Description : Tagg N Go - Car Wash
Address : 1365 N 2nd E
Application Type :
Document Filename : TaggNGo_Rexburg_PermitSet_091923.pdf Array
Comment Author Contact Information:
Corrections in the following table need to be applied before a permit can be issued
Review Report
Revisions Required
Page Reference Annotation
Type
Author : Department Status Page Review Comments Applicant Response Comments
T-1.0 Free Text Cody Jones : Building Open 1 2018
T-1.0 Free Text Cody Jones : Building Open 1 Site plan needed.
A-1.1 Note Cody Jones : Building Open 3 Concealed spaces are fireblocked/draftstopped per Section
718
A-1.1 Note Cody Jones : Building Open 3 Seating at Tables, Counters and Work Areas comply with IBC
1109.11
A-1.1 Note Cody Jones : Building Open 3 Ventilation is provided as per IBC Section 1203
A-1.1 Note Cody Jones : Building Open 3 Site Grading meets the requirements of IBC Section 1804.4
A-1.1 Note Cody Jones : Building Open 3 Dampproofing/Waterproofing comply with IBC Section 1805
A-1.1 Note Cody Jones : Building Open 3 Exit Lighting and Exit Signs comply with IBC 1008 & 1013
S1.0 Free Text Cody Jones : Building Open 13 Will need prior to building permit
S1.0 Free Text Cody Jones : Building Open 13 Special Inspector to be identified.
T-1.0 Callout Alex Owens : Electrical Open 1 For verification: Idaho is currently under 2017 NEC, not 2020.
# 23-00669
New Commercial Building
Please digitally re-submit all pages of the plan set in response to requested revisions
for our next review cycle, with noted items resolved.
Report Date: 09.25.2023
Approval of plans does not constitute approval of variance from code
Page 1 of 2
Page Reference Annotation
Type
Author : Department Status Page Review Comments Applicant Response Comments
E701 Callout Alex Owens : Electrical Open 34 These requirements (wire size for concrete encased electrode)
surpass NEC requirements. Please verify these requirements
are desired.
T-1.0 Callout Don Allen : Mechanical Open 1 for verification: Idaho state plumbing code 2017
T-1.0 Callout Don Allen : Mechanical Open 1 Foe verification 2018 international mechanical code
Report Date: 09.25.2023
Approval of plans does not constitute approval of variance from code
Page 2 of 2