HomeMy WebLinkAboutROMAC FIELD FLANGE - 22-00795 - Madison Station Apartments - Bldg 17-18
April 4, 2016
1-800-426-9341 www.romac.com
ROMACINDUSTRIES,INC.Romac Field Flange™
Ma
t
e
r
i
a
l
S
p
e
c
i
f
i
c
a
t
i
o
n
s
Castings: Ductile iron per ASTM A 536, Grade 65-
45-12. Flange in accordance with ANSI Class 150
drilling. Black shopcoat.
Set Screws: 5/8" x 2", 4140 steel alloy. Screws are
designed with a unique “TRUE TORQUE”™ head
(7/16", 12 point) which will shear off at approximately
80 ft-lbs. of torque.
Gaskets: SBR per ASTM D-2000 MBA 710, com-
pounded for water and sewer service.
Other compounds available on request.
Use: The Field Flange™ joins plain-end pipe of
ductile iron and steel sizes to flanged fittings. It
requires no threading or welding.
Not for use on PVC pipe or plain end mechanical
joint fittings.6" Field Flange™
4" Field Flange 4: 5/8" x 2" 11 # 300 3° $105.02
6" Field Flange 8: 5/8" x 2" 16 # 300 2° 113.08
8" Field Flange 8: 5/8" x 2" 19 # 300 2° 132.18
10" Field Flange 12: 5/8" x 2" 31 # 250 2° 283.50
12" Field Flange 12: 5/8" x 2" 43 # 175 1.5° 330.27
GASKET ONLY FIELD FLANGE ONLY
LIST PRICENOM.PIPESIZE
APPROX. WEIGHT (lbs.)
WORKING PRESSURE PSI 1
CATALOG NUMBER MAXIMUM JOINT DEFLECTIONSET SCREWS
NUMBER: SIZE
12"
10"
8"
6"
4"
1 Based on test pressure of at least
two times rated pressure.
Note: Not recommended for use on thin wall pipe such as,
Thickness Class 50 and Pressure Class 350 ductile iron pipe.
To Order: Specify catalog description.
1. Cut pipe to length. Pipe must be cut square and clean.
2. Slip flange over end of pipe. Tighten pins so that they are touching the pipe all around.
Inspect to make sure that any gap between pipe and flange is even all the way around the pipe.
3. Tap flange into place. Face of the flange should be flush with the end of the pipe.
4. Tighten pins evenly, checking to be sure that even gap between pipe and flange is maintained.
Continue until 80-85 ft-lbs. torque is reached or until the pin heads break off above the notch.
5. Stretch gasket over end of pipe and press firmly into flange.
6. Bolt Field Flange™ to its mating flange.
FIELD FLANGE™ INSTALLATION INSTRUCTIONS
MJ x IPS MJ x CI
$9.44
9.56
9.74
13.00
16.79
$9.44
9.56
9.74
13.00
16.79
NSF61 certified upon request.