HomeMy WebLinkAboutFS APPROVAL - 22-00818 - BYUI McKay - Library Remodel BYU-I McKay Library TI – Rexburg 1 of 1
STATE FIRE MARSHAL
IDAHO DEPARTMENT OF INSURANCE
700 W. State Street, 3rd Floor
P.O. Box 83720
Boise, ID 83720-0043
(208) 334-4370 | www.doi.idaho.gov/sfm
PLAN REVIEW FOR FIRE SPRINKLER SYSTEMS
PLANS RECEIVED: October 15 2024 APPROVED: October 28, 2024
REVIEWED BY: Rory Winch, Fire Plans Examiner
PROJECT: BYU-I McKay Library TI
STREET ADDRESS: 525 S Center Street CITY: Rexburg
AHJ: Madison Fire Department
SPRINKLER CONTRACTOR: 3-D Fire Protection
3196 N Spitfire St
Idaho Falls, ID 83401
IDAHO LICENSE: FPSC-008
CONTACT NAME: Sam Page
sam.page@3dfire.us
PHONE NO: (208) 881-5431
SYSTEM DESIGNED BY: Jason Blatter
jason.blatter@3dfire.us
PHONE NO: (208) 881-5439
TYPE OF SYSTEM: NFPA 13 HEAD COUNT: 49
TOTAL SYSTEMS: 1 OCCUPANCY CLASSIFICATION: Light Harzard Offices and
Classrooms
CONSTRUCTION TYPE: Steel and Concrete AREA SQUARE
FOOTAGE: 4500
SCOPE OF WORK: BYU-I McKAY LIBRARY BASEMENT: RELOCATE FIRE SPRINKLERS TO ACCOMMODATE A
NEW CEILING LAYOUT. EXISTING FIRE SPRINKLER SYSTEM IS HYDRAULICALLY DESIGNED
TO PROTECT A HAZARD CLASSIFICATION OF LIGHT HAZARD. NO CHANGES TO HAZARD
CLASSIFICATION WILL OCCUR AS PART OF THIS TENANT IMPROVEMENT. EXISTING FIRE
SPRINKLER RISERS, MAINS AND BRANCH LINES WILL BE DEMOLISHED AND RETURNED
LIKE FOR LIKE OR UPSIZED AND WILL BE USED TO SUPPLY RELOCATED FIRE SPRINKLERS.
EXISTING FIRE SYSTEM HAS ALREADY BEEN HYDRAULICALLY PROVEN TO PROTECT THE
HAZARD CLASSIFICATION PRESENT. NEW CEILINGS WILL BE LOWER THAN ORIGINAL
DESIGN THEREFORE THE REMOTE AREA WILL BE SMALLER AND HAVE A LOWER
HYDRAULIC DEMAND. NO ADDITIONAL HYDRAULIC CALCULATIONS SHOULD BE
REQUIRED. ADDITIONALLY VICTAULIC VS2 DROPS WILL BE USED WITH NO ADDITION
HYDRAULIC LOSS.
PLAN REVIEW COMMENTS: Accepted with comments
1. When a system modification affects more than 20 sprinklers, the new portion should
be isolated and tested at not less than 200 psi for 2 hours. (NFPA 13, 29.7.1.1)
2. No RED on drawings. Red is reserved for markups only.
Approval of shop drawings is not intended to imply waiver or modification of any requirements of the Idaho State Statutes or
Rules, International Fire Code, NFPA Standards or any other applicable criteria.
It is acknowledged that backflow preventer is installed per the demand of the local water purveyor. The State Fire Marshal’s
Office and its personnel does not take any responsibility for the back flow device.