HomeMy WebLinkAboutREVIEW RESPONSE 03-09-23 - 22-00795 - Madison Station Apartments - Bldg 1Author Name Author Email Author Phone No.: Cody Jones Cody.Jones@rexburg.org 208-372-2173 Description : Madison Station Apartments - Bldg 1 Address : 577 Trejo St - 1101-1312 Application Type : Document Filename : 03-09-23 City Review Response.pdf Array Comment Author Contact Information: Corrections in the following table need to be applied before a permit can be issued Review Report Revisions Required Page Reference Annotation Type Author : Department Status Page Review Comments Applicant Response Comments G1.1 Free Text Cody Jones : Building Open 3 Will need stamped truss plans with building design professionals approval. S1.0 Free Text Cody Jones : Building Open 14 Need additional structural pages. # 22-00795 New Multi-Family Residence Please digitally re-submit all pages of the plan set in response to requested revisions for our next review cycle, with noted items resolved. Report Date: 03.23.2023 Approval of plans does not constitute approval of variance from code Page 1 of 1 Powered by TCPDF (www.tcpdf.org) SEE REVISED G1.1 FOR CORRECTION SEE REVISED G1.1 SEE S1.0 DEFERRED SUBMITTAL NOTE & G1.1 FOR ADDED DEFERRED SUBMITTAL NOTE. SEE REVISED A5.1 FOR SELF CLOSING HARDWARE NOTE ADDED TO SCHEDULE SEE REVISED A5.1 FOR ADDED DETAIL SEE REVISED SHEETS A1.1, 1.2 & 1.3 SEE REVISED SHEETS G1.0, A1.1, 1.2 & 1.3 SD1.1 REVISED TO SHOW COMPLIANCE D/SD2.1, 2% MAX CROSS SLOPE ADDED A3.1, WALL INSULATION CORRECTED A3.1, ROOF INSULATION CORRECTED A3.1, STC RATING CLARIFIED PRESCRIPTIVE CITY FORM UPLOADED SEE ATTACHED FOR NOTE ADDED TO DETAIL 2/A3.1 SEE ATTACHED FOR NOTE ADDED TO DETAIL 3/A3.1 GA DESCRIPTION PROVIDED, SEE REVISED A3.3 REVISED SHEET A6.1, NOTE PROVIDED CORRECTION MADE, SEE REVISED S1.0 SEE S1.1 FOR SPECIAL INSPECTOR NOTE, AND G1.0 FOR ADDED NOTE UNDER DEFERRED SUBMITTAL - SPECIAL INSPECTOR WILL BE EAGLEROCK ENGINEERING - AREA MAP PROJECT SITE DRAWING INDEX GENERAL NOTES 1. all dimensions are from face of stud. (u.n.o) 2. SITE CONCRETE FLATWORK THAT ABUTS FOUNDATION SHALL UTILIZE 1/2" EXPANSION MATERIAL WITH CONTINUOUS SEALING ON TOP. 3. HORIZONTAL GYPSUM SHALL BE INSTALLED PERPENDICULAR TO CEILING FRAMING PER IBC 2508.5.2. 4. ELECTRICAL BOXES IN RATED ASSEMBLIES SHALL BE STEEL OR HAVE A LISTED FIRE-RATING EQUIVALENT TO THE ASSEMBLY. ANNULAR SPACE BETWEEN THE MEMBRANE AND THE BOX SHALL NOT EXCEED 1/8" PER IBC 714.3.2. 5. RECESSED LUMINAIRES INSTALLED WITHIN THE BUILDING ENVELOPE SHALL COMPLY WITH IECC R402.4.5. FIXTURES SHALL BE IC-RATED AND SEALED AIR TIGHT. 6. WALL TILE IN SHOWER/TUB ENCLOSURES SHALL BE INSTALLED PER IBC 2509.2, WITH THE USE OF GLASS-MAT GYPSUM PANELS, ASTM C1178, FIBER-CEMENT BACKER BOARD, ASTM C1288, OR FIBER-MAT REINFORCED CEMENTITIOUS BACKER BOARD, ASTM C1325. 7. UPPER LEVEL OPERABLE WINDOWS WITH SILLS WITHIN 36" OF THE FLOOR SHALL COMPLY WITH ASTM F2090 & IBC SECTION 1030.2 (OPENING CONTROL DEVICE) 8. all bedroom windows shall comply with ibc 1030. 9. all ventilation shall be installed per ibc 1203. 10. all walls, partitions, and floor-ceiling assemblies separating units shall have a sound transmission class of at least 50. 11. site grading shall meet requirements of ibc 1804. 12. damp proofing shall comply with ibc 1805. 13. fire blocking: A. provide fire blocking at floor and ceiling levels. B. provide fire blocking horizontally at intervals not to exceed 10-feet. CODE REVIEW APPLICABLE BUILDING CODES: 2018 IBC, IMC, IECC, NEC OCCUPANCY: R-2 CONSTRUCTION TYPE: V-B FIRE SPRINKLER: YES, 13-R fire extinguishers • f.e.: 1. 1a;10b;c 2. fire extiguisher • f.e.c.: 1. 4a;60b'c 2. surface mounted fire extiguisher cabinet. STATE OF IDAHO BRENT A. McFARLAND AR-2561 11 5 2 B O N D A V E N U E - S u i t e A RE X B U R G , I D A H O 8 3 4 4 0 VO I C E ( 2 0 8 ) 3 5 9 - 2 3 0 9 F A X ( 2 0 8 ) 3 5 9 - 2 2 7 1 WW W . J R W A . C O M Job Number: Date: Drawn By: STRUCTURAL ENGINEERING Frost Structural Engineering 1020 Lincoln Road Idaho Falls, ID 83401 Tel: (208) 227-8404 Fax: (208) 227-8405 Checked By: Plot Date: Consultants: Drawing Number: File: Revisions: Pr o j e c t : Dr a w i n g T i t l e : MECHANICAL ENGINEERING Engineered Systems Assoc. 1335 East Center Street Pocetello, Idaho 83204 Tel: (208) 233-0501 Fax: (208) 233-0529 ELECTRICAL ENGINEERING Payne Engineering INC. 1832 East Center Street Pocetello, Idaho 83201 Tel: (208) 232-4439 Fax: (208) 232-1435 OF 3/7/2023 3:47:08 PM S:\Drawings\870-Sweetwater Apartment - Madison Station\BIM CD\SWEETWATER APARTMENT-October Redlines.rvtG1.1 CO V E R S H E E T 870 MA D I S O N S T A T I O N A P T S . OCT, 2022 EUP BAM 5 RE X B U R G ID A H O RE X B U R G , I D A H O REXBURG IDAHO MADISON STATION APTS. GENERAL SITE DESIGN CIVIL ARCHITECTURAL G1.1 COVER SHEET G1.2 GENERAL ACCESSIBILITY REQUIREMENTS G1.3 MAIN FLOOR CODE REVIEW G1.4 2ND FLOOR CODE REVIEW G1.5 3RD FLOOR CODE REVIEW ---- COVER G-1 NOTES C-1 EXISTING CONDITIONS & DEMOLITION PLAN C-2 OVERALL SITE PLAN C-3 GRADING & STORM PLAN C-4 STORM AREA TABLES PP-1 ALIGNMENT D, G, & E PP-2 ALIGNMENT F PP-3 ALIGNMENT C & H PP-4 ALIGNMENT A PP-5 ALIGNMENT B, I, & J PP-6 ALIGNMENT K SWPPP STORM WATER POLLUTION PREVENTION PLAN D-1 DETAILS D-2 DETAILS SD1.1 ARCHITECTURAL SITE PLAN SD2.1 ARCHITECTURAL SITE DETAILS A1.1 MAIN FLOOR PLAN A1.2 2ND FLOOR PLAN A1.3 3RD FLOOR PLAN A1.4 ROOF PLAN A2.1 EXTERIOR ELEVATIONS A2.2 EXTERIOR ELEVATIONS A3.1 BUILDING SECTIONS A3.2 STAIR SECTIONS A3.3 WALL TYPES A4.1 MILWORK DETAILS - TYPE "1" UNIT A4.2 MILWORK DETAILS - TYPE "2" UNIT A4.3 MILWORK DETAILS - TYPE "3" UNIT A5.1 DOOR SCHEDULE PLUMBING MECHANICAL ELECTRICAL STRUCTURAL A5.2 WINDOW SCHEDULE A6.1 LARGE SCALE PLAN - TYP. TYPE 1 UNIT A6.2 LARGE SCALE PLAN - TYP. TYPE 2 UNIT A6.3 LARGE SCALE PLAN - TYP. TYPE 3 UNIT S1.0 GENERAL STRUCTURAL NOTES S1.1 SPECIAL INSPECTIONS S1.2 TYPICAL DETAILS S1.3 TYPICAL DETAILS S1.4 PLAN SCHEDULES S2.0 FOUNDATION PLAN S2.1 SECOND FLOOR FRAMING PLAN S2.2 THIRD FLOOR FRAMING PLAN S2.3 ROOF FRAMING PLAN S3.0 FOUNDATION DETAILS S4.0 FLOOR FRAMING DETAILS S4.1 FLOOR FRAMING DETAILS S5.0 ROOF FRAMING DETAILS P1.0 FOUNDATION PLUMBING PLAN P1.1 LEVEL 1 PLUMBING FLOOR PLAN P1.2 LEVEL 2 PLUMBING FLOOR PLAN P1.3 LEVEL 3 PLUMBING FLOOR PLAN P2.1 LARGE SCALE TYP. APT. PLUMBING PLANS P3.0 PLUMBING DETAILS & SCHEDULES M1.1 LEVEL 1 MECHANICAL FLOOR PLAN M1.2 LEVEL 2 MECHANICAL FLOOR PLAN M1.3 LEVEL 3 MECHANICAL FLOOR PLAN M2.1 LARGE SCALE TYP. APT. MECH. PLANS M3.0 MECHANICAL DETAILS & SCHEDULES E0.0 ELECTRICAL SYMBOLS & DETAILS E1.1 1ST FLOOR ELECTRICAL PLANS E1.2 2ND FLOOR ELECTRICAL PLANS E1.3 3RD FLOOR ELECTRICAL PLANS E2.0 TYPICAL UNIT PLANS E3.0 POWER RISER DIAGRAM & SCHEDULES ARCHITECTURAL CONT. 2A10BC 2 DEFERRED SUBMITTALS ENGINEERED TRUSS SHOP DRAWINGS TO BE SUBMITTED TO CITY UPON RECEIPT FROM TRUSS MANUFACTURER ENGINEER. SPECIAL INSPECTOR FOR CITY APPROVAL 2 2 2 3/9/23 RESPONSE TO CITY WINDOW TYPE 'B' FIRE SUPPRESSION WINDOW WASH BASIS OF DESIGN: 2 Will need stamped truss plans with building design professionals approval. ACCESSIBLE PARKING STALLS 2018 IBC 1106.1, 2% x 600 = 12 ACCESSIBLE STALLS REQUIRED, W/ (2) BEING VAN ACCESSIBLE ACTUAL VAN ACCESSIBLE STALLS: 16 16 > 12, PASS 3 3 3/9/23 RESPONSE TO CITY STRUCTURAL ENGINEERING Frost Structural Engineering 1020 Lincoln Road Idaho Falls, ID 83401 Tel: (208) 227-8404 Fax: (208) 227-8405 MECHANICAL ENGINEERING Engineered Systems Assoc. 1335 East Center Street Pocetello, Idaho 83204 Tel:(208) 233-0501 Fax:(208) 233-0529 ELECTRICAL ENGINEERING Payne Engineering INC. 1832 East Center Street Pocetello, Idaho 83201 Tel: (208) 232-4439 Fax: (208) 232-1435 Consultants: STATE OF IDAHO BRENT A. McFARLAND AR-2561 NOTE: CROSS SLOPE OF SIDEWALKS NOT TO EXCEED 2%2 2 3/9/23 RESPONSE TO CITY W D DW WD DW UP W D DW WD DW W D DW W D DW W D DW W D DW UP WD DW W D DW W D DW WD DW A6.1 1 A6.3 1 1 A3.1 A6.2 1 4'-0"8'-7"23'-3"17'-7"6'-7" 4' - 2 " 19 ' - 1 0 " 14 ' - 1 1 " 9' - 1 " 9' - 1 " 14 ' - 1 1 " 19 ' - 1 0 " 4' - 2 " 4' - 2 " 9 1 / 4 " 7' - 5 " 5' - 1 0 1 / 2 " 7' - 5 " 16 ' - 6 1 / 4 " 11 ' - 8 " 38 ' - 0 " 4' - 2 " 4'-0"8'-7"23'-3"17'-7"6'-7" 96 ' - 0 " 60'-0"14'-0"60'-0" W1 W1 W3 W3 W3 W3 W3 UNIT type 3 UNIT 101 1 A3.2 1 A3.2 UNIT type 2 UNIT 103 UNIT type 1 UNIT 105 W1 W1 W1 W1 W2 W2 W2 W2 W2 W2 W2 W1 W1 W1 4'-0"8'-7"23'-3"17'-7"6'-7" 4' - 2 " 19 ' - 1 0 " 14 ' - 1 1 " 9' - 1 " 9' - 1 " 14 ' - 1 1 " 19 ' - 1 0 " 4' - 2 " 4'-0"8'-7"23'-3"17'-7"6'-7" W1 W1 W3 W3 W3 W3 W3 W1 W1 W1 W1 W2 W2 W2W2 W2 W2 W2 W1 W1 W1 134'-0" 134'-0" 96 ' - 0 " F1 F2 W2 W2W2 W2 F.E.C.F.E.C. fire riser IT/ comm riser 0" / 1 2 " 1/ 1 6 " / 1 2 " 1: 2 0 s l o p e 1: 2 0 s l o p e 1 A2.2 60'-0"14'-0"60'-0" W2 W2 W2 W2 8" furr-out for gas piping. length of furr- out to be determined by gas meter size. 8" furr-out for gas piping. length of furr- out to be determined by gas meter size. UNIT type 1 UNIT 102 UNIT type 2 UNIT 104 UNIT type 3 UNIT 106 UNIT type 3 UNIT 112 UNIT type 2 UNIT 110 UNIT type 1 UNIT 108 UNIT type 1 UNIT 111 UNIT type 2 UNIT 109 UNIT type 3 UNIT 107 1 1 1 1 A A A A AA B BB AA A A A A A B A A A STATE OF IDAHO BRENT A. McFARLAND AR-2561 11 5 2 B O N D A V E N U E - S u i t e A RE X B U R G , I D A H O 8 3 4 4 0 VO I C E ( 2 0 8 ) 3 5 9 - 2 3 0 9 F A X ( 2 0 8 ) 3 5 9 - 2 2 7 1 WW W . J R W A . C O M Job Number: Date: Drawn By: STRUCTURAL ENGINEERING Frost Structural Engineering 1020 Lincoln Road Idaho Falls, ID 83401 Tel: (208) 227-8404 Fax: (208) 227-8405 MECHANICAL ENGINEERING Engineered Systems Assoc. 1335 East Center Street Pocetello, Idaho 83204 Tel:(208) 233-0501 Fax:(208) 233-0529 ELECTRICAL ENGINEERING Payne Engineering INC. 1832 East Center Street Pocetello, Idaho 83201 Tel: (208) 232-4439 Fax: (208) 232-1435 Checked By: Plot Date: Consultants: Drawing Number: File: Revisions: Pr o j e c t : Dr a w i n g T i t l e : ® J R W & A S S O C I A T E S , P L L C . D R A W I N G S A N D D E S I G N S A R E PR O T E C T E D B Y C O P Y R I G H T A N D T H E A R C H I T E C T R E T A I N S T O TA L O W N E R S H I P A N D C O N T R OL . A N Y U N A U T H O R I Z E D U S E O F D R A W I N G S , D E S I G N S O R I D EA S W I T H O U T W R I T T E N C O N S E N T O F T H E A R C H I T E C T I S P R O HI B I T E D OF 3/9/2023 3:14:30 PM S:\Drawings\870-Sweetwater Apartment - Madison Station\BIM CD\SWEETWATER APARTMENT-October Redlines.rvtA1.1 MA I N F L O O R P L A N 870 MA D I S O N S T A T I O N A P T S . OCT, 2022 EUP BAM RE X B U R G ID A H O RE X B U R G , I D A H O 16 SCALE:3/16" = 1'-0" F.F. 1ST FLOOR PLAN NORTH 1 2/13/23 OWNER CHANGES W2W1 W2W1 W2W1 W2W2W1 2 2 2 CONTRACTOR'S OPTION, WINDOWS TO BE FIRE RATED OR HAVE APPROVED FIRE SPRINKLER WASH SYSTEM 2 CONTRACTOR'S OPTION, WINDOWS TO BE FIRE RATED OR HAVE APPROVED FIRE SPRINKLER WASH SYSTEM 2 2 3/9/23 RESPONSE TO CITY DN UP W D DW WD DW W D DW W D DW WD DW W D DW DNUP W D DW W D DW WD DW W D DW W D DW WD DW 1 A3.1 4'-0"8'-7"23'-3"17'-7"6'-7" 4' - 2 " 19 ' - 1 0 " 24 ' - 0 " 24 ' - 0 " 19 ' - 1 0 " 4' - 2 " 4' - 2 " 38 ' - 0 " 11 ' - 8 " 38 ' - 0 " 4' - 2 " 4'-0"8'-7"23'-3"17'-7"6'-7" 96 ' - 0 " 14'-0"60'-0" 1 A3.2 60'-0"14'-0" 1 A3.2 W1 W1 W3 W3 W3 W3 W1 W1 W1 W1 W2 W2 W2 W2 W2 W2 W2 W2 4'-0"8'-7"23'-3"17'-7"6'-7" 4' - 2 " 19 ' - 1 0 " 24 ' - 0 " 24 ' - 0 " 19 ' - 1 0 " 4' - 2 " 4'-0"8'-7"23'-3"17'-7"6'-7" 96 ' - 0 " 60'-0" 60'-0" W1 W1 W3 W3 W3 W3 W1 W1 W1 W1 W2 W2 W2 W2 W2W2 W2 W2 fire riser roof below 9" / 12" 1'-0" wall below 6' - 2 " 134'-0" 134'-0" F.E.C.F.E.C. W2 W2 W3W3 W2 W2 1 A2.2 8" furr-out for gas piping. length of furr- out to be determined by gas meter size. 8" furr-out for gas piping. length of furr- out to be determined by gas meter size. UNIT type 3 UNIT 201 UNIT type 2 UNIT 203 UNIT type 1 UNIT 205 UNIT type 1 UNIT 202 UNIT type 2 UNIT 204 UNIT type 3 UNIT 206 UNIT type 3 UNIT 212 UNIT type 2 UNIT 210 UNIT type 1 UNIT 208 UNIT type 1 UNIT 211 UNIT type 2 UNIT 209 UNIT type 3 UNIT 207 1 1 1 1 A A B B A A A A A A AA BB AA A A A A STATE OF IDAHO BRENT A. McFARLAND AR-2561 11 5 2 B O N D A V E N U E - S u i t e A RE X B U R G , I D A H O 8 3 4 4 0 VO I C E ( 2 0 8 ) 3 5 9 - 2 3 0 9 F A X ( 2 0 8 ) 3 5 9 - 2 2 7 1 WW W . J R W A . C O M Job Number: Date: Drawn By: STRUCTURAL ENGINEERING Frost Structural Engineering 1020 Lincoln Road Idaho Falls, ID 83401 Tel: (208) 227-8404 Fax: (208) 227-8405 MECHANICAL ENGINEERING Engineered Systems Assoc. 1335 East Center Street Pocetello, Idaho 83204 Tel:(208) 233-0501 Fax:(208) 233-0529 ELECTRICAL ENGINEERING Payne Engineering INC. 1832 East Center Street Pocetello, Idaho 83201 Tel: (208) 232-4439 Fax: (208) 232-1435 Checked By: Plot Date: Consultants: Drawing Number: File: Revisions: Pr o j e c t : Dr a w i n g T i t l e : ® J R W & A S S O C I A T E S , P L L C . D R A W I N G S A N D D E S I G N S A R E PR O T E C T E D B Y C O P Y R I G H T A N D T H E A R C H I T E C T R E T A I N S T O TA L O W N E R S H I P A N D C O N T R OL . A N Y U N A U T H O R I Z E D U S E O F D R A W I N G S , D E S I G N S O R I D EA S W I T H O U T W R I T T E N C O N S E N T O F T H E A R C H I T E C T I S P R O HI B I T E D OF 3/9/2023 3:14:31 PM S:\Drawings\870-Sweetwater Apartment - Madison Station\BIM CD\SWEETWATER APARTMENT-October Redlines.rvtA1.2 2N D F L O O R P L A N 870 MA D I S O N S T A T I O N A P T S . OCT, 2022 EUP BAM RE X B U R G ID A H O RE X B U R G , I D A H O 16 SCALE:3/16" = 1'-0" F.F. 2ND FLOOR PLAN NORTH 1 2/13/23 OWNER CHANGES W1 W2W1 W2W1 W2W1 2 2 2 CONTRACTOR'S OPTION, WINDOWS TO BE FIRE RATED OR HAVE APPROVED FIRE SPRINKLER WASH SYSTEM 2 CONTRACTOR'S OPTION, WINDOWS TO BE FIRE RATED OR HAVE APPROVED FIRE SPRINKLER WASH SYSTEM 2 2 3/9/23 RESPONSE TO CITY W D DW WD DW W D DW W D DW WD DW W D DW W D DW W D DW WD DW W D DW W D DW WD DW 1 A3.1 96 ' - 0 " 4' - 2 " 38 ' - 0 " 11 ' - 8 " 38 ' - 0 " 4' - 2 " 1 A3.2 2 A3.1 4'-0"8'-7"23'-3"17'-7"6'-7" 4' - 2 " 19 ' - 1 0 " 24 ' - 0 " 24 ' - 0 " 19 ' - 1 0 " 4' - 2 " 4'-0"8'-7"23'-3"17'-7"6'-7" 1 A3.2 W1 W1 W3 W3 W3 W3 W1 W1 W1 W1 W2 W2 W2 W2 W2 W2 W2 96 ' - 0 " 4'-0"8'-7"23'-3"17'-7"6'-7" 4' - 2 " 19 ' - 1 0 " 24 ' - 0 " 24 ' - 0 " 19 ' - 1 0 " 4' - 2 " 4'-0"8'-7"23'-3"17'-7"6'-7" W1 W1 W3 W3 W3 W3 W1 W1 W1 W1 W2 W2 W2 W2W2 W2 W2 6' - 2 " 134'-0" 134'-0" F.E.C.F.E.C. W2 W2 W3 W3 1 A2.2 60'-0"14'-0"60'-0" 60'-0"14'-0"60'-0" W2W2 W2 W2 8" furr-out for gas piping. length of furr- out to be determined by gas meter size. 8" furr-out for gas piping. length of furr- out to be determined by gas meter size. UNIT type 3 UNIT 301 UNIT type 2 UNIT 303 UNIT type 1 UNIT 305 UNIT type 1 UNIT 302 UNIT type 2 UNIT 304 UNIT type 3 UNIT 306 UNIT type 3 UNIT 312 UNIT type 2 UNIT 310 UNIT type 1 UNIT 308 UNIT type 1 UNIT 311 UNIT type 2 UNIT 309 UNIT type 3 UNIT 307 1 1 1 1 A A A A A A AA BB AA A A A A A A B B STATE OF IDAHO BRENT A. McFARLAND AR-2561 11 5 2 B O N D A V E N U E - S u i t e A RE X B U R G , I D A H O 8 3 4 4 0 VO I C E ( 2 0 8 ) 3 5 9 - 2 3 0 9 F A X ( 2 0 8 ) 3 5 9 - 2 2 7 1 WW W . J R W A . C O M Job Number: Date: Drawn By: STRUCTURAL ENGINEERING Frost Structural Engineering 1020 Lincoln Road Idaho Falls, ID 83401 Tel: (208) 227-8404 Fax: (208) 227-8405 MECHANICAL ENGINEERING Engineered Systems Assoc. 1335 East Center Street Pocetello, Idaho 83204 Tel:(208) 233-0501 Fax:(208) 233-0529 ELECTRICAL ENGINEERING Payne Engineering INC. 1832 East Center Street Pocetello, Idaho 83201 Tel: (208) 232-4439 Fax: (208) 232-1435 Checked By: Plot Date: Consultants: Drawing Number: File: Revisions: Pr o j e c t : Dr a w i n g T i t l e : ® J R W & A S S O C I A T E S , P L L C . D R A W I N G S A N D D E S I G N S A R E PR O T E C T E D B Y C O P Y R I G H T A N D T H E A R C H I T E C T R E T A I N S T O TA L O W N E R S H I P A N D C O N T R OL . A N Y U N A U T H O R I Z E D U S E O F D R A W I N G S , D E S I G N S O R I D EA S W I T H O U T W R I T T E N C O N S E N T O F T H E A R C H I T E C T I S P R O HI B I T E D OF 3/9/2023 3:14:32 PM S:\Drawings\870-Sweetwater Apartment - Madison Station\BIM CD\SWEETWATER APARTMENT-October Redlines.rvtA1.3 3R D F L O O R P L A N 870 MA D I S O N S T A T I O N A P T S . OCT, 2022 EUP BAM RE X B U R G ID A H O RE X B U R G , I D A H O 16 SCALE:3/16" = 1'-0" F.F. 3RD FLOOR PLAN NORTH 1 2/13/23 OWNER CHANGES 2 2 W2W1 W2W1 W2W1 W2W1 CONTRACTOR'S OPTION, WINDOWS TO BE FIRE RATED OR HAVE APPROVED FIRE SPRINKLER WASH SYSTEM 2 CONTRACTOR'S OPTION, WINDOWS TO BE FIRE RATED OR HAVE APPROVED FIRE SPRINKLER WASH SYSTEM 2 2 3/9/23 RESPONSE TO CITY elev0" F.F. 1ST FLOOR elev10'-3" F.F. 2ND FLOOR elev20'-6" F.F. 3RD FLOOR elev29'-7 1/2" ROOF 14 22 811 12 34 5 7 8 6 12 16 21 11 14 14 1 1013 15 22 8 11 1 2 3 4 57 8 6 12 16 21 11 1 10 13 18 23 23 15 elev0" F.F. 1ST FLOOR elev10'-3" F.F. 2ND FLOOR elev20'-6" F.F. 3RD FLOOR elev-4'-0" T.O.FOOTING elev29'-7 1/2" ROOF 1 A3.1 1221112 3344 5566 7 8888 6 9 10 11 12 13 15 8 16 18 19 20 21 2 34 5 6 10 11 13 8 21 7 9 11 12 15 8 16 19 20 21 9 11 8 21 3 4 5 6 11 111111 9' - 1 1 / 2 " 10 ' - 3 " 10 ' - 3 " 9 17 17 212121 9 9 21 17 17 17 17 17 17 17 23 23 10 131013 1010 A2.1 A 18 1 A2.2 STATE OF IDAHO BRENT A. McFARLAND AR-2561 11 5 2 B O N D A V E N U E - S u i t e A RE X B U R G , I D A H O 8 3 4 4 0 VO I C E ( 2 0 8 ) 3 5 9 - 2 3 0 9 F A X ( 2 0 8 ) 3 5 9 - 2 2 7 1 WW W . J R W A . C O M Job Number: Date: Drawn By: STRUCTURAL ENGINEERING Frost Structural Engineering 1020 Lincoln Road Idaho Falls, ID 83401 Tel: (208) 227-8404 Fax: (208) 227-8405 MECHANICAL ENGINEERING Engineered Systems Assoc. 1335 East Center Street Pocetello, Idaho 83204 Tel:(208) 233-0501 Fax:(208) 233-0529 ELECTRICAL ENGINEERING Payne Engineering INC. 1832 East Center Street Pocetello, Idaho 83201 Tel: (208) 232-4439 Fax: (208) 232-1435 Checked By: Plot Date: Consultants: Drawing Number: File: Revisions: Pr o j e c t : Dr a w i n g T i t l e : ® J R W & A S S O C I A T E S , P L L C . D R A W I N G S A N D D E S I G N S A R E PR O T E C T E D B Y C O P Y R I G H T A N D T H E A R C H I T E C T R E T A I N S T O TA L O W N E R S H I P A N D C O N T R OL . A N Y U N A U T H O R I Z E D U S E O F D R A W I N G S , D E S I G N S O R I D EA S W I T H O U T W R I T T E N C O N S E N T O F T H E A R C H I T E C T I S P R O HI B I T E D OF 3/7/2023 3:46:53 PM S:\Drawings\870-Sweetwater Apartment - Madison Station\BIM CD\SWEETWATER APARTMENT-October Redlines.rvtA3.1 BU I L D I N G S E C T I O N S 870 MA D I S O N S T A T I O N A P T S . OCT, 2022 eup bam RE X B U R G ID A H O RE X B U R G , I D A H O 16SCALE:3/16" = 1'-0" Section b SCALE:3/16" = 1'-0" Section A KEY NOTES 1 FOOTING AND FOUNDATION AS PER STRUCTURAL DRAWINGS 2 COMPACTED ENGINEERED FILL 3 6" FREE DRAINING GRAVEL 4 VAPOR BARRIER 5 4" CONCRETE SLAB - SEE STRUCTURE 6 TREATED 2X PLATE W/ ANCHOR BOLTS - SEE STRUCTURAL DRAWINGS 7 BITUMINOUS DAMPPROOFING 8 (2) LAYERS 5/8" TYPE 'x' GYP. BD. ON CHANNELS (1 HOUR RATED CEILING) 9 3" CONCRETE ON FLOOR STRUCTURE, SEE STRUCTRAL DRAWINGS 10 2 LAYERS 5/8" TYPE 'X' GYP. BD. CEILING (1 HOUR RATED) 11 SOUND BATT INSULATION - FLOORS. fill cavity 12 EXTERIOR WALL BATT INSULATION. r-21 13 FOIL SCRIM KRAFT (FSK) BATT INSULATION ABOVE SUSPENDED GYP. CEILING SYSTEMS IN ATTIC SPACE. r-50 14 sound batt insulation - walls. Fill cavity 15 ARCHITECTURAL ASPHALT SHINGLES ON ICE & WATER SHEILD ON 30# BUILDING FELT THROUGHOUT. 16 5/8" TYPE 'X' GYP. BD. (INSIDE ONLY) 17 5/8" TYPE 'X' GYP. BD. (1 LAYER EA. SIDE OF WALL) 1 HOUR FIRE RATED 18 ATTIC DRAFT STOP - (1) LAYER 5/8" TYPE 'X' GYP. BD. ON (1) SIDE OF ROOF TRUSS TAPE ALL JOINTS AND SEAL ALL PENETRATIONS 19 AIR INFILTRATION BARRIER - TYVEK COMMERCIAL WRAP "d" OR EQUAL, ALL JOINTS AND PENETRATIONS TO BE TAPED AND SEALED, TYPICAL, ALL EXTERIOR WALLS 20 SHEATHING 21 1" GYP. CRETE ON 1/4" SOUND REDUCTION BD. (1 1/4" GYP. CRETE IF SOUND BD. IS DELETED) ON FLOOR SEATHING 22 11 7/8" TJI FLOOR JOIST - SEE STRUCTURAL DRAWINGS 23 2" r-10 rigid insulation MINIMUM INSULATION VALUES • EXTERIOR WALL R21 • ROOF R38 • FOUNDATION WALL R20 • SOUND INSULATED FLOOR R11 CONTRACTOR'S OPTION, WINDOWS TO BE FIRE RATED OR HAVE APPROVED FIRE SPRINKLER WASH SYSTEM R22 R49 AS REQ'D FOR STC RATING OF 50 MIN 2 2 3/9/23 RESPONSE TO CITY elev0" F.F. 1ST FLOOR elev10'-3" F.F. 2ND FLOOR elev20'-6" F.F. 3RD FLOOR A3.2 2 A3.2 3 STEEL STRUCTURE - SEE STRUCTURAL CONC. LANDING OVER STEEL DECK -SEE STRUCT. 4" x 4" x 1/4" STEEL ANGLE WELD TO BEAM AND STRINGER 1 x 2" x 1/4" x REQ'D LENGTH WELD TO PLATE STAIR STRINGER SEE STRUCT. 1" WIDE VISUAL MARKING STRIPE TREAD: PRECAST CONC. BOLT TO ANGLE 5/8" BOLTS CAST INTO TREAD (2) EA. END 3/16" PLATE RISER WELDED TO STRINGER EA. END STEEL BEAM SEE STRUCT. STEEL ANGLE BRACKET 1 1/2" x 1 1/2" x 3/16" WELD AT STRINGER 1" SQUARE TUBE STEEL WELDED TO RAILS 1 1/2" SQUARE TUBE STEEL TOP RAILS 3" SQUARE TUBE STEEL RISER WELDED TO STRINGER 1 1/2" 0 O.D. TUBE STEEL HAND RAIL A A STAIR STRINGER SEE STRUCT.STAIR STRINGER SEE STRUCT. 1 1/2" SQUARE TUBE STEEL TOP RAIL 1 1/2" 0 O.D. TUBE STEEL HAND RAIL 1 1/2" SQUARE TUBE STEEL BOTTOM RAIL • ALL WELDS TO BE GROUND SMOOTH • ALL STEEL RAILING COMPONENTS TO BE POWDER COATED • COMPONENTS SHALL BE ASSEMBLED SO AS A 4" 0 CYLINDER CANNOT PASS THROUGH GAP 3" SQUARE TUBE STEEL RISER WELDED TO STRINGER NOTCH RISER AT STRINGER GRIND WELDS SMOOTH ELEVATION SECTION A TREAD: PRECAST CONC. BOLT TO ANGLE 5/8" BOLTS CAST INTO TREAD (2) EA. END TREAD: PRECAST CONC. BOLT TO ANGLE 5/8" BOLTS CAST INTO TREAD (2) EA. END CLCL CL CL STATE OF IDAHO BRENT A. McFARLAND AR-2561 11 5 2 B O N D A V E N U E - S u i t e A RE X B U R G , I D A H O 8 3 4 4 0 VO I C E ( 2 0 8 ) 3 5 9 - 2 3 0 9 F A X ( 2 0 8 ) 3 5 9 - 2 2 7 1 WW W . J R W A . C O M Job Number: Date: Drawn By: STRUCTURAL ENGINEERING Frost Structural Engineering 1020 Lincoln Road Idaho Falls, ID 83401 Tel: (208) 227-8404 Fax: (208) 227-8405 MECHANICAL ENGINEERING Engineered Systems Assoc. 1335 East Center Street Pocetello, Idaho 83204 Tel:(208) 233-0501 Fax:(208) 233-0529 ELECTRICAL ENGINEERING Payne Engineering INC. 1832 East Center Street Pocetello, Idaho 83201 Tel: (208) 232-4439 Fax: (208) 232-1435 Checked By: Plot Date: Consultants: Drawing Number: File: Revisions: Pr o j e c t : Dr a w i n g T i t l e : ® J R W & A S S O C I A T E S , P L L C . D R A W I N G S A N D D E S I G N S A R E PR O T E C T E D B Y C O P Y R I G H T A N D T H E A R C H I T E C T R E T A I N S T O TA L O W N E R S H I P A N D C O N T R OL . A N Y U N A U T H O R I Z E D U S E O F D R A W I N G S , D E S I G N S O R I D EA S W I T H O U T W R I T T E N C O N S E N T O F T H E A R C H I T E C T I S P R O HI B I T E D OF 3/7/2023 3:46:53 PM S:\Drawings\870-Sweetwater Apartment - Madison Station\BIM CD\SWEETWATER APARTMENT-October Redlines.rvtA3.2 ST A I R S E C T I O N S 870 MA D I S O N S T A T I O N A P T S . OCT, 2022 EUP BAM RE X B U R G ID A H O RE X B U R G , I D A H O 16 SCALE:1/2" = 1'-0"A3.2 1STAIR SECTION SCALE:1 1/2" = 1'-0"A3.2 2STAIR DETAIL SCALE:3/4" = 1'-0"A3.2 3STAIR DETAIL RISE HEIGHT: 4-7" MIN. TREAD DEPTH: 11"2 34 - 36" A.F.F. 42" A.F.F. 2 2 3/9/23 RESPONSE TO CITY plywood sheathing -see structural 5/8" TYPE 'X' GYP. BD. 2x6 STUD WALL @ 16" O.C. SEAL ALL PENETRATIONS BY AN APPROVED MEANS TO MAINTAIN FIRE RATING 1 HOUR FIRE RATED r-21 batt insulation 5/8" TYPE 'X' GYP. BD. OR FIBERGLASS REINFORCED GYP. BD. WHERE EXPOSED TO WEATHER. siding per owner's selection vapor barrier 5/8" TYPE 'X' GYP. BOARD SOUND ATTENUATION BAtt INSULATION 5/8" TYPE 'X' GYP. BOARD DOUBLE 2x4 STUD WALL @ 16" O.C. STAGGER STUD SEAL ALL PENETRATIONS BY AN APPROVED MEANS TO MAINTAIN FIRE RATING 1 HOUR FIRE RATED SOUND ATTENUATION plywood sheathing -see structural 5/8" TYPE 'X' GYP. BD. 2x6 STUD WALL @ 16" O.C. r-21 batt insulation siding per owner's selection vapor barrier 5/8" GYP. BD. EA. SIDE 2x4 STUD WALL @ 16" O.C. 5/8" GYP. BD. EA. SIDE 2x4 STUD WALL @ 16" O.C. STATE OF IDAHO BRENT A. McFARLAND AR-2561 11 5 2 B O N D A V E N U E - S u i t e A RE X B U R G , I D A H O 8 3 4 4 0 VO I C E ( 2 0 8 ) 3 5 9 - 2 3 0 9 F A X ( 2 0 8 ) 3 5 9 - 2 2 7 1 WW W . J R W A . C O M Job Number: Date: Drawn By: STRUCTURAL ENGINEERING Frost Structural Engineering 1020 Lincoln Road Idaho Falls, ID 83401 Tel: (208) 227-8404 Fax: (208) 227-8405 MECHANICAL ENGINEERING Engineered Systems Assoc. 1335 East Center Street Pocetello, Idaho 83204 Tel:(208) 233-0501 Fax:(208) 233-0529 ELECTRICAL ENGINEERING Payne Engineering INC. 1832 East Center Street Pocetello, Idaho 83201 Tel: (208) 232-4439 Fax: (208) 232-1435 Checked By: Plot Date: Consultants: Drawing Number: File: Revisions: Pr o j e c t : Dr a w i n g T i t l e : ® J R W & A S S O C I A T E S , P L L C . D R A W I N G S A N D D E S I G N S A R E PR O T E C T E D B Y C O P Y R I G H T A N D T H E A R C H I T E C T R E T A I N S T O TA L O W N E R S H I P A N D C O N T R OL . A N Y U N A U T H O R I Z E D U S E O F D R A W I N G S , D E S I G N S O R I D EA S W I T H O U T W R I T T E N C O N S E N T O F T H E A R C H I T E C T I S P R O HI B I T E D OF 3/7/2023 3:46:54 PM S:\Drawings\870-Sweetwater Apartment - Madison Station\BIM CD\SWEETWATER APARTMENT-October Redlines.rvtA3.3 WA L L T Y P E S 870 MA D I S O N S T A T I O N A P T S . OCT, 2022 JRN BAM RE X B U R G ID A H O RE X B U R G , I D A H O 16 wall type 1wall type 2wall type 3wall type 4wall type 5 2 2 3/9/23 RESPONSE TO CITY 2 panel PATIO SE E S C H E D U L E SEE SCHEDULE 12 " A B SEE SCHEDULE SE E S C H E D U L E 2" VA R I E S VA R I E S 3" HOLLOW METAL FI E L D VE R I F Y BA WOOD FRAME 3" 4 3/4" 5/8" TYPE 'X' GYP. BOARD EACH SIDE HEADER SEE STRUCT. WOOD STUD WALL, SEE WALL TYPE 2 4 2 4 HARDWOOD FRAME 3" 4 3 / 4 " 5/8" TYPE 'X' GYP. BOARD EACH SIDE DOUBLE STUD 2 4 2 4 WOOD STUD WALL, SEE WALL TYPE HARDWOOD FRAME 9" 2 6 HOLLOW METAL FRAME INSULATED CONTINUOUS CAULK BOTH SIDES HEADER SEE STRUCT. INSULATE 2X6 STUD WALLSEE WALL TYPES FOR WALL CONSTRUCTION AT DOOR LOCATION CONTINUOUS CAULK BOTH SIDESHOLLOW METAL FRAME INSULATED 2 6 2 6 FRAME ANCHOR INSULATE 2X6 STUD wall SEE WALL TYPES FOR WALL CONSTRUCTION AT DOOR LOCATION STATE OF IDAHO BRENT A. McFARLAND AR-2561 11 5 2 B O N D A V E N U E - S u i t e A RE X B U R G , I D A H O 8 3 4 4 0 VO I C E ( 2 0 8 ) 3 5 9 - 2 3 0 9 F A X ( 2 0 8 ) 3 5 9 - 2 2 7 1 WW W . J R W A . C O M Job Number: Date: Drawn By: STRUCTURAL ENGINEERING Frost Structural Engineering 1020 Lincoln Road Idaho Falls, ID 83401 Tel: (208) 227-8404 Fax: (208) 227-8405 MECHANICAL ENGINEERING Engineered Systems Assoc. 1335 East Center Street Pocetello, Idaho 83204 Tel:(208) 233-0501 Fax:(208) 233-0529 ELECTRICAL ENGINEERING Payne Engineering INC. 1832 East Center Street Pocetello, Idaho 83201 Tel: (208) 232-4439 Fax: (208) 232-1435 Checked By: Plot Date: Consultants: Drawing Number: File: Revisions: Pr o j e c t : Dr a w i n g T i t l e : ® J R W & A S S O C I A T E S , P L L C . D R A W I N G S A N D D E S I G N S A R E PR O T E C T E D B Y C O P Y R I G H T A N D T H E A R C H I T E C T R E T A I N S T O TA L O W N E R S H I P A N D C O N T R OL . A N Y U N A U T H O R I Z E D U S E O F D R A W I N G S , D E S I G N S O R I D EA S W I T H O U T W R I T T E N C O N S E N T O F T H E A R C H I T E C T I S P R O HI B I T E D OF 3/9/2023 2:45:27 PM S:\Drawings\870-Sweetwater Apartment - Madison Station\BIM CD\SWEETWATER APARTMENT-October Redlines.rvtA5.1 DO O R S C H E D U L E 870 MA D I S O N S T A T I O N A P T S . OCT, 2022 JRN BAM RE X B U R G ID A H O RE X B U R G , I D A H O 16 DOOR SCHEDULE MA R K SI N G L E PA I R DO O R T Y P E DOOR FRAME DETAILS UL L A B E L ( I N M I N U T E S ) REMARKS SIZE MA T E R I A L FI N I S H FR A M E T Y P E FI N I S H HE A D JA M B WI D T H HE I G H T TH I C K N E S S A1 ●A 3'-0" 6'-8" 1 3/4" METAL PAINT B PAINT 3/A5.1 4/A5.1 20 INSULATED A2 ●A 2'-0" 6'-8" 1 3/4" WOOD PAINT A PAINT 1/A5.1 2/A5.1 A3 ●A 2'-0" 6'-8" 1 3/4" WOOD PAINT A PAINT 1/A5.1 2/A5.1 A4 ●A 5'-0" 6'-8" 1 3/4" WOOD PAINT A PAINT 1/A5.1 2/A5.1 A5 ●A 2'-10" 6'-8" 1 3/4" WOOD PAINT A PAINT 1/A5.1 2/A5.1 A6 ●A 2'-10" 6'-8" 1 3/4" WOOD PAINT A PAINT 1/A5.1 2/A5.1 A7 ●A 2'-10" 6'-8" 1 3/4" WOOD PAINT A PAINT 1/A5.1 2/A5.1 A8 ●B 6'-0" 6'-8" 1 3/4" METAL PAINT A PAINT 1/A5.1 2/A5.1 INSULATED A9 ●A 2'-6" 6'-8" 1 3/4" METAL PAINT A PAINT 1/A5.1 2/A5.1 INSULATED A10 ●A 2'-10" 6'-8" 1 3/4" WOOD PAINT A PAINT 1/A5.1 2/A5.1 B1 ●A 3'-0" 6'-8" 1 3/4" METAL PAINT B PAINT 3/A5.1 4/A5.1 20 INSULATED B2 ●A 2'-0" 6'-8" 1 3/4" WOOD PAINT A PAINT 1/A5.1 2/A5.1 B3 ●A 3'-0" 6'-8" 1 3/4" WOOD PAINT - - 1/A5.1 2/A5.1 BARN DOOR HARDWARE B4 ●A 4'-0" 6'-8" 1 3/4" WOOD PAINT A PAINT 1/A5.1 2/A5.1 B5 ●A 2'-10" 6'-8" 1 3/4" WOOD PAINT A PAINT 1/A5.1 2/A5.1 B6 ●B 6'-0" 6'-8" 1 3/4" METAL PAINT A PAINT 1/A5.1 2/A5.1 INSULATED B7 ●A 2'-6" 6'-8" 1 3/4" METAL PAINT A PAINT 1/A5.1 2/A5.1 INSULATED B8 ●A 2'-10" 6'-8" 1 3/4" WOOD PAINT A PAINT 1/A5.1 2/A5.1 B9 ●A 2'-10" 6'-8" 1 3/4" WOOD PAINT A PAINT 1/A5.1 2/A5.1 B10 ●A 2'-10" 6'-8" 1 3/4" WOOD PAINT A PAINT 1/A5.1 2/A5.1 C1 ●A 3'-0" 6'-8" 1 3/4" METAL PAINT B PAINT 3/A5.1 4/A5.1 20 INSULATED C2 ●A 2'-0" 6'-8" 1 3/4" WOOD PAINT A PAINT 1/A5.1 2/A5.1 C3 ●A 4'-0" 6'-8" 1 3/4" WOOD PAINT A PAINT 1/A5.1 2/A5.1 C4 ●A 2'-10" 6'-8" 1 3/4" WOOD PAINT A PAINT 1/A5.1 2/A5.1 C5 ●A 2'-10" 6'-8" 1 3/4" WOOD PAINT A PAINT 1/A5.1 2/A5.1 C6 ●A 4'-0" 6'-8" 1 3/4" WOOD PAINT A PAINT 1/A5.1 2/A5.1 C7 ●B 5'-0" 6'-8" 1 3/4" METAL PAINT A PAINT 1/A5.1 2/A5.1 INSULATED C8 ●A 2'-6" 6'-8" 1 3/4" METAL PAINT A PAINT 1/A5.1 2/A5.1 INSULATED C9 ●A 2'-10" 6'-8" 1 3/4" WOOD PAINT A PAINT 1/A5.1 2/A5.1 C10 ●A 2'-10" 6'-8" 1 3/4" WOOD PAINT A PAINT 1/A5.1 2/A5.1 C11 ●A 2'-10" 6'-8" 1 3/4" WOOD PAINT A PAINT 1/A5.1 2/A5.1 F1 ●A 3'-0" 6'-8" 1 3/4" METAL PAINT B PAINT 3/A5.1 4/A5.1 30 F2 ●A 3'-0" 6'-8" 1 3/4" METAL PAINT B PAINT 3/A5.1 4/A5.1 30 SCALE:n.t.s. DOOR TYPES SCALE:n.t.s. TYP. FRAME PROFILE SCALE:N.T.S.A5.1 1HEADER - 2x4 SCALE: N.T.S.A5.1 2JAMB - 2x4 SCALE: N.T.S.A5.1 3HEADER - 2X6 SCALE: N.T.S.A5.1 4JAMB - 2X6 NOTE:FOR DOOR CHANGES IN TYPE 'A' UNITS, SEE ENLARGED FLOOR PLANS ON SHEETS A6.1-A6.3. , SELF CLOSING , SELF CLOSING , SELF CLOSING , SELF CLOSING , SELF CLOSING , SELF CLOSING SELF CLOSING SELF CLOSING NOTE: ALL RATED DOORS TO BE SELF CLOSING. SEE DETAIL 5/A5.1 FOR TYPICAL EXTERIOR DETAILS ALL GLAZING IN DOORS TO BE TEMPERED 2 2 2 2 2 SCALE: N.T.S.A5.1 4JAMB - 2X6 TYPICAL EXTERIOR THRESHOLD 5 2 2 3/9/23 RESPONSE TO CITY A B SEE SCHEDULE SE E S C H E D U L E SEE SCHEDULE SE E S C H E D U L E WINDOW NOTES • GLAZING FOR TYPE 1 TO BE 1" INSULATED LOW "E" ON ALL SIDEs • GLAZING TO BE CLEAR 2 6 2 6 SHEATHING W/ BLDG. WRAP 2x6 STUD WALL INSULATED CONTINUOUS CAULK EA. SIDE. TYPICAL DRIP FLASHING SHIM AS NEEDED 5/8" TYPE 'X' GYP. BD. TEXTURE AND PAINT SEE WINDOW SCHED. FOR WINDOW TYPE SIDING PER OWNER'S SELECTION VINYL 'J' TRIM 5/8" TYPE 'X' GYP. BD. WHERE OCCURS. SEE WALL TYPES R 1 /2 " 2 6 2 6 CONTINUOUS CAULK EA. SIDE. TYP. 1/2" SHEATHING 2x6 STUD WALL INSULATED AIR INFILTRATION BARRIER WOOD SILL PAINTED 5/8" TYPE 'X' GYP. BD. TEXTURE AND PAINT SEE WINDOW SCHED. FOR WINDOW TYPES 5/8" TYPE 'X' GYP. BD. WHERE OCCURS 6 2 6 1/2" SHEATHING 2x6 STUD WALL INSULATED CONTINUOUS CAULK EA. SIDE. TYPICAL 2 SHIM AS NEEDED SEE WINDOW SCHED. FOR WINDOW TYPE 5/8" TYPE 'X' GYP. BD. TEXTURE AND PAINT 5/8" TYPE 'X' GYP BD. WHERE OCCURS AIR INFILTRATION BARRIER 3/4" WOOD SILL PAINTED 3/4"x3 1/2" WOOD TRIM PAINTED SIDING PER OWNER'S SELECTION STATE OF IDAHO BRENT A. McFARLAND AR-2561 11 5 2 B O N D A V E N U E - S u i t e A RE X B U R G , I D A H O 8 3 4 4 0 VO I C E ( 2 0 8 ) 3 5 9 - 2 3 0 9 F A X ( 2 0 8 ) 3 5 9 - 2 2 7 1 WW W . J R W A . C O M Job Number: Date: Drawn By: STRUCTURAL ENGINEERING Frost Structural Engineering 1020 Lincoln Road Idaho Falls, ID 83401 Tel: (208) 227-8404 Fax: (208) 227-8405 MECHANICAL ENGINEERING Engineered Systems Assoc. 1335 East Center Street Pocetello, Idaho 83204 Tel:(208) 233-0501 Fax:(208) 233-0529 ELECTRICAL ENGINEERING Payne Engineering INC. 1832 East Center Street Pocetello, Idaho 83201 Tel: (208) 232-4439 Fax: (208) 232-1435 Checked By: Plot Date: Consultants: Drawing Number: File: Revisions: Pr o j e c t : Dr a w i n g T i t l e : ® J R W & A S S O C I A T E S , P L L C . D R A W I N G S A N D D E S I G N S A R E PR O T E C T E D B Y C O P Y R I G H T A N D T H E A R C H I T E C T R E T A I N S T O TA L O W N E R S H I P A N D C O N T R OL . A N Y U N A U T H O R I Z E D U S E O F D R A W I N G S , D E S I G N S O R I D EA S W I T H O U T W R I T T E N C O N S E N T O F T H E A R C H I T E C T I S P R O HI B I T E D OF 3/9/2023 2:45:27 PM S:\Drawings\870-Sweetwater Apartment - Madison Station\BIM CD\SWEETWATER APARTMENT-October Redlines.rvtA5.2 WI N D O W S C H E D U L E 870 MA D I S O N S T A T I O N A P T S . OCT, 2022 eup BAM RE X B U R G ID A H O RE X B U R G , I D A H O 16 WINDOW SCHEDULE MARK SIZE FRAME REMARKSWIDTH HEIGHT MAT. FIN. OPER GLAZ'G BLINDS A 6'-0" 5'-0" VINYL FACTORY SLIDING 1 Yes B 6'-0" 5'-0" VINYL FACTORY FIXED 1 Yes SCALE:1/2" = 1'-0" WINDOW TYPES SCALE: N.T.S.A5.2 4WINDOW HEADER SCALE: N.T.S.A5.2 5WINDOW JAMB SCALE: N.T.S.A5.2 6WINDOW SILL GLAZING WITHIN 24" OF DOOR SHALL BE TEMPERED 2 2 3/9/23 RESPONSE TO CITY CONTRACTOR'S OPTION; WINDOW B TO BE PROTECTED BY FIRE SUPPRESSION WINDOW WASH OR 20 MIN. UL RATED 2 CAST IN PLACE CENTERLINE CENTERLINE OF BEAM CENTERLINE OF COLUMN CENTERLINE OF WALL CLEAR CONCRETE CONCRETE CONTROL JOINT CONCRETE SAWCUT JOINT CONCRETE MASONRY UNIT CONNECTION CONTINUOUS DEAD LOAD DOWN DRAWING(S) EQUAL EQUIPMENT EXPANSION JOINT EACH WAY FINISHED FLOOR FACE OF STEEL FACE OF WALL GAUGE GALVANIZED GENERAL STRUCTURAL NOTES CENTERLINE OF FOOTING FACE OF MEMBER EXPANSION BOLT EDGE OF SLAB DIAMETER GALV. GSN DN. DWG(S) EQ. EQUIP. EXP. JT (E.J.) E.W. F.F. F.O.S. F.O.W. GA. F.O.M. EXP. BOLT E.O.S. o OR DIA. C.I.P. C.L. C.L.B. C.L.C. C.L.W. CLR CONC C.C.J. C.S.J. C.M.U. CONN. CONT. D.L. C.L.F. W/ WITH W/O WITHOUT T.O.P. U.N.O. W.W.F. TYP. VERT T.O.S. T.O.W. T.O.D. T.O.F. T.O.L. T.O.M. STD T.O.B. T.L. SLH SLV SIM. SQ. PSF PSI REINF. PREFAB OPP. P.C. PLF N.T.S. O.C. O.F.W. TOP OF FOOTING UNLESS NOTED OTHERWISE WELDED WIRE FABRIC TOP OF MASONRY TOP OF PLATE TOP OF STEEL TOP OF WALL TYPICAL VERTICAL STANDARD TOP OF BEAM TOP OF DECK TOP OF LEDGER TOTAL LOAD OUTSIDE FACE OF WALL PRECAST CONCRETE POUNDS PER LINEAR FOOT POUNDS PER SQUARE FOOT POUNDS PER SQUARE INCH SHORT LEG VERTICAL SHORT LEG HORIZONTAL REINFORCING SIMILAR SQUARE NOT TO SCALE ON CENTER OPPOSITE PREFABRICATED AGGREGATE BASE COURSE AIR CONDITIONER ABOVE FINISHED FLOOR ALTERNATE ANCHOR BOLT AT (MEASUREMENT) BEAM BOTTOM OF BEAM BOTTOM OF DECK BEARING BELOW FINISHED FLOOR BOTTOM OF FOOTING A.B.C. A/C A.F.F. ALT. A.B. @ BM B.O.B. B.O.D. BRG B.F.F B.O.F. ABBREVIATIONS LBS (#) MFR('S) M.C.J. MECH'L. N/A LLV LLH HORIZ. K(KIP) GLB (GLULAM) I.F.W. L.L. LONG LEG VERTICAL MANUFACTURER('S) MASONRY CONTROL JOINT NOT APPLICABLE LONG LEG HORIZONTAL GLUED-LAMINATED BEAM INSIDE FACE OF WALL POUNDS MECHANICAL HORIZONTAL 1000 POUNDS LIVE LOAD EXISTING(E) MIN.MINIMUM MAX.MAXIMUM SYMBOLS LEDGEND WALLS WITH SOLID LINES DESIGNATE STRUCTURAL (BEARING) WALLS. WALLS WITH DASHED LINES DESIGNATE NON-STRUCTURAL (NON-BEARING) WALLS. WALLS WITH HATCH DESIGNATE MASONRY WALLS. , , , -AS SHOWN ON PLAN INDICATES A SHEARWALL; HATCHING IN WALL DESIGNATES SHEARWALL LENGTH. 5 6 7 , , - AS SHOWN ON PLAN INDICATES A SHEARWALL HOLDOWN. SEE HOLDOWN SCHEDULES AND DETAILS FOR ADDITIONAL INFORMATION. A B INDICATES HVAC EQUIPMENT ON ROOF OR IN ATTIC SPACE. SEE TYPICAL DETAILS FOR FRAMING INFORMATION. - AS SHOWN ON PLAN INDICATES A HELICAL PIER. XXXX CS16, CMSTC16, ECT. - AS SHOWN AT WALL OPENINGS INDICATE STRAPPING, PROVIDE STRAPPING PER "TYPICAL STRAP AT OPENING" DETAIL. D=xxx# INDICATES DRAG LOAD (ASD) THAT TRUSS MANUFACTURER IS TO DESIGN TRUSS FOR IN BOTH TENSION AND COMPRESSION. STEP INDICATES STEPPED OR DEPRESSED SLAB. C=X" INDICATES CAMBER IN BEAM. INDICATES RIDGID CONNECTION. (NOT ALL SYMBOLS NECESSARILY APPLY TO THIS PROJECT) P1, P2, ETC. AS SHOWN ON PLAN INDICATES A WOOD POST. SEE POST SCHEDULE FOR MORE INFORMATION. SC1, SC2, ETC. - AS SHOWN ON PLAN INDICATES A STEEL COLUMN. SEE STEEL COLUMN SCHEDULE FOR ADDITIONAL INFORMATION. COLUMNS START AT THE LEVEL THEY ARE CALLED OUT ON. PX SCX RME XXX# 11 5 2 B O N D A V E N U E - S u i t e A RE X B U R G , I D A H O 8 3 4 4 0 VO I C E ( 2 0 8 ) 3 5 9 - 2 3 0 9 F A X ( 2 0 8 ) 3 5 9 - 2 2 7 1 WW W . J R W A . C O M Job Number: Date: Drawn By: STRUCTURAL ENGINEERING Frost Structural Engineering 1020 Lincoln Road Idaho Falls, ID 83401 Tel: (208) 227-8404 Fax: (208) 227-8405 MECHANICAL ENGINEERING Engineered Systems Assoc. 1335 East Center Street Pocetello, Idaho 83204 Tel:(208) 233-0501 Fax:(208) 233-0529 ELECTRICAL ENGINEERING Payne Engineering INC. 1832 East Center Street Pocetello, Idaho 83201 Tel: (208) 232-4439 Fax: (208) 232-1435 Checked By: Plot Date: Consultants: Drawing Number: Revisions: Pr o j e c t : Dr a w i n g T i t l e : ® J R W & A S S O C I A T E S , P L L C . D R A W I N G S A N D D E S I G N S A R E P R O T EC T E D B Y C O P Y R I G H T A N D T H E A R C H I T E C T R E T A I N S T O T A L O W N E RS H I P A N D C O N T R OL . A N Y U N A U T H O R I Z E D U S E O F D R A W I N G S , D E S I G N S O R I D E A S WI T H O U T W R I T T E N C O N S E N T O F T H E A R C H I T E C T I S P R O H I B I T ED 3/1/2023 7:56:56 AM S1.0 GE N E R A L S T R U C T U R A L N O T E S MA D I S O N S T A T I O N A P T S . 09/27/2022 RE X B U R G ID A H O RE X B U R G , I D A H O SHEET INDEX SHEET DESCRIPTION DETAILS S1.0 GENERAL STRUCTURAL NOTES --- S1.1 SPECIAL INSPECTIONS --- S1.2 TYPICAL DETAILS T - SERIES S1.3 TYPICAL DETAILS T - SERIES S1.4 PLAN SCHEDULES --- S2.0 FOUNDATION PLAN --- S2.0A FOUNDATION PLAN CRAWL SPACE OPTION --- S2.0B FIRST FLOOR FRAMING PLAN CRAWL SPACE OPTION --- S2.1 SECOND FLOOR FRAMING PLAN --- S2.2 THIRD FLOOR FRAMING PLAN --- S2.3 ROOF FRAMING PLAN --- S3.0 FOUNDATION DETAILS 100 - SERIES S3.0A CRAWL SPACE FOUNDATION DETAILS 100 - SERIES S4.0 FLOOR FRAMING DETAILS 200 - SERIES S4.1 FLOOR FRAMING DETAILS 200 - SERIES S5.0 ROOF FRAMING DETAILS 300 - SERIES LOCATION LIVE / SNOW LOAD DEAD LOAD ELEMENTS LIVE LOAD TOTAL LOAD LOCATION:MINIMUM COVER TOLERANCE USE:CONCRETE STRENGTH: MAX W/C RATIO AIR ENTRAINMENT USE:MATERIAL: GENERAL REQUIREMENTS: BASIS FOR DESIGN: FOUNDATION NOTES:CONCRETE:WOOD:DEFERRED SUBMITTAL ITEMS: 1.THE STRUCTURAL SYSTEMS AND MEMBERS DEPICTED HEREIN HAVE BEEN DESIGNED PRIMARILY TO SAFEGUARD AGAINST MAJOR STRUCTURAL DAMAGE AND LOSS OF LIFE, NOT TO LIMIT DAMAGE OR MAINTAIN FUNCTION (IBC SECTION 101.3). 2.THESE DRAWINGS, AND THEIR ASSOCIATED STRUCTURAL CALCULATIONS, HAVE BEEN PERFORMED USING STANDARDS OF PROFESSIONAL CARE AND COMPLETENESS NORMALLY EXERCISED UNDER SIMILAR CIRCUMSTANCES BY REPUTABLE STRUCTURAL ENGINEER'S IN THIS OR SIMILAR LOCALITIES. THEY NECESSARILY ASSUME THAT THE WORK DEPICTED WILL BE PERFORMED BY AN EXPERIENCED CONTRACTOR AND/OR WORKMEN WHO HAVE A WORKING KNOWLEDGE OF THE INTERNATIONAL BUILDING CODE CONVENTIONAL FRAMING REQUIREMENTS AND OF INDUSTRY ACCEPTED STANDARD GOOD PRACTICE. AS NOT EVERY CONDITION OR FRAMING ELEMENT IS (OR CAN BE) EXPLICITLY SHOWN ON THESE DRAWINGS, IT IS UNDERSTOOD THAT THE CONTRACTOR WILL USE INDUSTRY ACCEPTED STANDARD GOOD PRACTICE FOR ALL MISCELLANEOUS WORK NOT EXPLICITLY SHOWN. 3.THESE DRAWINGS REPRESENT THE FINISHED STRUCTURE. THEY DO NOT INDICATE THE METHOD OF CONSTRUCTION. THE CONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR CONSTRUCTION MEANS, METHODS, TECHNIQUES, SEQUENCES AND PROCEDURES. CONSTRUCTION MATERIALS SHALL BE SPREAD OUT IF PLACED ON FRAMED CONSTRUCTION SUCH THAT DESIGN LIVE LOAD PER SQUARE FOOT AS STATED HEREIN IS NOT EXCEEDED. OPTIONS ARE FOR CONTRACTOR'S CONVENIENCE. IF AN OPTION IS USED, THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL NECESSARY CHANGES, AND SHALL COORDINATE ALL DETAILS. 4.WHERE DISCREPANCIES OCCUR BETWEEN PLANS, DETAILS, GENERAL STRUCTURAL NOTES AND SPECIFICATIONS, THE GREATER REQUIREMENTS SHALL GOVERN. TYPICAL DETAILS AND NOTES ARE NOT NECESSARILY INDICATED ON THE PLANS, BUT SHALL APPLY NONE-THE-LESS. WHERE NO DETAILS ARE SHOWN, CONSTRUCTION SHALL CONFORM TO SIMILAR WORK ON THE PROJECT. DETAILS MAY SHOW ONLY ONE SIDE OF CONNECTION OR MAY OMIT INFORMATION FOR CLARITY. 5.ESTABLISH AND VERIFY ALL OPENINGS AND INSERTS FOR ARCHITECTURAL, MECHANICAL, PLUMBING AND ELECTRICAL WITH APPROPRIATE TRADES, DRAWINGS AND SUBCONTRACTORS PRIOR TO CONSTRUCTION. CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFICATION OF ALL DIMENSIONS WITH ARCHITECTURAL DRAWINGS PRIOR TO START OF CONSTRUCTION. RESOLVE ANY DISCREPANCY WITH THE ARCHITECT AND STRUCTURAL ENGINEER. 6.ANY INSPECTIONS, SPECIAL (IBC CHAPTER 17) OR OTHERWISE THAT ARE REQUIRED BY THE BUILDING CODES, LOCAL BUILDING DEPARTMENTS, OR BY THESE PLANS SHALL BE DONE BY AN INDEPENDENT INSPECTION COMPANY OR THE BUILDING DEPARTMENT, SITE VISITS BY THE STRUCTURAL ENGINEER DO NOT CONSTITUTE AN OFFICIAL INSPECTION, UNLESS SPECIFICALLY CONTRACTED FOR. 1.BUILDING CODE: 2018 EDITION OF THE IBC WITH BINGHAM COUNTY AMENDMENTS. RISK CATEGORY = II 4. SEISMIC DESIGN PARAMETERS: ANALYSIS PROCEDURE EQUIVALENT LATERAL FORCE PROCEDURE IMPORTANCE FACTOR Ie = 1.00 SITE CLASS C SEISMIC DESIGN CATEGORY C MAPPED SPECTRAL RESPONSE ACCELERATIONS S1 = 0.142, SS = 0.366 DESIGN SPECTRAL RESPONSE ACCELERATIONS PERCENT SNOW INCLUDED WITH SEISMIC LOADS 20 VERTICAL SHEAR TRANSFER ELEMENTS: PLYWOOD SHEARWALL(S)R = 6.5, CS = 0.057 5. WIND DESIGN PARAMETERS (STRENGTH): ULTIMATE WIND SPEED 105 MPH (3 SECOND GUST) WIND EXPOSURE C IMPORTANCE FACTOR Iw = 1.00 INTERNAL PRESSURE COEFFICIENT -0.18 COMPONENT AND CLADDING PRESSURE 32.3 PSF NET UPLIFT ON ROOF 16.1 PSF 2. VERTICAL LOADS: ROOF ROOF = 35 PSF GROUND = 50 PSF 20 PSF FLOOR 40 PSF 35 PSF STAIRS / CORRIDORS 100 PSF 50 PSF 3. DEFLECTION LIMITS: ROOF TRUSSES/JOISTS L/360 L/240 FLOOR JOISTS L/600 L/240 BEAMS L/360 L/240 FOUNDATIONS DESIGNED IN CONFORMANCE WITH RECOMMENDATIONS BY: EAGLE ROCK ENGINEERING REPORT NO. 22109 DATED SEPTEMBER 23, 2022. 2.SITE PREPARATION AND GRADING REQUIREMENTS OF THE SOIL REPORT AND ANY ADDENDUM'S SHALL BE COMPLETED PRIOR TO CONSTRUCTION OF FOUNDATIONS. ANY TESTS OR INSPECTIONS REQUIRED BY THE SOIL REPORT SHALL BE PERFORMED PRIOR TO PLACEMENT OF FOUNDATION REINFORCING STEEL OR CONCRETE. ALTERATIONS TO SITE PREPARATION OR GRADING SHALL BE REPORTED TO THE GEOTECHNICAL ENGINEER PRIOR TO FOUNDATION CONSTRUCTION. 3.A ONE-THIRD INCREASE IN BEARING PRESSURES IS ALLOWED WITH SEISMIC OR WIND LOAD COMBINATIONS. LATERAL BEARING AND LATERAL SLIDING RESISTANCE MAY BE COMBINED. 4.ALL FOUNDATIONS SHALL BEAR ON EITHER UNDISTURBED WELL/POORLY GRADED GRAVEL WITH SAND (GW/GP) OR ON COMPACTED STRUCTURAL FILL. OVER EXCAVATION DEPTHS OF 1.5-7 FEET SHOULD BE EXPECTED DEPENDING ON OPTION CHOSEN AND LOCATION ON JOBSITE. STRUCTURAL FILL SHOULD BE AT LEAST 24" IN DEPTH COMPACTED TO 95% DRY DENSITY ACCORDING TO ASTM D698. THE WIDTH OF COMPACTED STRUCTURAL FILL BENEATH FOOTINGS SHOULD BE EQUAL TO TWICE THE WIDTH OF THE FOOTING. GRADE IS DEFINED AS LOWEST ADJACENT GRADE WITHIN 5 FEET OF THE BUILDING FOR PERIMETER FOOTINGS. WHERE EXTERIOR PAVING OR CONCRETE IS DIRECTLY ADJACENT TO BUILDING, GRADE IS DEFINED AS TOP OF EXTERIOR PAVING AT LEAST 5 FEET FROM BUILDING. CONCRETE FOOTING EXCAVATIONS SHALL BE CLEAN AND FREE OF LOOSE DEBRIS OR UN-COMPACTED MATERIAL AT TIME OF CONCRETE PLACEMENT. 5.CONCRETE SLABS ON GRADE SHALL BE SUPPORTED ON A 4 INCH (MIN) LAYER OF FREE-DRAINING GRANULAR MAT (DRAINAGE FILL COURSE). THE MAT SHOULD CONSIST OF A WELL GRADED SAND AND GRAVEL MIXTURE WITH MAXIMUM 3/4-INCH CRUSHED AGGREGATE. THE GRANULAR MAT SHOULD BE COMPACTED TO NO LESS THAN 95% OF THE MAXIMUM DRY DENSITY AS DETERMINED BY ASTM D698. THE SUBGRADE BELOW THE 4 INCH BASE SHOULD BE EITHER UNDISTURBED WELL/POORLY GRADED GRAVEL WITH SAND (GW/GP) OR A MINIMUM OF 12 INCHES OF STRUCTURAL FILL COMPACTED TO 95% DRY DENSITY ACCORDING TO ASTM D698. 6.BACKFILL AGAINST RESTRAINED WALLS SHALL NOT BE PLACED UNTIL AFTER THE WALLS ARE SUPPORTED BY THE COMPLETION OF INTERIOR FLOOR SYSTEMS AND CONCRETE OR GROUT STRENGTH HAS REACHED THE 28 DAY STRENGTH LISTED BELOW. THE SOIL DESIGN VALUES FOR THE FOUNDATION ARE: ALLOWABLE BEARING PRESSURE 3000 PSF FOUNDATION BEARING DEPTH 36" BELOW FINISHED GRADE 2.ALL NORMAL WEIGHT CONCRETE SHALL BE REGULAR WEIGHT OF 150 POUNDS PER CUBIC FOOT USING HARD ROCK AGGREGATES. AGGREGATE USED IN CONCRETE SHALL CONFORM TO ASTM C33. 3.LAP SPLICES FOR BEAMS AND FLOOR SLABS SLABS SHALL BE ACCORDING TO CHAPTER 12 OF ACI 318 OR LAP SCHEDULE ON THESE DRAWINGS. STAGGER SPLICES A MINIMUM OF ONE LAP LENGTH. NO TACK WELDING OF REINFORCING BARS ALLOWED WITHOUT PRIOR REVIEW OF PROCEDURE WITH THE STRUCTURAL ENGINEER. LATEST ACI CODE AND DETAILING MANUAL APPLY. PROVIDE BENT CORNER BARS TO MATCH AND LAP WITH HORIZONTAL BARS AT ALL CORNERS AND INTERSECTIONS PER TYPICAL DETAILS. VERTICAL WALL BARS SHALL BE SPLICED AT OR NEAR FLOOR LINES. 4.ALL DIMENSIONS SHOWING THE LOCATION OF REINFORCING STEEL NOT NOTED AS "CLEAR" OR "CLR" ARE TO CENTER OF STEEL. MINIMUM COVER FOR NON-PRESTRESSED CONCRETE REINFORCING SHALL BE AS FOLLOWS: 5.MAXIMUM SLUMP FOR ALL CONCRETE SHALL BE 6". PORTLAND CEMENT SHALL CONFORM TO ASTM C150. TYPE V CEMENT SHALL BE USED FOR CONCRETE IN CONTACT WITH ALKALINE SOIL, AND TYPE II ELSEWHERE. 6.NO MORE THAN 90 MINUTES SHALL ELAPSE BETWEEN CONCRETE BATCHING AND CONCRETE PLACEMENT UNLESS APPROVED BY THE TESTING AGENCY. 7.CONCRETE PLACEMENT AND QUALITY SHALL BE PER RECOMMENDATIONS IN ACI 614, ACI 301 AND ACI 318. MECHANICALLY VIBRATE ALL CONCRETE WHEN PLACED, EXCEPT THAT SLABS ON GRADE NEED BE VIBRATED ONLY AROUND AND UNDER FLOOR DUCTS, ETC. CAST CLOSURE POUR, WHERE SHOWN ON PLANS AROUND COLUMNS AFTER COLUMN DEAD LOAD IS APPLIED. REMOVE ALL DEBRIS FROM FORMS BEFORE PLACING CONCRETE. ALL ITEMS TO BE CAST IN CONCRETE SUCH AS REINFORCING, DOWELS, BOLTS, ANCHORS, PIPES, SLEEVES, ETC., SHALL BE SECURELY POSITIONED IN THE FORMS BEFORE PLACING THE CONCRETE. 8.ALL CONCRETE SLABS ON GRADE SHALL BE DIVIDED INTO AREAS BY CONTROL JOINTS (KEYED OR SAW CUT) SUCH THAT ONE SLAB AREA DOES NOT EXCEED A MAXIMUM LENGTH OF 24 TIMES THE SLAB THICKNESS IN BOTH DIRECTIONS (EXAMPLE: 4" SLAB = 8'-0" LENGTH). SQUARE LAYOUTS ARE PREFERRED, BUT THE SLAB GEOMETRY MAY DICTATE OTHERWISE. THE RATIO OF THE LONG TO SHORT DISTANCE SHALL NOT EXCEED 1.3. IT IS RECOMMENDED THAT SAW CUTS BE MADE WITHIN 16 HOURS OF CONCRETE BATCHING. KEYED CONTROL JOINTS NEED ONLY OCCUR AT EXPOSED EDGES DURING POURING, ALL OTHER JOINTS MAY BE SAW CUT. 9.HORIZONTAL PIPES AND ELECTRICAL CONDUITS SHALL NOT BE EMBEDDED IN STRUCTURAL CONCRETE AND SLABS ON GRADE EXCEPT WHERE SPECIFICALLY APPROVED OR NOTED BY THE STRUCTURAL ENGINEER. PIPES AND CONDUITS SHALL NOT IMPAIR THE STRENGTH OF THE WORK. 10.FLY ASH MAY BE USED ONLY IF PERMITTED BY ARCHITECTURAL SPECIFICATIONS AND SHALL BE LIMITED TO 18 PERCENT OF CEMENTITIOUS MATERIALS AND SHALL HAVE A REPLACEMENT FACTOR OF 1.2 RELATIVE TO CEMENT REPLACED. NO FLY ASH ADDITIVES SHALL BE USED IN FLATWORK OR ARCHITECTURALLY EXPOSED CONCRETE. 11.COLD/HOT WEATHER CONCRETE CONSTRUCTION: PROTECT CONCRETE FROM DAMAGE OR REDUCED STRENGTH IN COMPLIANCE WITH ACI 305 AND 306. 12.CONCRETE MIXES SHALL BE DESIGNED BY A CERTIFIED LABORATORY AND APPROVED BY THE STRUCTURAL ENGINEER. 13.LIMIT ALKALI-SILICA REACTION (ASR) TO 0.1% EXPANSION AT 28 DAYS IN CONCRETE MIX AT ALL EXTERIOR CONCRETE AND INTERIOR CONCRETE EXPOSED TO MOISTURE. CAST AGAINST EARTH (FOOTINGS)3"± 3/8" SLABS ON GRADE 1 1/2" EXPOSED TO EARTH OR WEATHER - #5 AND SMALLER EXPOSED TO EARTH OR WEATHER - #6 AND LARGER 2" NOT EXPOSED TO WEATHER OR IN CONTACT WITH THE GROUND ROOF SLAB 1" STRUCTURAL SLABS AND WALLS BEAMS AND COLUMNS (PRIMARY) REINFORCEMENT, TIES, STIRRUPS AND SPIRALS 1. MINIMUM 28 DAY CONCRETE STRENGTH SHALL BE AS FOLLOWS: FOOTINGS 3500 PSI 0.50 5.5% ± 1% FOUNDATION WALLS 4500 PSI 0.45 5.5% ± 1% INTERIOR CONCRETE SLABS ON GRADE 3500 PSI 0.45 N/A 1.GENERAL: DO NOT NOTCH OR DRILL JOISTS, BEAMS, OR LOAD BEARING STUDS WITHOUT PRIOR APPROVAL OF THE STRUCTURAL ENGINEER THROUGH THE ARCHITECT. DOUBLE UP JOISTS AND BLOCKING UNDER PARTITIONS. PROVIDE 2" (NOMINAL) SOLID BLOCKING AT SUPPORTS OF ALL JOISTS. UNLESS NOTED OTHERWISE ON PLANS/DETAILS PROVIDE 2x SOLID BLOCKING AT MID-HEIGHT OF BEARING STUD WALLS. ALL NAILING NOT NOTED SHALL BE ACCORDING TO IBC TABLE 2304.10.1. JOIST HANGERS AND OTHER MISC. FRAMING ANCHORS SHALL BE SIMPSON STRONG-TIE COMPANY, INC. OR OTHER MANUFACTURER WITH CURRENT ICC-ES APPROVAL. 2.SAWN LUMBER: FRAMING LUMBER SHALL COMPLY WITH THE LATEST EDITION OF THE GRADING RULES OF THE WESTERN WOOD PRODUCTS ASSOCIATION (WWPA) OR THE WEST COAST LUMBER INSPECTION BUREAU (WCLIB). ALL SAWN LUMBER SHALL BE STAMPED WITH THE GRADE MARK OF AN APPROVED LUMBER GRADING AGENCY. SAWN LUMBER SHALL HAVE THE FOLLOWING MINIMUM GRADE UNLESS NOTED OTHERWISE IN SCHEDULES: 2x4 STUDS DOUGLAS-FIR NO. 2, MINIMUM (U.N.O.) 2x6 STUDS DOUGLAS-FIR NO. 2, MINIMUM (U.N.O.) JOISTS, TOP PLATES AND ALL OTHER SAWN LUMBER DOUGLAS-FIR NO. 2, MINIMUM (U.N.O.) BEAMS AND POSTS DOUGLAS-FIR NO. 2, MINIMUM (U.N.O.) LOCATION:NOMINAL THICKNESS: SPAN INDEX RATING: EDGE ATTACHMENT: FIELD ATTACHMENT: WALL 8d AT 6" O.C.8d AT 12" O.C. ROOF 8d AT 6" O.C. 8d AT 12" O.C. ROOF 8d AT 6" O.C. 8d AT 12" O.C. ROOF 10d AT 6" O.C. 10d AT 12" O.C. ROOF 10d AT 6" O.C. 10d AT 12" O.C. ROOF 10d AT 6" O.C. 10d AT 12" O.C. FLOOR 10d AT 6" O.C. OR #8 SCREWS AT 6" O.C. 10d AT 6" O.C. OR #8 SCREWS AT 12" O.C. FLOOR 10d AT 6" O.C. OR #8 SCREWS AT 6" O.C. 10d AT 6" O.C. OR #8 SCREWS AT 12" O.C. FLOOR 10d AT 6" O.C. OR #8 SCREWS AT 6" O.C. 10d AT 6" O.C. OR #8 SCREWS AT 12" O.C. 3.PLYWOOD: ALL PLYWOOD SHALL BE C-D OR C-C SHEATHING CONFORMING TO STANDARD PS 1-95. LAY UP PLYWOOD WITH FACE GRAIN IN PERPENDICULAR TO SUPPORTS (ON ROOFS WHERE PLYWOOD IS LAID UP WITH FACE GRAIN PARALLEL TO SUPPORTS, USE A MINIMUM OF 5-PLY PLYWOOD, STAGGER JOINTS). ALL NAILING, COMMON NAILS. BLOCKING AT PANEL EDGES WHERE INDICATED ON PLANS. ALL PLYWOOD SHALL BE OF THE FOLLOWING NOMINAL THICKNESS, SPAN/INDEX RATING AND SHALL BE NAILED AS FOLLOWS UNLESS NOTED OTHERWISE ON THE PLANS: SCREWS AT FLOOR SHEATHING SHALL BE #8 SCREWS AND SHALL PENETRATE AT LEAST 1 1/2" INTO THE SUPPORTING MEMBER. ALL FLOOR SHEATHING SHALL BE GLUED TO SUPPORTING MEMBERS WITH AN APA AFG-01 QUALIFIED ADHESIVE. PLYWOOD ALTERNATE: AMERICAN PLYWOOD ASSOCIATION PERFORMANCE RATED SHEATHING MAY BE USED AS AN ALTERNATE TO PLYWOOD WITH PRIOR APPROVAL OF OWNER, ARCHITECT AND ROOFER. IT MAY NOT BEUSED ON ROOFS WHERE BUILT UP ROOF SYSTEM IS TO BE GUARANTEED BY ROOFER. RATED SHEATHING SHALL COMPLY WITH CURRENT ICC-ES REPORTS AND SHALL HAVE A SPAN RATING EQUIVALENT TO OR BETTER THAN THE PLYWOOD IT REPLACES. ATTACHMENT AND THICKNESS (WITHIN 1/32") SHALL BE THE SAME AS THE PLYWOOD IT REPLACES. INSTALL PER MANUFACTURER'S RECOMMENDATIONS. 4.NOMINAL 2x AND 3x DECKING. TONGUE AND GROOVE TYPE. MINIMUM Fb = 1,600 PSI, MINIMUM E = 1,300,000 PSI. INSTALL WITH TONGUES UP SLOPE ON PITCHED ROOFS, AND OUTWARD IN THE DIRECTION OF LAYING ON FLAT ROOFS. NAIL EACH PLANK WITH 16d TOENAIL (THRU THE TONGUE) AND 16d FACE NAIL AT EACH SUPPORT. DECK SHALL BE INSTALLED AS SIMPLE SPAN WITH ALL PLANKS BEARING ON TWO SUPPORTS. FOR REFERENCE AND/OR ADDITIONAL INFORMATION SEE AITC 117-2010. 5.GLUED-LAMINATED BEAMS (GLB): GLUED-LAMINATED BEAMS SHALL BE DOUGLAS FIR COMBINATION AT 24F-V4 AT SIMPLE SPAN BEAMS AND 24F-V8 AT MULTI-SPAN AND CANTILEVERED BEAMS WITH THE FOLLOWING MINIMUM PROPERTIES: FB = 2,400 PSI, FV = 190 PSI, FC (PERPENDICULAR) = 650 PSI, E =1,800 KSI. ALL BEAMS SHALL BE FABRICATED USING WATERPROOF GLUE. FABRICATION AND HANDLING PER LATEST AITC AND WCLA STANDARDS. BEAMS TO BEAR GRADE STAMP AND AITC STAMP AND CERTIFICATE. CAMBER AS SHOWN ON DRAWINGS. STANDARD CAMBER IS BASED ON A RADIUS OF CURVATURE OF 2000 FEET. 6.GLUED-LAMINATED COLUMNS: GLUED-LAMINATED COLUMNS SHALL BE DOUGLAS FIR COMBINATION 3 WITH THE FOLLOWING MINIMUM PROPERTIES: FBY = 2,100 PSI, FBX = 2000 PSI, FVY = 230 PSI, FVX = 265 PSI, FC (PERPENDICULAR) = 650 PSI, E =1,900 KSI. ALL COLUMNS SHALL BE FABRICATED USING WATERPROOF GLUE. FABRICATION AND HANDLING PER LATEST AITC AND WCLA STANDARDS. COLUMNS TO BEAR GRADE STAMP AND AITC STAMP AND CERTIFICATE. 7.LAMINATED VENEER LUMBER (LVL): DESIGN, FABRICATION AND ERECTION IN ACCORDANCE WITH THE LATEST ICC-ES REPORT. MINIMUM PROPERTIES FOR LVLs SHALL BE: FB = 2,600 PSI, FV = 285 PSI, E = 2,000 KSI. 8.PARALLEL STRAND LUMBER (PSL): DESIGN, FABRICATION AND ERECTION IN ACCORDANCE WITH THE LATEST ICC-ES REPORT. MINIMUM PROPERTIES FOR PSLs SHALL BE: FB = 2,900 PSI, FV = 290 PSI, E = 2,000 KSI. 9.LAMINATED STRAND LUMBER (LSL): DESIGN, FABRICATION AND ERECTION IN ACCORDANCE WITH THE LATEST ICC-ES REPORT. MINIMUM PROPERTIES FOR LSLs SHALL BE: FB = 2,325 PSI, FV = 310 PSI, E = 1,550 KSI. 10.SILL PLATES RESTING ON CONCRETE OR MASONRY SHALL BE OF TREATED FIR. SHEAR WALLS AND EXTERIOR WALL SILLS AT CONCRETE SLAB SHALL HAVE A MINIMUM OF (2) ANCHOR BOLTS PER PIECE. PROVIDE ANCHOR BOLT AT 9" MAXIMUM, 4" MINIMUM FROM THE END OF EACH PIECE AT SPLICE OR END OF WALL. MAXIMUM ANCHOR BOLT SPACING SHALL BE 72" ON CENTER UNLESS NOTED OTHERWISE ON PLANS OR DETAILS. ALL ANCHOR BOLTS (OTHER THAN BOLTS FOR HOLDOWNS) SHALL EMBED 7" INTO CONCRETE. ANCHOR BOLTS FOR HOLDOWNS SHALL NOT BE CONSIDERED AS PART OF REQUIRED ANCHOR BOLTS ON SHEAR WALLS. ALL EXTERIOR WALLS SHALL BE SECURED WITH MINIMUM ANCHOR BOLTS. INTERIOR WALLS MAY BE SECURED TO CONCRETE WITH EITHER ANCHOR BOLTS OR POWER DRIVEN SHOT PINS UNLESS NOTED OTHERWISE ON PLANS. 11.BOLTING: ALL BOLTS IN WOOD CONNECTIONS SHALL CONFORM TO ASTM A307. BOLTS SHALL BE INSTALLED IN HOLES BORED WITH A BIT 1/16" LARGER THAN THE Ø (DIAMETER) OF THE BOLT. BOLTS AND NUTS SEATING ON WOOD SHALL HAVE CUT STEEL WASHERS UNDER HEADS AND NUTS. NICK THREADS TO PREVENT LOOSENING. 12. PREFABRICATED WOOD ROOF TRUSSES BALCONY 60 PSF 15 PSF SD1 = 0.220, SDS = 0.368 GENERAL STRUCTURAL NOTES (APPLY UNLESS NOTED OTHERWISE ON PLANS/DETAILS) ± 1/4" 1 1/2"± 3/8" ± 3/8" 1/8" 3/4"1/8" 1 1/2"3/8" PREFABRICATED WOOD TRUSSES: PREFABRICATED WOOD TRUSSES SHALL BE DESIGNED TO SUPPORT SELF WEIGHT PLUS LIVE LOAD AND SUPERIMPOSED DEAD LOADS. WHERE UNINHABITABLE ATTIC SPACE CAN BE USED FOR STORAGE, A 20 PSF LIVE LOAD ON THE BOTTOM CHORD SHALL BE INCLUDED IN THE ANALYSIS. BRIDGING SIZE AND SPACING BY TRUSS MANUFACTURER UNLESS NOTED OTHERWISE. CONTRACTOR SHALL SUBMIT SHOP DRAWINGS WITH DESIGN CALCULATIONS SEALED BY A REGISTERED ENGINEER FOR REVIEW PRIOR TO MANUFACTURE FOR BOTH ROOF AND FLOOR TRUSSES WHEN USED. SHOP DRAWINGS SHALL SHOW ANY SPECIAL DETAILS REQUIRED AT BEARING POINTS. ALL CONNECTORS SHALL HAVE CURRENT ICC-ES APPROVAL. ADDITIONAL TRUSSES SHALL BE SUPPLIED AS REQUIRED TO SUPPORT MECHANICAL EQUIPMENT. PER IBC SECTION 2303.4 AND TPI-1: EACH TRUSS SHALL BE LEGIBLY BRANDED, MARKED OR OTHERWISE HAVE PERMANENTLY AFFIXED THERETO THE IDENTITY OF THE COMPANY MANUFACTURING THE TRUSS, THE DESIGN LOADS, AND THE TRUSS SPACING - WITHIN TWO FEET OF THE CENTER OF THE SPAN ON THE FACE OF THE BOTTOM CHORD. PREFABRICATED WOOD/STEEL WEB JOIST/PURLINS (TJI/TJL SERIES OR EQUAL): DESIGN, FABRICATION AND ERECTION IN ACCORDANCE WITH THE LATEST EDITION ICC-ES REPORT. CONNECTIONS AND BEARING MATERIAL TO BE DESIGNED AND FURNISHED BY JOIST FABRICATOR. CONTRACTOR SHALL SUBMIT SHOP DRAWINGS WITH DESIGN CALCULATIONS SEALED BY A REGISTERED STRUCTURAL ENGINEER FOR REVIEW PRIOR TO MANUFACTURE. ADDITIONAL JOISTS SHALL BE SUPPLIED AS REQUIRED TO SUPPORT MECHANICAL EQUIPMENT. 7/16" OR 1/2" 7/16" OR 1/2" 15/32" OR 1/2" 19/32" OR 5/8" 23/32" OR 3/4" 7/8" 3/4" T&G 7/8" T&G 1 1/8" T&G 24/16 24/16 32/16 40/20 48/24 60/32 48/24 60/32 60/48 1. REINFORCING STEEL: 1.ASTM A615 GRADE 60 (FY = 60 KSI) DEFORMED BARS FOR ALL BARS #4 AND LARGER. ASTM A615 GRADE 40 (FY = 40 KSI) DEFORMED BARS FOR ALL BARS #3 AND SMALLER. GRADE 60 DEFORMED BARS SHALL BE USED FOR CONCRETE WALLS, BEAMS, AND ELEVATED SLAB REINFORCING. 2. WELDING OF REINFORCING BARS SHALL BE MADE ONLY TO ASTM A706 GRADE 60 BARS AND ONLY USING E90 SERIES RODS. WELDING OF REINFORCING BARS SHALL BE MADE ONLY AT LOCATIONS SHOWN ON PLANS OR DETAILS. 3. REINFORCING BAR SPACING GIVEN ARE MAXIMUM ON CENTERS. ALL BARS PER CRSI SPECIFICATIONS AND HANDBOOK. DOWEL ALL VERTICAL REINFORCING TO FOUNDATION. SECURELY TIE ALL BARS IN LOCATION BEFORE PLACING CONCRETE. STEEL: 1.MATERIALS: ROLLED W SHAPES, SHALL CONFORM TO ASTM A992 (FY=50 KSI). ALL OTHER STRUCTURAL STEEL SHAPES, ROLLED SECTIONS, BARS AND PLATES SHALL CONFORM TO ASTM A36 (FY = 36 KSI). ALL PIPE STEEL SHALL BE ASTM A501 (FY = 36 KSI) OR ASTM A53, TYPE E OR S, GRADE B (FY = 35 KSI). ALL TUBULAR STEEL SHALL BE ASTM A500 (FY = 46 KSI). 2.ALL BOLTS AND STUDS SHALL BE ASTM A307, UNLESS NOTED OTHERWISE. ALL EXPANSION BOLTS TO HAVE CURRENT ICC REPORT RATING FOR MATERIAL INTO WHICH INSTALLATION TAKES PLACE. HEADED STUDS SHALL CONFORM TO ALL REQUIREMENTS OF THE LATEST EDITION OF THE "RECOMMENDED PRACTICES FOR STUD WELDING" AND THE "STRUCTURAL WELDING CODE" PUBLISHED BY AWS. ALL BOLTS, ANCHOR BOLTS, EXPANSION BOLTS, ETC. SHALL BE INSTALLED WITH STEEL WASHERS AT FACE OF WOOD OR AT SLOTTED HOLES IN STEEL SECTIONS. 3.ALL STRUCTURAL AND MISCELLANEOUS STEEL SHALL BE FABRICATED AND ERECTED IN ACCORDANCE WITH AISC SPECIFICATIONS FOR THE DESIGN, FABRICATION AND ERECTION OF STRUCTURAL STEEL FOR BUILDINGS, LATEST EDITION. 4.WELDING SHALL BE BY WELDERS HOLDING VALID CERTIFICATES AND HAVING CURRENT EXPERIENCE IN THE TYPE OF WELD SHOWN ON THE DRAWINGS OR NOTES. ALL WELDING SHALL USE E70 SERIES LOW HYDROGEN RODS UNLESS NOTED OTHERWISE. ALL WELDING PER LATEST AMERICAN WELDING SOCIETY STANDARDS. ALL WELDS ON DRAWINGS ARE SHOWN AS SHOP WELDS. CONTRACTOR MAY SHOP WELD OR FIELD WELD AT HIS DISCRETION. ALL FULL PENETRATION WELDS SHALL BE TESTED AND CERTIFIED BY AN INDEPENDENT TESTING LABORATORY. 5.STEEL TO STEEL BOLTED CONNECTIONS: HIGH STRENGTH BOLTS SHALL BE ASTM A325N AND SHALL BE INSTALLED AS BEARING-TYPE CONNECTIONS WITH THREADS INCLUDED IN SHEAR PLANE (TYPE "N" CONNECTION UNLESS NOTED OTHERWISE). BOLTS MAY BE TIGHTENED USING ANY AISC APPROVED METHOD. 6. DRYPACK SHALL BE 5,000 PSI FIVE STAR NON-SHRINK GROUT OR EQUIVALENT. INSTALL DRYPACK UNDER BEARING PLATES BEFORE FRAMING MEMBER IS INSTALLED. AT COLUMNS, INSTALL DRYPACK UNDER BASE PLATES AFTER COLUMN HAS BEEN PLUMBED BUT PRIOR TO FLOOR OR ROOF INSTALLATION. 7.SHOP DRAWINGS SHALL BE SUBMITTED FOR ALL STRUCTURAL ITEMS IN ADDITION TO ITEMS REQUIRED BY ARCHITECTURAL SPECIFICATIONS, THE CONTRACTOR SHALL REVIEW ALL SHOP DRAWINGS PRIOR TO SUBMITTAL. ITEMS NOT IN ACCORDANCE WITH CONTRACT DRAWINGS SHALL BE FLAGGED UPON HIS REVIEW. VERIFY ALL DIMENSIONS WITH ARCHITECT. ANY CHANGES, SUBSTITUTIONS, OR DEVIATIONS FROM ORIGINAL CONTRACT DRAWINGS SHALL BE CLOUDED. ANY OF THE AFOREMENTIONED WHICH ARE NOT CLOUDED OR FLAGGED BY SUBMITTING PARTIES, SHALL NOT BE CONSIDERED APPROVED AFTER THE STRUCTURAL ENGINEER'S REVIEW, UNLESS NOTED ACCORDINGLY. ANY ENGINEERING PROVIDED BY OTHERS AND SUBMITTED FOR REVIEW, SHALL BEAR THE SEAL OF A STRUCTURAL ENGINEER REGISTERED IN THE APPROPRIATE STATE. THE SHOP DRAWINGS DO NOT REPLACE THE ORIGINAL CONTRACT DRAWINGS. ITEMS OMITTED OR SHOWN INCORRECTLY AND ARE NOT FLAGGED BY THE STRUCTURAL ENGINEER ARE NOT TO BE CONSIDERED CHANGES TO ORIGINAL DRAWINGS. THE ADEQUACY OF ENGINEERING DESIGNS AND LAYOUT PERFORMED BY THE OTHERS RESTS WITH THE DESIGNING OR SUBMITTING AUTHORITY. REVIEWING IS INTENDED ONLY AS AN AID TO THE CONTRACTOR IN OBTAINING CORRECT SHOP DRAWINGS. RESPONSIBILITY FOR CORRECTNESS SHALL REST WITH THE CONTRACTOR. ALLOW (5) WORKING DAYS FOR THE STRUCTURAL ENGINEER'S REVIEW. ONE COPY OF EACH SUBMITTAL WILL BE RETAINED FOR THE STRUCTURAL ENGINEER'S RECORDS. STEEL DECKING: 1.PROTECT STEEL DECK FROM CORROSION, DEFORMATION, AND OTHER DAMAGE DURING DELIVERY, STORAGE AND HANDLING. IF GROUND STORAGE IS NEEDED, THE DECK BUNDLES MUST BE STORED OFF THE GROUND, WITH ONE END ELEVATED TO PROVIDE DRAINAGE. BUNDLES MUST BE PROTECTED AGAINST CONDENSATION WITH A VENTILATED WATERPROOF COVERING. BUNDLES MUST BE STACKED SO THERE IS NO DANGER OF TIPPING, SLIDING, ROLLING, SHIFTING OR MATERIAL DAMAGE. BUNDLES MUST BE PERIODICALLY CHECKED FOR TIGHTNESS, AND RETIGHTENED AS NECESSARY. DECK BUNDLES PLACED ON THE BUILDING FRAME MUST BE PLACED NEAR A MAIN SUPPORTING BEAM AT A COLUMN OR WALL. IN NO CASE ARE THE BUNDLES TO BE PLACED ON UNBOLTED FRAMES OR ON UNATTACHED AND/OR UNBRIDGED JOISTS. THE STRUCTURAL FRAME MUST BE PROPERLY BRACED TO RECEIVE THE BUNDLES. 2.EXAMINE SUPPORT FRAMING AND FIELD CONDITIONS FOR COMPLIANCE WITH REQUIREMENTS FOR INSTALLATION TOLERANCES AND OTHER CONDITIONS AFFECTING PERFORMANCE OF WORK OF THIS SECTION. ALL OSHA RULES FOR ERECTION MUST BE FOLLOWED. PLACE DECK IN ACCORDANCE WITH APPROVED INSTALLATION DRAWINGS. LOCATE DECK BUNDLES TO PREVENT OVERLOADING OF SUPPORT MEMBERS. INSTALL DECK PANELS AND ACCESSORIES ACCORDING TO ANSI/SDI RD - 2010 AND IN ACCORDANCE WITH APPROVED INSTALLATION DRAWINGS AND REQUIREMENTS OF THIS SECTION. PLACE DECK PANELS ON STRUCTURAL SUPPORTS AND ADJUST TO FINAL POSITION WITH ENDS ALIGNED. ATTACH FIRMLY TO THE SUPPORTS INNEDIATELY AFTER PLACEMENT IN ORDER TO FORM A SAFE WORKING PLATFORM. CUT AND NEATLY FIT DECK UNITS AND ACCESSORIES AROUND OPENINGS AND OTHER WORK PROJECTING THROUGH OR ADJACENT TO THE DECKING. TRADES THAT SUBSEQUENTLY CUT UNSCHEDULED OPENINGS THROUGH THE DECK ARE RESPONSIBLE FOR REINFORCING THE OPENINGS. BEFORE PLACEMENT OF ROOF INSULATION AND ROOF COVERING, THE DECK SHALL BE INSPECTED FOR TEARS, DENTS OR OTHER DAMAGE THAT MAY PREVENT THE DECK FROM ACTING AS A STRUCTURAL ROOF BASE. THE NEED FOR REPAIR OF DAMAGED DECK SHALL BE DETERMINED BY THE ENGINEER OF RECORD BASED ON STRUCTURAL PERFORMANCE, UNLESS AESTHETICS HAVE BEEN SPECIFICALLY ADDRESSED IN THE CONTRACT DOCUMENTS. DO NOT USE DECK UNITS AS A WORKING PLATFORM OR STORAGE AREA UNTIL UNITS ARE IN POSITION AND PERMANENTLY ATTACHED TO THE STRUCTURE. CONSTRUCTION LOADS MUST NOT EXCEED LOAD CARRYING CAPACITY OF THE DECK. EXTERIOR CONCRETE SLABS ON GRADE 4500 PSI 0.45 5.5% ± 1% 03 / 0 1 / 2 0 2 3 D 2 2 3/9/23 RESPONSE TO CITY N eed additional struc tural pages.