HomeMy WebLinkAboutREVISIONS 2 - 21-00694 - 240 E Moody - Wendy's - New BuildingGENERAL NOTES
A. PAY ALL FEES AND ARRANGE FOR EXECUTION OF ALL TAPS, METERS WITH REQUIRED
ENCLOSURES (IF ANY), AND APPURTENANCES INHERENT TO THE INSTALLATION OF PLUMBING
SERVICE.
B. PROVIDE ALL LABOR, EQUIPMENT, AND MATERIALS NECESSARY TO EXECUTE THE PLUMBING
WORK INDICATED ON THE DRAWINGS AS SPECIFIED, AND AS REQUIRED BY LOCAL CODES AND
ORDINANCES. PLUMBING WORK SHALL INCLUDE ALL PIPING FOR DOMESTIC HOT AND COLD
WATER LINES, VENT AND SANITARY LINES, HOOK-UP OF ALL FIXTURES SCHEDULED ON THE
DRAWINGS, AND INSULATION OF DESIGNATED PIPING. WORK SHALL ALSO INCLUDE ALL GAS
PIPING AND EQUIPMENT CONNECTIONS WHERE REQUIRED. INCLUDE ALL ITEMS SUCH AS
FITTINGS NOT MENTIONED BUT UNDERSTOOD TO BE NECESSARY TO COMPLETE THE
PLUMBING SYSTEM. COORDINATE ALL WORK WITH OTHER CONTRACTORS.
C. PROVIDE FOR DRAINING WATER SYSTEM AND CAP ALL STUBS UNTIL FINISH WORK IS
INSTALLED. INSTALL DRAIN VALVE AT WATER METER WITH 3/4" HOSE THREAD AND VACUUM
BREAKER.
D. PROVIDE VALVES ON WATER SUPPLIES TO EACH FIXTURE & EQUIPMENT. VALVES SHALL BE 1/4
TURN SHUT-OFF VALVES.
E. INSULATE ALL PIPING PER SPECIFICATIONS.
F. PLUMBING FIXTURES SHALL BE PROVIDED WHERE SHOWN ON DRAWINGS. FIXTURE FITTINGS
AND EXPOSED FIXTURE PIPING SHALL BE BRASS CHROMIUM PLATED. TRAPS SHALL BE CAST
BRASS. FIXTURES SHALL BE EQUAL IN ALL RESPECTS TO FIXTURES SPECIFIED.
G. PROVIDE ROUGH-IN AND FINAL CONNECTIONS OF REQUIRED WASTE, VENT, AND WATER
SUPPLY PIPING.
H. THIS CONTRACTOR SHALL GUARANTEE ALL WORK INSTALLED UNDER THE CONTRACT TO BE
FREE FROM DEFECTIVE WORKMANSHIP AND MATERIALS, (USUAL WEAR IS EXPECTED), AND
SHOULD DEFECTS DEVELOP WITHIN A PERIOD OF ONE YEAR AFTER ACCEPTANCE OF THE
BUILDING BY THE OWNER, THIS CONTRACTOR SHALL REPAIR AND/OR REPLACE DEFECTIVE
ITEMS AND ALL DAMAGE RESULTING FROM FAILURE OF THESE ITEMS, AT NO EXPENSE
WHATSOEVER TO THE OWNER
I. THE DIRECTION OF THE SANITARY MAIN AND THE LOCATION OF THE GREASE INTERCEPTOR
SHALL BE COORDINATED WITH CIVIL DRAWINGS PRIOR TO ROUGH-IN.
J. PROVIDE PROVENT TRAP GUARD (OR APPROVED EQUAL) AT ALL FLOOR DRAINS. PROVIDE
TRAP PRIMERS ON FLOOR DRAINS ONLY IF REQUIRED BY AUTHORITY HAVING JURISDICTION
(AHJ). IF AHJ REQUIRES TRAP PRIMERS, LAYOUT DISTRIBUTION TO CONNECT MULTIPLE FLOOR
DRAINS TO ONE TRAP PRIMER.
K. COORDINATE LOCATION AND ROUGH-IN HEIGHT OF KITCHEN EQUIPMENT WITH OWNER AND
MILLWORK PRIOR TO ROUGH-IN.
L. PROVIDE WATER HAMMER ARRESTORS AT END RUN OF ALL WATER PIPING. SIZE AND LOCATE
AS RECOMMENDED BY PLUMBING AND DRAINAGE INSTITUTE STANDARD PDI-WH201, AND AS
RECOMMENDED BY THE MANUFACTURER.
M. ALL PIPING (GAS AND WATER) SHALL BE CONCEALED IN WALL SPACE WHEN POSSIBLE,
UNLESS NOTED OTHERWISE.
N. DAMAGES TO EXISTING WALLS, FLOORS, FINISHES ETC. BY THIS CONTRACTOR SHALL BE
REPAIRED AT THIS CONTRACTOR'S EXPENSE.
O. WATER HEATER, WATER METER AND BACKFLOW PREVENTER SHALL BE INSTALLED TO MEET
ALL STATE, COUNTY AND LOCAL JURISDICTION CODES.
P. ON ALL SYNFLEX LINE INSTALLATIONS (EXCEPT DRINK STATIONS AND COFFEE BREWER)
TRANSITION TO COPPER AT TOP OF WALL, AND ROUTE DOWN INSIDE WALL AND THEN
THROUGH WALL TO EXPOSED SHUT OFF VALVE. DRINK STATIONS WILL HAVE SYNFLEX LINES
FROM FILTER TO UNIT INSTALLED BY BEVERAGE SYSTEM INSTALLER.
Q. 3 COMP SINK, COMBI OVEN AND 2 AREA FLOOR DRAINS BETWEEN HOOD AREA SHALL BE
ROUTED TO GREASE WASTE LINE. ALL OTHER DRAINS SHALL BE ROUTED TO BUILDING
SANITARY.
R. ALL WATER SUPPLY LINES, VENT STACK LINES, SANITARY LINES, AND OTHER EXPOSED
PLUMBING LINES SHALL BE COMPLETELY SEALED AT ALL WALL PENETRATIONS. PROVIDE
CHROME ESCUTCHEON PLATE SEALED TO WALL WITH SILICONE SEALANT.
S. SEE CONNECTION SCHEDULE FOR ALL INDIVIDUAL PIPE SIZES.
WATER CALCULATION
CRITICAL ELEVATIONS AND DISTANCES: FEET
ELEVATION OF CONTROLLING FIXTURE (WATER CLOSET)4.0
ELEVATION OF FINISHED FLOOR 0.0
ELEVATION OF WATER MAIN -4.0
ELEVATION OF WATER ENTRY -4.0
VERTICAL DIST. FROM WATER MAIN TO CONTROLLING FIXTURE 8.0
SYSTEM PRESSURE REQUIREMENTS:PSI
ELEVATION (VERTICAL DISTANCE) X 0.434 PSI/FT 3.5
PRESSURE NEEDED AT CONTROLLING FIXTURE 20.0
BACKFLOW PREVENTER: 1-1/2" AT 66 GPM 8.0
WATER METER: 1-1/2" AT 66 GPM 10.0
TOTAL 41.5
PIPE RUNS:FEET
EXTERIOR, MAIN TO BUILDING ENTRY 100.0
EXTERIOR, VERTICAL RISE 0.0
INTERIOR, ENTRY TO CONTROLLING FIXTURE 60.0
INTERIOR, VERTICAL RISE 8.0
ALLOWANCE FOR FITTINGS, ETC. (LENGTH X 0.25)42.0
TOTAL 210.0
SYSTEM PRESSURE DATA: PSI
STREET PRESSURE 80.0
SYSTEM PRESSURE REQUIRED 41.5
PRESSURE AVAILABLE FOR (PIPING) FRICTION LOSS 38.5
PIPE SIZING:PSI/100'
PRESSURE AVAILABLE X 100 / (TOTAL PIPE RUN)18.3
* NOTE: ALL PIPING IS SIZED FOR 5 PSI/100' PRESSURE LOSS
REFER TO WENDY'S CONSOLIDATOR LIST
TO OBTAIN BUILDING MATERIAL QUOTES.
REFER TO WENDY'S APPROVED SUPPLIER
LIST FOR PHONE NUMBERS AND CONTACTS.
ATTENTION ALL BIDDERS
REMARKS (#)
FIXTURE & EQUIPMENT CONNECTION SCHEDULE
SY
M
B
O
L
QU
A
N
T
I
T
Y
GENERAL FIXTURE DESCRIPTION
DOMESTIC WATER SANITARY
NATURAL
GAS
US
E
D
C
O
O
K
I
N
G
O
I
L
REMARKS (#)
FI
L
T
E
R
E
D
W
A
T
E
R
-
F
C
W
1
FI
L
T
E
R
E
D
W
A
T
E
R
-
F
C
W
2
FI
L
T
E
R
E
D
W
A
T
E
R
-
F
C
W
3
FI
L
T
E
R
E
D
W
A
T
E
R
-
F
C
W
4
CO
L
D
W
A
T
E
R
HO
T
W
A
T
E
R
(
1
4
0
°
)
HO
T
W
A
T
E
R
(
1
1
0
°
)
MO
U
N
T
I
N
G
H
E
I
G
H
T
DR
A
I
N
L
I
N
E
S
I
Z
E
TR
A
P
FI
X
T
U
R
E
D
R
A
I
N
DI
R
E
C
T
/
I
N
D
I
R
E
C
T
(
D
/
I
)
SA
N
I
T
A
R
Y
/
G
R
E
A
S
E
(
S
/
G
)
VE
N
T
MO
U
N
T
I
N
G
H
E
I
G
H
T
CO
N
N
E
C
T
I
O
N
S
I
Z
E
BT
U
L
O
A
D
PLUMBING FIXTURES
WC 2 WATER CLOSET (ACCESSIBLE)114"(1)4" INT 4" D S 2" FL
(3), (6)
LAV-1 2 LAVATORY
12"12"(1)112"112"112"D S1
12"(1) (3), (6)
LAV-2 1 LAVATORY 12"12"(1)112"112"112"D S1
12"(1) (3), (6)
FPWH 2 FROST PROOF WALL HYDRANT
3 4"18"(3), (6)
PLUMBING DRAINS
FD 11 FLOOR DRAIN 3" 3" * 1
12"FL (3), (8), (9)
FS-1 4 FLOOR SINK 3" 3" * 1
12"FL (3), (8), (9)
FS-2 1 FLOOR SINK 3" 3"*112"FL (3), (8), (9)
HD 1 HUB DRAIN 3" 3" * 1
12" 12"
(3), (8), (9)
KITCHEN EQUIPMENT - FRONT COUNTER
E2302 1 BACK COUNTER HAND SINK
12"12"14"2"112"112"D S1
12" 12"
(4), (6), (8), (9)
KITCHEN EQUIPMENT - BEVERAGE LINE
A0105 1
BEVERAGE SYSTEM (DRIVE-THRU)12"14"IS (4), (14), (15)
A0608 1 COFFEE BREWER
12"14"(4), (10), (11)
E4006 1 DRIVE-THRU HAND SINK ASSEMBLY 12"12"14" 2"112"112"D S1
12"(4), (8), (9)
KITCHEN EQUIPMENT - FRYLINE
K1401 1 COMBI OVEN 12"12" 30" 3" 3" I G 1
12"(5), (10), (11)
KITCHEN EQUIPMENT - PREP AREA / WAREWASH
A0801 1 TEA BREWER *
12" 72"
(4), (10), (11)
T1213 1 CHEMICAL BLEND STATION (FOR
T2011)12"12"54"(4)
T0902 1 1 COMP PREP SINK
12"12"14"(4), (6), (7), (8),
(9)
T2011 1 3 COMP SINK
12"12"14"(4), (6), (7), (8),
(9)
T2061 1 WAREWASH MACHINE
12"3 4"61.75" 3" 3"2" I G 1
12"(4), (6), (7), (8),
(9), (10)
KITCHEN EQUIPMENT - HAND SINK
T2703 1 HAND SINK
12"12"14"2"112"112"D S1
12" 12"
(4), (6), (8), (9)
KITCHEN EQUIPMENT - DRINK EQUIPMENT
QP0909 1 ICE MAKER - KITCHEN
12" 72" 3" 3"
3 4"I S1
12"(4), (6), (7),
(10)
T2212 1 WATER TREATMENT UNIT
3 4"85"(4), (11), (13)
KITCHEN EQUIPMENT - MOP SINK / CLEANING EQUIPMENT
T0303 1
MOP SINK FAUCET (FOR T0602 -
LOWER)12"12"36"(4), (6)
T0304 1
MOP SINK FAUCET (FOR T0602 -
UPPER BLEND CENTER)12"12"54"(4), (6)
T0602 1 MOP SINK 3" 3" 3" D S 1
12"FL (4), (6)
T1212 1 CHEMICAL BLEND CENTER
12"12"54"(4)
T2213 1 REVERSE OSMOSIS SYSTEM
12"12"85"(5)
A0304 1 BAG-IN-BOX
12"85"(5), (11), (12)
KITCHEN EQUIPMENT - DRINK STAND
A0202 2 BEVERAGE SYSTEM (SELF-SERVE -
DINING ROOM)12"14"IS (4), (14), (15)
QP0222 2 ICE MAKER (CUBER) - DINING ROOM 12" 96" 3" 3"
3 4"I S1
12"(4), (6), (7),
(10)
*VERIFY QUANTITIES WITH ARCHITECTURAL EQUIPMENT PLAN AND SCHEDULE.*
1. REFER TO MANUFACTURER'S INSTALLATION INSTRUCTIONS.
2. PLUMBING FIXTURE PROVIDED BY PLUMBING INSTALLER.
REFER TO PLUMBING FIXTURE SCHEDULE
3. EQUIPMENT FURNISHED BY OTHERS.
4. PLUMBING INSTALLER TO MAKE FINAL CONNECTIONS TO
EQUIPMENT.
5. FINAL CONNECTION TO EQUIPMENT BY OTHERS.
6. PROVIDE VALVE AT EACH CONNECTION TO EQUIPMENT.
7. PLUMBING CONTRACTOR TO PROVIDE INDIRECT DRAIN TO
FLOOR DRAIN OR SINK.
8. VERIFY DIRECT OR INDIRECT WASTE CONNECTION PER
LOCAL CODE REQUIREMENTS.
9. VERIFY SANITARY OR GREASE WASTE CONNECTION PER
LOCAL CODE REQUIREMENTS.
10. SHUTOFF VALVE AND FLEX CONNECTOR LINES TO
PRE-RINSE ARE PROVIDED WITH FIXTURE.
11. PROVIDE WITH BACKFLOW PROTECTION PER BACKFLOW
PREVENTOR SCHEDULE. COORDINATE BACKFLOW
INSTALLATION WITH KITCHEN EQUIPMENT PROVIDER AND
BEVERAGE INSTALLER.
12. PROVIDE WITH WATTS NO. SS009 BACKFLOW PREVENTER
WHEN LOCAL JURISDICTION REQUIRES A HIGHER LEVEL OF
PROTECTION THAN PROVIDED BY THE INTEGRAL ASSE 1022
DOUBLE CHECK VALVE.
13. PLUMBING INSTALLER TO RUN WATER LINE TO FILTRATION
SYSTEM WITH FINAL CONNECTIONS BY BEVERAGE
INSTALLER.
14. BEVERAGE INSTALLER TO ROUTE LINE TO POINT OF USE
AND PLUMBING INSTALLER TO MAKE FINAL CONNECTION.
15. WATER SUPPLY LINE IS PART OF THE BEVERAGE BUNDLE.
PUMP SCHEDULE
SYMBOL MANUF. MODEL GPM
HEAD
(FT)VPHA W
NOTES
(#)
RCP GRUNDFOS ALPHA2 5 12 115 1 0.65 5 - 65
(1)
NOTES:
1.RECIRCULATING PUMP: BRONZE BODY RECIRCULATING PUMP WITH "AUTOADAPT" VARIABLE
SPEED MOTOR, INSTALL NEAR WATER HEATER PER MANUFACTURER'S INSTRUCTIONS. PROVIDE
WITH ALPHA 3-PRONG PLUG AND COORDINATE CONNECTION WITH ELECTRICAL CONTRACTOR.
PROVIDE WITH HONEYWELL L6006C SURFACE MOUNT AQUASTAT SET TO 5°F BELOW WATER
HEATER OPERATING TEMPERATURE.
WSFU CALCULATIONS
FIXTURE QTY.WSFU TOTAL
WATER CLOSET (FLUSH)21020
LAVATORY 3 2 6
MOP BASIN 1 33
HAND SINK 3 2 6
1-COMP SINK 1 4 4
3-COMP SINK 1 44
WAREWASH 1 3 3
BEVERAGE STATION 3 1 3
BAG-N-BOX 1 33
ICE MAKER 3 1 3
COMBI-OVEN 1 1 1
COFFEE BREWER 1 0.5 0.5
TEA BREWER 1 0.5 0.5
HOSE BIBB 2 36.0
*WSFU VALUES GIVEN PER IPC* WSFU TOTAL 63.00
DFU CALCULATIONS
FIXTURE QTY.DFU TOTAL
WATER CLOSET (FLUSH)248
LAVATORY 3 1 3
MOP BASIN 1 2 2
HAND SINK 3 1 3
3" HUB DRAIN 1 5 5
3" FLOOR SINK 7 5 35
3" FLOOR DRAIN
(EMERGENCY)9--
*DFU VALUES GIVEN PER IPC* DFU TOTAL 56.0
EXPANSION TANK SCHEDULE
SYMBOL MANUF.MODEL GAL.
ACCEPT.
GAL.
CONN.
LOC.
CONN.
SIZE MOUNTING NOTES
(#)
ET-1 AMTROL ST-8 4.4 3.2 TOP
3 4"ABOVE WH-1 (1), (2)
NOTES:
1. EXPANSION TANK: STEEL SHELL, HEAVY DUTY BUTYL NSF/ANSI 61, FACTORY PRECHARGED TO
50 PSIG. MAX OPERATING TEMPERATURE 200°, MAX OPERATING PRESSURE 150 PSI, 1 YEAR
MANUFACTURER'S WARRANTY. INSTALL PER MANUFACTURER'S INSTRUCTIONS.
2.FIELD CHARGE EXPANSION TANK TO SYSTEM PRESSURE BEFORE CONNECTION TO DOMESTIC
WATER SYSTEM. FIELD VERIFY PRESSURE REQUIREMENTS.
GREASE INTERCEPTOR SIZING
FIXTURE QTY.FLOW RATE
(2 MIN)
FLOW RATE
(1 MIN)
FLOOR DRAIN 3 0.00 0.00
FLOOR SINK 8 0.00 0.00
MOP BASIN 1 9.35 18.70
THREE COMP SINK 1 30.00 60.00
DISHWASHER 1 5.00 10.00
TOTAL FIXTURE FLOW RATE 44.35
CALCULATED FLOW
RATE
(GPM)
PIPE SIZE FLOW RATE (4 IN)75 44.35
[(CU IN / 231) = GAL X 0.75 / 2 MIN = 2 MIN FLOW RATE]
NUMBER OF SEATS 55
GREASE PRODUCTION
(LBS OF FOG)
AVG. MEALS PER SEAT PER DAY 4 693.0
FAST FOOD - FULL PREP
(HIGH / NO FLATWARE: 0.035 LBS PER SERVING)0.035
DAYS BETWEEN PUMP OUTS 90
[SERVINGS PER DAY X GREASE PRODUCTION VALUE X DAYS BETWEEN PUMP-OUTS = GREASE
OUTPUT]
BACKFLOW PREVENTER SCHEDULE
LOCATION TAG MODEL ASSE
MAIN WATER SUPPLY RPZ WATTS LF009-QT-S 1013
CARBONATOR DCV-1 WATTS SD-3 1022
SODA DISPENSORS DCV-2 WATTS SD-2 1022
OTHER EQUIPMENT DCV-3 WATTS SERIES 7 1024
NOTE:
VERIFY BACKFLOW VALVE REQUIREMENTS AND APPROVAL FOR ALL EQUIPMENT WITH AUTHORITIES
HAVING JURISDICTION PRIOR TO INSTALLATION.
GAS FIRED WATER HEATER SCHEDULE
SYMBOL MANUF. MODEL GAL. BTU
GAS
PRESSURE
RECOVERY
(GPH/100°F)
SET POINT
(°F)
NOTES
(#)
WH-1 BRAFDORD
WHITE
EF-100T-1
99E-3N 100 199,999 7" W.C. 235 140
(1), (2)
NOTES:
1.GAS FIRED WATER HEATER: THREE YEAR TANK/PARTS WARRANTY, GLASS LINED STEEL TANK,
150 PSI WORKING PRESSURE, THERMAL EFFICIENCY OF 97% MEETING CURRENT EDITION OF
ASHRAE 90.1B AND LOCAL ENERGY CONSERVATION REQUIREMENTS. PROVIDE T&P RELIEF
VALVE.
2.FURNISH WITH EXPANSION TANK AS SPECIFIED ON PLANS.
ELECTRIC WATER HEATER SCHEDULE
SYMBOL MANUF.MODEL GAL. KW V PH FLA
RECOVERY
(GPH/90°F)
SET POINT
(°F)
NOTES
(#)
WH-2 BRADFORD
WHITE LE16U3 6 6 208 1 28.8 25 140
(1), (2)
NOTES:
1.ELECTRIC WATER HEATER: THREE YEAR TANK/PARTS WARRANTY, GLASS LINED STEEL TANK,
150 PSI WORKING PRESSURE, MEETING CURRENT EDITION OF ASHRAE 90.1B AND LOCAL
ENERGY CONSERVATION REQUIREMENTS (SMALL TANK WATER HEATERS BELOW 20 GALLONS
ARE EXEMPT FROM NAECA REQUIREMENTS AND ASHRAE 90.1). PROVIDE T&P RELIEF VALVE.
2. FURNISH WITH EXPANSION TANK AS SPECIFIED ON PLANS.
BV BALL VALVE
GW
D
G
UCO
FW
SANITARY WASTE (SAN) - BELOW SLAB/GRADE
PLUMBING VENT (V) - BELOW SLAB/GRADE
GREASE WASTE (GW) - BELOW SLAB/GRADE
USED COOKING OIL (UCO)
PLUMBING VENT (V)
CONDENSATE LINE (D)
HOT WATER RETURN (HWR) 140°, 120°
GAS LINE (G)
NSF 61 TUBING (NSF) [BY OTHERS]
FILTERED WATER SUPPLY (FW)
HOT WATER (HW) 140°, 120°
COLD WATER (CW) - BELOW SLAB/GRADE
COLD WATER (CW)
NSF
BFP
RI
BACKFLOW PREVENTER
ROUGH-IN
AFF/AFG
FCO/ECO
VTR
IW
WCO/CO
ABOVE FINISHED FLOOR/GRADE
FLOOR/EXTERIOR CLEANOUT
WALL CLEANOUT/ CLEANOUT
VENT THRU ROOF
INDIRECT WASTE
TYPICALTYP
AHJ
UNO
AUTHORITY HAVING JURISDICTION
UNLESS NOTED OTHERWISE
ABBREVIATIONS: LINETYPES:
END CAP
SHUTOFF VALVE (BALL TYPE)
TEE TURNING UP/DOWN
PIPE TURNING UP/DOWN
CHECK VALVE
BALANCING VALVE
PIPE SYMBOLS:
WALL HYDRANT
RO REVERSE OSMOSIS WATER SUPPLY (RO)
*NOT ALL SYMBOLS OR LINETYPES ARE NECESSARILY USED*PLUMBING SYMBOLS LEGEND
GREASE INTERCEPTOR SCHEDULE
SYMBOL MANUF. MODEL
FLOW RATE
(GPM)
GREASE
CAPACITY (LBS.)
LIQUID CAPACITY
(GAL.)NOTES (#)
GI SCHIER GB-250 100
1,895 277 (1), (2), (3)
NOTES:
1. CONTRACTOR SHALL SUBMIT PROPOSED GREASE INTERCEPTOR INSTALLATION PLANS AND
SPECIFICATIONS TO LOCAL AUTHORITIES FOR THEIR APPROVAL BEFORE ACQUISITION. SEE
MANUFACTURER INSTALLATION MANUAL FOR ADDITIONAL INSTRUCTIONS.
2.PROVIDE WITH C24HP H20 LOAD RATED PICKABLE CAST IRON LIDS WITH "SAFE MANWAY" FALL
PROTECTION COVER.
3. PROVIDE WITH AK1 ANCHOR KIT.
PLUMBING FIXTURE SCHEDULE
SYMBOL FIXTURE TYPE MANUF.MODEL DESCRIPTION ACCESSORIES/OPTIONS
NOTES (#)
WC WATER CLOSET
(ACCESSIBLE)SLOAN ST-2029
(2102029)
FLOOR MOUNT, WHITE VITREOUS CHINA, 1.1-1.6 GPF
ELONGATED SIPHON JET BOWL, 1-1/2" TOP SPUD, & RIM
HEIGHT 17" A.F.F.
TOTO #TMT1LN32#CP 1.28 GPF MANUAL WATER CLOSET
FLUSH VALVE. MAINLINE #ML1055SSC00 WHITE OPEN FRONT
ELONGATED TOILET SEAT LESS COVER.
(1), (4)
LAV-1 LAVATORY
(ACCESSIBLE)
AMERICAN
STANDARD
#0356.421.020
LUCERNE WALL HUNG, 2012"x1814", WHITE VITREOUS CHINA.TOTO #TL210DD12#CP POLISHED CHROME, LAVATORY
FAUCET, 1.2 GPM FLOW RATE (1), (2), (3), (4)
LAV-2 LAVATORY
(ACCESSIBLE)DURAVIT
D17511
(#0454120060)
VERO
WALL HUNG WASHBASIN, 4714"x1812", WHITE VITREOUS
CHINA,WITH CHROME METAL CONSOLE AND NO FAUCET
HOLES, SINGLE HOLE FOR FAUCET, & BACK OVERFLOW.
ROHL A1423LMAPC-2 "ACQUI WALL MOUNT BRIDGE
FAUCET", POLISHED CHROME, 8" WALL MOUNT, 10" SWIVEL
SPOUT, 1.2 GPM AERATOR. PROVIDE WITH CROW WORKS
27" HIGH GUNMETAL SINK STAND
(1), (2), (4), (5)
WB COMBI OVEN
WATER BOX SIOUX CHIEF 696-G2403WF
WHITE ABS WATER SUPPLY BOX WITH 3/4" HOSE THREAD,
AND PEX-A F1960 CONENCTIONS.INSTALL PER "COMBI OVEN SUPPLY BOX ROUGH-IN" DETIAL.
FPWH FROST PROOF
WALL HYDRANT WOODFORD MODEL 65
ANTI-SIPHON, AUTOMATIC DRAINING, WALL HYDRANT,
NON-FREEZE INTEGRAL VACUUM BREAKER, ALL BRONZE
INTERIOR PARTS, KEY OPERATED, 3/4" SOLDER INLET.
MOUNT 18" ABOVE FINISHED GRADE. PROVIDE
APPROPRIATE MODEL FOR WALL THICKNESS AND SITE
SPECIFIC TEMPERATURE REQUIREMENTS.
(4)
FD FLOOR DRAIN SIOUX CHIEF /
ZURN
832-35D-NR /
#ZN415-B-3NH
FLOOR DRAIN WITH 5" ROUND NICKEL BRONZE ADJUSTABLE
STRAINER AND CAST IRON BODY & 3" BOTTOM OUTLET.
PROVIDE WITH ASSE 1072 APPROVED TRAP SEAL DEVICE.
TRAP SEAL DEVICE SHALL BE TRAP PROSET TRAPGUARD
OR APPROVED EQUAL. INSTALL PER MANUFACTURER'S
RECOMMENDATIONS. PROVIDE DRAINS IN CUSTOMER
AREAS WITH VANDAL RESISTANT SCREWS.
(4)
FS-1 FLOOR SINK SIOUX CHIEF /
ZURN
#861-3PN-D /
#Z1900-3NH-K-4
12" SQUARE TOP FLOOR SINK W/8" DEEP PVC/CAST IRON
BODY & 3" BOTTOM OUTLET (CAST IRON OPTIONAL)(4)
FS-2 FLOOR SINK SIOUX CHIEF /
ZURN
#861-23X-N2 /
#Z1900-3NH-2NB
12" SQUARE TOP FLOOR SINK WITH 6" DEEP ACID
RESISTANT ENAMEL CAST IRON BODY AND 3"OUTLET WITH
12 NICKEL BRONZE GRATE.
SET FLOOR SINK LEVEL WITH FINISH FLOOR.(4)
HD HUB DRAIN N/A N/A
STUB 3" WASTE LINE 12" ABOVE FINISHED FLOOR SLAB FOR
FUTURE CONNECTIONS BY OTHERS.
PROVIDE WITH ASSE 1072 APPROVED TRAP SEAL DEVICE.
TRAP SEAL DEVICE SHALL BE TRAP PROSET TRAPGUARD
OR APPROVED EQUAL. INSTALL PER MANUFACTURER'S
RECOMMENDATIONS.
(4)
MV MIXING VALVE ZURN
ZW3870XLT /
ZW1070XL
THERMOSTATIC CONTROLLER WITH INTEGRAL CHECKS, ALL
BRASS BODY WITH DUAL STAINLESS STEEL STRAINER,
VANDAL RESISTANT TEMPERATURE ADJUSTMENT HANDLE.
SET TO 105°F. MOUNT IN ACCESSIBLE LOCATION.(4)
NOTES:
1.INSTALL IN ACCORDANCE TO ADA ACCESSIBILITY REQUIREMENTS.
2.PROVIDE WITH QUARTER TURN BRASS ANGLE COMPRESSION STOPS WITH LOOSE KEY HANDLES, STAINLESS BRAIDED SUPPLIES, CHROME SUPPLY AND DRAIN ESCUTCHEONS, CHROME GRID STRAINER
DRAIN WITH TAILPIECE, CHROME PLATED CAST BODY P-TRAP WITH CLEANOUT. INSULATE WASTE AND WATER PIPING WITH TRUEBRO "LAV-GUARD2" #101-EZ.
3. FURNISH WITH ZURN #Z-1231-81 LAVATORY CARRIER.
4.REFER TO ARCHITECTURAL SUPPLIER PAGE FOR WENDY'S NATIONAL VENDOR PRICING CONTACTS. VERIFY PRIOR TO BID IF GENERAL CONTRACTOR OR OWNER WILL PROVIDE EQUIPMENT.
PLUMBING SCHEDULE
AND NOTES
P1.0
AUTHOR
CHECKER
79
6
M
e
r
u
s
C
o
u
r
t
St
.
L
o
u
i
s
,
M
O
6
3
0
2
6
T
6
3
6
.
3
4
9
.
1
6
0
0
F
6
3
6
.
3
4
9
.
1
7
3
0
CE
R
T
I
F
I
C
A
T
E
O
F
A
U
T
H
O
R
I
T
Y
N
O
.
3
8
0
0
8/18/2021
SEAL
DESCRIPTIONDATEREV.
ISSUE DATE: 08/17/2021
PROJECT NUMBER: 21-008
DRAWN BY:
CHECKED BY:
SHEET NAME
SHEET NUMBER
MO
O
D
Y
R
D
&
N
2
N
D
E
RE
X
B
U
R
G
,
I
D
8
3
4
4
0
PROJECT TYPE:
SITE NUMBER:
BUILDING TYPE:
OWNER:
BASE VERSION:
DRAWING RELEASE:
PROJECT YEAR:
ASSET TYPE:
CLASSIFICATION:
UPGRADE CLASSIFICATION:
DESIGN TYPE:
#13487
(2.0) SMART 40+
FREESTANDING
NEW
FRANCHISE
2020
NEW BUILD
2021
(2.0) UM BRITE
SUMMER
NEW
SMART 40+
1 10/20/2021 City Comments
EX
T
.
R
A
M
P
LCA672LCE6120
V2201
SHARED\xUS2.0-P1-1 Base.dwg
1PLUMBING PLAN - SANITARY WASTE & VENT
1/4" = 1'-0"
SEE SITE PLAN FOR
CONTINUATION
GW
UTILITY
116
1
2
3
3
T2061
QP0909
A0105
T2011
T0902
T0602
T2703
T2703
E2302
ECO
4"
ECO
FD
FCO
FD
4"
4"
3"
4"
3"
2"
FCO
FD
2
4"
4"
4"
3"
4"
FS-1
FD
FD
FCO
3
FD
WCO
3"
4"4"3"
3"
3"
3"
3"
3"
4"
2"2"
GW
GW
GW
4"
4"
4"
3"
3"
UC
O
3 4"
6
INSTALL USED OIL
SYSTEM PER VENDOR
INSTRUCTIONS.WC
WC
LAV-1
LAV-1
3
3"3"
3"
4"4"4"
3"
2"2"
2"
3"
112"
2"
2"
112"
112"
112"2"
WCO
WCO
FS-1 FS-1
WH-18
4"
QP0222
FS-1
FCO
3"
GW
9
5
1"
CO
1"
3" HD
4"
3"
A0202
4"
GI
FDFD
3"
K1401 J1004
43"VTR
FD
WC
2"
3"
2"
2"
9
3
3"
3"
4
7
MAINTAIN SEPARATION BETWEEN UCO, SANITARY
LINES, VENT LINES, AND WATER LINES IN THIS
WALL. MAINTAIN SEPARATION BETWEEN THE
USED COOKING OIL LINE, VENT LINES, AND
DOMESTIC WATER LINES. ROUTE HOSE BIBB
BELOW USED COOKING OIL LINE.
3"VTR
3"3"
3 4"
UCO FS-2
#CODED NOTES:
1. EXTEND SANITARY LINE TO MAIN. FIELD VERIFY EXACT LOCATION WITH LOCAL UTILITY
COMPANY PRIOR TO BID.
2. PROVIDE GB-250 KITCHEN GREASE INTERCEPTOR. LOCATE CLEAR OF DRIVE-THRU LANE.
REFER TO CIVIL DRAWINGS FOR FINAL LOCATION. REFER TO "GREASE INTERCEPTOR" DETAIL.
3. VENT RISER FROM UNDER FLOOR PIPING. REFER TO SANITARY ISOMETRIC FOR
CONTINUATION.
4. PROVIDE SANITARY VENT THROUGH ROOF PER "VENT THRU ROOF (VTR)" DETAIL. LOCATE
VENT MINIMUM OF 10'-0" AWAY FROM AIR INTAKES ON ROOF, UNLESS APPROVED BY ENGINEER
PRIOR TO INSTALLATION. VTR SHALL BE EXTENDED HIGHER THAN ANY AIR INTAKES. LOCATE
PER ROOF PLAN.
5. ROUTE CONDENSATE FROM FREEZER/COOLER TO FLOOR DRAIN. PROVIDE RAYCHEM
GUARDIAN GM-51-IM HEAT TRACED LINE FROM INSIDE OF COOLER TO FLOOR DRAIN.
(COORDINATE POWER FOR HEAT TRACE WITH ELECTRICAL PLANS.) REFER TO
"COOLER/FREEZER CONDENSATE" DETAIL.
6. ROUTE USED COOKING OIL LINE BEHIND EQUIPMENT. EXTEND LINE TO USED COOKING OIL
TANK AS SHOWN. REFER TO "USED OIL RECOVERY" DETAIL.
7. ROUTE USED COOKING OIL LINE MINIMUM OF 6" ABOVE CEILING FROM EQUIPMENT TO
RECOVERY TANK AS SHOWN PER PLAN. SLOPE PIPING TO BACK OF BUILDING. REFER TO
INSTALLATION MANUAL FOR EXACT PITCH. LINE CANNOT HAVE ANY TRAPS. USE ONLY BACK
TO BACK 45 DEGREE ELBOW TO CHANGE DIRECTION.
8. PROVIDE THREADED BLACK IRON PIPE DOWN WALL. COVER UCO LINE FROM WALL ENTRY TO
POINT OF CONNECTION AT TANK WITH 1" THICK FIBERGLASS PIPE INSULATION WITH ASJ.
PROVIDE EXTERIOR PIPE INSULATION WITH STAINLESS STEEL PIPE COVER THAT IS BANDED
AND SEALED THROUGHOUT WITH CLEAR UV RESISTANT SILICONE CAULK. PROVIDE WALL
PENETRATOIN WITH STAINLESS STEEL ESCUTCHEON. DO NOT RUN PIPE THROUGH
REFRIGERATED BOXES OR SERVICES SPACES. TURN INTO TANK SHED AT 89" A.F.F. STUB OUT
EXTERIOR SIDE OF WALL.
9. EMERGENCY DRAIN IN RESTROOM SHALL BE INSTALLED FLUSH TO GRADE WITH NO SLOPE.
COORDINATE INSTALLATION HEIGHT WITH GENERAL CONTRACTOR TO ENSURE PROPER
INSTALLATION.
2-WAY
GCO
2-WAY
GCO
VENT PIPING
BELOW GRADE
5'-0"
5'-0"
FD
D
VENT PIPING
BELOW GRADE
FCO
3"
1"
2"
WCO
LAV-2
VENT PIPING
BELOW GRADE
WCO
QP0222
PLUMBING PLAN -
SANITARY WASTE & VENT
P1.1
AUTHOR
CHECKER
79
6
M
e
r
u
s
C
o
u
r
t
St
.
L
o
u
i
s
,
M
O
6
3
0
2
6
T
6
3
6
.
3
4
9
.
1
6
0
0
F
6
3
6
.
3
4
9
.
1
7
3
0
CE
R
T
I
F
I
C
A
T
E
O
F
A
U
T
H
O
R
I
T
Y
N
O
.
3
8
0
0
8/18/2021
SEAL
DESCRIPTIONDATEREV.
ISSUE DATE: 08/17/2021
PROJECT NUMBER: 21-008
DRAWN BY:
CHECKED BY:
SHEET NAME
SHEET NUMBER
MO
O
D
Y
R
D
&
N
2
N
D
E
RE
X
B
U
R
G
,
I
D
8
3
4
4
0
PROJECT TYPE:
SITE NUMBER:
BUILDING TYPE:
OWNER:
BASE VERSION:
DRAWING RELEASE:
PROJECT YEAR:
ASSET TYPE:
CLASSIFICATION:
UPGRADE CLASSIFICATION:
DESIGN TYPE:
#13487
(2.0) SMART 40+
FREESTANDING
NEW
FRANCHISE
2020
NEW BUILD
2021
(2.0) UM BRITE
SUMMER
NEW
SMART 40+
1 10/20/2021 City Comments
1
13
13
2
2
8
66
K1401
QP0909
T0602
A0304
A0801
A0105
T0902T2011
FCW-3
1/2" CW, 1/2" HW, AND (2) 1/2" FW DROP DOWN
IN WALL AND EXTEND THRU MILLWORK TO
E4003, A0608, A0105, A0202, & (2) QP0222.
FIELD VERIFY ROUTING.
FCW-3
FCW-4
FCW-1
FCW-2
FCW-3
FPWH
FPWH
E2302
5
5
T2703
1PLUMBING PLAN - DOMESTIC WATER
1/4" = 1'-0"
WC
LAV-1
LAV-1
WC
4
4
4
MV
MV
MV
MV
RCP
T0303
T0304
WH-1
1"
112"112"
112"
112"112"
112"
12"
12"
12"
3 4"
3 4"
3 4"
1"
1"
1"
12"12"
T2213
4
T1213
ET-1
2
3
1 T2061
3 4"
1"
1"
1"
FW
RO
WB
FW
RO
FW RO
MAINTAIN SEPARATION BETWEEN UCO, SANITARY
LINES, VENT LINES, AND WATER LINES IN THIS
WALL. MAINTAIN SEPARATION BETWEEN THE
USED COOKING OIL LINE, VENT LINES, AND
DOMESTIC WATER LINES. ROUTE HOSE BIBB
BELOW USED COOKING OIL LINE.
BEVERAGE EQUIPMENT NOTES
1. BEVERAGE EQUIPMENT SUPPLIER TO RUN NSF 61 TUBING FOR SODA DISPENSOR(S) AND SELF
SERVE ICE MAKER(S).
2. GC, OR PLUMBING CONTRACTOR, TO MAKE FINAL CONNECTIONS FOR ICE MAKER(S).
2. GC, OR PLUMBING CONTRACTOR, TO PROVIDE OETIKER CLAMPS FOR CONNECTING
BEVERAGE HOSES.
3. BEVERAGE EQUIPMENT SUPPLIER TO INSTALL SODA DISPENSERS AND ANCILLARY
EQUIPMENT INCLUDING RACK, WATER BOOSTER, ETC.
4. BEVERAGE EQUIPMENT SUPPLIER TO INSTALL STAINLESS STEEL CHASE COVERS FOR NSF 61
TUBING.
5. BEVERAGE EQUIPMENT SUPPLIER TO CLEAN, SEAL, AND CAP CHASE.
6. BEVERAGE EQUIPMENT SUPPLIER TO INSTALL STAINLESS STEEL CHASE COVERS FOR NSF 61
TUBING.
#CODED NOTES:
1. CHEMICAL FEED UNITS AND INSTALLATION KITS SUPPLIED BY OWNER'S REPRESENTATIVE AND
INSTALLED BY CONTRACTOR. FEED STATION LOCATIONS ARE TO BE VERIFIED WITH OWNER.
PROVIDE BACKFLOW PROTECTION AS REQUIRED BY LOCAL CODE AND PER BACKFLOW
PREVENTER SCHEDULE. INSTALL PER MANUFACTURER'S RECOMMENDATIONS.
2. PLUMBING CONTRACTOR TO PROVIDE 1/2" INSULATED COPPER LINES IN WALL WITH BALL VALVE
AT CONNECTION LOCATION AND MALE THREAD ADAPTOR ABOVE CEILING FOR CONNECTION BY
BEVERAGE EQUIPMENT INSTALLER TO NSF 61 TUBING LINES.
3. BEVERAGE EQUIPMENT INSTALLER TO PROVIDE 1/2" NSF 61 TUBING FILTERED COLD WATER LINE
FROM WATER FILTER TO CARBONATOR. BEVERAGE EQUIPMENT INSTALLER SHALL PROVIDE
REQUIRED CODE APPROVED STAINLESS STEEL BACKFLOW PREVENTOR PRIOR TO CARBONATOR
EQUIPMENT. NO COPPER WATER LINES SHALL BE USED FOR CARBONATED WATER LINES AFTER
THE BACKFLOW PREVENTOR.
4. PROVIDE INDIVIDUAL MIXING VALVE FOR ALL HAND SINKS AND LAVATORIES IN AN ACCESSIBLE
LOCATION.
5. ROUTE PEX-A FILTERED AND REVERSE OSMOSIS WATER LINES TO SERVE THE COMBI OVEN.
6. ROUTE 1
14" COLD WATER COPPER LINE FROM ABOVE CEILING DOWN TO APPROXIMATELY 30"+/-
AFF FOR THE WATER CLOSET FLUSH VALVE. SEE RISER DIAGRAMS FOR DETAILS AND
ARCHITECTURAL SHEETS FOR MORE INFORMATION. COORDINATE EXACT LOCATION WITH THE
MANUFACTURER'S EQUIPMENT PRIOR TO ROUGH-IN.
7. EXTEND
3 4" COLD WATER LINE TO WATER FILTRATION SYSTEM IN UTILITY AREA. PROVIDE ALL
CHECK VALVES AND SHUT-OFF VALVES REQUIRED. HOOK UP AND COMMISSION WATER
FILTRATION SYSTEMS, BOOSTER PUMP, AND REVERSE OSMOSIS (RO) SYSTEM PER
MANUFACTURER'S RECOMMENDATIONS. VERIFY ALL RESPONSIBILITIES WITH OWNER AND
PLUMBING FIXTURE SCHEDULE. REFER TO "WATER FILTRATION SYSTEM" DETAIL.
8. DROP 1" HW AND CW AND
12" HWR LINES TO WATER HEATER, EXPANSION TANK, AND
RECIRCULATING PUMP. CONTRACTOR TO FURNISH AND INSTALL WATER HEATER. REFER TO
"LARGE WATER HEATER", "RECIRCULATION PUMP", AND "SMALL EXPANSION TANK" DETAILS.
DISCHARGE T&P RELIEF VALVE AND OVERFLOW TO DRAIN. PROVIDE VALVE AND UNION ON INLET
AND OUTLET. PROVIDE BALANCING VALVES AS REQUIRED FOR RECIRCULATING SYSTEM.
9. BEVERAGE EQUIPMENT SUPPLIER TO RUN 1/2" COLD WATER NSF 61 TUBING LINE ABOVE CEILING
TO DINING ROOM FOR CONNECTION TO BEVERAGE SYSTEM. PROVIDE SHUT OFF VALVES AND
BACK-FLOW PREVENTERS AS REQUIRED TO MAKE FINAL CONNECTION. COORDINATE WITH
OWNER'S REPRESENTATIVE. BEVERAGE BUNDLE WHICH INCLUDES SYRUP AND FILTERED
WATER LINES TO RUN OVERHEAD ABOVE CEILING, EXTEND FROM FILTER SYSTEM AND THRU 6"
ESCUTCHEON PLATE IN CEILING, EXTEND OVERHEAD TO DRINK UNITS THEN DOWN THRU CEILING
AND THROUGH CHASE BEHIND BEVERAGE UNIT. VERIFY RESPONSIBILITIES WITH OWNER AND
FIXTURE SCHEDULE.
10. EXTEND 3/4" HOT AND COLD WATER COPPER LINES DOWN FOR THE MOP SINK/FAUCET FROM
MAIN. MAKE ALL FINAL CONNECTIONS. COORDINATE EXACT LOCATION PRIOR TO ROUGH-IN. MOP
SINK AREA HAS 2 FAUCETS MOUNTED DIRECTLY ABOVE EACH OTHER. REFER TO CONNECTION
SCHEDULE FO0R MOUNTING HEIGHTS. MOP SINK AND HUB DRAIN PROVIDED BY KITCHEN
EQUIPMENT SUPPLIER, SEE ARCHITECTURAL DETAILS. COORDINATE WITH ARCHITECTURAL AND
KITCHEN VENDOR DRAWINGS FOR INSTALLATION INSTRUCTIONS.
11. BEVERAGE EQUIPMENT INSTALLER SHALL PROVIDE NSF 61 TUBING LINES, FOR COLD WATER
SERVING BEVERAGE EQUIPMENT. LINES ARE SHOWN ARE SHOWN FOR REFERENCE ONLY.
COORDINATE WITH OWNER'S REPRESENTATIVE.
12. ROUTE 3/4" HW TO SMALL WATER HEATER SERVING WAREWASH MACHINE. REFER TO "SMALL
WATER HEATER ON PLATFORM" AND "WAREWASH W/ WATER HEATER" DETAILS.
13. EXTEND COPPER PIPING DOWN IN WALL TO FREEZE-PROOF WALL HYDRANT-WOODFORD MODEL
65 OR EQUAL, MOUNT 18" ABOVE FINISHED GRADE. VERIFY EXACT LOCATION WITH
ARCHITECTURAL ELEVATIONS.
14. 1
12" WATER METER AT FLOOR WITH RPZ BACKFLOW PREVENTER, PIPE DISCHARGE TO FLOOR
DRAIN. EXTEND LINE TO MAIN. FIELD VERIFY EXACT LOCATION WITH WATER COMPANY.
15. PROVIDE WATER BOX FOR FILTERED AND REVERSE OSMOSIS WATER LINES SERVING THE COMBI
OVEN PER THE "COMBI OVEN WATER ROUGH-IN" DETAIL.
EX
T
.
R
A
M
P
LCA672LCE6120
V2201
15
15
4 T2703
MV
MV ABOVE
CEILING
LAV-2 4
9
9A0202
QP0222
FCW-3
FCW-1
1"
1"
1"
14
7
11
T2212
T1212
12
9QP0222 FCW-1
WH-2
12
10
PLUMBING PLAN -
DOMESTIC WATER
P1.2
AUTHOR
CHECKER
79
6
M
e
r
u
s
C
o
u
r
t
St
.
L
o
u
i
s
,
M
O
6
3
0
2
6
T
6
3
6
.
3
4
9
.
1
6
0
0
F
6
3
6
.
3
4
9
.
1
7
3
0
CE
R
T
I
F
I
C
A
T
E
O
F
A
U
T
H
O
R
I
T
Y
N
O
.
3
8
0
0
8/18/2021
SEAL
DESCRIPTIONDATEREV.
ISSUE DATE: 08/17/2021
PROJECT NUMBER: 21-008
DRAWN BY:
CHECKED BY:
SHEET NAME
SHEET NUMBER
MO
O
D
Y
R
D
&
N
2
N
D
E
RE
X
B
U
R
G
,
I
D
8
3
4
4
0
PROJECT TYPE:
SITE NUMBER:
BUILDING TYPE:
OWNER:
BASE VERSION:
DRAWING RELEASE:
PROJECT YEAR:
ASSET TYPE:
CLASSIFICATION:
UPGRADE CLASSIFICATION:
DESIGN TYPE:
#13487
(2.0) SMART 40+
FREESTANDING
NEW
FRANCHISE
2020
NEW BUILD
2021
(2.0) UM BRITE
SUMMER
NEW
SMART 40+
1 10/20/2021 City Comments
EX
T
.
R
A
M
P
LCA672LCE6120
V2201
SHARED\xUS2.0-P1-3 Base.dwg
1PLUMBING PLAN - NATURAL GAS
1/4" = 1'-0"
1
2WH-1
1
3
3
RTU-2
RTU-1
G G
G
G
2"
114"
1 14"
114"
112"
112"
2WH-1
#CODED NOTES:
1. GAS SERVICE AND METER SETTING SIZED PER GAS COMPANY REQUIREMENTS FOR MAX
CONNECTED LOADS AS SHOWN IN "NATURAL GAS CALCULATIONS" TABLE WITH TOTAL
DEVELOPED LENGTH, INCLUDING FITTINGS, VALVES, ETC. OF 100 LINEAR FEET AND A TOTAL
SYSTEM PRESSURE DROP OF 0.3" W.C. WITH 14" W.C. DELIVERED AT THE METER. HOLD GAS
METER AND NATURAL GAS LINES TIGHT TO BUILDING. REFER TO "GAS SERVICE" DETAIL.
2. ROUTE NATURAL GAS LINE DOWN TO WATER HEATER AS SHOWN PER PLAN. COORDINATE
EXACT LOCATION WITH MECHANICAL CONTRACTOR PRIOR TO INSTALLATION. REFER TO
"LARGE WATER HEATER" DETAIL.
3. ROUTE NATURAL GAS UP THROUGH ROOF TO TO ROOFTOP EQUIPMENT AS SHOWN PER PLAN.
COORDINATE EXACT LOCATION WITH MECHANICAL CONTRACTOR PRIOR TO INSTALLATION.
REFER TO "ROOFTOP UNIT GAS CONNECTION" DETAIL. GAS LINES ON ROOF ARE TO BE
PAINTED SAFETY YELLOW. GAS LINES MUST BE ROUTED TO ALLOW FULL ACCESS TO RTU
EQUIPMENT.
GAS LINE BEHIND EQUIPMENT
4GAS LINE AUTO
SHUT-OFF VALVE
112"112"G
5
J1004
NATURAL GAS CALCULATIONS
EQUIPMENT MBH
ROOFTOP EQUIPMENT:
RTU-1 270
RTU-2 270
WATER HEATING
WH-1 199
KITCHEN EQUIPMENT
OPEN FRYER 4 WELL 300
TOTAL GAS LOAD (MBH)1039.0
PLUMBING PLAN -
NATURAL GAS
P1.3
AUTHOR
CHECKER
79
6
M
e
r
u
s
C
o
u
r
t
St
.
L
o
u
i
s
,
M
O
6
3
0
2
6
T
6
3
6
.
3
4
9
.
1
6
0
0
F
6
3
6
.
3
4
9
.
1
7
3
0
CE
R
T
I
F
I
C
A
T
E
O
F
A
U
T
H
O
R
I
T
Y
N
O
.
3
8
0
0
8/18/2021
SEAL
DESCRIPTIONDATEREV.
ISSUE DATE: 08/17/2021
PROJECT NUMBER: 21-008
DRAWN BY:
CHECKED BY:
SHEET NAME
SHEET NUMBER
MO
O
D
Y
R
D
&
N
2
N
D
E
RE
X
B
U
R
G
,
I
D
8
3
4
4
0
PROJECT TYPE:
SITE NUMBER:
BUILDING TYPE:
OWNER:
BASE VERSION:
DRAWING RELEASE:
PROJECT YEAR:
ASSET TYPE:
CLASSIFICATION:
UPGRADE CLASSIFICATION:
DESIGN TYPE:
#13487
(2.0) SMART 40+
FREESTANDING
NEW
FRANCHISE
2020
NEW BUILD
2021
(2.0) UM BRITE
SUMMER
NEW
SMART 40+
1 10/20/2021 City Comments
1PLUMBING RISER - SANITARY WASTE & VENT
NTS
2PLUMBING RISER - DOMESTIC WATER
NTS
T0902
T2011
T2061
FCW-2
E2302
T2703
T2703
T2703
T2703
E2302
4"
3"
3"
FD
4"4"
4"
4"
4"
4"
4"
4"
3"
3"
3"
4"
4"
4"
4"
4"
3"
3"
3"
3"3"
3"
ECO
FCO
FCO
FCO
FCO
ECO
FS-2
FS-1
FS-1
FS-1
FD
FD
FD
FD
FD
FD
FCO
4"
3"
3"
3"
2"
2"
2"
2"
2"
2"
2"
2"
FD
WCO
WCO
WC
WC
LAV-1
LAV-1
4"
4"
4"
4"
4"4"
3"
2"
2"
2"2"
2"
2"
2"
2"
2"
2"
2"
112"
112"
112"
112"
112"
112"
112"
112"
112"
112"
112"
112"
3"
3"
M
REFER TO WATER
FILTRATION SYSTEM
DETAIL
114"
3 4"
3 4"
T1212
T0304
3 4" HW&CW
LAV-1
WC FPWH
WC
114"
FPWH
3 4"
3 4"
3 4"3 4"
12"12"
12"12"
12"
12"
12"
12"
12"
12"
3 4"
3 4"
12"
112"
FCW-3
FCW-4
K1401
MV
LAV-1
MV
MV
MV
3 4"
MV
ET-1
WH-1
QP0909 A0304
A0801
FCW-1
FCW-2
FCW-3
12"
12"
12"
12"12"
12"
3 4"
1"
12"
3 4" CW1"
1"
1"
1"
112"
112"
112"
112"
112"
112"
112"
3 4" HW
1"
1"
1"
T2213
GW
GW GW
GW
GW
GW
RCP
FD
FCO
4"
GW
GW 3"
T06024"
3"
3"
A0105
T1213
1"
WB
3 4"
12"
12"
12"
12"
12"
FW
RO
FW
RO
GI
3"
HD
A0202
QP0222
4"
4"
WCO
3"
FD
3"
FD
3"VTR
2"
2"
3"
112"2"
3"VTR
3"
3"
3"
3"3"
112"
2- WAY
FCO
2- WAY
FCO
112"
112"
3"
FS-1
112"
LAV-2
MV
112"
2"
LAV-2
WH-2
A0608
FCW-2
FCW-3
A0202
QP0222
FCW-3
FCW-1
12"
12"A0105
12"
PLUMBING RISERS
P2.0
AUTHOR
CHECKER
79
6
M
e
r
u
s
C
o
u
r
t
St
.
L
o
u
i
s
,
M
O
6
3
0
2
6
T
6
3
6
.
3
4
9
.
1
6
0
0
F
6
3
6
.
3
4
9
.
1
7
3
0
CE
R
T
I
F
I
C
A
T
E
O
F
A
U
T
H
O
R
I
T
Y
N
O
.
3
8
0
0
8/18/2021
SEAL
DESCRIPTIONDATEREV.
ISSUE DATE: 08/17/2021
PROJECT NUMBER: 21-008
DRAWN BY:
CHECKED BY:
SHEET NAME
SHEET NUMBER
MO
O
D
Y
R
D
&
N
2
N
D
E
RE
X
B
U
R
G
,
I
D
8
3
4
4
0
PROJECT TYPE:
SITE NUMBER:
BUILDING TYPE:
OWNER:
BASE VERSION:
DRAWING RELEASE:
PROJECT YEAR:
ASSET TYPE:
CLASSIFICATION:
UPGRADE CLASSIFICATION:
DESIGN TYPE:
#13487
(2.0) SMART 40+
FREESTANDING
NEW
FRANCHISE
2020
NEW BUILD
2021
(2.0) UM BRITE
SUMMER
NEW
SMART 40+
1 10/20/2021 City Comments
3'-9 1/2"
6'-10 3/4"
1'-6"
6'-0 1/2"
13'-3 1/2"
11
'
-
2
1
/
2
"
20
'
-
7
1
/
4
"
10
'
-
7
1
/
2
"
2'
-
7
"
13
'
-
1
1
"
12
'
-
1
0
"
17
'
-
1
0
3
/
4
"
11
'
-
5
1
/
2
"
9'
-
9
1
/
2
"
8'
-
4
3
/
4
"
9'
-
9
1
/
4
"
6'
-
4
1
/
4
"
6'
-
8
"
21'-1 1/4"
5'-11 3/4"
9'-9 1/4"
2'-2"
13'-4 1/4"
1'
-
0
1
/
2
"
8'
-
3
1
/
4
"
3'
-
5
3
/
4
"
11
'
-
5
3
/
4
"
16'-1 1/2"
3'
-
6
1
/
2
"
3'
-
5
3
/
4
"
5
1
/
2
"
12
'
-
1
0
1
/
4
"
23'-2"
24'-8 1/2"
30'-1 1/2"
31'-0 1/4"
30'-1 1/2"
30'-11 3/4"
13'-8 3/4"
11'-8 3/4"
25'-9 1/2"
1'
-
5
1
/
2
"
8'
-
2
1
/
4
"
9'
-
9
1
/
4
"
1'
-
1
0
3
/
4
"
6'
-
8
1
/
2
"
7'-2 3/4"
1PLUMBING PLAN - DIMENSION CALLOUT
1/4" = 1'-0"
DIMENSIONS ARE FOR REFERENCE ONLY.
GENERAL CONTRACTOR TO VERIFY LAYOUT
WITH WENDY'S REPRESENTATIVE.
28'-5"
0"
0"0"
0"
5'
-
4
1
/
2
"
REFERENCE POINT
OUTSIDE FACE OF
SHEATHING
15
'
-
6
1
/
2
"
1'-6 3/4"
2'-9 1/2"
EX
T
.
R
A
M
P
LCA672LCE6120
V2201
15
'
-
5
"
15'-2 3/4"
8'-10 1/4"
PLUMBING DIMENSION
PLAN
P3.0
AUTHOR
CHECKER
79
6
M
e
r
u
s
C
o
u
r
t
St
.
L
o
u
i
s
,
M
O
6
3
0
2
6
T
6
3
6
.
3
4
9
.
1
6
0
0
F
6
3
6
.
3
4
9
.
1
7
3
0
CE
R
T
I
F
I
C
A
T
E
O
F
A
U
T
H
O
R
I
T
Y
N
O
.
3
8
0
0
8/18/2021
SEAL
DESCRIPTIONDATEREV.
ISSUE DATE: 08/17/2021
PROJECT NUMBER: 21-008
DRAWN BY:
CHECKED BY:
SHEET NAME
SHEET NUMBER
MO
O
D
Y
R
D
&
N
2
N
D
E
RE
X
B
U
R
G
,
I
D
8
3
4
4
0
PROJECT TYPE:
SITE NUMBER:
BUILDING TYPE:
OWNER:
BASE VERSION:
DRAWING RELEASE:
PROJECT YEAR:
ASSET TYPE:
CLASSIFICATION:
UPGRADE CLASSIFICATION:
DESIGN TYPE:
#13487
(2.0) SMART 40+
FREESTANDING
NEW
FRANCHISE
2020
NEW BUILD
2021
(2.0) UM BRITE
SUMMER
NEW
SMART 40+
1 10/20/2021 City Comments
BLOCKING BY GENERAL
CONTRACTOR
WOOD BLOCKING
CONTINUOUS
INSULATION
THROUGH PIPE
SUPPORT
WATER LINE INSULATION/PIPE SUPPORT
NOT TO SCALE
PIPE SUPPORT (IN-WALL)15
CW
G
VENT/INTAKE PIPE PROVIDED BY PLUMBING CONTRACTOR. PROVIDE 3" INTAKE PIPE AND 3" EXHAUST
PIPE FROM WATER HEATER TO CONCENTRIC VENT INTAKE AIR WALL TERMINATION KIT. MAKE ALL FINAL
INTAKE/ EXHAUST CONNECTIONS. COORDINATE LOCATION OF WALL OPENING WITH ARCHITECT PRIOR
TO ROUGH-IN. MAINTAIN 10' CLEARANCE FROM ALL OUTSIDE AIR INTAKES. INSTALL PER
MANUFACTURER'S RECOMMENDATION.
CHECK VALVE 1"
A.S.M.E. APPROVED
TEMPERATURE AND
PRESSURE RELIEF VALVE
SIZE GAS PER PLAN
EXTEND FULL SIZE TO
DRAIN
DRAIN VALVE
3/4"
1"
1"140° HW
THERMOMETER WITH
GAGE COCK (TYP.) -
EQUAL TO WATTS
#TB-1-1/2-1
SEE FLOOR PLAN FOR
CONTINUATION
VACUUM RELIEF VALVE
1"
1"
TO EXPANSION
TANK
3/4"TO RECIRC
PUMP
NOT TO SCALE
LARGE WATER HEATER 12
INSTALL PIPE HIGH AS POSSIBLE, ANCHORED TO WALL OF BOX WITH SUPPORTS AT MAXIMUM SIX FOOT
CENTERS. USE TYPE "M" HARD COPPER TUBE AND FITTINGS WITH LEAD-FREE SOLDER JOINTS. SLOPE
HORIZONTAL PIPE AT MINIMUM TWO PERCENT. REFER TO LOCAL CODE FOR INDIRECT DRAIN
REQUIREMENTS. ELECTRICAL AND PLUMBING CONTRACTORS TO COORDINATE WORK. ELECTRICAL
CONTRACTOR TO PROVIDE AND INSTALL HEAT TRACING.
FLOOR
1"DX COIL
CO
CO
NO INSULATION ON PIPE RISER
SEE FLOOR PLAN FOR RECEPTACLE LOCATION.
WALK-IN COOLER OR FREEZER BOX
PROVIDE TRAP AT
BOTTOM OF RISER AND
DISCHARGE INTO FLOOR
DRAIN OR FLOOR SINK
WITH AIR GAP OF TWO
PIPE DIAMETERS
SILICONE SEAL AROUND
PIPE PENETRATION
PROVIDE 1" ELASTOMERIC INSULATION OVER
FREEZE PROTECTION ON CONDENSATE LINE -
IF/WHEN FREEZER BOX ONLY - (PROVIDE
ELECTRIC HEAT TRACE CABLE PER PLAN.
COORDINATE POWER REQUIREMENTS)
PROVIDE CLEANOUT
IN TURNS AND ENDS
OF PIPE
MAKE CONNECTION TO
COIL AS REQUIRED
NOT TO SCALE
COOLER/FREEZER CONDENSATE 8
PROVIDE FIBERGLASS INSULATION WITH ALL-SERVICE JACKET WITH VAPOR BARRIER ON ALL COLD/HOT
WATER PIPING AND CONDENSATE DRAIN PIPE. REFER TO SPECIFICATIONS FOR FURTHER
INFORMATION REGARDING INSULATION. INSTALL ALL ITEMS PER SPECIFICATIONS AND
MANUFACTURERS INSTRUCTIONS. MAINTAIN VAPOR BARRIER ON COLD PIPING BY MEANS OF SEALANT
AND TAPE. FLAME-SPREAD AND SMOKE-DEVELOPED INDEXES SHALL NOT EXCEED 25/50. SEAL
EXPOSED ENDS OF FIBERGLASS INSULATION WITH ADHESIVE MASTIC.
REFER TO OTHER DETAILS
FOR TREATMENT OF
INSULATION AT PENETRATION
OF WALLS AND FIREWALLS
PROVIDE INSULATION ON DOMESTIC
HOT/COLD WATER PIPES, STORM WATER
PIPES, AND CONDENSATE DRAIN PIPING
IN WALLS AND CHASES
MITER THE INSULATION AT TEES AND
ELBOWS SO THAT THERE ARE NO GAPS
AT JOINTS. PROVIDE ONE-PIECE
PRE-MOULDED PVC FITTING COVERS
PROVIDE A ONE FOOT LENGTH OF
NON-COMPRESSIBLE INSULATION AT
HANGERS FOR ALL PIPE 2" AND
LARGER
COVER VALVE BODIES WITH INSULATION, BUT NOT UNIONS
TAPE JOINTS OF
FIBERGLASS
INSULATION
FLOOR
NOT TO SCALE
PIPE INSULATION 4
AI
R
G
A
P
2"
M
I
N
.
FINISHED
FLOOR
PVC PIPE (SIZE
WILL VARY)
3" SANITARY LINE (SEE
PLUMBING PLAN)
FLOOR SINK (BY PLUMBING
CONTRACTOR)
NOT TO SCALE
INDIRECT DRAIN 19
PROVIDE ONE PIECE SPUN ALUMINUM BASE
WITH, GRADUATED STEPPED PVC BOOT,
AND ADJUSTABLE STAINLESS STEEL
CLAMPS. SET BASE IN BED OF MASTIC
MINIMUM 12" BELOW ROOF
ROOF INSULATION
ROOF DECK
REFER TO ARCHITECT'S DRAWING
FOR APPLICATION OF VENT PIPE
BOOT INSTALLATION WITH
ROOFING MATERIAL
PROVIDE SLEEVE IF
REQUIRED BY TYPE
OF ROOF DECK
PROVIDE PIPE INCREASER
WHERE REQUIRED TO MAKE
MINIMUM 3" VENT THRU ROOF
ANCHOR PIPE TO ROOF DECK OR JOISTS
WITH U-BOLT AROUND PIPE AND ANGLE
IRON WELDED OR SCREWED TO DECK OR
JOIST
HUBLESS PIPE CONNECTORS ON CAST
IRON PIPE
REFER TO PLANS FOR VTR PIPE SIZES AND LOCATIONS. LOCATE VTR A MINIMUM OF 10 FEET
HORIZONTAL (UNLESS APPROVED BY ENGINEER PRIOR TO INSTALLATION) OR THREE FEET VERTICAL
ABOVE ANY BUILDING OPENING OR FRESH AIR INTAKE, AND ONE FOOT FROM ANY VERTICAL SURFACE.
PROVIDE 1" FIBERGLASS INSULATION WITH ALL-SERVICE JACKET ON VENT PIPE INSIDE BUILDING
WITHIN SIX FEET OF VENT THRU ROOF LOCATION. VERIFY FLASHING AND COUNTERFLASHING WITH
ROOFING CONTRACTOR.
TERMINATE VENT FLUSH WITH
TOP OF PARAPET WALL.
NOT TO SCALE
VENT THRU ROOF (VTR)18
BALL VALVE:
BRONZE BODY,
FULL PORT,
SCREWED ENDS
(TYP)
FULL SIZED REDUCED
PRESSURE TYPE BACKFLOW
PREVENTION DEVICE
STRAINER: BRONZE BODY, STAINLESS SCREEN.
24
"
M
I
N
.
3" MIN.
6" MIN.
PRV SET AT
75PSI
SLEEVE AND CAULK
CITY WATER
METER
DETAIL SHOWS GENERAL SCHEMATIC REQUIREMENTS. PROVIDE BACKFLOW PREVENTER OF TYPE AND
MANUFACTURER APPROVED BY LOCAL AUTHORITIES. PROVIDE PRESSURE REDUCING VALVE ONLY IF
PRESSURE EXCEEDS 80 PSI - VERIFY. STRAINER AND REDUCING VALVE MAY BE INSTALLED IN VERTICAL
PIPE IF SPACE LIMITATIONS REQUIRE IT. CLEAN STRAINER BEFORE TURNING BUILDING OVER TO
OWNER. PROVIDE ANY REQUIRED CERTIFICATION OF TEST OF BACKFLOW PREVENTER TO LOCAL
AUTHORITIES.
FLOOR
TO FIXTURES
NOT TO SCALE
DOMESTIC WATER SERVICE ENTRY 14
MOP SINK
PC TO PROVIDE WATER HAMMER ARRESTERS BY SIOUX CHIEF, PRECISION PLUMBING PRODUCTS,
WATTS OR APPROVED EQUIVALENT WITH PISTON AND 0-RING CONSTRUCTION, HAVING PDI #WH-201,
ASSE #1010 OR ANSI #A112.26.1M CERTIFICATION. SIZE AND INSTALL PER PDI #WH-201 STANDARD OR
MANUFACTURER'S INSTRUCTION. THE TABLES ABOVE ARE BASED ON THE SIOUX CHIEF PRODUCT LINE.
IF PRESSURE IS IN EXCESS OF 65 PSIG THEN UPSIZE THE ARRESTER BY ONE (EXAMPLE: AN 'A'
ARRESTER WOULD BECOME A 'B' ARRESTER.)
UNIT LOAD
FIXTUREPDI
SIZE
SINGLE FIXTURE
KITCHEN SINKS
2.252.25
MULTIPLE FIXTURES
FIXTURE UNIT TABULATION
FIXTURE
3
HOT
-
3
COLD
10AA
A
B
C
D
1-3
4-11
12-32
33-60
61-113
ON HORIZONTAL BRANCH LINE LESS
THAN 20 FEET LONG, PLACE ONE WITHIN
SIX FEET OF THE LAST FIXTURE SERVED
ON BRANCH LINE GREATER THAN 20
FEET LONG, PLACE ANOTHER ARRESTER
IN THE MIDDLE, EACH IS SIZED FOR HALF
THE FIXTURE UNITS
LAVATORY
WATER CLOSET (VALVE)
HW OR
CW
ARRESTER
WITHIN SIX
FEET OF
FIXTURE
SERVED
HAND SINKS 1.51.5
WALL HYDRANT/HOSE BIB 22
1.51.5
NOT TO SCALE
WATER HAMMER ARRESTORS 6
ENTER BUILDING ABOVE GRADE WITH
SLEEVE. SEAL ENTRANCE INTO BUILDING
WEATHER-TIGHT
SIZE AS SHOWN ON PLAN - USE BLACK
STEEL PIPE
GAS METER - CFH
CAPACITY PER PLAN
SHUT-OFF
VALVE
GRADE OR
PAVEMENT
PRESSURE
REGULATOR (7"
W.C.)
EXTERIOR BUILDING WALL
BY GAS COMPANY (VERIFY)
FLOOR
BY PLUMBING CONTRACTOR
STRAINER
PRESSURE TEST COCK
PIPE INCREASER
VERIFY REQUIREMENTS FOR METERING AND PIPING WITH GAS COMPANY. GAS COMPANY SHALL
EXCAVATE, BACKFILL, AND REPAIR PAVING AND SOD FOR GAS SERVICE LINE INSTALLATION FROM MAIN
TO BUILDING. PLUMBING CONTRACTOR TO PAY ALL GAS COMPANY FEES FOR THIS INSTALLATION. USE
WELDED OR SCREWED PIPE AND FITTINGS PER SPECIFICATIONS. PAINT EXPOSED METAL GAS PIPE,
FITTINGS AND ITEMS TO MATCH BUILDING.
6" DEEP SEDIMENT TRAP
NOT TO SCALE
GAS SERVICE 2
SANITARY LINE (SEE
PLUMBING PLAN)
FINISH FLOOR
VENT LINE (SEE
PLUMBING PLAN)
3" CAPPED PVC PIPE
STUBBED 1'-0" AFF
NOT TO SCALE
HUB DRAIN 9
PIPING ARRANGEMENT SHOWN IS SCHEMATIC. ADJUST TO SUIT FIELD CONDITIONS. MAKE PIPE SAME
SIZE AS TANK FITTING. FOLLOW MANUFACTURER'S INSTRUCTIONS FOR INSTALLATION PROCEDURE.
VERIFY PROPER OPERATION WHEN INSTALLED.
EXPANSION TANK INSTALLATION SHALL OCCUR ONLY WHEN THERE IS A BACKFLOW PREVENTION
DEVICE INSTALLED WITHIN THE BUILDING WATER SYSTEM.
WELDED STEEL
THEN OPEN VALVE
WATER PRESSURE,
PRESSURE TO MATCH
FILL TANK WITH AIR
AIR CHARGING VALVE
BUTYL DIAPHRAGM
POLYPROPYLENE LINING
EXPANSION TANK WITH
DISSIMILAR METALS
DIELECTRIC IF
TO WATER HEATER
COLD WATER SUPPLY
PIPE UNION:
NEXT TO PIPE TEE
PIPE HANGER
NOT TO SCALE
SMALL EXPANSION TANK 3
TO EXPANSION TANK IF
REQUIRED, SEE DETAIL
STRAP-ON AQUASTAT SET 5
DEGREES LOWER THAN
HEATER TEMPERATURE
H.W.
C.W.
STRAINER
RECIRCULATION PUMP
CHECK VALVE
WATER HEATER
PIPING ARRANGEMENT SHOWN IS SCHEMATIC. ADJUST TO SUIT FIELD CONDITIONS. REFER TO "LARGE
WATER HEATER" DETAIL FOR MORE INFORMATION.
19RECIRCULATION PUMP
NOT TO SCALE
GB-250 - 100 GPM - 277 GALLON CAPACITY:
DETAIL SHOWS GENERAL SCHEMATIC REQUIREMENTS. CONTRACTOR SHALL SUBMIT PROPOSED
GREASE INTERCEPTOR INSTALLATION PLANS AND SPECIFICATIONS TO LOCAL AUTHORITIES FOR THEIR
APPROVAL BEFORE ACQUISITION. SEE MANUFACTURER INSTALLATION MANUAL FOR ADDITIONAL
INSTRUCTIONS.
BED OF UNDISTURBED EARTH OR COMPACTED SAND BACKFILL: 4" - 6"
24" DIAMETER HEAVY DUTY MANHOLES
4"4"
INLET DIFFUSER
OUTLET DIFFUSER
WATER LINE
NOT TO SCALE
GREASE INTERCEPTOR 15
PIPE OVER FOUR INCH
CLEVIS HANGER FOR
PROVIDE UPPER ATTACHMENT AS REQUIRED FOR CASES NOT SHOWN HERE. DO NOT INSTALL HANGER
INSIDE INSULATION OR OTHERWISE PENETRATE VAPOR BARRIER. DO NOT HANG ONE PIPE FROM
ANOTHER EXCEPT IN CHASES. TRAPEZE HANGERS MAY BE USED FOR MULTIPLE PARALLEL PIPES.
HANGER SPACING FOR PIPE SIZE: COPPER: 4"=12'-0"; 3"=11'-0"; 212"=10'-0"; 2"=9'-0"; 112"=8'-0"; 114"=7'-0"; 1" &
3 4"=6'-0"; 12"=5'-0". CAST IRON: 10'-0" AND ONE NEAR ALL JOINTS. STEEL: 4"=14'-0"; 3"=12'-0"; 212"=11'-0";
2"=10'-0"; 112"=9'-0"; 1"=7'-0"; 3 4"=6'-0"; 12"=5'-0". LOCATE HANGERS AS CLOSE AS POSSIBLE TO TURNS AND
TEES OF PIPE. PROVIDE SUPPLEMENTARY STEEL STRUTS BETWEEN JOISTS IF REQUIRED. LOCATE
HANGERS TO TAKE LOAD OFF OF EQUIPMENT CONNECTIONS. ANCHOR WATER PIPE AGAINST SWAYING
DUE TO CHANGES IN WATER VELOCITY. PROVIDE SEISMIC BRACING IF/AS REQUIRED BY LOCAL
AUTHORITIES. CHAINS OR PERFORATED STRAP IRON OR STEEL IS NOT ACCEPTABLE. REFER TO
CODES FOR FURTHER INFORMATION.
PROVIDE GALVANIZED STEEL SADDLE FOR ALL INSULATED PIPE
LARGER THAN 3 4". VERIFY INSULATION THICKNESS WHEN SIZING
HANGERS.
ADJUSTABLE
BAND HANGER
FOR PIPING
FOUR INCH OR
LESS
TOP BEAM
C-CLAMP IF
STEEL BAR
JOIST
STEEL
DECK
ALL-THREAD ROD.
LENGTH AS REQ'D
FOR PIPE SLOPE
PROVIDE COPPER
OR NON-METALLIC
COATING WHERE
HANGERS CONTACT
BARE COPPER PIPE
DO NOT HANG PIPE
LARGER THAN 3" FROM
BOTTOM OF JOISTS.
NOT TO SCALE
PIPE HANGERS 5
BA
C
K
R
O
O
M
I
C
E
M
A
K
E
R
FI
L
T
E
R
BACKFLOW
PREVENTER
FC
W
-
2
FC
W
-
2
CO
F
F
E
E
TE
A
FI
L
T
E
R
FI
L
T
E
R
BOOSTER
PUMP
PRV
SCALE
STICK
3/4" CW
PR
E
S
S
U
R
E
G
A
U
G
E
P
S
B
FILTER LINES TO EQUIPMENT (BY OTHERS)
FILTER MANIFOLD MOUNTED ON WALL
NSF 61
TUBING
WATER LINE
PLAN OVERVIEW LAYOUT SEE DIAGRAM FOR COMPLETE DETAILS
MANIFOLDS ON DRINK RACK
3/4" COLD WATER LINE
F FF
AUTOMATIC
BY-PASS
MODULE
1/2" FCW-3
1/2" FCW-4
COMBI OVEN
(CLEANING CYCLE)
COMBI OVEN
(STEAM CYCLE)
RO SYSTEM
(MOUNTED AT MOP SINK)
1/
2
"
CW
FC
W
-
1
FC
W
-
1
FC
W
-
1
FC
W
-
1
FR
O
N
T
R
O
O
M
I
C
E
M
A
K
E
R
(D
I
N
I
N
G
R
O
O
M
B
E
V
E
R
A
G
E
U
N
I
T
)
FC
W
-
3
FC
W
-
3
FC
W
-
3
FC
W
-
3
1/
2
"
F
C
W
1/2"
1/2"
ICE MACHINE MANIFOLD
BEVERAGE LINE MANIFOLD
EQUIPMENT
MANIFOLD
NSF 61
TUBING
NSF 61
TUBING
BE
V
E
R
A
G
E
L
I
N
E
(D
R
I
V
E
-
T
H
R
U
)
BE
V
E
R
A
G
E
L
I
N
E
(D
I
N
I
N
G
R
O
O
M
)
CA
R
B
O
N
A
T
O
R
(U
T
I
L
I
T
Y
A
R
E
A
)
FILTER LINES
TO EQUIPMENT
(BY OTHERS)
FILTER LINES TO
EQUIPMENT (BY
OTHERS)
SP
A
R
E
24
"
A
F
F
.
OI
L
FRYERS
CAP
24"
UNION
WALL PENETRATION
3/4" USED OIL RECOVERY LINE MOUNTED TO WALL WITH
STANDOFF ANCHORS, ALL THREAD, AND SPLIT RING HANGERS.
COORDINATE WITH ARCHITECTURAL AND VENDOR DRAWINGS
FOR INSTALLATION. USED COOKING OIL LINE CANNOT
PROTRUDE MORE THAN 3" FROM THE WALL.
PITCH DOWN 1/4"
PER FOOT TO
USED COOKING
OIL TANK
3"
MAX.OIL
PROVIDE STAINLESS
STEEL ESCUTCHEON
AT WALL
7USED OIL RECOVERY LINE
NOT TO SCALE
NOT TO SCALE
WATER FILTRATION SYSTEM 1
HOT WATER TO WAREWASH AS
SHOWN ON PLANS
REFER TO SPECIFICATIONS AND
SCHEDULE
SET WATER HEATER ON PLATFORM
(BY OTHERS).
PIPING ARRANGEMENT SHOWN IS SCHEMATIC. ADJUST TO SUIT FIELD CONDITIONS. REFER TO FLOOR
PLAN FOR PIPE SIZES. SET WATER HEATER THERMOSTAT AT 140° FAHRENHEIT. PROVIDE SEISMIC
STRAP OR BRACING AND FLEXIBLE CONNECTORS TO WATER AND GAS CONNECTIONS IF/AS REQUIRED
BY LOCAL AUTHORITIES.
SHUT-OFF VALVE PIPE UNIONS,
(DIELECTRIC REQUIRED FOR
DISSIMILAR METALS)
VALVE
DRAIN
PROVIDE A 210° F TEMPERATURE
AND 150 PSI PRESSURE RELIEF
VALVE WITH TEST LEVER SIZED WITH
AGA TEMPERATURE RATING 10%
OVER HEATING INPUT
HARD COPPER RELIEF DISCHARGE
LINE. FULL SIZE OF VALVE OUTLET TO
END OVER FLOOR SINK WITH 6 INCH
AIR GAP
140° FC HOT WATER SUPPLY TO
WATER HEATER
NOT TO SCALE
SMALL WATER HEATER ON PLATFORM 10
GAS
36
"
A
F
F
.
GA
S
1"
FRYERS
1-1/2"
1" NPT TO FRYER
1-1/2" GAS LINE. EXTEND THROUGH WALL TO AUTOMATIC
GAS SHUTOFF VALVE BELOW FINISHED CEILING
WALL
PENETRATIONS
3"
MAX.
QUICK DISCONNECT (TYP.)
1-1/2" GAS LINE MOUNTED TO WALL WITH STANDOFF ANCHORS,
ALL THREAD, AND SPLIT RING HANGERS. COORDINATE WITH
ARCHITECTURAL AND VENDOR DRAWINGS FOR INSTALLATION.
LINE TO EXTEND COMPLETELY THROUGH WALL AND UP TO VALVE
LOCATED BELOW CEILING. GAS LINE CANNOT PROTRUDE MORE
THAN 3" FROM THE WALL.
3" DEEP
SEDIMENT TRAP
11NATURAL GAS COOKING LINE
NOT TO SCALE
FR
O
N
T
R
O
O
M
I
C
E
M
A
K
E
R
(D
I
N
I
N
G
R
O
O
M
B
E
V
E
R
A
G
E
U
N
I
T
)
BE
V
E
R
A
G
E
L
I
N
E
(D
I
N
I
N
G
R
O
O
M
)
PLUMBING DETAILS
P4.0
AUTHOR
CHECKER
79
6
M
e
r
u
s
C
o
u
r
t
St
.
L
o
u
i
s
,
M
O
6
3
0
2
6
T
6
3
6
.
3
4
9
.
1
6
0
0
F
6
3
6
.
3
4
9
.
1
7
3
0
CE
R
T
I
F
I
C
A
T
E
O
F
A
U
T
H
O
R
I
T
Y
N
O
.
3
8
0
0
8/18/2021
SEAL
DESCRIPTIONDATEREV.
ISSUE DATE: 08/17/2021
PROJECT NUMBER: 21-008
DRAWN BY:
CHECKED BY:
SHEET NAME
SHEET NUMBER
MO
O
D
Y
R
D
&
N
2
N
D
E
RE
X
B
U
R
G
,
I
D
8
3
4
4
0
PROJECT TYPE:
SITE NUMBER:
BUILDING TYPE:
OWNER:
BASE VERSION:
DRAWING RELEASE:
PROJECT YEAR:
ASSET TYPE:
CLASSIFICATION:
UPGRADE CLASSIFICATION:
DESIGN TYPE:
#13487
(2.0) SMART 40+
FREESTANDING
NEW
FRANCHISE
2020
NEW BUILD
2021
(2.0) UM BRITE
SUMMER
NEW
SMART 40+
1 10/20/2021 City Comments
ANCHOR TANK LEGS TO FLOOR OR PLATFORM OR AS REQUIRED BY LOCAL CODE AUTHORITIES.
SET TANK AS CLOSE TO WALL AS POSSIBLE.
PROVIDE WOOD BLOCKS FOR SPACERS BETWEEN
WALL AND TANK IF REQUIRED. ATTACH TO WALL AS
REQUIRED (TYP FOR 2)
PROVIDE 1"x18" STEEL BAND DOWN 1/3 FROM THE
TOP, AND UP 1/3 FROM THE BOTTOM OF TANK. BEND
ENDS OF STRAP AND ANCHOR SECURELY TO WALL
AS REQUIRED. (TYP FOR 2)
WATER
HEATER
OR TANK
NOT TO SCALE
TANK SEISMIC RESTRAINT 3
SUPPLY PIPE
4" LONG
SEDIMENT TRAP
G
SHUT-OFF VALVE.PRESSURE REGULATOR AS
REQUIRED
UNION.
BLACK IRON. PAINT LINES
SAFETY YELLOW. ROUTE
LINES TO AVOID CONFLICTS ROOF
TO EQUIPMENT
NOT TO SCALE
ROOFTOP UNIT GAS CONNECTION 1
PIPE
SIZE
SPACING TRANSVERSE
BRACE
LONGITUDINAL
BRACE
BOLT
SIZE
ROD
SIZE
MAX
ROD
LENGTH
VERTICAL
BRACETR. LO.
1"-2" 20' 20' 2"X2"X18GA 2"X2"X18GA
14"3 8" 20" 2"X2"X18GA
212"-3" 40' 40' 2
12"X212"X16GA 2
12"X212"X16GA 3 8"12"25" 2"X2"X16GA
4"-5" 40' 40' 2
12"X212"X16GA 2
12"X212"X16GA 12"5 8" 31" 2"X2"X16GA
6" 40' 40' 2
12"X212"X12GA 2
12"X212"X12GA 12"3 4"37"212"X212"X16GA
8" 40' 40'212"X212"X12GA 2
12"X212"X12GA 5 8"7 8"43" 2
12"X212"X12GA
10" 20' 20' 2
12"X212"X12GA 2
12"X212"X12GA 3 4"7 8" 43" 2
12"X212"X12GA
DO NOT BRACE ANY PIPES WHERE TOP OF PIPE TO BOTTOM OF UPPER ATTACHMENT IS LESS THAN 12". BRACE GAS, OIL AND AIR PIPES 1" AND LARGER. BRACE ALL PIPES IN EQUIPMENT ROOMS 1-1/4" AND
LARGER. BRACE ALL OTHER PIPE 2-1/2" AND LARGER. BRACE HUBLESS CAST IRON PIPE ON EACH SIDE OF ANY CHANGE IN DIRECTION OF 90 DEGREES OR MORE. MAXIMUM HANGER ROD LENGTH IS 6 FEET.
WHERE LENGTH OF RUN EXCEEDS LONGITUDINAL BRACE SPACING, PROVIDE 2 FEET OFFSET IN PIPE AND LOCATE BRACE AT MID RUNS. REFER TO CURRENT EDITION OF SMACNA "SEISMIC RESTRAINT MANUAL" FOR
ALTERNATIVE ATTACHMENTS AND ADDITIONAL INFORMATION AND REQUIREMENTS. (THIS DETAIL APPLIES IN THE ABSENCE OF OTHER LOCAL CODE REQUIREMENTS.)
STANDARD STEEL PIPE CLAMP
TRANSVERSE BRACE
4" MAXIMUM TYPICAL ALL BRACES
2 MAX.
1 MIN.
1
LONGITUDINAL BRACE
1 MIN.
2 MAX.
WELD
1/8" 1"-24"
STEEL
BEAM
CONCRETE
1
WOOD BEAM
PROVIDE ROD SIZE TABULATED,
WITH VERTICAL BRACE IF ROD
LENGTH EXCEEDS TABULATION.
ANGLE IRON BRACE AND
BOLTS PER TABLE (TYP.)
STEEL JOIST
PIPE
HANGER
DRILLED IN THREADED INSERT.
DO NOT USE SHOT-IN INSERTS.
BOLT (WITH TWO
WASHERS)
BETWEEN JOIST
MEMBERS
BOLT (WITH TWO
WASHERS) NEAR
TOP OF BEAM
BOLT (WITH TWO
WASHERS) NEAR
TOP OF BEAM
UPC ZONE 3 OR
4; SMACNA
SHL-A
NOT TO SCALE
SEISMIC BRACING FOR PIPE 4
7'
-
1
1
"
12" NSF 61 TUBING
CARBONATOR
RACK
NOT TO SCALE
CARBONATOR RACK ROUGH-IN 7
3" MAX.
2'
-
0
"
3'
-
0
"
1'
-
0
"
WHEEL CHOCK (BY OTHERS)
GAS MANIFOLD
USED COOKING OIL LINE
RESTRAINING CABLE (BY OTHERS)
REFER TO HOOD DRAWINGS
9GAS FRYER INSTALLATION
NOT TO SCALE
2'
-
6
"
2'-6"
WB WATER BOX WITH CAPPED DRAIN OUTLET. MARK
SUPPLY OUTLETS WITH R.O. AND F.W. STICKERS.
12" PEX-A FW TUBING IN WALL
COMBI
OVEN
12" PEX-A RO TUBING WALL
NOT TO SCALE
COMBI OVEN WATER ROUGH-IN 6
7'
-
4
3
/
4
"
T.O.F.F.
CEILING
8'-10"
WH-2
5'
-
1
3
/
4
"
T2061
3 4"HW
3 4"HW
5WAREWASH W/ WATER HEATER
NOT TO SCALE
PLUMBING DETAILS
P4.1
AUTHOR
CHECKER
79
6
M
e
r
u
s
C
o
u
r
t
St
.
L
o
u
i
s
,
M
O
6
3
0
2
6
T
6
3
6
.
3
4
9
.
1
6
0
0
F
6
3
6
.
3
4
9
.
1
7
3
0
CE
R
T
I
F
I
C
A
T
E
O
F
A
U
T
H
O
R
I
T
Y
N
O
.
3
8
0
0
8/18/2021
SEAL
DESCRIPTIONDATEREV.
ISSUE DATE: 08/17/2021
PROJECT NUMBER: 21-008
DRAWN BY:
CHECKED BY:
SHEET NAME
SHEET NUMBER
MO
O
D
Y
R
D
&
N
2
N
D
E
RE
X
B
U
R
G
,
I
D
8
3
4
4
0
PROJECT TYPE:
SITE NUMBER:
BUILDING TYPE:
OWNER:
BASE VERSION:
DRAWING RELEASE:
PROJECT YEAR:
ASSET TYPE:
CLASSIFICATION:
UPGRADE CLASSIFICATION:
DESIGN TYPE:
#13487
(2.0) SMART 40+
FREESTANDING
NEW
FRANCHISE
2020
NEW BUILD
2021
(2.0) UM BRITE
SUMMER
NEW
SMART 40+
1 10/20/2021 City Comments
PLUMBING SPECIFICATIONS
20500 GENERAL PROVISIONS
A. PROVIDE ALL MATERIALS AND EQUIPMENT AND PERFORM ALL LABOR REQUIRED TO INSTALL A
PLUMBING SYSTEM, COMPLETE AS INDICATED ON THE DRAWINGS, AS REQUIRED BY CODE AND AS
SPECIFIED HEREIN.
B. WITHOUT RESTRICTING THE GENERALITY OF THE FIRST STATEMENT, THE WORK TO BE
PERFORMED UNDER THIS DIVISION SHALL INCLUDE, BUT IS NOT LIMITED TO, THE FOLLOWING:
1. PLUMBING WORK AS DESCRIBED IN SECTIONS 220500 THROUGH 224000.
C. THE ELECTRICAL CONTRACTOR, UNLESS OTHERWISE NOTED, IS TO PROVIDE POWER WIRING FOR
EACH ITEM OF ELECTRICAL EQUIPMENT AND MAKE FINAL CONNECTIONS TO MOTORS.
D. ALL FINISH PAINTING IS TO BE PERFORMED BY THE GENERAL CONTRACTOR, EXCEPT AS NOTED
ELSEWHERE. THIS CONTRACTOR SHALL RESTORE TO ORIGINAL CONDITION ANY PAINTING
DEFACED BY THIS CONTRACTOR AFTER ORIGINAL PAINTING.
E. ALL WORK SHALL CONFORM TO CODES, RULES, AND REGULATIONS:
1. STATE PLUMBING CODE.
2. LOCAL BUILDING CODE.
3. NATIONAL FIRE PROTECTION ASSOCIATION.
4. CERTAIN CODES AND STANDARDS AS SET UP BY VARIOUS TECHNICAL SOCIETIES SUCH AS
ASME, ASHRAE, ASTM, SMACNA, ARI, AABC, OR IEEE.
5. FEDERAL OCCUPATIONAL SAFETY AND HEALTH STANDARDS.
6. LOCAL INSPECTOR'S REQUIREMENTS.
7. STATE INDUSTRIAL COMMISSION REQUIREMENTS.
8. BUILDING INSURING AGENCY REQUIREMENTS.
F. ALL PERMITS REQUIRED BY LAWS, ORDINANCES AND BUILDING CODES HAVING JURISDICTION
SHALL BE OBTAINED AT THE PROPER TIME BY AND AT THE EXPENSE OF THIS CONTRACTOR.
G. THIS CONTRACTOR SHALL OBTAIN ALL INSPECTIONS REQUIRED BY ALL LAWS, ORDINANCES AND
PUBLIC AUTHORITY HAVING JURISDICTION AND SHALL OBTAIN CERTIFICATES OF SUCH
INSPECTIONS AND SUBMIT SAME TO THE ARCHITECT AND SHALL PAY ALL FEES, CHARGES,
ASSESSMENTS AND OTHER EXPENSES IN CONNECTION THEREWITH.
H. PIPING AND EQUIPMENT LAYOUT IS SCHEMATIC. EXACT LOCATIONS ARE DETERMINED BY
STRUCTURAL AND OTHER CONDITIONS. DESIGN OF SYSTEM MAY NOT BE CHANGED. ONLY EXACT
LOCATION OF PIPING MAY BE REVISED TO SUIT CONSTRUCTION CONDITIONS AND AID IN
COORDINATION WITH WORK OF OTHER CONTRACTORS.
I. THE MATERIALS AND EQUIPMENT INSTALLED IN THE WORK SHALL MEET THE REQUIREMENTS OF
THE CONTRACT DOCUMENTS AND NO MATERIALS OR EQUIPMENT SHALL BE ORDERED UNTIL
REVIEWED BY THE ENGINEER AND/ OR ARCHITECT.
J. THIS CONTRACTOR SHALL SUBMIT SHOP DRAWINGS PER THE DOCUMENTS PROVIDED BY THE
OWNER/ARCHITECT/CONTRACTOR.
1. EXPANSION TANK
2. DRAINS AND CLEANOUTS
3. VALVES
4. ALL PLUMBING FIXTURES, FAUCETS AND FITTINGS
5. WATER HEATER
6. PIPE INSULATION
7. GREASE INTERCEPTOR
K. CATALOG DATA FOR EQUIPMENT REVIEWED BY THE ARCHITECT SHALL NOT SUPERSEDE THE
ENGINEER'S CONTRACT DOCUMENTS. THE REVIEW OF THE ENGINEER SHALL NOT RELIEVE THE
CONTRACTOR FROM RESPONSIBILITY FOR DEVIATIONS FROM DRAWINGS OR SPECIFICATIONS,
PROVIDING PROPER CLEARANCE FABRICATION PROCESS AND COORDINATION WITH OTHER
TRADES.
L. WHEN SUBMITTED FOR THE ARCHITECT'S REVIEW, SHOP DRAWINGS SHALL BEAR THE
CONTRACTOR'S CERTIFICATION THAT THEY HAVE REVIEWED, CHECKED AND APPROVED THE SHOP
DRAWINGS, THAT THEY ARE IN HARMONY WITH THE REQUIREMENTS OF THE PROJECT AND WITH
THE PROVISIONS OF THE CONTRACT DOCUMENTS AND THAT THEY HAVE VERIFIED ALL FIELD
MEASUREMENTS AND CONSTRUCTION CRITERIA, MATERIALS, CATALOG NUMBERS AND SIMILAR
DATA. CONTRACTOR SHALL ALSO CERTIFY THAT THE WORK REPRESENTED BY THE SHOP
DRAWINGS IS RECOMMENDED BY THE CONTRACTOR AND THE CONTRACTOR'S GUARANTEE WILL
FULLY APPLY.
M. ALL CONTRACTORS SUBMITTING PROPOSALS FOR THIS WORK SHALL FIRST EXAMINE THE SITE
AND ALL CONDITIONS THEREIN. ALL PROPOSALS SHALL TAKE INTO CONSIDERATION ALL SUCH
CONDITIONS AS MAY AFFECT THE WORK UNDER THIS CONTRACT. THE SUBMITTING OF A BID
AUTOMATICALLY IMPLIES THAT THIS EXAMINATION OF SITE HAS BEEN DONE.
N. CONTRACTOR SHALL VERIFY LOCATION OF UTILITIES AND NOTE CONDITIONS WHICH WOULD
AFFECT THE WORK. ALL DISCREPANCIES SHALL THEN BE REPORTED PRIOR TO THE BID AWARD.
O. PROVIDE INSTRUCTION TO OWNER'S OPERATING PERSONNEL AS NECESSARY, SHOWING
LOCATIONS AND PROPER OPERATION OF MAJOR ITEMS OF EQUIPMENT AND SYSTEM
COMPONENTS AND REFERRING TO THE OPERATING INSTRUCTION MANUAL DESCRIBED BELOW AS
A GUIDE.
P. COMPILE A WRITTEN MANUAL OF OPERATING INSTRUCTIONS INCLUDING COPIES OF SHOP
DRAWINGS AND A LISTING OF EQUIPMENT SUPPLIERS. ASSEMBLE IN 8-1/2" X 11" HARD BACKED
INDEXED BINDER. MATERIAL SHALL BE AS FOLLOWS:
1. TITLE PAGE: TITLE OF JOB, TENANT, ADDRESS, DATE OF SUBMISSION, CONTRACTOR AND
ENGINEER.
2. INDEX.
3. ST OF MAJOR EQUIPMENT USED IN PROJECT ACCOMPANIED BY CONTRACTOR PURCHASE
ORDER NUMBERS AND SUPPLIERS NAMES AND ADDRESSES.
4. ONE COPY OF EACH SHOP DRAWING GROUPED BY TYPES OF EQUIPMENT, I.E., PLUMBING
FIXTURES, VALVES, ETC.
5. SECTION FOR EACH SYSTEM INCLUDING:
5.1. BRIEF DESCRIPTION OF SYSTEM OPERATION WITH LOCATION OF MAJOR COMPONENTS.
5.2. LIST OF ITEMS IN SYSTEM REQUIRING PERIODIC SERVICE.
Q. SUBMIT A COMPLETED COPY TITLED "PLUMBING OPERATING INSTRUCTION MANUAL" ON THE
BINDING EDGE OF BINDER TO ARCHITECT FOR APPROVAL. AFTER ARCHITECT'S REVIEW AND ANY
CORRECTIONS REQUIRED ARE COMPLETED, SUBMIT A COPY OF THE MANUAL, TO THE OWNER.
220502 FIRESTOPPING
A. EACH CONTRACTOR SHALL BE RESPONSIBLE FOR FIRESTOPPING AROUND ALL OPENINGS FOR
PIPES, DUCTS, CONDUITS ETC., INSTALLED BY CONTRACTOR AT ALL FIRE WALLS. FIRESTOPPING
SHALL BE PERFORMED BY AN INSTALLER WHO HAS BEEN TRAINED BY THE MANUFACTURER, OR
MANUFACTURER'S REPRESENTATIVE, IN THE INSTALLATION PROCEDURES BASED ON PUBLISHED
UL TESTED FIRE STOP SYSTEMS.
B. FIRESTOPPING SHALL MEET THE REQUIREMENTS OF ASTM E-814 OR UL 1479 FIRE TESTS BY A
RECOGNIZED TESTING AGENCY. FIRESTOPPING SHALL ALSO CONFORM TO THE FOLLOWING
GOVERNING CODES: INTERNATIONAL BUILDING CODE, NFPA 101- LIFE SAFETY CODE & NFPA 70 -
NATIONAL ELECTRIC CODE.
C. PENETRATION
1. CLEAN PENETRATION HOLES OF DIRT, LOOSE MATERIALS AND FOREIGN MATTER WHICH MAY
AFFECT BOND OR INSTALLATION.
2. REMOVE COATINGS SUCH AS PAINT, CURING COMPOUNDS, WATER REPELLENT & SEALERS
AS REQUIRED.
3. INSTALL BACKING MATERIALS TO PREVENT LIQUID MATERIAL LEAKAGE.
D. APPLICATION
1. PREPARE AND APPLY PENETRATION SEALING SYSTEMS IN ACCORDANCE WITH
MANUFACTURER'S PRINTED INSTRUCTIONS.
2. EMPLOY INSTALLATION TECHNIQUES WHICH WILL ENSURE THAT FIRESTOPPING IS
DEPOSITED TO FILL AND SEAL HOLES AND OPENINGS.
3. TOOL EXPOSED SURFACES OF APPLIED SEALANT TO SMOOTH FINISH.
4. PROTECT MATERIALS FROM DAMAGE ON SURFACES SUBJECTED TO TRAFFIC.
E. PROVIDE INTUMESCENT SEALANTS AND COLLARS AT OPENINGS INVOLVING PLASTIC OR
INSULATED PIPE SIMILAR TO THE METACAULK SERIES 880 AND 950.
F. FIRESTOPPING BY DOW CORNING, 3M, HILTI OR METACAULK MAY FURNISHED AT THE
CONTRACTOR'S OPTION.
220529 PIPE ANCHORS, HANGERS AND SUPPORTS
A. ALL PIPING SHALL BE SEPARATELY HUNG AND SUPPORTED FROM APPROVED STRUCTURAL
MEMBERS OR CONCRETE OVERHEAD STRUCTURE ONLY. NO PIPE SHALL BE HUNG FROM ROOF
DECK, PIPE, DUCTS OR OTHER COMPONENTS OR EQUIPMENT OF OTHER TRADES.
B. PROVIDE LISTED/APPROVED ADJUSTABLE HANGERS, INSERTS, BRACKETS, CLAMPS,
SUPPLEMENTARY STEEL AND OTHER DEVICES REQUIRED FOR PROPER SUPPORT OF ALL PIPE
LINES.
C. HANGERS SHALL BE DESIGNED TO ALLOW FOR EXPANSION AND CONTRACTION AND TO ALLOW
INSULATION (WHERE APPLICABLE) TO RUN CONTINUOUSLY THROUGH HANGERS.
D. WIRE OR STRAP HANGERS ARE NOT PERMITTED. ADJUST HANGERS SO AS TO DISTRIBUTE WEIGHT
LOAD EQUALLY ON ATTACHMENTS.
220548 PLUMBING SYSTEM TESTING
A. SYSTEM TESTING SHALL PROVIDE FOR THE FOLLOWING:
1. TEST NEW INTERIOR DOMESTIC WATER SYSTEM.
2. TEST ALL SOIL, WASTE, AND VENT PIPING.
3. FURNISH ALL PUMPS FOR AIR AND WATER PRESSURE TESTS ALONG WITH GAUGES AND ANY
OTHER REQUIRED TEST EQUIPMENT.
4. UNDERGROUND LINES TO BE TESTED BEFORE BEING CONCEALED. CONTRACTOR SHALL
REPAIR ANY LEAKS AND ALL DAMAGE RESULTING THEREFROM.
5. CHANGES IN AMBIENT TEMPERATURE WILL BE TAKEN INTO ACCOUNT WHEN TESTING
UNDERGROUND PIPING, HOWEVER, THE VARIOUS SYSTEMS SHALL BE THOROUGHLY
INSPECTED FOR LEAKS BEFORE HYDROSTATIC PRESSURE TESTS ARE CONCLUDED.
6. INTERIOR WATER PIPING: HYDROSTATIC TEST AT 125 PSI AWWA PROCEDURES AND TO THE
SATISFACTION OF LOCAL AUTHORITY HAVING JURISDICTION.
7. SOIL, WASTE, AND VENT PIPING SHALL BE WATER AND SMOKE OR AIR TIGHT (STATE
PLUMBING CODE).
B. MEASURE LEAKAGE BY METERING WATER REQUIRED TO MAINTAIN LINE PRESSURE. REMOVE AIR
BEFORE TESTING.
C. REPAIR ANY LEAKING JOINTS AND DEMONSTRATE ACCEPTABLE LEAKAGE TO SATISFACTION OF
OWNER'S REPRESENTATIVE AND APPROVING AUTHORITY. FLUSH ALL PIPING BEFORE PLACING
INTO OPERATION.
220550 STERILIZATION
A. STERILIZE NEW DOMESTIC WATER LINES AFTER INSTALLATION.
B. FURNISH A CERTIFICATE OF STERILIZATION AND APPROVAL FOR HUMAN CONSUMPTION TO BE
SIGNED BY A PROFESSIONAL ENGINEER REGISTERED IN THIS STATE, REGULARLY EMPLOYED BY
THE TESTING LABORATORY. CERTIFICATE MUST BE GIVEN TO THE ARCHITECT AND OWNER
BEFORE FINAL PAYMENT WILL BE MADE.
C. STERILIZATION SHALL BE BY MEANS OF CHLORINE INJECTED INTO THE WATER SYSTEM NEAR THE
SOURCE AND OUTLETS THROUGHOUT THE SYSTEM SHALL BE TESTED TO PROVE PRESENCE OF
MINIMUM REQUIREMENTS. LEAVE CHLORINE IN FOR 24 HOURS AND FLUSH OUT SYSTEM UPON
COMPLETION OF WORK. STERILIZATION PROCEDURE SHALL BE WITNESSED BY THE OWNER'S
REPRESENTATIVE.
D. STERILIZATION SHALL BE PERFORMED UNDER THE IMMEDIATE SUPERVISION OF A WATER TESTING
LABORATORY REGULARLY ENGAGED IN THE SERVICE AND SHALL BE DONE ACCORDING TO THEIR
INSTRUCTIONS.
220560 IDENTIFICATION FOR PLUMBING PIPING AND EQUIPMENT
A. STENCILS, LABELS, TAGS, AND COLOR CODES SHALL CONFORM TO ANSI A13.
B. PRODUCTS SHALL BE SETON. EQUAL PRODUCTS BY BRADY MAY BE FURNISHED AT
CONTRACTOR'S OPTION.
C. STENCILS FOR EQUIPMENT SHALL BE REUSABLE AND HAVE 1" HIGH CHARACTERS. CHARACTERS
SHALL BE PAINTED WHITE OVER A BLACK BACKGROUND. STENCIL ONLY AFTER FINAL PAINTING IS
COMPLETE. CHARACTERS SHALL BE LEGIBLE FROM FLOOR. APPLY CLEAR ACRYLIC, LACQUER, OR
VARNISH OVER THE FINISHED STENCIL.
D. FOR PIPING PROVIDE ANSI STANDARD COLOR FLEXIBLE VINYL LABELS WITH PERMANENT
PRESSURE SENSITIVE ADHESIVE BACK. LABEL SHALL BE OF SUFFICIENT LENGTH TO ENCIRCLE
THE PIPE (AND INSULATION WHEN APPLICABLE) AND OVERLAP ON ITSELF. EACH LABEL SHALL
HAVE AT LEAST ONE FLOW DIRECTION ARROW AND SHALL BE PERMANENTLY LABELED WITH PIPE
CONTENT.
E. SYSTEM PIPING TO LABLED SHALL INCLUDE THE FOLLOWING:
1. DOMESTIC WATER (INCLUDING COLD, HOT, RECIRCULATING, FILTERED, AND REVERSE
OSMISIS)
2. SANITARY WASTE AND VENT (ABOVE GRADE ONLY)
3. NATURAL GAS
4. USED COOKING OIL
F. DOMESTIC WATER PIPING SHALL BE LABLED ON EXTEROR OF INSULATION IN ACCORDANCE WITH
ANSI A13.
G. PIPING, VALVES, DRAINS, CONTROL PANELS AND SIMILAR EQUIPMENT SHALL BE IDENTIFIED AS TO
FUNCTION AND SYSTEM NUMBER AS DIRECTED BY THE OWNER'S REPRESENTATIVE AND AS LISTED
BELOW:
IDENTIFICATION ITEM : TYPE
PIPING : STENCIL OR PIPE LABEL
VALVES : TAG
PIPING SPECIALTY : TAG
WATER HEATER AND OTHER EQUIPMENT : STENCIL
H. IDENTIFY PIPE LINES WITH STENCIL OR PIPE LABEL WITH COLOR CODED BANDS AT THE
FOLLOWING LOCATIONS:
1. AT EQUIPMENT CONNECTION AT EACH VALVE.
2. AT BOTH SIDES OF WALLS THROUGH WHICH PIPE PASSES.
3. AT EVERY 20 FT. INTERVAL ON CONTINUOUS PIPE LINES.
4. AT EACH BRANCH CONNECTION.
5. SHOW FLOW DIRECTION ARROWS AT EACH IDENTIFICATION POINT.
220700 INSULATION
A. PIPE INSULATION AND APPURTENANCES AND COVERINGS ON PIPES USED IN CHASES, SHAFTS OR
OTHER CONCEALED SPACES IN TYPES 1 AND 2 CONSTRUCTION SHALL HAVE A FLAME SPREAD
RATING NOT EXCEEDING TWENTY-FIVE (25) AND IN TYPE 3 AND 4 CONSTRUCTION NOT EXCEEDING
SEVENTY-FIVE (75) AND A SMOKE DEVELOPED RATING NOT EXCEEDING FIFTY (50).
B. INSULATION SHALL BE RIDGE ONE-PIECE FIBERGLASS PIPE INSULATION WITH REQUIREMENTS
COMPLYING WITH ASTM C 547, SELF-SEALING ADHESIVE LAP LONGITUDINAL JOINTS AND BUTT
STRIPS FOR TRANSVERSE JOINTS. JACKETING SHALL CONFORM TO ASTM C 1136, TYPE I,
MAXIMUM VAPOR TRANSMISSION RATING OF 0.02 PERM WHEN TESTED ACCORDING TO ASTM E 96,
PROCEDURE A. (K VALVE) 0.25 BTU/IN./HR. * FT2 * °F AT 75°F MEAN TEMPERATURE WITH A MINIMUM
R-VALVE OF R4.
PROVIDE INSULATION THICKNESS AS INDICATED:
DOMESTIC COLD WATER PIPING 1" AND SMALLER: 1/2" THICKNESS
DOMESTIC COLD WATER PIPING 1-1/4" - 1-1/2": 3/4" THICKNESS
DOMESTIC COLD WATER 2" AND LARGER: 1" THICKNESS
DOMESTIC HOT WATER PIPING 3/4" AND SMALLER: 1" THICKNESS
DOMESTIC HOT WATER PIPING 1" - 1-1/2: 1-1/2" THICKNESS
PLUMBING VENT PIPING WITHIN 6 FEET OF ROOF OUTLET: 1" THICKNESS
CONDENSATE PIPING: 1/2" THICKNESS
USED COOKING OIL : 1" THICKNESS
C. GLUE IN PLACE WITH SCHULLER U-GLUE.
D. THE FITTINGS SHALL BE INSULATED WITH SCHULLER ZESTON INSULATION AND HAVE FACTORY
PREMOLDED PVC COVERS. BUTT THE JOINTS TOGETHER AND WRAP WITH 3" WIDE STRIP TAPE,
SEAL IN PLACE WITH SCHULLER U-GLUE.
E. INSULATION SHALL NOT BE APPLIED UNTIL THE GENERAL CONSTRUCTION HAS PROGRESSED
SUFFICIENTLY TO INSURE AGAINST PHYSICAL OR MOISTURE DAMAGE TO THE INSULATION. ALL
INSULATION DAMAGED THROUGH FAILURE TO OBSERVE THIS DIRECTIVE SHALL BE REPLACED AT
PLUMBING CONTRACTOR'S EXPENSE.
F. INSTALL ALL INSULATION ACCORDING TO MANUFACTURER'S RECOMMENDATIONS.
G. INSULATION SHALL NOT BE APPLIED OVER FLANGES, JOINTS AND SEAMS IN PIPING.
H. INSULATION SHALL BE SCHULLER. EQUAL PRODUCT BY ARMSTRONG, CERTAINTEED,
OWENS-CORNING OR KNAUF MAY BE FURNISHED AT THE CONTRACTOR'S OPTION.
221113 PLUMBING BASIC MATERIALS AND METHODS
A. PROVIDE AND ERECT THE FOLLOWING PIPING AS SHOWN ON THE DRAWINGS AND/OR AS
REQUIRED.
1. SANITARY BUILDING DRAIN AND VENT PIPING SHALL BE SERVICE WEIGHT CAST IRON SOIL
PIPE.
2. SCHEDULE 40 PVC PIPING MAY BE USED FOR SANITARY WASTE AND VENT PIPING AT THE
CONTRACTOR'S OPTION IF CEILING SPACE IS NOT USED AS A RETURN AIR PLENUM SPACE.
3. DOMESTIC HOT AND COLD WATER USE TYPE "L" HARD COPPER PIPE.
4. CAST IRON - NON-COMBUSTIBLE PIPING REQUIRED IN WALL AT HOODS.
B. THIS CONTRACTOR IS TO BECOME INFORMED OF THE EXACT DIMENSIONS OF FINISHED WORK
WHERE PIPES ARE TO BE PLACED AND WILL ARRANGE THE WORK ACCORDINGLY, ASSUMING ALL
RESPONSIBILITY FOR PROPER LOCATION. IN THE ERECTION OF THE MAINS, SPECIAL CARE SHALL
BE USED PROVIDING SUPPORT AND PROPER ALLOWANCES SHALL BE MADE FOR EXPANSION.
C. ALL PIPE LINES MUST BE PROVIDED WITH A SUFFICIENT NUMBER OF FITTINGS OR UNIONS TO
MAKE POSSIBLE DISASSEMBLY WITHOUT BREAKAGE OF FITTINGS.
D. ALL EXPOSED PIPING SHALL BE NEAT AND CAREFULLY ALIGNED WITH THE STRUCTURAL
ELEMENTS OF THE BUILDING. NO OFFSETS OR OBLIQUE BENDS WILL BE PERMITTED. DRAWINGS
ARE DIAGRAMMATIC AND SHOULD NOT BE USED FOR LAYOUT WORK.
E. ALL LOW POINTS IN WATER PIPING TO HAVE DRAIN VALVES WITH STANDARD HOSE ATTACHMENTS.
HOT AND COLD WATER PIPING IS TO PITCH TOWARD THE NEAREST DRAIN VALVE.
F. ALL PIPES TO BE INSTALLED SHALL BE LOCATED AT SUFFICIENT DISTANCE FROM WALLS, OTHER
PIPES, CONDUIT, DUCTWORK AND OTHER OBSTACLES TO AVOID INTERFERENCE AND TO PERMIT
THE APPLICATION OF FULL THICKNESS OF INSULATION SPECIFIED.
G. MECHANICAL JOINT TYPE PIPING SHALL BE INSTALLED PER MANUFACTURER'S
RECOMMENDATIONS. THERMOMETERS BY TRERICE, ASHCROFT, MARSHALLTOWN, AND WEISS
ARE ACCEPTABLE.
221000 PLUMBING SYSTEMS
A. SANITARY BUILDING DRAIN, SOIL, WASTE AND VENT LINES SHALL BE SERVICE WEIGHT CAST IRON
HUBLESS PIPE WITH STAINLESS STEEL AT COUPLINGS. SCHEDULE 40 PVC MAY BE USED FOR
SANITARY WASTE AND VENT PIPING IF CEILING SPACE IS NOT USED AS A RETURN AIR PLENUM.
TYPE NO. S1110-4 MAY BE USED IN LIEU OF FIELD FABRICATED FLASHINGS.
B. VENT STACKS SHALL EXTEND THROUGH THE BUILDING, TERMINATING 12" ABOVE THE ROOF.
STANDARD FLASHING SHALL BE EXTENDED 12" IN ALL DIRECTIONS FROM THE VENT TERMINAL AND
TURNED DOWN INTO VENT. FLASHING UNITS AS MADE BY STONEMAN CAULK TYPE NO. S1110-4 MAY
BE USED IN LIEU OF FIELD FABRICATED FLASHINGS.
C. HORIZONTAL RUNS SHALL BE GIVEN AS STEEP A PITCH TOWARD THE OUTLET AS CONDITIONS WILL
PERMIT BUT NOT LESS THAN 1/8" PER FOOT.
D. FULL "Y" BRANCH FITTINGS AND EXTENSION WITH BRASS NIPPLES AND FINISHED SCREW PLUGS
FOR CLEANOUTS SHALL BE PLACED IN ACCESSIBLE POSITIONS AT ENDS OF HORIZONTAL LINES OF
PIPE AND AT FOOT OF ALL VERTICAL LINES OF PIPE OR ELSEWHERE, AS MAY BE REQUIRED BY THE
CODE.
E. WHERE CLEANOUTS OCCUR IN FINISHED AREAS, THEY SHALL BE RECESSED AND COVERS TO BE
FLUSH WITH THE FLOOR OR WALL.
F. HOT AND COLD WATER PIPING SHALL BE PROVIDED AS FOLLOWS:
1. TYPE "L" HARD COPPER TUBE WITH SOLDER FITTINGS. COPPER TUBING SHALL HAVE SWEAT
JOINTS AND BE CLEAN OF SCALE AND FOREIGN MATTER BEFORE INSTALLATION. ALL ENDS
OF TUBING TO BE SWEATED SHALL BE REAMED, CLEANED AND BURNISHED TO REMOVE DIRT
AND OXIDE. HARD 95-5 LEAD-FREE SOLDER SHALL BE USED AND APPLIED TO THE JOINTS
ACCORDING TO STANDARD PRACTICE AND/OR MANUFACTURER'S RECOMMENDATIONS.
COMPRESSION STOPS AND BRAIDED SUPPLIES SHALL BE USED AT CONNECTION TO
EQUIPMENT.
2. PEX-A TUBING WITH ASTM F1960 FITTINGS. PEX TUBING SHALL BE SUPPORTED WITH
ADDITIONAL PEX-A PIPE CHANNEL PER MANUFACTURER'S RECOMENDATIONS. PEX PIPING
SHALL BE TERMINATED AT FIXTURES WITH PREMANUFACTURERED COPPER STUBOUTS.
COMPRESSION STOPS, AND BRAIDED SUPPLIES SHALL BE USED AT CONNECTION TO
EQUIPMENT. PROVIDE RED TUBING FOR HOT WATER, BLUE TUBING FOR COLD WATER, AND
WHITE/TRANSLUCENT TUBING FOR ALL OTHER DOMESTIC WATER.
G. EACH HOT AND COLD WATER BRANCH SHALL BE PROVIDED WITH A BALL VALVE SHUT-OFF.
H. GREASE INTERCEPTOR - SHALL BE AS SPECIFIED ON DRAWINGS.
221118 GAS PIPING
A. ASTM A-53 SCHEDULE 40 STEEL PIPE PAINTED WITH YELLOW ANTI-CORROSIVE PAINT, SCREWED
OR WELDED IN ACCORDANCE WITH CODE REQUIREMENT (FITTINGS FOR LINES LARGER THAN 2"
SHALL BE WELDED STEEL. FITTINGS FOR LINES 2" AND SMALLER, EXCEPT WHEN LOCATED IN AIR
PLENUMS, SHALL BE SCREWED. STANDARD WEIGHT BLACK MALLEABLE). NO VALVES ARE TO BE
LOCATED IN AIR PLENUMS.
B. GAS COCK'S 1-1/2" AND SMALLER SHALL BE ALL BRONZE, SCREWED, FLAT HEAD, BRASS PLUG AND
WASHER 200 LB. NOG. PROVIDE LINE SIZE 6" LONG DIRT LEG DOWN STREAM OF GAS COCK AT ALL
EQUIPMENT CONNECTIONS.
C. PROVIDE AND INSTALL THE NATURAL GAS MANIFOLD FOR COOKING EQUIPMENT WHEN NATURAL
GAS IS USED FOR FRYERS.
D. ALL EQUIPMENT SHALL SHALL BE CONNECTED WITH RIGID PIPING AS SPECIFIED ABOVE, FLEXIBLE
CONNECTORS ARE NOT ACCEPTABLE.
E. PROVIDE UNION AT ALL EQUIPMENT CONNECTIONS.
F. PROVIDE GAS PIPE SUPPORTS IN ACCORDANCE WITH CODE REQUIREMENTS.
221120 DRAIN PIPING
A. FURNISH AND INSTALL A GRAVITY DRAIN PIPING SYSTEM FROM WATER HEATER, TERMINATING AT
THE MOP SINK.
B. PIPING IS TO BE SCHEDULE 40 PVC WITH DRAINAGE PATTERN FITTINGS, BONDED ACCORDING TO
THE MANUFACTURERS RECOMMENDATIONS.
C. PIPING IS TO BE SECURED TO PIPE HANGERS, USING PROPER SPACING AND THE APPROPRIATE
HEIGHT TO ALLOW THE PIPE TO PITCH PROPERLY.
221140 PLUMBING PIPING SPECIALTIES - USED COOKING OIL
A. ASTM A-53 SCHEDULE 40 STEEL PIPE THRESED AND SCREWED OR WELDED WITH STANDARD
WEIGHT BLACK MALLEABLE FITTINGS.
B. PROVIDE UNION AT ALL EQUIPMENT CONNECTIONS.
C. PROVIDE PIPE SUPPORTS AND STANDOFF HANGERS IN ACCORDANCE WITH CODE
REQUIREMENTS.
D. EXTERIOR UCO PIPING WITH INSULATION TO THE EXTERIOR TANK REQUIRES A STAINLESS STEEL
INSULATION JACKET WITH ALL JOINTS AND SEAMS SEALED WATER TIGHT USING WATERPROOF UV
RESISTANT CLEAR SEALANT (3M CLEAR HYBRID 730 UV OR EQUAL RATED TO 194 DEGREE F) WITH
THE ENDS COVERED TO PREVENT WATER INTRUSION AND SEAL. PROVIDE A PIPE ESCUTCHEON AT
THE WALL.
223300 WATER HEATER
ELECTRIC WATER HEATERS:
A. PROVIDE WATER HEATER, SIZE, LOCATION AND CAPACITY AND MANUFACTURER AS INDICATED ON
THE DRAWINGS.
B. TANK TYPE ELECTRIC WATER HEATER WITH GLASS-LINED TANK RATED AT 150 PSI WORKING
PRESSURE, MAGNESIUM ANODE PROTECTION, BRONZE DRAIN VALVE, HIGH TEMPERATURE
CUT-OFF SWITCH AND IMMERSION THERMOSTAT. TANK TO HAVE A MINIMUM R-VALUE OF 10.
C. FURNISH AND INSTALL A WATTS NO. 40L, 3/4" TEMPERATURE AND PRESSURE RELIEF VALVE AND
EXTEND DISCHARGE PIPE, FULL SIZE, TO WITHIN 6" ABOVE THE MOP SINK OR FLOOR DRAIN.
D. PROVIDE AMTROL EXPANSION TANK AS SIZED ON THE DRAWINGS. EQUAL PRODUCTS BY BELL AND
GOSSETT OR ADAMSON MAY BE PROVIDED AT THE CONTRACTOR'S OPTION.
FUEL FIRED WATER HEATERS
A. FURNISH AND INSTALL HIGH EFFICIENCY, 96% THERMAL EFFICIENCY OR BETTER, GAS FIRED,
STORAGE WATER HEATER, SIZE, LOCATION AND CAPACITY AS INDICATED ON THE DRAWINGS.
B. WATER HEATER SHALL BE RHEEM RUUD WITH INTELLIGENT CONTROL SYSTEM/LCD DISPLAY.
EQUAL HEATERS BY A.O. SMITH, OR LOCHINVAR MAY BE FURNISHED AT THE CONTRACTOR'S
OPTION.
C. TANK TYPE GAS FIRED WATER HEATER WITH GLASS-LINED TANK RATED AT 150 PSI WORKING
PRESSURE, POWERED ANODES PROTECTION, BRONZE DRAIN VALVE. TANK TO HAVE A MINIMUM
R-VALUE OF 10.
D. FACTORY-INSTALLED TEMPERATURE AND PRESSURE RELIEF VALVE. EXTEND DISCHARGE PIPE,
FULL SIZE, TO WITHIN 6" ABOVE THE MOP SINK OR FLOOR DRAIN.
E. PROVIDE WATTS, POTABLE WATER EXPANSION TANK AS SIZED ON THE DRAWINGS. EQUAL
PRODUCTS BY AMTROL BELL & GOSSETT MAY BE PROVIDED AT THE CONTRACTOR'S OPTION.
224000 PLUMBING FIXTURES AND EQUIPMENT
A. WATER CLOSETS AND LAVATORIES SHALL BE VITREOUS CHINA AND SHALL ALL BE BY THE SAM
MANUFACTURER.
B. ALL WALL HUNG LAVATORIES, FLUSH VALVES, ETC., SHALL BE PER DRAWINGS AND MOUNTED AT
THE MANUFACTURER'S RECOMMENDED ROUGHING IN MEASUREMENTS, UNLESS NOTED
OTHERWISE.
C. VALVES TO BE AS FOLLOWS:
125 LB. S.W.P. GATE, GLOBE AND CHECK VALVES:
2. GATE (2-1/2" AND SMALLER) - ALL BRONZE, SCREWED, TAPERED, SOLID WEDGE DISC,
SCREWED BONNET, RISING STEM.
3. BALL (2-1/2" AND SMALLER) - ALL BRONZE, TEFLON STEM SEALS AND SEAT, 1/4 TURN
SHUT-OFF, VINYL COVERED HANDLES.
4. GLOBE (2-1/2" AND SMALLER) - ALL BRONZE, SCREWED, TAPERED, SOLID WEDGE DISC,
SCREWED BONNET, RISING STEM.
5. CHECK (2-1/2" AND SMALLER) - ALL BRONZE, SCREWED, HORIZONTAL SWING CHECK WITH
BRONZE DISC.
C. VALVES SHALL BE MILWAUKEE. EQUAL PRODUCTS BY CRANE, HAMMOND, POWELL, WALWORTH,
NORTHERN INDIANA BRASS COMPANY OR STOCKHAM MAY BE FURNISHED AT THE CONTRACTOR'S
OPTION.
D. UNIONS TO BE AS FOLLOWS:
1. UNIONS FOR COPPER PIPE TO BE 150LB., ALL BRONZE, SOLDER END TYPE BY CHASE. EQUAL
PRODUCTS BY CRANE, MUELLER OR NORTHERN INDIANA BRASS COMPANY MAY BE
FURNISHED AT THE CONTRACTOR'S OPTION.
2. DIELECTRIC UNIONS BETWEEN FERROUS AND COPPER SHALL BE INSULATED TO PREVENT
METAL-TO-METAL CONTACT AND SHALL BE MANUFACTURED BY CAPITAL MANUFACTURING
COMPANY OF COLUMBUS, OHIO. EQUAL PRODUCTS BY PATROL OR PECO SALES COMPANY.
E. CLEANOUTS TO BE AS FOLLOWS:
1. FLOOR TYPE TO BE ADJUSTABLE CAST IRON WITH NICKEL BRONZE TOP. TOP TO BE FLUSH
WITH FLOOR. SEE DRAWINGS FOR MODEL AND MANUFACTURER.
2. WALL TYPE TO BE CAST IRON TEE WITH ROUND POLISHED STAINLESS STEEL ACCESS COVER
AND THREADED PLUG. SEE DRAWINGS FOR MODEL AND MANUFACTURER.
F. FLOOR DRAINS TO BE AS FOLLOWS:
1. CAST IRON BODY SHALLOW SUMP DRAIN WITH DOUBLE DRAINAGE FLANGE AND
WEEPHOLES, FLASHING CLAMP, BOTTOM OUTLET WITH NEOPRENE GASKET INSIDE
CONNECTOR, 6" DIAMETER ADJUSTABLE GRATE. FRAME AND GRATE TO HAVE POLISHED
NICKEL-BRONZE FINISH. SEE DRAWINGS FOR MODEL AND MANUFACTURER. EQUAL PRODUCT
MAY BE SUPPLIED AT THE CONTRACTOR'S OPTION.
PLUMBING
SPECIFICATIONS
P5.0
AUTHOR
CHECKER
79
6
M
e
r
u
s
C
o
u
r
t
St
.
L
o
u
i
s
,
M
O
6
3
0
2
6
T
6
3
6
.
3
4
9
.
1
6
0
0
F
6
3
6
.
3
4
9
.
1
7
3
0
CE
R
T
I
F
I
C
A
T
E
O
F
A
U
T
H
O
R
I
T
Y
N
O
.
3
8
0
0
8/18/2021
SEAL
DESCRIPTIONDATEREV.
ISSUE DATE: 08/17/2021
PROJECT NUMBER: 21-008
DRAWN BY:
CHECKED BY:
SHEET NAME
SHEET NUMBER
MO
O
D
Y
R
D
&
N
2
N
D
E
RE
X
B
U
R
G
,
I
D
8
3
4
4
0
PROJECT TYPE:
SITE NUMBER:
BUILDING TYPE:
OWNER:
BASE VERSION:
DRAWING RELEASE:
PROJECT YEAR:
ASSET TYPE:
CLASSIFICATION:
UPGRADE CLASSIFICATION:
DESIGN TYPE:
#13487
(2.0) SMART 40+
FREESTANDING
NEW
FRANCHISE
2020
NEW BUILD
2021
(2.0) UM BRITE
SUMMER
NEW
SMART 40+
1 10/20/2021 City Comments
03EXPOSED BRANCH DUCT INSTALLATION DETAIL
NOT TO SCALE
DIFFUSER STARTER COLLAR
90° 1.5R SPIRAL ELBOW
BEADED SLEEVE JOINT (TYPICAL)
SPIRAL BRANCH DUCT. SUPPORT WITH GALVANIZED STEEL STRAPS
ROUND BALANCING DAMPER
SPIRAL SUPPLY DUCT
BALANCING HANDLE. LOCK INTO
POSITION AND MARK PERMANENTLY
MOUNT DIFFUSER TIGHT
TO BOTTOM OF 90° ELBOW
1" DIAMETER CONDENSATE
DRAIN PIPE WITH SUPPORT AT
MAXIMUM 2 FOOT INTERVALS.
TERMINATE AT SCUPPER.
STRUCTURE BELOW SLOPES DOWN
AT 1/4" PER 1'-0"
5.5" THICK R-30
ROOF INSULATION
ROOF SHEATHING
SINGLE PLY ROOF
MEMBRANE
CURB MOUNTED RTU
LEVELING OF CURB
BY CONTRACTOR
EF-2 EF-1
RTU-1
3'-0"
3'
-
0
"
3'
-
0
"
PROVIDE 3" DEEP WATER
TRAP MINIMUM.
2X6 BLOCKING
DUCT DROP
INSULATION
STRIP
PROVIDE MANUFACTURER
REQUIRED CLEARANCE FROM RTU
TO FAN AND A MINIMUM OF 2'-0"
BETWEEN EF-1 & EF-2
APPROX. 53" ABOVE ROOF
SURFACE TO FAN DISCHARGE.
DISCHARGE TO BE SLIGHTLY
ABOVE THE ADJACENT
PARAPET. IN ALL CASES
MAINTAIN 40 INCHES ABOVE
ROOF TO FAN DISCHARGE
MINIMUM AND AT LEAST 18
INCHES CLEAR OF
COMBUSTIBLE MATERIAL.
INSTALLATION OF KITCHEN EXHAUST FANS
WILL PROVIDE 18 INCHES CLEAR OF FAN AND
FAN BASE TO COMBUSTIBLE MATERIALS
INCLUDING ROOF MEMBRANE MATERIAL
ALONG THE BASE OF THE CURB. FAN
DISCHARGE ELEVATION WILL BE AT LEAST 40
INCHES ABOVE THE ADJACENT ROOF.
DISCHARGE WILL BE 60 INCHES CLEAR OF
THE ADJACENT PARAPET IF THE FAN
DISCHARGE IS BELOW THE PARAPET HEIGHT.
THE DISCHARGE SHALL BE TEN FEET FROM
ANY ADJACENT BUILDING.
ALL EQUIPMENT SHALL BE FASTENED AND
CURBS PERMANENTLY AFFIXED. FINAL
INSTALLATION SHALL BE SUITABLE FOR WIND
LOADS AT THE SITE. ALL REQUIREMENTS ARE
TO BE REVIEWED AND APPROVED BY A
LICENSED PROFESSIONAL ENGINEER.
REFER TO STRUCTURAL FRAMING DETAILS
AND/OR STRUCTURAL REVIEW LETTER FOR
ROOF CURB STRUCTURAL FRAMING DETAILS.
08EXHAUST FAN AND RTU CURB DETAIL
1/4" = 1'-0"
6'
-
6
"
CO
IN A SHAFT PROVIDE CLEARANCE REDUCTION METHOD WITH A 6"
MINIMUM CLEARANCE.6"
KITCHEN CEILING
18"
22 GAUGE METAL
COMBUSTIBLE MATERIAL
1" NON COMBUSTIBLE SPACER
1" MINERAL WOOL BATT
SCREW
WEATHER PROTECTED OPENING.
NO 90° BENDS IN GREASE DUCT ALLOWED UNLESS RADIUS
ELBOWS WITH ACCESS PANELS ARE PROVIDED WITH
CONSTRUCTION MANAGER APPROVAL.
CONTRACTOR TO PROVIDE AIR
BALANCING IN DUCTWORK FOR ALL
KITCHEN EXHAUST FANS.
CURB AS SUPPLIED
BY FAN MANUFACTURER
LISTED ACCESS
OPENING ROOF
REFER TO 08/M2.0
KITCHEN HOOD DUCTWORK SHALL BE 16 GAUGE CARBON
STEEL OR 18 GAUGE STAINLESS STEEL. DUCTWORK SHALL BE
CONTINUOUSLY EXTERNALLY WELDED LIQUID TIGHT. ALL
PORTIONS OF WELDED DUCTWORK SHALL BE SLOPED BACK
TO HOOD FOR DRAINAGE WITH NO TRAPS. CONTRACTOR
SHALL COORDINATE AT SITE WITH TRADES TO ENSURE THIS
CAN BE DONE.
OPERATION OF KITCHEN HOOD SHALL BE INTERLOCKED WITH
ASSOCIATED EXHAUST FAN, MOTORIZED DAMPERS,
ASSOCIATED UNITS BRINGING IN MAKE UP AIR AND ANY
REMOTE APPLIANCE WHERE FLUE IS DISCHARGING INTO
HOOD. UPON ACTIVATION OF FIRE SUPPRESSION SYSTEM,
MAKE UP AIR SYSTEM AND ALL APPLIANCES WILL SHUT
DOWN AND KITCHEN EXHAUST SYSTEM WILL CONTINUE TO
OPERATE.
ALL GAS PIPING SHALL FOLLOW APPLICABLE GAS CODES AND
BE INSTALLED BY A LICENSED CONTRACTOR FAMILIAR WITH
THESE CODES.
PROVIDE AUTOMATICALLY ELECTRICALLY OPERATED GAS
VALVE SERVING GAS FIRED COOKING EQUIPMENT BEING
SERVED BY AUTOMATIC FIRE EXTINGUISHING SYSTEM.
PROVIDE INTERLOCK SO THAT COOKING EQUIPMENT WILL
SHUT-DOWN ON ACTIVATION OF FIRE SUPPRESSION SYSTEM.
VALVE SHALL BE LABELED, WITH INSTRUCTIONS AND
LOCATED OUTSIDE OF PROTECTED AREA. AN ADDITIONAL
MANUAL SHUT-OFF VALVE SHALL BE ACCESSIBLE AND BE
LOCATED IMMEDIATELY UPSTREAM OF AUTOMATIC VALVE.PROVIDE MAIN GAS VALVE TO
SHUT DOWN COOK LINE.
LOCATE VALVE NEAR COOK
LINE SO EMPLOYEE CAN
MANUALLY SHUT DOWN
WITHOUT HAVING TO USE
LADDER, ETC.
EMERGENCY PULL
STATION SHALL BE
ACCESSIBLY
LOCATED 42" TO 48"
OFF FLOOR AT
POINT OF EXIT
DURING A FIRE. SEE
POWER PLAN FOR
LOCATION.
CLEARANCE AND CLEARANCE REDUCTION METHODS
NFPA 96 1-3.2 CLEARANCE NOTE:
HOODS, GREASE EXTRACTORS, DUCTS, ECOLOGY UNITS,
FANS SHALL HAVE A CLEARANCE OF AT LEAST:
18" TO COMBUSTIBLES
3" TO LIMITED COMBUSTIBLES, 6" IN SHAFT
0" TO NON COMBUSTIBLES, 6" IN SHAFT
WHERE SPACE DOES NOT ALLOW FOR NOTED CLEARANCES
AS IT PERTAINS TO THE TYPE OF CONSTRUCTION, A
CLEARANCE REDUCTION METHOD MAY BE APPLIED.
OPTION 1 : AS ILLUSTRATED BELOW
OPTION 2 : USE LISTED 3M FIRE DUCT WRAP 615+
MANUFACTURER PREFABRICATED UL APPROVED
INSULATED GREASE EXHAUST DUCT IS PERMITTED
IF PROVIDED BY THE HOOD SUPPLIER AS PART OF
A COMPLETE HOOD AND FAN PACKAGED SYSTEM.
COMPLETE ERECTION DOCUMENTS DETAILING THE
REQUIRED INSTALLATION PROCEDURES SHALL BE
PROVIDED FOR THE CODE OFFICIAL AND THE
INSTALLING CONTRACTOR. DUCT SHALL CONFORM
TO ALL NFPA 96 REQUIREMENTS AND UL LISTING.
PROVIDE ACCESSIBLE CLEANOUTS
AT EVERY 90 DEGREE CHANGE IN
DIRECTION AND AT THE TOP OF A
VERTICAL RISER UNDER ROOF.
01MECHANICAL EXHAUST DUCT DETAIL
NOT TO SCALE
D
(2) D
D
D
04RADIUS ELBOW
NOT TO SCALE
8"
M
I
N
.
3 PIECE PVC DURO-LAST CHILLER STACK KIT
DURO-LAST CAULK
DURO-LAST PREFABRICATED VENT STACK FLASHING
REFRIGERATION LINESROOF DECK
ALL COUNTERFLASHING DRIP SHIELD AND EXPOSED
DUCTWORK SHALL BE 18 GA. GALVANIZED SHEETMETAL
ALL SOLDERED AIR-TIGHT CONSTRUCTION
STAINLESS STEEL BAND POSITIONED 1/4"
FROM THE TOP OF THE STACK FLASHING
INSULATION
MEMBRANE
NOT TO SCALE
GOOSENECK WEATHERHOLD ROOF PENETRATION DETAIL 09
CB
FE
L
L
WHEN SHOWNTAPS TO TRUNK ONLY
ECCENTRIC
TRANSITION
CONCENTRIC
TRANSITION
RECTANGULAR TO ROUND
RECTANGULAR TO ROUND RECTANGULAR TO RECTANGULAR
ROUND TO ROUND
45°
ROUND DUCT BRANCH DUCT
MAIN DUCT
AIR FLOW
AIR FLOW
RECTANGULAR DUCT
AIR FLOW
45
RECTANGULAR DUCT
CONICAL FITTING. SEAL
AIRTIGHT WITH MASTIC
Ø-MAX.45° DIVERGING,
60° CONVERGING
Ø-MAX.
Ø
Ø
°
NOTE: USE PLAN AS GUIDE
TO FITTING TYPE.
A
D
02DUCT FITTING DETAILS
NOT TO SCALE
1-1/2"
NOTE:
FOR DUCT SUPPORT
AND SEISMIC
REQUIREMENTS, REFER
TO SMACNA GUIDELINES
AND LOCAL CODE
REQUIREMENTS.
STRAP
1/4" BOLT
STRAP
05ROUND DUCT HANGER DETAIL
NOT TO SCALE
METAL BAND SUPPORT
NYLON DRAW BAND (TYP)
SUPPLY AIR
DIFFUSER WITH
ROUND NECK
PROVIDE 1" BLANKET
INSULATION COVERING
AIR DEVICE BACK
FLEX DUCT
WITH 2"
EXTERNAL
INSULATION
MAX. LENGTH
6'-0"
T-BAR TYPE/GYP
SUSPENDED CEILING
RIGID ROUND
INSULATED DUCT JOINT
SCREWED & SEALED
INSULATED SHEETMETAL
SUPPLY DUCT. SEAL PER
SPECIFICATIONS
TIE OFF TO ROOF
STRUCTURE
06CEILING DIFFUSER DETAIL
NOT TO SCALE
NOTES:
1. DETAIL IS FOR CONDENSATE DRAIN CONNECTIONS LOCATED ON FAN INLET SIDE ONLY.
2. SLOPE CONDENSATE DRAIN AS MUCH AS POSSIBLE TOWARD DISCHARD POINT BUT NO LESS
THAN 1/4" PER FOOT. PROVIDE CLEANOUTS AT TURNS AND WHERE INDICATED. USE
SCHEDULE 40 PVC PIPE AND FITTINGS WITH PRIMED AND SOLVENT WELDED JOINTS. USE
DWV FITTINGS FOR SIZES 1-1/4" DIAMETER AND LARGER PIPE. SUPPORT PIPING AT FOUR
FOOT INTERVALS MAXIMUM.
3. PIPING ARRANGEMENT SHOWN IS SCHEMATIC. ADJUST AS REQUIRED TO SUIT SITE
CONDITION. REFER TO LOCAL CODE REQUIREMENTS FOR INDIRECT DRAIN REQUIREMENTS.
4. PROVIDE 6" HIGH PIPE VENT OPEN TO ATMOSPHERE IF REQUIRED BY LOCAL CODES.
TYPICAL ROOFTOP AIR
CONDITIONING UNIT
CONDENSATE CONNECTION. TRAP SIZE TO BE
EQUAL TO OR LARGER THAN CONNECTION SIZE BUT
NO LESS THAN 3/4"
PROVIDE MIRO INDUSTRIES MODEL 3-RAH ADJUSTABLE PIPE SUPPORTS & PADS, OR
EQUIVALENT. PROVIDE SUPPORTS TO PREVENT PIPE SAGGING AND ALLOW FOR SLOPE.
UNION CONNECTION2"
1"
ROUTE TO NEAREST SCUPPER
CLEANOUT TEE WITH PLUG (TYP.)
DIMENSION SHALL BE EQUAL TO OR
GREATER THAN FAN INLET PRESSURE IN
INCHES PLUS ONE INCH THEN DIVIDED BY
TWO (MINIMUM DIMENSION IS ONE INCH).
DIMENSION SHALL BE EQUAL TO OR
GREATER THAN FAN INLET PRESSURE IN
INCHES PLUS ONE INCH (MINIMUM
DIMENSION ALLOWED IS TWO INCHES).
ROOF
10ROOFTOP UNIT CONDENSATE
5" = 1'-0"
22 GAUGE GALVANIZED SHEET
METAL PLENUM WITH
EXTERNALLY APPLIED 2" THICK
EXTERNAL DUCT WRAP
PERFORATED SD-2 DIFFUSER
07DUMP BOX DETAIL
NOT TO SCALE
CEILING
INSULATED FLEXIBLE DUCT
WITH BAND FASTENER
ROUND SPIN-IN
DUCT COLLAR
10"
24"
16"FASTEN TO DIFFUSER IN
EIGHT PLACES WITH
SHEETMETAL SCREWS
(TWO ON EACH CORNER
SIDE OF PLENUM BOX)
2"
NOTES:
1. TOP INLETS TO PLENUM BOX ARE NOT ALLOWED.
2. DOVETAIL COLLARS ARE NOT ALLOWED.
3. SEAL COLLAR WITH SEAL CLASS 'A' DUCT SEALANT.
4. DO NOT CRUSH OR MODIFY DUMP BOX SIZE TO FIT OTHER
MECHANICAL EQUIPMENT IN CEILING CAVITY.
SUPPORT TO STUCTURE
WITH SHEETMETAL STRAPS
DROP FROM
HVAC EQUIPMENT
RECTANGULAR
TRUNK DUCT ROUND TRUNK DUCT
MANUAL DAMPER
(TYPICAL)
45° ENTRY
FITTING (TYPICAL)
FLEXIBLE DUCT
NOT TO SCALE
ROOFTOP EQUIPMENT DUCT DROP DETAIL 11 03EXPOSED BRANCH DUCT INSTALLATION DETAIL
NOT TO SCALE
DIFFUSER STARTER COLLAR
90° 1.5R SPIRAL ELBOW
BEADED SLEEVE JOINT (TYPICAL)
SPIRAL BRANCH DUCT. SUPPORT WITH GALVANIZED STEEL STRAPS
ROUND BALANCING DAMPER
SPIRAL SUPPLY DUCT
BALANCING HANDLE. LOCK INTO
POSITION AND MARK PERMANENTLY
MOUNT DIFFUSER TIGHT
TO BOTTOM OF 90° ELBOW
1" DIAMETER CONDENSATE
DRAIN PIPE WITH SUPPORT AT
MAXIMUM 2 FOOT INTERVALS.
TERMINATE AT SCUPPER.
STRUCTURE BELOW SLOPES DOWN
AT 1/4" PER 1'-0"
5.5" THICK R-30
ROOF INSULATION
ROOF SHEATHING
SINGLE PLY ROOF
MEMBRANE
CURB MOUNTED RTU
LEVELING OF CURB
BY CONTRACTOR
EF-2 EF-1
RTU-1
3'-0"
3'
-
0
"
3'
-
0
"
PROVIDE 3" DEEP WATER
TRAP MINIMUM.
2X6 BLOCKING
DUCT DROP
INSULATION
STRIP
PROVIDE MANUFACTURER
REQUIRED CLEARANCE FROM RTU
TO FAN AND A MINIMUM OF 2'-0"
BETWEEN EF-1 & EF-2
APPROX. 53" ABOVE ROOF
SURFACE TO FAN DISCHARGE.
DISCHARGE TO BE SLIGHTLY
ABOVE THE ADJACENT
PARAPET. IN ALL CASES
MAINTAIN 40 INCHES ABOVE
ROOF TO FAN DISCHARGE
MINIMUM AND AT LEAST 18
INCHES CLEAR OF
COMBUSTIBLE MATERIAL.
INSTALLATION OF KITCHEN EXHAUST FANS
WILL PROVIDE 18 INCHES CLEAR OF FAN AND
FAN BASE TO COMBUSTIBLE MATERIALS
INCLUDING ROOF MEMBRANE MATERIAL
ALONG THE BASE OF THE CURB. FAN
DISCHARGE ELEVATION WILL BE AT LEAST 40
INCHES ABOVE THE ADJACENT ROOF.
DISCHARGE WILL BE 60 INCHES CLEAR OF
THE ADJACENT PARAPET IF THE FAN
DISCHARGE IS BELOW THE PARAPET HEIGHT.
THE DISCHARGE SHALL BE TEN FEET FROM
ANY ADJACENT BUILDING.
ALL EQUIPMENT SHALL BE FASTENED AND
CURBS PERMANENTLY AFFIXED. FINAL
INSTALLATION SHALL BE SUITABLE FOR WIND
LOADS AT THE SITE. ALL REQUIREMENTS ARE
TO BE REVIEWED AND APPROVED BY A
LICENSED PROFESSIONAL ENGINEER.
REFER TO STRUCTURAL FRAMING DETAILS
AND/OR STRUCTURAL REVIEW LETTER FOR
ROOF CURB STRUCTURAL FRAMING DETAILS.6'
-
6
"
CO
IN A SHAFT PROVIDE CLEARANCE REDUCTION METHOD WITH A 6"
MINIMUM CLEARANCE.6"
KITCHEN CEILING
18"
22 GAUGE METAL
COMBUSTIBLE MATERIAL
1" NON COMBUSTIBLE SPACER
1" MINERAL WOOL BATT
SCREW
WEATHER PROTECTED OPENING.
NO 90° BENDS IN GREASE DUCT ALLOWED UNLESS RADIUS
ELBOWS WITH ACCESS PANELS ARE PROVIDED WITH
CONSTRUCTION MANAGER APPROVAL.
CONTRACTOR TO PROVIDE AIR
BALANCING IN DUCTWORK FOR ALL
KITCHEN EXHAUST FANS.
CURB AS SUPPLIED
BY FAN MANUFACTURER
LISTED ACCESS
OPENING ROOF
REFER TO 08/M2.0
KITCHEN HOOD DUCTWORK SHALL BE 16 GAUGE CARBON
STEEL OR 18 GAUGE STAINLESS STEEL. DUCTWORK SHALL BE
CONTINUOUSLY EXTERNALLY WELDED LIQUID TIGHT. ALL
PORTIONS OF WELDED DUCTWORK SHALL BE SLOPED BACK
TO HOOD FOR DRAINAGE WITH NO TRAPS. CONTRACTOR
SHALL COORDINATE AT SITE WITH TRADES TO ENSURE THIS
CAN BE DONE.
OPERATION OF KITCHEN HOOD SHALL BE INTERLOCKED WITH
ASSOCIATED EXHAUST FAN, MOTORIZED DAMPERS,
ASSOCIATED UNITS BRINGING IN MAKE UP AIR AND ANY
REMOTE APPLIANCE WHERE FLUE IS DISCHARGING INTO
HOOD. UPON ACTIVATION OF FIRE SUPPRESSION SYSTEM,
MAKE UP AIR SYSTEM AND ALL APPLIANCES WILL SHUT
DOWN AND KITCHEN EXHAUST SYSTEM WILL CONTINUE TO
OPERATE.
ALL GAS PIPING SHALL FOLLOW APPLICABLE GAS CODES AND
BE INSTALLED BY A LICENSED CONTRACTOR FAMILIAR WITH
THESE CODES.
PROVIDE AUTOMATICALLY ELECTRICALLY OPERATED GAS
VALVE SERVING GAS FIRED COOKING EQUIPMENT BEING
SERVED BY AUTOMATIC FIRE EXTINGUISHING SYSTEM.
PROVIDE INTERLOCK SO THAT COOKING EQUIPMENT WILL
SHUT-DOWN ON ACTIVATION OF FIRE SUPPRESSION SYSTEM.
VALVE SHALL BE LABELED, WITH INSTRUCTIONS AND
LOCATED OUTSIDE OF PROTECTED AREA. AN ADDITIONAL
MANUAL SHUT-OFF VALVE SHALL BE ACCESSIBLE AND BE
LOCATED IMMEDIATELY UPSTREAM OF AUTOMATIC VALVE.PROVIDE MAIN GAS VALVE TO
SHUT DOWN COOK LINE.
LOCATE VALVE NEAR COOK
LINE SO EMPLOYEE CAN
MANUALLY SHUT DOWN
WITHOUT HAVING TO USE
LADDER, ETC.
EMERGENCY PULL
STATION SHALL BE
ACCESSIBLY
LOCATED 42" TO 48"
OFF FLOOR AT
POINT OF EXIT
DURING A FIRE. SEE
POWER PLAN FOR
LOCATION.
CLEARANCE AND CLEARANCE REDUCTION METHODS
NFPA 96 1-3.2 CLEARANCE NOTE:
HOODS, GREASE EXTRACTORS, DUCTS, ECOLOGY UNITS,
FANS SHALL HAVE A CLEARANCE OF AT LEAST:
18" TO COMBUSTIBLES
3" TO LIMITED COMBUSTIBLES, 6" IN SHAFT
0" TO NON COMBUSTIBLES, 6" IN SHAFT
WHERE SPACE DOES NOT ALLOW FOR NOTED CLEARANCES
AS IT PERTAINS TO THE TYPE OF CONSTRUCTION, A
CLEARANCE REDUCTION METHOD MAY BE APPLIED.
OPTION 1 : AS ILLUSTRATED BELOW
OPTION 2 : USE LISTED 3M FIRE DUCT WRAP 615+
MANUFACTURER PREFABRICATED UL APPROVED
INSULATED GREASE EXHAUST DUCT IS PERMITTED
IF PROVIDED BY THE HOOD SUPPLIER AS PART OF
A COMPLETE HOOD AND FAN PACKAGED SYSTEM.
COMPLETE ERECTION DOCUMENTS DETAILING THE
REQUIRED INSTALLATION PROCEDURES SHALL BE
PROVIDED FOR THE CODE OFFICIAL AND THE
INSTALLING CONTRACTOR. DUCT SHALL CONFORM
TO ALL NFPA 96 REQUIREMENTS AND UL LISTING.
PROVIDE ACCESSIBLE CLEANOUTS
AT EVERY 90 DEGREE CHANGE IN
DIRECTION AND AT THE TOP OF A
VERTICAL RISER UNDER ROOF.
D
(2) D
D
D
8"
M
I
N
.
3 PIECE PVC DURO-LAST CHILLER STACK KIT
DURO-LAST CAULK
DURO-LAST PREFABRICATED VENT STACK FLASHING
REFRIGERATION LINESROOF DECK
ALL COUNTERFLASHING DRIP SHIELD AND EXPOSED
DUCTWORK SHALL BE 18 GA. GALVANIZED SHEETMETAL
ALL SOLDERED AIR-TIGHT CONSTRUCTION
STAINLESS STEEL BAND POSITIONED 1/4"
FROM THE TOP OF THE STACK FLASHING
INSULATION
MEMBRANE
CB
FE
L
L
WHEN SHOWNTAPS TO TRUNK ONLY
ECCENTRIC
TRANSITION
CONCENTRIC
TRANSITION
RECTANGULAR TO ROUND
RECTANGULAR TO ROUND RECTANGULAR TO RECTANGULAR
ROUND TO ROUND
45°
ROUND DUCT BRANCH DUCT
MAIN DUCT
AIR FLOW
AIR FLOW
RECTANGULAR DUCT
AIR FLOW
45
RECTANGULAR DUCT
CONICAL FITTING. SEAL
AIRTIGHT WITH MASTIC
Ø-MAX.45° DIVERGING,
60° CONVERGING
Ø-MAX.
Ø
Ø
°
NOTE: USE PLAN AS GUIDE
TO FITTING TYPE.
A
D
1-1/2"
NOTE:
FOR DUCT SUPPORT
AND SEISMIC
REQUIREMENTS, REFER
TO SMACNA GUIDELINES
AND LOCAL CODE
REQUIREMENTS.
STRAP
1/4" BOLT
STRAP
METAL BAND SUPPORT
NYLON DRAW BAND (TYP)
SUPPLY AIR
DIFFUSER WITH
ROUND NECK
PROVIDE 1" BLANKET
INSULATION COVERING
AIR DEVICE BACK
FLEX DUCT
WITH 2"
EXTERNAL
INSULATION
MAX. LENGTH
6'-0"
T-BAR TYPE/GYP
SUSPENDED CEILING
RIGID ROUND
INSULATED DUCT JOINT
SCREWED & SEALED
INSULATED SHEETMETAL
SUPPLY DUCT. SEAL PER
SPECIFICATIONS
TIE OFF TO ROOF
STRUCTURE
NOTES:
1. DETAIL IS FOR CONDENSATE DRAIN CONNECTIONS LOCATED ON FAN INLET SIDE ONLY.
2. SLOPE CONDENSATE DRAIN AS MUCH AS POSSIBLE TOWARD DISCHARD POINT BUT NO LESS
THAN 1/4" PER FOOT. PROVIDE CLEANOUTS AT TURNS AND WHERE INDICATED. USE
SCHEDULE 40 PVC PIPE AND FITTINGS WITH PRIMED AND SOLVENT WELDED JOINTS. USE
DWV FITTINGS FOR SIZES 1-1/4" DIAMETER AND LARGER PIPE. SUPPORT PIPING AT FOUR
FOOT INTERVALS MAXIMUM.
3. PIPING ARRANGEMENT SHOWN IS SCHEMATIC. ADJUST AS REQUIRED TO SUIT SITE
CONDITION. REFER TO LOCAL CODE REQUIREMENTS FOR INDIRECT DRAIN REQUIREMENTS.
4. PROVIDE 6" HIGH PIPE VENT OPEN TO ATMOSPHERE IF REQUIRED BY LOCAL CODES.
TYPICAL ROOFTOP AIR
CONDITIONING UNIT
CONDENSATE CONNECTION. TRAP SIZE TO BE
EQUAL TO OR LARGER THAN CONNECTION SIZE BUT
NO LESS THAN 3/4"
PROVIDE MIRO INDUSTRIES MODEL 3-RAH ADJUSTABLE PIPE SUPPORTS & PADS, OR
EQUIVALENT. PROVIDE SUPPORTS TO PREVENT PIPE SAGGING AND ALLOW FOR SLOPE.
UNION CONNECTION2"
1"
ROUTE TO NEAREST SCUPPER
CLEANOUT TEE WITH PLUG (TYP.)
DIMENSION SHALL BE EQUAL TO OR
GREATER THAN FAN INLET PRESSURE IN
INCHES PLUS ONE INCH THEN DIVIDED BY
TWO (MINIMUM DIMENSION IS ONE INCH).
DIMENSION SHALL BE EQUAL TO OR
GREATER THAN FAN INLET PRESSURE IN
INCHES PLUS ONE INCH (MINIMUM
DIMENSION ALLOWED IS TWO INCHES).
ROOF
22 GAUGE GALVANIZED SHEET
METAL PLENUM WITH
EXTERNALLY APPLIED 2" THICK
EXTERNAL DUCT WRAP
PERFORATED SD-2 DIFFUSER
07DUMP BOX DETAIL
NOT TO SCALE
CEILING
INSULATED FLEXIBLE DUCT
WITH BAND FASTENER
ROUND SPIN-IN
DUCT COLLAR
10"
24"
16"FASTEN TO DIFFUSER IN
EIGHT PLACES WITH
SHEETMETAL SCREWS
(TWO ON EACH CORNER
SIDE OF PLENUM BOX)
2"
NOTES:
1. TOP INLETS TO PLENUM BOX ARE NOT ALLOWED.
2. DOVETAIL COLLARS ARE NOT ALLOWED.
3. SEAL COLLAR WITH SEAL CLASS 'A' DUCT SEALANT.
4. DO NOT CRUSH OR MODIFY DUMP BOX SIZE TO FIT OTHER
MECHANICAL EQUIPMENT IN CEILING CAVITY.
SUPPORT TO STUCTURE
WITH SHEETMETAL STRAPS
DROP FROM
HVAC EQUIPMENT
RECTANGULAR
TRUNK DUCT ROUND TRUNK DUCT
MANUAL DAMPER
(TYPICAL)
45° ENTRY
FITTING (TYPICAL)
FLEXIBLE DUCT
NOT TO SCALE
ROOFTOP EQUIPMENT DUCT DROP DETAIL 11
10ROOFTOP UNIT CONDENSATE
5" = 1'-0"06CEILING DIFFUSER DETAIL
NOT TO SCALE
05ROUND DUCT HANGER DETAIL
NOT TO SCALE
02DUCT FITTING DETAILS
NOT TO SCALE
NOT TO SCALE
GOOSENECK WEATHERHOLD ROOF PENETRATION DETAIL 09
04RADIUS ELBOW
NOT TO SCALE 01MECHANICAL EXHAUST DUCT DETAIL
NOT TO SCALE08EXHAUST FAN AND RTU CURB DETAIL
1/4" = 1'-0"
03EXPOSED BRANCH DUCT INSTALLATION DETAIL
NOT TO SCALE
DIFFUSER STARTER COLLAR
90° 1.5R SPIRAL ELBOW
BEADED SLEEVE JOINT (TYPICAL)
SPIRAL BRANCH DUCT. SUPPORT WITH GALVANIZED STEEL STRAPS
ROUND BALANCING DAMPER
SPIRAL SUPPLY DUCT
BALANCING HANDLE. LOCK INTO
POSITION AND MARK PERMANENTLY
MOUNT DIFFUSER TIGHT
TO BOTTOM OF 90° ELBOW
1" DIAMETER CONDENSATE
DRAIN PIPE WITH SUPPORT AT
MAXIMUM 2 FOOT INTERVALS.
TERMINATE AT SCUPPER.
STRUCTURE BELOW SLOPES DOWN
AT 1/4" PER 1'-0"
5.5" THICK R-30
ROOF INSULATION
ROOF SHEATHING
SINGLE PLY ROOF
MEMBRANE
CURB MOUNTED RTU
LEVELING OF CURB
BY CONTRACTOR
EF-2 EF-1
RTU-1
3'-0"
3'
-
0
"
3'
-
0
"
PROVIDE 3" DEEP WATER
TRAP MINIMUM.
2X6 BLOCKING
DUCT DROP
INSULATION
STRIP
PROVIDE MANUFACTURER
REQUIRED CLEARANCE FROM RTU
TO FAN AND A MINIMUM OF 2'-0"
BETWEEN EF-1 & EF-2
APPROX. 53" ABOVE ROOF
SURFACE TO FAN DISCHARGE.
DISCHARGE TO BE SLIGHTLY
ABOVE THE ADJACENT
PARAPET. IN ALL CASES
MAINTAIN 40 INCHES ABOVE
ROOF TO FAN DISCHARGE
MINIMUM AND AT LEAST 18
INCHES CLEAR OF
COMBUSTIBLE MATERIAL.
INSTALLATION OF KITCHEN EXHAUST FANS
WILL PROVIDE 18 INCHES CLEAR OF FAN AND
FAN BASE TO COMBUSTIBLE MATERIALS
INCLUDING ROOF MEMBRANE MATERIAL
ALONG THE BASE OF THE CURB. FAN
DISCHARGE ELEVATION WILL BE AT LEAST 40
INCHES ABOVE THE ADJACENT ROOF.
DISCHARGE WILL BE 60 INCHES CLEAR OF
THE ADJACENT PARAPET IF THE FAN
DISCHARGE IS BELOW THE PARAPET HEIGHT.
THE DISCHARGE SHALL BE TEN FEET FROM
ANY ADJACENT BUILDING.
ALL EQUIPMENT SHALL BE FASTENED AND
CURBS PERMANENTLY AFFIXED. FINAL
INSTALLATION SHALL BE SUITABLE FOR WIND
LOADS AT THE SITE. ALL REQUIREMENTS ARE
TO BE REVIEWED AND APPROVED BY A
LICENSED PROFESSIONAL ENGINEER.
REFER TO STRUCTURAL FRAMING DETAILS
AND/OR STRUCTURAL REVIEW LETTER FOR
ROOF CURB STRUCTURAL FRAMING DETAILS.6'
-
6
"
CO
IN A SHAFT PROVIDE CLEARANCE REDUCTION METHOD WITH A 6"
MINIMUM CLEARANCE.6"
KITCHEN CEILING
18"
22 GAUGE METAL
COMBUSTIBLE MATERIAL
1" NON COMBUSTIBLE SPACER
1" MINERAL WOOL BATT
SCREW
WEATHER PROTECTED OPENING.
NO 90° BENDS IN GREASE DUCT ALLOWED UNLESS RADIUS
ELBOWS WITH ACCESS PANELS ARE PROVIDED WITH
CONSTRUCTION MANAGER APPROVAL.
CONTRACTOR TO PROVIDE AIR
BALANCING IN DUCTWORK FOR ALL
KITCHEN EXHAUST FANS.
CURB AS SUPPLIED
BY FAN MANUFACTURER
LISTED ACCESS
OPENING ROOF
REFER TO 08/M2.0
KITCHEN HOOD DUCTWORK SHALL BE 16 GAUGE CARBON
STEEL OR 18 GAUGE STAINLESS STEEL. DUCTWORK SHALL BE
CONTINUOUSLY EXTERNALLY WELDED LIQUID TIGHT. ALL
PORTIONS OF WELDED DUCTWORK SHALL BE SLOPED BACK
TO HOOD FOR DRAINAGE WITH NO TRAPS. CONTRACTOR
SHALL COORDINATE AT SITE WITH TRADES TO ENSURE THIS
CAN BE DONE.
OPERATION OF KITCHEN HOOD SHALL BE INTERLOCKED WITH
ASSOCIATED EXHAUST FAN, MOTORIZED DAMPERS,
ASSOCIATED UNITS BRINGING IN MAKE UP AIR AND ANY
REMOTE APPLIANCE WHERE FLUE IS DISCHARGING INTO
HOOD. UPON ACTIVATION OF FIRE SUPPRESSION SYSTEM,
MAKE UP AIR SYSTEM AND ALL APPLIANCES WILL SHUT
DOWN AND KITCHEN EXHAUST SYSTEM WILL CONTINUE TO
OPERATE.
ALL GAS PIPING SHALL FOLLOW APPLICABLE GAS CODES AND
BE INSTALLED BY A LICENSED CONTRACTOR FAMILIAR WITH
THESE CODES.
PROVIDE AUTOMATICALLY ELECTRICALLY OPERATED GAS
VALVE SERVING GAS FIRED COOKING EQUIPMENT BEING
SERVED BY AUTOMATIC FIRE EXTINGUISHING SYSTEM.
PROVIDE INTERLOCK SO THAT COOKING EQUIPMENT WILL
SHUT-DOWN ON ACTIVATION OF FIRE SUPPRESSION SYSTEM.
VALVE SHALL BE LABELED, WITH INSTRUCTIONS AND
LOCATED OUTSIDE OF PROTECTED AREA. AN ADDITIONAL
MANUAL SHUT-OFF VALVE SHALL BE ACCESSIBLE AND BE
LOCATED IMMEDIATELY UPSTREAM OF AUTOMATIC VALVE.PROVIDE MAIN GAS VALVE TO
SHUT DOWN COOK LINE.
LOCATE VALVE NEAR COOK
LINE SO EMPLOYEE CAN
MANUALLY SHUT DOWN
WITHOUT HAVING TO USE
LADDER, ETC.
EMERGENCY PULL
STATION SHALL BE
ACCESSIBLY
LOCATED 42" TO 48"
OFF FLOOR AT
POINT OF EXIT
DURING A FIRE. SEE
POWER PLAN FOR
LOCATION.
CLEARANCE AND CLEARANCE REDUCTION METHODS
NFPA 96 1-3.2 CLEARANCE NOTE:
HOODS, GREASE EXTRACTORS, DUCTS, ECOLOGY UNITS,
FANS SHALL HAVE A CLEARANCE OF AT LEAST:
18" TO COMBUSTIBLES
3" TO LIMITED COMBUSTIBLES, 6" IN SHAFT
0" TO NON COMBUSTIBLES, 6" IN SHAFT
WHERE SPACE DOES NOT ALLOW FOR NOTED CLEARANCES
AS IT PERTAINS TO THE TYPE OF CONSTRUCTION, A
CLEARANCE REDUCTION METHOD MAY BE APPLIED.
OPTION 1 : AS ILLUSTRATED BELOW
OPTION 2 : USE LISTED 3M FIRE DUCT WRAP 615+
MANUFACTURER PREFABRICATED UL APPROVED
INSULATED GREASE EXHAUST DUCT IS PERMITTED
IF PROVIDED BY THE HOOD SUPPLIER AS PART OF
A COMPLETE HOOD AND FAN PACKAGED SYSTEM.
COMPLETE ERECTION DOCUMENTS DETAILING THE
REQUIRED INSTALLATION PROCEDURES SHALL BE
PROVIDED FOR THE CODE OFFICIAL AND THE
INSTALLING CONTRACTOR. DUCT SHALL CONFORM
TO ALL NFPA 96 REQUIREMENTS AND UL LISTING.
PROVIDE ACCESSIBLE CLEANOUTS
AT EVERY 90 DEGREE CHANGE IN
DIRECTION AND AT THE TOP OF A
VERTICAL RISER UNDER ROOF.
D
(2) D
D
D
8"
M
I
N
.
3 PIECE PVC DURO-LAST CHILLER STACK KIT
DURO-LAST CAULK
DURO-LAST PREFABRICATED VENT STACK FLASHING
REFRIGERATION LINESROOF DECK
ALL COUNTERFLASHING DRIP SHIELD AND EXPOSED
DUCTWORK SHALL BE 18 GA. GALVANIZED SHEETMETAL
ALL SOLDERED AIR-TIGHT CONSTRUCTION
STAINLESS STEEL BAND POSITIONED 1/4"
FROM THE TOP OF THE STACK FLASHING
INSULATION
MEMBRANE
CB
FE
L
L
WHEN SHOWNTAPS TO TRUNK ONLY
ECCENTRIC
TRANSITION
CONCENTRIC
TRANSITION
RECTANGULAR TO ROUND
RECTANGULAR TO ROUND RECTANGULAR TO RECTANGULAR
ROUND TO ROUND
45°
ROUND DUCT BRANCH DUCT
MAIN DUCT
AIR FLOW
AIR FLOW
RECTANGULAR DUCT
AIR FLOW
45
RECTANGULAR DUCT
CONICAL FITTING. SEAL
AIRTIGHT WITH MASTIC
Ø-MAX.45° DIVERGING,
60° CONVERGING
Ø-MAX.
Ø
Ø
°
NOTE: USE PLAN AS GUIDE
TO FITTING TYPE.
A
D
1-1/2"
NOTE:
FOR DUCT SUPPORT
AND SEISMIC
REQUIREMENTS, REFER
TO SMACNA GUIDELINES
AND LOCAL CODE
REQUIREMENTS.
STRAP
1/4" BOLT
STRAP
METAL BAND SUPPORT
NYLON DRAW BAND (TYP)
SUPPLY AIR
DIFFUSER WITH
ROUND NECK
PROVIDE 1" BLANKET
INSULATION COVERING
AIR DEVICE BACK
FLEX DUCT
WITH 2"
EXTERNAL
INSULATION
MAX. LENGTH
6'-0"
T-BAR TYPE/GYP
SUSPENDED CEILING
RIGID ROUND
INSULATED DUCT JOINT
SCREWED & SEALED
INSULATED SHEETMETAL
SUPPLY DUCT. SEAL PER
SPECIFICATIONS
TIE OFF TO ROOF
STRUCTURE
NOTES:
1. DETAIL IS FOR CONDENSATE DRAIN CONNECTIONS LOCATED ON FAN INLET SIDE ONLY.
2. SLOPE CONDENSATE DRAIN AS MUCH AS POSSIBLE TOWARD DISCHARD POINT BUT NO LESS
THAN 1/4" PER FOOT. PROVIDE CLEANOUTS AT TURNS AND WHERE INDICATED. USE
SCHEDULE 40 PVC PIPE AND FITTINGS WITH PRIMED AND SOLVENT WELDED JOINTS. USE
DWV FITTINGS FOR SIZES 1-1/4" DIAMETER AND LARGER PIPE. SUPPORT PIPING AT FOUR
FOOT INTERVALS MAXIMUM.
3. PIPING ARRANGEMENT SHOWN IS SCHEMATIC. ADJUST AS REQUIRED TO SUIT SITE
CONDITION. REFER TO LOCAL CODE REQUIREMENTS FOR INDIRECT DRAIN REQUIREMENTS.
4. PROVIDE 6" HIGH PIPE VENT OPEN TO ATMOSPHERE IF REQUIRED BY LOCAL CODES.
TYPICAL ROOFTOP AIR
CONDITIONING UNIT
CONDENSATE CONNECTION. TRAP SIZE TO BE
EQUAL TO OR LARGER THAN CONNECTION SIZE BUT
NO LESS THAN 3/4"
PROVIDE MIRO INDUSTRIES MODEL 3-RAH ADJUSTABLE PIPE SUPPORTS & PADS, OR
EQUIVALENT. PROVIDE SUPPORTS TO PREVENT PIPE SAGGING AND ALLOW FOR SLOPE.
UNION CONNECTION2"
1"
ROUTE TO NEAREST SCUPPER
CLEANOUT TEE WITH PLUG (TYP.)
DIMENSION SHALL BE EQUAL TO OR
GREATER THAN FAN INLET PRESSURE IN
INCHES PLUS ONE INCH THEN DIVIDED BY
TWO (MINIMUM DIMENSION IS ONE INCH).
DIMENSION SHALL BE EQUAL TO OR
GREATER THAN FAN INLET PRESSURE IN
INCHES PLUS ONE INCH (MINIMUM
DIMENSION ALLOWED IS TWO INCHES).
ROOF
22 GAUGE GALVANIZED SHEET
METAL PLENUM WITH
EXTERNALLY APPLIED 2" THICK
EXTERNAL DUCT WRAP
PERFORATED SD-2 DIFFUSER
07DUMP BOX DETAIL
NOT TO SCALE
CEILING
INSULATED FLEXIBLE DUCT
WITH BAND FASTENER
ROUND SPIN-IN
DUCT COLLAR
10"
24"
16"FASTEN TO DIFFUSER IN
EIGHT PLACES WITH
SHEETMETAL SCREWS
(TWO ON EACH CORNER
SIDE OF PLENUM BOX)
2"
NOTES:
1. TOP INLETS TO PLENUM BOX ARE NOT ALLOWED.
2. DOVETAIL COLLARS ARE NOT ALLOWED.
3. SEAL COLLAR WITH SEAL CLASS 'A' DUCT SEALANT.
4. DO NOT CRUSH OR MODIFY DUMP BOX SIZE TO FIT OTHER
MECHANICAL EQUIPMENT IN CEILING CAVITY.
SUPPORT TO STUCTURE
WITH SHEETMETAL STRAPS
DROP FROM
HVAC EQUIPMENT
RECTANGULAR
TRUNK DUCT ROUND TRUNK DUCT
MANUAL DAMPER
(TYPICAL)
45° ENTRY
FITTING (TYPICAL)
FLEXIBLE DUCT
NOT TO SCALE
ROOFTOP EQUIPMENT DUCT DROP DETAIL 11
10ROOFTOP UNIT CONDENSATE
5" = 1'-0"06CEILING DIFFUSER DETAIL
NOT TO SCALE
05ROUND DUCT HANGER DETAIL
NOT TO SCALE
02DUCT FITTING DETAILS
NOT TO SCALE
NOT TO SCALE
GOOSENECK WEATHERHOLD ROOF PENETRATION DETAIL 09
04RADIUS ELBOW
NOT TO SCALE 01MECHANICAL EXHAUST DUCT DETAIL
NOT TO SCALE08EXHAUST FAN AND RTU CURB DETAIL
1/4" = 1'-0"
12
/
2
2
/
2
0
1
7
4
:
1
1
:
5
2
P
M
79
6
M
e
r
u
s
C
o
u
r
t
St
.
L
o
u
i
s
,
M
O
6
3
0
2
6
T
6
3
6
.
3
4
9
.
1
6
0
0
F
6
3
6
.
3
4
9
.
1
7
3
0
CE
R
T
I
F
I
C
A
T
E
O
F
A
U
T
H
O
R
I
T
Y
N
O
.
3
8
0
0
8/18/2021
SEAL
DESCRIPTIONDATEREV.
ISSUE DATE: 08/17/2021
PROJECT NUMBER: 21-008
DRAWN BY:
CHECKED BY:
SHEET NAME
SHEET NUMBER
MO
O
D
Y
R
D
&
N
2
N
D
E
RE
X
B
U
R
G
,
I
D
8
3
4
4
0
PROJECT TYPE:
SITE NUMBER:
BUILDING TYPE:
OWNER:
BASE VERSION:
DRAWING RELEASE:
PROJECT YEAR:
ASSET TYPE:
CLASSIFICATION:
UPGRADE CLASSIFICATION:
DESIGN TYPE:
#13487
(2.0) SMART 40+
FREESTANDING
NEW
FRANCHISE
2020
NEW BUILD
2021
(2.0) UM BRITE
SUMMER
NEW
SMART 40+
1 10/20/2021 City Comments
HVAC DETAILS
M2.0
OM
DRC
MECHANICAL SPECIFICATIONS
230500 COMMON WORK RESULTS FOR HVAC
A. PROVIDE MATERIALS AND EQUIPMENT AND LABOR REQUIRED TO INSTALL HEATING, VENTILATING
AND AIR CONDITIONING SYSTEM, COMPLETE AS INDICATED ON DRAWINGS, AS REQUIRED BY CODE
AND AS SPECIFIED HEREIN.
B. WITHOUT RESTRICTING THE GENERALITY OF THE FIRST STATEMENT, THE WORK TO BE
PERFORMED UNDER THIS DIVISION SHALL INCLUDE, BUT IS NOT LIMITED TO, THE FOLLOWING:
1. HVAC WORK AS DESCRIBED IN SECTIONS 230500 THROUGH 233813.
C. ELECTRICAL CONTRACTOR, UNLESS OTHERWISE NOTED, SHALL PROVIDE POWER WIRING FOR
EACH ITEM OF ELECTRICAL EQUIPMENT AND MAKE FINAL CONNECTION TO MOTORS.
D. FINISH PAINTING SHALL BE PERFORMED BY GENERAL CONTRACTOR, EXCEPT AS NOTED
ELSEWHERE. CONTRACTOR SHALL RESTORE TO ORIGINAL CONDITION PAINTING DEFACED BY
CONTRACTOR AFTER ORIGINAL PAINTING.
E. ALL WORK SHALL CONFORM TO CODES, RULES, AND REGULATIONS:
1. NATIONAL ELECTRICAL CODE.
2. STANDARD FOR THE INSTALLATION OF AIR CONDITIONING AND VENTILATING SYSTEMS, NFPA
90A.
3. CODE FOR SAFETY TO LIFE FROM FIRE IN BUILDINGS AND STRUCTURES, NFPA 101.
4. FEDERAL OCCUPATIONAL SAFETY AND HEALTH STANDARDS.
5. STATE MECHANICAL CODE.
6. STATE BUILDING CODE
7. STATE INDUSTRIAL COMMISSION REQUIREMENTS.
8. LOCAL BUILDING CODE REQUIREMENTS.
9. BUILDING INSURING AGENCY REQUIREMENTS.
F. PERMITS REQUIRED BY LAWS, ORDINANCES AND BUILDING CODES HAVING JURISDICTION SHALL
BE OBTAINED AT THE PROPER TIME BY AND AT EXPENSE OF CONTRACTOR.
G. CONTRACTOR SHALL OBTAIN INSPECTIONS REQUIRED BY LAWS, ORDINANCES AND PUBLIC
AUTHORITY HAVING JURISDICTION AND SHALL OBTAIN CERTIFICATES OF SUCH INSPECTIONS AND
SUBMIT SAME TO ARCHITECT AND SHALL PAY FEES, CHARGES, ASSESSMENTS AND OTHER
EXPENSES IN CONNECTION THEREWITH.
H. PIPING AND EQUIPMENT LAYOUT ARE SCHEMATIC. EXACT LOCATIONS ARE DETERMINED BY
STRUCTURAL AND OTHER CONDITIONS. DESIGN OF SYSTEM MAY NOT BE CHANGED. ONLY EXACT
LOCATION OF PIPING AND DUCTS MAY BE REVISED TO SUIT CONSTRUCTION CONDITIONS AND AID
IN COORDINATION WITH WORK OF OTHER CONTRACTORS.
I. MATERIALS AND EQUIPMENT INSTALLED AS PART OF THE WORK SHALL MEET REQUIREMENTS OF
THE CONTRACT DOCUMENTS AND NO MATERIALS OR EQUIPMENT SHALL BE ORDERED UNTIL
REVIEWED BY OWNER. ARCHITECT OF RECORD IS RESPONSIBLE FOR REVIEWING AND APPROVING
HVAC SUBMITTALS. HVAC UNITS SHALL NOT BE CONSIDERED AS ORDERED AND IN PROGRESS
UNTIL SUBMITTALS ARE FORMALLY APPROVED AND RETURNED TO HVAC SUPPLIER.
J. CATALOG DATA FOR EQUIPMENT REVIEWED BY OWNER SHALL NOT SUPERSEDE CONTRACT
DOCUMENTS. REVIEW OF PRODUCTS SHALL NOT RELIEVE CONTRACTOR FROM RESPONSIBILITY
FOR DEVIATIONS FROM DRAWINGS OR SPECIFICATIONS, PROVIDING PROPER CLEARANCE,
FABRICATION PROCESS AND COORDINATION WITH OTHER TRADES.
K. WHEN SUBMITTED FOR REVIEW, SHOP DRAWINGS SHALL BEAR CONTRACTOR'S CERTIFICATION
THAT CONTRACTOR HAS REVIEWED, CHECKED AND APPROVED SHOP DRAWINGS, THAT THEY ARE
IN HARMONY WITH REQUIREMENTS OF THE PROJECT AND WITH THE PROVISIONS OF CONTRACT
DOCUMENTS AND THAT CONTRACTOR HAS VERIFIED ALL FIELD MEASUREMENTS AND
CONSTRUCTION CRITERIA, MATERIALS, CATALOG NUMBERS AND SIMILAR DATA. CONTRACTOR
SHALL ALSO CERTIFY THAT WORK REPRESENTED BY THE SHOP DRAWINGS IS RECOMMENDED BY
CONTRACTOR AND THE CONTRACTOR'S GUARANTEE WILL FULLY APPLY.
L. CONTRACTOR SHALL VERIFY LOCATION OF UTILITIES AND NOTE CONDITIONS WHICH WOULD
AFFECT THE WORK. DISCREPANCIES SHALL BE REPORTED PRIOR TO BID AWARD.
M. PROVIDE INSTRUCTION TO OWNER'S OPERATING PERSONNEL AS NECESSARY, SHOWING
LOCATIONS AND PROPER OPERATION OF MAJOR ITEMS OF EQUIPMENT AND SYSTEM
COMPONENTS AND REFERRING TO OPERATING INSTRUCTION MANUAL DESCRIBED BELOW AS A
GUIDE.
N. COMPILE WRITTEN MANUAL OF OPERATING INSTRUCTIONS INCLUDING COPIES OF SHOP
DRAWINGS AND LISTING OF EQUIPMENT SUPPLIERS. ASSEMBLE IN 8-1/2" X 11" HARD BACKED
INDEXED BINDER. MATERIAL SHALL BE AS FOLLOWS:
1. TITLE PAGE: TITLE OF JOB, OWNER, ADDRESS, DATE OF SUBMISSION, CONTRACTOR AND
ENGINEER.
2. INDEX.
3. LIST OF MAJOR EQUIPMENT USED IN PROJECT ACCOMPANIED BY CONTRACTOR PURCHASE
ORDER NUMBERS AND SUPPLIERS NAMES AND ADDRESSES.
4. ONE COPY OF EACH SHOP DRAWING GROUPED BY TYPES OF EQUIPMENT, I.E., ROOFTOP UNITS,
FANS, ETC.
5. SECTION FOR EACH SYSTEM INCLUDING:
a. BRIEF DESCRIPTION OF SYSTEM OPERATION WITH LOCATION OF MAJOR COMPONENTS.
b. HVAC SYSTEM MAINTENANCE AND CALIBRATION INFORMATION, INCLUDING WIRING
DIAGRAMS AND SCHEMATICS.
O. SUBMIT A COMPLETED COPY TITLED "HVAC OPERATING INSTRUCTION MANUAL" ON BINDING EDGE
OF BINDER TO ARCHITECT FOR APPROVAL. AFTER ARCHITECT'S REVIEW AND ANY CORRECTIONS
REQUIRED ARE COMPLETED, SUBMIT A COPY OF THE MANUAL TO OWNER.
P. WITHIN 90 DAYS AFTER DATE OF SYSTEM ACCEPTANCE, RECORD DRAWINGS OF ACTUAL
INSTALLATION SHALL BE PROVIDED TO BUILDING OWNER. RECORD DRAWINGS SHALL INCLUDE AT
A MINIMUM LOCATION AND PERFORMANCE DATA ON EACH PIECE OF EQUIPMENT, GENERAL
CONFIGURATION OF DUCT DISTRIBUTION SYSTEM INCLUDING SIZES, AND AIR DESIGN FLOW
RATES.
Q. CONTRACTOR IS TO BECOME INFORMED OF EXACT DIMENSIONS OF FINISHED WORK WHERE
PIPES, DUCTS AND EQUIPMENT ARE TO BE PLACED AND WILL ARRANGE THE WORK ACCORDINGLY,
ASSUMING ALL RESPONSIBILITY FOR PROPER LOCATION AND COORDINATION OF THE WORK.
R. IN ERECTION OF DUCTWORK, SPECIAL CARE SHALL BE USED PROVIDING SUPPORT.
S. DUCTWORK SHALL BE PLACED SO AS TO AVOID INTERFERENCES WITH PLUMBING PIPES, ELECTRIC
CONDUITS OR PIPES OF OTHER CONTRACTORS.
T. DUCTWORK SHALL BE PROVIDED WITH SUFFICIENT DISTANCE FROM WALLS, PIPES, AND OTHER
OBSTACLES TO PERMIT APPLICATION OF FULL THICKNESS OF INSULATION SPECIFIED.
230593 TESTING, ADJUSTING, & BALANCING HVAC
A. CONTRACTOR SHALL COMPLETE INSTALLATION OF HOOD SYSTEM, ROOFTOP EQUIPMENT, AND
CONTROL SYSTEM IN ACCORDANCE WITH DRAWINGS PRIOR TO PERFORMING TAB. CONTRACTOR
SHALL PROGRAM THERMOSTATS IN ACCORDANCE WITH REQUIREMENTS LISTED AND FOLLOWING
STATUS AS INDICATED IN TAB CONFIRMATION FORM. CONTRACTOR SHALL UTILIZE PERSONNEL
AND SUBCONTRACTORS THAT ARE FULLY TRAINED AND CERTIFIED BY MANUFACTURER FOR
EQUIPMENT BEING INSTALLED.
B. CONTRACTOR SHALL COMPLETE CALIBRATIONS AND TESTS OUTLINED IN WENDY'S TEST
PROTOCOLS AND DOCUMENT RESULTS ON DESIGNATED FORMS. COPIES OF FORMS ARE
AVAILABLE ONLINE:
HTTP://WWW.IGNITORLABS.COM/WRVT-DOC-HOME/
C. CONTRACTORS WORKING ON PROJECT ARE REQUIRED TO HAVE COMPLETED WENDY'S
RESTAURANT VENTILATION COURSE FROM IGNITOR LABS WITHIN PAST 12 MONTHS:
HTTPS://PORTAL.IGNITORLABS.COM
A COMPLETION CERTIFICATE FROM IGNITOR LABS WITH A SCORE OF 80% OR HIGHER IS REQUIRED.
CONTRACTOR IS RESPONSIBLE FOR THE NOMINAL COSTS REQUIRED FOR PROJECT PERSONNEL TO
TAKE THE COURSE.
D. PROCEDURES/CHECKLISTS:
CHECKLIST PROCEDURE TROUBLESHOOTING
BREAKER PANELS
WESCO RQC-2017-013 RQC-2017-014 RQC-2017-015
CPI RQC-2017-043 RQC-2017-044 RQC-2017-045
ROOFTOP UNITS
AAON RQC-2020-075 RQC-2020-076 RQC-2020-077
TRANE RQC-2020-025 RQC-2020-026 RQC-2020-027
YORK/CAPTIVE-AIR RQC-2020-105 RQC-2020-106 RQC-2020-107
HOOD SYSTEM
HALTON (CAPTUREJET) RQC-2020-052 RQC-2020-053
HALTON (STANDARD FILTER HOOD) RQC-2020-054 RQC-2020-055
CAPTIVE-AIRE RQC-2020-062 RQC-2020-063
E. QUALIFICATIONS:
1. BALANCER SHALL BE A MEMBER IN GOOD STANDING AND CERTIFIED WITH THE ASSOCIATED AIR
BALANCE COUNCIL (AABC), OR THE NATIONAL ENVIRONMENTAL BALANCING BUREAU (NEBB).
BALANCER SHALL BE TOTALLY INDEPENDENT, HAVING NO AFFILIATION WITH ANY PROJECT
CONTRACTOR, DESIGN PROFESSIONAL, EQUIPMENT MANUFACTURER OR SUPPLIER OF HVAC
RELATED EQUIPMENT. BALANCER SHALL HAVE BEEN REGULARLY ENGAGED IN TAB OF HEATING,
VENTILATING, AND AIR CONDITIONING SYSTEMS FOR RESTAURANTS. BALANCER SHALL
PROVIDE PROOF THAT PERSONNEL PERFORMING WORK HAVE SUCCESSFULLY COMPLETED AT
LEAST FIVE RESTAURANT PROJECTS OF SIMILAR SIZE AND SCOPE. A COMPLETE LIST OF
REFERENCE PROJECTS, INCLUDING NAME AND PHONE NUMBER OF CONFIRMING CONTACTS,
SHALL BE SUBMITTED WITH QUOTE, IF REQUESTED.
2. INSTRUMENTS USED FOR TAB SHALL BE ACCURATELY CALIBRATED WITHIN TWELVE (12)
MONTHS OF BALANCING AND MAINTAINED IN GOOD WORKING ORDER. PROVIDE RECORDS OF
LAST CALIBRATION (AS REQUESTED) AND INCLUDE THIS SUMMARY IN THE FINAL TAB REPORT.
ENGINEER OF RECORD, OR THEIR REPRESENTATIVE, MAY OBSERVE TAB ACTIVITIES.
3. UNLESS OTHERWISE NOTED RESTAURATEUR SHALL PROCURE SERVICES OF AND CONTRACT
DIRECTLY WITH AN INDEPENDENT TAB CONTRACTOR (BALANCER) MEETING QUALIFICATIONS OF
THIS SECTION. BALANCER SHALL TEST, BALANCE, AND ADJUST ALL AIR MOVING EQUIPMENT
(RTUS AND FANS), AIR DISTRIBUTION DUCTS AND AIR DEVICES, EXHAUST SYSTEMS, AND
TEMPERATURE CONTROL SYSTEMS.
4. IF CONTRACTOR IS REQUIRED TO PROCURE TAB SERVICES DIRECTLY, CONTRACTOR SHALL
PROVIDE QUALIFICATIONS OF BALANCER TO RESTAURATEUR OR THEIR REPRESENTATIVE FOR
APPROVAL. CONTRACTOR SHALL CONTRACT BALANCER AS SOON AS POSSIBLE AFTER
CONSTRUCTION START TO COORDINATE THEIR WORK WITH OTHER TRADES, WHILE MEETING
COMPLETION DATE. CONTRACTOR SHALL PREPARE A CRITICAL PATH SCHEDULE,
COORDINATED WITH SUBCONTRACTORS, TO ACCOMPLISH ALL TASKS REQUIRED OF BALANCER.
5. CONTRACTORS SHALL COOPERATE AND ASSIST BALANCER AS REQUIRED. BALANCER SHALL
INSPECT MECHANICAL, EXHAUST, AND CONTROL SYSTEM WORK. ANY DEVIATIONS FROM PLANS
AND SPECIFICATIONS THAT MAY AFFECT PERFORMANCE OF THE SYSTEM SHALL BE REPORTED
IN WRITING TO CONTRACTOR, ARCHITECT OF RECORD, ENGINEER AND RESTAURATEUR.
F. CONTRACTOR SHALL COMPLETE THE FOLLOWING PRIOR TO TAB: PERMANENT POWER SHALL BE
PROVIDED, ROOFTOP UNIT FULL INSTALLED AND STARTED, HOOD SYSTEMS AND FANS STARTED,
COMPLETE CONTROLS OPERATIONAL AND PROGRAMMED, DUCTWORK, DIFFUSER AND CEILING
INSTALLATION COMPLETED. ADDITIONAL TAB COSTS ARE THE CONTRACTOR'S RESPONSIBILITY IF
REQUIRED ITEMS ARE NOT COMPLETE AT START OF TAB PROCEDURES.
G. DESIGN BALANCE DEVIATION TOLERANCES:
1. KITCHEN HOODS ARE UL LISTED AND SHALL BE BALANCED FROM 100% TO 105% OF DESIGN
AIRFLOW. DO NOT SET EXHAUST RATE BELOW THAT SCHEDULED. INCREASE RTU AIRFLOW AS
NEEDED TO ACHIEVE POSITIVE PRESSURE IN THE RESTAURANT.
2. TOTAL OF ALL AIR DISTRIBUTION DEVICES ON SAME ROOFTOP UNIT DUCT SYSTEM SHALL BE
BALANCED TO 100% TO 105% OF DESIGN.
3. ROOFTOP UNITS SHALL PROVIDE OUTDOOR AIR CFM BETWEEN 100% TO 105% OF DESIGN FOR
ALL SUPPLY FAN SPEEDS DURING REGULAR HOURS AND SHALL BE SET TO TRACK AIR VOLUME
WITH THE SUPPLY FAN FOR THE FAN SPEED PROVIDED BY THE UNITS.
4. ECONOMIZERS SHALL PROVIDE REQUIRED OUTDOOR AIR WHEN CLOSED FOR BUSINESS
(MINIMUM ONLY).
5. OVERALL SYSTEM SHALL BE BALANCED TO POSITIVE CFM AS SHOWN ON THE VENTILATION
SCHEDULE WITH SUPPLY AND EXHAUST FANS IN OPERATION.
6. CONTACT RTU MANUFACTURER TO RESOLVE AIRFLOW DELIVERY IF ROOFTOP UNIT AIRFLOWS
ARE BELOW DESIGN. THIS INCLUDES VERIFICATION OF DUCTWORK STATIC PRESSURE,
ADJUSTMENT OF FAN RPM, REPLACEMENT OF DRIVES, ETC. RESTAURANT SHALL BE LEFT IN A
POSITIVE AIR PRESSURE STATE.
H. PLAN REVIEW: PROVIDE WRITTEN TESTING AND BALANCING PLAN REVIEW WITHIN FIVE (5)
BUSINESS DAYS UPON RECEIPT OF CONTRACT. PLAN REVIEW SHALL INCLUDE
RECOMMENDATIONS TO IMPROVE TESTING AND BALANCING. TRANSMIT THESE COMMENTS
DIRECTLY TO CONTRACTOR. REVIEW WENDY'S RESTAURANT VENTILATION EQUIPMENT PRE-START
AND START-UP FORMS.
I. EQUIPMENT SUBMITTAL DATA: CONTRACTOR SHALL PROVIDE RESTAURANT EQUIPMENT
SUBMITTAL DATA TO BALANCER. COMPLETED EQUIPMENT STARTUP AND CALIBRATION FORMS
SHALL BE PROVIDED TO BALANCER PRIOR TO PERFORMING TAB.
J. UPDATED DESIGN REQUIREMENTS: IF ANY, SHALL BE PROVIDED TO BALANCER PRIOR TO TAB.
DESIGN REQUIREMENT CHANGES SHALL INCLUDE DATE OF THE CHANGE AND REFERENCES TO
THE CONTRACT DOCUMENTS (ADDENDA, CHANGE ORDER, OR CONSTRUCTION CHANGE
DIRECTIVE), WHICH DIRECTED THE CHANGE. CHANGES MADE WITHOUT RESTAURATEUR WRITTEN
APPROVAL ARE INVALID.
K. BALANCER TEST AND BALANCE REPORT:
1. PERFORM TAB WORK ASSOCIATED WITH THE RESTAURANT VENTILATION SYSTEM PER DESIGN
DOCUMENTS. SUBMIT AN ELECTRONIC PDF COPY OF TABULATED REPORTS IN NEATLY
ORGANIZED TYPED FORMS (WITH NUMBERED PAGES) WITH AABC OR NEBB FULLY COMPLETED,
STAMPED AND SEALED REPORTS. REPORT SHALL BE PROVIDED WITHIN SEVEN (7) DAYS OF
COMPLETION OF TESTS TO ARCHITECT OF RECORD, ENGINEER, CONTRACTOR AND
RESTAURATEUR. REPORT SHALL INCLUDE START-UP CHECKLIST FORMS AND REPORTS
PROVIDED TO BALANCER BY CONTRACTOR, EQUIPMENT TEST DATA AND DRAWINGS TO
COINCIDE WITH TEST REPORT. IN ADDITION, REPORTS SHALL INCORPORATE:
2. A SUMMARY THAT SHALL INCLUDE A GENERAL DESCRIPTION OF PROJECT (BUILDING TYPE,
SYSTEM TYPE, AND EQUIPMENT DESCRIPTION).
3. A DESCRIPTIVE LIST OF ALL EQUIPMENT AND TEST RESULTS THAT DO NOT MEET PLANS AND
SPECIFICATIONS (INCLUDE PHOTOGRAPHS).
4. COPIES OF REDUCED PLAN DRAWINGS THAT UNIQUELY IDENTIFY AND CROSS REFERENCE AIR
DEVICES AND HVAC EQUIPMENT.
5. PROVIDE BUILDING PRESSURE TABLES THAT INDICATE DESIGN AND ACTUAL RESULTS.
6. REPORTS THAT ARCHITECT AND/OR ENGINEER DETERMINES IS INACCURATE, OR INCOMPLETE,
SHALL BE RETURNED FOR CORRECTION, COMPLETION, OR RE-TESTING AT BALANCERS COST.
REVISED REPORTS SHALL BE SUBMITTED IN THEIR ENTIRETY. EACH REVISION SHALL BE
HIGHLIGHTED AND SHALL INDICATE REVISION DATE. COVER PAGE SHALL INDICATE DATE OF
FIRST EDITION AND REVISION DATE.
L. TEST & BALANCE CONFIRMATION FORM: BALANCER SHALL COMPLETE A WENDY'S TEST & BALANCE
CONFIRMATION FORM WHILE PERFORMING SYSTEM TESTING. IT SHALL BE SIGNED OFF WHEN TAB
IS COMPLETE AND INCLUDED AT THE END OF THE TEST AND BALANCE REPORT. A DIGITAL VERSION
OF THIS FORM CAN BE FOUND UNDER TEST AND BALANCE REPORTS AT:
HTTP://WWW.IGNITORLABS.COM/WRVT-DOC-HOME/
M. CONTRACTOR'S RESPONSIBILITIES FOR TAB:
1. CONTRACTOR SHALL BE COMPLETELY FAMILIAR WITH ALL PROVISIONS AND RESPONSIBILITIES
OF BALANCER AND SHALL PROVIDE COOPERATION AND SUPPORT REQUIRED.
2. CONTRACTOR SHALL CORRECT OR REPAIR DEFICIENCIES NOTED BY BALANCER IMMEDIATELY.
IF DEFICIENCIES ARE NOT CORRECTED WHILE BALANCER IS ON SITE, AND DEFICIENCIES
PREVENT COMPLETION OF TAB WORK, CONTRACTOR SHALL ASSUME COSTS FOR EXTENDING
TAB, OR FOR FOLLOW UP TAB VISITS.
3. CONTRACTOR SHALL PROVIDE DOCUMENTATION OF CORRECTION OF ANY OPEN ISSUES PRIOR
TO SUBMISSION OF FINAL REPORT. SHOULD ANY OPEN HVAC SYSTEM ITEMS BE INCAPABLE OF
CORRECTION WITHIN SEVEN DAY PERIOD FOR THE FINAL BALANCING REPORT, CONTRACTOR
SHALL INFORM BALANCER AND OWNER IMMEDIATELY AND CONTRACTOR SHALL BE
RESPONSIBLE FOR ALL COSTS, DELAYS, AND RESCHEDULING REQUIRED.
4. CONTRACTOR IS RESPONSIBLE FOR CORRECTION OF IDENTIFIED ITEMS AND FOR SUBSEQUENT
TESTS IN EVENT OF THE FOLLOWING:
a. NO PERMANENT POWER FOR THE RESTAURANT.
b. DIFFUSERS NOT INSTALLED FOR TEST.
c. CEILING TILES NOT INSTALLED.
d. PASSWORD FOR RTU THERMOSTATS NOT PROVIDED.
e. INOPERABLE EQUIPMENT.
f. THERMOSTATS NOT PROGRAMMED.
5. ADDITIONAL RESPONSIBILITIES INCLUDE; PROVIDE REQUIRED SHOP DRAWINGS AND
EQUIPMENT DATA INCLUDING ANY APPROVALS OF DESIGN MODIFICATIONS, PROVIDE SAFE AND
CLEAR ACCESS TO ALL HVAC SYSTEMS AS NEEDED TO PERFORM TAB WORK (LADDERS, LIFTS,
ROOF ACCESS, ACCESS PANELS AND THE LIKE), PROVIDE TEST OPENINGS AS REQUIRED FOR
TESTING AND BALANCING HVAC SYSTEMS, PROVIDE UPDATED JOB SCHEDULE AND TIMELY
NOTICE PRIOR TO SCHEDULED EVENTS. MAKE TESTS AND CALIBRATION TO ESTABLISH
ADEQUACY, QUALITY, SAFETY, COMPLETED STATUS, AND SATISFACTORY OPERATION OF HVAC
SYSTEMS AND COMPONENTS.
6. DURING TAB PERIOD, OPERATE HVAC EQUIPMENT AS NECESSARY TO PERMIT SYSTEMS TO BE
TESTED AND BALANCED AS FULLY OPERATING FUNCTIONAL SYSTEMS. WORK HARMONIOUSLY
WITH BALANCER TO EXPEDITE THE WORK. REMOVE AND REPLACE CEILINGS AS NECESSARY TO
PERMIT TAB OPERATIONS. REMOVE AND REPLACE EQUIPMENT, LIGHTS, OR OTHER ITEMS
WHICH OBSTRUCT TESTING AND BALANCING OPERATIONS (WHERE EQUIPMENT, LIGHTS, OR
OTHER ITEMS INTERFERE WITH FUTURE ADJUSTMENTS OF HVAC SYSTEM. SUCH EQUIPMENT,
LIGHTS, OR OTHER ITEMS SHALL BE RELOCATED BY CONTRACTOR AS DIRECTED BY ENGINEER
OF RECORD.
7. REPLACE BELTS AND DRIVES AS REQUIRED FOR PROPER BALANCING - DRIVES SHALL BE
ADJUSTED AND ALIGNED BY CONTRACTOR TO PREVENT ABNORMAL BELT WEAR AND
VIBRATION. ADJUST FAN SPEED AS REQUIRED NOT TO EXCEED MOTOR CAPACITY.
CONTRACTOR SHALL ADJUST DAMPERS FOR THE BALANCER DURING TAB WORK. IDENTIFY
CONCEALED DAMPER LOCATIONS WITH ORANGE TAPE. MANUALLY OPEN AND TEST DAMPERS
FOR SMOOTH VIBRATION-FREE OPERATION AND TIGHTEN PRIOR TO COMMENCEMENT OF TAB
WORK. VERIFY THAT ALL CONTROLS ARE INSTALLED AND OPERATING AS REQUIRED IN BOTH
STORE OPEN AND CLOSED MODES. BEFORE REQUESTING FINAL TESTING AND BALANCING,
SUBMIT SIGNED STATEMENT THAT HVAC SYSTEMS ARE INSTALLED, ADJUSTED, SERVICED,
OPERATING SATISFACTORILY, AND ARE READY FOR USE.
N. SYSTEM READY NOTICE: ALLOW ADEQUATE TIME TO PERFORM TESTING AND BALANCING WORK.
TAB IS REQUIRED TO BE PERFORMED PRIOR TO RESTAURANT OPENING. NOTIFY BALANCER UPON
COMMENCEMENT OF WORK RELATED TO HVAC SYSTEM AND COORDINATE PROPER TIME FOR
NOTICE TO SCHEDULE TRAVEL AND PROVIDE THE DURATION REQUIRED FOR TEST AND BALANCING
AND FOR ANY POSSIBLE CORRECTIONS.
O. BALANCER RESPONSIBILITIES:
1. RECORD DATA REQUIRED BY AABC OR NEBB FORMS. TEST AND ADJUST SYSTEMS FOR DESIGN
CFM OF SUPPLY, OUTSIDE AIR (IN MULTIPLE FAN SPEEDS), AND EXHAUST AIR. KITCHEN
APPLIANCES SHOULD BE OPERATIONAL WHILE MAKING ADJUSTMENTS. HOOD SIDE SKIRTS
SHALL BE IN PLACE ON THE CORRECT ENDS OF HOODS (FRY HOOD DUMP SKIRT HAS A CUT
OUT). TEST AND RECORD SYSTEM STATIC PRESSURE PROFILES. ADJUST SUPPLY AND RETURN
DUCTS TO DESIGN AIRFLOW. TEST AND ADJUST FANS. ADJUST ALL DIFFUSERS, GRILLES, AND
REGISTERS TO MINIMIZE DRAFTS. PROVIDE BUILDING DIFFERENTIAL PRESSURE (INSIDE TO
OUTSIDE) AT ALL OPERATIONAL CONDITIONS AND INCLUDE IN THE FINAL REPORT.
2. PROVIDE TABLE IN THE REPORT THAT ITEMIZES ALL SUPPLY AND EXHAUST AIR CFM (SPECIFIED
AND ACTUAL) TO SHOW THAT BUILDING SHOULD BE UNDER POSITIVE PRESSURE. SIZE, Ak
CATALOG FACTORS OF DIFFUSERS, GRILLES, REGISTERS, AND ALL TESTED EQUIPMENT SHALL
BE IDENTIFIED AND LISTED. READINGS AND TEST OF DIFFUSERS, GRILLES, AND REGISTERS
SHALL INCLUDE REQUIRED VELOCITY (FPM), REQUIRED CFM, AND RESULTANT CFM. WHEN
DIRECT CFM MEASURING INSTRUMENTS ARE USED, VELOCITIES ARE NOT REQUIRED.
3. BALANCER SHALL COMPLETE A WENDY'S TEST & BALANCE CONFIRMATION FORM WHILE
PERFORMING SYSTEM TESTING. FORM SHALL BE SIGNED OFF WHEN TAB IS COMPLETE AND
INCLUDED AT THE END OF TAB REPORT.
230700 HVAC INSULATION
A. DUCT INSULATION AND APPURTENANCES SHALL HAVE FLAME SPREAD RATING NOT EXCEEDING
TWENTY-FIVE (25) AND SMOKE DEVELOPED RATING NOT EXCEEDING FIFTY (50). DUCT INSULATION
SHALL HAVE AN INSTALLED R-VALUE OF 6.
B. CONCEALED SUPPLY DUCTWORK SHALL HAVE FLEXIBLE FIBERGLASS DUCT WRAP LAMINATED TO
FOIL REINFORCED KRAFT VAPOR BARRIER FACING WITH 2" STAPLING FLANGE OF SUFFICIENT
DENSITY AND THICKNESS TO MEET LOCAL CODE REQUIREMENTS. ONLY COMMERCIAL GRADE
INSULATION PRODUCTS MAY BE USED.
C. INSULATION SHALL NOT BE APPLIED UNTIL CONSTRUCTION HAS PROGRESSED SUFFICIENTLY TO
ENSURE AGAINST PHYSICAL OR MOISTURE DAMAGE TO INSULATION. INSULATION DAMAGED
THROUGH FAILURE TO OBSERVE THIS DIRECTIVE SHALL BE REPLACED AT THIS CONTRACTOR'S
EXPENSE.
D. HANGER RODS SHALL BE PERPENDICULAR TO DUCTWORK BEFORE INSULATION IS INSTALLED.
E. INSTALL INSULATION ACCORDING TO MANUFACTURER'S RECOMMENDATIONS.
F. INSULATION SHALL BE APPLIED OVER FLANGES, JOINTS AND SEAMS IN PIPING AND DUCTWORK.
G. JOINTS AND SEAMS IN INSULATION SHALL BE PROPERLY SEALED TO MAINTAIN VAPOR BARRIER.
H. INSULATION SHALL BE OWENS-CORNING. EQUAL PRODUCT BY ARMSTRONG, CERTAINTEED,
SCHULLER OR KNAUF MAY BE PROVIDED AT CONTRACTOR'S OPTION.
230800 COMMISSIONING OF HVAC
A. THIS CONTRACTOR SHALL COORDINATE COMMISSIONING OF HVAC SYSTEMS AND SHALL ASSIST
OWNERS TAB CONTRACTOR TO COMPLETION. CONTRACTOR IS RESPONSIBLE FOR CORRECTING
DEFICIENCIES NOTED IN THE TAB REPORT.
C. CONTRACTOR SHALL PROVIDE DOCUMENTATION OF TESTING AND COMMISSIONING TO BE
INCLUDED IN OPERATING INSTRUCTIONS MANUAL (SEE GENERAL REQUIREMENTS).
DOCUMENTATION SHALL INCLUDE:
1. CONSTRUCTION AND SYSTEM CHECKLISTS.
2. CERTIFICATE OF READINESS.
3. INTERIM AND FINAL TEST AND INSPECTION REPORTS AND CERTIFICATES.
4. APPROVED SUBMITTALS.
5. CERTIFICATE OF COMPLETION.
6. AS-BUILT DOCUMENTATION.
233133 METAL DUCTS
A. THIS SECTION INCLUDES SPECIFICATIONS FOR DUCTWORK EXCEPT 'GREASE DUCT' (EXHAUST
DUCT CONNECTED TO TYPE I HOODS WHERE GREASE LADEN VAPORS MAY BE PRESENT). REFER
TO PLANS AND DETAILS FOR INFORMATION ON 'GREASE DUCT'.
B. CONTRACTOR SHALL PROVIDE COMPLETE DUCT SYSTEM CONSISTING OF DUCTWORK, PLENUMS,
FITTINGS AND CONNECTORS OF SIZE AND LOCATION AS INDICATED ON DRAWINGS.
C. ALL PORTIONS OF DUCT SYSTEM SHALL BE DESIGNED, FABRICATED AND INSTALLED PER THE
FOLLOWING REQUIREMENTS:
1. LATEST EDITION OF SMACNA “HVAC DUCT CONSTRUCTION STANDARDS - METAL AND FLEXIBLE”.
2. RIGID GALVANIZED SHEET METAL OF THICKNESS AND WITH STIFFENERS AS INDICATED IN
SMACNA PER 2” WATER COLUMN CHART.
3. AIR VELOCITIES NO MORE THAN 2000 FPM AND STATIC PRESSURE IN DUCT OF 2” OR LESS.
4. SEALING PER SMACNA 'CLASS B' OR AS REQUIRED TO MEET AIR BALANCE.
5. CROSS-BREAKING, STIFFENING, BRACES, TOES, ANGLES AND OTHER BRACING AND SUPPORT
REQUIRED TO MAINTAIN DUCT CONFORMITY (TRUE TO SHAPE, PREVENT BUCKLING OR
CAVITATION).
6. ALL VERTICAL DUCTS SHALL BE ABLE TO CARRY AN ADDITIONAL 100 LBS. SUSPENDED LOAD
FROM HANGERS WITHOUT BUCKLING.
7. SEAMS OF ALL DUCTS AND JOINTS SHALL BE HAMMERED TO A SMOOTH SURFACE ON THE
INSIDE.
D. FLEXIBLE CONNECTIONS SHALL BE INSTALLED AT ROOFTOP UNIT SUPPLY AND RETURN AIR
CONNECTIONS. CONNECTIONS SHALL BE AT LEAST 6" LONG, MADE OF NFPA 90A APPROVED
FLAMEPROOF FABRIC.
E. INSTALL HANGERS AND SUPPORTS WITHIN 24 INCHES OF EACH ELBOW AND WITHIN 48 INCHES OF
EVERY BRANCH CONNECTION. HANGERS EXPOSED TO VEIW SHALL BE THREADED ROD AND ANGLE
OR CHANNEL SUPPORTS.
F. ROUND SHEET METAL DUCT: PROVIDE SPIRAL SEAM (ALL SIZES) OR SNAP LOCK (DUCT
CONCEALED ABOVE CEILINGS SIZES UP TO 10") GALVANIZED STEEL COMPLYING WITH SMACNA
STANDARDS. SPIRAL SEAM DUCTWORK SHALL HAVE SMACNA SEAM TYPE RL-1. ROUND EXPOSED
DUCTWORK SHALL BE SPIRAL SEAM (ALL SIZES).
G. EXPOSED DUCTWORK: EXPOSED DUCTWORK SHALL BE CLEANED OF DEBRIS AND OIL, THEN WIPED
DOWN WITH VINEGAR OR OTHER SURFACE PREPARING CHEMICAL TO PREPARE DUCT FOR PAINT.
H. PROVIDE VOLUME CONTROLLER AND EXTRACTOR AT BRANCH TAKEOFFS IN SUPPLY AND RETURN
AND AT OTHER LOCATIONS IN SUPPLY AND RETURN MAIN DUCTS AS REQUIRED TO PROPERLY
BALANCE SYSTEMS. DAMPER SHALL BE AS SPECIFIED IN SECTION 233300.
I. PROVIDE TURNING VANES IN ELBOWS OF RECTANGULAR SUPPLY DUCTS. BLADES SHALL BE
HOLLOW-FORMED DOUBLE THICKNESS VANES.
J. PROVIDE SUPPLY, RETURN, AND EXHAUST REGISTERS, GRILLES AND DIFFUSERS AS INDICATED ON
DRAWINGS AND/OR SCHEDULES. VERIFY AIR DEVICE REQUIREMENTS WITH GENERAL
CONTRACTOR PRIOR TO ORDERING.
K. PROVIDE FLEXIBLE SUPPLY AIR DUCTWORK UL 181, CLASS 1, TWO-PLY VINYL FILM SUPPORTED BY
HELICALLY WOUND SPRING-STEEL WIRE, R-6 FIBERGLASS BLANKET INSULATION WITH METALIZED
FILM VAPOR BARRIER OUTER JACKET IN LENGTHS THAT DO NOT EXCEED SIX FEET, AT AIR DEVICE
CONNECTIONS (GRILLES, REGISTERS AND DIFFUSERS).
233300 DAMPERS
A. CONTRACTOR SHALL PROVIDE RECTANGULAR AND ROUND GALVANIZED STEEL MANUAL AND/OR
MOTORIZED VOLUME CONTROL DAMPERS THAT SHALL BE:
1. NO MORE THAN 6" IN ONE DIMENSION (LARGER DAMPERS SHALL BE OPPOSED-BLADE WITH
EACH BLADE BEING NO MORE THAN 6”),
2. MINIMUM OF 16 GAUGE AND AT LEAST 2 GAUGES HEAVIER THAN DUCT INSTALLED IN,
3. CHANNEL FRAME WITH BRACED CORNERS, CONCEALED LINKAGE, TEFLON FILLED BEARINGS,
BLADE STOPS
4. REPLACEABLE BUTYL RUBBER SEALS INSTALLED ALONG TOP, BOTTOM AND SIDES OF FRAME
AS WELL AS ALONG ALL SIDES OF EACH BLADE
5. 6" LONG CONTROL SHAFT WITH INSULATION STAND-OFF,
6. LOCKING QUADRANT MANUAL HANDLES OR MOTORIZED OPERATORS COMPATIBLE WITH
CONTROL SYSTEM,
7. OPERATE FROM FULL OPEN TO FULL CLOSED.
B. PROVIDE ACCESS AND PROPER CLEARANCES AS REQUIRED TO OPERATE DAMPERS.
C. CHECK DAMPERS FOR PROPER OPERATION BEFORE AND AFTER INSTALLATION.
D. INSTALL BALANCE DAMPERS WHERE INDICATED ON DRAWINGS AND ELSEWHERE AS NECESSARY
TO OBTAIN PROPER SYSTEM BALANCE.
233418 ROOF EXHAUST FAN
A. ROOF MOUNTED UP BLAST EXHAUST FAN SHALL BE CENTRIFUGAL DIRECT DRIVE TYPE. FAN SHALL
BE CONSTRUCTED OF SPUN ALUMINUM WITH STRUCTURAL ELEMENTS OF MINIMUM 16 GAUGE
MARINE ALLOY ALUMINUM.
B. INTEGRAL MOTOR SHALL BE HEAVY DUTY TYPE WITH PERMANENTLY LUBRICATED SEALED
BEARINGS ENCLOSED IN WEATHER-TIGHT COMPARTMENT AND SEPARATED FROM THE EXHAUST
AIR STREAM.
C. THE WHEEL SHALL BE CENTRIFUGAL BACKWARD INCLINED TYPE WITH COMPLETELY ALUMINUM
CONSTRUCTION WITH CONE INLET AND DYNAMICALLY BALANCED TO MINIMIZE VIBRATION.
D. FANS SHALL BEAR THE AMCA CERTIFIED RATINGS SEAL FOR SOUND AND AIR PERFORMANCE AND
SHALL BE UL LISTED AND CSA APPROVED. CAPACITIES AS SHOWN ON THE DRAWINGS.
E. WIRING SHALL BE BY ELECTRICAL CONTRACTOR.
F. VERIFY MANUFACTURER MAKE AND MODEL OF EXHAUST FANS WITH HOOD DRAWINGS.
233713 AIR DISTRIBUTION DEVICES
A. DIFFUSERS, REGISTERS AND GRILLES SHALL BE PROVIDED BY CONTRACTOR.
B. COORDINATE AIR DISTRIBUTION DEVICE LOCATIONS WITH AFFECTED CONTRACTORS BEFORE
INSTALLING DUCTWORK. CHANGES IN LOCATION FROM THE DRAWINGS MUST BE APPROVED BY
OWNER BEFORE INSTALLATION.
C. SUSPEND CEILING AIR DEVICES FROM STRUCTURE ON WIRE HANGERS OR FROM RIGID
DUCTWORK. CEILING MUST NOT BE USED TO SUPPORT AIR DISTRIBUTION DEVICES.
D. SECURELY FASTEN SIDE WALL AIR DEVICES TO RIGID DUCTWORK OR STRUCTURE.
233813 - COMMERCIAL-KITCHEN HOODS
A. PROVIDE SUBMITTALS ON TYPE I HOODS, FILTERS AND BAFFLES, AND LIGHTING FIXTURES.
B. COORDINATE WITH KITCHEN EQUIPMENT LAYOUT, LIGHTING FIXTURES, HVAC EQUIPMENT,
PLUMBING, SPRINKLER SYSTEM, AND FIRE-SUPPRESSION SYSTEM COMPONENTS.
C. TYPE I HOOD SHALL BE MANUFACTURED OF STAINLESS STEEL ASTM A 666, TYPE 304 STEEL WITH
MINIMUM THICKNESS OF 0.050".
D. TYPE I HOODS SHALL BE WELDED AT ALL JOINTS EXPOSED TO GREASE WITH CONTINUOUS WELDS,
HAVE EASILY ACCESSIBLE FILTERS/BAFFLES, AND MAKE-UP AIR DIFFUSERS EASILY ACCESSIBLE
FOR CLEANING. HOODS SHALL BE FABRICATED ACCORDING TO FSF2 AND UL 710 LISTED AND
LABELED.
E. PROVIDE ACCESS PANELS FOR FIRE DAMPERS AND FUSIBLE LINKS.
F. DUCT-COLLAR FIRE DAMPERS - COLLAR AND DAMPER SHALL COMPLY WITH UL 710 TESTING AND
LISTING REQUIRED FOR THE ENTIRE HOOD.
G. LIGHTING FIXTURES - LIGHTING FIXTURES ARE PROVIDED IN THE LIGHTING PACKAGE. LED HEAT
RATED LAMPS AT 3500K ARE REQUIRED. SUBSTITUTION OF CFL OR INCANDESCENT LAMPS IS NOT
AUTHORIZED.
H. HOOD CONTROLS - HOOD CONTROLS SHALL BE ENCLOSED WITHIN A WALL MOUNTED CONTROL
PANEL, FACTORY WIRED AND FABRICATED OF STAINLESS STEEL. ON-OFF SWITCHES SHALL START
AND STOP THE EXHAUST FAN WITH AN INTERLOCK FOR THE SUPPLY FAN TO OPERATE
SIMULTANEOUSLY. INTERLOCK EXHAUST FAN WITH FIRE-SUPPRESSION SYSTEM TO OPERATE FAN
DURING FIRE-SUPPESSION-AGENT RELEASE AND TO REMAIN IN OPERATION UNTIL MANUALLY
STOPPED.
12
/
2
2
/
2
0
1
7
4
:
1
3
:
4
7
P
M
79
6
M
e
r
u
s
C
o
u
r
t
St
.
L
o
u
i
s
,
M
O
6
3
0
2
6
T
6
3
6
.
3
4
9
.
1
6
0
0
F
6
3
6
.
3
4
9
.
1
7
3
0
CE
R
T
I
F
I
C
A
T
E
O
F
A
U
T
H
O
R
I
T
Y
N
O
.
3
8
0
0
8/18/2021
SEAL
DESCRIPTIONDATEREV.
ISSUE DATE: 08/17/2021
PROJECT NUMBER: 21-008
DRAWN BY:
CHECKED BY:
SHEET NAME
SHEET NUMBER
MO
O
D
Y
R
D
&
N
2
N
D
E
RE
X
B
U
R
G
,
I
D
8
3
4
4
0
PROJECT TYPE:
SITE NUMBER:
BUILDING TYPE:
OWNER:
BASE VERSION:
DRAWING RELEASE:
PROJECT YEAR:
ASSET TYPE:
CLASSIFICATION:
UPGRADE CLASSIFICATION:
DESIGN TYPE:
#13487
(2.0) SMART 40+
FREESTANDING
NEW
FRANCHISE
2020
NEW BUILD
2021
(2.0) UM BRITE
SUMMER
NEW
SMART 40+
1 10/20/2021 City Comments
MECHANICAL
SPECIFICATIONS
M4.0
OM
DRC
TOTAL EXH. CFM =
20"
11"L0502 EO 1500 1
5
-
13"
13"KSA EXPO 18 GA. 430 S.S. 48612"
79
6
M
e
r
u
s
C
o
u
r
t
St
.
L
o
u
i
s
,
M
O
6
3
0
2
6
T
6
3
6
.
3
4
9
.
1
6
0
0
F
6
3
6
.
3
4
9
.
1
7
3
0
CE
R
T
I
F
I
C
A
T
E
O
F
A
U
T
H
O
R
I
T
Y
N
O
.
3
8
0
0
8/18/2021
SEAL
DESCRIPTIONDATEREV.
ISSUE DATE: 08/17/2021
PROJECT NUMBER: 21-008
DRAWN BY:
CHECKED BY:
SHEET NAME
SHEET NUMBER
MO
O
D
Y
R
D
&
N
2
N
D
E
RE
X
B
U
R
G
,
I
D
8
3
4
4
0
PROJECT TYPE:
SITE NUMBER:
BUILDING TYPE:
OWNER:
BASE VERSION:
DRAWING RELEASE:
PROJECT YEAR:
ASSET TYPE:
CLASSIFICATION:
UPGRADE CLASSIFICATION:
DESIGN TYPE:
#13487
(2.0) SMART 40+
FREESTANDING
NEW
FRANCHISE
2020
NEW BUILD
2021
(2.0) UM BRITE
SUMMER
NEW
SMART 40+
1 10/20/2021 City Comments
HOOD DETAILS
H1.1
HALTON
HALTON
TOTAL EXH. CFM =
20"
11"L0307 EO 1100 - - 1
3
-
13"
13"KSA EXPO 18 GA. 430 S.S. 38512"
79
6
M
e
r
u
s
C
o
u
r
t
St
.
L
o
u
i
s
,
M
O
6
3
0
2
6
T
6
3
6
.
3
4
9
.
1
6
0
0
F
6
3
6
.
3
4
9
.
1
7
3
0
CE
R
T
I
F
I
C
A
T
E
O
F
A
U
T
H
O
R
I
T
Y
N
O
.
3
8
0
0
8/18/2021
SEAL
DESCRIPTIONDATEREV.
ISSUE DATE: 08/17/2021
PROJECT NUMBER: 21-008
DRAWN BY:
CHECKED BY:
SHEET NAME
SHEET NUMBER
MO
O
D
Y
R
D
&
N
2
N
D
E
RE
X
B
U
R
G
,
I
D
8
3
4
4
0
PROJECT TYPE:
SITE NUMBER:
BUILDING TYPE:
OWNER:
BASE VERSION:
DRAWING RELEASE:
PROJECT YEAR:
ASSET TYPE:
CLASSIFICATION:
UPGRADE CLASSIFICATION:
DESIGN TYPE:
#13487
(2.0) SMART 40+
FREESTANDING
NEW
FRANCHISE
2020
NEW BUILD
2021
(2.0) UM BRITE
SUMMER
NEW
SMART 40+
1 10/20/2021 City Comments
HOOD DETAILS
H1.2
HALTON
HALTON
79
6
M
e
r
u
s
C
o
u
r
t
St
.
L
o
u
i
s
,
M
O
6
3
0
2
6
T
6
3
6
.
3
4
9
.
1
6
0
0
F
6
3
6
.
3
4
9
.
1
7
3
0
CE
R
T
I
F
I
C
A
T
E
O
F
A
U
T
H
O
R
I
T
Y
N
O
.
3
8
0
0
8/18/2021
SEAL
DESCRIPTIONDATEREV.
ISSUE DATE: 08/17/2021
PROJECT NUMBER: 21-008
DRAWN BY:
CHECKED BY:
SHEET NAME
SHEET NUMBER
MO
O
D
Y
R
D
&
N
2
N
D
E
RE
X
B
U
R
G
,
I
D
8
3
4
4
0
PROJECT TYPE:
SITE NUMBER:
BUILDING TYPE:
OWNER:
BASE VERSION:
DRAWING RELEASE:
PROJECT YEAR:
ASSET TYPE:
CLASSIFICATION:
UPGRADE CLASSIFICATION:
DESIGN TYPE:
#13487
(2.0) SMART 40+
FREESTANDING
NEW
FRANCHISE
2020
NEW BUILD
2021
(2.0) UM BRITE
SUMMER
NEW
SMART 40+
1 10/20/2021 City Comments
HOOD DETAILS
H1.3
HALTON
HALTON
SP
MAXLITE
LED
MAXLITE
LED
MAXLITE
LED
EX
T
.
R
A
M
P
MA
X
L
I
T
E
LE
D
MAXLITE
LED
MA
X
L
I
T
E
LE
D
MAXLITE
LED
LCA672LCE6120
MAXLITE
LED
MAXLITE
LED
1LIGHTING PLAN
1/4" = 1'-0"
DINING
101
A- 6
A7
T2
T2
EX1B
A7
6'
P4L
P4L
EX1B
T2
T2
6'
A- 2
SWITCH E
A7
4'
T2
2'
T2
EM2B
A7
EM2B
A7
A7
8
6
2
J
J
J
#10
A7/NL
A7/NL
SWITCH C
TL1
EX1RB
T2T
T2T
T2T
T2T
T2
A7
A7 A7
A-12
SWITCH B
A6
T1 T1
P4L
P4L
SWITCH D
SWITCH C
A7/NL
T1
T1 T1
SWITCH D
K12A-2 #10
T1
A6
A-2
TL1
8
8
TL1
K12 K12
K12A-2
#10
K12K12 K12
2 A-4
J
7 A-2#10
A1
OS1 EM2WEM2W
A-17
OS1
OS OS
OS1
OS
A1
A1
A1
A1
EM2W
A1
A1
A1
A1A1
A1
5
A1/NL
A-33
SWITCH A
A1/NL
J
EM2W
4
NL
B4B4 B4
EM2W
NL
B4B4
B4
B4
EM2W
1
1
33 3
HL1HL1HL1
3
HL1
3
HL1
J
J
C-21
2
B4/NL
A-8
J
#10
NL
B4
NL
B4
NL
B4
B4
B4B4
B4
B4B4
B4
B4
OS
EM2W
A-13
B4
B4
EX1W
D
EX1RB
WP4
WB1
EX1W
OS2OS
A-11
OS2
OS
WB1
WB1
WB1
WB1
WB1
WB1
WB1WB1
K12 K12
A-2
OS2
OS
T1
T1
B4
T1
K12
A- 16
2
J
#10
EM2W
EM2W
FAMILY
103
FAMILY
102OFFICE
108
FREEZER
110
RECEIVING
112
COOLER
111
CREW
114
KITCHEN
106
DRIVE THRU
105
PAY WINDOW
113
SERVICE
104
UTILITY
116
ENTRY
100
12
/
2
2
/
2
0
1
7
4
:
0
9
:
5
0
P
M
LIGHTING PLAN
E1.1
KH
MJ
79
6
M
e
r
u
s
C
o
u
r
t
St
.
L
o
u
i
s
,
M
O
6
3
0
2
6
T
6
3
6
.
3
4
9
.
1
6
0
0
F
6
3
6
.
3
4
9
.
1
7
3
0
CE
R
T
I
F
I
C
A
T
E
O
F
A
U
T
H
O
R
I
T
Y
N
O
.
3
8
0
0
8/18/2021
SEAL
DESCRIPTIONDATEREV.
ISSUE DATE: 08/17/2021
PROJECT NUMBER: 21-008
DRAWN BY:
CHECKED BY:
SHEET NAME
SHEET NUMBER
MO
O
D
Y
R
D
&
N
2
N
D
E
RE
X
B
U
R
G
,
I
D
8
3
4
4
0
PROJECT TYPE:
SITE NUMBER:
BUILDING TYPE:
OWNER:
BASE VERSION:
DRAWING RELEASE:
PROJECT YEAR:
ASSET TYPE:
CLASSIFICATION:
UPGRADE CLASSIFICATION:
DESIGN TYPE:
#13487
(2.0) SMART 40+
FREESTANDING
NEW
FRANCHISE
2020
NEW BUILD
2021
(2.0) UM BRITE
SUMMER
NEW
SMART 40+
1 10/20/2021 City Comments
A-2
B1
RECESSED CAN LIGHT FIXTURE
RECESSED CAN NIGHT LIGHT FIXTURE
LED LIGHT FIXTURE
LED NIGHT LIGHT FIXTURE
HANGING LIGHT FIXTURE
MONO POINT LIGHT FIXTURE
EMERGENCY REMOTE EGRESS HEAD
CIRCUIT NUMBER
FIXTURE SYMBOL
OCCUPANCY SENSOR (WALL MOUNTED OR
CEILING MOUNTED)
SINGLE POLE WALL SWITCH AT 4'-6" A.F.F.
EMERGENCY FLOOR LIGHT (WALL MOUNTED OR
CEILING SURFACE MOUNTED)
DIMMER SWITCH, (LEVITON #IP710-DLZ-WH)D
OS
LIGHTING LEGEND
LED TAPE LIGHT
GLOBE PENDANT LIGHT
PENDANT LIGHT
TRACK HEAD
BUILDING MOUNTED DECORATIVE LIGHT
OS
LIGHTING TRACK
A. COORDINATE WORK WITH MECHANICAL, REFRIGERATION AND EQUIPMENT CONTRACTORS,
INCLUDING COOLER/FREEZER WORK AND ICE MACHINE CONDENSING UNITS.
B. VERIFY ROUGH-IN DIMENSIONS AND POWER REQUIREMENTS WITH KITCHEN EQUIPMENT
DISTRIBUTOR PRIOR TO ROUGH-IN.
C. PROVIDE FINAL CONNECTIONS WITHIN FRONT COUNTER, COOKCENTER PANEL, REMOTE
REFRIGERATION UNITS, AND ICE MACHINE REMOTE UNIT WHEN INSTALLED BY VENDOR.
D. VERIFY AVAILABLE FAULT CURRENT AT PRIMARY SERVICE AND COMPATIBILITY WITH
MODULAR PANEL SYSTEM.
E. ENSURE ADEQUATE CONDUIT SIZE FOR ELECTRICAL AND COMMUNICATION WIRING ON SITE
AND INTO BUILDING.
F. CIRCUITS MAY BE GROUPED WITHIN COMMON CONDUITS PER NEC REQUIREMENTS UNLESS
NOTED OTHERWISE.
G. PROVIDE WALL BOX WITH 1/2" CONDUIT WITH PULLSTRING AND NYLON BUSHING STUBBED
ABOVE NEAREST ACCESSIBLE CEILING FOR THERMOSTATS, TEMPERATURE SENSORS,
CARBON DIOXIDE SENSOR, AND HUMIDISTATS UNLESS OTHERWISE NOTED.
H. WIRE ROOF TOP UNIT CONTROL CIRCUIT THROUGH AUXILIARY CONTACTS IN SMOKE
DETECTOR AND MAKE ALL FINAL CONNECTIONS. (TYPICAL OF ALL ROOF TOP UNITS)
I. COOKCENTER IS ASSEMBLED AND PREWIRED AT THE FACTORY. WIRING IS PROVIDED IN THE
PRE- INSTALLED SPLICE BOX, COILED AND TAGGED. A LENGTH OF CONDUIT WITH WIRES IS
PROVIDED FOR THE REMOTE CONDENSING ROOFTOP UNIT. RUNS POWER FROM THE SPLICE
BOX TO THE COOKCENTER PANEL.
J. ROOFTOP UNIT IS FACTORY PROVIDED WITH DISCONNECT AND UNPOWERED SERVICE
RECEPTACLE.
K. IN AREAS WITHOUT CEILINGS OR WHERE ANY CONDUITS, CONDUCTORS, FEEDERS. OR LOW-
VOLTAGE WALL EMT CONDUIT. CABLING IS VISIBLE, ALL WIRING SHALL BE IN RIGID
GALVANIZED STEEL (RGSC) OR THIN WALL EMT CONDUIT. BX, AC, AND MC CABLE ARE NOT
PERMITTED. CONDUITS ARE TO BE RUN TIGHT TO DECK EITHER PARALLEL OR
PERPENDICULAR TO BUILDING LINES AND ONLY DROP AT POINT OF CONNECTION. JUNCTION
BOXES SHALL HAVE CIRCUIT NUMBERS WRITTEN ON THE INSIDE OF THE JUNCTION BOX
COVER.
L. SEAL ROOF PENETRATIONS PER ROOFING MANUFACTURER'S INSTRUCTIONS.
M. COORDINATE WORK ABOVE THE CEILING WITH OTHER TRADES TO PROVIDE THE GREATEST
POSSIBLE CLEARANCE.CONDUITS SHALL BE ROUTED IN THE DIRECTION OF THE TRUSSES.
N. ONLY EMT CONDUITS ARE ALLOWED IN RECEIVING/DRY STORAGE.
O. DEFINITIONS: FURNISH MEANS TO SUPPLY AND DELIVER TO PROJECT SITE, READY FOR
INSTALLATION. INSTALL MEANS TO PLAN IN POSITION AND MAKE CONNECTIONS FOR SERVICE
OR USE. PROVIDE MEANS TO FURNISH AND INSTALL, COMPLETE AND READY FOR INTENDED
USE.
1. JUNCTION BOX ABOVE CEILING FOR HOOD LIGHTS AND EXHAUST HOOD.
2. PROVIDE WEATHERPROOF JUNCTION BOX AND TOGGLE TYPE 20A-1P DISCONNECT FOR
SIGNAGE. COORDINATE EXACT REQUIREMENTS WITH SIGN CONTRACTOR. VERIFY
LOCATION PRIOR TO ROUGH IN.
3. PROVIDE LAMP FOR HOOD LIGHT. SUBSTITUTION OF CFL OR INCANDESCENT LAMP IS
PROHIBITED.
4. LOCATION OF LIGHTING SWITCH BANK. REFER TO SWITCH AND HOOD SUPPRESSION
ELEVATION ON SHEET E5.2 FOR ADDITIONAL INFORMATION.
5. PROVIDE JUNCTION BOX AND SWITCH FOR ILLUMINATED MIRROR AT 4'-0" AFF AND CONNECT
TO CIRCUIT SHOWN. REFER TO ARCHITECTURAL ELEVATIONS FOR EXACT MOUNTING
LOCATION.
6. LED TAPE LIGHTING DRIVER MUST BE INSTALLED INSIDE OF BUILDING DUE TO
TEMPERATURE RATING OF DRIVER. REFER TO LED DRIVER MOUNTING DETAIL, SHEET E5.2.
7. LIGHTS IN CANOPY PROVIDED BY CANOPY MANUFACTURER.
8. EXTERIOR LED TAPE LIGHTING 'TL1'. REFER TO ARCHITECTURAL SHEETS FOR MORE
INFORMATION. VERIFY LENGTHS AND DRIVER REQUIREMENTS PRIOR TO INSTALLATION.
REFER TO WALL PENETRATION DETAIL, SHEET E5.2.
CODED NOTES:LIGHTING GENERAL NOTES
A. CONNECT EXIT/EMERGENCY/NIGHT FIXTURES TO UNSWITCHED HOT CONDUCTOR AHEAD OF
ANY LIGHTING CONTROLS.
B. REFER TO ARCHITECTURAL REFLECTED CEILING PLAN AND DETAILS FOR THE LOCATION OF
ALL LIGHTING FIXTURES AND ALL OTHER CEILING MOUNTED EQUIPMENT. VERIFY MOUNTING
HEIGHTS AND FINISHES WITH ARCHITECT PRIOR TO ROUGH-IN.
C. REFER TO THE POWER PLANS FOR LOCATION OF ELECTRICAL EQUIPMENT.
D. PROVIDE INDICATED CONDUCTOR SIZE FOR ENTIRE CIRCUIT WHERE CONDUCTOR SIZES
ARE SHOWN ON HOMERUNS.
E. PROVIDE A DEDICATED NEUTRAL WITH ALL DIMMING SYSTEM CIRCUITS. NO COMMON
NEUTRALS SHALL BE ALLOWED.
F. PROVIDE (2) ADDITIONAL #12 CONDUCTORS FOR ALL 0-10V DIMMING CIRCUITS.