Loading...
HomeMy WebLinkAboutFS PLANS - 22-00818 - BYUI McKay - Library RemodelTHIS AUTOMATIC SPRINKLER SYSTEM IS SIZED BASED ON HYDRAULIC CALCULATIONS IN ACCORDANCE WITH THE REQUIREMENTS OF NFPA 13 2019 EDITION DENSITY AREA METHOD. FIRE SPRINKLER SYSTEM IN AREA OF WORK IS DESIGNED TO , LIGHT HAZARD OCCUPANCIES. PERMISSIBLE DECREASES AND REQUIRED INCREASES FROM NFPA 13 HAVE BEEN APPLIED TO DESIGN AREA . WATER SUPPLY DATA: STATIC PRESSURE: 99 RESIDUAL PRESSURE: 120 FLOW: 1850 DATE: 12/15/2021 SOURCE: 3-D FIRE PROTECTION SYSTEM DESIGN NOTES 1. SYSTEM DESIGN, INSTALLATION AND TESTING SHALL BE IN ACCORDANCE WITH NFPA 13 (2019 EDITION) AND LOCAL FIRE AUTHORITY. 2. ALL MATERIAL AND DEVICES TO BE U.L. LISTED AND/OR F.M. APPROVED FOR FIRE SPRINKLER USE. 3. ALL 1" SYSTEM PIPING SHALL BE SCHEDULE 40 BLACK PIPE WITH THREADED CI FITTINGS. 4. ALL SYSTEM PIPING 1¼" AND LARGER SHALL BE SCHEDULE 40 BLACK PIPE WITH GROOVED FITTINGS & GROOVED RIGID COUPLINGS. 5. PIPE SHALL BE MANUFACTURED TO MEET ASTM A135 STANDARDS. CRR VALUE = 1.0 OR GREATER 6. ALL HANGERS SHALL BE DESIGNED, SPACED AND INSTALLED AS PER NFPA-13, 2019 EDITION, CHAPTER-18. MAX LENGTH OF UNSUPPORTED ARMOVERS SHALL BE 24" (PRESSURE LESS THAN 100 PSI). 7. SPRINKLERS LOCATED IN ACOUSTICAL GRID CEILINGS SHALL BE INSTALLED CENTER OF TILE OR QUARTER POINTS. 8. ALL ALARM SYSTEM WIRING AND INSTALLATION IS BY OTHERS. 24 HOUR SUPERVISION TO BE PROVIDED BY OTHERS. 9. PAINTING, WIRING, FIRE EXTINGUISHERS, HYDRANTS, THRUST BLOCKING, CITY WATER CONNECTION, EXCAVATION, BACKFILLING AND SYSTEM MONITORING SHALL BE PROVIDED BY OTHERS. 10. FLUSHING AND TESTING OF UNDERGROUND PIPING SHALL BE COMPLETED BY THE INSTALLING CONTRACTOR BEFORE CONNECTION TO THE FIRE SPRINKLER SYSTEM. 11. ALL PENETRATIONS THROUGH FIRE RATED ASSEMBLIES SHALL BE FIRE STOPPED. FIRE STOPPING MATERIAL SHALL BE INSTALLED PER MANUFACTURERS INSTRUCTION BY OTHERS. 12. HYDRAULIC PLACARD SHALL BE POSTED ON RISER. 13. BUILDING OWNER SHALL BE RESPONSIBLE FOR ADEQUATE HEAT (40ºF AND ABOVE) IN ALL WET PIPE AREAS TO PREVENT SPRINKLER SYSTEM FROM FREEZING. BUILDING DETAILS SCOPE OF WORK GENERAL NOTES - BUILDING STRUCTURE AND CONSTRUCTION CONSISTS OF: -CONCRETE FOUNDATION/FLOOR -STEEL WALLS -SHEETROCK INTERIOR WALLS -STEEL BEAMS - TOTAL SQUARE FOOTAGE: SCOPE OF WORK: 10,000 FT² - BUILDING CODE CLASSIFICATION - OCCUPANCY - OFFICE/CLASSROOMS - CONSTRUCTION TYPE - STEEL, CONCRETE EXISTING RISER HYDRAULIC CALCULATIONS BYU-I McKAY LIBRARY BASEMENT: RELOCATE FIRE SPRINKLERS TO ACCOMMODATE A NEW CEILING LAYOUT. EXISTING FIRE SPRINKLER SYSTEM IS HYDRAULICALLY DESIGNED TO PROTECT A HAZARD CLASSIFICATION OF LIGHT HAZARD. NO CHANGES TO HAZARD CLASSIFICATION WILL OCCUR AS PART OF THIS TENANT IMPROVEMENT. EXISTING FIRE SPRINKLER RISERS, MAINS AND BRANCH LINES WILL BE DEMOLISHED AND RETURNED LIKE FOR LIKE OR UPSIZED AND WILL BE USED TO SUPPLY RELOCATED FIRE SPRINKLERS. EXISTING FIRE SYSTEM HAS ALREADY BEEN HYDRAULICALLY PROVEN TO PROTECT THE HAZARD CLASSIFICATION PRESENT. NEW CEILINGS WILL BE LOWER THAN ORIGINAL DESIGN THEREFORE THE REMOTE AREA WILL BE SMALLER AND HAVE A LOWER HYDRAULIC DEMAND. NO ADDITIONAL HYDRAULIC CALCULATIONS SHOULD BE REQUIRED. ADDITIONALLY VICTAULIC VS2 DROPS WILL BE USED WITH NO ADDITION HYDRAULIC LOSS. SYSTEM DESIGN SHALL BE IN ACCORDANCE WITH NFPA 13 2019 EDITION AND LOCAL AUTHORITY. DESIGNED BY: JASON BLATTER 208-881-5439 - OFFICE 3196 SPITFIRE ST IDAHO FALLS, ID AUTHORITY HAVING JURISDICTION: REXBURG FIRE MARSHAL 26 N. CENTER REXBURG, ID 83440 208-359-3010 GENERAL CONTRACTOR: BIG-D CONSTRUCTION Sprinkler Legend Symbol Manufacturer SIN Model Quantity K-Factor Type Size Response Finish Temperature Note Generic 49 5.6 Pendent ½Quick Chrome 155°F Total = 49 FP-01 Idaho Falls, ID 10/03/24PRINT DATE 3- D F i r e P r o t e c t i o n 1 2 3 4 DESCRIPTIONNO.DATE FOR APPROVAL10/03/24 REVISIONS OWNERSHIP OF DOCUMENTS ALL DRAWINGS, SPECIFICATIONS, AND OTHER WORK PRODUCT OF 3-D FOR THIS PROJECT ARE INSTRUMENTS OF SERVICE FOR THIS PROJECT ONLY AND SHALL REMAIN THE PROPERTY OF 3-D WHETHER THE PROJECT IS COMPLETED OR NOT. REUSE OF ANY OF THE INSTRUMENTS OF SERVICE, BY THE OWNER OREXTENSIONS OF THE PROJECT WITHOUT WRITTENPERMISSION OF 3-D SHALL BE AT THE OWNER'S RISK AND THE OWNER AGREES TO DEFEND, INDEMNIFY, AND HOLD HARMLESS 3-D FROM ALL CLAIMS, DAMAGES, AND EXPENSES INCLUDING ATTORNEYS' FEES ARISING OUT OF UNAUTHORIZED REUSE OF THE INSTRUMENTS OF SERVICE BY THE OWNER OR BY OTHERS ACTING THROUGH THE OWNER DRAWN BY 4C0189 Jason Blatter 3-D FIRE PROJECT NUMBER Jason.Blatter@3Dfire.us Tel. 208-881-5439 FREEZING CONDITIONS IN LOCATIONS SUBJECT TO FREEZING CONDITIONS, IT IS THE OWNERS RESPONSIBILITY TO PROVIDE HEAT ANDADEQUATE INSULATION THROUGHOUT WET PIPE SPRINKLERSYSTEM AREAS AND IN ENCLOSURES FOR DRY PIPE ANDOTHER TYPES OF VALVES CONTROLLING WATER SUPPLIES TO SPRINKLER SYSTEMS. I have reviewed these plans and certify that they comply with the adopted NFPA standards. NORTH 52 5 S . C E N T E R S T R E E T RE X B U R G , I D 8 3 4 6 0 BY U - I C A M P U S 3196 SPITFIRE ST 8142 SCALE 1/8" = 1'-0" 0 8142 SCALE 1/8" = 1'-0" 0 BY U - I M c K A Y L I B R A R Y B A S E M E N T AREA OF WORK 4" 8" DIAMETER 1.442 1" M I N MAX HANGER 2.067 NOMINAL 2" SCHEDULE 40 PIPE 11.78 lbs/ft KWIK BOLT ANCHOR PIPE ALL THREAD ROD SWIVEL RING CONCRETE DECK KWIK BOLT ANCHOR 5.89 lbs/ft 1¼" FLEXIBLE DROP TO SPRINKLER (IN.) SCHEDULE 10 PIPE 1" 15'-0 1/2" BALL VALVE 15'-0 6" STEEL PIPE DIMENSION TABLE 8.249 SUPPORTED HANGER SPACING - STEEL PIPE 4" 15'-0 1.610 1.049 BRANCHLINE CEILING 6.065 7.94 lbs/ft INSTALL SPRINKLER 1"-12" BELOW DECK POWDER DRIVEN STUD POWDER DRIVEN STUD PIPE ALL THREAD ROD SWIVEL RING CONCRETE DECK ROD COUPLING 4" (Sch 10) 2 1/2" (Sch 10) CONCEALED SPRINKLER UPRIGHT SPRINKLER INSIDENOMINAL WET SYSTEM AIR VENT BRANCHLINE UPRIGHT SPRINKLER 3.260 6.357 (IN.) 23.03 lbs/ft 2.93 lbs/ft SPACING FLEXIBLE DROP 1/2" X 0-3 NIPPLE 15'-0 12'-0 1½" 1.097 1.682 HILTI DROP IN ANCHOR HILTI HDI (DRILLED) PIPE ALL THREAD ROD SWIVEL RING CONCRETE DECK 2.469 DIAMETER 4.22 lbs/ft 2" 3.068 PIPE SIZE FILLED PIPE 1 1/2" (Sch 10) 1" (Sch 40) WELDED OUTLET 3"15'-0 15'-0 SIZE OF PIPE MOUNTING BRACKET 2.635 WEIGHT OF WATER 6" 6" (Sch 10) 1½" 4 WAY RISER BRACE DETAIL "FAST CLAMP" RISER PIPE CONCRETE WALL TOLCO FIG 1000 1" SCH.40 PIPE TOLCO FIG 980 KWIK BOLT ANCHOR (IN.) UPRIGHT SPRINKLER DETAIL 1" SCH.40 PIPE 2.157 INSIDE 3" (Sch 10) 2" (Sch 10) SPRINKLER CENTER OF TILE 1" X 1/2" ELBOW PIPE SIZE 3" 7.981 1.380 4.260 8" UPRIGHT SPRINKLER DETAIL CEILING 12'-0 1/2" X 0-3 NIPPLE HILTI HDI ANCHOR PIPE SWIVEL RING ALL THREAD ROD OFFSET EYELET BOLT & WASHER 2/ 3 HDI ANCHOR ( CONCRETE TWIN TEE ) HILTI KH-EZ ANCHOR ALL THREAD ROD CONCRETE DECK PIPE KH-EZ SCREW ANCHOR SWIVEL RING 1¼" 2½" 1/2" PLUG BRANCHLINE PIPING (IN.) 3.04 lbs/ft 1" 2½" 2.05 lbs/ft 4.026 1 1/4" (Sch 40) 12 " M A X 1/2" 90º ELBOW NOTE: 56" FLEXIBLE DROP LENGTH VS2 VICTAULIC MAX NUMBER OF 90 DEGREE BENDS = 4 MIN RADIUS = 2" (UL) EQUIVALENT LENGTH 0 NOTE: A SINGLE AIR VENT SHALL BE LOCATED NEAR A HIGH POINT IN THE SYSTEM. BASEMENT DEMOLITION PLAN SPRINKLER AND HANGING DETAIL NO SCALE IDAHO STATE FIRE MARSHAL'S OFFICE FIRE SPRINKLER PLAN REVIEW ACCEPTED 10/28/2024WITH COMMEN T S When a system modification affects more than 20 sprinklers, the new portion should be isolated and tested at not less than 200 psi for 2 hours. (NFPA 13, 29.7.1.1) No RED on drawings. Red is reserved for markups only. Sprinkler Legend Symbol Manufacturer SIN Model Quantity K-Factor Type Size Response Finish Temperature Note Note2 Victaulic V3204 VS2 48 5.6 Concealed Pendent 1 Quick Brass 155°F NO HYDRAULIC LOSS PER CUT SHEET Total = 48 FP-02 Idaho Falls, ID 10/03/24PRINT DATE 3- D F i r e P r o t e c t i o n 1 2 3 4 DESCRIPTIONNO.DATE FOR APPROVAL10/03/24 REVISIONS OWNERSHIP OF DOCUMENTS ALL DRAWINGS, SPECIFICATIONS, AND OTHER WORK PRODUCT OF 3-D FOR THIS PROJECT ARE INSTRUMENTS OF SERVICE FOR THIS PROJECT ONLY AND SHALL REMAIN THE PROPERTY OF 3-D WHETHER THE PROJECT IS COMPLETED OR NOT. REUSE OF ANY OF THE INSTRUMENTS OF SERVICE, BY THE OWNER OREXTENSIONS OF THE PROJECT WITHOUT WRITTENPERMISSION OF 3-D SHALL BE AT THE OWNER'S RISK AND THE OWNER AGREES TO DEFEND, INDEMNIFY, AND HOLD HARMLESS 3-D FROM ALL CLAIMS, DAMAGES, AND EXPENSES INCLUDING ATTORNEYS' FEES ARISING OUT OF UNAUTHORIZED REUSE OF THE INSTRUMENTS OF SERVICE BY THE OWNER OR BY OTHERS ACTING THROUGH THE OWNER DRAWN BY 4C0189 Jason Blatter 3-D FIRE PROJECT NUMBER Jason.Blatter@3Dfire.us Tel. 208-881-5439 FREEZING CONDITIONS IN LOCATIONS SUBJECT TO FREEZING CONDITIONS, IT IS THE OWNERS RESPONSIBILITY TO PROVIDE HEAT ANDADEQUATE INSULATION THROUGHOUT WET PIPE SPRINKLERSYSTEM AREAS AND IN ENCLOSURES FOR DRY PIPE ANDOTHER TYPES OF VALVES CONTROLLING WATER SUPPLIES TO SPRINKLER SYSTEMS. OTHERSUBMITTALAS-BUILT I have reviewed these plans and certify that they comply with the adopted NFPA standards. NORTH 52 5 S . C E N T E R S T R E E T RE X B U R G , I D 8 3 4 6 0 BY U - I C A M P U S BY U - I M c K A Y L I B R A R Y B A S E M E N T 3196 SPITFIRE ST 8142 SCALE 1/8" = 1'-0" 0 8142 SCALE 1/8" = 1'-0" 0 2½" WELDED OUTLET 1/2" BALL VALVE 2.93 lbs/ft 15'-0 1.610 6" (Sch 10) 1.09712'-0 2.469 3" (Sch 10) SPRINKLER SCHEDULE 10 PIPEFILLED PIPE PIPE SIZE UPRIGHT SPRINKLER (IN.) 1 1/4" (Sch 40) 4.260 SUPPORTED 4" 6" CEILING SCHEDULE 40 PIPE 11.78 lbs/ft FLEXIBLE DROP TO SPRINKLER 1" SCH.40 PIPE 1¼" 1/2" PLUG 2" 3.04 lbs/ft 15'-0 7.98115'-0 BRANCHLINE CEILING DIAMETER 15'-0 2.067 4" (Sch 10) 2.157 INSIDE BRANCHLINE PIPING WET SYSTEM AIR VENT (IN.) 1 1/2" (Sch 10) 3.2603" 4" 2.635 1/2" X 0-3 NIPPLE WEIGHT OF WATER 1½" 1¼" UPRIGHT SPRINKLER DETAIL UPRIGHT SPRINKLER 4.22 lbs/ft NOMINAL BRANCHLINE 4.026 SPACING FLEXIBLE DROP STEEL PIPE DIMENSION TABLE 15'-0 1.049 MAX HANGER 1.682 DIAMETER (IN.) 2" (Sch 10) CENTER OF TILE PIPE SIZE 1" 3" 12 " M A X 8.249 1/2" 90º ELBOW HANGER SPACING - STEEL PIPE UPRIGHT SPRINKLER DETAIL 8" 1½" INSTALL SPRINKLER 1"-12" BELOW DECK 1/2" X 0-3 NIPPLE 5.89 lbs/ft 2½" 3.068 1" X 1/2" ELBOW 2.05 lbs/ft 15'-0 1.380 SIZE OF PIPE MOUNTING BRACKET 1.442 12'-0 NOMINAL (IN.) 2 1/2" (Sch 10) CONCEALED SPRINKLER INSIDE 1" 1" (Sch 40) 6.357 23.03 lbs/ft 6" 8" 1" M I N 6.065 7.94 lbs/ft 2" HILTI HDI ANCHOR PIPE SWIVEL RING ALL THREAD ROD OFFSET EYELET BOLT & WASHER 2/ 3 HDI ANCHOR ( CONCRETE TWIN TEE ) HILTI DROP IN ANCHOR HILTI HDI (DRILLED) PIPE ALL THREAD ROD SWIVEL RING CONCRETE DECK KWIK BOLT ANCHOR PIPE ALL THREAD ROD SWIVEL RING CONCRETE DECK KWIK BOLT ANCHOR 4 WAY RISER BRACE DETAIL "FAST CLAMP" RISER PIPE CONCRETE WALL TOLCO FIG 1000 1" SCH.40 PIPE TOLCO FIG 980 KWIK BOLT ANCHOR POWDER DRIVEN STUD POWDER DRIVEN STUD PIPE ALL THREAD ROD SWIVEL RING CONCRETE DECK ROD COUPLING HILTI KH-EZ ANCHOR ALL THREAD ROD CONCRETE DECK PIPE KH-EZ SCREW ANCHOR SWIVEL RING NOTE: A SINGLE AIR VENT SHALL BE LOCATED NEAR A HIGH POINT IN THE SYSTEM. NOTE: 56" FLEXIBLE DROP LENGTH VS2 VICTAULIC MAX NUMBER OF 90 DEGREE BENDS = 4 MIN RADIUS = 2" (UL) EQUIVALENT LENGTH 0 BASEMENT REINSTALLATION PLAN SPRINKLER AND HANGING DETAIL NO SCALE IDAHO STATE FIRE MARSHAL'S OFFICE FIRE SPRINKLER PLAN REVIEW ACCEPTED 10/28/2024WITH COMMEN T S