Corrections in the following table need to be applied before a permit can be issued
Review Report
Revisions Required
Page Reference Annotation
Type
Author : Department Status Page Review Comments Applicant Response Comments
E3.1 Free text Alex Owens : Electrical Open 5 Verify use of concrete encased electrode (UFFER) with #4
copper wire between service ground bar and "UFFER" (250.50,
250.52A3)
# 21-00694
New Commercial Building
Panic Hardware shall be installed as per IBC Section 1010.1.10
Report Date: 01.12.2022
Approval of plans does not constitute approval of variance from code
Page 1 of 1
Powered by TCPDF (www.tcpdf.org)
79
6
M
e
r
u
s
C
o
u
r
t
St
.
L
o
u
i
s
,
M
O
6
3
0
2
6
T
6
3
6
.
3
4
9
.
1
6
0
0
F
6
3
6
.
3
4
9
.
1
7
3
0
CE
R
T
I
F
I
C
A
T
E
O
F
A
U
T
H
O
R
I
T
Y
N
O
.
3
8
0
0
8/18/2021
SEAL
DESCRIPTIONDATEREV.
ISSUE DATE: 08/17/2021
PROJECT NUMBER: 21-008
DRAWN BY:
CHECKED BY:
SHEET NAME
SHEET NUMBER
MO
O
D
Y
R
D
&
N
2
N
D
E
RE
X
B
U
R
G
,
I
D
8
3
4
4
0
PROJECT TYPE:
SITE NUMBER:
BUILDING TYPE:
OWNER:
BASE VERSION:
DRAWING RELEASE:
PROJECT YEAR:
ASSET TYPE:
CLASSIFICATION:
UPGRADE CLASSIFICATION:
DESIGN TYPE:
#13487
(2.0) SMART 40+
FREESTANDING
NEW
FRANCHISE
2020
NEW BUILD
2021
(2.0) UM BRITE
SUMMER
NEW
SMART 40+
1 10/20/2021 City Comments
12
/
2
2
/
2
0
1
7
4
:
0
9
:
5
0
P
M
PHOTOMETRIC PLAN
E1.2
KH
MJ
NEUTRAL
SHUNT
TRIP
BREAKERS
IN 'MDP'
RED
BLACK
CIRCUIT
A-5
MICRO SWITCH
IN HOOD
POWER KILL
SWITCHES
NOT TO SCALE
SHUNT TRIP CIRCUIT DETAIL 2
SERIES RATED NOTES
MAIN BREAKERS IN MDP TO BE "FULLY" RATED TO WITHSTAND THE AVAILABLE
FAULT CURRENT AT M.D.P. OF 65,000 AMPS R.M.S.
2.THE DISTRIBUTION SYSTEM IS TO BE A "SERIES" RATED, TWO-TIER, 65/10 SYSTEM.
3.MOTOR LOAD CONTRIBUTION TO THESE PANELBOARDS SHALL NOT EXCEED 1.0%
OF THE PANELBOARD A.I.C. RATING.
4.WHERE "SERIES" RATING IS USED, PANELBOARDS AND DISTRIBUTION PANELS ARE
TO BE LEGIBLY MARKED TO INDICATE THE EQUIPMENT HAS BEEN APPLIED WITH A
"SERIES" COMBINATION RATING. LABELS CAN BE FACTORY INSTALLED OR
ENGRAVED PLASTIC-LAMINATE CARD. MARKING SHALL COMPLY WITH ARTICLE
110-22 OF N.E.C.
CONTROL ZONES
ZONE 1 KITCHEN LIGHTS & WORK LIGHTS
ZONE 2 DINING ROOM - GENERAL LIGHTS
ZONE 3 HOODS
ZONE 4 PARKING LOT LIGHTS
ZONE 5 EXTERIOR BUILDING LIGHTS/ BUILDING SIGNS/ MENU BOARDS
ZONE 6 NOT USED
ZONE 7 NOT USED
*SEE SHEET W1.1 FOR LIGHT ZONE CONTROL INFORMATION.
ARC FLASH LABELING
A.SWITCHBOARDS, PANELBOARDS AND BUSWAY SHALL HAVE A COMMERCIALLY
PRODUCED PERMANENT LABEL APPLIED, SIMILAR TO IMAGE BELOW, TO WARN OF
POTENTIAL ARC FLASH HAZARDS IN ACCORDANCE WITH NEC 110.16 AND NFPA 70E
B.LABELING MAY BE COMPLETED BY THE CONTRACTOR. THE CONTRACTOR SHALL
VERIFY THAT SWITCHBOARDS AND PANELBOARDS ARE PROPERLY LABELED IN THE
FIELD.
C.PROVIDE AND INSTALL A LABEL SIMILAR TO BELOW TO COMPLY WITH NEC 110.16
AND NFPA 70E. THE MARKING SHALL BE LOCATED SO AS TO BE CLEARLY TO
QUALIFIED PERSONS BEFORE EXAMINATION, ADJUSTMENT, SERVICING OR
MAINTENANCE OF THE EQUIPMENT. LABEL SHALL NOT BE LOCATED ON A HINGED
DOOR, OR A MOVABLE SERVICE.
PANEL
'C'
PANEL
'A'
PANEL
'B'
'COOK-
CENTER'
PANEL
PANEL
'MDP'
EXTERIOR WALL
POWER COMPANY
METER
WP C/T EQUIPMENT
CABINET
REFER TO SHEET W1.2
FOR MORE INFORMATION
ON 'FC/LC'
'LC'
LIGHTING
CONTROL
'FC'
FAN
CONTROL
CONTACT SUPPLIER FOR
SEISMIC BRACING.
SEE ARCHITECTURAL
SHEETS FOR CURB AT
SWITCHGEAR
NOTE: CONTRACTOR TO
ORDER ELECTRICAL PANEL
SYSTEM AT THE START OF
CONSTRUCTION GIVEN THE
6 WEEK LEAD TIME FOR THE
MODULAR PANEL SYSTEM.
CONTRACTOR TO PROVIDE
MECHANICAL AND
ELECTRICAL PLANS WHEN
PLACING ORDER.
SURGE PROTECTION
DEVICE
SPD
NOTE:
CONTRACTOR TO DOWNLOAD AND EXECUTE
MODULAR PANEL SYSTEM'S START UP AND
SYSTEM CHECK LIST REQUIREMENTS FROM
WENDY'S.
PANEL B RTU #2 *
208V
3PH, 3W
*SHUNT-TRIP BREAKER CONTROLLED
BY ANSUL SYSTEM. SHUTDOWN OF
POWER ON LOAD SIDE OF BREAKER
SHALL OCCUR ON ACTIVATION OF FIRE
SUPPRESSION SYSTEM OR UPON
MOMENTARY CONTACT OF
ELECTRICAL SHUT DOWN SWITCH "W"
SUB FEEDERS TO PANELS "A", "B", "C"
AND "COOKCENTER" ARE PREWIRED
AND PREINSTALLED INSIDE THE
MODULAR PANEL SYSTEM.
GND. 2/0
AWG, CU.
1
200/3
6
200/3*
SHUNT
TRIP
3
80/3*
SHUNT
TRIP
5
225/3*
SHUNT
TRIP
2/0 AWG, CU.
PANEL A
MDP
208/120V, 3 PHASE,
4 WIRE 65K AIC
PANEL
COOKCENTER*
MAIN WATER
SERVICE PIPE
REFER TO HVAC
CONNECTION
SCHEDULE IN
SHEET E3.2
C.T.
METER
800A. BUS
2
200/3
E.C. TO PROVIDE NEW WEATHERPROOF
C/T CABINET WITH 8OOA C/T IN
ACCORDANCE WITH UTILITY COMPANY
REQUIREMENTS.
80/3*
SHUNT
TRIP
PANEL C *
EC TO PROVIDE NEW 120/208V,
800A METER SOCKET IN
LANDLORD PROVIDED METER
BASE IN ACCORDANCE WITH
UTILITY COMPANY
REQUIREMENTS.
NEUT.
ISOLATED GROUND
2/0 AWG, CU.
BUILDING STEEL
2/0 AWG, CU.
#6 AWG, CU.
10'-0" COPPER
CLAD GND. ROD
G.C. AND UTILITY TO VERIFY CAPACITY OF EXISTING TRANSFORMER.
IF EXISTING TRANSFORMER ISN'T LARGE ENOUGH FOR UPGRADED
SERVICE SIZE, UTILITY TO UPGRADE TRANSFORMER.
E.C. TO PROVIDE TWO PARALLEL SETS OF
FOUR 600MCM EACH IN 4"CONDUIT
4
RTU #1 *
208V
3PH, 3W
ELECTRICAL DISTRIBUTION GENERAL NOTES
1.PANELS "A", "B" , "C" AND "COOKCENTER" SHALL BE CIRCUITED AS SHOWN.
2.THERMOSTATS TO BE PROVIDED WITH "FC/LC" FAN CONTROL/LIGHTING CONTROL PANEL ALONG WITH REMOTE SENSORS.
3.SYSTEM IS DESIGNED TO FORCE EXHAUST FANS ON WHEN ANSUL SYSTEM ACTIVATES TO MEET CODE REQUIREMENTS.
NEW PRE-PACKAGED,
PRE-WIRED
SWITCHGEAR MODULAR
PANEL SYSTEM
800/3P
MAIN CIRCUIT
BREAKER
NOT TO SCALE
ELECTRICAL ONE-LINE DIAGRAM 1NOT TO SCALE
ELECTRICAL DISTRIBUTION ELEVATION (CPI)3
GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFIGFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI
EC IS RESPONSIBLE FOR FIELD VERIFICATION OF SITE CONDITIONS AND REPORTING ANY DIFFERENCES
OR DISCREPANCIES TO ELECTRICAL ENGINEER PRIOR TO BID. NO EXTRAS OR CHANGE ORDERS SHALL BE
GIVEN FOR CONTRACTOR'S FAILURE TO VERIFY SITE CONDITIONS PRIOR TO BIDDING. UNLESS
SPECIFICALLY DETERMINED IN THE LEASE, IT IS THE RESPONSIBILITY OF THE TENANT TO INSTALL A
UTILITY OR SUB METER PER LANDLORD SPECIFICATIONS. ALL SUB METERS MUST BE FUNCTIONING
PROPERLY BEFORE TENANT OPENS FOR BUSINESS. THE TOTAL TENANT CONNECTED LOAD CANNOT
EXCEED THE LANDLORD SUPPLIED UTILITY.
ELECTRICAL CONTRACTOR SHALL VERIFY ALL EQUIPMENT VOLTAGE AND
AMPERAGE REQUIREMENTS PRIOR TO FINAL CONNECTION AND REPORT ANY
DIFFERENCES TO ENGINEER. DO NOT MAKE ANY FINAL CONNECTIONS IF
VOLTAGES SHOWN ON PLANS DO NOT MATCH EQUIPMENT DELIVERED.
·ALL KITCHEN 120V, SINGLE PHASE, 15A AND 20A RECEPTACLES SHALL BE GFI TYPE PER
NEC SECTION 210.8 (B).
·ALL GFCI RECEPTACLES SHALL BE INSTALLED IN A READILY ACCESSIBLE LOCATION OR A
GFCI CIRCUIT BREAKER SHALL BE USED TO FEED THE CIRCUIT NOTED.
·ALL 125V, 15A AND 20A CIRCUITS TO KITCHEN EQUIPMENT SHALL BE FED WITH A
DEDICATED NEUTRAL WIRE.
GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI
E.C. TO PROVIDE TWO PARALLEL SETS OF
FOUR 600MCM EACH IN 4"CONDUIT
GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI
79
6
M
e
r
u
s
C
o
u
r
t
St
.
L
o
u
i
s
,
M
O
6
3
0
2
6
T
6
3
6
.
3
4
9
.
1
6
0
0
F
6
3
6
.
3
4
9
.
1
7
3
0
CE
R
T
I
F
I
C
A
T
E
O
F
A
U
T
H
O
R
I
T
Y
N
O
.
3
8
0
0
11/26/2021
SEAL
DESCRIPTIONDATEREV.
ISSUE DATE: 08/17/2021
PROJECT NUMBER: 21-008
DRAWN BY:
CHECKED BY:
SHEET NAME
SHEET NUMBER
MO
O
D
Y
R
D
&
N
2
N
D
E
RE
X
B
U
R
G
,
I
D
8
3
4
4
0
PROJECT TYPE:
SITE NUMBER:
BUILDING TYPE:
OWNER:
BASE VERSION:
DRAWING RELEASE:
PROJECT YEAR:
ASSET TYPE:
CLASSIFICATION:
UPGRADE CLASSIFICATION:
DESIGN TYPE:
#13487
(2.0) SMART 40+
FREESTANDING
NEW
FRANCHISE
2020
NEW BUILD
2021
(2.0) UM BRITE
SUMMER
NEW
SMART 40+
1 10/20/2021 City Comments
2 11/26/2021 City Comments
ELECTRIC DISTRIBUTION
(GAS HEAT/GAS COOKING)
E3.1
KH
MJ
Verify use of concrete encased
electrode EUFFERF with #Q
copper wire between service
ground bar and "UFFER"
EORMKRMI ORMKROAPF
FUTURE BEE HIVE CREDIT UNION
SEAL
DESCRIPTIONDATEREV.
ISSUE DATE: **/**/****
PROJECT NUMBER: 21-008
DRAWN BY:
CHECKED BY:
SHEET NAME
SHEET NUMBER
MO
O
D
Y
R
D
&
N
2
N
D
E
RE
X
B
U
R
G
,
I
D
8
3
4
4
0
PROJECT TYPE:
SITE NUMBER:
BUILDING TYPE:
OWNER:
BASE VERSION:
DRAWING RELEASE:
PROJECT YEAR:
ASSET TYPE:
CLASSIFICATION:
UPGRADE CLASSIFICATION:
DESIGN TYPE:
#13487
(2.0) SMART 40+
FREESTANDING
NEW
FRANCHISE
2020
NEW BUILD
2021
(2.0) UM BRITE
SUMMER
NEW
SMART 40+
7629
T
OHADIFOETA
T
S
ER
DEREGIS
GREBEIFRFF
J
E
E
R
E
E
N
I
G
NEONALSI
E S
RO F
P
9/21/21
01 EXIST. SANITARY SEWER
02 EXIST. 16" WATER LINE
03 EXIST. FIRE HYDRANT
04 EXIST. WATER VALVE
05 EXIST. POWER POLE
06 EXIST. CURB & GUTTER, RETAIN & PROTECT
07 16" x 8" HOT TAP WITH 8" GATE VALVE
(SEE SHEET 4)
08 8" CLASS 50 DUCTILE IRON WATER LINE
(SEE SHEET 3.0)
09 20' - 8" CLASS 50 D.I. WATER LINE STUB
10 8" GATE VALVE
11 STD. FIRE HYDRANT RE: ISPWC SD-404
12 112" WATER SERVICE CONNECTION RE: CITY OF
REXBURG STD. DWG. 402
13 112" INTERIOR WATER METER RE: CITY OF
REXBURG STD. DWG. 402
14 112" HDPE WATER SERVICE LINE
15 112" HDPE LANDSCAPE WATER LINE
16 CITY APPROVED BACKFLOW PREVENTOR
17 4" x 8" SANITARY SEWER TEE
18 8" PVC SANITARY SEWER LINE
(SEE SHEET C3.0)
19 SANITARY SEWER MANHOLE
(SEE SHEET C3.0)
20 20' - 8" PVC SANITARY SEWER STUB @0.40%
21 4" PVC SDR35 SANITARY SEWER SERVICE LINE
22 1500 GALLON TRAFFIC RATED GREASE TRAP
23 4" TRAFFIC RATED CLEAN-OUT
RE: ISPWC SD-506A
24 RMP TRANSFORMER RE: ELECTRICAL SITE PLAN
25 UNDERGROUND ELECTRICAL CONDUIT
RE: ELECTRICAL SITE PLAN
26 GAS LINE - TRENCH BY SITE CONTRACTOR, GAS
LINE AND METER BY IMG.
27 DELIVERY ACCESS RAMP
28 ADA RAMP; RE: B2 / C4.0
29 4" YELLOW PAVEMENT MARKING
30 WHITE PAVEMENT MARKING WHERE SHOWN
31 ADA PARKING PAVEMENT MARKINGS WITH
RESERVED PARKING SIGN
32 4' WIDE TRUNCATED DOME PANEL
33 WHITE PAINTED CROSSWALK
34 4" WIDE YELLOW PARKING STRIPE
35 DUMPSTER ENCLOSURE RE: ARCHITECTURAL
PLANS (NO GATES)
36 PEDESTAL SIGN RE: ELECTRICAL SITE PLAN
37 SITE LIGHTING RE: ELECTRICAL SITE PLAN
38 PRE-SELL BOARD
39 ORDER STATION
40 2" CALIPER DECIDUOUS TREES @ 30' O.C.
(5 EACH) (SEE LANDSCAPING PLAN L1.00)
41 TURF SEEDING / SOD
(SEE LANDSCAPING PLAN L1.00)
42 LARGE SHRUB / SCREENING SHRUB
(SEE LANDSCAPING PLAN L1.00)
43 SMALL SHRUB (SEE LANDSCAPING PLAN L1.00)
44 4" GREASE LINE
45 4" WASTE LINE
46 8" THICK CONCRETE PAD
47 FUTURE BEEHIVE CREDIT UNION SERVICE LINES
48 SNOW STORAGE
49 SAFETY RAILING RE: 9/C5.3
50 STEEL BOLLARDS RE: 12/C5.3
51 PEDISTRIAN AREA AND BENCH
52 CITY STREET LIGHT (LOCATION TO BE
DETERMINED)
#
SITE/UTILITY PLAN
C1.0
01
02
03
0405
06
07
08
10 09
11
12
13
14
15
17
18
18
19
19
19
20
20
21
22
23
24
25
26
27
28
08
2930
31
32
33
34
29
2929
34
35
36
37
38
38
39
39
40 41
41
42
42
43
43
43
43
44
45
46
47
SITE INFORMATION
SNOW STORAGE
SURFACE AREA - 14,350 SQ. FT.
STORAGE AREA REQUIRED - 1,435 SQ. FT.
STORAGE AREA PROVIDED - 2,492 SQ. FT.
SNOW STORAGE FOR PRIVATE ROAD WILL BE
ALONG THE EAST AND SOUTH SIDE
RESPECTIVELY
LANDSCAPE
LOT AREA - 29,666 SQ. FT.
LANDSCAPE REQUIRED - 2,967 SQ. FT. (10%)
LANDSCAPE PROVIDED - 5,020 SQ. FT.
48 48
48
48
48
48
49
50
50
51
16
52