HomeMy WebLinkAboutFA APPLICATION REVISED - 22-00795 - Madison Station Apartments - Bldg 1
IDAHO STATE FIRE MARSHAL
Department of Insurance
700 W. State Street, 3rd Floor
Boise, Idaho 83720-0043
Phone: (208) 334-4370 | www.doi.idaho.gov/sfm
FIRE ALARM PLAN REVIEW APPLICATION
NEW RESUBMITTAL DATE:
NAME OF PROJECT STATE PROJECT
Yes No
ADDRESS OF PROJECT
CITY OF PROJECT COUNTY OF PROJECT
FIRE DEPARTMENT JURISDICTION
OWNER’S INFORMATION
OWNER’S NAME
OWNER’S ADDRESS
CITY STATE ZIP
ALARM CONTRACTOR
CONTRACTOR’S NAME
CONTRACTOR’S ADDRESS
CITY STATE ZIP
CONTACT NAME PHONE NUMBER EMAIL
INSTALLATION CONTRACTOR
CONTRACTOR’S NAME
CONTRACTOR’S ADDRESS
CITY STATE ZIP
Shop drawings for fire alarm systems and emergency communications systems are intended to provide basic
information consistent with the objective of installing a fully operational, code compliant fire alarm system and to
provide the basis for the required record (as-built) drawings.
APPROVAL OF SHOP DRAWINGS IS NOT INTENDED TO IMPLY WAIVER OR MODIFICATION OF ANY REQUIREMENTS OF THE STATE
LAWS OR RULES, INTERNATIONAL FIRE CODE, THE NFPA 72 CODE OR ANY OTHER APPLICABLE CRITERIA.
ANY CHANGES, MODIFICATIONS, ADDENDUMS, AND/OR SUPPLEMENTAL INSTRUCTIONS TO THE APPROVED SET OF PLANS AFTER
DATE OF APPROVAL WILL REQUIRE RESUBMITTAL AND APPROVAL THROUGH THE STATE FIRE MARSHALS OFFICE.
ALL SHOP DRAWINGS SHOULD INCLUDE THE FOLLOWING INFORMATION:
IFC 907.1.2
Shop drawings for fire alarm systems shall be submitted for review and approval prior to system installation, and shall
include, but not limited to, all of the following:
1. A floor plan that indicates the use of all rooms
2. Locations of alarm-initiating devices
3. Locations of alarm notification appliances, including candela ratings for visible alarm notification appliances
4. Design minimum audibility level for occupant notifications
5. Location of fire alarm control unit, transponders and notification power supplies
6. Annunciators
7. Power connection
8. Battery calculations
9. Conductor type and sizes
10. Voltage drop calculations
11. Manufacturers’ data sheets indicating model numbers and listing information for equipment, devices and materials
12. Details of ceiling height and construction
13. The interface of fire safety control functions
14. Classification of the supervising station
IFC 907.2 & NFPA 72, 7.4.4
Shop drawings shall include the following information:
1. Name of protected premises, owner, and occupant (where applicable)
2. Name of installer or contractor
3. Location of protected premises
4. Device legend and symbols in accordance with NFPA 170, or other symbols acceptable to the authority having
jurisdiction
5. Date of issue and any revision dates.
IFC 907.2 & NFPA 72, 7.4.5
Floor plan drawings shall be drawn to an indicated scale and shall include the following information, where applicable for
the particular system:
1.Floor or level identification
2.Point of compass (indication of North)
3.Graphic scale
4.All walls and doors
5.All partitions extending to within 15 percent of the ceiling height (where applicable and when known)
6.Room and area description
7.System devices/component locations
8.Locations of fire alarm primary power disconnecting means
9.Locations of monitor/control interfaces to other systems
10.System riser locations
11.Type and number of system components/devices on each circuit, on each floor or level
12.Type and quantity of conductors and conduit (if used) for each circuit
13.Identification of any ceiling over 10 ft. in height where automatic fire detection is being proposed
14.Details of ceiling geometries, including beams and solid joists, where automatic fire detection is being proposed
15.Where known, acoustic properties of spaces
IFC 907.2 & NFPA 72, 7.4.10
System calculations shall be included as follows:
1.Battery calculations
2.Notification appliance circuit voltage drop calculations
3.Other required calculations, such as line resistance calculations, where required
4Sight Security
6944 Big Bend Drive, Idaho Falls, ID 83406
208.403.1434 Office 208.404.2002 Cell
jasonperron79@gmail.com:trevor@4sightsecurity.org
Madison Station Apartments
Fire Alarm Submittals
545-589 TREJO ST,
Rexburg, ID 83440
System shall be installed and inspected in accordance with NEC, NFPA-72 and IFC
Jason Perron
ID ELE #25206
NICET III #129957
Jasonperron79@gmail.com
Cell – (208) 404-2002
This is new construction for a 36 Unit apartment building. This is a fully sprinklered
building. HVAC plans were not provided, I calculated the estimated CFM via the
electrical load. All air handlers appear to be far less than 2000 CFM per CFM calcs
using 7000VA and 10,000VA electrical loa ds.
Manual Pull Stations in common areas have been removed and strobes in living
areas added per AHJ request.
Project Name: Standby Hours: 24
Alarm Mins: 5
Installed By: Safety Margin:20%
Designed By: SLC Type: Class B
Date: 9/12/2023 NAC Source Voltage: 20.4
Model #: AFC-1000 Max Panel Current (amps): 10
Panel ID:
Location:
Qty Part #Description Each Total Each Total
1 AFC-1000 Analog Addressable FACP 0.130 0.130 0.220 0.220
Panel Standby: 0.130 Panel Alarm: 0.220
1 UD-2000 / UD-1000 0.016 0.016 0.023 0.023
RA-6075 0.020 0.025
RA-6500F 0.020 0.025
LED-16F 0.025 0.025
LED-16F LED Annunciator LED Power*0.015 0.210
CA-6500 0.060 0.100
1 PSN-1000(E)0.015 0.015 0.015 0.015
NOHMI-SLCE-127*0.060 0.060
PAD100-SLCE-127 SLC Expander (9 Max)0.060 0.060
IDC-6 Initating Zone Expander 0.020 0.020
IDC-6 Initating Zone Expander Power*0.020 0.270
RLY-5 Relay Expander 0.025 0.035
RLY-5 Relay Expander Power*0.010 0.135
DRV-50 LED Driver Module 0.025 0.025
DRV-50 LED Driver Module LED Power*0.010 0.215
FCB-1000 Fire Communications Bridge 0.025 0.025
FIB-1000 Fiber Interface Board 0.030 0.030
MC-1000 Multi-Connect Expander 0.010 0.010
SPG-1000 Serial Parallel Gateway 0.040 0.040
*REQUIRED IF USING NOHMI PROTOCOL SLC DEVICES
(Maximum current draw is 1 Amp per P-Link circuit, with 2 amps total)P-LINK Standby: 0.031 P-LINK Alarm: 0.038
*Only enter quantity if PLINK power is being used to power devices
AFC / ARC Series
3 PAD100-PD Analog Photo Smoke 0.000300 0.000900 0.000300 0.000900
PAD100-PHD Analog Photo Smoke/Heat 0.000300 0.000300
PAD100-HD Analog Fixed Temp Heat 0.000300 0.000300
1 PAD100-CD Analog Carbon Monoxide Detector 0.000300 0.000300 0.000300 0.000300
PAD100-DRTS Duct Remote Test Switch 0.010000 0.015000
PAD100-DUCT Addressable Duct Detector 0.000300 0.000300
PAD100-DUCTR*Addressable Duct Detector w/Relay 0.000500 0.000500
1 PAD100-PSSA/PSDA Addressable Pull Station Single/Dual Action 0.000200 0.000200 0.000200 0.000200
PAD100-MIM Micro Input Module 0.000200 0.000200
3 PAD100-SIM Single Input Module 0.000240 0.000720 0.000240 0.000720
1 PAD100-DIM Dual Input Module 0.000240 0.000240 0.000240 0.000240
PAD100-RM Relay Module 0.000240 0.000240
PAD100-OROI One Relay One Input Module 0.000240 0.000240
PAD100-TRTI Two Relay Two Input Module 0.000240 0.000240
PAD100-ZM*Conventional Zone Module 0.000240 0.000240
1 PAD100-NAC*Notification Appliance Circuit 0.000200 0.000200 0.000200 0.000200
PAD100-SM Speaker Module 0.000200 0.000200
PAD100-IM Isolator Module 0.000150 0.000150
PAD100-LED LED Module 0.000240 0.000240
PAD100-LEDK Addressable LED w/ Key Switch 0.000200 0.000200
PAD100-SB*Addressable Sounder Base 0.000200 0.000200
PAD100-LFSB*Addressable Low Frequency Sounder Base 0.000200 0.000200
PAD100-RB*Addressable Relay Base 0.000200 0.000200
PAD100-IB Addressable Isolator Base 0.000150 0.000150
PFC-6000 Series
PSA Analog Photo Smoke 0.000325 0.000325
PSHA Analog Photo Smoke/Heat 0.000325 0.000325
RHA Analog Rate of Rise Heat 0.000325 0.000325
FHA Analog Fixed Temp Heat 0.000325 0.000325
DDA Addressable Duct Detector 0.000325 0.000325
APS-SA/APS-DA Addressable Pull Station Single/Dual Action 0.000325 0.000325
MCM Mini Contact Input Module 0.000325 0.000325
SCM-4 Single Contact Input Module 0.000325 0.001000
DCM-4 Dual Contact Input Module 0.000325 0.001000
TRM-4 Twin Relay Output Module 0.000325 0.001000
CIZM-4 *Conventional Zone Input Mod 0.000325 0.001000
MOM-4 *Monitored Output Module 0.000325 0.001000
ARB *Detector Base w/Relay 0.000325 0.000325
ASB *Detector Base w/Sounder 0.000325 0.000325
SCI **Short Circuit Isolator (Class A)0.000325 0.002340
AIB **Detector Base w/Isolator (Class A)0.000325 0.002340
IM/IB/SCI/AIB Class B **
Standby Alarm
Flush Mount LED Annunciator
Power Expander
SLC Expander (9 Max)
SLC Devices
Class A Module
LCD Annunciator
Flush Mount LCD Annunciator
Standby (amps)
P-LINK (RS-485) (Both P-Link Circuits Combined)
Potter AFC-1000
Battery & Voltage Drop
Calculations
FACP
Madison Station Apartments Bldg #1
1st Floor I.T. Riser Room
Current Draw from Install Manual
Madison Station Apartments #1
Rexburg, ID
4Sight Security
Jason Perron
User assumes all responsibility to ensure the quantities and
current draw values in this worksheet are accurate prior to
submittal.
Alarm (amps)
Standby Alarm
DACT Card
Potter Electric Signal (C)2017 1 of 6 AFC-4000 Battery and Voltage Drop Calculation
1 0.000000 0.000000 0.036000 0.036000
*Requires Aux Power (Configure Below)SLC Standby: 0.002560 SLC Alarm: 0.038560
**
SLC Loop Alarm LED Current
See the installation manual for special considerations when installing IM, IB, AIB,
SCI devices on Class B loops.
Potter Electric Signal (C)2017 2 of 6 AFC-4000 Battery and Voltage Drop Calculation
Standby (amps)Alarm (amps)
Ckt Use Description Total Total
1 Notification 0.00000 2.81700
2 Notification 0.00000 2.78600
3 Notification 0.00000 2.78600
4 Aux Power 0.00000 0.38900
5 Notification 0.00000 0.36000
6 Notification 0.00000 0.36000
NAC Standby:0.00000 NAC Alarm:9.49800
Standby (amps)Alarm (amps)
Ckt Use Description Total Total
1 Aux Power 0.07100 0.20000
2 Unused 0.00000 0.00000
3 Unused 0.00000 0.00000
4 Unused 0.00000 0.00000
I/O Standby:0.07100 I/O Alarm:0.20000
Battery Calculation Summary Standby (amps)Alarm (amps)
Panel Current: 0.13000 0.22000
P-Link Current: 0.03100 0.03800
SLC Device Current: 0.00256 0.03856
NAC Circuit Current: 0.00000 9.49800
I/O Circuit Current: 0.07100 0.20000
SLC Loop Type: Class B Total Standby: 0.234560 Total Alarm: 9.99456
Device Addresses Used:10 Standby Hours: 24 Alarm Mins: 5
Device Addresses Available: 127 AH Required:5.63 AH Required:0.84
10 Total Combined Standby & Alarm Amp Hours Required: 6.47
Safety Margin: 20%
Required Battery AmpHours: 7.76
Battery AmpHours Provided: 12
Note: The cabinet will house two 8 AH or 18 AH batteries. The charging
circuit is rated for up to two 55 AH batteries.
NAC Circuits (See NAC Configuration below)
1ST FLOOR WEST
2ND FLOOR WEST
I/O Circuits (See I/O Configuration below)
FIRE ALARM COMMUNICATOR
#REF!
3RD FLOOR WEST
ADA ROOM NAC MODULE
2ND FLOOR WEST
Potter Electric Signal (C)2017 3 of 6 AFC-4000 Battery and Voltage Drop Calculation
NAC Circuit Configuration & Voltage Drop 8/1/2023
NAC 1 MAX Circuit Current (amps): 3 Source Voltage Used (VDC): 20.4
Usage:Description:
Wire Type Ohms/1000ft Length 1-Way Actual Ohms Max Load (amps)Volts @ EOL Min Volts Req'd
#14 Solid 2.5 200 1.000 2.817 17.58 16
Qty Lookup Type Each Total Each Total
9 HORN/STROBE 0.000000 0.000000 0.269000 2.421000
1 HORN/STROBE 0.000000 0.000000 0.096000 0.096000
5 STROBE 0.000000 0.000000 0.060000 0.300000
Total Standby:0.00000 Total Alarm: 2.81700
NAC 2 MAX Circuit Current (amps): 3 Source Voltage Used (VDC): 20.4
Usage:Description:
Wire Type Ohms/1000ft Length 1-Way Actual Ohms Max Load (amps)Volts @ EOL Min Volts Req'd
#14 Solid 2.5 250 1.250 2.786 16.92 16
Qty Lookup Type Each Total Each Total
10 HORN/STROBE 0.000000 0.000000 0.269000 2.690000
1 HORN/STROBE 0.000000 0.000000 0.096000 0.096000
Total Standby:0.00000 Total Alarm: 2.78600
NAC 3 MAX Circuit Current (amps): 3 Source Voltage Used (VDC): 20.4
Usage:Description:
Wire Type Ohms/1000ft Length 1-Way Actual Ohms Max Load (amps)Volts @ EOL Min Volts Req'd
#14 Solid 2.5 260 1.300 2.786 16.78 16
Qty Lookup Type Each Total Each Total
10 HORN/STROBE 0.000000 0.000000 0.269000 2.690000
1 HORN/STROBE 0.000000 0.096000 0.096000
Total Standby:0.00000 Total Alarm: 2.78600
Note: The cabinet will house two 8 AH or 18 AH batteries. The charging
circuit is rated for up to two 55 AH batteries.
SYSTEM SENSOR CEILING 185CD LF
SYSTEM SENSOR CEILING 15CD
Madison Station Apartments #1
2ND FLOOR WEST
3RD FLOOR WEST
Standby (amps)Alarm (amps)
Standby (amps)
Notification
SYSTEM SENSOR CEILING 185CD LF
Description
Description
Circuit Devices
SYSTEM SENSOR CEILING 15CD
Description
1ST FLOOR WEST
Standby (amps)Alarm (amps)
Alarm (amps)
SYSTEM SENSOR CEILING 15CD
Circuit Devices
SYSTEM SENSOR STROBE
Circuit Devices
Notification
Notification
SYSTEM SENSOR CEILING 185CD LF
Potter Electric Signal (C)2017 4 of 6 AFC-4000 Battery and Voltage Drop Calculation
NAC Circuit Configuration & Voltage Drop (cont'd)
NAC 4 MAX Circuit Current (amps): 3 Source Voltage Used (VDC): 20.4
Usage:Description:
Wire Type Ohms/1000ft Length 1-Way Actual Ohms Max Load (amps)Volts @ EOL Min Volts Req'd
#18 Solid 8.08 130 2.101 0.389 19.58 16
Qty Lookup Type Each Total Each Total
1 HORN/STROBE 0.000000 0.000000 0.269000 0.269000
2 STROBE 0.000000 0.000000 0.060000 0.120000
Total Standby:0.00000 Total Alarm: 0.38900
NAC 5 MAX Circuit Current (amps): 3 Source Voltage Used (VDC): 20.4
Usage:Description:
Wire Type Ohms/1000ft Length 1-Way Actual Ohms Max Load (amps)Volts @ EOL Min Volts Req'd
#18 Solid 8.08 250 4.040 0.360 18.95 16
Qty Lookup Type Each Total Each Total
6 STROBE 0.000000 0.000000 0.060000 0.360000
Total Standby:0.00000 Total Alarm: 0.36000
NAC 6 MAX Circuit Current (amps): 3 Source Voltage Used (VDC): 20.4
Usage:Description:
Wire Type Ohms/1000ft Length 1-Way Actual Ohms Max Load (amps)Volts @ EOL Min Volts Req'd
#18 Solid 8.08 270 4.363 0.360 18.83 16
Qty Lookup Type Each Total Each Total
6 STROBE 0.000000 0.000000 0.060000 0.360000
Total Standby:0.00000 Total Alarm: 0.36000
ADA ROOM NAC MODULEAux Power
Circuit Devices
Description
Description
Description
SYSTEM SENSOR STROBE
Standby (amps)
2ND FLOOR WEST
Notification
Alarm (amps)
SYSTEM SENSOR CEILING 185CD LF
Alarm (amps)Circuit Devices Standby (amps)
SYSTEM SENSOR CEILING 15CD
Notification
Standby (amps)Alarm (amps)
3RD FLOOR WEST
SYSTEM SENSOR STROBE
Circuit Devices
Potter Electric Signal (C)2017 5 of 6 AFC-4000 Battery and Voltage Drop Calculation
I/O Circuit Configuration & Voltage Drop 8/1/2023
I/O 1 MAX Circuit Current (amps): 1 Source Voltage Used (VDC): 20.4
Usage:Description:
Wire Type Ohms/1000ft Length 1-Way Actual Ohms Max Load (amps)Volts @ EOL Min Volts Req'd
#14 Solid 2.5 5 0.025 0.200 20.40 16
Qty Lookup Type Each Total Each Total
1 COMMUNICATOR 0.071000 0.071000 0.200000 0.200000
Total Standby:0.07100 Total Alarm: 0.20000
I/O 2 MAX Circuit Current (amps): 1 Source Voltage Used (VDC): 20.4
Usage:Description:
Wire Type Ohms/1000ft Length 1-Way Actual Ohms Max Load (amps)Volts @ EOL Min Volts Req'd
#N/A 40 #N/A 0.000 #N/A 16
Qty Lookup Type Each Total Each Total
Total Standby:0.00000 Total Alarm: 0.00000
8/1/2023
I/O 3 MAX Circuit Current (amps): 1 Source Voltage Used (VDC): 20.4
Usage:Description:
Wire Type Ohms/1000ft Length 1-Way Actual Ohms Max Load (amps)Volts @ EOL Min Volts Req'd
#N/A #N/A 0.000 #N/A 16
Qty Lookup Type Each Total Each Total
Total Standby:0.00000 Total Alarm: 0.00000
I/O 4 MAX Circuit Current (amps): 1 Source Voltage Used (VDC): 20.4
Usage:Description:
Wire Type Ohms/1000ft Length 1-Way Actual Ohms Max Load (amps)Volts @ EOL Min Volts Req'd
#N/A #N/A 0.000 #N/A 16
Qty Lookup Type Each Total Each Total
Total Standby:0.00000 Total Alarm: 0.00000
Standby (amps)Alarm (amps)
Standby (amps)Alarm (amps)
Madison Station Apartments #1
FIRE ALARM COMMUNICATOR
Unused
NAPCO LTEFIRE
Circuit Devices
Description
Description
Circuit Devices Standby (amps)Alarm (amps)
Unused
Alarm (amps)Standby (amps)
Description
Description
Madison Station Apartments #1
Circuit Devices
Aux Power
Circuit Devices
Unused
Potter Electric Signal (C)2017 6 of 6 AFC-4000 Battery and Voltage Drop Calculation
AFC-1000
Fire Alarm Control Panel
8830135 - REV K • 5/23 PAGE 1 OF 5
Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 • www.pottersignal.com
Description
The AFC-1000 is an expandable analog/addressable releasing fire alarm
system with a total system capacity of 1270 addresses. Additional capacity
on the system is achieved using multi-point SLC modules The control
panel utilizes the exclusive Potter protocol that includes a complete line of
sensors and modules. Each SLC may be comprised of any combination of
smoke sensor, heat detectors or modules and allows for a total of 50 ohms
of impedance and may use any wire compliant with the National Electrical
Code (NEC).
The AFC-1000 has a 10 Amp power supply with six Notification
Appliance Circuits (NACs) and four Input/Output (I/O) circuits. The
NACs are rated at 3 Amps each and the I/Os are rated at 1 Amp each.
Each output is regulated and power limited. In addition, each output is
uniquely programmable and may be configured for steady signal, strobe
synchronization, constant power, door holder power, or releasing. The
strobe synchronization includes Gentex, AMSECO, System Sensor and
Cooper/Wheelock and with the exclusive Quadrasync each output may
have a unique brand and all strobes will flash together.
The NACs may be expanded using the PSN-1000 series intelligent power
supplies. Each PSN-1000 adds another 10 Amps of power, 2 additional
input circuits and the AFC-1000 will support up to 31 power supplies. The
system will synchronize the strobes system wide. In addition, the PSN-
1000E has space to allow the installation of up to six PAD100-SLCE SLC
loop expansion cards. The cards mount on a stacker bracket that allows
access to all SLC circuit connections.
Technical Specifications
Features
• 1,270 addresses available on this analog addressable system
• Additional system capacity achieved via multi-point SLC modules
• 1500 software zones
• NFPA 72 Compliant Smoke Sensitivity Test Built-In
• System Operates as Class A or Class B for SLC, P-Link and NACs
• 10 Amp Power Supply, Expandable to 315 amps
• 6 NACS, Regulated, Rated at 3 Amps each, expandable to 192
• 4 Input/Output (I/O) Circuits for system flexibility rated at 1 Amp each
• Strobe Synchronization and System Wide Sync for Gentex®,
AMSECO®, Cooper Wheelock® and System Sensor® strobes
• Dedicated Alarm, Supervisory and Trouble Relays
• 4,000 Event History Buffer
• Optional two line DACT with UD-2000 that can report General, Zone or
Point Information
• Built in IP communicator
• Ethernet Port for Programming and Network Connectivity
• E-Mail System Status, Reports and Event Information
• Product includes 5 year warranty
Dimensions 18 15/16”W x 27 5/16”H x 4 7/16”D
AC Mains 5.0 Amps @ 120 VAC 50/60 HZ
3.0 Amps @ 240 VAC 50/60 HZ
Enclosure 16 gauge cold rolled steel with removable
locked door with Lexan viewing window
Battery
Standby Current-130 mA
Alarm Current-220 mA
• 10 Amps power for NACs, I/O, and P-Link
• 3 Amps per NAC, regulated
• 1 Amp per I/O circuit, regulated
• Battery Charger range 8-55 Ah
• Battery Charger voltage 27.3 VDC
• P-Link maximum current of 1 Amp
Temperature and
Humidity Range
32° to 120° (0°C to 49°C) with a maximum
humidity of 93% non-condensing.
Standards
• NFPA, 13,15, 16, 17, 17A, 70, 72, and 750
• ANSI/UL 864 - Local (L), Remote Station
(RS), Central Station (CS), Propriety
(PPU), Auxiliary (AUX). Type of Service:
Automatic (A), Manual (M),Water flow
(WF) Sprinkler Supervisory (SS) Type of
Signaling: Digital Alarm Communicator
(DAC), March Time (March), Non Coded
(NC), Reverse Polarity (Rev Pol), Other
Technologies (OT)
• IBC (International Building Code)
S7357165-0328:0509
NYC Fire Dept.
Certificate of Approval
6256
8830136 - REV K • 5/23 PAGE 2 OF 5
Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 • www.pottersignal.com
AFC-1000
Fire Alarm Control Panel
SLC Loop Accessories
SLC Loop Devices
The control panel may be connected with up to 1,270 addressable devices or modules in any combination. The SLC is not restricted by any special
wire requirements and may be wired with any wire that complies with the NEC.
Device Description
PAD Series-PD Analog Photoelectric Smoke Detector is a smoke detector with a listed obscuration of 1.1 to 3.5%/foot. UL 268 7th Edition.
PAD Series-PHD
Combination Analog Photoelectric Smoke/Heat Detector – a smoke detector with a listed obscuration of 1.1 to 3.5 %/foot
obscuration and a fixed temperature range of 135° to 185° F heat detector. Smoke detection compliant with UL 268 7th
Edition.
PAD Series-PCD Combination Photoelectric Smoke/Carbon Monoxide Detector. Smoke detection compliant with UL 268 7th Edition. Carbon
Monoxide detection compliant with UL 2075.
PAD200-PCHD
Combination Photoelectric Smoke/Heat/Carbon Monoxide Detector. Smoke detection compliant with UL 268 7th Edition. Heat
detection with a fixed temperature range of 135° to 185° F and UL 521 7th Edition compliant. Carbon Monoxide detection
compliant with UL 2075.
PAD Series-HD Analog Fixed Temperature (135° - 185°F) or Rate-of-Rise Heat Detector (software selectable).
PAD Series-DUCTR Addressable Duct Smoke Detector with Form C Relay rate at 10Amps @ 250/120VAC or 8 Amps at 30VDC.
PAD Series-DUCT Addressable Duct Smoke Detector.
PAD100-6DB 6” round base that is mountable to an electrical box and wired for connection to the PAD100/200 devices.
PAD100-4DB 4” round base that may be mounted to an electrical box and wired for connection to the PAD100/200 devices.
PAD100-IB Isolator base that interrupts a short in a SLC and prevents the short from affecting protected devices on the loop and used for
connection to the PAD100/200 devices.
PAD100-RB Addressable Relay Base that contains one relay controlled by the SLC. Relay at rated at 2 amps at 30 VDC or 0.5A at
125VAC. For PAD100/200 devices only.
PAD100-SB Addressable Sounder Base that contains an addressable sounder module which allows for configuration of local, group, and/
or all call. For PAD100/200 devices only.
PAD Series-CD Addressable CO gas detector.
PAD200-DD Addressable photoelectric smoke detector for use in DUCT/DUCTR enclosure.
PAD300-DD Addressable photoelectric smoke detector for use in DUCT/DUCTR enclosure or pendant mount applications.
PAD100-LFSB
Addressable Low Frequency Sounder Base that contains an addressable sounder module which allows for configuration
of local, group, and/or all call. The LFSB complies with the Low Frequency Signal Requirements (520 Hz) and used for
connection to the PAD100/200 devices.
PAD100-SPKB Speaker base is a wall or ceiling mount speaker capable of 25 or 70.7 VRMS and is field selectable from 1/8W to 4W and
used for connection with the PAD100/200 devices.
PAD300-6DB 6” round base which is mountable to an electrical box and wired for connection to the PAD300 devices.
PAD300-4DB 4” round base which is mountable to an electrical box and wired for connection to the to the PAD300 devices.
PAD300-IB Isolator base that interrupts a short in a SLC and prevents the short from affecting protected devices on the loop. Used for
connection to the PAD300 devices.
PAD300-RB Addressable Relay Base that contains one relay controlled by the SLC. The Relay is rated 2 amps at 30 VDC or 0.5A at
125VAC and used for connection to the PAD300 devices
PAD300-SB Addressable Sounder Base that contains an addressable sounder module which allows for configuration of local, group, and/or
all call; and used for connection to the PAD300 devices.
PAD300-LFSB
Addressable Low Frequency Sounder Base that contains an addressable sounder module which allows for configuration
of local, group, and/or all call. The LFSB complies with the Low Frequency Signal Requirements (520 Hz) and used for a
connection to the PAD300 devices.
8830136 - REV K • 5/23 PAGE 3 OF 5
Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 • www.pottersignal.com
AFC-1000
Fire Alarm Control Panel
Modules
Device Description
PAD100-MIM Micro Input Module provides a small foot print contact module for mounting inside an enclosure.
PAD100-PSSA Single Action Addressable Pull Station.
PAD100-PSDA Dual Action Addressable Pull Station.
PAD100-SIM Single Input Module is a standard contact module with an LED that mounts into a 4” square electrical box.
PAD100-DIM Dual Input Module is a device that can monitor two distinct inputs with a single device or in a Class A mode.
PAD100-TRTI Two Relay Two Input module provides two form C relays that are individually controlled by the control panel. Each relay is rated for 2
amps at 30VDC or 0.5 amps at 125VAC. Also provides two contact inputs.
PAD100-NAC Notification Appliance Circuit module is an addressable remote appliance circuit controlled by the panel.
PAD100-ZM Zone Module is used to connect conventional 2-wire smoke detectors to the system.
PAD100-IM Module interrupts a short on the SLC and prevents the short from affecting protected devices on the loop.
PAD100-RM Relay Module that provides one form C relay controlled by the control panel. Relay is rated for 2 amps at 30VDC or 0.5 amps at 125VAC.
PAD100-LED Module provides a single addressable LED that is controlled by the control panel.
PAD100-SM Speaker Module provides switching for two audio channels.
PAD100-LEDK Addressable LED and key switch that mounts in a single gang box.
PAD100-DRTS DUCTR Remote Test Switch that mounts in a single gang box and optionally supervised. For use with the PAD100-DUCTR only.
PAD100-OROI One Relay One Input Module provides one form C relay and one input. The relay is rated at 2 amps at 30VDC or 0.5 amps at 125VAC.
8830136 - REV K • 5/23 PAGE 4 OF 5
Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 • www.pottersignal.com
AFC-1000
Fire Alarm Control Panel
SLC Features
Sensor Features
User Interface
Ethernet/I.P. Connection
P-Link
The Potter protocol is a digital protocol with a proven design for
reliability and noise immunity. The system does not require special
cable or conductors for connection of the Signaling Line Circuit
as long as the cable is compliant with NFPA 70 and NFPA 72.
The system allows for Class A or Class B installations as well as
“T-Taps.”Each loop is capable of 127 points, with a max wiring
distance of 10,000 ft.
The sensors through the fire alarm control panel provide a real
time status as to the condition of the system. The smoke detector
sensitivity, heat detector temperature level and drift compensation
are all programmable options. The system also allows for a day/night
mode where the panel automatically adjusts the sensitivity depending
on the time of day. To assist in the reduction of false alarms, the
smoke detectors also have a maintenance warning that sends a trouble
signal when a detector is dirty to the point that it can no longer
maintain the programmed sensitivity.
The AFC-1000 is shipped standard with an Ethernet connection.
This connection is the programming port and may be connected
to a building Wide Area Network (WAN) or Local Area Network
(LAN). Once connected to the Internet, the panel may be selectively
programmed to e-mail alarm conditions, trouble conditions,
supervisory conditions, test, Event History and detector status. An
e-mail may be sent to the panel and the panel will e-mail the event
history, detector status, configuration file or server status to an
authorized E-mail account. In addition, reminders may be set to send
an e-mail for service, testing or other conditions.
In addition, the Ethernet connection is UL listed as an IP
communicator. The IP communicator is listed to report to the UL
listed Sur-Gard III IP receiver. The IP communicator replaces the
traditional less reliable alarm communicator transmitter that utilized
telephone lines. The IP communicator is an active method of
connection and communication to the monitoring station.
The AFC-1000 has a proprietary communication protocol that
communicates through a RS-485 connection to field devices. Up
to 64 devices may be connected to a single P-Link connection. The
P-Link includes the communication terminals and regulated 24 VDC
connection for the field devices. The field devices may be any of the
following:
PAD100-SLCE-Analog/Addressable loop expansion module
SLCE-127 -Nohmi addressable loop expansion module for retrofit
applications.
The fire alarm control panel has a 4 x 40 LCD display to provide
information to the system status. The keypad has navigation keys
to allow manipulation of the Menu on board the panel. The panel is
shipped standard with the following LEDs:
• AC Power - Green
• Alarm - Red
• Earth Fault - Amber
• Supervisory - Amber
• Silenced - Amber
• Trouble - Amber
• Pre-Release - Amber
• Release - Red
The common buttons include a Silence, Reset, Acknowledge, and
Drill. All of the buttons are accessible once the locked door is
opened.
RA-6075R – 2 x 16 LCD annunciator with a key pad in a locked
metal enclosure.
RA-6500R(F) – 4 x 40 LCD annunciator with a key pad in a locked
metal enclosure. Flush mount version available.
LED-16(F) – 16 LED annunciator with common indicators in a
locked metal enclosure. Flush mount version available.
PSN-1000(E) – 10 amp, remote intelligent power supply with
6 NACs, 2 Inputs and a P-Link repeater. This panel is listed in
conjunction with the AFC-100 as releasing circuits
CA-6500 – Class A convertor that converts the SLC, NACs and
P-Link connection
UD-2000 – UL listed, Dual line telephone alarm communicator
DRV-50 – LED driver expander, used to connect up to 50 LEDs in a
graphic display
FCB-1000 – Fire communication bridge, provides remote mounting
of the Ethernet connection
FIB-1000 – Fiber interface module, used to extend P-Link to multi-
mode fiber (2 required)
RLY-5 – Relay module, provides 5 form C relay contacts rated at 3.0
amps 24VDC/125AC
SPG-1000 – Serial parallel gateway, allows for the connection to a
serial or parallel printer
The FIB-1000, FCB-1000 and the SPG-1000 may be installed in the
stacker bracket or ordered with the optional rack mount enclosure.
MC-1000 Multi-Connect allows up to sixty-three AFC series panels
to share a single reporting technology.
IDC-6 – Initiating device circuit provides 6 programmable inputs
AE-2 – Two card expansion cabinet
AE-8 – Eight card expansion cabinet
AE-14 – Fourteen card expansion cabinet
8830136 - REV K • 5/23 PAGE 5 OF 5
Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 • www.pottersignal.com
AFC-1000
Fire Alarm Control Panel
2
7
.
3
2
“
2
6
.
0
0
“
4.41”
3.75“
17.60”
18.91”
BOTTOM
RIGHT SIDE
DEPTH
DE
P
T
H
TOP
LEFT SIDE
Dimensions
Model Description Stock No.
AFC-1000 Fire Alarm Control Panel 3992754
Replacement Board AFC-1000 3992758
Ordering Information
Project Name: Standby Hours: 24
Alarm Mins: 5
Installed By: Batt Efficiency %: 80%
Designed By: SLC Type: Class B
Date: 9/12/2023 NAC Source Voltage: 20.4
Model #: PSN-1000(E)Max Panel Current (amps): 10
Panel ID:
Location:
Qty Part #Description Each Total Each Total
1 PSN-1000(E)Intelligent Power Expander 0.060 0.060 0.200 0.200
Panel Standby: 0.060 Panel Alarm: 0.200
RA-6075 0.020 0.025
RA-6500 0.020 0.050
LED-16 0.025 0.025
LED-16*0.015 0.210
PSN-1000(E)0.015 0.015
SLCE-127 0.060 0.060
RLY-5 Relay Expander 0.025 0.035
RLY-5*Relay Expander Power*0.010 0.135
DRV-50 LED Driver Module 0.025 0.025
DRV-50*LED Driver Module LED Power*0.010 0.215
FCB-1000 Fire Communications Bridge 0.025 0.025
FIB-1000 Fiber Interface Board 0.030 0.030
SPG-1000 Serial Parallel Gateway 0.040 0.040
(Maximum current draw on P-Link limited to 1 Amp)P-LINK Standby: 0.000 P-LINK Alarm: 0.000
PSA Analog Photo Smoke 0.000325 0.000325
PSHA Analog Photo Smoke/Heat 0.000325 0.000325
RHA Analog Rate of Rise Heat 0.000325 0.000325
FHA Analog Fixed Temp Heat 0.000325 0.000325
DDA Addressable Duct Detector 0.000325 0.000325
APS-SA/DA Addressable Pull Station 0.000325 0.000325
MCM Mini Contact Input Module 0.000325 0.000325
SCM-4 Single Contact Input Module 0.000325 0.001000
DCM-4 Dual Contact Input Module 0.000325 0.001000
TRM-4 Twin Relay Output Module 0.000325 0.001000
CIZM-4 *Conventional Zone Input Mod 0.000325 0.001000
MOM-4 *Monitored Output Module 0.000325 0.001000
ARB *Detector Base w/Relay 0.000325 0.000325
ASB *Detector Base w/Sounder 0.000325 0.000325
SCI **Short Circuit Isolator (Class A)0.000325 0.002340
AIB **Detector Base w/Isolator (Class A)0.000325 0.002340
SCI/AIB Class B **Current Draw from Install Manual
0 SLC Loop Alarm LED Current 0.000000 0.000000 0.027000 0.000000
*Requires Aux Power (Configure Below)SLC Standby:0.000000 SLC Alarm: 0.000000
**See the installation manual for special considerations when installing AIB, SCI devices on Class B loops.
*Only enter quantity if PLINK power is being used to power devices
Alarm (amps)
Standby Alarm
Standby Alarm
User assumes all responsibility to ensure the quantities and
current draw values in this worksheet are accurate prior to
submittal.
Madison Station Apartments #1
Rexburg, ID
4Sight Security
Jason Perron
LCD Annunciator
SLC Expander (7 Max)
P-LINK (RS-485)
SLC Devices
Standby (amps)
LED Annunciator
LED Annunciator Power*
Power Expander
PSN-1000(E)
Battery & Voltage Drop
Calculations
Panel
Madison Station Bldg #1
1st Floor I.T. Riser Room
LCD Annunciator
Potter Electric Signal (C)2011 1 of 5 PSN-1000(E) Battery and Voltage Drop Calculation
NAC Circuits (See NAC Configuration below)Standby (amps)Alarm (amps)
Ckt Use Description Total Total
1 Notification 1ST FLOOR EAST 0.00000 2.78600
2 Notification 2ND FLOOR EAST 0.00000 2.78600
3 Notification 3RD FLOOR EAST 0.00000 2.78600
4 Notification 1ST FLOOR EAST 0.00000 0.55800
5 Notification 2ND FLOOR EAST 0.00000 0.36000
6 Notification 3RD FLOOR EAST 0.00000 0.36000
NAC Standby:0.00000 NAC Alarm:9.63600
Battery Calculation Summary Standby (amps)Alarm (amps)
Panel Current: 0.06000 0.20000
P-Link Current: 0.00000 0.00000
SLC Device Current: 0.00000 0.00000
NAC Circuit Current: 0.00000 9.63600
SLC Loop Type: Class B Total Standby: 0.060000 Total Alarm: 9.83600
Point Capacity Needed: 0 Standby Hours: 24 Alarm Mins: 5
Point Capacity Actual: 0 AH Required:1.44 AH Required:0.82
Total Combined Standby & Alarm AmpHours Required: 2.26
Efficiency Factor: 80%
Required Battery AmpHours: 2.83
Battery AmpHours Provided: 7
See the installation manual for special considerations when installing AIB, SCI devices on Class B loops.
Potter Electric Signal (C)2011 2 of 5 PSN-1000(E) Battery and Voltage Drop Calculation
NAC Circuit Configuration & Voltage Drop Madison Station Apartments #1 8/1/2023
NAC 1 MAX Circuit Current (amps): 3 Source Voltage Used (VDC): 20.4
Usage:Description:
Wire Type Ohms/1000ft Length 1-Way Actual Ohms Max Load (amps)Volts @ EOL Min Volts Req'd
#14 Solid 2.5 250 1.250 2.786 16.92 16
Circuit Devices Standby (amps)Alarm (amps)
Qty Lookup Type Desc Each Total Each Total
10 HORN/STROBE 0.000000 0.000000 0.269000 2.690000
1 HORN/STROBE 0.000000 0.000000 0.096000 0.096000
Total Standby:0.00000 Total Alarm: 2.78600
NAC 2 MAX Circuit Current (amps): 3 Source Voltage Used (VDC): 20.4
Usage:Description:
Wire Type Ohms/1000ft Length 1-Way Actual Ohms Max Load (amps)Volts @ EOL Min Volts Req'd
#14 Solid 2.5 280 1.400 2.786 16.50 16
Circuit Devices Standby (amps)Alarm (amps)
Qty Lookup Type Desc Each Total Each Total
10 HORN/STROBE 0.000000 0.000000 0.269000 2.690000
1 HORN/STROBE 0.000000 0.000000 0.096000 0.096000
Total Standby:0.00000 Total Alarm: 2.78600
Notification
SYSTEM SENSOR CEILING 185CD LF
SYSTEM SENSOR CEILING 15CD
SYSTEM SENSOR CEILING 185CD LF
SYSTEM SENSOR CEILING 15CD
Notification 1ST FLOOR EAST
2ND FLOOR EAST
Potter Electric Signal (C)2011 3 of 5 PSN-1000(E) Battery and Voltage Drop Calculation
NAC Circuit Configuration & Voltage Drop (cont'd)Madison Station Apartments #1 8/1/2023
NAC 3 MAX Circuit Current (amps): 3 Source Voltage Used (VDC): 20.4
Usage:Description:
Wire Type Ohms/1000ft Length 1-Way Actual Ohms Max Load (amps)Volts @ EOL Min Volts Req'd
#14 Solid 2.5 315 1.575 2.786 16.01 16
Circuit Devices Standby (amps)Alarm (amps)
Qty Lookup Type Desc Each Total Each Total
10 HORN/STROBE 0.000000 0.000000 0.269000 2.690000
1 HORN/STROBE 0.000000 0.000000 0.096000 0.096000
Total Standby:0.00000 Total Alarm: 2.78600
NAC 4 MAX Circuit Current (amps): 3 Source Voltage Used (VDC): 20.4
Usage:Description:
Wire Type Ohms/1000ft Length 1-Way Actual Ohms Max Load (amps)Volts @ EOL Min Volts Req'd
#18 Solid 6.4 220 2.816 0.558 18.83 16
Circuit Devices Standby (amps)Alarm (amps)
Qty Lookup Type Desc Each Total Each Total
1 WGEC24-75WR 0.000000 0.000000 0.198000 0.198000
6 STROBE 0.000000 0.000000 0.060000 0.360000
Total Standby:0.00000 Total Alarm: 0.55800
75CD HIGH DB
SYSTEM SENSOR STROBE
Notification
Notification
SYSTEM SENSOR CEILING 185CD LF
SYSTEM SENSOR CEILING 15CD
1ST FLOOR EAST
3RD FLOOR EAST
Potter Electric Signal (C)2011 4 of 5 PSN-1000(E) Battery and Voltage Drop Calculation
NAC Circuit Configuration & Voltage Drop (cont'd)Madison Station Apartments #1 8/1/2023
NAC 5 MAX Circuit Current (amps): 3 Source Voltage Used (VDC): 20.4
Usage:Description:
Wire Type Ohms/1000ft Length 1-Way Actual Ohms Max Load (amps)Volts @ EOL Min Volts Req'd
#18 Solid 6.4 260 3.328 0.360 19.20 16
Circuit Devices Standby (amps)Alarm (amps)
Qty Lookup Type Desc Each Total Each Total
6 STROBE 0.000000 0.000000 0.060000 0.360000
Total Standby:0.00000 Total Alarm: 0.36000
NAC 6 MAX Circuit Current (amps): 3 Source Voltage Used (VDC): 20.4
Usage:Description:
Wire Type Ohms/1000ft Length 1-Way Actual Ohms Max Load (amps)Volts @ EOL Min Volts Req'd
#18 Solid 6.4 300 3.840 0.360 19.02 16
Circuit Devices Standby (amps)Alarm (amps)
Qty Lookup Type Desc Each Total Each Total
6 STROBE 0.000000 0.000000 0.060000 0.360000
Total Standby:0.00000 Total Alarm: 0.36000
SYSTEM SENSOR STROBE
Notification
SYSTEM SENSOR STROBE
Notification 2ND FLOOR EAST
3RD FLOOR EAST
Potter Electric Signal (C)2011 5 of 5 PSN-1000(E) Battery and Voltage Drop Calculation
PSN-1000(E)
Power Expander
8830032 - REV E • 04/20 PAGE 1 OF 2
Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 • www.pottersignal.com
7165-0328: 0195 S2930
Description
The PSN-1000 series is a UL listed intelligent 10 amp notification
power supply and P-Link (RS-485) repeater. The power supply
connects to the P-Link bus from the control panel and is operated and
supervised from the panel. The power supply may be installed 6,500
feet from the control panel. The PSN-1000 then repeats the P-Link
communication for another 6,500 feet.
The power supply has six (6) Class B or three (3) Class A power
outputs. Each output is regulated and power limited with a 3
Amp maximum rating. In addition, the PSN-1000 has two (2)
programmable dry contact inputs. The dry contact inputs are Class B,
supervised inputs.
The power supply operates on either 120 or 220 VAC power and
has a regulated 24 VDC output. In addition, the panel can charge
up to 55 AH batteries and will house 18 AH batteries. The cabinet
is constructed out of 18 gauge cold rolled steel with a durable
red powder coat finish. A standard Potter key lock is provided for
securing the door. Electrical conduit knockouts are provided on the
sides and top providing installers with multiple options for installing
conduits and providing proper power separations.
The PSN-1000 is a self contained intelligent power supply/P-Link
repeater complete with cabinet. The PSN-1000E is the intelligent
power supply/P-Link repeater with additional cabinet roomfor
mounting stacker bracket modules including PAD100-SLCE loop
expanders. Both cabinets include space for 18 AH batteries.
Features
• 10 Amp Power Supply
• 3 Amps, regulated per NAC
• 6 NACs Class B or 3 NACs Class A
• 2 dry contact inputs
• Fully programmable and monitored through control panel
• Isolated P-Link repeater connection, Class A or B
• Up to 31 power supplies per control panel with system wide
sync
• Quadrasync feature synchronizes strobes from AMSECO,
Gentex, Cooper-Wheelock and System Sensor.
Size (H x W x D)PSN-1000: 16 3/4"x 16 1/8" x 3 1/2"
PSN-1000 E: 26" x 17.6" x 3.75"
Enclosure Sixteen (16) gauge sheet steel with hinged, locked doors
Power Input 120 VAC at 50 HZ240 VAC at 60 HZ5.1 Amps/3.0 Amps max draw
Current Standby 60 mA
Alarm 200 mA
Temperature 32° to 120°F, humidity 93% non-condensing
Compatible Panles
IPA Series, AFC/ARC Series, PFC-4064,
P Series*, PFC-6000 Adressable Series*
* Legacy Product
Technical Specifications
The power supplies are programmed and controlled through the main
control panel P-Link bus. The panel displays any troubles or off
normal conditions of the power supply and the events are stored in
the panel history buffer.
Each output can be independently configured to provide one of four
synchronization patterns, Amseco®, Gentex®, Cooper Wheelock®
and System Sensor®. The ouputs can be also configured for constant
power, resettable power, sounder base power, door holder power
(with or without a low AC drop out), ANSI temporal Code 3, City Tie
or be a releasing circuit for 24vdc solenoids.
8830032 - REV E • 04/20 PAGE 2 OF 2
Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 • www.pottersignal.com
PSN-1000(E)
Power Expander
Ordering Information
Model Description Stock No.
PSN-1000 Power Expander Standard
Cabinet
3992662
PSN-1000(E)Power Expander Large Cabinet 3992665
PAD100-DIM
Dual Input Module
8830082 - REV D • 12/18 page 1 OF 2
potter electric Signal Company, LLC • St. Louis, MO • phone: 800-325-3936 • www.pottersignal.com
Description
The paD100-DIM uses one (1) SLC loop address when monitoring
two (2) Class B circuits or one (1) Class a circuit. The module mounts
on either a 4” square or double gang box. The module is capable
of monitoring two (2) separate class B circuits making it ideal for
PRQLWRULQJ VSULQNOHU ZDWHUÀRZ DQG YDOYH WDPSHU VZLWFKHV ZKHQ WKH\
DUH ORFDWHG LQ WKH VDPH SUR[LPLW\ 7KH 3$'',0 LQFOXGHV RQH UHG
LeD to indicate the module’s status. In normal condition, the LeD
ÀDVKHV ZKHQ WKH GHYLFH LV EHLQJ SROOHG E\ WKH FRQWURO SDQHO :KHQ DQ
LQSXW LV DFWLYDWHG WKH /(' ZLOO ÀDVK DW D IDVW UDWH
Application
The paD100-DIM is compatible with potter’s Ipa and aFC/aRC
VHULHV DGGUHVVDEOH ¿UH DODUP FRQWURO SDQHOV 7KH 3$'',0 LV DQ
LQWHUIDFH PRGXOH XVHG WR PRQLWRU GU\ FRQWDFW GHYLFHV VXFK DV VSULQNOHU
ZDWHUÀRZ YDOYH WDPSHU VZLWFKHV RU FRQYHQWLRQDO SXOO VWDWLRQV 7KH
module is capable of monitoring two separate Class B or one Class a
circuits.
Setting the Address
(DFK DGGUHVVDEOH 6/& GHYLFH PXVW EH DVVLJQHG DQ DGGUHVV 7KH
DGGUHVV LV VHW XVLQJ WKH ',3 VZLWFK ORFDWHG RQ WKH 3$'',0 :KHQ
WKH 3$' ',0 LV XVHG WR PRQLWRU WZR LQGLYLGXDO &ODVV % FLUFXLWV
D VLQJOH GHYLFH DGGUHVV LV DVVLJQHG HDFK LQSXW LV WKHQ LGHQWL¿HG DV D
sub-point of the module address. For example, if the address number
LV DVVLJQHG DV ³´ WKH ¿UVW LQSXW ZLOO EH ³´ DQG WKH VHFRQG LQSXW
will be “8.2”.
%HIRUH FRQQHFWLQJ D GHYLFH WR WKH 6/& ORRS WDNH WKH IROORZLQJ
SUHFDXWLRQV WR SUHYHQW SRWHQWLDO GDPDJH WR WKH SDQHO RU GHYLFH
1. 3RZHU WR WKH GHYLFH LV UHPRYHG
2. )LHOG ZLULQJ LV FRUUHFWO\ LQVWDOOHG
3. Field wiring has no open or short circuits.
Technical Specifications
Operating Voltage 24.0V
0D[ 6/& 6WDQGE\ Current ȝ$
Max SLC alarm Current ȝ$
0D[ :LULQJ 5HVLVWDQFH of IDC ȍ
0D[ :LULQJ Capacitance of IDC ȝ)
eOL Resistor . ȍ
Operating Temperature Range 32 to 120ºF (0 to 49ºC)
2SHUDWLQJ +XPLGLW\ Range 0 to 93% (non-condensing)
Max no. of Module per
Loop 127 units
Dimensions 4.17” (106mm)L × 4.17”
PP: î ´ PP'
Mounting Options Standard 4” Square or
Double gang Box
6KLSSLQJ :HLJKW 0.6 lbs
Features
• Single module with dual contact monitoring inputs
• Two (2) Class B or one (1) Class a monitoring inputs
• SLC Class a, Class X & Class B
• Mounts in a standard 4” or double gang box
• :LULQJ WHUPLQDOV DFFHVVLEOH ZKHQ PRXQWHG LQ ER[
• $OO ZLULQJ WHUPLQDOV DFFHSW WR $:*
• 3URGXFW LQFOXGHV D \HDU ZDUUDQW\
• UUKL Listed for Smoke Control
NOTE: This addressable module does not support 2-wire smoke
detectors.
8830082 - REV D • 12/18 page 2 OF 2
potter electric Signal Company, LLC • St. Louis, MO • phone: 800-325-3936 • www.pottersignal.com
PAD100-DIM
Dual Input Module
FROM FACP OR
PREVIOUS MODULE
TO NEXT MODULE
NOTE:
END-OF-LINE RESISTOR
IS NOT REQUIRED
MOVE THE “CL-A” DIP SWITCH
TO “UP” POSITION
FOR CLASS A WIRING
Installation Using Compatible Electrical Box
Wiring Diagrams
PAD100-DIM With One Class A Circuit
PAD100-DIM With Two Class B Circuits
Fig 2
Fig 3
Fig 1
Model Description Stock No.
paD100-DIM Dual Input Module 3992703
Ordering Information
MOVE THE “CL-A” DIP SWITCH
TO “DOWN” POSITION
FOR CLASS B WIRING
FROM FACP OR
PREVIOUS MODULE
TO NEXT MODULE
END-OF-LINE
RESISTOR
5.1K OHM 12 W
END-OF-LINE
RESISTOR
5.1K OHM 12 W
Part #3005013
Part #3005013
PAD100-SIM
Single Input Module
8830083 - REV D • 12/18 page 1 OF 2
potter electric Signal Company, LLC • St. Louis, MO • phone: 800-325-3936 • www.pottersignal.com
Description
The paD100-SIM uses one (1) SLC loop addresses when monitoring
one (1) Class B circuit. The module mounts on either a 4” square or
double gang box. The module is capable of monitoring one (1) Class
B circuit. The paD100-SIM includes one red LeD to indicate the
PRGXOH¶V VWDWXV ,Q QRUPDO FRQGLWLRQ WKH /(' ÀDVKHV ZKHQ WKH GHYLFH
LV EHLQJ SROOHG E\ WKH FRQWURO SDQHO :KHQ WKH LQSXW LV DFWLYDWHG WKH
/(' ZLOO ÀDVK DW D IDVW UDWH
Application
The paD100-SIM is compatible with potter’s Ipa and aFC/aRC
VHULHV DGGUHVVDEOH ¿UH DODUP FRQWURO SDQHOV 7KH 3$'6,0 LV DQ
LQWHUIDFH PRGXOH XVHG WR PRQLWRU GU\ FRQWDFW GHYLFHV VXFK DV VSULQNOHU
ZDWHUÀRZ YDOYH WDPSHU VZLWFKHV RU FRQYHQWLRQDO SXOO VWDWLRQV 7KH
module is capable of monitoring one Class B circuit.
Setting the Address
(DFK DGGUHVVDEOH 6/& GHYLFH PXVW EH DVVLJQHG DQ DGGUHVV 7KH DGGUHVV
is set using the DIp switch located on the paD100-SIM.
%HIRUH FRQQHFWLQJ D GHYLFH WR WKH 6/& ORRS WDNH WKH IROORZLQJ
SUHFDXWLRQV WR SUHYHQW SRWHQWLDO GDPDJH WR WKH SDQHO RU GHYLFH
1. 3RZHU WR WKH GHYLFH LV UHPRYHG
2. Field wiring is correctly installed.
3. Field wiring has no open or short circuits.
Technical Specifications
Operating Voltage 24.0V
Max SLC Standby Current ȝ$
Max SLC alarm Current ȝ$
Max Wiring Resistance of IDC ȍ
Max Wiring Capacitance of IDC ȝ)
eOL Resistor . ȍ
Operating Temperature Range 32 to 120ºF (0 to 49ºC)
Operating Humidity Range 0 to 93% (non-condensing)
Max no. of Module per
Loop 127 units
Dimensions 4.17” (106mm)L × 4.17”
(106mm)W × 1.14” (29mm)D
Mounting Options Standard 4” Square or
Double gang Box
Shipping Weight 0.6 lbs
Features
• One (1) Class B monitoring input
• SLC Class a, Class X & Class B
• Mounts in a standard 4” or double gang box
• Wiring terminals accessible when mounted in box
• all wiring terminals accept 22 to 12 aWg
• product includes a 5 year warranty
• 88./ /LVWHG IRU 6PRNH &RQWURO
NOTE: 7KLV DGGUHVVDEOH PRGXOH GRHV QRW VXSSRUW ZLUH VPRNH
detectors.
8830083 - REV D • 12/18 page 2 OF 2
potter electric Signal Company, LLC • St. Louis, MO • phone: 800-325-3936 • www.pottersignal.com
PAD100-SIM
Single Input Module
Installation Using Compatible Electrical Box
Wiring Diagram
PAD100-SIM With Class B Circuit
Fig 1
Model Description Stock No.
paD100-SIM Single Input Module 3992704
Ordering Information
Fig 2
FROM FACP OR
PREVIOUS MODULE
TO NEXT MODULE
END-OF-LINE RESISTOR
5.1K OHM
Part #3005013
12 W
PAD100-NAC
Notification Appliance Circuit
8830086 - REV D • 12/18 page 1 OF 2
potter electric Signal Company, LLC St. Louis, MO phone: 800-325-3936 www.pottersignal.com
Description
The paD100-NaC module uses one (1) address on an SLC Loop. The
module provides a programmable source of power to supervise and
control one ClaVV % or ClaVV A Notification Appliance or one
Class B Releasing Circuit. The module requires and supervises a 24
VDC auxiliary power connection. The paD100-NaC includes one red
LeD to indicate the module’s status. In normal condition, the LeD
ÀaVKeV ZKen tKe GeYice iV EeinJ polleG E\ tKe control panel
Application
The paD100-NaC is compatible with potter’s Ipa and aFC/aRC
VerieV aGGreVVaEle fire alarP control panelV 7Ke 3A'NAC iV
a PonitoreG Notification Appliance Circuit tKat ZireV to tKe 6/C
loop to proYiGe an aGGitional notification circuit :Ken uVeG ZitK a
potter addressable releasing panel, the paD100-NaC can provide an
additional releasing circuit.
Setting the Address
each addressable SLC device must be assigned an address. The
address is set using the DIp switches on the paD100-NaC module.
Before connecting a device to the SLC loop, take the following
precautions to prevent potential damage to the panel or device:
1. power to the device is removed.
2. Field wiring is correctly installed.
3. Field wiring has no open or short circuits.
7HFKQLFDO 6SHFLÀFDWLRQV
Operating Voltage 24.0V
Max SLC Standby Current ȝA
Max SLC alarm Current ȝA
aux power Required 16-33 VDC
Output Ratings 24 VDC, 2a
eOL Resistor . ȍ
eOL Resistor Diode Stock #3005012 Releasing
applications (Not Included)
Operating Temperature Range 32 to 120ºF (0 to 49ºC)
Operating Humidity Range 0 to 93% (non-condensing)
Max no. of Module per Loop 127 units
Dimensions 4.17” (106mm)L × 4.17”
PP: î ´ PP'
Mounting Options Standard 4” Square or
Double gang Box
6KippinJ :eiJKt 0.6 lbs
Features
Monitored output module that provides an additional supervised
output
Can be used as either a NaC or Releasing Output
NaC can be wired Class a or Class B
Monitors presence of 24 VDC aux power
SLC Class a, Class X & Class B
Mounts in a standard 4” or double gang box
:irinJ terPinalV acceVViEle ZKen PounteG in Eo[
All ZirinJ terPinalV accept to A:*
product includes a 5 year warranty
UUKL Listed for Smoke Control
8830086 - REV D • 12/18 page 2 OF 2
potter electric Signal Company, LLC • St. Louis, MO • phone: 800-325-3936 • www.pottersignal.com
PAD100-NAC
Notification Appliance Circuit
FROM FACP OR
PREVIOUS MODULE
TO NEXT MODULE
AUXILIARY
FROM FACP
24 VOLT POWER
NOTE: END-OF-LINE DIODE
ASSEMBLY REQUIRED
PAD100-NAC Releasing Solenoid
Part #305012
NOTE: EOL DEVICE SHALL BE INSTALLED IN
THE SAME ELCTRICAL ENCLOSURE AS THE
RELEASING DEVICE.
SOLENOID
RED BLACK
Installation Using Compatible Electrical Box
2XWSXW &RQQHFWHG WR D 1RWL¿FDWLRQ $SSOLDQFH &LUFXLW
7\SLFDO &ODVV % :LULQJ 'LDJUDP
7\SLFDO &ODVV $ :LULQJ 'LDJUDP
Wiring Diagrams
5HOHDVLQJ $SSOLFDWLRQ)LJ
)LJ
Model Description Stock No.
paD100-NaC Notification Appliance Circuit3992707
Ordering Information
It is possible that the internal relay in the paD100-NaC may be shipped in the non-normal / activated state. To ensure that the internal relay is set to the
normal state, connect the module to the SLC loop and reset the control panel before terminating the wiring to the modules output.
)LJ
)LJ
FROM FACP OR
PREVIOUS MODULE
TO NEXT MODULE
24 VOLT POWER FROM FACP
OR PREVIOUS MODULE
NOTE: END-OF-LINE
RESISTOR IS NOT
REQUIRED
PAD100-NAC CLASS A
NOT SUITABLE FOR
SYNCHRONIZATION OF
NOTIFICATION APPLIANCES
+-+-+-
24 VOLT POWER TO FACP
OR NEXT MODULE
FROM FACP OR
PREVIOUS MODULE
TO NEXT MODULE
AUXILIARY 24
FROM FACP
VOLT POWER
END-OF-LINE RESISTOR
5.1K OHM
Part #3005013
12 W+-
NOT SUITABLE FOR
SYNCHRONIZATION OF
NOTIFICATION
APPLIANCES
PAD100-NAC CLASS B
+-+-
PAD100-PSSA/PSDA
Addressable Pull Station
Single/Dual Action
8830097 - REV D • 12/18 page 1 OF 2
potter electric Signal Company, LLC • St. Louis, MO • phone: 800-325-3936 • www.pottersignal.com
Description
The paD100-pSSa (Single action) is activated by simply pulling
the white “T” bar handle down. The paD100-pSDa (Dual action)
is activated by lifting the front cover and then pulling the white “T”
bar handle down. Once activated, the “T” bar cannot be reset without
opening the front cover. Opening the front cover will also activate the
pull station. To reset the paD100-pS Series, use the potter WS-93 key
to unlock and open the front cover. Once the cover is open, push the
“T” bar back into the normal position and re-secure the front cover.
Application
The paD100-pSSa/pSDa is compatible with potter’s Ipa and aFC/
$5& VHULHV DGGUHVVDEOH ¿UH DODUP FRQWURO SDQHOV ,W LV D QRQFRGHG
addressable pull station available in either a single or dual action
model and installs on a single gang box or surface mounts using the
p32-BB or p32-DBB (deep) back box.
Technical Specifications
Operating Voltage 24.0 VDC
Max SLC Standby Current 200ua
Max SLC alarm Current 200ua
environmental Limitations 32°F - 120°F (0° - 49°C)
Indoor Only
Dimensions 4.75” H x 3.25” W x 1.75” D
Relative Humidity Range 0 - 93% (non-condensing)
Mounting Options Single gang box or
potter p32-BB/DBB
Shipping Weight apS-Sa - 1.22 lbs.
apS-Da - 1.46 lbs.
Features
• Single or Dual action versions
• Durable die-cast construction
• 5HVHW NH\ PDWFKHV WKH ¿UH DODUP FRQWURO SDQHOV
• Compatible with Ipa Series panels
• SLC Class a, Class X & Class B
• product includes a 5 year warranty
• UUKL Listed for Smoke Control
8830097 - REV D • 12/18 page 2 OF 2
potter electric Signal Company, LLC • St. Louis, MO • phone: 800-325-3936 • www.pottersignal.com
PAD100-PSSA/PSDA
Addressable Pull Station
Single/Dual Action
The paD100-pS Series uses one SLC address assigned to the device. The address is set using the DIp switch located on the back of the paD100-pS
device.
Setting the Address
Fig 1
Fig 2
Model Description Stock No.
paD100-pSSa addressable pull Station, Single action 3992721
paD100-pSDa addressable pull Station, Dual action 3992720
Ordering Information
P POTTER P POTTER
Pull Station Front View
Pull Station Back View and Wiring
paD100-pSDa paD100-pSSa
FACTORY WIRED CONTACTS
FROM FACP OR
PREVIOUS DEVICE
TO NEXT DEVICE
PAD200-PCD
Photoelectric Smoke / Carbon-Monoxide Detector
8830197 - REV B • 2/22 PAGE 1 OF 2
Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 • www.pottersignal.com
Description
The Photoelectric Smoke Sensor and the Carbon Monoxide (CO)
sensor are both listed Analog Addressable sensors compatible with fire
alarm control panels that utilize the Potter Addressable Device (PAD)
protocol.
The CO sensing portion utilizes a proven electrochemical sensor for
accurate detection of CO gas for life safety applications.
The photoelectric sensor complies with UL 268 7th edition enhanced
smoke sensitivity tests. It has a wide sensitivity range of 1.0 to 3.7%
per foot, and features drift compensation with built in dirty detector
warning.
The sensor and the control panel communicate over a proven and robust
digital communication path and the system analyzes the information
at the particular device. The total polling speed is less than five
(5) seconds, well under the UL requirements.
The sensor is compatible with any of the PAD sensor bases and simply
twists on. The PAD200-PCD is addressed using DIP switches in the
rear of the sensor and can be easily programmed in the field without
special tools.
Setting the Address
Each addressable device on the SLC loop must have a unique address
from 1 to 127 to function properly. The address is set using DIP
switches.
Before connecting a device to the SLC loop, take the following
precautions to prevent potential damage to SLC or device. Verify the
following:
1. Power to the device is removed
2. Field wiring is correctly installed.
3. Field wiring has no open or short circuits.
Technical Specifications
Operating Voltage 24 VDC
Detector Current Draw 300 μA
Alarm indicator 1 LED
Alarm set-point range 1.1-3.5 %/ft. (3.6-11%/m)
Installation temperature
range 32 to 120°F / 0 to 49°C
Operating relative
humidity range 0% to 93% (non-condensing)
Start-up time 1 second
Maximum number of
addresses per loop 127
Maximum number of
lighted indicators in
alarm per loop.
30
Color Eggshell White
Weight (without base)113 g (4.0 oz)
Dimensions (without
base)
Height: 1.35 in (34 mm)
Diameter: 3.93 in. (100 mm)
Features
• Photoelectric Smoke Detection compliant with UL 268 7th
Edition
• Carbon Monoxide (CO) detection compliant with UL 2075
• 10 year Carbon Monoxide detection lifespan with built in end of
life indication
• Walk Test mode allows for fast easy validation of CO sensor
operation
• Low profile, less than 2 inches with the base
• Wide selectable sensitivity range of 1.0 to 3.7%/foot
• Sensor communicates sensitivity to control panel
• UL listed smoke calibration and sensitivity
• Optional locking tab to prevent unwanted removal
• Simple DIP switch address setting, no programming tool required
• LED alarm indicator
• Product includes a 5 year warranty
• UUKL Listed for Smoke Control
8830197 - REV B • 2/22 PAGE 2 OF 2
Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 • www.pottersignal.com
PAD200-PCD
Photoelectric Smoke / Carbon-Monoxide Detector
Air Velocity Ratings
Operation
Sensor Sensitivity
Spacing
Compatible Bases
Ordering Information
The PAD200-PCD has an Open Area of Protection air velocity rating of 0 to 300 feet per minute.
The system has a maximum of 30 LEDs that can be turned on simultaneously. If the system already has 30 LEDs on, the PAD200-PCD will operate
even though the LED may not illuminate.
The PAD200-PCD is an analog addressable sensor that uses one address on the Signaling Line Circuit (SLC) of a compatible fire alarm control panel.
The unit communicates with the control panel as it is polled. The LEDs flash every time the unit is polled and they will flash at a fast rate if the unit is
in an active status. The polling LED can be turned off if desired for less conspicuous operation.
The PAD200-PCD with the PAD100-4DB or PAD100-6DB has a low profile of less than two (2) inches to blend into the surrounding environment. The
sensor includes an insect screen to prevent foreign objects from reaching the chamber and the can be cleaned to restore operation of a dirty detector.
The PAD200-PCD and the compatible control panel work in tandem to keep the sensitivity consistent. As the sensor is installed over time, the sensor
compensates for the dirt in the unit until it is out of range. At that time, the panel will indicate a dirty sensor. The sensor will then have to be cleaned
or replaced.
The PAD200-PCD can be programmed to provide a maintenance alert prior to reaching the dirty sensor level which will allow for intervention prior to
the sensor going into trouble. This allows for sensor replacement or cleaning prior to a nuisance trouble occurs.
NOTE: As required by NFPA, do not install the sensors until all construction is complete and the work area has been thoroughly cleaned. If the sensors
have been installed in a construction environment, they should be cleaned or replaced before the system is placed into service.
The PAD200-PCD is UL listed with a recommended maximum spacing of 30 feet. Refer to NFPA 72 for specific information regarding detector
spacing, placement and special applications.
All bases will mount on a single gang, double gang, octagon, 4” square or mud ring electrical box.
Device Description Stock No.
PAD100-4DB 4” Standard Base 3992731
PAD100-6DB 6” Standard Base 3992732
PAD100-IB 6” base with an isolator module included. 3992730
PAD100-RB 6” base with one Form-C relay contact. 2A @ 30VDC, 0.5A @ 125VAC 3992728
PAD100-SB 6" base with sounder module included. Sound pattern is provided from external source. 3992729
PAD100-SPKB 6” base with speaker included 3992762
Model Description Stock No.
PAD200-PCD Photoelectric Smoke/Carbon-Monoxide Detector 3992772
8830203 - REV B • 2/23PRINTED IN USA PAGE 1 OF 2
Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 • www.pottersignal.com
PAD300-4DB/6DB
4”/6” Detector Base
Features
Application
The Potter PAD300-6DB and PAD300-4DB detector bases are used
to install PAD300 series detectors. The PAD300-6DB will mount on
a single gang, double gang, octagon, 4” square, 50mm, 60mm, and
70mm electrical box.
Description
The PAD300-6DB and PAD300-4DB are low-profile, surface-mount
bases used with Potter’s addressable detectors. The base uses screw
clamp terminals that accept wire ranging from 22 to 12 AWG.
When installed on recessed electrical boxes, the PAD300-6DB is
wide enough to completely cover the back box and the immediate
surrounding area. The base is equipped with a locking tab to deter
unauthorized removal of the attached detector.
Technical Specifications
Installation Temp Range 32°F to 150°F (0°C to 66°C)
Operating Humidity Range 0% to 93% (Non-condensing)
Dimension PAD300-4DB: 3.93 in / 100 mm
PAD300-6DB: 6.3 in / 160 mm
Weight PAD300-4DB: 1.34 oz / 38 g
PAD300-6DB: 3.03 oz / 86 g
Height 0.76 in / 20 mm
Acceptable Wire Gauge 22 to 12AWG
Mounting Options
• Single Gang
• Double Gang
• 3-1/2” Octagon Box
• 4” Octagon Box
• 4” Square with Plaster Ring
• 50mm c/c Box
• 60mm c/c Box
• 70mm c/c Box
• Terminals marked with polarity to assist with installation
• Duplicate Terminals for In-and-out SLC Wiring
• Terminals accept 22 to 12 AWG wire sizes
• Installs on Single Gang, Double Gang, Octagon or 4” Square
Box
• Locking tab prevents unauthorized detector removal
• Product includes 5-year warranty
• 6” mounting base comes with trim plate cover
0328-0539
8830203- REV B • 2/23PRINTED IN USA PAGE 2 OF 2
Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 • www.pottersignal.com
PAD300-4DB/6DB
4”/6” Detector Base
Wiring Diagrams
Model Description Stock No.
PAD300-4DB 4” Detector Base 3992781
PAD300-6DB 6” Detector Base 3992782
Ordering Information
Locking Feature
The PAD300-6DB and PAD300-4DB include a locking feature that
prevents removal of the detector without using a tool.
1. To enable this feature, break off the locking tab (See Figure 1), and
then install the detector.
2. To remove the detector from the base when the locking feature has
been enabled, insert a small screwdriver into the slot on the base to
push the plastic tab while simultaneously turning the detector head
counter-clockwise.
Break off tab (gray area) in
image to enable locking feature.
Insert small
screwdriver into
slot to remove
detector from base.
Fig. 1
Fig. 2
Fig. 3
1) Class B Wiring:
2) Class A Wiring:
3) Class X Wiring:
PAD300-PD
Photoelectric Smoke Detector
8830216 - REV B • 2/23 PAGE 1 OF 2
Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 • www.pottersignal.com
Description
The Photoelectric Smoke Detector is a listed Analog Addressable
smoke detector compatible with fire alarm control panels that utilize
the Potter Addressable Device (PAD) protocol. The PAD300-PD is a
low profile smoke detector with a wide sensitivity range. The detector
and base are made of a durable plastic in an off-white color to blend
in with the ceiling.
The PAD300-PD has a sensitivity range of 1.1 to 3.5 % per foot and is
UL listed. The PAD300-PD features drift compensation and has built
in dirty detector warning as well. The PAD300-PD and the control
panel communicate over a proven and robust digital communication
path and the system analyzes the information at the particular device.
The total polling speed is less than five (5) seconds, well under the UL
requirements.
The detector is compatible with any of the PAD300 series detector
bases and simply twists on. The PAD300-PD is addressed using DIP
switches in the rear of the detector and can be easily programmed in
the field without special tools.
Setting the Address
Each addressable device on the SLC loop must have a unique address
from 1 to 127 to function properly. The address is set using DIP
switches.
Before connecting a device to the SLC loop, take the following
precautions to prevent potential damage to SLC or device. Verify the
following:
1. Power to the device is removed.
2. Field wiring is correctly installed.
3. Field wiring has no open or short circuits.
Technical Specifications
Operating Voltage 24 VDC
Detector Current Draw 300 µA
Alarm Indicator 1 LED
Alarm Set-point Range 1.1 to 3.5%/ft (3.6 to 11%/m)
Installation Temperature Range 32 to 120 ° F (0 to 49 ° C)
Operating Relative Humidity
range 0% to 93% (Non-condensing)
Start-up Time Max. 1 sec.
Maximum Number of Addresses
Per Loop 127
Maximum Number of Lighted
Indicators in Alarm Per Loop 30
Color Eggshell White
Weight (without base)91g (3.2oz)
Dimensions (without base)Height: 1.42 in (36mm)
Diameter: 3.93 in (100 mm)
Features
• Low profile, less than 2 inches with the base
• Wide selectable sensitivity range of 1.1 to 3.5%/foot
• Detector communicates sensitivity to control panel
• UL listed smoke calibration and sensitivity
• Optional locking tab to prevent unwanted removal
• Simple DIP switch address setting, no programming tool
required
• Magnetic test switch
• LED alarm indicator
• Product includes 5-year warranty
• UUKL Listed for Smoke Control
• UL268 7th edition compliant
0328-0541
8830216- REV B • 2/23 PAGE 2 OF 2
Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 • www.pottersignal.com
PAD300-PD
Photoelectric Smoke Detector
Air Velocity Ratings
Operation
Detector Sensitivity
Spacing
Compatible Bases
Model Description Stock No.
PAD300-PD Photoelectric Smoke Detector 3992775
Ordering Information
The PAD300-PD has an Open Area of Protection air velocity rating of 0 to 300 feet per minute.
The system has a maximum of 30 LEDs that can be turned on simultaneously. If the system already has 30 LEDs on, the PAD300-PD will operate even
though the LED may not illuminate.
The PAD300-PD is an analog addressable detector that uses one address on the Signaling Line Circuit (SLC) of a compatible fire alarm control panel.
The unit communicates with the control panel as it is polled. The LEDs flash every time the unit is polled and they will flash at a fast rate if the unit is
in an active status. The polling LED can be turned off if desired for less conspicuous operation.
The PAD300-PD with the PAD300-4DB or PAD300-6DB has a low profile of less than two (2) inches to blend into the surrounding environment. The
detector includes an insect screen to prevent foreign objects from reaching the chamber and can be cleaned to restore operation of a dirty detector.
The PAD300-PD and the compatible control panel work in tandem to keep the sensitivity consistent. As the detector is installed over time, the detector
compensates for the dirt in the unit until it is out of range. At that time, the panel will indicate a dirty detector. The detector will then have to be cleaned
or replaced.
The PAD300-PD can be programmed to provide a maintenance alert prior to reaching the dirty detector level which will allow for intervention prior to
the detector going into trouble. This allows for detector replacement or cleaning prior to a nuisance trouble occurs.
NOTE: As required by NFPA, do not install the detectors until all construction is complete and the work area has been thoroughly cleaned. If the
detectors have been installed in a construction environment, they should be cleaned or replaced before the system is placed into service.
The PAD300-PD is UL listed with a recommended maximum spacing of 30 feet. Refer to NFPA 72 for specific information regarding detector spacing,
placement and special applications.
All bases will mount on a single gang, 3-1/2” octagon, 3-1/2” square, double gang, 4” octagon, 4” square, 50mm c/c, 60mm c/c and 70mm c/c boxes.
Device Description Stock No.
PAD300-4DB 4” Detector Base 3992781
PAD300-6DB 6” Detector Base 3992782
PAD300-IB 6” base with an isolator module included 3992783
PAD300-RB 6” base with one Form-C relay contact. 2A @ 30VDC, 0.5A @ 125VAC 3992784
PAD300-SB 6" base with sounder module included. Sound pattern is provided from external source 3992785
PAD300-LFSB 6” base with 520Hz sounder module included. Sound pattern is provided from external source 3992786
8830146 - REV B • 6/19 page 1 OF 3
potter electric Signal Company, LLC • St. Louis, MO • Tech Support: 866-956-1211 / Customer Service: 866-572-3005 • www.pottersignal.com
UD-2000
Digital Alarm Communicator
Description
The UD-2000 Digital alarm Communicator Transmitter (DaCT)
provides for up to two (2) phone lines for communication to a
monitoring station. The UD-2000 communicates using the SIa-
DCS or ademco Contact ID protocols. When enabled, the DaCT
automatically monitors each phone line or voltage and has the
ability to seize the line and connect with a remote receiver. Once the
communication is complete, the DaCT will hang up.
The DaCT is provided with terminal blocks for each phone line and
two RJ45 cords. In order for the DaCT to work properly, it must be
installed on a plain old telephone service (pOTS) line or equivalent
deemed by the authority having jurisdiction. The DaCT must be
installed before any other equipment to ensure it can seize the phone
line.
phone lines are high voltage and should be run in a separate conduit
from other circuits. The wire conductors connecting the DaCT to the
phone system should be 26 aWg or larger.
7HFKQLFDO 6SHFLÀFDWLRQV
Operating Voltage 22.0-24.0V
Standby Current 16ma
alarm Current 23ma
Max UD-2000s per panel 1
Dimensions 4”W * 6”H * 1-5/8”D
Operating Tempuratures 0°C - 49°C (32°F- 120°F)
Operating Humidity Range 10% - 93% @ 30°C (86°F)
(non-condensing)
Mounting Options In FaCp Behind keypad
Shipping Weight 0.47 lbs
Features
• allows for communication to Monitoring Station
• Communicates using SIa-DCS or ademco Contact ID protocols
• For use with Ipa, aFC, and aRC series addressable panels and
pFC-4064 Conventional panel
• Status LeDs indicate operation of DaCT card
• Installs with ease behind main panel LCD display via User
Interface bracket
• Device address is set internally to address 1
• Includes two (2) RJ45 phone cords
8830146 - REV B • 6/19 page 2 OF 3
potter electric Signal Company, LLC • St. Louis, MO • Tech Support: 866-956-1211 / Customer Service: 866-572-3005 • www.pottersignal.com
UD-2000
Digital Alarm Communicator
Installation
,QVWDOO LQ DFFRUGDQFH ZLWK FRPSDWLEOH ¿UH DODUP FRQWURO SDQHO LQVWDOODWLRQ PDQXDO
The UD-2000 DaCT is connected to the control panel using the provided four-wire cable connection (p/N 5210514) between p4 and UD-2000 p1. The
connection is power limited and supervised.
1. power system down.
2. Slide the UD-2000 into the card guides located under the User Interface bracket.
3. Secure the UD-2000 to the User Interface bracket using the provided #6-32x3/8” screw
4. Install the provided four-wire conductor jumper between UD-2000 p1 and p4.
1
2
3
4 5
6
7
8 1 - Grey
2 - Ta n
3 - Black
4 - Red
5 - Green
6 - Ye llow
7 - Blue
8 - Brown
1
2
3
4 5
6
7
8
Plain Old Te lephone (POTS) lines
RJ31X Phone Jack to UD-2000
Ring (Grey)
Line In From Te lco
UD-2000 Communicator
Tip (Brown)Out to Premises Phones
Ring (Red)
Tip (Green)
Ring (Grey)
Tip (Brown)Out to Premises Phones
Ring (Red)
Tip (Green)
Line In From Te lco
Te lco 2
TipRingTip Ring TipRingTip Ring
Phone 2Telco 1 Phone 1
Te lco Ti p = Red
Te lco Ring = Green
Phone Tip = Brown
Phone Ring = Grey
8830146 - REV B • 6/19 page 3 OF 3
potter electric Signal Company, LLC • St. Louis, MO • Tech Support: 866-956-1211 / Customer Service: 866-572-3005 • www.pottersignal.com
UD-2000
Digital Alarm Communicator
UD-2000 DACT Installation on
Small Platform Panel
UD-2000 DACT Installation on
Large Platform Panel
Slides in guides under main board.
Screw
DWG #593-32A
Slides in guides under main board.
Screw
DWG #593-32A
DETAIL E SCALE 1 : 1
DETAIL D SCALE 1 : 1
p Connector on
small platform
control panel
p Connector
on main board
DETAIL B SCALE 1 : 1
Fig 1 Fig 2
Ordering Information
Model Description Stock No.
UD-2000 Digital Alarm Communicator 3992769