HomeMy WebLinkAboutAPPROVED FIRE ALARM SUBMITTAL - 23-00751 - BYUI University Operation Building - Fire AlarmAuthor Name Author Email Author Phone No.: Alex Owens Alex.Owens@rexburg.org 208-372-2172 Description : BYUI University Operation Building - Fire Alarm Address : 426 S 2nd E Record Type : Fire System Construction Permit Document Filename : BYU I University Operations Fire Alarm Upgrade Submittal.pdf Comment Author Contact Information: Corrections in the following table need to be applied before a permit can be issued Review Report Approved # 23-00751 Page Reference Annotation Type Author : Department Status Page Review Comments Applicant Response Comments 1 Stamp Alex Owens : Electrical Open 1 Approved - Electrical Inspector 1 Free Text Alex Owens : Electrical Open 1 All electrical work must comply with 2017 NEC and meet NFPA 72 standards. Fire System Construction Permit Approval of plans does not constitute approval of variance from code FIRE CONTROL INSTRUMENTS-GAMEWELL-BOSCH 1481 SOUTH MAJOR STREET S.L.C., UT 84115 P. 801-468-8300 F. 801-468-8305 University Operations Fire Alarm Upgrade – Brigham Young University Idaho Rexburg, ID. 83460 University Operations Fire Alarm Upgrade Brigham Young University - Idaho Fire Alarm System Submittal & Drawings All electrical work must comply with 2017 NEC and meet NFPA 72 standards. PROJECT Equipment Manufacturer: Gamewell-FCI University Operations Fire Alarm Upgrade Authorized Distributor: Nelson Fire Systems Brigham Young University - Idaho 1481 S Major St Fire Alarm System SLC, UT 84115 801-468-8300... University Operations Fire Alarm Upgrade – Brigham Young University Idaho Rexburg, ID. 83460 TABLE OF CONTENTS Data Sheet Part No. Description FACU: (Existing) Gamewell-FCI E3 Series Emergency Evacuation System VOICE PANEL: (Existing) Gamewell-FCI INI-VGE E3 Series Voice Command Center DEVICES: Gamewell-FCI ASD-PL3/B300-6 Addressable Photo Smoke Detector w/Base Gamewell-FCI ATD-L3R/B300-6 Addressable Heat Detector w/Base Gamewell-FCI MS-7AF Addressable Pull Station Gamewell-FCI SPSWL White Speaker/Strobe – Wall Mount Gamewell-FCI SPSCWL White Speaker/Strobe – Ceiling Mount Gamewell-FCI SPCWL White Speaker Only – Ceiling Mount Battery Calculations E3 System Battery Calc HPFF8 Battery Calc CKT Voltage Drops Drawings Sheet No. Description Cover Page FA-C-01 Fire Alarm Cover Riser Diagram FA-R-01 Fire Alarm Riser and Matrix Lower FA-L-01 Addressable Circuits Lower FA-L-02 Notification Circuits Ground FA-G-01 Addressable Circuits Ground FA-G-02 Notification Circuits Devices ASD-PL2F/ASD-PTL2F ASD-PL2FR Velociti® Series 3 Detectors Photoelectric Detectors Addressable Devices Photoelectric Detector Description The Gamewell-FCI, Velociti® Series 3 intelligent photoelectric detectors with integral communication provide point location for alarm communication and selective maintenance. Designed in a modern bright white color, the Velociti Series 3 is aesthetically pleasing for today's contemporary buildings. The Velociti Series 3 smoke detectors are intelligent addressable detectors with point ID capability that enable each detector address to be set with rotary address switches providing exact device locations. The photoelectric detector continually monitors the detected temperature and reports it to the fire alarm control panel. The modern design and expanded color options support a variety of contemporary aesthetic demands. In addition, each detector is constructed for exceptional installation and maintenance efficiency. The Gamewell-FCI, ASD-PL3 photoelectric detector's re-designed optical sensing chamber is engineered to sense smoke produced by a wide range of combustion sources in accordance with more stringent code standards. The sensitivity of Velociti series detectors can be programmed using the control panel software to suit the environment. The ASD-PL3R photoelectric detector is also remote test capable that may be used with a DNR (DNRW) duct smoke detector housing. The ASD-PTL3 multi- sensor detector offers either photoelectric detection or thermal detection through dual electronic thermistors at 135°F fixed temperature thermal sensing. For legacy installations, service detectors are available in the classic ivory color that will operate in both Velociti and CLIP protocol for backwards compatibility. Service models are designated by the -IV part number after the detector model. Note: Although the E3 Series® and S3 Series panels support both the Velociti® and CLIP™ protocols, the GWF-7075 panel does not support the CLIP protocol. To obtain a complete list of panels that are listed to Velociti Series 3 detectors, refer to the Compatibility Addendum for Gamewell-FCI Manuals, P/N:9000-0427-L8. FEATURES & BENEFITS • Complies with UL® Standard 268 7th Edition • Designed with a new profile to offer modern and improved aesthetics • Contains a built-in functional test switch activated by external magnet • Supports a low standby current • Provides rotary address switches (01-159) • Supplies optional relay, isolator, or sounder bases (standard or low frequency) • Includes dual LEDs for 360° visibility • Offers expanded color options 2 Ordering Information NOTE: "-IV" suffix indicates Ivory color model. NOTE: "-BL" suffix indicates Black color model. NOTE: “WH” suffix indicates Bright White color model. ASD-PL3: Photoelectric smoke detector, bright white, Velociti ASD-PL3R: Photoelectric smoke detector, remote test capable, for use with DNR(W) duct smoke detectors, bright white, Velociti ASD-PTL3: Photoelectric smoke detector with thermal sensing, bright white, Velociti ASD-PL3-IV : Photoelectric smoke detector, ivory, Velociti/ CLIP ASD-PL3R-IV: Photoelectric smoke detector, remote test capable, for use with DNR(W) duct smoke detectors, ivory, Velociti/CLIP ASD-PTL3-IV : Photoelectric smoke detector with thermal sensing, ivory, Velociti/CLIP Intelligent Bases For details on intelligent bases, refer to Data Sheet P/N: 9021-60540. Note: “IV” suffix indicates Flashscan and CLIP devices. “WH” suffix indicates bright white B501-WHITE: 4” Flangeless mounting base, bright white B501-WHITE-BP: 4” Flangeless mounting base bulk pack, bright white B501-IV: 4” Flangeless mounting base, ivory B300-6: 6” Flanged mounting base, bright white B300-6-IV: 6” Flanged mounting base, ivory B300-6-BP: 6” Flanged mounting base bulk (Pack of 10) B200SR-WH: Standard sounder base, bright white B200SR-IV: Standard sounder base, ivory B200S-WH: Intelligent addressable sounder base, bright white B200S-IV: Intelligent addressable sounder base, ivory B200SR-LF-WH: Standard low frequency sounder base, bright white B200SR-LF-IV: Standard low frequency sounder base, ivory B200S-LF-WH: Intelligent addressable low frequency sounder base, bright white B200S-LF-IV: Intelligent addressable low frequency sounder base, ivory B224RB-WH: Relay base, bright white B224RB-IV: Relay base, ivory B224BI-WH: Isolator base, bright white B224BI-IV: Isolator base, ivory DNR: Intelligent duct detector housing, non-relay DNRW: Intelligent duct detector housing, non-relay, watertight Ordering Information Accessories SMB600: Surface Mounting Kit (flanged) TR300: Accessory Flange Ring for B300 6” Base, bright white TR300-IV: Accessory Flange Ring for B300 6” Base, ivory RA100Z: Remote LED annunciator, 3-32 VDC The annunciator mounts to a U.S. single-gang electrical box. For use with B501 and B300-6. CK300: Bright White detector kit (Pack of 10) CK300-IR: White, detector color kit for use with MCS-COF Series Detectors. (Pack of 10) CK300-IV: Ivory, detector color kit. (Pack of 10) CK300-IR-IV: Ivory, detector color kit for use with MCSCOF Series detectors. (Pack of 10) CK300-BL: Black detector kit. (Pack of 10) CK300-IR-Bl: Black, detector color kit for use with MCSCOF Series detectors. (Pack of 10) M02-04-01: Detector test magnet. M02-09-00: Test magnet with telescoping handle. XR2B: Detector removal tool. Allows the installation and/ or removal of the detector heads from the bases in high ceiling applications. XP-4: Extension pole for XR2B. Shipped with three, 5-foot (1.524,m) sections. Velociti® Series 3 Detectors Technical Specifications 9020-0617 | K | 04/2018 ©2018 Honeywell International Inc. For a complete listing of all compliance approvals and certifications, please visit: http://www.gamewell- fci.com/en-US/ documentation/Pages/ Listings.aspx E3 Series®, Velociti® and Gamewell-FCI® are registered trademarks of Honeywell International Inc. UL® is a registered trademark of Underwriter’s Laboratories Inc. This document is not intended to be used for installation purposes. We try to keep our product information up-to- date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice. Honeywell Gamewell-FCI 12 Clintonville Road Northford, CT 06472-1610 203.484.7161 www.honeywell.com For more information Learn more about Gamewell-FCI’s Velociti® Series 3 Detectors and other products available by visiting www.Gamewell-FCI.com SYSTEMS Photoelectric Intelligent Detector: Physical Specifications Height: 2.0 inches (51 mm) installed in B300-6 base Diameter: 6.1 inches (15.49 cm) installed in B300-6 base 4 inches (10.16 cm) installed in B501 base Shipping Weight: 3.4 oz (96.4 g) Operating Temperature Range: Photo: 32° F to 122° F (0° C to 50° C) Photo in Duct Applications: -4° F to 158° F (-20° C to 70° C) Photo with Thermal: 32° F to 100° F (0° C to 38° C) Operating Humidity Range: 10% to 93% non-condensing Rate-of-Rise Detection: Responds to greater than 15°F/minute or 135°F (8.3° C/minute or 57°C Air Velocity Range: 0 to 4,000 ft/min (0 to 1219.2 m/min) Electrical Specifications Voltage Range: 15 to 32 VDC Standby Current (@ 24 VDC): 200 UA (one communication every 5 seconds with green LED enabled) Max Alarm Current (max.): 2 mA @ 24 VDC (one communication every 5 seconds with red LED enabled) Max Current (max.): 4.5 mA @ 24 VDC (one communication every 5 seconds with amber LED enabled) Isolator Load Rating: 0.0063 STANDARDS The Velociti® Series 3 Photoelectric Detectors are designed to comply with the following standard: UL Standard: UL 268 AGENCY LISTINGS AND APPROVALS These listings and approvals apply to the modules specified in this document. In some cases, certain modules or applications may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status. UL: S2332 FM: 3023594 MEA FDNY: COA-219-02-E Vol. VI CSFM: 7272-1703:0501 ISO 9001 Certification Thermal Detector Velociti® Series 3 Detectors Thermal Detectors Addressable Devices Description The Gamewell-FCI, Velociti® Series 3 intelligent thermal detectors with integral communication provide point location for alarm communication and selective maintenance. Designed in a modern bright white color, the Velociti Series 3 is aesthetically pleasing for today's contemporary buildings. The Velociti Series 3 heat detectors are intelligent addressable detectors with point ID capability that enable each detector address to be set with rotary address switches providing exact device locations. The thermal detector continually monitors the detected temperature and reports it to the fire alarm control panel. The modern design and expanded color options support a variety of contemporary aesthetic demands. In addition, each detector is constructed for exceptional installation and maintenance efficiency. Velociti Series 3 thermal detectors provide cost-effective, intelligent property protection using the following single thermistor: • ATD-L3 offers 135°F fixed thermal detection. • ATD-L3R offers 135°F fixed and rate-of-rise thermal detection. • ATD-L3H provides fixed high-temperature detection at 190°F . For legacy installations, service detectors are available in the classic ivory color that will operate in both Velociti and CLIP protocol for backwards compatibility. Service models are designated by the -IV part number that appears after the detector model. Note: The E3 Series® and S3 Series panels support both the Velociti® and CLIP™ protocols, and the GWF-7075 panel supports only the Velociti® protocol. To obtain a complete list of panels that are listed to Velociti Series 3 detectors, refer to the Compatibility Addendum for Gamewell-FCI Manuals, P/N:9000-0427-L8. FEATURES & BENEFITS • Complies with UL® 268 7th Edition • Designed with a new profile to offer modern and improved aesthetics • Contains a built-in functional test switch activated by an external magnet • Supports a low standby current • Provides rotary address switches (01-159) • Supplies optional relay, isolator, or sounder bases (standard or low frequency) •Includes dual LEDs used for 360° visibility • Offers expanded color options 2 Ordering Information NOTE: "-IV" suffix indicates Ivory color model. NOTE: "-BL" suffix indicates Black color model. NOTE: “WH” suffix indicates Bright White color model. ATD-L3: Thermal heat detector, 135°F fixed, bright white, Velociti ATD-L3-IV: Thermal heat detector, 135°F fixed, ivory, Velociti/CLIP ATD-L3R: Thermal heat detector, 135°F rate of rise, bright white, Velociti ATD-L3R-IV: Thermal heat detector, 135°F rate of rise, ivory, Velociti/CLIP ATD-L3H: Thermal heat detector, 190°F high temp, bright white, Velociti ATD-L3H-IV: Thermal heat detector, 190°F high temp, ivory, Velociti/CLIP Intelligent Bases For details on intelligent bases, refer to Data Sheet P/N: 9021-60540. B501-White: 4" Flangeless mounting base, bright white B501-White-BP: 4" Flangeless mounting base bulk pack, bright white B501-IV: 4" Flangeless mounting base, ivory B501-BL 4" Flangeless mounting base, B300-6: 6" Flanged mounting base, bright white B300-6-IV: 6" Flanged mounting base, ivory B300-6-BP: 6" Flanged mounting base bulk pack B200SR-WH: Standard sounder base, bright white B200SR-IV: Standard sounder base, ivory B200S-WH: Intelligent addressable sounder base, bright white B200S-IV: Intelligent addressable sounder base, ivory B200SR-LF-WH: Standard low frequency sounder base, bright white B200SR-LF-IV: Standard low frequency sounder base, ivory B200S-LF-WH: Intelligent addressable low frequency sounder base, bright white B200S-LF-IV: Intelligent addressable low frequency sounder base, ivory B224RB-WH: Relay base, bright white B224RB-IV: Relay base, ivory B224BI-WH: Isolator base, bright white B224BI-IV: Isolator base, ivory Ordering Information Accessories SMB600: Surface Mounting Kit (flanged) TR300: Accessory Flange Ring for B300 6" Base, bright white TR300-IV: Accessory Flange Ring for B300 6" Base, ivory RA100Z: Remote LED annunciator, 3-32 VDC The annunciator mounts to a U.S. single-gang electrical box. For use with B501 and B300-6. CK300: Bright White detector kit (Pack of 10) CK300-IR: White, detector color kit for use with MCS-COF Series Detectors. (Pack of 10) CK300-IV: Ivory, detector color kit. (Pack of 10) CK300-IR-IV: Ivory, detector color kit for use with MCS- COF Series detectors. (Pack of 10) CK300-BL: Black detector kit (Pack of 10) CK300-IR-Bl: Black, detector color kit for use with MCS- COF Series detectors. (Pack of 10) M02-04-01: Detector test magnet. M02-09-00: Test magnet with telescoping handle. XR2B: Detector removal tool. Allows the installation and/or removal of the detector heads from the bases in high ceiling applications. XP-4: Extension pole for XR2B. Shipped with three, 5- foot (1.524,m) sections. Velociti® Series 3 Detectors Technical Specifications 9020-0620 | G | 04/2018 ©2018 Honeywell International Inc. For a complete listing of all compliance approvals and certifications, please visit: http://www.gamewell- fci.com/en-US/ documentation/Pages/ Listings.aspx E3 Series®, Velociti® and Gamewell-FCI® are registered trademarks and CLIP™ is a trademark of Honeywell International Inc. UL® is a registered trademark of Underwriter’s Laboratories Inc. This document is not intended to be used for installation purposes. We try to keep our product information up-to- date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice. Honeywell Gamewell-FCI 12 Clintonville Road Northford, CT 06472-1610 203.484.7161 www.honeywell.com For more information Learn more about Gamewell-FCI’s Velociti® Series 3 Detectors and other products available by visiting www.Gamewell-FCI.com SYSTEMS Thermal Intelligent Detector Physical Specifications Height: 2.0 inches (51 mm) installed in B300-6 base Diameter: 6.1 inches (15.6 cm) installed in B300-6 base 4 inches (10.2 cm) installed in B501 base Shipping Weight: 3.4 oz (95 g) Operating Temperature Range: Thermal 135° F fixed: -4° F to 100° F (-20° C to 38° C) Thermal 135° F rate-of-rise: -4° F to 100° F (-20° C to 38° C) Thermal 190° F rate-of-rise: -4° F to 135° F (-20° C to 57° C) Operating Humidity Range: 10% to 93% non- condensing Rate-of-Rise Detection: : Responds to greater than 15°F/minute or 135°F (8.3° C/minute or 57°C Electrical Specifications Voltage Range: : 15 to 32 VDC Standby Current (@ 24 VDC): 200 uA (one communication every 5 seconds with green LED enabled) Max Alarm Current (max.): : 2 mA @ 24 VDC (one communication every 5 seconds with red LED enabled) Max Current (max.): : 4.5 mA @ 24 VDC (one communication every 5 seconds with amber LED enabled) Isolator Load Rating: : 0.0063 STANDARDS The Velociti® Series 3 Thermal Detectors are designed to comply with the following standard: UL Standard: UL 268 AGENCY LISTINGS AND APPROVALS These listings and approvals apply to the modules specified in this document. In some cases, certain modules or applications may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status. UL: S2332 FM: 3023594 MEA-FDNY: 219-02-E Vol. VI CSFM: 7270-1703-0502 ISO 9001 Certification Figure 1 B501 Mounting Base Figure 2 B210LP Mounting Base Figure 3 B224BI Mounting Base Figure 4 B224RB Mounting Base Intelligent Bases B501, B210LP, B224BI, B224RB and Mounting Kits and Accessories Addressable Devices General The Intelligent Velociti® and CLIP™ mounting bases and kits provide a variety of ways to install Gamewell-FCI detectors in any application. These mounting bases are non- addressable and are available in both the Velociti and CLIP protocols. The intelligent detectors can be mounted in any of the following devices, depending on the junction box selection (see Table 1 - Junction Box Selection Guide). •flanged bases • flangeless bases •plastic rings Note: The E3 Series® and S3 Series panels support both the Velociti® and CLIP™ protocols, and the GWF-7075 panel supports only the Velociti protocol. Relay, isolator, and sounder bases can be used to meet local code requirements. Relay bases provide one Form-C contact relay for the control of auxiliary functions such as door closure and elevator recall. Isolator bases allow loops to continue to operate under fault conditions and automatically restore when the fault is removed. Sounder bases are available in a combination temporal 3 and continuous tone model. The Intelligent Bases provide a variety of mounting options to meet your installation challenges. The bases are available in flanged or flangeless versions, so that you can mount the bases to a variety of junction boxes. See Table 1 for the Junction Box Selection Guide. You can use the SMB600 surface mounting box to mount the following bases: • B210LP relay base • B224BI isolator base • B224RB relay base FEATURES & BENEFITS All sounder bases offer the following features. •Complies with UL® Standards 268 and 464 •Includes the following three types of bases that comply with local code requirements: - Relay - Isolator - Sounder Relay Base Feature • Relay bases provide one Form-C contact relay Isolator Base Feature • Isolator bases include data communications lines to operate under fault condition Installation Features The bases offer the following flexible installation characteristics: • Offers multiple accessory options • Includes an installation mounting kit and accessories for several types of model options • Uses 12-24 AWG gauge wire ranges to provide the bases with flexible installation • Contains bases that enable quick and secure detector plug-in • Provides SEMS screws for easy wiring connections • Available in temporal and non-temporal pattern versions 2 Ordering Information NOTE: “WH” suffix indicates Bright White color model. NOTE: "-IV" suffix indicates Ivory color model. NOTE: "-BL" suffix indicates Black color model. Intelligent Bases B501-WHITE: Flangeless mounting base, bright white Dimensions: 4” (10.2 cm) diameter x 0.74” (18.8 mm) height B501-WHITE-BP: Flangeless mounting base bulk pack, bright white B501-IV: Standard European flangeless mounting base, ivory B501-BL: Standard European flangeless mounting base, black B224BI-WH: Plug-in Isolator detector base, bright white Dimensions: 6.85 (17.4 cm) diameter x 1.61” (4.1 cm) height B224BI-IV: Plug-in Isolator detector base, ivory B224RB-WH: Plug-in Relay detector base, bright white Dimensions: 6.85” (17.4 cm) diameter x 1.61” (4.1 cm) height B224RB-IV: Plug-in Relay detector base, ivory B300-6 : Standard flanged low-profile mounting base, white Dimensions: 6.1" (15.49 cm) diameter B300-6-BP: Bulk pack of B200-6 package contains 10 B300-6-IV: Standard flanged low-profile mounting base, ivory Ordering Information Mounting Kits and Accessories: BCK-200B: Detector kit, black CK300: Detector color kit, white Pack of 10 CK300-IR: Detector color kit for use with MCS-COF Series Detectors, white. Pack of 10 CK300-IV: Detector color kit, ivory. Pack of 10. CK300-IR-IV: Detector color kit for use with MCS-COF Series detectors, ivory. Pack of 10. CK300-BL: Detector color kit, black. Pack of 10. CK300-IR-Bl: Detector color kit for use with MCS-COF Series detectors, black. Pack of 10. TR300: Accessory flange ring for B300-6, bright white TR300-IV: Accessory flange ring for B300-6m ivory M02-04-01: Detector test magnet. M02-09-00: Test magnet with telescoping handle. RA100Z: Remote LED annunciator. 3-32 VDC. Mounts to a U.S. single-gang electrical box. For use with B401 and B300-6. SMB600: Surface mounting kit, flanged. TR300: Replacement flange for B210LP base, white TR300-IV: Replacement flange for B210LP base, ivory WCK-200B: Detector kit, white Mounting Kits and Accessories Table 1 lists the mounting kits and accessories assigned to each model. SINGLE- GANG 3.5" OCTAGONA L 4.0" OCTAGONA L 4.0" SQUARE 4.0" SQUARE WITH 3.0" MUD RING 50 MM 60 MM 70 MM 75 MM B501 No Yes No No Yes Yes Yes Yes No B210LP Yes Yes Yes Yes Yes No No No No B224BI No Yes Yes Yes Yes No Yes Yes Yes B224RB No Yes Yes Yes Yes No Yes Yes Yes NOTE: The box depth is contingent on the base and the wire size. For information on applicable local codes for appropriate recommendation, refer to the National Electrical Code. Table 1: Intelligent Bases Mounting Kits Intelligent Bases Technical Specifications 9021-60540 | J | 07/2018 ©2018 Honeywell International Inc. For a complete listing of all compliance approvals and certifications, please visit: http://www.gamewell- fci.com/en-US/ documentation/Pages/ Listings.aspx Gamewell-FCI®, E3 Series® and Velociti® are registered trademarks and Clip™ is a trademark of Honeywell International Inc. UL® is a registered trademark of Underwriters Laboratories Inc. ULC® is a registered trademark of Underwriters Laboratories of Canada Inc. This document is not intended to be used for installation purposes. We try to keep our product information up-to- date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice. Honeywell Gamewell-FCI 12 Clintonville Road Northford, CT 06472-1610 203.484.7161 www.honeywell.com For more information Learn more about Gamewell-FCI’s Intelligent Bases and other products available by visiting www.Gamewell-FCI.com SYSTEM Temperature Range: For B224RB, B224BI, and B210LP: 32°F to 120°F (0°C to 49° C) For B210LP, B300-6, B501: -4° F to 150°F (-20°C to 66°C) Humidity Range: 10% to 93% RH, non-condensing Wire Gauge: For B224BI, B224RB: 14 to 24 AWG For B210LP, B300-6, B501: 12 to 24 AWG Electrical Ratings: For B501, B224RB, B224BI: Operating Voltage: 15 to 32 VDC (powered by SLC) Standby Ratings: B501: 150 uA B224BI: 450 uA maximum B224RB: 170 uA Set Time (B224RB only): Short delay: 55-90 m seconds Long delay: 6 to 9 seconds Reset Time (B224RB only): 20 m seconds maximum Relay Characteristics (B224RB only): Two-coil Latching Relay One Form-C Contact Ratings (UL/CSA): 0.9 A @ 125 VAC (resistive) 0.9 A @ 110 VDC (inductive) 3.0 A @ 30 VDC (resistive) TEMPERATURE AND HUMIDITY RANGES This system meets NFPA requirements for operation at 0 – 49°C/32 – 120°F and at a relative humidity 93% ± 2% RH (noncondensing) at 32°C ± 2°C (90°F ± 3°F). However, the useful life of the system's standby batteries and the electronic components may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and its peripherals be installed in an environment with a normal room temperature of 15 – 27°C/60 – 80°F. STANDARDS The Intelligent Bases are designed to comply with the following standards: UL Standards: UL 268 UL 464 AGENCY LISTINGS AND APPROVALS These listings and approvals apply to the modules specified in this document. In some cases, certain modules or applications may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status. UL: S911 FM: 3035027 CSFM: 7135-1653:0213 7300-1653:0109 7300-1653:0126 7300-1653:0238 ISO 9001 Certification MS-7 Series MS-7 Series Manual Fire Alarm Pull Stations Addressable Devices General The Gamewell-FCI, MS-7 Series manual fire alarm pull stations are available in a wide variety of configurations. The pull stations comply with the Americans with Disabilities Act (ADA) 5-lb. maximum pull force requirement. Operating instructions and Braille text are engraved in the handle. All pull stations include a key lock/reset which is keyed alike with the Gamewell-FCI fire alarm control panels and other manual fire alarm pull stations. MS-7AF Velociti Addressable Station The MS-7AF Velociti® Series addressable station is a double action pull station designed for installation in the signaling line circuit of Gamewell-FCI analog addressable control panels. Activation of the pull station causes its assigned address to register at the fire alarm control panel. The door contains an LED which flashes green in normal condition and lights steady red when the station has been activated.* The station features screw terminals. MS-7ASF Velociti Addressable Station The MS-7ASF Velociti® Series addressable pull station is a single action station designed for installation in the signaling line circuit of Gamewell-FCI analog addressable control panels. Activation of the station causes its assigned address to register at the control panel. The door contains an LED which flashes green in normal condition and lights steady red when the pull station is activated.* The station features screw terminals. The Velociti® Series pull stations use a communication protocol that substantially increases the speed of communication between the sensors and certain Gamewell-FCI analog addressable fire alarm controls. These devices operate in a grouped fashion. If one of the devices in the group has a status change, the panel’s microprocessor stops the group poll and focuses on the single device. The net effect offers a response speed up to five times greater than earlier designs. MS-7 Double Action Station The MS-7 double action pull station is used with conventional fire alarm control panels. It features a set of single pole contacts and screw terminals for connection to an initiating circuit. FEATURES & BENEFITS • Addressable stations compatible with all Gamewell-FCI analog addressable fire alarm controls • Conventional stations suitable for use with any UL® Listed control panel • The pull stations (MS- 7LOB) are Listed for outdoor applications • Complies with ADA pull force requirements • Offers surface or semi- flush mounting • Shock and vibration resistant • Both single and double action pull stations available • Includes a tumbler lock for test and reset keyed alike with analog addressable fire alarm controls *Only the red LED is operative in panels that do not operate in Velociti mode 2 MS-7S Single Action Station The MS-7S single action pull station is used with conventional fire alarm control panels. It features a set of single pole contacts and wire leads for connection to an initiating circuit. MS-7SP Double Action Station The MS-7SP is a double action pull station similar to the MS-7 station, with the additional feature of including both English and Spanish instructions molded into the unit. MS-7LR Dual-action Agent Release Station The MS-7LR is designed for use with the Gamewell-FCI fire alarm control panels with releasing capabilities and Flex Series releasing systems. It features a set of single pole contacts and screw terminals used to connect to an initiating circuit. MS-7LRA Agent Release Station with Abort The MS-7LRA is designed for use with the Gamewell- FCI fire alarm control panels with releasing capabilities and Flex Series releasing systems where system abort capabilities are required. It consists of the following: • An MS-7LR mounted on a plate with an abort switch • LED indicators that signal system normal and system activated status MS-7LOB Double Action Station (Listed for Outdoor Applications) The MS-7LOB station must be mounted on a Model SB-I/O backbox. In retrofit applications, the pull station is UL Listed for use with the WP-10 backbox. It is intended for use with conventional control panels and has a set of single pole contacts and screw terminals. Mounting The MS-7 interior pull stations may be surface mounted or semi-flush mounted on a standard double-gang, or 4-inch (10.2 cm) square electrical box. An optional trim ring (BG12TR) may also be used for semi-flush mounting. NYC-Plate The NYC-Plate provides the backplate for the manual pull station. (See Figure 1). Figure 1 NYC-Plate Ordering Information MS-7: Double action station MS-7AF**: Velociti addressable double action station MS-7ASF**: Velociti addressable single action station MS-7S: Single action station, wire leads MS-7SP: Double action station, English and Spanish instructions MS-7LR: Agent release station, dual-action MS-7LRA: Agent release station with abort switch, LED indicators, dual- action MS-7LOB: Double action station, outdoor use (Includes SB-I/O - Indoor/outdoor use backbox) SB-I/O: Indoor/outdoor use backbackbox SB-10: Surface backbox BG12TR: Trim ring for semi-flush mount, plastic NY-PLATE: NYC backplate for manual pull station **For use with the Gamewell-FCI analog addressable control panels only. MS-7 Series Technical Specifications 9020-0616 | F | 11/17 ©2017 Honeywell International Inc. For a complete listing of all compliance approvals and certifications, please visit: http://www.gamewell- fci.com/en-US/ documentation/Pages/ Listings.aspx LEXAN® is a registered trademark of GE Plastics, a subsidiary of General Electric Company. Velociti® and Gamewell-FCI are registered trademarks of Honeywell International Inc. UL® is a registered trademark of Underwriter’s Laboratories Inc. This document is not intended to be used for installation purposes. We try to keep our product information up-to- date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice. Honeywell Gamewell-FCI 12 Clintonville Road Northford, CT 06472-1610 203.484.7161 www.honeywell.com For more information Learn more about Gamewell-FCI’s MS-7 Series and other products available by visiting www.Gamewell-FCI.com SYSTEMS Material: Lexan® Contact Ratings: 0.25 amps. @ 30 VAC/VDC (resistive) Dimensions: 5 5/8” H x 4 1/4” W x 1 1/4” D (14 x 10.1 x 3.2 cm) Operating Temperature: (MS-7AF, MS-7ASF): 32° to 120° F (0° to 49° C) (MS-7LOB): -30° to 150° F (-35° to 66° C) Relative Humidity : (MS-7AF, MS-7ASF): 10 to 93% (non-condensing) (MS-7LOB): 85% ± 5% @ 86° ± 3.6° (30° ± 2° C) Alarm Current: .0030 amp. 0.007 for LED Supervisory Current: (MS-7AF, MS-7ASF): .00030 amps. TEMPERATURE AND HUMIDITY RANGES This system meets NFPA requirements for operation at 0 – 49°C/32 – 120°F and at a relative humidity 93% ± 2% RH (noncondensing) at 32°C ± 2°C (90°F ± 3°F). However, the useful life of the system's standby batteries and the electronic components may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and its peripherals be installed in an environment with a normal room temperature of 15 – 27°C/60 – 80°F. STANDARDS The MS-7 Series is designed to comply with the following standard: UL Standard: UL 864 9th Edition AGENCY LISTINGS AND APPROVALS These listings and approvals apply to the modules specified in this document. In some cases, certain modules or applications may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status. UL: S2465 FM: 3023594 MEA FDNY: 67-02-E Vol. VII CSFM: 7160-1703:0119 7160-1703:0170 7160-1703:0109 ISO 9001 Certification Ceiling Speaker Strobes L Series, Indoor Ceiling Strobes and Dual Speakers Indoor Output Speaker Strobes and Dual Speakers for Ceiling Applications Notification Appliances General The L-Series indoor selectable-output speaker strobes and dual-voltage evacuation speakers offer a modern, aesthetic plug-in design that reduce costly ground faults. The universal mounting plate can be used in ceiling applications and its flexible design enables the Installer to easily perform the following: • Pre-wire mounting plates •Dress the wires Confirm wiring continuity before the Installer plugs-in the speakers. In addition, this product includes a protective plastic cover which shields exposed speaker components and prevents nicked wires. These devices enable faster installations by providing instant feedback to the Installer to ensure the following: • The wiring is properly connected. • The rotary switches are set to the selected voltage and power settings. • The 7 field-selectable candela settings are configured for wall speaker strobes. • The low total harmonic distortion of the SP speaker offers both high-fidelity and high-volume sound output so that it can be used in high ambient noise applications. L-Series makes installation easy to install the L-Series speakers or speaker strobe, do the following: 1. Attach a universal mounting plate to a 4 x 4 x 2 1/8 inch backbox. Flush- mount applications do not require an extension ring. 2. Connect the notification appliance circuit or speaker wiring to the terminals on the mounting plate. 3. To attach the speaker or speaker strobe to the mounting plate, insert the product tabs into the mounting plate grooves. 4. Hinge the device into position to lock the product pins into the mounting plate terminals. 5. A catch temporarily holds the device in place until you secure the device with a captured mounting screw. FEATURES & BENEFITS • Includes a plug-in feature and protective cover to reduce ground faults • Contains a universal mounting plate with an on-board shorting spring that is used to test the wiring continuity before an installation • No extension ring required • Field-selectable candela settings on ceiling units: - 15 - 30 - 75 - 95 - 115 - 150 - 177 • Uses an automatic selection of 12- or 24- volt operation at 15 and 30 candela • Provides a rotary switch that simplifies the field selection of speaker voltage (25) and 70.7 VRMS) and the following power settings: - 1/4 watt - 1/2 watt - 1 watt - 2 watts • Offers speakers with both high-fidelity and high-volume sound output • Compatible with the System Sensor synchronization protocol • Supports electrical compatibility with the existing SpectrAlert and the SpectrAlert Advance products •Designed with a tamper-resistant construction • Built with an updated modern design 2 L-Series Speaker and Speaker Strobe Specifications Architectural/Engineering Specifications General The L-Series speaker and speaker strobes shall mount to a 4 x 4 x 2 1/8-inch backbox. A universal mounting plate shall be used for the mounting ceiling and wall products. The notification appliance circuit and amplifier wiring shall terminate at the universal mounting plate. Also, the L-Series speaker strobes, when used with the Sync•Circuit. Module accessory, shall be powered from a non-coded notification appliance circuit output and shall operate on a nominal 12 or 24 volts. When these devices are used with the Sync•Circuit Module, either of the following may occur. • 12-volt rated notification appliance circuit outputs shall operate between 8.5 and 17.5 volts. • 24-volt rated notification appliance circuit outputs shall operate between 16.5 and 33 volts. The Indoor L-Series products shall operate between 32° F and 120°F from a regulated DC, or full-wave rectified, unfiltered power supply. Speaker strobes shall have the following field-selectable candela settings: Speaker The speaker shall be an L-Series model _______ dual- voltage transformer speaker capable of operating at 25.0 or 70.7 nominal VRMS. It should be listed to UL Standard 1480 and shall be approved for fire protective service. The speaker shall have a frequency range of 400 to 4,000 Hz and shall have an operating temperature between 32°F and 120°F. The speaker shall have power taps and voltage that are selected by rotary switches. Speaker Strobe Combination The speaker strobe shall be an L-Series model __________ listed to UL Standard 1480 and UL Standard 1971 and be approved for fire protective signaling systems. The speaker shall be capable of operating at 25.0 or 70.7 nominal VRMS selected via rotary switch, and shall have a frequency range of 400 to 4,000 Hz. The speaker shall have power taps that are selected by rotary switch. The strobe shall comply with the NFPA 72 requirements for visible signaling appliances, flashing at 1 Hz over the strobe’s entire operating voltage range. The strobe light shall consist of a xenon flash tube and associated lens/reflector system. Synchronization Module The module shall be a Sync•Circuit model MDL3 listed to UL Standard 464 and shall be approved for fire protective service. The module shall synchronize SpectrAlert strobes at 1 Hz. The module shall mount to a 4 11/16 x 4 11/16 x 2 1/8-inch back box. The module shall also control two Style Y (Class B) circuits or one Style Z (Class A) circuit. The module shall synchronize multiple zones. Daisy chaining two or more synchronization modules together will synchronize all the zones they control. The module shall not operate on a coded power supply. UL Current Draw Data Table 1 lists the UL maximum strobe current draw. Table 2 lists the ceiling mount speaker sound outputs. Table 3 lists the ceiling-mount speaker strobe sound outputs. •15 •30 •75 •95 •115 •150 •177 8-17.5 Volts 16-33 Volts Candela DC DC FWR 15 87 41 60 30 153 63 86 75 NA 111 142 95 NA 134 164 115 NA 158 191 150 NA 189 228 177 NA 226 264 Table 1 UL Max. Strobe Current Draw (mA RMS) Setting UL Reverberant (dBA @10 ft) UL Anechoic (dBA @10 ft) 1/4 W 79 79 1/2 W 82 82 1 W 85 85 2 W 88 88 Table 2 Ceiling Speaker Sound Outputs Setting UL Reverberant (dBA @10 ft) UL Anechoic (dBA @10 ft) 1/4 W 77 77 1/2 W 80 80 1 W 83 83 2 W 86 86 Table 3 Ceiling-Mount Speaker Strobe Sound Output 3 Dimensions Figure 1 shows the speaker dimensions. Figure 2 shows the speaker dimensions. Surface Mounting Figure 3 illustrates the ceiling-mount speaker and speaker strobes with the SBBCR/SBBCWL surface mount backbox. L-Series Ordering Information SpectrAlert Speakers and Strobes: Ceiling Mount: SPCWL: White Speaker only SPCRL: Red Speaker only SPSCWL: White Speaker Strobe SPSCRL: Red Speaker Strobe SPSCWL-P: Plain, Speaker Strobe SPSCWL-SP: Fuego, Speaker Strobe SPSCWL-CLR-ALERT : Alert, Speaker Strobe,Clear Lens Accessories: SBBCWL: White, Universal Ceiling Surface Mount Back Box SBBCRL: Red, Universal Ceiling Surface Mount Back Box TRC-2W: White, Universal Ceiling Trim Ring TRC-2: Red, Universal Ceiling Trim Ring Figure 1 Speaker Dimensions Figure 2 Speaker Dimensions Figure 3 Ceiling-Mount Speaker and Speaker Strobe with SBBCRL/SBBCWL Surface Mount Backbox L Series, Indoor Ceiling Strobes and Dual Speakers Technical Specifications 9021-60930 | C | 03/18 ©2018 Honeywell International Inc. For a complete listing of all compliance approvals and certifications, please visit: http://www.gamewell- fci.com/en-US/ documentation/Pages/ Listings.aspx E3 Series® and Gamewell-FCI® are registered trademarks of Honeywell International Inc. UL® is a registered trademark of Underwriter’s Laboratories Inc. This document is not intended to be used for installation purposes. We try to keep our product information up-to- date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice. Honeywell Gamewell-FCI 12 Clintonville Road Northford, CT 06472-1610 203.484.7161 www.honeywell.com For more information Learn more about Gamewell-FCI’s L Series, Indoor Ceiling Strobes and Dual Speakers and other products available by visiting www.Gamewell-FCI.com SYSTEM Electrical/Operating Specifications: Nominal Voltage (speakers): 25 Volts or 70.7 Volts (nominal) Maximum Supervisory Voltage (speakers): 50 VDC Strobe Flash Rate: 1 flash per second Nominal Voltage (strobes): Regulated 12 VDC or Regulated 24 VDC/FWR Operating Voltage Range (includes fire alarm panels with built-in sync): 8 to 17.5 V (12 V nominal) or 16 to 33 V (24 V nominal) Operating Voltage with MDL3 Sync Module: 8.5 to 17.5 V (12 V nominal) or 16.5 to 33 V (24 V nominal) Frequency Range: Frequency Range: 400 to 4,000 Hz Power: ¼, ½, 1, 2 watts STANDARDS The L-Series, Indoor Ceiling Strobes and Horn Strobes are designed to comply with the following standard: UL Standard: UL 1971 and UL 464 AGENCY LISTINGS AND APPROVALS These listings and approvals apply to the modules specified in this document. In some cases, certain modules or applications may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status. UL: S5512, S4011 CSFM: 7320-1653:0505 ISO 9001 Certification Physical Specifications: Operating Temperature:32°F to 120°F (0°C to 49°C) Humidity Range:10 to 93% non-condensing Dimensions,Ceiling-Mount:Diameter Depth SPC Speaker 6.8 in, 173 mm 1.0 in, 25 mm With Surface Mount BacKbox 6.9 in, 176 mm 3.5 in, 89 mm SPSC Speaker Strobe 6.8 in, 173 mm 2.8 in, 73 mm With Surface Mount Backbox 6.9 in, 176 mm 5.37 in,136 mm Wall Speaker Strobe L Series, Indoor Wall Speaker Strobes and Speakers Indoor Selectable-Output Speaker Strobes and Dual-Voltage Evacuation Speakers for Wall Applications Notification Appliances General The L-Series indoor selectable-output speaker strobes and dual-voltage evacuation speakers offer a modern, aesthetic plug-in design that reduce costly ground faults. The universal mounting plate can be used in wall installation applications and its flexible design enables the Installer to easily perform the following: • Pre-wire mounting plates •Dress the wires • Confirm wiring continuity before the Installer plugs-in the speakers This product includes a protective plastic cover which shields exposed speaker components and prevents nicked wires. These devices enable faster installations by providing instant feedback to the Installer to ensure the following: • The wiring is properly connected. • The rotary switches are set to the selected voltage and power settings. • The 7 field-selectable candela settings are configured for wall speaker strobes. The low total harmonic distortion of the speaker offers both high-fidelity and high- volume sound output so that it can be used in high ambient noise applications. L-Series makes installation easy To install the L-Series speakers or speaker strobe, do the following: 1. Attach a universal mounting plate to a 4 x 4 x 2 1/8 inch backbox. Flush-mount applications do not require an extension ring. 2. Connect the notification appliance circuit or speaker wiring to the terminals on the mounting plate. 3. To attach the speaker or speaker strobe to the mounting plate, insert the product tabs into the mounting plate grooves. 4. Hinge the device into position to lock the product pins into the mounting plate terminals. 5. A catch will temporarily hold the device in place until you secure the device with a captured mounting screw. FEATURES & BENEFITS • Includes a plug-in feature to reduce ground faults and a protective cover to shield speaker components • Contains a universal mounting plate with an on-board shorting spring that is used to test the wiring continuity before an installation • No extension ring required • Field-selectable candela settings on wall units: - 15 - 30 - 75 - 95 - 110 - 135 - 185 • Uses an automatic selection of 12- or 24- volt operation at 15 and 30 candela • Provides a rotary switch that simplifies the field selection of speaker voltage (25) and 70.7 VRMS) and the following power settings: - 1/4 watt - 1/2 watt - 1 watt - 2 watts • Offers speakers with both a high-fidelity and a high-volume sound output • Compatible with the System Sensor® synchronization protocol • Supports electrical compatibility with the existing SpectrAlert™ and the SpectrAlert Advance products •Designed with a tamper-resistant construction • Built with an updated modern design 2 L-Series Speaker and Speaker Strobe Specifications Architectural/Engineering Specifications General The L-Series speaker and speaker strobes shall mount to a 4 x 4 x 2 1/8-inch backbox. A universal mounting plate shall be used for the mounting ceiling and wall products. The notification appliance circuit and amplifier wiring shall terminate at the universal mounting plate. Also, the L-Series speaker strobes, when used with the Sync•Circuit. Module accessory, shall be powered from a non-coded notification appliance circuit output and shall operate on a nominal 12 or 24 volts. When it is used with the Sync•Circuit Module, either of the following may occur. • 12-volt rated notification appliance circuit outputs shall operate between 8.5 and 17.5 volts. • 24-volt rated notification appliance circuit outputs shall operate between 16.5 and 33 volts. The Indoor L-Series products shall operate between 32° F and 120°F from a regulated DC, or full-wave rectified, unfiltered power supply. Wall-mount speaker strobes shall include the following field-selectable candela settings: Speaker The speaker shall be an L-Series model _______ dual- voltage transformer speaker capable of operating at 25.0 or 70.7 nominal VRMS. It should be listed to UL Standard 1480 and shall be approved for fire protective service. The speaker shall have a frequency range of 400 to 4,000 Hz and shall have an operating temperature between 32°F and 120°F. The speaker shall have power taps and voltage that are selected by rotary switches. Speaker Strobe Combination The speaker strobe shall be an L-Series model __________ listed to UL Standard 1480 and UL Standard 1971 and be approved for fire protective signaling systems. The speaker shall be capable of operating at 25.0 or 70.7 nominal VRMS selected via rotary switch, and shall have a frequency range of 400 to 4,000 Hz. The speaker shall have power taps that are selected by rotary switch. The strobe shall comply with the NFPA 72 requirements for visible signaling appliances, flashing at 1 Hz over the strobe’s entire operating voltage range. The strobe light shall consist of a xenon flash tube and associated lens/reflector system. Synchronization Module The module shall be a Sync•Circuit model MDL3 listed to UL Standard 464 and shall be approved for fire protective service. The module shall synchronize SpectrAlert strobes at 1 Hz. The module shall mount to a 4 11/16 x 4 11/16 x 21/8-inch backbox. The module shall also control two Style Y (Class B) circuits or one Style Z (Class A) circuit. The module shall synchronize multiple zones. Daisy-chaining two or more synchronization modules together will synchronize all the zones they control. The module shall not operate on a coded power supply. UL Current Draw Data Table 1 lists the UL maximum strobe current draw. Table 2 lists the speaker strobe sound outputs. Table 3 lists the speaker sound outputs. •15 •30 •75 •95 •110 •135 •185 Candela 8-17.5 Volts 16-33 Volts FWRDCDC 15 88 43 60 30 143 63 83 75 N/A 107 136 95 N/A 121 155 110 N/A 148 179 135 N/A 172 209 185 N/A 222 257 Table 1: UL Max. Strobe Current Draw (mA RMS) Setting UL Reverberant (dBA @10 ft) UL Anechoic (dBA @10 ft) 1/4 W 77 77 1/2 W 80 80 1 W 83 83 2 W 86 86 Table 2: Sound Output Speaker Strobe Setting UL Reverberant (dBA @10 ft) UL Anechoic (dBA @10 ft) 1/4 W 79 79 1/2 W 82 82 1 W 83 85 2 W 88 88 Table 3: Sound Output Speaker 3 Dimensions Figure 1 shows the speaker dimensions. Figure 2 shows the speaker dimensions. Surface Mounting Figure 3 illustrates the wall-mount speaker and speaker strobes with the SBBSPRL surface mount backbox. L-Series Ordering Information Speakers and Speaker Strobes Wall Mount: SPWL: White, Speaker only SPRL: Red, Speaker only SPSWL: White, Speaker Strobe SPSRL: Red, Speaker Strobe SPSRL-P: Plain Speaker Strobe SPSWL-P: White, Plain Speaker Strobe SPSWL-ALERT: White, Speaker Strobe, Amber Lens SPSWL-CLR-ALERT : White Speaker Strobe Clear Lens SPSRL-SP: White, Speaker Strobe, Fuego Accessories: RFPW: White, 7 in × 9.5 in Retrofit Plate RFP: Red, 7 in × 9.5 in Retrofit Plate SBBSPW: White, Surface Mount Back Box for Speakers and Speaker Strobes SBBSPR: Red, Surface Mount Back Box for Speakers and Speaker Strobes TRW: White, Wall Mount Trim Ring TR: Red, Wall Mount Trim Ring Note: All -P models have a plain housing (no “FIRE” marking on the cover). Figure 1 Wall-Mount Speaker Figure 2 Wall-Mount Speaker Strobe Figure 3 Wall-Mount Speaker Strobe with SBBSPRL Surface Mount Backbox L Series, Indoor Wall Speaker Strobes and Speakers Technical Specifications 9021-60931 | C | 03/18 ©2018 Honeywell International Inc. For a complete listing of all compliance approvals and certifications, please visit: http://www.gamewell- fci.com/en-US/ documentation/Pages/ Listings.aspx E3 Series®, Gamewell-FCI® are registered trademarks and System Sensor™ and SpectrAlert™ is a trademark of Honeywell International Inc. UL® is a registered trademark of Underwriter’s Laboratories Inc. This document is not intended to be used for installation purposes. We try to keep our product information up-to- date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice. Honeywell Gamewell-FCI 12 Clintonville Road Northford, CT 06472-1610 203.484.7161 www.honeywell.com For more information Learn more about Gamewell-FCI’s L Series, Indoor Wall Speaker Strobes and Speakers and other products available by visiting www.Gamewell-FCI.com SYSTEMS Temperature Range: Operating Temperature: 32°F to 120°F (0°C to 49°C) Humidity Range: 10 to 93% non-condensing Electrical/Operating Specifications: Nominal Voltage (speakers): 25 Volts or 70.7 Volts (nominal) Maximum Supervisory Voltage (speakers): 50 VDC Strobe Flash Rate: 1 flash per second Nominal Voltage (strobes): Regulated 12 VDC or Regulated 24 VDC/FWR Operating Voltage Range (includes fire alarm panels with built-in sync): 8 to 17.5 V (12 V nominal) or 16 to 33 V (24 V nominal) Operating Voltage with MDL3 Sync Module: 8.5 to 17.5 V (12 V nominal) or 16.5 to 33 V(24 V nominal) Frequency Range: 400 to 4,000 Hz Power: ¼, ½, 1, 2 watts TEMPERATURE AND HUMIDITY RANGES This system meets NFPA requirements for operation at 0 – 49°C/32 – 120°F and at a relative humidity 93% ± 2% RH (noncondensing) at 32°C ± 2°C (90°F ± 3°F). However, the useful life of the system's standby batteries and the electronic components may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and its peripherals be installed in an environment with a normal room temperature of 15 – 27°C/60 – 80°F. STANDARDS The L-Series, Indoor Wall Speaker Strobes and Speakers are designed to comply with the following standard: UL Standard: UL 1971 and UL 464 AGENCY LISTINGS AND APPROVALS These listings and approvals apply to the modules specified in this document. In some cases, certain modules or applications may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status. UL: S5512, S4011 CSFM: 7320-1653:0505 ISO 9001 Certification Physical Specifications Dimensions, Wall-Mount:Length Width Depth SP Speaker:6.5 in, 165 mm 5 in, 127 mm 2.3 in, 58 mm With Surface Mount Backbox: 6.6 in, 168 mm 5.1 in, 130 mm 3.2 in, 82 mm SPS Speaker/Strobe (including lens and speaker): 6.5 in, 165 mm 5.0 in, 127 mm 2.3 in, 58 mm With Surface Mount Backbox:6.6 in, 168 mm 5.1 in, 130 mm 4.55 in 116 mm Calculations Protected Premises:Date:2/23/2024 Address: City:State:ID Zip:83460 Prepared Phone:801-468-8300 Address:Email: City:State:Utah Zip:84115 Secondary Load Requirements 9.73 Amp Hours Total (AH) 8.04 0.07 8.11 x 1.20 9.73 AH 18.00 Amp Hours Battery Distribution Chart Spare Battery Capacity 8.27 Amp Hours Secondary Standby Load 9.65 Amp Hours Secondary Alarm Load 0.08 Amp Hours Current Draw Time (hours) Total Secondary Load from the calculation table below. Shows amp-hour distribution of your selections. Derating factor Secondary Load Requirements 18 AH Battery (12 Volt Required Alarm Time (hours) 0.084 hours Salt Lake City 24 hours Required Standby Time University Operations Fire Alarm Upgrade Brigham Young University Idaho Rexburg Nelson Fire Systems System Power Requirements E3 Fire Alarm Control Panel with Broadband Battery Selection Secondary Standby Load 0.335 A Secondary Alarm Load 1481 S Major Street office@nelsonfire.com 0.803 A x x Select batteries from the list bl Total Secondary Load Spare Battery Capacity 46% Secondary Standby Load 54% Secondary Alarm Load 0%Spare Battery Capacity Secondary Standby Load Secondary Alarm Load 0.335 A 0.803 A Qty Draw Standby Qty Draw Alarm 1 x 0.08100 0.08100 1 x 0.15000 0.15000 1 x 0.08100 0.08100 1 x 0.15000 0.15000 Intel. Loop Interface Main Board - Apollo (ILI95-MB-E3)0 x 0.05000 0 x 0.09100 Intel. Loop Interface Supplement Board - Apollo (ILI95-S-E3)0 x 0.05000 0 x 0.09100 E3 Panel, 1 SLC 0 x 0.05600 0 x 0.07600 E3 Panel, 1 SLC with DACT 0 x 0.07500 0 x 0.09500 1 x 0.06500 0.06500 1 x 0.08500 0.08500 0 x 0.08500 0 x 0.10500 120V Power Supply Sub-Assembly (PM-9)1 x 0.05000 0.05000 1 x 0.05000 0.05000 240V Power Supply Sub-Assembly (PM-9G)0 x 0.02700 0 x 0.05000 1 x 0.02400 0.02400 1 x 0.02800 0.02800 0 x 0.01300 0 x 0.01300 0 x 0.01800 0 x 0.01800 0 x 0.05000 0 x 0.07500 0 x 0.20000 0 x 0.20000 1 x 0.01100 0.01100 1 x 0.01100 0.01100 0 x 0.01100 0 x 0.01100 0 x 0.06500 0 x 0.06500 Intelligent Network Inferface Module (INI-7100)0 x 0.04000 0 x 0.04000 0 x 0.02000 0 x 0.02000 0 x 0.03500 0 x 0.200000x0.00100 0 x 0.00100 0 x 0.00100 0 x 0.00100 0 x 0.15000 0 x 0.15000 0 x 0.01100 0 x 0.01100 0 x 0.00100 0 x 0.00100 0 x 0.02000 0 x 0.020000x0.00200 0 x 0.00650 0 x 0.15000 0 x 0.150000x0.05000 0 x 0.05000 240V Power Supply Sub-Assembly (PM-9G)0 x 0.02700 0 x 0.050000x0.08600 0 x 2.20600 Amplifier Sub-assembly, 50 watt 70V (AM-50-70)0 x 0.04900 0 x 2.300000x0.00200 0 x 0.00650 0 x 0.00200 0 x 0.00650 0 x 0.00200 0 x 0.00650 0 x 0.15000 0 x 0.15000 0 x 0.01100 0 x 0.01100 0 x 0.00100 0 x 0.00100 0 x 0.02000 0 x 0.02000 0 x 0.00200 0 x 0.00650 0 x 0.00200 0 x 0.00650 0 x 0.00200 0 x 0.00650 13 x 0.00020 0.00260 13 x 0.00200 0.02600 64 x 0.00020 0.01280 64 x 0.00200 0.12800 0 x 0.00020 0 x 0.00200 0 x 0.00038 0 x 0.00500 0 x 0.00038 0 x 0.00650 25 x 0.00030 0.00750 25 x 0.00700 0.17500 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 0 x 0.00000 1 1 Intel. Loop Interface Supplement Board (ILI-S-E3) Total Standby Load:0.335 A 0.803 ATotal Alarm Load: E3 Panel, 2 SLC with DACT 2. E3 Optional Modules Remote LED Driver Module (ANU-48) Addressable Node Expander (ANX) Digital Communicator (DACT-E3) Remote LED Driver Module (LDM-7100) Optional Remote Serial Annunicator (LCD-7100) Alarm CurrentStandby Current System Current Draw - FACP E3 Series Control Panel with Broadband Total AlarmTotal Standby Intel. Loop Interface, Main Board (ILI-MB-E3) Addressable Switch Sub-assembly (ASM-16) Addressable Output Module-Telephone (AOM-TEL) Addressable Output Module-Signal (AOM-2SF) 1. System Device E3 Panel, 2 SLC Amplifier Sub-assembly, 50 watt 25V (AM-50) 5. INI-VGX Voice Gateway LCD Display & Switch Control (LCD-E3) ARCNET Repeater (RPT-E3) Printer Transient Module (PTRM) Firefighter's Telephone (Handset) 3. 7100 Optional Modules Intel. Network Command Voice Gateway (INI-VGE) Addressable Switch Sub-assembly (ASM-16) Voice Paging Microphone (Microphone) Network LCD Annunicator (NGA) Auxiliary Switch Sub-Assembly (ASM-16) 4. INI-VGC Command Center Intel. Network Command Center (INI-VGC) 6. INI-VGE Command Center Voice Gateway DNR Firefighter's Telephone (Handset) Addressable Output Module-Signal (AOM-2SF) Intel. Network Voice Gateway (INI-VGX) 120V Power Supply Sub-Assembly (PM-9) Class A Option Module (CAOM) Municipal Circuit Option Module (MCOM) Addressable Output Module-Telephone (AOM-TEL) Addressable Output Module-Audio (AOM-MUX) Voice Paging Microphone (Microphone) MS-7AF 8. Notification Appliances Addressable Output Module-Telephone (AOM-TEL) Addressable Output Module-Audio (AOM-MUX) ASD-PL3 7. Smoke Detectors/Modules ATD-RL3 Device AMM-4F/AMM-2F AOM-2RF/AOM-2SF Protected Premises:Date:2/23/2024 Address: City:State:ID Zip:83460 Prepared Phone:801-468-8300 Address:Email: City:State:Utah Zip:84115 Secondary Load Requirements 11.78 Amp Hours Total (AH) 8.69 1.13 9.82 x 1.20 11.78 AH 18.00 Amp Hours Battery Distribution Chart Spare Battery Capacity 6.22 Amp Hours Secondary Standby Load 10.43 Amp Hours Secondary Alarm Load 1.35 Amp Hours Current Draw Time (hours) Total Secondary Load from the calculation table below. Shows amp-hour distribution of your selections. Derating factor Secondary Load Requirements 18 AH Battery (12 Volt Required Alarm Time (hours) 0.084 hours Salt Lake City 24 hours Required Standby Time University Operations Fire Alarm Upgrade Brigham Young University Idaho Rexburg Nelson Fire Systems System Power Requirements E3 Fire Alarm Control Panel with Broadband Battery Selection Secondary Standby Load 0.362 A Secondary Alarm Load 1481 S Major Street office@nelsonfire.com 13.422 A x x Select batteries from the list bl Total Secondary Load Spare Battery Capacity 35%Secondary Standby Load 58% Secondary Alarm Load 7%Spare Battery Capacity Secondary Standby Load Secondary Alarm Load 0.362 A 13.422 A Qty Draw Standby Qty Draw Alarm 0 x 0.08100 1 x 0.15000 0.15000 0 x 0.08100 0 x 0.15000 Intel. Loop Interface Main Board - Apollo (ILI95-MB-E3)0 x 0.05000 0 x 0.09100 Intel. Loop Interface Supplement Board - Apollo (ILI95-S-E3)0 x 0.05000 0 x 0.09100 E3 Panel, 1 SLC 0 x 0.05600 0 x 0.07600 E3 Panel, 1 SLC with DACT 0 x 0.07500 0 x 0.09500 1 x 0.06500 0.06500 1 x 0.08500 0.08500 0 x 0.08500 0 x 0.10500 120V Power Supply Sub-Assembly (PM-9)1 x 0.05000 0.05000 1 x 0.05000 0.05000 240V Power Supply Sub-Assembly (PM-9G)0 x 0.02700 0 x 0.05000 0 x 0.02400 1 x 0.02800 0.02800 0 x 0.01300 0 x 0.01300 0 x 0.01800 0 x 0.01800 0 x 0.05000 0 x 0.07500 0 x 0.20000 0 x 0.20000 1 x 0.01100 0.01100 1 x 0.01100 0.01100 0 x 0.01100 0 x 0.01100 0 x 0.06500 0 x 0.06500 Intelligent Network Inferface Module (INI-7100)0 x 0.04000 0 x 0.04000 0 x 0.02000 0 x 0.02000 0 x 0.03500 0 x 0.200000x0.00100 0 x 0.00100 0 x 0.00100 0 x 0.00100 0 x 0.15000 0 x 0.15000 0 x 0.01100 0 x 0.01100 0 x 0.00100 0 x 0.00100 0 x 0.02000 0 x 0.020000x0.00200 0 x 0.00650 1 x 0.15000 0.15000 1 x 0.15000 0.150000x0.05000 0 x 0.05000 240V Power Supply Sub-Assembly (PM-9G)0 x 0.02700 0 x 0.050001x0.08600 0.08600 1 x 2.20600 2.20600 Amplifier Sub-assembly, 50 watt 70V (AM-50-70)0 x 0.04900 0 x 2.300000x0.00200 0 x 0.00650 0 x 0.00200 0 x 0.00650 0 x 0.00200 0 x 0.00650 0 x 0.15000 0 x 0.15000 0 x 0.01100 0 x 0.01100 0 x 0.00100 0 x 0.00100 0 x 0.02000 0 x 0.02000 0 x 0.00200 0 x 0.00650 0 x 0.00200 0 x 0.00650 0 x 0.00200 0 x 0.00650 0 x 0.00020 0 x 0.00200 0 x 0.00020 0 x 0.00200 0 x 0.00020 0 x 0.00200 0 x 0.00038 0 x 0.00500 0 x 0.00038 0 x 0.00650 0 x 0.00030 0 x 0.00700 0 x 0.00000 0 x 0.00000 1 x 0.00000 0.00000 1 x 0.08200 0.08200 95 x 0.00000 0.00000 95 x 0.08200 7.79000 35 x 0.00000 0.00000 35 x 0.08200 2.87000 0 x 0.00000 0 x 0.00000 1 1 Intel. Loop Interface Supplement Board (ILI-S-E3) Total Standby Load:0.362 A 13.422 ATotal Alarm Load: E3 Panel, 2 SLC with DACT 2. E3 Optional Modules Remote LED Driver Module (ANU-48) Addressable Node Expander (ANX) Digital Communicator (DACT-E3) Remote LED Driver Module (LDM-7100) Optional Remote Serial Annunicator (LCD-7100) Alarm CurrentStandby Current System Current Draw - FACP E3 Series Control Panel with Broadband Total AlarmTotal Standby Intel. Loop Interface, Main Board (ILI-MB-E3) Addressable Switch Sub-assembly (ASM-16) Addressable Output Module-Telephone (AOM-TEL) Addressable Output Module-Signal (AOM-2SF) 1. System Device E3 Panel, 2 SLC Amplifier Sub-assembly, 50 watt 25V (AM-50) 5. INI-VGX Voice Gateway LCD Display & Switch Control (LCD-E3) ARCNET Repeater (RPT-E3) Printer Transient Module (PTRM) Firefighter's Telephone (Handset) 3. 7100 Optional Modules Intel. Network Command Voice Gateway (INI-VGE) Addressable Switch Sub-assembly (ASM-16) Voice Paging Microphone (Microphone) Network LCD Annunicator (NGA) Auxiliary Switch Sub-Assembly (ASM-16) 4. INI-VGC Command Center Intel. Network Command Center (INI-VGC) 6. INI-VGE Command Center Voice Gateway DNR Firefighter's Telephone (Handset) Addressable Output Module-Signal (AOM-2SF) Intel. Network Voice Gateway (INI-VGX) 120V Power Supply Sub-Assembly (PM-9) Class A Option Module (CAOM) Municipal Circuit Option Module (MCOM) Addressable Output Module-Telephone (AOM-TEL) Addressable Output Module-Audio (AOM-MUX) Voice Paging Microphone (Microphone) MS-7AF SPSCWL 8. Notification Appliances SPSWL Addressable Output Module-Telephone (AOM-TEL) Addressable Output Module-Audio (AOM-MUX) ASD-PL3 7. Smoke Detectors/Modules ATD-RL3 SPCWL Device AMM-4F/AMM-2F AOM-2RF/AOM-2SF Drawings UNIVERSITY OPERATIONS FIRE ALARM UPGRADE BRIGHAM YOUNG UNIVERSITY- IDAHO FIRE ALARM SYSTEM JPK PAYNE TDT (ARCH D) 1/16" = 1' XXXX XXXX UN I V E R S I T Y O P E R A T I O N S F I R E A L A R M U P G R A D E BR I G H A M Y O U N G U N I V E R S I T Y - I D A H O RE X B U R G , I D A H O FI R E A L A R M S Y S T E M PROJECT COVER SHEET FA-C-01 NELSON FIRE SYSTEMS DRAWN BY: DESIGNED BY: APPROVED BY: DATE: SCALE: PROJECT NO: REVISION NO: DRAWING NAME: NO T E : NF S D R A W I N G S A R E B A S E D O N T H E P R O J E C T AR C H I T E C T U R E / E N G I N E E R ( A / E ) P L A N S A N D SP E C I F I C A T I O N S F U R N I S H E D T O N F S . A / E I S S O L E L Y RE S P O N S I B L E ( N O T N F S ) F O R T H E T Y P E , S I Z E , LO C A T I O N , A N D S U I T A B I L I T Y O F A L L F I R E A L A R M S , CO N T R O L P A N E L S , A N D O T H E R D E V I C E S S H O W N O N TH E A / E P L A N S . N F S D R A W I N G S A R E T O S H O W O N L Y TH E W I R I N G D I A G R A M S B E T W E E N F I R E A L A R M DE V I C E S A N D C O N T R O L P A N E L S . N F S I S N O T RE S P O N S I B L E F O R T H E I N F O R M A T I O N S H O W N O N T H E A/ E P L A N S . NELSON FIRE SYSTEMS PAGE: BYU-I UO FA UPGRADE C.DWG 2/8/2024 1:45:26 PM INDEX OF DRAWINGS PAGE 1 2 3 4 5 6 FA-C-01 FA-R-01 FA-L-01 FA-L-02 FA-G-01 FA-G-02 SHEET #LEVEL PROJECT COVER SHEET / INDEX OF DRAWINGS FIRE ALARM BUILDING RISER DIAGRAM / MATRIX LOWER LOWER GROUND GROUND DEVICE SCHEDULE COUNTS SMOKE DETECTOR w/BASE HEAT DETECTOR w/BASE MANUAL PULL STATION SPEAKER/STROBE- WALL SPEAKER/STROBE- CEILING ASD-PL3 w/B300-6 ATD-L3R w/B300-6 MS-7AF SPSWL SPSCWL DESCRIPTION FIRE ALARM CONTROL UNIT EXISTING TRANSPONDER PANEL EXISTING S T F SS SS FACU TRAN C 4 SQ. 2-1/8" DEEP BOX MINIMUM w/3/O MUD RING 4 SQ. 2-1/8" DEEP BOX MINIMUM w/3/O MUD RING 4 SQ. 2-1/8" DEEP BOX MINIMUM w/SINGLE GANG MUD RING 4 SQ. 2-1/8" DEEP BOX MINIMUM w/1-1/2" EXT. RING 4 SQ. 2-1/8" DEEP BOX MINIMUM w/1-1/2" EXT. RING EXISTING TO REMAIN EXISTING TO REMAIN PART NUMBER MOUNTING REQUIREMENTSYMBOL 13 64 25 1 95 SHEET CONTENTS ADDRESSABLE CIRCUITS NOTIFICATION CIRCUITS ADDRESSABLE CIRCUITS NOTIFICATION CIRCUITS SPEAKER ONLY- CEILING SPCWLSC 4 SQ. 2-1/8" DEEP BOX MINIMUM w/1-1/2" EXT. RING35 BUILDING CONSTRUCTION TYPE: IIB BUILDING SQUARE FOOTAGE: 55,364 FT 2 BUILDING SPRINKLERED: INDICATED ON DRAWINGS DO NOT USE SHIELDED WIRE ON ADDRESSABLE CIRCUIT JPK PAYNE TDT (ARCH D) 1/16" = 1' XXXX XXXX UN I V E R S I T Y O P E R A T I O N S F I R E A L A R M U P G R A D E BR I G H A M Y O U N G U N I V E R S I T Y - I D A H O FI R E A L A R M R I S E R D I A G R A M / M A T R I X RE X B U R G , I D A H O FI R E A L A R M S Y S T E M FIRE RISER DIAGRAM / MATRIX FA-R-01 NELSON FIRE SYSTEMS DRAWN BY: DESIGNED BY: APPROVED BY: DATE: SCALE: PROJECT NO: REVISION NO: DRAWING NAME: NO T E : NF S D R A W I N G S A R E B A S E D O N T H E P R O J E C T AR C H I T E C T U R E / E N G I N E E R ( A / E ) P L A N S A N D SP E C I F I C A T I O N S F U R N I S H E D T O N F S . A / E I S S O L E L Y RE S P O N S I B L E ( N O T N F S ) F O R T H E T Y P E , S I Z E , LO C A T I O N , A N D S U I T A B I L I T Y O F A L L F I R E A L A R M S , CO N T R O L P A N E L S , A N D O T H E R D E V I C E S S H O W N O N TH E A / E P L A N S . N F S D R A W I N G S A R E T O S H O W O N L Y TH E W I R I N G D I A G R A M S B E T W E E N F I R E A L A R M DE V I C E S A N D C O N T R O L P A N E L S . N F S I S N O T RE S P O N S I B L E F O R T H E I N F O R M A T I O N S H O W N O N T H E A/ E P L A N S . NELSON FIRE SYSTEMS PAGE: BYU-I UO FA UPGRADE R.DWG 2/8/2024 1:45:27 PM WIRING NOTES: - THREE AND A HALF TWISTS PER FOOT MINIMUM - DO NOT USE SHIELDED WIRE ON ADDRESSABLE CIRCUITS 1 FOOT S SMOKE DETECTOR T HEAT DETECTOR F PULL STATION TS TAMPER SWITCH MONITOR WF WATERFLOW SWITCH MONITOR SS SPEAKER/STROBE- WALL SS SPEAKER/STROBE- CEILINGC S SPEAKER ONLY- CEILINGC DEVICE LEGEND DESCRIPTIONSYMBOL LOWER LEVEL GROUND LEVEL EXISTING BATTERY CABINET FACU EXISTING T T SFFSFF SS C SS C SS CSSCSSCSSCSCSCSCSCSSCSSC SS C SS C S C SS C SS CSSC SS C SS C SS C SS C SS C S C S CSSCSSC SS C SS C SS C 1/2W1/2W SP1-1 1/2W1/2W SP1-2 1/2W SP1-3 1/2W SP1-4 1/4W1/4W SP1-5SP1-7 SP1-6 1/4W SP1-8 1/2W1/2W SP1-9 1/2W SP1-10SP1-11SP1-12 1 PAIR #14'S TWISTED SHIELDED SPEAKER CIRCUIT L1-1 15cd L1-2 15cd L1-3 15cd L1-4 30cd L1-5 95cd L1-6 95cd L1-7 30cd L1-8 30cd L1-9 15cd 1/2W SP1-24 1/4W SP1-23 1/4W SP1-22 1/4W SP1-14 SP1-21 1/2W SP1-20 1/2W SP1-19 1/4W SP1-18 1/2W SP1-17 1/2W SP1-16 1/2W SP1-15 1/2W 15cd 1/2W SP1-13 L2-8 15cd30cd L2-7 15cd L2-6 15cd L2-5L2-4 15cd L2-3 15cd L2-2L2-1 15cd L1-11 75cd L1-10 75cd (2) STROBE CIRCUITS 4 #14'S 1/4W SP1-25 1/4W SP1-26 1/2W SP1-27 L2-9 75cd 1/2W SP1-28 L2-10 75cd 1/2W SP1-29 L2-11 75cd 1/2W SP1-30 L2-12 95cd E.O.L. 3.9K E.O.L. 4.7K 3.9K 1 PAIR #14'S TWISTED ADDRESSABLE CIRCUIT MMMM WFTS 4 #14'S4 #14'S TRANSPONDER EXISTING ST 1/2W 1/2W 1/2W SP2-6 1/2W SP2-1 1/2W SP2-2 1/2W SP2-3 1/2W SP2-4 1/2W SP2-5 SP2-7 SP2-8 1/2W SP2-9 SP2-12SP2-10 1/2W 1/2W SP2-11 1/2W 1 PAIR #14'S TWISTED SHIELDED L3-1 SPEAKER CIRCUIT15cd L3-2 15cd L3-3 15cd L3-4 15cd L3-5 15cd L3-6 15cd L3-7 15cd L3-8 15cd L3-9 15cd L3-10 15cd L3-11 30cd L3-12 75cd 1/2W SP2-15 1/2W SP2-14 1/2W SP2-13 30cd L3-15L3-14 75cd L3-13 75cd 2 #14'S STROBE CIRCUITS SS C SS C SS C SS C SS C SS C SS C SS C SS C SS C SS C SS C SS C SS C SS C 1 PAIR #14'S TWISTED ADDRESSABLE CIRCUIT E.O.L. 4.7K 3.9K T T T T T T T F FTTSTTTT SP3-4 1/2W 1/2W SP3-1 1/2W SP3-2 1/2W SP3-3 1/2W SP3-11 1/2W SP3-5SP3-6 1/2W SP3-7 1/2W SP3-8SP3-9 1/2W1/2W SP3-10 1/2W1/2W SP3-12 1 PAIR #14'S TWISTED SHIELDED SPEAKER CIRCUIT L4-1 15cd L4-2 15cd L4-3 30cd L4-4 30cd L4-5 15cd L4-6 30cd L4-7 30cd L4-8 30cd L4-9 30cd L4-10 30cd L4-11 30cd 1/2W SP3-17 1/2W SP3-16 1/2W SP3-15 1/2W SP3-14 1/2W SP3-13 L4-15 30cd 30cd L4-16 30cd 30cd L4-14 30cd L4-13 L4-12 STROBE CIRCUITS 2 #14'S SS CSSCSSCSSCSSCSSCSSCSSCSSCSSCSSCSSCSSCSC SS CSSCSSC E.O.L. 4.7K 3.9K 1/2W1/2W SP4-1 1/4W 1/4W SP4-2 1/2W SP4-3 1/2W SP4-4SP4-5 1/2W SP4-6SP4-7 1/4W1/2W SP4-8 1/4W1/4W SP4-9SP4-10 1/4W SP4-11SP4-12 1 PAIR #14'S TWISTED SHIELDED SPEAKER CIRCUIT L5-1 15cd L5-2 15cd L5-3 75cd L5-4 30cd L5-5 30cd L5-6 15cd 1/4W SP4-20 1/4W SP4-19 1/2W SP4-18 1/2W SP4-17 1/2W SP4-16 1/4W SP4-15 1/2W SP4-14 1/2W SP4-13 L5-11 30cd L5-10 75cd L5-9 30cd L5-8 30cd L5-7 75cd 2 #14'S STROBE CIRCUITS SS CSSCSSCSSCSSCSSCSSCSSCSSCSSCSSCSCSCSCSCSCSCSCSCSC 1 PAIR #14'S TWISTED ADDRESSABLE CIRCUIT FFFFFFF E.O.L. 3.9K E.O.L. 4.7K T S F 1/2W SP5-6 SP5-7 SP5-8SP5-1 1/4W SP5-2 1/4W SP5-3 1/2W SP5-4 1/4W SP5-5 1/4W 1/2W 1/4W SP5-12 1/2W SP5-9 1/2W SP5-10 1/4W SP5-11 1/4W 1 PAIR #14'S TWISTED SHIELDED SPEAKER CIRCUIT L6-1 30cd L6-2 30cd L6-3 15cd L6-4 15cd L6-5 15cd 2 #14'S STROBE CIRCUITS 1/2W SP5-24 1/2W SP5-23 1/2W SP5-22 1/4W SP5-21 1/4W SP5-20 1/4W SP5-19 L6-9 1/2W SP5-18 1/2W SP5-17 1/4W SP5-16 1/4W SP5-15 1/4W SP5-14 1/4W SP5-13 L6-10 15cd15cd L6-8 15cd L6-7 15cd L6-6 30cd SS C SS C SS C SS C SS C SS C SS C SS CSCSCSCSCSCSCSCSCSCSCSCSCSCSCSSCSSC E.O.L. 4.7K 3.9K 1 PAIR #14'S TWISTED ADDRESSABLE CIRCUITTTTTTSSTTTT TTTTTSFSTTTTTST T FS 1/2W SP6-1 1/2W SP6-8 1/2W SP6-2 1/2W SP6-3 1/2W SP6-4 1/2W SP6-5 1/2W SP6-6 1/2W SP6-7 1/4W1/2W SP6-10 SP6-9SP6-11 1/2W1/2W SP6-12 SPEAKER CIRCUIT 1 PAIR #14'S TWISTED SHIELDED L7-1 75cd L7-2 75cd L7-3 30cd L7-4 15cd L7-5 75cd L7-6 95cd L7-7 30cd L7-8 75cd L7-9 75cd L7-10 75cd L7-11 30cd 1/4W SP6-16 1/4W SP6-15 1/4W SP6-14 1/4W SP6-13 L7-13 15cd L7-12 30cd 2 #14'S STROBE CIRCUITS SS CSSCSSCSSCSSCSSCSSCSSCSSCSSCSSCSCSCSC E.O.L. 3.9K E.O.L. 4.7K SS C SS C 1 PAIR #14'S TWISTED ADDRESSABLE CIRCUIT TTTTTTTTTF S F T T T F T T TT F T SHOP UNIVERSITY OPERATIONS T FF SS C SS CSC E.O.L. 4.7K 3.9K SP8-2 SP8-3 1/2W SP8-1 1/4W 1/2W SPEAKER CIRCUIT 1 PAIR #14'S TWISTED SHIELDED L9-1 75cd L9-1 75cd STROBE CIRCUITS 2 #14'S 1 PAIR #14'S TWISTED ADDRESSABLE CIRCUITTTT F SS CSS SP7-3 SP7-5 SP7-6 1/2W SP7-1 1/2W SP7-2 1/4W 1/4W SP7-4 1/2W 1/2W 1 PAIR #14'S TWISTED SHIELDED SPEAKER CIRCUIT L8-1 30cd L8-2 30cd L8-3 15cd L8-4 15cd L8-5 75cd L8-6 75cd 2 #14'S STROBE CIRCUITS SS C SS C SS C SS C E.O.L. 4.7K 3.9K 1 PAIR #14'S TWISTED ADDRESSABLE CIRCUITTTTTTF SHOP BUILDING UNIVERSITY OPERATIONS UNIVERSITY OPERATIONS SHOP BUILDING GREEN HOUSE/SIGN SHOP GROUNDS SHOP PLUMBING/WELDING BUILDING INITIATING DEVICES LOSS OF POWER ANY PANEL OR NAC LOW BATTERY CONDITIONS OPEN CIRCUIT CONDITIONS GROUND FAULTS AL A R M S I G N A L T O F I R E A L A R M D I S P L A Y TR O U B L E S I G N A L T O F I R E A L A R M D I S P L A Y BU I L D I N G S P E A K E R / S T R O B E S HV A C S H U T - D O W N FI R E / S M O K E D A M P E R S RE L E A S E M A G N E T I C D O O R H O L D E R S AL A R M S I G N A L T O M O N I T O R I N G C O M P A N Y TR O U B L E S I G N A L T O M O N I T O R I N G C O M P A N Y FACP ANNUNCIATION NOTIFICATION FIRE SAFETY CONTROL REPORTING SYSTEM INPUTS SYSTEM OUTPUTSFIRE ALARM INPUT/OUTPUT MATRIX IN (-) (+) AD D R E S S A B L E C K T AMM-4F NO NC COM FIELD DEVICE [AMM-4F] MONITOR MODULE CLASS 'A' CKT (+) (-) OUT (+) (-) [MS-7AF] MANUAL PULL STATION ADDRESSABLE CKT 1 2 3 4 FIRE PUSH IN PULL DOWN IN (+) (-)TO NEXT DEVICEOUT(+) (-)FIRE 80" FLOOR LINE 96" 48" 60" MOUNTING HEIGHTS PULL STATION TOP AT 48" WALL NOTIFICATION DEVICE MAXIMUM 96" TO TOP MINIMUM 80" TO BOTTOM FACU TOP AT 72" REMOTE ANNUNCIATOR TOP AT 60" 72" [B300-6] ADDRESSABLE DETECTOR BASE 3 2(+) 1(-) (+) (-) FR O M T R A N P A N E L (+) (-) AD D R E S S A B L E C K T OR P R E V I O U S D E V I C E TO N E X T D E V I C E [SPCWL] CEILING SPEAKER ONLY TO NEXT DEVICESPEAKER CKT OUTIN DRAIN WIRE (MUST NOT BE GROUNDED) [SPSWL] WALL SPEAKER STROBE TO NEXT DEVICESPEAKER CKT OUTIN TO NEXT DEVICE(+) (-)STROBE CIRCUIT IN OUT(+) (-) DRAIN WIRE (MUST NOT BE GROUNDED) [SPSCWL] CEILING SPEAKER STROBE TO NEXT DEVICESPEAKER CKT OUTIN TO NEXT DEVICE(+) (-)STROBE CIRCUIT IN OUT(+) (-) DRAIN WIRE (MUST NOT BE GROUNDED) UP UP DN UP S S T T T T T T T T T T T T T T T S WF TS F F F S S T F F F F 198 REPAIR UNIVERSITY OPERATIONS SHOP BUILDING FA C U 1 A 1 A 1 A 1 A JPK PAYNE TDT (ARCH D) 1/16" = 1' XXXX XXXX UN I V E R S I T Y O P E R A T I O N S F I R E A L A R M U P G R A D E BR I G H A M Y O U N G U N I V E R S I T Y - I D A H O RE X B U R G , I D A H O FI R E A L A R M S Y S T E M LOWER LEVEL ADDRESSABLE FA-L-01 25'10'50' NELSON FIRE SYSTEMS 801-468-8300 DRAWN BY: DESIGNED BY: APPROVED BY: DATE: SCALE: PROJECT NO: REVISION NO: DRAWING NAME: NO T E : NF S D R A W I N G S A R E B A S E D O N T H E P R O J E C T AR C H I T E C T U R E / E N G I N E E R ( A / E ) P L A N S A N D SP E C I F I C A T I O N S F U R N I S H E D T O N F S . A / E I S S O L E L Y RE S P O N S I B L E ( N O T N F S ) F O R T H E T Y P E , S I Z E , LO C A T I O N , A N D S U I T A B I L I T Y O F A L L F I R E A L A R M S , CO N T R O L P A N E L S , A N D O T H E R D E V I C E S S H O W N O N TH E A / E P L A N S . N F S D R A W I N G S A R E T O S H O W O N L Y TH E W I R I N G D I A G R A M S B E T W E E N F I R E A L A R M DE V I C E S A N D C O N T R O L P A N E L S . N F S I S N O T RE S P O N S I B L E F O R T H E I N F O R M A T I O N S H O W N O N T H E A/ E P L A N S . NELSON FIRE SYSTEMS PAGE: W E S N 2/19/2024 9:22:42 AM BYU-I UO FA UPGRADE L.DWG 1.INSTALLATION SHALL COMPLY WITH NEC, NFPA 72 AND OTHER APPLICABLE CODES AS REQUIRED BY THE LOCAL AHJ. CLASS "B" WIRING IS REQUIRED. 2.WIRING DEPICTED ON THESE PLAN IS SCHEMATIC - ACTUAL WIRE LOCATIONS MAY DIFFER FROM THESE PLANS. WIRING SHALL BE PERFORMED AS ACTUAL BUILDING CONSTRUCTION CONDITION ALLOW AND TO MINIMIZE PENETRATIONS THROUGH AREA SEPARATION WALLS AND FIRE WALLS. THE USE OF A RACEWAY IS PERMITTED AS LONG AS NO 110V OR HIGHER CABLES ARE IN THE RACEWAY. 3.POWER-LIMITED (PL) AND NONPOWER-LIMITED (NPL) CKT WIRING MUST REMAIN SEPARATED IN CABINET. ALL PL CKT WIRING MUST REMAIN AT LEAST 0.25" AWAY FROM ANY NPL CKT. FURTHERMORE, ALL PL AND NPL CKT WIRING MUST ENTER AND EXIT THE CABINET THROUGH A DIFFERENT KNOCKOUT AND/OR SEPARATE CONDUIT. 4.ONLY FIRE ALARM WIRING IS PERMITTED IN FIRE ALARM CONDUIT. DO NOT USE 110V OR HIGHER IN FIRE ALARM CONDUIT. 5.SMOKE DETECTORS SHALL BE INSTALLED AND COVERED UNTIL TESTING AND FINAL INSPECTION ARE COMPLETED. DO NOT INSTALL SMOKE DETECTORS UNTIL BUILDING IS CLEAN. 6.LOCATE SMOKE DETECTORS A MINIMUM OF THREE (3) FEET FROM MECHANICAL DIFFUSERS. 7.DO NOT USE SHIELDED WIRE ON ADDRESSABLE CKTS. 8.A SMOKE DETECTOR MUST BE IN EVERY ROOM WITH A FIRE ALARM CONTROL UNIT OR POWER SUPPLY. 9.FIRE ALARM CKTS NEED TO BE FREE OF GROUNDS, FAULTS, AND SHORTS PRIOR TO CONNECTION TO FIRE ALARM EQUIPMENT. 10.DEDICATED 120 VAC CKTS SHALL BE MARKED AS "FIRE ALARM CKT" AND BE ACCESSIBLE ONLY TO PERSONNEL. DISCONNECTS FOR THESE CKTS WILL BE RED IN COLOR AND THEIR LOCATION WILL BE NOTED AT EACH CONTROL UNIT. GENERAL NOTES: WIRE SCHEDULE NOTE DESCRIPTION WIRES A ADDRESSABLE CIRCUIT 1 PAIR #14'S TWISTED S L SPEAKER CIRCUIT 1 PAIR #14'S TWISTED/SHIELDED STROBE CIRCUIT 2 #14'S WIRING NOTE DESCRIPTION A =2 TOTAL CONDUCTORS (2)A =4 TOTAL CONDUCTORS A,(2)B =6 TOTAL CONDUCTORS SYSTEM NOTES: 1 TO TRANSPONDER LOCATED IN ELEC 106D 129 WORK 127 OFFICE 110 STORAGE 1-A FOYER 120 OFFICE 120A OFFICE 130 REPAIR 140 ELECTRONICS 152 MECH 157 CONFERENCE 155 CONFERENCE 155A TELCOM 141 WOMENS 143 MENS 145 AUTO REPAIR 145A OFFICE 145B OFFICE 145C PARTS 1-J HALL 149 LOBBY 144 WOMEN 135 MEN 142 CUST 138 MEN 136 OFFICE 151 SHOP 1-F HALL 1-H STAIR 106A LAUNDRY 139 LUNCH 106B OFFICE 106C STORAGE 106 STORAGE 106D OFFICE 106C TELCOM 106D ELEC 103 VAULT 1-E HALL 1-D STAIR 102 MECH S SMOKE DETECTOR T HEAT DETECTOR F PULL STATION TS TAMPER SWITCH MONITOR WF WATERFLOW SWITCH MONITOR SS SPEAKER/STROBE- WALL FACU FIRE ALARM CONTROL UNIT- EXISTING 13 64 25 1 1 SS SPEAKER/STROBE- CEILINGC S SPEAKER ONLY- CEILINGC DEVICE LEGEND DESCRIPTIONCOUNTSSYMBOL LOWER LEVEL SPRINKLERED NOT SPRINKLERED UP UP DN UP SS C SS C SS C SS C SS C SS C S C S C S C S C SS C SS C SS C SS C S C SS C SS C SS C SS C SS C SS C SS C SS C SS C SS C SS C SS C SS C SS C SS C SS C SS C SS C SS C SS C SS C SS C SS C S C S C SS C SS C SS C SS C SS C 198 REPAIR UNIVERSITY OPERATIONS SHOP BUILDING SP1-1 1/2W L1-1 15cd SP1-2 1/2W L1-2 15cd SP1-3 1/2W L1-3 15cd SP1-4 1/2W L1-4 30cd SP1-5 1/4W SP1-6 1/2W L1-5 95cd SP1-7 1/2W L1-6 95cd SP1-8 1/4W SP1-9 1/2W L1-7 30cd SP1-10 1/2W L1-8 30cd SP1-11 1/2W L1-9 15cd SP1-12 1/4WSP1-13 1/2W L1-10 75cd SP1-14 1/2W L1-11 75cd SP1-15 1/2W L2-1 15cd SP1-16 1/2W L2-2 30cd SP1-17 1/2W L2-3 15cdSP1-19 1/2W L2-5 15cd SP1-20 1/2W L2-6 15cd SP1-21 1/4W L2-7 15cd SP1-22 1/4W SP1-23 1/4W SP1-24 1/2W L2-8 15cd SP1-25 1/4W SP1-26 1/4W SP1-27 1/2W L2-9 75cd SP1-28 1/2W L2-10 75cd SP1-29 1/2W L2-11 75cd SP1-30 1/2W L2-12 95cd SP1-18 1/4W L2-4 15cd E.O.L. 4.7K 3.9K E.O.L. 3.9K 1 S,(2)L FA C U SP2-1 1/2W L3-1 15cd SP2-2 1/2W L3-2 15cd SP2-3 1/2W L3-3 15cd SP2-4 1/2W L3-4 15cd SP2-5 1/2W L3-5 15cd SP2-6 1/2W L3-6 15cd SP2-7 1/2W L3-7 15cd SP2-8 1/2W L3-8 15cd SP2-9 1/2W L3-9 15cd SP2-10 1/2W L3-10 30cd SP2-11 1/2W L3-11 75cd SP2-12 1/2W L3-12 75cd SP2-13 1/2W L3-13 75cd SP2-14 1/2W L3-14 15cd SP2-15 1/2W L3-15 30cd E.O.L. 4.7K 3.9K 1 S,L JPK PAYNE TDT (ARCH D) 1/16" = 1' XXXX XXXX UN I V E R S I T Y O P E R A T I O N S F I R E A L A R M U P G R A D E BR I G H A M Y O U N G U N I V E R S I T Y - I D A H O RE X B U R G , I D A H O FI R E A L A R M S Y S T E M LOWER LEVEL NOTIFICATION FA-L-02 25'10'50' NELSON FIRE SYSTEMS 801-468-8300 DRAWN BY: DESIGNED BY: APPROVED BY: DATE: SCALE: PROJECT NO: REVISION NO: DRAWING NAME: NO T E : NF S D R A W I N G S A R E B A S E D O N T H E P R O J E C T AR C H I T E C T U R E / E N G I N E E R ( A / E ) P L A N S A N D SP E C I F I C A T I O N S F U R N I S H E D T O N F S . A / E I S S O L E L Y RE S P O N S I B L E ( N O T N F S ) F O R T H E T Y P E , S I Z E , LO C A T I O N , A N D S U I T A B I L I T Y O F A L L F I R E A L A R M S , CO N T R O L P A N E L S , A N D O T H E R D E V I C E S S H O W N O N TH E A / E P L A N S . N F S D R A W I N G S A R E T O S H O W O N L Y TH E W I R I N G D I A G R A M S B E T W E E N F I R E A L A R M DE V I C E S A N D C O N T R O L P A N E L S . N F S I S N O T RE S P O N S I B L E F O R T H E I N F O R M A T I O N S H O W N O N T H E A/ E P L A N S . NELSON FIRE SYSTEMS PAGE: W E S N 2/19/2024 9:22:42 AM BYU-I UO FA UPGRADE L.DWG 1.INSTALLATION SHALL COMPLY WITH NEC, NFPA 72 AND OTHER APPLICABLE CODES AS REQUIRED BY THE LOCAL AHJ. CLASS "B" WIRING IS REQUIRED. 2.WIRING DEPICTED ON THESE PLAN IS SCHEMATIC - ACTUAL WIRE LOCATIONS MAY DIFFER FROM THESE PLANS. WIRING SHALL BE PERFORMED AS ACTUAL BUILDING CONSTRUCTION CONDITION ALLOW AND TO MINIMIZE PENETRATIONS THROUGH AREA SEPARATION WALLS AND FIRE WALLS. THE USE OF A RACEWAY IS PERMITTED AS LONG AS NO 110V OR HIGHER CABLES ARE IN THE RACEWAY. 3.POWER-LIMITED (PL) AND NONPOWER-LIMITED (NPL) CKT WIRING MUST REMAIN SEPARATED IN CABINET. ALL PL CKT WIRING MUST REMAIN AT LEAST 0.25" AWAY FROM ANY NPL CKT. FURTHERMORE, ALL PL AND NPL CKT WIRING MUST ENTER AND EXIT THE CABINET THROUGH A DIFFERENT KNOCKOUT AND/OR SEPARATE CONDUIT. 4.ONLY FIRE ALARM WIRING IS PERMITTED IN FIRE ALARM CONDUIT. DO NOT USE 110V OR HIGHER IN FIRE ALARM CONDUIT. 5.SMOKE DETECTORS SHALL BE INSTALLED AND COVERED UNTIL TESTING AND FINAL INSPECTION ARE COMPLETED. DO NOT INSTALL SMOKE DETECTORS UNTIL BUILDING IS CLEAN. 6.LOCATE SMOKE DETECTORS A MINIMUM OF THREE (3) FEET FROM MECHANICAL DIFFUSERS. 7.DO NOT USE SHIELDED WIRE ON ADDRESSABLE CKTS. 8.A SMOKE DETECTOR MUST BE IN EVERY ROOM WITH A FIRE ALARM CONTROL UNIT OR POWER SUPPLY. 9.FIRE ALARM CKTS NEED TO BE FREE OF GROUNDS, FAULTS, AND SHORTS PRIOR TO CONNECTION TO FIRE ALARM EQUIPMENT. 10.DEDICATED 120 VAC CKTS SHALL BE MARKED AS "FIRE ALARM CKT" AND BE ACCESSIBLE ONLY TO PERSONNEL. DISCONNECTS FOR THESE CKTS WILL BE RED IN COLOR AND THEIR LOCATION WILL BE NOTED AT EACH CONTROL UNIT. GENERAL NOTES: WIRE SCHEDULE NOTE DESCRIPTION WIRES A ADDRESSABLE CIRCUIT 1 PAIR #14'S TWISTED S L SPEAKER CIRCUIT 1 PAIR #14'S TWISTED/SHIELDED STROBE CIRCUIT 2 #14'S WIRING NOTE DESCRIPTION A =2 TOTAL CONDUCTORS (2)A =4 TOTAL CONDUCTORS A,(2)B =6 TOTAL CONDUCTORS SYSTEM NOTES: 1 TO TRANSPONDER LOCATED IN ELEC 106D 129 WORK 127 OFFICE 110 STORAGE 1-A FOYER 120 OFFICE 120A OFFICE 130 REPAIR 140 ELECTRONICS 152 MECH 157 CONFERENCE 155 CONFERENCE 155A TELCOM 141 WOMENS 143 MENS 145 AUTO REPAIR 145A OFFICE 145B OFFICE 145C PARTS 1-J HALL 149 LOBBY 144 WOMEN 135 MEN 142 CUST 138 MEN 136 OFFICE 151 SHOP 1-F HALL 1-H STAIR 106A LAUNDRY 139 LUNCH 106B OFFICE 106C STORAGE 106 STORAGE 106D OFFICE 106C TELCOM 106D ELEC 103 VAULT 1-E HALL 1-D STAIR 102 MECH S SMOKE DETECTOR T HEAT DETECTOR F PULL STATION TS TAMPER SWITCH MONITOR WF WATERFLOW SWITCH MONITOR SS SPEAKER/STROBE- WALL FACU FIRE ALARM CONTROL UNIT- EXISTING 1 SS SPEAKER/STROBE- CEILING95C S SPEAKER ONLY- CEILING35C DEVICE LEGEND DESCRIPTIONCOUNTSSYMBOL LOWER LEVEL SPRINKLERED NOT SPRINKLERED DN DN DN UP UP UP DN UP DN UP LOADING DOCK T T T T T T T T T T T T T T T T T T T T T T T T T T T F S S T S S T T T T T T T T T T T T T T T T F F F F F F F F F F F F T T T T F FF S S F F F FF S S GROUND LEVEL UNIVERSITY OPERATIONS SHOP BUILDING 1 A 1 A 1 A 1 A 1 A 1 A 1 A 1 A 1 A 1 A 229 OFFICE JPK PAYNE TDT (ARCH D) 1/16" = 1' XXXX XXXX UN I V E R S I T Y O P E R A T I O N S F I R E A L A R M U P G R A D E BR I G H A M Y O U N G U N I V E R S I T Y - I D A H O RE X B U R G , I D A H O FI R E A L A R M S Y S T E M GROUND LEVEL ADDRESSABLE FA-G-01 25'10'50' NELSON FIRE SYSTEMS 801-468-8300 DRAWN BY: DESIGNED BY: APPROVED BY: DATE: SCALE: PROJECT NO: REVISION NO: DRAWING NAME: NO T E : NF S D R A W I N G S A R E B A S E D O N T H E P R O J E C T AR C H I T E C T U R E / E N G I N E E R ( A / E ) P L A N S A N D SP E C I F I C A T I O N S F U R N I S H E D T O N F S . A / E I S S O L E L Y RE S P O N S I B L E ( N O T N F S ) F O R T H E T Y P E , S I Z E , LO C A T I O N , A N D S U I T A B I L I T Y O F A L L F I R E A L A R M S , CO N T R O L P A N E L S , A N D O T H E R D E V I C E S S H O W N O N TH E A / E P L A N S . N F S D R A W I N G S A R E T O S H O W O N L Y TH E W I R I N G D I A G R A M S B E T W E E N F I R E A L A R M DE V I C E S A N D C O N T R O L P A N E L S . N F S I S N O T RE S P O N S I B L E F O R T H E I N F O R M A T I O N S H O W N O N T H E A/ E P L A N S . NELSON FIRE SYSTEMS PAGE: W E S N 2/19/2024 9:22:36 AM BYU-I UO FA UPGRADE G.DWG 285 OFFICE 2-F VEST 283 OFFICE 283D OFFICE 283C STORAGE 283B OFFICE 283A OFFICE 249B OFFICE 249A OFFICE 249 OFFICE 249C OFFICE 2-C VEST 2-A HALL 226 OFFICE 224 OFFICE 213B OFFICEOFFICE OFFICE 258 CUST 266 MENS 252 WOMENS 284 OFFICE 272 OFFICE 100 EQUIPMENT STORAGE/SHOP 100A STORAGE 120 ROOM MTG/BREAK 120B ROOM CHANGING 120A ROOM CHANGING 100 WELDING SHOP 130 OFFICE 150 STORAGE 140 PLUMBING SHOP/STORAGE ROOFED EXTERIOR STORAGE 291D BREAK ROOM 291B OFFICE 291A OFFICE 291 ELECTRICAL SHOP 120C STORAGE TOOL 275A OFFICE 291E STORAGE 291F STORAGE 275 CAMPUS MAINTENANCE SHOP 275B ROOM BREAK MAINTENANCE 265A OFFICE 265B OFFICE 265C OFFICE 265D OFFICE 265E OFFICE 265 CUSTODIAL FOYER 255 PAINT SHOP 255D PAINT BOOTH 255A PAINT BOOTH 265E OFFICE/STORAGE 228C STORAGE TOOL 228 STRUCTURAL SHOP 228A STORAGE 211 UPHOLSTERY SHOP 211B UPHOLSTERY SHOP 209 OFFICE 120C SHOP OFFICE/ 209A OFFICE 205 TOO CRIB 190 PLASTIC GREENHOUSE 180 PLASTIC GREENHOUSE 172 HEAD HOUSE 120 PLASTIC GREENHOUSE 160 FLORAL PREP RM 160C STORAGE 160B COOLER 160A OFFICE 150 STORAGE 150A STORAGE 176 GREENHOUSE PLASTIC 178 STORAGE POT 130 SPRINKLER SHOP 120 SIGN SHOP 120A OFFICE SIGN SHOP 100A SUPERVISOR GROUNDS 104 RR 102 RR 106 FURNACE 1.INSTALLATION SHALL COMPLY WITH NEC, NFPA 72 AND OTHER APPLICABLE CODES AS REQUIRED BY THE LOCAL AHJ. CLASS "B" WIRING IS REQUIRED. 2.WIRING DEPICTED ON THESE PLAN IS SCHEMATIC - ACTUAL WIRE LOCATIONS MAY DIFFER FROM THESE PLANS. WIRING SHALL BE PERFORMED AS ACTUAL BUILDING CONSTRUCTION CONDITION ALLOW AND TO MINIMIZE PENETRATIONS THROUGH AREA SEPARATION WALLS AND FIRE WALLS. THE USE OF A RACEWAY IS PERMITTED AS LONG AS NO 110V OR HIGHER CABLES ARE IN THE RACEWAY. 3.POWER-LIMITED (PL) AND NONPOWER-LIMITED (NPL) CKT WIRING MUST REMAIN SEPARATED IN CABINET. ALL PL CKT WIRING MUST REMAIN AT LEAST 0.25" AWAY FROM ANY NPL CKT. FURTHERMORE, ALL PL AND NPL CKT WIRING MUST ENTER AND EXIT THE CABINET THROUGH A DIFFERENT KNOCKOUT AND/OR SEPARATE CONDUIT. 4.ONLY FIRE ALARM WIRING IS PERMITTED IN FIRE ALARM CONDUIT. DO NOT USE 110V OR HIGHER IN FIRE ALARM CONDUIT. 5.SMOKE DETECTORS SHALL BE INSTALLED AND COVERED UNTIL TESTING AND FINAL INSPECTION ARE COMPLETED. DO NOT INSTALL SMOKE DETECTORS UNTIL BUILDING IS CLEAN. 6.LOCATE SMOKE DETECTORS A MINIMUM OF THREE (3) FEET FROM MECHANICAL DIFFUSERS. 7.DO NOT USE SHIELDED WIRE ON ADDRESSABLE CKTS. 8.A SMOKE DETECTOR MUST BE IN EVERY ROOM WITH A FIRE ALARM CONTROL UNIT OR POWER SUPPLY. 9.FIRE ALARM CKTS NEED TO BE FREE OF GROUNDS, FAULTS, AND SHORTS PRIOR TO CONNECTION TO FIRE ALARM EQUIPMENT. 10.DEDICATED 120 VAC CKTS SHALL BE MARKED AS "FIRE ALARM CKT" AND BE ACCESSIBLE ONLY TO PERSONNEL. DISCONNECTS FOR THESE CKTS WILL BE RED IN COLOR AND THEIR LOCATION WILL BE NOTED AT EACH CONTROL UNIT. GENERAL NOTES: WIRE SCHEDULE NOTE DESCRIPTION WIRES A ADDRESSABLE CIRCUIT 1 PAIR #14'S TWISTED S L SPEAKER CIRCUIT 1 PAIR #14'S TWISTED/SHIELDED STROBE CIRCUIT 2 #14'S WIRING NOTE DESCRIPTION A =2 TOTAL CONDUCTORS (2)A =4 TOTAL CONDUCTORS A,(2)B =6 TOTAL CONDUCTORS SYSTEM NOTES: 1 TO TRANSPONDER LOCATED IN ELEC 106D S SMOKE DETECTOR T HEAT DETECTOR F PULL STATION TS TAMPER SWITCH MONITOR WF WATERFLOW SWITCH MONITOR SS SPEAKER/STROBE- WALL FACU FIRE ALARM CONTROL UNIT- EXISTING 13 64 25 1 1 SS SPEAKER/STROBE- CEILINGC S SPEAKER ONLY- CEILINGC DEVICE LEGEND DESCRIPTIONCOUNTSSYMBOL NOT SPRINKLERED SPRINKLERED GREENHOUSE/SIGN SHOP NOT SPRINKLERED GROUNDS SHOP NOT SPRINKLERED PLUMBING/WELDING NOT SPRINKLERED DN DN DN UP UP UP DN UP DN UP LOADING DOCK SS C S C S C S C S C S C S C S C S C SS C SS C SS C SS C S C S C S C S C S C S C SS C SS C SS C SS C SS C SS C SS C SS C SS SS C SS C SS C SS C S C SS C SS C SS C SS C SS C SS C SS C SS C SS C S C S C S C SS C SS C SS C SS C SS C SS C SS C SS C SS C SS C SS C S C S C S C S C S C S C SS C S C S C S CSSC SS C SS C SS C SS C SS C SS C SS C SS C SS C SS C SS C SS C SS C S C SS C SS C SS C SS CSSC GROUND LEVEL UNIVERSITY OPERATIONS SHOP BUILDING 1 S,L SP3-1 1/2W L4-1 15cd SP3-2 1/2W L4-2 15cdSP3-3 1/2W L4-3 30cd SP3-4 1/2W L4-4 30cd SP3-5 1/4W SP3-6 1/2W L4-5 30cd SP3-7 1/2W L4-6 15cdSP3-8 1/2W L4-7 30cd SP3-9 1/2W L4-8 30cd SP3-10 1/2W L4-9 30cd SP3-11 1/2W L4-10 30cd SP3-12 1/2W L4-11 30cd SP3-14 1/2W L4-13 30cd SP3-15 1/2W L4-14 30cd SP3-16 1/2W L4-15 30cd SP3-17 1/2W L4-16 30cd SP3-13 1/2W L4-12 30cd SP4-1 1/2W L5-1 15cd SP4-2 1/4W SP4-3 1/2W L5-2 15cd SP4-4 1/2W L5-3 75cd SP4-5 1/2W L5-4 30cd SP4-6 1/2W L5-5 30cd SP4-7 1/4W SP4-8 1/4W SP4-9 1/4W SP4-10 1/4W SP4-11 1/4W SP4-12 1/4W L5-6 15cd SP4-13 1/2W L5-7 75cd SP4-14 1/2W L5-8 30cd SP4-15 1/4W SP4-16 1/2W L5-9 30cd SP4-17 1/2W L5-10 75cd SP4-18 1/2W L5-11 30cd SP4-19 1/4W SP4-20 1/4W E.O.L. 4.7K 1 S,L 1 S,L SP5-1 1/2W L6-1 30cd SP5-2 1/4W SP5-3 1/4W SP5-4 1/2W L6-2 30cd SP5-5 1/4W SP5-6 1/4W SP5-7 1/2W L6-3 15cd SP5-8 1/4W SP5-9 1/2W L6-4 15cd SP5-10 1/2W L6-5 15cd SP5-11 1/4W SP5-12 1/4W SP5-13 1/4W SP5-14 1/4W SP5-15 1/4W SP5-16 1/4W SP5-17 1/2W L6-6 30cd SP5-18 1/2W L6-7 15cd SP5-19 1/4W SP5-20 1/4W SP5-21 1/4W SP5-22 1/2W L6-8 15cd SP5-23 1/2W L6-9 15cd SP5-24 1/2W L6-10 15cd E.O.L. 4.7K 3.9K E.O.L. 4.7K 3.9K 1 S,L SP6-1 1/2W L7-1 75cd SP6-2 1/2W L7-2 75cd SP6-3 1/2W L7-3 30cd SP6-4 1/2W L7-4 15cd SP6-5 1/2W L7-5 75cd SP6-6 1/2W L7-6 95cd SP6-7 1/2W L7-7 30cd SP6-8 1/4W SP6-9 1/2W L7-8 75cd SP6-10 1/2W L7-9 75cd SP6-11 1/2W L7-10 75cd SP6-12 1/2W L7-11 30cd SP6-13 1/2W SP6-14 1/4W L7-12 30cd SP6-15 1/4W L7-13 15cd SP6-16 1/4W 1 S,L SP7-1 1/2W L8-1 30cd SP7-2 1/2W L8-2 30cd SP7-4 1/4W L8-4 15cd SP7-5 1/2W L8-5 75cd SP7-6 1/2W L8-6 75cd SP7-3 1/4W L8-3 15cd SP8-1 1/2W L9-1 75cd 1 S,L SP8-2 1/4W SP8-3 1/2W L9-2 75cd E.O.L. 4.7K E.O.L. 4.7K 3.9K E.O.L. 4.7K 3.9K E.O.L. 3.9K 229 OFFICE JPK PAYNE TDT (ARCH D) 1/16" = 1' XXXX XXXX UN I V E R S I T Y O P E R A T I O N S F I R E A L A R M U P G R A D E BR I G H A M Y O U N G U N I V E R S I T Y - I D A H O RE X B U R G , I D A H O FI R E A L A R M S Y S T E M GROUND LEVEL NOTIFICATION FA-G-02 25'10'50' NELSON FIRE SYSTEMS 801-468-8300 DRAWN BY: DESIGNED BY: APPROVED BY: DATE: SCALE: PROJECT NO: REVISION NO: DRAWING NAME: NO T E : NF S D R A W I N G S A R E B A S E D O N T H E P R O J E C T AR C H I T E C T U R E / E N G I N E E R ( A / E ) P L A N S A N D SP E C I F I C A T I O N S F U R N I S H E D T O N F S . A / E I S S O L E L Y RE S P O N S I B L E ( N O T N F S ) F O R T H E T Y P E , S I Z E , LO C A T I O N , A N D S U I T A B I L I T Y O F A L L F I R E A L A R M S , CO N T R O L P A N E L S , A N D O T H E R D E V I C E S S H O W N O N TH E A / E P L A N S . N F S D R A W I N G S A R E T O S H O W O N L Y TH E W I R I N G D I A G R A M S B E T W E E N F I R E A L A R M DE V I C E S A N D C O N T R O L P A N E L S . N F S I S N O T RE S P O N S I B L E F O R T H E I N F O R M A T I O N S H O W N O N T H E A/ E P L A N S . NELSON FIRE SYSTEMS PAGE: W E S N 2/19/2024 9:22:36 AM BYU-I UO FA UPGRADE G.DWG 285 OFFICE 2-F VEST 283 OFFICE 283D OFFICE 283C STORAGE 283B OFFICE 283A OFFICE 249B OFFICE 249A OFFICE 249 OFFICE 249C OFFICE 2-C VEST 2-A HALL 226 OFFICE 224 OFFICE 213B OFFICEOFFICE OFFICE 258 CUST 266 MENS 252 WOMENS 284 OFFICE 272 OFFICE 100 EQUIPMENT STORAGE/SHOP 100A STORAGE 120 ROOM MTG/BREAK 120B ROOM CHANGING 120A ROOM CHANGING 100 WELDING SHOP 130 OFFICE 150 STORAGE 140 PLUMBING SHOP/STORAGE ROOFED EXTERIOR STORAGE 291D BREAK ROOM 291B OFFICE 291A OFFICE 291 ELECTRICAL SHOP 120C STORAGE TOOL 275A OFFICE 291E STORAGE 291F STORAGE 275 CAMPUS MAINTENANCE SHOP 275B ROOM BREAK MAINTENANCE 265A OFFICE 265B OFFICE 265C OFFICE 265D OFFICE 265E OFFICE 265 CUSTODIAL FOYER 255 PAINT SHOP 255D PAINT BOOTH 255A PAINT BOOTH 265E OFFICE/STORAGE 228C STORAGE TOOL 228 STRUCTURAL SHOP 228A STORAGE 211 UPHOLSTERY SHOP 211B UPHOLSTERY SHOP 209 OFFICE 120C SHOP OFFICE/ 209A OFFICE 205 TOO CRIB 190 PLASTIC GREENHOUSE 180 PLASTIC GREENHOUSE 172 HEAD HOUSE 120 PLASTIC GREENHOUSE 160 FLORAL PREP RM 160C STORAGE 160B COOLER 160A OFFICE 150 STORAGE 150A STORAGE 176 GREENHOUSE PLASTIC 178 STORAGE POT 130 SPRINKLER SHOP 120 SIGN SHOP 120A OFFICE SIGN SHOP 100A SUPERVISOR GROUNDS 104 RR 102 RR 106 FURNACE 1.INSTALLATION SHALL COMPLY WITH NEC, NFPA 72 AND OTHER APPLICABLE CODES AS REQUIRED BY THE LOCAL AHJ. CLASS "B" WIRING IS REQUIRED. 2.WIRING DEPICTED ON THESE PLAN IS SCHEMATIC - ACTUAL WIRE LOCATIONS MAY DIFFER FROM THESE PLANS. WIRING SHALL BE PERFORMED AS ACTUAL BUILDING CONSTRUCTION CONDITION ALLOW AND TO MINIMIZE PENETRATIONS THROUGH AREA SEPARATION WALLS AND FIRE WALLS. THE USE OF A RACEWAY IS PERMITTED AS LONG AS NO 110V OR HIGHER CABLES ARE IN THE RACEWAY. 3.POWER-LIMITED (PL) AND NONPOWER-LIMITED (NPL) CKT WIRING MUST REMAIN SEPARATED IN CABINET. ALL PL CKT WIRING MUST REMAIN AT LEAST 0.25" AWAY FROM ANY NPL CKT. FURTHERMORE, ALL PL AND NPL CKT WIRING MUST ENTER AND EXIT THE CABINET THROUGH A DIFFERENT KNOCKOUT AND/OR SEPARATE CONDUIT. 4.ONLY FIRE ALARM WIRING IS PERMITTED IN FIRE ALARM CONDUIT. DO NOT USE 110V OR HIGHER IN FIRE ALARM CONDUIT. 5.SMOKE DETECTORS SHALL BE INSTALLED AND COVERED UNTIL TESTING AND FINAL INSPECTION ARE COMPLETED. DO NOT INSTALL SMOKE DETECTORS UNTIL BUILDING IS CLEAN. 6.LOCATE SMOKE DETECTORS A MINIMUM OF THREE (3) FEET FROM MECHANICAL DIFFUSERS. 7.DO NOT USE SHIELDED WIRE ON ADDRESSABLE CKTS. 8.A SMOKE DETECTOR MUST BE IN EVERY ROOM WITH A FIRE ALARM CONTROL UNIT OR POWER SUPPLY. 9.FIRE ALARM CKTS NEED TO BE FREE OF GROUNDS, FAULTS, AND SHORTS PRIOR TO CONNECTION TO FIRE ALARM EQUIPMENT. 10.DEDICATED 120 VAC CKTS SHALL BE MARKED AS "FIRE ALARM CKT" AND BE ACCESSIBLE ONLY TO PERSONNEL. DISCONNECTS FOR THESE CKTS WILL BE RED IN COLOR AND THEIR LOCATION WILL BE NOTED AT EACH CONTROL UNIT. GENERAL NOTES: WIRE SCHEDULE NOTE DESCRIPTION WIRES A ADDRESSABLE CIRCUIT 1 PAIR #14'S TWISTED S L SPEAKER CIRCUIT 1 PAIR #14'S TWISTED/SHIELDED STROBE CIRCUIT 2 #14'S WIRING NOTE DESCRIPTION A =2 TOTAL CONDUCTORS (2)A =4 TOTAL CONDUCTORS A,(2)B =6 TOTAL CONDUCTORS SYSTEM NOTES: 1 TO TRANSPONDER LOCATED IN ELEC 106D S SMOKE DETECTOR T HEAT DETECTOR F PULL STATION TS TAMPER SWITCH MONITOR WF WATERFLOW SWITCH MONITOR SS SPEAKER/STROBE- WALL FACU FIRE ALARM CONTROL UNIT- EXISTING 1 SS SPEAKER/STROBE- CEILING95C S SPEAKER ONLY- CEILING35C DEVICE LEGEND DESCRIPTIONCOUNTSSYMBOL E.O.L. 3.9K NOT SPRINKLERED SPRINKLERED GREENHOUSE/SIGN SHOP NOT SPRINKLERED GROUNDS SHOP NOT SPRINKLERED PLUMBING/WELDING NOT SPRINKLERED