADDITION TO THE ARCHITECTURAL AND ELECTRICAL DRAWINGS, INSTALL POS
SYSTEM INFRASTRUCTURE IN ACCORDANCE WITH POINT-OF-SALE MANUFACTURER'S
INSTALLATION LITERATURE (DRB TUNNEL SOLUTIONS).
B. IT IS CONTRACTORS RESPONSIBILITY TO AQUIRE POINT-OF-SALE MANUFACTURER'S
INSTALLATION LITERATURE AVAILABLE THROUGH OWNER.
C. ALL ELECTRICAL WORK SHALL BE PERFORMED BY LICENSED ELECTRICIAN AND
INSTALLED IN ACCORDANCE WITH LOCALLY ADOPTED CODES.
D. IN ADDITION TO ROUTING OF ALL POWER AND CONTROLS CONDUCTORS THROUGH
THE PULL BOX, ALSO ROUTE CONDUCTORS BETWEEN EQUIPMENT THROUGH PULL-
BOX.
3/16" = 1'-0"
POS ELEVATION3
NORTH
0'4'2'8'
NORTH
0'4'2'8'
KEYNOTES
MARK:DESCRIPTION:
32 39 13 METAL BOLLARDS
REVISIONS
#DATE
NOT
F
O
R
C
O
N
S
T
R
U
C
T
I
O
N
3
A4.1
5 1
3
4
2
J
J
J
CE
N
T
E
R
L
I
N
E
O
F
PO
S
S
Y
S
T
E
M
J
2 3
J4J
5 1
3
A4.1
6
7
9
10
11
12
5 1
8
J
J
J
J
7
10
6
9
5 1
8
J
J
J
12 J
11
CENTERLINE OF
POS SYSTEM
NOTE: PULL BOX IS ALSO USED TO
CONNECT POWER AND CONTROLS
CONDUITS AND CONDUCTORS
BETWEEN POS ISLAND EQUIPMENT (NOT
SHOWN)
POWER
CONTROLS
CONDUIT FOR MAGNETIC GATE, XPT,
AND MENU SIGN
CONDUIT FOR MECHANICAL CIRCUITS
CONDUIT FOR RECEPTICAL
POWER AND LIGHTING
1" C FOR XPT CONTROL
1" C FOR BACKUP
DIVIDER 13
14
STAMP:
THESE DOCUMENTS HAVE BEEN PRODUCED AS AN
INSTRUMENT OF SERVICE AND ARE INTENDED SOLELY
FOR THE PURPOSE OF CONSTRUCTING, USING AND
MAINTAINING THE PROJECT. SPOTLESS WASH
SOLUTIONS USA INC, AS THE ARCHITECT OF RECORD
FOR THE PROJECT RETAINS OWNERSHIP OF THESE
DOCUMENTS.
ANY USE OF THESE DOCUMENTS OR USE OF THIS
DESIGN, IDEAS OR CONCEPTS DESCRIBED HEREIN IN
WHOLE OR PART BY ANY MEANS WHATSOEVER IS
STRICTLY PROHIBITED EXCEPT BY WRITTEN CONSENT
OF SPOTLESS WASH SOLUTIONS USA INC.
REPRODUCTION OF THIS DOCUMENT IS STRICTLY
PROHIBITED EXCEPT BY WRITTEN CONSENT OF
SPOTLESS WASH SOLUTIONS USA INC.
COPYRIGHT 2022
SPOTLESS WASH SOLUTIONS USA INC.
CHECKED:
DATE:
JOB NUMBER:
ISSUED FOR:
SHEET NUMBER:
SP
O
T
L
E
S
S
W
A
S
H
S
O
L
U
T
I
O
N
S
PO
B
O
X
5
4
5
6
TW
I
N
F
A
L
L
S
,
I
D
A
H
O
8
3
3
0
3
PH
.
(
2
0
8
)
8
4
1
-
4
5
2
4
DRAWN:
BI
N
D
I
N
G
02/15/2022
PERMIT REVIEW SET
NOT FOR CONSTRUCTION
21005
BUILDING PERMIT - NFC
A4.2
POS ISLAND
POWER & SPECIAL
SYSTEMS PLANS
AS
NI
T
R
O
C
A
R
W
A
S
H
RE
X
B
U
R
G
,
I
D
13
7
1
N
2
N
D
E
RE
X
B
U
R
G
,
I
D
8
3
4
4
8
5/4/22
1/4" = 1'-0"
POS POWER PLAN11/4" = 1'-0"
POS SPECIAL SYSTEMS PLAN2
GENERAL NOTES
A. IN ADDITION TO THE ARCHITECTURAL AND ELECTRICAL DRAWINGS, INSTALL POS
SYSTEM INFRASTRUCTURE IN ACCORDANCE WITH POINT-OF-SALE MANUFACTURER'S
INSTALLATION LITERATURE (DRB TUNNEL SOLUTIONS).
B. IT IS CONTRACTORS RESPONSIBILITY TO AQUIRE POINT-OF-SALE MANUFACTURER'S
INSTALLATION LITERATURE AVAILABLE THROUGH OWNER.
C. ALL ELECTRICAL WORK SHALL BE PERFORMED BY LICENSED ELECTRICIAN AND
INSTALLED IN ACCORDANCE WITH LOCALLY ADOPTED CODES.
D. IN ADDITION TO ROUTING OF ALL POWER AND CONTROLS CONDUCTORS THROUGH
THE PULL BOX, ALSO ROUTE CONDUCTORS BETWEEN EQUIPMENT THROUGH PULL-
BOX.
1 : 25
PULL BOX CONDUIT3
SHEET NOTES
8 CONDUIT AND CONNECTION FROM XPT TO FASTPASS RFID BY DIVISION 16 CONTRACTOR. CONNECT
OWNER FURNISHED CA06050 PRE-TERMINATED CABLE TO 48V POWER SUPPLY AND CONTROL
TERMINAL STRIP AT XPT.
9 CONTROL CONDUIT, CONDUCTORS AND CONNECTION FROM XPT TO MAGNETIC GATE BY DIVISION 16
CONTRACTOR. CONNECT CAT 6 CABLE.
10 CONDUIT AND CONTROL CONNECTION FROM MAGNETIC GATE TO GATE LOOP BY DIVISION 16
CONTRACTOR. CONDUCTORS ARE FURNISHED BY OWNER AND INSTALLED BY DIVISION 16
CONTRACTOR. OWNER FURNISHED ASSEMBLY TO BE LEAD-IN-SYSTEMS OR EQUAL PART IMSA
51-3/18 MANUFACTURED LOOP FOR DIRECT BURY INSTALL. LOOP LEAD IN WIRES ARE 16AWG
TWISTED 6 TURNS PER FOOT FROM EDGE OF LOOP TO THE CONNECTIONS ON THE LOOP DETECTOR
SOCKET INSIDE OF THE GATE. THE FURNISHED LOOP SENSING CONDUCTORS ARE TO BE STRANDED,
TINNED COPPER WITH XLPE INSULATION RATED FOR 600V.
11 CONTROL CONNECTION FROM MAGNETIC GATE TO MERGE LOOP BY DIVISION 16 CONTRACTOR.
CONDUIT AND CONDUCTORS ARE NOT PROVIDED BY OWNER. DIVISION 16 CONTRACTOR SHALL
PROVIDE PVC CONDUIT AND LEAD-IN-SYSTEMS OR EQUAL PART IMSA 51-3/18 MANUFACTURED LOOP
FOR DIRECT BURY INSTALL. LOOP LEAD IN WIRES ARE 16AWG TWISTED 6 TURNS PER FOOT FROM
EDGE OF LOOP TO THE CONNECTIONS ON THE LOOP DETECTOR SOCKET INSIDE OF THE GATE. THE
FURNISHED LOOP SENSING CONDUCTORS ARE TO BE STRANDED, TINNED COPPER WITH XLPE
INSULATION RATED FOR 600V.
12 CONTROL CONNECTION FROM SIGN CONTROL STATION AT MANAGERS OFFICE TO FUTURE DIGITAL
SIGN BY DIVISION 16 CONTRACTOR. PROVIDE CAT-6 CABLE ROUTED THROUGH ISLAND PULL-BOX.
13 (3) 1" POWER CONDUITS TO 120VAC PANEL. PROVIDE DEDICATED 20AMP BREAKER FOR EACH.
14 (2) 1" CONTROL CONDUITS TO DRB SERVER RACK HEAD END EQUIPMENT LOCATED IN MANAGER'S
OFFICE. (1) IS SPARE.
SHEET NOTES
1 PROVIDE CONDUIT AND CONDUCTORS BETWEEN ISLAND EQUIPMENT AND PULL-BOX. DIVISION 16 TO
TERMINATE POWER AND CONTROLS CONDUCTORS TO THE EQUIPMENT.
2 POWER CONNECTION FROM PANEL TO DRB XPT (POS UNIT) BY DIVISION 16 CONTRACTOR. 120VAC, 8
AMP "COMPUTER GRADE POWER" WITH DEDICATED EARTH GROUND AND 20AMP DEDICATED
CIRCUIT. USE 1" METAL CONDUIT FROM PANEL TO PULL-BOX.
3 POWER CONNECTION FROM PANEL TO DRB MAGNETIC GATE BY DIVISION 16 CONTRACTOR. 115VAC,
5AMP, PROVIDE 20 AMP DEDICATED CIRCUIT. USE 1" METAL CONDUIT FROM PANEL TO PULL-BOX.
4 POWER CONNECTION FROM PANEL TO DIGITAL SCREEN MENU BY DIVISION 16 CONTRACTOR.
100-240VAC, 6 AMP, PROVIDE 20AMP DEDICATED CIRCUIT. ROUTE CIRCUIT THROUGH LIGHTING
CONTROL PANEL. USE 1" METAL CONDUIT FROM PANEL TO PULL-BOX.
5 PULL-BOX, SEE DETAIL C5/A4.2. ROUTE ALL ISLAND POWER AND CONTROLS CONDUCTORS FROM
BUILDING AND BETWEEN DRB AND OTHER POS ISLAND EQUIPMENT THROUGH BOX. DO NOT
TERMINATE OR SPLICE AT BOX. DIVISION 16 CONTRACTOR TO EXTEND (3) 1" METAL POWER CONDUIT
WITH DEDICATED 20AMP CIRCUITS TO NORTH DIVIDED HALF OF PULL BOX AND (2) 1" METAL
CONTROLS CONDUITS AT SOUTH SIDE OF PULL BOX.
6 DIVISION 16 CONTRACTOR TO PROVIDE (3) 1" CONDUITS WITH (4) CAT6 CONDUCTORS EACH FOR
CONNECTION TO ALARM SYSTEM, SITE WATCH SERVER, INTERCOM SYSTEM AND SECURITY CAMERA
SYSTEM. EXTEND TO DRB HEAD END EQUIPMENT LOCATED IN MANAGER'S OFFICE. ROUTE CONDUIT
AND CONDUCTORS THROUGH PULL-BOX. CONDUITS FROM PULL-BOX TO EQUIPMENT TO BE
PROVIDED BY DIVISION 16 CONTRACTOR.
7 CONTROL CONNECTION TO EXTERNAL PROXIMITY LOOP BY DIVISION 16 CONTRACTOR. OWNER
FURNISHED ASSEMBLY TO BE LEAD-IN-SYSTEMS OR EQUAL PART IMSA 51-3/18 MANUFACTURED LOOP
FOR DIRECT BURY INSTALL. LOOP LEAD IN WIRES ARE 16AWG TWISTED 6 TURNS PER FOOT FROM
EDGE OF LOOP TO THE CONNECTIONS ON THE LOOP DETECTOR SOCKET INSIDE OF THE XPT. THE
FURNISHED LOOP SENSING CONDUCTORS ARE TO BE STRANDED, TINNED COPPER WITH XLPE
INSULATION RATED FOR 600V.
NORTH
0'4'2'8'
NORTH
0'4'2'8'
REVISIONS
#DATE
NOT
F
O
R
C
O
N
S
T
R
U
C
T
I
O
N
SEALANT AND BACKER ROD
ALUMINUM STOREFRONT SYSTEM
NOTE: SET FRAME WEEP IN THE OPPOSITE
POSITION (INTERIOR) SO THAT WATER DOES
NOT MIGRATE FROM TUNNEL TO EXTERIOR
OF CAR WASH. GLAZING TO BE SET SO THAT
1ST SURFACE IS AT EXTERIOR. DO NOT
BLOCK WEEP WITH SEALANT.
TUNNEL EXTERIOR
SEALANT AND BACKER ROD
ALUMINUM STOREFRONT SYSTEM
NOTE: SET FRAME WEEP IN THE OPPOSITE POSITION (INTERIOR) SO THAT WATER DOES
NOT MIGRATE FROM TUNNEL TO EXTERIOR OF CAR WASH. GLAZING TO BE SET SO THAT
1ST SURFACE IS AT EXTERIOR. DO NOT BLOCK WEEP WITH SEALANT.
TUNNEL
EXTERIOR
SEALANT AND BACKER ROD
ALUMINUM STOREFRONT SYSTEM
NOTE: SET FRAME WEEP IN THE OPPOSITE POSITION (INTERIOR) SO THAT WATER DOES NOT
MIGRATE FROM TUNNEL TO EXTERIOR OF CAR WASH. GLAZING TO BE SET SO THAT 1ST SURFACE
IS AT EXTERIOR. DO NOT BLOCK WEEP WITH SEALANT.
TUNNEL EXTERIOR
3"
20 GA STAINLESS STEEL FLASHING
WITH WITH HEMMED DRIP EDGE AT
BOTH SIDES OF WALL
NOTE: SEE SCHEDULE FOR
GALVANNEALED DOOR &
FRAME LOCATIONS
SEALANT AND BACKER ROD
RAIN DRIP AT EXTERIOR OR AT WASH
BAY
HOLLOW METAL FRAME
NOTE: SEE SCHEDULE FOR
GALVANNEALED DOOR & FRAME
LOCATIONS
SEALANT AND BACKER ROD
HOLLOW METAL FRAME
CONCRETE ANCHOR SIZE AND
QUANTITY AS RECOMMENDED BY
STEEL DOOR INSTITUTE
SEALANT AND BACKER ROD
RAIN DRIP AT EXTERIOR OR AT WASH
BAY
HOLLOW METAL FRAME
CORNER METAL
SEALANT
NOTE: SEE SCHEDULE FOR
GALVANNEALED DOOR & FRAME
LOCATIONS
NOTE: SEE SCHEDULE FOR GALVANNEALED
DOOR & FRAME LOCATIONS
SEALANT AND BACKER ROD
HOLLOW METAL FRAME
CONCRETE ANCHOR SIZE AND
QUANTITY AS RECOMMENDED BY
STEEL DOOR INSTITUTE
CORNER METAL
SEALANT
BREAK METAL FACIA, SEE
ELEVATIONS FOR COLOR
FASTENING CLEAT
METAL SIDING
SEE A3.1b BUILDING SECTION FOR OH DOOR CONTINUATION
OH DOOR CURTAIN & GUIDE ANGLES
INTERIOR EXTERIOR
BREAK METAL FACIA, SEE
ELEVATIONS FOR COLOR
BREAK METAL TRIM, SEE ELEVATIONS
FOR COLOR
FASTENING CLEAT
WEATHER-RESISTIVE BARRIER
5/8" EXTERIOR GRADE PLYWOOD
SHEATHING
6" METAL RUNNER CHANNEL
NOTE: DOOR ASSEMBLY GUIDE ANGLES
TO EXTEND PAST OPENING THE SAME
AMOUNT AT EACH SIDE OF OPENING.
INSTALL PER MANUFACTURER'S WRITTEN
INSTRUCTIONS.
OH DOOR CURTAIN ANGLES
INTERIOR
EXTERIOR
BREAK METAL FACIA, SEE
ELEVATIONS FOR COLOR
BREAK METAL TRIM, SEE ELEVATIONS
FOR COLOR
FASTENING CLEAT
METAL SIDING
WEATHER-RESISTIVE BARRIER
R-15 BLANKET
HEADER PER STRUCTURAL W/
INSULATION
SEALANTSEALANT
1/2"
HOLLOW METAL FRAME
SEALANT AND BACKER ROD
ALUMINUM STOREFRONT SYSTEM
CORNER METAL
SEALANT
INTERIOR
EXTERIOR
BREAK METAL FACIA, SEE
ELEVATIONS FOR COLOR
FASTENING CLEAT
METAL SIDING
SEALANT AND BACKER ROD
ALUMINUM STOREFRONT SYSTEM
INTERIOR EXTERIOR
1"SOLID SURFACE
19mm (3/4") THICK
WITH 25mm (1")
THICK SQUARE
EDGE
SEALANT
WALL, SEE PLAN
BREAK METAL FLASHING WITH WITH
HEMMED DRIP EDGE
3/
4
"
BREAK METAL FACIA, SEE
ELEVATIONS FOR COLOR
METAL SIDING
1/2" PREFORMED JOINT FILLER
DOOR PANEL AS SCHEDULED
GROUT SOLID THRESHOLD
CAVITY
DOOR HARDWARE AS
SCHEDULED
EXTERIORINTERIOR
EDGE OF GRADE BEAM BLOCK-
OUT BEYOND
CONCRETE SLAB, REF.
STRUCTURAL. SEE
A1.2 FOR ELEVATIONS
& SLOPES
CONCRETE GRADE
BEAM, REF.
STRUCTURAL
1/2" PREFORMED JOINT FILLER
OVERHEAD DOOR PANEL
AS SCHEDULED
CONCRETE WALL
PANEL BEYOND
EXTERIOR
INTERIOR
CONCRETE SLAB, REF.
STRUCTURAL. SEE A1.2 FOR
ELEVATIONS & SLOPES
CONCRETE APRON
PER SITE PLAN
CONCRETE GRADE BEAM,
REF. STRUCTURAL
SEALANT AND BACKER ROD
ALUMINUM STOREFRONT SYSTEMCORNER METAL SEALANT
INTERIOR EXTERIOR
BREAK METAL FACIA, SEE
ELEVATIONS FOR COLOR
FASTENING CLEAT
METAL SIDING
SEE A3.1b BUILDING SECTION FOR OH DOOR CONTINUATION
OH DOOR CURTAIN & GUIDE ANGLES
IN
T
E
R
I
O
R
EX
T
E
R
I
O
R
NOTE: DOOR ASSEMBLY GUIDE
ANGLES TO EXTEND PAST
OPENING THE SAME AMOUNT AT
EACH SIDE OF OPENING.
INSTALL PER MANUFACTURER'S
WRITTEN INSTRUCTIONS.
OH DOOR CURTAIN ANGLES
INTERIOR
EXTERIOR
STAMP:
THESE DOCUMENTS HAVE BEEN PRODUCED AS AN
INSTRUMENT OF SERVICE AND ARE INTENDED SOLELY
FOR THE PURPOSE OF CONSTRUCTING, USING AND
MAINTAINING THE PROJECT. SPOTLESS WASH
SOLUTIONS USA INC, AS THE ARCHITECT OF RECORD
FOR THE PROJECT RETAINS OWNERSHIP OF THESE
DOCUMENTS.
ANY USE OF THESE DOCUMENTS OR USE OF THIS
DESIGN, IDEAS OR CONCEPTS DESCRIBED HEREIN IN
WHOLE OR PART BY ANY MEANS WHATSOEVER IS
STRICTLY PROHIBITED EXCEPT BY WRITTEN CONSENT
OF SPOTLESS WASH SOLUTIONS USA INC.
REPRODUCTION OF THIS DOCUMENT IS STRICTLY
PROHIBITED EXCEPT BY WRITTEN CONSENT OF
SPOTLESS WASH SOLUTIONS USA INC.
COPYRIGHT 2022
SPOTLESS WASH SOLUTIONS USA INC.
CHECKED:
DATE:
JOB NUMBER:
ISSUED FOR:
SHEET NUMBER:
SP
O
T
L
E
S
S
W
A
S
H
S
O
L
U
T
I
O
N
S
PO
B
O
X
5
4
5
6
TW
I
N
F
A
L
L
S
,
I
D
A
H
O
8
3
3
0
3
PH
.
(
2
0
8
)
8
4
1
-
4
5
2
4
DRAWN:
BI
N
D
I
N
G
02/15/2022
PERMIT REVIEW SET
NOT FOR CONSTRUCTION
21005
BUILDING PERMIT - NFC
A5.1
DOOR AND
WINDOW DETAILS
AS
NI
T
R
O
C
A
R
W
A
S
H
RE
X
B
U
R
G
,
I
D
13
7
1
N
2
N
D
E
RE
X
B
U
R
G
,
I
D
8
3
4
4
8
5/4/22
1 1/2" = 1'-0"
AL CONC. HEAD TUNNELA11 1/2" = 1'-0"
AL CONC. JAMB TUNNELA21 1/2" = 1'-0"
AL CONC. SILL TUNNELA3
1 1/2" = 1'-0"
HM CONC. HEADB11 1/2" = 1'-0"
HM CONC. JAMBB21 1/2" = 1'-0"
HM CONC. HEAD OFFICEB31 1/2" = 1'-0"
HM CONC. JAMB OFFICEB4
1 1/2" = 1'-0"
OH CONC. HEAD EXITC11 1/2" = 1'-0"
OH CONC. JAMB EXITC2
1 1/2" = 1'-0"
HM STUD INTERIOR HEAD/JAMBA4
1 1/2" = 1'-0"
AL CONC. JAMB OFFICED21 1/2" = 1'-0"
AL CONC. SILL OFFICED31 1/2" = 1'-0"
TYPICAL HM/AL THRESHOLDD4
1 1/2" = 1'-0"
TYPICAL OH THRESHOLDE4
1 1/2" = 1'-0"
AL CONC. HEAD OFFICED1
1 1/2" = 1'-0"
OH CONC. HEAD ENTRYC31 1/2" = 1'-0"
OH CONC. JAMB ENTRYC4
REVISIONS
#DATE
NOT
F
O
R
C
O
N
S
T
R
U
C
T
I
O
N
GL-2
GL-2
F G FG
SC
H
E
D
U
L
E
SE
E
D
O
O
R
1
3
4
2
OR
3
SCHEDULE
SEE DOOR
SCHEDULE
SEE DOOR
SCHEDULE
SEE DOOR
36
"
-
4
8
"
TY
P
I
C
A
L
6"
6"
AREA OF
REFUGE
4'
-
0
"
M
I
N
5'
-
0
"
M
A
X
STAMP:
THESE DOCUMENTS HAVE BEEN PRODUCED AS AN
INSTRUMENT OF SERVICE AND ARE INTENDED SOLELY
FOR THE PURPOSE OF CONSTRUCTING, USING AND
MAINTAINING THE PROJECT. SPOTLESS WASH
SOLUTIONS USA INC, AS THE ARCHITECT OF RECORD
FOR THE PROJECT RETAINS OWNERSHIP OF THESE
DOCUMENTS.
ANY USE OF THESE DOCUMENTS OR USE OF THIS
DESIGN, IDEAS OR CONCEPTS DESCRIBED HEREIN IN
WHOLE OR PART BY ANY MEANS WHATSOEVER IS
STRICTLY PROHIBITED EXCEPT BY WRITTEN CONSENT
OF SPOTLESS WASH SOLUTIONS USA INC.
REPRODUCTION OF THIS DOCUMENT IS STRICTLY
PROHIBITED EXCEPT BY WRITTEN CONSENT OF
SPOTLESS WASH SOLUTIONS USA INC.
COPYRIGHT 2022
SPOTLESS WASH SOLUTIONS USA INC.
CHECKED:
DATE:
JOB NUMBER:
ISSUED FOR:
SHEET NUMBER:
SP
O
T
L
E
S
S
W
A
S
H
S
O
L
U
T
I
O
N
S
PO
B
O
X
5
4
5
6
TW
I
N
F
A
L
L
S
,
I
D
A
H
O
8
3
3
0
3
PH
.
(
2
0
8
)
8
4
1
-
4
5
2
4
DRAWN:
BI
N
D
I
N
G
02/15/2022
PERMIT REVIEW SET
NOT FOR CONSTRUCTION
21005
BUILDING PERMIT - NFC
A6.1
DOOR AND FINISH
SCHEDULES
AS
NI
T
R
O
C
A
R
W
A
S
H
RE
X
B
U
R
G
,
I
D
13
7
1
N
2
N
D
E
RE
X
B
U
R
G
,
I
D
8
3
4
4
8
5/4/22
1/4" = 1'-0"
DOOR PANEL TYPES
ROOM FINISH SCHEDULE
ROOM #ROOM NAME
FLOORS WALLS CEILING
WIN
D
O
W
C
O
V
E
R
I
N
G
REMARKSMA
T
E
R
I
A
L
FI
N
I
S
H
BA
S
E
NORTH EAST SOUTH WEST
MA
T
E
R
I
A
L
FI
N
I
S
H
HE
I
G
H
T
MA
T
E
R
I
A
L
FI
N
I
S
H
WA
I
N
S
C
O
T
MA
T
E
R
I
A
L
FI
N
I
S
H
WA
I
N
S
C
O
T
MA
T
E
R
I
A
L
FI
N
I
S
H
WA
I
N
S
C
O
T
MA
T
E
R
I
A
L
FI
N
I
S
H
WA
I
N
S
C
O
T
101 MANAGER CS PC1 RB1 GB P1 - GB P1 - GB P1 - GB P1 - SAP1 FF 10' - 6" -
102 CONTROL CS PC1 RB1 GB P1 - GB P1 - GB P1 - GB P1 - SAP1 FF 10' - 6" -
103 HALL CS PC1 RB1 GB P1 - GB P1 - GB P1 - GB P1 - SAP1 FF 10' - 6" -
104 TOILET CS T2 T1 T1/GB P1 - T1/GB P1 - T1/GB P1 - T1/GB P1 - GSB P1 9' - 0" -
105 CLEAN EQUIPMENT CS PC1 RB1 PLY P3 - PLY P3 - PLY P3 - PLY P3 - CC - -
106 EQUIPMENT CS CC2 - CW - - PLY P3 - CW - - PLY P3 - CC - -
107 ELECTRICAL CS CC2 - PLY P3 - CW - - PLY P3 - PLY P3 - CC - -
108 MAT WASH CS CC2 - PLY PVC - CW - - PLY PVC - PLY PVC - CC - - PLYWOOD WITH EXTRUTECH LINER AT INTERIOR WALLS
109 WASH TUNNEL CS CC2 - CW CC1 - CW CC1 - CW CC1 - CW CC1 - CC - - CAULK ENTIRE PERIMTER OF TUNNEL CEILING TO WALL JOINT
110 WASH TUNNEL TRENCH CS CC2 - CW - - CW - - CW - - CW - - - - -
WS1 WINDOW SHADES MECHOSHADE, 6000 SERIES, 3% OPEN, COLOR: TBD SEE SCHEDULE / ELEVATIONS
T2 PORCELAIN FLOOR TILE AMERICAN OLEAN, INFUSION, GRAY FABRIC, IF55, 12x24 AT TOILET ROOM FLOOR
T1 PORCELAIN WALL TILE AMERICAN OLEAN, HORIZON, GREY JOLLY, HZ04, 6x16, HORIZONTAL AT TOILET ROOM WALLS, PARTIAL HEIGHT, SEE ELEVATIONS
ST1 WOOD DOOR STAIN MINWAX, WOOD FINISH, PENETRATING STAIN, CLASSIC GRAY 271, TWO COATS ALL WOOD DOORS
SS1 SOLID SURFACE COUNTERTOPS WILSONART 9091ML, MIDNIGHT MELANGE ALL COUNTERTOPS AND ALL WINDOW SILLS AT OFFICE AREA
SAP1 ACOUSTICAL CEILING PANEL ARMSTRONG, CORTEGA #769, SQUARE EDGE, IN 2x4 GRID -
RB1 RUBBER BASE 1 JOHNSONITE, 4" TOPSET, 0.125" (3.17mm) THICK, COVED TOE, COLOR: #82 BLACK PEARL AT OFFICES, WORK ROOM AND BREAK AREAS
PL1 PLASTIC LAMINATE 1 WILSONART 8200K-16, WHITE DRIFTWOOD ALL VERTICAL MILLWORK SURFACES EXCEPT AS NOTED
PC1 POLISHED CONCRETE
SCOFIELD, GRADE 1 - LIGHT SAND, CLASS 2 MEDIUM - 800 GRIT, APPLY FORMULA ONE LITHIUM
DENS. MP & GUARD-W PROTECT CONCRETE SURFACE DURING OTHER TRADES CONSTRUCTION
P4 SEVERE EXPOSURE PAINT BOD: MAX WAX PRODUCT PROVIDE AT ALL EMBED STEEL IN WASH TUNNEL WALLS. DO NOT PAINT STAINLESS STEEL PLATES.
P3 PAINT SHERWIN-WILLIAMS, SEMI-GLOSS; WHITE SANDED PLYWOOD WALLS AT WORK ROOM & ELECTRICAL
P2 HOLLOW METAL DOOR AND FRAME PAINT SHERWIN-WILLIAMS, SEMI-GLOSS, COLOR: 7674 PEPPERCORN ALL HOLLOW METAL DOORS & FRAMES; DO NOT PAINT STAINLESS STEEL
P1 INTERIOR WALL FIELD PAINT SHERWIN-WILLIAMS, EGG SHELL, COLOR: 7649 SILVERPLATE ALL WALLS, UNLESS NOTED OTHERWISE
EB1 VINYL EDGE BAND WILSONART 8200K-16, WHITE DRIFTWOOD USE AT ALL EDGE BANDS
CC2 CONCRETE FLOOR SEALER CRETO: DPS - DEEP PENETRATING SEALER PENETRATING SEALER AT ALL EXPOSED SLABS
CC1 CONCRETE WALL SEALER V-SEAL: V-SEAL 101 APPLIED AFTER POUR WITH SECONDARY PHASE II LITHIUM SILICATE WATER... PENETRATING SEALER AT INTERIOR OF CONCRETE WALLS AS INDICATED
TYPE:DESCRIPTION:MANUFACTURER:NOTES:
INTERIOR MATERIALS KEYPERIMETER SEAL PEMKO PK55 D 1
DOOR BOTTOM PEMKO 4131CRL A 1
WALL STOP ROCKWOOD 409 32D 1
ENTRANCE LOCK SARGENT 28-7G05-LL 26D 1
HW HINGES MCKINNEY T4A3386 - 4.5 X 4.5 X NRP 32D 3
GROUP 5 MANUFACTURER:PART #:FINISH:QUANITY:
PERIMETER SEAL PEMKO PK55 D 1
CLOSER... SARGENT SR-351-CPSH-TB, WITH HO EN 1
DOOR BOTTOM PEMKO 4131CRL A 1
WALL STOP ROCKWOOD 409 32D 1
SERVICE STATION LOCK SARGENT 28-10G44-LL (10 LINE) 26D 1
HW HINGES MCKINNEY T4A3386 - 4.5 X 4.5 X NRP 32D 3
GROUP 4 MANUFACTURER:PART #:FINISH:QUANITY:
ALL HARDWARE INCLUDING HINGES, CLASSROOM FUNCTION LEVER STYLE LOCK, CLOSER, THRESHOLD, DOOR SWEEP AND BRUSH
WEATHERSWEEP TO BE SUPPLIED BY DOOR MANUFACTURER. IT IS ACCEPTABLE AS OPTION TO PROVIDE EXIT DEVICE IN LIEU OF
INSIDE LATCH, BUT EXTERIOR LATCH MUST BE PROVIDED. NON-LATCHING PULL HANDLES ARE NOT ACCEPTABLE.
GROUP 3 MANUFACTURER:PART #:FINISH:QUANITY:
DOOR SWEEP PEMKO 345ANB A 1
WEATHER SEAL PEMKO PK55 D 1
CLOSER SARGENT SR-351-CPSH-TB, WITH HO EN 1
PASSAGE LATCH SARGENT 28-7U15-LL 26D 1
HW HINGES MCKINNEY T4A3386 - 4.5 X 4.5 X NRP 32D 3
GROUP 2 MANUFACTURER:PART #:FINISH:QUANITY:
BRUSH WEATHERSTRIP PEMKO 45061CNB A 1
DOOR SWEEP PEMKO 345ANB A 1
WEATHER SEAL PEMKO PK55 D 1
CLOSER SARGENT SR-351-CPSH-TB, WITH HO EN 1
CLASSROOM LOCK SARGENT 28-7G37-LL 26D 1
HW HINGES MCKINNEY T4A3386 - 4.5 X 4.5 X NRP... 32D 3
GROUP 1B MANUFACTURER:PART #:FINISH:QUANITY:
BRUSH WEATHERSTRIP PEMKO 45061CNB A 1
DOOR SWEEP PEMKO 345ANB A 1
WEATHER SEAL PEMKO PK55 D 1
THRESHOLD PEMKO 271A A 1
CLOSER SARGENT SR-351-CPSH-TB, WITH HO EN 1
CLASSROOM LOCK SARGENT 28-7G37-LL 26D 1
HW HINGES MCKINNEY T4A3386 - 4.5 X 4.5 X NRP 32D 3
GROUP 1A MANUFACTURER:PART #:FINISH:QUANITY:
DOOR HARDWARE SCHEDULE GENERAL NOTES
A. PROVIDE FRT SOLID WOOD BACKING IN FRAMED WALLS AT ALL WALL MOUNTED DOOR
STOPS.
B. ALL GLAZING IN DOORS AND ADJACENT LITES SHALL BE TEMPERED SAFETY GLAZING.
C. PROVIDE NRFC RATED EXTERIOR STOREFRONT WINDOW AND ENTRANCE ASSEMBLIES
FOR PERFORMANCE VALUES INDICATED IN SPECIFICATIONS.
D. SEE A0.1 ENERGY CODE NOTES FOR DOOR, FRAME AND GLAZING ASSEMBLY U-
VALUES.
E. DOOR HARDWARE SHALL MEET THE REQUIREMENTS OF LOCAL CODES AND
JURDICTIONAL REQUIREMNETS. HARDWARE SHALL NOT REQUIRE PINCHING, TIGHT
GRASPING, OR TWISTING OF THE WRIST TO OPERATE.
F. OVERHEAD DOOR: OVERALL SGI -2.12 OR BETTER
G. VERIFY ALL DOOR HARDWARE KEYING & KEY GROUPINGS WITH OWNER PRIOR TO
PROCUREMENT.
a. GRAND MASTER KEY BETWEEN SITES
b. MASTER KEY: ALL DOORS INCLUDING RESTROOMS
c. KEY GROUP 1: ALL DOORS EXCEPT MANAGERS OFFICE AND RESTROOMS
d. KEY GROUP 2: RESTROOMS ONLY
e. KEY GROUP 3: MANAGER'S OFFICE ONLY
ABBREVIATIONS
A ANNEALED GLASS
AL ALUMINUM
CC1, CC2...CONCRETE SURFACE FINISH AND / OR CURING COMPOUND
CS CONCRETE SLAB
CW CONCRETE WALL
EP1, EP2...EPOXY PAINT
FF FACTORY FINISHED
FG FROSTED GLASS
GB 5/8" TYPE 'X' GYPSUM BOARD
GSB 1/2" EXTERIOR GYPSUM SOFFIT BOARD
GHM GALVANNEALED HOLLOW METAL FRAME
HM HOLLOW METAL (WELDED FRAME)
IGM INSULATED GALVANNEALED METAL DOOR / FRAME WITH TOP CAP SEAL
IHM INSULATED HOLLOW METAL DOOR / FRAME
ISS INSULATED HOLLOW STAINLESS STEEL DOOR / FRAME WITH TOP CAP SEAL
IT 1" INSULATED TEMPERED SAFETY GLAZING
O OVERHEAD DOOR
P1, P2...PAINT
PLY 7/16" PLYWOOD SANDED SMOOTH FOR PAINT FINISH
S1, S2...SIGNAGE TYPE, SEE DETAIL THIS SHEET
SAP1 SUSPENDED ACOUSTICAL PANEL CEILING SYSTEM
SS STAINLESS STEEL FRAME (SEAMLESS)
VWP VINYL WALL PANELING
VT1 LUXURY VINYL TILE FLOORING
T TEMPERED SAFETY GLAZING
T1, T2...TILE
TC TILT CONCRETE WALLS OR HOLLOW CORE ROOF PANELS
WD WOOD PANEL WITH LAMINATE FACE & EDGE, BOD LYNDEN LD3500-4-SCL-HDPL
WS1 WINDOW SHADE
NOTES - FINISHES
1 INSULATED HOLLOW METAL DOOR. SEE SCHEDULE FOR HOLLOW METAL AND
GALVANNEALED "A" OR "ZF" COATED UNITS. WHERE GALVANNEALED UNITS ARE
SPECIFIED, PROVIDE 0.6 OUNCES OF ZINC PER SQUARE FOOT (60 WEIGHT).
2 STOREFRONT ENTRANCE DOOR. PROVIDE WIDE STILE UNITS TO ACCOMMODATE
MORTISE LOCK SYSTEMS.
3 WOOD SOLID CORE DOOR.
CODE SIGNAGE
PROVIDE BASIS-OF-DESIGN CODE COMPLIANT SIGNAGE WITH BRAILLE LETTERING FOR
THE FOLLOWING ROOMS AS MANUFACTURED BY INPRO CORPORATION OR ARCHITECT
APPROVED EQUAL:
S1: TACTILE EXIT SIGNS:
BLACK FACE, WHITE TEXT4”H X 8”W (S320QS-EX-0152)
MOUNT ON WALL AT HINGE SIDE OF DOOR #107b.
S2: UNISEX TOILET ROOM:
BLACK FACE, WHITE TEXT 8”X 6”(S320QS-UH-0152)
MOUNT ON WALL AT STRIKE SIDE OF DOORS #106, #112.
S3: MECHANICAL ROOM:
BLACK FACE, WHITE TEXT 4”H X 8”W (S320QS-MR-0152)
MOUNT ON WALL AT STRIKE SIDE OF DOOR #110B.
S4: ELECTRICAL ROOM:
BLACK FACE, WHITE TEXT 4”H X 8”W (S320QS-ELE-0152)
MOUNT ON WALL AT STRIKE SIDE OF DOOR #111.
DOOR SCHEDULE
DOOR
NUMBER
SIZE DOOR FRAME DETAILS
FI
R
E
R
A
T
I
N
G
HA
R
D
W
A
R
E
G
R
O
U
P
SI
G
N
A
G
E
REMARKSWI
D
T
H
HE
I
G
H
T
TY
P
E
TH
I
C
K
N
E
S
S
MA
T
E
R
I
A
L
FI
N
I
S
H
GL
A
Z
I
N
G
TY
P
E
MA
T
E
R
I
A
L
FI
N
I
S
H
THRESHOLD:
HE
A
D
JA
M
B
101 3' - 0" 7' - 0" F 1 3/4" WD ST1 - S9 HM P2 A5.1/A4 A5.1/A4 -5 - WOOD DOOR, HOLLOW METAL FRAME
102a 3' - 0" 7' - 0" G 1 3/4" AL FF GL-1 S5 AL FF - - - 3 S1 ALUMINUM ENTRANCE DOOR AND STOREFRONT FRAME
102b 3' - 0" 7' - 0" G 1 3/4" AL FF GL-1 S1 AL FF - - - 3 S1 ALUMINUM ENTRANCE DOOR AND STOREFRONT FRAME
103 2' - 10" 7' - 0" F 1 3/4" SS FF - S6 HM SS A5.1/B1 A5.1/B2 -1B - STAINLESS STEEL DOOR, HOLLOW METAL SS FRAME
104 3' - 0" 7' - 0" F 1 3/4" IGM P2 - H1 HM TP5 A5.1/B3 A5.1/B4 - 4 S2 GALVANNEALED DOOR, HOLLOW METAL FRAME
105a 3' - 0" 7' - 0" F 1 3/4" WD ST1 - H1 HM P2 A5.1/A4 A5.1/A4 - 2 - WOOD DOOR, HOLLOW METAL FRAME
105b 3' - 0" 7' - 0" F 1 3/4" IHM P2 - H1 HM P2 A5.1/A4 A5.1/A4 - 2 - INSULATED HOLLOW METAL DOOR AND FRAME
106a 3' - 0" 7' - 0" F 1 3/4" IGM P2 - H1 HM TP5 A5.1/B1 A5.1/B2 - 1A S1, S3 GALVANNEALED DOOR, HOLLOW METAL FRAME
106b 3' - 0" 7' - 0" F 1 3/4" SS FF - H1 HM SS A5.1/B1 A5.1/B2 -1B - STAINLESS STEEL DOOR, HOLLOW METAL SS FRAME
107 3' - 0" 7' - 0" F 1 3/4" IGM P2 - H1 HM TP5 A5.1/B1 A5.1/B2 - 1A S1, S4 GALVANNEALED DOOR, HOLLOW METAL FRAME
OH106 6' - 0" 8' - 0" O 2" - FF - - - FF A5.1/C1 A5.1/C2 - - - VINYL SPEED DOOR; OWNER FURNISHED, CONTRACTOR INSTALLED
OH108 10' - 0" 8' - 0" O 2" - FF - - - FF A5.1/C1 A5.1/C2 - - - VINYL SPEED DOOR; OWNER FURNISHED, CONTRACTOR INSTALLED
OH109a 12' - 0" 10' - 0" O 2" - FF - - - FF A5.1/C1 A5.1/C2 - - - MANUAL OPERATED OVERHEAD COILING DOOR; OWNER FURNISHED, CONTRACTOR
INSTALLED
OH109b 12' - 0" 10' - 0" O 2" - FF - - - FF A5.1/C1 A5.1/C2 - - - VINYL SPEED DOOR; OWNER FURNISHED, CONTRACTOR INSTALLED
1/4" = 1'-0"
CODE SIGNAGE
REVISIONS
#DATE
1 5/4/22
1
NOT
F
O
R
C
O
N
S
T
R
U
C
T
I
O
N
2"
DOOR SIZE
VARIES PER 2"
DOOR SIZE
VA
R
I
E
S
P
E
R
2"
1
T/O FLOOR
100' -0"
D1
A5.1
D2
A5.1
D2
A5.1
D4
A5.1
2"
2'
-
8
"
2"
3'
-
1
0
"
2"
3'
-
0
"
8' - 0"
10
'
-
0
"
2" 4' - 6" 0" 3' - 2" 2"
GL-1 GL-1
GL-1
102b
GL-1
08 42 13
10 71 13.43
T/O FLOOR
100' -0"
7'
-
0
"
3'
-
0
"
2' - 6"
D1
A5.1
D2
A5.1
D2
A5.1
D3
A5.1
GL-1
08 43 13
10 71 13.43
T/O FLOOR
100' -0"
7'
-
0
"
3'
-
0
"
D1
A5.1
D2
A5.1
D2
A5.1
D3
A5.1
4' - 0"
GL-1
08 43 13
10 71 13.43
T/O FLOOR
100' -0"
3'
-
0
"
7
'
-
0
"
8' - 0"
D3
A5.1
D1
A5.1
D2
A5.1
D2
A5.1
GL-1
10
'
-
0
"
08 43 13
10 71 13.43
GL-1
GL-1 GL-1
T/O FLOOR
100' -0"
10
'
-
0
"
D1
A5.1
D2
A5.1
D2
A5.1
D4
A5.1
2" 2' - 2" 2" 3' - 0" 2" 2' - 2" 2"
8' - 0"
2"
6
'
-
1
0
"
2
"
2
'
-
8
"
2
"
102a
GL-1
GL-1GL-1GL-1
GL-1
GL-1 08 42 13
10 71 13.43
T/O FLOOR
100' -0"
B1
A5.1
B2
A5.1
B2
A5.1
B2
A5.1
GL-2
103
2' - 10" 4' - 1"
3'
-
1
0
"
2"
3'
-
0
"
08 11 13
T/O FLOOR
100' -0"
B1
A5.1
B2
A5.1
B2
A5.1
B2
A5.1
4'
-
2
"
3'
-
0
"
7' - 5 1/2"
GL-4
08 12 13
T/O FLOOR
100' -0"
4'
-
2
"
3'
-
0
"
4' - 0"
GL-4
A4
A5.1
A4
A5.1
A4
A5.1
A4
A5.1
08 12 13
T/O FLOOR
100' -0"
2"
3'
-
1
0
"
2"
3'
-
0
"
2" 4' - 6" 2" 3' - 0" 2"
8' - 0"
GL-2
101
A4
A5.1
A4
A5.1
A4
A5.1
A4
A5.1
7'
-
2
"
08 11 13
T/O FLOOR
100' -0"
A1
A5.1
A2
A5.1
A2
A5.1
A3
A5.1
1'
-
0
"
7
'
-
0
"
5' - 0"
GL-2
T/O FLOOR
100' -0"
A3
A5.1
A1
A5.1
A2
A5.1A2
A5.1
GL-2GL-2
1'
-
0
"
7
'
-
0
"
10' - 0"
2" 4' - 9" 2" 4' - 9" 2"
STAMP:
THESE DOCUMENTS HAVE BEEN PRODUCED AS AN
INSTRUMENT OF SERVICE AND ARE INTENDED SOLELY
FOR THE PURPOSE OF CONSTRUCTING, USING AND
MAINTAINING THE PROJECT. SPOTLESS WASH
SOLUTIONS USA INC, AS THE ARCHITECT OF RECORD
FOR THE PROJECT RETAINS OWNERSHIP OF THESE
DOCUMENTS.
ANY USE OF THESE DOCUMENTS OR USE OF THIS
DESIGN, IDEAS OR CONCEPTS DESCRIBED HEREIN IN
WHOLE OR PART BY ANY MEANS WHATSOEVER IS
STRICTLY PROHIBITED EXCEPT BY WRITTEN CONSENT
OF SPOTLESS WASH SOLUTIONS USA INC.
REPRODUCTION OF THIS DOCUMENT IS STRICTLY
PROHIBITED EXCEPT BY WRITTEN CONSENT OF
SPOTLESS WASH SOLUTIONS USA INC.
COPYRIGHT 2022
SPOTLESS WASH SOLUTIONS USA INC.
CHECKED:
DATE:
JOB NUMBER:
ISSUED FOR:
SHEET NUMBER:
SP
O
T
L
E
S
S
W
A
S
H
S
O
L
U
T
I
O
N
S
PO
B
O
X
5
4
5
6
TW
I
N
F
A
L
L
S
,
I
D
A
H
O
8
3
3
0
3
PH
.
(
2
0
8
)
8
4
1
-
4
5
2
4
DRAWN:
BI
N
D
I
N
G
02/15/2022
PERMIT REVIEW SET
NOT FOR CONSTRUCTION
21005
BUILDING PERMIT - NFC
A6.2
FRAME TYPES
AS
NI
T
R
O
C
A
R
W
A
S
H
RE
X
B
U
R
G
,
I
D
13
7
1
N
2
N
D
E
RE
X
B
U
R
G
,
I
D
8
3
4
4
8
5/4/22
1/4" = 1'-0"
STOREFRONT FRAMES
H1
1 : 50
HOLLOW METAL FRAMES
GENERAL NOTES
A. ALL GLAZING IN DOORS AND ADJACENT LITES AND WHERE OTHERWISE NOTED SHALL
BE TEMPERED SAFETY GLAZING.
B. PROVIDE NRFC RATED EXTERIOR STOREFRONT WINDOW AND ENTRANCE ASSEMBLIES
FOR PERFORMANCE VALUES INDICATED.
C. BASIS OF DESIGN STOREFRONT SYSTEM IS KAWNEER TRIFAB 451T.
D. BASIS OF DESIGN ENTRANCE DOOR SYSTEM IS KAWNEER 350T.
E. BASIS OF DESIGN SUNSHADE IS KAWNEER VERSOLEIL SUNSHADE OUTRIGGER SYSTEM
WITH PLANAR STYLE BADES.
F. ALL STOREFRONT DOORS AND ENTRANCE DOORS ARE CLEAR ANODIZED.
G. PROVIDE STOREFRONT OR CURTAINWALL ASSEMBLIES EXCEEDING THE FOLLOWING
ENERGY PERFORMANCE CHARACTERISTICS PER NECB:
a. FIXED WINDOWS: OVERALL SGI -0.39 OR BETTER
b. OPERABLE WINDOWS: OVERALL SGI -0.39 OR BETTER
c. ENTRANCE DOORS SOLID: OVERALL SGI -0.35 OR BETTER
H. AS-BUILT FRAME OPENINGS SHALL BE VERIFIED PRIOR TO SHOP DRAWINGS AND
FRAME FABRICATION. SUBMIT RFI'S FOR DISCREPANCIES.
I. FIRE-RATED GLAZING TO BE FIRELITE OR APPROVED EQUAL SET IN 60-MIN RATED
HOLLOW METAL FRAME.
J. GLAZING TYPES: SEE SPECIFICATIONS. ALL GLASS IS HEAT STRENGTHENED
TEMPERED SAFETY.
a. GL-1: LOW-E, GREY INSULATING GLASS UNIT
b. GL-2: CLEAR, LOW REFLECTANCE INSULATING GLASS UNIT
c. GL-3: CLEAR, 60-MIN FIRE RATED INSULATING GLASS UNIT (NOT USED)
d. GL-4: SURVEILLANCE MIRROR GLASS
SHEET NOTES
1 INSULATED HOLLOW METAL DOOR OR WOOD DOOR AS SCHEDULED.
S1S2S3S4S5
H4H5 H3 H2
S6S7
KEYNOTES
MARK:DESCRIPTION:
08 11 13 HOLLOW METAL DOOR AND FRAME AS SCHEDULED. PAINT.
08 12 13 HOLLOW METAL FRAME AS SCHEDULED. PAINT.
08 42 13 ALUMINUM-FRAMED ENTRANCE
08 43 13 ALUMINUM-FRAMED STOREFRONT
10 71 13.43 FIXED SUN SCREENS INTEGRAL WITH ALUMINUM STOREFRONT
0'4'2'8'
REVISIONS
#DATE
NOT
F
O
R
C
O
N
S
T
R
U
C
T
I
O
N
T/O FLOOR
100' -0"
E011E012
E013
E014
3
A7.1
4b 4a
SAND / OIL INTERCEPTOR
3
THIRD SETTLING TANK
2
SECOND SETTLING TANK
1
FIRST SETTLING TANK
3"
1'
-
4
"
2'
-
0
"
RW5
RW5
RW5 05 43 00
SL
3
SL
3
SL
3
05 43 00
C5
d
C5
c
C5
b
C5
a
E1
0
4
10
"
2'
-
0
"
1'
-
4
"
2'
-
0
"
1'
-
4
"
2'
-
0
"
6 8
7
DIRECTION OF FLOW
91.20 IE
1'
-
4
"
2'
-
0
"
E1
0
5
1 2
1 2
1 2
1 2
4
11 10
11 10
11 10
5
5
5
3
3
3
3
7
7
RW
2
RW
3
93.17 IE
D2
93.26 IE
D3
5'
-
4
"
8'
-
0
"
8"
8"
8"
92.50 IE
91.83 IE
91.00 IE
2"
8"
92.00 IE
1
A7.1
E014 E013 E012 E011 3
A7.1
1 2
3
4b 4a
4
GREASE INTERCEPTOR
1
2
3
5
11 10
3
THIRD SETTLING TANK
7
1 2
3
5
11 10
2
SECOND SETTLING TANK
1 2
5
3
1
FIRST SETTLING TANK
RW5
RW5RW5
6 8
SL
3
SL
3
SL
3
E104
7 71110C5d
C5c
C5b
C5a
E105
DIRECTION OF FLOW
RW
3
RW
2
D2
D3
T/O FLOOR
100' -0"
T/O FOOTING
97' -10"
B C D
95.56 B.T.
94.00 BP
TRASH PIT CONVEYOR
TRENCH
106
EQUIPMENT
109
WASH
TUNNEL
RW
5
05 53 00
05 53 00
1FIRST SETTLING
TANK
A7.1
4
A1.2
3
95.52 IE
1/4" / 12"
95.35 IE
8" D2
8" D2
SL
3
10" D1
1/4" / 12"
93.96 IE
93.26 IE93.17 IE
1
A7.1
94.75 TT
87.83 BT
T/O FLOOR
100' -0"
94.91 IE
96.30 IE
05 53 00
05 53 00
95.95 TG
03 15 13
10" INLET FROM
TRENCH
8" OUTLET TO
RECLAIM TANK
94.95 BP
A1.2
4
A1.2
4
A1.2
6
A1.2
6
05 53 00.1 05 53 00.1
STAMP:
THESE DOCUMENTS HAVE BEEN PRODUCED AS AN
INSTRUMENT OF SERVICE AND ARE INTENDED SOLELY
FOR THE PURPOSE OF CONSTRUCTING, USING AND
MAINTAINING THE PROJECT. SPOTLESS WASH
SOLUTIONS USA INC, AS THE ARCHITECT OF RECORD
FOR THE PROJECT RETAINS OWNERSHIP OF THESE
DOCUMENTS.
ANY USE OF THESE DOCUMENTS OR USE OF THIS
DESIGN, IDEAS OR CONCEPTS DESCRIBED HEREIN IN
WHOLE OR PART BY ANY MEANS WHATSOEVER IS
STRICTLY PROHIBITED EXCEPT BY WRITTEN CONSENT
OF SPOTLESS WASH SOLUTIONS USA INC.
REPRODUCTION OF THIS DOCUMENT IS STRICTLY
PROHIBITED EXCEPT BY WRITTEN CONSENT OF
SPOTLESS WASH SOLUTIONS USA INC.
COPYRIGHT 2022
SPOTLESS WASH SOLUTIONS USA INC.
CHECKED:
DATE:
JOB NUMBER:
ISSUED FOR:
SHEET NUMBER:
SP
O
T
L
E
S
S
W
A
S
H
S
O
L
U
T
I
O
N
S
PO
B
O
X
5
4
5
6
TW
I
N
F
A
L
L
S
,
I
D
A
H
O
8
3
3
0
3
PH
.
(
2
0
8
)
8
4
1
-
4
5
2
4
DRAWN:
BI
N
D
I
N
G
02/15/2022
PERMIT REVIEW SET
NOT FOR CONSTRUCTION
21005
BUILDING PERMIT - NFC
A7.1
RECLAIM SYSTEM
DETAILS
AS
NI
T
R
O
C
A
R
W
A
S
H
RE
X
B
U
R
G
,
I
D
13
7
1
N
2
N
D
E
RE
X
B
U
R
G
,
I
D
8
3
4
4
8
5/4/22
SHEET NOTES
1 24" CONTINUOUS PRECAST MANHOLE, LID AND FRAME, TYPICAL.
2 30" CONTINUOUS PRECAST MANHOLE, LID AND FRAME, TYPICAL.
3 FIXED LADDER PROVIDED BY TANK MANUFACTURER, TYPICAL. FIRST LADDER RUNG SHALL BEGIN NO MORE
THAN 12" ABOVE BOTTOM OF TANK AND EXTEND UP INTO TANK GOOSENECK WITH THE HIGHEST
LADDER RUNG NO MORE THAN 12" BELOW MANHOLE RIM ELEVATION.
4 PROVIDE PIPING AT INTERIOR AND EXTERIOR OF GREASE INTERCEPTOR TO MEET LOCALLY ADOPTED
CODES AND STANDARDS. SUBMIT RFI IF DESIGN DOES NOT CONFORM TO LOCAL JURISDICTIONAL
REQUIREMENTS. CONTRACTOR SHALL REVIEW REQUIREMENTS WITH PLUMBING INSPECTOR PRIOR TO
FABRICATION.
5 ALL PIPES TO TANKS AND BETWEEN TANKS ARE 8" SCH40 PVC UNLESS INDICATED OTHERWISE.
6 8" SCH40 PVC WITH CAST IRON GCO - GRADE CLEAN-OUT. COVER TO BE INSCRIBED "SANITARY SEWER
CLEANOUT".
7 EXTEND PIPE DOWN WALL TO HEIGHT INDICATED AND ATTACH WITH P1000-ST 316 STAINLESS STEEL
UNISTRUT PARALLEL TO PIPE WITH SS CUSH-A-CLAMP CONNECTOS. ANCHOR UNISTRUT TO TANK WITH SS
WEDGE ANCHORS AT 12" O.C.
8 3" SCH-40 PVC VENT TO EXTEND TO INSIDE STUD WALL CAVITY AND VTR WITH TERMINATION. ROUTING PER
GC.
10 1 1/2" SCH80 PVC AT LID FOR AIR, SECURE TO WALL TO 3' ABOVE BOTTOM OF TANK WITH SS UNISTRUT, SEE
SHEET A1.2 FOR TERMINATION AT BUILDING.
11 1" SCH80 PVC AT LID FOR OZONE,
SECURE TO WALL TO 3' ABOVE BOTTOM OF TANK WITH SS UNISTRUT.
GENERAL NOTES
A. TANKS: STRUCTURAL ENGINEERING DESIGN OF TANKS IS RESPONSIBILITY OF THE
CONTRACTOR. PROVIDE STAMPED AND SEALED SHOP DRAWING SUBMITTAL FOR
ARCHITECT'S REVIEW. DESIGN SHALL ASSUME VEHICLE LIVE LOAD FOR (HL-93 DESIGN
TRUCK) = 32 KIP (SINGLE AXLE).
B. THE CIVIL ENGINEER WILL PROVIDE MANHOLE RIM ELEVATIONS. IT IS CONTRACTOR'S
RESPONSIBILITY TO REQUEST / VERIFY RIM ELEVATIONS WITH CIVIL ENGINEER.
C. TANKS: IF TANKS ARE MANUFACTURED WITH MULTIPLE SECTIONS, PROVIDE (2)
CONTINUOUS VOLCLAY WATER STOP STRIPS OR WATERPROOFING MEASURE
RECOMMENDED BY TANK MANUFACTURER AT EACH JOINT.
D. TANKS: MODIFY MANUFACTURER'S STANDARD PRECAST TANK SPECIFICATIONS TO MATCH
REQUIREMENTS INDICATED.
E. TANKS: ALL HOLES FOR INLET / OUTLET PIPES SHALL BE CORE DRILLED. PROVIDE A WATER
TIGHT SEAL (KOR-N-SEAL I OR LINK-SEAL CONNECTORS). GROUTED CONNECTIONS ARE
NOT PERMITTED.
F. TANKS: TANK WATERTIGHTNESS IS RESPONSIBILITY OF THE CONTRACTOR. FILL TANKS
AND TEST WATERTIGHTNESS PRIOR TO BACKFILLING.
G. MANHOLE COVERS AND FRAMES: PROVIDE RECESSED FLUSH HEAVY DUTY TRAFFIC RATED
ASTM A48 FIBERGLASS BOLT DOWN MANHOLE COVER. PROVIDE 32mm (1-1/4") MINIMUM
LETTERS INDICATING "RECLAIM". LABELING AT MANHOLE COVERS WITH LADDERS TO READ
"LADDER".
H. MANHOLE: PRECAST MANHOLE TO EXTEND FROM TOP OF TANK TO UNDERSIDE OF
MANHOLE LID. SET LID PER MANUFACTURER'S INSTRUCTIONS.
I. TANKS: IT IS CONTRACTOR'S RESPONSIBILITY TO REQUEST / VERIFY RIM ELEVATIONS WITH
GRADING PLAN DESIGNER WHEN NOT ILLUSTRATED ON GRADING PLAN.
J. TANKS: SEE EQUIPMENT SCHEDULE FOR TANK RESPONSIBILITY MATRIX.
K. PIPING: ALL PIPING TO TANKS, BETWEEN TANKS, INSIDE OF TANKS AND BACK TO BUILDING
IS RESPONSIBILITY OF THE CONTRACTOR. TERMINATE PIPING A MINIMUM OF 203mm (8")
PAST INSIDE OF TANK. A SINGLE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL PIPING
INCLUDING WHERE THE PIPES STUB UP INSIDE THE BUILDING AT THE EQUIPMENT ROOM.
L. PIPING: ALL PIPES TO, BETWEEN AND INSIDE OF TANKS ARE 300mm (12") SCH40 PVC UNLESS
INDICATED OTHERWISE. TERMINATE PVC PIPING A MINIMUM OF 200mm (8") PAST INSIDE
FACE OF TANK WALL.
M. PROTECT EXISTING AND NEW TANKS AND PIPING DURING CONSTRUCTION ACTIVITIES. IT IS
RESPONSIBILITY OF CONTRACTOR FOR CONSTRUCTION DAMAGE TO EXISTING AND NEW
TANK ASSEMBLIES AND PIPING.
N. LADDERS: EXTEND FROM BOTTOM OF TANK TO TOP OF MANHOLE LID. MAXIMUM RISER
FROM TANK BOTTOM TO GRADE AT LID TO BE 305mm (12"). USE BASIS-OF-DESIGN LADDER
OR MANUFACTURED STEP PER LANE POLYPROPYLENE P-10938 OR EQUAL.
O. INSTALL XYPEX WATERPROOFING AT CONCRETE TANK WALLS, TRASH PIT WALLS, PUMP PIT
WALLS, CONVEYOR TRENCH WALLS.
P. ABBREVIATIONS:
a. BP = BOTTOM OF PIT
b. BT = BOTTOM OF TRENCH
c. IE = INVERT ELEVATION AT PIPE
d. TG = TOP OF GRATING
RECLAIM PIPE SCHEDULE
#DESCRIPTION
RW1 6" SCH80 PVC RECLAIM WATER HEADER PIPING FROM FILTER TO PUMPS AND TRENCH FLUSH
RW2 6" SCH80 PVC RECLAIM WATER FROM SUMP PUMP TO FILTER
RW3 4" SCH80 PVC RECLAIM WATER FROM NIGHT TIME SUMP PUMP. STUB UP AT EQUIPMENT ROOM AND
CONNECT TO VERTICAL LEG OF RW4 PUMBING WITH WYE FITTING ARRANGED FOR DOWNWARD FLOW AT
12" ABOVE SLAB
RW4 6" SCH40 PVC RECLAIM WATER TRENCH FLUSH PIPE ASSEMBLY. PROVIDE CONSTANT DOWNWARD
SLOPE EACH DIRECTION FROM WYE FITTING AS ILLUSTRATED TO SIDEWALL OF TRENCH. PIPE INVERT AT
TRENCH TO BE 3" ABOVE GUTTER FLOOR OF TRENCH TO ACCOMMODATE WATERSTOP ASSEMBLIES.
RW5 8" SCH40 PVC RECLAIM WATER SANITARY TEE BETWEEN TANKS. PIPE INVERT AT EACH TANK TO BE SAME
ELEVATION AS INLET PIPE RW1
RECLAIM CONDUIT SCHEDULE
#DESCRIPTION
C5a CONDUIT TO MCC FOR SUMP PUMP VFD CABLES. SEE SHEET A1.2b FOR CONDUIT RUNS AND STUB-UP
LOCATIONS
C5b CONDUIT TO MCC FOR SUMP PUMP VFD CABLES. SEE SHEET A1.2b FOR CONDUIT RUNS AND STUB-UP
LOCATIONS
C5c 1" PVC CONDUIT TO TC FOR FLOAT CONDUCTORS
C5d 1" PVC CONDUIT TO TC FOR HEAT SENSOR CONDUCTORS
1/4" = 1'-0"
RECLAIM SYSTEM SECTION1
1/4" = 1'-0"
RECLAIM SYSTEM PLAN VIEW2
NORTH
0'4'2'8'
1/4" = 1'-0"
RECLAIM / TRASH PIT / TRENCH SECTION3
3/4" = 1'-0"
TRASH PIT4
KEYNOTES
MARK:DESCRIPTION:
03 15 13 WATERSTOP, SERRATED
05 43 00 SLOTTED CHANNEL FRAMING, UNISTRUT P1000 1-5/8" X 1-5/8",PRE-GALVANIZED, STANDARD HOLE
PATTERN
05 53 00 METAL GRATING, OWNER PROVIDED, AMD 1.5x1.5x1.5 MOLDED PROFILE NUMBER 14, YELLOW, OR
APPROVED EQUAL
05 53 00.1 1.75" x 1.75" x 1/4" FEMALE EMBED ANGLE AT PERIMETER OF SLAB OPENING FOR OWNER
PROVIDED GRATING. PROVIDE 1/4" x 2" NELSON STUDS AT 12" O.C.
REVISIONS
#DATE
NOT
F
O
R
C
O
N
S
T
R
U
C
T
I
O
N
fl
fl
fl
fl
fl
fl
fl
fl
fl
toetoetoetoetoetoetoetoetoe
toe
toetoetoe
eee
eee
pp
sd
sd
pp
tob
to
b
14'' w 14'' w
s
IR
R
IR
R
IR
R
IR
R
IR
R
IR
R
fl
fl
fl
fl
fl
fl
fl
fl
fl
toetoetoetoetoetoetoetoetoe
toe
toetoetoe
eee
eee
pp
sd
sd
pp
tob
to
b
14'' w 14'' w
s
7'
7'14'
5.5'15
'
7'
R3
.
5
'
R3.5'
9'
TYP
12.5'
TYP
9'
TYP
12.5'
TYP
20
'
TY
P
131.5'
9'
15
'
5.5'
3.5'
1.5'
23'
29
'
3.5'
30
.
3
'
11.5'
R4'
24
'
11.5'
1.1'
68'
13
.
3
'
12.1'
R
4
'
5'
6.
7
'
24'
55
.
7
'
5'
R
3
.
5
'
1.
5
'
233.9'
R3
0
.
5
'
2.8'
R2
9
.
5
'
20'
R2
9
.
5
'
2.8'
R3
0
.
5
'
30.7'
R
5
.
5
'
R20
'6.7'
R1
9
.
5
'
24.2'
14
'
R14
'
11.9'
17.1'
5'
5.
4
'
9.
1
'
R
4
.
5
'
42'
46.5'
22
.
6
'
5'
5'
16
.
4
'
9'
11
.
9
'
14
'
31
'
R11
.
5
'
35'
2.9'
R
4
.
5
'
11.7'
R3
0
.
5
'
2.8'
R2
9
.
5
'
20'
7.1'
4.
5
'
7.9'13
.
5
'
4.
1
'
5'
R2
9
.
5
'
2.8'
R3
0
.
5
'
233.9'
R3.5
'
1'
R
3
.
5
'
235.2'
R5.
5
'
6'
18'
4'
R
1
'
21
.
9
'
21
.
4
'
20
.
1
'
24
'
12'
7'
17
.
5
'
9.5'
2.
5
'
14
.
5
'
47.5'
14
.
5
'
7'
11'
R
1
4
.
5
'
3.
5
'
15
'
11
.
7
'
9.4'
13
.
5
'
R4.5
'
3.9
'
6.5
'
5'
10
'
52.5'
1.5'
18
'
TY
P
8'
0.9'9.
7
'
17.7'
24'
23.5'
297.9'
5'
22
8
.
1
'
5'
5'
56
'
16
.
5
'
14
'
15
.
2
'
3'
3.
1
'
7.5'
7'
6.3'
10.5'
6.
5
'
4
'
302.8'26
.
8
'
6.
5
'
4.
6
'
26
.
3
'
29.1'
70
.
1
'
2.5'
R14
.
5
'
R
1
4
.
5
'
6.8'
30
'
3.5'
TYP
5.5'
5.5'
3.5'
TYP
7'
8'
7'
7'
6'
2'
22
.
6
'
55.5'
7'
11
.
9
'
6.4'
42
'
43
.
2
'
6.7'
29.1'
R4.5'
23.5'6'
13
.
2
'
2.5'
5'
10'
R2
.
5
'
R4'
R4'
8'
R4.5
'
1'
R
1
1
.
5
'
3' TYP
4.
5
'
T
Y
P
60
'
26
.
3
'
NOTE:
THIS LOT WILL BE
DESIGNED AS PART OF A
SEPARATE SITE PLAN
SUBMITTAL
1 5
RE
V
I
S
I
O
N
S
RE
V
#
DA
T
E
DR
A
W
I
N
G
I
N
F
O
DA
T
E
DE
S
I
G
N
E
D
DR
A
W
N
*S
E
E
G
E
N
E
R
A
L
N
O
T
E
S
S
H
E
E
T
WA
R
N
I
N
G
0
1
2
IF
T
H
I
S
B
A
R
D
O
E
S
N
O
T
ME
A
S
U
R
E
2
"
T
H
E
N
DR
A
W
I
N
G
I
S
N
O
T
T
O
S
C
A
L
E
CI
T
Y
R
E
V
I
E
W
S
E
T
ww
w
.
h
o
r
r
o
c
k
s
.
c
o
m
PAGE
C
PR
O
J
E
C
T
CH
E
C
K
E
D
D
B
A
#
2 3 4
21
9
4
S
n
a
k
e
R
i
v
e
r
P
k
w
y
.
,
S
u
i
t
e
2
0
5
Id
a
h
o
F
a
l
l
s
,
I
D
8
3
4
0
2
(2
0
8
)
5
2
2
-
1
2
2
3
PRELIMINARY
NOT FOR
CONSTRUCTION
H
O R R O C
K
S
E
N
G I N E E R
S
0 30'60'
SCALE: 1" = 30'
N
ID
-
L
D
-
4
0
7
0
-
2
1
CJ
F
TL
M
JB
F
05
/
0
3
/
2
0
2
2
OV
E
R
A
L
L
S
I
T
E
P
L
A
N
RE
X
B
U
R
G
N
O
R
T
H
N
I
T
R
O
C
A
R
W
A
S
H
RE
X
B
U
R
G
,
I
D
A
H
O
6
C.3.1
SHEET NOTES:
1.DRIVE AISLE DIMENSIONS MEASURED TO FACE OF CURB, WHERE CURB IS PROPOSED OR TO
EDGE OF PAVEMENT OTHERWISE.
SITE PLAN KEYNOTES
INSTALL LIGHT DUTY ASPHALT (SEE FLEXIBLE PAVEMENT SECTION
SUMMARY TABLE SHEET C.3.2)
INSTALL HEAVY DUTY ASPHALT (SEE FLEXIBLE PAVEMENT SECTION
SUMMARY TABLE SHEET C.3.2)
ADA SIGN PER DETAIL 4 SHEET C.3.2
INSTALL 1.5' FLAT PAN CURB & GUTTER SEE DETAIL 3 SHEET C.3.2
TIE INTO EXISTING ASPHALT, SAWCUT AS REQUIRED
INSTALL 4" THICK SIDEWALK, (WIDTH PER PLAN) PER ISPWC SD-709, 714,
714A, 714B UNLESS OTHERWISE NOTED
INSTALL BOLLARD PER DETAIL 5 SHEET C.3.2
INSTALL 6" THICKEND EDGE SIDEWALK PER DETAIL 6 SHEET C.3.2
INSTALL HEATED CONCRETE PER MANUFACTURES SPECIFICATIONS
INSTALL TRASH ENCLOSURE PAD ENCLOSURE PER CITY OF REXBURG SD-11
INSTALL ADA RAMP WITH TRUNCATED DOMES PER CITY OF REXBURG SD
INSTALL LANDSCAPE PER LANDSCAPE PLAN
STRIPING PER MUTCD STANDARDS
INSTALL CONCRETE PAVEMENT PER PCCP PAVEMENT SECTION PER TABLE
SHEET C.3.2
INSTALL 1.5' FLAT PAN CURB & GUTTER W/ DEPRESSED CURB HEAD PER
DETAIL 5 SHEET C.3.2
PYLON SIGN APPROXIMATE LOCATION
INSTALL LIGHT POLE (REFER TO ARCHITECTURAL AND ELECTRICAL PLANS
FOR DETAILS) LIGHT POLES SHOWN IN APPROXIMATE LOCATIONS
INSTALL STOP SIGN PER MUTCD STANDARDS
INSTALL VACUUM AND CANOPY SYSTEM PER ARCHITECTS EQUIPMENTS
PLAN
ELECTRICAL TRANSFORMER PAD (SEE ELECTRICAL PLANS)
INSTALL TYPICAL SECTION PER CITY OF REXBURG SD-3
CURB & GUTTER TRANSITION FROM CITY OF REXBURG SD-3 TO 1.5' FLAT PAN
CURB
INSTALL SHELTER SEE ARCHITECTURAL PLANS FOR DETAILS
SNOW STORAGE ARE ( SEE LANDSCAPE TABLE FOR AREA)
INSTALL CONCRETE CURB CUT DIMENSION PER PLAN
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
MOODY ST
NO
R
T
H
2
N
D
E
A
S
T
01
01
02
02
03
04
04
04
04
04
05
05
05
06
06
06
06
0808
09
10
11
11
12
12
12
12
12
12
12
12
12
12
12
12
12 1313
13
14
14
14
18
20
19
20
21
21
PROPOSED BUILDING
± 4,593 SF
C.
3
.
2
2
C.3.2
1
18
17
17
17
24
24
24
11
11
25
25
25
21
05
VAN ACCESSIBLE
ONLY LANDSCAPE AND
SIDEWALK OF ROW
104
3
22
19
05/04/22
PRE
L
I
M
I
N
A
R
Y
N
O
T
F
O
R
C
O
N
S
T
R
U
C
T
I
O
N
FOR
R
E
V
I
E
W
O
N
L
Y
PR
E
L
I
M
I
N
A
R
Y
N
O
T
F
O
R
CO
N
S
T
R
U
C
T
I
O
N
FO
R
R
E
V
I
E
W
O
N
L
Y
1 5
RE
V
I
S
I
O
N
S
RE
V
#
DA
T
E
DR
A
W
I
N
G
I
N
F
O
DA
T
E
DE
S
I
G
N
E
D
DR
A
W
N
*S
E
E
G
E
N
E
R
A
L
N
O
T
E
S
S
H
E
E
T
WA
R
N
I
N
G
0
1
2
IF
T
H
I
S
B
A
R
D
O
E
S
N
O
T
ME
A
S
U
R
E
2
"
T
H
E
N
DR
A
W
I
N
G
I
S
N
O
T
T
O
S
C
A
L
E
CI
T
Y
R
E
V
I
E
W
S
E
T
ww
w
.
h
o
r
r
o
c
k
s
.
c
o
m
PAGE
C
PR
O
J
E
C
T
CH
E
C
K
E
D
D
B
A
#
2 3 4
21
9
4
S
n
a
k
e
R
i
v
e
r
P
k
w
y
.
,
S
u
i
t
e
2
0
5
Id
a
h
o
F
a
l
l
s
,
I
D
8
3
4
0
2
(2
0
8
)
5
2
2
-
1
2
2
3
PRELIMINARY
NOT FOR
CONSTRUCTION
ID
-
L
D
-
4
0
7
0
-
2
1
CJ
F
TL
M
JB
F
05
/
0
3
/
2
0
2
2
SI
T
E
P
L
A
N
D
E
T
A
I
L
S
RE
X
B
U
R
G
N
O
R
T
H
N
I
T
R
O
C
A
R
W
A
S
H
RE
X
B
U
R
G
,
I
D
A
H
O
7
C.3.2
FLEXIBLE PAVEMENT SECTION SUMMARY
CLASSIFICATION LIGHT DUTY HEAVY DUTY
ASPHALTIC CONCRETE 2.5"3.0"
CRUSHED AGGREGATE BASE 4.0"6.0"
STRUCTURAL SUBBASE 10.0"14.0"
MATERIAL SPECIFICATIONS:
ASPHALTIC CONCRETE:ASPHALT MIX SHALL MEET THE REQUIREMENTS OF THE ISPWC, SECTION
810 CLASS III PLANT MIX. MATERIALS SHALL BE PLACED IN ACCORDANCE
WITH ISPWC STANDARD SPECIFICATIONS FOR HIGHWAY CONSTRUCTION.
AGGREGATE BASE:MATERIAL COMPLYING WITH ISPWC STANDARDS FOR CRUSHED
AGGREGATE MATERIALS
STRUCTURAL SUBBASE:THE MAXIMUM MATERIAL DIAMETER IS NO MORE THAN 2 3 THE COMPONENT
THICKNESS. GRADATION AND SUITABILITY REQUIREMENTS SHALL BE PER
ISPWC SECTION 801, TABLE 1.
HD 25'
50' BACK TO BACK
P/L
25'
2%
LANDSCAPE
2%
6.5'
LANDSCAPE
5'
79' ROW
6.5'5'.5'.5'
SCALE: NTS
MOODY STREET TYPICAL SECTION1
C.3.2
48'
96' BACK TO BACK
P/L
48'
2%
LANDSCAPE
2%
6.5'
LANDSCAPE
5'
125' ROW
6.5'5'.5'.5'
SCALE: NTS
NORTH 2ND EAST TYPICAL SECTION2
C.3.2
2.5'2.5'
2.5'2.5'
P/L
P/L
LANDSCAPING TABLE
*OVERALL SITE LANDSCAPING
SITE AREA = 51,793 SF
TOTAL LANDSCAPING = 14,240 SF (27.5% OF SITE)
TOTAL HARDSCAPE = 37,553 SF (72.5% OF SITE)
SITE INTERIOR LANDSCAPING FOR PARKING PROV. = 12,358 SF
SITE INTERIOR LANDSCAPING FOR PARKING REQ. = 1,284 SF
TOTAL SNOW REMOVAL AREA= 25,149.68 SF (48.55 % OF SITE)
TOTAL SNOW STORAGE = 2,793.79 SF (11.1% OF PLOW-ABLE
HARDSCAPE)
PARKING ANALYSIS
REQUIREMENTS REQUIRED PROVIDED
PARKING STALLS 13 18
ADA STALLS 1
TOTAL 13 19
BUILDING ANALYSIS
BUILDING MAIN FLOOR
BUILDING AREA
(TOTAL = 55,980 SF)±4,593 SF
MAX BUILDING HEIGHT 28'
BUILDING TYPE (IBC) *II-B* SPRINKLED
IBC OCCUPANCY
CLASSIFICATION AI, AII, AIII
NOTES:
* BUILDING TYPE TO BE VERIFIED WITH
ARCHITECTURAL PLANS, ARCHITECTURAL PLANS
TO SUPERCEDE.
STALL COUNT#
LD
SNOW STORAGE AREA
WIDTH VARIES
6"
VA
R
I
E
S
-
6
"
M
A
X
1'
-
6
"
6"
R = 1'
SE
E
G
R
A
D
I
N
G
P
L
A
N
SCALE:
6
C.3.2
6" THICKENED EDGE SIDEWALK
NTS
VA
R
I
E
S
3'
M
I
N
"
1
3
/
8
"
3"
M
I
N
.
9"9"
CAP TOP OF POST
3/8"X3 1/2"
CADMIUM PLATED
HEX HEAD BOLT WITH
FLAT LOCK WASHER
AND NUT
6'
-
0
"
4"
18
"
6"
12"
BLUE BACKGROUND
W/ WHITE SYMBOL
AND LETTERING
PROVIDE SIGN THAT
IDENTIFIES ALL VAN
ACCESSIBLE STALLS.
REFER TO PLAN FOR
LOCATIONS
NOTE: TOP OF POST TO
BE CUT 1/2" BELOW TOP
OF SIGN
SCALE:
3
C.3.2
FLAT PAN CURB & GUTTER
NTS
3/4" GRAVEL ROAD BASE
FIN. GRADE
(W/ LIP FLAT)
CONC. CURB & GUTTER
3/4'' GRAVEL
ROAD BASE
ASPHALT PAVEMENT
1.
0
'
0.
5
'
0.
5
'
2''±
4''
1.5'
0.5'
1'
SCALE:
4
C.3.2
TYPICAL HANDICAP SIGN DETAIL
NTSSCALE:
5
C.3.2
PIPE BOLLARD DETAIL
NTS
PER CITY OF REXBURG REQUIREMENTS FOR PARKING FOR
COMMERCIAL USE (CAR WASH) 3 STALLS PER 1,000 SF
6" VERTICAL
CURB & GUTTER
PER ISPWC6" - 3/4" CRUSHED GRAVEL
3" ASPHALT PLANT MIX
CHIP AND SEAL COAT
(FULL WIDTH)
COMPACT UPPER 6" OF
SUBGRADE TO 95% DRY DENSITY
6" VERTICAL
CURB & GUTTER
PER ISPWC 20" PIT RUN GRAVEL
6" VERTICAL
CURB & GUTTER
PER ISPWC3" - 3/4" CRUSHED GRAVEL
6" ASPHALT PLANT MIX
CHIP AND SEAL COAT
(FULL WIDTH)
COMPACT UPPER 6" OF
SUBGRADE TO 95% DRY DENSITY
6" VERTICAL
CURB & GUTTER
PER ISPWC 20" PIT RUN GRAVEL
ASPHALT
CRUSHED
AGGREGATE BASE
COMPACTED
SUBBASE
NATURAL GROUND
2 - #4 REBAR
EVENLY SPACED
SMOOTH SLOPED
MORTAR CAP PAINTED
ASPHALT PAVEMENT
OR CONCRETE WHERE
OCCURS SEE PLAN
6" DIA. STANDARD STEEL
PIPE FILLED WITH CONCRETE
AND PAINTED YELLOW
18" DIA. CONCRETE
FOOTING
(2) #6 BARS 12" LONG
EACH WAY WELD TO PIPE
ONLY LANDSCAPE AND
SIDEWALK OF ROW
FABRIC WRAP OUTER EDGES
FABRIC WRAP OUTER EDGES FABRIC WRAP OUTER EDGES
FABRIC WRAP OUTER EDGES
05/04/22
PRE
L
I
M
I
N
A
R
Y
N
O
T
F
O
R
C
O
N
S
T
R
U
C
T
I
O
N
FOR
R
E
V
I
E
W
O
N
L
Y
PR
E
L
I
M
I
N
A
R
Y
N
O
T
F
O
R
CO
N
S
T
R
U
C
T
I
O
N
FO
R
R
E
V
I
E
W
O
N
L
Y
fl
fl
fl
fl
fl
fl
fl
fl
fl
toetoetoetoetoetoetoetoetoe
toe
toetoetoe
eee
eee
pp
sd
sd
pp
tob
to
b
14'' w 14'' w 14'' w 14'' w
s
fl
fl
fl
fl
fl
fl
fl
fl
fl
toetoetoetoetoetoetoetoetoe
toe
toetoetoe
eee
eee
pp
sd
sd
pp
tob
to
b
14'' w 14'' w 14'' w 14'' w
s
4876
4878
4878
4877
4
8
7
5
48
7
7
4
8
7
5
4
8
7
6
TBC: 4878.20
TBC: 4878.00
FG: 4877.13
FG: 4877.56
FG: 4877.74
FG: 4876.99
TBC: 4879.25
TBC: 4879.29
TBC: 4878.96
TBC: 4878.96
DTBC: 4878.50
DTBC: 4878.47
TBC: 4878.88
TBC: 4878.81
TBC: 4878.93
TBC: 4878.44
TBC: 4878.56
TBC: 4878.38
TBC: 4878.46
TBC: 4878.10
TBC: 4878.05
TBC: 4878.14
TBC: 4878.36
TBC: 4878.99
TBC: 4878.89
TBC: 4878.75
TBC: 4878.70
TBC: 4878.12
TBC: 4878.68
DTBC: 4878.76
DTBC: 4878.32
DTBC: 4878.29
TBC: 4879.01
TBC: 4878.73
TBC: 4878.58
TBC: 4878.65
TBC: 4877.66
TBC: 4877.76
TBC: 4877.75
TBC: 4877.69
TBC: 4878.61
TBC: 4878.61
TBC: 4878.25
TBC: 4878.33
TBC: 4878.39
TBC: 4878.48
TBC: 4879.10
TBC: 4879.02
TBC: 4878.96
TBC: 4878.88
TBC: 4879.58
TBC: 4879.34
TBC: 4879.34
DTBC: 4878.32
DTBC: 4878.29
TBC: 4878.71
TBC: 4878.51
TBC: 4878.38
TBC: 4878.25
TBC: 4879.32
TBC: 4879.26
TBC: 4879.05
TBC: 4878.90
TBC: 4879.52
TBC: 4879.59
TBC: 4879.89
TBC: 4880.46
TBC: 4880.39
TBC: 4878.84
TBC: 4879.32
TBC: 4879.32
TBC: 4879.35
TBC: 4880.03
TBC: 4878.69
TBC: 4880.08
TBC: 4879.48
TBC: 4878.54
TBC: 4878.54
TBC: 4878.75
TBC: 4878.68
TBC: 4878.33
TBC: 4878.38
TBC: 4878.24
TBC: 4877.99TBC: 4877.52
TBC: 4877.58
TBC: 4878.30
TBC: 4878.23
TBC: 4878.08
TBC: 4877.80
TOA:4877.60
TOC: 4877.94
TOC: 4877.70
TOC: 4879.49
TOC: 4879.40
TOC: 4879.12
TOC: 4879.62
TOC: 4879.63
TOC: 4879.73
TOC: 4879.73
TOC: 4879.12
TOC: 4877.63
TOC: 4877.80
TOC: 4878.31
TOC: 4878.08
TOC: 4878.78
TOC: 4878.64
TOC: 4878.78
TOC: 4878.37
TOC: 4878.37
TOC: 4878.55
TOC: 4878.23
TOC: 4878.14
TOC: 4878.47
TOC: 4878.50
DTBC: 4878.47
DTBC: 4878.50
TOC: 4879.33
TOC: 4879.33
TOC: 4879.33
DTBC: 4878.39
TBC: 4879.59
TOC: 4879.09
TOC: 4879.24
TBC: 4879.19
TOA:4878.00
TOA:4878.11
TOA:4878.11
TOA:4877.49
TOA:4877.19
TOC: 4877.88
TOC: 4877.70
TOC: 4878.30
TOC: 4878.48
TOC: 4880.00
TOC: 4879.96
FG: 4879.32
FG: 4879.45
FG: 4879.63
FG: 4879.40
FG: 4879.40
FG: 4879.40
FG: 4879.40FG: 4879.40
FG: 4878.70
FFE: 4879.40
GRADE
BREAK
GR
A
D
E
BR
E
A
K
GR
A
D
E
BR
E
A
K
GRADE
BREAK
GR
A
D
E
BR
E
A
K
GRADE
BREAK
3.3%
2.
1
%
2.2
%
2
.
2
%
2
.
3
%
2.
7
%
0
.
5
%
1.7
%
1
.
9
%
1
.
0
%
2.1
%
1.6%
1.6%
5.2%
1.6%
0.8%0.6%
0.7%1.0%
1.0%
0.0%0.2%
1.
9
%
5.0%
3.6
%
3.4
%
4
8
7
6
48
7
5
4876
487
7
4
8
7
8
48
7
6
4877
4
8
7
8
4878
4878
4877
4876
4
8
7
8
4879
4
8
7
8
487
9 4879
4878
4878
TBC: 4879.96
TOC: 4878.93
TOC: 4879.05
GR
A
D
E
BR
E
A
K
2
.
0
%
1.2%
TBC: 4877.63
TOC: 4878.26
TOC: 4878.74
TOA:4879.00
TOC: 4878.10
TOC: 4878.10 TBC: 4878.85
TOC: 4878.74
TBC: 4878.73
TBC: 4879.00
TBC: 4877.68
TBC: 4877.68
TBC: 4878.09
TBC: 4878.09
TBC: 4878.09
TBC: 4878.09TBC: 4877.66
TBC: 4877.68
TBC: 4878.20
FG: 4876.24
FG: 4876.67
FG: 4876.67
FG: 4876.27
TBC: 4878.10
TBC: 4877.31
TBC: 4878.36
TBC: 4877.67
METBC: 4878.17
METBC: 4877.77
METOA: 4877.92
METOA: 4877.50
TOC: 4877.73
TOC: 4877.75
TBC: 4877.67
TBC: 4877.59TBC: 4877.74
TOC: 4877.65TOC: 4877.81
TBC: 4877.62
TOC: 4878.38
TOC: 4878.35
METOA: 4877.78
METOA: 4877.87
TOA:4877.71
TOA:4877.61
TOC: 4877.87
TOC: 4877.69
TBC: 4878.63
TBC: 4878.62
TOC: 4877.43
TOC: 4877.44
TOC: 4878.44
TOC: 4878.43
TOC: 4878.45
TOC: 4878.49
TBC: 4878.26
TOC: 4878.17
TOC: 4878.21
TOC: 4878.50
TOC: 4878.52
TBC: 4879.36
TBC: 4879.31
TOC: 4878.47
TOC: 4878.46
FG: 4876.25
FG: 4876.25
TBC: 4879.73
TBC: 4879.78
1 5
RE
V
I
S
I
O
N
S
RE
V
#
DA
T
E
DR
A
W
I
N
G
I
N
F
O
DA
T
E
DE
S
I
G
N
E
D
DR
A
W
N
*S
E
E
G
E
N
E
R
A
L
N
O
T
E
S
S
H
E
E
T
WA
R
N
I
N
G
0
1
2
IF
T
H
I
S
B
A
R
D
O
E
S
N
O
T
ME
A
S
U
R
E
2
"
T
H
E
N
DR
A
W
I
N
G
I
S
N
O
T
T
O
S
C
A
L
E
CI
T
Y
R
E
V
I
E
W
S
E
T
ww
w
.
h
o
r
r
o
c
k
s
.
c
o
m
PAGE
C
PR
O
J
E
C
T
CH
E
C
K
E
D
D
B
A
#
2 3 4
21
9
4
S
n
a
k
e
R
i
v
e
r
P
k
w
y
.
,
S
u
i
t
e
2
0
5
Id
a
h
o
F
a
l
l
s
,
I
D
8
3
4
0
2
(2
0
8
)
5
2
2
-
1
2
2
3
PRELIMINARY
NOT FOR
CONSTRUCTION
H
O R R O C
K
S
E
N
G I N E E R
S
0 30'60'
SCALE: 1" = 30'
N
ID
-
L
D
-
4
0
7
0
-
2
1
CJ
F
TL
M
JB
F
05
/
0
3
/
2
0
2
2
OV
E
R
A
L
L
G
R
A
D
I
N
G
P
L
A
N
RE
X
B
U
R
G
N
O
R
T
H
N
I
T
R
O
C
A
R
W
A
S
H
RE
X
B
U
R
G
,
I
D
A
H
O
9
C.4.0
LEGEND
TOA: TOP OF ASPHALT
METOA: MATCH EXISTING TOP OF ASPHALT
TBC: TOP BACK OF CURB
DTBC: DEPRESSED TOP BACK OF CURB
METBC: MATCH EXISTING TOP BACK CURB
TOC: TOP OF CONCRETE
METOC: MATCH EXISTING TOP OF CONCRETE
FFE: FINAL FLOOR ELEVATION
FG: FINISH GRADE
FL: FLOW LINE
TOP: TOP OF POND
BOP: BOTTOM OF POND
TOG: TOP OF GRATE
-CONTOURS SHOWN AT 1.0' AND 5.0' INTERVALS
-ALL ELEVATIONS ARE FG
SHEET NOTE
SHEET C.7.0
SH
E
E
T
C
.
7
.
1
PR
I
V
A
T
E
D
R
I
V
E
SH
E
E
T
C
.
7
.
2
MOODY STREET
NO
R
T
H
2
N
D
E
A
S
T
PROPOSED BUILDING
FFE = 4879.50'
ARCH PLAN = 100
05/04/22
PRE
L
I
M
I
N
A
R
Y
N
O
T
F
O
R
C
O
N
S
T
R
U
C
T
I
O
N
FOR
R
E
V
I
E
W
O
N
L
Y
PR
E
L
I
M
I
N
A
R
Y
N
O
T
F
O
R
CO
N
S
T
R
U
C
T
I
O
N
FO
R
R
E
V
I
E
W
O
N
L
Y
fl
fl
fl
fl
fl
fl
fl
fl
fl
toe toe toe toe toe toe toe toe
toetoetoetoetoetoetoetoetoe
toe
toetoetoe
eee
e
ee
pp
sd
sd
pp
to
b
to
b
t
o
b
to
b
t
o
b
tobtobtobtobtobtobtobtobtobtob
tob tob tob tob tob tob tob tob tob
tob
to
b
to
b
to
b
to
b
to
b
to
b
to
b
to
b
t
o
b
to
b
to
b
to
b
to
b
to
b
to
b
to
b
tob
to
b
14'' w 14'' w 14'' w 14'' w 14'' w
s
s
s
fl
fl
fl
fl
fl
fl
fl
fl
fl
toe toe toe toe toe toe toe toe
toetoetoetoetoetoetoetoetoe
toe
toetoetoe
eee
e
ee
pp
sd
sd
pp
to
b
to
b
t
o
b
to
b
t
o
b
tobtobtobtobtobtobtobtobtobtob
tob tob tob tob tob tob tob tob tob
tob
to
b
to
b
to
b
to
b
to
b
to
b
to
b
to
b
t
o
b
to
b
to
b
to
b
to
b
to
b
to
b
to
b
tob
to
b
14'' w 14'' w 14'' w 14'' w 14'' w
s
s
s
IR
R
IR
R
IR
R
IR
R
IR
R
IR
R
16'' W16'' W16'' W16'' W16'' W16'' W16'' W16'' W16'' W16'' W16'' W16'' W16'' W16'' W
SS
SD SD
SD
8'
'
W
8'
'
W
8'
'
W
8'
'
W
8'
'
W
8'
'
W
8'
'
W
8'
'
W
S s
S
s
sssssssssss
S
S
SSSSSSSS S
SS
SS
SSS
EX-SSMH - 1
100LF 4" WATER SERVICE
49LF 4" WATER SERVICE8LF 4" WATER SERVICE
4878
48
7
8
4
8
7
8
4878
4
8
7
8
4878
4878
48784878
4879
4879
STRUCTURE - (22)
RIM: 4868.10
INV: 4870.88 4" (N)
SSMH 2
RIM: 4879.00
INV IN: 4868.07 8" (S)
INV IN: 4868.50 6" (W)
INV OUT: 4867.97 8" (N)
INV OUT: 4867.97 4" (E)
REC TANK 2
RIM: 4878.24
INV IN: 4872.76 4" (W)
INV OUT: 4872.10 4" (E)
REC TANK 1
RIM: 4878.19
INV IN: 4872.76 8" (N)
INV OUT: 4872.76 4" (E)
SSMH 5
RIM: 4878.03
INV IN: 4858.00 12" (E)
INV IN: 4858.23 8" (S)
INV OUT: 4857.90 12" (W)
SS PLUG - 3
RIM: 4878.01
INV IN: 4873.49 6" (S)
SS PLUG - 2
RIM: 4877.35
INV OUT: 4873.49 8" (S)
SS PLUG - 1
RIM: 4877.04
INV OUT: 4873.49 4" (S)
INV: 4872.68 4" (E)SSMH 3
RIM: 4875.18
INV IN: 4872.00 4" (W)
SSMH 4
RIM: 4878.63
INV OUT: 4868.34 8" (N)
25LF OF 6" SS @ -1.20%
28LF OF 6" SS @ -6.00%
40LF OF 4" SS @ 2.00%
92LF OF 4" SS @ 1.95%
68LF OF 8" SS @ 0.40%
15
0
L
F
O
F
8
"
S
S
@
6
.
5
0
%
121LF OF 4" SS @ -3.34%
35LF OF 6" SS @ 4.18%
GI 1
RIM: 4878.49
INV IN: 4870.78 4" (W)
INV IN: 4870.78 4" (S)
INV OUT: 4869.95 6" (E)
10LF OF 4" SS @ 1.00%
REC TANK 3
RIM: 4878.32
INV IN: 4872.10 4" (W)
INV OUT: 4871.44 6" (N)
INV OUT: 4871.44 4" (E)
28LF OF 8" SS @ 2.58%
1 5
RE
V
I
S
I
O
N
S
RE
V
#
DA
T
E
DR
A
W
I
N
G
I
N
F
O
DA
T
E
DE
S
I
G
N
E
D
DR
A
W
N
*S
E
E
G
E
N
E
R
A
L
N
O
T
E
S
S
H
E
E
T
WA
R
N
I
N
G
0
1
2
IF
T
H
I
S
B
A
R
D
O
E
S
N
O
T
ME
A
S
U
R
E
2
"
T
H
E
N
DR
A
W
I
N
G
I
S
N
O
T
T
O
S
C
A
L
E
CI
T
Y
R
E
V
I
E
W
S
E
T
ww
w
.
h
o
r
r
o
c
k
s
.
c
o
m
PAGE
C
PR
O
J
E
C
T
CH
E
C
K
E
D
D
B
A
#
2 3 4
21
9
4
S
n
a
k
e
R
i
v
e
r
P
k
w
y
.
,
S
u
i
t
e
2
0
5
Id
a
h
o
F
a
l
l
s
,
I
D
8
3
4
0
2
(2
0
8
)
5
2
2
-
1
2
2
3
PRELIMINARY
NOT FOR
CONSTRUCTION
H
O R R O C
K
S
E
N
G I N E E R
S
0 30'60'
SCALE: 1" = 30'
N
ID
-
L
D
-
4
0
7
0
-
2
1
CJ
F
TL
M
JB
F
05
/
0
3
/
2
0
2
2
OV
E
R
A
L
L
U
T
I
L
I
T
Y
P
L
A
N
RE
X
B
U
R
G
N
O
R
T
H
N
I
T
R
O
C
A
R
W
A
S
H
RE
X
B
U
R
G
,
I
D
A
H
O
10
C.5.0
SHEET C.7.0
SH
E
E
T
C
.
7
.
2
SH
E
E
T
C
.
7
.
1
MOODY ST
NO
R
T
H
2
N
D
E
A
S
T
WATER KEYNOTES
TIE INTO EXISTING 8" WATER MAIN
INSTALL 8" DUCTILE IRON PIPE (PER CITY OF CITY OF REXBURG
STANDARD), LENGTH PER PLANS, MUST MAINTAIN 5' COVER
INSTALL FIRE HYDRANT PER ISPWC SD-404. FIRE HYDRANT TO MEET
CITY OF REXBURG STANDARDS.
INSTALL 6" X 8" TEE WITH GATE VALVE PER CITY OF REXBURG
STANDARDS.
INSTALL 4" WATER SERVICE STUB PER ISPWC SD-402. STUBS PER
CITY OF REXBURG STANDARD. INCLUDE PLUG, SEE ARCHITECTS
PLANS FOR CONTINUATION
INSTALL 8" PLUG
POTABLE & NON-POTABLE VERTICAL LINE CROSSING PER ISPWC
SD-407, MINIMUM 1.5' VERTICAL SEPARATION
INSTALL 8" X 8" TEE
INSTALL 8" GATE VALVE
INSTALL 16" X 4" TEE
36
37
38
39
40
41
42
43
44
45
SEWER KEYNOTES
INSTALL RECLAIM TANKS AND RECLAIM SYSTEM PER
ARCHITECTURAL PLANS
INSTALL 4" SANITARY SEWER SERVICE LINE (LENGTH PER PLANS),
INCLUDE PLUG, SEE ARCHITECTS PLANS FOR CONTINUATION
INSTALL 6" SANITARY SEWER SERVICE LINE (LENGTH PER PLANS),
INCLUDE PLUG, SEE ARCHITECTS PLANS FOR CONTINUATION
INSTALL 8" SANITARY SEWER SERVICE LINE (LENGTH PER PLANS),
INCLUDE PLUG, SEE ARCHITECTS PLANS FOR CONTINUATION
INSTALL SEWER CLEANOUT WITH TRAFFIC RATED LID PER ISPWC
SD-506
INSTALL SANITARY SEWER MAIN LINE (SIZE, LENGTH, AND SLOPE
PER PLANS)
INSTALL 1500 GALLON GREASE INTERCEPTOR PER ARCHITECTURAL
PLANS
INSTALL SANITARY SEWER MANHOLE PER ISPWC SD-501A, SIZE PER
PLAN
51
52
53
54
55
56
57
58
40
51
51
52
52
54
52
56
56
56
56
57
52 58 58
58
58
TIE INTO EXISTING SS MANHOLE
CONTRACTOR TO FIELD VERIFY LOCATION
45
42
42
53
40 LF
52 LF
28 LF
05/04/22
PRE
L
I
M
I
N
A
R
Y
N
O
T
F
O
R
C
O
N
S
T
R
U
C
T
I
O
N
FOR
R
E
V
I
E
W
O
N
L
Y
PR
E
L
I
M
I
N
A
R
Y
N
O
T
F
O
R
CO
N
S
T
R
U
C
T
I
O
N
FO
R
R
E
V
I
E
W
O
N
L
Y
fl
fl
fl
fl
fl
fl
fl
fl
fl
toe toe toe toe toe toe toe toe
toetoetoetoetoetoetoetoetoe
toe
toetoetoe
eee
eee
pp
sd
sd
pp
tob
to
b
14'' w 14'' w 14'' w
s
4876
4878
4878
4877
4
8
7
5
48
7
7
48
7
8
48
7
6
48
7
6
48
7
7
48
7
7
fl
fl
fl
fl
fl
fl
fl
fl
fl
toe toe toe toe toe toe toe toe
toetoetoetoetoetoetoetoetoe
toe
toetoetoe
eee
eee
pp
sd
sd
pp
tob
to
b
14'' w 14'' w 14'' w
s
IR
R
IR
R
IR
R
IR
R
IR
R
IR
R
16'' W16'' W16'' W16'' W16'' W16'' W16'' W16'' W16'' W16'' W16'' W16'' W16'' W16'' W
SS
IR
IR
IR
IR
SD SD
SD
8'
'
W
8'
'
W
8'
'
W
8'
'
W
8'
'
W
8'
'
W
8'
'
W
8'
'
W
S s
S
IR
ssssssss
S
S
SSSSSSSS S
SS
SS
SSS
EX-SSMH - 1
48'
10
'
58.5'
5'
10'
10
'
92LF OF 12" S.D. @ 0.50%82LF OF 12" S.D. @ 0.40%
5LF OF 12" S.D. @ 1.00%
60LF OF 12" S.D. @ 0.00%
SD INLET - E
RIM: 4879.04
INV IN: 4875.59 6" (NW)
INV IN: 4875.11 6" (N)
RD PLUG - B
RIM: 4877.30
INV OUT: 4876.28 6" (S)
SD INLET - D
RIM: 4876.82
INV IN: 4872.55 6" (N)
INV OUT: 4870.00 24" (E)
RD PLUG - A
INV OUT: 4876.29 6" (S)
SD CO - B
RIM: 4877.24
INV IN: 4876.22 6" (N)
INV OUT: 4876.22 6" (W)
RD PLUG - C
RIM: 4879.31
INV OUT: 4876.12 6" (SE)
6LF OF 6" S.D. @ 1.00%
7LF OF 6" S.D. @ 6.13%
48LF OF 6" S.D. @ 1.04%
49LF OF 6" S.D. @ 6.27%
17LF OF 6" S.D. @ 3.18%
SDMH - A
RIM: 4878.40
INV IN: 4873.06 12" (N)
INV OUT: 4872.96 12" (W)
SD INLET - A
RIM: 4877.35
INV OUT: 4874.10 12" (E)
SD INLET - C
RIM: 4877.79
INV IN: 4873.21 12" (W)
INV OUT: 4873.11 12" (S)
SD INLET - B
RIM: 4877.61
INV IN: 4873.64 12" (W)
INV OUT: 4873.54 12" (E)
3LF OF 24" S.D. @ 1.00%
SD CO - A
RIM: 4876.89
INV IN: 4875.87 6" (N)
INV IN: 4875.72 6" (E)
INV OUT: 4875.62 6" (S)
27LF OF 6" S.D. @ 1.00%
SD CO - C
RIM: 4879.11
INV IN: 4875.38 6" (NW)
INV OUT: 4875.38 6" (S)
31LF OF 6" S.D. @ 1.00%
SD PLUG - D
RIM: 4878.69
INV OUT: 4875.69 6" (SE)
1 5
RE
V
I
S
I
O
N
S
RE
V
#
DA
T
E
DR
A
W
I
N
G
I
N
F
O
DA
T
E
DE
S
I
G
N
E
D
DR
A
W
N
*S
E
E
G
E
N
E
R
A
L
N
O
T
E
S
S
H
E
E
T
WA
R
N
I
N
G
0
1
2
IF
T
H
I
S
B
A
R
D
O
E
S
N
O
T
ME
A
S
U
R
E
2
"
T
H
E
N
DR
A
W
I
N
G
I
S
N
O
T
T
O
S
C
A
L
E
CI
T
Y
R
E
V
I
E
W
S
E
T
ww
w
.
h
o
r
r
o
c
k
s
.
c
o
m
PAGE
C
PR
O
J
E
C
T
CH
E
C
K
E
D
D
B
A
#
2 3 4
21
9
4
S
n
a
k
e
R
i
v
e
r
P
k
w
y
.
,
S
u
i
t
e
2
0
5
Id
a
h
o
F
a
l
l
s
,
I
D
8
3
4
0
2
(2
0
8
)
5
2
2
-
1
2
2
3
PRELIMINARY
NOT FOR
CONSTRUCTION
DRAINAGE SYSTEM CALCULATIONS
SYSTEM REQUIREMENTS:
DRAINAGE AREA OF "REXBURG NORTH NITRO CARWASH": 46,688 SF
RIGHT OF WAY: 1,217 CF
NORTH BASIN: 221 CF
SOUTH BASIN:2,630 CF
DESIGN STORM:1.3 IN
SEDIMENT FACTOR:15 %
STORM VOLUME REQUIRED:4,068 CF
SUMMARY:
STORAGE SYSTEM:STORM POND & INFILTRATOR
STORAGE PROVIDED
RIGHT OF WAY: 1,398 CF
NORTH BASIN:
NORTH STORM SWALE
CONTRIBUTIONS:342 CF
SOUTH BASIN:
SOUTH STORM SWALE
CONTRIBUTIONS:1,119 CF
INFILTRATOR
CONTRIBUTIONS: 1,658 CF
PROVIDED STORAGE:4,517 CF
-----------------------------------------------------------------------------------------------------------------------------------------------
TOTAL STORAGE REQUIRED:4,068 CF
TOTAL STORAGE PROVIDED:4,517 CF
H
O R R O C
K
S
E
N
G I N E E R
S
0 30'60'
SCALE: 1" = 30'
N
ID
-
L
D
-
4
0
7
0
-
2
1
CJ
F
TL
M
JB
F
05
/
0
3
/
2
0
2
2
OV
E
R
A
L
L
D
R
A
I
N
A
G
E
P
L
A
N
RE
X
B
U
R
G
N
O
R
T
H
N
I
T
R
O
C
A
R
W
A
S
H
RE
X
B
U
R
G
,
I
D
A
H
O
11
C.6.0
STORM DRAIN KEYNOTES
INSTALL STORM DRAIN PIPE. LENGTH, SIZE AND SLOPE OF PIPE PER
PLANS
INSTALL STORM DRAIN CURB CATCH BASIN PER STD IF-604-A (2010)
INSTALL MARK AND PLUG FOR ROOF DRAIN & BUILDING
CONNECTIONS PER DETAIL 1
INSTALL UNDERGROUND INFILTRATOR, SEE DETAIL 2
INSTALL STORM DRAIN CLEAN OUT
66
67
68
69
70
MOODY ST
NO
R
T
H
2
N
D
E
A
S
T
66
66
67
67
67
67
67
6666
68
6868
69
69
69
TYPICAL ROOF DRAIN CONNECTION DETAIL
NTS
1
C.6.0
6" S.D. (P.V.C. SDR 35)
1% MIN. TO ROOF
D
R
A
I
N
H
E
A
D
E
R
5'
1.
5
'
C
O
V
E
R
M
I
N
.
(SEE STORM DRAIN P
L
A
N
S
)
FINISH GRADE
END ROOF DRAIN PIPE 5' FROM BUILDING
SEE ARCHITECTURAL PLANS FOR
CONTINUATION & CONNECTION
EXCAVATE TO FREE DRAINING
SAND AND GRAVEL PER PROJECT
GEOTECHNICAL REPORT. CONSULT
GEOTECHNICAL
ENGINEER (TYP)
3/4" TO 2"WASHED
GRANITE STONE
BA
C
K
F
I
L
L
UNDISTURBED MATERIAL
WRAP TRENCHES TOP
AND SIDES WITH AMOCO
4545 OR EQUIVALENT
SCALE:
2
C.6.0
TYPICAL INFILTRATION TRENCH DETAIL
NTS
10'
8'
MIN 12" COVER IN LANDSCAPING
70
70
7068
66
05/04/22
PRE
L
I
M
I
N
A
R
Y
N
O
T
F
O
R
C
O
N
S
T
R
U
C
T
I
O
N
FOR
R
E
V
I
E
W
O
N
L
Y
PR
E
L
I
M
I
N
A
R
Y
N
O
T
F
O
R
CO
N
S
T
R
U
C
T
I
O
N
FO
R
R
E
V
I
E
W
O
N
L
Y
fl
toetoetoetoetoetoetoetoetoe
toe
toetoetoe
tob
to
b
14'' w 14'' w 14'' w 14'' w 14'' w
s
s
s
IR
R
IR
R
fl
toetoetoetoetoetoetoetoetoe
toe
toetoetoe
tob
to
b
14'' w 14'' w 14'' w 14'' w 14'' w
s
s
s
16'' W16'' W16'' W16'' W16'' W16'' W16'' W16'' W16'' W16'' W16'' W16'' W16'' W16'' W
0+44 1+00 2+00 3+00 4+00
4+
5
4
BP
:
0
+
4
4
.
1
1
PC
:
4
+
0
2
.
2
0
EP: 4+53.53
SD SD
SD
8'
'
W
8'
'
W
8'
'
W
8'
'
W
S s
S
s
sssssssssssSSSSSSSSS
SS
SS
48
7
8
4876
4878
4877
4878
4878
TBC: 4879.09
TOC: 4878.68
TOC: 4878.68
TOC: 4878.55
TOC: 4879.01
TOC: 4879.10
TOC: 4879.04
TOC: 4878.34
TOC: 4878.73
TOC: 4878.79
TOC: 4878.98
TOC: 4879.02
TBC: 4878.74
DTBC: 4878.77
DTBC: 4878.83
TBC: 4878.90
DTBC: 4878.96
DTBC: 4879.02
METOA:4878.30
TOG: 4877.62
TOG: 4877.80
TOG: 4877.37
TBC: 4878.00
TBC: 4877.78
TOA:4877.38
4878
4
8
7
8
4879
4878 SDMH - A
RIM: 4878.40
INV IN: 4873.06 12" (N)
INV OUT: 4872.96 12" (W)
SD INLET - C
RIM: 4877.79
INV IN: 4873.21 12" (W)
INV OUT: 4873.11 12" (S)
SD INLET - B
RIM: 4877.61
INV IN: 4873.64 12" (W)
INV OUT: 4873.54 12" (E)
SD INLET - A
RIM: 4877.35
INV OUT: 4874.10 12" (E)
92LF OF 12" S.D. @ 0.50%
82LF OF 12" S.D. @ 0.40%
5LF OF 12" S.D. @ 1.00%
60LF OF 12" S.D. @ 0.00%
58.5'
5'
2.
1
%
2.1
%
2.1
%
0.7%0.9%0.3%0.5%
METOA:4877.77
EX-SSMH - 1
SSMH 6
12" S.S.
30LF OF 8" SS @ 0.40%
SSMH - 4
RIM: 4870.15
INV OUT: 4857.61 8" (S)
12" S.S.
SS PLUG - 6
12" S.S.
SSMH 5
El
e
v
a
t
i
o
n
4840
4850
4860
4870
4880
4890
4840
4850
4860
4870
4880
4890
0+00 1+00 2+00 3+00 4+00 5+00 6+00
1+00
48
7
8
.
0
4
48
7
8
.
1
7
2+00
48
7
8
.
2
2
48
7
8
.
2
9
3+00
48
7
8
.
6
2
48
7
8
.
3
3
4+00
48
7
9
.
0
4
48
7
9
.
1
0
5+00
ST
A
:
4
+
4
0
.
8
1
(
-
1
7
9
.
5
2
,
L
)
EX
S
S
M
H
RI
M
:
4
8
7
7
.
4
1
IN
V
I
N
:
4
8
5
9
.
0
7
-
8
"
(
N
)
IN
V
O
U
T
:
4
8
5
8
.
9
7
-
8
"
(
W
)
ST
A
:
4
+
3
7
.
6
8
(
-
1
8
9
.
2
6
,
L
)
EX
L
I
F
T
S
T
A
T
I
O
N
RI
M
:
4
8
7
8
.
0
0
IN
V
O
U
T
:
4
8
5
9
.
0
0
-
8
"
(
S
)
ST
A
:
4
+
1
9
.
3
4
(
-
6
0
.
2
2
,
L
)
EX
-
S
S
M
H
-
1
RI
M
:
4
8
7
8
.
6
6
IN
V
I
N
:
4
8
5
8
.
4
9
-
8
"
(
E
)
IN
V
O
U
T
:
4
8
5
8
.
1
6
-
1
2
"
(
W
)
EX. 8" S.S.
70.53' of 12" @ 0.22%
20.66' of 12" @ 0.22%
ST
A
:
0
+
8
8
.
0
2
(
-
4
9
.
8
4
,
L
)
SS
M
H
6
RI
M
:
4
8
7
7
.
1
4
IN
V
I
N
:
4
8
5
7
.
4
9
-
8
"
(
N
)
IN
V
I
N
:
4
8
5
7
.
2
6
-
1
2
"
(
E
)
IN
V
O
U
T
:
4
8
5
7
.
1
6
-
1
2
"
(
W
)
ST
A
:
0
+
1
9
.
6
8
(
-
5
.
3
3
,
L
)
SS
M
H
-
4
RI
M
:
4
8
7
0
.
1
5
IN
V
O
U
T
:
4
8
5
7
.
6
1
-
8
"
(
S
)
IR
R
.
M
H
-
D
RI
M
:
4
8
7
9
.
8
1
IN
V
I
N
:
4
8
7
0
.
9
7
-
4
8
"
(
S
)
IN
V
O
U
T
:
4
8
7
3
.
7
5
-
3
6
"
(
N
)
IR
R
.
M
H
-
E
RI
M
:
4
8
7
7
.
9
2
IN
V
I
N
:
4
8
7
3
.
7
5
-
3
6
"
(
S
)
104.71 of 48" EQUIVALENT SQUASH PIPE @ 0.00%
ST
A
=
0
+
4
9
.
8
4
T.
O
.
W
.
=
4
8
7
2
.
0
2
STA = 3+30.99
T.O.W. = 4871.72
STA = 4+28.93
T.O.W. = 4872.31
STA = 4+32.86
T.O.W. = 4872.30
ST
A
:
3
+
5
5
.
2
9
4"
W
A
T
E
R
S
E
R
V
I
C
E
(
R
T
)
ST
A
:
1
+
8
0
.
0
5
16
"
x
6
"
W
A
T
E
R
T
E
E
ST
A
:
1
+
9
1
.
3
2
16
"
B
U
T
T
E
R
F
L
Y
V
A
L
V
E
ST
A
:
0
+
5
8
.
3
2
16
"
x
8
"
W
A
T
E
R
T
E
E
ST
A
:
4
+
3
1
.
2
8
16
"
C
O
N
N
E
C
T
I
O
N
T
O
E
X
.
M
A
I
N
ST
A
:
0
+
4
9
.
8
4
16
"
P
L
U
G
EX 14" DI WATER PIPE281LF OF 16" DI WATER PIPE
98LF OF 16" DI WATER PIPE
14" to 16" REDUCER
SD
I
N
L
E
T
-
A
RI
M
:
4
8
7
7
.
3
5
IN
V
O
U
T
:
4
8
7
4
.
1
0
-
1
2
"
(
E
)
91.88' of 12" RCP @ 0.50%
SD
I
N
L
E
T
-
B
RI
M
:
4
8
7
7
.
6
1
IN
V
I
N
:
4
8
7
3
.
6
4
-
1
2
"
(
W
)
IN
V
O
U
T
:
4
8
7
3
.
5
4
-
1
2
"
(
E
)
81.71' of 12" RCP @ 0.40%
SD
I
N
L
E
T
-
C
RI
M
:
4
8
7
7
.
7
9
IN
V
I
N
:
4
8
7
3
.
2
1
-
1
2
"
(
W
)
IN
V
O
U
T
:
4
8
7
3
.
1
1
-
1
2
"
(
S
)
1 5
RE
V
I
S
I
O
N
S
RE
V
#
DA
T
E
DR
A
W
I
N
G
I
N
F
O
DA
T
E
DE
S
I
G
N
E
D
DR
A
W
N
*S
E
E
G
E
N
E
R
A
L
N
O
T
E
S
S
H
E
E
T
WA
R
N
I
N
G
0
1
2
IF
T
H
I
S
B
A
R
D
O
E
S
N
O
T
ME
A
S
U
R
E
2
"
T
H
E
N
DR
A
W
I
N
G
I
S
N
O
T
T
O
S
C
A
L
E
CI
T
Y
R
E
V
I
E
W
S
E
T
ww
w
.
h
o
r
r
o
c
k
s
.
c
o
m
PAGE
C
PR
O
J
E
C
T
CH
E
C
K
E
D
D
B
A
#
2 3 4
21
9
4
S
n
a
k
e
R
i
v
e
r
P
k
w
y
.
,
S
u
i
t
e
2
0
5
Id
a
h
o
F
a
l
l
s
,
I
D
8
3
4
0
2
(2
0
8
)
5
2
2
-
1
2
2
3
PRELIMINARY
NOT FOR
CONSTRUCTION
C.3.2
1
H
O R R O C
K
S
E
N
G I N E E R
S
0 30'60'
SCALE: 1" = 30'
N
ID
-
L
D
-
4
0
7
0
-
2
1
CJ
F
TL
M
JB
F
05
/
0
3
/
2
0
2
2
PL
A
N
&
P
R
O
F
I
L
E
-
M
O
O
D
Y
S
T
R
E
E
T
RE
X
B
U
R
G
N
O
R
T
H
N
I
T
R
O
C
A
R
W
A
S
H
RE
X
B
U
R
G
,
I
D
A
H
O
12
C.7.0
MOODY STREET
SHEET C.7.1
MOODY STREET
NO
R
T
H
2
N
D
E
A
S
T
01 HD
02
02
03
03
03
04
04
05
06
06
07
PROPOSED SURFACE
EXISTING SURFACE
A
66
6666
6767
68
69
6' MINIMUM
47
47
38
41
SHEET C.7.2
38
48
50
34
WATER KEYNOTES
INSTALL 16" PLUG
INSTALL 16" X 4" TEE
INSTALL 16" TO 14" REDUCER
TIE INTO EXISTING 8" WATER MAIN
INSTALL 8" DUCTILE IRON PIPE (PER CITY OF CITY OF REXBURG
STANDARD), LENGTH PER PLANS, MUST MAINTAIN 5' COVER
INSTALL FIRE HYDRANT PER ISPWC SD-404. FIRE HYDRANT TO MEET
CITY OF REXBURG STANDARDS.
INSTALL 6" X 8" TEE WITH GATE VALVE PER CITY OF REXBURG
STANDARDS.
INSTALL 4" WATER SERVICE
INSTALL 2" WATER SERVICE STUB PER ISPWC SD-402. STUBS PER
CITY OF REXBURG STANDARD.
INSTALL 8" PLUG
POTABLE & NON-POTABLE VERTICAL LINE CROSSING PER ISPWC
SD-407, MINIMUM 1.5' VERTICAL SEPARATION
INSTALL 8" X 8" TEE
INSTALL 8" GATE VALVE
INSTALL 6" FIRE CONNECTION. WATER SERVICE TO HAVE A MINIMUM
1.5' VERTICAL SEPARATION TO ANY NON-POTABLE UTILITY LINE
INSTALL 16" DUCTILE IRON PIPE (PER CITY OF CITY OF REXBURG
STANDARD), LENGTH PER PLANS, MUST MAINTAIN 5' COVER
INSTALL 16" X 6" TEE
INSTALL 16" X 8" TEE
INSTALL 16" VALVE
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
LEGEND
METOA: MATCH EXISTING TOP OF ASPHALT
TBC: TOP BACK OF CURB
DTBC: DEPRESSED TOP BACK OF CURB
METBC: MATCH EXISTING TOP BACK CURB
TOC: TOP OF CONCRETE
METOC: MATCH EXISTING TOP OF CONCRETE
TOG: TOP OF GRATE
1.DRIVE AISLE DIMENSIONS MEASURED TO FACE OF CURB, WHERE
CURB IS PROPOSED OR TO EDGE OF PAVEMENT OTHERWISE.
2. CONTOURS SHOWN AT 1.0' AND 5.0' INTERVALS
3. ALL ELEVATIONS ARE FG
4. ALL DIMENSIONS PERTAINING TO PLAN AND PROFILE SHEETS C.7.0,
C.7.1, C.7.2, & C.7.3 ARE SHOWN ON SHEET C.3.0
SHEET NOTE
MISCELLANEOUS KEYNOTES
PARKING LOT LIGHT POLE PER ELECTRICAL PLANSA
STORM DRAIN KEYNOTES
INSTALL STORM DRAIN CATCH BASIN PER ISPWC SD-601 TYPE 1.
GRATE TO BE NEENAH MODEL NUMBER R-3067 OR APPROVED
EQUAL
INSTALL STORM DRAIN PIPE, SIZE AND LENGTH PER PLAN
INSTALL INFILTRATOR DRAIN PER REXBURG SD-16. TO INCLUDE
MANHOLE, CHAMBERS, AND DRAIN ROCK MATERIALS. SEE
DRAINAGE CALCULATIONS TABLE, AND DETAIL 1 SHEET C.6.0
INSTALL UNDERGROUND INFILTRATOR, SEE DETAIL 2, SHEET C.6.0
66
67
68
69
IRRIGATION KEYNOTES
INSTALL 72" IRRIGATION CONCRETE STRUCTURE
INSTALL 48" CULVERT (CONCRETE OR METAL)
TIE INTO EXISTING CULVERT
81
82
83
SITE PLAN KEYNOTES
INSTALL HEAVY DUTY ASPHALT (SEE FLEXIBLE PAVEMENT SECTION
SUMMARY TABLE SHEET C.3.2)
INSTALL 2.5' CURB & GUTTER PER CITY OF REXBURG SD-3
TIE INTO EXISTING ASPHALT, SAWCUT AS REQUIRED
INSTALL 4" THICK SIDEWALK, (WIDTH PER PLAN) PER ISPWC SD-709, 714,
714A, 714B UNLESS OTHERWISE NOTED
INSTALL ADA RAMP WITH TRUNCATED DOMES PER CITY OF REXBURG SD
INSTALL LANDSCAPE PER LANDSCAPE PLAN
INSTALL STOP SIGN PER MUTCD STANDARDS
INSTALL LIGHT DUTY ASPHALT (SEE FLEXIBLE PAVEMENT SECTION
SUMMARY TABLE SHEET C.3.2)
01
02
03
04
05
06
07
08
SHEET C.3.1, C.4.0, C.5.0, C.6.0
SEWER KEYNOTES
TIE INTO EXISTING SANITARY SEWER MANHOLE
INSTALL 8" SANITARY SEWER MAIN LINE (LENGTH PER PLANS)
INSTALL SANITARY SEWER MANHOLE PER ISPWC- SD-501A
INSTALL CAP AND MARK (TO SURFACE) SEE ARCHITECTS PLANS
FOR CONTINUATION
INSTALL 12" SANITARY SEWER MAIN LINE (LENGTH PER PLANS)
51
52
53
54
55
5251
43
555354
47
49
35
33
EXISTING LIFT
STATION
37
43 43
43
53
53 55
52
55
05/04/22
PRE
L
I
M
I
N
A
R
Y
N
O
T
F
O
R
C
O
N
S
T
R
U
C
T
I
O
N
FOR
R
E
V
I
E
W
O
N
L
Y
PR
E
L
I
M
I
N
A
R
Y
N
O
T
F
O
R
CO
N
S
T
R
U
C
T
I
O
N
FO
R
R
E
V
I
E
W
O
N
L
Y
fl fl fl fl fl fl fl fl fl
sd
sd
14
'
'
w
14
'
'
w
s
IRRIRRIRRIRRIRRIRR
fl fl fl fl fl fl fl fl fl
sd
sd
14
'
'
w
14
'
'
w
s
16
'
'
W
16
'
'
W
16
'
'
W
7+
0
0
7+
3
2
IR
IR IR IR
0+00
1+002+003+004+00
4+83
BP
:
0
+
0
0
.
0
0
PI
:
0
+
2
1
.
2
2
PI
:
1
+
0
9
.
4
2
PI
:
2
+
4
2
.
2
2
PI
:
4
+
2
2
.
5
8
E
P
:
4
+
8
3
.
0
5
s
IR
EP: 7+32.07
ss
ss
S S SSSSS
S
SS
EX-SSMH - 1
2.1
%
48
7
9
1
.
6
%
2
.
9
%
1.
7
%
TBC: 4878.61
TBC: 4879.10
TOC: 4878.68
TOC: 4878.68
TOC: 4878.55
TOC: 4879.01
TOC: 4879.10
TOC: 4879.04
TOC: 4878.34
TOC: 4878.73
TOC: 4878.79
TOC: 4878.98
TOC: 4879.02
TBC: 4878.74
DTBC: 4878.77
DTBC: 4878.83
TBC: 4878.90
DTBC: 4879.02
DTBC: 4878.10
DTBC: 4877.75
METBC:4878.14
DTBC: 4878.36
TBC: 4878.33
DTBC: 4877.73
TBC: 4878.26
METBC:4877.77
TBC: 4878.01
TBC: 4878.08
TBC: 4877.63
METOA:4877.86
METOA:4877.93
METOA:4877.41
METOA:4877.50
4
8
7
7
4878
4878 4878
4
8
7
8
4
8
7
7
48
7
7
METOA:4877.41
32LF OF 48" S.D. @ 0.59
%
DTBC: 4877.31
DTBC: 4877.66
IRR. MH - E
RIM: 4877.92
INV IN: 4873.75 36" (S)
105LF OF 36" S.D. @ 0.00%
IRR. MH - D
RIM: 4879.81
INV IN: 4870.97 48" (S)
INV OUT: 4873.75 36" (N)
144LF OF 48" S.D. @ 0.00%
IRR. MH - C
RIM: 4878.96
INV IN: 4870.97 48" (S)
INV OUT: 4870.97 48" (N)
140LF OF 48" S.D. @ 0.00%
IRR. MH - B
RIM: 4878.31
INV IN: 4870.97 48" (SE)
INV OUT: 4870.97 48" (N)
36LF OF 48" S.D. @ 7.41%
IRR. MH - A
RIM: 4878.54
INV IN: 4873.62 48" (S)
INV OUT: 4873.62 48" (NW)
0+001+002+003+004+005+00
0+00
48
7
6
.
0
0
1+00
48
7
4
.
4
7
48
7
8
.
8
4
2+00
48
7
4
.
8
7
48
7
8
.
5
1
3+00
48
7
4
.
4
6
48
7
8
.
3
3
4+00
48
7
4
.
1
5
48
7
7
.
9
7
5+00
144LF OF 48" CONCRETE @ 0.00%
105LF OF 48" EQUIVALENT SQUASHED PIPE @ 0.00%
IR
R
.
M
H
-
D
RI
M
:
4
8
7
9
.
8
1
IN
V
I
N
:
4
8
7
0
.
9
7
-
4
8
"
(
S
)
IN
V
O
U
T
:
4
8
7
3
.
7
5
-
3
6
"
(
N
)
IR
R
.
M
H
-
E
RI
M
:
4
8
7
7
.
9
2
IN
V
I
N
:
4
8
7
3
.
7
5
-
3
6
"
(
S
)
IR
R
.
M
H
-
C
RI
M
:
4
8
7
8
.
9
6
IN
V
I
N
:
4
8
7
0
.
9
7
-
4
8
"
(
S
)
IN
V
O
U
T
:
4
8
7
0
.
9
7
-
4
8
"
(
N
)
IR
R
.
M
H
-
A
RI
M
:
4
8
7
8
.
5
4
IN
V
O
U
T
:
4
8
7
3
.
6
2
-
4
8
"
(
S
)
IN
V
I
N
:
4
8
7
3
.
6
2
-
4
8
"
(
N
W
)
36LF OF 48" CONCRETE @ 7.41%
140LF OF 48" CONCRETE @ 0.00%140LF OF 48" CONCRETE @ 0.00%EX. 48" CULVERT
ST
A
:
2
+
2
7
.
7
3
(
5
4
.
2
4
,
R
)
SS
M
H
4
RI
M
:
4
8
7
8
.
6
3
IN
V
O
U
T
:
4
8
6
8
.
3
4
-
8
"
(
N
)
68.33' of 8" S.S. @ 0.40%
ST
A
:
1
+
5
9
.
4
0
(
5
4
.
1
3
,
R
)
SS
M
H
2
RI
M
:
4
8
7
9
.
0
0
IN
V
I
N
:
4
8
6
8
.
0
7
-
8
"
(
S
)
IN
V
I
N
:
4
8
6
8
.
5
0
-
6
"
(
W
)
IN
V
O
U
T
:
4
8
6
7
.
9
7
-
8
"
(
N
)
IN
V
O
U
T
:
4
8
6
7
.
9
7
-
4
"
(
E
)
149.
7
6
'
o
f
8
"
S
.
S
.
@
6
.
5
0
%
ST
A
:
0
+
8
9
.
7
7
(
9
8
.
5
2
,
R
)
SS
M
H
5
RI
M
:
4
8
7
8
.
0
3
IN
V
I
N
:
4
8
5
8
.
0
0
-
1
2
"
(
E
)
IN
V
I
N
:
4
8
5
8
.
2
3
-
8
"
(
S
)
IN
V
O
U
T
:
4
8
5
7
.
9
0
-
1
2
"
(
W
)
4850
4860
4870
4880
4890
4900
6+00
4850
4860
4870
4880
4890
4900
-1+00
1 5
RE
V
I
S
I
O
N
S
RE
V
#
DA
T
E
DR
A
W
I
N
G
I
N
F
O
DA
T
E
DE
S
I
G
N
E
D
DR
A
W
N
*S
E
E
G
E
N
E
R
A
L
N
O
T
E
S
S
H
E
E
T
WA
R
N
I
N
G
0
1
2
IF
T
H
I
S
B
A
R
D
O
E
S
N
O
T
ME
A
S
U
R
E
2
"
T
H
E
N
DR
A
W
I
N
G
I
S
N
O
T
T
O
S
C
A
L
E
CI
T
Y
R
E
V
I
E
W
S
E
T
ww
w
.
h
o
r
r
o
c
k
s
.
c
o
m
PAGE
C
PR
O
J
E
C
T
CH
E
C
K
E
D
D
B
A
#
2 3 4
21
9
4
S
n
a
k
e
R
i
v
e
r
P
k
w
y
.
,
S
u
i
t
e
2
0
5
Id
a
h
o
F
a
l
l
s
,
I
D
8
3
4
0
2
(2
0
8
)
5
2
2
-
1
2
2
3
PRELIMINARY
NOT FOR
CONSTRUCTION
H
O R R O C
K
S
E
N
G I N E E R
S
0 30'60'
SCALE: 1" = 30'
N
ID
-
L
D
-
4
0
7
0
-
2
1
CJ
F
TL
M
JB
F
05
/
0
3
/
2
0
2
2
PL
A
N
&
P
R
O
F
I
L
E
-
N
O
R
T
H
2
N
D
E
A
S
T
RE
X
B
U
R
G
N
O
R
T
H
N
I
T
R
O
C
A
R
W
A
S
H
RE
X
B
U
R
G
,
I
D
A
H
O
13
C.7.1
NORTH 2ND EAST
SHEET C.7.0
MO
O
D
Y
S
T
R
E
E
T
NORTH 2ND EAST
01HD02
02
03
04
06 05
PROPOSED SURFACE EXISTING SURFACE
A
A
C.3.2
2
SHEET C.3.1, C.4.0, C.5.0, C.6.0
05
EL
E
V
A
T
I
O
N
01HD
96" CIRCULAR STRUCTURE
96" CIRCULAR
STRUCTURE
WATER KEYNOTES
INSTALL 16" PLUG
INSTALL 16" X 4" TEE
INSTALL 16" TO 14" REDUCER
TIE INTO EXISTING 8" WATER MAIN
INSTALL 8" DUCTILE IRON PIPE (PER CITY OF CITY OF REXBURG
STANDARD), LENGTH PER PLANS, MUST MAINTAIN 5' COVER
INSTALL FIRE HYDRANT PER ISPWC SD-404. FIRE HYDRANT TO MEET
CITY OF REXBURG STANDARDS.
INSTALL 6" X 8" TEE WITH GATE VALVE PER CITY OF REXBURG
STANDARDS.
INSTALL 4" WATER SERVICE
INSTALL 2" WATER SERVICE STUB PER ISPWC SD-402. STUBS PER
CITY OF REXBURG STANDARD.
INSTALL 8" PLUG
POTABLE & NON-POTABLE VERTICAL LINE CROSSING PER ISPWC
SD-407, MINIMUM 1.5' VERTICAL SEPARATION
INSTALL 8" X 8" TEE
INSTALL 8" GATE VALVE
INSTALL 6" FIRE CONNECTION. WATER SERVICE TO HAVE A MINIMUM
1.5' VERTICAL SEPARATION TO ANY NON-POTABLE UTILITY LINE
INSTALL 16" DUCTILE IRON PIPE (PER CITY OF CITY OF REXBURG
STANDARD), LENGTH PER PLANS, MUST MAINTAIN 5' COVER
INSTALL 16" X 6" TEE
INSTALL 16" X 8" TEE
INSTALL 16" VALVE
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
LEGEND
METOA: MATCH EXISTING TOP OF ASPHALT
TBC: TOP BACK OF CURB
DTBC: DEPRESSED TOP BACK OF CURB
METBC: MATCH EXISTING TOP BACK CURB
TOC: TOP OF CONCRETE
METOC: MATCH EXISTING TOP OF CONCRETE
TOG: TOP OF GRATE
1.DRIVE AISLE DIMENSIONS MEASURED TO FACE OF CURB, WHERE
CURB IS PROPOSED OR TO EDGE OF PAVEMENT OTHERWISE.
2. CONTOURS SHOWN AT 1.0' AND 5.0' INTERVALS
3. ALL ELEVATIONS ARE FG
4. ALL DIMENSIONS PERTAINING TO PLAN AND PROFILE SHEETS C.7.0,
C.7.1, C.7.2, & C.7.3 ARE SHOWN ON SHEET C.3.0
SHEET NOTE
MISCELLANEOUS KEYNOTES
PARKING LOT LIGHT POLE PER ELECTRICAL PLANSA
STORM DRAIN KEYNOTES
INSTALL STORM DRAIN CATCH BASIN PER ISPWC SD-601 TYPE 1.
GRATE TO BE NEENAH MODEL NUMBER R-3067 OR APPROVED
EQUAL
INSTALL STORM DRAIN PIPE, SIZE AND LENGTH PER PLAN
INSTALL INFILTRATOR DRAIN PER REXBURG SD-16. TO INCLUDE
MANHOLE, CHAMBERS, AND DRAIN ROCK MATERIALS. SEE
DRAINAGE CALCULATIONS TABLE, AND DETAIL 1 SHEET C.6.0
INSTALL UNDERGROUND INFILTRATOR, SEE DETAIL 2, SHEET C.6.0
66
67
68
69
IRRIGATION KEYNOTES
INSTALL 72" IRRIGATION CONCRETE STRUCTURE
INSTALL 48" CULVERT (CONCRETE OR METAL)
TIE INTO EXISTING CULVERT
81
82
83
SITE PLAN KEYNOTES
INSTALL HEAVY DUTY ASPHALT (SEE FLEXIBLE PAVEMENT SECTION
SUMMARY TABLE SHEET C.3.2)
INSTALL 2.5' CURB & GUTTER PER CITY OF REXBURG SD-3
TIE INTO EXISTING ASPHALT, SAWCUT AS REQUIRED
INSTALL 4" THICK SIDEWALK, (WIDTH PER PLAN) PER ISPWC SD-709, 714,
714A, 714B UNLESS OTHERWISE NOTED
INSTALL ADA RAMP WITH TRUNCATED DOMES PER CITY OF REXBURG SD
INSTALL LANDSCAPE PER LANDSCAPE PLAN
INSTALL STOP SIGN PER MUTCD STANDARDS
INSTALL LIGHT DUTY ASPHALT (SEE FLEXIBLE PAVEMENT SECTION
SUMMARY TABLE SHEET C.3.2)
01
02
03
04
05
06
07
08
SEWER KEYNOTES
TIE INTO EXISTING SANITARY SEWER MANHOLE
INSTALL 8" SANITARY SEWER MAIN LINE (LENGTH PER PLANS)
INSTALL SANITARY SEWER MANHOLE PER ISPWC- SD-501A
INSTALL CAP AND MARK (TO SURFACE) SEE ARCHITECTS PLANS
FOR CONTINUATION
INSTALL 12" SANITARY SEWER MAIN LINE (LENGTH PER PLANS)
51
52
53
54
55
83
81
81
8182
82 82 82
81
51
52
5253
53
5353
4" SS PRESSURE MAIN LINE
05/04/22
PRE
L
I
M
I
N
A
R
Y
N
O
T
F
O
R
C
O
N
S
T
R
U
C
T
I
O
N
FOR
R
E
V
I
E
W
O
N
L
Y
PR
E
L
I
M
I
N
A
R
Y
N
O
T
F
O
R
CO
N
S
T
R
U
C
T
I
O
N
FO
R
R
E
V
I
E
W
O
N
L
Y
0+00 1+00 2+00 3+00 4+00
0+00 1+00
48
7
6
.
9
8
48
7
7
.
6
6
2+00
48
7
5
.
3
0
48
7
7
.
7
1
3+00
48
7
5
.
0
1
48
7
7
.
1
3
4+00
48
7
5
.
2
1
48
7
5
.
5
8
ST
A
:
0
+
4
9
.
5
9
(
-
5
.
6
8
,
L
)
SS
M
H
6
RI
M
:
4
8
7
7
.
1
4
IN
V
I
N
:
4
8
5
7
.
4
9
-
8
"
(
N
)
IN
V
I
N
:
4
8
5
7
.
2
6
-
1
2
"
(
E
)
IN
V
O
U
T
:
4
8
5
7
.
1
6
-
1
2
"
(
W
)
ST
A
:
0
+
1
9
.
6
8
(
-
5
.
3
3
,
L
)
SS
M
H
-
4
RI
M
:
4
8
7
0
.
1
5
IN
V
O
U
T
:
4
8
5
7
.
6
1
-
8
"
(
S
)
29.91' of 8" S.S. @ 0.40%
↕ 19.98' (SS)
↕ 12.54' (SS)
ST
A
=
0
+
2
7
.
4
5
T.
O
.
W
.
=
4
8
7
2
.
1
6
STA = 2+73.61
T.O.W. = 4870.48
ST
A
:
0
+
6
1
.
6
3
8"
x
9
0
°
H
O
R
Z
.
B
E
N
D
ST
A
:
2
+
6
2
.
6
3
8"
G
A
T
E
V
A
L
V
E
ST
A
:
2
+
7
3
.
9
0
8"
x
6
"
W
A
T
E
R
T
E
E
343LF OF 8" DI WATER PIPE
t
o
e
t
o
e
t
o
e
to
e
to
e
t
o
e
t
o
e
t
o
e
to
e
to
e
16
'
'
W
16
'
'
W
16
'
'
W
0+00 1+00 2+00 3+00 4+00
8'' W 8'' W 8'' W 8'' W 8'' W 8'' W 8'' W 8'' W
SSBP
:
0
+
0
0
.
0
0
PI
:
4
+
2
6
.
4
8
SS
48
7
6
48
7
8
4878
48
7
8
4
8
7
8
4
8
7
7
4875
4876
4
8
7
7
487
6
SSMH 6
SSMH - 4
8" S.S.
4830
4840
4850
4860
4870
4880
4890
4900
9+00
El
e
v
a
t
i
o
n
4830
4840
4850
4860
4870
4880
4890
4900
-1+00
1 5
RE
V
I
S
I
O
N
S
RE
V
#
DA
T
E
DR
A
W
I
N
G
I
N
F
O
DA
T
E
DE
S
I
G
N
E
D
DR
A
W
N
*S
E
E
G
E
N
E
R
A
L
N
O
T
E
S
S
H
E
E
T
WA
R
N
I
N
G
0
1
2
IF
T
H
I
S
B
A
R
D
O
E
S
N
O
T
ME
A
S
U
R
E
2
"
T
H
E
N
DR
A
W
I
N
G
I
S
N
O
T
T
O
S
C
A
L
E
CI
T
Y
R
E
V
I
E
W
S
E
T
ww
w
.
h
o
r
r
o
c
k
s
.
c
o
m
PAGE
C
PR
O
J
E
C
T
CH
E
C
K
E
D
D
B
A
#
2 3 4
21
9
4
S
n
a
k
e
R
i
v
e
r
P
k
w
y
.
,
S
u
i
t
e
2
0
5
Id
a
h
o
F
a
l
l
s
,
I
D
8
3
4
0
2
(2
0
8
)
5
2
2
-
1
2
2
3
PRELIMINARY
NOT FOR
CONSTRUCTION
H
O R R O C
K
S
E
N
G I N E E R
S
0 30'60'
SCALE: 1" = 30'
N
ID
-
L
D
-
4
0
7
0
-
2
1
CJ
F
TL
M
JB
F
05
/
0
3
/
2
0
2
2
PL
A
N
&
P
R
O
F
I
L
E
-
P
R
I
V
A
T
E
D
R
I
V
E
W
E
S
T
RE
X
B
U
R
G
N
O
R
T
H
N
I
T
R
O
C
A
R
W
A
S
H
RE
X
B
U
R
G
,
I
D
A
H
O
14
C.7.2
PRIVATE DRIVE
SHEET C.3.1, C.4.0, C.5.0, C.6.0
SHEET C.7.0
01
08 0807
06
06
06
04
03
02 02
37 37
38
3943
45
PROPOSED SURFACE
EXISTING SURFACE
43
INSTALL 8" 90° HORIZONTAL BEND,
INCLUDING THRUST BLOCK PER ISPWC SD-403
MO
O
D
Y
S
T
PRIVATE DRIVE
WATER KEYNOTES
INSTALL 16" PLUG
INSTALL 16" X 4" TEE
INSTALL 16" TO 14" REDUCER
TIE INTO EXISTING 8" WATER MAIN
INSTALL 8" DUCTILE IRON PIPE (PER CITY OF CITY OF REXBURG
STANDARD), LENGTH PER PLANS, MUST MAINTAIN 5' COVER
INSTALL FIRE HYDRANT PER ISPWC SD-404. FIRE HYDRANT TO MEET
CITY OF REXBURG STANDARDS.
INSTALL 6" X 8" TEE WITH GATE VALVE PER CITY OF REXBURG
STANDARDS.
INSTALL 4" WATER SERVICE
INSTALL 2" WATER SERVICE STUB PER ISPWC SD-402. STUBS PER
CITY OF REXBURG STANDARD.
INSTALL 8" PLUG
POTABLE & NON-POTABLE VERTICAL LINE CROSSING PER ISPWC
SD-407, MINIMUM 1.5' VERTICAL SEPARATION
INSTALL 8" X 8" TEE
INSTALL 8" GATE VALVE
INSTALL 6" FIRE CONNECTION. WATER SERVICE TO HAVE A MINIMUM
1.5' VERTICAL SEPARATION TO ANY NON-POTABLE UTILITY LINE
INSTALL 16" DUCTILE IRON PIPE (PER CITY OF CITY OF REXBURG
STANDARD), LENGTH PER PLANS, MUST MAINTAIN 5' COVER
INSTALL 16" X 6" TEE
INSTALL 16" X 8" TEE
INSTALL 16" VALVE
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
LEGEND
METOA: MATCH EXISTING TOP OF ASPHALT
TBC: TOP BACK OF CURB
DTBC: DEPRESSED TOP BACK OF CURB
METBC: MATCH EXISTING TOP BACK CURB
TOC: TOP OF CONCRETE
METOC: MATCH EXISTING TOP OF CONCRETE
TOG: TOP OF GRATE
1.DRIVE AISLE DIMENSIONS MEASURED TO FACE OF CURB, WHERE
CURB IS PROPOSED OR TO EDGE OF PAVEMENT OTHERWISE.
2. CONTOURS SHOWN AT 1.0' AND 5.0' INTERVALS
3. ALL ELEVATIONS ARE FG
4. ALL DIMENSIONS PERTAINING TO PLAN AND PROFILE SHEETS C.7.0,
C.7.1, C.7.2, & C.7.3 ARE SHOWN ON SHEET C.3.0
SHEET NOTE
MISCELLANEOUS KEYNOTES
PARKING LOT LIGHT POLE PER ELECTRICAL PLANSA
STORM DRAIN KEYNOTES
INSTALL STORM DRAIN CATCH BASIN PER ISPWC SD-601 TYPE 1.
GRATE TO BE NEENAH MODEL NUMBER R-3067 OR APPROVED
EQUAL
INSTALL STORM DRAIN PIPE, SIZE AND LENGTH PER PLAN
INSTALL INFILTRATOR DRAIN PER REXBURG SD-16. TO INCLUDE
MANHOLE, CHAMBERS, AND DRAIN ROCK MATERIALS. SEE
DRAINAGE CALCULATIONS TABLE, AND DETAIL 1 SHEET C.6.0
INSTALL UNDERGROUND INFILTRATOR, SEE DETAIL 2, SHEET C.6.0
66
67
68
69
IRRIGATION KEYNOTES
INSTALL 72" IRRIGATION CONCRETE STRUCTURE
INSTALL 48" CULVERT (CONCRETE OR METAL)
TIE INTO EXISTING CULVERT
81
82
83
SITE PLAN KEYNOTES
INSTALL HEAVY DUTY ASPHALT (SEE FLEXIBLE PAVEMENT SECTION
SUMMARY TABLE SHEET C.3.2)
INSTALL 2.5' CURB & GUTTER PER CITY OF REXBURG SD-3
TIE INTO EXISTING ASPHALT, SAWCUT AS REQUIRED
INSTALL 4" THICK SIDEWALK, (WIDTH PER PLAN) PER ISPWC SD-709, 714,
714A, 714B UNLESS OTHERWISE NOTED
INSTALL ADA RAMP WITH TRUNCATED DOMES PER CITY OF REXBURG SD
INSTALL LANDSCAPE PER LANDSCAPE PLAN
INSTALL STOP SIGN PER MUTCD STANDARDS
INSTALL LIGHT DUTY ASPHALT (SEE FLEXIBLE PAVEMENT SECTION
SUMMARY TABLE SHEET C.3.2)
01
02
03
04
05
06
07
08
SEWER KEYNOTES
TIE INTO EXISTING SANITARY SEWER MANHOLE
INSTALL 8" SANITARY SEWER MAIN LINE (LENGTH PER PLANS)
INSTALL SANITARY SEWER MANHOLE PER ISPWC- SD-501A
INSTALL CAP AND MARK (TO SURFACE) SEE ARCHITECTS PLANS
FOR CONTINUATION
INSTALL 12" SANITARY SEWER MAIN LINE (LENGTH PER PLANS)
51
52
53
54
55
6' MINIMUM
6' MINIMUM
42
53 5352
49
54
05/04/22
PRE
L
I
M
I
N
A
R
Y
N
O
T
F
O
R
C
O
N
S
T
R
U
C
T
I
O
N
FOR
R
E
V
I
E
W
O
N
L
Y
PR
E
L
I
M
I
N
A
R
Y
N
O
T
F
O
R
CO
N
S
T
R
U
C
T
I
O
N
FO
R
R
E
V
I
E
W
O
N
L
Y
fl
fl
fl sd
fl
fl
fl sd
IR
R
IR
R
2
1.
3
9
1
A
C
4876
48
7
6
4
8
7
8
48
7
6
4
8
7
6
48
7
7
TOA:4877.66
TOA:4876.99
TOA:4876.36
TOA:4877.90
TOA:4877.30
TOA:4875.14
TOA:4875.39
TOA:4875.91
TOA:4875.74
4+
0
0
5+00 6+00 7+00 7+32
PI: 4+26.48
EP
:
7
+
3
2
.
0
7
0.9%1.8
%
1.8
%
0.5%
4
8
7
7
4877
4
8
7
7
4876
4+00 5+00 6+00 7+00
4+00
48
7
5
.
2
1
48
7
5
.
5
8
5+00
48
7
5
.
4
7
48
7
5
.
8
2
6+00
48
7
5
.
9
6
48
7
6
.
6
0
7+00
48
7
5
.
9
1
48
7
6
.
6
7
ST
A
=
6
+
9
1
.
4
4
T.
O
.
W
.
=
4
8
6
7
.
7
2
ST
A
:
5
+
6
7
.
3
7
8"
x
6
"
W
A
T
E
R
T
E
E
271LF OF 8" DI WATER PIPE
18" MIN.
El
e
v
a
t
i
o
n
4830
4840
4850
4860
4870
4880
4890
4900
-1+00
4830
4840
4850
4860
4870
4880
4890
4900
9+00
1 5
RE
V
I
S
I
O
N
S
RE
V
#
DA
T
E
DR
A
W
I
N
G
I
N
F
O
DA
T
E
DE
S
I
G
N
E
D
DR
A
W
N
*S
E
E
G
E
N
E
R
A
L
N
O
T
E
S
S
H
E
E
T
WA
R
N
I
N
G
0
1
2
IF
T
H
I
S
B
A
R
D
O
E
S
N
O
T
ME
A
S
U
R
E
2
"
T
H
E
N
DR
A
W
I
N
G
I
S
N
O
T
T
O
S
C
A
L
E
CI
T
Y
R
E
V
I
E
W
S
E
T
ww
w
.
h
o
r
r
o
c
k
s
.
c
o
m
PAGE
C
PR
O
J
E
C
T
CH
E
C
K
E
D
D
B
A
#
2 3 4
21
9
4
S
n
a
k
e
R
i
v
e
r
P
k
w
y
.
,
S
u
i
t
e
2
0
5
Id
a
h
o
F
a
l
l
s
,
I
D
8
3
4
0
2
(2
0
8
)
5
2
2
-
1
2
2
3
PRELIMINARY
NOT FOR
CONSTRUCTION
1
H
O R R O C
K
S
E
N
G I N E E R
S
0 30'60'
SCALE: 1" = 30'
N
ID
-
L
D
-
4
0
7
0
-
2
1
CJ
F
TL
M
JB
F
05
/
0
3
/
2
0
2
2
PL
A
N
&
P
R
O
F
I
L
E
-
P
R
I
V
A
T
E
D
R
I
V
E
S
O
U
T
H
RE
X
B
U
R
G
N
O
R
T
H
N
I
T
R
O
C
A
R
W
A
S
H
RE
X
B
U
R
G
,
I
D
A
H
O
15
C.7.3
SHEET C.7.1
NO
R
T
H
2
N
D
E
A
S
T
PROPOSED SURFACE
EXISTING SURFACE
6' MINIMUM
SHEET C.7.2
SHEET C.3.1, C.4.0, C.5.0, C.6.0
PRIVATE DRIVE SOUTH
01 HD
PRIVATE DRIVE SOUTH
WATER KEYNOTES
INSTALL 16" PLUG
INSTALL 16" X 4" TEE
INSTALL 16" TO 14" REDUCER
TIE INTO EXISTING 8" WATER MAIN
INSTALL 8" DUCTILE IRON PIPE (PER CITY OF CITY OF REXBURG
STANDARD), LENGTH PER PLANS, MUST MAINTAIN 5' COVER
INSTALL FIRE HYDRANT PER ISPWC SD-404. FIRE HYDRANT TO MEET
CITY OF REXBURG STANDARDS.
INSTALL 6" X 8" TEE WITH GATE VALVE PER CITY OF REXBURG
STANDARDS.
INSTALL 4" WATER SERVICE
INSTALL 2" WATER SERVICE STUB PER ISPWC SD-402. STUBS PER
CITY OF REXBURG STANDARD.
INSTALL 8" PLUG
POTABLE & NON-POTABLE VERTICAL LINE CROSSING PER ISPWC
SD-407, MINIMUM 1.5' VERTICAL SEPARATION
INSTALL 8" X 8" TEE
INSTALL 8" GATE VALVE
INSTALL 6" FIRE CONNECTION. WATER SERVICE TO HAVE A MINIMUM
1.5' VERTICAL SEPARATION TO ANY NON-POTABLE UTILITY LINE
INSTALL 16" DUCTILE IRON PIPE (PER CITY OF CITY OF REXBURG
STANDARD), LENGTH PER PLANS, MUST MAINTAIN 5' COVER
INSTALL 16" X 6" TEE
INSTALL 16" X 8" TEE
INSTALL 16" VALVE
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
LEGEND
METOA: MATCH EXISTING TOP OF ASPHALT
TBC: TOP BACK OF CURB
DTBC: DEPRESSED TOP BACK OF CURB
METBC: MATCH EXISTING TOP BACK CURB
TOC: TOP OF CONCRETE
METOC: MATCH EXISTING TOP OF CONCRETE
TOG: TOP OF GRATE
1.DRIVE AISLE DIMENSIONS MEASURED TO FACE OF CURB, WHERE
CURB IS PROPOSED OR TO EDGE OF PAVEMENT OTHERWISE.
2. CONTOURS SHOWN AT 1.0' AND 5.0' INTERVALS
3. ALL ELEVATIONS ARE FG
4. ALL DIMENSIONS PERTAINING TO PLAN AND PROFILE SHEETS C.7.0,
C.7.1, C.7.2, & C.7.3 ARE SHOWN ON SHEET C.3.0
SHEET NOTE
MISCELLANEOUS KEYNOTES
PARKING LOT LIGHT POLE PER ELECTRICAL PLANSA
STORM DRAIN KEYNOTES
INSTALL STORM DRAIN CATCH BASIN PER ISPWC SD-601 TYPE 1.
GRATE TO BE NEENAH MODEL NUMBER R-3067 OR APPROVED
EQUAL
INSTALL STORM DRAIN PIPE, SIZE AND LENGTH PER PLAN
INSTALL INFILTRATOR DRAIN PER REXBURG SD-16. TO INCLUDE
MANHOLE, CHAMBERS, AND DRAIN ROCK MATERIALS. SEE
DRAINAGE CALCULATIONS TABLE, AND DETAIL 1 SHEET C.6.0
INSTALL UNDERGROUND INFILTRATOR, SEE DETAIL 2, SHEET C.6.0
66
67
68
69
IRRIGATION KEYNOTES
INSTALL 72" IRRIGATION CONCRETE STRUCTURE
INSTALL 48" CULVERT (CONCRETE OR METAL)
TIE INTO EXISTING CULVERT
81
82
83
SITE PLAN KEYNOTES
INSTALL HEAVY DUTY ASPHALT (SEE FLEXIBLE PAVEMENT SECTION
SUMMARY TABLE SHEET C.3.2)
INSTALL 2.5' CURB & GUTTER PER CITY OF REXBURG SD-3
TIE INTO EXISTING ASPHALT, SAWCUT AS REQUIRED
INSTALL 4" THICK SIDEWALK, (WIDTH PER PLAN) PER ISPWC SD-709, 714,
714A, 714B UNLESS OTHERWISE NOTED
INSTALL ADA RAMP WITH TRUNCATED DOMES PER CITY OF REXBURG SD
INSTALL LANDSCAPE PER LANDSCAPE PLAN
INSTALL STOP SIGN PER MUTCD STANDARDS
INSTALL LIGHT DUTY ASPHALT (SEE FLEXIBLE PAVEMENT SECTION
SUMMARY TABLE SHEET C.3.2)
01
02
03
04
05
06
07
08
SEWER KEYNOTES
TIE INTO EXISTING SANITARY SEWER MANHOLE
INSTALL 8" SANITARY SEWER MAIN LINE (LENGTH PER PLANS)
INSTALL SANITARY SEWER MANHOLE PER ISPWC- SD-501A
INSTALL CAP AND MARK (TO SURFACE) SEE ARCHITECTS PLANS
FOR CONTINUATION
INSTALL 12" SANITARY SEWER MAIN LINE (LENGTH PER PLANS)
51
52
53
54
55
PROPOSED SURFACE
05/04/22
PRE
L
I
M
I
N
A
R
Y
N
O
T
F
O
R
C
O
N
S
T
R
U
C
T
I
O
N
FOR
R
E
V
I
E
W
O
N
L
Y
PR
E
L
I
M
I
N
A
R
Y
N
O
T
F
O
R
CO
N
S
T
R
U
C
T
I
O
N
FO
R
R
E
V
I
E
W
O
N
L
Y
fl
fl
fl
fl
fl
fl
fl
fl
fl
toe toe toe toe toe toe toe toe
toetoetoetoetoetoetoetoetoe
toe
toetoetoe
eee
e
ee
pp
sd
sd
pp
to
b
to
b
t
o
b
to
b
t
o
b
tobtobtobtobtobtobtobtobtobtob
tob tob tob tob tob tob tob tob tob
tob
to
b
to
b
to
b
to
b
to
b
to
b
to
b
to
b
t
o
b
to
b
to
b
to
b
to
b
to
b
to
b
to
b
tob
to
b
14'' w
s
LOD LOD LOD LOD LOD LOD LOD LOD LOD LOD LOD
LO
D
LO
D
LO
D
LO
D
LO
D
LO
D
LOD LOD
LO
D
LO
D
LO
D
LO
D
LO
D
LO
D
LO
D
LO
D
LO
D
LO
D
LO
D
LOD
LO
D
LO
D
LODLODLODLODLODLODLODLODLODLODLODLODLODLODLOD
LO
D
LO
D
LO
D
LO
D
LO
D
LO
D
LO
D
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SF
SFSFSFSFSFSFSFSFSFSFSFSFSFSFSFSF
SF
SF
SF
48
7
5
48
7
6
4878
4879
4878
4877
4
8
7
8
48
7
7
fl
fl
fl
fl
fl
fl
fl
fl
fl
toe toe toe toe toe toe toe toe
toetoetoetoetoetoetoetoetoe
toe
toetoetoe
eee
e
ee
pp
sd
sd
pp
to
b
to
b
t
o
b
to
b
t
o
b
tobtobtobtobtobtobtobtobtobtob
tob tob tob tob tob tob tob tob tob
tob
to
b
to
b
to
b
to
b
to
b
to
b
to
b
to
b
t
o
b
to
b
to
b
to
b
to
b
to
b
to
b
to
b
tob
to
b
14'' w
s
IR
R
IR
R
IR
R
IR
R
IR
R
IR
R
4877
48
7
8
4877
48
7
7
48
7
5
48
7
6
4
8
7
6
48
7
6
48
7
6
487
7
4
8
7
8
4876
48
7
7
4877
4876
1 5
RE
V
I
S
I
O
N
S
RE
V
#
DA
T
E
DR
A
W
I
N
G
I
N
F
O
DA
T
E
DE
S
I
G
N
E
D
DR
A
W
N
*S
E
E
G
E
N
E
R
A
L
N
O
T
E
S
S
H
E
E
T
WA
R
N
I
N
G
0
1
2
IF
T
H
I
S
B
A
R
D
O
E
S
N
O
T
ME
A
S
U
R
E
2
"
T
H
E
N
DR
A
W
I
N
G
I
S
N
O
T
T
O
S
C
A
L
E
CI
T
Y
R
E
V
I
E
W
S
E
T
ww
w
.
h
o
r
r
o
c
k
s
.
c
o
m
PAGE
C
PR
O
J
E
C
T
CH
E
C
K
E
D
D
B
A
#
2 3 4
21
9
4
S
n
a
k
e
R
i
v
e
r
P
k
w
y
.
,
S
u
i
t
e
2
0
5
Id
a
h
o
F
a
l
l
s
,
I
D
8
3
4
0
2
(2
0
8
)
5
2
2
-
1
2
2
3
PRELIMINARY
NOT FOR
CONSTRUCTION
H
O R R O C
K
S
E
N
G I N E E R
S
0 30'60'
SCALE: 1" = 30'
N
LEGEND
SILT FENCE SEE DETAIL THIS SHEETSFSF
CONSTRUCTION FENCE
INLET PROTECTION SEE DETAIL THIS SHEET
STABILIZED CONSTRUCTION ENTRANCE SEE DETAIL
THIS SHEET
PROPERTY BOUNDARY
LIMITS OF DISTURBANCE
PORTABLE TOILET CONTAINMENT
JOBSITE DUMPSTER
CONCRETE WASHOUT AREA
DIRECTION OF EXISTING OVERLAND FLOW
LOD LOD
INSTALL TEMPORARY INLET PROTECTION AT STORM DRAIN
INLETS, 2 BAGS HIGH PER BMP31. ALL SILT TO BE REMOVED
REGULARLY(FOR EXISTING AND PROPOSED INLETS)
STABILIZED CONSTRUCTION ENTRANCE PER APWA 126 AT
ENTRANCES AS SHOWN.
CONSTRUCT SILT FENCE/PRESERVATION PER BMP 63-68
PROVIDE DUST CONTROL FOR ENTIRE SITE.
CONCRETE WASHOUT AREA
APPROXIMATE QUANTITY SUMMARY
LINEAR FIBER ROLL -
SILT FENCE 981'
CONSTRUCTION FENCE -
EARTH DIKE & DRAINAGE
SWALE -
RIP RAP -
HYDROSEEDING -
STABILIZED CONSTRUCTION
ENTRANCE 2 EA
STABILIZED STAGING AREA 1 EA
CONCRETE WASH OUT 1 EA
SEDIMENT BASIN -
WHEEL WASH -
INLET PROTECTION 7 EA
CHECK DAM -
LIMITS OF DISTURBANCE ±2 AC
PROJECT ACRES ±2 AC
1
2
3
4
5
1)BMP NEEDS FOR STORM WATER RUNOFF FOR A PARTICULAR AREA WILL BE
DETERMINED WHEN A NEW STRUCTURE IS PROPOSED FOR CONSTRUCTION.
2)IT IS NOT INTENDED FOR THE SITE TO RECEIVE ANY ONCOMING FLOW FROM
OUTSIDE SOURCES NOT CONTAINED IN EXISTING FLOW STRUCTURES.
3)FIELD MARK LIMITS OF DISTURBANCE FOR APPROVAL BY LOCAL AUTHORITY
AND OBTAIN APPROPRIATE STORM WATER MANAGEMENT PERMIT.
4)INSTALL SILT FENCE AND/OR ENVIRONMENTAL FENCE AROUND PERIMETER OF
PROJECT AS INDICATED ON THIS PLAN SHEET.
5)INSTALL SEDIMENT CONTROL MEASURES INDICATED IN ALL EXISTING STORM
DRAIN INLETS ADJACENT TO THE CONSTRUCTION SITE.
6)CONTRACTOR WILL BEGIN DEMOLITION, GRADING, EXCAVATION, AND
CONSTRUCTING SITE UTILITY IMPROVEMENTS AS NEW DRAINAGE ELEMENTS
ARE COMPLETED, CONSTRUCT SEDIMENT PROTECTION AT ALL NEW INLETS.
7)AREAS DISTURBED BY CONSTRUCTION ACTIVITIES WILL BE STABILIZED WITH
NATIVE GRASS MATERIAL OUTSIDE THE STREET RIGHT OF WAY AND
PAVEMENT AREAS OF PARKING AND DRIVEWAY AREAS. SITE STABILIZATION
OF AREAS DISTURBED BY CONSTRUCTION ACTIVITIES TO BE COMPLETED
WITHIN 14 DAYS OF FINISHING AN AREA TO THE FINAL LINES AND GRADES
INDICATED ON THE GRADING PLAN.
8)LANDSCAPE ESTABLISHMENT, REMOVE TEMPORARY MEASURES AND CLEAN
STORM DRAIN SYSTEM PRIOR TO RELEASING SYSTEM TO PROJECT OWNER.
9)DISCHARGE FROM THE SITE WILL BE THROUGH THE NEW STORM DRAIN
SYSTEM AND INTO THE SNAKE RIVER LANDING COMMUNAL SYSTEM.
10)THE BMPS AND SITE WILL BE MONITORED REGULARLY, ANY ADDITIONAL
BMPS THAT ARE NEEDED WILL BE DETERMINED DURING REGULAR
INSPECTIONS AND INSTALLED ACCORDING TO SPECIFICATIONS.
11)CONTRACTOR TO UTILIZE STABLIZED CONSTRUCTION ENTRANCE FOR
VEHICLE TIRE WASH, AS NECESSARY.
EROSION CONTROL NOTES
NOTE: SEE LANDSCAPE PLAN FOR FINAL STABILIZATION
ID
-
L
D
-
4
0
7
0
-
2
1
CJ
F
TL
M
JB
F
05
/
0
3
/
2
0
2
2
ER
O
S
I
O
N
C
O
N
T
R
O
L
RE
X
B
U
R
G
N
O
R
T
H
N
I
T
R
O
C
A
R
W
A
S
H
RE
X
B
U
R
G
,
I
D
A
H
O
15
C.8.0
1
INLET PROTECTION (PAVED AREA)
BMP 31
RETRIEVAL STRAP
OVERFLOW
(PEAK STORM)
SEDIMENT ACCUMULATION
GEOTEXTILE FABRIC
SILT FENCE
BMP 63-68
EQUAL ALTERNATE: STEEL FENCE POST
FILTER FABRIC MATERIAL 60" WIDE ROLLS. USE
STAPLES OR WIRE RINGS TO ATTACH FABRIC
TO WIRE
2" X 2" 14 GA WIRE
FABRIC OR EQUIV.
BURY BOTTOM OF FILTER MATERIAL IN
8" X 12" TRENCH
FILTER FABRIC MATERIAL
2" X 2" 14 GA WIRE
FABRIC OR EQUIV.
PROVIDE 3/4" - 1 1/2" WASHED GRAVEL
BACKFILL IN TRENCH AND ON BOTH
SIDES OR FILTER FENCE FABRIC ON
THE SURFACE
2" X 4" WOOD POST ALT:
STEEL FENCE POSTS
8"
12
"
2'
-
6
"
2'
-
0
"
5'
-
0
"
6"
12"
DIAMETER ROCK
6" MIN
18" MIN
18
"
M
I
N
48" MIN48" MIN
4" PVC PIPE
FLOW
CROSS-SECTION
WOVEN FABRIC SANDBAG FILLED WITH
COARSE SAND-MIN WEIGHT 40 LBS.
24" MIN
FRONT VIEW
4" PVC PIPE FOR DRAINAGE
SANDBAG BARRIER
SPC-2
R25'
1" TO 3"
COARSE AGGREGATE
FILTER FABRIC
50' MI
N
PUB
L
I
C
R
O
A
D
HA
R
D
S
U
R
F
A
C
E
STABILIZED CONSTRUCTION ENTRANCE
EC-5
30'
MI
N
2
3
3
3
3
4
4
5
111
4
4
4
1
2
MOODY ST
PR
I
V
A
T
E
D
R
I
V
E
NO
R
T
H
2
N
D
E
A
S
T
1
1
PROPOSED BUILDING
± 4,613 SF
05/04/22
PRE
L
I
M
I
N
A
R
Y
N
O
T
F
O
R
C
O
N
S
T
R
U
C
T
I
O
N
FOR
R
E
V
I
E
W
O
N
L
Y
PR
E
L
I
M
I
N
A
R
Y
N
O
T
F
O
R
CO
N
S
T
R
U
C
T
I
O
N
FO
R
R
E
V
I
E
W
O
N
L
Y
...\22-06 SE-1 SITE ELECTRICAL PLA 1/13/2022 2:04:00 PM
NOT
F
O
R
C
O
N
S
T
R
U
C
T
I
O
N
...\22-06 SE-2 ENLARGED POINT OF S 1/13/2022 2:06:37 PM
NOT
F
O
R
C
O
N
S
T
R
U
C
T
I
O
N
PRO
F
E
S
S
I
O
N
A
L
EN GI N E E R
ST ATE
O
F
I
D
A
H
O
A
1/
7
/
2
2
14
1
3
4
D VID
B
.
P
O
R
T
E
R
L
I
C
E
N
SED
GENERAL STRUCTURAL NOTES
(APPLY UNLESS NOTED OTHERWISE ON PLANS/DETAILS)
GENERAL REQUIREMENTS:
1.THE STRUCTURAL SYSTEMS AND MEMBERS DEPICTED HEREIN HAVE BEEN DESIGNED
PRIMARILY TO SAFEGUARD AGAINST MAJOR STRUCTURAL DAMAGE AND LOSS OF
LIFE, NOT TO LIMIT DAMAGE OR MAINTAIN FUNCTION (IBC SECTION 101.3).
2.THESE DRAWINGS, AND THEIR ASSOCIATED STRUCTURAL CALCULATIONS, HAVE
BEEN PERFORMED USING STANDARDS OF PROFESSIONAL CARE AND
COMPLETENESS NORMALLY EXERCISED UNDER SIMILAR CIRCUMSTANCES BY
REPUTABLE STRUCTURAL ENGINEER'S IN THIS OR SIMILAR LOCALITIES. THEY
NECESSARILY ASSUME THAT THE WORK DEPICTED WILL BE PERFORMED BY AN
EXPERIENCED CONTRACTOR AND/OR WORKMEN WHO HAVE A WORKING
KNOWLEDGE OF THE INTERNATIONAL BUILDING CODE CONVENTIONAL FRAMING
REQUIREMENTS AND OF INDUSTRY ACCEPTED STANDARD GOOD PRACTICE. AS NOT
EVERY CONDITION OR FRAMING ELEMENT IS (OR CAN BE) EXPLICITLY SHOWN ON
THESE DRAWINGS, IT IS UNDERSTOOD THAT THE CONTRACTOR WILL USE INDUSTRY
ACCEPTED STANDARD GOOD PRACTICE FOR ALL MISCELLANEOUS WORK NOT
EXPLICITLY SHOWN.
3.THESE DRAWINGS REPRESENT THE FINISHED STRUCTURE. THEY DO NOT INDICATE
THE METHOD OF CONSTRUCTION. THE CONTRACTOR SHALL BE SOLELY
RESPONSIBLE FOR CONSTRUCTION MEANS, METHODS, TECHNIQUES, SEQUENCES
AND PROCEDURES. CONSTRUCTION MATERIALS SHALL BE SPREAD OUT IF PLACED
ON FRAMED CONSTRUCTION SUCH THAT DESIGN LIVE LOAD PER SQUARE FOOT AS
STATED HEREIN IS NOT EXCEEDED. OPTIONS ARE FOR CONTRACTOR'S
CONVENIENCE. IF AN OPTION IS USED, THE CONTRACTOR SHALL BE RESPONSIBLE
FOR ALL NECESSARY CHANGES, AND SHALL COORDINATE ALL DETAILS.
4.WHERE DISCREPANCIES OCCUR BETWEEN PLANS, DETAILS, GENERAL STRUCTURAL
NOTES AND SPECIFICATIONS, THE GREATER REQUIREMENTS SHALL GOVERN.
TYPICAL DETAILS AND NOTES ARE NOT NECESSARILY INDICATED ON THE PLANS, BUT
SHALL APPLY NONE-THE-LESS. WHERE NO DETAILS ARE SHOWN, CONSTRUCTION
SHALL CONFORM TO SIMILAR WORK ON THE PROJECT. DETAILS MAY SHOW ONLY
ONE SIDE OF CONNECTION OR MAY OMIT INFORMATION FOR CLARITY.
5.ESTABLISH AND VERIFY ALL OPENINGS AND INSERTS FOR ARCHITECTURAL,
MECHANICAL, PLUMBING AND ELECTRICAL WITH APPROPRIATE TRADES, DRAWINGS
AND SUBCONTRACTORS PRIOR TO CONSTRUCTION. CONTRACTOR SHALL BE
RESPONSIBLE FOR VERIFICATION OF ALL DIMENSIONS WITH ARCHITECTURAL
DRAWINGS PRIOR TO START OF CONSTRUCTION. RESOLVE ANY DISCREPANCY WITH
THE ARCHITECT AND STRUCTURAL ENGINEER.
6.ANY INSPECTIONS, SPECIAL (IBC CHAPTER 17) OR OTHERWISE THAT ARE REQUIRED
BY THE BUILDING CODES, LOCAL BUILDING DEPARTMENTS, OR BY THESE PLANS
SHALL BE DONE BY AN INDEPENDENT INSPECTION COMPANY OR THE BUILDING
DEPARTMENT, SITE VISITS BY THE STRUCTURAL ENGINEER DO NOT CONSTITUTE AN
OFFICIAL INSPECTION, UNLESS SPECIFICALLY CONTRACTED FOR.
7.SHOP DRAWINGS SHALL BE SUBMITTED FOR ALL STRUCTURAL ITEMS IN ADDITION TO
ITEMS REQUIRED BY ARCHITECTURAL SPECIFICATIONS, THE CONTRACTOR SHALL
REVIEW ALL SHOP DRAWINGS PRIOR TO SUBMITTAL. ITEMS NOT IN ACCORDANCE
WITH CONTRACT DRAWINGS SHALL BE FLAGGED UPON HIS REVIEW. VERIFY ALL
DIMENSIONS WITH ARCHITECT. ANY CHANGES, SUBSTITUTIONS, OR DEVIATIONS
FROM ORIGINAL CONTRACT DRAWINGS SHALL BE CLOUDED. ANY OF THE
AFOREMENTIONED WHICH ARE NOT CLOUDED OR FLAGGED BY SUBMITTING PARTIES,
SHALL NOT BE CONSIDERED APPROVED AFTER THE STRUCTURAL ENGINEER'S
REVIEW, UNLESS NOTED ACCORDINGLY. ANY ENGINEERING PROVIDED BY OTHERS
AND SUBMITTED FOR REVIEW, SHALL BEAR THE SEAL OF A STRUCTURAL ENGINEER
REGISTERED IN THE APPROPRIATE STATE. THE SHOP DRAWINGS DO NOT REPLACE
THE ORIGINAL CONTRACT DRAWINGS. ITEMS OMITTED OR SHOWN INCORRECTLY
AND ARE NOT FLAGGED BY THE STRUCTURAL ENGINEER ARE NOT TO BE
CONSIDERED CHANGES TO ORIGINAL DRAWINGS. THE ADEQUACY OF ENGINEERING
DESIGNS AND LAYOUT PERFORMED BY THE OTHERS RESTS WITH THE DESIGNING OR
SUBMITTING AUTHORITY. REVIEWING IS INTENDED ONLY AS AN AID TO THE
CONTRACTOR IN OBTAINING CORRECT SHOP DRAWINGS. RESPONSIBILITY FOR
CORRECTNESS SHALL REST WITH THE CONTRACTOR. ALLOW (5) WORKING DAYS FOR
THE STRUCTURAL ENGINEER'S REVIEW. ONE COPY OF EACH SUBMITTAL WILL BE
RETAINED FOR THE STRUCTURAL ENGINEER'S RECORDS.
BASIS FOR DESIGN:
1.BUILDING CODE: 2018 EDITION OF THE IBC WITH CITY/COUNTY AMENDMENTS.
RISK CATEGORY = II
4. SEISMIC DESIGN PARAMETERS:
ANALYSIS PROCEDURE EQUIVALENT LATERAL FORCE
PROCEDURE
IMPORTANCE FACTOR Ie = 1.00
SITE CLASS D
SEISMIC DESIGN CATEGORY D
MAPPED SPECTRAL RESPONSE
ACCELERATIONS S1 = 0.141, SS = 0.373
DESIGN SPECTRAL RESPONSE
ACCELERATIONS SD1 = 0.218, SDS = 0.374
PERCENT SNOW INCLUDED WITH
SEISMIC LOADS 20%
VERTICAL SHEAR TRANSFER ELEMENTS:
INTERMEDIATE PRECAST
SHEARWALL(S)R = 4.0, CS = 0.094
5. WIND DESIGN PARAMETERS (STRENGTH):
ULTIMATE WIND SPEED 115 MPH (3 SECOND GUST)
WIND EXPOSURE C
IMPORTANCE FACTOR Iw = 1.00
INTERNAL PRESSURE COEFFICIENT -0.18
COMPONENT AND CLADDING PRESSURE 27.8 PSF
NET UPLIFT ON ROOF 4.5 PSF
2. VERTICAL LOADS:
LOCATION LIVE / SNOW
LOAD DEAD LOAD
PRECAST ROOF 35 PSF 50 PSF
3. DEFLECTION LIMITS:
ELEMENTS LIVE LOAD TOTAL LOAD
ROOF PANELS L/360 L/240
BEAMS L/360 L/240
FOUNDATION NOTES:
1.FOUNDATIONS DESIGNED IN CONFORMANCE WITH RECOMMENDATIONS BY:
ATLAS, INC. REPORT NO. E212744g, DATED DECEMBER 1, 2021.
2.SITE PREPARATION AND GRADING REQUIREMENTS OF THE SOIL REPORT AND ANY
ADDENDUM'S SHALL BE COMPLETED PRIOR TO CONSTRUCTION OF FOUNDATIONS.
ANY TESTS OR INSPECTIONS REQUIRED BY THE SOIL REPORT SHALL BE PERFORMED
PRIOR TO PLACEMENT OF FOUNDATION REINFORCING STEEL OR CONCRETE.
ALTERATIONS TO SITE PREPARATION OR GRADING SHALL BE REPORTED TO THE
GEOTECHNICAL ENGINEER PRIOR TO FOUNDATION CONSTRUCTION.
3.A ONE-THIRD INCREASE IN BEARING PRESSURES IS ALLOWED WITH SEISMIC OR
WIND LOAD COMBINATIONS. LATERAL BEARING AND LATERAL SLIDING RESISTANCE
MAY BE COMBINED.
4.ALL FOUNDATIONS SHALL BEAR ON COMPACTED ENGINEERED FILL OR COMPETENT
NATIVE SOIL SUBBASE COMPACTED TO 95% DRY DENSITY (STANDARD PROCTOR).
GRADE IS DEFINED AS LOWEST ADJACENT GRADE WITHIN 5 FEET OF THE BUILDING
FOR PERIMETER FOOTINGS. WHERE EXTERIOR PAVING OR CONCRETE IS DIRECTLY
ADJACENT TO BUILDING, GRADE IS DEFINED AS TOP OF EXTERIOR PAVING AT LEAST
5 FEET FROM BUILDING. CONCRETE FOOTING EXCAVATIONS SHALL BE CLEAN AND
FREE OF LOOSE DEBRIS OR UN-COMPACTED MATERIAL AT TIME OF CONCRETE
PLACEMENT.
5.CONCRETE SLABS ON GRADE SHALL BE SUPPORTED ON A 4 INCH (MIN) LAYER OF
FREE-DRAINING GRANULAR MAT (DRAINAGE FILL COURSE). THE MAT SHOULD
CONSIST OF A WELL GRADED SAND AND GRAVEL MIXTURE WITH MAXIMUM 3/4-INCH
CRUSHED AGGREGATE. THE GRANULAR MAT SHOULD BE COMPACTED TO NO LESS
THAN 95% OF THE MAXIMUM DRY DENSITY AS DETERMINED BY ASTM D1557
6.BACKFILL AGAINST RESTRAINED WALLS SHALL NOT BE PLACED UNTIL AFTER THE
WALLS ARE SUPPORTED BY THE COMPLETION OF INTERIOR FLOOR SYSTEMS AND
CONCRETE OR GROUT STRENGTH HAS REACHED THE 28 DAY STRENGTH LISTED
BELOW.
THE SOIL DESIGN VALUES FOR THE FOUNDATION ARE:
ALLOWABLE BEARING PRESSURE 2500 PSF
ALLOWABLE LATERAL BEARING PRESSURE 346 PSF/FT
ALLOWABLE LATERAL SLIDING COEFFICIENT .35
FOUNDATION BEARING DEPTH
36" BELOW FINISHED GRADE
CONCRETE:
2.ALL NORMAL WEIGHT CONCRETE SHALL BE REGULAR WEIGHT OF 150 POUNDS PER
CUBIC FOOT USING HARD-ROCK AGGREGATES. AGGREGATE USED IN CONCRETE
SHALL CONFORM TO ASTM C33.
3.LAP SPLICES FOR BEAMS AND FLOOR SLABS SLABS SHALL BE ACCORDING TO
CHAPTER 12 OF ACI 318 OR LAP SCHEDULE ON THESE DRAWINGS.
STAGGER SPLICES A MINIMUM OF ONE LAP LENGTH. NO TACK WELDING OF
REINFORCING BARS ALLOWED WITHOUT PRIOR REVIEW OF PROCEDURE WITH THE
STRUCTURAL ENGINEER. LATEST ACI CODE AND DETAILING MANUAL APPLY. PROVIDE
BENT CORNER BARS TO MATCH AND LAP WITH HORIZONTAL BARS AT ALL CORNERS
AND INTERSECTIONS PER TYPICAL DETAILS. VERTICAL WALL BARS SHALL BE
SPLICED AT OR NEAR FLOOR LINES.
4.ALL DIMENSIONS SHOWING THE LOCATION OF REINFORCING STEEL NOT NOTED AS
"CLEAR" OR "CLR" ARE TO CENTER OF STEEL. MINIMUM COVER FOR
NON-PRESTRESSED CONCRETE REINFORCING SHALL BE AS FOLLOWS:
5.MAXIMUM SLUMP FOR ALL CONCRETE SHALL BE 6". PORTLAND CEMENT SHALL
CONFORM TO ASTM C150. TYPE V CEMENT SHALL BE USED FOR CONCRETE IN
CONTACT WITH ALKALINE SOIL, AND TYPE II ELSEWHERE.
6.NO MORE THAN 90 MINUTES SHALL ELAPSE BETWEEN CONCRETE BATCHING AND
CONCRETE PLACEMENT UNLESS APPROVED BY THE TESTING AGENCY.
7.CONCRETE PLACEMENT AND QUALITY SHALL BE PER RECOMMENDATIONS IN ACI 614,
ACI 301 AND ACI 318. MECHANICALLY VIBRATE ALL CONCRETE WHEN PLACED,
EXCEPT THAT SLABS ON GRADE NEED BE VIBRATED ONLY AROUND AND UNDER
FLOOR DUCTS, ETC. CAST CLOSURE POUR, WHERE SHOWN ON PLANS AROUND
COLUMNS AFTER COLUMN DEAD LOAD IS APPLIED. REMOVE ALL DEBRIS FROM
FORMS BEFORE PLACING CONCRETE.
ALL ITEMS TO BE CAST IN CONCRETE SUCH AS REINFORCING, DOWELS, BOLTS,
ANCHORS, PIPES, SLEEVES, ETC., SHALL BE SECURELY POSITIONED IN THE FORMS
BEFORE PLACING THE CONCRETE.
8.ALL CONCRETE SLABS ON GRADE SHALL BE DIVIDED INTO AREAS BY CONTROL
JOINTS (KEYED OR SAW CUT) SUCH THAT ONE SLAB AREA DOES NOT EXCEED A
MAXIMUM LENGTH OF 24 TIMES THE SLAB THICKNESS IN BOTH DIRECTIONS
(EXAMPLE: 4" SLAB = 8'-0" LENGTH). SQUARE LAYOUTS ARE PREFERRED, BUT THE
SLAB GEOMETRY MAY DICTATE OTHERWISE. THE RATIO OF THE LONG TO SHORT
DISTANCE SHALL NOT EXCEED 1.3. IT IS RECOMMENDED THAT SAW CUTS BE MADE
WITHIN 16 HOURS OF CONCRETE BATCHING.
KEYED CONTROL JOINTS NEED ONLY OCCUR AT EXPOSED EDGES DURING POURING,
ALL OTHER JOINTS MAY BE SAW CUT.
9.HORIZONTAL PIPES AND ELECTRICAL CONDUITS SHALL NOT BE EMBEDDED IN
STRUCTURAL CONCRETE AND SLABS ON GRADE EXCEPT WHERE SPECIFICALLY
APPROVED OR NOTED BY THE STRUCTURAL ENGINEER. PIPES AND CONDUITS SHALL
NOT IMPAIR THE STRENGTH OF THE WORK.
10.FLY ASH MAY BE USED ONLY IF PERMITTED BY ARCHITECTURAL SPECIFICATIONS
AND SHALL BE LIMITED TO 18 PERCENT OF CEMENTITIOUS MATERIALS AND SHALL
HAVE A REPLACEMENT FACTOR OF 1.2 RELATIVE TO CEMENT REPLACED. NO FLY ASH
ADDITIVES SHALL BE USED IN FLATWORK OR ARCHITECTURAL EXPOSED CONCRETE.
11.COLD/HOT WEATHER CONCRETE CONSTRUCTION: PROTECT CONCRETE FROM
DAMAGE OR REDUCED STRENGTH IN COMPLIANCE WITH ACI 305 AND 306.
12.CONCRETE MIXES SHALL BE DESIGNED BY A CERTIFIED LABORATORY AND
APPROVED BY THE STRUCTURAL ENGINEER.
13.LIMIT ALKALI-SILICA REACTION (ASR) TO 0.1% EXPANSION AT 28 DAYS IN CONCRETE
MIX AT ALL EXTERIOR CONCRETE AND INTERIOR CONCRETE EXPOSED TO MOISTURE.
LOCATION:MINIMUM
COVER TOLERANCE
CAST AGAINST EARTH (FOOTINGS)3"± 3 8"
SLABS ON GRADE 112"± 14"
EXPOSED TO EARTH OR WEATHER - #5 AND SMALLER 112"± 3 8"
EXPOSED TO EARTH OR WEATHER - #6 AND LARGER 2"± 3 8"
NOT EXPOSED TO WEATHER OR IN CONTACT WITH THE
GROUND ROOF SLAB 1"18"
STRUCTURAL SLABS AND WALLS 3 4"18"
BEAMS AND COLUMNS (PRIMARY) REINFORCEMENT,
TIES, STIRRUPS AND SPIRALS 112"3 8"
1. MINIMUM 28 DAY CONCRETE STRENGTH SHALL BE AS FOLLOWS:
USE:CONCRETE
STRENGTH:
MAX W/C
RATIO
AIR
ENTRAINMENT
FOUNDATIONS 3500 PSI 0.45 5.5% ± 1%
CONCRETE SLABS ON
GRADE & TOPPING SLAB 3500 PSI 0.45 N/A
PRECAST WALLS & ROOF
HOLLOW CORE PANELS 6000 PSI 0.36 2.0% ± 1.5%
REINFORCING STEEL:
1.ASTM A615 GRADE 60 (FY = 60 KSI) DEFORMED BARS FOR ALL BARS #4 AND LARGER.
ASTM A615 GRADE 40 (FY = 40 KSI) DEFORMED BARS FOR ALL BARS #3 AND SMALLER.
GRADE 60 DEFORMED BARS SHALL BE USED FOR CONCRETE WALLS, BEAMS,
ELEVATED SLABS AND COLUMN REINFORCING.
2.WELDING OF REINFORCING BARS SHALL BE MADE ONLY TO ASTM A706 GRADE 60
BARS AND ONLY USING E90 SERIES RODS. WELDING OF REINFORCING BARS SHALL
BE MADE ONLY AT LOCATIONS SHOWN ON PLANS OR DETAILS.
3.REINFORCING BAR SPACING GIVEN ARE MAXIMUM ON CENTERS. ALL BARS PER CRSI
SPECIFICATIONS AND HANDBOOK. DOWEL ALL VERTICAL REINFORCING TO
FOUNDATION. SECURELY TIE ALL BARS IN LOCATION BEFORE PLACING CONCRETE.
DEFERRED SUBMITTAL ITEMS:
PRECAST WALLS AND HOLLOW CORE ROOF PANELS
SHEET INDEX
SHEET DESCRIPTION DETAILS
S1.0 GENERAL STRUCTURAL NOTES ---
S1.1 TYPICAL DETAILS T-SERIES
S2.0 FOUNDATION PLAN ---
S2.1 ROOF FRAMING PLAN ---
S3.0 FOUNDATION DETAILS 100 - SERIES
S4.0 ROOF FRAMING DETAILS 200 - SERIES
S5.0 PANEL WALL ELEVATIONS ---
S5.1 PANEL WALL ELEVATIONS ---
CAST IN PLACE
CENTERLINE
CENTERLINE OF BEAM
CENTERLINE OF COLUMN
CENTERLINE OF WALL
CLEAR
CONCRETE
CONCRETE CONTROL JOINT
CONCRETE SAWCUT JOINT
CONCRETE MASONRY UNIT
CONNECTION
CONTINUOUS
DEAD LOAD
DOWN
DRAWING(S)
EQUAL
EQUIPMENT
EXPANSION JOINT
EACH WAY
FINISHED FLOOR
FACE OF STEEL
FACE OF WALL
GAUGE
GALVANIZED
GENERAL STRUCTURAL NOTES
CENTERLINE OF FOOTING
FACE OF MEMBER
EXPANSION BOLT
EDGE OF SLAB
DIAMETER
GALV
GSN
DN.
DWG(S)
EQ
EQUIP
EXP. JT (E.J.)
E.W.
F.F.
F.O.S.
F.O.W.
GA
F.O.M.
EXP. BOLT
E.O.S.
Ø OR DIA.
C.I.P.
C L
C.L.B.
C.L.C.
C.L.W.
CLR
CONC
C.C.J.
C.S.J.
C.M.U.
CONN.
CONT
D L
C.L.F.
W/WITH
W/O WITHOUT
T.O.P.
U.N.O.
W.W.F.
TYP
VERT
T.O.S.
T.O.W.
T.O.D.
T.O.F.
T.O.L.
T.O.M.
STD
T.O.B.
T L
SLH
SLV
SIM
SQ
PSF
PSI
REINF
PREFAB
OPP
P.C.
PLF
N.T.S.
O.C.
O.F.W.
TOP OF FOOTING
UNLESS NOTED OTHERWISE
WELDED WIRE FABRIC
TOP OF MASONRY
TOP OF PLATE
TOP OF STEEL
TOP OF WALL
TYPICAL
VERTICAL
STANDARD
TOP OF BEAM
TOP OF DECK
TOP OF LEDGER
TOTAL LOAD
OUTSIDE FACE OF WALL
PRECAST CONCRETE
POUNDS PER LINEAR FOOT
POUNDS PER SQUARE INCH
SHORT LEG VERTICAL
SHORT LEG HORIZONTAL
REINFORCING
SIMILAR
SQUARE
NOT TO SCALE
ON CENTER
OPPOSITE
PREFABRICATED
AGGREGATE BASE COURSE
AIR CONDITIONER
ABOVE FINISHED FLOOR
ALTERNATE
ANCHOR BOLT
AT (MEASUREMENT)
BEAM
BOTTOM OF BEAM
BOTTOM OF DECK
BEARING
BELOW FINISHED FLOOR
BOTTOM OF FOOTING
A.B.C.
A/C
A.F.F.
ALT
A.B.
@
BM
B.O.B.
B.O.D.
BRG
B.F.F
B.O.F.
ABBREVIATIONS
LBS (#)
MFR('S)
M.C.J.
MECH
N/A
LLV
LLH
HORIZ
K(KIP)
L L
LONG LEG VERTICAL
MANUFACTURER('S)
MASONRY CONTROL JOINT
NOT APPLICABLE
LONG LEG HORIZONTAL
POUNDS
MECHANICAL
HORIZONTAL
1000 POUNDS
LIVE LOAD
EXISTING(E)
MIN MINIMUM
MAX MAXIMUM
POUNDS PER SQUARE FOOT
GLUED-LAMINATED BEAMGLB
PFT PREFAB FLOOR TRUSSES
PRT PREFAB ROOF TRUSSES
I.F.W.INSIDE FACE OF WALL
PT PRESSURE TREATED
CONCRETE COLUMNC.C.
ANCHORAGE TO CONCRETE:
ADHESIVE ANCHORS:
HILTI HIT-HY 200 PER ICC ESR-3187
HILTI HIT-RE 500 V3 PER ICC ESR-3814
SIMPSON SET-3G PER ICC ESR-4057
MECHANICAL ANCHORS:
HILTI KWIK HUS PER ICC ESR-3027
HILTI KWIK BOLT-TZ EXPANSION ANCHORS PER ICC ESR-1917
SIMPSON TITEN HD PER ICC ESR-2713
SIMPSON STRONG BOLT-2 PER ICC ESR-3037
REBAR DOWELING TO CONCRETE:
ADHESIVES:
HILTI HIT-HY 200 PER ICC ESR-3187
HILTI HIT-RE 500 V3 PER ICC ESR-3814
SIMPSON AT-XP PER IAPMO ER-263
SIMPSON SET-XP PER ICC ESR-2508
2.SUBSTITUTION REQUESTS FOR ALTERNATE PRODUCTS MUST BE APPROVED IN
WRITING BY THE STRUCTURAL ENGINEER OF RECORD PRIOR TO USE. CONTRACTOR
SHALL PROVIDE CALCULATIONS DEMONSTRATING THAT THE SUBSTITUTED PRODUCT
IS CAPABLE OF ACHIEVING THE PERFORMANCE VALUES OF THE SPECIFIED
PRODUCT. SUBSTITUTIONS WILL BE EVALUATED BY THEIR HAVING AN ICC ESR OR
IAPMO ER SHOWING COMPLIANCE WITH THE RELEVANT BUILDING CODE FOR SEISMIC
USES, LOAD RESISTANCE, INSTALLATION CATEGORY, AND AVAILABILITY OF
COMPREHENSIVE INSTALLATION INSTRUCTIONS. ADHESIVE ANCHOR EVALUATION
WILL ALSO CONSIDER CREEP, IN-SERVICE TEMPERATURE AND INSTALLATION
TEMPERATURE.
3.INSTALL THE ANCHORS PER THE MANUFACTURER INSTRUCTIONS, AS INCLUDED IN
THE ANCHOR PACKAGING.
4.THE CONTRACTOR SHALL ARRANGE AN ANCHOR MANUFACTURER'S
REPRESENTATIVE TO PROVIDE ONSITE INSTALLATION TRAINING FOR ALL OF THEIR
ANCHORING PRODUCTS SPECIFIED. THE STRUCTURAL ENGINEER OF RECORD MUST
RECEIVE DOCUMENTED CONFIRMATION THAT ALL OF THE CONTRACTOR'S
PERSONNEL WHO INSTALL ANCHORS ARE TRAINED PRIOR TO THE COMMENCEMENT
OF INSTALLING ANCHORS.
5.ANCHOR CAPACITY IS DEPENDANT UPON SPACING BETWEEN ADJACENT ANCHORS
AND PROXIMITY OF ANCHORS TO EDGE OF CONCRETE. INSTALL ANCHORS IN
ACCORDANCE WITH SPACING AND EDGE CLEARANCES INDICATED ON THE
DRAWINGS.
POST-INSTALLED ANCHORS:
1.EXCEPT WHERE INDICATED ON THE DRAWINGS, POST-INSTALLED ANCHORS SHALL
CONSIST OF THE FOLLOWING ANCHOR TYPES. ALL ANCHORS ARE TO BE INSTALLED
PER THE MANUFACTURERS RECOMMENDATIONS.
SPECIAL INSPECTION ITEMS:
1.THE OWNER OR THE OWNER'S AUTHORIZED AGENT, OTHER THAN THE
CONTRACTOR, SHALL EMPLOY ONE OR MORE APPROVED AGENCIES TO PROVIDE
SPECIAL INSPECTIONS AND TESTS DURING CONSTRUCTION ON THE TYPES OF
WORK SPECIFIED PER IBC SECTION 1705 AND IDENTIFY THE APPROVED AGENCIES
TO THE BUILDING OFFICIAL. SPECIAL INSPECTIONS ARE REQUIRED AS FOLLOWS:
2.QUALITY ASSURANCE PROGRAM:
A.THE SPECIAL INSPECTOR SHALL OBSERVE THE WORK ASSIGNED TO BE
CERTAIN IT CONFORMS WITH THE APPROVED DESIGN DRAWINGS AND
SPECIFICATIONS.
B.THE SPECIAL INSPECTOR SHALL FURNISH INSPECTION REPORTS TO THE
BUILDING OFFICIAL, AND TO THE STRUCTURAL ENGINEER OF RECORD. ALL
DISCREPANCIES SHALL BE BROUGHT TO THE IMMEDIATE ATTENTION OF THE
CONTRACTOR FOR CORRECTION, THEN, IF UNCORRECTED, TO THE DESIGN
AUTHORITY AND THE BUILDING OFFICIAL.
CONCRETE (IBC TABLE 1705.3)
VERIFICATION AND INSPECTION
CONTINUOUS
SPECIAL
INSPECTION
PERIODIC
SPECIAL
INSPECTION
1. INSPECT REINFORCEMENT, INCLUDING PRESTRESSING
TENDONS, AND VERIFY PLACEMENT -X
2. REINFORCING BAR WELDING:
A. VERIFY WELDABILITY OF REINFORCING BARS OTHER THAN
ASTM A 706;-X
B. INSPECT SINGLE-PASS FILLET WELDS, MAXIMUM 5 16" ; AND X
C. INSPECT ALL OTHER WELDS.X
3. INSPECT ANCHORS CAST IN CONCRETE -X
4. INSPECT ANCHORS POST INSTALLED IN HARDENED CONCRETE
MEMBERS.
A. ADHESIVE ANCHORS INSTALLED IN HORIZONTALLY OR
UPWARDLY INCLINED ORIENTATIONS TO RESIST SUSTAINED
TENSION LOADS.
X
B. MECHANICAL ANCHORS AND ADHESIVE ANCHORS NOT
DEFINED IN 4.A.X
5. VERIFY USE OF REQUIRED DESIGN MIX.-X
6. PRIOR TO CONCRETE PLACEMENT, FABRICATE SPECIMENS FOR
STRENGTH TESTS, PERFORM SLUMP AND AIR CONTENT TESTS,
AND DETERMINE THE TEMPERATURE OF THE CONCRETE.
X -
7. INSPECT CONCRETE AND SHOTCRETE PLACEMENT FOR
PROPER APPLICATION TECHNIQUES.X -
8. VERIFY MAINTENANCE OF SPECIFIED CURING TEMPERATURE
AND TECHNIQUES.-X
9. INSPECT ERECTION OF PRECAST CONCRETE MEMBERS.-X
10. INSPECT FORMWORK FOR SHAPE, LOCATION AND DIMENSIONS
OF THE CONCRETE MEMBER BEING FORMED.-X
ANCHORAGE TO CONCRETE:
ADHESIVE ANCHORS:
HILTI HIT-HY 200 PER ICC ESR-3187
HILTI HIT-RE 500 V3 PER ICC ESR-3814
SIMPSON AT-XP PER IAPMO ER-263
SIMPSON SET-XP PER ICC ESR-2508
MECHANICAL ANCHORS:
HILTI KWIK HUS PER ICC ESR-3027
HILTI KWIK BOLT-TZ EXPANSION ANCHORS PER ICC ESR-1917
SIMPSON TITEN HD PER ICC ESR-2713
SIMPSON STRONG BOLT-2 PER ICC ESR-3037
ADHESIVES:
HILTI HIT-HY 200 PER ICC ESR-3187
HILTI HIT-RE 500 V3 PER ICC ESR-3814
SIMPSON AT-XP PER IAPMO ER-263
SIMPSON SET-XP PER ICC ESR-2508
REBAR DOWELING TO CONCRETE:
SOILS (IBC TABLE 1705.6)
VERIFICATION AND INSPECTION
CONTINUOUS
SPECIAL
INSPECTION
PERIODIC
SPECIAL
INSPECTION
1. VERIFY MATERIALS BELOW SHALLOW FOUNDATIONS ARE
ADEQUATE TO ACHIEVE THE DESIGN BEARING CAPACITY.-X
2. VERIFY EXCAVATIONS ARE EXTENDED TO PROPER DEPTH
AND HAVE REACHED PROPER MATERIAL.-X
3. PERFORM CLASSIFICATION AND TESTING OF COMPACTED
FILL MATERIALS.-X
4. VERIFY USE OF PROPER MATERIALS, DENSITIES AND LIFT
THICKNESS DURING PLACEMENT AND COMPACTION OF
COMPACTED FILL.
X -
5. PRIOR TO PLACEMENT OF COMPACTED FILL, INSPECT
SUBGRADE AND VERIFY THAT SITE HAS BEEN PREPARED
PROPERLY.
-X
date
drawn
job no.
sheet number:
checked
sheet title:
THESE DOCUMENTS HAVE BEEN PRODUCED AS AN
INSTRUMENT OF SERVICE AND ARE INTENDED
SOLELY FOR THE PURPOSE OF CONSTRUCTING,
USING AND MAINTAINING THE PROJECT. SPOTLESS
WASH SOLUTIONS USA INC, AS THE ARCHITECT OF
RECORD FOR THE PROJECT RETAINS OWNERSHIP
OF THESE DOCUMENTS.
ANY USE OF THESE DOCUMENTS OR USE OF THIS
DESIGN, IDEAS OR CONCEPTS DESCRIBED HEREIN
IN WHOLE OR PART BY ANY MEANS WHATSOEVER IS
STRICTLY PROHIBITED EXCEPT BY WRITTEN
CONSENT OF SPOTLESS WASH SOLUTIONS USA INC.
REPRODUCTION OF THIS DOCUMENT IS STRICTLY
PROHIBITED EXCEPT BY WRITTEN CONSENT OF
SPOTLESS WASH SOLUTIONS USA INC.
COPYRIGHT 2021
SPOTLESS WASH SOLUTIONS USA INC.
SP
O
T
L
E
S
S
W
A
S
H
S
O
L
U
T
I
O
N
S
U
S
A
I
N
C
TW
I
N
F
A
L
L
S
,
I
D
A
H
O
8
3
3
0
3
PH
.
(
2
0
8
)
8
4
1
-
4
5
2
4
issued for
revisions:
stamp
PO
B
O
X
5
4
5
6
NI
T
R
O
C
A
R
W
A
S
H
RE
X
B
U
R
G
,
I
D
13
7
1
N
2
N
D
E
RE
X
B
U
R
G
,
I
D
8
3
4
4
0
-
-
-
-
-
GENERAL
STRUCTURAL
NOTES
S1.0
PROJECT MANAGER:CAD OPERATOR:JOB NO.:
fax: 208.227.8405
1020 E. Lincoln Road
Idaho Falls, ID 83401
Structural Engineering
phone: 208.227.8404
This drawing is the property of FROST Structural Engineering, Inc. Legally, the drawing can NOT be copied in whole or in pieces. It is only to be used for the project and site
specifically identified hereon and is not to be used on any other project. Contractor shall carefully review all dimensions, details, and conditions and report at once any error,
inconsistency or omission discovered before construction. The contractor assumes full liability for deviations from the intent of these plans.
contact@frost-structural.com
AVBBCIF-381
2.SITE PREPARATION AND GRADING REQUIREMENTS OF THE SOIL REPORT AND ANY
ADDENDUM'S SHALL BE COMPLETED PRIOR TO CONSTRUCTION OF FOUNDATIONS.
ANY TESTS OR INSPECTIONS REQUIRED BY THE SOIL REPORT SHALL BE PERFORMED
PRIOR TO PLACEMENT OF FOUNDATION REINFORCING STEEL OR CONCRETE.
ALTERATIONS TO SITE PREPARATION OR GRADING SHALL BE REPORTED TO THE
GEOTECHNICAL ENGINEER PRIOR TO FOUNDATION CONSTRUCTION.
3.A ONE-THIRD INCREASE IN BEARING PRESSURES IS ALLOWED WITH SEISMIC OR
WIND LOAD COMBINATIONS. LATERAL BEARING AND LATERAL SLIDING RESISTANCE
MAY BE COMBINED.
4.ALL FOUNDATIONS SHALL BEAR ON COMPACTED ENGINEERED FILL OR COMPETENT
NATIVE SOIL SUBBASE COMPACTED TO 95% DRY DENSITY (STANDARD PROCTOR).
GRADE IS DEFINED AS LOWEST ADJACENT GRADE WITHIN 5 FEET OF THE BUILDING
FOR PERIMETER FOOTINGS. WHERE EXTERIOR PAVING OR CONCRETE IS DIRECTLY
ADJACENT TO BUILDING, GRADE IS DEFINED AS TOP OF EXTERIOR PAVING AT LEAST
5 FEET FROM BUILDING. CONCRETE FOOTING EXCAVATIONS SHALL BE CLEAN AND
FREE OF LOOSE DEBRIS OR UN-COMPACTED MATERIAL AT TIME OF CONCRETE
PLACEMENT.
5.CONCRETE SLABS ON GRADE SHALL BE SUPPORTED ON A 4 INCH (MIN) LAYER OF
FREE-DRAINING GRANULAR MAT (DRAINAGE FILL COURSE). THE MAT SHOULD
CONSIST OF A WELL GRADED SAND AND GRAVEL MIXTURE WITH MAXIMUM 3/4-INCH
CRUSHED AGGREGATE. THE GRANULAR MAT SHOULD BE COMPACTED TO NO LESS
THAN 95% OF THE MAXIMUM DRY DENSITY AS DETERMINED BY ASTM D1557
6.BACKFILL AGAINST RESTRAINED WALLS SHALL NOT BE PLACED UNTIL AFTER THE
WALLS ARE SUPPORTED BY THE COMPLETION OF INTERIOR FLOOR SYSTEMS AND
CONCRETE OR GROUT STRENGTH HAS REACHED THE 28 DAY STRENGTH LISTED
THE SOIL DESIGN VALUES FOR THE FOUNDATION ARE:
ALLOWABLE BEARING PRESSURE 2500 PSF
ALLOWABLE LATERAL BEARING PRESSURE 346 PSF/FT
ALLOWABLE LATERAL SLIDING COEFFICIENT .35
FOUNDATION BEARING DEPTH
36" BELOW FINISHED GRADE
3.A ONE-THIRD INCREASE IN BEARING PRESSURES IS ALLOWED WITH SEISMIC OR
WIND LOAD COMBINATIONS. LATERAL BEARING AND LATERAL SLIDING RESISTANCE
MAY BE COMBINED.
4.ALL FOUNDATIONS SHALL BEAR ON COMPACTED ENGINEERED FILL OR COMPETENT
NATIVE SOIL SUBBASE COMPACTED TO 95% DRY DENSITY (STANDARD PROCTOR).
GRADE IS DEFINED AS LOWEST ADJACENT GRADE WITHIN 5 FEET OF THE BUILDING
FOR PERIMETER FOOTINGS. WHERE EXTERIOR PAVING OR CONCRETE IS DIRECTLY
ADJACENT TO BUILDING, GRADE IS DEFINED AS TOP OF EXTERIOR PAVING AT LEAST
5 FEET FROM BUILDING. CONCRETE FOOTING EXCAVATIONS SHALL BE CLEAN AND
FREE OF LOOSE DEBRIS OR UN-COMPACTED MATERIAL AT TIME OF CONCRETE
PLACEMENT.
5.CONCRETE SLABS ON GRADE SHALL BE SUPPORTED ON A 4 INCH (MIN) LAYER OF
FREE-DRAINING GRANULAR MAT (DRAINAGE FILL COURSE). THE MAT SHOULD
CONSIST OF A WELL GRADED SAND AND GRAVEL MIXTURE WITH MAXIMUM 3/4-INCH
CRUSHED AGGREGATE. THE GRANULAR MAT SHOULD BE COMPACTED TO NO LESS
THAN 95% OF THE MAXIMUM DRY DENSITY AS DETERMINED BY ASTM D1557
6.BACKFILL AGAINST RESTRAINED WALLS SHALL NOT BE PLACED UNTIL AFTER THE
WALLS ARE SUPPORTED BY THE COMPLETION OF INTERIOR FLOOR SYSTEMS AND
CONCRETE OR GROUT STRENGTH HAS REACHED THE 28 DAY STRENGTH LISTED
BELOW.
THE SOIL DESIGN VALUES FOR THE FOUNDATION ARE:
ALLOWABLE BEARING PRESSURE 2500 PSF
ALLOWABLE LATERAL BEARING PRESSURE 346 PSF/FT
ALLOWABLE LATERAL SLIDING COEFFICIENT .35
FOUNDATION BEARING DEPTH
36" BELOW FINISHED GRADE
7. GRADE SLOPE AWAY FROM BUILDING 6" IN FIRST 10'.
SPECIAL INSPECTOR:
Atlas Technical Consultants
17778 E. Precision Dr.
Idaho Falls ID 83401
208-529-8242
NOT
F
O
R
C
O
N
S
T
R
U
C
T
I
O
N
KEYNOTES:
1.FINISHED GRADE WHERE OCCURS
2.DO NOT EXCAVATE A TRENCH
CLOSER THAN A 45 DEGREE ANGLE
TO BELOW BOTTOM FOOTING OR
FOUNDATION
3.BOTTOM OF CONCRETE FOOTING
4.BOTTOM OF TRENCH
NOTE:
A.DO NOT UNDERCUT EXISTING
FOOTINGS
B.NO PIPE OR OTHER UTILITIES SHALL
PASS THRU WALL FOOTINGS OR
UNDER COLUMN FOOTINGS
1
1
1
2
3
4
FOR CONSTRUCTION ABOVE
FOOTING, SEE DETAILS.
T1 TRENCH PARALLEL TO CONTINUOUS STRAP FOOTING
TD01 NO SCALE
KEYNOTES:
1.CONCRETE FOOTING
2.SLEEVE - PROVIDE 12" MINIMUM
CLEARANCE AROUND PIPE OR
CONDUIT
3.PIPE OR CONDUIT
4.CONCRETE FILL TO BE PLACED
BEFORE FOOTING IS POURED -
FORM SAME AS FOOTING AND
POUR FULL WIDTH OF PIPE TRENCH
5.STEM WALL
NOTE:
A.NO PIPE SHALL PASS THRU
FOOTING OR UNDER COLUMN
FOOTINGS. FOR TRENCHES
GREATER THAN 3'-6" BELOW
BOTTOM OF FOOTING, SEE PIPE
PASSING BELOW WALL FOOTING
DETAIL.
1
2
3
4
5
5
4
2
1
3
T2 PIPE PASSING UNDER WALL FOOTING IN SHALLOW TRENCH
TD02 NO SCALE
6"
M
I
N
8"
M
I
N
3'
-
0
"
M
A
X
8" MIN
A
SECTIONA
KEYNOTES:
1.STEM WALL
2.CONCRETE FOOTING
3.1'-6" MAXIMUM - WHERE TRENCH
EXCEEDS 1'-6" NOTIFY STRUCTURAL
ENGINEER PRIOR TO PLACEMENT
OF FOOTINGS
4.BACKFILL AND RECOMPACT
TRENCH PER SOILS REPORT AND
SPECIFICATIONS
5.BOTTOM OF TRENCH
NOTE:
A.DO NOT UNDERCUT EXISTING
FOOTINGS
B.NO PIPES OR OTHER UTILITIES
SHALL PASS THRU WALL FOOTINGS
OR UNDER COLUMN FOOTINGS
1
5
4
3
2
3'
-
1
"
O
R
G
R
E
A
T
E
R
FOR CONSTRUCTION ABOVE
FOOTING, SEE DETAILS.
T3 PIPE PASSING BELOW FOOTING IN DEEP TRENCH
TD03 NO SCALE
KEYNOTES:
1.SLOPED FINISH GRADE
2.MINIMUM FOOTING DEPTH PER
G.S.N. - 12" MINIMUM
3.DEEPEN FOOTING AS REQUIRED TO
ACCOUNT FOR SLOPED GRADE
4.CONCRETE FOOTING
NOTE:
A.FOR ADDITIONAL INFORMATION,
SEE PLANS AND DETAILS
1
4
3
2
5'-0"
T4 TYPICAL DETAIL FOR FOUNDATION EMBEDMENT
TD04 NO SCALE
KEYNOTES:
1.CORNER DOWELS TO MATCH
HORIZONTAL REINFORCEMENT
2.CONCRETE WALL WITH
REINFORCEMENT
18" MIN LAP
SPLICE (TYP)
T5 TYPICAL CONCRETE CORNER
TD05 NO SCALE
2
1
KEYNOTES:
1.CONCRETE SLAB ON GRADE
2.CONT KEYED JOINT
3.SAWCUT 18" WIDE x 14 SLAB
THICKNESS IN DEPTH - CUT SHALL
BE MADE SOON ENOUGH TO
PREVENT SHRINKAGE CRACKING,
BUT NOT SO SOON AS TO CAUSE
SPALLING OF THE CONCRETE
WHILE SAWING. WORK MUST BE
COMPLETE WITHIN 16 HOURS OF
CONCRETE PLACEMENT.
NOTE:
A.KEYED JOINTS NEED ONLY OCCUR
AT EXPOSED EDGES DURING
PLACEMENT UNLESS SPECIFICALLY
NOTED ON THE PLANS.
B."TOOL WET JOINT", "ZIP STRIP", ETC
SHALL MATCH SAWCUT
REQUIREMENTS
1
2
3
1
12"6"6"12"
X SAWCUT JOINT
X KEYED JOINT
T6 CONTROL JOINTS IN CONCRETE SLAB ON GRADE
TD07 NO SCALE
6 MIN
BAR OFFSET
BAR CLEARANCE SPLICE DETAIL
BEND & HOOK DETAILS
COLUMN TIES BEAM STIRRUPS
"d"
45°
"d"
"d"
1
2
4
5
6
10
9
8
7
3
1
5
5
9
10
8
KEYNOTES:
1.LAP - SEE G.S.N.
2.MAXIMUM 15 LAP BUT NOT MORE
THAN 6"
3.WIRE TIES
4.1d (1" MINIMUM)
5.RADIUS = 3d FOR BARS NOT OVER
#8; 4d FOR #9, #10, AND #1 BARS; 5d
FOR #14 AND #18 BARS, 5d FOR ALL
GRADE 40 BARS WITH 180 DEGREE
HOOK
6.4D (4" MINIMUM)
7.12d (90 DEGREE HOOK)
8.6d (4" MINIMUM)
9.135 DEGREE BEND
10.BEND AROUND 112" PIN FOR #3
BARS. BEND AROUND 2" PIN FOR #4
BARS. BEND AROUND 212" PIN FOR
#5 BARS.
T7 TYPICAL REINFORCING DETAILS
TD10 NO SCALE
NOTES:
1.TOP BARS ARE ANY HORIZONTAL BARS PLACED SO THAT MORE THAN 12" OF FRESH CONCRETE IS CAST IN THE
MEMBER BELOW THE REINFORCEMENT.
2.UNLESS NOTED OTHERWISE, LAP SPLICES IN CONCRETE BEAMS, SLABS AND WALLS SHALL BE CLASS "B" TENSION LAP
SPLICES.
BAR
SIZE
CLASS B TENSION SPLICE LENGTHS
f'c = 3,000 PSI f'c = 4,000 PSI f'c = 5,000 PSI
HOIRZONTAL
BARS W/ >12" OF
CONC. BELOW
VERTICAL AND
BOTTOM
HORIZONTAL
BARS
HOIRZONTAL
BARS W/ >12" OF
CONC. BELOW
VERTICAL AND
BOTTOM
HORIZONTAL
BARS
HOIRZONTAL
BARS W/ >12" OF
CONC. BELOW
VERTICAL AND
BOTTOM
HORIZONTAL
BARS
#3 12"12"12"12"12"12"
#4 19"15"17"13"15"12"
#5 29"23"26"20"23"18"
#6 32"25"28"21"25"19"
#7 54"41"47"36"42"32"
#8 70"54"61"47"54"42"
#9 89"68"77"59"69"53"
#10 112"87"97"75"87"67"
T9 STEEL REINFORCING LAP SPLICES IN CONCRETE
TD14 NO SCALE
T8 TYPICAL PIPE THROUGH STEM WALL
TD61 NO SCALE
NOTE:
A.NO PIPE SHALL PASS THROUGH
FOOTINGS OR UNDER COLUMN
FOOTINGS. FOR ADDITIONAL
INFORMATION SEE PLANS AND
DETAILS
B.MULTIPLE PIPES/CONDUIT SLEEVES
ALLOWED PROVIDED SLEEVES ARE
SPACED W/ MINIMUM OF 2x SLEEVE
DIAMETER BETWEEN SLEEVES
C.SLEEVES SHALL NOT OCCUR
WITHIN 12" OF POINT LOADS OR
HOLDOWN ANCHORS
1'
-
0
"
MI
N
1
7
3
4
5
6
KEYNOTES:
1.WALL AS OCCURS, SEE PLAN
2.SIDEWALK, PAVEMENT, OR FINISH
GRADE PER ARCH
3.SLEEVE, 8"Ø MAX, PROVIDE 12"
MINIMUM CLEARANCE AROUND
PIPE-CONDUIT
4.CONCRETE WALL, SEE PLAN
5.CONCRETE FOOTING, SEE PLAN
6.COMPACTED SUB-GRADE BELOW
FOOTING, SEE PLAN
7.PIPE OR CONDUIT
8.SIDEWALK, PAVEMENT, OR FINISH
GRADE PER ARCH
9.PROVIDE DRAINAGE SYSTEM
BEHIND WALL, SEE TYPICAL DETAIL
10.FILTER FABRIC WRAPPED AROUND
MIN 12"x12" OF GRAVEL BACKFILL
22
KEYNOTES:
1.CONCRETE WALL, SEE PLAN
2.3 1
2" STEEL STUD (33 MILS MIN
THICKNESS) PLANT WALL PER
ARCH, ATTACH W/ .145"DIA MIN
SHOT PIN AT 16" O.C.
3.3 1
2" STUD BLOCKING TOP AND
BOTTOM AND AT 16" O.C.
REMAINDER
4.7
16" SHEATHING, ATTACH W/ #8 SELF
TAPPING SCREWS AT 12" O.C.
5.SIDEWALK, PAVEMENT, OR FINISH
GRADE PER ARCH
1"
T10 TYPICAL PLANT WALL ATTACHMENT
TD05 NO SCALE
3
2
4
1
3
T11 TYPICAL SPLICE IN CONTINUOUS STEEL CHORD/EDGE ANGLE
TD_SF15 NO SCALE
KEYNOTES:
1.STEEL CHORD/EDGE ANGLE - FOR SIZE
AND LOCATION, SEE PLAN
2.8" LONG x 2"x3 8" THICK STEEL PLATES
1/2" M
A
X
1/4
TYP
1
1
2
2
5
PRO
F
E
S
S
I
O
N
A
L
EN GI N E E R
ST ATE
O
F
I
D
A
H
O
A
1/
7
/
2
2
14
1
3
4
D VID
B
.
P
O
R
T
E
R
L
I
C
E
N
SED
date
drawn
job no.
sheet number:
checked
sheet title:
THESE DOCUMENTS HAVE BEEN PRODUCED AS AN
INSTRUMENT OF SERVICE AND ARE INTENDED
SOLELY FOR THE PURPOSE OF CONSTRUCTING,
USING AND MAINTAINING THE PROJECT. SPOTLESS
WASH SOLUTIONS USA INC, AS THE ARCHITECT OF
RECORD FOR THE PROJECT RETAINS OWNERSHIP
OF THESE DOCUMENTS.
ANY USE OF THESE DOCUMENTS OR USE OF THIS
DESIGN, IDEAS OR CONCEPTS DESCRIBED HEREIN
IN WHOLE OR PART BY ANY MEANS WHATSOEVER IS
STRICTLY PROHIBITED EXCEPT BY WRITTEN
CONSENT OF SPOTLESS WASH SOLUTIONS USA INC.
REPRODUCTION OF THIS DOCUMENT IS STRICTLY
PROHIBITED EXCEPT BY WRITTEN CONSENT OF
SPOTLESS WASH SOLUTIONS USA INC.
COPYRIGHT 2021
SPOTLESS WASH SOLUTIONS USA INC.
SP
O
T
L
E
S
S
W
A
S
H
S
O
L
U
T
I
O
N
S
U
S
A
I
N
C
TW
I
N
F
A
L
L
S
,
I
D
A
H
O
8
3
3
0
3
PH
.
(
2
0
8
)
8
4
1
-
4
5
2
4
issued for
revisions:
stamp
PO
B
O
X
5
4
5
6
NI
T
R
O
C
A
R
W
A
S
H
RE
X
B
U
R
G
,
I
D
13
7
1
N
2
N
D
E
RE
X
B
U
R
G
,
I
D
8
3
4
4
0
-
-
-
-
-
TYPICAL
DETAILS
S1.1
PROJECT MANAGER:CAD OPERATOR:JOB NO.:
fax: 208.227.8405
1020 E. Lincoln Road
Idaho Falls, ID 83401
Structural Engineering
phone: 208.227.8404
This drawing is the property of FROST Structural Engineering, Inc. Legally, the drawing can NOT be copied in whole or in pieces. It is only to be used for the project and site
specifically identified hereon and is not to be used on any other project. Contractor shall carefully review all dimensions, details, and conditions and report at once any error,
inconsistency or omission discovered before construction. The contractor assumes full liability for deviations from the intent of these plans.
contact@frost-structural.com
AVBBCIF-381
NOT
F
O
R
C
O
N
S
T
R
U
C
T
I
O
N
1
1
2
2
3
3
4
4
5
5
DD
CC
BB
AA
4" CONCRETE SLAB ON GRADE W/
#3 AT 24" O.C. EACH WAY
CENTERED IN SLAB THICKNESS
OVER COMPACTED FILL.
(SEE GSN)
PROVIDE SLAB JOINTS PER
TYPICAL DETAIL WITHIN 16 HOURS
OF BATCH TIME
FINISH FLOOR = VARIES
CONCRETE SLAB ON GRADE
6" CONCRETE SLAB ON GRADE W/
#3 AT 24" O.C. EACH WAY
CENTERED IN SLAB THICKNESS
OVER COMPACTED FILL.
(SEE GSN)
PROVIDE SLAB JOINTS PER
TYPICAL DETAIL WITHIN 16 HOURS
OF BATCH TIME
FINISH FLOOR = VARIES
CONCRETE SLAB ON GRADE
WF24
WF24
WF24
WF
2
4
WF
2
4
WF24
WF24
WF
2
4
A
F36
WF
2
4
WF
2
4
WF
2
4
WF
2
4
WF24
101 101
108
105
108
105
109
104 107
106
102 103
103
103102
103102103102102106103
103
102
106
1
1
1
1
1
WF
2
4
A
WF
2
4
A
2
2
2
TYP TOF=97'-10"
TYP TOF=97'-10"
WF
2
4
WF
2
4
TYP TOF=97'-10"
TYP TOF=97'-10"
TYP TOF=97'-10"
D
I
C
H
A
B
K
J
G
F
E
137'-0"
24'-0"111'-0"
14'-0"8'-0"2'-0"3'-4"43'-1"6'-0"5'-2"3'-4"34'-0"10'-0"4'-0"
35
'
-
0
"
125'-0"
12'-0"
6'-81
2"2'-0"
17
'
-
0
"
23
'
-
0
"
5'
-
0
"
12
'
-
0
"
3'
-
0
"
4'
-
0
"
12
'
-
0
"
4'
-
0
"
2'-5"
2'-5"
3'-6"3'-4"87'-3"3'-4"23'-0"
2'-0"
10
'
-
0
"
3'
-
8
"
6'
-
4
"
20
'
-
0
"
15
'
-
0
"
7'
-
1
0
1 2"
3'
-
4
"
3'
-
9
1 2"
4'
-
9
"
10
'
-
6
"
4'
-
9
"
5'
-
0
"
15
'
-
0
"
5'
-
0
"
20
'
-
0
"
40
'
-
0
"
102'-8"22'-4"
3'-31
2"
4'
-
0
"
4'
-
0
"
20
'
-
0
"
4'-7"
4'
-
9
"
10
'
-
6
"
4'
-
9
"
8'-0"12'-0"105'-0"
2'-1"
SCALE:
FOUNDATION PLAN
3/16" = 1'-0"
PRO
F
E
S
S
I
O
N
A
L
EN G I N E E R
S T ATE
O
F
I
D
A
H
O
A
1/
7
/
2
2
14
1
3
4
D VID
B
.
P
O
R
T
E
R
L
I
C
E
N
SED
FOOTING SCHEDULE
NOTES:
1. FOR CONSTRUCTION ABOVE FOOTING, SEE DETAILS.
2. FOR MINIMUM CLEARANCE (CLR) OF REINFORCING, SEE GENERAL STRUCTURAL NOTES (GSN).
MARK LENGTH WIDTH THICKN
ESS FOOTING REINFORCING REMARKS
F36 36"36"10"(4) #4 CONT TOP & BOTTOM ---
WF24 CONT 24"10"(2) #4 CONT BOTTOM
WF24A CONT 24"10"(3) #4 CONT TOP & BOTTOM ---
STRIP FOOTING
1.PRE-FINISHED METAL PANEL PER ARCH
2.TURN DOWN SLAB TO BE USED AT
OPENING, SEE DETAIL 106
PLAN KEYNOTESX
A.VERIFY ALL DIMENSIONS WITH ALL ARCHITECTURAL
DRAWINGS.
B.ALL SCHEDULED MARK DESIGNATIONS MAY NOT
NECESSARILY BE FOUND ON THIS PLAN. SCHEDULES ARE
TYPICAL TO THIS PROJECT.
C.THE DEPTH OF FOOTING DIMENSION INDICATED IN THE G.S.N.
IS A MINIMUM. FOUNDATION CONTRACTOR SHALL
COORDINATE WITH THE SOILS REPORT AND OTHER TRADES
TO INSURE THAT THESE MINIMUMS ARE SUFFICIENT FOR THE
WORK. SEE TYPICAL DETAILS FOR ADDITIONAL
REQUIREMENTS.
D. WALLS WITH SOLID LINES DESIGNATED
STRUCTURAL (BEARING) WALLS.
E. WALLS WITH DASHED LINES DESIGNATE
NON-STRUCTURAL (NON-BEARING) WALLS.
F.W1, W2, ETC. - AS SHOWN ON PLAN INDICATES CONCRETE OR
MASONRY WALLS. SEE WALL SCHEDULE FOR ADDITIONAL
INFORMATION.
G.WF18, WF24, ETC. - AS SHOWN ON PLAN INDICATES A
CONTINUOUS WALL FOOTING. SEE FOOTING SCHEDULE FOR
ADDITIONAL INFORMATION.
H.F36, F48, ETC. - AS SHOWN ON PLAN INDICATES A CONCRETE
FOOTING. SEE FOOTING SCHEDULE FOR ADDITIONAL
INFORMATION.
I.VERIFY EXACT SIZE AND LOCATION OF DEPRESSED AND/OR
RAISED SLABS WITH ARCHITECTURAL DRAWINGS.
J.FOR SIDEWALK AND LANDING LOCATIONS, SEE
ARCHITECTURAL DRAWINGS.
K.VERIFY EXACT SIZE AND LOCATION OF OPENINGS IN PRECAST
CONCRETE WALL PANELS WITH ARCHITECTURAL DRAWINGS.
FOUNDATION PLAN NOTES
NORTH
date
drawn
job no.
sheet number:
checked
sheet title:
THESE DOCUMENTS HAVE BEEN PRODUCED AS AN
INSTRUMENT OF SERVICE AND ARE INTENDED
SOLELY FOR THE PURPOSE OF CONSTRUCTING,
USING AND MAINTAINING THE PROJECT. SPOTLESS
WASH SOLUTIONS USA INC, AS THE ARCHITECT OF
RECORD FOR THE PROJECT RETAINS OWNERSHIP
OF THESE DOCUMENTS.
ANY USE OF THESE DOCUMENTS OR USE OF THIS
DESIGN, IDEAS OR CONCEPTS DESCRIBED HEREIN
IN WHOLE OR PART BY ANY MEANS WHATSOEVER IS
STRICTLY PROHIBITED EXCEPT BY WRITTEN
CONSENT OF SPOTLESS WASH SOLUTIONS USA INC.
REPRODUCTION OF THIS DOCUMENT IS STRICTLY
PROHIBITED EXCEPT BY WRITTEN CONSENT OF
SPOTLESS WASH SOLUTIONS USA INC.
COPYRIGHT 2021
SPOTLESS WASH SOLUTIONS USA INC.
SP
O
T
L
E
S
S
W
A
S
H
S
O
L
U
T
I
O
N
S
U
S
A
I
N
C
TW
I
N
F
A
L
L
S
,
I
D
A
H
O
8
3
3
0
3
PH
.
(
2
0
8
)
8
4
1
-
4
5
2
4
issued for
revisions:
stamp
PO
B
O
X
5
4
5
6
NI
T
R
O
C
A
R
W
A
S
H
RE
X
B
U
R
G
,
I
D
13
7
1
N
2
N
D
E
RE
X
B
U
R
G
,
I
D
8
3
4
4
0
-
-
-
-
-
FOUNDATION
PLAN
S2.0
PROJECT MANAGER:CAD OPERATOR:JOB NO.:
fax: 208.227.8405
1020 E. Lincoln Road
Idaho Falls, ID 83401
Structural Engineering
phone: 208.227.8404
This drawing is the property of FROST Structural Engineering, Inc. Legally, the drawing can NOT be copied in whole or in pieces. It is only to be used for the project and site
specifically identified hereon and is not to be used on any other project. Contractor shall carefully review all dimensions, details, and conditions and report at once any error,
inconsistency or omission discovered before construction. The contractor assumes full liability for deviations from the intent of these plans.
contact@frost-structural.com
AVBBCIF-381
NOT
F
O
R
C
O
N
S
T
R
U
C
T
I
O
N
1
1
2
2
3
3
4
4
5
5
DD
CC
BB
AA
202202
201
203
203
210
205
202
203
8" PRECAST HOLLOW CORE PANELS AT 48" O.C. (UNO)
8" PRECAST HOLLOW CORE PANELS AT 48" O.C. (UNO)
1
1
2
2
205
204
201
201
204
3
3
28.5 KIPS (STRENGTH)
TYP
208
209
206
TYP
208
207
D
I
C
H
A
B
K
J
G
F
(4) #4 DOWELS EVENLY
SPACED AT PANEL JOINT
(3) #4 DOWELS EVENLY
SPACED AT PANEL JOINT (2) #4 DOWELS AT 1/3 POINTSTYP
208 (3) #4 DOWELS EVENLY
SPACED AT PANEL JOINT (4) #4 DOWELS EVENLY
SPACED AT PANEL JOINT
(4) #4 DOWELS EVENLY
SPACED AT PANEL JOINT
(3) #4 DOWELS EVENLY
SPACED AT PANEL JOINT(2) #4 DOWELS AT 1/3 POINTS(4) #4 DOWELS EVENLY
SPACED AT PANEL JOINT
(3) #4 DOWELS EVENLY
SPACED AT PANEL JOINTE
SCALE:
ROOF FRAMING PLAN
3/16" = 1'-0"
PRO
F
E
S
S
I
O
N
A
L
EN G I N E E R
S T ATE
O
F
I
D
A
H
O
A
1/
7
/
2
2
14
1
3
4
D VID
B
.
P
O
R
T
E
R
L
I
C
E
N
SED
NORTH
1.ROOF PANEL LESS THAN 48" WIDE
2.FINAL PANEL LAYOUT BY PRECAST MANUFACTURER AND TO
BE REVIEWED BY FROST STRUCTURAL ENGINEERING
3.PRE-FINISHED METAL PANEL PER ARCH
PLAN KEYNOTESX ROOF FRAMING PLAN NOTES
A.VERIFY ALL DIMENSIONS WITH ALL ARCHITECTURAL
DRAWINGS.
B.ALL SCHEDULED MARK DESIGNATIONS MAY NOT NECESSARILY
BE FOUND ON THIS PLAN. SCHEDULES ARE TYPICAL TO THIS
PROJECT.
C.IF DOUBLE TOP PLATE IS NOTCHED, STEPPED OR BROKEN,
PROVIDE A SIMPSON MSTC40 STRAP AT DISCONTINUITY.
D.TYPICAL BEARING WALL FRAMING SHALL BE 8" PRECAST
CONCRETE WALLS.
E. WALLS WITH SOLID LINES DESIGNATED
STRUCTURAL (BEARING) WALLS.
F. WALLS WITH DASHED LINES DESIGNATE
NON-STRUCTURAL (NON-BEARING) WALLS.
G.FOR CLARITY, DETAILS MAY SHOW ONLY ONE SIDE OF
FRAMING CONDITION.
H.FOR CLARITY, ALL ROOF OPENINGS MAY NOT BE SHOWN ON
THE ROOF FRAMING PLAN. FOR EXACT SIZE, NUMBER AND
LOCATION OF OPENINGS, SEE ARCHITECTURAL, MECHANICAL,
PLUMBING, AND ELECTRICAL DRAWINGS. FOR FRAMING AT
OPENINGS, SEE TYPICAL DETAILS.
I. INDICATES HVAC EQUIPMENT ON ROOF OR IN
ATTIC SPACE. SEE TYPICAL DETAILS FOR
FRAMING INFORMATION.
J.VERIFY EXACT SIZE AND WEIGHT OF EQUIPMENT ON ROOF
WITH MECHANICAL DRAWINGS.
PROJECT MANAGER:CAD OPERATOR:JOB NO.:
fax: 208.227.8405
1020 E. Lincoln Road
Idaho Falls, ID 83401
Structural Engineering
phone: 208.227.8404
This drawing is the property of FROST Structural Engineering, Inc. Legally, the drawing can NOT be copied in whole or in pieces. It is only to be used for the project and site
specifically identified hereon and is not to be used on any other project. Contractor shall carefully review all dimensions, details, and conditions and report at once any error,
inconsistency or omission discovered before construction. The contractor assumes full liability for deviations from the intent of these plans.
contact@frost-structural.com
AVBBCIF-381
date
drawn
job no.
sheet number:
checked
sheet title:
THESE DOCUMENTS HAVE BEEN PRODUCED AS AN
INSTRUMENT OF SERVICE AND ARE INTENDED
SOLELY FOR THE PURPOSE OF CONSTRUCTING,
USING AND MAINTAINING THE PROJECT. SPOTLESS
WASH SOLUTIONS USA INC, AS THE ARCHITECT OF
RECORD FOR THE PROJECT RETAINS OWNERSHIP
OF THESE DOCUMENTS.
ANY USE OF THESE DOCUMENTS OR USE OF THIS
DESIGN, IDEAS OR CONCEPTS DESCRIBED HEREIN
IN WHOLE OR PART BY ANY MEANS WHATSOEVER IS
STRICTLY PROHIBITED EXCEPT BY WRITTEN
CONSENT OF SPOTLESS WASH SOLUTIONS USA INC.
REPRODUCTION OF THIS DOCUMENT IS STRICTLY
PROHIBITED EXCEPT BY WRITTEN CONSENT OF
SPOTLESS WASH SOLUTIONS USA INC.
COPYRIGHT 2021
SPOTLESS WASH SOLUTIONS USA INC.
SP
O
T
L
E
S
S
W
A
S
H
S
O
L
U
T
I
O
N
S
U
S
A
I
N
C
TW
I
N
F
A
L
L
S
,
I
D
A
H
O
8
3
3
0
3
PH
.
(
2
0
8
)
8
4
1
-
4
5
2
4
issued for
revisions:
stamp
PO
B
O
X
5
4
5
6
NI
T
R
O
C
A
R
W
A
S
H
RE
X
B
U
R
G
,
I
D
13
7
1
N
2
N
D
E
RE
X
B
U
R
G
,
I
D
8
3
4
4
0
-
-
-
-
-
ROOF
FRAMING
PLAN
S2.1
NOT
F
O
R
C
O
N
S
T
R
U
C
T
I
O
N
KEYNOTES:
1.8" CONCRETE PRECAST WALL
PANEL, SEE PLAN
2.CONCRETE SLAB ON GRADE, SEE
PLAN
3.EMBED CHANNEL BY PRECAST
4.3 8"x3"x0'-8" PLATE EACH SIDE
5.112" SHIM AND GROUT
6.12"x12"x1'-0" EMBED PLATE W/ (4) 12"Ø
x 5" LONG HEADED STUDS
7.COMPACTED SUB-GRADE BELOW
FOOTING, SEE PLAN
8.CONCRETE FOOTING, SEE PLAN
9.MINIMUM FOOTING DEPTH, SEE GSN
10.FINISH GRADE PER ARCH
11.GROUT OVER ALL EXPOSED STEEL
BELOW GRADE
101 CONCRETE PRECAST WALL AT FOUNDATION
NO SCALE
102 CONCRETE PRECAST WALL AT FOUNDATION
NO SCALE
3"
CLR
3"
CL
R
7
8
1
9
10
3
4
5
6
2
KEYNOTES:
1.PRECAST WALL PANEL BEYOND, SEE
PLAN
2.CONCRETE SLAB ON GRADE, SEE
PLAN
3.EMBED CHANNEL BY PRECAST
4.3 8"x3"x0'-8" PLATE EACH SIDE
5.112" SHIM AND GROUT
6.12"x12"x1'-0" EMBED PLATE W/ (4) 12"Ø
x 5" LONG HEADED STUDS
7.COMPACTED SUB-GRADE BELOW
FOOTING, SEE PLAN
8.CONCRETE FOOTING, SEE PLAN
9.MINIMUM FOOTING DEPTH, SEE GSN
10.FINISH GRADE PER ARCH
11.8" CONCRETE PRECAST WALL
PANEL, SEE PLAN
12.#4 x 2'-0" DRILL AND EPOXY PER GSN
13.GROUT OVER ALL EXPOSED STEEL
BELOW GRADE
3"
CLR
3"
CL
R
7
8
1
9
10
3
4
5
6
2
11
12
KEYNOTES:
1.8" CONCRETE PRECAST WALL
PANEL, SEE PLAN
2.CONCRETE SLAB ON GRADE, SEE
PLAN
3.EMBED CHANNEL BY PRECAST
4.3 8"x3"x0'-8" PLATE EACH SIDE
5.112" SHIM AND GROUT
6.12"x12"x1'-0" EMBED PLATE W/ (4) 12"Ø
x 5" LONG HEADED STUDS
7.COMPACTED SUB-GRADE BELOW
FOOTING, SEE PLAN
8.CONCRETE FOOTING, SEE PLAN
9.MINIMUM FOOTING DEPTH, SEE GSN
10.FINISH GRADE PER ARCH
11.NON-STRUCTURAL FURRED OUT
WOOD STUD WALL
12.GROUT OVER ALL EXPOSED STEEL
BELOW GRADE
103 CONCRETE PRECAST WALL AT FOUNDATION
NO SCALE
3"
CLR
3"
CL
R
7
8
1
9
10
3
4
5
6
2
11
KEYNOTES:
1.8" CONCRETE PRECAST WALL
PANEL, SEE PLAN
2.CONCRETE SLAB ON GRADE, SEE
PLAN
3.EMBED CHANNEL BY PRECAST
4.3 8"x3"x0'-8" PLATE EACH SIDE
5.112" SHIM AND GROUT
6.12"x12"x1'-0" EMBED PLATE W/ (4) 12"Ø
x 5" LONG HEADED STUDS
7.COMPACTED SUB-GRADE BELOW
FOOTING, SEE PLAN
8.CONCRETE FOOTING, SEE PLAN
9.GROUT OVER ALL EXPOSED STEEL
BELOW GRADE
105 CONCRETE PRECAST WALL AT FOUNDATION
NO SCALE
3"
CLR
3"
CL
R
7
8
1
2
3
4
5
6
2
KEYNOTES:
1.8" CONCRETE PRECAST WALL
PANEL, SEE PLAN
2.CONCRETE SLAB ON GRADE, SEE
PLAN
3.EMBED CHANNEL BY PRECAST
4.3 8"x3"x0'-8" PLATE EACH SIDE
5.112" SHIM AND GROUT
6.12"x12"x1'-0" EMBED PLATE W/ (4) 12"Ø
x 5" LONG HEADED STUDS
7.COMPACTED SUB-GRADE BELOW
FOOTING, SEE PLAN
8.CONCRETE FOOTING, SEE PLAN
9.NON-STRUCTURAL FURRED OUT
WOOD STUD WALL
10.GROUT OVER ALL EXPOSED STEEL
BELOW GRADE
104 CONCRETE PRECAST WALL AT FOUNDATION
NO SCALE
3"
CLR
3"
CL
R
7
8
1
2
3
4
5
6
2
9
107 CONCRETE PRECAST WALL AT FOUNDATION
NO SCALE
KEYNOTES:
1.PRECAST WALL PANEL BEYOND, SEE
PLAN
2.CONCRETE SLAB ON GRADE, SEE
PLAN
3.EMBED CHANNEL BY PRECAST
4.3 8"x3"x0'-8" PLATE EACH SIDE
5.112" SHIM AND GROUT
6.12"x12"x1'-0" EMBED PLATE W/ (4) 12"Ø
x 5" LONG HEADED STUDS
7.COMPACTED SUB-GRADE BELOW
FOOTING, SEE PLAN
8.CONCRETE FOOTING, SEE PLAN
9.8" CONCRETE PRECAST WALL
PANEL, SEE PLAN
10.#4 x 2'-0" DRILL AND EPOXY PER GSN
11.GROUT OVER ALL EXPOSED STEEL
BELOW GRADE
3"
CLR
3"
CL
R
7
8
1
2
3
4
5
6
2
9 10
109 TRENCH DRAIN IN CONCRETE SLAB
NO SCALE
KEYNOTES:
1.#4 BENT DOWEL AT 18" O.C.
2.TRENCH DRAIN, SEE
ARCHITECTURAL DRAWINGS
3.CONCRETE SLAB ON GRADE, SEE
PLAN
1'-3"
MIN LAP
1'-6"
MIN
6"
M
I
N
3
12
TYP 1/4
TYP 1/4
TYP
TYP 1/4
TYP
TYP 1/4
TYP
TYP 1/4
TYP
TYP 1/4
TYP
TYP 1/4
11
9
10 11
13
12
106 CONCRETE SLAB AT FOUNDATION
CW_S104 NO SCALE
3"
CLR
3"
CL
R
8
7
6
5
4
3
1
2
KEYNOTES:
1.WALL BEYOND, SEE PLAN
2.#4 BENT DOWEL AT 24" O.C.
3.CONCRETE SLAB ON GRADE, SEE PLAN
4.6" SLAB TURN DOWN TO FOUNDATION, #3
REBAR 24" O.C.
5.CONCRETE FOOTING, SEE PLAN
6.COMPACTED SUB-GRADE BELOW
FOOTING, SEE PLAN
7.MINIMUM FOOTING DEPTH, SEE GSN
8.SIDEWALK, PAVEMENT, OR FINISH GRADE
PER ARCH
18"
24"
KEYNOTES:
1.CONCRETE SLAB ON GRADE, SEE
PLAN
2.CONT L13 4x13 4x14 W/ 14"Ø x 2" HEADED
STUDS AT 18" O.C.
3.L212x212x14 W/ 14"Ø x 2" HEADED
STUDS AT 18" O.C.
4.#4 BENT BARS AT 18" O.C.
5.8" CAST IN PLACE CONCRETE WALL,
SEE PLAN
6.#4 BARS AT 18" O.C., EACH WAY
7.WATER STOP, SEE ARCH
8.CONCRETE SLAB W/
REINFORCEMENT, SEE PLAN
9.STEEL EMBED PLATE W/ (4) 12"Ø x 3"
LONG HEADED STUDS
10.#4 x 2'-0" DRILL AND EPOXY PER GSN
11.COMPACTED SUB-GRADE BELOW
FOOTING, SEE PLAN
12.SLOPED FLOOR PER ARCH
108 TRENCH DRAIN
NO SCALE
1
4
11
6"
B.O. PIT
VARIES
9
2
4
5
10
66
1 3
5
10
66
7
8
12
PER ARCH PER ARCH
PRO
F
E
S
S
I
O
N
A
L
EN GI N E E R
ST ATE
O
F
I
D
A
H
O
A
1/
7
/
2
2
14
1
3
4
D VID
B
.
P
O
R
T
E
R
L
I
C
E
N
SED
PROJECT MANAGER:CAD OPERATOR:JOB NO.:
fax: 208.227.8405
1020 E. Lincoln Road
Idaho Falls, ID 83401
Structural Engineering
phone: 208.227.8404
This drawing is the property of FROST Structural Engineering, Inc. Legally, the drawing can NOT be copied in whole or in pieces. It is only to be used for the project and site
specifically identified hereon and is not to be used on any other project. Contractor shall carefully review all dimensions, details, and conditions and report at once any error,
inconsistency or omission discovered before construction. The contractor assumes full liability for deviations from the intent of these plans.
contact@frost-structural.com
AVBBCIF-381
date
drawn
job no.
sheet number:
checked
sheet title:
THESE DOCUMENTS HAVE BEEN PRODUCED AS AN
INSTRUMENT OF SERVICE AND ARE INTENDED
SOLELY FOR THE PURPOSE OF CONSTRUCTING,
USING AND MAINTAINING THE PROJECT. SPOTLESS
WASH SOLUTIONS USA INC, AS THE ARCHITECT OF
RECORD FOR THE PROJECT RETAINS OWNERSHIP
OF THESE DOCUMENTS.
ANY USE OF THESE DOCUMENTS OR USE OF THIS
DESIGN, IDEAS OR CONCEPTS DESCRIBED HEREIN
IN WHOLE OR PART BY ANY MEANS WHATSOEVER IS
STRICTLY PROHIBITED EXCEPT BY WRITTEN
CONSENT OF SPOTLESS WASH SOLUTIONS USA INC.
REPRODUCTION OF THIS DOCUMENT IS STRICTLY
PROHIBITED EXCEPT BY WRITTEN CONSENT OF
SPOTLESS WASH SOLUTIONS USA INC.
COPYRIGHT 2021
SPOTLESS WASH SOLUTIONS USA INC.
SP
O
T
L
E
S
S
W
A
S
H
S
O
L
U
T
I
O
N
S
U
S
A
I
N
C
TW
I
N
F
A
L
L
S
,
I
D
A
H
O
8
3
3
0
3
PH
.
(
2
0
8
)
8
4
1
-
4
5
2
4
issued for
revisions:
stamp
PO
B
O
X
5
4
5
6
NI
T
R
O
C
A
R
W
A
S
H
RE
X
B
U
R
G
,
I
D
13
7
1
N
2
N
D
E
RE
X
B
U
R
G
,
I
D
8
3
4
4
0
-
-
-
-
-
FOUNDATION
DETAILS
S3.0
NOT
F
O
R
C
O
N
S
T
R
U
C
T
I
O
N
202 PRECAST ROOF PANEL AT PRECAST CONCRETE WALL
NO SCALE
KEYNOTES:
1.PRECAST CONCRETE WALLS, SEE
PLAN
2.CONCRETE CORBEL BY PRECAST
MANUFACTURER
3.CONT 12" x 3" KOROLATH BEARING
PAD OR EQUAL
4.PRECAST ROOF PANEL, SEE PLAN
5.1/4"x4"x4" EMBED PLATE W/ (1) 5
8"x5"
HEADED STUD AT 48" O.C.
6.CONT L4x4X1/4 ANGLE
201 PRECAST ROOF PANEL AT PRECAST CONCRETE WALL
NO SCALE
KEYNOTES:
1.1/4"x4"x4" EMBED PLATE W/ (1) 5
8"x5"
HEADED STUD AT 48" O.C.
2.PRECAST CONCRETE WALLS, SEE
PLAN
3.PRECAST ROOF PANEL, SEE PLAN
4.CONT 12" x 3" KOROLATH BEARING
PAD OR EQUAL
5.CONCRETE CORBEL BY PRECAST
MANUFACTURER
6.CONT L4x4X1/4 ANGLE
6"
4" MIN
BEARING
4" MIN
BEARING
6"
1
2
3
1
5
4
2
34
5
NOTE:
A.PRECAST MANUFACTURER SHALL
DESIGN PARAPET FOR ±38 PSF
(ASD) WIND LOAD
NOTE:
A.PRECAST MANUFACTURER SHALL
DESIGN PARAPET FOR ±38 PSF
(ASD) WIND LOAD
203 PRECAST ROOF PANEL AT PRECAST CONCRETE WALL
NO SCALE
KEYNOTES:
1.PRECAST CONCRETE WALLS, SEE
PLAN
2.1/4"x4"x4" EMBED PLATE W/ (1) 5
8"x5"
HEADED STUD AT 32" O.C.
3.PRECAST ROOF PANEL, SEE PLAN
NOTE:
A.PRECAST MANUFACTURER SHALL
DESIGN PARAPET FOR ±38 PSF
(ASD) WIND LOAD
3
1
205 PRECAST ROOF PANEL AT PRECAST CONCRETE WALL
NO SCALE
2 3" MIN
BEARING
204 PRECAST ROOF PANEL AT PRECAST CONCRETE WALL
NO SCALE
KEYNOTES:
1.12" LONG #5 REBAR DOWEL AT 12"
O.C. DRILL AND EPOXY INTO WALL
W/ SIMPSON SET-3G EPOXY AND 6"
EMBEDMENT INTO WALL
2.PRECAST ROOF PANEL, SEE PLAN
3.PRECAST CONCRETE WALLS, SEE
PLAN
2
3
KEYNOTES:
1.#4 BENT DOWEL AT 48" O.C.
STAGGERED EACH DIRECTION,
DRILL AND EPOXY INTO WALL 10"
2.PRECAST ROOF PANEL, SEE PLAN
3.PRECAST CONCRETE WALLS, SEE
PLAN
4.CONT 12" x 3" KOROLATH BEARING
PAD OR EQUAL
5.36" LONG #4 BAR AT EACH BENT
DOWEL
6.GROUT IN PLACE EVERY CELL
WHERE THAT HAS A REBAR DOWEL,
BREAK OUT HOLLOWCORE AS
NEEDED TO INSERT REBAR
2
3
44
1
1
3/164
5
6
6
2
2
3/164
3/16 4
3/16 4
206 PRECAST ROOF PANEL AT PRECAST CONCRETE WALL
NO SCALE
KEYNOTES:
1.PRECAST CONCRETE WALLS, SEE
PLAN
2.CONCRETE CORBEL BY PRECAST
MANUFACTURER
3.CONT 12" x 3" KOROLATH BEARING
PAD OR EQUAL
4.PRECAST ROOF PANEL, SEE PLAN
5.1/4"x4"x4" EMBED PLATE W/ (1) 5
8"x5"
HEADED STUD AT 48" O.C.
6.12" LONG L4x4X1/4 ANGLE AT EACH
EMBED PLATE
7.CONT L5x5x3
8 ANGLE W/ 5
8"Øx6" TITEN
HD ANCHOR AT 16" O.C.
8.600S162-43 STEEL STUD JOIST AT
24" O.C.
9.12"x6" TITEN HD ANCHOR AT 4'-0"
O.C. (EVERY OTHER JOIST)
10.7
16" ROOF SHEATHING W/ #6 SELF
TAPPING SCREWS AT 6" O.C.
11.CONT 600T150-43 STEEL TRACK
12.3" LONG L3x3x14 ANGLE CLIP AT
EACH ANCHOR
6"
4" MIN
BEARING
1
2
3 4
5
NOTE:
A.PRECAST MANUFACTURER SHALL
DESIGN PARAPET FOR ±38 PSF
(ASD) WIND LOAD
5
6
3/16 4
3" MIN
BEARING
3
5
6
5
3/16 4
5
2"
7
98
10
207 PRECAST ROOF PANEL AT PRECAST CONCRETE WALL
NO SCALE
KEYNOTES:
1.PRECAST CONCRETE WALLS, SEE
PLAN
2.1/4"x4"x4" EMBED PLATE W/ (1) 5
8"x5"
HEADED STUD AT 8" O.C.
3.PRECAST ROOF PANEL, SEE PLAN
NOTE:
A.PRECAST MANUFACTURER SHALL
DESIGN PARAPET FOR ±38 PSF
(ASD) WIND LOAD
3
1
2
2
3/16 4
3/16 4
208 CONCRETE PANEL AT CONCRETE PANEL
NO SCALE
KEYNOTES:
1.PRECAST ROOF PANEL, SEE PLAN
2.#4 REBAR DOWEL AT SPACING
SPECIFIED ON THE ROOF PLAN
3.GROUT IN PLACE EVERY CELL
WHERE THAT HAS A REBAR DOWEL,
BREAK OUT HOLLOWCORE AS
NEEDED TO INSERT REBAR
3
1
2
209 PRECAST ROOF PANEL AT PRECAST CONCRETE WALL
NO SCALE
KEYNOTES:
1.1/4"x4"x4" EMBED PLATE W/ (1) 5
8"x5"
HEADED STUD AT 48" O.C.
2.PRECAST CONCRETE WALLS, SEE
PLAN
3.PRECAST ROOF PANEL, SEE PLAN
4.CONT 12" x 3" KOROLATH BEARING
PAD OR EQUAL
5.CONCRETE CORBEL BY PRECAST
MANUFACTURER
6.CONT L4x4X1/4 ANGLE
7.600S162-43 STEEL STUD JOIST AT
24" O.C.
8.12"x6" TITEN HD ANCHOR AT 4'-0"
O.C. (EVERY OTHER JOIST)
9.7
16" ROOF SHEATHING W/ #6 SELF
TAPPING SCREWS AT 6" O.C.
10.CONT 600T150-43 STEEL TRACK
11.3" LONG L3x3x14 ANGLE CLIP AT
EACH ANCHOR
4" MIN
BEARING
6"
2
3
1
5
4
NOTE:
A.PRECAST MANUFACTURER SHALL
DESIGN PARAPET FOR ±38 PSF
(ASD) WIND LOAD
1
3/164
6
2'-0"
210 PRECAST ROOF PANEL AT PRECAST CONCRETE WALL
NO SCALE
KEYNOTES:
1.PRECAST CONCRETE WALLS, SEE
PLAN
2.1/4"x4"x4" EMBED PLATE W/ (1) 5
8"x5"
HEADED STUD AT 32" O.C.
3.PRECAST ROOF PANEL, SEE PLAN
4.C6x8.2 AT 24" O.C.
5.(2) 1
2"x5" TITEN HD ANCHOR
6.7
16" ROOF SHEATHING W/ #6 SELF
TAPPING SCREWS AT 6" O.C.
NOTE:
A.PRECAST MANUFACTURER SHALL
DESIGN PARAPET FOR ±38 PSF
(ASD) WIND LOAD
3
1
2
2
3/16 4
3/16 4
1
6
15"
14
"
1/4
1111
12
10"
10
"
10
"
1
8 7
9
2'-0"10 10
1/4
11
8
7
9
10
10
1/4
11
2'-0"
PRO
F
E
S
S
I
O
N
A
L
EN GI N E E R
ST ATE
O
F
I
D
A
H
O
A
1/
7
/
2
2
14
1
3
4
D VID
B
.
P
O
R
T
E
R
L
I
C
E
N
SED
PROJECT MANAGER:CAD OPERATOR:JOB NO.:
fax: 208.227.8405
1020 E. Lincoln Road
Idaho Falls, ID 83401
Structural Engineering
phone: 208.227.8404
This drawing is the property of FROST Structural Engineering, Inc. Legally, the drawing can NOT be copied in whole or in pieces. It is only to be used for the project and site
specifically identified hereon and is not to be used on any other project. Contractor shall carefully review all dimensions, details, and conditions and report at once any error,
inconsistency or omission discovered before construction. The contractor assumes full liability for deviations from the intent of these plans.
contact@frost-structural.com
AVBBCIF-381
date
drawn
job no.
sheet number:
checked
sheet title:
THESE DOCUMENTS HAVE BEEN PRODUCED AS AN
INSTRUMENT OF SERVICE AND ARE INTENDED
SOLELY FOR THE PURPOSE OF CONSTRUCTING,
USING AND MAINTAINING THE PROJECT. SPOTLESS
WASH SOLUTIONS USA INC, AS THE ARCHITECT OF
RECORD FOR THE PROJECT RETAINS OWNERSHIP
OF THESE DOCUMENTS.
ANY USE OF THESE DOCUMENTS OR USE OF THIS
DESIGN, IDEAS OR CONCEPTS DESCRIBED HEREIN
IN WHOLE OR PART BY ANY MEANS WHATSOEVER IS
STRICTLY PROHIBITED EXCEPT BY WRITTEN
CONSENT OF SPOTLESS WASH SOLUTIONS USA INC.
REPRODUCTION OF THIS DOCUMENT IS STRICTLY
PROHIBITED EXCEPT BY WRITTEN CONSENT OF
SPOTLESS WASH SOLUTIONS USA INC.
COPYRIGHT 2021
SPOTLESS WASH SOLUTIONS USA INC.
SP
O
T
L
E
S
S
W
A
S
H
S
O
L
U
T
I
O
N
S
U
S
A
I
N
C
TW
I
N
F
A
L
L
S
,
I
D
A
H
O
8
3
3
0
3
PH
.
(
2
0
8
)
8
4
1
-
4
5
2
4
issued for
revisions:
stamp
PO
B
O
X
5
4
5
6
NI
T
R
O
C
A
R
W
A
S
H
RE
X
B
U
R
G
,
I
D
13
7
1
N
2
N
D
E
RE
X
B
U
R
G
,
I
D
8
3
4
4
0
-
-
-
-
-
ROOF
FRAMING
DETAILS
S4.0
NOT
F
O
R
C
O
N
S
T
R
U
C
T
I
O
N
...\22-06 P-1 WASTE AND VENT FLOOR 1/13/2022 2:25:20 PM
NOT
F
O
R
C
O
N
S
T
R
U
C
T
I
O
N
...\22-06 P-2 WATER AND GAS FLOOR 1/13/2022 3:31:19 PM
NOT
F
O
R
C
O
N
S
T
R
U
C
T
I
O
N
...\22-06 P-3 PLUMBING FIXTURE SCH 1/13/2022 2:33:14 PM
NOT
F
O
R
C
O
N
S
T
R
U
C
T
I
O
N
...\21-93 M-1 HVAC FLOOR PLAN.dgn 1/13/2022 2:27:52 PM
NOT
F
O
R
C
O
N
S
T
R
U
C
T
I
O
N
...\21-93 M-2 HVAC ROOF PLAN.dgn 1/13/2022 2:30:48 PM
NOT
F
O
R
C
O
N
S
T
R
U
C
T
I
O
N
Air System Sizing Summary for RTU-1
Project Name: 21-93 DR.SHINE CARWASH 08/18/2021
Prepared by: Kartchner Beaucannon Associates 01:14PM
Air System Information
Air System Name ............................................. RTU-1
Equipment Class ....................................... SPLT AHU
Air System Type .............................................. SZCAV
Number of zones .......................................................... 1
Floor Area .............................................................. 436.0 ft²
Location ............................................ Idaho Falls, Idaho
Sizing Calculation Information
Calculation Months .................................... Jan to Dec
Sizing Data .......................................... User-Modified
Zone CFM Sizing ................ Sum of space airflow rates
Space CFM Sizing ............ Individual peak space loads
Central Cooling Coil Sizing Data
Total coil load ......................................................... 2.2 Tons
Total coil load ....................................................... 26.4 MBH
Sensible coil load ................................................. 26.4 MBH
Coil CFM at Aug 1500 ......................................... 1200 CFM
Max block CFM ................................................... 1200 CFM
Sum of peak zone CFM ....................................... 1200 CFM
Sensible heat ratio .............................................. 1.000
CFM/Ton ............................................................ 545.3
ft²/Ton ................................................................. 198.1
BTU/(hr·ft²) ........................................................... 60.6
Water flow @ 10.0 °F rise ...................................... N/A
Load occurs at ................................................ Aug 1500
OA DB / WB ................................................... 92.0 / 61.0 °F
Entering DB / WB ........................................... 82.3 / 62.9 °F
Leaving DB / WB ........................................... 58.0 / 54.9 °F
Coil ADP .................................................................. 55.3 °F
Bypass Factor ........................................................ 0.100
Resulting RH .............................................................. 37 %
Design supply temp. ................................................ 58.0 °F
Zone T-stat Check ................................................. 0 of 1 OK
Max zone temperature deviation ................................ 7.0 °F
Central Heating Coil Sizing Data
Max coil load ........................................................ 15.6 MBH
Coil CFM at Des Htg ........................................... 1200 CFM
Max coil CFM ...................................................... 1200 CFM
Water flow @ 20.0 °F drop .................................... N/A
Load occurs at ................................................... Des Htg
BTU/(hr·ft²) .............................................................. 35.7
Ent. DB / Lvg DB ............................................ 70.0 / 84.3 °F
Supply Fan Sizing Data
Actual max CFM .................................................. 1200 CFM
Standard CFM ..................................................... 1008 CFM
Actual max CFM/ft² ............................................... 2.75 CFM/ft²
Fan motor BHP ........................................................ 0.00 BHP
Fan motor kW .......................................................... 0.00 kW
Fan static ................................................................. 0.00 in wg
Outdoor Ventilation Air Data
Design airflow CFM ................................................. 27 CFM
CFM/ft² ................................................................. 0.06 CFM/ft²
CFM/person ........................................................... 13.58 CFM/person
Air System Sizing Summary for RTU-2
Project Name: 21-93 DR.SHINE CARWASH 08/18/2021
Prepared by: Kartchner Beaucannon Associates 01:19PM
Air System Information
Air System Name ............................................. RTU-2
Equipment Class ....................................... SPLT AHU
Air System Type .............................................. SZCAV
Number of zones .......................................................... 1
Floor Area .............................................................. 166.0 ft²
Location ............................................ Idaho Falls, Idaho
Sizing Calculation Information
Calculation Months .................................... Jan to Dec
Sizing Data .......................................... User-Modified
Zone CFM Sizing ................ Sum of space airflow rates
Space CFM Sizing ............ Individual peak space loads
Central Cooling Coil Sizing Data
Total coil load ......................................................... 2.9 Tons
Total coil load ....................................................... 34.5 MBH
Sensible coil load ................................................. 34.5 MBH
Coil CFM at Jul 1400 ........................................... 1200 CFM
Max block CFM ................................................... 1200 CFM
Sum of peak zone CFM ....................................... 1200 CFM
Sensible heat ratio .............................................. 1.000
CFM/Ton ............................................................ 417.3
ft²/Ton ................................................................... 57.7
BTU/(hr·ft²) ......................................................... 207.9
Water flow @ 10.0 °F rise ...................................... N/A
Load occurs at .................................................. Jul 1400
OA DB / WB ................................................... 91.0 / 60.7 °F
Entering DB / WB ........................................... 89.7 / 59.4 °F
Leaving DB / WB ........................................... 58.0 / 47.7 °F
Coil ADP .................................................................. 54.5 °F
Bypass Factor ........................................................ 0.100
Resulting RH .............................................................. 17 %
Design supply temp. ................................................ 58.0 °F
Zone T-stat Check ................................................. 0 of 1 OK
Max zone temperature deviation ................................ 8.7 °F
Central Heating Coil Sizing Data
Max coil load .......................................................... 3.6 MBH
Coil CFM at Des Htg ........................................... 1200 CFM
Max coil CFM ...................................................... 1200 CFM
Water flow @ 20.0 °F drop .................................... N/A
Load occurs at ................................................... Des Htg
BTU/(hr·ft²) .............................................................. 21.8
Ent. DB / Lvg DB ............................................ 59.6 / 62.9 °F
Supply Fan Sizing Data
Actual max CFM .................................................. 1200 CFM
Standard CFM ..................................................... 1008 CFM
Actual max CFM/ft² ............................................... 7.23 CFM/ft²
Fan motor BHP ........................................................ 0.00 BHP
Fan motor kW .......................................................... 0.00 kW
Fan static ................................................................. 0.00 in wg
Outdoor Ventilation Air Data
Design airflow CFM ................................................. 10 CFM
CFM/ft² ................................................................. 0.06 CFM/ft²
CFM/person ............................................................. 0.00 CFM/person
COMcheck Software Version 4.1.5.3
Mechanical Compliance Certificate
Project Title:
2018 IECC
Project Type: New Construction
Location: Rexburg, Idaho
Climate Zone: 6b
Construction Site:
1371 N 2ND E
REXBURG, ID
Owner/Agent:
JOSH HOWA
HOWA DESIGN
1891 N. WILDWOOD ST.
TWIN FALLS, ID 83303
208-841-4524
Designer/Contractor:
TYLER BEAUCANNON
KARTCHER BEAUCANNON
ASSOCIATES
1301 S FIVE MILE RD
BOISE, ID 83709
208-888-7145
tbeaucannon@kbamep.com
Project Information
Energy Code:
NITRO CAR WASH
Credits: 1.0 Required 1.0 Proposed
Reduced Lighting Power, 1.0 credit
Additional Efficiency Package(s)
Mechanical Systems List
Quantity System Type & Description
Heating: 1 each − Central Furnace, Gas, Capacity = 67 kBtu/h
Proposed Efficiency = 81.00% Et, Required Efficiency: 80.00 % Et or 80% AFUE
Cooling: 1 each − Single Package DX Unit, Capacity = 35 kBtu/h, Air−Cooled Condenser, Air Economizer
Proposed Efficiency = 14.00 SEER, Required Efficiency: 14.00 SEER
Fan System: None
2 RTU (Single Zone):
Heating: 1 each − Unit Heater, Gas, Capacity = 30 kBtu/h
Proposed Efficiency = 82.00% Ec, Required Efficiency: 80.00 % Ec
Fan System: None
2 HVAC System 2 (Single Zone):
Heating: 1 each − Radiant Heater, Gas, Capacity = 34 kBtu/h
No minimum efficiency requirement applies
Fan System: None
1 HVAC System 3 (Single Zone):
Heating: 1 each − Central Furnace, Gas, Capacity = 143 kBtu/h
Proposed Efficiency = 92.00% Et, Required Efficiency: 80.00 % Et or 80% AFUE
Fan System: None
1 MAU (Single Zone):
Mechanical Compliance Statement
Compliance Statement: The proposed mechanical design represented in this document is consistent with the building plans,
specifications, and other calculations submitted with this permit application. The proposed mechanical systems have been
designed to meet the 2018 IECC requirements in COM check Version 4.1.5.3 and to comply with any applicable mandatory
requirements listed in the Inspection Checklist.
Name - Title Signature Date
Project Title:
Data filename:
NITRO CAR WASH
H:\Google Drive\2022\22-06 Nitro Carwash\ComCheck.cck
01/13/22Report date:
121 of Page
...\21-93 M-3 MECHANICAL SCHEDULES 1/13/2022 2:33:26 PM
NOT
F
O
R
C
O
N
S
T
R
U
C
T
I
O
N
...\21-93 M-4 MECHANICAL DETAILS.d 1/13/2022 2:34:15 PM
NOT
F
O
R
C
O
N
S
T
R
U
C
T
I
O
N
...\22-06 E-1 POWER FLOOR PLAN.dgn 1/13/2022 2:24:33 PM
14. ALL ELECTRICAL WORK IN CAR WASH TUNNEL IS TO BE WET LOCATION IP65 RATED OR
BETTER.
15. ALL MOUNTING AND SUSPENSION SYSTEMS AND FASTENERS INSIDE OF TUNNEL TO BE
STAINLESS STEEL.
16. ALL CONDUIT INSIDE OF CAR WASH TUNNEL TO BE WATER-TIGHT AND PVC.
NOT
F
O
R
C
O
N
S
T
R
U
C
T
I
O
N
...\22-06 E-2 LIGHTING FLOOR PLAN. 1/13/2022 2:20:11 PM
NOT
F
O
R
C
O
N
S
T
R
U
C
T
I
O
N
...\22-06 E-3 SPECIAL SYSTEMS FLOO 1/13/2022 2:26:51 PM
NOT
F
O
R
C
O
N
S
T
R
U
C
T
I
O
N
...\22-06 E-4 ELECTRICAL ROOF PLAN 1/13/2022 2:16:36 PM
NOT
F
O
R
C
O
N
S
T
R
U
C
T
I
O
N
TYPE MANUFACTURER CATALOG NUMBER DESCRIPTION MOUNTING LAMPS QTY
FIXTURE
WATTS
TOTAL WATTS VOLTAGE REMARKS
DSX1-LED-30-1050-40K-T3M-MVOLT-SPA-DBLXD-PIRH-FAO POLE MOUNTED SQUARE SOFT CORNER POLE LED
AL1 LITHONIA NO. POLE:SSS-20-4G-DM 19A S-DBLXD-SBC4 ALUMINUM HOUSING, GASKETED LENS, ARM 12582 3 102
306 MULTI 2
LED, TYPE III-ASYMMETRIC DISTRIBUTION MOUNTED 4000K
SINGLE HEAD, 20 FT. POLE W/BASE COVER
DSX1-LED-30-1050-40K-T4-MVOLT-SPA-DBLXD-PIRH-FAO POLE MOUNTED SQUARE SOFT CORNER LED
LITHONIA NO. POLE:SSS-20-4G-DM 19A S-DBLXD-SBC4 ALUMINUM HOUSING, GASKETED LENS, POLE 12582 3 102
306 MULTI 2
AL2 LED, TYPE IV-ASYMMETRIC DISTRIBUTION ARM 4000K
SINGLE HEAD, 20 FT. POLE W/BASE COVER MOUNTED
POLE MOUNTED SQUARE SOFT CORNER, 2 HEADS (2)LED
LITHONIA NO. DSX1-LED-30-1050-40K-T4-MVOLT-SPA-DBLXD-PIRH-FAO ALUMINUM HOUSING, GASKETED LENS, POLE 12582
AL3 2 HEADS POLE:SSS-20-4G-DM 28A S-DBLXD-SBC4 LED, TYPE IV-ASYMMETRIC DISTRIBUTION ARM 4000K 2 102
204 MULTI 2
SINGLE HEAD, 20 FT. POLE W/BASE COVER MOUNTED
EMERGENCY LIGHTING UNIT WALL WITH
EL1 LITHONIA NO. ELM2-LED-W-SD LOW PROFILE, THERMOPLASTIC HOUSING 7'-6"FIXTURE 2 3
6 120/277 2
DUAL LITE EV2DI DUAL HEAD AFF
EMERGENCY LIGHTING UNIT WALL
EL2 MULE LTG MRD-WL-LED-BL LOW PROFILE, THERMOPLASTIC HOUSING 7'-6" WITH 4 3
12 120/277 2
EELP ELM16-WL-LED-BLK DUALHEAD WER LOCATION AFF FIXTURE
EXIT/EM LIGHT COMBO, LED, RED STENCIL ABOVE
EX1 LITHONIA NO. LHQM-LED-R-SD-120/S77-W/ NI-CAD THERMOPLASTIC HOUSING,DOOR WITH 4 3
12 120/277 2
DUAL LITE EVCURWDI SINGLE OR DOUBLE FACE FIXTURE
NI-CAD BATTERY
EXIT/EM LIGHT COMBO, LED, RED STENCIL ABOVE
EX2 MULE LTG CWL-1-R-BL-SD THERMOPLASTIC HOUSING,DOOR WITH 3 3
9 120/277 2
ENVOY CWLEZ-1-R-B-SDT SINGLE OR DOUBLE FACE FIXTURE
NI-CAD BATTERY
2'X4' LED GRID MOUNTED TROFFER LED
GL1 LITHONIA 2BLT4-30L-SDP-GZ10-LP835 ACRYLIC LENS, 0-10V DIMMING GRID 2962LMNS 7 24
168 120/277 2
3500K
8' LINEAR, LED, IP68 RATED CEILING LED
SL1 G&G WPX8-SO-40K-WOX-PSU-80-WPX-MNT-NM SATIN LENS, AIRCRAFT CABLE HUNG PENDANT 8000LM 4 57
228 120/277
OWNER FURNISHED, DIVISION 16 INSTALLED 9'-0" AFF 4000K
WPX8-SO-40K-WPX-PSU-600-WPX-MNT-NM 8', LINEAR LED, IP68 RATED CEILING LED
SL2 G&G POWER SUPPLY.SATIN LENS, AIRCRAFT CABLE HUNG PENDANT 8000LM 33 57
1881 120/277
OWNER FURNISHED, DIVISION 16 INSTALLED 9'-0" AFF 4000K
7" ROUND SURFACE, LED CEILING LED
SL3 JUNO JSF-7-35K-90-120-WH SURFACE 1000LMNS 1 13
13 120/277 2
3500K
LED EXTERIOR WALL PACK, TYPE 3 DISTRIBUTION LED
WL1 LITHONIA DSXW LED-20C-700-40K-T3M-MVOLT-DNA XD-PIR LED, MOTION SENSOR AND BI-LEVEL DIMMING WALL 5454LMNS 12 46
552 120/277 2
4000K
LED EXTERIOR WALL PACK, TYPE 3 DISTRIBUTION LED
WL1E LITHONIA DSXW LED-20-700-40K-T3M-MVOLT DNA XD-PIR-ELECW LED, MOTION SENSOR AND BI-LEVEL DIMMING WALL 5454LMNS 5 46
230 120/277 1,2,4
EMERGENCY DRIVER 4000K
WATTSTOPPER NO. LIA42-115/277-48HD-1GS-HCLK8S(F) SURFACE/FLUSH (42)RELAY MASTER LIGHTING CONTROL PANEL SURFACE
LCP LEVITON NO. R48MD-XXX NETWORK CAPABLE, ASTRONOMICAL TIMECLOCK OR N/A 120/277 2
HUBBELL CX82S482NM LCD SCREEN, INDIVIDUAL RELAY MANUAL OVERRIDE FLUSH
PHOTOCELL, OCC. SENSOR, LOW VOTLAGE SWITCH INPUTS MOUNTED
RELAYS:10 MILLION ON/OFF CYCLES, 14KAIC MIN. SEE DWGS.
WATTSTOPPER NO. HDLS2SS (2)BUTTON DIGITAL SWITCH FLUSH DIGITAL
DS1 LEVITON NO. ZMDSW-02W STATUS LED FOR EACH BUTTON MOUNTED N/A LOW 2
HUBBELL CXSW-2-W MATCHING WALL PLATE, CUSTJOM LABEL KIT FOR EACH IN DEEP VOLTAGE
SWITCH FOR IN-FIELD LABELING SWITCH BOX
WATTSTOPPER NO. HDLS4SS (4)BUTTON DIGITAL SWITCH FLUSH DIGITAL
DS2 LEVITON NO. ZMDSW-04W STATUS LED FOR EACH BUTTON MOUNTED N/A LOW 2
HUBBELL CXSW-4-W MATCHING WALL PLATE, CUSTJOM LABEL KIT FOR EACH IN DEEP VOLTAGE
SWITCH FOR IN-FIELD LABELING SEITCH BOX
REMARKS
1. PROVIDE WITH BODINE EMERGENCY BATTERY PACK SUITABLE FOR LAMP TYPE AND HALF THE LAMP LUMEN OUTPUT, PROVIDE WITH SELF TEST LIGHT AND PUSHBUTTON.
2.OR PRE-BID APPROVED EQUAL
3. SEE LIGHTING DRAWINGS AND LIGHTING CONTROL PANEL SCHEDULES FOR ADDITIONAL INFORMATION INCLUDING NUM BER AND TYPE OF RELAYS
THE ELECTRICAL CONTRACTOR SHALL INCLUDE FACTORY START-UP AND PROGRAMMING OF THE LIGHTING CONTROL SYSTEM AS WELL AS COMMISSIONING.
4. WHEN INSTALLED IN AN INSULATED CEILING, FIXTURE TO BE INSTALLED WITH FIRE RATED OR IC RATED ENCLOSURE OR HAVE SHEET ROCK ENCLOSURE BUILT PER DETAIL
NOTE TO BIDDERS
1. BID ONLY PRODUCTS THAT ARE SPECIFIED OR APPROVED VIA ADDENDUM. SUBMITTED ITEMS NOT APPROVED VIA ADDENDUM WILL BE REJECTED
2. PACKAGING OF LIGHT FIXTURES WITH OTHER SYSTEMS IS NOT ALLOWED
3. WHEN ONLY ONE PRODUCT IS APPROVED FOR BIDDING, THE PRICE FOR THAT ITEM SHALL BE BROKEN OUT SEPERATELY WHEN SUBMITTING PRICING
TO THE VARIOUS DISTRIBUTORS AND/OR CONTRACTORS AS REQUESTED.
SWITCH TYPE/INPUT AREA(S) CONTROLLED SWITCH SWITCH/INPUT
NAME SWITCH LOCATION BUTTON NO.NOTES RELAY(S) CONTROLLED
HA 20 1 REALY 1 2 277 20A/1P DIG. SWITCH DS1 EQUIPMENT ROOM 1 ALL ON 1 7
HA 22 2 RELAY 2 2 277 20A/1P 2 ALL OFF 7
HA 24 3 RELAY 3 2 277 20A/1P
HA 26 4 RELAY 4 2 277 20A/1P DIG. SWITCH DS2 OFFICE 1 ALL ON 1 1,2,3,4,5,6,7
HA 28 5 RELAY 5 2 277 20A/1P 2 ALL OFF 1,2,3,4,5,6,7
HA 30 6 RELAY 6 2 277 20A/1P 3 TUNNEL ON 1,2,3,4,5,6
HA 23 7 RELAY 7 2 277 20A/1P 4 TUNNEL OFF 1,2,3,4,5,6
HA 13 8 RELAY 8 1 277 20A/1P
HA 17 9 RELAY 9 1 277 20A/1P
HA 19 10 RELAY 10 1 277 20A/1P
HA 18 11 RELAY 11 1 277 20A/1P
HA 15 12 RELAY 12 1 120 20A/1P
LA 57 13 RELAY 13 1 120 20A/1P
LA 59 14 RELAY 14 1 120 20A/1P
LA 61 15 RELAY 15 1 120 20A/1P
LA 63 16 RELAY 16 1 120 20A/1P
LA 61 17 RELAY 17 1 120 20A/1P
LA 64 18 RELAY 18 1 120 20A/1P
LA 43 19 RELAY 19 3 120 20A/1P
LA 45 20 RELAY 20 3 120 20A/1P
LA 47 21 RELAY 21 3 120 20A/1P
LA 49 22 RELAY 22 3 120 20A/1P
LA 44 23 RELAY 23 3 120 20A/1P
LA 50 24 RELAY 24 3 120 20A/1P
LA 56 25 RELAY 25 3 120 20A/1P
LA 66 26 RELAY 26 3 120 20A/1P
26 RELAY 27
28 RELAY 28
29 RELAY 29
30 RELAY 30
31 RELAY 31
32 RELAY 32
33 RELAY 33
34 RELAY 34
35 RELAY 35
36 RELAY 36
37 RELAY 37
38 RELAY 38
38 RELAY 39
40 RELAY 40
41 RELAY 41
42 RELAY 42
43 RELAY 43
44 RELAY 44
45 RELAY 45
46 RELAY 46
47 RELAY 47
48 RELAY 48
RELAY NOTES:
1) THE RELAY SHALL BE CONTROLLED:PHOTO TO CELL ON, TIMECLOCK
2) THESE RELAYS SHALL BE PROGRAMMED FOR LIGHT SWEEP
CONTROL LIGHTING CIRCUITS INDICATED BY OWNER. THE OVERRIDE
SWITCHES SHALL BE PROGRAMMED TO PROVIDE AND
ADDITIONAL 2-HOURS OF OVERRIDE WHEN ACTIVATED.
LIGHTING CONTROL PANEL SCHEDULE-MASTER
PANEL NAME: LCP PANEL VOLTAGE: 120V PANEL MOUNTING: SURFACE
PROJECT NAME: DR. SHINE CAR WASH PANEL NOTES: PROVIDE ADDITIONAL INPUT CARDS AS REQUIRED FOR NUMBER OF INPUTS INDICATTED
SWITCH BUTTON LABEL
RELAY OUTPUTS LOCAL CONTACT INPUTS
PANEL CKT
SWITCH/INPUT NOTES:
1) BUTTON TO BE UTALIZED FOR 2-HR OVERRIDE AS INDICATED IN RELAY NOTE #2.
TYPE INPUT TYPERELAY RELAY NAME RELAY NOTES VOLTAGE
3) COORDINATE PROGRAMMING WITH OWNER
...\22-06 E-5 LIGHTING SCHEDULES.d 1/13/2022 2:16:05 PM
NOT
F
O
R
C
O
N
S
T
R
U
C
T
I
O
N
THREE PHASE PANEL BOARD SCHEDULE
PANELBOARD ID: PANEL 'HA'FEATURES:
LOCATION: See Plan
AIC: 42000
WIRE SIZE LTG REC MISC KIT MTR BRKR/POLE CCT PHASE CCT BRKR/P OLE LTG REC MISC KIT MTR CIRCUIT DESCRIPTION WIRE SIZE
12 8 20/3 1 A 2 20/3 8 12
12 8 3 B 4 8 12
12 8 5 C 6 8 12
12 14 20/3 7 A 8 20/3 14 12
12 14 9 B 10 14 12
12 14 11 C 12 14 12
12 2 20/1 13 A 14 20/3 14 12
12 8.5 20/1 15 B 16 14 12
12 6 20/1 17 C 18 14 12
12 20/1 19 A 20 20/1 2 12
12 1.5 20/1 21 B 22 20/1 2 12
12 2 . 20/1 23 C 24 20/1 2 12
6 40 60/3 25 A 26 20/1 2 12
6 40 27 B 28 20/3 8 10
6 40 29 C 30 8 10
31 A 32 8 10
33 B 34
35 C 36
37 A 38
39 B 40
41 C 42
REMARKS:
CONNECTED KVA/PHASE
31.0 PHASE A TOTAL LOADS
CONNECTED LOAD (KVA) DEMAND LOAD (KVA)32.7 PHASE B 92.1 TOTAL CONNECTED KVA
LIGHTING LIGHTING 32.1 PHASE C 94.2 TOTAL DEMAND KVA
RECEPTACLE RECEPTACLE CONNECTED AMP/PHASE 113 TOTAL DEMAND AMPS
MISC MISC 112 PHASE A 200 PANEL DESIGN AMPS
KITCHEN KITCHEN 118 PHASE B
MOTOR MOTOR 116 PHASE C
CIRCUIT DESCRIPTION
RO PRODUCTION PUMP RO REJECT PUMP
SEE PLAN Wires: 4
Bus Amps: 200 AMPS
CONNECTED AMPS CONNECTED AMPS
Voltage: 480Y/277V MAIN: MLO
Phase: 3 MOUNTING: Surface
LTG:EXTERIOR AIR COMPRESSOR
LTG:PARKING
HOTSY AIR COMPRESSOR
LTG:EQUIPMENT ROOM LTG:TUNNEL
SUMP PUMP LTG:TUNNEL
SUMP PUMP
LTG:VACUUM
FUTURE LTG:VACUUM LTG:TUNNEL
LTG:OFFICE/ELEC.LTG:TUNNEL
BLANK
BLANK
BLANK
BLANK
BLANK
BLANK BLANK
BLANK BLANK
BLANK BLANK
0 0
81.4 82.0
7.8 9.3
0.0 0.0
2.9 2.9
THREE PHASE PANEL BOARD SCHEDULE
PANELBOARD ID: PANEL 'LA'FEATURES:
LOCATION: See Plan
AIC: 42000
WIRE SIZE LTG REC MISC KIT MTR BRKR/POLE CCT PHASE CCT BRKR/POLE LTG REC MISC KIT MTR CIRCUIT DESCRIPTION WIRE SIZE
12 3 20/1 1 A 2 20/1 3 12
12 3 20/1 3 B 4 20/1 3 12
12 7.5 20/1 5 C 6 20/1 3 12
12 7 20/1 7 A 8 20/1 1.5 12
12 3 20/1 9 B 10
12 7 20/1 11 C 12 20/3 16 12
12 3 20/1 13 A 14 16 12
12 10 20/1 15 B 16 16 12
12 12.5 20/1 17 C 18 20/1 3 12
12 12.5 20/1 19 A 20 20/1 5 12
12 6 20/1 21 B 22 20/1 5 12
12 1.5 20/1 23 C 24 20/1 16 12
12 3 20/1 25 A 26 20/1 16 12
12 16 20/1 27 B 28 20/1 16 12
12 16 20/1 29 C 30 20/1 16 12
8 40 50/3 31 A 32 30/1 22 10
8 40 33 B 34 30/1 22 10
8 40 35 C 36 40/2 30 8
12 5 20/1 37 A 38 30 8
12 5 20/1 39 B 40 20/1 10 12
12 5 20/1 41 C 42 20/1 5 12
12 5 20/1 43 A 44 20/2 12 12
12 5 20/1 45 B 46 12 12
10 18 25/3 47 C 48 20/1 5 12
10 18 49 A 50 20/1 5 12
10 18 51 B 52 20/1 8 12
12 3 20/1 53 C 54 20/1 8 12
12 20/1 55 A 56 25/3 18 10
21 16 20/1 57 B 58 18 10
12 16 20/1 59 C 60 18 10
12 16 20/1 61 A 62 20/1 3 12
12 16 20/1 63 B 64 20/1 16 10
12 6 20/1 65 C 66 20/1 8 12
12 6.5 15/3 67 A 68 20/1 8 12
12 6.5 69 B 70 20/1 8 12
12 6.5 71 C 72 20/1 6 12
12 9 20/1 73 A 74 20/1 6 12
12 9 20/1 75 B 76 20/1 6 12
12 20/1 77 C 78 20/1 6 12
12 20/1 79 A 80 20/1 6 12
12 20/1 81 B 82 20/1 6 12
12 20/1 83 C 84
REMARKS: GFEP TYPE BREAKER FOR HEAT TAPE CIRCUIT
CONNECTED KVA/PHASE
33.5 PHASE A TOTAL LOADS
CONNECTED LOAD (KVA) DEMAND LOAD (KVA)35.9 PHASE B 103 TOTAL CONNECTED KVA
LIGHTING LIGHTING 21.4 PHASE C 104 TOTAL DEMAND KVA
RECEPTACLE RECEPTACLE CONNECTED AMP/PHASE 288 TOTAL DEMAND AMPS
MISC MISC 167 PHASE A 400 PANEL DESIGN AMPS
KITCHEN KITCHEN 155 PHASE B
MOTOR MOTOR 178.5 PHASE C
SPARE BLANK
REC: EQUIPMENT GATE CONTROLLER
REC: EQUIPMENT GATE CONTROLLER
SPARE POINT OF SALE MONITOR
SPARE POINT OF SALE MONITOR
SPARE POINT OF SALE MONITOR
EXTERIOR SIGN DIRECTIONAL SIGN
HEAT TAPE POINT OF SALE
MAU-1 POINT OF SALE
POINT OF SALE
GATE CONTROLLER
REC: ROOF SNOW MELT BOILER
SPARE RTU-2
EXTERIOR SIGN
EXTERIOR SIGN
EXTERIOR SIGN REC:VACUUMS
LOADING STATION DOOR MOTOR
RH-1
RTU-1 UH-2
EF-2
BOILER
0 0
0.0 0.0
3.1 3.7
7.0 7.0
92.8 92.8
IRRIGATION CONTROL
RO SKID
LIGHTING CONTROL PANEL
ENTRY ARCH
HYDRAFLEX ACCU PUMP
WELDER MAT WASHER
MAT WASHER
TUNNEL CONTROLLER
ENTRY EYES
REC: RESTROOM ACCU PUMP
RO CARBON FILTER ACCU PUMP
HYDRAFLEX ACCU PUMP
MICROWAVE RECLAIM FILTER
COFFEE MAKER UH-1
REC: STAFF WASHING MACHINE
PRINTER PETIT SYSTEM CONTROLLER
REC: COMMON
REFRIG
REC: MANAGER REC: WORK
PRINTER WATER SOFTENER
REC: RECEPTION
CIRCUIT DESCRIPTION
REC: T.T.B.D REC: WORK
REC: SECURITY/DATA REC: WORK
SEE PLAN Wires: 4
Bus Amps: 400 AMPS
CONNECTED AMPS CONNECTED AMPS
Voltage: 208Y/120V MAIN: MLO
Phase: 3 MOUNTING: Surface
COMcheck Software Version 4.1.5.3
Interior Lighting Compliance Certificate
Project Title:
2018 IECC
Project Type: New Construction
Construction Site:
1371 N 2ND E
REXBURG, ID
Owner/Agent:
JOSH HOWA
HOWA DESIGN
1891 N. WILDWOOD ST.
TWIN FALLS, ID 83303
208-841-4524
Designer/Contractor:
TYLER BEAUCANNON
KARTCHER BEAUCANNON
ASSOCIATES
1301 S FIVE MILE RD
BOISE, ID 83709
208-888-7145
tbeaucannon@kbamep.com
Project Information
Energy Code:
NITRO CAR WASH
Credits: 1.0 Required 1.0 Proposed
Reduced Lighting Power, 1.0 credit
Additional Efficiency Package(s)
Allowed Interior Lighting Power
A
Area Category
B
Floor Area
(ft2)
C
Allowed
Watts / ft2
D
Allowed Watts
(B X C)
1−Automotive Facility 11672 0.64 7458
7458Total Allowed Watts =
Proposed I nterior Lighti ng Power
E
(C X D)
D
Fixture
Watt.
A
Fixture ID : Description / Lamp / Wattage Per Lamp / Ballast
B
Lamps/
Fixture
C
# of
Fixtures
1−Automotive Facility
LED1: GL1: LED Panel 19W: 1 7 24 168
LED 2: SL1: LED Linear 33W: 1 4 57 228
LED 3: SL2: LED Linear 33W: 1 33 57 1881
LED 4: SL3: Other: 1 1 13 13
2290Total Proposed Watts =
Interior Lighting Compliance Statement
Compliance Statement: The proposed interior lighting design represented in this document is consistent with the building plans,
specifications, and other calculations submitted with this permit application. The proposed interior lighting systems have been
designed to meet the 2018 IECC requirements in COMcheck Version 4.1.5.3 and to comply with any applicable mandatory
requirements listed in the Inspection Checklist.
Name - Title Signature Date
Interior Li ghting PASSES: Desi gn 69% better than code
Project Title:
Data filename:
NITRO CAR WASH
H:\Google Drive\2022\22-06 Nitro Carwash\ComCheck.cck
01/13/22Report date:
61 of Page
COMcheck Software Version 4.1.5.3
Exterior Lighting Compliance Certificate
Project Title:
2018 IECC
Project Type: New Construction
Construction Site:
1371 N 2ND E
REXBURG, ID
Owner/Agent:
JOSH HOWA
HOWA DESIGN
1891 N. WILDWOOD ST.
TWIN FALLS, ID 83303
208-841-4524
Designer/Contractor:
TYLER BEAUCANNON
KARTCHER BEAUCANNON
ASSOCIATES
1301 S FIVE MILE RD
BOISE, ID 83709
208-888-7145
tbeaucannon@kbamep.com
Project Information
Energy Code:
NITRO CAR WASH
2 (Neighborhood business district (LZ2)) Exterior Lighting Zone
Allowed Exterior Lighting Power
A
Area/Surface Category
B
Quantity
C
Allowed
Watts / Unit
D
Tradable Wa
ttage
E
Allowed Watts
(B X C)
Illuminated area of facade wall or surface 7050 ft2 0.07 No 529
Parking area 25000 ft2 0.04 Yes 1000
Total Tradable Watts (a) =
Total Allowed Watts =
Total Allowed Supplemental Watts (b) =
1000
1529
400
(a) Wattage tradeoffs are only allowed between tradable areas/surfaces.
(b) A supplemental allowance equal to 400 watts may be applied toward compliance of both non−tradable and tradable areas/surfaces.
Proposed Exterior Lighting Power
E
(C X D)
D
Fixture
Watt.
A
Fixture ID : Description / Lamp / Wattage Per Lamp / Ballast
B
Lamps/
Fixture
C
# of
Fixtures
Illuminated area of facade wall or surface (7050 ft2): Non−tradable Wattage
LED 1: WL1: Other: 1 12 46 552
LED 2: WL1E: Other: 1 5 46 230
Parking area (25000 ft2): Tradable Wattage
LED 3: AL1: Other: 1 3 10 2 306
LED 4: AL2: Other: 1 3 10 2 306
LED 5: AL3: Other: 1 2 10 2 204
816Total Tradable Proposed Watts =
Exterior Lighting Compliance Statement
Compliance Statement: The proposed exterior lighting design represented in this document is consistent with the building
plans, specifications, and other calculations submitted with this permit application. The proposed exterior lighting systems have
been designed to meet the 2018 IECC requirements in COMcheck Version 4.1.5.3 and to comply with any applicable mandatory
requirements listed in the Inspection Checklist.
Exterior Lighting PASSES: Design 29% better than code
Project Title:
Data filename:
NITRO CAR WASH
H:\Google Drive\2022\22-06 Nitro Carwash\ComCheck.cck
01/13/22Report date:
61 of Page
COMcheck Software Version 4.1.5.3
Exterior Lighting Compliance Certificate
Project Title:
2018 IECC
Project Type: New Construction
Construction Site:
1371 N 2ND E
REXBURG, ID
Owner/Agent:
JOSH HOWA
HOWA DESIGN
1891 N. WILDWOOD ST.
TWIN FALLS, ID 83303
208-841-4524
Designer/Contractor:
TYLER BEAUCANNON
KARTCHER BEAUCANNON
ASSOCIATES
1301 S FIVE MILE RD
BOISE, ID 83709
208-888-7145
tbeaucannon@kbamep.com
Project Information
Energy Code:
NITRO CAR WASH
2 (Neighborhood business district (LZ2)) Exterior Lighting Zone
Allowed Exterior Lighting Power
A
Area/Surface Category
B
Quantity
C
Allowed
Watts / Unit
D
Tradable Wa
ttage
E
Allowed Watts
(B X C)
Illuminated area of facade wall or surface 7050 ft2 0.07 No 529
Parking area 25000 ft2 0.04 Yes 1000
Total Tradable Watts (a) =
Total Allowed Watts =
Total Allowed Supplemental Watts (b) =
1000
1529
400
(a) Wattage tradeoffs are only allowed between tradable areas/surfaces.
(b) A supplemental allowance equal to 400 watts may be applied toward compliance of both non−tradable and tradable areas/surfaces.
Proposed Exterior Lighting Power
E
(C X D)
D
Fixture
Watt.
A
Fixture ID : Description / Lamp / Wattage Per Lamp / Ballast
B
Lamps/
Fixture
C
# of
Fixtures
Illuminated area of facade wall or surface (7050 ft2): Non−tradable Wattage
LED 1: WL1: Other: 1 12 46 552
LED 2: WL1E: Other: 1 5 46 230
Parking area (25000 ft2): Tradable Wattage
LED 3: AL1: Other: 1 3 10 2 306
LED 4: AL2: Other: 1 3 10 2 306
LED 5: AL3: Other: 1 2 10 2 204
816Total Tradable Proposed Watts =
Exterior Lighting Compliance Statement
Compliance Statement: The proposed exterior lighting design represented in this document is consistent with the building
plans, specifications, and other calculations submitted with this permit application. The proposed exterior lighting systems have
been designed to meet the 2018 IECC requirements in COMcheck Version 4.1.5.3 and to comply with any applicable mandatory
requirements listed in the Inspection Checklist.
Exterior Lighting PASSES: Design 29% better than code
Project Title:
Data filename:
NITRO CAR WASH
H:\Google Drive\2022\22-06 Nitro Carwash\ComCheck.cck
01/13/22Report date:
61 of Page
Name - Title Signature Date
Project Title:
Data filename:
NITRO CAR WASH
H:\Google Drive\2022\22-06 Nitro Carwash\ComCheck.cck
01/13/22Report date:
62 of Page
...\22-06 E-6 ELECTRICAL PANEL SCH 1/13/2022 2:12:32 PM
NOT
F
O
R
C
O
N
S
T
R
U
C
T
I
O
N
Source Target Amps Fault Current Conductor/Conduit Type Wire Size C Value Length # of Conduct/Phase (n) Voltage of Circuit (E.) "f" Factor Multiplier (M) Sym RMS
XFMR DISCO. 1000 51463 Copper NonMag 400 24297 50 3 480 0.127 0.887 45648.358
Source Target Amps Fault Current Conductor/Conduit Type Wire Size C Value Length # of Conduct/Phase (n) Voltage of Circuit (E.) "f" Factor Multiplier (M) Sym RMS
MDP PANEL HA 200 45648.36 Copper NonMag 3\0 13923 15 1 480 0.177 0.8493 38768.637
Source Target Amps Fault Current Conductor/Conduit Type Wire Size C Value Length # of Conduct/Phase (n) Voltage of Circuit (E.) "f" Factor Multiplier (M) Sym RMS
MDP PANEL LA 400 45648.358 Copper NonMag 3\0 13923 15 2 208 0.205 0.8300 37890.104
Line 10
Line 1
Line 11
...\22-06 E-7 ELECTRICAL SINGLE LI 1/13/2022 2:15:25 PM
NOT
F
O
R
C
O
N
S
T
R
U
C
T
I
O
N