FA PLANS REVISED - 22-00795 - Madison Station Apartments - Bldg 1
NOTES: 1. SMOKE DETECTORS SHALL BE NO MORE THAN 30 LINEAR FEET APART IN HALLWAYS 2. SMOKE DETECTORS SHALL BE LOCATED MORE THAN 3' FROM ANY HVAC RETURN OR SUPPLY 3. SMOKE DETECTORS SHALL BE LOCATED NO MORE THAN 5' FROM MAGNETIC DOOR HOLDERS 4. SMOKE DETECTORS SHALL BE LOCATED NO MORE THAN 15 LINEAR FEET FROM THE END/BEGINNING OF A HALLWAY 5. SMOKE DETECTORS SHALL BE PLACED A MINIMUM OF 3' FROM CEILING FANS 6.CANDELA SETTINGS OF HORN/STROBE AND STROBE DEVICES SHALL ADHERE TO 2016 NFPA-72 18.5.5.4 FOR ADEQUATE INTENSITY 7. STROBES AND HORN/STROBES IN HALLWAYS SHALL BE LOCATED NO MORE THAN 15' FROM THE BEGINNING/END OF A HALLWAY AND BE SPACED NO MORE THAN 100' FROM EACH OTHER 8. ADDRESSABLE DETECTORS AND MODULES SHALL HAVE ADDRESSES NOTED ON THE DEVICE AND VISIBLE FROM THE FLOOR 9. ALL HORN/STROBES SHALL BE PLACED ON LOW VOLUME SETTING UNLESS NOTED OTHERWISE 10. VERIFY THAT VERIZON CELLULAR COVERAGE IS ADEQUATE AT FACP LOCATION. IF IT IS NOT WIRE 18 AWG 4 COND FROM FACP TO LOCATION WHERE VERISON CELLULAR SERVICE IS ADEQUATE 11. DUCT SMOKE DETECTORS WITH AUTOMATIC UNIT SHUTDOWN SHALL BE INSTALLED IN ANY UNIT, OR AGGREGATE OF UNITS THAT SUPPLY AIR TO THE SAME AREA, FOR A TOTAL AMOUNT OF AIR FLOW EQUAL TO OR EXCEEDING 2000 CFM. COORDINATE WITH HVAC CONTRACTOR FOR CLARIFICATION 12. ALL CIRCUITS ARE CLASSIFIED AS CLASS B WITH A SURVIVABILITY LEVEL OF 1. FPL IS ACCEPTABLE WHERE PERMITTED BY NFPA-70 AND ABOVE 10' AFF. ALL WIRING BELOW 10' AFF SHALL BE IN CONDUIT OR CONCEALED 13. ALL WIRING IS NOTED WITH WIRING SIZE AND NUMBER OF CONDUCTORS REQUIRED 14. DUCT SMOKE DETECTORS ARE PROVIDED AND INSTALLED BY HVAC CONTRACTOR. PROVIDE SLC TO RTU AND INSTALL MONITOR MODULE IN RTU FOR DUCT SMOKE SUPERVISION. LOCATIONS ARE NOT SPECIFIED ON HVAC PLANS, COORDINATE WITH HVAC CONTRACTOR FOR ALL LOCATIONS OF REQUIRED DUCT SMOKE DETECTORS WHERE REQUIRED. 15. 120 VOLT A/C SMOKE DETECTORS AND CARBON MONOXIDE/SMOKE COMBINATION DETECTORS SHALL BE TIED TO ONE ANOTHER FOR ALARM SOUNDING PURPOSES ON A UNIT-BY-UNIT BASIS. IN THE EVENT OF AN ALARM OR TEST, ONLY THE DETECTORS IN THE UNIT WHERE THE ALARM OR TEST CONDITION OCCURRED SHALL SOUND AN ALARM. 16. SYSTEM SHALL BE INSTALLED IN ACCORDANCE WITH IFC 2018 VERSION, NFPA-72 2019 VERSION AND NFPA-70 (NEC) 2020 VERSION 17. ALL HVAC ROOF TOP UNITS APPEAR TO BE BELOW 2000 CFM AND DO NOT REQUIRE DUCT SMOKE DETECTORS TIED INTO THE FACP. CONTRACTOR SHALL VERIFY THIS WITH THE HVAC CONTRACTOR AND BE RESPONSIBLE FOR INSTALLATION OF DUCT SMOKE DETECTORS THAT ARE TIED INTO THE FACP FOR SHUTDOWN OF THE UNIT AND A SUPERVISORY SIGNAL SENT TO THE FACP. 18. AMBIENT NOISE LEVELS OF ALL BEDROOMS IS APPROXIMATELY 50DB, LIVING SPACES IS APPROXIMATELY 60DB AND COMMON AREAS IS APPROXIMATELY 60DB 19. SMOKE DETECTORS AND CARBON MONOXIDE/SMOKE COMBINATION DETECTORS IN ADA COMPLIANT ROOMS SHALL BE TIED TO ONE ANOTHER FOR ALARM SOUNDING PURPOSES ON A UNIT-BY-UNIT BASIS, IN THE EVENT OF AN ALARM OR TEST, ONLY THE STROBES AND HORN/STOBES IN THE UNIT WHERE THE ALARM OR TEST CONDITION OCCURRED SHALL SOUND AN ALARM. 20. SMOKE DETECTORS IN COMMON/GENERAL AREAS, PULL STATIONS, SPRINKLER FLOWS AND ANY OTHER GENERAL ALARM CONDITION SHALL SOUND ALL STROBES AND HORN/STROBES IN THE FACILITY. 96 ' - 0 " 4' - 2 " 19 ' - 1 0 " 14 ' - 1 1 " 9' - 1 " 9' - 1 " 14 ' - 1 1 " 19 ' - 1 0 " 4' - 2 " W D D W DW DW 1: 2 0 s l o p e 0" / 1 2 " 4' - 2 " 38 ' - 0 " 11 ' - 8 " 16 ' - 6 1 / 4 " 7' - 5 " 1/ 1 6 " / 1 2 " 1: 2 0 s l o p e 14 ' - 0 3 / 4 " 4' - 2 " DW DW W D D W 4' - 2 " 19 ' - 1 0 " 14 ' - 1 1 " 9' - 1 " 96 ' - 0 " 9' - 1 " 14 ' - 1 1 " 19 ' - 1 0 " 4' - 2 " 134'-0" 60'-0" 4'-0" 8" furr-out for gas piping. length of furr- out to be determined by gas meter size. 1 A2.2 W2 1 A3.1 W2 8'-7"23'-3"17'-7"6'-7" 14'-0" 6'-7"17'-7" 60'-0" 23'-3"8'-7"4'-0" 8" furr-out for gas piping. length of furr- out to be determined by gas meter size. W2 W2 UNIT 102 UNIT type 1 W1 IT/ F2 W2 W D W3 W1 W1 W1 fire W3 W2 A6.3 1 W1 A6.2 1 W1 DW UNIT 103 UNIT type 2 W3 W1 1 A3.2 UP UP 1 A3.2 W3 W1 W1 DW UNIT 110 UNIT type 2 DW UNIT 101 UNIT type 3 UNIT 112 UNIT type 3 D W W1 riser F1 W D W3 W2 DW W1 UNIT 111 UNIT type 1 W3 W2 comm riser W2 D W W2 W1 W2 W2 UNIT 104 UNIT type 2 W1 F.E.C. DW W1 W1 W1 F.E.C. DW UNIT 109 UNIT type 2 DW W1 W2 UNIT 106 UNIT type 3 UNIT 107 UNIT type 3 DW W1 W2 A6.1 1 D W W D W3 W3 UNIT 108 UNIT type 1 W D W2 W3 W2 W2 W3 D W W2 W2 UNIT 105 UNIT type 1 W2 4'-0"8'-7"23'-3" 60'-0" 17'-7"6'-7" 14'-0" 134'-0" F.F. 1ST FLOOR SCALE: 1/8" = 1'-0" PLAN NORTH 6'-7"17'-7" 60'-0" W2 23'-3"8'-7"4'-0" W2 14 AWG 2 COND TO FACP NAC 1 185CD LF FACP S F FIRE RISER ASSEMBLY F T 75CD EOL 18AWG 2 COND TO APU NAC 4 LOCATE ABOVE FIRE SPRINKLER FDC APU S 185CD LF 185CD LF 185CD LF 185CD LF 185CD LF 185CD LF 185CD LF 185CD LF 185CD LF 15CD EOL 15CD EOL 14 AWG 2 COND TO APU NAC 1 185CD LF 185CD LF 185CD LF 185CD LF 185CD LF 185CD LF 185CD LF 185CD LF 185CD LF 185CD LF S 120VAC S 120VAC S 120VAC S 120VAC 120VAC 120VAC S S 120VAC S 120VAC 120VAC S 120VAC 120VAC S 120VAC S 120VAC S 120VAC S 120VAC 120VAC S 120VAC 120VAC S 120VAC S 120VAC S 120VAC S 120VAC 120VAC S 120VAC 120VAC S 120VAC S 120VAC 120VAC S 120VAC S 120VAC S 120VAC 120VAC S 120VAC S 120VAC S 120VAC 120VAC S 120VAC CO CO CO CO CO COCOCO CO CO CO CO 5'-0" 10'-0" 15CD N EOL 15CD 14 AWG 2 COND TO FACP NAC 4 18 AWG 2 COND TO FACP SLC 15CD 15CD 15CD 15CD 15CD 15CD 15CD 15CD 15CD 15CD 15CD EOL FIRE ALARM MATRIX GENERAL CAUSE AND EFFECT SOUND ALARM BUILT INTO 120VAC DETECTORS IN UNITS SOUND GENERAL BUILDING ALARM NOTIFY FIRE DEPARTMENT INITIATE SUPERVISORY SIGNAL TO MAINTENANCE DISPLAY EVENT ON FACP DISPLAY DISPLAY EVENT ON REMOTE ANNUNCIATOR DISPLAY ADA ROOM HORN/STROBES AND STROBES MANUAL PULL STATION X X X X GENERAL AREA SMOKE DETECTOR X X X X X 120VAC SMOKE AND C/O DETECTOR X SPRINKLER WATERFLOW X X X X X SPRINKLER TAMPER X X X A/C POWER LOSS X X X LOSS OF BATTERY INTEGRITY X X X GROUND FAULT X X X OPEN NAC CIRCUIT X X X OPEN INITIATING CIRCUIT X X X ADA ROOM SMOKE OR CO ALARM X X X X DATE: SCALE: DRAWN BY: 4S i g h t S e c u r i t y (2 0 8 ) 4 0 3 - 1 4 3 4 4 S i g h t S e c u r i t y @ c a b l e o n e . n e t 69 4 4 B i g B e n d D r i v e , I d a h o F a l l s , I D 8 3 4 0 6 Fi r e , A c c e s s , S e c u r i t y a n d S u r v e i l l a n c e NE W C O N S T R U C T I O N MA D I S O N S T A T I O N A P T S 54 5 - 5 8 9 T R E J O S T , R E X B U R G , I D 8 3 4 4 0 FI R E A L A R M 1 ANN APU FACP F H M M F S T FIRE ALARM CONTROL PANEL REMOTE ANNUNCIATOR NAC POWER SUPPLY FIRE ALARM BELL C/O SMOKE DETECTOR COMBO- SMOKE DETECTOR-120VAC=120 HORN STROBE-LF=LOW FREQUENCY STROBE MANUAL PULL STATION SPRINKLER TAMPER HEAT DETECTOR MAGNETIC DOOR HOLDER MONITOR MODULE SPRINKLER FLOW LEGEND OF SYMBOLS VOLTS A/C CO 120VAC=120 VOLTS A/C 134'-0" 60'-0" 4'-0" 8" furr-out for gas piping. length of furr- out to be determined by gas meter size. 1 A2.2 1 A3.1 8'-7"23'-3"17'-7"6'-7" 14'-0" 6'-7"17'-7" 60'-0" 23'-3"8'-7"4'-0" 8" furr-out for gas piping. length of furr- out to be determined by gas meter size. W2 W2 W2 W2 1'-0" W2 W D W3 fire riser roof below UNIT 202 UNIT type 1 wall below W2 UNIT 211 UNIT type 1 9" / 12" W3 W2 D W W D W3 W2 W3 D W W2 W2 W1 DW UNIT 201 UNIT type 3 UNIT 212 UNIT type 3 DW W1 W1 DW UNIT 203 UNIT type 2 W3 W1 1 A3.2 DN UP UP DN 1 A3.2 W1 W1 DW UNIT 210 UNIT type 2 W3 UNIT 204 UNIT type 2 W1 F.E.C. DW W1 W1 W1 F.E.C. DW UNIT 209 UNIT type 2 W2 W2 DW W1 UNIT 206 UNIT type 3 UNIT 207 UNIT type 3 DW W1 D W W D W3 W3 UNIT 205 UNIT type 1 W2 W D W2 W3 W2 W3 D W UNIT 208 UNIT type 1 W2 W2 W2 W2 4'-0"8'-7"23'-3" 60'-0" 17'-7"6'-7" 14'-0" 134'-0" F.F. 2ND FLOOR SCALE: 1/8" = 1'-0" PLAN NORTH 6'-7"17'-7" 60'-0" W2 23'-3"8'-7"4'-0" 96 ' - 0 " 4' - 2 " 19 ' - 1 0 " 24 ' - 0 " 24 ' - 0 " 19 ' - 1 0 " 4' - 2 " W D D W DW DW 4' - 2 " 38 ' - 0 " 11 ' - 8 " 38 ' - 0 " 4' - 2 " 6' - 2 " DW DW W D D W 4' - 2 " 19 ' - 1 0 " 24 ' - 0 " 96 ' - 0 " 24 ' - 0 " 19 ' - 1 0 " 4' - 2 " 14 AWG 2 COND TO FACP NAC 2 185CD LF 185CD LF 185CD LF 185CD LF 185CD LF 185CD LF 185CD LF 185CD LF 185CD LF 185CD LF 15CD EOL 15CD 14 AWG 2 COND TO APU NAC 2 185CD LF 185CD LF 185CD LF 185CD LF 185CD LF 185CD LF 185CD LF 185CD LF 185CD LF 185CD LF S 120VAC S 120VAC S 120VAC S 120VAC 120VAC 120VAC S 120VAC 120VAC S 120VAC S 120VAC 120VAC S 120VAC 120VAC S 120VAC S 120VAC S 120VAC S 120VAC 120VAC S 120VAC 120VAC S 120VAC S 120VAC S 120VAC S 120VAC 120VAC S 120VAC 120VAC S 120VAC S 120VAC 120VAC S 120VAC S 120VAC S 120VAC 120VAC S 120VAC S 120VAC S 120VAC 120VAC S 120VAC CO CO CO CO CO COCOCO CO CO CO CO 5'-0" 10'-0" 15CD 15CD 15CD 15CD 15CD 15CD EOL 18 AWG 2 COND TO FACP NAC 5 15CD 15CD 15CD 15CD 15CD 15CD EOL 15CD EOL 15CD 18 AWG 2 COND TO APU NAC 5 FACP SLC 2-#18, ADDRESSABLE SMOKE, HEAT DETECTORS, MONITOR, RELAY AND CONTROL MODULES 3-#12 120VAC NAC1 2-#14, COMBINATION OF STROBES AND HORN/STROBES WITH EOL RESISTORS FOR SUPERVISION POTTER AFC-1000 ONE LINE DRAWING NAC2 NAC3 5.1K EOL 185CD 1-1 LF 1-2 LF 1-3 1-4 1-5 LF 1-6 LF 1-7 LF 1-8 1-9 LF NAC4 4-1 15CD 5.1K EOL 1-10 LF 1-11 185CD 185CD 185CD 185CD 185CD 185CD 15CD 5.1K EOL 185CD 2-1 LF 2-2 LF 2-3 LF 2-4 LF 2-5 LF 2-6 LF 2-7 LF 2-8 LF 2-9 LF 2-10 LF 2-11 185CD 185CD 185CD 185CD 185CD 185CD 185CD 185CD 185CD 15CD 5.1K EOL 185CD 3-1 LF 3-2 LF 3-3 LF 3-4 LF 3-5 LF 3-6 LF 3-7 LF 3-8 LF 3-9 LF 3-10 LF 3-11 185CD 185CD 185CD 185CD 185CD 185CD 185CD 185CD 185CD 15CD 2-#14, COMBINATION OF STROBES AND HORN/STROBES WITH EOL RESISTORS FOR SUPERVISION 5.1K EOL 185CD 1-1 LF 1-2 LF 1-3 LF 1-4 LF 1-5 LF 1-6 LF 1-7 LF 1-8 LF 1-9 LF 1-10 LF 1-11 185CD 185CD 185CD 185CD 185CD 185CD 185CD 185CD 185CD 15CD 5.1K EOL 185CD 2-1 LF 2-2 LF 2-3 LF 2-4 LF 2-5 LF 2-6 LF 2-7 LF 2-8 LF 2-9 LF 2-10 LF 2-11 185CD 185CD 185CD 185CD 185CD 185CD 185CD 185CD 185CD 15CD 5.1K EOL 185CD 3-1 LF 3-2 LF 3-3 LF 3-4 LF 3-5 LF 3-6 LF 3-7 LF 3-8 LF 3-9 LF 3-10 LF 3-11 185CD 185CD 185CD 185CD 185CD 185CD 185CD 185CD 185CD 15CD 3-#12 120VAC POTTER PFC-1000 APU 4-#18 FACP P-LINK 4-#18 APU P-LINK 5.1K EOL 4-2 4-3 LF 15CD 185CD 185CD 185CD 15CD 15CD 15CD 15CD 1-12 1-13 1-14 1-15 15CD NAC5 5-1 15CD 5-2 15CD 5-3 15CD 5-4 15CD 5-5 15CD 5-6 15CD 5.1K EOLNAC6 6-1 15CD 6-2 15CD 6-3 15CD 6-4 15CD 6-5 15CD 6-6 15CD I/O1 2-#18, POWER FOR NAPCO COMMUNICATOR 5.1K EOLNAC5 5-1 15CD 5-2 15CD 5-3 15CD 5-4 15CD 5-5 15CD 5-6 15CD 5.1K EOLNAC6 6-1 15CD 6-2 15CD 6-3 15CD 6-4 15CD 6-5 15CD 6-6 15CD 5.1K EOLNAC4 4-1 75CD 4-2 15CD 4-3 15CD 4-4 15CD 4-5 15CD 4-6 15CD 4-7 15CD NAC3 NAC2 NAC1 DATE: SCALE: DRAWN BY: 4S i g h t S e c u r i t y (2 0 8 ) 4 0 3 - 1 4 3 4 4 S i g h t S e c u r i t y @ c a b l e o n e . n e t 69 4 4 B i g B e n d D r i v e , I d a h o F a l l s , I D 8 3 4 0 6 Fi r e , A c c e s s , S e c u r i t y a n d S u r v e i l l a n c e NE W C O N S T R U C T I O N MA D I S O N S T A T I O N A P T S 54 5 - 5 8 9 T R E J O S T , R E X B U R G , I D 8 3 4 4 0 FI R E A L A R M 2 96 ' - 0 " 4' - 2 " 19 ' - 1 0 " 24 ' - 0 " 24 ' - 0 " 19 ' - 1 0 " 4' - 2 " W D D W DW DW 4' - 2 " 38 ' - 0 " 11 ' - 8 " 38 ' - 0 " 4' - 2 " 6' - 2 " DW DW W D D W 4' - 2 " 19 ' - 1 0 " 24 ' - 0 " 96 ' - 0 " 24 ' - 0 " 19 ' - 1 0 " 4' - 2 " 60'-0" 134'-0" 14'-0" 4'-0" 8" furr-out for gas piping. length of furr- out to be determined by gas meter size. 1 A2.2 W2 1 A3.1 W2 8'-7"23'-3"17'-7"6'-7"6'-7"17'-7" 60'-0" 23'-3"8'-7"4'-0" 8" furr-out for gas piping. length of furr- out to be determined by gas meter size. W2 W2 W2 W2 W2 W2 W2W D W3 W2 W3 D W UNIT 302 UNIT type 1 UNIT 311 UNIT type 1 W3 W3 W2 D W W D W2 W1 DW UNIT 301 UNIT type 3 UNIT 312 UNIT type 3 DW W1 W1 DW UNIT 303 UNIT type 2 W3 W1 1 A3.2 1 A3.2 W1 W1 DW UNIT 310 UNIT type 2 W3 UNIT 304 UNIT type 2 W1 F.E.C. DW W1 W1 W1 F.E.C. DW UNIT 309 UNIT type 2 W2 W2 DW W1 UNIT 306 UNIT type 3 2 A3.1 D W W D UNIT 307 UNIT type 3 DW W1 W3 W3 UNIT 305 UNIT type 1 W D W2 W3 W2 W2 W2 W3 UNIT 308 UNIT type 1 D W W2 4'-0"8'-7"23'-3" 60'-0" 17'-7"6'-7" 14'-0" 134'-0" F.F. 3RD FLOOR SCALE: 1/8" = 1'-0" PLAN NORTH 6'-7"17'-7" 60'-0" W2 23'-3"8'-7"4'-0" 14 AWG 2 COND TO FACP NAC 3 185CD LF 185CD LF 185CD LF 185CD LF 185CD LF 185CD LF 185CD LF 185CD LF 185CD LF 185CD LF 15CD EOL 15CD 14 AWG 2 COND TO APU NAC 3 185CD LF 185CD LF 185CD LF 185CD LF 185CD LF 185CD LF 185CD LF 185CD LF 185CD LF 185CD LF S 120VAC S 120VAC S 120VAC S 120VAC 120VAC 120VAC S 120VAC 120VAC S 120VAC S 120VAC 120VAC S 120VAC 120VAC S 120VAC S 120VAC S 120VAC S 120VAC 120VAC S 120VAC 120VAC S 120VAC S 120VAC S 120VAC S 120VAC 120VAC S 120VAC 120VAC S 120VAC S 120VAC 120VAC S 120VAC S 120VAC S 120VAC 120VAC S 120VAC S 120VAC S 120VAC 120VAC S 120VAC CO CO CO CO CO COCOCO CO CO CO CO 5'-0" 10'-0" 15CD EOL 15CD 15CD 15CD 15CD 15CD 18 AWG 2 COND TO FACP NAC 6 15CD EOL 15CD 15CD 15CD 15CD 15CD 18 AWG 2 COND TO APU NAC 6 545 Trejo St MALAD STATION APARTMENTS Imagery ©2023 Airbus, CNES / Airbus, Maxar Technologies, USDA/FPAC/GEO, Map data ©2023 200 ft DATE: SCALE: DRAWN BY: 4S i g h t S e c u r i t y (2 0 8 ) 4 0 3 - 1 4 3 4 4 S i g h t S e c u r i t y @ c a b l e o n e . n e t 69 4 4 B i g B e n d D r i v e , I d a h o F a l l s , I D 8 3 4 0 6 Fi r e , A c c e s s , S e c u r i t y a n d S u r v e i l l a n c e NE W C O N S T R U C T I O N MA D I S O N S T A T I O N A P T S 54 5 - 5 8 9 T R E J O S T , R E X B U R G , I D 8 3 4 4 0 FI R E A L A R M 3