HomeMy WebLinkAboutREDLINED ARCHITECTURAL PLANS 2 - 21-00694 - 240 E Moody - Wendy's - New BuildingAuthor Name Author Email Author Phone No.:
Alex Owens Alex.Owens@rexburg.org 208-372-2330
Cody Jones Cody.Jones@rexburg.org 208-372-2173
Description : 240 E Moody - Wendy's - New Building
Address : 240 E Moody
Application Type :
Document Filename : Wendys_Rexburg ID_Architectural Plans_2 of 2.pdf Array
Comment Author Contact Information:
Corrections in the following table need to be applied before a permit can be issued
Review Report
Revisions Required
Page Reference Annotation
Type
Author : Department Status Page Review Comments Applicant Response Comments
E1.1 Callout Alex Owens : Electrical Open 19 EMT or MC cable assumed in concealed locations. If not
accurate please verify.
E3.1 Callout Alex Owens : Electrical Open 23 Available fault current calculation required.
E6.1 Callout Alex Owens : Electrical Open 28 All wiring must meet 2017 NEC standards
# 21-00694
New Commercial Building
Panic Hardware shall be installed as per IBC Section 1010.1.10
Report Date: 10.05.2021
Approval of plans does not constitute approval of variance from code
Page 1 of 1
Powered by TCPDF (www.tcpdf.org)
SP
MAXLITE
LED
MAXLITE
LED
MAXLITE
LED
EX
T
.
R
A
M
P
MA
X
L
I
T
E
LE
D
MAXLITE
LED
MA
X
L
I
T
E
LE
D
MAXLITE
LED
LCA672LCE6120
MAXLITE
LED
MAXLITE
LED
1LIGHTING PLAN
1/4" = 1'-0"
DINING
101
A- 6
A7
T2
T2
EX1B
A7
6'
P4L
P4L
EX1B
T2
T2
6'
A- 2
SWITCH E
A7
4'
T2
2'
T2
EM2B
A7
EM2B
A7
A7
8
6
2
J
J
J
#10
A7/NL
A7/NL
SWITCH C
TL1
EX1RB
T2T
T2T
T2T
T2T
T2
A7
A7 A7
A-12
SWITCH B
A6
T1 T1
P4L
P4L
SWITCH D
SWITCH C
A7/NL
T1
T1 T1
SWITCH D
K12A-2 #10
T1
A6
A-2
TL1
8
8
TL1
K12 K12
K12A-2
#10
K12K12 K12
2 A-4
J
7 A-2#10
A1
OS1 EM2WEM2W
A-17
OS1
OS OS
OS1
OS
A1
A1
A1
A1
EM2W
A1
A1
A1
A1A1
A1
5
A1/NL
A-33
SWITCH A
A1/NL
J
EM2W
4
NL
B4B4 B4
EM2W
NL
B4B4
B4
B4
EM2W
1
1
33 3
HL1HL1HL1
3
HL1
3
HL1
J
J
C-21
2
B4/NL
A-8
J
#10
NL
B4
NL
B4
NL
B4
B4
B4B4
B4
B4B4
B4
B4
OS
EM2W
A-13
B4
B4
EX1W
D
EX1RB
WP4
WB1
EX1W
OS2OS
A-11
OS2
OS
WB1
WB1
WB1
WB1
WB1
WB1
WB1WB1
K12 K12
A-2
OS2
OS
T1
T1
B4
T1
K12
A- 16
2
J
#10
EM2W
EM2W
FAMILY
103
FAMILY
102OFFICE
108
FREEZER
110
RECEIVING
112
COOLER
111
CREW
114
KITCHEN
106
DRIVE THRU
105
PAY WINDOW
113
SERVICE
104
UTILITY
116
ENTRY
100
12
/
2
2
/
2
0
1
7
4
:
0
9
:
5
0
P
M
LIGHTING PLAN
E1.1
KH
MJ
79
6
M
e
r
u
s
C
o
u
r
t
St
.
L
o
u
i
s
,
M
O
6
3
0
2
6
T
6
3
6
.
3
4
9
.
1
6
0
0
F
6
3
6
.
3
4
9
.
1
7
3
0
CE
R
T
I
F
I
C
A
T
E
O
F
A
U
T
H
O
R
I
T
Y
N
O
.
3
8
0
0
8/18/2021
SEAL
DESCRIPTIONDATEREV.
ISSUE DATE: 08/17/2021
PROJECT NUMBER: 21-008
DRAWN BY:
CHECKED BY:
SHEET NAME
SHEET NUMBER
MO
O
D
Y
R
D
&
N
2
N
D
E
RE
X
B
U
R
G
,
I
D
8
3
4
4
0
PROJECT TYPE:
SITE NUMBER:
BUILDING TYPE:
OWNER:
BASE VERSION:
DRAWING RELEASE:
PROJECT YEAR:
ASSET TYPE:
CLASSIFICATION:
UPGRADE CLASSIFICATION:
DESIGN TYPE:
#13487
(2.0) SMART 40+
FREESTANDING
NEW
FRANCHISE
2020
NEW BUILD
2021
(2.0) UM BRITE
SUMMER
NEW
SMART 40+
A-2
B1
RECESSED CAN LIGHT FIXTURE
RECESSED CAN NIGHT LIGHT FIXTURE
LED LIGHT FIXTURE
LED NIGHT LIGHT FIXTURE
HANGING LIGHT FIXTURE
MONO POINT LIGHT FIXTURE
EMERGENCY REMOTE EGRESS HEAD
CIRCUIT NUMBER
FIXTURE SYMBOL
OCCUPANCY SENSOR (WALL MOUNTED OR
CEILING MOUNTED)
SINGLE POLE WALL SWITCH AT 4'-6" A.F.F.
EMERGENCY FLOOR LIGHT (WALL MOUNTED OR
CEILING SURFACE MOUNTED)
DIMMER SWITCH, (LEVITON #IP710-DLZ-WH)
D
OS
LIGHTING LEGEND
LED TAPE LIGHT
GLOBE PENDANT LIGHT
PENDANT LIGHT
TRACK HEAD
BUILDING MOUNTED DECORATIVE LIGHT
OS
LIGHTING TRACK
A. COORDINATE WORK WITH MECHANICAL, REFRIGERATION AND EQUIPMENT CONTRACTORS,
INCLUDING COOLER/FREEZER WORK AND ICE MACHINE CONDENSING UNITS.
B. VERIFY ROUGH-IN DIMENSIONS AND POWER REQUIREMENTS WITH KITCHEN EQUIPMENT
DISTRIBUTOR PRIOR TO ROUGH-IN.
C. PROVIDE FINAL CONNECTIONS WITHIN FRONT COUNTER, COOKCENTER PANEL, REMOTE
REFRIGERATION UNITS, AND ICE MACHINE REMOTE UNIT WHEN INSTALLED BY VENDOR.
D. VERIFY AVAILABLE FAULT CURRENT AT PRIMARY SERVICE AND COMPATIBILITY WITH
MODULAR PANEL SYSTEM.
E. ENSURE ADEQUATE CONDUIT SIZE FOR ELECTRICAL AND COMMUNICATION WIRING ON SITE
AND INTO BUILDING.
F. CIRCUITS MAY BE GROUPED WITHIN COMMON CONDUITS PER NEC REQUIREMENTS UNLESS
NOTED OTHERWISE.
G. PROVIDE WALL BOX WITH 1/2" CONDUIT WITH PULLSTRING AND NYLON BUSHING STUBBED
ABOVE NEAREST ACCESSIBLE CEILING FOR THERMOSTATS, TEMPERATURE SENSORS,
CARBON DIOXIDE SENSOR, AND HUMIDISTATS UNLESS OTHERWISE NOTED.
H. WIRE ROOF TOP UNIT CONTROL CIRCUIT THROUGH AUXILIARY CONTACTS IN SMOKE
DETECTOR AND MAKE ALL FINAL CONNECTIONS. (TYPICAL OF ALL ROOF TOP UNITS)
I. COOKCENTER IS ASSEMBLED AND PREWIRED AT THE FACTORY. WIRING IS PROVIDED IN THE
PRE- INSTALLED SPLICE BOX, COILED AND TAGGED. A LENGTH OF CONDUIT WITH WIRES IS
PROVIDED FOR THE REMOTE CONDENSING ROOFTOP UNIT. RUNS POWER FROM THE SPLICE
BOX TO THE COOKCENTER PANEL.
J. ROOFTOP UNIT IS FACTORY PROVIDED WITH DISCONNECT AND UNPOWERED SERVICE
RECEPTACLE.
K. IN AREAS WITHOUT CEILINGS OR WHERE ANY CONDUITS, CONDUCTORS, FEEDERS. OR LOW-
VOLTAGE WALL EMT CONDUIT. CABLING IS VISIBLE, ALL WIRING SHALL BE IN RIGID
GALVANIZED STEEL (RGSC) OR THIN WALL EMT CONDUIT. BX, AC, AND MC CABLE ARE NOT
PERMITTED. CONDUITS ARE TO BE RUN TIGHT TO DECK EITHER PARALLEL OR
PERPENDICULAR TO BUILDING LINES AND ONLY DROP AT POINT OF CONNECTION. JUNCTION
BOXES SHALL HAVE CIRCUIT NUMBERS WRITTEN ON THE INSIDE OF THE JUNCTION BOX
COVER.
L. SEAL ROOF PENETRATIONS PER ROOFING MANUFACTURER'S INSTRUCTIONS.
M. COORDINATE WORK ABOVE THE CEILING WITH OTHER TRADES TO PROVIDE THE GREATEST
POSSIBLE CLEARANCE.CONDUITS SHALL BE ROUTED IN THE DIRECTION OF THE TRUSSES.
N. ONLY EMT CONDUITS ARE ALLOWED IN RECEIVING/DRY STORAGE.
O. DEFINITIONS: FURNISH MEANS TO SUPPLY AND DELIVER TO PROJECT SITE, READY FOR
INSTALLATION. INSTALL MEANS TO PLAN IN POSITION AND MAKE CONNECTIONS FOR SERVICE
OR USE. PROVIDE MEANS TO FURNISH AND INSTALL, COMPLETE AND READY FOR INTENDED
USE.
1. JUNCTION BOX ABOVE CEILING FOR HOOD LIGHTS AND EXHAUST HOOD.
2. PROVIDE WEATHERPROOF JUNCTION BOX AND TOGGLE TYPE 20A-1P DISCONNECT FOR
SIGNAGE. COORDINATE EXACT REQUIREMENTS WITH SIGN CONTRACTOR. VERIFY
LOCATION PRIOR TO ROUGH IN.
3. PROVIDE LAMP FOR HOOD LIGHT. SUBSTITUTION OF CFL OR INCANDESCENT LAMP IS
PROHIBITED.
4. LOCATION OF LIGHTING SWITCH BANK. REFER TO SWITCH AND HOOD SUPPRESSION
ELEVATION ON SHEET E5.2 FOR ADDITIONAL INFORMATION.
5. PROVIDE JUNCTION BOX AND SWITCH FOR ILLUMINATED MIRROR AT 4'-0" AFF AND CONNECT
TO CIRCUIT SHOWN. REFER TO ARCHITECTURAL ELEVATIONS FOR EXACT MOUNTING
LOCATION.
6. LED TAPE LIGHTING DRIVER MUST BE INSTALLED INSIDE OF BUILDING DUE TO
TEMPERATURE RATING OF DRIVER. REFER TO LED DRIVER MOUNTING DETAIL, SHEET E5.2.
7. LIGHTS IN CANOPY PROVIDED BY CANOPY MANUFACTURER.
8. EXTERIOR LED TAPE LIGHTING 'TL1'. REFER TO ARCHITECTURAL SHEETS FOR MORE
INFORMATION. VERIFY LENGTHS AND DRIVER REQUIREMENTS PRIOR TO INSTALLATION.
REFER TO WALL PENETRATION DETAIL, SHEET E5.2.
CODED NOTES:LIGHTING GENERAL NOTES
A. CONNECT EXIT/EMERGENCY/NIGHT FIXTURES TO UNSWITCHED HOT CONDUCTOR AHEAD OF
ANY LIGHTING CONTROLS.
B. REFER TO ARCHITECTURAL REFLECTED CEILING PLAN AND DETAILS FOR THE LOCATION OF
ALL LIGHTING FIXTURES AND ALL OTHER CEILING MOUNTED EQUIPMENT. VERIFY MOUNTING
HEIGHTS AND FINISHES WITH ARCHITECT PRIOR TO ROUGH-IN.
C. REFER TO THE POWER PLANS FOR LOCATION OF ELECTRICAL EQUIPMENT.
D. PROVIDE INDICATED CONDUCTOR SIZE FOR ENTIRE CIRCUIT WHERE CONDUCTOR SIZES
ARE SHOWN ON HOMERUNS.
E. PROVIDE A DEDICATED NEUTRAL WITH ALL DIMMING SYSTEM CIRCUITS. NO COMMON
NEUTRALS SHALL BE ALLOWED.
F. PROVIDE (2) ADDITIONAL #12 CONDUCTORS FOR ALL 0-10V DIMMING CIRCUITS.
EMT or MC cable assumed in
concealed locations. If not
accurate please verify.
NEUTRAL
SHUNT
TRIP
BREAKERS
IN 'MDP'
RED
BLACK
CIRCUIT
A-5
MICRO SWITCH
IN HOOD
POWER KILL
SWITCHES
NOT TO SCALE
SHUNT TRIP CIRCUIT DETAIL 2
SERIES RATED NOTES
MAIN BREAKERS IN MDP TO BE "FULLY" RATED TO WITHSTAND THE AVAILABLE
FAULT CURRENT AT M.D.P. OF 65,000 AMPS R.M.S.
2. THE DISTRIBUTION SYSTEM IS TO BE A "SERIES" RATED, TWO-TIER, 65/10 SYSTEM.
3. MOTOR LOAD CONTRIBUTION TO THESE PANELBOARDS SHALL NOT EXCEED 1.0%
OF THE PANELBOARD A.I.C. RATING.
4. WHERE "SERIES" RATING IS USED, PANELBOARDS AND DISTRIBUTION PANELS ARE
TO BE LEGIBLY MARKED TO INDICATE THE EQUIPMENT HAS BEEN APPLIED WITH A
"SERIES" COMBINATION RATING. LABELS CAN BE FACTORY INSTALLED OR
ENGRAVED PLASTIC-LAMINATE CARD. MARKING SHALL COMPLY WITH ARTICLE
110-22 OF N.E.C.
CONTROL ZONES
ZONE 1 KITCHEN LIGHTS & WORK LIGHTS
ZONE 2 DINING ROOM - GENERAL LIGHTS
ZONE 3 HOODS
ZONE 4 PARKING LOT LIGHTS
ZONE 5 EXTERIOR BUILDING LIGHTS/ BUILDING SIGNS/ MENU BOARDS
ZONE 6 NOT USED
ZONE 7 NOT USED
*SEE SHEET W1.1 FOR LIGHT ZONE CONTROL INFORMATION.
ARC FLASH LABELING
A. SWITCHBOARDS, PANELBOARDS AND BUSWAY SHALL HAVE A COMMERCIALLY
PRODUCED PERMANENT LABEL APPLIED, SIMILAR TO IMAGE BELOW, TO WARN OF
POTENTIAL ARC FLASH HAZARDS IN ACCORDANCE WITH NEC 110.16 AND NFPA 70E
B. LABELING MAY BE COMPLETED BY THE CONTRACTOR. THE CONTRACTOR SHALL
VERIFY THAT SWITCHBOARDS AND PANELBOARDS ARE PROPERLY LABELED IN THE
FIELD.
C. PROVIDE AND INSTALL A LABEL SIMILAR TO BELOW TO COMPLY WITH NEC 110.16
AND NFPA 70E. THE MARKING SHALL BE LOCATED SO AS TO BE CLEARLY TO
QUALIFIED PERSONS BEFORE EXAMINATION, ADJUSTMENT, SERVICING OR
MAINTENANCE OF THE EQUIPMENT. LABEL SHALL NOT BE LOCATED ON A HINGED
DOOR, OR A MOVABLE SERVICE.
PANEL
'C'
PANEL
'A'
PANEL
'B'
'COOK-
CENTER'
PANEL
PANEL
'MDP'
EXTERIOR WALL
POWER COMPANY
METER
WP C/T EQUIPMENT
CABINET
REFER TO SHEET W1.2
FOR MORE INFORMATION
ON 'FC/LC'
'LC'
LIGHTING
CONTROL
'FC'
FAN
CONTROL
CONTACT SUPPLIER FOR
SEISMIC BRACING.
SEE ARCHITECTURAL
SHEETS FOR CURB AT
SWITCHGEAR
NOTE: CONTRACTOR TO
ORDER ELECTRICAL PANEL
SYSTEM AT THE START OF
CONSTRUCTION GIVEN THE
6 WEEK LEAD TIME FOR THE
MODULAR PANEL SYSTEM.
CONTRACTOR TO PROVIDE
MECHANICAL AND
ELECTRICAL PLANS WHEN
PLACING ORDER.
SURGE PROTECTION
DEVICE
SPD
NOTE:
CONTRACTOR TO DOWNLOAD AND EXECUTE
MODULAR PANEL SYSTEM'S START UP AND
SYSTEM CHECK LIST REQUIREMENTS FROM
WENDY'S.
PANEL B OAU #1 *
208V
3PH, 3W
*SHUNT-TRIP BREAKER CONTROLLED
BY ANSUL SYSTEM. SHUTDOWN OF
POWER ON LOAD SIDE OF BREAKER
SHALL OCCUR ON ACTIVATION OF FIRE
SUPPRESSION SYSTEM OR UPON
MOMENTARY CONTACT OF
ELECTRICAL SHUT DOWN SWITCH "W"
SUB FEEDERS TO PANELS "A", "B", "C"
AND "COOKCENTER" ARE PREWIRED
AND PREINSTALLED INSIDE THE
MODULAR PANEL SYSTEM.
GND. 2/0
AWG, CU.
1
200/3
6
200/3*
SHUNT
TRIP
3
110/3*
SHUNT
TRIP
5
225/3*
SHUNT
TRIP
2/0 AWG, CU.
PANEL A
MDP
208/120V, 3 PHASE,
4 WIRE 65K AIC
PANEL
COOKCENTER*
MAIN WATER
SERVICE PIPE
REFER TO HVAC
CONNECTION
SCHEDULE IN
SHEET E3.2
C.T.
METER
800A. BUS
2
200/3
E.C. TO PROVIDE NEW WEATHERPROOF
C/T CABINET WITH 8OOA C/T IN
ACCORDANCE WITH UTILITY COMPANY
REQUIREMENTS.
60/3*
SHUNT
TRIP
PANEL C *
EC TO PROVIDE NEW 120/208V,
800A METER SOCKET IN
LANDLORD PROVIDED METER
BASE IN ACCORDANCE WITH
UTILITY COMPANY
REQUIREMENTS.
NEUT.
ISOLATED GROUND
2/0 AWG, CU.
BUILDING STEEL
2/0 AWG, CU.
#6 AWG, CU.
10'-0" COPPER
CLAD GND. ROD
G.C. AND UTILITY TO VERIFY CAPACITY OF EXISTING TRANSFORMER.
IF EXISTING TRANSFORMER ISN'T LARGE ENOUGH FOR UPGRADED
SERVICE SIZE, UTILITY TO UPGRADE TRANSFORMER.
E.C. TO PROVIDE TWO PARALLEL SETS OF
FOUR 600MCM EACH IN 4"CONDUIT
4
RTU #1 *
208V
3PH, 3W
ELECTRICAL DISTRIBUTION GENERAL NOTES
1. PANELS "A", "B" , "C" AND "COOKCENTER" SHALL BE CIRCUITED AS SHOWN.
2. THERMOSTATS TO BE PROVIDED WITH "FC/LC" FAN CONTROL/LIGHTING CONTROL PANEL ALONG WITH REMOTE SENSORS.
3. SYSTEM IS DESIGNED TO FORCE EXHAUST FANS ON WHEN ANSUL SYSTEM ACTIVATES TO MEET CODE REQUIREMENTS.
NEW PRE-PACKAGED,
PRE-WIRED
SWITCHGEAR MODULAR
PANEL SYSTEM
800/3P
MAIN CIRCUIT
BREAKER
NOT TO SCALE
ELECTRICAL ONE-LINE DIAGRAM 1NOT TO SCALE
ELECTRICAL DISTRIBUTION ELEVATION (CPI)3
GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFIGFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI
FI
FI
EC IS RESPONSIBLE FOR FIELD VERIFICATION OF SITE CONDITIONS AND REPORTING ANY DIFFERENCES
OR DISCREPANCIES TO ELECTRICAL ENGINEER PRIOR TO BID. NO EXTRAS OR CHANGE ORDERS SHALL BE
GIVEN FOR CONTRACTOR'S FAILURE TO VERIFY SITE CONDITIONS PRIOR TO BIDDING. UNLESS
SPECIFICALLY DETERMINED IN THE LEASE, IT IS THE RESPONSIBILITY OF THE TENANT TO INSTALL A
UTILITY OR SUB METER PER LANDLORD SPECIFICATIONS. ALL SUB METERS MUST BE FUNCTIONING
PROPERLY BEFORE TENANT OPENS FOR BUSINESS. THE TOTAL TENANT CONNECTED LOAD CANNOT
EXCEED THE LANDLORD SUPPLIED UTILITY.
ELECTRICAL CONTRACTOR SHALL VERIFY ALL EQUIPMENT VOLTAGE AND
AMPERAGE REQUIREMENTS PRIOR TO FINAL CONNECTION AND REPORT ANY
DIFFERENCES TO ENGINEER. DO NOT MAKE ANY FINAL CONNECTIONS IF
VOLTAGES SHOWN ON PLANS DO NOT MATCH EQUIPMENT DELIVERED.
x ALL KITCHEN 120V, SINGLE PHASE, 15A AND 20A RECEPTACLES SHALL BE GFI TYPE PER
NEC SECTION 210.8 (B).
x ALL GFCI RECEPTACLES SHALL BE INSTALLED IN A READILY ACCESSIBLE LOCATION OR A
GFCI CIRCUIT BREAKER SHALL BE USED TO FEED THE CIRCUIT NOTED.
x ALL 125V, 15A AND 20A CIRCUITS TO KITCHEN EQUIPMENT SHALL BE FED WITH A
DEDICATED NEUTRAL WIRE.
FI
GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI
E.C. TO PROVIDE TWO PARALLEL SETS OF
FOUR 600MCM EACH IN 4"CONDUIT
FI
GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI
79
6
M
e
r
u
s
C
o
u
r
t
St
.
L
o
u
i
s
,
M
O
6
3
0
2
6
T
6
3
6
.
3
4
9
.
1
6
0
0
F
6
3
6
.
3
4
9
.
1
7
3
0
CE
R
T
I
F
I
C
A
T
E
O
F
A
U
T
H
O
R
I
T
Y
N
O
.
3
8
0
0
8/18/2021
SEAL
DESCRIPTIONDATEREV.
ISSUE DATE: 08/17/2021
PROJECT NUMBER: 21-008
DRAWN BY:
CHECKED BY:
SHEET NAME
SHEET NUMBER
MO
O
D
Y
R
D
&
N
2
N
D
E
RE
X
B
U
R
G
,
I
D
8
3
4
4
0
PROJECT TYPE:
SITE NUMBER:
BUILDING TYPE:
OWNER:
BASE VERSION:
DRAWING RELEASE:
PROJECT YEAR:
ASSET TYPE:
CLASSIFICATION:
UPGRADE CLASSIFICATION:
DESIGN TYPE:
#13487
(2.0) SMART 40+
FREESTANDING
NEW
FRANCHISE
2020
NEW BUILD
2021
(2.0) UM BRITE
SUMMER
NEW
SMART 40+
ELECTRIC DISTRIBUTION
(GAS HEAT/GAS COOKING)
E3.1
KH
MJ
Available fault current
calculation required.
260500 - COMMON WORK RESULTS FOR ELECTRICAL
A. PROVIDE ALL MATERIALS AND EQUIPMENT AND PERFORM ALL LABOR REQUIRED TO INSTALL NEW
COMPLETE ELECTRICAL SYSTEM AS INDICATED ON DRAWINGS, AS REQUIRED BY CODE AND AS
SPECIFIED HEREIN, IN SECTIONS 260500 THROUGH 270511.
1. TEMPORARY SERVICE AS REQUIRED.
2. PRIMARY DISTRIBUTION BY ELECTRIC COMPANY.
3. SECONDARY SERVICE AND METERING INSTALLATION BY CONTRACTOR.
4. EMERGENCY AND EXIT LIGHTING SYSTEMS.
5. TELEPHONE SYSTEM CONDUIT AND CABLES AS SHOWN ON THE DRAWINGS.
6. LIGHTING, HEATING AND POWER PANELS AND BRANCH CIRCUIT WIRING.
7. WIRING DEVICES AND PLATES.
8. INTERIOR AND EXTERIOR LIGHTING FIXTURES AND LAMPS, INSTALLATION AND WIRING.
9. LIGHTING CONTROLS.
10. CONNECTIONS TO EQUIPMENT FURNISHED BY OTHERS.
B. WORK WHICH SHALL BE PERFORMED BY OTHERS INCLUDES THE FOLLOWING:
1. FINAL CONNECTIONS OF MISCELLANEOUS EQUIPMENT BY ELECTRICAL CONTRACTOR.
2. CONTROL WIRING THAT IS FURNISHED BY OTHERS PRE-WIRED IN UNITS.
3. TELEPHONES AND FINAL CONNECTION OF WIRING THERETO.
4. INTERNAL WIRING OF EQUIPMENT FURNISHED AND PRE-WIRED BY OTHERS.
5. SECURITY SYSTEM FURNISHED AND INSTALLED BY SECURITY CONTRACTOR.
C. THIS CONTRACTOR SHALL FURNISH ALL LABOR, MATERIALS AND EQUIPMENT NECESSARY TO
INSTALL ALL OF THE 208/120 VOLT ELECTRICAL SERVICE FROM THE UTILITY COMPANY
TRANSFORMER TO THE SERVICE ENTRANCE EQUIPMENT, INCLUDING CABLES, CONDUIT, PULL
WIRE, AND GROUND ROD AND SLEEVE. CONTRACTOR SHALL COORDINATE INSTALLATION OF THE
MAIN ELECTRICAL DISCONNECT WITH THIS WORK.
D. ELECTRICAL EQUIPMENT FURNISHED BY OTHER TRADES OR BY THIS CONTRACTOR AND SPECIFIED
IN OR SHOWN ON CONTRACT DOCUMENTS SHALL BE INSTALLED AND CONNECTED BY THIS
CONTRACTOR, EXCEPT AS OTHERWISE NOTED. PROVIDE BRANCH CIRCUIT CONNECTIONS TO
ELECTRICALLY OPERATED EQUIPMENT FURNISHED BY OTHERS AS SPECIFIED IN OR SHOWN ON
THE CONTRACT DOCUMENTS. TEMPORARY WIRING FOR OTHER CONTRACTORS SHALL BE
FURNISHED AND INSTALLED BY THIS CONTRACTOR WHO SHALL BE ENTIRELY RESPONSIBLE FOR
THE SAFE AND SATISFACTORY OPERATION OF SAID TEMPORARY WIRING. COMPLY WITH LATEST
REQUIREMENTS OF OCCUPATIONAL SAFETY AND HEALTH ACT (OSHA). PROVIDE PERSONNEL
GROUND FAULT PROTECTION ON ALL TEMPORARY POWER AND LIGHTING CIRCUITS 30 AMPERES
OR LESS. GROUND FAULT CIRCUIT INTERRUPTERS ON CONSTRUCTION CIRCUITS ARE NOT
REQUIRED WHERE CIRCUIT IS A PERMANENT CIRCUIT TO BE A PART OF THE COMPLETED
BUILDING. HOWEVER, CONTRACTOR SHALL PROVIDE APPROVED CORD SETS INCORPORATING
GFCI PROTECTION FOR PERSONNEL. REFER TO THE NEC.
E. ALL FINISH PAINTING IS TO BE PERFORMED BY GENERAL CONTRACTOR EXCEPT THAT THIS
CONTRACTOR SHALL RESTORE TO ORIGINAL CONDITION ANY PAINTING DEFACED BY THIS
CONTRACTOR AFTER ORIGINAL PAINTING.
F. ALL WORK SHALL BE DONE IN ACCORDANCE WITH:
1. NATIONAL ELECTRICAL CODE.
2. CODES: STATE, CITY AND COUNTY BUILDING CODES AND ORDINANCES.
3. NATIONAL BOARD OF FIRE UNDERWRITERS.
4. CERTAIN CODES AND STANDARDS AS SET UP BY VARIOUS TECHNICAL SOCIETIES SUCH AS
UL, NEMA, NECA, IEEE, ASTM, IES, IPCEA, AND ANSI.
5. THIS WORK SHALL BE GOVERNED ALSO BY LOCAL INSPECTOR'S REQUIREMENTS.
6. FEDERAL OCCUPATIONAL SAFETY AND HEALTH ACT STANDARDS.
7. AMERICANS WITH DISABILITIES ACT.
G. ALL PERMITS REQUIRED BY LAWS, ORDINANCES AND BUILDING CODES HAVING JURISDICTION
SHALL BE OBTAINED AT PROPER TIME BY AND AT THE EXPENSE OF THIS CONTRACTOR.
H. ALL ELECTRICAL WORK SHALL BE INSPECTED BY THE GOVERNMENTAL AGENCY HAVING
JURISDICTION, INCLUDING LOCAL INSPECTION AUTHORITIES.
I. UPON COMPLETION OF THE WORK, THIS CONTRACTOR SHALL FURNISH TO THE ARCHITECT A
CERTIFICATE OF INSPECTION AND APPROVAL FROM THE ABOVE DEPARTMENT BEFORE FINAL
PAYMENT ON CONTRACT WILL BE ALLOWED.
J. TEST ALL WIRING AND CONNECTIONS FOR CONTINUITY AND GROUNDING BEFORE ANY EQUIPMENT
IS CONNECTED. WHEN DIRECTED BY ARCHITECT, DEMONSTRATE BY PROPER VOLTAGE MEGGER
TEST OF INSULATION RESISTANCE OF ANY CONDUCTORS AND REPLACE ALL CONDUCTORS WHICH
FAIL SAID TESTS UNTIL ALL CONDUCTORS ARE FREE FROM INSULATION FAULTS.
K. ELECTRICAL LAYOUTS ARE SCHEMATIC. EXACT LOCATIONS ARE DETERMINED BY EXACT LOCATION
OF EQUIPMENT, ETC., AND MAY BE REVISED TO SUIT THE CONSTRUCTION CONDITIONS AND AID IN
COORDINATION WITH WORK OF OTHER CONTRACTORS.
L. ELECTRICAL DRAWINGS ARE INTENDED TO INDICATE APPROXIMATE LOCATIONS OF SWITCHES,
RECEPTACLES, LIGHTING FIXTURES AND OTHER ITEMS OF VARIOUS ELECTRICAL SYSTEMS OF
PROJECT. EXACT LOCATIONS AND ROUGH-IN DIMENSIONS FOR ALL WORK AND EQUIPMENT SHALL
BE OBTAINED FROM ARCHITECT OR OWNER AS WORK PROGRESSES. SHOULD THE ELECTRICAL
CONTRACTOR FAIL TO PROPERLY OBTAIN SUCH LOCATIONS OR DIMENSIONS, THE CONTRACTOR
SHALL REVISED THE LOCATIONS AT THE CONTRACTOR'S EXPENSE WHEN REQUESTED BY
ARCHITECT OR OWNER. ARCHITECT AND OWNER RESERVE THE RIGHT TO MAKE MINOR CHANGES
IN LOCATION OF ELECTRICAL WORK OR EQUIPMENT PRIOR TO ROUGHING IN WITH NO ADDITIONAL
COST.
M. OWNER RESERVES THE RIGHT TO DIRECT REMOVAL AND REPLACEMENT OF ANY ITEM WHICH DO
NOT PRESENT AN ORDERLY OR REASONABLY NEAT OR WORKMANLIKE APPEARANCE, PROVIDED
THAT SUCH ITEM CAN BE PROPERLY INSTALLED IN SUCH ORDERLY WAY BY METHODS USUAL IN
SUCH WORK. ADDITIONALLY, OWNER WILL DIRECT REMOVAL AND REPLACEMENT OF ANY ITEM
WHICH DOES NOT COMPLY WITH CONTRACT DRAWINGS OR SPECIFICATIONS. SUCH REMOVALS OR
REPLACEMENTS SHALL BE AT THE SOLE DISCRETION OF THE OWNER AND SHALL BE DONE BY
CONTRACTOR, AT THE CONTRACTOR'S EXPENSE, WHEN SO DIRECTED IN WRITING BY THE OWNER.
N. THE MATERIALS AND EQUIPMENT INSTALLED IN THE WORK SHALL MEET THE REQUIREMENTS OF
THE CONTRACT DOCUMENTS AND NO MATERIALS OR EQUIPMENT SHALL BE ORDERED UNTIL
REVIEWED BY THE OWNER.
O. MANUFACTURER'S CATALOG CUTS MAY BE SUBMITTED FOR STANDARD CATALOG LIGHTING
FIXTURES AND OTHER EQUIPMENT. CATALOG CUTS MAY BE MARKED UP TO MEET THE PROJECT
SPECIFICATIONS. CUTS SHALL BE MARKED TO INDICATE MODEL NUMBER, SIZE, TYPE, COLOR,
RATING, ETC., OF THE ITEM TO BE FURNISHED.
P. PROVIDE INSTRUCTION TO OWNER'S OPERATING PERSONNEL AS NECESSARY, SHOWING
LOCATIONS AND PROPER OPERATION OF MAJOR ITEMS OF EQUIPMENT AND SYSTEM
COMPONENTS AND REFERRING TO THE OPERATING INSTRUCTION MANUAL DESCRIBED BELOW AS
A GUIDE.
Q. COMPILE TWO (2) WRITTEN MANUALS OF OPERATING INSTRUCTIONS INCLUDING COPIES OF SHOP
DRAWINGS AND A LISTING OF EQUIPMENT SUPPLIERS. ASSEMBLE IN 8-1/2" X 11" HARD BACKED
INDEXED BINDER. MATERIAL SHALL BE AS FOLLOWS:
1. TITLE PAGE: TITLE OF JOB, TENANT, ADDRESS, DATE OF SUBMISSION, CONTRACTOR, AND
ENGINEER.
2. INDEX.
3. LIST OF MAJOR EQUIPMENT USED IN PROJECT ACCOMPANIED BY CONTRACTOR PURCHASE
ORDER NUMBERS AND SUPPLIERS' NAMES AND ADDRESSES.
4. ONE COPY OF EACH SHOP DRAWING GROUPED BY TYPES OF EQUIPMENT, I.E., LIGHTING
FIXTURES, PANELBOARDS, ETC.
5. SECTION FOR EACH SYSTEM, INCLUDING:
a. BRIEF DESCRIPTION OF SYSTEM OPERATION WITH LOCATION OF MAJOR COMPONENTS.
b. LIST OF ITEMS IN SYSTEM REQUIRING PERIODIC SERVICE. REQUIRES SEPARATE SECTION
FOR EACH OF: ELECTRICAL DISTRIBUTION SYSTEM FROM THE SERVICE ENTRANCE TO
EACH LIGHTING AND POWER PANEL AND OTHER SYSTEMS (I.E. CONTROL SYSTEMS AND
ANY OTHER ELECTRICAL CONTRACTOR SYSTEM LISTED IN THESE SPECIFICATIONS.)
R. ELECTRICAL CONTRACTOR SHALL GUARANTEE HIS WORKMANSHIP AND MATERIAL FOR A PERIOD
OF ONE YEAR FROM DATE OF SUBSTANTIAL COMPLETION AND LEAVE HIS WORK IN PERFECT
ORDER AT COMPLETION.
S. SHOULD DEFECTS DEVELOP WITHIN GUARANTEE PERIOD, THIS CONTRACTOR SHALL, UPON
NOTICE OF SAME, REMEDY DEFECTS AND HAVE DAMAGES TO OTHER WORK OR FURNISHINGS
CAUSED BY DEFECTS OR WORK OR CORRECTING SAME REPAIRED AND/OR REPLACED AT HIS
EXPENSE TO CONDITION BEFORE SUCH DAMAGE.
T. WITHIN 90 DAYS AFTER THE DATE OF SYSTEM ACCEPTANCE, RECORD DRAWINGS OF THE ACTUAL
INSTALLATION SHALL BE PROVIDED TO THE BUILDING OWNER. RECORD DRAWINGS SHALL INCLUDE
AS A MINIMUM THE LOCATION AND RATING OF EACH PIECE OF EQUIPMENT, GENERAL
CONFIGURATION OF WIRE AND CONDUITS INCLUDING SIZES AND ROUTING, ETC.
260519 - LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES
A. CONDUCTORS SHALL BE COPPER. UNLESS NOTED OTHERWISE ON THE DRAWINGS, THE MINIMUM
COPPER WIRE SIZES FOR WET AND DRY AREAS AS DEFINED BY THE NEC.
B. CONDUCTORS USED FOR EMERGENCY LIGHTING CIRCUITS SHALL BE #10 AWG, MINIMUM, AND
SHALL BE RUN IN SEPARATE CONDUIT USED FOR NO OTHER PURPOSE.
C. THE FOLLOWING COLOR CODE SHALL BE USED:
208/120 VOLT
PHASE A BLACK
PHASE B RED
PHASE C BLUE
NEUTRAL WHITE
GROUND GREEN
ISOLATED GROUND GREEN/YELLOW TRACER
260526 - GROUNDING AND BONDING
A. FURNISH AND INSTALL A COMPLETE GROUNDING SYSTEM IN COMPLIANCE WITH ALL
REQUIREMENTS OF THE NATIONAL ELECTRICAL CODE.
B. BOND ALL STRUCTURAL STEEL TO EARTH, GROUND RODS OR PLATES, OR WATER SYSTEM AND
ISOLATED GROUND FOR IT.
C. BOND ALL ROOF MOUNTED EQUIPMENT TO NEC ACCEPTABLE GROUNDS ONLY.
D. A SEPARATE EQUIPMENT GROUNDING CONDUCTOR, MINIMUM SIZE PER NEC TABLE 250.122, SHALL
BE INSTALLED IN ALL FEEDERS, BRANCH CIRCUITS AND CONTROL CIRCUITS. CONDUCTOR
INSULATION SHALL BE GREEN.
E. CONDUIT SYSTEM SHALL BE ELECTRICALLY CONTINUOUS. ALL ENCLOSURES AND NON-CURRENT
CARRYING METALS TO BE GROUNDED. ALL LOCK NUTS MUST CUT THROUGH ENAMELED OR
PAINTED SURFACES ON ENCLOSURES. WHERE ENCLOSURES AND NON-CURRENT CARRYING
METALS ARE ISOLATED FROM THE CONDUIT SYSTEM, USE BONDING JUMPERS WITH APPROVED
CLAMPS.
F. ALL RECEPTACLES SHALL BE BONDED TO A GROUND CONDUCTOR USING A #12 AWG MINIMUM
BONDING JUMPER BETWEEN RECEPTACLE TERMINAL AND GROUND CONDUCTOR.
METAL-TO-METAL CONTACT BETWEEN THE DEVICE YOKE AND THE OUTLET BOX IS NOT
ACCEPTABLE FOR EITHER SURFACE MOUNTED BOXES OR FLUSH TYPE BOXES.
G. LIGHTING FIXTURES SHALL BE GROUNDED BY THE USE OF A PIGTAIL FASTENED ON BARE METAL
THAT IS FREE OF PAINT.
260533 - RACEWAY AND BOXES
A. ELECTRICAL CONDUCTORS SHALL BE ENCLOSED IN CONTINUOUS GROUNDED EMT CONDUIT
RACEWAY SYSTEM EXCEPT AS OTHERWISE NOTED.
B. RACEWAY AND ENCLOSURE SIZES SHALL BE AS SHOWN ON DRAWINGS OR, IF NOT SHOWN, SHALL
BE SIZED TO COMPLY WITH NEC FILL REQUIREMENTS FOR CONDUCTORS ENCLOSED.
C. PULL OR JUNCTION BOXES SHALL BE PROVIDED IN ALL RACEWAY SYSTEMS AT MAXIMUM OF 100
FOOT INTERVALS AND WHERE REQUIRED TO AVOID EXCESSIVE NUMBER OF BENDS, TO FACILITATE
WIRE PULLING OR TO PROVIDE ACCESS TO RACEWAY SYSTEM.
D. RACEWAYS AND ENCLOSURES SHALL BE ADEQUATELY SUPPORTED FROM BUILDING STRUCTURE
WITH APPROVED SUPPORT RODS AND/OR CLAMPS.
E. ALL CONDUIT SHALL BE RIGID HEAVYWALL GALVANIZED STEEL OR THIN WALL EMT WHERE
PERMITTED BY CODE OR AS HEREINAFTER SPECIFIED. PVC SCHEDULE 80 CONDUIT WITH RIGID
GALVANIZED STEEL ELBOWS MAY BE USED UNDER FLOOR SLAB. MINIMUM CONDUIT SIZE SHALL BE
3/4".
F. ALL CONDUIT FITTINGS SHALL BE GALVANIZED MALLEABLE IRON OR STEEL. CONNECTORS AND
COUPLINGS SHALL BE THREADED OR CUPPED SET SCREW TYPE, CONCRETE TIGHT. CONDUIT
BODIES SHALL BE MALLEABLE IRON, THREADED FOR HEAVYWALL CONDUIT AND CUPPED SET
SCREW TYPE FOR EMT, WITH CADMIUM FINISH AND CADMIUM PLATED SHEET STEEL COVERS.
SYNTHETIC RUBBER GASKETS SHALL BE USED UNDER BODY COVERS EXPOSED TO WEATHER. EMT
CONNECTORS SHALL BE INSULATED THROAT TYPE.
G. EMT THIN WALL CONDUIT MAY BE USED INSIDE HOLLOW PARTITIONS, AND ABOVE SUSPENDED
CEILINGS AND EXPOSED ABOVE 8'-0" ABOVE FINISHED FLOOR OR ABOVE PANELBOARDS. EMT
CONDUIT MAY NOT BE USED BURIED IN EARTH OR FILL, IN OR UNDER CONCRETE FLOOR OR IN
POURED CONCRETE CONSTRUCTION. PVC CONDUIT USED UNDER FLOOR SLABS SHALL HAVE
RIGID GALVANIZED STEEL ELLS AND METALLIC CONDUIT ABOVE FLOOR SLAB.
H. CONDUIT SHALL GENERALLY BE CONCEALED WHERE POSSIBLE. NO CONDUIT SHALL BE RUN IN
SLAB, EXCEPT AS REQUIRED FOR FLOOR-MOUNTED DEVICES.
I. EXPOSED CONDUIT WILL BE PERMITTED IN ELECTRIC ROOMS, AND SIMILAR UNFINISHED SPACES,
OVERHEAD IN AREAS WITHOUT CEILINGS AND ELSEWHERE AT THE DISCRETION OF THE OWNER.
J. DURING ROUGHING-IN, CAP ALL CONDUITS WHICH MAY BECOME FOULED WITH FOREIGN MATERIAL.
1. FLEXIBLE CONDUIT SHALL BE USED FOR "MAKEUP" CONNECTIONS TO VIBRATING
EQUIPMENT, MOTORS, AND AS OTHERWISE NECESSARY OR PERMITTED BY CODE. LIGHTING
FIXTURES MAY BE SUPPLIED WITH SHORT LENGTHS (MAX. 6'-0") OF FLEXIBLE CONDUIT.
GROUNDING SHALL BE GREEN GROUNDING CONDUCTOR AS SPECIFIED IN "GROUNDING".
2. FLEXIBLE CONDUIT SHALL BE UL APPROVED 1/2" MINIMUM TRADE SIZE.
3. LIQUID-TIGHT FLEXIBLE CONDUIT AND LIQUID-TIGHT FITTINGS SHALL BE USED IN AREAS
EXPOSED TO THE WEATHER OR EXCESSIVE MOISTURE.
K. NO MORE THAN FOUR (4) 90-DEGREE BENDS WILL BE ALLOWED IN ANY ONE CONDUIT RUN. WHERE
MORE BENDS ARE NECESSARY IN ANY SINGLE RUN, A PULL BOX SHALL BE INSTALLED. PULL BOXES
SHALL ALSO BE INSTALLED IN LONG RUNS AT A MAXIMUM SEPARATION OF 100'-0". ALL CONDUIT
EXCEPT IN CONCRETE SLAB OR EARTH SHALL BE ROUTED PARALLEL OR PERPENDICULAR TO THE
LINES OF THE BUILDING, AND NO OUT-OF-PLUMB OR DIAGONAL LINES WILL BE ACCEPTED.
L. OUTLETS SHALL BE PROVIDED FOR DEVICES, LIGHTING FIXTURES, MOTORS AND
EQUIPMENT CONNECTIONS, SYSTEMS EQUIPMENT CONNECTIONS, SPECIAL OUTLETS, AND
AS OTHERWISE REQUIRED.
260553 - IDENTIFICATION
A. PROVIDE NAMEPLATES ON THE FOLLOWING EQUIPMENT:
B. NAMEPLATES SHALL INDICATE FUNCTION OF EACH DEVICE. NAMEPLATES SHALL BE LAMINATED
PHENOLIC WITH A WHITE SURFACE AND BLACK CORE. USE 1/16" THICK MATERIAL FOR PLATES UP
TO 2" X 4". FOR LARGER SIZES, USE 1/8" THICK MATERIAL.
C. LETTERING SHALL BE CONDENSED GOTHIC. THE SPACE BETWEEN LINES SHALL BE EQUAL TO THE
WIDTH OF THE LETTERS. USE 1/4" MINIMUM HEIGHT LETTERS WHICH OCCUPY FOUR TO THE INCH.
INCREASE LETTER SIZE TO 3/4" ON LARGER PLATES.
D. FASTEN NAMEPLATES TO EQUIPMENT USING ADHESIVE MATERIAL THAT IS INTENDED FOR USE ON
ENAMELED SURFACES. ADHESIVE SHALL BE NON_AGING FOR AN APPLICATION AND USAGE
TEMPERATURE RANGE OF 0 TO 50 DEGREES CELSIUS.
262416 - PANELBOARDS
A. INSTALL MODULAR SWITCHGEAR WHICH INCLUDES PANELBOARDS WITH ALL CIRCUIT BREAKERS,
PLUS CONTROL SYSTEMS FOR HOODS, HVAC AND LIGHTING AS SHOWN ON THE DRAWINGS.
SUBSTITUTIONS OF LOOSE PANELS INSTEAD OF MODULAR SWITCHGEAR IS NOT ALLOWED.
MODULAR SWITCHGEAR SHALL BE LISTED/LABLED BY A RECOGNIZED TESTING LABORATORY.
B. MODULAR SWITCHGEAR SHALL BE PURCHASED FROM ONE OF THE 'SUPPLIER LIST' COMPANIES
(REFER TO ARCHITECTURAL DRAWINGS). NO SUBSTITUTIONS ARE ALLOWED. THIS CONTRACTOR
MUST VERIFY ALL REQUIREMENTS OF MODULAR SWITCHGEAR WITH SUPPLIER PRIOR TO
ORDERING. AT MINIMUM, THIS CONTRACTOR SHALL VERIFY THE FOLLOWING:
1. ANY BREAKER MODIFICATIONS (AMPACITY, NUMBER OF POLES, CONTROL, RATINGS, GFCI,
HACR, SWITCHING DUTY, SHUNT TRIP, ETC.).
2. RELOCATION OF ANY CIRCUITS.
3. AIC RATING REQUIRED, AFTER COORDINATING THIS WITH THE LOCAL UTILITY COMPANY.
4. HVAC (RTU AND HOOD FANS) CONTROL PACKAGE INCLUDED.
5. ANY OTHER SITE SPECIFIC MODIFICATIONS.
C. CIRCUIT BREAKERS SHALL BE QUICK MAKE, QUICK BREAK, BOLT ON, THERMAL MAGNETIC TRIP
(ENCLOSURE COMPENSATED), MOLDED CASE TYPE, UL LISTED. 15 AND 20 AMP SINGLE POLE
BREAKERS SHALL CARRY THE UL "SWD" MARKING.
D. REFER TO PANEL SCHEDULES ON PLANS FOR ADDITIONAL INFORMATION.
E. THIS CONTRACTOR SHALL PROVIDE A TYPED CIRCUIT DIRECTORY CARD MOUNTED IN A FRAME
WITH A CLEAR PLASTIC PROTECTIVE COVER ON INSIDE OF PANEL DOORS.
262713 - ELECTRICAL SERVICE AND METERING
A.METERING EQUIPMENT SHALL BE FURNISHED BY ELECTRICAL UTILITY COMPANY, AND INSTALLED
BY THIS CONTRACTOR. COORDINATE WITH ELECTRIC COMPANY. EQUIPMENT SHALL BE INSTALLED
AS INDICATED IN ONE-LINE DIAGRAM ON THE DRAWINGS.
262726 - WIRING DEVICES
A. FURNISH AND INSTALL WIRING DEVICES, INCLUDING SWITCHES, RECEPTACLES AND POWER
RECEPTACLES, TELEPHONE OUTLET BOXES, COVERPLATES AND BLANK OUTLET PLATES AS
SHOWN OR DESCRIBED ON DRAWINGS. WIRING DEVICES SHALL BE HUBBELL OR EQUIVALENT
PREMIUM SPECIFICATION GRADE AS MANUFACTURED BY BRYANT, EAGLE, SLATER, PASS &
SEYMOUR, OR LEVITON. COLOR SHALL BE AS DIRECTED BY ARCHITECT OR OWNER.
B. RECESSED OUTLET BOXES SHALL BE STAMPED STEEL SUITABLE FOR THE DEVICE INSTALLED.
C. SURFACE MOUNTED OUTLET BOXES SHALL BE CAST IRON SUITABLE FOR THE DEVICE INSTALLED.
D. DUPLEX RECEPTACLES SHALL BE A MINIMUM OF 20 AMPERE RATING.
E. COVERPLATES SHALL BE PLASTIC UNLESS OTHERWISE NOTED. COLOR SHALL BE AS DIRECTED BY
ARCHITECT OR OWNER.
F. COVERPLATES FOR SURFACE MOUNTED BOXES SHALL BE STAMPED STEEL SUITABLE FOR THE
PARTICULAR BOX AND DEVICE CONFIGURATION.
G. WIRING DEVICES UNLESS OTHERWISE PROPERLY AUTHORIZED, SHALL BE SAME MANUFACTURERS
ONLY; NO ADDITIONAL MANUFACTURERS SHALL BE PERMITTED UNLESS SPECIFICALLY
AUTHORIZED BY THE OWNER.
H. LOW VOLTAGE CONTROL DEVICES SHALL BE AS NOTED ON DRAWINGS OR AS REQUIRED.
I. THIS CONTRACTOR SHALL FURNISH AND INSTALL ALL MOTOR CONTROLS, INCLUDING STARTERS,
SAFETY DEVICES AND REMOTE CONTROL STATIONS, UNLESS FURNISHED BY EQUIPMENT
MANUFACTURER IN PRE-WIRED ASSEMBLIES.
J. FURNISH AND INSTALL CONTACTORS, CONTROL RELAYS, PUSHBUTTON STATIONS, SELECTOR
SWITCHES, PILOT LIGHTS, FUSES AND SIMILAR CONTROL AUXILIARIES AS SHOWN ON DRAWINGS
AND/OR REQUIRED TO PROVIDE PROPER CONTROL AND ISOLATION BETWEEN VARIOUS
AUTOMATIC CONTROLLERS AND EQUIPMENT SHOWN ON THE DRAWINGS.
K. ALL CIRCUIT BREAKERS FEEDING MOTOR LOADS SHALL BE HACR TYPE.
L. EQUIPMENT SHALL BE SAME MAKE AS MOTOR STARTERS. PUSHBUTTON STATIONS, SELECTOR
SWITCHES, PILOT LIGHTS: HEAVY DUTY, OIL TIGHT, STANDARD SIZE, WITH TRANSFORMER TYPE
PILOT LIGHTS, FLUSH MOUNTED WHERE PRACTICAL.
M. ANY ACCESS PANELS REQUIRED BUT NOT SPECIFIED OR SHOWN ON DRAWINGS SHALL BE
FURNISHED BY THIS CONTRACTOR WITH DESIGN TO BE APPROVED BY ARCHITECT BEFORE
INSTALLATION.
262813 - FUSES
A. ALL FUSES SHALL BE BUSSMANN, SIZES AS NOTED ON DRAWINGS.
B. ALL FUSES SHALL BE UL LISTED, CURRENT-LIMITING TYPE, MINIMUM 200,000 AMPS INTERRUPTING
CAPACITY.
C. FUSES 1 AMP AND ABOVE SHALL BE BUSSMANN "LOW PEAK" RK-1. 250 VOLT FUSES SHALL BE USED
ON 208/120 VOLT SYSTEMS.
D. CONTROL FUSES FOR MOTOR STARTERS, CONTACTORS, AND CONTROL PANEL TRANSFORMERS
SHALL BE BUSSMANN FNQ-R SIZED AT 500% RATED CURRENT.
E. FURNISH SPARE FUSES TO THE OWNER IN THE FOLLOWING QUANTITIES: 10% OF TOTAL PROJECT
QUANTITY (BUT NOT LESS THAN THREE (3) FOR EACH TYPE AND RATING OF FUSES).
F. TYPED LIST OF ALL SPARES SHALL ALSO BE INCLUDED.
262816 - ENCLOSED SWITCHES AND CIRCUIT BREAKERS
A. DISCONNECT SWITCHES SHALL BE HEAVY-DUTY TYPE, UL LISTED.
B. ALL SWITCHES SHALL HAVE SWITCH BLADES WHICH ARE FULLY VISIBLE IN THE "OFF" POSITION
WHEN THE SWITCH DOOR IS OPEN. SWITCHES SHALL HAVE REMOVABLE ARC SUPPRESSORS
WHERE NECESSARY TO PERMIT EASY ACCESS TO LINE SIDE LUGS. LUGS SHALL BE FRONT
REMOVABLE AND UL LISTED FOR 75 DEGREES C., ALUMINUM OR COPPER WIRES.
C. SWITCHES SHALL BE QUICK-MAKE, QUICK-BREAK. THE OPERATING HANDLE SHALL BE AN INTEGRAL
PART OF THE BOX, NOT THE COVER. PROVISIONS FOR PADLOCKING THE SWITCH IN THE "OFF"
POSITION WITH AT LEAST THREE LOCKS SHALL BE PROVIDED. SWITCHES SHALL HAVE A DUAL
COVER INTERLOCK TO PREVENT UNAUTHORIZED OPENING OF THE SWITCH DOOR WHEN THE
HANDLE IS IN THE "ON" POSITION, AND TO PREVENT CLOSING OF THE SWITCH MECHANISM WITH
THE DOOR OPEN. THE HANDLE POSITION SHALL INDICATE WHETHER THE SWITCH IS "ON" OR "OFF".
D. SWITCHES SHALL BE FURNISHED IN NEMA 1 GENERAL PURPOSE ENCLOSURE EXCEPT ALL
SWITCHES LOCATED OUTDOORS SHALL BE NEMA 3R WEATHERPROOF (WP). NEMA 3R ENCLOSURE
SHALL BE MANUFACTURED FROM GALVANIZED STEEL. ENCLOSURES SHALL HAVE A GRAY BAKED
ENAMEL FINISH, ELECTRODEPOSITED, ON CLEANED, PHOSPHATIZED STEEL.
E. SWITCHES SHALL BE RATED FOR AC. FUSIBLE SWITCHES MUST ACCEPT CLASS R FUSES AND HAVE
PROVISIONS TO REJECT ALL FUSES EXCEPT CLASS R. THE UL LISTED SHORT CIRCUIT RATING OF
THE SWITCHES SHALL BE 200,000 RMS SYMMETRICAL AMPERES WHEN CLASS R FUSES ARE USED.
265100 - INTERIOR LIGHTING
A. INSTALL LIGHTING FIXTURES AS SHOWN ON THE DRAWINGS.
B. ALL FIXTURES SHALL BE LISTED AND LABELED BY UNDERWRITERS LABORATORIES AND ENERGY
STAR AND/OR DLC LISTING.
C. FIXTURES ARE TO BE PROVIDED COMPLETE WITH END AND TRIM PLATES AND ALL MOUNTING
ACCESSORIES REQUIRED FOR A COMPLETE FIXTURE INSTALLATION.
D. USE STEEL WIRE HANGERS FASTENED TO THE BUILDING STRUCTURE TO SUPPORT RECESSED
FIXTURES AT EACH CORNER. (FOUR-CORNER SUSPENDED). FIXTURES TO FIT TIGHT AGAINST
CONSTRUCTION TO ELIMINATE LIGHT LEAKS.
E. WALL-MOUNTED FIXTURES SHALL BE MOUNTED PLUMB WITH BUILDING LINES AND
INSTALLED WITH LIGHTING CONTROL PROPER BOX AND COVER HARDWARE.
F. SURFACE-MOUNTED FIXTURES SHALL COVER MOUNTING HARDWARE. USE A CANOPY THAT IS NO
LONGER THAN THE LENGTH AND WIDTH OF THE FIXTURE AND AT A HEIGHT THAT IS NO HIGHER
THAN REQUIRED TO MOUNT FIXTURE ABSOLUTELY VERTICAL. CANOPY FINISH SHALL MATCH
FIXTURE FINISH.
G. STEM-MOUNTED FIXTURES SHALL BE MOUNTED SO AS TO BE ABSOLUTELY VERTICAL AND
HORIZONTAL. INSTALL AND SUPPORT AS SHOWN ON DRAWINGS.
270510 - TELEPHONE CONDUIT SYSTEM
A. CONDUIT FOR TELEPHONE WALL OUTLETS SHALL BE A MINIMUM OF 3/4" UNLESS NOTED
OTHERWISE.
B. TELEPHONE OUTLET BOXES SHALL BE SINGLE GANG. PLATES SHALL BE FURNISHED AND
INSTALLED BY THIS CONTRACTOR.
C. FURNISH AND INSTALL A 3/4" THICK TELEPHONE BACKBOARD AT LOCATION SHOWN ON THE
DRAWINGS. THE PLYWOOD BACKBOARD SHALL BE SECURELY ATTACHED TO THE BUILDING WALLS
TO SUPPORT RELAY PANELS, TERMINAL BLOCKS AND OTHER HARDWARE WEIGHING
APPROXIMATELY 10 POUNDS PER SQUARE FOOT. PRIME AND PAINT THE BACKBOARD SIDES AND
EDGES WITH TWO COATS OF GRAY FLAMEPROOF PAINT.
D. CONDUIT SYSTEM SHALL BE CONTINUOUS FROM OUTLETS TO TELEPHONE BACKBOARD. INSTALL
PULL STRING IN EMPTY CONDUITS.
E. INSTALL #6 GROUND WIRE FROM TELEPHONE BACKBOARD TO SERVICE ENTRANCE GROUND PER
TELEPHONE COMPANY'S REQUIREMENTS.
270511 - IT INSTALLATION
A. THE CONTRACTOR IS RESPONSIBLE FOR REVIEWING AND UNDERSTANDING WENDY'S
REQUIREMENTS AND FORMS TO ENSURE A TIMELY INSTALLATION OF IT EQUIPMENT. THE
CONTRACTOR SHALL COMPLETE, SIGN, AND RETURN THE IT READINESS FORM AS REQUIRED.
B. THE FOLLOWING ARE THE SITE READINESS MINIMUM REQUIREMENTS.
1. THE INSTALLATION OF ALL KITCHEN EQUIPMENT IS COMPLETE.
2. THE BUILDING HAS PERMANENT POWER.
3. ALL ISOLATED GROUND (IG RECEPTACLES) ARE INSTALLED AND ENERGIZED.
4. THE FRONT COUNTERS ARE COMPLETE AND ENERGIZED.
6. INTERIOR WALLS ARE COMPLETED FOR KIOSKS. ELECTRICAL EQUIP IS INSTALLED &
OPERATIONAL.
7. ELECTRICAL IS INSTALLED AND ENERGIZED & WALLS ARE COMPLETED & READY FOR
QUEUING BOARDS.
8. DRIVE THRU LOOPS ARE INSTALLED TO HME'S SPECIFICATIONS.
9. BUN WARMERS ARE INSTALLED.
10. MWS CART IS ONSITE.
11. HME LOOPS (DRIVE THRU LOOPS) ARE VISIBLE.
C. THE CONTRACTOR SHALL COORDINATE WITH WENDY'S CONSTRUCTION MANAGER, WENDY'S IT
MANAGER, AND WENDY'S IT INSTALLATION CONTRACTOR TO SCHEDULE THE INSTALLATION IN A
TIMELY MANNER.
ELECTRICAL SPECIFICATIONS
12
/
2
2
/
2
0
1
7
4
:
1
3
:
5
2
P
M
79
6
M
e
r
u
s
C
o
u
r
t
St
.
L
o
u
i
s
,
M
O
6
3
0
2
6
T
6
3
6
.
3
4
9
.
1
6
0
0
F
6
3
6
.
3
4
9
.
1
7
3
0
CE
R
T
I
F
I
C
A
T
E
O
F
A
U
T
H
O
R
I
T
Y
N
O
.
3
8
0
0
8/18/2021
SEAL
DESCRIPTIONDATEREV.
ISSUE DATE: 08/17/2021
PROJECT NUMBER: 21-008
DRAWN BY:
CHECKED BY:
SHEET NAME
SHEET NUMBER
MO
O
D
Y
R
D
&
N
2
N
D
E
RE
X
B
U
R
G
,
I
D
8
3
4
4
0
PROJECT TYPE:
SITE NUMBER:
BUILDING TYPE:
OWNER:
BASE VERSION:
DRAWING RELEASE:
PROJECT YEAR:
ASSET TYPE:
CLASSIFICATION:
UPGRADE CLASSIFICATION:
DESIGN TYPE:
#13487
(2.0) SMART 40+
FREESTANDING
NEW
FRANCHISE
2020
NEW BUILD
2021
(2.0) UM BRITE
SUMMER
NEW
SMART 40+
ELECTRICAL
SPECIFICATIONS
E6.1
KH
MJ
All wiring must meet 2017
NEC standards