HomeMy WebLinkAboutFS APPROVAL - 22-00818 - BYUI McKay - Library Remodel BYU-I McKay Library TI – Rexburg 1 of 1 STATE FIRE MARSHAL IDAHO DEPARTMENT OF INSURANCE 700 W. State Street, 3rd Floor P.O. Box 83720 Boise, ID 83720-0043 (208) 334-4370 | www.doi.idaho.gov/sfm PLAN REVIEW FOR FIRE SPRINKLER SYSTEMS PLANS RECEIVED: October 15 2024 APPROVED: October 28, 2024 REVIEWED BY: Rory Winch, Fire Plans Examiner PROJECT: BYU-I McKay Library TI STREET ADDRESS: 525 S Center Street CITY: Rexburg AHJ: Madison Fire Department SPRINKLER CONTRACTOR: 3-D Fire Protection 3196 N Spitfire St Idaho Falls, ID 83401 IDAHO LICENSE: FPSC-008 CONTACT NAME: Sam Page sam.page@3dfire.us PHONE NO: (208) 881-5431 SYSTEM DESIGNED BY: Jason Blatter jason.blatter@3dfire.us PHONE NO: (208) 881-5439 TYPE OF SYSTEM: NFPA 13 HEAD COUNT: 49 TOTAL SYSTEMS: 1 OCCUPANCY CLASSIFICATION: Light Harzard Offices and Classrooms CONSTRUCTION TYPE: Steel and Concrete AREA SQUARE FOOTAGE: 4500 SCOPE OF WORK: BYU-I McKAY LIBRARY BASEMENT: RELOCATE FIRE SPRINKLERS TO ACCOMMODATE A NEW CEILING LAYOUT. EXISTING FIRE SPRINKLER SYSTEM IS HYDRAULICALLY DESIGNED TO PROTECT A HAZARD CLASSIFICATION OF LIGHT HAZARD. NO CHANGES TO HAZARD CLASSIFICATION WILL OCCUR AS PART OF THIS TENANT IMPROVEMENT. EXISTING FIRE SPRINKLER RISERS, MAINS AND BRANCH LINES WILL BE DEMOLISHED AND RETURNED LIKE FOR LIKE OR UPSIZED AND WILL BE USED TO SUPPLY RELOCATED FIRE SPRINKLERS. EXISTING FIRE SYSTEM HAS ALREADY BEEN HYDRAULICALLY PROVEN TO PROTECT THE HAZARD CLASSIFICATION PRESENT. NEW CEILINGS WILL BE LOWER THAN ORIGINAL DESIGN THEREFORE THE REMOTE AREA WILL BE SMALLER AND HAVE A LOWER HYDRAULIC DEMAND. NO ADDITIONAL HYDRAULIC CALCULATIONS SHOULD BE REQUIRED. ADDITIONALLY VICTAULIC VS2 DROPS WILL BE USED WITH NO ADDITION HYDRAULIC LOSS. PLAN REVIEW COMMENTS: Accepted with comments 1. When a system modification affects more than 20 sprinklers, the new portion should be isolated and tested at not less than 200 psi for 2 hours. (NFPA 13, 29.7.1.1) 2. No RED on drawings. Red is reserved for markups only. Approval of shop drawings is not intended to imply waiver or modification of any requirements of the Idaho State Statutes or Rules, International Fire Code, NFPA Standards or any other applicable criteria. It is acknowledged that backflow preventer is installed per the demand of the local water purveyor. The State Fire Marshal’s Office and its personnel does not take any responsibility for the back flow device.