HomeMy WebLinkAboutREINFORCING STEEL - 23-00669 - Tagg N Go - Car WashInspection Details
Date Contractor Inspector Ambient
Temperature (°F)
Weather Permit Number
11/30/2023 Richardson Concrete Vaughn, Adam 24 Overcast/Chilly 230069
Reinforcing Steel
Is this a reinspection?No
Atlas Personals Performed:Periodic Inspection
Inspected reinforcing steel placement for element:
Exterior Continuous Footing
Inspected reinforcing steel placement at location:
All exterior footings.
Plans used:Structural Clearance as specified?Yes
Drawing No.:S1.0/S2.0
Rebar size as per plans?Yes
Notes:
Octavio with Richardson Concrete was informed of passing results. Email sent to all approved recipients.
Work inspected was:
in compliance
in compliance, except as noted in discrepancies section
reinspection/retesting required
Does this inspection have any discrepancies to open or close?
(if yes see comments section)
No✔
Reinforcing Steel Inspection
ASTM A955
00Report #:
11/30/2023Report Date:
Atlas Technical Consultants, LLC Idaho
Falls
1753 E Precision Drive
Idaho Falls, ID 83402
Phone: (208) 5298242
Client:
Twin Towers, LLC
15464 Midnight view way
Bluffdale, UT 84065
Project:
E232004c
Tagg n Go Carwash, 1365 N 2nd E, Rexburg, ID
1365 NORTH 2ND EAST
Rexburg, ID 83440
This report shall not be reproduced, in full, without prior written approval of Atlas Technical Consultants, LLC.
Results only relate to the items inspected or tested.
Page 1 of 2Page 1 of 1
Inspection Details
Date Contractor Inspector Ambient
Temperature (°F)
Weather Permit Number
02/08/2024 Richardson Concrete Rowley, Daniel 41 Cloudy Not Provided
Reinforcing Steel
Is this a reinspection?No
Atlas Personals Performed:Periodic Inspection
Inspected reinforcing steel placement for element:
Other, See Location Details
Inspected reinforcing steel placement at location:
Conveyer pit drain as seen in Detail 108 of Drawing S3.1
Plans used:Structural Clearance as specified?Yes
Drawing No.:Detail 108 on S3.0
Rebar size as per plans?Yes
Notes:
Atlas representative checked in with Blaine from. Richardson Concrete and was informed of results, emailed all approved recipients.
Work inspected was:
in compliance
in compliance, except as noted in discrepancies section
reinspection/retesting required
Does this inspection have any discrepancies to open or close?
(if yes see comments section)
No✔
Reinforcing Steel Inspection
ASTM A955
02Report #:
02/16/2024Report Date:
Atlas Technical Consultants, LLC Idaho
Falls
1753 E Precision Drive
Idaho Falls, ID 83402
Phone: (208) 5298242
Client:
CkQ Rexburg 2, LLC
PO Box 911839
ST. George, UT 84791
Project:
E232004c
Tagg n Go Carwash, 1365 N 2nd E, Rexburg, ID
1365 NORTH 2ND EAST
Rexburg, ID 83440
These test results are only based upon the actual items observed, sampled, inspected or tested as part of the
Services. Unless noted otherwise, test results comply with the acceptance criteria in the most recent client
approved project plans and specifications. We use the simple acceptance/rejection decision rule; accordingly,
measurement uncertainty is not applied in this determination unless required by project plans and specifications
or specified by contract. This report shall not be reproduced, except in full, without prior written approval from our
company.
Page 1 of 2Page 1 of 1
Inspection Details
Date Contractor Inspector Ambient
Temperature (°F)
Weather Permit Number
02/08/2024 Richardson Concrete Rowley, Daniel 41 Cloudy NA
Reinforcing Steel
Is this a reinspection?No
Atlas Personals Performed:Periodic Inspection
Inspected reinforcing steel placement for element:
Other, See Location Details
Inspected reinforcing steel placement at location:
Conveyer pit drain.
Plans used:Structural Clearance as specified?Yes
Drawing No.:Detail 108 on S3.0
Rebar size as per plans?Yes
Notes:
Atlas Rep informed CkQ Forman of test results. Emailed to all approved recipients.
Work inspected was:
in compliance
in compliance, except as noted in discrepancies section
reinspection/retesting required
Does this inspection have any discrepancies to open or close?
(if yes see comments section)
No✔
Reinforcing Steel Inspection
ASTM A955
00Report #:
02/08/2024Report Date:
Atlas Technical Consultants, LLC Idaho
Falls
1753 E Precision Drive
Idaho Falls, ID 83402
Phone: (208) 5298242
Client:
CkQ Rexburg 2, LLC
PO Box 911839
ST. George, UT 84791
Project:
E232004c
Tagg n Go Carwash, 1365 N 2nd E, Rexburg, ID
1365 NORTH 2ND EAST
Rexburg, ID 83440
These test results are only based upon the actual items observed, sampled, inspected or tested as part of the
Services. Unless noted otherwise, test results comply with the acceptance criteria in the most recent client
approved project plans and specifications. We use the simple acceptance/rejection decision rule; accordingly,
measurement uncertainty is not applied in this determination unless required by project plans and specifications
or specified by contract. This report shall not be reproduced, except in full, without prior written approval from our
company.
Page 1 of 2Page 1 of 1
Inspection Details
Date Contractor Inspector Ambient
Temperature (°F)
Weather Permit Number
02/15/2024 Richardson Concrete Wielang, Andrew 34 Snowing 230069
Reinforcing Steel
Is this a reinspection?No
Atlas Personals Performed:Periodic Inspection
Inspected reinforcing steel placement for element:
Interior Stem Wall
Inspected reinforcing steel placement at location:
Gridlines D2, C2
Gridlines 6 DC, 2 DC. Conveyor trench
Plans used:Structural Clearance as specified?Yes
Drawing No.:S1.0
Rebar size as per plans?Yes
Notes:
Atlas representative checked in with Blaine from Richardson Concrete and informed him of results, emailed all approved recipients
Work inspected was:
in compliance
in compliance, except as noted in discrepancies section
reinspection/retesting required
Does this inspection have any discrepancies to open or close?
(if yes see comments section)
No
Photo Documentation Below
✔
Reinforcing Steel Inspection
ASTM A955
01Report #:
02/16/2024Report Date:
Atlas Technical Consultants, LLC Idaho
Falls
1753 E Precision Drive
Idaho Falls, ID 83402
Phone: (208) 5298242
Client:
CkQ Rexburg 2, LLC
PO Box 911839
ST. George, UT 84791
Project:
E232004c
Tagg n Go Carwash, 1365 N 2nd E, Rexburg, ID
1365 NORTH 2ND EAST
Rexburg, ID 83440
These test results are only based upon the actual items observed, sampled, inspected or tested as part of the
Services. Unless noted otherwise, test results comply with the acceptance criteria in the most recent client
approved project plans and specifications. We use the simple acceptance/rejection decision rule; accordingly,
measurement uncertainty is not applied in this determination unless required by project plans and specifications
or specified by contract. This report shall not be reproduced, except in full, without prior written approval from our
company.
Page 1 of 3Page 1 of 2
Inspection DetailsDateContractor Inspector AmbientTemperature (°F)Weather Permit Number02/15/2024 Richardson Concrete Wielang, Andrew 34 Snowing 230069Reinforcing SteelIs this a reinspection?NoAtlas Personals Performed:Periodic InspectionInspected reinforcing steel placement for element:Interior Stem Wall Inspected reinforcing steel placement at location:Gridlines D2, C2 Gridlines 6 DC, 2 DC. Conveyor trench Plans used:Structural Clearance as specified?YesDrawing No.:S1.0Rebar size as per plans?YesNotes:Atlas representative checked in with Blaine from Richardson Concrete and informed him of results, emailed all approved recipients
Work inspected was:
in compliance
in compliance, except as noted in discrepancies section
reinspection/retesting required
Does this inspection have any discrepancies to open or close?
(if yes see comments section)
No
Photo Documentation Below
Conveyor trench walls
✔
Reinforcing Steel Inspection
ASTM A955
01Report #:
02/16/2024Report Date:
Atlas Technical Consultants, LLC Idaho
Falls
1753 E Precision Drive
Idaho Falls, ID 83402
Phone: (208) 5298242
Client:
CkQ Rexburg 2, LLC
PO Box 911839
ST. George, UT 84791
Project:
E232004c
Tagg n Go Carwash, 1365 N 2nd E, Rexburg, ID
1365 NORTH 2ND EAST
Rexburg, ID 83440
These test results are only based upon the actual items observed, sampled, inspected or tested as part of the
Services. Unless noted otherwise, test results comply with the acceptance criteria in the most recent client
approved project plans and specifications. We use the simple acceptance/rejection decision rule; accordingly,
measurement uncertainty is not applied in this determination unless required by project plans and specifications
or specified by contract. This report shall not be reproduced, except in full, without prior written approval from our
company.
Page 2 of 3Page 2 of 2
Inspection Details
Date Contractor Inspector Ambient
Temperature (°F)
Weather Permit Number
02/15/2024 Richardson conc6 Wielang, Andrew 34 Snowing 230069
Reinforcing Steel
Is this a reinspection?No
Atlas Personals Performed:Periodic Inspection
Inspected reinforcing steel placement for element:
Interior Stem Wall
Inspected reinforcing steel placement at location:
Gridlines D2, C2
Gridlines 6 DC, 2 DC. Conveyor trench
Plans used:Structural Clearance as specified?Yes
Drawing No.:S1.0
Rebar size as per plans?Yes
Notes:
Atlas representative checked in with Blaine from Richardson Concrete and was informed of results, emailed all approved recipients
Work inspected was:
in compliance
in compliance, except as noted in discrepancies section
reinspection/retesting required
Does this inspection have any discrepancies to open or close?
(if yes see comments section)
No
Photo Documentation Below
✔
Reinforcing Steel Inspection
ASTM A955
00Report #:
Reinforcing Steel
02/15/2024Report Date:
Atlas Technical Consultants, LLC Idaho
Falls
1753 E Precision Drive
Idaho Falls, ID 83402
Phone: (208) 5298242
Client:
CkQ Rexburg 2, LLC
PO Box 911839
ST. George, UT 84791
Project:
E232004c
Tagg n Go Carwash, 1365 N 2nd E, Rexburg, ID
1365 NORTH 2ND EAST
Rexburg, ID 83440
These test results are only based upon the actual items observed, sampled, inspected or tested as part of the
Services. Unless noted otherwise, test results comply with the acceptance criteria in the most recent client
approved project plans and specifications. We use the simple acceptance/rejection decision rule; accordingly,
measurement uncertainty is not applied in this determination unless required by project plans and specifications
or specified by contract. This report shall not be reproduced, except in full, without prior written approval from our
company.
Page 1 of 3Page 1 of 2
Inspection DetailsDateContractor Inspector AmbientTemperature (°F)Weather Permit Number02/15/2024 Richardson conc6 Wielang, Andrew 34 Snowing 230069Reinforcing SteelIs this a reinspection?NoAtlas Personals Performed:Periodic InspectionInspected reinforcing steel placement for element:Interior Stem Wall Inspected reinforcing steel placement at location:Gridlines D2, C2 Gridlines 6 DC, 2 DC. Conveyor trench Plans used:Structural Clearance as specified?YesDrawing No.:S1.0Rebar size as per plans?YesNotes:Atlas representative checked in with Blaine from Richardson Concrete and was informed of results, emailed all approved recipients
Work inspected was:
in compliance
in compliance, except as noted in discrepancies section
reinspection/retesting required
Does this inspection have any discrepancies to open or close?
(if yes see comments section)
No
Photo Documentation Below
Conveyor trench walls
✔
Reinforcing Steel Inspection
ASTM A955
00Report #:
Reinforcing Steel
02/15/2024Report Date:
Atlas Technical Consultants, LLC Idaho
Falls
1753 E Precision Drive
Idaho Falls, ID 83402
Phone: (208) 5298242
Client:
CkQ Rexburg 2, LLC
PO Box 911839
ST. George, UT 84791
Project:
E232004c
Tagg n Go Carwash, 1365 N 2nd E, Rexburg, ID
1365 NORTH 2ND EAST
Rexburg, ID 83440
These test results are only based upon the actual items observed, sampled, inspected or tested as part of the
Services. Unless noted otherwise, test results comply with the acceptance criteria in the most recent client
approved project plans and specifications. We use the simple acceptance/rejection decision rule; accordingly,
measurement uncertainty is not applied in this determination unless required by project plans and specifications
or specified by contract. This report shall not be reproduced, except in full, without prior written approval from our
company.
Page 2 of 3Page 2 of 2
Inspection Details
Date Contractor Inspector Ambient
Temperature (°F)
Weather Permit Number
03/19/2024 Richardson Concrete Dale, Mason 27 Sunny 230069
Reinforcing Steel
Is this a reinspection?No
Atlas Personals Performed:Periodic Inspection
Inspected reinforcing steel placement for element:
Interior Slab on Grade
Inspected reinforcing steel placement at location:
North half slab of car wash building.
Plans used:Structural Clearance as specified?Yes
Drawing No.:S2.0, S1.0, S1.1
Rebar size as per plans?Yes
Notes:
Doug with Richardson concrete was informed of results, email sent to all approved recipients.
Work inspected was:
in compliance
in compliance, except as noted in discrepancies section
reinspection/retesting required
Does this inspection have any discrepancies to open or close?
(if yes see comments section)
No✔
Reinforcing Steel Inspection
ASTM A955
00Report #:
03/19/2024Report Date:
Atlas Technical Consultants, LLC Idaho
Falls
1753 E Precision Drive
Idaho Falls, ID 83402
Phone: (208) 5298242
Client:
CkQ Rexburg 2, LLC
PO Box 911839
ST. George, UT 84791
Project:
E232004c
Tagg n Go Carwash, 1365 N 2nd E, Rexburg, ID
1365 NORTH 2ND EAST
Rexburg, ID 83440
These test results are only based upon the actual items observed, sampled, inspected or tested as part of the
Services. Unless noted otherwise, test results comply with the acceptance criteria in the most recent client
approved project plans and specifications. We use the simple acceptance/rejection decision rule; accordingly,
measurement uncertainty is not applied in this determination unless required by project plans and specifications
or specified by contract. This report shall not be reproduced, except in full, without prior written approval from Atlas.
The recording of false, fictitious or fraudulent statements or entries on this document may be punishable as a
felony under Federal Statute.
Page 1 of 2Page 1 of 1
Inspection Details
Date Contractor Inspector Ambient
Temperature (°F)
Weather Permit Number
03/19/2024 Richardson Concrete Dale, Mason 27 Sunny 230069
Reinforcing Steel
Is this a reinspection?No
Atlas Personals Performed:Periodic Inspection
Inspected reinforcing steel placement for element:
Interior Slab on Grade
Inspected reinforcing steel placement at location:
North half slab of car wash building.
Plans used:Structural Clearance as specified?Yes
Drawing No.:S2.0, S1.0, S1.1
Rebar size as per plans?Yes
Notes:
Doug with Richardson concrete was informed of results, email sent to all approved recipients.
Work inspected was:
in compliance
in compliance, except as noted in discrepancies section
reinspection/retesting required
Does this inspection have any discrepancies to open or close?
(if yes see comments section)
No✔
Reinforcing Steel Inspection
ASTM A955
01Report #:
03/19/2024Report Date:
Atlas Technical Consultants, LLC Idaho
Falls
1753 E Precision Drive
Idaho Falls, ID 83402
Phone: (208) 5298242
Client:
CkQ Rexburg 2, LLC
PO Box 911839
ST. George, UT 84791
Project:
E232004c
Tagg n Go Carwash, 1365 N 2nd E, Rexburg, ID
1365 NORTH 2ND EAST
Rexburg, ID 83440
These test results are only based upon the actual items observed, sampled, inspected or tested as part of the
Services. Unless noted otherwise, test results comply with the acceptance criteria in the most recent client
approved project plans and specifications. We use the simple acceptance/rejection decision rule; accordingly,
measurement uncertainty is not applied in this determination unless required by project plans and specifications
or specified by contract. This report shall not be reproduced, except in full, without prior written approval from Atlas.
The recording of false, fictitious or fraudulent statements or entries on this document may be punishable as a
felony under Federal Statute.
Page 1 of 2Page 1 of 1
Reviewed and Approved by: Troy Posio
Project Manager 03/19/2024
Inspection Details
Date Contractor Inspector Ambient
Temperature (°F)
Weather Permit Number
04/01/2024 Richardson Concrete Hedrick, Benjiman 28 Foggy 230069
Reinforcing Steel
Is this a reinspection?No
Atlas Personals Performed:Periodic Inspection
Inspected reinforcing steel placement for element:
Interior Slab on Grade
Inspected reinforcing steel placement at location:
SOG for wash bay.
Plans used:Structural Clearance as specified?Yes
Drawing No.:S2.0
Rebar size as per plans?Yes
Notes:
Doug of Richardson was informed of results. Emailed all approved recipients.
Work inspected was:
in compliance
in compliance, except as noted in discrepancies section
reinspection/retesting required
Does this inspection have any discrepancies to open or close?
(if yes see comments section)
No✔
Reinforcing Steel Inspection
ASTM A955
01Report #:
04/02/2024Report Date:
Atlas Technical Consultants, LLC Idaho
Falls
1753 E Precision Drive
Idaho Falls, ID 83402
Phone: (208) 5298242
Client:
CkQ Rexburg 2, LLC
PO Box 911839
ST. George, UT 84791
Project:
E232004c
Tagg n Go Carwash, 1365 N 2nd E, Rexburg, ID
1365 NORTH 2ND EAST
Rexburg, ID 83440
These test results are only based upon the actual items observed, sampled, inspected or tested as part of the
Services. Unless noted otherwise, test results comply with the acceptance criteria in the most recent client
approved project plans and specifications. We use the simple acceptance/rejection decision rule; accordingly,
measurement uncertainty is not applied in this determination unless required by project plans and specifications
or specified by contract. This report shall not be reproduced, except in full, without prior written approval from Atlas.
The recording of false, fictitious or fraudulent statements or entries on this document may be punishable as a
felony under Federal Statute.
Page 1 of 2Page 1 of 1
Reviewed and Approved by: Troy Posio
Project Manager 04/02/2024
Inspection Details
Date Contractor Inspector Ambient
Temperature (°F)
Weather Permit Number
04/01/2024 Richardson Concrete Hedrick, Benjiman 28 Foggy 230069
Reinforcing Steel
Is this a reinspection?No
Atlas Personals Performed:Periodic Inspection
Inspected reinforcing steel placement for element:
Interior Slab on Grade
Inspected reinforcing steel placement at location:
Interior slab on grade of actual car wash.
Plans used:Structural Clearance as specified?Yes
Drawing No.:S2.0
Rebar size as per plans?Yes
Notes:
Doug of Richardson was informed of results. Emailed all approved recipients.
Work inspected was:
in compliance
in compliance, except as noted in discrepancies section
reinspection/retesting required
Does this inspection have any discrepancies to open or close?
(if yes see comments section)
No✔
Reinforcing Steel Inspection
ASTM A955
00Report #:
Rebar
04/01/2024Report Date:
Atlas Technical Consultants, LLC Idaho
Falls
1753 E Precision Drive
Idaho Falls, ID 83402
Phone: (208) 5298242
Client:
CkQ Rexburg 2, LLC
PO Box 911839
ST. George, UT 84791
Project:
E232004c
Tagg n Go Carwash, 1365 N 2nd E, Rexburg, ID
1365 NORTH 2ND EAST
Rexburg, ID 83440
These test results are only based upon the actual items observed, sampled, inspected or tested as part of the
Services. Unless noted otherwise, test results comply with the acceptance criteria in the most recent client
approved project plans and specifications. We use the simple acceptance/rejection decision rule; accordingly,
measurement uncertainty is not applied in this determination unless required by project plans and specifications
or specified by contract. This report shall not be reproduced, except in full, without prior written approval from Atlas.
The recording of false, fictitious or fraudulent statements or entries on this document may be punishable as a
felony under Federal Statute.
Page 1 of 2Page 1 of 1
Inspection Details
Date Contractor Inspector Ambient
Temperature (°F)
Weather Permit Number
04/25/2024 Richardson Concrete Garyson, Todd 48 Light Rain 230069
Reinforcing Steel
Is this a reinspection?No
Atlas Personals Performed:Periodic Inspection
Inspected reinforcing steel placement for element:
Other, See Location Details
Inspected reinforcing steel placement at location:
Overflow Box Walls, and car wash trench
Plans used:Structural Clearance as specified?Yes
Drawing No.:S2.0
Rebar size as per plans?Yes
Notes:
Blaine with Richardson Concrete was notified verbally that rebar placement was in compliance. Report emailed to approved recipients.
Work inspected was:
in compliance
in compliance, except as noted in discrepancies section
reinspection/retesting required
Does this inspection have any discrepancies to open or close?
(if yes see comments section)
No
Photo Documentation Below
✔
Reinforcing Steel Inspection
ASTM A955
00Report #:
04/25/2024Report Date:
Atlas Technical Consultants, LLC Idaho
Falls
1753 E Precision Drive
Idaho Falls, ID 83402
Phone: (208) 5298242
Client:
CkQ Rexburg 2, LLC
PO Box 911839
ST. George, UT 84791
Project:
E232004c
Tagg n Go Carwash, 1365 N 2nd E, Rexburg, ID
1365 NORTH 2ND EAST
Rexburg, ID 83440
These test results are only based upon the actual items observed, sampled, inspected or tested as part of the
Services. Unless noted otherwise, test results comply with the acceptance criteria in the most recent client
approved project plans and specifications. We use the simple acceptance/rejection decision rule; accordingly,
measurement uncertainty is not applied in this determination unless required by project plans and specifications
or specified by contract. This report shall not be reproduced, except in full, without prior written approval from Atlas.
The recording of false, fictitious or fraudulent statements or entries on this document may be punishable as a
felony under Federal Statute.
Page 1 of 3Page 1 of 2
Inspection DetailsDateContractor Inspector AmbientTemperature (°F)Weather Permit Number04/25/2024 Richardson Concrete Garyson, Todd 48 Light Rain 230069Reinforcing SteelIs this a reinspection?NoAtlas Personals Performed:Periodic InspectionInspected reinforcing steel placement for element:Other, See Location Details Inspected reinforcing steel placement at location:Overflow Box Walls, and car wash trenchPlans used:Structural Clearance as specified?YesDrawing No.:S2.0Rebar size as per plans?YesNotes:Blaine with Richardson Concrete was notified verbally that rebar placement was in compliance. Report emailed to approved recipients.
Work inspected was:
in compliance
in compliance, except as noted in discrepancies section
reinspection/retesting required
Does this inspection have any discrepancies to open or close?
(if yes see comments section)
No
Photo Documentation Below
Overflow Box wall Car wash trench
✔
Reinforcing Steel Inspection
ASTM A955
00Report #:
04/25/2024Report Date:
Atlas Technical Consultants, LLC Idaho
Falls
1753 E Precision Drive
Idaho Falls, ID 83402
Phone: (208) 5298242
Client:
CkQ Rexburg 2, LLC
PO Box 911839
ST. George, UT 84791
Project:
E232004c
Tagg n Go Carwash, 1365 N 2nd E, Rexburg, ID
1365 NORTH 2ND EAST
Rexburg, ID 83440
These test results are only based upon the actual items observed, sampled, inspected or tested as part of the
Services. Unless noted otherwise, test results comply with the acceptance criteria in the most recent client
approved project plans and specifications. We use the simple acceptance/rejection decision rule; accordingly,
measurement uncertainty is not applied in this determination unless required by project plans and specifications
or specified by contract. This report shall not be reproduced, except in full, without prior written approval from Atlas.
The recording of false, fictitious or fraudulent statements or entries on this document may be punishable as a
felony under Federal Statute.
Page 2 of 3Page 2 of 2