Loading...
HomeMy WebLinkAboutELECTRICAL PLAN - 23-00732 - Good 2 Go - New Commercial BldgA. CONDUIT, CONDUCTORS AND AIC CALCULATIONS FOR ALL SERVICE, PANEL AND EQUIPMENT FEEDERS INDICATED ON THE ONE-LINE HAVE BEEN SIZED BASED ON COPPER. THE CONTRACTOR MAY USE COMPRESSED ALUMINUM CONDUCTORS FOR THESE FEEDERS PROVIDING THE CONDUIT, CONDUCTOR SIZES AND AIC CALCULATIONS ARE ADJUSTED AS REQUIRED TO MEET ALL NATIONAL ELECTRICAL CODE REQUIREMENTS. B. FURNISH AND INSTALL ENGRAVED LABEL ON THE FRONT OF THE MAIN SERVICE EQUIPMENT NOTING THE AVAILABLE FAULT CURRENT VALUE SHOWN. 1. COORDINATE EXACT REQUIREMENTS WITH UTILITY COMPANY PRIOR TO BEGINNING WORK. 2. FURNISH AND INSTALL CONCRETE PAD FOR UTILITY TRANSFORMER PER UTILITY COMPANY'S REQUIREMENTS. 3. ELECTRICAL CONTRACTOR SHALL INSTALL CONDUCTORS EMERGENCY STOP BUTTONS AND TERMINATIONS FOR EMERGENCY STOP COORDINATE REQUIREMENTS WITH FUEL SYSTEM SUPPLIER GENERAL NOTES: 208Y/120, 3Ø, 4W, 800 AMP, MLO, 65K AIC SERVICE ENTRANCE RATED PAD MOUNT TRANSFORMER BY ROCKY MOUNTAIN POWER SYMBOL USED FOR NOTE CALLOUT. KEYED NOTES: 59,482 CONCRETE PAD BY ELECTRICAL CONTRACTOR # 2 MAXIMUM SYMMETRICAL RMS FAULT CURRENT BASED ON 300 KVA TRANSFORMER (TYPICAL OF SYMBOL) PANEL 'CB' 31,252 SHUNT PANEL 'CG' 2- 1 / 2 " - 4 # 3 / 0 , 1 # 6 G M (3 ) 3 " C E A C H W I T H 4# 3 0 0 K C M I L AN D 1 # 1 / 0 G (2) 2"C EACH WITH 4#3/0 KCMIL AND 1#3G SEE GROUNDING DETAIL ON THIS DRAWING 54,442 (4) 4"C EACH WITH 4#350 KCMIL 34,473 31,741 METERED SWITCHBOARD CASHIER FRONT RESTURANT ESTOP ESTOP 1 1 PANEL 'CC' 30,126 208V 1200 AMP 3ø 2- 1 / 2 " - 4 # 4 / 0 , 1 # 4 G PANEL 'CD' 29,078 FRONT C-STORE ESTOP FRONT CANOPY ESTOP 3 3 3 FRONT CANOPY ESTOP 3 3 2- 1 / 2 " - 4 # 3 / 0 , 1 # 6 G 2- 1 / 2 " - 4 # 3 / 0 , 1 # 6 G PARKING LOT ESTOP 3 1 4" UNDERGROUND PRIMARY CONDUIT FROM TRANSFORMER TO UTILITY CONNECTION POINT BY CONTRACTOR AND CONDUCTORS BY ROCKY MOUNTAIN POWER ELECTRICAL CONTRACTOR SHALL PROVIDE PROVIDE FIBER GLASS LONG SWEEP ELBOWS AT ALL ELBOWS AS REQUIRED BY ROCKY MOUNTAIN POWER COORDINATE WITH UTILITY FOR REQUIREMENTS 208Y/120, 3Ø, 4W, 400 AMP, MLO, 22K AIC SERVICE ENTRANCE RATED 15,817 (2) 2"C EACH WITH 4#3/0 KCMIL AND 1#3G 32,972 N G 800 AMP CLASS J 400 AMP CLASS J 400 AMP CLASS J 4. NOTED PANEL TO BE PROTECTED BY BREAKER SERIES RATING. 4 4 4 4 4 PANEL 'MCA' 4 PANEL 'MSA' 208Y/120, 3Ø, 4W, 400 AMP, MLO, 65K AIC SERVICE ENTRANCE RATED 4 PANEL 'MSA' M 1 M 1 54,442 54,442 4" 3/ 4 " - 1 # 3 / 0 G T O M P B TO W A T E R P I P I N G TO T E L E P H O N E 1/ 2 " - 1 # 6 G WALL BRACKET TO B U I L D I N G S T E E L 3/ 4 " - 1 # 3 / 0 G 12" 3/ 4 " - 1 # 3 / 0 G TE R M I N A L B O A R D GROUNDING BUSHING TYPICAL UNO 20' UFER (3)8'x5/8" ROD ELECTRODES NEWTON WALL-MOUNT GROUND BAR OR EQUIVALENT UFER GROUND #4 COPPER FINISHED FLOOR #6 BARE COPPER AS A P P L I C A B L E A. ALL CONDUCTORS SHALL BE IN EMT CONDUIT UNLESS NOTED OTHERWISE. ALL CONDUIT SHALL HAVE A GROUNDING BUSHING AT EACH END. B. ALL CONNECTIONS SHALL BE EXOTHERMIC WELD, LISTED PRESSURE CONNECTORS, LISTED CLAMPS OR OTHER LISTED MEANS. C. PROVIDE BONDING OF GAS PIPING PER NEC 250.104(B)(1). DETAIL GENERAL NOTES: TO E A C H D R Y T R A N S F O R M E R 3/ 4 " - 1 # 3 / 0 G AS A P P L I C A B L E 25 0 . 6 6 FU L L S I Z E 25 0 . 6 6 FU L L S I Z E AL W A Y S #6 C U AL W A Y S 3 / 0 25 0 . 1 0 4 AL W A Y S 3 / 0 25 0 . 1 0 4 250.66 FULL SIZE PROJECT NO. TH E S E P L A N S . D R A W I N G S . A N D D E S I G N S A R E T H E E X C L U S I V E P R O P E R T Y O F R E S I N A R C H I T E C T U R E L L C A N D S H A L L N O T BE R E P R O D U C E D I N A N Y F O RM W I T H O U T W R I T T E N C O N S E N T . A L L R I G H T S R E S E R V E D © 20 2 3 R E S I N A R C H I T E C T U R E . L L C . TH E S E P L A N S . D R A W I N G S . A N D D E S I G N S A R E T H E E X C L U S I V E P R O P E R T Y O F R E S I N A R C H I T E C T U R E L L C A N D S H A L L N O T BE R E P R O D U C E D I N A N Y F O RM W I T H O U T W R I T T E N C O N S E N T . A L L R I G H T S R E S E R V E D © 20 2 3 R E S I N A R C H I T E C T U R E . L L C . ID DA T E DE S C R I P T I O N CONNECT ENGINEERING 1150 HOLLIPARK DRIVE IDAHO FALLS, ID 83401 PHONE: (208) 681-8590 MUSGROVE ENGINEERING 645 W. 25TH STREET IDAHO FALLS, ID 83402 PHONE: (208) 384-0585 MUSGROVE ENGINEERING 234 S. WHISPERWOOD WAY BOISE, ID 83709 PHONE: (208) 384-0585 FROST STRUCTURAL ENGINEERING 1020 LINCOLN RD IDAHO FALLS, ID 83401 PHONE: (208) 227-8404 MECHANICAL / PLUMBING STRUCTURAL ELECTRICAL CIVIL 23-211 E-500 Go o d 2 G o 1 0 4 - R e x b u r g I D TB D R e x b u r g I D 8 3 4 4 0 22007 SINGLE-LINE DIAGRAM NTS1SINGLE-LINE DIAGRAM 1" = 1'-0"2 GROUNDING DETAIL 1 1 1 RE S P O N S E T O A H J 10 / 3 1 / 2 0 2 3 10/31/2023