HomeMy WebLinkAboutINFRASTRUCTURE 10.13.23 - 23-00732 - GOOD 2 GO - Connect Engineering Responses 10-26-23Author Name Author Email Author Phone No.:
Stan Crittenden Stan.Crittenden@rexburg.org 208-372-2314
Joel Gray Joel.Gray@rexburg.org 208-372-2331
Kyle Baldwin Kyle.Baldwin@rexburg.org 208-372-2164
Todd Smith Todd.Smith@rexburg.org 208-372-2181
Description : Good 2 Go - New Commercial Bldg
Address : 1055 S 12th W
Application Type :
Document Filename : INFRASTRUCTURE 10.13.23 - 23-00732 - GOOD 2 GO - New Commercial Bldg.pdf Array
Comment Author Contact Information:
Corrections in the following table need to be applied before a permit can be issued
Review Report
Revisions Required
Page Reference Annotation
Type
Author : Department Status Page Review Comments Applicant Response Comments
7 Callout Todd Smith : Broadband Open 7 What is this "Proposed Conduit" for?
6 Free Text Stan Crittenden : Fire Open 6 IFC 2018 Appendix C
requires maximum distance to a fire hydrant be 225 ft.
6 Callout Kyle Baldwin : P&Z Open 6 Please provide seating quantity for parking requirement
verification.
6 Free Text Joel Gray : PW Open 6 Roadway design required per Development Agreement..
6 Callout Joel Gray : PW Open 6 Sampling port required.
6 Free Text Joel Gray : PW Open 6 Plumbing and site plan don't match.
6 Callout Joel Gray : PW Open 6 Street light required.
7 Callout Joel Gray : PW Open 7 Fire hydrant required near end of water line
# 23-00732
New Commercial Building
Please digitally re-submit all pages of the plan set in response to requested revisions
for our next review cycle, with noted items resolved.
Report Date: 10.23.2023
Approval of plans does not constitute approval of variance from code
Page 1 of 1
Powered by TCPDF (www.tcpdf.org)
Added fire hydrant in southeast
corner of lot. 128' from building
Seating for building added to sheet
C-05. Seating quantity = 40
Road improvements to be submitted
Added call out for sampling port
Site plan now matched plumbing plan
Street light added to improvement drawings
Added fire hydrant
Conduit for future power design.
Developer still coordinating with RMP
The restaurant on the west side of the building is a sit down
restaurant. So only 10 spaces are required per Rexburg code. The