December 21, 2021
Electrical Narrative
E1.1 – EMT or MC cable assumed in concealed locations. If not accurate please verify.
Response: EMT called out on drawings.
E2.0 – Panic hardware shall be installed as per IBC Section 1010.10.
Response: Panic hardware and note added to back door. Also added a circuit in Panel B.
E3.1 – Available Fault Current calculations.
Response: Fault current calcs added to one-line diagram.
E6.1 – All wiring must meet 2017 NEC standards.
Response: Note added to specifications.