HomeMy WebLinkAboutAPPROVED PLANS - 22-00818 - BYUI McKay - Library RemodelAuthor Name Author Email Author Phone No.:
Cody Jones Cody.Jones@rexburg.org 208-372-2173
Don Allen Don.Allen@rexburg.org 208-372-2174
Alex Owens Alex.Owens@rexburg.org 208-372-2172
Description : BYUI McKay - Library Remodel
Address : 479 S Center St
Record Type : Commercial - Remodel
Document Filename : MCK Library Remodel Bid Set Drawings - 10.28.22.pdf
Comment Author Contact Information:
Corrections in the following table need to be applied before a permit can be issued
Review Report
Approved
# 22-00818
Page Reference Annotation
Type
Author : Department Status Page Review Comments Applicant Response Comments
G000 Stamp Cody Jones : Building Open 1 Approved - Building Inspector
S003 Free Text Cody Jones : Building Open 18 Special Inspector needs to be identified.
G000 Stamp Alex Owens : Electrical Open 1 Approved - Electrical Inspector
G000 Free Text Alex Owens : Electrical Open 1 All electrical work to comply with 2017 NEC
G000 Free Text Alex Owens : Electrical Open 1 Ensure all emergency egress lighting and exit signs comply
with NEC requirements as well as IBC1008 and 1013
EG000 Free Text Alex Owens : Electrical Open 200 All electrical work to comply with 2017 NEC
EE400 Free Text Alex Owens : Electrical Open 231 Ensure all grounding/bonding in affected areas still comply
with article 250 of NEC.
G000 Stamp Don Allen : Mechanical Open 1 Approved - Plumbing Inspector
G000 Stamp Don Allen : Mechanical Open 1 Approved - Mechanical Inspector
Commercial - Remodel
Approval of plans does not constitute approval of variance from code
Powered by TCPDF (www.tcpdf.org)
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
10/28/22
G000
Cover Sheet
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
MCK Library Remodel
Bid Set - 10/28/2022
owner
brigham young university -idaho
university operations 283b
rexburg, id 83460
(208) 496-2660
andy johnson
johnsona@byui.edu
architect
method studio
360 w aspen ave
salt lake city, ut 84101
(801) 532-4422
contact:
civil
horrocks engineers
2194 snake river parkway suite 205
idaho falls, id 83402
(208) 522-1223
clint boyle
general contractor
big-d construction
925 s utah ave
idaho falls, id 83402
(208) 538-3479
andrew wolford
andrew.wolford@big-d.com
structural
tbse inc
233 north 1250 west #201
centerville, ut 84014
(801) 298-8795
donald barfuss
mechanical
heath engineering company
377 west 800 north
salt lake city, ut 84103
(801) 322-0487
andrew pasket
electrical
payne engineering inc
1823 e center
pocatello, id 83201
(208) 232-4439
todd payne
MATERIAL LEGEND
EARTH (EXISTING)
EARTH (BACKFILL)
DRAINAGE FILL
COMPACTED FILL
CONCRETE
CAST-IN-PLACE
CONCRETE
PRECAST
BRICK
CONCRETE MASONRY
UNIT
GROUT
STEEL
ALUMINUM
CONTINUOUS WOOD
SHEATHING
INTERMITTENT WOOD
BLOCKING
WOOD FINISH
HARDBOARD
PARTICLE BOARD
BATT INSULATION
LOOSE FILL INSULATION
RIGID INSULATION
FIRE SPRAY
GYPSUM BOARD
ARCHITECTURE SYMBOLS
A102
SHEET TYPE
DISCIPLINE
SHEET NUMBER SEQUENCE
?
XX
E022A.2
F1
R1
S3x
WALL FUNCTION
CORE MATERIAL
CORE SIZE (ROUNDED)
MODIFIER
101M
AWS STANDARD CASEWORK TYPE
MODIFIED CASEWORK TYPE
REFER TO CASEWORK DESIGN SERIES (CDS) OF
THE ARCHITECTURAL WOODWORK STANDARDS
(AWS) FOR A FULL DESCRIPTION OF CASEWORK
TYPES
100' - 0"
MAIN LEVEL
LEVEL NAME
LEVEL ELEVATION
AE000
1 Ref
1
Re
f
1 Ref
1
Re
f
AE000
1 Ref
1
Re
f
1 Ref
1
Re
f
SHEET NUMBER
POSITION ON SHEET
SHEET NUMBER
POSITION ON SHEET
DRAWING NUMBER
VIEW NAME
DRAWING SCALE
ORIGINAL SOURCE OF DETAIL
SIMA1
A526.a
SIMA1
A526.a
POSITION ON SHEET
SHEET NUMBER
SHEET NUMBER
VIEW DIRECTION
POSITION ON SHEET
A1
AE101
SIM
A1
AE101
SIM
A1
AE101
SIM
VIEW DIRECTION
POSITION ON SHEET
SHEET NUMBER
ROOM NUMBER
ROOM AREA
01A
SIGN TYPE
SIGN NUMBER
VIEW DIRECTION
POSITION ON SHEET
SHEET NUMBER
1 DELTA MARKER
10' - 0"
HEIGHT OF ELEMENT
C1 10' - 0"
CEILING TYPE
CEILING HEIGHT
1 2
A
B
A1 STARTS AT UPPER LEFT CORNER;
NUMBERS ARE VERTICAL GRIDS AND
LETTERS ARE HORIZONTAL GRIDS
(EXCLUDES LETTERS "I" AND "O")
Room name
101
F
B
W
F
CP
T
-
0
1
?
ROOM NAME
ROOM NUMBER
WALL FINISH
BASE FINISH
FLOOR FINISH
WALL,BASE, OR FLOOR
MATERIAL FINISH CODE
ARROWS REPRESENT EXTENT OF SCOPE
REFER TO FINISH LEGEND
WC-01
00.00
ROOM NAME
101
150 SF
KEYNOTE TAG
CURTAIN WALL TAG
DOOR TAG
FLOOR TAG
ROOF TAG
WALL TAG
REVISION CLOUD
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
10/28/22
G001
Index,
General
Notes,
Location Map,
Legends
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
ABBREVIATION SCHEDULE
Abbrev.Description
0
# NUMBER OR POUND
& AND
2:1 SL 2 HORIZONTAL TO 1 VERTICAL SLOPE
@ AT
[ CHANNEL
± PLUS MINUS
≤ LESS THAN OR EQUAL TO
≥ GREATER THAN OR EQUAL TO
A
AB ANCHOR BOLT
AC APSHALTIC CONCRETE
ACST ACOUSTIC
AD AREA DRAIN
ADJ ADJUSTABLE
AFF ABOVE FINISH FLOOR
ALT ALTERNATE
ALUM ALUMINUM
ARCH ARCHITECTURAL, ARCHITECT, ARCHITECTURE
ASPH ASPHALT
B
B BASELINE
B BOTTOM
BEJ BRICK EXPANSION JOINT
BLDG BUILDING
BLK BLOCK
BM BEAM
BO BOARD
BRG BEARING
BSMT BASEMENT
C
C&G CURB & GUTTER
CAP CAPACITY
CEM CEMENT
CG CORNER GUARD
CIP CAST IN PLACE, CAST IRON PIPE
CIR CIRCULATING
CJ CONTROL JOINT
CL CENTERLINE
CL CENTERLINE
CLG CEILING
CLR CLEAR
CMU CONCRETE MASONRY UNITS
COL COLUMN
CONC CONCRETE
CONN CONNECTION
CONST CONSTRUCTION
CONT CONTINUOUS
CPT CARPET
CSK COUNTERSUNK
CT CERAMIC TILE
CTR CENTER
D
D DEPTH
DET DETAIL
DF DRINKING FOUNTAIN
DIA DIAMETER
DIM DIMENSION
DN DOWN
DS DOWNSPOUT
DWG DRAWING
E
E EAST
E/P EDGE OF PAVEMENT
EA EACH
EL ELEVATION
ELECT ELECTRICAL
ELEV ELEVATOR
EMER EMERGENCY
EQ EQUAL
EQUIP EQUIPMENT
EW EACH WAY
EWC ELECTRIC WATER COOLER
EXIST EXISTING
EXP EXPANSION
EXP JT EXPANSION JOINT
EXT EXTERIOR
F
F.V. FIELD VERIFY
FD FLOOR DRAIN
FDN FOUNDATION
FE FIRE EXTINGUISHER
FFE FINISHED FLOOR ELEVATION
FH FIRE HYDRANT
FHC FIRE HOSE CABINET
FIN FINISH
FLR FLOOR
FR FRAME
FTG FOOTING
FXTR FIXTURE
G
G GROUND
GA GA
GALV GALVANIZED
GL GLASS
GR GRADE
GRD GROUND
GWB GYPSUM WALL BOARD
H
HB HOSE BIBB
HC HANDICAPPED
HDW HARDWARE
HGT HEIGHT
HORZ HORIZONTAL
HR HOUR
HW HOT WATER
I
ID INSIDE DIAMETER
IE INVERT ELEVATION
INSUL INSULATION
INT INTERIOR
INTX INTERSECTION
INV INVERT
J
JB JUNCTION BOX
JCT JUNCTION
JST JOIST
JT JOINT
GENERAL NOTES - MISCELLANEOUS
1 THE PROJECT MANUAL, UNDER SEPARATE COVER, IS AN INTEGRAL PART OF THESE
CONSTRUCTION DRAWINGS.
2 PLANS, SECTIONS, ELEVATIONS, DETAILS AND DIMENSIONS LABELED "TYPICAL" SHALL APPLY
TO ALL SITUATION OCCURRING THAT ARE THE SAME OR SIMILAR TO THOSE SPECIFICALLY
KEYED ON THE DRAWINGS.
3 ALL WORK, MATERIALS, AND METHODS SHALL BE IN CONFORMANCE WITH THE CODES,
ORDINANCES AND REGULATIONS OF ALL GOVERNMENTAL AGENCIES HAVING JURISDICTION
AT THE PROJECT LOCATION.
4 UNLESS OTHERWISE INDICATED IN THE CONSTRUCTION DOCUMENTS AS BEING NOT IN
CONTRACT (N.I.C.) OR EXISTING, ALL ITEMS, MATERIALS AND INSTALLATION OF SAME ARE
PART OF THE CONTRACT AS DEFINED BY THE CONSTRUCTION DOCUMENTS. THE
CONTRACTOR SHALL PROVIDE AND INSTALL ALL ACCESSORIES, COMPONENTS AND
ASSEMBLIES REQUIRED FOR THE WORK DEPICTED OR SPECIFIED.
5 CONTRACTORS ARE RESPONSIBLE FOR ALL WORK REGARDLESS OF THE LOCATION OF THE
INFORMATION ON THE DOCUMENTS.
6 KEEP SITE CLEAN AND CLEAR OF DEBRIS AND IN ORDERLY CONDITION THAT DOES NOT
DETRACT FROM THE SURROUNDING SITE AND REPAIR ANY DAMAGE CAUSED BY WORK OF
THE CONTRACT.
7 ALL DIMENSIONS ARE TO THE FACE OF METAL OR WOOD STUD FRAMED WALLS AND TO THE
FACE OF CONCRETE AND MASONRY WALLS AS SHOWN, UNLESS NOTED OTHERWISE.
8 INSTALL SEALANT AT EXTERIOR SIDE OF ALL JOINTS, SEAMS, CONNECTIONS OR OPENINGS
WHICH WOULD ALLOW WATER OR AIR INFILTRATION EXCEPT AS NOTED OTHERWISE.
SEALANT COLOR TO MATCH ADJACENT SURFACE. COLOR REQUIRES ARCHITECTS APPROVAL.
9 DOOR OPENINGS IN FRAME CONSTRUCTION WHICH ARE NOT DIMENSIONED ARE EITHER
CENTERED IN THE WALL, FACE OF JAMB OR LOCATED 4" FROM THE FACE OF STUD TO THE
FINISHED JAMB.
10 ALL SPECIAL ACCESSIBLE FACILITIES SHALL BE IDENTIFIED WITH APPROVED SIGNAGE.
11 THE CONTRACTOR IS RESPONSIBLE FOR PRODUCING A WEATHER TIGHT BUILDING, DETAILS
AND OMISSIONS TO DRAWINGS NOTWITHSTANDING. ALL DRAWING CONFLICTS WHICH MAY
NOT ALLOW A WEATHERTIGHT CONDITION SHALL BE BROUGHT TO THE ATTENTION OF THE
ARCHITECT.
12 DISCREPANCIES BETWEEN ACTUAL CONDITIONS AND PLANS SHALL BE BROUGHT TO THE
ATTENTION OF THE ARCHITECT. CONTRACTOR SHALL SUBMIT SPECIFIC DISCREPANCIES FOR
ARCHITECT REVIEW.
13 PROVIDE FULL METAL BACKING PLATE (16 GAUGE X 6" HIGH SECURED TO 3 STUDS MIN.) OR
WOOD BLOCKING AS REQUIRED TO SECURELY ANCHOR ALL WALL MOUNTED EQUIPMENT
(CABINETS, TOILET ROOM ACCESSORIES, HARDWARE, ETC.). BLOCKING SHALL PROVIDE A
RIGID CONNECTION CAPABLE OF SUPPORTING DESIGN LOADS. PROVIDE A 16 GAUGE X 6" STL.
STUD/TRACK SECURED TO 2 STUDS TO SECURELY SUPPORT ALL WALL STOPS (DOOR
BUMPER).
14 COORDINATE WITH ALL TRADES, SIZES AND LOCATIONS OF ALL OPENINGS FOR MECHANICAL,
PLUMBING AND ELECTRICAL EQUIPMENT, EQUIPMENT PADS OR BASES, AS WELL AS ELECTRIC
POWER, WATER, AND DRAIN INSTALLATIONS, BEFORE PROCEEDING WITH WORK.
CONTRACTOR SHALL PROVIDE COORDINATION DRAWINGS FOR PROPER PLACEMENT OF ALL
TRADES' WORK. ANY CONCERNS, SPACE LIMITATIONS OR STRUCTURAL CONFLICTS, SHALL BE
BROUGHT TO THE ATTENTION OF THE ARCHITECT. A REASONABLE RESPONSE TIME SHALL BE
ALLOWED AS NOTED IN THE SPECIFICATIONS.
15 ALL FLOOR OR WALL OPENINGS REQUIRED FOR PIPES, DUCTS, CONDUITS,ETC. SHALL BE
SEALED IN AN APPROVED MANNER.
16 FIRE SPRINKLER DESIGN TO BE DONE BY A CERTIFIED SUB-CONTRACTOR AND WILL REQUIRE
APPROVALS BY THE CITY AND STATE FIRE MARSHAL. APPROVALS BY THE FIRE MARSHAL ARE
TO BE OBTAINED BY THE CONTRACTOR PRIOR TO SUBMITTAL TO ARCHITECT. SUBMITTAL TO
THE ARCHITECT ALSO INDICATES THAT THE CONTRACTOR HAS REVIEWED AND COORDINATED
FIRE-SPRINKLER PIPING LOCATIONS WITH ALL TRADES.
17 ROOMS ENCLOSED WITH RATED WALLS REQUIRE RATED DOORS. ANY DUCTS PASSING
THROUGH WALLS REQUIRE FIRE DAMPERS AND OR FIRE/SMOKE DAMPERS. ANY CONDUIT OR
PIPING REQUIRES RATED SEALANT AT JOINTS.
18 GENERAL STRUCTURAL NOTES GOVERN TYPICAL CONDITIONS WHETHER OR NOT
SPECIFICALLY DETAILED OR NOTED.
19 IT IS THE CONTRACTOR'S RESPONSIBILITY TO COORDINATE AND LOCATE ELECTRICAL, DATA
AND PHONE RECEPTACLES, SWITCHES, ETC. TO AVOID CASEWORK, DOORS, ETC.
20 THE DRAWINGS AND SPECIFICATIONS INDICATE THE GENERAL SCOPE OF THE PROJECT IN
TERMS OF THE ARCHITECTURAL AND STRUCTURAL DESIGN CONCEPT. THE DIMENSIONS OF
THE BUILDING, THE TYPE OF STRUCTURAL, MECHANICAL, ELECTRICAL AND UTILITY SYSTEMS
AND MAJOR ARCHITECTURAL ELEMENTS OF CONSTRUCTION AS "SCOPE" DOCUMENTS.
21 1.THE DRAWINGS AND SPECIFICATIONS DO NOT NECESSARILY INDICATE OR DESCRIBE ALL
WORK REQUIRED FOR THE FULL PERFORMANCE AND COMPLETION OF THE WORK.
CONTRACTS SHALL BE LET ON THE BASIS OF SUCH DOCUMENTS, WITH THE UNDERSTANDING
THAT THE CONTRACTOR IS TO FURNISH ALL ITEMS REQUIRED FOR PROPER COMPLETION OF
THE WORK WITH OUT ADJUSTMENT TO CONTRACT PRICE. IT IS INTENDED THAT THE WORK TO
BE OF SOUND AND QUALITY CONSTRUCTION AND THE CONTRACTOR SHALL BE SOLELY
RESPONSIBLE FOR THE INCLUSION OF ADEQUATE AMOUNTS TO COVER INSTALLATION OF ALL
ITEMS INDICATED, DESCRIBED OR REASONABLY IMPLIED.
22 CONTRACT DOCUMENTS NEED TO BE VIEWED IN COLOR TO CLARIFY DATA.
DRAWING INDEX
GENERAL
G000 Cover Sheet
G001 Index, General Notes, Location Map, Legends
G002 Code Analysis
G003 Code Analysis & Plans - Level 00
G004 Code Analysis & Plans - Level 01
G005 Code Analysis & Plans - Level 02
G006 Code Analysis & Plans - Level 03
G010 Phasing Plans
G011.1 ADA Guidelines
G011.2 ADA Guidelines Cont.
G011.3 Accessibility Details
G015 Code Required Signage & Details
CIVIL & LANDSCAPE
C.2.0 Existing Conditions & Demo.
C.3.0 Site Plan
L.1.0 Landscape Plan
STRUCTURAL
S001 GENERAL NOTES
S002 SCHEDULES
S003 INSPECTIONS
S004 INSPECTIONS
S101 LEVEL 1 FLOOR FRAMING
S102 LEVEL 2 FLOOR FRAMING
S103 LEVEL 3 FLOOR FRAMING
S401 PENETRATION 1ST FLOOR
S402 PENETRATION 2ND FLOOR
S403 PENETRATION 3RD FLOOR
S501 DETAILS
ARCHITECTURAL DEMOLITION
D100a Level 00 Area A Demolition Plan
D101a Level 01 Area A Demolition Plan
D101b Level 01 Area B Demolition Plan
D102a Level 02 Area A Demolition Plan
D102b Level 02 Area B Demolition Plan
D103a Level 03 Area A Demolition Plan
D130a Level 00 Area A Demolition RCP Plan
D131a Level 01 Area A Demolition RCP Plan
D131b Level 01 Area B Demolition RCP Plan
D132a Level 02 Area A Demolition RCP Plan
D132b Level 02 Area B Demolition RCP Plan
D133a Level 03 Area A Demolition RCP Plan
ARCHITECTURAL
A100a Level 00 Area A Floor Plan
A100b Level 00 Area B Floor Plan
A101 Level 01 Overall Floor Plan
A101a Level 01 Area A Floor Plan
A101b Level 01 Area B Floor Plan
A102 Level 02 Overall Floor Plan
A102a Level 02 Area A Floor Plan
A102b Level 02 Area B Floor Plan
A103a Level 03 Area A Floor Plan
A111 Level 01 Area A Slab Plan
A112 Level 01 Area B Slab Plan
A120a Level 00 Area A Wall Type & Dimension Plan
A121a Level 01 Area A Wall Type & Dimension Plan
A121b Level 01 Area B Wall Type & Dimension Plan
A122a Level 02 Area A Wall Type & Dimension Plan
A122b Level 02 Area B Wall Type & Dimension Plan
A123a Level 03 Area A Wall Type & Dimension Plan
A130a Level 00 Area A Reflected Ceiling Plan
A131a Level 01 Area A Reflected Ceiling Plan
A131b Level 01 Area B Reflected Ceiling Plan
A132a Level 02 Area A Reflected Ceiling Plan
A132b Level 02 Area B Reflected Ceiling Plan
A133a Level 03 Area A Reflected Ceiling Plan
A141 Level 00 Area A Finish Plan
A142 Level 01 Area A Finish Plan
A143 Level 01 Area B Finish Plan
A144 Level 02 Area A Finish Plan
A145 Level 02 Area B Finish Plan
A146 Level 03 Area A Finish Plan
A147 Enlarged Finish Plans
A201 Exterior Elevations
A301 Building Sections
A311 Wall Sections
A411 Enlarged Plans & Interior Elevations
A412 Enlarged Plans & Interior Elevations
A413 Enlarged Plans & Interior Elevations
A414 Enlarged Plans & Interior Elevations
A415 Enlarged Plans & Interior Elevations
A416 Interior Elevations
A417 Interior Elevations
A418 Interior Elevations
A419 Interior Elevations
A420 Interior Elevations
A421 Interior Elevations
A422 Interior Elevations
A431 High Density Shelving Equipment Plan
A440 Interior Renderings
A501 Wall & Soffit Assemblies
A503 Structural Steel Framing Details
A511 Plan Details
A512 Details
A513 Entrance Details
A514 Ceiling Details
A515 Ceiling Details
A516 Enlarged RCP Details
A541 Door Details
A551 Exterior Glazing Details
A561 Interior Glazing Details
A571 Interior Details
A572 Interior Details
A581 Casework Details
A582 Casework Details
A601 Door Schedule
A602 Door Types
A604 Window Types & Glazing Schedule
A605 Window Types & Glazing Schedule
A611 Finish Schedules, Accessory Schedules
A710 Signage Schedule and Details
A800 Level 00 Area A Furniture Plan
A801 Level 01 Area A Furniture Plan
A802 Level 01 Area B Furniture Plan
A803 Level 02 Area A Furniture Plan
A804 Level 02 Area B Furniture Plan
A805 Level 03 Area A Furniture Plan
ABBREVIATION SCHEDULE
Abbrev.Description
L
L ANGLE
L LENGTH
LC LENGTH OF CURVE
LDC LEAD COVERED
LL LIVE LOAD
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
LT LIGHT
M
MAS MASONRY
MATL MATERIAL
MAX MAXIMUM
MECH MECHANICAL
MET METAL
MFR MANUFACTURER
MH MANHOLE
MIN MINIMUM
MISC MISCELLANEOUS
MO MASONRY OPENING
MTD MOUNTED
MTG MOUNTING
MULL MULLION
MWP MEMBRANE WATERPROOFING
N
N NORTH
NA NOT APPLICABLE
NE NORTHEAST
NEC NATIONAL ELECTRIC CODE
NEUT NEUTRAL
NIC NOT IN CONTRACT
NO NUMBER
NOM NOMINAL
NTS NOT TO SCALE
NW NIORTHWEST
O
OA OUTSIDE AIR
OA OUTSIDE AIR
OC ON CENTER
OFCI OWNER FURNISHED, CONTRACTOR INSTALLED
OFOI OWNER FURNISHED, OWNER INSTALLED
OPP OPPOSITE
OVHD OVERHEAD
P
PI POINT IF INTERSECTION
PL PLATE
PLAS PLASTER
PLYWD PLYWOOD
PNL PANEL
PNT PAINT
PRELIM PRELIMINARY
PRESS PRESSURE
PRIM PRIMARY
PRTN PARTITION
PT POINT, POINT OF TANGENT
Q
QT QUARRY TILE
R
R RADIUS
RA RETURN AIR
RB RESILIENT VINYL BASE
RCP REINFORCED CONCRETE PIPE
RD ROOF DRAIN
RECP RECEPTACLE
REINF REINFORCEMENT
REQD REQUIRED
REV REVISION
RF ROOF
RFLCP REFLECTIVE CEILING PLAN
RM ROOM
RVT RESILIENT VINYL TILE
S
S SOUTH
SCH SCHEDULE
SD STORM DRAIN
SE SOUTHEAST
SECT SECTION
SHT SHEET
SIM SIMILIAR
SL SLOPE
SPEC SPECIFICATION
SQ SQUARE
STL STEEL
SUSP SUSPENDED
T
T TOP
T&B TOP AND BOTTOM
TEL TELEPHONE
TEMP TEMPORARY
TERM TERMINAL
THK THICK/THICKNESS
THRSLD THRESHOLD
TO TOP OF
TOS TOP OF STEEL, TOP OF SLAB
TOW TOP OF WALL
TYP TYPICAL
U
UNO UNLESS NOTED OTHERWISE
V
VCT VINYL COMPOSITION TILE
VENT VENTILIATING
VERT VERTICAL
VEST VESTIBULE
VWC VINYL WALL COVERING
W
W WIDTH, WEST
W/ WITH
W/O WITHOUT
WC WATER CLOSET
WD WIDTH
WT WEIGHT
WWF WELDED WIRE FABRIC
X
X TRANSFORMER
DRAWING INDEX
MECHANICAL
M-001 Mechanical Schedules and Symbol Legend
M-002 Mechanical Schedules
M-003 Mechanical Schedules
M-004 Mechanical Schedules
MD100a Level 00 Area A Mechanical Demolition Plan
MD101a Level 01 Area A Mechanical Demolition Plan
MD101b Level 01 Area B Mechanical Demolition Plan
MD102a Level 02 Area A Mechanical Demolition Plan
MD102b Level 02 Area B Mechanical Demolition Plan
MD103a Level 03 Area A Mechanical Demolition Plan
MD104a Roof Area A Mechanical Demolition Plan
MD104b Roof Area B Mechanical Demolition Plan
MD110a Level 00 Area A Mechanical Piping Demolition Plan
MD110b Level 00 Area B Mechanical Piping Demolition Plan
MD111a Level 01 Area A Mechanical Piping Demolition Plan
MD111b Level 01 Area B Mechanical Piping Demolition Plan
MD112a Level 02 Area A Mechanical Piping Demolition Plan
MD112b Level 02 Area B Mechanical Piping Demolition Plan
MD113a Level 03 Area A Mechanical Piping Demolition Plan
MD401 Enlarged Level 00 Area A Mechanical Room Demolition Plan
MD402 Enlarged Level 01 Area B Mechanical Room Demolition Plan
MH100a Level 00 Area A Mechanical Remodel Plan
MH101a Level 01 Area A Mechanical Remodel Plan
MH101b Level 01 Area B Mechanical Remodel Plan
MH102a Level 02 Area A Mechanical Remodel Plan
MH102b Level 02 Area B Mechanical Remodel Plan
MH103a Level 03 Area A Mechanical Remodel Plan
MH104a Roof Area A Mechanical Remodel Plan
MH104b Roof Area B Mechanical Remodel Plan
MH401 Enlarged Level 00 Area A Mechanical Remodel Plan
MH402 Enlarged Level 01 Area B Mechanical Room Remodel Plan
MH501 Mechanical Details
MI601 Mechanical Control Diagrams
MI602 Mechanical Control Diagrams
MI603 Mechanical Control Diagrams
MI604 Mechanical Control Diagrams
MI605 Mechanical Control Diagrams
MI606 Mechanical Control Diagrams
MI607 Mechanical Control Diagrams
MI608 Mechanical Control Valve Schedules
MI609 Mechanical Control Valve Schedules
MP110a Level 00 Area A Mechanical Piping Remodel Plan
MP110b LEVEL 00 AREA B MECHANICAL PLUMBING REMODEL PLAN
MP111a Level 01 Area A Mechanical Piping Remodel Plan
MP111b Level 01 Area B Mechanical Piping Remodel Plan
MP112a Level 02 Area A Mechanical Piping Remodel Plan
MP112b Level 02 Area B Mechanical Piping Remodel Plan
MP113a Level 03 Area A Mechanical Piping Remodel Plan
MP401 Enlarged Level 00 Area A Mechanical Room Remodel Plan
MP501 Mechanical Piping Details
MP502 Mechanical Piping Details
MP601 CHILLED WATER SYSTEM FLOW DIAGRAM
MP602 STEAM TO HEATING WATER FLOW DIAGRAM
PLUMBING
P-001 Plumbing Legend And Schedules
PD100a Level 00 Area A Plumbing Demolition Plan
PD100b Level 00 Area B Plumbing Demolition Plan
PD101a Level 01 Area A Plumbing Demolition Plan
PD101b Level 01 Area B Plumbing Demolition Plan
PD102a Level 02 Area A Plumbing Demolition Plan
PD102b Level 02 Area B Plumbing Demolition Plan
PD103a Level 03 Area A Plumbing Demolition Plan
PL100a Level 00 Area A Plumbing Remodel Plan
PL100b Level 00 Area B Plumbing Remodel Plan
PL101a Level 01 Area A Plumbing Remodel Plan
PL101b Level 01 Area B Plumbing Remodel Plan
PL102a Level 02 Area A Plumbing Remodel Plan
PL102b Level 02 Area B Plumbing Remodel Plan
PL103a Level 03 Area A Plumbing Remodel Plan
PL103b Roof Level Area B Plumbing Remodel Plan
PL401 Enlarged Plumbing Remodel Plans
PL402 Enlarged Plumbing Remodel Plans
PL501 Plumbing Details
PL502 Plumbing Details
PL601 East Side Water Flow Diagram
PL602 West Side Water Flow Diagram
EG000 Electrical Symbols & Details
EG100 Electrical Details
ES100 Electrical Site Plan - West Entrance
ED100 Existing Lighting Plan Level 0
ED101 Existing Lighting Plan Level 1 Area A
ED102 Existing Lighting Plan Level 1 Area B
ED103 Existing Lighting Plan Level 2 Area A
ED104 Existing Lighting Plan Level 2 Area B
ED105 Existing Lighting Plan Level 3
ED200 Existing Electrical Plan Level 0
ED201 Existing Electrical Plan Level 1 Area A
ED202 Existing Electrical Plan Level 1 Area B
ED203 Existing Electrical Plan Level 2 Area A
ED204 Existing Electrical Plan Level 2 Area B
ED205 Existing Electrical Plan Level 3
EE100 Lighitng Plan Level 0
EE101 Lighitng Plan Level1 Area A
EE102 Lighitng Plan Level1 Area B
EE103 Lighitng Plan Level2 Area A
EE104 Lighitng Plan Level2 Area B
EE105 Lighitng Plan Level 3
EE200 Power Plan Level 0
EE201 Power Plan Level 1 Area A
EE202 Power Plan Level 1 Area B
EE203 Power Plan Level 2 Area A
EE204 Power Plan Level 2 Area B
EE205 Power Plan Level 3
EE300 Access Control Plan Level 0
EE301 Access Control Plan Level 1
EE302 Access Control Plan Level 2
EE303 Access Control Plan Level 3
EE400 Riser Diagram
EE401 Emergency Power Riser Diagram
EE500 Panel Schedules
EE501 Panel Schedules
EE502 Panel Schedules
EE503 Panel Schedules
EE504 Panel Schedules
EE600 Schedules
EF100 Fire Alarm Plan Level 0
EF101 Fire Alarm Plan Level 1 Area A
EF102 Fire Alarm Plan Level 1 Area B
EF103 Fire Alarm Plan Level 2 Area A
EF104 Fire Alarm Plan Level 2 Area B
EF105 Fire Alarm Plan Level 3
ELECTRICAL
FIRE PROTECTION
FD100a Level 00 Area A Fire Protection Demolition Plan
FD101a Level 01 Area A Fire Protection Demolition Plan
FD101b Level 01 Area B Fire Protection Demolition Plan
FD102a Level 02 Area A Fire Protection Demolition Plan
FD102b Level 02 Area B Fire Protection Demolition Plan
FD103a Level 03 Area A Fire Protection Demolition Plan
FD100a Level 00 Area A Fire Protection Plan
FP101a Level 01 Area A Fire Protection Plan
FP101b Level 01 Area B Fire Protection Plan
FP102a Level 02 Area A Fire Protection Plan
FP102b Level 02 Area B Fire Protection Plan
FP103a Level 03 Area A Fire Protection Demolition Plan
Type II-B Allowable Height and Area (Chapter 5)
Allowable Height and Number of Stories (Table 504.3 & 504.4)with Sprinkler Throughout (S)
B: Is allowed 4 stories and a maximum height of 75'
Allowable Area per Floor (Table 506.2) with Sprinkler Throughout (SM)
Equation 5-2
B:= [69,000 + (23,000x0.59)] = 82,570 SF per Floor x3 Levels = Total Building Allowable Area 247,710
Actual Area Type B
Level 0 9,930 SF
Level 1 48,065 SF
Level 2 48,065 SF
Level 3 26,950 SF
TOTAL 136,010 SF
1004.3 Multiple function occupant load.Where an area under consideration contains multiple functions having different occupant
load factors, the design occupant load for such area shall be based on the floor area of each function calculated independently.
Special Use and Occupancy (e.g. High Rise, Covered Mall): ___________________
BAHTBABABA
Design Wind Speed: 115 mph.Seismic Design Category: D
Fire Resistance Rating Requirements for Building Elements (hours).
Number of Stories: 3 below grade, 1 above grade
Required: ______ Provided: ______ Type of Sprinkler System: ______
Fully sprinklered with approved system as required by IBC, Section 903.2.8., Section 903.2.10, Section 903.3.1.1. Portable
fire extinguishers are required by IBC, Section 906.1.1.
Sprinklers: Fully sprinkled
No Requirements for the Exterior Walls based on the fire seperation distance
Change in Use: Yes ______ No _____ Mixed Occupancy: Yes _____ No ______
International Building Code
International Mechanical Code
International Plumbing Code
National Electric Code
International Fire Code
Accessibility ICC/ANSI A117.1
APPLICABLE CODES
CODE ANALYSIS
1
3
IBC CHAPTER 3
IBC CHAPTER 6
4 IBC CHAPTER 5
5 IBC CHAPTER 6
6 IBC CHAPTER 7
7 IBC CHAPTER 9
8 IBC CHAPTER 10
International Energy Conservation Code
2 IBC CHAPTER 16
Building Height: 44'-6"
Primary Structural Frame
Bearing Walls Exterior
Bearing Walls Interior
Non-Bearing Walls Exterior
Non-Bearing Walls Interior
Floor Construction
Roof Construction
Exterior Doors & Windows
Shaft Enclosures
* = where FSD > 30', rated wall not required See A500's for assembly listings
3 STORY EXISTING BYU IDAHO UNIVERISTY INTERIOR REMODEL - ( UNDER THE 2018 IEBC – Level 3 Alterations)
PROJECT DESCRIPTION
Occupancy Group B
OCCUPANCY CLASSIFICATION AND USE
STRUCTURAL DESIGN
TYPE OF CONSTRUCTION
GENERAL BUILDING HEIGHTS AND AREAS
FIRE-RESISTANCE RATINGS AND ASSEMBLIES
FIRE SEPERATION
FIRE PROTECTION SYSTEMS
MEANS OF EGRESS
2018
2018
2018
2017
2018
0-HR
0-HR
0-HR
0-HR*
0-HR
0-HR
0-HR
0-HR
2-HR
TYPE II-B
X X
NA
X X NFPA 13
Egress Width Calculations See Code Analysis Sheets
The means of egress shall be configured such that the loss of any one exit shall not reduce the available capacity or width to less
than 50 percent of the required capacity or width (Section 1005.5).
See individual code sheets for calculations.
Maximum Common Path of Egress Travel Distance (Table 1006.2.1)
A Occupancy = 75 feet, maximum 49 occupant load of space when there is only one exit
B Occupancy = 100 feet, maximum 49 occupant load of space when there is only one exit
Egress Based on Occupant Load (Section 1006.3.2)
Occupant Load of 1-500 per story = 2 exits minimum
Occupant Load of 501-1,000 per story = 3 exits minimum
Exit and Exit Doorway Access
Number of exits provided for the Existing Building are 7 exits.
Where two exits are required, they shall not be placed a distance apart equal to not less than 1/3 of the length of the maximum diagonal
dimension of the area served (Section 1007.1.2).
Two-way Communication (Section 1009.8)
A two-way communications system shall be provided at the landing serving each elevator or bank of elevators on each accessible
floor that is one or more levels above or below the level of exit discharge.
The two-way communication system provide communication between each required location and the fire command center or a
central control point location approved by the fire department. Where the central control point is not a constantly attended location,
the system shall have a timed automatic telephone dial-out capability to a monitoring location or 9-1-1, and include both audible and
cisible signals.
Directions for use shall be posted adjacent to the two-way communication system. Signage shall comply with ICC A117.1
requirements for visual characters.
Exit Access Travel Distance (Table 1017.2)
A Occupancy travel distance not to exceed 250 feet – See Code Analysis Sheets per Level
B Occupancy travel distance not to exceed 300 feet – See Code Analysis Sheets per Level
Dead-End Corridor (Section 1020.4.2)
Where more than one exit is required, the exit access shall be arranged such that dead-end corridors do not exceed 50 feet in
length.
2015
Non-Separated Occupancies
No separation is required between non-separated occupancies
2009
TYPE II-B
9 IBC CHAPTER 29PLUMBING REQUIREMENTS
11 ZONING UNCHANGED
10 IBC CHAPTER 30
Provided: 2 Number of stops: 4 / 2 Elevator Lobby: Level 1
ELEVATORS
PLUMBING FIXTURE ANALYSIS SUMMARY
OCCUPANCY
GROUP
B
OCCUPANT LOAD
MALE FEMALE
WATER CLOSETS
MALE FEMALE
LAVORATORIES
MALE FEMALE
BATHTUBS/
SHOWERS
DRINKING
FOUNTAIN SERVICE SINK
1,300 1,300 26 26 17 17REQUIRED NA 26 1 PER FLOOR
33 26 19 21PROVIDED NA 30 1 PER FLOOR
NOTES:Provided fixtures are derived from the project aggregate with multiple occupancies. The fractional numbers were first summed in project aggregate, then rounded up
to the next whole number. (IBC 2902.1.1)
OCCUPANCY LOAD AND EXIT REQUIREMENTS (table 1004.5)
Basement = 9,930 sf
a. Business area = 4,449@150 = 30 occ
b. Storage area = 4,137@300 = 14 occ
44 occ
Level 1 = 48,065 sf
a. Business area = 31,112@150 = 208 occ
b. Assembly (unconc.) area = 4,626@15 = 309 occ
c. Education Classroom area = 4,956@20 = 248 occ
765 occ
Level 2 = 48,065 sf
a. Business area = 20,398@150 = 140 occ
b. Assembly (unconc.) area = 8,710@15 = 326 occ
c. Education Classroom = 6,154@20 = 567 occ
d. Storage area = 3,002@300 = 10 occ
1,043 occ
Level 3 29,950 sf
a. Business area = 11,167@150 = 75 occ
b. Assembly (unconc.) area = 8,696@15 = 580 occ
c. Education Classroom area = 1,849@20 = 93 occ
d. Storage area = 729@300 = 3 occ
751 occ
TOTAL DESIGN OCCUPANT LOAD = 2,601 OCC
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
10/28/22
G002
Code
Analysis
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
STORAGE
032
QA
022A
OFFICE
020
OPS
022
TECH ROOM
024
STUDENTS
026F
OFFICE
026C
SHORT TERM
STORAGE
028
OFFICE
012
OFFICE
026A
OFFICE
011
OFFICE
010
TIER 2
016
OFFICE
018
BREAK ROOM
013
STORAGE
044
CUSTODIAL
STORAGE
042
BDF
040
MEN'S RR
015
WOMEN'S RR
014
ELECTRICAL
038
CUSTODIAL
036
MECH CHASE
034
ELEV
0-JSTAIR
0-E
MECH CHASE
O-F
STAIR
0-E
MECH ROOM
030
CHEMICALS
ROOM
O-D
IMAGING AND
STORAGE
009
TD 66 FT
TD 110 FT
CPE 46 FT
TD 117 FT
OCC.
Req.
Prov.
8.55"
DOOR
34"
57OCC.
Req.
Prov.
11.4"
STAIR
59"
57
OCC.
Req.
Prov.
5.25"
DOOR
34"
35OCC.
Req.
Prov.
7"
STAIR
48"
35
OCC.
Req.
Prov.
5.25"
DOOR
34"
35
Basement ___________ __ __9,930 SF
a. BUSINESS AREA = 4,449@150 = 30 OCC
b. STORAGE AREA = 4,137@300 = 14 OCC
44 OCC
FE
1
FE
1
FE
2
K
GRAPHIC LEGEND
OCC.
Req.
Prov.
30"
DOOR
36"
150
OCC.
Req.
Prov.
25.5"
STAIR
44"
85
REQUIRED AND PROVIDED DOOR OPENING SIZE (IN INCHES) BASED
OFF NUMBER OF EXITING OCCUPANTS
REQUIRED AND PROVIDED STAIR WIDTH SIZE (IN INCHES) BASED
OFF NUMBER OF EXITING OCCUPANTS
FIRE EXTINGUISHER IN SEMI-RECESSED CABINET; 75' RADIUS
COMMON PATH OF EGRESS (CPE)
TRAVEL DISTANCE (TD)
POINT AT WHICH A CHOICE OF TWO EXITS BECOME AVAILABLE
25 TRAVEL PATH OCCUPANTS & DIRECTION OF TRAVEL
NOTES:
a. SEE SHEET SERIES A500's FOR ADDITIONAL WALL TYPE INFORMATION AND UL LISTINGS
b. SEE G000's FOR ADDITIONAL CODE INFORMATION
1 HOUR RATING
2 HOUR RATING
3 HOUR RATING
1
1 2
1 2 3
REMOTE POINT
FIRE RATING OF OPENING (IN MINUTES)
ADDITIONAL INFORMATION PROVIDED IN A600's SERIES
FE
1
FE
2
120
FIRE EXTINGUISHER SURFACE MOUNTED ON WALL HOOK; 75' RADIUS
NEW FIRE RATED DOOR EXISTING FIRE RATED DOOR
K KNOX BOX LOCATION
STAND PIPE LOCATION
BUSINESS USE OCCUPANCY
150 GSF PER OCC.
CLASSROOM USE OCCUPANCY
20 NET PER OCC.
ASSEMBLY USE OCCUPANCY
15 GSF PER OCC.
ACCESSORY MECHANICAL STORAGE
300 GSF PER OCC.
OCCUPANCY LOAD AND EXIT REQUIREMENTS (table 1004.5)
Basement = 9,930 sf
a. Business area = 4,449@150 = 30 occ
b. Storage area = 4,137@300 = 14 occ
44 occ
Level 1 = 48,065 sf
a. Business area = 31,112@150 = 208 occ
b. Assembly (unconc.) area = 4,626@15 = 309 occ
c. Education Classroom area = 4,956@20 = 248 occ
765 occ
Level 2 = 48,065 sf
a. Business area = 20,398@150 = 140 occ
b. Assembly (unconc.) area = 8,710@15 = 326 occ
c. Education Classroom = 6,154@20 = 567 occ
d. Storage area = 3,002@300 = 10 occ
1,043 occ
Level 3 29,950 sf
a. Business area = 11,167@150 = 75 occ
b. Assembly (unconc.) area = 8,696@15 = 580 occ
c. Education Classroom area = 1,849@20 = 93 occ
d. Storage area = 729@300 = 3 occ
751 occ
TOTAL DESIGN OCCUPANT LOAD = 2,602 OCC
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
10/28/22
G003
Code
Analysis &
Plans - Level
00
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
3/32" = 1'-0"A1 LEVEL 00 CODE PLAN
KEY PLAN
A
B
UP
UP
UP
UP
UP
DN
TD 146 FT
CP
E
2
5
F
T
CPE 58 FT
C
P
E
5
5
F
T
CPE 60 FT
NO DEAD END CORRIDOR
LESS THAN 24 FT
TD
1
5
6
F
T
SMALL MEETING
192A
WORKSTATIONS/
FLEX SPACE
192
STORAGE
192C
OFFICE
192B
OFFICE
160B
OFFICE
160A
CONFERENCE
ROOM
158
TUTORING
ADMIN OPEN
AREA
160
STORAGE
190C
TRAINING AREA
190
OFFICE
190B
OFFICE
190A
OFFICE
188A
CONFERENCE
188B
OFFICE
186
OFFICE
185
OFFICE
184
OFFICE
183
OFFICE
182
OFFICE
181
ADJUNCT
OFFICE
180
COLLABORATIVE
SPACE
188
I.T. HELP DESK
176
MATH LAB
RECEPTION
175
STUDENT PREP
174
CLASSROOM
172
STUDY
178
STUDY
179
DROP IN MATH
LAB
170
STORAGE
170C
STUDY
170B
STUDY
170A
CLASSROOM
168
CLASSROOM
166
CLASSROOM
164
CLASSROOM
162
PRACTICE
156C
PRACTICE
156B
PRACTICE
156A
STORAGE
156D
PRACTICE
156E
OFFICE
156F
WORKSPACE
156
WOMENS
148
MENS
146
JANITORS
OFFICE
147
CONFERENCE
ROOM
140
BREAKROOM
142
OPEN STUDY
122A
STUDY (MED)
132
OFFICE
131
OFFICE
130
OFFICE
129
STUDY (SM)
128
STUDY (SM)
127
RECEPTION
134
OFFICE
136
OFFICE
138
FAMILY RR
144
OPEN STUDY
122B
OPEN STUDY
122C
STUDY (MED)
125
STUDY (SM)
126
STUDY (MED)
124
HD BOOK
COLLECTION
122
VESTIBULE
1-F
OPEN STUDY
118
CIRCULATION
RECEPTION
110
INTER LIBRARY
LOAN
WORKSPACE
114
OFFICE
114A
CHECK-IN
112 OFFICE
108
OFFICE
106
OFFICE
104
VESTIBULE
1-U
ELECTRICAL
173
VESTIBULE
1-Z
MECH
08
ELEV EQUIP
08A
ELEV
1-T
CPE 66 FT
NO DEAD END CORRIDOR
LESS THAN 46 FT
MEN'S
RESTROOM
154
WOMEN'S
RESTROOM
152
STAIR
1-H
STAIR
1-B
VESTIBULE
1-A
TD
1
7
7
F
T
CPE 64 FT
CPE 93 FT
OCC.
Req.
Prov.
19.05"
DOOR 7
34"
127
OCC.
Req.
Prov.
19.05"
DOOR
170"
127 OCC.
Req.
Prov.
11.4"
STAIR
132"
57
OCC.
Req.
Prov.
11.2"
STAIR / DOOR 5
72"
56
OCC.
Req.
Prov.
11.2"
STAIR
59"
56
OCC.
Req.
Prov.
13.4"
STAIR
72"
67
OCC.
Req.
Prov.
13.6"
STAIR
72"
68
OCC.
Req.
Prov.
19.05"
DOOR 3
34"
127 OCC.
Req.
Prov.
19.05"
DOOR 2
136"
127
OCC.
Req.
Prov.
19.05"
DOOR 1
204"
127
OCC.
Req.
Prov.
8.55"
DOOR 4
204"
57
OCC.
Req.
Prov.
19.05"
DOOR 6
144"
127
MECH CHASE
1-K
ELEVATOR
1-JMECH CHASE
1-G
OPEN STUDY
122A
RESERVE MEDIA
116
ELEC ROOM
102
OPEN STUDY
100
ENTRY HALL
120A
ENTRY HALL
120B
FE
1
FE
1
FE
1
FE
1
FE
1
FE
1
FE
1
FE
1
FE
1
MECH
1-E
STAIR
1-D
HALLWAY
1-C
READING
150
STAIRS
1-N
FE
1
FE
2
K
K
K
BUSINESS USE OCCUPANCY
150 GSF PER OCC.
CLASSROOM USE OCCUPANCY
20 NET PER OCC.
ASSEMBLY USE OCCUPANCY
15 GSF PER OCC.
ACCESSORY MECHANICAL STORAGE
300 GSF PER OCC.
OCCUPANCY LOAD AND EXIT REQUIREMENTS (table 1004.5)
Basement = 9,930 sf
a. Business area = 4,449@150 = 30 occ
b. Storage area = 4,137@300 = 14 occ
44 occ
Level 1 = 48,065 sf
a. Business area = 31,112@150 = 208 occ
b. Assembly (unconc.) area = 4,626@15 = 309 occ
c. Education Classroom area = 4,956@20 = 248 occ
765 occ
Level 2 = 48,065 sf
a. Business area = 20,398@150 = 140 occ
b. Assembly (unconc.) area = 8,710@15 = 326 occ
c. Education Classroom = 6,154@20 = 567 occ
d. Storage area = 3,002@300 = 10 occ
1,043 occ
Level 3 29,950 sf
a. Business area = 11,167@150 = 75 occ
b. Assembly (unconc.) area = 8,696@15 = 580 occ
c. Education Classroom area = 1,849@20 = 93 occ
d. Storage area = 729@300 = 3 occ
751 occ
TOTAL DESIGN OCCUPANT LOAD = 2,602 OCC
GRAPHIC LEGEND
OCC.
Req.
Prov.
30"
DOOR
36"
150
OCC.
Req.
Prov.
25.5"
STAIR
44"
85
REQUIRED AND PROVIDED DOOR OPENING SIZE (IN INCHES) BASED
OFF NUMBER OF EXITING OCCUPANTS
REQUIRED AND PROVIDED STAIR WIDTH SIZE (IN INCHES) BASED
OFF NUMBER OF EXITING OCCUPANTS
FIRE EXTINGUISHER IN SEMI-RECESSED CABINET; 75' RADIUS
COMMON PATH OF EGRESS (CPE)
TRAVEL DISTANCE (TD)
POINT AT WHICH A CHOICE OF TWO EXITS BECOME AVAILABLE
25 TRAVEL PATH OCCUPANTS & DIRECTION OF TRAVEL
NOTES:
a. SEE SHEET SERIES A500's FOR ADDITIONAL WALL TYPE INFORMATION AND UL LISTINGS
b. SEE G000's FOR ADDITIONAL CODE INFORMATION
1 HOUR RATING
2 HOUR RATING
3 HOUR RATING
1
1 2
1 2 3
REMOTE POINT
FIRE RATING OF OPENING (IN MINUTES)
ADDITIONAL INFORMATION PROVIDED IN A600's SERIES
FE
1
FE
2
120
FIRE EXTINGUISHER SURFACE MOUNTED ON WALL HOOK; 75' RADIUS
NEW FIRE RATED DOOR EXISTING FIRE RATED DOOR
K KNOX BOX LOCATION
STAND PIPE LOCATION
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
10/28/22
G004
Code
Analysis &
Plans - Level
01
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
3/32" = 1'-0"A1 LEVEL 01 CODE PLAN
KEY PLAN
A
B
DN
DN
UP
UP
UP
PREP /
STORAGE
256A
OFFICE
256B
OFFICE
256C
CLASSROOM
258
CLASSROOM
260
WRITING
CENTER OPEN
TUTORING
256
OPEN TUTORING
254
OFFICE
264
OFFICE
265
STUDY
266
STUDY
267
STUDY
268
STUDY
269
OPEN TUTORING
CENTER
270
PREP /
STORAGE
270B
PREFUNCTION
270F
STUDY
270H
STORAGE
270J
CLASSROOM
272
CLASSROOM
278
PRE-FUNCTION
270E
PRE-FUNCTION
270D
PRE-FUNCTION
270C
TR / COMM.
280
OFFICE
288B
OFFICE
288C
ADJUNCT
OFFICE
286
1,157 SF
ENGLISH
TRANSITION
CENTER
288
STUDY SKILLS
252
STUDY
252C
OFFICE
252D
OFFICE
252E
STORAGE
252F
PREP /
STORAGE
252G
STUDY
252B
STUDY
252A
OPEN
COMPUTERS
240
LARGE
COMPUTER
CLASSROOM
234
SHEET MUSIC
236
SCANNER
228C
TECH SERV
STORAGE
2-E
DCAM
228B
OFFICE
228A
OFFICE
232
OFFICE
230
JANITOR'S
OFFICE
241
MOTHERS
243
ELECTRICAL
ROOM
242
I.T.
245
OPEN STUDY
53
OFFICE
200
OFFICE
202
STUDY (SM)
204
STUDY (SM)
208
STUDY (SM)
210
STUDY (SM)
212
OPEN STUDY
220
STUDY (MED)
214
STUDY (MED)
216
STUDY (MED)
218
INSTRUCTION 1
222
INSTRUCTION 2
224
PRESS ROOM
226
SPECIAL
COLLECTIONS
228
ARCHIVE
228D
VAULT
228E
MECHANICAL
2-D
TECH SERVICES
238
MEN'S
RESTROOM
247
WOMEN'S
RESTROOM
248
STAIR
2-G
ELEV
2-H
MECH CHASE
2-J
STAIR
2-A
STAIR
2-B
OCC.
Req.
Prov.
17.4"
DOOR
34"
116
OCC.
Req.
Prov.
18.75"
DOOR
34"
125
OCC.
Req.
Prov.
45"
DOOR
136"
300 OCC.
Req.
Prov.
60"
STAIR
132"
300
OCC.
Req.
Prov.
23.2"
STAIR
72"
116
OCC.
Req.
Prov.
25"
STAIR
72"
125
OCC.
Req.
Prov.
22.4"
STAIR
72"
112
OCC.
Req.
Prov.
55"
STAIR
72"
275
TD 128 FT
CPE 62 FT
CPE 92 FT
CPE 85 FT
TD 139 FT
C P E 5 0 FT
CPE 73 FT
TD 195 FT
WOMEN'S
RESTROOM
284
MEN'S
RESTROOM
282
STAIR
2-P
STOR
299
STUDY
288D
STUDY
288E
STUDY
288F
STUDY
288G
STUDY
288A
STORAGE
288H
STUDY
270G
FE
1
FE
1
FE
1
FE
1
FE
1
FE
1
FE
1
FE
1
OCC.
Req.
Prov.
16.95"
DOOR
72"
113
FAMILY RR
244
JANITOR'S
CLOSET
249
OPEN STUDY
250
MECH
2-C
MECH CHASE
2-F
RECEPTION
270A
ELEV
2-R
ELECTRICAL
2-I
STAIR
2-A
FE
1
FE
3
FE
1
BUSINESS USE OCCUPANCY
150 GSF PER OCC.
CLASSROOM USE OCCUPANCY
20 NET PER OCC.
ASSEMBLY USE OCCUPANCY
15 GSF PER OCC.
ACCESSORY MECHANICAL STORAGE
300 GSF PER OCC.
OCCUPANCY LOAD AND EXIT REQUIREMENTS (table 1004.5)
Basement = 9,930 sf
a. Business area = 4,449@150 = 30 occ
b. Storage area = 4,137@300 = 14 occ
44 occ
Level 1 = 48,065 sf
a. Business area = 31,112@150 = 208 occ
b. Assembly (unconc.) area = 4,626@15 = 309 occ
c. Education Classroom area = 4,956@20 = 248 occ
765 occ
Level 2 = 48,065 sf
a. Business area = 20,398@150 = 140 occ
b. Assembly (unconc.) area = 8,710@15 = 326 occ
c. Education Classroom = 6,154@20 = 567 occ
d. Storage area = 3,002@300 = 10 occ
1,043 occ
Level 3 29,950 sf
a. Business area = 11,167@150 = 75 occ
b. Assembly (unconc.) area = 8,696@15 = 580 occ
c. Education Classroom area = 1,849@20 = 93 occ
d. Storage area = 729@300 = 3 occ
751 occ
TOTAL DESIGN OCCUPANT LOAD = 2,602 OCC
GRAPHIC LEGEND
OCC.
Req.
Prov.
30"
DOOR
36"
150
OCC.
Req.
Prov.
25.5"
STAIR
44"
85
REQUIRED AND PROVIDED DOOR OPENING SIZE (IN INCHES) BASED
OFF NUMBER OF EXITING OCCUPANTS
REQUIRED AND PROVIDED STAIR WIDTH SIZE (IN INCHES) BASED
OFF NUMBER OF EXITING OCCUPANTS
FIRE EXTINGUISHER IN SEMI-RECESSED CABINET; 75' RADIUS
COMMON PATH OF EGRESS (CPE)
TRAVEL DISTANCE (TD)
POINT AT WHICH A CHOICE OF TWO EXITS BECOME AVAILABLE
25 TRAVEL PATH OCCUPANTS & DIRECTION OF TRAVEL
NOTES:
a. SEE SHEET SERIES A500's FOR ADDITIONAL WALL TYPE INFORMATION AND UL LISTINGS
b. SEE G000's FOR ADDITIONAL CODE INFORMATION
1 HOUR RATING
2 HOUR RATING
3 HOUR RATING
1
1 2
1 2 3
REMOTE POINT
FIRE RATING OF OPENING (IN MINUTES)
ADDITIONAL INFORMATION PROVIDED IN A600's SERIES
FE
1
FE
2
120
FIRE EXTINGUISHER SURFACE MOUNTED ON WALL HOOK; 75' RADIUS
NEW FIRE RATED DOOR EXISTING FIRE RATED DOOR
K KNOX BOX LOCATION
STAND PIPE LOCATION
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
10/28/22
G005
Code
Analysis &
Plans - Level
02
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
3/32" = 1'-0"A1 LEVEL 02 CODE PLAN
KEY PLAN
A
B
UP
DN
DN
( QUIET )
OPEN STUDY
342
STUDY (SM)
340
STUDY (SM)
338
STUDY (SM)
336
STUDY (SM)
334
STUDY (SM)
332
STUDY (SM)
330
ELECTRICAL
324B
MAC EQUIP
324A
OFFICE
322
STUDY (SM)
320
STUDY (SM)
318
MAC LAB
324
STUDY (LG)
326
STUDY (LG)
328
STUDY (SM)
316
STUDY (SM)
314
OFFICE
312
OFFICE
310
JUVENILE
300
ELECTRICAL
308
STORAGE
306
STUDY (MED)
304
STUDY (MED)
302
BRIDGE
CONNECTION
3-A
Bridge
Connection
-
TEST RM
378
TEST RM
374
Janitors Closet
376
ELEC
364
OPEN STUDY
362
STORAGE
352
RESTROOM
344B
KIDS PLAY
344CMOTHERS
ROOM
344A
FAMILY STUDY
344
TEST RM
382
TEST RM
380
TEST RM
372
TEST RM
370
TEST RM
360
TEST RM
358
TEST RM
356
TEST RM
350
TEST RM
348
TEST RM
346
MECH CHASE
3-E
MECH
3-D
TD 172 FT CPE 41 FT
OCC.
Req.
Prov.
26.25"
DOOR
34"
175
OCC.
Req.
Prov.
26.25"
DOOR
34"
175
OCC.
Req.
Prov.
60.15"
DOOR
136"
401 OCC.
Req.
Prov.
49.8"
STAIR
132"
249
OCC.
Req.
Prov.
35"
STAIR
72"
175
OCC.
Req.
Prov.
35"
STAIR
72"
175
CPE 54 FT
FE
1
FE
1
FE
1
FE
1
FE
1
MECH CHASE
3-H
ELEV
3-G
STAIRS
3-C
MENS
368
WOMENS
366
STAIR
3-F
STAIR 1
3-B
FE
1
FE
1
BUSINESS USE OCCUPANCY
150 GSF PER OCC.
CLASSROOM USE OCCUPANCY
20 NET PER OCC.
ASSEMBLY USE OCCUPANCY
15 GSF PER OCC.
ACCESSORY MECHANICAL STORAGE
300 GSF PER OCC.
OCCUPANCY LOAD AND EXIT REQUIREMENTS (table 1004.5)
Basement = 9,930 sf
a. Business area = 4,449@150 = 30 occ
b. Storage area = 4,137@300 = 14 occ
44 occ
Level 1 = 48,065 sf
a. Business area = 31,112@150 = 208 occ
b. Assembly (unconc.) area = 4,626@15 = 309 occ
c. Education Classroom area = 4,956@20 = 248 occ
765 occ
Level 2 = 48,065 sf
a. Business area = 20,398@150 = 140 occ
b. Assembly (unconc.) area = 8,710@15 = 326 occ
c. Education Classroom = 6,154@20 = 567 occ
d. Storage area = 3,002@300 = 10 occ
1,043 occ
Level 3 29,950 sf
a. Business area = 11,167@150 = 75 occ
b. Assembly (unconc.) area = 8,696@15 = 580 occ
c. Education Classroom area = 1,849@20 = 93 occ
d. Storage area = 729@300 = 3 occ
751 occ
TOTAL DESIGN OCCUPANT LOAD = 2,602 OCC
GRAPHIC LEGEND
OCC.
Req.
Prov.
30"
DOOR
36"
150
OCC.
Req.
Prov.
25.5"
STAIR
44"
85
REQUIRED AND PROVIDED DOOR OPENING SIZE (IN INCHES) BASED
OFF NUMBER OF EXITING OCCUPANTS
REQUIRED AND PROVIDED STAIR WIDTH SIZE (IN INCHES) BASED
OFF NUMBER OF EXITING OCCUPANTS
FIRE EXTINGUISHER IN SEMI-RECESSED CABINET; 75' RADIUS
COMMON PATH OF EGRESS (CPE)
TRAVEL DISTANCE (TD)
POINT AT WHICH A CHOICE OF TWO EXITS BECOME AVAILABLE
25 TRAVEL PATH OCCUPANTS & DIRECTION OF TRAVEL
NOTES:
a. SEE SHEET SERIES A500's FOR ADDITIONAL WALL TYPE INFORMATION AND UL LISTINGS
b. SEE G000's FOR ADDITIONAL CODE INFORMATION
1 HOUR RATING
2 HOUR RATING
3 HOUR RATING
1
1 2
1 2 3
REMOTE POINT
FIRE RATING OF OPENING (IN MINUTES)
ADDITIONAL INFORMATION PROVIDED IN A600's SERIES
FE
1
FE
2
120
FIRE EXTINGUISHER SURFACE MOUNTED ON WALL HOOK; 75' RADIUS
NEW FIRE RATED DOOR EXISTING FIRE RATED DOOR
K KNOX BOX LOCATION
STAND PIPE LOCATION
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
10/28/22
G006
Code
Analysis &
Plans - Level
03
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
3/32" = 1'-0"A1 LEVEL 03 CODE PLAN
KEY PLAN
A
B
DN
PHASE 1.1
PHASE 1.2
PHASE 2
PHASE 1.1
PHASE 1.3
STAIR TO BE USED AS EGRESS DURING CONSTRUCTION.
MODIFICATIONS TO FIRE SUPRRESION, CEILINGS, ETC.
PHASE 1.2
PHASE 2
PHASE 1.3
STAIR TO BE USED AS EGRESS DURING CONSTRUCTION.
MODIFICATIONS TO FIRE SUPRRESION, CEILINGS, ETC.
PHASE 1.2
PHASE 1.3
STAIR TO BE USED AS EGRESS DURING CONSTRUCTION.
MODIFICATIONS TO FIRE SUPRRESION, CEILINGS, ETC.
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
10/28/22
G010
Phasing Plans
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
3/64" = 1'-0"C1 LEVEL 00 PHASING PLAN
3/64" = 1'-0"C4 LEVEL 01 PHASING PLAN
3/64" = 1'-0"A1 LEVEL 02 PHASING PLAN
3/64" = 1'-0"A4 LEVEL 03 PHASING PLAN
GENERAL NOTE: OWNER WILL REMOVE FURNITURE, BOOKS, AND OTHER ITEMS PRIOR TO CONSTRUCTION.
PHASE 1.1 -
• REMODEL BASEMENT LEVEL IN AREA 'A' (WEST WING)
• MOVE LIBRARY OUT OF LEVELS ONE THROUGH THREE
• CREATE SOUTH ENTRANCE OF AREA 'B' (EAST WING)
PHASE 1.2 -
• REMODEL LEVELS ONE, TWO AND THREE IN AREA 'A'
• CREATE LEVEL THREE OPENING IN MIDDEL STAIRWELL
PHASE 1.3
• REMODEL MIDDLE STAIRWELL AREA 'A'
PHASE 2
• REMODEL LEVELS ONE AND TWO OF AREA 'B', INCLUDING THE
BREEZEWAY CONNECTION BETWEEN THE TWO AREAS.
MIRROR SOAP DISPENSER PAPER TOWEL
DISPENSER
TOILET PAPER HOLDER SANITARY NAPKIN
DISPOSAL
SANITARY NAPKIN
DISPENSER
BABY CHANGING
STATION
TOILET SEAT COVERS
DISPENSER
WASTE RECEPTACLE FIRE
EXTINGUISHER
CABINET
HAND DRYER
TO
R
E
F
L
E
C
T
I
V
E
SU
R
F
A
C
E
TO
D
I
S
P
E
N
S
E
R
TO
D
I
S
P
E
N
S
E
R
/
H
A
N
D
L
E
TO
O
P
E
N
,
F
L
A
T
SU
R
F
A
C
E
O
F
B
E
D
NOTES:
1. WHERE SHOWN, 48" MAX HEIGHT SHALL BE MEASURED FROM FLOOR TO ANY HIGHEST OPERABLE PART
2. PROVIDE BLOCKING FOR ALL EQUIPMENT PER MANUFACTURER'S WRITTEN INSTRUCTIONS
3' - 4"MAX
3' - 6"
4' - 0"MAX
15" MIN
2' - 0"
2' - 6"4' - 0"MAX
2' - 10"
4' - 0"MAX
TO TOP OF OPENING
4' - 0"MAX
4' - 0"MAX
4' - 0"
TO
D
I
S
P
E
N
S
E
R
/
H
A
N
D
L
E
4' - 0"MAX
TRASH CHUTE DOOR
1' - 2"
1' - 0"
3'-2" MIN
4' - 0"MAX
TOWEL BARS
LOCKER CONTROLS
15" MIN - 48" MAX
TO TOP OF ACCESSIBLE
ACCESSIBLE
LOCKER
FIRE CABINET CUPS COAT HOOKS
TOP LOCKER SHELF:
46" MAX. AFF
BOT. LOCKER SHELF:
15" MIN. AFF
NON ACCESSIBLE
LOCKER
2x4 TOP EDGE MID RAIL
4x4 POSTS 4'-0" O.C.
2x6 CROSS ROOF SUPPORTS 4'-0"
O.C.
3/4" CDX PLYWOOD
1/2" CDX PLYWOOD SHEATHING
NAILED TO 2x4 RAILS
2x4 MID AND BOTTOM RAIL
2x4 TOP RAIL
2x4 TOP EDGE MID RAIL
8' - 5"
4x4 POSTS 4'-0" O.C.
2x6 CROSS ROOF SUPPORTS
4'-0" O.C.
3/4" CDX PLYWOOD
1/2" CDX PLYWOOD SHEATHING
NAILED TO 2x4 RAILS
2x4 MID AND BOTTOM RAIL
2x4 TOP RAIL
4' - 0"
9' - 0"
2' - 6"MIN
4' - 0"MIN
2' - 0"2' - 0"
CR
PU
SH
TO
OP
EN
4' - 0"MAX
ELEVATIONPLAN
SILICONE CAULK
CONT. FLANGE TRIM KIT KFTK125 & KXFTK125
FRAMING AS SCHEDULED
GRAB BAR WHERE SCHEDULED
LATEX CAULK (PAINTABLE)
BLOCKING CURVED SHOWER ROD
TUB/SHOWER INSERT
SILICONE CAULK
CONT. FLANGE TRIM KIT KFTK125 & KXFTK125
5/8" WATER RESISTANT TYPE 'X' GYP
BD
LOCTITE: POWER GRAB CONST. ADHESIVE
LATEX CAULK (PAINTABLE)
PLAN / JAMBELEVATION - TOP OF SHOWER OR TUB/SHOWER INSERT
TUB/SHOWER INSERT
LOCTITE: POWER GRAB CONST. ADHESIVE
5/8" WATER RESISTANT TYPE 'X' GYP
BD
ACCESSIBLE UNIT TUB
CONTROL SIDE BACK WALL HEAD
ACCESSIBLE UNIT ROLL-IN SHOWER
BLOCKING REQUIREMENTS: TUB AT ACCESSIBLE AND TYPE B UNITS
CONTROL SIDE
BACK/CONTROL WALL
BLOCKING REQUIREMENTS: ROLL-IN SHOWER AT ACCESSIBLE AND TYPE B UNITS
BACK WALL HEAD
END WALL END/SEAT WALL
ROLL-IN SHOWER PLAN
CONTROL VALVE CAN BE
ANYWHERE IN THIS SQUARE,
COORDINATE W/ MANUF
INSTRUCTIONS
TUB PLAN
FLOOR CLEARANCE
TRANSFER TYPE SHOWER PLAN
℄
CONTR
OL
WALL
℄
SEAT
WALL
℄
BACK
WALL
BACK WALL
DRAIN
℄
BACK
WALL
CONTROL WALL
DRAIN
℄
BACK
WALL
RECESSED
SOAP DISH
SLIDING
SHOWER
HEAD
CONTROL
VALVE
BOUNDARY
EXTENTS
ACCESSIBLE UNIT TRANSFER TYPE SHOWER
OPP
NOTE:
SHOWER MIXING VALVE SHALL HAVE A
TEMPERATURE CONTROL REGULATOR TO PREVENT
SCOLDING AS REQUIRED BY CODE
ALL WET WALLS NEED TO COMPLY WITH ASTM #D3273 BEHIND ALL TUB/SHOWER ENCLCOSURES
VARIES
5' - 0"
6' - 4"
5' - 0"
VARIES
4' - 0"MIN 6"MAX
6" MAX
38" MIN
2' - 0"
38" MIN
2' - 6"MAX
2' - 0"MIN
FLOOR CLEARANCE
SHOWER HEAD
TUB SPOUT
5' - 0"
2' - 0"MIN
38" MIN
2' - 6"MAX
33" - 3' - 0"
6" MAX
33" - 2' - 10"
24" MIN 12" MAX
8" - 10"
VARIES 8" - 10"
12" MIN
TRANSFER SEAT
17" - 1' - 7"
5"MIN.
3" - 6"
1' - 6"
SHOWER HEAD
VARIES
8" - 10"
33" - 2' - 10"
5"
5' - 0"TILE HEIGHT
48" MAX
4" MAX
24" MIN
2"
BAR IS OMITTED IF BUILT
IN TRANSFER SEAT IS
INSTALLED
SLIDING SHOWER
HEAD
5"
TILE HEIGHT
6' - 4"
6" MAX
END WALL
CONTROL VALVE
BOUNDARY EXTENTS
BACK/CONTROL WALL
MAX
1' - 6"
38" MIN
1' - 9"- 24"
6" -8"
8"
2' - 10"
3' - 2"MIN
8"
2' - 6"MAX
8"
2' - 6"MAX
8"
DRAIN
DRAIN
DRAIN
RECESSED SOAP DISH
38" - 44"
RECESSED SOAP
DISH
3' - 2"- 48"
GRAB BAR
SHALL NOT
EXTEND
OVER SEAT 1' - 6"
SHOWER SEAT (INCLUDED IN SPECIFICATION; IF NO
SHOWER SEAT PROVIDED, INCLUDE ADDITIONAL
GRAB BARS OVER SEAT AREA PER DRAWINGS)
30" MIN
CONTROL SIDE
24" MIN6" MAX
15"-16"
22"-23"
1 1/2"MAX
2' - 6"
FLOOR CLEARANCE
60" MIN
LENGTH OF SHOWER
5' - 0"
2' - 6"
BAR IS OMITTED IF BUILT IN TRANSFER SEAT IS
INSTALLED
12" MIN
12" MAX24" MIN12" MAX
24" MIN
CONTROL SIDE
15"-16"
22"-23"
14" - 15"
2 1/2" MAX
1 1/2"MAX
2' - 6"
LENGTH OF TUB
16" MIN
27" MAX
ABOVE GRAB BAR
48" MAX
33" - 36"
12" MAX24" MIN
33" - 36"
6" MAX
6' - 4"
38" MIN
2' - 6"MAX
SLIDING SHOWER
HEAD
END/SEAT WALL
TUB SPOUT
CONTROL VALVE CAN BE
ANYWHERE IN THIS SQUARE,
COORDINATE W/ MANUF
INSTRUCTIONS
VARIES
5' - 0"
5' - 0"
VARIES
4' - 0"MIN 6"MAX
6" MAX
38" MIN
2' - 0"
SHOWER HEAD
TUB
SPOUT
5' - 0"
2' - 0"MIN
38" MIN
2' - 6"MAX
BLOCKING REQUIREMENTS: TUB AT TYPE A & B UNITS
CONTROL SIDE BACK WALL HEAD
38" MIN
1' - 9"- 24"
6" -8"
8"8"
2' - 6"MAX
CONTROL VALVE CAN BE ANYWHERE IN THIS
SQUARE, COORDINATE W/ MANUF
INSTRUCTIONS
℄
5' - 0"
TUB PLAN
BAR IS OMITTED IF
BUILT-IN TRANSFER
SEAT IS INSTALLED
MAX
12"24" MIN
MAX
12"
CONTROL SIDE
15"-16"
22"-23"
14" - 15"
2 1/2" MAX
LENGTH OF TUB
FLOOR CLEARANCE
33" - 2' - 10"
24" MIN 12" MAX
8" - 10"
VARIES
8" - 10"
VARIES
12" MIN
TRANSFER SEAT
17" - 1' - 7"TUB SPOUT
5"MIN.
3" - 6"
1' - 6"
SHOWER HEAD
W/ 60" HOSE
VARIES
8" - 10"
33" - 2' - 10"
5"
48" MAX
4" MAX
24" MIN
2"
TUB AT TYPE A UNIT
BAR IS OMITTED IF BUILT
IN TRANSFER SEAT IS
INSTALLED
CONTROL SIDE BACK WALL HEAD
MAX
1' - 6"
DRAIN DRAIN
RECESSED
SOAP DISH
3' - 2"- 48"
5' - 0"TILE HEIGHT
5' - 0"TILE HEIGHT
NOTE:
- SHOWER MIXING VALVE SHALL HAVE A TEMPERATURE CONTROL REGULATOR TO PREVENT SCOLDING AS REQUIRED BY CODE
- BLOCKING MUST BE PROVIDED FOR ALL UNITS, FOR FUTURE GRAB BARS
TOP OF TILE FOR TUB &
SHOWER ENCLOSURE
CONTROL VALVE CAN BE ANYWHERE IN THIS
SQUARE, COORDINATE W/ MANUF
INSTRUCTIONS
2' - 6"
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
10/28/22
G011.1
ADA
Guidelines
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
1/2" = 1'-0"E1 TYPICAL MOUNTING HEIGHTS1
1/2" = 1'-0"C3 TYPICAL PEDESTRIANPROTECTION CORRIDOR1
1/2" = 1'-0"C5 CARD READER VIEW1
3" = 1'-0"D5 TUB / SHOWER INSERT DETAIL
3/8" = 1'-0"A1 SHOWER/TUB GRAB & BLOCKING LOCATION
3/8" = 1'-0"C1 TUB / TUB BLOCKING LOCATIONS
NOT APPLICABLE
NOT APPLICABLE
NOT APPLICABLE
5' - 7"MIN
5' - 8"MIN
3' - 0"MIN
5' - 0"MIN
1' - 4"MIN 3' - 0"MIN 1' - 4"MIN
2' - 0"MIN
10"MAX
OVERLAP OF KNEE AND TOE
5' - 0"MIN
2' - 1"MAX
OVERLAP OF KNEE AND TOE
8"MIN
8"MIN
CIRCULAR TURNING SPACE -
NEW BUILDINGS
CIRCULAR TURNING SPACE -
EXISTING BUILDINGS
T-SHAPED TURNING SPACE -
NEW BUILDINGS - OPTION 1
5' - 4"MIN
3' - 2"MIN
5' - 0"MIN
11"MIN 3' - 6"MIN 11"MIN
1' - 10"MIN
T-SHAPED TURNING SPACE -
NEW BUILDINGS - OPTION 2
5' - 4"MIN
3' - 4"MIN
5' - 0"MIN
1' - 0"MIN 3' - 4"MIN 1' - 0"MIN
1' - 8"MIN
T-SHAPED TURNING SPACE -
NEW BUILDINGS - OPTION 3
ARM
BASE
BASE
ARM
T-SHAPED TURNING SPACE -
NEW BUILDINGS - OVERLAP
SIZE OF CLEAR FLOOR SPACE
2' - 6"MIN
EXISTING BLDGS - 48" MIN
NEW BLDGS - 4' - 4"MIN
3' - 0"MIN
X > 2' - 0"
X >1' - 3"
5' - 0"MIN
POSITION OF CLEAR FLOOR SPACE
FORWARD
POSITION OF CLEAR FLOOR SPACE
PARALLEL
MANUEVERING CLEARANCE IN AN ALCOVE
PARALLEL APPROACH
MANUEVERING CLEARANCE IN AN ALCOVE
FORWARD APPROACH
27" MAX
6' - 8" MINIMUM.
1/2" DIAMETER STEEL
GUARDRAIL; FINISH TO MATCH REST OF
STAIR
SCHEDULED STAIR
RE: ENLARGED STAIR PLANS
REDUCED VERTICAL CLEARANCE
UNOBSTRUCTED FORWARD REACH OBSTRUCTED FORWARD REACH UNOBSTRUCTED SIDE REACH OBSTRUCTED HIGH SIDE REACH
15
M
I
N
38
0
48
M
A
X
12
2
0
48
M
A
X
12
2
0
44
M
A
X
11
2
0
>20-25 MAX
510-635
20 MAX
510
(a)(b)
10 MAX
255
12
2
0
48
M
A
X
15
M
I
N
38
0
10 MAX
255
12
2
0
48
M
A
X
34
M
A
X
86
5
34
M
A
X
86
5
46
M
A
X
11
7
0
> 10-24 MAX
255-610
(a)(b)
PUSH SIDE
4' - 10"MIN.
MIN.
1' - 0"
12" MIN. IF DOOR
HAS LATCH AND
CLOSER 12" MIN. IF DOOR
HAS LATCH AND
CLOSER
MIN.
1' - 0"
MIN.
2' - 8"
4' - 0"MIN.
FRONT APPROACHHINGE APPROACH
5' - 0"MIN.
3' - 6"MIN.
LATCH APPROACH
SWINGING DOORS SWINGING DOORS
3' - 6"MIN.
SWINGING DOORS STANDARD HARDWARE DOOR PROVIDED WITH CLOSER & LATCH
22" MIN.5' - 0"MIN.
4' - 0"MIN.
1' - 6"MIN.
4' - 0"MIN.
4' - 0" MIN.
1' - 0"MIN.
8" MAX2' - 0"MIN.4' - 6"MIN.
5' - 0"MIN.
3' - 0"MIN.
3' - 6"MIN.
1' - 10"MIN.
3' - 6"MIN.
1' - 6"MIN.
5' - 0"MIN.
8" MAX
5' - 0" MIN.5' - 0" MIN.
BETWEEN HANDRAILS
3' - 0"MIN.
5' - 0" MIN.
1' - 0"1' - 0"
5' - 0" MIN.
1' - 0"
DOWN
DOWN
3' - 0" MIN.
LANDINGLANDING RAMP RUN RAMP RUN
1:12 MAX SLOPE
(8%)
NOTES:
A. RAMP DETAILS ARE SHOWN AS CODE
MINMUM REQUIREMENTS.
ACTUAL CONDITIONS MAY VARY. SEE SITE
PLAN AND DETAILS
B. CLEAR WIDTH OF LANDINGS SHALL BE AT
LEAST AS WIDE AS THE WIDEST RAMP RUN
LEADING TO THE LANDING
C. RAMP RUNS WITH A RISE GREATER THAN 6
INCHES SHALL HAVE HANDRAILS
1:48 MAX SLOPE
(2%)
LANDING
CONTINUOUS HANDRAIL
AT INSIDE CORNER OF
LANDING
30" MAX VERTICAL RISE
[A] STRAIGHT RUN
[B] CHANGE IN DIRECTION
30" MAX
TYPICAL
3' - 0"
1:48 MAX SLOPE
(2%)
1' - 0"HORIZONTAL RUN 1' - 0"
1
12
SECTION VIEW
SLOPE MAX RISE
1:8* - 1:10 3"
1:10 - 1:12 6"
*SLOPE STEEPER THAN 1:8 IS NOT PERMITTED
ESCUTCHEON
PLATE; FINISH
TO MATCH RAILS
& STANCHIONS;
SCHEDULED WALL
DRINKING FOUNTAIN AND BOTTLE FILLING STATIONS
℄ ℄
CLEAR FLOOR SPACE AT WHEELCHAIR
DRINKING FOUNTAINS
CLEAR FLOOR SPACE AT WHEELCHAIR
DRINKING FOUNTAINS - PRIMARILY FOR
CHILDRENS USE EXCEPTION
DRINKING FOUNTAIN AND BOTTLE FILLING STATIONS
5"MAX 1' - 3"MIN - ADULT
WHEELCHAIR DF SPOUT LOCATION STANDING US DF SPOUT LOCATION
5"MAX
430 - 635
17 - 25
760
2' - 6"min
(b)
plan(a)
elevation
430 - 635
17 - 25
760
30 min
(b)
planFIG 306.2
TOE CLEARANCE
230
9
150
6 max
(a)
elevation FIG 306.3
KNEE CLEARANCE
230
9 min
280
11 min
685
27 min
SCHEDULED WALL
WHEELCHAIR
ACCESSIBLE
FOUNTAIN
CL
1'-3"2'-4 3/8"
CL CL
CANE DETECTION
RAILS
4" MAX
1
2
MAX.
1/2"
MAX.
1/4"
1/4" - 1/2"
1
2
LEVEL CHANGE IN FLOOR SURFACE CARPET ON FLOOR SURFACES
MAX.
0' - 0 1/2"
ALL TRANSITIONS SHALL COMPLY WITH
2009 ICC A117.1 SECTIONS 302 AND 303
STYLE OF COOLER
MAY VARY
CANE TOUCH APRON;
SELECT APRON
APPROPRIATE FOR
INSTALLED FOUNTAIN
MOUNTING HARDWARE
PROVIDED WITH APRON
27" MAXIMUM HEIGHT
ABOVE FINISH FLOOR
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
10/28/22
G011.2
ADA
Guidelines
Cont.
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
3/8" = 1'-0"E1 (ANSI 304) TURNING SPACE1
3/8" = 1'-0"C1 (ANSI 305) CLEAR FLOOR SPACE1
1/2" = 1'-0"A4 (ANSI 307) REDUCED VERTICAL CLEARANCE1
3/8" = 1'-0"D1 (ANSI 308) REACH RANGES1
1/4" = 1'-0"B1 (ANSI 404) DOORS AND DOORWAYS1
1/4" = 1'-0"A1 (ANSI 405) RAMPS1
1 1/2" = 1'-0"C6 ELEVATION - CANE DETECTION AT WATER COOLER
3/8" = 1'-0"C4 (ANSI 602) DF CLEAR FLOOR SPACE1
3/8" = 1'-0"C5 (ANSI 602) DF SPOUT LOCATION1
3/8" = 1'-0"D4 (ANSI 604) TOE / KNEE CLEARANCE1
1" = 1'-0"D6 CANE DETECTION AT WATER COOLER1
12" = 1'-0"A3 ACCESSIBLE FLOOR TRANSITIONS
1" = 1'-0"B5 CANE APRON AT WATER COOLER
68" Min.
58" Min.
18" Min.
60 Min.
.
.
.66" Min.
48" Min.
15" Min 18" Min.
33" Min.
48" Min.
.
.
(a) clear floor space for water closets
60" Min.
48" Min.
.
(b) clear floor space at bathtubs
30" Min.
15" Min 18" Min.
33" Min.
.
fig. 7 clear floor space for adaptable bathrooms
48" Min.
lavatory without knee space
19" Max.
48" Min.17" Min.
lavatory with knee space
30" Min.
30" Min.
(c) clear floor space at lavatories
3'-0"
36" Min.
48" Min.
30" Min.
(e) clear floor space at shower
30" Min.
48" Min
(d) clear floor space at bathtub
note: clear floor space beside tub may overlap with clear floor space beneath adjacent fixtures
CLCL CL
DISPENSER OUTLET LOCATION - PROTRUDING
DISPENSER BELOW GRAB BAR
14" MIN
1'-6" MIN
SECTION 609.3
1 1/2" MIN
1'-0" MIN
48" MAX
2'-0" MIN
3'-6" MAX
2'-0" MIN
3'-0" MAX
DISPENSER OUTLET LOCATION - PROTRUDING
DISPENSER ABOVE GRAB BAR
4'-0" MAX
2'-0" MIN
3'-6" MAX
DISPENSER OUTLET LOCATION - RECESSED
DISPENSER
3'-0" MAX
1'-6" MIN
(CHILDREN)
19" MAX
(C
H
I
L
D
R
E
N
)
CHILDRENS DISPENSER OUTLET - EXCEPTION
1'-2" MIN
7" -9"
SECTION 609.3
5 1/2" MIN
19" MAX
℄
1'-0" MAX 3'-6"
3'-3" -41"
4'-6" MIN
1'-6" MIN
3'-3" -41"
SECTION 609.4.1
33"- 3'-0"
3'-0" MIN.
SECTION 609.4.1
33"- 3'-0"
NOTE:
FLUSH CONTRILS SHALL BE LOCATED ON
OPEN SIDE OF WATER CLOSET
℄
3'-6" MIN
6" MAX
SIDE WALL GRAB BAR FOR WATER CLOSET REAR WALL GRAB BAR FOR WATER CLOSET
1'-0" MIN 3'-6" MIN
34" - 36"
4'-6" MIN
1'-6" MIN
21" - 30"
18" - 27"
℄
POSITION OF CHILDRENS GRAB BARS SIDE
WALL VIEW
SECTION 604.5.1
16"- 1'-6"
4'-8" MIN
5'-0" MIN
2'-6" MIN
4'-0" MIN
SIZE OF CLEARANCE FOR WATER CLOSETAMBULATORY ACCESSIBLE WATER CLOSET
5'-0" MIN 3'-6" MIN
3'-0" MIN
17"-19"
1'-0" MAX 3'-6"
4'-6" MIN
3'-3" MIN
TYPICAL WATER CLOSET
5'-0" MIN
3'-0" MIN
2'-8" MIN
SIZE OF CLEARANCE FOR WATER CLOSET
5'-0" MIN
3'-6" MIN5'-0" MIN
(1) Req'd when 6 or more stalls are provided
1'-0"3'-6" MIN
3'-3" -41"
1'-0" MIN
2'-0" MIN
3'-6" MIN5'-0" MIN
1'-0"3'-6" MIN
3'-3" -41"
1'-0" MIN
2'-0" MIN 4" MAX
5'-0" MIN
4" MAX
option 1
option 2
NOTE:
FLUSH CONTRILS SHALL BE LOCATED ON
OPEN SIDE OF WATER CLOSET
NOTE:
FLUSH CONTRILS SHALL BE LOCATED ON
OPEN SIDE OF WATER CLOSET
NOTE:
FLUSH CONTROLS SHALL BE LOCATED ON
OPEN SIDE OF WATER CLOSET
WHEELCHAIR TOILET COMPARTMENT -
WALL HUNG CLOSET, ADULT
5'-0" MIN.
4'-8" MIN
WHEELCHAIR TOILET COMPARTMENTS
ALTERNATE WHEELCHAIR TOILET COMPARTMENT
5'-0" MIN.
4" MAX
4'-8" MIN.
56" MIN
5'-0" MIN.
WHEELCHAIR TOILET COMPARTMENT - DOOR SWINGING INTO
WHEELCHAIR TOILET COMPARTMENT
WHEELCHAIR TOILET COMPARTMENTS
FLOOR MOUNTED WATER CLOSET, ADULT - WALL HUNG
AND FLOOR MOUNTED WATER CLOSET, CHILDREN
5'-0" MIN.
59" MIN
7'-0" MIN
WALL MOUNTED WC - ADULT
59" MIN
WALL AND FLOOR MOUNTED WC - CHILDREN
FLOOR MOUNTED WC - ADULT
DOOR SHALL NOT SWING
INTO THE REQUIRED MINIMUM
AREA OF THE COMPARTMENT
2'-10" MAX
1'-3"
MIN.
LAVATORY OR VANITY SINK
2'-3" MIN
ACCESSIBLE SINK
BOWL 6 1/2" DEEP
COUNTER (WHERE
OCCURS)
1'-5"
NOTE:HOT WATER AND DRAIN PIPES MUST BE
CONFIGURED TO PROTECT AGAINST CONTACT. PROVIDE
HEAT SHIELDS AND/OR ISOLATION WRAP IN EXPOSED
AREAS
MIRROR
ACCESSIBLE AND TYPE B UNITS: SINK
MI
N
H.C.
1'-5" MAX.
STD.
1'-5" - 24"
1'-0" MAX.
18" MIN
2'-10" MAX.
1'-3" MIN
URINAL
URINAL SCREEN WHERE
OCCURS
LAVATORY OR VANITY SINK
2'-3" MIN.
ACCESSIBLE SINK BOWL 6
1/2" DEEP
COUNTER WHERE OCCURS
PUSH
SPOUT
FRONT VIEW SIDE VIEW
STAND'G PERSONS
SPOUT HT. 38" - 43"
PUSH
9" MIN.
2'-3" MIN.
2'-3" MIN.
MIN
1'-5"
7 7/8" MIN.
10 7/8" MIN.
MIN.
9"
1'-5"
BOTTLE FILLING STATION
NOTE:
HOT WATER AND DRAIN PIPES MUST BE CONFIGURED TO PROTECT AGAINST CONTACT.
PROVIDE HEAT SHIELDS AND OR ISOLATION WRAP IN EXPOSED AREAS.
5'-0" MIN.
WHEELCHAIR ACCESS.
SPOUT HT. 36" MAX
Figure 604.8.1.4
Wheelchair Accessible Toilet
Compartment Toe Clearance
(a)
elevation
adult
150
9 MIN
230
6 MIN
PARTITION
6 MIN
150
6 MIN
150
(c)
plan
6 MIN
(b)
elevation
children
12 MIN
150
305
PARTITION
1'-0" max 3'-6" MIN
3'-3" - 41"
4'-6" MIN
1'-6" min
3'-3" -41"
2'-9" - 36"
24" MIN
3'-0" PREFERRED
2'-9" - 36"
12" MIN 1'-0" MIN
SEAT
1'-5" -19"
2'-6" MAX
MAX
1'-0"2'-0" MIN
PREFERRED
3'-6"
BLOCKING REQUIREMENTS
ALL UNITS: TOILET AREA
1'-6"
3'-2" MIN
24" MIN
MIN
1'-0"
MIN
1'-0"2" - 4" ADDITIONAL REINFORCING AT
SIDES RECOMMENDED
2'-2" PREFERRED
1'-7" MIN
MIN
1'-7"
MIN
3'-0"
TOILET PAPER DISPENSER
LOCATION
ACCESSIBLE UNIT: TOILET
1'-6"
1'-0" MAX 3'-6"
39" - 41"
4'-6" MIN
1'-6" MIN
3'-3" -41"
33"- 3'-0"
3'-0"
33"- 3'-0"
2'-0" MIN 1'-0" MIN
1'-5" -19"
604.10.4
11" - 17" @
CHILDREN'S FACILITIES
NOTE:
FLUSH CONTROLS SHALL BE LOCATED ON
OPEN SIDE OF WATER CLOSET
GRAB BAR PLACEMENT
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
10/28/22
G011.3
Accessibility
Details
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
1/4" = 1'-0"E1 ADA CLEAR FLOOR SPACE
3/8" = 1'-0"D1 (ANSI 604) DISPENSER LOCATION
3/8" = 1'-0"D3 (ANSI 604) GRAB BAR PLACEMENT
3/8" = 1'-0"B1 (ANSI 604) RESTROOM STALL LAYOUT
3/8" = 1'-0"C1 (ANSI 604) WHEELCHAIR ACCESSIBLE COMPARTMENT
3/8" = 1'-0"B6 ACCESSIBLE UNIT - LAVATORY X
3/8" = 1'-0"C4 PLUMBING FIXTURE
3/8" = 1'-0"D5
WHEELCHAIR ACCESSIBLE COMPARTMENT TOE CLEARANCE (ANSI
604)
NOT APPLICABLE NOT APPLICABLE
1/2" = 1'-0"A2 (ANSI 604) ACCESSIBLE UNIT - GRAB BAR LOCATIONS
1" RAISED WHITE
LETTERS, ON RED
BACKGROUND
SANDBLASTED, CLEAR
ANODIZED ALUMINUM
SIGN W/ 4 EPOXY
PIN ANCHORS
FDC SIGN
FIRE
DEPARTMENT
CONNECTION
IN CASE OF
FIRE
DO NOT USE ELEVATORS
USE STAIRWAYS
ELEVATOR SIGN
- SETON STYLE NO. 25639 OR EQ.
2"
LETTERS
1" LETTERS,
TYP. UNO
1" LETTERS,
TYP. UNO
MAXIMUM
OCCUPANCY
NOT TO EXCEED
370 PERSONS
OCCUPANT LOAD SIGN
- SETON STYLE NO. 43355 OR EQ.
STAIR
WOMEN
MEN
ROOM NAME
315
PICTOGRAMS (SYMBOL)
RAISED 1/32" OFF FACE, TYP.
3/4" HIGH LETTERING,
RAISED 1/32", TYP.
GRADE 2 BRAILLE
APPLIED TO FACE, TYP.
315
SANDBLASTED, CLEAR
ANODIZED
ALUMINUM PANEL
3/4" HIGH LETTERING,
RAISED 1/32", TYP.
GRADE 2 BRAILLE
APPLIED TO FACE, TYP.
SANDBLASTED, CLEAR
ANODIZED
ALUMINUM PANEL
SANDBLASTED, CLEAR
ANODIZED
ALUMINUM PANEL
SANDBLASTED, CLEAR
ANODIZED
ALUMINUM PANEL
SANDBLASTED, CLEAR
ANODIZED
ALUMINUM PANEL
TRANSPARENT, MOLDED
POLYCARBONATE
UPDATEABLE PANEL
3/4" HIGH LETTERING,
RAISED 1/32", TYP.
GRADE 2 BRAILLE
APPLIED TO FACE, TYP.
SIGNAGE LEGEND
3/4" HIGH LETTERING,
RAISED 1/32", TYP.
GRADE 2 BRAILLE
APPLIED TO FACE, TYP.
PICTOGRAMS (SYMBOL)
RAISED 1/32" OFF FACE, TYP.
PICTOGRAM (SYMBOL)
RAISED 1/32" OFF FACE, TYP.
ROOM NAME
315
SANDBLASTED, CLEAR
ANODIZED
ALUMINUM PANEL
3/4" HIGH LETTERING,
RAISED 1/32", TYP.
UNISEX
SANDBLASTED, CLEAR
ANODIZED
ALUMINUM PANEL
3/4" HIGH LETTERING,
RAISED 1/32", TYP.
GRADE 2 BRAILLE
APPLIED TO FACE, TYP.
PICTOGRAMS (SYMBOL)
RAISED 1/32" OFF FACE, TYP.
6"
6"
6"
6"
6"
6"
8
1
/
2
"
2
1
/
2
"
8
1
/
2
"
6"
6"
2
1
/
2
"
6
"
2
1
/
2
"
6
"
9"
9"
5"
H
I
G
H
1'-0" WIDE
8
1
/
2
"
6"
2
1
/
2
"
6
"
6" WIDE
7"
H
I
G
H
1'-0" WIDE
8
1
/
2
"
H
I
G
H
BRAILLE AREA, TYP
2"
OR AS REQ'D
8"±
NOTE:
-COLOR AS SELECTED BY ARCHITECT
-CHARACTER SIZE AND BRAILLE
LOCATION PER ANSI A117.1, CH. 7
EXIT SIGN SIGNAGE
BY OWNER
SIGN
60" MAX
48" MIN
ACTIVE LEAF INACTIVE LEAF ACTIVE LEAF ACTIVE LEAF
SIGN HEIGHT ABOVE THE FLOOR. TACTILE CHARACTERS SHALL BE 48 INCHES
MINIMUM ABOVE THE FLOOR. MEASURED TO THE BASELINE OF THE LOWEST TACTILE
CHARACTER AND 60 INCHES MAXIMUM ABOVE THE FLOOR. MEASURED TO THE
BASELINE OF THE HIGHEST TACTILE CHARACTER. (ICC/ANSI 703.3.10)
SIGN LOCATION. WHERE A TACTILE SIGN IS PROVIDED AT A DOOR. THE SIGN
SHALL BE ALONGSIDE THE DOOR AT THE LATCH SIDE. WHERE A TACTILE SIGN IS
PROVIDED AT DOUBLE DOORS WITH ONE ACTIVE LEAF. THE SIGN SHALL BE
LOCATED ON THE INACTIVE LEAF. WHERE A TACTILE SIGN IS PROVIDED AT DOUBLE
DOORS WITH TWO ACTIVE LEAVES. THE SIGN SHALL BE TO THE RIGHT OF THE
RIGHT HAND DOOR. WHERE THERE IS NO WALL SPACE ON THE LATCH SIDE OF A
SINGLE DOOR, OR TO THE RIGHT SIDE OF DOUBLE DOORS. SIGNS SHALL BE ON
THE NEAREST ADJACENT WALL. SIGNS SHALL BE ON THE NEAREST SHALL BE
LOCATED SO THAT A CLEAR FLOOR AREA 18 INCHES MINIMUM BUY 18 INCHES
MINIMUM, CENTERED ON THE TACTILE CHARACTERS, IS PROVIDED BEYOND THE
ARC OF THE ANY DOOR SWING BETWEEN THE CLOSED POSITION AND 45 DEGREE
OPEN POSITION. (ICC/ANSI 703.311)
SIGNAGE LOCATIONS
WALL CONSTRUCTION
ACCESSORY MOUNTED
OVER FINISHED WALL
GYPSUM BOARD
NOTE:
1. TYPICAL BLOCKING REQUIRED
BEHIND WALL MOUNTED
ACCESSORIES AND EQUIPMENT
(OPTION 1) 20 GA x 6" FLAT STEEL
BLOCKING. ATTACH W SELF TAPPING
PAN HEAD SCREWS
(OPTION 3) SISTER 16 GA. STL.
STUD ATTACH FIXTURE TO
SISTER STUD W/ SELF
TAPPING SCREWS OR
ANCHORS
(OPTION 2) INLAID FIRE
RETARDANT WOOD
BLOCKING (COMPLY WITH
IBC 2006 2303.2)
STUDS SHOWN @ 16" O.C. SEE WALL TYPES
FOUNTAIN
20 GA x 6" FLAT STEEL
BLOCKING
20 GA x 6" FLAT STEEL
BLOCKING
16 GA SUPPORT STUD
FOR STL. ANGLE
BRACING
WATER
COOLER/
FOUNTAIN
PROVIDE FULL VERTICAL BLOCKING AT
CENTERLINE OF URINAL
NAPKIN
TAMPON
HAND DRYER
20 GA x 6" FLAT STEEL
BLOCKING
TYPICAL BLOCKING DETAILS
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
10/28/22
G015
Code
Required
Signage &
Details
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
e
ir
ir
ir
90
95
91
92
93
94
96
97
9
8
95
92
93
94
96
97
98
10
0
90
95
91
92
93
94
96
99
99
13
.
5
'
11.9'
100
P01
H
O R R O C
K
S
E
N
G I N E E R
SN
0 10'20'
SCALE: 1" = 10'
1.CONTOURS ARE SHOWN AT 1' INTERVALS.
SHEET NOTES
WEST ENTRANCE
EAST ENTRANCE
MC
K
A
Y
L
I
B
R
A
R
Y
MCKAY LIBRARY
DEMOLITION/EXISTING KEY NOTES:
EXISTING CONCRETE SIDEWALK TO BE REMOVED
EXISTING LANDSCAPE PLANTER TO BE REMOVED (AS NEEDED)
EXISTING TREE TO BE GROUND DOWN AND COVERED
EXISTING LANDSCAPING TO BE REMOVED (AS NEEDED)
EXISTING GUARDRAIL TO BE REMOVED. CUT OFF AT BASE AND
TO BE FILLED AND COVERED WITH NON-SHRINK GROUT
D01
D02
D03
D04
D05
PROTECT IN PLACE NOTES:
EXISTING CONCRETE SIDEWALK
EXISTING TREE
EXISTING LANDSCAPING
EXISTING LIGHT POLE
EXISTING LANDSCAPE PLANTER
EXISTING BUILDING
EXISTING ELECTRICAL BOX
EXISTING IRRIGATION BOX
EXISTING STORM DRAIN INLET
EXISTING HAND RAILING
EXISTING RETAINING WALL
EXISTING TRELLIS STRUCTURE
EXISTING GATE
P01
P02
P03
P04
P05
P06
P07
P08
P09
P10
P11
P12
P13
P06
D02
P06
P06
P06
P01
P01
P01
P01
P02
P02
P02
P02
P02
P02
P02
P02
P02
P03
P03
P03
P03 P03
P04
P04
P05 P05
P07
P08
P08
P08
P09P09
D01
D01
D01
D02
D03
D04
APPROX. 220 SF
(VERIFY SIZE WITH
SITE PLAN)
P01
APPROX. 160 SF EXTERIOR
CONCRETE IN FRONT OF DOORS;
SEE ARCH PLANS FOR INTERIOR
CONCRETE REMOVAL
APPROX. 270 SF
D04D05
D05
P11 P11
P12P12
P11
P11
P11
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
C.2.0
EXISTING
CONDITIONS &
DEMO
ID-LD-4745-22
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
BID SET
D05
D05
D05
D04D04
D03
D03
D02 D02
D05
D05
20
'
10.8'
D04
D04
D04
D04
P13
BUSHES TO BE
REMOVED AS NEEDED
10/31/2022
DN
1
J
L
M
N
P
Q
1.5
STUDY (MED)
124
STUDY (MED)
125
VESTIBULE
1-F
e
ir
ir
ir
90
95
91
92
93
94
96
97
9
8
95
92
93
94
96
97
98
10
0
90
95
91
92
93
94
96
99
99
10.8'
20
'
R4
'
R4
'
10.9'
12
.
2
'
METOC: 94.80
METOC: 93.53
TOC: 94.17
TOC: 94.57
TOC: 95.16
TOC: 94.96
TOC: 96.01
TOC: 96.01
TOC: 97.06
TOC: 97.38
TOC: 97.38
TOC: 96.69
TOC: 99.39
TOC: 99.50
9.1'
R
1
2
0
'
21.9
'
R
2
0
'
9'
1
0
'
9
6
94
94
95
97
METOC: 94.19
METOC: 98.91 METOC: 99.00
METOC: 100.00
METOC: 99.91
METOC: 99.90
99
TOC: 97.48
TOC: 97.48
4.0%
5.0%
4.8%
2.0%
5.7%
6
.
1
%
TOC: 97.06
TOC: 96.69
14131211109
1
0
0
16.4'
5.
9
'
19.1'
11
.
9
'
METOC: 99.63 METOC: 99.73
METOC: 99.70
METOC: 99.90
METOC: 99.90
METOC: 99.63
TOC: 99.76
METOC: 100.00 METOC: 100.00
METOC: 99.70
METOC: 99.73
METOC: 99.53
METOC: 99.50
METOC: 99.62
METOC: 100.10
5.
0
%
1
.
8
%
1
.
8
%
RE
F
.
RE
F
.
DN
1
1
16
16
15
15
14
14
13
13
12
12
11
11
10
10
9
9
8
87
K
H
F
D
B
A
G
J
LL
M
M
NN
PP
Q
Q
E
C
2
2
3
3
4
4
5
5
1.5
1.5
6
6
e
ir
ir
ir
HANDRAIL HEIGHT, MEASURED
ABOVE THE STAIR TREAD NOSINGS,
OR FINISH SURFACE OF THE RAMP
SLOPE, SHALL BE UNIFORM AND
INSTALLED AT 36 INCHES.
IBC 2018 - 1014.2
THE HANDRAIL SHALL EXTEND HORIZONTALLY
NOT LESS THAT 12 INCHES BEYOND THE TOP
RISER AND CONTINUE TO SLOPE FOR THE DEPTH
OF ONE TREAD BEYOND THE BOTTOM RISER.
IBC 2018 - 1014.6
HANDRAILS WITH A CIRCULAR
CROSS SECTION TO HAVE A
DIAMETER OF 1 1
2" AND SHALL
BE PLAS-COAT COLOR GREY
613. HANDRAIL TO TURN 90°
TO CONNECT TO POST
SUPPORT
3" SLEEVE TO BE PLACED IN
THE CONCRETE. TO BE
SEALED WITH AN EXTERIOR
NON-SHRINK GROUT
42
"
1' TYP
1' TYP
VERTICAL BRACES PLACED AT
A 5' MINIMUM DISTANCE AND
EQUALLY SPACED.
36
"
36
"
SQUARE 1 1
2" X 1 1
2" TOP
RAIL
INSTALL SKATEBOARD
DETERRENT IN CENTER OF
RAILING.
1' TYP
1' TYP
97.0'
97.5'
98.0'98.5'
99.0'99.5'
ADD BRACE SUPPORT FROM
TOP RAIL TO BOTTOM OF
HANDRAIL
4" MAX
TYP
11
2" SQUARE STEEL SUPPORT POST
AND RAIL
GUARDRAIL TO BE PLAS-COATED IN
COLOR GREY 613, ALL SECTIONS TO
BE PRE-FABRICATED
1
2" SQUARE STEEL PIPE BALUSTER
EXISTING CONCRETE
SEE STRUCTURAL DETAIL 3, SHEET
C.3.0
5' - 0" MAX O.C.
3"
3'
-
6
"
GUARDRAILS TO BE JOINED WITH
3 INCH PLAS-COATED SLEEVE.
SLEEVE TO BE SCREWED INTO
GUARDRAILS WITH ZINC COATED
OR GALVANIZED SCREWS.
SCALE: NTS-
1A SECTION
1A
-
6"
MI
N
.
3"
MIN.
5"
GUARDRAIL POST @
5'-0" MAX SPACING
(BY OTHERS)
PL 12"x8"x4" w/ (2) 12" Ø
SIMPSON SET-3G DRILL
& EPOXY ANCHORS,
EMBED 3"3"
EM
B
E
D
NOTES:
ALL STEEL ELEMENTS NEED TO BE ZINC COATED OR
GALVANIZED TO PROTECT AGAINST CORROSION.
3"
MI
N
.
11 2"5"11 2"
2"
4"
8"
GUARDRAIL POST (BY OTHERS)
12" Ø ANCHOR BOLT, TYP
FULL LAP
2'-4"
FUL
L
L
A
P
2'-4"
#5 DOWEL @ 12" O.C.
1'
-
0
"
4'
-
0
"
M
A
X
5'
-
0
"
M
A
X
1'-2"10"
2'-0"
#4 DOWEL @
18" O.C.
#4 DOWEL @ 18" O.C.
#4 BARS @
12" O.C. DRILL
& EPOXY w/ 9"
EMBED, TYP
1'-8"
STD
#4 DOWEL @ 18" O.C.
#4 @ 12"
O.C., E.F.
EXISTING PLANTER WALL
EXISTING
PLANTER WALL
EXISTING
PLANTER WALL
#4 @ 12" O.C., E.F.
#4 BARS @ 12" O.C. DRILL
& EPOXY w/ 9" EMBED, TYP
ST
D
2" CLR
TYP
2" CLR
TYP
3"
CL
R
2'-0"
10"
H
O R R O
C
K
S
E
N
G I N E E R
SN
0 10'20'
SCALE: 1" = 10'
WEST ENTRANCE
EAST ENTRANCE
MC
K
A
Y
L
I
B
R
A
R
Y
MCKAY LIBRARY
VICINITY MAP
MCKAY LIBRARY
PROPOSED WEST ENTRANCE
PROPOSED EAST ENTRANCE
SITE PLAN KEYNOTES
INSTALL 6" THICK SIDEWALK, (WIDTH PER PLAN) PER ISPWC SD-709, 714,
714A, 714B UNLESS OTHERWISE NOTED. USE TITAN MIX FROM IMC
INSTALL 6" THICK SIDEWALK WITH HYDRONIC HEATING, (WIDTH PER PLAN)
PER ISPWC SD-709, 714, 714A, 714B UNLESS OTHERWISE NOTED (SEE MECH.
PLANS FOR HYDRONIC HEATING DETAILS). USE TITAN MIX FROM IMC
INSTALL CONCRETE END CAP WALL. SEE DETAIL 5, THIS SHEET. END CAP TO
MATCH EXISTING PLANTER AESTHETICS.
INSTALL CONCRETE STAIRS PER ISPWC SD-713. SEE DETAIL 1, THIS SHEET,
FOR ADDITIONAL DETAILS.
TIE INTO EXISTING CONCRETE, SAWCUT AS REQUIRED
INSTALL LANDSCAPE PER LANDSCAPE PLAN
INSTALL HANDRAIL PER UNIVERSITY STANDARDS. SEE DETAIL 1, THIS SHEET
INSTALL LIGHT POLE (SEE ELECTRICAL PLANS FOR DETAILS)
INSTALL GUARDRAIL PER UNIVERSITY STANDARDS. SEE DETAILS 2 & 3, THIS
SHEET.
INSTALL CONCRETE STAIRS PER ISPWC SD-713. SEE DETAIL 4, THIS SHEET,
FOR ADDITIONAL DETAILS.
01
02
03
04
05
06
07
08
09
10
01
01
01
02
02
03
03
05
05
05
05
05
05 05
05
06
06
04
07
07
09
STEAM LINES & HIGH
VOLTAGE ELETRICAL IN
AREA, COORD. W/ OWNER
FOR EXACT LOCATIONS
08
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
C.3.0
SITE PLAN &
GRADING
ID-LD-4745-22
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
BID SET
(2) 3-INCH SLEEVES (COORD.
EXACT LOCATION WITH
OWNER)
02
09
09
09
09
CONTINUE NEW GUARDRAIL
BEYOND PATIO AREA
STAMP CONCRETE AT
SLEEVE CROSSING ON BOTH
SIDES (STAMP PROVIDED BY
OWNER)
STAMP CONCRETE AT
SLEEVE CROSSING ON BOTH
SIDES (STAMP PROVIDED BY
OWNER)
(2) 3-INCH SLEEVES (COORD.
EXACT LOCATION WITH
OWNER)
STAMP CONCRETE AT
SLEEVE CROSSING ON BOTH
SIDES (STAMP PROVIDED BY
OWNER)
0101
02
08
SCALE:
1
C.3.0
STAIR & RAILING
NTS
SCALE:
2
C.3.0
GUARDRAIL DETAIL
NTS
SCALE:
3
C.3.0
GUARDRAIL POST CONNECTION DETAIL
NTS
SCALE:
4
C.3.0
STAIR CONNECTION TO EX. CONCRETE
NTS
SCALE:
5
C.3.0
PLANTER BOX DETAIL
NTS
(2) 3-INCH SLEEVES (COORD.
EXACT LOCATION WITH
OWNER)
10/31/2022
DN
1
J
L
M
N
P
Q
1.5
STUDY (MED)
124
STUDY (MED)
125
VESTIBULE
1-F
e
ir
ir
ir
14131211109
RE
F
.
RE
F
.
DN
1
1
16
16
15
15
14
14
13
13
12
12
11
11
10
10
9
9
8
87
K
H
F
D
B
A
G
J
LL
MM
NN
PP
QQ
E
C
2
2
3
3
4
4
5
5
1.5
1.5
6
6
e
ir
ir
ir
H
O R R O C
K
S
E
N
G I N E E R
SN
0 10'20'
SCALE: 1" = 10'
WEST ENTRANCE
EAST ENTRANCE
MC
K
A
Y
L
I
B
R
A
R
Y
MCKAY LIBRARY
VICINITY MAP
MCKAY LIBRARY
PROPOSED WEST ENTRANCE
PROPOSED EAST ENTRANCE
2
3
6
6
1
4
SHRUBS BOTANICAL / COMMON NAME SIZE QTY
CALAMAGROSTIS X ACUTIFLORA `KARL FOERSTER`1 GAL 6
FEATHER REED GRASS
EUONYMUS ALATUS `COMPACTUS`5 GAL 4
COMPACT BURNING BUSH
PLANT SCHEDULE
77
1
SYMBOL DESCRIPTION QTY
PLANTER BED AREA. MATCH EXISTING TOP DRESSING IN 458 SF
COLOR, TEXTURE, AND DEPTH.
MAINTAIN EXISTING SHOVEL CUT BED LINE
REVISE BED LINE, TIE INTO EXISTING
EXISTING SHOVEL CUT BED LINE TO REMAIN
REPAIR/REPLACE EXISTING TURF SOD AND IRRIGATION. SOD 1,560 SF
REMOVED FROM WALKWAY MAY BE REUSED IF APPROVED
BY OWNER. ENSURE A MINIMUM OF 4" OF CLEAN TOPSOIL
UNDER ALL NEW SOD.
CONTRACTOR SHALL REPALCE EXISTING ANNUAL PLANTS IN
RAISED PLANTERS AT A 1:1 RATIO FOR THOSE REMOVED OR
DISTURBED DURING CONSTRUCTION. COORDINATE WITH
OWNER FOR PLANT SELECTION.
1
2
3
4
6
7
REFERENCE NOTES SCHEDULE
1.LANDSCAPE CONTRACTOR IS RESPONSIBLE FOR VERIFYING
QUANTITIES OF ALL MATERIALS FOR BIDDING AND INSTALLATION
PURPOSES. IF DISCREPANCIES EXIST, THE PLAN SHALL DICTATE
QUANTITIES TO BE USED.
2.PLANT MATERIAL TO BE INSTALLED PER PLANT LEGEND. IF
SUBSTITUTIONS ARE WANTED, PROPOSED CHANGES MUST BE
SUBMITTED TO THE LANDSCAPE ARCHITECT FOR APPROVAL PRIOR
TO PLANTING.
3.TOPSOIL TO BE IMPLEMENTED AT THE FOLLOWING DEPTHS:
3.1.6" DEPTH IN ALL PLANTER BED AREAS
3.2.4" DEPTH IN ALL TURF SOD AREAS
3.3.4" DEPTH IN ALL NEW SEED AREAS.
3.4.2" DEPTH IN ALL RESTORATION AREAS THAT WERE PREVIOUSLY
VEGETATED.
4.LANDSCAPE ROCK AND BARK MULCH COLOR AND TYPE TO BE
APPROVED BY OWNER. SUBMIT SAMPLES FOR APPROVAL PRIOR TO
INSTALLATION. MULCH MATERIAL SHALL BE IMPLEMENTED IN ALL
PLANTER BED AREAS INDICATED ON THE PLANS AT THE FOLLOWING
DEPTHS:
4.1.1-2" DIAMETER FRACTURED STONE : 4"
4.2.2-4" DIAMETER FRACTURED STONE: 4"
4.3.STONE LARGER THAN 4" IN DIAMETER: DEPTH SHALL BE TWICE
THE DIAMETER OF THE SMALLEST STONE IN THE SPECIFIED
GRADATION.
4.4.1-2" COBBLE MULCH: 4"
4.5.2-4" COBBLE MULCH: 6"
4.6.PULL MULCH MIN. OF 3" AWAY FROM BASE OF ALL PERENNIALS
AND SHRUBS AND MIN. 6" AWAY FROM ALL TREES.
5.INSTALLATION SHALL COMPLY WITH ALL NATIONAL, STATE AND LOCAL
LAWS AND ORDINANCES.
6.ALL MATERIALS SHALL BE NEW AND WITHOUT FLAWS OR DEFECTS OF
THE QUALITY AND PERFORMANCE SPECIFIED, AND SHALL MEET THE
REQUIREMENTS OF THIS SYSTEM. USE MATERIALS AS SPECIFIED, NO
SUBSTITUTIONS SHALL BE PERMITTED WITHOUT WRITTEN
PERMISSION OF THE OWNER OR LANDSCAPE ARCHITECT
7.BASE PLAN & LOCATION OF EXISTING EQUIPMENT ARE SCHEMATIC IN
NATURE. FIELD VERIFY ALL BASE & EXISTING ELEMENTS PRIOR TO
CONSTRUCTION & PROVIDE NECESSARY ADJUSTMENTS.
8.ALL PLANTS SHALL BE WATERED THOROUGHLY TWICE DURING THE
FIRST 24 HOUR PERIOD AFTER PLANTING. ALL PLANTS SHALL THEN
BE WATERED ON A REGULAR SCHEDULE DURING THE FIRST
GROWING SEASON.
9.THE CONTRACTOR SHALL WARRANTY ALL PLANT MATERIAL FOR
ONE-YEAR AFTER DATE OF FINAL ACCEPTANCE.
10.THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE VERIFICATION
AND AVOIDANCE OF ALL UNDERGROUND UTILITIES DURING THE
INSTALLATION OF LANDSCAPE AND IRRIGATION ELEMENTS. SHOULD
ANY DAMAGE OCCUR TO UNDERGROUND UTILITIES THE
CONTRACTOR SHALL REPLACE OR REPAIR THE DAMAGE AT NO
ADDITIONAL COST TO THE OWNER.
11.ALL IMPACTED OR NEW LANDSCAPE AREAS SHALL HAVE IRRIGATION
REPAIRED BY THE CONTRACTOR TO ENSURE COMPLETE COVERAGE.
ADDITIONAL HEADS, PIPING, VALVES, AND TRENCHING MAY BE
NECESSARY TO ENSURE COVERAGE WITHOUT OVER-SPRAY ONTO
HARDSCAPE AREAS. MATCH EXISTING IRRIGATION TYPE AND
MANUFACTURER.
12.CONTRACTOR IS RESPONSIBLE TO MAINTAIN THE HEALTH OF ALL
PLANT MATERIAL INCLUDING TURF GRASS, PLANTS, SHRUBS, AND
TREES DURING CONSTRUCTION ACTIVITIES. THIS MAY INCLUDE
TEMPORARY WATERING TO ENSURE PLANT HEALTH. THIS CARE IS TO
BE CONSIDERED INCIDENTAL TO THE LANDSCAPE SCOPE OF WORK
AND IS TOT BE COMPLETE AT NO ADDITIONAL COST TO THE OWNER.
GENERAL LANDSCAPE NOTES
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
L.1.0
LANDSCAPE
PLAN
ID-LD-4745-22
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
BID SET
6
STRUCTURAL GENERAL NOTES
BASIS OF DESIGN
1.GOVERNING BUILDING CODE...............................................2018 IBC
2.OCCUPANCY CATEGORY.......................................................III
3.LOAD COMBINATIONS:
ASD -GRAVITY AND LATERAL.......................................1605.3.1
4.GRAVITY DESIGN:
NO CHANGE. ORIGINAL DESIGN
5.LATERAL DESIGN:
WIND DESIGN PER ASCE 7-16
ULTIMATE DESIGN WIND SPEED..................................112 MPH
EXPOSURE.....................................................................B
INTERNAL PRESSURE COEFFICIENT..........................0.18
TOPOGRAPHIC FACTOR...............................................1.00
COMPONENTS AND CLADDING FORCES SHOWN IN DETAIL A4/S003.
SEISMIC DESIGN
SEISMIC DESIGN PROCEDURE.....................................EQV LATERAL FORCE
Ss CHART VALUE............................................................0.369 g
S1 CHART VALUE............................................................0.143 g
SITE COEFFICIENT FA....................................................1.3
SITE COEFFICIENT FV....................................................1.5
SDS...................................................................................0.319 g
SD1...................................................................................0.143 g
SITE CLASS.....................................................................C
SEISMIC DESIGN CATEGORY.......................................C
IMPORTANCE FACTOR Ie...............................................1.25
REDUNDANCY FACTOR..................................................1.00
PORTION OF SNOW LOAD INCLUDED..........................20%
BUILDING PERIOD T........................................................0.615 SEC.
LATERAL FORCE RESISTING SYSTEM.........................REINFORCED MASONRY/CONCRETE SHEAR
WALLS
R........................................................................................5
OMEGA.............................................................................2.5
Cd......................................................................................3
Cs.......................................................................................0.064 g
GENERAL
1.THE GENERAL CONTRACTOR SHALL:
A.BECOME FAMILIAR WITH ALL PORTIONS OF THE CONTRACT DOCUMENTS AND INSURE THAT ALL
SUBCONTRACTORS ARE FAMILIAR WITH THOSE PORTIONS PERTAINING TO THEIR AREA OF
WORK. NO DEVIATIONS WILL BE ALLOWED UNLESS AGREED UPON BY ALL PARTIES IN
WRITING PRIOR TO CONSTRUCTION FABRICATION.
B.VERIFY ALL DIMENSIONS AND ELEVATIONS. COORDINATE ALL DOORS, WINDOWS, NON-
BEARING INTERIOR AND EXTERIOR WALLS, ELEVATIONS, SLOPES, STAIRS, CURBS, DRAINS,
RECESSES, DEPRESSIONS, RAILINGS, WATERPROOFING, FINISHES, CHAMFERS, KERFS, ETC.
C.FIELD VERIFY ALL SITE CONDITIONS AND IMMEDIATELY NOTIFY THE ARCHITECT AND
STRUCTURAL ENGINEER REGARDING ACTUAL CONDITIONS AT THE SITE WHICH ARE NOT PER
THE DRAWINGS.
D.COORDINATE ALL WORK BETWEEN THE VARIOUS TRADES AND SUBCONTRACTORS. REPORT
ANY MODIFICATIONS TO THE STRUCTURAL PORTION OF THE BUILDING BY OTHER TRADES TO
THE ARCHITECT AND STRUCTURAL ENGINEER.
E.BE RESPONSIBLE FOR SAFETY AND PROTECTION IN AND AROUND THE JOB SITE AND/OR
ADJACENT PROPERTIES.
F.REPORT PROGRESS OF WORK TO ARCHITECT AND STRUCTURAL ENGINEER.
G.COORDINATE AND VERIFY LOCATIONS AND WEIGHTS OF MECHANICAL UNITS AND/OR OTHER
EQUIPMENT OR DEVICES PRIOR TO FABRICATION AND/OR INSTALLATION OF ANY SUPPORTING
STRUCTURE. SUCH LOADS SHALL BE REPORTED TO THE ARCHITECT AND STRUCTURAL
ENGINEER FOR REVIEW. ADDITIONAL FRAMING MAY BE REQUIRED FOR THE PROPER SUPPORT
OF SUCH UNITS AND/OR EQUIPMENT. LATERAL SUPPORT FOR THE EQUIPMENT SHALL BE
PROVIDED BY EQUIPMENT INSTALLER.
H.COORDINATE AND VERIFY ROOF, FLOOR, AND WALL OPENINGS REQUIRED WITH
ARCHITECTURAL, MECHANICAL, ELECTRICAL, AND/OR OTHER DRAWINGS PRIOR TO
CONSTRUCTION. REPORT OPENINGS REQUIRED WHICH ARE NOT SPECIFICALLY SHOWN ON
THE STRUCTURAL DRAWINGS TO THE ARCHITECT AND STRUCTURAL ENGINEER FOR REVIEW.
I.COORDINATE ANY CONSTRUCTION SITUATION NOT COVERED BY THESE PLANS, GENERAL
NOTES, OR SPECIFICATIONS WITH THE ARCHITECT AND STRUCTURAL ENGINEER.
2.CONTRACT DOCUMENTS:
A.REFER TO THE SPECIFICATIONS FOR INFORMATION NOT COVERED BY THESE GENERAL NOTES
OR THE DRAWINGS.
B.DETAILS, SECTIONS AND NOTES SHOWN ON THE STRUCTURAL DRAWINGS ARE INTENDED TO
BE TYPICAL AND SHALL APPLY TO ALL SIMILAR SITUATIONS ELSEWHERE, UNLESS NOTED OR
SHOWN OTHERWISE.
C.THE CONTRACT DOCUMENTS SHALL TAKE PRECEDENCE OVER SHOP DRAWINGS UNLESS
SPECIFICALLY NOTED OTHERWISE.
D.INFORMATION ON DRAWINGS INDICATING EXISTING CONDITIONS IS BASED ON BEST PRESENT
KNOWLEDGE, BUT MAY NOT BE ENTIRELY ACCURATE AND MUST BE FIELD VERIFIED.
3.BUILDING CODE COMPLIANCE:
A.INSPECTION, TESTING, CONSTRUCTION, WORKMANSHIP AND MATERIALS SHALL CONFORM TO
THE REQUIREMENTS OF THE GOVERNING BUILDING CODE AND STANDARDS. ASTM, IBC, AND
OTHER DESIGNATIONS SHALL BE AS AMENDED TO LATEST DATE UNLESS NOTED OTHERWISE.
4.CONSTRUCTION SEQUENCE, SHORING, AND BRACING REQUIREMENTS:
A.THE GENERAL CONTRACTOR IS RESPONSIBLE FOR THE METHOD, MEANS, AND SEQUENCE OF
ALL STRUCTURAL ERECTION EXCEPT WHEN SPECIFICALLY NOTED OTHERWISE ON THE
DRAWINGS. THE CONTRACTOR SHALL PROVIDE TEMPORARY SHORING AND BRACING TO
PROVIDE ADEQUATE VERTICAL AND LATERAL SUPPORT DURING ERECTION. THIS SHORING AND
BRACING SHALL REMAIN IN PLACE UNTIL ALL PERMANENT MEMBERS ARE PLACED AND ALL
FINAL CONNECTIONS ARE COMPLETED, INCLUDING ALL ROOF AND FLOOR ATTACHMENTS.
B.SHORING AND SUPPORTING FORM WORK FOR SUSPENDED CONCRETE OR MASONRY
MATERIAL SHALL REMAIN IN PLACE AND SHALL NOT BE REMOVED UNTIL THE STRUCTURAL
MEMBERS HAVE ACQUIRED SUFFICIENT STRENGTH TO SAFELY SUPPORT THEIR OWN WEIGHT
AND ANY ADDITIONAL CONSTRUCTION, STORAGE, AND/OR OTHER LOADS TO WHICH THE MAY
BE SUBJECTED. IN NO CASE SHALL THEY BE REMOVED PRIOR TO 7 DAYS. RE-SHORING SHALL
BE IMMEDIATELY INSTALLED UPON REMOVAL OF SUCH FORMS AND SHALL REMAIN IN PLACE
UNTIL 28 DAYS AFTER PLACING OF MATERIAL OR UNTIL MATERIAL HAS REACHED ITS 28 DAY
DESIGN STRENGTH, WHICHEVER IS LONGER. DO NOT REMOVE LARGE AREAS OF SHORING
BEFORE STARTING RE-SHORING PROCEDURES.
C.NON-BEARING INTERIOR WALLS SHALL BE ADEQUATELY BRACED TO THE STRUCTURE ABOVE
WITH ALLOWANCE FOR DEFLECTION OF THE STRUCTURE ABOVE AND/OR BELOW.
5.OMISSIONS AND/OR CONFLICTS:
A.OMISSIONS IN AND/OR CONFLICTS BETWEEN THE VARIOUS ELEMENTS OF THE CONTRACT
DOCUMENTS SHALL BE BROUGHT TO THE IMMEDIATE ATTENTION OF THE ARCHITECT AND
STRUCTURAL ENGINEER AND SHALL BE RESOLVED BEFORE PROCEEDING WITH ANY WORK
INVOLVED.
B.IN CASE OF CONFLICTS IN THE STRUCTURAL WORK, THE MOST STRINGENT REQUIREMENTS, AS
DIRECTED BY THE ARCHITECT AND STRUCTURAL ENGINEER, SHALL BE IMPLEMENTED AT NO
ADDITIONAL COST TO THE OWNER.
6.MISCELLANEOUS:
A.DURING AND AFTER CONSTRUCTION, THE CONTRACTOR AND/OR OWNER SHALL KEEP THE
LOADS ON THE STRUCTURE WITHIN THE LIMITS OF THE DESIGN.
B.OBSERVATION VISITS TO THE SITE BY REPRESENTATIVES OF THE ARCHITECT AND/OR
STRUCTURAL ENGINEER SHALL NOT BE CONSTRUED AS INSPECTION NOR APPROVAL OF
CONSTRUCTION.
C.STAIRS ARE TO BE AS PER THE ARCHITECTURAL DRAWINGS.
D.ALL WORK SHALL BE DONE IN ACCORDANCE WITH OSHA REQUIREMENTS. ANY CONFLICTS
BETWEEN THESE DOCUMENTS AND OSHA REQUIREMENTS SHALL BE BROUGHT TO THE
ATTENTION OF THE ARCHITECT AND STRUCTURAL ENGINEER BEFORE PROCEEDING WITH
WORK.
CONCRETE
1.CODES AND STANDARDS:
A.CONCRETE CONSTRUCTION, WORKMANSHIP, AND MATERIALS SHALL COMPLY WITH THE
AMERICAN CONCRETE INSTITUTE (ACI) EDITIONS OF:
I.ACI 301, "SPECIFICATIONS FOR STRUCTURAL CONCRETE FOR BUILDINGS".
II.ACI 318, "BUILDING CODE REQUIREMENTS FOR REINFORCED CONCRETE", EXCEPT AS
MODIFIED BY THE IBC.
III.ACI 347, "RECOMMENDED PRACTICE FOR CONCRETE FORM WORK".
2.MATERIALS:
A.CEMENT SHALL CONFORM TO ASTM C150, PORTLAND CEMENT.
I.USE TYPE I OR II FOR EXPOSURE CLASS S0
II.USE TYPE I OR V FOR EXPOSURE CLASS S1
III.USE TYPE V FOR EXPOSURE CLASS S2 AND S3
B.HARD ROCK AGGREGATES SHALL CONFORM TO ASTM C33. LIGHTWEIGHT AGGREGATES SHALL
CONFORM TO ASTM C330.
C.WATER SHALL BE POTABLE.
D.AIR ENTRAINMENT SHALL CONFORM TO ASTM C260.
I.LIMIT AIR CONTENT TO 3% AT TROWEL FINISHED FLOOR SLABS OR FINISH PER ACI302.1R-96
"GUIDE FOR CONCRETE FLOOR AND SLAB CONSTRUCTION" WHERE AIR CONTENT IS >3%.
E.FLY ASH, CLASS F POZZOLAN SHALL CONFORM TO ASTM C618.
F.CALCIUM CHLORIDE SHALL NOT BE USED.
G.DEFORMED BAR ANCHORS (DBA) SHALL CONFORM TO ASTM A496.
H.HEADED ANCHOR STUDS (HAS) SHALL CONFORM TO ASTM A108.
I.SILICA FUME (2% TO SUSPENDED PARKING SLABS) SHALL CONFORM TO ASTM C1240
3.MIX DESIGNS:
A.ONLY ONE TYPE OF CONCRETE SHALL BE PLACED AT THE SITE AT ANY GIVEN TIME.
B.LIMIT SLUMP TO 4" MAXIMUM PRIOR TO THE ADDITION OF PLASTICIZERS AND WATER REDUCING ADD
MIXTURES. CONCRETE SUPPLIER SHALL INDICATE FINAL SLUMP OF EACH CONCRETE MIX DESIGN.
C.CONCRETE MIXES SHALL CONFORM TO THE FOLLOWING:
D. LIMIT FLY ASH TO 25% OF THE TOTAL CEMENTITIOUS MATERIAL.
E. PEA GRAVEL AGGREGATE AND/OR PLASTICIZER MAY BE USED IN CONGESTED AREAS WHEN
REQUIRED TO PROPERLY FILL ALL VOIDS AND/OR FOR WORKABILITY. (CONTRACTORS OPTION).
4.CONSTRUCTION:
A. CONCRETE SHALL BE PROPERLY VIBRATED DURING PLACEMENT.
B. PRIOR TO PLACING CONCRETE, CHECK WITH ALL TRADES TO INSURE PROPER PLACEMENT
OF OPENINGS, BLOCK OUTS, SLEEVES, CURBS, CONDUITS, BOLTS, INSERTS, EMBEDS, DOWELS,
ETC. ANCHOR BOLTS AND DOWELS SHALL BE PLACED PRIOR TO CASTING CONCRETE.
C. CONSTRUCTION JOINTS AND BULKHEADS SHALL BE FORMED WITH A KEY WAY. ALL CONTACT
SURFACES, NEW OR EXISTING, AT CONSTRUCTION JOINTS SHALL BE INTENTIONALLY
ROUGHENED TO A 1/4" AMPLITUDE PRIOR TO CASTING ADJACENT POUR.
D. GROUT SOLID AROUND ALL JOIST AND BEAM ENDS, TYPICAL UNLESS NOTED OTHERWISE.
E. OPENINGS IN FLOORS AND/OR WALLS SHALL HAVE ADDITIONAL REINFORCING AROUND ALL
SIDES OF THE OPENING EQUIVALENT TO THE BARS CUT BY THE OPENING WITH HALF ON EACH
SIDE OF THE OPENING OR 2-#5 BARS, WHICHEVER IS GREATER, UNLESS NOTED OTHERWISE.
BARS PARALLEL TO THE PRINCIPAL REINFORCING SHALL RUN FULL LENGTH OF THE SPAN.
BARS IN THE OTHER DIRECTION SHALL RUN 24 INCHES BEYOND THE EDGE OF THE OPENING
OR END WITH A STANDARD HOOK. ALSO PROVIDE 2-#5 X 4'-0" DIAGONAL BARS AT EACH
CORNER OF EACH OPENING.
F.NO PENETRATION SHALL BE ALLOWED THROUGH ANY CONCRETE BEAM, JOIST, COLUMN, PIER,
OR JAMB WITHOUT THE ARCHITECT?S AND STRUCTURAL ENGINEER'S PRIOR WRITTEN
APPROVAL. PENETRATIONS SHALL BE RE-ROUTED AS REQUIRED AT THESE LOCATIONS.
G.ALL BOLT HOLES TO BE FILLED WITH EPOXY SHALL BE WIRE BRUSHED AND CLEANED WITH
COMPRESSED AIR. FOLLOW MANUFACTURERS RECOMMENDATIONS.
5.FOOTINGS:
A.FOOTINGS SHALL BEAR ON PROPERLY PREPARED MATERIAL. SEE THE SITE PREPARATION
NOTES.
B.FOOTINGS SHALL BE CENTERED BELOW THE WALL AND/OR COLUMN ABOVE, TYPICAL UNLESS
NOTED OTHERWISE.
C.EXTERIOR FOOTINGS SHALL BEAR BELOW THE EFFECTS OF FROST.
D.PROVIDE A 2X4 BEVELED KEY WAY IN ALL CONTINUOUS WALL FOOTINGS.
E.STAGGER FOOTING CONSTRUCTION JOINTS FROM WALL CONSTRUCTION JOINTS ABOVE BY AT
LEAST 6 FEET.
F.REINFORCING IN CONTINUOUS FOOTINGS SHALL BE CONTINUOUS AT CORNERS AND/OR
INTERSECTIONS BY PROVIDING PROPER LAP LENGTHS AND/OR CORNER BARS.
G.CONTINUOUS FOOTINGS WITHOUT CONCRETE FOUNDATION WALLS ABOVE SHALL BE
REINFORCED WITH A MINIMUM OF 2-#6 LONGITUDINAL TOP BARS IN ADDITION TO REINFORCING
SPECIFIED IN THE FOOTING SCHEDULE. AT OPENINGS, PROVIDE (1) #6 TOP BAR FOR EACH
FOOT OF FOOTING WIDTH OR PORTION THEREOF, EXTEND 24" BEYOND EDGE OF OPENING,
EACH SIDE.
H.NO PENETRATIONS SHALL BE ALLOWED THROUGH ANY CONCRETE FOOTING. WHEN CONFLICTS
ARISE BETWEEN UNDERGROUND PLUMBING, UTILITIES, ETC., THE FOOTING SHALL BE STEPPED
DOWN BELOW THE CONFLICT AND A CONCRETE WALL, PIER, COLUMN ETC., SHALL BE
EXTENDED TO THE FOOTING AS REQUIRED.
I.BEARING SURFACES FOR FOOTINGS WHICH ARE, OR BECOME, UNDERMINED DURING
CONSTRUCTION SHALL BE BACKFILLED WITH A LEAN-MIX CONCRETE (2000 PSI MIN.).
6.SLABS ON GRADE:
A.INTERIOR SLABS ON GRADE SHALL BE A MINIMUM OF 4 INCHES THICK, SHALL BEAR ON A 4
INCH MINIMUM LAYER OF FREE-DRAINING GRAVEL, AND SHALL BE REINFORCED WITH #4 BARS
AT 18" O.C. BOTH WAYS, TYPICAL UNLESS NOTED OTHERWISE. PROVIDE CHAIRS WITH SAND
PLATES FOR PROPER PLACEMENT.
B.SLABS ON GRADE SHALL BE SUBDIVIDED BY CONSTRUCTION AND/OR CONTRACTION (CONTROL)
JOINTS INTO ROUGHLY SQUARES WHOSE SIDES SHALL NOT EXCEED 15 FEET IN EITHER
DIRECTION.
C.SEE ARCHITECTURAL FOR EXTERIOR SLABS ON GRADE, TYPICAL, UNLESS NOTED OTHERWISE.
REINFORCING STEEL
1.CODES AND STANDARDS:
A.REINFORCING STEEL SHALL COMPLY WITH:
I.CONCRETE REINFORCING STEEL INSTITUTE "MANUAL OF STANDARD PRACTICE".
II.AMERICAN CONCRETE INSTITUTE "DETAILING MANUAL", ACI 315 (OR SP-66).
2.MATERIALS:
A.REINFORCING STEEL SHALL BE NEW STOCK DEFORMED BARS AND SHALL CONFORM TO ASTM
A615, GRADE 60, WITH A DESIGN YIELD STRENGTH OF 60,000 PSI, EXCEPT AS NOTED BELOW.
I. DOWELS TO BE BENT IN THE FIELD DURING CONSTRUCTION SHALL BE ASTM A615, GRADE
40 OR ASTM A706, GRADE 60, "LOW-ALLOY STEEL".
II. REINFORCING TO BE WELDED SHALL BE ASTM A706, GRADE 60,"LOW-ALLOY STEEL".
B.MASONRY JOINT REINFORCING SHALL CONFORM TO ASTM 951 AND SHALL BE MANUFACTURED
FROM WIRE WHICH CONFORMS TO ASTM A82.
C.MECHANICAL SPLICE COUPLERS SHALL BE CAPABLE OF DEVELOPING 125% OF THE SPECIFIED
STRENGTH OF THE BAR.
3.CONSTRUCTION:
A.REINFORCING SHALL BE DETAILED, BOLSTERED, AND SUPPORTED PER ACI 315.
B.REINFORCING STEEL SHALL BE FREE OF LOOSE FLAKY RUST, SCALE, GREASE, OIL, DIRT, AND
OTHER MATERIALS WHICH MIGHT AFFECT OR IMPAIR BOND.
C.REINFORCING SHALL BE CONTINUOUS IN WALLS, BEAMS, COLUMNS, SLABS, FOOTINGS, ETC.
D.SPLICES IN CONTINUOUS REINFORCING SHALL BE MADE IN AREAS OF COMPRESSION AND/OR
AT POINTS OF MINIMUM STRESS, TYPICAL UNLESS NOTED OTHERWISE. LAP SPLICES SHALL
BE MINIMUM OF 40 BAR DIAMETERS LONG IN CONCRETE AND 48 BAR DIAMETERS LONG IN
MASONRY, TYPICAL UNLESS NOTED OTHERWISE. MINIMUM LAP SHALL BE 24 INCHES LONG.
DOWELS SHALL HAVE A MINIMUM OF 30 BAR DIAMETERS EMBEDMENT. TENSION SPICES
SHALL BE USED IN CONCRETE WHEN SPECIFICALLY NOTED, USE A CLASS B SPLICE. SPLICES
IN TOP BARS IN SUSPENDED SLABS AND BEAMS SHALL BE MADE AT MID SPAN. SPLICES IN
BOTTOM BARS IN SUSPENDED SLABS AND BEAMS SHALL BE MADE AT SUPPORTS.
E.BENDS SHALL BE MADE COLD. DO NOT USE HEAT. BENDS SHALL BE DONE IN THE
FABRICATOR'S SHOP UNLESS SPECIFICALLY NOTED FOR THE FIELD. DO NOT UN-BEND OR RE-
BEND A PREVIOUSLY BENT BAR.
F.REINFORCING STEEL IN CONCRETE SHALL BE SECURELY ANCHORED AND TIED IN PLACE PRIOR
TO PLACING CONCRETE AND SHALL BE POSITIONED WITH THE FOLLOWING MINIMUM CONCRETE
COVER:
CONCRETE CAST AGAINST AND PERMANENTLY
EXPOSED TO EARTH................................................................3"
CONCRETE EXPOSED TO EARTH OR WEATHER:
#6 AND LARGER........................................................................2"
#5 AND SMALLER......................................................................1-1/2"
CONCRETE NOT EXPOSED TO EARTH OR WEATHER:
SLABS AND WALLS, #11 AND SMALLER..................................3/4"
BEAMS AND COLUMNS, MAIN REINFORCING OR TIES.........1-1/2"
SLABS ON GRADE.....................................................................CENTER OF SLAB
G.REINFORCING STEEL IN MASONRY SHALL BE PLACED PRIOR TO GROUTING AND SHALL BE
PLACED, POSITIONED, AND LOCATED ACCORDING TO THE STRUCTURAL DRAWINGS. IT SHALL
BE SECURED AGAINST DISPLACEMENT AT INTERVALS NOT TO EXCEED 200 BAR DIAMETERS OR
TEN FEET.
H.NO REINFORCING SHALL BE WELDED UNLESS SPECIFICALLY NOTED AS SUCH. USE E90XX
ELECTRODES AND ASTM A706 REINFORCING. COMPLY WITH AWS D1.4 REQUIREMENTS.
I.EPOXY COATED REINFORCING BARS SHALL BE USED WHEN SPECIFICALLY NOTED. INCREASE
LAP SPLICE LENGTHS AS REQUIRED BY THE IBC AND ACI.
STRUCTURAL STEEL
1.CODES AND STANDARDS:
A.STRUCTURAL STEEL DESIGN, FABRICATION, AND ERECTION SHALL COMPLY WITH:
I.THE AMERICAN INSTITUTE OF STEEL CONSTRUCTION (AISC) "SPECIFICATION FOR
STRUCTURAL STEEL BUILDINGS (AISC 360-16)", WITH "COMMENTARY".
II.AISC "CODE OF STANDARD PRACTICE FOR STEEL BUILDINGS AND BRIDGES (AISC 303-10)"
EXCLUDING SECTIONS 1.5.1,4.4,7.5.4, AND 7.13.3.
III.AMERICAN WELDING SOCIETY (AWS-D1.1) "STRUCTURAL WELDING CODE -STEEL",
EXCLUDING ITEMS CONFLICTING WITH AISC REQUIREMENTS.
2.MATERIALS:
A.STRUCTURAL STEEL WIDE FLANGE SHAPES SHALL CONFORM TO ASTM A992. OTHER
STRUCTURAL STEEL SHAPES, PLATES, ANGLES, ETC. SHALL CONFORM TO ASTM A36.
RUSSIAN STEEL IS NOT PERMITTED.
B.HOLLOW STRUCTURAL SECTIONS SHALL CONFORM TO ASTM A500, GRADE C, WITH A MINIMUM
YIELD STRENGTH Fy = 50 KSI.
C.STRUCTURAL PIPE SHALL CONFORM TO ASTM ASTM A500, GRADE C, WITH A MINIMUM
YIELD STRENGTH Fy = 46 KSI.
D.HIGH STRENGTH BOLTS SHALL CONFORM TO ASTM A325. ANCHOR RODS SHALL HAVE
HEADED STUDS AND SHALL CONFORM TO ASTM F1554. ALL OTHER BOLTS SHALL CONFORM TO
ASTM A307 OR BETTER.
E.HEADED ANCHOR STUDS AND DEFORMED BAR ANCHORS SHALL CONFORM TO THE
MANUFACTURER'S SPECIFICATIONS.
F.ALL MEMBERS AND WELDS WHICH HAVE COMPLETE PENETRATION GROOVE WELDS SHALL
MEET THE CHARPY V-NOTCH TOUGHNESS IMPACT TEST OF 20 FOOT POUNDS AT 0 DEGREES
FAHRENHEIT AND 40 FOOT POUNDS AT 70 DEGREES FAHRENHEIT.
3.CONSTRUCTION:
A.FABRICATION SHALL BE DONE IN AN APPROVED FABRICATOR'S SHOP.
B.CAMBER IN BEAMS SHALL BE AS INDICATED ON PLANS.
C.PROVIDE A SHOP COAT OF PAINT ON ALL STEEL ITEMS, EXCEPT AT AREAS OF WELDING
AND/OR BOLTING.
D.USE HIGH STRENGTH (8000 PSI MINIMUM AT 28 DAY), NON-SHRINK, LIQUID EPOXY GROUT
BENEATH ALL STEEL BASE PLATES AND BEARING PLATES. MIX GROUT WITH SAND OR PEA
GRAVEL AS RECOMMENDED BY THE MANUFACTURER. PLACE GROUT AS SOON AS STEEL
MEMBER HAS BEEN PROPERLY POSITIONED AND ALIGNED.
E.WHERE STRUCTURAL STEEL WIDE FLANGE, PIPE, OR HOLLOW STRUCTURAL SECTIONS ARE
EMBEDDED IN CONCRETE OR MASONRY AND REINFORCING BARS BUTT TO IT, DEFORMED BAR
ANCHORS OR REINFORCING BARS WITH THE SAME SIZE AND SPACING AS THE ADJACENT
REINFORCING BARS, 48 BAR DIAMETERS LONG, SHALL BE WELDED TO THE STRUCTURAL
STEEL. THE MANUFACTURER?S WELDING PROCEDURES SHALL BE ADHERED TO.
4.BOLTED CONNECTIONS:
A.STEEL TO STEEL BOLTED CONNECTIONS SHALL BE MADE WITH ASTM A325 HIGH
STRENGTH BOLTS AND NUTS, UNLESS NOTED OTHERWISE. BOLTS SHALL CARRY THE
IDENTIFYING MARK OF THREE (3) RADIAL LINES.
B.ALL OTHER BOLTED CONNECTIONS SHALL BE MADE WITH BOLTS AND NUTS CONFORMING TO
ASTM A307 UNLESS NOTED OTHERWISE.
C.BOLTS SHALL BE 3/4"(7/8")DIAMETER, TYPICAL, UNLESS NOTED OTHERWISE. STANDARD
SPACING SHALL BE 3" O.C. AND STANDARD EDGE DISTANCE SHALL BE 1.1/2", TYPICAL, UNLESS
NOTED OTHERWISE.
D.BOLT SHALL BE BEARING TYPE CONNECTIONS WITH THREADS EXCLUDED UNLESS NOTED
OTHERWISE.
E.BOLTED CONNECTIONS SHALL BE TIGHTENED SNUG TIGHT AND SHALL
HAVE WASHERS AS REQUIRED BY AISC UNLESS NOTED OTHERWISE.
F.ENLARGING OF HOLES SHALL BE ACCOMPLISHED BY MEANS OF REAMING. DO NOT USE A
TORCH ON ANY BOLT HOLES.
5.WELDED CONNECTIONS:
A.WELDING AND GAS CUTTING SHALL BE DONE PER AWS.
B.WELDERS SHALL BE CURRENTLY CERTIFIED ACCORDING TO AWS. ALL WELDING PROCEDURES
SHALL BE PRE-QUALIFIED. WELDERS SHALL FOLLOW WELDING PROCEDURES.
C.WELDED CONNECTIONS SHALL BE MADE USING LOW HYDROGEN MATCHING FILLER MATERIAL
ELECTRODES, UNLESS NOTED OTHERWISE.
D.WELDS SHALL HAVE THE SLAG REMOVED.
E.FULL PENETRATION WELDS, SHOP OR FIELD, SHALL HAVE BACKER BARS REMOVED, BE BACK
GOUGED, AND REWELDED PER AWS TO HAVE FULL PENETRATION WELD.
COMPOSITE STEEL BEAMS
1.STUD SPACING AND PLACEMENT:
A.COMPOSITE STEEL BEAMS ARE INDICATED ON THE FRAMING PLANS WITH THE SUFFIX (##). THE
NUMBER INSIDE THE PARENTHESES INDICATES THE NUMBER OF STUDS FOR THE BEAM OR
SECTION OF BEAM. BEAMS OR SECTION OF BEAMS SHALL HAVE THE STUDS SPACED
UNIFORMLY OVER THE BEAM OR SECTION OF BEAM.
B.ALL HEADED ANCHOR STUDS SHALL CONFORM TO ASTM A-108. DIMENSIONS SHALL COMPLY
WITH AISC. USE 3/4" DIAMETER STUDS. HEADED ANCHOR STUDS SHALL EXTEND 1 1/2"
MINIMUM ABOVE THE TOP OF THE STEEL DECK AFTER WELDING. HEADED ANCHOR STUDS
SHALL BE APPLIED THROUGH THE METAL DECK TO THE TOP FLANGE OF THE STEEL SECTION
OR WELDED DIRECTLY TO THE STEEL SECTION.
C.THE MINIMUM ON CENTER SPACING OF STUD CONNECTORS SHALL BE 6 DIAMETERS ALONG
THE LONGITUDINAL AXIS OF THE SUPPORTING COMPOSITE BEAM AND 4 DIAMETERS
TRANSVERSE TO THE LONGITUDINAL AXIS OF THE SUPPORTING COMPOSITE BEAM. THE
MAXIMUM SPACING SHALL NOT EXCEED 36" ON CENTER.
2. BEAM CAMBER:
A.COMPOSITE BEAMS SHALL BE CAMBERED AS INDICATED ON THE PLANS BY C=0.00", WHICH
DENOTES THE BEAM CAMBER DIMENSION (UPWARD) IN INCHES.
B.CAMBER TOLERANCE SHALL BE +1/4", -0".
C.CONCRETE TOPPING SLABS SHALL BE SCREEDED TO A CONSTANT THICKNESS.
POST-INSTALLED ANCHORS
1.EPOXY ANCHORS:
A.THE FOLLOWING EPOXY ADHESIVES SYSTEMS SHALL BE ALLOWED:
FOR CONCRETE:
SIMPSON SET-XP
HILTI HIT-RE 500-V3
HILTI HIT-RE 100
FOR SOLID GROUTED MASONRY:
SIMPSON SET
HILTI HIT HY 200
FOR UNGROUTED MASONRY:
SIMPSON ET
HILTI HY 270
B.ANCHOR RODS SHALL BE ASTM A-307, THREADED AND GALVANIZED, AND THE DIAMETER AS
INDICATED ON PLAN.
C.SCREEN TUBES SHALL BE USED AT UNGROUTED MASONRY UNITS.
D.ALL ANCHORS SHALL BE INSTALLED PER MANUFACTURER'S INSTRUCTIONS. AS A MINIMUM BOLT
HOLES SHALL BE WIRE BRUSHED AND CLEANED WITH COMPRESSED AIR.
E.INSTALLATION OF ADHESIVE ANCHORS THAT ARE TO BE UNDER SUSTAINED TENSION LOADING IN
HORIZONTAL TO VERTICALLY OVERHEAD ORIENTATION SHALL BE DONE BY A CERTIFIED ADHESIVE
ANCHOR INSTALLER (AAI) AS CERTIFIED THROUGH ACI AND IN ACCORDANCE WITH ACI 318-2014
(Section 17.8.2.2). PROOF OF CURENT CERTIFICATION SHALL BE SUBMITTED TO THE ENGINEER FOR
APPROVAL PRIOR TO COMMENCEMENT OF INSTALLATION.
F.PER ACI 318-2014 (Section 17.1.2) ADHESIVE ANCHORS SHALL BE INSTALLLED IN CONCRETE HAVING A
MINIMUM AGE OF 21 DAYS AT TIME OF ANCHOR INSTALLATION. FOR INSTALLATIONS SOONER THAN 21
DAYS CONSULT ADHESIVE MANUFACTURER.
G.IF TEMPERATURE OF BASE MATERIAL AT TIME OF ADHESIVE INSTALLATION IS AT 45 DEGREES
(FAHRENHEIT) OR LESS, AN “ACRYLIC” (COLD WEATHER) ADHESIVE IS REQUIRED –ie DEWALT AC200+,
HILTI HY200, SIMPSON AT-XP.
2.MECHANICAL ANCHORS
A.THE FOLLOWING MECHANICAL ANCHORS SHALL BE ALLOWED:
SIMPSON TITEN HD
HILTI KWIK HUS-EZ
B.ALL ANCHORS SHALL BE INSTALLED PER MANUFACTURER'S INSTRUCTIONS. AS A MINIMUM BOLT
HOLES SHALL BE WIRE BRUSHED AND CLEANED WITH COMPRESSED AIR.
3.SUBSTITUTES: CONTRACTOR SHALL SUBMIT A WRITTEN REQUEST FOR APPROVAL TO THE
ARCHITECT AND STRUCTURAL ENGINEER.
7.SUBMITTALS:
A.THE FOLLOWING ITEMS SHALL BE SUBMITTED TO THE ARCHITECT AND STRUCTURAL ENGINEER
FOR REVIEW PRIOR TO FABRICATION, ERECTION, INSTALLATION, OR OTHERWISE BEING
INCORPORATED INTO THE WORK.
MATERIALS CERTIFICATION FOR ALL CONCRETE MATERIALS.
MIX DESIGNS FOR EACH TYPE OF CONCRETE.
MATERIALS CERTIFICATION FOR ALL MASONRY MATERIALS.
REINFORCING STEEL SHOP DRAWINGS.
STRUCTURAL STEEL SHOP DRAWINGS.
WELDING PROCEDURES AND CERTIFICATIONS.
LIGHT GAGE METAL SHOP DRAWINGS.
STEEL DECK SHOP DRAWINGS.
VENEER TIES AND ANCHORS.
B.A MINIMUM OF TWO WEEKS SHALL BE ALLOWED FOR THE REVIEW OF ALL SUBMITTALS BY THE
ARCHITECT AND STRUCTURAL ENGINEER.
C.REQUESTS FOR SUBSTITUTIONS SHALL BE SUBMITTED TO THE ARCHITECT AND STRUCTURAL
ENGINEER IN WRITING. REASON(S) FOR THE REQUEST AND COST DIFFERENTIALS SHALL BE
INCLUDED IN THE REQUESTS. SUBSTITUTIONS ARE NOT ALLOWED UNLESS APPROVED IN
WRITING BY THE ARCHITECT AND STRUCTURAL ENGINEER.
SOILS
1.SOILS REPORT BY: NOT APPLICABLE
QUALITY ASSURANCE PLAN FOR STRUCTURE
1.INSPECTION:
A.THE OWNER SHALL PROVIDE SPECIAL INSPECTION BY QUALIFIED INSPECTORS FOR THE
FOLLOWING TYPES OF CONSTRUCTION IN ACCORDANCE WITH IBC, SECTION 1704 AND 1707, THE
SPECIFICATIONS, AND THE ATTACHED TABLES INCLUDED IN THESE GENERAL NOTES.
REINFORCED CONCRETE:DURING THE CASTING OF ALL CONCRETE AND TAKING OF ALL
TEST SPECIMENS, AND SHALL VERIFY THE PLACEMENT OF ALL REINFORCING. INSPECTOR
SHALL BE ACI-II OR ICC CERTIFIED. SEE ATTACHED TABLE LABELED REQUIRED
VERIFICATION AND INSPECTION OF CONCRETE/STEEL CONSTRUCTION.
MASONRY: DURING THE PLACING OF ALL MASONRY UNITS, ALL GROUTING PROCEDURES,
AND TAKING OF ALL TEST SPECIMENS, AND SHALL VERIFY THE PLACEMENT OF ALL
REINFORCING. INSPECTOR SHALL BE ICC CERTIFIED. SEE ATTACHED TABLE LABELED
LEVEL 1/LEVEL 2 SPECIAL INSPECTION OF MASONRY CONSTRUCTION.
BOLTING: ALL HIGH STRENGTH BOLTS AND BOLTS EMBEDDED IN CONCRETE AND/OR
EPOXY. SEE ATTACHED TABLE LABELED REQUIRED VERIFICATION AND INSPECTION OF
CONCRETE/STEEL CONSTRUCTION.
WELDING: ALL SHOP AND FIELD WELDS. INSPECTOR SHALL BE AWS-QC1 CERTIFIED. SEE
ATTACHED TABLE LABELED REQUIRED VERIFICATION AND INSPECTION OF STEEL
CONSTRUCTION.
2.TESTING:
A.THE OWNER SHALL PROVIDE TESTING BY QUALIFIED TESTING AGENCIES FOR THE FOLLOWING
TYPES OF CONSTRUCTION IN ACCORDANCE WITH IBC, SECTION 1708 AND THE SPECIFICATIONS.
SOILS: COMPACTION OF STRUCTURAL FILL.
CONCRETE: STRENGTH, SLUMP, AIR, AND TEMPERATURE.
MASONRY: STRENGTH OF MORTAR, GROUT, BLOCK, AND PRISMS.
BOLTING: PROPER INSTALLATION AND CORRECT TORQUE AND/OR TENSION.
WELDING:TYPE, SIZE, LENGTH, AND QUALITY OF ALL SHOP AND FIELD WELDS BY
APPROVED METHODS. ULTRASONICALLY TEST ALL COMPLETE PENETRATION WELDS.
3.STRUCTURAL OBSERVATIONS:
A.THE STRUCTURAL ENGINEER SHALL BE NOTIFIED TO PERFORM STRUCTURAL OBSERVATIONS
AT SIGNIFICANT STAGES OF CONSTRUCTION.
B.THE STRUCTURAL ENGINEER SHALL PROVIDE A COPY OF THE OBSERVATION REPORT TO THE
ARCHITECT FOR FURTHER DISTRIBUTION.
4.THE CONTRACTOR SHALL:
A.SUBMIT A STATEMENT OF RESPONSIBILITY TO THE OWNER AND BUILDING OFFICIAL PRIOR TO
COMMENCING WORK ON STRUCTURE THAT INCLUDES AWARENESS OF THE QUALITY
ASSURANCE PLAN REQUIREMENTS, ACKNOWLEDGMENT THAT CONTROL WILL BE EXERCISED
TO OBTAIN CONFORMANCE TO CONSTRUCTION DOCUMENTS, PROCEDURES FOR EXERCISING
CONTROL, METHOD AND FREQUENCY OF REPORTING, AND IDENTIFICATION AND
QUALIFICATIONS OF PERSONNEL IN CHARGE OF CONTROL.
B.CORRECT ALL WORK FOUND TO BE DEFICIENT AT NO ADDITIONAL COST TO THE OWNER.
C.COORDINATE ALL THE REQUIRED INSPECTIONS, TESTING, AND/OR STRUCTURAL
OBSERVATIONS OF THE QUALITY ASSURANCE PLAN. DO NOT PROCEED WITH SUBSEQUENT
WORK UNTIL THE REQUIRED INSPECTIONS, TESTING, AND STRUCTURAL OBSERVATIONS HAVE
BEEN PROVIDED. NOTIFY THE ARCHITECT AND STRUCTURAL ENGINEER AT LEAST 48 HOURS
PRIOR TO ANY REQUIRED OBSERVATIONS.
D.PROVIDE COPIES OF THE DAILY INSPECTION REPORTS AND ALL TESTING RESULTS TO THE
ARCHITECT, STRUCTURAL ENGINEER, OWNER, AND BUILDING OFFICIAL.
MASONRY
1.CODES AND STANDARDS:
A.MASONRY CONSTRUCTION, WORKMANSHIP, AND MATERIALS SHALL COMPLY WITH THE
AMERICAN CONCRETE INSTITUTE (ACI) 530.1, "SPECIFICATIONS FOR MASONRY STRUCTURES",
AND SECTIONS 2103, 2104, AND 2105 OF THE IBC.
2.MATERIALS:
A.MASONRY BLOCK SHALL BE LIGHTWEIGHT CONCRETE MASONRY UNITS AND SHALL CONFORM
TO ASTM C90, GRADE N, TYPE 1, WITH A MINIMUM COMPRESSIVE STRENGTH OF 1900
PSI AT 28 DAYS FOR NET AREA.
B.MASONRY BRICK SHALL BE CLAY MASONRY UNITS AND SHALL
CONFORM TO ASTM C62 , GRADE SW, WITH A MINIMUM COMPRESSIVE
STRENGTH OF 4,000 PSI AT 28 DAYS.
C.MORTAR SHALL BE TYPE "S" AS DEFINED BY THE IBC AND SHALL CONFORM TO ASTM C270,
WITH A MINIMUM COMPRESSIVE STRENGTH OF 1800 PSI AT 28 DAYS. IT SHALL CONSIST OF 1.0
PART PORTLAND CEMENT, 0.25 TO 0.5 PARTS HYDRATED LIME OR PUTTY LIME, AND 3.5 TO 4.5
PARTS SAND. ALL MEASUREMENTS ARE PARTS BY VOLUME. NO ADDITIVES ARE ALLOWED.
D.GROUT SHALL CONFORM TO ASTM C476 WITH A MINIMUM COMPRESSIVE STRENGTH OF 2000
PSI AT 28 DAYS. IT SHALL BE OF A FLUID
CONSISTENCY AND SHALL CONSIST OF A MINIMUM OF 1.0 PART PORTLAND CEMENT, 2.25 TO 3.0
PARTS SAND, AND MAY CONTAIN AN ADDITIONAL 1 TO 2 PARTS PEA GRAVEL IF GROUT SPACES
ARE 4" OR MORE IN EVERY DIRECTION. ALL MEASUREMENTS ARE PARTS BY VOLUME. LIMIT
FLY ASH TO 15% OF THE TOTAL CEMENTITIOUS MATERIAL.
E.PRISM TESTS SHALL HAVE A MINIMUM COMPRESSIVE STRENGTH OF F'M = 1500 PSI AT 28 DAYS.
F.EPOXY SHALL CONFORM TO ASTM C881, TYPES I, II, IV, AND V, GRADE 3, CLASSES B AND C.
3.CONSTRUCTION:
A.ALL MASONRY BLOCK SHALL BE STORED UNDER COVER AT THE JOB SITE.
B.FACE SHELLS SHALL BE FULLY BEDDED.
C.ALL MORTAR JOINTS SHALL BE TOOLED CONCAVE UNLESS NOTED OTHERWISE.
D.DO NOT USE MORTAR FOR GROUT.
E.DO NOT USE ANY FROZEN MATERIAL.
F.PRIOR TO PLACING MASONRY, CHECK WITH ALL TRADES TO INSURE PROPER PLACEMENT OF
OPENINGS, BLOCK OUTS, SLEEVES, CURBS, CONDUITS, BOLTS, INSERTS, EMBEDS, DOWELS,
ETC.
G.GROUT SHALL BE POURED IN ACCORDANCE WITH LOW LIFT PROCEDURES PER ACI 530,
TYPICAL, UNLESS NOTED OTHERWISE.
H.GROUT SHALL BE CONSOLIDATED BY MECHANICAL VIBRATION DURING PLACING AND
RECONSOLIDATED AFTER EXCESS MOISTURE HAS BEEN ABSORBED BUT BEFORE
WORKABILITY IS LOST.
I.ALL CELLS WHICH CONTAIN REINFORCING, BOLTS, ANCHORS, ETC., AND AS OTHERWISE
SPECIFIED SHALL BE GROUTED SOLID. ALL CELLS WHICH ARE TO BE GROUTED SHALL BE
CLEAN AND FREE FROM DELETERIOUS MATERIALS.
J.GROUT SOLID AROUND ALL JOIST AND BEAM ENDS, TYPICAL UNLESS NOTED OTHERWISE.
K.HOLES FOR BOLTS IN MASONRY FACE OR END SHELLS SHALL HAVE A DIAMETER TWO INCHES
LARGER THAN THE BOLT DIAMETER AND THE HOLE SHALL BE FILLED WITH GROUT.
L.NO PENETRATION SHALL BE ALLOWED THROUGH ANY MASONRY BEAM, COLUMN, PIER, OR
JAMB WITHOUT THE ARCHITECT'S AND STRUCTURAL ENGINEER'S PRIOR WRITTEN APPROVAL.
PENETRATIONS SHALL BE RE-ROUTED AS REQUIRED AT THESE LOCATIONS.
M.ALL BOLTS TO BE DRILLED AND EPOXIED SHALL BE INSTALLED IN SOLID MATERIAL. AT CAVITY
LOCATIONS GROUT SOLID. ALL BOLT HOLES TO BE FILLED WITH EPOXY SHALL BE WIRE
BRUSHED AND CLEANED WITH COMPRESSED AIR. FOLLOW MANUFACTURERS
RECOMMENDATIONS.
4.WALLS:
A.MASONRY WALLS SHALL BE CONSTRUCTED UTILIZING COMMON RUNNING BOND, TYPICAL,
UNLESS NOTED OTHERWISE.
B.MASONRY WALLS SHALL BE BUILT AS AN INTEGRAL UNIT AT CORNERS AND INTERSECTIONS.
REINFORCING SHALL BE CONTINUOUS AND BACK TO BACK END SHELLS SHALL BE REMOVED IN
EACH COURSE.
C.MASONRY WALLS SHALL BE REINFORCED AS FOLLOWS, UNLESS NOTED OTHERWISE.
WALL VERTICAL HORIZONTAL
THICKNESS REINFORCING REINFORCING
(WITHOUT JOINT REINFORCING)
6"1-#5 AT 32" O.C.1-#4 AT 48" O.C.
8"1-#5 AT 32" O.C.2-#4 AT 48" O.C.
10"1-#6 AT 32" O.C.2-#4 AT 48" O.C.
12"1-#7 AT 32" O.C.2-#4 AT 48" O.C.
SEE PLANS, SCHEDULES, AND DETAILS FOR OTHER REINFORCING REQUIREMENTS.
D.PLACE VERTICAL REINFORCING IN THE CENTER OF THE WALL UNLESS EACH FACE IS
SPECIFIED OR UNLESS NOTED OTHERWISE.
E.VERTICAL REINFORCING SHALL BE DOWELED TO CONCRETE FOOTING OR FOUNDATION WALL
BELOW AND TO STRUCTURE ABOVE WITH THE SAME SIZE BAR AND SPACING, TYPICAL,
UNLESS NOTED OTHERWISE.
F.PROVIDE VERTICAL REINFORCING IN GROUTED CELL AT ALL CORNERS AND INTERSECTIONS.
G.PROVIDE CORNER BARS AT ALL INTERSECTIONS AND CORNERS. USE SAME SIZE BAR AND
SPACING AS THE HORIZONTAL REINFORCING.
H.HORIZONTAL REINFORCING SHALL TERMINATE AT THE ENDS OF WALLS AND AT OPENINGS WITH
A STANDARD HOOK.
I.HORIZONTAL REINFORCING SHALL OCCUR AT THE TOP AND BOTTOM COURSE OF ALL MASONRY
WALLS EXCEPT THE BOTTOM COURSE HORIZONTAL REINFORCING MAY BE OMITTED WHEN THE
WALL IS DOWELED TO A CONCRETE FOUNDATION WALL BELOW.
J.OPENINGS IN WALLS WHICH EXCEED 24 INCHES IN EITHER DIRECTION SHALL BE REINFORCED
WITH A MINIMUM OF 2-#5 BARS IN GROUTED SPACE ON ALL SIDES OF THE OPENING, TYPICAL,
UNLESS NOTED OTHERWISE. VERTICAL BARS SHALL EXTEND THE FULL HEIGHT OF THE WALL
BETWEEN SUPPORTS. HORIZONTAL BARS SHALL EXTEND A MINIMUM OF 24 INCHES BEYOND
THE EDGES OF THE OPENING.
K.PENETRATIONS THROUGH ANY MASONRY WALL SHALL BE BUILT INTO THE WALL AS THE WALL
IS BEING CONSTRUCTED AND SHALL BE REVIEWED BY THE ARCHITECT AND STRUCTURAL
ENGINEER PRIOR TO INSTALLATION.
L.CONSTRUCTION JOINTS IN REINFORCED MASONRY WALLS SHALL NOT OCCUR AT THE EDGE OF
BEAM SUPPORTS AND SHALL BE PROVIDED PER THE ARCHITECTURAL DRAWINGS.
M.WHERE HORIZONTAL REINFORCING BARS JOIN CONCRETE WALLS, COLUMNS, OR PILASTERS,
REINFORCING SHALL BE CONTINUOUS. ALSO, A KEY SHALL BE PROVIDED BETWEEN THE
MASONRY AND THE CONCRETE. FILL KEY WITH GROUT.
5.BEAMS:
A.BEAMS SHALL BE BUILT AS AN INTEGRAL PART WITH THE SUPPORT. NO TOOTHING OR
DOWELING ONLY WILL BE PERMITTED. MASONRY UNITS WITH ONE END OPEN-ENDED ("A"
BLOCKS) SHALL BE USED IN ALL MASONRY BEAMS. BACK-TO-BACK END SHELLS ARE NOT
ALLOWED. GROUT ALL MASONRY BEAMS SOLID FOR FULL DEPTH AND WIDTH SHOWN IN
MASONRY BEAM SCHEDULE.
B.REINFORCING IN THE MASONRY BEAM SCHEDULE IS IN ADDITION TO STANDARD WALL
REINFORCING.
C.HORIZONTAL REINFORCING BARS IN THE TOP OF THE MASONRY BEAM SHALL BE PLACED IN
THE TOP 4 INCHES OF THE BEAM AND SHALL EXTEND A MINIMUM OF 72 BAR DIAMETERS
BEYOND THE EDGE OF THE OPENING OR SHALL BE HOOKED IF REQUIRED.
D.HORIZONTAL REINFORCING BARS IN THE BOTTOM OF THE MASONRY BEAM SHALL BE PLACED
IN THE BOTTOM 4 INCHES OF THE BEAM AND SHALL EXTEND A MINIMUM OF 24 INCHES BEYOND
THE EDGE OF THE OPENING OR SHALL BE HOOKED IF REQUIRED.
E.VERTICAL REINFORCING BARS SHALL HOOK AROUND THE BOTTOM HORIZONTAL REINFORCING
BARS. THEY SHALL ALSO HOOK AROUND THE TOP HORIZONTAL REINFORCING BARS OR
EXTEND INTO THE WALL ABOVE THE MASONRY BEAM A MINIMUM OF 48 BAR DIAMETERS.
F.DO NOT SPLICE HORIZONTAL TOP OR BOTTOM BARS, TYPICAL UNLESS NOTED OTHERWISE.
G.FOR OPENINGS NOT SHOWN, USE SIMILAR BEAM AS SHOWN IN THAT WALL OR TYPE OF WALL
FOR SIMILAR LENGTH OPENINGS. VERIFY WITH THE STRUCTURAL ENGINEER.
H.USE THE FOLLOWING MASONRY BEAM SIZES FOR OPENINGS IN NON-BEARING MASONRY
WALLS:
WIDTH OF OPENING BEAM WIDTH BEAM DEPTH HORIZ. REINF.
(FEET)(INCHES)(INCHES)
UP TO 4'-0"SAME AS WALL 16 2 # 5 BOTT.
UP TO 8'-0"SAME AS WALL 24 2 # 5 TOP & BOTT.
UP TO 10'-0”SAME AS WALL 32 2 # 5 TOP & BOTT.
FOR WIDER OPENINGS CONTACT THE STRUCTURAL ENGINEER. SEE THE MASONRY BEAM
SCHEDULE FOR ADDITIONAL INFORMATION.
6.COLUMNS:
A.GROUT JAMBS SOLID FOR FULL HEIGHT OF WALL (FLOOR TO FLOOR AND/OR ROOF) AT SIDES
OF OPENINGS; ONE CELL FOR EACH 4'-0" OF SPAN OR PORTION THEREOF. REINFORCE WITH 2-
#5 VERTICAL BARS IN EACH GROUTED CELL WITH ONE BAR PLACED AT EACH FACE OF WALL,
TYPICAL UNLESS NOTED OTHERWISE. SEE PLANS, SCHEDULES, AND DETAILS FOR OTHER
REINFORCING REQUIREMENTS.
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # :
TBSE 22129
S001
GENERAL
NOTES
10/21/2022
Enter address here
BYUI McKay
Library
Remodel
Bid set
12242
SLAB ON GRADE 3000 0.48 145 1 - 470 F0,S0,P0,C0
WALLS 4000 0.45 145 3/4 - 564 F0,S0,P0,C0
FOOTINGS 4000 0.45 145 1 - 564 F0,S0,P0,C0
INTERIOR MEMBERS
TYPE OF MEMBER
MIN.
STRENGTH
@ 28 DAYS
(PSI)
MAX.
W/C
(RATIO)
DRY
WEIGHT
(PCF)
MAX
AGGREGTE
SIZE
(INCHES)
AIR
ENTRAIN-
MENT (%)
MIN.
CEMENT
PER YARD
(LBS)
EXPOSURE
CLASS
CONCRETE MIX DESIGN TABLE
STRUCTURAL - DRAWING INDEX
STRUCTURAL
S001 GENERAL NOTES
S101 LEVEL 1 FLOOR FRAMING
S102 LEVEL 2 FLOOR FRAMING
S103 LEVEL 3 FLOOR FRAMING
S401 PENETRATION 1ST FLOOR
S402 PENETRATION 2ND FLOOR
S403 PENETRATION 3RD FLOOR
10/28/2022
A
A
B B
VIEW A-A
VIEW B-B
EXISTING MASONRY WALL
GROUT CELL SOLID IF
NOT SOLID GROUTED
5/8"Ø BOLT
EXISTING MASONRY WALL
GROUT CELL SOLID IF
NOT SOLID GROUTED
5/8"Ø BOLT W/
WASHERS @ 24" O.C.
NOTES:
1.ALL LINTEL ANCHOR BOLTS MUST BE INSTALLED IN GROUTED CELLS. IF EXISITING CELL IS
NOT GROUTED, CUT OPENING ABOVE ANCHOR BOLT LOCATION AND GROUT SOLID.
2.THE LONG LEG OF ANGLES SHALL BE INSTALLED AT FACE OF WALL.
NEW OPENING
DOUBLE ANGLE MASONRY LINTEL,
SEE SCHEDULE
5/8"Ø BOLTS W/ WASHERS IN GROUTED
CELLS @ 24" O.C. AND ONE EACH END
DOUBLE ANGLE JAMB COLUMN
OR COLUMN, SEE SCHEDULE
TYP.
3/16
0' - 1 1/2"
NOTES:
1.PROVIDE 1" OF BEARING FOR EACH FOOT OF OPENING, 6" MINIMUM, EACH SIDE.
2.CONTRACT STRUCTURAL ENGINEER FOR ALL LINTELS WITH SPANS GREATER THAN 9 FEET.
A
A
B B
VIEW A-A
VIEW B-B
EXISTING CONCRETE WALL
5/8"Ø BOLT
EXISTING MASONRY WALL
5/8"Ø BOLT W/
WASHERS @ 24" O.C.
NOTES:
1.ALL LINTEL ANCHOR BOLTS MUST BE INSTALLED IN GROUTED CELLS. IF EXISITING CELL IS
NOT GROUTED, CUT OPENING ABOVE ANCHOR BOLT LOCATION AND GROUT SOLID.
2.THE LONG LEG OF ANGLES SHALL BE INSTALLED AT FACE OF WALL.
NEW OPENING
DOUBLE ANGLE MASONRY LINTEL,
SEE SCHEDULE
5/8"Ø BOLTS W/ WASHERS IN GROUTED
CELLS @ 24" O.C. AND ONE EACH END
DOUBLE ANGLE JAMB COLUMN
OR COLUMN, SEE SCHEDULE
TYP.
3/16
0' - 1 1/2"
FULL DEPTH STIFFENER EACH
SIDE OF BEAM. MATCH SINGLE
SHEAR PLATE THICKNESS.
STEEL BEAM.
STEEL COLUMN.
SHEAR PLATE.
STEEL BEAM.
TYP
DSW
12" TYP.
STEEL BEAM.
SINGLE SHEAR STIFFENER. ADD
TABS WHERE BEAMS OCCUR.
STEEL COLUMN.
TYP
DSW
SINGLE SHEAR PLATE.
FULL DEPTH SINGLE SHEAR
PLATE AT LOCATIONS WHERE
BEAMS ARE SAME DEPTH.
COPE JOIST FLANGES
WHERE REQUIRED.
3 SIDES
SSW
NOTES:
1.BOLTS SHALL BE ASTM A325 HIGH STRENGTH BOLTS
2.BOLT EDGE DISTANCE SHALL BE 1.1/2" MINIMUM AT ALL EDGES.
3.BOLT SPACING SHALL BE 3" MIN. BOLT SPACING MAY BE REDUCED TO 3X
BOLT DIAMETER IF REQUIRED FOR A SINGLE ROW OF BOLTS.
4.CHANNELS AND MISCELLANEOUS CHANNELS USE SIMILAR CONNECTION TO SAME DEPTH WIDE FLANGE.
5.EXTEND ANGLED SINGLE PLATES TO ALLOW FOR BOLT CLEARANCE.
6.FOR COLUMN CAP PLATES, SEE TYPICAL STEEL COLUMN CAP PLATE DETAIL.
7.WHERE COLUMNS STOP AT FLOOR OR ROOF FRAMING, BEAM SHALL BEAR ON TOP OF COLUMN AND PROVIDE CAP
PLATE ON TOP OF COLUMN, TYP.
TYP
DSW
TYP
DSW
TYP
DSW
TYP
DSW
TYP
DSW
HORIZ. STIFFENER PLATES
TOP AND BOTTOM
THICKNESS TO MATCH SPT.
TYP
DSW
TYP
DSW
SSW
1/4
BEAM WEB, COLUMN
WEB, OR COLUMN
FLANGE.
SINGLE PLATE
SINGLE PLATE
SINGLE BENT PLATE.
EXTEND AS REQ'D TO
ACHIEVE BOLT CLEARANCE.
0
°
TO
3
0°
O
V
E
R
4
5
°
BEAMS OVER COLUMN SINGLE PLATE CONNECTION
BEAM TO BEAM SINGLE PLATE CONNECTION BEAM TO BEAM SINGLE PLATE CONNECTION
BEAM TO COLUMN STIFFENER PLATE CONNECTION BEAM TO COLUMN SINGLE PLATE CONNECTION
BEAM TO COLUMN FLANGE SINGLE PLATE CONNECTION BEAM TO COLUMN WEB SINGLE PLATE CONNECTION
0° TO 30°30° TO 45°OVER 45°
HSS TUBE COLUMN.
WIDE FLANGE COLUMN.WIDE FLANGE COLUMN.
BEAM WEB, COLUMN
WEB, OR COLUMN
FLANGE.
3" TYP.
2.1/2" MAX.
SKEWED SINGLE PLATE CONNECTIONS
2.1/2" MAX.
2.1/2" MAX.2.1/2" MAX.
2.1/2" MAX.2.1/2" MAX.
COLUMN WEB.
COPE JOIST FLANGES
WHERE REQUIRED.
KNIFE PLATE THROUGH
COLUMN AT DRAG
CONNECTION ONLY
3 " M A X .
S
P
T
4"
T
Y
P
.
S
P
T
(4) 7/8"Ø BOLTS TYP.
(4) 7/8"Ø BOLTS TYP.
FULL DEPTH SINGLE SHEAR
PLATE AT LOCATIONS WHERE
BEAMS ARE HIGHER.
COPE JOIST
FLANGES WHERE
REQUIRED.
TYP
DSW
RAISED BEAM AT SINGLE PLATE CONNECTION
FULL DEPTH SINGLE SHEAR
PLATE AT LOCATIONS WHERE
JOIST HANGS BELOW BEAM.
COPE JOIST
FLANGES WHERE
REQUIRED.
TYP
DSW
LOWERED BEAM AT SINGLE PLATE CONNECTION
(2) ROWS OF SLIP CRITICAL
BOLTS AT DRAGS, TYP.
(2) ROWS OF SLIP CRITICAL
BOLTS AT DRAGS, TYP.
SSW
6" M A X.
4" AT DRAGS
S
P
T
3 1 /2 " M A X .3
0
°
T
O
4
5
°
CAP PLATE
PER DETAIL
CAP PLATE PER DETAIL
STEEL BEAM.
STEEL COLUMN.
TYP
DSW
BEAM OVER COLUMN SINGLE PLATE CONNECTION
(2) 7/8"Ø BOLTS
TYP.CAP PLATE
PER DETAIL
FULL DEPTH STIFFENER
EACH SIDE OF BEAM.
MATCH SINGLE SHEAR
PLATE THICKNESS.
1/4
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # :
TBSE 22129
S002
SCHEDULES
10/21/2022
Enter address here
BYUI McKay
Library
Remodel
Bid set
12242
OVER 10' - 0" SEE STRUCTURAL ENGINEER SEE STRUCTURAL ENGINEER SEE STRUCTURAL ENGINEER - - -
8' - 0" TO 10' - 0" L5X3½X 3/8 LLV (2) L4X3X3/8
6' - 0" TO 8' - 0" L4X3X5/16 LLV (2) L4X3X5/16
4' - 0" TO 6' - 0" L4X3X5/16 LLV (2) L4X3X5/16
UP TO 4' - 0" L4X3X1/4 LLV (2) L4X3X1/4
8" CMU 10" CMU 12" CMU 8" CMU 10" CMU 12" CMU
CLEAR OPENING DOUBLE ANGLE LINTEL SIZE DOUBLE JAMB COLUMN SIZE
LINTELS & JAMBS AROUND NEW OPENINGS IN EXISTING MASONRY WALL
3/4" = 1'-0"S002
C1
LINTELS AND JAMBS FOR NEW OPENINGS IN EXISTING
MASONRY WALL
L-3 7'-0" TO 9'-0" L6X6X1/2
L-2 5'-0" TO 7'-0" L6X6X3/8
L-1 UP TO 5'-0" L6X6X5/16
MARK CLEAR OPENING ANGLE SIZE
NON-BEARING CMU STEEL ANGLE LINTEL SCHEDULE
3/4" = 1'-0"S002
D5 SCHED LINTEL CMU
OVER 13' - 0" SEE STRUCTURAL ENGINEER SEE STRUCTURAL ENGINEER SEE STRUCTURAL ENGINEER - - -
10' - 0" TO 13' - 0" (2) L8X4X3/8 LLV (2) L8X4X3/8 LLV (2) L4X3X3/8 (2) L5X5X1/4
8' - 0" TO 10' - 0" (2) L5X3½X 3/8 LLV (2) L5X5X1/4 (2) L4X3X3/8 (2) L5X5X1/4
6' - 0" TO 8' - 0" (2) L4X3X5/16 LLV (2) L5X5X1/4 (2) L4X3X5/16 (2) L5X5X1/4
4' - 0" TO 6' - 0" (2) L4X3X5/16 LLV (2) L5X5X1/4 (2) L4X3X5/16 (2) L5X5X1/4
UP TO 4' - 0" (2) L4X3X1/4 LLV (2) L5X5X1/4 (2) L4X3X1/4 (2) L5X5X1/4
8" 10" 12" 8" 10" 12"
CLEAR OPENING DOUBLE ANGLE LINTEL SIZE DOUBLE JAMB COLUMN SIZE
LINTELS & JAMBS AROUND NEW OPENINGS IN EXISTING CONCRETE WALL
3/4" = 1'-0"S002
A1
LINTELS AND JAMBS FOR NEW OPENINGS IN EXISTING
CONCRETE WALLS
3/4" = 1'-0"S002
A4 SCHED STEEL TO STEEL
W36 (11) 7/8" Ø 7/16" 5/16" 1/2"
W33 (10) 7/8" Ø 7/16" 5/16" 1/2"
W30 (9) 7/8" Ø 7/16" 5/16" 1/2"
W27 (8) 7/8" Ø 7/16" 5/16" 1/2"
W24 (7) 7/8" Ø 7/16" 5/16" 1/2"
W21 (6) 7/8" Ø 7/16" 5/16" 1/2"
W18 (5) 7/8" Ø 5/16" 1/4" 3/8"
W16 (4) 7/8" Ø 5/16" 1/4" 3/8"
W12, W14, C12 (3) 7/8" Ø 5/16" 1/4" 3/8"
W8, W10, C8, C10 (2) 7/8" Ø 5/16" 1/4" 3/8"
BEAM SIZE NO. BOLTS PER ROW SINGLE SIDED WELD (SSW) DOUBLE SIDED WELD (DSW) SHEAR PLATE THICKNESS (SPT)
STEEL TO STEEL CONNECTION SCHEDULE
10/28/2022
1'12
2 0.
6
h
0.
6
h
0.6h
0.
6
h
0.
2
h
0.2h
3 3
3 3
1 2
2
a a
5 4 5
"BOX" ROOF PLAN "BOX" WALL ELEVATION
NOTES;
1. a = 10% OF LEAST HORIZONTAL DIMENSION OF 0.4h, WHICHEVER IS SMALLER, BU NOT LESS THAN EIGHER 4$ OF LEAST HORIZONTAL DIMENSION OR 3 FT.
2. h = MEAN ROOF HEIGHT, IN FT, EXCEP THAT EAVE HEIGHT SALL BE USED FOR ROOF SLOPES LESS THAN 10°
3. θ = ANGLE OF PLANE OF ROOF FROM HORIZONTAL, IN DEGREES.
4. PLUS AND MINUS SIGNS SIGNIFY PRESSURES ACTING TOWARDS AND AWAY FROM THE SURFACES RESPECTIVELY.
5. WALL AND PARAPET FORCES SHALL BE APPLIED INWARD AND OUTWARD AS ALTERNATIVE LOAD CASES.
6. PLAN AND ROOF ARE SKETCHES TO SHOW ZONES OF PRESSURE VARIATION. THEY DO NOT REPRESENT THE ACTUAL BUILDING CONFIGURATIONS.
.θ
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # :
TBSE 22129
S003
INSPECTIONS
10/21/2022
Enter address here
BYUI McKay
Library
Remodel
Bid set
12242
REINFORCEMENT COMPLYING WITH ASTM A
615 IN SPECIAL MOMENT FRAMES,
SPECTION STRUCTURAL WALLS, AND
COUPLING BEAMS
X VERFY THAT ASTM A 615 REINFORCING STEEL USED IN THESE
AREAS COMPLIES WITH ACI 318: 21.1.5.2 BY MEANS OF CERTIFIED
MILL TEST REPORTS. IF THIS REINFORCING STEEL IS TO BE
WELDED CHEMICAL TESTS SHALL BE PERFORMED IN ACCORDANCE
WITH ACI 318: 3.5.2.
FORMWORK X VERIFY THAT THE FORMS ARE PLACED PLUMB AND CONFORM TO
THE SHAPES, LINES, AND DIMENSIONS OF THE MEMBERS AS
REQUIRED BY THE APPROVED CONSTRUCTION DOCUMENTS.
STRENGTH VERIFICATION X VERIFY THAT ADEQUATE STRENGTH HAS BEEN ACHIEVED PRIOR
TO THE REMOVAL OF SHORES AND FORMS OR THE STRESSING OF
POST-TENSIONED TENDONS.
ERECTION OF PRECAST CONCRETE X VERIFY THAT ALL PRECAST ELEMENTS ARE LIFTED, ASSEMBLED
AND BRACED IN ACCORDANCE WITH THE APPROVED
CONSTRUCTION DOCUMENTS.
PRE-STRESSED CNCRETE X
CURING TEMPERATURE AND TECHNIQUES X VERIFY THAT THE AMBIENT TEMPERATURE FOR CONCRETE IS KEPT
AT >50°F FOR AT LEAST 7 DAYS AFTER PLACEMENT.
HIGH-EARLY-STRENGTH CONCRETE SHALL BE KEPT AT >50°F FOR
AT LEAST 3 DAYS. ACCELERATED CURING METHODS MAY BE USED
(SEE ACI 318: 5.11.3). THE AMBIENT TEMPERATURE FOR SHOTCRETE
SHALL BE >40°F FOR THE SAME PERIOD OF TIME AS NOTED FOR
CONCRETE. SHOTCRETE SHALL BE KEPT CONTINUOUSLY MOIST
FOR AT LEAST 24 HOURS AFTER SHOTCRETING. ALL CONCRETE
MATERIALS, REINFORCEMENT, FORMS FILLERS, AND GROUND
SHALL BE FREE FROM FROST. IN HOT WEATHER CONDITIONS
ENSURE THAT APPROPRIATE MEASURES ARE TAKEN TO AVOID
PLASTIC SHRINKAGE CRACKING AND THAT THE SPECIFIED
WATER/CEMENT RATIO IS NOT EXCEEDED.
CONCRETE AND SHOTCRETE PLACEMENT X
CONCRETE SAMPLING FOR STRENGTH
TESTS, SLUMP, AIR CONTENT, AND
TEMPERATURE
X
USE OF REQUIRED MIX DESIGN X VERIFY THAT ALL MIXES USED COMPLY WITH THE APPROVED
CONSTRUCTION DOCUMENTS; ACI 318-11: CH. 4,5.2-5.4; AND IBC
1904.3, 1913.2, 1913.3.
POST-INSTALLED ANCHORS OR DOWELS X ALL POST-INSTALLED ANCHORS/DOWELS SHALL BE SPECIALLY
INSPECTED AS REQUIRED BY THE APPROVED ICC-ES REPORT.
CAST-IN BOLTS AND EMBEDS X INSPECTION OF ANCHORS OR EMBEDS CAST IN CONCRETE IS
REQUIRED WHEN ALLOWABLE LOADS HAVE BEEN INCREASED OR
WHERE STRENGTH DESIGN IS USED.
REINFORCING STEEL, INCLUDING
PRESTRESSING TENDONS
X VERIFY PRIOR TO PLACING CONCRETE THAT REINFORCING IS OF
SPECIFIED TYPE, GRADE AND SIZE; THAT IT IS FREE OF OIL, DIRT,
AND RUST; THAT IT IS LOCATED AND SPACED PROPERLY; THAT
HOOKS, BENDS, TIES, STIRRUPS, AND SUPPLEMENTAL...
CONCRETE CONSTRUCTION (IBC 1705.3)
ITEM CONTIN-
UOUS PERIODIC DETAILED INSTRUCTION AND FREQUENCIES
CONCRETE CONSTRUCTION (IBC 1705.3 AND 1705.12.1)
REINFORCEMENT COMPLYING WITH ASTM A
615 IN SPECIAL MOMENT FRAMES,
SPECTION STRUCTURAL WALLS, AND
COUPLING BEAMS
X VERFY THAT ASTM A 615 REINFORCING STEEL USED IN THESE
AREAS COMPLIES WITH ACI 318: 21.1.5.2 BY MEANS OF CERTIFIED
MILL TEST REPORTS. IF THIS REINFORCING STEEL IS TO BE
WELDED CHEMICAL TESTS SHALL BE PERFORMED IN ACCORDANCE
WITH ACI 318: 3.5.2.
FORMWORK X VERIFY THAT THE FORMS ARE PLACED PLUMB AND CONFORM TO
THE SHAPES, LINES, AND DIMENSIONS OF THE MEMBERS AS
REQUIRED BY THE APPROVED CONSTRUCTION DOCUMENTS.
STRENGTH VERIFICATION X VERIFY THAT ADEQUATE STRENGTH HAS BEEN ACHIEVED PRIOR
TO THE REMOVAL OF SHORES AND FORMS OR THE STRESSING OF
POST-TENSIONED TENDONS.
ERECTION OF PRECAST CONCRETE X VERIFY THAT ALL PRECAST ELEMENTS ARE LIFTED, ASSEMBLED
AND BRACED IN ACCORDANCE WITH THE APPROVED
CONSTRUCTION DOCUMENTS.
PRE-STRESSED CONCRETE X APPLICATION OF PRESTRESSING FORCES AND GROUTING OF
BONDED PRESTRESSING TENDONS.
CURING TEMPERATURE AND TECHNIQUES X VERIFY THAT THE AMBIENT TEMPERATURE FOR CONCRETE IS KEPT
AT >50°F FOR AT LEAST 7 DAYS AFTER PLACEMENT.
HIGH-EARLY-STRENGTH CONCRETE SHALL BE KEPT AT >50°F FOR
AT LEAST 3 DAYS. ACCELERATED CURING METHODS MAY BE USED
(SEE ACI 318: 5.11.3). THE AMBIENT TEMPERATURE FOR SHOTCRETE
SHALL BE >40°F FOR THE SAME PERIOD OF TIME AS NOTED FOR
CONCRETE. SHOTCRETE SHALL BE KEPT CONTINUOUSLY MOIST
FOR AT LEAST 24 HOURS AFTER SHOTCRETING. ALL CONCRETE
MATERIALS, REINFORCEMENT, FORMS FILLERS, AND GROUND
SHALL BE FREE FROM FROST. IN HOT WEATHER CONDITIONS
ENSURE THAT APPROPRIATE MEASURES ARE TAKEN TO AVOID
PLASTIC SHRINKAGE CRACKING AND THAT THE SPECIFIED
WATER/CEMENT RATIO IS NOT EXCEEDED.
CONCRETE AND SHOTCRETE PLACEMENT X
CONCRETE SAMPLING FOR STRENGTH
TESTS, SLUMP, AIR CONTENT, AND
TEMPERATURE
X
USE OF REQUIRED MIX DESIGN X VERIFY THAT ALL MIXES USED COMPLY WITH THE APPROVED
CONSTRUCTION DOCUMENTS; ACI 318-11: CH. 4,5.2-5.4; AND IBC
1904.3, 1913.2, 1913.3.
B. MECHANICAL ANCHORS AND ADHESIVE
ANCHORS NOT DEFINED IN 4.a.
X
A. ADHESIVE ANCHORS INSTALLED IN
HORIZONTALLY OR UPWARDLY INCLINED
ORIENTATIONS TO RESIST SUSTAINED
TENSION LOADS.
X
POST-INSTALLED ANCHORS OR DOWELS. X ALL POST-INSTALLED ANCHORS/DOWELS SHALL BE SPECIALLY
INSPECTED AS REQUIRED BY THE APPROVED ICC-ES REPORT.
CAST-IN BOLTS AND EMBEDS X INSPECTION OF ANCHORS OR EMBEDS CAST IN CONCRETE IS
REQUIRED WHEN ALLOWABLE LOADS HAVE BEEN INCREASED OR
WHERE STRENGTH DESIGN IS USED.
C. INSPECT ALL OTHER WELDS X
B. INSPECT SINGLE-PASS FILLET WELDS,
MAXIMUM 5/16"
X
A. VERIFY WELDABILITY OF REINFORCING
BARS OTHER THAN ASTM A706
X
REINFORCING BAR WELDING
REINFORCING STEEL, INCLUDING
PRESTRESSING TENDONS
X VERIFY PRIOR TO PLACING CONCRETE THAT REINFORCING IS OF
SPECIFIED TYPE, GRADE AND SIZE; THAT IT IS FREE OF OIL, DIRT,
AND RUST; THAT IT IS LOCATED AND SPACED PROPERLY; THAT
HOOKS, BENDS, TIES, STIRRUPS, AND SUPPLEMENTAL...
CONCRETE CONSTRUCTION (IBC 1705.3)
ITEM CONTIN-
UOUS PERIODIC DETAILED INSTRUCTION AND FREQUENCIES
CONCRETE CONSTRUCTION (IBC 2015 1705.3)
VERIFY THAT HELICAL PILES USED MATCH
THE APPROVED SUBMITTAL
X
RECORD INSTALLATION EQUIPMENT USED,
PILE DIMENSIONS, TIP ELEVATIONS, FINAL
DEPTH, AND FINAL INSTALLATION TORQUE
X
HELICAL PILE FOUNDATIONS (IBC 1705.9):
PERFORM ADDITIONAL INSPECTIONS FOR
CONCRETE ELEMENTS
CONCRETE PER IBC 1705.3.
VERIFY PLACEMENT LOCATIONS AND
PLUMBNESS, CONFIRM ELENTDIAMETERS,
LENGTHSMBENTE END-BEARING CAPACITY.
RECORD CONCRETE OR GROUT VOLUMES
X
OBSERVE DRILLING OPERATION AND
REPORTING
X
CAST-IN-PLACE DEEP FOUNDATIONS (IBC 1705.8):
PERFORM ADDITIONAL INSPECTIONS FOR
STEEL, CONCRETE OR OTHER SPECIALTY
ELEMENTS
STEEL PER IBC 1705.2, CONCRETE PER IBC 1705.3, SPECIALTY
ITEMS PER REGISTERED DESIGN PROFESSIONAL.
VERIFY PLACEMENT LOCATION AND
PLUMBNESS, CONFIRM TYPE AND SIZE OF
HAMMER, RECORD NUMBER OF BLOWS PER
FOOT, RECORD TIP AND BUTT ELEVATIONS,
AND DOCUMENT ANDY DAMAGE TO
ELEMENT
X
OBSERVE DRILLING OPERATIONS X
DETERMINE CAPACITIES AND CONDUCT
NECESSARY LOAD TESTS
X
VERIFY MATERIALS, SIZES AND LENGTHS X
DRIVEN DEEP FOUNDATIONS (IBC 1705.7):
ITEM CONTIN-
UOUS PERIODIC DETAILED INSTRUCTION AND FREQUENCIES
FOUNDATIONS (IBC 1705.7, 1705.8, AND 1705.9)
5. OBSERVE PREPARATION OF GROUT
SPECIMENTS, MORTAR SPECIMENS,
AND/OR PRISMS
G. PLACEMENT OF AAC MASONRY UNITS
AND CONSTRUCTION OF THIN-BED MORTAR
JOINTS
F. PLACEMENT OF GROUT AND
PRESTRESSING GROUT FOR BONDED
TENDONS IS IN COMPLIANCE
E. APPLICATION AND MEASUREMENT OF
PRESTRESSING FORCE
D. PREPARATION, CONSTRUCTION, AND
PROTECTION OF MASONRY DURING COLD
WEATHER (TEMPERATURE BELOW 40°F
(4.4°C)) OR HOT WEATHER (TEMPERATURE
ABOVE 90°F (32.2°C))
C. WELDING OF REINFORCEMENT
B. TYPE, SIZE, AND LOCATION OF
ANCHORS, INCLUDING OTHER DETAILS OF
ANCHORAGE OF MASONRY TO
STRUCTURAL MEMBERS, FRAMES, OR
OTHER CONSTRUCTION
A. SIZE AND LOCATION OF STRUCTURAL
ELEMENTS
4. VERIFY DURING CONSTRUCTION:
E. CONSTRUCTION OR MORTAR JOINTS X
D. PROPORTIONS OF SITE-PREPARED
GROUT AND PRESTRESSING GROUT FOR
BONDED TENDONS
X
C. PLACEMENT OF REINFORCEMENT,
CONNECTORS, AND PRESTRESSING
TENDONS AND ANCHORAGES
X
B. GRADE, TYPE, AND SIZE OF
REINFORCEMENT AND ANCHOR BOLTS,
AND PRESTRESSING TENDONS AND
ANCHORS
X
A. GROUT SPACE X
3. PRIOR TO GROUTING, VERIFY THAT THE
FOLLOWING ARE IN COMPLIANCE:
X
F. PROPERTIES OF THIN-BED MORTAR FOR
AAC MASONRY
X X
E. PRESTRESSING TECHNIQUE X
D. LOCATION OF REINFORCEMENT,
CONNECTORS, AND PRESTRESSING
TENDONS AND ANCHORAGES
X
C. GRADE AND SIZE OF PRESTRESSING
TENDONS AND ANCHORAGES
X
B. CONSTRUCTION OF MORTAR JOINTS X
A. PROPORTIONS OF SITE-PREPARED
MORTAR
X
2. AS MASONRY CONSTRUCTION BEGINS,
VERIFY THAT THE FOLLOWING ARE IN
COMPLIANCE:
X
1. VERIFY COMPLIANCE WITH THE
APPROVED SUBMITTALS
X
ITEM CONTIN-
UOUS PERIODIC DETAILED INSTRUCTION AND FREQUENCIES
MINIMUM SPECIAL INSPECTION
VERIFICATION OF f'm AND f'AAC IN ACCORDANCE WITH SPECIFICATION ARTICLE 1.4 B PRIOR TO CONSTRUCTION, EXCEPT WHERE
SPECIFICALLY EXEMPTED BY THIS CODE
VERIFICATION OF SLUMP FLOW AND VISUAL STABILITY INDEX (VSI) AS DELIVERED TO THE PROJECT SITE IN ACCORDANCE WITH
SPECIFICATION ARTICLE 1.5 B.1.b.3 FOR SELF-CONSOLIDATING GROUT
MINIMUM TESTS
MASONRY CONSTRUCTION LEVEL B (IBC 2015 1705.4, TBS 402...
3. OBSERVE PREPARATION OF GROUT
SPECIMENTS, MORTAR SPECIMENS,
AND/OR PRISMS
M. PROPERTIES OF THIN-BED MORTAR
FOR AAC MASONRY
L. PLACEMENT OF AAC MASONRY UNITS
AND CONSTRUCTION OF THIN-BED MORTAR
JOINTS
K. APPLICATION AND MEASUREMENT OF
PRESTRESSING FORCE
X
J. PREPARATION, CONSTRUCTION, AND
PROTECTION OF MASONRY DURING COLD
WEATHER (TEMPERATURE BELOW 40°F
(4.4°C)) OR HOT WEATHER (TEMPERATURE
ABOVE 90°F (32.2°C))
X
I. WELDING OF REINFORCEMENT X
H. TYPE, SIZE, AND LOCATION OF
ANCHORS, INCLUDING OTHER DETAILS OF
ANCHORAGE OF MASONRY TO
STRUCTURAL MEMBERS, FRAMES, OR
OTHER CONSTRUCTION
X
G. SIZE AND LOCATION OF STRUCTURAL
ELEMENTS
X
F. PLACEMENT OF GROUT AND
PRESTRESSING GROUT FOR BONDED
TENDONS IS IN COMPLIANCE
X X
E. GROUT SPACE PRIOR TO GROUTING X
D. PLACEMENT OF REINFORCEMENT,
CONNECTORS, AND PRESTRESSING
TENDONS AND ANCHORAGES
X
C. PLACEMENT OF MASONRY UNITS AND
CONSTRUCTION OF MORTAR JOINTS
X
B. GRADE, TYPE, AND SIZE OF
REINFORCEMENT AND ANCHOR BOLTS,
AND PRESTRESSING TENDONS AND
ANCHORS
X
A. PROPORTIONS OF SITE-MIXED
MORTAR, GROUT AND PRESTRESSING
GROUT FOR BONDED TENDONS
X
2. VERIFY THAT THE FOLLOWING ARE IN
COMPLIANCE:
X
1. VERIFY COMPLIANCE WITH THE
APPROVED SUBMITTALS
X
ITEM CONTIN-
UOUS PERIODIC DETAILED INSTRUCTION AND FREQUENCIES
MINIMUM SPECIAL INSPECTION
VERIFICATION OF SLUMP FLOW AND VISUAL STABILITY INDEX (VSI) AS DELIVERED TO THE PROJECT SITE IN ACCORDANCE WITH
SPECIFICATION ARTICLE 1.5 B.1.b.3 FOR SELF-CONSOLIDATING GROUT
VERIFICATION OF PROPORTIONS OF MATERIALS IN PREMIXED OR PREBLENDED MORTAR, PRESTRESSING GROUT, AND GROUT
OTHER THAN SELF-CONSOLIDATING GROUT, AS DELIVERED TO THE PROJECT SITE
VERIFICATION OF f'm AND f'AAC IN ACCORDANCE WITH SPECIFICATION ARTICLE 1.4 B PRIOR TO CONSTRUCTION, EXCEPT WHERE
SPECIFICALLY EXEMPTED BY THIS CODE
MINIMUM TESTS
MASONRY CONSTRUCTION LEVEL C (IBC 2015 1705.4, TBS 402...
BRIDGING THAT DIFFERS FROM THE SJI
SPECIFICATIONS LISTED IN SECTION 2207.1
X
STANDARD BRIDGING X
BRIDGING - HORIZONTAL OR DIAGONAL
END CONNECTIONS - WELDING OR BOLTED X
INSTALLATION OF OPEN-WEB STEEL JOISTS AND JOIST GIRDERS
ITEM CONTIN-
UOUS PERIODIC DETAILED INSTRUCTION AND FREQUENCIES
OPEN WEB STEEL JOISTS AND JOIST GIRDERS (IBC 2015 1705.2.3)
DOCUMENT ACCEPTED AND REJECTED CONNECTIONS P D P D
TASK DOC. TASK DOC.
INSPECTION TASKS AFTER BOLTING (AISC 341-10 TABLE J7-3)QC QA
BOLTS ARE PRETENSIONED PROGRESSING SYSTEMATICALLY FROM THE MOST
RIGID POINT TOWARD THE FREE EDGES O - O -
FASTENER COMPONENT NOT TURNED BY THE WRENCH PREVENTED FROM
ROTATING O - O -
JOINT BROUGHT TO THE SNUG TIGHT CONDITION PRIOR TO THE PRETENSIONING
OPERATION O - O -
FASTENER ASSEMBLIES PLACE IN ALL HOLES AND WASHERS (IF REQUIRED) ARE
POSITIONED AS REQUIRED O - O -
TASK DOC. TASK DOC.
INSPECTION TASKS DURING BOLTING (AISC 341-10 TABLE J7-2)QC QA
PROPER STORAGE PROVIDED FOR BOLTS, NUTS, WASHERS, AND OTHER
FASTENER COMPONENTS O - O -
PRE-INSTALLATION VERIFICATION TESTIN BY INSTALLATION PERSONNEL
OPBSERVED FOR FASTENER ASSEMBLIES AND METHODS USED P D O D
CONNECTION ELEMENTS, INCLUDING THE APPROPRIATE FAYING SURFACE
CONDITION AND HOLE PREPARATION, IF SPECIFIED, MEET APPLICABLE
REQUIREMENTS
O - O -
PROPER BOLTIN PROCEDURE SELECTED FOR BOLT DETAIL O - O -
PROPER FASTENERS SELECTED FOR JOINT DETAIL O - O -
TASK DOC. TASK DOC.
INSPECTION TASKS PRIOR TO BOLTING (AISC 341-10 TABLE J7-1)QC QA
SFRS STEEL BOLTING INSPECTION TASKS (AISC 341 J7.1,2,3)
VERIFY PROPER MATERIALS, DENSITIES
AND LIFT THICKNESSES DURING
PLACEMENT AND COMPACTION
X
PERFORM CLASSIFICATION AND TESTING
OF COMPACTED FILL MATERIALS
X ALL MATERIALS SHALL BE CHECKED AT EACH LIFT FOR PROPER
CLASSIFICATIONS AND GRADATIONS NOT LESS THAN ONCE FOR
EACH 10,000 SQUARE-FEET OF SURFACE AREA.
VERIFY THAT SUBGRADE HAS BEEN
APPROPRIATELY PREPARED PRIOR TO
PLACING COMPACTED FILL
X PRIOR TO PLACEMENT OF COMPACTED FILL.
VERIFY EXCAVATIONS EXTEND TO PROPER
DEPTH AND MATERIAL
X PRIOR TO PLACEMENT OF COMPACTED FILL OR CONCRETE.
VERIFY SUBGRADE IS ADEQUATE TO
ACHIEVE DESIGN BEARING CAPACITY
X PRIOR TO PLACEMENT OF CONCRETE.
SOILS CONSTRUCTION (IBC 1705.6):
ITEM CONTIN-
UOUS PERIODIC DETAILED INSTRUCTION AND FREQUENCIES
SOILS CONSTRUCTION (IBC 1705.6)
3/4" = 1'-0"S003
A4 WIND - COMPONENTS AND CLADDING
5 33.3 38.7
PARAPET 4 33.3 24.2
3 -43.7 -37.1 -31.5 -27.8
2 -43.7 -37.1 -31.5 -27.8
1' -19 -19 -16 -16ROOF
1 -33.1 -28 -23.7 -20.8
4 -20.6 -16
WALLS 5 -25.3 -16
<10 50 200 >500
LOCATION TRIBUTARY AREA (ft²)
COMPONENET AND CLADDING ULTIMATE DESIGN WIND PRESSURE (PSF)
10/28/2022
LEGEND
INDICATES BRACE CONNECTION.
INDICATES CONCRETE FILLED STEEL
COLUMN, FILL WITH 4000psi SELF
CONSOLIDATING CONCRETE.HSS?? CFINDICATES CONCRETE SLAB ON GRADE,
SEE PLAN NOTES.
INDICATES FRAME ELEVATION VIEW.
INDICATES CHANGE IN SLAB ELEVATION
AND DEPTH FROM F.S.E.
OPEN INDICATES OPENING IN DECK, SEE
DETAIL ______.
INDICATES CONCRETE WALL, SEE
SCHEDULE.
1 Ref
SE?-??
INDICATES SPECIAL MOMENT FRAME
CONNECTION, SEE DETAIL C1/SE514.
INDICATES DRAG CONNECTION, SEE
STEEL TO STEEL CONNECTION
SCHEDULE.
INDICATES CANTILEVER MOMENT
CONNECTION, SEE DETAIL _______.
INDICATES SNOW DRIFT LOADS TO BE
APPLIED TO JOISTS, SEE DRIFT
SCHEDULE.
INDICATES RECESSED SLAB, SEE ARCH.
INDICATES FINISHED FLOOR SLAB
ELEVATION.
T.F. = ??'-??"INDICATES TOP OF FOOTING
ELEVATION.
INDICATES TOP OF WALL ELEVATION.
INDICATES TOP OF PIER ELEVATION.
T.W. = ??'-??"
T.P. = ??'-??"
INDICATES BAR GRATING SPAN
DIRECTION, SEE PLAN NOTES.
INDICATES EXPANSION JOINT.
CW-??
??"
INDICATES MOMENT FRAME BRACING.
INDICATES FOLDING PARTITION.
DR-?
INDICATES TOP OF STEEL ELEVATION.T.S. = ??'-??"
INDICATES WOOD SHEATHING SPAN
DIRECTION, SEE PLAN NOTES.
SW-X.X-Y INDICATES STEEL STUD SHEAR WALL
TYPE (X.X) AND SHEATHING (Y) IF
REQUIRED. ARROW INDICATES FACE OF
WALL SHEATHING SIDE OF STEEL STUD
SHEAR WALL, SEE STEEL STUD
SCHEDULES FOR SHEATHING AND
NAILING.
WW-X.X-Y INDICATES WOOD SHEAR WALL TYPE
(X.X) AND SHEATHING (Y) IF REQUIRED.
ARROW INDICATES FACE OF WALL
SHEATHING SIDE OF WOOD STUD
SHEAR WALL WHERE OCCURS, SEE
WOOD SCHEDULES FOR SHEATHING
AND NAILING.
INDICATES MASONRY WALL, SEE
SCHEDULE.
MW-??
INDICATES DETAIL SECTION VIEW.?
SE?-??
?
SE?-??INDICATES DETAIL VIEW OR ENLARGED
PLAN CALLOUT.
INDICATES CONCRETE BEAM, SEE
SCHEDULE.
CB-??
INDICATES MASONRY BEAM, SEE
SCHEDULE.
MB-??
INDICATES NUMBER OF OF TRIMMER
STUDS (T) AND KINGPOSTS (K)
F.S.E. =
INDICATES CONCRETE PIER (CP), SEE
SCHEDULESCP-?
INDICATES STEEL HSS (HSS) OR STEEL
WIDE FLANGE (W). COLUMN AND BASE
PLATE, SEE SCHEDULESBP-?BP-?HSS??W?X??INDICATES STEEL ROOF DECK SPAN
DIRECTION AND TYPE, SEE SCHEDULES
INDICATES CONCRETE ON METAL DECK
SPAN DIRECTION AND TYPE, SEE
SCHEDULES.
??-??
??-??-??
T-K
INDICATES DIFFERENT SLAB THICKNESS
INDICATES RECESS IN CONCRETE
FOUNDATION WALL
CW-??
INDICATES NON-BEARING MASONRY
WALL.
MW-??
SS INDICATES STEP IN WALL
F-????'-??"INDICATES CONCRETE FOOTING TYPE
AND TOP OF FOOTING ELEVATION.
INDICATES CONCRETE FOOTING &
FOUNDATION WALL, SEE SCHEDULES
FOR SIZE AND REINFORCING.
INDICATES ISOLATION JOINT IN SLAB ON
GRADE. SEE DETAIL
?"
INDICATESMASONRY PIER (MP) OR
COLUMN (MC), SEE SCHEDULESM?-?INDICATES MASONRY CHANNEL EMBED
PLATE, SEE MASONRY SCHEDULES.
MCE-?
INDICATES MASONRY BEARING PLATE,
SEE MASONRY SCHEDULES.
MBC-?
INDICATES CONCRETE CHANNEL
EMBED PLATE, SEE CONCRETE
SCHEDULES.
CCE-?
INDICATES CONCRETE BEARING PLATE,
SEE CONCRETE SCHEDULES.
CBP-?
INDICATES BEAM WEB OPENING WIDTH-
DEPTH-ELEVATION.
W-D-E
INDICATES OPENING FOR STRONG
POINT, SEE ARCH.
CS??
INDICATES SIZE/TYPE OF STRAP
ABOVE AND BELOW WINDOW/DOOR,
SEE TYPICAL STRAPPING OVER
WINDOWS/DOORS DETAILHDU?MST??INDICATES STRAP OR HOLD DOWN, SEE
HOLD DOWN AND STRAP SCHEDULE
ABBREVIATIONS
@ AT
AB ANCHOR BOLT
ABV ABOVE
ALT ALTERNATE
APPROX APPROXIMATE
ARCH ACHITECT
BLDG BUILDING
BLW BELOW
BM BEAM
BOT BOTTOM
BRG BEARING
BTWN BETWEEN
CJ CONSTRUCTION
/CONTROLJOINT
CJP COMPLETE JOINT
PENETRATION
CMU CONCRETE
MASONRY UNIT
COL COLUMN
CONC CONCRETE
CONST CONSTRUCTION
CONT CONTINUOUS
CONTR CONTRACTOR
CTR CENTER
D.B.DECK BEARING
D.B.A.DEFORMED BAR
ANCHOR
DBL DOUBLE
DET DETAIL
DIA (Ø)DIAMETER
DIAG DIAGONAL
DIM DIMENSION
DK DECK
DN DOWN
DWG DRAWING
DWL DOWEL
E.F.EACH FACE
E.J.EXPANSION JOINT
E.W.EACH WAY
EA EACH
EL ELEVATION
ELECT ELECTRICAL
ELEV ELEVATOR
ENG ENGINEER
EQ EQUAL
EQUIP EQUIPMENT
EXIST (E)EXISTING
EXP EXPOSED/
EXPANSION
EXT EXTERIOR
F.D.FLOOR DRAIN
F.F.FINISH FLOOR
F.S.E.FINISH FLOOR
ELEVATION
F.V.FIELD VERIFY
FDTN FOUNDATION
FIN FINISH
FL FLOOR
FT FOOT
FTG FOOTING
GA GAUGE
GALV GALVANIZED
GLB GLU-LAMINATED
BEAM
GR GRADE
G.S.N.GENERAL
STRUCTURAL
NOTES
HB HORIZONTAL
BRIDGING
HORIZ HORIZONTAL
H.S.A.HEADED STUD
ANCHORS
HSS HOLLLOW
STRUCTURAL
STEEL
HT HEIGHT
I.F.INSIDE FACE
IBC INTERNATIONAL
BUILDING CODE
ICBO INTERNATIONAL
CONFERENCE OF
BUILDING OFFICIALS
ICC INTERNATIONAL CODE
COUNCIL
IN INCHES
INSUL INSULATION
INT INTERIOR
JT JOINT
JST JOIST
K KIPS -1,000 POUNDS
KLF KIPS PER LINEAR FOOT
KSF KIPS PER SQUARE FOOT
KSI KIPS PER SQUARE INCH
LBS POUNDS
LF LINEAR FOOT
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
MAS MASONRY
MAX MAXIMUM
MECH MECHANICAL
MFR MANUFACTURER
MIN MINIMUM
MISC MISCELLANEOUS
NTS NOT TO SCALE
O OBSERVE
O.C.ON CENTER
O.F.OUTSIDE FACE
OPNG OPENING
OPP OPPOSITE
P PERFORM
PCF POUNDS PER
CUBIC FOOT
PJP PARTIAL JOINT
PENETRATION
PL PLATE
PLF POUNDS PER
LINEAR FOOT
PNL PANEL
PP PARTIAL PENETRATION
PSF POUNDS PER
SQUARE FOOT
PSI POUNDS PER SQUARE
INCH
P/T POST TENSIONED
PT POINT
REINF REINFORCING
REQ'D REQUIRED
SFRS SEISMIC FORCE
RESISTING SYSTEM
SHT SHEET
SIM SIMILAR
S.O.G.SLAB ON GRADE
SQ SQUARE
STD STANDARD
ST STEEL
STIFF STIFFENER
STRUCT STRUCTURAL
T&B TOP AND BOTTOM
T.O.TOP OF
TEMP TEMPERATURE
T.C.TOP OF CONCRETE
T.F.TOP OF FOOTING
T.S.TOP OF SLAB
T.ST.TOP OF STEEL
T.W.TOP OF WALL
TYP TYPICAL
U.N.O.UNLESSS NOTED
OTHERWISE
VERT VERTICAL
W.P.WORK POINT
W/WITH
WF WIDE FLANGE
WT WEIGHT
W.W.F.WELDED WIRE FABRIC
YD YARD
MEMBER DESIGNATION
W12X26 (25) C = 1/2"
HSS3X3X1/4
INDICATES SIZE AND TYPE OF BEAM
(HSS, WIDE FLANGE, PIPE, ETC.)
NUMBER IN PARENTHESES
INDICATES NUMBER OF EQUALLY
SPACED 3/4" Ø X 3.1/2"SHEAR STUDS
UPWARD CAMBER AT MIDSPAN OF BEAM
STANDARD STEEL CONNECTION, SEE
STEEL TO STEEL CONNECTION SCHEDULE
OR SEE PLAN FOR SPECIFIC INSTANCES
FILLED TRIANGLE INDICATES MOMENT
CONNECTION
OPEN TRIANGLE INDICATES
CANTILEVERED MOMENT CONNECTION
FILLED CIRCLE INDICATES DRAG
CONNECTION, ADDITIONAL ROW OF
BOLTS REQUIRED, SEE STEEL TO STEEL
CONNECTION SCHEDULE
INFORMATION BELOW IS FOR REFERENCE ONLY. SEE PLAN FOR
ACTUAL MEMBER SIZES, SPACING, TYPES, SHAPES, CAMBER, ETC.
SEE MOMENT CONNECTION DETAIL SHEET FOR MOMENT
CONNECTION INFORMATION.
(2) 1¾x11⅞LVL
STEEL BEAMS
WOOD
INFORMATION BELOW IS FOR REFERENCE ONLY. SEE PLAN FOR
ACTUAL MEMBER SIZES, SPACING, TYPES, SHAPES, CAMBER, ETC. SEE
STANDARD WOOD CONNECTION DETAILS FOR MORE INFORMATION.
LEADING NUMBER IN PARENTHESES
INDICATES NUMBER OF PLYS
MEMBER WIDTH
MEMBER DEPTH
MEMBER TYPE (LVL, GLULAM, LSL, ETC.)
STEEL JOISTS
18LH05
JOIST DEPTH
JOIST TYPE
DBP 88DLH 730/375
SPECIAL JOIST SHAPE OR DESIGNATION AS
REQUIRED (I.E. DPB = DOUBLE PITCH)
JOIST DEPTH
JOIST TYPE
TOTAL LOAD
LIVE/SNOW LOAD
INFORMATION BELOW IS FOR REFERENCE ONLY. SEE PLAN FOR
ACTUAL MEMBER SIZES, SPACING, TYPES, SHAPES, CAMBER, ETC. SEE
PLAN, TRUSS LOADING DIAGRAMS, AND GENERAL NOTES FOR
APPROPRIATE LOADS. SEE PLAN FOR MECHANICAL UNIT LOCATIONS
EL = 4"
BEAM ELEVATION BELOW T.S.
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # :
TBSE 22129
S004
INSPECTIONS
10/21/2022
Enter address here
BYUI McKay
Library
Remodel
Bid set
12242
DOCUMENT ACCEPTANCE OR REJECTION OF STEEL ELEMENTS P P
PLACEMENT AND INSTALLATION OF STEEL HEADED STUD ANCHORS P P
PLACEMENT AND INSTALLATION OF STEEL DECK P P
INSPECTION TASKS PRIOR TO CONCRETE PLACMENT (TABLE N6.1) QC QA
STRUCTURAL STEEL COMPOSITE ELEMENTS (AISC 360 N6.1)
COMPOSITE MEMBER SIZE X VERIFY THAT COMPOSIT MEMBER IS THE REQUIRED SIZE.
REINFORCING STEEL X VERIFY APPROPRIATE REINFORCEMENT SIZE, SPACING, AND
ORIENTATION; THAT IT HAS NOT BEEN RE-BENT IN FIELD; THAT IT IS
CORRECTLY TIED AND SUPPORTED; AND THAT REQUIRED STEEL...
DOCUMENT ACCEPTANCE OR REJECTION
OF STEEL ELEMENTS
X
PLACEMENT AND INSTALLATION OF STEEL
HEADED STUD ANCHORS
X
PLACEMENT AND INSTALLATION OF STEEL
DECK
X
STEEL ELEMENTS OF COMPOSITE CONSTRUCTION (TABLE N6.1, AISC 360-10; TABLES J9-1 THRU J9-3, AISC 341-11):
H-PILES X VERIFY THAT NO HOLES OR UNAPPROVED ATTACHMENTS ARE
MADE WITHIN THE PROTECTED ZONE OF PILING (SEE TABLE J8-1 OF
AISC 341-10).
PROTECTED ZONES X VERIFY THAT NO HOLES OR UNAPPROVED ATTACHMENTS ARE
MADE WITHIN THE PROTECTED ZONE (SEE TABLE J8-1 OF AISC...
REDUCED BEAM SECTIONS (RBS) X VERIFY CONTOUR AND FINISH AS WELL AS DIMENSIONAL
TOLERANCES (SEE TABLE J8-1 OF AISC 341-10).
ANCHOR RODS AND OTHER EMBEDMENTS
SUPPORTING STRUCTURAL STEEL
X SHALL BE ON THE PREMISES DURING THE PLACMENT OF ANCHOR
RODS AND OTHER EMBEDMENTS SUPPORTING STRUCTURAL STEEL
FOR COMPLIANCE WITH CONSTRUCTION DOCUMENTS. VERIFY TH...
STRUCTURAL STEEL DETAILS X ALL FABRICATED STEEL OR STEEL FRAMES SHALL BE INSPECTED
TO VERIFY COMPLIANCE WITH THE DETAILS SHOWN IN THE
CONSTRUCTION DOCUMENTS, SUCH AS BRACES, STIFFENERS,...
OTHER STEEL INSPECTIONS (SECTION N5.7, AISC 360-10; TABLES J8-1 & J10-1, AISC 341-10):
DOCUMENT ACCEPTANCE OR REJECTION
OF BOLTED CONNECTIONS
X
AFTER BOLTING (TABLE N5.6, AISC 360-10):
PRETENSIONED FASTENERS X VERIFY THAT FASTENERS ARE PRTENSIONED IN ACCORDANCE
WITH RCSC SPECIFICATION, PROGRESSING SYSTEMATICALLY
FROM THE MOST RIGID POINT TOWARD THE FREE EDGES.
FASTENER COMPONENT X VERIFY THAT FASTENER COMPONENT IS NOT TURNED BY WRENCH
PREVENTED FROM ROTATING.
SNUG-TIGHT PRIOR TO PRETENSIONING X VERIFY THAT JOINTS ARE BROUGHT TO SNUG-TIGHT CONDITION
PRIOR TO PRETENSIONING OPERATION.
FASTENER ASSEMBLIES X VERIFY THAT FASTENER ASSEMBLIES AR OF SUITABLE CONDITION,
PLACED IN ALL HOLES, AND WASHERS ARE POSITIONED AS
REQUIRED.
- NOT REQUIRED FOR PRETENSIONED JOINTS USING TURN-OF-THE-NUT METHOD WITH MATCH-MARKING,
DIRECT-TENSION-INDICATORS,OR TWIST-OFF TYPE TENSION CONTROL METHOD [PER SECTION N5.6(2) OF AISC 360-10].
- NOT REQUIRED IF ONLY SNUG-TIGHT JOINTS ARE SPECIFIED [PER SECTION N5.6(1) OF AISC 360-10].
DURING BOLTING (TABLE N5.6-2, AISC 360-10):
PROPER STORAGE X VERIFY PROPER STORAGE OF BOLTS, NUTS, WASHERS, AND OTHER
FASTENER COMPONENTS
PRE-INSTALLATION VERIFICATION TESTING X OBSERVE AND DOCUMENT VERIFICATION TESTING BY
INSTALLATION PERSONNEL FOR FASTENER ASSEMBLIES AND...
CONNECTING ELEMENTS X VERIFY APPROPIRATE FAYING SURFACE CONDITION AND HOLE
PREPARATION, IF SPECIFIED, MEET REQUIRMENTS.
PROPER BOLTING PROCEDURE X VERIFY PROPER PROCEDURE IS USED FOR THE JOINT DETAIL.
PROPER FATENERS FOR JOINT X VERIFY GRADE, TYPE, AND BOLT LENGTH IF THREADS ARE
EXCLUDED FROM THE SHEAR PLANE.
FASTENERS MARKED X VERIFY THAT FASTENERS HAVE BEEN MARKED IN ACCORDANCE
WITH ASTM REQUIREMENTS.
CERTIFICATIONS OF FASTENERS X
- NOT REQUIRED IF ONLY SNUG-TIGHT JOINTS ARE SPECIFIED [PER SECTION N5.6(1) OF AISC 360-10]
PRIOR TO BOLTING (TABLE N5.6, AISC 360-10):
WELDED JOINTS SUBJECT TO FATIGUE X
ACCESS HOLES (FLANGE > 2") X
CJP WELDS (RISK CAT. III OR IV) X A REDUCTION IN THE RATE OF ULTRASONIC TESTING IS ALLOWED
PER SECTION N5.5E.
CJP WELDS (RISK CAT. II) X ULTRASONIC TESTIN SHALL BE PERFORMED ON 10% OF CJP
GROOVE WELDS IN BUTT, T- AND CORNER JOINTS SUBJECT TO
TRANSVERSELY APPLIED TENSION LOADING IN MATERIALS...
NONDESTRUCTIVE TESTING (SECTION N5.5,
AISC 360-10):
DOCUMENT ACCEPTANCE OR REJECTION
OF WELDED JOINT/MEMBER
X
BACKING AND WELD TABS REMOVED X
K-AREA X
ARC STRIKES X
WELDS MEET VISUAL ACCEPTANCE
CRITERIA
X
SIZE, LENGTH, AND LOCATION OF WELDS X
WELDS CLEANED X VERIFY THAT WELDS HAVE BEEN PROPERLY CLEANED.
AFTER WELDING (TABLE N5.4-3, AISC 360-10):
WELDING TECHNIQUES X VERIFY INTERPASS AND FINAL CLEANING, EACH PASS IS WITHIN
PROFILE LIMITATIONS, AND QUALITY OF EACH PASS.
WPB FOLLOWED X VERIFY ITEMS SUCH AS SETTINGS ON WELDING EQUIPMENT,
TRAVEL SPEED, WEDLING MATERIALS, SHIELDING GAS TYP/FLOW
RATE, PREHEAT APPLIED, INTERPASS TEMPERATURE MAINTAINED...
ENVIRONMENTAL CONDITIONS X VERIFY WIND SPEED IS WITHIN LIMITS AS WELL AS PRECIPITATION
AND TEMPERATURE.
CRACKED TACK WELDS X VERIFY THAT WEDLING DOES NOT OCCUR OVER CRACKED TACK
WELDS
CONTROL AND HANDLING OF WELDING
CONSUMABLES
X VERIFY PACKAGING AND EXPOSURE CONTROL.
USE OF QUALIFIED WELDERS X VERIFY THAT WELDERS ARE APROPRIATELY QUALIFIED.
DURING WEDLING (TABLE N5.4-2, AISE 360-10):
FIT-UP OF FILLET WELDS X VERIFY ALIGNMENT, GAPS AT ROOT, CLEANLINESS OF STEEL
SURFACES, AND TACK WELD QUALITY AND LOCATION.
ACCESS HOLES X VERIFY CONFIGURATION AND FINISH.
FIT-UP GROOVE WELD X VERIFY JOINT PREPARATION, DIMENSIONS, CLEANLINESS, TACKING,
AND BACKING.
WELDER IDENTIFICATION X A SYSTEM SHALL BE MAINTAINED BY WHICH A WELDER WHO HAS
WELDED A JOINT OR MEMBER CAN BE IDENTIFIED.
MATERIAL IDENTIFICATION X VERIFY TYPE AND GRADE OF MATERIAL.
VERIFY WELDING PROCEDURES (WPS) AND
CONSUMABLE CERTIFICATES
X
PRIOR TO WELDING (TABLE N5.4-1, AISC 360-10):
ITEM CONTIN-
UOUS PERIODIC DETAILED INSTRUCTION AND FREQUENCIES
STRUCTURAL STEEL (IBC 1705.2.1,1705.11.1, & 1705.12.2)
DOCUMENT ACCEPTANCE OR REJECTION OF BOLTED CONNECTIONS P P
INSPECTIONS TASKS AFTER BOLTING (TABLE N5.6-3)QC QA
SYSTEMATICALLY FROM THE MOST RIGID PO9INT TOWARD THE FREE EDGES
FASTENERS ARE PRETENSIONED IN ACCORDANCE WITH THE TCSC SPECIFICATION, PROGRESSING
O O
FASTENER COMPONENT NOT TURNED BY THE WRENCH PREVENTED FROM ROTATING O O
JOINT BROUGHT TO THE SNUG-TIGHT CONDITION PRIOR TO PRETENSIONING OPERATION O O
REQUIRED) ARE POSITIONED AS REQUIRED
FASTENER ASSEMBLIES, OF SUITABLE CONDITION, PLACED IN ALL HOLES AND WASHERS (IF
O O
INSPECTION TASKS DURING BOLTING (TABLE N5.6-2)QC QA
PROPER STORAGE PROVIDED FOR BOLTS, NUTS, WASHER, AND OTHER FASTENER COMPONENTS O O
DOCUMENT FOR FASTENER ASSEMBLIES AND METHODS USED
PRE-INSTALLATION VERIFCATION TESTING BY INSTALLATION PERSONNEL OBSERVED AND
P O
HOLE PREPARATIOIN, IF SPECIFIED, MEET APPLICABLE REQUIREMENTS
CONNECTION ELEMENTS, INCLUDING THE APPROPRIATE FAYING SURFACE CONDITION AND
O O
PROPER BOLTING PROCEDURE SELECTED FOR JOINT DETAIL O O
THREADS ARE TO BE EXCLUDED FROM SHEAR PLANE)
PROPER FASTENERS SELECTED FOR THE JOINT DETAIL (GRADE, TYPE, BOLT LENGTH IF
O O
FASTENERS MARKED IN ACCORDANCE WITH ASTM REQUIREMENTS O O
MANUFACTURER'S CERTIFICATIONS AVAILABLE FOR FASTNER MATERIALS O P
INSPECTION TASKS PRIOR TO BOLTING (TABLE N5.6-1) QC QA
STRUCTURAL STEEL BOLTING INSPECTIONS (AISC 360 N5.6-1,2,3)
INSPECT THE WEB K-AREA FOR CRACKS WITHIN 3 INCHES OF THE WELD.
* WHEN WELDING OF DOUBLER PLATES, CONTINUITY PLATES OR STIFFENERS HAS BEEN PERFORMED IN THE K-AREA, VISUALLY
DOCUMENT ACCEPTANCE OR REJECTION OF WELDED JOINT OR MEMBER P P
REPAIR ACTIVITIES P P
BACKING REMOVED AND WELD TABS REMOVED (IF REQUIRED)P P
K-AREA*P P
ARC STRIKES P P
- POROSITY
- UNDERCUT
- WELD SIZE
- WELD PROFILES
- CRATER CORSS SECTION
- WELD/BASE-METAL FUSION
- CRACK PROHIBITION
WELDS MEET VISUAL ACCEPTANCE CRITERIA
P P
SIZE, LENGTH AND LOCATION OF WELDS P P
WELDS CLEANED O O
INSPECTIONS TASKS AFTER WELDING (TABLE N5.4-3)QC QA
- EACH PASS MEETS QUAILITY REQUIREMENTS
- EACH PASS WITHIN PROFILE LIMITATIONS
- INTERPASS AND FINAL CLEANING
WELDING TECHNIQUES
O O
- PROPER POSITION (F, V, H, OH)
- INTERPASS TEMPERATURE MAINTAINED (MIN./MAX.)
- PREHEAT APPLIED
- SHIELDING GAS TYPE/FLOW RATE
- SELECTED WELDING MATERIALS
- TRAVEL SPEED
- SETTINGS ON WELDING EQUIPMENT
WPS FOLLOWED
O O
- PRECIPITATION AND TEMPERATURE
- WIND SPEED WITHIN LIMITS
ENVIRNOMENTAL CONDITIONS
O O
NO WELDING OVER CRACKED TACK WELDS O O
- EXPOSURE CONTROL
- PACKAGING
CONTROL AND HANDLING OF WELDING CONSUMABLES
O O
USE OF QUALIFIED WELDERS O O
INSPECTION TASKS DURING WELDING (TABLE N5.4-2)QC QA
OR MEMBER CAN BE IDNTIFIED. STAMPS, IF USED, SHALL BE THE LOW STRESS TYPE.
* THE FABRICATOR OR ERECTOR, AS APPLICABLE, SHALL MAINTAIN A SYSTEM BY WHICH A WELDER WHO HAS WELDED A JOINT
CHECK WELDING EQUIPMENT O -
- TACKING (TACK WELD QUALITY AND LOCATION)
- CLEANLINESS (CONDITION OF STEEL SURFACES)
- DIMENSIONS (ALIGNMENT, GAPS AT ROOT)
FIT-UP OF FILLET WELDS
O O
CONFIGURATION AND FINISH OF ACCESS HOLES O O
- BACKING TYPE AND FIT (IF APPLICABLE)
- TACKING (TACK WELD QUALITY AND LOCATION)
- CLEANLINESS (CONDICATION OF STEEL SURFACES)
- DIMENSIONS (ALIGNMENT, ROOT OPENING, ROOT FACE, BEVEL)
- JOINT PREPARATION
FIT-UP OF GROOVE WELDS (INCLUDING JOINT GEOMETRY)
O O
WELDER IDNETIFICATION SYSTEM*O O
MATERIAL IDENTIFICATION (TYPE/GRADE)O O
MANUFACTURER CERTIFICATIONS FOR WELDING CONSUMABLES AVAILIABLE P P
WELDING PROCEDURE SPECIFICATIONS (WPSs) AVAILABLE P P
INSPECTION TASKS PRIOR TO WELDING (TABLE N5.4-1) QC QA
STRUCTURAL STEEL WELDING INSPECTIONS (AISC 360 N5.4-1,2,3)
Sheet List
Sheet Number Sheet Name
S001 GENERAL NOTES
S002 SCHEDULES
S003 INSPECTIONS
S004 INSPECTIONS
S101 LEVEL 1 FLOOR FRAMING
S102 LEVEL 2 FLOOR FRAMING
S103 LEVEL 3 FLOOR FRAMING
S401 PENETRATION 1ST FLOOR
S402 PENETRATION 2ND FLOOR
S403 PENETRATION 3RD FLOOR
S501 DETAILS
10/28/2022
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 161.5
A
B
C
D
E
F
G
H
J
K
L
M
N
P
Q
REMOVE MASONRY
WALL ALONG GRID 1.5
TO FLOOR ABOVE
A1
S501
1
2
2
INDICATES NOTES ARE KEYED ON PLAN.
1.DEMOLISH SUSPENDED SLAB. DO NOT OVERCUT OVER
TUNNEL.
2.HIGH DENSITY STORAGE AREA. SEE DETAIL D1/S501
FOR EMBEDING TRACKS INTO SLAB. SEE ARCHITECT
FOR NUMBER OF TRACKS AND EXTENT.
KEYED SHEET NOTES
CONCRETE
STEEL
1.
GENERAL SHEET NOTES
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # :
TBSE 22129
S101
LEVEL 1
FLOOR
FRAMING
10/21/2022
Enter address here
BYUI McKay
Library
Remodel
Bid set
12242
1/16" = 1'-0"S101
1 Level 1 Overall
10/28/2022
REF.
REF.
ELECTRICAL
ROOM
242
TECH SERV
STORAGE
2-E
TECH SERVICES
238
SHEET MUSIC
236
LARGE
COMPUTER
CLASSROOM
234
OPEN
COMPUTERS
240
MOTHERS
243
OPEN STUDY
53
PRESS ROOM
226
SPECIAL
COLLECTIONS
228
VAULT
228E
ARCHIVE
228D
INSTRUCTION 2
224
INSTRUCTION 1
222
DCAM
228B
OFFICE
228A
SCANNER
228C
OFFICE
232
STUDY (MED)
216
STUDY (MED)
214
STUDY (MED)
218
CLASSROOM
272
OFFICE
288B
OFFICE
288C
ENGLISH
TRANSITION
CENTER
288
STUDY (SM)
204
OPEN TUTORING
254
STUDY SKILLS
252
WRITING
CENTER OPEN
TUTORING
256
STUDY
269
STUDY
268
STUDY
267
STUDY
266
OFFICE
265
OFFICE
264
STORAGE
270J
STUDY
270H
JANITOR'S
OFFICE
241
PREP /
STORAGE
270B
CLASSROOM
258
CLASSROOM
260
PREP /
STORAGE
256A
OFFICE
256B OFFICE
256C
OPEN TUTORING
CENTER
270
OFFICE
230
OFFICE
202
STUDY (SM)
212 STUDY (SM)
210
STUDY (SM)
208
OFFICE
200
OPEN STUDY
220
ADJUNCT
OFFICE
286
TR / COMM.
280
MECHANICAL
2-D
CLASSROOM
278
PRE-FUNCTION
270C
PRE-FUNCTION
270D
PRE-FUNCTION
270E
RECEPTION
270A
PREFUNCTION
270F
I.T.
245
STORAGE
288H
STUDY
252B
PREP /
STORAGE
252G
OFFICE
252E
STORAGE
252F
OFFICE
252D
STUDY
252A
STUDY
252C
MEN'S
RESTROOM
247
WOMEN'S
RESTROOM
248
STAIR
2-G
ELEV
2-H
MECH CHASE
2-J
STAIR
2-A
STAIR
2-B
STUDY
270G
ELEV
2-R
OPEN STUDY
250
MECH
2-C
HALL
2-K
STAIR
2-P
STOR
299
WOMEN'S
RESTROOM
284
MEN'S
RESTROOM
282
MECH
2-T
CLASSROOM
276
CLASSROOM
274
Room
2-S
HALL
2-Q
HALL
2-U
HALL
2-WFAMILY RR
244
STUDY (MED)
206
JANITOR'S
CLOSET
249
STUDY
288G
STUDY
288F
STUDY
288E
STUDY
288D
STUDY
288A
IT
241A
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
9
9
10
10
11
11
12
12
13
13
14
14
15
15
16
16
1.5
1.5
A A
B B
C C
D D
E E
F F
G G
H H
J JKK
L L
M M
N N
P P
Q Q
12
4
'
-
8
"
10
2
'
-
0
"
76
'
-
6
"
W
1
0
X
1
9
EL
=
-
5
"
MC12X40
EL = -5"
W
1
0
X
1
9
EL
=
-
5
"
MC12X40
EL = -5"W
1
8
X
1
3
0
EL
=
-
2
3
"HSS5X5X1/4HSS5X5X1/4W
1
8
X
1
3
0
EL
=
-
2
5
"HSS5X5X1/4HSS5X5X1/4S102
A4
PENETRATION IN MASONRY.
USE LL6X4X1/4 ANGLE WITH
BOLTS AT 48"O.C. BEAR 6"
ON EACH END.
B4
S501
B4
S501
B4
S501
B4
S501
B4
S501
B4
S501
B4
S501
B4
S501
B4
S501
B4
S501HSS4X4X1/4EXISTING 12" CONCRETE SLAB. 4"Ø
HOLES MAY BE CORED AT 4'-0"O.C.
FERROUS SCAN TO MISS THE TOP #
6 CROSS BARS SPACED AT 5.5"O.C.
HSS6X4X1/4
HSS16X4X1/4
HS
S
4
X
4
X
1
/
4
HS
S
6
X
4
X
1
/
4
HS
S
4
X
4
X
1
/
4
C2
S501
C1
S501
C4
S501
1110
D
B
10
10
11
11
B B
C C
D D
-
---
_______
11
2
'
-
1
"
W1
8
X
1
3
0
113' - 7"
MC12X40
11
3
'
-
7
"
L6
X
6
X
3
/
8
11
1
'
-
1
1
"
W
1
8
X
1
3
0
11
3
'
-
7
"
W1
0
X
1
9
11
3
'
-
7
"
W
1
0
X
1
9
11
3
'
-
7
"
L6
X
6
X
3
/
8
113' - 7"
MC12X40HSS5X5X1/4HSS5X5X1/4HSS5X5X1/4HSS5X5X1/4MASONRY WALLS AROUND
EXISTING STAIRS MAY BE REMOVED
INFILL STAIR PENETRATION WITH 5" TOTAL
THICKNESS CONCRETE ON METAL DECK (1.5"
"B" DECK). REINFORCE WITH #3 AT 18"O.C.
EACH WAY. SEE LEVEL 2 FLOOR FRAMING
FOR ADDITIONAL STRUCTURAL SUPPORTS.
TOP OF CONCRETE ON METAL DECK
ELEVATION = 114'-0"
1110
D
B
D2
S501
FIELD VERIFY W18 ELEVATION WITH EXISTING
FRAMING.
D4
S501
D4
S501
D5
S501
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # :
TBSE 22129
S102
LEVEL 2
FLOOR
FRAMING
10/21/2022
Enter address here
BYUI McKay
Library
Remodel
Bid set
12242
1/16" = 1'-0"S102
B1 Level 2 Overall
1/4" = 1'-0"S102
A4 ENLARGED PLAN - LEVEL 2
10/28/2022
OFFICE
310
OFFICE
312
JUVENILE
300
STORAGE
306
STUDY (MED)
304
STUDY (MED)
302
KIDS PLAY
344C
MOTHERS
ROOM
344A
RESTROOM
344B
FAMILY STUDY
344
OPEN STUDY
362
Bridge
Connection
-
BRIDGE
CONNECTION
3-A
STAIR 1
3-B
MENS
368
WOMENS
366
TEST RM
378
STUDY (SM)
330 Janitors Closet
376
OFFICE
322
MAC EQUIP
324A
STUDY (LG)
328
STUDY (LG)
326
MAC LAB
324
STUDY (SM)
332
STUDY (SM)
334
STUDY (SM)
336
TEST RM
374
STUDY (SM)
314
STUDY (SM)
316
STUDY (SM)
320
ELECTRICAL
324B
ELEC
364
STUDY (SM)
338
STUDY (SM)
340
STUDY (SM)
318
( QUIET )
OPEN STUDY
342
ELECTRICAL
308
STORAGE
352
TEST RM
380
TEST RM
382
TEST RM
372
TEST RM
370
TEST RM
360
TEST RM
358
TEST RM
356
TEST RM
350
TEST RM
348
TEST RM
346
STAIRS
3-C
MECH
3-D
MECH CHASE
3-E
STAIR
3-F
ELEV
3-G
MECH CHASE
3-H
CIRC DESK
OPEN STUDY
TYP.
TYP.
TYP.
TYP.
SIM.
TYP.
TYP.TYP.
JUVENILE COLLECTION
K - 12 BOOKS
310
312
3-B.23-B.1
344A
324
322.1
382
346
354
360 358 356 364
380
378
324A
324B
374
372
370
308 306
314
316
318
320
304 302
332
334
336
338
340
344
344B
348 350
330
326
3-B.5
3-B.6
3-B.7
3-B.8
SF70
SF71SF72
SF73
SF74
SF75
SF76
SF77 SF78 SF79 SF80
SF81
SF82SF83SF84
SF85
SF86
SF87
SF88
SF89
SF90
SF91
OPEN STUDY
383
22.07
22.1910.12
10.12
10.12
10.12
10.12
10.12
10.12
TYP.
TILE WIDTH
5' - 4 3/4"
11.11
11.11
11.11
11.11
11.11
11.11
11.11 11.1111.11
11.11
11.11
11.11
11.11 11.11
TYP.
TYP.
TYP.
3-F
3-C
328
4"
1 2 3 4 5 6 7
7
8
8
9
9
10
10
11
11
12
12
13
13
14
14
15
15
16
16
1.5
A
B
C
D
E
F
G
H
J
K
L
M
N
P
QHSS3-1/2X3-1/2X1/4HSS3-1/2X3-1/2X1/4HSS3-1/2X3-1/2X1/4HSS3-1/2X3-1/2X1/4HSS3-1/2X3-1/2X1/4HSS3-1/2X3-1/2X1/412
6
'
-
0
"
W1
0
X
2
2
12
6
'
-
6
"
W
1
0
X
2
2
12
6
'
-
0
"
W1
0
X
2
2
A2
S501
A2
S501
B4
S501
12
5
'
-
1
1
"
W
1
0
X
2
2
12
5
'
-
1
1
"
W
1
0
X
2
2
B4
S501
B4
S501
INDICATES NOTES ARE KEYED ON PLAN.
1.PROVIDE LINTEL ABOVE NEW DOOR OPENING, SEE
NON-BEARING CMU STEEL LINTEL SCHEDULE ON
SHEET S002
2.PROVIDE STEEL ANGLES AT NEW OPENING, SEE SCHEDULE
ON SHEET S002
KEYED SHEET NOTES
GENERAL SHEET NOTES
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # :
TBSE 22129
S103
LEVEL 3
FLOOR
FRAMING
10/21/2022
Enter address here
BYUI McKay
Library
Remodel
Bid set
12242
1/16" = 1'-0"S103
1 Level 3 Area A Framing Plan
2
10/28/2022
REMOVE MASONRY WALL ALONG
GRID 1.5 TO FLOOR ABOVE.
MASONRY WALLS AROUND EXISTING
STAIRS MAY BE REMOVED WITH
STAIRS.
MASONRY WALL TO BE REMOVED.
CAREFULLY REMOVE VENEER (TO
BE RE-USED). DEMOLISH WALLS
AS REQUIRED. INSTALL VENEER
SUPPORT BEAM.
INFILL WALL WITH STUD
AT EXISTING OPENING
ENLARGE FLOOR
PENETRATION
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # :
TBSE 22129
S401
PENETRATION
1ST FLOOR
10/21/2022
Enter address here
BYUI McKay
Library
Remodel
Bid set
12242
S401
A1 LEVEL 1 PENETRATIONS 3D
10/28/2022
PENETRATION IN MASONRY. SEE
LINTEL SCHEDULE.
MASONRY WALLS AROUND EXISTING
STAIRS MAY BE REMOVED.
INFILL STAIR PENETRATION WITH 5"
TOTAL THICKNESS CONCRETE ON
METAL DECK (1.5" "B" DECK). SEE
LEVEL 2 FLOOR FRAMING FOR
ADDITIONAL STRUCTURAL SUPPORTS.
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # :
TBSE 22129
S402
PENETRATION
2ND FLOOR
10/21/2022
Enter address here
BYUI McKay
Library
Remodel
Bid set
12242
S402
A1 LEVEL 2 PENETRATIONS 3D
10/28/2022
PORTION OF CONCRETE WALL TO
BE REMOVED. SEE SCHEDULE FOR
FRAMING NEW OPENING.
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # :
TBSE 22129
S403
PENETRATION
3RD FLOOR
10/21/2022
Enter address here
BYUI McKay
Library
Remodel
Bid set
12242
S403
1 LEVEL 3 PENETRATIONS
10/28/2022
3 5/8" STUD WALL, 20 GAUGE.
SPACE STUDS 16"O.C. ATTACH
CHANNEL TO CONCRETE USING
(2) 3/16X1 3/4 SIMPSON TITEN
TURBO CONCRETE SCREWS AT
16"O.C.
EXISTING CONCRETE WALL
EXISTING FLOOR SLAB
EXISTING
ROOF DECK
EXISTING ROOF JOIST
1/4
L2X2X1/4" ANGLE BRACES AT 48"
O.C. AND AT STEEL COLUMN
1/2"Ø THREADED RODS AT 24"O. STAGGERED. CUT HOLES IN STEEL
BEAM AS REQ'D. COORDINATE WITH FOLDING DOOR SUPPLIER.
NEW STEEL BEAM AT
SKYFOLD/MODERN FOLD
DOOR, SEE PLAN
SKYFOLD / MODERN
FOLD DOORS
WHERE OCCURS,
SEE ARCH.
1/4
1/2"X7.5"XCONTINUOUS PLATE OR C8X11.5
(FLANGES TURNED UP). COORDINATE WITH
DOOR SUPPLIER.
EXISTING
ROOF DECK
EXISTING ROOF JOIST
1/4
1/2"Ø THREADED RODS AT 24"O. STAGGERED. CUT HOLES IN
STEEL BEAM AS REQ'D. COORDINATE WITH FOLDING DOOR
SUPPLIER.
NEW STEEL BEAM AT SKYFOLD/MODERN FOLD DOOR,
SEE PLAN
SKYFOLD / MODERN
FOLD DOORS
WHERE OCCURS,
SEE ARCH.
1/4
1/2"X7.5"XCONTINUOUS PLATE OR C8X11.5
(FLANGES TURNED UP). COORDINATE WITH
DOOR SUPPLIER.
1
2
L2X2X1/4" ANGLE BRACES AT 48"
O.C. AND AT STEEL COLUMN
L3X3X1/4" ANGLE BRACES AT TOP
CHORD PANNEL POINT
L2X2X1/4" BRACE MAY DIRECTLY
GO TO TOP CHORD OF ADJACENT
JOIST IF SLOPE IS LESS THAN 1:2
1/2"X3"X4" PLATE
MID HT OR HIGHER
MID HT OR HIGHER
L3X3X1/4
EXISTING BRICK VENEER, CMU,
REINFORCED CMU.
CAREFULLY REMOVE BRICK
VENEER TO REUSE ABOVE
LINTEL ANGLE. REMOVE CMU
AND REINFORCE CMU FOR
NEW OPENING.
1/4
L6X4X3/8
BEAM, SEE PLAN
5/16
1.5" B DECK
INFILL WITH LIGHT GAUGE STUD
WALL, 362S137-33MIL MINIMUM
STUDS. SPACE STUDS AT 16"O.C.
PROVIDE SLIP TRACK AT TOP.
VIEW B-B
EXISTING MASONRY WALL
GROUT CELL SOLID IF NOT
SOLID GROUTED
5/8"Ø TITEN HD BOLT W/
WASHERS AT BOTTOM,
BEAM SEAT AND 48" O.C.
BETWEEN.
VIEW A-A
A A
B B
EXISTING REINFORCED
MASONRY WALL
3/16
L6X4X5/16 BY 4" AT BOLT
5/16
3/4"X4.5"X7" CAP PLATE
3/4"X4"X4" BASE PLATE
1' - 0"
0' - 8"
INDIVIDUAL RAIL OPTION WHOLE SLAB OPTION
1' - 6"
1' - 0"
0' - 8"
0' - 1 1/2"
#3 DOWEL @ 15"O.C. AT
EXSITING SLAB. DRILL AND
EPOXY, EMBED 4" MINIMUM.
#4 BY CONT.
#4 @ 18"O.C. EACH
WAY.
#3 BENT DOWELS
UNDER RAILS
EXISTING SLAB.
HIGH DENSITY
STORAGE RAIL,
COORDINATE WITH
SUPPLIER.
1' - 0"
0' - 1 1/2"
0' - 5"
EXISTING ROOF DECK
EXISTING FLOOR SYSTEM
1/4
L2X2X1/4" ANGLE BRACES AT 48" O.C. AND AT STEEL COLUMN
1/2"Ø THREADED RODS AT 24"O. STAGGERED. CUT HOLES IN STEEL
BEAM AS REQ'D. COORDINATE WITH FOLDING DOOR SUPPLIER.
NEW STEEL BEAM AT SKYFOLD/MODERN FOLD DOOR, SEE PLAN
SKYFOLD / MODERN
FOLD DOORS
WHERE OCCURS,
SEE ARCH.
3/16
1/2"X7.5"XCONTINUOUS PLATE OR C8X11.5
(FLANGES TURNED UP). COORDINATE WITH
DOOR SUPPLIER.
0' - 4 1/2"
1/2"X3"X10" PLATE WITH (2) 5/8"Ø BOLTS.
DRILL AND EPOXY 5" MINIMUM. 1/2"X3"X3"
"T" PLATE WELDED AT CENTER.
1/2"X3"X4" PLATE
MID HT OR HIGHER
1/2"X3.5"X8" BASE PLATE WITH (2)
1/4"ØX1.625" TITEN HD ANCHOR.
1/2"X3.5"X8" CAP PLATE WITH (2)
7/8"Ø BOLTS.
1/4
5/16 STIFFENER PLATE EACH SIDE
EXISTING FLOOR (3" SLAB
MINIMUM).
BEAM, SEE PLAN
SEE SCHEDULE FOR STEEL TO
STEEL CONNECTION
1/4" BY CONTINUOUS BENT
PLATE. OVER LAP CHANNEL BY
1" MINIMUM.
0' - 2 1/2"
CONCRETE ON METAL DECK,
SEE PLAN. REINFORCE PER
PLAN.
#3 AT 18"O.C. DRILL AND EPOXY
4" MINIMUM EMBEDMENT
EXISTING CONCRETE WAFFLE
SLAB FRAMING. FIELD VERIFY
EDGE CONDITION.
3/16 2@12
L3X3X1/4, NOT SHOWN, TO
SUPPORT METAL DECK.
SEE DETAIL C1/S501 FOR
ADDITIONAL INFORMATION.
1/4
BEAM, SEE PLAN
1.5" B DECK, NOT SHOWN
0
'
-
8"
0
'
-
1
1
/
2
"
SHIM AS REQUIRED
3 SIDES
1/4
3/8" BY 12" BENT PLATE WITH
(2) 3/4"Ø TITEN HD, 5" MIN.
EMBED. SPACE PLATES 4'-0"
MAXIMUM FULL LENGTH OF
WF BEAM.
SEE D2/S501 FOR SLAB
CONNECTION.
CHANNEL, SEE PLAN
CJP
1/2" PLATE WITH 1/2"X3"
STIFFENER ALL AROUND.
ALIGN PLATE UNDER WEB OF
CHANNEL AND EXTEND
STIFFENER PLATES SAME
DIRECTION AS CHANNEL
FLANGES.
SEE D2/S501 FOR SLAB
CONNECTION.
1' - 0"
1' - 8"
BOLT CONNECTION PER
STEEL-STEEL SCHEDULE.
FIELD VERIFY. CONTACT
STRUCTURAL ENGINEER IF IT
NEEDS TO BE 2'-0" OR
GREATER.
1' - 0"
COLUMN, SEE PLAN, WITH
1"X9"X9" CAP PLATE AND (2)
3/4"Ø BOLTS
BEAM, SEE PLAN, WITH 3/8"
STIFFENER PLATES EACH
SIDE AT COLUMN.
3/16
0' - 8"
0' - 4"
0' - 1 3/4"
GUARDRAIL
1/2"X4"X8" WITH (2)
1/2"Ø HILTI KWICK
BOLTS, EMBED 3¼"
EXISTING CONCRETE
WALL
HSS1½"X1½"X3/16
GUARDRAIL AT 4'-0"
MAXIMUM SPACING.
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # :
TBSE 22129
S501
DETAILS
10/21/2022
Enter address here
BYUI McKay
Library
Remodel
Bid set
12242
3/4" = 1'-0"S501
A1
3/4" = 1'-0"S501
A2 TYPICAL FOLDING DOOR
NO SCALES501
C1
3/4" = 1'-0"S501
C4
3/4" = 1'-0"S501
D1 HIGH DENSITY SUPPORT
3/4" = 1'-0"S501
B2 TYPICAL FOLDING DOOR - WAFFLE SLAB
3/4" = 1'-0"S501
B4 TYPICAL FOLDING DOOR COLUMN SUPPORT
3/4" = 1'-0"S501
D2 FLOOR INFILL - SIDE
3/4" = 1'-0"S501
C2
3/4" = 1'-0"S501
D4
3/4" = 1'-0"S501
D5
3/4" = 1'-0"S501
B1 GUARDRAIL
10/28/2022
3
1
G
J
L
M
N
P
Q
E
C
2 3 4 5
STORAGE RM #40
ELEV
EQUIP.
CUST.
STOR.STORAGESTORAGE
MECH
CHASE
BDF
CUST.ELEV
MEN'S RR WOMEN'S RR
BREAK ROOMOFFICE
TRAININGSTORAGE
IMAGING &
STORAGE
MECHANICAL ROOM
STORAGE STORAGE
AIR HANDLING UNITSAIR HANDLING UNITS
02.14
02.12
02.15
02.16
6
02.18
02.13
02.17
02.36
02.43
EXISTING WALLS TO REMAIN
LEGEND
INTERIOR PARTITION STUD AND GYPSUM BOARD WALLS AND/OR
DEMOUNTABLE PARTITIONS, TO BE DEMOLISHED
EXISTING DOOR TO BE DEMOLISHED
FURNITURE TO BE KEPT AND REUSED BY BYU-IDAHO. CONTRACTOR
TO RETURN TO OWNER. COORDINATE WITH OWNER.
REMOVE EXISTING FLOORING (MOSTLY CARPET AND SOME TILE
AROUND DESK AREAS, ETC...) AND PREP FOR FLOOR FOR NEW
FLOORING. RE: FLOOR PLANS FOR NEW FLOORING.
INTERIOR PARTITION NON-REINFORCED CMU/MASONRY WALLS TO BE
DEMOLISHED - PROTECT FLOORS AND SURROUNDING AREAS FROM
DAMAGE
FURNITURE TO BE SOLD BY BYU-IDAHO. CONTRACTOR TO RETURN TO
OWNER. COORDINATE WITH OWNER.
N.I.C.
EXISTING TUNNEL BELOW
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
10/28/22
D100a
Level 00 Area
A Demolition
Plan
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
GENERAL NOTES - DEMO
1 GENERAL CONTRACTOR SHALL FIELD VERIFY ALL CONDITIONS, MATERIALS, FINISHES, AND DIMENSIONS BEFORE AND
AFTER DEMOLITION, AND TO CONTACT THE ARCHITECT WITH ANY UNFORESEEN CONDITIONS
2 GENERAL CONTRACTOR SHALL PROTECT EXISTING STRUCTURE/ASSEMBLIES/EQUIPMENT AS REQUIRED. REPAIR, PATCH
AND/OR REPLACE EXISTING CONSTRUCTED ITEMS AND EQUIPMENT THAT ARE TO REMAIN AS REQUIRED FOR NEW
CONSTRUCTION
3 GENERAL CONTRACTOR SHALL PATCH AND REPAIR TO MATCH EXISTING FINISHES AT WALLS, FLOORS, CEILINGS/SOFFITS,
ETC... AS REQUIRED IN ARES NOT SPECIFICALLY CALLED OUT IN THE DRAWINGS BUT ARE IMPACTED BY CONSTRUCTION
4 REFER TO MECHANICAL, PLUMBING, AND ELECTRICAL DRAWINGS FOR ADDITIONAL DEMOLITION COORDINATION
5 GENERAL CONTRACTOR SHALL PROVIDE A 6 MIL POLYETHYLENE DUST BARRIER FROM FLOOR TO DECK ABOVE TO
ENSURE THAT ALL CORRIDORS OUTSIDE OF CONSTRUCTION AREA ARE KEPT CLEAN AND CLEAR OF DEBRIS AND
OBSTRUCTIONS AT ALL TIMES. DUST BARRIER SHALL BE SEALED AIR TIGHT IN ALL PHASED AREAS OF CONSTRUCTION
6 UPON COMPLETION OF CONSTRUCTION IN EACH PHASE IT IS THE GENERAL CONTRACTORS RESPONSIBILITY TO
THOROUGHLY CLEAN ALL AREAS IN WHICH CONSTRUCTION TOOK PLACE AND AREAS IMPACTED BY CONSTRUCTION. THE
GENERAL CONTRACTOR SHALL CLEAN ALL CARPET, REMOVE ALL DUST, CLEAN DOORS AND FRAMES, LIGHT FIXTURES,
CEILING SYSTEMS, MECHANICAL GRILLES, ELECTRICAL PANELS, WINDOW SYSTEMS, GLAZING, ETC...
7 GENERAL CONTRACTOR TO PREVENT WATER BUILD-UP AND/OR DAMAGE FOUNDATIONS ON THE CONSTRUCTION SITE OR
ADJACENT AREAS
8 GENERAL CONTRACTOR TO KEEP AN ACTIVE PEDESTRIAN PATHWAY TO AND AT EGRESS ROUTES FREE OF
OBSTRUCTIONS AT ALL TIMES. CONTRACTOR TO PROVIDE PROTECTION TO PEDESTRIANS BEFORE DEMOLITION (IBC 3303)
9 GENERAL CONTRACTOR TO MAINTAIN EXITS, EXISTING STRUCTURAL ELEMENTS, APPLIED FIREPROOFING PROTECTION
DEVICES, AND SANITARY SAFEGUARDS AT ALL TIMES DURING DEMOLITION AND CONSTRUCTION
10 ALL EXISTING FURNITURE TO BE SALVAGED AND RETURNED TO OWNER FOR RE-USE OR SURPLUS
11 CHAIR RAIL, PICTURE RAIL BULLETIN BOARDS, TO BE REMOVED FROM ANY EXISTING WALLS THAT WILL REMAIN, TO BE
PATCHED AND REPAIRD FOR FINAL FINISHES
12 ALL WINDOW COVERINGS TO BE REMOVED AND DISPOSED OF
13 TILE AT REMAINING DRINKING FOUNTAINS WALLS TO BE REMOVED, WALL PATCHED AND REFINISHED PER FINISH
PLANS/ELEVATIONS
14 WINDOW SILLS TO BE REPLACED AT ALL LOCATIONS
1/8" = 1'-0"A1 Level 00 Area A Demolition Plan KEY PLAN
A
B
KEYED NOTES
02.12 EXISTING CMU WALL TO BE DEMOLISHED
02.13 EXISTING INTERIOR GYP BOARD PARTITION WALL TO BE DEMOLISHED
02.14 EXISTING HIGH DENSITY SHELVING TO BE REMOVED AND DEMOLISHED, INCLUDING THE BUILT-UP AND TRACK ON
TOP OF THE CONCRETE. EXISTING CONCRETE TO BE PROTECTED AND PREPPED FOR NEW FLOORING
02.15 REMOVE AND DISPOSE OF EXISTING DRINKING FOUNTAIN. SEE FLOOR PLANS AND MECHANICAL DRAWINGS.
02.16 EXISTING FIRE EXTINGUISHER AND CABINET TO BE SALVAGED FOR RE-USE
02.17 REMOVE EXISTING DOOR AND PREP FOR LARGER DOOR. SEE NEW FLOOR PLAN.
02.18 EXISTING TILE ON WALL TO BE REMOVED
02.36 REMOVE EXISTING DOOR. NEW DOOR NEEDS TO SWING INTO SPACE.
02.43 DEMO EXISTING GYP BOARD TO PROVIDE POWER AND BLOCKING, SEE FLOOR PLANS.
DN
1
G
J
L
M
N
P
Q
E
C
2 3 4 5
OFFICE
ISSUE / 2-DAY CHECK OUT
DVD'S
RESERVES & MISC. STORAGE
OVERSIZE BOOKS COLLECTION
OFFICE OFFICE STUDY ROOM
OFFICE
MAC LAB
ELEV MECH.
COMMONS
READING ROOM
MEN'S RR WOMEN'S RR
CUSTODIAL
STORAGE
PC/CLIENT
MANAGER
COMPUTER
SUPPORT
STORAGE COMPUTER PC/CLIENT
MANAGER
ADMIN OFFICE OFFICE
OFFICE
OFFICE
BREAK AREA
OFFICE OFFICE
OFFICE
CD'S
VESTIBULE
POPULAR BOOKS COLLECTION
CO
M
P
U
T
E
R
S
CO
M
P
U
T
E
R
S
NEW BOOKS
COLLABORATIVE STUDY SPACE
STUDY ROOM
SECURITY DESK
VENDING MACHINES
PERIODICALS
1.5 6
2'-4"
B5
A311
02.22
02.21
02.20
02.35 02.24
02.25
02.26
02.19
02.27
02.15
02.35
02.37
02.38
02.21
E1
A516
02.44
02.45
02.22
02.46
TYP.
02.45
02.22
02.15
02.35
02.46
02.46
02.4602.46
02.4602.46
B2
A431
02.59
02.58
22.23
EXISTING WALLS TO REMAIN
LEGEND
INTERIOR PARTITION STUD AND GYPSUM BOARD WALLS AND/OR
DEMOUNTABLE PARTITIONS, TO BE DEMOLISHED
EXISTING DOOR TO BE DEMOLISHED
FURNITURE TO BE KEPT AND REUSED BY BYU-IDAHO. CONTRACTOR
TO RETURN TO OWNER. COORDINATE WITH OWNER.
REMOVE EXISTING FLOORING (MOSTLY CARPET AND SOME TILE
AROUND DESK AREAS, ETC...) AND PREP FOR FLOOR FOR NEW
FLOORING. RE: FLOOR PLANS FOR NEW FLOORING.
INTERIOR PARTITION NON-REINFORCED CMU/MASONRY WALLS TO BE
DEMOLISHED - PROTECT FLOORS AND SURROUNDING AREAS FROM
DAMAGE
FURNITURE TO BE SOLD BY BYU-IDAHO. CONTRACTOR TO RETURN TO
OWNER. COORDINATE WITH OWNER.
N.I.C.
EXISTING TUNNEL BELOW
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
10/28/22
D101a
Level 01 Area
A Demolition
Plan
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
1/8" = 1'-0"A1 Level 01 Area A Demolition Plan
GENERAL NOTES - DEMO
1 GENERAL CONTRACTOR SHALL FIELD VERIFY ALL CONDITIONS, MATERIALS, FINISHES, AND DIMENSIONS BEFORE AND
AFTER DEMOLITION, AND TO CONTACT THE ARCHITECT WITH ANY UNFORESEEN CONDITIONS
2 GENERAL CONTRACTOR SHALL PROTECT EXISTING STRUCTURE/ASSEMBLIES/EQUIPMENT AS REQUIRED. REPAIR, PATCH
AND/OR REPLACE EXISTING CONSTRUCTED ITEMS AND EQUIPMENT THAT ARE TO REMAIN AS REQUIRED FOR NEW
CONSTRUCTION
3 GENERAL CONTRACTOR SHALL PATCH AND REPAIR TO MATCH EXISTING FINISHES AT WALLS, FLOORS, CEILINGS/SOFFITS,
ETC... AS REQUIRED IN ARES NOT SPECIFICALLY CALLED OUT IN THE DRAWINGS BUT ARE IMPACTED BY CONSTRUCTION
4 REFER TO MECHANICAL, PLUMBING, AND ELECTRICAL DRAWINGS FOR ADDITIONAL DEMOLITION COORDINATION
5 GENERAL CONTRACTOR SHALL PROVIDE A 6 MIL POLYETHYLENE DUST BARRIER FROM FLOOR TO DECK ABOVE TO
ENSURE THAT ALL CORRIDORS OUTSIDE OF CONSTRUCTION AREA ARE KEPT CLEAN AND CLEAR OF DEBRIS AND
OBSTRUCTIONS AT ALL TIMES. DUST BARRIER SHALL BE SEALED AIR TIGHT IN ALL PHASED AREAS OF CONSTRUCTION
6 UPON COMPLETION OF CONSTRUCTION IN EACH PHASE IT IS THE GENERAL CONTRACTORS RESPONSIBILITY TO
THOROUGHLY CLEAN ALL AREAS IN WHICH CONSTRUCTION TOOK PLACE AND AREAS IMPACTED BY CONSTRUCTION. THE
GENERAL CONTRACTOR SHALL CLEAN ALL CARPET, REMOVE ALL DUST, CLEAN DOORS AND FRAMES, LIGHT FIXTURES,
CEILING SYSTEMS, MECHANICAL GRILLES, ELECTRICAL PANELS, WINDOW SYSTEMS, GLAZING, ETC...
7 GENERAL CONTRACTOR TO PREVENT WATER BUILD-UP AND/OR DAMAGE FOUNDATIONS ON THE CONSTRUCTION SITE OR
ADJACENT AREAS
8 GENERAL CONTRACTOR TO KEEP AN ACTIVE PEDESTRIAN PATHWAY TO AND AT EGRESS ROUTES FREE OF
OBSTRUCTIONS AT ALL TIMES. CONTRACTOR TO PROVIDE PROTECTION TO PEDESTRIANS BEFORE DEMOLITION (IBC 3303)
9 GENERAL CONTRACTOR TO MAINTAIN EXITS, EXISTING STRUCTURAL ELEMENTS, APPLIED FIREPROOFING PROTECTION
DEVICES, AND SANITARY SAFEGUARDS AT ALL TIMES DURING DEMOLITION AND CONSTRUCTION
10 ALL EXISTING FURNITURE TO BE SALVAGED AND RETURNED TO OWNER FOR RE-USE OR SURPLUS
11 CHAIR RAIL, PICTURE RAIL BULLETIN BOARDS, TO BE REMOVED FROM ANY EXISTING WALLS THAT WILL REMAIN, TO BE
PATCHED AND REPAIRD FOR FINAL FINISHES
12 ALL WINDOW COVERINGS TO BE REMOVED AND DISPOSED OF
13 TILE AT REMAINING DRINKING FOUNTAINS WALLS TO BE REMOVED, WALL PATCHED AND REFINISHED PER FINISH
PLANS/ELEVATIONS
14 WINDOW SILLS TO BE REPLACED AT ALL LOCATIONS
KEY PLAN
A
B
KEYED NOTES
02.15 REMOVE AND DISPOSE OF EXISTING DRINKING FOUNTAIN. SEE FLOOR PLANS AND MECHANICAL DRAWINGS.
02.19 ALL EXISTING METAL SHELVING TO BE SALVAGED AND RETURNED TO OWNER FOR RE-USE.
02.20 ALL EXISTING FURNITURE IS TO BE SALVAGED AND RETURNED TO OWNER FOR SURPLUS/RE-USE.
02.21 REMOVE AND DISPOSE OF EXISTING STOREFRONT SYSTEM
02.22 SAWCUT EXISTING BRICK AND CMU HERE
02.24 REMOVE EXISTING DOOR AND PREP FOR INFILL. SEE FLOOR PLANS AND STRUCTURAL.
02.25 REMOVE AND DISPOSE OF EXISTING GATE SYSTEM
02.26 REMOVE AND DISPOSE OF EXISTING SECURITY DESK
02.27 REMOVE AND DISPOSE OF EXISTING CIRCULATION DESK
02.35 REMOVE EXISTING FIRE CABINET. PATCH AND REPAIR TO MATCH EXISTING WALL.
02.37 DEMO EXISTING CONCRETE FOR HEATED SIDEWALK. SEE CIVIL DRAWINGS.
02.38 REMOVE GRAVEL AND DEMO EXISTING TRAVERTINE CURB. PREP FOR PATCHED FLOOR IN THIS AREA.
02.44 DEMO EXISTING STOREFRONT DOORS.
02.45 REMOVE EXISTING CMU WALL TO PROVIDE TEMPORARY ACCESS TO THE SHAFT DURING CONSTRUCTION. SEE
MECHANICAL.
02.46 REFER TO SLAB EDGE PLANS FOR ADDITIONAL FLOOR DEMOLITION FOR ELECTRICAL, PLUMBING, HIGH DENSITY
SHELVING, ETC...
02.58 DEMO WALL AS NEEDED TO REPLACE DRINKING FOUNTAIN. PATCH AND REPAIR WALL AS NEEDED.
02.59 EXISTING METAL BASE AT BRICK TO REMAIN.
22.23 ACCESS FROM FRONT SIDE OF WALL AS NEEDED. DO NOT ACCESS FROM BACK SIDE.
ALLY CHAIRS
16151413121110987
K
H
F
D
B
A
GENERAL COLLECTION A - F
MAPS
MICROFILM
OFFICE OF FACULTY
DEVELOPMENT & MENTORED
RESEARCH
SECURITY DESK
OPEN CLASSROOM /
COMPUTERS
WOMEN'S RR MEN'S RR LIBRARY SCIENCE CLASSROOM
(COMPUTERS)
OFFICE
OFFICE
OFFICE
ELEV
ELEV EQUIP.
MECHANICAL ROOM
CUST.
ENTRY
VESTIBULE
OFFICE
OFFICE
INTERLIBRARY DOCUMENT
PROCESSING
STORAGE OFFICE
SERVICE
DESK
COMPUTERS
02.31
02.25
02.34
02.15
02.39
02.40
02.22
02.22
02.27
02.26
02.4602.46
02.20
TYP.
16' - 10 1/4"
9 7/8"
02.54
02.56
02.57
02.5002.50
EXISTING WALLS TO REMAIN
LEGEND
INTERIOR PARTITION STUD AND GYPSUM BOARD WALLS AND/OR
DEMOUNTABLE PARTITIONS, TO BE DEMOLISHED
EXISTING DOOR TO BE DEMOLISHED
FURNITURE TO BE KEPT AND REUSED BY BYU-IDAHO. CONTRACTOR
TO RETURN TO OWNER. COORDINATE WITH OWNER.
REMOVE EXISTING FLOORING (MOSTLY CARPET AND SOME TILE
AROUND DESK AREAS, ETC...) AND PREP FOR FLOOR FOR NEW
FLOORING. RE: FLOOR PLANS FOR NEW FLOORING.
INTERIOR PARTITION NON-REINFORCED CMU/MASONRY WALLS TO BE
DEMOLISHED - PROTECT FLOORS AND SURROUNDING AREAS FROM
DAMAGE
FURNITURE TO BE SOLD BY BYU-IDAHO. CONTRACTOR TO RETURN TO
OWNER. COORDINATE WITH OWNER.
N.I.C.
EXISTING TUNNEL BELOW
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
10/28/22
D101b
Level 01 Area
B Demolition
Plan
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
GENERAL NOTES - DEMO
1 GENERAL CONTRACTOR SHALL FIELD VERIFY ALL CONDITIONS, MATERIALS, FINISHES, AND DIMENSIONS BEFORE AND
AFTER DEMOLITION, AND TO CONTACT THE ARCHITECT WITH ANY UNFORESEEN CONDITIONS
2 GENERAL CONTRACTOR SHALL PROTECT EXISTING STRUCTURE/ASSEMBLIES/EQUIPMENT AS REQUIRED. REPAIR, PATCH
AND/OR REPLACE EXISTING CONSTRUCTED ITEMS AND EQUIPMENT THAT ARE TO REMAIN AS REQUIRED FOR NEW
CONSTRUCTION
3 GENERAL CONTRACTOR SHALL PATCH AND REPAIR TO MATCH EXISTING FINISHES AT WALLS, FLOORS, CEILINGS/SOFFITS,
ETC... AS REQUIRED IN ARES NOT SPECIFICALLY CALLED OUT IN THE DRAWINGS BUT ARE IMPACTED BY CONSTRUCTION
4 REFER TO MECHANICAL, PLUMBING, AND ELECTRICAL DRAWINGS FOR ADDITIONAL DEMOLITION COORDINATION
5 GENERAL CONTRACTOR SHALL PROVIDE A 6 MIL POLYETHYLENE DUST BARRIER FROM FLOOR TO DECK ABOVE TO
ENSURE THAT ALL CORRIDORS OUTSIDE OF CONSTRUCTION AREA ARE KEPT CLEAN AND CLEAR OF DEBRIS AND
OBSTRUCTIONS AT ALL TIMES. DUST BARRIER SHALL BE SEALED AIR TIGHT IN ALL PHASED AREAS OF CONSTRUCTION
6 UPON COMPLETION OF CONSTRUCTION IN EACH PHASE IT IS THE GENERAL CONTRACTORS RESPONSIBILITY TO
THOROUGHLY CLEAN ALL AREAS IN WHICH CONSTRUCTION TOOK PLACE AND AREAS IMPACTED BY CONSTRUCTION. THE
GENERAL CONTRACTOR SHALL CLEAN ALL CARPET, REMOVE ALL DUST, CLEAN DOORS AND FRAMES, LIGHT FIXTURES,
CEILING SYSTEMS, MECHANICAL GRILLES, ELECTRICAL PANELS, WINDOW SYSTEMS, GLAZING, ETC...
7 GENERAL CONTRACTOR TO PREVENT WATER BUILD-UP AND/OR DAMAGE FOUNDATIONS ON THE CONSTRUCTION SITE OR
ADJACENT AREAS
8 GENERAL CONTRACTOR TO KEEP AN ACTIVE PEDESTRIAN PATHWAY TO AND AT EGRESS ROUTES FREE OF
OBSTRUCTIONS AT ALL TIMES. CONTRACTOR TO PROVIDE PROTECTION TO PEDESTRIANS BEFORE DEMOLITION (IBC 3303)
9 GENERAL CONTRACTOR TO MAINTAIN EXITS, EXISTING STRUCTURAL ELEMENTS, APPLIED FIREPROOFING PROTECTION
DEVICES, AND SANITARY SAFEGUARDS AT ALL TIMES DURING DEMOLITION AND CONSTRUCTION
10 ALL EXISTING FURNITURE TO BE SALVAGED AND RETURNED TO OWNER FOR RE-USE OR SURPLUS
11 CHAIR RAIL, PICTURE RAIL BULLETIN BOARDS, TO BE REMOVED FROM ANY EXISTING WALLS THAT WILL REMAIN, TO BE
PATCHED AND REPAIRD FOR FINAL FINISHES
12 ALL WINDOW COVERINGS TO BE REMOVED AND DISPOSED OF
13 TILE AT REMAINING DRINKING FOUNTAINS WALLS TO BE REMOVED, WALL PATCHED AND REFINISHED PER FINISH
PLANS/ELEVATIONS
14 WINDOW SILLS TO BE REPLACED AT ALL LOCATIONS
KEY PLAN
A
B
1/8" = 1'-0"A1 Level 01 Area B Demolition Plan
KEYED NOTES
02.15 REMOVE AND DISPOSE OF EXISTING DRINKING FOUNTAIN. SEE FLOOR PLANS AND MECHANICAL DRAWINGS.
02.20 ALL EXISTING FURNITURE IS TO BE SALVAGED AND RETURNED TO OWNER FOR SURPLUS/RE-USE.
02.22 SAWCUT EXISTING BRICK AND CMU HERE
02.25 REMOVE AND DISPOSE OF EXISTING GATE SYSTEM
02.26 REMOVE AND DISPOSE OF EXISTING SECURITY DESK
02.27 REMOVE AND DISPOSE OF EXISTING CIRCULATION DESK
02.31 REMOVE EXISTING STAIRWELL, INCLUDING STAIRS, RAILS, AND MASONRY STAIRWELL WALLS. RE: STRUCTURAL
02.34 REMOVE EXISTING DRINKING FOUNTAIN AND SALVAGE FOR FUTURE RE-USE.
02.39 REMOVE EXISTING MASONRY WALLS FOR NEW VESTIBULE. RE: STRUCTURAL
02.40 EXISTING UNDERGROUND TUNNEL. ALL TRADES TO COORDINATE ACCORDINGLY.
02.46 REFER TO SLAB EDGE PLANS FOR ADDITIONAL FLOOR DEMOLITION FOR ELECTRICAL, PLUMBING, HIGH DENSITY
SHELVING, ETC...
02.50 DEMO EXISTING GYP BOARD ON BACK SIDE OF RESTROOMS TO REPLACE PLUMBING.
02.54 EXISTING RAILING TO REMAIN.
02.56 REMOVE EXISTING BULLETIN BOARD FRAME AND BULLETIN BOARD MATERIAL, PRESERVE SURROUNDING STONE.
02.57 REMOVE EXISTING RECESSED MAILBOX.
BRODY BRODY BRODY
BRODY BRODY BRODY
BR
O
D
Y
BR
O
D
Y
BR
O
D
Y
BR
O
D
Y
BR
O
D
Y
BR
O
D
Y
BR
O
D
Y
JENNY
JE
N
N
Y
JE
N
N
Y
JE
N
N
Y
JE
N
N
Y
JE
N
N
Y
JE
N
N
Y
JE
N
N
Y
JE
N
N
Y
GMC
1
G
J
L
M
N
P
Q
E
C
2 3 4 5
GENERAL COLLECTION
G - Z
SPECIAL COLLECTIONS
ARCHIVES
OFFICE
OFFICE
DCAM OFFICE
TECHNICAL SERVICES
4 EXISTING OFFICES
OFFICE
MCKAY GALLERY MEN'S RR WOMEN'S RR
GRANDIN PRESS
DISPLAY ROOM
GROUP STUDY
ROOMS
GROUP STUDY
ROOMS
COMPUTERS
BREAK ROOM
CUSTODIAL
MAIL ROOM
CONFERENCE ROOM
ELEV
CONFERENCE
ROOM
OFFICE
SPECIAL COLLECTIONS STORAGE
COMPUTERS COMPUTERS
1.5
VAULT
6
B5
A311
02.20
02.15
02.35
02.35
02.13
02.49
02.27
02.47
02.35
02.48
TYP.
22.23
02.15
02.58
EXISTING WALLS TO REMAIN
LEGEND
INTERIOR PARTITION STUD AND GYPSUM BOARD WALLS AND/OR
DEMOUNTABLE PARTITIONS, TO BE DEMOLISHED
EXISTING DOOR TO BE DEMOLISHED
FURNITURE TO BE KEPT AND REUSED BY BYU-IDAHO. CONTRACTOR
TO RETURN TO OWNER. COORDINATE WITH OWNER.
REMOVE EXISTING FLOORING (MOSTLY CARPET AND SOME TILE
AROUND DESK AREAS, ETC...) AND PREP FOR FLOOR FOR NEW
FLOORING. RE: FLOOR PLANS FOR NEW FLOORING.
INTERIOR PARTITION NON-REINFORCED CMU/MASONRY WALLS TO BE
DEMOLISHED - PROTECT FLOORS AND SURROUNDING AREAS FROM
DAMAGE
FURNITURE TO BE SOLD BY BYU-IDAHO. CONTRACTOR TO RETURN TO
OWNER. COORDINATE WITH OWNER.
N.I.C.
EXISTING TUNNEL BELOW
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
10/28/22
D102a
Level 02 Area
A Demolition
Plan
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set1/8" = 1'-0"A1 Level 02 Area A Demolition Plan
GENERAL NOTES - DEMO
1 GENERAL CONTRACTOR SHALL FIELD VERIFY ALL CONDITIONS, MATERIALS, FINISHES, AND DIMENSIONS BEFORE AND
AFTER DEMOLITION, AND TO CONTACT THE ARCHITECT WITH ANY UNFORESEEN CONDITIONS
2 GENERAL CONTRACTOR SHALL PROTECT EXISTING STRUCTURE/ASSEMBLIES/EQUIPMENT AS REQUIRED. REPAIR, PATCH
AND/OR REPLACE EXISTING CONSTRUCTED ITEMS AND EQUIPMENT THAT ARE TO REMAIN AS REQUIRED FOR NEW
CONSTRUCTION
3 GENERAL CONTRACTOR SHALL PATCH AND REPAIR TO MATCH EXISTING FINISHES AT WALLS, FLOORS, CEILINGS/SOFFITS,
ETC... AS REQUIRED IN ARES NOT SPECIFICALLY CALLED OUT IN THE DRAWINGS BUT ARE IMPACTED BY CONSTRUCTION
4 REFER TO MECHANICAL, PLUMBING, AND ELECTRICAL DRAWINGS FOR ADDITIONAL DEMOLITION COORDINATION
5 GENERAL CONTRACTOR SHALL PROVIDE A 6 MIL POLYETHYLENE DUST BARRIER FROM FLOOR TO DECK ABOVE TO
ENSURE THAT ALL CORRIDORS OUTSIDE OF CONSTRUCTION AREA ARE KEPT CLEAN AND CLEAR OF DEBRIS AND
OBSTRUCTIONS AT ALL TIMES. DUST BARRIER SHALL BE SEALED AIR TIGHT IN ALL PHASED AREAS OF CONSTRUCTION
6 UPON COMPLETION OF CONSTRUCTION IN EACH PHASE IT IS THE GENERAL CONTRACTORS RESPONSIBILITY TO
THOROUGHLY CLEAN ALL AREAS IN WHICH CONSTRUCTION TOOK PLACE AND AREAS IMPACTED BY CONSTRUCTION. THE
GENERAL CONTRACTOR SHALL CLEAN ALL CARPET, REMOVE ALL DUST, CLEAN DOORS AND FRAMES, LIGHT FIXTURES,
CEILING SYSTEMS, MECHANICAL GRILLES, ELECTRICAL PANELS, WINDOW SYSTEMS, GLAZING, ETC...
7 GENERAL CONTRACTOR TO PREVENT WATER BUILD-UP AND/OR DAMAGE FOUNDATIONS ON THE CONSTRUCTION SITE OR
ADJACENT AREAS
8 GENERAL CONTRACTOR TO KEEP AN ACTIVE PEDESTRIAN PATHWAY TO AND AT EGRESS ROUTES FREE OF
OBSTRUCTIONS AT ALL TIMES. CONTRACTOR TO PROVIDE PROTECTION TO PEDESTRIANS BEFORE DEMOLITION (IBC 3303)
9 GENERAL CONTRACTOR TO MAINTAIN EXITS, EXISTING STRUCTURAL ELEMENTS, APPLIED FIREPROOFING PROTECTION
DEVICES, AND SANITARY SAFEGUARDS AT ALL TIMES DURING DEMOLITION AND CONSTRUCTION
10 ALL EXISTING FURNITURE TO BE SALVAGED AND RETURNED TO OWNER FOR RE-USE OR SURPLUS
11 CHAIR RAIL, PICTURE RAIL BULLETIN BOARDS, TO BE REMOVED FROM ANY EXISTING WALLS THAT WILL REMAIN, TO BE
PATCHED AND REPAIRD FOR FINAL FINISHES
12 ALL WINDOW COVERINGS TO BE REMOVED AND DISPOSED OF
13 TILE AT REMAINING DRINKING FOUNTAINS WALLS TO BE REMOVED, WALL PATCHED AND REFINISHED PER FINISH
PLANS/ELEVATIONS
14 WINDOW SILLS TO BE REPLACED AT ALL LOCATIONS
KEY PLAN
A
B
KEYED NOTES
02.13 EXISTING INTERIOR GYP BOARD PARTITION WALL TO BE DEMOLISHED
02.15 REMOVE AND DISPOSE OF EXISTING DRINKING FOUNTAIN. SEE FLOOR PLANS AND MECHANICAL DRAWINGS.
02.20 ALL EXISTING FURNITURE IS TO BE SALVAGED AND RETURNED TO OWNER FOR SURPLUS/RE-USE.
02.27 REMOVE AND DISPOSE OF EXISTING CIRCULATION DESK
02.35 REMOVE EXISTING FIRE CABINET. PATCH AND REPAIR TO MATCH EXISTING WALL.
02.47 GRANDIN PRESS - RELOCATE CAREFULLY, PER OWNERS DESIRED LOCATION AND STORE DURING CONSTRUCTION.
02.48 LARGE PAPER CUTTER TO BE RELOCATED PER OWNERS INSTRUCTIONS DURING CONSTRUCTION. COORDINATE
WITH OWNER.
02.49 SALVAGE EXISTING VAULT DOOR FOR RE-USE.
02.58 DEMO WALL AS NEEDED TO REPLACE DRINKING FOUNTAIN. PATCH AND REPAIR WALL AS NEEDED.
22.23 ACCESS FROM FRONT SIDE OF WALL AS NEEDED. DO NOT ACCESS FROM BACK SIDE.
1.5" TALLER
1.5" TALLER
OLD STEELCASE OLD STEELCASE
GMC
ATCATCATC
ATCATCATC
ATCATCATC
ATCATCATC
ATCATCATC
ATCATCATC
ATCATCATC
ATCATCATC
ATCATCATC
ATCATCATC
ATCATCATC
ATCATCATC
16151413121110987
K
H
F
D
B
A
OFFICEOFFICESTUDYSTUDY
STUDY
STUDY
STUDY
STUDY
CLASSROOM
OFFICE
STORAGE
STORAGE
OFFICE
READING CENTER
MATH CENTER
OFFICE
OFFICE
OFFICE
OFFICE
CLASSROOM
OFFICE OFFICE OFFICE OFFICE OFFICE
STORAGE
OFFICE
CLASSROOMCLASSROOM
OFFICE OFFICE
STORAGE
OFFICE
OPEN TUTORINGOPEN TUTORING /
WRITING CENTER
OPEN TUTORING
02.31
02.20
02.1302.34
TYP.
02.50 02.50
02.15
22.23
EXISTING WALLS TO REMAIN
LEGEND
INTERIOR PARTITION STUD AND GYPSUM BOARD WALLS AND/OR
DEMOUNTABLE PARTITIONS, TO BE DEMOLISHED
EXISTING DOOR TO BE DEMOLISHED
FURNITURE TO BE KEPT AND REUSED BY BYU-IDAHO. CONTRACTOR
TO RETURN TO OWNER. COORDINATE WITH OWNER.
REMOVE EXISTING FLOORING (MOSTLY CARPET AND SOME TILE
AROUND DESK AREAS, ETC...) AND PREP FOR FLOOR FOR NEW
FLOORING. RE: FLOOR PLANS FOR NEW FLOORING.
INTERIOR PARTITION NON-REINFORCED CMU/MASONRY WALLS TO BE
DEMOLISHED - PROTECT FLOORS AND SURROUNDING AREAS FROM
DAMAGE
FURNITURE TO BE SOLD BY BYU-IDAHO. CONTRACTOR TO RETURN TO
OWNER. COORDINATE WITH OWNER.
N.I.C.
EXISTING TUNNEL BELOW
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
10/28/22
D102b
Level 02 Area
B Demolition
Plan
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
GENERAL NOTES - DEMO
1 GENERAL CONTRACTOR SHALL FIELD VERIFY ALL CONDITIONS, MATERIALS, FINISHES, AND DIMENSIONS BEFORE AND
AFTER DEMOLITION, AND TO CONTACT THE ARCHITECT WITH ANY UNFORESEEN CONDITIONS
2 GENERAL CONTRACTOR SHALL PROTECT EXISTING STRUCTURE/ASSEMBLIES/EQUIPMENT AS REQUIRED. REPAIR, PATCH
AND/OR REPLACE EXISTING CONSTRUCTED ITEMS AND EQUIPMENT THAT ARE TO REMAIN AS REQUIRED FOR NEW
CONSTRUCTION
3 GENERAL CONTRACTOR SHALL PATCH AND REPAIR TO MATCH EXISTING FINISHES AT WALLS, FLOORS, CEILINGS/SOFFITS,
ETC... AS REQUIRED IN ARES NOT SPECIFICALLY CALLED OUT IN THE DRAWINGS BUT ARE IMPACTED BY CONSTRUCTION
4 REFER TO MECHANICAL, PLUMBING, AND ELECTRICAL DRAWINGS FOR ADDITIONAL DEMOLITION COORDINATION
5 GENERAL CONTRACTOR SHALL PROVIDE A 6 MIL POLYETHYLENE DUST BARRIER FROM FLOOR TO DECK ABOVE TO
ENSURE THAT ALL CORRIDORS OUTSIDE OF CONSTRUCTION AREA ARE KEPT CLEAN AND CLEAR OF DEBRIS AND
OBSTRUCTIONS AT ALL TIMES. DUST BARRIER SHALL BE SEALED AIR TIGHT IN ALL PHASED AREAS OF CONSTRUCTION
6 UPON COMPLETION OF CONSTRUCTION IN EACH PHASE IT IS THE GENERAL CONTRACTORS RESPONSIBILITY TO
THOROUGHLY CLEAN ALL AREAS IN WHICH CONSTRUCTION TOOK PLACE AND AREAS IMPACTED BY CONSTRUCTION. THE
GENERAL CONTRACTOR SHALL CLEAN ALL CARPET, REMOVE ALL DUST, CLEAN DOORS AND FRAMES, LIGHT FIXTURES,
CEILING SYSTEMS, MECHANICAL GRILLES, ELECTRICAL PANELS, WINDOW SYSTEMS, GLAZING, ETC...
7 GENERAL CONTRACTOR TO PREVENT WATER BUILD-UP AND/OR DAMAGE FOUNDATIONS ON THE CONSTRUCTION SITE OR
ADJACENT AREAS
8 GENERAL CONTRACTOR TO KEEP AN ACTIVE PEDESTRIAN PATHWAY TO AND AT EGRESS ROUTES FREE OF
OBSTRUCTIONS AT ALL TIMES. CONTRACTOR TO PROVIDE PROTECTION TO PEDESTRIANS BEFORE DEMOLITION (IBC 3303)
9 GENERAL CONTRACTOR TO MAINTAIN EXITS, EXISTING STRUCTURAL ELEMENTS, APPLIED FIREPROOFING PROTECTION
DEVICES, AND SANITARY SAFEGUARDS AT ALL TIMES DURING DEMOLITION AND CONSTRUCTION
10 ALL EXISTING FURNITURE TO BE SALVAGED AND RETURNED TO OWNER FOR RE-USE OR SURPLUS
11 CHAIR RAIL, PICTURE RAIL BULLETIN BOARDS, TO BE REMOVED FROM ANY EXISTING WALLS THAT WILL REMAIN, TO BE
PATCHED AND REPAIRD FOR FINAL FINISHES
12 ALL WINDOW COVERINGS TO BE REMOVED AND DISPOSED OF
13 TILE AT REMAINING DRINKING FOUNTAINS WALLS TO BE REMOVED, WALL PATCHED AND REFINISHED PER FINISH
PLANS/ELEVATIONS
14 WINDOW SILLS TO BE REPLACED AT ALL LOCATIONS
KEY PLAN
A
B
1/8" = 1'-0"A1 Level 02 Area B Demolition Plan
KEYED NOTES
02.13 EXISTING INTERIOR GYP BOARD PARTITION WALL TO BE DEMOLISHED
02.15 REMOVE AND DISPOSE OF EXISTING DRINKING FOUNTAIN. SEE FLOOR PLANS AND MECHANICAL DRAWINGS.
02.20 ALL EXISTING FURNITURE IS TO BE SALVAGED AND RETURNED TO OWNER FOR SURPLUS/RE-USE.
02.31 REMOVE EXISTING STAIRWELL, INCLUDING STAIRS, RAILS, AND MASONRY STAIRWELL WALLS. RE: STRUCTURAL
02.34 REMOVE EXISTING DRINKING FOUNTAIN AND SALVAGE FOR FUTURE RE-USE.
02.50 DEMO EXISTING GYP BOARD ON BACK SIDE OF RESTROOMS TO REPLACE PLUMBING.
22.23 ACCESS FROM FRONT SIDE OF WALL AS NEEDED. DO NOT ACCESS FROM BACK SIDE.
1
G
J
L
M
N
P
Q
E
C
2 3 4 5
JUVENILE COLLECTION
K - 12 BOOKS
OFFICE
SERVICE DESK
TEACHERS LEARNING CENTER
SECURITY DESK
GROUP STUDY GROUP STUDY
DI
E
C
U
T
S
COMPUTERS
COMPUTERS
GROUP STUDY AREA
COMPUTER CLASSROOM
VIDEO
EDITING
VIDEO
EDITING
PHOTO STUDIO
PHOTO SERVICES VOLUNTEER CONNECTION
ELEV
DISABILITY SERVICES
CONFERENCE ROOM FACULTY TECHNOLOGY CENTER
INSTRUCTIONAL DEVELOPMENT
STAGING AREA OFFICE / WORKROOM
HELP DESK AREA
COMPUTER REPAIR
OFFICE
MEN'S RR WOMEN'S RR
CONFERENCE ROOMOFFICE
MUSIC STORAGE
RESEARCH & CREATIVE WORKS
OFFICE SERVER &
STORAGE
OFFICE PRINTER
ROOM
OFFICE
OFFICE
STORAGE
OFFICEINSTRUCTIONAL DEVELOPMENT
STAGING AREA
OFFICE
OFFICE
CUSTODIAL
OFFICE
STORAGE
OFFICE
STORAGE STORAGE
OFFICESPRAY ROOM
OFFICE
OFFICE
OFFICE
1.5 6
02.20
02.26
02.25
02.15
02.35
02.35
02.45
02.22
02.35
02.29
02.30
02.2202.22
12'-11 3/4"
02.27
02.45
02.22
TYP.
22.23
02.60
EXISTING WALLS TO REMAIN
LEGEND
INTERIOR PARTITION STUD AND GYPSUM BOARD WALLS AND/OR
DEMOUNTABLE PARTITIONS, TO BE DEMOLISHED
EXISTING DOOR TO BE DEMOLISHED
FURNITURE TO BE KEPT AND REUSED BY BYU-IDAHO. CONTRACTOR
TO RETURN TO OWNER. COORDINATE WITH OWNER.
REMOVE EXISTING FLOORING (MOSTLY CARPET AND SOME TILE
AROUND DESK AREAS, ETC...) AND PREP FOR FLOOR FOR NEW
FLOORING. RE: FLOOR PLANS FOR NEW FLOORING.
INTERIOR PARTITION NON-REINFORCED CMU/MASONRY WALLS TO BE
DEMOLISHED - PROTECT FLOORS AND SURROUNDING AREAS FROM
DAMAGE
FURNITURE TO BE SOLD BY BYU-IDAHO. CONTRACTOR TO RETURN TO
OWNER. COORDINATE WITH OWNER.
N.I.C.
EXISTING TUNNEL BELOW
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
10/28/22
D103a
Level 03 Area
A Demolition
Plan
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set1/8" = 1'-0"A1 Level 03 Area A Demolition Plan
GENERAL NOTES - DEMO
1 GENERAL CONTRACTOR SHALL FIELD VERIFY ALL CONDITIONS, MATERIALS, FINISHES, AND DIMENSIONS BEFORE AND
AFTER DEMOLITION, AND TO CONTACT THE ARCHITECT WITH ANY UNFORESEEN CONDITIONS
2 GENERAL CONTRACTOR SHALL PROTECT EXISTING STRUCTURE/ASSEMBLIES/EQUIPMENT AS REQUIRED. REPAIR, PATCH
AND/OR REPLACE EXISTING CONSTRUCTED ITEMS AND EQUIPMENT THAT ARE TO REMAIN AS REQUIRED FOR NEW
CONSTRUCTION
3 GENERAL CONTRACTOR SHALL PATCH AND REPAIR TO MATCH EXISTING FINISHES AT WALLS, FLOORS, CEILINGS/SOFFITS,
ETC... AS REQUIRED IN ARES NOT SPECIFICALLY CALLED OUT IN THE DRAWINGS BUT ARE IMPACTED BY CONSTRUCTION
4 REFER TO MECHANICAL, PLUMBING, AND ELECTRICAL DRAWINGS FOR ADDITIONAL DEMOLITION COORDINATION
5 GENERAL CONTRACTOR SHALL PROVIDE A 6 MIL POLYETHYLENE DUST BARRIER FROM FLOOR TO DECK ABOVE TO
ENSURE THAT ALL CORRIDORS OUTSIDE OF CONSTRUCTION AREA ARE KEPT CLEAN AND CLEAR OF DEBRIS AND
OBSTRUCTIONS AT ALL TIMES. DUST BARRIER SHALL BE SEALED AIR TIGHT IN ALL PHASED AREAS OF CONSTRUCTION
6 UPON COMPLETION OF CONSTRUCTION IN EACH PHASE IT IS THE GENERAL CONTRACTORS RESPONSIBILITY TO
THOROUGHLY CLEAN ALL AREAS IN WHICH CONSTRUCTION TOOK PLACE AND AREAS IMPACTED BY CONSTRUCTION. THE
GENERAL CONTRACTOR SHALL CLEAN ALL CARPET, REMOVE ALL DUST, CLEAN DOORS AND FRAMES, LIGHT FIXTURES,
CEILING SYSTEMS, MECHANICAL GRILLES, ELECTRICAL PANELS, WINDOW SYSTEMS, GLAZING, ETC...
7 GENERAL CONTRACTOR TO PREVENT WATER BUILD-UP AND/OR DAMAGE FOUNDATIONS ON THE CONSTRUCTION SITE OR
ADJACENT AREAS
8 GENERAL CONTRACTOR TO KEEP AN ACTIVE PEDESTRIAN PATHWAY TO AND AT EGRESS ROUTES FREE OF
OBSTRUCTIONS AT ALL TIMES. CONTRACTOR TO PROVIDE PROTECTION TO PEDESTRIANS BEFORE DEMOLITION (IBC 3303)
9 GENERAL CONTRACTOR TO MAINTAIN EXITS, EXISTING STRUCTURAL ELEMENTS, APPLIED FIREPROOFING PROTECTION
DEVICES, AND SANITARY SAFEGUARDS AT ALL TIMES DURING DEMOLITION AND CONSTRUCTION
10 ALL EXISTING FURNITURE TO BE SALVAGED AND RETURNED TO OWNER FOR RE-USE OR SURPLUS
11 CHAIR RAIL, PICTURE RAIL BULLETIN BOARDS, TO BE REMOVED FROM ANY EXISTING WALLS THAT WILL REMAIN, TO BE
PATCHED AND REPAIRD FOR FINAL FINISHES
12 ALL WINDOW COVERINGS TO BE REMOVED AND DISPOSED OF
13 TILE AT REMAINING DRINKING FOUNTAINS WALLS TO BE REMOVED, WALL PATCHED AND REFINISHED PER FINISH
PLANS/ELEVATIONS
14 WINDOW SILLS TO BE REPLACED AT ALL LOCATIONS
KEY PLAN
A
B
KEYED NOTES
02.15 REMOVE AND DISPOSE OF EXISTING DRINKING FOUNTAIN. SEE FLOOR PLANS AND MECHANICAL DRAWINGS.
02.20 ALL EXISTING FURNITURE IS TO BE SALVAGED AND RETURNED TO OWNER FOR SURPLUS/RE-USE.
02.22 SAWCUT EXISTING BRICK AND CMU HERE
02.25 REMOVE AND DISPOSE OF EXISTING GATE SYSTEM
02.26 REMOVE AND DISPOSE OF EXISTING SECURITY DESK
02.27 REMOVE AND DISPOSE OF EXISTING CIRCULATION DESK
02.29 DEMO FIRE/SMOKE DOOR.
02.30 DEMO EXISTING DOORS, BUT KEEP DOOR FRAMES INTACT.
02.35 REMOVE EXISTING FIRE CABINET. PATCH AND REPAIR TO MATCH EXISTING WALL.
02.45 REMOVE EXISTING CMU WALL TO PROVIDE TEMPORARY ACCESS TO THE SHAFT DURING CONSTRUCTION. SEE
MECHANICAL.
02.60 DEMO AND REMOVE RAILING
22.23 ACCESS FROM FRONT SIDE OF WALL AS NEEDED. DO NOT ACCESS FROM BACK SIDE.
1
G
J
L
M
N
P
Q
E
C
2 3 4 51.5
STORAGE RM #40
ELEV
EQUIP.
CUST.
STOR.STORAGESTORAGE
MECH
CHASE
BDF
CUST.ELEV
MEN'S RR WOMEN'S RR
OFFICEOFFICE
STORAGESTORAGE
RECEPTION
MECHANICAL ROOM
COMPUTER LAB (UNUSED)IT
6
02.52
EXISTING WALLS TO REMAIN
LEGEND
INTERIOR PARTITION STUD AND GYPSUM BOARD WALLS AND/OR
DEMOUNTABLE PARTITIONS, TO BE DEMOLISHED
ACT CEILING TO BE DEMOLISHED
INTERIOR PARTITION NON-REINFORCED CMU/MASONRY WALLS TO BE
DEMOLISHED - PROTECT FLOORS AND SURROUNDING AREAS FROM
DAMAGE
N.I.C.
GYP. BOARD CEILING TO BE DEMOLISHED
SOFFIT TO BE DEMOLISHED
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
10/28/22
D130a
Level 00 Area
A Demolition
RCP Plan
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
GENERAL NOTES - DEMO
1 GENERAL CONTRACTOR SHALL FIELD VERIFY ALL CONDITIONS, MATERIALS, FINISHES, AND DIMENSIONS BEFORE AND
AFTER DEMOLITION, AND TO CONTACT THE ARCHITECT WITH ANY UNFORESEEN CONDITIONS
2 GENERAL CONTRACTOR SHALL PROTECT EXISTING STRUCTURE/ASSEMBLIES/EQUIPMENT AS REQUIRED. REPAIR, PATCH
AND/OR REPLACE EXISTING CONSTRUCTED ITEMS AND EQUIPMENT THAT ARE TO REMAIN AS REQUIRED FOR NEW
CONSTRUCTION
3 GENERAL CONTRACTOR SHALL PATCH AND REPAIR TO MATCH EXISTING FINISHES AT WALLS, FLOORS, CEILINGS/SOFFITS,
ETC... AS REQUIRED IN ARES NOT SPECIFICALLY CALLED OUT IN THE DRAWINGS BUT ARE IMPACTED BY CONSTRUCTION
4 REFER TO MECHANICAL, PLUMBING, AND ELECTRICAL DRAWINGS FOR ADDITIONAL DEMOLITION COORDINATION
5 GENERAL CONTRACTOR SHALL PROVIDE A 6 MIL POLYETHYLENE DUST BARRIER FROM FLOOR TO DECK ABOVE TO
ENSURE THAT ALL CORRIDORS OUTSIDE OF CONSTRUCTION AREA ARE KEPT CLEAN AND CLEAR OF DEBRIS AND
OBSTRUCTIONS AT ALL TIMES. DUST BARRIER SHALL BE SEALED AIR TIGHT IN ALL PHASED AREAS OF CONSTRUCTION
6 UPON COMPLETION OF CONSTRUCTION IN EACH PHASE IT IS THE GENERAL CONTRACTORS RESPONSIBILITY TO
THOROUGHLY CLEAN ALL AREAS IN WHICH CONSTRUCTION TOOK PLACE AND AREAS IMPACTED BY CONSTRUCTION. THE
GENERAL CONTRACTOR SHALL CLEAN ALL CARPET, REMOVE ALL DUST, CLEAN DOORS AND FRAMES, LIGHT FIXTURES,
CEILING SYSTEMS, MECHANICAL GRILLES, ELECTRICAL PANELS, WINDOW SYSTEMS, GLAZING, ETC...
7 GENERAL CONTRACTOR TO PREVENT WATER BUILD-UP AND/OR DAMAGE FOUNDATIONS ON THE CONSTRUCTION SITE OR
ADJACENT AREAS
8 GENERAL CONTRACTOR TO KEEP AN ACTIVE PEDESTRIAN PATHWAY TO AND AT EGRESS ROUTES FREE OF
OBSTRUCTIONS AT ALL TIMES. CONTRACTOR TO PROVIDE PROTECTION TO PEDESTRIANS BEFORE DEMOLITION (IBC 3303)
9 GENERAL CONTRACTOR TO MAINTAIN EXITS, EXISTING STRUCTURAL ELEMENTS, APPLIED FIREPROOFING PROTECTION
DEVICES, AND SANITARY SAFEGUARDS AT ALL TIMES DURING DEMOLITION AND CONSTRUCTION
10 ALL EXISTING FURNITURE TO BE SALVAGED AND RETURNED TO OWNER FOR RE-USE OR SURPLUS
11 CHAIR RAIL, PICTURE RAIL BULLETIN BOARDS, TO BE REMOVED FROM ANY EXISTING WALLS THAT WILL REMAIN, TO BE
PATCHED AND REPAIRD FOR FINAL FINISHES
12 ALL WINDOW COVERINGS TO BE REMOVED AND DISPOSED OF
13 TILE AT REMAINING DRINKING FOUNTAINS WALLS TO BE REMOVED, WALL PATCHED AND REFINISHED PER FINISH
PLANS/ELEVATIONS
14 WINDOW SILLS TO BE REPLACED AT ALL LOCATIONS
KEY PLAN
A
B
1/8" = 1'-0"A1 Level 00 Area A RCP Demolition Plan
KEYED NOTES
02.52 DEMO EXISTING CEILING AS NEEDED FOR HVAC, PLUMBING, AND FIRE. SEE MECHANICAL, PLUMBING, AND FIRE.
1
G
J
L
M
N
P
Q
E
C
2 3 4 51.5
OFFICE
RESERVES & MISC. STORAGE
OFFICE OFFICE STUDY ROOM
OFFICE
MECH.
CHASE
MAC LAB
ELEV MECH.
COMMONS
MEN'S RR WOMEN'S RR
CUSTODIAL
STORAGE
PC/CLIENT
MANAGER COMPUTER
SUPPORT
STORAGE COMPUTER
PC/CLIENT
MANAGER
ADMIN OFFICE OFFICE
OFFICE
OFFICE
BREAK AREA
OFFICE OFFICE
OFFICE
CD'S
VESTIBULE
POPULAR BOOKS COLLECTION
CO
M
P
U
T
E
R
S
CO
M
P
U
T
E
R
S
COLLABORATIVE STUDY SPACE
STUDY ROOM
SECURITY DESK
VENDING MACHINES
6
02.32
EXISTING WALLS TO REMAIN
LEGEND
INTERIOR PARTITION STUD AND GYPSUM BOARD WALLS AND/OR
DEMOUNTABLE PARTITIONS, TO BE DEMOLISHED
ACT CEILING TO BE DEMOLISHED
INTERIOR PARTITION NON-REINFORCED CMU/MASONRY WALLS TO BE
DEMOLISHED - PROTECT FLOORS AND SURROUNDING AREAS FROM
DAMAGE
N.I.C.
GYP. BOARD CEILING TO BE DEMOLISHED
SOFFIT TO BE DEMOLISHED
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
10/28/22
D131a
Level 01 Area
A Demolition
RCP Plan
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
GENERAL NOTES - DEMO
1 GENERAL CONTRACTOR SHALL FIELD VERIFY ALL CONDITIONS, MATERIALS, FINISHES, AND DIMENSIONS BEFORE AND
AFTER DEMOLITION, AND TO CONTACT THE ARCHITECT WITH ANY UNFORESEEN CONDITIONS
2 GENERAL CONTRACTOR SHALL PROTECT EXISTING STRUCTURE/ASSEMBLIES/EQUIPMENT AS REQUIRED. REPAIR, PATCH
AND/OR REPLACE EXISTING CONSTRUCTED ITEMS AND EQUIPMENT THAT ARE TO REMAIN AS REQUIRED FOR NEW
CONSTRUCTION
3 GENERAL CONTRACTOR SHALL PATCH AND REPAIR TO MATCH EXISTING FINISHES AT WALLS, FLOORS, CEILINGS/SOFFITS,
ETC... AS REQUIRED IN ARES NOT SPECIFICALLY CALLED OUT IN THE DRAWINGS BUT ARE IMPACTED BY CONSTRUCTION
4 REFER TO MECHANICAL, PLUMBING, AND ELECTRICAL DRAWINGS FOR ADDITIONAL DEMOLITION COORDINATION
5 GENERAL CONTRACTOR SHALL PROVIDE A 6 MIL POLYETHYLENE DUST BARRIER FROM FLOOR TO DECK ABOVE TO
ENSURE THAT ALL CORRIDORS OUTSIDE OF CONSTRUCTION AREA ARE KEPT CLEAN AND CLEAR OF DEBRIS AND
OBSTRUCTIONS AT ALL TIMES. DUST BARRIER SHALL BE SEALED AIR TIGHT IN ALL PHASED AREAS OF CONSTRUCTION
6 UPON COMPLETION OF CONSTRUCTION IN EACH PHASE IT IS THE GENERAL CONTRACTORS RESPONSIBILITY TO
THOROUGHLY CLEAN ALL AREAS IN WHICH CONSTRUCTION TOOK PLACE AND AREAS IMPACTED BY CONSTRUCTION. THE
GENERAL CONTRACTOR SHALL CLEAN ALL CARPET, REMOVE ALL DUST, CLEAN DOORS AND FRAMES, LIGHT FIXTURES,
CEILING SYSTEMS, MECHANICAL GRILLES, ELECTRICAL PANELS, WINDOW SYSTEMS, GLAZING, ETC...
7 GENERAL CONTRACTOR TO PREVENT WATER BUILD-UP AND/OR DAMAGE FOUNDATIONS ON THE CONSTRUCTION SITE OR
ADJACENT AREAS
8 GENERAL CONTRACTOR TO KEEP AN ACTIVE PEDESTRIAN PATHWAY TO AND AT EGRESS ROUTES FREE OF
OBSTRUCTIONS AT ALL TIMES. CONTRACTOR TO PROVIDE PROTECTION TO PEDESTRIANS BEFORE DEMOLITION (IBC 3303)
9 GENERAL CONTRACTOR TO MAINTAIN EXITS, EXISTING STRUCTURAL ELEMENTS, APPLIED FIREPROOFING PROTECTION
DEVICES, AND SANITARY SAFEGUARDS AT ALL TIMES DURING DEMOLITION AND CONSTRUCTION
10 ALL EXISTING FURNITURE TO BE SALVAGED AND RETURNED TO OWNER FOR RE-USE OR SURPLUS
11 CHAIR RAIL, PICTURE RAIL BULLETIN BOARDS, TO BE REMOVED FROM ANY EXISTING WALLS THAT WILL REMAIN, TO BE
PATCHED AND REPAIRD FOR FINAL FINISHES
12 ALL WINDOW COVERINGS TO BE REMOVED AND DISPOSED OF
13 TILE AT REMAINING DRINKING FOUNTAINS WALLS TO BE REMOVED, WALL PATCHED AND REFINISHED PER FINISH
PLANS/ELEVATIONS
14 WINDOW SILLS TO BE REPLACED AT ALL LOCATIONS
KEY PLAN
A
B
1/8" = 1'-0"A1 Level 01 Area A RCP Demolition Plan
KEYED NOTES
02.32 DEMO EXISTING SOFFIT FOR NEW VESTIBULE
16151413121110987
K
H
F
D
B
A
GENERAL COLLECTION A - F
OFFICE OF FACULTY
DEVELOPMENT & MENTORED
RESEARCH
OPEN CLASSROOM /
COMPUTERS
WOMEN'S RR MEN'S RR LIBRARY SCIENCE CLASSROOM
(COMPUTERS)
OFFICE
OFFICE
OFFICE
ELEV
ELEV EQUIP.
MECHANICAL ROOM
CUST.
ENTRY
VESTIBULE
OFFICE
OFFICE
INTERLIBRARY DOCUMENT
PROCESSING
STORAGE OFFICE
SERVICE
DESK
COMPUTERS
02.31
02.55
EXISTING WALLS TO REMAIN
LEGEND
INTERIOR PARTITION STUD AND GYPSUM BOARD WALLS AND/OR
DEMOUNTABLE PARTITIONS, TO BE DEMOLISHED
ACT CEILING TO BE DEMOLISHED
INTERIOR PARTITION NON-REINFORCED CMU/MASONRY WALLS TO BE
DEMOLISHED - PROTECT FLOORS AND SURROUNDING AREAS FROM
DAMAGE
N.I.C.
GYP. BOARD CEILING TO BE DEMOLISHED
SOFFIT TO BE DEMOLISHED
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
10/28/22
D131b
Level 01 Area
B Demolition
RCP Plan
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
GENERAL NOTES - DEMO
1 GENERAL CONTRACTOR SHALL FIELD VERIFY ALL CONDITIONS, MATERIALS, FINISHES, AND DIMENSIONS BEFORE AND
AFTER DEMOLITION, AND TO CONTACT THE ARCHITECT WITH ANY UNFORESEEN CONDITIONS
2 GENERAL CONTRACTOR SHALL PROTECT EXISTING STRUCTURE/ASSEMBLIES/EQUIPMENT AS REQUIRED. REPAIR, PATCH
AND/OR REPLACE EXISTING CONSTRUCTED ITEMS AND EQUIPMENT THAT ARE TO REMAIN AS REQUIRED FOR NEW
CONSTRUCTION
3 GENERAL CONTRACTOR SHALL PATCH AND REPAIR TO MATCH EXISTING FINISHES AT WALLS, FLOORS, CEILINGS/SOFFITS,
ETC... AS REQUIRED IN ARES NOT SPECIFICALLY CALLED OUT IN THE DRAWINGS BUT ARE IMPACTED BY CONSTRUCTION
4 REFER TO MECHANICAL, PLUMBING, AND ELECTRICAL DRAWINGS FOR ADDITIONAL DEMOLITION COORDINATION
5 GENERAL CONTRACTOR SHALL PROVIDE A 6 MIL POLYETHYLENE DUST BARRIER FROM FLOOR TO DECK ABOVE TO
ENSURE THAT ALL CORRIDORS OUTSIDE OF CONSTRUCTION AREA ARE KEPT CLEAN AND CLEAR OF DEBRIS AND
OBSTRUCTIONS AT ALL TIMES. DUST BARRIER SHALL BE SEALED AIR TIGHT IN ALL PHASED AREAS OF CONSTRUCTION
6 UPON COMPLETION OF CONSTRUCTION IN EACH PHASE IT IS THE GENERAL CONTRACTORS RESPONSIBILITY TO
THOROUGHLY CLEAN ALL AREAS IN WHICH CONSTRUCTION TOOK PLACE AND AREAS IMPACTED BY CONSTRUCTION. THE
GENERAL CONTRACTOR SHALL CLEAN ALL CARPET, REMOVE ALL DUST, CLEAN DOORS AND FRAMES, LIGHT FIXTURES,
CEILING SYSTEMS, MECHANICAL GRILLES, ELECTRICAL PANELS, WINDOW SYSTEMS, GLAZING, ETC...
7 GENERAL CONTRACTOR TO PREVENT WATER BUILD-UP AND/OR DAMAGE FOUNDATIONS ON THE CONSTRUCTION SITE OR
ADJACENT AREAS
8 GENERAL CONTRACTOR TO KEEP AN ACTIVE PEDESTRIAN PATHWAY TO AND AT EGRESS ROUTES FREE OF
OBSTRUCTIONS AT ALL TIMES. CONTRACTOR TO PROVIDE PROTECTION TO PEDESTRIANS BEFORE DEMOLITION (IBC 3303)
9 GENERAL CONTRACTOR TO MAINTAIN EXITS, EXISTING STRUCTURAL ELEMENTS, APPLIED FIREPROOFING PROTECTION
DEVICES, AND SANITARY SAFEGUARDS AT ALL TIMES DURING DEMOLITION AND CONSTRUCTION
10 ALL EXISTING FURNITURE TO BE SALVAGED AND RETURNED TO OWNER FOR RE-USE OR SURPLUS
11 CHAIR RAIL, PICTURE RAIL BULLETIN BOARDS, TO BE REMOVED FROM ANY EXISTING WALLS THAT WILL REMAIN, TO BE
PATCHED AND REPAIRD FOR FINAL FINISHES
12 ALL WINDOW COVERINGS TO BE REMOVED AND DISPOSED OF
13 TILE AT REMAINING DRINKING FOUNTAINS WALLS TO BE REMOVED, WALL PATCHED AND REFINISHED PER FINISH
PLANS/ELEVATIONS
14 WINDOW SILLS TO BE REPLACED AT ALL LOCATIONS
KEY PLAN
A
B
1/8" = 1'-0"A1 Level 01 Area B RCP Demolition Plan
KEYED NOTES
02.31 REMOVE EXISTING STAIRWELL, INCLUDING STAIRS, RAILS, AND MASONRY STAIRWELL WALLS. RE: STRUCTURAL
02.55 REMOVE EXISTING WOOD AT SOFFIT.
1
G
J
L
M
N
P
Q
E
C
2 3 4 51.5
GENERAL COLLECTION
G - Z
SERVICE DESK
SPECIAL COLLECTIONS
ARCHIVES
OFFICE
OFFICE
DCAM OFFICE
TECHNICAL SERVICES
4 EXISTING OFFICES?
OFFICE
MCKAY GALLERY MEN'S RR WOMEN'S RR
GRANDIN PRESS
DISPLAY ROOM
GROUP STUDY
ROOMS
GROUP STUDY
ROOMS
COMPUTERS
BREAK ROOM
CUSTODIAL
MAIL ROOM
CONFERENCE ROOM
ELEV MECH
CONFERENCE
ROOM
OFFICE MECH
CHASE
SPECIAL COLLECTIONS STORAGE
COMPUTERS COMPUTERS
VAULT
6
STAIR
2-A
OPEN STUDY
250
EXISTING WALLS TO REMAIN
LEGEND
INTERIOR PARTITION STUD AND GYPSUM BOARD WALLS AND/OR
DEMOUNTABLE PARTITIONS, TO BE DEMOLISHED
ACT CEILING TO BE DEMOLISHED
INTERIOR PARTITION NON-REINFORCED CMU/MASONRY WALLS TO BE
DEMOLISHED - PROTECT FLOORS AND SURROUNDING AREAS FROM
DAMAGE
N.I.C.
GYP. BOARD CEILING TO BE DEMOLISHED
SOFFIT TO BE DEMOLISHED
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
10/28/22
D132a
Level 02 Area
A Demolition
RCP Plan
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
GENERAL NOTES - DEMO
1 GENERAL CONTRACTOR SHALL FIELD VERIFY ALL CONDITIONS, MATERIALS, FINISHES, AND DIMENSIONS BEFORE AND
AFTER DEMOLITION, AND TO CONTACT THE ARCHITECT WITH ANY UNFORESEEN CONDITIONS
2 GENERAL CONTRACTOR SHALL PROTECT EXISTING STRUCTURE/ASSEMBLIES/EQUIPMENT AS REQUIRED. REPAIR, PATCH
AND/OR REPLACE EXISTING CONSTRUCTED ITEMS AND EQUIPMENT THAT ARE TO REMAIN AS REQUIRED FOR NEW
CONSTRUCTION
3 GENERAL CONTRACTOR SHALL PATCH AND REPAIR TO MATCH EXISTING FINISHES AT WALLS, FLOORS, CEILINGS/SOFFITS,
ETC... AS REQUIRED IN ARES NOT SPECIFICALLY CALLED OUT IN THE DRAWINGS BUT ARE IMPACTED BY CONSTRUCTION
4 REFER TO MECHANICAL, PLUMBING, AND ELECTRICAL DRAWINGS FOR ADDITIONAL DEMOLITION COORDINATION
5 GENERAL CONTRACTOR SHALL PROVIDE A 6 MIL POLYETHYLENE DUST BARRIER FROM FLOOR TO DECK ABOVE TO
ENSURE THAT ALL CORRIDORS OUTSIDE OF CONSTRUCTION AREA ARE KEPT CLEAN AND CLEAR OF DEBRIS AND
OBSTRUCTIONS AT ALL TIMES. DUST BARRIER SHALL BE SEALED AIR TIGHT IN ALL PHASED AREAS OF CONSTRUCTION
6 UPON COMPLETION OF CONSTRUCTION IN EACH PHASE IT IS THE GENERAL CONTRACTORS RESPONSIBILITY TO
THOROUGHLY CLEAN ALL AREAS IN WHICH CONSTRUCTION TOOK PLACE AND AREAS IMPACTED BY CONSTRUCTION. THE
GENERAL CONTRACTOR SHALL CLEAN ALL CARPET, REMOVE ALL DUST, CLEAN DOORS AND FRAMES, LIGHT FIXTURES,
CEILING SYSTEMS, MECHANICAL GRILLES, ELECTRICAL PANELS, WINDOW SYSTEMS, GLAZING, ETC...
7 GENERAL CONTRACTOR TO PREVENT WATER BUILD-UP AND/OR DAMAGE FOUNDATIONS ON THE CONSTRUCTION SITE OR
ADJACENT AREAS
8 GENERAL CONTRACTOR TO KEEP AN ACTIVE PEDESTRIAN PATHWAY TO AND AT EGRESS ROUTES FREE OF
OBSTRUCTIONS AT ALL TIMES. CONTRACTOR TO PROVIDE PROTECTION TO PEDESTRIANS BEFORE DEMOLITION (IBC 3303)
9 GENERAL CONTRACTOR TO MAINTAIN EXITS, EXISTING STRUCTURAL ELEMENTS, APPLIED FIREPROOFING PROTECTION
DEVICES, AND SANITARY SAFEGUARDS AT ALL TIMES DURING DEMOLITION AND CONSTRUCTION
10 ALL EXISTING FURNITURE TO BE SALVAGED AND RETURNED TO OWNER FOR RE-USE OR SURPLUS
11 CHAIR RAIL, PICTURE RAIL BULLETIN BOARDS, TO BE REMOVED FROM ANY EXISTING WALLS THAT WILL REMAIN, TO BE
PATCHED AND REPAIRD FOR FINAL FINISHES
12 ALL WINDOW COVERINGS TO BE REMOVED AND DISPOSED OF
13 TILE AT REMAINING DRINKING FOUNTAINS WALLS TO BE REMOVED, WALL PATCHED AND REFINISHED PER FINISH
PLANS/ELEVATIONS
14 WINDOW SILLS TO BE REPLACED AT ALL LOCATIONS
KEY PLAN
A
B
1/8" = 1'-0"A1 Level 02 Area A RCP Demolition Plan
16151413121110987
K
H
F
D
B
A
OFFICEOFFICESTUDYSTUDY
STUDY
STUDY
STUDY
STUDY
CLASSROOM
OFFICE
STORAGE
STORAGE
OFFICE
READING CENTER
MATH CENTER
OFFICE
OFFICE
OFFICE
OFFICE
CLASSROOM
OFFICE OFFICE OFFICE OFFICE OFFICE
STORAGE
OFFICE
CLASSROOMCLASSROOM
OFFICE OFFICE
STORAGE
OFFICE
OPEN TUTORINGOPEN TUTORING /
WRITING CENTER
OPEN TUTORING
22.2122.21
EXISTING WALLS TO REMAIN
LEGEND
INTERIOR PARTITION STUD AND GYPSUM BOARD WALLS AND/OR
DEMOUNTABLE PARTITIONS, TO BE DEMOLISHED
ACT CEILING TO BE DEMOLISHED
INTERIOR PARTITION NON-REINFORCED CMU/MASONRY WALLS TO BE
DEMOLISHED - PROTECT FLOORS AND SURROUNDING AREAS FROM
DAMAGE
N.I.C.
GYP. BOARD CEILING TO BE DEMOLISHED
SOFFIT TO BE DEMOLISHED
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
10/28/22
D132b
Level 02 Area
B Demolition
RCP Plan
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
GENERAL NOTES - DEMO
1 GENERAL CONTRACTOR SHALL FIELD VERIFY ALL CONDITIONS, MATERIALS, FINISHES, AND DIMENSIONS BEFORE AND
AFTER DEMOLITION, AND TO CONTACT THE ARCHITECT WITH ANY UNFORESEEN CONDITIONS
2 GENERAL CONTRACTOR SHALL PROTECT EXISTING STRUCTURE/ASSEMBLIES/EQUIPMENT AS REQUIRED. REPAIR, PATCH
AND/OR REPLACE EXISTING CONSTRUCTED ITEMS AND EQUIPMENT THAT ARE TO REMAIN AS REQUIRED FOR NEW
CONSTRUCTION
3 GENERAL CONTRACTOR SHALL PATCH AND REPAIR TO MATCH EXISTING FINISHES AT WALLS, FLOORS, CEILINGS/SOFFITS,
ETC... AS REQUIRED IN ARES NOT SPECIFICALLY CALLED OUT IN THE DRAWINGS BUT ARE IMPACTED BY CONSTRUCTION
4 REFER TO MECHANICAL, PLUMBING, AND ELECTRICAL DRAWINGS FOR ADDITIONAL DEMOLITION COORDINATION
5 GENERAL CONTRACTOR SHALL PROVIDE A 6 MIL POLYETHYLENE DUST BARRIER FROM FLOOR TO DECK ABOVE TO
ENSURE THAT ALL CORRIDORS OUTSIDE OF CONSTRUCTION AREA ARE KEPT CLEAN AND CLEAR OF DEBRIS AND
OBSTRUCTIONS AT ALL TIMES. DUST BARRIER SHALL BE SEALED AIR TIGHT IN ALL PHASED AREAS OF CONSTRUCTION
6 UPON COMPLETION OF CONSTRUCTION IN EACH PHASE IT IS THE GENERAL CONTRACTORS RESPONSIBILITY TO
THOROUGHLY CLEAN ALL AREAS IN WHICH CONSTRUCTION TOOK PLACE AND AREAS IMPACTED BY CONSTRUCTION. THE
GENERAL CONTRACTOR SHALL CLEAN ALL CARPET, REMOVE ALL DUST, CLEAN DOORS AND FRAMES, LIGHT FIXTURES,
CEILING SYSTEMS, MECHANICAL GRILLES, ELECTRICAL PANELS, WINDOW SYSTEMS, GLAZING, ETC...
7 GENERAL CONTRACTOR TO PREVENT WATER BUILD-UP AND/OR DAMAGE FOUNDATIONS ON THE CONSTRUCTION SITE OR
ADJACENT AREAS
8 GENERAL CONTRACTOR TO KEEP AN ACTIVE PEDESTRIAN PATHWAY TO AND AT EGRESS ROUTES FREE OF
OBSTRUCTIONS AT ALL TIMES. CONTRACTOR TO PROVIDE PROTECTION TO PEDESTRIANS BEFORE DEMOLITION (IBC 3303)
9 GENERAL CONTRACTOR TO MAINTAIN EXITS, EXISTING STRUCTURAL ELEMENTS, APPLIED FIREPROOFING PROTECTION
DEVICES, AND SANITARY SAFEGUARDS AT ALL TIMES DURING DEMOLITION AND CONSTRUCTION
10 ALL EXISTING FURNITURE TO BE SALVAGED AND RETURNED TO OWNER FOR RE-USE OR SURPLUS
11 CHAIR RAIL, PICTURE RAIL BULLETIN BOARDS, TO BE REMOVED FROM ANY EXISTING WALLS THAT WILL REMAIN, TO BE
PATCHED AND REPAIRD FOR FINAL FINISHES
12 ALL WINDOW COVERINGS TO BE REMOVED AND DISPOSED OF
13 TILE AT REMAINING DRINKING FOUNTAINS WALLS TO BE REMOVED, WALL PATCHED AND REFINISHED PER FINISH
PLANS/ELEVATIONS
14 WINDOW SILLS TO BE REPLACED AT ALL LOCATIONS
KEY PLAN
A
B
1/8" = 1'-0"A1 Level 02 Area B RCP Demolition Plan
KEYED NOTES
22.21 ABANDON PIPES IN CMU AND ADD CULINARY PIPING IN NEW FUR OUT WALL.
1
G
J
L
M
N
P
Q
E
C
2 3 4 51.5
JUVENILE COLLECTION
K - 12 BOOKS
OFFICE
SERVICE DESK
TEACHERS LEARNING CENTER
SECURITY DESK
GROUP STUDY GROUP STUDY
DI
E
C
U
T
S
COMPUTERS
COMPUTERS
GROUP STUDY AREA
COMPUTER CLASSROOM
VIDEO
EDITING
VIDEO
EDITING
PHOTO STUDIO
PHOTO SERVICES VOLUNTEER CONNECTION
ELEV
DISABILITY SERVICES
CONFERENCE ROOM FACULTY TECHNOLOGY CENTER
INSTRUCTIONAL DEVELOPMENT
STAGING AREA OFFICE / WORKROOM
HELP DESK AREA
COMPUTER REPAIR
OFFICE
MEN'S RR WOMEN'S RR
CONFERENCE ROOMOFFICE
MUSIC STORAGE
RESEARCH & CREATIVE WORKS
OFFICE SERVER &
STORAGE
OFFICE PRINTER
ROOM
OFFICE
OFFICE
STORAGE
OFFICEINSTRUCTIONAL DEVELOPMENT
STAGING AREA
OFFICE
OFFICE
CUSTODIAL
OFFICE
STORAGE
OFFICE
MECH
CHASE
MECH
CHASE
STORAGE STORAGE
OFFICESPRAY ROOM
OFFICE
OFFICE
OFFICE
6
02.33
STAIR 1
3-B
EXISTING WALLS TO REMAIN
LEGEND
INTERIOR PARTITION STUD AND GYPSUM BOARD WALLS AND/OR
DEMOUNTABLE PARTITIONS, TO BE DEMOLISHED
ACT CEILING TO BE DEMOLISHED
INTERIOR PARTITION NON-REINFORCED CMU/MASONRY WALLS TO BE
DEMOLISHED - PROTECT FLOORS AND SURROUNDING AREAS FROM
DAMAGE
N.I.C.
GYP. BOARD CEILING TO BE DEMOLISHED
SOFFIT TO BE DEMOLISHED
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
10/28/22
D133a
Level 03 Area
A Demolition
RCP Plan
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
GENERAL NOTES - DEMO
1 GENERAL CONTRACTOR SHALL FIELD VERIFY ALL CONDITIONS, MATERIALS, FINISHES, AND DIMENSIONS BEFORE AND
AFTER DEMOLITION, AND TO CONTACT THE ARCHITECT WITH ANY UNFORESEEN CONDITIONS
2 GENERAL CONTRACTOR SHALL PROTECT EXISTING STRUCTURE/ASSEMBLIES/EQUIPMENT AS REQUIRED. REPAIR, PATCH
AND/OR REPLACE EXISTING CONSTRUCTED ITEMS AND EQUIPMENT THAT ARE TO REMAIN AS REQUIRED FOR NEW
CONSTRUCTION
3 GENERAL CONTRACTOR SHALL PATCH AND REPAIR TO MATCH EXISTING FINISHES AT WALLS, FLOORS, CEILINGS/SOFFITS,
ETC... AS REQUIRED IN ARES NOT SPECIFICALLY CALLED OUT IN THE DRAWINGS BUT ARE IMPACTED BY CONSTRUCTION
4 REFER TO MECHANICAL, PLUMBING, AND ELECTRICAL DRAWINGS FOR ADDITIONAL DEMOLITION COORDINATION
5 GENERAL CONTRACTOR SHALL PROVIDE A 6 MIL POLYETHYLENE DUST BARRIER FROM FLOOR TO DECK ABOVE TO
ENSURE THAT ALL CORRIDORS OUTSIDE OF CONSTRUCTION AREA ARE KEPT CLEAN AND CLEAR OF DEBRIS AND
OBSTRUCTIONS AT ALL TIMES. DUST BARRIER SHALL BE SEALED AIR TIGHT IN ALL PHASED AREAS OF CONSTRUCTION
6 UPON COMPLETION OF CONSTRUCTION IN EACH PHASE IT IS THE GENERAL CONTRACTORS RESPONSIBILITY TO
THOROUGHLY CLEAN ALL AREAS IN WHICH CONSTRUCTION TOOK PLACE AND AREAS IMPACTED BY CONSTRUCTION. THE
GENERAL CONTRACTOR SHALL CLEAN ALL CARPET, REMOVE ALL DUST, CLEAN DOORS AND FRAMES, LIGHT FIXTURES,
CEILING SYSTEMS, MECHANICAL GRILLES, ELECTRICAL PANELS, WINDOW SYSTEMS, GLAZING, ETC...
7 GENERAL CONTRACTOR TO PREVENT WATER BUILD-UP AND/OR DAMAGE FOUNDATIONS ON THE CONSTRUCTION SITE OR
ADJACENT AREAS
8 GENERAL CONTRACTOR TO KEEP AN ACTIVE PEDESTRIAN PATHWAY TO AND AT EGRESS ROUTES FREE OF
OBSTRUCTIONS AT ALL TIMES. CONTRACTOR TO PROVIDE PROTECTION TO PEDESTRIANS BEFORE DEMOLITION (IBC 3303)
9 GENERAL CONTRACTOR TO MAINTAIN EXITS, EXISTING STRUCTURAL ELEMENTS, APPLIED FIREPROOFING PROTECTION
DEVICES, AND SANITARY SAFEGUARDS AT ALL TIMES DURING DEMOLITION AND CONSTRUCTION
10 ALL EXISTING FURNITURE TO BE SALVAGED AND RETURNED TO OWNER FOR RE-USE OR SURPLUS
11 CHAIR RAIL, PICTURE RAIL BULLETIN BOARDS, TO BE REMOVED FROM ANY EXISTING WALLS THAT WILL REMAIN, TO BE
PATCHED AND REPAIRD FOR FINAL FINISHES
12 ALL WINDOW COVERINGS TO BE REMOVED AND DISPOSED OF
13 TILE AT REMAINING DRINKING FOUNTAINS WALLS TO BE REMOVED, WALL PATCHED AND REFINISHED PER FINISH
PLANS/ELEVATIONS
14 WINDOW SILLS TO BE REPLACED AT ALL LOCATIONS
KEY PLAN
A
B
1/8" = 1'-0"A1 Level 03 Area A RCP Demolition Plan
KEYED NOTES
02.33 NORTH OF GRIDLINE 'M', REMOVE GYPSUM BOARD CEILING ABOVE THE LAY-IN CEILING.
REF.REF.
1
G
J
L
M
N
P
Q
E
C
2 3 4 5
UNEXCAVATED
D3
A301
D3
A301
C1
A301
C1
A301
TIER 2
016
OFFICE
010
OFFICE
026A
OFFICE
011
BREAK ROOM
013
OFFICE
018
STORAGE
032
OFFICE
012
OFFICE
026C
STUDENTS
026F
TECH ROOM
024
SHORT TERM
STORAGE
028
QA
022A
OFFICE
020
OPS
022
STORAGE
044
CUSTODIAL
STORAGE
042
BDF
040
MEN'S RR
015
WOMEN'S RR
014
ELECTRICAL
038
CUSTODIAL
036
MECH CHASE
034
ELEV
0-JSTAIR
0-E
MECH CHASE
O-F
STAIR
0-E
MECH ROOM
030
CHEMICALS
ROOM
O-D
IMAGING AND
STORAGE
009
OFFICE
026D
OFFICE
026E
OFFICE
026B
HALL
0-C
HALL
0-D
FTE
026
HALL
0-B
HALL
0-A
HALL
0-G
UNEXCAVATED
6
8' - 0"
A417
A1
A417
B5
A417 A2
SIM
A416 A1
SIM
A416 A1
SIM
A416 A1
SIM
A416 A1 SIM
A416A1
SIM
A416
A1 SIM
A416
A1
MIR
A416
SF05SF02
SF04
SF03
SF01
SF06
SF07
A417
C5
SIM
A416
A1
020.2
026A
018.1
0-D
028
011
018.2020.1
022A.2
024
026E 026D 026C 026B
026F
016022
10.12
10.12
10.14
SIM
A422A1
22.07
TI
L
E
W
I
D
T
H
4'
-
1
1
5
/
8
"
022A.1
07.13
07.1307.13
02.53
A416
B4
B5 B5
B4
0-E
D6
A503
D6
A503D6
A503
D6
A503
D6
A503
D6
A503
D6
A503
014015
012 010
A3
2 3/4"
8'
-
3
3
/
4
"
48
"
A417
A3
A. GENERAL CONTRACTOR SHALL FIELD VERIFY ALL CONDITIONS AND SHALL REPORT TO THE ARCHITECT ANY
UNKNOWN CONDITIONS, ERRORS, OR CONFLICTS IN THE DRAWINGS BEFORE BEGINNING WORK
B. DO NOT SCALE THE DRAWINGS
C. ALL EXPOSED INTERIOR STEEL COLUMNS TO BE PAINTED PNT-01 - SEE FINISH SCHEDULE
D. ALL EXPOSED EXTERIOR STEEL TO BE GALVANIZED, UNLESS NOTED OTHERWISE
E. SEE G000'S FOR TYPICAL MOUNTING HEIGHTS. PROVIDE SOLID BLOCKING IN WALLS FOR ALL WALL-MOUNTED
ITEMS WHETHER BLOCKING IS DEPICTED IN DRAWINGS OR NOT
F. COORDINATE ALL EQUIPMENT AND ACCESSORIES, INCLUDING ITEMS THAT ARE OWNER FURNISHED, OWNER
INSTALLED
G. SEE SHEET SERIES A500 FOR WALL AND ASSEMBLY TYPES
H. SEE SHEET SERIES A600 FOR DOOR AND WINDOW TYPES
I. SEE ELEVATIONS AND FINISH SCHEDULES FOR SURFACE TREATMENTS AT WALLS
J. SEE ELEVATIONS, SECTIONS, AND DETAILS FOR ADDITIONAL WALL CONSTRUCTION INFORMATION
K. DOOR OPENINGS ARE TO BE LOCATED 4" FROM THE FACE OF ADJACENT STUD UNLESS NOTED
OTHERWISE.
L. SEE FINISH PLANS AND INTERIOR ELEVATIONS FOR LEVEL 5 WALL FINISH LOCATIONS.
M. SEE SIGNAGE PLAN FOR IN WALL BLOCKING LOCATIONS.
N. ALL EXPOSED VINYL WALL COVERING WRAPPED COLUMNS ARE TO RECIEVE A PAINTED 1/4" GYP BOARD
WRAP DIRECTLY OVER EXISTING WALL
GENERAL NOTES
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
10/28/22
A100a
Level 00 Area
A Floor Plan
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set1/8" = 1'-0"A1 Level 00 Area A Floor Plan KEY PLAN
A
B
KEYED NOTES
02.53 EXISTING KNOX BOX TO REMAIN.
07.13 SEAL ALL PENETRATIONS/HOLES WITH FIRE CAULK AND SAFING TO COMPLETE THE INTEGRITY OF THE RATED
WALL. SEE DIMENSION PLAN FOR WALL TYPE REQUIREMENTS.
10.12 SEMI-RECESSED FIRE EXTINGUISHER CABINET
10.14 BRACKET MOUNTED FIRE EXTINGUISHER
22.07 HI LO DRINKING FOUNTAIN WITH BOTTLE FILLER - ADA COMPLIANT, RE: PLUMBING
16151413121110987
K
H
F
D
B
A
02.40
A. GENERAL CONTRACTOR SHALL FIELD VERIFY ALL CONDITIONS AND SHALL REPORT TO THE ARCHITECT ANY
UNKNOWN CONDITIONS, ERRORS, OR CONFLICTS IN THE DRAWINGS BEFORE BEGINNING WORK
B. DO NOT SCALE THE DRAWINGS
C. ALL EXPOSED INTERIOR STEEL COLUMNS TO BE PAINTED PNT-01 - SEE FINISH SCHEDULE
D. ALL EXPOSED EXTERIOR STEEL TO BE GALVANIZED, UNLESS NOTED OTHERWISE
E. SEE G000'S FOR TYPICAL MOUNTING HEIGHTS. PROVIDE SOLID BLOCKING IN WALLS FOR ALL WALL-MOUNTED
ITEMS WHETHER BLOCKING IS DEPICTED IN DRAWINGS OR NOT
F. COORDINATE ALL EQUIPMENT AND ACCESSORIES, INCLUDING ITEMS THAT ARE OWNER FURNISHED, OWNER
INSTALLED
G. SEE SHEET SERIES A500 FOR WALL AND ASSEMBLY TYPES
H. SEE SHEET SERIES A600 FOR DOOR AND WINDOW TYPES
I. SEE ELEVATIONS AND FINISH SCHEDULES FOR SURFACE TREATMENTS AT WALLS
J. SEE ELEVATIONS, SECTIONS, AND DETAILS FOR ADDITIONAL WALL CONSTRUCTION INFORMATION
K. DOOR OPENINGS ARE TO BE LOCATED 4" FROM THE FACE OF ADJACENT STUD UNLESS NOTED
OTHERWISE.
L. SEE FINISH PLANS AND INTERIOR ELEVATIONS FOR LEVEL 5 WALL FINISH LOCATIONS.
M. SEE SIGNAGE PLAN FOR IN WALL BLOCKING LOCATIONS.
N. ALL EXPOSED VINYL WALL COVERING WRAPPED COLUMNS ARE TO RECIEVE A PAINTED 1/4" GYP BOARD
WRAP DIRECTLY OVER EXISTING WALL
GENERAL NOTES
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
10/28/22
A100b
Level 00 Area
B Floor Plan
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
KEY PLAN
A
B
1/8" = 1'-0"A1 Level 00 Area B Floor Plan
KEYED NOTES
02.40 EXISTING UNDERGROUND TUNNEL. ALL TRADES TO COORDINATE ACCORDINGLY.
RE
F
.
RE
F
.
DN
1
1
16
16
15
15
14
14
13
13
12
12
11
11
10
10
9
9
8
87
K
H
F
D
B
A
G
J
LL
MM
NN
PP
QQ
E
C
2
2
3
3
4
4
5
5
1.5
1.5
OFFICE
131
CHECK-IN
112
OFFICE
129
OFFICE
130
STUDY (MED)
132
OFFICE
136
RECEPTION
134
OFFICE
138
CONFERENCE
ROOM
140BREAKROOM
142
STORAGE
170C
STUDY
170B
STUDY
170A
CLASSROOM
168
CLASSROOM
166
ADJUNCT
OFFICE
180
OFFICE
181
OFFICE
182
OFFICE
183
OFFICE
184
OFFICE
185
OFFICE
186
CONFERENCE
ROOM
158
CONFERENCE
188B
COLLABORATIVE
SPACE
188
STUDY (SM)
128
STUDY (MED)
124
STUDY (MED)
125
STUDY (SM)
126
STUDY (SM)
127
OPEN STUDY
122A
HD BOOK
COLLECTION
122
VESTIBULE
1-F
CIRCULATION
RECEPTION
110
OFFICE
108
INTER LIBRARY
LOAN
WORKSPACE
114
FAMILY RR
144
OPEN STUDY
122C
OPEN STUDY
122B
CLASSROOM
162
CLASSROOM
164
OFFICE
190B
OFFICE
190A
TRAINING AREA
190
OFFICE
192B
SMALL MEETING
192A
OFFICE
160A
OFFICE
160B
TUTORING
ADMIN OPEN
AREA
160
OFFICE
156F
PRACTICE
156E
WORKSPACE
156
STORAGE
156D
DROP IN MATH
LAB
170
WORKSTATIONS/
FLEX SPACE
192
CLASSROOM
172
STUDENT PREP
174
STUDY
178
STUDY
179
MATH LAB
RECEPTION
175
I.T. HELP DESK
176
OPEN STUDY
118
MENS
146
WOMENS
148
JANITORS
OFFICE
147
OFFICE
188A
OFFICE
106
OFFICE
104
STORAGE
190C
STORAGE
192C
PRACTICE
156C
PRACTICE
156B
PRACTICE
156A
OFFICE
114A
VESTIBULE
1-U
ELECTRICAL
173
VESTIBULE
1-Z
MECH
08
ELEV EQUIP
08A
ELEV
1-T
MEN'S
RESTROOM
154
WOMEN'S
RESTROOM
152
STAIR
1-H
STAIR
1-B VESTIBULE
1-A
HALL
1-S
HALL
1-R
READING
150
HALL
1-P
STAIRS
1-N
MECH
1-Q
HALL
1-V
HALL
1-X
HALL
1-Y
ENTRY HALL
120A
OPEN STUDY
100
6
6
ELEVATOR
1-J
MECH CHASE
1-K
A. GENERAL CONTRACTOR SHALL FIELD VERIFY ALL CONDITIONS AND SHALL REPORT TO THE ARCHITECT ANY
UNKNOWN CONDITIONS, ERRORS, OR CONFLICTS IN THE DRAWINGS BEFORE BEGINNING WORK
B. DO NOT SCALE THE DRAWINGS
C. ALL EXPOSED INTERIOR STEEL COLUMNS TO BE PAINTED PNT-01 - SEE FINISH SCHEDULE
D. ALL EXPOSED EXTERIOR STEEL TO BE GALVANIZED, UNLESS NOTED OTHERWISE
E. SEE G000'S FOR TYPICAL MOUNTING HEIGHTS. PROVIDE SOLID BLOCKING IN WALLS FOR ALL WALL-MOUNTED
ITEMS WHETHER BLOCKING IS DEPICTED IN DRAWINGS OR NOT
F. COORDINATE ALL EQUIPMENT AND ACCESSORIES, INCLUDING ITEMS THAT ARE OWNER FURNISHED, OWNER
INSTALLED
G. SEE SHEET SERIES A500 FOR WALL AND ASSEMBLY TYPES
H. SEE SHEET SERIES A600 FOR DOOR AND WINDOW TYPES
I. SEE ELEVATIONS AND FINISH SCHEDULES FOR SURFACE TREATMENTS AT WALLS
J. SEE ELEVATIONS, SECTIONS, AND DETAILS FOR ADDITIONAL WALL CONSTRUCTION INFORMATION
K. DOOR OPENINGS ARE TO BE LOCATED 4" FROM THE FACE OF ADJACENT STUD UNLESS NOTED
OTHERWISE.
L. SEE FINISH PLANS AND INTERIOR ELEVATIONS FOR LEVEL 5 WALL FINISH LOCATIONS.
M. SEE SIGNAGE PLAN FOR IN WALL BLOCKING LOCATIONS.
N. ALL EXPOSED VINYL WALL COVERING WRAPPED COLUMNS ARE TO RECIEVE A PAINTED 1/4" GYP BOARD
WRAP DIRECTLY OVER EXISTING WALL
GENERAL NOTES
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
10/28/22
A101
Level 01
Overall Floor
Plan
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
1/16" = 1'-0"A1 Level 01 Overall Floor Plan KEY PLAN
A
B
RE
F
.
DN
1
G
J
L
M
NN
PP
QQ
EE
CC
2 3 4 5
D3
A301
D3
A301
C1
A301
C1
A301
1.5
OFFICE
129
OFFICE
130
OFFICE
131
STUDY (MED)
132 OFFICE
136
RECEPTION
134
OFFICE
138
CONFERENCE
ROOM
140
BREAKROOM
142
STUDY (SM)
128
STUDY (MED)
124
STUDY (MED)
125
STUDY (SM)
126
STUDY (SM)
127
OPEN STUDY
122A
HD BOOK
COLLECTION
122
VESTIBULE
1-F
OFFICE
108
INTER LIBRARY
LOAN
WORKSPACE
114
FAMILY RR
144
OPEN STUDY
122C
OPEN STUDY
122B
MENS
146
WOMENS
148
JANITORS
OFFICE
147
OFFICE
106
OFFICE
104
CHECK-IN
112
OFFICE
114A
MECH CHASE
1-G
ELEVATOR
1-JSTAIR
1-H
MECH CHASE
1-K
Room
1-L
Room
1-M
CIRCULATION
RECEPTION
110
RESERVE MEDIA
116
MECH
1-E
HALLWAY
1-C
STAIR
1-D
ELEC ROOM
102
ENTRY HALL
120A
STAIR
1-B
VESTIBULE
1-A
A416
A4
A5
D1
A412
E1
A411
OPAC
OPAC
130
131
136
138
140142.1
144
1-F.3
1-F.4
1-F.2
1-F.1
102
104
108
106
142.2
1-F.5
132
124
125
127
129
6
A1
A415
TUNNEL
BELOW
TUNNEL
BELOW
A416 D1
A416
E3
A416
E1
A416C1
D6
A511
A5
A511
TYPA6
A511
E6
A511
TYPA6
A511
SIM.
A416 D3
SIM
A416
A4
SIM
A416
A5
SIM
A416
A4
SIM
A416
A4
A5
A4
A5
126
128
126
A416 B1
A416
B2
A416B3
SIM
A416 A5
SIM
A416
A1
SIM
A416
A1
SIM
A416A1
SIM
A416A4 SIM
A416A1
SIM
A416
A1
A417
B2
B3
B1
CIRCULATION
RECEPTION
110
OPEN STUDY
118
A416
C4
A422A1
MIR
A416
B2
MIR
A416 B3
SF19A
SF10 SF08
SF11
SF09
SF17
SF12
SF13
SF14
SF15
SF16
114A
1-B.1
1-B.2
SIM
A416
A1
SIM
A416
A1
SIM
A416
A1
B5
A511
D5
A551
TYP.
E5
A551
E6
A551
E6
A551
TYPA6
A511
22.19
SF19B
10.19
10.19
10.19
10.19 22.07
10.12
10.12
10.12
10.12
B4
A511
A416
E5
SIM
A416
C4
SIM
A416
C4
A416
C5
10.12
SIM
A416
C5
A419
B1
A419
B2
D1
A415
TI
L
E
W
I
D
T
H
5'
-
4
3
/
4
"
03.14
A416
A1
A421 B5
B5
A311
TYP.
11.11
11.11
11.11
11.11
11.11
11.11
1-H
134
A422
B3
B2
SF18
1'-8 1/4"
4'
-
0
3
/
4
"
EQEQ
4'
-
0
3
/
4
"
2'-8"
EQ EQ
148
1415 SF
147
146
READING
150
SIM
A416
E5
SIM
A416
C4
10.17
08.18
08.18
08.17
08.17
08.17
A422
D5
B2
A431
D6
A511
A5
A511
A5
A511
A5
A511
D6
A511
D6
A511
D6
A511
E6
A511
E5
A551
D6
A511
C6
A551
C6
A551
C6
A551
C6
A551
C5
A551
C6
A551
C6
A551
C6
A551
C6
A551
C6
A551
C6
A551
C6
A551
C6
A551
36
"
2"
4
5
/
8
"
A. GENERAL CONTRACTOR SHALL FIELD VERIFY ALL CONDITIONS AND SHALL REPORT TO THE ARCHITECT ANY
UNKNOWN CONDITIONS, ERRORS, OR CONFLICTS IN THE DRAWINGS BEFORE BEGINNING WORK
B. DO NOT SCALE THE DRAWINGS
C. ALL EXPOSED INTERIOR STEEL COLUMNS TO BE PAINTED PNT-01 - SEE FINISH SCHEDULE
D. ALL EXPOSED EXTERIOR STEEL TO BE GALVANIZED, UNLESS NOTED OTHERWISE
E. SEE G000'S FOR TYPICAL MOUNTING HEIGHTS. PROVIDE SOLID BLOCKING IN WALLS FOR ALL WALL-MOUNTED
ITEMS WHETHER BLOCKING IS DEPICTED IN DRAWINGS OR NOT
F. COORDINATE ALL EQUIPMENT AND ACCESSORIES, INCLUDING ITEMS THAT ARE OWNER FURNISHED, OWNER
INSTALLED
G. SEE SHEET SERIES A500 FOR WALL AND ASSEMBLY TYPES
H. SEE SHEET SERIES A600 FOR DOOR AND WINDOW TYPES
I. SEE ELEVATIONS AND FINISH SCHEDULES FOR SURFACE TREATMENTS AT WALLS
J. SEE ELEVATIONS, SECTIONS, AND DETAILS FOR ADDITIONAL WALL CONSTRUCTION INFORMATION
K. DOOR OPENINGS ARE TO BE LOCATED 4" FROM THE FACE OF ADJACENT STUD UNLESS NOTED
OTHERWISE.
L. SEE FINISH PLANS AND INTERIOR ELEVATIONS FOR LEVEL 5 WALL FINISH LOCATIONS.
M. SEE SIGNAGE PLAN FOR IN WALL BLOCKING LOCATIONS.
N. ALL EXPOSED VINYL WALL COVERING WRAPPED COLUMNS ARE TO RECIEVE A PAINTED 1/4" GYP BOARD
WRAP DIRECTLY OVER EXISTING WALL
GENERAL NOTES
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
10/28/22
A101a
Level 01 Area
A Floor Plan
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
KEY PLAN
A
B
1/8" = 1'-0"A1 Level 01 Area A Floor Plan
KEYED NOTES
03.14 FLOAT AND INFILL RECESSED SLAB AREA. THE NEW FLOATED FLOOR IS TO BE FLUSH WITH ADJACENT FLOOR. -SEE
FINISH PLAN FOR FLOOR COVERING.
08.17 SURFACE MOUNTED WIRED ADA ACTUATOR, RE: ELECT.
08.18 JAMB MOUNTED WIRED ADA ACTUATOR, RE: ELECT.
10.12 SEMI-RECESSED FIRE EXTINGUISHER CABINET
10.17 SURFACE MOUNTED KNOX BOX
10.19 HIGH DENSITY LIBRARY MANUAL BOOK STORAGE - B.O.D. SPACE SAVER
11.11 ROOM SCHEDULER, SEE ELECTRICAL DRAWINGS.
22.07 HI LO DRINKING FOUNTAIN WITH BOTTLE FILLER - ADA COMPLIANT, RE: PLUMBING
22.19 HI LO DRINKING FOUNTAIN - ADA COMPLIANT, RE: PLUMBING
RE
F
.
16
16
15
15
14
14
13
13
12
12
11
11
10
10
9
9
8
8
7
7
K
H
F
D
B
A
C1
A301
C1
A301
A4
A301
A4
A301
B3
A301
B3
A301
STORAGE
170C
STUDY
170B
STUDY
170A
CLASSROOM
168
CLASSROOM
166
ADJUNCT
OFFICE
180
OFFICE
181
OFFICE
182
OFFICE
183
OFFICE
184
OFFICE
185
OFFICE
186
CONFERENCE
ROOM
158
CONFERENCE
188B
COLLABORATIVE
SPACE
188
CLASSROOM
162
CLASSROOM
164
OFFICE
190B
OFFICE
190A
TRAINING AREA
190
OFFICE
192B
SMALL MEETING
192A
OFFICE
160A
OFFICE
160B
TUTORING
ADMIN OPEN
AREA
160
OFFICE
156F
PRACTICE
156E
WORKSPACE
156
STORAGE
156D
DROP IN MATH
LAB
170
WORKSTATIONS/
FLEX SPACE
192
CLASSROOM
172
STUDENT PREP
174
STUDY
178
STUDY
179
MATH LAB
RECEPTION
175
I.T. HELP DESK
176
OFFICE
188A
STORAGE
190C
STORAGE
192C
PRACTICE
156C
PRACTICE
156B
PRACTICE
156A
ELECTRICAL
173
VESTIBULE
1-U
HALL
1-X
VESTIBULE
1-Z
HALL
1-Y
HALL
1-V
B1
A412
D1
A414
MEN'S
RESTROOM
154
WOMEN'S
RESTROOM
152
HALL
1-P
STAIRS
1-N
ELEV
1-T
ELEV EQUIP
08A
MECH
08
A422
A5
SIM
A416A1
SIM
A416 A1
A416A1A416A1
SIM
A416 A1
SIM
A416 A1
SIM
A416 A1
SIM
A416 A1
SIM
A416A1
SIM
A416A1
SIM
A416A1
SIM
A416
A513
A2
A420
D3
A420 D2
A416A2 A3
SIM
A416
A2
SIM
A416
A2
SIM
A416
A2
A3
A3
A3
A418
E4
E5
A420D4
A420B5
B1
B2
B3
SIM
A416A5 A5
SIM
A416A5 A5
A418D5
D1
B1
A411
D3
D2
A417
B4
190
166 168162164
192A
156E
1-U.1
170C
172
174
188B
1-V
190C
180
170.1
158
192B
156
156C
156B
156A
156D
188
192C
192
1-X
160B160A
156F
190B190A
186 185 183 182184 181
179
188A
1-U.2
1-U.41-U.3
SF26
SF23
SF21
SF30
SF32
SF34
SF20
SF29
SF22
SF25
SF31
A417C4
SF24A
178
SF24B
170.2
A419 B5
A420
A1
A420E3 E1
C3
A417C2 C1
A418
E1
A418
E3
SIM
D1
D2
SIM
A420
B3
B5 B2
A420
C1
C2
C3
C5
22.19
10.12
22.07
22.19
10.12 10.12
E6
A551
E6
A551
E6
A551
E6
A551
10.14 10.12
10.12
E5
A551
E5
A551
SIM
A422
A1
SIM
A422
A1
D5
D1
SIM
A416 A5
SIM
A416A5
A421
D2
A418D5
A418
C1
TILE WIDTH
4' - 8"
TILE WIDTH
5' - 4 1/4"
A1
A413
D1
A513
A421D3
SF27SF28
170A 170B
SF33
D3
A513
HALL
1-R
HALL
1-S
A1 A3
E2
C1
A411
SIM
A416
A1
A1
A422 D2
D6
A503
D6
A503
D6
A503
D6
A503
154152
1-N
173
A422
B5
08.16
08.16
10.16
08.16
E1-Z.3
E1-Z.6
08.17
08.17
TYPA6
A511
C5
A551 TYP.
C5
A551 TYP.
C5
A551 TYP.
C5
A551
TYP.C5
A551
TYP.
C5
A551 TYP.
(RELOCATE EXISTING)
(RELOCATE EXISTING)
10.17
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
10/28/22
A101b
Level 01 Area
B Floor Plan
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
KEY PLAN
A
B
1/8" = 1'-0"A1 Level 01 Area B Floor Plan
GENERAL NOTES - FLOOR PLAN
1 GENERAL CONTRACTOR SHALL FIELD VERIFY ALL CONDITIONS AND SHALL REPORT TO THE ARCHITECT ANY UNKNOWN
CONDITIONS, ERRORS, OR CONFLICTS IN THE DRAWINGS BEFORE BEGINNING WORK
2 DO NOT SCALE THE DRAWINGS
3 SEE G000's FOR TYPICAL MOUNTING HEIGHTS. PROVIDE SOLID BLOCKING IN WALLS FOR ALL WALL-MOUNTED ITEMS
WHETHER BLOCKING IS DEPICTED IN DRAWINGS OR NOT
4 COORDINATE ALL EQUIPMENT AND ACCESSORIES, INCLUDING ITEMS THAT ARE OWNER FURNISHED, OWNER INSTALLED
5 SEE SHEET SERIES A500's FOR WALL AND ASSEMBLY TYPES
6 SEE SHEET SERIES A600's FOR DOOR AND WINDOW TYPES
7 SEE ELEVATIONS AND FINISH SCHEDULES FOR SURFACE TREATMENTS AT WALLS
8 SEE ELEVATIONS, SECTIONS, AND DETAILS FOR ADDITIONAL WALL CONSTRUCTION INFORMATION
9 ELECTRICIAN SHALL NOT SET ANY CEILING J-BOXES THAT ARE FOR LIGHTS BEFORE THE FINAL LOCATION OF THE
DROPPED SOFFITS HAVE BEEN DETERMINED. THIS WILL ENSURE THAT THE LIGHTS THAT NEED TO BE CENTERED ARE
CORRECTLY CENTERED BETWEEN THE SOFFITS
10 DOOR OPENINGS IN FRAME CONSTRUCTION WITH NO SPECIFIED DIMENSION ARE EITHER CENTERED IN THE LENGTH OF
WALL RUN OR (IF DRAWN NEAR CORNER) LOCATED 4" FROM THE FACE OF ADJACENT STUD. ASSUME CENTERED IN FACE
OF JAMB UNLESS NOTED OTHERWISE
11 ALL EXPOSED CONCRETE COLUMNS ARE TO BE FURRED/WRAPPED SEE COLUMN PLAN DETAILS, SEE ELECTRICAL FOR
OUTLET COORDINATION
KEYED NOTES
08.16 FULLY RECESSED WIRED ADA ACTUATOR, RE: ELECT.
08.17 SURFACE MOUNTED WIRED ADA ACTUATOR, RE: ELECT.
10.12 SEMI-RECESSED FIRE EXTINGUISHER CABINET
10.14 BRACKET MOUNTED FIRE EXTINGUISHER
10.16 FULLY RECESSED KNOX BOX
10.17 SURFACE MOUNTED KNOX BOX
22.07 HI LO DRINKING FOUNTAIN WITH BOTTLE FILLER - ADA COMPLIANT, RE: PLUMBING
22.19 HI LO DRINKING FOUNTAIN - ADA COMPLIANT, RE: PLUMBING
REF.
REF.
1
1 16
15
15
14
14
13
13
12
12
11
11
10
10
9
9
8
8
7
7
K
H
F
D
B
A
G
J
LL
MM
NN
PP
QQ
E
C
2
2
3
3
4
4
5
5
1.5
1.5
ELECTRICAL
ROOM
242
TECH SERV
STORAGE
2-E
TECH SERVICES
238
SHEET MUSIC
236
LARGE
COMPUTER
CLASSROOM
234
OPEN
COMPUTERS
240
MOTHERS
243
OPEN STUDY
53
PRESS ROOM
226
SPECIAL
COLLECTIONS
228
VAULT
228E
ARCHIVE
228D
INSTRUCTION 2
224
INSTRUCTION 1
222
DCAM
228B
OFFICE
228A
SCANNER
228C
OFFICE
232
STUDY (MED)
216
STUDY (MED)
214
STUDY (MED)
218
CLASSROOM
272
OFFICE
288B
OFFICE
288C
ENGLISH
TRANSITION
CENTER
288
STUDY (SM)
204
OPEN TUTORING
254
STUDY SKILLS
252
WRITING
CENTER OPEN
TUTORING
256
STUDY
269
STUDY
268
STUDY
267
STUDY
266
OFFICE
265
OFFICE
264
STORAGE
270J
STUDY
270H
JANITOR'S
OFFICE
241
PREP /
STORAGE
270B
CLASSROOM
258
CLASSROOM
260
PREP /
STORAGE
256A
OFFICE
256B OFFICE
256C
OPEN TUTORING
CENTER
270
OFFICE
230
OFFICE
202
STUDY (SM)
212 STUDY (SM)
210
STUDY (SM)
208
OFFICE
200
OPEN STUDY
220
ADJUNCT
OFFICE
286
TR / COMM.
280
MECHANICAL
2-D
CLASSROOM
278
PRE-FUNCTION
270C
PRE-FUNCTION
270D
PRE-FUNCTION
270E
RECEPTION
270A
PREFUNCTION
270F
I.T.
245
STORAGE
288H
STUDY
252B
PREP /
STORAGE
252G
OFFICE
252E
STORAGE
252F
OFFICE
252D
STUDY
252A
STUDY
252C
MEN'S
RESTROOM
247
WOMEN'S
RESTROOM
248
STAIR
2-G
ELEV
2-H
MECH CHASE
2-J
STAIR
2-A
STAIR
2-B
STUDY
270G
ELEV
2-R
OPEN STUDY
250
MECH
2-C
HALL
2-K
STAIR
2-P
STOR
299
WOMEN'S
RESTROOM
284
MEN'S
RESTROOM
282
MECH
2-T
CLASSROOM
276
CLASSROOM
274
Room
2-S
HALL
2-Q
HALL
2-U
HALL
2-W
6
6
FAMILY RR
244
STUDY (MED)
206
JANITOR'S
CLOSET
249
STUDY
288G
STUDY
288F
STUDY
288E
STUDY
288D
STUDY
288A
IT
241A
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
10/28/22
A102
Level 02
Overall Floor
Plan
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
1/16" = 1'-0" (REF: A1/A201)
A1 Level 02 Overall Floor Plan
GENERAL NOTES - FLOOR PLAN
1 GENERAL CONTRACTOR SHALL FIELD VERIFY ALL CONDITIONS AND SHALL REPORT TO THE ARCHITECT ANY UNKNOWN
CONDITIONS, ERRORS, OR CONFLICTS IN THE DRAWINGS BEFORE BEGINNING WORK
2 DO NOT SCALE THE DRAWINGS
3 SEE G000's FOR TYPICAL MOUNTING HEIGHTS. PROVIDE SOLID BLOCKING IN WALLS FOR ALL WALL-MOUNTED ITEMS
WHETHER BLOCKING IS DEPICTED IN DRAWINGS OR NOT
4 COORDINATE ALL EQUIPMENT AND ACCESSORIES, INCLUDING ITEMS THAT ARE OWNER FURNISHED, OWNER INSTALLED
5 SEE SHEET SERIES A500's FOR WALL AND ASSEMBLY TYPES
6 SEE SHEET SERIES A600's FOR DOOR AND WINDOW TYPES
7 SEE ELEVATIONS AND FINISH SCHEDULES FOR SURFACE TREATMENTS AT WALLS
8 SEE ELEVATIONS, SECTIONS, AND DETAILS FOR ADDITIONAL WALL CONSTRUCTION INFORMATION
9 ELECTRICIAN SHALL NOT SET ANY CEILING J-BOXES THAT ARE FOR LIGHTS BEFORE THE FINAL LOCATION OF THE
DROPPED SOFFITS HAVE BEEN DETERMINED. THIS WILL ENSURE THAT THE LIGHTS THAT NEED TO BE CENTERED ARE
CORRECTLY CENTERED BETWEEN THE SOFFITS
10 DOOR OPENINGS IN FRAME CONSTRUCTION WITH NO SPECIFIED DIMENSION ARE EITHER CENTERED IN THE LENGTH OF
WALL RUN OR (IF DRAWN NEAR CORNER) LOCATED 4" FROM THE FACE OF ADJACENT STUD. ASSUME CENTERED IN FACE
OF JAMB UNLESS NOTED OTHERWISE
11 ALL EXPOSED CONCRETE COLUMNS ARE TO BE FURRED/WRAPPED SEE COLUMN PLAN DETAILS, SEE ELECTRICAL FOR
OUTLET COORDINATION
KEY PLAN
A
B
GENERAL NOTES - FLOOR PLAN
1 GENERAL CONTRACTOR SHALL FIELD VERIFY ALL CONDITIONS AND SHALL REPORT TO THE ARCHITECT ANY UNKNOWN
CONDITIONS, ERRORS, OR CONFLICTS IN THE DRAWINGS BEFORE BEGINNING WORK
2 DO NOT SCALE THE DRAWINGS
3 SEE G000's FOR TYPICAL MOUNTING HEIGHTS. PROVIDE SOLID BLOCKING IN WALLS FOR ALL WALL-MOUNTED ITEMS
WHETHER BLOCKING IS DEPICTED IN DRAWINGS OR NOT
4 COORDINATE ALL EQUIPMENT AND ACCESSORIES, INCLUDING ITEMS THAT ARE OWNER FURNISHED, OWNER INSTALLED
5 SEE SHEET SERIES A500's FOR WALL AND ASSEMBLY TYPES
6 SEE SHEET SERIES A600's FOR DOOR AND WINDOW TYPES
7 SEE ELEVATIONS AND FINISH SCHEDULES FOR SURFACE TREATMENTS AT WALLS
8 SEE ELEVATIONS, SECTIONS, AND DETAILS FOR ADDITIONAL WALL CONSTRUCTION INFORMATION
9 ELECTRICIAN SHALL NOT SET ANY CEILING J-BOXES THAT ARE FOR LIGHTS BEFORE THE FINAL LOCATION OF THE
DROPPED SOFFITS HAVE BEEN DETERMINED. THIS WILL ENSURE THAT THE LIGHTS THAT NEED TO BE CENTERED ARE
CORRECTLY CENTERED BETWEEN THE SOFFITS
10 DOOR OPENINGS IN FRAME CONSTRUCTION WITH NO SPECIFIED DIMENSION ARE EITHER CENTERED IN THE LENGTH OF
WALL RUN OR (IF DRAWN NEAR CORNER) LOCATED 4" FROM THE FACE OF ADJACENT STUD. ASSUME CENTERED IN FACE
OF JAMB UNLESS NOTED OTHERWISE
11 ALL EXPOSED CONCRETE COLUMNS ARE TO BE FURRED/WRAPPED SEE COLUMN PLAN DETAILS, SEE ELECTRICAL FOR
OUTLET COORDINATION
1
G
J
L
M
N
P
Q
E
C
2 3 4 5
D3
A301
D3
A301
C1
A301
C1
A301
1.5
TECH SERVICES
238
SHEET MUSIC
236 LARGE
COMPUTER
CLASSROOM
234
OPEN
COMPUTERS
240
MOTHERS
243
OPEN STUDY
53
PRESS ROOM
226
SPECIAL
COLLECTIONS
228
VAULT
228E
ARCHIVE
228D
INSTRUCTION 2
224
INSTRUCTION 1
222
DCAM
228B
OFFICE
228A
SCANNER
228C
OFFICE
232
STUDY (MED)
216
STUDY (MED)
214
STUDY (MED)
218
OFFICE
230
OFFICE
202
STUDY (SM)
212
STUDY (SM)
210
STUDY (SM)
208
OFFICE
200
OPEN STUDY
220
ELECTRICAL
ROOM
242
I.T.
245
STUDY (SM)
204
JANITOR'S
OFFICE
241
MECHANICAL
2-D
TECH SERV
STORAGE
2-E
NEW OPENING
MECH
2-C
STAIR
2-A
MECH CHASE
2-F
STAIR
2-G
ELEV
2-H
MECH CHASE
2-J
HALL
2-K
MEN'S
RESTROOM
247
WOMEN'S
RESTROOM
248
Room
2-M
HALL
2-M
STAIR
2-B
D1
A411
A417
D1
E4
230.2
6
FAMILY RR
244
20
'
-
2
1
/
2
"
D6
A511
E6
A511
A5
A511
TYPA6
A511
TYP.
TYP.
TYPA6
A511SIM.
TYP.
STUDY (MED)
206
A417 E1
A417 E2
JANITOR'S
CLOSET
249
A1
A411
SIM
A422A1
SF39 SF38 SF37 SF36
SF35
SF42 SF41 SF40
SF43 SF44
SF45
SF46
238
236
234
249
228
226224.2
202
222.1
224.1
241A
232.2
242
2-E
2-D
228D
228A.1
228E
228C
228B
212 210 208 206
204
222.2 224.3
232.1
230.1
200
218
243
244
216 214
228A.2
2-A.1
2-A.2
2-A.3
2-A.4
2-A.1
2-A.2
2-A.3
2-A.4
2-A.1
2-A.2
2-A.1
2-A.3
2-A.2
2-A.4
SIM
A416 A5
SIM
A416 A4
SIM
A416 A4A5A5
SIM
A416 A4
SIM
A416 A4
SIM
A416 A5
SIM
A416A4
SIM
A416
A5
A4
SIM
A416
SIM
A416
SIM
A416
SIM
A416
SIM
A416
E6
A551
E6
A551
10.27
10.27
10.12
10.12
10.12
22.07
22.19
10.12
10.14
07.12
E5
A551
E5
A551
E6
A551
10.12
10.12
SIM
A416
A422E4
A420
A2
A420
A3
A4A4A5
A5
E3
A415
MIR
A420
A2
MIR
A420
A3
TI
L
E
W
I
D
T
H
5'
-
4
3
/
4
"
A421
C3
A421
D4
E2
A421A2
11.11 11.11 11.11 11.11
11.11
11.1111.1111.11
OPEN STUDY
250
IT
241A
241
D5
A551
TYP.
A1
A1
A1
A1A1
A1
222M
224M
TYP.
2-G
2-B
E6
A512
E5
A512
23
'
-
2
1
/
2
"
17
'
-
8
"
E1
CLOSET
222a
CLOSET
224a
A422C3
26.08
06.15
248247
245
C1
A413
A422
D5
SIM
A422 C4
E6
A511
A5
A511
A5
A511
A5
A511
D6
A511
D6
A511
D6
A511
E6
A511
D6
A511
D6
A511
D6
A511
TYPA6
A511
C6
A551
TYP.
C6
A551
C6
A551
C6
A551
C6
A551
C6
A551
C6
A551
C6
A551
C6
A551 TYP.
C6
A551 TYP.
C6
A551
TYP.
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
10/28/22
A102a
Level 02 Area
A Floor Plan
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
KEY PLAN
A
B
1/8" = 1'-0"A1 Level 02 Area A Floor Plan
GENERAL NOTES - FLOOR PLAN
1 GENERAL CONTRACTOR SHALL FIELD VERIFY ALL CONDITIONS AND SHALL REPORT TO THE ARCHITECT ANY UNKNOWN
CONDITIONS, ERRORS, OR CONFLICTS IN THE DRAWINGS BEFORE BEGINNING WORK
2 DO NOT SCALE THE DRAWINGS
3 SEE G000's FOR TYPICAL MOUNTING HEIGHTS. PROVIDE SOLID BLOCKING IN WALLS FOR ALL WALL-MOUNTED ITEMS
WHETHER BLOCKING IS DEPICTED IN DRAWINGS OR NOT
4 COORDINATE ALL EQUIPMENT AND ACCESSORIES, INCLUDING ITEMS THAT ARE OWNER FURNISHED, OWNER INSTALLED
5 SEE SHEET SERIES A500's FOR WALL AND ASSEMBLY TYPES
6 SEE SHEET SERIES A600's FOR DOOR AND WINDOW TYPES
7 SEE ELEVATIONS AND FINISH SCHEDULES FOR SURFACE TREATMENTS AT WALLS
8 SEE ELEVATIONS, SECTIONS, AND DETAILS FOR ADDITIONAL WALL CONSTRUCTION INFORMATION
9 ELECTRICIAN SHALL NOT SET ANY CEILING J-BOXES THAT ARE FOR LIGHTS BEFORE THE FINAL LOCATION OF THE
DROPPED SOFFITS HAVE BEEN DETERMINED. THIS WILL ENSURE THAT THE LIGHTS THAT NEED TO BE CENTERED ARE
CORRECTLY CENTERED BETWEEN THE SOFFITS
10 DOOR OPENINGS IN FRAME CONSTRUCTION WITH NO SPECIFIED DIMENSION ARE EITHER CENTERED IN THE LENGTH OF
WALL RUN OR (IF DRAWN NEAR CORNER) LOCATED 4" FROM THE FACE OF ADJACENT STUD. ASSUME CENTERED IN FACE
OF JAMB UNLESS NOTED OTHERWISE
11 ALL EXPOSED CONCRETE COLUMNS ARE TO BE FURRED/WRAPPED SEE COLUMN PLAN DETAILS, SEE ELECTRICAL FOR
OUTLET COORDINATION
KEYED NOTES
06.15 PROVIDE 3/4" PLYWOOD, 4'-0" TALL AND 30" A.F.F. ALL AROUND ROOM FOR HEAD END ACCESS EQUIPMENT.
07.12 VAPOR BARRIER REQUIRED FOR HUMIDITY CONTROL. VAPOR BARRIER AND R-13 INSULATION TO DECK. RE:
MECHANICAL.
10.12 SEMI-RECESSED FIRE EXTINGUISHER CABINET
10.14 BRACKET MOUNTED FIRE EXTINGUISHER
10.27 MOTORIZED MODERNFOLD FOLDING PARTITION
11.11 ROOM SCHEDULER, SEE ELECTRICAL DRAWINGS.
22.07 HI LO DRINKING FOUNTAIN WITH BOTTLE FILLER - ADA COMPLIANT, RE: PLUMBING
22.19 HI LO DRINKING FOUNTAIN - ADA COMPLIANT, RE: PLUMBING
26.08 (2) 4" CONDUIT TO LEVEL 1 AND (2) 4" CONDUIT TO LEVEL 3, SEE ELECTRICAL. FIRE CAULK AROUND
PENETRATIONS.
REF.
REF.
16151413121110987
K
H
F
D
B
A
C1
A301
C1
A301
A4
A301
A4
A301
B3
A301
B3
A301
389 SF
CLASSROOM
272
119 SF
OFFICE
288B
118 SF
OFFICE
288C
1,157 SF
ENGLISH
TRANSITION
CENTER
288
613 SF
OPEN TUTORING
254
1,612 SF
STUDY SKILLS
252 1,300 SF
WRITING
CENTER OPEN
TUTORING
256
137 SF
STUDY
269
108 SF
STUDY
268
112 SF
STUDY
267
114 SF
STUDY
266
117 SF
OFFICE
265
118 SF
OFFICE
264
59 SF
STORAGE
270J
98 SF
STUDY
270H
119 SF
PREP /
STORAGE
270B
573 SF
CLASSROOM
260
119 SF
PREP /
STORAGE
256A
130 SF
OFFICE
256B
146 SF
OFFICE
256C
3,139 SF
OPEN TUTORING
CENTER
270
196 SF
ADJUNCT
OFFICE
286
144 SF
TR / COMM.
280
341 SF
CLASSROOM
278
141 SF
PRE-FUNCTION
270C
133 SF
PRE-FUNCTION
270D
119 SF
PRE-FUNCTION
270E
42 SF
STORAGE
288H
106 SF
PREP /
STORAGE
252G
163 SF
OFFICE
252E
625 SF
CLASSROOM
258
78 SF
STORAGE
252F
126 SF
OFFICE
252D
120 SF
STUDY
252A
89 SF
STUDY
252C
94 SF
STUDY
270G
122 SF
STUDY
252B
A1
A414
A419C3
65 SF
STUDY
288E
65 SF
STUDY
288F
63 SF
STUDY
288G
59 SF
STUDY
288D
77 SF
STUDY
288A
STOR
299
MEN'S
RESTROOM
282
WOMEN'S
RESTROOM
284
MECH
2-T
HALL
2-U
293 SF
CLASSROOM
274347 SF
CLASSROOM
276
A417
A4
HALL
2-W
A421C1
276
258
260
269
280
278 274 272
286
270B
270.2
270.1
252E
252G
252F
270J
256C256B
264 265
252A
252B
252C
252D
288B288C
288H
2U-1
256A
288A
288E288G
268267
288F 288D
266
256.2
A419 B5
270H
SF67
SF66
SF68
SF64 SF65
SF48SF49
SF69
SF47
SF54 SF53 SF52 SF51
SF50
SF55A
SF58SF57SF59
SF60
SF61 SF62 SF63
SIM
A416
A5
SIM
A416
A5
A5
A5
A5
SIM
A416
A5
A5
A5
SIM
A416
A419
E1
E2
E3
A419 E5
E4
D1
SIM
A416
SIM
A416
SIM
A416
SIM
A416
C2
SIM
A416
SIM
A416
SIM
A419 C3
A419B4
SIM
A419 B4 SIM
A419B4
A419 D3
SIM
A419 D3
E6
A512 E6
A512
10.27
10.28
10.27
22.1922.19
10.12
10.12
22.07
10.12
10.12
10.23
03.04
08.12
E6
A551
E6
A551
SIM
A422
A1
SIM
A422 A1
SIM
A422
A1
TI
L
E
W
I
D
T
H
4'
-
8
"
TILE WIDTH
5'-1 1/2"
TILE WIDTH
4' - 8"
MIR
A419
C2
A421
E1
E2
D2
D4
C1
C1
A419
C4
D4
A421
E4
E5
A421
C2
A421 B1A1
A421
B4
A422D1
A421
D5
SIM
A416A5
A5
SIM
A416A5
A5
A5
SIM
A416A5
SIM
A416A5
SIM
A416A5
SIM
A416A5A5A5A5
D4
A412
11.11 11.11 11.11 11.11
11.11
11.11
A1A1
A416A1
A1
A1 A1
A1 A1
A422C1
C4
278M 274M276S25
'
-
2
3
/
4
"
270G
SF55B
SF56
256.1
16
"
24"
24
"
18
"
18
"
PREP
2U
ELECTRICAL
2-I
2-I
A420A4
SIM
A422
B5
RECEPTION
270A
D5
A422
A4
A2
E5
A551
E5
A551
E5
A551
TYPA6
A511
TYPA6
A511
TYPA6
A511
TYPA6
A511
TYPA6
A511
C5
A551 C5
A551
C5
A551
C5
A551
C5
A551
C5
A551
C5
A551
C5
A551
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
10/28/22
A102b
Level 02 Area
B Floor Plan
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
KEY PLAN
A
B
1/8" = 1'-0"A1 Level 02 Area B Floor Plan
GENERAL NOTES - FLOOR PLAN
1 GENERAL CONTRACTOR SHALL FIELD VERIFY ALL CONDITIONS AND SHALL REPORT TO THE ARCHITECT ANY UNKNOWN
CONDITIONS, ERRORS, OR CONFLICTS IN THE DRAWINGS BEFORE BEGINNING WORK
2 DO NOT SCALE THE DRAWINGS
3 SEE G000's FOR TYPICAL MOUNTING HEIGHTS. PROVIDE SOLID BLOCKING IN WALLS FOR ALL WALL-MOUNTED ITEMS
WHETHER BLOCKING IS DEPICTED IN DRAWINGS OR NOT
4 COORDINATE ALL EQUIPMENT AND ACCESSORIES, INCLUDING ITEMS THAT ARE OWNER FURNISHED, OWNER INSTALLED
5 SEE SHEET SERIES A500's FOR WALL AND ASSEMBLY TYPES
6 SEE SHEET SERIES A600's FOR DOOR AND WINDOW TYPES
7 SEE ELEVATIONS AND FINISH SCHEDULES FOR SURFACE TREATMENTS AT WALLS
8 SEE ELEVATIONS, SECTIONS, AND DETAILS FOR ADDITIONAL WALL CONSTRUCTION INFORMATION
9 ELECTRICIAN SHALL NOT SET ANY CEILING J-BOXES THAT ARE FOR LIGHTS BEFORE THE FINAL LOCATION OF THE
DROPPED SOFFITS HAVE BEEN DETERMINED. THIS WILL ENSURE THAT THE LIGHTS THAT NEED TO BE CENTERED ARE
CORRECTLY CENTERED BETWEEN THE SOFFITS
10 DOOR OPENINGS IN FRAME CONSTRUCTION WITH NO SPECIFIED DIMENSION ARE EITHER CENTERED IN THE LENGTH OF
WALL RUN OR (IF DRAWN NEAR CORNER) LOCATED 4" FROM THE FACE OF ADJACENT STUD. ASSUME CENTERED IN FACE
OF JAMB UNLESS NOTED OTHERWISE
11 ALL EXPOSED CONCRETE COLUMNS ARE TO BE FURRED/WRAPPED SEE COLUMN PLAN DETAILS, SEE ELECTRICAL FOR
OUTLET COORDINATION
KEYED NOTES
03.04 CONCRETE INFILL SLAB COORDINATE WITH STRUCTURAL DRAWINGS - SEE STRUCTURAL
08.12 HALF HEIGHT GLASS WITH MANUAL SHADES.
10.12 SEMI-RECESSED FIRE EXTINGUISHER CABINET
10.23 CEILING MOUNTED PROJECTOR, OFOI, STEEL PIPE SUPPORT PROVIDED BY CONTRACTOR
10.27 MOTORIZED MODERNFOLD FOLDING PARTITION
10.28 MOTORIZED SKYFOLD PARTITION
11.11 ROOM SCHEDULER, SEE ELECTRICAL DRAWINGS.
22.07 HI LO DRINKING FOUNTAIN WITH BOTTLE FILLER - ADA COMPLIANT, RE: PLUMBING
22.19 HI LO DRINKING FOUNTAIN - ADA COMPLIANT, RE: PLUMBING
1
G
J
L
M
N
P
Q
E
C
2 3 4 5
D3
A301
D3
A301
C1
A301
C1
A301
1.5
OFFICE
310
OFFICE
312
JUVENILE
300
STORAGE
306
STUDY (MED)
304
STUDY (MED)
302
KIDS PLAY
344C
MOTHERS
ROOM
344A
RESTROOM
344B
FAMILY STUDY
344
OPEN STUDY
362
Bridge
Connection
-
BRIDGE
CONNECTION
3-A
STAIR 1
3-B
MENS
368
WOMENS
366
TEST RM
378
STUDY (SM)
330
Janitors Closet
376
OFFICE
322
MAC EQUIP
324A
STUDY (LG)
328
STUDY (LG)
326
MAC LAB
324
STUDY (SM)
332
STUDY (SM)
334
STUDY (SM)
336
TEST RM
374
STUDY (SM)
314
STUDY (SM)
316
STUDY (SM)
320
ELECTRICAL
324B
ELEC
364
STUDY (SM)
338
STUDY (SM)
340
STUDY (SM)
318
( QUIET )
OPEN STUDY
342
ELECTRICAL
308
STORAGE
352
TEST RM
380
TEST RM
382
TEST RM
372
TEST RM
370
TEST RM
360
TEST RM
358
TEST RM
356
TEST RM
350
TEST RM
348
TEST RM
346
STAIRS
3-C
MECH
3-D
MECH CHASE
3-E
STAIR
3-F
ELEV
3-G
MECH CHASE
3-H
CIRC DESK
OPEN STUDY
A418 B4
A418
D1
A413
A1
A412
A418B1
20
4
'
-
0
"
6
D6
A511
E6
A511
A5
A511
TYPA6
A511
TYPA6
A511SIM.
TYP.
C6
A511
B6
A511
TYP.TYP.
A418
B3
A418A1
A418
A4
JUVENILE COLLECTION
K - 12 BOOKS
E1
A415
A421 E3
SIM
A422A1
A419
A5
A4
A419A2
C2
A1
310
312
3-B.23-B.1
344A
324
322.1
382
346
354
360 358 356
364
380
378
324A
324B
374
372
370
308 306
314
316
318
320
304 302
332
334
336
338
340
344
344B
348 350
330
326
3-B.5
3-B.6
3-B.7
3-B.8
SF70
SF71SF72
SF73
SF74
SF75
SF76
SF77 SF78 SF79 SF80
SF81
SF82SF83SF84
SF85
SF86
SF87
SF88
SF89
SF90
SF91
SIM
A416
A4
SIM
A416
A4
SIM
A416
A5
SIM
A416
A4
SIM
A416
A5
SIM
A416
A4
A5
A4
A5
A4
A5
A5
SIM
A416
A4
SIM
A416
A5
SIM
A416
A4
SIM
A416
A5
A5
A4
A5
A4
SIM
A419A2
SIM
A416A4
SIM
A416 A5A4A5
OPEN STUDY
383
22.07
22.1910.12
10.12
10.12
10.12
10.12
10.12
10.12
E5
A551
SIM
A416
A421
D1
SIM
A416
TILE WIDTH
5' - 4 3/4"
B4
A311
11.11
11.11
11.11
11.11
11.11
11.11
11.11 11.11
11.11
11.11
11.11
11.11
11.11 11.11
D5
A551
TYP.
D5
A551
TYP.
A1
A1
TYP.
3-F
3-C
C4
C5
A422 C2
328
A422
B1
C5
A412
D6
A503
C5
A422 B4
4"
A421 A5
E5
A551 D6
A511
E5
A551
D6
A511
SIM
TYPA6
A511
E6
A511
E6
A511
E6
A511
E6
A511
E6
A511
E6
A511
A5
A511
A5
A511
C6
A551
TYP.
C6
A551
TYP.
C6
A551
C6
A551
C6
A551
TYP.
E5
A551
TYP.
E5
A551
TYP.
C6
A551
C6
A551 TYP.
C6
A551
05.04
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
10/28/22
A103a
Level 03 Area
A Floor Plan
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
1/8" = 1'-0"A1 Level 03 Area A Floor Plan KEY PLAN
A
B
GENERAL NOTES - FLOOR PLAN
1 GENERAL CONTRACTOR SHALL FIELD VERIFY ALL CONDITIONS AND SHALL REPORT TO THE ARCHITECT ANY UNKNOWN
CONDITIONS, ERRORS, OR CONFLICTS IN THE DRAWINGS BEFORE BEGINNING WORK
2 DO NOT SCALE THE DRAWINGS
3 SEE G000's FOR TYPICAL MOUNTING HEIGHTS. PROVIDE SOLID BLOCKING IN WALLS FOR ALL WALL-MOUNTED ITEMS
WHETHER BLOCKING IS DEPICTED IN DRAWINGS OR NOT
4 COORDINATE ALL EQUIPMENT AND ACCESSORIES, INCLUDING ITEMS THAT ARE OWNER FURNISHED, OWNER INSTALLED
5 SEE SHEET SERIES A500's FOR WALL AND ASSEMBLY TYPES
6 SEE SHEET SERIES A600's FOR DOOR AND WINDOW TYPES
7 SEE ELEVATIONS AND FINISH SCHEDULES FOR SURFACE TREATMENTS AT WALLS
8 SEE ELEVATIONS, SECTIONS, AND DETAILS FOR ADDITIONAL WALL CONSTRUCTION INFORMATION
9 ELECTRICIAN SHALL NOT SET ANY CEILING J-BOXES THAT ARE FOR LIGHTS BEFORE THE FINAL LOCATION OF THE
DROPPED SOFFITS HAVE BEEN DETERMINED. THIS WILL ENSURE THAT THE LIGHTS THAT NEED TO BE CENTERED ARE
CORRECTLY CENTERED BETWEEN THE SOFFITS
10 DOOR OPENINGS IN FRAME CONSTRUCTION WITH NO SPECIFIED DIMENSION ARE EITHER CENTERED IN THE LENGTH OF
WALL RUN OR (IF DRAWN NEAR CORNER) LOCATED 4" FROM THE FACE OF ADJACENT STUD. ASSUME CENTERED IN FACE
OF JAMB UNLESS NOTED OTHERWISE
11 ALL EXPOSED CONCRETE COLUMNS ARE TO BE FURRED/WRAPPED SEE COLUMN PLAN DETAILS, SEE ELECTRICAL FOR
OUTLET COORDINATION
KEYED NOTES
05.04 NEW STEEL PIPE GUARD RAIL SEE DETAIL - PAINTED
10.12 SEMI-RECESSED FIRE EXTINGUISHER CABINET
11.11 ROOM SCHEDULER, SEE ELECTRICAL DRAWINGS.
22.07 HI LO DRINKING FOUNTAIN WITH BOTTLE FILLER - ADA COMPLIANT, RE: PLUMBING
22.19 HI LO DRINKING FOUNTAIN - ADA COMPLIANT, RE: PLUMBING
1
G
J
L
M
N
P
Q
E
C
2 3 4 51.5 6
VERIFY
5' - 8"
VERIFY
5' - 10"
VERIFY
5' - 4"
VERIFY
5' - 4"
VERIFY
9' - 10"
VERIFY
7' - 10"
VERIFY
7' - 10"
VERIFY
7' - 10"
VERIFY
8' - 3"
VERIFY
5' - 8"
VERIFY
5' - 4"
VERIFY
5' - 4"
VERIFY
5' - 4"
VERIFY
9' - 10"
VERIFY
7' - 10"
VERIFY
7' - 10"
VERIFY
7' - 10"
VERIFY
8' - 3"
6' - 7 1/4"
7' - 1 1/4"19' - 1"
19' - 1"
20' - 6 1/4"
4' - 5 3/4"
20' - 3 5/8"
6' - 5 5/8"
9 1/4"
02.03
02.23
02.23
03.14
02.37
EXISTING SLAB ON GRADE.
SEE STRUCTURAL.
EXISTING WAFFLE SLAB.
SEE STRUCTURAL.
13'-6" V.I.F.
11'-5" V.I.F.
26'-3" V.I.F.
39'-7" V.I.F.
29'-2 3/4" V.I.F.
29'-5 3/4" V.I.F.
13'-2" V.I.F.
02.51
02.51
A5
A431
______________TYP.
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
10/28/22
A111
Level 01 Area
A Slab Plan
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set1/8" = 1'-0"A1 Level 01 Area A Slab Plan
KEYED NOTES
02.03 EXISTING CONCRETE COLUMN
02.23 SLAB ON GRADE CONCRETE CUTOUTS FOR NEW HIGH DENSITY SHELVING. LOCATION NEEDS TO BE VERIFIED WITH
MANUFACTURER'S EQUIPMENT. SEE STRUCTURAL.
02.37 DEMO EXISTING CONCRETE FOR HEATED SIDEWALK. SEE CIVIL DRAWINGS.
02.51 SAWCUT AND REMOVE 1'-0" WIDE SECTIONS OF EXISTING CONCRETE AS HATCHED AND INDICATED FOR NEW
ELECTRICAL. SEE ELECTRICAL PLANS FOR COORDINATION.
03.14 FLOAT AND INFILL RECESSED SLAB AREA. THE NEW FLOATED FLOOR IS TO BE FLUSH WITH ADJACENT FLOOR. -SEE
FINISH PLAN FOR FLOOR COVERING.
GENERAL NOTES - SLAB
1 COORDINATE SLAB EDGE PLANS WITH STRUCTURAL DRAWINGS FOR REQUIRED, REINFORCING, ESPECIALLY AT ALL
PENETRATIONS
2 COORDINATE SLAB EDGE PLANS WITH MECHANICAL DRAWINGS FOR HOUSEKEEPING PADS, SIZE(S), AND EXACT
LOCATION(S)
3 COORDINATE SLAB EDGE PLANS WITH WALL TYPES FOR ACOUSTIC ISOLATION TREATMENTS
4 COORDINATE SLAB EDGE PLANS WITH MANUFACTURER FOR DEPTHS AND DIMENSIONS OF ALL ELEVATOR PUTS AND
WHEELCHAIR LIFT SLAB RECESSES
5 MAJOR SLAB PENETRATIONS SHOWN ON THIS PLAN. MINOR PENETRATIONS, SUCH AS FOR INDIVIDUAL PIPES AND
CONDUITS TO BE COORDINATED WITH MECHANICAL, PLUMBING, ELECTRICAL, AND FIRE DESIGNS. LOCATIONS TO BE
PROVIDED TO ARCHITECT FOR APPROVAL BY CONTRACTOR PRIOR TO COMMENCING WORK
6 THE MINIMUM SLOPE FOR ANY DRAINING SURFACE IS 1/4" PER 1'-0"
7 DRAIN PENETRATIONS SHOWN ARE FOR COORDINATION PURPOSES ONLY, VERIFY SIZE AND PLACEMENT WITH PLUMBING
AND MANUFACTURE OF SHOWER INSERTS
16151413121110987
K
H
F
D
B
A
C1
A301
C1
A301
A4
A301
A4
A301
B3
A301
B3
A301
4'-5 1/2"16'-5 3/4"1'-0 3/4"
2'-11 1/2"
7'-0 1/2"
10'-0"
02.37
03.04
02.4202.42
02.42
02.42
EXISTING
ELEVATOR
HOISTWAY
25'-4"
50'-10 1/4"
33'-3"
14'-6"
9'-1 3/4"
8'-8 1/4"
02.51
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
10/28/22
A112
Level 01 Area
B Slab Plan
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
1/8" = 1'-0"A1 Level 01 Area B Slab Plan
KEYED NOTES
02.37 DEMO EXISTING CONCRETE FOR HEATED SIDEWALK. SEE CIVIL DRAWINGS.
02.42 SAWCUT AND REMOVE 1'-0" WIDE SECTIONS OF EXISTING CONCRETE AS HATCHED AND INDICATED FOR NEW
PLUMBING CONNECTIONS. SEE PLUMBING PLANS FOR COORDINATION.
02.51 SAWCUT AND REMOVE 1'-0" WIDE SECTIONS OF EXISTING CONCRETE AS HATCHED AND INDICATED FOR NEW
ELECTRICAL. SEE ELECTRICAL PLANS FOR COORDINATION.
03.04 CONCRETE INFILL SLAB COORDINATE WITH STRUCTURAL DRAWINGS - SEE STRUCTURAL
GENERAL NOTES - SLAB
1 COORDINATE SLAB EDGE PLANS WITH STRUCTURAL DRAWINGS FOR REQUIRED, REINFORCING, ESPECIALLY AT ALL
PENETRATIONS
2 COORDINATE SLAB EDGE PLANS WITH MECHANICAL DRAWINGS FOR HOUSEKEEPING PADS, SIZE(S), AND EXACT
LOCATION(S)
3 COORDINATE SLAB EDGE PLANS WITH WALL TYPES FOR ACOUSTIC ISOLATION TREATMENTS
4 COORDINATE SLAB EDGE PLANS WITH MANUFACTURER FOR DEPTHS AND DIMENSIONS OF ALL ELEVATOR PUTS AND
WHEELCHAIR LIFT SLAB RECESSES
5 MAJOR SLAB PENETRATIONS SHOWN ON THIS PLAN. MINOR PENETRATIONS, SUCH AS FOR INDIVIDUAL PIPES AND
CONDUITS TO BE COORDINATED WITH MECHANICAL, PLUMBING, ELECTRICAL, AND FIRE DESIGNS. LOCATIONS TO BE
PROVIDED TO ARCHITECT FOR APPROVAL BY CONTRACTOR PRIOR TO COMMENCING WORK
6 THE MINIMUM SLOPE FOR ANY DRAINING SURFACE IS 1/4" PER 1'-0"
7 DRAIN PENETRATIONS SHOWN ARE FOR COORDINATION PURPOSES ONLY, VERIFY SIZE AND PLACEMENT WITH PLUMBING
AND MANUFACTURE OF SHOWER INSERTS
REF.REF.
A. GENERAL CONTRACTOR SHALL FIELD VERIFY ALL CONDITIONS AND SHALL REPORT TO THE ARCHITECT ANY
UNKNOWN CONDITIONS, ERRORS, OR CONFLICTS IN THE DRAWINGS BEFORE BEGINNING WORK
B. DO NOT SCALE THE DRAWINGS
C. ALL EXPOSED INTERIOR STEEL COLUMNS TO BE PAINTED PNT-01 - SEE FINISH SCHEDULE
D. ALL EXPOSED EXTERIOR STEEL TO BE GALVANIZED, UNLESS NOTED OTHERWISE
E. SEE G000'S FOR TYPICAL MOUNTING HEIGHTS. PROVIDE SOLID BLOCKING IN WALLS FOR ALL WALL-MOUNTED
ITEMS WHETHER BLOCKING IS DEPICTED IN DRAWINGS OR NOT
F. COORDINATE ALL EQUIPMENT AND ACCESSORIES, INCLUDING ITEMS THAT ARE OWNER FURNISHED, OWNER
INSTALLED
G. SEE SHEET SERIES A500 FOR WALL AND ASSEMBLY TYPES
H. SEE SHEET SERIES A600 FOR DOOR AND WINDOW TYPES
I. SEE ELEVATIONS AND FINISH SCHEDULES FOR SURFACE TREATMENTS AT WALLS
J. SEE ELEVATIONS, SECTIONS, AND DETAILS FOR ADDITIONAL WALL CONSTRUCTION INFORMATION
K. DOOR OPENINGS ARE TO BE LOCATED 4" FROM THE FACE OF ADJACENT STUD UNLESS NOTED
OTHERWISE.
L. SEE FINISH PLANS AND INTERIOR ELEVATIONS FOR LEVEL 5 WALL FINISH LOCATIONS.
M. SEE SIGNAGE PLAN FOR IN WALL BLOCKING LOCATIONS.
N. ALL EXPOSED VINYL WALL COVERING WRAPPED COLUMNS ARE TO RECIEVE A PAINTED 1/4" GYP BOARD
WRAP DIRECTLY OVER EXISTING WALL
GENERAL NOTES
LEGEND: INT. PARTITION CONDITIONS
1-HR FIRE RATED PARTITION
2-HR FIRE RATED PARTITION
NON-FIRE RATED WALL TAG (description)
SA6a
CORE MATERIAL (SEE LEGEND)
LAYERS (SEE LEGEND)
CORE SIZE (ROUNDED; SEE LEGEND)
HEAD CONDITION MODIFIER (IF APPLICABLE)
FIRE RATED WALL TAG (description)
FIRE RATING (IF APPLICABLE)
1SA6a
CORE MATERIAL (SEE LEGEND BELOW)
LAYERS (REF PARTITIONS SHEET)
CORE SIZE (ROUNDED; SEE LEGEND)
HEAD CONDITION MODIFIER (IF APPLICABLE)
C = CONCRETE WALLS, MASONRY
S = STEEL STUDS
W = WOOD STUDS
CORE MATERIAL LEGEND
CORE SIZE LEGEND
STEEL STUDS WOOD STUDS MASONRY (WIDTH)
BCONCRETE (WIDTH)
1 =A7/8"
2 = 1 5/8" 1 1/2"
3 = 2 1/2" 2 1/2"
4 = 3 5/8" 3 1/2" MASONRY SIZE 4"
5 =
6 = 6" 5 1/2" MASONRY SIZE 6" CONCRETE 6"
8 = 8" 7 1/4" MASONRY SIZE 8" CONCRETE 8"
10 = 9 1/4" MASONRY SIZE 10" CONCRETE 10"
12 = 11 1/4" MASONRY SIZE 12" CONCRETE 12"
14 = CONCRETE 14"
16 =MASONRY SIZE 16"
SUPERSCRIPT NOTES -
A - HAT CHANNEL FURRING IN LIEU OF METAL STUD
B - IF WALL IS STRUCTURAL, DO NOT TAG WALL OR INCLUDE IN WALL TYPES
1
G
J
L
M
N
P
Q
E
C
2 3 4 5
UNEXCAVATED
TIER 2
016
OFFICE
010
OFFICE
026A
OFFICE
011
BREAK ROOM
013
OFFICE
018
STORAGE
032
OFFICE
012
OFFICE
026C
STUDENTS
026F
TECH ROOM
024
SHORT TERM
STORAGE
028
QA
022A
OFFICE
020
OPS
022
STORAGE
044
CUSTODIAL
STORAGE
042
BDF
040
MEN'S RR
015
WOMEN'S RR
014
ELECTRICAL
038
CUSTODIAL
036
MECH CHASE
034
ELEV
0-JSTAIR
0-E
MECH CHASE
O-F
STAIR
0-E
MECH ROOM
030
CHEMICALS
ROOM
O-D
IMAGING AND
STORAGE
009
SA6
SA4
SA4
SA4.1
SA4
SA6
SA6
SA6
SA4
SA4
SA4.1
SA4.1
SA4
SA4
SA4
SA4
SA4
SA4 SA4
AL
I
G
N
OFFICE
026B
OFFICE
026D
OFFICE
026E
UNEXCAVATED
6'-8 3/4"
3'-10 1/2"
8 1/2"ALIGN FINISH
WITH COLUMN
10'-1 1/2"
9 3/4"
AL
I
G
N
ALIGN
3 3/4"13'-5"9'-1"
2'-8 1/4"
6'-4 3/4"9'-1"
ALIGN
ALIGN
9 3/4"
4'-4 1/2"
11'-5 1/2"
9 3/4"8'-10 1/2"
4'-11"
6
11'-1"8'-6"
8 3/4"
10'-4 1/4"
AL
I
G
N
ALIGNSB4.1
SA4
10'-7 1/2"
AL
I
G
N
SB4.1
07.13
07.1307.13
D6
A503
D6
A503
D6
A503
D6
A503
D6
A503
D6
A503
D6
A503
AL
I
G
N
7'-3 3/4"3'-3 3/4"
3'-6 1/4"4'-5"
2'-8 1/4"
3'-6 1/2"4'-5"3'-1 3/4"
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
10/28/22
A120a
Level 00 Area
A Wall Type &
Dimension
Plan
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
1/8" = 1'-0"A1 Level 00 Area A Dimension Plan KEY PLAN
A
B
RE
F
.
DN
A. GENERAL CONTRACTOR SHALL FIELD VERIFY ALL CONDITIONS AND SHALL REPORT TO THE ARCHITECT ANY
UNKNOWN CONDITIONS, ERRORS, OR CONFLICTS IN THE DRAWINGS BEFORE BEGINNING WORK
B. DO NOT SCALE THE DRAWINGS
C. ALL EXPOSED INTERIOR STEEL COLUMNS TO BE PAINTED PNT-01 - SEE FINISH SCHEDULE
D. ALL EXPOSED EXTERIOR STEEL TO BE GALVANIZED, UNLESS NOTED OTHERWISE
E. SEE G000'S FOR TYPICAL MOUNTING HEIGHTS. PROVIDE SOLID BLOCKING IN WALLS FOR ALL WALL-MOUNTED
ITEMS WHETHER BLOCKING IS DEPICTED IN DRAWINGS OR NOT
F. COORDINATE ALL EQUIPMENT AND ACCESSORIES, INCLUDING ITEMS THAT ARE OWNER FURNISHED, OWNER
INSTALLED
G. SEE SHEET SERIES A500 FOR WALL AND ASSEMBLY TYPES
H. SEE SHEET SERIES A600 FOR DOOR AND WINDOW TYPES
I. SEE ELEVATIONS AND FINISH SCHEDULES FOR SURFACE TREATMENTS AT WALLS
J. SEE ELEVATIONS, SECTIONS, AND DETAILS FOR ADDITIONAL WALL CONSTRUCTION INFORMATION
K. DOOR OPENINGS ARE TO BE LOCATED 4" FROM THE FACE OF ADJACENT STUD UNLESS NOTED
OTHERWISE.
L. SEE FINISH PLANS AND INTERIOR ELEVATIONS FOR LEVEL 5 WALL FINISH LOCATIONS.
M. SEE SIGNAGE PLAN FOR IN WALL BLOCKING LOCATIONS.
N. ALL EXPOSED VINYL WALL COVERING WRAPPED COLUMNS ARE TO RECIEVE A PAINTED 1/4" GYP BOARD
WRAP DIRECTLY OVER EXISTING WALL
GENERAL NOTES
LEGEND: INT. PARTITION CONDITIONS
1-HR FIRE RATED PARTITION
2-HR FIRE RATED PARTITION
NON-FIRE RATED WALL TAG (description)
SA6a
CORE MATERIAL (SEE LEGEND)
LAYERS (SEE LEGEND)
CORE SIZE (ROUNDED; SEE LEGEND)
HEAD CONDITION MODIFIER (IF APPLICABLE)
FIRE RATED WALL TAG (description)
FIRE RATING (IF APPLICABLE)
1SA6a
CORE MATERIAL (SEE LEGEND BELOW)
LAYERS (REF PARTITIONS SHEET)
CORE SIZE (ROUNDED; SEE LEGEND)
HEAD CONDITION MODIFIER (IF APPLICABLE)
C = CONCRETE WALLS, MASONRY
S = STEEL STUDS
W = WOOD STUDS
CORE MATERIAL LEGEND
CORE SIZE LEGEND
STEEL STUDS WOOD STUDS MASONRY (WIDTH)
BCONCRETE (WIDTH)
1 =A7/8"
2 = 1 5/8" 1 1/2"
3 = 2 1/2" 2 1/2"
4 = 3 5/8" 3 1/2" MASONRY SIZE 4"
5 =
6 = 6" 5 1/2" MASONRY SIZE 6" CONCRETE 6"
8 = 8" 7 1/4" MASONRY SIZE 8" CONCRETE 8"
10 = 9 1/4" MASONRY SIZE 10" CONCRETE 10"
12 = 11 1/4" MASONRY SIZE 12" CONCRETE 12"
14 = CONCRETE 14"
16 =MASONRY SIZE 16"
SUPERSCRIPT NOTES -
A - HAT CHANNEL FURRING IN LIEU OF METAL STUD
B - IF WALL IS STRUCTURAL, DO NOT TAG WALL OR INCLUDE IN WALL TYPES
1
G
J
L
M
N
P
QQ
E
C
2 3 4 51.5
SA4.1 SA4.1 SA4
SA4
SA4.1
SA4 SA4
SA4SA4
SA4
CHECK-IN
112
OFFICE
129
OFFICE
130
OFFICE
131
STUDY (MED)
132
OFFICE
136
RECEPTION
134
OFFICE
138
CONFERENCE
ROOM
140BREAKROOM
142
STUDY (SM)
128
STUDY (MED)
124
STUDY (MED)
125
STUDY (SM)
126
STUDY (SM)
127
OPEN STUDY
122A
HD BOOK
COLLECTION
122
OPEN STUDY
120A
VESTIBULE
1-F
CIRCULATION
RECEPTION
110
OFFICE
108
INTER LIBRARY
LOAN
WORKSPACE
114
FAMILY RR
144
OPEN STUDY
122C
OPEN STUDY
122B
OPEN STUDY
118
MENS
146
WOMENS
148
JANITORS
OFFICE
147
OFFICE
106
OFFICE
104
OFFICE
114A
STAIR
1-H
STAIR
1-B
VESTIBULE
1-A
STAIR
1-D
HALLWAY
1-C
MECH CHASE
1-KMECH CHASE
1-G
ELEVATOR
1-J
Room
1-L
Room
1-M
RESERVE MEDIA
116
MECH
1-E
ELEC ROOM
102
OPEN STUDY
100
ENTRY HALL
120A
READING
150
SD4
SA4
SA4
SD4
SD4.1
SD4.1
SD4.1
SD4.1
SA4
SA4
SA4SA4
SA4
SA4
SA4
SA4
SA4
SA4
SA4SB4
SA4.1 SB4.1
4'-9 1/2"
7'-1"
5'-3 1/2"
8'-8 1/2"
8'-5"
12'-5 3/4"
4'-7 1/2"
7'-9 3/4"
9'-8"5'-2"
7'-9"
7'-9"
9'-0"
CL
5'-0"
10'-4"
8 1/2"7'-1"
7'-6"
11"
11'-2 1/2"3'-11 1/2"17'-4 1/4"4'-2 1/4"1 1/2"13'-1"
2'-2 3/4"
7 1/2"
1'-7 1/4"
4'-10 1/2"
9'-5 1/2"
9'-5"
1'-11"
7'-6"
6
B5
A311
SA4.1
SA4
SA4
SG1
SG1
SA4
SC4SC4SC4
SC4 SC4
SC4
SC4
SC4
SC4
SC4
SC4
SC4
SC4
SC4
SC4 SC4
SC4
2SH4
SA4
SA4
SC4 SC4
SC4
SC4
SC4
SC4
SC4
SC4
SC4
SC4
SC4
SC4
SC4
SC4
SC4
SC4
SA4.1
ABOVE & BELOW
EXTERIOR
WINDOW, TYP.
TYP. AT COLUMNS,
UNLESS OTHERWISE NOTED.
SC4SC4
SC4 SC4
SC4 SC4
SC4SC4
SC4
SC4
SC4
SC4SC4
5'-0 1/2"7'-10 1/4"
AL
I
G
N
FR
A
M
I
N
G
T
O
CO
L
U
M
N
,
T
Y
P
.
8 1/2"
5'-5"
2'-9 3/4"20'-0"
SB4.1
SB4.1SB4.1
SB4.1
1'-0 3/4"3'-9"10'-0"
CL
8 1/4"
11'-10 1/2"
11 3/4"
1' - 0"
1' - 0"
AL
I
G
N
1'-1 1/4"
9'-4 1/4"
1' - 2"
1' - 2"
8 1/4"
ALIGN
FRAMING TO
COLUMN
AL
I
G
N
AL
I
G
N
SB4.1
SB4.1
SB3.1
SA4.1
SA4.1
SA4.1
SB4.1
1"
4'-4"
4'-5"
4'-5"
4'-5"
4'-5"
3' - 4"
4'-9 1/4"
11 1/4"9 1/2"
4'-3"
SB4.1
SB4.1
SB4.1
SB4.1 SB3.1
SB3.1
SB3.1
SB4.1 SB4.1
SB4.1
SB4.1SB4.1
SB4.1 SB3.1
SB3.1
SB4.1
SB4.1
SB4.1SB3.1
SB3.1
SB3.1
SB2.1
3'-11 3/4"1'-0 3/4"
1'-0 3/4"
1'-0 3/4"
3'-11 3/4"3'-11 3/4"
1'-0 3/4"
1'-0 3/4"
1'-0 3/4"3'-11 3/4"
1'-0 3/4"
1'-0 3/4"
SB4 SB4.1
SB2.1
SB4
2SH4
SA4.1
SA4.1
SB4
2SH4
SA4.1 SA4.1 SA4.1
2'-4 3/4"1'-10 1/4"
4'-3"4'-3"4'-3"4'-3"
3' - 4"
4 1/4"
4'-5 1/2"
4'-5 1/2"
4'-5 1/2"
SA6
10.19
10.19
10.19
10.19
2'-4 1/2"
7'-9 1/4"
SA4
SA4.1
SA4.1
SA4
SA4.1
SA4
1'-8 3/4"
14'-9 1/2"
1'-4"
7'-8"
8'-1 1/2"
1'-4"
11'-1 1/2"
1'-4"
3'-7"
7'-6 1/2"1'-3"
11'-1 1/2"
1'-6 1/4"
4"
1'-1 1/4"
17'-0"
1'-5 1/2"
TUNNEL
BELOW
TUNNEL
BELOW
SB3.1
SB3.1
SB2.1
SB2.1SB2.1
SB2.1
SB2.1
SB2.1
916 SF
SB2.1
SB2.1
SB2.1
SB2.1
SB2.1
SB2.1
SB2.1
SB2.1
SA4.1
SA4.1
ABOVE
SA4
ABOVE
TYP.
B5
A311 TYP.
B5
A311 TYP.
B2
A431
2 1/2"
7 1/4"7 1/4"
4"
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
10/28/22
A121a
Level 01 Area
A Wall Type &
Dimension
Plan
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set1/8" = 1'-0"A1 Level 01 Area A Dimension Plan KEY PLAN
A
B
KEYED NOTES
10.19 HIGH DENSITY LIBRARY MANUAL BOOK STORAGE - B.O.D. SPACE SAVER
RE
F
.
A. GENERAL CONTRACTOR SHALL FIELD VERIFY ALL CONDITIONS AND SHALL REPORT TO THE ARCHITECT ANY
UNKNOWN CONDITIONS, ERRORS, OR CONFLICTS IN THE DRAWINGS BEFORE BEGINNING WORK
B. DO NOT SCALE THE DRAWINGS
C. ALL EXPOSED INTERIOR STEEL COLUMNS TO BE PAINTED PNT-01 - SEE FINISH SCHEDULE
D. ALL EXPOSED EXTERIOR STEEL TO BE GALVANIZED, UNLESS NOTED OTHERWISE
E. SEE G000'S FOR TYPICAL MOUNTING HEIGHTS. PROVIDE SOLID BLOCKING IN WALLS FOR ALL WALL-MOUNTED
ITEMS WHETHER BLOCKING IS DEPICTED IN DRAWINGS OR NOT
F. COORDINATE ALL EQUIPMENT AND ACCESSORIES, INCLUDING ITEMS THAT ARE OWNER FURNISHED, OWNER
INSTALLED
G. SEE SHEET SERIES A500 FOR WALL AND ASSEMBLY TYPES
H. SEE SHEET SERIES A600 FOR DOOR AND WINDOW TYPES
I. SEE ELEVATIONS AND FINISH SCHEDULES FOR SURFACE TREATMENTS AT WALLS
J. SEE ELEVATIONS, SECTIONS, AND DETAILS FOR ADDITIONAL WALL CONSTRUCTION INFORMATION
K. DOOR OPENINGS ARE TO BE LOCATED 4" FROM THE FACE OF ADJACENT STUD UNLESS NOTED
OTHERWISE.
L. SEE FINISH PLANS AND INTERIOR ELEVATIONS FOR LEVEL 5 WALL FINISH LOCATIONS.
M. SEE SIGNAGE PLAN FOR IN WALL BLOCKING LOCATIONS.
N. ALL EXPOSED VINYL WALL COVERING WRAPPED COLUMNS ARE TO RECIEVE A PAINTED 1/4" GYP BOARD
WRAP DIRECTLY OVER EXISTING WALL
GENERAL NOTES
16151413121110987
K
H
F
D
B
A
SA4
SA4
SA4
SA4.1
SA4.1 SA4.1
SA4
SA4 SA4 SA4SA4
SA4
SA4
SD4
SA4
SA4SA4
SA4
SA4
SA4.1
SA6.1
SA4
SA4
SA4
SA6
SA4
SA6
SA4
SA4
SA4
SD4
SD4
SA4.1
SA4.1
SA4
SA4.1
SA4
SA4
SA4 SA4 SA4
SA4.1
SA4.1
SA4.1
SA4.1
SA4
SA4.1
SA4
SD4
SA4.1
SA4
SA4
SA4.1
SA4.1
SA4
SA4
STORAGE
170C
STUDY
170B
STUDY
170A
CLASSROOM
168
CLASSROOM
166
ADJUNCT
OFFICE
180
OFFICE
181
OFFICE
182
OFFICE
183
OFFICE
184
OFFICE
185
OFFICE
186
CONFERENCE
ROOM
158
CONFERENCE
188B
COLLABORATIVE
SPACE
188
CLASSROOM
162
CLASSROOM
164
OFFICE
190B
OFFICE
190A
TRAINING AREA
190
OFFICE
192B
SMALL MEETING
192A
OFFICE
160A OFFICE
160B
TUTORING
ADMIN OPEN
AREA
160
OFFICE
156F
PRACTICE
156E
WORKSPACE
156
STORAGE
156D
DROP IN MATH
LAB
170
WORKSTATIONS/
FLEX SPACE
192
CLASSROOM
172
STUDENT PREP
174
STUDY
178
STUDY
179
MATH LAB
RECEPTION
175
I.T. HELP DESK
176
OFFICE
188A
STORAGE
190C
STORAGE
192C
PRACTICE
156C
PRACTICE
156B
PRACTICE
156A
VESTIBULE
1-U
ELECTRICAL
173
VESTIBULE
1-Z
MECH
08
ELEV EQUIP
08A
ELEV
1-T
MEN'S
RESTROOM
154
WOMEN'S
RESTROOM
152
HALL
1-S
HALL
1-R
HALL
1-P
STAIRS
1-N
MECH
1-Q
HALL
1-V
HALL
1-X
HALL
1-Y
SA4
10'-8 1/4"
8 1/4"
9'-10"
5'-0"
AL
I
G
N
9'-4 1/2"
9 1/2"
10'-8 1/2"11'-3 1/2"
9'-2"
10'-0"
11'-10"
8"
10'-8 1/2"11'-3 1/2"
6 3/4"
AL
I
G
N
11'-10"
1/2"
10'-0"
10'-7"
1'-5"
4'-9"
10'-5"
6'-10"
1'-11"
7 1/4"10'-1"
AL
I
G
N
17'-10 1/4"3'-11 3/4"18'-0 1/4"4'-1 1/4"
ALIGN
10 3/4"
22'-0"5'-3"16'-9"11'-5"10'-7"10'-7"10'-8 1/2"
8 3/4"
1'-0 1/2"
3'-3 1/2"
8'-11 1/4"
9'-9 1/4"
4 1/4"
8 3/4"
10'-9"
1'-0 1/4"
10'-3 1/4"11'-3 1/2"
5 1/4"
10'-10 1/4"11'-1 3/4"
1 3/4"
11'-3 1/2"9'-10 1/4"
8 3/4"
5"
9'-8 3/4"
11'-1 3/4"
8 3/4"
11'-0"
10'-10 1/2"10'-1 1/4"9 3/4"2'-2 3/4"18'-11 1/2"10'-11 3/4"
9'-10"
AL
I
G
N
6'-3 1/2"7'-2 1/4"
2'-6"
7'-9 1/4"
11'-6 3/4"
11'-4 1/4"
11'-4 1/4"
SF1
SF1
SA4
SA4
SD6
SD4.1
11'-5 1/2"
SD4
AL
I
G
N
9'-9 1/4"
8 3/4"
SB4.1
1' - 4"
4'-5"10'-2"
1'-8 1/4"
6 1/4"
ALIGN
1' - 4"
SB4.1
SB4.1
SB4.1
SB4.1
AL
I
G
N
7 1/4"
10'-4 1/4"
SA6
SB2.1
SB2.1
SB4
SA6.1 HALF WALL
ALIGN
1' - 0"
9'-5"
1'-0 1/4"
AL
I
G
N
1'-0 3/4"
10'-3 1/2"
SB2.1
SB4.1
ESA4
ESA4
AL
I
G
N
FR
A
M
I
N
G
T
O
EL
E
V
A
T
O
R
WA
L
L
SB4.1
SA6
SA4
SB2.1
EX
I
S
T
I
N
G
R
A
M
P
D6
A503
D6
A503
D6
A503
D6
A503
AL
I
G
N
SA4.1
SA4
SA4.1
SA4.1
SA4.1
SA6.1
SA4
SA4
22'-0"
3/4"
21'-2"
9 1/4"
1'-5"
1'-0 1/2"
3'-3 1/2"
10'-0 1/4"
2 1/2"4 1/2"
10'-0"1'-6"
7 1/4"
SB3.1
SB3.1
SB3.1SB3.1
SB3.1
SB3.1
SB3.1
SB3.1
SB3.1
SB3.1
SB3.1
SB3.1SB2.1
SB3.1
SB2.1
SB3.1
SB3.1
SB3.1
SB3.1
SA8
AL
I
G
N
C5
A511
4"
2'-10 3/4"
2 1/2"2 1/2"
2 1/2"4"
10 3/4"
3 1/4"3 1/4"
4"
LEGEND: INT. PARTITION CONDITIONS
1-HR FIRE RATED PARTITION
2-HR FIRE RATED PARTITION
NON-FIRE RATED WALL TAG (description)
SA6a
CORE MATERIAL (SEE LEGEND)
LAYERS (SEE LEGEND)
CORE SIZE (ROUNDED; SEE LEGEND)
HEAD CONDITION MODIFIER (IF APPLICABLE)
FIRE RATED WALL TAG (description)
FIRE RATING (IF APPLICABLE)
1SA6a
CORE MATERIAL (SEE LEGEND BELOW)
LAYERS (REF PARTITIONS SHEET)
CORE SIZE (ROUNDED; SEE LEGEND)
HEAD CONDITION MODIFIER (IF APPLICABLE)
C = CONCRETE WALLS, MASONRY
S = STEEL STUDS
W = WOOD STUDS
CORE MATERIAL LEGEND
CORE SIZE LEGEND
STEEL STUDS WOOD STUDS MASONRY (WIDTH)
BCONCRETE (WIDTH)
1 =A7/8"
2 = 1 5/8" 1 1/2"
3 = 2 1/2" 2 1/2"
4 = 3 5/8" 3 1/2" MASONRY SIZE 4"
5 =
6 = 6" 5 1/2" MASONRY SIZE 6" CONCRETE 6"
8 = 8" 7 1/4" MASONRY SIZE 8" CONCRETE 8"
10 = 9 1/4" MASONRY SIZE 10" CONCRETE 10"
12 = 11 1/4" MASONRY SIZE 12" CONCRETE 12"
14 = CONCRETE 14"
16 =MASONRY SIZE 16"
SUPERSCRIPT NOTES -
A - HAT CHANNEL FURRING IN LIEU OF METAL STUD
B - IF WALL IS STRUCTURAL, DO NOT TAG WALL OR INCLUDE IN WALL TYPES
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
10/28/22
A121b
Level 01 Area
B Wall Type &
Dimension
Plan
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
1/8" = 1'-0"A1 Level 01 Area B Dimension Plan
KEY PLAN
A
B
ABOVE
A. GENERAL CONTRACTOR SHALL FIELD VERIFY ALL CONDITIONS AND SHALL REPORT TO THE ARCHITECT ANY
UNKNOWN CONDITIONS, ERRORS, OR CONFLICTS IN THE DRAWINGS BEFORE BEGINNING WORK
B. DO NOT SCALE THE DRAWINGS
C. ALL EXPOSED INTERIOR STEEL COLUMNS TO BE PAINTED PNT-01 - SEE FINISH SCHEDULE
D. ALL EXPOSED EXTERIOR STEEL TO BE GALVANIZED, UNLESS NOTED OTHERWISE
E. SEE G000'S FOR TYPICAL MOUNTING HEIGHTS. PROVIDE SOLID BLOCKING IN WALLS FOR ALL WALL-MOUNTED
ITEMS WHETHER BLOCKING IS DEPICTED IN DRAWINGS OR NOT
F. COORDINATE ALL EQUIPMENT AND ACCESSORIES, INCLUDING ITEMS THAT ARE OWNER FURNISHED, OWNER
INSTALLED
G. SEE SHEET SERIES A500 FOR WALL AND ASSEMBLY TYPES
H. SEE SHEET SERIES A600 FOR DOOR AND WINDOW TYPES
I. SEE ELEVATIONS AND FINISH SCHEDULES FOR SURFACE TREATMENTS AT WALLS
J. SEE ELEVATIONS, SECTIONS, AND DETAILS FOR ADDITIONAL WALL CONSTRUCTION INFORMATION
K. DOOR OPENINGS ARE TO BE LOCATED 4" FROM THE FACE OF ADJACENT STUD UNLESS NOTED
OTHERWISE.
L. SEE FINISH PLANS AND INTERIOR ELEVATIONS FOR LEVEL 5 WALL FINISH LOCATIONS.
M. SEE SIGNAGE PLAN FOR IN WALL BLOCKING LOCATIONS.
N. ALL EXPOSED VINYL WALL COVERING WRAPPED COLUMNS ARE TO RECIEVE A PAINTED 1/4" GYP BOARD
WRAP DIRECTLY OVER EXISTING WALL
GENERAL NOTES
1
G
J
L
M
N
P
Q
E
C
2 3 4 51.5
?
ELECTRICAL
ROOM
242
TECH SERV
STORAGE
2-E
TECH SERVICES
238
SA4
SA4
SA4.1
SHEET MUSIC
236
SA4
SA4
LARGE
COMPUTER
CLASSROOM
234
OPEN
COMPUTERS
240
SA4.1
SA4.1
MOTHERS
243
SA4
OPEN STUDY
53
SJ4.1
SJ4.1
PRESS ROOM
226
SPECIAL
COLLECTIONS
228
VAULT
228E
ARCHIVE
228D
SJ4.1
INSTRUCTION 2
224
INSTRUCTION 1
222
DCAM
228B
OFFICE
228A
SCANNER
228C
SA4
SA4
OFFICE
232
SD4.1 SD4.1
STUDY (MED)
216
STUDY (MED)
214
STUDY (MED)
218
STUDY (SM)
204
JANITOR'S
OFFICE
241
SA4
SA4
OFFICE
230
SD4
OFFICE
202
SE4.1 SD4.1 SD4.1
STUDY (SM)
212
STUDY (SM)
210
STUDY (SM)
208
OFFICE
200
OPEN STUDY
220
MECHANICAL
2-D
SA4
SA4.1
SA6.1
SA4SA4
SA4
I.T.
245
SA4.1 SA4.1
SA4.1
SA4.1
SA4.1
SJ4.1
SA4
SA4.1
SA4.1
SA4.1
MEN'S
RESTROOM
247
WOMEN'S
RESTROOM
248
STAIR
2-G
ELEV
2-H
MECH CHASE
2-J
STAIR
2-A
STAIR
2-B
OPEN STUDY
250
MECH
2-C
MECH CHASE
2-F
HALL
2-K
Room
2-M
HALL
2-M
SA4.1 SA4.1
SA4.1
SA4.1 SA4.1 SA4.1
4'-11 1/2"
2'-6"1'-3 1/4"
1'-1 3/4"
28'-3"
1'-3 1/4"
11 1/4"
12'-11"
11'-8"
11 1/4"
25'-6"
5'-6"
5'-9 1/4"7'-0 3/4"
18'-6"
4'-2"
8'-2 1/2"
13'-1 3/4"
15'-3 1/2"15'-4 1/4"
15'-4"
1'-2"
11'-9"
12'-4"
3"
12'-0 1/4"11'-7 1/2"11'-4 3/4"
6'-6"
4'-11 1/2"
2'-5 1/4"2'-1 3/4"
4'-11 1/2"16'-10 1/2"
1'-6 3/4"
3'-0 3/4"11'-11 1/4"10'-6"
1'-0"
1'-0"24'-6"7'-5 1/4"
3'-9 1/2"9'-1 3/4"
6
SC4
ALIGN FRAMING
TO COLUMN, TYP.
FAMILY RR
244
SF1
SC4
SC4
SC4
SC4 SA4.1
SC4SC4 SC4 SC4
SC4
SC4
SC4
SA4.1
SC4
SC4
SC4
SC4
SC4
SC4
SC4
SC4
SC4
SC4
SC4
SC4
SC4
SC4
SC4
SC4
SC4
SC4
SA4
SA4 SA4
SA4
SC4
SA4.1
SA4.1
SA4.1
5'-2 3/4"
7'-1 3/4"
2'-7 1/4"
10'-6 1/2"
5'-6"
ALIGN
1'-0"
1'-0"
9'-9 1/4"5'-5"
3'-5 1/4"
4'-7"
ALIGN
ALIGN
7'-0 3/4"
6'-4"
ALIGN
ABOVE & BELOW
EXTERIOR
WINDOW, TYP.
1' - 0"
TYP.
SB3.1
SC4
SC4
SC6SC6SC4
SC4
SC6 SC4
SC4 SC6
SC4
SC6
SC4
SC6 SC4
SA4
SA4.1
SA4.1
SA4.1
SA4.1
SA4.1
5'-2 3/4"
4'-6"
4'-6"
4'-6"
5'-2 3/4"
7 1/2"
SA4.1
SA4.1
SA4.1
SA4.1
SA4.1
SA4.1
5'-2 3/4"
4'-6"
4'-6"
4'-6"
5'-2 3/4"
7 1/2"
3' - 4"
3' - 4"
16'-8 1/2"
4'-9 3/4"7'-1 1/2"
1'-6"
ALIGN
ALIGN FRAMING
AT COLUMN, TYP.
SA4.1 SA4.1
SB4.1SB4.1
SB4 SB2.1SA4SA4
SB4 SB4.1
SA4
SJ4.1
SJ4.1
SA4 SA4
SA4
SA4
07.12
JANITOR'S
CLOSET
249
STUDY (MED)
206
SA4.1
SA4.1
SA4.1
SA4
SB4.1 SB4.1
SB4.1
IT
241A
SA4
SA4
ALIGNALIGN
ALIGN
SIME3
A415
4 1/4"
11'-4 1/2"2 1/2"
1'-6 1/2"
6 3/4"12'-4"1'-4"13'-11 1/2"1'-4"13'-11 1/2"1'-5 3/4"1'-5 1/4"10'-5 1/2"1'-4 1/4"9'-11 1/2"1'-4 1/4"9'-11 1/2"
1'-4 1/2"
4'-5 1/2"
10'-9 3/4"
11'-7 1/2"
1'-5 3/4"
6'-5 1/2"
23'-2 1/2"
20'-2 1/2"
17'-8"
15'-3"
E6
A512 SIME5
A512
TYP. AT COLUMNS,
UNLESS OTHERWISE NOTED.
SB2.1
SB2.1
SB2.1
SB2SA4
SB2.1
SA4.1
SB2.1
SB2.1
SB2
SA4.1
SB2.1
SB1
SB1
SB4.1
SB3.1
SB3.1
2"
2"2"
4'-0"8 1/2"
2"
2 1/2"
2'-5 3/4"
LEGEND: INT. PARTITION CONDITIONS
1-HR FIRE RATED PARTITION
2-HR FIRE RATED PARTITION
NON-FIRE RATED WALL TAG (description)
SA6a
CORE MATERIAL (SEE LEGEND)
LAYERS (SEE LEGEND)
CORE SIZE (ROUNDED; SEE LEGEND)
HEAD CONDITION MODIFIER (IF APPLICABLE)
FIRE RATED WALL TAG (description)
FIRE RATING (IF APPLICABLE)
1SA6a
CORE MATERIAL (SEE LEGEND BELOW)
LAYERS (REF PARTITIONS SHEET)
CORE SIZE (ROUNDED; SEE LEGEND)
HEAD CONDITION MODIFIER (IF APPLICABLE)
C = CONCRETE WALLS, MASONRY
S = STEEL STUDS
W = WOOD STUDS
CORE MATERIAL LEGEND
CORE SIZE LEGEND
STEEL STUDS WOOD STUDS MASONRY (WIDTH)
BCONCRETE (WIDTH)
1 =A7/8"
2 = 1 5/8" 1 1/2"
3 = 2 1/2" 2 1/2"
4 = 3 5/8" 3 1/2" MASONRY SIZE 4"
5 =
6 = 6" 5 1/2" MASONRY SIZE 6" CONCRETE 6"
8 = 8" 7 1/4" MASONRY SIZE 8" CONCRETE 8"
10 = 9 1/4" MASONRY SIZE 10" CONCRETE 10"
12 = 11 1/4" MASONRY SIZE 12" CONCRETE 12"
14 = CONCRETE 14"
16 =MASONRY SIZE 16"
SUPERSCRIPT NOTES -
A - HAT CHANNEL FURRING IN LIEU OF METAL STUD
B - IF WALL IS STRUCTURAL, DO NOT TAG WALL OR INCLUDE IN WALL TYPES
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
10/28/22
A122a
Level 02 Area
A Wall Type &
Dimension
Plan
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
1/8" = 1'-0"A1 Level 02 Area A Dimension Plan KEY PLAN
A
B
ALIGN
REF.
REF.
A. GENERAL CONTRACTOR SHALL FIELD VERIFY ALL CONDITIONS AND SHALL REPORT TO THE ARCHITECT ANY
UNKNOWN CONDITIONS, ERRORS, OR CONFLICTS IN THE DRAWINGS BEFORE BEGINNING WORK
B. DO NOT SCALE THE DRAWINGS
C. ALL EXPOSED INTERIOR STEEL COLUMNS TO BE PAINTED PNT-01 - SEE FINISH SCHEDULE
D. ALL EXPOSED EXTERIOR STEEL TO BE GALVANIZED, UNLESS NOTED OTHERWISE
E. SEE G000'S FOR TYPICAL MOUNTING HEIGHTS. PROVIDE SOLID BLOCKING IN WALLS FOR ALL WALL-MOUNTED
ITEMS WHETHER BLOCKING IS DEPICTED IN DRAWINGS OR NOT
F. COORDINATE ALL EQUIPMENT AND ACCESSORIES, INCLUDING ITEMS THAT ARE OWNER FURNISHED, OWNER
INSTALLED
G. SEE SHEET SERIES A500 FOR WALL AND ASSEMBLY TYPES
H. SEE SHEET SERIES A600 FOR DOOR AND WINDOW TYPES
I. SEE ELEVATIONS AND FINISH SCHEDULES FOR SURFACE TREATMENTS AT WALLS
J. SEE ELEVATIONS, SECTIONS, AND DETAILS FOR ADDITIONAL WALL CONSTRUCTION INFORMATION
K. DOOR OPENINGS ARE TO BE LOCATED 4" FROM THE FACE OF ADJACENT STUD UNLESS NOTED
OTHERWISE.
L. SEE FINISH PLANS AND INTERIOR ELEVATIONS FOR LEVEL 5 WALL FINISH LOCATIONS.
M. SEE SIGNAGE PLAN FOR IN WALL BLOCKING LOCATIONS.
N. ALL EXPOSED VINYL WALL COVERING WRAPPED COLUMNS ARE TO RECIEVE A PAINTED 1/4" GYP BOARD
WRAP DIRECTLY OVER EXISTING WALL
GENERAL NOTES
16151413121110987
K
H
F
D
B
A
OFFICE
264
CLASSROOM
276
STUDY
288D
STUDY
288G
SA4
CLASSROOM
272
SA4
OFFICE
288B
OFFICE
288C
ENGLISH
TRANSITION
CENTER
288
OPEN TUTORING
254
STUDY SKILLS
252
WRITING
CENTER OPEN
TUTORING
256
SA4 SA4.1 SA4.1 SA4.1
STUDY
269
STUDY
268
STUDY
267
STUDY
266
OFFICE
265
SA4.1
STORAGE
270J
STUDY
270H
PREP /
STORAGE
270B
CLASSROOM
258
CLASSROOM
260
PREP /
STORAGE
256A
OFFICE
256B
SA4
SA4
OFFICE
256C
STUDY
288F
STUDY
288E
OPEN TUTORING
CENTER
270
SA4 SA4
SA4
SA4
ADJUNCT
OFFICE
286
TR / COMM.
280
SA4
SA4
SA4
SA4.1
SA4
SA4
SA4
SA4
SA4
CLASSROOM
278
PRE-FUNCTION
270C
PRE-FUNCTION
270D
PRE-FUNCTION
270E
RECEPTION
270A
SA4
PREFUNCTION
270F
STORAGE
288H
SA4
SA4.1
SA4.1
STUDY
252B
PREP /
STORAGE
252G
SA4.1
OFFICE
252E
SA4.1
SA4.1
SA4
SA4
STORAGE
252F
OFFICE
252D
SA4.1
STUDY
252A
SA4
SA4
SA4.1
SA4.1
STUDY
252C
SA4 SA4.1
SA4.1
STUDY
270G
ELEV
2-R
WOMEN'S
RESTROOM
284
MEN'S
RESTROOM
282
STAIR
2-P
STOR
299
MECH
2-T
CLASSROOM
274
Room
2-S
HALL
2-Q
HALL
2-U
HALL
2-W
SA4
SA4
SA4
STUDY
288A
SA4.1
2'-2"5'-4 1/2"7'-6 1/2"7'-6 1/2"
1'-6 1/2"
6'-0"11'-11 1/4"4'-1"
10'-7 3/4"
8'-8"3'-9"16'-2 1/2"5'-5 1/4"
4 1/4"
SB4.1 SB4.1SB4.1
5'-6"4'-9 1/2"
6'-9 1/2"7'-10 1/2"14'-1 1/2"5"14'-8"6'-11"
8'-9 1/2"
SA4.1
10'-11"
9"11'-8"10'-4"2'-0 1/2"10'-11 1/2"9'-0"1'-9"10'-6"
5'-8 1/2"
10'-3 1/2"8"10'-11 1/2"5'-5"5'-7 1/2"
7'-0"
11'-9"
10'-7"
2'-2"
9"
1'-0"
SA4
SA4
2'-6"
7'-6"
10'-0"
4'-6"
4'-6"
7'-0"
10'-6"
10'-10"
2'-0"
1'-0"
8"
12'-5"
8 3/4"
ALIGN
ALIGN
10' - 10"
AL
I
G
N
AL
I
G
N
AL
I
G
N
11 5/8"
SA4.1 SA4.1
SA4.1
SA4.1
SA4.1 SA4.1 SA4.1
7'-7 1/4"
8'-5"
AL
I
G
N
ALIGN
ALIGN
5'-8 1/2"
ALIGN
SA4.1
SA4.1
SA4.1
SB4.1
SA4
SA4.1
SB2.1
2'-5 1/2"
8'-8 1/2"
6'-3 1/2"7'-11"
AL
I
G
N
1'-0 3/4"9'-11 3/4"
AL
I
G
N
AL
I
G
N
AL
I
G
N
1'-8"4'-1 1/4"
SA4.1
SA4.1
SA4
SA4
SA4
SB4.1
SA6.1
HALF WALL
SA4 SA4 SA4SB4
SA4.1
SA4.1
4'-6"
SA4.1
D6
A503
SA4
SB4.1
SG1
SA4.1
SA4.1
SA4.1
SA4.1
5'-10 1/2"
AL
I
G
N
2'-6"
ALIGN
1'-5 1/2"
1'-11 1/2"
5'-0 1/4"7"6'-11 1/2"7"6'-11 1/2"7"
1'-4"
5'-7 3/4"3/4"1"
9'-9"
9 3/4"
9 1/2"
5'-7 1/2"36'-7 1/2"
1'-7"
4 1/4"
2'-1 3/4"
7'-3 1/2"
9"
5'-4 1/2"
25'-2 3/4"
E6
A512
E6
A512
20'-6"25'-2 3/4"
SB3.1
SB3.1
SB3.1
SB3.1
SB3.1
SB3.1
SB3.1
SB3.1 SB3.1
SB3.1
SB3.1
SB3.1
SB3.1
SB3.1
SB3.1
SB3.1
SB3.1
SB3.1
SB3.1
SB3.1
SB3.1
SB3.1
SB3.1
SB3.1
SB2.1SB2.1
SB3.1
SB3.1
SB3.1
SB3.1
SB3.1
SB3.1
SB3.1
SB3.1
SB3.1
SB3.1
SB3.1
SB3.1
SB3.1
SB3.1
SB3.1
SB3.1
SB3.1
SB3.1
SB3.1
SB3.1
SA6
2 1/2"
5 3/4"
7"
LEGEND: INT. PARTITION CONDITIONS
1-HR FIRE RATED PARTITION
2-HR FIRE RATED PARTITION
NON-FIRE RATED WALL TAG (description)
SA6a
CORE MATERIAL (SEE LEGEND)
LAYERS (SEE LEGEND)
CORE SIZE (ROUNDED; SEE LEGEND)
HEAD CONDITION MODIFIER (IF APPLICABLE)
FIRE RATED WALL TAG (description)
FIRE RATING (IF APPLICABLE)
1SA6a
CORE MATERIAL (SEE LEGEND BELOW)
LAYERS (REF PARTITIONS SHEET)
CORE SIZE (ROUNDED; SEE LEGEND)
HEAD CONDITION MODIFIER (IF APPLICABLE)
C = CONCRETE WALLS, MASONRY
S = STEEL STUDS
W = WOOD STUDS
CORE MATERIAL LEGEND
CORE SIZE LEGEND
STEEL STUDS WOOD STUDS MASONRY (WIDTH)
BCONCRETE (WIDTH)
1 =A7/8"
2 = 1 5/8" 1 1/2"
3 = 2 1/2" 2 1/2"
4 = 3 5/8" 3 1/2" MASONRY SIZE 4"
5 =
6 = 6" 5 1/2" MASONRY SIZE 6" CONCRETE 6"
8 = 8" 7 1/4" MASONRY SIZE 8" CONCRETE 8"
10 = 9 1/4" MASONRY SIZE 10" CONCRETE 10"
12 = 11 1/4" MASONRY SIZE 12" CONCRETE 12"
14 = CONCRETE 14"
16 =MASONRY SIZE 16"
SUPERSCRIPT NOTES -
A - HAT CHANNEL FURRING IN LIEU OF METAL STUD
B - IF WALL IS STRUCTURAL, DO NOT TAG WALL OR INCLUDE IN WALL TYPES
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
10/28/22
A122b
Level 02 Area
B Wall Type &
Dimension
Plan
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set1/8" = 1'-0"A1 Level 02 Area B Dimension Plan KEY PLAN
A
B
A. GENERAL CONTRACTOR SHALL FIELD VERIFY ALL CONDITIONS AND SHALL REPORT TO THE ARCHITECT ANY
UNKNOWN CONDITIONS, ERRORS, OR CONFLICTS IN THE DRAWINGS BEFORE BEGINNING WORK
B. DO NOT SCALE THE DRAWINGS
C. ALL EXPOSED INTERIOR STEEL COLUMNS TO BE PAINTED PNT-01 - SEE FINISH SCHEDULE
D. ALL EXPOSED EXTERIOR STEEL TO BE GALVANIZED, UNLESS NOTED OTHERWISE
E. SEE G000'S FOR TYPICAL MOUNTING HEIGHTS. PROVIDE SOLID BLOCKING IN WALLS FOR ALL WALL-MOUNTED
ITEMS WHETHER BLOCKING IS DEPICTED IN DRAWINGS OR NOT
F. COORDINATE ALL EQUIPMENT AND ACCESSORIES, INCLUDING ITEMS THAT ARE OWNER FURNISHED, OWNER
INSTALLED
G. SEE SHEET SERIES A500 FOR WALL AND ASSEMBLY TYPES
H. SEE SHEET SERIES A600 FOR DOOR AND WINDOW TYPES
I. SEE ELEVATIONS AND FINISH SCHEDULES FOR SURFACE TREATMENTS AT WALLS
J. SEE ELEVATIONS, SECTIONS, AND DETAILS FOR ADDITIONAL WALL CONSTRUCTION INFORMATION
K. DOOR OPENINGS ARE TO BE LOCATED 4" FROM THE FACE OF ADJACENT STUD UNLESS NOTED
OTHERWISE.
L. SEE FINISH PLANS AND INTERIOR ELEVATIONS FOR LEVEL 5 WALL FINISH LOCATIONS.
M. SEE SIGNAGE PLAN FOR IN WALL BLOCKING LOCATIONS.
N. ALL EXPOSED VINYL WALL COVERING WRAPPED COLUMNS ARE TO RECIEVE A PAINTED 1/4" GYP BOARD
WRAP DIRECTLY OVER EXISTING WALL
GENERAL NOTES
1
G
J
L
M
N
P
Q
E
C
2 3 4 5
KIDS PLAY
344CRESTROOM
344B
MOTHERS
ROOM
344A
STUDY (SM)
332
STUDY (SM)
336
STUDY (SM)
314
STUDY (SM)
316
ELEC
364
STUDY (SM)
320
STUDY (SM)
338
STUDY (SM)
318
ELECTRICAL
324B
STUDY (SM)
334
SA4.1
OFFICE
310
OFFICE
312
JUVENILE
300
SD4.1
STORAGE
306
SD4.1
STUDY (MED)
304
STUDY (MED)
302
SB4
SA4
SA4
SA6.1
FAMILY STUDY
344
( QUIET )
OPEN STUDY
342
OPEN STUDY
362
Bridge
Connection
-
BRIDGE
CONNECTION
3-A
STAIR 1
3-B
MENS
368
WOMENS
366
TEST RM
378
STUDY (SM)
330
Janitors Closet
376
SD4.1
OFFICE
322
MAC EQUIP
324A
STUDY (LG)
328
STUDY (LG)
326
SD4.1
SA4.1
MAC LAB
324
SD4.1
SD4.1
SD4.1
SA4
SA4
SA4
TEST RM
374
SA4
SA4
SA4
SA4
SA4
SA4
SD4
SD4.1
SA4
SA4
SA4.1
SA4
SA4 SA4
SA4
SA4
SA4 SA4
SA4
SA4.1
SD4.1
SD4.1
STUDY (SM)
340
SA4.1
ELECTRICAL
308
STORAGE
352
TEST RM
382
TEST RM
380
TEST RM
372
TEST RM
370
TEST RM
360
TEST RM
358
TEST RM
356
TEST RM
350
TEST RM
348
TEST RM
346
MECH CHASE
3-E
MECH
3-D
STAIRS
3-C
STAIR
3-F
ELEV
3-G
MECH CHASE
3-H
SB4
SA6.1
6"6'-4"9'-11 1/2"8'-8 3/4"4'-3 1/4"
ALIGN
11'-3 3/4"
11'-7"
3'-10 1/2"
9'-11 3/4"
8'-8"
6'-10 1/2"
9 1/2"
10'-6"
14'-2 3/4"
11'-8 1/2"
13'-0 1/2"
9 1/4"
12'-3 1/4"
13'-0 1/4"
12'-9"
12'-10 3/4"
12'-7 1/4"
12'-8"
9 1/2"
9 1/2"
9 1/2"
16'-2"
9'-4"7'-8 1/4"
ALIGN
5'-11"
9'-1 3/4"
9'-0"
9'-0 3/4"
ALIGN
1'-1"
7'-1"
8'-2"
ALIGN
ALIGN
ALIGN
5'-11"1'-8"7'-7"7'-7 3/4"
3'-1"
14'-3 3/4"
6
5'-11"1'-8"7'-7"7'-7 3/4"
10'-9"
5'-11"
10 1/4"
8'-10 1/2"4'-9 1/2"5'-0"
HALF WALL HALF WALL
SA4
SA4
SA4
SA4
SC4
SC4
SA4
SA4.1
SD4.1
SD4.1
SA4.1
SC4
SA4.1
SA4.1
SC4
SA4.1
SC4
SC4
SC4
SC4
SC4
SC4
SC4
SC4
SC4 SC4 SC4 SC4
SC4
SC4
SA4
1'-0"
10"
11'-2 1/2"
6'-8 1/2"
7'-7"
4'-8"
1'-0"
1'-0"
TYP.
SB3.1
ABOVE & BELOW
EXTERIOR
WINDOW, TYP.
SC4
AL
I
G
N
SA4
SA4
SC4SC4
ALIGN FRAMING
AT COLUMN, TYP.
SA4.1
SA4.1
SA4.1
SA4.1 SA4.1 SA4.1 SA4.1 SA4.1 SA4.1
3'-3 1/2"2'-8 1/2"4'-5"6'-0"4'-5"6'-0"
3'-4 3/4"
4'-6"
4'-4 3/4"
4'-5 1/4"
3'-4"
ALIGN
FRAMING
@ COLUMN
3'-3 1/2"
AL
I
G
N
AL
I
G
N
1'-0"
14'-2 3/4"
SB4
2SH4
SD4.1
SA6
SA4.1
OPEN STUDY
383
D6
A503
TYP.
D6
A503
SA4.1
SA4
SA4
2SH4
SB4
SA4.1
SA4.1
SA4
SA6.1
SIME1
A415
TYP. AT COLUMNS,
UNLESS OTHERWISE NOTED.
SB2.1
SB3.1
1'-0 1/2"
1'-2 1/2"
2"2"2"
2"2"
2"
2"
2"
2"
2"
2"
2"
2"2"2"
2"2 1/2"2"
2 1/2"
2 1/2"
2 1/2"
2 1/2"
2 1/2"
2 1/2"
LEGEND: INT. PARTITION CONDITIONS
1-HR FIRE RATED PARTITION
2-HR FIRE RATED PARTITION
NON-FIRE RATED WALL TAG (description)
SA6a
CORE MATERIAL (SEE LEGEND)
LAYERS (SEE LEGEND)
CORE SIZE (ROUNDED; SEE LEGEND)
HEAD CONDITION MODIFIER (IF APPLICABLE)
FIRE RATED WALL TAG (description)
FIRE RATING (IF APPLICABLE)
1SA6a
CORE MATERIAL (SEE LEGEND BELOW)
LAYERS (REF PARTITIONS SHEET)
CORE SIZE (ROUNDED; SEE LEGEND)
HEAD CONDITION MODIFIER (IF APPLICABLE)
C = CONCRETE WALLS, MASONRY
S = STEEL STUDS
W = WOOD STUDS
CORE MATERIAL LEGEND
CORE SIZE LEGEND
STEEL STUDS WOOD STUDS MASONRY (WIDTH)
BCONCRETE (WIDTH)
1 =A7/8"
2 = 1 5/8" 1 1/2"
3 = 2 1/2" 2 1/2"
4 = 3 5/8" 3 1/2" MASONRY SIZE 4"
5 =
6 = 6" 5 1/2" MASONRY SIZE 6" CONCRETE 6"
8 = 8" 7 1/4" MASONRY SIZE 8" CONCRETE 8"
10 = 9 1/4" MASONRY SIZE 10" CONCRETE 10"
12 = 11 1/4" MASONRY SIZE 12" CONCRETE 12"
14 = CONCRETE 14"
16 =MASONRY SIZE 16"
SUPERSCRIPT NOTES -
A - HAT CHANNEL FURRING IN LIEU OF METAL STUD
B - IF WALL IS STRUCTURAL, DO NOT TAG WALL OR INCLUDE IN WALL TYPES
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
10/28/22
A123a
Level 03 Area
A Wall Type &
Dimension
Plan
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set1/8" = 1'-0"A1 Level 03 Area A Dimension Plan KEY PLAN
A
B
1
G
J
L
M
N
P
Q
E
C
2 3 4 51.5
TIER 2
016
OFFICE
018
OFFICE
020
MEN'S RR
015
WOMEN'S RR
014
CUSTODIAL
STORAGE
042
STORAGE
044
QA
022A
OPS
022
BDF
040
ELECTRICAL
038
CUSTODIAL
036
MECH CHASE
034
ELEV
0-J
STAIR
0-E
MECH CHASE
O-F
STAIR
0-E
STORAGE
032
MECH ROOM
030
CHEMICALS
ROOM
O-D
TECH ROOM
024
STUDENTS
026F OFFICE
026C
SHORT TERM
STORAGE
028
OFFICE
026A OFFICE
011
OFFICE
012
OFFICE
010
IMAGING AND
STORAGE
009
BREAK ROOM
013
A1 8' - 0"
B1 8' - 0"B1 8' - 0"
A1 8' - 0"
A1 8' - 0"
A1 8' - 0"
A1 8' - 0"
A1 8' - 0"
A1 8' - 0"
A1 8' - 0"
A1 8' - 0"A1 8' - 0"
A1 8' - 0"A1 8' - 0"A1 8' - 0"
A1 8' - 0"
0' - 0"E1
(EXISTING)
A1 8' - 0"A1 8' - 0"A1 8' - 0"A1 8' - 0"
6
OFFICE
026E
OFFICE
026D
OFFICE
026B
A1 8' - 0"
C6
A515
C6
A515
C6
A515
A1 8' - 0"
C6
A515
02.52
12.02 12.02
ACT-01:
2' x 2' LAY-IN ACOUSTICAL TILE & SUSPENSION SYSTEM, RE: FINISH SCHEDULE
CEILING LEGEND
TYPE A1
5/8" GYPSUM BOARD CEILING OR CLOUD ON METAL STUD, PAINTED PNT-02a
TYPE B1
EXPOSED STRUCTURE, WAFFLE CEILING. CLEAN AND PREP CONCRETE CEILING PRIOR TO PAINTING,
INCLUDING REMOVAL OF ANY RESIDUAL FORMS, TIES, CHAMFER STRIPS, ETC, FOR A NEAT
APPEARANCE. PAINTED PNT-02b @ ALL EXPOSED ELEMENTS INCLUDING BUT NOT LIMITED TO EXPOSED
CONDUIT, SPRINKLER PIPING, ETC. REFER TO DETAIL E5/A514 FOR EXPOSED UNISTRUT AREAS.
TYPE E-1
DECORATIVE CLOUD CEILING, GYP WITH WOOD VENEER SURROUND, RE: CEILING DETAILS FOR ALL
FINISH TYPES
TYPE D1
NOTE:
ALL DROPS NEED TO BE NON-COMBUSTABLE METAL FRAMING OR LIGHT GAUGE METAL FRAMING AND
MEET L/360 STANDARD FOR ALLOWABLE DEFLECTION.
DECORATIVE CLOUD CEILING, WOOD VENEER WV-01, RE: FINISH SCHEDULE
TYPE D1
EXISTING CEILING TILE/GRID, PROTECT DURING CONSTRUCTION
EXISTING
DRYVIT "CCP 2 COMMERCIAL CEMENT PLASTER"ASSEMBLY - SEE ASSEMBLY SHEET FOR DETAILS
FINISH TO BE "SANDPEBBLE FINE"
COLOR - OFFWHITE TO BE SELECTED FROM FULL RANGE OF COLOR OPTIONS
TYPE F-1
ACP-02: TECTUM PANELS, RE: FINISH SCHEDULE
SUBMIT ACOUSTICAL PANEL LAYOUT FOR APPROVAL
NOT IN SCOPE
TYPE G-1
EXPOSED TO EXISTING STRUCTURE
TYPE E-2
5/8" GYPSUM BOARD CEILING OR CLOUD ON METAL STUD, PAINTED PNT-02c
TYPE B2
INTEGRATED PICTURE RAIL, SEE CEILING DETAILS
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
10/28/22
A130a
Level 00 Area
A Reflected
Ceiling Plan
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
GENERAL NOTES - CEILING
1 VERIFY ALL MECHANICAL DUCT, GRILLE, DIFFUSER, AND VENT LOCATIONS WITH MECHANICAL DRAWINGS
2 CEILING GRID SHOWN IS ONLY A GRAPHIC REPRESENTATION OF CEILING. CEILING PATTERN IS TO BE CENTERED IN THE
ROOM, UNLESS NOTED OTHERWISE. CONTRACTOR SHALL VERIFY ACTUAL GRID LAYOUT/LOCATION
3 VERIFY AND COORDINATE ALL MECHANICAL DUCT, GRILL DIFFUSER & LOCATIONS, VENTS, AND QUANTITY WITH
MECHANICAL PLANS
4 VERIFY ALL LIGHTS, SMOKE DETECTORS, AND EXIT DEVICE LOCATIONS AND QUANTITIES WITH ELECTRICAL DRAWINGS.
SEE ARCHITECTURE FOR LIGHT LAYOUT LOCATION. LIGHT FIXTURES TO BE CENTERED AND SYMMETRICALLY LOCATED
IN UNITS AND SHARED SPACES UNLESS NOTED OTHERWISE
5 PROVIDE DEFLECTION TRACKS AT TOP OF ALL COLD FORMED METAL FRAMING; SEE SHEET SERIES AE500
6 MAKE FACTORY EDGE WHERE TILE IS CUT TYPICAL FOR ALL LAY-IN ACOUSTICAL TILE WITH REGULAR EDGE
7 SEE SHEET SERIES A600's FOR FINISH MATERIAL SPECIFICATIONS
8 VERIFY CEILING HEIGHTS IN UNITS WITH SHEET SERIES A400's. CONTRACTOR TO VERIFY AND MAXIMIZE CEILING HEIGHT
IN ALL AREAS DEPENDENT ON DUCTWORK LOCATIONS
9 ELECTRICIAN SHALL NOT SET ANY CEILING J-BOXES THAT ARE FOR LIGHTS BEFORE THE FINAL LOCATION OF THE
DROPPED SOFFITS HAVE BEEN DETERMINED. THIS WILL ENSURE THAT THE LIGHTS THAT NEED TO BE CENTERED ARE
CORRECTLY CENTERED BETWEEN THE SOFFITS
10 PAINT ALL EXPOSED ELECTRICAL CONDUIT. ATTACH AND HOLD TIGHT TO CONCRETE WEB/FLANGE. RE: ELECTRICAL
11 EXPOSED SPRINKLER PIPING HELD DIRECTLY AGAINST BOTTOM OF CONCRETE FLANGE, PREP AND PAINT ALL EXPOSED
SPRINKLER PIPE AND ATTACHMENTS, WHERE OCCURS
12 PREP AND PAINT ALL EXPOSED MECHANICAL DUCTING, PIPING, AND ACCESSORIES
13 PREP AND PAINT ALL EXPOSED CONCRETE CEILING STRUCTURE
KEY PLAN
A
B
1/8" = 1'-0"A1 Level 00 Area A Reflected Ceiling Plan
KEYED NOTES
02.52 DEMO EXISTING CEILING AS NEEDED FOR HVAC, PLUMBING, AND FIRE. SEE MECHANICAL, PLUMBING, AND FIRE.
12.02 SINGLE ROLLER WINDOW SHADE, MANUAL, RS-01, RE: A1;A515 DETAIL, RE: FINISH SCHEDULE
SS
SS
SS
SS
SS
SS
PC
PCPC
ACT-01:
2' x 2' LAY-IN ACOUSTICAL TILE & SUSPENSION SYSTEM, RE: FINISH SCHEDULE
CEILING LEGEND
TYPE A1
5/8" GYPSUM BOARD CEILING OR CLOUD ON METAL STUD, PAINTED PNT-02a
TYPE B1
EXPOSED STRUCTURE, WAFFLE CEILING. CLEAN AND PREP CONCRETE CEILING PRIOR TO PAINTING,
INCLUDING REMOVAL OF ANY RESIDUAL FORMS, TIES, CHAMFER STRIPS, ETC, FOR A NEAT
APPEARANCE. PAINTED PNT-02b @ ALL EXPOSED ELEMENTS INCLUDING BUT NOT LIMITED TO EXPOSED
CONDUIT, SPRINKLER PIPING, ETC. REFER TO DETAIL E5/A514 FOR EXPOSED UNISTRUT AREAS.
TYPE E-1
DECORATIVE CLOUD CEILING, GYP WITH WOOD VENEER SURROUND, RE: CEILING DETAILS FOR ALL
FINISH TYPES
TYPE D1
NOTE:
ALL DROPS NEED TO BE NON-COMBUSTABLE METAL FRAMING OR LIGHT GAUGE METAL FRAMING AND
MEET L/360 STANDARD FOR ALLOWABLE DEFLECTION.
DECORATIVE CLOUD CEILING, WOOD VENEER WV-01, RE: FINISH SCHEDULE
TYPE D1
EXISTING CEILING TILE/GRID, PROTECT DURING CONSTRUCTION
EXISTING
DRYVIT "CCP 2 COMMERCIAL CEMENT PLASTER"ASSEMBLY - SEE ASSEMBLY SHEET FOR DETAILS
FINISH TO BE "SANDPEBBLE FINE"
COLOR - OFFWHITE TO BE SELECTED FROM FULL RANGE OF COLOR OPTIONS
TYPE F-1
ACP-02: TECTUM PANELS, RE: FINISH SCHEDULE
SUBMIT ACOUSTICAL PANEL LAYOUT FOR APPROVAL
NOT IN SCOPE
TYPE G-1
EXPOSED TO EXISTING STRUCTURE
TYPE E-2
5/8" GYPSUM BOARD CEILING OR CLOUD ON METAL STUD, PAINTED PNT-02c
TYPE B2
INTEGRATED PICTURE RAIL, SEE CEILING DETAILS
1
G
J
L
M
N
P
Q
E
C
2 3 4 51.5 6
B5
A311
A4
A516
E1
A516
E5
A515
TYP
C5
A515
TYP
A2
A561
TYP
C5
A515
TYP
E5
A515
TYP
E5
A515
TYP
E5
A515
TYP
C5
A515
TYP
C5
A515
TYP
A2
A515
TYP
TYP.
A1 10' - 0"
A1 10' - 0"
A1 10' - 0"
A1 10' - 0"
A1 10' - 0"
A1 10' - 0"A1 9' - 0"
A1 10' - 0"
A1 10' - 0"
A1 10' - 0"
A1 10' - 0"
B1 10' - 0"
B1 10' - 0"
A1 10' - 0"
A1 10' - 0"
A1 10' - 0"
B1 10' - 0"
A1 10' - 0"
A1 10' - 0"
A1 10' - 0"
A1 10' - 0"
A1 10' - 0"
A1 10' - 0"
A1 10' - 0"
A1 10' - 0"
B2 7' - 2"
B2 7' - 2"
B1 9' - 10"
B1 9' - 0"
B2 7' - 2"
B1 10' - 2"B1 10' - 2"
B1 10' - 2"B1 10' - 2"
B1 10' - 2"B1 10' - 2"
A1 10' - 0"
B1 9' - 10"B1 9' - 10"
A1 10' - 0"
A1 10' - 0"
A1 10' - 0"
F1 13' - 6"
F1 13' - 6"
F1 13' - 6"
F1 13' - 6"
F1 13' - 6"
F1 13' - 6"
F1 13' - 6"
F1 13' - 6"
OFFICE
130
OFFICE
129
OFFICE
131
STUDY (MED)
132
STAIR
1-H
RECEPTION
134
OFFICE
136
OFFICE
138
CONFERENCE
ROOM
140
BREAKROOM
142
FAMILY RR
144
OPEN STUDY
122B
MENS
146
WOMENS
148
JANITORS
OFFICE
147
OPEN STUDY
122C
STAIR
1-B
HD BOOK
COLLECTION
122
OPEN STUDY
122A
STUDY (SM)
128
STUDY (SM)
127
STUDY (SM)
126
STUDY (MED)
125
STUDY (MED)
124
VESTIBULE
1-F
CIRCULATION
RECEPTION
110
OPEN STUDY
118
OFFICE
114A
CHECK-IN
112
INTER LIBRARY
LOAN
WORKSPACE
114
OFFICE
106
OFFICE
108
OFFICE
104
STAIR
1-D
HALLWAY
1-C
MECH CHASE
1-K
CIRCULATION
RECEPTION
110
ELEC ROOM
102
RESERVE MEDIA
116
RESTROOM
VESTIBULE
144A
READING
150
ENTRY HALL
120B
VESTIBULE
1-A
STAIR
1-B
6' - 9 1/2"
C3
A515
TYP
C3
A515
TYP
D4
A515
TYP
E6
A515
B3
A515
C3
A515
TYP
C3
A515
TYP
E4
A515
E4
A515
E6
A515
B5
A515
A5
A515
TYP
B5
A515
A2
A515
TYP
G1 10' - 0"
G1 10' - 0"
G1 10' - 0"
15
'
-
4
1
/
2
"
5'
-
0
3
/
4
"
5'
-
0
3
/
4
"
15
'
-
4
1
/
2
"
5'
-
0
3
/
4
"
5'-0 3/4"11'-3"6'-0"8'-3"8'-3"6'-0"11'-3"5'-0 3/4"
4'-7 1/2"10'-9 3/4"2'-1 1/2"
1'
-
3
1
/
2
"
3'
-
9
1
/
2
"
15
'
-
4
1
/
2
"
3'
-
9
1
/
2
"
1'
-
3
1
/
2
"
1'-8 1/4"
11'-3"6'-0"8'-3"20'-5 1/4"5'-0 3/4"1'-8 1/4"15'-6 3/4"
CL
B2
A515
B3
A515
E-2
E-2
B1
A515
TYP
12.02 12.02 12.02 12.02
12.02
12.02
12.02
12.02 12.02 12.02
12.0212.0212.02
12.02
12.02
12.02
12.02
12.02
12.02
12.02
12.02
12.02
12.02
A1 10' - 0"
PNT-02a PNT-02a
PNT-02a PNT-02a
B1
MATCH EXISITNG
HEIGHT
B1
MATCH EXISITNG
HEIGHT
B5
A311 TYP.
A2
A561
TYP
10.44
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
10/28/22
A131a
Level 01 Area
A Reflected
Ceiling Plan
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
GENERAL NOTES - CEILING
1 VERIFY ALL MECHANICAL DUCT, GRILLE, DIFFUSER, AND VENT LOCATIONS WITH MECHANICAL DRAWINGS
2 CEILING GRID SHOWN IS ONLY A GRAPHIC REPRESENTATION OF CEILING. CEILING PATTERN IS TO BE CENTERED IN THE
ROOM, UNLESS NOTED OTHERWISE. CONTRACTOR SHALL VERIFY ACTUAL GRID LAYOUT/LOCATION
3 VERIFY AND COORDINATE ALL MECHANICAL DUCT, GRILL DIFFUSER & LOCATIONS, VENTS, AND QUANTITY WITH
MECHANICAL PLANS
4 VERIFY ALL LIGHTS, SMOKE DETECTORS, AND EXIT DEVICE LOCATIONS AND QUANTITIES WITH ELECTRICAL DRAWINGS.
SEE ARCHITECTURE FOR LIGHT LAYOUT LOCATION. LIGHT FIXTURES TO BE CENTERED AND SYMMETRICALLY LOCATED
IN UNITS AND SHARED SPACES UNLESS NOTED OTHERWISE
5 PROVIDE DEFLECTION TRACKS AT TOP OF ALL COLD FORMED METAL FRAMING; SEE SHEET SERIES AE500
6 MAKE FACTORY EDGE WHERE TILE IS CUT TYPICAL FOR ALL LAY-IN ACOUSTICAL TILE WITH REGULAR EDGE
7 SEE SHEET SERIES A600's FOR FINISH MATERIAL SPECIFICATIONS
8 VERIFY CEILING HEIGHTS IN UNITS WITH SHEET SERIES A400's. CONTRACTOR TO VERIFY AND MAXIMIZE CEILING HEIGHT
IN ALL AREAS DEPENDENT ON DUCTWORK LOCATIONS
9 ELECTRICIAN SHALL NOT SET ANY CEILING J-BOXES THAT ARE FOR LIGHTS BEFORE THE FINAL LOCATION OF THE
DROPPED SOFFITS HAVE BEEN DETERMINED. THIS WILL ENSURE THAT THE LIGHTS THAT NEED TO BE CENTERED ARE
CORRECTLY CENTERED BETWEEN THE SOFFITS
10 PAINT ALL EXPOSED ELECTRICAL CONDUIT. ATTACH AND HOLD TIGHT TO CONCRETE WEB/FLANGE. RE: ELECTRICAL
11 EXPOSED SPRINKLER PIPING HELD DIRECTLY AGAINST BOTTOM OF CONCRETE FLANGE, PREP AND PAINT ALL EXPOSED
SPRINKLER PIPE AND ATTACHMENTS, WHERE OCCURS
12 PREP AND PAINT ALL EXPOSED MECHANICAL DUCTING, PIPING, AND ACCESSORIES
13 PREP AND PAINT ALL EXPOSED CONCRETE CEILING STRUCTURE
KEY PLAN
A
B
KEYED NOTES
10.44 CEILING MOUNTED DISPLAY TV, OFOI, CONTRACTOR TO PROVIDE TV MOUNT AND SUPPORT AT CEILING
12.02 SINGLE ROLLER WINDOW SHADE, MANUAL, RS-01, RE: A1;A515 DETAIL, RE: FINISH SCHEDULE
1/8" = 1'-0"A1 Level 01 Area A Reflected Ceiling Plan
PC
16151413121110987
K
H
F
D
B
A
MECH
08
SMALL MEETING
192A
WORKSTATIONS/
FLEX SPACE
192
STORAGE
156D
PRACTICE
156C
PRACTICE
156E
OFFICE
156F
ELEV
1-T
ELEV EQUIP
08A
STORAGE
192C
OFFICE
192B
OFFICE
160B
OFFICE
160A
CONFERENCE
ROOM
158
TUTORING
ADMIN OPEN
AREA
160
PRACTICE
156B
PRACTICE
156A
WORKSPACE
156
WOMEN'S
RESTROOM
152
MEN'S
RESTROOM
154
CLASSROOM
162
CLASSROOM
164
VESTIBULE
1-U
CLASSROOM
166
CLASSROOM
168
STUDY
170A
STUDY
170B
STORAGE
170C
MATH LAB
RECEPTION
175
STUDENT PREP
174
I.T. HELP DESK
176
CLASSROOM
172
DROP IN MATH
LAB
170
ADJUNCT
OFFICE
180
OFFICE
181
OFFICE
182
OFFICE
183
OFFICE
184
OFFICE
185
OFFICE
186
ELECTRICAL
173
COLLABORATIVE
SPACE
188
CONFERENCE
188B
OFFICE
188A
VESTIBULE
1-Z
OFFICE
190B
OFFICE
190A
TRAINING AREA
190
STORAGE
190C
A1 9' - 0"
A1 9' - 0"
A1 9' - 0"
A1 9' - 0"
A1 10' - 0"
A1 10' - 0"
A1 10' - 0"A1 10' - 0"
B1 10' - 0"
B1 10' - 0"
B1 10' - 6"
A1 9' - 0"
STUDY
179
STUDY
178
A1 10' - 0"
A1 10' - 0"
A1 10' - 0"
A1 10' - 0"A1 10' - 0"
A1 10' - 0"
A1 10' - 0"A1 10' - 0"
A1 10' - 0"
A1 10' - 0"
A1 10' - 0"
0' - 0"E1
A1 10' - 0"
A1 10' - 0"A1 10' - 0"
A1 9' - 0"
A1 10' - 0"A1 10' - 0"
A1 10' - 0"
A1 10' - 0"
A1 10' - 0"
A1 10' - 0"A1 10' - 0"
B1 10' - 0"B1 10' - 0"
A4
A512
A1 9' - 0"
HALL
1-Y
B1 10' - 0"
D1 9' - 0"
HALL
1-S
A1 10' - 0"
STAIRS
1-N
HALL
1-P
HALL
1-X
A1 10' - 0"
A1 10' - 0"A1 10' - 0"A1 10' - 0"A1 10' - 0"A1 10' - 0"A1 10' - 0"
A1 10' - 0"A1 10' - 0"
C5
A515
TYP
C3
A515
TYP
A5
A515
TYP
A1 10' - 0"
A5
A515
TYPA5
A515
TYP
10.23
E2
A516
10.23 10.23
10.23
12.05
A1 10' - 0"
D1 9' - 0"
10.23
10.23
C5
A515
TYP
A1
A516A3
A516
B5
A516
B4
A516
HALL
1-R
9' - 3 3/4"
14' - 0"14' - 0"
14
'
-
0
"
14
'
-
0
"
14' - 0"
E1
A516
SIM.
TYP.
14' - 0"
8'
-
3
"
F1 13' - 6
1/2"
11"5'-7"12'-2 1/4"2'-4 3/4"11"
19
'
-
4
1
/
2
"
12
'
-
6
"
9'
-
6
"
6'
-
6
"
15
'
-
6
"
14
'
-
5
"
14' - 0"
10.23
B1
A515
TYP
B1
A515
TYP
A1 8' - 0"
B1
A515
TYP
12.02
12.06
12.02 12.02
12.02 12.02 12.02 12.02
12.06 12.06 12.06
12.06
B1
A515
TYP
B1
A515
TYP
12.02
12.02
ACT-01:
2' x 2' LAY-IN ACOUSTICAL TILE & SUSPENSION SYSTEM, RE: FINISH SCHEDULE
CEILING LEGEND
TYPE A1
5/8" GYPSUM BOARD CEILING OR CLOUD ON METAL STUD, PAINTED PNT-02a
TYPE B1
EXPOSED STRUCTURE, WAFFLE CEILING. CLEAN AND PREP CONCRETE CEILING PRIOR TO PAINTING,
INCLUDING REMOVAL OF ANY RESIDUAL FORMS, TIES, CHAMFER STRIPS, ETC, FOR A NEAT
APPEARANCE. PAINTED PNT-02b @ ALL EXPOSED ELEMENTS INCLUDING BUT NOT LIMITED TO EXPOSED
CONDUIT, SPRINKLER PIPING, ETC. REFER TO DETAIL E5/A514 FOR EXPOSED UNISTRUT AREAS.
TYPE E-1
DECORATIVE CLOUD CEILING, GYP WITH WOOD VENEER SURROUND, RE: CEILING DETAILS FOR ALL
FINISH TYPES
TYPE D1
NOTE:
ALL DROPS NEED TO BE NON-COMBUSTABLE METAL FRAMING OR LIGHT GAUGE METAL FRAMING AND
MEET L/360 STANDARD FOR ALLOWABLE DEFLECTION.
DECORATIVE CLOUD CEILING, WOOD VENEER WV-01, RE: FINISH SCHEDULE
TYPE D1
EXISTING CEILING TILE/GRID, PROTECT DURING CONSTRUCTION
EXISTING
DRYVIT "CCP 2 COMMERCIAL CEMENT PLASTER"ASSEMBLY - SEE ASSEMBLY SHEET FOR DETAILS
FINISH TO BE "SANDPEBBLE FINE"
COLOR - OFFWHITE TO BE SELECTED FROM FULL RANGE OF COLOR OPTIONS
TYPE F-1
ACP-02: TECTUM PANELS, RE: FINISH SCHEDULE
SUBMIT ACOUSTICAL PANEL LAYOUT FOR APPROVAL
NOT IN SCOPE
TYPE G-1
EXPOSED TO EXISTING STRUCTURE
TYPE E-2
5/8" GYPSUM BOARD CEILING OR CLOUD ON METAL STUD, PAINTED PNT-02c
TYPE B2
INTEGRATED PICTURE RAIL, SEE CEILING DETAILS
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
10/28/22
A131b
Level 01 Area
B Reflected
Ceiling Plan
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
GENERAL NOTES - CEILING
1 VERIFY ALL MECHANICAL DUCT, GRILLE, DIFFUSER, AND VENT LOCATIONS WITH MECHANICAL DRAWINGS
2 CEILING GRID SHOWN IS ONLY A GRAPHIC REPRESENTATION OF CEILING. CEILING PATTERN IS TO BE CENTERED IN THE
ROOM, UNLESS NOTED OTHERWISE. CONTRACTOR SHALL VERIFY ACTUAL GRID LAYOUT/LOCATION
3 VERIFY AND COORDINATE ALL MECHANICAL DUCT, GRILL DIFFUSER & LOCATIONS, VENTS, AND QUANTITY WITH
MECHANICAL PLANS
4 VERIFY ALL LIGHTS, SMOKE DETECTORS, AND EXIT DEVICE LOCATIONS AND QUANTITIES WITH ELECTRICAL DRAWINGS.
SEE ARCHITECTURE FOR LIGHT LAYOUT LOCATION. LIGHT FIXTURES TO BE CENTERED AND SYMMETRICALLY LOCATED
IN UNITS AND SHARED SPACES UNLESS NOTED OTHERWISE
5 PROVIDE DEFLECTION TRACKS AT TOP OF ALL COLD FORMED METAL FRAMING; SEE SHEET SERIES AE500
6 MAKE FACTORY EDGE WHERE TILE IS CUT TYPICAL FOR ALL LAY-IN ACOUSTICAL TILE WITH REGULAR EDGE
7 SEE SHEET SERIES A600's FOR FINISH MATERIAL SPECIFICATIONS
8 VERIFY CEILING HEIGHTS IN UNITS WITH SHEET SERIES A400's. CONTRACTOR TO VERIFY AND MAXIMIZE CEILING HEIGHT
IN ALL AREAS DEPENDENT ON DUCTWORK LOCATIONS
9 ELECTRICIAN SHALL NOT SET ANY CEILING J-BOXES THAT ARE FOR LIGHTS BEFORE THE FINAL LOCATION OF THE
DROPPED SOFFITS HAVE BEEN DETERMINED. THIS WILL ENSURE THAT THE LIGHTS THAT NEED TO BE CENTERED ARE
CORRECTLY CENTERED BETWEEN THE SOFFITS
10 PAINT ALL EXPOSED ELECTRICAL CONDUIT. ATTACH AND HOLD TIGHT TO CONCRETE WEB/FLANGE. RE: ELECTRICAL
11 EXPOSED SPRINKLER PIPING HELD DIRECTLY AGAINST BOTTOM OF CONCRETE FLANGE, PREP AND PAINT ALL EXPOSED
SPRINKLER PIPE AND ATTACHMENTS, WHERE OCCURS
12 PREP AND PAINT ALL EXPOSED MECHANICAL DUCTING, PIPING, AND ACCESSORIES
13 PREP AND PAINT ALL EXPOSED CONCRETE CEILING STRUCTURE
KEY PLAN
A
B
1/8" = 1'-0"A1 Level 01 Area B Reflected Ceiling Plan
KEYED NOTES
10.23 CEILING MOUNTED PROJECTOR, OFOI, STEEL PIPE SUPPORT PROVIDED BY CONTRACTOR
12.02 SINGLE ROLLER WINDOW SHADE, MANUAL, RS-01, RE: A1;A515 DETAIL, RE: FINISH SCHEDULE
12.05 SINGLE ROLLER WINDOW SHADE, MANUAL, RS-01, RE: E3;A514 DETAIL, RE: FINISH SCHEDULE
12.06 DOUBLE ROLLER WINDOW SHADE, MANUAL, RS-02, RE: E4;A514 DETAIL, RE: FINISH SCHEDULE
SS
SSSSSSSSSSSS SS
PC
PC
1
G
J
L
M
N
P
Q
E
C
2 3 4 5
A1 10' - 0"
TECH SERVICES
238
MECHANICAL
2-D
SHEET MUSIC
236
SCANNER
228C
DCAM
228B
VAULT
228E
ARCHIVE
228D
OFFICE
228A
OFFICE
232
LARGE
COMPUTER
CLASSROOM
234
STAIR
2-G
TECH SERV
STORAGE
2-E
ELEV
2-H
MECH CHASE
2-J
OPEN
COMPUTERS
240
OPEN STUDY
53
JANITOR'S
OFFICE
241
MOTHERS
243
ELECTRICAL
ROOM
242
MEN'S
RESTROOM
247
WOMEN'S
RESTROOM
248
I.T.
245
STAIR
2-A
OFFICE
200
OFFICE
202
STUDY (SM)
204
STUDY (SM)
208
STUDY (SM)
210
STUDY (SM)
212
STAIR
2-B
OPEN STUDY
220
STUDY (MED)
214
STUDY (MED)
216
STUDY (MED)
218
INSTRUCTION 1
222
INSTRUCTION 2
224
PRESS ROOM
226
SPECIAL
COLLECTIONS
228
OFFICE
230
B1 10' - 0"
A1 10' - 0"
A1 10' - 0"
STAIR
2-A
A1 10' - 0"
B2 7' - 2"
A1 10' - 0"
A1 10' - 0"
A1 10' - 0"
A1 10' - 0"
A1 10' - 0"
A1 10' - 0"
A1 10' - 0"
A1 10' - 0"A1 10' - 0"
A1 10' - 0"A1 10' - 0"
A1 10' - 0"
A1 10' - 0"
A1 10' - 0"
6
A1 10' - 0"
A1 10' - 0"
A1 10' - 0"A1 10' - 0"
A1 10' - 0"
A1 10' - 0"
A1 10' - 0"
A1 10' - 0"
31' - 3 3/4"
B1 7' - 2"
B1 10' - 0"
FAMILY RR
244
A1 10' - 0"
CLOSET
224a
CLOSET
222aA1 10' - 0"A1 10' - 0"
B1 10' - 0"
B1 9' - 0"
A1 8' - 0"
JANITOR'S
CLOSET
249
STUDY (MED)
206
A1 8' - 0"
B1 10' - 0"
B1 10' - 0"
A1 10' - 0"
A5
A515
TYP
D6
A515
A1 10' - 0"
C6
A515
B5
A515
A2
A561
TYP
E5
A515
TYP
C5
A512
C5
A512
B1
A516
B2
A516
HALL
2-K
E1
A516
SIM.
TYP.
B1
A516
B1
A516
B1
A516
E5
A515
TYP
E5
A515
TYP
E5
A515
TYP
F1 13' - 6
1/2"F1 13' - 6
1/2"F1 13' - 6
1/2"
A1 8' - 0"
IT
241A
B1 9' - 0"
B1 9' - 0"
1'-4"
3 1/2"1'-5 1/4"
1'-3 1/2"
8'-3"9'-0"8'-3"8'-3"9'-0"8'-3"8'-3"9'-0"
17
'
-
3
"
25
'
-
6
"
5'
-
0
3
/
4
"
47
'
-
9
3
/
4
"
CL CL CL CL CL CL
CL
CL
3'-7"
1'-4 1/2"
1'-5 1/4"
1'-4 1/2"CL
E-2
12.02
12.02
12.02
12.02
12.02
12.02
12.02
12.02 12.02 12.02 12.02
12.02
12.02
12.02
12.02
12.02
12.02 12.02 12.02
12.02 12.02 12.02
12.02
12.02
B1
A515
TYP
B1
A515
TYP
B1
A515
TYP
B1
A515
TYP
B1
A515
TYP
B1
A515
TYP
B1
A515
TYP
OPEN STUDY
250
PNT-02a PNT-02a
PNT-02a PNT-02a
B1
MATCH EXISITNG
HEIGHT
B1
MATCH EXISITNG
HEIGHT
ACT-01:
2' x 2' LAY-IN ACOUSTICAL TILE & SUSPENSION SYSTEM, RE: FINISH SCHEDULE
CEILING LEGEND
TYPE A1
5/8" GYPSUM BOARD CEILING OR CLOUD ON METAL STUD, PAINTED PNT-02a
TYPE B1
EXPOSED STRUCTURE, WAFFLE CEILING. CLEAN AND PREP CONCRETE CEILING PRIOR TO PAINTING,
INCLUDING REMOVAL OF ANY RESIDUAL FORMS, TIES, CHAMFER STRIPS, ETC, FOR A NEAT
APPEARANCE. PAINTED PNT-02b @ ALL EXPOSED ELEMENTS INCLUDING BUT NOT LIMITED TO EXPOSED
CONDUIT, SPRINKLER PIPING, ETC. REFER TO DETAIL E5/A514 FOR EXPOSED UNISTRUT AREAS.
TYPE E-1
DECORATIVE CLOUD CEILING, GYP WITH WOOD VENEER SURROUND, RE: CEILING DETAILS FOR ALL
FINISH TYPES
TYPE D1
NOTE:
ALL DROPS NEED TO BE NON-COMBUSTABLE METAL FRAMING OR LIGHT GAUGE METAL FRAMING AND
MEET L/360 STANDARD FOR ALLOWABLE DEFLECTION.
DECORATIVE CLOUD CEILING, WOOD VENEER WV-01, RE: FINISH SCHEDULE
TYPE D1
EXISTING CEILING TILE/GRID, PROTECT DURING CONSTRUCTION
EXISTING
DRYVIT "CCP 2 COMMERCIAL CEMENT PLASTER"ASSEMBLY - SEE ASSEMBLY SHEET FOR DETAILS
FINISH TO BE "SANDPEBBLE FINE"
COLOR - OFFWHITE TO BE SELECTED FROM FULL RANGE OF COLOR OPTIONS
TYPE F-1
ACP-02: TECTUM PANELS, RE: FINISH SCHEDULE
SUBMIT ACOUSTICAL PANEL LAYOUT FOR APPROVAL
NOT IN SCOPE
TYPE G-1
EXPOSED TO EXISTING STRUCTURE
TYPE E-2
5/8" GYPSUM BOARD CEILING OR CLOUD ON METAL STUD, PAINTED PNT-02c
TYPE B2
INTEGRATED PICTURE RAIL, SEE CEILING DETAILS
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
10/28/22
A132a
Level 02 Area
A Reflected
Ceiling Plan
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set1/8" = 1'-0"A1 Level 02 Area A Reflected Ceiling Plan
GENERAL NOTES - CEILING
1 VERIFY ALL MECHANICAL DUCT, GRILLE, DIFFUSER, AND VENT LOCATIONS WITH MECHANICAL DRAWINGS
2 CEILING GRID SHOWN IS ONLY A GRAPHIC REPRESENTATION OF CEILING. CEILING PATTERN IS TO BE CENTERED IN THE
ROOM, UNLESS NOTED OTHERWISE. CONTRACTOR SHALL VERIFY ACTUAL GRID LAYOUT/LOCATION
3 VERIFY AND COORDINATE ALL MECHANICAL DUCT, GRILL DIFFUSER & LOCATIONS, VENTS, AND QUANTITY WITH
MECHANICAL PLANS
4 VERIFY ALL LIGHTS, SMOKE DETECTORS, AND EXIT DEVICE LOCATIONS AND QUANTITIES WITH ELECTRICAL DRAWINGS.
SEE ARCHITECTURE FOR LIGHT LAYOUT LOCATION. LIGHT FIXTURES TO BE CENTERED AND SYMMETRICALLY LOCATED
IN UNITS AND SHARED SPACES UNLESS NOTED OTHERWISE
5 PROVIDE DEFLECTION TRACKS AT TOP OF ALL COLD FORMED METAL FRAMING; SEE SHEET SERIES AE500
6 MAKE FACTORY EDGE WHERE TILE IS CUT TYPICAL FOR ALL LAY-IN ACOUSTICAL TILE WITH REGULAR EDGE
7 SEE SHEET SERIES A600's FOR FINISH MATERIAL SPECIFICATIONS
8 VERIFY CEILING HEIGHTS IN UNITS WITH SHEET SERIES A400's. CONTRACTOR TO VERIFY AND MAXIMIZE CEILING HEIGHT
IN ALL AREAS DEPENDENT ON DUCTWORK LOCATIONS
9 ELECTRICIAN SHALL NOT SET ANY CEILING J-BOXES THAT ARE FOR LIGHTS BEFORE THE FINAL LOCATION OF THE
DROPPED SOFFITS HAVE BEEN DETERMINED. THIS WILL ENSURE THAT THE LIGHTS THAT NEED TO BE CENTERED ARE
CORRECTLY CENTERED BETWEEN THE SOFFITS
10 PAINT ALL EXPOSED ELECTRICAL CONDUIT. ATTACH AND HOLD TIGHT TO CONCRETE WEB/FLANGE. RE: ELECTRICAL
11 EXPOSED SPRINKLER PIPING HELD DIRECTLY AGAINST BOTTOM OF CONCRETE FLANGE, PREP AND PAINT ALL EXPOSED
SPRINKLER PIPE AND ATTACHMENTS, WHERE OCCURS
12 PREP AND PAINT ALL EXPOSED MECHANICAL DUCTING, PIPING, AND ACCESSORIES
13 PREP AND PAINT ALL EXPOSED CONCRETE CEILING STRUCTURE
KEY PLAN
A
B
KEYED NOTES
12.02 SINGLE ROLLER WINDOW SHADE, MANUAL, RS-01, RE: A1;A515 DETAIL, RE: FINISH SCHEDULE
PC
161514
13
13121110987
K
H
F
D
B
A
WRITING
CENTER OPEN
TUTORING
256
PREP /
STORAGE
256A
OFFICE
256B
OFFICE
256C
CLASSROOM
258
CLASSROOM
260
OFFICE
264
OFFICE
265
STUDY
266
STUDY
267
STUDY
268 STUDY
269
OPEN TUTORING
CENTER
270
PREFUNCTION
270F
PRE-FUNCTION
270E
STUDY
270H
STORAGE
270J
CLASSROOM
272
CLASSROOM
278
MEN'S
RESTROOM
282
WOMEN'S
RESTROOM
284
TR / COMM.
280
PRE-FUNCTION
270C
PRE-FUNCTION
270D
PREP /
STORAGE
270B
OPEN TUTORING
254
OFFICE
252E
STORAGE
252F
PREP /
STORAGE
252G
STUDY
252B
STUDY
252A
STUDY
252C
OFFICE
252D
STUDY SKILLS
252
STAIR
2-P
STOR
299
ENGLISH
TRANSITION
CENTER
288
STORAGE
288H
OFFICE
288B
OFFICE
288C
ADJUNCT
OFFICE
286
A1 10' - 0"
A1 10' - 0"
A1 9' - 0"
A1 9' - 0"
A1 9' - 0"
A1 10' - 0"
A1 10' - 0"
A1 10' - 0"
A1 10' - 0"
A1 10' - 0"
A1 10' - 0"
A1 10' - 0"
B1 10' - 0"B1 10' - 0"B1 10' - 0"
A1 10' - 0"A1 10' - 0"
B1 10' - 0"
A1 10' - 0"
B1 8' - 0"
B1 8' - 0"
A1 10' - 0"
B1 8' - 0"
A1 10' - 0"
A1 10' - 0"
A1 10' - 0"
A1 10' - 0"A1 10' - 0"
A1 10' - 0"A1 10' - 0"
A1 10' - 0"A1 10' - 0"A1 10' - 0"
A1 10' - 0"
A1 10' - 0"
A1 10' - 0"
A1 10' - 0"
STUDY
270G
OPEN TUTORING
CENTER
270
ELEV
2-R
RECEPTION
270A
A1 10' - 0"
CLASSROOM
276
CLASSROOM
274
A1 10' - 0"A1 10' - 0"
A1 10' - 0"
STUDY
288A
STUDY
288D
STUDY
288E
STUDY
288F
STUDY
288G
HALL
2-Q
HALL
2-Q
STUDY SKILLS
252
HALL
2-W
HALL
2-U
STUDY SKILLS
252
A4
A512
A1 10' - 0"
B1 10' - 0"
B1 8' - 4"
A1 10' - 0"
B1 10' - 0"
B1 10' - 0"
A5
A515
TYP
A5
A515
TYP
A2
A561
TYP
C6
A515
A1 10' - 0"
A5
A515
TYP
A5
A515
TYP
C5
A512
C5
A512
A5
A512
B5
A512
10.23
10.23
10.23
10.23 10.23
10.23
D4
A516
A1 10' - 0"
A1 10' - 0"A1 10' - 0"
A1 10' - 0"
A1 10' - 0"
B1 10' - 6
1/2"
D3
A516
12.05
12' - 0"14' - 0"
14' - 0"
14' - 0"
14' - 0"
14' - 0"
A2
A512
C1
A516
1'-5 3/4"1'-5 1/4"1'-5 3/4"1'-5 3/4"1'-5 1/4"1'-5 3/4"
E-2
E-2
12.05
12.0212.02
12.02
12.02
14'-0"
12
'
-
0
"
10.23
STAIRS
2-V
12.02 12.02
12.06
12.06
12.02
12.02 12.02
12.02 12.02
12.02 12.0212.02
ACT-01:
2' x 2' LAY-IN ACOUSTICAL TILE & SUSPENSION SYSTEM, RE: FINISH SCHEDULE
CEILING LEGEND
TYPE A1
5/8" GYPSUM BOARD CEILING OR CLOUD ON METAL STUD, PAINTED PNT-02a
TYPE B1
EXPOSED STRUCTURE, WAFFLE CEILING. CLEAN AND PREP CONCRETE CEILING PRIOR TO PAINTING,
INCLUDING REMOVAL OF ANY RESIDUAL FORMS, TIES, CHAMFER STRIPS, ETC, FOR A NEAT
APPEARANCE. PAINTED PNT-02b @ ALL EXPOSED ELEMENTS INCLUDING BUT NOT LIMITED TO EXPOSED
CONDUIT, SPRINKLER PIPING, ETC. REFER TO DETAIL E5/A514 FOR EXPOSED UNISTRUT AREAS.
TYPE E-1
DECORATIVE CLOUD CEILING, GYP WITH WOOD VENEER SURROUND, RE: CEILING DETAILS FOR ALL
FINISH TYPES
TYPE D1
NOTE:
ALL DROPS NEED TO BE NON-COMBUSTABLE METAL FRAMING OR LIGHT GAUGE METAL FRAMING AND
MEET L/360 STANDARD FOR ALLOWABLE DEFLECTION.
DECORATIVE CLOUD CEILING, WOOD VENEER WV-01, RE: FINISH SCHEDULE
TYPE D1
EXISTING CEILING TILE/GRID, PROTECT DURING CONSTRUCTION
EXISTING
DRYVIT "CCP 2 COMMERCIAL CEMENT PLASTER"ASSEMBLY - SEE ASSEMBLY SHEET FOR DETAILS
FINISH TO BE "SANDPEBBLE FINE"
COLOR - OFFWHITE TO BE SELECTED FROM FULL RANGE OF COLOR OPTIONS
TYPE F-1
ACP-02: TECTUM PANELS, RE: FINISH SCHEDULE
SUBMIT ACOUSTICAL PANEL LAYOUT FOR APPROVAL
NOT IN SCOPE
TYPE G-1
EXPOSED TO EXISTING STRUCTURE
TYPE E-2
5/8" GYPSUM BOARD CEILING OR CLOUD ON METAL STUD, PAINTED PNT-02c
TYPE B2
INTEGRATED PICTURE RAIL, SEE CEILING DETAILS
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
10/28/22
A132b
Level 02 Area
B Reflected
Ceiling Plan
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
GENERAL NOTES - CEILING
1 VERIFY ALL MECHANICAL DUCT, GRILLE, DIFFUSER, AND VENT LOCATIONS WITH MECHANICAL DRAWINGS
2 CEILING GRID SHOWN IS ONLY A GRAPHIC REPRESENTATION OF CEILING. CEILING PATTERN IS TO BE CENTERED IN THE
ROOM, UNLESS NOTED OTHERWISE. CONTRACTOR SHALL VERIFY ACTUAL GRID LAYOUT/LOCATION
3 VERIFY AND COORDINATE ALL MECHANICAL DUCT, GRILL DIFFUSER & LOCATIONS, VENTS, AND QUANTITY WITH
MECHANICAL PLANS
4 VERIFY ALL LIGHTS, SMOKE DETECTORS, AND EXIT DEVICE LOCATIONS AND QUANTITIES WITH ELECTRICAL DRAWINGS.
SEE ARCHITECTURE FOR LIGHT LAYOUT LOCATION. LIGHT FIXTURES TO BE CENTERED AND SYMMETRICALLY LOCATED
IN UNITS AND SHARED SPACES UNLESS NOTED OTHERWISE
5 PROVIDE DEFLECTION TRACKS AT TOP OF ALL COLD FORMED METAL FRAMING; SEE SHEET SERIES AE500
6 MAKE FACTORY EDGE WHERE TILE IS CUT TYPICAL FOR ALL LAY-IN ACOUSTICAL TILE WITH REGULAR EDGE
7 SEE SHEET SERIES A600's FOR FINISH MATERIAL SPECIFICATIONS
8 VERIFY CEILING HEIGHTS IN UNITS WITH SHEET SERIES A400's. CONTRACTOR TO VERIFY AND MAXIMIZE CEILING HEIGHT
IN ALL AREAS DEPENDENT ON DUCTWORK LOCATIONS
9 ELECTRICIAN SHALL NOT SET ANY CEILING J-BOXES THAT ARE FOR LIGHTS BEFORE THE FINAL LOCATION OF THE
DROPPED SOFFITS HAVE BEEN DETERMINED. THIS WILL ENSURE THAT THE LIGHTS THAT NEED TO BE CENTERED ARE
CORRECTLY CENTERED BETWEEN THE SOFFITS
10 PAINT ALL EXPOSED ELECTRICAL CONDUIT. ATTACH AND HOLD TIGHT TO CONCRETE WEB/FLANGE. RE: ELECTRICAL
11 EXPOSED SPRINKLER PIPING HELD DIRECTLY AGAINST BOTTOM OF CONCRETE FLANGE, PREP AND PAINT ALL EXPOSED
SPRINKLER PIPE AND ATTACHMENTS, WHERE OCCURS
12 PREP AND PAINT ALL EXPOSED MECHANICAL DUCTING, PIPING, AND ACCESSORIES
13 PREP AND PAINT ALL EXPOSED CONCRETE CEILING STRUCTURE
KEY PLAN
A
B
1/8" = 1'-0"A1 Level 02 Area B Reflected Ceiling Plan
KEYED NOTES
10.23 CEILING MOUNTED PROJECTOR, OFOI, STEEL PIPE SUPPORT PROVIDED BY CONTRACTOR
12.02 SINGLE ROLLER WINDOW SHADE, MANUAL, RS-01, RE: A1;A515 DETAIL, RE: FINISH SCHEDULE
12.05 SINGLE ROLLER WINDOW SHADE, MANUAL, RS-01, RE: E3;A514 DETAIL, RE: FINISH SCHEDULE
12.06 DOUBLE ROLLER WINDOW SHADE, MANUAL, RS-02, RE: E4;A514 DETAIL, RE: FINISH SCHEDULE
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS SS
SS
SS
SS
SS
SS
SS
SS SS SS
SSSSSS
PC
1
G
J
L
M
N
P
Q
E
C
2 3 4 51.5
STUDY (SM)
340
STUDY (SM)
338
STUDY (SM)
336
STUDY (SM)
334
STUDY (SM)
332
STUDY (SM)
330
ELECTRICAL
324B
MAC EQUIP
324A
OFFICE
322
STUDY (SM)
320
STUDY (SM)
318
STUDY (SM)
316
STUDY (SM)
314
OFFICE
312
OFFICE
310
ELECTRICAL
308
STORAGE
306
STUDY (MED)
304
STUDY (MED)
302
BRIDGE
CONNECTION
3-A
Bridge
Connection
-
STAIR 1
3-B
JUVENILE
300
STUDY (LG)
328
TEST RM
382
TEST RM
380
TEST RM
378
Janitors Closet
376
WOMENS
366
MENS
368
TEST RM
370
TEST RM
372
TEST RM
374
ELEC
364
TEST RM
356
TEST RM
358
TEST RM
360
OPEN STUDY
362
STORAGE
352
TEST RM
350
TEST RM
348
TEST RM
346
RESTROOM
344B
KIDS PLAY
344C
MOTHERS
ROOM
344A
FAMILY STUDY
344
( QUIET )
OPEN STUDY
342
0' - 0"E1
0' - 0"E1
0' - 0"E1
0' - 0"E1
A1 10' - 0"
A1 10' - 0"
A1 10' - 0"A1 10' - 0"A1 10' - 0"
A1 10' - 0"A1 10' - 0"A1 10' - 0"
A1 10' - 0"
A1 10' - 0"
A1 10' - 0"
A1 10' - 0"
A1 10' - 0"
A1 10' - 0"
A1 10' - 0"
A1 10' - 0"A1 10' - 0"
A1 10' - 0"
A1 10' - 0"
A1 10' - 0"
A1 10' - 0"
A1 10' - 0"
A1 10' - 0"
A1 10' - 0"
A1 10' - 0"
A1 10' - 0"
A1 10' - 0"
A1 10' - 0"
A1 10' - 0"
A1 10' - 0"
A1 10' - 0"
A1 10' - 0"
A1 10' - 0"
A1 10' - 0"
A1 10' - 0"
MAC LAB
324
STUDY (LG)
326
B1 9' - 6"
B1 8' - 0"
B1 8' - 0"B1 8' - 0"
A1 10' - 0"
A1 10' - 0"
6
B1 10' - 0"
A1 10' - 0"
B2 7' - 2"
B2 7' - 2"
B1 9' - 0"
B1 10' - 0"
B1 10' - 6"B1 10' - 6"
B1 10' - 6"B1 10' - 6"
B1 10' - 6"B1 10' - 6"
A1 10' - 0"
B1 10' - 0"
A2
A561
TYP
E5
A515
TYP
C6
A515
C3
A515
TYP
E5
A515
TYP
D4
A515
TYP
C3
A515
TYP
B5
A515
D6
A515
D6
A515
D6
A515
A1 10' - 0"
D2
A516
D1
A516
OPEN STUDY
383
A1 10' - 0"
E1
A516
SIM.
TYP.
B4
A311
E5
A515
TYP
E5
A515
TYP
E5
A515
TYP
E5
A515
TYP
E5
A515
TYP
08.13
08.13
F1 13' - 6
1/2"F1 13' - 6
1/2"
D1 9' - 0"
5'-0 3/4"11'-3"6'-0"8'-3"8'-3"6'-0"11'-3"5'-0 3/4"
15
'
-
4
1
/
2
"
5'
-
0
3
/
4
"
5'
-
0
3
/
4
"
15
'
-
4
1
/
2
"
5'
-
0
3
/
4
"
15
'
-
4
1
/
2
"
5'
-
0
3
/
4
"
5'
-
0
3
/
4
"
8'-3"9'-0"8'-3"8'-3"9'-0"8'-3"
5'
-
0
3
/
4
"
25
'
-
6
"
17
'
-
3
"
8'
-
3
"
5'-9 3/4"5'-9 3/4"
9'
-
1
1
1
/
4
"
4'
-
9
1
/
4
"
12.02
B1
A515
TYP
B1
A515
TYP
12.02
12.02
12.02
12.02
12.0212.0212.02
12.02
12.02
12.02
12.02
12.02
12.02
12.02
12.02
12.02
12.02 12.02
12.02
PNT-02a PNT-02a PNT-02a PNT-02a
B1
MATCH EXISITNG
HEIGHT
B1
MATCH EXISITNG
HEIGHT
ACT-01:
2' x 2' LAY-IN ACOUSTICAL TILE & SUSPENSION SYSTEM, RE: FINISH SCHEDULE
CEILING LEGEND
TYPE A1
5/8" GYPSUM BOARD CEILING OR CLOUD ON METAL STUD, PAINTED PNT-02a
TYPE B1
EXPOSED STRUCTURE, WAFFLE CEILING. CLEAN AND PREP CONCRETE CEILING PRIOR TO PAINTING,
INCLUDING REMOVAL OF ANY RESIDUAL FORMS, TIES, CHAMFER STRIPS, ETC, FOR A NEAT
APPEARANCE. PAINTED PNT-02b @ ALL EXPOSED ELEMENTS INCLUDING BUT NOT LIMITED TO EXPOSED
CONDUIT, SPRINKLER PIPING, ETC. REFER TO DETAIL E5/A514 FOR EXPOSED UNISTRUT AREAS.
TYPE E-1
DECORATIVE CLOUD CEILING, GYP WITH WOOD VENEER SURROUND, RE: CEILING DETAILS FOR ALL
FINISH TYPES
TYPE D1
NOTE:
ALL DROPS NEED TO BE NON-COMBUSTABLE METAL FRAMING OR LIGHT GAUGE METAL FRAMING AND
MEET L/360 STANDARD FOR ALLOWABLE DEFLECTION.
DECORATIVE CLOUD CEILING, WOOD VENEER WV-01, RE: FINISH SCHEDULE
TYPE D1
EXISTING CEILING TILE/GRID, PROTECT DURING CONSTRUCTION
EXISTING
DRYVIT "CCP 2 COMMERCIAL CEMENT PLASTER"ASSEMBLY - SEE ASSEMBLY SHEET FOR DETAILS
FINISH TO BE "SANDPEBBLE FINE"
COLOR - OFFWHITE TO BE SELECTED FROM FULL RANGE OF COLOR OPTIONS
TYPE F-1
ACP-02: TECTUM PANELS, RE: FINISH SCHEDULE
SUBMIT ACOUSTICAL PANEL LAYOUT FOR APPROVAL
NOT IN SCOPE
TYPE G-1
EXPOSED TO EXISTING STRUCTURE
TYPE E-2
5/8" GYPSUM BOARD CEILING OR CLOUD ON METAL STUD, PAINTED PNT-02c
TYPE B2
INTEGRATED PICTURE RAIL, SEE CEILING DETAILS
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
10/28/22
A133a
Level 03 Area
A Reflected
Ceiling Plan
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
GENERAL NOTES - CEILING
1 VERIFY ALL MECHANICAL DUCT, GRILLE, DIFFUSER, AND VENT LOCATIONS WITH MECHANICAL DRAWINGS
2 CEILING GRID SHOWN IS ONLY A GRAPHIC REPRESENTATION OF CEILING. CEILING PATTERN IS TO BE CENTERED IN THE
ROOM, UNLESS NOTED OTHERWISE. CONTRACTOR SHALL VERIFY ACTUAL GRID LAYOUT/LOCATION
3 VERIFY AND COORDINATE ALL MECHANICAL DUCT, GRILL DIFFUSER & LOCATIONS, VENTS, AND QUANTITY WITH
MECHANICAL PLANS
4 VERIFY ALL LIGHTS, SMOKE DETECTORS, AND EXIT DEVICE LOCATIONS AND QUANTITIES WITH ELECTRICAL DRAWINGS.
SEE ARCHITECTURE FOR LIGHT LAYOUT LOCATION. LIGHT FIXTURES TO BE CENTERED AND SYMMETRICALLY LOCATED
IN UNITS AND SHARED SPACES UNLESS NOTED OTHERWISE
5 PROVIDE DEFLECTION TRACKS AT TOP OF ALL COLD FORMED METAL FRAMING; SEE SHEET SERIES AE500
6 MAKE FACTORY EDGE WHERE TILE IS CUT TYPICAL FOR ALL LAY-IN ACOUSTICAL TILE WITH REGULAR EDGE
7 SEE SHEET SERIES A600's FOR FINISH MATERIAL SPECIFICATIONS
8 VERIFY CEILING HEIGHTS IN UNITS WITH SHEET SERIES A400's. CONTRACTOR TO VERIFY AND MAXIMIZE CEILING HEIGHT
IN ALL AREAS DEPENDENT ON DUCTWORK LOCATIONS
9 ELECTRICIAN SHALL NOT SET ANY CEILING J-BOXES THAT ARE FOR LIGHTS BEFORE THE FINAL LOCATION OF THE
DROPPED SOFFITS HAVE BEEN DETERMINED. THIS WILL ENSURE THAT THE LIGHTS THAT NEED TO BE CENTERED ARE
CORRECTLY CENTERED BETWEEN THE SOFFITS
10 PAINT ALL EXPOSED ELECTRICAL CONDUIT. ATTACH AND HOLD TIGHT TO CONCRETE WEB/FLANGE. RE: ELECTRICAL
11 EXPOSED SPRINKLER PIPING HELD DIRECTLY AGAINST BOTTOM OF CONCRETE FLANGE, PREP AND PAINT ALL EXPOSED
SPRINKLER PIPE AND ATTACHMENTS, WHERE OCCURS
12 PREP AND PAINT ALL EXPOSED MECHANICAL DUCTING, PIPING, AND ACCESSORIES
13 PREP AND PAINT ALL EXPOSED CONCRETE CEILING STRUCTURE
KEY PLAN
A
B
1/8" = 1'-0"A1 Level 03 Area A Reflected Ceiling Plan
KEYED NOTES
08.13 24" X 24" CEILING ACCESS PANEL PAINTED TO MATCH ADJACENT CEILING COLOR.
12.02 SINGLE ROLLER WINDOW SHADE, MANUAL, RS-01, RE: A1;A515 DETAIL, RE: FINISH SCHEDULE
3
TT
FLOOR FINISH LEGEND
CARPET TILE
Room name
101
F
B
W WALL FINISH
BASE FINISH
FLOOR FINISH
ROOM NUMBER
FINISH KEY
FINISH CODE; REFER TO
ELEVATIONS FOR ENTIRE
SCOPE.
REFER TO FINISH SCHEDULE
FOR BASIS OF DESIGN.
CPT-02
CPT-01
LUXURY VINYL TILERF-01CONCRETE
CONCRETE
PSC-01
SC-01
NOTE: INDICATES MAIN FIELD FINISH; ASSUME THIS
FINISH IN ENTIRE AREA UNLESS AN ACCENT IS CALLED
OUT IN PLANS OR ELEVATION
CARPET TILE
*MULTIPLE FINISHES;
SEE ELEVATION
TYP. ROOM FINISH TAG ACCENT TAG
XX
-
X
X
EX
T
E
N
T
O
F
F
I
N
I
S
H
SC
O
P
E
ENTRY MAT TILEEM-01 TL-01 PORCELAIN TILE
CPT-03 CARPET TILE
WDF-01 WOOD FLOOR
D3
A301
D3
A301
C1
A301
C1
A301
TIER 2
016
CPT-01
WB-01
PNT-01
OFFICE
010
CPT-01
WB-01
PNT-01
OFFICE
026A
CPT-01
WB-01
PNT-01
OFFICE
011
CPT-01
WB-01
PNT-01
BREAK ROOM
013
RF-01
WB-01
PNT-01
OFFICE
018
CPT-01
WB-01
PNT-01
STORAGE
032
CPT-01
WB-01
PNT-01
OFFICE
012
CPT-01
WB-01
PNT-01
OFFICE
026C
CPT-01
WB-01
PNT-01
STUDENTS
026F
CPT-01
WB-01
PNT-01
TECH ROOM
024
CPT-01
WB-01
PNT-01
SHORT TERM STORAGE
028
CPT-01
WB-01
PNT-01
QA
022A
CPT-01
WB-01
PNT-01
OFFICE
020
CPT-01
WB-01
PNT-01
OPS
022
CPT-01
WB-01
PNT-01
STORAGE CUSTODIAL
STORAGE BDF
MEN'S RR WOMEN'S RR
ELECTRICAL
CUSTODIALMECH CHASEELEVSTAIR
MECH CHASESTAIR
MECH ROOM
CHEMICALS
ROOM
IMAGING AND
STORAGE
OFFICE
026D
CPT-01
WB-01
PNT-01
OFFICE
026E
CPT-01
WB-01
PNT-01
OFFICE
026B
CPT-01
WB-01
PNT-01
HALL
0-C
CPT-01
WB-01
PNT-01
HALL
0-D
CPT-01
WB-01
PNT-01
FTE
026
CPT-01
WB-01
PNT-01
HALL
0-B
CPT-01
WB-01
PNT-01
HALL
0-A
CPT-01
WB-01
PNT-01
HALL
DIRECTION OF FLOORING
DI
R
E
C
T
I
O
N
O
F
F
L
O
O
R
I
N
G
DI
R
E
C
T
I
O
N
O
F
F
L
O
O
R
I
N
G
DIRECTION OF FLOORING
DI
R
E
C
T
I
O
N
O
F
F
L
O
O
R
I
N
G
DI
R
E
C
T
I
O
N
O
F
F
L
O
O
R
I
N
G
DI
R
E
C
T
I
O
N
O
F
F
L
O
O
R
I
N
G
DI
R
E
C
T
I
O
N
O
F
F
L
O
O
R
I
N
G
DI
R
E
C
T
I
O
N
O
F
F
L
O
O
R
I
N
G
DI
R
E
C
T
I
O
N
O
F
F
L
O
O
R
I
N
G
DI
R
E
C
T
I
O
N
O
F
F
L
O
O
R
I
N
G
DI
R
E
C
T
I
O
N
O
F
F
L
O
O
R
I
N
G
DIRECTION OF FLOORING
DIRECTION OF FLOORING
DIRECTION OF FLOORING
DIRECTION OF FLOORING
DI
R
E
C
T
I
O
N
O
F
F
L
O
O
R
I
N
G
DI
R
E
C
T
I
O
N
O
F
F
L
O
O
R
I
N
G
DI
R
E
C
T
I
O
N
O
F
F
L
O
O
R
I
N
G
DI
R
E
C
T
I
O
N
O
F
F
L
O
O
R
I
N
G
DI
R
E
C
T
I
O
N
O
F
F
L
O
O
R
I
N
G
HALL
253
CPT-01
WB-01
PNT-01
HALL
257
CPT-01
WB-01
PNT-01
E2
A571
______________
E4
A572
TYP
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
10/28/22
A141
Level 00 Area
A Finish Plan
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
GENERAL NOTES - FINISH
1 SEE FLOOR PLANS FOR INTERIOR ELEVATIONS
2 ALL MATERIALS TO BE INSTALLED PER SPECIFIC MANUFACTURER'S INSTALLATION RECOMMENDATIONS
3 FLOORING MATERIAL TRANSITIONS TO OCCUR AT CENTERLINE OF DOOR THRESHOLDS, UNLESS NOTED OTHERWISE
4 PREPARE FLOORS/WALLS TO RECEIVE FINISH MATERIAL. REFER TO MANUFACTURER'S RECOMMENDATIONS FOR
SURFACE PREPARATION. NOTIFY ARCHITECT IF CONDITIONS ARE INADEQUATE FOR REQUIRED INSTALLATION
5 REFER TO ROOM FINISH LEGEND ON SHEET SERIES A600's FOR MORE INFORMATION
6 SEE DIMENSION PLAN SHEET SERIES A120's FOR WALL TYPE LOCATIONS; SEE SHEET SERIES A500's FOR WALL TYPE AND
ASSEMBLY DESCRIPTIONS
7 CONTRACTOR TO PROVIDE SOLID BLOCKING AT ALL CASEWORK, FIXED FURNISHINGS, AND EQUIPMENT. COORDINATE
WITH ELEVATIONS, SECTIONS, FURNITURE, FIXTURE SHEETS, AND SPECIFICATIONS
8 SEE SHEET SERIES A500's FOR TYPICAL DETAILS
9 TILE INSTALLER TO FOLLOW TCNA & ANSI GUIDELINES
10 ALL FLOORING MATERIALS ARE TO RUN WALL TO WALL AND BENEATH CASEWORK
11 VERIFY LOCATION OF POINT OR ORIGIN OF TILE AND CONTROL JOINTS ON SHOP DRAWINGS AND WITH ARCHITECT
ON-SITE PRIOR TO INSTALLATION
12 ALL GROUT TO BE SEALED
13 GENERAL CONTRACTOR TO COORDINATE POWER/DATA PLACEMENT WITH FURNITURE PROVIDER
14 LEVEL 5 FINISH REQUIRED FOR ALL WALL GRAPHIC AND WALLCOVERING LOCATIONS. SEE FINISH PLANS AND ELEVATIONS
FOR LOCATIONS
15 ALL METAL STUD WALLS TO DECK ABOVE, UNLESS NOTED OTHERWISE; SEE SHEET SERIES A500's FOR WALL TYPES
16 PROVIDE DEFLECTION TRACKS AT ALL STUD WALLS, SEE DETAILS ON SHEET SERIES A500's
17 ALL EXPOSED METAL TO BE INSTALLED PER SPECIFIC MANUFACTURER'S INSTALLATION RECOMMENDATIONS
18 CREATE A CLEAN, STRAIGHT TRANSITION LINE FROM POLISHED SEALED CONCRETE FLOORING TO SEALED CONCRETE
FLOORING UNDER DOORS. USE APPROPRIATE MEANS TO ACHIEVE A CLEAN TRANSITION
19 ALL GYP BOARD WALLS TO BE FINISHED. SEE FINISH PLAN ROOM TAGS FOR PAINT COLOR AND/OR FINISH
1/8" = 1'-0"A1 Level 00 AREA A FINISH PLAN
KEYED NOTES
FLOOR FINISH LEGEND
CARPET TILE
Room name
101
F
B
W WALL FINISH
BASE FINISH
FLOOR FINISH
ROOM NUMBER
FINISH KEY
FINISH CODE; REFER TO
ELEVATIONS FOR ENTIRE
SCOPE.
REFER TO FINISH SCHEDULE
FOR BASIS OF DESIGN.
CPT-02
CPT-01
LUXURY VINYL TILERF-01CONCRETE
CONCRETE
PSC-01
SC-01
NOTE: INDICATES MAIN FIELD FINISH; ASSUME THIS
FINISH IN ENTIRE AREA UNLESS AN ACCENT IS CALLED
OUT IN PLANS OR ELEVATION
CARPET TILE
*MULTIPLE FINISHES;
SEE ELEVATION
TYP. ROOM FINISH TAG ACCENT TAG
XX
-
X
X
EX
T
E
N
T
O
F
F
I
N
I
S
H
SC
O
P
E
ENTRY MAT TILEEM-01 TL-01 PORCELAIN TILE
CPT-03 CARPET TILE
WDF-01 WOOD FLOOR
CHECK-IN
112
CPT-01
WB-01
PNT-01
OFFICE
129
CPT-01
WB-01
PNT-01
OFFICE
130
CPT-01
WB-01
PNT-01
OFFICE
131
CPT-01
WB-01
PNT-01
STUDY (MED)
132
CPT-02
WB-01
PNT-01
OFFICE
136
CPT-01
WB-01
PNT-01RECEPTION
134
CPT-01
WB-01
PNT-01
OFFICE
138
CPT-01
WB-01
PNT-01
CONFERENCE ROOM
140
CPT-01
WB-01
PNT-01
BREAKROOM
142
RF-01
WB-01
PNT-01
STUDY (SM)
128
CPT-02
WB-01
PNT-01
STUDY (MED)
124
CPT-02
WB-01
PNT-01
STUDY (MED)
125
CPT-02
WB-01
PNT-01
STUDY (SM)
126
CPT-02
WB-01
PNT-01
STUDY (SM)
127
CPT-02
WB-01
PNT-01
OPEN STUDY
122A
CPT-01
WB-01
PNT-01
HD BOOK COLLECTION
122
CPT-01
WB-01
PNT-01
VESTIBULE
1-F
EM-01
-
-
CIRCULATION RECEPTION
110
CPT-01
WB-01
*
OFFICE
108
CPT-01
WB-01
PNT-01
INTER LIBRARY LOAN
WORKSPACE
114
CPT-01
WB-01
PNT-01
FAMILY RR
144
TL-01
WB-02
*
OPEN STUDY
122C
CPT-02
WB-01
PNT-01
OPEN STUDY
122B
CPT-02
WB-01
PNT-01
MENS WOMENS
JANITORS
OFFICE
OFFICE
106
CPT-01
WB-01
PNT-01
OFFICE
104
CPT-01
WB-01
PNT-01
OFFICE
114A
CPT-01
WB-01
PNT-01
STAIR
STAIR VESTIBULE
STAIR HALLWAY
MECH CHASE
MECH CHASE
ELEVATOR
Room
Room
1-M
NIC
NIC
PNT-01
RESERVE MEDIA
116
CPT-01
WB-01
PNT-01
MECH
ELEC ROOM
102
SC-01
WB-01
PNT-01
OPEN STUDY
100
CPT-01
WB-01
PNT-01
ENTRY HALL
120A
TL-01
WB-01
PNT-01
READING
150
CPT-01
WB-01
PNT-01
B5
A311
PNT-04
WB-03
PNT-04
WB-03
PNT-04
WB-03PNT-04
WB-03
PNT-04
WB-06
WV-01, WB-07
OPEN STUDY
118
CPT-01
WB-01
PNT-01
WC-01
LEVEL 5
FINISH
WC-01
WC-01
ENTRY HALL
120B
BDF
34
RESTROOM VESTIBULE
144A
CPT-01
WB-01
PNT-01
CPT-02
CPT-02
17' - 7 13/16"6' - 5 11/16"
9' - 4 3/8"
31' - 4 11/16"
3' - 4 15/16"
16' - 1 1/16"
3' - 8"
PNT-01
WB-05
PNT-01
WB-05
TL-01TL-02
PNT-05,
WB-04
E2
A147
D1
A147
E3
A147
PNT-04, WB-06
EM-01
EM-01
WC-01
LEVEL 5
FINISH
DI
R
E
C
T
I
O
N
O
F
F
L
O
O
R
I
N
G
WC-01
LEVEL 5
FINISH
DI
R
E
C
T
I
O
N
O
F
F
L
O
O
R
I
N
G
WC-01
LEVEL 5
FINISH
DI
R
E
C
T
I
O
N
O
F
F
L
O
O
R
I
N
G
WC-01
LEVEL 5
FINISH
DI
R
E
C
T
I
O
N
O
F
F
L
O
O
R
I
N
G
WC-01
LEVEL 5
FINISH
DI
R
E
C
T
I
O
N
O
F
F
L
O
O
R
I
N
G
DI
R
E
C
T
I
O
N
O
F
F
L
O
O
R
I
N
G
DI
R
E
C
T
I
O
N
O
F
F
L
O
O
R
I
N
G
DIRECTION OF FLOORING
DIRECTION OF FLOORING
WC-01
LEVEL 5
FINISH
DI
R
E
C
T
I
O
N
O
F
F
L
O
O
R
I
N
G
DI
R
E
C
T
I
O
N
O
F
F
L
O
O
R
I
N
G
DI
R
E
C
T
I
O
N
O
F
F
L
O
O
R
I
N
G
DI
R
E
C
T
I
O
N
O
F
F
L
O
O
R
I
N
G
DIRECTION OF FLOORING DIRECTION OF FLOORING
DI
R
E
C
T
I
O
N
O
F
F
L
O
O
R
I
N
G
DI
R
E
C
T
I
O
N
O
F
F
L
O
O
R
I
N
G
DIRECTION OF FLOORING
DIRECTION OF FLOORING
DIRECTION OF FLOORING
DI
R
E
C
T
I
O
N
O
F
F
L
O
O
R
I
N
G
DI
R
E
C
T
I
O
N
O
F
F
L
O
O
R
I
N
G
DIRECTION OF FLOORING
D1
A571
TYP
D1
A571
TYP
E1
A571
______________
D1
A571
TYP
E2
A571
______________
E2
A571
______________
D1
A571
TYP
D1
A571
TYP
WC-01
LEVEL 5
FINISH
WC-01
LEVEL 5
FINISH
WC-01
LEVEL 5
FINISH
16'-1"
ALIGN
ALIGN
TL-01 TL-02
2'-0"
EM-01
WC-01
LEVEL 5
FINISH
WC-01
LEVEL 5
FINISH
B2
A431
ALIGN
ALIGN
6'-8 1/4"
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
10/28/22
A142
Level 01 Area
A Finish Plan
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
GENERAL NOTES - FINISH
1 SEE FLOOR PLANS FOR INTERIOR ELEVATIONS
2 ALL MATERIALS TO BE INSTALLED PER SPECIFIC MANUFACTURER'S INSTALLATION RECOMMENDATIONS
3 FLOORING MATERIAL TRANSITIONS TO OCCUR AT CENTERLINE OF DOOR THRESHOLDS, UNLESS NOTED OTHERWISE
4 PREPARE FLOORS/WALLS TO RECEIVE FINISH MATERIAL. REFER TO MANUFACTURER'S RECOMMENDATIONS FOR
SURFACE PREPARATION. NOTIFY ARCHITECT IF CONDITIONS ARE INADEQUATE FOR REQUIRED INSTALLATION
5 REFER TO ROOM FINISH LEGEND ON SHEET SERIES A600's FOR MORE INFORMATION
6 SEE DIMENSION PLAN SHEET SERIES A120's FOR WALL TYPE LOCATIONS; SEE SHEET SERIES A500's FOR WALL TYPE AND
ASSEMBLY DESCRIPTIONS
7 CONTRACTOR TO PROVIDE SOLID BLOCKING AT ALL CASEWORK, FIXED FURNISHINGS, AND EQUIPMENT. COORDINATE
WITH ELEVATIONS, SECTIONS, FURNITURE, FIXTURE SHEETS, AND SPECIFICATIONS
8 SEE SHEET SERIES A500's FOR TYPICAL DETAILS
9 TILE INSTALLER TO FOLLOW TCNA & ANSI GUIDELINES
10 ALL FLOORING MATERIALS ARE TO RUN WALL TO WALL AND BENEATH CASEWORK
11 VERIFY LOCATION OF POINT OR ORIGIN OF TILE AND CONTROL JOINTS ON SHOP DRAWINGS AND WITH ARCHITECT
ON-SITE PRIOR TO INSTALLATION
12 ALL GROUT TO BE SEALED
13 GENERAL CONTRACTOR TO COORDINATE POWER/DATA PLACEMENT WITH FURNITURE PROVIDER
14 LEVEL 5 FINISH REQUIRED FOR ALL WALL GRAPHIC AND WALLCOVERING LOCATIONS. SEE FINISH PLANS AND ELEVATIONS
FOR LOCATIONS
15 ALL METAL STUD WALLS TO DECK ABOVE, UNLESS NOTED OTHERWISE; SEE SHEET SERIES A500's FOR WALL TYPES
16 PROVIDE DEFLECTION TRACKS AT ALL STUD WALLS, SEE DETAILS ON SHEET SERIES A500's
17 ALL EXPOSED METAL TO BE INSTALLED PER SPECIFIC MANUFACTURER'S INSTALLATION RECOMMENDATIONS
18 CREATE A CLEAN, STRAIGHT TRANSITION LINE FROM POLISHED SEALED CONCRETE FLOORING TO SEALED CONCRETE
FLOORING UNDER DOORS. USE APPROPRIATE MEANS TO ACHIEVE A CLEAN TRANSITION
19 ALL GYP BOARD WALLS TO BE FINISHED. SEE FINISH PLAN ROOM TAGS FOR PAINT COLOR AND/OR FINISH
1/8" = 1'-0"A1 Level 01 AREA A FINISH PLAN
KEYED NOTES
STORAGE
170C
CPT-01
WB-01
PNT-01
STUDY
170B
CPT-02
WB-01
PNT-01
STUDY
170A
CPT-02
WB-01
PNT-01
CLASSROOM
168
CPT-01
WB-01
PNT-01
CLASSROOM
166
CPT-01
WB-01
PNT-01
ADJUNCT OFFICE
180
CPT-01
WB-01
PNT-01
OFFICE
181
CPT-01
WB-01
PNT-01
OFFICE
182
CPT-01
WB-01
PNT-01
OFFICE
183
CPT-01
WB-01
PNT-01
OFFICE
184
CPT-01
WB-01
PNT-01
OFFICE
185
CPT-01
WB-01
PNT-01
OFFICE
186
CPT-01
WB-01
PNT-01
CONFERENCE ROOM
158
CPT-01
WB-01
PNT-01
CONFERENCE
188B
CPT-01
WB-01
PNT-01
COLLABORATIVE SPACE
188
CPT-01
WB-01
PNT-01
CLASSROOM
162
CPT-01
WB-01
PNT-01
CLASSROOM
164
CPT-01
WB-01
PNT-01
OFFICE
190B
CPT-01
WB-01
PNT-01
OFFICE
190A
CPT-01
WB-01
PNT-01
TRAINING AREA
190
CPT-01
WB-01
PNT-01
OFFICE
192B
CPT-01
WB-01
PNT-01
SMALL MEETING
192A
CPT-01
WB-01
PNT-01
OFFICE
160A
CPT-01
WB-01
PNT-01
OFFICE
160B
CPT-01
WB-01
PNT-01
TUTORING ADMIN OPEN
AREA
160
CPT-02
WB-01
*
OFFICE
156F
CPT-01
WB-01
PNT-01
PRACTICE
156E
CPT-01
WB-01
PNT-01
WORKSPACE
156
CPT-01
WB-01
PNT-01
STORAGE
156D
RF-01
WB-01
PNT-01 DROP IN MATH LAB
170
CPT-01
WB-01
PNT-01
WORKSTATIONS/ FLEX
SPACE
192
CPT-01
WB-01
PNT-01
CLASSROOM
172
CPT-01
WB-01
PNT-01
STUDENT PREP
174
CPT-01
WB-01
PNT-01
STUDY
178
CPT-02
WB-01
PNT-01
STUDY
179
CPT-02
WB-01
PNT-01
MATH LAB RECEPTION
175
CPT-02
WB-01
*
I.T. HELP DESK
176
CPT-02
WB-01
*
OFFICE
188A
CPT-01
WB-01
PNT-01
STORAGE
190C
CPT-01
WB-01
PNT-01
STORAGE
192C
CPT-01
WB-01
PNT-01
PRACTICE
156C
CPT-01
WB-01
PNT-01
PRACTICE
156B
CPT-01
WB-01
PNT-01
PRACTICE
156A
CPT-01
WB-01
PNT-01
VESTIBULE
1-U
EM-01
WB-01
PNT-01
ELECTRICAL
VESTIBULE
1-Z
EM-01
WB-01
PNT-01
MECH
ELEV EQUIP
ELEV
MEN'S
RESTROOM
WOMEN'S
RESTROOM
HALL
1-S
CPT-02
WB-01
PNT-01
HALL
1-R
CPT-01
WB-01
PNT-01
HALL
1-P
CPT-01
WB-01
PNT-01
STAIRS
1-N
CPT-01
WB-01
PNT-01
MECH
HALL
1-V
CPT-01
WB-01
PNT-01
HALL
1-X
CPT-01
WB-01
PNT-01HALL
1-Y
TL-01
WB-01
PNT-01
PNT-04
WB-03
PNT-04
WB-03
2' - 0"
5' - 4 1/4"
TL-02
TL-02
3' - 0"
2' - 6"
5' - 1"
2' - 2"
4' - 8"
2' - 0"
CP
T
-
0
2
-
A
L
I
G
N
S
W
I
T
H
E
X
P
O
S
E
D
C
E
I
L
I
N
G
CP
T
-
0
2
-
A
L
I
G
N
S
W
I
T
H
E
X
P
O
S
E
D
C
E
I
L
I
N
G
ALIGN
CPT-02 - ALIGNS WITH D1 CEILING CPT-02 - ALIGNS WITH D1 CEILING
DI
R
E
C
T
I
O
N
O
F
F
L
O
O
R
I
N
G
DI
R
E
C
T
I
O
N
O
F
F
L
O
O
R
I
N
G
DI
R
E
C
T
I
O
N
O
F
F
L
O
O
R
I
N
G
DI
R
E
C
T
I
O
N
O
F
F
L
O
O
R
I
N
G
DI
R
E
C
T
I
O
N
O
F
F
L
O
O
R
I
N
G
DI
R
E
C
T
I
O
N
O
F
F
L
O
O
R
I
N
G
DI
R
E
C
T
I
O
N
O
F
F
L
O
O
R
I
N
G
DIRECTION OF FLOORING
DIRECTION OF FLOORING DIRECTION OF FLOORING
DIRECTION OF FLOORING
DIRECTION OF FLOORINGDIRECTION OF FLOORING
DIRECTION OF FLOORING
DIRECTION OF FLOORING
DIRECTION OF FLOORING
RF-01
ALIGN
TL-01
TL-02
TL-01
TL-02
WALL GRAPHICS
LEVEL 5 FINISH
WALL GRAPHICS
LEVEL 5 FINISH
WA
L
L
G
R
A
P
H
I
C
S
,
LE
V
E
L
5
F
I
N
I
S
H
WALL GRAHPICS
LEVEL 5 FINISH
WALL GRAPHICS,
LEVEL 5 FINISH
4' - 8"
ALIGNS WITH
CEILING CLOUD
ALIGNS WITH
CEILING CLOUD
EM-01
ALIGN ALIGN
7' - 3"
10 1/4"
D1
A571
TYP
D1
A571
TYP
D1
A571
TYP
D1
A571
TYP
D1
A571
TYP
D1
A571
TYP
D1
A571
TYP
E2
A571
______________
RESTROOM VESTIBULE
2V
CPT-01
WB-01
PNT-01
EM-01
E4
A572
TYP
D1
A571
TYP
D2
A571
E5
A571
TYP
WALL GRAPHICS
LEVEL 5 FINISH
DI
R
E
C
T
I
O
N
O
F
F
L
O
O
R
I
N
G
FLOOR FINISH LEGEND
CARPET TILE
Room name
101
F
B
W WALL FINISH
BASE FINISH
FLOOR FINISH
ROOM NUMBER
FINISH KEY
FINISH CODE; REFER TO
ELEVATIONS FOR ENTIRE
SCOPE.
REFER TO FINISH SCHEDULE
FOR BASIS OF DESIGN.
CPT-02
CPT-01
LUXURY VINYL TILERF-01CONCRETE
CONCRETE
PSC-01
SC-01
NOTE: INDICATES MAIN FIELD FINISH; ASSUME THIS
FINISH IN ENTIRE AREA UNLESS AN ACCENT IS CALLED
OUT IN PLANS OR ELEVATION
CARPET TILE
*MULTIPLE FINISHES;
SEE ELEVATION
TYP. ROOM FINISH TAG ACCENT TAG
XX
-
X
X
EX
T
E
N
T
O
F
F
I
N
I
S
H
SC
O
P
E
ENTRY MAT TILEEM-01 TL-01 PORCELAIN TILE
CPT-03 CARPET TILE
WDF-01 WOOD FLOOR
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
10/28/22
A143
Level 01 Area
B Finish Plan
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
1/8" = 1'-0"A1 Level 01 AREA B FINISH PLAN
GENERAL NOTES - FINISH
1 SEE FLOOR PLANS FOR INTERIOR ELEVATIONS
2 ALL MATERIALS TO BE INSTALLED PER SPECIFIC MANUFACTURER'S INSTALLATION RECOMMENDATIONS
3 FLOORING MATERIAL TRANSITIONS TO OCCUR AT CENTERLINE OF DOOR THRESHOLDS, UNLESS NOTED OTHERWISE
4 PREPARE FLOORS/WALLS TO RECEIVE FINISH MATERIAL. REFER TO MANUFACTURER'S RECOMMENDATIONS FOR
SURFACE PREPARATION. NOTIFY ARCHITECT IF CONDITIONS ARE INADEQUATE FOR REQUIRED INSTALLATION
5 REFER TO ROOM FINISH LEGEND ON SHEET SERIES A600's FOR MORE INFORMATION
6 SEE DIMENSION PLAN SHEET SERIES A120's FOR WALL TYPE LOCATIONS; SEE SHEET SERIES A500's FOR WALL TYPE AND
ASSEMBLY DESCRIPTIONS
7 CONTRACTOR TO PROVIDE SOLID BLOCKING AT ALL CASEWORK, FIXED FURNISHINGS, AND EQUIPMENT. COORDINATE
WITH ELEVATIONS, SECTIONS, FURNITURE, FIXTURE SHEETS, AND SPECIFICATIONS
8 SEE SHEET SERIES A500's FOR TYPICAL DETAILS
9 TILE INSTALLER TO FOLLOW TCNA & ANSI GUIDELINES
10 ALL FLOORING MATERIALS ARE TO RUN WALL TO WALL AND BENEATH CASEWORK
11 VERIFY LOCATION OF POINT OR ORIGIN OF TILE AND CONTROL JOINTS ON SHOP DRAWINGS AND WITH ARCHITECT
ON-SITE PRIOR TO INSTALLATION
12 ALL GROUT TO BE SEALED
13 GENERAL CONTRACTOR TO COORDINATE POWER/DATA PLACEMENT WITH FURNITURE PROVIDER
14 LEVEL 5 FINISH REQUIRED FOR ALL WALL GRAPHIC AND WALLCOVERING LOCATIONS. SEE FINISH PLANS AND ELEVATIONS
FOR LOCATIONS
15 ALL METAL STUD WALLS TO DECK ABOVE, UNLESS NOTED OTHERWISE; SEE SHEET SERIES A500's FOR WALL TYPES
16 PROVIDE DEFLECTION TRACKS AT ALL STUD WALLS, SEE DETAILS ON SHEET SERIES A500's
17 ALL EXPOSED METAL TO BE INSTALLED PER SPECIFIC MANUFACTURER'S INSTALLATION RECOMMENDATIONS
18 CREATE A CLEAN, STRAIGHT TRANSITION LINE FROM POLISHED SEALED CONCRETE FLOORING TO SEALED CONCRETE
FLOORING UNDER DOORS. USE APPROPRIATE MEANS TO ACHIEVE A CLEAN TRANSITION
19 ALL GYP BOARD WALLS TO BE FINISHED. SEE FINISH PLAN ROOM TAGS FOR PAINT COLOR AND/OR FINISH
KEYED NOTES
ELECTRICAL ROOM
242
SC-01
WB-01
PNT-01
TECH SERV STORAGE
2-E
SC-01
WB-01
PNT-01
TECH SERVICES
238
CPT-01
WB-01
PNT-01
SHEET MUSIC
236
CPT-01
WB-01
PNT-01
LARGE COMPUTER
CLASSROOM
234
CPT-01
WB-01
PNT-01
OPEN COMPUTERS
240
CPT-01
WB-01
PNT-01
MOTHERS
243
RF-01
WB-01
PNT-01
OPEN STUDY
53
CPT-01
WB-01
PNT-01
PRESS ROOM
226
WDF-01
WB-01
PNT-01
SPECIAL COLLECTIONS
228
CPT-01
WB-01
PNT-01
VAULT
228E
CPT-01
WB-01
PNT-01
ARCHIVE
228D
CPT-01
WB-01
PNT-01
INSTRUCTION 2
224
CPT-01
WB-01
PNT-01
INSTRUCTION 1
222
CPT-01
WB-01
PNT-01
DCAM
228B
CPT-01
WB-01
PNT-01
OFFICE
228A
CPT-01
WB-01
PNT-01
SCANNER
228C
CPT-01
WB-01
PNT-01
OFFICE
232
CPT-01
WB-01
PNT-01
STUDY (MED)
216
CPT-02
WB-01
PNT-01
STUDY (MED)
214
CPT-02
WB-01
PNT-01
STUDY (MED)
218
CPT-02
WB-01
PNT-01
STUDY (SM)
204
CPT-02
WB-01
PNT-01
JANITOR'S OFFICE
241
CPT-01
WB-01
PNT-01
OFFICE
230
CPT-01
WB-01
PNT-01
OFFICE
202
CPT-01
WB-01
PNT-01
STUDY (SM)
212
CPT-02
WB-01
PNT-01
STUDY (SM)
210
CPT-02
WB-01
PNT-01
STUDY (SM)
208
CPT-02
WB-01
PNT-01
OFFICE
200
CPT-01
WB-01
PNT-01
OPEN STUDY
220
CPT-01
WB-01
PNT-01
MECHANICAL
2-D
SC-01
WB-01
PNT-01
I.T.
MEN'S
RESTROOM
WOMEN'S
RESTROOM
STAIR
ELEV MECH CHASE
STAIR
STAIR
2-B
OPEN STUDY
250
CPT-01
WB-01
PNT-01
MECH
MECH CHASE
HALL
2-K
CPT-01
WB-01
PNT-01
Room
HALL
2-M
CPT-01
WB-01
PNT-01
FAMILY RR
244
TL-01
WB-02
*
CLOSET
222a
CPT-01
WB-01
PNT-01
CLOSET
224a
CPT-01
WB-01
PNT-01
B5
A311
STUDY (MED)
206
CPT-02
WB-01
PNT-01
PNT-04,
WB-03
PNT-04,
WB-03
PNT-04,
WB-03
D4
A147
C2
A147
DIRECTION OF FLOORING
DI
R
E
C
T
I
O
N
OF
F
L
O
O
R
I
N
G
TL-01 TL-02
2' - 0"
5' - 4 3/4"
JANITOR'S CLOSET
249
SC-01
WB-01
PNT-01
3' - 0"
3' - 0"
FRP-01
DI
R
E
C
T
I
O
N
O
F
F
L
O
O
R
I
N
G
DI
R
E
C
T
I
O
N
O
F
F
L
O
O
R
I
N
G
DI
R
E
C
T
I
O
N
O
F
F
L
O
O
R
I
N
G
DI
R
E
C
T
I
O
N
O
F
F
L
O
O
R
I
N
G
DIRECTION OF FLOORING
DIRECTION OF FLOORING
DIRECTION OF FLOORING
DIRECTION OF FLOORING
DI
R
E
C
T
I
O
N
O
F
F
L
O
O
R
I
N
G
DI
R
E
C
T
I
O
N
O
F
F
L
O
O
R
I
N
G
DI
R
E
C
T
I
O
N
O
F
F
L
O
O
R
I
N
G
DI
R
E
C
T
I
O
N
O
F
F
L
O
O
R
I
N
G
DI
R
E
C
T
I
O
N
OF
F
L
O
O
R
I
N
G
DI
R
E
C
T
I
O
N
OF
F
L
O
O
R
I
N
G
DIRECTION OF FLOORING
DI
R
E
C
T
I
O
N
O
F
F
L
O
O
R
I
N
G
DI
R
E
C
T
I
O
N
OF
F
L
O
O
R
I
N
G
DIRECTION
OF FLOORING
DIRECTION OF FLOORING
DI
R
E
C
T
I
O
N
OF
F
L
O
O
R
I
N
G
DI
R
E
C
T
I
O
N
OF
F
L
O
O
R
I
N
G
DIRECTION
OF FLOORING
C2
A571
______________
C2
A571
______________
E1
A571
______________
E1
A571
______________
E2
A571
______________
D1
A571
TYP
D1
A571
TYP
E1
A571
______________
E1
A571
______________
IT
241A
SC-01
WB-01
PNT-01
WC-01
LEVEL 5
FINISH
DIRECTION OF FLOORING
WC-01
LEVEL 5
FINISH
DIRECTION OF FLOORING
WC-01
LEVEL 5
FINISH
DIRECTION OF FLOORING
WC-01
LEVEL 5
FINISH
DIRECTION OF FLOORING
WC-01
LEVEL 5
FINISH
DIRECTION OF FLOORING
WC-01
LEVEL 5
FINISH
DIRECTION OF FLOORING
WC-01
LEVEL 5
FINISH
WC-01
LEVEL 5
FINISH
FLOOR FINISH LEGEND
CARPET TILE
Room name
101
F
B
W WALL FINISH
BASE FINISH
FLOOR FINISH
ROOM NUMBER
FINISH KEY
FINISH CODE; REFER TO
ELEVATIONS FOR ENTIRE
SCOPE.
REFER TO FINISH SCHEDULE
FOR BASIS OF DESIGN.
CPT-02
CPT-01
LUXURY VINYL TILERF-01CONCRETE
CONCRETE
PSC-01
SC-01
NOTE: INDICATES MAIN FIELD FINISH; ASSUME THIS
FINISH IN ENTIRE AREA UNLESS AN ACCENT IS CALLED
OUT IN PLANS OR ELEVATION
CARPET TILE
*MULTIPLE FINISHES;
SEE ELEVATION
TYP. ROOM FINISH TAG ACCENT TAG
XX
-
X
X
EX
T
E
N
T
O
F
F
I
N
I
S
H
SC
O
P
E
ENTRY MAT TILEEM-01 TL-01 PORCELAIN TILE
CPT-03 CARPET TILE
WDF-01 WOOD FLOOR
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
10/28/22
A144
Level 02 Area
A Finish Plan
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set1/8" = 1'-0"A1 Level 02 AREA A FINISH PLAN
GENERAL NOTES - FINISH
1 SEE FLOOR PLANS FOR INTERIOR ELEVATIONS
2 ALL MATERIALS TO BE INSTALLED PER SPECIFIC MANUFACTURER'S INSTALLATION RECOMMENDATIONS
3 FLOORING MATERIAL TRANSITIONS TO OCCUR AT CENTERLINE OF DOOR THRESHOLDS, UNLESS NOTED OTHERWISE
4 PREPARE FLOORS/WALLS TO RECEIVE FINISH MATERIAL. REFER TO MANUFACTURER'S RECOMMENDATIONS FOR
SURFACE PREPARATION. NOTIFY ARCHITECT IF CONDITIONS ARE INADEQUATE FOR REQUIRED INSTALLATION
5 REFER TO ROOM FINISH LEGEND ON SHEET SERIES A600's FOR MORE INFORMATION
6 SEE DIMENSION PLAN SHEET SERIES A120's FOR WALL TYPE LOCATIONS; SEE SHEET SERIES A500's FOR WALL TYPE AND
ASSEMBLY DESCRIPTIONS
7 CONTRACTOR TO PROVIDE SOLID BLOCKING AT ALL CASEWORK, FIXED FURNISHINGS, AND EQUIPMENT. COORDINATE
WITH ELEVATIONS, SECTIONS, FURNITURE, FIXTURE SHEETS, AND SPECIFICATIONS
8 SEE SHEET SERIES A500's FOR TYPICAL DETAILS
9 TILE INSTALLER TO FOLLOW TCNA & ANSI GUIDELINES
10 ALL FLOORING MATERIALS ARE TO RUN WALL TO WALL AND BENEATH CASEWORK
11 VERIFY LOCATION OF POINT OR ORIGIN OF TILE AND CONTROL JOINTS ON SHOP DRAWINGS AND WITH ARCHITECT
ON-SITE PRIOR TO INSTALLATION
12 ALL GROUT TO BE SEALED
13 GENERAL CONTRACTOR TO COORDINATE POWER/DATA PLACEMENT WITH FURNITURE PROVIDER
14 LEVEL 5 FINISH REQUIRED FOR ALL WALL GRAPHIC AND WALLCOVERING LOCATIONS. SEE FINISH PLANS AND ELEVATIONS
FOR LOCATIONS
15 ALL METAL STUD WALLS TO DECK ABOVE, UNLESS NOTED OTHERWISE; SEE SHEET SERIES A500's FOR WALL TYPES
16 PROVIDE DEFLECTION TRACKS AT ALL STUD WALLS, SEE DETAILS ON SHEET SERIES A500's
17 ALL EXPOSED METAL TO BE INSTALLED PER SPECIFIC MANUFACTURER'S INSTALLATION RECOMMENDATIONS
18 CREATE A CLEAN, STRAIGHT TRANSITION LINE FROM POLISHED SEALED CONCRETE FLOORING TO SEALED CONCRETE
FLOORING UNDER DOORS. USE APPROPRIATE MEANS TO ACHIEVE A CLEAN TRANSITION
19 ALL GYP BOARD WALLS TO BE FINISHED. SEE FINISH PLAN ROOM TAGS FOR PAINT COLOR AND/OR FINISH
KEYED NOTES
CLASSROOM
276
CPT-01
WB-01
PNT-01
CLASSROOM
272
CPT-01
WB-01
PNT-01
OFFICE
288B
CPT-01
WB-01
PNT-01OFFICE
288C
CPT-01
WB-01
PNT-01
ENGLISH TRANSITION
CENTER
288
CPT-01
WB-01
PNT-01
OPEN TUTORING
254
CPT-01
WB-01
PNT-01
STUDY SKILLS
252
CPT-01
WB-01
PNT-01
WRITING CENTER OPEN
TUTORING
256
CPT-01
WB-01
PNT-01
STUDY
269
CPT-02
WB-01
PNT-01
STUDY
268
CPT-02
WB-01
PNT-01
STUDY
267
CPT-02
WB-01
PNT-01
STUDY
266
CPT-02
WB-01
PNT-01
OFFICE
265
CPT-01
WB-01
PNT-01
OFFICE
264
CPT-01
WB-01
PNT-01
STORAGE
270J
CPT-01
WB-01
PNT-01
STUDY
270H
CPT-02
WB-01
PNT-01
PREP / STORAGE
270B
RF-01
WB-01
PNT-01
CLASSROOM
258
CPT-01
WB-01
PNT-01
CLASSROOM
260
CPT-01
WB-01
PNT-01
PREP / STORAGE
256A
RF-01
WB-01
PNT-01
OFFICE
256B
CPT-01
WB-01
PNT-01
OFFICE
256C
CPT-01
WB-01
PNT-01
OPEN TUTORING CENTER
270
CPT-01
WB-01
PNT-01
ADJUNCT OFFICE
286
CPT-01
WB-01
PNT-01
TR / COMM.
280
CPT-01
WB-01
PNT-01
CLASSROOM
278
CPT-01
WB-01
PNT-01
PRE-FUNCTION
270C
CPT-02
WB-01
PNT-01
PRE-FUNCTION
270D
CPT-02
WB-01
PNT-01
PRE-FUNCTION
270E
CPT-02
WB-01
PNT-01
RECEPTION
270A
CPT-02
WB-01
PNT-01
PREFUNCTION
270F
CPT-02
WB-01
PNT-01
STUDY
252B
CPT-02
WB-01
PNT-01
PREP / STORAGE
252G
RF-01
WB-01
PNT-01
OFFICE
252E
CPT-01
WB-01
PNT-01
STORAGE
252F
RF-01
WB-01
PNT-01
OFFICE
252D
CPT-01
WB-01
PNT-01
STUDY
252A
CPT-02
WB-01
PNT-01
STUDY
252C
CPT-02
WB-01
PNT-01
STUDY
270G
CPT-02
WB-01
PNT-01
ELEV
WOMEN'S
RESTROOM
MEN'S
RESTROOM
STAIR
2-P
CPT-01
WB-01
PNT-01
STOR
MECH
CLASSROOM
274
CPT-01
WB-01
PNT-01
HALL
2-Q
CPT-01
WB-01
PNT-01
HALL
2-U
CPT-01
WB-01
PNT-01
HALL
2-W
CPT-01
WB-01
PNT-01
STORAGE
288H
CPT-01
WB-01
PNT-01
STUDY
288G
CPT-02
WB-01
PNT-01
STUDY
288F
CPT-02
WB-01
PNT-01
STUDY
288E
CPT-02
WB-01
PNT-01
STUDY
288D
CPT-02
WB-01
PNT-01
STUDY
288A
CPT-02
WB-01
PNT-01
PNT-04
WB-03
PNT-04
WB-03 PNT-04
WB-03
PNT-04
WB-03
PNT-04
WB-03
PNT-04
WB-03
PNT-04,
WB-03
Room
142f
CPT-01
WB-01
PNT-01
Room
142g
TL-01
TL-02
2' - 0"
4' - 8"
TL-01
TL-02
2' - 0"
5' - 1 3/8"
CPT-02
CPT-02
ALIGN
2' - 5 3/4"
ALGIN
ALGIN
2' - 2 3/4"
2' - 6"
11' - 0 3/16"
4' - 8"
2' - 0"
TL-01
TL-02
D1
A571
TYP D1
A571
TYP
E2
A571
______________
D1
A571
TYPD1
A571
TYPE2
A571
______________
E2
A571
______________
E2
A571
______________
ALIGN ALIGN
ALIGN
CPT-02
2'-5 3/4"
E4
A572
TYP
WALL GRAPHICS,
LEVEL 5 FINISH
WALL GRAPHICS,
LEVEL 5 FINISH
WALL GRAPHICS,
LEVEL 5 FINISH
WALL GRAPHICS,
LEVEL 5 FINISH
STAIRS
2-V
NIC
WB-01
PNT-01
DI
R
E
C
T
I
O
N
O
F
F
L
O
O
R
I
N
G
DI
R
E
C
T
I
O
N
O
F
F
L
O
O
R
I
N
G
DIRECTION OF FLOORING
DIRECTION OF FLOORING
DIRECTION OF FLOORING
DIRECTION OF FLOORING
DIRECTION OF FLOORING
DIRECTION OF FLOORING
DIRECTION OF FLOORING
DI
R
E
C
T
I
O
N
O
F
F
L
O
O
R
I
N
G
DIRECTION OF FLOORINGDIRECTION OF FLOORING
DIRECTION OF FLOORING
DIRECTION OF FLOORING
DIRECTION OF FLOORING
DIRECTION OF FLOORING
DI
R
E
C
T
I
O
N
O
F
F
L
O
O
R
I
N
G
FLOOR FINISH LEGEND
CARPET TILE
Room name
101
F
B
W WALL FINISH
BASE FINISH
FLOOR FINISH
ROOM NUMBER
FINISH KEY
FINISH CODE; REFER TO
ELEVATIONS FOR ENTIRE
SCOPE.
REFER TO FINISH SCHEDULE
FOR BASIS OF DESIGN.
CPT-02
CPT-01
LUXURY VINYL TILERF-01CONCRETE
CONCRETE
PSC-01
SC-01
NOTE: INDICATES MAIN FIELD FINISH; ASSUME THIS
FINISH IN ENTIRE AREA UNLESS AN ACCENT IS CALLED
OUT IN PLANS OR ELEVATION
CARPET TILE
*MULTIPLE FINISHES;
SEE ELEVATION
TYP. ROOM FINISH TAG ACCENT TAG
XX
-
X
X
EX
T
E
N
T
O
F
F
I
N
I
S
H
SC
O
P
E
ENTRY MAT TILEEM-01 TL-01 PORCELAIN TILE
CPT-03 CARPET TILE
WDF-01 WOOD FLOOR
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
10/28/22
A145
Level 02 Area
B Finish Plan
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
1/8" = 1'-0"B1 Level 02 AREA B FINISH PLAN
GENERAL NOTES - FINISH
1 SEE FLOOR PLANS FOR INTERIOR ELEVATIONS
2 ALL MATERIALS TO BE INSTALLED PER SPECIFIC MANUFACTURER'S INSTALLATION RECOMMENDATIONS
3 FLOORING MATERIAL TRANSITIONS TO OCCUR AT CENTERLINE OF DOOR THRESHOLDS, UNLESS NOTED OTHERWISE
4 PREPARE FLOORS/WALLS TO RECEIVE FINISH MATERIAL. REFER TO MANUFACTURER'S RECOMMENDATIONS FOR
SURFACE PREPARATION. NOTIFY ARCHITECT IF CONDITIONS ARE INADEQUATE FOR REQUIRED INSTALLATION
5 REFER TO ROOM FINISH LEGEND ON SHEET SERIES A600's FOR MORE INFORMATION
6 SEE DIMENSION PLAN SHEET SERIES A120's FOR WALL TYPE LOCATIONS; SEE SHEET SERIES A500's FOR WALL TYPE AND
ASSEMBLY DESCRIPTIONS
7 CONTRACTOR TO PROVIDE SOLID BLOCKING AT ALL CASEWORK, FIXED FURNISHINGS, AND EQUIPMENT. COORDINATE
WITH ELEVATIONS, SECTIONS, FURNITURE, FIXTURE SHEETS, AND SPECIFICATIONS
8 SEE SHEET SERIES A500's FOR TYPICAL DETAILS
9 TILE INSTALLER TO FOLLOW TCNA & ANSI GUIDELINES
10 ALL FLOORING MATERIALS ARE TO RUN WALL TO WALL AND BENEATH CASEWORK
11 VERIFY LOCATION OF POINT OR ORIGIN OF TILE AND CONTROL JOINTS ON SHOP DRAWINGS AND WITH ARCHITECT
ON-SITE PRIOR TO INSTALLATION
12 ALL GROUT TO BE SEALED
13 GENERAL CONTRACTOR TO COORDINATE POWER/DATA PLACEMENT WITH FURNITURE PROVIDER
14 LEVEL 5 FINISH REQUIRED FOR ALL WALL GRAPHIC AND WALLCOVERING LOCATIONS. SEE FINISH PLANS AND ELEVATIONS
FOR LOCATIONS
15 ALL METAL STUD WALLS TO DECK ABOVE, UNLESS NOTED OTHERWISE; SEE SHEET SERIES A500's FOR WALL TYPES
16 PROVIDE DEFLECTION TRACKS AT ALL STUD WALLS, SEE DETAILS ON SHEET SERIES A500's
17 ALL EXPOSED METAL TO BE INSTALLED PER SPECIFIC MANUFACTURER'S INSTALLATION RECOMMENDATIONS
18 CREATE A CLEAN, STRAIGHT TRANSITION LINE FROM POLISHED SEALED CONCRETE FLOORING TO SEALED CONCRETE
FLOORING UNDER DOORS. USE APPROPRIATE MEANS TO ACHIEVE A CLEAN TRANSITION
19 ALL GYP BOARD WALLS TO BE FINISHED. SEE FINISH PLAN ROOM TAGS FOR PAINT COLOR AND/OR FINISH
KEYED NOTES
STUDY (SM)
332
CPT-02
WB-01
PNT-01
STUDY (SM)
336
CPT-02
WB-01
PNT-01
STUDY (SM)
314
CPT-02
WB-01
PNT-01
STUDY (SM)
316
CPT-02
WB-01
PNT-01
ELEC
364
SC-01
WB-01
PNT-01
STUDY (SM)
320
CPT-02
WB-01
PNT-01
STUDY (SM)
338
CPT-02
WB-01
PNT-01
STUDY (SM)
318
CPT-02
WB-01
PNT-01
ELECTRICAL
324B
SC-01
WB-01
PNT-01
STUDY (SM)
334
CPT-02
WB-01
PNT-01
OFFICE
310
CPT-01
WB-01
PNT-01
OFFICE
312
CPT-01
WB-01
PNT-01
JUVENILE
300
CPT-01
WB-01
PNT-01
STORAGE
306
CPT-01
WB-01
PNT-01
STUDY (MED)
304
CPT-02
WB-01
PNT-01
STUDY (MED)
302
CPT-02
WB-01
PNT-01
KIDS PLAY
344C
CPT-03
WB-01
PNT-01
MOTHERS ROOM
344A
RF-01
WB-01
PNT-01
RESTROOM
344B
TL-01
WB-02
*
FAMILY STUDY
344
CPT-02
WB-01
PNT-01
( QUIET ) OPEN STUDY
342
CPT-01
WB-01
PNT-01
OPEN STUDY
362
CPT-01
WB-01
PNT-01
BRIDGE CONNECTION
3-A
CPT-01
WB-01
PNT-01
STAIR 1
MENS WOMENS
TEST RM
378
CPT-01
WB-01
PNT-01
STUDY (SM)
330
CPT-02
WB-01
PNT-01 Janitors Closet
OFFICE
322
CPT-01
WB-01
PNT-01
MAC EQUIP
324A
CPT-01
WB-01
PNT-01
STUDY (LG)
328
CPT-02
WB-01
PNT-01
STUDY (LG)
326
CPT-02
WB-01
PNT-01
MAC LAB
324
CPT-01
WB-01
PNT-01
TEST RM
374
CPT-01
WB-01
PNT-01
STUDY (SM)
340
CPT-02
WB-01
PNT-01
ELECTRICAL
308
SC-01
WB-01
PNT-01
STORAGE
352
CPT-01
WB-01
PNT-01
TEST RM
382
CPT-01
WB-01
PNT-01
TEST RM
380
CPT-01
WB-01
PNT-01
TEST RM
372
CPT-01
WB-01
PNT-01
TEST RM
370
CPT-01
WB-01
PNT-01
TEST RM
360
CPT-01
WB-01
PNT-01
TEST RM
358
CPT-01
WB-01
PNT-01
TEST RM
356
CPT-01
WB-01
PNT-01
TEST RM
350
CPT-01
WB-01
PNT-01
TEST RM
348
CPT-01
WB-01
PNT-01
TEST RM
346
CPT-01
WB-01
PNT-01
MECH CHASE
MECH STAIRS
STAIR
ELEV MECH CHASE
PNT-04
WB-03
PNT-04,
WB-03
PNT-04
WB-03
TL-01 TL-02
TL-01 TL-02
TL-01TL-02
C1
A147 PNT-04,
WB-03
DI
R
E
C
T
I
O
N
O
F
FL
O
O
R
I
N
G
DI
R
E
C
T
I
O
N
O
F
FL
O
O
R
I
N
G
DI
R
E
C
T
I
O
N
O
F
FL
O
O
R
I
N
G
DI
R
E
C
T
I
O
N
O
F
FL
O
O
R
I
N
G
DI
R
E
C
T
I
O
N
O
F
FL
O
O
R
I
N
G
DI
R
E
C
T
I
O
N
O
F
FL
O
O
R
I
N
G
DI
R
E
C
T
I
O
N
O
F
FL
O
O
R
I
N
G
DI
R
E
C
T
I
O
N
O
F
FL
O
O
R
I
N
G
DI
R
E
C
T
I
O
N
O
F
FL
O
O
R
I
N
G
DI
R
E
C
T
I
O
N
O
F
F
L
O
O
R
I
N
G
DI
R
E
C
T
I
O
N
O
F
F
L
O
O
R
I
N
G
DI
R
E
C
T
I
O
N
O
F
FL
O
O
R
I
N
G
DI
R
E
C
T
I
O
N
O
F
FL
O
O
R
I
N
G
DI
R
E
C
T
I
O
N
O
F
FL
O
O
R
I
N
G
DI
R
E
C
T
I
O
N
O
F
FL
O
O
R
I
N
G
DI
R
E
C
T
I
O
N
O
F
FL
O
O
R
I
N
G
DI
R
E
C
T
I
O
N
O
F
FL
O
O
R
I
N
G
DIRECTION OF
FLOORING
DIRECTION OF
FLOORING
DI
R
E
C
T
I
O
N
O
F
FL
O
O
R
I
N
G
DI
R
E
C
T
I
O
N
O
F
FL
O
O
R
I
N
G
5' - 4 3/4"
E2
A571
______________D1
A571
TYP
E1
A571
______________
D1
A571
TYP
D1
A571
TYP
E1
A571
______________
D1
A571
TYP
WB-02
WC-01
LEVEL 5
FINISH
DIRECTION OF FLOORING
WC-01
LEVEL 5
FINISH
DIRECTION OF FLOORING
WC-01
LEVEL 5
FINISH
WC-01
LEVEL 5
FINISH
WC-01
LEVEL 5
FINISH
WC-01
LEVEL 5
FINISH
WC-01
LEVEL 5
FINISH
WC-01
LEVEL 5
FINISH
WC-01
LEVEL 5
FINISH
WC-01
LEVEL 5
FINISH
WC-01
LEVEL 5
FINISH
WC-01
LEVEL 5
FINISH
WC-03
FLOOR FINISH LEGEND
CARPET TILE
Room name
101
F
B
W WALL FINISH
BASE FINISH
FLOOR FINISH
ROOM NUMBER
FINISH KEY
FINISH CODE; REFER TO
ELEVATIONS FOR ENTIRE
SCOPE.
REFER TO FINISH SCHEDULE
FOR BASIS OF DESIGN.
CPT-02
CPT-01
LUXURY VINYL TILERF-01CONCRETE
CONCRETE
PSC-01
SC-01
NOTE: INDICATES MAIN FIELD FINISH; ASSUME THIS
FINISH IN ENTIRE AREA UNLESS AN ACCENT IS CALLED
OUT IN PLANS OR ELEVATION
CARPET TILE
*MULTIPLE FINISHES;
SEE ELEVATION
TYP. ROOM FINISH TAG ACCENT TAG
XX
-
X
X
EX
T
E
N
T
O
F
F
I
N
I
S
H
SC
O
P
E
ENTRY MAT TILEEM-01 TL-01 PORCELAIN TILE
CPT-03 CARPET TILE
WDF-01 WOOD FLOOR
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
10/28/22
A146
Level 03 Area
A Finish Plan
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set1/8" = 1'-0"A1 Level 03 AREA A FINISH PLAN
GENERAL NOTES - FINISH
1 SEE FLOOR PLANS FOR INTERIOR ELEVATIONS
2 ALL MATERIALS TO BE INSTALLED PER SPECIFIC MANUFACTURER'S INSTALLATION RECOMMENDATIONS
3 FLOORING MATERIAL TRANSITIONS TO OCCUR AT CENTERLINE OF DOOR THRESHOLDS, UNLESS NOTED OTHERWISE
4 PREPARE FLOORS/WALLS TO RECEIVE FINISH MATERIAL. REFER TO MANUFACTURER'S RECOMMENDATIONS FOR
SURFACE PREPARATION. NOTIFY ARCHITECT IF CONDITIONS ARE INADEQUATE FOR REQUIRED INSTALLATION
5 REFER TO ROOM FINISH LEGEND ON SHEET SERIES A600's FOR MORE INFORMATION
6 SEE DIMENSION PLAN SHEET SERIES A120's FOR WALL TYPE LOCATIONS; SEE SHEET SERIES A500's FOR WALL TYPE AND
ASSEMBLY DESCRIPTIONS
7 CONTRACTOR TO PROVIDE SOLID BLOCKING AT ALL CASEWORK, FIXED FURNISHINGS, AND EQUIPMENT. COORDINATE
WITH ELEVATIONS, SECTIONS, FURNITURE, FIXTURE SHEETS, AND SPECIFICATIONS
8 SEE SHEET SERIES A500's FOR TYPICAL DETAILS
9 TILE INSTALLER TO FOLLOW TCNA & ANSI GUIDELINES
10 ALL FLOORING MATERIALS ARE TO RUN WALL TO WALL AND BENEATH CASEWORK
11 VERIFY LOCATION OF POINT OR ORIGIN OF TILE AND CONTROL JOINTS ON SHOP DRAWINGS AND WITH ARCHITECT
ON-SITE PRIOR TO INSTALLATION
12 ALL GROUT TO BE SEALED
13 GENERAL CONTRACTOR TO COORDINATE POWER/DATA PLACEMENT WITH FURNITURE PROVIDER
14 LEVEL 5 FINISH REQUIRED FOR ALL WALL GRAPHIC AND WALLCOVERING LOCATIONS. SEE FINISH PLANS AND ELEVATIONS
FOR LOCATIONS
15 ALL METAL STUD WALLS TO DECK ABOVE, UNLESS NOTED OTHERWISE; SEE SHEET SERIES A500's FOR WALL TYPES
16 PROVIDE DEFLECTION TRACKS AT ALL STUD WALLS, SEE DETAILS ON SHEET SERIES A500's
17 ALL EXPOSED METAL TO BE INSTALLED PER SPECIFIC MANUFACTURER'S INSTALLATION RECOMMENDATIONS
18 CREATE A CLEAN, STRAIGHT TRANSITION LINE FROM POLISHED SEALED CONCRETE FLOORING TO SEALED CONCRETE
FLOORING UNDER DOORS. USE APPROPRIATE MEANS TO ACHIEVE A CLEAN TRANSITION
19 ALL GYP BOARD WALLS TO BE FINISHED. SEE FINISH PLAN ROOM TAGS FOR PAINT COLOR AND/OR FINISH
PNT-04,
WB-03
PNT-04,
WB-03
PNT-04,
WB-03
PNT-04,
WB-03
PNT-04,
WB-03
WC-01
WB-03
WC-01
WB-03
WC-01
WB-03
WC-01
WB-03
WC-01
WB-03
PNT-05
WB-04
PNT-05
WB-04
PNT-05
WB-04
CPT-01 CPT-01 CPT-01 CPT-01 CPT-01
PNT-04,
WB-03
PNT-04,
WB-03
WC-01
WB-03
WC-01
WB-03
WC-01
WC-01
WB-03
WC-01
WC-01
WC-01
WB-03
PNT-04,
WB-03
PNT-04,
WB-03
PNT-04,
WB-03
PNT-04,
WB-03
PNT-04,
WB-03
PNT-04,
WB-03
PNT-04,
WB-03
WC-01
WB-03WC-01
WB-03
PNT-05,
WB-04
PNT-05,
WB-04
CPT-02CPT-02CPT-02
CPT-02
CPT-02
CPT-02
CPT-02
CPT-02
CPT-02
PNT-05,
WB-04
PNT-04
WB-03 WC-01 CPT-02
PNT-04
WB-03 WC-01 CPT-02
PNT-04
WB-03 WC-01 CPT-02
PNT-04
WB-03
PNT-04
WB-03
PNT-04
WB-03
PNT-04
WB-03
PNT-04
WB-03
WC-01
WC-01
WB-03
WC-01
WB-03
WC-01
WB-03
WC-01
PNT-05
WB-04
PNT-05,
WB-04
PNT-05,
WB-04
PNT-04
WB-03 WC-01
WC-01
WB-03
WC-01
WB-03
WC-01
WB-03
PNT-04
WB-03 WC-01
PNT-04
WB-03
PNT-04
WB-03
PNT-04
WB-03
CPT-02
CPT-02
CPT-02
CPT-02
CPT-02
WC-01
WB-03
PNT-04
WB-03
WC-01
WB-03
PNT-04
WB-03
WC-01
WB-03
PNT-04
WB-03
WC-01
PNT-04
WB-03
WC-01
PNT-04
WB-03
WC-01
WC-01
WB-03
PNT-04
WB-03
PNT-05,
WB-04
CPT-02CPT-02 CPT-02 CPT-02 CPT-02
PNT-05,
WB-04
CPT-02
PNT-04
WB-03 CPT-02
PNT-04
WB-03 CPT-02WC-01
WB-03
PNT-05,
WB-04
FLOOR FINISH LEGEND
CARPET TILE
Room name
101
F
B
W WALL FINISH
BASE FINISH
FLOOR FINISH
ROOM NUMBER
FINISH KEY
FINISH CODE; REFER TO
ELEVATIONS FOR ENTIRE
SCOPE.
REFER TO FINISH SCHEDULE
FOR BASIS OF DESIGN.
CPT-02
CPT-01
LUXURY VINYL TILERF-01CONCRETE
CONCRETE
PSC-01
SC-01
NOTE: INDICATES MAIN FIELD FINISH; ASSUME THIS
FINISH IN ENTIRE AREA UNLESS AN ACCENT IS CALLED
OUT IN PLANS OR ELEVATION
CARPET TILE
*MULTIPLE FINISHES;
SEE ELEVATION
TYP. ROOM FINISH TAG ACCENT TAG
XX
-
X
X
EX
T
E
N
T
O
F
F
I
N
I
S
H
SC
O
P
E
ENTRY MAT TILEEM-01 TL-01 PORCELAIN TILE
CPT-03 CARPET TILE
WDF-01 WOOD FLOOR
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
10/28/22
A147
Enlarged
Finish Plans
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
1/4" = 1'-0"E2
LEVEL 1 OPEN STUDY 122A NORTH BOOTHS - ENLARGED FINISH
PLAN
1/4" = 1'-0"D1 LEVEL 1 OPEN STUDY 122A EAST BOOTHS - ENLARGED FINISH PLAN
1/4" = 1'-0"E3 LEVEL 1 OPEN STUDY 118 BOOTHS- ENLARGED FINISH PLAN
1/4" = 1'-0"D4 LEVEL 2 OPEN STUDY 53 NORTH BOOTHS - ENLARGED FINISH PLAN
1/4" = 1'-0"C2 LEVEL 2 OPEN STUDY 53 SOUTH BOOTHS - ENLARGED FINISH PLAN
1/4" = 1'-0"C1 Level 03 QUIET OPEN STUDY 342 BOOTHS - ENLARGED FINISH PLAN
GENERAL NOTES - FINISH
1 SEE FLOOR PLANS FOR INTERIOR ELEVATIONS
2 ALL MATERIALS TO BE INSTALLED PER SPECIFIC MANUFACTURER'S INSTALLATION RECOMMENDATIONS
3 FLOORING MATERIAL TRANSITIONS TO OCCUR AT CENTERLINE OF DOOR THRESHOLDS, UNLESS NOTED OTHERWISE
4 PREPARE FLOORS/WALLS TO RECEIVE FINISH MATERIAL. REFER TO MANUFACTURER'S RECOMMENDATIONS FOR
SURFACE PREPARATION. NOTIFY ARCHITECT IF CONDITIONS ARE INADEQUATE FOR REQUIRED INSTALLATION
5 REFER TO ROOM FINISH LEGEND ON SHEET SERIES A600's FOR MORE INFORMATION
6 SEE DIMENSION PLAN SHEET SERIES A120's FOR WALL TYPE LOCATIONS; SEE SHEET SERIES A500's FOR WALL TYPE AND
ASSEMBLY DESCRIPTIONS
7 CONTRACTOR TO PROVIDE SOLID BLOCKING AT ALL CASEWORK, FIXED FURNISHINGS, AND EQUIPMENT. COORDINATE
WITH ELEVATIONS, SECTIONS, FURNITURE, FIXTURE SHEETS, AND SPECIFICATIONS
8 SEE SHEET SERIES A500's FOR TYPICAL DETAILS
9 TILE INSTALLER TO FOLLOW TCNA & ANSI GUIDELINES
10 ALL FLOORING MATERIALS ARE TO RUN WALL TO WALL AND BENEATH CASEWORK
11 VERIFY LOCATION OF POINT OR ORIGIN OF TILE AND CONTROL JOINTS ON SHOP DRAWINGS AND WITH ARCHITECT
ON-SITE PRIOR TO INSTALLATION
12 ALL GROUT TO BE SEALED
13 GENERAL CONTRACTOR TO COORDINATE POWER/DATA PLACEMENT WITH FURNITURE PROVIDER
14 LEVEL 5 FINISH REQUIRED FOR ALL WALL GRAPHIC AND WALLCOVERING LOCATIONS. SEE FINISH PLANS AND ELEVATIONS
FOR LOCATIONS
15 ALL METAL STUD WALLS TO DECK ABOVE, UNLESS NOTED OTHERWISE; SEE SHEET SERIES A500's FOR WALL TYPES
16 PROVIDE DEFLECTION TRACKS AT ALL STUD WALLS, SEE DETAILS ON SHEET SERIES A500's
17 ALL EXPOSED METAL TO BE INSTALLED PER SPECIFIC MANUFACTURER'S INSTALLATION RECOMMENDATIONS
18 CREATE A CLEAN, STRAIGHT TRANSITION LINE FROM POLISHED SEALED CONCRETE FLOORING TO SEALED CONCRETE
FLOORING UNDER DOORS. USE APPROPRIATE MEANS TO ACHIEVE A CLEAN TRANSITION
19 ALL GYP BOARD WALLS TO BE FINISHED. SEE FINISH PLAN ROOM TAGS FOR PAINT COLOR AND/OR FINISH
LEVEL 01
100' - 0"
LEVEL 02
114' - 0"
LEVEL 03
128' - 0"
G J L M N P QEC
LEVEL 00
87' - 0"
E6
A604
4'-0"
4'-0"
6'-0"
6'-0"
4'-0"
LEVEL 01
100' - 0"
LEVEL 02
114' - 0"
1
LEVEL 03
128' - 0"
16 15 14 13 12 11 10 9 8 7 2345
LEVEL 00
87' - 0"
TUTORING BRIDGE LIBRARY
6
2'-4 1/2"
2'-4 1/2"11'-0"
9'-10"
APPROXIMATE CEILING HEIGHT
10'-0"
2'-4 1/2"
2'-4 1/2"
4'-0"
4'-0"
6'-0"
4'-0"
4'-0"
6'-0"
37'-7 1/2"
LEVEL 01
100' - 0"
LEVEL 02
114' - 0"
LEVEL 03
128' - 0"
K H F D BGJLMNPQEC
10'-2 3/4"
4'-0"
6'-0"
4'-0"
8'-0"
ESTIMATED CEILING HEIGHT
10'-0"
4'-0"
2'-3 1/2"
2'-6 3/4"
LIBRARY
TUTORNING
LEVEL 01
100' - 0"
LEVEL 02
114' - 0"
1
LEVEL 03
128' - 0"
161514131211109872345
BRIDGE TUTORINGLIBRARY
6
A2
A513
E5
A604
37'-7 1/2"
6'-0"
4'-0"
4'-0"
9'-10"
11'-0"
2'-4 1/2"
2'-4 1/2"
2'-4 1/2"
2'-4 1/2"
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
10/28/22
A201
Exterior
Elevations
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
GENERAL NOTES - EXTERIOR ELEVATIONS
1 EXISTING EXTERIOR WINDOW HEIGHTS ARE DIMENSIONED TO HELP DETERMINE ROLLER SHADES COVERAGE. SEE RCP'S
FOR ROLLER SHADE LOCATIONS.
2 EXTERIOR ELEVATIONS ARE FOR REFERENCE AND CONTEXT. REFER TO FLOOR PLANS FOR FURTHER INFORMATION.
3 SEE CIVIL SHEETS FOR EXTERIOR RAILING TYPES
1/16" = 1'-0"C1 WEST ELEVATION
1/16" = 1'-0"D1 NORTH ELEVATION
1/16" = 1'-0"A1 TUTORING EAST ELEVATION
1/16" = 1'-0"B1 SOUTH ELEVATION
LEVEL 01
100' - 0"
LEVEL 02
114' - 0"
LEVEL 03
128' - 0"
G J L M N P QEC
LEVEL 00
87' - 0"
ROOF
142' - 0"
OPEN STUDY
122A
HD BOOK
COLLECTION
122
CIRCULATION
RECEPTION
110
SHEET MUSIC
236
ARCHIVE
228D
INSTRUCTION 2
224
DCAM
228B
SCANNER
228C
OPEN STUDY
220
JUVENILE
300
( QUIET )
OPEN STUDY
342
STUDY (LG)
326
OFFICE
114A
HALL
0-G
RESERVE MEDIA
116
ENTRY HALL
120A
OPEN STUDY
383
LEVEL 01
100' - 0"
LEVEL 02
114' - 0"
1
LEVEL 03
128' - 0"
16 15 14 13 12 11 10 9 8 7 2345
LEVEL 00
87' - 0"
ROOF
142' - 0"
6
STUDY (SM)
338
OFFICE
010
ELECTRICAL
ROOM
242
CONFERENCE
ROOM
140
STUDY (SM)
127
OPEN STUDY
122A
LARGE
COMPUTER
CLASSROOM
234
OPEN STUDY
53
VAULT
228E
DCAM
228B
DROP IN MATH
LAB
170
ENGLISH
TRANSITION
CENTER
288
OPEN TUTORING
CENTER
270
ADJUNCT
OFFICE
286
TR / COMM.
280
( QUIET )
OPEN STUDY
342
OPEN STUDY
362
PRE-FUNCTION
270C
PRE-FUNCTION
270D
PRE-FUNCTION
270E
PREFUNCTION
270F
OFFICE
012
SHORT TERM
STORAGE
028
OPS
022
STORAGE
352
MECH ROOM
030
IMAGING AND
STORAGE
009
OPEN STUDY
250
STOR
299
HALL
2-K
HALL
1-R
READING
150
HALL
1-V
LEVEL 01
100' - 0"
LEVEL 02
114' - 0"
LEVEL 03
128' - 0"
16151413121110987
DROP IN MATH
LAB
170
WORKSTATIONS/
FLEX SPACE
192
STUDY SKILLS
252
WRITING
CENTER OPEN
TUTORING
256
OPEN TUTORING
CENTER
270
STUDY
178
STUDY
179
STORAGE
192C
PREP /
STORAGE
252G
ELECTRICAL
173
HALL
1-Y
ELECTRICAL
2-I
LEVEL 01
100' - 0"
LEVEL 02
114' - 0"
LEVEL 03
128' - 0"
KHFDBA
CLASSROOM
164
OFFICE
192B
OFFICE
160B
TUTORING
ADMIN OPEN
AREA
160
OPEN TUTORING
254
WRITING
CENTER OPEN
TUTORING
256
OFFICE
256C
STORAGE
190C
STORAGE
192C
MECH
2-T
HALL
2-U
HALL
1-R
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
10/28/22
A301
Building
Sections
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
GENERAL NOTES - SECTIONS
1 SEE SHEET SERIES A500's FOR WALL AND ASSEMBLY TYPES
2 SEE SHEET SERIES A600's FOR DOOR AND WINDOW TYPES
1/16" = 1'-0"D3 Building Section (Grid 3)
1/16" = 1'-0"C1 Building Section (Grid G)
1/16" = 1'-0"B3 Building Section (Grid D)
1/16" = 1'-0"A4 Building Section (Grid 11)
A1
A311
10' - 0"
9' - 10"
TYPC3
A515
A3
A311
B2
A431
TYPA2
A561
TYPICAL
STUDY ROOM
A1 10' - 0"
STOREFRONT GLAZING
FINISH FLOOR AS SCHEDULED
TERMINATE STUD FRAMING AND GYP
BD AT BOTTOM OF WAFFLE SLAB
B2
A431
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
10/28/22
A311
Wall Sections
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
GENERAL NOTES - SECTIONS
1 SEE SHEET SERIES A500's FOR WALL AND ASSEMBLY TYPES
2 SEE SHEET SERIES A600's FOR DOOR AND WINDOW TYPES
1/4" = 1'-0"A3 AREA A EAST/WEST CEILING SECTION
1/4" = 1'-0"A1 AREA A NORTH/SOUTH CEILING SECTION
3/8" = 1'-0"B4 Mechanical Access Panel @ Booth Section
1/4" = 1'-0"B5 TYPICAL STUDY ROOM SECTION
F
F
A411D3
MOTHERS
243
FAMILY RR
244A411
D4
D5
C4
C5
D2
3' - 0"
22.17
12.03
D1
A581
______________
10.20
4' - 0"
8"
2' - 10"
3' - 0"
21 3/4"
10.06
A411
E2
E3
E4
E5
FAMILY RR
144
3' - 0"
10.15
E5
A571
TYP
144
7' - 2"
2' - 4"
E5
A571
TYP
09.01
09.12
D3
A571
______________
D3
A571
______________
10.03
7' - 2"
3' - 6"
2' - 10"
4"
3' - 6"
1' - 7 1/2"D1
A581
______________E5
A571
TYP
09.01
09.12
10.20
22.17
12.03
D3
A571
______________
10.06
3'-0"
B2
A431
7' - 2"
4' - 2"
E5
A571
TYP
09.01
09.12
10.10
D3
A571
______________
D3
A571
______________B2
A431
CASEWORK TAG
101M
AWS STANDARD CASEWORK TYPE
MODIFIED CASEWORK TYPE
REFER TO CASEWORK DESIGN SERIES (CDS) OF THE ARCHITECTURAL WOODWORK
STANDARDS (AWS) FOR A FULL DESCRIPTION OF CASEWORK TYPES
CASEWORK SYMBOL
INDICATES LOCKS REQUIRED
E5
A571
TYP
09.01
CL
3' - 0"
10.15
09.01
244
E5
A571
TYP
2' - 4"
7' - 2"
09.12
D3
A571
______________
D3
A571
______________
10.03
7' - 2"
1' - 6"
2' - 10"
4"
3' - 8"
09.01
22.17
12.03
09.12
10.10
E5
A571
TYP
3' - 6"
10.20
D3
A571
______________
22.14
D1
A581
______________
3' - 0"
7' - 2"
09.01
09.12
10.10
E5
A571
TYP
4' - 6"
D3
A571
______________
D3
A571
______________
A411 B2
B3
STORAGE
192C
24"
24"B4
A411
A5
A411B5 A411A4A2
A411
A3
SPECIAL
COLLECTIONS
RECEPTION
228b
MIR
A411
A3
6' - 5 1/8"
6' - 4 1/2"
08.15
30"
30"
8"
SF45
228 228
SF45
230 230
4"
FILLER
1"
12"50"12"
FILLER
1"
4"
12.04
06.07
09.13
06.06
B5
A582
30"
34"
06.06
38"
OPEN TO
BEYOND
A4
A582
SF44
36"
112 112
1 1/2"36"36"36"
FILLER
1"
112
12.01
06.07
63 3/8"
6 1/4"
14 3/8"
22"
16"
06.06
B5
A582
A6
A582
TYP
OPEN TO
BEYOND
30"
56"
30"
102 102 102
36"36"36"
06.06
12.01
1 1/2"
16 1/8"
3/4"
17 1/4"
3/4"
35 1/4"
3/4"
17 1/4"
3/4"
16 1/8"1 1/2"
B4
A581
100 100
06.07
36"
06.08
09.13
300 300
06.07
24"18"
24"18"
129 1/4"
24"
20"
20"
D4
A581
______________
1' - 6"
10.03
12.03
CL
3' - 0"
10.15
A411
C2
STORAGE
156D
C3
24"
D4
A581
______________
1' - 5"
1' - 5"
1' - 5"
1' - 5"
8' - 11 5/8"
11.01
17"
17"
17"
17"
24"
D4
A581
______________
20"
20"
24"
45 1/8"
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
10/28/22
A411
Enlarged
Plans &
Interior
Elevations
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
1/4" = 1'-0"D1 MOTHERS 243/ FAMILY RR 244- ENLARGED PLAN
1/4" = 1'-0"D3 MOTHERS 243- WEST
1/4" = 1'-0"E1 FAMILY RR 144- ENLARGED PLAN
1/4" = 1'-0"E2 FAMILY RR 144- NORTH
1/4" = 1'-0"E3 FAMILY RR 144- EAST
1/4" = 1'-0"E4 FAMILY RR 144- SOUTH
1/4" = 1'-0"E5 FAMILY RR 144- WEST
KEYED NOTES
06.06 WOOD VENEER, WV-01, RE: FINISH SCHEDULE
06.07 PLASTIC LAMINATE, PL-01, RE: FINISH SCHEDULE
06.08 PLASTIC LAMINATE, PL-02, RE: FINISH SCHEDULE
08.15 OPENING FOR GROMMET
09.01 PAINTED GYP, PNT-01, RE: FINISH SCHEDULE
09.12 TILE WALL, TL-02, RE: FINISH SCHEDULE
09.13 WALL BASE, WB-04, RE: FINISH SCHEDULE
10.03 WALL MOUNTED SOAP DISPENSER, OWNER FURNISHED, OWNER INSTALLED
10.06 PAPER TOWEL DISPENSER, OWNER FURNISHED, OWNER INSTALLED
10.10 32" GRAB BAR, STAINLESS STEEL; RE: ACCESSORY SCHEDULE;
10.15 FULLY RECESSED BABY CHANGING STATION, RE: ACCESSORY SCHEDULE
10.20 MIRROR, RE: ACCESSORY SCHEDULE
11.01 REFRIGERATOR; OFOI
12.01 QUARTZ COUNTER TOP, ST-01, RE: FINISH SCHEDULE
12.03 SOLID SURFACE COUNTER, SS-01, RE: FINISH SCHEDULE
12.04 QUARTZ COUNTER TOP, ST-02, RE: FINISH SCHEDULE
22.14 WALL HUNG WATER CLOSET, RE: PLUMBING
22.17 SINK, RE: PLUMBING
GENERAL NOTES - INT PLAN/ELEV
1 GENERAL CONTRACTOR SHALL FIELD VERIFY ALL CONDITIONS AND SHALL REPORT TO THE ARCHITECT ANY UNKNOWN
CONDITIONS, ERRORS, OR CONFLICTS IN THE DRAWINGS BEFORE BEGINNING WORK
2 DO NOT SCALE DRAWINGS
3 SEE SHEET GI003 FOR TYPICAL MOUNTING HEIGHTS. PROVIDE SOLID BLOCKING IN WALLS FOR ALL WALL-MOUNTED ITEMS
WHETHER BLOCKING IS DEPICTED IN DRAWINGS OR NOT.
4 UPPER, LOWER, AND TALL MILLWORK CABINETS NOT TO EXCEED 36" IN WIDTH
5 UNLESS NOTED OTHERWISE, MATCH UPPER CABINET WIDTH DIMENSIONS TO BASE
CABINETS - TYP.
6 ALL ELECTRICAL AND DATA OUTLETS ABOVE COUNTER TOPS SHOULD BE
MOUNTED HORIZONTALLY
7 PROVIDE SAFETY INSULATION ON ALL EXPOSED SUPPLY WATER LINES AND WASTE LINES
8 PROVIDE ALUMINUM EDGE MOULDING @ ALL TILE TO H.M. DOOR TRANSITIONS
9 PROVIDE METAL TRIM AT ALL OUTSIDE EDGES ON TILE WALLS. SEE: FINISH SCHEDULE
10 PROVIDE METAL TRIM AT ALL TILE TO FLOOR TRANSITIONS. SEE: FINISH SCHEDULE
11 ALL EXPOSED STEEL COLUMNS TO BE PAINTED TO MATCH ADJACENT WALL
12 ALL MILLWORK INTERIOR FINISH TO BE WHITE MELAMINE, UNLESS NOTED OTHERWISE
13 COUNTERTOP EDGE PROFILES TO BE SQUARE EDGE. IF SHOWN IN ELEVATION, PROVIDE 4" BACKSPLASH
14 ALL WOOD GRAIN TO RUN VERTICALLY, UNLESS NOTED OTHERWISE
15 CALLED OUT RESTROOM ACCESSORIES TO BE INSTALLED AT EVERY STALL
16 ALL SIGNAGE, LETTERING, GRAPHICS TO BE COORDINATED WITH OWNER PER CAMPUS GRAPHIC STANDARDS
17 PROVIDE MILLWORK LOCKS WITH CAMPUS STANDARD LOCKS WHERE INDICATED WITH LOCK SYMBOL AT MILLWORK ELEVATION
1/4" = 1'-0"D4 FAMILY RR 244 - NORTH
1/4" = 1'-0"D5 FAMILY RR 244 - EAST
1/4" = 1'-0"C4 FAMILY RR 244 - SOUTH
1/4" = 1'-0"C5 FAMILY RR 244 - WEST
1/4" = 1'-0"B1 STORAGE 192C ENLARGED FLOOR PLAN
1/4" = 1'-0"A1 SPECIAL COLLECTIONS RECEPTION
1/4" = 1'-0"A4 SPECIAL COLLECTONS 228 - EAST
1/4" = 1'-0"A3 S.C. 228 - S
1/4" = 1'-0"A5 SPECIAL COLLECTIONS 228 - S
1/4" = 1'-0"A2 SPECIAL COLLECTONS 228 - WEST
1/4" = 1'-0"B5 S. C. 228 - W
1/4" = 1'-0"B2 STORAGE 192C - EAST
1/4" = 1'-0"B3 STORAGE 192C - SOUTH
1/4" = 1'-0"D2 MOTHERS 243 - SOUTH
1/4" = 1'-0"C1 STORAGE 156D - ENLARGED PLAN
1/4" = 1'-0"C2 STORAGE 156D - NORTH
1/4" = 1'-0"C3 STORAGE 156D - EAST
1/4" = 1'-0"B4 STORAGE 192C - WEST
F
302302302
230
30"
20"
34"
30"36"30"1 5/8"
1 5/8"18"18"18"30"
06.07
06.09
12.04 OPEN TO
BEYOND
11.05
11.05
230230 D3
A581
______________A412
E2
E3
A412
E4
BREAK ROOM
CUBBIES
142b
BREAKROOM
142
18"
18"
MIR
A412
E4
34"
20"
30"
211 152
301 302 301
18"36"
18"36"12"
06.09
06.07
3"
18"
12.04
22.17
3"
10.03
10.06
A412 B3
C1
C2
A412B4
B2
A412
C3
TUTORING
ADMIN OPEN
AREA
160
29"
33"
25 1/2"
29"
08.15
TYP.4
230
1 1/2"
15"
06.06
06.07
30"
8"
OPEN TO
BEYOND
09.13
12.04
A3
A582
B5
A582
A4
A582
30"
8"
230 230
15"79"7 1/2"88 1/2"15"
30"
8"
FILLER
1"
4"63 3/4"4"
FILLER
1"
OPEN TO
BEYOND 12.01
06.07
06.06
09.13
TYP
TYP
TYP
TYP. 2
B5
A582
OPEN TO
BEYOND
101
61 5/8"24"
1 1/2"
12.01
06.07
09.13
30"
A4
A582
06.06
OPEN TO
BEYOND
59 1/2"60 5/8"
30"
8"
12.04
B5
A582
A3
A582
A5
A582
TYP
6 1/4"
9"
A412 A3
A2
A412
B5
A412A5
OPEN STUDY
383
MIR
A412
B5
MIR
A412 A5
MIR
A412A4
MIR
A412
A2
A3
A4
3' - 3"
4' - 4 1/16"
2' - 2 1/8"
28 1/2"
83"
28 1/2"
28 1/2"
28 1/2"
08.15
TYP.2
230
12"
FILLER
1"
4"
30"
8"
OPEN TO
BEYOND
8"
14"
12"
12.04
06.07
09.13
06.06
B5
A582
A4
A582
09.23 211
4"
FILLER
1"
24"
30"
OPEN TO
BEYOND
22"
12"
4"
06.07
06.06
09.13
A3
A582
A4
A582
09.23
84"
13 1/2"48"48"
420 420
06.07
TYP
15 1/4"
TYP
15 1/4"
400
160A 160B
09.11
10"
14"
10.30 3"
8'-8"
22'-10 1/2"
CASEWORK TAG
101M
AWS STANDARD CASEWORK TYPE
MODIFIED CASEWORK TYPE
REFER TO CASEWORK DESIGN SERIES (CDS) OF THE ARCHITECTURAL WOODWORK
STANDARDS (AWS) FOR A FULL DESCRIPTION OF CASEWORK TYPES
CASEWORK SYMBOL
INDICATES LOCKS REQUIRED
211
30"
4"
FILLER
1"
24"
OPEN TO
BEYOND
06.07
12.04
09.13 A3
A582
OPEN TO
BEYOND
22
"
16
"
06.06
12 1/2"
6"
97 1/2"12 1/2"
6"
80 1/2"63 3/4"
TYP
B5
A582
B5
A582
A5
A582
TYP
A5
A582
TYP
OPEN TO
BEYOND
38"
22"
16"
63 3/4"
6 1/4"
13"
06.06
B5
A582
A6
A582
TYP09.23
10.24
30"
8"
OPEN TO
BEYOND
13 3/8"
6 1/4"
46"39"32 1/2"
12.04
TYP
A6
A582
TYP
A3
A582
SIM
A416A5
SIM
A416A5
SIM
A416A5
SIM
A416A5
A5 A5 A5 A5
STUDY
288G
STUDY
288F
STUDY
288E
STUDY
288D
A412D3
D2 MAC EQUIP
324A
400222222222
84"
34"
5"33"30"33"
06.08
06.07
09.13
10.33 06.07
222222
34
"
FILLER
1"
36"36"
FILLER
2 1/8"
06.08
06.07
09.13
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
10/28/22
A412
Enlarged
Plans &
Interior
Elevations
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
1/4" = 1'-0"E2 BREAKROOM 142- NORTH
1/4" = 1'-0"D1 BREAKROOM 142 - ENLARGED PLAN
1/4" = 1'-0"E3 BREAKROOM 142- WEST
1/4" = 1'-0"B1 TUTORING ADMIN OPEN AREA 160 - ENLARGED PLAN
1/4" = 1'-0"B3 TUTORING ADMIN 160 DESK INT. - EAST
1/4" = 1'-0"C1 TUTORING ADMIN 160 DESK INT. - SOUTH
1/4" = 1'-0"C2 TUTORING ADMIN 160 DESK INT. - WEST
1/4" = 1'-0"B4 TUTORING ADMIN 160 DESK EXT - WEST 2
1/4" = 1'-0"A1 LEVEL 3 CIRC DESK- ENLARGED PLAN
1/4" = 1'-0"A3 LEVEL 3 CIRC DESK INT. - EAST/WEST
1/4" = 1'-0"A4 LEVEL 3 CIRC DESK EXT. - NORTH/WEST
1/4" = 1'-0"E4 TYPICAL BREAKROOM CUBBIES 142b - NORTH/SOUTH
1/4" = 1'-0"B2 TUTORING ADMIN OPEN AREA 160- NORTH
KEYED NOTES
06.06 WOOD VENEER, WV-01, RE: FINISH SCHEDULE
06.07 PLASTIC LAMINATE, PL-01, RE: FINISH SCHEDULE
06.08 PLASTIC LAMINATE, PL-02, RE: FINISH SCHEDULE
06.09 PLASTIC LAMINATE, PL-03, RE: FINISH SCHEDULE
08.15 OPENING FOR GROMMET
09.11 HATCH PATTERN INDICATES EXTENT OF FULL COLOR VINYL WALL GRAPHIC, SEE SIGN SCHEDULE, PREP WALL
WITH LEVEL 5 FINISH PRIOR TO INSTALLING VINYL
09.13 WALL BASE, WB-04, RE: FINISH SCHEDULE
09.23 WALL BASE, WB-08, RE: FINISH SCHEDULE
10.03 WALL MOUNTED SOAP DISPENSER, OWNER FURNISHED, OWNER INSTALLED
10.06 PAPER TOWEL DISPENSER, OWNER FURNISHED, OWNER INSTALLED
10.24 SIGNAGE, SEE SIGNAGE SCHEDULE
10.30 SIGNAGE, SEE SIGNAGE SCHEDULE
10.33 MARKER BOARD, 4'x 4', OFOI
11.05 MICROWAVE, OFOI
12.01 QUARTZ COUNTER TOP, ST-01, RE: FINISH SCHEDULE
12.04 QUARTZ COUNTER TOP, ST-02, RE: FINISH SCHEDULE
22.17 SINK, RE: PLUMBING
GENERAL NOTES - INT PLAN/ELEV
1 GENERAL CONTRACTOR SHALL FIELD VERIFY ALL CONDITIONS AND SHALL REPORT TO THE ARCHITECT ANY UNKNOWN
CONDITIONS, ERRORS, OR CONFLICTS IN THE DRAWINGS BEFORE BEGINNING WORK
2 DO NOT SCALE DRAWINGS
3 SEE SHEET GI003 FOR TYPICAL MOUNTING HEIGHTS. PROVIDE SOLID BLOCKING IN WALLS FOR ALL WALL-MOUNTED ITEMS
WHETHER BLOCKING IS DEPICTED IN DRAWINGS OR NOT.
4 UPPER, LOWER, AND TALL MILLWORK CABINETS NOT TO EXCEED 36" IN WIDTH
5 UNLESS NOTED OTHERWISE, MATCH UPPER CABINET WIDTH DIMENSIONS TO BASE
CABINETS - TYP.
6 ALL ELECTRICAL AND DATA OUTLETS ABOVE COUNTER TOPS SHOULD BE
MOUNTED HORIZONTALLY
7 PROVIDE SAFETY INSULATION ON ALL EXPOSED SUPPLY WATER LINES AND WASTE LINES
8 PROVIDE ALUMINUM EDGE MOULDING @ ALL TILE TO H.M. DOOR TRANSITIONS
9 PROVIDE METAL TRIM AT ALL OUTSIDE EDGES ON TILE WALLS. SEE: FINISH SCHEDULE
10 PROVIDE METAL TRIM AT ALL TILE TO FLOOR TRANSITIONS. SEE: FINISH SCHEDULE
11 ALL EXPOSED STEEL COLUMNS TO BE PAINTED TO MATCH ADJACENT WALL
12 ALL MILLWORK INTERIOR FINISH TO BE WHITE MELAMINE, UNLESS NOTED OTHERWISE
13 COUNTERTOP EDGE PROFILES TO BE SQUARE EDGE. IF SHOWN IN ELEVATION, PROVIDE 4" BACKSPLASH
14 ALL WOOD GRAIN TO RUN VERTICALLY, UNLESS NOTED OTHERWISE
15 CALLED OUT RESTROOM ACCESSORIES TO BE INSTALLED AT EVERY STALL
16 ALL SIGNAGE, LETTERING, GRAPHICS TO BE COORDINATED WITH OWNER PER CAMPUS GRAPHIC STANDARDS
17 PROVIDE MILLWORK LOCKS WITH CAMPUS STANDARD LOCKS WHERE INDICATED WITH LOCK SYMBOL AT MILLWORK ELEVATION
1/4" = 1'-0"A2 LEVEL 3 CIRC DESK INT. - NORTH/SOUTH
1/4" = 1'-0"C3 TUTORING ADMIN OPEN AREA 160 - NORTH
1/4" = 1'-0"A5 LEVEL 3 CIRC DESK EXT. - EAST/WEST
1/4" = 1'-0"B5 LEVEL 3 CIRC DESK EXT. - N/S
1/4" = 1'-0"D4 STUDY ROOMS 288D-G ENLARGED FLOOR PLAN
1/4" = 1'-0"C5 MAC EQUIP 324A - ENLARGED PLAN
1/4" = 1'-0"D2 MAC EQUIP 324A - NORTH
1/4" = 1'-0"D3 MAC EQUIP 324A - WEST
F
F
A413
E3
A413 E4
A413
C5
D3
D4
D5A413
C3
B5
A413
B3
B2B4
B1
FAMILY STUDY
344
KIDS PLAY
344C
MOTHERS
ROOM
344A
C4
22.18
344B 344A
OPEN TO
BEYOND
IN BACKGROUND
2' - 8"
4' - 0 5/8"
7' - 0"
22.18
09.12
3' - 6"
D3
A571
______________
D3
A571
______________
D3
A571
______________
CL
09.07
E5
A571
TYP
344
SF91
10.24
4 1/2"
09.04
09.09 223223
15"28 1/2"15"
06.09
06.07
11.10
10.43
6'-10"
11'-6"
2'-4"
5'-10"
OPEN TO
BEYOND
3' - 6"
09.22
10.24
COORDINATE WITH WALL GRAPHIC
OPEN TO
BEYOND
1'-6"
1'-11 1/4"
1'-9"
10.40
CASEWORK TAG
101M
AWS STANDARD CASEWORK TYPE
MODIFIED CASEWORK TYPE
REFER TO CASEWORK DESIGN SERIES (CDS) OF THE ARCHITECTURAL WOODWORK
STANDARDS (AWS) FOR A FULL DESCRIPTION OF CASEWORK TYPES
CASEWORK SYMBOL
INDICATES LOCKS REQUIRED
4"
3' - 6"
3' - 0"
22.17
12.03
D1
A581
______________
10.20
10.15
IN FOREGROUND
CL3' - 0"
7' - 0"
4' - 6"
09.12
10.10
09.01
E5
A571
TYP
D3
A571
______________
D3
A571
______________
344B
E5
A571
TYP
CL 2' - 1"
10.15
7' - 0"
3' - 0"
09.01
09.12
10.06
CL3' - 0"
E5
A571
TYP
D3
A571
______________
D3
A571
______________
7' - 0"
2' - 10"
4"
3' - 6"
09.01
09.12
10.20
22.17
12.03
E5
A571
TYP
3' - 4"
D1
A581
______________
1' - 6"
10.03
10.06
CL4' - 6"
A413
A4
A413
A3
HALL
1-X
STUDY
178
STUDY
179
HALL
1-Y
4' - 8"
4' - 8"
7' - 2"
EQ EQ
09.12
OPEN TO
BEYOND
22.20
8' - 8"
179 178
09.04
09.09
IN FOREGROUND
SF24A SF24B
JANITOR'S
CLOSET
249
A413 C2
5'-0"
3'-0"
1'-7"
4'-0"
06.16 10.41
22.11
22.22
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
10/28/22
A413
Enlarged
Plans &
Interior
Elevations
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
1/4" = 1'-0"D1 FAMILY STUDY 344- ENLARGED PLAN
1/4" = 1'-0"E3 FAMILY STUDY 344 - SOUTH
1/4" = 1'-0"E4 EXT FAMILY STUDY 344 - EAST
1/4" = 1'-0"C5 KIDS PLAY 344B- NORTH
1/4" = 1'-0"D3 KIDS PLAY 344B- EAST
1/4" = 1'-0"D4 KIDS PLAY 344B- SOUTH
1/4" = 1'-0"D5 KIDS PLAY 344B- WEST
KEYED NOTES
06.07 PLASTIC LAMINATE, PL-01, RE: FINISH SCHEDULE
06.09 PLASTIC LAMINATE, PL-03, RE: FINISH SCHEDULE
06.16 FIBRE-REINFORCED PLASTIC, FRP-01, RE: FINISH SCHEDULE
09.01 PAINTED GYP, PNT-01, RE: FINISH SCHEDULE
09.04 PAINTED GYP, PNT-04, RE: FINISH SCHEDULE
09.07 TILE WALL BASE, WB-02, RE: FINISH SCHEDULE
09.09 WALL BASE, WB-03, RE: FINISH SCHEDULE
09.12 TILE WALL, TL-02, RE: FINISH SCHEDULE
09.22 WALLCOVERING, WC-03, RE: FINISH SCHEDULE
10.03 WALL MOUNTED SOAP DISPENSER, OWNER FURNISHED, OWNER INSTALLED
10.06 PAPER TOWEL DISPENSER, OWNER FURNISHED, OWNER INSTALLED
10.10 32" GRAB BAR, STAINLESS STEEL; RE: ACCESSORY SCHEDULE;
10.15 FULLY RECESSED BABY CHANGING STATION, RE: ACCESSORY SCHEDULE
10.20 MIRROR, RE: ACCESSORY SCHEDULE
10.24 SIGNAGE, SEE SIGNAGE SCHEDULE
10.40 ACTIVITY WALL PANEL, RE: ACCESSORY SCHEDULE
10.41 MOP/BROOM HOLDER, OFOI
10.43 HATCH INDICATES EXTENT OF FULL COLOR WINDOW VINYL GRAPHIC, SEE SIGNAGE SCHEDULE
11.10 PRINTER, OFOI, RE: ACCESSORY SCHEDULE; POWER AND DATAT TO BE PROVIDED, RE:ELECTRICAL
12.03 SOLID SURFACE COUNTER, SS-01, RE: FINISH SCHEDULE
22.11 MOP SINK, RE: PLUMBING
22.17 SINK, RE: PLUMBING
22.18 DRINKING FOUNTAINS DESIGNED SPECIFICALLY FOR CHILDREN SPOUT 30 INCHES HIGH MAX A.F.F. RE: PLUMBING
22.20 DRINKING FOUNTAIN TYPE VARIES, RE: FLOOR PLAN FOR TYPES, RE: PLUMBING
22.22 CHEMICAL STATION, RE: PLUMBING
GENERAL NOTES - INT PLAN/ELEV
1 GENERAL CONTRACTOR SHALL FIELD VERIFY ALL CONDITIONS AND SHALL REPORT TO THE ARCHITECT ANY UNKNOWN
CONDITIONS, ERRORS, OR CONFLICTS IN THE DRAWINGS BEFORE BEGINNING WORK
2 DO NOT SCALE DRAWINGS
3 SEE SHEET GI003 FOR TYPICAL MOUNTING HEIGHTS. PROVIDE SOLID BLOCKING IN WALLS FOR ALL WALL-MOUNTED ITEMS
WHETHER BLOCKING IS DEPICTED IN DRAWINGS OR NOT.
4 UPPER, LOWER, AND TALL MILLWORK CABINETS NOT TO EXCEED 36" IN WIDTH
5 UNLESS NOTED OTHERWISE, MATCH UPPER CABINET WIDTH DIMENSIONS TO BASE
CABINETS - TYP.
6 ALL ELECTRICAL AND DATA OUTLETS ABOVE COUNTER TOPS SHOULD BE
MOUNTED HORIZONTALLY
7 PROVIDE SAFETY INSULATION ON ALL EXPOSED SUPPLY WATER LINES AND WASTE LINES
8 PROVIDE ALUMINUM EDGE MOULDING @ ALL TILE TO H.M. DOOR TRANSITIONS
9 PROVIDE METAL TRIM AT ALL OUTSIDE EDGES ON TILE WALLS. SEE: FINISH SCHEDULE
10 PROVIDE METAL TRIM AT ALL TILE TO FLOOR TRANSITIONS. SEE: FINISH SCHEDULE
11 ALL EXPOSED STEEL COLUMNS TO BE PAINTED TO MATCH ADJACENT WALL
12 ALL MILLWORK INTERIOR FINISH TO BE WHITE MELAMINE, UNLESS NOTED OTHERWISE
13 COUNTERTOP EDGE PROFILES TO BE SQUARE EDGE. IF SHOWN IN ELEVATION, PROVIDE 4" BACKSPLASH
14 ALL WOOD GRAIN TO RUN VERTICALLY, UNLESS NOTED OTHERWISE
15 CALLED OUT RESTROOM ACCESSORIES TO BE INSTALLED AT EVERY STALL
16 ALL SIGNAGE, LETTERING, GRAPHICS TO BE COORDINATED WITH OWNER PER CAMPUS GRAPHIC STANDARDS
17 PROVIDE MILLWORK LOCKS WITH CAMPUS STANDARD LOCKS WHERE INDICATED WITH LOCK SYMBOL AT MILLWORK ELEVATION
1/4" = 1'-0"C3 MOTHER'S ROOM 344A - SOUTH
1/4" = 1'-0"B5 MOTHER'S ROOM 344A - EAST
1/4" = 1'-0"B4 RESTROOM 344B - WEST
1/4" = 1'-0"B1 RESTROOM 344B - NORTH
1/4" = 1'-0"B2 RESTROOM 344B - EAST
1/4" = 1'-0"B3 RESTROOM 344B - SOUTH
1/4" = 1'-0"C4 MOTHER'S ROOM 344A - WEST
1/4" = 1'-0"A1 Level 01 Area B Floor Plan - Callout 2
1/4" = 1'-0"A3 DRINKING FOUNTAIN
1/4" = 1'-0"A4 STUDY ROOM 178/179 - SOUTH
1/4" = 1'-0"C1 LEVEL 2 JANITOR'S CLOSET 249 ENLARGED PLAN
1/4" = 1'-0"C2 JANITOR'S CLOSET 249 - EAST
A414
E3
A414
D3
D4
A414 C1
A414
C5
A414
E2
D2
A414
C3
C2C4
I.T. HELP DESK
176
STUDENT PREP
174
HALL
1-V
MATH LAB
RECEPTION
175
3' - 10 5/8"A414
E5
33"
28"
33"
08.15
TYP.3
2'-1 1/4"
15"
FILLER
1"
4"
8"
30
"
OPEN TO
BEYOND
06.07
06.06
230
09.13
12.04
B5
A582
OPEN TO
BEYOND
4"
FILLER
1"
15"53 7/8"
12.01
06.07
30"
230
38"
09.13
A3
A582
OPEN TO
BEYOND
OPEN TO
BEYOND
8"
30"
06.06
230 230
117 7/8"15"15"71"
06.07
09.13
FILLER
1 1/2"
FILLER
1 1/2"
12.04
TYP
TYP
TYP
TYP
B5
A582
A4
A582
A4
A582
OPEN TO
BEYOND
OPEN TO
BEYOND
06.06
22"
12"
4"
6"28 1/16"24 1/2"6 5/8"
A5
A582
TYP A5
A582
TYP
B5
A582
OPEN TO
BEYOND
06.06
1' - 10"
1' - 0"
4"
30"
80 1/8"
12.04
A5
A582
TYP
A3
A582
A414
A4
A414B5
A414 B2
A414
B1
A3
A2
A5
B3 PREP /
STORAGE
270B
RECEPTION
270A
14"
18"
14"
36"
ALIGN
B4
30"
30"
08.15
TYP.2
PREP
2U
SIM
A414
C5
14"
36"
19"
17"
D4
A581
______________
100100
33"36"1 5/8"
06.08
06.07
09.13
14"
30"81 5/8"15"
FILLER
1 1/2"
8"
30"
OPEN TO
BEYOND
06.07
09.13
TYP
230
TYP
12.04
06.06
B5
A582
A4
A582
OPEN TO
BEYOND
38"
06.06
102 1/8"6"20"
B5
A582
A5
A582
TYP
OPEN TO
BEYOND
8"
30"
06.06
A3
A582
12.04
72"
CASEWORK TAG
101M
AWS STANDARD CASEWORK TYPE
MODIFIED CASEWORK TYPE
REFER TO CASEWORK DESIGN SERIES (CDS) OF THE ARCHITECTURAL WOODWORK
STANDARDS (AWS) FOR A FULL DESCRIPTION OF CASEWORK TYPES
CASEWORK SYMBOL
INDICATES LOCKS REQUIRED
20"
30"
20"
34"
100M 100M100
BEHIND WALL
24"30"24"
BEHIND WALL
300M300300M
FILLER 24"30"24"FILLER
22.17
12.03
06.07
06.07
10.06
10.08
174
OPEN TO
BEYOND
09.11
09.11
10"
10.30
3"
10"
3"10.30
42"
87 1/2"
D5
A581
TYP
8'-8"
12'-7 3/4"8'-6"
OPEN TO
BEYOND 06.06
38"
19"
6 1/2"
66 1/2"
101101
76 3/4"30"30"
42"
12.04
06.07
09.13
D5
A581
TYP
TYP
12.01
A5
A582
TYP
A3
A582
09.23
21"
17"
17"
17"
D4
A581
______________
72 1/4"14"
174
400 400 400
18"18"18"
06.07
84"
15 1/4"
16 1/2"
17"
17"
17"
21"
D4
A581
______________
75 1/2"24"
50"18"18"18"18"
400 400 400 400
84"
06.07
15 1/4"
16 1/2"09.13
14"
17"
19"
36"
24 3/4"36"36"
36"
19"
17"
D4
A581
______________
100100100
06.08
06.07
09.13
270B OPEN TO
BEYOND
09.11
5'-4 1/2"
CL
CLEQ EQ
10.29
10"
3"
8'-8"
11'-3 1/2"
10.24
270B17"
54"
14"
D4
A581
______________
5'-0"
4"
3/4"
A3
A582
OPEN TO
BEYOND
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
10/28/22
A414
Enlarged
Plans &
Interior
Elevations
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
1/4" = 1'-0"D1 I.T. HELP DESK 176 AND MATH LAB RECEPTION. 175- ENLARGED PLAN
1/4" = 1'-0"E3 I.T. HELP DESK 176 INT. - NORTH
1/4" = 1'-0"D3 MATH LAB 175 RECEPTION DESK EXT. - SOUTH
1/4" = 1'-0"D4 MATH LAB 175, IT HELP DESK RECEPTION DESK INT. - WEST
1/4" = 1'-0"C1 MATH LAB 175 RECPECTION DESK EXT. - EAST
1/4" = 1'-0"E5 MATH LAB RECPECTION. 175- NORTH
1/4" = 1'-0"A1 RECEPTION 270A AND STORAGE 270B - ENLARGED PLAN
1/4" = 1'-0"A4 STORAGE 270B- SOUTH
1/4" = 1'-0"B5 RECEPTION DESK INT. 270A - WEST
1/4" = 1'-0"B2 RECEPTION 270A- EAST
1/4" = 1'-0"B1 RECEPTION 270A- NORTH
KEYED NOTES
06.06 WOOD VENEER, WV-01, RE: FINISH SCHEDULE
06.07 PLASTIC LAMINATE, PL-01, RE: FINISH SCHEDULE
06.08 PLASTIC LAMINATE, PL-02, RE: FINISH SCHEDULE
08.15 OPENING FOR GROMMET
09.11 HATCH PATTERN INDICATES EXTENT OF FULL COLOR VINYL WALL GRAPHIC, SEE SIGN SCHEDULE, PREP WALL
WITH LEVEL 5 FINISH PRIOR TO INSTALLING VINYL
09.13 WALL BASE, WB-04, RE: FINISH SCHEDULE
09.23 WALL BASE, WB-08, RE: FINISH SCHEDULE
10.06 PAPER TOWEL DISPENSER, OWNER FURNISHED, OWNER INSTALLED
10.08 42" GRAB BAR, STAINLESS STEEL; RE: ACCESSORY SCHEDULE;
10.24 SIGNAGE, SEE SIGNAGE SCHEDULE
10.29 TV, CONTRACTOR TO PROVIDE 3/4" SHEATHING FOR THE ENTIRE WALL, OFOI
10.30 SIGNAGE, SEE SIGNAGE SCHEDULE
12.01 QUARTZ COUNTER TOP, ST-01, RE: FINISH SCHEDULE
12.03 SOLID SURFACE COUNTER, SS-01, RE: FINISH SCHEDULE
12.04 QUARTZ COUNTER TOP, ST-02, RE: FINISH SCHEDULE
22.17 SINK, RE: PLUMBING
GENERAL NOTES - INT PLAN/ELEV
1 GENERAL CONTRACTOR SHALL FIELD VERIFY ALL CONDITIONS AND SHALL REPORT TO THE ARCHITECT ANY UNKNOWN
CONDITIONS, ERRORS, OR CONFLICTS IN THE DRAWINGS BEFORE BEGINNING WORK
2 DO NOT SCALE DRAWINGS
3 SEE SHEET GI003 FOR TYPICAL MOUNTING HEIGHTS. PROVIDE SOLID BLOCKING IN WALLS FOR ALL WALL-MOUNTED ITEMS
WHETHER BLOCKING IS DEPICTED IN DRAWINGS OR NOT.
4 UPPER, LOWER, AND TALL MILLWORK CABINETS NOT TO EXCEED 36" IN WIDTH
5 UNLESS NOTED OTHERWISE, MATCH UPPER CABINET WIDTH DIMENSIONS TO BASE
CABINETS - TYP.
6 ALL ELECTRICAL AND DATA OUTLETS ABOVE COUNTER TOPS SHOULD BE
MOUNTED HORIZONTALLY
7 PROVIDE SAFETY INSULATION ON ALL EXPOSED SUPPLY WATER LINES AND WASTE LINES
8 PROVIDE ALUMINUM EDGE MOULDING @ ALL TILE TO H.M. DOOR TRANSITIONS
9 PROVIDE METAL TRIM AT ALL OUTSIDE EDGES ON TILE WALLS. SEE: FINISH SCHEDULE
10 PROVIDE METAL TRIM AT ALL TILE TO FLOOR TRANSITIONS. SEE: FINISH SCHEDULE
11 ALL EXPOSED STEEL COLUMNS TO BE PAINTED TO MATCH ADJACENT WALL
12 ALL MILLWORK INTERIOR FINISH TO BE WHITE MELAMINE, UNLESS NOTED OTHERWISE
13 COUNTERTOP EDGE PROFILES TO BE SQUARE EDGE. IF SHOWN IN ELEVATION, PROVIDE 4" BACKSPLASH
14 ALL WOOD GRAIN TO RUN VERTICALLY, UNLESS NOTED OTHERWISE
15 CALLED OUT RESTROOM ACCESSORIES TO BE INSTALLED AT EVERY STALL
16 ALL SIGNAGE, LETTERING, GRAPHICS TO BE COORDINATED WITH OWNER PER CAMPUS GRAPHIC STANDARDS
17 PROVIDE MILLWORK LOCKS WITH CAMPUS STANDARD LOCKS WHERE INDICATED WITH LOCK SYMBOL AT MILLWORK ELEVATION
1/4" = 1'-0"C5 HALL 1-V CLOSET/PREP 2U - NORTH
1/4" = 1'-0"D2 MATH LAB RECPECTION 175 INT. - EAST
1/4" = 1'-0"E2 I.T. HELP DESK 176 EXT. - SOUTH
1/4" = 1'-0"C3 STUDENT PREP 174 - SOUTH
1/4" = 1'-0"C4 STUDENT PREP 174 - WEST
1/4" = 1'-0"C2 STUDENT PREP 174 - EAST
1/4" = 1'-0"A2 STORAGE 270B - NORTH
1/4" = 1'-0"A3 STORAGE 270B - EAST
1/4" = 1'-0"B3 RECEPTION 270 A - EAST
1/4" = 1'-0"A5 STORAGE 270B - WEST
1/4" = 1'-0"B4 RECEPTION 270A - INT. SOUTH
F
C1
CASEWORK TAG
101M
AWS STANDARD CASEWORK TYPE
MODIFIED CASEWORK TYPE
REFER TO CASEWORK DESIGN SERIES (CDS) OF THE ARCHITECTURAL WOODWORK
STANDARDS (AWS) FOR A FULL DESCRIPTION OF CASEWORK TYPES
CASEWORK SYMBOL
INDICATES LOCKS REQUIRED
A415
C1
A415
D4
A415
A3
B5 A5
B3
A415
C4
CIRCULATION
RECEPTION
110
INTER LIBRARY
LOAN
WORKSPACE
114
A415C3A415C2
3' - 6 7/8"
1'-1 1/2"1'-6 1/2"
A571
A5
RECESSED OPENING ELEVATION
08.15
08.15
1'-1 3/4"
2'-11 3/4"
2'-6 1/2"
3'-10 1/2"4'-3"
OPEN TO
BEYOND
09.01
06.06
12.01
101 3/4"144"101 3/4"
40"
C3
A582
C1
A582
TYP
30"
09.19
OPEN TO
BEYOND
230230M110110100230M
39 1/2"15"24"53 1/4"36"24"24"53 3/4"18"24"36"
10"
30"
09.01
06.06
09.19
12.01
06.06
TYP.
06.07
100
09.13
14"
C3
A582
C1
A582
TYP
A1
A582
34"
A1
A582
TYP.
EQ EQ
OPEN TO
BEYOND
OPEN TO
BEYOND
REFERENCE LINE
CEILING CLOUD
24"
3/4"
5 1/2"
3/4"
33 3/4"
3/4"
18"
3/4"
3"65 1/2"3"
3/4"
18"
3/4"
33 3/4"
3/4"
5 1/2"
3/4"
24"
4"3/4"
32"
3/4"
48"
3/4"
33 3/4"
3"
5 1/2"
3"
5 1/2"
10.24
06.06
08.10
08.11
08.10
08.1008.10
08.11
08.1108.11
2'-0 1/2"
B2
A571
TYP
24 3/4"
5 1/2"
35 1/4"18"
3/4"3"
65 1/2"
A1
A571
______________
NOTE: SEE SOUTH RECEPTION WALL RECESSED
OPENING ELEVATION DETAIL ON A5/A571
EQEQ
TYP. 6
OPEN TO
BEYOND
12"2 1/4"
10"
30"
230
09.01
06.06
12.01
06.07
09.13
B3
A582 B1
A582
OPEN TO
BEYOND
06.06
12.01
100
2 1/2"53 1/8"30"
6"
34"
06.07
09.13
C5
A582
TYP
EQ EQ
402 212 212
36"36"36"
36"36"
30"
20"
34"
302302
06.07
06.08
06.07
84"
TYP
OPEN TO
BEYOND
09.04
TYP
4"
32 3/4"
3/4"
48"
3/4"
33 3/4"
18 21/32"
3/4"
9"
3/4"41"3/4"48 13/16"3/4"41"3/4"
9"
3/4"
18 17/32"
4"
32 3/4"
3/4"
48"
3/4"
33 3/4"
18 17/32"
3/4"
9"
3/4"41"3/4"71 1/2"3/4"41"3/4"
9"
3/4"
18 17/32"
5 1/2"3/4"
09.17
TYP
D5
A571
TYP
D5
A571
TYP D5
A571
TYP
D5
A571
TYP
D6
A571
TYP
D6
A571
TYP
OPEN TO
BEYOND
09.01
06.06
12.01
09.19
06.06
40"
34"85 5/8"
C1
A571
TYP
34"
B2
A571
TYP
C5
A582
TYP
10.24
18"8 1/2"18"6 3/4"
08.09
OPEN TO
BEYOND
09.01
06.06
09.19
12.01
06.06
30"
13 5/8"72"34"
40"
C1
A571
TYP
B2
A571
TYP B3
A582
B1
A582
A415
E2
SIM
A415E2
SIM
A415
E2
SIM
A415 E2
TYP. TYP.
SB3.1SA4.1
6'-1 1/4"
6'-1 1/4"
3'-0 3/4"3'-0 3/4"
3'-0 3/4"
3'-0 3/4"
TYP
TYP
TYP
D5
A581
TYP
30"
24"44 3/8"
09.15
09.01
06.08
A415 D2
D3
A415
INTEGRAL BOOK DROP ASSEMBLY
MODEL -"AMERICAN BOOK RETURNS - HCU FOR BOOKS"
STOREFRONT, SEE WINDOW TYPES
BOOK DROP BOX BY OWNER
1-F.1
A415
E5
E4
SIM
A415
E4
SIM
A415E4SIM
A415
E4
E5 E5
E5
3'-10 1/2"3'-10 1/2"
3'-10 1/2"
3'-10 1/2"
7'-9"
7'-9"
SA4.1
SB2.1
TYP.
TYP.
OPEN TO
BEYOND
09.10
09.15
OPEN TO
BEYOND
09.10
09.15
D3
A415
3'-0"
1'-2"
3'-0"
1'-10"
EQ
R.O.
1'-5"EQ
R.O.
1'-0"
STAINLESS STEEL COVER PLATE
EDGES TO ALIGN WITH EDGES
OF STOREFRONT FRAMING
D6
A551
BOOK DROP
BOX
INTEGRAL BOOK DROP ASSEMBLY
MODEL -"AMERICAN BOOK RETURNS - HCU FOR BOOKS"
STOREFRONT, SEE WINDOW TYPES
BOOK DROP BOX BY OWNER
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
10/28/22
A415
Enlarged
Plans &
Interior
Elevations
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
KEYED NOTES
06.06 WOOD VENEER, WV-01, RE: FINISH SCHEDULE
06.07 PLASTIC LAMINATE, PL-01, RE: FINISH SCHEDULE
06.08 PLASTIC LAMINATE, PL-02, RE: FINISH SCHEDULE
08.09 BOOK DROP, OPENING IN COUNTERTOP
08.10 DECORATIVE GLASS, GP-01, RE: FINISH SCHEDULE
08.11 DECORATIVE GLASS, GP-02, RE: FINISH SCHEDULE
08.15 OPENING FOR GROMMET
09.01 PAINTED GYP, PNT-01, RE: FINISH SCHEDULE
09.04 PAINTED GYP, PNT-04, RE: FINISH SCHEDULE
09.10 WALLCOVERING, LEVEL 5 FINISH PROVIDED, WC-01, RE: FINISH SCHEDULE
09.13 WALL BASE, WB-04, RE: FINISH SCHEDULE
09.15 WALL BASE, WB-01, RE: FINISH SCHEDULE
09.17 WALL BASE, WB-06, RE: FINISH SCHEDULE
09.19 PAINTED MILLWORK FINISH, TO MATCH PNT-04, RE: FINISH SCHEDULE
10.24 SIGNAGE, SEE SIGNAGE SCHEDULE
12.01 QUARTZ COUNTER TOP, ST-01, RE: FINISH SCHEDULE
GENERAL NOTES - INT PLAN/ELEV
1 GENERAL CONTRACTOR SHALL FIELD VERIFY ALL CONDITIONS AND SHALL REPORT TO THE ARCHITECT ANY UNKNOWN
CONDITIONS, ERRORS, OR CONFLICTS IN THE DRAWINGS BEFORE BEGINNING WORK
2 DO NOT SCALE DRAWINGS
3 SEE SHEET GI003 FOR TYPICAL MOUNTING HEIGHTS. PROVIDE SOLID BLOCKING IN WALLS FOR ALL WALL-MOUNTED ITEMS
WHETHER BLOCKING IS DEPICTED IN DRAWINGS OR NOT.
4 UPPER, LOWER, AND TALL MILLWORK CABINETS NOT TO EXCEED 36" IN WIDTH
5 UNLESS NOTED OTHERWISE, MATCH UPPER CABINET WIDTH DIMENSIONS TO BASE
CABINETS - TYP.
6 ALL ELECTRICAL AND DATA OUTLETS ABOVE COUNTER TOPS SHOULD BE
MOUNTED HORIZONTALLY
7 PROVIDE SAFETY INSULATION ON ALL EXPOSED SUPPLY WATER LINES AND WASTE LINES
8 PROVIDE ALUMINUM EDGE MOULDING @ ALL TILE TO H.M. DOOR TRANSITIONS
9 PROVIDE METAL TRIM AT ALL OUTSIDE EDGES ON TILE WALLS. SEE: FINISH SCHEDULE
10 PROVIDE METAL TRIM AT ALL TILE TO FLOOR TRANSITIONS. SEE: FINISH SCHEDULE
11 ALL EXPOSED STEEL COLUMNS TO BE PAINTED TO MATCH ADJACENT WALL
12 ALL MILLWORK INTERIOR FINISH TO BE WHITE MELAMINE, UNLESS NOTED OTHERWISE
13 COUNTERTOP EDGE PROFILES TO BE SQUARE EDGE. IF SHOWN IN ELEVATION, PROVIDE 4" BACKSPLASH
14 ALL WOOD GRAIN TO RUN VERTICALLY, UNLESS NOTED OTHERWISE
15 CALLED OUT RESTROOM ACCESSORIES TO BE INSTALLED AT EVERY STALL
16 ALL SIGNAGE, LETTERING, GRAPHICS TO BE COORDINATED WITH OWNER PER CAMPUS GRAPHIC STANDARDS
17 PROVIDE MILLWORK LOCKS WITH CAMPUS STANDARD LOCKS WHERE INDICATED WITH LOCK SYMBOL AT MILLWORK ELEVATION
1/4" = 1'-0"A1 CIRCULATION RECEPTION 110 - ENLARGED PLAN
1/4" = 1'-0"C1 CIRCULATION 110 RECEPTION EXT. - SOUTH
1/4" = 1'-0"A3 CIRCULATION RECEPTION 110 DESK INT. - NORTH
1/4" = 1'-0"B3 CIRCULATION RECEPTION 110 - SOUTH
1/4" = 1'-0"A5 CIRCULATION RECEPTION 110 DESK INT. - EAST
1/4" = 1'-0"B5 CIRCULATION RECEPTION 110 DESK INT. - WEST
1/4" = 1'-0"C4 INTER LIBRARY LOAN WORKSPACE - NORTH
1/4" = 1'-0"D4 INTER LIBRARY LOAN WORKSPACE EXT - SOUTH
1/4" = 1'-0"C2 CIRCULATION 110 RECEPTION DESK EXT. - EAST
1/4" = 1'-0"C3 CIRCULATION 110 RECEPTION DESK EXT. - WEST
1/4" = 1'-0"E1 OPEN STUDY 342 INTEGRATED DESKS - ENLARGED PLAN
1/4" = 1'-0"E2 TYP. OPEN STUDY 342 INTEGRATED DESKS ELEV.
1/4" = 1'-0"D1 VESTIBULE 1-F BOOK DROP - ENLARGED PLAN
1/4" = 1'-0"E3 OPEN STUDY 220 WRITABLE WALLS - ENLARGED PLAN
1/4" = 1'-0"E4 TYP. OPEN STUDY 220 WRITABLE WALL 1
1/4" = 1'-0"E5 TYP. OPEN STUDY 220 WRITABLE WALL 2
1/4" = 1'-0"D2 VESTIBULE 1-F BOOK DROP - EAST
1/4" = 1'-0"D3 VESTIBULE 1-F BOOK DROP SECTION
CL EQEQ
5' - 0"
VARIES; RE: FLOOR PLANS
10.29CL
B2
A431
CL EQEQ
5' - 0"
VARIES; RE: FLOOR PLANS
10.32CL
B2
A431 CASEWORK TAG
101M
AWS STANDARD CASEWORK TYPE
MODIFIED CASEWORK TYPE
REFER TO CASEWORK DESIGN SERIES (CDS) OF THE ARCHITECTURAL WOODWORK
STANDARDS (AWS) FOR A FULL DESCRIPTION OF CASEWORK TYPES
CASEWORK SYMBOL
INDICATES LOCKS REQUIRED
09.10 22.07 09.10
8"
LEVEL 5 FINISH
26' - 4"8"8"
LEVEL 5 FINISH
22' - 1 1/4"8"
TYP
8' - 2"
TYP
8"
9' - 10"
06.06
06.06
OPEN TO
BEYOND
EQ 30"EQ
34"
12.04
D1
A582
______________
06.07
09.13
D1
A572
______________D1
A572
______________
1' - 6"
132
TYP.5
IN BACKGROUNDIN MIDGROUND
09.04
09.09
09.04 09.04 09.04 09.04 09.04
09.05
09.1009.13
8' - 8"
SF17
7' - 2"
IN FOREGROUND
09.15
TYP. 5 TYP
TYPB1
A581
TYPB2
A581
09.05
09.10
09.0409.0409.0409.0409.0409.04
SF18
SF18
15"55 1/4"15"
FILLER
1 1/2"
11.1011.1011.10
11.10
06.09
30"
IN FOREGROUND
TYP. 6
TYPB1
A581
B1
A581
TYPTYPB2
A581
D5
A581
TYP
223 22306.07
TYP
09.13
09.15
09.13
TYP
TYP
TYP
09.04 09.04
09.05
09.10
09.13
09.04
TYPB2
A581
TYPB1
A581
09.15
CL8' - 10 3/32"
5' - 6 1/2"
10.29
124 125 126 127 128
IN MIDGROUND
10.12
09.09
SF12 SF13 SF14 SF15 SF168' - 8"
09.04
B5
A311
TYP.
5' - 0"
EQ EQ
10.32
CL
CL
EQ EQ
5' - 0"
10.29 CL
09.0409.0409.04
09.09
7' - 2"
11.10
09.10
TYP. 3
15"30"15"38 3/8"
30"
11.10
TYP
223 223
06.08
06.07
TYP
09.04
B1
A581
TYP09.13
SF19B
08.19
OPEN TO
BEYOND
OPEN TO
BEYOND
09.01
11.09
09.16
1' - 7 1/4"3/4"6' - 8"3/4"1' - 7 1/4"
4"
2' - 8 3/4"
3/4"
6' - 10 1/2"
EQ
EQ
EQEQ
CL
CL
B6
A571
______________
D5
A571
TYP
D5
A571
TYP
E1
A572
______________
OPEN TO
BEYOND
OPEN TO
BEYOND
09.01
09.16
4"
2' - 8 3/4"
3/4"
6' - 10 1/2"
2' - 4"
D5
A571
TYP
D5
A571
TYP
OPEN TO
BEYOND
OPEN TO
BEYOND
09.10
LEVEL 5 FINISH
OPEN TO
BEYOND
OPEN TO
BEYOND
09.10
LEVEL 5 FINISH
OPEN TO
BEYOND
OPEN TO
BEYOND
06.07
3/4"
22"
3/4"
34"
C2
A581
09.13
5' - 0"
10.33
4' - 0"
9"1' - 6"
CL
EQEQ
C1
A581
______________
CL
SIDE VARIES; RE: PLAN VIEW
BEHIND DOOR
4' - 0"
1'-6"9"
C1
A581
______________
CLEQ EQ
5' - 0"
10.33CL
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
10/28/22
A416
Interior
Elevations
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
1/4" = 1'-0"A4 TYPICAL STUDY ROOM WALL - TV
1/4" = 1'-0"A5 TYPICAL STUDY ROOM WALL - WHITE BOARD
GENERAL NOTES - INTERIOR ELEVATIONS
1 GENERAL CONTRACTOR SHALL FIELD VERIFY ALL CONDITIONS AND SHALL REPORT TO THE ARCHITECT ANY UNKNOWN
CONDITIONS, ERRORS, OR CONFLICTS IN THE DRAWINGS BEFORE BEGINNING WORK
2 DO NOT SCALE DRAWINGS
3 SEE SHEET SERIES G000's FOR TYPICAL MOUNTING HEIGHTS. PROVIDE SOLID BLOCKING IN WALLS FOR ALL
WALL-MOUNTED ITEMS WHETHER BLOCKING IS DEPICTED IN DRAWINGS OR NOT
4 UPPER, LOWER, AND TALL MILLWORK CABINETS NOT TO EXCEED 36" IN WIDTH, UNLESS NOTED OTHERWISE
5 UNLESS NOTED OTHERWISE, MATCH UPPER CABINET WIDTH DIMENSIONS TO BASE CABINETS - TYPICAL
6 ALL ELECTRICAL AND DATA OUTLETS ABOVE COUNTER TOPS SHOULD BE HORIZONTALLY ALIGNED AND MOUNTED
HORIZONTALLY
7 PROVIDE SAFETY INSULATION ON ALL EXPOSED SUPPLY WATER LINES AND WASTE LINES
8 PROVIDE METAL TRIM AT ALL OUTSIDE EDGES ON TILE WALLS; SEE DETAILS AND FINISH SCHEDULE
9 PROVIDE METAL TRIM AT ALL TILE TO FLOOR TRANSITIONS; SEE DETAILS AND FINISH SCHEDULE
10 ALL MILLWORK INTERIOR FINISH TO BE WHITE MELAMINE, UNLESS NOTED OTHERWISE
11 CONTRACTOR TO PROVIDE RESTROOM ACCESSORIES; SEE ACCESSORY SCHEDULE
12 SEE AF600 SERIES FOR MATERIAL SPECIFICATIONS
13 SEE SHEET SERIES A500's FOR WALL AND ASSEMBLY TYPES
14 SEE SHEET SERIES A600's FOR DOOR AND WINDOW TYPES
15 SEE SHEET SERIES A500's FOR CASEWORK DETAILS
16 ALL SIGNAGE, LETTERING, GRAPHICS TO BE COORDINATED WITH OWNER PER CAMPUS GRAPHIC STANDARDS
KEYED NOTES
06.06 WOOD VENEER, WV-01, RE: FINISH SCHEDULE
06.07 PLASTIC LAMINATE, PL-01, RE: FINISH SCHEDULE
06.08 PLASTIC LAMINATE, PL-02, RE: FINISH SCHEDULE
06.09 PLASTIC LAMINATE, PL-03, RE: FINISH SCHEDULE
08.19 24" X 24" ACCESS PANEL PAINTED TO MATCH ADJACENT WALL COLOR.
09.01 PAINTED GYP, PNT-01, RE: FINISH SCHEDULE
09.04 PAINTED GYP, PNT-04, RE: FINISH SCHEDULE
09.05 NEW GYP BD WALL TO ALIGN AND VISUALLY BLEND WITH EXISTING GYP BD WALL, MATCH EXISTING WALL PAINT
09.09 WALL BASE, WB-03, RE: FINISH SCHEDULE
09.10 WALLCOVERING, LEVEL 5 FINISH PROVIDED, WC-01, RE: FINISH SCHEDULE
09.13 WALL BASE, WB-04, RE: FINISH SCHEDULE
09.15 WALL BASE, WB-01, RE: FINISH SCHEDULE
09.16 WALL BASE, WB-05, RE: FINISH SCHEDULE
10.12 SEMI-RECESSED FIRE EXTINGUISHER CABINET
10.29 TV, CONTRACTOR TO PROVIDE 3/4" SHEATHING FOR THE ENTIRE WALL, OFOI
10.32 MARKER BOARD, 6'x 4', OFOI
10.33 MARKER BOARD, 4'x 4', OFOI
11.09 ELECTRIC FIREPLACE, RE: ACCESSORY SCHEDULE
11.10 PRINTER, OFOI, RE: ACCESSORY SCHEDULE; POWER AND DATAT TO BE PROVIDED, RE:ELECTRICAL
12.04 QUARTZ COUNTER TOP, ST-02, RE: FINISH SCHEDULE
22.07 HI LO DRINKING FOUNTAIN WITH BOTTLE FILLER - ADA COMPLIANT, RE: PLUMBING
1/4" = 1'-0"D3 OPEN STUDY 122B/122C - EAST
1/4" = 1'-0"E1 OPEN STUDY 122A - NORTH
1/4" = 1'-0"D1 OPEN STUDY 122A - EAST
1/4" = 1'-0"E3 OPEN STUDY 122 - NORTH
1/4" = 1'-0"C1 OPEN STUDY 122 - WEST
1/4" = 1'-0"A2 TYP PRACTICE ROOM WHITE BOARD WALL
1/4" = 1'-0"A3 TYP PRACTICE ROOM TV WALL
1/4" = 1'-0"B1 OPEN STUDY 118 - EAST
1/4" = 1'-0"B2 CIRCULATION RECEPTION 110 FIREPLACE - SOUTH / MIRROR NORTH
1/4" = 1'-0"B3 CIR. RECEPTION 1110 FIREPLACE E/W
1/4" = 1'-0"E5 OPEN STUDY 122A WHITE BOARD WALL 1- N + S
1/4" = 1'-0"C4 OPEN STUDY 122A TYP. WHITE BOARD WALL 2- N
1/4" = 1'-0"C5 OPEN STUDY 122A OPAC
CL
1/4" = 1'-0"A1 TYP OFFICE WHITE BOARD/COAT HOOK WALL
1/4" = 1'-0"B4 OFFICE 018 & 020 COAT HOOK - SOUTH
1/4" = 1'-0"B5 OFFICE 018 & 020 WHITE BOARD WALL
CASEWORK TAG
101M
AWS STANDARD CASEWORK TYPE
MODIFIED CASEWORK TYPE
REFER TO CASEWORK DESIGN SERIES (CDS) OF THE ARCHITECTURAL WOODWORK
STANDARDS (AWS) FOR A FULL DESCRIPTION OF CASEWORK TYPES
CASEWORK SYMBOL
INDICATES LOCKS REQUIRED
8' - 8"
206 208 210 212
09.04
09.09
SF37 SF38 SF39
TYP
214
SF40
216 218
SF41 SF42
TY
P
IN MIDGROUND IN MIDGROUND
15 1/2"
3/4"
69"
3/4"
EQ 3/4"48"3/4"168"3/4"48"3/4"EQ
06.0609.18
CL EQEQ
10.29
10.39
4' - 2"
TYP
CL
TYP
E2
A572
TYP
E3
A572
TYP
E3
A572
TYP
E3
A572
TYP
10.12
09.04
09.09
200 202 204
8' - 8"
SF35
09.05
09.0409.0409.0409.0409.04
09.10
09.13
IN FOREGROUND
TYP. 5
7' - 2"
09.15B1
A581
TYP TYPB2
A581
TYPB1
A581
34"
06.07
D1
A582
______________
EQ 30"EQ
12.04
09.13
RECESSED
4' - 8 3/16"
10' - 0"
IN FOREGROUND
09.05
09.10
09.0409.0409.0409.0409.04
09.13EQEQ
22.20
09.12
B1
A581
TYP TYPB1
A581
TYPB2
A581
267 268266
09.04
09.09
8' - 8"
SF61 SF62 SF63
IN MIDGROUND
4' - 10"
10.29CL
10' - 11 7/8"
4' - 3"
A5
A581
______________
15' - 0"
27"21"2"
211
34"
D3
A581
______________
11.0111.01
11.05
11.05
06.08
06.07
TYP
09.13
4' - 10"
4' - 6"
10.33
CL
CL
140 140
18"36"36"36"18"FILLER
3 1/8"
222 222101 101
34"
06.08
06.07
222 3' - 0"
142.2
06.12
CL EQEQ
4' - 10"
10.29 CL 156E 156F
EQ EQ
5' - 0"
10.29CL
CL
EQ EQ
4' - 10"
10.23
10.31 10.3310.33CL
CL
CLEQ EQ
4' - 10"
19010.31
CL
CLEQ EQ
5' - 0"
10.32
CL
CLEQ EQ
5' - 0"
10.29CL
OPEN TO
BEYOND
100 100
34"
24"24"
06.07
06.08
09.13
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
10/28/22
A417
Interior
Elevations
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
GENERAL NOTES - INTERIOR ELEVATIONS
1 GENERAL CONTRACTOR SHALL FIELD VERIFY ALL CONDITIONS AND SHALL REPORT TO THE ARCHITECT ANY UNKNOWN
CONDITIONS, ERRORS, OR CONFLICTS IN THE DRAWINGS BEFORE BEGINNING WORK
2 DO NOT SCALE DRAWINGS
3 SEE SHEET SERIES G000's FOR TYPICAL MOUNTING HEIGHTS. PROVIDE SOLID BLOCKING IN WALLS FOR ALL
WALL-MOUNTED ITEMS WHETHER BLOCKING IS DEPICTED IN DRAWINGS OR NOT
4 UPPER, LOWER, AND TALL MILLWORK CABINETS NOT TO EXCEED 36" IN WIDTH, UNLESS NOTED OTHERWISE
5 UNLESS NOTED OTHERWISE, MATCH UPPER CABINET WIDTH DIMENSIONS TO BASE CABINETS - TYPICAL
6 ALL ELECTRICAL AND DATA OUTLETS ABOVE COUNTER TOPS SHOULD BE HORIZONTALLY ALIGNED AND MOUNTED
HORIZONTALLY
7 PROVIDE SAFETY INSULATION ON ALL EXPOSED SUPPLY WATER LINES AND WASTE LINES
8 PROVIDE METAL TRIM AT ALL OUTSIDE EDGES ON TILE WALLS; SEE DETAILS AND FINISH SCHEDULE
9 PROVIDE METAL TRIM AT ALL TILE TO FLOOR TRANSITIONS; SEE DETAILS AND FINISH SCHEDULE
10 ALL MILLWORK INTERIOR FINISH TO BE WHITE MELAMINE, UNLESS NOTED OTHERWISE
11 CONTRACTOR TO PROVIDE RESTROOM ACCESSORIES; SEE ACCESSORY SCHEDULE
12 SEE AF600 SERIES FOR MATERIAL SPECIFICATIONS
13 SEE SHEET SERIES A500's FOR WALL AND ASSEMBLY TYPES
14 SEE SHEET SERIES A600's FOR DOOR AND WINDOW TYPES
15 SEE SHEET SERIES A500's FOR CASEWORK DETAILS
16 ALL SIGNAGE, LETTERING, GRAPHICS TO BE COORDINATED WITH OWNER PER CAMPUS GRAPHIC STANDARDS
KEYED NOTES
06.06 WOOD VENEER, WV-01, RE: FINISH SCHEDULE
06.07 PLASTIC LAMINATE, PL-01, RE: FINISH SCHEDULE
06.08 PLASTIC LAMINATE, PL-02, RE: FINISH SCHEDULE
06.12 TECH STATION OWNER PROVIDED OWNER INSTALLED
09.04 PAINTED GYP, PNT-04, RE: FINISH SCHEDULE
09.05 NEW GYP BD WALL TO ALIGN AND VISUALLY BLEND WITH EXISTING GYP BD WALL, MATCH EXISTING WALL PAINT
09.09 WALL BASE, WB-03, RE: FINISH SCHEDULE
09.10 WALLCOVERING, LEVEL 5 FINISH PROVIDED, WC-01, RE: FINISH SCHEDULE
09.12 TILE WALL, TL-02, RE: FINISH SCHEDULE
09.13 WALL BASE, WB-04, RE: FINISH SCHEDULE
09.15 WALL BASE, WB-01, RE: FINISH SCHEDULE
09.18 WALLCOVERING, WC-02, RE: FINISH SCHEDULE
10.12 SEMI-RECESSED FIRE EXTINGUISHER CABINET
10.23 CEILING MOUNTED PROJECTOR, OFOI, STEEL PIPE SUPPORT PROVIDED BY CONTRACTOR
10.29 TV, CONTRACTOR TO PROVIDE 3/4" SHEATHING FOR THE ENTIRE WALL, OFOI
10.31 MARKER BOARD, 8'x 4', OFOI
10.32 MARKER BOARD, 6'x 4', OFOI
10.33 MARKER BOARD, 4'x 4', OFOI
10.39 SPECIALTY WALL SLAT PANEL, SP-03, RE: FINISH SCHEDULE
11.01 REFRIGERATOR; OFOI
11.05 MICROWAVE, OFOI
12.04 QUARTZ COUNTER TOP, ST-02, RE: FINISH SCHEDULE
22.20 DRINKING FOUNTAIN TYPE VARIES, RE: FLOOR PLAN FOR TYPES, RE: PLUMBING
1/4" = 1'-0"D1 OPEN STUDY 220- SOUTH ELEVATION
1/4" = 1'-0"E4 OPEN STUDY 220 - EAST
1/4" = 1'-0"E1 OPEN STUDY 53 - EAST
1/4" = 1'-0"E2 OPEN STUDY 53 - EAST CONT.
1/4" = 1'-0"A4 HALL 2-W - NORTH
1/4" = 1'-0"A1 OPS 022 - SOUTH
1/4" = 1'-0"A2 TIER 2 015 - EAST
1/4" = 1'-0"B5 BREAK ROOM 013 - SOUTH
1/4" = 1'-0"C5 TECH ROOM 024 - NORTH
1/4" = 1'-0"B1 CONFERNECE ROOM 140 - NORTH
1/4" = 1'-0"B3 CONFERENCE ROOM 140 - WEST
1/4" = 1'-0"B2 CONFERENCE ROOM 140 - SOUTH
1/4" = 1'-0"B4 WORKSPACE 156 - NORTH
1/4" = 1'-0"C4 TRAINING AREA 190 - WEST
1/4" = 1'-0"C3 TRAINING AREA 190 - EAST
1/4" = 1'-0"C1 SMALL MEETING 192A - EAST
1/4" = 1'-0"C2 SMALL MEETING 192A - WEST
1/4" = 1'-0"A3 TIER 2 015 WORK BENCH - NORTH/SOUTH
320318316314
10.12
09.04
09.09
SF73 SF74 SF75 SF76
TYP
CASEWORK TAG
101M
AWS STANDARD CASEWORK TYPE
MODIFIED CASEWORK TYPE
REFER TO CASEWORK DESIGN SERIES (CDS) OF THE ARCHITECTURAL WOODWORK
STANDARDS (AWS) FOR A FULL DESCRIPTION OF CASEWORK TYPES
CASEWORK SYMBOL
INDICATES LOCKS REQUIRED
09.05
09.13
09.0409.0409.0409.04 09.04
IN FOREGROUND
09.15
TYP. 3
304302
09.04
09.09
8' - 8"
SF71 SF72
IN MIDGROUND
330 332 334 336 338 340
IN BACKGROUND
8' - 8"
09.04
09.09
SF85 SF86 SF87 SF88 SF89 SF90
IN MIDGROUND
TYP
09.05
09.13
09.0409.0409.04
OPEN TO
BEYOND
IN FOREGROUND
09.15
TYP. 2
09.10
B4
A311
06.12
OPEN TO
BEYOND
OPEN TO
BEYOND
CL EQEQ
5' - 0"
10.29CL
CL EQEQ
4' - 10"
162
10.22
06.13
TYP ALL WALLS
32"
CL
A1
A581
TYP
CL 10' - 11 3/4"
4' - 10"
10.22
10.33 10.33
TYP ALL WALLS
32"
06.13
CL A1
A581
TYP
1' - 0"
10.34
CL 10' - 9 3/8"11' - 0"
4' - 4 1/2"
10.22
TYP ALL WALLS
32"
06.13
CL A1
A581
TYP
06.12
CLEQ EQ
4' - 10"
10.2210.33 10.33
TYP ALL WALLS
32"
06.13
CL
9' - 0"
10.34
A1
A581
TYP
EQEQ
5' - 0"
10.31
CL
CL
EQ EQ
5' - 0"
10.29
CL
CL
TYP ALL WALLS
32"
06.13
A1
A581
TYP
CL EQEQ
10.34
9'-0"
CL 8' - 6 3/4"3' - 0"
5'-0"
CL 10.33
10' - 6 5/8"11' - 2"
4' - 10"06.12
10.22
TYP ALL WALLS
32"
06.13
CL
A1
A581
TYP
10.34
1' - 0"
CLEQ EQ
SF77
230 230 101 101 101 230 230 101 101 101 230 230
FILLER
1 1/16"
21"24"24"24"24"24"24"24"24"24"24"21"
FILLER
1 1/16"
06.07
06.08
06.13
12"
12"
12"
42"
88 3/4"
324B
TYP ALL WALLS
32"
06.13
A1
A581
TYP
E4
A582
______________
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
10/28/22
A418
Interior
Elevations
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
1/4" = 1'-0"B1 JUVENILE 300- WEST ELEVATION
KEYED NOTES
06.07 PLASTIC LAMINATE, PL-01, RE: FINISH SCHEDULE
06.08 PLASTIC LAMINATE, PL-02, RE: FINISH SCHEDULE
06.12 TECH STATION OWNER PROVIDED OWNER INSTALLED
06.13 WOOD CHAIR RAIL, WHITE OAK, STAINED AND ROUTED TO MATCH ARCHITECT SAMPLE
09.04 PAINTED GYP, PNT-04, RE: FINISH SCHEDULE
09.05 NEW GYP BD WALL TO ALIGN AND VISUALLY BLEND WITH EXISTING GYP BD WALL, MATCH EXISTING WALL PAINT
09.09 WALL BASE, WB-03, RE: FINISH SCHEDULE
09.10 WALLCOVERING, LEVEL 5 FINISH PROVIDED, WC-01, RE: FINISH SCHEDULE
09.13 WALL BASE, WB-04, RE: FINISH SCHEDULE
09.15 WALL BASE, WB-01, RE: FINISH SCHEDULE
10.12 SEMI-RECESSED FIRE EXTINGUISHER CABINET
10.22 MARKER BOARD, 12'x 4', OFOI
10.29 TV, CONTRACTOR TO PROVIDE 3/4" SHEATHING FOR THE ENTIRE WALL, OFOI
10.31 MARKER BOARD, 8'x 4', OFOI
10.33 MARKER BOARD, 4'x 4', OFOI
10.34 WALL MOUNTED PROJECTOR SCREEN, OFOI, BACKING PROVIDED BY CONTRACTOR, VERIFY MOUNTING HEIGHT
WITH MFGR REQ.
GENERAL NOTES - INTERIOR ELEVATIONS
1 GENERAL CONTRACTOR SHALL FIELD VERIFY ALL CONDITIONS AND SHALL REPORT TO THE ARCHITECT ANY UNKNOWN
CONDITIONS, ERRORS, OR CONFLICTS IN THE DRAWINGS BEFORE BEGINNING WORK
2 DO NOT SCALE DRAWINGS
3 SEE SHEET SERIES G000's FOR TYPICAL MOUNTING HEIGHTS. PROVIDE SOLID BLOCKING IN WALLS FOR ALL
WALL-MOUNTED ITEMS WHETHER BLOCKING IS DEPICTED IN DRAWINGS OR NOT
4 UPPER, LOWER, AND TALL MILLWORK CABINETS NOT TO EXCEED 36" IN WIDTH, UNLESS NOTED OTHERWISE
5 UNLESS NOTED OTHERWISE, MATCH UPPER CABINET WIDTH DIMENSIONS TO BASE CABINETS - TYPICAL
6 ALL ELECTRICAL AND DATA OUTLETS ABOVE COUNTER TOPS SHOULD BE HORIZONTALLY ALIGNED AND MOUNTED
HORIZONTALLY
7 PROVIDE SAFETY INSULATION ON ALL EXPOSED SUPPLY WATER LINES AND WASTE LINES
8 PROVIDE METAL TRIM AT ALL OUTSIDE EDGES ON TILE WALLS; SEE DETAILS AND FINISH SCHEDULE
9 PROVIDE METAL TRIM AT ALL TILE TO FLOOR TRANSITIONS; SEE DETAILS AND FINISH SCHEDULE
10 ALL MILLWORK INTERIOR FINISH TO BE WHITE MELAMINE, UNLESS NOTED OTHERWISE
11 CONTRACTOR TO PROVIDE RESTROOM ACCESSORIES; SEE ACCESSORY SCHEDULE
12 SEE AF600 SERIES FOR MATERIAL SPECIFICATIONS
13 SEE SHEET SERIES A500's FOR WALL AND ASSEMBLY TYPES
14 SEE SHEET SERIES A600's FOR DOOR AND WINDOW TYPES
15 SEE SHEET SERIES A500's FOR CASEWORK DETAILS
16 ALL SIGNAGE, LETTERING, GRAPHICS TO BE COORDINATED WITH OWNER PER CAMPUS GRAPHIC STANDARDS
1/4" = 1'-0"B3 OPEN STUDY 342 - NORTH
1/4" = 1'-0"A4 OPEN STUDY 383 - SOUTH
1/4" = 1'-0"A1 OPEN STUDY 342 - WEST
1/4" = 1'-0"B4 OPEN STUDY 342 - EAST
1/4" = 1'-0"E1 WORKSTATIONS/FLEX SPACE 192 - NORTH
1/4" = 1'-0"E3 CONFERENCE ROOM 158 - NORTH
1/4" = 1'-0"D1 CLASSROOM 162 & 164 - NORTH
1/4" = 1'-0"D2 CLASSROOM 162 & 164 - EAST
1/4" = 1'-0"D3 CLASSROOM 162 - SOUTH
1/4" = 1'-0"D5 CLASSROOM 162 & 164 - WEST
1/4" = 1'-0"E4 CONFERENCE 188B - NORTH
1/4" = 1'-0"E5 CONFERENCE 188B - WEST
1/4" = 1'-0"C2 MAC LAB 324 - NORTH
1/4" = 1'-0"C1 CLASSROOM 164 - SOUTH
1/4" = 1'-0"E2 WORKSTATIONS/FLEX SPACE 192 - WEST
1/4" = 1'-0"C4 MAC LAB 324 - SOUTH
1/4" = 1'-0"C5 MAC LAB 324 - WEST
CASEWORK TAG
101M
AWS STANDARD CASEWORK TYPE
MODIFIED CASEWORK TYPE
REFER TO CASEWORK DESIGN SERIES (CDS) OF THE ARCHITECTURAL WOODWORK
STANDARDS (AWS) FOR A FULL DESCRIPTION OF CASEWORK TYPES
CASEWORK SYMBOL
INDICATES LOCKS REQUIRED
CLEQ EQ
4' - 10"
10.33 10.3310.22CL
4' - 10"
CLEQ EQ
CLCLEQEQ
CLCLEQ EQ
10.32 10.3210.29CL
34"
102
36"58 9/16"36"3"
102
06.08
06.07
34"
102 102
3"36"62 3/4"36"36"1 1/2"
102
06.08
06.07
TYP ALL WALLS
32"
06.13
CLEQ EQ
10.23
8' - 3"CL
A1
A581
TYP
4'-10"
10.31
10.33 10.33
C1
A581
______________
24"
30"
48"
18"16"
18"18"18"18"
400 400 400 400
06.07
93"
21"
17"
17"
17"
11.01
D4
A581
______________18"
06.14
C1
A581
______________
30"
48"
58"
4"4"4"
18"18"18"
400 400 400
06.07
11.01 84"
4' - 10"
CLEQ EQ
256A 10.33 CL
CLEQ EQ
4' - 10"
10.32CL
CLEQ EQ
10.23
4' - 10"
10.33 10.33
10.22
TYP ALL WALLS
32"
06.138' - 3"
CL
A1
A581
TYP
3' - 0"
06.12
278
TYP ALL WALLS
32"
06.13
A1
A581
TYP
02.41
STAIR LANDING
09.01
09.16
09.01
09.15
4"
3' - 3"
3/4"
1' - 0 1/4"
3/4"
9' - 3 1/4"
8"
3/4"
2' - 3 1/4"
STONE REVEAL
1' - 11 1/4"
3/4"5 1/4"
3/4"
STONE REVEAL
7' - 8 1/4"
3/4"
5 1/4"3/4"
1' - 11 1/4"
2' - 5 1/4"
3/4"
1' - 4 1/4"
3/4"
4' - 10 1/4"
3/4"
1' - 4 1/4"
3/4"
D5
A571
TYP
D5
A571
TYP
C3
A571
TYP
C3
A571
TYP
C3
A571
TYP
C3
A571
TYP
OPEN TO
BEYOND
OPEN TO
BEYOND
TYP
4 3/4"
TYP
8 1/2"
10.3710.3710.37
10.38
10.38
10.38
10.38
B2
A431 OPEN TO
BEYOND
OPEN TO
BEYOND
10.37
10.38
10.38
10.37
10.38
10.38
10.37
10.38
10.38
10.37
TYP
4 3/4"
TYP
8 1/2"B2
A431
3' - 0"TYP ALL WALLS
32"
06.12
06.13
A1
A581
TYP 258
TYP ALL WALLS
32"
4' - 10"
CL EQEQ
10.22 10.3310.33
06.13
CL
A1
A581
TYP
4' - 10"
CLEQ EQ
TYP ALL WALLS
32"
10.22 06.13
CL A1
A581
TYP
10.22 10.33
CL EQEQ
3' - 0"
4' - 10"
TYP ALL WALLS
32"
06.12
06.13
CL A1
A581
TYP
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
10/28/22
A419
Interior
Elevations
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
KEYED NOTES
02.41 EXISTING STONE WALL, TO BE PROTECTED DURING CONSTRUCTION, TO BE CLEANED THROROUGHLY, MATCHING
PATCH MATERIAL TO BE USED AND APPROVED BY ARCHITECT AT ANY HOLES FROM ELECTRICAL ITEMS
RELOCATING
06.07 PLASTIC LAMINATE, PL-01, RE: FINISH SCHEDULE
06.08 PLASTIC LAMINATE, PL-02, RE: FINISH SCHEDULE
06.12 TECH STATION OWNER PROVIDED OWNER INSTALLED
06.13 WOOD CHAIR RAIL, WHITE OAK, STAINED AND ROUTED TO MATCH ARCHITECT SAMPLE
06.14 WOOD COAT STRIP, WHITE OAK, STAINED AND ROUTED TO MATCH CAMPUS STANDARD, 3 HOOKS AT EACH TO
MATCH CAMPUS STANDARD
09.01 PAINTED GYP, PNT-01, RE: FINISH SCHEDULE
09.15 WALL BASE, WB-01, RE: FINISH SCHEDULE
09.16 WALL BASE, WB-05, RE: FINISH SCHEDULE
10.22 MARKER BOARD, 12'x 4', OFOI
10.23 CEILING MOUNTED PROJECTOR, OFOI, STEEL PIPE SUPPORT PROVIDED BY CONTRACTOR
10.29 TV, CONTRACTOR TO PROVIDE 3/4" SHEATHING FOR THE ENTIRE WALL, OFOI
10.31 MARKER BOARD, 8'x 4', OFOI
10.32 MARKER BOARD, 6'x 4', OFOI
10.33 MARKER BOARD, 4'x 4', OFOI
10.37 SPECIALTY WALL PARTITION, SP-01, RE: FINISH SCHEDULE
10.38 SPECIALTY WALL PARTITION, SP-02, RE: FINISH SCHEDULE
11.01 REFRIGERATOR; OFOI
GENERAL NOTES - INTERIOR ELEVATIONS
1 GENERAL CONTRACTOR SHALL FIELD VERIFY ALL CONDITIONS AND SHALL REPORT TO THE ARCHITECT ANY UNKNOWN
CONDITIONS, ERRORS, OR CONFLICTS IN THE DRAWINGS BEFORE BEGINNING WORK
2 DO NOT SCALE DRAWINGS
3 SEE SHEET SERIES G000's FOR TYPICAL MOUNTING HEIGHTS. PROVIDE SOLID BLOCKING IN WALLS FOR ALL
WALL-MOUNTED ITEMS WHETHER BLOCKING IS DEPICTED IN DRAWINGS OR NOT
4 UPPER, LOWER, AND TALL MILLWORK CABINETS NOT TO EXCEED 36" IN WIDTH, UNLESS NOTED OTHERWISE
5 UNLESS NOTED OTHERWISE, MATCH UPPER CABINET WIDTH DIMENSIONS TO BASE CABINETS - TYPICAL
6 ALL ELECTRICAL AND DATA OUTLETS ABOVE COUNTER TOPS SHOULD BE HORIZONTALLY ALIGNED AND MOUNTED
HORIZONTALLY
7 PROVIDE SAFETY INSULATION ON ALL EXPOSED SUPPLY WATER LINES AND WASTE LINES
8 PROVIDE METAL TRIM AT ALL OUTSIDE EDGES ON TILE WALLS; SEE DETAILS AND FINISH SCHEDULE
9 PROVIDE METAL TRIM AT ALL TILE TO FLOOR TRANSITIONS; SEE DETAILS AND FINISH SCHEDULE
10 ALL MILLWORK INTERIOR FINISH TO BE WHITE MELAMINE, UNLESS NOTED OTHERWISE
11 CONTRACTOR TO PROVIDE RESTROOM ACCESSORIES; SEE ACCESSORY SCHEDULE
12 SEE AF600 SERIES FOR MATERIAL SPECIFICATIONS
13 SEE SHEET SERIES A500's FOR WALL AND ASSEMBLY TYPES
14 SEE SHEET SERIES A600's FOR DOOR AND WINDOW TYPES
15 SEE SHEET SERIES A500's FOR CASEWORK DETAILS
16 ALL SIGNAGE, LETTERING, GRAPHICS TO BE COORDINATED WITH OWNER PER CAMPUS GRAPHIC STANDARDS
1/4" = 1'-0"A1 STUDY (LG) 326 - EAST
1/4" = 1'-0"A2 STUDY (LG) 326 & 328 - WEST
1/4" = 1'-0"A4 JUVENILE 300 - EAST
1/4" = 1'-0"A5 JUVENILE 300 - SOUTH
1/4" = 1'-0"D3 CLASSROOM 258 & 260 - EAST
1/4" = 1'-0"E2 PREP/STORAGE 252G - EAST
1/4" = 1'-0"E1 PREP/STORAGE 252G - NORTH
1/4" = 1'-0"E3 PREP/STORAGE 252G - SOUTH
1/4" = 1'-0"E5 PREP/STORAGE 256A- EAST
1/4" = 1'-0"E4 PREP/STORAGE 256A- NORTH
1/4" = 1'-0"D1 PREP/STORAGE 256A- SOUTH
1/4" = 1'-0"B4 TYP PRE-FUNCTION WHITEBOARD WALL
1/4" = 1'-0"C3 CLASS. 278 & READING CENTER 272 - W
1/4" = 1'-0"C2 CLASS. 278 & READING CENTER 272 - N
1/4" = 1'-0"B5 STAIRS 2-U - EAST
1/4" = 1'-0"B1 ENRY HALL 120A TRANSLUCENT PARTITION WALL 1
1/4" = 1'-0"B2 ENRY HALL 120A TRANSLUCENT PARTITION WALL 2
1/4" = 1'-0"D2 CLASSROOM 258 - NORTH
1/4" = 1'-0"D4 CLASSROOM 258 & 260 - SOUTH
1/4" = 1'-0"C1 CLASSROOM 258 & 260 - WEST
1/4" = 1'-0"C4 CLASSROOM 260 - SOUTH
CASEWORK TAG
101M
AWS STANDARD CASEWORK TYPE
MODIFIED CASEWORK TYPE
REFER TO CASEWORK DESIGN SERIES (CDS) OF THE ARCHITECTURAL WOODWORK
STANDARDS (AWS) FOR A FULL DESCRIPTION OF CASEWORK TYPES
CASEWORK SYMBOL
INDICATES LOCKS REQUIRED
36"24"24"1 1/2"
434 400 400
84"
06.07
09.13
188
10.13
SF22
09.11
RECESSED
09.01 06.0606.0602.41
6"4'-0 3/8"4'-0 3/8"4'-0 3/8"4'-0 3/8"4'-0 3/8"
6 3/4"
2'-0 1/8"
1' - 11 1/4"
5' - 1 1/4"
8"
2' - 3 1/2"
D5
A571
TYP
D5
A571
TYP
D5
A571
TYP
C3
A571
TYP
C3
A571
TYP
C3
A571
TYP
C3
A571
TYP
C3
A571
TYP
61 1/4"
35 1/4"
EQ 54"EQ
06.06
02.41
10.26
C4
A571
TYP
C4
A571
TYP
C4
A571
TYP
B1
A571
TYP
EQ
EQ
EQ EQ
10.303"
5"
192 190192
SF21
RECESSED
09.11
5' - 0"
CL
10.29
3' - 1 3/8"
CL
09.01 06.0602.41
02.41
1' - 11 1/4"
5' - 1 1/4"
2' - 11 1/2"
06.06
09.01
EQ 54"EQ
35 1/4"
61 1/4"
D5
A571
TYP D5
A571
TYP
D5
A571
TYP
C3
A571
TYP C3
A571
TYP
C3
A571
TYP
C3
A571
TYP
C3
A571
TYP
C3
A571
TYP
3'-5 1/4"6 3/4"4'-0 3/8"4'-0 3/8"4'-0 3/8"6"
10"
3"10.30
FILLER 30"30"30"30"FILLER
34"
20"
30"
1/2"30"30"30"30"7/8"
212 212 212 212
302 302 302 302
06.07
06.08
06.07
09.15
180
4' - 10"
10.33 CL
4' - 0"
7 1/8"1' - 6"
C1
A581
______________
6' - 9"
CL
10' - 1 1/2"11' - 1 1/2"
4' - 10"
10.22
3' - 0"
06.12
TYP. ALL WALLS
32"
06.13
CL
A1
A581
TYP
CLEQ EQ
10.22
CLEQ EQ
4' - 10"
10.31
TYP. ALL WALLS
32"
06.13
CL
A1
A581
TYP
CL 10' - 7 1/8"10' - 7 7/8"
4' - 10"
17210.22
TYP. ALL WALLS
32"
06.13
CL
10.33
A1
A581
TYP
4' - 10"
CLEQ EQ
10.31 10.31
TYP. ALL WALLS
32"
06.13
CL 10.22
10.34
A1
A581
TYP
1' - 0"
CL EQEQ
4' - 10"
166
10.22
TYP. ALL WALLS
32"
06.13CL
A1
A581
TYP
4' - 10"
3' - 0"
06.12
10.33 10.22
TYP ALL WALLS
32"
06.13CL
10' - 9 3/4"11' - 1 3/4"
CL
A1
A581
TYP
4' - 4 1/2"
10.23
CL EQEQ
10.2210.32 10.32
TYP. ALL WALLS
32"
06.13
COORINATE WITH WINDOW
A1
A581
TYP
CL
CLEQ EQ
4' - 10"
10.2210.33 10.33
TYP. ALL WALLS
32"
06.13
CL
A1
A581
TYP
4' - 10"
5' - 8 5/8"5' - 8 5/8"5' - 7 3/4"
168 10.31 10.31
TYP ALL WALLS
32"
06.13
CL
CLCLCL
A1
A581
TYP
E1-Z.4 E1-Z.5 E1-Z.6E1-Z.5 E1-Z.6E1-Z.4
09.01
2' - 0 13/16"
CLEQ EQ
4' - 10"
10.22
06.12
CL
TYP ALL WALLS
32"
A1
A581
TYP
06.13
222.1
TYP ALL WALLS
32"
A1
A581
TYP
06.13
10.31
EQEQ
CL
5'-0"
CLEQ EQ
CL 10.29OPEN TO
BEYOND
256.1 SF64 SF65 256.2 OPEN TO
BEYOND
10"
3"09.11 10.30
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
10/28/22
A420
Interior
Elevations
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
GENERAL NOTES - INTERIOR ELEVATIONS
1 GENERAL CONTRACTOR SHALL FIELD VERIFY ALL CONDITIONS AND SHALL REPORT TO THE ARCHITECT ANY UNKNOWN
CONDITIONS, ERRORS, OR CONFLICTS IN THE DRAWINGS BEFORE BEGINNING WORK
2 DO NOT SCALE DRAWINGS
3 SEE SHEET SERIES G000's FOR TYPICAL MOUNTING HEIGHTS. PROVIDE SOLID BLOCKING IN WALLS FOR ALL
WALL-MOUNTED ITEMS WHETHER BLOCKING IS DEPICTED IN DRAWINGS OR NOT
4 UPPER, LOWER, AND TALL MILLWORK CABINETS NOT TO EXCEED 36" IN WIDTH, UNLESS NOTED OTHERWISE
5 UNLESS NOTED OTHERWISE, MATCH UPPER CABINET WIDTH DIMENSIONS TO BASE CABINETS - TYPICAL
6 ALL ELECTRICAL AND DATA OUTLETS ABOVE COUNTER TOPS SHOULD BE HORIZONTALLY ALIGNED AND MOUNTED
HORIZONTALLY
7 PROVIDE SAFETY INSULATION ON ALL EXPOSED SUPPLY WATER LINES AND WASTE LINES
8 PROVIDE METAL TRIM AT ALL OUTSIDE EDGES ON TILE WALLS; SEE DETAILS AND FINISH SCHEDULE
9 PROVIDE METAL TRIM AT ALL TILE TO FLOOR TRANSITIONS; SEE DETAILS AND FINISH SCHEDULE
10 ALL MILLWORK INTERIOR FINISH TO BE WHITE MELAMINE, UNLESS NOTED OTHERWISE
11 CONTRACTOR TO PROVIDE RESTROOM ACCESSORIES; SEE ACCESSORY SCHEDULE
12 SEE AF600 SERIES FOR MATERIAL SPECIFICATIONS
13 SEE SHEET SERIES A500's FOR WALL AND ASSEMBLY TYPES
14 SEE SHEET SERIES A600's FOR DOOR AND WINDOW TYPES
15 SEE SHEET SERIES A500's FOR CASEWORK DETAILS
16 ALL SIGNAGE, LETTERING, GRAPHICS TO BE COORDINATED WITH OWNER PER CAMPUS GRAPHIC STANDARDS
1/4" = 1'-0"D2 COLLABORATIVE SPACE 188 - EAST
1/4" = 1'-0"E1 HALL 1-Y - EAST
1/4" = 1'-0"E3 HALL 1-Y - WEST
1/4" = 1'-0"D3 COLLABORATIVE SPACE 188 - S
1/4" = 1'-0"D4 ADJUNCT OFFICE 180 - WEST
1/4" = 1'-0"C1 CLASSROOM 172 - NORTH
1/4" = 1'-0"C2 CLASSROOM 172 - EAST
1/4" = 1'-0"C3 CLASSROOM 172 - SOUTH
1/4" = 1'-0"C5 CLASSROOM 172 - WEST
1/4" = 1'-0"B1 CLASSROOM 166 - NORTH
1/4" = 1'-0"B2 CLASSROOM 166 & 168 - EAST
1/4" = 1'-0"B3 CLASSROOM 166 & 168 - SOUTH
1/4" = 1'-0"B5 CLASSROOM 166 & 168 - WEST
1/4" = 1'-0"A1 CLASSROOM 168 - NORTH
1/4" = 1'-0"D1 HALL 1-Y - NORTH KEYED NOTES
02.41 EXISTING STONE WALL, TO BE PROTECTED DURING CONSTRUCTION, TO BE CLEANED THROROUGHLY, MATCHING
PATCH MATERIAL TO BE USED AND APPROVED BY ARCHITECT AT ANY HOLES FROM ELECTRICAL ITEMS
RELOCATING
06.06 WOOD VENEER, WV-01, RE: FINISH SCHEDULE
06.07 PLASTIC LAMINATE, PL-01, RE: FINISH SCHEDULE
06.08 PLASTIC LAMINATE, PL-02, RE: FINISH SCHEDULE
06.12 TECH STATION OWNER PROVIDED OWNER INSTALLED
06.13 WOOD CHAIR RAIL, WHITE OAK, STAINED AND ROUTED TO MATCH ARCHITECT SAMPLE
09.01 PAINTED GYP, PNT-01, RE: FINISH SCHEDULE
09.11 HATCH PATTERN INDICATES EXTENT OF FULL COLOR VINYL WALL GRAPHIC, SEE SIGN SCHEDULE, PREP WALL
WITH LEVEL 5 FINISH PRIOR TO INSTALLING VINYL
09.13 WALL BASE, WB-04, RE: FINISH SCHEDULE
09.15 WALL BASE, WB-01, RE: FINISH SCHEDULE
10.13 FULLY RECESSED FIRE EXTINGUISHER CABINET
10.22 MARKER BOARD, 12'x 4', OFOI
10.23 CEILING MOUNTED PROJECTOR, OFOI, STEEL PIPE SUPPORT PROVIDED BY CONTRACTOR
10.26 SIGNAGE, SEE SIGNAGE SCHEDULE
10.29 TV, CONTRACTOR TO PROVIDE 3/4" SHEATHING FOR THE ENTIRE WALL, OFOI
10.30 SIGNAGE, SEE SIGNAGE SCHEDULE
10.31 MARKER BOARD, 8'x 4', OFOI
10.32 MARKER BOARD, 6'x 4', OFOI
10.33 MARKER BOARD, 4'x 4', OFOI
10.34 WALL MOUNTED PROJECTOR SCREEN, OFOI, BACKING PROVIDED BY CONTRACTOR, VERIFY MOUNTING HEIGHT
WITH MFGR REQ.
1/4" = 1'-0"A2 INSTRUCTION 222 & 224 - NORTH
1/4" = 1'-0"A3 INSTRUCTION 222 & 224 - SOUTH
1/4" = 1'-0"A4 OPEN TUTORING 254 - TV - WEST
1/4" = 1'-0"D5 WRITING CENTER 256 - NORTH
CASEWORK TAG
101M
AWS STANDARD CASEWORK TYPE
MODIFIED CASEWORK TYPE
REFER TO CASEWORK DESIGN SERIES (CDS) OF THE ARCHITECTURAL WOODWORK
STANDARDS (AWS) FOR A FULL DESCRIPTION OF CASEWORK TYPES
CASEWORK SYMBOL
INDICATES LOCKS REQUIRED
4' - 10"
EQEQ
10.22 10.22
CL
CL
4' - 10"
EQ EQ
IN BACKGROUND
10.22
10.22
10.23
CL
CL
8' - 3"
270J 270H
8' - 8"
09.04
09.09
SF55A
OPEN
270G
SF55B
EQ EQ
7' - 6"
22.07
09.12
CL
15"56 3/4"15"
7 5/8"
D5
A581
TYP
06.08
11.1011.1011.10
30"
223 22306.07
11.10
09.13
TYP
TYP
156SF32 SF32156
17 1/4"
IN BACKGROUND
OPEN TO
BEYOND
11.10
10'-3 1/2"
10"
3"
10.3009.11
31'-6"
9'-8"
30"
60"
OPEN TO
BEYOND 06.08
11.10
D5
A582
______________
11.10
11.10
17"
17"
17"
21"
D4
A581
______________
109 3/8"24"
17"
17"
17"
21"
D4
A581
______________
16"63 1/8"
SF56
09.04
OPEN TO
BEYOND
272
5' - 0"
10.31 10.32 10.33 10.22
CLEQ EQ
CLEQ EQ
10.33
CLEQ EQ
CL
TYP ALL WALLS
32"
06.13
A1
A581
TYP
1'-0"
10.34
CL17' - 7 7/8"
CL EQEQ
10.22
5' - 0"
CL
5' - 0"
CLEQ EQ
10.33 10.3310.22OPEN TO
BEYONDCL
TYP ALL WALLS
32"
06.13
A1
A581
TYP
11.10
30"
222.1
D5
A581
TYP
17' - 11 1/4"
06.08
06.07
15"30"15"
09.13
11.10
TYP
TYP
30"
15"96 7/8"15"
11.10
D5
A581
TYP
06.08
223223
06.07
TYP
09.13
TYP
IN FOREGROUND
SF46
228
SF45
228
SF45
OPEN TO
BEYOND
06.06
09.113"
10"
10.30
20'-3 1/4"
1'-10"
280
11.10
30"
15"30"15"
OPEN TO
BEYOND06.08 D5
A581
TYP
11.10
223 223
06.07 11.10TYP
09.13
TYP
38"
24"24"24"24"
06.07
06.07
A2
A581
TYP
10.44
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
10/28/22
A421
Interior
Elevations
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
GENERAL NOTES - INTERIOR ELEVATIONS
1 GENERAL CONTRACTOR SHALL FIELD VERIFY ALL CONDITIONS AND SHALL REPORT TO THE ARCHITECT ANY UNKNOWN
CONDITIONS, ERRORS, OR CONFLICTS IN THE DRAWINGS BEFORE BEGINNING WORK
2 DO NOT SCALE DRAWINGS
3 SEE SHEET SERIES G000's FOR TYPICAL MOUNTING HEIGHTS. PROVIDE SOLID BLOCKING IN WALLS FOR ALL
WALL-MOUNTED ITEMS WHETHER BLOCKING IS DEPICTED IN DRAWINGS OR NOT
4 UPPER, LOWER, AND TALL MILLWORK CABINETS NOT TO EXCEED 36" IN WIDTH, UNLESS NOTED OTHERWISE
5 UNLESS NOTED OTHERWISE, MATCH UPPER CABINET WIDTH DIMENSIONS TO BASE CABINETS - TYPICAL
6 ALL ELECTRICAL AND DATA OUTLETS ABOVE COUNTER TOPS SHOULD BE HORIZONTALLY ALIGNED AND MOUNTED
HORIZONTALLY
7 PROVIDE SAFETY INSULATION ON ALL EXPOSED SUPPLY WATER LINES AND WASTE LINES
8 PROVIDE METAL TRIM AT ALL OUTSIDE EDGES ON TILE WALLS; SEE DETAILS AND FINISH SCHEDULE
9 PROVIDE METAL TRIM AT ALL TILE TO FLOOR TRANSITIONS; SEE DETAILS AND FINISH SCHEDULE
10 ALL MILLWORK INTERIOR FINISH TO BE WHITE MELAMINE, UNLESS NOTED OTHERWISE
11 CONTRACTOR TO PROVIDE RESTROOM ACCESSORIES; SEE ACCESSORY SCHEDULE
12 SEE AF600 SERIES FOR MATERIAL SPECIFICATIONS
13 SEE SHEET SERIES A500's FOR WALL AND ASSEMBLY TYPES
14 SEE SHEET SERIES A600's FOR DOOR AND WINDOW TYPES
15 SEE SHEET SERIES A500's FOR CASEWORK DETAILS
16 ALL SIGNAGE, LETTERING, GRAPHICS TO BE COORDINATED WITH OWNER PER CAMPUS GRAPHIC STANDARDS
1/4" = 1'-0"E1 STUDY SKILLS 252-NORTH
1/4" = 1'-0"E2 STUDY SKILLS 252 - WEST
1/4" = 1'-0"C1 STUDY 270G-J - WEST
1/4" = 1'-0"E3 LEVEL 3 RECESSED DRINKING FOUNTAIN
1/4" = 1'-0"D1 LEVEL 3 PRINT STATION
1/4" = 1'-0"D2 HALL 1-R - NORTH
1/4" = 1'-0"D3 HALL 1-S - WEST
1/4" = 1'-0"E4 STORAGE 252F - NORTH
1/4" = 1'-0"E5 STORAGE 252F - EAST
1/4" = 1'-0"C2 STUDY 270 G - SOUTH
1/4" = 1'-0"B1 OPEN TUTORING CENTER - EAST
1/4" = 1'-0"B4 OPEN TUTORING CENTER- SOUTH
1/4" = 1'-0"A1 OPEN TUTORING CENTER - WEST
1/4" = 1'-0"C3 OPEN STUDY 220 - NORTH
1/4" = 1'-0"D4 OPEN COMPUTERS 240 - NORTH
1/4" = 1'-0"A2 HALL 2-K - WEST
KEYED NOTES
06.06 WOOD VENEER, WV-01, RE: FINISH SCHEDULE
06.07 PLASTIC LAMINATE, PL-01, RE: FINISH SCHEDULE
06.08 PLASTIC LAMINATE, PL-02, RE: FINISH SCHEDULE
06.13 WOOD CHAIR RAIL, WHITE OAK, STAINED AND ROUTED TO MATCH ARCHITECT SAMPLE
09.04 PAINTED GYP, PNT-04, RE: FINISH SCHEDULE
09.09 WALL BASE, WB-03, RE: FINISH SCHEDULE
09.11 HATCH PATTERN INDICATES EXTENT OF FULL COLOR VINYL WALL GRAPHIC, SEE SIGN SCHEDULE, PREP WALL
WITH LEVEL 5 FINISH PRIOR TO INSTALLING VINYL
09.12 TILE WALL, TL-02, RE: FINISH SCHEDULE
09.13 WALL BASE, WB-04, RE: FINISH SCHEDULE
10.22 MARKER BOARD, 12'x 4', OFOI
10.23 CEILING MOUNTED PROJECTOR, OFOI, STEEL PIPE SUPPORT PROVIDED BY CONTRACTOR
10.30 SIGNAGE, SEE SIGNAGE SCHEDULE
10.31 MARKER BOARD, 8'x 4', OFOI
10.32 MARKER BOARD, 6'x 4', OFOI
10.33 MARKER BOARD, 4'x 4', OFOI
10.34 WALL MOUNTED PROJECTOR SCREEN, OFOI, BACKING PROVIDED BY CONTRACTOR, VERIFY MOUNTING HEIGHT
WITH MFGR REQ.
10.44 CEILING MOUNTED DISPLAY TV, OFOI, CONTRACTOR TO PROVIDE TV MOUNT AND SUPPORT AT CEILING
11.10 PRINTER, OFOI, RE: ACCESSORY SCHEDULE; POWER AND DATAT TO BE PROVIDED, RE:ELECTRICAL
22.07 HI LO DRINKING FOUNTAIN WITH BOTTLE FILLER - ADA COMPLIANT, RE: PLUMBING
1/4" = 1'-0"D5 LEVEL 2B PRINT STATION - SOUTH
1/4" = 1'-0"A5 JUVENILE 300 - SHELVING EAST
1/4" = 1'-0"B5 ENTRY HALL 120A - EAST
CASEWORK TAG
101M
AWS STANDARD CASEWORK TYPE
MODIFIED CASEWORK TYPE
REFER TO CASEWORK DESIGN SERIES (CDS) OF THE ARCHITECTURAL WOODWORK
STANDARDS (AWS) FOR A FULL DESCRIPTION OF CASEWORK TYPES
CASEWORK SYMBOL
INDICATES LOCKS REQUIRED
2' - 11 1/8"
TYP ALL WALLS
32"
06.12
A1
A581
TYP
06.1310.22 10.32
2 1/4"
TYP ALL WALLS
32"
5' - 0"
CL 10.31 10.3110.22
EQ EQ
CL
A1
A581
TYP
06.13
10.23
CL
8' - 0"
12' - 6"
252E
1'-6"9"IN BACKGROUND
C1
A581
______________
4'-0"
CL
IN BACKGROUND
10.42 10.42
TYP ALL WALLS
32"
A1
A581
TYP 06.13
36"
06.12
10.34
23'-3 3/8"
1'-0"
OF WINDOWS
ALIGN WITH BOTTOM
62 3/8"
10.4210.42
EQEQ
10.22 10.22
FILLER
1 1/2"
15"28 1/2"15"
30"
11.10
06.08
06.07
223 223
D5
A581
TYP
11.10
09.13
TYP
TYP
224.1
06.06
12.01
102102102102102102102
56 1/2"
29 1/2"
36"36"36"36"36"36"36"
B4
A581
35 1/4"3/4"34 1/8"1 1/2"
310
CLEQ EQ
5'-0"
CL 10.33
3'-10"
1'-6"9"
C1
A581
______________
402 230
36"15"
84"
30"
06.08
06.07
06.07
09.13
TYP 230 230 230 230
164"24"24"24"24"
30"
D5
A581
TYP
06.08
06.07
10.31
09.13
EQ 30"EQ
34"
06.07
D1
A582
______________
12.04
OPEN TO
BEYOND
5'-0"
8"
CL 10.29OPEN TO
BEYOND
6' - 0"
09.12
22.20
09.01
EQ EQ
FOR TILE WIDTH
RE: FLOOR PLAN
D3
A571
______________
D3
A571
______________D3
A571
______________
E5
A571
TYP
SF48 SF49OPEN TO
BEYOND
3"
10"
10.30 09.11
1'-10"
48'-9"
6'-10"
OPEN TO
BEYOND
498
3"
10"
09.1110.30
14'-5"
8'-8"
FILLER
30"24 13/16"
FILLER
24 5/8"30"1"
15"
33"
36"
302
152
12.04
06.07
09.13
22.17
11.02
E3
A582
06.07
11.05
302
10.06
10.03
3/4"
69"
3/4"
24 3/4"
11'-8"11'-8"
4'-7 1/4"14'-1 1/2"4'-7 1/4"
06.06
09.18
E5
A572
TYP
E5
A572
TYP
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
10/28/22
A422
Interior
Elevations
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
GENERAL NOTES - INTERIOR ELEVATIONS
1 GENERAL CONTRACTOR SHALL FIELD VERIFY ALL CONDITIONS AND SHALL REPORT TO THE ARCHITECT ANY UNKNOWN
CONDITIONS, ERRORS, OR CONFLICTS IN THE DRAWINGS BEFORE BEGINNING WORK
2 DO NOT SCALE DRAWINGS
3 SEE SHEET SERIES G000's FOR TYPICAL MOUNTING HEIGHTS. PROVIDE SOLID BLOCKING IN WALLS FOR ALL
WALL-MOUNTED ITEMS WHETHER BLOCKING IS DEPICTED IN DRAWINGS OR NOT
4 UPPER, LOWER, AND TALL MILLWORK CABINETS NOT TO EXCEED 36" IN WIDTH, UNLESS NOTED OTHERWISE
5 UNLESS NOTED OTHERWISE, MATCH UPPER CABINET WIDTH DIMENSIONS TO BASE CABINETS - TYPICAL
6 ALL ELECTRICAL AND DATA OUTLETS ABOVE COUNTER TOPS SHOULD BE HORIZONTALLY ALIGNED AND MOUNTED
HORIZONTALLY
7 PROVIDE SAFETY INSULATION ON ALL EXPOSED SUPPLY WATER LINES AND WASTE LINES
8 PROVIDE METAL TRIM AT ALL OUTSIDE EDGES ON TILE WALLS; SEE DETAILS AND FINISH SCHEDULE
9 PROVIDE METAL TRIM AT ALL TILE TO FLOOR TRANSITIONS; SEE DETAILS AND FINISH SCHEDULE
10 ALL MILLWORK INTERIOR FINISH TO BE WHITE MELAMINE, UNLESS NOTED OTHERWISE
11 CONTRACTOR TO PROVIDE RESTROOM ACCESSORIES; SEE ACCESSORY SCHEDULE
12 SEE AF600 SERIES FOR MATERIAL SPECIFICATIONS
13 SEE SHEET SERIES A500's FOR WALL AND ASSEMBLY TYPES
14 SEE SHEET SERIES A600's FOR DOOR AND WINDOW TYPES
15 SEE SHEET SERIES A500's FOR CASEWORK DETAILS
16 ALL SIGNAGE, LETTERING, GRAPHICS TO BE COORDINATED WITH OWNER PER CAMPUS GRAPHIC STANDARDS
1/4" = 1'-0"E2 LARGE COMPUTER CLASSROOM 234 - SOUTH
1/4" = 1'-0"E4 LARGE COMPUTER CLASSROOM 234 - WEST
KEYED NOTES
06.06 WOOD VENEER, WV-01, RE: FINISH SCHEDULE
06.07 PLASTIC LAMINATE, PL-01, RE: FINISH SCHEDULE
06.08 PLASTIC LAMINATE, PL-02, RE: FINISH SCHEDULE
06.12 TECH STATION OWNER PROVIDED OWNER INSTALLED
06.13 WOOD CHAIR RAIL, WHITE OAK, STAINED AND ROUTED TO MATCH ARCHITECT SAMPLE
09.01 PAINTED GYP, PNT-01, RE: FINISH SCHEDULE
09.11 HATCH PATTERN INDICATES EXTENT OF FULL COLOR VINYL WALL GRAPHIC, SEE SIGN SCHEDULE, PREP WALL
WITH LEVEL 5 FINISH PRIOR TO INSTALLING VINYL
09.12 TILE WALL, TL-02, RE: FINISH SCHEDULE
09.13 WALL BASE, WB-04, RE: FINISH SCHEDULE
09.18 WALLCOVERING, WC-02, RE: FINISH SCHEDULE
10.03 WALL MOUNTED SOAP DISPENSER, OWNER FURNISHED, OWNER INSTALLED
10.06 PAPER TOWEL DISPENSER, OWNER FURNISHED, OWNER INSTALLED
10.22 MARKER BOARD, 12'x 4', OFOI
10.23 CEILING MOUNTED PROJECTOR, OFOI, STEEL PIPE SUPPORT PROVIDED BY CONTRACTOR
10.29 TV, CONTRACTOR TO PROVIDE 3/4" SHEATHING FOR THE ENTIRE WALL, OFOI
10.30 SIGNAGE, SEE SIGNAGE SCHEDULE
10.31 MARKER BOARD, 8'x 4', OFOI
10.32 MARKER BOARD, 6'x 4', OFOI
10.33 MARKER BOARD, 4'x 4', OFOI
10.34 WALL MOUNTED PROJECTOR SCREEN, OFOI, BACKING PROVIDED BY CONTRACTOR, VERIFY MOUNTING HEIGHT
WITH MFGR REQ.
10.42 MARKER BOARD, 12'x 3'6", OFOI
11.02 UNDER CABINET REFRIGERATOR, OFOI
11.05 MICROWAVE, OFOI
11.10 PRINTER, OFOI, RE: ACCESSORY SCHEDULE; POWER AND DATAT TO BE PROVIDED, RE:ELECTRICAL
12.01 QUARTZ COUNTER TOP, ST-01, RE: FINISH SCHEDULE
12.04 QUARTZ COUNTER TOP, ST-02, RE: FINISH SCHEDULE
22.17 SINK, RE: PLUMBING
22.20 DRINKING FOUNTAIN TYPE VARIES, RE: FLOOR PLAN FOR TYPES, RE: PLUMBING
1/4" = 1'-0"D1 WRITING CENTER OPEN TUTORING 256 - NORTH
1/4" = 1'-0"C4 OFFICE 252E/TECH SERVICES 238 COAT HOOK
1/4" = 1'-0"C1 OFFICE 252E WHITE BOARD - WEST
1/4" = 1'-0"D2 DROP IN MATH LAB 170 - EAST
1/4" = 1'-0"E1 LARGE COMPUTER CLASSROOM 234 - NORTH
1/4" = 1'-0"C2 LEVEL 3 PRINT STATION - EAST
1/4" = 1'-0"C3 SPECIAL COLLECTIONS 228 - WEST
1/4" = 1'-0"C5 OFFICE 310 - EAST
1/4" = 1'-0"B1 OFFICE 310 - SOUTH
1/4" = 1'-0"B2 INTER LIBRARY LOAN WORK SPACE 114 - EAST
1/4" = 1'-0"B3 INTER LIBRARY LOAN WORK SPACE 114 - SOUTH
1/4" = 1'-0"B4 BOOK CHECK OUT LEVEL 3 - EAST
1/4" = 1'-0"B5 1B & 2B CORRIDOR TVS
1/4" = 1'-0"A1 TYP DRINKING FOUNTAIN
1/4" = 1'-0"A2 ENGLISH TRANSTION CENTER 288 - SOUTH
1/4" = 1'-0"A4 STUDY SKILLS 252 - N
1/4" = 1'-0"A5 FLEX SPACE 192 - NORTH
1/4" = 1'-0"D5 LEVEL 2A STAIR - NORTH
J
L
M
2 3 4 51.5
CLEAR
3'-8 1/4"8'-3"18'-1"5'-9"1'-8"25'-6"8'-10"
HD BOOK
COLLECTION
122
OPEN STUDY
122C
OPEN STUDY
122B
ENTRY HALL
120B
36'-0"
20'-6 1/2"
36"36"36"36"36"36"36"30"24"
36"36"36"36"36"36"36"30"24"
36"36"36"36"36"36"36"30"24"
36"36"36"36"36"36"36"30"24"
36"36"36"36"36"36"36"30"24"
36"36"36"36"36"36"36"30"24"
52"
30"24"24"
3 3/8"
25 1/4"
1 3/8"
36"36"36"36"30"24"
SHELVING WIDTH
25'-6"
TOTAL SHELVING WIDTH
26'-4"
7'-10"17'-8"
TYPICAL
26 5/8"
2'-0" OVERHANG2'-0" OVERHANG
5'-4 1/2"5'-4 1/2"5'-4 1/2"5'-4 1/2"
CLEAR
3'-8"
36"36"30"36"36"36"36"30"24"
36"36"30"36"36"36"36"30"24"
36"36"30"36"36"36"36"30"24"
36"36"30"36"36"36"36"30"24"
36"36"30"36"36"36"36"30"24"
36"36"30"36"36"36"36"30"24"
36"36"30"36"36"36"36"30"24"
36"36"30"36"36"36"36"30"24"
36"36"30"36"36"36"36"30"24"
36"36"30"36"36"36"36"30"24"
REQUIRED
20'-6 1/2"
27'-7 1/4"
53"
26 5/8"
2'-0"
6' - 7 3/4"5' - 3"5' - 3"5' - 3"5' - 3"
36"36"36"36"36"36"36"30"30"30"30"30"30"
11"
5'-4"
9'-10 3/4"
36"36"36"36"36"36"30"30"30"30"30"30"
36"36"36"36"36"36"36"30"30"30"30"30"30"
36"36"36"36"36"36"36"30"30"30"30"30"30"
36"36"36"36"36"36"36"30"30"30"30"30"30"
36"36"36"36"36"36"36"30"30"30"30"30"30"
4'-4 3/4"
36"36"36"36"36"36"36"30"30"30"30"30"30"
6'-4 3/4"6'-4 3/4"6'-4 3/4"6'-4 3/4"6'-4 3/4"
36"36"36"36"36"36"36"30"30"30"30"30"30"
36"36"36"36"36"36"30"30"30"30"30"30"
36"36"36"36"36"36"36"30"30"30"30"30"30"
36"36"36"36"36"36"36"30"30"30"30"30"30"
36"36"36"36"36"36"36"30"30"30"30"30"30"
36"36"36"36"36"36"36"30"30"30"30"30"30"
36"36"36"36"36"36"30"30"30"30"30"30"
36"36"36"36"36"36"36"30"30"30"30"30"30"
36"36"36"36"36"36"36"30"30"30"30"30"30"
36"36"36"36"36"36"36"30"30"30"30"30"30"
27'-7 1/4"
36'-0"
25'-0"
SHELVING WIDTH
36'-0"
TOTAL SHELVING WIDTH
36'-10"
2'-0" OVERHANG
A5
A431
______________
A5
A431
______________
A3
A431
______________
A3
A431
______________
A3
A431
______________
A3
A431
______________TYP.
TYP.
TYP.
TYP.A5
A431
______________
A5
A431
______________
1'-0"
1 1/2"
CONCRETE STRUCTURAL POUR BACK FOR HIGH
DENSITY SHELVING, SEE STRUCTURAL
SECOND CONCRETE POUR BACK - THIS OCCURS
AFTER HIGH DENSITY SHELVING RAILS HAVE BEEN
INSTALLED BY SHELVING CONTRACTOR
FINISH FLOOR AS SCHEDULED
INVERTED CHANNEL PROVIDED TO PROTECT RAIL
DURRING SECOND CONCRETE POUR
HIGH DENSITY SHELVING RAIL SYSTEM INSTALLED PER MFR
REQUIREMENTS COORDINATE WITH MFR
4 1/2"3"4 1/2"
1'-0"
CONCRETE STRUCTURAL POUR BACK FOR HIGH
DENSITY SHELVING, SEE STRUCTURAL
SECOND CONCRETE POUR BACK - THIS OCCURS
AFTER HIGH DENSITY SHELVING RAILS HAVE BEEN
INSTALLED BY SHELVING CONTRACTOR
FINISH FLOOR AS SCHEDULED
INVERTED CHANNEL PROVIDED TO PROTECT RAIL
DURRING SECOND CONCRETE POUR
HIGH DENSITY SHELVING RAIL SYSTEM INSTALLED PER
MFR REQUIREMENTS COORDINATE WITH MFR
8"
4 1/2"3"4 1/2"
CL
1'-2"
8"
2'-0"
EDGE OF CANTALIEVER FOR HIGH DENSITY SHELVING
6"
EXISTING CONCRETE FLOOR
EXISTING CONCRETE WALL MECHANICAL TUNNEL
STRUCTURAL REINFORCING AS REQUIRED BY
STRUCTURAL, SEE STRUCTURAL
RAIL
CL RAIL
10"
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
10/28/22
A431
High Density
Shelving
Equipment
Plan
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
1/4" = 1'-0"B2 Enlarged High Density Shelving Layout
3" = 1'-0"A5 HIGH DENSITY SHELVING RAIL DETAIL
3" = 1'-0"A3 HIGH DENSITY SHELVING RAIL DETAIL AT TUNNEL
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
10/28/22
A440
INTERIOR
RENDERINGS
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
1 1/2" = 1'-0"D1 TUTORING RECEPTION RENDERING
1 1/2" = 1'-0"D3 EAST ENTRY
1 1/2" = 1'-0"B1 LIBRARY CIRCULATION DESK
THE RENDERINGS SHOWN ARE A LOOSE REPRESENTATION ONLY AND ARE NOT TO BE USED FOR CONSTRUCTION PURPOSES
1 1/2" = 1'-0"B3 OPEN STUDY - AREA A
STEEL FRAMING
(RE: CORE SIZE LEGEND)
STEEL FRAMING
(RE: CORE SIZE LEGEND)
SEALANT (BOTH SIDES)
RUNNER TRACK
SOUND INSULATION TO DECK,
AS NOTED IN SCHEDULE BELOW
SILL
PLAN
FIRE RATING: SEE SCHEDULE
SOUND RATING (STC): SEE SCHEDULE
UL DESIGN NUMBER: SEE SCHEDULE
INTERIOR PARTITION
SA_
5/8" GYP. BOARD, TYPE X,
BOTH SIDES
STEEL FRAMING
(RE: CORE SIZE LEGEND)
STEEL FRAMING
(RE: CORE SIZE LEGEND)
SEALANT
RUNNER TRACK
SOUND INSULATION TO DECK,
AS NOTED IN SCHEDULE BELOW
SILL
PLAN
FIRE RATING: SEE SCHEDULE
SOUND RATING (STC): SEE SCHEDULE
UL DESIGN NUMBER: SEE SCHEDULE
INTERIOR PARTITION
SB_
5/8" GYP. BOARD, TYPE X
STEEL FRAMING
(RE: CORE SIZE LEGEND)
STEEL FRAMING
(RE: CORE SIZE LEGEND)
SEALANT
RUNNER TRACK
R-13- BATT INSULATION EXTEND TO
B.O. STRUCTURE / WAFFLE SLAB
SILL
PLAN
FIRE RATING: SEE SCHEDULE
SOUND RATING (STC): SEE SCHEDULE
UL DESIGN NUMBER: SEE SCHEDULE
INTERIOR PARTITION
SC_
5/8" GYP. BOARD, TYPE X
3" CLOSED CELL SPRAY FOAM INSULATION
R-15 MIN EXTEND TO B.O. STRUCTURE /
WAFFLE SLAB
EXISTING EXTERIOR MASONRY WALL
1/2"
STEEL FRAMING
(RE: CORE SIZE LEGEND)
STEEL FRAMING
(RE: CORE SIZE LEGEND)
SEALANT BOTH SIDES TYP.
RUNNER TRACK
SOUND INSULATION TO DECK,
AS NOTED IN SCHEDULE BELOW
SILL
PLAN
FIRE RATING: SEE SCHEDULE
SOUND RATING (STC): SEE SCHEDULE
UL DESIGN NUMBER: SEE SCHEDULE
INTERIOR PARTITION
SD_
5/8" GYP. BOARD, TYPE X
BOTH SIDES TYP.
3/4" PLYWOOD SHEATHING
STEEL FRAMING
(RE: CORE SIZE LEGEND)
STEEL FRAMING
(RE: CORE SIZE LEGEND)
SEALANT BOTH SIDES TYP.
RUNNER TRACK
SOUND INSULATION TO DECK,
AS NOTED IN SCHEDULE BELOW
SILL
PLAN
FIRE RATING: SEE SCHEDULE
SOUND RATING (STC): SEE SCHEDULE
UL DESIGN NUMBER: SEE SCHEDULE
INTERIOR PARTITION
SE_
3/4" PLYWOOD SHEATHING
BOTH SIDES TYP.
5/8" GYP. BOARD, TYPE X
BOTH SIDES TYP.
7/8" STEEL HAT CHANNEL
STEEL FRAMING
(RE: CORE SIZE LEGEND)
SEALANT
EXISTING WALL
SILL
PLAN
FIRE RATING: SEE SCHEDULE
SOUND RATING (STC): SEE SCHEDULE
UL DESIGN NUMBER: SEE SCHEDULE
INTERIOR PARTITION
SF_
5/8" GYP. BOARD, TYPE X
3/4" PLYWOOD SHEATHING
7/8" STEEL HAT CHANNEL
STEEL FRAMING
(RE: CORE SIZE LEGEND)
SEALANT
EXISTING WALL
SILL
PLAN
FIRE RATING: SEE SCHEDULE
SOUND RATING (STC): SEE SCHEDULE
UL DESIGN NUMBER: SEE SCHEDULE
INTERIOR PARTITION
SG_
5/8" GYP. BOARD, TYPE X
STEEL FRAMING
(RE: CORE SIZE LEGEND)
STEEL FRAMING
(RE: CORE SIZE LEGEND)
SEALANT (BOTH SIDES)
RUNNER TRACK
SOUND INSULATION TO DECK,
AS NOTED IN SCHEDULE BELOW
SILL
PLAN
FIRE RATING: SEE SCHEDULE
SOUND RATING (STC): SEE SCHEDULE
UL DESIGN NUMBER: SEE SCHEDULE
INTERIOR PARTITION
2SH_
2 LAYERS 5/8" GYP. BOARD,
TYPE X, BOTH SIDES
CORE SIZE LEGEND
C = CONCRETE WALLS, MASONRY
S = STEEL STUDS
W = WOOD STUDS
G = GLAZING
CORE MATERIAL LEGEND
STEEL STUDS
1 =A7/8"
2 = 1 5/8"
3 = 2 1/2"
4 = 3 5/8"
5 =
6 = 6"
8 = 8"
10 =
12 =
14 =
16 =
SUPERSCRIPT NOTES -
A - HAT CHANNEL FURRING IN LIEU OF METAL STUD
STEEL FRAMING
(RE: CORE SIZE LEGEND)
STEEL FRAMING
(RE: CORE SIZE LEGEND)
SEALANT
RUNNER TRACK
BATT INSULATION (R-13)
SILL
PLAN
FIRE RATING: SEE SCHEDULE
SOUND RATING (STC): SEE SCHEDULE
UL DESIGN NUMBER: SEE SCHEDULE
EXTERIOR PARTITION
ESA_
5/8" GYP. BOARD, TYPE X
RIGID INSULATION (R-10)
AIR BARRIER
ACM METAL PANEL SYSTEM
GYPSUM SHEATHING
1/2"
2 1/4"2"5/8"3 5/8"5/8"
FINISH COAT
PRIMER COAT
COMMERCIAL CEMENT PLASTER BASE
GALVANIZED SELF-FURRING LATH
EXTERIOR GYPSUM SHEATHING
FLUID APPLIED AIR BARRIER
EXISTING SOFFIT STEEL FRAMING TO REMAIN
R-38 BATT INSULATION
DRYVIT "CCP 2 COMMERCIAL CEMENT PLASTER"
SOFFIT SYSTEM
EXTEND GYP BOARD, ACOUSTICAL BATT INSULATION
AND STUD FRAMING INTO WAFFLE SLAB CEILING PANS
STUD FRAMING IN WALL AS SCHEDULED
EXISTING STRUCTURAL WAFFLE SLAB
ACOUSTICAL CAULK ENTIRE PERIMETER (BOTH SIDES) WHERE
GYP/STUD FRAMING MEETS CONCRETE WAFFLE SLAB - SEAL ALL
PENETRATIONS BOTH SIDES
(CAULK SHOWN AS DARK LINE)
DEFLECTION AND INNER SLIP TRACK TO
WITHSTAND LOADING & DEFLECTION
NOTE: ACOUSTICAL CAULK ALSO AT WALL JAMB
AND BASE CONDITION TYPICAL (BOTH SIDES)
SEAL ALL GAPS / PENETRATIONS
EXTEND GYP BOARD AND STUD FRAMING
TO B.O. WAFFLE SLAB CEILING
STUD FRAMING IN WALL AS SCHEDULED
EXISTING STRUCTURAL WAFFLE SLAB
CONT. DEFLECTION AND INNER SLIP TRACK TO
WITHSTAND LOADING & DEFLECTION
EXISTING WALL
SCHEDULED CEILING TILE - SEE RCP
STUD FRAMING AS SCHEDULED
CEILING EDGE TRIM
6"
STEEL FRAMING (RE: CORE SIZE LEGEND)
STEEL FRAMING
(RE: CORE SIZE LEGEND)
SEALANT (BOTH SIDES)
RUNNER TRACK
SOUND INSULATION TO DECK,
AS NOTED IN SCHEDULE BELOW
SILL
PLAN
FIRE RATING: SEE SCHEDULE
SOUND RATING (STC): SEE SCHEDULE
UL DESIGN NUMBER: SEE SCHEDULE
INTERIOR PARTITION
SJ_
5/8" GYP. BOARD, TYPE X
5/8" GYP. BOARD, TYPE X
15 MIL POLYFILM (OVERLAP FILM 6" MIN,
TAPE ALL SEAMS
5/8" GYP. BOARD, TYPE X
HU
M
I
D
I
T
Y
C
O
N
T
R
O
L
L
E
D
S
I
D
E
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
10/28/22
A501
Wall & Soffit
Assemblies
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
GENERAL NOTES - WALL TYPES
1 REFER TO A100's SHEET SERIES FOR LOCATION OF WALL TYPES
2 REFER TO SCHEDULES & DETAILS FOR FINISHES
3 "LINE OF STRUCTURE" AS SHOWN AT THE HEAD CONDITIONS OF EACH WALL TYPE IS DIAGRAMMATIC ONLY AND DOES
NOT INDICATE THE EXACT CONSTRUCTION CONDITION. RATED WALLS ARE TO TERMINATE AT STRUCTURAL MEMBERS
WITH A FIRE RESISTANT RATING. WHERE REQUIRED APPROPRIATE FRAMING AND GYP BOARD IS TO BE INSTALLED AND
OFFSET AROUND STRUCTURAL MEMBERS OR OTHER OBSTRUCTIONS SUCH AS PIPING OR DUCTWORK, TO MAINTAIN THE
FIRE RESISTANCE RATING. NON-RATED WALLS THAT CONTINUE TO STRUCTURE ARE TO TERMINATE AT PROPER
LOCATIONS TO MAINTAIN THE INTENT OF THE CONTINUOUS PLANE OF ONE LAYER OF GYP BOARD AS A NOISE, SMOKE OR
OTHER TYPE OF BARRIER. SEE HEAD AND SILL DETAILS FOR MORE INFORMATION
4 ALL GYP BOARD SHALL BE 5/8", UNLESS NOTED OTHERWISE
5 ALL RATED WALLS SHALL BE CONSTRUCTED FIRST AND HAVE CONTINUITY PRIORITY OVER NON-RATED WALLS.
SECONDARY, OR NON-RATED WALLS, ARE TO ABUTT, BUT NOT PENETRATE THE RATED WALLS
6 FIRESTOPPING TO BE PROVIDED AT ALL PENETRATIONS THROUGH RATED WALLS AS SPECIFIED. COORDINATE WITH
CODE PLANS
7 APPROPRIATE SUBMITTAL INFORMATION MUST BE PROVIDED TO SUBSTANTIATE THAT THE MATERIALS AND ASSEMBLY
USED BY THE CONTRACTOR HAVE BEEN TESTED BY A RECOGNIZED TESTING AGENCY TO MEET THE FIRE RESISTANCE
RATING SCHEDULED ON THESE WALL TYPES
8 ALL GYPSUM WALL BOARD MUST BE MOISTURE RESISTANT AT THE FOLLOWING LOCATIONS:
a. TOILET ROOMS
b. WET WALLS
c. SHOWERS
d. JANITOR'S CLOSETS
9 SOUND ATTENUATION BLANKETS SHALL EXTEND THE FULL HEIGHT OF THE WALLS
10 SPACING OF THE METAL STUDS HAS NOT BEEN INDICATED ON THE WALL TYPES OR DETAILS. STUD SPACING IS TO BE
DETERMINED BY THE HEIGHT OF THE PARTITION AS SHOWN IN THE TABLE ON SHEET A503. EACH STUD GOING TO
STRUCTURE AND EXCEEDING ALLOWABLE HEIGHTS SHALL BE BRACED 45
11 REFER TO INTERIOR DETAILS FOR ADDITIONAL INFORMATION
12 UL DESIGN NUMBERS REFER TO FIRE RESISTANCE IN MOST CURRENT EDITION OF THE UL DIRECTORY
13 IN PARTITIONS WITHOUT GYP BOARD ON BOTH SIDES, SUPPORT INSULATION WITH WIRE MESH TO STRUCTURE
14 MAINTAIN 1/2" SPACE BETWEEN FLOOR SLAB AND BOTTOM OF GYP BOARD ON ALL WALLS
15 STOP STUD 1" BELOW METAL RUNNER (TOP TRACK) TO ALLOW FOR VERTICAL EXPANSION; DO NOT ATTACH STUDS OR
GYP BOARD TO TOP TRACK
16 SEE STRUCTURAL DRAWINGS FOR EXTERIOR METAL STUD WALL SPACING, GAUGES, BRACING, AND CONNECTIONS
17 PROVIDE NEOPRENE FLASHING BETWEEN ALL DISSIMILAR METALS, TYPICAL
18 EXTERIOR SILL PLATES OR TRACKS TO BE SET IN 3 DISTINCT BEADS OF CONTINUOUS SEALANT
19 EIFS BASIS OF DESIGN - DRYVIT OUTSULATION PLUS MD OR EQUAL, SYSTEM SHALL BE INSTALLED PER MFR'S
RECOMMENDED INSTALLATION DETAILS
PARTITION
TAG
INSULATION
TYPE
FIRE
RATING
HEAD
DETAIL
STUD
DEPTH
CORE SIZE
(NOM.)
TOTAL
THICKNESS
LOAD
BEARING FIRE TEST
STC
RATING
SA4 R-13 BATT 3 5/8" 4 0' - 4 7/8"
SA4.1 3 5/8" 4 0' - 4 7/8"
SA4.1 NONE 3 5/8" 4 0' - 4 7/8"
SA6 6" 6 0' - 7 1/4"
SA6 R-13 BATT A5/A501 6" 6 0' - 7 1/4"
SA6.1 NONE 6" 6 0' - 7 1/4"
SA8 R-13 BATT 8" 8 0' - 9 1/4"
PARTITION
TAG
INSULATIO
N TYPE
FIRE
RATING
HEAD
DETAIL
STUD
DEPTH
CORE SIZE
(NOM.)
TOTAL
THICKNESS
LOAD
BEARING FIRE TEST
STC
RATING
SB1 NONE 7/8" 1 0' - 1 1/2"
SB2 NONE 1 5/8" 2 0' - 2 1/4"
SB2.1 NONE 1 5/8" 2 0' - 2 1/4"
SB3.1 NONE 2 1/2" 3 0' - 3 1/8"
SB4 R-13 BATT A5/A501 3 5/8" 4 0' - 4 1/4"
SB4.1 3 5/8" 4 0' - 4 1/4"
SB4.1 NONE 3 5/8" 4 0' - 4 1/4"
SB4.1 NONE B5/A501 3 5/8" 4 0' - 4 1/4"
PARTITION
TAG
INSULATION
TYPE
FIRE
RATING
HEAD
DETAIL
STUD
DEPTH
CORE SIZE
(NOM.)
TOTAL
THICKNESS
LOAD
BEARING FIRE TEST
STC
RATING
SC4 SPRAY/BATT D5/A551 3 5/8" 4 0' - 6 3/4"
SC6 SPRAY/BATT D5/A551 6" 6 0' - 11 1/8"
PARTITION
TAG
INSULATION
TYPE
FIRE
RATING
HEAD
DETAIL
STUD
DEPTH
CORE SIZE
(NOM.)
TOTAL
THICKNESS
LOAD
BEARING FIRE TEST
STC
RATING
SD4 R-13 BATT A5/A501 3 5/8" 4 0' - 5 5/8"
SD4.1 NONE B5/A501 3 5/8" 4 0' - 5 5/8"
SD6 R-13 BATT A5/A501 6" 6 0' - 7 3/4"
PARTITION
TAG
INSULATION
TYPE
FIRE
RATING
HEAD
DETAIL
STUD
DEPTH
CORE SIZE
(NOM.)
TOTAL
THICKNESS
LOAD
BEARING FIRE TEST
STC
RATING
SE4.1 NONE B5/A501 3 5/8" 4 0' - 6 3/8"
PARTITION
TAG
INSULATION
TYPE
FIRE
RATING
HEAD
DETAIL
STUD
DEPTH
CORE SIZE
(NOM.)
TOTAL
THICKNESS
LOAD
BEARING FIRE TEST
STC
RATING
SF1 NONE C6/A501 7/8" 1 0' - 2 1/4"
PARTITION
TAG
INSULATION
TYPE
FIRE
RATING
HEAD
DETAIL
STUD
DEPTH
CORE SIZE
(NOM.)
TOTAL
THICKNESS
LOAD
BEARING FIRE TEST
STC
RATING
SG1 NONE C6/A501 7/8" 1 0' - 1 1/2"
PARTITION
TAG
INSULATION
TYPE
FIRE
RATING
HEAD
DETAIL
STUD
DEPTH
CORE SIZE
(NOM.)
TOTAL
THICKNESS
LOAD
BEARING FIRE TEST
STC
RATING
2|2SH4 R-13 BATT 2 HR A5/A501 3 5/8" 4 0' - 6 1/8"
PARTITION
TAG
INSULATION
TYPE
FIRE
RATING
HEAD
DETAIL
STUD
DEPTH
CORE SIZE
(NOM.)
TOTAL
THICKNESS
LOAD
BEARING FIRE TEST
STC
RATING
ESA4 3 5/8" 4 <varies>
3/4" = 1'-0"B5 Acoustical Wall Head Termination at Waffle Slab Detail
3/4" = 1'-0"A5 Typical Wall Head Termination at Waffle Slab Detail
WHERE WALL IS FIRE RATED - PROVIDE FIRE CAULK IN LIEU OF ACOUSTICAL CAULK 1 1/2" = 1'-0"C6 Typical Furring Wall Head Termination Detail
BOTTOM TRACK -
SEE PARTITION
TYPE GENERAL
NOTE 21.
STUD - SEE WALL
SCHEDULE
JAMB BASE
ATTACHMENT - SEE
JAMB SCHEDULE
BOTTOM TRACK
ATTACHMENT -
SEE PARTITION
TYPE GENERAL 21.
JAMB STUDS - SEE
JAMB SCHEDULE
ADDITIONAL ANCHOR
AS REQ'D. BY JAMB
SCHEDULE
JAMB STUDS - SEE
JAMB SCHEDULE
JAMB BASE
ATTACHMENT - SEE
JAMB SCHEDULE
BOTTOM TRACK
ATTACHMENT -
SEE PARTITION
TYPE GENERAL 21.
BOTTOM TRACK -
SEE PARTITION
TYPE GENERAL
NOTE 21.
OPENING
ADDITIONAL ANCHOR
AS REQ'D. BY JAMB
SCHEDULEPLAN VIEW
BOTTOM TRACK -
SEE PARTITION
TYPE GENERAL
NOTE 21.
BOTTOM TRACK
ATTACHMENT - SEE
PARTITION TYPE GENERAL
21.
A
(1) #8 SCREW @ EACH
FLANGE
STUD - SEE
WALL
SCHEDULE
JAMB BASE CONNECTIONS
SCALE: NONE
TYPICAL BOTTOM TRACK CONNECTIONS
SCALE: NONE
TYPICAL STEEL STUD JAMB SECTIONS
SCALE: NONE
STANDARD FRAMING JAMB STUD SCHEDULE
TSN MID WALL SCHEDULE (W/ HANDRAIL LOAD):
TSN MID WALL SCHEDULE:
J1
ONE TRACK
ONE STUD
J2
ONE TRACK
TWO STUDS
J3
TWO TRACKS
TWO STUDS
J4
TWO TRACKS
THREE STUDS
MATCH WALL BOTTOM
TRACK & STUD SIZE TYPICAL
UNO
#10 @ 12" O.C. TYP
UNO
TOP CONNECTION TYPE 1 (DEFLECTION TRACK ATTACHMENT WITHOUT VERTICLIP)
SCALE: NONE
DEFLECTION TRACK
STUD
STURUCTURE
TRACK ATTACHMENT - SEE
PARTITION TYPES GENERAL
NOTES 22
ATTACH TO CONCRETE SLAB:
PARALLEL TO
FLUTE AT
FLUTE
STUD
DEFLECTION TRACK
STRUCTURE
TRACK ATTACHMENT -
SEE PARTITION TYPES GENERAL
NOTE 22. SEE DETAIL WITH
ADDITIONAL 68mil PLATE IF
OVERLAPPING <3"
ATTACH TO CONCRETE SLAB ON METAL
DECK:
PARALLEL TO
FLUTE BETWEEN
FLUTES
FIRE PROOFING IF
REQUIRED
TRACK ATTACHMENT -
SEE PARTITION TYPES GENERAL
NOTES 22.
68 MIL x 14" x CONTINUOUS PLATE W
(1) ROWS OF HILTI X-U @ 6" O.C.
EACH SIDE. EMBEDMENT = 1" MIN.
PERPENDICULAR TO
FLUTE
STUD
DEFLECTION TRACK
TRACK ATTACHMENT -
SEE PARTITION TYPES
GENERAL NOTES 22.
FIRE PROOFING IF
REQUIRED
PARALLEL TO
FLUTE AT
FLUTE
DEFLECTION TRACK
TRACK ATTACHMENT -
SEE PARTITION TYPES
GENERAL NOTES 22.
METAL DECK
PARALLEL TO
FLUTE BETWEEN
FLUTES
PERPENDICULAR TO
FLUTE
68 MIL x 8" x
CONTINUOUS PLATE W/ #
10 SCREWS EACH SIDE
@ 4" O.C.
FIRE PROOFING IF
REQUIRED
TRACK ATTACHMENT -
SEE PARTITION TYPES
GENERAL NOTES 22.
STUD
DEFLECTION TRACK
TRACK
ATTACHMENT -
SEE PARTITION
TYPES GENERAL
NOTES 22.
FIRE PROOFING IF
REQUIRED
ATTACH TO METAL DECK:
ATTACH TO STEEL BEAM:
STUD
HILTI X-U15 PAF'S AT 8"
O.C. STAGGERED
STEEL BEAM
STUD
HILTI X-U15 PAF'S AT 8"
O.C. STAGGERED
STEEL BEAM
54 MIL PLATE x 6" x 12"
AT 32" O.C.
(2) #10 SCREWS AT
EACH PLATE
STEEL BEAM
(2) HILTI X-U15
ANCHORS PER Z-CLIP
54 MIL Z-CLIP FOR
FIREPROOFING AT 32"
MAX. SPACING
DEFLECTION TRACK
STUD
TYPICAL STUD SPACING
WALL
HEIGHT
TYPICAL WALL STUD
TWO ADJACENT
MIDWALL™ SUPPORTS
REQUIRED AT TYPICAL
STUD SPACING FOR
END OF WALL
MIDWALL™
STANDARD TOP TRACK
STEEL BEAM
HILTI X-U15 PAF'S AT
8"O.C. STAGGERED
STUD
TSN VERTICLIP SLD AT EACH
JAMB W/ (2) #8 SCREWS IN
EACH JAMB & (2) #8 SCREWS
INTO TRACK
(2) HILTI X-U15 PAF'S AT
EACH PLATE
54 MIL PLATE x 6" x 12" AT 32"
O.C.
TSN VERTICLIP SLD AT EACH JAMB
W/ (2) #8 SCREWS IN EACH JAMB &
(2) #8 SCREWS INTO TRACK AND
PLATE
STUD
STEEL BEAM STEEL BEAM
(2) HILTI X-U15
ANCHORS PER Z-CLIP
54 MIL Z-CLIP FOR FIRE
PROOFING AT 32" MAX.
SPACING
DEFLECTION TRACK
STUD
ATTACH TO METAL DECK:
ATTACH TO STEEL BEAM:
TOP TRACK. EACH SIDE OF JAMB
CONNECTION (WHERE OCCURS). SEE
SS08 FOR DEFLECTION TRACK AND
SLOTTED TRACK INFORMATION
(1) #12 SCREWS PER FLUTE
METAL DECK
TSN VERTICLIP SLD AT EACH
JAMB W/ (2) #8 SCREWS IN
EACH JAMB & (2) #8
SCREWS INTO TRACK AND
PLATE
68 MIL x 12" x 25"
PLATE AT EACH
JAMB
JAMB STUD
TSN VERTICLIP SLD AT EACH
JAMB W/ (2) #8 SCREWS IN
EACH JAMB & (2) #8
SCREWS INTO TRACK
68 MIL x 12" x 25"
PLATE AT EACH
JAMB
TYPICAL STUD
(5) #12 SCREWS IN
EACH FLUTE - (10)
TOTAL
METAL DECK
DEFLECTION TRACK
JAMB STUDS
TRACK
PARALLEL TO
FLUTE AT FLUTE PERPENDICULAR TO
FLUTE
ATTACH TO CONCRETE SLAB ON METAL
DECK:
TRACK
(4) 3/8" HILTI KH-EZ ANCHOR
W/ 2-1/2" EMBEDMENT AT
EACH LOWER FLUTE
IF CLIP IS LOCATED PARTIALLY ON PLATE AND
ON CONCRETE, REPLACE SCREWS INTO
CONCRETE WITH 1/4" HILTI KH-EZ ANCHORS
WITH 2" MINIMUM EMBEDMENT
12"
TSN VERTICLIP SLD AT EACH
JAMB W/ (2) #8 SCREWS IN
EACH JAMB & (2) #8
SCREWS INTO TRACK AND
PLATE
JAMB STUD
DEFLECTION TRACK
CONCRETE SLAB ON METAL
DECK
68 MIL x 14" x 25"
PLATE AT EACH
JAMB
68 MIL x 14" x 25"
PLATE AT EACH
JAMB
DEFLECTION
TRACK
(4) 3/8" DIA. HILTI KH-
EZ ANCHORS W/
2-1/2" EMBEDMENT
IN EACH FLUTE. (4)
TOTAL.
CONCRETE SLAB
ON METAL DECK
TYPICAL STUD
JAMB STUDSTSN VERTICLIP SLD AT EACH
JAMB W/ (2) #8 SCREWS IN
EACH JAMB & (2) #8
SCREWS INTO TRACK AND
PLATE
12"
TRACK
TRACKPARALLEL TO
FLUTE AT FLUTE
PERPENDICULAR TO
FLUTE
ATTACH TO CONCRETE SLAB:
TOP CONNECTION TYPE 2 (DEFLECTION TRACK ATTACHMENT WITH VERTICLIP)
SCALE: NONE
NOTE:
• ONLY ONE CLIP IS REQ'D FOR JAMBS AT TYPICAL
LOCATION. WHERE JAMB CONFIG J3 AND J4 ARE
USED, THE CLIP MUST BE LOCATED AT THE
CENTER JAMB, OR TWO CLIPS MUST BE USE ONE
ON EACH SIDE OF BUILT UP JAMB
CONCRETE SLAB
DEFLECTION TRACK
TSN VERTICLIP SLD W/ (2) SLOTS
@ EACH JAMB W/ (2) #8 SCREWS
IN EACH JAMB & (2) 1/2" DIA.
HILTI HUS-EZ ANCHORS W/ 3"
EMBEDMENT
TYPICAL STUD
STUD TO FIT TIGHT
AGAINST RADIUS OF
TRACK
SECTION APLAN VIEW
MIDWALL SUPPORT DETAIL
SCALE: NONE
Typ. Stud Spacing Max Wall Height Mid Wall to base connection Comment
250MW-24: 16"O.C. 4'-0" 1/2" dia HAS-E Threaded Epoxy Anchor w/ HIT-HY 200. Embed=6"min For Concrete Slab only, EOR must deign base connection for concrete over metal deck application
24"O.C. 4'-0" 1/2" dia HAS Super Threaded Epoxy Anchor w/ HIT-HY 200. Embed=6"min For Concrete Slab only, EOR must deign base connection for concrete over metal deck application
250MW-48: 16"O.C. 7'-0" 1/2" dia HAS Super Threaded Epoxy Anchor w/ HIT-HY 200. Embed=6"min For Concrete Slab only, EOR must deign base connection for concrete over metal deck application
24"O.C. 5'-0" 1/2" dia HAS Super Threaded Epoxy Anchor w/ HIT-HY 200. Embed=6"min For Concrete Slab only, EOR must deign base connection for concrete over metal deck application
362MW-24: 16"O.C. 3'-6" (2) 3/8" dia Kwik Bolt 3. Embed=2.375" For Concrete over metal deck
4'-0" (2) 3/8" dia HAS-E Threaded Epoxy Anchor w/ HIT-HY 200. Embed=2.375"min For Concrete Slab
24"O.C. 3'-0" (2) 3/8" dia Kwik Bolt 3. Embed=2.375" For Concrete over metal deck
4'-0" (2) 3/8" dia HAS-E Threaded Epoxy Anchor w/ HIT-HY 200. Embed=2.375"min For Concrete Slab
362MW-48: 16"O.C. 8'-6" (2) 3/8" dia HAS Super Threaded Epoxy Anchor w/ HIT-HY 200. Embed=2.375"min For Concrete Slab only, EOR must deign base connection for concrete over metal deck application
24"O.C. 7'-6" (2) 3/8" dia HAS Super Threaded Epoxy Anchor w/ HIT-HY 200. Embed=2.375"min For Concrete Slab only, EOR must deign base connection for concrete over metal deck application
600MW-24: 16"O.C. 4'-0" (2) 3/8" dia Kwik Bolt 3. Embed=2.375" For Concrete over metal deck
(2) 3/8" dia HAS-E Threaded Epoxy Anchor w/ HIT-HY 200. Embed=2.375"min For Concrete Slab
24"O.C. 3'-6" (2) 3/8" dia Kwik Bolt 3. Embed=2.375" For Concrete over metal deck
4'-0" (2) 3/8" dia HAS-E Threaded Epoxy Anchor w/ HIT-HY 200. Embed=2.375"min For Concrete Slab
600MW-48: 16"O.C. 4'-6" (2) 3/8" dia Kwik Bolt 3. Embed=2.375" For Concrete over metal deck
10'-6" (2) 3/8" dia HAS Super Threaded Epoxy Anchor w/ HIT-HY 200. Embed=2.375"min For Concrete Slab
24"O.C. 9'-0" (2) 3/8" dia HAS Super Threaded Epoxy Anchor w/ HIT-HY 200. Embed=2.375"min For Concrete Slab only, EOR must deign base connection for concrete over metal deck application
Note: Max wall height are calculated base on one 5/8" GYP BD on each side
MidWall attaches to every other stud, studs attach to MidWall=xxxS162-54. All other typ stud=xxxS137-33, typ top track=xxxT125-33
Base connection based on concrete slab or concrete on metal deck with minimum compressive strength, f'c=3000psi
Typ. Stud Spacing Max Wall Height Mid Wall to base connection Comment
250MW-24: 16"O.C. 4'-0" 1/2" dia HAS Super Threaded Epoxy Anchor w/ HIT-HY 200. Embed=6"min to Concrete Slab For Concrete Slab only, EOR must deign base connection for concrete over metal deck application
250MW-48: 16"O.C. 7'-0" 1/2" dia HAS Super Threaded Epoxy Anchor w/ HIT-HY 200. Embed=6"min to Concrete Slab For Concrete Slab only, EOR must deign base connection for concrete over metal deck application
362MW-24: 16"O.C. 4'-0" (2) 3/8" dia HAS Super Threaded Epoxy Anchor w/ HIT-HY 200. Embed=2.375"min to Concrete Slab For Concrete Slab only, EOR must deign base connection for concrete over metal deck application
24"O.C. 4'-0" (2) 3/8" dia HAS Super Threaded Epoxy Anchor w/ HIT-HY 200. Embed=2.375"min to Concrete Slab For Concrete Slab only, EOR must deign base connection for concrete over metal deck application
362MW-48: 16"O.C. 8'-6" (2) 3/8" dia HAS Super Threaded Epoxy Anchor w/ HIT-HY 200. Embed=2.375"min to Concrete Slab For Concrete Slab only, EOR must deign base connection for concrete over metal deck application
24"O.C. 7'-0" (2) 3/8" dia HAS Super Threaded Epoxy Anchor w/ HIT-HY 200. Embed=2.375"min to Concrete Slab For Concrete Slab only, EOR must deign base connection for concrete over metal deck application
600MW-24: 16"O.C. 4'-0" (2) 3/8" dia HAS-E Threaded Epoxy Anchor w/ HIT-HY 200. Embed=2.375"min to Concrete Slab For Concrete Slab only, EOR must deign base connection for concrete over metal deck application
24"O.C. 4'-0" (2) 3/8" dia HAS-Super Threaded Epoxy Anchor w/ HIT-HY 200. Embed=2.375"min to Concrete Slab For Concrete Slab only, EOR must deign base connection for concrete over metal deck application
600MW-48: 16"O.C. 10'-6" (2) 3/8" dia HAS Super Threaded Epoxy Anchor w/ HIT-HY 200. Embed=2.375"min to Concrete Slab For Concrete Slab only, EOR must deign base connection for concrete over metal deck application
24"O.C. 9'-0" (2) 3/8" dia HAS Super Threaded Epoxy Anchor w/ HIT-HY 200. Embed=2.375"min to Concrete Slab For Concrete Slab only, EOR must deign base connection for concrete over metal deck application
Note: Max wall height are calculated base on one 5/8" GYP BD on each side
MidWall attaches to every other stud, studs attach to MidWall=xxxS162-54. All other typ stud=xxxS137-33, typ top track=xxxT125-33
Handrail loads (50plf or 200lb point live load) are applied at 3'-0" above the base connection
Base connection based on concrete slab or concrete on metal deck minimum compressive strength f'c=3000psi
JAMB DEPTH MAX. JAMB HEIGHT MAX. OPENING WIDTH JAMB COMPONENTS CONFIGURATION BASE CONNECTION TOP CONNECTION
2-1/2" 12'-0" 4'-0"(2)250S162-33 & (1)250T150-33 J2 (1) 3/8" HILTI KH-EZ w/ embed=3-1/4" (SOG) or 1-5/8" (COMD) Type 1
8'-0" (1 layer Gyp each side Max.) (2)250S162-33 & (1)250T125-54 J2 (1) 3/8" HILTI KH-EZ w/ embed=3-1/4" (SOG) or 1-5/8" (COMD) Type 2
12'-0" (1 layer Gyp 1 side Max.) (2)250S162-33 & (2)250T150-43 J3 (1) 3/8" HILTI KH-EZ w/ embed=3-1/4" (SOG) or 1-5/8" (COMD) Type 2
3-5/8" 10'-0" 4'-0"362S137-33 & 362T125-33 J1 (1) 3/8" HILTI KH-EZ w/ embed=3-1/4" (SOG) or 1-5/8" (COMD) Type 1
8'-0"362S137-33 & 362T125-33 J1 (1) 3/8" HILTI KH-EZ w/ embed=3-1/4" (SOG) or 1-5/8" (COMD) Type 2
12'-0"362S137-33 & 362T125-33 J1 (2) 3/8" HILTI KH-EZ w/ embed=3-1/4" (SOG) or 1-5/8" (COMD) Type 2
15'-0" 4'-0"362S137-33 & 362T125-33 J1 (1) 3/8" HILTI KH-EZ w/ embed=3-1/4" (SOG) or 1-5/8" (COMD) Type 1
8'-0"362S200-33 & 362T125-33 J1 (2) 3/8" HILTI KH-EZ w/ embed=3-1/4" (SOG) or 1-5/8" (COMD) Type 2
12'-0"(2)362S137-33 & (1)362T125-33 J2 (2) 3/8" HILTI KH-EZ w/ embed=3-1/4" (SOG) or 1-5/8" (COMD) Type 2
16'-0" (1 layer Gyp each side Max.) (2)362S137-33 & (2)362T125-33 J3 (2) 3/8" HILTI KH-EZ w/ embed=3-1/4" (SOG) or 1-5/8" (COMD) Type 2
18'-0" 4'-0"362S162-33 & 362T125-33 J1 (1) 3/8" HILTI KH-EZ w/ embed=3-1/4" (SOG) or 1-5/8" (COMD) Type 1
8'-0"(2)362S162-33 & (1)362T150-33 J2 (2) 3/8" HILTI KH-EZ w/ embed=3-1/4" (SOG) or 1-5/8" (COMD) Type 2
12'-0"(2)362S200-33 & (2)362T150-33 J3 (3) 3/8" HILTI KH-EZ w/ embed=3-1/4" (SOG) or 1-5/8" (COMD) Type 2
16'-0" (1 layer Gyp each side Max.) (3)362S200-33 & (2)362T150-33 J4 (1) 3/8" HILTI KH-EZ w/ embed=3-1/4" (SOG) or 1-5/8" (COMD) Type 2
6" 10'-0" 4'-0"600S137-33 & 600T125-33 J1 (1) 3/8" HILTI KH-EZ w/ embed=3-1/4" (SOG) or 1-5/8" (COMD) Type 1
8'-0"600S137-33 & 600T125-33 J1 (2) 3/8" HILTI KH-EZ w/ embed=3-1/4" (SOG) or 1-5/8" (COMD) Type 2
12'-0"600S137-33 & 600T125-33 J1 (2) 3/8" HILTI KH-EZ w/ embed=3-1/4" (SOG) or 1-5/8" (COMD) Type 2
16'-0"600S137-33 & 600T125-33 J1 (2) 3/8" HILTI KH-EZ w/ embed=3-1/4" (SOG) or 1-5/8" (COMD) Type 2
15'-0" 4'-0"600S137-33 & 600T125-33 J1 (2) 3/8" HILTI KH-EZ w/ embed=3-1/4" (SOG) or 1-5/8" (COMD) Type 1
8'-0"600S137-33 & 600T125-33 J1 (2) 3/8" HILTI KH-EZ w/ embed=3-1/4" (SOG) or 1-5/8" (COMD) Type 2
12'-0"600S137-33 & 600T125-33 J1 (3) 3/8" HILTI KH-EZ w/ embed=3-1/4" (SOG) or 1-5/8" (COMD) Type 2
16'-0"600S162-33 & 600T150-33 J1 (3) 3/8" HILTI KH-EZ w/ embed=3-1/4" (SOG) or 1-5/8" (COMD) Type 2
20'-0" 4'-0"600S137-33 & 600T125-33 J1 (2) 3/8" HILTI KH-EZ w/ embed=3-1/4" (SOG) or 1-5/8" (COMD) Type 1
8'-0"(2)600S137-33 & (1)600T125-33 J2 (3) 3/8" HILTI KH-EZ w/ embed=3-1/4" (SOG) or 1-5/8" (COMD) Type 2
12'-0"(2)600S137-33 & (1)600T125-33 J2 (3) 3/8" HILTI KH-EZ w/ embed=3-1/4" (SOG) or 1-5/8" (COMD) Type 2
16'-0"(2)600S162-33 & (2)600T150-33 J3 (3) 3/8" HILTI KH-EZ w/ embed=3-1/4" (SOG) or 1-5/8" (COMD) Type 2
25'-0" 4'-0"600S162-33 & 600T150-33 J1 (2) 3/8" HILTI KH-EZ w/ embed=3-1/4" (SOG) or 1-5/8" (COMD) Type 1
8'-0"(2)600S137-33 & (1)600T125-33 J2 (3) 3/8" HILTI KH-EZ w/ embed=3-1/4" (SOG) or 1-5/8" (COMD) Type 2
12'-0"(2)600S200-33 & (1)600T200-33 J2 (3) 3/8" HILTI KH-EZ w/ embed=3-1/4" (SOG) or 1-5/8" (COMD) Type 2
16'-0"(3)600S162-33 & (2)600T150-33 J4 (3) 3/8" HILTI KH-EZ w/ embed=3-1/4" (SOG) or 1-5/8" (COMD) Type 2
12" 50-0" 16'-8"(3)1200S350-118 & (2)1200T200-54 J4 (3) 3/8" HILTI KH-Fz w/ embed=3-1/4" (SOG) SEE DETAILS ATTACHED
NOTE: SOG=SLAB ON GRADE
COMD=CONCRETE ON METAL DECK
6" METAL STUD
SIMPSON RCKW5.5 @ 48" O.C. WITH
(6) #12 SCREWS TO STUD
(2) 3/8" Ø BY 2.5" TITEN HD ANCHOR
EXISTING CONCRETE FLOOR
SCHEDULED STOREFRONT WINDOW SYSTEM
A5
A561
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
10/28/22
A503
Structural
Steel Framing
Details
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
3" = 1'-0"D6 STRUCTURAL KNEE WALL ANCHOR DETAIL
WALL AS SCHEDULED BELOW
ADHERE GYP BD TO EXISTING MASONRY
EXISTING EXTERIOR WALL BELOW
EXISTING STOREFRONT
EXISTING STRUCTURAL COLUMN
SEALANT
WALL AS SCHEDULED
WALL BELOW AS SCHEDULED
EXISTING EXTERIOR
WALL BELOW
EXISTING STOREFRONT
EXISTING STRUCTURAL
COLUMN
ADHERE GYP BD TO
EXISTING MASONRY
TERMINATE SPRAY
INSULATION AT OUTSIDE EDGE
SEALANT BOTH SIDES, TYP.
SOLID SURFACE WINDOW SILL CAP,
SEE INTERIOR FINISHES
WALL AS SCHEDULED
WALL BELOW AS SCHEDULED
EXISTING WALL
EXISTING EXTERIOR
WALL BELOW
EXISTING STOREFRONT
EXISTING STRUCTURAL
COLUMN
ADHERE GYP BD TO
EXISTING MASONRY
TERMINATE SPRAY
INSULATION AT OUTSIDE EDGE
SEALANT
SOLID SURFACE WINDOW SILL CAP,
SEE INTERIOR FINISHES
WALL AS SCHEDULED
EXISTING STRUCTURAL
WALL AS SCHEDULED 1/2" GAP
1/2" GAP
WALL AS SCHEDULED
EXISTING STRUCTURAL
WALL AS SCHEDULED
1/2" GAP
ADHERE GYP BD TO
EXISTING COLUMN
WALL AS SCHEDULED
EXISTING STRUCTURAL
WALL AS SCHEDULED
1/2" GAP
ADHERE GYP BD TO
EXISTING COLUMN
WALL AS SCHEDULED
ADHERE GYP BD TO
EXISTING COLUMN
STOREFRONT SYSTEM, AS SCHEDULED
BACKER ROD AND SEALANT, BOTH SIDES
18 GA. ALUMINUM BREAK METAL
TO MATCH STOREFRONT RETURN ENDS
5/8" GYP. BD. OVER 3 5/8" FRAMING
HYDRONIC SUPPLY LINES, SEE PLUMBING
18 GA. ALUMINUM INFILL PANEL
TO MATCH STOREFRONT
RIGID INSULATION
BATT INSULATION
EXISTING SHAFT WALL
2 LAYERS OF TYP X 5/8" GYP,
BOTH SIDES
10" STUD FRAMING
EXISTING GYP. BOARD
ALIGN
INFILL WALL TO CONTINUE 2 HOUR RATED STAIR WELL ENCLOSURE
ALIGN
FIRE CAULK OR FIRE SAFE ALL PENENTRATIONS
1'-2" ±
SEE SPEC
PLAN
SEE G011.1
FOR MOUNTING HEIGHT
3" MAX
SECTION
SEMI-RECESSED
FIRE EXTINGUISHER
CABINET - SEE SPEC
PROVIDE RECESS
FOR F.E. CABINET AS
REQ'D - REFER TO
WALL TYPES FOR
WALL CONSTRUCTION
EXISTING COLUMN SEE STRUCTURAL
VINYL WALLCOVERING OVER
EXISTING FRAMED WALLS
NEW 1/4" GYP BD OVER EXISTING WALL
ON ALL EXPOSED WALL COVERING
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
10/28/22
A511
Plan Details
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set3/4" = 1'-0"A5 TYPICAL EXTERIOR COLUMN CORNER DETAIL
3/4" = 1'-0"E6 TYPICAL EXTERIOR COLUMN @ 2 STOREFRONT
3/4" = 1'-0"D6 TYPICAL EXTERIOR COLUMN @ 1 STOREFRONT
3/4" = 1'-0"A6 TYPICAL INTERIOR COLUMN
3/4" = 1'-0"B6 TYPICAL INTERIOR COLUMN @ 2 WALLS
3/4" = 1'-0"C6 TYPICAL INTERIOR COLUMN @ 3 WALLS
1 1/2" = 1'-0"B5 SNOWMELT PIPE CHASE DETAIL3/4" = 1'-0"B4 Stair Shaft Door Infill Detail
3/4" = 1'-0"A4 Semi-Recessed Fire Extinguisher Detail
3/4" = 1'-0"C5 TYPICAL INTERIOR COLUMN DETAIL
11 1_
2"
5'-3 3_
4"
Equal Equal
Acoustic barrier: two layers gypsum board, both sides,
with acoustic material to provide an equal/comparable
acoustic performance as the Skyfold partition (by others).
(Ref: ASTM E 557)
Typical
detail
Suspended ceiling
tile only (by others)LC
Lateral brace as
required (by others)
"J" or "U" trim
10'-
1"
11'-5 1_
2"A.F.F.
11'-6 1_
2"A.F.F.
B.
B.O. Acoustic barrier
T.O. Pocket
9" (REF)
Framing (by others) must not
interfere with motor unit, lifting
mechanisms & cables.
12'-7" A.F.F.
B.O. C8 x 11.5
ceiling0" A.F.F.
O. Pocket
Ceiling supports to be
attached to Structural
Framing before
construction of
acoustic barrier &
pocket
Skyfold wall
Acoustic barrier
11'-5 1_
2"A.F.F.
1"
B.O. Acoustic barrier
Structural Framing
(RE: STRUCTURAL)
Adapter plate
(by Skyfold)
12'-7" A.F.F.
B.O. C8 x 11.5
2'-1 3__
16"±
0.5 HP motor
maximum torque
4075 lbin.
Sh
a
f
t
3
3_4"
Motor unit weight (450 lbs ±) is
offset from wall centerline: 4 1_
4"±
17" min
clearance
required
6
1__16
"
CR
CL
CL
BRACKET
7 1/2"
GAGE
5"
SOFFIT
10 1/4"
FABRICATION HEIGHT
9'-0" DOOR OPENING HEIGHT
3/4"
1'-2 1/2"
STUD FRAMING
EXTEND 2 LAYERS OF 5/8" GYP. BOARD AND STUD FRAMING TO
DECK, PROVIDE ACOUSTICAL SEALANT TO SEAL ALL PENETRATIONS
0.5" DIA. X 9" LONG HANGER RODS BY MODERNFOLD
ROLLER CHAIN
HANGER BRACKET BY MODERNFOLD
STEEL, BALL BEARING TROLLEY
OFF WHITE BAKED ENAMEL SOFFIT TRIM PAN
BY MODERNFOLD
#14 GUIDE RAIL PRE-PAINTED OFF WHITE
VINYL TOP SEAL
FLOATING BOTTOM SEAL PROVIDES
3" OPERATING CLEARANCE (+.50" / -2.50")
FLOORING AS SCHEDULED
AC TILE CEILING AS SCHEDULED
GYP. BOARD SOFFIT
1'-5 1/4"
1'-0"
9"
ACOUSTICAL BATT INSULATION
LEVEL 02
114' - 0"
2'-9"
10'-0"
1'-0"
11'-0"
DASHED LINE REPRESENTS
DOOR IN POCKET
OPERABLE DOOR
DUCTING, SEE MECHANICAL
EXISTING ROOF STRUCTURE
STEEL BEAM, SEE STRUCTURAL
EXTEND STUD FRAMING AND GYP
BOARD TO DECK PROVIDE ACOUSTICAL
SEALANT TO SEAL ALL PENETRATIONS
FINISH FLOOR, SEE FINISH SCHEDULE
CONCRETE FLOOR, SEE STRUCTURAL
9'-0"
OPERABLE DOOR POCKET,
PAINT INTERIOR POCKET SAME
AS ADJACENT COLOR
C5
A512
10'-0" CEILING HEIGHT
A5
A512
B5
A512
TOP OF STEEL BEAM
12'-6"
B.O. POCKET 9'-0"
SKYFOLD OPERABLE DOOR
COORDINATE DUCTING, SEE MECHANICAL
EXISTING ROOF STRUCTURE
STEEL BEAM, SEE STRUCTURAL
EXTEND STUD FRAMING AND GYP
BOARD TO DECK PROVIDE ACOUSTICAL
SEALANT TO SEAL ALL PENETRATIONS
FINISH FLOOR, SEE FINISH SCHEDULE
CONCRETE FLOOR, SEE STRUCTURAL
POCKET DEPTH
1'-6 1/2"
TOP OF DOOR POCKET
10'-6 1/2"
CLEAR POCKET WIDTH
5'-3 3/4"
ACOUSTIC BARRIER, SEE DETAILS
SEAL AT ROOF STRUCTURE, ACOUSTICALLY
SEAL ALL PENETRATIONS, OPENINGS OR GAPS
3'-0"
CLEAR
4'-2"
CL
2'-1"2'-1"ALIGN WALLS TO FRONT FACE
OF CLOSED PANEL. FIELD VERIFY
AND CONSULT SHOP DRAWINGS.
INTERIOR OR DOOR POCKET TO BE PAINTED
TO MATCH ADJACENT / ROOM FINISH
CL
2'-5"
CLEAR
4'-4"
ALIGN WALLS TO FRONT FACE OF
CLOSED PANEL. FIELD VERIFY AND
CONSULT SHOP DRAWINGS.
INTERIOR OR DOOR
POCKET TO BE PAINTED
TO MATCH ADJACENT /
ROOM FINISH
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
10/28/22
A512
Details
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set3/4" = 1'-0"A5 SKYFOLD CEILING POCKET DETAIL
3/4" = 1'-0"B5 SKYFOLD MECHANICAL DETAIL
1 1/2" = 1'-0"C5 MODERNFOLD DETAIL
1/2" = 1'-0"A2 MODERNFOLD SECTION - LEVEL 2 AREA B
1/2" = 1'-0"A4 SKYFOLD SECTION - LEVEL 2 AREA B
1/2" = 1'-0"E6 MODERNFOLD 7 PANEL POCKET DETAIL
1/2" = 1'-0"E5 MODERNFOLD 5 PANEL POCKET DETAIL
F
CR
F
1/8" / 1'-0"
STOREFRONT GLAZING
C5
A513
C6
A513
EXISTING BRICK TO BE
REINSTALLED, SEE DETAILS
EXISTING EXTERIOR BRICK
B.O. STEEL/ BOTTOM OF DECK
FULLY ADHERED 60 MILL PVC OVER
VAPOR BARRIER, LAP AND ADHEAR INTO
COLLECTOR BOX
PREFINISHED METAL COUNTER FLASHING SEE SECTION DETAIL
STEEL DECKING, RE: STRUCTURAL
ACM PANEL SYSTEM
FLUID APPLIED AIR BARRIER
OVER GYPSUM SHEATHING
EL. 108' - 9"
FULLY ADHERED 60 MILL PVC MEMBRANE OVER AIR BARRIER
WRAP UP AND OVER PARAPET, WRAP INTO COLLECTOR BOX
ACM PANEL SYSTEM
FLUID APPLIED AIR BARRIER
ON GYPSUM SHEATHING
STEEL BEAM, SEE STRUCTURAL
2" DRAIN PIPE TO OVERFLOW
SCUPPER BELOW
4" STUD FRAMING
EL. 109' - 6"
T.O. ACM PANEL SYSTEM
EL. 108' - 9"
B.O. STEEL BEAM
COVER BOARD OVER SHAPED AND
TAPERED INSULATION - SLOPE TO DRAIN
GUTTER COLLECTOR BOX
FULLY ADHERED 60 MILL PVC WRAP UP WALL MIN 8"
STEEL BEAM, RE: STRUCTURAL
EXISTING EXTERIOR BRICK COLUMN
PREFINISHED METAL COUNTER FLASHING WITH DRIP, PREP
BRICK TO RECIEVE BARBED ATTACHMENT, SET IN SEALANT
B.O. STEEL/ BOTTOM OF DECK
FULLY ADHERED VAPOR BARRIER WRAP UP EXISTING BRICK COLUMN
PREFINISHED METAL COUNTER FLASHING
SEE SECTION DETAIL
EL. 108' - 9"
STEEL DECKING, RE: STRUCTURAL
ACM PANEL SYSTEM
FLUID APPLIED AIR BARRIER OVER
GYPSUM SHEATHING
1/2"
COVER BOARD OVER SHAPED AND TAPERED
INSULATION - SLOPE TO DRAIN
K
EXISTING BRICK AND BRICK LEDGER
RECTANGULAR STEEL TUBE, RE: STRUCTURAL
60 MILL PVC MEMBRANE WRAP UP WALL MIN 8"
6"X3" STEEL LINTEL ANGLE, RE: STRUCTURAL
INSTALL RECLAIMED BRICK FROM ENTRANCE DEMOLTITION
AS NEW BRICK SYSTEM, INCLUDING WEEPS, BRICK TIES,
AND PROPER DRAINAGE ELEMENTS
E5
A513
FLEXIBLE FLASHING UP AND OVER
PREFINISHED METAL COUNTER FLASHING WITH DRIP
EL. 108' - 9"
B.O. STEEL/ BOTTOM OF DECK
OUTSIDE BEAM TO OUTSIDE BEAM
1'-8 1/2"
1'-0"
ACM PANEL SYSTEM, COLOR TO MATCH
CLEAR ANODIZED STOREFRONT SYSTEM
C4
A513
FLUID APPLIED AIR BARRIER OVER GLASSMAT SHEATHING
LAP VAPOR BARRIER OVER FLUID APPLIED AIR BARRIER
PREFINISHED METAL COUNTER FLASHING WITH DRIP
LAP NEW FLUID APPLIED AIR BARRIER OVER EXISTING
WEATHER BARRIER WITH CHEMICALLY NEUTRAL TRANSITION
SLOPE
RIGID TAPERED INSULATION
ACM PANEL SYSTEM, COLOR TO MATCH
CLEAR ANODIZED STOREFRONT SYSTEM
SIM.
EL. 109' - 8 1/2"
B.O. STEEL LEDGER, COORDINATE WITH BRICK COURSING
12
K
1'-5"
1'-0 1/2"
8"
2'-3 1/2"
AL
I
G
N
ACM PANEL SYSTEM
RIGID INSULATION, SEE WALL TYPES
AIR BARRIER OVER
GLASS MAT SHEATHING
BATT INSULATION, SEE WALL TYPES
EXISTING STRUCTURAL COLUMN,
RE: STRUCTURAL
EXISTING EXTERIOR WALL
EXISTING INTERIOR WALL
ESA4A513A3
3/4" OPEN JOINT
SimB3
A513
E5
A513
LINE OF CANOPY ABOVE
FULLY RECESSED ADA ACTUATOR
FULLY RECESSED KNOX BOX
ABOVE
K
ACM PANEL SYSTEM
RIGID INSULATION, SEE WALL TYPES
AIR BARRIER OVER GLASS MAT SHEATHING
3 5/8" STUD FRAMING
ROOF DRAIN. RE: PLUMBING
EXISTING EXTERIOR WALL
COW TONGUE DOWNSPOUT
1'-5"
1'-1"
R-21 BATT INSULATION
AIR BARRIER OVER GLASS MAT SHEATHING
STRUCTURAL COLUMN
RE: STUCTURAL
BATT INSULATION, SEE WALL TYPES
E5
A513
1'-5 3/4"
SB4
LINE OF CANOPY ABOVE
ACM PANEL JOINT
ACM PANEL
17'-1"
1'-1"
9'-6"
1'-0"
A5
A513
C5
A513
C6
A513ACM PANEL SYSTEM FACIA
1-U.21-U.1
ACM PANEL JOINT
ACM PANEL SYSTEM
EXISTING BRICK COLUMN
FULLY RECESSED ADA ACTUATOR
3'-0"
FULLY RECESSED KNOX BOX
4'-6"
3'-4"
KNOX
BOX
3/4".
ACM PANEL SYSTEM
MASONRY WALL, RE: STRUCTURAL
FLUID APPLIED AIR & MOISTURE BARRIER
4" MINERAL WOOL BATT INSULATION
VERTICAL GIRT AND CLIP SYSTEM
4 1/2"2 1/4"
1" X 1" X 1/8" X 3/4"
LONG EXTRUSION (CORNER CLIP)
CORNER BRACE ATTACHED
TO VERTICAL AND HORIZONTAL
ALUMINUM EXTRUSION
SHIM AS REQUIRED
FASTENER:
EXPOSED SCREWS TO BE (S.B.A.)
[STAINLESS STEEL OR
PAINTED TO MATCH
ALUMINUM EXTRUSION]
LIGHT GAGE "Z" FRAMING
(1 1/2" x 1" x 1 1/4")
[SEE WALL TYPES]
ALUMINUM EXTRUSION WITH
1/8" WEEP HOLES TRIMMED
AT VERTICAL
ALUMINUM EXTRUSION
COLOR TO BE (S.B.A.)
*BOTH VERTICAL AND HORIZONTAL
ALUMINUM EXTRUSIONS MUST BE
STRUCTURALLY ATTACHED TO
THE WALL.
METAL PANEL
COLOR TO BE (S.B.A.)
3/4".
WATERTIGHT FULLY WELDED GUTTER COLLECTION BOX
2" DRAIN PIPE, WELDED TO BOTTOM OF COLLECTION
F U L L L E N G T H
3".
SLOPESLOPE
SL
O
P
E
SL
O
P
E
WATERTIGHT FULLY WELDED GUTTER COLLECTION BOX
2" DRAIN PIPE, WELDED AND
PLAN VIEW
AXONOMETRIC VIEW
SECTION VIEW
2" DRAIN PIPE, WELDED AND
WATERTIGHT FULLY WELDED
GUTTER COLLECTION BOX
PROVIDE DEBRIS SCREEN AT TOP OF PIPE
DEBRIS SCREEN
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
10/28/22
A513
Entrance
Details
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
3/4" = 1'-0"E5 CANOPY SECTION
3" = 1'-0"C5 CANOPY SECTION
3" = 1'-0"C6 CANOPY SECTION
1 1/2" = 1'-0"A5 EAST WING SOUTH VESTIBULE SHROUD DETAIL
1 1/2" = 1'-0"D3 SOUTHEAST VESTIBULE SHROUD PLAN DETAIL - EAST
1 1/2" = 1'-0"D1 SOUTHEAST VESTIBULE SHROUD PLAN DETAIL - WEST
1/4" = 1'-0"A1 EAST VESTIBULE
1/4" = 1'-0"A2 EAST WING SOUTH VESTIBULE ELEVATION-2
1/4" = 1'-0"A3 WEST VESTIBULE
1 1/2" = 1'-0"B3 ACM MASONRY WALL
6" = 1'-0"C4 ACM METAL PANEL VERTICAL JOINT
B1 EXTERIOR CANOPY 3D REFERENCE VIEW
3" = 1'-0"A4 GUTTER COLLECTOR BOX DETAIL
REVEAL
3/4"REVEAL
3/
8
"
FINISHED PLYWOOD PANEL BEYOND
PER LIGHT FIXTURE REQ.
3/4" PLYWOOD PANEL, WOOD VENEER
FINISH, WV-01; RE: FINISH SCHEDULE
LED INTERGRATED, TRIMLESS
LIGHT, RE: ELECTRICAL, LIGHT
TO BE ACCESSIBLE FOR
OCCASSIONAL MAINTENANCE;
RE: ELECTRICAL PLANS
REVEAL
3/4"
RE
V
EA
L
3/
8
"
FINISHED PLYWOOD PANEL BEYOND
3/4" PLYWOOD PANEL, WOOD VENEER
FINISH, WV-01; RE: FINISH SCHEDULE
MANUAL ROLLER SHADE SYSTEM,(RS-01) RE:
FINISH SCHEDULE. BREAK AT VERT. WINDOW
MULLION. FASTEN PER MANUF. SPEC'S
SNAPLOC FRONT FASCIA COVER: ARCH. TO
SELECT FINISH COLOR FROM MANUF.
STANDARD COLORS.
ALIGN
ANGLE BRACKET, AS REQ. BY
MANUFACTURER
CEILING (WHERE OCCURS), RE: RCP
RS-01, RE: FINISH SCHEDULE
AL
I
G
N
EXISTING WALL, TYPE VARIES
EXISTING WINDOW, HEIGHTS VARY, RE:
EXTERIOR ELEVATIONS FOR ROUGH
DIMENSIONS, CONTRACTOR TO FEILD VERIFY
ALL WINDOW DIMENSIONS FOR INSTALL
VARIES
PREP EXISTING CONCRETE FOR PAINT,
SEE FINISH SCHEDULE.
CLEAN AND REMOVE DEBRIS,
PREP FOR PAINT.3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
10/28/22
A514
Ceiling
Details
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
3" = 1'-0"E1 INTEGRATED LIGHT AT WOOD CEILING
3" = 1'-0"E2 WOOD CEILING REVEAL
3" = 1'-0"E3 MANUAL ROLLER SHADE AT INTERIOR STOREFRONT 3" = 1'-0"E4 MANUAL DUAL ROLLER SHADE
1 1/2" = 1'-0"E5 EXISTING CONCRETE & UNISTRUT DETAIL
GYP. VALANCE WALL ATTACHED TO
STRUCTURE ABOVE
SCHED. CEILING - SEE RCP FOR HEIGHT
CL
PAINT EXPOSED CONCRETE WAFFLE SLAB,
SEE FINISH SCHEDULE
AL
I
G
N
STRUCTURAL WAFFLE SLAB BEAM
MECHANICAL DUCT AS OCCURS,
SEE MECHANICAL.
GYP. FRAMED HEADER ATTACHED TO
STRUCTURE ABOVE
SCHED. CEILING - SEE RCP FOR HEIGHT
PAINT EXPOSED CONCRETE WAFFLE SLAB,
SEE FINISH SCHEDULE
AL
I
G
N
T
O
E
D
G
E
6"
2"
5/8" GYP BD (PAINTED) ON 3-5/8" METAL STUD
FRAMING, TYP.
SCHED. CEILING - SEE RCP FOR HEIGHT
SCHED. CEILING TILE - SEE RCP
FOR HEIGHT
3-5/8" METAL STUD BRACING
@ 16" O.C.
SHADOW MOLDING REVEAL BY MFR.
6"
GYP. FRAMED HEADER ATTACHED TO
STRUCTURE ABOVE
SCHED. CEILING - SEE RCP FOR HEIGHT
4"BREAK METAL TRIM,
PAINTED BLACK
2"
2"
3/8"
REVEAL
3/4"
3/4" PLYWOOD SUBSTRATE WITH WOOD
VENEER FINISH, WV-01; RE: FINISH
SCHEDULE, FINISHED AT ALL EXPOSED
EDGES
GYP. FRAMED HEADER ATTACHED TO
STRUCTURE ABOVE
BREAK METAL TRIM,
PAINTED BLACK
CLOUD TRIM,
BY MANUFACTURER
2"FOR CEILING HEIGHT
RE: RCP
4"
3/4" PLYWOOD SUBSTRATE WITH WOOD
VENEER FINISH, WV-01; RE: FINISH
SCHEDULE, FINISHED AT ALL EXPOSED
EDGES
REVEAL
3/4"
3/8"
GYP. FRAMED HEADER ATTACHED TO
STRUCTURE ABOVE
SCHED. CEILING TILE - SEE RCP
FOR HEIGHT
SHADOW MOLDING REVEAL BY MFR.,
BOTH SIDES
6"
SCHED. CEILING TILE - SEE RCP
FOR HEIGHT
6"
GYP. FRAMED HEADER ATTACHED TO
STRUCTURE ABOVE
SCHED. CEILING - SEE RCP FOR HEIGHT
CL
AL
I
G
N
STRUCTURAL WAFFLE SLAB BEAM
6"
SCHED. CEILING - SEE RCP FOR HEIGHT
2"4"
GYP. FRAMED HEADER ATTACHED TO
STRUCTURE ABOVE
SCHED. CEILING - SEE RCP FOR HEIGHT
CL
AL
I
G
N
STRUCTURAL WAFFLE SLAB BEAM
SCHED. CEILING - SEE RCP FOR HEIGHT
GYP. FRAMED HEADER ATTACHED TO
STRUCTURE ABOVE
SCHED. CEILING - SEE RCP FOR HEIGHT
CL
PAINT EXPOSED CONCRETE
WAFFLE SLAB,
SEE FINISH SCHEDULE
AL
I
G
N
STRUCTURAL WAFFLE SLAB BEAM
6"
2"
GYP. FRAMED HEADER ATTACHED TO
STRUCTURE ABOVE
WALL AS SCHEDULED
SCHED. CEILING - SEE RCP FOR HEIGHT
6"
BREAK METAL TRIM,
PAINTED BLACK 4"
2"3/4" PLYWOOD SUBSTRATE WITH WOOD
VENEER FINISH, WV-01; RE: FINISH
SCHEDULE, FINISHED AT ALL EXPOSED
EDGES
REVEAL
3/4"
3/8"
GYP. FRAMED HEADER ATTACHED TO
STRUCTURE ABOVE
CL STRUCTURAL WAFFLE SLAB BEAM
REVEAL
1/2"
6"
3/4" PLYWOOD SUBSTRATE WITH WOOD
VENEER FINISH, WV-01; RE: FINISH
SCHEDULE, ALL JOINTS TO BE MITERED
PAINTED GYP, PNT-02a, RE: FINISH
SCHEDULE
WOOD WRAP CONTINUES BEYOND, RE: PLAN
VIEW
RE: RCP FOR CEILING HEIGHT
RE: RCP
GYP. FRAMED HEADER ATTACHED TO
STRUCTURE ABOVE
SCHED. CEILING - SEE RCP FOR
HEIGHT
SHADOW MOLDING REVEAL BY MFR.
SCHED. CEILING - SEE RCP FOR
HEIGHT
6"
VARIES
VARIES
GYP. FRAMED HEADER (FLUSH) ATTACHED TO
STRUCTURE ABOVE
SCHED. CEILING - SEE RCP FOR
HEIGHT
SCHED. CEILING TILE - SEE RCP
FOR HEIGHT
SHADOW MOLDING REVEAL BY MFR.,
BOTH SIDES
6"
6" STUD GYP. FRAMED HEADER (FLUSH)
ATTACHED TO STRUCTURE ABOVE
SCHED. CEILING TILE - SEE RCP
FOR HEIGHT
SHADOW MOLDING REVEAL BY MFR.,
BOTH SIDES
6"
SCHED. CEILING TILE - SEE RCP
FOR HEIGHT
GYP. FRAMED HEADER ATTACHED TO
STRUCTURE ABOVE
SCHED. CEILING - SEE RCP FOR HEIGHT
CL
AL
I
G
N
STRUCTURAL WAFFLE SLAB BEAM
6"
2"4"
12 GA. HANGER SEE
SPECIFICATION
1 1/2" C.R. CHANNEL @
48" O.C.
5/8" TYPE 'X' GYP BD
3/4" FURRING CHANNELS @ 24" O.C.
x ;1 2'-0 " (M A X .)
x ;6 '-0 " M A X .
FIRST LINE OF BRACING 6'-0" OR LESS
FROM WALL BOUNDARY
CEILING SUSPENSION
SYSTEM
WALL
SPLAY WIRE
COMPRESSION POST
NOTE:
AREAS SMALLER THAN 144 SQ. FT. & WITH
WALLS ON FOUR SIDES EXTENDING TO THE
STRUCTURE NEED NOT BE BRACED. BOUNDARY
WALLS MUST BE BRACED TOP & BOTTOM
INDEPENDENT OF CEILING TO QUALIFY.
x
;
1
2
'
-
0
"
(
M
A
X
.
)
GYP. VALANCE WALL (FLAT FRAMED)
ATTACHED TO STRUCTURE ABOVE
SCHED. CEILING - SEE RCP FOR HEIGHT
CL CL
PAINT EXPOSED CONCRETE WAFFLE SLAB,
SEE FINISH SCHEDULE
AL
I
G
N
LINE OF GYP. BD HEADER BEYOND
STRUCTURAL WAFFLE SLAB BEAM
MECHANICAL EQUIPMENT,
RE: MECHANICAL
AL
I
G
N
GYP. FRAMED HEADER ATTACHED TO
STRUCTURE ABOVE
REVEAL
1/2"3/4" PLYWOOD SUBSTRATE WITH WOOD
VENEER FINISH, WV-01; RE: FINISH
SCHEDULE, ALL JOINTS TO BE MITERED
REVEAL
1/2"
PAINTED GYP, PNT-02a, RE: FINISH
SCHEDULE
WOOD WRAP CONTINUES BEYOND, RE: PLAN
VIEW
FOR CEILING HEIGHTS
RE: RCP
RE: RCP
GYP. FRAMED HEADER ATTACHED TO
STRUCTURE ABOVE
SCHED. CEILING - SEE RCP FOR HEIGHT
REVEAL
1/2"
WOOD WRAP: 3/4" PLYWOOD
SUBSTRATE WITH WOOD VENEER
FINISH, WV-01; RE: FINISH SCHEDULE,
ALL JOINTS TO BE MITERED
REVEAL
1/2"
PAINTED GYP, PNT-02a, RE: FINISH
SCHEDULE
WOOD WRAP CONTINUES BEYOND, RE: PLAN
VIEW
PAINTED EXPOSED EXISTING
STRUCTURAL WAFFLE SLAB
ATTACH WITH COLOR
MATCHED FACE FASTENERS
7/8" HAT CHANNEL / 1X FURRING STRIP
EQ.EQ.
ELEVATION
13'-6 1/2" A.F.F.
2 1/2"
STANDARD ACOUSTICAL PANEL MODUAL (APPROX 24"X24") WHERE WAFFLE
SLAB SIZE VARIES MODIFY ACOUSTICAL PANEL TO FIT AS SHOWN
EXPOSED SPRINKLER PIPING HELD DIRECTLY AGAINST CONCRETE FLANGE, PREP
AND PAINT ALL EXPOSED SPRINKLER PIPE AND ATTACHMENTS, WHERE OCCURS
EXISTING STRUCTURAL WAFFLE SLAB
ACOUSTICAL PANELS
SUSPENSION TEE
SUSPENSION WIRE
POKE THROUGH FLOOR BOX.
RE: ELECTRICAL.
PAINTED ALL EXPOSED ELECTRICAL
CONDUIT. ATTACH AND HOLD
TIGHT TO CONCRETE WEB/FLANGE.
RE: ELECTRICAL
CL
AL
I
G
N
STRUCTURAL WAFFLE SLAB BEAM
1 1/2"1 1/2"
PAINTED EXPOSED EXISTING
STRUCTURAL WAFFLE SLAB
ACOUSTICAL PANEL HELD TIGHT TO J-BOX
FACE FASTEN ACOUSTICAL
PANEL ON CLIP /STUD
PENDANT LIGHT FIXTURE, COORDINATE J-BOX TO
BE CENTERED IN WAFFLE SLAB RE: ELECTRICAL.
PAINTED ELECTRICAL CONDUIT. ATTACH AND HOLD
TIGHT TO CONCRETE WEB/FLANGE. RE: ELECTRICAL
CL
AL
I
G
N
STRUCTURAL WAFFLE
SLAB BEAM
CL STRUCTURAL WAFFLE
SLAB
EQ.EQ.
J-BOX COORDINATE WITH ELECTRICAL
GYP. FRAMED HEADER ATTACHED TO
STRUCTURE ABOVE
BREAK METAL TRIM,
PAINTED BLACK
CLOUD TRIM,
BY MANUFACTURER
2"FOR CEILING HEIGHTS
RE: RCP
4"
3"
3/4" PLYWOOD SUBSTRATE WITH WOOD
VENEER FINISH, WV-01; RE: FINISH
SCHEDULE, ALL JOINTS TO BE MITERED
REVEAL
1/2"
PAINTED GYP, PNT-02a, RE: FINISH
SCHEDULE
WOOD WRAP CONTINUES BEYOND, RE: PLAN
VIEW
GYP. FRAMED HEADER
ATTACHED TO
STRUCTURE ABOVE
BREAK METAL TRIM,
PAINTED BLACK
CLOUD TRIM,
BY MANUFACTURER,
WHITE
4"
GYP WALL, RE: ELEVATIONS
FOR FINISH
2"
2"
8 1/2"
8 1/2"
2"
GYP. BOARD, PAINTED
PNT-02a, SEE FINISH
SCHEDULE.
SCHED. CEILING -
SEE RCP FOR HEIGHT
EDGE OF DECORATIVE
CEILING BEYOND
1'-0"
GYP. BOARD AT REVEAL,
PAINTED PNT-04, SEE
FINISH SCHEDULE.
WOOD PANEL WRAP, EDGE
AT REVEAL TO MATCH
ANGLE, WOOD FINISHED AT
ALL EXPOSED EGES
GYP. BOARD, PAINTED
PNT-02a, SEE FINISH
SCHEDULE.
SCHED. CEILING -
SEE RCP FOR HEIGHT
EDGE OF DECORATIVE
CEILING BEYOND
GYP. BOARD AT
REAVEAL, PAINTED
PNT-04, SEE FINISH
SCHEDULE.
2"
1'-0"
WOOD PANEL WRAP, ALIGN WITH
EDGE OF REVEAL, WOOD
FINISHED AT ALL EXPOSED EDGES
GYP. FRAMED HEADER ATTACHED TO
STRUCTURE ABOVE
SCHED. CEILING - SEE RCP FOR HEIGHT
AL
I
G
N
T
O
E
D
G
E
PAINT EXPOSED CONCRETE WAFFLE SLAB,
SEE FINISH SCHEDULE
SCHED. CEILING TILE - SEE RCP
FOR HEIGHT
WALL AS SCHEDULED, RE: PLAN VIEW
INTERGRATED PICTURE RAIL TRACK,
MFGR: AS HANGING DIPSLAY SYSTEMS, DROP CEILING
TRACK #A1080HF, WHITE FINISH, RE: RCP FOR TRACK
EXTENTS
ANGLE BRACKET, AS REQ. BY
MANUFACTURER
CEILING (WHERE OCCURS), RE: RCP
RS-01, RE: FINISH SCHEDULE
AL
I
G
N
EXISTING WALL, TYPE VARIES
EXISTING WINDOW, HEIGHTS VARY, RE:
EXTERIOR ELEVATIONS FOR ROUGH
DIMENSIONS, CONTRACTOR TO FEILD VERIFY
ALL WINDOW DIMENSIONS FOR INSTALL
VARIES
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
10/28/22
A515
Ceiling
Details
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
3/4" = 1'-0"C5 Gyp. Framed Header @ Waffle Slab 2
3/4" = 1'-0"E4 Gyp. Framed Header @ Waffle Slab 7
1 1/2" = 1'-0"B5 Gyp to ACT 3
3/4" = 1'-0"A4 Gyp. Framed Header @ Waffle Slab 6
3/4" = 1'-0"C4 Gyp. Framed Header @ Waffle Slab 5
1 1/2" = 1'-0"C6 Gyp. Framed Header @ ACT Both Sides
3/4" = 1'-0"D4 Gyp. Framed Header @ Waffle Slab 3
3/4" = 1'-0"D5 Gyp. Framed Header @ Waffle Slab 8
3/4" = 1'-0"E5 Gyp. Framed Header @ Waffle Slab 1
3/4" = 1'-0"A3 Gyp. Framed Header @ Waffle Slab 10
3/4" = 1'-0"B4 Gyp. Framed Header @ Waffle Slab 9
1 1/2" = 1'-0"D6 Gyp. Framed Header @ ACT and Gyp. Bd.
1 1/2" = 1'-0"A5 Flush Gyp. @ ACT
1 1/2" = 1'-0"E6 Flush Gyp. Framed Header @ ACT Both Sides
3/4" = 1'-0"B3 Gyp. Framed Header @ Waffle Slab 4
1 1/2" = 1'-0"A6 Suspended Ceiling Channel Detail
1 1/2" = 1'-0"B6 Typical Suspended Ceiling Layout
3/4" = 1'-0"C3 MEP Ceiling Bridge Detail
3/4" = 1'-0"D3 Gyp. Framed Header @ Waffle Slab 11
3/4" = 1'-0"E3 Gyp. Framed Header @ Waffle Slab 12
3/4" = 1'-0"E2 Waffle Slab Baffle Detail
3/4" = 1'-0"D2 Waffle Slab Baffle Detail @ Floor Box
3/4" = 1'-0"E1 Waffle Slab Baffle Detail at Pendant Light
3/4" = 1'-0"D1 Gyp. Framed Header @ Waffle Slab 13
3/4" = 1'-0"A2 Gyp. Framed Header @ Waffle Slab 14
1 1/2" = 1'-0"C1 Angled Decorative Ceiling Reveal Detail
1 1/2" = 1'-0"C2 Straight Decorative Ceiling Slice Detail
3/4" = 1'-0"B2 Gyp. Framed Header @ Waffle Slab 15
1 1/2" = 1'-0"B1 INTERGRATED CEILING PICTURE RAIL
3" = 1'-0"A1 TYPICAL ROLLER SHADE DETAIL @ EXTERIOR WINDOWS
FBP
N
2"19'-8"2"
C4
A515
TYP
A4
A515
9' - 2"D2
C4
A515
TYP
26.01
TYP.6
2"
12'-11 1/4"
2"
TYP
4"
E1
A514
TYP
E2
A514
TYP
26.01
57 5/8"
36 1/2"
6 1/4"
54"
3/4"
3/4"
17 1/2"
3 3/4"
6 1/4"
3 3/4"
64"
3 3/4"
41 5/8"
E2
A514
TYP
3/4"
17 1/2"
3 3/4"
59 1/2"3 3/4"64 3/4"3 3/4"59 1/2"
3 3/4"
18 1/4"3/4"
12
K
1'-0 1/4"
6'-0 3/4"
1'-4 1/2"
6'-0 3/4"
1'-4 1/4"1'-1"
1' - 5"
11 3/4"
2' - 11 1/2"
5' - 5"
16'-1 1/4"
3/4" TYP.
C4
A513
C4
A513
ALIGN
EXISTING EXTERIOR
BRICK COLUMN
98
F
D3
A515
3'-0"
AL
I
G
N
3'-0"
10'-8 1/2"
13'-8 1/2"
8 3/4"
AL
I
G
N
3/4"15'-4 3/4"2"10"2"5'-4 3/4"
8 3/4"
22'-8"
D1 9' - 0"
TYP.
B1 10' - 0"
A1 10' - 0"
E3
A515
D3
A515
C2
A515
C2
A515
8 3/4"
8 3/4"1110
B4
A515
D3
A515
3' - 0"
5' - 1"
D1 9' - 0"
13'-0 1/2"
28' - 3 3/4"6"
ALIGN
1'-11 1/4"
8 1/2"
10"
9'-6 3/4"
2
"
2
"
2
"
3'-7 1/2"1'-7"1'-10 1/4"21'-3"
C1
A515
C2
A515
3 3/4"22'-0"11"
1312
F
2' - 9 3/4"9' - 4"
2'-6"
2"
1'-9 1/2"
2"
6 1/2"
2"
9'-1"
2'-6 1/2"2"
6 1/2"
2"
4'-11 1/2"
ALIGN
22'-9 1/2"
11' - 6 3/4"
23' - 8 1/2"
1' - 1 1/4"
7'-7 3/4"
8 3/4"
14'-5"
22'-9 1/2"
D3
A515
TYP.
B4
A515
TYP.
D1 9' - 0"
B1 10' - 0"
C1
A515
C1
A515
C2
A515
MIR
1211
B
2'-2"
3'-1 1/2"
2"
6 1/2"
2"
7'-0 1/4"
D1 9' - 0"
D1 9' - 0"
7'-10"
2"
2'-0 1/4"
6'-1 1/2"
2"
6 1/2"
2"
1'-10"
2"
4'-6"
6'-10 3/4"
6'-7 1/4"
10'-0 1/4"
23'-6"
1'-4"
1'-1 1/4"
4'-10 3/4"
10 3/4"
11'-0 1/4"
6"
6"
ALIGN
B4
A515
D3
A515
TYP.
TYP.
C1
A515
C2
A515
C2
A515
C1
A515
98
F
D3
A515
4'-2 1/4"
2"
3'-1 1/2"
2"
6 1/2"
2"
7'-7"
2' - 2 3/4"
2' - 5 3/4"
8'-6 1/2"22'-0"11 3/4"2"
3'-10"2"13'-0 3/4"
D3
A515
C4
A515
TYP
AL
I
G
N
15' - 11 1/4"
48'-9"
AL
I
G
N
D1 9' - 0"
D1 9' - 0"
B1 10' - 0"
ALIGN
A1 10' - 0"
A1 10' - 0"
D6
A515
C1
A515
C2
A515
C2
A515
C2
A515
2"11'-0 3/4"3'-2 1/4"
12
F
D3
A515
2'-6"2"
1'-3 1/2"
2"
6 1/2"
2"
8'-11 1/2"
3'-3 1/4"7'-9"
5'-0 1/4"
8'-9 1/4"
ALIGN
ALIGN
D1 9' - 0"
D3
A515
D3
A515
D3
A515
C1
A515
C2
A515
A5
A515
TYP
3'-7 1/2"1'-11 1/4"
TYP.
0' - 11 1/8"
TYP.
1' - 0"
5'-11 1/2"
TYP.
1' - 9 13/16"
TYP.
1' - 10 11/16"
3'-8 1/2"
2'-0 1/4"
6'-1 1/2"
B1 10' - 0"
CL
CL3'-0 3/4"
3'-0 3/4"
2'-11 3/4"2'-11 3/4"
4
D1
A515
TYP
5'-7 3/4"5'-7 3/4"
9'-7 1/4"
2"
2"
2"2"
D1 9' - 0"
2'-9"
1'-4"
5'-6 1/4"
6 1/2"
2"
2"
2"
C1
A515
C2
A515
M
4
C4
A515
TYP
21' - 10 3/4"7' - 5 3/4"1' - 6"
1'-6"
1'-2 3/4"
19'-0 3/4"
AL
I
G
N
D1 9' - 0"
C4
A515
TYP
C4
A515
TYP
370 1/2"
261 1/4"
A5
A515
TYP
4'-5 1/2"2'-10 3/4"
7'-9"
4'-5 1/2"
2'-10 3/4"
7'-9"
TYP.
EQ
TYP.
EQ
TYP.
EQ
TYP.
EQ
B1 10' - 0"
CL
CL
3'-10 1/2"
3'-10 1/2"
3'-10 1/2"3'-10 1/2"
EQ
EQ
EQ EQ
CENTER ALIGN LIGHTING WITHIN WAFFLE
SLAB, TYP.
EQ EQ CENTER ALIGN CONDUIT ON CONCRETE
WAFFLE SLAB WEB/FLANGES, TYP.
1 " T Y P .ACOUSTICAL PANELS WITH 1" RADIUS
CORNERS, TYP. SEE FINISH SCHEDULE.
11
D
D1 9' - 0"
A1 10' - 0"
E3
A515
D3
A5152'-5 3/4"
1'-0 3/4"
2' - 9 1/2"8 1/2"5' - 8 3/4"
20' - 11 1/4"11' - 3 3/4"
2"2"2"
C1
A515
C2
A515
2 1/2"
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
10/28/22
A516
Enlarged RCP
Details
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set1/4" = 1'-0"A4 CIRCULATION RECEPTION 110 - ENLARGED RCP
1/4" = 1'-0"E2 VESTIBULE 1-U - ENLARGED RCP
1/4" = 1'-0"A3 HALL 1-R - ENLARGED RCP
1/4" = 1'-0"A1 TUTORING ADMIN OPEN AREA 160 - ENLARGED RCP
1/4" = 1'-0"B5 MATH LAB RECEPTIONIST 175 / I.T. HELP DESK 176 - ENLARGED RCP
1/4" = 1'-0"B4 HALL 1-Y - ENLARGED RCP
1/4" = 1'-0"D4 STUDY SKILLS 252 / HALL 2-Q - ENLARGED RCP
1/4" = 1'-0"D3 RECEPTION 270A - ENLARGED RCP
1/4" = 1'-0"D2 OPEN STUDY 342 "PINWHEEL" - ENLARGED RCP
1/4" = 1'-0"D1 OPEN STUDY 383 - ENLARGED RCP
1/4" = 1'-0"B2 HALL 2-K - ENLARGED RCP
1/4" = 1'-0"B1 OPEN STUDY 220 "PINWHEEL" - ENLARGED RCP
1/4" = 1'-0"E1 TYPICAL RCP COORDINATION VIEW
1/4" = 1'-0"C1 OPEN TUTORING 254 - ENLARGED RCP
KEYED NOTES
26.01 LIGHT FIXTURE, RE: ELECT.
5/8" GYP. BOARD, SEE FINISH
SCHEDULE
WALL AS SCHEDULED
HOLLOW METAL FRAME
DOOR AS SCHEDULED
CONT. SEALANT BOTH SIDES, TYP.
5/8" GYP. BOARD, SEE FINISH
SCHEDULE
WALL AS SCHEDULED
HOLLOW METAL FRAME
DOOR AS SCHEDULED
CONT. SEALANT BOTH SIDES, TYP.
SIDE LIGHT OR SCHEDULED
WINDOW
METAL STUDS
HOLLOW METAL FRAME.
CONT. SEALANT BOTH SIDES
TYP.
WALL TYPE AS SCHEDULED
FRAME ANCHOR, RE:
SPECIFICATION
ALUMINUM FRAME. PER
DOOR SCHEDULE
DOOR AS SCHEDULED
SEALANT, EACH SIDE
PUSH SIDEPULL SIDE
PULL SIDEPUSH SIDE
SCHEDULED DOOR
STOREFRONT SYSTEM
SCHEDULED GLAZING
2 1/2"
WALL TYPE AS SCHEDULED
ALUMINUM FRAME. PER
DOOR SCHEDULE
DOOR AS SCHEDULED
SEALANT, EACH SIDE
SCHEDULED GLAZING
2 1/2"
PUSH SIDE
PULL SIDE
SCHEDULED DOOR
STOREFRONT SYSTEM
SIDE LIGHT OR SCHEDULED
WINDOW
METAL STUDS
HOLLOW METAL FRAME
CONT. SEALANT BOTH SIDES
TYP.
DOOR AS SCHEDULED,
HINGE SIDE
STOREFRONT SYSTEM
SHIM
BACKER ROD & SEALANT,
EACH SIDE
WALL AS SCHEDULED
STOREFRONT, SEE WINDOW TYPES
DOOR AS SCHEDULED,
HINGE SIDE
STOREFRONT SYSTEM
SHIM
BACKER ROD & SEALANT,
EACH SIDE
WALL AS SCHEDULED
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
10/28/22
A541
Door Details
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
GENERAL NOTES - DOORS
1 ALL HOLLOW METAL FRAMES AND DOORS ARE TO BE PAINTED IF NOT NOTED OTHERWISE MATCH ADJACENT WALL FINISH
2 ALL INTERIOR HOLLOW METAL FRAME WIDTHS ARE TO MATCH WALL WIDTHS; COORDINATE WITH VERTICAL ASSEMBLY
TYPES
3 WOOD GRAIN DIRECTION TO BE VERTICAL, UNLESS NOTED OTHERWISE
4 FINISH OF HOLLOW METAL FRAMES TO MATCH ADJACENT IF NOT NOTED OTHERWISE
5 IF COLOR TRANSITIONS OCCUR, THEY ARE TO OCCUR AT INSIDE OF FRAME STOP
6 DOORS SERVING SPACES WITH AN OCCUPANT LOAD OF 50 OR MORE SHALL NOT BE PROVIDED WITH A LATCH OR LOCK
OTHER THAN PANIC HARDWARE. SEE DOOR HARDWARE SPECIFICATIONS
3" = 1'-0"D5 HM DOOR JAMB AT GYP WALL DETAIL
3" = 1'-0"E5 HM DOOR HEAD AT METAL FRAMING DETAIL
3" = 1'-0"C5 HM DOOR JAMB AT GYP WALL SIDELITE
3" = 1'-0"E4 STOREFRONT DOOR HEAD AT GYP WALL - INT
3" = 1'-0"D4 STOREFRONT DOOR HEAD - INT
3" = 1'-0"C4 STOREFRONT DOOR JAMB AT GYP WALL - INT
3" = 1'-0"B4 STOREFRONT DOOR JAMB AT SIDELITE - INT
3" = 1'-0"A4 STOREFRONT DOOR JAMB AT SIDELITE - INT
3" = 1'-0"B5 STOREFRONT DOOR JAMB AT STEEL STUD
3" = 1'-0"A5 STOREFRONT DOOR JAMB AT STEEL STUD
EXISTING STOREFRONT GLAZING
WALL AS SCHEDULED
SNAP COVER TO CONCEAL FASTENERS
EXTRUDED ALUMINUM TO MATCH
EXISTING WINDOW SYSTEM FRAMING
PROVIDE THE "MULL IT OVER 60 WIDE"WALL TO
WINDOW TERMINATION SYSTEM
MATCH EXISTING STOREFRONT
MULLION DEPTH
COMPRESSIBLE GASKET
EXISTING STOREFRONT GLAZING
WALL AS SCHEDULED
SNAP COVER TO CONCEAL FASTENERS
EXTRUDED ALUMINUM TO MATCH
EXISTING WINDOW SYSTEM FRAMING
COMPRESSIBLE GASKET
MATCH EXISTING STOREFRONT MULLION DEPTH
EXISTING MULLION
PROVIDE THE "MULL IT OVER 60 CLASSIC"WALL TO
WINDOW TERMINATION SYSTEM
STOREFRONT, SEE WINDOW TYPES
SEALANT BOTH SIDES TYP.
EXISTING COLUMN
SHIM
CLOSED CELL BACKER ROD & SEALANT
BEHIND WINDOW WEEPS
STOREFRONT, SEE WINDOW TYPES
EXISTING CONCRETE SLAB, RE: STRUCTURAL
SHIM AS NEEDED
1'-0"
4"
STOREFRONT, SEE WINDOW TYPES
3 5/8" STUD FRAMING
BOOK DROP ASSEMBLY
CUSTOM BACK COVER PLATE 1/4" THICK CLEAR ANODIZED
ALUMINUM BACK PANEL TO MATCH STOREFRONT,
COORDINATE WITH BOOK DROP ASSEMBLY, EDGES OF COVER
PLATE TO ALIGNT WITH EDGES OF STOREFRONT FRAMING
STOREFRONT, SEE WINDOW TYPES
BATT INSULATION
TAMPER-PROOF COLOR MATCHED FASTENERS
EXISTING WALL
EXISTING STOREFRONT
SYSTEM
EXISTING WALL
WALL AS SCHEDULED
ACOUSTIC CEILING AS SCHEDULED
TERMINATE SPRAY INSULATION AT EDGE
ADHERE GYP BD TO EXISTING WALL
TERMINATE SPRAY INSULATION AT EDGE
BASE AS SCHEDULED
FLOOR FINISH AS SCHEDULED
CLEAR SEALANT
CLEAR SEALANT
1/2" OVERHANG
SPRAY INSULATION AS SCHEDULED
WINDOW SILL, TYP. SEE FINISH SCHEDULE
EXTEND SPRAY/BATT INSULATION TO B.O. WAFFLE SLAB
EXISTING WALL
WALL AS SCHEDULED
TERMINATE SPRAY INSULATION AT EDGE
ADHERE GYP BD TO EXISTING WALL
CLEAR SEALANT
1/2" OVERHANG
SPRAY INSULATION AS SCHEDULED
PROVIDE WINDOW SILL AT ALL EXTERIOR
GLAZING, TYP. SEE FINISH SCHEDULE
10" V.I.F.
EXISTING WALL WALL AS SCHEDULED
TERMINATE SPRAY INSULATION AT EDGE
ADHERE GYP BD TO EXISTING WALL
CLEAR SEALANT
1/2" OVERHANG
PROVIDE WINDOW SILL AT ALL EXTERIOR
GLAZING, TYP. SEE FINISH SCHEDULE
16" V.I.F.
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
10/28/22
A551
Exterior
Glazing
Details
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
1 1/2" = 1'-0"E6 WALL CONNECTION @ GLASS DETAIL
1 1/2" = 1'-0"E5 WALL CONNECTION @ MULLION DETAIL
3" = 1'-0"E4 EXTERIOR STOREFRONT JAMB @ COLUMN
3" = 1'-0"D4 TYP. EXTERIOR STOREFRONT SILL
1 1/2" = 1'-0"D6 Book Drop Section Detail
3/4" = 1'-0"D5 TYP. EXT. STOREFRONT HEAD AND SILL GB WRAP DETAIL
1 1/2" = 1'-0"C6 WINDOW SILL DETAIL A
1 1/2" = 1'-0"C5 WINDOW SILL DETAIL B
BUTT JOINT WITH STRUCTURAL SILICONE, TYP
SCHEDULED GLAZING
STOREFRONT, SEE WINDOW TYPES
SEALANT BOTH SIDES TYP.
EXISTING CONCRETE WALL
SHIM
SEALANT (ALL AROUND
FRAME)
SHIM
STOREFRONT, SEE WINDOW TYPES
WALL AS SCHEDULED
FILL WITH SPRAY FOAM OR
BATT INSULATION
5/8" GYP BOARD
STOREFRONT CORNER MULLION
SEALANT (ALL AROUND FRAME)
SHIM
STOREFRONT, SEE WINDOW TYPES
WALL AS SCHEDULED
INSULATION AS SCHEDULED,
SEE WALL TYPES
5/8" GYP BOARD
SEALANT (ALL AROUND FRAME)
SHIM
STOREFRONT, SEE WINDOW TYPES
WALL AS SCHEDULED
FILL WITH SPRAY FOAM OR
BATT INSULATION
5/8" GYP BOARD
HEADER, RE: STRUCTURAL
STOREFRONT, SEE WINDOW TYPES
STOREFRONT CORNER MULLION
SEALANT (ALL AROUND
FRAME)
SHIM
STOREFRONT, SEE WINDOW TYPES
WALL AS SCHEDULED
FILL WITH SPRAY FOAM OR
BATT INSULATION
5/8" GYP BOARD
CLOSED CELL BACKER ROD & SEALANT
BEHIND WINDOW WEEPS
STOREFRONT, SEE WINDOW TYPES
EXISTING CONCRETE SLAB, RE: STRUCTURAL
SHIM AS NEEDED
STOREFRONT, SEE WINDOW TYPES
SEALANT BOTH SIDES TYP.
EXISTING COLUMN
SHIM
EXISTING COLUMN WRAP
SEALANT (ALL AROUND
FRAME)
SHIM
STOREFRONT, SEE WINDOW TYPES
WALL AS SCHEDULED
FILL WITH SPRAY FOAM OR
BATT INSULATION
5/8" GYP BOARD
SEALANT (ALL AROUND
FRAME)
SHIM
STOREFRONT, SEE WINDOW TYPES
WALL AS SCHEDULED
FILL WITH SPRAY FOAM OR
BATT INSULATION
5/8" GYP BOARD
WALL TYPE AS SCHEDULED
ALUMINUM FRAME. PER
DOOR SCHEDULE
GLAZING AS SCHEDULED
SEALANT, EACH SIDETYPICAL
STUDY
ROOM
PAINT AND FINISH ALL
EXPOSED DRYWALL
PAINT AND FINISH ALL
DRYWALL SOFFIT
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
10/28/22
A561
Interior
Glazing
Details
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
3" = 1'-0"E6 TYP. INTERIOR FRAMELESS GLAZING BUTT JOINT
3" = 1'-0"E5 INT. STOREFRONT JAMB @ CONCRETE WALL
3" = 1'-0"D5 INT. STOREFRONT JAMB CORNER @ WALL
3" = 1'-0"A5 TYPICAL HALF WALL STOREFRONT SILL DETAIL
3" = 1'-0"C6 TYP. INTERIOR STOREFRONT HEAD
3" = 1'-0"D6 TYP. INTERIOR STOREFRONT JAMB CORNER
3" = 1'-0"B6 TYP. INTERIOR STOREFRONT JAMB
3" = 1'-0"A6 TYP. INTERIOR STOREFRONT SILL
3" = 1'-0"A4 INTERIOR STOREFRONT JAMB @ COLUMN
3" = 1'-0"B5 INTERIOR STOREFRONT JAMB @ WALL
3" = 1'-0"C5 INTERIOR STOREFRONT JAMB @ WALL END
3" = 1'-0"A2 STUDY ROOM HEADER DETAIL
EXISTING CONCRETE
FLOOR OVER DECK
FLOORING AS SCHEDULED
TRANSITION, TS-05, RE: FINISH
SCHEDULE
FLOORING AS SCHEDULED
SCHEDULED DOOR, AS
OCCURS.
EXISTING CONCRETE
FLOOR OVER DECK
SCHEDULED
FLOORING
TRANSITION TS-04, RE: FINISH
SCHEDULE
CONCRETE FLOOR AS
SCHEDULED
SCHEDULED DOOR, AS
OCCURS.
TRANSITION TS-03, RE: FINISH
SCHEDULE
MORTOR BED
SINGLE COMPONENT
GROUT
FINISH WALL MATERIAL; SEE
ELEVATION FOR TYPE
ALIGN
GYP. FACE WALL, RE: FINISH
FLOOR PLAN FOR FINISH.
EXISTING CONCRETE
FLOOR OVER DECK
TRANSITION TS-01, RE: FINISH
SCHEDULE
MORTAR BED
OVER CRACK ISOLATION
SINGLE COMPONENT
GROUT
PORCELAIN FLOOR TILE, RE: FINISH PLANS
SCHEDULED WALL FINISH, RE: FINISH PLANS + ELEVATIONS
EXISTING CONCRETE FLOOR
FLOORING AS SCHEDULED
TRANSITION TS-02, RE: FINISH
SCHEDULE
SCHEDULED DOOR, AS
OCCURS.
MORTAR BED
OVER CRACK ISOLATION
SINGLE COMPONENT
GROUT
SCHEDULED FLOOR TILE, RE: FINISH PLANS
SCHEDULED. WALL TILE, RE:
FINISH PLAN + ELEVATIONS
THINSET LATEX-PORTLAND CEMENT
MORTAR BOND COAT
WALL AS SCHED. SEE FLOOR PLAN
FOR TYPE
TRANSITION TS-03, RE: FINISH SCHEDULE
SCHEDULED. WALL TILE, RE:
FINISH PLAN + ELEVATIONS
SINGLE COMPONENT GROUT
BACKER BOARD
TRANSITION STRIP,TS-03 ; RE: FINISH
SCHEDULE
SCHEDULED WALL
TILE WALL, RE: ELEVATION
FOR TYPE
PAINTED GYP. SEE ELEVATION FOR
FINISH
WALL AS SCHEDULED,
RE: PLAN VIEW
3/4"W X 5/8"D GYP REVEAL,
BOD: FLANNER DWR
625-75, RUNS HORIZONTAL
AND VERTICAL; RE:
ELEVATION, PAINTED WITH
WALL FINISH
PAINTED GYP FINISH,
RE: ELEVATIONS FOR
TYPE
WALL AS SCHEDULED, RE: PLAN
VIEW
3/4" REGLET, FRY REGLET, MWU 7550,
ANODIZED ALUMINUM
PAINTED GYP FINISH, RE: ELEVATIONS FOR
TYPE
4" MDF WALL BASE, SQUARE EDGE, PAINTED
TO MATCH ADJACENT WALL, RE: ELEVATION
FOR PAINT COLOR
FINISHED FLOOR4 3/4"
ELECTRIC FIREPLACE; RE:
ACCESSORY SCHEDULE
4" BASE, WB-05; RE: FINISH SCHEDULE,
MILLWORK U CHANNEL, BOD: FRY REGLET,
MWU 7550, ANODIZED ALUMINUM
1'-9 3/4"
11 1/2"
1/8" KERF CUT REVEAL
PLYWOOD SHEETS, FACE WITH WV-01; RE
FINISH SCHEDULE
2"
ALIGN
3/4" SOLID WOOD END PIECE, WD-1: RE FINISH
SCHEDULE. TO MATCH ADJACENT WOOD
VENEER WALL PANEL. MOUNTED TO WALL AS
NEEDED, W/WOOD FILLER. PATCH TO MATCH
WOOD. 1/8"X1/8" KERF CUT AT SOLID WOOD TO
VENEER TRANSITION.
WALL AS SCHEDULED; SEE PLAN FOR
TYPE
EXISTING STONE WALL
WOOD FRAME, 3/4" PLYWOOD
SUBSTRATE FACED WITH WV-01; RE:
FINISH SCHEDULE, AT ALL EXPOSED
EDGES, MITER ALL CORNERS
WALL AS SCHEDULED, RE: PLAN
VIEW
FLUSH
RE: ELEVATION
STONE REVEAL
2 1/4"
3/4"W X 5/8"D GYP REVEAL, BOD: FLANNER DWR
625-75, RUNS HORIZONTAL AND VERTICAL; RE:
ELEVATION, PAINTED WITH WALL FINISH
EXISTING STONE WALL
WOOD FRAME, 3/4" PLYWOOD SUBSTRATE FACED
WITH WV-01; RE: FINISH SCHEDULE, AT ALL
EXPOSED EDGES, MITER ALL CORNERS
WALL AS SCHEDULED, RE: PLAN
VIEW
2 1/4"
1/2" PLYWOOD PANEL WITH WOOD VENEER
FINISH, WV-01; RE: FINISH SCHEDULE
BLOCKING/FURRING AT DEMO'D BULLETIN
BOARD RECESS
FLUSH
3/4"W X 5/8"D GYP REVEAL, BOD: FLANNER DWR
625-75, RUNS HORIZONTAL AND VERTICAL; RE:
ELEVATION, PAINTED WITH WALL FINISH
WOOD FRAME, 3/4" PLYWOOD SUBSTRATE FACED
WITH WV-01; RE: FINISH SCHEDULE, AT ALL
EXPOSED EDGES, MITER ALL CORNERS
EXISTING WALL
2 1/4"
1/2" PLYWOOD PANEL WITH WOOD VENEER
FINISH, WV-01; RE: FINISH SCHEDULE
BLOCKING/FURRING AT DEMO'D BULLETIN
BOARD RECESS
WALL AS SCHEDULED, RE: PLAN
VIEW
3/4" REGLET, FRY REGLET, MWU 7550,
ANODIZED ALUMINUM
3/4" PLYWOOD WITH VENEER FINISH, RE:
ELEVATION FOR FINISH TYPE
4" MDF WALL BASE WB-07; RE: FINISH
SCHEDULE
FINISHED FLOOR4"
3/4" PLYWOOD WITH WOOD
VENEER FINISH, WV-01; RE:
FINISH SCHEDULE
3/4" FRENCH CLEAT FROM
PLYWOOD MATERIAL
WALL AS SCHEDULED; RE: PLAN VIEW
FRAMING TO ACCOMODATE RECESSED LIGHT POCKETS;
RE: DETAIL ELEVATION VIEW
GLASS PANEL, VARIES; RE:
ELEVATION FOR FINISH TYPE
BUTT JOINT, WOOD FINISHED AT
ALL EXPOSED EDGES
LED TAPE LIGHT WITH CHANNELESS
LENS
B3
A571
NOTE: PRIOR TO FABRICATING ALL PANELS, CONTRACTOR TO BUILD
MOCK-UP IN PLACE TO REVIEW WITH ARCHITECT ON SITE TO ENSURE
ADEQUATE LIGHT DIFFUSION
A5;A571 + B3;A415
RE: ELEVATIONS FOR DIMENSIONS
TYPC1
A571
REVEAL
3/4"
REVEAL
3/8"
GLASS PANEL VARIES, RE: ELEVATIONS
FOR FINISH TYPE
2"
FINISHED PLYWOOD PANEL BEYOND RE: ELEVATION FOR DIMS
OPENING VARIES
2ND GYP LAYER
INTERIOR OF POCKET
TO BE PAINTED WHITE
METAL Z-CLIP AT ALL SIDES OF
GLASS TO FASTEN IN PLACE
NOTE: PRIOR TO FABRICATING ALL PANELS, CONTRACTOR TO BUILD MOCK-UP IN PLACE
TO REVIEW WITH ARCHITECT ON SITE TO ENSURE ADEQUATE LIGHT DIFFUSION
RUBBER GASKET
3/4" PLYWOOD PANEL, WOOD VENEER
FINISH, WV-01; RE: FINISH SCHEDULE
LED LIGHT, RE: ELECTRICAL,
LIGHT TO BE ACCESSIBLE FOR
OCCASSIONAL MAINTENANCE;
RE: ELECTRICAL PLANS
FRENCH CLEAT ATTACHMENT
4 3/4"
2' - 8"
3"
3"
4 3/4"
2' - 8"
4' - 1 1/2"
2' - 9 3/4"
3/4"
4' - 0"
3/4"
2' - 9 3/4"
4' - 5 1/4"5' - 8 1/2"4' - 5 1/4"
6' - 8"
5 1/2"
11 3/4"
5 1/2"
2' - 11 1/4"1' - 6"
3/4"
3"3"
1' - 6"
3/4"
6' - 8"
5 1/2"
4 3/4"
2' - 8"
3/4"
4' - 0"
3/4"
2' - 9 3/4"
4 3/4"
2' - 8"
4' - 1 1/2"
2' - 9 3/4"
2' - 0 3/4"
5 1/2"
B3
A571
______________
TYP.
B3
A571
______________
TYP.
B3
A571
______________
TYP.
EXISTING CONCRETE FLOOR
TS-06; RE: FINISH SCHEDULE
SCHEDULED WOOD FLOOR
SCHEDULED CARPET
OPERABLE PARTITION
DOOR AS SCHEDULED
4"
CL DOOR
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
10/28/22
A571
Interior
Details
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
3" = 1'-0"E2 Carpet to LVT
3" = 1'-0"E1 Carpet To Concrete
3" = 1'-0"E6 Edge Trim @ Outside Corner
3" = 1'-0"E5 Metal Cove Base- Tile to Tile
3" = 1'-0"D1 Tile To Carpet
3" = 1'-0"D2 Tile To Tile @ Outside Corner
3" = 1'-0"D3 TILE EDGE DETAIL
3" = 1'-0"D5 TYPICAL GYP REVEAL
3" = 1'-0"D6 RECESSED WOOD BASE REVEAL
1 1/2" = 1'-0"B6 RECESSED FIREPLACE AND WALL BASE SECTION
3" = 1'-0"C1 WOOD VENEER TO PAINTED GYP. CORNER
3" = 1'-0"C3 WOOD FRAME REVEAL
3" = 1'-0"C4 WOOD FRAME REVEAL WITH WOOD BACKING
3" = 1'-0"B1 WOOD FRAME WOOD EACH SIDE
3" = 1'-0"B2 WOOD WALL BASE @WOOD PANEL WALL
1" = 1'-0"A1 CIRCULATION RECEPTION WALL SECTION
3" = 1'-0"B3
CIRCULATION RECEPTION WALL REVEAL/GLASS INSERT ENLARGED
DETAIL
1/2" = 1'-0"A5 CIRCULATION RECEPTION WALL RECESSED OPENING ELEVATION
3" = 1'-0"C2 WOOD FLOOR TO CARPET
DISPLAY REVEAL: AS HANGING DISPLAY
SYSTEMS, #A1025, STANDARD FINISH,
ALIGN WITH ADJACENT DROPPED
CEILING
WOOD FRAME, 3/4" PLYWOOD SUBSTRATE FACED
WITH WV-01; RE: FINISH SCHEDULE, AT ALL
EXPOSED EDGES, MITER ALL CORNERS
WALL AS SCHEDULED, RE: PLAN VIEW
BULLETIN BOARD MATERIAL, WC-02; RE:
FINISH SCHEDULE
3/4"
4"
WOOD SLAT WALL PANEL,
SP-03, RE: FINISH SCHEDULE
WOOD FRAME BEYOND
NOTE: BACK WALL MATERIAL ORIENTATION VAIES, RE:
ELEVATIONS FOR LOCATIONS
WOOD FRAME, 3/4" PLYWOOD SUBSTRATE FACED
WITH WV-01; RE: FINISH SCHEDULE, AT ALL
EXPOSED EDGES, MITER ALL CORNERS
WALL AS SCHEDULED; RE: PLAN VIEW
WOOD FRAME BEYOND
BACK MATERIAL VARIES, RE:
ELEVATION
WOOD FRAME, 3/4" PLYWOOD SUBSTRATE FACED
WITH WV-01; RE: FINISH SCHEDULE, AT ALL
EXPOSED EDGES, MITER ALL CORNERS
WALL AS SCHEDULED, RE: PLAN VIEW
BLOCKING AS NEEDED
8"
RE: ELEVATION
WOOD FRAME BEYOND
WHITE BOARD WALL RE: ELEVATION
FOR FINISH TYPE
8"
SCHED. CARPET, RE: FINISH PLANS STAIR NOSING, TS-07; RE: FINISH SCHEDULE
EXISTING STAIRS
WOOD FRAME, 3/4" PLYWOOD SUBSTRATE FACED
WITH WV-01; RE: FINISH SCHEDULE, AT ALL
EXPOSED EDGES, MITER ALL CORNERS
EXISTING BRICK WALL
WOOD FRAME BEYOND
BULLETIN BOARD MATERIAL, RE:
ELEVATION FOR FINISH TYPE
3/4" PLYWOOD SHEATHING
4"
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
10/28/22
A572
Interior
Details
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
1 1/2" = 1'-0"E1 RECESSED PICTURE DISPLAY RAIL
3" = 1'-0"E2 WOOD FRAMED DISPLAY WALL - DETAIL 1
3" = 1'-0"E3 WOOD FRAMED DISPLAY WALL - DETAIL 2
1 1/2" = 1'-0"D1 OPEN STUDY WALL TALKER CASING
6" = 1'-0"E4 STAIR NOSING
3" = 1'-0"E5 WOOD FRAMED BULLETIN BOARD
SEE FLOOR PLAN FOR WALL TYPES
FINISHED FLOOR
FAUCET - REFER TO PLUMBING
24"
RE: ELEVATION
COUNTERTOP: SOLID SURFACE COUNTERTOP W/
PLYWOOD SUBSTRATE, RE: ELEVATION FOR FINISH
TYPE, EASED EDGE, MITER OUTSIDE CORNER,
FINISHED ON ALL EXPOSED SIDES, SCRIBE TIGHTLY
TO WALL, SEAL SEAMS WITH MATCHING SILICONE,
MATCHING 4" BACKSPLASH, WHERE OCCURS, RE:
ELEVATIONS FOR LOCATIONS
UNDER MOUNT SINK, SEE PLUMBING
UNDER SINK LAVATORY GUARD FOR ALL EXPOSED
PIPING
FULL CONCEALED STEEL SUPPORT BRACKET
FINISH TO MATCH ADJACENT WALL COLOR/FINISH (WHERE
EXPOSED)
MIN. CLEARANCE
27"
EQ 1"EQ
(4) #12 SDS SCREWS
7"
RE: ELEVATION
4"
4"
10 1/2"
SPECIFIED PRODUCT
VERIFY W/
1 1/2"
COUNTERTOP: RE: ELEVATIONS FOR
FINISH TYPE, MATCHING 4"
BACKSPLASH WHERE OCCURS
MICROWAVE, OFOI, COORDINATE
MICROWAVE SIZE WITH ARCHITECT +
OWNER DURING SUBMITTAL
DRAWER: 3/4" MDF CORE, WHITE
MELAMINE INTERIOR. DRAWER PANEL
FINISHED WITH PLASTIC LAMINATE, RE:
ELEVATION FOR FINISH TYPE
BASE AS SCHEDULED, RE: ELEVATIONS
FOR TYPE
FINISHED FLOOR, RE: PLAN.
WALL AS SCHEDULED; RE: PLAN.
CABINET PULL: AMEROCK EDGE PULL,
3.75", SATIN NICKEL
2' - 0"
3"
POWER, RE: ELECTRICAL,
DEDICATED
MICROWAVE OPENING,
WHITE MELAMINTE FINISH
1' - 0"
3/4"
SHELF: 3/4" PLYWOOD WITH WHITE MELAMINE
FINISH, MATCHING PVC EDGEBANDING AT
EXPOSED EDGES
ADJUSTABLE SHELVING BRACKET AND
CORRESPONDING VERTICAL RAIL, INSTALLATION PER
MANUFACTURER'S INSTRUCTIONS, RAIL SPACING PER
MANUFACTURER'S RECOMMENDATION
PROVIDE BLOCKING/SHEATHING AS NEEDED
RE: ELEVATION FOR HEIGHT AFF
DESK BELOW
1' - 3"
POWER PROVIDED FOR COMPUTER
MONITORS AT DESK AND SHELF
COMPUTER MONITOR AT SHELF
COMPUTER MONITOR AT DESK
WALL AS SCHEDULED; SEE FLOOR PLAN FOR
WALL TYPES
FINISHED FLOOR
COUNTERTOP: 3/4" PLYWOOD SUBSTRATE WITH LAMINATE
FINISH, RE: ELEVATION FOR FINISH TYPE, MATCHING 3MM
PVC EDGE BANDING AT EXPOSED EDGES
BASE AS SPECIFIED. SEE ELEVATION
FULL CONCEALED STEEL SUPPORT BRACKET - FINISH
TO MATCH ADJACENT WALL COLOR/FINISH (WHERE
EXPOSED), SIMILAR FOR EXPOSED BRACKET IN
EXISTING WALL WHERE FULLY CONCEALED IS NOT AN
OPTION
23 1/2"2"
4" BACKSPLASH WHERE OCCURS, RE: ELEVATION, MATERIAL
TO MATCH COUNTERTOP MATERIAL, ADHERED TO WALL WITH
CALKING AT WALL JOINT, SQUARE, EASED EDGE
25 1/2"
CAULKING AT JOINT TO MATCH WALL FINISH
OPENING FOR CORD MANAGEMENT WHERE POWER IS NOT ABOVE
COUNTERTOP, CONTRACTOR TO FIELD VERIFY AND COORDINATE
WITH ELECTRICAL PLANS, PROVIDE GROMMET; BASIS OF DESIGN -
MOCKET MAX2/A-94-3-15/16"
RE: ELEVATION
WALL AS SCHEDULED, RE:
PLAN VIEW
1/2" THICK, MDF, EASED
EDGES, PAINTED PNT-01; RE:
FINISH SCHEDULE
COAT HOOK, RE: ACCESSORY
SCHEDULE
RE: ELEVATIONS
4 1/2"
3 1/2"
RE: ELEVATION
WALL AS SCHEDULED,
RE: PLAN VIEW
CALKING AT JOINT TO
MATCH WALL FINISH
3/4" THICK, WHITE OAK
PLAIN SLICED, STAINED,
CLEAR FINISH,
EASED/SQUARE EDGES
RE: PLAN VIEW
VARIES
SHELF: 3/4" PLYWOOD WITH WHITE MELAMINE
FINISH, MATCHING 3MM PVC EDGEBANDING AT
EXPOSED EDGES
KV 185 WHITE (WH) DOUBLE BRACKETS, COORDINATING
BRACKET PER SHELF DEPTH, RE: PLAN VIEW FOR SHELF
DEPTH
PROVIDE 3/4" PLYWOOD SHEATHING FOR
BACKING/BLOCKING
WALL BASE AS SCHEDULED, RE: FINISH PLAN
FINISHED FLOOR
RE: ELEVATION
WALL AS SCHEDULED, RE: PLAN VIEW
KV 85 WHITE (WH) SERIES STANDARDS, COORDINATING
STANDARD PER OVERALL SHELVING HEIGHT, RE: ELEVATION
FOR SHELVING HEIGHTS
3"
4"
RE: ELEVATIONS
4"
RE: ELEVATIONS
RE: ELEVATIONS
SCHEDULED FINISH FLOOR; RE:
FINISH FLOOR PLANS
LOWER CABINET; RE: ELEVATION FOR
CABINET TYPE
WALL AS SCHEDULED; RE:
PLAN FOR TYPE
UPPER CABINET, RE: ELEVATION FOR
CABINET TYPE
BACKSPLASH WHERE OCCURS, RE:
ELEVATION, SAME MATERIAL AS
COUNTERTOP, CALKING AT JOINTS TO
MATCH COUNTERTOP MATERIAL, SQUARE,
EASED EDGES
BASE TO MATCH MILLWORK MATERIAL
UNLESS NOTED IN ELEVATIONS
12"
25 1/2"
1 1/2"
MEDIUM DENSITY FOAM WITH
UPHOLSTERY WRAP, FB-02; RE: FINISH
SCHEDULE
3/4" PLYWOOD FACED WITH HIGH PRESSURE LAMINATE
AT ALL EXPOSED FACES/EDGES, PL-04; RE: FINISH
SCHEDULE, OUTSIDE EDGES FINISHED WITH
COORDINATING PVC EDGEBANDING AT EXPOSED EDGES
3" HIGH DENSITY FOAM WITH UPHOLSTERY WRAP,
FB-01; RE: FINISH SCHEDULE, CUSHION ATTACHED
WITH HEAVY DUTY VELCRO
BLOCKING AS REQUIRED
FINISHED FLOOR
WALL AS SCHEDULED, RE: PLAN VIEW
15"
2 1/2"
3"
5 29/32"
8 7/32"
13/32"
8"13"
WALL AS SCHEDULED; SEE FLOOR PLAN FOR
WALL TYPES
FINISHED FLOOR
DESKTOP: 3/4" PLYWOOD SUBSTRATE WITH HIGH
PRESSURE LAMINATE FINISH, PL-04; RE: FINISH
SCHEDULE, COORDINATING PVC EDGEBANDING AT ALL
EXPOSED EDGES
BASE, WB-03
FULL CONCEALED STEEL SUPPORT BRACKET - FINISH
TO MATCH ADJACENT WALL COLOR/FINISH (WHERE
EXPOSED), SIMILAR FOR EXPOSED BRACKET IN
EXISTING WALL WHERE FULLY CONCEALED IS NOT AN
OPTION
22"2"
24"
CALKING AT JOINT TO MATCH COUNTERTOP FINISH
30"
3/4" MDF CORE FINISHED WITH HIGH
PRESSURE LAMINATE, RE: ELEVATIONS
FOR FINISH TYPE
FINISHED FLOOR
WALL AS SCHEDULED; RE: PLAN.
7"
27"
34"
12"
BASE AS SPECIFIED. SEE ELEVATION
PROVIDE BLOCKING/SHEATHING AS NEEDED
COUNTERTOP: 3/4" PLYWOOD SUBSTRATE,
FINISHED WITH HIGH PRESSURE LAMINATE
RE: ELEVATION FOR FINISH TYPE
1 1/2"
COUNTERTOP: 3/4" PLYWOOD SUBSTRATE WITH
QUARTZ FINISH, SQUARE, EASED EDGE - SCRIBE
TIGHTLY TO WALL, CALKING TO MATCH
COUNTERTOP, RE: ELEVATIONS FOR FINISH TYPE
3/4" MDF CORE, WHITE MELAMINE INTERIOR
RUBBER BASE, WB-08; RE: FINISH
SCHEDULE
FINISHED FLOOR, RE: PLAN.
WALL AS SCHEDULED; RE: PLAN.
CABINET PULL, RE: HARDWARE SCHEDULE
15"
BLOCKING AS REQUIRED
2 1/2"
LOCK, OLYMPUS LOCKS PER CAMPUS
STANDARD
15"
1 1/2"
54 1/2"
30"
DISPLAY GLASS: 1/4" GAUGE, WITH
ADJUSTABLE PINS APPROPRIATE FOR
GLASS SHELVES
BACK AND INTERIOR SIDES, 3/4"
PLYWOOD FACED WITH WOOD VENEER,
WV-01; RE: FINISH SCHEDULE, PIN
HOLES AT SIDES FOR ADJUSTABLE
SHELVING
OUTER SURROUND: 1 1/2" PLYWOOD FACED WITH
WOOD VENEER, WV-01; RE: FINISH SCHEDULE,
EASED, SQUARE EDGES, MITER CORNERS
CABINET: WOOD VENEER FINISH, WV-01; RE:
FINISH SCHEDULE
BOOK SHELF:3/4" MDF CORE WITH HIGH PRESSURE
LAMINATE FINISH AT ALL EXPOSED SURFACES
(FRONT,SIDES, TOP AND BACK), PL-01; RE: FINISH
SCHEDULE WHITE MELAMINE INTERIOR
BASE: PL-01 AT RAISED BASE + WB-04
AT ALL SIDES, RE: FINISH SCHEDULE
FINISHED FLOOR, RE: PLAN.
8 1/4"
28"
3/4"
1"
38"
FIXED VERTICAL DIVIDERS: 1/4" MDF
FINISHED WITH WHITE MELAMINE, QTY 3
WITH EQUAL SPACING
2 1/2"
24"
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
10/28/22
A581
Casework
Details
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
1 1/2" = 1'-0"D1 SINK W/ APRON FRONT - SECTION
1 1/2" = 1'-0"D3 LOWER MICROWAVE CABINET W/ DRAWER
1 1/2" = 1'-0"A5 IT MONITOR SHELF
1 1/2" = 1'-0"D5 COUNTERTOP WITH SUPPORT BRACKET
3" = 1'-0"C1 MOUNTED COAT HOOK SECTION
3" = 1'-0"A1 CHAIR RAIL
1 1/2" = 1'-0"D4 TYPICAL ADJUSTABLE SHELVING SECTION
1 1/2" = 1'-0"B5 TYPICAL MILLWORK DETAIL
1 1/2" = 1'-0"B1 TYPICAL BOOTH SEAT SECTION DETAIL
1 1/2" = 1'-0"B2 TYPICAL BOOTH DESKTOP SECTION
1 1/2" = 1'-0"C2 TYPICAL OPAC SECTION
1 1/2" = 1'-0"B4 DISPLAY SHELVES/ CABINET
1 1/2" = 1'-0"A2 JUVENILE BOOK SHELF
1 1/2"
COUNTERTOP: 3/4" PLYWOOD
SUBSTRATE WITH QUARTZ FINISH,
SQUARE, EASED EDGE - SCRIBE TIGHTLY
TO WALL, CALKING TO MATCH
COUNTERTOP. RE: ELEVATIONS FOR
FINISH TYPE
3/4" MDF CORE, WHITE MELAMINE INTERIOR
BASE AS SCHEDULED, RE: ELEVATIONS
FOR TYPE
FINISHED FLOOR, RE: PLAN.
WALL AS SCHEDULED; RE: PLAN.
CABINET PULL, RE: HARDWARE SCHEDULE
24"
POWER, RE: ELECTRICAL, DEDICATED
BLOCKING AS REQUIRED
CABINET DOOR: 3/4" MDF CORE, SQUARE
EDGES. 4" TRIM WITH PERFORATED METAL
AT OPENING, RE: ELEVATION FOR FINISH
TYPE
34"
2 1/2"
4"
20 1/32"
4"
4"
BOD: MCNICHOLS PERFORATED METAL,
ROUND, ALUMINUM, 14 GA., 1/4" ROUND ON
5/16 STAGGERED CENTERS, 58% OPEN AREA,
#17145163, METAL CLEANED AND POWDER
COATED TO MATCH LAMINATE
LOCK, OLYMPUS LOCKS PER CAMPUS
STANDARD
3/4"
GROMMET; RE: HARDWARE SCHEDULE
25 1/2"WALL AS SCHED. SEE
PLAN FOR TYPE
MICROWAVE CABINET: 3/4" MDF CORE,
FINISHED WITH PLASTIC LAMINATE, RE:
ELEVATION FOR FINISH TYPE, WHITE
MELAMINE INTERIOR
BLOCKING AS REQUIRED
MICROWAVE, OFOI
ELECTRICAL RECEPTICLE, RE: ELECTRICAL
DRAWINGS
CONCEALED SPEED BRACE AS REQUIRED
RE: ACCESSORY SCHEDULE
15"
15"
TO BE VERIFIED WITH MICROWAVE PRIOR TO CONSTRUCTION
12 1/8"
2 1/8"
WALL AS SCHED. SEE PLAN FOR TYPE
BLOCKING AS REQUIRED
4"
RE: ELEVATION
2"
12"
FLOATING SHELF: 3/4" MDF CORE,
PANEL FINISHED WITH PLASTIC
LAMINATE, PL-03 RE: FINISH SCHEDULE,
RE: ELEVATION FOR QTY.
CONCEALED BRACKET, SPACING
ACCORDING TO BRACKET
MANUFACTURER'S RECOMMENDATION
WALL AS SCHEDULED; SEE FLOOR PLAN FOR
WALL TYPES
FINISHED FLOOR
COUNTERTOP: 3/4" PLYWOOD SUBSTRATE WITH LAMINATE
FINISH, RE: ELEVATION FOR FINISH TYPE, MATCHING 3MM
PVC EDGE BANDING AT EXPOSED EDGES
BASE AS SPECIFIED. SEE ELEVATION
FULL CONCEALED STEEL SUPPORT BRACKET - FINISH
TO MATCH ADJACENT WALL COLOR/FINISH (WHERE
EXPOSED), SIMILAR FOR EXPOSED BRACKET IN
EXISTING WALL WHERE FULLY CONCEALED IS NOT AN
OPTION
16 1/2"1 1/2"
4" BACKSPLASH WHERE OCCURS, RE: ELEVATION, MATERIAL
TO MATCH COUNTERTOP MATERIAL, ADHERED TO WALL WITH
CALKING AT WALL JOINT
18"
CAULKING AT JOINT TO MATCH WALL FINISH
OPENING FOR CORD MANAGEMENT WHERE POWER IS NOT ABOVE
COUNTERTOP, CONTRACTOR TO FIELD VERIFY AND COORDINATE
WITH ELECTRICAL PLANS, PROVIDE GROMMET; BASIS OF DESIGN -
MOCKET MAX2/A-94-3-15/16"
RE: ELEVATION
31"3"
4"
5 7/8"
REVEAL
1/8"
3"
27"
1 1/2"
3/4" PLYWOOD FACED WITH WOOD
VENEER, WV-01; RE: FINISH SCHEDULE
HARDWOOD PIECE AT TOP CAP FACED WITH
WOOD VENEER, WV-01; RE: FINISH SCHEDULE,
SQUARE, EASED EDGES
3/4" MDF PAINTED LACQUER TO MATCH
PNT-04, RE: FINISH SCHEDULE
3/4" PLYWOOD FACED WITH WOOD VENEER,
WV-01; RE: FINISH SCHEDULE
BASE: 3/4" PLYWOOD FACED WITH WOOD
VENEER, WV-01; RE: FINISH SCHEDULE
FINISHED FLOOR
24"
COUNTERTOP: 3/4" PLYWOOD
SUBSTRATE FACED WITH ST-01, RE:
FINISH SCHEDULE, EASED, SQUARE
CORNERS
GROMETTS: RE: PLAN VIEW FOR
QTY, RE: HARDWARE SCHEDULE
FOR PRODUCT
3"3"
1/4"
CABINET VARIES, RE: ELEVATIONS FOR
CABINET TYPES, LAMINATE PL-01 AT ALL
CABINETS AND RECEPTION INTERIOR,
OLYMPUS CABINET LOCKS AT ALL
CLOSED CABINETS, FULL DEPTH
FINISHED SIDE PANELS AT EXPOSED
CABINET SIDES
RUBBER BASE AT ALL CABINETS AND
INTERIOR OF RECEPTION DESK, WB-04;
RE: FINISH SCHEDULE
10"
3"
4"
4"
1 7/8"
REVEAL
1/8"
2"
22"
WOOD VENEER BEYOND
3/4" MDF PAINTED LACQUER TO MATCH PNT-04, RE: FINISH SCHEDULE
3/4" PLYWOOD FACED WITH WOOD VENEER, WV-01; RE: FINISH SCHEDULE
BASE: 3/4" PLYWOOD FACED WITH WOOD
VENEER, WV-01; RE: FINISH SCHEDULE
FINISHED FLOOR
24"
COUNTERTOP: 3/4" PLYWOOD
SUBSTRATE FACED WITH ST-01, RE:
FINISH SCHEDULE, EASED, SQUARE
CORNERS
GROMETTS: RE: PLAN VIEW FOR
QTY, RE: HARDWARE SCHEDULE
FOR PRODUCT
3"
1/4"
CABINET VARIES, RE: ELEVATIONS FOR
CABINET TYPES, LAMINATE PL-01 AT ALL
CABINETS AND RECEPTION INTERIOR,
OLYMPUS CABINET LOCKS AT ALL
CLOSED CABINETS, FULL DEPTH
FINISHED SIDE PANELS AT EXPOSED
CABINET SIDES
RUBBER BASE AT ALL CABINETS AND
INTERIOR OF RECEPTION DESK, WB-04;
RE: FINISH SCHEDULE
COUNTERTOP WATERFALL: 3/4"
PLYWOOD SUBSTRATE FACED WITH
ST-01, RE: FINISH SCHEDULE, EASED,
SQUARE CORNERS
32 1/2"
3"
30"
1 1/2"
1 1/2"
1 1/2"
4"
5 7/8"
REVEAL
1/8"
3"
21"
6"
WOOD VENEER BEYOND
3/4" MDF PAINTED LACQUER TO MATCH PNT-04, RE: FINISH SCHEDULE
3/4" PLYWOOD FACED WITH WOOD VENEER, WV-01; RE: FINISH SCHEDULE
BASE: 3/4" PLYWOOD FACED WITH WOOD
VENEER, WV-01; RE: FINISH SCHEDULE
FINISHED FLOOR
COUNTERTOP: 3/4" PLYWOOD SUBSTRATE FACED
WITH ST-01, RE: FINISH SCHEDULE, EASED, SQUARE
CORNERS
3"
1/4"
CABINET, RE: ELEVATIONS FOR CABINET TYPES,
LAMINATE PL-01 AT ALL CABINETS AND RECEPTION
INTERIOR, OLYMPUS CABINET LOCKS AT ALL
CLOSED CABINETS, FULL DEPTH FINISHED SIDE
PANELS AT EXPOSED CABINET SIDES
RUBBER BASE AT ALL CABINETS AND
INTERIOR OF RECEPTION DESK, WB-04;
RE: FINISH SCHEDULE
COUNTERTOP WATERFALL: 3/4" PLYWOOD
SUBSTRATE FACED WITH ST-01, RE: FINISH
SCHEDULE, EASED, SQUARE CORNERS
25 13/32"
1 1/2"
BOOK CARTS, OFOI, SIZED FOR AMERICAN
SECURITY CABINETS UNDER COUNTER BOOK
TRUCK, #UCBT-PC, MODEL TO BE VERIFIED
WITH OWNER
34"
32 1/2"
1 1/2"
LETTERING ADHERED TO FRONT OF SURFACE,
RE: SIGNAGE SCHEDULE
24"
BOOK RETURN OPENING, VERIFY DIMENSIONS
WITH ARCHITECT PRIOR TO CONSTRUCTION PER
FINAL CART SELECTION BY OWNER
24"
2 1/2"
4 1/2"
1"
4 1/2"
1 1/2"
4"
5 7/8"
REVEAL
1/8"
WRAPS AT INTERIOR SITTING SPACE
3"
17"
WOOD VENEER BEYOND
3/4" MDF PAINTED LACQUER TO MATCH PNT-04, RE: FINISH SCHEDULE
3/4" PLYWOOD FACED WITH WOOD VENEER, WV-01; RE: FINISH SCHEDULE
BASE: 3/4" PLYWOOD FACED WITH WOOD
VENEER, WV-01; RE: FINISH SCHEDULE
FINISHED FLOOR
24"
COUNTERTOP: 3/4" PLYWOOD
SUBSTRATE FACED WITH ST-01, RE:
FINISH SCHEDULE, EASED, SQUARE
CORNERS
3"
1/4"
CABINET DRAWER, RE: ELEVATIONS FOR
TYPE, LAMINATE PL-01 AT ALL CABINETS
AND RECEPTION INTERIOR, OLYMPUS
CABINET LOCKS AT ALL CLOSED
CABINETS, FULL DEPTH FINISHED SIDE
PANEL AT EXPOSED INTERIOR SIDE
RUBBER BASE AT ALL CABINETS AND
INTERIOR OF RECEPTION DESK, WB-04;
RE: FINISH SCHEDULE
COUNTERTOP WATERFALL: 3/4"
PLYWOOD SUBSTRATE FACED WITH
ST-01, RE: FINISH SCHEDULE, EASED,
SQUARE CORNERS
3"
30"
1 1/2"
1 1/2"
37 1/2"
1 1/2"
WOOD VENEER BEYOND
3/4" MDF PAINTED LACQUER BEYOND, TO MATCH
PNT-04, RE: FINISH SCHEDULE
3/4" PLYWOOD FACED WITH WOOD VENEER BEYOND,
WV-01; RE: FINISH SCHEDULE
BASE: 3/4" PLYWOOD FACED WITH WOOD
VENEER, WV-01; RE: FINISH SCHEDULE
FINISHED FLOOR
24"
COUNTERTOP: 3/4" PLYWOOD
SUBSTRATE FACED WITH ST-01, RE:
FINISH SCHEDULE, EASED, SQUARE
CORNERS
GROMETTS: RE: PLAN VIEW FOR
QTY, RE: HARDWARE SCHEDULE
FOR PRODUCT
RUBBER BASE AT ALL CABINETS AND
INTERIOR OF RECEPTION DESK, WB-04;
RE: FINISH SCHEDULE
COUNTERTOP WATERFALL: 3/4"
PLYWOOD SUBSTRATE FACED WITH
ST-01, RE: FINISH SCHEDULE, EASED,
SQUARE CORNERS
30"
25 1/2"12"1 1/2"
LAMINATE FINISH AT INTRIORIOR , PL-01
1 1/2"
17"
3"
1/8"
5 7/8"
4"
9 7/8"REVEAL
1/8"
3"
RE: ELEVATIONS FOR OVERALL HEIGHT
VARIES
3/4" MDF PAINTED LACQUER TO MATCH PNT-04, RE: FINISH SCHEDULE
3/4" PLYWOOD FACED WITH WOOD VENEER, WV-01; RE: FINISH SCHEDULE
FINISHED FLOOR
COUNTERTOP: 3/4" PLYWOOD
SUBSTRATE FACED WITH ST-01, RE:
FINISH SCHEDULE, EASED, SQUARE
CORNERS, MITERED JOINTS
1/4"
COUNTERTOP WATERFALL: 3/4"
PLYWOOD SUBSTRATE FACED WITH
ST-01, RE: FINISH SCHEDULE, EASED,
SQUARE CORNERS
VARIES, RE: ELEVATION FOR OVERALL HEIGHT
2 1/4"
4"
RE: PLAN VIEW
VARIES
30"
4"
12 3/4"
21 1/4"
3"2 1/2"3"
24"
COUNTERTOP: 3/4" PLYWOOD SUBSTRATE FACED
WITH ST-02, RE: FINISH SCHEDULE, EASED, SQUARE
CORNERS
CABINET VARIES, RE: ELEVATIONS FOR CABINET
TYPES, LAMINATE PL-01 AT ALL CABINETS AND
RECEPTION INTERIOR, OLYMPUS CABINET LOCKS
AT ALL CLOSED CABINETS, FULL DEPTH FINISHED
SIDE PANELS AT EXPOSED CABINET SIDES
3/4" PLYWOOD FACED WITH WOOD
VENEER, WV-01; RE: FINISH
SCHEDULE
HARDWOOD PIECE AT TOP CAP FACED
WITH WOOD VENEER, WV-01; RE: FINISH
SCHEDULE, SQUARE, EASED EDGES
8"
RUBBER BASE, WB-08; RE: FINISH SCHEDULE
GROMETTS: RE: PLAN VIEW FOR
QTY, RE: HARDWARE SCHEDULE
FOR PRODUCT
FINISHED FLOOR
RE: PLAN VIEW
VARIES
30"
4"
12"
14"
3"2 1/2"3"
24"
COUNTERTOP: 3/4" PLYWOOD SUBSTRATE FACED
WITH ST-02, RE: FINISH SCHEDULE, EASED, SQUARE
CORNERS
CABINET VARIES, RE: ELEVATIONS FOR CABINET
TYPES, LAMINATE PL-01 AT ALL CABINETS AND
RECEPTION INTERIOR, OLYMPUS CABINET LOCKS
AT ALL CLOSED CABINETS, FULL DEPTH FINISHED
SIDE PANELS AT EXPOSED CABINET SIDES
3/4" PLYWOOD FACED WITH WOOD
VENEER, WV-01; RE: FINISH
SCHEDULE
GROMETTS: RE: PLAN VIEW FOR QTY, RE:
HARDWARE SCHEDULE FOR PRODUCT
FINISHED FLOOR
RUBBER BASE, WB-04; RE: FINISH SCHEDULE
3/4" PLYWOOD FACED WITH WOOD
VENEER, WV-01; RE: FINISH
SCHEDULE
RE: ELEVATION
VARIES
REVEAL
1/8"
4 3/8"4 3/8"
REVEAL
1/8"
RE: ELEVATION
VARIES
3/4" MDF, PAINTED LACQUER FINISH,
TO MATCH PNT-06; RE: FINISH
SCHEDULE, MITERED JOINTS
3/4" MDF, PAINTED LACQUER FINISH,
TO MATCH PNT-04; RE: FINISH
SCHEDULE, MITERED JOINTS
3"
3/4" PLYWOOD FACED WITH WOOD
VENEER, WV-01; RE: FINISH
SCHEDULE
RE: ELEVATION
VARIES
REVEAL
1/8"
4 3/8"4 3/8"
REVEAL
1/8"
RE: ELEVATION
VARIES
3/4" MDF, PAINTED LACQUER FINISH,
TO MATCH PNT-04; RE: FINISH
SCHEDULE, MITERED JOINTS
3"
4"
12"
1 1/2"
2 1/2"
3/4" PLYWOOD FACED WITH WOOD VENEER,
WV-01; RE: FINISH SCHEDULE
COUNTERTOP: 3/4" PLYWOOD SUBSTRATE FACED
WITH ST-02, RE: FINISH SCHEDULE, EASED, SQUARE
CORNERS
CABINET VARIES, RE: ELEVATIONS FOR CABINET
TYPES, LAMINATE PL-01 AT ALL CABINETS AND
RECEPTION INTERIOR, OLYMPUS CABINET LOCKS
AT ALL CLOSED CABINETS, FULL DEPTH FINISHED
SIDE PANELS AT EXPOSED CABINET SIDES
FINISHED FLOOR
RUBBER BASE (COORDINATES WITH WOOD
VENEER) , WB-08; RE: FINISH SCHEDULE
WOOD VENEER PARTITION WHERE OCCURS, RE:
ELEVATIONS
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
10/28/22
A582
Casework
Details
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
1 1/2" = 1'-0"D1 SELF CHECK-OUT BASE CABINET
1 1/2" = 1'-0"E3 15" UPPER MICROWAVE CABINET 1 1/2" = 1'-0"E4 MAC LAB 324 SHELVING
1 1/2" = 1'-0"D5 COUNTERTOP WITH SUPPORT BRACKET 2
1 1/2" = 1'-0"C1 CIRCULATION RECEPTION DESK FRONT - HIGH
1 1/2" = 1'-0"C3 CIRCULATION RECEPTION DESK FRONT - LOW
1 1/2" = 1'-0"C5 CIRCULATION RECEPTION DESK WEST - BOOK DROP
1 1/2" = 1'-0"B1 CIRCULATION DESK EAST - W/ CABINET
1 1/2" = 1'-0"B3 CIRCULATION DESK EAST - SITTING SPACE
1 1/2" = 1'-0"A1 CIRCULATION RECEPTION DESK END
1 1/2" = 1'-0"B5 RECEPTION DESK HIGH
1 1/2" = 1'-0"A3 RECEPTION DESK LOW
1 1/2" = 1'-0"A5 RECEPTION DESK ANGLES - MULTI-COLOR
1 1/2" = 1'-0"A6 RECEPTION DESK ANGLES - SINGLE COLOR
1 1/2" = 1'-0"A4 RECEPTION DESK END
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
10/28/22
A601
Door
Schedule
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
GENERAL NOTES - DOORS
1 ALL HOLLOW METAL FRAMES AND DOORS ARE TO BE PAINTED IF NOT NOTED OTHERWISE MATCH ADJACENT WALL FINISH
2 ALL INTERIOR HOLLOW METAL FRAME WIDTHS ARE TO MATCH WALL WIDTHS; COORDINATE WITH VERTICAL ASSEMBLY
TYPES
3 WOOD GRAIN DIRECTION TO BE VERTICAL, UNLESS NOTED OTHERWISE
4 FINISH OF HOLLOW METAL FRAMES TO MATCH ADJACENT IF NOT NOTED OTHERWISE
5 IF COLOR TRANSITIONS OCCUR, THEY ARE TO OCCUR AT INSIDE OF FRAME STOP
6 DOORS SERVING SPACES WITH AN OCCUPANT LOAD OF 50 OR MORE SHALL NOT BE PROVIDED WITH A LATCH OR LOCK
OTHER THAN PANIC HARDWARE. SEE DOOR HARDWARE SPECIFICATIONS
ALL DOOR HANDLES & HARDWARE USED ON THE PROJECT MUST NOT REQUIRE PINCHING, TIGHT GRASPING, OR TWISTING OF THE WRIST IN ORDER TO OPERATE, IN ACCORDANCE WITH 2018 IBC 1010.1.9.1
DOOR SCHEDULE - ALL
DOOR
NUMBER
ROOMS DOOR DIMENSIONS DOOR FRAME FIRE
RATING
Card
Access COMMENTSTO RM # WIDTH HEIGHT THK TYPE MATERIAL FINISH TYPE MATERIAL FINISH
LEVEL 00
0-D HALL 0-D 3' - 6" 7' - 0" 1 3/4" D8 VENEER-WV-01 PAINTED PNT-03 Yes
0-E STAIR 0-E 3' - 0" 7' - 0" 1 3/4" D10 HOLLOW METAL PNT - 03 F1 HOLLOW METAL PAINTED PNT-03 90 FIRE RATED GLAZING REQUIRED
010 OFFICE 010 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F1 HOLLOW METAL PAINTED PNT-03 NEW DOOR AND HARDWARE IN EXISTING FRAME
011 OFFICE 011 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F1 HOLLOW METAL PAINTED PNT-03
012 OFFICE 012 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F1 HOLLOW METAL PAINTED PNT-03 NEW DOOR AND HARDWARE IN EXISTING FRAME
014 WOMEN'S RR 014 3' - 0" 7' - 0" 1 3/4" D3 SOLID CORE WOOD VENEER-WV-01 F1 HOLLOW METAL PAINTED PNT-03 NEW DOOR AND HARDWARE IN EXISTING FRAME
015 MEN'S RR 015 3' - 0" 7' - 0" 1 3/4" D3 SOLID CORE WOOD VENEER-WV-01 F1 HOLLOW METAL PAINTED PNT-03 NEW DOOR AND HARDWARE IN EXISTING FRAME
016 HALL 0-D 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F4 ALUMINUM STOREFRONT CLEAR ANODIZED
018.1 OFFICE 018 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F1 HOLLOW METAL PAINTED PNT-03
018.2 OFFICE 018 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F2 HOLLOW METAL PAINTED PNT-03
020.1 OFFICE 020 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F1 HOLLOW METAL PAINTED PNT-03
020.2 OFFICE 020 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F1 HOLLOW METAL PAINTED PNT-03
022 OPS 022 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F4 ALUMINUM STOREFRONT CLEAR ANODIZED
022A.1 QA 022A 3' - 6" 7' - 0" 1 3/4" D3 SOLID CORE WOOD VENEER-WV-01 F1 HOLLOW METAL PAINTED PNT-03 Yes
022A.2 QA 022A 3' - 0" 7' - 0" 1 3/4" D3 SOLID CORE WOOD VENEER-WV-01 F1 HOLLOW METAL PAINTED PNT-03
024 TECH ROOM 024 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F1 HOLLOW METAL PAINTED PNT-03 Yes
026A OFFICE 026A 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F1 HOLLOW METAL PAINTED PNT-03
026B OFFICE 026B 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F2 HOLLOW METAL PAINTED PNT-03
026C OFFICE 026C 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F2 HOLLOW METAL PAINTED PNT-03
026D OFFICE 026D 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F2 HOLLOW METAL PAINTED PNT-03
026E OFFICE 026E 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F2 HOLLOW METAL PAINTED PNT-03
026F STUDENTS 026F 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F1 HOLLOW METAL PAINTED PNT-03
028 SHORT TERM STORAGE 028 3' - 0" 7' - 0" 1 3/4" D3 SOLID CORE WOOD VENEER-WV-01 F1 HOLLOW METAL PAINTED PNT-03 Yes
LEVEL 01
1-B.1 ENTRY HALL 120A 6' - 0" 7' - 0" 1 3/4" D2 SOLID CORE WOOD VENEER-WV-01 F9 HOLLOW METAL CLEAR ANODIZED 90 Yes ADA ACTUATOR & FIRE-RESISTIVE GLAZING REQUIRED TO MEET "D-H-W-90", NFPA 252, ASTM E119 or UL
263
1-B.2 ENTRY HALL 120A 6' - 0" 7' - 0" 1 3/4" D2 SOLID CORE WOOD VENEER-WV-01 F9 HOLLOW METAL CLEAR ANODIZED 90 Yes FIRE-RESISTIVE GLAZING REQUIRED TO MEET "D-H-W-90", NFPA 252, ASTM E119 or UL 263
1-F.1 VESTIBULE 1-F 6' - 0" 7' - 0" 1 3/4" D4 ALUMINUM CLEAR ANODIZED F4 ALUMINUM STOREFRONT CLEAR ANODIZED Yes
1-F.2 VESTIBULE 1-F 6' - 0" 7' - 0" 1 3/4" D4 ALUMINUM CLEAR ANODIZED F4 ALUMINUM STOREFRONT CLEAR ANODIZED Yes
1-F.3 VESTIBULE 1-F 6' - 0" 7' - 0" 1 3/4" D4 ALUMINUM CLEAR ANODIZED F4 ALUMINUM STOREFRONT CLEAR ANODIZED No ADA ACTUATOR
1-F.4 VESTIBULE 1-F 6' - 0" 7' - 0" 1 3/4" D4 ALUMINUM CLEAR ANODIZED F4 ALUMINUM STOREFRONT CLEAR ANODIZED No
1-F.5 VESTIBULE 1-F 6' - 0" 7' - 0" 1 3/4" D4 ALUMINUM CLEAR ANODIZED F4 ALUMINUM STOREFRONT CLEAR ANODIZED Yes ADA ACTUATOR
1-H STAIR 1-H 3' - 0" 7' - 0" 1 3/4" D10 HOLLOW METAL PNT - 03 F1 HOLLOW METAL PAINTED PNT-03 90 FIRE RATED GLAZING REQUIRED
1-N STAIRS 1-N 3' - 0" 7' - 0" 1 3/4" D3 SOLID CORE WOOD VENEER-WV-01 F1 HOLLOW METAL PAINTED PNT-03
1-U.1 VESTIBULE 1-U 6' - 0" 7' - 0" 1 3/4" D4 ALUMINUM CLEAR ANODIZED F4 ALUMINUM STOREFRONT CLEAR ANODIZED Yes
1-U.2 VESTIBULE 1-U 6' - 0" 7' - 0" 1 3/4" D4 ALUMINUM CLEAR ANODIZED F4 ALUMINUM STOREFRONT CLEAR ANODIZED Yes ADA ACTUATOR
1-U.3 VESTIBULE 1-U 6' - 0" 7' - 0" 1 3/4" D4 ALUMINUM CLEAR ANODIZED F4 ALUMINUM STOREFRONT CLEAR ANODIZED
1-U.4 VESTIBULE 1-U 6' - 0" 7' - 0" 1 3/4" D4 ALUMINUM CLEAR ANODIZED F4 ALUMINUM STOREFRONT CLEAR ANODIZED ADA ACTUATOR
1-V HALL 1-V 3' - 0" 7' - 0" 1 3/4" D6 SOLID CORE WOOD VENEER-WV-01 F3 HOLLOW METAL PAINTED PNT-03 0
1-X HALL 1-X 3' - 0" 7' - 0" 1 3/4" D3 SOLID CORE WOOD VENEER-WV-01 F1 HOLLOW METAL PAINTED PNT-03
102 ELEC ROOM 102 3' - 0" 7' - 0" 1 3/4" D7 HOLLOW METAL PNT - 04 F1 HOLLOW METAL PAINTED PNT-04 Yes
104 OFFICE 104 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F2 HOLLOW METAL PAINTED PNT-03
106 OFFICE 106 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F2 HOLLOW METAL PAINTED PNT-03
108 OFFICE 108 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F2 HOLLOW METAL PAINTED PNT-03
114A OFFICE 114A 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F4 ALUMINUM STOREFRONT CLEAR ANODIZED
124 STUDY (MED) 124 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F4 ALUMINUM STOREFRONT CLEAR ANODIZED
125 STUDY (MED) 125 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F4 ALUMINUM STOREFRONT CLEAR ANODIZED
126 STUDY (SM) 126 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F4 ALUMINUM STOREFRONT CLEAR ANODIZED
127 STUDY (SM) 127 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F4 ALUMINUM STOREFRONT CLEAR ANODIZED
128 STUDY (SM) 128 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F4 ALUMINUM STOREFRONT CLEAR ANODIZED
129 OFFICE 129 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F2 HOLLOW METAL PAINTED PNT-03
130 OFFICE 130 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F1 HOLLOW METAL PAINTED PNT-03
131 OFFICE 131 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F2 HOLLOW METAL PAINTED PNT-03
132 STUDY (MED) 132 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F4 ALUMINUM STOREFRONT CLEAR ANODIZED
134 RECEPTION 134 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F4 ALUMINUM STOREFRONT CLEAR ANODIZED
136 OFFICE 136 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F2 HOLLOW METAL PAINTED PNT-03
138 OFFICE 138 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F2 HOLLOW METAL PAINTED PNT-03
140 CONFERENCE ROOM 140 6' - 0" 7' - 0" 1 3/4" D2 SOLID CORE WOOD VENEER-WV-01 F3 HOLLOW METAL PAINTED PNT-03
142.1 BREAKROOM 142 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F2 HOLLOW METAL PAINTED PNT-03
142.2 BREAKROOM 142 3' - 0" 7' - 0" 1 3/4" D3 SOLID CORE WOOD VENEER-WV-01 F1 HOLLOW METAL PAINTED PNT-03
144 FAMILY RR 144 3' - 0" 7' - 0" 1 3/4" D3 SOLID CORE WOOD VENEER-WV-01 F1 HOLLOW METAL PAINTED PNT-03
146 MENS 146 3' - 0" 7' - 0" 1 3/4" D3 SOLID CORE WOOD VENEER-WV-01 F1 HOLLOW METAL PAINTED PNT-03 NEW DOOR SLAB IN EXISTING FRAME - RE-USE EXISTING HARDWARE VIF DOOR SIZE
147 JANITORS OFFICE 147 3' - 0" 7' - 0" 1 3/4" D9 SOLID CORE WOOD VENEER-WV-01 F1 HOLLOW METAL PAINTED PNT-03 NEW DOOR SLAB IN EXISTING FRAME - RE-USE EXISTING HARDWARE VIF DOOR SIZE
148 WOMENS 148 3' - 0" 7' - 0" 1 3/4" D3 SOLID CORE WOOD VENEER-WV-01 F1 HOLLOW METAL PAINTED PNT-03 NEW DOOR SLAB IN EXISTING FRAME - RE-USE EXISTING HARDWARE VIF DOOR SIZE
152 WOMEN'S RESTROOM 152 3' - 0" 7' - 0" 1 3/4" D3 SOLID CORE WOOD VENEER-WV-01 F1 HOLLOW METAL PAINTED PNT-03 NEW DOOR SLAB IN EXISTING FRAME - RE-USE EXISTING HARDWARE VIF DOOR SIZE
154 MEN'S RESTROOM 154 3' - 0" 7' - 0" 1 3/4" D3 SOLID CORE WOOD VENEER-WV-01 F1 HOLLOW METAL PAINTED PNT-03 NEW DOOR SLAB IN EXISTING FRAME - RE-USE EXISTING HARDWARE VIF DOOR SIZE
156 WORKSPACE 156 6' - 0" 7' - 0" 1 3/4" D4 ALUMINUM CLEAR ANODIZED F4 ALUMINUM STOREFRONT CLEAR ANODIZED Yes
156A PRACTICE 156A 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F1 HOLLOW METAL PAINTED PNT-03
156B PRACTICE 156B 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F1 HOLLOW METAL PAINTED PNT-03
156C PRACTICE 156C 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F1 HOLLOW METAL PAINTED PNT-03
156D STORAGE 156D 3' - 0" 7' - 0" 1 3/4" D7 HOLLOW METAL PNT - 03 F1 HOLLOW METAL PAINTED PNT-03
156E WORKSPACE 156 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F1 HOLLOW METAL PAINTED PNT-03
156F WORKSPACE 156 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F2 HOLLOW METAL PAINTED PNT-03
158 CONFERENCE ROOM 158 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F4 ALUMINUM STOREFRONT CLEAR ANODIZED
160A TUTORING ADMIN OPEN AREA 160 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F2 HOLLOW METAL PAINTED PNT-03
160B OFFICE 160B 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F2 HOLLOW METAL PAINTED PNT-03
162 CLASSROOM 162 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F1 HOLLOW METAL PAINTED PNT-03
164 CLASSROOM 164 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F1 HOLLOW METAL PAINTED PNT-03
166 CLASSROOM 166 3' - 0" 7' - 0" 1 3/8" D1 SOLID CORE WOOD VENEER-WV-01 F1 HOLLOW METAL PAINTED PNT-03 NEW DOOR SLAB IN EXISTING FRAME - RE-USE EXISTING HARDWARE VIF DOOR SIZE
168 CLASSROOM 168 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F1 HOLLOW METAL PAINTED PNT-03
170.1 DROP IN MATH LAB 170 6' - 0" 7' - 0" 1 3/4" D4 ALUMINUM CLEAR ANODIZED F4 ALUMINUM STOREFRONT CLEAR ANODIZED Yes
170.2 DROP IN MATH LAB 170 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F4 ALUMINUM STOREFRONT CLEAR ANODIZED
170A DROP IN MATH LAB 170 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F4 ALUMINUM STOREFRONT CLEAR ANODIZED
170B DROP IN MATH LAB 170 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F4 ALUMINUM STOREFRONT CLEAR ANODIZED
170C STORAGE 170C 3' - 6" 7' - 0" 1 3/4" D3 SOLID CORE WOOD PNT - 03 F1 HOLLOW METAL PAINTED PNT-03
172 CLASSROOM 172 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F1 HOLLOW METAL PAINTED PNT-03
173 ELECTRICAL 173 3' - 0" 7' - 0" 1 3/4" D7 HOLLOW METAL PNT - 03 F1 HOLLOW METAL PAINTED PNT-03 NEW DOOR SLAB IN EXISTING FRAME - RE-USE EXISTING HARDWARE VIF DOOR SIZE
174 STUDENT PREP 174 3' - 0" 7' - 0" 1 3/4" D3 SOLID CORE WOOD VENEER-WV-01 F1 HOLLOW METAL PAINTED PNT-03
178 STUDY 178 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F4 ALUMINUM STOREFRONT CLEAR ANODIZED
179 STUDY 179 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F4 ALUMINUM STOREFRONT CLEAR ANODIZED
180 ADJUNCT OFFICE 180 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F2 HOLLOW METAL PAINTED PNT-03
181 HALL 1-X 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F2 HOLLOW METAL PAINTED PNT-03
182 HALL 1-X 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F2 HOLLOW METAL PAINTED PNT-03
183 OFFICE 183 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F2 HOLLOW METAL PAINTED PNT-03
184 HALL 1-X 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F2 HOLLOW METAL PAINTED PNT-03
185 OFFICE 185 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F2 HOLLOW METAL PAINTED PNT-03
186 OFFICE 186 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F2 HOLLOW METAL PAINTED PNT-03
188 HALL 1-Y 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F4 ALUMINUM STOREFRONT CLEAR ANODIZED
188A OFFICE 188A 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F2 HOLLOW METAL PAINTED PNT-03
188B CONFERENCE 188B 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F4 ALUMINUM STOREFRONT CLEAR ANODIZED
190 HALL 1-Y 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F1 HOLLOW METAL PAINTED PNT-03
190A OFFICE 190A 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F2 HOLLOW METAL PAINTED PNT-03
190B TRAINING AREA 190 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F2 HOLLOW METAL PAINTED PNT-03
190C STORAGE 190C 3' - 0" 7' - 0" 1 3/4" D7 HOLLOW METAL PNT - 03 F1 HOLLOW METAL PAINTED PNT-03
192 WORKSTATIONS/ FLEX SPACE 192 6' - 0" 7' - 0" 1 3/4" D4 ALUMINUM CLEAR ANODIZED F4 ALUMINUM STOREFRONT CLEAR ANODIZED Yes
192A SMALL MEETING 192A 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F4 ALUMINUM STOREFRONT CLEAR ANODIZED
192B OFFICE 192B 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F2 HOLLOW METAL PAINTED PNT-03
192C WORKSTATIONS/ FLEX SPACE 192 3' - 0" 7' - 0" 1 3/4" D7 HOLLOW METAL PNT - 03 F1 HOLLOW METAL PAINTED PNT-03
LEVEL 02
2-A.1 STAIR 2-A 3' - 0" 7' - 0" 1 3/4" D8 SOLID CORE WOOD VENEER-WV-01 F1 HOLLOW METAL PAINTED PNT-03 90 Yes FIRE-RESISTIVE GLAZING REQUIRED TO MEET "D-H-W-90", NFPA 252, ASTM E119 or UL 263
2-A.2 STAIR 2-A 3' - 0" 7' - 0" 1 3/4" D8 SOLID CORE WOOD VENEER-WV-01 F1 HOLLOW METAL PAINTED PNT-03 90 Yes FIRE-RESISTIVE GLAZING REQUIRED TO MEET "D-H-W-90", NFPA 252, ASTM E119 or UL 263
2-A.3 STAIR 2-A 3' - 0" 7' - 0" 1 3/4" D8 SOLID CORE WOOD VENEER-WV-01 F1 HOLLOW METAL PAINTED PNT-03 90 Yes FIRE-RESISTIVE GLAZING REQUIRED TO MEET "D-H-W-90", NFPA 252, ASTM E119 or UL 263
2-A.4 STAIR 2-A 3' - 0" 7' - 0" 1 3/4" D8 SOLID CORE WOOD VENEER-WV-01 F1 HOLLOW METAL PAINTED PNT-03 90 Yes FIRE-RESISTIVE GLAZING REQUIRED TO MEET "D-H-W-90", NFPA 252, ASTM E119 or UL 263
2-B STAIR 2-B 3' - 0" 7' - 0" 1 3/4" D10 HOLLOW METAL VENEER-WV-01 F1 HOLLOW METAL PAINTED PNT-03 90 FIRE-RESISTIVE GLAZING REQUIRED TO MEET "D-H-W-90", NFPA 252, ASTM E119 or UL 263
2-D MECHANICAL 2-D 3' - 0" 7' - 0" 1 3/4" D7 HOLLOW METAL PNT - 03 F1 HOLLOW METAL PAINTED PNT-03 Yes
2-E TECH SERV STORAGE 2-E 3' - 0" 7' - 0" 1 3/4" D7 HOLLOW METAL PNT - 03 F1 HOLLOW METAL PAINTED PNT-03
2-G STAIR 2-G 3' - 0" 7' - 0" 1 3/4" D10 HOLLOW METAL PNT - 03 F1 HOLLOW METAL PAINTED PNT-03 90 FIRE-RESISTIVE GLAZING REQUIRED TO MEET "D-H-W-90", NFPA 252, ASTM E119 or UL 263
2U-1 HALL 2-U 3' - 0" 7' - 0" 1 3/4" D6 SOLID CORE WOOD VENEER-WV-01 F3 HOLLOW METAL PAINTED PNT-03 0
200 OFFICE 200 3' - 0" 7' - 0" 1 1/2" D1 SOLID CORE WOOD VENEER-WV-01 F2 HOLLOW METAL PAINTED PNT-03
202 OFFICE 202 3' - 0" 7' - 0" 1 1/2" D1 SOLID CORE WOOD VENEER-WV-01 F2 HOLLOW METAL PAINTED PNT-03
204 STUDY (SM) 204 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F4 ALUMINUM STOREFRONT CLEAR ANODIZED
206 STUDY (MED) 206 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F4 ALUMINUM STOREFRONT CLEAR ANODIZED
208 STUDY (SM) 208 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F4 ALUMINUM STOREFRONT CLEAR ANODIZED
ALL DOOR HANDLES & HARDWARE USED ON THE PROJECT MUST NOT REQUIRE PINCHING, TIGHT GRASPING, OR TWISTING OF THE WRIST IN ORDER TO OPERATE, IN ACCORDANCE WITH 2018 IBC 1010.1.9.1
DOOR SCHEDULE - ALL
DOOR
NUMBER
ROOMS DOOR DIMENSIONS DOOR FRAME FIRE
RATING
Card
Access COMMENTSTO RM # WIDTH HEIGHT THK TYPE MATERIAL FINISH TYPE MATERIAL FINISH
210 STUDY (SM) 210 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F4 ALUMINUM STOREFRONT CLEAR ANODIZED
212 STUDY (SM) 212 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F4 ALUMINUM STOREFRONT CLEAR ANODIZED
214 OPEN STUDY 220 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F4 ALUMINUM STOREFRONT CLEAR ANODIZED
216 OPEN STUDY 220 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F4 ALUMINUM STOREFRONT CLEAR ANODIZED
218 OPEN STUDY 220 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F4 ALUMINUM STOREFRONT CLEAR ANODIZED
222.1 INSTRUCTION 1 222 3' - 0" 7' - 0" 1 1/2" D1 SOLID CORE WOOD VENEER-WV-01 F1 HOLLOW METAL PAINTED PNT-03 Yes
222.2 CLOSET 222a 3' - 0" 7' - 0" 1 3/4" D7 HOLLOW METAL PNT - 03 F1 HOLLOW METAL PAINTED PNT-03 No
222M INSTRUCTION 2 224 22' - 11 1/2" 9' - 0" 4" D12 SEE DOOR TYPES Yes V.I.F. COORDINATE WIDTH AND HEIGHT WITH DIMENSION PLANS AND CEILNG PLANS
224.1 INSTRUCTION 2 224 3' - 6" 7' - 0" 1 1/2" D1 SOLID CORE WOOD VENEER-WV-01 F1 HOLLOW METAL PAINTED PNT-03 Yes
224.2 INSTRUCTION 2 224 3' - 0" 7' - 0" 1 1/2" D1 SOLID CORE WOOD VENEER-WV-01 F1 HOLLOW METAL PAINTED PNT-03 Yes
224.3 CLOSET 224a 3' - 0" 7' - 0" 1 3/4" D7 HOLLOW METAL PNT - 03 F1 HOLLOW METAL PAINTED PNT-03
224M INSTRUCTION 2 224 17' - 8" 9' - 0" D13 SEE DOOR TYPES Yes V.I.F. COORDINATE WIDTH AND HEIGHT WITH DIMENSION PLANS AND CEILNG PLANS
226 PRESS ROOM 226 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F4 ALUMINUM STOREFRONT CLEAR ANODIZED Yes
228 SPECIAL COLLECTIONS
RECEPTION
228b 6' - 0" 7' - 0" 1 3/4" D4 ALUMINUM CLEAR ANODIZED F4 ALUMINUM STOREFRONT CLEAR ANODIZED Yes
228A.1 OFFICE 228A 3' - 0" 7' - 0" 1 1/2" D1 SOLID CORE WOOD VENEER-WV-01 F2 HOLLOW METAL PAINTED PNT-03
228A.2 DCAM 228B 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F1 HOLLOW METAL PAINTED PNT-03
228B SPECIAL COLLECTIONS 228 4' - 2" 7' - 0" 1 1/2" D1 SOLID CORE WOOD VENEER-WV-01 F1 HOLLOW METAL PAINTED PNT-03
228C SCANNER 228C 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F1 HOLLOW METAL PAINTED PNT-03
228D ARCHIVE 228D 3' - 6" 7' - 0" 1 3/4" D3 SOLID CORE WOOD VENEER-WV-01 F1 HOLLOW METAL PAINTED PNT-03 Yes
228E VAULT 228E 3' - 0" 7' - 0" 1 3/4"F1 EXISTING VAULT DOOR - COORDINATE INSTALL WITH EXISTING DOOR REQUIREMENTS
230.1 OFFICE 230 3' - 0" 7' - 0" 1 1/2" D1 SOLID CORE WOOD VENEER-WV-01 F2 HOLLOW METAL PAINTED PNT-03
230.2 OFFICE 230 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F1 HOLLOW METAL PAINTED PNT-03
232.1 OFFICE 232 3' - 0" 7' - 0" 1 1/2" D1 SOLID CORE WOOD VENEER-WV-01 F2 HOLLOW METAL PAINTED PNT-03
232.2 SPECIAL COLLECTIONS 228 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F1 HOLLOW METAL PAINTED PNT-03
234 LARGE COMPUTER CLASSROOM 234 3' - 0" 7' - 0" 1 1/2" D1 SOLID CORE WOOD VENEER-WV-01 F2 HOLLOW METAL PAINTED PNT-03
236 SHEET MUSIC 236 3' - 0" 7' - 0" 1 3/4" D3 SOLID CORE WOOD VENEER-WV-01 F1 HOLLOW METAL PAINTED PNT-03
238 TECH SERVICES 238 3' - 6" 7' - 0" 1 1/2" D1 SOLID CORE WOOD VENEER-WV-01 F1 HOLLOW METAL PAINTED PNT-03
241 JANITOR'S OFFICE 241 3' - 0" 7' - 0" 1 3/4" D3 SOLID CORE WOOD VENEER-WV-01 F1 HOLLOW METAL PAINTED PNT-03
241A IT 241A 3' - 0" 7' - 0" 1 3/4" D7 HOLLOW METAL PNT - 03 F1 HOLLOW METAL PAINTED PNT-03
242 ELECTRICAL ROOM 242 3' - 0" 7' - 0" 1 3/4" D7 HOLLOW METAL PNT - 03 F1 HOLLOW METAL PAINTED PNT-03 Yes
243 MOTHERS 243 3' - 0" 7' - 0" 1 3/4" D3 SOLID CORE WOOD VENEER-WV-01 F1 HOLLOW METAL PAINTED PNT-03
244 FAMILY RR 244 3' - 0" 7' - 0" 1 3/4" D3 SOLID CORE WOOD VENEER-WV-01 F1 HOLLOW METAL PAINTED PNT-03
245 OPEN STUDY 53 3' - 0" 7' - 0" 1 3/4" D3 SOLID CORE WOOD VENEER-WV-01 F1 HOLLOW METAL
247 MEN'S RESTROOM 247 3' - 0" 7' - 0" 1 3/4" D3 SOLID CORE WOOD VENEER-WV-01 F1 HOLLOW METAL
248 WOMEN'S RESTROOM 248 3' - 0" 7' - 0" 1 3/4" D3 SOLID CORE WOOD VENEER-WV-01 F1 HOLLOW METAL
249 JANITOR'S CLOSET 249 3' - 0" 7' - 0" 1 3/4" D7 HOLLOW METAL PNT - 03 F1 HOLLOW METAL PAINTED PNT-03 Yes
252A STUDY 252A 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F4 ALUMINUM STOREFRONT CLEAR ANODIZED
252B STUDY 252B 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F4 ALUMINUM STOREFRONT CLEAR ANODIZED
252C STUDY 252C 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F4 ALUMINUM STOREFRONT CLEAR ANODIZED
252D OFFICE 252D 3' - 0" 7' - 0" 1 1/2" D1 SOLID CORE WOOD VENEER-WV-01 F2 HOLLOW METAL PAINTED PNT-03
252E OFFICE 252E 3' - 0" 7' - 0" 1 1/2" D1 SOLID CORE WOOD VENEER-WV-01 F2 HOLLOW METAL PAINTED PNT-03
252F STORAGE 252F 3' - 0" 7' - 0" 1 3/4" D7 HOLLOW METAL PNT - 03 F1 HOLLOW METAL PAINTED PNT-03
252G PREP / STORAGE 252G 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F1 HOLLOW METAL PAINTED PNT-03
256.1 WRITING CENTER OPEN
TUTORING
256 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F4 ALUMINUM STOREFRONT CLEAR ANODIZED Yes
256.2 WRITING CENTER OPEN
TUTORING
256 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F4 ALUMINUM STOREFRONT CLEAR ANODIZED Yes
256A PREP / STORAGE 256A 3' - 0" 7' - 0" 1 3/4" D3 SOLID CORE WOOD VENEER-WV-01 F1 HOLLOW METAL PAINTED PNT-03
256B OFFICE 256B 3' - 0" 7' - 0" 1 1/2" D1 SOLID CORE WOOD VENEER-WV-01 F2 HOLLOW METAL PAINTED PNT-03
256C OFFICE 256C 3' - 0" 7' - 0" 1 1/2" D1 SOLID CORE WOOD VENEER-WV-01 F2 HOLLOW METAL PAINTED PNT-03
258 CLASSROOM 258 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F1 HOLLOW METAL PAINTED PNT-03
260 HALL 2-U 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F1 HOLLOW METAL PAINTED PNT-03
264 OFFICE 264 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F2 HOLLOW METAL PAINTED PNT-03
265 OFFICE 265 3' - 0" 7' - 0" 1 1/2" D1 SOLID CORE WOOD VENEER-WV-01 F2 HOLLOW METAL PAINTED PNT-03
266 STUDY 266 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F4 ALUMINUM STOREFRONT CLEAR ANODIZED
267 STUDY 267 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F4 ALUMINUM STOREFRONT CLEAR ANODIZED
268 STUDY 268 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F4 ALUMINUM STOREFRONT CLEAR ANODIZED
269 OPEN TUTORING CENTER 270 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F4 ALUMINUM STOREFRONT CLEAR ANODIZED
270.1 OPEN TUTORING CENTER 270 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F4 ALUMINUM STOREFRONT CLEAR ANODIZED
270.2 OPEN TUTORING CENTER 270 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F4 ALUMINUM STOREFRONT CLEAR ANODIZED
270B PREP / STORAGE 270B 3' - 0" 7' - 0" 1 3/4" D3 SOLID CORE WOOD VENEER-WV-01 F1 HOLLOW METAL PAINTED PNT-03
270G STUDY 270G 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F4 ALUMINUM STOREFRONT CLEAR ANODIZED
270H OPEN TUTORING CENTER 270 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F4 ALUMINUM STOREFRONT CLEAR ANODIZED
270J STORAGE 270J 3' - 6" 7' - 0" 1 3/4" D3 SOLID CORE WOOD PNT - 03 F1 HOLLOW METAL PAINTED PNT-03 3'-0"X3'-0" STAINLESS KICK PLATE ON INTERIOR SIDE OF DOOR
272 OPEN TUTORING CENTER 270 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F1 HOLLOW METAL PAINTED PNT-03
274 PRE-FUNCTION 270E 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F1 HOLLOW METAL PAINTED PNT-03
274M CLASSROOM 272 25' - 2 1/4" 9' - 0" 4" D12 SEE DOOR TYPES Yes V.I.F. COORDINATE WIDTH AND HEIGHT WITH DIMENSION PLANS AND CEILNG PLANS
276 CLASSROOM 276 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F1 HOLLOW METAL PAINTED PNT-03
276S CLASSROOM 276 20' - 6 1/2" 10' - 6
1/2"
11 3/4" D14 SEE DOOR TYPES Yes V.I.F. COORDINATE WIDTH AND HEIGHT WITH DIMENSION PLANS AND CEILNG PLANS
278 CLASSROOM 278 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F1 HOLLOW METAL PAINTED PNT-03
278M CLASSROOM 278 25' - 2 1/4" 9' - 0" 4" D12 SEE DOOR TYPES Yes V.I.F. COORDINATE WIDTH AND HEIGHT WITH DIMENSION PLANS AND CEILNG PLANS
280 TR / COMM. 280 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F1 HOLLOW METAL PAINTED PNT-03 Yes
286 ADJUNCT OFFICE 286 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F2 HOLLOW METAL PAINTED PNT-03
288A ENGLISH TRANSITION CENTER 288 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F4 ALUMINUM STOREFRONT CLEAR ANODIZED
288B OFFICE 288B 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F1 HOLLOW METAL PAINTED PNT-03
288C ENGLISH TRANSITION CENTER 288 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F2 HOLLOW METAL PAINTED PNT-03
288D STUDY 288D 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F4 ALUMINUM STOREFRONT CLEAR ANODIZED
288E STUDY 288E 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F4 ALUMINUM STOREFRONT CLEAR ANODIZED
288F STUDY 288F 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F4 ALUMINUM STOREFRONT CLEAR ANODIZED
288G STUDY 288G 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F4 ALUMINUM STOREFRONT CLEAR ANODIZED
288H ENGLISH TRANSITION CENTER 288 3' - 0" 7' - 0" 1 3/4" D3 SOLID CORE WOOD VENEER-WV-01 F1 HOLLOW METAL PAINTED PNT-03
LEVEL 03
3-B.1 STAIR 1 3-B 3' - 0" 7' - 0" 1 3/4" D6 SOLID CORE WOOD VENEER-WV-01 F3 HOLLOW METAL PAINTED PNT-03 90 No MAG HOLD
3-B.2 STAIR 1 3-B 3' - 0" 7' - 0" 1 3/4" D6 SOLID CORE WOOD VENEER-WV-01 F3 HOLLOW METAL PAINTED PNT-03 90 No MAG HOLD
3-B.5 STAIR 1 3-B 3' - 0" 7' - 0" 1 3/4" D8 SOLID CORE WOOD VENEER-WV-01 F1 HOLLOW METAL PAINTED PNT-03 90 Yes FIRE-RESISTIVE GLAZING REQUIRED TO MEET "D-H-W-90", NFPA 252, ASTM E119 or UL 263
3-B.6 STAIR 1 3-B 3' - 0" 7' - 0" 1 3/4" D8 SOLID CORE WOOD VENEER-WV-01 F1 HOLLOW METAL PAINTED PNT-03 90 Yes FIRE-RESISTIVE GLAZING REQUIRED TO MEET "D-H-W-90", NFPA 252, ASTM E119 or UL 263
3-B.7 STAIR 1 3-B 3' - 0" 7' - 0" 1 3/4" D8 SOLID CORE WOOD VENEER-WV-01 F1 HOLLOW METAL PAINTED PNT-03 90 Yes FIRE-RESISTIVE GLAZING REQUIRED TO MEET "D-H-W-90", NFPA 252, ASTM E119 or UL 263
3-B.8 STAIR 1 3-B 3' - 0" 7' - 0" 1 3/4" D8 SOLID CORE WOOD VENEER-WV-01 F1 HOLLOW METAL PAINTED PNT-03 90 Yes FIRE-RESISTIVE GLAZING REQUIRED TO MEET "D-H-W-90", NFPA 252, ASTM E119 or UL 263
3-C STAIRS 3-C 3' - 0" 7' - 0" 1 3/4" D10 HOLLOW METAL PNT - 03 F1 HOLLOW METAL PAINTED PNT-03 90 FIRE-RESISTIVE GLAZING REQUIRED TO MEET "D-H-W-90", NFPA 252, ASTM E119 or UL 263
3-F STAIR 3-F 3' - 0" 7' - 0" 1 3/4" D10 HOLLOW METAL PNT - 03 F1 HOLLOW METAL PAINTED PNT-03 90 FIRE-RESISTIVE GLAZING REQUIRED TO MEET "D-H-W-90", NFPA 252, ASTM E119 or UL 263
302 STUDY (MED) 302 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F4 ALUMINUM STOREFRONT CLEAR ANODIZED
304 STUDY (MED) 304 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F4 ALUMINUM STOREFRONT CLEAR ANODIZED
306 STORAGE 306 3' - 0" 7' - 0" 1 3/4" D7 HOLLOW METAL PNT - 03 F1 HOLLOW METAL PAINTED PNT-03
308 ELECTRICAL 308 3' - 0" 7' - 0" 1 3/4" D7 HOLLOW METAL PNT - 03 F1 HOLLOW METAL PAINTED PNT-03 Yes
310 OFFICE 310 3' - 0" 7' - 0" 1 1/2" D1 SOLID CORE WOOD VENEER-WV-01 F2 HOLLOW METAL PAINTED PNT-03
312 OFFICE 312 3' - 0" 7' - 0" 1 1/2" D1 SOLID CORE WOOD VENEER-WV-01 F2 HOLLOW METAL PAINTED PNT-03
314 JUVENILE 300 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F4 ALUMINUM STOREFRONT CLEAR ANODIZED
316 JUVENILE 300 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F4 ALUMINUM STOREFRONT CLEAR ANODIZED
318 STUDY (SM) 318 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F4 ALUMINUM STOREFRONT CLEAR ANODIZED
320 STUDY (SM) 320 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F4 ALUMINUM STOREFRONT CLEAR ANODIZED
322.1 OFFICE 322 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F1 HOLLOW METAL PAINTED PNT-03
324 MAC LAB 324 6' - 0" 7' - 0" 1 3/4" D2 SOLID CORE WOOD VENEER-WV-01 F3 HOLLOW METAL PAINTED PNT-03 Yes
324A MAC EQUIP 324A 3' - 0" 7' - 0" 1 3/4" D7 HOLLOW METAL PNT - 03 F1 HOLLOW METAL PAINTED PNT-03 Yes
324B ELECTRICAL 324B 3' - 0" 7' - 0" 1 3/4" D7 HOLLOW METAL PNT - 03 F1 HOLLOW METAL PAINTED PNT-03 Yes
326 OPEN STUDY 383 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F4 ALUMINUM STOREFRONT CLEAR ANODIZED
328 OPEN STUDY 383 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F4 ALUMINUM STOREFRONT CLEAR ANODIZED
330 STUDY (SM) 330 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F4 ALUMINUM STOREFRONT CLEAR ANODIZED
332 STUDY (SM) 332 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F4 ALUMINUM STOREFRONT CLEAR ANODIZED
334 STUDY (SM) 334 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F4 ALUMINUM STOREFRONT CLEAR ANODIZED
336 STUDY (SM) 336 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F4 ALUMINUM STOREFRONT CLEAR ANODIZED
338 STUDY (SM) 338 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F4 ALUMINUM STOREFRONT CLEAR ANODIZED
340 STUDY (SM) 340 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F4 ALUMINUM STOREFRONT CLEAR ANODIZED
344 FAMILY STUDY 344 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F4 ALUMINUM STOREFRONT CLEAR ANODIZED
344A MOTHERS ROOM 344A 3' - 0" 7' - 0" 1 3/4" D3 SOLID CORE WOOD VENEER-WV-01 F1 HOLLOW METAL PAINTED PNT-03
344B RESTROOM 344B 3' - 0" 7' - 0" 1 3/4" D3 SOLID CORE WOOD VENEER-WV-01 F1 HOLLOW METAL PAINTED PNT-03
346 TEST RM 346 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F1 HOLLOW METAL PAINTED PNT-03
348 TEST RM 348 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F1 HOLLOW METAL PAINTED PNT-03
350 TEST RM 350 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F1 HOLLOW METAL PAINTED PNT-03
354 STORAGE 352 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F1 HOLLOW METAL PAINTED PNT-03
356 TEST RM 356 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F1 HOLLOW METAL PAINTED PNT-03
358 TEST RM 358 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F1 HOLLOW METAL PAINTED PNT-03
360 TEST RM 360 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F1 HOLLOW METAL PAINTED PNT-03
364 ELEC 364 3' - 0" 7' - 0" 1 3/4" D3 SOLID CORE WOOD VENEER-WV-01 F1 HOLLOW METAL PAINTED PNT-03 Yes
370 TEST RM 370 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F1 HOLLOW METAL PAINTED PNT-03
372 TEST RM 372 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F1 HOLLOW METAL PAINTED PNT-03
374 TEST RM 374 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F1 HOLLOW METAL PAINTED PNT-03
378 TEST RM 378 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F1 HOLLOW METAL PAINTED PNT-03
380 TEST RM 380 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F1 HOLLOW METAL PAINTED PNT-03
382 TEST RM 382 3' - 0" 7' - 0" 1 3/4" D1 SOLID CORE WOOD VENEER-WV-01 F1 HOLLOW METAL PAINTED PNT-03
Grand total: 246
C.L. OF HARDWARE
3' - 4"
CL
SEE SCHEDULE
6"
VARIES
10"
D2
SOLID CORE WOOD,
DOUBLE WITH FULL LITE
G1 G1
6"VARIES 6"6"VARIES 6"
SEE SCHEDULE
C.L. OF HARDWARE
3' - 4"
CL
SEE SCHEDULE
6"
VARIES
10"
D4
ALUMINUM, DOUBLE*
G2 G2
6"VARIES 6"6"VARIES 6"
SEE SCHEDULESEE SCHEDULE
SEE SCHEDULE
6"
VARIES
10"
6"VARIES 6"
D1
SOLID CORE WOOD
WITH FULL LITE
G1
SEE SCHEDULE
SEE SCHEDULE
D3
SOLID CORE WOOD
SEE SCHEDULE
SEE SCHEDULE
6"
VARIES
10"
6"VARIES 6"
D5
ALUMINUM INTERIOR DOOR
WITH FULL LITE
G1
SEE SCHEDULE
D6
SOLID CORE WOOD, DOUBLE
SEE SCHEDULE
CL
G1 G1
D8
C.L. OF HARDWARE
3' - 4"
C.L. OF HARDWARE
3' - 4"
SEE SCHEDULE
SEE SCHEDULE
CLCLCLCL CL
4'-0"
2'-0"
FROSTED FILM ON
INSIDE OF GLASS
AT OFFICES ONLY
7 EQ PANELS
CONTRACTOR TO VERIFY OPENING
*EXTERIOR DOORS TO HAVE INSULATED GLASS,
INTERIOR DOORS TO HAVE SINGLE PANE
D12
MODERNFOLD,
7 PANEL
SEE SCHEDULE
WHITE MARKERBOARD
FINISH BOTH SIDES, TYP.
5 EQ PANELS
CONTRACTOR TO VERIFY OPENING
D13
MODERNFOLD,
5 PANEL
SEE SCHEDULE
“WHITE MARKERBOARD ON
CLASSROOM SIDE, FABRIC
ON PRESS ROOM SIDE”
CONTRACTOR TO VERIFY OPENING
D14
SKYFOLD
SEE SCHEDULE
WHITE MARKERBOARD
FINISH BOTH SIDES, TYP.
G3
SEE SCHEDULE
SEE SCHEDULE
D7
HOLLOW METAL DOOR
CL
C.L. OF HARDWARE
3' - 4"
C.L. OF HARDWARE
3' - 4"
D9
C.L. OF HARDWARE
3' - 4"
C.L. OF HARDWARE
3' - 4"
SEE SCHEDULE
6"VARIES 6"
D10
SOLID CORE WOOD
WITH HALF LITE
G1
CL
D11
SOLID CORE WOOD
WITH HALF LITE
G4 G4G4
G4
SEE SCHEDULE
SEE SCHEDULE
CL
G3
HOLLOW METAL
WITH HALF LITE
NOT USED
F1
PAINTED HOLLOW METAL
2"
SEE SCHEDULE
2"SEE SCH.2"
F3
PAINTED HOLLOW METAL
DOUBLE DOOR FRAME
2"
SEE SCHEDULE
2"SEE SCHEDULE 2"
F2
PAINTED HOLLOW METAL
WITH TEMPERED SIDE LITE
2"
SEE SCHEDULE
2"SEE SCH.
2"
1'-6"2"
F4
CLEAR ANODIZED ALUMINUM STOREFRONT
FRAME AND TEMPERED GLASS SIDE-LITE*
*SEE WINDOW SCHEDULE FOR SIZE, ORIENTATION,
AND LAYOUT OF ADJACENT GLAZING
2"
SEE SCHEDULE
2"SEE SCH.
2"
SEE GLAZING ELEVATIONS
VARIES 2"
G2 G2
2'-0"
4'-0"
FROSTED FILM ON INSIDE OF
GLASS AT OFFICES ONLY
G1 1/4" SINGLE CLEAR GLAZING MINIMUM PANE THICKNESS OR AS
REQUIRED FOR GLASS SIZES INDICATED - TEMPERED
GLAZING TYPE LEGEND
G2 1" INSULATED GLAZING UNIT - TEMPERED
G3 1/2" SINGLE PANE CLEAR GLAZING - TEMPERED
G4 GLAZING AS REQUIRED TO MAINTAIN 90 MINUTE DOOR AND FRAME
RATING
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
10/28/22
A602
Door Types
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
GENERAL NOTES - DOORS
1 ALL HOLLOW METAL FRAMES AND DOORS ARE TO BE PAINTED IF NOT NOTED OTHERWISE MATCH ADJACENT WALL FINISH
2 ALL INTERIOR HOLLOW METAL FRAME WIDTHS ARE TO MATCH WALL WIDTHS; COORDINATE WITH VERTICAL ASSEMBLY
TYPES
3 WOOD GRAIN DIRECTION TO BE VERTICAL, UNLESS NOTED OTHERWISE
4 FINISH OF HOLLOW METAL FRAMES TO MATCH ADJACENT IF NOT NOTED OTHERWISE
5 IF COLOR TRANSITIONS OCCUR, THEY ARE TO OCCUR AT INSIDE OF FRAME STOP
6 DOORS SERVING SPACES WITH AN OCCUPANT LOAD OF 50 OR MORE SHALL NOT BE PROVIDED WITH A LATCH OR LOCK
OTHER THAN PANIC HARDWARE. SEE DOOR HARDWARE SPECIFICATIONS
1/4" = 1'-0"
DOOR TYPES
1/4" = 1'-0"
DOOR FRAME TYPES
4' - 5"
4' - 2"
SF02
G1
FLOOR LEVEL
(VARIES)
3' - 0"
2" TYP.
7' - 2"
B6
A561
A5
A561
C6
A561
SA6
4' - 2"
4'-5"
SF03
G1
3' - 0"
FLOOR LEVEL
(VARIES)
4 1/2"
7' - 2"
D6
A561
C6
A561
B6
A561
A5
A561
2" TYP.
SA6
4' - 2"
SF04
G1 G1
3' - 0"
2" TYP.
FLOOR LEVEL
(VARIES)
7' - 2"
4 1/2"EQEQ
7'-3"
B6
A561
D6
A561
C6
A561
A5
A561
E6
A561
SA6
4' - 5"
SF05
G1
FLOOR LEVEL
(VARIES)
3' - 0"
2" TYP.
4' - 2"
7' - 2"
B6
A561
C6
A561
A5
A561
SA6
9' - 0"
11' - 1"
EQ EQ EQ
SF11
G2 G2 G2
2" TYP.
FLOOR LEVEL
(VARIES)
C6
A561
D4
A551
E4
A551
G2 G2 G2
B2
A431
11' - 1"
9' - 0"
1-F.5
SF09
G2G2
G2G2G2
1' - 10"
7' - 2"
2' - 6 1/2"
SCHEDULE
SEE 2' - 6 1/2"
2" TYP.
FLOOR LEVEL
(VARIES)
E4
A551
C6
A561
D4
A551
9' - 0"
23' - 2"
1-F.1 1-F.2
SF10
G2
G2
G2 G2 G2 G2
7' - 2"
1' - 10"
FLOOR LEVEL
(VARIES)
2" TYP.
E4
A551
C6
A561
D4
A551
4' - 6"
SCHEDULE
SEE 1' - 2"
SCHEDULE
SEE 4' - 6"
B5
A511
D3
A415
D2
A415
G2
G2 G2
23' - 2"
9' - 0"
1-F.4 1-F.3
SF08
G2 G2G2
G2 G2 G2 G2 G2
7' - 2"
1' - 10"
4' - 10"
SCHEDULE
SEE 1' - 6"
SCHEDULE
SEE 4' - 10"
2" TYP.
FLOOR LEVEL
(VARIES)
E4
A551
C6
A561
D4
A551
B2
A431
14'-9 1/2"
7'-2" TYP.
15'-9 1/2"11'-1 1/2"
SF12 SF13 SF15
G1 G1G1 G1 G1 G1 G1G1G1G1 G1 G1
SF14 SF16
EQ EQ EQ
2" TYP.
SCHEDULE
SEE EQ EQ
11'-1 1/2"
EQ EQ
2" TYP.2" TYP.2" TYP.2" TYP.
EQ EQ
11'-1 1/2"
EQ EQ EQ
124 125 127126 128
FLOOR LEVEL
(VARIES)
SCHEDULE
SEE
SCHEDULE
SEE
SCHEDULE
SEE
SCHEDULE
SEE
B6
A561
A2
A561
TYP
A6
A561
E6
A561
B5
A541
SA4.1
B2
A431
17' - 0"
7' - 2"
SF17
G1 132G1G1G1
EQ EQ EQ EQ
SCHEDULE
SEE
FLOOR LEVEL
(VARIES)
B6
A561
A2
A561
TYP
A6
A561
E6
A561
2"TYP.
SA4.1
4' - 2"
3' - 0"
7' - 2"
SF32
156
G1
G1 G1
FLOOR LEVEL
(VARIES)
G1
EQ EQ EQ
SCHEDULE
SEE
21'-1 1/2"
D6
A561
B6
A561
E6
A561
A5
A561
A5
A561
2" TYP.3'-10"4 1/2"
SA6
FLOOR LEVEL
(VARIES)
B6
A561
D6
A561
E6
A561
C6
A561
A5
A561
3' - 0"
4' - 2"
7' - 2"
10' - 7"
4 1/2"EQ EQ EQ 2"TYP.
SF33
G1G1G1
SA6
10'-1 1/2"
7'-2"
158
SF34
G1 G1
EQ EQ
SCHEDULE
SEE 2" TYP.
FLOOR LEVEL
(VARIES)
B6
A561
E6
A561
A6
A561
C6
A561
SA4
192A
7' - 2"
10'-9"
SF20
G1 G1
EQ EQ
SCHEDULE
SEE 2" TYP.
FLOOR LEVEL
(VARIES)
B6
A561
C6
A561
A6
A561
E6
A561
SA4
7' - 2"
SF21
G1192
2" TYP.
9' - 10"
FLOOR LEVEL
(VARIES)
SCHEDULE
SEE 3' - 4"
B6
A561
C6
A561
A6
A561
SA4
7' - 2"
188
SF22
G1
2" TYP.
SCHEDULE
SEE 5'-0"
8'-6"
FLOOR LEVEL
(VARIES)
B6
A561
C6
A561
A6
A561
SA4
188B
SF23
G1G1
7' - 2"
2" TYP.
SCHEDULE
SEE EQ EQ
9'-8"
FLOOR LEVEL
(VARIES)
B6
A561
C6
A561
A6
A561
E6
A561
SA4
179
10'-4"
G1
2" TYP.
SCHEDULE
SEE
7'-2"
FLOOR LEVEL
(VARIES)
G1
SF24A
EQEQ
10'-2"
2" TYP.
SCHEDULE
SEEEQEQ
178G1G1
SF24B
B6
A561
E6
A561
A6
A561
A2
A561
TYP
SA4.1
SF25 SF26
G1G1G1G1
FLOOR LEVEL
(VARIES)
EQ EQ EQ EQ EQ
G1
7' - 2"
2" TYP.
B6
A561
E6
A561
A5
A561
C6
A561
170.2
G1 G1
SCHEDULE
SEE 1' - 2"2" TYP.5' - 2"
10' - 0"
SA6.1 SB3.1 SA6.1
18'-0"
FLOOR LEVEL
(VARIES)
B5
A541
E6
A561
A6
A561
A2
A561
TYP
B6
A561
SF28
G1170AG1
SF27
G1170BG1
10'-0"10'-0 1/4"
SCHEDULE
SEE EQEQ
SCHEDULE
SEE EQEQ
7'-2"
2" TYP.
SA4.1
SF29
170.1G1 G1
FLOOR LEVEL
(VARIES)
7' - 2"
EQ
SCHEDULE
SEE EQ
9' - 0"
2" TYP.
B6
A561
C6
A561
A6
A561
SA4.1
11'-8"
204
7' - 2"
SF35
G1G1
2" TYP.
SCHEDULE
SEE EQ EQ
FLOOR LEVEL
(VARIES)
4 1/2"
D6
A561
A2
A561
TYP
A6
A561
E6
A561
SA4.1
206
4'-5 1/2"
7'-2"
SF36
G1
SCHEDULE
SEE
D6
A561
4 1/2"
9"
A2
A561
TYP
A6
A561
9'-11 1/2"
208
SF37
G1 G1
EQ EQ
SCHEDULE
SEE
9'-11 1/2"
EQ EQ
210
SF38
G1 G1
SCHEDULE
SEE
10'-5 1/2"
EQEQ
212
SF39
G1 G1
SCHEDULE
SEE 2" TYP.
FLOOR LEVEL
(VARIES)
E6
A561
B5
A541
SA4.1
G1214G1G1
SF40
2" TYP.
SCHEDULE
SEE EQ EQ EQ
13' - 11 1/2"
7' - 2"
SF41
G1216G1G1
13' - 11 1/2"
218
SF42
G1G1G1
EQ EQ EQ
12' - 4"
FLOOR LEVEL
(VARIES)
E6
A561
B6
A561
A2
A561
TYP
A6
A561
SCHEDULE
SEE EQEQEQ
SCHEDULE
SEE
B5
A541
SA4.1
FLOOR LEVEL
(VARIES)
E5
A561
A2
A561
TYP
A6
A561
7'-5"
SCHEDULE
SEE 2" TYP.3'-11"
7'-2"
SF18
SA4
G1 134
1-U.3 1-U.4
SF31
G2 G2 G2
G2 G2 G2 G2 G2
1' - 4"
7' - 2"
8' - 6"
2" TYP.
FLOOR LEVEL
(VARIES)
EQ
SCHEDULE
SEE EQ
SCHEDULE
SEE EQ
VERIFY
16'-9 1/2"
B6
A561
C6
A561
A6
A561
1-U.1 1-U.2
SF30
G2 G2 G2
G2 G2 G2 G2 G2
1' - 4"
7' - 2"
8' - 6"
EQ
SCHEDULE
SEE EQ
SCHEDULE
SEE EQ
VERIFY
16'-3"
2" TYP.
FLOOR LEVEL
(VARIES)
B6
A561
C6
A561
A6
A561
SF19A
G1G1
7' - 2"
FLOOR LEVEL
(VARIES)
SCHEDULE
SEE 2" TYP.
10'-3"
EQ EQ
114A
B6
A561
C6
A561
A6
A561
E6
A561
SA4
SF01
022
G1 G1 G1
7' - 2"
13'-3 1/2"
4' - 2"
3' - 0"
FLOOR LEVEL
(VARIES)
SCHEDULE
SEE
C6
A561
A4
A561
A5
A561
E6
A561
EQ EQ EQ 2" TYP.
SA6
EQ EQ
016
G1
G1
SF06
FLOOR LEVEL
(VARIES)
SCHEDULE
SEE 2" TYP.
3' - 0"
4' - 2"
7' - 2"
8'-10"
D6
A561
C6
A561
A5
A561
E6
A561
SA6
SF07
G1 G1G1G1G1G1G1G1
FLOOR LEVEL
(VARIES)
25'-9"
3' - 0"
4' - 2"
4 1/2"
7' - 2"
EQEQEQEQEQEQEQEQ2" TYP.
D6
A561
E6
A561
C5
A561
C6
A561
A5
A561 SA6
G1 1/4" SINGLE CLEAR GLAZING MINIMUM PANE THICKNESS OR AS
REQUIRED FOR GLASS SIZES INDICATED - TEMPERED
GLAZING TYPE LEGEND
G2 1" INSULATED GLAZING UNIT - TEMPERED
G3 1/2" SINGLE PANE CLEAR GLAZING - TEMPERED
G4 GLAZING AS REQUIRED TO MAINTAIN 90 MINUTE DOOR AND FRAME
RATING
SF19B
G1 G1 G1
7' - 2"
1' - 4"
10'-7"
EQ EQ EQ
C5
A561
C6
A561
E6
A561
A5
A561
FLOOR LEVEL
(VARIES)
2" TYP.
SA4
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
10/28/22
A604
Window
Types &
Glazing
Schedule
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
GLAZING GENERAL NOTES
1 CONTRACTOR TO CONFIRM AND VERIFY QUANTITIES OF ALL GLAZING TYPES
2 ALL GLAZING DIMENSIONS TO BE FIELD VERIFIED PRIOR TO BIDDING, ORDERING, AND INSTALLING
3 ROUGH OPENING REQUIREMENTS SHALL BE COORDINATED WITH WINDOW MANUFACTURER, TYP
4 ALL CURTAINWALL SYSTEMS REQUIRE DELEGATED DESIGN SUBMITTAL
5 SEE DOOR SCHEDULE FOR SCHEDULED GLAZING WITHIN DOORS
6 SEE FLOOR PLAN AND ELEVATIONS FOR WALL TYPE AND MATERIAL CONDITION IN REFERING TO WINDOW AND
STOREFRONT DETAILS
7 ALL GLAZING SHALL BE FULLY TEMPERED IN ACCORDANCE WITH IBC 2406.4
8 JOINTS AROUND STOREFRONTS ARE TO BE EVEN AND EQUAL. NO VARYING WIDTHS.
9 CLEAR SILICONE CAULK AT BUTT GLAZING. BLACK AT STOREFRONT EDGES.
10 HORIZONTAL STOREFRONT MULLIONS ARE 2" X 4 1/2", TYPICAL.
11 VERTICAL STOREFRONT MULLIONS ARE 2" X 4 1/2", TYPICAL, UNLESS OTHERWISE NOTATED.
SF50
G1288A
9'-9"
SCHEDULE
SEE 6' - 3"
7' - 2"
2" TYP.
B6
A561
A2
A561
TYP
A6
A561
SA4.1
3' - 5 1/2"
SCHEDULE
SEE
6' - 11 1/2"
3' - 5 1/2"
SCHEDULE
SEE
6' - 11 1/2"
3' - 5 1/2"
SCHEDULE
SEE
6' - 11 1/2"
3' - 5 1/2"
SCHEDULE
SEE
6' - 11 1/2"
7' - 2"
2" TYP.
B5
A541
SF52
G1 288E
SF54
288G
SF53
288F
SF51
G1 288D
B6
A561
A6
A561
A2
A561
TYP
SA4.1
5'-4 1/2"9'-5"
2" TYP.1'-10 1/2"
SCHEDULE
SEE
SCHEDULE
SEE EQ EQ
7' - 2"
SF67
G1252AG1
SF66
G1 252B
C5
A561
E6
A561
A5
A541
B5
A561
SA4.1
8'-2 1/2"
7' - 2"
252C
4'-8 1/2"
SCHEDULE
SEE 2" TYP.
SF68
G1
B6
A561
A6
A561
C6
A561
SA4.1
20'-11"
7' - 2"
EQEQEQEQEQ
SCHEDULE
SEE4 1/2"1' - 0"2" TYP.
SF60
G1270.1 G1 G1 G1 G1G1
B6
A561
E6
A561
C6
A561
A6
A561
D6
A561
SA4.1
7' - 2"
3'-10 1/2"
4 1/2"3'-1 1/2"4 1/2"
2"
2"
G1
D6
A561
C6
A561
A6
A561SF59
SA4.1
SF63
G1268G1
SF62
G1267G1
SF61
G1266G1
10' - 3 1/4"10' - 0 3/4"9' - 9 3/4"
SCHEDULE
SEE EQEQ
SCHEDULE
SEE EQEQ
SCHEDULE
SEE EQEQ
7' - 2"
B6
A561
E6
A561
A2
A561
TYP
A6
A561
2" TYP.
SA4.1
8'-8 1/2"
269
SCHEDULE
SEE EQEQ
34'-4 1/2"
4 1/2"EQ EQ EQ EQ EQ EQ EQ EQ
SCHEDULE
SEE
7' - 2"
2" TYP.
SF58
G1G1
SF57
G1 270.2G1G1G1G1G1G1G1
B6
A561
E6
A561
A5
A541
C6
A561
A6
A561
D6
A561
SA4.1
SF55A
G1270H
8'-2 1/2"
SCHEDULE
SEE 4'-8 1/2"
7' - 2"
B6
A561
A6
A561
A2
A561
TYP
SA4.1
SF55B
G1 270G
5'-11"
2'-5"
SCHEDULE
SEE 2" TYP.
EQ EQ EQ EQ EQ EQ EQ EQ
7' - 2"
36'-4"
SF70
G1 G1 G1 G1 G1 G1 G1 G1
2" TYP.4 1/2"
D6
A561
E5
A561
C6
A561
A6
A561
SA4.1
11'-7"
304302
6'-10"
7'-2"
SF72
G1G1
SF71
G1
EQEQ
SCHEDULE
SEE 2" TYP.4 1/2"3'-1 1/2"
SCHEDULE
SEE
B5
A541
D6
A561
E6
A561
A6
A561
A2
A561
TYP
SA4.1
13'-1 1/4"10'-5 1/2"9'-5"10'-4 1/4"
7'-2"
314 316 318 320
SF73
G1G1
SF74
G1G1
SF75
G1G1
SF76
G1G1
EQ EQ EQ
SCHEDULE
SEE EQ EQ
SCHEDULE
SEE EQ EQ
SCHEDULE
SEE EQ EQ
SCHEDULE
SEE 2" TYP.
B6
A561
E6
A561
B5
A541
A6
A561
A2
A561
TYP
SA4.1
G1
EQ EQ EQ EQ EQ EQ EQ EQ EQ
SCHEDULE
SEE EQEQ 2'-4 1/2"
SCHEDULE
SEE 4 1/2"
23'-8"14' - 10"7' - 2 1/2"6'-3"
7' - 2"
4' - 2"
3' - 0"
SF79
G1G1
SF77
G1
SF78
326G1G1G1
SF80
G1
G1G1
G1
G1G1
328
B6
A561
E6
A561
B5
A541
D6
A561
A4
A561
A5
A561
C6
A561
A6
A561
C6
A561
B6
A561
A4
A561
SA4.1
SA6.1
2" TYP.
27'-2"
7' - 2"
4 1/2"EQ EQ EQ EQ EQ EQ EQ 4 1/2"
SF81
G1 G1 G1 G1 G1 G1
D6
A561
D6
A561
E6
A561
A6
A561
C6
A561
SA4.1
2"
2"
G1
36'-7 1/2"
7' - 2"
EQEQEQEQEQEQEQEQEQ
SF69
G1 G1 G1 G1 G1 G1 G1 G1 G1
B6
A561
E6
A561
C6
A561
A6
A561
SA4.1
7' - 2"
226G1G1
EQEQ
SCHEDULE
SEE 2" TYP.
11'-4 1/2"
B6
A561
E6
A561
A6
A561
C6
A561
SF43
SA4.1
G17'-2"
EQEQ 4 1/2"2" TYP.
6'-5 1/2"
D6
A561
E6
A561
B6
A561
A6
A561
A6
A561
SF44
G1
SA4.1
7' - 2"
G1G1228 G1 G1G1G1 G1G1G1G1
4 1/2"EQ EQ
SCHEDULE
SEE EQ EQ 2" TYP.
20'-3"
SF45 SF46
EQ EQ EQ EQ EQ EQ
28' - 3"
2" TYP.
D6
A561
B6
A561
E6
A561
A6
A561
C6
A561
SA4.1
4'-6"
7'-2"
SF47
G1
4 1/2"3'-11 1/2"2" TYP.
B6
A561
D6
A561
C6
A561
A6
A561
SA4.1
EQ EQ EQ EQ EQ EQ EQ
29'-7"
SF49
G1
SF48
G1 G1 G1 G1 G1 G1 G1G1
EQEQ
8'-7 1/2"
OPEN
TO
BEYOND
D6
A561
E6
A561
B6
A561
B6
A561
A6
A561
2" TYP.4 1/2"
7' - 2"
SA4.1
G1 1/4" SINGLE CLEAR GLAZING MINIMUM PANE THICKNESS OR AS
REQUIRED FOR GLASS SIZES INDICATED - TEMPERED
GLAZING TYPE LEGEND
G2 1" INSULATED GLAZING UNIT - TEMPERED
G3 1/2" SINGLE PANE CLEAR GLAZING - TEMPERED
G4 GLAZING AS REQUIRED TO MAINTAIN 90 MINUTE DOOR AND FRAME
RATING
EQEQEQEQ 5' - 0"
SCHEDULE
SEE 2" TYP.
19' - 8 1/2"8'-6"
7' - 2"
SF64
G1 G1G1 G1
SF65
G1 256.2
E6
A561
B6
A561
B6
A561
A6
A561
C6
A561
256.1
SA4
SCHEDULE
SEE
6'-10"7'-10 1/2"15'-1"
7' - 2"
EQ EQ EQ EQ EQ EQ EQ EQ4 1/2"
SF84
G1 G1G1 G1
SF82
G1 G1
SF83
G1G1
D6
A561
B6
A561
E6
A561
C6
A561
A6
A561
B6
A561
2"TYP.
SA4.1
332 334 336 338 340
11'-11 1/2"11'-3 1/2"11'-8 1/2"11'-8 1/2"11'-8 1/2"8'-4 1/2"
4' - 10 1/2"
SCHEDULE
SEE
SCHEDULE
SEE
SCHEDULE
SEE
SCHEDULE
SEE
SCHEDULE
SEE
SCHEDULE
SEEEQEQEQEQEQEQEQEQEQEQ
7' - 2"
2" TYP.
SF86
G1G1
SF87
G1G1
SF88
G1G1
SF89
G1G1
SF90
G1G1
SF85
330G1
B6
A561
A2
A561
TYP
A6
A561
B5
A541
SA4.1
EQ EQ EQ
SCHEDULE
SEE 2" TYP.
15' - 0"
7' - 2"
SF91
344G1G1G1
B6
A561
A6
A561
C6
A561
E6
A561
SA4
SF56
G1
SA4.1
G1 G1
10'-0 1/2"
EQEQEQ 2" TYP.
7'-2"
E6
A561
B6
A561
C6
A561
A6
A561
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
10/28/22
A605
Window
Types &
Glazing
Schedule
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
GLAZING GENERAL NOTES
1 CONTRACTOR TO CONFIRM AND VERIFY QUANTITIES OF ALL GLAZING TYPES
2 ALL GLAZING DIMENSIONS TO BE FIELD VERIFIED PRIOR TO BIDDING, ORDERING, AND INSTALLING
3 ROUGH OPENING REQUIREMENTS SHALL BE COORDINATED WITH WINDOW MANUFACTURER, TYP
4 ALL CURTAINWALL SYSTEMS REQUIRE DELEGATED DESIGN SUBMITTAL
5 SEE DOOR SCHEDULE FOR SCHEDULED GLAZING WITHIN DOORS
6 SEE FLOOR PLAN AND ELEVATIONS FOR WALL TYPE AND MATERIAL CONDITION IN REFERING TO WINDOW AND
STOREFRONT DETAILS
7 ALL GLAZING SHALL BE FULLY TEMPERED IN ACCORDANCE WITH IBC 2406.4
8 JOINTS AROUND STOREFRONTS ARE TO BE EVEN AND EQUAL. NO VARYING WIDTHS.
9 CLEAR SILICONE CAULK AT BUTT GLAZING. BLACK AT STOREFRONT EDGES.
10 HORIZONTAL STOREFRONT MULLIONS ARE 2" X 4 1/2", TYPICAL.
11 VERTICAL STOREFRONT MULLIONS ARE 2" X 4 1/2", TYPICAL, UNLESS OTHERWISE NOTATED.
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
10/28/22
A611
Finish
Schedules,
Accessory
Schedules
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
SCHEDULED MATERIALS AND FINISHES SHALL BE USED FOR BASIS OF DESIGN U.N.O.
FINISH SCHEDULE
CODE PRODUCT TYPE MANUFACTURER STYLE COLOR SPECIFICATION FINISH NOTES/ REMARKS
DIVISION 03 - CONCRETE
CNC-01 SEALED CONCRETE EXISTING CONCRETE FLOOR TO BE PREPED FOR SEALED CONCRETE, CARPET TILE GLUE REMOVED, ETC.
DIVISION 06 - WOODS, PLASTICS & COMPOSITES
FRP-01 FIBER-GLASS REINFORCED PANEL MARLITE SMOOTH S100G WHITE @ ALL JANITOR SINKS, COORDINATING FACTORY TRIM PROVEDED AT ALL OUTSIDE EDGES, INSTALLATION PER MANUFACTURERS INSTRUCTIONS
PL-01 PLASTIC LAMINATE FORMICA STANDARD HPL | MATTE FINISH PLATINUM 902-58 BASE CABINETS
PL-02 PLASTIC LAMINATE FORMICA STANDARD HPL | MATTE FINISH PALOMA POLAR COUNTERTOPS
PL-03 PLASTIC LAMINATE NEVAMAR STANDARD HPL - S7040-T SPA WHITE UPPER CABINETS
PL-04 PLASTIC LAMINATE WILSONART STANDARD HPL LANDMARK WOOD 7981
WV-01 WOOD VENEER RIFT CUT, WHITE OAK STAINED TO MATCH ARCHITECT SAMPLE, CLEAR FINISH GRAIN TO RUN VERTICAL
DIVISION 08 - OPENINGS
GP-01 GLASS PANEL 3FORM LOW IRON GLASS, MONOLITHIC ARCTIC BLUE 1/4" GAUGE, SATIN FINISH, FOLLOW MANUFACTURERS INSTRUCTIONS FOR CUTTING
GP-02 GLASS PANEL 3FORM LOW IRON GLASS, MONOLITHIC POLAR D04 1/4" GAUGE, SATIN FINISH, FOLLOW MANUFACTURERS INSTRUCTIONS FOR CUTTING
DIVISION 09 - BASE & TRANSITIONS
TS-01 METAL COVE BASE SCHLUTER DILEX-AHK SATIN ANNODIZED ALUMINUM HEIGHT TO MATCH MATERIAL THICKNESS. INTSTALL PER MANUFACTURERS INSTRUCTIONS.
TS-02 METAL FLOOR TRANSITION STRIP SCHLUTER SCHIENE SATIN ANNODIZED ALUMINUM HEIGHT TO MATCH MATERIAL THICKNESS. INTSTALL PER MANUFACTURERS INSTRUCTIONS.
TS-03 METAL EDGE TRIM SCHLUTER JOLLY SATIN ANNODIZED ALUMINUM HEIGHT TO MATCH MATERIAL THICKNESS. INTSTALL PER MANUFACTURERS INSTRUCTIONS. RE: INTERIOR DETAILS FOR INSTALLATION LOCATION TYPES, RE: ELEVATIONS FOR LOCATIONS
TS-04 RUBBER FLOOR TRANSITION JOHNSONITE SLT-XX-L 29 MOON ROCK WG CARPET TO CONCRETE/SUBFLOOR TRANSITION, 100% VULCANIZED RUBBER TRANSITION STRIP, INSTALLATION PER MANUFACTURERS INSTRUCTIONS, RE: FINISH PLANS AND INTERIOR DETAILS FOR
LOCATIONS/INSTANCES, CONTRACTOR TO VERIFY PRODUCT FIT WITH SCHEDULED FLOORING
TS-05 RUBBER FLOOR TRANSITION JOHNSONITE SLT-XX-C 29 MOON ROCK WG CARPET TO LVT TRANSITION, 100% VULCANIZED RUBBER TRANSITION STRIP, INSTALLATION PER MANUFACTURERS INSTRUCTIONS, RE: FINISH PLANS AND INTERIOR DETAILS FOR
LOCATIONS/INSTANCES, CONTRACTOR TO VERIFY PRODUCT FIT WITH SCHEDULED FLOORING
TS-06 RUBBER FLOOR TRANSITION JOHNSONITE CTA-XX-L 29 MOON ROCK WG WOOD FLOOR TO CARPET TRANSITION, 100% VULCANIZED RUBBER TRANSITION STRIP, INSTALLATION PER MANUFACTURERS INSTRUCTIONS, RE: FINISH PLANS AND INTERIOR DETAILS FOR
LOCATIONS/INSTANCES, CONTRACTOR TO VERIFY PRODUCT FIT WITH SCHEDULED FLOORING
TS-07 RUBBER STAIR NOSING JOHNSONITE VCD-XX 29 MOON ROCK WG 100% VULCANIZED RUBBER TRANSITION STRIP, INSTALLATION PER MANUFACTURERS INSTRUCTIONS, RE: FINISH PLANS AND INTERIOR DETAILS FOR LOCATIONS/INSTANCES, CONTRACTOR TO VERIFY
PRODUCT FIT WITH SCHEDULED FLOORING
WB-01 RUBBER WALL BASE TARKETT/JOHNSONITE 4" TRADITIONAL WALL BASE, WITH TOE 34 ALMOND INSTALLATION PER MANUFACTURERS INSTRUCTIONS, RE: FINISH PLANS AND ELEVATIONS FOR LOCATIONS
WB-02 TILE BASE EMSER BORIGNI GRAY 3"X12", INSTALL ADJACENT TO TL-01 FLOOR TILE, DO NOT INSTALL BELOW TL-02 WALL TILE, TS-03 REQUIRED AT TOP EDGE IF UNFINISHED/RAW
WB-03 RUBBER WALL BASE TARKETT/JOHNSONITE 4" TRADITIONAL WALL BASE WITH TOE 18 NAVY BLUE INSTALLATION PER MANUFACTURERS INSTRUCTIONS, RE: FINISH PLANS AND ELEVATIONS FOR LOCATIONS COORDINATES WITH PNT-04
WB-04 RUBBER WALL BASE TARKETT/JOHNSONITE 4" TRADITIONAL WALL BASE WITH TOE TA5 COLONIAL GREY CG INSTALLATION PER MANUFACTURERS INSTRUCTIONS, RE: FINISH PLANS AND ELEVATIONS FOR LOCATIONS COORDINATES WITH PNT-05 AND GRAY LAMINATE (PL-01)
WB-05 WOOD WALL BASE N/A 4" MDF WALL BASE, EASED SQUARE EDGE PAINTED TO MATCH PNT-01 @LEVEL 1 FIREPLACE WALL BASE, RE: ELEVATIONS + FINISH PLANS FOR ALL LOCATIONS
WB-06 WOOD WALL BASE N/A 4" MDF WALL BASE, EASED SQUARE EDGE PAINTED TO MATCH PNT-04 @LEVEL 1 CIRC AREA GYP WALL, RE: ELEVATIONS + FINISH PLANS FOR LOCATIONS
WB-07 WOOD WALL BASE N/A 4" MDF WALL BASE WOOD VENEER FINISH, WV-01 SQUARE, EASED EDGE @RE: FINISH PLANS AND ELEVATIONS FOR LOCATIONS
WB-08 RUBBER WALL BASE TARKETT/JOHNSONITE 4" TRADITIONAL WALL BASE WITH TOE TANNER WB TA1 INSTALLATION PER MANUFACTURERS INSTRUCTIONS, RE: FINISH PLANS AND ELEVATIONS FOR LOCATIONS COORDINATES WITH WV-01 MILLWORK
DIVISION 09 - CEILINGS
ACP-01 ACOUSTICAL CEILING PANEL USG 2110 RADAR WHITE 24" X 24" USG 15/16" DONN SUSPENSION SYSTEM
ACP-02 ACOUSTICAL CEILING PANEL ARMSTRONG TECTUM PAINT TO MATCH ADJACENT CEILING COLOR 1" THICK HIGH NRC PANELS WITH SQUARE EDGE
DIVISION 09 - FLOORS
CPT-01 CARPET TILE INTERFACE SILVER LININGS SL920 | #138780AK00 104514 NICKEL LINE 25CM X 1M, ASHLAR INSTALLATION, DIRECT GLUE, INSTALLATION PER MANUFACTURERS INSTALLATION INSTRUCTIONS, RE: FINISH PLANS FOR LOCATIONS AND INSTALLATION DIRECTION
CPT-02 CARPET TILE INTERFACE UR501 | #127340AK0 103616 NAVY 25CM X 1M, ASHLAR INSTALLATION, DIRECT GLUE, INSTALATION PER MANUFACTURERS INSTALLATION INSTRUCTIONS, RE: FINISH PLANS FOR LOCATIONS AND INSTALLATION DIRECTION
CPT-03 CARPET TILE INTERFACE UR501 | #127340AK0 103616 NAVY 25CM X 1M, ASHLAR INSTALLATION, DIRECT GLUE, INSTALATION PER MANUFACTURERS INSTALLATION INSTRUCTIONS, RE: FINISH PLANS FOR LOCATIONS AND INSTALLATION DIRECTION
EM-01 CARPET TILE INTERFACE STEP REPEAT 104940 IRON 19.69" X 19.69", MONOLITHIC INSTALLATION PATTERN, DIRECT GLUE, INSTALLATION PER MANUFACTURERS INSTALLATION INSTRUCTIONS, RE: FINISH PLANS FOR LOCATIONS AND INSTALLATION
DIRECTION
RF-01 LUXURY VINYL TILE TARKETT ID LATITUDE WOOD BRINED 4692 6"X48", 20 MIL, ASHLAR INSTALLATION, RE: FINISH PLANS FOR LOCATIONS AND FLOORING DIRECTION, DIRECT GLUE, INSTALLATION PER MANUFACTURERS INSTRUCTIONS
WDF-01 ENGINEERED WOOD FLOOR UPTOWN FLOORS AUTHENTIC AMERICAN WITH CONTRASTING WOOD PEGS WHITE OAK RICH RESERVE ENGINEERED, 3/4" X 6 1/4" WIDTH, FINISH BY MFGR TWO WOOD PEGS AT END OF EACH BOARD
DIVISION 09 - PAINT & WALLCOVERING
PNT-01 FIELD WALL PAINT SHERWIN-WILLIAMNS CASHMERE OYSTER BAR SW7565 MEDIUM LUSTRE
PNT-02a FIELD CEILIING PAINT SHERWIN-WILLIAMNS BYUI STANDARD FOR CEILING PAINT OYSTER BAR SW7565 FLAT FINISH
PNT-02b EXPOSED WAFFLE CEILING PAINT SHERWIN-WILLIAMNS BYUI STANDARD FOR CEILING PAINT DORIAN GRAY SW7017 FLAT FINISH
PNT-02c ACCENT CEILING PAINT SHERWIN-WILLIAMNS BYUI STANDARD FOR CEILING PAINT TO MATCH: BENJAMIN MOORE 2063-20 DOWNPOUR BLUE FLAT FINISH
PNT-03 TRIM PAINT (HOLLOW METAL DOORS/
FRAMES)
SHERWIN-WILLIAMNS BYUI STANDARD FOR DOOR + DOOR FRAME PAINT OYSTER BAR SW7565 ACRYLIC, DTM, MEDIUM LUSTRE
PNT-04 ACCENT PAINT SHERWIN WILLIAMS CASHMERE TO MATCH: BENJAMIN MOORE 2063-20 DOWNPOUR BLUE
PNT-05 ACCENT PAINT SHERWIN WILLIAMS CASHMERE DORIAN GRAY SW7017
PNT-06 ACCENT PAINT SHERWIN WILLIAMS CASHMERE TO MATCH: BENJAMIN MOORE 2005-10 RED ROCK
WC-01 WALL COVERING KOROSEAL WALLTALKER: JUST-RITE, JR60-00 WHITE LEVEL 5 FINISH PROVIDED ON GYP SURFACE, INSTALLATION PER MANUFACTURER'S INSTALLATION INSTRUCTIONS, RE: ELEVATIONS AND FINISH PLANS FOR LOCATIONS, MUD/SUBSTRATE PROVIDED AT
CMU BLOCK WALLS
WC-02 WALL COVERING FORBO BULLETIN BOARD OYSTER SHELL 2206 RE: ELEVATIONS FOR LOCATIONS, INSTALLATION PER MANUFCATURERS INSTRUCTIONS
WC-03 WALL COVERING HOVIA SAFARI (KIDS MAP WALLPAPER MURAL) CUSTOM FIT TO WALL LEVEL 5 FINISH, RE: ELEVATIONS FOR LOCATIONS, INSTALLATION PER MANUFCATURERS INSTRUCTIONS
DIVISION 09 - TILE
TL-01 FLOOR TILE EMSER TILE BORIGNI GRAY SATIN, 12"X23", STACKED BOND INSTALLATION, GROUT: , RE: FINISH PLANS FOR LOCATIONS
TL-02 WALL TILE DALTILE COLOR WHEEL K775 MATTE BISCUIT 4"X12",VERTICAL STACKED BOND INSTALLATION, RE: ELEVATIONS + FINISH PLANS FOR LOCATIONS, FULL TILE AT TOP ROW
DIVISION 10 - SPECIALTIES
CG-01 CORNER GUARD TO MATCH BYUI STANDARD STAINLESS STEEL 1 1/2"x1 1/2"x8', INSTALLED AT ALL OUTSIDE CORNERS IN PUBLIC SPACES
PR-01 PICTURE RAIL
SP-01 PARTITION WALL B+N INDUSTRIES SORBETTI 2.0 POLES: BLACK ANODIZED - 039, PANELS: TRANSLUCENT FLOOR TO CEILING POLES, RE: RCP'S FOR HEIGHT, RE: ELEVATIONS FOR QTY, SPANNING TRANSULCENT PANELS, RE: ELEVATIONS FOR QTY, 48"X96" TRANSLUCENT PANELS
SP-02 PARTITION WALL B+N INDUSTRIES SORBETTI 2.0 POLES: BLACK ANODIZED - 039, PANELS: TRANSLUCENT FLOOR TO CEILING POLES, RE: RCP'S FOR HEIGHT, RE: ELEVATIONS FOR QTY, SPANNING TRANSULCENT PANELS, RE: ELEVATIONS FOR QTY, CUSTOM SIZE 24"X48" TRANSLUCENT PANELS
SP-03 SLAT DISPLAY WALL ULINE SLATWALL PANELS H-4776 PAINT READY PAINTED WITH PNT-05 (DORIAN GRAY SW7017)4X8 PANELS, HORIZONTAL WALL SLATS FOR DISPLAY, ALUMINUM SLATWALL INSERTS #H-5064, PROVIDED AT EACH CHANNEL, INSTALLATION PER MANUFACTURERS RECOMMENDATION, DISPLAY
ACCESSORIES TO BE COORDINATED WITH OWNER/ARCHITECT
DIVISION 12 - FURNISHINGS
FB-01 UPHOLSTERY FABRIC JUSTIN DAVID PATTON OCEANIC @BOOTH SEAT
FB-02 UPHOLSTERY FABRIC MAHARAM COLUMN 466192 007 NAVY @ BOOTH SEAT BACK, STRIPES IN PATTERN TO RUN VERTICAL
RS-01 ROLLER SHADES DRAPER SINGLE SHADE 3% OPENESS, MANUAL SCREEN FABRIC: MERMET E SCREEN, PEARL GRAY SURFACE MOUNT WITH FASCIA COVER
RS-02 ROLLER SHADES DRAPER DUAL SHADE 3% OPENESS + BLACKOUT, MANUAL SCREEN FABRIC: MERMET E SCREEN, PEARL GRAY -
SS-01 SOLID SURFACE COUNTERTOP WILSONART STANDARD MYSTIQUE 9200CS 1/2 THCKNESS, SQUARE, EASED EDGES
SS-02 SOLID SURFACE WILSONART STANDARD RELAXED WHITE 9247SS 5/8" THICK STOCK CUT (NO EARS OR DRIP), 5/8"
OVERHANG
ST-01 QUARTZ COUNTERTOP DALTILE ONE QUARTZ NQ51 CABRINI GREY 2CM
ST-02 QUARTZ COUNTERTOP DALTILE ONE QUARTZ NQ09 WOVEN WOOL 2CM
ACCESSORY SCHEDULE
CODE PRODUCT TYPE MANUFACTURER FINISH MAKE/MODEL COMMENTS
10.03 WALL MOUNTED SOAP DISPENSER OWNER PROVIDED/ OWNER INSTALLED
10.05 TOILET PAPER DISPENSER OWNER PROVIDED/ OWNER INSTALLED
10.06 PAPER TOWEL DISPENSER OWNER PROVIDED/ OWNER INSTALLED
10.08 42" GRAB BAR BOBRICK SATIN-FINISH STAINLESS STEEL B-2111 INSTALL PER MANUFACTURER'S RECOMMENDATIONS
10.09 18" GRAB BAR BOBRICK SATIN-FINISH STAINLESS STEEL B-2111 INSTALL PER MANUFACTURER'S RECOMMENDATIONS
10.10 36" GRAB BAR BOBRICK SATIN-FINISH STAINLESS STEEL B-2111 INSTALL PER MANUFACTURER'S RECOMMENDATIONS
10.15 BABY CHANGING STATION KOALABEAR STAINLESS STEEL KB310-SSRE INSTALL PER MANUFACTURER'S RECOMMENDATIONS
10.18 SANITARY NAPKIN DISPOSAL OWNER PROVIDED/ OWNER INSTALLED
10.20 FRAMELESS MIRROR N/A PENCIL EDGE GRIND CUSTOM FRAMELESS MIRROR ADHERED DIRECTLY TO FINISHED WALL, RE: ELEVATIONS FOR SIZES
10.40 ACTIVITY WALL PANEL LEARNING ADVANTAGE GREEN CROCODILE ACTIVITY WALL PANEL INSTALL PER MANUFACTURER'S RECOMMENDATIONS, CONTRACTOR TO PROVIDE BLOCKING
11.09 ELECTRIC FIREPLACE CORRETTO BLACK 72" CORRETTO WALL-MOUNT ELECTRIC FIREPLACE BY REAL FLAME, MODEL #1360E INSTALL PER MANUFACTURER'S RECOMMENDATIONS
HARDWARE SCHEDULE
PRODUCT TYPE MODEL FINISH SPECIFICATIONS
CABINET PULL AMEROCK EDGE PULL SATIN NICKEL 3.75"
CABINET LOCKS OLYMPUS LOCKS PER CAMPUS STANDARD
DESK GROMMET MOCKETT MAX2/A SMALL SQUARE DESK GROMMET SATIN ALUMINUM 94 3 15/16"
WALL HOOKS RICHELIEU DOUBLE ROBE HOOK, NH1253021195 BRUSHED NICKEL RE: ELEVATIONS FOR QTY
PICTURE RAIL AS HANGING DISPLAY SYSTEMS, DROP CEILING TRACK #A1080HF WHITE
PICTURE RAIL AS HANGING DISPLAY SYSTEMS DISPLAY REVEAL #A1025 STANDARD FINISH
SIGN TYPE SIGN TEXT REFERENCE QTY LOCATION DESCRIPTION / REMARKS
A1 (VINYL WALL GRAPHIC)B2/A412 1 TUTORING ADMIN OPEN AREA 160 FULL COLOR PRINTED VINYL WALL GRAPHIC. SEE INTERIOR ELEVATIONS FOR DIMENSIONS. EXACT GRAPHIC TO BE PROVIDED AT A LATER TIME.
A2 (VINYL WALL GRAPHIC)D2/A414 1 MATH LAB RECEPTIONIST 175 FULL COLOR PRINTED VINYL WALL GRAPHIC. SEE INTERIOR ELEVATIONS FOR DIMENSIONS. EXACT GRAPHIC TO BE PROVIDED AT A LATER TIME.
A3 (VINYL WALL GRAPHIC)E1/A421 1 COLLABORATIVE SPACE 188 FULL COLOR PRINTED VINYL WALL GRAPHIC. SEE INTERIOR ELEVATIONS FOR DIMENSIONS. EXACT GRAPHIC TO BE PROVIDED AT A LATER TIME.
A4 (VINYL WALL GRAPHIC)E3/A421 1 TRAINING AREA 190 FULL COLOR PRINTED VINYL WALL GRAPHIC. SEE INTERIOR ELEVATIONS FOR DIMENSIONS. EXACT GRAPHIC TO BE PROVIDED AT A LATER TIME.
A5 (VINYL WALL GRAPHIC)B5/A414 1 RECEPTION 270A FULL COLOR PRINTED VINYL WALL GRAPHIC. SEE INTERIOR ELEVATIONS FOR DIMENSIONS. EXACT GRAPHIC TO BE PROVIDED AT A LATER TIME.
B1 (GLASS SAFETY GRAPHIC)A1/A710 SEE WINDOW TYPES
MULTIPLE (ON APPROX 75 WINDOW TYPES) DUSTED CRYSTAL VINYL. 3" TALL X CONTINUOUS ACROSS EACH INTERIOR FULL HEIGHT (7'-2") GLASS PANE.
B2 (GLASS ENTRY GRAPHIC)A4/A710 SEE WINDOW TYPES
MULTIPLE (ON APPROX 62 DOORS)DUSTED CRYSTAL VINYL ON EACH ENTRY DOOR ADJACENT TO FULL HEIGHT GLASS PANELS. VINYL SIZE FOR EACH DOOR 24" WIDE X 8" TALL. EXACT GRAPHIC TO BE PROVIDED AT A LATER TIME.
C1 (OFFICE SIDELIGHT PRIVACY FILM)A601; A602 SEE A601 & A602 MULTIPLE DUSTED CRYSTAL VINYL ON SIDELITE OF EACH TYPE F2 DOOR FRAME. SEE FRAME TYPES FOR DIMENSIONS
C2 (OFFICE DOOR PRIVACY FILM)A601; A602 SEE A601 & A602 MULTIPLE DUSTED CRYSTAL VINYL ON THE LITE OF EACH TYPE D1 DOOR. SEE DOOR TYPES FOR DIMENSIONS
E1 BYU-IDAHO B3/A415 1 CIRCULATION 110 15" TALL BYU-IDAHO LOGO. 1/4" THICK STUD MOUNTED CLEAR ANODIZED ALUMINUM LETTERS
E2 MCKAY LIBRARY B3/A415 1 CIRCULATION 110 4" TALL 1/4" THICK STUD MOUNTED CLEAR ANODIZED ALUMINUM LETTERS IN NEWS GOTHIC MEDIUM FONT
F MATH STUDY CENTER D2/A414 1 MATH LAB RECEPTIONIST 175 1” THICK CNC CUT MDF LETTERING PAINTED. COLOR BY ARCHITECT. RE: FINISH SCHEDULE. NEWS GOTHIC MEDIUM FONT. "MATH" 12" TALL. "STUDY CENTER" 8" TALL.
G INFO TECH D2/A414 1 IT HELP DESK 176 12” TALL 1” THICK CNC CUT MDF LETTERING PAINTED. COLOR BY ARCHITECT. RE: FINISH SCHEDULE. NEWS GOTHIC MEDIUM FONT.
H ACADEMIC SUCCESS AND TUTORING B2/A412 1 TUTORING ADMIN OPEN AREA 160 1” THICK CNC CUT MDF LETTERING PAINTED. COLOR BY ARCHITECT. RE: FINISH SCHEDULE. NEWS GOTHIC MEDIUM FONT. "ACADEMIC SUCCESS" 12" TALL. "AND TUTORING" 8" TALL.
J PRESENTATION PRACTICE D2/A422 1 WORKSPACE 156 12" TALL CUT VINYL ON GLASS. EXACT GRAPHIC TO BE PROVIDED AT A LATER TIME.
K VOLUNTEER CONNECTION CENTER E3/A421 1 WORKSTATIONS / FLEX SPACE 192 12” TALL 1” THICK CNC CUT MDF LETTERING PAINTED. COLOR BY ARCHITECT. RE: FINISH SCHEDULE. NEWS GOTHIC MEDIUM FONT.
L COLLEGE SUCCESS E3/A421 1 TRAINING AREA 190 12” TALL 1” THICK CNC CUT MDF LETTERING PAINTED. COLOR BY ARCHITECT. RE: FINISH SCHEDULE. NEWS GOTHIC MEDIUM FONT.
M
OFFICE OF ACADEMIC SUCCESS AND
INTERDISCIPLINARY STUDIES E1/A421 1 COLLABORATIVE SPACE 188 1” THICK CNC CUT MDF LETTERING PAINTED. COLOR BY ARCHITECT. RE: FINISH SCHEDULE. NEWS GOTHIC MEDIUM FONT. SEE ELEVATIONS FOR LETTER HEIGHTS.
N STUDY SKILLS AND READING CENTER 1 STUDY SKILLS 252 12" TALL CUT VINYL ON GLASS. EXACT GRAPHIC TO BE PROVIDED AT A LATER TIME.
P ENGLISH TRANSITION CENTER 1 ENGLISH TRANSITION CETNER 288 12" TALL CUT VINYL ON GLASS. EXACT GRAPHIC TO BE PROVIDED AT A LATER TIME.
Q WRITING CENTER 1 WRITING CENTER OPEN TUTORING 256 12" TALL CUT VINYL ON GLASS. EXACT GRAPHIC TO BE PROVIDED AT A LATER TIME.
R OPEN TUTORING B5/A414 1 RECEPTION 270A 1” THICK CNC CUT MDF LETTERING PAINTED. COLOR BY ARCHITECT. RE: FINISH SCHEDULE. NEWS GOTHIC MEDIUM FONT. "OPEN" 8" TALL. "TUTORING" 12" TALL.
S1 BOOK DROP SF10/A604 1 VESTIBULE 1-F 4" TALL CUT VINYL ON GLASS
S2 BOOK DROP C2/A415 1 CIRCULATION 110 4" TALL 1/4" THICK STUD MOUNTED CLEAR ANODIZED ALUMINUM LETTERS IN NEWS GOTHIC MEDIUM FONT
T SPECIAL COLLECTIONS A2/A422 1 SPECIAL COLLECTIONS 228 12” TALL 1” THICK CNC CUT MDF LETTERING PAINTED. COLOR BY ARCHITECT. RE: FINISH SCHEDULE. NEWS GOTHIC MEDIUM FONT.
U1 FAMILY STUDY E4/A413 1 FAMILY STUDY 344 12” TALL 1” THICK CNC CUT MDF LETTERING PAINTED. COLOR BY ARCHITECT. RE: FINISH SCHEDULE. NEWS GOTHIC MEDIUM FONT.
U2 (VINYL GLASS GRAPHIC)E4/A413 1 FAMILY STUDY 344 FULL COLOR PRINTED VINYL WALL GRAPHIC. SEE INTERIOR ELEVATIONS FOR DIMENSIONS. EXACT GRAPHIC TO BE PROVIDED AT A LATER TIME.
V INFORMATION A5/A412 2 3RD FLOOR DESK 4" TALL 1/4" THICK STUD MOUNTED CLEAR ANODIZED ALUMINUM LETTERS IN NEWS GOTHIC MEDIUM FONT
W I SPY WITH MY LITTLE EYE… D4/A413 1 KIDS PLAY 344C 8” TALL 1” THICK CNC CUT MDF LETTERING PAINTED. COLOR BY ARCHITECT. RE: FINISH SCHEDULE. NEWS GOTHIC MEDIUM FONT.
X (DEDICATION PLAQUE)2 TO BE COORDINATED WITH ARCHITECT 18" WIDE X 22" TALL X 1/4" ALUMINUM. LETTERING AND GRAPHICS TO BE MACHINED INTO ALUMINUM AND PAINTED BLACK. EXACT GRAPHIC TO BE PROVIDED AT A LATER TIME.
Y (QUOTE - SEE ELEVATION)E1/A421 1 HALL 1-Y 5" TALL 1/4" THICK STUD MOUNTED CLEAR ANODIZED ALUMINUM LETTERS IN MINION REGULAR FONT
**PRODUCTION FILES FOR SIGNAGE CAN BE PROVIDED BY ARCHITECT BY REQUEST
***SEE SHEET G015 FOR ADDITIONAL CODE REQUIRED SIGNS
THIS DRAWING INDICATES SIGNAGE APPLICATION AT ONE WINDOW
LOCATION TO COMMUNICATE DESIGN INTENT. GLASS SIZES AND
QUANTITIES VARY. SEE WINDOW TYPES FOR DIMENSIONS AND GLASS
CONFIGURATIONS AT ALL REQUIRED LOCATIONS OF THE SIGNAGE.
5'-4"
3"
THIS DRAWING INDICATES SIGNAGE APPLICATION AT ONE WINDOW
LOCATION TO COMMUNICATE DESIGN INTENT. GLASS SIZES AND
QUANTITIES VARY. SEE WINDOW TYPES FOR DIMENSIONS AND GLASS
CONFIGURATIONS AT ALL REQUIRED LOCATIONS OF THE SIGNAGE.
5'-4"
3"
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
10/28/22
A710
Signage
Schedule and
Details
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
3/4" = 1'-0"A4 SIGNAGE GLASS SAMPLE ELEVATION - TYPE B2
3/4" = 1'-0"A1 SIGNAGE GLASS SAMPLE ELEVATION - TYPE B1
1
G
J
L
M
N
P
Q
E
C
2 3 4 5 6
UNEXCAVATED
366 SF
TIER 2
016
111 SF
OFFICE
010
139 SF
OFFICE
026A
207 SF
OFFICE
011
209 SF
BREAK ROOM
013
109 SF
OFFICE
018
42 SF
STORAGE
032
116 SF
OFFICE
012
77 SF
OFFICE
026C
179 SF
STUDENTS
026F
258 SF
TECH ROOM
024
207 SF
SHORT TERM
STORAGE
028
224 SF
QA
022A
111 SF
OFFICE
020
473 SF
OPS
022
55 SF
STORAGE
044
61 SF
CUSTODIAL
STORAGE
042
111 SF
BDF
040
139 SF
MEN'S RR
015
138 SF
WOMEN'S RR
014
420 SF
ELECTRICAL
038
66 SF
CUSTODIAL
036
32 SF
MECH CHASE
034
71 SF
ELEV
0-J
296 SF
STAIR
0-E
79 SF
MECH CHASE
O-F
203 SF
STAIR
0-E
3,474 SF
MECH ROOM
030
78 SF
CHEMICALS
ROOM
O-D
592 SF
IMAGING AND
STORAGE
009
76 SF
OFFICE
026D
74 SF
OFFICE
026E
77 SF
OFFICE
026B
154 SF
HALL
0-C
128 SF
HALL
0-D
163 SF
FTE
026
42 SF
HALL
0-B
56 SF
HALL
0-A
137 SF
HALL
0-G
UNEXCAVATED
EX:TC-03
TYP. 7
EX:TC-03
TYP. 16
TC-03
EX:TC-03
EX:TC-03
TYP. 5
CLT-05
TYP. 5
TC-03 TC-03
TC-03
TRND-03
TC-04
TYP. 4
TREC-02
TC-03
TC-03
TRND-03
TC-04
TYP. 4
EX:TC-03
TYP. 8
TC-034' - 0"
EX: TC-07
TYP. 2
TYP. 3
EX: TC-07
TYP. 2
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
10/28/22
A800
Level 00 Area
A Furniture
Plan
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
1/8" = 1'-0"A1 Level 00 Area A Furniture Plan KEY PLAN
A
B
FURNITURE WILL BE A SEPARATE PACKAGE
AFTER THE CD'S ARE COMPLETE. TYPE OF
FURNITURE IS IN PROGRESS. FURNITURE IN THE
FURNITURE PLANS ARE FOR TO HELP
COORDINATE WITH CIRCULATION, QUANTITIES,
MECHANICAL AND ELECTRICAL EQUIPMENT,
ETC...
1
G
J
L
M
NN
PP
QQ
EE
CC
2 3 4 51.5 6
OFFICE
129
OFFICE
130
OFFICE
131
STUDY (MED)
132 OFFICE
136
RECEPTION
134
OFFICE
138
CONFERENCE
ROOM
140
BREAKROOM
142
STUDY (SM)
128
STUDY (MED)
124
STUDY (MED)
125
STUDY (SM)
126
STUDY (SM)
127
HD BOOK
COLLECTION
122
VESTIBULE
1-F
OFFICE
108INTER LIBRARY
LOAN
WORKSPACE
114
FAMILY RR
144
OPEN STUDY
122C
OPEN STUDY
122B
MENS
146
WOMENS
148
JANITORS
OFFICE
147
HIGH DENSITY STORAGE AREA
HIGH DENSITY STORAGE AREA
HIGH DENSITY STORAGE AREA
HIGH DENSITY STORAGE AREA
OFFICE
106
OFFICE
104
CHECK-IN
112
OFFICE
114A
MECH CHASE
1-G
ELEVATOR
1-JSTAIR
1-H
MECH CHASE
1-K
Room
1-L
Room
1-M
CIRCULATION
RECEPTION
110
RESERVE MEDIA
116
MECH
1-E
HALLWAY
1-C
STAIR
1-D
ELEC ROOM
102
ENTRY HALL
120A
STAIR
1-B
VESTIBULE
1-A
OPAC
OPAC
OPEN STUDY
120A
OPEN STUDY
100
TUNNEL
BELOW
OPEN STUDY
122A
OPEN STUDY
122A
OPEN STUDY
118
EX:BT-01
EX:SC-06EX: SF-02
EX: SC-05
EX: SC-03
EX: TC-02
TYP.7
EX: SC-03
EX: SC-02
EX: TC-02
EX: TC-02
EX: TC-02
EX: TC-02
EX: TC-02
EX: TC-02
EX:PT-04
EX:TC-01
TYP.8
TC-01
TYP. 76
SF-01 LC-01
LC-02
TYP. 8
LC-04
LC-06
TYP. 8
TYP. 16
SF-01
LC-06
TYP. 10
TYP. 8
TC-05
TYP.25
COT-02
TC-03
TC-03
TC-04 TSQ-02TC-03GC-02
TYP. 8
TSQ-01
TYP. 2
TC-03TC-03
TRND-03
GC-02
TC-03
TSQ-01
TSQ-01
TSQ-01
TSQ-01
TSQ-01
TYP. 2
TYP. 2
TYP. 8
TYP. 8
TYP. 4
TYP. 4
TYP. 4
TYP. 4
TSQ-02
TYP. 14
TREC-11
OTT-02
TYP. 4TYP. 8
LT-01
TYP. 8
LT-02
TYP. 3
CST-01
TYP. 16
OTT-01
TQR-01
TYP. 24
TREC-12
CST-01
TYP. 8
CST-01
TREC-12
OTT-01
OTT-02
OTT-01
OTT-02
TYP. 8
GC-01
TC-03
TSQ-02
PT-04 TC-03
TC-03
TC-03 PT-04
TYP. 5
OTT-02
OTT-01
COF-01
TYP. 4
TYP. 2
TYP. 2
CST-02
TYP. 6
TREC-13
10.19
10.19
10.19
10.19
TUNNEL
BELOW
READING
150
TSQ-02
EX: TC-02
TYP. 2
TYP. 6
TYP 2
TYP 4
TYP 8
EX: ST-01
EX: TC-07
TYP. 2
EX: TC-07
EX: TC-07
TYP. 2
TYP. 2
TYP. 4
TYP. 2
EX: TC-07
TYP. 2
TYP. 16
TYP. 4
TYP. 4
LT-02
TYP. 3
TYP. 4
TYP. 4
TYP. 5
TYP. 3TYP. 7
TYP. 2
TYP. 3
TYP. 2
TYP. 2
TYP. 2
EX: TC-07
TYP. 2
EX: TC-07
TYP. 2
EX: TC-07
TYP. 2
EX: TC-07
TYP. 2
TYP. 3TYP. 3
TYP. 2 TYP. 2 TYP. 2
TYP. 2
TYP. 2
BOOK
MICROWAVE
2 STACK LOCKERS, FF%
E PVC
TC-03
TREC-14
TYP. 2 TC-03
B2
A431
TC-01TQR-01
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
10/28/22
A801
Level 01 Area
A Furniture
Plan
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set1/8" = 1'-0"A1 Level 01 Area A Furniture Plan KEY PLAN
A
B
FURNITURE WILL BE A SEPARATE PACKAGE
AFTER THE CD'S ARE COMPLETE. TYPE OF
FURNITURE IS IN PROGRESS. FURNITURE IN THE
FURNITURE PLANS ARE FOR TO HELP
COORDINATE WITH CIRCULATION, QUANTITIES,
MECHANICAL AND ELECTRICAL EQUIPMENT,
ETC...
KEYED NOTES
10.19 HIGH DENSITY LIBRARY MANUAL BOOK STORAGE - B.O.D. SPACE SAVER
16
16
15
15
14
14
13
13
12
12
11
11
10
10
9
9
8
8
7
7
K
H
F
D
B
A
STORAGE
170C
STUDY
170B
STUDY
170A
CLASSROOM
168
CLASSROOM
166
ADJUNCT
OFFICE
180
OFFICE
181
OFFICE
182
OFFICE
183
OFFICE
184
OFFICE
185
OFFICE
186
CONFERENCE
ROOM
158
CONFERENCE
188B
COLLABORATIVE
SPACE
188
CLASSROOM
162
CLASSROOM
164
OFFICE
190B
OFFICE
190A
TRAINING AREA
190
OFFICE
192B
SMALL MEETING
192A
OFFICE
160A
OFFICE
160B
TUTORING
ADMIN OPEN
AREA
160
OFFICE
156FPRACTICE
156E
WORKSPACE
156
STORAGE
156D
DROP IN MATH
LAB
170
WORKSTATIONS/
FLEX SPACE
192
CLASSROOM
172
STUDENT PREP
174
STUDY
178
STUDY
179
MATH LAB
RECEPTION
175
I.T. HELP DESK
176
OFFICE
188A
STORAGE
190C
STORAGE
192C
PRACTICE
156C
PRACTICE
156B
PRACTICE
156A
ELECTRICAL
173
VESTIBULE
1-U
HALL
1-X
VESTIBULE
1-Z
HALL
1-Y
HALL
1-V
MEN'S
RESTROOM
154
WOMEN'S
RESTROOM
152
HALL
1-P
STAIRS
1-N
ELEV
1-T
ELEV EQUIP
08A
MECH
08
EX:RT-02
D4
A802
EX: SC-01
LC-06
TYP. 4
LC-06
LC-06
TYP. 14 TYP. 28
TD-01 TC-02 TC-02TD-01
CLT-02
TC-01
TYP. 14
TYP. 28
CLT-02 TC-01
TYP. 14 TYP. 28
EX: TC-02
TYP. 8
TREC-04
CLT-06
TYP. 10
CLT-07
CLT-08
TYP. 24
TYP. 18
TREC-01
TC-01
TYP. 116
ST-01
ST-01
TYP. 3
ST-01
TYP. 2
TC-03
TC-03
TC-03TC-03TC-03TC-03
TC-03
TC-03
TC-05
TC-03
EX: TC-02
TYP. 5
TREC-04
TC-05
TYP. 4
TC-03TC-03TC-03
TC-05
TYP. 22
TREC-08
TC-05
TC-05
TYP. 13
TC-03
TC-05
COT-01
TYP. 10
TC-03
TC-01TRND-03CLT-06
TYP. 3 TYP. 24
TC-04
TC-04
TC-04 TC-04TREC-04
TREC-04
TREC-04
TREC-04
TC-03
TC-01
CLT-02
TC-01TSQ-02 TC-05
5' - 0"
6' - 6"
TC-05
GC-03
ST-01
TYP. 4
TC-04
TYP. 4
CLT-02
TC-03
TC-02
TD-01
TC-01
TREC-04
CLT-05 TC-01 TC-02TD-01
EX: TC-02
TRND-02
TYP 2
TYP 2
TYP 2 TYP 2
TYP. 2
EX: TC-07
TYP. 2
TYP. 3
TC-02
TD-01
CLT-05TC-01
TYP. 28 TYP. 14
TYP. 2
TYP. 4
TYP. 14
TYP. 28
TYP. 2
TYP. 8
TREC-04
EX: TC-07
TYP. 2
EX: TC-07
TYP. 2TYP. 2
EX: TC-07
TYP. 2
TYP. 4
EX: TC-07
TYP. 2
TYP. 6
TYP. 4TYP. 2
TYP. 4TYP. 2
TYP. 4
TYP. 2
TC-03
TYP. 2
EX: TC-07
TYP. 2
EX: TC-07 EX: TC-07
TYP. 2 TYP. 2
EX: ST-01
TYP. 3
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
10/28/22
A802
Level 01 Area
B Furniture
Plan
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
1/8" = 1'-0"A1 Level 01 Area B Furniture Plan KEY PLAN
A
B
FURNITURE WILL BE A SEPARATE PACKAGE
AFTER THE CD'S ARE COMPLETE. TYPE OF
FURNITURE IS IN PROGRESS. FURNITURE IN THE
FURNITURE PLANS ARE FOR TO HELP
COORDINATE WITH CIRCULATION, QUANTITIES,
MECHANICAL AND ELECTRICAL EQUIPMENT,
ETC...
1/8" = 1'-0"D4 LEVEL 01 AREA B SACRAMENT LAYOUT
1
G
J
L
M
N
P
Q
E
C
2 3 4 51.5 6
TECH SERVICES
238
SHEET MUSIC
236
LARGE
COMPUTER
CLASSROOM
234
OPEN
COMPUTERS
240
MOTHERS
243
OPEN STUDY
53
PRESS ROOM
226
SPECIAL
COLLECTIONS
228
VAULT
228E
ARCHIVE
228D
INSTRUCTION 2
224
INSTRUCTION 1
222
DCAM
228B
OFFICE
228A
SCANNER
228C
OFFICE
232
STUDY (MED)
216
STUDY (MED)
214
STUDY (MED)
218
OFFICE
230
OFFICE
202
STUDY (SM)
212
STUDY (SM)
210
STUDY (SM)
208
OFFICE
200
OPEN STUDY
220
ELECTRICAL
ROOM
242
I.T.
245
STUDY (SM)
204
JANITOR'S
OFFICE
241
MECHANICAL
2-D
TECH SERV
STORAGE
2-E
NEW OPENING
MECH
2-C
STAIR
2-A
JOLENE'S OPEN
OFFICE
EVYLYN'S OPEN
OFFICE MECH CHASE
2-F
STAIR
2-G
ELEV
2-H
MECH CHASE
2-J
HALL
2-K
MEN'S
RESTROOM
247
WOMEN'S
RESTROOM
248
Room
2-M
HALL
2-M
STAIR
2-B
FAMILY RR
244
OPEN STUDY
53
STUDY (MED)
206
JANITOR'S
CLOSET
249
EX: SF-03
SELF
CHECK-OUT
EX: SC-05
EX:SC-06EX:STC-01EX: SC-05
EX:BN-01
EX: TC-02
EX: TC-02
EX: TC-02EX: TC-02EX: TC-02EX: TC-02EX: TC-02
EX: TC-02
EX: TC-02
LC-01
TYP. 12
LC-02
LT-02
TYP. 18
TYP. 10
LC-04
TYP. 4
SF-01 TC-01
TYP. 48
EX: TC-02
TYP. 48
TTD-01
TYP. 8
TTZ-01
TYP. 16
TYP. 46
TYP. 33
TC-03
TC-03
TC-03
CLT-06
TC-01
TYP. 18
TYP. 36
TC-02
TD-01
TC-05
TC-03
TC-03
TYP. 10
TC-03
TC-02
TD-01
TC-02
CLT-06
TC-01
TYP. 12
TYP. 24
EX:TBL-02
EX: SF-04
TYP. 5
TYP. 10
TSQ-02
TYP. 16
PT-04
OTT-01
OTT-02
TC-03
TC-03
TSQ-01
TSQ-01TSQ-01TSQ-01TSQ-01
TYP. 4
TYP. 2TYP. 2TYP. 2TYP. 2 TYP. 6 TYP. 6 TYP. 6
TYP. 8
TYP. 8
TYP. 8
TYP. 8
TSQ-01
TSQ-01
TYP. 2
TYP. 2
TSQ-01
TYP. 2
LT-02
TC-04
TSQ-02
TREC-04
OPEN STUDY
250
TYP. 2
TYP. 2
EX: TC-07
TYP. 2
TYP. 2
EX: TC-07
TYP. 2
TYP. 8
TYP. 4 TYP. 5 TYP. 4
TYP. 4 TYP. 4 TYP. 8
TYP. 2
TYP. 3
TYP. 7
TYP. 2
TYP. 2
EX: TC-07
TYP. 2
EX: TC-07
TYP. 2
EX: TC-07
TYP. 2
TD-01
CLT-06
TC-01
TYP. 12
TYP. 24
IT
241A
EX: TBL-03
TYP. 2
TREC-02
TYP. 2
CLT-04 3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
10/28/22
A803
Level 02 Area
A Furniture
Plan
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
1/8" = 1'-0"A1 Level 02 Area A Furniture Plan KEY PLAN
A
B
FURNITURE WILL BE A SEPARATE PACKAGE
AFTER THE CD'S ARE COMPLETE. TYPE OF
FURNITURE IS IN PROGRESS. FURNITURE IN THE
FURNITURE PLANS ARE FOR TO HELP
COORDINATE WITH CIRCULATION, QUANTITIES,
MECHANICAL AND ELECTRICAL EQUIPMENT,
ETC...
16151413121110987
K
H
F
D
B
A
389 SF
CLASSROOM
272
OFFICE
288B
OFFICE
288C
1,157 SF
ENGLISH
TRANSITION
CENTER
288
613 SF
OPEN TUTORING
254
1,612 SF
STUDY SKILLS
252
1,300 SF
WRITING
CENTER OPEN
TUTORING
256
137 SF
STUDY
269
108 SF
STUDY
268
112 SF
STUDY
267
114 SF
STUDY
266
117 SF
OFFICE
265
118 SF
OFFICE
264
59 SF
STORAGE
270J
98 SF
STUDY
270H
119 SF
PREP /
STORAGE
270B
573 SF
CLASSROOM
260
119 SF
PREP /
STORAGE
256A
130 SF
OFFICE
256B
146 SF
OFFICE
256C
3,139 SF
OPEN TUTORING
CENTER
270
196 SF
ADJUNCT
OFFICE
286
144 SF
TR / COMM.
280
341 SF
CLASSROOM
278
141 SF
PRE-FUNCTION
270C
133 SF
PRE-FUNCTION
270D 119 SF
PRE-FUNCTION
270E
STORAGE
288H
106 SF
PREP /
STORAGE
252G
163 SF
OFFICE
252E
ONLINE WORKSTATIONS
625 SF
CLASSROOM
258
78 SF
STORAGE
252F
126 SF
OFFICE
252D
120 SF
STUDY
252A
89 SF
STUDY
252C
7'-10"
7'-6"
94 SF
STUDY
270G
STUDY
252B
STUDY
288E
STUDY
288F
STUDY
288G
STUDY
288D
STUDY
288A
STOR
299
MEN'S
RESTROOM
282
WOMEN'S
RESTROOM
284
MECH
2-T
HALL
2-U
CLASSROOM
274
CLASSROOM
276
CHECK-IN STATION
TECH STATION OPCI TECH STATION OPCI
TECH STATION OPCI
TECH STATION OPCI
PROJECTOR SCREEN, RE: RCP'S FOR
SCREEN AND PROJECTOR
TYPICAL STUDY ROOM IN EAST WING
TO HAVE TWO WHITE BOARDS PER
ROOM
TYPICAL FOR CLASSROOMS IN EAST
WING TO HAVE AS MUCH WHITE
BOARD ON WALLS AS POSSIBLEPROJECTOR SCREEN, RE: RCP'S FOR
SCREEN AND PROJECTOR
WHITEBOARDS ALONG THIS WALL
CUBBIES
SHELVES
PROJECTOR
SCREEN, RE: RCP'S
FOR SCREEN AND
PROJECTOR
EX: SC-04 EX: SC-04
EX: RT-03
EX: RT-03
EX:TC-03TC-01
TYP.64TYP.10
EX: TC-02
TYP.4
EX: SC-05
EX: SC-04
EX: SC-04
LC-06
TC-01
TYP. 18
EX: TC-02
TYP. 8
TREC-02
TYP. 4
TC-03 TC-03 CLT-06 TC-01
TYP. 15 TYP. 30
CLT-06 TC-01
TYP. 15 TYP. 30
TC-02 TD-01 TD-01 TC-02
EX: TC-02
TYP. 4
EX: TC-02
TYP. 4
TC-01
TYP. 8
OTT-02
OTT-02
TREC-02
TYP. 9
TREC-04
TREC-04
EX: TC-02
EX: TC-02
TYP. 4
TYP. 4
TC-01
TYP. 44
TREC-02
TYP. 16
TREC-07
TYP. 4
TC-03 TC-03 EX:STC-03
TYP. 10
TC-06
TYP. 19
TC-01
CLT-05
CLT-03
TYP. 10
TC-01
TYP. 30
TC-03
TC-03 TREC-04 TREC-04 TREC-04
EX: TC-02EX: TC-02EX: TC-02
TYP. 4 TYP. 4 TYP. 4
TREC-08
EX: TC-02
TYP. 6
TYP. 29
TYP. 114
TRND-02
TYP. 6
CLT-05
TC-05
TC-03TC-05
TREC-09
TC-05
TREC-02
EX: TC-02
OTT-02 OTT-01TC-01
TYP. 44
TRND-03
TYP. 4
TREC-02
TYP. 7
TYP. 8
TREC-06
TREC-02
TYP. 16
TREC-10
TYP.2
TC-03
TREC-04
TC-05
CLT-05
TC-01
TC-03TRND-03TC-01
ST-01
OTT-02
PREFUNCTION
270F
RECEPTION
270A
TC-01
EX: TBL-01
CLT-06
TYP. 3
TYP. 8
TYP. 2TYP. 2TYP. 2TYP. 2
EX: TC-07 EX: TC-07
TYP. 2 TYP. 2
TYP. 4 TYP. 2
TYP. 2 TYP. 2TYP. 4
TYP. 2
TYP. 4
EX: TC-07
TYP. 2
TYP. 2
EX: TC-07
TYP. 2
TYP. 2
TYP. 2
TYP. 4
TYP. 2
EX: TC-07
TYP. 2
EX: TC-07
TYP. 2
EX: TC-07 EX: TC-07
TYP. 2 TYP. 2
TREC-14
TREC-14
TD-01
TC-02
TD-01
TC-02
D4
A804
TC-01
TYP
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
10/28/22
A804
Level 02 Area
B Furniture
Plan
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
1/8" = 1'-0"A1 Level 02 Area B Furniture Plan KEY PLAN
A
B
FURNITURE WILL BE A SEPARATE PACKAGE
AFTER THE CD'S ARE COMPLETE. TYPE OF
FURNITURE IS IN PROGRESS. FURNITURE IN THE
FURNITURE PLANS ARE FOR TO HELP
COORDINATE WITH CIRCULATION, QUANTITIES,
MECHANICAL AND ELECTRICAL EQUIPMENT,
ETC...
1/8" = 1'-0"D4 Area B Sacrament Layout
1
G
J
L
M
N
P
Q
E
C
2 3 4 51.5 6
OFFICE
310
OFFICE
312
JUVENILE
300
STORAGE
306
STUDY (MED)
304
STUDY (MED)
302
KIDS PLAY
344CMOTHERS
ROOM
344A
RESTROOM
344B
FAMILY STUDY
344
OPEN STUDY
362
Bridge
Connection
-
BRIDGE
CONNECTION
3-A
STAIR 1
3-B
MENS
368
WOMENS
366
TEST RM
378
STUDY (SM)
330 Janitors Closet
376
OFFICE
322
MAC EQUIP
324A
STUDY (LG)
328
STUDY (LG)
326
MAC LAB
324
STUDY (SM)
332
STUDY (SM)
334
STUDY (SM)
336
TEST RM
374
STUDY (SM)
314
STUDY (SM)
316
STUDY (SM)
320
ELECTRICAL
324B
ELEC
364
STUDY (SM)
338
STUDY (SM)
340
STUDY (SM)
318
ELECTRICAL
308
STORAGE
352
TEST RM
380
TEST RM
382
TEST RM
372
TEST RM
370
TEST RM
360
TEST RM
358
TEST RM
356
TEST RM
350
TEST RM
348
TEST RM
346
STAIRS
3-C
MECH
3-D
MECH CHASE
3-E
STAIR
3-F
ELEV
3-G
MECH CHASE
3-H
CIRC DESK
SE
L
F
CH
E
C
K
O
U
T
play structure
TEACHER RESOURCE CENTER SHELFTEACHER RESOURCE CENTER SHELF
EX: SF-01
EX: SC-01
EX: SC-05 EX: TC-02
EX: TC-02
EX: TC-02
EX: ST-01
EX: SC-04
EX: SC-01
EX: SC-05
EX: TC-02
EX: TC-02
EX: TC-02
EX: SC-05
EX:COF-01
EX:PT-03
EX:SC-06
TYP.16
EX: RT-01
TYP. 20
EX:RT-02
EX: TC-02
EX: SF-02
EX: TC-02
EX: TC-02
EX: RT-01
TYP. 21
TYP. 4
EX:BN-01
EX: TC-02
TYP.18
EX: TC-02
TYP.18
EX: SC-03
TYP.12
EX:STC-01
EX:SCN-01L
EX: SCN-01R
TYP.4
EX:TC-01
TYP. 24
EX: SC-04
EX: SC-02
EX: TC-02
TC-01
TYP. 32
TYP. 14
LC-01
TYP. 10
LC-02
TYP. 30
LC-03
LC-04
TYP. 16
TYP. 4
TYP. 8 TYP. 10
SF-01
TYP. 12
LT-01
TYP. 22
LT-02
TYP. 36
SF-01
LC-07
TSQ-01
TYP. 2
TSQ-01
TYP. 2
TREC-03
TYP. 4
TREC-03
TYP. 4
TC-03
TYP. 2
TYP. 4
LC-08
TYP. 2
TYP. 6
EX: TC-02
TYP. 6
EX: TC-02
TYP. 6
EX: TC-02
TYP. 6
EX: TC-02
TYP. 6
EX: TC-02
TYP. 6
TREC-05
TREC-05
TREC-05
TREC-05
TREC-05
TREC-05
EX: TC-02
EX: TC-02
EX: TC-02
EX: TC-02
TYP. 6
TYP. 6
TYP. 6
TYP. 6
TREC-05
TREC-05
TREC-05
TREC-05
TSQ-01 TSQ-01
TYP. 2 TYP. 3
TYP. 5
OTT-02
OTT-02 EX: SC-03
TYP. 4
TC-03
EX: BT-01
CLT-01
CLT-01
CLT-01
CLT-01
TRND-01
TC-04
TYP. 4
FRD-01
TYP. 3
TREC-01
TC-03
TREC-01
EX: TC-02
TYP. 5
OPEN STUDY
383
OPEN STUDY
383
( QUIET )
OPEN STUDY
342
TYP. 2
TYP. 2
TYP. 5
TYP. 3
TYP. 6
TYP. 4TYP. 2
TYP. 5
TYP. 2
TYP. 2
TYP. 2 TYP. 4 TYP. 2
TYP. 4
TYP. 15
TYP. 8
TYP. 30
LC-05
TYP.4
TYP. 8
TYP. 6
TYP. 3
TYP. 2
TYP. 3
TYP. 2
TYP. 4
L L L L
R R R R
L L L
L L L
RRRR
L L L
L L L
L
R R
L L
R
L L L
L L L
L L L
L L L
RRRR
DISPLAY
SHELVES
PROJECTOR
LOCKER FOR 4
PEOPLE
STANDARD HT
with power
WHITE
BOARD
OUTLETS
CLT-06
EX: TC-07
TYP. 2
TYP. 3
TREC-04
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
10/28/22
A805
Level 03 Area
A Furniture
Plan
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set1/8" = 1'-0"A1 Level 03 Area A Furniture Plan KEY PLAN
A
B
FURNITURE WILL BE A SEPARATE PACKAGE
AFTER THE CD'S ARE COMPLETE. TYPE OF
FURNITURE IS IN PROGRESS. FURNITURE IN THE
FURNITURE PLANS ARE FOR TO HELP
COORDINATE WITH CIRCULATION, QUANTITIES,
MECHANICAL AND ELECTRICAL EQUIPMENT,
ETC...
VARIABLE FREQUENCY DRIVE (VFD)
MCKAY LIBRARY SNOW MELTING CAPACITY REQUIREMENTS
CIRCUIT BALANCE VALVE
HEATING WATER PUMP
WALL HUNG HUMIDIFIER
FAN COIL CIRCULATING PUMP
SEE SPECIFICATION SECTION 232123
SYMBOL HEAD
FEET GPM EFF.
VOLTS
ELECTRICAL
PHASEHERTZ HP RPM
HWP-10
HWP-9
45 51 120
48 58 255
74 208 60 3
75 208 60 3
3 1750 e-1531
7.5 1750 e-1531
2ADTERMINAL UNIT HEATING WATER COILS
2.5BB(E) AHU HEATING WATER COIL
35% PROPYLENE GLYCOL
35% PROPYLENE GLYCOL
REMARKS
BELL AND
GOSSETT
SERIES
BELL AND
GOSSETT
MODEL
DUTY
CLOSE COUPLED END SUCTION
CLOSE COUPLED END SUCTION
%HEAD
SHUT-OFF
TYPE
SEE SPECIFICATION SECTION 232123
SYMBOL HEAD
FEET GPM
VOLTS
ELECTRICAL
PHASEHERTZ HP
FCP-1 35 45 15 120 60 1 1/2 UPS UPS 26-150 FFAN COIL CHILLED WATER 35% PROPYLENE GLYCOL
REMARKS
GRUNDFOS
SERIES
GRUNDFOS
MODELDUTY
IN-LINE
HEAD
SHUT-OFF
TYPE
(E)
CHWS
CHWR
HWR
HWS
FSRD
FD
D
T
S
S.F.D.
A.D.
H.D.
RISE
24"x12"
LVT
SYMBOL LEGEND
HOT WATER SUPPLY
COLD WATER
CHILLED WATER RETURN
CHILLED WATER SUPPLY
HOT WATER RETURN
SOIL OR WASTE
DOMESTIC HOT WATER
EXISTING
LOW PRESSURE STEAM
LOW PRESSURE CONDENSATE
DOMESTIC HOT WATER RECIRCULATING
VENT
EXHAUST GRILLE
CONCENTRIC REDUCER
THERMOMETER
GAUGE WITH GAUGE COCK
GAUGE COCK
ECCENTRIC REDUCER
THERMOMETER OR GAUGE WELL
SAFETY OR RELIEF VALVE
SOLENOID VALVE
GLOBE VALVE
PIPE GUIDE
PIPE ANCHOR
BLIND FLANGE
PRESSURE/TEMPERATURE TEST PLUG (PETE'S PLUG)
FLOW CONTROLLER OR BALANCE VALVE
FLOOR DRAIN, FLOOR SINK OR ROOF DRAIN
PRESSURE REDUCING VALVE - (PRV)
STEAM TRAP
DIRT LEG
DRAIN
STRAINER
OPPOSED BLADE DAMPER
PARALLEL BLADE DAMPER
BRANCH DUCT TAKE-OFF
SPIN-IN FITTING
THERMOSTAT
TEMPERATURE SENSOR
DROP IN PIPE
VALVE IN RISE
BALL VALVE
GATE VALVE
CHECK VALVE
2 WAY CONTROL VALVE
3 WAY CONTROL VALVE
BUTTERFLY VALVE
CONTROL VALVE (PLAN VIEW)
RISE IN PIPE
PLUG VALVE
CAP
UNION
NEW CONNECTION
FLAT OVAL (CROSS SECTION)
ROUND DUCT (CROSS SECTION)
SUPPLY DUCT (CROSS SECTION)
HAND DAMPER
SUPPLY AIR DIRECTION
TURNING VANES IN DUCT
ACCESS DOOR FOR FIRE DAMPER
ACCOUSTICAL LINING IN DUCT
DROP OR RISE IN SUPPLY DUCT
SUPPLY DIFFUSER
COMBINATION SMOKE/FIRE DAMPER
RISE OR DROP IN ROUND OVAL DUCT
INSIDE CLEAR DIMENSION IN INCHES
DUCT SIZE, INSIDE CLEAR DIMENSION IN INCHES
RETURN AIR OR EXHAUST DUCT (CROSS SECTION)
RETURN AIR OR EXHAUST DIRECTION
RETURN AIR GRILLE
24"x18"
DUCT RISE
DESCRIPTIONSYMBOL
LOW VOLTAGE TRANSFORMER
CONNECTION
10 - 15 5 AS125 1-1/4
SEE SPECIFICATION SECTION 230523
6 - 9
1.5 - 2.5
3 - 5
1.5 - 2.5
.5 - 1.4
GPM RANGE
IN FT
5
5
5
5
5
PRESSURE
DROP
AVERAGE
ASO75L
AS100
ASO75H
ASO50L
ASO5OH
3/4
1
3/4
1/2
1/2
FLOWSET
SIZE SIZE
REMARKS
131 - 275
76 - 130
46 - 75
26 - 45
16 - 25
AS400
AS300
AS200
AS250
AS150
5
5
5
5
5
2-1/2
1-1/2
4
3
2
-
-
-
-
-
-
-
-
-
-
-
SEE SPECIFICATION SECTION 238414
H-1
SYMBOL
PROVIDE WITH REMOTE HUMIDISTAT AND DUCT DISTRIBUTOR KIT SIZED FOR THE APPLICATION.
PHASEHERTZVOLTSLB/HR
10 208 60 3
ELECTRICAL CHARACTERISTICSCAPACITY
REMARKS
15
WATER
RO
TYPE
CONDAIR MODEL
RS DUCT 010
MCA
10.3
MOCP
AMPS
SYMBOL
VFD-2
VFD-1
SEE SPECIFICATION SECTION 230513
HTZ
602
DUTY
(E) HWP-1
FAN MOTOR
VOLTAGE
208
PH
3
DRIVES, INCLUDING THE INSTALLATION AND COORDINATING THE
EFFORTS OF THE SUPPLIER, ELECTRICAL CONTRACTOR FOR POWER
THIS CONTRACTOR SHALL HAVE THE FULL RESPONSIBILITY FOR THE
THE DRIVES SHALL MATCH THE MOTORS PROVIDED WITH THE FANS.
WIRING, AND CONTROL WORK BY ATC CONTRACTOR.
REMARKS
DRIVEN
QUANTITY OF
MOTORS HP
TOTAL
1
602(E) HWP-2 208 31
VFD-8
VFD-7 6040(E) CHWP-7 208 31
6040(E) CHWP-8 208 31
VFD-10
VFD-9 607.5HWP-9 208 31
603HWP-10 208 31
*FOR SPACING OF SNOW MELT TUBING IN STAIRWAYS, SEE STAIRWAY SNOW MELTING DETAILS.
ZONE NO. ZONE NAME
*PRIMARY
SPACING
(INCHES)
PRIMARY AREA
(SQ. FT.)
HEATING INTENSITY
(BTU/SQ. FT.)
REQUIRED HEAT
(BTUH)
GLYCOL CONCENTRATION
(PROP. GLYCOL)
SUPPLY FLUID TEMP
(DEG. F)
DELTA T (DEG.
F)
NO. OF
CIRCUITS
APPROX GPM/
CIRCUIT TOTAL GPM MAX. TUBE HEAD
LOSS (FT)
WATTS RADIANT MODEL
TOTAL LENGTH
(FT)/CIRCUIT
EFFECTIVE LENGTH
(FT)/CIRCUIT
REMARKS
TUBE TYPE SIZE
1A (EXIST.) WEST NORTH ENTRY STAIRS 6 549.5 189 103652.19 50%105 25 3 3.05 9.15 9 RADIANTPEX+ 5/8 200 183 INCLUDES EDGE LOSS
1B (EXIST.) EAST NORTH ENTRY STAIRS 6 549.5 189 103652.19 50%105 25 6 1.55 9.3 9 RADIANTPEX+ 5/8 200 183 INCLUDES EDGE LOSS
2 (EXIST.)NORTH ENTRY HANDICAPPED RAMP 6 391 190 74426.85 50%105 25 4 1.65 6.6 11.1 RADIANTPEX+ 5/8 220 195 INCLUDES EDGE LOSS
3 (EXIST.)WEST ENTRY 6 773 224 172796.42 50%105 25 8 1.9 15.2 13 RADIANTPEX+ 5/8 200 193 INCLUDES EDGE LOSS
4 SOUTH ENTRY 6 97 218 21098.47 50%105 25 1 1.85 1.85 13.6 RADIANTPEX+ 5/8 220 194 INCLUDES EDGE LOSS
5 REMOTE ENTRY AND STAIRWAY 6 232 208 48272.24 50%105 25 3 1.4 4.2 6.8 RADIANTPEX+ 5/8 180 154 INCLUDES EDGE LOSS
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
Mechanical
Schedules
and Symbol
Legend
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
GRILLE AND DIFFUSER SCHEDULE
CABINET HEATERS LOUVER
BAROMETRIC PRESSURE RELIEF DAMPERS
FAN COIL UNITS (DX)
FAN COIL UNITS (CHW)
SPLIT SYSTEM AIR CONDITIONING UNIT
ROOFTOP EXHAUST FANS
UNIT
AIRFLOW
CFM
FAN COIL ELECTRICAL HEATING COIL - 35% PROPYLENE GLYCOL - 8 FPI DX COOLING COIL
AAON
MODEL
NUMBER
SYMBOL
ESP.
MOUNTING DISCHARGE INLET
TYPE HEATING ENTERING / ENTERING / WATER PRESS. NUMBER SENSIBLE CLG. TOTAL CLG. NUMBER
REMARKS
IN. WG.OF FAN MCA MOCP MOTOR VOLTS HERTZ PHASE CAPACITY LEAVING WATER LEAVING AIR GPM DROP MAX OF CAPACITY CAPACITY OF
HP BTUH TEMP °F TEMP °F FT W.C. ROWS BTUH BTUH ROWS
DXFCU-1 1000 .5 FLOOR VERTICAL REAR PLENUM 3 15 1.1 208 60 3 40,000 180 / 140 54 / 97 2.2 1.3 2 21,000 32,400 6 V3-ARB 1,2,3,4,5,6
NOTES:
1. FURNISH WITH A 4" PLEATED - 85% EFF. - MERV 13 POST FILTER.
2. PROVIDE WITH INTERNAL REMOVABLE CONTROL PANEL. DISCONNECT BY OTHERS.
SEE SPECIFICATION SECTION 238200
3. EC MOTOR.
SYMBOL FACE SIZE DESCRIPTION MANUFACTURER MODEL REMARKS
S-1 24"x24" CEILING DIFFUSER - LAY IN KRUEGER 1400 -
S-2 VARIES CEILING DIFFUSER - SURFACE KRUEGER SH -
S-3 VARIES SIDEWALL KRUEGER 880 -
R-1 VARIES CEILING RETURN GRILLE KRUEGER 6490 -
R-2 VARIES SIDEWALL RETURN GRILLE KRUEGER S80 38° BLADE DEFLECTION
E-1 VARIES CEILING EXHAUST GRILLE - LAY IN KRUEGER EGC5 -
E-2 VARIES CEILING EXHAUST GRILLE - SURFACE KRUEGER EGC5 -
SEE SPECIFICATION SECTION 233713
SEE SPECIFICATION SECTION 238200
CH-1
SYMBOL
NOMINAL
AIR FLOW
CFM
1000
GPM
HEATING COIL
PROVIDE WITH FACTORY DISCONNECT
TYPE MIN. CAP.
BTUH
60,000 60°F180°F
ENT. AIR
TEMP °F
ENT. WTR
TEMP °F
2.6
VOLTS
1731
MAX. PRESSURE
DROP FT.WATTS
160115
HERTZ
ELECTRICAL
PHASE
FFEB10
TRANE
MODEL REMARKS
HORIZONTAL
AREA SERVED
VESTIBULE
60°F180°F 60115 1
NOTES:
1
1 2
1 2
CH-2
CH-3 500 30,000 1.5 831 FFJB06VERTICAL
NO. OF
ROWS
3
3
MIN
MCA
6.1
3.9
TOP BAR GRILLE OUTLET, FRONT BAR GRILLE INTLET
75" x 10" x 29"
MAX SIZE
L x W x H
48" x 10" x 29"
60°F180°F 60115 1 1 2CH-4 500 30,000 1.5 831 FFJB06VERTICAL3 3.9 48" x 10" x 29"
CH-5
CH-6
CH-7
CONDENSING UNIT ELECTRICAL
MCA MOCP MOTOR VOLTS HERTZ PHASE
HP
17 25 .33 208 60 3
SEE SPECIFICATION SECTION 233713
L-1
SYMBOL REMARKS
10" x 10"
SIZE
W x H
DXFCU-1 OUTSIDE AIR
DUTY
MECHANICAL 2-D
LOCATION
ELF6375DX
RUSKIN
MODEL
-
60°F180°F 60115 1 1 2500 30,000 1.5 831 FFJB06VERTICAL3 3.9 48" x 10" x 29" VESTIBULE
VESTIBULE
VESTIBULE
60°F180°F 60115 1 1 2500 30,000 1.5 831 FFJB06VERTICAL3 3.9 48" x 10" x 29"
60°F180°F 60115 1 1 2500 30,000 1.5 831 FFJB06VERTICAL3 3.9 48" x 10" x 29"
60°F180°F 60115 1 1 2500 30,000 1.5 831 FFJB06VERTICAL3 3.9 48" x 10" x 29" VESTIBULE
VESTIBULE
VESTIBULE
OUTSIDE
AIR
CFM
150
4. FURNISH WITH CFA-003 CONDENSING UNIT.
5. HEATING COIL SHALL BE IN THE REHEAT POSITION.
6. FURNISH WIUTH MIXING BOX WITH R.A. AND O.A. DAMPERS.
SYMBOL
DAMPER SIZE
BLADE
ORIENTATION
MANUFACTURER MODEL
NORMAIL
POSITION
SERVICE REMARKS
HEIGHTWIDTH
BD-1 8"8" PARALLEL RUSKIN BD6 CLOSED VAULT RELIEF 1,2
BD-2 PARALLEL RUSKIN BD6 CLOSED ARCHIVE RELIEF 1,2
NOTES:
1. HORIZONTAL INSTALLATION.
2. PROVIDE WITH STATIC PRESSURE CONTROLLER
SEE SPECIFICATION SECTION 233300
8"8"
3 BOTTOM STAMPED LOUVER OUTLET, BOTTOM STAMPED LOUVER INLET
SYMBOL
NOMINAL AIR
FLOW CFM
TYPE
COOLING COILS HEATING COILS ELECTRICAL
TRANE MODEL REMARKS# OF
ROWS
MIN.CAP.
BTUH
ENT.
WTR
TEMP F°
LVG.
WTR
TEMP F°
ENT. AIR
TEMP F°
LVG. AIR
TEMP F°
GPM
MAX
PRESS
DROP
FT.
# OF
ROWS
MIN.CAP.
BTUH
ENT. WTR
TEMP F°
LVG. WTR
TEMP F°
ENT. AIR
TEMP F°
LVG. AIR
TEMP F°
GPM
MAX
PRESS
DROP
FT.
MCA MOCP VOLTS HERTZ PHASE
FCU-1 1,200 HORIZONTAL CONCEALED 4 24,000 44 56 75 55 4.4 10 1 25,000 180 150 75 98 1.8 5 6.1 15 115 60 1 FCCB12 1, 2, 3, 4
FCU-2 1,200 HORIZONTAL CONCEALED 4 28,900 44 56 80 55 5.1 10 1 36,000 180 165 60 94 5.2 10 6.1 15 115 60 1 FCCB12 1, 2, 3, 4
FCU-3 1,200 HORIZONTAL CONCEALED 4 24,000 44 56 75 55 4.4 10 1 25,000 180 150 75 98 1.8 5 6.1 15 115 60 1 FCCB12 1, 2, 3, 4
1. PROVIDE W/ FACTORY DISCONNECT
2. PROVIDE W/ CONDENSATE OVERFLOW DETECTION IN DRAINPAN
3. PROVIDE WITH CONDENSATE PUMP
4. 35% PROPYLENE GLYCOL
SEE SPECIFICATION 238200
SYMBOL
COOLING
CFM HIGH
SPEED
HEATING
CAPACITY BTUH
INDOOR UNIT OUTDOOR SECTION
SEER RATING HEATING HSPF AREA SERVED REMARKS
EAT DB/WB °F BTUH TOTAL BTU SENSIBLE MITSUBISHI MODEL
FULL LOAD
AMPS
SYMBOL MITSUBISHI MODEL EAT °F
ELECTRICAL
VOLTS PHASE HERTZ MCA MOCP
SAC-040 80/62 36,000 25,200 920 22,400 PKA-A36KA7 0.57 SCU-040 PUZ-A36NKA7 95 208-230 1 60 26 42 18.5 10 IT 1, 2, 3, 4, 5, 6
SAC-245A 80/62 36,000 25,200 920 22,400 PKA-A36KA7 0.57 SCU-245A PUZ-A36NKA7 95 208-230 1 60 26 42 18.5 10 IT 1, 2, 3, 4, 5, 6
SAC-245B 80/62 36,000 25,200 920 22,400 PKA-A36KA7 0.57 SCU-245B PUZ-A36NKA7 95 208-230 1 60 26 42 18.5 10 IT 1, 2, 3, 4, 5, 6
SAC-280A 80/62 36,000 25,200 920 22,400 PKA-A36KA7 0.57 SCU-280A PUZ-A36NKA7 95 208-230 1 60 26 42 18.5 10 IT 1, 2, 3, 4, 5, 6
SAC-280B 80/62 36,000 25,200 920 22,400 PKA-A36KA7 0.57 SCU-280B PUZ-A36NKA7 95 208-230 1 60 26 42 18.5 10 IT 1, 2, 3, 4, 5, 6
NOTES:
1. AT SITE ELEVATION 4. FURNISH WITH WIRED THERMOSTAT
2. OR EQUAL FROM SANYO OR CARRIER. INDOOR SECTION RECEIVES POWER FROM OUTDOOR UNIT THROUGH 5. WALL MOUNT UNIT
FIELD SUPPLIED INTERCONNECT WIRING. INVERTER DRIVEN COMPRESSOR. LOW AMBIENT CONTROL TO 0°F.6. CONNECT TO EMERGENCY POWER
3. TOTAL RATING x S/T RATIO x 0.95 ALTITUDE CORRECTION FACTOR.
SEE SPECIFICATION 232300
S-4 VARIES SLOT DIFFUSER KRUEGER 1900 3/4" SLOTS
SEE SPECIFICATION 233416
SYMBOL
MAXIMUM AIRFLOW
CFM
TOTAL STATIC
PRESSURE IN. W.C.
BHP FAN RPM
ELECTRICAL
DRIVE TYPE COOK MODEL
MAX WEIGHT
(LBS)
MAXIMUM SOUND LEVELS dB (OCTAVE BAND)
REMARKS
VOLTS PHASE HERTZ MOTOR HP 1 2 3 4 5 6 7 8 LWA dBA
REF-1 4750 0.5 0.95 971 208 3 60 2 DIRECT 210C17DVF 150 82 83 83 77 72 69 62 57 79 68 1, 2
REF-2 1900 0.5 0.25 957 208 3 60 1/2 DIRECT 165C17DVF 75 72 74 72 65 64 59 54 49 69 58 1, 2
REF-3 500 0.5 0.12 1620 115 1 60 1/6 DIRECT 100C17DHVF 30 64 78 74 63 59 53 48 43 69 57 1, 2
REF-4 250 0.5 0.06 1552 115 1 60 1/6 DIRECT 90C17DEC 30 64 68 68 57 54 49 44 40 62 50 1, 2
NOTES:
1. WITH LOW LEAKAGE DAMPER, RUSKIN CD-50 OR BETTER, MAX LEAKAGE 3 CFM/FT2 AT 1" W.C. WIRE DAMPER TO OPEN WHEN FAN RUNS.
2. WITH EC MOTOR
T-1 VARIES TRANSFER AIR GRILLE KRUEGER SH -
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
Mechanical
Schedules
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
VARIABLE VOLUME WITH REHEAT (VAVR) - WEST AHU
BALANCE MINIMUM MAX.HEATING COIL 30% PROPYLENE GLYCOL MIN.
SYMBOL AIRFLOW AIRFLOW AIRFLOW HTG. CAPACITY
GPM
EWT MIN MAX. PRESSURE TITUS INLET REMARKS
CLG. CFM CFM HTG. CFM BTU/HR DEG F. ROWS DROP, FT. W.C. SIZE SIZE IN.
VAVR-001 750 165 445 16,051 1.1 180 2 0.3 10 10
VAV-002 500 0 0 NA NA NA NA NA 8 8 COOLING ONLY
VAVR-009 1000 235 1000 49,392 3.5 180 3 2.2 12 12
VAVR-010 105 60 100 1,801 0.5 180 1 0.3 6 6
VAVR-011 150 70 150 5,973 0.5 180 2 0.4 6 6
VAVR-012 155 60 100 1,801 0.5 180 1 0.3 6 6
VAVR-013 310 60 100 1,801 0.5 180 1 0.3 6 6
VAVR-015 300 60 300 13,347 0.9 180 3 1.8 6 6
VAVR-016 945 165 165 2,972 0.5 180 1 0.1 10 10
VAVR-018 100 60 100 1,801 0.5 180 1 0.3 6 6
VAVR-020 100 60 100 1,801 0.5 180 1 0.3 6 6
VAVR-022 1050 235 235 4,233 0.5 180 1 0.1 12 12
VAVR-022A 510 105 105 1,891 0.5 180 1 0.3 8 8
VAVR-024 300 65 100 1,801 0.5 180 1 0.3 6 6
VAVR-026A 100 60 100 3,954 0.5 180 1 0.3 6 6
VAVR-026B 100 60 100 3,658 0.5 180 1 0.3 6 6
VAVR-026C 100 60 100 3,658 0.5 180 1 0.3 6 6
VAVR-026D 100 60 100 3,658 0.5 180 1 0.3 6 6
VAVR-026E 100 60 100 3,658 0.5 180 1 0.3 6 6
VAVR-026F 320 60 185 6,672 0.5 180 2 0.4 6 6
VAV-040 200 0 0 NA NA NA NA NA 6 6 COOLING ONLY
VAVR-0-C 100 60 100 1,801 0.5 180 1 0.3 6 6
VAVR-100A 2115 420 770 27,714 2.0 180 2 0.3 16 16
VAVR-100B 2115 420 770 27,714 2.0 180 2 0.3 16 16
VAV-102 100 0 0 NA NA NA NA NA 6 6 COOLING ONLY
VAVR-104 105 60 100 1,801 0.5 180 1 0.3 6 6
VAVR-106 105 60 100 1,801 0.5 180 1 0.3 6 6
VAVR-108 105 60 100 1,801 0.5 180 1 0.3 6 6
VAVR-110 485 140 140 2,522 0.5 180 1 0.3 8 8
VAVR-112 125 60 100 1,801 0.5 180 1 0.3 6 6
VAVR-114 195 60 100 1,801 0.5 180 1 0.3 6 6
VAVR-114A 150 60 100 1,801 0.5 180 1 0.3 6 6
VAVR-118A 2040 420 640 23,060 1.6 180 2 0.3 16 16
VAVR-118B 2040 420 640 23,060 1.6 180 2 0.3 16 16
VAVR-120AA 1245 235 1245 52,412 3.7 180 3 2.5 12 12
VAVR-120AB 1050 335 335 6,034 0.5 180 1 0.1 12 12
VAVR-122AA 1320 445 445 8,016 0.6 180 1 0.1 12 12
VAVR-122AB 1320 445 445 8,016 0.6 180 1 0.1 12 12
VAVR-122AC 1485 535 535 9,637 0.7 180 1 0.0 14 14
VAVR-122AD 700 165 255 9,180 0.6 180 2 0.3 9 9
VAVR-122AE 1400 320 320 10,351 0.7 180 1 0.0 14 14
VAVR-122B 560 220 220 3,963 0.5 180 1 0.3 8 8
VAVR-124 770 165 290 10,416 0.7 180 2 0.3 10 10
VAVR-125 325 90 100 3,066 0.5 180 1 0.3 6 6
VAVR-126 165 60 100 2,713 0.5 180 1 0.3 6 6
VAVR-127 165 60 100 2,757 0.5 180 1 0.3 6 6
VAVR-128 165 60 100 2,713 0.5 180 1 0.3 6 6
VAVR-129 415 105 160 5,724 0.5 180 1 0.3 8 8
VAVR-130 1010 235 600 21,593 1.5 180 2 0.8 12 12
VAVR-131 240 60 220 7,935 0.6 180 2 0.4 6 6
VAVR-132 320 95 100 3,051 0.5 180 1 0.3 6 6
VAVR-134 180 60 155 5,589 0.5 180 2 0.4 6 6
VAVR-136 670 135 550 19,785 1.4 180 2 0.4 9 9
VAVR-138 600 135 210 7,558 0.5 180 1 0.1 9 9
VAVR-140 840 240 240 6,698 0.5 180 1 0.1 10 10
VAVR-142 420 145 145 2,612 0.5 180 1 0.3 8 8
VAVR-146 350 105 105 1,891 0.5 180 1 0.3 8 8
VAVR-148 350 105 105 2,663 0.5 180 1 0.3 8 8
VAVR-200 415 105 175 6,301 0.5 180 1 0.3 8 8
VAVR-202 480 105 185 6,702 0.5 180 2 0.5 8 8
VAVR-204 490 105 170 6,087 0.5 180 1 0.3 8 8
VAVR-206 980 165 445 16,073 1.1 180 2 0.3 10 10
VAVR-208 490 105 135 4,877 0.5 180 1 0.3 8 8
VAVR-210 210 60 100 2,625 0.5 180 1 0.3 6 6
VAVR-212 210 60 100 2,625 0.5 180 1 0.3 6 6
VAVR-214 265 90 100 2,889 0.5 180 1 0.3 6 6
VAVR-216 680 135 175 6,321 0.5 180 1 0.1 9 9
VAVR-218 860 165 505 18,229 1.3 180 2 0.4 10 10
VAVR-220A 1700 320 585 21,042 1.5 180 2 0.4 14 14
VAVR-220B 1700 320 585 21,042 1.5 180 2 0.4 14 14
VAVR-220C 1575 530 530 9,547 0.7 180 1 0.0 14 14
VAVR-220D 1575 530 530 9,547 0.7 180 1 0.0 14 14
VAVR-220E 1595 530 530 9,547 0.7 180 1 0.0 14 14
VAVR-222 840 240 305 10,949 0.8 180 2 0.3 10 10
VAVR-224 840 240 240 4,323 0.5 180 1 0.1 10 10
VAVR-226 210 110 110 1,981 0.5 180 1 0.3 6 6
VAVR-228 945 320 320 5,764 0.5 180 1 0.1 10 10
VAVR-228A 115 60 100 1,801 0.5 180 1 0.3 6 6
VAVR-228B 735 160 160 2,882 0.5 180 1 0.1 9 9
VAVR-228C 125 60 100 1,801 0.5 180 1 0.3 6 6
VAVR-230 110 60 100 1,801 0.5 180 1 0.3 6 6
VAVR-232 145 60 100 1,801 0.5 180 1 0.3 6 6
VAVR-234 1980 420 420 7,565 0.5 180 1 0.1 16 16
VAVR-236 100 60 100 1,801 0.5 180 1 0.3 6 6
VAVR-238 1720 320 860 30,952 2.2 180 2 0.8 14 14
VAVR-240A 1890 320 410 14,745 1.0 180 1 0.1 14 14
VAVR-240B 1840 320 420 15,131 1.1 180 1 0.1 14 14
VAVR-241 115 60 100 2,581 0.5 180 1 0.3 6 6
VAVR-242 100 60 100 1,801 0.5 180 1 0.3 6 6
VAVR-243 100 60 100 2,389 0.5 180 1 0.3 6 6
VAVR-246 250 60 100 1,801 0.5 180 1 0.3 6 6
VAVR-248 350 105 105 3,634 0.5 180 1 0.3 8 8
VAVR-253 980 350 350 6,304 0.5 180 1 0.1 10 10
VAVR-300A 1425 420 420 13,678 1.0 180 1 0.1 14 14
VAVR-300B 1260 255 395 14,185 1.0 180 2 0.4 12 12
VAVR-300C 1425 420 420 13,678 1.0 180 1 0.1 14 14
VAVR-300D 1575 465 465 12,830 0.9 180 1 0.1 14 14
VAVR-302 1005 235 335 12,077 0.9 180 2 0.4 12 12
VAVR-304 410 105 135 4,866 0.5 180 1 0.3 8 8
VAVR-306 200 60 100 3,603 0.5 180 1 0.3 6 6
VAVR-310 620 135 365 13,192 0.9 180 2 0.3 9 9
VAVR-312 510 105 210 7,531 0.5 180 2 0.5 8 8
VAVR-314 560 105 195 6,984 0.5 180 2 0.5 8 8
VAVR-316 610 135 210 7,585 0.5 180 1 0.1 9 9
VAVR-318 480 105 155 5,610 0.5 180 1 0.3 8 8
VAVR-320 540 105 180 6,479 0.5 180 1 0.3 8 8
VAVR-322 240 60 125 4,519 0.5 180 1 0.3 6 6
VAVR-324AA 1260 235 235 5,702 0.5 180 1 0.1 12 12
VAVR-324B 200 60 100 3,526 0.5 180 1 0.3 6 6
VAVR-324BB 1260 235 235 5,702 0.5 180 1 0.1 12 12
VAVR-326 580 170 170 4,342 0.5 180 1 0.3 8 8
VAVR-328 740 195 195 4,786 0.5 180 1 0.1 9 9
VAVR-330 225 60 100 2,892 0.5 180 1 0.3 6 6
VAVR-332 225 60 100 3,175 0.5 180 1 0.3 6 6
VAVR-334 225 60 100 3,175 0.5 180 1 0.3 6 6
VAVR-336 225 60 100 3,175 0.5 180 1 0.3 6 6
VAVR-338 225 60 100 3,175 0.5 180 1 0.3 6 6
VAVR-340 225 60 100 3,175 0.5 180 1 0.3 6 6
VAVR-342A 1920 420 995 35,800 2.5 180 2 0.5 16 16
VAVR-342B 740 220 220 6,253 0.5 180 1 0.1 9 9
VAVR-342C 1480 440 440 12,505 0.9 180 1 0.1 14 14
VAVR-342D 1490 440 440 12,505 0.9 180 1 0.1 14 14
VAVR-342E 1525 455 455 13,220 0.9 180 1 0.1 14 14
VAVR-342F 1480 440 440 12,505 0.9 180 1 0.1 14 14
VAVR-344 1650 365 905 32,574 2.3 180 2 0.9 14 14
VAVR-344A 100 60 100 2,154 0.5 180 1 0.3 6 6
VAVR-344C 160 70 100 3,175 0.5 180 1 0.3 6 6
VAVR-346 150 60 100 2,174 0.5 180 1 0.3 6 6
VAVR-352 200 60 105 3,749 0.5 180 1 0.3 6 6
VAVR-360 150 60 100 2,148 0.5 180 1 0.3 6 6
VAVR-362 175 60 100 2,571 0.5 180 1 0.3 6 6
VAVR-366 700 135 205 7,373 0.5 180 1 0.1 9 9
VAVR-368 250 60 100 2,583 0.5 180 1 0.3 6 6
VAVR-374 150 60 100 2,148 0.5 180 1 0.3 6 6
VAVR-378 320 85 120 4,312 0.5 180 1 0.3 6 6
VAVR-3-A 840 165 410 14,746 1.0 180 2 0.3 10 10
VARIABLE VOLUME WITH REHEAT (VAVR) - WEST AHU
BALANCE MINIMUM MAX.HEATING COIL 30% PROPYLENE GLYCOL MIN.
SYMBOL AIRFLOW AIRFLOW AIRFLOW HTG. CAPACITY
GPM
EWT MIN MAX. PRESSURE TITUS INLET REMARKS
CLG. CFM CFM HTG. CFM BTU/HR DEG F. ROWS DROP, FT. W.C. SIZE SIZE IN.
VARIABLE VOLUME AIR BOXES WITH HW HEAT (VAVR) SELECTION CHART
SYMBOL
VAV-
VAV-
VAV-
VAV-
VAV-
VAV-
VAV-
VAV-
DIMENSION
INCH. (WxH)
12"x8"
12"x10"
14"x12"-1/2"
14"x12"-1/2"
16"x15"
20"x17"-1/2"
24"x18"
38"x18"
RANGE
10-399
400-599
600-849
850-999
1000-1349
1350-1999
2000-2399
2400-4800
9
10
12
14
16
22
KRUEGER
SIZE
8
6
LMHS
LMHS
LMHS
LMHS
LMHS
LMHS
CFM
LMHS
LMHS
KRUEGER
MODEL
AIR PRESSURE
DROP W/ 1 ROW
COIL IN. W.C.
0.75
0.75
0.75
0.75
0.75
0.75
0.75
0.75
SYSTEM
OPERATING
STATIC IN. W.C.
0.30
0.30
0.30
0.30
0.30
0.30
0.30
0.30
COIL
REMARKS
SEE SPECIFICATION SECTION 233616
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
Mechanical
Schedules
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
VARIABLE VOLUME WITH REHEAT (VAVR) - EAST AHU
BALANCE MINIMUM MAX.HEATING COIL 30% PROPYLENE GLYCOL MIN.
SYMBOL AIRFLOW AIRFLOW AIRFLOW HTG. CAPACITY
GPM
EWT MIN MAX. PRESSURE TITUS INLET REMARKS
CLG. CFM CFM HTG. CFM BTU/HR DEG F. ROWS DROP, FT. W.C. SIZE SIZE IN.
VAVR-150A 1400 320 1400 53,009 3.7 180 2 2.0 14 14
VAVR-150B 1400 320 1400 53,009 3.7 180 2 2.0 14 14
VAVR-152 500 105 500 19,043 1.3 180 2 0.8 8 8
VAVR-156 690 230 230 4,143 0.5 180 1 0.1 9 9
VAVR-156A 105 60 100 2,276 0.5 180 1 0.3 6 6
VAVR-156B 140 60 140 5,070 0.5 180 1 0.3 6 6
VAVR-156C 145 60 145 5,185 0.5 180 2 0.4 6 6
VAVR-156E 155 60 100 1,801 0.5 180 1 0.3 6 6
VAVR-156F 105 60 100 1,801 0.5 180 1 0.3 6 6
VAVR-158 290 100 100 1,801 0.5 180 1 0.3 6 6
VAVR-160 435 150 150 2,702 0.5 180 1 0.3 8 8
VAVR-160A 105 60 100 1,801 0.5 180 1 0.3 6 6
VAVR-160B 105 60 100 1,801 0.5 180 1 0.3 6 6
VAVR-162 1260 265 265 9,563 0.7 180 1 0.2 12 12
VAVR-164 940 265 305 11,016 0.8 180 2 0.3 10 10
VAVR-166 1480 320 330 11,850 0.8 180 1 0.1 14 14
VAVR-168 1520 320 340 12,278 0.9 180 1 0.1 14 14
VAVR-170A 360 105 125 4,507 0.5 180 1 0.3 8 8
VAVR-170AA 1800 350 665 23,932 1.7 180 2 0.5 14 14
VAVR-170B 355 105 190 6,873 0.5 180 2 0.5 8 8
VAVR-170BB 1920 640 640 11,528 0.8 180 1 0.1 16 16
VAVR-170C 325 60 325 11,708 0.8 180 2 0.4 6 6
VAVR-172 880 280 280 5,044 0.5 180 1 0.1 10 10
VAV-173 100 0 0 NA NA NA NA NA 6 6 COOLING ONLY
VAVR-174 125 60 100 1,801 0.5 180 1 0.3 6 6
VAVR-175 290 65 100 1,801 0.5 180 1 0.3 6 6
VAVR-178 140 60 100 1,801 0.5 180 1 0.3 6 6
VAVR-179 140 60 100 1,801 0.5 180 1 0.3 6 6
VAVR-180 630 135 585 21,094 1.5 180 2 0.4 9 9
VAVR-181 170 60 170 6,823 0.5 180 2 0.4 6 6
VAVR-182 170 60 135 4,890 0.5 180 1 0.3 6 6
VAVR-183 170 60 135 4,890 0.5 180 1 0.3 6 6
VAVR-184 170 60 135 4,890 0.5 180 1 0.3 6 6
VAVR-185 160 60 110 3,988 0.5 180 1 0.3 6 6
VAVR-186 105 60 100 1,801 0.5 180 1 0.3 6 6
VAVR-188 575 165 265 9,521 0.7 180 2 0.5 8 8
VAVR-188A 325 60 325 12,851 0.9 180 3 1.8 6 6
VAVR-188B 240 60 240 9,645 0.7 180 2 0.4 6 6
VAVR-190 975 215 245 8,861 0.6 180 2 0.3 10 10
VAVR-190A 240 60 240 9,695 0.7 180 2 0.4 6 6
VAVR-190B 325 60 325 12,851 0.9 180 3 1.8 6 6
VAVR-192 870 165 165 2,972 0.5 180 1 0.1 10 10
VAVR-192A 265 60 150 5,408 0.5 180 2 0.4 6 6
VAVR-192B 105 60 100 1,801 0.5 180 1 0.3 6 6
VAVR-192C 280 60 100 1,801 0.5 180 1 0.3 6 6
VAVR-1-U 975 165 495 17,836 1.3 180 2 0.4 10 10
VAVR-1-V 265 100 100 1,801 0.5 180 1 0.3 6 6
VAVR-1-X 200 100 100 1,801 0.5 180 1 0.3 6 6
VAVR-1-Y 580 295 295 5,314 0.5 180 1 0.3 8 8
VAVR-1-Z 490 105 490 19,746 1.4 180 3 1.0 8 8
VAVR-250A 1360 320 1350 51,404 3.6 180 2 2.0 14 14
VAVR-250B 1360 320 1350 51,404 3.6 180 2 2.0 14 14
VAVR-252A 165 60 100 2,160 0.5 180 1 0.3 6 6
VAVR-252AA 1680 420 795 28,607 2.0 180 2 0.8 14 14
VAVR-252B 165 60 100 2,160 0.5 180 1 0.3 6 6
VAVR-252BB 1680 420 795 28,607 2.0 180 2 0.8 14 14
VAVR-252C 305 60 100 2,068 0.5 180 1 0.3 6 6
VAVR-252D 225 60 160 5,753 0.5 180 2 0.4 6 6
VAVR-252E 300 70 300 10,467 0.7 180 2 0.4 6 6
VAVR-252G 275 60 100 2,352 0.5 180 1 0.3 6 6
VAVR-254 1080 340 340 10,925 0.8 180 1 0.3 12 12
VAVR-256 1440 390 465 16,739 1.2 180 2 0.3 14 14
VAVR-256A 285 60 285 10,958 0.8 180 2 0.4 6 6
VAVR-256B 250 60 250 10,056 0.7 180 2 0.4 6 6
VAVR-256C 280 60 280 11,318 0.8 180 2 0.4 6 6
VAVR-258 1200 295 775 27,898 2.0 180 2 0.9 12 12
VAVR-260 1180 340 340 10,451 0.7 180 1 0.2 12 12
VAVR-264 180 60 180 5,911 0.5 180 2 0.4 6 6
VAVR-265 180 60 180 6,191 0.5 180 2 0.4 6 6
VAVR-266 215 60 145 5,208 0.5 180 2 0.4 6 6
VAVR-267 215 60 140 5,001 0.5 180 1 0.3 6 6
VAVR-268 215 60 210 7,598 0.5 180 2 0.4 6 6
VAVR-269 510 105 485 17,509 1.2 180 2 0.5 8 8
VAVR-270A 205 60 100 2,690 0.5 180 1 0.3 6 6
VAVR-270AA 1410 320 940 33,849 2.4 180 2 0.9 14 14
VAVR-270B 200 60 100 2,148 0.5 180 1 0.3 6 6
VAVR-270BB 1350 320 580 20,903 1.5 180 2 0.4 14 14
VAVR-270CC 1650 945 945 20,931 1.5 180 1 0.3 14 14
VAVR-270D 345 110 110 3,151 0.5 180 1 0.3 6 6
VAVR-270DD 810 255 255 6,681 0.5 180 1 0.1 10 10
VAVR-270F 290 115 115 2,996 0.5 180 1 0.3 6 6
VAVR-270G 150 60 100 2,035 0.5 180 1 0.3 6 6
VAVR-270H 150 60 100 2,026 0.5 180 1 0.3 6 6
VAVR-270J 245 60 155 5,580 0.5 180 2 0.4 6 6
VAVR-272 1040 235 290 10,409 0.7 180 1 0.2 12 12
VAVR-274 740 140 215 7,785 0.5 180 1 0.1 9 9
VAVR-276 860 165 255 9,231 0.7 180 2 0.3 10 10
VAVR-278 720 160 270 9,723 0.7 180 2 0.3 9 9
VAVR-284 500 105 405 14,551 1.0 180 2 0.5 8 8
VAVR-286 225 60 100 2,373 0.5 180 1 0.3 6 6
VAVR-288A 100 60 100 2,032 0.5 180 1 0.3 6 6
VAVR-288AA 1350 430 430 10,352 0.7 180 1 0.0 14 14
VAVR-288B 310 60 215 7,734 0.5 180 2 0.4 6 6
VAVR-288BB 380 110 110 2,929 0.5 180 1 0.3 8 8
VAVR-288C 360 105 165 5,921 0.5 180 1 0.3 8 8
VAVR-288D 155 60 100 3,646 0.5 180 1 0.3 6 6
VAVR-288E 100 60 100 3,783 0.5 180 1 0.3 6 6
VAVR-288F 100 60 100 3,783 0.5 180 1 0.3 6 6
VAVR-288G 150 60 150 6,049 0.5 180 2 0.4 6 6
VAVR-299 850 165 850 34,424 2.4 180 3 0.9 10 10
VAVR-2-Q 275 90 275 7,755 0.5 180 2 0.4 6 6
VAVR-2-U 200 60 100 2,586 0.5 180 1 0.3 6 6
VAVR-2-W 285 90 100 3,170 0.5 180 1 0.3 6 6
VAV-3-I 100 0 0 NA NA NA NA NA 6 6 COOLING ONLY
VARIABLE VOLUME WITH REHEAT (VAVR) - EAST AHU
BALANCE MINIMUM MAX.HEATING COIL 30% PROPYLENE GLYCOL MIN.
SYMBOL AIRFLOW AIRFLOW AIRFLOW HTG. CAPACITY
GPM
EWT MIN MAX. PRESSURE TITUS INLET REMARKS
CLG. CFM CFM HTG. CFM BTU/HR DEG F. ROWS DROP, FT. W.C. SIZE SIZE IN.
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
Mechanical
Schedules
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
1111
GGGG
JJJJ
LLLL
MMMM
NNNN
PPPP
QQQQ
EEEE
CCCC
2222 3333 4444 5555
2222
1111
1111
1111
2222
2222
2222
2222
2222
2222
2222
2222
2222
dbkbo^i=klqbp
A.A.A.A.REMOVE ALL EXISTING S.A. / E.A DUCTWORK, S.A. / REMOVE ALL EXISTING S.A. / E.A DUCTWORK, S.A. / REMOVE ALL EXISTING S.A. / E.A DUCTWORK, S.A. / REMOVE ALL EXISTING S.A. / E.A DUCTWORK, S.A. /
R.A. / E.A. DIFFUSERS / GRILLES, CONTROLS, R.A. / E.A. DIFFUSERS / GRILLES, CONTROLS, R.A. / E.A. DIFFUSERS / GRILLES, CONTROLS, R.A. / E.A. DIFFUSERS / GRILLES, CONTROLS,
SENSORS, VAV REHEAT BOXES AND ASSOCIATED SENSORS, VAV REHEAT BOXES AND ASSOCIATED SENSORS, VAV REHEAT BOXES AND ASSOCIATED SENSORS, VAV REHEAT BOXES AND ASSOCIATED
HEATING WATER BRANCH PIPING, VALVES, HEATING WATER BRANCH PIPING, VALVES, HEATING WATER BRANCH PIPING, VALVES, HEATING WATER BRANCH PIPING, VALVES,
STRAINER, ETC. UNLESS OTHERWISE NOTED. STRAINER, ETC. UNLESS OTHERWISE NOTED. STRAINER, ETC. UNLESS OTHERWISE NOTED. STRAINER, ETC. UNLESS OTHERWISE NOTED.
REFERENCE MECHANICAL PIPING DEMOLITION REFERENCE MECHANICAL PIPING DEMOLITION REFERENCE MECHANICAL PIPING DEMOLITION REFERENCE MECHANICAL PIPING DEMOLITION
PLANS.PLANS.PLANS.PLANS.
FIELD VERIFY EXACT LOCATIONS OF EXISTING FIELD VERIFY EXACT LOCATIONS OF EXISTING FIELD VERIFY EXACT LOCATIONS OF EXISTING FIELD VERIFY EXACT LOCATIONS OF EXISTING
PIPING, DUCTWORK, EQUIPMENT, ETC. PIPING, DUCTWORK, EQUIPMENT, ETC. PIPING, DUCTWORK, EQUIPMENT, ETC. PIPING, DUCTWORK, EQUIPMENT, ETC.
DEMOLITION FLOOR PLANS HAVE BEEN CREATED DEMOLITION FLOOR PLANS HAVE BEEN CREATED DEMOLITION FLOOR PLANS HAVE BEEN CREATED DEMOLITION FLOOR PLANS HAVE BEEN CREATED
USING AVAILABLE RECORD DRAWINGS. USING AVAILABLE RECORD DRAWINGS. USING AVAILABLE RECORD DRAWINGS. USING AVAILABLE RECORD DRAWINGS.
CONTRACTOR SHALL BE RESPONSIBLE FOR CONTRACTOR SHALL BE RESPONSIBLE FOR CONTRACTOR SHALL BE RESPONSIBLE FOR CONTRACTOR SHALL BE RESPONSIBLE FOR
VERIFYING EXACT ROUTING OF ALL PIPING, VERIFYING EXACT ROUTING OF ALL PIPING, VERIFYING EXACT ROUTING OF ALL PIPING, VERIFYING EXACT ROUTING OF ALL PIPING,
DUCTWORK, ETC. DURING CONSTRUCTION. DUCTWORK, ETC. DURING CONSTRUCTION. DUCTWORK, ETC. DURING CONSTRUCTION. DUCTWORK, ETC. DURING CONSTRUCTION.
DEMOLITION OF EXISTING MECHANICAL AND DEMOLITION OF EXISTING MECHANICAL AND DEMOLITION OF EXISTING MECHANICAL AND DEMOLITION OF EXISTING MECHANICAL AND
PLUMBING CONSTRUCTION SHALL BE TO THE PLUMBING CONSTRUCTION SHALL BE TO THE PLUMBING CONSTRUCTION SHALL BE TO THE PLUMBING CONSTRUCTION SHALL BE TO THE
EXTENT REQUIRED TO ACCOMMODATE THE EXTENT REQUIRED TO ACCOMMODATE THE EXTENT REQUIRED TO ACCOMMODATE THE EXTENT REQUIRED TO ACCOMMODATE THE
RENOVATION AND THE ADDITION OF NEW WORK. RENOVATION AND THE ADDITION OF NEW WORK. RENOVATION AND THE ADDITION OF NEW WORK. RENOVATION AND THE ADDITION OF NEW WORK.
REFERENCE ARCHITECTURAL DEMOLITION REFERENCE ARCHITECTURAL DEMOLITION REFERENCE ARCHITECTURAL DEMOLITION REFERENCE ARCHITECTURAL DEMOLITION
DRAWINGS TO COORDINATE AND VERIFY THE DRAWINGS TO COORDINATE AND VERIFY THE DRAWINGS TO COORDINATE AND VERIFY THE DRAWINGS TO COORDINATE AND VERIFY THE
EXTENT OF THE DEMOLITION WORK REQUIRED. EXTENT OF THE DEMOLITION WORK REQUIRED. EXTENT OF THE DEMOLITION WORK REQUIRED. EXTENT OF THE DEMOLITION WORK REQUIRED.
ALL PIPING, DUCTWORK, ETC. TO REMAIN SHALL BE ALL PIPING, DUCTWORK, ETC. TO REMAIN SHALL BE ALL PIPING, DUCTWORK, ETC. TO REMAIN SHALL BE ALL PIPING, DUCTWORK, ETC. TO REMAIN SHALL BE
PROTECTED THROUGHOUT THE CONSTRUCTION PROTECTED THROUGHOUT THE CONSTRUCTION PROTECTED THROUGHOUT THE CONSTRUCTION PROTECTED THROUGHOUT THE CONSTRUCTION
PERIOD. PERIOD. PERIOD. PERIOD.
PROVIDE AND INSTALL CAPS ON EXISTING MAIN PROVIDE AND INSTALL CAPS ON EXISTING MAIN PROVIDE AND INSTALL CAPS ON EXISTING MAIN PROVIDE AND INSTALL CAPS ON EXISTING MAIN
DUCTWORK AND / OR PIPING BRANCH BEING DUCTWORK AND / OR PIPING BRANCH BEING DUCTWORK AND / OR PIPING BRANCH BEING DUCTWORK AND / OR PIPING BRANCH BEING
REMOVED. REFERENCE ARCHITECTURAL FOR REMOVED. REFERENCE ARCHITECTURAL FOR REMOVED. REFERENCE ARCHITECTURAL FOR REMOVED. REFERENCE ARCHITECTURAL FOR
PATCHWORK. PATCHWORK. PATCHWORK. PATCHWORK.
INDICATED DEMOLITION OF PIPING AND DUCTWORK INDICATED DEMOLITION OF PIPING AND DUCTWORK INDICATED DEMOLITION OF PIPING AND DUCTWORK INDICATED DEMOLITION OF PIPING AND DUCTWORK
INCLUDES, BUT IS NOT LIMITED TO, THE REMOVAL INCLUDES, BUT IS NOT LIMITED TO, THE REMOVAL INCLUDES, BUT IS NOT LIMITED TO, THE REMOVAL INCLUDES, BUT IS NOT LIMITED TO, THE REMOVAL
OF DUCTWORK, PIPING, FITTINGS, VALVES, OF DUCTWORK, PIPING, FITTINGS, VALVES, OF DUCTWORK, PIPING, FITTINGS, VALVES, OF DUCTWORK, PIPING, FITTINGS, VALVES,
HANGERS, SUPPORTS, INSULATION, ETC. UNLESS HANGERS, SUPPORTS, INSULATION, ETC. UNLESS HANGERS, SUPPORTS, INSULATION, ETC. UNLESS HANGERS, SUPPORTS, INSULATION, ETC. UNLESS
NOTED OTHERWISE. NOTED OTHERWISE. NOTED OTHERWISE. NOTED OTHERWISE.
INDICATED DEMOLITION OF MECHANICAL INDICATED DEMOLITION OF MECHANICAL INDICATED DEMOLITION OF MECHANICAL INDICATED DEMOLITION OF MECHANICAL
EQUIPMENT INCLUDES, BUT IS NOT LIMITED TO, EQUIPMENT INCLUDES, BUT IS NOT LIMITED TO, EQUIPMENT INCLUDES, BUT IS NOT LIMITED TO, EQUIPMENT INCLUDES, BUT IS NOT LIMITED TO,
THE REMOVAL OF EQUIPMENT, PIPING, VALVES, THE REMOVAL OF EQUIPMENT, PIPING, VALVES, THE REMOVAL OF EQUIPMENT, PIPING, VALVES, THE REMOVAL OF EQUIPMENT, PIPING, VALVES,
INSULATION, SEISMIC BRACING, CONTROLS, INSULATION, SEISMIC BRACING, CONTROLS, INSULATION, SEISMIC BRACING, CONTROLS, INSULATION, SEISMIC BRACING, CONTROLS,
ELECTRICAL, ETC. UNLESS NOTED OTHERWISE. ELECTRICAL, ETC. UNLESS NOTED OTHERWISE. ELECTRICAL, ETC. UNLESS NOTED OTHERWISE. ELECTRICAL, ETC. UNLESS NOTED OTHERWISE.
FIELD VERIFY EXACT LOCATIONS OF FIELD VERIFY EXACT LOCATIONS OF FIELD VERIFY EXACT LOCATIONS OF FIELD VERIFY EXACT LOCATIONS OF
THERMOSTATS, SENSOR AND CONTROLLING THERMOSTATS, SENSOR AND CONTROLLING THERMOSTATS, SENSOR AND CONTROLLING THERMOSTATS, SENSOR AND CONTROLLING
UNITS. UNITS. UNITS. UNITS.
CONTRACTOR SHALL BE RESPONSIBLE FOR CONTRACTOR SHALL BE RESPONSIBLE FOR CONTRACTOR SHALL BE RESPONSIBLE FOR CONTRACTOR SHALL BE RESPONSIBLE FOR
PATCHING AND REPAIRING ANY DAMAGE CAUSED PATCHING AND REPAIRING ANY DAMAGE CAUSED PATCHING AND REPAIRING ANY DAMAGE CAUSED PATCHING AND REPAIRING ANY DAMAGE CAUSED
BY HIS / HER PERSONNEL TO EXISTING THAT IS TO BY HIS / HER PERSONNEL TO EXISTING THAT IS TO BY HIS / HER PERSONNEL TO EXISTING THAT IS TO BY HIS / HER PERSONNEL TO EXISTING THAT IS TO
REMAIN OR TO NEWLY INSTALLED BUILDING REMAIN OR TO NEWLY INSTALLED BUILDING REMAIN OR TO NEWLY INSTALLED BUILDING REMAIN OR TO NEWLY INSTALLED BUILDING
COMPONENTS. COMPONENTS. COMPONENTS. COMPONENTS.
PATCH AND SEAL ALL ABANDONED OPENINGS PATCH AND SEAL ALL ABANDONED OPENINGS PATCH AND SEAL ALL ABANDONED OPENINGS PATCH AND SEAL ALL ABANDONED OPENINGS
THROUGH WALLS AND FLOORS. MATCH EXISTING THROUGH WALLS AND FLOORS. MATCH EXISTING THROUGH WALLS AND FLOORS. MATCH EXISTING THROUGH WALLS AND FLOORS. MATCH EXISTING
SURROUNDING FINISH. SURROUNDING FINISH. SURROUNDING FINISH. SURROUNDING FINISH.
CONTRACTOR SHALL REPLACE ANY INSULATION CONTRACTOR SHALL REPLACE ANY INSULATION CONTRACTOR SHALL REPLACE ANY INSULATION CONTRACTOR SHALL REPLACE ANY INSULATION
THAT IS DAMAGED DURING CONSTRUCTION ON THAT IS DAMAGED DURING CONSTRUCTION ON THAT IS DAMAGED DURING CONSTRUCTION ON THAT IS DAMAGED DURING CONSTRUCTION ON
PIPE OR DUCTWORK THAT IS TO REMAIN. PIPE OR DUCTWORK THAT IS TO REMAIN. PIPE OR DUCTWORK THAT IS TO REMAIN. PIPE OR DUCTWORK THAT IS TO REMAIN.
PRIOR TO DEMOLITION OF ANY EQUIPMENT WORK PRIOR TO DEMOLITION OF ANY EQUIPMENT WORK PRIOR TO DEMOLITION OF ANY EQUIPMENT WORK PRIOR TO DEMOLITION OF ANY EQUIPMENT WORK
WITH ELECTRICAL CONTRACTOR AND CONTROLS WITH ELECTRICAL CONTRACTOR AND CONTROLS WITH ELECTRICAL CONTRACTOR AND CONTROLS WITH ELECTRICAL CONTRACTOR AND CONTROLS
CONTRACTOR TO MAKE CERTAIN POWER AND CONTRACTOR TO MAKE CERTAIN POWER AND CONTRACTOR TO MAKE CERTAIN POWER AND CONTRACTOR TO MAKE CERTAIN POWER AND
CONTROLS ARE PROPERLY DISCONNECTED AND CONTROLS ARE PROPERLY DISCONNECTED AND CONTROLS ARE PROPERLY DISCONNECTED AND CONTROLS ARE PROPERLY DISCONNECTED AND
TERMINATED.TERMINATED.TERMINATED.TERMINATED.
B.B.B.B.
C.C.C.C.
D.D.D.D.
E.E.E.E.
F.F.F.F.
G.G.G.G.
H.H.H.H.
I.I.I.I.
J.J.J.J.
K.K.K.K.
L.L.L.L.
M.M.M.M.
N.N.N.N.
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
Level 00 Area
A Mechanical
Demolition
Plan
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
KEY PLAN
A
B
ao^tfkd=klqbp
SCALE:SCALE:SCALE:SCALE:MD100aMD100aMD100aMD100a 1/8" = 1'1/8" = 1'1/8" = 1'1/8" = 1'----0"0"0"0"
ibsbi=MM=^ob^=^=jb`e^kf`^i=abjlifqflk=mi^k1111
0000555510101010 10101010 20202020
NOTE
#DESCRIPTION
1111 REMOVE EXISTING S.A. SOUND TRAP.REMOVE EXISTING S.A. SOUND TRAP.REMOVE EXISTING S.A. SOUND TRAP.REMOVE EXISTING S.A. SOUND TRAP.
2222 EXISTING DUCTWORK AND DIFFUSERS / GRILLESEXISTING DUCTWORK AND DIFFUSERS / GRILLESEXISTING DUCTWORK AND DIFFUSERS / GRILLESEXISTING DUCTWORK AND DIFFUSERS / GRILLES
SHOWN UNHATCHED TO REMAIN. PROTECTSHOWN UNHATCHED TO REMAIN. PROTECTSHOWN UNHATCHED TO REMAIN. PROTECTSHOWN UNHATCHED TO REMAIN. PROTECT
DURING CONSTRUCTION PREPARATORY FOR NEWDURING CONSTRUCTION PREPARATORY FOR NEWDURING CONSTRUCTION PREPARATORY FOR NEWDURING CONSTRUCTION PREPARATORY FOR NEW
CONNECTION. SEE REMODEL PLAN.CONNECTION. SEE REMODEL PLAN.CONNECTION. SEE REMODEL PLAN.CONNECTION. SEE REMODEL PLAN.
1111
GGGG
JJJJ
LLLL
MMMM
NNNN
PPPP
QQQQ
EEEE
CCCC
2222 3333 4444 5555
1111
1111
1111
2222
2222
dbkbo^i=klqbp
A.A.A.A.REMOVE ALL EXISTING S.A. / E.A DUCTWORK, S.A. / REMOVE ALL EXISTING S.A. / E.A DUCTWORK, S.A. / REMOVE ALL EXISTING S.A. / E.A DUCTWORK, S.A. / REMOVE ALL EXISTING S.A. / E.A DUCTWORK, S.A. /
R.A. / E.A. DIFFUSERS / GRILLES, CONTROLS, R.A. / E.A. DIFFUSERS / GRILLES, CONTROLS, R.A. / E.A. DIFFUSERS / GRILLES, CONTROLS, R.A. / E.A. DIFFUSERS / GRILLES, CONTROLS,
SENSORS, VAV REHEAT BOXES AND ASSOCIATED SENSORS, VAV REHEAT BOXES AND ASSOCIATED SENSORS, VAV REHEAT BOXES AND ASSOCIATED SENSORS, VAV REHEAT BOXES AND ASSOCIATED
HEATING WATER BRANCH PIPING, VALVES, HEATING WATER BRANCH PIPING, VALVES, HEATING WATER BRANCH PIPING, VALVES, HEATING WATER BRANCH PIPING, VALVES,
STRAINER, ETC. UNLESS OTHERWISE NOTED. STRAINER, ETC. UNLESS OTHERWISE NOTED. STRAINER, ETC. UNLESS OTHERWISE NOTED. STRAINER, ETC. UNLESS OTHERWISE NOTED.
REFERENCE MECHANICAL PIPING DEMOLITION REFERENCE MECHANICAL PIPING DEMOLITION REFERENCE MECHANICAL PIPING DEMOLITION REFERENCE MECHANICAL PIPING DEMOLITION
PLANS.PLANS.PLANS.PLANS.
FIELD VERIFY EXACT LOCATIONS OF EXISTING FIELD VERIFY EXACT LOCATIONS OF EXISTING FIELD VERIFY EXACT LOCATIONS OF EXISTING FIELD VERIFY EXACT LOCATIONS OF EXISTING
PIPING, DUCTWORK, EQUIPMENT, ETC. PIPING, DUCTWORK, EQUIPMENT, ETC. PIPING, DUCTWORK, EQUIPMENT, ETC. PIPING, DUCTWORK, EQUIPMENT, ETC.
DEMOLITION FLOOR PLANS HAVE BEEN CREATED DEMOLITION FLOOR PLANS HAVE BEEN CREATED DEMOLITION FLOOR PLANS HAVE BEEN CREATED DEMOLITION FLOOR PLANS HAVE BEEN CREATED
USING AVAILABLE RECORD DRAWINGS. USING AVAILABLE RECORD DRAWINGS. USING AVAILABLE RECORD DRAWINGS. USING AVAILABLE RECORD DRAWINGS.
CONTRACTOR SHALL BE RESPONSIBLE FOR CONTRACTOR SHALL BE RESPONSIBLE FOR CONTRACTOR SHALL BE RESPONSIBLE FOR CONTRACTOR SHALL BE RESPONSIBLE FOR
VERIFYING EXACT ROUTING OF ALL PIPING, VERIFYING EXACT ROUTING OF ALL PIPING, VERIFYING EXACT ROUTING OF ALL PIPING, VERIFYING EXACT ROUTING OF ALL PIPING,
DUCTWORK, ETC. DURING CONSTRUCTION. DUCTWORK, ETC. DURING CONSTRUCTION. DUCTWORK, ETC. DURING CONSTRUCTION. DUCTWORK, ETC. DURING CONSTRUCTION.
DEMOLITION OF EXISTING MECHANICAL AND DEMOLITION OF EXISTING MECHANICAL AND DEMOLITION OF EXISTING MECHANICAL AND DEMOLITION OF EXISTING MECHANICAL AND
PLUMBING CONSTRUCTION SHALL BE TO THE PLUMBING CONSTRUCTION SHALL BE TO THE PLUMBING CONSTRUCTION SHALL BE TO THE PLUMBING CONSTRUCTION SHALL BE TO THE
EXTENT REQUIRED TO ACCOMMODATE THE EXTENT REQUIRED TO ACCOMMODATE THE EXTENT REQUIRED TO ACCOMMODATE THE EXTENT REQUIRED TO ACCOMMODATE THE
RENOVATION AND THE ADDITION OF NEW WORK. RENOVATION AND THE ADDITION OF NEW WORK. RENOVATION AND THE ADDITION OF NEW WORK. RENOVATION AND THE ADDITION OF NEW WORK.
REFERENCE ARCHITECTURAL DEMOLITION REFERENCE ARCHITECTURAL DEMOLITION REFERENCE ARCHITECTURAL DEMOLITION REFERENCE ARCHITECTURAL DEMOLITION
DRAWINGS TO COORDINATE AND VERIFY THE DRAWINGS TO COORDINATE AND VERIFY THE DRAWINGS TO COORDINATE AND VERIFY THE DRAWINGS TO COORDINATE AND VERIFY THE
EXTENT OF THE DEMOLITION WORK REQUIRED. EXTENT OF THE DEMOLITION WORK REQUIRED. EXTENT OF THE DEMOLITION WORK REQUIRED. EXTENT OF THE DEMOLITION WORK REQUIRED.
ALL PIPING, DUCTWORK, ETC. TO REMAIN SHALL BE ALL PIPING, DUCTWORK, ETC. TO REMAIN SHALL BE ALL PIPING, DUCTWORK, ETC. TO REMAIN SHALL BE ALL PIPING, DUCTWORK, ETC. TO REMAIN SHALL BE
PROTECTED THROUGHOUT THE CONSTRUCTION PROTECTED THROUGHOUT THE CONSTRUCTION PROTECTED THROUGHOUT THE CONSTRUCTION PROTECTED THROUGHOUT THE CONSTRUCTION
PERIOD. PERIOD. PERIOD. PERIOD.
PROVIDE AND INSTALL CAPS ON EXISTING MAIN PROVIDE AND INSTALL CAPS ON EXISTING MAIN PROVIDE AND INSTALL CAPS ON EXISTING MAIN PROVIDE AND INSTALL CAPS ON EXISTING MAIN
DUCTWORK AND / OR PIPING BRANCH BEING DUCTWORK AND / OR PIPING BRANCH BEING DUCTWORK AND / OR PIPING BRANCH BEING DUCTWORK AND / OR PIPING BRANCH BEING
REMOVED. REFERENCE ARCHITECTURAL FOR REMOVED. REFERENCE ARCHITECTURAL FOR REMOVED. REFERENCE ARCHITECTURAL FOR REMOVED. REFERENCE ARCHITECTURAL FOR
PATCHWORK. PATCHWORK. PATCHWORK. PATCHWORK.
INDICATED DEMOLITION OF PIPING AND DUCTWORK INDICATED DEMOLITION OF PIPING AND DUCTWORK INDICATED DEMOLITION OF PIPING AND DUCTWORK INDICATED DEMOLITION OF PIPING AND DUCTWORK
INCLUDES, BUT IS NOT LIMITED TO, THE REMOVAL INCLUDES, BUT IS NOT LIMITED TO, THE REMOVAL INCLUDES, BUT IS NOT LIMITED TO, THE REMOVAL INCLUDES, BUT IS NOT LIMITED TO, THE REMOVAL
OF DUCTWORK, PIPING, FITTINGS, VALVES, OF DUCTWORK, PIPING, FITTINGS, VALVES, OF DUCTWORK, PIPING, FITTINGS, VALVES, OF DUCTWORK, PIPING, FITTINGS, VALVES,
HANGERS, SUPPORTS, INSULATION, ETC. UNLESS HANGERS, SUPPORTS, INSULATION, ETC. UNLESS HANGERS, SUPPORTS, INSULATION, ETC. UNLESS HANGERS, SUPPORTS, INSULATION, ETC. UNLESS
NOTED OTHERWISE. NOTED OTHERWISE. NOTED OTHERWISE. NOTED OTHERWISE.
INDICATED DEMOLITION OF MECHANICAL INDICATED DEMOLITION OF MECHANICAL INDICATED DEMOLITION OF MECHANICAL INDICATED DEMOLITION OF MECHANICAL
EQUIPMENT INCLUDES, BUT IS NOT LIMITED TO, EQUIPMENT INCLUDES, BUT IS NOT LIMITED TO, EQUIPMENT INCLUDES, BUT IS NOT LIMITED TO, EQUIPMENT INCLUDES, BUT IS NOT LIMITED TO,
THE REMOVAL OF EQUIPMENT, PIPING, VALVES, THE REMOVAL OF EQUIPMENT, PIPING, VALVES, THE REMOVAL OF EQUIPMENT, PIPING, VALVES, THE REMOVAL OF EQUIPMENT, PIPING, VALVES,
INSULATION, SEISMIC BRACING, CONTROLS, INSULATION, SEISMIC BRACING, CONTROLS, INSULATION, SEISMIC BRACING, CONTROLS, INSULATION, SEISMIC BRACING, CONTROLS,
ELECTRICAL, ETC. UNLESS NOTED OTHERWISE. ELECTRICAL, ETC. UNLESS NOTED OTHERWISE. ELECTRICAL, ETC. UNLESS NOTED OTHERWISE. ELECTRICAL, ETC. UNLESS NOTED OTHERWISE.
FIELD VERIFY EXACT LOCATIONS OF FIELD VERIFY EXACT LOCATIONS OF FIELD VERIFY EXACT LOCATIONS OF FIELD VERIFY EXACT LOCATIONS OF
THERMOSTATS, SENSOR AND CONTROLLING THERMOSTATS, SENSOR AND CONTROLLING THERMOSTATS, SENSOR AND CONTROLLING THERMOSTATS, SENSOR AND CONTROLLING
UNITS. UNITS. UNITS. UNITS.
CONTRACTOR SHALL BE RESPONSIBLE FOR CONTRACTOR SHALL BE RESPONSIBLE FOR CONTRACTOR SHALL BE RESPONSIBLE FOR CONTRACTOR SHALL BE RESPONSIBLE FOR
PATCHING AND REPAIRING ANY DAMAGE CAUSED PATCHING AND REPAIRING ANY DAMAGE CAUSED PATCHING AND REPAIRING ANY DAMAGE CAUSED PATCHING AND REPAIRING ANY DAMAGE CAUSED
BY HIS / HER PERSONNEL TO EXISTING THAT IS TO BY HIS / HER PERSONNEL TO EXISTING THAT IS TO BY HIS / HER PERSONNEL TO EXISTING THAT IS TO BY HIS / HER PERSONNEL TO EXISTING THAT IS TO
REMAIN OR TO NEWLY INSTALLED BUILDING REMAIN OR TO NEWLY INSTALLED BUILDING REMAIN OR TO NEWLY INSTALLED BUILDING REMAIN OR TO NEWLY INSTALLED BUILDING
COMPONENTS. COMPONENTS. COMPONENTS. COMPONENTS.
PATCH AND SEAL ALL ABANDONED OPENINGS PATCH AND SEAL ALL ABANDONED OPENINGS PATCH AND SEAL ALL ABANDONED OPENINGS PATCH AND SEAL ALL ABANDONED OPENINGS
THROUGH WALLS AND FLOORS. MATCH EXISTING THROUGH WALLS AND FLOORS. MATCH EXISTING THROUGH WALLS AND FLOORS. MATCH EXISTING THROUGH WALLS AND FLOORS. MATCH EXISTING
SURROUNDING FINISH. SURROUNDING FINISH. SURROUNDING FINISH. SURROUNDING FINISH.
CONTRACTOR SHALL REPLACE ANY INSULATION CONTRACTOR SHALL REPLACE ANY INSULATION CONTRACTOR SHALL REPLACE ANY INSULATION CONTRACTOR SHALL REPLACE ANY INSULATION
THAT IS DAMAGED DURING CONSTRUCTION ON THAT IS DAMAGED DURING CONSTRUCTION ON THAT IS DAMAGED DURING CONSTRUCTION ON THAT IS DAMAGED DURING CONSTRUCTION ON
PIPE OR DUCTWORK THAT IS TO REMAIN. PIPE OR DUCTWORK THAT IS TO REMAIN. PIPE OR DUCTWORK THAT IS TO REMAIN. PIPE OR DUCTWORK THAT IS TO REMAIN.
PRIOR TO DEMOLITION OF ANY EQUIPMENT WORK PRIOR TO DEMOLITION OF ANY EQUIPMENT WORK PRIOR TO DEMOLITION OF ANY EQUIPMENT WORK PRIOR TO DEMOLITION OF ANY EQUIPMENT WORK
WITH ELECTRICAL CONTRACTOR AND CONTROLS WITH ELECTRICAL CONTRACTOR AND CONTROLS WITH ELECTRICAL CONTRACTOR AND CONTROLS WITH ELECTRICAL CONTRACTOR AND CONTROLS
CONTRACTOR TO MAKE CERTAIN POWER AND CONTRACTOR TO MAKE CERTAIN POWER AND CONTRACTOR TO MAKE CERTAIN POWER AND CONTRACTOR TO MAKE CERTAIN POWER AND
CONTROLS ARE PROPERLY DISCONNECTED AND CONTROLS ARE PROPERLY DISCONNECTED AND CONTROLS ARE PROPERLY DISCONNECTED AND CONTROLS ARE PROPERLY DISCONNECTED AND
TERMINATED.TERMINATED.TERMINATED.TERMINATED.
B.B.B.B.
C.C.C.C.
D.D.D.D.
E.E.E.E.
F.F.F.F.
G.G.G.G.
H.H.H.H.
I.I.I.I.
J.J.J.J.
K.K.K.K.
L.L.L.L.
M.M.M.M.
N.N.N.N.
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
Level 01 Area
A Mechanical
Demolition
Plan
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
KEY PLAN
A
B
ao^tfkd=klqbp
0000555510101010 10101010 20202020
NOTE
#DESCRIPTION
1111 PROTECT EXISTING DUCTWORK DURINGPROTECT EXISTING DUCTWORK DURINGPROTECT EXISTING DUCTWORK DURINGPROTECT EXISTING DUCTWORK DURING
CONSTRUCTION PREPARATORY FOR NEWCONSTRUCTION PREPARATORY FOR NEWCONSTRUCTION PREPARATORY FOR NEWCONSTRUCTION PREPARATORY FOR NEW
CONNECTION. SEE REMODEL PLAN.CONNECTION. SEE REMODEL PLAN.CONNECTION. SEE REMODEL PLAN.CONNECTION. SEE REMODEL PLAN.
2222 REMOVE EXISTING E.A. GRILLE AND PROTECTREMOVE EXISTING E.A. GRILLE AND PROTECTREMOVE EXISTING E.A. GRILLE AND PROTECTREMOVE EXISTING E.A. GRILLE AND PROTECT
EXISTING DUCTWORK PREPARATORY FOR NEW E.A.EXISTING DUCTWORK PREPARATORY FOR NEW E.A.EXISTING DUCTWORK PREPARATORY FOR NEW E.A.EXISTING DUCTWORK PREPARATORY FOR NEW E.A.
GRILLE CONNECTION. SEE REMODEL PLAN.GRILLE CONNECTION. SEE REMODEL PLAN.GRILLE CONNECTION. SEE REMODEL PLAN.GRILLE CONNECTION. SEE REMODEL PLAN.
SCALE:SCALE:SCALE:SCALE:MD101aMD101aMD101aMD101a 1/8" = 1'1/8" = 1'1/8" = 1'1/8" = 1'----0"0"0"0"
ibsbi=N=^ob^=^=jb`e^kf`^i=abjlifqflk=mi^k1111
16161616151515151414141413131313121212121111111110101010999988887777
KKKK
HHHH
FFFF
DDDD
BBBB
AAAA
MD402MD402MD402MD402
1111
1111
1111
1111
1111
1111
1111
dbkbo^i=klqbp
A.A.A.A.REMOVE ALL EXISTING S.A. / E.A DUCTWORK, S.A. / REMOVE ALL EXISTING S.A. / E.A DUCTWORK, S.A. / REMOVE ALL EXISTING S.A. / E.A DUCTWORK, S.A. / REMOVE ALL EXISTING S.A. / E.A DUCTWORK, S.A. /
R.A. / E.A. DIFFUSERS / GRILLES, CONTROLS, R.A. / E.A. DIFFUSERS / GRILLES, CONTROLS, R.A. / E.A. DIFFUSERS / GRILLES, CONTROLS, R.A. / E.A. DIFFUSERS / GRILLES, CONTROLS,
SENSORS, VAV REHEAT BOXES AND ASSOCIATED SENSORS, VAV REHEAT BOXES AND ASSOCIATED SENSORS, VAV REHEAT BOXES AND ASSOCIATED SENSORS, VAV REHEAT BOXES AND ASSOCIATED
HEATING WATER BRANCH PIPING, VALVES, HEATING WATER BRANCH PIPING, VALVES, HEATING WATER BRANCH PIPING, VALVES, HEATING WATER BRANCH PIPING, VALVES,
STRAINER, ETC. UNLESS OTHERWISE NOTED. STRAINER, ETC. UNLESS OTHERWISE NOTED. STRAINER, ETC. UNLESS OTHERWISE NOTED. STRAINER, ETC. UNLESS OTHERWISE NOTED.
REFERENCE MECHANICAL PIPING DEMOLITION REFERENCE MECHANICAL PIPING DEMOLITION REFERENCE MECHANICAL PIPING DEMOLITION REFERENCE MECHANICAL PIPING DEMOLITION
PLANS.PLANS.PLANS.PLANS.
FIELD VERIFY EXACT LOCATIONS OF EXISTING FIELD VERIFY EXACT LOCATIONS OF EXISTING FIELD VERIFY EXACT LOCATIONS OF EXISTING FIELD VERIFY EXACT LOCATIONS OF EXISTING
PIPING, DUCTWORK, EQUIPMENT, ETC. PIPING, DUCTWORK, EQUIPMENT, ETC. PIPING, DUCTWORK, EQUIPMENT, ETC. PIPING, DUCTWORK, EQUIPMENT, ETC.
DEMOLITION FLOOR PLANS HAVE BEEN CREATED DEMOLITION FLOOR PLANS HAVE BEEN CREATED DEMOLITION FLOOR PLANS HAVE BEEN CREATED DEMOLITION FLOOR PLANS HAVE BEEN CREATED
USING AVAILABLE RECORD DRAWINGS. USING AVAILABLE RECORD DRAWINGS. USING AVAILABLE RECORD DRAWINGS. USING AVAILABLE RECORD DRAWINGS.
CONTRACTOR SHALL BE RESPONSIBLE FOR CONTRACTOR SHALL BE RESPONSIBLE FOR CONTRACTOR SHALL BE RESPONSIBLE FOR CONTRACTOR SHALL BE RESPONSIBLE FOR
VERIFYING EXACT ROUTING OF ALL PIPING, VERIFYING EXACT ROUTING OF ALL PIPING, VERIFYING EXACT ROUTING OF ALL PIPING, VERIFYING EXACT ROUTING OF ALL PIPING,
DUCTWORK, ETC. DURING CONSTRUCTION. DUCTWORK, ETC. DURING CONSTRUCTION. DUCTWORK, ETC. DURING CONSTRUCTION. DUCTWORK, ETC. DURING CONSTRUCTION.
DEMOLITION OF EXISTING MECHANICAL AND DEMOLITION OF EXISTING MECHANICAL AND DEMOLITION OF EXISTING MECHANICAL AND DEMOLITION OF EXISTING MECHANICAL AND
PLUMBING CONSTRUCTION SHALL BE TO THE PLUMBING CONSTRUCTION SHALL BE TO THE PLUMBING CONSTRUCTION SHALL BE TO THE PLUMBING CONSTRUCTION SHALL BE TO THE
EXTENT REQUIRED TO ACCOMMODATE THE EXTENT REQUIRED TO ACCOMMODATE THE EXTENT REQUIRED TO ACCOMMODATE THE EXTENT REQUIRED TO ACCOMMODATE THE
RENOVATION AND THE ADDITION OF NEW WORK. RENOVATION AND THE ADDITION OF NEW WORK. RENOVATION AND THE ADDITION OF NEW WORK. RENOVATION AND THE ADDITION OF NEW WORK.
REFERENCE ARCHITECTURAL DEMOLITION REFERENCE ARCHITECTURAL DEMOLITION REFERENCE ARCHITECTURAL DEMOLITION REFERENCE ARCHITECTURAL DEMOLITION
DRAWINGS TO COORDINATE AND VERIFY THE DRAWINGS TO COORDINATE AND VERIFY THE DRAWINGS TO COORDINATE AND VERIFY THE DRAWINGS TO COORDINATE AND VERIFY THE
EXTENT OF THE DEMOLITION WORK REQUIRED. EXTENT OF THE DEMOLITION WORK REQUIRED. EXTENT OF THE DEMOLITION WORK REQUIRED. EXTENT OF THE DEMOLITION WORK REQUIRED.
ALL PIPING, DUCTWORK, ETC. TO REMAIN SHALL BE ALL PIPING, DUCTWORK, ETC. TO REMAIN SHALL BE ALL PIPING, DUCTWORK, ETC. TO REMAIN SHALL BE ALL PIPING, DUCTWORK, ETC. TO REMAIN SHALL BE
PROTECTED THROUGHOUT THE CONSTRUCTION PROTECTED THROUGHOUT THE CONSTRUCTION PROTECTED THROUGHOUT THE CONSTRUCTION PROTECTED THROUGHOUT THE CONSTRUCTION
PERIOD. PERIOD. PERIOD. PERIOD.
PROVIDE AND INSTALL CAPS ON EXISTING MAIN PROVIDE AND INSTALL CAPS ON EXISTING MAIN PROVIDE AND INSTALL CAPS ON EXISTING MAIN PROVIDE AND INSTALL CAPS ON EXISTING MAIN
DUCTWORK AND / OR PIPING BRANCH BEING DUCTWORK AND / OR PIPING BRANCH BEING DUCTWORK AND / OR PIPING BRANCH BEING DUCTWORK AND / OR PIPING BRANCH BEING
REMOVED. REFERENCE ARCHITECTURAL FOR REMOVED. REFERENCE ARCHITECTURAL FOR REMOVED. REFERENCE ARCHITECTURAL FOR REMOVED. REFERENCE ARCHITECTURAL FOR
PATCHWORK. PATCHWORK. PATCHWORK. PATCHWORK.
INDICATED DEMOLITION OF PIPING AND DUCTWORK INDICATED DEMOLITION OF PIPING AND DUCTWORK INDICATED DEMOLITION OF PIPING AND DUCTWORK INDICATED DEMOLITION OF PIPING AND DUCTWORK
INCLUDES, BUT IS NOT LIMITED TO, THE REMOVAL INCLUDES, BUT IS NOT LIMITED TO, THE REMOVAL INCLUDES, BUT IS NOT LIMITED TO, THE REMOVAL INCLUDES, BUT IS NOT LIMITED TO, THE REMOVAL
OF DUCTWORK, PIPING, FITTINGS, VALVES, OF DUCTWORK, PIPING, FITTINGS, VALVES, OF DUCTWORK, PIPING, FITTINGS, VALVES, OF DUCTWORK, PIPING, FITTINGS, VALVES,
HANGERS, SUPPORTS, INSULATION, ETC. UNLESS HANGERS, SUPPORTS, INSULATION, ETC. UNLESS HANGERS, SUPPORTS, INSULATION, ETC. UNLESS HANGERS, SUPPORTS, INSULATION, ETC. UNLESS
NOTED OTHERWISE. NOTED OTHERWISE. NOTED OTHERWISE. NOTED OTHERWISE.
INDICATED DEMOLITION OF MECHANICAL INDICATED DEMOLITION OF MECHANICAL INDICATED DEMOLITION OF MECHANICAL INDICATED DEMOLITION OF MECHANICAL
EQUIPMENT INCLUDES, BUT IS NOT LIMITED TO, EQUIPMENT INCLUDES, BUT IS NOT LIMITED TO, EQUIPMENT INCLUDES, BUT IS NOT LIMITED TO, EQUIPMENT INCLUDES, BUT IS NOT LIMITED TO,
THE REMOVAL OF EQUIPMENT, PIPING, VALVES, THE REMOVAL OF EQUIPMENT, PIPING, VALVES, THE REMOVAL OF EQUIPMENT, PIPING, VALVES, THE REMOVAL OF EQUIPMENT, PIPING, VALVES,
INSULATION, SEISMIC BRACING, CONTROLS, INSULATION, SEISMIC BRACING, CONTROLS, INSULATION, SEISMIC BRACING, CONTROLS, INSULATION, SEISMIC BRACING, CONTROLS,
ELECTRICAL, ETC. UNLESS NOTED OTHERWISE. ELECTRICAL, ETC. UNLESS NOTED OTHERWISE. ELECTRICAL, ETC. UNLESS NOTED OTHERWISE. ELECTRICAL, ETC. UNLESS NOTED OTHERWISE.
FIELD VERIFY EXACT LOCATIONS OF FIELD VERIFY EXACT LOCATIONS OF FIELD VERIFY EXACT LOCATIONS OF FIELD VERIFY EXACT LOCATIONS OF
THERMOSTATS, SENSOR AND CONTROLLING THERMOSTATS, SENSOR AND CONTROLLING THERMOSTATS, SENSOR AND CONTROLLING THERMOSTATS, SENSOR AND CONTROLLING
UNITS. UNITS. UNITS. UNITS.
CONTRACTOR SHALL BE RESPONSIBLE FOR CONTRACTOR SHALL BE RESPONSIBLE FOR CONTRACTOR SHALL BE RESPONSIBLE FOR CONTRACTOR SHALL BE RESPONSIBLE FOR
PATCHING AND REPAIRING ANY DAMAGE CAUSED PATCHING AND REPAIRING ANY DAMAGE CAUSED PATCHING AND REPAIRING ANY DAMAGE CAUSED PATCHING AND REPAIRING ANY DAMAGE CAUSED
BY HIS / HER PERSONNEL TO EXISTING THAT IS TO BY HIS / HER PERSONNEL TO EXISTING THAT IS TO BY HIS / HER PERSONNEL TO EXISTING THAT IS TO BY HIS / HER PERSONNEL TO EXISTING THAT IS TO
REMAIN OR TO NEWLY INSTALLED BUILDING REMAIN OR TO NEWLY INSTALLED BUILDING REMAIN OR TO NEWLY INSTALLED BUILDING REMAIN OR TO NEWLY INSTALLED BUILDING
COMPONENTS. COMPONENTS. COMPONENTS. COMPONENTS.
PATCH AND SEAL ALL ABANDONED OPENINGS PATCH AND SEAL ALL ABANDONED OPENINGS PATCH AND SEAL ALL ABANDONED OPENINGS PATCH AND SEAL ALL ABANDONED OPENINGS
THROUGH WALLS AND FLOORS. MATCH EXISTING THROUGH WALLS AND FLOORS. MATCH EXISTING THROUGH WALLS AND FLOORS. MATCH EXISTING THROUGH WALLS AND FLOORS. MATCH EXISTING
SURROUNDING FINISH. SURROUNDING FINISH. SURROUNDING FINISH. SURROUNDING FINISH.
CONTRACTOR SHALL REPLACE ANY INSULATION CONTRACTOR SHALL REPLACE ANY INSULATION CONTRACTOR SHALL REPLACE ANY INSULATION CONTRACTOR SHALL REPLACE ANY INSULATION
THAT IS DAMAGED DURING CONSTRUCTION ON THAT IS DAMAGED DURING CONSTRUCTION ON THAT IS DAMAGED DURING CONSTRUCTION ON THAT IS DAMAGED DURING CONSTRUCTION ON
PIPE OR DUCTWORK THAT IS TO REMAIN. PIPE OR DUCTWORK THAT IS TO REMAIN. PIPE OR DUCTWORK THAT IS TO REMAIN. PIPE OR DUCTWORK THAT IS TO REMAIN.
PRIOR TO DEMOLITION OF ANY EQUIPMENT WORK PRIOR TO DEMOLITION OF ANY EQUIPMENT WORK PRIOR TO DEMOLITION OF ANY EQUIPMENT WORK PRIOR TO DEMOLITION OF ANY EQUIPMENT WORK
WITH ELECTRICAL CONTRACTOR AND CONTROLS WITH ELECTRICAL CONTRACTOR AND CONTROLS WITH ELECTRICAL CONTRACTOR AND CONTROLS WITH ELECTRICAL CONTRACTOR AND CONTROLS
CONTRACTOR TO MAKE CERTAIN POWER AND CONTRACTOR TO MAKE CERTAIN POWER AND CONTRACTOR TO MAKE CERTAIN POWER AND CONTRACTOR TO MAKE CERTAIN POWER AND
CONTROLS ARE PROPERLY DISCONNECTED AND CONTROLS ARE PROPERLY DISCONNECTED AND CONTROLS ARE PROPERLY DISCONNECTED AND CONTROLS ARE PROPERLY DISCONNECTED AND
TERMINATED.TERMINATED.TERMINATED.TERMINATED.
B.B.B.B.
C.C.C.C.
D.D.D.D.
E.E.E.E.
F.F.F.F.
G.G.G.G.
H.H.H.H.
I.I.I.I.
J.J.J.J.
K.K.K.K.
L.L.L.L.
M.M.M.M.
N.N.N.N.
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
Level 01 Area
B Mechanical
Demolition
Plan
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
KEY PLAN
A
B
ao^tfkd=klqbp
0000555510101010 10101010 20202020
NOTE
# DESCRIPTION
1111 PROTECT EXISTING DUCTWORK DURINGPROTECT EXISTING DUCTWORK DURINGPROTECT EXISTING DUCTWORK DURINGPROTECT EXISTING DUCTWORK DURING
CONSTRUCTION PREPARATORY FOR NEWCONSTRUCTION PREPARATORY FOR NEWCONSTRUCTION PREPARATORY FOR NEWCONSTRUCTION PREPARATORY FOR NEW
CONNECTION. SEE REMODEL PLAN.CONNECTION. SEE REMODEL PLAN.CONNECTION. SEE REMODEL PLAN.CONNECTION. SEE REMODEL PLAN.
SCALE:SCALE:SCALE:SCALE:MD101bMD101bMD101bMD101b 1/8" = 1'1/8" = 1'1/8" = 1'1/8" = 1'----0"0"0"0"
ibsbi=N=^ob^=_=jb`e^kf`^i=abjlifqflk=mi^k1111
1111
GGGG
JJJJ
LLLL
MMMM
NNNN
PPPP
QQQQ
EEEE
CCCC
2222 3333 4444 5555
1111
1111
33333333
2222
2222
dbkbo^i=klqbp
A.A.A.A.REMOVE ALL EXISTING S.A. / E.A DUCTWORK, S.A. / REMOVE ALL EXISTING S.A. / E.A DUCTWORK, S.A. / REMOVE ALL EXISTING S.A. / E.A DUCTWORK, S.A. / REMOVE ALL EXISTING S.A. / E.A DUCTWORK, S.A. /
R.A. / E.A. DIFFUSERS / GRILLES, CONTROLS, R.A. / E.A. DIFFUSERS / GRILLES, CONTROLS, R.A. / E.A. DIFFUSERS / GRILLES, CONTROLS, R.A. / E.A. DIFFUSERS / GRILLES, CONTROLS,
SENSORS, VAV REHEAT BOXES AND ASSOCIATED SENSORS, VAV REHEAT BOXES AND ASSOCIATED SENSORS, VAV REHEAT BOXES AND ASSOCIATED SENSORS, VAV REHEAT BOXES AND ASSOCIATED
HEATING WATER BRANCH PIPING, VALVES, HEATING WATER BRANCH PIPING, VALVES, HEATING WATER BRANCH PIPING, VALVES, HEATING WATER BRANCH PIPING, VALVES,
STRAINER, ETC. UNLESS OTHERWISE NOTED. STRAINER, ETC. UNLESS OTHERWISE NOTED. STRAINER, ETC. UNLESS OTHERWISE NOTED. STRAINER, ETC. UNLESS OTHERWISE NOTED.
REFERENCE MECHANICAL PIPING DEMOLITION REFERENCE MECHANICAL PIPING DEMOLITION REFERENCE MECHANICAL PIPING DEMOLITION REFERENCE MECHANICAL PIPING DEMOLITION
PLANS.PLANS.PLANS.PLANS.
FIELD VERIFY EXACT LOCATIONS OF EXISTING FIELD VERIFY EXACT LOCATIONS OF EXISTING FIELD VERIFY EXACT LOCATIONS OF EXISTING FIELD VERIFY EXACT LOCATIONS OF EXISTING
PIPING, DUCTWORK, EQUIPMENT, ETC. PIPING, DUCTWORK, EQUIPMENT, ETC. PIPING, DUCTWORK, EQUIPMENT, ETC. PIPING, DUCTWORK, EQUIPMENT, ETC.
DEMOLITION FLOOR PLANS HAVE BEEN CREATED DEMOLITION FLOOR PLANS HAVE BEEN CREATED DEMOLITION FLOOR PLANS HAVE BEEN CREATED DEMOLITION FLOOR PLANS HAVE BEEN CREATED
USING AVAILABLE RECORD DRAWINGS. USING AVAILABLE RECORD DRAWINGS. USING AVAILABLE RECORD DRAWINGS. USING AVAILABLE RECORD DRAWINGS.
CONTRACTOR SHALL BE RESPONSIBLE FOR CONTRACTOR SHALL BE RESPONSIBLE FOR CONTRACTOR SHALL BE RESPONSIBLE FOR CONTRACTOR SHALL BE RESPONSIBLE FOR
VERIFYING EXACT ROUTING OF ALL PIPING, VERIFYING EXACT ROUTING OF ALL PIPING, VERIFYING EXACT ROUTING OF ALL PIPING, VERIFYING EXACT ROUTING OF ALL PIPING,
DUCTWORK, ETC. DURING CONSTRUCTION. DUCTWORK, ETC. DURING CONSTRUCTION. DUCTWORK, ETC. DURING CONSTRUCTION. DUCTWORK, ETC. DURING CONSTRUCTION.
DEMOLITION OF EXISTING MECHANICAL AND DEMOLITION OF EXISTING MECHANICAL AND DEMOLITION OF EXISTING MECHANICAL AND DEMOLITION OF EXISTING MECHANICAL AND
PLUMBING CONSTRUCTION SHALL BE TO THE PLUMBING CONSTRUCTION SHALL BE TO THE PLUMBING CONSTRUCTION SHALL BE TO THE PLUMBING CONSTRUCTION SHALL BE TO THE
EXTENT REQUIRED TO ACCOMMODATE THE EXTENT REQUIRED TO ACCOMMODATE THE EXTENT REQUIRED TO ACCOMMODATE THE EXTENT REQUIRED TO ACCOMMODATE THE
RENOVATION AND THE ADDITION OF NEW WORK. RENOVATION AND THE ADDITION OF NEW WORK. RENOVATION AND THE ADDITION OF NEW WORK. RENOVATION AND THE ADDITION OF NEW WORK.
REFERENCE ARCHITECTURAL DEMOLITION REFERENCE ARCHITECTURAL DEMOLITION REFERENCE ARCHITECTURAL DEMOLITION REFERENCE ARCHITECTURAL DEMOLITION
DRAWINGS TO COORDINATE AND VERIFY THE DRAWINGS TO COORDINATE AND VERIFY THE DRAWINGS TO COORDINATE AND VERIFY THE DRAWINGS TO COORDINATE AND VERIFY THE
EXTENT OF THE DEMOLITION WORK REQUIRED. EXTENT OF THE DEMOLITION WORK REQUIRED. EXTENT OF THE DEMOLITION WORK REQUIRED. EXTENT OF THE DEMOLITION WORK REQUIRED.
ALL PIPING, DUCTWORK, ETC. TO REMAIN SHALL BE ALL PIPING, DUCTWORK, ETC. TO REMAIN SHALL BE ALL PIPING, DUCTWORK, ETC. TO REMAIN SHALL BE ALL PIPING, DUCTWORK, ETC. TO REMAIN SHALL BE
PROTECTED THROUGHOUT THE CONSTRUCTION PROTECTED THROUGHOUT THE CONSTRUCTION PROTECTED THROUGHOUT THE CONSTRUCTION PROTECTED THROUGHOUT THE CONSTRUCTION
PERIOD. PERIOD. PERIOD. PERIOD.
PROVIDE AND INSTALL CAPS ON EXISTING MAIN PROVIDE AND INSTALL CAPS ON EXISTING MAIN PROVIDE AND INSTALL CAPS ON EXISTING MAIN PROVIDE AND INSTALL CAPS ON EXISTING MAIN
DUCTWORK AND / OR PIPING BRANCH BEING DUCTWORK AND / OR PIPING BRANCH BEING DUCTWORK AND / OR PIPING BRANCH BEING DUCTWORK AND / OR PIPING BRANCH BEING
REMOVED. REFERENCE ARCHITECTURAL FOR REMOVED. REFERENCE ARCHITECTURAL FOR REMOVED. REFERENCE ARCHITECTURAL FOR REMOVED. REFERENCE ARCHITECTURAL FOR
PATCHWORK. PATCHWORK. PATCHWORK. PATCHWORK.
INDICATED DEMOLITION OF PIPING AND DUCTWORK INDICATED DEMOLITION OF PIPING AND DUCTWORK INDICATED DEMOLITION OF PIPING AND DUCTWORK INDICATED DEMOLITION OF PIPING AND DUCTWORK
INCLUDES, BUT IS NOT LIMITED TO, THE REMOVAL INCLUDES, BUT IS NOT LIMITED TO, THE REMOVAL INCLUDES, BUT IS NOT LIMITED TO, THE REMOVAL INCLUDES, BUT IS NOT LIMITED TO, THE REMOVAL
OF DUCTWORK, PIPING, FITTINGS, VALVES, OF DUCTWORK, PIPING, FITTINGS, VALVES, OF DUCTWORK, PIPING, FITTINGS, VALVES, OF DUCTWORK, PIPING, FITTINGS, VALVES,
HANGERS, SUPPORTS, INSULATION, ETC. UNLESS HANGERS, SUPPORTS, INSULATION, ETC. UNLESS HANGERS, SUPPORTS, INSULATION, ETC. UNLESS HANGERS, SUPPORTS, INSULATION, ETC. UNLESS
NOTED OTHERWISE. NOTED OTHERWISE. NOTED OTHERWISE. NOTED OTHERWISE.
INDICATED DEMOLITION OF MECHANICAL INDICATED DEMOLITION OF MECHANICAL INDICATED DEMOLITION OF MECHANICAL INDICATED DEMOLITION OF MECHANICAL
EQUIPMENT INCLUDES, BUT IS NOT LIMITED TO, EQUIPMENT INCLUDES, BUT IS NOT LIMITED TO, EQUIPMENT INCLUDES, BUT IS NOT LIMITED TO, EQUIPMENT INCLUDES, BUT IS NOT LIMITED TO,
THE REMOVAL OF EQUIPMENT, PIPING, VALVES, THE REMOVAL OF EQUIPMENT, PIPING, VALVES, THE REMOVAL OF EQUIPMENT, PIPING, VALVES, THE REMOVAL OF EQUIPMENT, PIPING, VALVES,
INSULATION, SEISMIC BRACING, CONTROLS, INSULATION, SEISMIC BRACING, CONTROLS, INSULATION, SEISMIC BRACING, CONTROLS, INSULATION, SEISMIC BRACING, CONTROLS,
ELECTRICAL, ETC. UNLESS NOTED OTHERWISE. ELECTRICAL, ETC. UNLESS NOTED OTHERWISE. ELECTRICAL, ETC. UNLESS NOTED OTHERWISE. ELECTRICAL, ETC. UNLESS NOTED OTHERWISE.
FIELD VERIFY EXACT LOCATIONS OF FIELD VERIFY EXACT LOCATIONS OF FIELD VERIFY EXACT LOCATIONS OF FIELD VERIFY EXACT LOCATIONS OF
THERMOSTATS, SENSOR AND CONTROLLING THERMOSTATS, SENSOR AND CONTROLLING THERMOSTATS, SENSOR AND CONTROLLING THERMOSTATS, SENSOR AND CONTROLLING
UNITS. UNITS. UNITS. UNITS.
CONTRACTOR SHALL BE RESPONSIBLE FOR CONTRACTOR SHALL BE RESPONSIBLE FOR CONTRACTOR SHALL BE RESPONSIBLE FOR CONTRACTOR SHALL BE RESPONSIBLE FOR
PATCHING AND REPAIRING ANY DAMAGE CAUSED PATCHING AND REPAIRING ANY DAMAGE CAUSED PATCHING AND REPAIRING ANY DAMAGE CAUSED PATCHING AND REPAIRING ANY DAMAGE CAUSED
BY HIS / HER PERSONNEL TO EXISTING THAT IS TO BY HIS / HER PERSONNEL TO EXISTING THAT IS TO BY HIS / HER PERSONNEL TO EXISTING THAT IS TO BY HIS / HER PERSONNEL TO EXISTING THAT IS TO
REMAIN OR TO NEWLY INSTALLED BUILDING REMAIN OR TO NEWLY INSTALLED BUILDING REMAIN OR TO NEWLY INSTALLED BUILDING REMAIN OR TO NEWLY INSTALLED BUILDING
COMPONENTS. COMPONENTS. COMPONENTS. COMPONENTS.
PATCH AND SEAL ALL ABANDONED OPENINGS PATCH AND SEAL ALL ABANDONED OPENINGS PATCH AND SEAL ALL ABANDONED OPENINGS PATCH AND SEAL ALL ABANDONED OPENINGS
THROUGH WALLS AND FLOORS. MATCH EXISTING THROUGH WALLS AND FLOORS. MATCH EXISTING THROUGH WALLS AND FLOORS. MATCH EXISTING THROUGH WALLS AND FLOORS. MATCH EXISTING
SURROUNDING FINISH. SURROUNDING FINISH. SURROUNDING FINISH. SURROUNDING FINISH.
CONTRACTOR SHALL REPLACE ANY INSULATION CONTRACTOR SHALL REPLACE ANY INSULATION CONTRACTOR SHALL REPLACE ANY INSULATION CONTRACTOR SHALL REPLACE ANY INSULATION
THAT IS DAMAGED DURING CONSTRUCTION ON THAT IS DAMAGED DURING CONSTRUCTION ON THAT IS DAMAGED DURING CONSTRUCTION ON THAT IS DAMAGED DURING CONSTRUCTION ON
PIPE OR DUCTWORK THAT IS TO REMAIN. PIPE OR DUCTWORK THAT IS TO REMAIN. PIPE OR DUCTWORK THAT IS TO REMAIN. PIPE OR DUCTWORK THAT IS TO REMAIN.
PRIOR TO DEMOLITION OF ANY EQUIPMENT WORK PRIOR TO DEMOLITION OF ANY EQUIPMENT WORK PRIOR TO DEMOLITION OF ANY EQUIPMENT WORK PRIOR TO DEMOLITION OF ANY EQUIPMENT WORK
WITH ELECTRICAL CONTRACTOR AND CONTROLS WITH ELECTRICAL CONTRACTOR AND CONTROLS WITH ELECTRICAL CONTRACTOR AND CONTROLS WITH ELECTRICAL CONTRACTOR AND CONTROLS
CONTRACTOR TO MAKE CERTAIN POWER AND CONTRACTOR TO MAKE CERTAIN POWER AND CONTRACTOR TO MAKE CERTAIN POWER AND CONTRACTOR TO MAKE CERTAIN POWER AND
CONTROLS ARE PROPERLY DISCONNECTED AND CONTROLS ARE PROPERLY DISCONNECTED AND CONTROLS ARE PROPERLY DISCONNECTED AND CONTROLS ARE PROPERLY DISCONNECTED AND
TERMINATED.TERMINATED.TERMINATED.TERMINATED.
B.B.B.B.
C.C.C.C.
D.D.D.D.
E.E.E.E.
F.F.F.F.
G.G.G.G.
H.H.H.H.
I.I.I.I.
J.J.J.J.
K.K.K.K.
L.L.L.L.
M.M.M.M.
N.N.N.N.
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
Level 02 Area
A Mechanical
Demolition
Plan
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
KEY PLAN
A
B
ao^tfkd=klqbp
0000555510101010 10101010 20202020
NOTE
#DESCRIPTION
1111 PROTECT EXISTING DUCTWORK DURINGPROTECT EXISTING DUCTWORK DURINGPROTECT EXISTING DUCTWORK DURINGPROTECT EXISTING DUCTWORK DURING
CONSTRUCTION PREPARATORY FOR NEWCONSTRUCTION PREPARATORY FOR NEWCONSTRUCTION PREPARATORY FOR NEWCONSTRUCTION PREPARATORY FOR NEW
CONNECTION. SEE REMODEL PLAN.CONNECTION. SEE REMODEL PLAN.CONNECTION. SEE REMODEL PLAN.CONNECTION. SEE REMODEL PLAN.
2222 REMOVE EXISTING E.A. GRILLE AND PROTECTREMOVE EXISTING E.A. GRILLE AND PROTECTREMOVE EXISTING E.A. GRILLE AND PROTECTREMOVE EXISTING E.A. GRILLE AND PROTECT
EXISTING DUCTWORK PREPARATORY FOR NEW E.A.EXISTING DUCTWORK PREPARATORY FOR NEW E.A.EXISTING DUCTWORK PREPARATORY FOR NEW E.A.EXISTING DUCTWORK PREPARATORY FOR NEW E.A.
GRILLE CONNECTION. SEE REMODEL PLAN.GRILLE CONNECTION. SEE REMODEL PLAN.GRILLE CONNECTION. SEE REMODEL PLAN.GRILLE CONNECTION. SEE REMODEL PLAN.
3333 REMOVE EXISTING SPLIT AC SYSTEM COMPLETEREMOVE EXISTING SPLIT AC SYSTEM COMPLETEREMOVE EXISTING SPLIT AC SYSTEM COMPLETEREMOVE EXISTING SPLIT AC SYSTEM COMPLETE
WITH CORRESPONDING REFRIGERATION PIPINGWITH CORRESPONDING REFRIGERATION PIPINGWITH CORRESPONDING REFRIGERATION PIPINGWITH CORRESPONDING REFRIGERATION PIPING
AND ROOFTOP CONDENSING UNIT.AND ROOFTOP CONDENSING UNIT.AND ROOFTOP CONDENSING UNIT.AND ROOFTOP CONDENSING UNIT.
SCALE:SCALE:SCALE:SCALE:MD102aMD102aMD102aMD102a 1/8" = 1'1/8" = 1'1/8" = 1'1/8" = 1'----0"0"0"0"
ibsbi=O=^ob^=^=jb`e^kf`^i=abjlifqflk=mi^k1111
16161616151515151414141413131313121212121111111110101010999988887777
KKKK
HHHH
FFFF
DDDD
BBBB
AAAA
1111
1111
1111
2222 2222
1111
dbkbo^i=klqbp
A.A.A.A.REMOVE ALL EXISTING S.A. / E.A DUCTWORK, S.A. / REMOVE ALL EXISTING S.A. / E.A DUCTWORK, S.A. / REMOVE ALL EXISTING S.A. / E.A DUCTWORK, S.A. / REMOVE ALL EXISTING S.A. / E.A DUCTWORK, S.A. /
R.A. / E.A. DIFFUSERS / GRILLES, CONTROLS, R.A. / E.A. DIFFUSERS / GRILLES, CONTROLS, R.A. / E.A. DIFFUSERS / GRILLES, CONTROLS, R.A. / E.A. DIFFUSERS / GRILLES, CONTROLS,
SENSORS, VAV REHEAT BOXES AND ASSOCIATED SENSORS, VAV REHEAT BOXES AND ASSOCIATED SENSORS, VAV REHEAT BOXES AND ASSOCIATED SENSORS, VAV REHEAT BOXES AND ASSOCIATED
HEATING WATER BRANCH PIPING, VALVES, HEATING WATER BRANCH PIPING, VALVES, HEATING WATER BRANCH PIPING, VALVES, HEATING WATER BRANCH PIPING, VALVES,
STRAINER, ETC. UNLESS OTHERWISE NOTED. STRAINER, ETC. UNLESS OTHERWISE NOTED. STRAINER, ETC. UNLESS OTHERWISE NOTED. STRAINER, ETC. UNLESS OTHERWISE NOTED.
REFERENCE MECHANICAL PIPING DEMOLITION REFERENCE MECHANICAL PIPING DEMOLITION REFERENCE MECHANICAL PIPING DEMOLITION REFERENCE MECHANICAL PIPING DEMOLITION
PLANS.PLANS.PLANS.PLANS.
FIELD VERIFY EXACT LOCATIONS OF EXISTING FIELD VERIFY EXACT LOCATIONS OF EXISTING FIELD VERIFY EXACT LOCATIONS OF EXISTING FIELD VERIFY EXACT LOCATIONS OF EXISTING
PIPING, DUCTWORK, EQUIPMENT, ETC. PIPING, DUCTWORK, EQUIPMENT, ETC. PIPING, DUCTWORK, EQUIPMENT, ETC. PIPING, DUCTWORK, EQUIPMENT, ETC.
DEMOLITION FLOOR PLANS HAVE BEEN CREATED DEMOLITION FLOOR PLANS HAVE BEEN CREATED DEMOLITION FLOOR PLANS HAVE BEEN CREATED DEMOLITION FLOOR PLANS HAVE BEEN CREATED
USING AVAILABLE RECORD DRAWINGS. USING AVAILABLE RECORD DRAWINGS. USING AVAILABLE RECORD DRAWINGS. USING AVAILABLE RECORD DRAWINGS.
CONTRACTOR SHALL BE RESPONSIBLE FOR CONTRACTOR SHALL BE RESPONSIBLE FOR CONTRACTOR SHALL BE RESPONSIBLE FOR CONTRACTOR SHALL BE RESPONSIBLE FOR
VERIFYING EXACT ROUTING OF ALL PIPING, VERIFYING EXACT ROUTING OF ALL PIPING, VERIFYING EXACT ROUTING OF ALL PIPING, VERIFYING EXACT ROUTING OF ALL PIPING,
DUCTWORK, ETC. DURING CONSTRUCTION. DUCTWORK, ETC. DURING CONSTRUCTION. DUCTWORK, ETC. DURING CONSTRUCTION. DUCTWORK, ETC. DURING CONSTRUCTION.
DEMOLITION OF EXISTING MECHANICAL AND DEMOLITION OF EXISTING MECHANICAL AND DEMOLITION OF EXISTING MECHANICAL AND DEMOLITION OF EXISTING MECHANICAL AND
PLUMBING CONSTRUCTION SHALL BE TO THE PLUMBING CONSTRUCTION SHALL BE TO THE PLUMBING CONSTRUCTION SHALL BE TO THE PLUMBING CONSTRUCTION SHALL BE TO THE
EXTENT REQUIRED TO ACCOMMODATE THE EXTENT REQUIRED TO ACCOMMODATE THE EXTENT REQUIRED TO ACCOMMODATE THE EXTENT REQUIRED TO ACCOMMODATE THE
RENOVATION AND THE ADDITION OF NEW WORK. RENOVATION AND THE ADDITION OF NEW WORK. RENOVATION AND THE ADDITION OF NEW WORK. RENOVATION AND THE ADDITION OF NEW WORK.
REFERENCE ARCHITECTURAL DEMOLITION REFERENCE ARCHITECTURAL DEMOLITION REFERENCE ARCHITECTURAL DEMOLITION REFERENCE ARCHITECTURAL DEMOLITION
DRAWINGS TO COORDINATE AND VERIFY THE DRAWINGS TO COORDINATE AND VERIFY THE DRAWINGS TO COORDINATE AND VERIFY THE DRAWINGS TO COORDINATE AND VERIFY THE
EXTENT OF THE DEMOLITION WORK REQUIRED. EXTENT OF THE DEMOLITION WORK REQUIRED. EXTENT OF THE DEMOLITION WORK REQUIRED. EXTENT OF THE DEMOLITION WORK REQUIRED.
ALL PIPING, DUCTWORK, ETC. TO REMAIN SHALL BE ALL PIPING, DUCTWORK, ETC. TO REMAIN SHALL BE ALL PIPING, DUCTWORK, ETC. TO REMAIN SHALL BE ALL PIPING, DUCTWORK, ETC. TO REMAIN SHALL BE
PROTECTED THROUGHOUT THE CONSTRUCTION PROTECTED THROUGHOUT THE CONSTRUCTION PROTECTED THROUGHOUT THE CONSTRUCTION PROTECTED THROUGHOUT THE CONSTRUCTION
PERIOD. PERIOD. PERIOD. PERIOD.
PROVIDE AND INSTALL CAPS ON EXISTING MAIN PROVIDE AND INSTALL CAPS ON EXISTING MAIN PROVIDE AND INSTALL CAPS ON EXISTING MAIN PROVIDE AND INSTALL CAPS ON EXISTING MAIN
DUCTWORK AND / OR PIPING BRANCH BEING DUCTWORK AND / OR PIPING BRANCH BEING DUCTWORK AND / OR PIPING BRANCH BEING DUCTWORK AND / OR PIPING BRANCH BEING
REMOVED. REFERENCE ARCHITECTURAL FOR REMOVED. REFERENCE ARCHITECTURAL FOR REMOVED. REFERENCE ARCHITECTURAL FOR REMOVED. REFERENCE ARCHITECTURAL FOR
PATCHWORK. PATCHWORK. PATCHWORK. PATCHWORK.
INDICATED DEMOLITION OF PIPING AND DUCTWORK INDICATED DEMOLITION OF PIPING AND DUCTWORK INDICATED DEMOLITION OF PIPING AND DUCTWORK INDICATED DEMOLITION OF PIPING AND DUCTWORK
INCLUDES, BUT IS NOT LIMITED TO, THE REMOVAL INCLUDES, BUT IS NOT LIMITED TO, THE REMOVAL INCLUDES, BUT IS NOT LIMITED TO, THE REMOVAL INCLUDES, BUT IS NOT LIMITED TO, THE REMOVAL
OF DUCTWORK, PIPING, FITTINGS, VALVES, OF DUCTWORK, PIPING, FITTINGS, VALVES, OF DUCTWORK, PIPING, FITTINGS, VALVES, OF DUCTWORK, PIPING, FITTINGS, VALVES,
HANGERS, SUPPORTS, INSULATION, ETC. UNLESS HANGERS, SUPPORTS, INSULATION, ETC. UNLESS HANGERS, SUPPORTS, INSULATION, ETC. UNLESS HANGERS, SUPPORTS, INSULATION, ETC. UNLESS
NOTED OTHERWISE. NOTED OTHERWISE. NOTED OTHERWISE. NOTED OTHERWISE.
INDICATED DEMOLITION OF MECHANICAL INDICATED DEMOLITION OF MECHANICAL INDICATED DEMOLITION OF MECHANICAL INDICATED DEMOLITION OF MECHANICAL
EQUIPMENT INCLUDES, BUT IS NOT LIMITED TO, EQUIPMENT INCLUDES, BUT IS NOT LIMITED TO, EQUIPMENT INCLUDES, BUT IS NOT LIMITED TO, EQUIPMENT INCLUDES, BUT IS NOT LIMITED TO,
THE REMOVAL OF EQUIPMENT, PIPING, VALVES, THE REMOVAL OF EQUIPMENT, PIPING, VALVES, THE REMOVAL OF EQUIPMENT, PIPING, VALVES, THE REMOVAL OF EQUIPMENT, PIPING, VALVES,
INSULATION, SEISMIC BRACING, CONTROLS, INSULATION, SEISMIC BRACING, CONTROLS, INSULATION, SEISMIC BRACING, CONTROLS, INSULATION, SEISMIC BRACING, CONTROLS,
ELECTRICAL, ETC. UNLESS NOTED OTHERWISE. ELECTRICAL, ETC. UNLESS NOTED OTHERWISE. ELECTRICAL, ETC. UNLESS NOTED OTHERWISE. ELECTRICAL, ETC. UNLESS NOTED OTHERWISE.
FIELD VERIFY EXACT LOCATIONS OF FIELD VERIFY EXACT LOCATIONS OF FIELD VERIFY EXACT LOCATIONS OF FIELD VERIFY EXACT LOCATIONS OF
THERMOSTATS, SENSOR AND CONTROLLING THERMOSTATS, SENSOR AND CONTROLLING THERMOSTATS, SENSOR AND CONTROLLING THERMOSTATS, SENSOR AND CONTROLLING
UNITS. UNITS. UNITS. UNITS.
CONTRACTOR SHALL BE RESPONSIBLE FOR CONTRACTOR SHALL BE RESPONSIBLE FOR CONTRACTOR SHALL BE RESPONSIBLE FOR CONTRACTOR SHALL BE RESPONSIBLE FOR
PATCHING AND REPAIRING ANY DAMAGE CAUSED PATCHING AND REPAIRING ANY DAMAGE CAUSED PATCHING AND REPAIRING ANY DAMAGE CAUSED PATCHING AND REPAIRING ANY DAMAGE CAUSED
BY HIS / HER PERSONNEL TO EXISTING THAT IS TO BY HIS / HER PERSONNEL TO EXISTING THAT IS TO BY HIS / HER PERSONNEL TO EXISTING THAT IS TO BY HIS / HER PERSONNEL TO EXISTING THAT IS TO
REMAIN OR TO NEWLY INSTALLED BUILDING REMAIN OR TO NEWLY INSTALLED BUILDING REMAIN OR TO NEWLY INSTALLED BUILDING REMAIN OR TO NEWLY INSTALLED BUILDING
COMPONENTS. COMPONENTS. COMPONENTS. COMPONENTS.
PATCH AND SEAL ALL ABANDONED OPENINGS PATCH AND SEAL ALL ABANDONED OPENINGS PATCH AND SEAL ALL ABANDONED OPENINGS PATCH AND SEAL ALL ABANDONED OPENINGS
THROUGH WALLS AND FLOORS. MATCH EXISTING THROUGH WALLS AND FLOORS. MATCH EXISTING THROUGH WALLS AND FLOORS. MATCH EXISTING THROUGH WALLS AND FLOORS. MATCH EXISTING
SURROUNDING FINISH. SURROUNDING FINISH. SURROUNDING FINISH. SURROUNDING FINISH.
CONTRACTOR SHALL REPLACE ANY INSULATION CONTRACTOR SHALL REPLACE ANY INSULATION CONTRACTOR SHALL REPLACE ANY INSULATION CONTRACTOR SHALL REPLACE ANY INSULATION
THAT IS DAMAGED DURING CONSTRUCTION ON THAT IS DAMAGED DURING CONSTRUCTION ON THAT IS DAMAGED DURING CONSTRUCTION ON THAT IS DAMAGED DURING CONSTRUCTION ON
PIPE OR DUCTWORK THAT IS TO REMAIN. PIPE OR DUCTWORK THAT IS TO REMAIN. PIPE OR DUCTWORK THAT IS TO REMAIN. PIPE OR DUCTWORK THAT IS TO REMAIN.
PRIOR TO DEMOLITION OF ANY EQUIPMENT WORK PRIOR TO DEMOLITION OF ANY EQUIPMENT WORK PRIOR TO DEMOLITION OF ANY EQUIPMENT WORK PRIOR TO DEMOLITION OF ANY EQUIPMENT WORK
WITH ELECTRICAL CONTRACTOR AND CONTROLS WITH ELECTRICAL CONTRACTOR AND CONTROLS WITH ELECTRICAL CONTRACTOR AND CONTROLS WITH ELECTRICAL CONTRACTOR AND CONTROLS
CONTRACTOR TO MAKE CERTAIN POWER AND CONTRACTOR TO MAKE CERTAIN POWER AND CONTRACTOR TO MAKE CERTAIN POWER AND CONTRACTOR TO MAKE CERTAIN POWER AND
CONTROLS ARE PROPERLY DISCONNECTED AND CONTROLS ARE PROPERLY DISCONNECTED AND CONTROLS ARE PROPERLY DISCONNECTED AND CONTROLS ARE PROPERLY DISCONNECTED AND
TERMINATED.TERMINATED.TERMINATED.TERMINATED.
B.B.B.B.
C.C.C.C.
D.D.D.D.
E.E.E.E.
F.F.F.F.
G.G.G.G.
H.H.H.H.
I.I.I.I.
J.J.J.J.
K.K.K.K.
L.L.L.L.
M.M.M.M.
N.N.N.N.
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
Level 02 Area
B Mechanical
Demolition
Plan
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
KEY PLAN
A
B
ao^tfkd=klqbp
0000555510101010 10101010 20202020
NOTE
#DESCRIPTION
1111 PROTECT EXISTING DUCTWORK DURINGPROTECT EXISTING DUCTWORK DURINGPROTECT EXISTING DUCTWORK DURINGPROTECT EXISTING DUCTWORK DURING
CONSTRUCTION PREPARATORY FOR NEWCONSTRUCTION PREPARATORY FOR NEWCONSTRUCTION PREPARATORY FOR NEWCONSTRUCTION PREPARATORY FOR NEW
CONNECTION. SEE REMODEL PLAN.CONNECTION. SEE REMODEL PLAN.CONNECTION. SEE REMODEL PLAN.CONNECTION. SEE REMODEL PLAN.
2222 REMOVE EXISTING SPLIT AC SYSTEM COMPLETEREMOVE EXISTING SPLIT AC SYSTEM COMPLETEREMOVE EXISTING SPLIT AC SYSTEM COMPLETEREMOVE EXISTING SPLIT AC SYSTEM COMPLETE
WITH CORRESPONDING REFRIGERATION PIPINGWITH CORRESPONDING REFRIGERATION PIPINGWITH CORRESPONDING REFRIGERATION PIPINGWITH CORRESPONDING REFRIGERATION PIPING
AND ROOFTOP CONDENSING UNIT.AND ROOFTOP CONDENSING UNIT.AND ROOFTOP CONDENSING UNIT.AND ROOFTOP CONDENSING UNIT.
SCALE:SCALE:SCALE:SCALE:MD102bMD102bMD102bMD102b 1/8" = 1'1/8" = 1'1/8" = 1'1/8" = 1'----0"0"0"0"
ibsbi=O=^ob^=_=jb`e^kf`^i=abjlifqflk=mi^k1111
1111
GGGG
JJJJ
LLLL
MMMM
NNNN
PPPP
QQQQ
EEEE
CCCC
2222 3333 4444 5555
3333
3333 3333
3333
1111
1111
2222
2222
(E) REFRIGERANT
PIPING
dbkbo^i=klqbp
A.A.A.A.REMOVE ALL EXISTING S.A. / E.A DUCTWORK, S.A. / REMOVE ALL EXISTING S.A. / E.A DUCTWORK, S.A. / REMOVE ALL EXISTING S.A. / E.A DUCTWORK, S.A. / REMOVE ALL EXISTING S.A. / E.A DUCTWORK, S.A. /
R.A. / E.A. DIFFUSERS / GRILLES, CONTROLS, R.A. / E.A. DIFFUSERS / GRILLES, CONTROLS, R.A. / E.A. DIFFUSERS / GRILLES, CONTROLS, R.A. / E.A. DIFFUSERS / GRILLES, CONTROLS,
SENSORS, VAV REHEAT BOXES AND ASSOCIATED SENSORS, VAV REHEAT BOXES AND ASSOCIATED SENSORS, VAV REHEAT BOXES AND ASSOCIATED SENSORS, VAV REHEAT BOXES AND ASSOCIATED
HEATING WATER BRANCH PIPING, VALVES, HEATING WATER BRANCH PIPING, VALVES, HEATING WATER BRANCH PIPING, VALVES, HEATING WATER BRANCH PIPING, VALVES,
STRAINER, ETC. UNLESS OTHERWISE NOTED. STRAINER, ETC. UNLESS OTHERWISE NOTED. STRAINER, ETC. UNLESS OTHERWISE NOTED. STRAINER, ETC. UNLESS OTHERWISE NOTED.
REFERENCE MECHANICAL PIPING DEMOLITION REFERENCE MECHANICAL PIPING DEMOLITION REFERENCE MECHANICAL PIPING DEMOLITION REFERENCE MECHANICAL PIPING DEMOLITION
PLANS.PLANS.PLANS.PLANS.
FIELD VERIFY EXACT LOCATIONS OF EXISTING FIELD VERIFY EXACT LOCATIONS OF EXISTING FIELD VERIFY EXACT LOCATIONS OF EXISTING FIELD VERIFY EXACT LOCATIONS OF EXISTING
PIPING, DUCTWORK, EQUIPMENT, ETC. PIPING, DUCTWORK, EQUIPMENT, ETC. PIPING, DUCTWORK, EQUIPMENT, ETC. PIPING, DUCTWORK, EQUIPMENT, ETC.
DEMOLITION FLOOR PLANS HAVE BEEN CREATED DEMOLITION FLOOR PLANS HAVE BEEN CREATED DEMOLITION FLOOR PLANS HAVE BEEN CREATED DEMOLITION FLOOR PLANS HAVE BEEN CREATED
USING AVAILABLE RECORD DRAWINGS. USING AVAILABLE RECORD DRAWINGS. USING AVAILABLE RECORD DRAWINGS. USING AVAILABLE RECORD DRAWINGS.
CONTRACTOR SHALL BE RESPONSIBLE FOR CONTRACTOR SHALL BE RESPONSIBLE FOR CONTRACTOR SHALL BE RESPONSIBLE FOR CONTRACTOR SHALL BE RESPONSIBLE FOR
VERIFYING EXACT ROUTING OF ALL PIPING, VERIFYING EXACT ROUTING OF ALL PIPING, VERIFYING EXACT ROUTING OF ALL PIPING, VERIFYING EXACT ROUTING OF ALL PIPING,
DUCTWORK, ETC. DURING CONSTRUCTION. DUCTWORK, ETC. DURING CONSTRUCTION. DUCTWORK, ETC. DURING CONSTRUCTION. DUCTWORK, ETC. DURING CONSTRUCTION.
DEMOLITION OF EXISTING MECHANICAL AND DEMOLITION OF EXISTING MECHANICAL AND DEMOLITION OF EXISTING MECHANICAL AND DEMOLITION OF EXISTING MECHANICAL AND
PLUMBING CONSTRUCTION SHALL BE TO THE PLUMBING CONSTRUCTION SHALL BE TO THE PLUMBING CONSTRUCTION SHALL BE TO THE PLUMBING CONSTRUCTION SHALL BE TO THE
EXTENT REQUIRED TO ACCOMMODATE THE EXTENT REQUIRED TO ACCOMMODATE THE EXTENT REQUIRED TO ACCOMMODATE THE EXTENT REQUIRED TO ACCOMMODATE THE
RENOVATION AND THE ADDITION OF NEW WORK. RENOVATION AND THE ADDITION OF NEW WORK. RENOVATION AND THE ADDITION OF NEW WORK. RENOVATION AND THE ADDITION OF NEW WORK.
REFERENCE ARCHITECTURAL DEMOLITION REFERENCE ARCHITECTURAL DEMOLITION REFERENCE ARCHITECTURAL DEMOLITION REFERENCE ARCHITECTURAL DEMOLITION
DRAWINGS TO COORDINATE AND VERIFY THE DRAWINGS TO COORDINATE AND VERIFY THE DRAWINGS TO COORDINATE AND VERIFY THE DRAWINGS TO COORDINATE AND VERIFY THE
EXTENT OF THE DEMOLITION WORK REQUIRED. EXTENT OF THE DEMOLITION WORK REQUIRED. EXTENT OF THE DEMOLITION WORK REQUIRED. EXTENT OF THE DEMOLITION WORK REQUIRED.
ALL PIPING, DUCTWORK, ETC. TO REMAIN SHALL BE ALL PIPING, DUCTWORK, ETC. TO REMAIN SHALL BE ALL PIPING, DUCTWORK, ETC. TO REMAIN SHALL BE ALL PIPING, DUCTWORK, ETC. TO REMAIN SHALL BE
PROTECTED THROUGHOUT THE CONSTRUCTION PROTECTED THROUGHOUT THE CONSTRUCTION PROTECTED THROUGHOUT THE CONSTRUCTION PROTECTED THROUGHOUT THE CONSTRUCTION
PERIOD. PERIOD. PERIOD. PERIOD.
PROVIDE AND INSTALL CAPS ON EXISTING MAIN PROVIDE AND INSTALL CAPS ON EXISTING MAIN PROVIDE AND INSTALL CAPS ON EXISTING MAIN PROVIDE AND INSTALL CAPS ON EXISTING MAIN
DUCTWORK AND / OR PIPING BRANCH BEING DUCTWORK AND / OR PIPING BRANCH BEING DUCTWORK AND / OR PIPING BRANCH BEING DUCTWORK AND / OR PIPING BRANCH BEING
REMOVED. REFERENCE ARCHITECTURAL FOR REMOVED. REFERENCE ARCHITECTURAL FOR REMOVED. REFERENCE ARCHITECTURAL FOR REMOVED. REFERENCE ARCHITECTURAL FOR
PATCHWORK. PATCHWORK. PATCHWORK. PATCHWORK.
INDICATED DEMOLITION OF PIPING AND DUCTWORK INDICATED DEMOLITION OF PIPING AND DUCTWORK INDICATED DEMOLITION OF PIPING AND DUCTWORK INDICATED DEMOLITION OF PIPING AND DUCTWORK
INCLUDES, BUT IS NOT LIMITED TO, THE REMOVAL INCLUDES, BUT IS NOT LIMITED TO, THE REMOVAL INCLUDES, BUT IS NOT LIMITED TO, THE REMOVAL INCLUDES, BUT IS NOT LIMITED TO, THE REMOVAL
OF DUCTWORK, PIPING, FITTINGS, VALVES, OF DUCTWORK, PIPING, FITTINGS, VALVES, OF DUCTWORK, PIPING, FITTINGS, VALVES, OF DUCTWORK, PIPING, FITTINGS, VALVES,
HANGERS, SUPPORTS, INSULATION, ETC. UNLESS HANGERS, SUPPORTS, INSULATION, ETC. UNLESS HANGERS, SUPPORTS, INSULATION, ETC. UNLESS HANGERS, SUPPORTS, INSULATION, ETC. UNLESS
NOTED OTHERWISE. NOTED OTHERWISE. NOTED OTHERWISE. NOTED OTHERWISE.
INDICATED DEMOLITION OF MECHANICAL INDICATED DEMOLITION OF MECHANICAL INDICATED DEMOLITION OF MECHANICAL INDICATED DEMOLITION OF MECHANICAL
EQUIPMENT INCLUDES, BUT IS NOT LIMITED TO, EQUIPMENT INCLUDES, BUT IS NOT LIMITED TO, EQUIPMENT INCLUDES, BUT IS NOT LIMITED TO, EQUIPMENT INCLUDES, BUT IS NOT LIMITED TO,
THE REMOVAL OF EQUIPMENT, PIPING, VALVES, THE REMOVAL OF EQUIPMENT, PIPING, VALVES, THE REMOVAL OF EQUIPMENT, PIPING, VALVES, THE REMOVAL OF EQUIPMENT, PIPING, VALVES,
INSULATION, SEISMIC BRACING, CONTROLS, INSULATION, SEISMIC BRACING, CONTROLS, INSULATION, SEISMIC BRACING, CONTROLS, INSULATION, SEISMIC BRACING, CONTROLS,
ELECTRICAL, ETC. UNLESS NOTED OTHERWISE. ELECTRICAL, ETC. UNLESS NOTED OTHERWISE. ELECTRICAL, ETC. UNLESS NOTED OTHERWISE. ELECTRICAL, ETC. UNLESS NOTED OTHERWISE.
FIELD VERIFY EXACT LOCATIONS OF FIELD VERIFY EXACT LOCATIONS OF FIELD VERIFY EXACT LOCATIONS OF FIELD VERIFY EXACT LOCATIONS OF
THERMOSTATS, SENSOR AND CONTROLLING THERMOSTATS, SENSOR AND CONTROLLING THERMOSTATS, SENSOR AND CONTROLLING THERMOSTATS, SENSOR AND CONTROLLING
UNITS. UNITS. UNITS. UNITS.
CONTRACTOR SHALL BE RESPONSIBLE FOR CONTRACTOR SHALL BE RESPONSIBLE FOR CONTRACTOR SHALL BE RESPONSIBLE FOR CONTRACTOR SHALL BE RESPONSIBLE FOR
PATCHING AND REPAIRING ANY DAMAGE CAUSED PATCHING AND REPAIRING ANY DAMAGE CAUSED PATCHING AND REPAIRING ANY DAMAGE CAUSED PATCHING AND REPAIRING ANY DAMAGE CAUSED
BY HIS / HER PERSONNEL TO EXISTING THAT IS TO BY HIS / HER PERSONNEL TO EXISTING THAT IS TO BY HIS / HER PERSONNEL TO EXISTING THAT IS TO BY HIS / HER PERSONNEL TO EXISTING THAT IS TO
REMAIN OR TO NEWLY INSTALLED BUILDING REMAIN OR TO NEWLY INSTALLED BUILDING REMAIN OR TO NEWLY INSTALLED BUILDING REMAIN OR TO NEWLY INSTALLED BUILDING
COMPONENTS. COMPONENTS. COMPONENTS. COMPONENTS.
PATCH AND SEAL ALL ABANDONED OPENINGS PATCH AND SEAL ALL ABANDONED OPENINGS PATCH AND SEAL ALL ABANDONED OPENINGS PATCH AND SEAL ALL ABANDONED OPENINGS
THROUGH WALLS AND FLOORS. MATCH EXISTING THROUGH WALLS AND FLOORS. MATCH EXISTING THROUGH WALLS AND FLOORS. MATCH EXISTING THROUGH WALLS AND FLOORS. MATCH EXISTING
SURROUNDING FINISH. SURROUNDING FINISH. SURROUNDING FINISH. SURROUNDING FINISH.
CONTRACTOR SHALL REPLACE ANY INSULATION CONTRACTOR SHALL REPLACE ANY INSULATION CONTRACTOR SHALL REPLACE ANY INSULATION CONTRACTOR SHALL REPLACE ANY INSULATION
THAT IS DAMAGED DURING CONSTRUCTION ON THAT IS DAMAGED DURING CONSTRUCTION ON THAT IS DAMAGED DURING CONSTRUCTION ON THAT IS DAMAGED DURING CONSTRUCTION ON
PIPE OR DUCTWORK THAT IS TO REMAIN. PIPE OR DUCTWORK THAT IS TO REMAIN. PIPE OR DUCTWORK THAT IS TO REMAIN. PIPE OR DUCTWORK THAT IS TO REMAIN.
PRIOR TO DEMOLITION OF ANY EQUIPMENT WORK PRIOR TO DEMOLITION OF ANY EQUIPMENT WORK PRIOR TO DEMOLITION OF ANY EQUIPMENT WORK PRIOR TO DEMOLITION OF ANY EQUIPMENT WORK
WITH ELECTRICAL CONTRACTOR AND CONTROLS WITH ELECTRICAL CONTRACTOR AND CONTROLS WITH ELECTRICAL CONTRACTOR AND CONTROLS WITH ELECTRICAL CONTRACTOR AND CONTROLS
CONTRACTOR TO MAKE CERTAIN POWER AND CONTRACTOR TO MAKE CERTAIN POWER AND CONTRACTOR TO MAKE CERTAIN POWER AND CONTRACTOR TO MAKE CERTAIN POWER AND
CONTROLS ARE PROPERLY DISCONNECTED AND CONTROLS ARE PROPERLY DISCONNECTED AND CONTROLS ARE PROPERLY DISCONNECTED AND CONTROLS ARE PROPERLY DISCONNECTED AND
TERMINATED.TERMINATED.TERMINATED.TERMINATED.
B.B.B.B.
C.C.C.C.
D.D.D.D.
E.E.E.E.
F.F.F.F.
G.G.G.G.
H.H.H.H.
I.I.I.I.
J.J.J.J.
K.K.K.K.
L.L.L.L.
M.M.M.M.
N.N.N.N.
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
Level 03 Area
A Mechanical
Demolition
Plan
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
KEY PLAN
A
B
ao^tfkd=klqbp
0000555510101010 10101010 20202020
NOTE
#DESCRIPTION
1111 PROTECT EXISTING DUCTWORK DURINGPROTECT EXISTING DUCTWORK DURINGPROTECT EXISTING DUCTWORK DURINGPROTECT EXISTING DUCTWORK DURING
CONSTRUCTION PREPARATORY FOR NEWCONSTRUCTION PREPARATORY FOR NEWCONSTRUCTION PREPARATORY FOR NEWCONSTRUCTION PREPARATORY FOR NEW
CONNECTION. SEE REMODEL PLAN.CONNECTION. SEE REMODEL PLAN.CONNECTION. SEE REMODEL PLAN.CONNECTION. SEE REMODEL PLAN.
2222 REMOVE EXISTING E.A. GRILLE AND PROTECTREMOVE EXISTING E.A. GRILLE AND PROTECTREMOVE EXISTING E.A. GRILLE AND PROTECTREMOVE EXISTING E.A. GRILLE AND PROTECT
EXISTING DUCTWORK PREPARATORY FOR NEW E.A.EXISTING DUCTWORK PREPARATORY FOR NEW E.A.EXISTING DUCTWORK PREPARATORY FOR NEW E.A.EXISTING DUCTWORK PREPARATORY FOR NEW E.A.
GRILLE CONNECTION. SEE REMODEL PLAN.GRILLE CONNECTION. SEE REMODEL PLAN.GRILLE CONNECTION. SEE REMODEL PLAN.GRILLE CONNECTION. SEE REMODEL PLAN.
3333 REMOVE EXISTING ROOFTOP EXHAUST FAN.REMOVE EXISTING ROOFTOP EXHAUST FAN.REMOVE EXISTING ROOFTOP EXHAUST FAN.REMOVE EXISTING ROOFTOP EXHAUST FAN.
SCALE:SCALE:SCALE:SCALE:MD103aMD103aMD103aMD103a 1/8" = 1'1/8" = 1'1/8" = 1'1/8" = 1'----0"0"0"0"
ibsbi=P=^ob^=^=jb`e^kf`^i=abjlifqflk=mi^k1111
1111
GGGG
JJJJ
LLLL
MMMM
NNNN
PPPP
QQQQ
EEEE
CCCC
2222 3333 4444 5555
2222
1111
1111
2222
2222
2222
(E) CURB
TO REMAIN
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
Roof Area A
Mechanical
Demolition
Plan
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
KEY PLAN
A
B
ao^tfkd=klqbp
0000555510101010 10101010 20202020
SCALE:SCALE:SCALE:SCALE:MD104aMD104aMD104aMD104a 1/8" = 1'1/8" = 1'1/8" = 1'1/8" = 1'----0"0"0"0"
ollc=^ob^=^=jb`e^kf`^i=abjlifqflk=mi^k1111
NOTE
#DESCRIPTION
1111 REMOVE EXISTING CONDENSING UNIT AND PATCHREMOVE EXISTING CONDENSING UNIT AND PATCHREMOVE EXISTING CONDENSING UNIT AND PATCHREMOVE EXISTING CONDENSING UNIT AND PATCH
ROOF. REFERENCE ARCHITECTURAL DRAWINGSROOF. REFERENCE ARCHITECTURAL DRAWINGSROOF. REFERENCE ARCHITECTURAL DRAWINGSROOF. REFERENCE ARCHITECTURAL DRAWINGS
FOR ROOF PATCHING.FOR ROOF PATCHING.FOR ROOF PATCHING.FOR ROOF PATCHING.
2222 REMOVE EXISTING ROOFTOP EXHAUST FAN ANDREMOVE EXISTING ROOFTOP EXHAUST FAN ANDREMOVE EXISTING ROOFTOP EXHAUST FAN ANDREMOVE EXISTING ROOFTOP EXHAUST FAN AND
EXISTING CURB AND PATCH ROOF. REFERENCEEXISTING CURB AND PATCH ROOF. REFERENCEEXISTING CURB AND PATCH ROOF. REFERENCEEXISTING CURB AND PATCH ROOF. REFERENCE
ARCHITECTURAL DRAWINGS FOR ROOF PATCHING.ARCHITECTURAL DRAWINGS FOR ROOF PATCHING.ARCHITECTURAL DRAWINGS FOR ROOF PATCHING.ARCHITECTURAL DRAWINGS FOR ROOF PATCHING.
16161616151515151414141413131313121212121111111110101010999988887777
KKKK
HHHH
FFFF
DDDD
BBBB
AAAA
1111
2222
2222
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
Roof Area B
Mechanical
Demolition
Plan
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
KEY PLAN
A
B
ao^tfkd=klqbp
0000555510101010 10101010 20202020
NOTE
#DESCRIPTION
1111 REMOVE EXISTING CONDENSING UNIT AND PATCHREMOVE EXISTING CONDENSING UNIT AND PATCHREMOVE EXISTING CONDENSING UNIT AND PATCHREMOVE EXISTING CONDENSING UNIT AND PATCH
ROOF.ROOF.ROOF.ROOF.
2222 EXISTING EXHAUST AIR FAN TO REMAIN, PROTECTEXISTING EXHAUST AIR FAN TO REMAIN, PROTECTEXISTING EXHAUST AIR FAN TO REMAIN, PROTECTEXISTING EXHAUST AIR FAN TO REMAIN, PROTECT
DURING CONSTRUCTION.DURING CONSTRUCTION.DURING CONSTRUCTION.DURING CONSTRUCTION.
SCALE:SCALE:SCALE:SCALE:MD104bMD104bMD104bMD104b 1/8" = 1'1/8" = 1'1/8" = 1'1/8" = 1'----0"0"0"0"
ollc=^ob^=_=jb`e^kf`^i=abjlifqflk=mi^k1111
1111
GGGG
JJJJ
EEEE
CCCC
2222 3333 4444 5555
1111
MD401MD401MD401MD401
1111
2222
3333
4444
5555
1111
1111
1111
2222 1111 2222
1111
1111
1111
2222
1111
5555
4444
4444
4444
4444
6666
dbkbo^i=klqbp
A.A.A.A.FIELD VERIFY EXACT LOCATIONS OF EXISTING FIELD VERIFY EXACT LOCATIONS OF EXISTING FIELD VERIFY EXACT LOCATIONS OF EXISTING FIELD VERIFY EXACT LOCATIONS OF EXISTING
PIPING, DUCTWORK, EQUIPMENT, ETC. PIPING, DUCTWORK, EQUIPMENT, ETC. PIPING, DUCTWORK, EQUIPMENT, ETC. PIPING, DUCTWORK, EQUIPMENT, ETC.
DEMOLITION FLOOR PLANS HAVE BEEN CREATED DEMOLITION FLOOR PLANS HAVE BEEN CREATED DEMOLITION FLOOR PLANS HAVE BEEN CREATED DEMOLITION FLOOR PLANS HAVE BEEN CREATED
USING AVAILABLE RECORD DRAWINGS. USING AVAILABLE RECORD DRAWINGS. USING AVAILABLE RECORD DRAWINGS. USING AVAILABLE RECORD DRAWINGS.
CONTRACTOR SHALL BE RESPONSIBLE FOR CONTRACTOR SHALL BE RESPONSIBLE FOR CONTRACTOR SHALL BE RESPONSIBLE FOR CONTRACTOR SHALL BE RESPONSIBLE FOR
VERIFYING EXACT ROUTING OF ALL PIPING, VERIFYING EXACT ROUTING OF ALL PIPING, VERIFYING EXACT ROUTING OF ALL PIPING, VERIFYING EXACT ROUTING OF ALL PIPING,
DUCTWORK, ETC. DURING CONSTRUCTION. DUCTWORK, ETC. DURING CONSTRUCTION. DUCTWORK, ETC. DURING CONSTRUCTION. DUCTWORK, ETC. DURING CONSTRUCTION.
DEMOLITION OF EXISTING MECHANICAL AND DEMOLITION OF EXISTING MECHANICAL AND DEMOLITION OF EXISTING MECHANICAL AND DEMOLITION OF EXISTING MECHANICAL AND
PLUMBING CONSTRUCTION SHALL BE TO THE PLUMBING CONSTRUCTION SHALL BE TO THE PLUMBING CONSTRUCTION SHALL BE TO THE PLUMBING CONSTRUCTION SHALL BE TO THE
EXTENT REQUIRED TO ACCOMMODATE THE EXTENT REQUIRED TO ACCOMMODATE THE EXTENT REQUIRED TO ACCOMMODATE THE EXTENT REQUIRED TO ACCOMMODATE THE
RENOVATION AND THE ADDITION OF NEW WORK. RENOVATION AND THE ADDITION OF NEW WORK. RENOVATION AND THE ADDITION OF NEW WORK. RENOVATION AND THE ADDITION OF NEW WORK.
REFERENCE ARCHITECTURAL DEMOLITION REFERENCE ARCHITECTURAL DEMOLITION REFERENCE ARCHITECTURAL DEMOLITION REFERENCE ARCHITECTURAL DEMOLITION
DRAWINGS TO COORDINATE AND VERIFY THE DRAWINGS TO COORDINATE AND VERIFY THE DRAWINGS TO COORDINATE AND VERIFY THE DRAWINGS TO COORDINATE AND VERIFY THE
EXTENT OF THE DEMOLITION WORK REQUIRED. EXTENT OF THE DEMOLITION WORK REQUIRED. EXTENT OF THE DEMOLITION WORK REQUIRED. EXTENT OF THE DEMOLITION WORK REQUIRED.
ALL PIPING, DUCTWORK, ETC. TO REMAIN SHALL BE ALL PIPING, DUCTWORK, ETC. TO REMAIN SHALL BE ALL PIPING, DUCTWORK, ETC. TO REMAIN SHALL BE ALL PIPING, DUCTWORK, ETC. TO REMAIN SHALL BE
PROTECTED THROUGHOUT THE CONSTRUCTION PROTECTED THROUGHOUT THE CONSTRUCTION PROTECTED THROUGHOUT THE CONSTRUCTION PROTECTED THROUGHOUT THE CONSTRUCTION
PERIOD. PERIOD. PERIOD. PERIOD.
PROVIDE AND INSTALL CAPS ON EXISTING MAIN PROVIDE AND INSTALL CAPS ON EXISTING MAIN PROVIDE AND INSTALL CAPS ON EXISTING MAIN PROVIDE AND INSTALL CAPS ON EXISTING MAIN
BRANCH BEING REMOVED. REFERENCE BRANCH BEING REMOVED. REFERENCE BRANCH BEING REMOVED. REFERENCE BRANCH BEING REMOVED. REFERENCE
ARCHITECTURAL FOR PATCHWORK. ARCHITECTURAL FOR PATCHWORK. ARCHITECTURAL FOR PATCHWORK. ARCHITECTURAL FOR PATCHWORK.
INDICATED DEMOLITION OF PIPING INCLUDES, BUT INDICATED DEMOLITION OF PIPING INCLUDES, BUT INDICATED DEMOLITION OF PIPING INCLUDES, BUT INDICATED DEMOLITION OF PIPING INCLUDES, BUT
IS NOT LIMITED TO, THE REMOVAL OF PIPING, IS NOT LIMITED TO, THE REMOVAL OF PIPING, IS NOT LIMITED TO, THE REMOVAL OF PIPING, IS NOT LIMITED TO, THE REMOVAL OF PIPING,
FITTINGS, VALVES, HANGERS, SUPPORTS, FITTINGS, VALVES, HANGERS, SUPPORTS, FITTINGS, VALVES, HANGERS, SUPPORTS, FITTINGS, VALVES, HANGERS, SUPPORTS,
INSULATION, ETC. UNLESS NOTED OTHERWISE. INSULATION, ETC. UNLESS NOTED OTHERWISE. INSULATION, ETC. UNLESS NOTED OTHERWISE. INSULATION, ETC. UNLESS NOTED OTHERWISE.
INDICATED DEMOLITION OF MECHANICAL INDICATED DEMOLITION OF MECHANICAL INDICATED DEMOLITION OF MECHANICAL INDICATED DEMOLITION OF MECHANICAL
EQUIPMENT INCLUDES, BUT IS NOT LIMITED TO, EQUIPMENT INCLUDES, BUT IS NOT LIMITED TO, EQUIPMENT INCLUDES, BUT IS NOT LIMITED TO, EQUIPMENT INCLUDES, BUT IS NOT LIMITED TO,
THE REMOVAL OF EQUIPMENT, PIPING, VALVES, THE REMOVAL OF EQUIPMENT, PIPING, VALVES, THE REMOVAL OF EQUIPMENT, PIPING, VALVES, THE REMOVAL OF EQUIPMENT, PIPING, VALVES,
INSULATION, SEISMIC BRACING, CONTROLS, INSULATION, SEISMIC BRACING, CONTROLS, INSULATION, SEISMIC BRACING, CONTROLS, INSULATION, SEISMIC BRACING, CONTROLS,
ELECTRICAL, ETC. UNLESS NOTED OTHERWISE. ELECTRICAL, ETC. UNLESS NOTED OTHERWISE. ELECTRICAL, ETC. UNLESS NOTED OTHERWISE. ELECTRICAL, ETC. UNLESS NOTED OTHERWISE.
CONTRACTOR SHALL BE RESPONSIBLE FOR CONTRACTOR SHALL BE RESPONSIBLE FOR CONTRACTOR SHALL BE RESPONSIBLE FOR CONTRACTOR SHALL BE RESPONSIBLE FOR
PATCHING AND REPAIRING ANY DAMAGE CAUSED PATCHING AND REPAIRING ANY DAMAGE CAUSED PATCHING AND REPAIRING ANY DAMAGE CAUSED PATCHING AND REPAIRING ANY DAMAGE CAUSED
BY HIS / HER PERSONNEL TO EXISTING THAT IS TO BY HIS / HER PERSONNEL TO EXISTING THAT IS TO BY HIS / HER PERSONNEL TO EXISTING THAT IS TO BY HIS / HER PERSONNEL TO EXISTING THAT IS TO
REMAIN OR TO NEWLY INSTALLED BUILDING REMAIN OR TO NEWLY INSTALLED BUILDING REMAIN OR TO NEWLY INSTALLED BUILDING REMAIN OR TO NEWLY INSTALLED BUILDING
COMPONENTS. COMPONENTS. COMPONENTS. COMPONENTS.
PATCH AND SEAL ALL ABANDONED OPENINGS PATCH AND SEAL ALL ABANDONED OPENINGS PATCH AND SEAL ALL ABANDONED OPENINGS PATCH AND SEAL ALL ABANDONED OPENINGS
THROUGH WALLS AND FLOORS. MATCH EXISTING THROUGH WALLS AND FLOORS. MATCH EXISTING THROUGH WALLS AND FLOORS. MATCH EXISTING THROUGH WALLS AND FLOORS. MATCH EXISTING
SURROUNDING FINISH. SURROUNDING FINISH. SURROUNDING FINISH. SURROUNDING FINISH.
CONTRACTOR SHALL REPLACE ANY INSULATION CONTRACTOR SHALL REPLACE ANY INSULATION CONTRACTOR SHALL REPLACE ANY INSULATION CONTRACTOR SHALL REPLACE ANY INSULATION
THAT IS DAMAGED DURING CONSTRUCTION ON THAT IS DAMAGED DURING CONSTRUCTION ON THAT IS DAMAGED DURING CONSTRUCTION ON THAT IS DAMAGED DURING CONSTRUCTION ON
PIPE OR DUCTWORK THAT IS TO REMAIN. PIPE OR DUCTWORK THAT IS TO REMAIN. PIPE OR DUCTWORK THAT IS TO REMAIN. PIPE OR DUCTWORK THAT IS TO REMAIN.
PRIOR TO DEMOLITION OF ANY EQUIPMENT WORK PRIOR TO DEMOLITION OF ANY EQUIPMENT WORK PRIOR TO DEMOLITION OF ANY EQUIPMENT WORK PRIOR TO DEMOLITION OF ANY EQUIPMENT WORK
WITH ELECTRICAL CONTRACTOR AND CONTROLS WITH ELECTRICAL CONTRACTOR AND CONTROLS WITH ELECTRICAL CONTRACTOR AND CONTROLS WITH ELECTRICAL CONTRACTOR AND CONTROLS
CONTRACTOR TO MAKE CERTAIN POWER AND CONTRACTOR TO MAKE CERTAIN POWER AND CONTRACTOR TO MAKE CERTAIN POWER AND CONTRACTOR TO MAKE CERTAIN POWER AND
CONTROLS ARE PROPERLY DISCONNECTED AND CONTROLS ARE PROPERLY DISCONNECTED AND CONTROLS ARE PROPERLY DISCONNECTED AND CONTROLS ARE PROPERLY DISCONNECTED AND
TERMINATED.TERMINATED.TERMINATED.TERMINATED.
B.B.B.B.
C.C.C.C.
D.D.D.D.
E.E.E.E.
F.F.F.F.
G.G.G.G.
H.H.H.H.
I.I.I.I.
J.J.J.J.
K.K.K.K.
L.L.L.L.
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
Level 00 Area
A Mechanical
Piping
Demolition
Plan
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
KEY PLAN
A
B
ao^tfkd=klqbp
0000555510101010 10101010 20202020
SCALE:SCALE:SCALE:SCALE:MD110aMD110aMD110aMD110a 1/8" = 1'1/8" = 1'1/8" = 1'1/8" = 1'----0"0"0"0"
ibsbi=MM=^ob^=^=jb`e^kf`^i=mfmfkd=abjlifqflk=mi^k1111
NOTE
#DESCRIPTION
1111 REMOVE EXISTING VAV REHEAT BOX ANDREMOVE EXISTING VAV REHEAT BOX ANDREMOVE EXISTING VAV REHEAT BOX ANDREMOVE EXISTING VAV REHEAT BOX AND
ASSOCIATED REHEAT COIL, ISOLATION VALVES,ASSOCIATED REHEAT COIL, ISOLATION VALVES,ASSOCIATED REHEAT COIL, ISOLATION VALVES,ASSOCIATED REHEAT COIL, ISOLATION VALVES,
STRAINER, CONTROL VALVE, BALANCE VALVE,STRAINER, CONTROL VALVE, BALANCE VALVE,STRAINER, CONTROL VALVE, BALANCE VALVE,STRAINER, CONTROL VALVE, BALANCE VALVE,
CONTROLS, ETC. COMPLETE.CONTROLS, ETC. COMPLETE.CONTROLS, ETC. COMPLETE.CONTROLS, ETC. COMPLETE.
2222 REMOVE PORTION OF EXISTING HEATING WATERREMOVE PORTION OF EXISTING HEATING WATERREMOVE PORTION OF EXISTING HEATING WATERREMOVE PORTION OF EXISTING HEATING WATER
SUPPLY/RETURN PIPING AS SHOWN.SUPPLY/RETURN PIPING AS SHOWN.SUPPLY/RETURN PIPING AS SHOWN.SUPPLY/RETURN PIPING AS SHOWN.
3333 CAP HEATING WATER SUPPLY/RETURN AT MAIN.CAP HEATING WATER SUPPLY/RETURN AT MAIN.CAP HEATING WATER SUPPLY/RETURN AT MAIN.CAP HEATING WATER SUPPLY/RETURN AT MAIN.
4444 REMOVE EXISTING HWS/R PIPING SERVINGREMOVE EXISTING HWS/R PIPING SERVINGREMOVE EXISTING HWS/R PIPING SERVINGREMOVE EXISTING HWS/R PIPING SERVING
BASEBOARD HEATERS, INCLUDING THE RISERS INBASEBOARD HEATERS, INCLUDING THE RISERS INBASEBOARD HEATERS, INCLUDING THE RISERS INBASEBOARD HEATERS, INCLUDING THE RISERS IN
THE CHASE.THE CHASE.THE CHASE.THE CHASE.
5555 EXISTING HWS/R PIPING SERVING BASEBOARDEXISTING HWS/R PIPING SERVING BASEBOARDEXISTING HWS/R PIPING SERVING BASEBOARDEXISTING HWS/R PIPING SERVING BASEBOARD
HEATERS TO REMAIN AND BE RE-PURPOSED ASHEATERS TO REMAIN AND BE RE-PURPOSED ASHEATERS TO REMAIN AND BE RE-PURPOSED ASHEATERS TO REMAIN AND BE RE-PURPOSED AS
CHILLED WATER SUPPLY AND RETURN PIPING.CHILLED WATER SUPPLY AND RETURN PIPING.CHILLED WATER SUPPLY AND RETURN PIPING.CHILLED WATER SUPPLY AND RETURN PIPING.
FIELD VERIFY EXISTING PIPE ROUTING.FIELD VERIFY EXISTING PIPE ROUTING.FIELD VERIFY EXISTING PIPE ROUTING.FIELD VERIFY EXISTING PIPE ROUTING.
6666 EXISTING CHILLED WATER PIPING IN CHASE TOEXISTING CHILLED WATER PIPING IN CHASE TOEXISTING CHILLED WATER PIPING IN CHASE TOEXISTING CHILLED WATER PIPING IN CHASE TO
REMAIN.REMAIN.REMAIN.REMAIN.
dbkbo^i=klqbp
A.A.A.A.FIELD VERIFY EXACT LOCATIONS OF EXISTING FIELD VERIFY EXACT LOCATIONS OF EXISTING FIELD VERIFY EXACT LOCATIONS OF EXISTING FIELD VERIFY EXACT LOCATIONS OF EXISTING
PIPING, DUCTWORK, EQUIPMENT, ETC. PIPING, DUCTWORK, EQUIPMENT, ETC. PIPING, DUCTWORK, EQUIPMENT, ETC. PIPING, DUCTWORK, EQUIPMENT, ETC.
DEMOLITION FLOOR PLANS HAVE BEEN CREATED DEMOLITION FLOOR PLANS HAVE BEEN CREATED DEMOLITION FLOOR PLANS HAVE BEEN CREATED DEMOLITION FLOOR PLANS HAVE BEEN CREATED
USING AVAILABLE RECORD DRAWINGS. USING AVAILABLE RECORD DRAWINGS. USING AVAILABLE RECORD DRAWINGS. USING AVAILABLE RECORD DRAWINGS.
CONTRACTOR SHALL BE RESPONSIBLE FOR CONTRACTOR SHALL BE RESPONSIBLE FOR CONTRACTOR SHALL BE RESPONSIBLE FOR CONTRACTOR SHALL BE RESPONSIBLE FOR
VERIFYING EXACT ROUTING OF ALL PIPING, VERIFYING EXACT ROUTING OF ALL PIPING, VERIFYING EXACT ROUTING OF ALL PIPING, VERIFYING EXACT ROUTING OF ALL PIPING,
DUCTWORK, ETC. DURING CONSTRUCTION. DUCTWORK, ETC. DURING CONSTRUCTION. DUCTWORK, ETC. DURING CONSTRUCTION. DUCTWORK, ETC. DURING CONSTRUCTION.
DEMOLITION OF EXISTING MECHANICAL AND DEMOLITION OF EXISTING MECHANICAL AND DEMOLITION OF EXISTING MECHANICAL AND DEMOLITION OF EXISTING MECHANICAL AND
PLUMBING CONSTRUCTION SHALL BE TO THE PLUMBING CONSTRUCTION SHALL BE TO THE PLUMBING CONSTRUCTION SHALL BE TO THE PLUMBING CONSTRUCTION SHALL BE TO THE
EXTENT REQUIRED TO ACCOMMODATE THE EXTENT REQUIRED TO ACCOMMODATE THE EXTENT REQUIRED TO ACCOMMODATE THE EXTENT REQUIRED TO ACCOMMODATE THE
RENOVATION AND THE ADDITION OF NEW WORK. RENOVATION AND THE ADDITION OF NEW WORK. RENOVATION AND THE ADDITION OF NEW WORK. RENOVATION AND THE ADDITION OF NEW WORK.
REFERENCE ARCHITECTURAL DEMOLITION REFERENCE ARCHITECTURAL DEMOLITION REFERENCE ARCHITECTURAL DEMOLITION REFERENCE ARCHITECTURAL DEMOLITION
DRAWINGS TO COORDINATE AND VERIFY THE DRAWINGS TO COORDINATE AND VERIFY THE DRAWINGS TO COORDINATE AND VERIFY THE DRAWINGS TO COORDINATE AND VERIFY THE
EXTENT OF THE DEMOLITION WORK REQUIRED. EXTENT OF THE DEMOLITION WORK REQUIRED. EXTENT OF THE DEMOLITION WORK REQUIRED. EXTENT OF THE DEMOLITION WORK REQUIRED.
ALL PIPING, DUCTWORK, ETC. TO REMAIN SHALL BE ALL PIPING, DUCTWORK, ETC. TO REMAIN SHALL BE ALL PIPING, DUCTWORK, ETC. TO REMAIN SHALL BE ALL PIPING, DUCTWORK, ETC. TO REMAIN SHALL BE
PROTECTED THROUGHOUT THE CONSTRUCTION PROTECTED THROUGHOUT THE CONSTRUCTION PROTECTED THROUGHOUT THE CONSTRUCTION PROTECTED THROUGHOUT THE CONSTRUCTION
PERIOD. PERIOD. PERIOD. PERIOD.
PROVIDE AND INSTALL CAPS ON EXISTING MAIN PROVIDE AND INSTALL CAPS ON EXISTING MAIN PROVIDE AND INSTALL CAPS ON EXISTING MAIN PROVIDE AND INSTALL CAPS ON EXISTING MAIN
BRANCH BEING REMOVED. REFERENCE BRANCH BEING REMOVED. REFERENCE BRANCH BEING REMOVED. REFERENCE BRANCH BEING REMOVED. REFERENCE
ARCHITECTURAL FOR PATCHWORK. ARCHITECTURAL FOR PATCHWORK. ARCHITECTURAL FOR PATCHWORK. ARCHITECTURAL FOR PATCHWORK.
INDICATED DEMOLITION OF PIPING INCLUDES, BUT INDICATED DEMOLITION OF PIPING INCLUDES, BUT INDICATED DEMOLITION OF PIPING INCLUDES, BUT INDICATED DEMOLITION OF PIPING INCLUDES, BUT
IS NOT LIMITED TO, THE REMOVAL OF PIPING, IS NOT LIMITED TO, THE REMOVAL OF PIPING, IS NOT LIMITED TO, THE REMOVAL OF PIPING, IS NOT LIMITED TO, THE REMOVAL OF PIPING,
FITTINGS, VALVES, HANGERS, SUPPORTS, FITTINGS, VALVES, HANGERS, SUPPORTS, FITTINGS, VALVES, HANGERS, SUPPORTS, FITTINGS, VALVES, HANGERS, SUPPORTS,
INSULATION, ETC. UNLESS NOTED OTHERWISE. INSULATION, ETC. UNLESS NOTED OTHERWISE. INSULATION, ETC. UNLESS NOTED OTHERWISE. INSULATION, ETC. UNLESS NOTED OTHERWISE.
INDICATED DEMOLITION OF MECHANICAL INDICATED DEMOLITION OF MECHANICAL INDICATED DEMOLITION OF MECHANICAL INDICATED DEMOLITION OF MECHANICAL
EQUIPMENT INCLUDES, BUT IS NOT LIMITED TO, EQUIPMENT INCLUDES, BUT IS NOT LIMITED TO, EQUIPMENT INCLUDES, BUT IS NOT LIMITED TO, EQUIPMENT INCLUDES, BUT IS NOT LIMITED TO,
THE REMOVAL OF EQUIPMENT, PIPING, VALVES, THE REMOVAL OF EQUIPMENT, PIPING, VALVES, THE REMOVAL OF EQUIPMENT, PIPING, VALVES, THE REMOVAL OF EQUIPMENT, PIPING, VALVES,
INSULATION, SEISMIC BRACING, CONTROLS, INSULATION, SEISMIC BRACING, CONTROLS, INSULATION, SEISMIC BRACING, CONTROLS, INSULATION, SEISMIC BRACING, CONTROLS,
ELECTRICAL, ETC. UNLESS NOTED OTHERWISE. ELECTRICAL, ETC. UNLESS NOTED OTHERWISE. ELECTRICAL, ETC. UNLESS NOTED OTHERWISE. ELECTRICAL, ETC. UNLESS NOTED OTHERWISE.
CONTRACTOR SHALL BE RESPONSIBLE FOR CONTRACTOR SHALL BE RESPONSIBLE FOR CONTRACTOR SHALL BE RESPONSIBLE FOR CONTRACTOR SHALL BE RESPONSIBLE FOR
PATCHING AND REPAIRING ANY DAMAGE CAUSED PATCHING AND REPAIRING ANY DAMAGE CAUSED PATCHING AND REPAIRING ANY DAMAGE CAUSED PATCHING AND REPAIRING ANY DAMAGE CAUSED
BY HIS / HER PERSONNEL TO EXISTING THAT IS TO BY HIS / HER PERSONNEL TO EXISTING THAT IS TO BY HIS / HER PERSONNEL TO EXISTING THAT IS TO BY HIS / HER PERSONNEL TO EXISTING THAT IS TO
REMAIN OR TO NEWLY INSTALLED BUILDING REMAIN OR TO NEWLY INSTALLED BUILDING REMAIN OR TO NEWLY INSTALLED BUILDING REMAIN OR TO NEWLY INSTALLED BUILDING
COMPONENTS. COMPONENTS. COMPONENTS. COMPONENTS.
PATCH AND SEAL ALL ABANDONED OPENINGS PATCH AND SEAL ALL ABANDONED OPENINGS PATCH AND SEAL ALL ABANDONED OPENINGS PATCH AND SEAL ALL ABANDONED OPENINGS
THROUGH WALLS AND FLOORS. MATCH EXISTING THROUGH WALLS AND FLOORS. MATCH EXISTING THROUGH WALLS AND FLOORS. MATCH EXISTING THROUGH WALLS AND FLOORS. MATCH EXISTING
SURROUNDING FINISH. SURROUNDING FINISH. SURROUNDING FINISH. SURROUNDING FINISH.
CONTRACTOR SHALL REPLACE ANY INSULATION CONTRACTOR SHALL REPLACE ANY INSULATION CONTRACTOR SHALL REPLACE ANY INSULATION CONTRACTOR SHALL REPLACE ANY INSULATION
THAT IS DAMAGED DURING CONSTRUCTION ON THAT IS DAMAGED DURING CONSTRUCTION ON THAT IS DAMAGED DURING CONSTRUCTION ON THAT IS DAMAGED DURING CONSTRUCTION ON
PIPE OR DUCTWORK THAT IS TO REMAIN. PIPE OR DUCTWORK THAT IS TO REMAIN. PIPE OR DUCTWORK THAT IS TO REMAIN. PIPE OR DUCTWORK THAT IS TO REMAIN.
PRIOR TO DEMOLITION OF ANY EQUIPMENT WORK PRIOR TO DEMOLITION OF ANY EQUIPMENT WORK PRIOR TO DEMOLITION OF ANY EQUIPMENT WORK PRIOR TO DEMOLITION OF ANY EQUIPMENT WORK
WITH ELECTRICAL CONTRACTOR AND CONTROLS WITH ELECTRICAL CONTRACTOR AND CONTROLS WITH ELECTRICAL CONTRACTOR AND CONTROLS WITH ELECTRICAL CONTRACTOR AND CONTROLS
CONTRACTOR TO MAKE CERTAIN POWER AND CONTRACTOR TO MAKE CERTAIN POWER AND CONTRACTOR TO MAKE CERTAIN POWER AND CONTRACTOR TO MAKE CERTAIN POWER AND
CONTROLS ARE PROPERLY DISCONNECTED AND CONTROLS ARE PROPERLY DISCONNECTED AND CONTROLS ARE PROPERLY DISCONNECTED AND CONTROLS ARE PROPERLY DISCONNECTED AND
TERMINATED.TERMINATED.TERMINATED.TERMINATED.
B.B.B.B.
C.C.C.C.
D.D.D.D.
E.E.E.E.
F.F.F.F.
G.G.G.G.
H.H.H.H.
I.I.I.I.
J.J.J.J.
K.K.K.K.
L.L.L.L.
16161616151515151414141413131313121212121111111110101010999988887777
KKKK
HHHH
FFFF
DDDD
BBBB
AAAA
GGGG
JJJJ
EEEE
CCCC
(E)1" SHWS/R
1111
1111
1111
(E)1" SHWS/R
1111
MD402MD402MD402MD402
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
Level 00 Area
B Mechanical
Piping
Demolition
Plan
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
KEY PLAN
A
B
ao^tfkd=klqbp
0000555510101010 10101010 20202020
NOTE
#DESCRIPTION
1111 REMOVE PORTION OF EXISTING SNOWMELTREMOVE PORTION OF EXISTING SNOWMELTREMOVE PORTION OF EXISTING SNOWMELTREMOVE PORTION OF EXISTING SNOWMELT
HEATING WATER SUPPLY/RETURN PIPING ASHEATING WATER SUPPLY/RETURN PIPING ASHEATING WATER SUPPLY/RETURN PIPING ASHEATING WATER SUPPLY/RETURN PIPING AS
SHOWN. FIELD VERIFY EXISTING PIPE ROUTING.SHOWN. FIELD VERIFY EXISTING PIPE ROUTING.SHOWN. FIELD VERIFY EXISTING PIPE ROUTING.SHOWN. FIELD VERIFY EXISTING PIPE ROUTING.
SCALE:SCALE:SCALE:SCALE:MD110bMD110bMD110bMD110b 1/8" = 1'1/8" = 1'1/8" = 1'1/8" = 1'----0"0"0"0"
ibsbi=MM=^ob^=_=jb`e^kf`^i=mfmfkd=abjlifqflk=mi^k1111
1111
GGGG
JJJJ
LLLL
MMMM
NNNN
PPPP
QQQQ
EEEE
CCCC
2222 3333 4444 5555
1111
1111
1111
1111
22222222 2222
2222
2222
2222
1111
1111
1111
1111
1111
1111
2222 2222
2222
1111
1111
2222
2222
2222
2222
2222
2222
2222
2222
2222
2222
2222
2222
2222
2222
3333
4444
6666
7777
8888
2222
2222
2222
3333
4444
4444
4444
3333
3333
3333
4444
3333
3333
3333
4444
7777
7777
7777
7777
7777
6666
7777
7777
7777
3333
3333
4444
4444
3333
5555
8888
8888
4444
3333
8888
3333
4444
5555
3333
2222
2222
3333
4444
5555
4444
3333
5555
8888
3333
4444
3333
4444
4444
3333
3333
3333
4444
3333
3333
5555 4444
3333
3333
3333
33333333
4444
4444
4444
4444
9999
9999
4444
4444
4444
dbkbo^i=klqbp
A.A.A.A.FIELD VERIFY EXACT LOCATIONS OF EXISTING FIELD VERIFY EXACT LOCATIONS OF EXISTING FIELD VERIFY EXACT LOCATIONS OF EXISTING FIELD VERIFY EXACT LOCATIONS OF EXISTING
PIPING, DUCTWORK, EQUIPMENT, ETC. PIPING, DUCTWORK, EQUIPMENT, ETC. PIPING, DUCTWORK, EQUIPMENT, ETC. PIPING, DUCTWORK, EQUIPMENT, ETC.
DEMOLITION FLOOR PLANS HAVE BEEN CREATED DEMOLITION FLOOR PLANS HAVE BEEN CREATED DEMOLITION FLOOR PLANS HAVE BEEN CREATED DEMOLITION FLOOR PLANS HAVE BEEN CREATED
USING AVAILABLE RECORD DRAWINGS. USING AVAILABLE RECORD DRAWINGS. USING AVAILABLE RECORD DRAWINGS. USING AVAILABLE RECORD DRAWINGS.
CONTRACTOR SHALL BE RESPONSIBLE FOR CONTRACTOR SHALL BE RESPONSIBLE FOR CONTRACTOR SHALL BE RESPONSIBLE FOR CONTRACTOR SHALL BE RESPONSIBLE FOR
VERIFYING EXACT ROUTING OF ALL PIPING, VERIFYING EXACT ROUTING OF ALL PIPING, VERIFYING EXACT ROUTING OF ALL PIPING, VERIFYING EXACT ROUTING OF ALL PIPING,
DUCTWORK, ETC. DURING CONSTRUCTION. DUCTWORK, ETC. DURING CONSTRUCTION. DUCTWORK, ETC. DURING CONSTRUCTION. DUCTWORK, ETC. DURING CONSTRUCTION.
DEMOLITION OF EXISTING MECHANICAL AND DEMOLITION OF EXISTING MECHANICAL AND DEMOLITION OF EXISTING MECHANICAL AND DEMOLITION OF EXISTING MECHANICAL AND
PLUMBING CONSTRUCTION SHALL BE TO THE PLUMBING CONSTRUCTION SHALL BE TO THE PLUMBING CONSTRUCTION SHALL BE TO THE PLUMBING CONSTRUCTION SHALL BE TO THE
EXTENT REQUIRED TO ACCOMMODATE THE EXTENT REQUIRED TO ACCOMMODATE THE EXTENT REQUIRED TO ACCOMMODATE THE EXTENT REQUIRED TO ACCOMMODATE THE
RENOVATION AND THE ADDITION OF NEW WORK. RENOVATION AND THE ADDITION OF NEW WORK. RENOVATION AND THE ADDITION OF NEW WORK. RENOVATION AND THE ADDITION OF NEW WORK.
REFERENCE ARCHITECTURAL DEMOLITION REFERENCE ARCHITECTURAL DEMOLITION REFERENCE ARCHITECTURAL DEMOLITION REFERENCE ARCHITECTURAL DEMOLITION
DRAWINGS TO COORDINATE AND VERIFY THE DRAWINGS TO COORDINATE AND VERIFY THE DRAWINGS TO COORDINATE AND VERIFY THE DRAWINGS TO COORDINATE AND VERIFY THE
EXTENT OF THE DEMOLITION WORK REQUIRED. EXTENT OF THE DEMOLITION WORK REQUIRED. EXTENT OF THE DEMOLITION WORK REQUIRED. EXTENT OF THE DEMOLITION WORK REQUIRED.
ALL PIPING, DUCTWORK, ETC. TO REMAIN SHALL BE ALL PIPING, DUCTWORK, ETC. TO REMAIN SHALL BE ALL PIPING, DUCTWORK, ETC. TO REMAIN SHALL BE ALL PIPING, DUCTWORK, ETC. TO REMAIN SHALL BE
PROTECTED THROUGHOUT THE CONSTRUCTION PROTECTED THROUGHOUT THE CONSTRUCTION PROTECTED THROUGHOUT THE CONSTRUCTION PROTECTED THROUGHOUT THE CONSTRUCTION
PERIOD. PERIOD. PERIOD. PERIOD.
PROVIDE AND INSTALL CAPS ON EXISTING MAIN PROVIDE AND INSTALL CAPS ON EXISTING MAIN PROVIDE AND INSTALL CAPS ON EXISTING MAIN PROVIDE AND INSTALL CAPS ON EXISTING MAIN
BRANCH BEING REMOVED. REFERENCE BRANCH BEING REMOVED. REFERENCE BRANCH BEING REMOVED. REFERENCE BRANCH BEING REMOVED. REFERENCE
ARCHITECTURAL FOR PATCHWORK. ARCHITECTURAL FOR PATCHWORK. ARCHITECTURAL FOR PATCHWORK. ARCHITECTURAL FOR PATCHWORK.
INDICATED DEMOLITION OF PIPING INCLUDES, BUT INDICATED DEMOLITION OF PIPING INCLUDES, BUT INDICATED DEMOLITION OF PIPING INCLUDES, BUT INDICATED DEMOLITION OF PIPING INCLUDES, BUT
IS NOT LIMITED TO, THE REMOVAL OF PIPING, IS NOT LIMITED TO, THE REMOVAL OF PIPING, IS NOT LIMITED TO, THE REMOVAL OF PIPING, IS NOT LIMITED TO, THE REMOVAL OF PIPING,
FITTINGS, VALVES, HANGERS, SUPPORTS, FITTINGS, VALVES, HANGERS, SUPPORTS, FITTINGS, VALVES, HANGERS, SUPPORTS, FITTINGS, VALVES, HANGERS, SUPPORTS,
INSULATION, ETC. UNLESS NOTED OTHERWISE. INSULATION, ETC. UNLESS NOTED OTHERWISE. INSULATION, ETC. UNLESS NOTED OTHERWISE. INSULATION, ETC. UNLESS NOTED OTHERWISE.
INDICATED DEMOLITION OF MECHANICAL INDICATED DEMOLITION OF MECHANICAL INDICATED DEMOLITION OF MECHANICAL INDICATED DEMOLITION OF MECHANICAL
EQUIPMENT INCLUDES, BUT IS NOT LIMITED TO, EQUIPMENT INCLUDES, BUT IS NOT LIMITED TO, EQUIPMENT INCLUDES, BUT IS NOT LIMITED TO, EQUIPMENT INCLUDES, BUT IS NOT LIMITED TO,
THE REMOVAL OF EQUIPMENT, PIPING, VALVES, THE REMOVAL OF EQUIPMENT, PIPING, VALVES, THE REMOVAL OF EQUIPMENT, PIPING, VALVES, THE REMOVAL OF EQUIPMENT, PIPING, VALVES,
INSULATION, SEISMIC BRACING, CONTROLS, INSULATION, SEISMIC BRACING, CONTROLS, INSULATION, SEISMIC BRACING, CONTROLS, INSULATION, SEISMIC BRACING, CONTROLS,
ELECTRICAL, ETC. UNLESS NOTED OTHERWISE. ELECTRICAL, ETC. UNLESS NOTED OTHERWISE. ELECTRICAL, ETC. UNLESS NOTED OTHERWISE. ELECTRICAL, ETC. UNLESS NOTED OTHERWISE.
CONTRACTOR SHALL BE RESPONSIBLE FOR CONTRACTOR SHALL BE RESPONSIBLE FOR CONTRACTOR SHALL BE RESPONSIBLE FOR CONTRACTOR SHALL BE RESPONSIBLE FOR
PATCHING AND REPAIRING ANY DAMAGE CAUSED PATCHING AND REPAIRING ANY DAMAGE CAUSED PATCHING AND REPAIRING ANY DAMAGE CAUSED PATCHING AND REPAIRING ANY DAMAGE CAUSED
BY HIS / HER PERSONNEL TO EXISTING THAT IS TO BY HIS / HER PERSONNEL TO EXISTING THAT IS TO BY HIS / HER PERSONNEL TO EXISTING THAT IS TO BY HIS / HER PERSONNEL TO EXISTING THAT IS TO
REMAIN OR TO NEWLY INSTALLED BUILDING REMAIN OR TO NEWLY INSTALLED BUILDING REMAIN OR TO NEWLY INSTALLED BUILDING REMAIN OR TO NEWLY INSTALLED BUILDING
COMPONENTS. COMPONENTS. COMPONENTS. COMPONENTS.
PATCH AND SEAL ALL ABANDONED OPENINGS PATCH AND SEAL ALL ABANDONED OPENINGS PATCH AND SEAL ALL ABANDONED OPENINGS PATCH AND SEAL ALL ABANDONED OPENINGS
THROUGH WALLS AND FLOORS. MATCH EXISTING THROUGH WALLS AND FLOORS. MATCH EXISTING THROUGH WALLS AND FLOORS. MATCH EXISTING THROUGH WALLS AND FLOORS. MATCH EXISTING
SURROUNDING FINISH. SURROUNDING FINISH. SURROUNDING FINISH. SURROUNDING FINISH.
CONTRACTOR SHALL REPLACE ANY INSULATION CONTRACTOR SHALL REPLACE ANY INSULATION CONTRACTOR SHALL REPLACE ANY INSULATION CONTRACTOR SHALL REPLACE ANY INSULATION
THAT IS DAMAGED DURING CONSTRUCTION ON THAT IS DAMAGED DURING CONSTRUCTION ON THAT IS DAMAGED DURING CONSTRUCTION ON THAT IS DAMAGED DURING CONSTRUCTION ON
PIPE OR DUCTWORK THAT IS TO REMAIN. PIPE OR DUCTWORK THAT IS TO REMAIN. PIPE OR DUCTWORK THAT IS TO REMAIN. PIPE OR DUCTWORK THAT IS TO REMAIN.
PRIOR TO DEMOLITION OF ANY EQUIPMENT WORK PRIOR TO DEMOLITION OF ANY EQUIPMENT WORK PRIOR TO DEMOLITION OF ANY EQUIPMENT WORK PRIOR TO DEMOLITION OF ANY EQUIPMENT WORK
WITH ELECTRICAL CONTRACTOR AND CONTROLS WITH ELECTRICAL CONTRACTOR AND CONTROLS WITH ELECTRICAL CONTRACTOR AND CONTROLS WITH ELECTRICAL CONTRACTOR AND CONTROLS
CONTRACTOR TO MAKE CERTAIN POWER AND CONTRACTOR TO MAKE CERTAIN POWER AND CONTRACTOR TO MAKE CERTAIN POWER AND CONTRACTOR TO MAKE CERTAIN POWER AND
CONTROLS ARE PROPERLY DISCONNECTED AND CONTROLS ARE PROPERLY DISCONNECTED AND CONTROLS ARE PROPERLY DISCONNECTED AND CONTROLS ARE PROPERLY DISCONNECTED AND
TERMINATED.TERMINATED.TERMINATED.TERMINATED.
B.B.B.B.
C.C.C.C.
D.D.D.D.
E.E.E.E.
F.F.F.F.
G.G.G.G.
H.H.H.H.
I.I.I.I.
J.J.J.J.
K.K.K.K.
L.L.L.L.
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
Level 01 Area
A Mechanical
Piping
Demolition
Plan
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
KEY PLAN
A
B
ao^tfkd=klqbp
0000555510101010 10101010 20202020
SCALE:SCALE:SCALE:SCALE:MD111aMD111aMD111aMD111a 1/8" = 1'1/8" = 1'1/8" = 1'1/8" = 1'----0"0"0"0"
ibsbi=N=^ob^=^=jb`e^kf`^i=mfmfkd=abjlifqflk=mi^k1111
NOTE
#DESCRIPTION
1111 REMOVE EXISTING BASEBOARD HEATERREMOVE EXISTING BASEBOARD HEATERREMOVE EXISTING BASEBOARD HEATERREMOVE EXISTING BASEBOARD HEATER
INCLUDING ALL VALVES, STRAINERS, ETC.INCLUDING ALL VALVES, STRAINERS, ETC.INCLUDING ALL VALVES, STRAINERS, ETC.INCLUDING ALL VALVES, STRAINERS, ETC.
2222 REMOVE EXISTING HWS/R PIPING SERVINGREMOVE EXISTING HWS/R PIPING SERVINGREMOVE EXISTING HWS/R PIPING SERVINGREMOVE EXISTING HWS/R PIPING SERVING
BASEBOARD HEATERS BACK TO THE CHASE ASBASEBOARD HEATERS BACK TO THE CHASE ASBASEBOARD HEATERS BACK TO THE CHASE ASBASEBOARD HEATERS BACK TO THE CHASE AS
SHOWN.SHOWN.SHOWN.SHOWN.
3333 REMOVE EXISTING VAV REHEAT BOX ANDREMOVE EXISTING VAV REHEAT BOX ANDREMOVE EXISTING VAV REHEAT BOX ANDREMOVE EXISTING VAV REHEAT BOX AND
ASSOCIATED REHEAT COIL, ISOLATION VALVES,ASSOCIATED REHEAT COIL, ISOLATION VALVES,ASSOCIATED REHEAT COIL, ISOLATION VALVES,ASSOCIATED REHEAT COIL, ISOLATION VALVES,
STRAINER, CONTROL VALVE, BALANCE VALVE,STRAINER, CONTROL VALVE, BALANCE VALVE,STRAINER, CONTROL VALVE, BALANCE VALVE,STRAINER, CONTROL VALVE, BALANCE VALVE,
CONTROLS, ETC. COMPLETE.CONTROLS, ETC. COMPLETE.CONTROLS, ETC. COMPLETE.CONTROLS, ETC. COMPLETE.
4444 REMOVE PORTION OF EXISTING HEATING WATERREMOVE PORTION OF EXISTING HEATING WATERREMOVE PORTION OF EXISTING HEATING WATERREMOVE PORTION OF EXISTING HEATING WATER
SUPPLY/RETURN PIPING AS SHOWN.SUPPLY/RETURN PIPING AS SHOWN.SUPPLY/RETURN PIPING AS SHOWN.SUPPLY/RETURN PIPING AS SHOWN.
5555 CAP HEATING WATER SUPPLY/RETURN PIPING ATCAP HEATING WATER SUPPLY/RETURN PIPING ATCAP HEATING WATER SUPPLY/RETURN PIPING ATCAP HEATING WATER SUPPLY/RETURN PIPING AT
MAIN.MAIN.MAIN.MAIN.
6666 REMOVE EXISTING CABINET HEATERANDREMOVE EXISTING CABINET HEATERANDREMOVE EXISTING CABINET HEATERANDREMOVE EXISTING CABINET HEATERAND
ASSOCIATED ISOLATION VALVES, STRAINER,ASSOCIATED ISOLATION VALVES, STRAINER,ASSOCIATED ISOLATION VALVES, STRAINER,ASSOCIATED ISOLATION VALVES, STRAINER,
CONTROL VALVE, BALANCE VALVE, CONTROLS,CONTROL VALVE, BALANCE VALVE, CONTROLS,CONTROL VALVE, BALANCE VALVE, CONTROLS,CONTROL VALVE, BALANCE VALVE, CONTROLS,
ETC. COMPLETE.ETC. COMPLETE.ETC. COMPLETE.ETC. COMPLETE.
7777 REMOVE PORTION OF EXISTING HWS/R PIPINGREMOVE PORTION OF EXISTING HWS/R PIPINGREMOVE PORTION OF EXISTING HWS/R PIPINGREMOVE PORTION OF EXISTING HWS/R PIPING
SERVING BASEBOARD HEATER AS SHOWN.SERVING BASEBOARD HEATER AS SHOWN.SERVING BASEBOARD HEATER AS SHOWN.SERVING BASEBOARD HEATER AS SHOWN.
8888 PORTION OF EXISTING HWS/R PIPING SERVINGPORTION OF EXISTING HWS/R PIPING SERVINGPORTION OF EXISTING HWS/R PIPING SERVINGPORTION OF EXISTING HWS/R PIPING SERVING
BASEBOARD HEATERS TO REMAIN AND BEBASEBOARD HEATERS TO REMAIN AND BEBASEBOARD HEATERS TO REMAIN AND BEBASEBOARD HEATERS TO REMAIN AND BE
REPURPOSED AS CHILLED WATER SUPPLY ANDREPURPOSED AS CHILLED WATER SUPPLY ANDREPURPOSED AS CHILLED WATER SUPPLY ANDREPURPOSED AS CHILLED WATER SUPPLY AND
RETURN PIPING. FIELD VERIFY EXISTING PIPERETURN PIPING. FIELD VERIFY EXISTING PIPERETURN PIPING. FIELD VERIFY EXISTING PIPERETURN PIPING. FIELD VERIFY EXISTING PIPE
ROUTING.ROUTING.ROUTING.ROUTING.
9999 REMOVE EXISTING HWS/R RISER PIPING IN CHASEREMOVE EXISTING HWS/R RISER PIPING IN CHASEREMOVE EXISTING HWS/R RISER PIPING IN CHASEREMOVE EXISTING HWS/R RISER PIPING IN CHASE
AND PORTION OF MAIN PIPING AS SHOWNAND PORTION OF MAIN PIPING AS SHOWNAND PORTION OF MAIN PIPING AS SHOWNAND PORTION OF MAIN PIPING AS SHOWN
INCLUDING THE BALANCE AND GATE VALVE.INCLUDING THE BALANCE AND GATE VALVE.INCLUDING THE BALANCE AND GATE VALVE.INCLUDING THE BALANCE AND GATE VALVE.
16161616151515151414141413131313121212121111111110101010999988887777
KKKK
HHHH
FFFF
DDDD
BBBB
AAAA
1111
MD402MD402MD402MD402
1111
2222
3333 2222
2222
33332222
1111
1111
33332222
2222 1111
1111
1111
1111
1111
1111
1111
1111
1111
1111
1111
1111
1111
1111
3333
2222
2222
33332222
33332222
2222
2222
2222
2222
2222
2222
2222
2222
2222
33332222
2222
dbkbo^i=klqbp
A.A.A.A.FIELD VERIFY EXACT LOCATIONS OF EXISTING FIELD VERIFY EXACT LOCATIONS OF EXISTING FIELD VERIFY EXACT LOCATIONS OF EXISTING FIELD VERIFY EXACT LOCATIONS OF EXISTING
PIPING, DUCTWORK, EQUIPMENT, ETC. PIPING, DUCTWORK, EQUIPMENT, ETC. PIPING, DUCTWORK, EQUIPMENT, ETC. PIPING, DUCTWORK, EQUIPMENT, ETC.
DEMOLITION FLOOR PLANS HAVE BEEN CREATED DEMOLITION FLOOR PLANS HAVE BEEN CREATED DEMOLITION FLOOR PLANS HAVE BEEN CREATED DEMOLITION FLOOR PLANS HAVE BEEN CREATED
USING AVAILABLE RECORD DRAWINGS. USING AVAILABLE RECORD DRAWINGS. USING AVAILABLE RECORD DRAWINGS. USING AVAILABLE RECORD DRAWINGS.
CONTRACTOR SHALL BE RESPONSIBLE FOR CONTRACTOR SHALL BE RESPONSIBLE FOR CONTRACTOR SHALL BE RESPONSIBLE FOR CONTRACTOR SHALL BE RESPONSIBLE FOR
VERIFYING EXACT ROUTING OF ALL PIPING, VERIFYING EXACT ROUTING OF ALL PIPING, VERIFYING EXACT ROUTING OF ALL PIPING, VERIFYING EXACT ROUTING OF ALL PIPING,
DUCTWORK, ETC. DURING CONSTRUCTION. DUCTWORK, ETC. DURING CONSTRUCTION. DUCTWORK, ETC. DURING CONSTRUCTION. DUCTWORK, ETC. DURING CONSTRUCTION.
DEMOLITION OF EXISTING MECHANICAL AND DEMOLITION OF EXISTING MECHANICAL AND DEMOLITION OF EXISTING MECHANICAL AND DEMOLITION OF EXISTING MECHANICAL AND
PLUMBING CONSTRUCTION SHALL BE TO THE PLUMBING CONSTRUCTION SHALL BE TO THE PLUMBING CONSTRUCTION SHALL BE TO THE PLUMBING CONSTRUCTION SHALL BE TO THE
EXTENT REQUIRED TO ACCOMMODATE THE EXTENT REQUIRED TO ACCOMMODATE THE EXTENT REQUIRED TO ACCOMMODATE THE EXTENT REQUIRED TO ACCOMMODATE THE
RENOVATION AND THE ADDITION OF NEW WORK. RENOVATION AND THE ADDITION OF NEW WORK. RENOVATION AND THE ADDITION OF NEW WORK. RENOVATION AND THE ADDITION OF NEW WORK.
REFERENCE ARCHITECTURAL DEMOLITION REFERENCE ARCHITECTURAL DEMOLITION REFERENCE ARCHITECTURAL DEMOLITION REFERENCE ARCHITECTURAL DEMOLITION
DRAWINGS TO COORDINATE AND VERIFY THE DRAWINGS TO COORDINATE AND VERIFY THE DRAWINGS TO COORDINATE AND VERIFY THE DRAWINGS TO COORDINATE AND VERIFY THE
EXTENT OF THE DEMOLITION WORK REQUIRED. EXTENT OF THE DEMOLITION WORK REQUIRED. EXTENT OF THE DEMOLITION WORK REQUIRED. EXTENT OF THE DEMOLITION WORK REQUIRED.
ALL PIPING, DUCTWORK, ETC. TO REMAIN SHALL BE ALL PIPING, DUCTWORK, ETC. TO REMAIN SHALL BE ALL PIPING, DUCTWORK, ETC. TO REMAIN SHALL BE ALL PIPING, DUCTWORK, ETC. TO REMAIN SHALL BE
PROTECTED THROUGHOUT THE CONSTRUCTION PROTECTED THROUGHOUT THE CONSTRUCTION PROTECTED THROUGHOUT THE CONSTRUCTION PROTECTED THROUGHOUT THE CONSTRUCTION
PERIOD. PERIOD. PERIOD. PERIOD.
PROVIDE AND INSTALL CAPS ON EXISTING MAIN PROVIDE AND INSTALL CAPS ON EXISTING MAIN PROVIDE AND INSTALL CAPS ON EXISTING MAIN PROVIDE AND INSTALL CAPS ON EXISTING MAIN
BRANCH BEING REMOVED. REFERENCE BRANCH BEING REMOVED. REFERENCE BRANCH BEING REMOVED. REFERENCE BRANCH BEING REMOVED. REFERENCE
ARCHITECTURAL FOR PATCHWORK. ARCHITECTURAL FOR PATCHWORK. ARCHITECTURAL FOR PATCHWORK. ARCHITECTURAL FOR PATCHWORK.
INDICATED DEMOLITION OF PIPING INCLUDES, BUT INDICATED DEMOLITION OF PIPING INCLUDES, BUT INDICATED DEMOLITION OF PIPING INCLUDES, BUT INDICATED DEMOLITION OF PIPING INCLUDES, BUT
IS NOT LIMITED TO, THE REMOVAL OF PIPING, IS NOT LIMITED TO, THE REMOVAL OF PIPING, IS NOT LIMITED TO, THE REMOVAL OF PIPING, IS NOT LIMITED TO, THE REMOVAL OF PIPING,
FITTINGS, VALVES, HANGERS, SUPPORTS, FITTINGS, VALVES, HANGERS, SUPPORTS, FITTINGS, VALVES, HANGERS, SUPPORTS, FITTINGS, VALVES, HANGERS, SUPPORTS,
INSULATION, ETC. UNLESS NOTED OTHERWISE. INSULATION, ETC. UNLESS NOTED OTHERWISE. INSULATION, ETC. UNLESS NOTED OTHERWISE. INSULATION, ETC. UNLESS NOTED OTHERWISE.
INDICATED DEMOLITION OF MECHANICAL INDICATED DEMOLITION OF MECHANICAL INDICATED DEMOLITION OF MECHANICAL INDICATED DEMOLITION OF MECHANICAL
EQUIPMENT INCLUDES, BUT IS NOT LIMITED TO, EQUIPMENT INCLUDES, BUT IS NOT LIMITED TO, EQUIPMENT INCLUDES, BUT IS NOT LIMITED TO, EQUIPMENT INCLUDES, BUT IS NOT LIMITED TO,
THE REMOVAL OF EQUIPMENT, PIPING, VALVES, THE REMOVAL OF EQUIPMENT, PIPING, VALVES, THE REMOVAL OF EQUIPMENT, PIPING, VALVES, THE REMOVAL OF EQUIPMENT, PIPING, VALVES,
INSULATION, SEISMIC BRACING, CONTROLS, INSULATION, SEISMIC BRACING, CONTROLS, INSULATION, SEISMIC BRACING, CONTROLS, INSULATION, SEISMIC BRACING, CONTROLS,
ELECTRICAL, ETC. UNLESS NOTED OTHERWISE. ELECTRICAL, ETC. UNLESS NOTED OTHERWISE. ELECTRICAL, ETC. UNLESS NOTED OTHERWISE. ELECTRICAL, ETC. UNLESS NOTED OTHERWISE.
CONTRACTOR SHALL BE RESPONSIBLE FOR CONTRACTOR SHALL BE RESPONSIBLE FOR CONTRACTOR SHALL BE RESPONSIBLE FOR CONTRACTOR SHALL BE RESPONSIBLE FOR
PATCHING AND REPAIRING ANY DAMAGE CAUSED PATCHING AND REPAIRING ANY DAMAGE CAUSED PATCHING AND REPAIRING ANY DAMAGE CAUSED PATCHING AND REPAIRING ANY DAMAGE CAUSED
BY HIS / HER PERSONNEL TO EXISTING THAT IS TO BY HIS / HER PERSONNEL TO EXISTING THAT IS TO BY HIS / HER PERSONNEL TO EXISTING THAT IS TO BY HIS / HER PERSONNEL TO EXISTING THAT IS TO
REMAIN OR TO NEWLY INSTALLED BUILDING REMAIN OR TO NEWLY INSTALLED BUILDING REMAIN OR TO NEWLY INSTALLED BUILDING REMAIN OR TO NEWLY INSTALLED BUILDING
COMPONENTS. COMPONENTS. COMPONENTS. COMPONENTS.
PATCH AND SEAL ALL ABANDONED OPENINGS PATCH AND SEAL ALL ABANDONED OPENINGS PATCH AND SEAL ALL ABANDONED OPENINGS PATCH AND SEAL ALL ABANDONED OPENINGS
THROUGH WALLS AND FLOORS. MATCH EXISTING THROUGH WALLS AND FLOORS. MATCH EXISTING THROUGH WALLS AND FLOORS. MATCH EXISTING THROUGH WALLS AND FLOORS. MATCH EXISTING
SURROUNDING FINISH. SURROUNDING FINISH. SURROUNDING FINISH. SURROUNDING FINISH.
CONTRACTOR SHALL REPLACE ANY INSULATION CONTRACTOR SHALL REPLACE ANY INSULATION CONTRACTOR SHALL REPLACE ANY INSULATION CONTRACTOR SHALL REPLACE ANY INSULATION
THAT IS DAMAGED DURING CONSTRUCTION ON THAT IS DAMAGED DURING CONSTRUCTION ON THAT IS DAMAGED DURING CONSTRUCTION ON THAT IS DAMAGED DURING CONSTRUCTION ON
PIPE OR DUCTWORK THAT IS TO REMAIN. PIPE OR DUCTWORK THAT IS TO REMAIN. PIPE OR DUCTWORK THAT IS TO REMAIN. PIPE OR DUCTWORK THAT IS TO REMAIN.
PRIOR TO DEMOLITION OF ANY EQUIPMENT WORK PRIOR TO DEMOLITION OF ANY EQUIPMENT WORK PRIOR TO DEMOLITION OF ANY EQUIPMENT WORK PRIOR TO DEMOLITION OF ANY EQUIPMENT WORK
WITH ELECTRICAL CONTRACTOR AND CONTROLS WITH ELECTRICAL CONTRACTOR AND CONTROLS WITH ELECTRICAL CONTRACTOR AND CONTROLS WITH ELECTRICAL CONTRACTOR AND CONTROLS
CONTRACTOR TO MAKE CERTAIN POWER AND CONTRACTOR TO MAKE CERTAIN POWER AND CONTRACTOR TO MAKE CERTAIN POWER AND CONTRACTOR TO MAKE CERTAIN POWER AND
CONTROLS ARE PROPERLY DISCONNECTED AND CONTROLS ARE PROPERLY DISCONNECTED AND CONTROLS ARE PROPERLY DISCONNECTED AND CONTROLS ARE PROPERLY DISCONNECTED AND
TERMINATED.TERMINATED.TERMINATED.TERMINATED.
B.B.B.B.
C.C.C.C.
D.D.D.D.
E.E.E.E.
F.F.F.F.
G.G.G.G.
H.H.H.H.
I.I.I.I.
J.J.J.J.
K.K.K.K.
L.L.L.L.
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
Level 01 Area
B Mechanical
Piping
Demolition
Plan
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
KEY PLAN
A
B
ao^tfkd=klqbp
0000555510101010 10101010 20202020
SCALE:SCALE:SCALE:SCALE:MD111bMD111bMD111bMD111b 1/8" = 1'1/8" = 1'1/8" = 1'1/8" = 1'----0"0"0"0"
ibsbi=N=^ob^=_=jb`e^kf`^i=mfmfkd=abjlifqflk=mi^k1111
NOTE
#DESCRIPTION
1111 REMOVE EXISTING VAV REHEAT BOX ANDREMOVE EXISTING VAV REHEAT BOX ANDREMOVE EXISTING VAV REHEAT BOX ANDREMOVE EXISTING VAV REHEAT BOX AND
ASSOCIATED REHEAT COIL, ISOLATION VALVES,ASSOCIATED REHEAT COIL, ISOLATION VALVES,ASSOCIATED REHEAT COIL, ISOLATION VALVES,ASSOCIATED REHEAT COIL, ISOLATION VALVES,
STRAINER, CONTROL VALVE, BALANCE VALVE,STRAINER, CONTROL VALVE, BALANCE VALVE,STRAINER, CONTROL VALVE, BALANCE VALVE,STRAINER, CONTROL VALVE, BALANCE VALVE,
CONTROLS, ETC. COMPLETE.CONTROLS, ETC. COMPLETE.CONTROLS, ETC. COMPLETE.CONTROLS, ETC. COMPLETE.
2222 REMOVE PORTION OF EXISTING HEATING WATERREMOVE PORTION OF EXISTING HEATING WATERREMOVE PORTION OF EXISTING HEATING WATERREMOVE PORTION OF EXISTING HEATING WATER
SUPPLY/RETURN PIPING AS SHOWN.SUPPLY/RETURN PIPING AS SHOWN.SUPPLY/RETURN PIPING AS SHOWN.SUPPLY/RETURN PIPING AS SHOWN.
3333 CAP HEATING WATER SUPPLY/RETURN AT MAIN.CAP HEATING WATER SUPPLY/RETURN AT MAIN.CAP HEATING WATER SUPPLY/RETURN AT MAIN.CAP HEATING WATER SUPPLY/RETURN AT MAIN.
1111
GGGG
JJJJ
LLLL
MMMM
NNNN
PPPP
QQQQ
EEEE
CCCC
2222 3333 4444 5555
1111
1111
1111
1111
1111
2222
2222
2222
1111
1111
2222
1111
1111
1111
1111
1111
1111
1111
1111
2222
2222
2222
2222
2222
2222
2222
2222
2222
3333
4444
5555
6666
7777
8888
3333
3333
3333
4444
3333
8888
2222
3333
4444
2222
7777
7777
3333
4444
5555
5555
3333
4444
2222
2222
2222
4444
4444
3333
3333
4444
3333
4444
5555
3333
4444
5555 3333
4444
4444
3333
5555
4444
3333
8888
8888
3333
4444
5555
4444
3333
4444
4444
3333
3333
5555
3333
3333
4444
4444
3333
5555
6666
6666 6666
6666
6666
6666
6666
6666
3333
4444
4444
3333
3333
4444
5555
3333
4444
3333
9999
9999
4444
5555
55554444
dbkbo^i=klqbp
A.A.A.A.FIELD VERIFY EXACT LOCATIONS OF EXISTING FIELD VERIFY EXACT LOCATIONS OF EXISTING FIELD VERIFY EXACT LOCATIONS OF EXISTING FIELD VERIFY EXACT LOCATIONS OF EXISTING
PIPING, DUCTWORK, EQUIPMENT, ETC. PIPING, DUCTWORK, EQUIPMENT, ETC. PIPING, DUCTWORK, EQUIPMENT, ETC. PIPING, DUCTWORK, EQUIPMENT, ETC.
DEMOLITION FLOOR PLANS HAVE BEEN CREATED DEMOLITION FLOOR PLANS HAVE BEEN CREATED DEMOLITION FLOOR PLANS HAVE BEEN CREATED DEMOLITION FLOOR PLANS HAVE BEEN CREATED
USING AVAILABLE RECORD DRAWINGS. USING AVAILABLE RECORD DRAWINGS. USING AVAILABLE RECORD DRAWINGS. USING AVAILABLE RECORD DRAWINGS.
CONTRACTOR SHALL BE RESPONSIBLE FOR CONTRACTOR SHALL BE RESPONSIBLE FOR CONTRACTOR SHALL BE RESPONSIBLE FOR CONTRACTOR SHALL BE RESPONSIBLE FOR
VERIFYING EXACT ROUTING OF ALL PIPING, VERIFYING EXACT ROUTING OF ALL PIPING, VERIFYING EXACT ROUTING OF ALL PIPING, VERIFYING EXACT ROUTING OF ALL PIPING,
DUCTWORK, ETC. DURING CONSTRUCTION. DUCTWORK, ETC. DURING CONSTRUCTION. DUCTWORK, ETC. DURING CONSTRUCTION. DUCTWORK, ETC. DURING CONSTRUCTION.
DEMOLITION OF EXISTING MECHANICAL AND DEMOLITION OF EXISTING MECHANICAL AND DEMOLITION OF EXISTING MECHANICAL AND DEMOLITION OF EXISTING MECHANICAL AND
PLUMBING CONSTRUCTION SHALL BE TO THE PLUMBING CONSTRUCTION SHALL BE TO THE PLUMBING CONSTRUCTION SHALL BE TO THE PLUMBING CONSTRUCTION SHALL BE TO THE
EXTENT REQUIRED TO ACCOMMODATE THE EXTENT REQUIRED TO ACCOMMODATE THE EXTENT REQUIRED TO ACCOMMODATE THE EXTENT REQUIRED TO ACCOMMODATE THE
RENOVATION AND THE ADDITION OF NEW WORK. RENOVATION AND THE ADDITION OF NEW WORK. RENOVATION AND THE ADDITION OF NEW WORK. RENOVATION AND THE ADDITION OF NEW WORK.
REFERENCE ARCHITECTURAL DEMOLITION REFERENCE ARCHITECTURAL DEMOLITION REFERENCE ARCHITECTURAL DEMOLITION REFERENCE ARCHITECTURAL DEMOLITION
DRAWINGS TO COORDINATE AND VERIFY THE DRAWINGS TO COORDINATE AND VERIFY THE DRAWINGS TO COORDINATE AND VERIFY THE DRAWINGS TO COORDINATE AND VERIFY THE
EXTENT OF THE DEMOLITION WORK REQUIRED. EXTENT OF THE DEMOLITION WORK REQUIRED. EXTENT OF THE DEMOLITION WORK REQUIRED. EXTENT OF THE DEMOLITION WORK REQUIRED.
ALL PIPING, DUCTWORK, ETC. TO REMAIN SHALL BE ALL PIPING, DUCTWORK, ETC. TO REMAIN SHALL BE ALL PIPING, DUCTWORK, ETC. TO REMAIN SHALL BE ALL PIPING, DUCTWORK, ETC. TO REMAIN SHALL BE
PROTECTED THROUGHOUT THE CONSTRUCTION PROTECTED THROUGHOUT THE CONSTRUCTION PROTECTED THROUGHOUT THE CONSTRUCTION PROTECTED THROUGHOUT THE CONSTRUCTION
PERIOD. PERIOD. PERIOD. PERIOD.
PROVIDE AND INSTALL CAPS ON EXISTING MAIN PROVIDE AND INSTALL CAPS ON EXISTING MAIN PROVIDE AND INSTALL CAPS ON EXISTING MAIN PROVIDE AND INSTALL CAPS ON EXISTING MAIN
BRANCH BEING REMOVED. REFERENCE BRANCH BEING REMOVED. REFERENCE BRANCH BEING REMOVED. REFERENCE BRANCH BEING REMOVED. REFERENCE
ARCHITECTURAL FOR PATCHWORK. ARCHITECTURAL FOR PATCHWORK. ARCHITECTURAL FOR PATCHWORK. ARCHITECTURAL FOR PATCHWORK.
INDICATED DEMOLITION OF PIPING INCLUDES, BUT INDICATED DEMOLITION OF PIPING INCLUDES, BUT INDICATED DEMOLITION OF PIPING INCLUDES, BUT INDICATED DEMOLITION OF PIPING INCLUDES, BUT
IS NOT LIMITED TO, THE REMOVAL OF PIPING, IS NOT LIMITED TO, THE REMOVAL OF PIPING, IS NOT LIMITED TO, THE REMOVAL OF PIPING, IS NOT LIMITED TO, THE REMOVAL OF PIPING,
FITTINGS, VALVES, HANGERS, SUPPORTS, FITTINGS, VALVES, HANGERS, SUPPORTS, FITTINGS, VALVES, HANGERS, SUPPORTS, FITTINGS, VALVES, HANGERS, SUPPORTS,
INSULATION, ETC. UNLESS NOTED OTHERWISE. INSULATION, ETC. UNLESS NOTED OTHERWISE. INSULATION, ETC. UNLESS NOTED OTHERWISE. INSULATION, ETC. UNLESS NOTED OTHERWISE.
INDICATED DEMOLITION OF MECHANICAL INDICATED DEMOLITION OF MECHANICAL INDICATED DEMOLITION OF MECHANICAL INDICATED DEMOLITION OF MECHANICAL
EQUIPMENT INCLUDES, BUT IS NOT LIMITED TO, EQUIPMENT INCLUDES, BUT IS NOT LIMITED TO, EQUIPMENT INCLUDES, BUT IS NOT LIMITED TO, EQUIPMENT INCLUDES, BUT IS NOT LIMITED TO,
THE REMOVAL OF EQUIPMENT, PIPING, VALVES, THE REMOVAL OF EQUIPMENT, PIPING, VALVES, THE REMOVAL OF EQUIPMENT, PIPING, VALVES, THE REMOVAL OF EQUIPMENT, PIPING, VALVES,
INSULATION, SEISMIC BRACING, CONTROLS, INSULATION, SEISMIC BRACING, CONTROLS, INSULATION, SEISMIC BRACING, CONTROLS, INSULATION, SEISMIC BRACING, CONTROLS,
ELECTRICAL, ETC. UNLESS NOTED OTHERWISE. ELECTRICAL, ETC. UNLESS NOTED OTHERWISE. ELECTRICAL, ETC. UNLESS NOTED OTHERWISE. ELECTRICAL, ETC. UNLESS NOTED OTHERWISE.
CONTRACTOR SHALL BE RESPONSIBLE FOR CONTRACTOR SHALL BE RESPONSIBLE FOR CONTRACTOR SHALL BE RESPONSIBLE FOR CONTRACTOR SHALL BE RESPONSIBLE FOR
PATCHING AND REPAIRING ANY DAMAGE CAUSED PATCHING AND REPAIRING ANY DAMAGE CAUSED PATCHING AND REPAIRING ANY DAMAGE CAUSED PATCHING AND REPAIRING ANY DAMAGE CAUSED
BY HIS / HER PERSONNEL TO EXISTING THAT IS TO BY HIS / HER PERSONNEL TO EXISTING THAT IS TO BY HIS / HER PERSONNEL TO EXISTING THAT IS TO BY HIS / HER PERSONNEL TO EXISTING THAT IS TO
REMAIN OR TO NEWLY INSTALLED BUILDING REMAIN OR TO NEWLY INSTALLED BUILDING REMAIN OR TO NEWLY INSTALLED BUILDING REMAIN OR TO NEWLY INSTALLED BUILDING
COMPONENTS. COMPONENTS. COMPONENTS. COMPONENTS.
PATCH AND SEAL ALL ABANDONED OPENINGS PATCH AND SEAL ALL ABANDONED OPENINGS PATCH AND SEAL ALL ABANDONED OPENINGS PATCH AND SEAL ALL ABANDONED OPENINGS
THROUGH WALLS AND FLOORS. MATCH EXISTING THROUGH WALLS AND FLOORS. MATCH EXISTING THROUGH WALLS AND FLOORS. MATCH EXISTING THROUGH WALLS AND FLOORS. MATCH EXISTING
SURROUNDING FINISH. SURROUNDING FINISH. SURROUNDING FINISH. SURROUNDING FINISH.
CONTRACTOR SHALL REPLACE ANY INSULATION CONTRACTOR SHALL REPLACE ANY INSULATION CONTRACTOR SHALL REPLACE ANY INSULATION CONTRACTOR SHALL REPLACE ANY INSULATION
THAT IS DAMAGED DURING CONSTRUCTION ON THAT IS DAMAGED DURING CONSTRUCTION ON THAT IS DAMAGED DURING CONSTRUCTION ON THAT IS DAMAGED DURING CONSTRUCTION ON
PIPE OR DUCTWORK THAT IS TO REMAIN. PIPE OR DUCTWORK THAT IS TO REMAIN. PIPE OR DUCTWORK THAT IS TO REMAIN. PIPE OR DUCTWORK THAT IS TO REMAIN.
PRIOR TO DEMOLITION OF ANY EQUIPMENT WORK PRIOR TO DEMOLITION OF ANY EQUIPMENT WORK PRIOR TO DEMOLITION OF ANY EQUIPMENT WORK PRIOR TO DEMOLITION OF ANY EQUIPMENT WORK
WITH ELECTRICAL CONTRACTOR AND CONTROLS WITH ELECTRICAL CONTRACTOR AND CONTROLS WITH ELECTRICAL CONTRACTOR AND CONTROLS WITH ELECTRICAL CONTRACTOR AND CONTROLS
CONTRACTOR TO MAKE CERTAIN POWER AND CONTRACTOR TO MAKE CERTAIN POWER AND CONTRACTOR TO MAKE CERTAIN POWER AND CONTRACTOR TO MAKE CERTAIN POWER AND
CONTROLS ARE PROPERLY DISCONNECTED AND CONTROLS ARE PROPERLY DISCONNECTED AND CONTROLS ARE PROPERLY DISCONNECTED AND CONTROLS ARE PROPERLY DISCONNECTED AND
TERMINATED.TERMINATED.TERMINATED.TERMINATED.
B.B.B.B.
C.C.C.C.
D.D.D.D.
E.E.E.E.
F.F.F.F.
G.G.G.G.
H.H.H.H.
I.I.I.I.
J.J.J.J.
K.K.K.K.
L.L.L.L.
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
Level 02 Area
A Mechanical
Piping
Demolition
Plan
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
KEY PLAN
A
B
ao^tfkd=klqbp
0000555510101010 10101010 20202020
SCALE:SCALE:SCALE:SCALE:MD112aMD112aMD112aMD112a 1/8" = 1'1/8" = 1'1/8" = 1'1/8" = 1'----0"0"0"0"
ibsbi=O=^ob^=^=jb`e^kf`^i=mfmfkd=abjlifqflk=mi^k1111
NOTE
#DESCRIPTION
1111 REMOVE EXISTING BASEBOARD HEATERREMOVE EXISTING BASEBOARD HEATERREMOVE EXISTING BASEBOARD HEATERREMOVE EXISTING BASEBOARD HEATER
INCLUDING ALL VALVES, STRAINERS, ETC.INCLUDING ALL VALVES, STRAINERS, ETC.INCLUDING ALL VALVES, STRAINERS, ETC.INCLUDING ALL VALVES, STRAINERS, ETC.
2222 REMOVE EXISTING HWS/R PIPING SERVINGREMOVE EXISTING HWS/R PIPING SERVINGREMOVE EXISTING HWS/R PIPING SERVINGREMOVE EXISTING HWS/R PIPING SERVING
BASEBOARD HEATERS BACK TO THE CHASE ASBASEBOARD HEATERS BACK TO THE CHASE ASBASEBOARD HEATERS BACK TO THE CHASE ASBASEBOARD HEATERS BACK TO THE CHASE AS
SHOWN.SHOWN.SHOWN.SHOWN.
3333 REMOVE EXISTING VAV REHEAT BOX ANDREMOVE EXISTING VAV REHEAT BOX ANDREMOVE EXISTING VAV REHEAT BOX ANDREMOVE EXISTING VAV REHEAT BOX AND
ASSOCIATED REHEAT COIL, ISOLATION VALVES,ASSOCIATED REHEAT COIL, ISOLATION VALVES,ASSOCIATED REHEAT COIL, ISOLATION VALVES,ASSOCIATED REHEAT COIL, ISOLATION VALVES,
STRAINER, CONTROL VALVE, BALANCE VALVE,STRAINER, CONTROL VALVE, BALANCE VALVE,STRAINER, CONTROL VALVE, BALANCE VALVE,STRAINER, CONTROL VALVE, BALANCE VALVE,
CONTROLS, ETC. COMPLETE.CONTROLS, ETC. COMPLETE.CONTROLS, ETC. COMPLETE.CONTROLS, ETC. COMPLETE.
4444 REMOVE PORTION OF EXISTING HEATING WATERREMOVE PORTION OF EXISTING HEATING WATERREMOVE PORTION OF EXISTING HEATING WATERREMOVE PORTION OF EXISTING HEATING WATER
SUPPLY/RETURN PIPING AS SHOWN.SUPPLY/RETURN PIPING AS SHOWN.SUPPLY/RETURN PIPING AS SHOWN.SUPPLY/RETURN PIPING AS SHOWN.
5555 CAP HEATING WATER SUPPLY/RETURN PIPING ATCAP HEATING WATER SUPPLY/RETURN PIPING ATCAP HEATING WATER SUPPLY/RETURN PIPING ATCAP HEATING WATER SUPPLY/RETURN PIPING AT
MAIN.MAIN.MAIN.MAIN.
6666 REMOVE PORTION OF EXISTING HWS/R PIPINGREMOVE PORTION OF EXISTING HWS/R PIPINGREMOVE PORTION OF EXISTING HWS/R PIPINGREMOVE PORTION OF EXISTING HWS/R PIPING
SERVING BASEBOARD HEATER AS SHOWN.SERVING BASEBOARD HEATER AS SHOWN.SERVING BASEBOARD HEATER AS SHOWN.SERVING BASEBOARD HEATER AS SHOWN.
7777 REMOVE EXISTING STEAM AND CONDENSATEREMOVE EXISTING STEAM AND CONDENSATEREMOVE EXISTING STEAM AND CONDENSATEREMOVE EXISTING STEAM AND CONDENSATE
PIPING AS SHOWN.PIPING AS SHOWN.PIPING AS SHOWN.PIPING AS SHOWN.
8888 PORTION OF EXISTING HWS/R PIPING SERVINGPORTION OF EXISTING HWS/R PIPING SERVINGPORTION OF EXISTING HWS/R PIPING SERVINGPORTION OF EXISTING HWS/R PIPING SERVING
BASEBOARD HEATERS TO REMAIN AND BEBASEBOARD HEATERS TO REMAIN AND BEBASEBOARD HEATERS TO REMAIN AND BEBASEBOARD HEATERS TO REMAIN AND BE
REPURPOSED AS CHILLED WATER SUPPLY ANDREPURPOSED AS CHILLED WATER SUPPLY ANDREPURPOSED AS CHILLED WATER SUPPLY ANDREPURPOSED AS CHILLED WATER SUPPLY AND
RETURN PIPING. FIELD VERIFY EXISTING PIPERETURN PIPING. FIELD VERIFY EXISTING PIPERETURN PIPING. FIELD VERIFY EXISTING PIPERETURN PIPING. FIELD VERIFY EXISTING PIPE
ROUTING.ROUTING.ROUTING.ROUTING.
9999 REMOVE EXISTING HWS/R RISER PIPING IN CHASEREMOVE EXISTING HWS/R RISER PIPING IN CHASEREMOVE EXISTING HWS/R RISER PIPING IN CHASEREMOVE EXISTING HWS/R RISER PIPING IN CHASE
AND PORTION OF MAIN PIPING AS SHOWNAND PORTION OF MAIN PIPING AS SHOWNAND PORTION OF MAIN PIPING AS SHOWNAND PORTION OF MAIN PIPING AS SHOWN
INCLUDING THE BALANCE AND GATE VALVE.INCLUDING THE BALANCE AND GATE VALVE.INCLUDING THE BALANCE AND GATE VALVE.INCLUDING THE BALANCE AND GATE VALVE.
16161616151515151414141413131313121212121111111110101010999988887777
KKKK
HHHH
FFFF
DDDD
BBBB
AAAA
1111
2222
3333
4444
4444
4444
4444
1111
2222 2222
1111
1111
1111
1111 1111
1111
11111111
1111
1111
1111
1111
1111
1111
1111
1111
1111
11111111111111111111
1111 1111
1111
1111
1111
1111
2222
2222
2222
3333 3333
2222
3333
3333
2222 2222
3333
3333 3333
3333
2222
2222
2222
2222
3333 3333
2222
2222
3333
2222
3333
2222
33332222
3333
2222
22223333
2222
22222222
2222
dbkbo^i=klqbp
A.A.A.A.FIELD VERIFY EXACT LOCATIONS OF EXISTING FIELD VERIFY EXACT LOCATIONS OF EXISTING FIELD VERIFY EXACT LOCATIONS OF EXISTING FIELD VERIFY EXACT LOCATIONS OF EXISTING
PIPING, DUCTWORK, EQUIPMENT, ETC. PIPING, DUCTWORK, EQUIPMENT, ETC. PIPING, DUCTWORK, EQUIPMENT, ETC. PIPING, DUCTWORK, EQUIPMENT, ETC.
DEMOLITION FLOOR PLANS HAVE BEEN CREATED DEMOLITION FLOOR PLANS HAVE BEEN CREATED DEMOLITION FLOOR PLANS HAVE BEEN CREATED DEMOLITION FLOOR PLANS HAVE BEEN CREATED
USING AVAILABLE RECORD DRAWINGS. USING AVAILABLE RECORD DRAWINGS. USING AVAILABLE RECORD DRAWINGS. USING AVAILABLE RECORD DRAWINGS.
CONTRACTOR SHALL BE RESPONSIBLE FOR CONTRACTOR SHALL BE RESPONSIBLE FOR CONTRACTOR SHALL BE RESPONSIBLE FOR CONTRACTOR SHALL BE RESPONSIBLE FOR
VERIFYING EXACT ROUTING OF ALL PIPING, VERIFYING EXACT ROUTING OF ALL PIPING, VERIFYING EXACT ROUTING OF ALL PIPING, VERIFYING EXACT ROUTING OF ALL PIPING,
DUCTWORK, ETC. DURING CONSTRUCTION. DUCTWORK, ETC. DURING CONSTRUCTION. DUCTWORK, ETC. DURING CONSTRUCTION. DUCTWORK, ETC. DURING CONSTRUCTION.
DEMOLITION OF EXISTING MECHANICAL AND DEMOLITION OF EXISTING MECHANICAL AND DEMOLITION OF EXISTING MECHANICAL AND DEMOLITION OF EXISTING MECHANICAL AND
PLUMBING CONSTRUCTION SHALL BE TO THE PLUMBING CONSTRUCTION SHALL BE TO THE PLUMBING CONSTRUCTION SHALL BE TO THE PLUMBING CONSTRUCTION SHALL BE TO THE
EXTENT REQUIRED TO ACCOMMODATE THE EXTENT REQUIRED TO ACCOMMODATE THE EXTENT REQUIRED TO ACCOMMODATE THE EXTENT REQUIRED TO ACCOMMODATE THE
RENOVATION AND THE ADDITION OF NEW WORK. RENOVATION AND THE ADDITION OF NEW WORK. RENOVATION AND THE ADDITION OF NEW WORK. RENOVATION AND THE ADDITION OF NEW WORK.
REFERENCE ARCHITECTURAL DEMOLITION REFERENCE ARCHITECTURAL DEMOLITION REFERENCE ARCHITECTURAL DEMOLITION REFERENCE ARCHITECTURAL DEMOLITION
DRAWINGS TO COORDINATE AND VERIFY THE DRAWINGS TO COORDINATE AND VERIFY THE DRAWINGS TO COORDINATE AND VERIFY THE DRAWINGS TO COORDINATE AND VERIFY THE
EXTENT OF THE DEMOLITION WORK REQUIRED. EXTENT OF THE DEMOLITION WORK REQUIRED. EXTENT OF THE DEMOLITION WORK REQUIRED. EXTENT OF THE DEMOLITION WORK REQUIRED.
ALL PIPING, DUCTWORK, ETC. TO REMAIN SHALL BE ALL PIPING, DUCTWORK, ETC. TO REMAIN SHALL BE ALL PIPING, DUCTWORK, ETC. TO REMAIN SHALL BE ALL PIPING, DUCTWORK, ETC. TO REMAIN SHALL BE
PROTECTED THROUGHOUT THE CONSTRUCTION PROTECTED THROUGHOUT THE CONSTRUCTION PROTECTED THROUGHOUT THE CONSTRUCTION PROTECTED THROUGHOUT THE CONSTRUCTION
PERIOD. PERIOD. PERIOD. PERIOD.
PROVIDE AND INSTALL CAPS ON EXISTING MAIN PROVIDE AND INSTALL CAPS ON EXISTING MAIN PROVIDE AND INSTALL CAPS ON EXISTING MAIN PROVIDE AND INSTALL CAPS ON EXISTING MAIN
BRANCH BEING REMOVED. REFERENCE BRANCH BEING REMOVED. REFERENCE BRANCH BEING REMOVED. REFERENCE BRANCH BEING REMOVED. REFERENCE
ARCHITECTURAL FOR PATCHWORK. ARCHITECTURAL FOR PATCHWORK. ARCHITECTURAL FOR PATCHWORK. ARCHITECTURAL FOR PATCHWORK.
INDICATED DEMOLITION OF PIPING INCLUDES, BUT INDICATED DEMOLITION OF PIPING INCLUDES, BUT INDICATED DEMOLITION OF PIPING INCLUDES, BUT INDICATED DEMOLITION OF PIPING INCLUDES, BUT
IS NOT LIMITED TO, THE REMOVAL OF PIPING, IS NOT LIMITED TO, THE REMOVAL OF PIPING, IS NOT LIMITED TO, THE REMOVAL OF PIPING, IS NOT LIMITED TO, THE REMOVAL OF PIPING,
FITTINGS, VALVES, HANGERS, SUPPORTS, FITTINGS, VALVES, HANGERS, SUPPORTS, FITTINGS, VALVES, HANGERS, SUPPORTS, FITTINGS, VALVES, HANGERS, SUPPORTS,
INSULATION, ETC. UNLESS NOTED OTHERWISE. INSULATION, ETC. UNLESS NOTED OTHERWISE. INSULATION, ETC. UNLESS NOTED OTHERWISE. INSULATION, ETC. UNLESS NOTED OTHERWISE.
INDICATED DEMOLITION OF MECHANICAL INDICATED DEMOLITION OF MECHANICAL INDICATED DEMOLITION OF MECHANICAL INDICATED DEMOLITION OF MECHANICAL
EQUIPMENT INCLUDES, BUT IS NOT LIMITED TO, EQUIPMENT INCLUDES, BUT IS NOT LIMITED TO, EQUIPMENT INCLUDES, BUT IS NOT LIMITED TO, EQUIPMENT INCLUDES, BUT IS NOT LIMITED TO,
THE REMOVAL OF EQUIPMENT, PIPING, VALVES, THE REMOVAL OF EQUIPMENT, PIPING, VALVES, THE REMOVAL OF EQUIPMENT, PIPING, VALVES, THE REMOVAL OF EQUIPMENT, PIPING, VALVES,
INSULATION, SEISMIC BRACING, CONTROLS, INSULATION, SEISMIC BRACING, CONTROLS, INSULATION, SEISMIC BRACING, CONTROLS, INSULATION, SEISMIC BRACING, CONTROLS,
ELECTRICAL, ETC. UNLESS NOTED OTHERWISE. ELECTRICAL, ETC. UNLESS NOTED OTHERWISE. ELECTRICAL, ETC. UNLESS NOTED OTHERWISE. ELECTRICAL, ETC. UNLESS NOTED OTHERWISE.
CONTRACTOR SHALL BE RESPONSIBLE FOR CONTRACTOR SHALL BE RESPONSIBLE FOR CONTRACTOR SHALL BE RESPONSIBLE FOR CONTRACTOR SHALL BE RESPONSIBLE FOR
PATCHING AND REPAIRING ANY DAMAGE CAUSED PATCHING AND REPAIRING ANY DAMAGE CAUSED PATCHING AND REPAIRING ANY DAMAGE CAUSED PATCHING AND REPAIRING ANY DAMAGE CAUSED
BY HIS / HER PERSONNEL TO EXISTING THAT IS TO BY HIS / HER PERSONNEL TO EXISTING THAT IS TO BY HIS / HER PERSONNEL TO EXISTING THAT IS TO BY HIS / HER PERSONNEL TO EXISTING THAT IS TO
REMAIN OR TO NEWLY INSTALLED BUILDING REMAIN OR TO NEWLY INSTALLED BUILDING REMAIN OR TO NEWLY INSTALLED BUILDING REMAIN OR TO NEWLY INSTALLED BUILDING
COMPONENTS. COMPONENTS. COMPONENTS. COMPONENTS.
PATCH AND SEAL ALL ABANDONED OPENINGS PATCH AND SEAL ALL ABANDONED OPENINGS PATCH AND SEAL ALL ABANDONED OPENINGS PATCH AND SEAL ALL ABANDONED OPENINGS
THROUGH WALLS AND FLOORS. MATCH EXISTING THROUGH WALLS AND FLOORS. MATCH EXISTING THROUGH WALLS AND FLOORS. MATCH EXISTING THROUGH WALLS AND FLOORS. MATCH EXISTING
SURROUNDING FINISH. SURROUNDING FINISH. SURROUNDING FINISH. SURROUNDING FINISH.
CONTRACTOR SHALL REPLACE ANY INSULATION CONTRACTOR SHALL REPLACE ANY INSULATION CONTRACTOR SHALL REPLACE ANY INSULATION CONTRACTOR SHALL REPLACE ANY INSULATION
THAT IS DAMAGED DURING CONSTRUCTION ON THAT IS DAMAGED DURING CONSTRUCTION ON THAT IS DAMAGED DURING CONSTRUCTION ON THAT IS DAMAGED DURING CONSTRUCTION ON
PIPE OR DUCTWORK THAT IS TO REMAIN. PIPE OR DUCTWORK THAT IS TO REMAIN. PIPE OR DUCTWORK THAT IS TO REMAIN. PIPE OR DUCTWORK THAT IS TO REMAIN.
PRIOR TO DEMOLITION OF ANY EQUIPMENT WORK PRIOR TO DEMOLITION OF ANY EQUIPMENT WORK PRIOR TO DEMOLITION OF ANY EQUIPMENT WORK PRIOR TO DEMOLITION OF ANY EQUIPMENT WORK
WITH ELECTRICAL CONTRACTOR AND CONTROLS WITH ELECTRICAL CONTRACTOR AND CONTROLS WITH ELECTRICAL CONTRACTOR AND CONTROLS WITH ELECTRICAL CONTRACTOR AND CONTROLS
CONTRACTOR TO MAKE CERTAIN POWER AND CONTRACTOR TO MAKE CERTAIN POWER AND CONTRACTOR TO MAKE CERTAIN POWER AND CONTRACTOR TO MAKE CERTAIN POWER AND
CONTROLS ARE PROPERLY DISCONNECTED AND CONTROLS ARE PROPERLY DISCONNECTED AND CONTROLS ARE PROPERLY DISCONNECTED AND CONTROLS ARE PROPERLY DISCONNECTED AND
TERMINATED.TERMINATED.TERMINATED.TERMINATED.
B.B.B.B.
C.C.C.C.
D.D.D.D.
E.E.E.E.
F.F.F.F.
G.G.G.G.
H.H.H.H.
I.I.I.I.
J.J.J.J.
K.K.K.K.
L.L.L.L.
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
Level 02 Area
B Mechanical
Piping
Demolition
Plan
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
KEY PLAN
A
B
ao^tfkd=klqbp
0000555510101010 10101010 20202020
SCALE:SCALE:SCALE:SCALE:MD112bMD112bMD112bMD112b 1/8" = 1'1/8" = 1'1/8" = 1'1/8" = 1'----0"0"0"0"
ibsbi=O=^ob^=_=jb`e^kf`^i=mfmfkd=abjlifqflk=mi^k1111
NOTE
#DESCRIPTION
1111 REMOVE EXISTING VAV REHEAT BOX ANDREMOVE EXISTING VAV REHEAT BOX ANDREMOVE EXISTING VAV REHEAT BOX ANDREMOVE EXISTING VAV REHEAT BOX AND
ASSOCIATED REHEAT COIL, ISOLATION VALVES,ASSOCIATED REHEAT COIL, ISOLATION VALVES,ASSOCIATED REHEAT COIL, ISOLATION VALVES,ASSOCIATED REHEAT COIL, ISOLATION VALVES,
STRAINER, CONTROL VALVE, BALANCE VALVE,STRAINER, CONTROL VALVE, BALANCE VALVE,STRAINER, CONTROL VALVE, BALANCE VALVE,STRAINER, CONTROL VALVE, BALANCE VALVE,
CONTROLS, ETC. COMPLETE.CONTROLS, ETC. COMPLETE.CONTROLS, ETC. COMPLETE.CONTROLS, ETC. COMPLETE.
2222 REMOVE PORTION OF EXISTING HEATING WATERREMOVE PORTION OF EXISTING HEATING WATERREMOVE PORTION OF EXISTING HEATING WATERREMOVE PORTION OF EXISTING HEATING WATER
SUPPLY/RETURN PIPING AS SHOWN.SUPPLY/RETURN PIPING AS SHOWN.SUPPLY/RETURN PIPING AS SHOWN.SUPPLY/RETURN PIPING AS SHOWN.
3333 CAP HEATING WATER SUPPLY/RETURN AT MAIN.CAP HEATING WATER SUPPLY/RETURN AT MAIN.CAP HEATING WATER SUPPLY/RETURN AT MAIN.CAP HEATING WATER SUPPLY/RETURN AT MAIN.
4444 REMOVE EXISTING A/C UNIT AND ASSOCIATEDREMOVE EXISTING A/C UNIT AND ASSOCIATEDREMOVE EXISTING A/C UNIT AND ASSOCIATEDREMOVE EXISTING A/C UNIT AND ASSOCIATED
CONTROLS, CONDENSATE DRAIN PIPING,CONTROLS, CONDENSATE DRAIN PIPING,CONTROLS, CONDENSATE DRAIN PIPING,CONTROLS, CONDENSATE DRAIN PIPING,
REFRIGERANT LINES, CONDENSING UNIT (ONREFRIGERANT LINES, CONDENSING UNIT (ONREFRIGERANT LINES, CONDENSING UNIT (ONREFRIGERANT LINES, CONDENSING UNIT (ON
ROOF), ETC. COMPLETE.ROOF), ETC. COMPLETE.ROOF), ETC. COMPLETE.ROOF), ETC. COMPLETE.
1111
GGGG
JJJJ
LLLL
MMMM
NNNN
PPPP
QQQQ
EEEE
CCCC
2222 3333 4444 5555
1111
1111
1111
1111
1111
1111
1111
11111111
1111
2222
3333
4444
5555
6666
6666
2222 2222
33333333
2222
3333
5555
3333 4444
2222
4444
2222
2222
2222
3333
2222
2222
3333
2222
2222
3333
3333
2222
2222
3333
2222
2222
3333
3333
2222
3333
2222
3333
2222
2222 2222
2222
4444
3333
3333
4444
3333
3333
2222 2222
2222
2222
4444
3333
3333
2222
3333
2222
2222
2222
2222
3333
3333
2222
3333
3333
3333
3333
3333
3333
4444
4444
3333
3333
dbkbo^i=klqbp
A.A.A.A.FIELD VERIFY EXACT LOCATIONS OF EXISTING FIELD VERIFY EXACT LOCATIONS OF EXISTING FIELD VERIFY EXACT LOCATIONS OF EXISTING FIELD VERIFY EXACT LOCATIONS OF EXISTING
PIPING, DUCTWORK, EQUIPMENT, ETC. PIPING, DUCTWORK, EQUIPMENT, ETC. PIPING, DUCTWORK, EQUIPMENT, ETC. PIPING, DUCTWORK, EQUIPMENT, ETC.
DEMOLITION FLOOR PLANS HAVE BEEN CREATED DEMOLITION FLOOR PLANS HAVE BEEN CREATED DEMOLITION FLOOR PLANS HAVE BEEN CREATED DEMOLITION FLOOR PLANS HAVE BEEN CREATED
USING AVAILABLE RECORD DRAWINGS. USING AVAILABLE RECORD DRAWINGS. USING AVAILABLE RECORD DRAWINGS. USING AVAILABLE RECORD DRAWINGS.
CONTRACTOR SHALL BE RESPONSIBLE FOR CONTRACTOR SHALL BE RESPONSIBLE FOR CONTRACTOR SHALL BE RESPONSIBLE FOR CONTRACTOR SHALL BE RESPONSIBLE FOR
VERIFYING EXACT ROUTING OF ALL PIPING, VERIFYING EXACT ROUTING OF ALL PIPING, VERIFYING EXACT ROUTING OF ALL PIPING, VERIFYING EXACT ROUTING OF ALL PIPING,
DUCTWORK, ETC. DURING CONSTRUCTION. DUCTWORK, ETC. DURING CONSTRUCTION. DUCTWORK, ETC. DURING CONSTRUCTION. DUCTWORK, ETC. DURING CONSTRUCTION.
DEMOLITION OF EXISTING MECHANICAL AND DEMOLITION OF EXISTING MECHANICAL AND DEMOLITION OF EXISTING MECHANICAL AND DEMOLITION OF EXISTING MECHANICAL AND
PLUMBING CONSTRUCTION SHALL BE TO THE PLUMBING CONSTRUCTION SHALL BE TO THE PLUMBING CONSTRUCTION SHALL BE TO THE PLUMBING CONSTRUCTION SHALL BE TO THE
EXTENT REQUIRED TO ACCOMMODATE THE EXTENT REQUIRED TO ACCOMMODATE THE EXTENT REQUIRED TO ACCOMMODATE THE EXTENT REQUIRED TO ACCOMMODATE THE
RENOVATION AND THE ADDITION OF NEW WORK. RENOVATION AND THE ADDITION OF NEW WORK. RENOVATION AND THE ADDITION OF NEW WORK. RENOVATION AND THE ADDITION OF NEW WORK.
REFERENCE ARCHITECTURAL DEMOLITION REFERENCE ARCHITECTURAL DEMOLITION REFERENCE ARCHITECTURAL DEMOLITION REFERENCE ARCHITECTURAL DEMOLITION
DRAWINGS TO COORDINATE AND VERIFY THE DRAWINGS TO COORDINATE AND VERIFY THE DRAWINGS TO COORDINATE AND VERIFY THE DRAWINGS TO COORDINATE AND VERIFY THE
EXTENT OF THE DEMOLITION WORK REQUIRED. EXTENT OF THE DEMOLITION WORK REQUIRED. EXTENT OF THE DEMOLITION WORK REQUIRED. EXTENT OF THE DEMOLITION WORK REQUIRED.
ALL PIPING, DUCTWORK, ETC. TO REMAIN SHALL BE ALL PIPING, DUCTWORK, ETC. TO REMAIN SHALL BE ALL PIPING, DUCTWORK, ETC. TO REMAIN SHALL BE ALL PIPING, DUCTWORK, ETC. TO REMAIN SHALL BE
PROTECTED THROUGHOUT THE CONSTRUCTION PROTECTED THROUGHOUT THE CONSTRUCTION PROTECTED THROUGHOUT THE CONSTRUCTION PROTECTED THROUGHOUT THE CONSTRUCTION
PERIOD. PERIOD. PERIOD. PERIOD.
PROVIDE AND INSTALL CAPS ON EXISTING MAIN PROVIDE AND INSTALL CAPS ON EXISTING MAIN PROVIDE AND INSTALL CAPS ON EXISTING MAIN PROVIDE AND INSTALL CAPS ON EXISTING MAIN
BRANCH BEING REMOVED. REFERENCE BRANCH BEING REMOVED. REFERENCE BRANCH BEING REMOVED. REFERENCE BRANCH BEING REMOVED. REFERENCE
ARCHITECTURAL FOR PATCHWORK. ARCHITECTURAL FOR PATCHWORK. ARCHITECTURAL FOR PATCHWORK. ARCHITECTURAL FOR PATCHWORK.
INDICATED DEMOLITION OF PIPING INCLUDES, BUT INDICATED DEMOLITION OF PIPING INCLUDES, BUT INDICATED DEMOLITION OF PIPING INCLUDES, BUT INDICATED DEMOLITION OF PIPING INCLUDES, BUT
IS NOT LIMITED TO, THE REMOVAL OF PIPING, IS NOT LIMITED TO, THE REMOVAL OF PIPING, IS NOT LIMITED TO, THE REMOVAL OF PIPING, IS NOT LIMITED TO, THE REMOVAL OF PIPING,
FITTINGS, VALVES, HANGERS, SUPPORTS, FITTINGS, VALVES, HANGERS, SUPPORTS, FITTINGS, VALVES, HANGERS, SUPPORTS, FITTINGS, VALVES, HANGERS, SUPPORTS,
INSULATION, ETC. UNLESS NOTED OTHERWISE. INSULATION, ETC. UNLESS NOTED OTHERWISE. INSULATION, ETC. UNLESS NOTED OTHERWISE. INSULATION, ETC. UNLESS NOTED OTHERWISE.
INDICATED DEMOLITION OF MECHANICAL INDICATED DEMOLITION OF MECHANICAL INDICATED DEMOLITION OF MECHANICAL INDICATED DEMOLITION OF MECHANICAL
EQUIPMENT INCLUDES, BUT IS NOT LIMITED TO, EQUIPMENT INCLUDES, BUT IS NOT LIMITED TO, EQUIPMENT INCLUDES, BUT IS NOT LIMITED TO, EQUIPMENT INCLUDES, BUT IS NOT LIMITED TO,
THE REMOVAL OF EQUIPMENT, PIPING, VALVES, THE REMOVAL OF EQUIPMENT, PIPING, VALVES, THE REMOVAL OF EQUIPMENT, PIPING, VALVES, THE REMOVAL OF EQUIPMENT, PIPING, VALVES,
INSULATION, SEISMIC BRACING, CONTROLS, INSULATION, SEISMIC BRACING, CONTROLS, INSULATION, SEISMIC BRACING, CONTROLS, INSULATION, SEISMIC BRACING, CONTROLS,
ELECTRICAL, ETC. UNLESS NOTED OTHERWISE. ELECTRICAL, ETC. UNLESS NOTED OTHERWISE. ELECTRICAL, ETC. UNLESS NOTED OTHERWISE. ELECTRICAL, ETC. UNLESS NOTED OTHERWISE.
CONTRACTOR SHALL BE RESPONSIBLE FOR CONTRACTOR SHALL BE RESPONSIBLE FOR CONTRACTOR SHALL BE RESPONSIBLE FOR CONTRACTOR SHALL BE RESPONSIBLE FOR
PATCHING AND REPAIRING ANY DAMAGE CAUSED PATCHING AND REPAIRING ANY DAMAGE CAUSED PATCHING AND REPAIRING ANY DAMAGE CAUSED PATCHING AND REPAIRING ANY DAMAGE CAUSED
BY HIS / HER PERSONNEL TO EXISTING THAT IS TO BY HIS / HER PERSONNEL TO EXISTING THAT IS TO BY HIS / HER PERSONNEL TO EXISTING THAT IS TO BY HIS / HER PERSONNEL TO EXISTING THAT IS TO
REMAIN OR TO NEWLY INSTALLED BUILDING REMAIN OR TO NEWLY INSTALLED BUILDING REMAIN OR TO NEWLY INSTALLED BUILDING REMAIN OR TO NEWLY INSTALLED BUILDING
COMPONENTS. COMPONENTS. COMPONENTS. COMPONENTS.
PATCH AND SEAL ALL ABANDONED OPENINGS PATCH AND SEAL ALL ABANDONED OPENINGS PATCH AND SEAL ALL ABANDONED OPENINGS PATCH AND SEAL ALL ABANDONED OPENINGS
THROUGH WALLS AND FLOORS. MATCH EXISTING THROUGH WALLS AND FLOORS. MATCH EXISTING THROUGH WALLS AND FLOORS. MATCH EXISTING THROUGH WALLS AND FLOORS. MATCH EXISTING
SURROUNDING FINISH. SURROUNDING FINISH. SURROUNDING FINISH. SURROUNDING FINISH.
CONTRACTOR SHALL REPLACE ANY INSULATION CONTRACTOR SHALL REPLACE ANY INSULATION CONTRACTOR SHALL REPLACE ANY INSULATION CONTRACTOR SHALL REPLACE ANY INSULATION
THAT IS DAMAGED DURING CONSTRUCTION ON THAT IS DAMAGED DURING CONSTRUCTION ON THAT IS DAMAGED DURING CONSTRUCTION ON THAT IS DAMAGED DURING CONSTRUCTION ON
PIPE OR DUCTWORK THAT IS TO REMAIN. PIPE OR DUCTWORK THAT IS TO REMAIN. PIPE OR DUCTWORK THAT IS TO REMAIN. PIPE OR DUCTWORK THAT IS TO REMAIN.
PRIOR TO DEMOLITION OF ANY EQUIPMENT WORK PRIOR TO DEMOLITION OF ANY EQUIPMENT WORK PRIOR TO DEMOLITION OF ANY EQUIPMENT WORK PRIOR TO DEMOLITION OF ANY EQUIPMENT WORK
WITH ELECTRICAL CONTRACTOR AND CONTROLS WITH ELECTRICAL CONTRACTOR AND CONTROLS WITH ELECTRICAL CONTRACTOR AND CONTROLS WITH ELECTRICAL CONTRACTOR AND CONTROLS
CONTRACTOR TO MAKE CERTAIN POWER AND CONTRACTOR TO MAKE CERTAIN POWER AND CONTRACTOR TO MAKE CERTAIN POWER AND CONTRACTOR TO MAKE CERTAIN POWER AND
CONTROLS ARE PROPERLY DISCONNECTED AND CONTROLS ARE PROPERLY DISCONNECTED AND CONTROLS ARE PROPERLY DISCONNECTED AND CONTROLS ARE PROPERLY DISCONNECTED AND
TERMINATED.TERMINATED.TERMINATED.TERMINATED.
B.B.B.B.
C.C.C.C.
D.D.D.D.
E.E.E.E.
F.F.F.F.
G.G.G.G.
H.H.H.H.
I.I.I.I.
J.J.J.J.
K.K.K.K.
L.L.L.L.
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
Level 03 Area
A Mechanical
Piping
Demolition
Plan
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
KEY PLAN
A
B
ao^tfkd=klqbp
0000555510101010 10101010 20202020
SCALE:SCALE:SCALE:SCALE:MD113aMD113aMD113aMD113a 1/8" = 1'1/8" = 1'1/8" = 1'1/8" = 1'----0"0"0"0"
ibsbi=P=^ob^=^=jb`e^kf`^i=mfmfkd=abjlifqflk=mi^k1111
NOTE
#DESCRIPTION
1111 REMOVE EXISTING BASEBOARD HEATERREMOVE EXISTING BASEBOARD HEATERREMOVE EXISTING BASEBOARD HEATERREMOVE EXISTING BASEBOARD HEATER
INCLUDING ALL VALVES, STRAINERS, ETC.INCLUDING ALL VALVES, STRAINERS, ETC.INCLUDING ALL VALVES, STRAINERS, ETC.INCLUDING ALL VALVES, STRAINERS, ETC.
2222 REMOVE EXISTING VAV REHEAT BOX ANDREMOVE EXISTING VAV REHEAT BOX ANDREMOVE EXISTING VAV REHEAT BOX ANDREMOVE EXISTING VAV REHEAT BOX AND
ASSOCIATED REHEAT COIL, ISOLATION VALVES,ASSOCIATED REHEAT COIL, ISOLATION VALVES,ASSOCIATED REHEAT COIL, ISOLATION VALVES,ASSOCIATED REHEAT COIL, ISOLATION VALVES,
STRAINER, CONTROL VALVE, BALANCE VALVE,STRAINER, CONTROL VALVE, BALANCE VALVE,STRAINER, CONTROL VALVE, BALANCE VALVE,STRAINER, CONTROL VALVE, BALANCE VALVE,
CONTROLS, ETC. COMPLETE.CONTROLS, ETC. COMPLETE.CONTROLS, ETC. COMPLETE.CONTROLS, ETC. COMPLETE.
3333 REMOVE PORTION OF EXISTING HEATING WATERREMOVE PORTION OF EXISTING HEATING WATERREMOVE PORTION OF EXISTING HEATING WATERREMOVE PORTION OF EXISTING HEATING WATER
SUPPLY/RETURN PIPING AS SHOWN.SUPPLY/RETURN PIPING AS SHOWN.SUPPLY/RETURN PIPING AS SHOWN.SUPPLY/RETURN PIPING AS SHOWN.
4444 CAP HEATING WATER SUPPLY/RETURN AT MAIN.CAP HEATING WATER SUPPLY/RETURN AT MAIN.CAP HEATING WATER SUPPLY/RETURN AT MAIN.CAP HEATING WATER SUPPLY/RETURN AT MAIN.
5555 REMOVE ALL EXISTING STEAM AND CONDENSATEREMOVE ALL EXISTING STEAM AND CONDENSATEREMOVE ALL EXISTING STEAM AND CONDENSATEREMOVE ALL EXISTING STEAM AND CONDENSATE
PIPING BACK TO THE MECHANICAL ROOM ONPIPING BACK TO THE MECHANICAL ROOM ONPIPING BACK TO THE MECHANICAL ROOM ONPIPING BACK TO THE MECHANICAL ROOM ON
LEVEL 0. REFERENCE DRAWING MD401 FORLEVEL 0. REFERENCE DRAWING MD401 FORLEVEL 0. REFERENCE DRAWING MD401 FORLEVEL 0. REFERENCE DRAWING MD401 FOR
CONTINUATION.CONTINUATION.CONTINUATION.CONTINUATION.
6666 REMOVE EXISTING HWS/R RISER PIPING IN CHASEREMOVE EXISTING HWS/R RISER PIPING IN CHASEREMOVE EXISTING HWS/R RISER PIPING IN CHASEREMOVE EXISTING HWS/R RISER PIPING IN CHASE
AND PORTION OF MAIN PIPING AS SHOWNAND PORTION OF MAIN PIPING AS SHOWNAND PORTION OF MAIN PIPING AS SHOWNAND PORTION OF MAIN PIPING AS SHOWN
INCLUDING THE BALANCE AND GATE VALVE.INCLUDING THE BALANCE AND GATE VALVE.INCLUDING THE BALANCE AND GATE VALVE.INCLUDING THE BALANCE AND GATE VALVE.
1111
GGGG
JJJJ
EEEE
CCCC
2222 3333
1111
2222
3333
4444
5555
3333 3333
3333
4444
4444
5555
5555
1111
1111
1111
1111
AAAA
MH401MH401MH401MH401
BBBB
MH401MH401MH401MH401
6666
7777
7777
6666
6666
dbkbo^i=klqbp
A.A.A.A.REMOVE ALL EXISTING S.A. / E.A DUCTWORK, S.A. / REMOVE ALL EXISTING S.A. / E.A DUCTWORK, S.A. / REMOVE ALL EXISTING S.A. / E.A DUCTWORK, S.A. / REMOVE ALL EXISTING S.A. / E.A DUCTWORK, S.A. /
R.A. / E.A. DIFFUSERS / GRILLES, CONTROLS, R.A. / E.A. DIFFUSERS / GRILLES, CONTROLS, R.A. / E.A. DIFFUSERS / GRILLES, CONTROLS, R.A. / E.A. DIFFUSERS / GRILLES, CONTROLS,
SENSORS, VAV REHEAT BOXES AND ASSOCIATED SENSORS, VAV REHEAT BOXES AND ASSOCIATED SENSORS, VAV REHEAT BOXES AND ASSOCIATED SENSORS, VAV REHEAT BOXES AND ASSOCIATED
HEATING WATER BRANCH PIPING, VALVES, HEATING WATER BRANCH PIPING, VALVES, HEATING WATER BRANCH PIPING, VALVES, HEATING WATER BRANCH PIPING, VALVES,
STRAINER, ETC. UNLESS OTHERWISE NOTED. STRAINER, ETC. UNLESS OTHERWISE NOTED. STRAINER, ETC. UNLESS OTHERWISE NOTED. STRAINER, ETC. UNLESS OTHERWISE NOTED.
REFERENCE MECHANICAL PIPING DEMOLITION REFERENCE MECHANICAL PIPING DEMOLITION REFERENCE MECHANICAL PIPING DEMOLITION REFERENCE MECHANICAL PIPING DEMOLITION
PLANS.PLANS.PLANS.PLANS.
FIELD VERIFY EXACT LOCATIONS OF EXISTING FIELD VERIFY EXACT LOCATIONS OF EXISTING FIELD VERIFY EXACT LOCATIONS OF EXISTING FIELD VERIFY EXACT LOCATIONS OF EXISTING
PIPING, DUCTWORK, EQUIPMENT, ETC. PIPING, DUCTWORK, EQUIPMENT, ETC. PIPING, DUCTWORK, EQUIPMENT, ETC. PIPING, DUCTWORK, EQUIPMENT, ETC.
DEMOLITION FLOOR PLANS HAVE BEEN CREATED DEMOLITION FLOOR PLANS HAVE BEEN CREATED DEMOLITION FLOOR PLANS HAVE BEEN CREATED DEMOLITION FLOOR PLANS HAVE BEEN CREATED
USING AVAILABLE RECORD DRAWINGS. USING AVAILABLE RECORD DRAWINGS. USING AVAILABLE RECORD DRAWINGS. USING AVAILABLE RECORD DRAWINGS.
CONTRACTOR SHALL BE RESPONSIBLE FOR CONTRACTOR SHALL BE RESPONSIBLE FOR CONTRACTOR SHALL BE RESPONSIBLE FOR CONTRACTOR SHALL BE RESPONSIBLE FOR
VERIFYING EXACT ROUTING OF ALL PIPING, VERIFYING EXACT ROUTING OF ALL PIPING, VERIFYING EXACT ROUTING OF ALL PIPING, VERIFYING EXACT ROUTING OF ALL PIPING,
DUCTWORK, ETC. DURING CONSTRUCTION. DUCTWORK, ETC. DURING CONSTRUCTION. DUCTWORK, ETC. DURING CONSTRUCTION. DUCTWORK, ETC. DURING CONSTRUCTION.
DEMOLITION OF EXISTING MECHANICAL AND DEMOLITION OF EXISTING MECHANICAL AND DEMOLITION OF EXISTING MECHANICAL AND DEMOLITION OF EXISTING MECHANICAL AND
PLUMBING CONSTRUCTION SHALL BE TO THE PLUMBING CONSTRUCTION SHALL BE TO THE PLUMBING CONSTRUCTION SHALL BE TO THE PLUMBING CONSTRUCTION SHALL BE TO THE
EXTENT REQUIRED TO ACCOMMODATE THE EXTENT REQUIRED TO ACCOMMODATE THE EXTENT REQUIRED TO ACCOMMODATE THE EXTENT REQUIRED TO ACCOMMODATE THE
RENOVATION AND THE ADDITION OF NEW WORK. RENOVATION AND THE ADDITION OF NEW WORK. RENOVATION AND THE ADDITION OF NEW WORK. RENOVATION AND THE ADDITION OF NEW WORK.
REFERENCE ARCHITECTURAL DEMOLITION REFERENCE ARCHITECTURAL DEMOLITION REFERENCE ARCHITECTURAL DEMOLITION REFERENCE ARCHITECTURAL DEMOLITION
DRAWINGS TO COORDINATE AND VERIFY THE DRAWINGS TO COORDINATE AND VERIFY THE DRAWINGS TO COORDINATE AND VERIFY THE DRAWINGS TO COORDINATE AND VERIFY THE
EXTENT OF THE DEMOLITION WORK REQUIRED. EXTENT OF THE DEMOLITION WORK REQUIRED. EXTENT OF THE DEMOLITION WORK REQUIRED. EXTENT OF THE DEMOLITION WORK REQUIRED.
ALL PIPING, DUCTWORK, ETC. TO REMAIN SHALL BE ALL PIPING, DUCTWORK, ETC. TO REMAIN SHALL BE ALL PIPING, DUCTWORK, ETC. TO REMAIN SHALL BE ALL PIPING, DUCTWORK, ETC. TO REMAIN SHALL BE
PROTECTED THROUGHOUT THE CONSTRUCTION PROTECTED THROUGHOUT THE CONSTRUCTION PROTECTED THROUGHOUT THE CONSTRUCTION PROTECTED THROUGHOUT THE CONSTRUCTION
PERIOD. PERIOD. PERIOD. PERIOD.
PROVIDE AND INSTALL CAPS ON EXISTING MAIN PROVIDE AND INSTALL CAPS ON EXISTING MAIN PROVIDE AND INSTALL CAPS ON EXISTING MAIN PROVIDE AND INSTALL CAPS ON EXISTING MAIN
DUCTWORK AND / OR PIPING BRANCH BEING DUCTWORK AND / OR PIPING BRANCH BEING DUCTWORK AND / OR PIPING BRANCH BEING DUCTWORK AND / OR PIPING BRANCH BEING
REMOVED. REFERENCE ARCHITECTURAL FOR REMOVED. REFERENCE ARCHITECTURAL FOR REMOVED. REFERENCE ARCHITECTURAL FOR REMOVED. REFERENCE ARCHITECTURAL FOR
PATCHWORK. PATCHWORK. PATCHWORK. PATCHWORK.
INDICATED DEMOLITION OF PIPING AND DUCTWORK INDICATED DEMOLITION OF PIPING AND DUCTWORK INDICATED DEMOLITION OF PIPING AND DUCTWORK INDICATED DEMOLITION OF PIPING AND DUCTWORK
INCLUDES, BUT IS NOT LIMITED TO, THE REMOVAL INCLUDES, BUT IS NOT LIMITED TO, THE REMOVAL INCLUDES, BUT IS NOT LIMITED TO, THE REMOVAL INCLUDES, BUT IS NOT LIMITED TO, THE REMOVAL
OF DUCTWORK, PIPING, FITTINGS, VALVES, OF DUCTWORK, PIPING, FITTINGS, VALVES, OF DUCTWORK, PIPING, FITTINGS, VALVES, OF DUCTWORK, PIPING, FITTINGS, VALVES,
HANGERS, SUPPORTS, INSULATION, ETC. UNLESS HANGERS, SUPPORTS, INSULATION, ETC. UNLESS HANGERS, SUPPORTS, INSULATION, ETC. UNLESS HANGERS, SUPPORTS, INSULATION, ETC. UNLESS
NOTED OTHERWISE. NOTED OTHERWISE. NOTED OTHERWISE. NOTED OTHERWISE.
INDICATED DEMOLITION OF MECHANICAL INDICATED DEMOLITION OF MECHANICAL INDICATED DEMOLITION OF MECHANICAL INDICATED DEMOLITION OF MECHANICAL
EQUIPMENT INCLUDES, BUT IS NOT LIMITED TO, EQUIPMENT INCLUDES, BUT IS NOT LIMITED TO, EQUIPMENT INCLUDES, BUT IS NOT LIMITED TO, EQUIPMENT INCLUDES, BUT IS NOT LIMITED TO,
THE REMOVAL OF EQUIPMENT, PIPING, VALVES, THE REMOVAL OF EQUIPMENT, PIPING, VALVES, THE REMOVAL OF EQUIPMENT, PIPING, VALVES, THE REMOVAL OF EQUIPMENT, PIPING, VALVES,
INSULATION, SEISMIC BRACING, CONTROLS, INSULATION, SEISMIC BRACING, CONTROLS, INSULATION, SEISMIC BRACING, CONTROLS, INSULATION, SEISMIC BRACING, CONTROLS,
ELECTRICAL, ETC. UNLESS NOTED OTHERWISE. ELECTRICAL, ETC. UNLESS NOTED OTHERWISE. ELECTRICAL, ETC. UNLESS NOTED OTHERWISE. ELECTRICAL, ETC. UNLESS NOTED OTHERWISE.
FIELD VERIFY EXACT LOCATIONS OF FIELD VERIFY EXACT LOCATIONS OF FIELD VERIFY EXACT LOCATIONS OF FIELD VERIFY EXACT LOCATIONS OF
THERMOSTATS, SENSOR AND CONTROLLING THERMOSTATS, SENSOR AND CONTROLLING THERMOSTATS, SENSOR AND CONTROLLING THERMOSTATS, SENSOR AND CONTROLLING
UNITS. UNITS. UNITS. UNITS.
CONTRACTOR SHALL BE RESPONSIBLE FOR CONTRACTOR SHALL BE RESPONSIBLE FOR CONTRACTOR SHALL BE RESPONSIBLE FOR CONTRACTOR SHALL BE RESPONSIBLE FOR
PATCHING AND REPAIRING ANY DAMAGE CAUSED PATCHING AND REPAIRING ANY DAMAGE CAUSED PATCHING AND REPAIRING ANY DAMAGE CAUSED PATCHING AND REPAIRING ANY DAMAGE CAUSED
BY HIS / HER PERSONNEL TO EXISTING THAT IS TO BY HIS / HER PERSONNEL TO EXISTING THAT IS TO BY HIS / HER PERSONNEL TO EXISTING THAT IS TO BY HIS / HER PERSONNEL TO EXISTING THAT IS TO
REMAIN OR TO NEWLY INSTALLED BUILDING REMAIN OR TO NEWLY INSTALLED BUILDING REMAIN OR TO NEWLY INSTALLED BUILDING REMAIN OR TO NEWLY INSTALLED BUILDING
COMPONENTS. COMPONENTS. COMPONENTS. COMPONENTS.
PATCH AND SEAL ALL ABANDONED OPENINGS PATCH AND SEAL ALL ABANDONED OPENINGS PATCH AND SEAL ALL ABANDONED OPENINGS PATCH AND SEAL ALL ABANDONED OPENINGS
THROUGH WALLS AND FLOORS. MATCH EXISTING THROUGH WALLS AND FLOORS. MATCH EXISTING THROUGH WALLS AND FLOORS. MATCH EXISTING THROUGH WALLS AND FLOORS. MATCH EXISTING
SURROUNDING FINISH. SURROUNDING FINISH. SURROUNDING FINISH. SURROUNDING FINISH.
CONTRACTOR SHALL REPLACE ANY INSULATION CONTRACTOR SHALL REPLACE ANY INSULATION CONTRACTOR SHALL REPLACE ANY INSULATION CONTRACTOR SHALL REPLACE ANY INSULATION
THAT IS DAMAGED DURING CONSTRUCTION ON THAT IS DAMAGED DURING CONSTRUCTION ON THAT IS DAMAGED DURING CONSTRUCTION ON THAT IS DAMAGED DURING CONSTRUCTION ON
PIPE OR DUCTWORK THAT IS TO REMAIN. PIPE OR DUCTWORK THAT IS TO REMAIN. PIPE OR DUCTWORK THAT IS TO REMAIN. PIPE OR DUCTWORK THAT IS TO REMAIN.
PRIOR TO DEMOLITION OF ANY EQUIPMENT WORK PRIOR TO DEMOLITION OF ANY EQUIPMENT WORK PRIOR TO DEMOLITION OF ANY EQUIPMENT WORK PRIOR TO DEMOLITION OF ANY EQUIPMENT WORK
WITH ELECTRICAL CONTRACTOR AND CONTROLS WITH ELECTRICAL CONTRACTOR AND CONTROLS WITH ELECTRICAL CONTRACTOR AND CONTROLS WITH ELECTRICAL CONTRACTOR AND CONTROLS
CONTRACTOR TO MAKE CERTAIN POWER AND CONTRACTOR TO MAKE CERTAIN POWER AND CONTRACTOR TO MAKE CERTAIN POWER AND CONTRACTOR TO MAKE CERTAIN POWER AND
CONTROLS ARE PROPERLY DISCONNECTED AND CONTROLS ARE PROPERLY DISCONNECTED AND CONTROLS ARE PROPERLY DISCONNECTED AND CONTROLS ARE PROPERLY DISCONNECTED AND
TERMINATED.TERMINATED.TERMINATED.TERMINATED.
B.B.B.B.
C.C.C.C.
D.D.D.D.
E.E.E.E.
F.F.F.F.
G.G.G.G.
H.H.H.H.
I.I.I.I.
J.J.J.J.
K.K.K.K.
L.L.L.L.
M.M.M.M.
N.N.N.N.
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
Enlarged
Level 00 Area
A Mechanical
Room
Demolition
Plan
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
ao^tfkd=klqbp
SCALE:SCALE:SCALE:SCALE:MD401MD401MD401MD401 1/4" = 1'1/4" = 1'1/4" = 1'1/4" = 1'----0"0"0"0"
bki^odba=ibsbi=MM=^ob^=^=jb`e^kf`^i=ollj=abjlifqflk=mi^k1111
00002.52.52.52.55555 5555 10101010
NOTE
#DESCRIPTION
1111 REMOVE EXISTING HWS/R PIPING SERVINGREMOVE EXISTING HWS/R PIPING SERVINGREMOVE EXISTING HWS/R PIPING SERVINGREMOVE EXISTING HWS/R PIPING SERVING
BASEBOARD HEATERS AS SHOWN.BASEBOARD HEATERS AS SHOWN.BASEBOARD HEATERS AS SHOWN.BASEBOARD HEATERS AS SHOWN.
2222 EXISTING HWS/R PIPING SERVING BASEBOARDEXISTING HWS/R PIPING SERVING BASEBOARDEXISTING HWS/R PIPING SERVING BASEBOARDEXISTING HWS/R PIPING SERVING BASEBOARD
HEATERS TO REMAIN AND BE REPURPOSED ASHEATERS TO REMAIN AND BE REPURPOSED ASHEATERS TO REMAIN AND BE REPURPOSED ASHEATERS TO REMAIN AND BE REPURPOSED AS
CHILLED WATER SUPPLY AND RETURN PIPING.CHILLED WATER SUPPLY AND RETURN PIPING.CHILLED WATER SUPPLY AND RETURN PIPING.CHILLED WATER SUPPLY AND RETURN PIPING.
FIELD VERIFY EXISTING PIPE ROUTING.FIELD VERIFY EXISTING PIPE ROUTING.FIELD VERIFY EXISTING PIPE ROUTING.FIELD VERIFY EXISTING PIPE ROUTING.
3333 REMOVE ALL EXISTING STEAM AND CONDENSATEREMOVE ALL EXISTING STEAM AND CONDENSATEREMOVE ALL EXISTING STEAM AND CONDENSATEREMOVE ALL EXISTING STEAM AND CONDENSATE
PIPING IN CHASE BACK TO MAIN AS SHOWN ANDPIPING IN CHASE BACK TO MAIN AS SHOWN ANDPIPING IN CHASE BACK TO MAIN AS SHOWN ANDPIPING IN CHASE BACK TO MAIN AS SHOWN AND
CAP.CAP.CAP.CAP.
4444 REMOVE EXISTING HWS/R RISER PIPING IN CHASEREMOVE EXISTING HWS/R RISER PIPING IN CHASEREMOVE EXISTING HWS/R RISER PIPING IN CHASEREMOVE EXISTING HWS/R RISER PIPING IN CHASE
AND PORTION OF MAIN PIPING AS SHOWN.AND PORTION OF MAIN PIPING AS SHOWN.AND PORTION OF MAIN PIPING AS SHOWN.AND PORTION OF MAIN PIPING AS SHOWN.
5555 REMOVE EXISTING BASEBOARD HEATERREMOVE EXISTING BASEBOARD HEATERREMOVE EXISTING BASEBOARD HEATERREMOVE EXISTING BASEBOARD HEATER
CIRCULATION PUMP AND ASSOCIATED STRAINER,CIRCULATION PUMP AND ASSOCIATED STRAINER,CIRCULATION PUMP AND ASSOCIATED STRAINER,CIRCULATION PUMP AND ASSOCIATED STRAINER,
VALVES, CONTROLS, ETC. COMPLETE. CAP HWRVALVES, CONTROLS, ETC. COMPLETE. CAP HWRVALVES, CONTROLS, ETC. COMPLETE. CAP HWRVALVES, CONTROLS, ETC. COMPLETE. CAP HWR
PIPING AT MAIN. RETURN CIRCULATION PUMP TOPIPING AT MAIN. RETURN CIRCULATION PUMP TOPIPING AT MAIN. RETURN CIRCULATION PUMP TOPIPING AT MAIN. RETURN CIRCULATION PUMP TO
THE OWNER.THE OWNER.THE OWNER.THE OWNER.
6666 REMOVE PORTION OF EXISTING HWS PIPING ASREMOVE PORTION OF EXISTING HWS PIPING ASREMOVE PORTION OF EXISTING HWS PIPING ASREMOVE PORTION OF EXISTING HWS PIPING AS
SHOWN AND CAP.SHOWN AND CAP.SHOWN AND CAP.SHOWN AND CAP.
7777 REMOVE EXISTING HEATING WATER PUMP BACKREMOVE EXISTING HEATING WATER PUMP BACKREMOVE EXISTING HEATING WATER PUMP BACKREMOVE EXISTING HEATING WATER PUMP BACK
THROUGH THE BUTTERFLY VALVES PREPARATORYTHROUGH THE BUTTERFLY VALVES PREPARATORYTHROUGH THE BUTTERFLY VALVES PREPARATORYTHROUGH THE BUTTERFLY VALVES PREPARATORY
FOR NEW. REFERENCE REMODEL FLOW DIAGRAMFOR NEW. REFERENCE REMODEL FLOW DIAGRAMFOR NEW. REFERENCE REMODEL FLOW DIAGRAMFOR NEW. REFERENCE REMODEL FLOW DIAGRAM
ON DRAWING MP602 FOR ADDITIONAL DETAIL.ON DRAWING MP602 FOR ADDITIONAL DETAIL.ON DRAWING MP602 FOR ADDITIONAL DETAIL.ON DRAWING MP602 FOR ADDITIONAL DETAIL.
KEY PLAN
A
B
999988887777
DDDD
BBBB
2222
1111
1111
1111
1111
1111
3333
3333
dbkbo^i=klqbp
A.A.A.A.REMOVE ALL EXISTING S.A. / E.A DUCTWORK, S.A. / REMOVE ALL EXISTING S.A. / E.A DUCTWORK, S.A. / REMOVE ALL EXISTING S.A. / E.A DUCTWORK, S.A. / REMOVE ALL EXISTING S.A. / E.A DUCTWORK, S.A. /
R.A. / E.A. DIFFUSERS / GRILLES, CONTROLS, R.A. / E.A. DIFFUSERS / GRILLES, CONTROLS, R.A. / E.A. DIFFUSERS / GRILLES, CONTROLS, R.A. / E.A. DIFFUSERS / GRILLES, CONTROLS,
SENSORS, VAV REHEAT BOXES AND ASSOCIATED SENSORS, VAV REHEAT BOXES AND ASSOCIATED SENSORS, VAV REHEAT BOXES AND ASSOCIATED SENSORS, VAV REHEAT BOXES AND ASSOCIATED
HEATING WATER BRANCH PIPING, VALVES, HEATING WATER BRANCH PIPING, VALVES, HEATING WATER BRANCH PIPING, VALVES, HEATING WATER BRANCH PIPING, VALVES,
STRAINER, ETC. UNLESS OTHERWISE NOTED. STRAINER, ETC. UNLESS OTHERWISE NOTED. STRAINER, ETC. UNLESS OTHERWISE NOTED. STRAINER, ETC. UNLESS OTHERWISE NOTED.
REFERENCE MECHANICAL PIPING DEMOLITION REFERENCE MECHANICAL PIPING DEMOLITION REFERENCE MECHANICAL PIPING DEMOLITION REFERENCE MECHANICAL PIPING DEMOLITION
PLANS.PLANS.PLANS.PLANS.
FIELD VERIFY EXACT LOCATIONS OF EXISTING FIELD VERIFY EXACT LOCATIONS OF EXISTING FIELD VERIFY EXACT LOCATIONS OF EXISTING FIELD VERIFY EXACT LOCATIONS OF EXISTING
PIPING, DUCTWORK, EQUIPMENT, ETC. PIPING, DUCTWORK, EQUIPMENT, ETC. PIPING, DUCTWORK, EQUIPMENT, ETC. PIPING, DUCTWORK, EQUIPMENT, ETC.
DEMOLITION FLOOR PLANS HAVE BEEN CREATED DEMOLITION FLOOR PLANS HAVE BEEN CREATED DEMOLITION FLOOR PLANS HAVE BEEN CREATED DEMOLITION FLOOR PLANS HAVE BEEN CREATED
USING AVAILABLE RECORD DRAWINGS. USING AVAILABLE RECORD DRAWINGS. USING AVAILABLE RECORD DRAWINGS. USING AVAILABLE RECORD DRAWINGS.
CONTRACTOR SHALL BE RESPONSIBLE FOR CONTRACTOR SHALL BE RESPONSIBLE FOR CONTRACTOR SHALL BE RESPONSIBLE FOR CONTRACTOR SHALL BE RESPONSIBLE FOR
VERIFYING EXACT ROUTING OF ALL PIPING, VERIFYING EXACT ROUTING OF ALL PIPING, VERIFYING EXACT ROUTING OF ALL PIPING, VERIFYING EXACT ROUTING OF ALL PIPING,
DUCTWORK, ETC. DURING CONSTRUCTION. DUCTWORK, ETC. DURING CONSTRUCTION. DUCTWORK, ETC. DURING CONSTRUCTION. DUCTWORK, ETC. DURING CONSTRUCTION.
DEMOLITION OF EXISTING MECHANICAL AND DEMOLITION OF EXISTING MECHANICAL AND DEMOLITION OF EXISTING MECHANICAL AND DEMOLITION OF EXISTING MECHANICAL AND
PLUMBING CONSTRUCTION SHALL BE TO THE PLUMBING CONSTRUCTION SHALL BE TO THE PLUMBING CONSTRUCTION SHALL BE TO THE PLUMBING CONSTRUCTION SHALL BE TO THE
EXTENT REQUIRED TO ACCOMMODATE THE EXTENT REQUIRED TO ACCOMMODATE THE EXTENT REQUIRED TO ACCOMMODATE THE EXTENT REQUIRED TO ACCOMMODATE THE
RENOVATION AND THE ADDITION OF NEW WORK. RENOVATION AND THE ADDITION OF NEW WORK. RENOVATION AND THE ADDITION OF NEW WORK. RENOVATION AND THE ADDITION OF NEW WORK.
REFERENCE ARCHITECTURAL DEMOLITION REFERENCE ARCHITECTURAL DEMOLITION REFERENCE ARCHITECTURAL DEMOLITION REFERENCE ARCHITECTURAL DEMOLITION
DRAWINGS TO COORDINATE AND VERIFY THE DRAWINGS TO COORDINATE AND VERIFY THE DRAWINGS TO COORDINATE AND VERIFY THE DRAWINGS TO COORDINATE AND VERIFY THE
EXTENT OF THE DEMOLITION WORK REQUIRED. EXTENT OF THE DEMOLITION WORK REQUIRED. EXTENT OF THE DEMOLITION WORK REQUIRED. EXTENT OF THE DEMOLITION WORK REQUIRED.
ALL PIPING, DUCTWORK, ETC. TO REMAIN SHALL BE ALL PIPING, DUCTWORK, ETC. TO REMAIN SHALL BE ALL PIPING, DUCTWORK, ETC. TO REMAIN SHALL BE ALL PIPING, DUCTWORK, ETC. TO REMAIN SHALL BE
PROTECTED THROUGHOUT THE CONSTRUCTION PROTECTED THROUGHOUT THE CONSTRUCTION PROTECTED THROUGHOUT THE CONSTRUCTION PROTECTED THROUGHOUT THE CONSTRUCTION
PERIOD. PERIOD. PERIOD. PERIOD.
PROVIDE AND INSTALL CAPS ON EXISTING MAIN PROVIDE AND INSTALL CAPS ON EXISTING MAIN PROVIDE AND INSTALL CAPS ON EXISTING MAIN PROVIDE AND INSTALL CAPS ON EXISTING MAIN
DUCTWORK AND / OR PIPING BRANCH BEING DUCTWORK AND / OR PIPING BRANCH BEING DUCTWORK AND / OR PIPING BRANCH BEING DUCTWORK AND / OR PIPING BRANCH BEING
REMOVED. REFERENCE ARCHITECTURAL FOR REMOVED. REFERENCE ARCHITECTURAL FOR REMOVED. REFERENCE ARCHITECTURAL FOR REMOVED. REFERENCE ARCHITECTURAL FOR
PATCHWORK. PATCHWORK. PATCHWORK. PATCHWORK.
INDICATED DEMOLITION OF PIPING AND DUCTWORK INDICATED DEMOLITION OF PIPING AND DUCTWORK INDICATED DEMOLITION OF PIPING AND DUCTWORK INDICATED DEMOLITION OF PIPING AND DUCTWORK
INCLUDES, BUT IS NOT LIMITED TO, THE REMOVAL INCLUDES, BUT IS NOT LIMITED TO, THE REMOVAL INCLUDES, BUT IS NOT LIMITED TO, THE REMOVAL INCLUDES, BUT IS NOT LIMITED TO, THE REMOVAL
OF DUCTWORK, PIPING, FITTINGS, VALVES, OF DUCTWORK, PIPING, FITTINGS, VALVES, OF DUCTWORK, PIPING, FITTINGS, VALVES, OF DUCTWORK, PIPING, FITTINGS, VALVES,
HANGERS, SUPPORTS, INSULATION, ETC. UNLESS HANGERS, SUPPORTS, INSULATION, ETC. UNLESS HANGERS, SUPPORTS, INSULATION, ETC. UNLESS HANGERS, SUPPORTS, INSULATION, ETC. UNLESS
NOTED OTHERWISE. NOTED OTHERWISE. NOTED OTHERWISE. NOTED OTHERWISE.
INDICATED DEMOLITION OF MECHANICAL INDICATED DEMOLITION OF MECHANICAL INDICATED DEMOLITION OF MECHANICAL INDICATED DEMOLITION OF MECHANICAL
EQUIPMENT INCLUDES, BUT IS NOT LIMITED TO, EQUIPMENT INCLUDES, BUT IS NOT LIMITED TO, EQUIPMENT INCLUDES, BUT IS NOT LIMITED TO, EQUIPMENT INCLUDES, BUT IS NOT LIMITED TO,
THE REMOVAL OF EQUIPMENT, PIPING, VALVES, THE REMOVAL OF EQUIPMENT, PIPING, VALVES, THE REMOVAL OF EQUIPMENT, PIPING, VALVES, THE REMOVAL OF EQUIPMENT, PIPING, VALVES,
INSULATION, SEISMIC BRACING, CONTROLS, INSULATION, SEISMIC BRACING, CONTROLS, INSULATION, SEISMIC BRACING, CONTROLS, INSULATION, SEISMIC BRACING, CONTROLS,
ELECTRICAL, ETC. UNLESS NOTED OTHERWISE. ELECTRICAL, ETC. UNLESS NOTED OTHERWISE. ELECTRICAL, ETC. UNLESS NOTED OTHERWISE. ELECTRICAL, ETC. UNLESS NOTED OTHERWISE.
FIELD VERIFY EXACT LOCATIONS OF FIELD VERIFY EXACT LOCATIONS OF FIELD VERIFY EXACT LOCATIONS OF FIELD VERIFY EXACT LOCATIONS OF
THERMOSTATS, SENSOR AND CONTROLLING THERMOSTATS, SENSOR AND CONTROLLING THERMOSTATS, SENSOR AND CONTROLLING THERMOSTATS, SENSOR AND CONTROLLING
UNITS. UNITS. UNITS. UNITS.
CONTRACTOR SHALL BE RESPONSIBLE FOR CONTRACTOR SHALL BE RESPONSIBLE FOR CONTRACTOR SHALL BE RESPONSIBLE FOR CONTRACTOR SHALL BE RESPONSIBLE FOR
PATCHING AND REPAIRING ANY DAMAGE CAUSED PATCHING AND REPAIRING ANY DAMAGE CAUSED PATCHING AND REPAIRING ANY DAMAGE CAUSED PATCHING AND REPAIRING ANY DAMAGE CAUSED
BY HIS / HER PERSONNEL TO EXISTING THAT IS TO BY HIS / HER PERSONNEL TO EXISTING THAT IS TO BY HIS / HER PERSONNEL TO EXISTING THAT IS TO BY HIS / HER PERSONNEL TO EXISTING THAT IS TO
REMAIN OR TO NEWLY INSTALLED BUILDING REMAIN OR TO NEWLY INSTALLED BUILDING REMAIN OR TO NEWLY INSTALLED BUILDING REMAIN OR TO NEWLY INSTALLED BUILDING
COMPONENTS. COMPONENTS. COMPONENTS. COMPONENTS.
PATCH AND SEAL ALL ABANDONED OPENINGS PATCH AND SEAL ALL ABANDONED OPENINGS PATCH AND SEAL ALL ABANDONED OPENINGS PATCH AND SEAL ALL ABANDONED OPENINGS
THROUGH WALLS AND FLOORS. MATCH EXISTING THROUGH WALLS AND FLOORS. MATCH EXISTING THROUGH WALLS AND FLOORS. MATCH EXISTING THROUGH WALLS AND FLOORS. MATCH EXISTING
SURROUNDING FINISH. SURROUNDING FINISH. SURROUNDING FINISH. SURROUNDING FINISH.
CONTRACTOR SHALL REPLACE ANY INSULATION CONTRACTOR SHALL REPLACE ANY INSULATION CONTRACTOR SHALL REPLACE ANY INSULATION CONTRACTOR SHALL REPLACE ANY INSULATION
THAT IS DAMAGED DURING CONSTRUCTION ON THAT IS DAMAGED DURING CONSTRUCTION ON THAT IS DAMAGED DURING CONSTRUCTION ON THAT IS DAMAGED DURING CONSTRUCTION ON
PIPE OR DUCTWORK THAT IS TO REMAIN. PIPE OR DUCTWORK THAT IS TO REMAIN. PIPE OR DUCTWORK THAT IS TO REMAIN. PIPE OR DUCTWORK THAT IS TO REMAIN.
PRIOR TO DEMOLITION OF ANY EQUIPMENT WORK PRIOR TO DEMOLITION OF ANY EQUIPMENT WORK PRIOR TO DEMOLITION OF ANY EQUIPMENT WORK PRIOR TO DEMOLITION OF ANY EQUIPMENT WORK
WITH ELECTRICAL CONTRACTOR AND CONTROLS WITH ELECTRICAL CONTRACTOR AND CONTROLS WITH ELECTRICAL CONTRACTOR AND CONTROLS WITH ELECTRICAL CONTRACTOR AND CONTROLS
CONTRACTOR TO MAKE CERTAIN POWER AND CONTRACTOR TO MAKE CERTAIN POWER AND CONTRACTOR TO MAKE CERTAIN POWER AND CONTRACTOR TO MAKE CERTAIN POWER AND
CONTROLS ARE PROPERLY DISCONNECTED AND CONTROLS ARE PROPERLY DISCONNECTED AND CONTROLS ARE PROPERLY DISCONNECTED AND CONTROLS ARE PROPERLY DISCONNECTED AND
TERMINATED.TERMINATED.TERMINATED.TERMINATED.
B.B.B.B.
C.C.C.C.
D.D.D.D.
E.E.E.E.
F.F.F.F.
G.G.G.G.
H.H.H.H.
I.I.I.I.
J.J.J.J.
K.K.K.K.
L.L.L.L.
M.M.M.M.
N.N.N.N.
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
Enlarged
Level 01 Area
B Mechanical
Room
Demolition
Plan
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
SCALE:SCALE:SCALE:SCALE:MD402MD402MD402MD402 1/4" = 1'1/4" = 1'1/4" = 1'1/4" = 1'----0"0"0"0"
bki^odba=ibsbi=N=^ob^=_=jb`e^kf`^i=ollj=abjlifqflk=mi^k1111
00002.52.52.52.55555 5555 10101010
ao^tfkd=klqbp
NOTE
#DESCRIPTION
1111 REMOVE EXISTING DUCTWORK AS SHOWN.REMOVE EXISTING DUCTWORK AS SHOWN.REMOVE EXISTING DUCTWORK AS SHOWN.REMOVE EXISTING DUCTWORK AS SHOWN.
2222 REMOVE EXISTING VAV REHEAT BOX ANDREMOVE EXISTING VAV REHEAT BOX ANDREMOVE EXISTING VAV REHEAT BOX ANDREMOVE EXISTING VAV REHEAT BOX AND
ASSOCIATED DUCTWORK.ASSOCIATED DUCTWORK.ASSOCIATED DUCTWORK.ASSOCIATED DUCTWORK.
3333 REMOVE PORTION OF EXISTING SNOWMELTREMOVE PORTION OF EXISTING SNOWMELTREMOVE PORTION OF EXISTING SNOWMELTREMOVE PORTION OF EXISTING SNOWMELT
HEATING WATER SUPPLY/RETURN PIPING ASHEATING WATER SUPPLY/RETURN PIPING ASHEATING WATER SUPPLY/RETURN PIPING ASHEATING WATER SUPPLY/RETURN PIPING AS
SHOWN.SHOWN.SHOWN.SHOWN.
KEY PLAN
A
B
1111
GGGG
JJJJ
LLLL
MMMM
NNNN
PPPP
QQQQ
EEEE
CCCC
2222 3333 4444 5555
013
BREAK ROOM
026A
OFFICE
010
OFFICE
011
OFFICE
016
TIER 2
(E) AIR HANDLING UNIT
18"Ø18"Ø18"Ø18"Ø
18"Ø18"Ø18"Ø18"Ø
12"Ø12"Ø12"Ø12"Ø
013013013013
VAVRVAVRVAVRVAVR8"Ø8"Ø8"Ø8"Ø
10
"
x
8
"
+
1
"
A
L
10
"
x
8
"
+
1
"
A
L
10
"
x
8
"
+
1
"
A
L
10
"
x
8
"
+
1
"
A
L
015015015015
VAVRVAVRVAVRVAVR
8"Ø8"Ø8"Ø8"Ø
10"x10"+1"AL10"x10"+1"AL10"x10"+1"AL10"x10"+1"AL
12"Ø12"Ø12"Ø12"Ø
016016016016
VAVRVAVRVAVRVAVR
14"x12"+1"AL14"x12"+1"AL14"x12"+1"AL14"x12"+1"AL
8"x6"+1"AL8"x6"+1"AL8"x6"+1"AL8"x6"+1"AL
018018018018
VAVRVAVRVAVRVAVR
6"Ø6"Ø6"Ø6"Ø
8"x6"+1"AL8"x6"+1"AL8"x6"+1"AL8"x6"+1"AL
040040040040
VAVVAVVAVVAV
6"
Ø
6"
Ø
6"
Ø
6"
Ø
8"x6"+1"AL8"x6"+1"AL8"x6"+1"AL8"x6"+1"AL
010010010010
VAVRVAVRVAVRVAVR
6"Ø6"Ø6"Ø6"Ø
6"x8"+1"AL6"x8"+1"AL6"x8"+1"AL6"x8"+1"AL
011011011011
VAVRVAVRVAVRVAVR
8"x6"+1"AL8"x6"+1"AL8"x6"+1"AL8"x6"+1"AL
012012012012
VAVRVAVRVAVRVAVR6"Ø6"Ø6"Ø6"Ø
012
OFFICE
028
SHORT
TERM
STORAGE
026B
OFFICE026C
OFFICE
026D
OFFICE026E
OFFICE
026F
STUDENTS
024
TECH
ROOM
022
OPS
020
OFFICE
018
OFFICE
015
MEN'S
RR
014
WOMEN'S
RR
040
BDF
009
IMAGING
AND
STORAGE
14"Ø14"Ø14"Ø14"Ø 6"Ø6"Ø6"Ø6"Ø
12"Ø12"Ø12"Ø12"Ø
009009009009
VAVRVAVRVAVRVAVR
14"x12"+1"AL14"x12"+1"AL14"x12"+1"AL14"x12"+1"AL
8"x6"+1"AL8"x6"+1"AL8"x6"+1"AL8"x6"+1"AL
026A026A026A026A
VAVRVAVRVAVRVAVR
6"Ø6"Ø6"Ø6"Ø
8"x6"+1"AL8"x6"+1"AL8"x6"+1"AL8"x6"+1"AL
026B026B026B026B
VAVRVAVRVAVRVAVR
6"
Ø
6"
Ø
6"
Ø
6"
Ø
8"x6"+1"AL8"x6"+1"AL8"x6"+1"AL8"x6"+1"AL
026C026C026C026C
VAVRVAVRVAVRVAVR
6"Ø6"Ø6"Ø6"Ø
8"x6"+1"AL8"x6"+1"AL8"x6"+1"AL8"x6"+1"AL
026D026D026D026D
VAVRVAVRVAVRVAVR
6"Ø6"Ø6"Ø6"Ø
8"x6"+1"AL8"x6"+1"AL8"x6"+1"AL8"x6"+1"AL
026E026E026E026E
VAVRVAVRVAVRVAVR
026F026F026F026F
VAVRVAVRVAVRVAVR
8"Ø8"Ø8"Ø8"Ø
10"x8"+1"AL10"x8"+1"AL10"x8"+1"AL10"x8"+1"AL
024024024024
VAVRVAVRVAVRVAVR
8"Ø8"Ø8"Ø8"Ø
10"x8"+1"AL10"x8"+1"AL10"x8"+1"AL10"x8"+1"AL
12"Ø12"Ø12"Ø12"Ø
022022022022
VAVRVAVRVAVRVAVR
14"x12"+1"AL14"x12"+1"AL14"x12"+1"AL14"x12"+1"AL
8"x6"+1"AL8"x6"+1"AL8"x6"+1"AL8"x6"+1"AL
020020020020
VAVRVAVRVAVRVAVR
6"Ø6"Ø6"Ø6"Ø
022A022A022A022A
VAVRVAVRVAVRVAVR
10"Ø10"Ø10"Ø10"Ø
12"x10"+1"AL12"x10"+1"AL12"x10"+1"AL12"x10"+1"AL
022A
QA
10"Ø10"Ø10"Ø10"Ø
18"x8"+1"AL18"x8"+1"AL18"x8"+1"AL18"x8"+1"AL
001001001001
VAVRVAVRVAVRVAVR
62"Ø62"Ø62"Ø62"Ø
54"x68"F.O.54"x68"F.O.54"x68"F.O.54"x68"F.O.
1111
2222
3333
4444
5555 6666
7777
8888
9999
10101010
11111111
12121212
13131313
14141414
11111111
15151515
14141414
11111111
12121212 12121212
3333 3333 3333
3333
3333
3333
3333
3333
3333
3333
2222
2222
2222
3333
H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
8"Ø8"Ø8"Ø8"Ø
1111
8"Ø8"Ø8"Ø8"Ø
6"Ø6"Ø6"Ø6"Ø
6"Ø6"Ø6"Ø6"Ø H.D.H.D.H.D.H.D.
4444
3333
H.D.H.D.H.D.H.D. H.D.H.D.H.D.H.D.
6"Ø6"Ø6"Ø6"Ø
6"Ø6"Ø6"Ø6"Ø
4444
H.D.H.D.H.D.H.D.
6"Ø6"Ø6"Ø6"Ø
4444
H.D.H.D.H.D.H.D.
6"Ø6"Ø6"Ø6"Ø
4444
6"Ø6"Ø6"Ø6"Ø
H.D.H.D.H.D.H.D. H.D.H.D.H.D.H.D.
6"Ø6"Ø6"Ø6"Ø
6666
6"Ø6"Ø6"Ø6"Ø
H.D.H.D.H.D.H.D.H.D.H.D.H.D.H.D. H.D.H.D.H.D.H.D.
8"Ø8"Ø8"Ø8"Ø8"Ø8"Ø8"Ø8"Ø
5555
4444
H.D.H.D.H.D.H.D.6"Ø6"Ø6"Ø6"Ø
8"x6"+1"AL8"x6"+1"AL8"x6"+1"AL8"x6"+1"AL
0000----CCCC
VAVRVAVRVAVRVAVR
0-C
HALL
6"Ø6"Ø6"Ø6"Ø
H.D.H.D.H.D.H.D.H.D.H.D.H.D.H.D.H.D.H.D.H.D.H.D.H.D.H.D.H.D.H.D.
8"Ø8"Ø8"Ø8"Ø
8"Ø8"Ø8"Ø8"Ø
8888
8888
8"Ø8"Ø8"Ø8"Ø8"Ø8"Ø8"Ø8"Ø
8"Ø8"Ø8"Ø8"Ø
8"Ø8"Ø8"Ø8"Ø
8888
8888
3333
H.D.H.D.H.D.H.D.
6"
Ø
6"
Ø
6"
Ø
6"
Ø
4444
13131313
H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.10"Ø10"Ø10"Ø10"Ø
10
"
Ø
10
"
Ø
10
"
Ø
10
"
Ø
H.D.H.D.H.D.H.D. H.D.H.D.H.D.H.D. H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
6"Ø6"Ø6"Ø6"Ø
4444
9999
9999
10"Ø10"Ø10"Ø10"Ø 10"Ø10"Ø10"Ø10"Ø
10"Ø10"Ø10"Ø10"Ø
8"Ø8"Ø8"Ø8"Ø
H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
8"Ø8"Ø8"Ø8"Ø8"Ø8"Ø8"Ø8"Ø
10101010
3333
18181818
19191919
20202020
22222222
23232323
24242424
16161616
25252525
26262626
17171717
18"x8" EXH.18"x8" EXH.18"x8" EXH.18"x8" EXH.
12121212
17171717
555519191919
22222222
19191919
19191919
19191919 19191919
19191919
19191919
19191919 19191919
19191919
6"x6" EXH.6"x6" EXH.6"x6" EXH.6"x6" EXH.
6"x6" EXH.6"x6" EXH.6"x6" EXH.6"x6" EXH.
54"x68" F.O.54"x68" F.O.54"x68" F.O.54"x68" F.O.
MH401MH401MH401MH401
1111
27272727
21212121
8"Ø8"Ø8"Ø8"Ø
24242424
19191919
040040040040
SACSACSACSAC
LVTLVTLVTLVT
002002002002
VAVRVAVRVAVRVAVR
27272727
LVTLVTLVTLVT
040040040040
SCUSCUSCUSCU
8"Ø8"Ø8"Ø8"Ø
H.D.H.D.H.D.H.D.
28282828
dbkbo^i=klqbp
A.A.A.A.WHERE UNISTRUTS ARE NOT LOCATED NOR WHERE UNISTRUTS ARE NOT LOCATED NOR WHERE UNISTRUTS ARE NOT LOCATED NOR WHERE UNISTRUTS ARE NOT LOCATED NOR
ACCESSIBLE IN THE BOTTOM OF STRUCTURAL ACCESSIBLE IN THE BOTTOM OF STRUCTURAL ACCESSIBLE IN THE BOTTOM OF STRUCTURAL ACCESSIBLE IN THE BOTTOM OF STRUCTURAL
CONCRETE WEBS, ALL ANCHORS AND SUPPORTS CONCRETE WEBS, ALL ANCHORS AND SUPPORTS CONCRETE WEBS, ALL ANCHORS AND SUPPORTS CONCRETE WEBS, ALL ANCHORS AND SUPPORTS
SHALL BE CONNECTED TO THE SIDES OF THE WEBS. SHALL BE CONNECTED TO THE SIDES OF THE WEBS. SHALL BE CONNECTED TO THE SIDES OF THE WEBS. SHALL BE CONNECTED TO THE SIDES OF THE WEBS.
DO NOT ATTACH TO THE BOTTOM OF THE WEB IF DO NOT ATTACH TO THE BOTTOM OF THE WEB IF DO NOT ATTACH TO THE BOTTOM OF THE WEB IF DO NOT ATTACH TO THE BOTTOM OF THE WEB IF
THERE IS NO EXISTING UNISTRUT.THERE IS NO EXISTING UNISTRUT.THERE IS NO EXISTING UNISTRUT.THERE IS NO EXISTING UNISTRUT.
R.A. OPENINGS WITH SOUND BOOTS DO NOT NEED R.A. OPENINGS WITH SOUND BOOTS DO NOT NEED R.A. OPENINGS WITH SOUND BOOTS DO NOT NEED R.A. OPENINGS WITH SOUND BOOTS DO NOT NEED
TO BE INSTALLED IF THE WALL IN WHICH THEY ARE TO BE INSTALLED IF THE WALL IN WHICH THEY ARE TO BE INSTALLED IF THE WALL IN WHICH THEY ARE TO BE INSTALLED IF THE WALL IN WHICH THEY ARE
LOCATED, IS BETWEEN STRUCTURAL WEBS, AND LOCATED, IS BETWEEN STRUCTURAL WEBS, AND LOCATED, IS BETWEEN STRUCTURAL WEBS, AND LOCATED, IS BETWEEN STRUCTURAL WEBS, AND
THERE ARE OPENINGS, OF TOTAL AREA EQUAL TO OR THERE ARE OPENINGS, OF TOTAL AREA EQUAL TO OR THERE ARE OPENINGS, OF TOTAL AREA EQUAL TO OR THERE ARE OPENINGS, OF TOTAL AREA EQUAL TO OR
GREATER THAN THAT OF THE SOUND BOOT, INTO THE GREATER THAN THAT OF THE SOUND BOOT, INTO THE GREATER THAN THAT OF THE SOUND BOOT, INTO THE GREATER THAN THAT OF THE SOUND BOOT, INTO THE
STRUCTURAL PAN TO ALLOW AIR TO FLOW INTO THE STRUCTURAL PAN TO ALLOW AIR TO FLOW INTO THE STRUCTURAL PAN TO ALLOW AIR TO FLOW INTO THE STRUCTURAL PAN TO ALLOW AIR TO FLOW INTO THE
ADJACENT CEILING SPACE. CONTRACTOR TO ADJACENT CEILING SPACE. CONTRACTOR TO ADJACENT CEILING SPACE. CONTRACTOR TO ADJACENT CEILING SPACE. CONTRACTOR TO
PROVIDE CREDIT FOR SOUND BOOTS THAT WERE PROVIDE CREDIT FOR SOUND BOOTS THAT WERE PROVIDE CREDIT FOR SOUND BOOTS THAT WERE PROVIDE CREDIT FOR SOUND BOOTS THAT WERE
DEEMED UNNECESSARY.DEEMED UNNECESSARY.DEEMED UNNECESSARY.DEEMED UNNECESSARY.
B.B.B.B.
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
Level 00 Area
A Mechanical
Remodel Plan
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
KEY PLAN
A
B
ao^tfkd=klqbp
0000555510101010 10101010 20202020
NOTE
#
DIFFUSER
CALLOUT DESCRIPTION
1111 S-1S-1S-1S-1 160 CFM, 8"Ø NK S.A. DIFFUSER160 CFM, 8"Ø NK S.A. DIFFUSER160 CFM, 8"Ø NK S.A. DIFFUSER160 CFM, 8"Ø NK S.A. DIFFUSER
2222 R-1R-1R-1R-1 22"x22" NK R.A. GRILLE W/ SOUND22"x22" NK R.A. GRILLE W/ SOUND22"x22" NK R.A. GRILLE W/ SOUND22"x22" NK R.A. GRILLE W/ SOUND
BOOTBOOTBOOTBOOT
3333 R-1R-1R-1R-1 22"x10" NK R.A. GRILLE W/ SOUND22"x10" NK R.A. GRILLE W/ SOUND22"x10" NK R.A. GRILLE W/ SOUND22"x10" NK R.A. GRILLE W/ SOUND
BOOTBOOTBOOTBOOT
4444 S-1S-1S-1S-1 100 CFM, 6"Ø NK S.A. DIFFUSER100 CFM, 6"Ø NK S.A. DIFFUSER100 CFM, 6"Ø NK S.A. DIFFUSER100 CFM, 6"Ø NK S.A. DIFFUSER
5555 S-1S-1S-1S-1 150 CFM, 8"Ø NK S.A. DIFFUSER150 CFM, 8"Ø NK S.A. DIFFUSER150 CFM, 8"Ø NK S.A. DIFFUSER150 CFM, 8"Ø NK S.A. DIFFUSER
6666 S-1S-1S-1S-1 105 CFM, 6"Ø NK S.A. DIFFUSER105 CFM, 6"Ø NK S.A. DIFFUSER105 CFM, 6"Ø NK S.A. DIFFUSER105 CFM, 6"Ø NK S.A. DIFFUSER
7777 S-1S-1S-1S-1 50 CFM, 6"Ø NK S.A. DIFFUSER50 CFM, 6"Ø NK S.A. DIFFUSER50 CFM, 6"Ø NK S.A. DIFFUSER50 CFM, 6"Ø NK S.A. DIFFUSER
8888 S-1S-1S-1S-1 210 CFM, 8"Ø NK S.A. DIFFUSER210 CFM, 8"Ø NK S.A. DIFFUSER210 CFM, 8"Ø NK S.A. DIFFUSER210 CFM, 8"Ø NK S.A. DIFFUSER
9999 S-1S-1S-1S-1 315 CFM, 10"Ø NK S.A. DIFFUSER315 CFM, 10"Ø NK S.A. DIFFUSER315 CFM, 10"Ø NK S.A. DIFFUSER315 CFM, 10"Ø NK S.A. DIFFUSER
10101010 S-1S-1S-1S-1 155 CFM, 8"Ø NK S.A. DIFFUSER155 CFM, 8"Ø NK S.A. DIFFUSER155 CFM, 8"Ø NK S.A. DIFFUSER155 CFM, 8"Ø NK S.A. DIFFUSER
11111111 BALANCE EXISTING SUPPLY AIRBALANCE EXISTING SUPPLY AIRBALANCE EXISTING SUPPLY AIRBALANCE EXISTING SUPPLY AIR
DIFFUSER TO 200 CFM.DIFFUSER TO 200 CFM.DIFFUSER TO 200 CFM.DIFFUSER TO 200 CFM.
12121212 BALANCE EXISTING SUPPLY AIRBALANCE EXISTING SUPPLY AIRBALANCE EXISTING SUPPLY AIRBALANCE EXISTING SUPPLY AIR
DIFFUSER TO 150 CFM.DIFFUSER TO 150 CFM.DIFFUSER TO 150 CFM.DIFFUSER TO 150 CFM.
13131313 S-1S-1S-1S-1 255 CFM, 10"Ø NK S.A. DIFFUSER255 CFM, 10"Ø NK S.A. DIFFUSER255 CFM, 10"Ø NK S.A. DIFFUSER255 CFM, 10"Ø NK S.A. DIFFUSER
14141414 BALANCE EXISTING SUPPLY AIRBALANCE EXISTING SUPPLY AIRBALANCE EXISTING SUPPLY AIRBALANCE EXISTING SUPPLY AIR
DIFFUSER TO 500 CFM.DIFFUSER TO 500 CFM.DIFFUSER TO 500 CFM.DIFFUSER TO 500 CFM.
15151515 BALANCE EXISTING SUPPLY AIRBALANCE EXISTING SUPPLY AIRBALANCE EXISTING SUPPLY AIRBALANCE EXISTING SUPPLY AIR
DIFFUSER TO 50 CFM.DIFFUSER TO 50 CFM.DIFFUSER TO 50 CFM.DIFFUSER TO 50 CFM.
16161616 RISE 18"x8" E.A. DUCT TO LEVELRISE 18"x8" E.A. DUCT TO LEVELRISE 18"x8" E.A. DUCT TO LEVELRISE 18"x8" E.A. DUCT TO LEVEL
ABOVE.ABOVE.ABOVE.ABOVE.
17171717 BALANCE EXISTING EXHAUST AIRBALANCE EXISTING EXHAUST AIRBALANCE EXISTING EXHAUST AIRBALANCE EXISTING EXHAUST AIR
GRILLE TO 100 CFM.GRILLE TO 100 CFM.GRILLE TO 100 CFM.GRILLE TO 100 CFM.
18181818 E-1E-1E-1E-1 100 CFM, 6"x6" NK E.A. GRILLE100 CFM, 6"x6" NK E.A. GRILLE100 CFM, 6"x6" NK E.A. GRILLE100 CFM, 6"x6" NK E.A. GRILLE
19191919 12"x12"+1"AL R.A. OPENING W/12"x12"+1"AL R.A. OPENING W/12"x12"+1"AL R.A. OPENING W/12"x12"+1"AL R.A. OPENING W/
SOUND BOOT ABOVE CEILING.SOUND BOOT ABOVE CEILING.SOUND BOOT ABOVE CEILING.SOUND BOOT ABOVE CEILING.
20202020 56"x24" R.A. OPENING IN WALL ABOVE56"x24" R.A. OPENING IN WALL ABOVE56"x24" R.A. OPENING IN WALL ABOVE56"x24" R.A. OPENING IN WALL ABOVE
CEILING.CEILING.CEILING.CEILING.
21212121 BALANCE EXISTING SUPPLY AIR GRILLEBALANCE EXISTING SUPPLY AIR GRILLEBALANCE EXISTING SUPPLY AIR GRILLEBALANCE EXISTING SUPPLY AIR GRILLE
TO 500 CFM.TO 500 CFM.TO 500 CFM.TO 500 CFM.
22222222 16"x16"+1"AL R.A. OPENING W/16"x16"+1"AL R.A. OPENING W/16"x16"+1"AL R.A. OPENING W/16"x16"+1"AL R.A. OPENING W/
SOUND BOOT ABOVE CEILING.SOUND BOOT ABOVE CEILING.SOUND BOOT ABOVE CEILING.SOUND BOOT ABOVE CEILING.
23232323 22"x22"+1"AL R.A. OPENING W/22"x22"+1"AL R.A. OPENING W/22"x22"+1"AL R.A. OPENING W/22"x22"+1"AL R.A. OPENING W/
SOUND BOOT ABOVE CEILING.SOUND BOOT ABOVE CEILING.SOUND BOOT ABOVE CEILING.SOUND BOOT ABOVE CEILING.
24242424 18"x18"+1"AL R.A. OPENING W/18"x18"+1"AL R.A. OPENING W/18"x18"+1"AL R.A. OPENING W/18"x18"+1"AL R.A. OPENING W/
SOUND BOOT ABOVE CEILING.SOUND BOOT ABOVE CEILING.SOUND BOOT ABOVE CEILING.SOUND BOOT ABOVE CEILING.
25252525 BALANCE EXISTING EXHAUST AIRBALANCE EXISTING EXHAUST AIRBALANCE EXISTING EXHAUST AIRBALANCE EXISTING EXHAUST AIR
GRILLE TO 150 CFM.GRILLE TO 150 CFM.GRILLE TO 150 CFM.GRILLE TO 150 CFM.
26262626 BALANCE EXISTING EXHAUST AIRBALANCE EXISTING EXHAUST AIRBALANCE EXISTING EXHAUST AIRBALANCE EXISTING EXHAUST AIR
GRILLE TO 300 CFM.GRILLE TO 300 CFM.GRILLE TO 300 CFM.GRILLE TO 300 CFM.
27272727 SAW CUT WALL FOR NEW DUCTWORKSAW CUT WALL FOR NEW DUCTWORKSAW CUT WALL FOR NEW DUCTWORKSAW CUT WALL FOR NEW DUCTWORK
PENETRATIONS. FIRE-SMOKE DAMPERPENETRATIONS. FIRE-SMOKE DAMPERPENETRATIONS. FIRE-SMOKE DAMPERPENETRATIONS. FIRE-SMOKE DAMPER
REQUIRED FOR EACH PENETRATION INREQUIRED FOR EACH PENETRATION INREQUIRED FOR EACH PENETRATION INREQUIRED FOR EACH PENETRATION IN
THIS WALL.THIS WALL.THIS WALL.THIS WALL.
28282828 SCU-040 TO BE LOCATED IN FENCEDSCU-040 TO BE LOCATED IN FENCEDSCU-040 TO BE LOCATED IN FENCEDSCU-040 TO BE LOCATED IN FENCED
AREA WITH THE ICE BANKS.AREA WITH THE ICE BANKS.AREA WITH THE ICE BANKS.AREA WITH THE ICE BANKS.
COORDINATE EXACT LOCATION TOCOORDINATE EXACT LOCATION TOCOORDINATE EXACT LOCATION TOCOORDINATE EXACT LOCATION TO
ACCOMMODATE UNIT CLEARANCES.ACCOMMODATE UNIT CLEARANCES.ACCOMMODATE UNIT CLEARANCES.ACCOMMODATE UNIT CLEARANCES.
SCALE:SCALE:SCALE:SCALE:MH100aMH100aMH100aMH100a 1/8" = 1'1/8" = 1'1/8" = 1'1/8" = 1'----0"0"0"0"
ibsbi=MM=^ob^=^=jb`e^kf`^i=objlabi=mi^k1111
1111
GGGG
JJJJ
LLLL
MMMM
NNNN
PPPP
QQQQ
EEEE
CCCC
2222 3333 4444 5555
142
BREAKROOM
140
CONFERENCE ROOM
138
OFFICE
136
OFFICE
134
RECEPTION
132
STUDY (MED)
131
OFFICE
130
OFFICE
129
OFFICE
128
STUDY (SM)
127
STUDY (SM)
126
STUDY (SM)
125
STUDY (MED)
124
STUDY (MED)
146
MENS
148
WOMENS
144
FAMILY RR
147
JANITORS OFFICE
122
HD BOOK COLLECTION
122A
OPEN STUDY
108
OFFICE
114
INTER LIBRARY LOAN WORKSPACE
110
CIRCULATION RECEPTION
122C
OPEN STUDY
122B
OPEN STUDY
1-F
VESTIBULE
120A
OPEN STUDY
24"x14"F.O.24"x14"F.O.24"x14"F.O.24"x14"F.O.
40
"
x
2
0
"
F
.
O
.
40
"
x
2
0
"
F
.
O
.
40
"
x
2
0
"
F
.
O
.
40
"
x
2
0
"
F
.
O
.
32
"
x
1
6
"
F
.
O
.
32
"
x
1
6
"
F
.
O
.
32
"
x
1
6
"
F
.
O
.
32
"
x
1
6
"
F
.
O
.
40
"
x
2
0
"
F
.
O
.
40
"
x
2
0
"
F
.
O
.
40
"
x
2
0
"
F
.
O
.
40
"
x
2
0
"
F
.
O
.
16"Ø16"Ø16"Ø16"Ø
24"x18"F.O.24"x18"F.O.24"x18"F.O.24"x18"F.O.
26"x10" EXH.26"x10" EXH.26"x10" EXH.26"x10" EXH.
3333
CHCHCHCH
2222
CHCHCHCH
8"Ø8"Ø8"Ø8"Ø
6"Ø6"Ø6"Ø6"Ø
8"x8"+1"AL8"x8"+1"AL8"x8"+1"AL8"x8"+1"AL
10"x10"+1"AL10"x10"+1"AL10"x10"+1"AL10"x10"+1"AL
125125125125
VAVRVAVRVAVRVAVR
126126126126
VAVRVAVRVAVRVAVR
12"x12"+1"AL12"x12"+1"AL12"x12"+1"AL12"x12"+1"AL
124124124124
VAVRVAVRVAVRVAVR
6"Ø6"Ø6"Ø6"Ø
8"x8"+1"AL8"x8"+1"AL8"x8"+1"AL8"x8"+1"AL
128128128128
VAVRVAVRVAVRVAVR
6"Ø6"Ø6"Ø6"Ø
8"x8"+1"AL8"x8"+1"AL8"x8"+1"AL8"x8"+1"AL
127127127127
VAVRVAVRVAVRVAVR
10"x10"+1"AL10"x10"+1"AL10"x10"+1"AL10"x10"+1"AL
129129129129
VAVRVAVRVAVRVAVR
8"Ø8"Ø8"Ø8"Ø
6"
Ø
6"
Ø
6"
Ø
6"
Ø
8"x10"+1"AL8"x10"+1"AL8"x10"+1"AL8"x10"+1"AL
131131131131
VAVRVAVRVAVRVAVR
8"x10"+1"AL8"x10"+1"AL8"x10"+1"AL8"x10"+1"AL
132132132132
VAVRVAVRVAVRVAVR
8"Ø8"Ø8"Ø8"Ø
16"x12"+1"AL16"x12"+1"AL16"x12"+1"AL16"x12"+1"AL
130130130130
VAVRVAVRVAVRVAVR
16"x14"+1"AL16"x14"+1"AL16"x14"+1"AL16"x14"+1"AL
122AA122AA122AA122AA
VAVRVAVRVAVRVAVR
14"Ø14"Ø14"Ø14"Ø
10"Ø10"Ø10"Ø10"Ø
140140140140
VAVRVAVRVAVRVAVR
14"x12"+1"AL14"x12"+1"AL14"x12"+1"AL14"x12"+1"AL
10"x10"+1"AL10"x10"+1"AL10"x10"+1"AL10"x10"+1"AL
142142142142
VAVRVAVRVAVRVAVR
8"x8"+1"AL8"x8"+1"AL8"x8"+1"AL8"x8"+1"AL
134134134134
VAVRVAVRVAVRVAVR
8"
Ø
8"
Ø
8"
Ø
8"
Ø
8"x10"+1"AL8"x10"+1"AL8"x10"+1"AL8"x10"+1"AL
146146146146
VAVRVAVRVAVRVAVR
8"Ø8"Ø8"Ø8"Ø
8"x10"+1"AL8"x10"+1"AL8"x10"+1"AL8"x10"+1"AL
148148148148
VAVRVAVRVAVRVAVR
10"Ø10"Ø10"Ø10"Ø
122B122B122B122B
VAVRVAVRVAVRVAVR
12"x10"+1"AL12"x10"+1"AL12"x10"+1"AL12"x10"+1"AL
10
"
Ø
10
"
Ø
10
"
Ø
10
"
Ø
138138138138
VAVRVAVRVAVRVAVR
12"x10"+1"AL12"x10"+1"AL12"x10"+1"AL12"x10"+1"AL
136136136136
VAVRVAVRVAVRVAVR
14"x10"+1"AL14"x10"+1"AL14"x10"+1"AL14"x10"+1"AL
12"Ø12"Ø12"Ø12"Ø
120AB120AB120AB120AB
VAVRVAVRVAVRVAVR
12"x12"+1"AL12"x12"+1"AL12"x12"+1"AL12"x12"+1"AL14"Ø14"Ø14"Ø14"Ø
120AA120AA120AA120AA
VAVRVAVRVAVRVAVR
20"x16"+1"AL20"x16"+1"AL20"x16"+1"AL20"x16"+1"AL 16"Ø16"Ø16"Ø16"Ø
118
OPEN STUDY
118B118B118B118B
VAVRVAVRVAVRVAVR
20"x16"+1"AL20"x16"+1"AL20"x16"+1"AL20"x16"+1"AL
118A118A118A118A
VAVRVAVRVAVRVAVR
10"x10"+1"AL10"x10"+1"AL10"x10"+1"AL10"x10"+1"AL
110110110110
VAVRVAVRVAVRVAVR
20"x16"+1"AL20"x16"+1"AL20"x16"+1"AL20"x16"+1"AL
18"Ø18"Ø18"Ø18"Ø
100B100B100B100B
VAVRVAVRVAVRVAVR
100
OPEN STUDY
20"x16"+1"AL20"x16"+1"AL20"x16"+1"AL20"x16"+1"AL
100A100A100A100A
VAVRVAVRVAVRVAVR
106
OFFICE
104
OFFICE
102
ELEC ROOM
1-C
HALLWAY
1-D
STAIR
112
CHECK-IN
116
RESERVE MEDIA
114A
OFFICE
6"
Ø
6"
Ø
6"
Ø
6"
Ø
8"x6"+1"AL8"x6"+1"AL8"x6"+1"AL8"x6"+1"AL
104104104104
VAVRVAVRVAVRVAVR
6"
Ø
6"
Ø
6"
Ø
6"
Ø
8"x6"+1"AL8"x6"+1"AL8"x6"+1"AL8"x6"+1"AL 106106106106
VAVRVAVRVAVRVAVR
6"
Ø
6"
Ø
6"
Ø
6"
Ø
8"x6"+1"AL8"x6"+1"AL8"x6"+1"AL8"x6"+1"AL
108108108108
VAVRVAVRVAVRVAVR
6"
Ø
6"
Ø
6"
Ø
6"
Ø
6"x8"+1"AL6"x8"+1"AL6"x8"+1"AL6"x8"+1"AL
112112112112
VAVRVAVRVAVRVAVR
6"x8"+1"AL6"x8"+1"AL6"x8"+1"AL6"x8"+1"AL
114114114114
VAVRVAVRVAVRVAVR
6"
Ø
6"
Ø
6"
Ø
6"
Ø
6"x8"+1"AL6"x8"+1"AL6"x8"+1"AL6"x8"+1"AL
114A114A114A114A
VAVRVAVRVAVRVAVR
1-B
STAIR
1111
CHCHCHCH
150
READING 18"x12"+1"AL18"x12"+1"AL18"x12"+1"AL18"x12"+1"AL
18"x12"+1"AL18"x12"+1"AL18"x12"+1"AL18"x12"+1"AL
150B150B150B150B
VAVRVAVRVAVRVAVR
150A150A150A150A
VAVRVAVRVAVRVAVR
1111
2222
3333
4444
5555
6666
7777
8888
9999
10101010
11111111
12121212
13131313
14141414
15151515
16161616
18181818
19191919
20"x14"+1"AL20"x14"+1"AL20"x14"+1"AL20"x14"+1"AL
122AE122AE122AE122AE
VAVRVAVRVAVRVAVR
16"Ø16"Ø16"Ø16"Ø
50"x24"F.O.50"x24"F.O.50"x24"F.O.50"x24"F.O.
50"x24"F.O.50"x24"F.O.50"x24"F.O.50"x24"F.O.
20202020
21212121
22222222
23232323 24242424
25252525
26262626
27272727
28282828
31313131
32323232
33333333
30303030
18
"
Ø
18
"
Ø
18
"
Ø
18
"
Ø
10"Ø10"Ø10"Ø10"Ø
2222
10"Ø10"Ø10"Ø10"Ø
H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D. H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
10"Ø10"Ø10"Ø10"Ø
10"Ø10"Ø10"Ø10"Ø
H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
10"Ø10"Ø10"Ø10"Ø
H.D.H.D.H.D.H.D. H.D.H.D.H.D.H.D.
19191919 19191919
19191919 19191919 19191919
19191919 19191919 1919191910"Ø10"Ø10"Ø10"Ø
10"Ø10"Ø10"Ø10"Ø
10"Ø10"Ø10"Ø10"Ø
H.D.H.D.H.D.H.D.H.D.H.D.H.D.H.D.10"Ø10"Ø10"Ø10"ØH.D.H.D.H.D.H.D.
19191919 19191919 19191919
10"Ø10"Ø10"Ø10"Ø
10"Ø10"Ø10"Ø10"Ø 10"Ø10"Ø10"Ø10"Ø
10"Ø10"Ø10"Ø10"Ø
19191919 19191919 19191919
19191919 19191919 19191919
2222
22222222 2222
H.D.H.D.H.D.H.D.
6"Ø6"Ø6"Ø6"Ø
H.
D
.
H.
D
.
H.
D
.
H.
D
.
6"Ø6"Ø6"Ø6"Ø 9999
3333
6"Ø6"Ø6"Ø6"Ø
9999
H.D.H.D.H.D.H.D.
3333
8"Ø8"Ø8"Ø8"Ø
H.D.H.D.H.D.H.D. H.D.H.D.H.D.H.D. H.D.H.D.H.D.H.D.H.
D
.
H.
D
.
H.
D
.
H.
D
.
H.
D
.
H.
D
.
H.
D
.
H.
D
.
H.D.H.D.H.D.H.D.H.D.H.D.H.D.H.D.
8"Ø8"Ø8"Ø8"Ø
H.
D
.
H.
D
.
H.
D
.
H.
D
.
3333
8"Ø8"Ø8"Ø8"Ø
6"Ø6"Ø6"Ø6"Ø
H.D.H.D.H.D.H.D.
8"Ø8"Ø8"Ø8"Ø
H.D.H.D.H.D.H.D.
6"Ø6"Ø6"Ø6"Ø
8"Ø8"Ø8"Ø8"Ø
H.D.H.D.H.D.H.D.
3333
H.D.H.D.H.D.H.D.
10"Ø10"Ø10"Ø10"Ø
H.D.H.D.H.D.H.D.
36"x8" EXH.36"x8" EXH.36"x8" EXH.36"x8" EXH.
12"Ø12"Ø12"Ø12"Ø
26"x10" EXH.26"x10" EXH.26"x10" EXH.26"x10" EXH.
10
"
Ø
10
"
Ø
10
"
Ø
10
"
Ø
6"Ø6"Ø6"Ø6"Ø
12"Ø12"Ø12"Ø12"Ø8"Ø8"Ø8"Ø8"Ø
32323232
32323232
32323232
H.D.H.D.H.D.H.D. H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.H.
D
.
H.
D
.
H.
D
.
H.
D
.
H.
D
.
H.
D
.
H.
D
.
H.
D
.
H.
D
.
H.
D
.
H.
D
.
H.
D
.
8"Ø8"Ø8"Ø8"Ø
31313131
12"x8"+1"AL12"x8"+1"AL12"x8"+1"AL12"x8"+1"AL12"x8"+1"AL12"x8"+1"AL12"x8"+1"AL12"x8"+1"AL
12"x8"+1"AL12"x8"+1"AL12"x8"+1"AL12"x8"+1"AL12"x8"+1"AL12"x8"+1"AL12"x8"+1"AL12"x8"+1"AL
32323232
32323232
32323232
32323232
32323232 32323232
16"x14"+1"AL16"x14"+1"AL16"x14"+1"AL16"x14"+1"AL
122AC122AC122AC122AC
VAVRVAVRVAVRVAVR14"Ø14"Ø14"Ø14"Ø
16"x14"+1"AL16"x14"+1"AL16"x14"+1"AL16"x14"+1"AL
14"Ø14"Ø14"Ø14"Ø
122AB122AB122AB122AB
VAVRVAVRVAVRVAVR
H.D.H.D.H.D.H.D. H.D.H.D.H.D.H.D.
12"x8"+1"AL12"x8"+1"AL12"x8"+1"AL12"x8"+1"AL12"x8"+1"AL12"x8"+1"AL12"x8"+1"AL12"x8"+1"AL
H.D.H.D.H.D.H.D.
12"x8"+1"AL12"x8"+1"AL12"x8"+1"AL12"x8"+1"AL
H.D.H.D.H.D.H.D.
12"x8"+1"AL12"x8"+1"AL12"x8"+1"AL12"x8"+1"AL
12"x8"+1"AL12"x8"+1"AL12"x8"+1"AL12"x8"+1"AL12"x8"+1"AL12"x8"+1"AL12"x8"+1"AL12"x8"+1"AL
32323232 12"x8"+1"AL12"x8"+1"AL12"x8"+1"AL12"x8"+1"AL
H.D.H.D.H.D.H.D.
3232323212"x8"+1"AL12"x8"+1"AL12"x8"+1"AL12"x8"+1"AL
H.D.H.D.H.D.H.D.
31313131
31313131
8"Ø8"Ø8"Ø8"ØH.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
31313131
8"Ø8"Ø8"Ø8"Ø
H.D.H.D.H.D.H.D.H.D.H.D.H.D.H.D.
8"Ø8"Ø8"Ø8"Ø
H.D.H.D.H.D.H.D.
2222
2222
16
"
x
1
4
"
+
1
"
A
L
16
"
x
1
4
"
+
1
"
A
L
16
"
x
1
4
"
+
1
"
A
L
16
"
x
1
4
"
+
1
"
A
L
H.D.H.D.H.D.H.D.
10"Ø10"Ø10"Ø10"Ø
18181818
H.D.H.D.H.D.H.D.
10"Ø10"Ø10"Ø10"Ø
12"x12"+1"AL12"x12"+1"AL12"x12"+1"AL12"x12"+1"AL
1818181810"Ø10"Ø10"Ø10"Ø
H.D.H.D.H.D.H.D.
H.
D
.
H.
D
.
H.
D
.
H.
D
.
26262626
26262626
H.
D
.
H.
D
.
H.
D
.
H.
D
.
H.
D
.
H.
D
.
H.
D
.
H.
D
.
H.
D
.
H.
D
.
H.
D
.
H.
D
.
16
"
x
1
4
"
+
1
"
A
L
16
"
x
1
4
"
+
1
"
A
L
16
"
x
1
4
"
+
1
"
A
L
16
"
x
1
4
"
+
1
"
A
L
10"Ø10"Ø10"Ø10"Ø
10"Ø10"Ø10"Ø10"Ø
12"x12"+1"AL12"x12"+1"AL12"x12"+1"AL12"x12"+1"AL
10"Ø10"Ø10"Ø10"Ø
16"Ø16"Ø16"Ø16"Ø
26262626
26262626
26262626
18181818
18181818
18181818
2222
2222
2222
14"x10"+1"AL14"x10"+1"AL14"x10"+1"AL14"x10"+1"AL
14"x10"+1"AL14"x10"+1"AL14"x10"+1"AL14"x10"+1"AL
14"x10"+1"AL14"x10"+1"AL14"x10"+1"AL14"x10"+1"AL
14"x10"+1"AL14"x10"+1"AL14"x10"+1"AL14"x10"+1"AL14"x10"+1"AL14"x10"+1"AL14"x10"+1"AL14"x10"+1"AL
14"x10"+1"AL14"x10"+1"AL14"x10"+1"AL14"x10"+1"AL
H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
H.
D
.
H.
D
.
H.
D
.
H.
D
.
H.
D
.
H.
D
.
H.
D
.
H.
D
.
2222
14"x14"+1"AL14"x14"+1"AL14"x14"+1"AL14"x14"+1"AL
23232323 23232323
H.D.H.D.H.D.H.D. H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
18"x12"+1"AL18"x12"+1"AL18"x12"+1"AL18"x12"+1"AL18"x12"+1"AL18"x12"+1"AL18"x12"+1"AL18"x12"+1"AL
18"x12"+1"AL18"x12"+1"AL18"x12"+1"AL18"x12"+1"AL
2424242424242424
12"x8"+1"AL12"x8"+1"AL12"x8"+1"AL12"x8"+1"AL12"x8"+1"AL12"x8"+1"AL12"x8"+1"AL12"x8"+1"AL
H.D.H.D.H.D.H.D. H.D.H.D.H.D.H.D. H.D.H.D.H.D.H.D.
12"x8"+1"AL12"x8"+1"AL12"x8"+1"AL12"x8"+1"AL
24242424
12"x8"+1"AL12"x8"+1"AL12"x8"+1"AL12"x8"+1"AL
H.D.H.D.H.D.H.D.
24242424
12"x8"+1"AL12"x8"+1"AL12"x8"+1"AL12"x8"+1"AL
H.D.H.D.H.D.H.D.
10"Ø10"Ø10"Ø10"Ø
122AD122AD122AD122AD
VAVRVAVRVAVRVAVR
2222
2222
2222 2222 2222 2222
222214"x10"+1"AL14"x10"+1"AL14"x10"+1"AL14"x10"+1"AL
10"x10"+1"AL10"x10"+1"AL10"x10"+1"AL10"x10"+1"AL
10"x8"+1"AL10"x8"+1"AL10"x8"+1"AL10"x8"+1"AL
10
"
Ø
10
"
Ø
10
"
Ø
10
"
Ø
6"Ø6"Ø6"Ø6"Ø
H.D.H.D.H.D.H.D.
10101010
6"Ø6"Ø6"Ø6"Ø
H.D.H.D.H.D.H.D.
6"Ø6"Ø6"Ø6"Ø
10101010
10101010
6"Ø6"Ø6"Ø6"Ø
H.D.H.D.H.D.H.D.
10101010
6"Ø6"Ø6"Ø6"Ø
H.D.H.D.H.D.H.D.
10101010
6"Ø6"Ø6"Ø6"Ø
10101010
H.D.H.D.H.D.H.D.
6"Ø6"Ø6"Ø6"ØH.D.H.D.H.D.H.D.
10101010
10"x8"+1"AL10"x8"+1"AL10"x8"+1"AL10"x8"+1"AL
6"Ø6"Ø6"Ø6"Ø
10101010
6"Ø6"Ø6"Ø6"Ø
10101010
6"Ø6"Ø6"Ø6"Ø
H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
10101010
10"x8"+1"AL10"x8"+1"AL10"x8"+1"AL10"x8"+1"AL
6"Ø6"Ø6"Ø6"Ø
10101010
6"Ø6"Ø6"Ø6"Ø
H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
6"Ø6"Ø6"Ø6"Ø
10101010H.D.H.D.H.D.H.D.
10"x10"+1"AL10"x10"+1"AL10"x10"+1"AL10"x10"+1"AL
10101010
6"Ø6"Ø6"Ø6"Ø H.D.H.D.H.D.H.D.
10101010
6"Ø6"Ø6"Ø6"Ø
H.D.H.D.H.D.H.D.
10101010 H.D.H.D.H.D.H.D.
10101010 H.D.H.D.H.D.H.D.
6"Ø6"Ø6"Ø6"Ø
6"Ø6"Ø6"Ø6"Ø
10"x10"+1"AL10"x10"+1"AL10"x10"+1"AL10"x10"+1"AL
6"Ø6"Ø6"Ø6"Ø H.D.H.D.H.D.H.D.
6"Ø6"Ø6"Ø6"Ø
H.D.H.D.H.D.H.D.
10101010
10101010
6"Ø6"Ø6"Ø6"Ø
10101010
H.D.H.D.H.D.H.D.
6"Ø6"Ø6"Ø6"Ø
10101010
H.D.H.D.H.D.H.D.
8"Ø8"Ø8"Ø8"Ø
H.D.H.D.H.D.H.D.
8"Ø8"Ø8"Ø8"Ø
H.D.H.D.H.D.H.D.
8"Ø8"Ø8"Ø8"Ø
8"Ø8"Ø8"Ø8"Ø
H.D.H.D.H.D.H.D. H.D.H.D.H.D.H.D.
11111111
11111111
11111111
29292929
2222 2222
2222 2222
2222
10"Ø10"Ø10"Ø10"Ø
10"Ø10"Ø10"Ø10"Ø
20202020
H.D.H.D.H.D.H.D.
H.
D
.
H.
D
.
H.
D
.
H.
D
.
10"Ø10"Ø10"Ø10"Ø
8"Ø8"Ø8"Ø8"Ø
H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
55558"Ø8"Ø8"Ø8"Ø
H.D.H.D.H.D.H.D.
5555
8"Ø8"Ø8"Ø8"Ø
H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
12"Ø12"Ø12"Ø12"Ø
12"Ø12"Ø12"Ø12"Ø
1111
H.D.H.D.H.D.H.D.H.
D
.
H.
D
.
H.
D
.
H.
D
.
2222
3333
3333
3333
3333
3333
3333 3333
H.D.H.D.H.D.H.D.
10"Ø10"Ø10"Ø10"Ø10"Ø10"Ø10"Ø10"Ø
H.D.H.D.H.D.H.D.
2222
8"Ø8"Ø8"Ø8"Ø
H.D.H.D.H.D.H.D.
11111111
8"Ø8"Ø8"Ø8"Ø
11111111
H.D.H.D.H.D.H.D.
8"Ø8"Ø8"Ø8"Ø
11111111
H.D.H.D.H.D.H.D.
3333
8"Ø8"Ø8"Ø8"Ø
3333
10"Ø10"Ø10"Ø10"Ø
2222
10"Ø10"Ø10"Ø10"Ø
13131313
H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
2222
H.D.H.D.H.D.H.D.H.D.H.D.H.D.H.D.
12121212
10"Ø10"Ø10"Ø10"Ø
10"Ø10"Ø10"Ø10"Ø
2222
8"Ø8"Ø8"Ø8"Ø
11111111
8"Ø8"Ø8"Ø8"Ø
11111111
H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
8"Ø8"Ø8"Ø8"Ø
8"Ø8"Ø8"Ø8"Ø
11111111 11111111
H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
8"Ø8"Ø8"Ø8"Ø
8"Ø8"Ø8"Ø8"Ø
11111111 11111111
H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
6"Ø6"Ø6"Ø6"Ø
H.D.H.D.H.D.H.D.
10"Ø10"Ø10"Ø10"Ø
10"Ø10"Ø10"Ø10"Ø
H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
30303030
30303030
10"Ø10"Ø10"Ø10"Ø
10"Ø10"Ø10"Ø10"Ø
H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
30303030
30303030
10"Ø10"Ø10"Ø10"Ø
10"Ø10"Ø10"Ø10"Ø
H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
30303030
30303030
10"Ø10"Ø10"Ø10"Ø
10"Ø10"Ø10"Ø10"Ø
H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
30303030
2222 2222 2222
35353535
36363636
37373737
38383838
39393939
40404040
41414141
42424242
43434343
44444444
45454545
46464646
47474747
48484848
47474747
17171717
26
"
x
1
0
"
E
X
H
.
26
"
x
1
0
"
E
X
H
.
26
"
x
1
0
"
E
X
H
.
26
"
x
1
0
"
E
X
H
.
8"x8" EXH.8"x8" EXH.8"x8" EXH.8"x8" EXH.
6"x6" EXH.6"x6" EXH.6"x6" EXH.6"x6" EXH.
49494949
6"x6" EXH.6"x6" EXH.6"x6" EXH.6"x6" EXH.
3737373736363636
20"x12" EXH.20"x12" EXH.20"x12" EXH.20"x12" EXH.
A.D.A.D.A.D.A.D.
A.
D
.
A.
D
.
A.
D
.
A.
D
.
39393939
38383838
10"Ø10"Ø10"Ø10"Ø
36363636
36363636
36363636
36363636
36363636
37373737
A.D.A.D.A.D.A.D.
10"Ø10"Ø10"Ø10"Ø
10"Ø10"Ø10"Ø10"Ø
H.
D
.
H.
D
.
H.
D
.
H.
D
.
10"Ø10"Ø10"Ø10"Ø
8"x6"+1"AL8"x6"+1"AL8"x6"+1"AL8"x6"+1"AL
102102102102
VAVVAVVAVVAV
36363636
36363636
36363636
36363636
36363636
38383838
3333
1111
FCUFCUFCUFCU
20"x12"+1"AL20"x12"+1"AL20"x12"+1"AL20"x12"+1"AL
H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
10"Ø10"Ø10"Ø10"Ø
10"Ø10"Ø10"Ø10"Ø
12121212
12121212H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
10"Ø10"Ø10"Ø10"Ø
10"Ø10"Ø10"Ø10"Ø
12121212
12121212
20
"
x
1
0
"
+
1
"
A
L
20
"
x
1
0
"
+
1
"
A
L
20
"
x
1
0
"
+
1
"
A
L
20
"
x
1
0
"
+
1
"
A
L
50505050
51515151
LVTLVTLVTLVT
LVTLVTLVTLVT
8"Ø8"Ø8"Ø8"Ø8"Ø8"Ø8"Ø8"Ø
H.D.H.D.H.D.H.D.
25252525
2222 2222
8"Ø8"Ø8"Ø8"Ø
8"Ø8"Ø8"Ø8"Ø
8"Ø8"Ø8"Ø8"Ø31313131
H.D.H.D.H.D.H.D.
14"x14"+1"AL14"x14"+1"AL14"x14"+1"AL14"x14"+1"AL
10"x10"+1"AL10"x10"+1"AL10"x10"+1"AL10"x10"+1"AL
10"Ø10"Ø10"Ø10"Ø
52525252
52525252
47474747
47474747
H.D.H.D.H.D.H.D.
dbkbo^i=klqbp
A.A.A.A.WHERE UNISTRUTS ARE NOT LOCATED NOR WHERE UNISTRUTS ARE NOT LOCATED NOR WHERE UNISTRUTS ARE NOT LOCATED NOR WHERE UNISTRUTS ARE NOT LOCATED NOR
ACCESSIBLE IN THE BOTTOM OF STRUCTURAL ACCESSIBLE IN THE BOTTOM OF STRUCTURAL ACCESSIBLE IN THE BOTTOM OF STRUCTURAL ACCESSIBLE IN THE BOTTOM OF STRUCTURAL
CONCRETE WEBS, ALL ANCHORS AND SUPPORTS CONCRETE WEBS, ALL ANCHORS AND SUPPORTS CONCRETE WEBS, ALL ANCHORS AND SUPPORTS CONCRETE WEBS, ALL ANCHORS AND SUPPORTS
SHALL BE CONNECTED TO THE SIDES OF THE WEBS. SHALL BE CONNECTED TO THE SIDES OF THE WEBS. SHALL BE CONNECTED TO THE SIDES OF THE WEBS. SHALL BE CONNECTED TO THE SIDES OF THE WEBS.
DO NOT ATTACH TO THE BOTTOM OF THE WEB IF DO NOT ATTACH TO THE BOTTOM OF THE WEB IF DO NOT ATTACH TO THE BOTTOM OF THE WEB IF DO NOT ATTACH TO THE BOTTOM OF THE WEB IF
THERE IS NO EXISTING UNISTRUT.THERE IS NO EXISTING UNISTRUT.THERE IS NO EXISTING UNISTRUT.THERE IS NO EXISTING UNISTRUT.
R.A. OPENINGS WITH SOUND BOOTS DO NOT NEED R.A. OPENINGS WITH SOUND BOOTS DO NOT NEED R.A. OPENINGS WITH SOUND BOOTS DO NOT NEED R.A. OPENINGS WITH SOUND BOOTS DO NOT NEED
TO BE INSTALLED IF THE WALL IN WHICH THEY ARE TO BE INSTALLED IF THE WALL IN WHICH THEY ARE TO BE INSTALLED IF THE WALL IN WHICH THEY ARE TO BE INSTALLED IF THE WALL IN WHICH THEY ARE
LOCATED, IS BETWEEN STRUCTURAL WEBS, AND LOCATED, IS BETWEEN STRUCTURAL WEBS, AND LOCATED, IS BETWEEN STRUCTURAL WEBS, AND LOCATED, IS BETWEEN STRUCTURAL WEBS, AND
THERE ARE OPENINGS, OF TOTAL AREA EQUAL TO OR THERE ARE OPENINGS, OF TOTAL AREA EQUAL TO OR THERE ARE OPENINGS, OF TOTAL AREA EQUAL TO OR THERE ARE OPENINGS, OF TOTAL AREA EQUAL TO OR
GREATER THAN THAT OF THE SOUND BOOT, INTO THE GREATER THAN THAT OF THE SOUND BOOT, INTO THE GREATER THAN THAT OF THE SOUND BOOT, INTO THE GREATER THAN THAT OF THE SOUND BOOT, INTO THE
STRUCTURAL PAN TO ALLOW AIR TO FLOW INTO THE STRUCTURAL PAN TO ALLOW AIR TO FLOW INTO THE STRUCTURAL PAN TO ALLOW AIR TO FLOW INTO THE STRUCTURAL PAN TO ALLOW AIR TO FLOW INTO THE
ADJACENT CEILING SPACE. CONTRACTOR TO ADJACENT CEILING SPACE. CONTRACTOR TO ADJACENT CEILING SPACE. CONTRACTOR TO ADJACENT CEILING SPACE. CONTRACTOR TO
PROVIDE CREDIT FOR SOUND BOOTS THAT WERE PROVIDE CREDIT FOR SOUND BOOTS THAT WERE PROVIDE CREDIT FOR SOUND BOOTS THAT WERE PROVIDE CREDIT FOR SOUND BOOTS THAT WERE
DEEMED UNNECESSARY.DEEMED UNNECESSARY.DEEMED UNNECESSARY.DEEMED UNNECESSARY.
B.B.B.B.
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
Level 01 Area
A Mechanical
Remodel Plan
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
KEY PLAN
A
B
ao^tfkd=klqbp
0000555510101010 10101010 20202020
NOTE
#
DIFFUSER
CALLOUT DESCRIPTION
1111 S-1S-1S-1S-1 505 CFM, 12"Ø NK S.A. DIFFUSER505 CFM, 12"Ø NK S.A. DIFFUSER505 CFM, 12"Ø NK S.A. DIFFUSER505 CFM, 12"Ø NK S.A. DIFFUSER
2222 R-1R-1R-1R-1 22"x22" NK R.A. GRILLE W/ SOUND22"x22" NK R.A. GRILLE W/ SOUND22"x22" NK R.A. GRILLE W/ SOUND22"x22" NK R.A. GRILLE W/ SOUND
BOOTBOOTBOOTBOOT
3333 R-1R-1R-1R-1 22"x10" NK R.A. GRILLE W/ SOUND22"x10" NK R.A. GRILLE W/ SOUND22"x10" NK R.A. GRILLE W/ SOUND22"x10" NK R.A. GRILLE W/ SOUND
BOOTBOOTBOOTBOOT
4444 S-1S-1S-1S-1 415 CFM, 10"Ø NK S.A. DIFFUSER415 CFM, 10"Ø NK S.A. DIFFUSER415 CFM, 10"Ø NK S.A. DIFFUSER415 CFM, 10"Ø NK S.A. DIFFUSER
5555 S-1S-1S-1S-1 165 CFM, 8"Ø NK S.A. DIFFUSER165 CFM, 8"Ø NK S.A. DIFFUSER165 CFM, 8"Ø NK S.A. DIFFUSER165 CFM, 8"Ø NK S.A. DIFFUSER
6666 S-1S-1S-1S-1 240 CFM, 10"Ø NK S.A. DIFFUSER240 CFM, 10"Ø NK S.A. DIFFUSER240 CFM, 10"Ø NK S.A. DIFFUSER240 CFM, 10"Ø NK S.A. DIFFUSER
7777 S-1S-1S-1S-1 320 CFM, 10"Ø NK S.A. DIFFUSER320 CFM, 10"Ø NK S.A. DIFFUSER320 CFM, 10"Ø NK S.A. DIFFUSER320 CFM, 10"Ø NK S.A. DIFFUSER
8888 S-1S-1S-1S-1 325 CFM, 10"Ø NK S.A. DIFFUSER325 CFM, 10"Ø NK S.A. DIFFUSER325 CFM, 10"Ø NK S.A. DIFFUSER325 CFM, 10"Ø NK S.A. DIFFUSER
9999 S-1S-1S-1S-1 105 CFM, 6"Ø NK S.A. DIFFUSER105 CFM, 6"Ø NK S.A. DIFFUSER105 CFM, 6"Ø NK S.A. DIFFUSER105 CFM, 6"Ø NK S.A. DIFFUSER
10101010 S-1S-1S-1S-1 100 CFM, 6"Ø NK S.A. DIFFUSER100 CFM, 6"Ø NK S.A. DIFFUSER100 CFM, 6"Ø NK S.A. DIFFUSER100 CFM, 6"Ø NK S.A. DIFFUSER
11111111 S-1S-1S-1S-1 140 CFM, 8"Ø NK S.A. DIFFUSER140 CFM, 8"Ø NK S.A. DIFFUSER140 CFM, 8"Ø NK S.A. DIFFUSER140 CFM, 8"Ø NK S.A. DIFFUSER
12121212 S-1S-1S-1S-1 300 CFM, 10"Ø NK S.A. DIFFUSER300 CFM, 10"Ø NK S.A. DIFFUSER300 CFM, 10"Ø NK S.A. DIFFUSER300 CFM, 10"Ø NK S.A. DIFFUSER
13131313 S-1S-1S-1S-1 335 CFM, 10"Ø NK S.A. DIFFUSER335 CFM, 10"Ø NK S.A. DIFFUSER335 CFM, 10"Ø NK S.A. DIFFUSER335 CFM, 10"Ø NK S.A. DIFFUSER
14141414 S-1S-1S-1S-1 180 CFM, 8"Ø NK S.A. DIFFUSER180 CFM, 8"Ø NK S.A. DIFFUSER180 CFM, 8"Ø NK S.A. DIFFUSER180 CFM, 8"Ø NK S.A. DIFFUSER
15151515 S-2S-2S-2S-2 100 CFM, 6"Ø NK S.A. DIFFUSER100 CFM, 6"Ø NK S.A. DIFFUSER100 CFM, 6"Ø NK S.A. DIFFUSER100 CFM, 6"Ø NK S.A. DIFFUSER
16161616 S-2S-2S-2S-2 250 CFM, 10"Ø NK S.A. DIFFUSER250 CFM, 10"Ø NK S.A. DIFFUSER250 CFM, 10"Ø NK S.A. DIFFUSER250 CFM, 10"Ø NK S.A. DIFFUSER
17171717 S-2S-2S-2S-2 350 CFM, 10"Ø NK S.A. DIFFUSER350 CFM, 10"Ø NK S.A. DIFFUSER350 CFM, 10"Ø NK S.A. DIFFUSER350 CFM, 10"Ø NK S.A. DIFFUSER
18181818 S-1S-1S-1S-1 340 CFM, 10"Ø NK S.A. DIFFUSER340 CFM, 10"Ø NK S.A. DIFFUSER340 CFM, 10"Ø NK S.A. DIFFUSER340 CFM, 10"Ø NK S.A. DIFFUSER
19191919 S-1S-1S-1S-1 235 CFM, 10"Ø NK S.A. DIFFUSER235 CFM, 10"Ø NK S.A. DIFFUSER235 CFM, 10"Ø NK S.A. DIFFUSER235 CFM, 10"Ø NK S.A. DIFFUSER
20202020 S-1S-1S-1S-1 385 CFM, 10"Ø NK S.A. DIFFUSER385 CFM, 10"Ø NK S.A. DIFFUSER385 CFM, 10"Ø NK S.A. DIFFUSER385 CFM, 10"Ø NK S.A. DIFFUSER
21212121 S-1S-1S-1S-1 145 CFM, 8"Ø NK S.A. DIFFUSER145 CFM, 8"Ø NK S.A. DIFFUSER145 CFM, 8"Ø NK S.A. DIFFUSER145 CFM, 8"Ø NK S.A. DIFFUSER
22222222 S-1S-1S-1S-1 50 CFM, 6"Ø NK S.A. DIFFUSER50 CFM, 6"Ø NK S.A. DIFFUSER50 CFM, 6"Ø NK S.A. DIFFUSER50 CFM, 6"Ø NK S.A. DIFFUSER
23232323 S-3S-3S-3S-3 415 CFM, 18"x12" NK S.A. DIFFUSER415 CFM, 18"x12" NK S.A. DIFFUSER415 CFM, 18"x12" NK S.A. DIFFUSER415 CFM, 18"x12" NK S.A. DIFFUSER
24242424 S-3S-3S-3S-3 210 CFM, 12"x8" NK S.A. DIFFUSER210 CFM, 12"x8" NK S.A. DIFFUSER210 CFM, 12"x8" NK S.A. DIFFUSER210 CFM, 12"x8" NK S.A. DIFFUSER
25252525 S-4S-4S-4S-4 145 CFM, 4'-0" x 2 SLOT S.A.145 CFM, 4'-0" x 2 SLOT S.A.145 CFM, 4'-0" x 2 SLOT S.A.145 CFM, 4'-0" x 2 SLOT S.A.
DIFFUSERDIFFUSERDIFFUSERDIFFUSER
26262626 S-3S-3S-3S-3 340 CFM, 14"x10" NK S.A. DIFFUSER340 CFM, 14"x10" NK S.A. DIFFUSER340 CFM, 14"x10" NK S.A. DIFFUSER340 CFM, 14"x10" NK S.A. DIFFUSER
27272727 S-1S-1S-1S-1 150 CFM, 8"Ø NK S.A. DIFFUSER150 CFM, 8"Ø NK S.A. DIFFUSER150 CFM, 8"Ø NK S.A. DIFFUSER150 CFM, 8"Ø NK S.A. DIFFUSER
28282828 S-1S-1S-1S-1 125 CFM, 8"Ø NK S.A. DIFFUSER125 CFM, 8"Ø NK S.A. DIFFUSER125 CFM, 8"Ø NK S.A. DIFFUSER125 CFM, 8"Ø NK S.A. DIFFUSER
29292929 S-1S-1S-1S-1 195 CFM, 8"Ø NK S.A. DIFFUSER195 CFM, 8"Ø NK S.A. DIFFUSER195 CFM, 8"Ø NK S.A. DIFFUSER195 CFM, 8"Ø NK S.A. DIFFUSER
30303030 S-1S-1S-1S-1 350 CFM, 10"Ø NK S.A. DIFFUSER350 CFM, 10"Ø NK S.A. DIFFUSER350 CFM, 10"Ø NK S.A. DIFFUSER350 CFM, 10"Ø NK S.A. DIFFUSER
31313131 S-1S-1S-1S-1 220 CFM, 8"Ø NK S.A. DIFFUSER220 CFM, 8"Ø NK S.A. DIFFUSER220 CFM, 8"Ø NK S.A. DIFFUSER220 CFM, 8"Ø NK S.A. DIFFUSER
32323232 S-3S-3S-3S-3 220 CFM, 12"x8" NK S.A. DIFFUSER220 CFM, 12"x8" NK S.A. DIFFUSER220 CFM, 12"x8" NK S.A. DIFFUSER220 CFM, 12"x8" NK S.A. DIFFUSER
33333333 S-1S-1S-1S-1 165 CFM, 8"Ø NK S.A. DIFFUSER165 CFM, 8"Ø NK S.A. DIFFUSER165 CFM, 8"Ø NK S.A. DIFFUSER165 CFM, 8"Ø NK S.A. DIFFUSER
35353535 E-1E-1E-1E-1 100 CFM, 6"x6" NK E.A. GRILLE100 CFM, 6"x6" NK E.A. GRILLE100 CFM, 6"x6" NK E.A. GRILLE100 CFM, 6"x6" NK E.A. GRILLE
36363636 12"x12"+1"AL R.A. OPENING W/12"x12"+1"AL R.A. OPENING W/12"x12"+1"AL R.A. OPENING W/12"x12"+1"AL R.A. OPENING W/
SOUND BOOT ABOVE CEILING.SOUND BOOT ABOVE CEILING.SOUND BOOT ABOVE CEILING.SOUND BOOT ABOVE CEILING.
37373737 16"x16"+1"AL R.A. OPENING W/16"x16"+1"AL R.A. OPENING W/16"x16"+1"AL R.A. OPENING W/16"x16"+1"AL R.A. OPENING W/
SOUND BOOT ABOVE CEILING.SOUND BOOT ABOVE CEILING.SOUND BOOT ABOVE CEILING.SOUND BOOT ABOVE CEILING.
38383838 18"x18"+1"AL R.A. OPENING W/18"x18"+1"AL R.A. OPENING W/18"x18"+1"AL R.A. OPENING W/18"x18"+1"AL R.A. OPENING W/
SOUND BOOT ABOVE CEILING.SOUND BOOT ABOVE CEILING.SOUND BOOT ABOVE CEILING.SOUND BOOT ABOVE CEILING.
39393939 22"x22"+1"AL R.A. OPENING W/22"x22"+1"AL R.A. OPENING W/22"x22"+1"AL R.A. OPENING W/22"x22"+1"AL R.A. OPENING W/
SOUND BOOT ABOVE CEILING.SOUND BOOT ABOVE CEILING.SOUND BOOT ABOVE CEILING.SOUND BOOT ABOVE CEILING.
40404040 192"x22" R.A. OPENING IN WALL192"x22" R.A. OPENING IN WALL192"x22" R.A. OPENING IN WALL192"x22" R.A. OPENING IN WALL
ABOVE CEILING.ABOVE CEILING.ABOVE CEILING.ABOVE CEILING.
41414141 72"x36" R.A. OPENING IN WALL ABOVE72"x36" R.A. OPENING IN WALL ABOVE72"x36" R.A. OPENING IN WALL ABOVE72"x36" R.A. OPENING IN WALL ABOVE
CEILING W/ F.S.D.CEILING W/ F.S.D.CEILING W/ F.S.D.CEILING W/ F.S.D.
42424242 66"x22" R.A. OPENING IN WALL ABOVE66"x22" R.A. OPENING IN WALL ABOVE66"x22" R.A. OPENING IN WALL ABOVE66"x22" R.A. OPENING IN WALL ABOVE
CEILING W/ F.S.D.CEILING W/ F.S.D.CEILING W/ F.S.D.CEILING W/ F.S.D.
43434343 48"x22" R.A. OPENING IN WALL ABOVE48"x22" R.A. OPENING IN WALL ABOVE48"x22" R.A. OPENING IN WALL ABOVE48"x22" R.A. OPENING IN WALL ABOVE
CEILING W/ F.S.D.CEILING W/ F.S.D.CEILING W/ F.S.D.CEILING W/ F.S.D.
44444444 S-3S-3S-3S-3 100 CFM, 6"x6" NK S.A. DIFFUSER100 CFM, 6"x6" NK S.A. DIFFUSER100 CFM, 6"x6" NK S.A. DIFFUSER100 CFM, 6"x6" NK S.A. DIFFUSER
45454545 R-2R-2R-2R-2 10"x6" NK R.A. GRILLE W/ SOUND10"x6" NK R.A. GRILLE W/ SOUND10"x6" NK R.A. GRILLE W/ SOUND10"x6" NK R.A. GRILLE W/ SOUND
BOOTBOOTBOOTBOOT
46464646 18"x8" E.A. DUCT UP FROM LEVEL18"x8" E.A. DUCT UP FROM LEVEL18"x8" E.A. DUCT UP FROM LEVEL18"x8" E.A. DUCT UP FROM LEVEL
BELOW. RISE 24"x12" E.A. DUCT UPBELOW. RISE 24"x12" E.A. DUCT UPBELOW. RISE 24"x12" E.A. DUCT UPBELOW. RISE 24"x12" E.A. DUCT UP
TO LEVEL ABOVE.TO LEVEL ABOVE.TO LEVEL ABOVE.TO LEVEL ABOVE.
47474747 E-1E-1E-1E-1 350 CFM, MATCH PREVIOUS GRILLE350 CFM, MATCH PREVIOUS GRILLE350 CFM, MATCH PREVIOUS GRILLE350 CFM, MATCH PREVIOUS GRILLE
FACE AND NECK SIZE AND CONNECTFACE AND NECK SIZE AND CONNECTFACE AND NECK SIZE AND CONNECTFACE AND NECK SIZE AND CONNECT
TO EXISTING E.A. DUCTWORK.TO EXISTING E.A. DUCTWORK.TO EXISTING E.A. DUCTWORK.TO EXISTING E.A. DUCTWORK.
48484848 BALANCE EXISTING E.A. GRILLE TOBALANCE EXISTING E.A. GRILLE TOBALANCE EXISTING E.A. GRILLE TOBALANCE EXISTING E.A. GRILLE TO
100 CFM.100 CFM.100 CFM.100 CFM.
49494949 E-2E-2E-2E-2 100 CFM, 6"x6" NK E.A. GRILLE100 CFM, 6"x6" NK E.A. GRILLE100 CFM, 6"x6" NK E.A. GRILLE100 CFM, 6"x6" NK E.A. GRILLE
50505050 RISE 54"x56" F.O. S.A. DUCT FROMRISE 54"x56" F.O. S.A. DUCT FROMRISE 54"x56" F.O. S.A. DUCT FROMRISE 54"x56" F.O. S.A. DUCT FROM
LEVEL BELOW. RISE 54"x68" F.O. S.A.LEVEL BELOW. RISE 54"x68" F.O. S.A.LEVEL BELOW. RISE 54"x68" F.O. S.A.LEVEL BELOW. RISE 54"x68" F.O. S.A.
DUCT TO LEVEL ABOVE.DUCT TO LEVEL ABOVE.DUCT TO LEVEL ABOVE.DUCT TO LEVEL ABOVE.
51515151 RISE 62"Ø S.A. DUCT FROM LEVELRISE 62"Ø S.A. DUCT FROM LEVELRISE 62"Ø S.A. DUCT FROM LEVELRISE 62"Ø S.A. DUCT FROM LEVEL
BELOW. RISE 54"Ø S.A. DUCT TOBELOW. RISE 54"Ø S.A. DUCT TOBELOW. RISE 54"Ø S.A. DUCT TOBELOW. RISE 54"Ø S.A. DUCT TO
LEVEL ABOVE.LEVEL ABOVE.LEVEL ABOVE.LEVEL ABOVE.
52525252 T-1T-1T-1T-1 18"x18" NK T.A. GRILLE W/ SOUND18"x18" NK T.A. GRILLE W/ SOUND18"x18" NK T.A. GRILLE W/ SOUND18"x18" NK T.A. GRILLE W/ SOUND
BOOTBOOTBOOTBOOT
SCALE:SCALE:SCALE:SCALE:MH101aMH101aMH101aMH101a 1/8" = 1'1/8" = 1'1/8" = 1'1/8" = 1'----0"0"0"0"
ibsbi=N=^ob^=^=jb`e^kf`^i=objlabi=mi^k1111
16161616151515151414141413131313121212121111111110101010999988887777
KKKK
HHHH
FFFF
DDDD
BBBB
AAAA
156D
STORAGE
156E
PRACTICE
156F
OFFICE
156
WORKSPACE
158
CONFERENCE ROOM
160A
OFFICE
160B
OFFICE
192A
SMALL MEETING
192B
OFFICE
192
WORKSTATIONS/ FLEX SPACE
190
TRAINING AREA
190B
OFFICE
190A
OFFICE
188A
OFFICE
188B
CONFERENCE
188
COLLABORATIVE SPACE
186
OFFICE
185
OFFICE
184
OFFICE
183
OFFICE
182
OFFICE
181
OFFICE
180
ADJUNCT OFFICE
170
DROP IN MATH LAB
172
CLASSROOM
179
STUDY
178
STUDY
174
STUDENT PREP
175
MATH LAB RECEPTION
176
I.T. HELP DESK
170C
STORAGE
170B
STUDY170A
STUDY
168
CLASSROOM
166
CLASSROOM
164
CLASSROOM
162
CLASSROOM
160
TUTORING ADMIN OPEN AREA
44"x16"F.O.44"x16"F.O.44"x16"F.O.44"x16"F.O.32"x16"F.O.32"x16"F.O.32"x16"F.O.32"x16"F.O.
46"x16"F.O.46"x16"F.O.46"x16"F.O.46"x16"F.O.
32
"
x
1
6
"
F
.
O
.
32
"
x
1
6
"
F
.
O
.
32
"
x
1
6
"
F
.
O
.
32
"
x
1
6
"
F
.
O
.
7777
CHCHCHCH
6666
CHCHCHCH
48"x22"F.O.48"x22"F.O.48"x22"F.O.48"x22"F.O.
48
"
x
2
2
"
F
.
O
.
48
"
x
2
2
"
F
.
O
.
48
"
x
2
2
"
F
.
O
.
48
"
x
2
2
"
F
.
O
.
48"x22"F.O.48"x22"F.O.48"x22"F.O.48"x22"F.O.
20"x14"+1"AL20"x14"+1"AL20"x14"+1"AL20"x14"+1"AL
22"x14"+1"AL22"x14"+1"AL22"x14"+1"AL22"x14"+1"AL
16"Ø16"Ø16"Ø16"Ø
16"Ø16"Ø16"Ø16"Ø 170BB170BB170BB170BB
VAVRVAVRVAVRVAVR
170AA170AA170AA170AA
VAVRVAVRVAVRVAVR
10"Ø10"Ø10"Ø10"Ø
185185185185
VAVRVAVRVAVRVAVR
6"Ø6"Ø6"Ø6"Ø
6"x8"+1"AL6"x8"+1"AL6"x8"+1"AL6"x8"+1"AL
183183183183
VAVRVAVRVAVRVAVR
6"
Ø
6"
Ø
6"
Ø
6"
Ø
6"x8"+1"AL6"x8"+1"AL6"x8"+1"AL6"x8"+1"AL
186186186186
VAVRVAVRVAVRVAVR
6"Ø6"Ø6"Ø6"Ø
8"x6"+1"AL8"x6"+1"AL8"x6"+1"AL8"x6"+1"AL
12"Ø12"Ø12"Ø12"Ø
182182182182
VAVRVAVRVAVRVAVR
6"Ø6"Ø6"Ø6"Ø
6"x8"+1"AL6"x8"+1"AL6"x8"+1"AL6"x8"+1"AL
181181181181
VAVRVAVRVAVRVAVR
6"
Ø
6"
Ø
6"
Ø
6"
Ø
6"x8"+1"AL6"x8"+1"AL6"x8"+1"AL6"x8"+1"AL
184184184184
VAVRVAVRVAVRVAVR
6"Ø6"Ø6"Ø6"Ø
6"x8"+1"AL6"x8"+1"AL6"x8"+1"AL6"x8"+1"AL
180180180180
VAVRVAVRVAVRVAVR
12"x10"+1"AL12"x10"+1"AL12"x10"+1"AL12"x10"+1"AL
10"Ø10"Ø10"Ø10"Ø
6"Ø6"Ø6"Ø6"Ø
1111----XXXX
VAVRVAVRVAVRVAVR
1-X
HALL
8"x8"+1"AL8"x8"+1"AL8"x8"+1"AL8"x8"+1"AL
10"Ø10"Ø10"Ø10"Ø
170C170C170C170C
VAVRVAVRVAVRVAVR
8"Ø8"Ø8"Ø8"Ø
8"x10"+1"AL8"x10"+1"AL8"x10"+1"AL8"x10"+1"AL
170B170B170B170B
VAVRVAVRVAVRVAVR
8"Ø8"Ø8"Ø8"Ø
10"x8"+1"AL10"x8"+1"AL10"x8"+1"AL10"x8"+1"AL
170A170A170A170A
VAVRVAVRVAVRVAVR
8"Ø8"Ø8"Ø8"Ø
10"x8"+1"AL10"x8"+1"AL10"x8"+1"AL10"x8"+1"AL
166166166166
VAVRVAVRVAVRVAVR
16"x14"+1"AL16"x14"+1"AL16"x14"+1"AL16"x14"+1"AL
14"Ø14"Ø14"Ø14"Ø 168168168168
VAVRVAVRVAVRVAVR
14"Ø14"Ø14"Ø14"Ø
178178178178
VAVRVAVRVAVRVAVR
6"Ø6"Ø6"Ø6"Ø
6"x8"+1"AL6"x8"+1"AL6"x8"+1"AL6"x8"+1"AL
179179179179
VAVRVAVRVAVRVAVR
6"Ø6"Ø6"Ø6"Ø
6"x8"+1"AL6"x8"+1"AL6"x8"+1"AL6"x8"+1"AL
1111----VVVV
VAVRVAVRVAVRVAVR
6"Ø6"Ø6"Ø6"Ø
8"x10"+1"AL8"x10"+1"AL8"x10"+1"AL8"x10"+1"AL
174174174174
VAVRVAVRVAVRVAVR
6"Ø6"Ø6"Ø6"Ø
8"x8"+1"AL8"x8"+1"AL8"x8"+1"AL8"x8"+1"AL
175175175175
VAVRVAVRVAVRVAVR
6"Ø6"Ø6"Ø6"Ø
8"x8"+1"AL8"x8"+1"AL8"x8"+1"AL8"x8"+1"AL
1111----UUUU
VAVRVAVRVAVRVAVR
12"Ø12"Ø12"Ø12"Ø
162162162162
VAVRVAVRVAVRVAVR 14"Ø14"Ø14"Ø14"Ø
14
"
x
1
4
"
+
1
"
A
L
14
"
x
1
4
"
+
1
"
A
L
14
"
x
1
4
"
+
1
"
A
L
14
"
x
1
4
"
+
1
"
A
L
14
"
x
1
2
"
+
1
"
A
L
14
"
x
1
2
"
+
1
"
A
L
14
"
x
1
2
"
+
1
"
A
L
14
"
x
1
2
"
+
1
"
A
L
12"Ø12"Ø12"Ø12"Ø
164164164164
VAVRVAVRVAVRVAVR
154
MEN'S RESTROOM
152
WOMEN'S RESTROOM
1-N
STAIRS
1-P
HALL
156A
PRACTICE
156B
PRACTICE
156C
PRACTICE
08
MECH
1-T
ELEV
190C
STORAGE
08A
ELEV EQUIP
152152152152
VAVRVAVRVAVRVAVR
8"Ø8"Ø8"Ø8"Ø
22"Ø22"Ø22"Ø22"Ø
10"Ø10"Ø10"Ø10"Ø
156156156156
VAVRVAVRVAVRVAVR
12"x12"+1"AL12"x12"+1"AL12"x12"+1"AL12"x12"+1"AL
156A156A156A156A
VAVRVAVRVAVRVAVR
6"Ø6"Ø6"Ø6"Ø
8"x6"+1"AL8"x6"+1"AL8"x6"+1"AL8"x6"+1"AL
156B156B156B156B
VAVRVAVRVAVRVAVR
6"Ø6"Ø6"Ø6"Ø8"x6"+1"AL8"x6"+1"AL8"x6"+1"AL8"x6"+1"AL
156C156C156C156C
VAVRVAVRVAVRVAVR
6"Ø6"Ø6"Ø6"Ø
8"x6"+1"AL8"x6"+1"AL8"x6"+1"AL8"x6"+1"AL
156F156F156F156F
VAVRVAVRVAVRVAVR
6"Ø6"Ø6"Ø6"Ø
8"x6"+1"AL8"x6"+1"AL8"x6"+1"AL8"x6"+1"AL
156E156E156E156E
VAVRVAVRVAVRVAVR
6"Ø6"Ø6"Ø6"Ø
8"x6"+1"AL8"x6"+1"AL8"x6"+1"AL8"x6"+1"AL
14"Ø14"Ø14"Ø14"Ø
14"Ø14"Ø14"Ø14"Ø
160A160A160A160A
VAVRVAVRVAVRVAVR
8"
x
6
"
+
1
"
A
L
8"
x
6
"
+
1
"
A
L
8"
x
6
"
+
1
"
A
L
8"
x
6
"
+
1
"
A
L
6"Ø6"Ø6"Ø6"Ø
1111----YYYY
VAVRVAVRVAVRVAVR
10"Ø10"Ø10"Ø10"Ø
12"x10"+1"AL12"x10"+1"AL12"x10"+1"AL12"x10"+1"AL
192192192192
VAVRVAVRVAVRVAVR
12
"
Ø
12
"
Ø
12
"
Ø
12
"
Ø
14"x12"+1"AL14"x12"+1"AL14"x12"+1"AL14"x12"+1"AL
6"
Ø
6"
Ø
6"
Ø
6"
Ø
192B192B192B192B
VAVRVAVRVAVRVAVR
8"x6"+1"AL8"x6"+1"AL8"x6"+1"AL8"x6"+1"AL
192C192C192C192C
VAVRVAVRVAVRVAVR
6"Ø6"Ø6"Ø6"Ø
8"
x
8
"
+
1
"
A
L
8"
x
8
"
+
1
"
A
L
8"
x
8
"
+
1
"
A
L
8"
x
8
"
+
1
"
A
L
14"Ø14"Ø14"Ø14"Ø
1111----ZZZZ
VAVRVAVRVAVRVAVR
1-Y
HALL
10"x10"+1"AL10"x10"+1"AL10"x10"+1"AL10"x10"+1"AL
188188188188
VAVRVAVRVAVRVAVR
10"Ø10"Ø10"Ø10"Ø
12"x10"+1"AL12"x10"+1"AL12"x10"+1"AL12"x10"+1"AL
8"Ø8"Ø8"Ø8"Ø
188A188A188A188A
VAVRVAVRVAVRVAVR
8"x10"+1"AL8"x10"+1"AL8"x10"+1"AL8"x10"+1"AL
190A190A190A190A
VAVRVAVRVAVRVAVR
6"Ø6"Ø6"Ø6"Ø
188B188B188B188B
VAVRVAVRVAVRVAVR
8"x10"+1"AL8"x10"+1"AL8"x10"+1"AL8"x10"+1"AL
6"Ø6"Ø6"Ø6"Ø
192A192A192A192A
VAVRVAVRVAVRVAVR
8"x10"+1"AL8"x10"+1"AL8"x10"+1"AL8"x10"+1"AL
6"Ø6"Ø6"Ø6"Ø
12"Ø12"Ø12"Ø12"Ø
190190190190
VAVRVAVRVAVRVAVR
14"x12"+1"AL14"x12"+1"AL14"x12"+1"AL14"x12"+1"AL
172172172172
VAVRVAVRVAVRVAVR
12"x12"+1"AL12"x12"+1"AL12"x12"+1"AL12"x12"+1"AL
10"Ø10"Ø10"Ø10"Ø
5555
CHCHCHCH
4444
CHCHCHCH
MH402MH402MH402MH402
1111
2222
3333
4444
5555
6666
7777
8888
9999
10101010
11111111
12121212
13131313
14141414
15151515
16161616
17171717
1818181819191919
2020202021212121
2222222223232323
24242424
25252525
26262626
25252525 H.D.H.D.H.D.H.D. H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D. H.D.H.D.H.D.H.D.
10"Ø10"Ø10"Ø10"Ø
2222
23232323
10"Ø10"Ø10"Ø10"Ø 10"Ø10"Ø10"Ø10"Ø
23232323 23232323
H.D.H.D.H.D.H.D.H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D. H.D.H.D.H.D.H.D.
22222222
22222222 222222228"Ø8"Ø8"Ø8"Ø8"Ø8"Ø8"Ø8"Ø
8"Ø8"Ø8"Ø8"Ø 8"Ø8"Ø8"Ø8"Ø
2222
27272727
2222 2222
10"Ø10"Ø10"Ø10"Ø 10"Ø10"Ø10"Ø10"Ø
H.D.H.D.H.D.H.D. H.D.H.D.H.D.H.D.
21212121
10"Ø10"Ø10"Ø10"Ø 10"Ø10"Ø10"Ø10"Ø
H.D.H.D.H.D.H.D. H.D.H.D.H.D.H.D.
21212121 21212121
16"x14"+1"AL16"x14"+1"AL16"x14"+1"AL16"x14"+1"AL
2222
2222
10"Ø10"Ø10"Ø10"Ø 10"Ø10"Ø10"Ø10"Ø
H.D.H.D.H.D.H.D. H.D.H.D.H.D.H.D.
10"Ø10"Ø10"Ø10"Ø 10"Ø10"Ø10"Ø10"Ø
H.D.H.D.H.D.H.D. H.D.H.D.H.D.H.D.
20202020
20202020 20202020
8"Ø8"Ø8"Ø8"Ø
H.D.H.D.H.D.H.D.
3333
8"Ø8"Ø8"Ø8"Ø
H.D.H.D.H.D.H.D.
3333
8"Ø8"Ø8"Ø8"Ø
H.D.H.D.H.D.H.D.H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
10"Ø10"Ø10"Ø10"Ø
2222
44444444
3333
8"
Ø
8"
Ø
8"
Ø
8"
Ø
H.D.H.D.H.D.H.D.
4444
8"Ø8"Ø8"Ø8"Ø
H.D.H.D.H.D.H.D.
4444
H.D.H.D.H.D.H.D.
10"Ø10"Ø10"Ø10"Ø
4444
10"Ø10"Ø10"Ø10"Ø
4444
10"Ø10"Ø10"Ø10"Ø
4444
16
"
x
1
2
"
+
1
"
A
L
16
"
x
1
2
"
+
1
"
A
L
16
"
x
1
2
"
+
1
"
A
L
16
"
x
1
2
"
+
1
"
A
L
18
"
x
1
2
"
+
1
"
A
L
18
"
x
1
2
"
+
1
"
A
L
18
"
x
1
2
"
+
1
"
A
L
18
"
x
1
2
"
+
1
"
A
L
16
"
x
1
2
"
+
1
"
A
L
16
"
x
1
2
"
+
1
"
A
L
16
"
x
1
2
"
+
1
"
A
L
16
"
x
1
2
"
+
1
"
A
L
2222 2222
2222
H.D.H.D.H.D.H.D.
8"Ø8"Ø8"Ø8"Ø
H.D.H.D.H.D.H.D.
8"Ø8"Ø8"Ø8"Ø
8"Ø8"Ø8"Ø8"Ø
5555
H.
D
.
H.
D
.
H.
D
.
H.
D
.
5555
8"Ø8"Ø8"Ø8"Ø
8"Ø8"Ø8"Ø8"Ø 8"Ø8"Ø8"Ø8"ØH.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
H.
D
.
H.
D
.
H.
D
.
H.
D
.
5555 55555555
8"Ø8"Ø8"Ø8"Ø 8"Ø8"Ø8"Ø8"Ø
H.
D
.
H.
D
.
H.
D
.
H.
D
.
5555 55555555
H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
8"Ø8"Ø8"Ø8"Ø
2222
8"Ø8"Ø8"Ø8"Ø
H.D.H.D.H.D.H.D.
5555
5555
8"Ø8"Ø8"Ø8"Ø
H.
D
.
H.
D
.
H.
D
.
H.
D
.
5555
8"Ø8"Ø8"Ø8"Ø
H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
8"Ø8"Ø8"Ø8"Ø
26262626
26262626
H.D.H.D.H.D.H.D.
8"Ø8"Ø8"Ø8"Ø
H.D.H.D.H.D.H.D.H.D.H.D.H.D.H.D.26262626
8"Ø8"Ø8"Ø8"Ø8"Ø8"Ø8"Ø8"Ø
26262626H.D.H.D.H.D.H.D.H.D.H.D.H.D.H.D.26262626
8"Ø8"Ø8"Ø8"Ø8"Ø8"Ø8"Ø8"Ø
26262626H.D.H.D.H.D.H.D.H.D.H.D.H.D.H.D.26262626
8"Ø8"Ø8"Ø8"Ø8"Ø8"Ø8"Ø8"Ø
26262626
H.D.H.D.H.D.H.D.H.D.H.D.H.D.H.D.
26262626
8"Ø8"Ø8"Ø8"Ø8"Ø8"Ø8"Ø8"Ø
2222
8"Ø8"Ø8"Ø8"Ø 8"Ø8"Ø8"Ø8"Ø
17171717H.D.H.D.H.D.H.D.H.D.H.D.H.D.H.D.
17171717
8"Ø8"Ø8"Ø8"Ø 8"Ø8"Ø8"Ø8"Ø
17171717H.D.H.D.H.D.H.D.H.D.H.D.H.D.H.D.
H.
D
.
H.
D
.
H.
D
.
H.
D
.
H.
D
.
H.
D
.
H.
D
.
H.
D
.
8"Ø8"Ø8"Ø8"Ø 8"Ø8"Ø8"Ø8"Ø
7777
4444
4444
6"Ø6"Ø6"Ø6"Ø
H.D.H.D.H.D.H.D.
4444
8"Ø8"Ø8"Ø8"Ø
H.D.H.D.H.D.H.D.
8888
H.D.H.D.H.D.H.D.
8"Ø8"Ø8"Ø8"Ø
8888
H.D.H.D.H.D.H.D.
8"Ø8"Ø8"Ø8"Ø
8888
H.D.H.D.H.D.H.D.8"Ø8"Ø8"Ø8"Ø
8888
8"Ø8"Ø8"Ø8"Ø
2222
8"Ø8"Ø8"Ø8"Ø
H.
D
.
H.
D
.
H.
D
.
H.
D
.
4444
10"Ø10"Ø10"Ø10"Ø
H.D.H.D.H.D.H.D.
H.
D
.
H.
D
.
H.
D
.
H.
D
.
10"Ø10"Ø10"Ø10"Ø
H.
D
.
H.
D
.
H.
D
.
H.
D
.
10101010
44444444
8"x10"+1"AL8"x10"+1"AL8"x10"+1"AL8"x10"+1"AL
9999
10"Ø10"Ø10"Ø10"Ø
H.
D
.
H.
D
.
H.
D
.
H.
D
.
H.
D
.
H.
D
.
H.
D
.
H.
D
.
10101010
4444 4444
6666
4444
H.D.H.D.H.D.H.D.
6666
6"
Ø
6"
Ø
6"
Ø
6"
Ø
4444
H.D.H.D.H.D.H.D.
6666
H.D.H.D.H.D.H.D.
6"Ø6"Ø6"Ø6"Ø
4444
4444
4444
H.D.H.D.H.D.H.D.
8"Ø8"Ø8"Ø8"Ø
H.D.H.D.H.D.H.D.8"Ø8"Ø8"Ø8"Ø
7777
H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
8"Ø8"Ø8"Ø8"Ø
8888
8888 8888 8888
88888888
TYP.TYP.TYP.TYP.
2222
4444
6666
H.D.H.D.H.D.H.D.
6"Ø6"Ø6"Ø6"Ø
H.D.H.D.H.D.H.D.
6"Ø6"Ø6"Ø6"Ø
6"Ø6"Ø6"Ø6"Ø
H.D.H.D.H.D.H.D.6666
4444
H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
4444
H.D.H.D.H.D.H.D.
12121212
H.D.H.D.H.D.H.D.
10"Ø10"Ø10"Ø10"Ø10"Ø10"Ø10"Ø10"Ø
12121212
H.
D
.
H.
D
.
H.
D
.
H.
D
.
10"Ø10"Ø10"Ø10"Ø
2222
H.D.H.D.H.D.H.D.
10"Ø10"Ø10"Ø10"Ø
4444
8"Ø8"Ø8"Ø8"Ø
H.D.H.D.H.D.H.D.
8"Ø8"Ø8"Ø8"Ø
H.D.H.D.H.D.H.D.
8"Ø8"Ø8"Ø8"Ø
H.D.H.D.H.D.H.D.H.D.H.D.H.D.H.D.
8"Ø8"Ø8"Ø8"Ø
1111111111111111
11111111
2222
4444
H.D.H.D.H.D.H.D.6"Ø6"Ø6"Ø6"Ø
8"Ø8"Ø8"Ø8"Ø
11111111
H.D.H.D.H.D.H.D.
8"Ø8"Ø8"Ø8"Ø
H.D.H.D.H.D.H.D.3333
192C
STORAGE
4444
H.D.H.D.H.D.H.D.6"Ø6"Ø6"Ø6"Ø 14141414
4444
28282828
29292929
30303030
31313131
32323232
33333333
34343434
35353535
36363636
37373737
32323232H.D.H.D.H.D.H.D. H.D.H.D.H.D.H.D.
6"Ø6"Ø6"Ø6"Ø
6"Ø6"Ø6"Ø6"Ø
10"Ø10"Ø10"Ø10"Ø
H.D.H.D.H.D.H.D.
H.
D
.
H.
D
.
H.
D
.
H.
D
.
8"Ø8"Ø8"Ø8"Ø
33333333
H.
D
.
H.
D
.
H.
D
.
H.
D
.
8"Ø8"Ø8"Ø8"Ø
2222
158158158158
VAVRVAVRVAVRVAVR
6"Ø6"Ø6"Ø6"Ø
8"x8"+1"AL8"x8"+1"AL8"x8"+1"AL8"x8"+1"AL
8"Ø8"Ø8"Ø8"Ø
16161616
16161616
8"Ø8"Ø8"Ø8"Ø
8"Ø8"Ø8"Ø8"Ø
10"x10"+1"AL10"x10"+1"AL10"x10"+1"AL10"x10"+1"AL
160160160160
VAVRVAVRVAVRVAVR
H.D.H.D.H.D.H.D.
8"Ø8"Ø8"Ø8"Ø
160B160B160B160B
VAVRVAVRVAVRVAVR
8"
x
6
"
+
1
"
A
L
8"
x
6
"
+
1
"
A
L
8"
x
6
"
+
1
"
A
L
8"
x
6
"
+
1
"
A
L
6"Ø6"Ø6"Ø6"Ø
6"Ø6"Ø6"Ø6"Ø
H.
D
.
H.
D
.
H.
D
.
H.
D
.
10"Ø10"Ø10"Ø10"Ø
H.
D
.
H.
D
.
H.
D
.
H.
D
.
12"x8"+1"AL12"x8"+1"AL12"x8"+1"AL12"x8"+1"AL
2222
14"x14"+1"AL14"x14"+1"AL14"x14"+1"AL14"x14"+1"AL
2222
14"x12"+1"AL14"x12"+1"AL14"x12"+1"AL14"x12"+1"AL
29292929
29292929
H.D.H.D.H.D.H.D.H.D.H.D.H.D.H.D.H.D.H.D.H.D.H.D.
10"Ø10"Ø10"Ø10"Ø
10"Ø10"Ø10"Ø10"Ø10"Ø10"Ø10"Ø10"Ø
10"x10"+1"AL10"x10"+1"AL10"x10"+1"AL10"x10"+1"AL
173173173173
VAVVAVVAVVAV
6"x6"+1"AL6"x6"+1"AL6"x6"+1"AL6"x6"+1"AL173
ELECTRICAL
6"Ø6"Ø6"Ø6"Ø
8"Ø8"Ø8"Ø8"Ø
8"x10"+1"AL8"x10"+1"AL8"x10"+1"AL8"x10"+1"AL
10"Ø10"Ø10"Ø10"Ø
190B190B190B190B
VAVRVAVRVAVRVAVR
H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
31313131
4444
H.D.H.D.H.D.H.D.
6"Ø6"Ø6"Ø6"Ø
6666
38383838
39393939
40404040
41414141
42424242
44444444
45454545
46464646
47474747
48484848
49494949
50505050
14"x14" EXH.14"x14" EXH.14"x14" EXH.14"x14" EXH.
H.D.H.D.H.D.H.D.H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.H.D.H.D.H.D.H.D.
10"x10"+1"AL10"x10"+1"AL10"x10"+1"AL10"x10"+1"AL
10"Ø10"Ø10"Ø10"Ø
H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D. H.D.H.D.H.D.H.D.
8"Ø8"Ø8"Ø8"Ø
10"Ø10"Ø10"Ø10"Ø
10"Ø10"Ø10"Ø10"Ø
46"x18"F.O.46"x18"F.O.46"x18"F.O.46"x18"F.O.
12"Ø12"Ø12"Ø12"Ø
46464646 45454545
49494949
45454545
45454545
46464646
42424242
42424242
42424242
42424242
42424242
41414141 41414141
41414141
42424242
4242424242424242
4141414141414141
41414141
43434343 43434343
4343434343434343
42424242
42424242 424242424242424242424242
41414141
41414141
42424242
42424242 42424242
43434343 42424242
10"Ø10"Ø10"Ø10"Ø
42424242
43434343
4444
42424242
42424242
4242424243434343
51515151
52525252
53535353
54545454
LVTLVTLVTLVT 14"x14"14"x14"14"x14"14"x14"
6"x6" EXH.6"x6" EXH.6"x6" EXH.6"x6" EXH.
6"x6" EXH.6"x6" EXH.6"x6" EXH.6"x6" EXH.
8"x8"+1"AL8"x8"+1"AL8"x8"+1"AL8"x8"+1"AL
H.D.H.D.H.D.H.D.8"Ø8"Ø8"Ø8"Ø
53535353
H.D.H.D.H.D.H.D.
8"Ø8"Ø8"Ø8"Ø
LVTLVTLVTLVT
6"
x
6
"
6"
x
6
"
6"
x
6
"
6"
x
6
"
54545454
6"x6"6"x6"6"x6"6"x6"
H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.8"x8" EXH.8"x8" EXH.8"x8" EXH.8"x8" EXH.1111
23232323
23232323
5555
dbkbo^i=klqbp
A.A.A.A.WHERE UNISTRUTS ARE NOT LOCATED NOR WHERE UNISTRUTS ARE NOT LOCATED NOR WHERE UNISTRUTS ARE NOT LOCATED NOR WHERE UNISTRUTS ARE NOT LOCATED NOR
ACCESSIBLE IN THE BOTTOM OF STRUCTURAL ACCESSIBLE IN THE BOTTOM OF STRUCTURAL ACCESSIBLE IN THE BOTTOM OF STRUCTURAL ACCESSIBLE IN THE BOTTOM OF STRUCTURAL
CONCRETE WEBS, ALL ANCHORS AND SUPPORTS CONCRETE WEBS, ALL ANCHORS AND SUPPORTS CONCRETE WEBS, ALL ANCHORS AND SUPPORTS CONCRETE WEBS, ALL ANCHORS AND SUPPORTS
SHALL BE CONNECTED TO THE SIDES OF THE WEBS. SHALL BE CONNECTED TO THE SIDES OF THE WEBS. SHALL BE CONNECTED TO THE SIDES OF THE WEBS. SHALL BE CONNECTED TO THE SIDES OF THE WEBS.
DO NOT ATTACH TO THE BOTTOM OF THE WEB IF DO NOT ATTACH TO THE BOTTOM OF THE WEB IF DO NOT ATTACH TO THE BOTTOM OF THE WEB IF DO NOT ATTACH TO THE BOTTOM OF THE WEB IF
THERE IS NO EXISTING UNISTRUT.THERE IS NO EXISTING UNISTRUT.THERE IS NO EXISTING UNISTRUT.THERE IS NO EXISTING UNISTRUT.
R.A. OPENINGS WITH SOUND BOOTS DO NOT NEED R.A. OPENINGS WITH SOUND BOOTS DO NOT NEED R.A. OPENINGS WITH SOUND BOOTS DO NOT NEED R.A. OPENINGS WITH SOUND BOOTS DO NOT NEED
TO BE INSTALLED IF THE WALL IN WHICH THEY ARE TO BE INSTALLED IF THE WALL IN WHICH THEY ARE TO BE INSTALLED IF THE WALL IN WHICH THEY ARE TO BE INSTALLED IF THE WALL IN WHICH THEY ARE
LOCATED, IS BETWEEN STRUCTURAL WEBS, AND LOCATED, IS BETWEEN STRUCTURAL WEBS, AND LOCATED, IS BETWEEN STRUCTURAL WEBS, AND LOCATED, IS BETWEEN STRUCTURAL WEBS, AND
THERE ARE OPENINGS, OF TOTAL AREA EQUAL TO OR THERE ARE OPENINGS, OF TOTAL AREA EQUAL TO OR THERE ARE OPENINGS, OF TOTAL AREA EQUAL TO OR THERE ARE OPENINGS, OF TOTAL AREA EQUAL TO OR
GREATER THAN THAT OF THE SOUND BOOT, INTO THE GREATER THAN THAT OF THE SOUND BOOT, INTO THE GREATER THAN THAT OF THE SOUND BOOT, INTO THE GREATER THAN THAT OF THE SOUND BOOT, INTO THE
STRUCTURAL PAN TO ALLOW AIR TO FLOW INTO THE STRUCTURAL PAN TO ALLOW AIR TO FLOW INTO THE STRUCTURAL PAN TO ALLOW AIR TO FLOW INTO THE STRUCTURAL PAN TO ALLOW AIR TO FLOW INTO THE
ADJACENT CEILING SPACE. CONTRACTOR TO ADJACENT CEILING SPACE. CONTRACTOR TO ADJACENT CEILING SPACE. CONTRACTOR TO ADJACENT CEILING SPACE. CONTRACTOR TO
PROVIDE CREDIT FOR SOUND BOOTS THAT WERE PROVIDE CREDIT FOR SOUND BOOTS THAT WERE PROVIDE CREDIT FOR SOUND BOOTS THAT WERE PROVIDE CREDIT FOR SOUND BOOTS THAT WERE
DEEMED UNNECESSARY.DEEMED UNNECESSARY.DEEMED UNNECESSARY.DEEMED UNNECESSARY.
B.B.B.B.
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
Level 01 Area
B Mechanical
Remodel Plan
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
KEY PLAN
A
B
ao^tfkd=klqbp
0000555510101010 10101010 20202020
NOTE
#
DIFFUSER
CALLOUT DESCRIPTION
1111 RISE 10"x6" EXH. DUCT IN CHASERISE 10"x6" EXH. DUCT IN CHASERISE 10"x6" EXH. DUCT IN CHASERISE 10"x6" EXH. DUCT IN CHASE
ABOVE. SEE DRAWING MH102b FORABOVE. SEE DRAWING MH102b FORABOVE. SEE DRAWING MH102b FORABOVE. SEE DRAWING MH102b FOR
CONTINUATION.CONTINUATION.CONTINUATION.CONTINUATION.
2222 R-1R-1R-1R-1 22"x22" NK R.A. GRILLE W/ SOUND22"x22" NK R.A. GRILLE W/ SOUND22"x22" NK R.A. GRILLE W/ SOUND22"x22" NK R.A. GRILLE W/ SOUND
BOOTBOOTBOOTBOOT
3333 S-1S-1S-1S-1 170 CFM, 8"Ø NK S.A. DIFFUSER170 CFM, 8"Ø NK S.A. DIFFUSER170 CFM, 8"Ø NK S.A. DIFFUSER170 CFM, 8"Ø NK S.A. DIFFUSER
4444 R-1R-1R-1R-1 22"x10" NK R.A. GRILLE W/ SOUND22"x10" NK R.A. GRILLE W/ SOUND22"x10" NK R.A. GRILLE W/ SOUND22"x10" NK R.A. GRILLE W/ SOUND
BOOTBOOTBOOTBOOT
5555 S-1S-1S-1S-1 160 CFM, 8"Ø NK S.A. DIFFUSER160 CFM, 8"Ø NK S.A. DIFFUSER160 CFM, 8"Ø NK S.A. DIFFUSER160 CFM, 8"Ø NK S.A. DIFFUSER
6666 S-1S-1S-1S-1 105 CFM, 6"Ø NK S.A. DIFFUSER105 CFM, 6"Ø NK S.A. DIFFUSER105 CFM, 6"Ø NK S.A. DIFFUSER105 CFM, 6"Ø NK S.A. DIFFUSER
7777 S-1S-1S-1S-1 140 CFM, 8"Ø NK S.A. DIFFUSER140 CFM, 8"Ø NK S.A. DIFFUSER140 CFM, 8"Ø NK S.A. DIFFUSER140 CFM, 8"Ø NK S.A. DIFFUSER
8888 S-1S-1S-1S-1 115 CFM, 8"Ø NK S.A. DIFFUSER115 CFM, 8"Ø NK S.A. DIFFUSER115 CFM, 8"Ø NK S.A. DIFFUSER115 CFM, 8"Ø NK S.A. DIFFUSER
9999 S-1S-1S-1S-1 240 CFM, 10"Ø NK S.A. DIFFUSER240 CFM, 10"Ø NK S.A. DIFFUSER240 CFM, 10"Ø NK S.A. DIFFUSER240 CFM, 10"Ø NK S.A. DIFFUSER
10101010 S-1S-1S-1S-1 325 CFM, 10"Ø NK S.A. DIFFUSER325 CFM, 10"Ø NK S.A. DIFFUSER325 CFM, 10"Ø NK S.A. DIFFUSER325 CFM, 10"Ø NK S.A. DIFFUSER
11111111 S-1S-1S-1S-1 195 CFM, 8"Ø NK S.A. DIFFUSER195 CFM, 8"Ø NK S.A. DIFFUSER195 CFM, 8"Ø NK S.A. DIFFUSER195 CFM, 8"Ø NK S.A. DIFFUSER
12121212 S-1S-1S-1S-1 290 CFM, 10"Ø NK S.A. DIFFUSER290 CFM, 10"Ø NK S.A. DIFFUSER290 CFM, 10"Ø NK S.A. DIFFUSER290 CFM, 10"Ø NK S.A. DIFFUSER
13131313 S-2S-2S-2S-2 60 CFM, 6"Ø NK S.A. DIFFUSER60 CFM, 6"Ø NK S.A. DIFFUSER60 CFM, 6"Ø NK S.A. DIFFUSER60 CFM, 6"Ø NK S.A. DIFFUSER
14141414 S-1S-1S-1S-1 50 CFM, 6"Ø NK S.A. DIFFUSER50 CFM, 6"Ø NK S.A. DIFFUSER50 CFM, 6"Ø NK S.A. DIFFUSER50 CFM, 6"Ø NK S.A. DIFFUSER
15151515 S-1S-1S-1S-1 265 CFM, 10"Ø NK S.A. DIFFUSER265 CFM, 10"Ø NK S.A. DIFFUSER265 CFM, 10"Ø NK S.A. DIFFUSER265 CFM, 10"Ø NK S.A. DIFFUSER
16161616 S-1S-1S-1S-1 145 CFM, 8"Ø NK S.A. DIFFUSER145 CFM, 8"Ø NK S.A. DIFFUSER145 CFM, 8"Ø NK S.A. DIFFUSER145 CFM, 8"Ø NK S.A. DIFFUSER
17171717 S-1S-1S-1S-1 220 CFM, 8"Ø NK S.A. DIFFUSER220 CFM, 8"Ø NK S.A. DIFFUSER220 CFM, 8"Ø NK S.A. DIFFUSER220 CFM, 8"Ø NK S.A. DIFFUSER
18181818 S-1S-1S-1S-1 355 CFM, 10"Ø NK S.A. DIFFUSER355 CFM, 10"Ø NK S.A. DIFFUSER355 CFM, 10"Ø NK S.A. DIFFUSER355 CFM, 10"Ø NK S.A. DIFFUSER
19191919 S-1S-1S-1S-1 360 CFM, 10"Ø NK S.A. DIFFUSER360 CFM, 10"Ø NK S.A. DIFFUSER360 CFM, 10"Ø NK S.A. DIFFUSER360 CFM, 10"Ø NK S.A. DIFFUSER
20202020 S-1S-1S-1S-1 380 CFM, 10"Ø NK S.A. DIFFUSER380 CFM, 10"Ø NK S.A. DIFFUSER380 CFM, 10"Ø NK S.A. DIFFUSER380 CFM, 10"Ø NK S.A. DIFFUSER
21212121 S-1S-1S-1S-1 370 CFM, 10"Ø NK S.A. DIFFUSER370 CFM, 10"Ø NK S.A. DIFFUSER370 CFM, 10"Ø NK S.A. DIFFUSER370 CFM, 10"Ø NK S.A. DIFFUSER
22222222 S-1S-1S-1S-1 235 CFM, 8"Ø NK S.A. DIFFUSER235 CFM, 8"Ø NK S.A. DIFFUSER235 CFM, 8"Ø NK S.A. DIFFUSER235 CFM, 8"Ø NK S.A. DIFFUSER
23232323 S-1S-1S-1S-1 315 CFM, 10"Ø NK S.A. DIFFUSER315 CFM, 10"Ø NK S.A. DIFFUSER315 CFM, 10"Ø NK S.A. DIFFUSER315 CFM, 10"Ø NK S.A. DIFFUSER
24242424 S-1S-1S-1S-1 125 CFM, 8"Ø NK S.A. DIFFUSER125 CFM, 8"Ø NK S.A. DIFFUSER125 CFM, 8"Ø NK S.A. DIFFUSER125 CFM, 8"Ø NK S.A. DIFFUSER
25252525 BALANCE EXISTING S.A. DIFFUSER TOBALANCE EXISTING S.A. DIFFUSER TOBALANCE EXISTING S.A. DIFFUSER TOBALANCE EXISTING S.A. DIFFUSER TO
250 CFM.250 CFM.250 CFM.250 CFM.
26262626 S-1S-1S-1S-1 180 CFM, 8"Ø NK S.A. DIFFUSER180 CFM, 8"Ø NK S.A. DIFFUSER180 CFM, 8"Ø NK S.A. DIFFUSER180 CFM, 8"Ø NK S.A. DIFFUSER
27272727 RISE 14"x14" EXHAUST UP INTO CHASERISE 14"x14" EXHAUST UP INTO CHASERISE 14"x14" EXHAUST UP INTO CHASERISE 14"x14" EXHAUST UP INTO CHASE
ABOVE AND CONNECT TO EXISTINGABOVE AND CONNECT TO EXISTINGABOVE AND CONNECT TO EXISTINGABOVE AND CONNECT TO EXISTING
E.A. DUCTWORK. SEE MH102b FORE.A. DUCTWORK. SEE MH102b FORE.A. DUCTWORK. SEE MH102b FORE.A. DUCTWORK. SEE MH102b FOR
CONTINUATION.CONTINUATION.CONTINUATION.CONTINUATION.
28282828 S-2S-2S-2S-2 265 CFM, 10"Ø NK S.A. DIFFUSER265 CFM, 10"Ø NK S.A. DIFFUSER265 CFM, 10"Ø NK S.A. DIFFUSER265 CFM, 10"Ø NK S.A. DIFFUSER
29292929 S-2S-2S-2S-2 325 CFM, 10"Ø NK S.A. DIFFUSER325 CFM, 10"Ø NK S.A. DIFFUSER325 CFM, 10"Ø NK S.A. DIFFUSER325 CFM, 10"Ø NK S.A. DIFFUSER
30303030 S-2S-2S-2S-2 290 CFM, 10"Ø NK S.A. DIFFUSER290 CFM, 10"Ø NK S.A. DIFFUSER290 CFM, 10"Ø NK S.A. DIFFUSER290 CFM, 10"Ø NK S.A. DIFFUSER
31313131 S-2S-2S-2S-2 245 CFM, 10"Ø NK S.A. DIFFUSER245 CFM, 10"Ø NK S.A. DIFFUSER245 CFM, 10"Ø NK S.A. DIFFUSER245 CFM, 10"Ø NK S.A. DIFFUSER
32323232 S-1S-1S-1S-1 100 CFM, 6"Ø NK S.A. DIFFUSER100 CFM, 6"Ø NK S.A. DIFFUSER100 CFM, 6"Ø NK S.A. DIFFUSER100 CFM, 6"Ø NK S.A. DIFFUSER
33333333 S-4S-4S-4S-4 145 CFM, 4'-0" x 2 SLOT S.A.145 CFM, 4'-0" x 2 SLOT S.A.145 CFM, 4'-0" x 2 SLOT S.A.145 CFM, 4'-0" x 2 SLOT S.A.
DIFFUSERDIFFUSERDIFFUSERDIFFUSER
34343434 S-3S-3S-3S-3 100 CFM, 6"x6" NK S.A. DIFFUSER100 CFM, 6"x6" NK S.A. DIFFUSER100 CFM, 6"x6" NK S.A. DIFFUSER100 CFM, 6"x6" NK S.A. DIFFUSER
35353535 R-2R-2R-2R-2 10"x10" NK R.A. GRILLE10"x10" NK R.A. GRILLE10"x10" NK R.A. GRILLE10"x10" NK R.A. GRILLE
36363636 S-3S-3S-3S-3 290 CFM, 12"x8" NK S.A. DIFFUSER290 CFM, 12"x8" NK S.A. DIFFUSER290 CFM, 12"x8" NK S.A. DIFFUSER290 CFM, 12"x8" NK S.A. DIFFUSER
37373737 R-2R-2R-2R-2 14"x14" NK R.A. GRILLE W/ SOUND14"x14" NK R.A. GRILLE W/ SOUND14"x14" NK R.A. GRILLE W/ SOUND14"x14" NK R.A. GRILLE W/ SOUND
BOOTBOOTBOOTBOOT
38383838 BALANCE EXISTING E.A. GRILLE TO 100BALANCE EXISTING E.A. GRILLE TO 100BALANCE EXISTING E.A. GRILLE TO 100BALANCE EXISTING E.A. GRILLE TO 100
CFM.CFM.CFM.CFM.
39393939 BALANCE EXISTING E.A. GRILLE TO 250BALANCE EXISTING E.A. GRILLE TO 250BALANCE EXISTING E.A. GRILLE TO 250BALANCE EXISTING E.A. GRILLE TO 250
CFM.CFM.CFM.CFM.
40404040 168"x30" R.A. OPENING IN WALL168"x30" R.A. OPENING IN WALL168"x30" R.A. OPENING IN WALL168"x30" R.A. OPENING IN WALL
ABOVE CEILING.ABOVE CEILING.ABOVE CEILING.ABOVE CEILING.
41414141 22"x22"+1"AL R.A. OPENING W/22"x22"+1"AL R.A. OPENING W/22"x22"+1"AL R.A. OPENING W/22"x22"+1"AL R.A. OPENING W/
SOUND BOOT ABOVE CEILING.SOUND BOOT ABOVE CEILING.SOUND BOOT ABOVE CEILING.SOUND BOOT ABOVE CEILING.
42424242 12"x12"+1"AL R.A. OPENING W/12"x12"+1"AL R.A. OPENING W/12"x12"+1"AL R.A. OPENING W/12"x12"+1"AL R.A. OPENING W/
SOUND BOOT ABOVE CEILING.SOUND BOOT ABOVE CEILING.SOUND BOOT ABOVE CEILING.SOUND BOOT ABOVE CEILING.
43434343 16"x16"+1"AL R.A. OPENING W/16"x16"+1"AL R.A. OPENING W/16"x16"+1"AL R.A. OPENING W/16"x16"+1"AL R.A. OPENING W/
SOUND BOOT ABOVE CEILING.SOUND BOOT ABOVE CEILING.SOUND BOOT ABOVE CEILING.SOUND BOOT ABOVE CEILING.
44444444 18"x18"+1"AL R.A. OPENING W/18"x18"+1"AL R.A. OPENING W/18"x18"+1"AL R.A. OPENING W/18"x18"+1"AL R.A. OPENING W/
SOUND BOOT ABOVE CEILING.SOUND BOOT ABOVE CEILING.SOUND BOOT ABOVE CEILING.SOUND BOOT ABOVE CEILING.
45454545 96"x24" R.A. OPENING IN WALL ABOVE96"x24" R.A. OPENING IN WALL ABOVE96"x24" R.A. OPENING IN WALL ABOVE96"x24" R.A. OPENING IN WALL ABOVE
CEILING.CEILING.CEILING.CEILING.
46464646 48"x24" R.A. OPENING IN WALL ABOVE48"x24" R.A. OPENING IN WALL ABOVE48"x24" R.A. OPENING IN WALL ABOVE48"x24" R.A. OPENING IN WALL ABOVE
CEILING.CEILING.CEILING.CEILING.
47474747 108"x24" R.A. OPENING IN WALL108"x24" R.A. OPENING IN WALL108"x24" R.A. OPENING IN WALL108"x24" R.A. OPENING IN WALL
ABOVE CEILING.ABOVE CEILING.ABOVE CEILING.ABOVE CEILING.
48484848 36"x24" R.A. OPENING IN WALL ABOVE36"x24" R.A. OPENING IN WALL ABOVE36"x24" R.A. OPENING IN WALL ABOVE36"x24" R.A. OPENING IN WALL ABOVE
CEILING.CEILING.CEILING.CEILING.
49494949 60"x24" R.A. OPENING IN WALL ABOVE60"x24" R.A. OPENING IN WALL ABOVE60"x24" R.A. OPENING IN WALL ABOVE60"x24" R.A. OPENING IN WALL ABOVE
CEILING.CEILING.CEILING.CEILING.
50505050 R-2R-2R-2R-2 10"x6" NK R.A. GRILLE10"x6" NK R.A. GRILLE10"x6" NK R.A. GRILLE10"x6" NK R.A. GRILLE
51515151 E-2E-2E-2E-2 100 CFM, 6"x6" NK E.A. GRILLE100 CFM, 6"x6" NK E.A. GRILLE100 CFM, 6"x6" NK E.A. GRILLE100 CFM, 6"x6" NK E.A. GRILLE
52525252 S-1S-1S-1S-1 165 CFM, 8"Ø NK S.A. DIFFUSER165 CFM, 8"Ø NK S.A. DIFFUSER165 CFM, 8"Ø NK S.A. DIFFUSER165 CFM, 8"Ø NK S.A. DIFFUSER
53535353 S-4S-4S-4S-4 135 CFM, 4'-0" x 2 SLOT S.A.135 CFM, 4'-0" x 2 SLOT S.A.135 CFM, 4'-0" x 2 SLOT S.A.135 CFM, 4'-0" x 2 SLOT S.A.
DIFFUSERDIFFUSERDIFFUSERDIFFUSER
54545454 E-2E-2E-2E-2 125 CFM, 6"x6" NK E.A. GRILLE125 CFM, 6"x6" NK E.A. GRILLE125 CFM, 6"x6" NK E.A. GRILLE125 CFM, 6"x6" NK E.A. GRILLE
SCALE:SCALE:SCALE:SCALE:MH101bMH101bMH101bMH101b 1/8" = 1'1/8" = 1'1/8" = 1'1/8" = 1'----0"0"0"0"
ibsbi=N=^ob^=_=jb`e^kf`^i=objlabi=mi^k1111
1111
GGGG
JJJJ
LLLL
MMMM
NNNN
PPPP
QQQQ
EEEE
CCCC
2222 3333 4444 5555
238
TECH SERVICES
23
6
SH
E
E
T
M
U
S
I
C
234
LARGE COMPUTER CLASSROOM
228D
ARCHIVE
228E
VAULT
226
PRESS ROOM
243
MOTHERS
242
ELECTRICAL ROOM
53
OPEN STUDY
240
OPEN COMPUTERS
228
SPECIAL COLLECTIONS
228B
DCAM
228C
SCANNER
228A
OFFICE
222
INSTRUCTION 1
224
INSTRUCTION 2
232
OFFICE
200
OFFICE
220
OPEN STUDY
202
OFFICE
230
OFFICE
208
STUDY (SM)
210
STUDY (SM)
212
STUDY (SM)
214
STUDY (MED)
216
STUDY (MED)
218
STUDY (MED)
20"x16"F.O.20"x16"F.O.20"x16"F.O.20"x16"F.O.
26"x10" EXH.26"x10" EXH.26"x10" EXH.26"x10" EXH.
52"x24"F.O.52"x24"F.O.52"x24"F.O.52"x24"F.O.
36
"
x
1
6
"
F
.
O
.
36
"
x
1
6
"
F
.
O
.
36
"
x
1
6
"
F
.
O
.
36
"
x
1
6
"
F
.
O
.
52"x24"F.O.52"x24"F.O.52"x24"F.O.52"x24"F.O.
26"x16"F.O.26"x16"F.O.26"x16"F.O.26"x16"F.O.18"Ø18"Ø18"Ø18"Ø
26
"
x
1
0
"
E
X
H
.
26
"
x
1
0
"
E
X
H
.
26
"
x
1
0
"
E
X
H
.
26
"
x
1
0
"
E
X
H
.
16"x16"+1"AL16"x16"+1"AL16"x16"+1"AL16"x16"+1"AL
238238238238
VAVRVAVRVAVRVAVR
16"Ø16"Ø16"Ø16"Ø
20"x16"+1"AL20"x16"+1"AL20"x16"+1"AL20"x16"+1"AL
240A240A240A240A
VAVRVAVRVAVRVAVR
16"Ø16"Ø16"Ø16"Ø
20"x16"+1"AL20"x16"+1"AL20"x16"+1"AL20"x16"+1"AL
240B240B240B240B
VAVRVAVRVAVRVAVR
16
"
Ø
16
"
Ø
16
"
Ø
16
"
Ø
20"x16"+1"AL20"x16"+1"AL20"x16"+1"AL20"x16"+1"AL
234234234234
VAVRVAVRVAVRVAVR
16"Ø16"Ø16"Ø16"Ø
26
"
x
1
0
"
E
X
H
.
26
"
x
1
0
"
E
X
H
.
26
"
x
1
0
"
E
X
H
.
26
"
x
1
0
"
E
X
H
.
14"x12"+1"AL14"x12"+1"AL14"x12"+1"AL14"x12"+1"AL
228228228228
VAVRVAVRVAVRVAVR
12"Ø12"Ø12"Ø12"Ø
12"Ø12"Ø12"Ø12"Ø
228A228A228A228A
VAVRVAVRVAVRVAVR
6"Ø6"Ø6"Ø6"Ø
6"x8"+1"AL6"x8"+1"AL6"x8"+1"AL6"x8"+1"AL
232232232232
VAVRVAVRVAVRVAVR
6"Ø6"Ø6"Ø6"Ø
6"x8"+1"AL6"x8"+1"AL6"x8"+1"AL6"x8"+1"AL
230230230230
VAVRVAVRVAVRVAVR
6"Ø6"Ø6"Ø6"Ø
8"x6"+1"AL8"x6"+1"AL8"x6"+1"AL8"x6"+1"AL
12"Ø12"Ø12"Ø12"Ø
228C228C228C228C
VAVRVAVRVAVRVAVR
6"x8"+1"AL6"x8"+1"AL6"x8"+1"AL6"x8"+1"AL
6"Ø6"Ø6"Ø6"Ø
236236236236
VAVRVAVRVAVRVAVR
8"x6"+1"AL8"x6"+1"AL8"x6"+1"AL8"x6"+1"AL
6"Ø6"Ø6"Ø6"Ø
253253253253
VAVRVAVRVAVRVAVR
14"x12"+1"AL14"x12"+1"AL14"x12"+1"AL14"x12"+1"AL
246246246246
VAVRVAVRVAVRVAVR
6"Ø6"Ø6"Ø6"Ø
8"
x
1
0
"
+
1
"
A
L
8"
x
1
0
"
+
1
"
A
L
8"
x
1
0
"
+
1
"
A
L
8"
x
1
0
"
+
1
"
A
L
247
MEN'S RESTROOM
248
WOMEN'S RESTROOM
226226226226
VAVRVAVRVAVRVAVR
6"Ø6"Ø6"Ø6"Ø
8"x8"+1"AL8"x8"+1"AL8"x8"+1"AL8"x8"+1"AL
14
"
x
1
4
"
+
1
"
A
L
14
"
x
1
4
"
+
1
"
A
L
14
"
x
1
4
"
+
1
"
A
L
14
"
x
1
4
"
+
1
"
A
L
222222222222
VAVRVAVRVAVRVAVR
12"Ø12"Ø12"Ø12"Ø
14"x10"+1"AL14"x10"+1"AL14"x10"+1"AL14"x10"+1"AL
10"Ø10"Ø10"Ø10"Ø
228B228B228B228B
VAVRVAVRVAVRVAVR
12"x12"+1"AL12"x12"+1"AL12"x12"+1"AL12"x12"+1"AL
10"Ø10"Ø10"Ø10"Ø
224224224224
VAVRVAVRVAVRVAVR
241241241241
VAVRVAVRVAVRVAVR
6"Ø6"Ø6"Ø6"Ø
6"x8"+1"AL6"x8"+1"AL6"x8"+1"AL6"x8"+1"AL 242242242242
VAVRVAVRVAVRVAVR
6"Ø6"Ø6"Ø6"Ø
8"x6"+1"AL8"x6"+1"AL8"x6"+1"AL8"x6"+1"AL
248248248248
VAVRVAVRVAVRVAVR
8"x10"+1"AL8"x10"+1"AL8"x10"+1"AL8"x10"+1"AL
8"Ø8"Ø8"Ø8"Ø
214214214214
VAVRVAVRVAVRVAVR
8"x10"+1"AL8"x10"+1"AL8"x10"+1"AL8"x10"+1"AL14"x10"+1"AL14"x10"+1"AL14"x10"+1"AL14"x10"+1"AL
10"Ø10"Ø10"Ø10"Ø
216216216216
VAVRVAVRVAVRVAVR
14"x12"+1"AL14"x12"+1"AL14"x12"+1"AL14"x12"+1"AL
218218218218
VAVRVAVRVAVRVAVR
12"Ø12"Ø12"Ø12"Ø 204
STUDY (SM)
2-A
STAIR
16"Ø16"Ø16"Ø16"Ø
220A220A220A220A
VAVRVAVRVAVRVAVR
18
"
x
1
6
"
+
1
"
A
L
18
"
x
1
6
"
+
1
"
A
L
18
"
x
1
6
"
+
1
"
A
L
18
"
x
1
6
"
+
1
"
A
L
220B220B220B220B
VAVRVAVRVAVRVAVR
220C220C220C220C
VAVRVAVRVAVRVAVR
14"Ø14"Ø14"Ø14"Ø
16
"
x
1
6
"
+
1
"
A
L
16
"
x
1
6
"
+
1
"
A
L
16
"
x
1
6
"
+
1
"
A
L
16
"
x
1
6
"
+
1
"
A
L
220E220E220E220E
VAVRVAVRVAVRVAVR
14"Ø14"Ø14"Ø14"Ø
220D220D220D220D
VAVRVAVRVAVRVAVR 14"Ø14"Ø14"Ø14"Ø
8"Ø8"Ø8"Ø8"Ø
200200200200
VAVRVAVRVAVRVAVR
10"x10"+1"AL10"x10"+1"AL10"x10"+1"AL10"x10"+1"AL
8"Ø8"Ø8"Ø8"Ø
202202202202
VAVRVAVRVAVRVAVR
8"x12"+1"AL8"x12"+1"AL8"x12"+1"AL8"x12"+1"AL
8"Ø8"Ø8"Ø8"Ø
204204204204
VAVRVAVRVAVRVAVR 8"x12"+1"AL8"x12"+1"AL8"x12"+1"AL8"x12"+1"AL
212212212212
VAVRVAVRVAVRVAVR
6"Ø6"Ø6"Ø6"Ø
8"x8"+1"AL8"x8"+1"AL8"x8"+1"AL8"x8"+1"AL
210210210210
VAVRVAVRVAVRVAVR
6"Ø6"Ø6"Ø6"Ø
8"x8"+1"AL8"x8"+1"AL8"x8"+1"AL8"x8"+1"AL
8"Ø8"Ø8"Ø8"Ø
208208208208
VAVRVAVRVAVRVAVR
8"x12"+1"AL8"x12"+1"AL8"x12"+1"AL8"x12"+1"AL
14"x12"+1"AL14"x12"+1"AL14"x12"+1"AL14"x12"+1"AL
206206206206
VAVRVAVRVAVRVAVR
12"Ø12"Ø12"Ø12"Ø
18"x12"+1"AL18"x12"+1"AL18"x12"+1"AL18"x12"+1"AL
18"x12"+1"AL18"x12"+1"AL18"x12"+1"AL18"x12"+1"AL
250
OPEN STUDY
250B250B250B250B
VAVRVAVRVAVRVAVR
250A250A250A250A
VAVRVAVRVAVRVAVR
2-D
MECHANICAL
1111
HHHH
1111
2222
1111
LLLL
10"x10"+2"AL10"x10"+2"AL10"x10"+2"AL10"x10"+2"AL
14"x14"+1"AL14"x14"+1"AL14"x14"+1"AL14"x14"+1"AL
1111
DXFCUDXFCUDXFCUDXFCU 3333
34343434
35353535
36363636
4444
12"x12"+1"AL12"x12"+1"AL12"x12"+1"AL12"x12"+1"AL
H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
8"Ø8"Ø8"Ø8"Ø
8"Ø8"Ø8"Ø8"Ø
34343434
34343434
H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
8"Ø8"Ø8"Ø8"Ø
8"Ø8"Ø8"Ø8"Ø
34343434
34343434
H.D.H.D.H.D.H.D.
8"Ø8"Ø8"Ø8"Ø
H.D.H.D.H.D.H.D.
8"Ø8"Ø8"Ø8"Ø 34343434
14"x14"+1"AL14"x14"+1"AL14"x14"+1"AL14"x14"+1"AL
12"x12"+1"AL12"x12"+1"AL12"x12"+1"AL12"x12"+1"AL
H.
D
.
H.
D
.
H.
D
.
H.
D
.
H.
D
.
H.
D
.
H.
D
.
H.
D
.
BDBDBDBD
2222
4444
BDBDBDBD
1111
55556666
7777
8888
9999
10101010
11111111 12121212
13131313
14141414
15151515
16161616
17171717
18181818
19191919
20202020
21212121
22222222
2323232324242424
25252525
26262626
27272727
28282828
29292929
30303030
31313131
32323232
33333333
H.D.H.D.H.D.H.D.
H.
D
.
H.
D
.
H.
D
.
H.
D
.
H.
D
.
H.
D
.
H.
D
.
H.
D
.
H.
D
.
H.
D
.
H.
D
.
H.
D
.
12121212
10
"
Ø
10
"
Ø
10
"
Ø
10
"
Ø
10"Ø10"Ø10"Ø10"Ø
12121212
12121212
10"Ø10"Ø10"Ø10"Ø
10"Ø10"Ø10"Ø10"Ø
48
"
x
2
0
"
F
.
O
.
48
"
x
2
0
"
F
.
O
.
48
"
x
2
0
"
F
.
O
.
48
"
x
2
0
"
F
.
O
.
H.D.H.D.H.D.H.D.
12"Ø12"Ø12"Ø12"Ø
7777
H.D.H.D.H.D.H.D.
8"Ø8"Ø8"Ø8"Ø
H.D.H.D.H.D.H.D.
8"Ø8"Ø8"Ø8"Ø
10101010
7777
7777
12"Ø12"Ø12"Ø12"Ø
12
"
Ø
12
"
Ø
12
"
Ø
12
"
Ø
6666
5555
H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
5555
H.D.H.D.H.D.H.D.
H.
D
.
H.
D
.
H.
D
.
H.
D
.
8888
10"Ø10"Ø10"Ø10"Ø
10"Ø10"Ø10"Ø10"Ø
H.D.H.D.H.D.H.D.10"Ø10"Ø10"Ø10"Ø
11111111
12"Ø12"Ø12"Ø12"Ø7777
12"Ø12"Ø12"Ø12"Ø
H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
10"Ø10"Ø10"Ø10"Ø
7777
7777
18
"
x
1
4
"
+
1
"
A
L
18
"
x
1
4
"
+
1
"
A
L
18
"
x
1
4
"
+
1
"
A
L
18
"
x
1
4
"
+
1
"
A
L
16"Ø16"Ø16"Ø16"Ø
18"Ø18"Ø18"Ø18"Ø 18"Ø18"Ø18"Ø18"Ø
5555
5555
5555
5555
5555 5555
5555 5555 5555
5555
5555
5555
14"x10"+1"AL14"x10"+1"AL14"x10"+1"AL14"x10"+1"AL
H.D.H.D.H.D.H.D.
25252525
14"x10"+1"AL14"x10"+1"AL14"x10"+1"AL14"x10"+1"AL
H.D.H.D.H.D.H.D.
25252525
14"x10"+1"AL14"x10"+1"AL14"x10"+1"AL14"x10"+1"AL
H.D.H.D.H.D.H.D.
25252525
14"x10"+1"AL14"x10"+1"AL14"x10"+1"AL14"x10"+1"AL
H.D.H.D.H.D.H.D.
25252525
14"x10"+1"AL14"x10"+1"AL14"x10"+1"AL14"x10"+1"AL
18
"
x
1
6
"
+
1
"
A
L
18
"
x
1
6
"
+
1
"
A
L
18
"
x
1
6
"
+
1
"
A
L
18
"
x
1
6
"
+
1
"
A
L
25252525
14"x10"+1"AL14"x10"+1"AL14"x10"+1"AL14"x10"+1"AL H.D.H.D.H.D.H.D.
25252525
14"x10"+1"AL14"x10"+1"AL14"x10"+1"AL14"x10"+1"AL H.D.H.D.H.D.H.D.
25252525
14"x10"+1"AL14"x10"+1"AL14"x10"+1"AL14"x10"+1"AL
H.D.H.D.H.D.H.D.
25252525
14"x10"+1"AL14"x10"+1"AL14"x10"+1"AL14"x10"+1"AL H.D.H.D.H.D.H.D.
25252525
14"x10"+1"AL14"x10"+1"AL14"x10"+1"AL14"x10"+1"AL
H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
10"x8"+1"AL10"x8"+1"AL10"x8"+1"AL10"x8"+1"AL
27272727
H.D.H.D.H.D.H.D.
10"x8"+1"AL10"x8"+1"AL10"x8"+1"AL10"x8"+1"AL
27272727
H.D.H.D.H.D.H.D.
10"x8"+1"AL10"x8"+1"AL10"x8"+1"AL10"x8"+1"AL
27272727
H.D.H.D.H.D.H.D.
10"x8"+1"AL10"x8"+1"AL10"x8"+1"AL10"x8"+1"AL
27272727
H.
D
.
H.
D
.
H.
D
.
H.
D
.
10"x8"+1"AL10"x8"+1"AL10"x8"+1"AL10"x8"+1"AL
27272727
H.D.H.D.H.D.H.D.
10"x8"+1"AL10"x8"+1"AL10"x8"+1"AL10"x8"+1"AL
27272727
H.D.H.D.H.D.H.D.
10"x8"+1"AL10"x8"+1"AL10"x8"+1"AL10"x8"+1"AL
27272727
H.D.H.D.H.D.H.D.
10"x8"+1"AL10"x8"+1"AL10"x8"+1"AL10"x8"+1"AL
27272727
H.D.H.D.H.D.H.D.
10"x8"+1"AL10"x8"+1"AL10"x8"+1"AL10"x8"+1"AL
27272727H.D.H.D.H.D.H.D.
10"x8"+1"AL10"x8"+1"AL10"x8"+1"AL10"x8"+1"AL
16
"
x
1
6
"
+
1
"
A
L
16
"
x
1
6
"
+
1
"
A
L
16
"
x
1
6
"
+
1
"
A
L
16
"
x
1
6
"
+
1
"
A
L
H.D.H.D.H.D.H.D.8"Ø8"Ø8"Ø8"Ø
26262626
H.D.H.D.H.D.H.D.8"Ø8"Ø8"Ø8"Ø
26262626
H.D.H.D.H.D.H.D.8"Ø8"Ø8"Ø8"Ø
26262626
H.D.H.D.H.D.H.D.
H.
D
.
H.
D
.
H.
D
.
H.
D
.
26262626
H.D.H.D.H.D.H.D.
26262626
8"Ø8"Ø8"Ø8"Ø
H.D.H.D.H.D.H.D.
26262626
8"Ø8"Ø8"Ø8"Ø
H.D.H.D.H.D.H.D.
26262626
8"Ø8"Ø8"Ø8"Ø
8"Ø8"Ø8"Ø8"Ø
8"Ø8"Ø8"Ø8"Ø
8"Ø8"Ø8"Ø8"ØH.D.H.D.H.D.H.D. H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
19191919 19191919
19191919
8"Ø8"Ø8"Ø8"Ø
8"Ø8"Ø8"Ø8"Ø
H.D.H.D.H.D.H.D. H.D.H.D.H.D.H.D.
19191919 19191919
8"Ø8"Ø8"Ø8"ØH.D.H.D.H.D.H.D.
19191919
8"Ø8"Ø8"Ø8"Ø H.D.H.D.H.D.H.D.
8"Ø8"Ø8"Ø8"Ø
H.D.H.D.H.D.H.D.
19191919
8"Ø8"Ø8"Ø8"Ø
H.D.H.D.H.D.H.D.
19191919
19191919 8"Ø8"Ø8"Ø8"Ø
H.D.H.D.H.D.H.D.
19191919
8"Ø8"Ø8"Ø8"Ø H.D.H.D.H.D.H.D.
5555
8"Ø8"Ø8"Ø8"Ø
H.D.H.D.H.D.H.D.
161616168"Ø8"Ø8"Ø8"Ø
H.D.H.D.H.D.H.D.
16161616 8"Ø8"Ø8"Ø8"Ø
H.D.H.D.H.D.H.D.
161616168"Ø8"Ø8"Ø8"Ø
H.D.H.D.H.D.H.D.
16161616 8"Ø8"Ø8"Ø8"Ø
H.D.H.D.H.D.H.D.
161616168"Ø8"Ø8"Ø8"Ø
H.D.H.D.H.D.H.D.
1616161616161616
5555
1616161616161616
1616161616161616
H.D.H.D.H.D.H.D.H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D. H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
8"Ø,8"Ø,8"Ø,8"Ø,
TYP.TYP.TYP.TYP.
H.D.H.D.H.D.H.D.
6"Ø6"Ø6"Ø6"Ø
15151515
H.D.H.D.H.D.H.D.
6"Ø6"Ø6"Ø6"Ø
7777
5555
16161616
16161616 H.D.H.D.H.D.H.D.
8"Ø8"Ø8"Ø8"Ø
H.D.H.D.H.D.H.D.
8"
Ø
8"
Ø
8"
Ø
8"
Ø
16161616
H.D.H.D.H.D.H.D.
8"Ø8"Ø8"Ø8"Ø
16161616
H.D.H.D.H.D.H.D.
8"Ø8"Ø8"Ø8"Ø
16161616 H.D.H.D.H.D.H.D.
8"Ø8"Ø8"Ø8"Ø
16161616 H.D.H.D.H.D.H.D.
8"Ø8"Ø8"Ø8"Ø
16161616
H.D.H.D.H.D.H.D.
8"
Ø
8"
Ø
8"
Ø
8"
Ø
5555
8"Ø8"Ø8"Ø8"Ø
H.D.H.D.H.D.H.D.
17171717
8"Ø8"Ø8"Ø8"Ø
H.D.H.D.H.D.H.D.
8"x8"+1"AL8"x8"+1"AL8"x8"+1"AL8"x8"+1"AL
17171717
8"Ø8"Ø8"Ø8"Ø
10"x10"+1"AL10"x10"+1"AL10"x10"+1"AL10"x10"+1"AL
H.D.H.D.H.D.H.D.
17171717
8"Ø8"Ø8"Ø8"Ø
H.D.H.D.H.D.H.D.
8"Ø8"Ø8"Ø8"Ø
17171717
H.D.H.D.H.D.H.D.
8"Ø8"Ø8"Ø8"Ø
17171717
H.D.H.D.H.D.H.D.
17171717
8"Ø8"Ø8"Ø8"Ø
H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
7777 H.D.H.D.H.D.H.D.
6"Ø6"Ø6"Ø6"Ø
5555 5555 5555
H.D.H.D.H.D.H.D.
10"Ø10"Ø10"Ø10"Ø
8888
H.D.H.D.H.D.H.D.
10"Ø10"Ø10"Ø10"Ø
8888
H.D.H.D.H.D.H.D.
10"Ø10"Ø10"Ø10"Ø
8888
H.D.H.D.H.D.H.D.
10"Ø10"Ø10"Ø10"Ø
8888
10"Ø10"Ø10"Ø10"Ø10"Ø10"Ø10"Ø10"Ø 10"Ø10"Ø10"Ø10"Ø
10"Ø10"Ø10"Ø10"Ø888888888888 8888
H.D.H.D.H.D.H.D.H.D.H.D.H.D.H.D. H.D.H.D.H.D.H.D. H.D.H.D.H.D.H.D.
5555
5555
34"x8" EXH.34"x8" EXH.34"x8" EXH.34"x8" EXH.
16"x8"F.O.16"x8"F.O.16"x8"F.O.16"x8"F.O.
H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
6"Ø6"Ø6"Ø6"Ø
6"Ø6"Ø6"Ø6"Ø
15151515
15151515
H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
6"Ø6"Ø6"Ø6"Ø
6"Ø6"Ø6"Ø6"Ø
15151515
15151515
H.D.H.D.H.D.H.D.
6"Ø6"Ø6"Ø6"Ø
15151515
15151515
15151515
H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
6"Ø6"Ø6"Ø6"Ø
6"Ø6"Ø6"Ø6"Ø
8"Ø8"Ø8"Ø8"Ø
249
JANITOR'S
CLOSET
H.D.H.D.H.D.H.D.
6"Ø6"Ø6"Ø6"Ø
H.D.H.D.H.D.H.D.
6"Ø6"Ø6"Ø6"Ø
31313131
241
JANITOR'S
OFFICE
H.D.H.D.H.D.H.D.
8"Ø8"Ø8"Ø8"Ø
7777
7777
H.D.H.D.H.D.H.D.
8"Ø8"Ø8"Ø8"Ø
20202020
8"Ø8"Ø8"Ø8"Ø
H.D.H.D.H.D.H.D.19191919
7777
8"Ø8"Ø8"Ø8"Ø
8"Ø8"Ø8"Ø8"Ø
H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
8"Ø8"Ø8"Ø8"Ø
H.D.H.D.H.D.H.D.
24242424
24242424
24242424
8"Ø8"Ø8"Ø8"Ø
8"Ø8"Ø8"Ø8"Ø
H.D.H.D.H.D.H.D.
24242424
24242424
8"Ø8"Ø8"Ø8"Ø
8"Ø8"Ø8"Ø8"Ø
24242424
8"Ø8"Ø8"Ø8"Ø
H.D.H.D.H.D.H.D. H.D.H.D.H.D.H.D.H.
D
.
H.
D
.
H.
D
.
H.
D
.
H.D.H.D.H.D.H.D.
24242424 24242424
8"Ø8"Ø8"Ø8"Ø
54"Ø54"Ø54"Ø54"Ø
10"Ø10"Ø10"Ø10"Ø
10"Ø10"Ø10"Ø10"Ø
H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
23232323
23232323
10"Ø10"Ø10"Ø10"Ø
10"Ø10"Ø10"Ø10"Ø
H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
23232323
23232323
10"Ø10"Ø10"Ø10"Ø
10"Ø10"Ø10"Ø10"Ø
H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
23232323
555555555555
10"Ø10"Ø10"Ø10"Ø
10"Ø10"Ø10"Ø10"Ø
H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
23232323
23232323
5555
10"Ø10"Ø10"Ø10"Ø
H.D.H.D.H.D.H.D.
22222222
22222222
10"Ø10"Ø10"Ø10"Ø
H.D.H.D.H.D.H.D.
22222222
10"Ø10"Ø10"Ø10"Ø
H.D.H.D.H.D.H.D.
10"Ø10"Ø10"Ø10"Ø
H.D.H.D.H.D.H.D.
22222222
10"Ø10"Ø10"Ø10"Ø
H.D.H.D.H.D.H.D.
22222222
10"Ø10"Ø10"Ø10"Ø
H.D.H.D.H.D.H.D.
243243243243
VAVRVAVRVAVRVAVR
6"Ø6"Ø6"Ø6"Ø
8"x6"+1"AL8"x6"+1"AL8"x6"+1"AL8"x6"+1"AL
244
FAMILY
RR
H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
313131316"Ø6"Ø6"Ø6"Ø
7777
55555555
H.D.H.D.H.D.H.D.8"Ø8"Ø8"Ø8"Ø
H.D.H.D.H.D.H.D.
8"Ø8"Ø8"Ø8"Ø
8"Ø8"Ø8"Ø8"Ø
H.D.H.D.H.D.H.D.
21212121
21212121
21212121
H.D.H.D.H.D.H.D.
8"Ø8"Ø8"Ø8"Ø
H.D.H.D.H.D.H.D.
8"Ø8"Ø8"Ø8"Ø
8"Ø8"Ø8"Ø8"Ø
H.D.H.D.H.D.H.D.
21212121
21212121
21212121
H.D.H.D.H.D.H.D.
8"Ø8"Ø8"Ø8"Ø
H.D.H.D.H.D.H.D.
8"Ø8"Ø8"Ø8"Ø
H.
D
.
H.
D
.
H.
D
.
H.
D
.
21212121
21212121
7777
H.
D
.
H.
D
.
H.
D
.
H.
D
.
8"Ø8"Ø8"Ø8"Ø
7777
6"Ø6"Ø6"Ø6"ØH.D.H.D.H.D.H.D.
51515151
52525252
53535353
54545454
55555555
57575757
57575757
H.
D
.
H.
D
.
H.
D
.
H.
D
.
56565656
10"Ø10"Ø10"Ø10"Ø
10"Ø10"Ø10"Ø10"Ø
10"Ø10"Ø10"Ø10"Ø 10"Ø10"Ø10"Ø10"Ø
H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
20"x12"+1"AL20"x12"+1"AL20"x12"+1"AL20"x12"+1"AL
2222
FCUFCUFCUFCU
20
"
x
1
0
"
+
1
"
A
L
20
"
x
1
0
"
+
1
"
A
L
20
"
x
1
0
"
+
1
"
A
L
20
"
x
1
0
"
+
1
"
A
L
37373737
38383838
39393939
40404040
41414141
42424242
43434343
44444444
45454545
46464646
47474747
49494949
50505050
A.D.A.D.A.D.A.D.
34"x8" EXH.34"x8" EXH.34"x8" EXH.34"x8" EXH.
20"x12"20"x12"20"x12"20"x12"
48484848
43434343
43434343 43434343
38383838
206
STUDY (MED)
38383838
37373737 37373737
8"
Ø
8"
Ø
8"
Ø
8"
Ø
A.D.A.D.A.D.A.D.39393939 44444444
39393939
39393939
37373737
40404040
4040404040404040
40404040
40404040 40404040
40404040
40404040
40404040
37373737
37373737
6"x6" EXH.6"x6" EXH.6"x6" EXH.6"x6" EXH.
39393939
40404040
47474747
6"
x
6
"
E
X
H
.
6"
x
6
"
E
X
H
.
6"
x
6
"
E
X
H
.
6"
x
6
"
E
X
H
.
40404040 40404040
40404040
40404040
40404040
40404040
5555
5555
44444444
44444444
44444444
44444444
44444444
41414141
40404040
40404040
40404040
40404040
40404040
40404040
33333333
H.
D
.
H.
D
.
H.
D
.
H.
D
.
6"Ø6"Ø6"Ø6"Ø
LVTLVTLVTLVT
5555 5555
LVTLVTLVTLVT
18"x12"+1"AL18"x12"+1"AL18"x12"+1"AL18"x12"+1"AL
18"x12"+1"AL18"x12"+1"AL18"x12"+1"AL18"x12"+1"AL
58585858
59595959
245
I.T.
245A245A245A245A
SACSACSACSAC
245B245B245B245B
SACSACSACSAC
56"x54" F.O.56"x54" F.O.56"x54" F.O.56"x54" F.O.
7777
7777
37373737
48484848
10"Ø10"Ø10"Ø10"Ø
10"Ø10"Ø10"Ø10"Ø
48484848
48484848
60606060
60606060
8"Ø8"Ø8"Ø8"Ø
dbkbo^i=klqbp
A.A.A.A.WHERE UNISTRUTS ARE NOT LOCATED NOR WHERE UNISTRUTS ARE NOT LOCATED NOR WHERE UNISTRUTS ARE NOT LOCATED NOR WHERE UNISTRUTS ARE NOT LOCATED NOR
ACCESSIBLE IN THE BOTTOM OF STRUCTURAL ACCESSIBLE IN THE BOTTOM OF STRUCTURAL ACCESSIBLE IN THE BOTTOM OF STRUCTURAL ACCESSIBLE IN THE BOTTOM OF STRUCTURAL
CONCRETE WEBS, ALL ANCHORS AND SUPPORTS CONCRETE WEBS, ALL ANCHORS AND SUPPORTS CONCRETE WEBS, ALL ANCHORS AND SUPPORTS CONCRETE WEBS, ALL ANCHORS AND SUPPORTS
SHALL BE CONNECTED TO THE SIDES OF THE WEBS. SHALL BE CONNECTED TO THE SIDES OF THE WEBS. SHALL BE CONNECTED TO THE SIDES OF THE WEBS. SHALL BE CONNECTED TO THE SIDES OF THE WEBS.
DO NOT ATTACH TO THE BOTTOM OF THE WEB IF DO NOT ATTACH TO THE BOTTOM OF THE WEB IF DO NOT ATTACH TO THE BOTTOM OF THE WEB IF DO NOT ATTACH TO THE BOTTOM OF THE WEB IF
THERE IS NO EXISTING UNISTRUT.THERE IS NO EXISTING UNISTRUT.THERE IS NO EXISTING UNISTRUT.THERE IS NO EXISTING UNISTRUT.
R.A. OPENINGS WITH SOUND BOOTS DO NOT NEED R.A. OPENINGS WITH SOUND BOOTS DO NOT NEED R.A. OPENINGS WITH SOUND BOOTS DO NOT NEED R.A. OPENINGS WITH SOUND BOOTS DO NOT NEED
TO BE INSTALLED IF THE WALL IN WHICH THEY ARE TO BE INSTALLED IF THE WALL IN WHICH THEY ARE TO BE INSTALLED IF THE WALL IN WHICH THEY ARE TO BE INSTALLED IF THE WALL IN WHICH THEY ARE
LOCATED, IS BETWEEN STRUCTURAL WEBS, AND LOCATED, IS BETWEEN STRUCTURAL WEBS, AND LOCATED, IS BETWEEN STRUCTURAL WEBS, AND LOCATED, IS BETWEEN STRUCTURAL WEBS, AND
THERE ARE OPENINGS, OF TOTAL AREA EQUAL TO OR THERE ARE OPENINGS, OF TOTAL AREA EQUAL TO OR THERE ARE OPENINGS, OF TOTAL AREA EQUAL TO OR THERE ARE OPENINGS, OF TOTAL AREA EQUAL TO OR
GREATER THAN THAT OF THE SOUND BOOT, INTO THE GREATER THAN THAT OF THE SOUND BOOT, INTO THE GREATER THAN THAT OF THE SOUND BOOT, INTO THE GREATER THAN THAT OF THE SOUND BOOT, INTO THE
STRUCTURAL PAN TO ALLOW AIR TO FLOW INTO THE STRUCTURAL PAN TO ALLOW AIR TO FLOW INTO THE STRUCTURAL PAN TO ALLOW AIR TO FLOW INTO THE STRUCTURAL PAN TO ALLOW AIR TO FLOW INTO THE
ADJACENT CEILING SPACE. CONTRACTOR TO ADJACENT CEILING SPACE. CONTRACTOR TO ADJACENT CEILING SPACE. CONTRACTOR TO ADJACENT CEILING SPACE. CONTRACTOR TO
PROVIDE CREDIT FOR SOUND BOOTS THAT WERE PROVIDE CREDIT FOR SOUND BOOTS THAT WERE PROVIDE CREDIT FOR SOUND BOOTS THAT WERE PROVIDE CREDIT FOR SOUND BOOTS THAT WERE
DEEMED UNNECESSARY.DEEMED UNNECESSARY.DEEMED UNNECESSARY.DEEMED UNNECESSARY.
B.B.B.B.
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
Level 02 Area
A Mechanical
Remodel Plan
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
KEY PLAN
A
B
ao^tfkd=klqbp
0000555510101010 10101010 20202020
NOTE
#
DIFFUSER
CALLOUT DESCRIPTION
1111 RO UNIT, REFERENCE PLUMBINGRO UNIT, REFERENCE PLUMBINGRO UNIT, REFERENCE PLUMBINGRO UNIT, REFERENCE PLUMBING
DRAWINGS.DRAWINGS.DRAWINGS.DRAWINGS.
2222 WALL MOUNT HUMIDIFIER PERWALL MOUNT HUMIDIFIER PERWALL MOUNT HUMIDIFIER PERWALL MOUNT HUMIDIFIER PER
MANUFACTURER'SMANUFACTURER'SMANUFACTURER'SMANUFACTURER'S
RECOMMENDATIONS. FIELDRECOMMENDATIONS. FIELDRECOMMENDATIONS. FIELDRECOMMENDATIONS. FIELD
COORDINATE EXACT LOCATION.COORDINATE EXACT LOCATION.COORDINATE EXACT LOCATION.COORDINATE EXACT LOCATION.
3333 FM200 SYSTEM, REFERENCE FIREFM200 SYSTEM, REFERENCE FIREFM200 SYSTEM, REFERENCE FIREFM200 SYSTEM, REFERENCE FIRE
PROTECTION DRAWINGS.PROTECTION DRAWINGS.PROTECTION DRAWINGS.PROTECTION DRAWINGS.
4444 INSTALL BAROMETRIC RELIEF DAMPERINSTALL BAROMETRIC RELIEF DAMPERINSTALL BAROMETRIC RELIEF DAMPERINSTALL BAROMETRIC RELIEF DAMPER
IN WALL ABOVE CEILING.IN WALL ABOVE CEILING.IN WALL ABOVE CEILING.IN WALL ABOVE CEILING.
5555 R-1R-1R-1R-1 22"x22" NK R.A. GRILLE W/ SOUND22"x22" NK R.A. GRILLE W/ SOUND22"x22" NK R.A. GRILLE W/ SOUND22"x22" NK R.A. GRILLE W/ SOUND
BOOTBOOTBOOTBOOT
6666 S-1S-1S-1S-1 430 CFM, 12"Ø NK S.A. DIFFUSER430 CFM, 12"Ø NK S.A. DIFFUSER430 CFM, 12"Ø NK S.A. DIFFUSER430 CFM, 12"Ø NK S.A. DIFFUSER
7777 R-1R-1R-1R-1 22"x10" NK R.A. GRILLE W/ SOUND22"x10" NK R.A. GRILLE W/ SOUND22"x10" NK R.A. GRILLE W/ SOUND22"x10" NK R.A. GRILLE W/ SOUND
BOOTBOOTBOOTBOOT
8888 S-1S-1S-1S-1 340 CFM, 10"Ø NK S.A. DIFFUSER340 CFM, 10"Ø NK S.A. DIFFUSER340 CFM, 10"Ø NK S.A. DIFFUSER340 CFM, 10"Ø NK S.A. DIFFUSER
9999 S-1S-1S-1S-1 265 CFM, 10"Ø NK S.A. DIFFUSER265 CFM, 10"Ø NK S.A. DIFFUSER265 CFM, 10"Ø NK S.A. DIFFUSER265 CFM, 10"Ø NK S.A. DIFFUSER
10101010 S-1S-1S-1S-1 210 CFM, 8"Ø NK S.A. DIFFUSER210 CFM, 8"Ø NK S.A. DIFFUSER210 CFM, 8"Ø NK S.A. DIFFUSER210 CFM, 8"Ø NK S.A. DIFFUSER
11111111 S-1S-1S-1S-1 490 CFM, 12"Ø NK S.A. DIFFUSER490 CFM, 12"Ø NK S.A. DIFFUSER490 CFM, 12"Ø NK S.A. DIFFUSER490 CFM, 12"Ø NK S.A. DIFFUSER
12121212 S-1S-1S-1S-1 245 CFM, 10"Ø NK S.A. DIFFUSER245 CFM, 10"Ø NK S.A. DIFFUSER245 CFM, 10"Ø NK S.A. DIFFUSER245 CFM, 10"Ø NK S.A. DIFFUSER
13131313 S-1S-1S-1S-1 480 CFM, 12"Ø NK S.A. DIFFUSER480 CFM, 12"Ø NK S.A. DIFFUSER480 CFM, 12"Ø NK S.A. DIFFUSER480 CFM, 12"Ø NK S.A. DIFFUSER
14141414 S-1S-1S-1S-1 415 CFM, 10"Ø NK S.A. DIFFUSER415 CFM, 10"Ø NK S.A. DIFFUSER415 CFM, 10"Ø NK S.A. DIFFUSER415 CFM, 10"Ø NK S.A. DIFFUSER
15151515 S-1S-1S-1S-1 105 CFM, 6"Ø NK S.A. DIFFUSER105 CFM, 6"Ø NK S.A. DIFFUSER105 CFM, 6"Ø NK S.A. DIFFUSER105 CFM, 6"Ø NK S.A. DIFFUSER
16161616 S-1S-1S-1S-1 140 CFM, 8"Ø NK S.A. DIFFUSER140 CFM, 8"Ø NK S.A. DIFFUSER140 CFM, 8"Ø NK S.A. DIFFUSER140 CFM, 8"Ø NK S.A. DIFFUSER
17171717 S-1S-1S-1S-1 135 CFM, 8"Ø NK S.A. DIFFUSER135 CFM, 8"Ø NK S.A. DIFFUSER135 CFM, 8"Ø NK S.A. DIFFUSER135 CFM, 8"Ø NK S.A. DIFFUSER
18181818 S-1S-1S-1S-1 110 CFM, 6"Ø NK S.A. DIFFUSER110 CFM, 6"Ø NK S.A. DIFFUSER110 CFM, 6"Ø NK S.A. DIFFUSER110 CFM, 6"Ø NK S.A. DIFFUSER
19191919 S-1S-1S-1S-1 145 CFM, 8"Ø NK S.A. DIFFUSER145 CFM, 8"Ø NK S.A. DIFFUSER145 CFM, 8"Ø NK S.A. DIFFUSER145 CFM, 8"Ø NK S.A. DIFFUSER
20202020 S-1S-1S-1S-1 115 CFM, 8"Ø NK S.A. DIFFUSER115 CFM, 8"Ø NK S.A. DIFFUSER115 CFM, 8"Ø NK S.A. DIFFUSER115 CFM, 8"Ø NK S.A. DIFFUSER
21212121 S-1S-1S-1S-1 220 CFM, 8"Ø NK S.A. DIFFUSER220 CFM, 8"Ø NK S.A. DIFFUSER220 CFM, 8"Ø NK S.A. DIFFUSER220 CFM, 8"Ø NK S.A. DIFFUSER
22222222 S-1S-1S-1S-1 315 CFM, 10"Ø NK S.A. DIFFUSER315 CFM, 10"Ø NK S.A. DIFFUSER315 CFM, 10"Ø NK S.A. DIFFUSER315 CFM, 10"Ø NK S.A. DIFFUSER
23232323 S-1S-1S-1S-1 230 CFM, 8"Ø NK S.A. DIFFUSER230 CFM, 8"Ø NK S.A. DIFFUSER230 CFM, 8"Ø NK S.A. DIFFUSER230 CFM, 8"Ø NK S.A. DIFFUSER
24242424 S-1S-1S-1S-1 180 CFM, 8"Ø NK S.A. DIFFUSER180 CFM, 8"Ø NK S.A. DIFFUSER180 CFM, 8"Ø NK S.A. DIFFUSER180 CFM, 8"Ø NK S.A. DIFFUSER
25252525 S-3S-3S-3S-3 340 CFM, 14"x10" NK R.A. GRILLE340 CFM, 14"x10" NK R.A. GRILLE340 CFM, 14"x10" NK R.A. GRILLE340 CFM, 14"x10" NK R.A. GRILLE
26262626 S-1S-1S-1S-1 175 CFM, 8"Ø NK S.A. DIFFUSER175 CFM, 8"Ø NK S.A. DIFFUSER175 CFM, 8"Ø NK S.A. DIFFUSER175 CFM, 8"Ø NK S.A. DIFFUSER
27272727 S-3S-3S-3S-3 175 CFM, 10"x8" NK S.A. DIFFUSER175 CFM, 10"x8" NK S.A. DIFFUSER175 CFM, 10"x8" NK S.A. DIFFUSER175 CFM, 10"x8" NK S.A. DIFFUSER
28282828 S-2S-2S-2S-2 250 CFM, 10"Ø NK S.A. DIFFUSER250 CFM, 10"Ø NK S.A. DIFFUSER250 CFM, 10"Ø NK S.A. DIFFUSER250 CFM, 10"Ø NK S.A. DIFFUSER
29292929 S-2S-2S-2S-2 350 CFM, 10"Ø NK S.A. DIFFUSER350 CFM, 10"Ø NK S.A. DIFFUSER350 CFM, 10"Ø NK S.A. DIFFUSER350 CFM, 10"Ø NK S.A. DIFFUSER
30303030 S-1S-1S-1S-1 50 CFM, 6"Ø NK S.A. DIFFUSER50 CFM, 6"Ø NK S.A. DIFFUSER50 CFM, 6"Ø NK S.A. DIFFUSER50 CFM, 6"Ø NK S.A. DIFFUSER
31313131 S-2S-2S-2S-2 50 CFM, 6"Ø NK S.A. DIFFUSER50 CFM, 6"Ø NK S.A. DIFFUSER50 CFM, 6"Ø NK S.A. DIFFUSER50 CFM, 6"Ø NK S.A. DIFFUSER
32323232 S-1S-1S-1S-1 125 CFM, 8"Ø NK S.A. DIFFUSER125 CFM, 8"Ø NK S.A. DIFFUSER125 CFM, 8"Ø NK S.A. DIFFUSER125 CFM, 8"Ø NK S.A. DIFFUSER
33333333 S-1S-1S-1S-1 100 CFM, 6"Ø NK S.A. DIFFUSER100 CFM, 6"Ø NK S.A. DIFFUSER100 CFM, 6"Ø NK S.A. DIFFUSER100 CFM, 6"Ø NK S.A. DIFFUSER
34343434 S-1S-1S-1S-1 165 CFM, 8"Ø NK S.A. DIFFUSER165 CFM, 8"Ø NK S.A. DIFFUSER165 CFM, 8"Ø NK S.A. DIFFUSER165 CFM, 8"Ø NK S.A. DIFFUSER
35353535 R-1R-1R-1R-1 660 CFM, 16"x16" NK R.A. GRILLE660 CFM, 16"x16" NK R.A. GRILLE660 CFM, 16"x16" NK R.A. GRILLE660 CFM, 16"x16" NK R.A. GRILLE
36363636 R-1R-1R-1R-1 330 CFM, 12"x12" NK R.A. GRILLE330 CFM, 12"x12" NK R.A. GRILLE330 CFM, 12"x12" NK R.A. GRILLE330 CFM, 12"x12" NK R.A. GRILLE
37373737 12"x12"+1"AL R.A. OPENING W/12"x12"+1"AL R.A. OPENING W/12"x12"+1"AL R.A. OPENING W/12"x12"+1"AL R.A. OPENING W/
SOUND BOOT ABOVE CEILING.SOUND BOOT ABOVE CEILING.SOUND BOOT ABOVE CEILING.SOUND BOOT ABOVE CEILING.
38383838 16"x16"+1"AL R.A. OPENING W/16"x16"+1"AL R.A. OPENING W/16"x16"+1"AL R.A. OPENING W/16"x16"+1"AL R.A. OPENING W/
SOUND BOOT ABOVE CEILING.SOUND BOOT ABOVE CEILING.SOUND BOOT ABOVE CEILING.SOUND BOOT ABOVE CEILING.
39393939 18"x18"+1"AL R.A. OPENING W/18"x18"+1"AL R.A. OPENING W/18"x18"+1"AL R.A. OPENING W/18"x18"+1"AL R.A. OPENING W/
SOUND BOOT ABOVE CEILING.SOUND BOOT ABOVE CEILING.SOUND BOOT ABOVE CEILING.SOUND BOOT ABOVE CEILING.
40404040 22"x22"+1"AL R.A. OPENING W/22"x22"+1"AL R.A. OPENING W/22"x22"+1"AL R.A. OPENING W/22"x22"+1"AL R.A. OPENING W/
SOUND BOOT ABOVE CEILING.SOUND BOOT ABOVE CEILING.SOUND BOOT ABOVE CEILING.SOUND BOOT ABOVE CEILING.
41414141 144"x22" R.A. OPENING IN WALL144"x22" R.A. OPENING IN WALL144"x22" R.A. OPENING IN WALL144"x22" R.A. OPENING IN WALL
ABOVE CEILING.ABOVE CEILING.ABOVE CEILING.ABOVE CEILING.
42424242 72"x36"+1"AL R.A. OPENING IN WALL72"x36"+1"AL R.A. OPENING IN WALL72"x36"+1"AL R.A. OPENING IN WALL72"x36"+1"AL R.A. OPENING IN WALL
ABOVE CEILING W/ F.S.D.ABOVE CEILING W/ F.S.D.ABOVE CEILING W/ F.S.D.ABOVE CEILING W/ F.S.D.
43434343 S-1S-1S-1S-1 300 CFM, 10"Ø NK S.A. DIFFUSER300 CFM, 10"Ø NK S.A. DIFFUSER300 CFM, 10"Ø NK S.A. DIFFUSER300 CFM, 10"Ø NK S.A. DIFFUSER
44444444 48"x22" R.A. OPENING IN WALL ABOVE48"x22" R.A. OPENING IN WALL ABOVE48"x22" R.A. OPENING IN WALL ABOVE48"x22" R.A. OPENING IN WALL ABOVE
CEILING.CEILING.CEILING.CEILING.
45454545 66"x22" R.A. OPENING IN WALL ABOVE66"x22" R.A. OPENING IN WALL ABOVE66"x22" R.A. OPENING IN WALL ABOVE66"x22" R.A. OPENING IN WALL ABOVE
CEILING.CEILING.CEILING.CEILING.
46464646 48"x22" R.A. OPENING IN WALL ABOVE48"x22" R.A. OPENING IN WALL ABOVE48"x22" R.A. OPENING IN WALL ABOVE48"x22" R.A. OPENING IN WALL ABOVE
CEILING W/ F.S.D.CEILING W/ F.S.D.CEILING W/ F.S.D.CEILING W/ F.S.D.
47474747 E-1E-1E-1E-1 100 CFM, 6"x6" NK E.A. GRILLE100 CFM, 6"x6" NK E.A. GRILLE100 CFM, 6"x6" NK E.A. GRILLE100 CFM, 6"x6" NK E.A. GRILLE
SCALE:SCALE:SCALE:SCALE:MH102aMH102aMH102aMH102a 1/8" = 1'1/8" = 1'1/8" = 1'1/8" = 1'----0"0"0"0"
ibsbi=O=^ob^=^=jb`e^kf`^i=objlabi=mi^k1111
NOTE
#
DIFFUSER
CALLOUT DESCRIPTION
48484848 E-1E-1E-1E-1 350 CFM, MATCH PREVIOUS GRILLE350 CFM, MATCH PREVIOUS GRILLE350 CFM, MATCH PREVIOUS GRILLE350 CFM, MATCH PREVIOUS GRILLE
FACE AND NECK SIZE AND CONNECTFACE AND NECK SIZE AND CONNECTFACE AND NECK SIZE AND CONNECTFACE AND NECK SIZE AND CONNECT
TO EXISTING E.A. DUCTWORK.TO EXISTING E.A. DUCTWORK.TO EXISTING E.A. DUCTWORK.TO EXISTING E.A. DUCTWORK.
49494949 BALANCE EXISTING E.A. GRILLE TO 100BALANCE EXISTING E.A. GRILLE TO 100BALANCE EXISTING E.A. GRILLE TO 100BALANCE EXISTING E.A. GRILLE TO 100
CFM.CFM.CFM.CFM.
50505050 24"x12" E.A. DUCT UP FROM BELOW.24"x12" E.A. DUCT UP FROM BELOW.24"x12" E.A. DUCT UP FROM BELOW.24"x12" E.A. DUCT UP FROM BELOW.
RISE 26"x18" E.A. DUCT UP TO LEVELRISE 26"x18" E.A. DUCT UP TO LEVELRISE 26"x18" E.A. DUCT UP TO LEVELRISE 26"x18" E.A. DUCT UP TO LEVEL
ABOVE.ABOVE.ABOVE.ABOVE.
51515151 TIE 10"x10"+2"AL O.A. DUCT FROMTIE 10"x10"+2"AL O.A. DUCT FROMTIE 10"x10"+2"AL O.A. DUCT FROMTIE 10"x10"+2"AL O.A. DUCT FROM
LOUVER L-1 INTO FAN COIL UNITLOUVER L-1 INTO FAN COIL UNITLOUVER L-1 INTO FAN COIL UNITLOUVER L-1 INTO FAN COIL UNIT
DXFCU-1 MIXING BOX. INSTALL ADXFCU-1 MIXING BOX. INSTALL ADXFCU-1 MIXING BOX. INSTALL ADXFCU-1 MIXING BOX. INSTALL A
MANUAL BALANCE DAMPER INMANUAL BALANCE DAMPER INMANUAL BALANCE DAMPER INMANUAL BALANCE DAMPER IN
DUCTWORK AND BALANCE OUTSIDEDUCTWORK AND BALANCE OUTSIDEDUCTWORK AND BALANCE OUTSIDEDUCTWORK AND BALANCE OUTSIDE
AIR TO 150 CFM.AIR TO 150 CFM.AIR TO 150 CFM.AIR TO 150 CFM.
52525252 TRANSITION AS REQUIRED FROMTRANSITION AS REQUIRED FROMTRANSITION AS REQUIRED FROMTRANSITION AS REQUIRED FROM
DXFCU-1 OUTLET TO 14"x14"+1"ALDXFCU-1 OUTLET TO 14"x14"+1"ALDXFCU-1 OUTLET TO 14"x14"+1"ALDXFCU-1 OUTLET TO 14"x14"+1"AL
SUPPLY AIR DUCT.SUPPLY AIR DUCT.SUPPLY AIR DUCT.SUPPLY AIR DUCT.
53535353 TRANSITION 14"x14"+1"AL RETURN AIRTRANSITION 14"x14"+1"AL RETURN AIRTRANSITION 14"x14"+1"AL RETURN AIRTRANSITION 14"x14"+1"AL RETURN AIR
DUCT AS REQUIRED AND CONNECT TODUCT AS REQUIRED AND CONNECT TODUCT AS REQUIRED AND CONNECT TODUCT AS REQUIRED AND CONNECT TO
DXFCU-1 MIXING BOX.DXFCU-1 MIXING BOX.DXFCU-1 MIXING BOX.DXFCU-1 MIXING BOX.
54545454 INSTALL STEAM DISTRIBUTOR ININSTALL STEAM DISTRIBUTOR ININSTALL STEAM DISTRIBUTOR ININSTALL STEAM DISTRIBUTOR IN
DUCTWORK RISE PERDUCTWORK RISE PERDUCTWORK RISE PERDUCTWORK RISE PER
MANUFACTURERS REQUIREMENTS.MANUFACTURERS REQUIREMENTS.MANUFACTURERS REQUIREMENTS.MANUFACTURERS REQUIREMENTS.
55555555 INSTALL/ROUTE STEAM DISTRIBUTIONINSTALL/ROUTE STEAM DISTRIBUTIONINSTALL/ROUTE STEAM DISTRIBUTIONINSTALL/ROUTE STEAM DISTRIBUTION
HOSE AND CONDENSATE HOSE PERHOSE AND CONDENSATE HOSE PERHOSE AND CONDENSATE HOSE PERHOSE AND CONDENSATE HOSE PER
MANUFACTURE'S REQUIREMENTS.MANUFACTURE'S REQUIREMENTS.MANUFACTURE'S REQUIREMENTS.MANUFACTURE'S REQUIREMENTS.
56565656 4" CONCRETE HOUSEKEEPING PAD.4" CONCRETE HOUSEKEEPING PAD.4" CONCRETE HOUSEKEEPING PAD.4" CONCRETE HOUSEKEEPING PAD.
57575757 SEAL AROUND DUCTWORK WALLSEAL AROUND DUCTWORK WALLSEAL AROUND DUCTWORK WALLSEAL AROUND DUCTWORK WALL
PENETRATION AIR TIGHT TO MAINTAINPENETRATION AIR TIGHT TO MAINTAINPENETRATION AIR TIGHT TO MAINTAINPENETRATION AIR TIGHT TO MAINTAIN
VAPOR BARRIER AROUND ARCHIVEVAPOR BARRIER AROUND ARCHIVEVAPOR BARRIER AROUND ARCHIVEVAPOR BARRIER AROUND ARCHIVE
ROOM.ROOM.ROOM.ROOM.
58585858 RISE 54"x56" F.O. S.A. DUCT FROMRISE 54"x56" F.O. S.A. DUCT FROMRISE 54"x56" F.O. S.A. DUCT FROMRISE 54"x56" F.O. S.A. DUCT FROM
LEVEL BELOW. RISE 54"x24" F.O. S.A.LEVEL BELOW. RISE 54"x24" F.O. S.A.LEVEL BELOW. RISE 54"x24" F.O. S.A.LEVEL BELOW. RISE 54"x24" F.O. S.A.
DUCT TO LEVEL ABOVE.DUCT TO LEVEL ABOVE.DUCT TO LEVEL ABOVE.DUCT TO LEVEL ABOVE.
59595959 RISE 54"Ø S.A. DUCT FROM LEVELRISE 54"Ø S.A. DUCT FROM LEVELRISE 54"Ø S.A. DUCT FROM LEVELRISE 54"Ø S.A. DUCT FROM LEVEL
BELOW. RISE 54"x24" F.O. S.A. DUCTBELOW. RISE 54"x24" F.O. S.A. DUCTBELOW. RISE 54"x24" F.O. S.A. DUCTBELOW. RISE 54"x24" F.O. S.A. DUCT
TO LEVEL ABOVE.TO LEVEL ABOVE.TO LEVEL ABOVE.TO LEVEL ABOVE.
60606060 T-1T-1T-1T-1 18"x18" NK T.A. GRILLE W/ SOUND18"x18" NK T.A. GRILLE W/ SOUND18"x18" NK T.A. GRILLE W/ SOUND18"x18" NK T.A. GRILLE W/ SOUND
BOOTBOOTBOOTBOOT
ao^tfkd=klqbp
16161616151515151414141413131313121212121111111110101010999988887777
KKKK
HHHH
FFFF
DDDD
BBBB
AAAA
252
STUDY SKILLS
254
OPEN TUTORING
256
WRITING CENTER OPEN TUTORING
256B
OFFICE
256A
PREP / STORAGE
256C
OFFICE
258
CLASSROOM
260
CLASSROOM 264
OFFICE
265
OFFICE
266
STUDY
267
STUDY
268
STUDY
269
STUDY
270
OPEN TUTORING CENTER
270F
PREFUNCTION
270E
PRE-FUNCTION
270D
PRE-FUNCTION
270C
PRE-FUNCTION
270B
PREP / STORAGE
270J
STORAGE
270H
STUDY
272
CLASSROOM
278
CLASSROOM
280
TR / COMM.
286
ADJUNCT OFFICE
288B
OFFICE
288
ENGLISH TRANSITION CENTER
52
"
x
2
4
"
F
.
O
.
52
"
x
2
4
"
F
.
O
.
52
"
x
2
4
"
F
.
O
.
52
"
x
2
4
"
F
.
O
.
46"x16"F.O.46"x16"F.O.46"x16"F.O.46"x16"F.O.36"x14"F.O.36"x14"F.O.36"x14"F.O.36"x14"F.O.
36
"
x
1
4
"
F
.
O
.
36
"
x
1
4
"
F
.
O
.
36
"
x
1
4
"
F
.
O
.
36
"
x
1
4
"
F
.
O
.
52"x24"F.O.52"x24"F.O.52"x24"F.O.52"x24"F.O.
16"Ø16"Ø16"Ø16"Ø
12"Ø12"Ø12"Ø12"Ø
14"Ø14"Ø14"Ø14"Ø
14"Ø14"Ø14"Ø14"Ø
22"x16"F.O.22"x16"F.O.22"x16"F.O.22"x16"F.O.
288H
STORAGE
299
STOR
14"Ø14"Ø14"Ø14"Ø
18"x12"+1"AL18"x12"+1"AL18"x12"+1"AL18"x12"+1"AL
270AA270AA270AA270AA
VAVRVAVRVAVRVAVR
18"x12"+1"AL18"x12"+1"AL18"x12"+1"AL18"x12"+1"AL
14"Ø14"Ø14"Ø14"Ø
270BB270BB270BB270BB
VAVRVAVRVAVRVAVR
18"x14"+1"AL18"x14"+1"AL18"x14"+1"AL18"x14"+1"AL
14"Ø14"Ø14"Ø14"Ø
270CC270CC270CC270CC
VAVRVAVRVAVRVAVR
8"x10"+1"AL8"x10"+1"AL8"x10"+1"AL8"x10"+1"AL
46"x16"F.O.46"x16"F.O.46"x16"F.O.46"x16"F.O.
6"Ø6"Ø6"Ø6"Ø
265265265265
VAVRVAVRVAVRVAVR
8"x8"+1"AL8"x8"+1"AL8"x8"+1"AL8"x8"+1"AL
6"
Ø
6"
Ø
6"
Ø
6"
Ø
266266266266
VAVRVAVRVAVRVAVR
8"x8"+1"AL8"x8"+1"AL8"x8"+1"AL8"x8"+1"AL
6"
Ø
6"
Ø
6"
Ø
6"
Ø
267267267267
VAVRVAVRVAVRVAVR
8"x8"+1"AL8"x8"+1"AL8"x8"+1"AL8"x8"+1"AL
268268268268
VAVRVAVRVAVRVAVR
8"x8"+1"AL8"x8"+1"AL8"x8"+1"AL8"x8"+1"AL
6"Ø6"Ø6"Ø6"Ø
8"Ø8"Ø8"Ø8"Ø
270J270J270J270J
VAVRVAVRVAVRVAVR
8"x8"+1"AL8"x8"+1"AL8"x8"+1"AL8"x8"+1"AL
6"Ø6"Ø6"Ø6"Ø
270H270H270H270H
VAVRVAVRVAVRVAVR
10"x8"+1"AL10"x8"+1"AL10"x8"+1"AL10"x8"+1"AL
6"
Ø
6"
Ø
6"
Ø
6"
Ø
270F270F270F270F
VAVRVAVRVAVRVAVR
269269269269
VAVRVAVRVAVRVAVR
10"x10"+1"AL10"x10"+1"AL10"x10"+1"AL10"x10"+1"AL
8"Ø8"Ø8"Ø8"Ø
12
"
Ø
12
"
Ø
12
"
Ø
12
"
Ø
276276276276
VAVRVAVRVAVRVAVR
14
"
x
1
2
"
+
1
"
A
L
14
"
x
1
2
"
+
1
"
A
L
14
"
x
1
2
"
+
1
"
A
L
14
"
x
1
2
"
+
1
"
A
L
270DD270DD270DD270DD
VAVRVAVRVAVRVAVR
12"x12"+1"AL12"x12"+1"AL12"x12"+1"AL12"x12"+1"AL
10"Ø10"Ø10"Ø10"Ø
10
"
Ø
10
"
Ø
10
"
Ø
10
"
Ø
278278278278
VAVRVAVRVAVRVAVR
12
"
x
1
2
"
+
1
"
A
L
12
"
x
1
2
"
+
1
"
A
L
12
"
x
1
2
"
+
1
"
A
L
12
"
x
1
2
"
+
1
"
A
L
10
"
Ø
10
"
Ø
10
"
Ø
10
"
Ø
274274274274
VAVRVAVRVAVRVAVR
12"x12"+1"AL12"x12"+1"AL12"x12"+1"AL12"x12"+1"AL
14"Ø14"Ø14"Ø14"Ø 12"Ø12"Ø12"Ø12"Ø
272B272B272B272B
VAVRVAVRVAVRVAVR
14
"
x
1
4
"
+
1
"
A
L
14
"
x
1
4
"
+
1
"
A
L
14
"
x
1
4
"
+
1
"
A
L
14
"
x
1
4
"
+
1
"
A
L
264264264264
VAVRVAVRVAVRVAVR
8"x6"+1"AL8"x6"+1"AL8"x6"+1"AL8"x6"+1"AL
6"Ø6"Ø6"Ø6"Ø
6"Ø6"Ø6"Ø6"Ø
270B270B270B270B
VAVRVAVRVAVRVAVR
8"x8"+1"AL8"x8"+1"AL8"x8"+1"AL8"x8"+1"AL
8"Ø8"Ø8"Ø8"Ø
270A270A270A270A
VAVRVAVRVAVRVAVR
10"x8"+1"AL10"x8"+1"AL10"x8"+1"AL10"x8"+1"AL
270A
RECEPTION
284
WOMEN'S RESTROOM
282
MEN'S RESTROOM
270D270D270D270D
VAVRVAVRVAVRVAVR
8"Ø8"Ø8"Ø8"Ø
10"x8"+1"AL10"x8"+1"AL10"x8"+1"AL10"x8"+1"AL
6"Ø6"Ø6"Ø6"Ø
2222----WWWW
VAVRVAVRVAVRVAVR
2-W
HALL
8"x8"+1"AL8"x8"+1"AL8"x8"+1"AL8"x8"+1"AL
14"x14"+1"AL14"x14"+1"AL14"x14"+1"AL14"x14"+1"AL
12"Ø12"Ø12"Ø12"Ø
260260260260
VAVRVAVRVAVRVAVR
14"x14"+1"AL14"x14"+1"AL14"x14"+1"AL14"x14"+1"AL
12
"
Ø
12
"
Ø
12
"
Ø
12
"
Ø
258258258258
VAVRVAVRVAVRVAVR
16"x14"+1"AL16"x14"+1"AL16"x14"+1"AL16"x14"+1"AL
256256256256
VAVRVAVRVAVRVAVR
6"
Ø
6"
Ø
6"
Ø
6"
Ø
256A256A256A256A
VAVRVAVRVAVRVAVR
8"x10"+1"AL8"x10"+1"AL8"x10"+1"AL8"x10"+1"AL
6"
Ø
6"
Ø
6"
Ø
6"
Ø
256B256B256B256B
VAVRVAVRVAVRVAVR
8"x10"+1"AL8"x10"+1"AL8"x10"+1"AL8"x10"+1"AL
256C256C256C256C
VAVRVAVRVAVRVAVR
8"x10"+1"AL8"x10"+1"AL8"x10"+1"AL8"x10"+1"AL
6"
Ø
6"
Ø
6"
Ø
6"
Ø
14"Ø14"Ø14"Ø14"Ø
288AA288AA288AA288AA
VAVRVAVRVAVRVAVR
14
"
Ø
14
"
Ø
14
"
Ø
14
"
Ø
18"x12"+1"AL18"x12"+1"AL18"x12"+1"AL18"x12"+1"AL
8"Ø8"Ø8"Ø8"Ø
288BB288BB288BB288BB
VAVRVAVRVAVRVAVR
10
"
x
8
"
+
1
"
A
L
10
"
x
8
"
+
1
"
A
L
10
"
x
8
"
+
1
"
A
L
10
"
x
8
"
+
1
"
A
L
6"Ø6"Ø6"Ø6"Ø
286286286286
VAVRVAVRVAVRVAVR
8"x6"+1"AL8"x6"+1"AL8"x6"+1"AL8"x6"+1"AL
6"Ø6"Ø6"Ø6"Ø 288A288A288A288A
VAVRVAVRVAVRVAVR
8"x6"+1"AL8"x6"+1"AL8"x6"+1"AL8"x6"+1"AL
288B288B288B288B
VAVRVAVRVAVRVAVR
8"
Ø
8"
Ø
8"
Ø
8"
Ø
8"x10"+1"AL8"x10"+1"AL8"x10"+1"AL8"x10"+1"AL
6"Ø6"Ø6"Ø6"Ø
2222----QQQQ
VAVRVAVRVAVRVAVR8"x8"+1"AL8"x8"+1"AL8"x8"+1"AL8"x8"+1"AL
252A
STUDY
252B
STUDY
252C
STUDY
2-R
ELEV
252G
PREP / STORAGE
252F
STORAGE
252D
OFFICE
252E
OFFICE
6"Ø6"Ø6"Ø6"Ø
252A252A252A252A
VAVRVAVRVAVRVAVR
6"x8"+1"AL6"x8"+1"AL6"x8"+1"AL6"x8"+1"AL
6"Ø6"Ø6"Ø6"Ø
252B252B252B252B
VAVRVAVRVAVRVAVR
6"x8"+1"AL6"x8"+1"AL6"x8"+1"AL6"x8"+1"AL
252G252G252G252G
VAVRVAVRVAVRVAVR 10"x8"+1"AL10"x8"+1"AL10"x8"+1"AL10"x8"+1"AL
252E252E252E252E
VAVRVAVRVAVRVAVR
8"Ø8"Ø8"Ø8"Ø
10"x8"+1"AL10"x8"+1"AL10"x8"+1"AL10"x8"+1"AL
14"Ø14"Ø14"Ø14"Ø
16"x14"+1"AL16"x14"+1"AL16"x14"+1"AL16"x14"+1"AL
252BB252BB252BB252BB
VAVRVAVRVAVRVAVR 6"Ø6"Ø6"Ø6"Ø
252C252C252C252C
VAVRVAVRVAVRVAVR
8"x8"+1"AL8"x8"+1"AL8"x8"+1"AL8"x8"+1"AL
8"Ø8"Ø8"Ø8"Ø
8"x8"+1"AL8"x8"+1"AL8"x8"+1"AL8"x8"+1"AL
252D252D252D252D
VAVRVAVRVAVRVAVR
299299299299
VAVRVAVRVAVRVAVR
12
"
x
1
2
"
+
1
"
A
L
12
"
x
1
2
"
+
1
"
A
L
12
"
x
1
2
"
+
1
"
A
L
12
"
x
1
2
"
+
1
"
A
L
12"Ø12"Ø12"Ø12"Ø
12"Ø12"Ø12"Ø12"Ø
254254254254
VAVRVAVRVAVRVAVR
14"x14"+1"AL14"x14"+1"AL14"x14"+1"AL14"x14"+1"AL
6"Ø6"Ø6"Ø6"Ø
2222----UUUU
VAVRVAVRVAVRVAVR
8"x8"+1"AL8"x8"+1"AL8"x8"+1"AL8"x8"+1"AL
8"Ø8"Ø8"Ø8"Ø
288G
STUDY
288F
STUDY
288E
STUDY 288D
STUDY
288C
OFFICE
288A
STUDY
2-P
STAIR
2-Q
HALL
6"
Ø
6"
Ø
6"
Ø
6"
Ø288G288G288G288G
VAVRVAVRVAVRVAVR
8"x6"+1"AL8"x6"+1"AL8"x6"+1"AL8"x6"+1"AL
6"
Ø
6"
Ø
6"
Ø
6"
Ø
288F288F288F288F
VAVRVAVRVAVRVAVR
8"x6"+1"AL8"x6"+1"AL8"x6"+1"AL8"x6"+1"AL
6"
Ø
6"
Ø
6"
Ø
6"
Ø
288E288E288E288E
VAVRVAVRVAVRVAVR
8"x6"+1"AL8"x6"+1"AL8"x6"+1"AL8"x6"+1"AL
6"
Ø
6"
Ø
6"
Ø
6"
Ø
288D288D288D288D
VAVRVAVRVAVRVAVR
6"x8"+1"AL6"x8"+1"AL6"x8"+1"AL6"x8"+1"AL
284284284284
VAVRVAVRVAVRVAVR
8"Ø8"Ø8"Ø8"Ø
8"Ø8"Ø8"Ø8"Ø
8"x10"+1"AL8"x10"+1"AL8"x10"+1"AL8"x10"+1"AL
288C288C288C288C
VAVRVAVRVAVRVAVR
5555
6666
7777
8888999910101010
11111111
12121212
13131313
14141414
15151515
16161616
17171717
18181818 19191919
20202020
21212121
22222222
23232323
24242424
2525252526262626
27272727
28282828
1111
2222
3333
4444
20202020
24242424
24242424 24242424
24242424
24242424
8"Ø8"Ø8"Ø8"Ø
8"Ø8"Ø8"Ø8"Ø
8"Ø8"Ø8"Ø8"Ø
H.D.H.D.H.D.H.D. H.D.H.D.H.D.H.D.
H.
D
.
H.
D
.
H.
D
.
H.
D
.
H.
D
.
H.
D
.
H.
D
.
H.
D
.
H.D.H.D.H.D.H.D. H.D.H.D.H.D.H.D.
8"Ø8"Ø8"Ø8"Ø
8"Ø8"Ø8"Ø8"Ø
8"
Ø
8"
Ø
8"
Ø
8"
Ø
2222
22222222
2222 2222
2222
1111
H.D.H.D.H.D.H.D.H.
D
.
H.
D
.
H.
D
.
H.
D
.
10"Ø10"Ø10"Ø10"Ø
10"Ø10"Ø10"Ø10"Ø
8"Ø8"Ø8"Ø8"Ø
H.D.H.D.H.D.H.D.
3333
4444 8"Ø8"Ø8"Ø8"Ø
3333
4444 8"Ø8"Ø8"Ø8"Ø
3333
8"Ø8"Ø8"Ø8"Ø8"Ø8"Ø8"Ø8"Ø
H.D.H.D.H.D.H.D.H.D.H.D.H.D.H.D.H.D.H.D.H.D.H.D.H.D.H.D.H.D.H.D.
3333
8"Ø8"Ø8"Ø8"Ø
H.D.H.D.H.D.H.D.
8"Ø8"Ø8"Ø8"Ø
H.D.H.D.H.D.H.D.
8"Ø8"Ø8"Ø8"Ø
H.D.H.D.H.D.H.D.H.D.H.D.H.D.H.D.
8"
Ø
8"
Ø
8"
Ø
8"
Ø
8"Ø8"Ø8"Ø8"Ø
H.D.H.D.H.D.H.D.
8"Ø8"Ø8"Ø8"Ø
H.D.H.D.H.D.H.D.
14141414
14141414 14141414
14141414 14141414
2222
10"Ø10"Ø10"Ø10"Ø
H.D.H.D.H.D.H.D.
10"Ø10"Ø10"Ø10"Ø
H.D.H.D.H.D.H.D.
25252525
10"Ø10"Ø10"Ø10"Ø 10"Ø10"Ø10"Ø10"Ø
H.D.H.D.H.D.H.D. H.D.H.D.H.D.H.D.H.D.H.D.H.D.H.D. H.D.H.D.H.D.H.D.
10"Ø10"Ø10"Ø10"Ø 10"Ø10"Ø10"Ø10"Ø
25252525
25252525
25252525 25252525
8"Ø8"Ø8"Ø8"Ø 8"Ø8"Ø8"Ø8"Ø
H.D.H.D.H.D.H.D. H.D.H.D.H.D.H.D.
26262626
280A280A280A280A
SACSACSACSAC
14"x8"+1"AL14"x8"+1"AL14"x8"+1"AL14"x8"+1"AL
2626262626262626H.D.H.D.H.D.H.D. H.D.H.D.H.D.H.D.8"Ø8"Ø8"Ø8"Ø
8"Ø8"Ø8"Ø8"Ø
2626262626262626
H.D.H.D.H.D.H.D. H.D.H.D.H.D.H.D.8"Ø8"Ø8"Ø8"Ø
8"Ø8"Ø8"Ø8"Ø
8"Ø8"Ø8"Ø8"Ø
H.D.H.D.H.D.H.D.
3333
8"x8"+1"AL8"x8"+1"AL8"x8"+1"AL8"x8"+1"AL 6"Ø6"Ø6"Ø6"Ø
270G270G270G270G
VAVRVAVRVAVRVAVR
270G
STUDY
3333
3333
3333
10"Ø10"Ø10"Ø10"Ø
H.
D
.
H.
D
.
H.
D
.
H.
D
.
8"Ø8"Ø8"Ø8"Ø
H.D.H.D.H.D.H.D.
12121212
H.
D
.
H.
D
.
H.
D
.
H.
D
.
22222222 10"Ø10"Ø10"Ø10"ØH.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
10"Ø10"Ø10"Ø10"Ø
10"Ø10"Ø10"Ø10"ØH.D.H.D.H.D.H.D.
10"Ø10"Ø10"Ø10"Ø
2222222222222222
H.D.H.D.H.D.H.D.
2222
2222
2222
8"Ø8"Ø8"Ø8"Ø
8"Ø8"Ø8"Ø8"Ø
H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
21212121
8"Ø8"Ø8"Ø8"Ø
H.D.H.D.H.D.H.D.
8"Ø8"Ø8"Ø8"Ø
H.D.H.D.H.D.H.D.
2121212121212121
274
CLASSROOM
276
CLASSROOM
H.D.H.D.H.D.H.D.
44448"Ø8"Ø8"Ø8"Ø
H.D.H.D.H.D.H.D.4444
8"Ø8"Ø8"Ø8"Ø
4444
8"Ø8"Ø8"Ø8"Ø
4444
H.D.H.D.H.D.H.D.H.D.H.D.H.D.H.D.
2222
8"Ø8"Ø8"Ø8"Ø
2222
8"Ø8"Ø8"Ø8"Ø
8"Ø8"Ø8"Ø8"Ø H.D.H.D.H.D.H.D.5555
5555 5555
8"Ø8"Ø8"Ø8"Ø
5555
8"Ø8"Ø8"Ø8"Ø
H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
2222
2222
10"Ø10"Ø10"Ø10"ØH.D.H.D.H.D.H.D.
10"Ø10"Ø10"Ø10"Ø
H.D.H.D.H.D.H.D.
6666
6666
6666
10"Ø10"Ø10"Ø10"ØH.D.H.D.H.D.H.D.
10"Ø10"Ø10"Ø10"Ø
H.D.H.D.H.D.H.D.
22222222
8"Ø8"Ø8"Ø8"Ø 8"Ø8"Ø8"Ø8"Ø
H.D.H.D.H.D.H.D.H.D.H.D.H.D.H.D.
77777777
H.D.H.D.H.D.H.D.
8"Ø8"Ø8"Ø8"Ø7777
8"Ø8"Ø8"Ø8"Ø 8"Ø8"Ø8"Ø8"Ø
H.D.H.D.H.D.H.D.H.D.H.D.H.D.H.D.H.D.H.D.H.D.H.D.
8"Ø8"Ø8"Ø8"Ø
7777 77777777
3333 3333 3333
10"Ø10"Ø10"Ø10"Ø10"Ø10"Ø10"Ø10"Ø
H.D.H.D.H.D.H.D. H.D.H.D.H.D.H.D.
10"Ø10"Ø10"Ø10"Ø
H.D.H.D.H.D.H.D.
22222222
2222
H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D. H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
1111111111111111
11111111
11111111
11111111 8"Ø8"Ø8"Ø8"Ø
8"Ø8"Ø8"Ø8"Ø
8"Ø8"Ø8"Ø8"Ø
8"Ø8"Ø8"Ø8"Ø
14"x12"+1"AL14"x12"+1"AL14"x12"+1"AL14"x12"+1"AL
10"Ø10"Ø10"Ø10"Ø
10"Ø10"Ø10"Ø10"Ø
H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
2222
8"Ø8"Ø8"Ø8"Ø
H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
5555
5555
8"Ø8"Ø8"Ø8"Ø
H.D.H.D.H.D.H.D.
5555
5555
5555
5555
8"Ø8"Ø8"Ø8"Ø
8"Ø8"Ø8"Ø8"ØH.D.H.D.H.D.H.D.
14141414
3333
3333
H.D.H.D.H.D.H.D.
10"Ø10"Ø10"Ø10"Ø
3333
H.D.H.D.H.D.H.D.
6"Ø6"Ø6"Ø6"Ø
H.D.H.D.H.D.H.D.
3333
10
"
Ø
10
"
Ø
10
"
Ø
10
"
Ø
8"Ø8"Ø8"Ø8"Ø
H.D.H.D.H.D.H.D.
3333
16161616
H.D.H.D.H.D.H.D.
6"Ø6"Ø6"Ø6"Ø
333333333333
16161616
6"Ø6"Ø6"Ø6"Ø
16161616
6"Ø6"Ø6"Ø6"Ø
H.D.H.D.H.D.H.D.H.D.H.D.H.D.H.D.H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
6"Ø6"Ø6"Ø6"Ø
H.D.H.D.H.D.H.D.
6"Ø6"Ø6"Ø6"Ø
17171717
17171717
H.D.H.D.H.D.H.D.
6"Ø6"Ø6"Ø6"Ø
H.D.H.D.H.D.H.D.
6"Ø6"Ø6"Ø6"Ø
17171717
8"Ø8"Ø8"Ø8"Ø
14141414
H.D.H.D.H.D.H.D.
8"Ø8"Ø8"Ø8"Ø
H.D.H.D.H.D.H.D.
14141414
8"Ø8"Ø8"Ø8"Ø
14141414
H.D.H.D.H.D.H.D.
8"Ø8"Ø8"Ø8"Ø
H.D.H.D.H.D.H.D.
14141414
8"Ø8"Ø8"Ø8"Ø
14141414
H.D.H.D.H.D.H.D.
8"Ø8"Ø8"Ø8"Ø
H.D.H.D.H.D.H.D.
14141414
2222
2222
2222 2222
H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
10"Ø10"Ø10"Ø10"Ø
10"Ø10"Ø10"Ø10"Ø
H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
10"Ø10"Ø10"Ø10"Ø
10"Ø10"Ø10"Ø10"Ø
10"Ø10"Ø10"Ø10"Ø
10"Ø10"Ø10"Ø10"Ø
H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
8888
88888888
88888888 8888
14"Ø14"Ø14"Ø14"Ø
16"x14"+1"AL16"x14"+1"AL16"x14"+1"AL16"x14"+1"AL
252AA252AA252AA252AA
VAVRVAVRVAVRVAVR
H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
10"Ø10"Ø10"Ø10"Ø
10"Ø10"Ø10"Ø10"Ø
H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
10"Ø10"Ø10"Ø10"Ø
10"Ø10"Ø10"Ø10"Ø
10"Ø10"Ø10"Ø10"Ø
10"Ø10"Ø10"Ø10"Ø
H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
888888888888
88888888 8888
8"Ø8"Ø8"Ø8"Ø
H.
D
.
H.
D
.
H.
D
.
H.
D
.
3333
3333
14141414
15151515 8"
Ø
8"
Ø
8"
Ø
8"
Ø
H.D.H.D.H.D.H.D.3333
3333
13131313
H.D.H.D.H.D.H.D.
8"Ø8"Ø8"Ø8"Ø
8"Ø8"Ø8"Ø8"Ø
H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
8"Ø8"Ø8"Ø8"Ø
14141414
3333
3333
8"Ø8"Ø8"Ø8"Ø 8"Ø8"Ø8"Ø8"Ø
12121212
12121212
H.D.H.D.H.D.H.D. H.D.H.D.H.D.H.D.
29292929
30303030
31313131 32323232
33333333
34343434
35353535
36363636
37373737
2222
3333
10"Ø10"Ø10"Ø10"Ø
37373737
37373737
10101010
H.D.H.D.H.D.H.D.
32323232
H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
8"Ø8"Ø8"Ø8"Ø
8"Ø8"Ø8"Ø8"Ø31313131
31313131
8"Ø8"Ø8"Ø8"Ø
8"Ø8"Ø8"Ø8"Ø
8"Ø8"Ø8"Ø8"Ø H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
6"
Ø
6"
Ø
6"
Ø
6"
Ø
2-I
ELECTRICAL
3333----1111
VAVVAVVAVVAV
6"x6"+1"AL6"x6"+1"AL6"x6"+1"AL6"x6"+1"AL
2-U
HALL
8"Ø8"Ø8"Ø8"ØH.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
8"
Ø
8"
Ø
8"
Ø
8"
Ø
H.D.H.D.H.D.H.D.
8"Ø8"Ø8"Ø8"Ø
10"Ø10"Ø10"Ø10"Ø
H.D.H.D.H.D.H.D.
2222
H.D.H.D.H.D.H.D.
10"Ø10"Ø10"Ø10"Ø
34343434
10"Ø10"Ø10"Ø10"Ø
H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
38383838
40404040
41414141
42424242
43434343 44444444
46464646
47474747
26
"
x
1
6
"
F
.
O
.
26
"
x
1
6
"
F
.
O
.
26
"
x
1
6
"
F
.
O
.
26
"
x
1
6
"
F
.
O
.
14"Ø14"Ø14"Ø14"Ø
8"Ø8"Ø8"Ø8"Ø
H.D.H.D.H.D.H.D.
8"Ø8"Ø8"Ø8"Ø
H.D.H.D.H.D.H.D.
48"x16"F.O.48"x16"F.O.48"x16"F.O.48"x16"F.O.
10"Ø10"Ø10"Ø10"Ø H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
22"x14"F.O.22"x14"F.O.22"x14"F.O.22"x14"F.O.
20"x12"F.O.20"x12"F.O.20"x12"F.O.20"x12"F.O.
14"Ø14"Ø14"Ø14"Ø
6"Ø6"Ø6"Ø6"Ø
H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
8"Ø8"Ø8"Ø8"Ø
8"Ø8"Ø8"Ø8"Ø
40404040
2222
2222
38383838
38383838
47474747
41414141
41414141
4444444443434343
41414141
41414141
41414141
41414141
45454545 45454545
41414141 41414141 41414141
43434343
41414141
41414141
41414141
41414141
45454545
45454545
45454545
45454545
45454545
45454545
45454545
45454545 45454545 43434343
41414141
414141414141414141414141
41414141
45454545
41414141 41414141 41414141
48484848
280B280B280B280B
SACSACSACSAC
LVTLVTLVTLVT
10"x6" EXH.10"x6" EXH.10"x6" EXH.10"x6" EXH.
5555
6"Ø6"Ø6"Ø6"Ø
H.
D
.
H.
D
.
H.
D
.
H.
D
.
49494949
6"
Ø
6"
Ø
6"
Ø
6"
Ø
dbkbo^i=klqbp
A.A.A.A.WHERE UNISTRUTS ARE NOT LOCATED NOR WHERE UNISTRUTS ARE NOT LOCATED NOR WHERE UNISTRUTS ARE NOT LOCATED NOR WHERE UNISTRUTS ARE NOT LOCATED NOR
ACCESSIBLE IN THE BOTTOM OF STRUCTURAL ACCESSIBLE IN THE BOTTOM OF STRUCTURAL ACCESSIBLE IN THE BOTTOM OF STRUCTURAL ACCESSIBLE IN THE BOTTOM OF STRUCTURAL
CONCRETE WEBS, ALL ANCHORS AND SUPPORTS CONCRETE WEBS, ALL ANCHORS AND SUPPORTS CONCRETE WEBS, ALL ANCHORS AND SUPPORTS CONCRETE WEBS, ALL ANCHORS AND SUPPORTS
SHALL BE CONNECTED TO THE SIDES OF THE WEBS. SHALL BE CONNECTED TO THE SIDES OF THE WEBS. SHALL BE CONNECTED TO THE SIDES OF THE WEBS. SHALL BE CONNECTED TO THE SIDES OF THE WEBS.
DO NOT ATTACH TO THE BOTTOM OF THE WEB IF DO NOT ATTACH TO THE BOTTOM OF THE WEB IF DO NOT ATTACH TO THE BOTTOM OF THE WEB IF DO NOT ATTACH TO THE BOTTOM OF THE WEB IF
THERE IS NO EXISTING UNISTRUT.THERE IS NO EXISTING UNISTRUT.THERE IS NO EXISTING UNISTRUT.THERE IS NO EXISTING UNISTRUT.
R.A. OPENINGS WITH SOUND BOOTS DO NOT NEED R.A. OPENINGS WITH SOUND BOOTS DO NOT NEED R.A. OPENINGS WITH SOUND BOOTS DO NOT NEED R.A. OPENINGS WITH SOUND BOOTS DO NOT NEED
TO BE INSTALLED IF THE WALL IN WHICH THEY ARE TO BE INSTALLED IF THE WALL IN WHICH THEY ARE TO BE INSTALLED IF THE WALL IN WHICH THEY ARE TO BE INSTALLED IF THE WALL IN WHICH THEY ARE
LOCATED, IS BETWEEN STRUCTURAL WEBS, AND LOCATED, IS BETWEEN STRUCTURAL WEBS, AND LOCATED, IS BETWEEN STRUCTURAL WEBS, AND LOCATED, IS BETWEEN STRUCTURAL WEBS, AND
THERE ARE OPENINGS, OF TOTAL AREA EQUAL TO OR THERE ARE OPENINGS, OF TOTAL AREA EQUAL TO OR THERE ARE OPENINGS, OF TOTAL AREA EQUAL TO OR THERE ARE OPENINGS, OF TOTAL AREA EQUAL TO OR
GREATER THAN THAT OF THE SOUND BOOT, INTO THE GREATER THAN THAT OF THE SOUND BOOT, INTO THE GREATER THAN THAT OF THE SOUND BOOT, INTO THE GREATER THAN THAT OF THE SOUND BOOT, INTO THE
STRUCTURAL PAN TO ALLOW AIR TO FLOW INTO THE STRUCTURAL PAN TO ALLOW AIR TO FLOW INTO THE STRUCTURAL PAN TO ALLOW AIR TO FLOW INTO THE STRUCTURAL PAN TO ALLOW AIR TO FLOW INTO THE
ADJACENT CEILING SPACE. CONTRACTOR TO ADJACENT CEILING SPACE. CONTRACTOR TO ADJACENT CEILING SPACE. CONTRACTOR TO ADJACENT CEILING SPACE. CONTRACTOR TO
PROVIDE CREDIT FOR SOUND BOOTS THAT WERE PROVIDE CREDIT FOR SOUND BOOTS THAT WERE PROVIDE CREDIT FOR SOUND BOOTS THAT WERE PROVIDE CREDIT FOR SOUND BOOTS THAT WERE
DEEMED UNNECESSARY.DEEMED UNNECESSARY.DEEMED UNNECESSARY.DEEMED UNNECESSARY.
B.B.B.B.
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
Level 02 Area
B Mechanical
Remodel Plan
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
KEY PLAN
A
B
ao^tfkd=klqbp
0000555510101010 10101010 20202020
NOTE
#
DIFFUSER
CALLOUT DESCRIPTION
1111 S-1S-1S-1S-1 255 CFM, 10"Ø NK S.A. DIFFUSER255 CFM, 10"Ø NK S.A. DIFFUSER255 CFM, 10"Ø NK S.A. DIFFUSER255 CFM, 10"Ø NK S.A. DIFFUSER
2222 R-1R-1R-1R-1 22"x22" NK R.A. GRILLE W/ SOUND22"x22" NK R.A. GRILLE W/ SOUND22"x22" NK R.A. GRILLE W/ SOUND22"x22" NK R.A. GRILLE W/ SOUND
BOOTBOOTBOOTBOOT
3333 R-1R-1R-1R-1 22"x10" NK R.A. GRILLE W/ SOUND22"x10" NK R.A. GRILLE W/ SOUND22"x10" NK R.A. GRILLE W/ SOUND22"x10" NK R.A. GRILLE W/ SOUND
BOOTBOOTBOOTBOOT
4444 S-1S-1S-1S-1 215 CFM, 8"Ø NK S.A. DIFFUSER215 CFM, 8"Ø NK S.A. DIFFUSER215 CFM, 8"Ø NK S.A. DIFFUSER215 CFM, 8"Ø NK S.A. DIFFUSER
5555 S-1S-1S-1S-1 180 CFM, 8"Ø NK S.A. DIFFUSER180 CFM, 8"Ø NK S.A. DIFFUSER180 CFM, 8"Ø NK S.A. DIFFUSER180 CFM, 8"Ø NK S.A. DIFFUSER
6666 S-1S-1S-1S-1 295 CFM, 10"Ø NK S.A. DIFFUSER295 CFM, 10"Ø NK S.A. DIFFUSER295 CFM, 10"Ø NK S.A. DIFFUSER295 CFM, 10"Ø NK S.A. DIFFUSER
7777 S-1S-1S-1S-1 200 CFM, 8"Ø NK S.A. DIFFUSER200 CFM, 8"Ø NK S.A. DIFFUSER200 CFM, 8"Ø NK S.A. DIFFUSER200 CFM, 8"Ø NK S.A. DIFFUSER
8888 S-1S-1S-1S-1 280 CFM, 10"Ø NK S.A. DIFFUSER280 CFM, 10"Ø NK S.A. DIFFUSER280 CFM, 10"Ø NK S.A. DIFFUSER280 CFM, 10"Ø NK S.A. DIFFUSER
9999 S-1S-1S-1S-1 250 CFM, 10"Ø NK S.A. DIFFUSER250 CFM, 10"Ø NK S.A. DIFFUSER250 CFM, 10"Ø NK S.A. DIFFUSER250 CFM, 10"Ø NK S.A. DIFFUSER
10101010 S-1S-1S-1S-1 285 CFM, 10"Ø NK S.A. DIFFUSER285 CFM, 10"Ø NK S.A. DIFFUSER285 CFM, 10"Ø NK S.A. DIFFUSER285 CFM, 10"Ø NK S.A. DIFFUSER
11111111 S-1S-1S-1S-1 120 CFM, 8"Ø NK S.A. DIFFUSER120 CFM, 8"Ø NK S.A. DIFFUSER120 CFM, 8"Ø NK S.A. DIFFUSER120 CFM, 8"Ø NK S.A. DIFFUSER
12121212 S-1S-1S-1S-1 150 CFM, 8"Ø NK S.A. DIFFUSER150 CFM, 8"Ø NK S.A. DIFFUSER150 CFM, 8"Ø NK S.A. DIFFUSER150 CFM, 8"Ø NK S.A. DIFFUSER
13131313 S-1S-1S-1S-1 165 CFM, 8"Ø NK S.A. DIFFUSER165 CFM, 8"Ø NK S.A. DIFFUSER165 CFM, 8"Ø NK S.A. DIFFUSER165 CFM, 8"Ø NK S.A. DIFFUSER
14141414 S-1S-1S-1S-1 225 CFM, 8"Ø NK S.A. DIFFUSER225 CFM, 8"Ø NK S.A. DIFFUSER225 CFM, 8"Ø NK S.A. DIFFUSER225 CFM, 8"Ø NK S.A. DIFFUSER
15151515 S-1S-1S-1S-1 155 CFM, 8"Ø NK S.A. DIFFUSER155 CFM, 8"Ø NK S.A. DIFFUSER155 CFM, 8"Ø NK S.A. DIFFUSER155 CFM, 8"Ø NK S.A. DIFFUSER
16161616 S-1S-1S-1S-1 100 CFM, 6"Ø NK S.A. DIFFUSER100 CFM, 6"Ø NK S.A. DIFFUSER100 CFM, 6"Ø NK S.A. DIFFUSER100 CFM, 6"Ø NK S.A. DIFFUSER
17171717 S-1S-1S-1S-1 95 CFM, 6"Ø NK S.A. DIFFUSER95 CFM, 6"Ø NK S.A. DIFFUSER95 CFM, 6"Ø NK S.A. DIFFUSER95 CFM, 6"Ø NK S.A. DIFFUSER
18181818 S-1S-1S-1S-1 360 CFM, 10"Ø NK S.A. DIFFUSER360 CFM, 10"Ø NK S.A. DIFFUSER360 CFM, 10"Ø NK S.A. DIFFUSER360 CFM, 10"Ø NK S.A. DIFFUSER
19191919 S-1S-1S-1S-1 310 CFM, 10"Ø NK S.A. DIFFUSER310 CFM, 10"Ø NK S.A. DIFFUSER310 CFM, 10"Ø NK S.A. DIFFUSER310 CFM, 10"Ø NK S.A. DIFFUSER
20202020 BALANCE EXISTING S.A. DIFFUSER TOBALANCE EXISTING S.A. DIFFUSER TOBALANCE EXISTING S.A. DIFFUSER TOBALANCE EXISTING S.A. DIFFUSER TO
250 CFM.250 CFM.250 CFM.250 CFM.
21212121 S-1S-1S-1S-1 185 CFM, 8"Ø NK S.A. DIFFUSER185 CFM, 8"Ø NK S.A. DIFFUSER185 CFM, 8"Ø NK S.A. DIFFUSER185 CFM, 8"Ø NK S.A. DIFFUSER
22222222 S-1S-1S-1S-1 260 CFM, 10"Ø NK S.A. DIFFUSER260 CFM, 10"Ø NK S.A. DIFFUSER260 CFM, 10"Ø NK S.A. DIFFUSER260 CFM, 10"Ø NK S.A. DIFFUSER
23232323 S-1S-1S-1S-1 245 CFM, 10"Ø NK S.A. DIFFUSER245 CFM, 10"Ø NK S.A. DIFFUSER245 CFM, 10"Ø NK S.A. DIFFUSER245 CFM, 10"Ø NK S.A. DIFFUSER
24242424 S-1S-1S-1S-1 235 CFM, 8"Ø NK S.A. DIFFUSER235 CFM, 8"Ø NK S.A. DIFFUSER235 CFM, 8"Ø NK S.A. DIFFUSER235 CFM, 8"Ø NK S.A. DIFFUSER
25252525 S-1S-1S-1S-1 275 CFM, 10"Ø NK S.A. DIFFUSER275 CFM, 10"Ø NK S.A. DIFFUSER275 CFM, 10"Ø NK S.A. DIFFUSER275 CFM, 10"Ø NK S.A. DIFFUSER
26262626 S-1S-1S-1S-1 135 CFM, 8"Ø NK S.A. DIFFUSER135 CFM, 8"Ø NK S.A. DIFFUSER135 CFM, 8"Ø NK S.A. DIFFUSER135 CFM, 8"Ø NK S.A. DIFFUSER
27272727 S-3S-3S-3S-3 50 CFM, 6"x6" NK S.A. DIFFUSER50 CFM, 6"x6" NK S.A. DIFFUSER50 CFM, 6"x6" NK S.A. DIFFUSER50 CFM, 6"x6" NK S.A. DIFFUSER
28282828 S-1S-1S-1S-1 50 CFM, 6"Ø NK S.A. DIFFUSER50 CFM, 6"Ø NK S.A. DIFFUSER50 CFM, 6"Ø NK S.A. DIFFUSER50 CFM, 6"Ø NK S.A. DIFFUSER
29292929 S-4S-4S-4S-4 150 CFM, 4'-0" x 2 SLOT S.A.150 CFM, 4'-0" x 2 SLOT S.A.150 CFM, 4'-0" x 2 SLOT S.A.150 CFM, 4'-0" x 2 SLOT S.A.
DIFFUSERDIFFUSERDIFFUSERDIFFUSER
30303030 S-4S-4S-4S-4 205 CFM, 4'-0" x 3 SLOT S.A.205 CFM, 4'-0" x 3 SLOT S.A.205 CFM, 4'-0" x 3 SLOT S.A.205 CFM, 4'-0" x 3 SLOT S.A.
DIFFUSERDIFFUSERDIFFUSERDIFFUSER
31313131 S-2S-2S-2S-2 115 CFM, 8"Ø NK S.A. DIFFUSER115 CFM, 8"Ø NK S.A. DIFFUSER115 CFM, 8"Ø NK S.A. DIFFUSER115 CFM, 8"Ø NK S.A. DIFFUSER
32323232 S-2S-2S-2S-2 145 CFM, 8"Ø NK S.A. DIFFUSER145 CFM, 8"Ø NK S.A. DIFFUSER145 CFM, 8"Ø NK S.A. DIFFUSER145 CFM, 8"Ø NK S.A. DIFFUSER
33333333 S-2S-2S-2S-2 275 CFM, 10"Ø NK S.A. DIFFUSER275 CFM, 10"Ø NK S.A. DIFFUSER275 CFM, 10"Ø NK S.A. DIFFUSER275 CFM, 10"Ø NK S.A. DIFFUSER
34343434 S-2S-2S-2S-2 375 CFM, 10"Ø NK S.A. DIFFUSER375 CFM, 10"Ø NK S.A. DIFFUSER375 CFM, 10"Ø NK S.A. DIFFUSER375 CFM, 10"Ø NK S.A. DIFFUSER
35353535 S-3S-3S-3S-3 100 CFM, 6"x6" NK S.A. DIFFUSER100 CFM, 6"x6" NK S.A. DIFFUSER100 CFM, 6"x6" NK S.A. DIFFUSER100 CFM, 6"x6" NK S.A. DIFFUSER
36363636 S-2S-2S-2S-2 200 CFM, 8"Ø NK S.A. DIFFUSER200 CFM, 8"Ø NK S.A. DIFFUSER200 CFM, 8"Ø NK S.A. DIFFUSER200 CFM, 8"Ø NK S.A. DIFFUSER
37373737 S-1S-1S-1S-1 240 CFM, 10"Ø NK S.A. DIFFUSER240 CFM, 10"Ø NK S.A. DIFFUSER240 CFM, 10"Ø NK S.A. DIFFUSER240 CFM, 10"Ø NK S.A. DIFFUSER
38383838 60"x24" R.A. OPENING IN WALL ABOVE60"x24" R.A. OPENING IN WALL ABOVE60"x24" R.A. OPENING IN WALL ABOVE60"x24" R.A. OPENING IN WALL ABOVE
CEILING.CEILING.CEILING.CEILING.
40404040 R-2R-2R-2R-2 10"x6" NK R.A. GRILLE WITH SOUND10"x6" NK R.A. GRILLE WITH SOUND10"x6" NK R.A. GRILLE WITH SOUND10"x6" NK R.A. GRILLE WITH SOUND
BOOTBOOTBOOTBOOT
41414141 12"x12"+1"AL R.A. OPENING W/12"x12"+1"AL R.A. OPENING W/12"x12"+1"AL R.A. OPENING W/12"x12"+1"AL R.A. OPENING W/
SOUND BOOT ABOVE CEILING.SOUND BOOT ABOVE CEILING.SOUND BOOT ABOVE CEILING.SOUND BOOT ABOVE CEILING.
42424242 14"x14" E.A. DUCT UP FROM BELOW.14"x14" E.A. DUCT UP FROM BELOW.14"x14" E.A. DUCT UP FROM BELOW.14"x14" E.A. DUCT UP FROM BELOW.
CONNECT TO EXISTING E.A.CONNECT TO EXISTING E.A.CONNECT TO EXISTING E.A.CONNECT TO EXISTING E.A.
DUCTWORK IN CHASE.DUCTWORK IN CHASE.DUCTWORK IN CHASE.DUCTWORK IN CHASE.
43434343 16"x16"+1"AL R.A. OPENING W/16"x16"+1"AL R.A. OPENING W/16"x16"+1"AL R.A. OPENING W/16"x16"+1"AL R.A. OPENING W/
SOUND BOOT ABOVE CEILING.SOUND BOOT ABOVE CEILING.SOUND BOOT ABOVE CEILING.SOUND BOOT ABOVE CEILING.
44444444 18"x18"+1"AL R.A. OPENING W/18"x18"+1"AL R.A. OPENING W/18"x18"+1"AL R.A. OPENING W/18"x18"+1"AL R.A. OPENING W/
SOUND BOOT ABOVE CEILING.SOUND BOOT ABOVE CEILING.SOUND BOOT ABOVE CEILING.SOUND BOOT ABOVE CEILING.
45454545 22"x22"+1"AL R.A. OPENING W/22"x22"+1"AL R.A. OPENING W/22"x22"+1"AL R.A. OPENING W/22"x22"+1"AL R.A. OPENING W/
SOUND BOOT ABOVE CEILING.SOUND BOOT ABOVE CEILING.SOUND BOOT ABOVE CEILING.SOUND BOOT ABOVE CEILING.
46464646 BALANCE EXISTING E.A. GRILLE TOBALANCE EXISTING E.A. GRILLE TOBALANCE EXISTING E.A. GRILLE TOBALANCE EXISTING E.A. GRILLE TO
250 CFM.250 CFM.250 CFM.250 CFM.
47474747 120"x24" R.A. OPENING IN WALL120"x24" R.A. OPENING IN WALL120"x24" R.A. OPENING IN WALL120"x24" R.A. OPENING IN WALL
ABOVE CEILING.ABOVE CEILING.ABOVE CEILING.ABOVE CEILING.
48484848 RISE 10"x6" E.A. DUCT UP TO ROOF,RISE 10"x6" E.A. DUCT UP TO ROOF,RISE 10"x6" E.A. DUCT UP TO ROOF,RISE 10"x6" E.A. DUCT UP TO ROOF,
TRANSITION IN RISE AND CONNECT TOTRANSITION IN RISE AND CONNECT TOTRANSITION IN RISE AND CONNECT TOTRANSITION IN RISE AND CONNECT TO
REF.REF.REF.REF.
49494949 BALANCE EXISTING S.A. DIFFUSER TOBALANCE EXISTING S.A. DIFFUSER TOBALANCE EXISTING S.A. DIFFUSER TOBALANCE EXISTING S.A. DIFFUSER TO
100 CFM.100 CFM.100 CFM.100 CFM.
SCALE:SCALE:SCALE:SCALE:MH102bMH102bMH102bMH102b 1/8" = 1'1/8" = 1'1/8" = 1'1/8" = 1'----0"0"0"0"
ibsbi=O=^ob^=_=jb`e^kf`^i=objlabi=mi^k1111
1111
GGGG
JJJJ
LLLL
MMMM
NNNN
PPPP
QQQQ
EEEE
CCCC
2222 3333 4444 5555
344A
MOTHERS ROOM
344
FAMILY STUDY
362
OPEN STUDY
368
MENS
366
WOMENS
3-B
STAIR 1
3-A
BRIDGE CONNECTION
-
Bridge Connection
302
STUDY (MED)
304
STUDY (MED)
306
STORAGE
310
OFFICE
312
OFFICE
300
JUVENILE
54"x24"F.O.54"x24"F.O.54"x24"F.O.54"x24"F.O.
48
"
x
2
2
"
F
.
O
.
48
"
x
2
2
"
F
.
O
.
48
"
x
2
2
"
F
.
O
.
48
"
x
2
2
"
F
.
O
.
48
"
x
2
2
"
F
.
O
.
48
"
x
2
2
"
F
.
O
.
48
"
x
2
2
"
F
.
O
.
48
"
x
2
2
"
F
.
O
.
22"x16"F.O.22"x16"F.O.22"x16"F.O.22"x16"F.O.20"x16"F.O.20"x16"F.O.20"x16"F.O.20"x16"F.O.
12"Ø12"Ø12"Ø12"Ø
18"Ø18"Ø18"Ø18"Ø
12"Ø12"Ø12"Ø12"Ø
344C
KIDS PLAY344B
RESTROOM
346
TEST RM
348
TEST RM
350
TEST RM
352
STORAGE
364
ELEC
356
TEST RM
358
TEST RM
360
TEST RM
370
TEST RM
372
TEST RM
374
TEST RM
376
Janitors Closet
378
TEST RM
380
TEST RM
382
TEST RM
328
STUDY (LG)
326
STUDY (LG)
324
MAC LAB
314
STUDY (SM)
316
STUDY (SM)
318
STUDY (SM)
320
STUDY (SM)
322
OFFICE
324A
MAC EQUIP
324B
ELECTRICAL
330
STUDY (SM)
332
STUDY (SM)
334
STUDY (SM)
336
STUDY (SM)
338
STUDY (SM)
340
STUDY (SM)
3-F
STAIR 3-G
ELEV
3-H
MECH CHASE
3-C
STAIRS
308
ELECTRICAL
338338338338
VAVRVAVRVAVRVAVR
8"x8"+1"AL8"x8"+1"AL8"x8"+1"AL8"x8"+1"AL
8"Ø8"Ø8"Ø8"Ø
340340340340
VAVRVAVRVAVRVAVR
8"x8"+1"AL8"x8"+1"AL8"x8"+1"AL8"x8"+1"AL
8"Ø8"Ø8"Ø8"Ø
8"x8"+1"AL8"x8"+1"AL8"x8"+1"AL8"x8"+1"AL
336336336336
VAVRVAVRVAVRVAVR
8"Ø8"Ø8"Ø8"Ø
334334334334
VAVRVAVRVAVRVAVR
8"x8"+1"AL8"x8"+1"AL8"x8"+1"AL8"x8"+1"AL
8"Ø8"Ø8"Ø8"Ø
332332332332
VAVRVAVRVAVRVAVR
8"x8"+1"AL8"x8"+1"AL8"x8"+1"AL8"x8"+1"AL
8"Ø8"Ø8"Ø8"Ø
20
"
x
1
6
"
+
1
"
A
L
20
"
x
1
6
"
+
1
"
A
L
20
"
x
1
6
"
+
1
"
A
L
20
"
x
1
6
"
+
1
"
A
L
342A342A342A342A
VAVRVAVRVAVRVAVR
16"Ø16"Ø16"Ø16"Ø
10
"
x
1
2
"
+
1
"
A
L
10
"
x
1
2
"
+
1
"
A
L
10
"
x
1
2
"
+
1
"
A
L
10
"
x
1
2
"
+
1
"
A
L
10"Ø10"Ø10"Ø10"Ø
14"Ø14"Ø14"Ø14"Ø
14"x16"+1"AL14"x16"+1"AL14"x16"+1"AL14"x16"+1"AL
330330330330
VAVRVAVRVAVRVAVR
8"x8"+1"AL8"x8"+1"AL8"x8"+1"AL8"x8"+1"AL
6"Ø6"Ø6"Ø6"Ø
324B324B324B324B
VAVRVAVRVAVRVAVR
8"x6"+1"AL8"x6"+1"AL8"x6"+1"AL8"x6"+1"AL
6"Ø6"Ø6"Ø6"Ø
322322322322
VAVRVAVRVAVRVAVR
8"x10"+1"AL8"x10"+1"AL8"x10"+1"AL8"x10"+1"AL
8"Ø8"Ø8"Ø8"Ø
12"x10"+1"AL12"x10"+1"AL12"x10"+1"AL12"x10"+1"AL
320320320320
VAVRVAVRVAVRVAVR
10"Ø10"Ø10"Ø10"Ø
318318318318
VAVRVAVRVAVRVAVR
10"x10"+1"AL10"x10"+1"AL10"x10"+1"AL10"x10"+1"AL
8"Ø8"Ø8"Ø8"Ø
12"x10"+1"AL12"x10"+1"AL12"x10"+1"AL12"x10"+1"AL
316316316316
VAVRVAVRVAVRVAVR
10"Ø10"Ø10"Ø10"Ø
12"x10"+1"AL12"x10"+1"AL12"x10"+1"AL12"x10"+1"AL
314314314314
VAVRVAVRVAVRVAVR
10"Ø10"Ø10"Ø10"Ø
12"x10"+1"AL12"x10"+1"AL12"x10"+1"AL12"x10"+1"AL
312312312312
VAVRVAVRVAVRVAVR
10"Ø10"Ø10"Ø10"Ø
12"x12"+1"AL12"x12"+1"AL12"x12"+1"AL12"x12"+1"AL
310310310310
VAVRVAVRVAVRVAVR
300B300B300B300B
VAVRVAVRVAVRVAVR
14"Ø14"Ø14"Ø14"Ø
16"x14"+1"AL16"x14"+1"AL16"x14"+1"AL16"x14"+1"AL
342B342B342B342B
VAVRVAVRVAVRVAVR
6"Ø6"Ø6"Ø6"Ø
306306306306
VAVRVAVRVAVRVAVR
8"x8"+1"AL8"x8"+1"AL8"x8"+1"AL8"x8"+1"AL
304304304304
VAVRVAVRVAVRVAVR
10"x10"+1"AL10"x10"+1"AL10"x10"+1"AL10"x10"+1"AL
8"Ø8"Ø8"Ø8"Ø 12"Ø12"Ø12"Ø12"Ø
14"x12"+1"AL14"x12"+1"AL14"x12"+1"AL14"x12"+1"AL
302302302302
VAVRVAVRVAVRVAVR
300D300D300D300D
VAVRVAVRVAVRVAVR
18
"
x
1
4
"
+
1
"
A
L
18
"
x
1
4
"
+
1
"
A
L
18
"
x
1
4
"
+
1
"
A
L
18
"
x
1
4
"
+
1
"
A
L
14"Ø14"Ø14"Ø14"Ø
14"x12"+1"AL14"x12"+1"AL14"x12"+1"AL14"x12"+1"AL
3333----AAAA
VAVRVAVRVAVRVAVR
12"Ø12"Ø12"Ø12"Ø
12"x12"+1"AL12"x12"+1"AL12"x12"+1"AL12"x12"+1"AL
328328328328
VAVRVAVRVAVRVAVR
10"Ø10"Ø10"Ø10"Ø
12"x10"+1"AL12"x10"+1"AL12"x10"+1"AL12"x10"+1"AL326326326326
VAVRVAVRVAVRVAVR
10"Ø10"Ø10"Ø10"Ø
10"Ø10"Ø10"Ø10"Ø 6"Ø6"Ø6"Ø6"Ø368368368368
VAVRVAVRVAVRVAVR
8"x10"+1"AL8"x10"+1"AL8"x10"+1"AL8"x10"+1"AL
6"Ø6"Ø6"Ø6"Ø 374374374374
VAVRVAVRVAVRVAVR
8"x6"+1"AL8"x6"+1"AL8"x6"+1"AL8"x6"+1"AL
6"Ø6"Ø6"Ø6"Ø
378378378378
VAVRVAVRVAVRVAVR
10"x8"+1"AL10"x8"+1"AL10"x8"+1"AL10"x8"+1"AL
16"x16"+1"AL16"x16"+1"AL16"x16"+1"AL16"x16"+1"AL
16"Ø16"Ø16"Ø16"Ø
344344344344
VAVRVAVRVAVRVAVR
6"Ø6"Ø6"Ø6"Ø
344C344C344C344C
VAVRVAVRVAVRVAVR
8"x8"+1"AL8"x8"+1"AL8"x8"+1"AL8"x8"+1"AL
6"
Ø
6"
Ø
6"
Ø
6"
Ø
344A344A344A344A
VAVRVAVRVAVRVAVR
8"x6"+1"AL8"x6"+1"AL8"x6"+1"AL8"x6"+1"AL
6"
Ø
6"
Ø
6"
Ø
6"
Ø
346346346346
VAVRVAVRVAVRVAVR
8"x6"+1"AL8"x6"+1"AL8"x6"+1"AL8"x6"+1"AL
6"Ø6"Ø6"Ø6"Ø
362362362362
VAVRVAVRVAVRVAVR
6"x8"+1"AL6"x8"+1"AL6"x8"+1"AL6"x8"+1"AL
6"Ø6"Ø6"Ø6"Ø
352352352352
VAVRVAVRVAVRVAVR
8"x8"+1"AL8"x8"+1"AL8"x8"+1"AL8"x8"+1"AL
6"Ø6"Ø6"Ø6"Ø
360360360360
VAVRVAVRVAVRVAVR
8"x6"+1"AL8"x6"+1"AL8"x6"+1"AL8"x6"+1"AL
10
"
Ø
10
"
Ø
10
"
Ø
10
"
Ø
12"x12"+1"AL12"x12"+1"AL12"x12"+1"AL12"x12"+1"AL
366366366366
VAVRVAVRVAVRVAVR
10"Ø10"Ø10"Ø10"Ø
342F342F342F342F
VAVRVAVRVAVRVAVR
1111
2222
3333
4444
5555
6666
7777
8888
9999
10101010
11111111
12121212
13131313
15151515
16161616
17171717
18181818
19191919
20202020
21212121
22222222
23232323
24242424
25252525
26262626
27272727
28282828
29292929
30303030
31313131
32323232
33333333
20"x16"F.O.20"x16"F.O.20"x16"F.O.20"x16"F.O.
54"x24"F.O.54"x24"F.O.54"x24"F.O.54"x24"F.O.
H.D.H.D.H.D.H.D.10"Ø10"Ø10"Ø10"Ø
2424242424242424
H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.10"Ø10"Ø10"Ø10"Ø
10"Ø10"Ø10"Ø10"Ø
3333
23232323
H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
8"Ø8"Ø8"Ø8"Ø8"Ø8"Ø8"Ø8"Ø
H.D.H.D.H.D.H.D.6"Ø6"Ø6"Ø6"Ø
6"x6"+1"AL6"x6"+1"AL6"x6"+1"AL6"x6"+1"AL
H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
8"Ø8"Ø8"Ø8"Ø
H.D.H.D.H.D.H.D.
8"Ø8"Ø8"Ø8"Ø
26262626
H.D.H.D.H.D.H.D.
8"Ø8"Ø8"Ø8"Ø
26262626
H.D.H.D.H.D.H.D.
8"Ø8"Ø8"Ø8"Ø
26262626
H.D.H.D.H.D.H.D.
8"Ø8"Ø8"Ø8"Ø
26262626
H.D.H.D.H.D.H.D.
8"Ø8"Ø8"Ø8"Ø
26262626
H.D.H.D.H.D.H.D.
8"Ø8"Ø8"Ø8"Ø
26262626
H.D.H.D.H.D.H.D.
8"Ø8"Ø8"Ø8"Ø
26262626
H.D.H.D.H.D.H.D.
8"Ø8"Ø8"Ø8"Ø
26262626
H.D.H.D.H.D.H.D.
8"Ø8"Ø8"Ø8"Ø
26262626
26262626
H.D.H.D.H.D.H.D.
8"Ø8"Ø8"Ø8"Ø
H.D.H.D.H.D.H.D.
8"Ø8"Ø8"Ø8"Ø
26262626
26262626
8"Ø8"Ø8"Ø8"Ø
H.D.H.D.H.D.H.D.
26262626
26262626
H.D.H.D.H.D.H.D.
8"Ø8"Ø8"Ø8"Ø
H.D.H.D.H.D.H.D.
8"Ø8"Ø8"Ø8"Ø
300C300C300C300C
VAVRVAVRVAVRVAVR
16
"
x
1
4
"
+
1
"
A
L
16
"
x
1
4
"
+
1
"
A
L
16
"
x
1
4
"
+
1
"
A
L
16
"
x
1
4
"
+
1
"
A
L
14"Ø14"Ø14"Ø14"Ø
H.D.H.D.H.D.H.D.
8"x6"+1"AL8"x6"+1"AL8"x6"+1"AL8"x6"+1"AL
22222222
H.D.H.D.H.D.H.D.
8"x6"+1"AL8"x6"+1"AL8"x6"+1"AL8"x6"+1"AL
22222222
H.D.H.D.H.D.H.D.
8"x6"+1"AL8"x6"+1"AL8"x6"+1"AL8"x6"+1"AL
22222222
H.D.H.D.H.D.H.D.
8"x6"+1"AL8"x6"+1"AL8"x6"+1"AL8"x6"+1"AL
22222222
H.D.H.D.H.D.H.D.
8"x6"+1"AL8"x6"+1"AL8"x6"+1"AL8"x6"+1"AL
22222222
300A300A300A300A
VAVRVAVRVAVRVAVR
16
"
x
1
4
"
+
1
"
A
L
16
"
x
1
4
"
+
1
"
A
L
16
"
x
1
4
"
+
1
"
A
L
16
"
x
1
4
"
+
1
"
A
L
14"Ø14"Ø14"Ø14"Ø
H.D.H.D.H.D.H.D.
8"x6"+1"AL8"x6"+1"AL8"x6"+1"AL8"x6"+1"AL
22222222
H.D.H.D.H.D.H.D.
8"x6"+1"AL8"x6"+1"AL8"x6"+1"AL8"x6"+1"AL
22222222
H.D.H.D.H.D.H.D.
22222222
H.D.H.D.H.D.H.D.
8"x6"+1"AL8"x6"+1"AL8"x6"+1"AL8"x6"+1"AL
22222222
H.D.H.D.H.D.H.D.8"x6"+1"AL8"x6"+1"AL8"x6"+1"AL8"x6"+1"AL
8"x6"+1"AL8"x6"+1"AL8"x6"+1"AL8"x6"+1"AL
H.D.H.D.H.D.H.D.
10"Ø10"Ø10"Ø10"Ø
H.D.H.D.H.D.H.D.7777
6"Ø6"Ø6"Ø6"Ø
H.D.H.D.H.D.H.D.7777
6"Ø6"Ø6"Ø6"Ø
H.D.H.D.H.D.H.D.7777
6"Ø6"Ø6"Ø6"Ø
10"Ø10"Ø10"Ø10"Ø
H.D.H.D.H.D.H.D.
25252525
8"Ø8"Ø8"Ø8"Ø
8"Ø8"Ø8"Ø8"Ø H.D.H.D.H.D.H.D.H.D.H.D.H.D.H.D.
21212121
7777
6"Ø6"Ø6"Ø6"Ø
H.D.H.D.H.D.H.D.
2222
2222
22222222
2222
2222
2222
7777
6"Ø6"Ø6"Ø6"Ø
H.D.H.D.H.D.H.D.
7777 6"Ø6"Ø6"Ø6"Ø
H.D.H.D.H.D.H.D.
21212121
8"Ø8"Ø8"Ø8"Ø
H.D.H.D.H.D.H.D.H.D.H.D.H.D.H.D.
8"Ø8"Ø8"Ø8"Ø
21212121
H.D.H.D.H.D.H.D.
8"Ø8"Ø8"Ø8"Ø
H.D.H.D.H.D.H.D.
8"Ø8"Ø8"Ø8"Ø
H.D.H.D.H.D.H.D.
8"Ø8"Ø8"Ø8"Ø
2222
2020202020202020
8"Ø8"Ø8"Ø8"Ø8"Ø8"Ø8"Ø8"Ø
2020202020202020
20202020
2222
2222
2222
2222
3333
3333
19191919
H.
D
.
H.
D
.
H.
D
.
H.
D
.
H.
D
.
H.
D
.
H.
D
.
H.
D
.
10"Ø10"Ø10"Ø10"Ø10"Ø10"Ø10"Ø10"Ø
H.
D
.
H.
D
.
H.
D
.
H.
D
.
H.
D
.
H.
D
.
H.
D
.
H.
D
.
10"Ø10"Ø10"Ø10"Ø10"Ø10"Ø10"Ø10"Ø
18181818
H.
D
.
H.
D
.
H.
D
.
H.
D
.
H.
D
.
H.
D
.
H.
D
.
H.
D
.
10"Ø10"Ø10"Ø10"Ø10"Ø10"Ø10"Ø10"Ø
H.
D
.
H.
D
.
H.
D
.
H.
D
.
H.
D
.
H.
D
.
H.
D
.
H.
D
.
10"Ø10"Ø10"Ø10"Ø10"Ø10"Ø10"Ø10"Ø
H.
D
.
H.
D
.
H.
D
.
H.
D
.
H.
D
.
H.
D
.
H.
D
.
H.
D
.
10"Ø10"Ø10"Ø10"Ø10"Ø10"Ø10"Ø10"Ø
H.D.H.D.H.D.H.D.
H.
D
.
H.
D
.
H.
D
.
H.
D
.
10"Ø10"Ø10"Ø10"Ø10"Ø10"Ø10"Ø10"Ø
17171717
16161616
10101010
15151515
8"Ø8"Ø8"Ø8"Ø 324BB324BB324BB324BB
VAVRVAVRVAVRVAVR
14"x14"+1"AL14"x14"+1"AL14"x14"+1"AL14"x14"+1"AL
14"Ø14"Ø14"Ø14"Ø
H.D.H.D.H.D.H.D.
8"Ø8"Ø8"Ø8"Ø
3333
H.D.H.D.H.D.H.D.
6"Ø6"Ø6"Ø6"Ø
4444
3333
H.D.H.D.H.D.H.D.
6"Ø6"Ø6"Ø6"Ø
4444
3333
H.D.H.D.H.D.H.D.
6"Ø6"Ø6"Ø6"Ø
2222
8"Ø8"Ø8"Ø8"Ø
H.D.H.D.H.D.H.D.
8"Ø8"Ø8"Ø8"Ø
H.D.H.D.H.D.H.D.
28282828
8"Ø8"Ø8"Ø8"Ø
H.D.H.D.H.D.H.D.H.D.H.D.H.D.H.D.
8"Ø8"Ø8"Ø8"Ø28282828 28282828
2222
8"Ø8"Ø8"Ø8"Ø
8"Ø8"Ø8"Ø8"Ø
H.
D
.
H.
D
.
H.
D
.
H.
D
.
H.D.H.D.H.D.H.D.
8"Ø8"Ø8"Ø8"Ø
H.
D
.
H.
D
.
H.
D
.
H.
D
.
H.D.H.D.H.D.H.D.
8"Ø8"Ø8"Ø8"Ø
27272727
27272727
27272727
22222222
14"Ø14"Ø14"Ø14"Ø
14"x14"+1"AL14"x14"+1"AL14"x14"+1"AL14"x14"+1"AL
324AA324AA324AA324AA
VAVRVAVRVAVRVAVR
H.D.H.D.H.D.H.D.
20202020
8"Ø8"Ø8"Ø8"Ø H.D.H.D.H.D.H.D.
20202020
8"Ø8"Ø8"Ø8"Ø H.D.H.D.H.D.H.D.8"Ø8"Ø8"Ø8"Ø
20202020
8"Ø8"Ø8"Ø8"Ø 8"Ø8"Ø8"Ø8"Ø
8"Ø8"Ø8"Ø8"Ø2020202020202020
20202020
8"Ø8"Ø8"Ø8"Ø 8"Ø8"Ø8"Ø8"Ø
8"Ø8"Ø8"Ø8"Ø
20202020 20202020 20202020
8"Ø8"Ø8"Ø8"Ø
20202020
20202020 20202020
H.D.H.D.H.D.H.D. H.D.H.D.H.D.H.D. H.D.H.D.H.D.H.D.
8"Ø8"Ø8"Ø8"Ø
H.D.H.D.H.D.H.D. H.D.H.D.H.D.H.D. H.D.H.D.H.D.H.D. H.D.H.D.H.D.H.D.H.D.H.D.H.D.H.D.
8"Ø8"Ø8"Ø8"Ø
H.D.H.D.H.D.H.D.
10"Ø10"Ø10"Ø10"Ø
3333
10101010
3333
H.D.H.D.H.D.H.D.
77776"x6"+1"AL6"x6"+1"AL6"x6"+1"AL6"x6"+1"AL
H.D.H.D.H.D.H.D.
6"Ø6"Ø6"Ø6"Ø
6666 8888
8"Ø8"Ø8"Ø8"Ø
8"
Ø
8"
Ø
8"
Ø
8"
Ø
3333
32323232
8"
Ø
8"
Ø
8"
Ø
8"
Ø 3333
32323232
8"
Ø
8"
Ø
8"
Ø
8"
Ø
3333
32323232
8"
Ø
8"
Ø
8"
Ø
8"
Ø
H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
3333
32323232
8"
Ø
8"
Ø
8"
Ø
8"
Ø
3333
32323232
8"
Ø
8"
Ø
8"
Ø
8"
Ø
3333
H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
342
( QUIET ) OPEN STUDY
8"Ø8"Ø8"Ø8"Ø
8"Ø8"Ø8"Ø8"Ø
14"x10"+1"AL14"x10"+1"AL14"x10"+1"AL14"x10"+1"AL
8"Ø8"Ø8"Ø8"Ø
1111
1111
H.D.H.D.H.D.H.D. H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
1111
8"Ø8"Ø8"Ø8"Ø
8"
Ø
8"
Ø
8"
Ø
8"
Ø
1111
1111
H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
8"Ø8"Ø8"Ø8"Ø
1111
8"Ø8"Ø8"Ø8"Ø
8"Ø8"Ø8"Ø8"Ø
14"x10"+1"AL14"x10"+1"AL14"x10"+1"AL14"x10"+1"AL
1111
1111
H.D.H.D.H.D.H.D.
H.
D
.
H.
D
.
H.
D
.
H.
D
.
H.D.H.D.H.D.H.D.
1111
8"Ø8"Ø8"Ø8"Ø
8"
Ø
8"
Ø
8"
Ø
8"
Ø
1111
1111
H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
8"Ø8"Ø8"Ø8"Ø
H.
D
.
H.
D
.
H.
D
.
H.
D
.
2222
2222
12"x12"+1"AL12"x12"+1"AL12"x12"+1"AL12"x12"+1"AL
10"x6"+1"AL10"x6"+1"AL10"x6"+1"AL10"x6"+1"AL10"x6"+1"AL10"x6"+1"AL10"x6"+1"AL10"x6"+1"AL
13131313
14"Ø14"Ø14"Ø14"Ø
342C342C342C342C
VAVRVAVRVAVRVAVR
14"x16"+1"AL14"x16"+1"AL14"x16"+1"AL14"x16"+1"AL
13131313 13131313 13131313 13131313
10"x6"+1"AL10"x6"+1"AL10"x6"+1"AL10"x6"+1"AL10"x6"+1"AL10"x6"+1"AL10"x6"+1"AL10"x6"+1"AL 10"x6"+1"AL10"x6"+1"AL10"x6"+1"AL10"x6"+1"AL 10"x6"+1"AL10"x6"+1"AL10"x6"+1"AL10"x6"+1"AL
10"x10"+1"AL10"x10"+1"AL10"x10"+1"AL10"x10"+1"AL
14"x12"+1"AL14"x12"+1"AL14"x12"+1"AL14"x12"+1"AL
13131313
10"x6"+1"AL10"x6"+1"AL10"x6"+1"AL10"x6"+1"AL10"x6"+1"AL10"x6"+1"AL10"x6"+1"AL10"x6"+1"AL
13131313
13131313 13131313 13131313 13131313
10"x6"+1"AL10"x6"+1"AL10"x6"+1"AL10"x6"+1"AL10"x6"+1"AL10"x6"+1"AL10"x6"+1"AL10"x6"+1"AL 10"x6"+1"AL10"x6"+1"AL10"x6"+1"AL10"x6"+1"AL 10"x6"+1"AL10"x6"+1"AL10"x6"+1"AL10"x6"+1"AL
13131313
10"x6"+1"AL10"x6"+1"AL10"x6"+1"AL10"x6"+1"AL10"x6"+1"AL10"x6"+1"AL10"x6"+1"AL10"x6"+1"AL
13131313
13131313 13131313 13131313 13131313
10"x6"+1"AL10"x6"+1"AL10"x6"+1"AL10"x6"+1"AL10"x6"+1"AL10"x6"+1"AL10"x6"+1"AL10"x6"+1"AL 10"x6"+1"AL10"x6"+1"AL10"x6"+1"AL10"x6"+1"AL 10"x6"+1"AL10"x6"+1"AL10"x6"+1"AL10"x6"+1"AL
18"Ø18"Ø18"Ø18"Ø
14"Ø14"Ø14"Ø14"Ø
342D342D342D342D
VAVRVAVRVAVRVAVR
16
"
x
1
4
"
+
1
"
A
L
16
"
x
1
4
"
+
1
"
A
L
16
"
x
1
4
"
+
1
"
A
L
16
"
x
1
4
"
+
1
"
A
L
H.D.H.D.H.D.H.D.H.D.H.D.H.D.H.D. H.D.H.D.H.D.H.D.
8"
Ø
8"
Ø
8"
Ø
8"
Ø
8"Ø8"Ø8"Ø8"Ø
H.
D
.
H.
D
.
H.
D
.
H.
D
.
12121212
2222
2222
2222
12121212
8"
Ø
8"
Ø
8"
Ø
8"
Ø
8"Ø8"Ø8"Ø8"Ø
H.
D
.
H.
D
.
H.
D
.
H.
D
.
12121212
H.
D
.
H.
D
.
H.
D
.
H.
D
.
H.D.H.D.H.D.H.D. H.D.H.D.H.D.H.D.H.
D
.
H.
D
.
H.
D
.
H.
D
.
8"
Ø
8"
Ø
8"
Ø
8"
Ø
8"
Ø
8"
Ø
8"
Ø
8"
Ø
H.
D
.
H.
D
.
H.
D
.
H.
D
.
12121212
12121212
H.D.H.D.H.D.H.D. H.D.H.D.H.D.H.D.
8"Ø8"Ø8"Ø8"Ø
H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D. H.D.H.D.H.D.H.D.
21212121
8"Ø8"Ø8"Ø8"Ø
21212121
H.D.H.D.H.D.H.D.
2222
H.D.H.D.H.D.H.D.
8"Ø8"Ø8"Ø8"Ø
21212121 21212121
H.D.H.D.H.D.H.D.
8"Ø8"Ø8"Ø8"Ø
8"x8"+1"AL8"x8"+1"AL8"x8"+1"AL8"x8"+1"AL
21212121
H.D.H.D.H.D.H.D.
8"Ø8"Ø8"Ø8"Ø
21212121
H.D.H.D.H.D.H.D.
8"Ø8"Ø8"Ø8"Ø
2222
H.D.H.D.H.D.H.D. H.D.H.D.H.D.H.D.H.D.H.D.H.D.H.D.
8"Ø8"Ø8"Ø8"Ø
12121212
H.D.H.D.H.D.H.D.
8"Ø8"Ø8"Ø8"Ø
12121212
H.D.H.D.H.D.H.D.
10"x8"+1"AL10"x8"+1"AL10"x8"+1"AL10"x8"+1"AL
H.D.H.D.H.D.H.D.
8"Ø8"Ø8"Ø8"Ø
H.D.H.D.H.D.H.D.
8"Ø8"Ø8"Ø8"Ø
12121212
12121212
H.D.H.D.H.D.H.D.
14"Ø14"Ø14"Ø14"Ø
16"x16"+1"AL16"x16"+1"AL16"x16"+1"AL16"x16"+1"AL
H.D.H.D.H.D.H.D. H.D.H.D.H.D.H.D.H.D.H.D.H.D.H.D.
8"Ø8"Ø8"Ø8"Ø
12121212
H.D.H.D.H.D.H.D.
8"Ø8"Ø8"Ø8"Ø
12121212
H.D.H.D.H.D.H.D.
10"x10"+1"AL10"x10"+1"AL10"x10"+1"AL10"x10"+1"AL
H.D.H.D.H.D.H.D.
8"Ø8"Ø8"Ø8"Ø
H.D.H.D.H.D.H.D.
8"Ø8"Ø8"Ø8"Ø
H.D.H.D.H.D.H.D.
342E342E342E342E
VAVRVAVRVAVRVAVR
12121212
10"Ø10"Ø10"Ø10"ØH.D.H.D.H.D.H.D.
4444
3333
6"Ø6"Ø6"Ø6"Ø
4444
3333
6"Ø6"Ø6"Ø6"Ø
4444
3333
6"Ø6"Ø6"Ø6"Ø
H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
8"Ø8"Ø8"Ø8"Ø
2222
2222
10"Ø10"Ø10"Ø10"Ø
10"Ø10"Ø10"Ø10"Ø
H.D.H.D.H.D.H.D. H.D.H.D.H.D.H.D.
10"Ø10"Ø10"Ø10"Ø
H.D.H.D.H.D.H.D.
11111111 11111111
10"Ø10"Ø10"Ø10"Ø10"Ø10"Ø10"Ø10"Ø
10"Ø10"Ø10"Ø10"Ø11111111 11111111 11111111
H.D.H.D.H.D.H.D. H.D.H.D.H.D.H.D.H.D.H.D.H.D.H.D.
3333
H.D.H.D.H.D.H.D.8"Ø8"Ø8"Ø8"Ø
1111
6"
Ø
6"
Ø
6"
Ø
6"
Ø
3333 4444
H.
D
.
H.
D
.
H.
D
.
H.
D
.
6"
Ø
6"
Ø
6"
Ø
6"
Ø
3333 4444
H.
D
.
H.
D
.
H.
D
.
H.
D
.
6"
Ø
6"
Ø
6"
Ø
6"
Ø
3333
4444
H.
D
.
H.
D
.
H.
D
.
H.
D
.
8"Ø8"Ø8"Ø8"Ø
H.D.H.D.H.D.H.D.
6"
Ø
6"
Ø
6"
Ø
6"
Ø
6"
Ø
6"
Ø
6"
Ø
6"
Ø
6"
Ø
6"
Ø
6"
Ø
6"
Ø
3333 3333 3333H.D.H.D.H.D.H.D. H.D.H.D.H.D.H.D. H.D.H.D.H.D.H.D.
4444 44444444
6"x6"+1"AL6"x6"+1"AL6"x6"+1"AL6"x6"+1"AL
6666
8888
H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
3333
7777
6"Ø6"Ø6"Ø6"Ø
6"Ø6"Ø6"Ø6"Ø
6"Ø6"Ø6"Ø6"Ø
H.D.H.D.H.D.H.D.
4444
3333
FCUFCUFCUFCU
20"x12"+1"AL20"x12"+1"AL20"x12"+1"AL20"x12"+1"AL
20
"
x
1
0
"
+
1
"
A
L
20
"
x
1
0
"
+
1
"
A
L
20
"
x
1
0
"
+
1
"
A
L
20
"
x
1
0
"
+
1
"
A
L
H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
10"Ø10"Ø10"Ø10"Ø 10"Ø10"Ø10"Ø10"Ø
10"Ø10"Ø10"Ø10"Ø 10"Ø10"Ø10"Ø10"Ø
34343434
35353535
36363636
37373737
38383838
39393939
40404040
41414141
42424242
43434343
44444444
45454545
46464646
14141414
41414141
41414141 41414141
A.D.A.D.A.D.A.D.
A.D.A.D.A.D.A.D.
26
"
x
1
8
"
E
X
H
.
26
"
x
1
8
"
E
X
H
.
26
"
x
1
8
"
E
X
H
.
26
"
x
1
8
"
E
X
H
.
36
"
x
1
6
"
F
.
O
.
36
"
x
1
6
"
F
.
O
.
36
"
x
1
6
"
F
.
O
.
36
"
x
1
6
"
F
.
O
.
43434343
12"x10"+1"AL12"x10"+1"AL12"x10"+1"AL12"x10"+1"AL
8"Ø8"Ø8"Ø8"Ø
8"Ø8"Ø8"Ø8"Ø
8"Ø8"Ø8"Ø8"Ø
H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
8"Ø8"Ø8"Ø8"Ø
H.D.H.D.H.D.H.D.
H.D.H.D.H.D.H.D.
20202020
20202020
20202020
20202020
2222
35353535
H.D.H.D.H.D.H.D. H.D.H.D.H.D.H.D.H.D.H.D.H.D.H.D.
10"Ø10"Ø10"Ø10"Ø
36363636
36363636
36363636
36363636
36363636
36363636
35353535
35353535
2222
2222
2222
35353535
3636363636363636
35353535
35353535
35353535
37373737
35353535
35353535
35353535
35353535
35353535
35353535
35353535
35353535
22"x12" EXH.22"x12" EXH.22"x12" EXH.22"x12" EXH.
35353535
35353535
35353535 35353535
35353535
35353535
353535353535353535353535
3535353537373737
37373737
H.D.H.D.H.D.H.D.
6"x6" EXH.6"x6" EXH.6"x6" EXH.6"x6" EXH.
3333
LVTLVTLVTLVT
LVTLVTLVTLVT
2222
2222
43434343
43434343
10"Ø10"Ø10"Ø10"Ø
H.D.H.D.H.D.H.D.
30303030
10"Ø10"Ø10"Ø10"Ø
H.D.H.D.H.D.H.D.
47474747
8"Ø8"Ø8"Ø8"Ø
dbkbo^i=klqbp
A.A.A.A.WHERE UNISTRUTS ARE NOT LOCATED NOR WHERE UNISTRUTS ARE NOT LOCATED NOR WHERE UNISTRUTS ARE NOT LOCATED NOR WHERE UNISTRUTS ARE NOT LOCATED NOR
ACCESSIBLE IN THE BOTTOM OF STRUCTURAL ACCESSIBLE IN THE BOTTOM OF STRUCTURAL ACCESSIBLE IN THE BOTTOM OF STRUCTURAL ACCESSIBLE IN THE BOTTOM OF STRUCTURAL
CONCRETE WEBS, ALL ANCHORS AND SUPPORTS CONCRETE WEBS, ALL ANCHORS AND SUPPORTS CONCRETE WEBS, ALL ANCHORS AND SUPPORTS CONCRETE WEBS, ALL ANCHORS AND SUPPORTS
SHALL BE CONNECTED TO THE SIDES OF THE WEBS. SHALL BE CONNECTED TO THE SIDES OF THE WEBS. SHALL BE CONNECTED TO THE SIDES OF THE WEBS. SHALL BE CONNECTED TO THE SIDES OF THE WEBS.
DO NOT ATTACH TO THE BOTTOM OF THE WEB IF DO NOT ATTACH TO THE BOTTOM OF THE WEB IF DO NOT ATTACH TO THE BOTTOM OF THE WEB IF DO NOT ATTACH TO THE BOTTOM OF THE WEB IF
THERE IS NO EXISTING UNISTRUT.THERE IS NO EXISTING UNISTRUT.THERE IS NO EXISTING UNISTRUT.THERE IS NO EXISTING UNISTRUT.
R.A. OPENINGS WITH SOUND BOOTS DO NOT NEED R.A. OPENINGS WITH SOUND BOOTS DO NOT NEED R.A. OPENINGS WITH SOUND BOOTS DO NOT NEED R.A. OPENINGS WITH SOUND BOOTS DO NOT NEED
TO BE INSTALLED IF THE WALL IN WHICH THEY ARE TO BE INSTALLED IF THE WALL IN WHICH THEY ARE TO BE INSTALLED IF THE WALL IN WHICH THEY ARE TO BE INSTALLED IF THE WALL IN WHICH THEY ARE
LOCATED, IS BETWEEN STRUCTURAL WEBS, AND LOCATED, IS BETWEEN STRUCTURAL WEBS, AND LOCATED, IS BETWEEN STRUCTURAL WEBS, AND LOCATED, IS BETWEEN STRUCTURAL WEBS, AND
THERE ARE OPENINGS, OF TOTAL AREA EQUAL TO OR THERE ARE OPENINGS, OF TOTAL AREA EQUAL TO OR THERE ARE OPENINGS, OF TOTAL AREA EQUAL TO OR THERE ARE OPENINGS, OF TOTAL AREA EQUAL TO OR
GREATER THAN THAT OF THE SOUND BOOT, INTO THE GREATER THAN THAT OF THE SOUND BOOT, INTO THE GREATER THAN THAT OF THE SOUND BOOT, INTO THE GREATER THAN THAT OF THE SOUND BOOT, INTO THE
STRUCTURAL PAN TO ALLOW AIR TO FLOW INTO THE STRUCTURAL PAN TO ALLOW AIR TO FLOW INTO THE STRUCTURAL PAN TO ALLOW AIR TO FLOW INTO THE STRUCTURAL PAN TO ALLOW AIR TO FLOW INTO THE
ADJACENT CEILING SPACE. CONTRACTOR TO ADJACENT CEILING SPACE. CONTRACTOR TO ADJACENT CEILING SPACE. CONTRACTOR TO ADJACENT CEILING SPACE. CONTRACTOR TO
PROVIDE CREDIT FOR SOUND BOOTS THAT WERE PROVIDE CREDIT FOR SOUND BOOTS THAT WERE PROVIDE CREDIT FOR SOUND BOOTS THAT WERE PROVIDE CREDIT FOR SOUND BOOTS THAT WERE
DEEMED UNNECESSARY.DEEMED UNNECESSARY.DEEMED UNNECESSARY.DEEMED UNNECESSARY.
B.B.B.B.
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
Level 03 Area
A Mechanical
Remodel Plan
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
KEY PLAN
A
B
ao^tfkd=klqbp
0000555510101010 10101010 20202020
NOTE
#
DIFFUSER
CALLOUT DESCRIPTION
1111 S-1S-1S-1S-1 160 CFM, 8"Ø NK S.A. DIFFUSER160 CFM, 8"Ø NK S.A. DIFFUSER160 CFM, 8"Ø NK S.A. DIFFUSER160 CFM, 8"Ø NK S.A. DIFFUSER
2222 R-1R-1R-1R-1 22"x22" NK R.A. GRILLE W/ SOUND22"x22" NK R.A. GRILLE W/ SOUND22"x22" NK R.A. GRILLE W/ SOUND22"x22" NK R.A. GRILLE W/ SOUND
BOOTBOOTBOOTBOOT
3333 R-1R-1R-1R-1 22"x10" NK R.A. GRILLE W/ SOUND22"x10" NK R.A. GRILLE W/ SOUND22"x10" NK R.A. GRILLE W/ SOUND22"x10" NK R.A. GRILLE W/ SOUND
BOOTBOOTBOOTBOOT
4444 S-1S-1S-1S-1 50 CFM, 6"Ø NK S.A. DIFFUSER50 CFM, 6"Ø NK S.A. DIFFUSER50 CFM, 6"Ø NK S.A. DIFFUSER50 CFM, 6"Ø NK S.A. DIFFUSER
5555 S-2S-2S-2S-2 50 CFM, 6"Ø NK S.A. DIFFUSER50 CFM, 6"Ø NK S.A. DIFFUSER50 CFM, 6"Ø NK S.A. DIFFUSER50 CFM, 6"Ø NK S.A. DIFFUSER
6666 S-3S-3S-3S-3 100 CFM, 6"x6" NK S.A.DIFFUSER100 CFM, 6"x6" NK S.A.DIFFUSER100 CFM, 6"x6" NK S.A.DIFFUSER100 CFM, 6"x6" NK S.A.DIFFUSER
7777 S-1S-1S-1S-1 100 CFM, 6"Ø NK S.A. DIFFUSER100 CFM, 6"Ø NK S.A. DIFFUSER100 CFM, 6"Ø NK S.A. DIFFUSER100 CFM, 6"Ø NK S.A. DIFFUSER
8888 R-2R-2R-2R-2 10"x6" NK R.A. GRILLE W/ SOUND10"x6" NK R.A. GRILLE W/ SOUND10"x6" NK R.A. GRILLE W/ SOUND10"x6" NK R.A. GRILLE W/ SOUND
BOOTBOOTBOOTBOOT
9999 S-2S-2S-2S-2 175 CFM, 8"Ø NK S.A. DIFFUSER175 CFM, 8"Ø NK S.A. DIFFUSER175 CFM, 8"Ø NK S.A. DIFFUSER175 CFM, 8"Ø NK S.A. DIFFUSER
10101010 S-1S-1S-1S-1 240 CFM, 10"Ø NK S.A. DIFFUSER240 CFM, 10"Ø NK S.A. DIFFUSER240 CFM, 10"Ø NK S.A. DIFFUSER240 CFM, 10"Ø NK S.A. DIFFUSER
11111111 S-1S-1S-1S-1 275 CFM, 10"Ø NK S.A. DIFFUSER275 CFM, 10"Ø NK S.A. DIFFUSER275 CFM, 10"Ø NK S.A. DIFFUSER275 CFM, 10"Ø NK S.A. DIFFUSER
12121212 S-1S-1S-1S-1 185 CFM, 8"Ø NK S.A. DIFFUSER185 CFM, 8"Ø NK S.A. DIFFUSER185 CFM, 8"Ø NK S.A. DIFFUSER185 CFM, 8"Ø NK S.A. DIFFUSER
13131313 S-3S-3S-3S-3 185 CFM, 10"x6" NK S.A.DIFFUSER185 CFM, 10"x6" NK S.A.DIFFUSER185 CFM, 10"x6" NK S.A.DIFFUSER185 CFM, 10"x6" NK S.A.DIFFUSER
14141414 E-2E-2E-2E-2 500 CFM, 10"x10" NK E.A. GRILLE500 CFM, 10"x10" NK E.A. GRILLE500 CFM, 10"x10" NK E.A. GRILLE500 CFM, 10"x10" NK E.A. GRILLE
15151515 S-1S-1S-1S-1 270 CFM, 10"Ø NK S.A. DIFFUSER270 CFM, 10"Ø NK S.A. DIFFUSER270 CFM, 10"Ø NK S.A. DIFFUSER270 CFM, 10"Ø NK S.A. DIFFUSER
16161616 S-1S-1S-1S-1 305 CFM, 10"Ø NK S.A. DIFFUSER305 CFM, 10"Ø NK S.A. DIFFUSER305 CFM, 10"Ø NK S.A. DIFFUSER305 CFM, 10"Ø NK S.A. DIFFUSER
17171717 S-1S-1S-1S-1 280 CFM, 10"Ø NK S.A. DIFFUSER280 CFM, 10"Ø NK S.A. DIFFUSER280 CFM, 10"Ø NK S.A. DIFFUSER280 CFM, 10"Ø NK S.A. DIFFUSER
18181818 S-1S-1S-1S-1 255 CFM, 10"Ø NK S.A. DIFFUSER255 CFM, 10"Ø NK S.A. DIFFUSER255 CFM, 10"Ø NK S.A. DIFFUSER255 CFM, 10"Ø NK S.A. DIFFUSER
19191919 S-1S-1S-1S-1 310 CFM, 10"Ø NK S.A. DIFFUSER310 CFM, 10"Ø NK S.A. DIFFUSER310 CFM, 10"Ø NK S.A. DIFFUSER310 CFM, 10"Ø NK S.A. DIFFUSER
20202020 S-1S-1S-1S-1 210 CFM, 8"Ø NK S.A. DIFFUSER210 CFM, 8"Ø NK S.A. DIFFUSER210 CFM, 8"Ø NK S.A. DIFFUSER210 CFM, 8"Ø NK S.A. DIFFUSER
21212121 S-1S-1S-1S-1 125 CFM, 8"Ø NK S.A. DIFFUSER125 CFM, 8"Ø NK S.A. DIFFUSER125 CFM, 8"Ø NK S.A. DIFFUSER125 CFM, 8"Ø NK S.A. DIFFUSER
22222222 S-3S-3S-3S-3 125 CFM, 8"x6" NK S.A.DIFFUSER125 CFM, 8"x6" NK S.A.DIFFUSER125 CFM, 8"x6" NK S.A.DIFFUSER125 CFM, 8"x6" NK S.A.DIFFUSER
23232323 S-1S-1S-1S-1 205 CFM, 8"Ø NK S.A. DIFFUSER205 CFM, 8"Ø NK S.A. DIFFUSER205 CFM, 8"Ø NK S.A. DIFFUSER205 CFM, 8"Ø NK S.A. DIFFUSER
24242424 S-1S-1S-1S-1 335 CFM, 10"Ø NK S.A. DIFFUSER335 CFM, 10"Ø NK S.A. DIFFUSER335 CFM, 10"Ø NK S.A. DIFFUSER335 CFM, 10"Ø NK S.A. DIFFUSER
25252525 S-1S-1S-1S-1 250 CFM, 10"Ø NK S.A. DIFFUSER250 CFM, 10"Ø NK S.A. DIFFUSER250 CFM, 10"Ø NK S.A. DIFFUSER250 CFM, 10"Ø NK S.A. DIFFUSER
26262626 S-1S-1S-1S-1 105 CFM, 8"Ø NK S.A. DIFFUSER105 CFM, 8"Ø NK S.A. DIFFUSER105 CFM, 8"Ø NK S.A. DIFFUSER105 CFM, 8"Ø NK S.A. DIFFUSER
27272727 S-1S-1S-1S-1 145 CFM, 8"Ø NK S.A. DIFFUSER145 CFM, 8"Ø NK S.A. DIFFUSER145 CFM, 8"Ø NK S.A. DIFFUSER145 CFM, 8"Ø NK S.A. DIFFUSER
28282828 S-1S-1S-1S-1 185 CFM, 8"Ø NK S.A. DIFFUSER185 CFM, 8"Ø NK S.A. DIFFUSER185 CFM, 8"Ø NK S.A. DIFFUSER185 CFM, 8"Ø NK S.A. DIFFUSER
29292929 S-2S-2S-2S-2 250 CFM, 10"Ø NK S.A. DIFFUSER250 CFM, 10"Ø NK S.A. DIFFUSER250 CFM, 10"Ø NK S.A. DIFFUSER250 CFM, 10"Ø NK S.A. DIFFUSER
30303030 S-2S-2S-2S-2 350 CFM, 10"Ø NK S.A. DIFFUSER350 CFM, 10"Ø NK S.A. DIFFUSER350 CFM, 10"Ø NK S.A. DIFFUSER350 CFM, 10"Ø NK S.A. DIFFUSER
31313131 S-1S-1S-1S-1 170 CFM, 8"Ø NK S.A. DIFFUSER170 CFM, 8"Ø NK S.A. DIFFUSER170 CFM, 8"Ø NK S.A. DIFFUSER170 CFM, 8"Ø NK S.A. DIFFUSER
32323232 S-1S-1S-1S-1 225 CFM, 8"Ø NK S.A. DIFFUSER225 CFM, 8"Ø NK S.A. DIFFUSER225 CFM, 8"Ø NK S.A. DIFFUSER225 CFM, 8"Ø NK S.A. DIFFUSER
33333333 S-1S-1S-1S-1 230 CFM, 8"Ø NK S.A. DIFFUSER230 CFM, 8"Ø NK S.A. DIFFUSER230 CFM, 8"Ø NK S.A. DIFFUSER230 CFM, 8"Ø NK S.A. DIFFUSER
34343434 RISE 10"x10" E.A. DUCT UP.RISE 10"x10" E.A. DUCT UP.RISE 10"x10" E.A. DUCT UP.RISE 10"x10" E.A. DUCT UP.
TRANSITION IN RISE AND CONNECT TOTRANSITION IN RISE AND CONNECT TOTRANSITION IN RISE AND CONNECT TOTRANSITION IN RISE AND CONNECT TO
REF-3.REF-3.REF-3.REF-3.
35353535 12"x12"+1"AL R.A. OPENING W/12"x12"+1"AL R.A. OPENING W/12"x12"+1"AL R.A. OPENING W/12"x12"+1"AL R.A. OPENING W/
SOUND BOOT ABOVE CEILING.SOUND BOOT ABOVE CEILING.SOUND BOOT ABOVE CEILING.SOUND BOOT ABOVE CEILING.
36363636 16"x16"+1"AL R.A. OPENING W/16"x16"+1"AL R.A. OPENING W/16"x16"+1"AL R.A. OPENING W/16"x16"+1"AL R.A. OPENING W/
SOUND BOOT ABOVE CEILING.SOUND BOOT ABOVE CEILING.SOUND BOOT ABOVE CEILING.SOUND BOOT ABOVE CEILING.
37373737 18"x18"+1"AL R.A. OPENING W/18"x18"+1"AL R.A. OPENING W/18"x18"+1"AL R.A. OPENING W/18"x18"+1"AL R.A. OPENING W/
SOUND BOOT ABOVE CEILING.SOUND BOOT ABOVE CEILING.SOUND BOOT ABOVE CEILING.SOUND BOOT ABOVE CEILING.
38383838 48"x22" RETURN AIR OPENING IN WALL48"x22" RETURN AIR OPENING IN WALL48"x22" RETURN AIR OPENING IN WALL48"x22" RETURN AIR OPENING IN WALL
ABOVE CEILING W/ F.S.D.ABOVE CEILING W/ F.S.D.ABOVE CEILING W/ F.S.D.ABOVE CEILING W/ F.S.D.
39393939 66"x22" RETURN AIR OPENING IN WALL66"x22" RETURN AIR OPENING IN WALL66"x22" RETURN AIR OPENING IN WALL66"x22" RETURN AIR OPENING IN WALL
ABOVE CEILING W/ F.S.D.ABOVE CEILING W/ F.S.D.ABOVE CEILING W/ F.S.D.ABOVE CEILING W/ F.S.D.
40404040 66"x36" RETURN AIR OPENING IN WALL66"x36" RETURN AIR OPENING IN WALL66"x36" RETURN AIR OPENING IN WALL66"x36" RETURN AIR OPENING IN WALL
ABOVE CEILING W/ F.S.D.ABOVE CEILING W/ F.S.D.ABOVE CEILING W/ F.S.D.ABOVE CEILING W/ F.S.D.
41414141 S-2S-2S-2S-2 300 CFM, 10"Ø NK S.A. DIFFUSER300 CFM, 10"Ø NK S.A. DIFFUSER300 CFM, 10"Ø NK S.A. DIFFUSER300 CFM, 10"Ø NK S.A. DIFFUSER
42424242 RISE 26"x18" E.A. DUCT UP.RISE 26"x18" E.A. DUCT UP.RISE 26"x18" E.A. DUCT UP.RISE 26"x18" E.A. DUCT UP.
TRANSITION IN RISE AND CONNECT TOTRANSITION IN RISE AND CONNECT TOTRANSITION IN RISE AND CONNECT TOTRANSITION IN RISE AND CONNECT TO
REF-1.REF-1.REF-1.REF-1.
43434343 E-1E-1E-1E-1 350 CFM, MATCH PREVIOUS GRILLE350 CFM, MATCH PREVIOUS GRILLE350 CFM, MATCH PREVIOUS GRILLE350 CFM, MATCH PREVIOUS GRILLE
FACE AND NECK SIZE AND CONNECTFACE AND NECK SIZE AND CONNECTFACE AND NECK SIZE AND CONNECTFACE AND NECK SIZE AND CONNECT
TO EXISTING E.A. DUCTWORK.TO EXISTING E.A. DUCTWORK.TO EXISTING E.A. DUCTWORK.TO EXISTING E.A. DUCTWORK.
44444444 BALANCE EXISTING E.A. GRILLE TO 100BALANCE EXISTING E.A. GRILLE TO 100BALANCE EXISTING E.A. GRILLE TO 100BALANCE EXISTING E.A. GRILLE TO 100
CFM.CFM.CFM.CFM.
45454545 RISE 22"x12" E.A. DUCT UP.RISE 22"x12" E.A. DUCT UP.RISE 22"x12" E.A. DUCT UP.RISE 22"x12" E.A. DUCT UP.
TRANSITION IN RISE AND CONNECT TOTRANSITION IN RISE AND CONNECT TOTRANSITION IN RISE AND CONNECT TOTRANSITION IN RISE AND CONNECT TO
REF-2.REF-2.REF-2.REF-2.
46464646 E-1E-1E-1E-1 100 CFM, 6"x6" NK E.A. GRILLE100 CFM, 6"x6" NK E.A. GRILLE100 CFM, 6"x6" NK E.A. GRILLE100 CFM, 6"x6" NK E.A. GRILLE
47474747 T-1T-1T-1T-1 18"x18" NK T.A. GRILLE W/ SOUND18"x18" NK T.A. GRILLE W/ SOUND18"x18" NK T.A. GRILLE W/ SOUND18"x18" NK T.A. GRILLE W/ SOUND
BOOTBOOTBOOTBOOT
SCALE:SCALE:SCALE:SCALE:MH103aMH103aMH103aMH103a 1/8" = 1'1/8" = 1'1/8" = 1'1/8" = 1'----0"0"0"0"
ibsbi=P=^ob^=^=jb`e^kf`^i=objlabi=mi^k1111
1111
GGGG
JJJJ
LLLL
MMMM
NNNN
PPPP
QQQQ
EEEE
CCCC
2222 3333 4444 5555
DXFCUDXFCUDXFCUDXFCU
1111
(CONDENSING(CONDENSING(CONDENSING(CONDENSING
UNIT)UNIT)UNIT)UNIT)
2222
REFREFREFREF
1111
REFREFREFREF
3333
REFREFREFREF
1111
245B245B245B245B
SCUSCUSCUSCU
245A245A245A245A
SCUSCUSCUSCU
(E) CURB
TO REMAIN
PROVIDE NEWPROVIDE NEWPROVIDE NEWPROVIDE NEW
18" TALL CURB18" TALL CURB18" TALL CURB18" TALL CURB
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
Roof Area A
Mechanical
Remodel Plan
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
SCALE:SCALE:SCALE:SCALE:MH104aMH104aMH104aMH104a 1/8" = 1'1/8" = 1'1/8" = 1'1/8" = 1'----0"0"0"0"
ollc=^ob^=^=jb`e^kf`^i=objlabi=mi^k1111 KEY PLAN
A
B
ao^tfkd=klqbp
0000555510101010 10101010 20202020
NOTE
#DESCRIPTION
1111 REFRIGERANT LINES UP FROM LEVEL BELOW ANDREFRIGERANT LINES UP FROM LEVEL BELOW ANDREFRIGERANT LINES UP FROM LEVEL BELOW ANDREFRIGERANT LINES UP FROM LEVEL BELOW AND
CONNECT TO DXFCU-1 CONDENSING UNIT. SIZECONNECT TO DXFCU-1 CONDENSING UNIT. SIZECONNECT TO DXFCU-1 CONDENSING UNIT. SIZECONNECT TO DXFCU-1 CONDENSING UNIT. SIZE
AND INSTALL REFRIGERANT LINES PERAND INSTALL REFRIGERANT LINES PERAND INSTALL REFRIGERANT LINES PERAND INSTALL REFRIGERANT LINES PER
MANUFACTURER'S REQUIREMENTS. SEE DRAWINGMANUFACTURER'S REQUIREMENTS. SEE DRAWINGMANUFACTURER'S REQUIREMENTS. SEE DRAWINGMANUFACTURER'S REQUIREMENTS. SEE DRAWING
MP113a FOR CONTINUATION.MP113a FOR CONTINUATION.MP113a FOR CONTINUATION.MP113a FOR CONTINUATION.
16161616151515151414141413131313121212121111111110101010999988887777
KKKK
HHHH
FFFF
DDDD
BBBB
AAAA
(E) REF
(E) REF
280A280A280A280A
SCUSCUSCUSCU
280B280B280B280B
SCUSCUSCUSCU
4444
REFREFREFREF
PROVIDE NEWPROVIDE NEWPROVIDE NEWPROVIDE NEW
18" TALL CURB18" TALL CURB18" TALL CURB18" TALL CURB
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
Roof Area B
Mechanical
Remodel Plan
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
KEY PLAN
A
B
ao^tfkd=klqbp
0000555510101010 10101010 20202020
SCALE:SCALE:SCALE:SCALE:MH104bMH104bMH104bMH104b 1/8" = 1'1/8" = 1'1/8" = 1'1/8" = 1'----0"0"0"0"
ollc=^ob^=_=jb`e^kf`^i=objlabi=mi^k1111
1111
GGGG
JJJJ
EEEE
2222 3333
030
MECH
ROOM
(E) AIR HANDLING UNIT
1111
2222
4444
5555
6666
3333 18"Ø18"Ø18"Ø18"Ø
4444
6666 7777
54"x68"F.O.54"x68"F.O.54"x68"F.O.54"x68"F.O.
1111
62"Ø62"Ø62"Ø62"Ø
AAAA
MH401MH401MH401MH401
BBBB
MH401MH401MH401MH401
8"Ø8"Ø8"Ø8"Ø
002002002002
VAVRVAVRVAVRVAVR
(E)40"x18"+1"AL R.A.
18"Ø18"Ø18"Ø18"Ø
3333
18"Ø18"Ø18"Ø18"Ø
56"x46" F.O.56"x46" F.O.56"x46" F.O.56"x46" F.O.
+2" INS. W/+2" INS. W/+2" INS. W/+2" INS. W/
PERF. LINERPERF. LINERPERF. LINERPERF. LINER
78"x46" F.O.+2" INSULATION78"x46" F.O.+2" INSULATION78"x46" F.O.+2" INSULATION78"x46" F.O.+2" INSULATION
DOUBLE WALL DUCT W/ PERF. DOUBLE WALL DUCT W/ PERF. DOUBLE WALL DUCT W/ PERF. DOUBLE WALL DUCT W/ PERF.
LINERLINERLINERLINER
(E) R.A. SOUND TRAP
3333
54"Ø+2" INS. 54"Ø+2" INS. 54"Ø+2" INS. 54"Ø+2" INS.
DOUBLE WALL DUCTDOUBLE WALL DUCTDOUBLE WALL DUCTDOUBLE WALL DUCT
W/ PERF. INNER LINERW/ PERF. INNER LINERW/ PERF. INNER LINERW/ PERF. INNER LINER
62"Ø +2" INSULATION62"Ø +2" INSULATION62"Ø +2" INSULATION62"Ø +2" INSULATION
DOUBLE WALL DUCT W/ PERF. DOUBLE WALL DUCT W/ PERF. DOUBLE WALL DUCT W/ PERF. DOUBLE WALL DUCT W/ PERF.
INNER LINERINNER LINERINNER LINERINNER LINER
(E) R.A. SOUND TRAP
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
Enlarged
Level 00 Area
A Mechanical
Remodel Plan
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
ao^tfkd=klqbp
00002.52.52.52.55555 5555 10101010
NOTE
#DESCRIPTION
1111 54"Ø+2" INSULATION DOUBLE WALL DUCT WITH54"Ø+2" INSULATION DOUBLE WALL DUCT WITH54"Ø+2" INSULATION DOUBLE WALL DUCT WITH54"Ø+2" INSULATION DOUBLE WALL DUCT WITH
PERFORATED INNER LINER. TRANSITION ANDPERFORATED INNER LINER. TRANSITION ANDPERFORATED INNER LINER. TRANSITION ANDPERFORATED INNER LINER. TRANSITION AND
CONNECT DUCT TO EXISTING AIR HANDLING UNITCONNECT DUCT TO EXISTING AIR HANDLING UNITCONNECT DUCT TO EXISTING AIR HANDLING UNITCONNECT DUCT TO EXISTING AIR HANDLING UNIT
(96"x60" OPENING).(96"x60" OPENING).(96"x60" OPENING).(96"x60" OPENING).
2222 62"Ø+2" INSULATION DOUBLE WALL DUCT WITH62"Ø+2" INSULATION DOUBLE WALL DUCT WITH62"Ø+2" INSULATION DOUBLE WALL DUCT WITH62"Ø+2" INSULATION DOUBLE WALL DUCT WITH
PERFORATED INNER LINER.PERFORATED INNER LINER.PERFORATED INNER LINER.PERFORATED INNER LINER.
3333 46"x58" F.O.+2" INSULATION DOUBLE WALL DUCT46"x58" F.O.+2" INSULATION DOUBLE WALL DUCT46"x58" F.O.+2" INSULATION DOUBLE WALL DUCT46"x58" F.O.+2" INSULATION DOUBLE WALL DUCT
WITH PERFORATED INNER LINER. TRANSITION ANDWITH PERFORATED INNER LINER. TRANSITION ANDWITH PERFORATED INNER LINER. TRANSITION ANDWITH PERFORATED INNER LINER. TRANSITION AND
CONNECT DUCT TO EXISTING AIR HANDLING UNITCONNECT DUCT TO EXISTING AIR HANDLING UNITCONNECT DUCT TO EXISTING AIR HANDLING UNITCONNECT DUCT TO EXISTING AIR HANDLING UNIT
(69"x60" OPENING).(69"x60" OPENING).(69"x60" OPENING).(69"x60" OPENING).
4444 78"x46" F.O.+2" INSULATION DOUBLE WALL DUCT78"x46" F.O.+2" INSULATION DOUBLE WALL DUCT78"x46" F.O.+2" INSULATION DOUBLE WALL DUCT78"x46" F.O.+2" INSULATION DOUBLE WALL DUCT
WITH PERFORATED INNER LINER.WITH PERFORATED INNER LINER.WITH PERFORATED INNER LINER.WITH PERFORATED INNER LINER.
5555 DROP DUCT DOWN THROUGH GRATING TO TUNNELDROP DUCT DOWN THROUGH GRATING TO TUNNELDROP DUCT DOWN THROUGH GRATING TO TUNNELDROP DUCT DOWN THROUGH GRATING TO TUNNEL
BELOW. MODIFY OPENING IN GRATING TOBELOW. MODIFY OPENING IN GRATING TOBELOW. MODIFY OPENING IN GRATING TOBELOW. MODIFY OPENING IN GRATING TO
ACCOMMODATE NEW DUCT. IT IS THE INTENTACCOMMODATE NEW DUCT. IT IS THE INTENTACCOMMODATE NEW DUCT. IT IS THE INTENTACCOMMODATE NEW DUCT. IT IS THE INTENT
THAT THE NEW DUCT FIT BETWEEN THE EXISTINGTHAT THE NEW DUCT FIT BETWEEN THE EXISTINGTHAT THE NEW DUCT FIT BETWEEN THE EXISTINGTHAT THE NEW DUCT FIT BETWEEN THE EXISTING
BEAMS SUPPORTING THE GRATING.BEAMS SUPPORTING THE GRATING.BEAMS SUPPORTING THE GRATING.BEAMS SUPPORTING THE GRATING.
6666 DUCTWORK BELOW FLOOR IN TUNNEL.DUCTWORK BELOW FLOOR IN TUNNEL.DUCTWORK BELOW FLOOR IN TUNNEL.DUCTWORK BELOW FLOOR IN TUNNEL.
7777 TRANSITION FROM 78"x46" F.O. TO 54"x68" F.O.TRANSITION FROM 78"x46" F.O. TO 54"x68" F.O.TRANSITION FROM 78"x46" F.O. TO 54"x68" F.O.TRANSITION FROM 78"x46" F.O. TO 54"x68" F.O.
END WALL DUCT AT TRANSITION.END WALL DUCT AT TRANSITION.END WALL DUCT AT TRANSITION.END WALL DUCT AT TRANSITION.
SCALE: NONESCALE: NONESCALE: NONESCALE: NONEMH401MH401MH401MH401
bki^odba=ibsbi=MM=^ob^=^=jb`e^kf`^i=objlabi=mi^k1111
SCALE:SCALE:SCALE:SCALE:MH401MH401MH401MH401 1/4" = 1'1/4" = 1'1/4" = 1'1/4" = 1'----0"0"0"0"
jb`e^kf`^i=pb`qflkAAAA
00002.52.52.52.55555 5555 10101010
SCALE:SCALE:SCALE:SCALE:MH401MH401MH401MH401 1/4" = 1'1/4" = 1'1/4" = 1'1/4" = 1'----0"0"0"0"
jb`e^kf`^i=pb`qflkBBBB
00002.52.52.52.55555 5555 10101010
KEY PLAN
A
B
999988887777
DDDD
BBBB
2" SHWS/R2" SHWS/R2" SHWS/R2" SHWS/R
1111
1111----1/4" SHWS/R1/4" SHWS/R1/4" SHWS/R1/4" SHWS/R
SEE DRAWING MP110bSEE DRAWING MP110bSEE DRAWING MP110bSEE DRAWING MP110b
FOR CONTINUATIONFOR CONTINUATIONFOR CONTINUATIONFOR CONTINUATION
SEE DRAWING MP111bSEE DRAWING MP111bSEE DRAWING MP111bSEE DRAWING MP111b
FOR CONTINUATIONFOR CONTINUATIONFOR CONTINUATIONFOR CONTINUATION
VFDVFDVFDVFD
1111
VFDVFDVFDVFD
2222
2222
3333
4444
5555
6666
2222
3333
48"x22"F.O.48"x22"F.O.48"x22"F.O.48"x22"F.O.
48"x22"F.O.48"x22"F.O.48"x22"F.O.48"x22"F.O.
(E)HWS AND HWR
UP IN CHASE ABOVE
(E) RETURN AIR
CHASE ABOVE
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
Enlarged
Level 01 Area
B Mechanical
Room
Remodel Plan
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
ao^tfkd=klqbp
00002.52.52.52.55555 5555 10101010
SCALE:SCALE:SCALE:SCALE:MH402MH402MH402MH402 1/4" = 1'1/4" = 1'1/4" = 1'1/4" = 1'----0"0"0"0"
bki^odba=ibsbi=N=^ob^=_=jb`e^kf`^i=ollj=objlabi=mi^k1111
NOTE
#DESCRIPTION
1111 ROUTE NEW 2" SHWS/R PIPING HIGH INROUTE NEW 2" SHWS/R PIPING HIGH INROUTE NEW 2" SHWS/R PIPING HIGH INROUTE NEW 2" SHWS/R PIPING HIGH IN
MECHANICAL ROOM THEN DROP DOWN WALL ANDMECHANICAL ROOM THEN DROP DOWN WALL ANDMECHANICAL ROOM THEN DROP DOWN WALL ANDMECHANICAL ROOM THEN DROP DOWN WALL AND
CONTINUE INTO TUNNEL. REFERENCE DRAWINGCONTINUE INTO TUNNEL. REFERENCE DRAWINGCONTINUE INTO TUNNEL. REFERENCE DRAWINGCONTINUE INTO TUNNEL. REFERENCE DRAWING
MP110b FOR CONTINUATION.MP110b FOR CONTINUATION.MP110b FOR CONTINUATION.MP110b FOR CONTINUATION.
2222 52"x24" F.O. +2" INSULATION DOUBLE WALL52"x24" F.O. +2" INSULATION DOUBLE WALL52"x24" F.O. +2" INSULATION DOUBLE WALL52"x24" F.O. +2" INSULATION DOUBLE WALL
DUCT WITH PERFORATED METAL LINER UP RETURNDUCT WITH PERFORATED METAL LINER UP RETURNDUCT WITH PERFORATED METAL LINER UP RETURNDUCT WITH PERFORATED METAL LINER UP RETURN
AIR CHASE ABOVE. SEE MH102b FORAIR CHASE ABOVE. SEE MH102b FORAIR CHASE ABOVE. SEE MH102b FORAIR CHASE ABOVE. SEE MH102b FOR
CONTINUATION.CONTINUATION.CONTINUATION.CONTINUATION.
3333 52"x26"+2" INSULATION DOUBLE WALL DUCT WITH52"x26"+2" INSULATION DOUBLE WALL DUCT WITH52"x26"+2" INSULATION DOUBLE WALL DUCT WITH52"x26"+2" INSULATION DOUBLE WALL DUCT WITH
PERFORATED METAL LINER. USE DOUBLE WALLPERFORATED METAL LINER. USE DOUBLE WALLPERFORATED METAL LINER. USE DOUBLE WALLPERFORATED METAL LINER. USE DOUBLE WALL
DUCT FROM PLENUM CONNECTION THROUGHDUCT FROM PLENUM CONNECTION THROUGHDUCT FROM PLENUM CONNECTION THROUGHDUCT FROM PLENUM CONNECTION THROUGH
ELBOW THEN TRANSITION TO SINGLE WALL DUCT.ELBOW THEN TRANSITION TO SINGLE WALL DUCT.ELBOW THEN TRANSITION TO SINGLE WALL DUCT.ELBOW THEN TRANSITION TO SINGLE WALL DUCT.
4444 RECONSTRUCT EXISTING PLENUM TORECONSTRUCT EXISTING PLENUM TORECONSTRUCT EXISTING PLENUM TORECONSTRUCT EXISTING PLENUM TO
ACCOMODATE NEW OPENINGS FOR NEWACCOMODATE NEW OPENINGS FOR NEWACCOMODATE NEW OPENINGS FOR NEWACCOMODATE NEW OPENINGS FOR NEW
DUCTWORK. EXISTING PLENUM HAS MULTIPLEDUCTWORK. EXISTING PLENUM HAS MULTIPLEDUCTWORK. EXISTING PLENUM HAS MULTIPLEDUCTWORK. EXISTING PLENUM HAS MULTIPLE
OPENINGS IN DIFFERENT LOCATIONS THAT WILLOPENINGS IN DIFFERENT LOCATIONS THAT WILLOPENINGS IN DIFFERENT LOCATIONS THAT WILLOPENINGS IN DIFFERENT LOCATIONS THAT WILL
NEED TO BE CAPPED AND SEALED SOMENEED TO BE CAPPED AND SEALED SOMENEED TO BE CAPPED AND SEALED SOMENEED TO BE CAPPED AND SEALED SOME
SECTIONS OF THE PLENUM MAY NEED TO BESECTIONS OF THE PLENUM MAY NEED TO BESECTIONS OF THE PLENUM MAY NEED TO BESECTIONS OF THE PLENUM MAY NEED TO BE
REPLACED.REPLACED.REPLACED.REPLACED.
5555 REMOVE PORTIONS OF THE EXISTING CEILING INREMOVE PORTIONS OF THE EXISTING CEILING INREMOVE PORTIONS OF THE EXISTING CEILING INREMOVE PORTIONS OF THE EXISTING CEILING IN
THIS LOCATION TO ENABLE DUCT TO FIT UP TIGHTTHIS LOCATION TO ENABLE DUCT TO FIT UP TIGHTTHIS LOCATION TO ENABLE DUCT TO FIT UP TIGHTTHIS LOCATION TO ENABLE DUCT TO FIT UP TIGHT
TO STRUCTURE.TO STRUCTURE.TO STRUCTURE.TO STRUCTURE.
6666 168"x30" R.A. OPENING IN WALL ABOVE CEILING168"x30" R.A. OPENING IN WALL ABOVE CEILING168"x30" R.A. OPENING IN WALL ABOVE CEILING168"x30" R.A. OPENING IN WALL ABOVE CEILING
TO THE WEST.TO THE WEST.TO THE WEST.TO THE WEST.
KEY PLAN
A
B
SINGLE VANE SCHEDULE
ONE SIDE
SQUARE ELBOW
NOTES:
RADIUS ELBOW
BOTH SIDES
45 DEG. ELBOW
45 DEG. TURNING VANE DETAIL
30 DEG. MAX.
1/2 W
INSIDE SQUARE, OUTSIDE RADIUS
ALL DUCTS (SUPPLY, RETURN
AND EXHAUST) TO HAVE TURNING
ELBOWS NOT ALLOWED.
2.
VANES IN SQUARE ELBOW.
1.
W
15 DEG. MAX.
TURNING
VANES
SINGLE
BLADE
SINGLE BLADE
SMALL
LARGE
2"
R
(51mm)
4-1/2"
(114mm)
1-1/2"
SP
(38mm)
3-1/4"
(83mm)
24
GA
(0.70mm)
22
(0.85mm)
22.5
(TYP.)
TURNING VANES,
SEE DETAIL AND
SCHEDULE BELOW
CL
45° LATERAL TEE
CONICAL 90° TEE
Y-BRANCH 90°
BRANCH TAKE-OFF
DIMENSIONS
FABRICATED ELBOW
D
R
ADD ONE PIECE FOR
EACH ADDITIONAL 18°
R = 1.5D
D = DUCT SIZE
0-35° ---- 2 PIECE
72-90° ----5 PIECE
36-71° ----3 PIECE
L
D
MITERED 90° ELBOW
REDUCER
OFFSET
1A MAX.
2"
1-1/4"
A
2A
TURNING
VANES
A
1-1/4"
D
45°
D = DUCT SIZE
DIMENSIONS
L = D/2+1"
D
2"
DUCT SIDE. PROVIDE 1" TRAILING
TO START AND STOP PARALLEL WITH
ANGLE OF DIRECTION CHANGE. VANES
EXHAUST) TO HAVE TURNING VANES
ALL DUCTS (SUPPLY, RETURN AND
WITH SQUARE TYPE ELBOWS AT ANY
EDGE.
NOTE:
kl=mlm=ofsbqp=^iiltba
HANGER STRAPS
`lkpqor`qflk=pq^ka^oap
ar`q=mbo=pj^`k^=es^`=ar`q
e^kdbo=pfwbp=clo=olrka
SELF TAPPING HEX HEAD SHEET
METAL SCREWS. STRAPS TO BE
TIGHT AGAINST DUCT
NO POP RIVETS ALLOWED
PER SMACNA HVAC DUCT CONSTRUCTION
HANGER SIZES FOR RECTANGULAR DUCT
STANDARDS.
TIGHT AGAINST DUCT.
SHEET METAL SCREWS. STRAPS TO BE
SELF TAPPING CADIUM PLATED HEX HEAD
1
HANGER STRAPS
ANGLE IRON
ROUND/OVAL DUCT
ANGLE IRON
HANGER STRAPS
e^kdbo=pfwbp=clo=olrka=L=ls^i
ar`q=mbo=pj^`k^=es^`=ar`q
`lkpqor`qflk=pq^ka^oap
ENDS OF LINER SHALL BE
COATED WITH ADHESIVE.
METAL DUCT
GALVANIZED SHEET
ALL ENDS OF LINER TO BE
BUTTED FIRMLY TOGETHER.
1 2 " C .C . M A X .
SIZED PER DRAWING
FROM EDGE OF LINER
NOT MORE THAN 2"
(TY P .)
2 "
DUCT LINER
ADHESIVE
ADHERED TO
DUCT W/100%
DUCT LINER.
LINER TO BE
TOP AND BOTTOM SECTION
OF LINER SHALL OVERLAP
THE SIDES
ROUND SHEET METAL DUCT
12" MAX. LENGTH
FACTORY MADE DUCT
5/8" SCREW TIGHTENING BINDING
STRAP OR NYLON CINCHE BAND.
2"
NOTE:
FOR INSULATED DUCT, PROVIDE ONE
ADDITIONAL BAND AROUND THE
INSULATION.
RETURN
SHEET METAL SCREWS
1" WIDE
22 GA. SHEET
UNDER 2" AND
FASTEN WITH
SHEET METAL
TURN HANGER
METAL SKIN
ACOUSTICAL
1" INTERIOR
DENSITY
LINING, 1 PCF
SCREW.W
(1 2" MI N .)
W
1/2 W (MIN. 8"+AL)
GRILLE
LENGTH
1/2 W
HANGING
STRAP
AIR GRILLE
BLADE MULTIPLES
(TACK WELD ROD
BLADE WITH V-GROOVE
SECURELY TO BLADE)
STRAP, RIVET TO BLADE
SHEET METAL DUCT
22 GA. BLADE 1/2"
SPRING LOADED END
TO BLADE (BLADE MUST
TACK WELD OR RIVET
APPROX. Ì" ON ALL SIDES)
CLEAR LINER OR DUCT
STRAP 1/2" ROD
DUCT SECTION
LOCKING QUADRANT
UP TO 30" - 3 BLADES
UP TO 20" - 2 BLADES
DUCT DEPTH
UP TO 12" - 1 BLADE
BLADE SECTION
(ONE PER BLADE)
LOCKING QUADRANT
1/2" ROD
RECTANGULAR DUCT
SEE PLANS FOR SIZING45 DEG. DUCT CONNECTION
BRANCH DUCT OR
SEE PLANS FOR SIZING
RUNOUT TO DIFFUSER
NOTE: MIN. AREA OF AxB SHALL
EQUAL CROSS SECTION AREA OF
AREA OF AxC SHALL BE EQUAL
ROUND DUCT RUNOUT TO DIFFUSER
HAND DAMPER
SEE PLANS FOR SIZING
RECTANGULAR DUCT
A
B
C
SEE PLANS FOR SIZING
45 BRANCH DUCT.
TO 1.5xAREA OF AxB.
MANUFACTURER
MANUFACTURER
FIRE/SMOKE DAMPER. LOCATE
IN WALL AS REQUIRED BY
MANUFACTURER. ALL AROUND
16 GA. MIN. OR AS REQUIRED BY
SLEEVE GAUGE AS REQUIRED BY
RETURN OR SUPPLY
SLIP CONNECTION (TYP.)
LENGTH PRIOR TO ORDERING
VERIFY REQUIRED SLEEVE
DAMPER ACTUATOR LARGE ENOUGH
DAMPER LINKAGE AND SMOKE
12"x12" MINIMUM
TO SERVICE AND RESET DAMPER.
RETURN OR SUPPLY
AIR DUCT. SEE PLANS
PROVIDE ACCESS DOOR TO FIRE
FOR SIZES
AIR DUCT
DAMPER ACTUATOR
MINIMUM & MAXIMUM CLEARANCE
AS REQUIRED BY MANUFACTURER
FIREWALL
DUCT-SEE PLANS FOR SIZE,
LOCATION AND CONTINUATION
NUMBER
HINGES
16 X 16
24 X 24
12 X 12
6 X 6
MAXIMUM
DIMENSION
GAUGE
BACK
24 2622
3 2 22 26
HANDLES
2
2
1
1
NUMBER
OF OF
26
26
26
26
DOOR
22
22
26
24
FRAME
BUTT HINGE
1"x1" (.025x.025)
LOCATION
ACCESS DOOR. SEE
PLANS FOR SIZE AND
SASH LOCK
GASKET
DUCT EXTERIOR
DENSITY FIBERGLASS
DUCT LINER 1" (.025) THICK
ONE AND ONE HALF POUND
NOTE:
IN ADDITION TO THOSE DOORS SHOWN
DOORS SHOWN IN THE DRAWINGS, THE
SHEET METAL CONTRACTOR SHALL
INSTALL AN ACCESS DOOR AT EACH
FIRE AND FIRE/ SMOKE DAMPER.
FROM MANUFACT. RECOMMEND.
FROM MANUFACT. RECOMMEND.
SAME AS MOTOR NAMEPLATE
INDICATE - STATIC PRESSURE, FOOT OF
HEAD ETC. AND RPM IF APPLICABLE
LUB. FREQUENCY:
MOTOR RPM/HP:
AREA SERVED:
LUBRICANT:
AT:
REFER TO PLANS
RPM
INDICATE TONS, GPM, CFM ETC.
SIZE:TYPE:
ITEM NAME/#:
CAPACITY:
CONTENTS:
FUNCTION:
POSITION:
THE OWNER
THE PLANS DIRECTED BY
LETTERING
BLACK FACED PLASTIC
INDICATE NORMALY OPEN OR NORMALLY
INDICATE SHUT-OFF, BALANCING, DRAIN ETC.
INDICATE CHILLED WATER,
HOT WATER, GAS ETC.
ANCHOR SECURELY
TO EQUIPMENT.
LAMINATE WITH ENGRAVED
INDICATE EXHAUST FAN,
PUMP, ETC. INDICATE
EQUIPMENT MARK AS SHOWN
3/16" MINIMUM LETTER HEIGHT
EQUIPMENT TAG
.
ATTACH AROUND VALVE HANDLE WITH CHAIN
STANDARD LETTERING
INDICATE GATE, BALL, CHECK ETC.
0.051" THICK BRASS TAG WITH
VALVE TAG
CLOSED OR AS MARKED.
INDICATE VALVE SIZE
3"
M
I
N
I
M
U
M
6" MINIMUM
1-
1
/
2
"
M
I
N
.
3"
LETTER HEIGHT
1/8" MINIMUM
NOTE:
NOTE:
1/2" ANCHOR BOLT
1/2" ANCHOR BOLT
WALL, SEE ARCH.
GALV. MESH SCREEN
FLANGE FOR DUCT CONNECTION OR
GALVANIZED STEEL SLEEVE ALL
AROUND. ANCHOR TO WALL
LOUVER
LOUVER FRAME
SLEEVE FOR DAMPER(S) (TYPICAL)
WALL, SEE ARCH.
AS REQUIRED TO SIZE INDICATED
TRANSITION FROM DISCHARGE END
SEE PLANS FOR SIZING
BRANCH DUCT TO DIFFUSERS,
ON PLANS.
VAV BOX, SEE PLANS FOR
SIZING AND LOCATION.
BELL TYPE FITTING
VAV BOX AS REQUIRED
TRANSITION TO INLET OF
ALTERNATE TAKE-OFF TYPE
MAIN SUPPLY DUCT
STRAIGHT DUCTWORK, PROVIDE MINIMUM
LENGTH OF 18" OR 1.5 TIMES INLET
DUCT DIAMETER, WHICH EVER IS GREATER.
CONTROLS ENCLOSURE,
VERIFY WHICH SIDE OF
BOX WITH DRAWINGS
ACOUSTICAL
NO LINE OF SIGHT THROUGH
CONSTRUCTED SO THERE IS
SOUND BOOT TO BE
THE SOUND BOOT.
NOTE:
1" INTERIOR
LINING, 1 lb.
DENSITY
W W
+
2"W
L
WALL
W
W
W+2"
LINE OF SIGHT
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
Mechanical
Details
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
SCALE: NONESCALE: NONESCALE: NONESCALE: NONEMH501MH501MH501MH501
ob`q^kdri^o=ar`q=cfqqfkdp=abq^fi1111
SCALE: NONESCALE: NONESCALE: NONESCALE: NONEMH501MH501MH501MH501
jbafrj=sbil`fqv=ar`q=cfqqfkdp=abq^fi2222
SCALE: NONESCALE: NONESCALE: NONESCALE: NONEMH501MH501MH501MH501
olrka=ar`q=e^kdbo=abq^fi3333
SCALE: NONESCALE: NONESCALE: NONESCALE: NONEMH501MH501MH501MH501
ar`q=pqo^m=e^kdbo=abq^fi4444
SCALE: NONESCALE: NONESCALE: NONESCALE: NONEMH501MH501MH501MH501
ls^i=ar`q=e^kdbo=abq^fi5555
SCALE: NONESCALE: NONESCALE: NONESCALE: NONEMH501MH501MH501MH501
ar`q=ifkbo=abq^fi6666
SCALE: NONESCALE: NONESCALE: NONESCALE: NONEMH501MH501MH501MH501
c^`qlov=j^ab=ar`q=abq^fi7777
SCALE: NONESCALE: NONESCALE: NONESCALE: NONEMH501MH501MH501MH501
plrka=qo^m=abq^fi8888
SCALE: NONESCALE: NONESCALE: NONESCALE: NONEMH501MH501MH501MH501
_o^k`e=ar`q=^ka=a^jmbo=abq^fi9999
SCALE: NONESCALE: NONESCALE: NONESCALE: NONEMH501MH501MH501MH501
ar`q=`lkkb`qflk=abq^fi10101010
SCALE: NONESCALE: NONESCALE: NONESCALE: NONEMH501MH501MH501MH501
cfob=L=pjlhb=a^jmbo=abq^fi11111111
SCALE: NONESCALE: NONESCALE: NONESCALE: NONEMH501MH501MH501MH501
ilt=mobpprob=ar`q=^``bpp=allo=abq^fi12121212
SCALE: NONESCALE: NONESCALE: NONESCALE: NONEMH501MH501MH501MH501
fabkqfcf`^qflk=q^d=abq^fi13131313
SCALE: NONESCALE: NONESCALE: NONESCALE: NONEMH501MH501MH501MH501
ilrsbo=abq^fi14141414
SCALE: NONESCALE: NONESCALE: NONESCALE: NONEMH501MH501MH501MH501
s^s=_lu=abq^fi15151515
SCALE: NONESCALE: NONESCALE: NONESCALE: NONEMH501MH501MH501MH501
qo^kpcboLobqrok=^fo=plrka=_llq=abq^fi16161616
dbkbo^i=klqbp=clo=jb`e^kf`^i=`lkqolip
POWER
(E)120V
(E)AHU AREA "A"
ATC PANEL(S)
(E) CHILLER CH-1
CONTROL PANEL
POWER
(E) 208/60/3
(E)120V
POWER
(E) SNOW
MELTING
ATC PANEL
COMMUNICATION
TRUNK
RS-485
CENTRAL
BASEMENT
120V POWER
LEVEL 00
PROCESSOR
120V
POWERREPEATER
EXTEND TO CAMPUS
ETHERNET. (VERIFY
EXACT LOCATION OF
ETHERNET CONNECTION
WITH OWNER)
ETHERNET
BY DIV. 26
TRANSFORMER
R
C R
120/60/1 POWER
FUSE
SURGE
OUTLET
SUPPRESSOR
ON/OFF
SWITCH
H
NH
CONTROLLERS,
DIRECT DIGITAL
FOR QUANTITY
FIRE ALARM CONTACT
SEE DRAWINGS
LIGHT
PILOT
DDC
R C
DDC
IN
DDCDDC
DDCDDC
OUT
CT
QUANTITY AS REQUIRED
COMMUNICATIONS CABLING120/60/1 POWER
TRUNK
COMMUNICATION
DDC CONTROLLER
CT
H
R
FIRE ALARM CONTACT
TRANSFORMER,
QUANTITY AS
REQUIRED
BY DIV. 26
N
PRESSURE SWITCHES, ELECTRIC OPERATED VALVES, ETC. ARE THE RESPONSIBILITY OF DIVISION 23.
ATC PANELS, SENSORS, ETC, AS INDICATED ON THE PLANS ALL IN ACCORDANCE WITH DIVISION 26.
ANY QUESTION OF RESPONSIBILITY SHALL BE CLARIFIED BY THE GENERAL CONTRACTOR
THE CONTROLS CONTRACTOR SHALL PROVIDE SHOP DRAWINGS FOR CONTROL SYSTEMS CIRCUITS.
THE CONTROLS CONTRACTOR SHALL ROUTE ALL CONDUIT FOR MECHANICAL CONTROLS, PULL WIRING REQUIRED
FOR MECHANICAL CONTROLS THROUGH THE CONDUITS AND MAKE CONNECTIONS TO MECHANICAL EQUIPMENT,
THROUGH THE CONTROL DEVICE AND BACK TO THE JUNCTION BOX.
CONTROLS CONTRACTOR SHALL INTERRUPT THE CIRCUIT IN THE MECHANICAL EQUIPMENT JUNCTION BOX, WIRE
THE ELECTRICIAN SHALL RUN AND CONNECT ALL WIRING AND DEVICES 120 VOLTS AND ABOVE WHICH POWER
AUXILIARY RELAYS, LOW VOLTAGE TRANSFORMERS, CONTROL PANEL SWITCHES AND DEVICES, THERMOSTATS,
ALL WIRING SHALL TERMINATE AT LABELED TERMINAL STRIPS.10.
9.
8.
CONTROLS CONTRACTOR (DIV 23).
PRODUCTS AND PRACTICES SHALL BE SIMILAR FOR ALL INSTALLATIONS.
RESPONSIBILITY OF DIVISION 26.
BREAKERS AND DISCONNECTS, AUXILIARY CONTACTS, STANDARD PILOT LIGHTS AND MAGNETIC STARTERS ARE THE
GENERAL CONTRACT. OF SPECIFIC CONCERN ARE THE CONTROL SYSTEMS RELATED TO MECHANICAL EQUIPMENT.
RESPONSIBILITY FOR THE CONTROL WORK IS DIVIDED BETWEEN THE PROJECT ELECTRICIAN (DIV. 26) AND A SPECIALTY
ALL ELECTRICAL INSTALLATION, BE IT POWER DISTRIBUTION OR SPECIAL SYSTEMS, IS INCLUDED IN THE SCOPE OF THE
THE ELECTRICIAN SHALL PROVIDE ALL POWER TO AND THROUGHOUT THE BUILDING, TO INCLUDE MOTOR CONTROL
ALL ELECTRICAL WORK SHALL BE IN ACCORDANCE WITH DIVISION 26 AND TO THE FULLEST EXTENT POSSIBLE,
CENTERS, BREAKER PANELS AND ALL OTHER SYSTEMS DESIGNATED TO THE ELECTRICIANS.
MOTORS AND OTHER MECHANICAL DEVICES. WHERE CONTROL DEVICES ARE LOCATED IN POWER CIRCUIT, THE
7.
6.
5.
4.
3.
2.
1.
ALLOW FOR ACCOMMODATION OF CHW DIFFERENTIAL PRESSURE SENSOR WIRING FROM THE MANWARING CENTER11.
AND HART BUILDING BACK TO THE NEW CENTRAL CHILLER PLANT WHERE ROUTING OF EACH PASSES THROUGH THE
AUDITORIUM SPACE OR SITE.
AREA "A"
LOW VOLTAGE
CONTROL WIRING
FROM LVTP
COMMUNICATION
TRUNK
RS-485
COMMUNICATION
TRUNK
RS-485
BY DIV. 26
120V POWER
LEVEL 01
ETHERNET
REPEATER
AREA "B"
LOW VOLTAGE
CONTROL WIRING
FROM LVTP
COMMUNICATION
TRUNK
RS-485
COMMUNICATION
TRUNK
RS-485
COMMUNICATION
TRUNK
RS-485
COMMUNICATION
TRUNK
RS-485
REPEATER
LEVEL 02
BY DIV. 26
120V POWER
ETHERNET
LOW VOLTAGE
CONTROL WIRING
FROM LVTP
COMMUNICATION
TRUNK
RS-485
COMMUNICATION
TRUNK
RS-485
COMMUNICATION
TRUNK
RS-485
COMMUNICATION
TRUNK
RS-485
BY DIV. 26
120V POWER
LEVEL 03
ETHERNET
LOW VOLTAGE
CONTROL WIRING
FROM LVTP
COMMUNICATION
TRUNK
RS-485
COMMUNICATION
TRUNK
RS-485
COMMUNICATION
TRUNK
RS-485
COMMUNICATION
TRUNK
RS-485
ROOF
REPEATER
LEVEL 01
LEVEL 02
ROOF
BY DIV. 26
120V POWER
ETHERNET
REPEATER
BY DIV. 26
120V POWER
LOW VOLTAGE
CONTROL WIRING
FROM LVTP
COMMUNICATION
TRUNK
RS-485
COMMUNICATION
TRUNK
RS-485
COMMUNICATION
TRUNK
RS-485
COMMUNICATION
TRUNK
RS-485
LOW VOLTAGE
CONTROL WIRING
FROM LVTP
COMMUNICATION
TRUNK
RS-485
POWER BY
DIV. 26
120V
120V
POWER
TYP.
LOW VOLTAGE
CONTROL WIRING
FROM LVTP
COMMUNICATION
TRUNK
RS-485
COMMUNICATION
TRUNK
RS-485
AREA "B"AREA "A"
VAVR
CONTROLLER
NEW HW HEAT EXCH.
CONTROL PANEL
HWS & CHWS
SYSTEMS
ATC PANEL
VAVR
CONTROLLER
VAVR
CONTROLLER
EXTEND TO
ADDITIONAL
CONTROLLERS AS
REQUIRED
LEVEL 01
CENTRAL
PROCESSOR
(LOCATE IN
ELEC. ROOM)
VAVR
CONTROLLER
VAVR
CONTROLLER
VAVR
CONTROLLER
VAVR
CONTROLLER
VAVR
CONTROLLER
CH-X
CONTROLLER
(WHERE
REQUIRED)
EXTEND TO
ADDITIONAL
CONTROLLERS AS
REQUIRED
LEVEL 02
CENTRAL
PROCESSOR
(LOCATE IN
ELEC. ROOM)
VAVR
CONTROLLER
VAVR
CONTROLLER
VAVR
CONTROLLER
VAVR
CONTROLLER
FCU-1
CONTROLLER
LEVEL 03
CENTRAL
PROCESSOR
(LOCATE IN
ELEC. ROOM)
VAVR
CONTROLLER
VAVR
CONTROLLER
VAVR
CONTROLLER
VAVR
CONTROLLER
VAVR
CONTROLLER
EXTEND TO
ADDITIONAL
CONTROLLERS AS
REQUIRED
LEVEL 01
CENTRAL
PROCESSOR
(LOCATE IN
ELEC. ROOM)
LEVEL 02
CENTRAL
PROCESSOR
(LOCATE IN
ELEC. ROOM)
VAVR
CONTROLLER
VAVR
CONTROLLER
VAVR
CONTROLLER
VAVR
CONTROLLER
EXTEND TO
ADDITIONAL
CONTROLLERS AS
REQUIRED
VAVR
CONTROLLER
VAVR
CONTROLLER
VAVR
CONTROLLER
VAVR
CONTROLLER
(E)AHU AREA "B"
ATC PANEL(S)
HWS & CHWS
SYSTEMS
ATC PANEL
VAVR
CONTROLLER
VAVR
CONTROLLER
VAVR
CONTROLLER
CH-X
CONTROLLER
(WHERE
REQUIRED)
EXTEND TO
ADDITIONAL
CONTROLLERS AS
REQUIRED
LOW VOLTAGE
CONTROL WIRING
FROM LVTP
LOW VOLTAGE
CONTROL WIRING
FROM LVTP
H-1 HUMIDIFIER
CONTROL PANEL
EXTEND TO
ADDITIONAL
CONTROLLERS AS
REQUIRED
460 / 60 / 3
LOW VOLTAGE
CONTROL WIRING
FROM LVTP
LOW VOLTAGE
CONTROL WIRING
FROM LVTP
(LOCATE IN
ELEC. ROOM)
120V POWER
BY DIV. 26.
(TYP.)
POWER BY DIV. 26
COMMUNICATION
TRUNK
RS-485
OUTSIDE WALL
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
Mechanical
Control
Diagrams
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
SCALE: NONESCALE: NONESCALE: NONESCALE: NONEMI601MI601MI601MI601
_rfiafkd=es^`=`lkqoli=pvpqbj=lkbJifkb=af^do^j1111
S
S
S
S
S
S
S
pmifq=pvpqbj=^fo=`lkafqflkfkd=rkfq=`lkqoli=af^do^j
DM
cfobLpjlhb=a^jmbo=`lkqoli=af^do^j
bibs^qlo=pjlhb=sbkq=`lkqoli=af^do^j
qvmf`^i=a^jmbo=jlqlo=af^do^j
qvmf`^i=`lkqoli=s^isb=af^do^j
pbkplo=jlrkqfkd=abq^fi
`^_fkbq=eb^qbo=`lkqoli=af^do^j
c^k=`lfi=rkfq=auc`rJN=`lkqoli=af^do^j
s^s=`llifkd=lkiv=`lkqoli=af^do^j
s^s=`llifkd=tfqe
qbojfk^i=obeb^q=`lkqoli=af^do^j
R
R
R G R R
1
CONTACT
(E)FREEZESTAT
DIV. 23
SMOKE VENT BY
NORMALLY OPEN TO FIRE ALARM CONTROL
CONTROL POWER
PANEL BY DIV. 26
ELECTRICAL
BY DIV. 23
DAMPER MOTOR
BY DIV. 26
DM
DIV. 26
RELAY BY
R
MD
15
MD
16
NORMALLY OPEN
DIV. 23
SMOKE VENT BY
ELECTRICAL DAMPER
MOTOR DIV. 23
NORMALLY CLOSED
FUSIBLE LINK
120 VOLT FIRE ALARM
POWER BY DIV. 26(WHERE APPLICABLE)
2 POSITION OR
DAMPER MOTOR DM
CONTROL SIGNAL
FROM DDC PANEL
MODULATING AS SHOWN
2 POSITION OR MODULATING AS SHOWN
CONTROL VALVE
2 OR 3-WAY AS SHOWN
FROM DDC PANEL
CONTROL SIGNAL
CV-XX
FLOOR
UP WITH LIGHT SWITCH
SENSOR SHALL LINE
CONCRETE BLOCK OR STUD WALL
STUD SPACE FIELD COORDINATE WITH
CONCRETE WALL OR CONCEALED WITHIN
CONTROL CONDUIT EMBEDDED WITHIN
ELBOW
RADIUS ELBOW
NOMINAL 2"x4"x2-1/2" DEEP
ROOM SENSOR OR SWITCH
48"
„
J-BOX
NOTE:
WALL CONSTRUCTION
90° SHORT
DI AOWIRING TO
TRUNK
MAIN COMMUNICATION
TYPICAL FOR ALL CABINET HEATERS
IN LVTP
TRANSFORMER
WALL SENSOR
AI
DO
DDC CONTROLLER
CT
UNIT MOUNTED AQUASTAT
SWITCH
120/60/1 POWER
SEE DIV. 26
HIGH/MED/LOW/OFF
FAN MOTOR
BY DIV. 26
120V/60/1 POWER
R
HWS
HWR
(SEE PLANS FOR EXACT
CONFIGURATION)
SERVING CABINET HEATERS FOR MAX.
5 FT. P.D. WHEN FULLY OPEN
SIZE ALL 2-WAY HW CONTROL VALVES
HCV-CHX
24 VOLT WIRING
TO TRANSFORMER
IN LVTP
WALL SENSOR
CONTROLLER
(TYPICAL)
DDC
NO
CONTROL VALVE
HWS
HWR
TEMPERATURE
VELOCITY SENSOR
TEMPERATURE/
MAIN COMMUNICATION TRUNK
VS
DM
CT
DAMPER MOTOR
AIR SENSOR
DISCHARGE
AI AI
AI AO
AO
SEE PLANS.
2 OR 3-WAY
DAMPER MOTOR
MAIN COMMUNICATION TRUNK
A VAV COOLING OR
24 VOLT WIRING
TO TRANSFORMER
IN LVTP
AOAI
AI
WALL TEMPERATURE
SENSOR (TYPICAL)
DDC CONTROLLER
DM
VELOCITY SENSOR
TEMPERATURE/
VS
CT
HEATING TERMINAL UNIT
(APPLICABLE WHERE ONLY
SERVES ONE ZONE)
AO
FROM LVTP
FILTER
HEATING COIL
DX COOLING COIL
HWS
HWR
B
DXFHCV-1
R.A.
A
S B
GAUGE
FILTER
DWYER
SCALE: NONE
2
E-501
SCALE: NONE
1
E-501
SCALE: NONE
3
E-501
SCALE: NONE
4
E-501
SCALE: NONE
5
E-501
SCALE: NONE
6
E-501
SCALE: NONE
9
E-501
SCALE: NONE
8
E-501
SCALE: NONE
7
E-501
NOTE: TYPICAL FOR
ELEVATOR SHAFTS
H C
H
H
AF
HI
1
S.A.
H
H.D.
O.A.
R1-1
MD
1
S
L
D
C
ROOF
HUMIDIFIER
S
H
1
460/60/3 POWER
SEE DIV. 26
TO R.A. DUCT
RH SENSOR
PROVIDE BACNET INTERFACE TO
HUMIDIFIER CONTROL PANEL(S).
SEE ONE-LINE DIAGRAM ON
DRAWING MI601.
H F
ARCHIVE 228D
H H
VAULT 228E
SPACE RELATIVE HUMIDITY
S E
ARCHIVE 228D
S G
VAULT 228E
SPACE TEMPERATURE
B
A
AI
24 VOLTDI
MAIN COMMUNICATION
TRUNK CABLE
AO B
DO
CT
A
D DI
C AI DO
C
F AI
E AI
H AI
G AI
EXTEND TO
HUMIDIFIER H-1
AIR PROVING SWITCH
HUMIDITY HIGH LIMIT
HUMIDITY SENSOR
FOR MODULATING
CONTROL
HUMIDIFIER INJECTOR
FAN COIL UNIT
SUPPLY FAN
EXTEND TO
HUMIDIFIER H-1
DAMPER OPENS
FROM AUXILIARY
RELAY ON FCU-1
SUPPLY FAN
H-O-A SWITCH.
OUTSIDE AIR
DAMPER
CONDENSING UNIT
REFRIGERANT PIPING
TO AIR PROVING SWITCH
TO HUMIDITY HIGH LIMIT
SWITCH
TO S.A. DUCT RH SENSOR
FAN COIL UNIT DXFCU-1 STATUS C.T.
FAN COIL UNIT DXFCU-1 DISCHARGE TEMPERATURE
FAN COIL UNIT DXFCU-1 DISCHARGE RH
DXFCU-1 CONDENSING UNIT STATUS ALARM
ARCHIVE 228D SPACE TEMPERATURE
ARCHIVE 228D SPACE REL. HUMIDITY
VAULT 228E SPACE TEMPERATURE
VAULT 228E SPACE REL. HUMIDITY
START / STOP FAN COIL UNIT DXFCU-1
MODULATE HEATING WATER VALVE DXFHCV-1
START / STOP DXFCU-1 CONDENSING UNIT
DIRECT DIGITAL CONTROLLER
INSTALL IN ATC PANEL
LOCATED NEAR THE
FAN COIL UNIT
A
208/60/3
DISCONNECT
SEE DIV. 26
POWER
FAULT
EXTERNAL
ENABLE
VFD
OFF
AUTO
ON
HAND
POWER
FAULT
VFD
FAN COIL
UNIT
CS
A
BUILT-IN VFD
A
R1-1
OUTSIDE
DAMPER RELAY
CONTROL DIAGRAM FOR FAN COIL UNITS FCU-1 THRU FCU-3 SIMILAR.
WITH THE ADDITION OF ANOTHER CONTROL VALVE TO CONTROL THE
COOLING COIL AND ADDITIONAL AQUASTAT IN THE CHWS LINE.
DXFCU
1
DXFCU
1
DXFCU
1
DDC CONTROLLER AND
DDC WIRING TO LOCAL
PROVIDE LOW VOLTAGE
DIGITAL INPUT
CONNECT INTO SPARE
INDOOR
UNIT
ALARM OUTPUT
REMOTE STATUS
CONTRACTOR
INSTALLED BY HVAC CONTROLS
FURNISHED BY UNIT MANUFACTURER
THERMOSTAT AND CONTROLLER,
WALL MOUNTED PROGRAMMABLE
CONTROL WIRING BY DIV. 23
FOR HARD WIRED CONTROLLERS.
DISCONNECT
ROOF
UNIT
OUTDOOR
120/60/1
POWER BY
DIV. 26
DISCONNECT
SIZE OF WIRES REQUIRED WITH UNIT
IN CONDUIT. VERIFY EXACT NUMBER AND
PROVIDE LOW VOLTAGE CONTROL WIRING
MANUFACTURER
208/60/1
DIV. 26
POWER BY
C17
SCU
-
WALL
SAC
-
C16
SPACE TEMPERATURE
BDF ROOM 040
TYP. FOR SAC-040/SCU-040, SAC-245A/SCU-245A, SAC-245B/SCU-245B, SAC-280A/SCU-280A & SAC-280B/SCU-280B
CONTROL WIRING BY
DIV. 23. DIV. 26 TO
PROVIDE CONDUIT.
CONTROL WIRING BY
DIV. 23. DIV. 26 TO
PROVIDE CONDUIT.
SAC-040 / SCU-040
D16
SPACE TEMPERATURE
IT ROOM 245
E15
SPACE TEMPERATURE
TR/COMM ROOM 280
ALARM OUTPUT
REMOTE STATUSD17
SAC-245A / SCU-245A
ALARM OUTPUT
REMOTE STATUSD18
SAC-245B / SCU-245B
ALARM OUTPUT
REMOTE STATUSE16
SAC-280A / SCU-280A
ALARM OUTPUT
REMOTE STATUSE17
SAC-280B / SCU-280B
REFERENCE DRAWINGS MI605,
MI606 AND MI607 FOR CONTROL
POINT REFERENCES.
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
Mechanical
Control
Diagrams
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
SD HDS
HDS AQ
FZ
LDS
DP
DM
DM
DM
DP
DP
DP
DP
R
^ob^=?^?=EbF^fo=e^kaifkd=pvpqbj=obsfpba=`lkqoli=af^do^j
ao^tfkd=klqbp
dbkbo^i=klqbp
ollcqlm=bue^rpq=c^kp=`lkqoli=af^do^j
FAULT
(E)START / STOP
CONTACT
POWER
ON ENABLE
VFD EXTERNALBYPASS
ON
VFD
FAULT
(E)RRF-1A VFD-2
(E)INTERLOCK
R
RELAYS
FAULT
CONTACT
POWER
ON ENABLE
VFD EXTERNALBYPASS
ON
VFD
FAULT
HAND
OFF
(E)RRF-1A VFD-1
R
VFD FAULT ALARM
(E)CONTACT CLOSURE
(E)RETURN / RELIEF
FAN WALL RRF-1A
(E)RETURN / RELIEF
FAN WALL RFF-1A
(E)FAN SHUTOFF FROM
BLDG. FIRE ALARM
(E)SRI-4
(E)INTERLOCK
RELAYS
(E)FAN SHUTOFF FROM
BLDG. FIRE ALARM
(E)SRI-3
(E)START / STOP
CONTACT
HAND
OFF
(E)SF-1A VFD-2
POWER
(E)208/60/3
(E)DISCONNECT
(E)INTERLOCK
RELAYS
VFD FAULT ALARM
(E)CONTACT CLOSURE
FAULT
CONTACT
POWER
ON ENABLE
VFD EXTERNALBYPASS
ON
VFD
FAULT
(E)SF-1A VFD-1
R
VFD FAULT ALARM
(E)CONTACT CLOSURE
(E)SUPPLY FAN
WALL SF-1A
(E)DISCONNECT
(E)SUPPLY FAN
WALL SF-1A
(E)FAN SHUTOFF FROM
BLDG. FIRE ALARM
(E)SRI-2
(E)INTERLOCK
RELAYS
(E)FAN SHUTOFF FROM
BLDG. FIRE ALARM
(E)SRI-1
FAULT
(E)START / STOP
CONTACT
POWER
ON ENABLE
VFD EXTERNALBYPASS
ON
VFD
FAULT
(E)CHWP-6 VFD
R
R
FAULT
CONTACT
POWER
ON ENABLE
VFD EXTERNALBYPASS
ON
VFD
FAULT
(E)CHWP-5 VFD
R
TO (E)CHILLED WATER
PUMP CHWP-6
(E)START / STOP
TO (E)CHILLED WATER
PUMP CHWP-5
A13A12
R G R G R
HAND
OFF
AUTO
VFD
BYPASS
A7
POWER
(E)208/60/3
(E)DISCONNECT
R
R
VFD FAULT ALARM
(E)CONTACT CLOSURE
R G R G R
AUTO
VFD
BYPASS
A5
R
(E)START / STOP
POWER
(E)208/60/3
(E)DISCONNECT
R
FAULT
POWER
R
ON
G
ENABLE
VFD EXTERNALBYPASS
R G
ON
VFD
FAULT
R
AUTO
VFD
BYPASS
A3
R
R
R
R G R G R
HAND
OFF
AUTO
VFD
BYPASS
A1
R
(E)START / STOP
POWER
(E)208/60/3
R
SR
SR1-1
(E)SF-1A
(E)SAFETIES RELAY
(E)LOW DUCT STATIC
(E)FREEZE STAT
SAFETIES CIRCUIT
(E)RA HIGH DUCT STATIC
(E)SA HIGH DUCT STATIC
SR1-2 SR1-3 SR1-4
(E)SAFETY RELAY CONTACTS
(E)SUPPLY DUCT
(E)CHWR
(E)CHWS
(E)HWR
(E)HWS
(E)CHWS
(E)RETURN /
RELIEF FAN
(E)SUPPLY
FAN WALL
(E)COOLING COIL
(E)HEATING COIL
(E)FILTER SECTION
(E)RETURN
AIR DAMPER
(E)OUTSIDE
AIR DAMPER
(E)RELIEF
DAMPER
(BEYOND)
R G R G R
HAND
OFF
AUTO
VFD
BYPASS
B9
POWER
(E)208/60/3
(E)DISCONNECT
(E)INTERLOCK RRELAYS
VFD FAULT ALARM
(E)CONTACT CLOSURE
R G R G R
HAND
OFF
AUTO
VFD
BYPASS
A12
R
R
VFD FAULT ALARM
(E)CONTACT CLOSURE
POWER
(E)208/60/3
(E)DISCONNECT
(E)INTERLOCK
RELAYS
DPDPDP
S
R RG G R
R
R
R G R R
A19A20
(E)COOLING COIL
CIRCULATING PUMP
CHWP-5
(E)COOLING COIL
CIRCULATING PUMP
CHWP-6
SCALE: NONE
TRANSFORMER
A2
IN ATC
A1
DI
24 VOLTAI
POWER
MAIN COMMUNICATION
TRUNK CABLE
AO A2
DO
CT
A1
-
DI
AI
DO
AO
-
-
-
A4 DI
A3 AI
AO A4
DO A3
AO A6
DO A5
AO A8
DO A7
AO A10
AO A9
DO A12
AO A11
DO A14
DO A13
AO A16
AO A15
A6 DI
A5 AI
A8 DI
A7 DI
A10 DI
A9 DI
A12 DI
A11 DI
A14 DI
A13 DI
A16
AI
A15
DIA18
AI
A17
AIA20
DI
A19
AIA22
AI
A21
AIA24
AI
A23
DIA26
DI
A25
DIA28
DI
A27
DIA30
DI
A29
DIA32
DI
A31
DIA34
DI
A33
DIA36
AI
A35
DIA38
AI
A37
AIA40
AI
A39
DIA42
AI
A41
AIA44
DI
A43
DIA46
DI
A45
DI
A47
AI
A7
A28
A8
A27 A5
A26
A6
A25
A3
A4
A4
A3 A1
A2
A2
A1
INPUT FROM (E)SF-1A VFD-1
ALARM FROM (E)SF-1A VFD-1
INPUT FROM (E)SF-1A VFD-2
ALARM FROM (E)SF-1A VFD-2
OUTSIDE AIR TEMPERATURE
AHU-1A FILTER STATUS D.P.
(E)SF-1A FAN WALL, FAN NO. 1 STATUS C.S.
(E)SF-1A FAN WALL, FAN NO. 2 STATUS C.S.
(E)SF-1A FAN WALL, FAN NO. 3 STATUS C.S.
(E)SF-1A FAN WALL, FAN NO. 4 STATUS C.S.
(E)SF-1A FAN WALL, FAN NO. 5 STATUS C.S.
(E)SF-1A FAN WALL, FAN NO. 6 STATUS C.S.
(E)SF-1A FAN WALL, FAN NO. 7 STATUS C.S.
(E)SF-1A FAN WALL, FAN NO. 8 STATUS C.S.
(E)AHU-1A HIGH DUCT STATIC
(E)AHU-1A SUPPLY AIR DISCHARGE TEMPERATURE
(E)AHU-1A CHWR TEMPERATURE
(E)AHU-1A S.A. DUCT STATIC PRESSURE
(E)AHU-1A MIXED AIR TEMPERATURE
(E)AHU-1A LOW DUCT STATIC
(E)AHU-1A OUTSIDE AIR FLOW
INPUT FROM (E)RRF-1A VFD-1
ALARM FROM (E)RRF-1A VFD-3
INPUT FROM (E)RRF-1A VFD-2
ALARM FROM (E)RRF-1A VFD-4
(E)RRF-1A FAN WALL, FAN NO. 1 STATUS C.S.
(E)RRF-1A FAN WALL, FAN NO. 2 STATUS C.S.
(E)RRF-1A FAN WALL, FAN NO. 3 STATUS C.S.
(E)RRF-1A FAN WALL, FAN NO. 4 STATUS C.S.
(E)RRF-1A FAN WALL, FAN NO. 5 STATUS C.S.
(E)RRF-1A FAN WALL, FAN NO. 6 STATUS C.S.
(E)RRF-1A FAN WALL, FAN NO. 7 STATUS C.S.
(E)RRF-1A FAN WALL, FAN NO. 8 STATUS C.S.
(E)RRF-1A FAN WALL, FAN NO. 9 STATUS C.S.
(E)RRF-1A FAN WALL, FAN NO. 10 STATUS C.S.
(E)RRF-1A R.A. TEMPERATURE
START / STOP (E)SF-1A VFD-1
OUTPUT TO (E)SF-1A VFD-1 - SPEED
START / STOP (E)SF-1A VFD-2
OUTPUT TO (E)SF-1A VFD-2 - SPEED
MODULATE (E)OAD-1A
MODULATE (E)RAD-1A
START / STOP (E)COOLING COIL CIRC. PUMP CHWP-5 VFD
START / STOP (E)COOLING COIL CIRC. PUMP CHWP-6 VFD
START / STOP HEATING COIL CIRC. PUMP HWP-9, VFD-9
MODULATE HEATING COIL BYPASS CONTROL VALVE BCV-1
OUTPUT TO (E) CHWP-5 VFD
SPARE ANALOG INPUT (4 SUCH)
SPARE DIGITAL INPUT (6 SUCH)
SPARE ANALOG OUTPUT (2 SUCH)
SPARE DIGITAL OUTPUT (3 SUCH)
DIRECT DIGITAL CONTROLLER(S)
QUANTITY AS REQUIRED
INSTALL IN ATC PANEL(S)
LOCATED NEAR (E)AREA "A"
(E)RRF-1A CO LEVEL
(E)RRF-1A VOC LEVEL
(E)RRF-1A HIGH DUCT STATIC
(E)RRF-1A DUCT S.P.
AREA "A" LEVEL 01 BUILDING STATIC
AREA "A" LEVEL 02 BUILDING STATIC
(E)COOLING COIL CIRC. PUMP STATUS D.P.
(E)COOLING COIL CIRC. PUMP STATUS D.P.
HEATING COIL CIRC. PUMP STATUS D.P.
SAFETIES RELAY SR1-5 STATUS
INPUT FROM (E) CHWP-5 VFD
AIR HANDLING UNIT
SR1-5
A49
A21
LOCATE IMMEDIATELY UPSTREAM FROM THE
MOST AERODYNAMICALLY REMOTE TERMINAL
(E)AREA "A" AIR HANDLING UNIT SA DUCT STATIC PRESSURE
BOX FROM THE AIR HANDLING UNIT. FIELD VERIFY
DWYER 602-0
DWYER 602-2
OUTSIDE
A45
INSIDE
LEVEL 02
DWYER 602-2
OUTSIDE
A44
INSIDE
A14
A48A47A46
A5
OUTSIDE AIR
TEMPERATURE
PROVIDE
SOLAR / WIND
SHIELD
LEVEL 01
WEST BUILDING STATIC
LOCATE SENSORS AS
DIRECTED IN FIELD ON
LEVEL INDICATED.
A18
S
A19
A33
A38
A32
A37
A31
A36
A30
A35
A29
A34
C.S.
A5A7
A42
DWYER 602-0
A43
S
A39 A40 A41
C.S.
A1
A3
A16 A17
A13 A14
A15
A12A11
A9 A10A8A7
S
A20
S
A22 A23
A6
A10
A9
A24
AFM
1
A11
(E)AREA "A" AIR HANDLING SYSTEM
A48
A50
A49
(E)SF-1A FAN WALL, FAN NO. 9 STATUS C.S.
(E)SF-1A FAN WALL, FAN NO. 10 STATUS C.S.
(E)SF-1A FAN WALL, FAN NO. 11 STATUS C.S.
DI
DI
DI
2
START / STOP (E)RRF-1A VFD-1
OUTPUT TO (E)RRF-1A VFD-3 - SPEED
START / STOP (E)RRF-1A VFD-2
OUTPUT TO (E)RRF-1A VFD-4 - SPEED
MODULATE (E)RELIEF DAMPER RED-1A
(E) ENABLE FROM RETURN / RELIEF
VAN VFD'S (TYPICAL OF 10 EACH)
(E) ENABLE FROM RETURN / RELIEF
VAN VFD'S (TYPICAL OF 11)
DIA51ALARM FROM (E) CHWP-5 VFD
AIINPUT FROM (E) CHWP-6 VFD A52
DIA53ALARM FROM (E) CHWP-6 VFD
AIINPUT FROM HWP-9, VFD-9 A54
DIA55ALARM FROM HWP-9, VFD-9
DIREF-1 STATUS C.S.A56
DIA57REF-2 STATUS C.S.
AO A18
AO A17 OUTPUT TO (E) CHWP-6 VFD
OUTPUT TO HWP-9, VFD-9
HEATING COIL
CIRCULATING PUMP
HWP
9
REFERENCE FLOW DIAGRAMS ON SHEETS
MP601 AND MP602 FOR EXACT PIPING
CONFIGURATION FOR CHW AND HW SYSTEMS.
A13
A53
A17
A52A12
A51
A16
A50
DISCONNECT
POWER
208/60/3
SEE DIV. 26
BYPASS
VFD
BYPASSVFDPOWER VFD
AUTO
HAND
INTERLOCK
RELAY
OFF
R
RA14 ON FAULTENABLE ON
START/STOP
CONTACT
VFD ALARM
HWP
9A14 WATER
HEATING
EXTERNAL
CONTACT CLOSURE
R
FAULT A54
A55
VFD-9
PUMP
A18
PROVIDE NEW
TEMPERATURE SENSOR
COORDINATE WITH MECHANICAL
CONTRACTOR TO PROVIDE NEW
THERMOWELL TO SERVE NEW
TEMPERATURE SENSOR
1 REPLACE EXISTING DAMPER ACTUATOR WITH NEW.
A.REMOVE ALL EXISTING CONTROLS SERVING AIR HANDLING
SYSTEM INCLUDING CONTROL PANELS, FIELD WIRING,
COMMUNICATION WIRING, SENSORS AND DAMPER ACTUATORS
INDICATED.
BCV-1
A15
PROVIDE NEW
DIFFERENTIAL
PRESSURE SWITCH
1
1
1
(E) PNEUMATIC
3-WAY VALVE
WITH THIRD LEG
CAPPED.
REMOVE PNEUMATIC TUBING
FROM CONTROL VALVE AND
LOCK IN THE WIDE OPEN POSITION
(E) CAPPED PIPE
PREVIOUSLY EXTENDING
TO 3-WAY VALVE
REF-3 STATUS C.S.A58 DI
START / STOP REF-2
START / STOP REF-3
DO A20
DO A19
DO A21
START / STOP REF-1
A19
460/60/3
DISCONNECT
SEE DIV. 26
POWER
FAULT
EXTERNAL
ENABLE
VFD
OFF
AUTO
ON
HAND
POWER
FAULT
VFD
CS
A56
REF
1
BUILT-IN VFD
ROOFTOP
EXHAUST
FANS
DAMPER RELAY
BLDG. FIRE ALARM
FAN SWITCH PANEL
BY DIV. 23
LOCATE IN LOCAL
ELECTRICAL ROOM
DM
REF
3
ROOFTOP
EXHAUST FAN
A21
DAMPER OPENS WHEN FAN
RUNS FROM AUXILIARY
CONTACT ON FAN MOTOR
JUNCTION
BOX
SEE DIV.
POWER
120/60/1
26
HH
0
A
A21
H
N
ROOFTOP
EXHAUST FAN
R
IN PANEL FACE
HAND-OFF-AUTO
PILOT LIGHT
A21
REF
3A58
C.S.
*
*
WIRING BETWEEN J-BOX
AND ATC BY DIV. 23.
DIV. 26 SHALL PROVIDE
CONDUIT.
CONTROL DAMPER WIRING
IN CONDUIT PROVIDED BY
DIV. 26. CONNECTED BY
DIV. 23.
EXHAUST FANS
ROOFTOPREF
2
A19
DM
DAMPER OPENS WHEN FAN
RUNS FROM AUXILIARY
CONTACT ON FAN MOTOR VFD.
SCALE: NONE
REF
1
A20 JUNCTION
BOX
A57
A20 REF
2
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
Mechanical
Control
Diagrams
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
DM
(E) RESTROOM AND STORAGE RM.
ROOFTOP EXHAUST FANS
(E) MOTORIZED DAMPER
POWER
(E) 120/60/1
(E) CONTROL DAMPER
WIRING IN CONDUIT
(E) RESTROOM AND STORAGE RM.
ROOFTOP EXHAUST FANS
DM
DM
DM
HDS
LDS DP
SDAQ
HDS SD
DPDP
DP
DP
R
R
^ob^=?_?=EbF^fo=e^kaifkd=pvpqbj=obsfpba=`lkqoli=af^do^j
ao^tfkd=klqbp
dbkbo^i=klqbp
ollcqlm=bue^rpq=c^kp=`lkqoli=af^do^j
FAULT
(E)START / STOP
CONTACT
POWER
ON ENABLE
VFD EXTERNALBYPASS
ON
VFD
FAULT
(E)CHWP-1 VFD
R
R
FAULT
CONTACT
POWER
ON ENABLE
VFD EXTERNALBYPASS
ON
VFD
FAULT
(E)CHWP-2 VFD
R
TO (E)CHILLED WATER
PUMP CHWP-1
(E)START / STOP
TO (E)CHILLED WATER
PUMP CHWP-2
FAULT
(E)START / STOP
CONTACT
POWER
ON ENABLE
VFD EXTERNALBYPASS
ON
VFD
FAULT
(E)RRF-1B VFD-2
(E)INTERLOCK
R
RELAYS
FAULT
CONTACT
POWER
ON ENABLE
VFD EXTERNALBYPASS
ON
VFD
FAULT
HAND
OFF
(E)RRF-1B VFD-1
R
VFD FAULT ALARM
(E)CONTACT CLOSURE
(E)RETURN / RELIEF
FAN WALL RRF-1B
(E)RETURN / RELIEF
FAN WALL RFF-1B
(E)FAN SHUTOFF FROM
BLDG. FIRE ALARM
(E)SRI-4
(E)INTERLOCK
RELAYS
(E)FAN SHUTOFF FROM
BLDG. FIRE ALARM
(E)SRI-3
(E)START / STOP
CONTACT
HAND
OFF
(E)SF-1B VFD-2
POWER
(E)460/60/3
(E)DISCONNECT
(E)INTERLOCK
RELAYS
VFD FAULT ALARM
(E)CONTACT CLOSURE
FAULT
CONTACT
POWER
ON ENABLE
VFD EXTERNALBYPASS
ON
VFD
FAULT
(E)SF-1B VFD-1
R
VFD FAULT ALARM
(E)CONTACT CLOSURE
(E)SUPPLY FAN
WALL SF-1B
(E)DISCONNECT
(E)SUPPLY FAN
WALL SF-1B
(E)FAN SHUTOFF FROM
BLDG. FIRE ALARM
(E)SRI-2
(E)INTERLOCK
RELAYS
(E)FAN SHUTOFF FROM
BLDG. FIRE ALARM
(E)SRI-1
ELEV.
EQUIP.
E152A
B11B9
R G R G R
HAND
OFF
AUTO
VFD
BYPASS
B9
POWER
(E)460/60/3
(E)DISCONNECT
(E)INTERLOCK RRELAYS
VFD FAULT ALARM
(E)CONTACT CLOSURE
R G R G R
HAND
OFF
AUTO
VFD
BYPASS
B11
R
R
VFD FAULT ALARM
(E)CONTACT CLOSURE
POWER
(E)460/60/3
(E)DISCONNECT
(E)INTERLOCK
RELAYS
R G R G R
HAND
OFF
AUTO
VFD
BYPASS
B7
POWER
(E)460/60/3
(E)DISCONNECT
R
R
VFD FAULT ALARM
(E)CONTACT CLOSURE
R G R G R
AUTO
VFD
BYPASS
B5
R
(E)START / STOP
POWER
(E)460/60/3
(E)DISCONNECT
R
FAULT
POWER
R
ON
G
ENABLE
VFD EXTERNALBYPASS
R G
ON
VFD
FAULT
R
AUTO
VFD
BYPASS
B3
R
R
R
R G R G R
HAND
OFF
AUTO
VFD
BYPASS
B1
R
(E)START / STOP
POWER
(E)460/60/3
R
SR
SR1-1
(E)SF-1
(E)SAFETIES RELAY
(E)LOW DUCT STATIC
(E)FREEZE STAT
SAFETIES CIRCUIT
(E)RA HIGH DUCT STATIC
(E)SA HIGH DUCT STATIC
SR1-2 SR1-3 SR1-4
(E)SAFETY RELAY CONTACTS
DP DP
S
(E)CHILLED
WATER PUMP
CHWP-1
(E)CHILLED
WATER PUMP
CHWP-2
(E)4" CHWS FROM
CENTRAL PLANT
(E)4" CHWR TO
CENTRAL PLANT
(E)4" CHWS TO AHU-1B
COOLING COIL
FLOOR
(E)54"x144"
RELIEF AIR
(E)60"x96" OA DAMPER
(E)COOLING COIL
(E)FILTER SECTION
(E)36"x144" RETURN AIR DAMPER
FLOOR FLOOR
CEILING
TYPICAL
EXISTING
DUCTWORK
DUCTWORK
EXISTING
TYPICAL
(E)TYPICAL
LIGHT
(E)HEATING
COIL
(E)PLENUM CEILING
(E)54"x144" OA DUCT
FLOOR
(E)4" CHWR TO
CENTRAL PLANT
(E)4" CHWS FROM
LOCAL CHW PUMPS
(E)SF-1B
(E)RRF-1B
(E)STEAM CONTROL VALVE
(E)L.P. STEAM LINE
SERVING AHU-1B
HEATING COIL
DAMPER
(E)L.P. STEAM
LINE
(E)L.P. COND. LINE
(E)4" CHWR FROM AHU-1B
COOLING COIL
SCALE: NONE
TRANSFORMER
B2
IN ATC
B1
DI
24 VOLTAI
POWER
MAIN COMMUNICATION
TRUNK CABLE
AO B2
DO
CT
B1
-
DI
AI
DO
AO
-
-
-
B4 DI
B3 AI
AO B4
DO B3
AO B6
DO B5
AO B8
DO B7
AO B10
DO B9
AO B12
DO B11
AO B14
AO B13
AO B16
AO B15
B6 DI
B5 AI
B8 DI
B7 DI
B10 DI
B9 DI
B12 DI
B11 DI
B14 DI
B13 DI
B16 AI
B15 DI
B18 AI
B17 AI
B20 DI
B19 AI
B22 AI
B21 AI
B24 AI
B23 DI
B26 DI
B25 DI
B28 DI
B27 DI
B30 DI
B29 DI
B32 DI
B31 DI
B34 AI
B33 DI
B36 AI
B35 AI
B38 AI
B37 DI
B40 DI
B39 DI
B42 DI
B41 DI
B44 DI
B43 DI
B46 AI
B45 AI
B47 DI
2
B9
B38
B10
B37B11
B40
B12
B39
B42B41
B7
B25
B8
B24 B5
B23
B6
B22
B3
B4
B4
B3 B1
B2
B2
B1
C.S.
B1
C.S.
B1
C.S.
B30
B5
C.S.
B26
B5
B7
B7
B31
B27
B32
B28
B33
B29
B15
B14
B13
*
*
*
*
B7
B11
B3
B3
B8
B12
B9
B13
B10
B14
(E) ENABLE FROM
SUPPLY FAN VFD'S
INPUT FROM (E)SF-1B VFD-1
ALARM FROM (E)SF-1B VFD-1
INPUT FROM (E)SF-1B VFD-2
ALARM FROM (E)SF-1B VFD-2
OUTSIDE AIR TEMPERATURE
AHU-1B FILTER STATUS D.P.
(E)SF-1B FAN WALL, FAN NO. 1 STATUS C.S.
(E)SF-1B FAN WALL, FAN NO. 2 STATUS C.S.
(E)SF-1B FAN WALL, FAN NO. 3 STATUS C.S.
(E)SF-1B FAN WALL, FAN NO. 4 STATUS C.S.
(E)SF-1B FAN WALL, FAN NO. 5 STATUS C.S.
(E)SF-1B FAN WALL, FAN NO. 6 STATUS C.S.
(E)SF-1B FAN WALL, FAN NO. 7 STATUS C.S.
(E)SF-1B FAN WALL, FAN NO. 8 STATUS C.S.
(E)AHU-1B HIGH DUCT STATIC
(E)AHU-1B SUPPLY AIR DISCHARGE TEMPERATURE
(E)AHU-1B CHWR TEMPERATURE
(E)AHU-1B S.A. DUCT STATIC PRESSURE
(E)AHU-1B MIXED AIR TEMPERATURE
(E)AHU-1B LOW DUCT STATIC
(E)AHU-1B OUTSIDE AIR FLOW
INPUT FROM (E)RRF-1B VFD-1
ALARM FROM (E)RRF-1B
INPUT FROM (E)RRF-1B VFD-2
ALARM FROM (E)RRF-1B
(E)RRF-1B FAN WALL, FAN NO. 1 STATUS C.S.
(E)RRF-1B FAN WALL, FAN NO. 2 STATUS C.S.
(E)RRF-1B FAN WALL, FAN NO. 3 STATUS C.S.
(E)RRF-1B FAN WALL, FAN NO. 4 STATUS C.S.
(E)RRF-1B FAN WALL, FAN NO. 5 STATUS C.S.
(E)RRF-1B FAN WALL, FAN NO. 6 STATUS C.S.
(E)RRF-1B FAN WALL, FAN NO. 7 STATUS C.S.
(E)RRF-1B FAN WALL, FAN NO. 8 STATUS C.S.
(E)RRF-1B R.A. TEMPERATURE
(E)RRF-1B CO LEVEL
(E)RRF-1B VOC LEVEL
START / STOP (E)SF-1B VFD-1
OUTPUT TO (E)SF-1B VFD-1 - SPEED
START / STOP (E)SF-1B VFD-2
OUTPUT TO (E)SF-1B VFD-2 - SPEED
START / STOP (E)CHWP-1 VFD
OUTPUT TO (E)CHWP-1 VFD - SPEED
START / STOP (E)CHWP-2 VFD
OUTPUT TO (E)CHWP-2 VFD - SPEED
MODULATE (E)OAD-1B
SPARE ANALOG INPUT (4 SUCH)
SPARE DIGITAL INPUT (6 SUCH)
SPARE ANALOG OUTPUT (2 SUCH)
SPARE DIGITAL OUTPUT (3 SUCH)
DIRECT DIGITAL CONTROLLER(S)
QUANTITY AS REQUIRED
INSTALL IN ATC PANEL(S)
LOCATED NEAR (E)AREA "B"
* (E) ENABLE FROM RETURN / RELIEF
FAN VFD'S (TYPICAL OF 4 EACH)
MODULATE (E)RAD-1B
MODULATE (E)RELIEF DAMPER RED-1
MODULATE (E)STEAM CONTROL VALVE
INPUT FROM (E)CHWP-1 VFD
ALARM FROM (E)CHWP-1 VFD
INPUT FROM (E)CHWP-2 VFD
ALARM FROM (E)CHWP-2 VFD
(E)CHWP-1 STATUS D.P.
(E)CHWP-2 STATUS D.P.
SAFETIES RELAY SR1-5 STATUS
(E)RRF-1B HIGH DUCT STATIC
(E)RRF-1B DUCT S.P.
AREA "B" LEVEL 01 BUILDING STATIC
AREA "B" LEVEL 02 BUILDING STATIC
AIR HANDLING UNIT
SR1-5
B43
B18
LOCATE IMMEDIATELY UPSTREAM FROM THE
MOST AERODYNAMICALLY REMOTE TERMINAL
(E)AREA "B" AIR HANDLING UNIT SA DUCT STATIC PRESSURE
BOX FROM THE AIR HANDLING UNIT. FIELD VERIFY
B47
LEVEL 02
B46
LEVEL 01
B5
OUTSIDE AIR
TEMPERATURE
PROVIDE
SOLAR / WIND
SHIELD
EAST BUILDING STATIC
LOCATE SENSORS AS
DIRECTED IN FIELD ON
LEVEL INDICATED.
B16
S
B17
B44
B45
DWYER 602-0
B19
S
B21
B20
S
B16
S
B34 B35 B36
B15
START / STOP (E)RRF-1B VFD-1
OUTPUT TO (E)RRF-1B VFD-1 - SPEED
START / STOP (E)RRF-1B VFD-2
OUTPUT TO (E)RRF-1B VFD-2 - SPEED
REFERENCE FLOW DIAGRAMS ON SHEETS
MP601 AND MP602 FOR EXACT PIPING
CONFIGURATION FOR CHW AND HW SYSTEMS.
DWYER 602-0
1 REPLACE EXISTING DAMPER ACTUATOR WITH NEW.
A.REMOVE ALL EXISTING CONTROLS SERVING AIR HANDLING
SYSTEM INCLUDING CONTROL PANELS, FIELD WIRING,
COMMUNICATION WIRING, SENSORS AND DAMPER ACTUATORS
INDICATED.
DWYER 602-2
OUTSIDE INSIDE
DWYER 602-2
OUTSIDE INSIDE
PROVIDE NEW
DIFFERENTIAL
PRESSURE SWITCH
PROVIDE NEW
TEMPERATURE SENSOR
COORDINATE WITH MECHANICAL
CONTRACTOR TO PROVIDE NEW
THERMOWELL TO SERVE NEW
TEMPERATURE SENSOR
(E) PNEUMATIC
3-WAY VALVE
WITH THIRD LEG
CAPPED.
REMOVE PNEUMATIC TUBING
FROM CONTROL VALVE AND
LOCK IN THE WIDE OPEN POSITION
(E) CAPPED PIPE
PREVIOUSLY EXTENDING
TO 3-WAY VALVE
(TYP OF 4)
(E) ENABLE FROM
SUPPLY FAN VFD'S
(TYP OF 4)
1
1
START / STOP REF-4
DO B18
DO B17
DO B19
START / STOP (E) RESTROOM EXHAUST FAN
START / STOP (E) STORAGE RM. EXHAUST FAN
B48 DI
B50 DI
B49 DI
REF-4 STATUS C.S.
(E) RESTROOM EXHAUST FAN STATUS C.S.
(E) STORAGE RM. EXHAUST FAN STATUS C.S.
NEW FAN SWITCH PANEL
BY DIV. 23
LOCATE IN LOCAL
ELECTRICAL ROOM
B18
HH
0
A
B18
H
N R
IN PANEL FACE
HAND-OFF-AUTO
PILOT LIGHT
B18
B49
C.S.
WIRING BETWEEN J-BOX
AND ATC BY DIV. 23.
DIV. 26 SHALL PROVIDE
CONDUIT.
SCALE: NONE
FAN SWITCH PANEL
BY DIV. 23
LOCATE IN LOCAL
ELECTRICAL ROOM
DM
REF
4
ROOFTOP
EXHAUST FAN
B17
DAMPER OPENS WHEN FAN
RUNS FROM AUXILIARY
CONTACT ON FAN MOTOR
SEE DIV.
POWER
120/60/1
26
HH
0
A
B17
H
N
ROOFTOP
EXHAUST FAN
R
IN PANEL FACE
HAND-OFF-AUTO
PILOT LIGHT
B17
REF
4B48
C.S.
*
*
WIRING BETWEEN J-BOX
AND ATC BY DIV. 23.
DIV. 26 SHALL PROVIDE
CONDUIT.
CONTROL DAMPER WIRING
IN CONDUIT PROVIDED BY
DIV. 26. CONNECTED BY
DIV. 23.
B19
B19
B19
B50
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
Mechanical
Control
Diagrams
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
DP DP
R
TO (E)CHILLED WATER
PUMP CHWP-7
R
TO (E)CHILLED WATER
PUMP CHWP-7
buqboflo=f`b=_^kh=mfmfkd=cilt=af^do^j
^ob^=?^?=`efiiba=t^qbo=pvpqbj=obsfpba=`lkqoli=af^do^j
S
C5 C3
S
V
VD
V
VD
C3
C5
S S S
R G R G R
R
R
S
S
R G R G R
R
R
R
R
(E)ICE BANK MB-1
(E)6" CHWS/R(E)4" CHWR
(E)4" CHWS (E)6" CHWS
(E)4"(E)6"
(E)4"
(E)4" CHWS
(E)4" CHWS
(E)8"
(E)8" CHWR
(E)8" CHWS
(E)8" CHWR
(E)8"
(E)3/4"
(E)8" CHWS
(E)8"(E)8" CHWR
(E)8" CHWS(E)8"
(E)8"
(E)6"
(E)8" CHWR
(E)8" CHWS
(E)6" CHWR
(E)6" CHWS/R
(E)6" CHWS
(E)6" CHWS
(E)FLEX CONNECTION
(TYP.)
(E)ICE BANK MB-2 (E)ICE BANK MB-3 (E)ICE BANK MB-4 (E)ICE BANK MB-5 (E)ICE BANK MB-6 (E)ICE BANK MB-7 (E)ICE BANK MB-8 (E)ICE BANK MB-9 (E)ICE BANK MB-10
(E)DCV-1
(E)MCV-1
(E)1"
(E)3/4"
EXISTING PROBE LINES FROM NEW ICE INVENTORY
METER TO EXISTING ICE BANK CONTROL PANEL.
(E)SUCTION
DIFFUSER
(E)CHW GLYCOL
MAKEUP UNIT
(E)CHWP-8 (E)CHWP-7
(E)BUTTERFLY
VALVE (TYP)
(E)R-8
ROLAIRTROL
(E)DRAIN TO GMU
(E)DIGITAL
THERMOMETER
(TYP)
(E)6" CHWS/R FROM MAIN
BUILDING CHW PUMPS.
SEE WEST WING BUILDING
PIPING REMODEL FLOW
DIAGRAM BELOW FOR
CONTINUATION.
(E)6" CHWS/R TO SECONDARY
SYSTEM SERVING THE EAST WING
BUILDING.
(E)8" CHWS/R TO ICE BANK
STORAGE TANKS. SEE ICE BANK
PIPING FLOW DIAGRAM ABOVE FOR
CONTINUATION.
(E)TRIPLE DUTY
VALVE (TYP)
(E)PACKAGED CHILLER
(E)REDUCED PRESSURE
BACKFLOW PREVENTER
(E)COMBINATION
PRESSURE REGULATOR
AND REDUCING VALVE
(E)SIGHT GLASS (E)24 GALLON EXPANSION
TANK WITH ATF-12 TANK
FITTING MOUNTED ON STAND
(E)B&G DT-2 DRAIN-AIR
CHARGER VALVE
(E)DRAIN TO GMU
(E)VENT TO GMU
(E)BYPASS VALVE
GMU
CONTROL
PANEL
(E)6"
(E)6"
(E)6"
(E)6"
(E)SECONDARY BYPASS VALVE
(E)FLEX
CONNECTION
(TYP)
(E)PRESSURE
GAUGE (TYP)
(E)CONCRETE
HOUSEKEEPING
PAD (TYP)
(E)SUCTION
DIFFUSER
(E)6" CHWS/R TO
SECONDARY SYSTEM
SERVING THE ADJACENT
WEST WING AIR
HANDLING UNIT.
(LAYOUT SIMILAR TO
EAST WING AHU)
(E)CHWP-5(E)CHWP-6
(E)2-1/2" CHWR
(E)2-1/2" CHWS
TRANSFORMER
C2
IN ATC
C1
AI
24 VOLTDI
POWER
MAIN COMMUNICATION
TRUNK CABLE
AO C2
DO
CT
C1
C4 AI
C3 AI
AO C4
DO C3
AO C6
DO C5
AO C8
DO C7
AO C9
C6 AI
C5 DI
C8 DI
C7 DI
C10 DI
C9 DI
C12 AI
C11 AI
C14 AI
C13 AI
(E)CHILLER CH-1 FAULT / STATUS
CHWS TEMPERATURE
CHWR TEMPERATURE
INPUT FROM VFD-7 ((E)CHWP-7)
ALARM FROM VFD-7
INPUT FROM VFD-8 ((E)CHWP-8)
ALARM FROM VFD-8
(E)CHWP-7 STATUS D.P.
(E)CHWP-8 STATUS D.P.
FCP-1 STATUS C.S.
(E)ICE BANKS M-1 THRU M-3 DISCH. TEMP.
(E)ICE BANKS M-4 THRU M-7 DISCH. TEMP.
(E)ICE BANKS M-8 THRU M-10 DISCH. TEMP.
ICE BANKS ICE LEVEL
START / STOP (E)CHILLER CH-1
RESET (E)CHILLER CH-1 CHW TEMP.
START / STOP VFD-7 ((E)CHWP-7)
OUTPUT FROM VFD-7 - SPEED
START / STOP VFD-8 ((E)CHWP-8)
OUTPUT FROM VFD-8 - SPEED
START / STOP FCP-1
MODULATE (E)MCV-1 CONTROL VALVE
MODULATE (E)DCV-1 CONTROL VALVE
SCALE: NONE
SCALE: NONE
C14
C12C11 C13
FAULT
START / STOP
CONTACT
POWER
ON ENABLE
VFD EXTERNALBYPASS
ON
VFD
FAULT
HAND
OFF
AUTO
VFD
BYPASS
VFD-7
POWER
208/60/3
DISCONNECT
INTERLOCK
C3
C7
C4
RELAYS
VFD FAULT ALARM
CONTACT CLOSURE
C6
VFD-8
C8
C9
C1
C2
C1
C2C3
-
C9 C8
EXISTING ICE
INVENTORY
METER
FCP
1
1-1/2" CHWS
1-1/2" CHWR
DIRECT DIGITAL CONTROLLER(S)
QUANTITY AS REQUIRED INSTALL
IN ATC PANEL(S) LOCATED IN
MECHANICAL ROOM NEAR
CHWP-7 AND CHWP-8
FAULT
START / STOP
CONTACT
POWER
ON ENABLE
VFD EXTERNALBYPASS
ON
VFD
FAULT
HAND
OFF
AUTO
VFD
BYPASS
POWER
208/60/3
DISCONNECT
INTERLOCK
C5
C5
C6
RELAYS
VFD FAULT ALARM
CONTACT CLOSURE
C4
BY DIV. 26
HAND-OFF-AUTO
IN PANEL FACE
ATC PANEL
PILOT LIGHT
C7
C7 N
H
0
A
H
H
INLINE CIRC. PUMP
FAN COIL
120V POWER
FCP
1
C.S.
C4
PROVIDE NEW
TEMPERATURE SENSOR
PROVIDE NEW
TEMPERATURE SENSOR
PROVIDE NEW
TEMPERATURE SENSOR
C7
PROVIDE NEW
TEMPERATURE SENSOR
GENERAL NOTE:
REMOVE ALL EXISTING CONTROLS SERVING CHW SYSTEM,
INCLUDING CONTROL PANELS, FIELD WIRING,
COMMUNICATION, WIRING, AND TEMPERATURE SENSORS.
SEE SHEET MI603 FOR
CONTROL OF THESE PUMPS
(E)CHW GLYCOL LOW LEVEL ALARM C15 DI
TERMINATE WITH
HOSE CONNECTION
BDF ROOM 040 SPACE TEMP.C16 AI
SAC-040 / SCU-040 STATUS ALARM C17 DI
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
Mechanical
Control
Diagrams
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
2012
R
ALARM
ALARM
D3
ao^tfkd=klqbp
^ob^=?^?=pqb^j=ql=eb^qfkd=t^qbo=`lkqoli=af^do^j
dbkbo^i=klqb
(E) HWS
(E) HWR
(E) HWR
1
A.
2
2
2 0-150 PSI
0-40 PSI
3
3
4
4
5
5
66
6
7
8
7
V
V
V
PS
DPDP
S
PS
PS
R RG G R
S
S
POWER
(E)120/60/1
(E)HAND-OFF-AUTO
IN PANEL FACE
(E)ATC PANEL
(E)PILOT LIGHT
D3 N
H
0
A
R
H
H
DOMESTIC CIRC. PUMP
(E)ICP-5
(E) 3/4" CW LINE
(E)3/4"
(E)1"
(E)1"
(E)1"
FROM PRV
ASSEMBLY SRV.
(E) HEATING COIL
(E) 3"
(E)
2-1/2"
(E)
2-1/2"
(E)3/4"
(E) HEATING COIL
(E) 3"
(E)
2-1/2"
(E)
2-1/2"
(E)3/4"
(E) HEATING COIL
(E) 3"
(E)
2-1/2"
(E)
2-1/2"
(E)3/4"
(E) 3"(E) 6"
(E)HW GLYCOL MAKEUP UNIT
(E) 6" (E) 6"
FRAME HEATING WATER
(E) PACKAGED PLATE &
HEAT EXCHANGER SYSTEM
(E)3/4"
(E) UP IN CHASE TO REHEAT COILS
(E) 6"(E) 6"(E) 6"(E) 6"
(E) 6"
(E) 6"
(E) 4"
(E)3/4"
(E)3/4"
(E) 4"
(E)2-1/2"
(E) 4"(E) 4"
RETURN UNIT
(E) CONDENSATE (E) FLASH TANK
(E) VENT UP IN CHASE
(E) 4"
(E) 4"
(E) 6"
(E) 1"
(E) 3"
(E) 1-1/2"
(E) 3"
(E) 2"
(E) 2"
(E) 1-1/2"
WATER PLATE & FRAME
(E) PACKAGED DOMESTIC
HEAT EXCHANGER SYSTEM
(E) 6"
(E) 6" (E) AIR PURGER
(E)1" DHWR
IN-LINE
CIRC. PUMP
(E)ICP-5
(E)REDUCED PRESSURE
BACKFLOW PREVENTER
(E)COMBINATION
PRESSURE REGULATOR
AND REDUCING VALVE
(E)3/4"
(E)SIGHT GLASS (E)24 GALLON EXPANSION
TANK WITH ATF-12 TANK
FITTING MOUNTED ON STAND
(E)B&G DT-2 DRAIN-AIR
CHARGER VALVE
(E)DRAIN TO GMU
(E)VENT TO GMU
(E)BYPASS VALVE
(E)CONTROL AIR COMPRESSOR
CAC-1
(E)CONTROL AIR COMPRESSOR
CONTROL PANEL
(E)CONTROL
COMPRESSED AIR
SUPPLY
(E)DHW
TRANSFORMER
D2
IN ATC
D1
AI
24 VOLTAI
POWER
MAIN COMMUNICATION
TRUNK CABLE
AO D2
DO
CT
D1
D4 AI
D3 AI DO
D3
D6 DI
D5 AI
D8 AI
D7 DI
D10 AI
D9 DI
D12 DI
D11 DI
D14 AI
D13 DI
(E)BUILDING HW SUPPLY TEMPERATURE
(E)M.P. STEAM PRESSURE
(E)L.P. STEAM PRESSURE
INPUT FROM VFD-10 (HWP-10)
ALARM VFD-10
(E) ICP-5 STATUS C.S.
DOMESTIC HW RETURN TEMPERATURE
HWP-9 DIFFERENTIAL PRESSURE
(E)DOMESTIC HW SUPPLY TEMPERATURE
HIGH WATER ALARM
(E)HW GLYCOL LOW LEVEL ALARM
(E)CAC-1 ALARM
(E)CAC-1 PRESSURE
START / STOP VFD-10 (HWP-10)
OUTPUT TO VFD-10 - SPEED
START / STOP (E) DOMESTIC WATER RECIRC. PUMP ICP-5
DIRECT DIGITAL CONTROLLER(S)
QUANTITY AS REQUIRED
INSTALL IN ATC PANEL(S)
LOCATED IN AREA "A" MECHANICAL ROOM
(E)HIGH / LOW CONDENSATE ALARM
AREA "A" WATER METER FLOW RATE
D15 DI
-
DI
AI
DO
AO
-
-
-
SPARE ANALOG INPUT(TYP. OF 2)
SPARE DIGITAL INPUT (TYP. OF 3)
SPARE ANALOG OUTPUT
SPARE DIGITAL OUTPUT
D3
1
3
SCALE: NONE
D12
-
-
D1
D9
PUMP
VAV REHEAT
D1 D3
D15
D4
1
BCV-1
HWP
10 COIL PUMP
AHU HWHWP
9
D7
C.S.
REMOVE ALL EXISTING CONTROLS SERVING HW SYSTEM,
INCLUDING CONTROL PANELS, FIELD WIRING,
COMMUNICATION WIRING, AND SENSORS.
REMOVE EXISTING PNEUMATIC VALVE WITH PNEUMATIC
TUBING. PROVIDE NEW ELECTRONIC VALVE AS
SCHEDULED.
D13
D14 PROVIDE NEW
PRESSURE
SENSOR
EXISTING CONTROL AIR
COMPRESSOR CONTROL DIAGRAM
DISCONNECT
POWER
208/60/3
SEE DIV. 26
BYPASS
VFD
BYPASSVFDPOWER VFD
AUTO
HAND
INTERLOCK
RELAY
OFF
R
RD1 ON FAULTENABLE ON
START/STOP
CONTACT
VFD ALARM
HWP
10D1 WATER
HEATING
EXTERNAL
CONTACT CLOSURE
R
FAULT D5
D6
VFD-10
PUMP
D2
AREA "A" WATER METER
D2
SEE PLUMBING PLANS
FOR EXACT LOCATION
HIGH WATER ALARM
ONE IN MECHANICAL ROOM
D11 PROVIDE NEW
HIGH WATER SENSOR
FLOOR 1"
PROVIDE NEW STEAM PRESSURE SENSOR
PROVIDE NEW HYDRONIC TEMPERATURE SENSOR,
COORDINATE WITH MECHANICAL CONTRACTOR TO
PROVIDE THERMOWELL IN (E)DHWR PIPING.
D8
D10
PROVIDE NEW HYDRONIC TEMPERATURE SENSOR. FIELD
VERIFY EXACT PIPING CONFIGURATION AND DHW SENSOR
LOCATION.
PROVIDE NEW HYDRONIC TEMPERATURE SENSOR.
8
PROVIDE NEW SWAGE
CONTROLLER FOR THIS
PACKAGED SYSTEM.
REFERENCE SPECIFICATIONS.
PROVIDE NEW DIFFERENTIAL PRESSURE SENSOR.
REFERENCE SHEET MI603 FOR CONTROL OF THIS PUMP
AND RELATED MIXING VALVE.
EXTEND CAT-6E FROM EXISTING BACNET AND CONNECT
TO NEW PACKAGED HW HEAT EXCHANGER CONTROL
PANEL.
IT ROOM 245 SPACE TEMP.
SAC-245A / SCU-245A STATUS ALARM
SAC-245B / SCU-245B STATUS ALARM
D16 AI
D18 DI
D17 DI
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
Mechanical
Control
Diagrams
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
R
R
2012
ao^tfkd=klqbp
^ob^=?_?=pqb^j=ql=eb^qfkd=t^qbo=^ka=pkltjbiqfkd=eb^qfkd=t^qbo=`lkqoli=af^do^j
EbFpklt=jbiqfkd
pvpqbj=bk^_ib
`lkqoli af^do^j
dbkbo^i=klqb
S
DP DP
E1 E2 --
1
2
5
2
1
1
1
1
1
3
33
1 1
1 1
4
4
4
1
A.
5
6
6 6
S
V
V
V
V
V
V
D
D
DD
V
P
PS
PS
DPDP
S
S
GLYCOL MAKE-UP
(E) SNOWMELT
UNIT
HEAT EXCHANGER
(E) HEATING WATER
(E) SNOWMELT
HEAT EXCHANGER
(E) SNOWMELTING
EXPANSION TANK
(E)3/4"
(E)3"
(E
)
3
"
H
W
S
(E
)
3
"
H
W
R
(E)3"
(E)3"
(E)1"
(E)3/4" DRAIN
(E)3/4" VENT
(E)3" SHWS/R
(E) SNOWMELT
AIR SEPARATOR
(E)2-1/2" SHWR
(E)2-1/2" SHWS
(E)2-1/2" SHWS
(E)2-1/2" SHWR
(E) CAP FOR FUTURE
SNOWMELTING SYSTEMS
SERVES
NORTH STAIR
(E
)
3
"
S
H
W
S
(E
)
3
"
S
H
W
S
(E
)
3
"
S
H
W
S
(E
)
3
"
S
H
W
S
(E)1" BYPASS
GLOBE VALVE
(E)3" SHWS
(E)3" SHWS
EXISTING 6" LP STEAM
(E) STEAM TRAP
ASSEMBLY
(E)2" LP STEAM
(E)2" LP STEAM
(E) 3" LP CONDENSATE
(E) STEAM TRAP
(E) STEAM TRAP
ASSEMBLY
(E) STEAM TRAP
(E
)
3
"
H
W
S
(E
)
3
"
H
W
S
(E
)
3
"
H
W
S
(E
)
3
"
H
W
S
(E)3/4"
(E)COMBINATION
PRESSURE REGULATOR
AND REDUCING VALVE
(E)3/4"
(E)SIGHT GLASS
(E)30 GALLON EXPANSION TANK
(E)BYPASS
(E)R-3
ROLAIRTROL
(E)DRAIN TO GMU
(E)3"
VALVE
(E) COLD WATER
FILL LINE
(E)3"
(E)2-1/2" HWS/R
TO/FROM 2nd FLOOR
(E)2" HWS/R
TO/FROM 1st FLOOR
(E)1"
(E)1"
(E)1"
(E)1"
(E)1"
(E)1"
(E)1-1/2"
(E)1"
(E)1-1/2"
(E)1"
(E)1"
(E)1"
(E)3" HWR
(E)3" HWS
(E)LP STEAM LINE
(E)MP STEAM LINE
POWER
26
(E)120/60/1
SEE DIV.
(E)WIRING BETWEEN
J-BOX AND ATC
A
H
H
N-
0
H
R
IN PANEL FACE
(E)ATC PANEL
(E)PILOT LIGHT
(E)HAND-OFF-AUTO
R
-
R
(E)LOCAL ENABLE
(E)DDC INTERFACEDI
(E)MASTER SNOW MELTING
SYSTEM ENABLE
FROM CAMPUS
E2
(E)HEATING WATER
PUMP HWP-2
(E)SNOWMELTING
HEATING WATER
FAULT
(E)START / STOP
CONTACT
POWER
R
ON
G
ENABLE
VFD EXTERNALBYPASS
R G
ON
VFD
FAULT
R
HAND
OFF
AUTO
VFD
BYPASS
-
POWER
(E)208/60/3
(E)DISCONNECT
(E)INTERLOCK
- R
R
R -
-
RELAYS
VFD FAULT ALARM
(E)CONTACT CLOSURE
-
PUMP SHWP-2
(E)SNOWMELTING
HEATING WATER
FAULT
(E)START / STOP
CONTACT
POWER
R
ON
G
ENABLE
VFD EXTERNALBYPASS
R G
ON
VFD
FAULT
R
HAND
OFF
AUTO
VFD
BYPASS
-
POWER
(E)208/60/3
(E)DISCONNECT
(E)INTERLOCK
- R
R
R -
-
RELAYS
VFD FAULT ALARM
(E)CONTACT CLOSURE
-
PUMP SHWP-1
E1
(E)HEATING WATER
PUMP HWP-1
(E) HEATING WATER HEAT EXCHANGER
CONTROL VALVE ASSEMBLY
EXISTING 3" LP
CONDENSATE
(E)HEATING STEAM CONTROL VALVE
(E)CONDENSATE PUMP
CONTROL PANEL
12"
(E)HIGH WATER ALARM
ONE IN MECHANICAL ROOM
(E)SNOWMELTING
HEATING WATER PUMP
SHWP-2
(E)SNOWMELTING
HEATING WATER PUMP
SHWP-1
(E)HEATING WATER PUMP
HWP-2
(E)HEATING WATER PUMP
HWP-1
(E)DUPLEX CONDENSATE PUMP
TRANSFORMER
E2
IN ATC
E1
AI
24 VOLTAI
POWER
MAIN COMMUNICATION
TRUNK CABLE
DO E2
DO
CT
E1
E4 AI
E3 AI
AO E4
AO E3
AO E5
E6 DI
E5 AI
E8 DI
E7 AI
E10 DI
E9 DI
E12 DI
E11 DI
E13 DI
START / STOP VFD-1 (E)HWP-1
START / STOP VFD-2 (E)HWP-2
OUTPUT TO VFD-1 SPEED
OUTPUT TO VFD-2 SPEED
MODULATE (E)HW STEAM CONTROL VALVE
DIRECT DIGITAL CONTROLLER(S)
QUANTITY AS REQUIRED
INSTALL IN ATC PANEL(S)
LOCATED IN AREA "B" MECHANICAL ROOM
-
DI
AI
DO
AO
-
-
-
SPARE ANALOG INPUT(TYP. OF 2)
SPARE DIGITAL INPUT (TYP. OF 3)
SPARE ANALOG OUTPUT
SPARE DIGITAL OUTPUT
SCALE: NONE
(E)SCV-1
E14 AI
AREA "B" WATER METER
E14
SNOW MELTING PUMPS WITH RELATED VFDS, SNOW
MELTING TEMPERATURE SENSORS, AND SNOW MELTING
CONTROL VALVE ARE CURRENTLY CONTROLLED AND
MONITORED FROM AN INDEPENDENT DDC CONTROLLER BY
JOHNSON CONTROLS. AS PART OF THIS PROJECT,
CONNECT THIS CONTROLLER INTO THE NEW BUILDING
AUTOMATION SYSTEM TO ALLOW FOR COMMUNICATION,
MONITORING, AND ADJSTING OF SET POINTS FROM
HEAD END MONITORING STATION. REFERENCE ONE-LINE
(E)BUILDING HW SUPPLY TEMPERATURE
(E)BUILDING HW RETURN TEMPERATURE
(E)M.P. STEAM PRESSURE
(E)L.P. STEAM PRESSURE
INPUT FROM VFD-1 (E)HWP-1
ALARM FROM VFD-1
INPUT FROM VFD-2 (E)HWP-2
ALARM FROM VFD-2
(E)HWP-1 DIFFERENTIAL PRESSURE
(E)HWP-2 DIFFERENTIAL PRESSURE
HIGH WATER ALARM
(E)SHW GLYCOL LOW LEVEL ALARM
(E)HIGH / LOW CONDENSATE ALARM
AREA "B" WATER METER FLOW RATE
SEE PLUMBING PLANS
FOR EXACT LOCATION
E3
E4
FAULT
START/STOP
CONTACT
POWER
R
ON
G
ENABLE
VFD EXTERNALBYPASS
R G
ON
VFD
FAULT
R
HAND
OFF
AUTO
VFD
BYPASS
SEE DIV.
26
POWER
208/60/3
DISCONNECT
INTERLOCK
E1 R
R E6
E3
RELAYS
VFD FAULT ALARM
CONTACT CLOSURE
E5
FAULT
START/STOP
CONTACT
POWER
R
ON
G
ENABLE
VFD EXTERNALBYPASS
R G
ON
VFD
FAULT
R
HAND
OFF
AUTO
VFD
BYPASS
SEE DIV.
26
POWER
208/60/3
DISCONNECT
INTERLOCK
E2 R
R E8
E4
RELAYS
VFD FAULT ALARM
CONTACT CLOSURE
E7
(E)SHWP-1 VFD
(E)SHWP-2 VFD
VFD-1
VFD-2
E5
E12
E11
PROVIDE NEW HIGH
PROVIDE NEW DIFFERENTIAL PRESSURE SENSOR
E10E9
PROVIDE NEW TEMPERATURE SENSOR. FIELD VERIFY EXACT
E2
E1
LOCATION OF EXISTING TEMPERATURE SENSOR.
PROVIDE NEW STEAM PRESSURE SENSOR WITH A 0-150 PSI
RANGE. FIELD VERIFY EXACT LOCATION OF EXISTING STEAM
PRESSURE SENSOR.
DIAGRAM.
REMOVE ALL EXISTING CONTROLS SERVING HW SYSTEM,
INCLUDING CONTROL PANELS, FIELD WIRING,
COMMUNICATION WIRING, AND SENSORS.
E16 DI
E15 AI
E17 DI
TR/COMM ROOM 280 SPACE TEMP.
SAC-280A / SCU-280A STATUS ALARM
SAC-280B / SCU-280B STATUS ALARM
COORDINATE WITH MECHANICAL CONTRACTOR TO PROVIDE
PROVIDE NEW STEAM PRESSURE SENSOR WITH A 0-40 PSI
RANGE. FIELD VERIFY EXACT LOCATION OF EXISTING STEAM
PRESSURE SENSOR.
NEW INTERCONNECTING PIPING TO THE NEW DIFFERENTIAL
PRESSURE SENSORS WITH BALL TYPE SHUTOFF VALVES,
IF REQUIRED.
WATER SENSOR
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
Mechanical
Control
Diagrams
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
j^fk=`lkqoli=s^isb=p`ebarib
`lkqoli=s^isb=p`ebarib
SYMBOL VALVE TYPE OPERATOR TYPE GPM
PRESSURE
DIFF.
PSI
MIN. REQ'D CV CIRCULATING FLUID DUTY REMARKS
FCCV-1 3-WAY ELECTRIC MODULATING 4.4 3 2.54
30% PROPYLENE GLYCOL
CHILLED WATER
FCU-1
COOLING COIL
FCCV-2 3-WAY ELECTRIC MODULATING 5.1 3 2.94
30% PROPYLENE GLYCOL
CHILLED WATER
FCU-2
COOLING COIL
FCCV-3 2-WAY ELECTRIC MODULATING 4.4 3 2.54
30% PROPYLENE GLYCOL
CHILLED WATER
FCU-3
COOLING COIL
BCV-1 3-WAY ELECTRIC MODULATING 255 1 255.00
35% PROPYLENE GLYCOL
HEATING WATER
AREA "A" AHU
HC BYPASS
FHCV-1 3-WAY ELECTRIC MODULATING 1.8 3 1.04
35% PROPYLENE GLYCOL
HEATING WATER
FCU-1 HEATING
COIL
FHCV-2 3-WAY ELECTRIC MODULATING 5.2 3 3.00
35% PROPYLENE GLYCOL
HEATING WATER
FCU-2 HEATING
COIL
FHCV-3 2-WAY ELECTRIC MODULATING 1.8 3 1.04
35% PROPYLENE GLYCOL
HEATING WATER
FCU-3 HEATING
COIL
DXFHCV-1 2-WAY ELECTRIC MODULATING 2.2 3 1.27
35% PROPYLENE GLYCOL
HEATING WATER
DXFCU-3
HEATING COIL
CH-1 3-WAY ELECTRIC MODULATING 2.6 3 1.50
35% PROPYLENE GLYCOL
HEATING WATER
CH-1 HEATING
COIL
CH-2 2-WAY ELECTRIC MODULATING 1.5 3 0.87
35% PROPYLENE GLYCOL
HEATING WATER
CH-2 HEATING
COIL
CH-3 3-WAY ELECTRIC MODULATING 1.5 3 0.87
35% PROPYLENE GLYCOL
HEATING WATER
CH-3 HEATING
COIL
CH-4 3-WAY ELECTRIC MODULATING 1.5 3 0.87
35% PROPYLENE GLYCOL
HEATING WATER
CH-4 HEATING
COIL
CH-5 3-WAY ELECTRIC MODULATING 1.5 3 0.87
35% PROPYLENE GLYCOL
HEATING WATER
CH-5 HEATING
COIL
CH-6 3-WAY ELECTRIC MODULATING 1.5 3 0.87
35% PROPYLENE GLYCOL
HEATING WATER
CH-6 HEATING
COIL
CH-7 3-WAY ELECTRIC MODULATING 1.5 3 0.87
35% PROPYLENE GLYCOL
HEATING WATER
CH-7 HEATING
COIL
tbpq=s^so=_lubp=`lkqoli=s^isb=p`ebarib
SYMBOL VALVE TYPE OPERATOR TYPE GPM
MAXIMUM
PRESSURE DROP
CIRCULATING
FLUID
DUTY REMARKS
tbpq=s^so=_lubp=`lkqoli=s^isb=p`ebarib
SYMBOL VALVE TYPE OPERATOR TYPE GPM
MAXIMUM
PRESSURE DROP
CIRCULATING
FLUID
DUTY REMARKS
VAVR-001 2-WAY ELECTRIC MODULATING 1.1 3 PSI
35% PROPYLENE
GLYCOL
VAVR-001 HEATING
COIL
VAVR-009 3-WAY ELECTRIC MODULATING 3.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-009 HEATING
COIL
VAVR-010 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-010 HEATING
COIL
VAVR-011 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-011 HEATING
COIL
VAVR-012 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-012 HEATING
COIL
VAVR-013 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-013 HEATING
COIL
VAVR-015 3-WAY ELECTRIC MODULATING 0.9 3 PSI
35% PROPYLENE
GLYCOL
VAVR-015 HEATING
COIL
VAVR-016 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-016 HEATING
COIL
VAVR-018 3-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-018 HEATING
COIL
VAVR-020 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-020 HEATING
COIL
VAVR-022 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-022 HEATING
COIL
VAVR-022A 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-022A HEATING
COIL
VAVR-024 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-024 HEATING
COIL
VAVR-026A 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-026A HEATING
COIL
VAVR-026B 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-026B HEATING
COIL
VAVR-026C 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-026C HEATING
COIL
VAVR-026D 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-026D HEATING
COIL
VAVR-026E 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-026E HEATING
COIL
VAVR-026F 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-026F HEATING
COIL
VAVR-0-C 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-0-C HEATING
COIL
VAVR-100A 2-WAY ELECTRIC MODULATING 2.0 3 PSI
35% PROPYLENE
GLYCOL
VAVR-100A HEATING
COIL
VAVR-100B 2-WAY ELECTRIC MODULATING 2.0 3 PSI
35% PROPYLENE
GLYCOL
VAVR-100B HEATING
COIL
VAVR-104 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-104 HEATING
COIL
VAVR-106 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-106 HEATING
COIL
VAVR-108 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-108 HEATING
COIL
VAVR-110 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-110 HEATING
COIL
VAVR-112 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-112 HEATING
COIL
VAVR-114 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-114 HEATING
COIL
VAVR-114A 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-114A HEATING
COIL
VAVR-118A 2-WAY ELECTRIC MODULATING 1.6 3 PSI
35% PROPYLENE
GLYCOL
VAVR-118A HEATING
COIL
VAVR-118B 2-WAY ELECTRIC MODULATING 1.6 3 PSI
35% PROPYLENE
GLYCOL
VAVR-118B HEATING
COIL
VAVR-120AA 2-WAY ELECTRIC MODULATING 3.7 3 PSI
35% PROPYLENE
GLYCOL
VAVR-120AA
HEATING COIL
VAVR-120AB 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-120AB
HEATING COIL
VAVR-122AA 2-WAY ELECTRIC MODULATING 0.6 3 PSI
35% PROPYLENE
GLYCOL
VAVR-122AA
HEATING COIL
VAVR-122AB 2-WAY ELECTRIC MODULATING 0.6 3 PSI
35% PROPYLENE
GLYCOL
VAVR-122AB
HEATING COIL
VAVR-122AC 2-WAY ELECTRIC MODULATING 0.7 3 PSI
35% PROPYLENE
GLYCOL
VAVR-122AC
HEATING COIL
VAVR-122AD 2-WAY ELECTRIC MODULATING 0.6 3 PSI
35% PROPYLENE
GLYCOL
VAVR-122AD
HEATING COIL
VAVR-122AE 2-WAY ELECTRIC MODULATING 0.7 3 PSI
35% PROPYLENE
GLYCOL
VAVR-122AE
HEATING COIL
VAVR-122B 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-122B HEATING
COIL
VAVR-124 2-WAY ELECTRIC MODULATING 0.7 3 PSI
35% PROPYLENE
GLYCOL
VAVR-124 HEATING
COIL
VAVR-125 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-125 HEATING
COIL
VAVR-126 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-126 HEATING
COIL
VAVR-127 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-127 HEATING
COIL
VAVR-128 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-128 HEATING
COIL
VAVR-129 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-129 HEATING
COIL
VAVR-130 2-WAY ELECTRIC MODULATING 1.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-130 HEATING
COIL
VAVR-131 2-WAY ELECTRIC MODULATING 0.6 3 PSI
35% PROPYLENE
GLYCOL
VAVR-2100 HEATING
COIL
VAVR-132 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-2103 HEATING
COIL
VAVR-134 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-2104 HEATING
COIL
VAVR-136 3-WAY ELECTRIC MODULATING 1.4 3 PSI
35% PROPYLENE
GLYCOL
VAVR-2105 HEATING
COIL
VAVR-138 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-2106 HEATING
COIL
VAVR-140 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-2108 HEATING
COIL
VAVR-142 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-2111 HEATING
COIL
VAVR-146 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-2112 HEATING
COIL
VAVR-148 3-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-2114 HEATING
COIL
VAVR-200 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-2116 HEATING
COIL
VAVR-202 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-2117 HEATING
COIL
VAVR-204 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-2121 HEATING
COIL
VAVR-206 3-WAY ELECTRIC MODULATING 1.1 3 PSI
35% PROPYLENE
GLYCOL
VAVR-2127 HEATING
COIL
VAVR-208 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-2128 HEATING
COIL
VAVR-210 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-2130A
HEATING COIL
VAVR-212 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-2130B
HEATING COIL
VAVR-214 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-2131 HEATING
COIL
VAVR-216 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-2135 HEATING
COIL
VAVR-218 3-WAY ELECTRIC MODULATING 1.3 3 PSI
35% PROPYLENE
GLYCOL
VAVR-2137 HEATING
COIL
VAVR-220A 2-WAY ELECTRIC MODULATING 1.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-2138 HEATING
COIL
VAVR-220B 2-WAY ELECTRIC MODULATING 1.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-2143 HEATING
COIL
VAVR-220C 2-WAY ELECTRIC MODULATING 0.7 3 PSI
35% PROPYLENE
GLYCOL
VAVR-2149 HEATING
COIL
VAVR-220D 2-WAY ELECTRIC MODULATING 0.7 3 PSI
35% PROPYLENE
GLYCOL
VAVR-2154 HEATING
COIL
VAVR-220E 2-WAY ELECTRIC MODULATING 0.7 3 PSI
35% PROPYLENE
GLYCOL
VAVR-2155 HEATING
COIL
VAVR-222 2-WAY ELECTRIC MODULATING 0.8 3 PSI
35% PROPYLENE
GLYCOL
VAVR-2157 HEATING
COIL
VAVR-224 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-2162 HEATING
COIL
VAVR-226 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-2163 HEATING
COIL
VAVR-228 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-2165 HEATING
COIL
VAVR-228A 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-2167 HEATING
COIL
VAVR-228B 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-2173 HEATING
COIL
VAVR-228C 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-2176 HEATING
COIL
VAVR-230 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-2178 HEATING
COIL
VAVR-232 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-2180 HEATING
COIL
VAVR-234 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-2182 HEATING
COIL
VAVR-236 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-2183 HEATING
COIL
VAVR-238 2-WAY ELECTRIC MODULATING 2.2 3 PSI
35% PROPYLENE
GLYCOL
VAVR-2185 HEATING
COIL
VAVR-240A 3-WAY ELECTRIC MODULATING 1.0 3 PSI
35% PROPYLENE
GLYCOL
VAVR-2186 HEATING
COIL
VAVR-240B 2-WAY ELECTRIC MODULATING 1.1 3 PSI
35% PROPYLENE
GLYCOL
VAVR-3100 HEATING
COIL
VAVR-241 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-3101 HEATING
COIL
VAVR-242 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-3102A
HEATING COIL
VAVR-243 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-3102B
HEATING COIL
VAVR-246 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-3105 HEATING
COIL
VAVR-248 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-3107 HEATING
COIL
VAVR-253 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-3109 HEATING
COIL
VAVR-300A 2-WAY ELECTRIC MODULATING 1.0 3 PSI
35% PROPYLENE
GLYCOL
VAVR-3113 HEATING
COIL
VAVR-300B 2-WAY ELECTRIC MODULATING 1.0 3 PSI
35% PROPYLENE
GLYCOL
VAVR-3114 HEATING
COIL
VAVR-300C 2-WAY ELECTRIC MODULATING 1.0 3 PSI
35% PROPYLENE
GLYCOL
VAVR-3118 HEATING
COIL
VAVR-300D 2-WAY ELECTRIC MODULATING 0.9 3 PSI
35% PROPYLENE
GLYCOL
VAVR-3124A
HEATING COIL
VAVR-302 2-WAY ELECTRIC MODULATING 0.9 3 PSI
35% PROPYLENE
GLYCOL
VAVR-3124B
HEATING COIL
VAVR-304 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-3130 HEATING
COIL
VAVR-306 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-3134 HEATING
COIL
VAVR-310 2-WAY ELECTRIC MODULATING 0.9 3 PSI
35% PROPYLENE
GLYCOL
VAVR-3137 HEATING
COIL
VAVR-312 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-3138 HEATING
COIL
VAVR-314 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-3144 HEATING
COIL
VAVR-316 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-3145 HEATING
COIL
VAVR-318 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-3146 HEATING
COIL
VAVR-320 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-3150 HEATING
COIL
VAVR-322 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-3153 HEATING
COIL
VAVR-324AA 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-3161 HEATING
COIL
VAVR-324B 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-3164 HEATING
COIL
VAVR-324BB 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-3165 HEATING
COIL
VAVR-326 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-3167 HEATING
COIL
VAVR-328 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-3168 HEATING
COIL
VAVR-330 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-4101 HEATING
COIL
VAVR-332 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-4102 HEATING
COIL
VAVR-334 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-4103 HEATING
COIL
VAVR-336 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-4104 HEATING
COIL
VAVR-338 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-4106 HEATING
COIL
VAVR-340 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-4109 HEATING
COIL
VAVR-342A 2-WAY ELECTRIC MODULATING 2.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-4110 HEATING
COIL
VAVR-342B 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-4116 HEATING
COIL
VAVR-342C 2-WAY ELECTRIC MODULATING 0.9 3 PSI
35% PROPYLENE
GLYCOL
VAVR-4118 HEATING
COIL
VAVR-342D 3-WAY ELECTRIC MODULATING 0.9 3 PSI
35% PROPYLENE
GLYCOL
VAVR-4119 HEATING
COIL
VAVR-342E 2-WAY ELECTRIC MODULATING 0.9 3 PSI
35% PROPYLENE
GLYCOL
VAVR-4120 HEATING
COIL
VAVR-342F 2-WAY ELECTRIC MODULATING 0.9 3 PSI
35% PROPYLENE
GLYCOL
VAVR-4123 HEATING
COIL
VAVR-344 2-WAY ELECTRIC MODULATING 2.3 3 PSI
35% PROPYLENE
GLYCOL
VAVR-4125 HEATING
COIL
VAVR-344A 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-4128 HEATING
COIL
VAVR-344C 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-4137 HEATING
COIL
VAVR-346 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-4139 HEATING
COIL
VAVR-352 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-4142 HEATING
COIL
VAVR-360 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-4146 HEATING
COIL
VAVR-362 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-4147 HEATING
COIL
VAVR-366 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-4151 HEATING
COIL
VAVR-368 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-4153 HEATING
COIL
VAVR-374 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-4156 HEATING
COIL
VAVR-378 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-3-A 2-WAY ELECTRIC MODULATING 1.0 3 PSI
35% PROPYLENE
GLYCOL
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
Mechanical
Control Valve
Schedules
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
b^pq=s^so=_lubp=`lkqoli=s^isb=p`ebarib
SYMBOL VALVE TYPE OPERATOR TYPE GPM
MAXIMUM
PRESSURE DROP
CIRCULATING
FLUID
DUTY REMARKS
VAVR-150A 2-WAY ELECTRIC MODULATING 3.7 3 PSI
35% PROPYLENE
GLYCOL
VAVR-1200 HEATING
COIL
VAVR-150B 3-WAY ELECTRIC MODULATING 3.7 3 PSI
35% PROPYLENE
GLYCOL
VAVR-1201A
HEATING COIL
VAVR-152 3-WAY ELECTRIC MODULATING 1.3 3 PSI
35% PROPYLENE
GLYCOL
VAVR-1201B
HEATING COIL
VAVR-156 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-1201C
HEATING COIL
VAVR-156A 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-1211 HEATING
COIL
VAVR-156B 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-1300 HEATING
COIL
VAVR-156C 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-1301 HEATING
COIL
VAVR-156E 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-1302 HEATING
COIL
VAVR-156F 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-1304 HEATING
COIL
VAVR-158 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-1306 HEATING
COIL
VAVR-160 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-1310 HEATING
COIL
VAVR-160A 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-1311 HEATING
COIL
VAVR-160B 2-WAY
ELECTRIC
TWO POSITION
0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-1313 HEATING
COIL
VAVR-162 2-WAY
ELECTRIC
TWO POSITION
0.7 3 PSI
35% PROPYLENE
GLYCOL
VAVR-1315 HEATING
COIL
VAVR-164 2-WAY
ELECTRIC
TWO POSITION
0.8 3 PSI
35% PROPYLENE
GLYCOL
VAVR-1316 HEATING
COIL
VAVR-166 2-WAY ELECTRIC MODULATING 0.8 3 PSI
35% PROPYLENE
GLYCOL
VAVR-1320 HEATING
COIL
VAVR-168 2-WAY ELECTRIC MODULATING 0.9 3 PSI
35% PROPYLENE
GLYCOL
VAVR-1321 HEATING
COIL
VAVR-170A 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-1323 HEATING
COIL
VAVR-170AA 2-WAY ELECTRIC MODULATING 1.7 3 PSI
35% PROPYLENE
GLYCOL
VAVR-1324 HEATING
COIL
VAVR-170B 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-1326 HEATING
COIL
VAVR-170BB 2-WAY ELECTRIC MODULATING 0.8 3 PSI
35% PROPYLENE
GLYCOL
VAVR-1327 HEATING
COIL
VAVR-170C 3-WAY ELECTRIC MODULATING 0.8 3 PSI
35% PROPYLENE
GLYCOL
VAVR-1328 HEATING
COIL
VAVR-172 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-1329 HEATING
COIL
VAVR-174 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-1338 HEATING
COIL
VAVR-175 2-WAY
ELECTRIC
MODULATING
0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-1339 HEATING
COIL
VAVR-178 2-WAY
ELECTRIC
MODULATING
0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-2200A
HEATING COIL
VAVR-179 2-WAY
ELECTRIC
MODULATING
0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-2200B
HEATING COIL
VAVR-180 3-WAY
ELECTRIC
MODULATING
1.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-2200C
HEATING COIL
VAVR-181 2-WAY
ELECTRIC
MODULATING
0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-2300A
HEATING COIL
VAVR-182 2-WAY
ELECTRIC
MODULATING
0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-2300B
HEATING COIL
VAVR-183 2-WAY
ELECTRIC
MODULATING
0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-2301 HEATING
COIL
VAVR-184 2-WAY
ELECTRIC
MODULATING
0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-2303 HEATING
COIL
VAVR-185 2-WAY
ELECTRIC
MODULATING
0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-2306A
HEATING COIL
VAVR-186 2-WAY
ELECTRIC
MODULATING
0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-2306B
HEATING COIL
VAVR-188 2-WAY
ELECTRIC
MODULATING
0.7 3 PSI
35% PROPYLENE
GLYCOL
VAVR-2308 HEATING
COIL
VAVR-188A 2-WAY
ELECTRIC
MODULATING
0.9 3 PSI
35% PROPYLENE
GLYCOL
VAVR-2309 HEATING
COIL
VAVR-188B 2-WAY ELECTRIC MODULATING 0.7 3 PSI
35% PROPYLENE
GLYCOL
VAVR-2313 HEATING
COIL
VAVR-190 2-WAY ELECTRIC MODULATING 0.6 3 PSI
35% PROPYLENE
GLYCOL
VAVR-2316 HEATING
COIL
VAVR-190A 2-WAY ELECTRIC MODULATING 0.7 3 PSI
35% PROPYLENE
GLYCOL
VAVR-2317 HEATING
COIL
VAVR-190B 2-WAY ELECTRIC MODULATING 0.9 3 PSI
35% PROPYLENE
GLYCOL
VAVR-2318 HEATING
COIL
VAVR-192 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-2319 HEATING
COIL
VAVR-192A 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-2324 HEATING
COIL
VAVR-192B 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-2325 HEATING
COIL
VAVR-192C 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-2329 HEATING
COIL
VAVR-1-U 2-WAY ELECTRIC MODULATING 1.3 3 PSI
35% PROPYLENE
GLYCOL
VAVR-2330 HEATING
COIL
VAVR-1-V 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-2331 HEATING
COIL
VAVR-1-X 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-2332 HEATING
COIL
VAVR-1-Y 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-2335 HEATING
COIL
VAVR-1-Z 2-WAY ELECTRIC MODULATING 1.4 3 PSI
35% PROPYLENE
GLYCOL
VAVR-3200A
HEATING COIL
VAVR-250A 2-WAY ELECTRIC MODULATING 3.6 3 PSI
35% PROPYLENE
GLYCOL
VAVR-3200B
HEATING COIL
VAVR-250B 2-WAY ELECTRIC MODULATING 3.6 3 PSI
35% PROPYLENE
GLYCOL
VAVR-3200C
HEATING COIL
VAVR-252A 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-3302 HEATING
COIL
b^pq=s^so=_lubp=`lkqoli=s^isb=p`ebarib
SYMBOL VALVE TYPE OPERATOR TYPE GPM
MAXIMUM
PRESSURE DROP
CIRCULATING
FLUID
DUTY REMARKS
VAVR-252AA 2-WAY ELECTRIC MODULATING 2.0 3 PSI
35% PROPYLENE
GLYCOL
VAVR-3305 HEATING
COIL
VAVR-252B 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-3306 HEATING
COIL
VAVR-252BB 2-WAY ELECTRIC MODULATING 2.0 3 PSI
35% PROPYLENE
GLYCOL
VAVR-3307 HEATING
COIL
VAVR-252C 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-3310 HEATING
COIL
VAVR-252D 2-WAY
ELECTRIC
MODULATING
0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-3318 HEATING
COIL
VAVR-252E 3-WAY
ELECTRIC
MODULATING
0.7 3 PSI
35% PROPYLENE
GLYCOL
VAVR-3320 HEATING
COIL
VAVR-252G 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-3321 HEATING
COIL
VAVR-254 2-WAY ELECTRIC MODULATING 0.8 3 PSI
35% PROPYLENE
GLYCOL
VAVR-3326 HEATING
COIL
VAVR-256 2-WAY ELECTRIC MODULATING 1.2 3 PSI
35% PROPYLENE
GLYCOL
VAVR-3327 HEATING
COIL
VAVR-256A 2-WAY ELECTRIC MODULATING 0.8 3 PSI
35% PROPYLENE
GLYCOL
VAVR-3330 HEATING
COIL
VAVR-256B 2-WAY ELECTRIC MODULATING 0.7 3 PSI
35% PROPYLENE
GLYCOL
VAVR-3333 HEATING
COIL
VAVR-256C 2-WAY ELECTRIC MODULATING 0.8 3 PSI
35% PROPYLENE
GLYCOL
VAVR-3334 HEATING
COIL
VAVR-258 3-WAY ELECTRIC MODULATING 2.0 3 PSI
35% PROPYLENE
GLYCOL
VAVR-3338 HEATING
COIL
VAVR-260 2-WAY ELECTRIC MODULATING 0.7 3 PSI
35% PROPYLENE
GLYCOL
VAVR-3340 HEATING
COIL
VAVR-264 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-3343 HEATING
COIL
VAVR-265 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-3344 HEATING
COIL
VAVR-266 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-4200A
HEATING COIL
VAVR-267 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-4200B
HEATING COIL
VAVR-268 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-4200C
HEATING COIL
VAVR-269 3-WAY ELECTRIC MODULATING 1.2 3 PSI
35% PROPYLENE
GLYCOL
VAVR-4300 HEATING
COIL
VAVR-270A 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-4301 HEATING
COIL
VAVR-270AA 3-WAY ELECTRIC MODULATING 2.4 3 PSI
35% PROPYLENE
GLYCOL
VAVR-4303 HEATING
COIL
VAVR-270B 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-4304 HEATING
COIL
VAVR-270BB 2-WAY ELECTRIC MODULATING 1.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-4305 HEATING
COIL
VAVR-270CC 2-WAY ELECTRIC MODULATING 1.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-4308 HEATING
COIL
VAVR-270D 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-4309 HEATING
COIL
VAVR-270DD 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-4315 HEATING
COIL
VAVR-270F 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-4316 HEATING
COIL
VAVR-270G 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-4318 HEATING
COIL
VAVR-270H 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-4320 HEATING
COIL
VAVR-270J 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-4323 HEATING
COIL
VAVR-272 2-WAY ELECTRIC MODULATING 0.7 3 PSI
35% PROPYLENE
GLYCOL
VAVR-4324 HEATING
COIL
VAVR-274 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-4326 HEATING
COIL
VAVR-276 2-WAY ELECTRIC MODULATING 0.7 3 PSI
35% PROPYLENE
GLYCOL
VAVR-4327 HEATING
COIL
VAVR-278 2-WAY ELECTRIC MODULATING 0.7 3 PSI
35% PROPYLENE
GLYCOL
VAVR-4330 HEATING
COIL
VAVR-284 2-WAY ELECTRIC MODULATING 1.0 3 PSI
35% PROPYLENE
GLYCOL
VAVR-4333 HEATING
COIL
VAVR-286 2-WAY ELECTRIC MODULATING 0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-4335 HEATING
COIL
VAVR-288A 2-WAY
ELECTRIC
MODULATING
0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-4338 HEATING
COIL
VAVR-288AA 2-WAY
ELECTRIC
MODULATING
0.7 3 PSI
35% PROPYLENE
GLYCOL
VAVR-4342 HEATING
COIL
VAVR-288B 2-WAY
ELECTRIC
MODULATING
0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-4344 HEATING
COIL
VAVR-288BB 2-WAY
ELECTRIC
MODULATING
0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-4348 HEATING
COIL
VAVR-288C 2-WAY
ELECTRIC
MODULATING
0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-4349 HEATING
COIL
VAVR-288D 2-WAY
ELECTRIC
MODULATING
0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-4350 HEATING
COIL
VAVR-288E 2-WAY
ELECTRIC
MODULATING
0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-4352 HEATING
COIL
VAVR-288F 2-WAY
ELECTRIC
MODULATING
0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-5301 HEATING
COIL
VAVR-288G 2-WAY
ELECTRIC
MODULATING
0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-5303 HEATING
COIL
VAVR-299 2-WAY
ELECTRIC
MODULATING
2.4 3 PSI
35% PROPYLENE
GLYCOL
VAVR-5306 HEATING
COIL
VAVR-2-Q 2-WAY
ELECTRIC
MODULATING
0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-5307 HEATING
COIL
VAVR-2-U 2-WAY
ELECTRIC
MODULATING
0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-5308 HEATING
COIL
VAVR-2-W 2-WAY
ELECTRIC
MODULATING
0.5 3 PSI
35% PROPYLENE
GLYCOL
VAVR-5310 HEATING
COIL
VAV-3-I 2-WAY
ELECTRIC
MODULATING
NA 3 PSI
35% PROPYLENE
GLYCOL
VAVR-5314 HEATING
COIL
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
Mechanical
Control Valve
Schedules
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
dbkbo^i=klqbp
A.A.A.A.ALL HWS AND HWR RUNOUTS TO VAV REHEAT ALL HWS AND HWR RUNOUTS TO VAV REHEAT ALL HWS AND HWR RUNOUTS TO VAV REHEAT ALL HWS AND HWR RUNOUTS TO VAV REHEAT
COILS TO BE 3/4" UNLESS OTHERWISE NOTED.COILS TO BE 3/4" UNLESS OTHERWISE NOTED.COILS TO BE 3/4" UNLESS OTHERWISE NOTED.COILS TO BE 3/4" UNLESS OTHERWISE NOTED.
ALL VAVR REHEAT COILS SHALL BE SERVED BY A ALL VAVR REHEAT COILS SHALL BE SERVED BY A ALL VAVR REHEAT COILS SHALL BE SERVED BY A ALL VAVR REHEAT COILS SHALL BE SERVED BY A
2222----WAY CONTROL VALVE UNLESS OTHERWISE WAY CONTROL VALVE UNLESS OTHERWISE WAY CONTROL VALVE UNLESS OTHERWISE WAY CONTROL VALVE UNLESS OTHERWISE
NOTED.NOTED.NOTED.NOTED.
WHERE UNISTRUTS ARE NOT LOCATED NOR WHERE UNISTRUTS ARE NOT LOCATED NOR WHERE UNISTRUTS ARE NOT LOCATED NOR WHERE UNISTRUTS ARE NOT LOCATED NOR
ACCESSIBLE IN THE BOTTOM OF STRUCTURAL ACCESSIBLE IN THE BOTTOM OF STRUCTURAL ACCESSIBLE IN THE BOTTOM OF STRUCTURAL ACCESSIBLE IN THE BOTTOM OF STRUCTURAL
CONCRETE WEBS, ALL ANCHORS AND SUPPORTS CONCRETE WEBS, ALL ANCHORS AND SUPPORTS CONCRETE WEBS, ALL ANCHORS AND SUPPORTS CONCRETE WEBS, ALL ANCHORS AND SUPPORTS
SHALL BE CONNECTED TO THE SIDES OF THE SHALL BE CONNECTED TO THE SIDES OF THE SHALL BE CONNECTED TO THE SIDES OF THE SHALL BE CONNECTED TO THE SIDES OF THE
WEBS. DO NOT ATTACH TO THE BOTTOM OF THE WEBS. DO NOT ATTACH TO THE BOTTOM OF THE WEBS. DO NOT ATTACH TO THE BOTTOM OF THE WEBS. DO NOT ATTACH TO THE BOTTOM OF THE
WEB IF THERE IS NO EXISTING UNISTRUT.WEB IF THERE IS NO EXISTING UNISTRUT.WEB IF THERE IS NO EXISTING UNISTRUT.WEB IF THERE IS NO EXISTING UNISTRUT.
B.B.B.B.
C.C.C.C.
1111
GGGG
JJJJ
EEEE
CCCC
2222 3333 4444 5555
1111
MP401MP401MP401MP401
001001001001
VAVRVAVRVAVRVAVR 022A022A022A022A
VAVRVAVRVAVRVAVR
020020020020
VAVRVAVRVAVRVAVR
022022022022
VAVRVAVRVAVRVAVR 0000----CCCC
VAVRVAVRVAVRVAVR
016016016016
VAVRVAVRVAVRVAVR
018018018018
VAVRVAVRVAVRVAVR 040040040040
VAVVAVVAVVAV
015015015015
VAVRVAVRVAVRVAVR
013013013013
VAVRVAVRVAVRVAVR
010010010010
VAVRVAVRVAVRVAVR
011011011011
VAVRVAVRVAVRVAVR
009009009009
VAVRVAVRVAVRVAVR
026A026A026A026A
VAVRVAVRVAVRVAVR
012012012012
VAVRVAVRVAVRVAVR
026B026B026B026B
VAVRVAVRVAVRVAVR026C026C026C026C
VAVRVAVRVAVRVAVR
026D026D026D026D
VAVRVAVRVAVRVAVR
026E026E026E026E
VAVRVAVRVAVRVAVR
026F026F026F026F
VAVRVAVRVAVRVAVR
024024024024
VAVRVAVRVAVRVAVR
026F
STUDENTS
026E
OFFICE
026D
OFFICE
026C
OFFICE
026B
OFFICE
026A
OFFICE
011
OFFICE
009
IMAGING
AND
STORAGE
010
OFFICE
013
BREAK
ROOM
0-A
HALL
012
OFFICE
028
SHORT
TERM
STORAGE
047
HALL
0-C
HALL
016
TIER
2
015
MEN'S
RR
014
WOMEN'S
RR
040
BDF
020
OFFICE 018
OFFICE
022
OPS
022A
QA
0-G
HALL
0-E
STAIR
0-J
ELEV
036
CUSTODIAL
038
ELECTRICAL
032
STORAGE
042
CUSTODIAL
STORAGE
044
STORAGE
3/4"HWS/R3/4"HWS/R3/4"HWS/R3/4"HWS/R
3/4"HWS/R3/4"HWS/R3/4"HWS/R3/4"HWS/R
3/4"HWS/R3/4"HWS/R3/4"HWS/R3/4"HWS/R
1"HWS/R1"HWS/R1"HWS/R1"HWS/R
3/4"HWS/R3/4"HWS/R3/4"HWS/R3/4"HWS/R
1111----1/4"HWS/R1/4"HWS/R1/4"HWS/R1/4"HWS/R
1111
2222
2222
2222
S
S
S
S
S
S
S
S
S
S
S
S
S
S S S S
S
S
S
S
040040040040
SACSACSACSAC
040040040040
SCUSCUSCUSCU
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
Level 00 Area
A Mechanical
Piping
Remodel Plan
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
KEY PLAN
A
B
ao^tfkd=klqbp
0000555510101010 10101010 20202020
SCALE:SCALE:SCALE:SCALE:MP110aMP110aMP110aMP110a 1/8" = 1'1/8" = 1'1/8" = 1'1/8" = 1'----0"0"0"0"
ibsbi=MM=^ob^=^=jb`e^kf`^i=mfmfkd=objlabi=mi^k1111
NOTE
#DESCRIPTION
1111 EXISTING 2-1/2" HWS/R PIPING TO REMAIN AND BEEXISTING 2-1/2" HWS/R PIPING TO REMAIN AND BEEXISTING 2-1/2" HWS/R PIPING TO REMAIN AND BEEXISTING 2-1/2" HWS/R PIPING TO REMAIN AND BE
REPURPOSED AS CHWS/R.REPURPOSED AS CHWS/R.REPURPOSED AS CHWS/R.REPURPOSED AS CHWS/R.
2222 3-WAY HEATING WATER CONTROL VALVE.3-WAY HEATING WATER CONTROL VALVE.3-WAY HEATING WATER CONTROL VALVE.3-WAY HEATING WATER CONTROL VALVE.
16161616151515151414141413131313121212121111111110101010999988887777
KKKK
HHHH
FFFF
DDDD
BBBB
AAAA
GGGG
JJJJ
EEEE
CCCC
1" SHWS/R1" SHWS/R1" SHWS/R1" SHWS/R
(E)1" SHWS/R
2" SHWS/R2" SHWS/R2" SHWS/R2" SHWS/R
1111 2222
1" SHWS/R1" SHWS/R1" SHWS/R1" SHWS/R
1" SHWS/R1" SHWS/R1" SHWS/R1" SHWS/R
1" SHWS/R1" SHWS/R1" SHWS/R1" SHWS/R
2" SHWS/R2" SHWS/R2" SHWS/R2" SHWS/R
1111
MH402MH402MH402MH402
dbkbo^i=klqbp
A.A.A.A.ALL HWS AND HWR RUNOUTS TO VAV REHEAT ALL HWS AND HWR RUNOUTS TO VAV REHEAT ALL HWS AND HWR RUNOUTS TO VAV REHEAT ALL HWS AND HWR RUNOUTS TO VAV REHEAT
COILS TO BE 3/4" UNLESS OTHERWISE NOTED.COILS TO BE 3/4" UNLESS OTHERWISE NOTED.COILS TO BE 3/4" UNLESS OTHERWISE NOTED.COILS TO BE 3/4" UNLESS OTHERWISE NOTED.
ALL VAVR REHEAT COILS SHALL BE SERVED BY A ALL VAVR REHEAT COILS SHALL BE SERVED BY A ALL VAVR REHEAT COILS SHALL BE SERVED BY A ALL VAVR REHEAT COILS SHALL BE SERVED BY A
2222----WAY CONTROL VALVE UNLESS OTHERWISE WAY CONTROL VALVE UNLESS OTHERWISE WAY CONTROL VALVE UNLESS OTHERWISE WAY CONTROL VALVE UNLESS OTHERWISE
NOTED.NOTED.NOTED.NOTED.
WHERE UNISTRUTS ARE NOT LOCATED NOR WHERE UNISTRUTS ARE NOT LOCATED NOR WHERE UNISTRUTS ARE NOT LOCATED NOR WHERE UNISTRUTS ARE NOT LOCATED NOR
ACCESSIBLE IN THE BOTTOM OF STRUCTURAL ACCESSIBLE IN THE BOTTOM OF STRUCTURAL ACCESSIBLE IN THE BOTTOM OF STRUCTURAL ACCESSIBLE IN THE BOTTOM OF STRUCTURAL
CONCRETE WEBS, ALL ANCHORS AND SUPPORTS CONCRETE WEBS, ALL ANCHORS AND SUPPORTS CONCRETE WEBS, ALL ANCHORS AND SUPPORTS CONCRETE WEBS, ALL ANCHORS AND SUPPORTS
SHALL BE CONNECTED TO THE SIDES OF THE SHALL BE CONNECTED TO THE SIDES OF THE SHALL BE CONNECTED TO THE SIDES OF THE SHALL BE CONNECTED TO THE SIDES OF THE
WEBS. DO NOT ATTACH TO THE BOTTOM OF THE WEBS. DO NOT ATTACH TO THE BOTTOM OF THE WEBS. DO NOT ATTACH TO THE BOTTOM OF THE WEBS. DO NOT ATTACH TO THE BOTTOM OF THE
WEB IF THERE IS NO EXISTING UNISTRUT.WEB IF THERE IS NO EXISTING UNISTRUT.WEB IF THERE IS NO EXISTING UNISTRUT.WEB IF THERE IS NO EXISTING UNISTRUT.
B.B.B.B.
C.C.C.C.
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
LEVEL 00
AREA B
MECHANICAL
PLUMBING
REMODEL
PLAN
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
ao^tfkd=klqbp
NOTE
#DESCRIPTION
1111 RISE 1" SHW/R UP TO SNOWMELT MANIFOLD BOXRISE 1" SHW/R UP TO SNOWMELT MANIFOLD BOXRISE 1" SHW/R UP TO SNOWMELT MANIFOLD BOXRISE 1" SHW/R UP TO SNOWMELT MANIFOLD BOX
ABOVE REFERENCE DRAWING MP111b FORABOVE REFERENCE DRAWING MP111b FORABOVE REFERENCE DRAWING MP111b FORABOVE REFERENCE DRAWING MP111b FOR
CONTINUATION.CONTINUATION.CONTINUATION.CONTINUATION.
2222 CORE DRILL, SLEEVE, AND ANCHOR NEW SHWS/RCORE DRILL, SLEEVE, AND ANCHOR NEW SHWS/RCORE DRILL, SLEEVE, AND ANCHOR NEW SHWS/RCORE DRILL, SLEEVE, AND ANCHOR NEW SHWS/R
PIPING THROUGH CONCRETE TUNNEL WALL. SEALPIPING THROUGH CONCRETE TUNNEL WALL. SEALPIPING THROUGH CONCRETE TUNNEL WALL. SEALPIPING THROUGH CONCRETE TUNNEL WALL. SEAL
ALL ROUND PENETRATION WATER TIGHT. SEEALL ROUND PENETRATION WATER TIGHT. SEEALL ROUND PENETRATION WATER TIGHT. SEEALL ROUND PENETRATION WATER TIGHT. SEE
DETAIL.DETAIL.DETAIL.DETAIL.
SCALE:SCALE:SCALE:SCALE:MP110bMP110bMP110bMP110b 1/8" = 1'1/8" = 1'1/8" = 1'1/8" = 1'----0"0"0"0"
ibsbi=MM=^ob^=_=jb`e^kf`^i=mfmfkd=objlabi=mi^k2222
KEY PLAN
A
B
dbkbo^i=klqbp
A.A.A.A.ALL HWS AND HWR RUNOUTS TO VAV REHEAT ALL HWS AND HWR RUNOUTS TO VAV REHEAT ALL HWS AND HWR RUNOUTS TO VAV REHEAT ALL HWS AND HWR RUNOUTS TO VAV REHEAT
COILS TO BE 3/4" UNLESS OTHERWISE NOTED.COILS TO BE 3/4" UNLESS OTHERWISE NOTED.COILS TO BE 3/4" UNLESS OTHERWISE NOTED.COILS TO BE 3/4" UNLESS OTHERWISE NOTED.
ALL VAVR REHEAT COILS SHALL BE SERVED BY A ALL VAVR REHEAT COILS SHALL BE SERVED BY A ALL VAVR REHEAT COILS SHALL BE SERVED BY A ALL VAVR REHEAT COILS SHALL BE SERVED BY A
2222----WAY CONTROL VALVE UNLESS OTHERWISE WAY CONTROL VALVE UNLESS OTHERWISE WAY CONTROL VALVE UNLESS OTHERWISE WAY CONTROL VALVE UNLESS OTHERWISE
NOTED.NOTED.NOTED.NOTED.
WHERE UNISTRUTS ARE NOT LOCATED NOR WHERE UNISTRUTS ARE NOT LOCATED NOR WHERE UNISTRUTS ARE NOT LOCATED NOR WHERE UNISTRUTS ARE NOT LOCATED NOR
ACCESSIBLE IN THE BOTTOM OF STRUCTURAL ACCESSIBLE IN THE BOTTOM OF STRUCTURAL ACCESSIBLE IN THE BOTTOM OF STRUCTURAL ACCESSIBLE IN THE BOTTOM OF STRUCTURAL
CONCRETE WEBS, ALL ANCHORS AND SUPPORTS CONCRETE WEBS, ALL ANCHORS AND SUPPORTS CONCRETE WEBS, ALL ANCHORS AND SUPPORTS CONCRETE WEBS, ALL ANCHORS AND SUPPORTS
SHALL BE CONNECTED TO THE SIDES OF THE SHALL BE CONNECTED TO THE SIDES OF THE SHALL BE CONNECTED TO THE SIDES OF THE SHALL BE CONNECTED TO THE SIDES OF THE
WEBS. DO NOT ATTACH TO THE BOTTOM OF THE WEBS. DO NOT ATTACH TO THE BOTTOM OF THE WEBS. DO NOT ATTACH TO THE BOTTOM OF THE WEBS. DO NOT ATTACH TO THE BOTTOM OF THE
WEB IF THERE IS NO EXISTING UNISTRUT.WEB IF THERE IS NO EXISTING UNISTRUT.WEB IF THERE IS NO EXISTING UNISTRUT.WEB IF THERE IS NO EXISTING UNISTRUT.
B.B.B.B.
C.C.C.C.
1111
GGGG
JJJJ
LLLL
MMMM
NNNN
PPPP
QQQQ
EEEE
CCCC
2222 3333 4444 5555
1111
NEW SNOWNEW SNOWNEW SNOWNEW SNOW
MELT ZONE 1MELT ZONE 1MELT ZONE 1MELT ZONE 1
1111----1/4" SHWS/R1/4" SHWS/R1/4" SHWS/R1/4" SHWS/R
1111----1/4" SHWS/R1/4" SHWS/R1/4" SHWS/R1/4" SHWS/R
SNOWMELT SNOWMELT SNOWMELT SNOWMELT
MANIFOLD BOXMANIFOLD BOXMANIFOLD BOXMANIFOLD BOX
1111----1/4" SHWS/R1/4" SHWS/R1/4" SHWS/R1/4" SHWS/R
(UNDERGROUND)(UNDERGROUND)(UNDERGROUND)(UNDERGROUND)
1111
CHCHCHCH
1-F
VESTIBULE
120A
ENTRY
HALL
118
OPEN
STUDY
110
CIRCULATION
RECEPTION
110
CIRCULATION
RECEPTION
102
ELEC
ROOM
104
OFFICE
106
OFFICE
108
OFFICE
112
CHECK-IN
114
INTER LIBRARY LOAN WORKSPACE114A
OFFICE
116
RESERVE
MEDIA
1-E
MECH
1-D
STAIR
1-B
STAIR
1-A
VESTIBULE
147
JANITORS
OFFICE
148
WOMENS146
MENS
1-M
Room
144A
RESTROOM
VESTIBULE
144
FAMILY
RR
120B
ENTRY
HALL
122
HD
BOOK
COLLECTION
124
STUDY
(MED)
125
STUDY
(MED)
126
STUDY
(SM)
127
STUDY
(SM)
128
STUDY
(SM)
129
OFFICE
130
OFFICE
131
OFFICE
132
STUDY
(MED)
1-J
ELEVATOR
134
RECEPTION
136
OFFICE
138
OFFICE
140
CONFERENCE
ROOM
1-H
STAIR
150
READING
130130130130
VAVRVAVRVAVRVAVR
131131131131
VAVRVAVRVAVRVAVR
132132132132
VAVRVAVRVAVRVAVR
129129129129
VAVRVAVRVAVRVAVR
128128128128
VAVRVAVRVAVRVAVR
127127127127
VAVRVAVRVAVRVAVR
126126126126
VAVRVAVRVAVRVAVR
125125125125
VAVRVAVRVAVRVAVR
122AA122AA122AA122AA
VAVRVAVRVAVRVAVR
122AC122AC122AC122AC
VAVRVAVRVAVRVAVR
122AB122AB122AB122AB
VAVRVAVRVAVRVAVR
124124124124
VAVRVAVRVAVRVAVR
122AE122AE122AE122AE
VAVRVAVRVAVRVAVR
122AD122AD122AD122AD
VAVRVAVRVAVRVAVR
120AA120AA120AA120AA
VAVRVAVRVAVRVAVR 120AB120AB120AB120AB
VAVRVAVRVAVRVAVR
118A118A118A118A
VAVRVAVRVAVRVAVR 110110110110
VAVRVAVRVAVRVAVR
114A114A114A114A
VAVRVAVRVAVRVAVR
118B118B118B118B
VAVRVAVRVAVRVAVR
114114114114
VAVRVAVRVAVRVAVR
112112112112
VAVRVAVRVAVRVAVR 108108108108
VAVRVAVRVAVRVAVR
106106106106
VAVRVAVRVAVRVAVR
100B100B100B100B
VAVRVAVRVAVRVAVR
100A100A100A100A
VAVRVAVRVAVRVAVR
104104104104
VAVRVAVRVAVRVAVR
122B122B122B122B
VAVRVAVRVAVRVAVR
146146146146
VAVRVAVRVAVRVAVR
150B150B150B150B
VAVRVAVRVAVRVAVR
150A150A150A150A
VAVRVAVRVAVRVAVR
140140140140
VAVRVAVRVAVRVAVR
138138138138
VAVRVAVRVAVRVAVR
134134134134
VAVRVAVRVAVRVAVR
136136136136
VAVRVAVRVAVRVAVR
142142142142
VAVRVAVRVAVRVAVR
148148148148
VAVRVAVRVAVRVAVR
3333
CHCHCHCH
2222
CHCHCHCH
2222
2222
2222
2222
1" HWS/R1" HWS/R1" HWS/R1" HWS/R
3/4" HWS/R3/4" HWS/R3/4" HWS/R3/4" HWS/R
1111----1/4" HWS/R1/4" HWS/R1/4" HWS/R1/4" HWS/R 1" HWS/R1" HWS/R1" HWS/R1" HWS/R
1" CHWS/R1" CHWS/R1" CHWS/R1" CHWS/R
1" HWS/R1" HWS/R1" HWS/R1" HWS/R
1" HWS/R1" HWS/R1" HWS/R1" HWS/R
3/4" HWS/R3/4" HWS/R3/4" HWS/R3/4" HWS/R
3/4" HWS/R3/4" HWS/R3/4" HWS/R3/4" HWS/R
1" HWS/R1" HWS/R1" HWS/R1" HWS/R
3/4" HWS/R3/4" HWS/R3/4" HWS/R3/4" HWS/R 3" HWR3" HWR3" HWR3" HWR
3" HWS3" HWS3" HWS3" HWS
ISOLATION BUTTERFLYISOLATION BUTTERFLYISOLATION BUTTERFLYISOLATION BUTTERFLY
VALVE, TYPICALVALVE, TYPICALVALVE, TYPICALVALVE, TYPICAL
3333
1111----1/4" HWS/R1/4" HWS/R1/4" HWS/R1/4" HWS/R
1111
FCUFCUFCUFCU
4444
5555
4444
4444
4444
4444
4444
S
S
S
102102102102
VAVVAVVAVVAV
S
S
S
S
S
S
S
S
S
T
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
SS
S
S
S
666666666666
6666 6666
2222----1/2"1/2"1/2"1/2"2"2"2"2"
1111----1/4" SHWS/R1/4" SHWS/R1/4" SHWS/R1/4" SHWS/R
1111----1/4" SHWS/R1/4" SHWS/R1/4" SHWS/R1/4" SHWS/R
3"3"3"3"
1111----1/4"1/4"1/4"1/4"
3/4"3/4"3/4"3/4"
HWS/RHWS/RHWS/RHWS/R
6666
666666666666
S
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
Level 01 Area
A Mechanical
Piping
Remodel Plan
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
KEY PLAN
A
B
ao^tfkd=klqbp
0000555510101010 10101010 20202020
SCALE:SCALE:SCALE:SCALE:MP111aMP111aMP111aMP111a 1/8" = 1'1/8" = 1'1/8" = 1'1/8" = 1'----0"0"0"0"
ibsbi=N=^ob^=^=jb`e^kf`^i=mfmfkd=objlabi=mi^k1111
NOTE
#DESCRIPTION
1111 DROP 1-1/2" SHWS/R DOWN WALL AND EXTENDDROP 1-1/2" SHWS/R DOWN WALL AND EXTENDDROP 1-1/2" SHWS/R DOWN WALL AND EXTENDDROP 1-1/2" SHWS/R DOWN WALL AND EXTEND
UNDERGROUND TO SNOWMELT MANIFOLD BOX ASUNDERGROUND TO SNOWMELT MANIFOLD BOX ASUNDERGROUND TO SNOWMELT MANIFOLD BOX ASUNDERGROUND TO SNOWMELT MANIFOLD BOX AS
SHOWN. SAWCUT EXISTING CONCRETE SLAB ASSHOWN. SAWCUT EXISTING CONCRETE SLAB ASSHOWN. SAWCUT EXISTING CONCRETE SLAB ASSHOWN. SAWCUT EXISTING CONCRETE SLAB AS
REQUIRED. REFERENCE ARCHITECTURALREQUIRED. REFERENCE ARCHITECTURALREQUIRED. REFERENCE ARCHITECTURALREQUIRED. REFERENCE ARCHITECTURAL
DRAWINGS FOR CONCRETE REPAIR.DRAWINGS FOR CONCRETE REPAIR.DRAWINGS FOR CONCRETE REPAIR.DRAWINGS FOR CONCRETE REPAIR.
2222 EXISTING 2-1/2" HWS/R PIPING TO REMAIN AND BEEXISTING 2-1/2" HWS/R PIPING TO REMAIN AND BEEXISTING 2-1/2" HWS/R PIPING TO REMAIN AND BEEXISTING 2-1/2" HWS/R PIPING TO REMAIN AND BE
REPURPOSED AS CHWS/R.REPURPOSED AS CHWS/R.REPURPOSED AS CHWS/R.REPURPOSED AS CHWS/R.
3333 4" HWS/R PIPING UP FROM LEVEL BELOW. AFTER4" HWS/R PIPING UP FROM LEVEL BELOW. AFTER4" HWS/R PIPING UP FROM LEVEL BELOW. AFTER4" HWS/R PIPING UP FROM LEVEL BELOW. AFTER
3" BRANCH TAKE-OFF CONTINUE 4" HWS/R UP TO3" BRANCH TAKE-OFF CONTINUE 4" HWS/R UP TO3" BRANCH TAKE-OFF CONTINUE 4" HWS/R UP TO3" BRANCH TAKE-OFF CONTINUE 4" HWS/R UP TO
LEVEL ABOVE. REFERENCE DRAWINGS MP112aLEVEL ABOVE. REFERENCE DRAWINGS MP112aLEVEL ABOVE. REFERENCE DRAWINGS MP112aLEVEL ABOVE. REFERENCE DRAWINGS MP112a
AND MP401 FOR CONTINUATION.AND MP401 FOR CONTINUATION.AND MP401 FOR CONTINUATION.AND MP401 FOR CONTINUATION.
4444 3-WAY HEATING WATER CONTROL VALVE.3-WAY HEATING WATER CONTROL VALVE.3-WAY HEATING WATER CONTROL VALVE.3-WAY HEATING WATER CONTROL VALVE.
5555 3-WAY CHILLED WATER CONTROL VALVE AND3-WAY CHILLED WATER CONTROL VALVE AND3-WAY CHILLED WATER CONTROL VALVE AND3-WAY CHILLED WATER CONTROL VALVE AND
3-WAY HEATING WATER CONTROL VALVE.3-WAY HEATING WATER CONTROL VALVE.3-WAY HEATING WATER CONTROL VALVE.3-WAY HEATING WATER CONTROL VALVE.
6666 THIS AREA HAS NO CEILING AND IS OPEN TO THETHIS AREA HAS NO CEILING AND IS OPEN TO THETHIS AREA HAS NO CEILING AND IS OPEN TO THETHIS AREA HAS NO CEILING AND IS OPEN TO THE
STRUCTURE. IT IS THE INTENT THAT NOSTRUCTURE. IT IS THE INTENT THAT NOSTRUCTURE. IT IS THE INTENT THAT NOSTRUCTURE. IT IS THE INTENT THAT NO
HYDRONIC PIPING BE INSTALLED IN THIS AREA,HYDRONIC PIPING BE INSTALLED IN THIS AREA,HYDRONIC PIPING BE INSTALLED IN THIS AREA,HYDRONIC PIPING BE INSTALLED IN THIS AREA,
NEW OR EXISTING.NEW OR EXISTING.NEW OR EXISTING.NEW OR EXISTING.
dbkbo^i=klqbp
A.A.A.A.ALL HWS AND HWR RUNOUTS TO VAV REHEAT ALL HWS AND HWR RUNOUTS TO VAV REHEAT ALL HWS AND HWR RUNOUTS TO VAV REHEAT ALL HWS AND HWR RUNOUTS TO VAV REHEAT
COILS TO BE 3/4" UNLESS OTHERWISE NOTED.COILS TO BE 3/4" UNLESS OTHERWISE NOTED.COILS TO BE 3/4" UNLESS OTHERWISE NOTED.COILS TO BE 3/4" UNLESS OTHERWISE NOTED.
ALL VAVR REHEAT COILS SHALL BE SERVED BY A ALL VAVR REHEAT COILS SHALL BE SERVED BY A ALL VAVR REHEAT COILS SHALL BE SERVED BY A ALL VAVR REHEAT COILS SHALL BE SERVED BY A
2222----WAY CONTROL VALVE UNLESS OTHERWISE WAY CONTROL VALVE UNLESS OTHERWISE WAY CONTROL VALVE UNLESS OTHERWISE WAY CONTROL VALVE UNLESS OTHERWISE
NOTED.NOTED.NOTED.NOTED.
WHERE UNISTRUTS ARE NOT LOCATED NOR WHERE UNISTRUTS ARE NOT LOCATED NOR WHERE UNISTRUTS ARE NOT LOCATED NOR WHERE UNISTRUTS ARE NOT LOCATED NOR
ACCESSIBLE IN THE BOTTOM OF STRUCTURAL ACCESSIBLE IN THE BOTTOM OF STRUCTURAL ACCESSIBLE IN THE BOTTOM OF STRUCTURAL ACCESSIBLE IN THE BOTTOM OF STRUCTURAL
CONCRETE WEBS, ALL ANCHORS AND SUPPORTS CONCRETE WEBS, ALL ANCHORS AND SUPPORTS CONCRETE WEBS, ALL ANCHORS AND SUPPORTS CONCRETE WEBS, ALL ANCHORS AND SUPPORTS
SHALL BE CONNECTED TO THE SIDES OF THE SHALL BE CONNECTED TO THE SIDES OF THE SHALL BE CONNECTED TO THE SIDES OF THE SHALL BE CONNECTED TO THE SIDES OF THE
WEBS. DO NOT ATTACH TO THE BOTTOM OF THE WEBS. DO NOT ATTACH TO THE BOTTOM OF THE WEBS. DO NOT ATTACH TO THE BOTTOM OF THE WEBS. DO NOT ATTACH TO THE BOTTOM OF THE
WEB IF THERE IS NO EXISTING UNISTRUT.WEB IF THERE IS NO EXISTING UNISTRUT.WEB IF THERE IS NO EXISTING UNISTRUT.WEB IF THERE IS NO EXISTING UNISTRUT.
B.B.B.B.
C.C.C.C.
16161616151515151414141413131313121212121111111110101010999988887777
KKKK
HHHH
FFFF
DDDD
BBBB
AAAA
NEWNEWNEWNEW
SNOWMELTSNOWMELTSNOWMELTSNOWMELT
ZONE 2ZONE 2ZONE 2ZONE 2
1111----1/4" SHWS1/4" SHWS1/4" SHWS1/4" SHWS
1111----1/4" SHWR1/4" SHWR1/4" SHWR1/4" SHWR
1111
SNOWMELTSNOWMELTSNOWMELTSNOWMELT
MANIFOLD BOXMANIFOLD BOXMANIFOLD BOXMANIFOLD BOX
156C
PRACTICE
156B
PRACTICE
156A
PRACTICE
156
WORKSPACE
156F
OFFICE
156E
PRACTICE
08A
ELEV
EQUIP
08
MECH
1-T
ELEV
192A
SMALL
MEETING
192
WORKSTATIONS/
FLEX
SPACE
190C
STORAGE
192C
STORAGE
192B
OFFICE
160A
OFFICE
160B
OFFICE
158
CONFERENCE
ROOM
1-S
HALL
160
TUTORING ADMIN OPEN AREA
162
CLASSROOM
164
CLASSROOM
1-U
VESTIBULE
166
CLASSROOM
168
CLASSROOM
174
STUDENT
PREP
176
I.T.
HELP
DESK
175
MATH
LAB
RECEPTION
1-Y
HALL
173
ELECTRICAL
152
WOMEN'S
RESTROOM
154
MEN'S
RESTROOM
1-R
HALL
1-N
STAIRS
172
CLASSROOM
170B
STUDY
170A
STUDY
170C
STORAGE
170
DROP
IN
MATH
LAB
180
ADJUNCT
OFFICE
181
OFFICE
182
OFFICE
183
OFFICE
184
OFFICE
185
OFFICE
186
OFFICE
188
COLLABORATIVE
SPACE
190
TRAINING
AREA
190A
OFFICE
190B
OFFICE 1-Z
VESTIBULE
188A
OFFICE
188B
CONFERENCE
156C156C156C156C
VAVRVAVRVAVRVAVR
156B156B156B156B
VAVRVAVRVAVRVAVR
156A156A156A156A
VAVRVAVRVAVRVAVR
156156156156
VAVRVAVRVAVRVAVR
156E156E156E156E
VAVRVAVRVAVRVAVR
156F156F156F156F
VAVRVAVRVAVRVAVR
192A192A192A192A
VAVRVAVRVAVRVAVR
192C192C192C192C
VAVRVAVRVAVRVAVR
192B192B192B192B
VAVRVAVRVAVRVAVR
192192192192
VAVRVAVRVAVRVAVR
160A160A160A160A
VAVRVAVRVAVRVAVR
160B160B160B160B
VAVRVAVRVAVRVAVR
1111----YYYY
VAVRVAVRVAVRVAVR
158158158158
VAVRVAVRVAVRVAVR
160160160160
VAVRVAVRVAVRVAVR
162162162162
VAVRVAVRVAVRVAVR
152152152152
VAVRVAVRVAVRVAVR
164164164164
VAVRVAVRVAVRVAVR
1111----UUUU
VAVRVAVRVAVRVAVR 166166166166
VAVRVAVRVAVRVAVR
168168168168
VAVRVAVRVAVRVAVR
175175175175
VAVRVAVRVAVRVAVR
174174174174
VAVRVAVRVAVRVAVR
1111----VVVV
VAVRVAVRVAVRVAVR
170BB170BB170BB170BB
VAVRVAVRVAVRVAVR
170AA170AA170AA170AA
VAVRVAVRVAVRVAVR
170A170A170A170A
VAVRVAVRVAVRVAVR
170B170B170B170B
VAVRVAVRVAVRVAVR
170C170C170C170C
VAVRVAVRVAVRVAVR
172172172172
VAVRVAVRVAVRVAVR
179179179179
VAVRVAVRVAVRVAVR
178178178178
VAVRVAVRVAVRVAVR
173173173173
VAVVAVVAVVAV
188188188188
VAVRVAVRVAVRVAVR
186186186186
VAVRVAVRVAVRVAVR
185185185185
VAVRVAVRVAVRVAVR
184184184184
VAVRVAVRVAVRVAVR
183183183183
VAVRVAVRVAVRVAVR
182182182182
VAVRVAVRVAVRVAVR
181181181181
VAVRVAVRVAVRVAVR
1111----XXXX
VAVRVAVRVAVRVAVR
180180180180
VAVRVAVRVAVRVAVR
1111----ZZZZ
VAVRVAVRVAVRVAVR
190190190190
VAVRVAVRVAVRVAVR
190A190A190A190A
VAVRVAVRVAVRVAVR
190B190B190B190B
VAVRVAVRVAVRVAVR
188A188A188A188A
VAVRVAVRVAVRVAVR
188B188B188B188B
VAVRVAVRVAVRVAVR
4444
CHCHCHCH
5555
CHCHCHCH
6666
CHCHCHCH
7777
CHCHCHCH
1111----1/4" HWS/R1/4" HWS/R1/4" HWS/R1/4" HWS/R
1111----1/4" HWR1/4" HWR1/4" HWR1/4" HWR
1111----1/4" HWS1/4" HWS1/4" HWS1/4" HWS
1111----1/4" HWS1/4" HWS1/4" HWS1/4" HWS
3/4" HWS/R3/4" HWS/R3/4" HWS/R3/4" HWS/R
1" HWS/R1" HWS/R1" HWS/R1" HWS/R
3/4" HWS/R3/4" HWS/R3/4" HWS/R3/4" HWS/R
3/4" HWS/R3/4" HWS/R3/4" HWS/R3/4" HWS/R
1" HWS/R1" HWS/R1" HWS/R1" HWS/R 1" HWS/R1" HWS/R1" HWS/R1" HWS/R
3/4" HWS/R3/4" HWS/R3/4" HWS/R3/4" HWS/R
1111----1/4" HWS/R1/4" HWS/R1/4" HWS/R1/4" HWS/R 1" HWS/R1" HWS/R1" HWS/R1" HWS/R 1" HWS/R1" HWS/R1" HWS/R1" HWS/R
3/4" HWS/R3/4" HWS/R3/4" HWS/R3/4" HWS/R3/4" 3/4" 3/4" 3/4"
HWS/RHWS/RHWS/RHWS/R
1111----1/4" HWS/R1/4" HWS/R1/4" HWS/R1/4" HWS/R
3/4" HWS/R3/4" HWS/R3/4" HWS/R3/4" HWS/R
3/4" HWS/R3/4" HWS/R3/4" HWS/R3/4" HWS/R
3/4" HWS/R3/4" HWS/R3/4" HWS/R3/4" HWS/R
1111----1/4" HWS/R1/4" HWS/R1/4" HWS/R1/4" HWS/R
1111----1/2" HWR1/2" HWR1/2" HWR1/2" HWR
1111----1/4" HWS/R1/4" HWS/R1/4" HWS/R1/4" HWS/R
3/4" 3/4" 3/4" 3/4"
HWS/RHWS/RHWS/RHWS/R
3/4" HWS/R3/4" HWS/R3/4" HWS/R3/4" HWS/R
2" HWS2" HWS2" HWS2" HWS
3/4" HWS/R3/4" HWS/R3/4" HWS/R3/4" HWS/R
2222
22222222
2222
2222
2222 2222
S
SS
S
S
S
S
S
S
S
S
SSSS
S
S
S
S
S
SS
S
S
S
S
S
S
S
S
S
S S S
S
S
S S
S S
SS
S S
S
SS
S
S
S
1111
MH402MH402MH402MH402
3333
1"1"1"1"
3333
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
Level 01 Area
B Mechanical
Piping
Remodel Plan
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
KEY PLAN
A
B
ao^tfkd=klqbp
0000555510101010 10101010 20202020
SCALE:SCALE:SCALE:SCALE:MP111bMP111bMP111bMP111b 1/8" = 1'1/8" = 1'1/8" = 1'1/8" = 1'----0"0"0"0"
ibsbi=N=^ob^=_=jb`e^kf`^i=mfmfkd=objlabi=mi^k1111
NOTE
#DESCRIPTION
1111 1" SHWS/R UP FROM BELOW. REFERENCE1" SHWS/R UP FROM BELOW. REFERENCE1" SHWS/R UP FROM BELOW. REFERENCE1" SHWS/R UP FROM BELOW. REFERENCE
DRAWING MP110b FOR CONTINUATION.DRAWING MP110b FOR CONTINUATION.DRAWING MP110b FOR CONTINUATION.DRAWING MP110b FOR CONTINUATION.
2222 3-WAY HEATING WATER CONTROL VALVE.3-WAY HEATING WATER CONTROL VALVE.3-WAY HEATING WATER CONTROL VALVE.3-WAY HEATING WATER CONTROL VALVE.
3333 THIS AREA HAS NO CEILING AND IS OPEN TO THETHIS AREA HAS NO CEILING AND IS OPEN TO THETHIS AREA HAS NO CEILING AND IS OPEN TO THETHIS AREA HAS NO CEILING AND IS OPEN TO THE
STRUCTURE. IT IS THE INTENT THAT NOSTRUCTURE. IT IS THE INTENT THAT NOSTRUCTURE. IT IS THE INTENT THAT NOSTRUCTURE. IT IS THE INTENT THAT NO
HYDRONIC PIPING BE INSTALLED IN THIS AREA,HYDRONIC PIPING BE INSTALLED IN THIS AREA,HYDRONIC PIPING BE INSTALLED IN THIS AREA,HYDRONIC PIPING BE INSTALLED IN THIS AREA,
NEW OR EXISTING.NEW OR EXISTING.NEW OR EXISTING.NEW OR EXISTING.
dbkbo^i=klqbp
A.A.A.A.ALL HWS AND HWR RUNOUTS TO VAV REHEAT ALL HWS AND HWR RUNOUTS TO VAV REHEAT ALL HWS AND HWR RUNOUTS TO VAV REHEAT ALL HWS AND HWR RUNOUTS TO VAV REHEAT
COILS TO BE 3/4" UNLESS OTHERWISE NOTED.COILS TO BE 3/4" UNLESS OTHERWISE NOTED.COILS TO BE 3/4" UNLESS OTHERWISE NOTED.COILS TO BE 3/4" UNLESS OTHERWISE NOTED.
ALL VAVR REHEAT COILS SHALL BE SERVED BY A ALL VAVR REHEAT COILS SHALL BE SERVED BY A ALL VAVR REHEAT COILS SHALL BE SERVED BY A ALL VAVR REHEAT COILS SHALL BE SERVED BY A
2222----WAY CONTROL VALVE UNLESS OTHERWISE WAY CONTROL VALVE UNLESS OTHERWISE WAY CONTROL VALVE UNLESS OTHERWISE WAY CONTROL VALVE UNLESS OTHERWISE
NOTED.NOTED.NOTED.NOTED.
WHERE UNISTRUTS ARE NOT LOCATED NOR WHERE UNISTRUTS ARE NOT LOCATED NOR WHERE UNISTRUTS ARE NOT LOCATED NOR WHERE UNISTRUTS ARE NOT LOCATED NOR
ACCESSIBLE IN THE BOTTOM OF STRUCTURAL ACCESSIBLE IN THE BOTTOM OF STRUCTURAL ACCESSIBLE IN THE BOTTOM OF STRUCTURAL ACCESSIBLE IN THE BOTTOM OF STRUCTURAL
CONCRETE WEBS, ALL ANCHORS AND SUPPORTS CONCRETE WEBS, ALL ANCHORS AND SUPPORTS CONCRETE WEBS, ALL ANCHORS AND SUPPORTS CONCRETE WEBS, ALL ANCHORS AND SUPPORTS
SHALL BE CONNECTED TO THE SIDES OF THE SHALL BE CONNECTED TO THE SIDES OF THE SHALL BE CONNECTED TO THE SIDES OF THE SHALL BE CONNECTED TO THE SIDES OF THE
WEBS. DO NOT ATTACH TO THE BOTTOM OF THE WEBS. DO NOT ATTACH TO THE BOTTOM OF THE WEBS. DO NOT ATTACH TO THE BOTTOM OF THE WEBS. DO NOT ATTACH TO THE BOTTOM OF THE
WEB IF THERE IS NO EXISTING UNISTRUT.WEB IF THERE IS NO EXISTING UNISTRUT.WEB IF THERE IS NO EXISTING UNISTRUT.WEB IF THERE IS NO EXISTING UNISTRUT.
B.B.B.B.
C.C.C.C.
1111
GGGG
JJJJ
LLLL
MMMM
NNNN
PPPP
QQQQ
EEEE
CCCC
2222 3333 4444 5555
1111
DXFCUDXFCUDXFCUDXFCU
1111
HHHH
S H
1111
2222
3333
4444
6666
1" HWS/R1" HWS/R1" HWS/R1" HWS/R
238
TECH
SERVICES
244
FAMILY
RR
243
MOTHERS
2-H
ELEV
234
LARGE
COMPUTER
CLASSROOM
236
SHEET
MUSIC
228C
SCANNER
228B
DCAM
228E
VAULT
2-D
MECHANICAL
228A
OFFICE
232
OFFICE
242
ELECTRICAL
ROOM
249
JANITOR'S
CLOSET
2-M
HALL
247
MEN'S
RESTROOM
248
WOMEN'S
RESTROOM
245
I.T.228
SPECIAL
COLLECTIONS
230
OFFICE
228D
ARCHIVE
224
INSTRUCTION
2
222
INSTRUCTION
1
226
PRESS
ROOM
220
OPEN
STUDY
2-A
STAIR
200
OFFICE
202
OFFICE
204
STUDY
(SM)
206
STUDY
(MED)
208
STUDY
(SM)
210
STUDY
(SM)
212
STUDY
(SM)2-B
STAIR
214
STUDY
(MED)
216
STUDY
(MED)
218
STUDY
(MED)
218218218218
VAVRVAVRVAVRVAVR
216216216216
VAVRVAVRVAVRVAVR
214214214214
VAVRVAVRVAVRVAVR
220B220B220B220B
VAVRVAVRVAVRVAVR
212212212212
VAVRVAVRVAVRVAVR
210210210210
VAVRVAVRVAVRVAVR
208208208208
VAVRVAVRVAVRVAVR
206206206206
VAVRVAVRVAVRVAVR
204204204204
VAVRVAVRVAVRVAVR
202202202202
VAVRVAVRVAVRVAVR
200200200200
VAVRVAVRVAVRVAVR
220C220C220C220C
VAVRVAVRVAVRVAVR
220A220A220A220A
VAVRVAVRVAVRVAVR
220D220D220D220D
VAVRVAVRVAVRVAVR
220E220E220E220E
VAVRVAVRVAVRVAVR
222222222222
VAVRVAVRVAVRVAVR
224224224224
VAVRVAVRVAVRVAVR
226226226226
VAVRVAVRVAVRVAVR
228228228228
VAVRVAVRVAVRVAVR
228B228B228B228B
VAVRVAVRVAVRVAVR 228A228A228A228A
VAVRVAVRVAVRVAVR
232232232232
VAVRVAVRVAVRVAVR
230230230230
VAVRVAVRVAVRVAVR
246246246246
VAVRVAVRVAVRVAVR
248248248248
VAVRVAVRVAVRVAVR
241241241241
VAVRVAVRVAVRVAVR
242242242242
VAVRVAVRVAVRVAVR
240B240B240B240B
VAVRVAVRVAVRVAVR
240A240A240A240A
VAVRVAVRVAVRVAVR
243243243243
VAVRVAVRVAVRVAVR
234234234234
VAVRVAVRVAVRVAVR
236236236236
VAVRVAVRVAVRVAVR
228C228C228C228C
VAVRVAVRVAVRVAVR
238238238238
VAVRVAVRVAVRVAVR
253253253253
VAVRVAVRVAVRVAVR
250B250B250B250B
VAVRVAVRVAVRVAVR
250A250A250A250A
VAVRVAVRVAVRVAVR
1" HWS/R1" HWS/R1" HWS/R1" HWS/R3/4" HWS/R3/4" HWS/R3/4" HWS/R3/4" HWS/R
3/4" HWS/R3/4" HWS/R3/4" HWS/R3/4" HWS/R
3/4" HWS/R3/4" HWS/R3/4" HWS/R3/4" HWS/R
1" HWS/R1" HWS/R1" HWS/R1" HWS/R
1" HWS/R1" HWS/R1" HWS/R1" HWS/R
1" CHWS/R1" CHWS/R1" CHWS/R1" CHWS/R
7777
8888
7777
7777
1" HWS/R1" HWS/R1" HWS/R1" HWS/R3/4" HWS/R3/4" HWS/R3/4" HWS/R3/4" HWS/R
1" HWS/R1" HWS/R1" HWS/R1" HWS/R
1" HWS/R1" HWS/R1" HWS/R1" HWS/R
7777
3/4" HWS/R3/4" HWS/R3/4" HWS/R3/4" HWS/R
3" HWR3" HWR3" HWR3" HWR
3" HWS3" HWS3" HWS3" HWS
ISOLATION BUTTERFLYISOLATION BUTTERFLYISOLATION BUTTERFLYISOLATION BUTTERFLY
VALVE, TYPICALVALVE, TYPICALVALVE, TYPICALVALVE, TYPICAL
9999
1111----1/4" HWS1/4" HWS1/4" HWS1/4" HWS
1111----1/4" HWR1/4" HWR1/4" HWR1/4" HWR
1" HWS1" HWS1" HWS1" HWS1" HWR1" HWR1" HWR1" HWR
2222
FCUFCUFCUFCU
10101010
11111111
10101010
10101010
10101010
10101010
12121212
S H
S
S
S
S
S
S
S
S
S
S
S
S S
S
S
S
S
S
S
S
S
SS
S
S
S
S
S
241A
IT
241
JANITOR'S
OFFICE
S S
S
S
S
S
S
S
S
S
S 13131313
245A245A245A245A
SACSACSACSAC
245B245B245B245B
SACSACSACSAC
14141414 14141414 14141414
1" HWS/R1" HWS/R1" HWS/R1" HWS/R
3/4" HWS/R3/4" HWS/R3/4" HWS/R3/4" HWS/R
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
Level 02 Area
A Mechanical
Piping
Remodel Plan
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
KEY PLAN
A
B
ao^tfkd=klqbp
0000555510101010 10101010 20202020
SCALE:SCALE:SCALE:SCALE:MP112aMP112aMP112aMP112a 1/8" = 1'1/8" = 1'1/8" = 1'1/8" = 1'----0"0"0"0"
ibsbi=O=^ob^=^=jb`e^kf`^i=mfmfkd=objlabi=mi^k1111
NOTE
#DESCRIPTION
1111 REMOTE MOUNTED HUMIDISTAT FURNISHED WITHREMOTE MOUNTED HUMIDISTAT FURNISHED WITHREMOTE MOUNTED HUMIDISTAT FURNISHED WITHREMOTE MOUNTED HUMIDISTAT FURNISHED WITH
HUMIDIFIER H-1. INSTALL PER MANUFACTURER'SHUMIDIFIER H-1. INSTALL PER MANUFACTURER'SHUMIDIFIER H-1. INSTALL PER MANUFACTURER'SHUMIDIFIER H-1. INSTALL PER MANUFACTURER'S
RECOMMENDATIONS.RECOMMENDATIONS.RECOMMENDATIONS.RECOMMENDATIONS.
2222 RO UNIT, REFERENCE PLUMBING DRAWINGS.RO UNIT, REFERENCE PLUMBING DRAWINGS.RO UNIT, REFERENCE PLUMBING DRAWINGS.RO UNIT, REFERENCE PLUMBING DRAWINGS.
3333 WALL MOUNT HUMIDIFIER PER MANUFACTURER'SWALL MOUNT HUMIDIFIER PER MANUFACTURER'SWALL MOUNT HUMIDIFIER PER MANUFACTURER'SWALL MOUNT HUMIDIFIER PER MANUFACTURER'S
RECOMMENDATIONS. FIELD COORDINATE EXACTRECOMMENDATIONS. FIELD COORDINATE EXACTRECOMMENDATIONS. FIELD COORDINATE EXACTRECOMMENDATIONS. FIELD COORDINATE EXACT
LOCATION.LOCATION.LOCATION.LOCATION.
4444 FM200 SYSTEM, REFERENCE FIRE PROTECTIONFM200 SYSTEM, REFERENCE FIRE PROTECTIONFM200 SYSTEM, REFERENCE FIRE PROTECTIONFM200 SYSTEM, REFERENCE FIRE PROTECTION
DRAWINGS.DRAWINGS.DRAWINGS.DRAWINGS.
6666 REGRIGERANT LINES UP TO LEVEL ABOVE.REGRIGERANT LINES UP TO LEVEL ABOVE.REGRIGERANT LINES UP TO LEVEL ABOVE.REGRIGERANT LINES UP TO LEVEL ABOVE.
CONTINUE SIZE AND INSTALL REFRIGERANT LINESCONTINUE SIZE AND INSTALL REFRIGERANT LINESCONTINUE SIZE AND INSTALL REFRIGERANT LINESCONTINUE SIZE AND INSTALL REFRIGERANT LINES
PER MANUFACTURER'S REQUIREMENTS.PER MANUFACTURER'S REQUIREMENTS.PER MANUFACTURER'S REQUIREMENTS.PER MANUFACTURER'S REQUIREMENTS.
REFERENCE DRAWING MP113A FORREFERENCE DRAWING MP113A FORREFERENCE DRAWING MP113A FORREFERENCE DRAWING MP113A FOR
CONTINUATION.CONTINUATION.CONTINUATION.CONTINUATION.
7777 EXISTING 1-1/4" HWS/R PIPING TO REMAIN AND BEEXISTING 1-1/4" HWS/R PIPING TO REMAIN AND BEEXISTING 1-1/4" HWS/R PIPING TO REMAIN AND BEEXISTING 1-1/4" HWS/R PIPING TO REMAIN AND BE
REPURPOSED AS CHWS/R.REPURPOSED AS CHWS/R.REPURPOSED AS CHWS/R.REPURPOSED AS CHWS/R.
8888 1" CHWS/R UP TO LEVEL ABOVE. REFERENCE1" CHWS/R UP TO LEVEL ABOVE. REFERENCE1" CHWS/R UP TO LEVEL ABOVE. REFERENCE1" CHWS/R UP TO LEVEL ABOVE. REFERENCE
DRAWING MP113a FOR CONTINUATION.DRAWING MP113a FOR CONTINUATION.DRAWING MP113a FOR CONTINUATION.DRAWING MP113a FOR CONTINUATION.
9999 4" HWS/R PIPING UP FROM LEVEL BELOW. AFTER4" HWS/R PIPING UP FROM LEVEL BELOW. AFTER4" HWS/R PIPING UP FROM LEVEL BELOW. AFTER4" HWS/R PIPING UP FROM LEVEL BELOW. AFTER
3" BRANCH TAKE-OFF CONTINUE 4" HWS/R UP TO3" BRANCH TAKE-OFF CONTINUE 4" HWS/R UP TO3" BRANCH TAKE-OFF CONTINUE 4" HWS/R UP TO3" BRANCH TAKE-OFF CONTINUE 4" HWS/R UP TO
LEVEL ABOVE. REFERENCE DRAWINGS MP111aLEVEL ABOVE. REFERENCE DRAWINGS MP111aLEVEL ABOVE. REFERENCE DRAWINGS MP111aLEVEL ABOVE. REFERENCE DRAWINGS MP111a
AND MP113a FOR CONTINUATION.AND MP113a FOR CONTINUATION.AND MP113a FOR CONTINUATION.AND MP113a FOR CONTINUATION.
10101010 3-WAY HEATING WATER CONTROL VALVE.3-WAY HEATING WATER CONTROL VALVE.3-WAY HEATING WATER CONTROL VALVE.3-WAY HEATING WATER CONTROL VALVE.
11111111 3-WAY CHILLED WATER CONTROL VALVE AND3-WAY CHILLED WATER CONTROL VALVE AND3-WAY CHILLED WATER CONTROL VALVE AND3-WAY CHILLED WATER CONTROL VALVE AND
3-WAY HEATING WATER CONTROL VALVE.3-WAY HEATING WATER CONTROL VALVE.3-WAY HEATING WATER CONTROL VALVE.3-WAY HEATING WATER CONTROL VALVE.
12121212 TEMPERATURE SENSOR AND HUMIDISTAT TO BETEMPERATURE SENSOR AND HUMIDISTAT TO BETEMPERATURE SENSOR AND HUMIDISTAT TO BETEMPERATURE SENSOR AND HUMIDISTAT TO BE
CONNECTED TO DDC SYSTEM FOR MONITORINGCONNECTED TO DDC SYSTEM FOR MONITORINGCONNECTED TO DDC SYSTEM FOR MONITORINGCONNECTED TO DDC SYSTEM FOR MONITORING
ONLY.ONLY.ONLY.ONLY.
13131313 TEMPERATURE SENSOR TO BE CONNECTED TOTEMPERATURE SENSOR TO BE CONNECTED TOTEMPERATURE SENSOR TO BE CONNECTED TOTEMPERATURE SENSOR TO BE CONNECTED TO
DDC SYSTEM FOR MONITORING ONLY.DDC SYSTEM FOR MONITORING ONLY.DDC SYSTEM FOR MONITORING ONLY.DDC SYSTEM FOR MONITORING ONLY.
14141414 THIS AREA HAS NO CEILING AND IS OPEN TO THETHIS AREA HAS NO CEILING AND IS OPEN TO THETHIS AREA HAS NO CEILING AND IS OPEN TO THETHIS AREA HAS NO CEILING AND IS OPEN TO THE
STRUCTURE. IT IS THE INTENT THAT NO HYDRONICSTRUCTURE. IT IS THE INTENT THAT NO HYDRONICSTRUCTURE. IT IS THE INTENT THAT NO HYDRONICSTRUCTURE. IT IS THE INTENT THAT NO HYDRONIC
PIPING BE INSTALLED IN THIS AREA, NEW ORPIPING BE INSTALLED IN THIS AREA, NEW ORPIPING BE INSTALLED IN THIS AREA, NEW ORPIPING BE INSTALLED IN THIS AREA, NEW OR
EXISTING.EXISTING.EXISTING.EXISTING.
dbkbo^i=klqbp
A.A.A.A.ALL HWS AND HWR RUNOUTS TO VAV REHEAT ALL HWS AND HWR RUNOUTS TO VAV REHEAT ALL HWS AND HWR RUNOUTS TO VAV REHEAT ALL HWS AND HWR RUNOUTS TO VAV REHEAT
COILS TO BE 3/4" UNLESS OTHERWISE NOTED.COILS TO BE 3/4" UNLESS OTHERWISE NOTED.COILS TO BE 3/4" UNLESS OTHERWISE NOTED.COILS TO BE 3/4" UNLESS OTHERWISE NOTED.
ALL VAVR REHEAT COILS SHALL BE SERVED BY A ALL VAVR REHEAT COILS SHALL BE SERVED BY A ALL VAVR REHEAT COILS SHALL BE SERVED BY A ALL VAVR REHEAT COILS SHALL BE SERVED BY A
2222----WAY CONTROL VALVE UNLESS OTHERWISE WAY CONTROL VALVE UNLESS OTHERWISE WAY CONTROL VALVE UNLESS OTHERWISE WAY CONTROL VALVE UNLESS OTHERWISE
NOTED.NOTED.NOTED.NOTED.
WHERE UNISTRUTS ARE NOT LOCATED NOR WHERE UNISTRUTS ARE NOT LOCATED NOR WHERE UNISTRUTS ARE NOT LOCATED NOR WHERE UNISTRUTS ARE NOT LOCATED NOR
ACCESSIBLE IN THE BOTTOM OF STRUCTURAL ACCESSIBLE IN THE BOTTOM OF STRUCTURAL ACCESSIBLE IN THE BOTTOM OF STRUCTURAL ACCESSIBLE IN THE BOTTOM OF STRUCTURAL
CONCRETE WEBS, ALL ANCHORS AND SUPPORTS CONCRETE WEBS, ALL ANCHORS AND SUPPORTS CONCRETE WEBS, ALL ANCHORS AND SUPPORTS CONCRETE WEBS, ALL ANCHORS AND SUPPORTS
SHALL BE CONNECTED TO THE SIDES OF THE SHALL BE CONNECTED TO THE SIDES OF THE SHALL BE CONNECTED TO THE SIDES OF THE SHALL BE CONNECTED TO THE SIDES OF THE
WEBS. DO NOT ATTACH TO THE BOTTOM OF THE WEBS. DO NOT ATTACH TO THE BOTTOM OF THE WEBS. DO NOT ATTACH TO THE BOTTOM OF THE WEBS. DO NOT ATTACH TO THE BOTTOM OF THE
WEB IF THERE IS NO EXISTING UNISTRUT.WEB IF THERE IS NO EXISTING UNISTRUT.WEB IF THERE IS NO EXISTING UNISTRUT.WEB IF THERE IS NO EXISTING UNISTRUT.
B.B.B.B.
C.C.C.C.
16161616151515151414141413131313121212121111111110101010999988887777
KKKK
HHHH
FFFF
DDDD
BBBB
AAAA
256A
PREP
/
STORAGE
256B
OFFICE
256C
OFFICE
258
CLASSROOM
256
WRITING CENTER OPEN TUTORING
260
CLASSROOM
264
OFFICE
265
OFFICE
266
STUDY
267
STUDY
268
STUDY
269
STUDY
270
OPEN
TUTORING
CENTER
270G
STUDY
270H
STUDY
270J
STORAGE
272
CLASSROOM
274
CLASSROOM
276
CLASSROOM
278
CLASSROOM
282
MEN'S
RESTROOM
284
WOMEN'S
RESTROOM
288B
OFFICE
288A
STUDY
286
ADJUNCT
OFFICE
280
TR / COMM.
270C
PRE-FUNCTION
270D
PRE-FUNCTION
270E
PRE-FUNCTION
270B
PREP / STORAGE
270A
RECEPTION
2-U
HALL
2-I
ELECTRICAL
254
OPEN
TUTORING
2-Q
HALL
252A
STUDY
252B
STUDY
252G
PREP / STORAGE
252F
STORAGE
252E
OFFICE
252D
OFFICE
252C
STUDY
2-R
ELEV
252
STUDY
SKILLS
299
STOR
2-P
STAIR
288H
STORAGE
288G
STUDY
288F
STUDY
288E
STUDY
288D
STUDY 288C
OFFICE
288
ENGLISH
TRANSITION
CENTER
256A256A256A256A
VAVRVAVRVAVRVAVR
256B256B256B256B
VAVRVAVRVAVRVAVR
256C256C256C256C
VAVRVAVRVAVRVAVR 258258258258
VAVRVAVRVAVRVAVR
260260260260
VAVRVAVRVAVRVAVR
256256256256
VAVRVAVRVAVRVAVR
264264264264
VAVRVAVRVAVRVAVR
265265265265
VAVRVAVRVAVRVAVR
266266266266
VAVRVAVRVAVRVAVR
267267267267
VAVRVAVRVAVRVAVR
268268268268
VAVRVAVRVAVRVAVR
269269269269
VAVRVAVRVAVRVAVR
2222----WWWW
VAVRVAVRVAVRVAVR
270DD270DD270DD270DD
VAVRVAVRVAVRVAVR
270CC270CC270CC270CC
VAVRVAVRVAVRVAVR
3333----1111
VAVVAVVAVVAV
270BB270BB270BB270BB
VAVRVAVRVAVRVAVR
270F270F270F270F
VAVRVAVRVAVRVAVR
270AA270AA270AA270AA
VAVRVAVRVAVRVAVR
270G270G270G270G
VAVRVAVRVAVRVAVR
270H270H270H270H
VAVRVAVRVAVRVAVR
270J270J270J270J
VAVRVAVRVAVRVAVR
272B272B272B272B
VAVRVAVRVAVRVAVR
274274274274
VAVRVAVRVAVRVAVR
276276276276
VAVRVAVRVAVRVAVR
278278278278
VAVRVAVRVAVRVAVR
270D270D270D270D
VAVRVAVRVAVRVAVR
270A270A270A270A
VAVRVAVRVAVRVAVR
270B270B270B270B
VAVRVAVRVAVRVAVR
280A280A280A280A
SACSACSACSAC
286286286286
VAVRVAVRVAVRVAVR
288A288A288A288A
VAVRVAVRVAVRVAVR
284284284284
VAVRVAVRVAVRVAVR
288B288B288B288B
VAVRVAVRVAVRVAVR
288C288C288C288C
VAVRVAVRVAVRVAVR
288D288D288D288D
VAVRVAVRVAVRVAVR
288E288E288E288E
VAVRVAVRVAVRVAVR
288F288F288F288F
VAVRVAVRVAVRVAVR
288G288G288G288G
VAVRVAVRVAVRVAVR
2222----QQQQ
VAVRVAVRVAVRVAVR
288AA288AA288AA288AA
VAVRVAVRVAVRVAVR
288BB288BB288BB288BB
VAVRVAVRVAVRVAVR
252A252A252A252A
VAVRVAVRVAVRVAVR
252B252B252B252B
VAVRVAVRVAVRVAVR
252BB252BB252BB252BB
VAVRVAVRVAVRVAVR
299299299299
VAVRVAVRVAVRVAVR
252AA252AA252AA252AA
VAVRVAVRVAVRVAVR
252D252D252D252D
VAVRVAVRVAVRVAVR
252C252C252C252C
VAVRVAVRVAVRVAVR
252E252E252E252E
VAVRVAVRVAVRVAVR
252G252G252G252G
VAVRVAVRVAVRVAVR
254254254254
VAVRVAVRVAVRVAVR
2222----UUUU
VAVRVAVRVAVRVAVR
1" HWS/R1" HWS/R1" HWS/R1" HWS/R
3/4" HWS/R3/4" HWS/R3/4" HWS/R3/4" HWS/R
1" HWS/R1" HWS/R1" HWS/R1" HWS/R
1" HWS/R1" HWS/R1" HWS/R1" HWS/R 1" HWS/R1" HWS/R1" HWS/R1" HWS/R 3/4" HWS/R3/4" HWS/R3/4" HWS/R3/4" HWS/R
1111----1/4" HWS1/4" HWS1/4" HWS1/4" HWS1111----1/4" HWS/R1/4" HWS/R1/4" HWS/R1/4" HWS/R
1" HWS/R1" HWS/R1" HWS/R1" HWS/R
3/4" HWS/R3/4" HWS/R3/4" HWS/R3/4" HWS/R
1" HWS1" HWS1" HWS1" HWS
3/4" HWS3/4" HWS3/4" HWS3/4" HWS
3/4" HWS3/4" HWS3/4" HWS3/4" HWS
3/4" HWS/R3/4" HWS/R3/4" HWS/R3/4" HWS/R
1111----1/4" HWR1/4" HWR1/4" HWR1/4" HWR
1111----1/4" HWR1/4" HWR1/4" HWR1/4" HWR
3/4" HWS/R3/4" HWS/R3/4" HWS/R3/4" HWS/R
1" HWS/R1" HWS/R1" HWS/R1" HWS/R
1" HWS/R1" HWS/R1" HWS/R1" HWS/R
3/4" HWS/R3/4" HWS/R3/4" HWS/R3/4" HWS/R
3/4" HWS/R3/4" HWS/R3/4" HWS/R3/4" HWS/R
1111----1/4" HWS1/4" HWS1/4" HWS1/4" HWS
1111
1111
1111
1111
S
S
S S S S
S S
S
S
S
S
S
S
S
SS
S
S
S
S
S
S
S S S
S
S
S S
S
S
S S S
S
S
S
S
S
S
S
S
S
SSSS
S
S
S
S
S
280B280B280B280B
SACSACSACSAC
2222
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
Level 02 Area
B Mechanical
Piping
Remodel Plan
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
KEY PLAN
A
B
ao^tfkd=klqbp
0000555510101010 10101010 20202020
SCALE:SCALE:SCALE:SCALE:MP112bMP112bMP112bMP112b 1/8" = 1'1/8" = 1'1/8" = 1'1/8" = 1'----0"0"0"0"
ibsbi=O=^ob^=_=jb`e^kf`^i=mfmfkd=objlabi=mi^k1111
NOTE
# DESCRIPTION
1111 3-WAY HEATING WATER CONTROL VALVE.3-WAY HEATING WATER CONTROL VALVE.3-WAY HEATING WATER CONTROL VALVE.3-WAY HEATING WATER CONTROL VALVE.
2222 TEMPERATURE SENSOR TO BE CONNECTED TOTEMPERATURE SENSOR TO BE CONNECTED TOTEMPERATURE SENSOR TO BE CONNECTED TOTEMPERATURE SENSOR TO BE CONNECTED TO
DDC SYSTEM FOR MONITORING ONLY.DDC SYSTEM FOR MONITORING ONLY.DDC SYSTEM FOR MONITORING ONLY.DDC SYSTEM FOR MONITORING ONLY.
dbkbo^i=klqbp
A.A.A.A.ALL HWS AND HWR RUNOUTS TO VAV REHEAT ALL HWS AND HWR RUNOUTS TO VAV REHEAT ALL HWS AND HWR RUNOUTS TO VAV REHEAT ALL HWS AND HWR RUNOUTS TO VAV REHEAT
COILS TO BE 3/4" UNLESS OTHERWISE NOTED.COILS TO BE 3/4" UNLESS OTHERWISE NOTED.COILS TO BE 3/4" UNLESS OTHERWISE NOTED.COILS TO BE 3/4" UNLESS OTHERWISE NOTED.
ALL VAVR REHEAT COILS SHALL BE SERVED BY A ALL VAVR REHEAT COILS SHALL BE SERVED BY A ALL VAVR REHEAT COILS SHALL BE SERVED BY A ALL VAVR REHEAT COILS SHALL BE SERVED BY A
2222----WAY CONTROL VALVE UNLESS OTHERWISE WAY CONTROL VALVE UNLESS OTHERWISE WAY CONTROL VALVE UNLESS OTHERWISE WAY CONTROL VALVE UNLESS OTHERWISE
NOTED.NOTED.NOTED.NOTED.
WHERE UNISTRUTS ARE NOT LOCATED NOR WHERE UNISTRUTS ARE NOT LOCATED NOR WHERE UNISTRUTS ARE NOT LOCATED NOR WHERE UNISTRUTS ARE NOT LOCATED NOR
ACCESSIBLE IN THE BOTTOM OF STRUCTURAL ACCESSIBLE IN THE BOTTOM OF STRUCTURAL ACCESSIBLE IN THE BOTTOM OF STRUCTURAL ACCESSIBLE IN THE BOTTOM OF STRUCTURAL
CONCRETE WEBS, ALL ANCHORS AND SUPPORTS CONCRETE WEBS, ALL ANCHORS AND SUPPORTS CONCRETE WEBS, ALL ANCHORS AND SUPPORTS CONCRETE WEBS, ALL ANCHORS AND SUPPORTS
SHALL BE CONNECTED TO THE SIDES OF THE SHALL BE CONNECTED TO THE SIDES OF THE SHALL BE CONNECTED TO THE SIDES OF THE SHALL BE CONNECTED TO THE SIDES OF THE
WEBS. DO NOT ATTACH TO THE BOTTOM OF THE WEBS. DO NOT ATTACH TO THE BOTTOM OF THE WEBS. DO NOT ATTACH TO THE BOTTOM OF THE WEBS. DO NOT ATTACH TO THE BOTTOM OF THE
WEB IF THERE IS NO EXISTING UNISTRUT.WEB IF THERE IS NO EXISTING UNISTRUT.WEB IF THERE IS NO EXISTING UNISTRUT.WEB IF THERE IS NO EXISTING UNISTRUT.
B.B.B.B.
C.C.C.C.
1111
GGGG
JJJJ
LLLL
MMMM
NNNN
PPPP
QQQQ
EEEE
CCCC
2222 3333 4444 5555
1111
DXFCUDXFCUDXFCUDXFCU
1111
(CONDENSING(CONDENSING(CONDENSING(CONDENSING
UNIT ON ROOF)UNIT ON ROOF)UNIT ON ROOF)UNIT ON ROOF)
342
(
QUIET
)
OPEN
STUDY
340
STUDY
(SM)
338
STUDY
(SM)
336
STUDY
(SM)
334
STUDY
(SM)
332
STUDY
(SM)
330
STUDY
(SM)
324B
ELECTRICAL
324A
MAC
EQUIP
322
OFFICE
320
STUDY
(SM)
324
MAC
LAB
326
STUDY
(LG)
328
STUDY
(LG)
342
(
QUIET
)
OPEN
STUDY
3-F
STAIR
3-G
ELEV
344
FAMILY
STUDY
344C
KIDS
PLAY
344B
RESTROOM
344A
MOTHERS
ROOM
350
TEST
RM
348
TEST
RM
346
TEST
RM
352
STORAGE
364
ELEC
356
TEST
RM
358
TEST
RM
360
TEST
RM
362
OPEN
STUDY
370
TEST
RM
372
TEST
RM
374
TEST
RM
368
MENS
366
WOMENS
376
Janitors
Closet
224f
Room
3-B
STAIR
1
383
OPEN
STUDY
318
STUDY
(SM)
316
STUDY
(SM)
314
STUDY
(SM)
312
OFFICE
310
OFFICE
224g
Room
224h
Room
3-C
STAIRS
308
ELECTRICAL
306
STORAGE
304
STUDY
(MED)302
STUDY
(MED)
-
Bridge
Connection
3-A
BRIDGE
CONNECTION
342A342A342A342A
VAVRVAVRVAVRVAVR
342D342D342D342D
VAVRVAVRVAVRVAVR
344344344344
VAVRVAVRVAVRVAVR
344A344A344A344A
VAVRVAVRVAVRVAVR
344C344C344C344C
VAVRVAVRVAVRVAVR
352352352352
VAVRVAVRVAVRVAVR
346346346346
VAVRVAVRVAVRVAVR
362362362362
VAVRVAVRVAVRVAVR
360360360360
VAVRVAVRVAVRVAVR
342E342E342E342E
VAVRVAVRVAVRVAVR
342B342B342B342B
VAVRVAVRVAVRVAVR
338338338338
VAVRVAVRVAVRVAVR
340340340340
VAVRVAVRVAVRVAVR
336336336336
VAVRVAVRVAVRVAVR
334334334334
VAVRVAVRVAVRVAVR
332332332332
VAVRVAVRVAVRVAVR
330330330330
VAVRVAVRVAVRVAVR
342C342C342C342C
VAVRVAVRVAVRVAVR
342F342F342F342F
VAVRVAVRVAVRVAVR
324AA324AA324AA324AA
VAVRVAVRVAVRVAVR
324BB324BB324BB324BB
VAVRVAVRVAVRVAVR
326326326326
VAVRVAVRVAVRVAVR
328328328328
VAVRVAVRVAVRVAVR
378378378378
VAVRVAVRVAVRVAVR
374374374374
VAVRVAVRVAVRVAVR
368368368368
VAVRVAVRVAVRVAVR
366366366366
VAVRVAVRVAVRVAVR
300A300A300A300A
VAVRVAVRVAVRVAVR
300C300C300C300C
VAVRVAVRVAVRVAVR
320320320320
VAVRVAVRVAVRVAVR
322322322322
VAVRVAVRVAVRVAVR
324B324B324B324B
VAVRVAVRVAVRVAVR
318318318318
VAVRVAVRVAVRVAVR
316316316316
VAVRVAVRVAVRVAVR
314314314314
VAVRVAVRVAVRVAVR
312312312312
VAVRVAVRVAVRVAVR
310310310310
VAVRVAVRVAVRVAVR
300B300B300B300B
VAVRVAVRVAVRVAVR
300D300D300D300D
VAVRVAVRVAVRVAVR 3333----AAAA
VAVRVAVRVAVRVAVR
304304304304
VAVRVAVRVAVRVAVR
306306306306
VAVRVAVRVAVRVAVR 302302302302
VAVRVAVRVAVRVAVR
2222
3333
4" HWR4" HWR4" HWR4" HWR
4" HWS4" HWS4" HWS4" HWS
ISOLATION BUTTERFLYISOLATION BUTTERFLYISOLATION BUTTERFLYISOLATION BUTTERFLY
VALVE, TYPICALVALVE, TYPICALVALVE, TYPICALVALVE, TYPICAL
3/4" HWS/R3/4" HWS/R3/4" HWS/R3/4" HWS/R
3/4" HWS/R3/4" HWS/R3/4" HWS/R3/4" HWS/R
3/4" HWS/R3/4" HWS/R3/4" HWS/R3/4" HWS/R
1" HWS/R1" HWS/R1" HWS/R1" HWS/R
3/4" HWS/R3/4" HWS/R3/4" HWS/R3/4" HWS/R
1" HWS/R1" HWS/R1" HWS/R1" HWS/R
1" HWS/R1" HWS/R1" HWS/R1" HWS/R
1" CHWS/R1" CHWS/R1" CHWS/R1" CHWS/R
3/4" HWS/R3/4" HWS/R3/4" HWS/R3/4" HWS/R
3/4" HWS/R3/4" HWS/R3/4" HWS/R3/4" HWS/R
3/4" HWS/R3/4" HWS/R3/4" HWS/R3/4" HWS/R
1" HWS1" HWS1" HWS1" HWS
3333
FCUFCUFCUFCU
4444
S
SSS
S
S S
SS
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S S
S S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
5555 5555
5555
5555
5555
5555
55555555
5555
5555
1111----1/2"1/2"1/2"1/2"
3"3"3"3"
6666
1" HWS/R1" HWS/R1" HWS/R1" HWS/R
5555
6666
6666
6666
4" HWR4" HWR4" HWR4" HWR
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
Level 03 Area
A Mechanical
Piping
Remodel Plan
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
KEY PLAN
A
B
ao^tfkd=klqbp
0000555510101010 10101010 20202020
SCALE:SCALE:SCALE:SCALE:MP113aMP113aMP113aMP113a 1/8" = 1'1/8" = 1'1/8" = 1'1/8" = 1'----0"0"0"0"
ibsbi=P=^ob^=^=jb`e^kf`^i=mfmfkd=objlabi=mi^k1111
NOTE
# DESCRIPTION
1111 REFRIGERANT LINES UP FROM LEVEL BELOW.REFRIGERANT LINES UP FROM LEVEL BELOW.REFRIGERANT LINES UP FROM LEVEL BELOW.REFRIGERANT LINES UP FROM LEVEL BELOW.
CONTINUE UP WALL AND THROUGH ROOF TOCONTINUE UP WALL AND THROUGH ROOF TOCONTINUE UP WALL AND THROUGH ROOF TOCONTINUE UP WALL AND THROUGH ROOF TO
DXFCU-1 CONDENSING UNIT ON ROOF ABOVE.DXFCU-1 CONDENSING UNIT ON ROOF ABOVE.DXFCU-1 CONDENSING UNIT ON ROOF ABOVE.DXFCU-1 CONDENSING UNIT ON ROOF ABOVE.
SIZE AND INSTALL REFRIGERANT LINES PERSIZE AND INSTALL REFRIGERANT LINES PERSIZE AND INSTALL REFRIGERANT LINES PERSIZE AND INSTALL REFRIGERANT LINES PER
MANUFACTURER'S REQUIREMENTS. SEEMANUFACTURER'S REQUIREMENTS. SEEMANUFACTURER'S REQUIREMENTS. SEEMANUFACTURER'S REQUIREMENTS. SEE
DRAWINGS MP112a AND MH104a FORDRAWINGS MP112a AND MH104a FORDRAWINGS MP112a AND MH104a FORDRAWINGS MP112a AND MH104a FOR
CONTINUATION.CONTINUATION.CONTINUATION.CONTINUATION.
2222 1" CHWS/R UP FROM LEVEL BELOW. REFERENCE1" CHWS/R UP FROM LEVEL BELOW. REFERENCE1" CHWS/R UP FROM LEVEL BELOW. REFERENCE1" CHWS/R UP FROM LEVEL BELOW. REFERENCE
DRAWING MP112a FOR CONTINUATION.DRAWING MP112a FOR CONTINUATION.DRAWING MP112a FOR CONTINUATION.DRAWING MP112a FOR CONTINUATION.
3333 4" HWS/R PIPING UP FROM LEVEL BELOW.4" HWS/R PIPING UP FROM LEVEL BELOW.4" HWS/R PIPING UP FROM LEVEL BELOW.4" HWS/R PIPING UP FROM LEVEL BELOW.
REFERENCE DRAWING MP112a FORREFERENCE DRAWING MP112a FORREFERENCE DRAWING MP112a FORREFERENCE DRAWING MP112a FOR
CONTINUATION.CONTINUATION.CONTINUATION.CONTINUATION.
4444 3-WAY HEATING WATER CONTROL VALVE.3-WAY HEATING WATER CONTROL VALVE.3-WAY HEATING WATER CONTROL VALVE.3-WAY HEATING WATER CONTROL VALVE.
5555 THIS AREA HAS NO CEILING AND IS OPEN TO THETHIS AREA HAS NO CEILING AND IS OPEN TO THETHIS AREA HAS NO CEILING AND IS OPEN TO THETHIS AREA HAS NO CEILING AND IS OPEN TO THE
STRUCTURE. IT IS THE INTENT THAT NO HYDRONICSTRUCTURE. IT IS THE INTENT THAT NO HYDRONICSTRUCTURE. IT IS THE INTENT THAT NO HYDRONICSTRUCTURE. IT IS THE INTENT THAT NO HYDRONIC
PIPING BE INSTALLED IN THIS AREA, NEW ORPIPING BE INSTALLED IN THIS AREA, NEW ORPIPING BE INSTALLED IN THIS AREA, NEW ORPIPING BE INSTALLED IN THIS AREA, NEW OR
EXISTING.EXISTING.EXISTING.EXISTING.
6666 RELOCATE EXISTING MAIN HEATING WATER PIPINGRELOCATE EXISTING MAIN HEATING WATER PIPINGRELOCATE EXISTING MAIN HEATING WATER PIPINGRELOCATE EXISTING MAIN HEATING WATER PIPING
AS REQUIRED TO KEEP PIPING OUT OF OPENAS REQUIRED TO KEEP PIPING OUT OF OPENAS REQUIRED TO KEEP PIPING OUT OF OPENAS REQUIRED TO KEEP PIPING OUT OF OPEN
CEILING AREA.CEILING AREA.CEILING AREA.CEILING AREA.
1111
GGGG
JJJJ
EEEE
CCCC
2222 3333
FCPFCPFCPFCP
1111
1111----1/2" CHWR1/2" CHWR1/2" CHWR1/2" CHWR
1111----1/2" CHWS1/2" CHWS1/2" CHWS1/2" CHWS
2222----1/2" CHWS1/2" CHWS1/2" CHWS1/2" CHWS
1111
2222
2222
6" HWR6" HWR6" HWR6" HWR
6" HWS6" HWS6" HWS6" HWS
4" HWR4" HWR4" HWR4" HWR
4" HWS4" HWS4" HWS4" HWS
ISOLATION BUTTERFLYISOLATION BUTTERFLYISOLATION BUTTERFLYISOLATION BUTTERFLY
VALVE, TYPICALVALVE, TYPICALVALVE, TYPICALVALVE, TYPICAL
VFDVFDVFDVFD
8888
VFDVFDVFDVFD
7777
VFDVFDVFDVFD
9999
VFDVFDVFDVFD
10101010
HWPHWPHWPHWP
10101010
HWPHWPHWPHWP
9999
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
Enlarged
Level 00 Area
A Mechanical
Room
Remodel Plan
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
ao^tfkd=klqbp
00002.52.52.52.55555 5555 10101010
SCALE:SCALE:SCALE:SCALE:MP401MP401MP401MP401 1/4" = 1'1/4" = 1'1/4" = 1'1/4" = 1'----0"0"0"0"
bki^odba=ibsbi=MM=^ob^=^=jb`e^kf`^i=ollj=objlabi=mi^k1111
NOTE
#DESCRIPTION
1111 4" HWS/R PIPING UP TO LEVEL ABOVE.4" HWS/R PIPING UP TO LEVEL ABOVE.4" HWS/R PIPING UP TO LEVEL ABOVE.4" HWS/R PIPING UP TO LEVEL ABOVE.
REFERENCE DRAWING MP111a FORREFERENCE DRAWING MP111a FORREFERENCE DRAWING MP111a FORREFERENCE DRAWING MP111a FOR
CONTINUATION.CONTINUATION.CONTINUATION.CONTINUATION.
2222 EXISTING 2-1/2" HWS/R PIPING TO REMAIN AND BEEXISTING 2-1/2" HWS/R PIPING TO REMAIN AND BEEXISTING 2-1/2" HWS/R PIPING TO REMAIN AND BEEXISTING 2-1/2" HWS/R PIPING TO REMAIN AND BE
REPURPOSED AS CHWS/R.REPURPOSED AS CHWS/R.REPURPOSED AS CHWS/R.REPURPOSED AS CHWS/R.
KEY PLAN
A
B
L
S
obcofdbo^kq=mfmfkd=ibdbka
clo=p`r=lk=ollc
INSULATE FULL LENGTH
THE CONTRACTOR ALONG WITH HIS EQUIPMENT SUPPLIER SHALL SUBMIT
COMPLETE REFRIGERATION PIPING SHOP DRAWING SHOWING SIZES, TRAPS,
PITCHES, VALVES, FILTER/DRYER, SEPARATORS, SITE GLASSES, PIPE
LENGTHS AND ELEVATIONS, ETC. THE DRAWING SHALL BE BASED ON
ACTUAL BUILDING CONDITIONS. TRAP AS REQUIRED TO ACCOMODATE
NOTE:
MOISTURE INDICATING SIGHT GLASS
LIQUID LINE
SUCTION LINE
DIRECTION OF SLOPE DOWN
FLEXIBLE CONNECTION
EXPANSION VALVE
REFRIGERANT SHUT-OFF VALVE
DESCRIPTIONSYMBOL
EVAP. COIL
SIGHT GLASS
EXTERNAL EQUALIZER
THERMAL EXPANSION VALVE
DISTRIBUTOR, TYPICAL
FACTORY FABRICATED
TRAP, ONE PIECE
(IF REQUIRED)
S
SHUT-OFF, TYPICAL
LSEE DETAIL 3/M5.2
FILTER DRYER
BELOW HORIZONTAL
THERMAL BULB @ 45°
F
THERMAL BULB, LOCATE
AS CLOSE TO COIL AS
POSSIBLE
UNIT CURB
FLEXIBLE CONNECTOR, TYPICAL
SIGHT GLASS, TYPICAL
LIQUID CHARGING VALVE
CONDENSING UNIT
PIPE PENETRATION CURB
SEE DETAIL 2/M5.2
TYPICAL
45°
ALL SUPPORT MEMBERS, BOLTS, NUTS,
REDWOOD PAD. SIZE PAD TO NOT VOID
BOLT SUPPORT TO TREATED WOOD OR
6" MIN.PLATES ETC. TO BE GALVANIZED.
PIPING, CENTER ON SUPPORT
SUPPORT ADDITIONAL
LENGTH AS REQUIRED TO
INSULATION, USE 20 GA. GALV.
LINES AT EACH SUPPORT, ON
INSULATION ON ALL SUCTION
POST.
SLEEVE x 6" LONG.
THE OUTSIDE OF THE
VARIES
WITH UNISTRUT UNICUSHION
FROM HANGER AND CLAMP
LIQUID PIPING ISOLATE PIPING
1 5/8" DOUBLE CHANNEL
NOTE:
SHEET METAL COVER
18 GAUGE GALVANIZED
ROOF
ROOF WARRANTY.
UNISTRUT CHANNEL
1-5/8" P-1000
SUCTION LINE
LIQUID LINE
PIPE CLAMP OR EQUAL (TYPICAL)
TO SUPPORTS WITH "UNISTRUT"
SECURE REFRIGERANT PIPING
INSULATION
1/2" THICK
6" LONG (TYP.) LINES
STEEL JOIST
CONNECT TO
"UNISTRUT" CHANNEL
HANGER ROD
EXTEND FOR ADDITIONAL
STEEL JOIST
HANGER SPACE.
20 GAUGE GALV. SLEEVE
INSULATION ON SUCTION
WITH CHANNEL CLAMP (TYP.)
SECURE PIPING TO SUPPORT
CUSHION (TYP.)
THERMOPLASTIC ELASTOMER
FROM HANGER AND CLAMP WITH
TYPICAL REFRIGERANT PIPE
LIQUID PIPING. ISOLATE PIPING
EXPANSION BOLT
INSULATION
ROOF DECK, SEE
ARCHITECTURAL
FLAT LOCK SOLDERED
1-1/2" WOOD SCREWS W/
NEOPRENE WASHERS
2"x12" REDWOOD FRAME.
NAIL TOGETHER WITH
2"x2" ANGLE IRON
ANCHOR TO ROOF WITH
16d NAILS
SEAMS (TYPICAL)
24 GA. GALVANIZED
METAL COUNTERFLASH
METAL
24 GA. GALVANIZED
FLAT LOCK SOLDERED
ROOFING, SEE
ARCH. PLANS
SEAMS (TYPICAL)
8" MIN.
SEAL ALL AROUND
PENETRATION
NOTE:COORDINATE WITH ROOF MANUFACTURER'S WARRANTY.
COMPLY WITH WARRANTY REQUIREMENTS.
2"
WOOD
TREATED SEAL WEATHER TIGHT MIN.
12"
2" TREATED WOOD
3/4" TREATED PLYWOOD
COVER
MEMBRANE OR CURB
PENETRATE ROOF
ALL BOLTS THAT
PROVIDE GASKETS ON
CONDENSING UNIT
COVER/COUNTERFLASHING
TO CURB
CONDENSING UNIT
SECURELY ANCHOR
18 GA. GALV. CURB
CANT STRIP ALL AROUND
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
Mechanical
Piping Details
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
SCALE: NONESCALE: NONESCALE: NONESCALE: NONEMP501MP501MP501MP501
obcofdbo^kq=mfmfkd=p`ebj^qf`1111
SCALE: NONESCALE: NONESCALE: NONESCALE: NONEMP501MP501MP501MP501
obcofdbo^kq=mfmb=prmmloq=abq^fi2222
SCALE: NONESCALE: NONESCALE: NONESCALE: NONEMP501MP501MP501MP501
obcofdbo^kq=mfmb=sboqf`^i=prmmloq=abq^fi3333
SCALE: NONESCALE: NONESCALE: NONESCALE: NONEMP501MP501MP501MP501
prpmbkaba=obcofdbo^kq=mfmb=prmmloq=^q=qorpp=abq^fi4444
SCALE: NONESCALE: NONESCALE: NONESCALE: NONEMP501MP501MP501MP501
mfmfkd=ollc=mbkbqo^qflk=abq^fi5555
SCALE: NONESCALE: NONESCALE: NONESCALE: NONEMP501MP501MP501MP501
`lkabkpfkd=rkfq=jlrkqfkd=abq^fi6666
WALL, CEILING
STRUCTURAL
OF THE DIMENSION TABULATED FOR THE LARGER PIPE, PLUS ONE-HALF OF THE
DIMENSION TABULATED FOR THE SMALLER PIPE, TO DETERMINE THE MINIMUM
NOTES:
OR OTHER
MEMBER
3 1/2"
4 1/2"
DIMENSION
MINIMUM CENTERLINE SPACING
5 1/2"
6 1/2"
2"-2 1/2"
6"
8"
3"-3 1/2"
5"
4"
PIPE SIZE
1"-1 1/4"-1 1/2"
1/2"-3/4"
NOMINAL
8}"
9"
10"
8"
7 1/2"
16"
14"
13"
12"
11"
DIMENSION
5"
7"
6"
A
DIMENSION
6"
8"
10"
B
INSULATED PIPE
A B C C
5"
8"
7 1/2"
6"
5"
11"
9"
7"
6"
DIMENSION
4"
C D
3"
4"
OR OTHER
MEMBER
STRUCTURAL
WALL, CEILING
BARE PIPE
E D
1. DIM "C": WHERE PIPES OF DIFFERENT SIZE ARE RUN PARALLEL, USE ONE-HALF
CENTER LINE SPACING BETWEEN ADJACENT RUNS.
2. TABLE APPLIES ONLY TO PIPING RUNS WHICH ARE NOT DIMENSIONED ON THE
PIPING PLANS.
~~
~
SPLIT RING
ROD SIZE
HANGERS SIZES AND SPACING ARE FOR SINGLE PIPES. HANGER ROD LOADING
FOR TRAPEZE HANGERS SHALL NOT EXCEED THE TOTAL LOADING INDICATED.
IF SMALLER ROD SIZE IS USED, DECREASE MAXIMUN SPACING SO THAT TOTAL
LOADING IS NOT EXCEEDED. SUPPORT FROM STRUCTURE PANEL POINTS.
UP TO 2000 LBS. USE
1" AND SMALLER
MAX. SPACING
NOTE:
5" - 8"
2-1/2" - 4"
1-1/4" - 2"
PIPE SIZE
12
16
8
10
TRAPEZE HANGER
PIPE LOAD
2.5/20
50/800
20/240
6/60
WEIGHT/FT. TOTAL
P-1001.
DOUBLE NUT HANGER
"UNISTRUT" 1-5/8"
UP TO 700 LBS. USE
P-1000, FOR LOADING
CHANNEL-FOR LOADING
ROD. TYPICAL
3/8"
5/8"
7/8"
3/8"
CALSIUM SILICATE THERMAL
INSULATION INSERT 360 DEG.
COVERAGE/ENCASEMENT WITH
GALVANIZED PROTECTION
SHIELD, 360 DEG. COVERAGE/
ENCASEMENT
PIPE INSULATION
CLEVIS HANGER
INSERTS OR BEAM /
TRUSS CONNECTION
CINCH ANCHORS
WELDED STEEL
WALL BRACKET
ANGLE
ROD
ADJUSTABLE
PIPE STAND
THRU-BOLT
EYE BOLTS
TURNBUCKLE
U-BOLT
WALL BRACKET
U-BOLTS
STEEL OFFSET
CI
N
C
H
A
N
C
H
O
R
S
EYE BOLT
PIPE CLAMP
ROD
TURNBUCKLE
I-BEAM
STEEL PLATE
BLOCK WALL
CLAMPS
ANGLE
U-BOLTS
ROD
SPLIT RING
CLEVIS HANGER
INSERTS OR BEAM /
TRUSS CONNECTION
C-CLAMP
LOCK NUT
TYP.
STEEL CLEAVIS
FIVE PIPE DIAMETERS MINIMUM
FIVE PIPE DIAMETERS MINIMUM
FLOW VENTURI OR
BALANCING DEVICE
VALVE OR OTHER FITTING
DIRECTION OF FLOW
DIRECTION
OF FLOW
FITTING
VALVE OR OTHER
TWO PIPE DIAMETERS MINIMUM
FS
REDUCER (TYPICAL)
UNION (TYPICAL)
MAIN OR BRANCH LINE
BALL VALVE
AIR CHNAMER
1-1/4" x 12" LONG
HIGH POINT
3/8"
WALLS, USE ASG ACOUSTICAL SEALANT.
FOR PENETRATIONS THROUGH SOUND
NOTE:
STANDARD WEIGHT STEEL PIPE
SLEEVE OF SIZE TO PASS PIPE
FINISHED ESCUTCHEON PLATE
FLUSH AGAINST WALL AND OF
SIZE TO COMPLETELY COVER
OPENING
FINISHED WALL SURFACE
PIPING EXPOSED TO VIEWCONCEALED PIPING
TERMINATE SLEEVE FLUSH WITH
FINISHED WALL SURFACES
SEAL OR CAULK SLEEVES THRU
FIRE WALLS IN A SMOKE TIGHT
MANNER
PIPE AND INSULATION TO BE
CENTERED IN SLEEVE-DO NOT
SUPPORT PIPE FROM SLEEVE
INTERIOR WALLS
HWR
MANUAL AIR VENT
HWS
SHUT-OFF BALL VALVE (TYP.)
AIR
FLOW
PROVIDE 1/2" BALL
VALVE FOR EACH
VENT HEADER
COPPER TEE W/
THREADED INSERT
& P/T PLUG.
1/2" BALL VALVE
W/ HOSE END & CAP
2-WAY MODULATING CONTROL
VALVE W/ UNION ENDS
COPPER
PIPE
COPPER
PIPE
NOTES:
1. INSTALL VALVES AS CLOSE TO COIL AS POSSIBLE.
MIN. 5 PIPE DIAMETERS
REDUCER
W/ MEMORY STOP & INDICATOR,
P AT RATED FLOW
VENTURI FOR 20" TO 50" W.G.
WILL NOT BE ACCEPTED). SELECT
(REFRIGERATION FLARE CONNS.
VENTURI W/ SCHRADER VALVES
FLOWSET ACCUSETTER VALVE
THREADED TO
SWEAT CONN.
SWEAT CONN.
THREADED TO
& P/T PLUG.
THREADED INSERT
COPPER TEE W/
2. VALVE SHALL BE INSTALLED WITHIN 2'-0" OF VALVE .B A
B
A
VALVE W/ UNION ENDS
MIN. 5 PIPE DIAMETERS
3-WAY MODULATING CONTROL
A
SHUT-OFF BALL VALVE (TYP.)
VALVES (REFRIGERATION FLARE
BALANCING VALVE W/ SCHRADER
W/ MEMORY STOP & INDICATOR,
CIRCUIT BALANCE VALVE
CONNS. WILL NOT BE ACCEPTED).
W/ HOSE END & CAP
2. VALVES & SHALL BE INSTALLED WITHIN 2'-0" OF VALVE
1. INSTALL VALVES AS CLOSE TO COIL AS POSSIBLE.
THREADED TO SWEAT
NOTES:
CB
CONNECTION
FLOW
AIR
C
1/2" BALL VALVE
THREADED INSERT
& P/T PLUG.
BALL VALVE W/
MEMORY STOP &
COPPER TEE W/
INDICATOR
B
VENT HEADER
MANUAL AIR VENT
VALVE FOR EACH
PROVIDE 1/2" BALL
INSERT AND P/T PLUG
COPPER TEE WITH THREADED
THREADED TO SWEAT
CONNECTION
N.O.
N.
C
.
C
NOTES:
HWS
REDUCER
HWR
A
1.
2.
VALVE PORTING IS DIAGRAMTIC. FIELD VERIFY ACTUAL PORTING OF TO BE
INSTALLED VALVE(S) PRIOR TO INSTALLATION INSURING PROPER FLOW
PATTERN.
TYPICAL FOR VAVR HW COILS WHERE INDICATED ON DRAWINGS.
ANCHOR INTO WALL (3/8" DIA. x3")
UNISTRUT PIPE CLAMP
PIPE INSULATION
UNISTRUT CHANNEL
WALL
HIGH DENSITY CALCIUM SILICATE
INSULATION INSERT 360 DEG.
COVERAGE / ENCASEMENT
GALVANIZED PROTECTION
SHIELD. 360 DEG.
COVERAGE/ENCASEMENT
16 GAGE MINIMUM (TYP.)
CONCRETE SLAB
CHANNEL GALVANIZED
1-5/8" x 1-5/8" UNISTRUT
UNISTRUT PIPE CLAMP
BOLTS, 3" LONG.
2-3/8" DIA. EXPANSION
3/8" x 4" x 8" PLATE WITH
3" x 3" x 3/16" ANGLE
1/4
ADJUSTMENT OF TENSION
DOUBLE NUT TO ALLOW
PIPING
1/4
PIPING
HIGH DENSITY CALSIUM SILICATE
INSULATION INSERT, 360 DEG.
COVERAGE/ENCASEMENT (TYPICAL).
GALVANIZED PROTECTION SHIELD
360 DEG. COVERAGE/ENCASEMENT
(TYPICAL)
GALVANIZED
(GALVANIZED)
GALVANIZED
GALVANIZED
EXTERIOR PIPE
INSULATION WITH
EMBOSED ALUMINUM
JACKET
OVERALL SIZE AS REQUIRED BY
EQUIPMENT. 12"x12" MIN.
USE SPECIAL BASES WHERE CALLED2.
FOR.
PLASTER AFTER
STRIPPING FORM
NOTES:
1.
CHAMFER AROUND
4000 PSI CONCRETE
INTO FLOOR SLAB
DOWEL INTO FLOOR WITH
1/2" ALL-THREAD 12" O.C.
ANCHOR BOLTS THRU PAD
#3 RE-BAR 6" O.C.
TIE TO REBAR
BOTH WAYS
4" MIN. (6" FOR AIR
HANDLING UNITS)
DIVISION 26
REFERENCE
FA SPEED
120V POWER
SWITCH
JUNCTION
MOTOR
FAN
BOX
THERMOSTAT
MOUNTED
MOUNTED
UNIT
UNITT
RETURN AIR
SUPPLY AIR
AIR
FLOW
CH
W
R
CH
W
S
HW
R
HW
S
COIL CONDENSATE
TO DRAIN
DRAIN PAN
UNION (TYPICAL)AIR VENT VALVE
(TYPICAL)
3-WAY CONTROL
VALVE (TYPICAL)
CIRCUIT BALANCING
VALVE WITH BALL
VALVE SHUT-OFF
(TYPICAL)
CIRCUIT BALANCING
VALVE (TYPICAL)
Y-STRAINER (TYPICAL)
SHUT-OFF BALL VALVE
(TYPICAL)
REFERENCE DRAWINGS FOR REQUIRED
PIPE SIZES. REFERENCE DRAWINGS FOR
REQUIRED LEFT OR RIGHT HAND PIPING
CONNECTION.
GLASS WASHER WITH NUT ON
1/2" ALL-THREAD ROD SET
INTO INSERT IN FLOOR. 3/4"
SLEEVE THRU BASE, FIBER-
TOP TO RESTRAIN MOVEMENT
GUARD
REDUCER
GROOVED JOINT
BALANCE VALVE
BUTTERFLY VALVE
CHECK VALVE
COUPLINGS
VALVE (TYP.)
SUCTION DIFFUSER WITH
INTERNAL STRAINER
DRAIN (3/4" MIN.)
DRAIN LINE TO FLOOR
ADJUSTABLE SUPPORT
6" SPOOL PIECE
DRAIN VALVE
1/2" TYP.
PRESSURE GAUGE
BAR STOCK NEEDLE
CONCRETE HOUSEKEEPING
PAD SEE DETAIL 5/MP504 FOR
REINFORCEMENTS.
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
Mechanical
Piping Details
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
SCALE: NONESCALE: NONESCALE: NONESCALE: NONEMP502MP502MP502MP502
mfmb=`ib^o^k`b=a^q^=abq^fi1111
SCALE: NONESCALE: NONESCALE: NONESCALE: NONEMP502MP502MP502MP502
mfmb=e^kdbo=abq^fi2222
SCALE: NONESCALE: NONESCALE: NONESCALE: NONEMP502MP502MP502MP502
qvmf`^i=mfmb=prmmloqp=abq^fi3333
SCALE: NONESCALE: NONESCALE: NONESCALE: NONEMP502MP502MP502MP502
_^i^k`b=L=cilt=absf`b=fkpq^ii^qflk=abq^fi4444
SCALE: NONESCALE: NONESCALE: NONESCALE: NONEMP502MP502MP502MP502
j^kr^i=^fo=sbkq=abq^fi5555
SCALE: NONESCALE: NONESCALE: NONESCALE: NONEMP502MP502MP502MP502
mfmb=mbkbqo^qflk=abq^fi6666
SCALE: NONESCALE: NONESCALE: NONESCALE: NONEMP502MP502MP502MP502
OJt^v=s^s=eb^qfkd=`lfi=mfmfkd=abq^fi7777
SCALE: NONESCALE: NONESCALE: NONESCALE: NONEMP502MP502MP502MP502
PJt^v=s^s=eb^qfkd=`lfi=mfmfkd=abq^fi8888
SCALE: NONESCALE: NONESCALE: NONESCALE: NONEMP502MP502MP502MP502
t^ii=jlrkq=mfmb=prmmloq=abq^fi9999
SCALE: NONESCALE: NONESCALE: NONESCALE: NONEMP502MP502MP502MP502
buqboflo=mfmb=prmmloq=abq^fi10101010
SCALE: NONESCALE: NONESCALE: NONESCALE: NONEMP502MP502MP502MP502
`lk`obqb=_^pb=L=elrpbhbbmfkd=m^a=abq^fi11111111
SCALE: NONESCALE: NONESCALE: NONESCALE: NONEMP502MP502MP502MP502
eb^qfkd=^ka=`llifkd=c^k=`lfi=rkfq=PJt^v=mfmfkd=abq^fi13131313
SCALE: NONESCALE: NONESCALE: NONESCALE: NONEMP502MP502MP502MP502
mrjm=^ka=_^pb=abq^fi12121212
DP DP
S
S
S
S
V
VD
V
VD
(E)8"
(E)8" CHWR
(E)8" CHWS
(E)8" CHWR
(E)8"
(E)3/4"
(E)8" CHWS
(E)8"(E)8" CHWR
(E)8" CHWS(E)8"
(E)8"
(E)6"
(E)8" CHWR
(E)8" CHWS
(E)DCV-1
(E)MCV-1
(E)1"
(E)3/4"
(E)SUCTION
DIFFUSER
(E)CHW GLYCOL
MAKEUP UNIT
(E)CHWP-8 (E)CHWP-7
(E)BUTTERFLY
VALVE (TYP)
(E)R-8
ROLAIRTROL
(E)DRAIN TO GMU
(E)6" CHWS/R TO SECONDARY
SYSTEM SERVING THE EAST WING
BUILDING.
(E)8" CHWS/R TO ICE BANK
STORAGE TANKS. SEE ICE BANK
PIPING FLOW DIAGRAM ABOVE FOR
CONTINUATION.
(E)TRIPLE DUTY
VALVE (TYP)
(E)PACKAGED CHILLER
(E)REDUCED PRESSURE
BACKFLOW PREVENTER
(E)COMBINATION
PRESSURE REGULATOR
AND REDUCING VALVE
(E)SIGHT GLASS (E)24 GALLON EXPANSION
TANK WITH ATF-12 TANK
FITTING MOUNTED ON STAND
(E)B&G DT-2 DRAIN-AIR
CHARGER VALVE
(E)DRAIN TO GMU
(E)VENT TO GMU
(E)BYPASS VALVE
GMU
CONTROL
PANEL
(E)6"
(E)6"
(E)6"
(E)6"
(E)SECONDARY BYPASS VALVE
(E)FLEX
CONNECTION
(TYP)
(E)CONCRETE
HOUSEKEEPING
PAD (TYP)
(E)SUCTION
DIFFUSER
(E)6" CHWS/R TO
SECONDARY SYSTEM
SERVING THE ADJACENT
WEST WING AIR
HANDLING UNIT.
(LAYOUT SIMILAR TO
EAST WING AHU)
(E)CHWP-5(E)CHWP-6
(E)2-1/2" CHWR
(E)2-1/2" CHWS
(E)PRESSURE
GAUGE (TYP)
FCP
1
1-1/2" CHWS
1-1/2" CHWR
TERMINATE WITH
HOSE CONNECTION
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
CHILLED
WATER
SYSTEM
FLOW
DIAGRAM
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
SCALE: NONESCALE: NONESCALE: NONESCALE: NONEMP601MP601MP601MP601
^ob^=?^?=`efiiba=t^qbo=pvpqbj=cilt=af^do^j1111
DPDP
(E) HWS
(E) HWR
(E) HWR
S
V
V
V
PS
PS
S
(E) 3/4" CW LINE
(E)3/4"
(E)1"
(E)1"
(E)1"
FROM PRV
ASSEMBLY SRV.
(E) HEATING COIL
(E) 3"
(E)
2-1/2"
(E)
2-1/2"
(E)3/4"
(E) HEATING COIL
(E) 3"
(E)
2-1/2"
(E)
2-1/2"
(E)3/4"
(E) HEATING COIL
(E) 3"
(E)
2-1/2"
(E)
2-1/2"
(E)3/4"
(E) 3"(E) 6"
(E) GLYCOL MAKEUP UNIT
(E) 6" (E) 6"
FRAME HEATING WATER
(E) PACKAGED PLATE &
HEAT EXCHANGER SYSTEM
(E)3/4"
(E) UP IN CHASE TO REHEAT COILS
(E) 6"(E) 6"(E) 6"(E) 6"
(E) 6"
(E) 6"
(E) 4"
(E)3/4"
(E)3/4"
(E) 4"
(E)2-1/2"
(E) 4"(E) 4"
RETURN UNIT
(E) CONDENSATE (E) FLASH TANK
(E) VENT UP IN CHASE
(E) 4"
(E) 4"
(E) 6"
(E) 1"
(E) 3"
(E) 1-1/2"
(E) 3"
(E) 2"
(E) 2"
(E) PRESSURE SENSOR,
0-150 PSI
(E) 1-1/2"
(E) PRESSURE SENSOR,
0-40 PSI
WATER PLATE & FRAME
(E) PACKAGED DOMESTIC
HEAT EXCHANGER SYSTEM
(E) 6"
(E) 6" (E) AIR PURGER
IN-LINE
CIRC. PUMP
(E) ICP-5
(E)REDUCED PRESSURE
BACKFLOW PREVENTER
(E)COMBINATION
PRESSURE REGULATOR
AND REDUCING VALVE
(E)3/4"
(E)SIGHT GLASS (E)24 GALLON EXPANSION
TANK WITH ATF-12 TANK
FITTING MOUNTED ON STAND
(E)B&G DT-2 DRAIN-AIR
CHARGER VALVE
(E)DRAIN TO GMU
(E)VENT TO GMU
(E)BYPASS VALVE
(E)1" DHWR
PUMP
VAV REHEAT
BCV-1
HWP
10 COIL PUMP
AHU HWHWP
9
1111
2222
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
STEAM TO
HEATING
WATER
FLOW
DIAGRAM
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
SCALE: NONESCALE: NONESCALE: NONESCALE: NONEMP602MP602MP602MP602
^ob^=?^?=pqb^j=ql=eb^qfkd=t^qbo=cilt=af^do^j1111
ao^tfkd=klqbp
NOTE
#DESCRIPTION
1111 REPLACE EXISTING PNEUMATIC 3-WAY CONTROLREPLACE EXISTING PNEUMATIC 3-WAY CONTROLREPLACE EXISTING PNEUMATIC 3-WAY CONTROLREPLACE EXISTING PNEUMATIC 3-WAY CONTROL
VALVE WITH NEW 3-WAY VALVE AS SCHEDULED.VALVE WITH NEW 3-WAY VALVE AS SCHEDULED.VALVE WITH NEW 3-WAY VALVE AS SCHEDULED.VALVE WITH NEW 3-WAY VALVE AS SCHEDULED.
REWORK PIPING AS REQUIRED TO ACCOMMODATEREWORK PIPING AS REQUIRED TO ACCOMMODATEREWORK PIPING AS REQUIRED TO ACCOMMODATEREWORK PIPING AS REQUIRED TO ACCOMMODATE
THE NEW VALVE.THE NEW VALVE.THE NEW VALVE.THE NEW VALVE.
2222 PROVIDE NEW THERMOWELL FOR INSTALLATION OFPROVIDE NEW THERMOWELL FOR INSTALLATION OFPROVIDE NEW THERMOWELL FOR INSTALLATION OFPROVIDE NEW THERMOWELL FOR INSTALLATION OF
NEW TEMPERATURE SENSOR FURNISHED BY THENEW TEMPERATURE SENSOR FURNISHED BY THENEW TEMPERATURE SENSOR FURNISHED BY THENEW TEMPERATURE SENSOR FURNISHED BY THE
CONTROLS CONTRACTOR. COORDINATE WITH THECONTROLS CONTRACTOR. COORDINATE WITH THECONTROLS CONTRACTOR. COORDINATE WITH THECONTROLS CONTRACTOR. COORDINATE WITH THE
CONTROLS CONTRACTOR IN THE INSTALLATION OFCONTROLS CONTRACTOR IN THE INSTALLATION OFCONTROLS CONTRACTOR IN THE INSTALLATION OFCONTROLS CONTRACTOR IN THE INSTALLATION OF
THE NEW TEMPERATURE SENSOR.THE NEW TEMPERATURE SENSOR.THE NEW TEMPERATURE SENSOR.THE NEW TEMPERATURE SENSOR.
mirj_fkd=cfuqrob=p`ebarib
SYMBOL DESCRIPTION COLD HOT TEPID TRAP WASTE VENT REMARKS
P-1 LAVATORY TO REMAIN, PROVIDE NEW FAUCET, CHROME PLATED BRASS, 0.5 GPM FLOW RATE 1/2" 1/2" - 1-1/2" 2" 2" -
P-1A LAVATORY - COUNTER MOUNT, ADA COMPLIANT 1/2" 1/2" - 1-1/2" 2" 2" -
P-2 WATER CLOSET TO REMAIN, PROVIDE NEW FLUSH VALVE 1" - - INT 3" 2" -
P-2A WATER CLOSET - FLOOR MOUNTED, FLUSH VALVE 1" - - INT 3" 2" -
P-3 URINAL TO REMAIN, PROVIDE NEW FLUSH VALVE 3/4" - - INT 3" 2" -
P-4 WORK SINK - COUNTER MOUNTED, SINGLE 1/2" 1/2" - 1-1/2" 2" 2" -
P-4A WORK SINK - COUNTER MOUNTED, DOUBLE COMPARTMENT 1/2" 1/2" - 1-1/2" 2" 2" -
P-5 SERVICE SINK TO REMAIN, PROVIDE NEW FAUCET 3/4" 3/4" - 3" 3" 2" -
P-5A SERVICE SINK - FLOOR MOUNTED 3/4" 3/4" - 3" 3" 2" -
P-6 ELECTRIC WATER COOLER: BI-LEVEL, WITH BOTTLE FILLER, ADA COMPLIANT 1/2" - - 1-1/4" 2" 2" -
P-6A ELECTRIC WATER COOLER: SINGLE LEVEL, WITH BOTTLE FILLER, ADA COMPLIANT 1/2" - - - - - -
WH WALL HYDRANT 3/4" - - - - - -
FD FLOOR DRAIN - - - 2" 2" 2" -
FS FLOOR SINK - - - 3" 3" 2" -
FCO FLOOR CLEAN OUT - - - - - - -
WCO WALL CLEAN OUT - - - - - - -
CO CLEAN OUT - - - - - - -
qebojlpq^qf`=jfufkd=s^isb
SYMBOL
MANUFACTURER
AND MODEL NO.
LOCATION
FLOW
RATE
(GPM)
ALLOWABLE
PRESSURE
DIFFERENTIAL
(PSI)
OUTLET
HOT WATER
TEMP. (°F)
INLET
SIZE
OUTLET
SIZE
ACCESSORIES
AND REMARKS
MV-1 POWERS - LFG480 BELOW HAND SINKS 0.5-2.0 5 105° 1/2'' 1/2'' ASSE 1070
obsbopb=lpjlpfp=t^qbo=bnrfmjbkq=p`ebarib
PRE FILTERS ACTIVE CARBON FILTER AND 5 MICRON FILTER ACCESSORIES PROVIDED WITH RO UNIT.
RO UNIT
LOW PRESSURE REVERSE OSMOSIS SYSTEM, CONDAIR TO-HM WITH PRE-FILTERS AND TANK
ACCESSORIES, 0.11 GPM PERMEATE CAPACITY AT 59 DEGREES F. 115/60/1.75 WATTS
PRESSURE TANK PRESSURE TANK, 6 GALLON, PROVIDED WITH RO UNIT.
t^qbo=e^jjbo=^oobpqbo=p`ebarib
MARK MANUFACTURER/MODEL # FIXTURE UNITS INLET SIZE REMARKS
WHA-A PPP SC-500 1-11 1/2'' PER PDI STANDARD PDI-WH 201
WHA-B PPP SC-750 12-32 3/4'' PER PDI STANDARD PDI-WH 201
WHA-C PPP SC-1000 33-60 1'' PER PDI STANDARD PDI-WH 201
Gollc=ao^fk=eb^q=qo^`b
pvj_li j^qbof^i abp`ofmqflk nqv rkfq
`^_ibp
`ljmlkbkqp
`lkqolip
HT-1 GM-IX ICESTOP SELF-REGULATING HEATING CABLE, 120V WITH POLYOLEFIN JACKET 20 FEET
RAYCLIC-PC
RAYCLIC POWER KIT WITH 5' POWERLEAD WIRES, A CONDUIT FITTING, END SEAL AND
PIPE MOUNTING BRACKET
1 EACH
PD PRO AUTOMATIC SNOW/ICE MELTING CONTROLLER, 30A AT 100-277 V, USE WITH CIT-1,
GIT-1 AND SIT-6E SNOW AND ICE SENSORS (SOLD SEPARATELY).
1 EACH
GIT-1
GUTTER DE-ICING SNOW SENSOR, CALLS FOR SNOW MELTING HEATER OPERATION AT
TEMPERATURES BELOW 38 DEG F (3.3 DEG C) WHILE PRECIPITATION, IN ANY FORM, IS
PRESENT, 24 VAC. (LOCATION IN SCUPPER DRAIN BODY)
1 EACH
*MATERIAL MODEL NUMBERS BASED ON RAYCHEM
mirj_fkd=pvj_li=ibdbka=^ka=^__obsf^qflkp
dbkbo^i=klqbp
WHA
COTG
CO
FCO
WCO
VENT
G
1.THE CONTRACTOR SHALL VERIFY ALL PLUMBING FIXTURES, EQUIPMENT REQUIREMMENTS AND
LOCATIONS, AND ALL RELATED UTILITIES WITH THE MECHANICAL AND ARCHITECTURAL PLANS
AND SPECIFICATIONS AND SHALL PROVIDE ALL SERVICES AS REQUIRED.
ALL WALL-HUNG PLUMBING FIXTURES SHALL BE SECURELY ATTACHED TO AND SUPPORTED BY
FLOOR MOUNTED CARRIERS OF ALL METAL CONSTRUCTION. FIXTURE HANGERS OR ARMS
SHALL BE SUPPORTED FREE OF THE FINISHED WALL. HANGERS SHALL BE BY WADE, SMITH,
JOSAM, OR ZURN.
EACH INDIVIDUAL FIXTURE SUPPLY SHALL BE PROVIDED WITH A CHROME-PLATED STOP VALVE.
BALL TYPE QUARTER-TURN STOPS SHALL BE ON BOTH HOT AND COLD WATER LINES.
FIXTURES AND ACCESSORIES SHALL BE AS SPECIFIED. EACH ITEM SHALL BE COMPLETE WITH
CHROME-PLATED BRASS TRIM. SEE PLUMBING FIXTURE SCHEDULE.
CAULK WITH SILICONE COMPOUND AROUND ALL FIXTURES AT INTERFACE WITH WALLS AND/OR
FLOOR.
ALL PLUMBING SHALL BE INSTALLED IN ACCORDANCE WITH THE LATEST ADOPTED EDITION OF
THE UTAH PLUMBING CODE AND/OR LOCAL ORDINANCES.
ALL FIXTURES SHALL BE NOTED ON PLUMBING FIXTURE SCHEDULE AND SPECIFIED IN SECTION
224200.
2.
3.
4.
5.
6.
7.
(FC#)
SOFT COLD WATER
DOWNSPOUT NOZZLE
NATURAL GAS
ROOF DRAIN LEADER
OVERFLOW ROOF DRAIN
SANITARY WASTE
DOMESTIC HOT WATER RECIRCULATING
DOMESTIC HOT WATER
DOMESTIC COLD WATER
VALVE IN RISE
RISE IN PIPE
DROP IN PIPE
VENT THROUGH ROOF
STORM DRAIN
DOMESTIC HOT WATER RECIRCULATING
DOMESTIC HOT WATER
DOMESTIC COLD WATER
SANITARY SEWER - (OUTSIDE)
WALL CLEAN OUT
FLOOR CLEAN OUT
FIXTURE COUNT
WATER METER
CHECK VALVE
BALL VALVE
GATE VALVE
UNION
ECCENTRIC REDUCER
CONCENTRIC REDUCER
CAP
WATER HAMMER ARRESTOR
PRESSURE / TEMPERATURE TEST PLUG (PETE'S PLUG)
PIPE ANCHOR
FLOOR DRAIN, FLOOR SINK OR ROOF DRAIN
SOLENOID VALVE
PRESSURE REDUCING VALVE - (PRV)
GAUGE WITH GAUGE COCK
FLOW CONTROLLER OR BALANCE VALVE
THERMOMETER OR GAUGE WELL
STRAINER
THERMOMETER
GAUGE COCK
CLEAN OUT TO GRADE
CLEAN OUT
M
FD
FS
RD
RD
ORD
SS
SD
SCW
DCW
DHW
DSN
VTR
DHWR
V
DESCRIPTIONSYMBOL SYMBOL DESCRIPTION
NEW CONNECTION
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
P-001
Plumbing
Legend And
Schedules
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
GGGG
JJJJ
LLLL
MMMM
NNNN
PPPP
QQQQ
EEEE
CCCC
2222 3333 4444 5555
1111
2222
3333
4444
1111
2222
PPPP----5555
PPPP----6666
5555 5555
6666
7777
8888
9999
10101010
11111111
1212121212121212
11111111
11111111
11111111
11111111
11111111
11111111
11111111
11111111
11111111
5555
5555
8888
dbkbo^i=abjlifqflk=klqbp
A.A.A.A.REMOVE ALL DOMESTIC COLD, HOT AND CIRCULATING PIPING
THAT IS ACCESSIBLE ABOVE REMODEL AREAS AND WITHIN
PLUMBING CHASES. PIPING THAT IS LOCATED IN EXISTING WALLS
THAT ARE NOT BEING REMOVED WILL BE REVIEWED AND
REPLACED WHERE POSSIBLE.
EXISTING ROOF DRAIN PIPING TO REMAIN. PROTECT DURING
CONSTRUCTION PERIOD.
EXISTING WASTE AND VENT PIPING TO REMAIN. PROTECT DURING
CONSTRUCTION PERIOD. UNLESS NOTED ON PLANS.
EXISTING PLUMBING FIXTURE IN TOILET ROOMS TO REMAIN.
FLUSH VALVES AND LAVATORY FAUCETS WILL BE REPLACED
WITH NEW AS PART OF THE PIPE REPLACEMENT PORTION OF THE
WORK.
EXISTING DRINKING FOUNTAINS WILL BE REPLACED OR
PROTECTED IN PLACE. EACH LOCATION WILL BE REVIEWED WITH
THE OWNER TO DETERMINE WHICH UNITS ARE TO BE REPLACED.
EXISTING MOP SINKS ARE TO REMAIN IN PLACE. NEW FAUCETS
WILL BE PROVIDED IN LOCATIONS THAT ARE DETERMINED TO
NEED REPLACEMENT.
B.B.B.B.
C.C.C.C.
D.D.D.D.
E.E.E.E.
F.F.F.F.
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
PD100a
Level 00 Area
A Plumbing
Demolition
Plan
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
KEY PLAN
A
B
ao^tfkd=klqbp
SCALE:SCALE:SCALE:SCALE:PD100aPD100aPD100aPD100a 1/8" = 1'1/8" = 1'1/8" = 1'1/8" = 1'----0"0"0"0"
ibsbi=MM=^ob^=^=mirj_fkd=abjlifqflk=mi^k1111
0000555510101010 10101010 20202020
NOTE
# DESCRIPTION
1111 REMOVE ALL DOMESTIC COLD, HOT ANDREMOVE ALL DOMESTIC COLD, HOT ANDREMOVE ALL DOMESTIC COLD, HOT ANDREMOVE ALL DOMESTIC COLD, HOT AND
RECIRCULATING PIPING COMPLETE PREPARATORYRECIRCULATING PIPING COMPLETE PREPARATORYRECIRCULATING PIPING COMPLETE PREPARATORYRECIRCULATING PIPING COMPLETE PREPARATORY
FOR NEW.FOR NEW.FOR NEW.FOR NEW.
2222 EXISTING WATER CLOSET, URINAL AND LAVATORYEXISTING WATER CLOSET, URINAL AND LAVATORYEXISTING WATER CLOSET, URINAL AND LAVATORYEXISTING WATER CLOSET, URINAL AND LAVATORY
FIXTURES TO REMAIN IN PLACE. PROTECT DURINGFIXTURES TO REMAIN IN PLACE. PROTECT DURINGFIXTURES TO REMAIN IN PLACE. PROTECT DURINGFIXTURES TO REMAIN IN PLACE. PROTECT DURING
CONSTRUCTION. REMOVE ASSOCIATED COLD ANDCONSTRUCTION. REMOVE ASSOCIATED COLD ANDCONSTRUCTION. REMOVE ASSOCIATED COLD ANDCONSTRUCTION. REMOVE ASSOCIATED COLD AND
HOT WATER PIPING, FLUSH VALVES, FAUCETS ANDHOT WATER PIPING, FLUSH VALVES, FAUCETS ANDHOT WATER PIPING, FLUSH VALVES, FAUCETS ANDHOT WATER PIPING, FLUSH VALVES, FAUCETS AND
TRIM PREPARATORY FOR NEW.TRIM PREPARATORY FOR NEW.TRIM PREPARATORY FOR NEW.TRIM PREPARATORY FOR NEW.
3333 EXISTING MOP SINK TO REMAIN. REMOVEEXISTING MOP SINK TO REMAIN. REMOVEEXISTING MOP SINK TO REMAIN. REMOVEEXISTING MOP SINK TO REMAIN. REMOVE
ASSOCIATED FAUCET AND WATER SUPPLY PIPINGASSOCIATED FAUCET AND WATER SUPPLY PIPINGASSOCIATED FAUCET AND WATER SUPPLY PIPINGASSOCIATED FAUCET AND WATER SUPPLY PIPING
PREPARATORY FOR NEW.PREPARATORY FOR NEW.PREPARATORY FOR NEW.PREPARATORY FOR NEW.
4444 EXISTING WATER ENTRY. REMOVE PIPING ANDEXISTING WATER ENTRY. REMOVE PIPING ANDEXISTING WATER ENTRY. REMOVE PIPING ANDEXISTING WATER ENTRY. REMOVE PIPING AND
VALVES DOWNSTREAM OF ISOLATION VALVEVALVES DOWNSTREAM OF ISOLATION VALVEVALVES DOWNSTREAM OF ISOLATION VALVEVALVES DOWNSTREAM OF ISOLATION VALVE
COMPLETE PREPARATORY FOR NEW.COMPLETE PREPARATORY FOR NEW.COMPLETE PREPARATORY FOR NEW.COMPLETE PREPARATORY FOR NEW.
5555 REMOVE DCW, DHW AND DHWR. CONTRACTOR TOREMOVE DCW, DHW AND DHWR. CONTRACTOR TOREMOVE DCW, DHW AND DHWR. CONTRACTOR TOREMOVE DCW, DHW AND DHWR. CONTRACTOR TO
FIELD VERIFY EXACT ROUTING.FIELD VERIFY EXACT ROUTING.FIELD VERIFY EXACT ROUTING.FIELD VERIFY EXACT ROUTING.
6666 PROTECT WATER HEATER SKID DURINGPROTECT WATER HEATER SKID DURINGPROTECT WATER HEATER SKID DURINGPROTECT WATER HEATER SKID DURING
CONSTRUCTION.CONSTRUCTION.CONSTRUCTION.CONSTRUCTION.
7777 PROTECT DOMESTIC HOT WATER CIRCULATIONPROTECT DOMESTIC HOT WATER CIRCULATIONPROTECT DOMESTIC HOT WATER CIRCULATIONPROTECT DOMESTIC HOT WATER CIRCULATION
PUMP WITH ASSOCIATED VALVES DURINGPUMP WITH ASSOCIATED VALVES DURINGPUMP WITH ASSOCIATED VALVES DURINGPUMP WITH ASSOCIATED VALVES DURING
CONSTRUCTION.CONSTRUCTION.CONSTRUCTION.CONSTRUCTION.
8888 REMOVE DRINKING FOUNTAIN COMPLETE.REMOVE DRINKING FOUNTAIN COMPLETE.REMOVE DRINKING FOUNTAIN COMPLETE.REMOVE DRINKING FOUNTAIN COMPLETE.
9999 REMOVE BRANCH PIPING AND BACKFLOWREMOVE BRANCH PIPING AND BACKFLOWREMOVE BRANCH PIPING AND BACKFLOWREMOVE BRANCH PIPING AND BACKFLOW
PREVENTER COMPLETE. SEE SHEET PL100a FORPREVENTER COMPLETE. SEE SHEET PL100a FORPREVENTER COMPLETE. SEE SHEET PL100a FORPREVENTER COMPLETE. SEE SHEET PL100a FOR
REINSTALLATION OF BACKFLOW PREVENTER.REINSTALLATION OF BACKFLOW PREVENTER.REINSTALLATION OF BACKFLOW PREVENTER.REINSTALLATION OF BACKFLOW PREVENTER.
10101010 REMOVE BRANCH PIPING AND VALVES COMPLETEREMOVE BRANCH PIPING AND VALVES COMPLETEREMOVE BRANCH PIPING AND VALVES COMPLETEREMOVE BRANCH PIPING AND VALVES COMPLETE
PREPARATORY FOR NEW.PREPARATORY FOR NEW.PREPARATORY FOR NEW.PREPARATORY FOR NEW.
11111111 CONTRACTOR TO PROVIDE COLOR CAMERACONTRACTOR TO PROVIDE COLOR CAMERACONTRACTOR TO PROVIDE COLOR CAMERACONTRACTOR TO PROVIDE COLOR CAMERA
INSPECTION OF UNDERGROUND WASTE AND ROOFINSPECTION OF UNDERGROUND WASTE AND ROOFINSPECTION OF UNDERGROUND WASTE AND ROOFINSPECTION OF UNDERGROUND WASTE AND ROOF
DRAIN PIPING AT THE BEGINNING OFDRAIN PIPING AT THE BEGINNING OFDRAIN PIPING AT THE BEGINNING OFDRAIN PIPING AT THE BEGINNING OF
CONSTRUCTION. PROVIDE VIDEO RECORDING OFCONSTRUCTION. PROVIDE VIDEO RECORDING OFCONSTRUCTION. PROVIDE VIDEO RECORDING OFCONSTRUCTION. PROVIDE VIDEO RECORDING OF
EACH MAIN INSPECTION RUN WITH NOTES OFEACH MAIN INSPECTION RUN WITH NOTES OFEACH MAIN INSPECTION RUN WITH NOTES OFEACH MAIN INSPECTION RUN WITH NOTES OF
FINDINGS AND LOCATIONS OF FINDINGS.FINDINGS AND LOCATIONS OF FINDINGS.FINDINGS AND LOCATIONS OF FINDINGS.FINDINGS AND LOCATIONS OF FINDINGS.
12121212 CONTRACTOR TO ALLOW OWNER TO VISUALLYCONTRACTOR TO ALLOW OWNER TO VISUALLYCONTRACTOR TO ALLOW OWNER TO VISUALLYCONTRACTOR TO ALLOW OWNER TO VISUALLY
INSPECT EXISTING PIPING SERVING RESTROOMSINSPECT EXISTING PIPING SERVING RESTROOMSINSPECT EXISTING PIPING SERVING RESTROOMSINSPECT EXISTING PIPING SERVING RESTROOMS
PRIOR TO REMOVAL. IF PIPING IS FOUND TO BE INPRIOR TO REMOVAL. IF PIPING IS FOUND TO BE INPRIOR TO REMOVAL. IF PIPING IS FOUND TO BE INPRIOR TO REMOVAL. IF PIPING IS FOUND TO BE IN
A CONDITION SATISFACTORY TO THE OWNER TOA CONDITION SATISFACTORY TO THE OWNER TOA CONDITION SATISFACTORY TO THE OWNER TOA CONDITION SATISFACTORY TO THE OWNER TO
LEAVE IN PLACE CONTRACTOR SHALL LEAVE INLEAVE IN PLACE CONTRACTOR SHALL LEAVE INLEAVE IN PLACE CONTRACTOR SHALL LEAVE INLEAVE IN PLACE CONTRACTOR SHALL LEAVE IN
PLACE AND PROVIDE CREDIT FOR WORK IN THISPLACE AND PROVIDE CREDIT FOR WORK IN THISPLACE AND PROVIDE CREDIT FOR WORK IN THISPLACE AND PROVIDE CREDIT FOR WORK IN THIS
AREA.AREA.AREA.AREA.
(E)AD
(E)FD
(E)3/4" DHWR
(E)1-1/4" DHW
(E)2-1/2" DCW
(E)3/4" DCW
& DHW UP
(E)3/4" DCW
& DHW UP
(E)1/2" DCW UP
(E)2" DCW &
1" DHW UP
(E)3/4"
(E)1-1/4"
(E)2-1/2"
(E)3/4" DCW
& DHW UP
(E)2-1/2"
(E)1"(E)1"
(E)2"
(E)3/4"
(E)3/4"
(E)1-1/4" DCW &
3/4" DHW UP
(E)3/4" DCW UP TO WH
(E)3/4" DCW UP TO WH
(E)3/4"
(E)AD
(E)FD
(E)FD
(E)FD
(E)FD
(E)FD
(E)FD(E)FD
(E)FS
(E)FD
(E)2"(E)2" VENT UP
(E)2"
(E)3"
(E)2"(E)2" (E)6"
(E)3"
(E)3"
(E)6"
(E)6"
(E)2"
(E)3"
(E)WH
(E)WH
(E)3/4"
(E)3/4"
(E)1"
(E)1-1/2"
(E)3/4"
(E)1"
(E)1"
dbkbo^i=abjlifqflk=klqbp
A.A.A.A. REMOVE ALL DOMESTIC COLD, HOT AND CIRCULATING PIPING
THAT IS ACCESSIBLE ABOVE REMODEL AREAS AND WITHIN
PLUMBING CHASES. PIPING THAT IS LOCATED IN EXISTING WALLS
THAT ARE NOT BEING REMOVED WILL BE REVIEWED AND
REPLACED WHERE POSSIBLE.
EXISTING ROOF DRAIN PIPING TO REMAIN. PROTECT DURING
CONSTRUCTION PERIOD.
EXISTING WASTE AND VENT PIPING TO REMAIN. PROTECT DURING
CONSTRUCTION PERIOD. UNLESS NOTED ON PLANS.
EXISTING PLUMBING FIXTURE IN TOILET ROOMS TO REMAIN.
FLUSH VALVES AND LAVATORY FAUCETS WILL BE REPLACED
WITH NEW AS PART OF THE PIPE REPLACEMENT PORTION OF THE
WORK.
EXISTING DRINKING FOUNTAINS WILL BE REPLACED OR
PROTECTED IN PLACE. EACH LOCATION WILL BE REVIEWED WITH
THE OWNER TO DETERMINE WHICH UNITS ARE TO BE REPLACED.
EXISTING MOP SINKS ARE TO REMAIN IN PLACE. NEW FAUCETS
WILL BE PROVIDED IN LOCATIONS THAT ARE DETERMINED TO
NEED REPLACEMENT.
B.B.B.B.
C.C.C.C.
D.D.D.D.
E.E.E.E.
F.F.F.F.
16161616151515151414141413131313121212121111111110101010999988887777
KKKK
HHHH
FFFF
DDDD
BBBB
AAAA
11112222
1111
1111
2222
11111111
1111
1111
1111
3333
1111
1111
11111111
1111
1111
1111
1111
2222
2222
4444
4444
4444
5555
6666
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
PD100b
Level 00 Area
B Plumbing
Demolition
Plan
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
KEY PLAN
A
B
ao^tfkd=klqbp
0000555510101010 10101010 20202020
SCALE:SCALE:SCALE:SCALE:PD100bPD100bPD100bPD100b 1/8" = 1'1/8" = 1'1/8" = 1'1/8" = 1'----0"0"0"0"
ibsbi=MM=^ob^=_=mirj_fkd=abjlifqflk=mi^k1111
NOTE
#DESCRIPTION
1111 REMOVE ALL DOMESTIC COLD, HOT ANDREMOVE ALL DOMESTIC COLD, HOT ANDREMOVE ALL DOMESTIC COLD, HOT ANDREMOVE ALL DOMESTIC COLD, HOT AND
RECIRCULATING PIPING COMPLETE PREPARATORYRECIRCULATING PIPING COMPLETE PREPARATORYRECIRCULATING PIPING COMPLETE PREPARATORYRECIRCULATING PIPING COMPLETE PREPARATORY
FOR NEW.FOR NEW.FOR NEW.FOR NEW.
2222 REMOVE EXISTING WALL HYDRANT ANDREMOVE EXISTING WALL HYDRANT ANDREMOVE EXISTING WALL HYDRANT ANDREMOVE EXISTING WALL HYDRANT AND
ASSOCIATED PIPING PREPARATORY FOR NEW.ASSOCIATED PIPING PREPARATORY FOR NEW.ASSOCIATED PIPING PREPARATORY FOR NEW.ASSOCIATED PIPING PREPARATORY FOR NEW.
3333 SEE PD101b FOR CONTINUATION.SEE PD101b FOR CONTINUATION.SEE PD101b FOR CONTINUATION.SEE PD101b FOR CONTINUATION.
4444 CONTRACTOR TO PROVIDE COLOR CAMERACONTRACTOR TO PROVIDE COLOR CAMERACONTRACTOR TO PROVIDE COLOR CAMERACONTRACTOR TO PROVIDE COLOR CAMERA
INSPECTION OF UNDERGROUND WASTE AND ROOFINSPECTION OF UNDERGROUND WASTE AND ROOFINSPECTION OF UNDERGROUND WASTE AND ROOFINSPECTION OF UNDERGROUND WASTE AND ROOF
DRAIN PIPING AT THE BEGINNING OFDRAIN PIPING AT THE BEGINNING OFDRAIN PIPING AT THE BEGINNING OFDRAIN PIPING AT THE BEGINNING OF
CONSTRUCTION. PROVIDE VIDEO RECORDING OFCONSTRUCTION. PROVIDE VIDEO RECORDING OFCONSTRUCTION. PROVIDE VIDEO RECORDING OFCONSTRUCTION. PROVIDE VIDEO RECORDING OF
EACH MAIN INSPECTION RUN WITH NOTES OFEACH MAIN INSPECTION RUN WITH NOTES OFEACH MAIN INSPECTION RUN WITH NOTES OFEACH MAIN INSPECTION RUN WITH NOTES OF
FINDINGS AND LOCATIONS OF FINDINGS.FINDINGS AND LOCATIONS OF FINDINGS.FINDINGS AND LOCATIONS OF FINDINGS.FINDINGS AND LOCATIONS OF FINDINGS.
5555 PROTECT DOMESTIC HOT WATER CIRCULATIONPROTECT DOMESTIC HOT WATER CIRCULATIONPROTECT DOMESTIC HOT WATER CIRCULATIONPROTECT DOMESTIC HOT WATER CIRCULATION
PUMP WITH ASSOCIATED VALVES DURINGPUMP WITH ASSOCIATED VALVES DURINGPUMP WITH ASSOCIATED VALVES DURINGPUMP WITH ASSOCIATED VALVES DURING
CONSTRUCTION.CONSTRUCTION.CONSTRUCTION.CONSTRUCTION.
6666 PROTECT WATER HEATER SKID DURINGPROTECT WATER HEATER SKID DURINGPROTECT WATER HEATER SKID DURINGPROTECT WATER HEATER SKID DURING
CONSTRUCTION.CONSTRUCTION.CONSTRUCTION.CONSTRUCTION.
1111
GGGG
JJJJ
LLLL
MMMM
NNNN
PPPP
QQQQ
EEEE
CCCC
2222 3333 4444 5555
1111
2222
2222
1111
3333
4444
3333
5555
6666
7777
4444
1111
1111
6666
dbkbo^i=abjlifqflk=klqbp
A.A.A.A. REMOVE ALL DOMESTIC COLD, HOT AND CIRCULATING PIPING
THAT IS ACCESSIBLE ABOVE REMODEL AREAS AND WITHIN
PLUMBING CHASES. PIPING THAT IS LOCATED IN EXISTING WALLS
THAT ARE NOT BEING REMOVED WILL BE REVIEWED AND
REPLACED WHERE POSSIBLE.
EXISTING ROOF DRAIN PIPING TO REMAIN. PROTECT DURING
CONSTRUCTION PERIOD.
EXISTING WASTE AND VENT PIPING TO REMAIN. PROTECT DURING
CONSTRUCTION PERIOD. UNLESS NOTED ON PLANS.
EXISTING PLUMBING FIXTURE IN TOILET ROOMS TO REMAIN.
FLUSH VALVES AND LAVATORY FAUCETS WILL BE REPLACED
WITH NEW AS PART OF THE PIPE REPLACEMENT PORTION OF THE
WORK.
EXISTING DRINKING FOUNTAINS WILL BE REPLACED OR
PROTECTED IN PLACE. EACH LOCATION WILL BE REVIEWED WITH
THE OWNER TO DETERMINE WHICH UNITS ARE TO BE REPLACED.
EXISTING MOP SINKS ARE TO REMAIN IN PLACE. NEW FAUCETS
WILL BE PROVIDED IN LOCATIONS THAT ARE DETERMINED TO
NEED REPLACEMENT.
B.B.B.B.
C.C.C.C.
D.D.D.D.
E.E.E.E.
F.F.F.F.
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
PD101a
Level 01 Area
A Plumbing
Demolition
Plan
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
KEY PLAN
A
B
ao^tfkd=klqbp
0000555510101010 10101010 20202020
NOTE
# DESCRIPTION
1111 REMOVE ALL DOMESTIC COLD, HOT ANDREMOVE ALL DOMESTIC COLD, HOT ANDREMOVE ALL DOMESTIC COLD, HOT ANDREMOVE ALL DOMESTIC COLD, HOT AND
RECIRCULATING PIPING COMPLETE PREPARATORYRECIRCULATING PIPING COMPLETE PREPARATORYRECIRCULATING PIPING COMPLETE PREPARATORYRECIRCULATING PIPING COMPLETE PREPARATORY
FOR NEW.FOR NEW.FOR NEW.FOR NEW.
2222 EXISTING WATER CLOSET, URINAL AND LAVATORYEXISTING WATER CLOSET, URINAL AND LAVATORYEXISTING WATER CLOSET, URINAL AND LAVATORYEXISTING WATER CLOSET, URINAL AND LAVATORY
FIXTURES TO REMAIN IN PLACE. PROTECT DURINGFIXTURES TO REMAIN IN PLACE. PROTECT DURINGFIXTURES TO REMAIN IN PLACE. PROTECT DURINGFIXTURES TO REMAIN IN PLACE. PROTECT DURING
CONSTRUCTION. REMOVE ASSOCIATED COLD ANDCONSTRUCTION. REMOVE ASSOCIATED COLD ANDCONSTRUCTION. REMOVE ASSOCIATED COLD ANDCONSTRUCTION. REMOVE ASSOCIATED COLD AND
HOT WATER PIPING, FLUSH VALVES, FAUCETS ANDHOT WATER PIPING, FLUSH VALVES, FAUCETS ANDHOT WATER PIPING, FLUSH VALVES, FAUCETS ANDHOT WATER PIPING, FLUSH VALVES, FAUCETS AND
TRIM PREPARATORY FOR NEW.TRIM PREPARATORY FOR NEW.TRIM PREPARATORY FOR NEW.TRIM PREPARATORY FOR NEW.
3333 REMOVE EXISTING 1/2" DCW IN WALL.REMOVE EXISTING 1/2" DCW IN WALL.REMOVE EXISTING 1/2" DCW IN WALL.REMOVE EXISTING 1/2" DCW IN WALL.
4444 REMOVE DCW AND DHW IN PLUMBING CHASEREMOVE DCW AND DHW IN PLUMBING CHASEREMOVE DCW AND DHW IN PLUMBING CHASEREMOVE DCW AND DHW IN PLUMBING CHASE
PREPARATORY FOR NEW. PROTECT WASTE ANDPREPARATORY FOR NEW. PROTECT WASTE ANDPREPARATORY FOR NEW. PROTECT WASTE ANDPREPARATORY FOR NEW. PROTECT WASTE AND
VENT PIPING IN PLUMBING CHASE.VENT PIPING IN PLUMBING CHASE.VENT PIPING IN PLUMBING CHASE.VENT PIPING IN PLUMBING CHASE.
5555 EXISTING MOP SINK TO REMAIN. REMOVEEXISTING MOP SINK TO REMAIN. REMOVEEXISTING MOP SINK TO REMAIN. REMOVEEXISTING MOP SINK TO REMAIN. REMOVE
ASSOCIATED FAUCET AND WATER SUPPLY PIPINGASSOCIATED FAUCET AND WATER SUPPLY PIPINGASSOCIATED FAUCET AND WATER SUPPLY PIPINGASSOCIATED FAUCET AND WATER SUPPLY PIPING
PREPARATORY FOR NEW.PREPARATORY FOR NEW.PREPARATORY FOR NEW.PREPARATORY FOR NEW.
6666 REMOVE DRINKING FOUNTAIN COMPLETEREMOVE DRINKING FOUNTAIN COMPLETEREMOVE DRINKING FOUNTAIN COMPLETEREMOVE DRINKING FOUNTAIN COMPLETE
PREPARATORY FOR NEW.PREPARATORY FOR NEW.PREPARATORY FOR NEW.PREPARATORY FOR NEW.
7777 REMOVE 1-1/2" WASTE PIPE COMPLETE.REMOVE 1-1/2" WASTE PIPE COMPLETE.REMOVE 1-1/2" WASTE PIPE COMPLETE.REMOVE 1-1/2" WASTE PIPE COMPLETE.
SCALE:SCALE:SCALE:SCALE:PD101aPD101aPD101aPD101a 1/8" = 1'1/8" = 1'1/8" = 1'1/8" = 1'----0"0"0"0"
ibsbi=N=^ob^=^=mirj_fkd=abjlifqflk=mi^k1111
16161616151515151414141413131313121212121111111110101010999988887777
KKKK
HHHH
FFFF
DDDD
BBBB
AAAA
1111
2222
3333
4444
3333
3333
2222
11111111
1111
PPPP----5555
5555
5555
6666
7777
8888
9999
8888
5555
9999
9999
9999
9999
9999
9999
9999
9999
9999
1111
1111
1111
dbkbo^i=abjlifqflk=klqbp
A.A.A.A. REMOVE ALL DOMESTIC COLD, HOT AND CIRCULATING PIPING
THAT IS ACCESSIBLE ABOVE REMODEL AREAS AND WITHIN
PLUMBING CHASES. PIPING THAT IS LOCATED IN EXISTING WALLS
THAT ARE NOT BEING REMOVED WILL BE REVIEWED AND
REPLACED WHERE POSSIBLE.
EXISTING ROOF DRAIN PIPING TO REMAIN. PROTECT DURING
CONSTRUCTION PERIOD.
EXISTING WASTE AND VENT PIPING TO REMAIN. PROTECT DURING
CONSTRUCTION PERIOD. UNLESS NOTED ON PLANS.
EXISTING PLUMBING FIXTURE IN TOILET ROOMS TO REMAIN.
FLUSH VALVES AND LAVATORY FAUCETS WILL BE REPLACED
WITH NEW AS PART OF THE PIPE REPLACEMENT PORTION OF THE
WORK.
EXISTING DRINKING FOUNTAINS WILL BE REPLACED OR
PROTECTED IN PLACE. EACH LOCATION WILL BE REVIEWED WITH
THE OWNER TO DETERMINE WHICH UNITS ARE TO BE REPLACED.
EXISTING MOP SINKS ARE TO REMAIN IN PLACE. NEW FAUCETS
WILL BE PROVIDED IN LOCATIONS THAT ARE DETERMINED TO
NEED REPLACEMENT.
B.B.B.B.
C.C.C.C.
D.D.D.D.
E.E.E.E.
F.F.F.F.
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
PD101b
Level 01 Area
B Plumbing
Demolition
Plan
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
KEY PLAN
A
B
ao^tfkd=klqbp
0000555510101010 10101010 20202020
NOTE
# DESCRIPTION
1111 REMOVE ALL DOMESTIC COLD, HOT ANDREMOVE ALL DOMESTIC COLD, HOT ANDREMOVE ALL DOMESTIC COLD, HOT ANDREMOVE ALL DOMESTIC COLD, HOT AND
RECIRCULATING PIPING COMPLETE PREPARATORYRECIRCULATING PIPING COMPLETE PREPARATORYRECIRCULATING PIPING COMPLETE PREPARATORYRECIRCULATING PIPING COMPLETE PREPARATORY
FOR NEW.FOR NEW.FOR NEW.FOR NEW.
2222 EXISTING WATER CLOSET, URINAL AND LAVATORYEXISTING WATER CLOSET, URINAL AND LAVATORYEXISTING WATER CLOSET, URINAL AND LAVATORYEXISTING WATER CLOSET, URINAL AND LAVATORY
FIXTURES TO REMAIN IN PLACE. PROTECT DURINGFIXTURES TO REMAIN IN PLACE. PROTECT DURINGFIXTURES TO REMAIN IN PLACE. PROTECT DURINGFIXTURES TO REMAIN IN PLACE. PROTECT DURING
CONSTRUCTION. REMOVE ASSOCIATED FLUSHCONSTRUCTION. REMOVE ASSOCIATED FLUSHCONSTRUCTION. REMOVE ASSOCIATED FLUSHCONSTRUCTION. REMOVE ASSOCIATED FLUSH
VALVES, FAUCETS AND TRIM PREPARATORY FORVALVES, FAUCETS AND TRIM PREPARATORY FORVALVES, FAUCETS AND TRIM PREPARATORY FORVALVES, FAUCETS AND TRIM PREPARATORY FOR
NEW.NEW.NEW.NEW.
3333 REMOVE EXISTING WALL HYDRANT ANDREMOVE EXISTING WALL HYDRANT ANDREMOVE EXISTING WALL HYDRANT ANDREMOVE EXISTING WALL HYDRANT AND
ASSOCIATED PIPING PREPARATORY FOR NEW.ASSOCIATED PIPING PREPARATORY FOR NEW.ASSOCIATED PIPING PREPARATORY FOR NEW.ASSOCIATED PIPING PREPARATORY FOR NEW.
4444 EXISTING MOP SINK TO REMAIN. REMOVEEXISTING MOP SINK TO REMAIN. REMOVEEXISTING MOP SINK TO REMAIN. REMOVEEXISTING MOP SINK TO REMAIN. REMOVE
ASSOCIATED FAUCET AND WATER SUPPLY PIPINGASSOCIATED FAUCET AND WATER SUPPLY PIPINGASSOCIATED FAUCET AND WATER SUPPLY PIPINGASSOCIATED FAUCET AND WATER SUPPLY PIPING
PREPARATORY FOR NEW.PREPARATORY FOR NEW.PREPARATORY FOR NEW.PREPARATORY FOR NEW.
5555 REMOVE EXISTING DCW & DHW IN WALL ACCESSREMOVE EXISTING DCW & DHW IN WALL ACCESSREMOVE EXISTING DCW & DHW IN WALL ACCESSREMOVE EXISTING DCW & DHW IN WALL ACCESS
FROM OUTSIDE OF RESTROOM.FROM OUTSIDE OF RESTROOM.FROM OUTSIDE OF RESTROOM.FROM OUTSIDE OF RESTROOM.
6666 REMOVE DCW AND DHW IN PLUMBING CHASEREMOVE DCW AND DHW IN PLUMBING CHASEREMOVE DCW AND DHW IN PLUMBING CHASEREMOVE DCW AND DHW IN PLUMBING CHASE
PREPARATORY FOR NEW. PROTECT WASTE ANDPREPARATORY FOR NEW. PROTECT WASTE ANDPREPARATORY FOR NEW. PROTECT WASTE ANDPREPARATORY FOR NEW. PROTECT WASTE AND
VENT PIPING IN PLUMBING CHASE.VENT PIPING IN PLUMBING CHASE.VENT PIPING IN PLUMBING CHASE.VENT PIPING IN PLUMBING CHASE.
7777 SAW CUT FLOOR AND REMOVE WASTE, ROOFSAW CUT FLOOR AND REMOVE WASTE, ROOFSAW CUT FLOOR AND REMOVE WASTE, ROOFSAW CUT FLOOR AND REMOVE WASTE, ROOF
DRAIN, AND WATER PIPING PREPARATORY FORDRAIN, AND WATER PIPING PREPARATORY FORDRAIN, AND WATER PIPING PREPARATORY FORDRAIN, AND WATER PIPING PREPARATORY FOR
NEW.NEW.NEW.NEW.
8888 REMOVE DRINKING FOUNTAIN COMPLETE.REMOVE DRINKING FOUNTAIN COMPLETE.REMOVE DRINKING FOUNTAIN COMPLETE.REMOVE DRINKING FOUNTAIN COMPLETE.
9999 CONTRACTOR TO PROVIDE COLOR CAMERACONTRACTOR TO PROVIDE COLOR CAMERACONTRACTOR TO PROVIDE COLOR CAMERACONTRACTOR TO PROVIDE COLOR CAMERA
INSPECTION OF UNDERGROUND WASTE AND ROOFINSPECTION OF UNDERGROUND WASTE AND ROOFINSPECTION OF UNDERGROUND WASTE AND ROOFINSPECTION OF UNDERGROUND WASTE AND ROOF
DRAIN PIPING AT THE BEGINNING OFDRAIN PIPING AT THE BEGINNING OFDRAIN PIPING AT THE BEGINNING OFDRAIN PIPING AT THE BEGINNING OF
CONSTRUCTION. PROVIDE VIDEO RECORDING OFCONSTRUCTION. PROVIDE VIDEO RECORDING OFCONSTRUCTION. PROVIDE VIDEO RECORDING OFCONSTRUCTION. PROVIDE VIDEO RECORDING OF
EACH MAIN INSPECTION RUN WITH NOTES OFEACH MAIN INSPECTION RUN WITH NOTES OFEACH MAIN INSPECTION RUN WITH NOTES OFEACH MAIN INSPECTION RUN WITH NOTES OF
FINDINGS AND LOCATIONS OF FINDINGS. COLORFINDINGS AND LOCATIONS OF FINDINGS. COLORFINDINGS AND LOCATIONS OF FINDINGS. COLORFINDINGS AND LOCATIONS OF FINDINGS. COLOR
CAMERA INSPECTION OF UNDERGROUND WASTECAMERA INSPECTION OF UNDERGROUND WASTECAMERA INSPECTION OF UNDERGROUND WASTECAMERA INSPECTION OF UNDERGROUND WASTE
AND ROOF DRAIN PIPING AT THE BEGINNING OFAND ROOF DRAIN PIPING AT THE BEGINNING OFAND ROOF DRAIN PIPING AT THE BEGINNING OFAND ROOF DRAIN PIPING AT THE BEGINNING OF
CONSTRUCTION. PROVIDE VIDEO RECORDING OFCONSTRUCTION. PROVIDE VIDEO RECORDING OFCONSTRUCTION. PROVIDE VIDEO RECORDING OFCONSTRUCTION. PROVIDE VIDEO RECORDING OF
EACH MAIN INSPECTION RUN WITH NOTES OFEACH MAIN INSPECTION RUN WITH NOTES OFEACH MAIN INSPECTION RUN WITH NOTES OFEACH MAIN INSPECTION RUN WITH NOTES OF
FINDINGS AND LOCATIONS OF FINDINGS.FINDINGS AND LOCATIONS OF FINDINGS.FINDINGS AND LOCATIONS OF FINDINGS.FINDINGS AND LOCATIONS OF FINDINGS.
SCALE:SCALE:SCALE:SCALE:PD101bPD101bPD101bPD101b 1/8" = 1'1/8" = 1'1/8" = 1'1/8" = 1'----0"0"0"0"
ibsbi=N=^ob^=_=mirj_fkd=abjlifqflk=mi^k1111
1111
GGGG
JJJJ
LLLL
MMMM
NNNN
PPPP
QQQQ
EEEE
CCCC
2222 3333 4444 5555
1111
2222 2222
1111
1111
1111
1111
3333
4444
3333
4444
5555
6666
7777
8888
5555
1111
1111
1111
1111
6666
8888
dbkbo^i=abjlifqflk=klqbp
A.A.A.A. REMOVE ALL DOMESTIC COLD, HOT AND CIRCULATING PIPING
THAT IS ACCESSIBLE ABOVE REMODEL AREAS AND WITHIN
PLUMBING CHASES. PIPING THAT IS LOCATED IN EXISTING WALLS
THAT ARE NOT BEING REMOVED WILL BE REVIEWED AND
REPLACED WHERE POSSIBLE.
EXISTING ROOF DRAIN PIPING TO REMAIN. PROTECT DURING
CONSTRUCTION PERIOD.
EXISTING WASTE AND VENT PIPING TO REMAIN. PROTECT DURING
CONSTRUCTION PERIOD. UNLESS NOTED ON PLANS.
EXISTING PLUMBING FIXTURE IN TOILET ROOMS TO REMAIN.
FLUSH VALVES AND LAVATORY FAUCETS WILL BE REPLACED
WITH NEW AS PART OF THE PIPE REPLACEMENT PORTION OF THE
WORK.
EXISTING DRINKING FOUNTAINS WILL BE REPLACED OR
PROTECTED IN PLACE. EACH LOCATION WILL BE REVIEWED WITH
THE OWNER TO DETERMINE WHICH UNITS ARE TO BE REPLACED.
EXISTING MOP SINKS ARE TO REMAIN IN PLACE. NEW FAUCETS
WILL BE PROVIDED IN LOCATIONS THAT ARE DETERMINED TO
NEED REPLACEMENT.
B.B.B.B.
C.C.C.C.
D.D.D.D.
E.E.E.E.
F.F.F.F.
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
PD102a
Level 02 Area
A Plumbing
Demolition
Plan
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
KEY PLAN
A
B
ao^tfkd=klqbp
0000555510101010 10101010 20202020
NOTE
# DESCRIPTION
1111 REMOVE ALL DOMESTIC COLD, HOT ANDREMOVE ALL DOMESTIC COLD, HOT ANDREMOVE ALL DOMESTIC COLD, HOT ANDREMOVE ALL DOMESTIC COLD, HOT AND
RECIRCULATING PIPING COMPLETE PREPARATORYRECIRCULATING PIPING COMPLETE PREPARATORYRECIRCULATING PIPING COMPLETE PREPARATORYRECIRCULATING PIPING COMPLETE PREPARATORY
FOR NEW.FOR NEW.FOR NEW.FOR NEW.
2222 EXISTING WATER CLOSET, URINAL AND LAVATORYEXISTING WATER CLOSET, URINAL AND LAVATORYEXISTING WATER CLOSET, URINAL AND LAVATORYEXISTING WATER CLOSET, URINAL AND LAVATORY
FIXTURES TO REMAIN IN PLACE. PROTECT DURINGFIXTURES TO REMAIN IN PLACE. PROTECT DURINGFIXTURES TO REMAIN IN PLACE. PROTECT DURINGFIXTURES TO REMAIN IN PLACE. PROTECT DURING
CONSTRUCTION. REMOVE ASSOCIATED FLUSHCONSTRUCTION. REMOVE ASSOCIATED FLUSHCONSTRUCTION. REMOVE ASSOCIATED FLUSHCONSTRUCTION. REMOVE ASSOCIATED FLUSH
VALVES, FAUCETS AND TRIM PREPARATORY FORVALVES, FAUCETS AND TRIM PREPARATORY FORVALVES, FAUCETS AND TRIM PREPARATORY FORVALVES, FAUCETS AND TRIM PREPARATORY FOR
NEW.NEW.NEW.NEW.
3333 REMOVE EXISTING 1/2" DCW IN WALL.REMOVE EXISTING 1/2" DCW IN WALL.REMOVE EXISTING 1/2" DCW IN WALL.REMOVE EXISTING 1/2" DCW IN WALL.
4444 REMOVE DCW AND DHW IN PLUMBING CHASEREMOVE DCW AND DHW IN PLUMBING CHASEREMOVE DCW AND DHW IN PLUMBING CHASEREMOVE DCW AND DHW IN PLUMBING CHASE
PREPARATORY FOR NEW. PROTECT WASTE ANDPREPARATORY FOR NEW. PROTECT WASTE ANDPREPARATORY FOR NEW. PROTECT WASTE ANDPREPARATORY FOR NEW. PROTECT WASTE AND
VENT PIPING IN PLUMBING CHASE.VENT PIPING IN PLUMBING CHASE.VENT PIPING IN PLUMBING CHASE.VENT PIPING IN PLUMBING CHASE.
5555 REMOVE DRINKING FOUNTAIN COMPLETEREMOVE DRINKING FOUNTAIN COMPLETEREMOVE DRINKING FOUNTAIN COMPLETEREMOVE DRINKING FOUNTAIN COMPLETE
PREPARATORY FOR NEW.PREPARATORY FOR NEW.PREPARATORY FOR NEW.PREPARATORY FOR NEW.
6666 REMOVE 1-1/2" VENT AS SHOWN.REMOVE 1-1/2" VENT AS SHOWN.REMOVE 1-1/2" VENT AS SHOWN.REMOVE 1-1/2" VENT AS SHOWN.
7777 REMOVE 2" WASTE. SEE REMODEL FOR NEWREMOVE 2" WASTE. SEE REMODEL FOR NEWREMOVE 2" WASTE. SEE REMODEL FOR NEWREMOVE 2" WASTE. SEE REMODEL FOR NEW
CONNECTION LOCATION.CONNECTION LOCATION.CONNECTION LOCATION.CONNECTION LOCATION.
8888 REMOVE DCW, DHW, AND DHWR VERTICAL INREMOVE DCW, DHW, AND DHWR VERTICAL INREMOVE DCW, DHW, AND DHWR VERTICAL INREMOVE DCW, DHW, AND DHWR VERTICAL IN
SHAFT.SHAFT.SHAFT.SHAFT.
SCALE:SCALE:SCALE:SCALE:PD102aPD102aPD102aPD102a 1/8" = 1'1/8" = 1'1/8" = 1'1/8" = 1'----0"0"0"0"
ibsbi=O=^ob^=^=mirj_fkd=abjlifqflk=mi^k1111
16161616151515151414141413131313121212121111111110101010999988887777
KKKK
HHHH
FFFF
DDDD
BBBB
AAAA
1111
2222 2222
3333
3333
4444
5555
6666
7777
8888
5555
6666
4444
3333
3333
33333333
33333333
9999
9999
dbkbo^i=abjlifqflk=klqbp
A.A.A.A. REMOVE ALL DOMESTIC COLD, HOT AND CIRCULATING PIPING
THAT IS ACCESSIBLE ABOVE REMODEL AREAS AND WITHIN
PLUMBING CHASES. PIPING THAT IS LOCATED IN EXISTING WALLS
THAT ARE NOT BEING REMOVED WILL BE REVIEWED AND
REPLACED WHERE POSSIBLE.
EXISTING ROOF DRAIN PIPING TO REMAIN. PROTECT DURING
CONSTRUCTION PERIOD.
EXISTING WASTE AND VENT PIPING TO REMAIN. PROTECT DURING
CONSTRUCTION PERIOD. UNLESS NOTED ON PLANS.
EXISTING PLUMBING FIXTURE IN TOILET ROOMS TO REMAIN.
FLUSH VALVES AND LAVATORY FAUCETS WILL BE REPLACED
WITH NEW AS PART OF THE PIPE REPLACEMENT PORTION OF THE
WORK.
EXISTING DRINKING FOUNTAINS WILL BE REPLACED OR
PROTECTED IN PLACE. EACH LOCATION WILL BE REVIEWED WITH
THE OWNER TO DETERMINE WHICH UNITS ARE TO BE REPLACED.
EXISTING MOP SINKS ARE TO REMAIN IN PLACE. NEW FAUCETS
WILL BE PROVIDED IN LOCATIONS THAT ARE DETERMINED TO
NEED REPLACEMENT.
B.B.B.B.
C.C.C.C.
D.D.D.D.
E.E.E.E.
F.F.F.F.
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
PD102b
Level 02 Area
B Plumbing
Demolition
Plan
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
KEY PLAN
A
B
ao^tfkd=klqbp
0000555510101010 10101010 20202020
NOTE
# DESCRIPTION
1111 REMOVE ALL DOMESTIC COLD, HOT ANDREMOVE ALL DOMESTIC COLD, HOT ANDREMOVE ALL DOMESTIC COLD, HOT ANDREMOVE ALL DOMESTIC COLD, HOT AND
RECIRCULATING PIPING COMPLETE PREPARATORYRECIRCULATING PIPING COMPLETE PREPARATORYRECIRCULATING PIPING COMPLETE PREPARATORYRECIRCULATING PIPING COMPLETE PREPARATORY
FOR NEW.FOR NEW.FOR NEW.FOR NEW.
2222 EXISTING WATER CLOSET, URINAL AND LAVATORYEXISTING WATER CLOSET, URINAL AND LAVATORYEXISTING WATER CLOSET, URINAL AND LAVATORYEXISTING WATER CLOSET, URINAL AND LAVATORY
FIXTURES TO REMAIN IN PLACE. PROTECT DURINGFIXTURES TO REMAIN IN PLACE. PROTECT DURINGFIXTURES TO REMAIN IN PLACE. PROTECT DURINGFIXTURES TO REMAIN IN PLACE. PROTECT DURING
CONSTRUCTION. REMOVE ASSOCIATED FLUSHCONSTRUCTION. REMOVE ASSOCIATED FLUSHCONSTRUCTION. REMOVE ASSOCIATED FLUSHCONSTRUCTION. REMOVE ASSOCIATED FLUSH
VALVES, FAUCETS AND TRIM PREPARATORY FORVALVES, FAUCETS AND TRIM PREPARATORY FORVALVES, FAUCETS AND TRIM PREPARATORY FORVALVES, FAUCETS AND TRIM PREPARATORY FOR
NEW.NEW.NEW.NEW.
3333 PROTECT ROOF DRAINS DURING CONSTRUCTION.PROTECT ROOF DRAINS DURING CONSTRUCTION.PROTECT ROOF DRAINS DURING CONSTRUCTION.PROTECT ROOF DRAINS DURING CONSTRUCTION.
4444 REMOVE DCW AND DHW IN PLUMBING CHASEREMOVE DCW AND DHW IN PLUMBING CHASEREMOVE DCW AND DHW IN PLUMBING CHASEREMOVE DCW AND DHW IN PLUMBING CHASE
PREPARATORY FOR NEW. PROTECT WASTE ANDPREPARATORY FOR NEW. PROTECT WASTE ANDPREPARATORY FOR NEW. PROTECT WASTE ANDPREPARATORY FOR NEW. PROTECT WASTE AND
VENT PIPING IN PLUMBING CHASE.VENT PIPING IN PLUMBING CHASE.VENT PIPING IN PLUMBING CHASE.VENT PIPING IN PLUMBING CHASE.
5555 REMOVE 1/2" DCW PIPE IN WALL. C0NTRACTOR TOREMOVE 1/2" DCW PIPE IN WALL. C0NTRACTOR TOREMOVE 1/2" DCW PIPE IN WALL. C0NTRACTOR TOREMOVE 1/2" DCW PIPE IN WALL. C0NTRACTOR TO
VERIFY EXACT ROUTING. REMOVE DRINKINGVERIFY EXACT ROUTING. REMOVE DRINKINGVERIFY EXACT ROUTING. REMOVE DRINKINGVERIFY EXACT ROUTING. REMOVE DRINKING
FOUNTAIN COMPLETE.FOUNTAIN COMPLETE.FOUNTAIN COMPLETE.FOUNTAIN COMPLETE.
6666 REMOVE EXISTING DCW & DHW IN WALL ACCESSREMOVE EXISTING DCW & DHW IN WALL ACCESSREMOVE EXISTING DCW & DHW IN WALL ACCESSREMOVE EXISTING DCW & DHW IN WALL ACCESS
FROM OUTSIDE OF RESTROOM.FROM OUTSIDE OF RESTROOM.FROM OUTSIDE OF RESTROOM.FROM OUTSIDE OF RESTROOM.
7777 EXISTING MOP SINK TO REMAIN. REMOVEEXISTING MOP SINK TO REMAIN. REMOVEEXISTING MOP SINK TO REMAIN. REMOVEEXISTING MOP SINK TO REMAIN. REMOVE
ASSOCIATED FAUCET AND WATER SUPPLY PIPINGASSOCIATED FAUCET AND WATER SUPPLY PIPINGASSOCIATED FAUCET AND WATER SUPPLY PIPINGASSOCIATED FAUCET AND WATER SUPPLY PIPING
PREPARATORY FOR NEW.PREPARATORY FOR NEW.PREPARATORY FOR NEW.PREPARATORY FOR NEW.
8888 REMOVE WATER SUPPLY LINES IN WALLREMOVE WATER SUPPLY LINES IN WALLREMOVE WATER SUPPLY LINES IN WALLREMOVE WATER SUPPLY LINES IN WALL
COMPLETE. CONTRACTOR TO VERIFY EXACTCOMPLETE. CONTRACTOR TO VERIFY EXACTCOMPLETE. CONTRACTOR TO VERIFY EXACTCOMPLETE. CONTRACTOR TO VERIFY EXACT
ROUTING.ROUTING.ROUTING.ROUTING.
9999 REMOVE 2" WASTE LINE AS SHOWN. CONTRACTORREMOVE 2" WASTE LINE AS SHOWN. CONTRACTORREMOVE 2" WASTE LINE AS SHOWN. CONTRACTORREMOVE 2" WASTE LINE AS SHOWN. CONTRACTOR
TO VERIFY EXACT ROUTING.TO VERIFY EXACT ROUTING.TO VERIFY EXACT ROUTING.TO VERIFY EXACT ROUTING.
SCALE:SCALE:SCALE:SCALE:PD102bPD102bPD102bPD102b 1/8" = 1'1/8" = 1'1/8" = 1'1/8" = 1'----0"0"0"0"
ibsbi=O=^ob^=_=mirj_fkd=abjlifqflk=mi^k1111
1111
GGGG
JJJJ
LLLL
MMMM
NNNN
PPPP
QQQQ
EEEE
CCCC
2222 3333 4444 5555
1111
2222
3333
3333 3333
3333
3333
1111
2222
5555
4444
4444
6666
6666
7777 8888
9999
10101010
CAPCAPCAPCAP
CAPCAPCAPCAP
10101010
10101010
5555
dbkbo^i=abjlifqflk=klqbp
A.A.A.A. REMOVE ALL DOMESTIC COLD, HOT AND CIRCULATING PIPING
THAT IS ACCESSIBLE ABOVE REMODEL AREAS AND WITHIN
PLUMBING CHASES. PIPING THAT IS LOCATED IN EXISTING WALLS
THAT ARE NOT BEING REMOVED WILL BE REVIEWED AND
REPLACED WHERE POSSIBLE.
EXISTING ROOF DRAIN PIPING TO REMAIN. PROTECT DURING
CONSTRUCTION PERIOD.
EXISTING WASTE AND VENT PIPING TO REMAIN. PROTECT DURING
CONSTRUCTION PERIOD. UNLESS NOTED ON PLANS.
EXISTING PLUMBING FIXTURE IN TOILET ROOMS TO REMAIN.
FLUSH VALVES AND LAVATORY FAUCETS WILL BE REPLACED
WITH NEW AS PART OF THE PIPE REPLACEMENT PORTION OF THE
WORK.
EXISTING DRINKING FOUNTAINS WILL BE REPLACED OR
PROTECTED IN PLACE. EACH LOCATION WILL BE REVIEWED WITH
THE OWNER TO DETERMINE WHICH UNITS ARE TO BE REPLACED.
EXISTING MOP SINKS ARE TO REMAIN IN PLACE. NEW FAUCETS
WILL BE PROVIDED IN LOCATIONS THAT ARE DETERMINED TO
NEED REPLACEMENT.
B.B.B.B.
C.C.C.C.
D.D.D.D.
E.E.E.E.
F.F.F.F.
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
PD103a
Level 03 Area
A Plumbing
Demolition
Plan
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
KEY PLAN
A
B
ao^tfkd=klqbp
0000555510101010 10101010 20202020
NOTE
# DESCRIPTION
1111 REMOVE ALL DOMESTIC COLD, HOT ANDREMOVE ALL DOMESTIC COLD, HOT ANDREMOVE ALL DOMESTIC COLD, HOT ANDREMOVE ALL DOMESTIC COLD, HOT AND
RECIRCULATING PIPING COMPLETE PREPARATORYRECIRCULATING PIPING COMPLETE PREPARATORYRECIRCULATING PIPING COMPLETE PREPARATORYRECIRCULATING PIPING COMPLETE PREPARATORY
FOR NEW.FOR NEW.FOR NEW.FOR NEW.
2222 EXISTING WATER CLOSET, URINAL AND LAVATORYEXISTING WATER CLOSET, URINAL AND LAVATORYEXISTING WATER CLOSET, URINAL AND LAVATORYEXISTING WATER CLOSET, URINAL AND LAVATORY
FIXTURES TO REMAIN IN PLACE. PROTECT DURINGFIXTURES TO REMAIN IN PLACE. PROTECT DURINGFIXTURES TO REMAIN IN PLACE. PROTECT DURINGFIXTURES TO REMAIN IN PLACE. PROTECT DURING
CONSTRUCTION. REMOVE ASSOCIATED FLUSHCONSTRUCTION. REMOVE ASSOCIATED FLUSHCONSTRUCTION. REMOVE ASSOCIATED FLUSHCONSTRUCTION. REMOVE ASSOCIATED FLUSH
VALVES, FAUCETS AND TRIM PREPARATORY FORVALVES, FAUCETS AND TRIM PREPARATORY FORVALVES, FAUCETS AND TRIM PREPARATORY FORVALVES, FAUCETS AND TRIM PREPARATORY FOR
NEW.NEW.NEW.NEW.
3333 REMOVE EXISTING WATER, WASTE AND VENTREMOVE EXISTING WATER, WASTE AND VENTREMOVE EXISTING WATER, WASTE AND VENTREMOVE EXISTING WATER, WASTE AND VENT
PIPING ASSOCIATED WITH REMOVED SINK.PIPING ASSOCIATED WITH REMOVED SINK.PIPING ASSOCIATED WITH REMOVED SINK.PIPING ASSOCIATED WITH REMOVED SINK.
4444 PROTECT EXISTING ROOF DRAINS DURINGPROTECT EXISTING ROOF DRAINS DURINGPROTECT EXISTING ROOF DRAINS DURINGPROTECT EXISTING ROOF DRAINS DURING
CONSTRUCTION.CONSTRUCTION.CONSTRUCTION.CONSTRUCTION.
5555 REMOVE 1/2" DCW IN WALL.REMOVE 1/2" DCW IN WALL.REMOVE 1/2" DCW IN WALL.REMOVE 1/2" DCW IN WALL.
6666 REMOVE DCW AND DHW IN PLUMBING CHASEREMOVE DCW AND DHW IN PLUMBING CHASEREMOVE DCW AND DHW IN PLUMBING CHASEREMOVE DCW AND DHW IN PLUMBING CHASE
PREPARATORY FOR NEW. PROTECT WASTE ANDPREPARATORY FOR NEW. PROTECT WASTE ANDPREPARATORY FOR NEW. PROTECT WASTE ANDPREPARATORY FOR NEW. PROTECT WASTE AND
VENT PIPING IN PLUMBING CHASE.VENT PIPING IN PLUMBING CHASE.VENT PIPING IN PLUMBING CHASE.VENT PIPING IN PLUMBING CHASE.
7777 REMOVE DRINKING FOUNTAIN COMPLETE.REMOVE DRINKING FOUNTAIN COMPLETE.REMOVE DRINKING FOUNTAIN COMPLETE.REMOVE DRINKING FOUNTAIN COMPLETE.
8888 EXISTING MOP SINK TO REMAIN. REMOVEEXISTING MOP SINK TO REMAIN. REMOVEEXISTING MOP SINK TO REMAIN. REMOVEEXISTING MOP SINK TO REMAIN. REMOVE
ASSOCIATED FAUCET AND WATER SUPPLY PIPINGASSOCIATED FAUCET AND WATER SUPPLY PIPINGASSOCIATED FAUCET AND WATER SUPPLY PIPINGASSOCIATED FAUCET AND WATER SUPPLY PIPING
PREPARATORY FOR NEW.PREPARATORY FOR NEW.PREPARATORY FOR NEW.PREPARATORY FOR NEW.
9999 PROTECT EXISTING 2" VENT THROUGH ROOF. SEEPROTECT EXISTING 2" VENT THROUGH ROOF. SEEPROTECT EXISTING 2" VENT THROUGH ROOF. SEEPROTECT EXISTING 2" VENT THROUGH ROOF. SEE
PL103a FOR NEW CONNECTION.PL103a FOR NEW CONNECTION.PL103a FOR NEW CONNECTION.PL103a FOR NEW CONNECTION.
10101010 REMOVE WASTE PIPE AS SHOWN.REMOVE WASTE PIPE AS SHOWN.REMOVE WASTE PIPE AS SHOWN.REMOVE WASTE PIPE AS SHOWN.
SCALE:SCALE:SCALE:SCALE:PD103aPD103aPD103aPD103a 1/8" = 1'1/8" = 1'1/8" = 1'1/8" = 1'----0"0"0"0"
ibsbi=P=^ob^=^=mirj_fkd=abjlifqflk=mi^k1111
GGGG
JJJJ
LLLL
MMMM
NNNN
PPPP
QQQQ
EEEE
CCCC
2222 3333 4444 5555
1111
22223333
1111
030
MECH ROOM
O-D
CHEMICALS ROOM
0-E
STAIR
O-F
MECH CHASE
032
STORAGE
022A
QA
0-E
STAIR
020
OFFICE
022
OPS
024
TECH ROOM
026F
STUDENTS
026C
OFFICE
026A
OFFICE
011
OFFICE
010
OFFICE
012
OFFICE
028
SHORT TERM STORAGE
016
TIER 2
013
BREAK ROOM
040
BDF
042
CUSTODIAL STORAGE
044
STORAGE
018
OFFICE
038
ELECTRICAL036
CUSTODIAL
034
MECH CHASE
0-J
ELEV
009
IMAGING AND STORAGE
(E)1"
4444
1" DHWR1" DHWR1" DHWR1" DHWR
1 1/2" DHW1 1/2" DHW1 1/2" DHW1 1/2" DHW
3" DCW3" DCW3" DCW3" DCW 2" DCW2" DCW2" DCW2" DCW
1" DHW1" DHW1" DHW1" DHW
1" DHW1" DHW1" DHW1" DHW
PL401PL401PL401PL401
1111
5555
6666
7777
8888
9999
13131313
12121212
11111111
10101010
1"1"1"1"
3"3"3"3"
1 1/2"1 1/2"1 1/2"1 1/2"
PPPP----5555
040040040040
SACSACSACSAC
3/4" COND.3/4" COND.3/4" COND.3/4" COND.
14141414
15151515
16161616
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
PL100a
Level 00 Area
A Plumbing
Remodel Plan
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
KEY PLAN
A
B
ao^tfkd=klqbp
0000555510101010 10101010 20202020
NOTE
# DESCRIPTION
1111 PROVIDE NEW DOMESTIC COLD, HOT ANDPROVIDE NEW DOMESTIC COLD, HOT ANDPROVIDE NEW DOMESTIC COLD, HOT ANDPROVIDE NEW DOMESTIC COLD, HOT AND
RECIRCULATING PIPING SIMILAR TO EXISTINGRECIRCULATING PIPING SIMILAR TO EXISTINGRECIRCULATING PIPING SIMILAR TO EXISTINGRECIRCULATING PIPING SIMILAR TO EXISTING
THROUGHOUT.THROUGHOUT.THROUGHOUT.THROUGHOUT.
2222 EXISTING MOP SINK TO REMAIN. PROVIDE NEWEXISTING MOP SINK TO REMAIN. PROVIDE NEWEXISTING MOP SINK TO REMAIN. PROVIDE NEWEXISTING MOP SINK TO REMAIN. PROVIDE NEW
FAUCET AND WATER SUPPLY PIPING. PROVIDEFAUCET AND WATER SUPPLY PIPING. PROVIDEFAUCET AND WATER SUPPLY PIPING. PROVIDEFAUCET AND WATER SUPPLY PIPING. PROVIDE
BACKFLOW PREVENTER AND PRV FOR CHEMICALBACKFLOW PREVENTER AND PRV FOR CHEMICALBACKFLOW PREVENTER AND PRV FOR CHEMICALBACKFLOW PREVENTER AND PRV FOR CHEMICAL
STATION, SEE DETAIL 9/PL502.STATION, SEE DETAIL 9/PL502.STATION, SEE DETAIL 9/PL502.STATION, SEE DETAIL 9/PL502.
3333 PROVIDE NEW WATER ENTRY, INCLUDINGPROVIDE NEW WATER ENTRY, INCLUDINGPROVIDE NEW WATER ENTRY, INCLUDINGPROVIDE NEW WATER ENTRY, INCLUDING
ISOLATION VALVES, PRESSURE REDUCINGISOLATION VALVES, PRESSURE REDUCINGISOLATION VALVES, PRESSURE REDUCINGISOLATION VALVES, PRESSURE REDUCING
VALVES, BACKFLOW PREVENTER, PRESSUREVALVES, BACKFLOW PREVENTER, PRESSUREVALVES, BACKFLOW PREVENTER, PRESSUREVALVES, BACKFLOW PREVENTER, PRESSURE
GAUGES, STRAINER AND REQUIRED FITTINGS. SEEGAUGES, STRAINER AND REQUIRED FITTINGS. SEEGAUGES, STRAINER AND REQUIRED FITTINGS. SEEGAUGES, STRAINER AND REQUIRED FITTINGS. SEE
DETAIL 1 / PL501.DETAIL 1 / PL501.DETAIL 1 / PL501.DETAIL 1 / PL501.
4444 RISE 3" DCW, 1-1/2" DHW AND 1" DHWR UP INRISE 3" DCW, 1-1/2" DHW AND 1" DHWR UP INRISE 3" DCW, 1-1/2" DHW AND 1" DHWR UP INRISE 3" DCW, 1-1/2" DHW AND 1" DHWR UP IN
SHAFT TO LEVEL ABOVE. SEE PL101A FORSHAFT TO LEVEL ABOVE. SEE PL101A FORSHAFT TO LEVEL ABOVE. SEE PL101A FORSHAFT TO LEVEL ABOVE. SEE PL101A FOR
CONTINUATION.CONTINUATION.CONTINUATION.CONTINUATION.
5555 PROVIDE ISOLATION BALL VALVE IN ACCESSIBLEPROVIDE ISOLATION BALL VALVE IN ACCESSIBLEPROVIDE ISOLATION BALL VALVE IN ACCESSIBLEPROVIDE ISOLATION BALL VALVE IN ACCESSIBLE
LOCATION. TYPICAL.LOCATION. TYPICAL.LOCATION. TYPICAL.LOCATION. TYPICAL.
6666 CONNECT NEW 1" PIPE TO EXISTING AT WALLCONNECT NEW 1" PIPE TO EXISTING AT WALLCONNECT NEW 1" PIPE TO EXISTING AT WALLCONNECT NEW 1" PIPE TO EXISTING AT WALL
PENETRATION PROVIDE ISOLATION VALVE IN RISE.PENETRATION PROVIDE ISOLATION VALVE IN RISE.PENETRATION PROVIDE ISOLATION VALVE IN RISE.PENETRATION PROVIDE ISOLATION VALVE IN RISE.
7777 CONNECT TO EXISTING 4" WATER MAIN AT GATECONNECT TO EXISTING 4" WATER MAIN AT GATECONNECT TO EXISTING 4" WATER MAIN AT GATECONNECT TO EXISTING 4" WATER MAIN AT GATE
VALVE. TRANSITION TO 3" BEFORE PRVVALVE. TRANSITION TO 3" BEFORE PRVVALVE. TRANSITION TO 3" BEFORE PRVVALVE. TRANSITION TO 3" BEFORE PRV
ASSEMBLY.ASSEMBLY.ASSEMBLY.ASSEMBLY.
8888 CONNECT NEW 3/4" WATER TO EXISTING AT WALLCONNECT NEW 3/4" WATER TO EXISTING AT WALLCONNECT NEW 3/4" WATER TO EXISTING AT WALLCONNECT NEW 3/4" WATER TO EXISTING AT WALL
PENETRATION. REINSTALL EXISTING BACK FLOWPENETRATION. REINSTALL EXISTING BACK FLOWPENETRATION. REINSTALL EXISTING BACK FLOWPENETRATION. REINSTALL EXISTING BACK FLOW
PREVENTER IN HORIZONTAL PIPE.PREVENTER IN HORIZONTAL PIPE.PREVENTER IN HORIZONTAL PIPE.PREVENTER IN HORIZONTAL PIPE.
9999 BYPASS VALVE, NORMALLY CLOSED.BYPASS VALVE, NORMALLY CLOSED.BYPASS VALVE, NORMALLY CLOSED.BYPASS VALVE, NORMALLY CLOSED.
10101010 CONNECT NEW 1-1/2" DCW TO WATER HEATERCONNECT NEW 1-1/2" DCW TO WATER HEATERCONNECT NEW 1-1/2" DCW TO WATER HEATERCONNECT NEW 1-1/2" DCW TO WATER HEATER
COLD INLET.COLD INLET.COLD INLET.COLD INLET.
11111111 CONNECT 1" DHWR TO RECIRCULATION PUMP.CONNECT 1" DHWR TO RECIRCULATION PUMP.CONNECT 1" DHWR TO RECIRCULATION PUMP.CONNECT 1" DHWR TO RECIRCULATION PUMP.
12121212 CONNECT NEW 1-1/2" DHW TO WATER HEATER.CONNECT NEW 1-1/2" DHW TO WATER HEATER.CONNECT NEW 1-1/2" DHW TO WATER HEATER.CONNECT NEW 1-1/2" DHW TO WATER HEATER.
13131313 WATER HEATER AND ALL ASSOCIATED VALVES,WATER HEATER AND ALL ASSOCIATED VALVES,WATER HEATER AND ALL ASSOCIATED VALVES,WATER HEATER AND ALL ASSOCIATED VALVES,
HEAT EXCHANGERS AND PUMPS TO REMAIN.HEAT EXCHANGERS AND PUMPS TO REMAIN.HEAT EXCHANGERS AND PUMPS TO REMAIN.HEAT EXCHANGERS AND PUMPS TO REMAIN.
14141414 RISE PUMPED CONDENSATE UP TO 3/4" GRAVITYRISE PUMPED CONDENSATE UP TO 3/4" GRAVITYRISE PUMPED CONDENSATE UP TO 3/4" GRAVITYRISE PUMPED CONDENSATE UP TO 3/4" GRAVITY
CONDENSATE DRAIN LINE.CONDENSATE DRAIN LINE.CONDENSATE DRAIN LINE.CONDENSATE DRAIN LINE.
15151515 ROUTE 3/4" CONDENSATE AS HIGH AS POSSIBLE.ROUTE 3/4" CONDENSATE AS HIGH AS POSSIBLE.ROUTE 3/4" CONDENSATE AS HIGH AS POSSIBLE.ROUTE 3/4" CONDENSATE AS HIGH AS POSSIBLE.
16161616 DROP 3/4" CONDENSATE DOWN ON WALL.DROP 3/4" CONDENSATE DOWN ON WALL.DROP 3/4" CONDENSATE DOWN ON WALL.DROP 3/4" CONDENSATE DOWN ON WALL.
INDIRECT INTO SERVICE SINK. PROVIDE A 1" AIRINDIRECT INTO SERVICE SINK. PROVIDE A 1" AIRINDIRECT INTO SERVICE SINK. PROVIDE A 1" AIRINDIRECT INTO SERVICE SINK. PROVIDE A 1" AIR
GAP.GAP.GAP.GAP.
SCALE:SCALE:SCALE:SCALE:PL100aPL100aPL100aPL100a 1/8" = 1'1/8" = 1'1/8" = 1'1/8" = 1'----0"0"0"0"
ibsbi=MM=^ob^=^=mirj_fkd=objlabi=mi^k1111
16161616151515151414141413131313121212121111111110101010999988887777
KKKK
HHHH
FFFF
DDDD
BBBB
AAAA
1111
2222 3333 4444
5555
6666
6666
8888
8888
7777
9999
10101010
11111111
3/4"3/4"3/4"3/4"
3/4"3/4"3/4"3/4"
3"3"3"3"
1111----1/4"1/4"1/4"1/4"
1"1"1"1"
3/4"3/4"3/4"3/4"
1"1"1"1"
1"1"1"1"
1111----1/4"1/4"1/4"1/4"
3"3"3"3"
12121212
1111----1/4" DCW1/4" DCW1/4" DCW1/4" DCW
3/4"3/4"3/4"3/4"3/4"3/4"3/4"3/4"
4"4"4"4"
1313131314141414
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
PL100b
Level 00 Area
B Plumbing
Remodel Plan
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
KEY PLAN
A
B
ao^tfkd=klqbp
0000555510101010 10101010 20202020
NOTE
#DESCRIPTION
1111 RISE 3/4" DCW AND 3/4" DHW TO SERVICE SINK.RISE 3/4" DCW AND 3/4" DHW TO SERVICE SINK.RISE 3/4" DCW AND 3/4" DHW TO SERVICE SINK.RISE 3/4" DCW AND 3/4" DHW TO SERVICE SINK.
2222 RISE 1-1/4" DHW AND 1" DCW UP TO PLUMBINGRISE 1-1/4" DHW AND 1" DCW UP TO PLUMBINGRISE 1-1/4" DHW AND 1" DCW UP TO PLUMBINGRISE 1-1/4" DHW AND 1" DCW UP TO PLUMBING
CHASE ABOVE.CHASE ABOVE.CHASE ABOVE.CHASE ABOVE.
3333 RISE 2-1/2" DCW UP TO PLUMBING CHASE ABOVE.RISE 2-1/2" DCW UP TO PLUMBING CHASE ABOVE.RISE 2-1/2" DCW UP TO PLUMBING CHASE ABOVE.RISE 2-1/2" DCW UP TO PLUMBING CHASE ABOVE.
4444 RISE 1-1/4" DHW AND 2" DCW UP TO PLUMBINGRISE 1-1/4" DHW AND 2" DCW UP TO PLUMBINGRISE 1-1/4" DHW AND 2" DCW UP TO PLUMBINGRISE 1-1/4" DHW AND 2" DCW UP TO PLUMBING
CHASE ABOVE.CHASE ABOVE.CHASE ABOVE.CHASE ABOVE.
5555 RISE 1-1/4" DHW, 1" DHW AND 3" DCW UP. SEERISE 1-1/4" DHW, 1" DHW AND 3" DCW UP. SEERISE 1-1/4" DHW, 1" DHW AND 3" DCW UP. SEERISE 1-1/4" DHW, 1" DHW AND 3" DCW UP. SEE
PL101b FOR CONTINUATION.PL101b FOR CONTINUATION.PL101b FOR CONTINUATION.PL101b FOR CONTINUATION.
6666 RISE 3/4" DCW UP TO WALL HYDRANT.RISE 3/4" DCW UP TO WALL HYDRANT.RISE 3/4" DCW UP TO WALL HYDRANT.RISE 3/4" DCW UP TO WALL HYDRANT.
7777 WATER ENTRY. SEE DETAIL 1/PL501.WATER ENTRY. SEE DETAIL 1/PL501.WATER ENTRY. SEE DETAIL 1/PL501.WATER ENTRY. SEE DETAIL 1/PL501.
8888 PROVIDE NEW WALL HYDRANT.PROVIDE NEW WALL HYDRANT.PROVIDE NEW WALL HYDRANT.PROVIDE NEW WALL HYDRANT.
9999 CONNECT NEW 1" DHWR PIPE TO EXISTING BEFORECONNECT NEW 1" DHWR PIPE TO EXISTING BEFORECONNECT NEW 1" DHWR PIPE TO EXISTING BEFORECONNECT NEW 1" DHWR PIPE TO EXISTING BEFORE
RECIRCULATION PUMP AND ASSOCIATED VALVES.RECIRCULATION PUMP AND ASSOCIATED VALVES.RECIRCULATION PUMP AND ASSOCIATED VALVES.RECIRCULATION PUMP AND ASSOCIATED VALVES.
10101010 CONNECT TO EXISTING 4" WATER MAIN ATCONNECT TO EXISTING 4" WATER MAIN ATCONNECT TO EXISTING 4" WATER MAIN ATCONNECT TO EXISTING 4" WATER MAIN AT
BUTTERFLY VALVE. TRANSITION TO 3" BEFORE PRVBUTTERFLY VALVE. TRANSITION TO 3" BEFORE PRVBUTTERFLY VALVE. TRANSITION TO 3" BEFORE PRVBUTTERFLY VALVE. TRANSITION TO 3" BEFORE PRV
ASSEMBLY.ASSEMBLY.ASSEMBLY.ASSEMBLY.
11111111 SEE PL101b FOR CONTINUATION.SEE PL101b FOR CONTINUATION.SEE PL101b FOR CONTINUATION.SEE PL101b FOR CONTINUATION.
12121212 CONNECT NEW VENT TO EXISTING VENT ATCONNECT NEW VENT TO EXISTING VENT ATCONNECT NEW VENT TO EXISTING VENT ATCONNECT NEW VENT TO EXISTING VENT AT
APPROXIMATELY THE LOCATION SHOWN.APPROXIMATELY THE LOCATION SHOWN.APPROXIMATELY THE LOCATION SHOWN.APPROXIMATELY THE LOCATION SHOWN.
13131313 CONNECT NEW 1-1/4" DHW TO EXISTING 1-1/4" ATCONNECT NEW 1-1/4" DHW TO EXISTING 1-1/4" ATCONNECT NEW 1-1/4" DHW TO EXISTING 1-1/4" ATCONNECT NEW 1-1/4" DHW TO EXISTING 1-1/4" AT
APPROXIMATELY THE LOCATION SHOWN.APPROXIMATELY THE LOCATION SHOWN.APPROXIMATELY THE LOCATION SHOWN.APPROXIMATELY THE LOCATION SHOWN.
14141414 CONNECT NEW 1-1/4" DCW TO EXISTING 1-1/4"CONNECT NEW 1-1/4" DCW TO EXISTING 1-1/4"CONNECT NEW 1-1/4" DCW TO EXISTING 1-1/4"CONNECT NEW 1-1/4" DCW TO EXISTING 1-1/4"
DCW SERVING WATER HEATER AT APPROXIMATELYDCW SERVING WATER HEATER AT APPROXIMATELYDCW SERVING WATER HEATER AT APPROXIMATELYDCW SERVING WATER HEATER AT APPROXIMATELY
THE LOCATION SHOWN.THE LOCATION SHOWN.THE LOCATION SHOWN.THE LOCATION SHOWN.
SCALE:SCALE:SCALE:SCALE:PL100bPL100bPL100bPL100b 1/8" = 1'1/8" = 1'1/8" = 1'1/8" = 1'----0"0"0"0"
ibsbi=MM=^ob^=_=mirj_fkd=objlabi=mi^k1111
1111
GGGG
JJJJ
LLLL
MMMM
NNNN
PPPP
QQQQ
EEEE
CCCC
2222 3333 4444 5555
1111
130
OFFICE
131
OFFICE
132
STUDY (MED)
1-H
STAIR
122A
OPEN STUDY
129
OFFICE
128
STUDY (SM)
127
STUDY (SM)
126
STUDY (SM)
125
STUDY (MED)
124
STUDY (MED)
122
HD BOOK COLLECTION
1-F
VESTIBULE
110
CIRCULATION RECEPTION
114A
OFFICE
114
INTER LIBRARY LOAN WORKSPACE
112
CHECK-IN
108
OFFICE
106
OFFICE
104
OFFICE
1-B
STAIR
1-A
VESTIBULE
122B
OPEN STUDY
122C
OPEN STUDY
142
BREAKROOM
140
CONFERENCE ROOM
138
OFFICE
136
OFFICE
134
RECEPTION
3" DCW3" DCW3" DCW3" DCW
1 1/2" DHW1 1/2" DHW1 1/2" DHW1 1/2" DHW
1" DHW1" DHW1" DHW1" DHW
PL401PL401PL401PL401
2222
22223333
3333
PPPP----6666
PPPP----4A4A4A4A
1/2"1/2"1/2"1/2"
1" DHW1" DHW1" DHW1" DHW
4444
5555
1111
FCUFCUFCUFCU
3/4" COND.3/4" COND.3/4" COND.3/4" COND.
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
PL101a
Level 01 Area
A Plumbing
Remodel Plan
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
KEY PLAN
A
B
ao^tfkd=klqbp
0000555510101010 10101010 20202020
NOTE
# DESCRIPTION
1111 RISE 1" DCW UP TO FIXTURES ABOVE.RISE 1" DCW UP TO FIXTURES ABOVE.RISE 1" DCW UP TO FIXTURES ABOVE.RISE 1" DCW UP TO FIXTURES ABOVE.
2222 RISE DHW LOOP TO WITHIN 2'-0" OF LAVATORY.RISE DHW LOOP TO WITHIN 2'-0" OF LAVATORY.RISE DHW LOOP TO WITHIN 2'-0" OF LAVATORY.RISE DHW LOOP TO WITHIN 2'-0" OF LAVATORY.
SEE 4/PL401 FOR CONTINUATION.SEE 4/PL401 FOR CONTINUATION.SEE 4/PL401 FOR CONTINUATION.SEE 4/PL401 FOR CONTINUATION.
3333 RISE DHW AND/OR DCW TO FIXTURE ABOVE. SEERISE DHW AND/OR DCW TO FIXTURE ABOVE. SEERISE DHW AND/OR DCW TO FIXTURE ABOVE. SEERISE DHW AND/OR DCW TO FIXTURE ABOVE. SEE
4/PL401 FOR CONTINUATION.4/PL401 FOR CONTINUATION.4/PL401 FOR CONTINUATION.4/PL401 FOR CONTINUATION.
4444 ROUTE 3/4" GRAVITY CONDENSATE LINE AS HIGHROUTE 3/4" GRAVITY CONDENSATE LINE AS HIGHROUTE 3/4" GRAVITY CONDENSATE LINE AS HIGHROUTE 3/4" GRAVITY CONDENSATE LINE AS HIGH
AS POSSIBLE.AS POSSIBLE.AS POSSIBLE.AS POSSIBLE.
5555 RISE PUMPED CONDENSATE UP TO 3/4" GRAVITYRISE PUMPED CONDENSATE UP TO 3/4" GRAVITYRISE PUMPED CONDENSATE UP TO 3/4" GRAVITYRISE PUMPED CONDENSATE UP TO 3/4" GRAVITY
LINE.LINE.LINE.LINE.
SCALE:SCALE:SCALE:SCALE:PL101aPL101aPL101aPL101a 1/8" = 1'1/8" = 1'1/8" = 1'1/8" = 1'----0"0"0"0"
ibsbi=N=^ob^=^=mirj_fkd=objlabi=mi^k1111
16161616151515151414141413131313121212121111111110101010999988887777
KKKK
HHHH
FFFF
DDDD
BBBB
AAAA
3333
4444
1111
2222
2222
08
MECH
156C
PRACTICE
156B
PRACTICE
156A
PRACTICE
156
WORKSPACE
156D
STORAGE
156E
PRACTICE
156F
OFFICE
1-T
ELEV
08A
ELEV EQUIP
192A
SMALL MEETING
158
CONFERENCE ROOM
160A
OFFICE
192
WORKSTATIONS/ FLEX SPACE
192B
OFFICE
160B
OFFICE
192C
STORAGE
190C
STORAGE
190
TRAINING AREA
190A
OFFICE
190B
OFFICE
1-Z
VESTIBULE
188A
OFFICE
188B
CONFERENCE
188
COLLABORATIVE SPACE
186
OFFICE
185
OFFICE
184
OFFICE
183
OFFICE
182
OFFICE
181
OFFICE
179
STUDY
178
STUDY
173
ELECTRICAL
180
ADJUNCT OFFICE
170
DROP IN MATH LAB172
CLASSROOM
174
STUDENT PREP
176
I.T. HELP DESK
175
MATH LAB RECEPTION160
TUTORING ADMIN OPEN AREA
170C
STORAGE
170B
STUDY
170A
STUDY
168
CLASSROOM
166
CLASSROOM
1-U
VESTIBULE
164
CLASSROOM
162
CLASSROOM
PPPP----4444
PPPP----4444
PL401PL401PL401PL401
3333
5555 66665555
5555
7777
8888
8888
3/4" DCW3/4" DCW3/4" DCW3/4" DCW
2 1/2"2 1/2"2 1/2"2 1/2"
3/4" DCW3/4" DCW3/4" DCW3/4" DCW
8888
4"4"4"4"
PPPP----6666
PPPP----6666
PPPP----6666
9999
11111111
2"2"2"2"
10101010
12121212
11111111
11111111
SEE SHEET PL100b FOR SEE SHEET PL100b FOR SEE SHEET PL100b FOR SEE SHEET PL100b FOR
WORK IN THIS AREAWORK IN THIS AREAWORK IN THIS AREAWORK IN THIS AREA
13131313
14141414
15151515
16161616
17171717
18181818
19191919
1/2" DCW1/2" DCW1/2" DCW1/2" DCW
14141414 13131313
2" W2" W2" W2" W
1 1/4"1 1/4"1 1/4"1 1/4"
3/4" DHW3/4" DHW3/4" DHW3/4" DHW
13131313
13131313
WCOWCOWCOWCO
13131313
3/4"3/4"3/4"3/4"1"1"1"1"1"1"1"1"
1"1"1"1"
1"1"1"1"1"1"1"1"
2"2"2"2"
1 1/4"1 1/4"1 1/4"1 1/4"
3" DCW3" DCW3" DCW3" DCW
1"1"1"1"
4444
PPPP----5555
3 GPM3 GPM3 GPM3 GPM
190 SQ. FT.190 SQ. FT.190 SQ. FT.190 SQ. FT.
2% SLOPE2% SLOPE2% SLOPE2% SLOPE
20202020
HTHTHTHT
1111
ollc=ao^fk=abpfdk=klqbp
DESIGN RAINFALL RATE 1.3"/HRDESIGN RAINFALL RATE 1.3"/HRDESIGN RAINFALL RATE 1.3"/HRDESIGN RAINFALL RATE 1.3"/HR
XX GPMXX GPMXX GPMXX GPM
XX SQ. FT.XX SQ. FT.XX SQ. FT.XX SQ. FT.
2% SLOPE2% SLOPE2% SLOPE2% SLOPE
DESIGN GALLONS PER MINUTEDESIGN GALLONS PER MINUTEDESIGN GALLONS PER MINUTEDESIGN GALLONS PER MINUTE
DESIGN ROOF DRAIN AREA (SQ. FT.)DESIGN ROOF DRAIN AREA (SQ. FT.)DESIGN ROOF DRAIN AREA (SQ. FT.)DESIGN ROOF DRAIN AREA (SQ. FT.)
MINIMUM DESIGN PIPE SLOPEMINIMUM DESIGN PIPE SLOPEMINIMUM DESIGN PIPE SLOPEMINIMUM DESIGN PIPE SLOPE
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
PL101b
Level 01 Area
B Plumbing
Remodel Plan
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
KEY PLAN
A
B
ao^tfkd=klqbp
0000555510101010 10101010 20202020
NOTE
# DESCRIPTION
1111 RISE DHW AND DCW UP TO SERVICE SINK ABOVE.RISE DHW AND DCW UP TO SERVICE SINK ABOVE.RISE DHW AND DCW UP TO SERVICE SINK ABOVE.RISE DHW AND DCW UP TO SERVICE SINK ABOVE.
2222 PROVIDE NEW WALL HYDRANT. WATER SUPPLYPROVIDE NEW WALL HYDRANT. WATER SUPPLYPROVIDE NEW WALL HYDRANT. WATER SUPPLYPROVIDE NEW WALL HYDRANT. WATER SUPPLY
FROM BELOW.FROM BELOW.FROM BELOW.FROM BELOW.
3333 EXISTING MOP SINK TO REMAIN. PROVIDE NEWEXISTING MOP SINK TO REMAIN. PROVIDE NEWEXISTING MOP SINK TO REMAIN. PROVIDE NEWEXISTING MOP SINK TO REMAIN. PROVIDE NEW
FAUCET AND WATER SUPPLY PIPING. PROVIDEFAUCET AND WATER SUPPLY PIPING. PROVIDEFAUCET AND WATER SUPPLY PIPING. PROVIDEFAUCET AND WATER SUPPLY PIPING. PROVIDE
BACKFLOW PREVENTER AND PRV FOR CHEMICALBACKFLOW PREVENTER AND PRV FOR CHEMICALBACKFLOW PREVENTER AND PRV FOR CHEMICALBACKFLOW PREVENTER AND PRV FOR CHEMICAL
STATION, SEE DETAIL 9/PL502.STATION, SEE DETAIL 9/PL502.STATION, SEE DETAIL 9/PL502.STATION, SEE DETAIL 9/PL502.
4444 PROVIDE NEW WORK SINK, STAINLESS-STEELPROVIDE NEW WORK SINK, STAINLESS-STEELPROVIDE NEW WORK SINK, STAINLESS-STEELPROVIDE NEW WORK SINK, STAINLESS-STEEL
DROP-IN SINK WITH GOOSENECK FAUCET.DROP-IN SINK WITH GOOSENECK FAUCET.DROP-IN SINK WITH GOOSENECK FAUCET.DROP-IN SINK WITH GOOSENECK FAUCET.
PROVIDE ASSOCIATED WATER, WASTE AND VENTPROVIDE ASSOCIATED WATER, WASTE AND VENTPROVIDE ASSOCIATED WATER, WASTE AND VENTPROVIDE ASSOCIATED WATER, WASTE AND VENT
PIPING TO SUPPORT NEW SINK.PIPING TO SUPPORT NEW SINK.PIPING TO SUPPORT NEW SINK.PIPING TO SUPPORT NEW SINK.
5555 DROP 4" ORD FROM ABOVE ON WARM SIDE OFDROP 4" ORD FROM ABOVE ON WARM SIDE OFDROP 4" ORD FROM ABOVE ON WARM SIDE OFDROP 4" ORD FROM ABOVE ON WARM SIDE OF
INSULATION. EXTEND THROUGH WALL 18" ABOVEINSULATION. EXTEND THROUGH WALL 18" ABOVEINSULATION. EXTEND THROUGH WALL 18" ABOVEINSULATION. EXTEND THROUGH WALL 18" ABOVE
FINISHED GRADE TO DOWNSPOUT NOZZLE.FINISHED GRADE TO DOWNSPOUT NOZZLE.FINISHED GRADE TO DOWNSPOUT NOZZLE.FINISHED GRADE TO DOWNSPOUT NOZZLE.
6666 DROP 3" ORD FROM ABOVE ON WARM SIDE OFDROP 3" ORD FROM ABOVE ON WARM SIDE OFDROP 3" ORD FROM ABOVE ON WARM SIDE OFDROP 3" ORD FROM ABOVE ON WARM SIDE OF
INSULATION. EXTEND THROUGH WALL 18" ABOVEINSULATION. EXTEND THROUGH WALL 18" ABOVEINSULATION. EXTEND THROUGH WALL 18" ABOVEINSULATION. EXTEND THROUGH WALL 18" ABOVE
FINISHED GRADE TO DOWNSPOUT NOZZLE.FINISHED GRADE TO DOWNSPOUT NOZZLE.FINISHED GRADE TO DOWNSPOUT NOZZLE.FINISHED GRADE TO DOWNSPOUT NOZZLE.
7777 RISE 2-1/2" DCW UP TO PLUMBING CHASE ABOVE.RISE 2-1/2" DCW UP TO PLUMBING CHASE ABOVE.RISE 2-1/2" DCW UP TO PLUMBING CHASE ABOVE.RISE 2-1/2" DCW UP TO PLUMBING CHASE ABOVE.
SEE 6/PL401 FOR CONTINUATION.SEE 6/PL401 FOR CONTINUATION.SEE 6/PL401 FOR CONTINUATION.SEE 6/PL401 FOR CONTINUATION.
8888 RISE 1/2" DHW AND/OR DCW TO FIXTURE ABOVE.RISE 1/2" DHW AND/OR DCW TO FIXTURE ABOVE.RISE 1/2" DHW AND/OR DCW TO FIXTURE ABOVE.RISE 1/2" DHW AND/OR DCW TO FIXTURE ABOVE.
SEE PL102b FOR CONTINUATION.SEE PL102b FOR CONTINUATION.SEE PL102b FOR CONTINUATION.SEE PL102b FOR CONTINUATION.
9999 3/4" DHW/DCW FROM BELOW. SEE SHEET PL100b3/4" DHW/DCW FROM BELOW. SEE SHEET PL100b3/4" DHW/DCW FROM BELOW. SEE SHEET PL100b3/4" DHW/DCW FROM BELOW. SEE SHEET PL100b
FOR CONTINUATION.FOR CONTINUATION.FOR CONTINUATION.FOR CONTINUATION.
10101010 ROUTE 4" WASTE BELOW SLAB. CONNECT TOROUTE 4" WASTE BELOW SLAB. CONNECT TOROUTE 4" WASTE BELOW SLAB. CONNECT TOROUTE 4" WASTE BELOW SLAB. CONNECT TO
EXISTING 4" AT APPROXIMATELY THE LOCATIONEXISTING 4" AT APPROXIMATELY THE LOCATIONEXISTING 4" AT APPROXIMATELY THE LOCATIONEXISTING 4" AT APPROXIMATELY THE LOCATION
SHOWN.SHOWN.SHOWN.SHOWN.
11111111 2" WASTE FROM FIXTURE ABOVE.2" WASTE FROM FIXTURE ABOVE.2" WASTE FROM FIXTURE ABOVE.2" WASTE FROM FIXTURE ABOVE.
12121212 CONNECT NEW VENT TO EXISTING VENT.CONNECT NEW VENT TO EXISTING VENT.CONNECT NEW VENT TO EXISTING VENT.CONNECT NEW VENT TO EXISTING VENT.
13131313 SAWCUT FLOOR TO INSTALL NEW WASTE PIPE.SAWCUT FLOOR TO INSTALL NEW WASTE PIPE.SAWCUT FLOOR TO INSTALL NEW WASTE PIPE.SAWCUT FLOOR TO INSTALL NEW WASTE PIPE.
CONTRACTOR TO VERIFY EXACT LOCATION OFCONTRACTOR TO VERIFY EXACT LOCATION OFCONTRACTOR TO VERIFY EXACT LOCATION OFCONTRACTOR TO VERIFY EXACT LOCATION OF
EXISTING WASTE.EXISTING WASTE.EXISTING WASTE.EXISTING WASTE.
14141414 CONNECT NEW WASTE TO EXISTING WASTE ATCONNECT NEW WASTE TO EXISTING WASTE ATCONNECT NEW WASTE TO EXISTING WASTE ATCONNECT NEW WASTE TO EXISTING WASTE AT
APPROXIMATELY THE LOCATION SHOWN.APPROXIMATELY THE LOCATION SHOWN.APPROXIMATELY THE LOCATION SHOWN.APPROXIMATELY THE LOCATION SHOWN.
15151515 RISE 2" DCW AND 1-1/4" DHW UP TO RESTROOMRISE 2" DCW AND 1-1/4" DHW UP TO RESTROOMRISE 2" DCW AND 1-1/4" DHW UP TO RESTROOMRISE 2" DCW AND 1-1/4" DHW UP TO RESTROOM
ABOVE.ABOVE.ABOVE.ABOVE.
16161616 DROP 1-1/4" DHW AND ROUTE AS SHOWN.DROP 1-1/4" DHW AND ROUTE AS SHOWN.DROP 1-1/4" DHW AND ROUTE AS SHOWN.DROP 1-1/4" DHW AND ROUTE AS SHOWN.
17171717 RISE 1-1/4" DHW TO FIXTURES ABOVE.RISE 1-1/4" DHW TO FIXTURES ABOVE.RISE 1-1/4" DHW TO FIXTURES ABOVE.RISE 1-1/4" DHW TO FIXTURES ABOVE.
18181818 RISE 1" DCW UP TO FIXTURES ABOVE. DROP 1"RISE 1" DCW UP TO FIXTURES ABOVE. DROP 1"RISE 1" DCW UP TO FIXTURES ABOVE. DROP 1"RISE 1" DCW UP TO FIXTURES ABOVE. DROP 1"
DHW AND ROUTE AS SHOWN.DHW AND ROUTE AS SHOWN.DHW AND ROUTE AS SHOWN.DHW AND ROUTE AS SHOWN.
19191919 DROP 6" RD DOWN IN WALL OFFSET BELOW SLABDROP 6" RD DOWN IN WALL OFFSET BELOW SLABDROP 6" RD DOWN IN WALL OFFSET BELOW SLABDROP 6" RD DOWN IN WALL OFFSET BELOW SLAB
AND CONNECT TO EXISTING.AND CONNECT TO EXISTING.AND CONNECT TO EXISTING.AND CONNECT TO EXISTING.
20202020 CONNECT 2" ROOF DRAIN TO CANOPY SCUPPER,CONNECT 2" ROOF DRAIN TO CANOPY SCUPPER,CONNECT 2" ROOF DRAIN TO CANOPY SCUPPER,CONNECT 2" ROOF DRAIN TO CANOPY SCUPPER,
SEE ARCHITECTURAL DETAIL. DROP 2" ROOF DRAINSEE ARCHITECTURAL DETAIL. DROP 2" ROOF DRAINSEE ARCHITECTURAL DETAIL. DROP 2" ROOF DRAINSEE ARCHITECTURAL DETAIL. DROP 2" ROOF DRAIN
DOWN IN WALL TO DOWNSPOUT NOZZLE AT 18"DOWN IN WALL TO DOWNSPOUT NOZZLE AT 18"DOWN IN WALL TO DOWNSPOUT NOZZLE AT 18"DOWN IN WALL TO DOWNSPOUT NOZZLE AT 18"
A.F.F. RUN HEAT TRACE IN 2" DRAIN PIPE.A.F.F. RUN HEAT TRACE IN 2" DRAIN PIPE.A.F.F. RUN HEAT TRACE IN 2" DRAIN PIPE.A.F.F. RUN HEAT TRACE IN 2" DRAIN PIPE.
SCALE:SCALE:SCALE:SCALE:PL101bPL101bPL101bPL101b 1/8" = 1'1/8" = 1'1/8" = 1'1/8" = 1'----0"0"0"0"
ibsbi=N=^ob^=_=mirj_fkd=objlabi=mi^k1111
1111
GGGG
JJJJ
LLLL
MMMM
NNNN
PPPP
QQQQ
EEEE
CCCC
2222 3333 4444 5555
1111
2222
228E
VAULT
228B
DCAM
2-D
MECHANICAL
228C
SCANNER
236
SHEET MUSIC
2-E
TECH SERV STORAGE
238
TECH SERVICES
2-G
STAIR
2-H
ELEV
240
OPEN COMPUTERS
234
LARGE COMPUTER CLASSROOM
228A
OFFICE
232
OFFICE
230
OFFICE
228
SPECIAL COLLECTIONS228D
ARCHIVE
224
INSTRUCTION 2
222
INSTRUCTION 1
226
PRESS ROOM
2-A
STAIR
200
OFFICE
245
I.T.
220
OPEN STUDY
218
STUDY (MED)
216
STUDY (MED)
214
STUDY (MED)
2-B
STAIR
212
STUDY (SM)
210
STUDY (SM)
208
STUDY (SM)
204
STUDY (SM)
202
OFFICE
1111
FCUFCUFCUFCU
3333
4444
FSFSFSFS
PL401PL401PL401PL401
5555
PPPP----6666
PL401PL401PL401PL401
4444
3/4" DCW3/4" DCW3/4" DCW3/4" DCW
5555
6666
7777
8888
9999
3/4" COND.3/4" COND.3/4" COND.3/4" COND.
2"2"2"2"
2222
FCUFCUFCUFCU
3/4" COND.3/4" COND.3/4" COND.3/4" COND.
3"3"3"3"
245A245A245A245A
SACSACSACSAC
245B245B245B245B
SACSACSACSAC
3/4" COND.3/4" COND.3/4" COND.3/4" COND.
8888
7777
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
PL102a
Level 02 Area
A Plumbing
Remodel Plan
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
KEY PLAN
A
B
ao^tfkd=klqbp
0000555510101010 10101010 20202020
NOTE
# DESCRIPTION
1111 RISE 1/2" DCW TO FIXTURE ABOVE. SEE PL103aRISE 1/2" DCW TO FIXTURE ABOVE. SEE PL103aRISE 1/2" DCW TO FIXTURE ABOVE. SEE PL103aRISE 1/2" DCW TO FIXTURE ABOVE. SEE PL103a
FOR CONTINUATION.FOR CONTINUATION.FOR CONTINUATION.FOR CONTINUATION.
2222 PROVIDE AND INSTALL AN ANSUL FM200 “TOTALPROVIDE AND INSTALL AN ANSUL FM200 “TOTALPROVIDE AND INSTALL AN ANSUL FM200 “TOTALPROVIDE AND INSTALL AN ANSUL FM200 “TOTAL
FLOOD” CLEAN AGENT FIRE SUPPRESSION SYSTEMFLOOD” CLEAN AGENT FIRE SUPPRESSION SYSTEMFLOOD” CLEAN AGENT FIRE SUPPRESSION SYSTEMFLOOD” CLEAN AGENT FIRE SUPPRESSION SYSTEM
WITH AUTOMATIC DETECTION AND CONTROL TOWITH AUTOMATIC DETECTION AND CONTROL TOWITH AUTOMATIC DETECTION AND CONTROL TOWITH AUTOMATIC DETECTION AND CONTROL TO
PROTECT THE IDENTIFIED AREA(S) OF THEPROTECT THE IDENTIFIED AREA(S) OF THEPROTECT THE IDENTIFIED AREA(S) OF THEPROTECT THE IDENTIFIED AREA(S) OF THE
REMODEL. THE SYSTEM SHALL BE COMPLETEREMODEL. THE SYSTEM SHALL BE COMPLETEREMODEL. THE SYSTEM SHALL BE COMPLETEREMODEL. THE SYSTEM SHALL BE COMPLETE
INCLUDING ALL REQUIRED MECHANICAL ANDINCLUDING ALL REQUIRED MECHANICAL ANDINCLUDING ALL REQUIRED MECHANICAL ANDINCLUDING ALL REQUIRED MECHANICAL AND
ELECTRICAL INSTALLATION, ALL DETECTION ANDELECTRICAL INSTALLATION, ALL DETECTION ANDELECTRICAL INSTALLATION, ALL DETECTION ANDELECTRICAL INSTALLATION, ALL DETECTION AND
CONTROL EQUIPMENT, AGENT STORAGECONTROL EQUIPMENT, AGENT STORAGECONTROL EQUIPMENT, AGENT STORAGECONTROL EQUIPMENT, AGENT STORAGE
CONTAINERS WITH FM-200 AGENT, DISCHARGECONTAINERS WITH FM-200 AGENT, DISCHARGECONTAINERS WITH FM-200 AGENT, DISCHARGECONTAINERS WITH FM-200 AGENT, DISCHARGE
NOZZLES, PIPE AND FITTINGS, MANUAL RELEASENOZZLES, PIPE AND FITTINGS, MANUAL RELEASENOZZLES, PIPE AND FITTINGS, MANUAL RELEASENOZZLES, PIPE AND FITTINGS, MANUAL RELEASE
AND ABORT STATIONS, AUDIBLE AND VISUALAND ABORT STATIONS, AUDIBLE AND VISUALAND ABORT STATIONS, AUDIBLE AND VISUALAND ABORT STATIONS, AUDIBLE AND VISUAL
ALARM DEVICES, AUXILIARY DEVICES ANDALARM DEVICES, AUXILIARY DEVICES ANDALARM DEVICES, AUXILIARY DEVICES ANDALARM DEVICES, AUXILIARY DEVICES AND
CONTROLS, SHUTDOWNS, ALARM INTERFACE,CONTROLS, SHUTDOWNS, ALARM INTERFACE,CONTROLS, SHUTDOWNS, ALARM INTERFACE,CONTROLS, SHUTDOWNS, ALARM INTERFACE,
CAUTION/ADVIDORY SIGNS, FUNCTIONALCAUTION/ADVIDORY SIGNS, FUNCTIONALCAUTION/ADVIDORY SIGNS, FUNCTIONALCAUTION/ADVIDORY SIGNS, FUNCTIONAL
CHECKOUT AND TESTING, TRAINING AND ALLCHECKOUT AND TESTING, TRAINING AND ALLCHECKOUT AND TESTING, TRAINING AND ALLCHECKOUT AND TESTING, TRAINING AND ALL
OTHER REQUIRED OPERATIONS FOR AOTHER REQUIRED OPERATIONS FOR AOTHER REQUIRED OPERATIONS FOR AOTHER REQUIRED OPERATIONS FOR A
FUNCTIONAL UL AND FM APPROVED SYSTEM.FUNCTIONAL UL AND FM APPROVED SYSTEM.FUNCTIONAL UL AND FM APPROVED SYSTEM.FUNCTIONAL UL AND FM APPROVED SYSTEM.
3333 PROTECT EXISTING ROOF DRAIN DURINGPROTECT EXISTING ROOF DRAIN DURINGPROTECT EXISTING ROOF DRAIN DURINGPROTECT EXISTING ROOF DRAIN DURING
CONSTRUCTION.CONSTRUCTION.CONSTRUCTION.CONSTRUCTION.
4444 RO SYSTEM, SEE DETAIL 8/PL501.RO SYSTEM, SEE DETAIL 8/PL501.RO SYSTEM, SEE DETAIL 8/PL501.RO SYSTEM, SEE DETAIL 8/PL501.
5555 CONNECT NEW 2" WASTE TO EXISTING 2" ATCONNECT NEW 2" WASTE TO EXISTING 2" ATCONNECT NEW 2" WASTE TO EXISTING 2" ATCONNECT NEW 2" WASTE TO EXISTING 2" AT
APPROXIMATELY WHE LOCATION SHOWN.APPROXIMATELY WHE LOCATION SHOWN.APPROXIMATELY WHE LOCATION SHOWN.APPROXIMATELY WHE LOCATION SHOWN.
CONTRACTOR TO VERIFY EXACT LOCATION.CONTRACTOR TO VERIFY EXACT LOCATION.CONTRACTOR TO VERIFY EXACT LOCATION.CONTRACTOR TO VERIFY EXACT LOCATION.
6666 RISE NEW 1-1/2" VENT IN WALL ABOVE. SEERISE NEW 1-1/2" VENT IN WALL ABOVE. SEERISE NEW 1-1/2" VENT IN WALL ABOVE. SEERISE NEW 1-1/2" VENT IN WALL ABOVE. SEE
PL103a FOR CONTINUATION.PL103a FOR CONTINUATION.PL103a FOR CONTINUATION.PL103a FOR CONTINUATION.
7777 ROUTE 3/4" GRAVITY CONDENSATE LINE AS HIGHROUTE 3/4" GRAVITY CONDENSATE LINE AS HIGHROUTE 3/4" GRAVITY CONDENSATE LINE AS HIGHROUTE 3/4" GRAVITY CONDENSATE LINE AS HIGH
AS POSSIBLE.AS POSSIBLE.AS POSSIBLE.AS POSSIBLE.
8888 RISE PUMPED CONDENSATE UP TO 3/4" GRAVITYRISE PUMPED CONDENSATE UP TO 3/4" GRAVITYRISE PUMPED CONDENSATE UP TO 3/4" GRAVITYRISE PUMPED CONDENSATE UP TO 3/4" GRAVITY
LINE.LINE.LINE.LINE.
9999 DROP 3/4" CONDENSATE DOWN ON WALL ANDDROP 3/4" CONDENSATE DOWN ON WALL ANDDROP 3/4" CONDENSATE DOWN ON WALL ANDDROP 3/4" CONDENSATE DOWN ON WALL AND
ROUTE AS SHOWN. INDIRECT INTO FLOOR SINK.ROUTE AS SHOWN. INDIRECT INTO FLOOR SINK.ROUTE AS SHOWN. INDIRECT INTO FLOOR SINK.ROUTE AS SHOWN. INDIRECT INTO FLOOR SINK.
SCALE:SCALE:SCALE:SCALE:PL102aPL102aPL102aPL102a 1/8" = 1'1/8" = 1'1/8" = 1'1/8" = 1'----0"0"0"0"
ibsbi=O=^ob^=^=mirj_fkd=objlabi=mi^k1111
16161616151515151414141413131313121212121111111110101010999988887777
KKKK
HHHH
FFFF
DDDD
BBBB
AAAA
1111
252
STUDY SKILLS 252C
STUDY
252D
OFFICE
252E
OFFICE
252F
STORAGE
252G
PREP / STORAGE
252B
STUDY
252A
STUDY
254
OPEN TUTORING
256
WRITING CENTER OPEN TUTORING
260
CLASSROOM
258
CLASSROOM
256C
OFFICE
256B
OFFICE
256A
PREP / STORAGE
264
OFFICE
265
OFFICE
266
STUDY
267
STUDY 268
STUDY
269
STUDY
270
OPEN TUTORING CENTER
270B
PREP / STORAGE
270F
PREFUNCTION
270E
PRE-FUNCTION270D
PRE-FUNCTION
270C
PRE-FUNCTION
280
TR / COMM.286
ADJUNCT OFFICE
270H
STUDY
270J
STORAGE288B
OFFICE
288
ENGLISH TRANSITION CENTER
PPPP----4444
PPPP----6666
PL401PL401PL401PL401
6666
2222
2222
2222
PPPP----6666
PPPP----66663333
4444
5555
5555
5555
4444
5555
2" WASTE2" WASTE2" WASTE2" WASTE
PPPP----5555
5555
2-I
ELECTRICAL
2-V
STAIRS
2-U
HALL
278
CLASSROOM
276
CLASSROOM
274
CLASSROOM
272
CLASSROOM
288C
OFFICE
288D
STUDY
288E
STUDY
288F
STUDY
288A
STUDY
284
WOMEN'S RESTROOM
282
MEN'S RESTROOM
2-R
ELEV
2-W
HALL
2-P
STAIR
299
STOR
288H
STORAGE
288G
STUDY
280A280A280A280A
SACSACSACSAC
280B280B280B280B
SACSACSACSAC
66667777
88889999 3/4" COND.3/4" COND.3/4" COND.3/4" COND.
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
PL102b
Level 02 Area
B Plumbing
Remodel Plan
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
KEY PLAN
A
B
ao^tfkd=klqbp
0000555510101010 10101010 20202020
NOTE
# DESCRIPTION
1111 PROVIDE NEW WORK SINK, STAINLESS-STEELPROVIDE NEW WORK SINK, STAINLESS-STEELPROVIDE NEW WORK SINK, STAINLESS-STEELPROVIDE NEW WORK SINK, STAINLESS-STEEL
DROP-IN SINK WITH GOOSENECK FAUCET.DROP-IN SINK WITH GOOSENECK FAUCET.DROP-IN SINK WITH GOOSENECK FAUCET.DROP-IN SINK WITH GOOSENECK FAUCET.
PROVIDE ASSOCIATED WATER, WASTE AND VENTPROVIDE ASSOCIATED WATER, WASTE AND VENTPROVIDE ASSOCIATED WATER, WASTE AND VENTPROVIDE ASSOCIATED WATER, WASTE AND VENT
PIPING TO SUPPORT NEW SINK.PIPING TO SUPPORT NEW SINK.PIPING TO SUPPORT NEW SINK.PIPING TO SUPPORT NEW SINK.
2222 DROP ROOF DRAIN ON WARM SIDE OFDROP ROOF DRAIN ON WARM SIDE OFDROP ROOF DRAIN ON WARM SIDE OFDROP ROOF DRAIN ON WARM SIDE OF
INSULATION. CONTRACTOR TO COORDINATEINSULATION. CONTRACTOR TO COORDINATEINSULATION. CONTRACTOR TO COORDINATEINSULATION. CONTRACTOR TO COORDINATE
CORE DRILLING WITH WAFFLE SLAB.CORE DRILLING WITH WAFFLE SLAB.CORE DRILLING WITH WAFFLE SLAB.CORE DRILLING WITH WAFFLE SLAB.
3333 CONNECT NEW VENT TO EXISTING VENT.CONNECT NEW VENT TO EXISTING VENT.CONNECT NEW VENT TO EXISTING VENT.CONNECT NEW VENT TO EXISTING VENT.
4444 DROP WASTE DOWN IN WALL. SEE PL101b FORDROP WASTE DOWN IN WALL. SEE PL101b FORDROP WASTE DOWN IN WALL. SEE PL101b FORDROP WASTE DOWN IN WALL. SEE PL101b FOR
CONTINUATION.CONTINUATION.CONTINUATION.CONTINUATION.
5555 1/2" DCW/DHW FROM BELOW. SEE PL101b FOR1/2" DCW/DHW FROM BELOW. SEE PL101b FOR1/2" DCW/DHW FROM BELOW. SEE PL101b FOR1/2" DCW/DHW FROM BELOW. SEE PL101b FOR
CONTINUATION.CONTINUATION.CONTINUATION.CONTINUATION.
6666 RISE PUMPED CONDENSATE UP TO 3/4" GRAVITYRISE PUMPED CONDENSATE UP TO 3/4" GRAVITYRISE PUMPED CONDENSATE UP TO 3/4" GRAVITYRISE PUMPED CONDENSATE UP TO 3/4" GRAVITY
CONDENSATE DRAIN LINE.CONDENSATE DRAIN LINE.CONDENSATE DRAIN LINE.CONDENSATE DRAIN LINE.
7777 ROUTE 3/4" CONDENSATE AS HIGH AS POSSIBLE.ROUTE 3/4" CONDENSATE AS HIGH AS POSSIBLE.ROUTE 3/4" CONDENSATE AS HIGH AS POSSIBLE.ROUTE 3/4" CONDENSATE AS HIGH AS POSSIBLE.
8888 DROP 3/4" CONDENSATE DOWN IN WALL ANDDROP 3/4" CONDENSATE DOWN IN WALL ANDDROP 3/4" CONDENSATE DOWN IN WALL ANDDROP 3/4" CONDENSATE DOWN IN WALL AND
CONNECT TO TAIL PIECE OF DRINKING FOUNTAIN.CONNECT TO TAIL PIECE OF DRINKING FOUNTAIN.CONNECT TO TAIL PIECE OF DRINKING FOUNTAIN.CONNECT TO TAIL PIECE OF DRINKING FOUNTAIN.
9999 EXISTING MOP SINK TO REMAIN. PROVIDE NEWEXISTING MOP SINK TO REMAIN. PROVIDE NEWEXISTING MOP SINK TO REMAIN. PROVIDE NEWEXISTING MOP SINK TO REMAIN. PROVIDE NEW
FAUCET AND WATER SUPPLY PIPING. PROVIDEFAUCET AND WATER SUPPLY PIPING. PROVIDEFAUCET AND WATER SUPPLY PIPING. PROVIDEFAUCET AND WATER SUPPLY PIPING. PROVIDE
BACKFLOW PREVENTER AND PRV FOR CHEMICALBACKFLOW PREVENTER AND PRV FOR CHEMICALBACKFLOW PREVENTER AND PRV FOR CHEMICALBACKFLOW PREVENTER AND PRV FOR CHEMICAL
STATION, SEE DETAIL 9/PL502.STATION, SEE DETAIL 9/PL502.STATION, SEE DETAIL 9/PL502.STATION, SEE DETAIL 9/PL502.
SCALE:SCALE:SCALE:SCALE:PL102bPL102bPL102bPL102b 1/8" = 1'1/8" = 1'1/8" = 1'1/8" = 1'----0"0"0"0"
ibsbi=O=^ob^=_=mirj_fkd=objlabi=mi^k1111
1111
GGGG
JJJJ
LLLL
MMMM
NNNN
PPPP
QQQQ
EEEE
CCCC
2222 3333 4444 5555
340
STUDY (SM)
338
STUDY (SM)
336
STUDY (SM)
334
STUDY (SM)
332
STUDY (SM)
330
STUDY (SM)
324B
ELECTRICAL
324A
MAC EQUIP
322
OFFICE
324
MAC LAB
326
STUDY (LG)
328
STUDY (LG)
342
( QUIET ) OPEN STUDY
320
STUDY (SM)
318
STUDY (SM)
316
STUDY (SM)
314
STUDY (SM)
300
JUVENILE
312
OFFICE
310
OFFICE
3-D
MECH
308
ELECTRICAL
306
STORAGE
304
STUDY (MED)
302
STUDY (MED)
-
Bridge Connection
3-A
BRIDGE CONNECTION
3-B
STAIR 1
382
TEST RM
380
TEST RM
376
Janitors Closet
372
TEST RM
370
TEST RM
360
TEST RM
358
TEST RM
356
TEST RM
364
ELEC
352
STORAGE
350
TEST RM
362
OPEN STUDY
348
TEST RM
346
TEST RM
344
FAMILY STUDY
3-E
MECH CHASE
1111
1111
PL402PL402PL402PL402
1111
2222
PPPP----6666
PL402PL402PL402PL402
2222
1" DHW1" DHW1" DHW1" DHW
1 1/4" DHW1 1/4" DHW1 1/4" DHW1 1/4" DHW
6666
5555
3333
4444
1 1/4" DCW1 1/4" DCW1 1/4" DCW1 1/4" DCW
3"3"3"3"
3333
FCUFCUFCUFCU
3/4" COND.3/4" COND.3/4" COND.3/4" COND.
1111 1111
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
PL103a
Level 03 Area
A Plumbing
Remodel Plan
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
KEY PLAN
A
B
ao^tfkd=klqbp
0000555510101010 10101010 20202020
NOTE
# DESCRIPTION
1111 PROTECT EXISTING ROOF DRAINS DURINGPROTECT EXISTING ROOF DRAINS DURINGPROTECT EXISTING ROOF DRAINS DURINGPROTECT EXISTING ROOF DRAINS DURING
CONSTRUCTION.CONSTRUCTION.CONSTRUCTION.CONSTRUCTION.
2222 RISE 2" VENT UP. INCREASE TO 3" VENT THROUGHRISE 2" VENT UP. INCREASE TO 3" VENT THROUGHRISE 2" VENT UP. INCREASE TO 3" VENT THROUGHRISE 2" VENT UP. INCREASE TO 3" VENT THROUGH
ROOF.ROOF.ROOF.ROOF.
3333 ROUTE 3/4" GRAVITY CONDENSATE LINE AS HIGHROUTE 3/4" GRAVITY CONDENSATE LINE AS HIGHROUTE 3/4" GRAVITY CONDENSATE LINE AS HIGHROUTE 3/4" GRAVITY CONDENSATE LINE AS HIGH
AS POSSIBLE.AS POSSIBLE.AS POSSIBLE.AS POSSIBLE.
4444 RISE PUMPED CONDENSATE UP TO 3/4" GRAVITYRISE PUMPED CONDENSATE UP TO 3/4" GRAVITYRISE PUMPED CONDENSATE UP TO 3/4" GRAVITYRISE PUMPED CONDENSATE UP TO 3/4" GRAVITY
LINE.LINE.LINE.LINE.
5555 1-1/2" VENT FROM BELOW. ROUTE AS SHOWN.1-1/2" VENT FROM BELOW. ROUTE AS SHOWN.1-1/2" VENT FROM BELOW. ROUTE AS SHOWN.1-1/2" VENT FROM BELOW. ROUTE AS SHOWN.
6666 CONNECT NEW 1-1/2" VENT TO EXISTING VTR.CONNECT NEW 1-1/2" VENT TO EXISTING VTR.CONNECT NEW 1-1/2" VENT TO EXISTING VTR.CONNECT NEW 1-1/2" VENT TO EXISTING VTR.
SCALE:SCALE:SCALE:SCALE:PL103aPL103aPL103aPL103a 1/8" = 1'1/8" = 1'1/8" = 1'1/8" = 1'----0"0"0"0"
ibsbi=P=^ob^=^=mirj_fkd=objlabi=mi^k1111
RD
RD
RD RD
RD
(E)4"RD
(E)4"RD(E)4"RD
(E)4"RD
(E)4"RD (E)4"RD
(E)4"RD
(E)4"RD
(E)4"RD
(E)4"(E)5"
(E)4"
(E)4"
(E)5"
(E)4"
(E)4"
(E)4"
(E)4"
(E)4"RD
(E)4"(E)5"
(E)4"RD
16161616151515151414141413131313121212121111111110101010999988887777
KKKK
HHHH
FFFF
DDDD
BBBB
AAAA
(E)ORD(E)ORD(E)ORD(E)ORD
(E)ORD(E)ORD(E)ORD(E)ORD
3" ORD3" ORD3" ORD3" ORD
(E)ORD(E)ORD(E)ORD(E)ORD
4" ORD4" ORD4" ORD4" ORD 3" ORD3" ORD3" ORD3" ORD
(E)ORD(E)ORD(E)ORD(E)ORD
3" ORD3" ORD3" ORD3" ORD
(E)ORD(E)ORD(E)ORD(E)ORD
(E)ORD(E)ORD(E)ORD(E)ORD
3" ORD3" ORD3" ORD3" ORD
3" ORD3" ORD3" ORD3" ORD
4" ORD4" ORD4" ORD4" ORD
(E)ORD(E)ORD(E)ORD(E)ORD
(E)ORD(E)ORD(E)ORD(E)ORD
(E)ORD(E)ORD(E)ORD(E)ORD
(E)ORD(E)ORD(E)ORD(E)ORD
(E)ORD(E)ORD(E)ORD(E)ORD
3333
1111
1111
2222
2222 2222
1111
23 GPM23 GPM23 GPM23 GPM
1700 SQ. FT.1700 SQ. FT.1700 SQ. FT.1700 SQ. FT.
2% SLOPE2% SLOPE2% SLOPE2% SLOPE
23 GPM23 GPM23 GPM23 GPM
1700 SQ. FT.1700 SQ. FT.1700 SQ. FT.1700 SQ. FT.
2% SLOPE2% SLOPE2% SLOPE2% SLOPE
23 GPM23 GPM23 GPM23 GPM
1700 SQ. FT.1700 SQ. FT.1700 SQ. FT.1700 SQ. FT.
2% SLOPE2% SLOPE2% SLOPE2% SLOPE
23 GPM23 GPM23 GPM23 GPM
1700 SQ. FT.1700 SQ. FT.1700 SQ. FT.1700 SQ. FT.
2% SLOPE2% SLOPE2% SLOPE2% SLOPE
23 GPM23 GPM23 GPM23 GPM
1700 SQ. FT.1700 SQ. FT.1700 SQ. FT.1700 SQ. FT.
2% SLOPE2% SLOPE2% SLOPE2% SLOPE
3" ORD3" ORD3" ORD3" ORD
3" ORD3" ORD3" ORD3" ORD
3" ORD3" ORD3" ORD3" ORD
4" ORD4" ORD4" ORD4" ORD
3" ORD3" ORD3" ORD3" ORD
23 GPM23 GPM23 GPM23 GPM
1700 SQ. FT.1700 SQ. FT.1700 SQ. FT.1700 SQ. FT.
2% SLOPE2% SLOPE2% SLOPE2% SLOPE
23 GPM23 GPM23 GPM23 GPM
1700 SQ. FT.1700 SQ. FT.1700 SQ. FT.1700 SQ. FT.
2% SLOPE2% SLOPE2% SLOPE2% SLOPE
23 GPM23 GPM23 GPM23 GPM
1700 SQ. FT.1700 SQ. FT.1700 SQ. FT.1700 SQ. FT.
2% SLOPE2% SLOPE2% SLOPE2% SLOPE
23 GPM23 GPM23 GPM23 GPM
1700 SQ. FT.1700 SQ. FT.1700 SQ. FT.1700 SQ. FT.
2% SLOPE2% SLOPE2% SLOPE2% SLOPE
23 GPM23 GPM23 GPM23 GPM
1700 SQ. FT.1700 SQ. FT.1700 SQ. FT.1700 SQ. FT.
2% SLOPE2% SLOPE2% SLOPE2% SLOPE
23 GPM23 GPM23 GPM23 GPM
1700 SQ. FT.1700 SQ. FT.1700 SQ. FT.1700 SQ. FT.
2% SLOPE2% SLOPE2% SLOPE2% SLOPE
ollc=ao^fk=abpfdk=klqbp
DESIGN RAINFALL RATE 1.3"/HRDESIGN RAINFALL RATE 1.3"/HRDESIGN RAINFALL RATE 1.3"/HRDESIGN RAINFALL RATE 1.3"/HR
XX GPMXX GPMXX GPMXX GPM
XX SQ. FT.XX SQ. FT.XX SQ. FT.XX SQ. FT.
2% SLOPE2% SLOPE2% SLOPE2% SLOPE
DESIGN GALLONS PER MINUTEDESIGN GALLONS PER MINUTEDESIGN GALLONS PER MINUTEDESIGN GALLONS PER MINUTE
DESIGN ROOF DRAIN AREA (SQ. FT.)DESIGN ROOF DRAIN AREA (SQ. FT.)DESIGN ROOF DRAIN AREA (SQ. FT.)DESIGN ROOF DRAIN AREA (SQ. FT.)
MINIMUM DESIGN PIPE SLOPEMINIMUM DESIGN PIPE SLOPEMINIMUM DESIGN PIPE SLOPEMINIMUM DESIGN PIPE SLOPE
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
PL103b
Roof Level
Area B
Plumbing
Remodel Plan
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
ao^tfkd=klqbp
0000555510101010 10101010 20202020
SCALE:SCALE:SCALE:SCALE:PL103bPL103bPL103bPL103b 1/8" = 1'1/8" = 1'1/8" = 1'1/8" = 1'----0"0"0"0"
ollc=ibsbi=^ob^=_=mirj_fkd=objlabi=mi^k1111
NOTE
# DESCRIPTION
1111 PROTECT EXISTING ROOF DRAINS DURINGPROTECT EXISTING ROOF DRAINS DURINGPROTECT EXISTING ROOF DRAINS DURINGPROTECT EXISTING ROOF DRAINS DURING
CONSTRUCTION.CONSTRUCTION.CONSTRUCTION.CONSTRUCTION.
2222 DROP ROOF DRAIN ON WARM SIDE OFDROP ROOF DRAIN ON WARM SIDE OFDROP ROOF DRAIN ON WARM SIDE OFDROP ROOF DRAIN ON WARM SIDE OF
INSULATION. CONTRACTOR TO COORDINATE COREINSULATION. CONTRACTOR TO COORDINATE COREINSULATION. CONTRACTOR TO COORDINATE COREINSULATION. CONTRACTOR TO COORDINATE CORE
DRILLING WITH WAFFLE SLAB.DRILLING WITH WAFFLE SLAB.DRILLING WITH WAFFLE SLAB.DRILLING WITH WAFFLE SLAB.
3333 CONTRACTOR TO COORDINATE CORE DRILLINGCONTRACTOR TO COORDINATE CORE DRILLINGCONTRACTOR TO COORDINATE CORE DRILLINGCONTRACTOR TO COORDINATE CORE DRILLING
WITH WAFFLE SLAB.WITH WAFFLE SLAB.WITH WAFFLE SLAB.WITH WAFFLE SLAB.
EEEE
PPPP----2222
PPPP----3333
PPPP----2222
PPPP----1111
PPPP----1111
PPPP----1111PPPP----1111
WHAWHAWHAWHA----CCCC
014
WOMEN'S RR
015
MEN'S RR
11111111
2222
PPPP----6666
10101010
12121212
2"2"2"2"
JJJJ
5555
144
FAMILY RR
146
MENS
148
WOMENS
147
JANITORS OFFICE
PPPP----2222
PPPP----2222
PPPP----2222
PPPP----2222
PPPP----2222
PPPP----2222
PPPP----2222
PPPP----1111
PPPP----1111
PPPP----1111
PPPP----1111
PPPP----1111
PPPP----1111
PPPP----3333
PPPP----3333
PPPP----3333
PPPP----3333
PPPP----6666
11111111
3333
WHAWHAWHAWHA----CCCC
PPPP----1A1A1A1APPPP----2A2A2A2A 144A
RESTROOM VESTIBULE
13131313
16161616
14141414
10101010
1 1/2"1 1/2"1 1/2"1 1/2"
1 1/4"1 1/4"1 1/4"1 1/4"
2222
22223"3"3"3"
1 1/2"1 1/2"1 1/2"1 1/2"
8888
FDFDFDFD
3/4" COND.3/4" COND.3/4" COND.3/4" COND.
PPPP----5555
22222222
99998888
KKKK
HHHH
PPPP----2222
PPPP----2222
PPPP----2222
PPPP----2222
PPPP----1111
PPPP----1111
PPPP----1111
PPPP----1111
PPPP----2222
PPPP----2222
PPPP----3333
PPPP----3333
PPPP----3333
PPPP----3333
PPPP----3333
PPPP----3333
PPPP----1111
PPPP----1111
PPPP----1111
PPPP----1111
WHWHWHWH
154
MEN'S RESTROOM
152
WOMEN'S RESTROOM
1111
1111
4444
2222
2222
2 1/2" DCW2 1/2" DCW2 1/2" DCW2 1/2" DCW
WHAWHAWHAWHA----CCCC
10101010
2"2"2"2"
WHAWHAWHAWHA----BBBB
1 1/4"1 1/4"1 1/4"1 1/4"1 1/4"1 1/4"1 1/4"1 1/4"
18181818
19191919
2 1/2" DCW2 1/2" DCW2 1/2" DCW2 1/2" DCW
1818181818181818
19191919
1 1/4"1 1/4"1 1/4"1 1/4"1 1/4"1 1/4"1 1/4"1 1/4"
1"1"1"1"
GGGG
JJJJ
5555
PPPP----2222
PPPP----2222
PPPP----3333
PPPP----3333
PPPP----3333
PPPP----2222
PPPP----2222
PPPP----2222
PPPP----2222
PPPP----1111 PPPP----1111
PPPP----1111
PPPP----1111
PPPP----1111
PPPP----1111
1 1/4" DHW1 1/4" DHW1 1/4" DHW1 1/4" DHW
3" DCW3" DCW3" DCW3" DCW
242
ELECTRICAL ROOM
247
MEN'S RESTROOM
248
WOMEN'S RESTROOM
1111 1111
5555
WHAWHAWHAWHA----CCCC
PPPP----5A5A5A5A
249
JANITOR'S CLOSET
1515151510101010
17171717
3/4" COND.3/4" COND.3/4" COND.3/4" COND.
8888
3/4"3/4"3/4"3/4"3/4"3/4"3/4"3/4"
3"3"3"3"
22222222
3/4" COND.3/4" COND.3/4" COND.3/4" COND.
20202020
21212121
11111111
KKKK
HHHH
PPPP----1111
PPPP----1111
PPPP----1111
PPPP----1111
PPPP----2222
PPPP----2222
PPPP----2222
PPPP----2222
PPPP----2222
PPPP----2222
PPPP----3333
PPPP----3333
PPPP----3333
PPPP----1111
PPPP----1111
PPPP----1111
PPPP----1111
PPPP----3333
PPPP----3333
282
MEN'S RESTROOM
284
WOMEN'S RESTROOM
1111
1111
6666
2222
WHAWHAWHAWHA----BBBBWHAWHAWHAWHA----CCCC
2222
1/2" DCW1/2" DCW1/2" DCW1/2" DCW
10101010
10101010
6" RD6" RD6" RD6" RD
11111111
19191919
19191919
1 1/4" DHW1 1/4" DHW1 1/4" DHW1 1/4" DHW
2"2"2"2"2 1/2"2 1/2"2 1/2"2 1/2"
1"1"1"1"
1" DCW1" DCW1" DCW1" DCW
1 1/4"1 1/4"1 1/4"1 1/4"
4" ORD4" ORD4" ORD4" ORD
CCCC
5555
PPPP----4444
PPPP----2A2A2A2A
PPPP----1A1A1A1A
WCOWCOWCOWCO7777
9999
7777
7777 243
MOTHERS
244
FAMILY RR
2-J
MECH CHASE
FDFDFDFD----1111
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
PL401
Enlarged
Plumbing
Remodel
Plans
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
SCALE:SCALE:SCALE:SCALE:PL401PL401PL401PL401 1/4" = 1'1/4" = 1'1/4" = 1'1/4" = 1'----0"0"0"0"
ibsbi=MM=^ob^=^=bki^odba
mirj_fkd=objlabi=mi^k1111
SCALE:SCALE:SCALE:SCALE:PL401PL401PL401PL401 1/4" = 1'1/4" = 1'1/4" = 1'1/4" = 1'----0"0"0"0"
ibsbi=N=^ob^=^=bki^odba
mirj_fkd=objlabi=mi^k2222
SCALE:SCALE:SCALE:SCALE:PL401PL401PL401PL401 1/4" = 1'1/4" = 1'1/4" = 1'1/4" = 1'----0"0"0"0"
ibsbi=N=^ob^=_=bki^odba
mirj_fkd=objlabi=mi^k3333
SCALE:SCALE:SCALE:SCALE:PL401PL401PL401PL401 1/4" = 1'1/4" = 1'1/4" = 1'1/4" = 1'----0"0"0"0"
ibsbi=O=^ob^=^=bki^odba
mirj_fkd=objlabi=mi^k5555
SCALE:SCALE:SCALE:SCALE:PL401PL401PL401PL401 1/4" = 1'1/4" = 1'1/4" = 1'1/4" = 1'----0"0"0"0"
ibsbi=O=^ob^=_=bki^odba
mirj_fkd=objlabi=mi^k6666
NOTE
# DESCRIPTION
1111 EXISTING WATER CLOSET, URINAL AND LAVATORYEXISTING WATER CLOSET, URINAL AND LAVATORYEXISTING WATER CLOSET, URINAL AND LAVATORYEXISTING WATER CLOSET, URINAL AND LAVATORY
FIXTURES TO REMAIN IN PLACE. PROTECT DURINGFIXTURES TO REMAIN IN PLACE. PROTECT DURINGFIXTURES TO REMAIN IN PLACE. PROTECT DURINGFIXTURES TO REMAIN IN PLACE. PROTECT DURING
CONSTRUCTION. PROVIDE NEW FLUSH VALVES,CONSTRUCTION. PROVIDE NEW FLUSH VALVES,CONSTRUCTION. PROVIDE NEW FLUSH VALVES,CONSTRUCTION. PROVIDE NEW FLUSH VALVES,
FAUCETS AND TRIM.FAUCETS AND TRIM.FAUCETS AND TRIM.FAUCETS AND TRIM.
2222 DROP DHW LOOP DOWN IN WALL TO WITHIN 2'-0"DROP DHW LOOP DOWN IN WALL TO WITHIN 2'-0"DROP DHW LOOP DOWN IN WALL TO WITHIN 2'-0"DROP DHW LOOP DOWN IN WALL TO WITHIN 2'-0"
OF LAVATORY.OF LAVATORY.OF LAVATORY.OF LAVATORY.
3333 RISE 3" DCW 1-1/4" DHW & 1" DHWR TO LEVELRISE 3" DCW 1-1/4" DHW & 1" DHWR TO LEVELRISE 3" DCW 1-1/4" DHW & 1" DHWR TO LEVELRISE 3" DCW 1-1/4" DHW & 1" DHWR TO LEVEL
ABOVE. SEE 5/PL401 FOR CONTINUATION.ABOVE. SEE 5/PL401 FOR CONTINUATION.ABOVE. SEE 5/PL401 FOR CONTINUATION.ABOVE. SEE 5/PL401 FOR CONTINUATION.
4444 PROVIDE NEW WALL HYDRANT. WATER SUPPLYPROVIDE NEW WALL HYDRANT. WATER SUPPLYPROVIDE NEW WALL HYDRANT. WATER SUPPLYPROVIDE NEW WALL HYDRANT. WATER SUPPLY
FROM BELOW.FROM BELOW.FROM BELOW.FROM BELOW.
5555 CONTINUE RISE OF 3" DCW, 1-1/4" DHW AND 1"CONTINUE RISE OF 3" DCW, 1-1/4" DHW AND 1"CONTINUE RISE OF 3" DCW, 1-1/4" DHW AND 1"CONTINUE RISE OF 3" DCW, 1-1/4" DHW AND 1"
DHWR TO LEVEL ABOVE. SEE 1/PL402 FORDHWR TO LEVEL ABOVE. SEE 1/PL402 FORDHWR TO LEVEL ABOVE. SEE 1/PL402 FORDHWR TO LEVEL ABOVE. SEE 1/PL402 FOR
CONTINUATION.CONTINUATION.CONTINUATION.CONTINUATION.
6666 DROP ROOF DRAIN ON WARM SIDE OFDROP ROOF DRAIN ON WARM SIDE OFDROP ROOF DRAIN ON WARM SIDE OFDROP ROOF DRAIN ON WARM SIDE OF
INSULATION. CONTRACTOR TO COORDINATE COREINSULATION. CONTRACTOR TO COORDINATE COREINSULATION. CONTRACTOR TO COORDINATE COREINSULATION. CONTRACTOR TO COORDINATE CORE
DRILLING WITH WAFFLE SLAB.DRILLING WITH WAFFLE SLAB.DRILLING WITH WAFFLE SLAB.DRILLING WITH WAFFLE SLAB.
7777 DHW AND/OR DCW FROM BELOW. SEE PL101aDHW AND/OR DCW FROM BELOW. SEE PL101aDHW AND/OR DCW FROM BELOW. SEE PL101aDHW AND/OR DCW FROM BELOW. SEE PL101a
FOR CONTINUATION.FOR CONTINUATION.FOR CONTINUATION.FOR CONTINUATION.
8888 DROP 3/4" CONDENSATE DOWN IN WALL. EXTENDDROP 3/4" CONDENSATE DOWN IN WALL. EXTENDDROP 3/4" CONDENSATE DOWN IN WALL. EXTENDDROP 3/4" CONDENSATE DOWN IN WALL. EXTEND
THROUGH WALL TO INDIRECT INTO SERVICE SINK.THROUGH WALL TO INDIRECT INTO SERVICE SINK.THROUGH WALL TO INDIRECT INTO SERVICE SINK.THROUGH WALL TO INDIRECT INTO SERVICE SINK.
TERMINATE 1" ABOVE SERVICE SINK RIM TOTERMINATE 1" ABOVE SERVICE SINK RIM TOTERMINATE 1" ABOVE SERVICE SINK RIM TOTERMINATE 1" ABOVE SERVICE SINK RIM TO
PROVIDE AIR GAP.PROVIDE AIR GAP.PROVIDE AIR GAP.PROVIDE AIR GAP.
9999 RISE 2" VENT UP. SEE PL103a FORRISE 2" VENT UP. SEE PL103a FORRISE 2" VENT UP. SEE PL103a FORRISE 2" VENT UP. SEE PL103a FOR
CONTINUATION.CONTINUATION.CONTINUATION.CONTINUATION.
10101010 CONNECT NEW VENT TO EXISTING.CONNECT NEW VENT TO EXISTING.CONNECT NEW VENT TO EXISTING.CONNECT NEW VENT TO EXISTING.
11111111 DROP WASTE DOWN IN WALL SEE PL101b FORDROP WASTE DOWN IN WALL SEE PL101b FORDROP WASTE DOWN IN WALL SEE PL101b FORDROP WASTE DOWN IN WALL SEE PL101b FOR
CONTINUATION.CONTINUATION.CONTINUATION.CONTINUATION.
12121212 SAW CUT FLOOR AND ROUTE NEW WASTE ASSAW CUT FLOOR AND ROUTE NEW WASTE ASSAW CUT FLOOR AND ROUTE NEW WASTE ASSAW CUT FLOOR AND ROUTE NEW WASTE AS
SHOWN. CONNECT TO EXISTING WASTE ATSHOWN. CONNECT TO EXISTING WASTE ATSHOWN. CONNECT TO EXISTING WASTE ATSHOWN. CONNECT TO EXISTING WASTE AT
APPROXIMATELY THE LOCATION SHOWN.APPROXIMATELY THE LOCATION SHOWN.APPROXIMATELY THE LOCATION SHOWN.APPROXIMATELY THE LOCATION SHOWN.
CONTRACTOR TO FIELD VERIFY EXACT LOCATIONCONTRACTOR TO FIELD VERIFY EXACT LOCATIONCONTRACTOR TO FIELD VERIFY EXACT LOCATIONCONTRACTOR TO FIELD VERIFY EXACT LOCATION
OF EXISTING WASTE AND DIRECTION OF FLOW.OF EXISTING WASTE AND DIRECTION OF FLOW.OF EXISTING WASTE AND DIRECTION OF FLOW.OF EXISTING WASTE AND DIRECTION OF FLOW.
13131313 RISE 3/4" DCW TO FIXTURES ABOVE.RISE 3/4" DCW TO FIXTURES ABOVE.RISE 3/4" DCW TO FIXTURES ABOVE.RISE 3/4" DCW TO FIXTURES ABOVE.
14141414 CONNECT NEW 3" WASTE FROM ABOVE TOCONNECT NEW 3" WASTE FROM ABOVE TOCONNECT NEW 3" WASTE FROM ABOVE TOCONNECT NEW 3" WASTE FROM ABOVE TO
EXISTING WASTE AT APPROXIMATELY THEEXISTING WASTE AT APPROXIMATELY THEEXISTING WASTE AT APPROXIMATELY THEEXISTING WASTE AT APPROXIMATELY THE
LOCATION SHOWN.LOCATION SHOWN.LOCATION SHOWN.LOCATION SHOWN.
15151515 3" WASTE FROM ABOVE. CONNECT 3" WASTE AND3" WASTE FROM ABOVE. CONNECT 3" WASTE AND3" WASTE FROM ABOVE. CONNECT 3" WASTE AND3" WASTE FROM ABOVE. CONNECT 3" WASTE AND
DROP TO LEVEL ONE.DROP TO LEVEL ONE.DROP TO LEVEL ONE.DROP TO LEVEL ONE.
16161616 DROP 3" WASTE DOWN AND CONNECT TODROP 3" WASTE DOWN AND CONNECT TODROP 3" WASTE DOWN AND CONNECT TODROP 3" WASTE DOWN AND CONNECT TO
EXISTING 6" WASTE.EXISTING 6" WASTE.EXISTING 6" WASTE.EXISTING 6" WASTE.
17171717 3/4" DCW FROM BELOW. CONTINUE 1/2" DCW UP3/4" DCW FROM BELOW. CONTINUE 1/2" DCW UP3/4" DCW FROM BELOW. CONTINUE 1/2" DCW UP3/4" DCW FROM BELOW. CONTINUE 1/2" DCW UP
TO FIXTURE ABOVE.TO FIXTURE ABOVE.TO FIXTURE ABOVE.TO FIXTURE ABOVE.
18181818 DHW AND/OR DCW FROM TUNNEL BELOW.DHW AND/OR DCW FROM TUNNEL BELOW.DHW AND/OR DCW FROM TUNNEL BELOW.DHW AND/OR DCW FROM TUNNEL BELOW.
19191919 DHW AND DCW TO BE RAN IN WALL SPACE.DHW AND DCW TO BE RAN IN WALL SPACE.DHW AND DCW TO BE RAN IN WALL SPACE.DHW AND DCW TO BE RAN IN WALL SPACE.
20202020 DROP 3/4" CONDENSATE DOWN IN SHAFT TODROP 3/4" CONDENSATE DOWN IN SHAFT TODROP 3/4" CONDENSATE DOWN IN SHAFT TODROP 3/4" CONDENSATE DOWN IN SHAFT TO
EXISTING HUB DRAIN. PROVIDE A 1" AIR GAP.EXISTING HUB DRAIN. PROVIDE A 1" AIR GAP.EXISTING HUB DRAIN. PROVIDE A 1" AIR GAP.EXISTING HUB DRAIN. PROVIDE A 1" AIR GAP.
21212121 PROVIDE BACKFLOW PREVENTER AND PRV FORPROVIDE BACKFLOW PREVENTER AND PRV FORPROVIDE BACKFLOW PREVENTER AND PRV FORPROVIDE BACKFLOW PREVENTER AND PRV FOR
CHEMICAL STATION, SEE DETAIL 9/PL502.CHEMICAL STATION, SEE DETAIL 9/PL502.CHEMICAL STATION, SEE DETAIL 9/PL502.CHEMICAL STATION, SEE DETAIL 9/PL502.
22222222 EXISTING MOP SINK TO REMAIN. PROVIDE NEWEXISTING MOP SINK TO REMAIN. PROVIDE NEWEXISTING MOP SINK TO REMAIN. PROVIDE NEWEXISTING MOP SINK TO REMAIN. PROVIDE NEW
FAUCET AND WATER SUPPLY PIPING. PROVIDEFAUCET AND WATER SUPPLY PIPING. PROVIDEFAUCET AND WATER SUPPLY PIPING. PROVIDEFAUCET AND WATER SUPPLY PIPING. PROVIDE
BACKFLOW PREVENTER AND PRV FOR CHEMICALBACKFLOW PREVENTER AND PRV FOR CHEMICALBACKFLOW PREVENTER AND PRV FOR CHEMICALBACKFLOW PREVENTER AND PRV FOR CHEMICAL
STATION, SEE DETAIL 9/PL502.STATION, SEE DETAIL 9/PL502.STATION, SEE DETAIL 9/PL502.STATION, SEE DETAIL 9/PL502.
ao^tfkd=klqbp
00002.52.52.52.55555 5555 10101010
00002.52.52.52.55555 5555 10101010
00002.52.52.52.55555 5555 10101010
00002.52.52.52.55555 5555 10101010
00002.52.52.52.55555 5555 10101010
SCALE:SCALE:SCALE:SCALE:PL401PL401PL401PL401 1/4" = 1'1/4" = 1'1/4" = 1'1/4" = 1'----0"0"0"0"
ibsbi=O=^ob^=^=bki^odba
mirj_fkd=objlabi=mi^k4444
00002.52.52.52.55555 5555 10101010
JJJJ
5555
PPPP----1111
PPPP----1111
PPPP----1111
PPPP----2222
PPPP----2222
PPPP----2222
PPPP----2222
PPPP----1111
PPPP----1111
PPPP----1111
PPPP----3333
PPPP----3333
PPPP----3333
PPPP----2222
PPPP----2222
PPPP----6666 3" DCW3" DCW3" DCW3" DCW
1 1/4" DHW1 1/4" DHW1 1/4" DHW1 1/4" DHW
366
WOMENS
368
MENS
WHAWHAWHAWHA----CCCC
PPPP----2222
PPPP----3333
3333
2222
1111
1111
2222
376
Janitors Closet
1" DHW1" DHW1" DHW1" DHW
4444
5555
6666
3/4" COND.3/4" COND.3/4" COND.3/4" COND.
PPPP----5555
7777
EEEE
5555
PPPP----4444
PPPP----2A2A2A2A
PPPP----6A6A6A6A
PPPP----1A1A1A1A
FCOFCOFCOFCO
344A
MOTHERS ROOM
344B
RESTROOM
344
FAMILY STUDY
1 1/4"1 1/4"1 1/4"1 1/4"
WHAWHAWHAWHA----AAAA
FDFDFDFD----1111
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
PL402
Enlarged
Plumbing
Remodel
Plans
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
00002.52.52.52.55555 5555 10101010
00002.52.52.52.55555 5555 10101010
SCALE:SCALE:SCALE:SCALE:PL402PL402PL402PL402 1/4" = 1'1/4" = 1'1/4" = 1'1/4" = 1'----0"0"0"0"
ibsbi=P=^ob^=^=bki^odba
mirj_fkd=objlabi=mi^k1111
SCALE:SCALE:SCALE:SCALE:PL402PL402PL402PL402 1/4" = 1'1/4" = 1'1/4" = 1'1/4" = 1'----0"0"0"0"
ibsbi=P=^ob^=^=bki^odba
mirj_fkd=objlabi=mi^k2222
ao^tfkd=klqbp
NOTE
# DESCRIPTION
1111 EXISTING WATER CLOSET, URINAL AND LAVATORYEXISTING WATER CLOSET, URINAL AND LAVATORYEXISTING WATER CLOSET, URINAL AND LAVATORYEXISTING WATER CLOSET, URINAL AND LAVATORY
FIXTURES TO REMAIN IN PLACE. PROTECT DURINGFIXTURES TO REMAIN IN PLACE. PROTECT DURINGFIXTURES TO REMAIN IN PLACE. PROTECT DURINGFIXTURES TO REMAIN IN PLACE. PROTECT DURING
CONSTRUCTION. PROVIDE NEW FLUSH VALVES,CONSTRUCTION. PROVIDE NEW FLUSH VALVES,CONSTRUCTION. PROVIDE NEW FLUSH VALVES,CONSTRUCTION. PROVIDE NEW FLUSH VALVES,
FAUCETS AND TRIM.FAUCETS AND TRIM.FAUCETS AND TRIM.FAUCETS AND TRIM.
2222 DROP DHW LOOP DOWN IN WALL TO WITHIN 2'-0"DROP DHW LOOP DOWN IN WALL TO WITHIN 2'-0"DROP DHW LOOP DOWN IN WALL TO WITHIN 2'-0"DROP DHW LOOP DOWN IN WALL TO WITHIN 2'-0"
OF LAVATORY.OF LAVATORY.OF LAVATORY.OF LAVATORY.
3333 3" DCW, 1-1/4" DHW AND 1" DHWR FROM BELOW.3" DCW, 1-1/4" DHW AND 1" DHWR FROM BELOW.3" DCW, 1-1/4" DHW AND 1" DHWR FROM BELOW.3" DCW, 1-1/4" DHW AND 1" DHWR FROM BELOW.
ROUTE AS SHOWN.ROUTE AS SHOWN.ROUTE AS SHOWN.ROUTE AS SHOWN.
4444 DROP 3/4" CONDENSATE DOWN IN WALL. EXTENDDROP 3/4" CONDENSATE DOWN IN WALL. EXTENDDROP 3/4" CONDENSATE DOWN IN WALL. EXTENDDROP 3/4" CONDENSATE DOWN IN WALL. EXTEND
THROUGH WALL TO INDIRECT INTO SERVICE SINK.THROUGH WALL TO INDIRECT INTO SERVICE SINK.THROUGH WALL TO INDIRECT INTO SERVICE SINK.THROUGH WALL TO INDIRECT INTO SERVICE SINK.
TERMINATE 1" ABOVE SERVICE SINK RIM TOTERMINATE 1" ABOVE SERVICE SINK RIM TOTERMINATE 1" ABOVE SERVICE SINK RIM TOTERMINATE 1" ABOVE SERVICE SINK RIM TO
PROVIDE AIR GAP.PROVIDE AIR GAP.PROVIDE AIR GAP.PROVIDE AIR GAP.
5555 DROP 3" WASTE DOWN TO LEVEL 2. SEE PL401DROP 3" WASTE DOWN TO LEVEL 2. SEE PL401DROP 3" WASTE DOWN TO LEVEL 2. SEE PL401DROP 3" WASTE DOWN TO LEVEL 2. SEE PL401
FOR CONTINUATION.FOR CONTINUATION.FOR CONTINUATION.FOR CONTINUATION.
6666 1/2" DCW FROM BELOW.1/2" DCW FROM BELOW.1/2" DCW FROM BELOW.1/2" DCW FROM BELOW.
7777 EXISTING MOP SINK TO REMAIN. PROVIDE NEWEXISTING MOP SINK TO REMAIN. PROVIDE NEWEXISTING MOP SINK TO REMAIN. PROVIDE NEWEXISTING MOP SINK TO REMAIN. PROVIDE NEW
FAUCET AND WATER SUPPLY PIPING. PROVIDEFAUCET AND WATER SUPPLY PIPING. PROVIDEFAUCET AND WATER SUPPLY PIPING. PROVIDEFAUCET AND WATER SUPPLY PIPING. PROVIDE
BACKFLOW PREVENTER AND PRV FOR CHEMICALBACKFLOW PREVENTER AND PRV FOR CHEMICALBACKFLOW PREVENTER AND PRV FOR CHEMICALBACKFLOW PREVENTER AND PRV FOR CHEMICAL
STATION, SEE DETAIL 9/PL502.STATION, SEE DETAIL 9/PL502.STATION, SEE DETAIL 9/PL502.STATION, SEE DETAIL 9/PL502.
180°
ASSE
175
1013
FPSI
180°ASSE
175
1013F
PSI
2012
5 PIPE DIAMETERS10 PIPE DIAMETERS
0 -200 PSI
GAUGE
0 -200 PSI
GAUGE
(ROL SEAL BY CLAVAL)
PRV SET FOR 70 PSI
(ROL SEAL BY CLAVAL)
PRV SET FOR 75 PSI
W/ CAP AND CHAIN
3/4" HOSE CONNECTOR
3/4" DRAIN VALVE
3"2"
2"
2"
2"
2"
2"X2"X2" TEE2"X2"X2" TEE
N.C. VALVE
3" BUTTERFLY
SHUT-OFF VALVE, TYPICAL
OF 2.
INLINE
TURBINE METER
TO BUILDING
3"
2"2"
SEE SHEET M1607 FOR
CONTROL POINT REFERENCE
MINIMUMMINIMUM
W/LOCK
N.C. VALVE
W/LOCK
3"
3"
4" TO 3"
REDUCER.
PRINCIPLE BACKFLOW
2" REDUCED PRESSURE
PREVENTER
PRINCIPLE BACKFLOW
2" REDUCED PRESSURE
PREVENTER
EXTEND TO DRAIN
EXTEND TO DRAIN
3"
TYPICAL
3" TO 2" REDUCER,
TYPICAL
3" TO 2" REDUCER,
TYPICAL
3" TO 2" REDUCER,
2"2"
CLAMPS
WELDED STEEL
WALL BRACKET
ROD
CINCH ANCHORS
THRU-BOLT
ADJUSTABLE
PIPE STAND
ANGLE
TURNBUCKLE
U-BOLT
STRAP
STEEL
EYE
BOLTS
STEEL PLATE
BLOCK WALL
CLAMP
STEEL
CLEVIS
LOCK
NUT C-
WALL BRACKET
STEEL OFFSET
U-BOLTS
CI
N
C
H
A
N
C
H
O
R
S
1/8"x1" RESTRAINING STRAP
ROD
PIPE CLAMP
I-BEAM
EYE
BOLT
TURNBUCKLE
ANCHOR
ROD
ANGLE
U-BOLTS
ANCHOR
LA
G
B
O
L
T
S
O
R
THIS IS REPRESENTED
SINK OR DRAIN
PIPE TO NEAREST FLOOR
BY THIS SYMBOL
BFP
BOLTS ON 9" CENTERS.
LONG WITH FOUR ANCHOR
SIDES OF PIPE. 3'-0"
3/8" CHANNEL BOTH
AND BOLT TO FLANGE
BETWEEN CHANNELS
WELD ANGLE IRON
PIPE FLANGE
"LINK-SEAL" (TM) TYPE WALL
WALL SLEEVE, MODEL WS
EXISTING CONCRETE WALL.
PROVIDE SLEEVE THROUGH
CONCRETE WALL STRUCTURE
"LINK-SEAL" (TM) TYPE WALL
PENETRATION SEAL
20 GUAGE PROTECTIVE SHEILD
FEET OF ANY AIR HANDLER
CONNECTING TO AND WITHIN 10
SPRING VIBRATION ISOLATORS
PIPING INSULATION
CLEVIS ASSEMBLY
HANGER ROD - SEE
SPECIFICATION FOR SIZE
FOR ADDITIONAL
SEE SHEET S5.2c
DETAILS
NOTE:
INSTALL ON ALL PIPING
OF 2 TRUSSES
MUST SPAN MINIMUM
UNISTRUT P-1000
TRUSS OR 'TJI'
BOTTOM CHORD OF
UNISTRUT NUT WITH SPRING
GALVANIZED PROTECTION SHIELD.
360 DEG. COVERAGE/ENCASEMENT
16 GAGE MINIMUM (TYP.)
HIGH DENSITY CALSIUM SILICATE
INSULATION INSERT 360 DEG.
COVERAGE/ENCASEMENT.
STANDARD WEIGHT STEEL PIPE
SLEEVE OF SIZE TO PASS PIPE
FINISHED ESCUTCHEON PLATE
FLUSH AGAINST WALL AND OF
SIZE TO COMPLETELY COVER
OPENING
FINISHED WALL SURFACE
PIPING EXPOSED TO VIEWCONCEALED PIPING
TERMINATE SLEEVE FLUSH WITH
FINISHED WALL SURFACES
SEAL OR CAULK SLEEVES THRU
FIRE WALLS IN A SMOKE TIGHT
MANNER
PIPE AND INSULATION TO BE
CENTERED IN SLEEVE-DO NOT
SUPPORT PIPE FROM SLEEVE
INTERIOR WALLS
2X6 BLOCKING IN
WALL FOR WATER
LINE SUPPORT.
PLUMBING FIXTURE
ESCUTCHEON RING
PIPING TO
15101
WALL STUDS
15105
3/4" DCW
3/4" BALL VALVE
3/8" TUBING
RO UNIT WITH PRE-FILTERS
3/8" DRAIN TUBING
6 GALLON PRESSURE TANK
ROOM HUMIDIFIER,
SEE MECHANICAL
3/8" RO TUBING
3/8" CONDENSATE DRAIN TUBING,
EXTEND TO FLOOR SINK
CONDENSATE RECEIVER, LITTLE
GIANT MODEL VCMA-20. PROVIDE
SHELF AND MOUNT AS HIGH AS
POSSIBLE NEAR HUMIDIFIER UNIT.
SILICONE
WH
18" A.F.G.WALL CLAMP
BALL VALVE, INSTALL
IN ACCESSIBLE LOCATION.
EXTERIOR WALL,
SEE ARCHITECTURAL
FOR WALL THICKNESS.
ROUTE SUPPLY PIPE WITHIN WALL
ON INTERIOR OF BUILDING TO PROTECT
FROM FREEZING. SEE PLAN.
GENERAL INSTALLATION NOTES:
INSTALL WALL HYDRANT (WH) PER
MANUFACTURERS WRITTEN INSTRUCTIONS
TO ENSURE PROPER CONNECTION AND
DRAINAGE OF FIXTURE.
3/4" DCW
CLEANOUT TO GRADE (COTG)FLOOR CLEANOUT (FCO)
1/8" BEND IF CLEANOUT
OCCURS AT END OF LINE
LENGTH TO SUIT
CAST IRON WASTE LINE,
1/8" CAST IRON BEND
WASTE LINE
CAST IRON WASTE LINE,
LENGTH TO SUIT
1/8" CAST IRON BEND
OCCURS AT END OF LINE
1/8" BEND IF CLEANOUT
WASTE LINE
COVER. TOP OF COVER
CLEANOUT AND ACCESS
TO BE FLUSH W/ TOP
OF FLOOR
FLOOR LINE
FINISH GRADE
BRASS CLEANOUT PLUG
W/ COUNTER SUNK HEAD.
TROWEL SMOOTH AND EDGE.
16" SQUARE CONCRETE PAD
STAINLESS STEEL
INCREASE VENT SIZE
BEFORE ROOF STRUCTURE
ONE SIZE LARGER
NO HUB BAND
NO HUB BAND
STAINLESS STEEL
RIGID INSULATION
GRINNELL FIG. 262
STEEL PIPE STRAP
SEE PLANS FOR
STEEL ANGLE
(TYPICAL)
2"x2"x1/4"
(TYPICAL)
CONTINUATION
ROOFING (EPDM)
ROOF STRUCTURE
WELD TO STRUCTURE
LAP SEALANT
2'
-
0
"
MI
N
I
M
U
M
(NON-ACOUSTICAL)
SEALANT
EXTENSION
VENT PIPE
VENT
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
PL501
Plumbing
Details
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
SCALE: NONESCALE: NONESCALE: NONESCALE: NONEPL501PL501PL501PL501
_rfiafkd=t^qbo=bkqov=abq^fi1111
SCALE: NONESCALE: NONESCALE: NONESCALE: NONEPL501PL501PL501PL501
qvmf`^i=mfmb=prmmloqp=abq^fi2222
SCALE: NONESCALE: NONESCALE: NONESCALE: NONEPL501PL501PL501PL501
qvmf`^i=_^`hcilt=mobsbkqbo=abq^fi3333
SCALE: NONESCALE: NONESCALE: NONESCALE: NONEPL501PL501PL501PL501
mfmb=bkqov=^q=`lk`obqb=t^ii=abq^fi4444
SCALE: NONESCALE: NONESCALE: NONESCALE: NONEPL501PL501PL501PL501
mfmb=e^kdbo=abq^fi5555
SCALE: NONESCALE: NONESCALE: NONESCALE: NONEPL501PL501PL501PL501
t^ii=mbkbqo^qflk=abq^fi6666
SCALE: NONESCALE: NONESCALE: NONESCALE: NONEPL501PL501PL501PL501
mfmb=prmmloq=abq^fi7777
SCALE: NONESCALE: NONESCALE: NONESCALE: NONEPL501PL501PL501PL501
ol=^ka=erjfafcfbo=cilt=abq^fi8888
SCALE: NONESCALE: NONESCALE: NONESCALE: NONEPL501PL501PL501PL501
t^ii=evao^kq=abq^fi9999
SCALE: NONESCALE: NONESCALE: NONESCALE: NONEPL501PL501PL501PL501
`ib^klrq=abq^fip11111111
SCALE: NONESCALE: NONESCALE: NONESCALE: NONEPL501PL501PL501PL501
sbkq=qeolrde=ollc=abq^fi10101010
REFERENCE ARCHITECTURAL
24" MIN.
TYPICAL.
TYPICAL.
ROOF INSULATION
AND MEMBRANE.
DRAWINGS.
RE: ARCHITECTURAL
UNDER DECK CLAMP,
CLAMPING RING,
ollc=ao^fk
TYPICAL.
NO-HUB
COUPLING,
PIPE
ROOF DECK, SEE
ARCHITECTURAL
DRAWINGS,
TYPICAL.
2" HIGH SECONDARY DRAIN
DRAWINGS.
AND MEMBRANE.
ROOF INSULATION
RE: ARCHITECTURAL
pb`lka^ov=ollc=ao^fk
TYPICAL.
ROOF DRAIN DOME,
CAST IRON OR ALUMINUM
CEILING
STRUCTURE
LAVATORY
3/4" 1/2"
1/2"2'-0" MAX.
DHW
DHWR
DCW
PIPING IN
WALL
FLOOR
THERMOSTATIC
MIXING VALVE
ASSE 1070
PER 2018 INTERNATIONAL
ENERGY CONSERVATION CODE
LAVATORY
1/2"2'-0" MAX.
PER 2018 INTERNATIONAL
ENERGY CONSERVATION CODE
FLOOR
THERMOSTATIC
MIXING VALVE
ASSE 1070
DCW
DHWR / DHW
DHW
DOWNSPOUT
ANCHOR FLANGE
WALL FLANGE
BOLTED TO WALL
TO WALL
NOZZLE
DOWNSPOUT
CAULK WEATHER
TIGHT
EXTERIOR WALL, SEE
ARCHITECTURAL
DRAIN LEADER,
ANCHORED TO WALL
SECONDARY ROOF
DRAWINGS
IRON PIPE
A VENT RISER
AS WASTE DROP OR
MAY EXTAND UP AS
12"
COVER AND SCREW
CHROME WALL
BATT INSULATION
STAINLESS STEEL
NO-HUB CAST
FLOOR
NO-HUB BAND
CLEANOUT
PLUGGED TEE
07212
WALL
CONNECT TO P-TRAP
SETTING BED
CERAMIC FLOOR TILE
CONTROL
SEEPAGE
DRAIN PIPE SHALL
SHANK
ADJUSTABLE
CLAMPING COLLAR
MEMBRANE
WATERPROOF
NOTE: LOCATE FLOOR DRAIN
IN LOCATION SHOWN ON
ARCHITECTURAL AND/OR
PLUMBING PLANS. SEE ARCH.
FOR LOCATION DIMENSIONS.
CONNECT TO P-TRAP
DRAIN PIPE SHALL
15105
OTHERWISE SPECIFIED
HALF GRATE UNLESS
15140
FLOOR
NPW PIPING
GRAVEL
ALL AROUND)
SAND (3" MIN.
CONCRETE FLOOR
1-1/2" PEX
COMPACTED
PIPE SLEEVE
DIRT FILL
3'-0"
5'-0"
6'-0"
(P-5) SERVICE SINK
SERVICE SINK
HB, CONSISTING OF A 1/2"
BALL VALVE, AND 3/4" HOSE
CONNECTION FOR SUPPLY
TO "CUSTODIAL SOLUTION
STATION (N.I.C.)".
3/4" DHW AND DCW
FLOOR
PRV SET @ 35
PSI AND 5 GPM.
1/2" REDUCED PRESSURE
PRINCIPLE BACKFLOW
PREVENTER.
3/4"
1/2"
1/2" SUPPLY BRANCH,
TYPICAL EACH FLOOR.
PRESSURE GUAGE.
FAUCET
1/2" DRAIN TO FLOOR
SINK WITH 1" AIR GAP
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
PL502
Plumbing
Details
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
SCALE: NONESCALE: NONESCALE: NONESCALE: NONEPL502PL502PL502PL502
ollc=ao^fk=abq^fi1111
SCALE: NONESCALE: NONESCALE: NONESCALE: NONEPL502PL502PL502PL502
aljbpqf`=t^qbo=mfmfkd=Ecolj=^_lsbF
ql=mr_if`=i^s^qlov=abq^fi2222
SCALE: NONESCALE: NONESCALE: NONESCALE: NONEPL502PL502PL502PL502
aljbpqf`=t^qbo=mfmfkd=Ecolj=_biltF
ql=mr_if`=i^s^qlov=abq^fi3333
SCALE: NONESCALE: NONESCALE: NONESCALE: NONEPL502PL502PL502PL502
altkpmlrq=klwwib=^q=t^ii=abq^fi4444
SCALE: NONESCALE: NONESCALE: NONESCALE: NONEPL502PL502PL502PL502
t^ii=`ib^klrq=abq^fi5555
SCALE: NONESCALE: NONESCALE: NONESCALE: NONEPL502PL502PL502PL502
cillo=ao^fk=abq^fi6666
SCALE: NONESCALE: NONESCALE: NONESCALE: NONEPL502PL502PL502PL502
cillo=pfkh=abq^fi7777
SCALE: NONESCALE: NONESCALE: NONESCALE: NONEPL502PL502PL502PL502
rkabodolrka=mfmb=abq^fi8888
SCALE: NONESCALE: NONESCALE: NONESCALE: NONEPL502PL502PL502PL502
pbosf`b=pfkh=abq^fi9999
LEVEL 01
LEVEL 00 (TUNNEL)
LEVEL 02
(E)WATER
HEATER
SKID
PRV
SEE DETAIL
1/PL501
4"
1-1/4"
MV
1 TYP.
P-1
(FC-2)
P-1
(FC-2)
P-1
(FC-2)
3"
1-1/4"
P-4
(FC-1.5)
1" DHWR
P-6
(FC-0.25)
P-6
(FC-0.25)
P-5
(FC-3)
1" 1-1/4"
1-1/4"
P-1
(FC-2)
P-6
(FC-0.25)
P-6
(FC-0.25)
2-1/2"
3"
P-2
(FC-10)
P-2
(FC-10)
P-2
(FC-10)
P-2
(FC-10)
P-3
(FC-5)
P-2
(FC-10)
P-3
(FC-5)
P-2
(FC-10)
P-3
(FC-5)
WHA-C
2-1/2"
P-1
(FC-2)
P-1
(FC-2)
2" 1-1/4"
P-1
(FC-2)
1"
WH
P-3
(FC-5)
P-3
(FC-5)
P-3
(FC-5)
WHA-B
2"
3" 1-1/4"
1"
WH
3/4"
WH
P-6
(FC-0.25)
P-4
(FC-1.5)
2-1/2"
1"
P-1
(FC-2)
WHA-B
2"
1"
P-1
(FC-2)
P-1
(FC-2)
P-1
(FC-2)
P-3
(FC-5)
P-3
(FC-5)
P-1
(FC-2)
P-1
(FC-2)
P-1
(FC-2)
P-1
(FC-2)
P-4
(FC-1.5)
P-6
(FC-0.25)
P-2
(FC-10)
P-2
(FC-10)
P-2
(FC-10)
P-2
(FC-10)
P-3
(FC-5)
WHA-C
2-1/2"
1/2"
P-2
(FC-10)
P-3
(FC-5)
P-2
(FC-10)
P-3
(FC-5)
1"
1"
BYPASSBYPASS
VALVE, NC VALVE, NC
BYPASS
VALVE, NC
P-1
(FC-2)
3/4"
WHWH
3/4"
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
PL601
East Side
Water Flow
Diagram
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
SCALE: NONESCALE: NONESCALE: NONESCALE: NONEPL601PL601PL601PL601
b^pq=pfab=t^qbo=cilt=af^do^j1111
LEVEL 01
LEVEL 00
LEVEL 02
LEVEL 03
(E)4"
(E)WATER
HEATER
SKID
PRV
SEE DETAIL
1/PL501
1-1/2"1"
2"
1"
P-6
(FC-0.25)
MV
1
P-1
(FC-2)
TYP.
P-1
(FC-2)
P-1
(FC-2)
P-1
(FC-2)
3"
P-3
(FC-5)
P-2
(FC-10)
P-2
(FC-10)
WHA-C 2"
P-5
(FC-3)
1"
P-6
(FC-0.25)
P-4
(FC-1.4)
3/4"
P-6
(FC-0.25)
P-6
(FC-0.25)
RO
SEE DETAIL 8/PL501
P-2
(FC-10)
1"
P-1
(FC-2)
P-4
(FC-1.4)
P-6
(FC-0.25)
P-6
(FC-0.25)
3/4"
P-6
(FC-0.25)
3/4"
3"
P-2
(FC-10)
P-1
(FC-2)
1-1/2"
P-1
(FC-2)
1-1/4"
P-2
(FC-10)
P-1
(FC-2)
P-2
(FC-10)
P-3
(FC-5)
P-2
(FC-10)
P-3
(FC-5)
P-2
(FC-10)
P-3
(FC-5)
P-3
(FC-5)
P-1
(FC-2)
WHA-C
P-2
(FC-10)
P-1
(FC-2)
P-1
(FC-2)
P-2
(FC-10)
P-1
(FC-2)
P-2
(FC-10)
3"
1"P-2
(FC-10)
3" 1-1/4"
P-2
(FC-10)
P-2
(FC-10)
P-2
(FC-10)
P-3
(FC-5)
P-2
(FC-10)
P-3
(FC-5)
P-2
(FC-10)
P-3
(FC-5)
WHA-C
P-1
(FC-2)
P-1
(FC-2)
P-1
(FC-2)
P-1
(FC-2)
P-1
(FC-2)
P-1
(FC-2)
P-5
(FC-3)
3"
3"
P-1
(FC-2)
1"
3"
1-1/4"
P-2
(FC-10)
P-1
(FC-2)
P-2
(FC-10)
P-1
(FC-2)
P-2
(FC-10)
P-3
(FC-5)
P-2
(FC-10)
P-2
(FC-10)
P-3
(FC-5)
P-3
(FC-5)
P-1
(FC-2)
P-3
(FC-5)
P-1
(FC-2)
P-2
(FC-10)
WHA-C
P-2
(FC-10)
P-1
(FC-2)
P-1
(FC-2)
1"
1-1/4"3"
P-6
(FC-0.25)
P-2
(FC-10)
P-4
(FC-1.5)
1/2"
3/4"1"
1"
TO CHEMICAL
ROOM
WHA-A
1-1/4"
3/4"
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # : 12242
PL602
West Side
Water Flow
Diagram
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
Bid Set
SCALE: NONESCALE: NONESCALE: NONESCALE: NONEPL602PL602PL602PL602
tbpq=pfab=t^qbo=cilt=af^do^j1111
KEY PLAN
A
B
SCALE: 1/8" = 1’-0"
LEVEL 00 AREA A FIRE PROTECTION DEMOLITION PLAN1
0510 10 20
FD100a
FD100a
Level 00 Area
Demolition
Plan
A Fire Protection
CHEMICALS RM
HALLWAY
MECH. CHASE
STAIRWELL
HALLWAY
STORAGE LIBRARY
STORAGE
LONG TERM
STORAGE
GENERAL
COLLECTION
STORAGE
ELEVATOR CUSTODIAL
HALLWAY
ELEV. EQUIP.
ELEV. EQ.CUSTODIAL
STOR BDF
MENS ROOM WOMEN ROOM
ELECTRICAL
STAIRWELL
IMAGING AND
STORAGE
STORAGE
OFFICE - RON
BREAK ROOM
HALLWAY
SURPLUS
STORAGE
G
J
L
M
N
P
Q
E
C
2 3 4 5 6
21.0780
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
10/27/2022
Bid Set
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # :12242
10/27/2022
1
2
3
FIRE PROTECTION DEMO KEY NOTES
RE: SHEETS FD100a - FD103a
TEST BY: GREG JONES - PCI
TEST LOCATION: SIDEWALK AREA NORTHWEST OF BUILDING
TEST DATE: 8/10/22
FLOW: 1,321 GPM
RESIDUAL PRESSURE: 72 PSI
STATIC PRESSURE: 81 PSI
SYSTEM SUPPLIES THE FOLLOWING PRESSURES/FLOW FOR FIRE PROTECTION:
EXISTING 6" FIRE PROTECTION WATER SUPPLY TO BUILDING TO REMAIN. WATER
CONNECT TO RISER DOWNSTREAM OF ALARM VALVE.
SUPPLY FROM EXTERIOR, FREE STANDING FIRE DEPARTMENT CONNECTION
VALVE ASSEMBLY (RETROFIT), 4" OS&Y VALVE AND ALARM VALVE WITH TRIM. 4"
EXISTING FIRE SPRINKLER RISER TO REMAIN. RISER INCLUDES 4" DOUBLE CHECK
TO ARCHITECTURAL PLANS TO DETERMINE SCOPE AND EXTENT OF REMODEL.
REUSED WHERE COMPLETELY FUNCTIONAL AND COMPLIANT WITH NFPA 13. REFER
OF REMODEL AREA. EXISTING PIPING SUPPORTS AND BRACES MAY REMAIN TO BE
PIPING, COUPLINGS, FITTINGS AND FIRE SPRINKLERS. REMOVE PIPING BACK TO EDGE
SHOULD BE REPLACED WITH NEW PIPING/SPRINKLERS REMOVE ALL EXISTING
INSTALLED IN 1979, ARE NEAR THE END OF THEIR ANTICIPATED SERVICE LIFE AND
TO UNDERGO REMODEL WITH NEW. PIPING/SPRINKLERS IN BASEMENT WERE
REPLACE EXISTING FIRE SPRINKLERS, AND PIPING THROUGHOUT BASEMENT AREAS
4
5
SPRINKLERS (SEE SHEETS FP101A THROUGH FP103A).
BRANCH LINE OUTLETS MAY REMAIN TO BE RE-USED TO SUPPLY NEW FIRE
REMOVE PIPING BACK TO CONNECTION TO EXISTING BRANCH LINE. EXISTING
ESCUTCHEONS AND 1" ARM-OVERS/DROPS TO FACILITATE REMODEL OF AREA.
PROPOSED BUILDING REMODEL. REMOVE ALL PENDENT FIRE SPRINKLERS,
PORTIONS OF THE BUILDING TO REMAIN AND TO BE MODIFIED TO ACCOMMODATE
SIGNIFICANT SERVICE LIFE REMAINING. EXISTING FIRE SPRINKLER SYSTEM IN THESE
FIRE SPRINKLERS AND PIPING ON LEVELS 1-3 WERE INSTALLED IN 1999 AND HAVE
AREAS TO MAINTAIN WATER SUPPLY.
RECONNECT PIPING TO NEW FIRE SPRINKLER PIPING THROUGHOUT REMODEL
EXISTING FIRE SPRINKLERS AND PIPING OUTSIDE OF REMODEL AREA TO REMAIN.
EXISTING 4" VERTICAL FEED MAIN INSTALLED IN MECHANICAL SHAFT TO REMAIN.
6
EACH FLOOR LEVEL TO REMAIN.
EXISTING FIRE SPRINKLER CONTROL VALVE TO ISOLATE FIRE SPRINKLERS ON
7
B (1ST AND 2ND LEVELS) TO REMAIN.
EXISTING 3" HORIZONTAL FEED MAIN TO SUPPLY FIRE SPRINKLER ZONES IN AREA
8
CLEAN AGENT FIRE SUPPRESSION SYSTEMS.
NO WATER FILLED PIPING WILL BE ALLOWED WITHIN SPACES PROTECTED BY
REQUIRED TO MAINTAIN WATER SUPPLY TO FIRE SPRINKLERS IN ADJACENT AREAS.
SUPPORTS AND BRACES FROM ENTIRE AREA. ROUTE PIPING AROUND AREA AS
FROM SPACE. REMOVE FIRE SPRINKLERS, ESCUTCHEONS, PIPING, FITTINGS
AGENT FIRE SUPPRESSION SYSTEM. REMOVE ALL FIRE SPRINKLER PROTECTION
AREA TO BE PROTECTED BY VESDA SMOKE DETECTION SYSTEM AND CLEAN
9
10
AND REMOUNT FIRE EXTINGUISHER IN NEW, SMALLER CABINET.
REMOVE CABINET VALVE AND SUPPLY PIPING. PATCH REMAINING HOLE IN WALL
THIS BUILDING PROTECTED THROUGHOUT BY AUTOMATIC FIRE SPRINKLERS.
REMOVED. OCCUPANT USE HOSE CABINETS ARE NOT REQUIRED BY CODE FOR
EXISTING OCCUPANT USE (1-1/2") FIRE HOSE VALVE WITH HOSE ALREADY
1
2
5
3
3 3 3
33
3
9
9
4
9
999
9 9
99
H
O
S
E
H
O
S
E
HOSE
KEY PLAN
A
B
SCALE: 1/8" = 1’-0"
LEVEL 01 AREA A FIRE PROTECTION DEMOLITION PLAN1
0510 10 20
FD101a FD101a
Demolition
Plan
A Fire Protection
Level 01 Area
Not Enclosed
MAC LAB
OFFICE - MARK
SYSTEMS LIB -
ASSISTANT
UNIV LIBRARIAN
CATALOG
LIBRARIAN -
SOUND TRAP
GROUP STUDY
MEDIUM MECH.
STAIR
STAIR
ELEV.
STUDENT
ENGAG. LI -
DIGITAL
CONTENT
SPECIALIST -
MAC LAB SUPER
- REBEKAH
STUDENT BREAK
ROOM
MAC LAB SUPER
- REBEKAH
INTERLIBRARY
LOAN
SUPERVISOR
MAC LAB EQUIP
OFFICE - CHRIS
OFFICE -
GROUP STUDY
LARGE
MECH
STAIRWELL VESTIBULE GROUP STUDY
STAIRWELL
VESTIBULE
VESTIBULE CUST.
MENS WOMENS
LIBRARY NEW
BOOKS AND
SEASONAL
BOOKS
VESTIBULE
TEC SERVICES
MECH
MAIN
CIRCULATION
DESK
CIRCULATION
SUPER - EMMIE
MECH
LITERACY
INFO
LIB
REFERENCE
21.0780
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
10/27/2022
Bid Set
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # :12242
10/27/2022
1
2
3
FIRE PROTECTION DEMO KEY NOTES
RE: SHEETS FD100a - FD103a
TEST BY: GREG JONES - PCI
TEST LOCATION: SIDEWALK AREA NORTHWEST OF BUILDING
TEST DATE: 8/10/22
FLOW: 1,321 GPM
RESIDUAL PRESSURE: 72 PSI
STATIC PRESSURE: 81 PSI
SYSTEM SUPPLIES THE FOLLOWING PRESSURES/FLOW FOR FIRE PROTECTION:
EXISTING 6" FIRE PROTECTION WATER SUPPLY TO BUILDING TO REMAIN. WATER
CONNECT TO RISER DOWNSTREAM OF ALARM VALVE.
SUPPLY FROM EXTERIOR, FREE STANDING FIRE DEPARTMENT CONNECTION
VALVE ASSEMBLY (RETROFIT), 4" OS&Y VALVE AND ALARM VALVE WITH TRIM. 4"
EXISTING FIRE SPRINKLER RISER TO REMAIN. RISER INCLUDES 4" DOUBLE CHECK
TO ARCHITECTURAL PLANS TO DETERMINE SCOPE AND EXTENT OF REMODEL.
REUSED WHERE COMPLETELY FUNCTIONAL AND COMPLIANT WITH NFPA 13. REFER
OF REMODEL AREA. EXISTING PIPING SUPPORTS AND BRACES MAY REMAIN TO BE
PIPING, COUPLINGS, FITTINGS AND FIRE SPRINKLERS. REMOVE PIPING BACK TO EDGE
SHOULD BE REPLACED WITH NEW PIPING/SPRINKLERS REMOVE ALL EXISTING
INSTALLED IN 1979, ARE NEAR THE END OF THEIR ANTICIPATED SERVICE LIFE AND
TO UNDERGO REMODEL WITH NEW. PIPING/SPRINKLERS IN BASEMENT WERE
REPLACE EXISTING FIRE SPRINKLERS, AND PIPING THROUGHOUT BASEMENT AREAS
4
5
SPRINKLERS (SEE SHEETS FP101A THROUGH FP103A).
BRANCH LINE OUTLETS MAY REMAIN TO BE RE-USED TO SUPPLY NEW FIRE
REMOVE PIPING BACK TO CONNECTION TO EXISTING BRANCH LINE. EXISTING
ESCUTCHEONS AND 1" ARM-OVERS/DROPS TO FACILITATE REMODEL OF AREA.
PROPOSED BUILDING REMODEL. REMOVE ALL PENDENT FIRE SPRINKLERS,
PORTIONS OF THE BUILDING TO REMAIN AND TO BE MODIFIED TO ACCOMMODATE
SIGNIFICANT SERVICE LIFE REMAINING. EXISTING FIRE SPRINKLER SYSTEM IN THESE
FIRE SPRINKLERS AND PIPING ON LEVELS 1-3 WERE INSTALLED IN 1999 AND HAVE
AREAS TO MAINTAIN WATER SUPPLY.
RECONNECT PIPING TO NEW FIRE SPRINKLER PIPING THROUGHOUT REMODEL
EXISTING FIRE SPRINKLERS AND PIPING OUTSIDE OF REMODEL AREA TO REMAIN.
EXISTING 4" VERTICAL FEED MAIN INSTALLED IN MECHANICAL SHAFT TO REMAIN.
6
EACH FLOOR LEVEL TO REMAIN.
EXISTING FIRE SPRINKLER CONTROL VALVE TO ISOLATE FIRE SPRINKLERS ON
7
B (1ST AND 2ND LEVELS) TO REMAIN.
EXISTING 3" HORIZONTAL FEED MAIN TO SUPPLY FIRE SPRINKLER ZONES IN AREA
8
CLEAN AGENT FIRE SUPPRESSION SYSTEMS.
NO WATER FILLED PIPING WILL BE ALLOWED WITHIN SPACES PROTECTED BY
REQUIRED TO MAINTAIN WATER SUPPLY TO FIRE SPRINKLERS IN ADJACENT AREAS.
SUPPORTS AND BRACES FROM ENTIRE AREA. ROUTE PIPING AROUND AREA AS
FROM SPACE. REMOVE FIRE SPRINKLERS, ESCUTCHEONS, PIPING, FITTINGS
AGENT FIRE SUPPRESSION SYSTEM. REMOVE ALL FIRE SPRINKLER PROTECTION
AREA TO BE PROTECTED BY VESDA SMOKE DETECTION SYSTEM AND CLEAN
9
10
AND REMOUNT FIRE EXTINGUISHER IN NEW, SMALLER CABINET.
REMOVE CABINET VALVE AND SUPPLY PIPING. PATCH REMAINING HOLE IN WALL
THIS BUILDING PROTECTED THROUGHOUT BY AUTOMATIC FIRE SPRINKLERS.
REMOVED. OCCUPANT USE HOSE CABINETS ARE NOT REQUIRED BY CODE FOR
EXISTING OCCUPANT USE (1-1/2") FIRE HOSE VALVE WITH HOSE ALREADY
4
4 4
4
44
44
4
4 4
4
4
4
4
4
4
4
9
9
9
9
9
9
9
10
10
10
5
6
KEY PLAN
A
B
SCALE: 1/8" = 1’-0"
LEVEL 01 AREA B FIRE PROTECTION DEMOLITION PLAN1
0510 10 20
FD101b
FD101b
Demolition
Plan
B Fire Protection
Level 01 Area
MED OFFICE
WOMENS MENS
CLASSROOM/MULTI-USE
MED OFFICE
MECHANICAL OFFICE - BRIAN
ELEV. EQUIP.
ELEV
OFFICE - DAVE
OFFICE PRACTICE ROOM
OFFICE - MARK
CONF. ROOM
MED OFFICE
ELECTRICAL
STAIRS
16
16
15
15
14
14
13
13
12
12
11
11
10
10
9
9
8
87
K
H
F
D
B
A
L
21.0780
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
10/27/2022
Bid Set
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # :12242
10/27/2022
1
2
3
FIRE PROTECTION DEMO KEY NOTES
RE: SHEETS FD100a - FD103a
TEST BY: GREG JONES - PCI
TEST LOCATION: SIDEWALK AREA NORTHWEST OF BUILDING
TEST DATE: 8/10/22
FLOW: 1,321 GPM
RESIDUAL PRESSURE: 72 PSI
STATIC PRESSURE: 81 PSI
SYSTEM SUPPLIES THE FOLLOWING PRESSURES/FLOW FOR FIRE PROTECTION:
EXISTING 6" FIRE PROTECTION WATER SUPPLY TO BUILDING TO REMAIN. WATER
CONNECT TO RISER DOWNSTREAM OF ALARM VALVE.
SUPPLY FROM EXTERIOR, FREE STANDING FIRE DEPARTMENT CONNECTION
VALVE ASSEMBLY (RETROFIT), 4" OS&Y VALVE AND ALARM VALVE WITH TRIM. 4"
EXISTING FIRE SPRINKLER RISER TO REMAIN. RISER INCLUDES 4" DOUBLE CHECK
TO ARCHITECTURAL PLANS TO DETERMINE SCOPE AND EXTENT OF REMODEL.
REUSED WHERE COMPLETELY FUNCTIONAL AND COMPLIANT WITH NFPA 13. REFER
OF REMODEL AREA. EXISTING PIPING SUPPORTS AND BRACES MAY REMAIN TO BE
PIPING, COUPLINGS, FITTINGS AND FIRE SPRINKLERS. REMOVE PIPING BACK TO EDGE
SHOULD BE REPLACED WITH NEW PIPING/SPRINKLERS REMOVE ALL EXISTING
INSTALLED IN 1979, ARE NEAR THE END OF THEIR ANTICIPATED SERVICE LIFE AND
TO UNDERGO REMODEL WITH NEW. PIPING/SPRINKLERS IN BASEMENT WERE
REPLACE EXISTING FIRE SPRINKLERS, AND PIPING THROUGHOUT BASEMENT AREAS
4
5
SPRINKLERS (SEE SHEETS FP101A THROUGH FP103A).
BRANCH LINE OUTLETS MAY REMAIN TO BE RE-USED TO SUPPLY NEW FIRE
REMOVE PIPING BACK TO CONNECTION TO EXISTING BRANCH LINE. EXISTING
ESCUTCHEONS AND 1" ARM-OVERS/DROPS TO FACILITATE REMODEL OF AREA.
PROPOSED BUILDING REMODEL. REMOVE ALL PENDENT FIRE SPRINKLERS,
PORTIONS OF THE BUILDING TO REMAIN AND TO BE MODIFIED TO ACCOMMODATE
SIGNIFICANT SERVICE LIFE REMAINING. EXISTING FIRE SPRINKLER SYSTEM IN THESE
FIRE SPRINKLERS AND PIPING ON LEVELS 1-3 WERE INSTALLED IN 1999 AND HAVE
AREAS TO MAINTAIN WATER SUPPLY.
RECONNECT PIPING TO NEW FIRE SPRINKLER PIPING THROUGHOUT REMODEL
EXISTING FIRE SPRINKLERS AND PIPING OUTSIDE OF REMODEL AREA TO REMAIN.
EXISTING 4" VERTICAL FEED MAIN INSTALLED IN MECHANICAL SHAFT TO REMAIN.
6
EACH FLOOR LEVEL TO REMAIN.
EXISTING FIRE SPRINKLER CONTROL VALVE TO ISOLATE FIRE SPRINKLERS ON
7
B (1ST AND 2ND LEVELS) TO REMAIN.
EXISTING 3" HORIZONTAL FEED MAIN TO SUPPLY FIRE SPRINKLER ZONES IN AREA
8
CLEAN AGENT FIRE SUPPRESSION SYSTEMS.
NO WATER FILLED PIPING WILL BE ALLOWED WITHIN SPACES PROTECTED BY
REQUIRED TO MAINTAIN WATER SUPPLY TO FIRE SPRINKLERS IN ADJACENT AREAS.
SUPPORTS AND BRACES FROM ENTIRE AREA. ROUTE PIPING AROUND AREA AS
FROM SPACE. REMOVE FIRE SPRINKLERS, ESCUTCHEONS, PIPING, FITTINGS
AGENT FIRE SUPPRESSION SYSTEM. REMOVE ALL FIRE SPRINKLER PROTECTION
AREA TO BE PROTECTED BY VESDA SMOKE DETECTION SYSTEM AND CLEAN
9
10
AND REMOUNT FIRE EXTINGUISHER IN NEW, SMALLER CABINET.
REMOVE CABINET VALVE AND SUPPLY PIPING. PATCH REMAINING HOLE IN WALL
THIS BUILDING PROTECTED THROUGHOUT BY AUTOMATIC FIRE SPRINKLERS.
REMOVED. OCCUPANT USE HOSE CABINETS ARE NOT REQUIRED BY CODE FOR
EXISTING OCCUPANT USE (1-1/2") FIRE HOSE VALVE WITH HOSE ALREADY
4
4
4
4
4
4
4
9
4
4
4
4
4
4
4
44
4
4
99
99
6
H
O
S
E
H
O
S
E
HOSE
KEY PLAN
A
B
SCALE: 1/8" = 1’-0"
LEVEL 02 AREA A FIRE PROTECTION DEMOLITION PLAN1
0510 10 20
FD102a FD102a
Demolition
Plan
A Fire Protection
Level 02 Area
STAIRWELL
MEN’S WOMEN’S
BDF
STACKS/COMPUTER/STUDY
AREA
MECH
GROUP STUDY GROUP STUDY
ARCHIVES
OFFICE - NOT
USED
EXHIBIT/MICROFILM/RESEARCH
&
READING/RECEPTION
Redundant Room
WORK ROOMVAULT
STORAGE &
ARCHIVES OFFICE
ELECTRONIC
RESOURCES
LIBRARIAN -
ARCHIVES AND
SPECIAL
COLLECTIONS
LIB - ADAM
D
C
AM
W
O
R
K
S
P
AC
E
/
S
U
P
E
R
VIS
O
R
DCAM-DIGITALIZATION
& SPECIAL
COLLECTIONS
WORK SPACE
TECHNICAL
SERVICES
DIGITAL
INITIATIVES
LIBRARIAN -STAIRWELL
ELEVATOR
Redundant Room
HALLWAY/EXHIBIT
CONFERENCE
RM
MAIL
CUST.
KITCHEN /
BREAK ROOM
PRESS ROOM
GROUP STUDY
Redundant Room
HALLWAY/EXHIBIT
STAIRWELL
21.0780
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
10/27/2022
Bid Set
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # :12242
10/27/2022
1
2
3
FIRE PROTECTION DEMO KEY NOTES
RE: SHEETS FD100a - FD103a
TEST BY: GREG JONES - PCI
TEST LOCATION: SIDEWALK AREA NORTHWEST OF BUILDING
TEST DATE: 8/10/22
FLOW: 1,321 GPM
RESIDUAL PRESSURE: 72 PSI
STATIC PRESSURE: 81 PSI
SYSTEM SUPPLIES THE FOLLOWING PRESSURES/FLOW FOR FIRE PROTECTION:
EXISTING 6" FIRE PROTECTION WATER SUPPLY TO BUILDING TO REMAIN. WATER
CONNECT TO RISER DOWNSTREAM OF ALARM VALVE.
SUPPLY FROM EXTERIOR, FREE STANDING FIRE DEPARTMENT CONNECTION
VALVE ASSEMBLY (RETROFIT), 4" OS&Y VALVE AND ALARM VALVE WITH TRIM. 4"
EXISTING FIRE SPRINKLER RISER TO REMAIN. RISER INCLUDES 4" DOUBLE CHECK
TO ARCHITECTURAL PLANS TO DETERMINE SCOPE AND EXTENT OF REMODEL.
REUSED WHERE COMPLETELY FUNCTIONAL AND COMPLIANT WITH NFPA 13. REFER
OF REMODEL AREA. EXISTING PIPING SUPPORTS AND BRACES MAY REMAIN TO BE
PIPING, COUPLINGS, FITTINGS AND FIRE SPRINKLERS. REMOVE PIPING BACK TO EDGE
SHOULD BE REPLACED WITH NEW PIPING/SPRINKLERS REMOVE ALL EXISTING
INSTALLED IN 1979, ARE NEAR THE END OF THEIR ANTICIPATED SERVICE LIFE AND
TO UNDERGO REMODEL WITH NEW. PIPING/SPRINKLERS IN BASEMENT WERE
REPLACE EXISTING FIRE SPRINKLERS, AND PIPING THROUGHOUT BASEMENT AREAS
4
5
SPRINKLERS (SEE SHEETS FP101A THROUGH FP103A).
BRANCH LINE OUTLETS MAY REMAIN TO BE RE-USED TO SUPPLY NEW FIRE
REMOVE PIPING BACK TO CONNECTION TO EXISTING BRANCH LINE. EXISTING
ESCUTCHEONS AND 1" ARM-OVERS/DROPS TO FACILITATE REMODEL OF AREA.
PROPOSED BUILDING REMODEL. REMOVE ALL PENDENT FIRE SPRINKLERS,
PORTIONS OF THE BUILDING TO REMAIN AND TO BE MODIFIED TO ACCOMMODATE
SIGNIFICANT SERVICE LIFE REMAINING. EXISTING FIRE SPRINKLER SYSTEM IN THESE
FIRE SPRINKLERS AND PIPING ON LEVELS 1-3 WERE INSTALLED IN 1999 AND HAVE
AREAS TO MAINTAIN WATER SUPPLY.
RECONNECT PIPING TO NEW FIRE SPRINKLER PIPING THROUGHOUT REMODEL
EXISTING FIRE SPRINKLERS AND PIPING OUTSIDE OF REMODEL AREA TO REMAIN.
EXISTING 4" VERTICAL FEED MAIN INSTALLED IN MECHANICAL SHAFT TO REMAIN.
6
EACH FLOOR LEVEL TO REMAIN.
EXISTING FIRE SPRINKLER CONTROL VALVE TO ISOLATE FIRE SPRINKLERS ON
7
B (1ST AND 2ND LEVELS) TO REMAIN.
EXISTING 3" HORIZONTAL FEED MAIN TO SUPPLY FIRE SPRINKLER ZONES IN AREA
8
CLEAN AGENT FIRE SUPPRESSION SYSTEMS.
NO WATER FILLED PIPING WILL BE ALLOWED WITHIN SPACES PROTECTED BY
REQUIRED TO MAINTAIN WATER SUPPLY TO FIRE SPRINKLERS IN ADJACENT AREAS.
SUPPORTS AND BRACES FROM ENTIRE AREA. ROUTE PIPING AROUND AREA AS
FROM SPACE. REMOVE FIRE SPRINKLERS, ESCUTCHEONS, PIPING, FITTINGS
AGENT FIRE SUPPRESSION SYSTEM. REMOVE ALL FIRE SPRINKLER PROTECTION
AREA TO BE PROTECTED BY VESDA SMOKE DETECTION SYSTEM AND CLEAN
9
10
AND REMOUNT FIRE EXTINGUISHER IN NEW, SMALLER CABINET.
REMOVE CABINET VALVE AND SUPPLY PIPING. PATCH REMAINING HOLE IN WALL
THIS BUILDING PROTECTED THROUGHOUT BY AUTOMATIC FIRE SPRINKLERS.
REMOVED. OCCUPANT USE HOSE CABINETS ARE NOT REQUIRED BY CODE FOR
EXISTING OCCUPANT USE (1-1/2") FIRE HOSE VALVE WITH HOSE ALREADY
3
3
3
3
3
3
3
3 33
3
3
33
3
3
3
3
8
8
8
8
8
8
9
9
9
9
9
99
10
10
10
5
6
7
7
7
7
7
KEY PLAN
A
B
SCALE: 1/8" = 1’-0"
LEVEL 02 AREA B FIRE PROTECTION DEMOLITION PLAN1
0510 10 20
FD102b
FD102b
Demolition
Plan
B Fire Protection
Level 02 Area
STAIRS
CUST.
TUTORING
STUDY ROOM
TUTORING
STUDY ROOM
TUTORING
STUDY ROOM
TUTORING
STUDY ROOM
TUTORING
STUDY ROOM
TUTORING
STUDY ROOM OFFICE
DANA
JOHNOSON’S
OFFICE
ELEVATOR
M
IC
H
AE
L
G
U
N
T
R
Y
O
F
F
IC
E
TR
U
L
Y
AN
N
’S
O
F
F
IC
E STAIRS
BDF
WRITING
CENTER
JP’S OFFICE OFFICE
PREP/STORAGE DEPT
CLASSROOM
HALLWAY
OPEN TUTORING
ZONE
DEPT
CLASSROOM
WOMEN’S
MEN’S
VESTIBULE
BREAKROOM/STORAGE
PAULETT’S
OFFICE
OFFICE
OFFICE
HALLWAY
TUTORING ZONE
DEPT
CLASSROOM
STAIRS
STUDY ROOM
STUDY ROOM
OFFICE
OFFICEELECTRICAL
DROP-IN-LAB
PREP/STORAGE
RM
OFFICEOFFICE
DANIEL’S
OFFICEOFFICEDON’S OFFICE
OPEN TUTORING
ZONE OFICE
RECEPTION
ZONE - ESTHER
16
15
15
14
14
13
13
12
12
11
11
10
10
9
9
8
8
7
7
K
H
F
D
B
A
L
21.0780
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
10/27/2022
Bid Set
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # :12242
10/27/2022
1
2
3
FIRE PROTECTION DEMO KEY NOTES
RE: SHEETS FD100a - FD103a
TEST BY: GREG JONES - PCI
TEST LOCATION: SIDEWALK AREA NORTHWEST OF BUILDING
TEST DATE: 8/10/22
FLOW: 1,321 GPM
RESIDUAL PRESSURE: 72 PSI
STATIC PRESSURE: 81 PSI
SYSTEM SUPPLIES THE FOLLOWING PRESSURES/FLOW FOR FIRE PROTECTION:
EXISTING 6" FIRE PROTECTION WATER SUPPLY TO BUILDING TO REMAIN. WATER
CONNECT TO RISER DOWNSTREAM OF ALARM VALVE.
SUPPLY FROM EXTERIOR, FREE STANDING FIRE DEPARTMENT CONNECTION
VALVE ASSEMBLY (RETROFIT), 4" OS&Y VALVE AND ALARM VALVE WITH TRIM. 4"
EXISTING FIRE SPRINKLER RISER TO REMAIN. RISER INCLUDES 4" DOUBLE CHECK
TO ARCHITECTURAL PLANS TO DETERMINE SCOPE AND EXTENT OF REMODEL.
REUSED WHERE COMPLETELY FUNCTIONAL AND COMPLIANT WITH NFPA 13. REFER
OF REMODEL AREA. EXISTING PIPING SUPPORTS AND BRACES MAY REMAIN TO BE
PIPING, COUPLINGS, FITTINGS AND FIRE SPRINKLERS. REMOVE PIPING BACK TO EDGE
SHOULD BE REPLACED WITH NEW PIPING/SPRINKLERS REMOVE ALL EXISTING
INSTALLED IN 1979, ARE NEAR THE END OF THEIR ANTICIPATED SERVICE LIFE AND
TO UNDERGO REMODEL WITH NEW. PIPING/SPRINKLERS IN BASEMENT WERE
REPLACE EXISTING FIRE SPRINKLERS, AND PIPING THROUGHOUT BASEMENT AREAS
4
5
SPRINKLERS (SEE SHEETS FP101A THROUGH FP103A).
BRANCH LINE OUTLETS MAY REMAIN TO BE RE-USED TO SUPPLY NEW FIRE
REMOVE PIPING BACK TO CONNECTION TO EXISTING BRANCH LINE. EXISTING
ESCUTCHEONS AND 1" ARM-OVERS/DROPS TO FACILITATE REMODEL OF AREA.
PROPOSED BUILDING REMODEL. REMOVE ALL PENDENT FIRE SPRINKLERS,
PORTIONS OF THE BUILDING TO REMAIN AND TO BE MODIFIED TO ACCOMMODATE
SIGNIFICANT SERVICE LIFE REMAINING. EXISTING FIRE SPRINKLER SYSTEM IN THESE
FIRE SPRINKLERS AND PIPING ON LEVELS 1-3 WERE INSTALLED IN 1999 AND HAVE
AREAS TO MAINTAIN WATER SUPPLY.
RECONNECT PIPING TO NEW FIRE SPRINKLER PIPING THROUGHOUT REMODEL
EXISTING FIRE SPRINKLERS AND PIPING OUTSIDE OF REMODEL AREA TO REMAIN.
EXISTING 4" VERTICAL FEED MAIN INSTALLED IN MECHANICAL SHAFT TO REMAIN.
6
EACH FLOOR LEVEL TO REMAIN.
EXISTING FIRE SPRINKLER CONTROL VALVE TO ISOLATE FIRE SPRINKLERS ON
7
B (1ST AND 2ND LEVELS) TO REMAIN.
EXISTING 3" HORIZONTAL FEED MAIN TO SUPPLY FIRE SPRINKLER ZONES IN AREA
8
CLEAN AGENT FIRE SUPPRESSION SYSTEMS.
NO WATER FILLED PIPING WILL BE ALLOWED WITHIN SPACES PROTECTED BY
REQUIRED TO MAINTAIN WATER SUPPLY TO FIRE SPRINKLERS IN ADJACENT AREAS.
SUPPORTS AND BRACES FROM ENTIRE AREA. ROUTE PIPING AROUND AREA AS
FROM SPACE. REMOVE FIRE SPRINKLERS, ESCUTCHEONS, PIPING, FITTINGS
AGENT FIRE SUPPRESSION SYSTEM. REMOVE ALL FIRE SPRINKLER PROTECTION
AREA TO BE PROTECTED BY VESDA SMOKE DETECTION SYSTEM AND CLEAN
9
10
AND REMOUNT FIRE EXTINGUISHER IN NEW, SMALLER CABINET.
REMOVE CABINET VALVE AND SUPPLY PIPING. PATCH REMAINING HOLE IN WALL
THIS BUILDING PROTECTED THROUGHOUT BY AUTOMATIC FIRE SPRINKLERS.
REMOVED. OCCUPANT USE HOSE CABINETS ARE NOT REQUIRED BY CODE FOR
EXISTING OCCUPANT USE (1-1/2") FIRE HOSE VALVE WITH HOSE ALREADY
4
4
4
4
4
4
4
4
4
4
4
44
4
4
4
4
4
4
9
9
6
7
H
O
S
E
H
O
S
E
HOSE
KEY PLAN
A
B
SCALE: 1/8" = 1’-0"
LEVEL 03 AREA A FIRE PROTECTION DEMOLITION PLAN1
0510 10 20
FD103a FD103a
Demolition
Plan
A Fire Protection
Level 03 Area
STAIRWELL
TLC LIBRARIAN -
STAIRWELL
MECHANICAL
CHASEGROUP STUDYGROUP STUDY
JUVENILE
COLLECTION
663 SF
EUT FTE
117 SF
PARTS
STORAGE
117 SF
FTE OFFICE
EUT STUDENTS
SERVICE DESK
OPS/ TIER 2
STUDENT
SUPPORT
CONFERENCE
ROOM
OFFICE
HALLWAY
SERVICE DESK
QA TEAM
OFFICE - TIM
SHEET MUSIC
DISABILITY
SERV.
HALLWAY
EUT PRINT
GEN. STOR.
GENERAL
STORAGE
PRINT/BREAK
EUT PRINT
OFFICE
CONFERENCE
ROOM
Redundant Room
CALL CENTER
OFFICE
OFFICE
OFFICE
HALLWAY
HALLWAY
OFFICE
OFFICE
PHOTO
SERVICES
DIGITAL
IMAGING
OFFICE PHOTO
SERVICES STOR
MECHANICAL
CHASE
STAIRWELL
PHOTO STUDIO
PHOTO SERV
STOR
ELEVATOR ELEV./MECH.
CHASE
MED OFFICE
SMALL
MEETING/STOR
HALLWAY
WORKSTATIONS/FLEX
SPACE
OFFICE
TRAINING RROM
WOMEN’S ROOM
MEN’S ROOM
HALLWAY
PIPE CHASE
CUST.VEST.
MEDIA EDITING
MED OFFICE
SOUND BOOTHSOUND BOOTH
1
G
J
L
M
N
P
Q
E
C
2 3 4 5 61.5
21.0780
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
10/27/2022
Bid Set
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # :12242
10/27/2022
1
2
3
FIRE PROTECTION DEMO KEY NOTES
RE: SHEETS FD100a - FD103a
TEST BY: GREG JONES - PCI
TEST LOCATION: SIDEWALK AREA NORTHWEST OF BUILDING
TEST DATE: 8/10/22
FLOW: 1,321 GPM
RESIDUAL PRESSURE: 72 PSI
STATIC PRESSURE: 81 PSI
SYSTEM SUPPLIES THE FOLLOWING PRESSURES/FLOW FOR FIRE PROTECTION:
EXISTING 6" FIRE PROTECTION WATER SUPPLY TO BUILDING TO REMAIN. WATER
CONNECT TO RISER DOWNSTREAM OF ALARM VALVE.
SUPPLY FROM EXTERIOR, FREE STANDING FIRE DEPARTMENT CONNECTION
VALVE ASSEMBLY (RETROFIT), 4" OS&Y VALVE AND ALARM VALVE WITH TRIM. 4"
EXISTING FIRE SPRINKLER RISER TO REMAIN. RISER INCLUDES 4" DOUBLE CHECK
TO ARCHITECTURAL PLANS TO DETERMINE SCOPE AND EXTENT OF REMODEL.
REUSED WHERE COMPLETELY FUNCTIONAL AND COMPLIANT WITH NFPA 13. REFER
OF REMODEL AREA. EXISTING PIPING SUPPORTS AND BRACES MAY REMAIN TO BE
PIPING, COUPLINGS, FITTINGS AND FIRE SPRINKLERS. REMOVE PIPING BACK TO EDGE
SHOULD BE REPLACED WITH NEW PIPING/SPRINKLERS REMOVE ALL EXISTING
INSTALLED IN 1979, ARE NEAR THE END OF THEIR ANTICIPATED SERVICE LIFE AND
TO UNDERGO REMODEL WITH NEW. PIPING/SPRINKLERS IN BASEMENT WERE
REPLACE EXISTING FIRE SPRINKLERS, AND PIPING THROUGHOUT BASEMENT AREAS
4
5
SPRINKLERS (SEE SHEETS FP101A THROUGH FP103A).
BRANCH LINE OUTLETS MAY REMAIN TO BE RE-USED TO SUPPLY NEW FIRE
REMOVE PIPING BACK TO CONNECTION TO EXISTING BRANCH LINE. EXISTING
ESCUTCHEONS AND 1" ARM-OVERS/DROPS TO FACILITATE REMODEL OF AREA.
PROPOSED BUILDING REMODEL. REMOVE ALL PENDENT FIRE SPRINKLERS,
PORTIONS OF THE BUILDING TO REMAIN AND TO BE MODIFIED TO ACCOMMODATE
SIGNIFICANT SERVICE LIFE REMAINING. EXISTING FIRE SPRINKLER SYSTEM IN THESE
FIRE SPRINKLERS AND PIPING ON LEVELS 1-3 WERE INSTALLED IN 1999 AND HAVE
AREAS TO MAINTAIN WATER SUPPLY.
RECONNECT PIPING TO NEW FIRE SPRINKLER PIPING THROUGHOUT REMODEL
EXISTING FIRE SPRINKLERS AND PIPING OUTSIDE OF REMODEL AREA TO REMAIN.
EXISTING 4" VERTICAL FEED MAIN INSTALLED IN MECHANICAL SHAFT TO REMAIN.
6
EACH FLOOR LEVEL TO REMAIN.
EXISTING FIRE SPRINKLER CONTROL VALVE TO ISOLATE FIRE SPRINKLERS ON
7
B (1ST AND 2ND LEVELS) TO REMAIN.
EXISTING 3" HORIZONTAL FEED MAIN TO SUPPLY FIRE SPRINKLER ZONES IN AREA
8
CLEAN AGENT FIRE SUPPRESSION SYSTEMS.
NO WATER FILLED PIPING WILL BE ALLOWED WITHIN SPACES PROTECTED BY
REQUIRED TO MAINTAIN WATER SUPPLY TO FIRE SPRINKLERS IN ADJACENT AREAS.
SUPPORTS AND BRACES FROM ENTIRE AREA. ROUTE PIPING AROUND AREA AS
FROM SPACE. REMOVE FIRE SPRINKLERS, ESCUTCHEONS, PIPING, FITTINGS
AGENT FIRE SUPPRESSION SYSTEM. REMOVE ALL FIRE SPRINKLER PROTECTION
AREA TO BE PROTECTED BY VESDA SMOKE DETECTION SYSTEM AND CLEAN
9
10
AND REMOUNT FIRE EXTINGUISHER IN NEW, SMALLER CABINET.
REMOVE CABINET VALVE AND SUPPLY PIPING. PATCH REMAINING HOLE IN WALL
THIS BUILDING PROTECTED THROUGHOUT BY AUTOMATIC FIRE SPRINKLERS.
REMOVED. OCCUPANT USE HOSE CABINETS ARE NOT REQUIRED BY CODE FOR
EXISTING OCCUPANT USE (1-1/2") FIRE HOSE VALVE WITH HOSE ALREADY
4
4 4
4
4
4
44
4
4
4 4
44
4
4
4
4
4
4
9
9
9
9
9
99
10
10
10
5
6
KEY PLAN
A
B
SCALE: 1/8" = 1’-0"
1
0510 10 20
FP100a
FP100a
Level 00 Area
Plan
LEVEL 00 AREA A FIRE PROTECTION PLAN
Protection
A Fire
TIER 2
TIM
DAN MARK
BREAK ROOM
Scott
STORAGE
RON
FTE
PAUL
DAN STUDENTS
PRINT
SHORT TERM
STORAGE
QA
MARY JO
OPS
ELEV EQUIP
CUSTODIAL
STORAGE
BDF
MEN’S
RESTROOM
WOMEN’S
RESTROOM
ELECTRICAL
CUSTODIALELEV EQUIPELEV
STAIRWELLMECH CHASE
HALLWAY
MECH ROOM
IMAGING AND
STORAGE
TIER 2
TIM
DAN MARK
BREAK ROOM
Scott
STORAGE
RON
FTE
PAUL
DAN STUDENTS
PRINT
SHORT TERM
STORAGE
QA
MARY JO
OPS
ELEV EQUIP
CUSTODIAL
STORAGE
BDF
MEN’S
RESTROOM
WOMEN’S
RESTROOM
ELECTRICAL
CUSTODIALELEV EQUIPELEV
STAIRWELLMECH CHASE
HALLWAY
MECH ROOM
IMAGING AND
STORAGE
TIER 2
TIM
DAN MARK
BREAK ROOM
Scott
STORAGE
RON
FTE
PAUL
DAN STUDENTS
PRINT
SHORT TERM
STORAGE
QA
MARY JO
OPS
ELEV EQUIP
CUSTODIAL
STORAGE
BDF
MEN’S
RESTROOM
WOMEN’S
RESTROOM
ELECTRICAL
CUSTODIALELEV EQUIPELEV
STAIRWELLMECH CHASE
HALLWAY
MECH ROOM
IMAGING AND
STORAGE
1
G
J
L
M
N
P
Q
E
C
2 3 4 5 6
21.0780
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
10/27/2022
Bid Set
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # :12242
10/27/2022
1
2
3
4
5
FIRE PROTECTION KEY NOTES
RE: SHEETS FP100a - FP103a
ZONE.
INDEPENDENTLY). SIZE AGENT STORAGE TO SUPPLY AGENT TO THE LARGEST
SYSTEM ZONE MAY SHARE AGENT STORAGE CYLINDERS (ZONE DISCHARGE
NFPA 2001 AND FIRE SUPPRESSION SYSTEM MANUFACTURER. FIRE SUPPRESSION
CALCULATED TO PROVIDE THE MINIMUM DESIGN CONCENTRATION REQUIRED BY
SHALL BE DETERMINED BY FACTORY TRAINED SYSTEM DESIGNER AND SHALL BE
WHERE INDICATED ON PLANS. SIZE/CAPACITY AND FILL LEVEL OF CYLINDERS
CLEAN AGENT STORAGE CYLINDERS. INSTALL IN OR NEAR PROTECTED AREA
11
CONTROL PANEL TO BUILDING FIRE ALARM SYSTEM.
REQUIREMENTS. CONNECT FIRE ALARM, SUPERVISORY AND TROUBLE RELAYS OF
APPLICABLE REQUIREMENTS OF NFPA 72, 2001 AND MANUFACTURER’S
SYSTEM SHALL BE DESIGNED, INSTALLED AND TESTED IN ACCORDANCE WITH ALL
RELEASE OF CLEAN AGENT FIRE SUPPRESSION SYSTEM. CONTROL/RELEASING
CONTROL PANEL (UL LISTED AND FM APPROVED FOR RELEASING SERVICE) FOR
12
REQUIREMENTS.
APPLICABLE PROVISIONS OF NFPA 72, NFPA 2001 AND MANUFACTURER’S
INSTALL AND TEST SMOKE DETECTION SYSTEM IN ACCORDANCE WITH ALL
CONNECTED TO DIFFERENT INITIATING DEVICE ZONES (ZONE A OR B). DESIGN,
WHERE PRESENT (NOT SHOWN ON PLANS). ADJACENT DETECTORS SHALL BE
DETECTORS IN EACH ROOM/SPACE INCLUDING AREAS UNDER RAISED FLOORS
EACH DETECTOR SHALL BE 225 SQ FT (15’ X 15’). PROVIDE AT LEAST 2
ACTUATION OF CLEAN AGENT FIRE SUPPRESSION SYSTEMS. MAXIMUM SPACING FOR
INSTALL CROSS ZONED SMOKE DETECTION SYSTEM TO PROVIDE AUTOMATIC
13
SYSTEM" OR "ABORT FIRE SUPPRESSION SYSTEM RELEASE" AS APPROPRIATE.
DESCRIBE SWITCH FUNCTION. SIGN SHALL STATE "RELEASE FIRE SUPPRESSION
FROM PROTECTED SPACE. INSTALL SIGNS ADJACENT TO EACH SWITCH TO
COUNTDOWN WHEN RELEASED. INSTALL SWITCHES ADJACENT TO EACH EXIT DOOR
ABORT SWITCH SHALL RESET DISCHARGE TIME DELAY COUNTER AND RESTART
PROVIDE MANUAL CONTROL OF EACH CLEAN AGENT FIRE SUPPRESSION SYSTEM.
INSTALL MANUAL RELEASE AND "CONSTANT PRESSURE" TYPE ABORT SWITCHES TO
14
SHALL TRANSMIT A SUPERVISORY ALARM TO CONTROL/RELEASING PANEL.
OF EACH FIRE SUPPRESSION SYSTEM WHEN ACTIVATED. ACTIVATION OF SWITCH
CONTROL/RELEASING PANEL. CONFIGURE SWITCH TO DISABLE RELEASING RELAYS
SUPPRESSION SYSTEM. INSTALL SYSTEM LOCKOUT ADJACENT TO
INSTALL KEY OPERATED, MANUAL LOCK OUT SWITCH FOR CLEAN AGENT FIRE
15
SYSTEMS TO BE DETERMINED BY INSTALLING CONTRACTOR.
SYSTEM. REQUIRED NUMBER AND LOCATION OF RELAYS AS WELL AS INTERFACED
OFF, ETC.) REQUIRED FOR PROPER FUNCTION OF CLEAN AGENT FIRE SUPPRESSION
AUXILIARY FUNCTIONS (I.E. DAMPER CLOSURE, FAN SHUTDOWN, EMERGENCY POWER
INSTALL RELAYS FROM CONTROL/RELEASING PANEL TO INITIATE ALL REQUIRED
16
SUPPRESSION SYSTEM PRE -DISCHARGE ALARM".
PROTECTED AREA. INSTALL SIGN ADJACENT TO EACH ALARM STATING "FIRE
SOUND UPON ACTIVATION OF ANY SINGLE SMOKE DETECTION ZONE FOR
PROTECTED SPACE ABOVE EACH EXIT DOOR. CONFIGURE ALARM TO FLASH AND
BUILDING FIRE ALARM) FOR CLEAN AGENT FIRE SUPPRESSION SYSTEM INSIDE
INSTALL PRE -DISCHARGE ALARM (AUDIBLE AND VISIBLE SIGNALS DISTINCT FROM
17
SYSTEM RELEASED WHEN FLASHING".
RELEASE. INSTALL SIGN ADJACENT TO EACH STROBE STATING "FIRE SUPPRESSION
ABOVE EACH EXIT DOOR AND CONFIGURE STROBES TO FLASH UPON AGENT
THE INTERIOR AND EXTERIOR OF PROTECTED SPACE. INSTALL DISCHARGE STROBES
INSTALL DISCHARGE STROBES FOR CLEAN AGENT FIRE SUPPRESSION SYSTEM IN
TEST BY: GREG JONES - PCI
TEST LOCATION: SIDEWALK AREA NORTHWEST OF BUILDING
TEST DATE: 8/10/22
FLOW: 1,321 GPM
RESIDUAL PRESSURE: 72 PSI
STATIC PRESSURE: 81 PSI
SYSTEM SUPPLIES THE FOLLOWING PRESSURES/FLOW FOR FIRE PROTECTION:
EXISTING 6" FIRE PROTECTION WATER SUPPLY TO BUILDING TO REMAIN. WATER
CONNECT TO RISER DOWNSTREAM OF ALARM VALVE.
SUPPLY FROM EXTERIOR, FREE STANDING FIRE DEPARTMENT CONNECTION
VALVE ASSEMBLY (RETROFIT), 4" OS&Y VALVE AND ALARM VALVE WITH TRIM. 4"
EXISTING FIRE SPRINKLER RISER TO REMAIN. RISER INCLUDES 4" DOUBLE CHECK
EXISTING 4" VERTICAL FEED MAIN INSTALLED IN MECHANICAL SHAFT TO REMAIN.
EACH FLOOR LEVEL TO REMAIN.
EXISTING FIRE SPRINKLER CONTROL VALVE TO ISOLATE FIRE SPRINKLERS ON
B (1ST AND 2ND LEVELS) TO REMAIN.
EXISTING 3" HORIZONTAL FEED MAIN TO SUPPLY FIRE SPRINKLER ZONES IN AREA
6
7
TO ARCHITECTURAL PLANS TO DETERMINE SCOPE AND EXTENT OF REMODEL.
REUSED WHERE COMPLETELY FUNCTIONAL AND COMPLIANT WITH NFPA 13. REFER
OF REMODEL AREA. EXISTING PIPING SUPPORTS AND BRACES MAY REMAIN TO BE
PIPING, COUPLINGS, FITTINGS AND FIRE SPRINKLERS. REMOVE PIPING BACK TO EDGE
SHOULD BE REPLACED WITH NEW PIPING/SPRINKLERS REMOVE ALL EXISTING
INSTALLED IN 1979, ARE NEAR THE END OF THEIR ANTICIPATED SERVICE LIFE AND
TO UNDERGO REMODEL WITH NEW. PIPING/SPRINKLERS IN BASEMENT WERE
REPLACE EXISTING FIRE SPRINKLERS, AND PIPING THROUGHOUT BASEMENT AREAS
REMODEL. COORDINATE WITH MECHANICAL AND ELECTRICAL SYSTEMS.
REFER TO ARCHITECTURAL PLANS TO DETERMINE SCOPE AND EXTENT OF
SPRINKLER PROTECTION THROUGHOUT BUILDING IN ACCORDANCE WITH NFPA 13.
AND PIPING AS REQUIRED TO ACCOMMODATE REMODEL AND ENSURE FIRE
PROPOSED BUILDING REMODEL. MODIFY, ADJUST AND/OR ADD FIRE SPRINKLERS
PORTIONS OF THE BUILDING TO REMAIN AND TO BE MODIFIED TO ACCOMMODATE
SIGNIFICANT SERVICE LIFE REMAINING. EXISTING FIRE SPRINKLER SYSTEM IN THESE
FIRE SPRINKLERS AND PIPING ON LEVELS 1-3 WERE INSTALLED IN 1999 AND HAVE
8
AREAS TO MAINTAIN WATER SUPPLY.
RECONNECT PIPING TO NEW FIRE SPRINKLER PIPING THROUGHOUT REMODEL
EXISTING FIRE SPRINKLERS AND PIPING OUTSIDE OF REMODEL AREA TO REMAIN.
9
ZONE 3 - RECEPTION/EXHIBIT 55
ZONE 2 - ARCHIVE 57
ZONE 1 - VAULT 56
PANEL AND EXTINGUISHING AGENT (EACH ZONE DISCHARGES INDEPENDENTLY):
SYSTEMS/ZONES AS INDICATED BELOW. ZONES MAY SHARE COMMON CONTROL
PRESENT. PROVIDE 3 SEPARATE AND COMPLETELY DISTINCT FIRE SUPPRESSION
SUSPENDED CEILING AND FLOOR INCLUDING VOLUME BELOW RAISED FLOOR WHERE
SYSTEM SHALL BE TOTAL FLOODING TYPE PROTECTING ENTIRE VOLUME BETWEEN
MANUFACTURER’S REQUIREMENTS AND PROJECT SPECIFICATIONS. CLEAN AGENT
ACCORDANCE WITH ALL APPLICABLE PROVISIONS OF NFPA 72, NFPA 2001,
SYSTEM. DESIGN, INSTALL AND TEST CLEAN AGENT FIRE SUPPRESSION SYSTEM IN
HATCHED AREA TO BE PROTECTED BY CLEAN AGENT (FM-200) FIRE SUPPRESSION
10
18
FIRE SUPPRESSION SYSTEM.
DETECTION/WARNING ONLY AND SHALL NOT BE USED TO RELEASE CLEAN AGENT
BUILDING FIRE ALARM SYSTEM. VESDA SYSTEM IS FOR EARLY SMOKE
NORMALLY OCCUPIED AREA. PROGRAM HIGH THRESHOLD ALARM TO ACTIVATE
PROGRAM LOW THRESHOLD ALARM (EARLY) TO SOUND SUPERVISORY ALARM IN
THROUGHOUT ARE PROTECTED BY CLEAN AGENT FIRE SUPPRESSION SYSTEM.
INSTALL AIR SAMPLING TYPE, EARLY WARNING SMOKE DETECTION SYSTEM (VESDA)
19
AREAS FOR WATER SUPPLY.
HAZARD GROUP 1. CONNECT TO EXISTING FIRE SPRINKLER PIPING IN ADJACENT
DESIGN FIRE SPRINKLERS TO PROTECT A HAZARD CLASSIFICATION OF ORDINARY
EXTEND FIRE SPRINKLER PROTECT INTO EXISTING BASEMENT ELECTRICAL ROOM.
19
1
2
3
8
8
8
8
6
6
6
6
88
8
KEY PLAN
A
B
SCALE: 1/8" = 1’-0"
1
0510 10 20
FP101a FP101a
Plan
Level 01 Area
LEVEL 01 AREA A FIRE PROTECTION PLAN
Protection
A Fire
CHRIS FOX
OFFICE
CHECK-IN
MATT’S OFFICE
SHANES OFFICE STUDY (MED)
CHRIS OLSEN
OFFICE
CASSIDY’S
OFFICE
NATES OFFICE
CONFERENCE
ROOM
BREAKROOMSTUDY (SM)
STUDY (MED)
STUDY (MED)
STUDY (SM)
STUDY (SM)
OPEN STUDY
COLLECTION
VESTIBULE
CIRCULATION
CIRC
SUPERVISOR
INTER LIBRARY
LOAN
WORKSPACE
FAMILY RR
OPEN STUDY
OPEN STUDY
CD’s / DVD’s
OPEN STUDY
POPULAR
COLLECTIONS
MENS WOMENS
JANITORS
OFFICE
LOCKERS
SAM’s OFFICE
DAVID’S OFFICE
INTER LIBRARY
LOAN OFFICE
STAIR
STAIR
VESTIBULE
OPEN STUDY
21.0780
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
10/27/2022
Bid Set
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # :12242
10/27/2022
1
2
3
4
5
FIRE PROTECTION KEY NOTES
RE: SHEETS FP100a - FP103a
ZONE.
INDEPENDENTLY). SIZE AGENT STORAGE TO SUPPLY AGENT TO THE LARGEST
SYSTEM ZONE MAY SHARE AGENT STORAGE CYLINDERS (ZONE DISCHARGE
NFPA 2001 AND FIRE SUPPRESSION SYSTEM MANUFACTURER. FIRE SUPPRESSION
CALCULATED TO PROVIDE THE MINIMUM DESIGN CONCENTRATION REQUIRED BY
SHALL BE DETERMINED BY FACTORY TRAINED SYSTEM DESIGNER AND SHALL BE
WHERE INDICATED ON PLANS. SIZE/CAPACITY AND FILL LEVEL OF CYLINDERS
CLEAN AGENT STORAGE CYLINDERS. INSTALL IN OR NEAR PROTECTED AREA
11
CONTROL PANEL TO BUILDING FIRE ALARM SYSTEM.
REQUIREMENTS. CONNECT FIRE ALARM, SUPERVISORY AND TROUBLE RELAYS OF
APPLICABLE REQUIREMENTS OF NFPA 72, 2001 AND MANUFACTURER’S
SYSTEM SHALL BE DESIGNED, INSTALLED AND TESTED IN ACCORDANCE WITH ALL
RELEASE OF CLEAN AGENT FIRE SUPPRESSION SYSTEM. CONTROL/RELEASING
CONTROL PANEL (UL LISTED AND FM APPROVED FOR RELEASING SERVICE) FOR
12
REQUIREMENTS.
APPLICABLE PROVISIONS OF NFPA 72, NFPA 2001 AND MANUFACTURER’S
INSTALL AND TEST SMOKE DETECTION SYSTEM IN ACCORDANCE WITH ALL
CONNECTED TO DIFFERENT INITIATING DEVICE ZONES (ZONE A OR B). DESIGN,
WHERE PRESENT (NOT SHOWN ON PLANS). ADJACENT DETECTORS SHALL BE
DETECTORS IN EACH ROOM/SPACE INCLUDING AREAS UNDER RAISED FLOORS
EACH DETECTOR SHALL BE 225 SQ FT (15’ X 15’). PROVIDE AT LEAST 2
ACTUATION OF CLEAN AGENT FIRE SUPPRESSION SYSTEMS. MAXIMUM SPACING FOR
INSTALL CROSS ZONED SMOKE DETECTION SYSTEM TO PROVIDE AUTOMATIC
13
SYSTEM" OR "ABORT FIRE SUPPRESSION SYSTEM RELEASE" AS APPROPRIATE.
DESCRIBE SWITCH FUNCTION. SIGN SHALL STATE "RELEASE FIRE SUPPRESSION
FROM PROTECTED SPACE. INSTALL SIGNS ADJACENT TO EACH SWITCH TO
COUNTDOWN WHEN RELEASED. INSTALL SWITCHES ADJACENT TO EACH EXIT DOOR
ABORT SWITCH SHALL RESET DISCHARGE TIME DELAY COUNTER AND RESTART
PROVIDE MANUAL CONTROL OF EACH CLEAN AGENT FIRE SUPPRESSION SYSTEM.
INSTALL MANUAL RELEASE AND "CONSTANT PRESSURE" TYPE ABORT SWITCHES TO
14
SHALL TRANSMIT A SUPERVISORY ALARM TO CONTROL/RELEASING PANEL.
OF EACH FIRE SUPPRESSION SYSTEM WHEN ACTIVATED. ACTIVATION OF SWITCH
CONTROL/RELEASING PANEL. CONFIGURE SWITCH TO DISABLE RELEASING RELAYS
SUPPRESSION SYSTEM. INSTALL SYSTEM LOCKOUT ADJACENT TO
INSTALL KEY OPERATED, MANUAL LOCK OUT SWITCH FOR CLEAN AGENT FIRE
15
SYSTEMS TO BE DETERMINED BY INSTALLING CONTRACTOR.
SYSTEM. REQUIRED NUMBER AND LOCATION OF RELAYS AS WELL AS INTERFACED
OFF, ETC.) REQUIRED FOR PROPER FUNCTION OF CLEAN AGENT FIRE SUPPRESSION
AUXILIARY FUNCTIONS (I.E. DAMPER CLOSURE, FAN SHUTDOWN, EMERGENCY POWER
INSTALL RELAYS FROM CONTROL/RELEASING PANEL TO INITIATE ALL REQUIRED
16
SUPPRESSION SYSTEM PRE -DISCHARGE ALARM".
PROTECTED AREA. INSTALL SIGN ADJACENT TO EACH ALARM STATING "FIRE
SOUND UPON ACTIVATION OF ANY SINGLE SMOKE DETECTION ZONE FOR
PROTECTED SPACE ABOVE EACH EXIT DOOR. CONFIGURE ALARM TO FLASH AND
BUILDING FIRE ALARM) FOR CLEAN AGENT FIRE SUPPRESSION SYSTEM INSIDE
INSTALL PRE -DISCHARGE ALARM (AUDIBLE AND VISIBLE SIGNALS DISTINCT FROM
17
SYSTEM RELEASED WHEN FLASHING".
RELEASE. INSTALL SIGN ADJACENT TO EACH STROBE STATING "FIRE SUPPRESSION
ABOVE EACH EXIT DOOR AND CONFIGURE STROBES TO FLASH UPON AGENT
THE INTERIOR AND EXTERIOR OF PROTECTED SPACE. INSTALL DISCHARGE STROBES
INSTALL DISCHARGE STROBES FOR CLEAN AGENT FIRE SUPPRESSION SYSTEM IN
TEST BY: GREG JONES - PCI
TEST LOCATION: SIDEWALK AREA NORTHWEST OF BUILDING
TEST DATE: 8/10/22
FLOW: 1,321 GPM
RESIDUAL PRESSURE: 72 PSI
STATIC PRESSURE: 81 PSI
SYSTEM SUPPLIES THE FOLLOWING PRESSURES/FLOW FOR FIRE PROTECTION:
EXISTING 6" FIRE PROTECTION WATER SUPPLY TO BUILDING TO REMAIN. WATER
CONNECT TO RISER DOWNSTREAM OF ALARM VALVE.
SUPPLY FROM EXTERIOR, FREE STANDING FIRE DEPARTMENT CONNECTION
VALVE ASSEMBLY (RETROFIT), 4" OS&Y VALVE AND ALARM VALVE WITH TRIM. 4"
EXISTING FIRE SPRINKLER RISER TO REMAIN. RISER INCLUDES 4" DOUBLE CHECK
EXISTING 4" VERTICAL FEED MAIN INSTALLED IN MECHANICAL SHAFT TO REMAIN.
EACH FLOOR LEVEL TO REMAIN.
EXISTING FIRE SPRINKLER CONTROL VALVE TO ISOLATE FIRE SPRINKLERS ON
B (1ST AND 2ND LEVELS) TO REMAIN.
EXISTING 3" HORIZONTAL FEED MAIN TO SUPPLY FIRE SPRINKLER ZONES IN AREA
6
7
TO ARCHITECTURAL PLANS TO DETERMINE SCOPE AND EXTENT OF REMODEL.
REUSED WHERE COMPLETELY FUNCTIONAL AND COMPLIANT WITH NFPA 13. REFER
OF REMODEL AREA. EXISTING PIPING SUPPORTS AND BRACES MAY REMAIN TO BE
PIPING, COUPLINGS, FITTINGS AND FIRE SPRINKLERS. REMOVE PIPING BACK TO EDGE
SHOULD BE REPLACED WITH NEW PIPING/SPRINKLERS REMOVE ALL EXISTING
INSTALLED IN 1979, ARE NEAR THE END OF THEIR ANTICIPATED SERVICE LIFE AND
TO UNDERGO REMODEL WITH NEW. PIPING/SPRINKLERS IN BASEMENT WERE
REPLACE EXISTING FIRE SPRINKLERS, AND PIPING THROUGHOUT BASEMENT AREAS
REMODEL. COORDINATE WITH MECHANICAL AND ELECTRICAL SYSTEMS.
REFER TO ARCHITECTURAL PLANS TO DETERMINE SCOPE AND EXTENT OF
SPRINKLER PROTECTION THROUGHOUT BUILDING IN ACCORDANCE WITH NFPA 13.
AND PIPING AS REQUIRED TO ACCOMMODATE REMODEL AND ENSURE FIRE
PROPOSED BUILDING REMODEL. MODIFY, ADJUST AND/OR ADD FIRE SPRINKLERS
PORTIONS OF THE BUILDING TO REMAIN AND TO BE MODIFIED TO ACCOMMODATE
SIGNIFICANT SERVICE LIFE REMAINING. EXISTING FIRE SPRINKLER SYSTEM IN THESE
FIRE SPRINKLERS AND PIPING ON LEVELS 1-3 WERE INSTALLED IN 1999 AND HAVE
8
AREAS TO MAINTAIN WATER SUPPLY.
RECONNECT PIPING TO NEW FIRE SPRINKLER PIPING THROUGHOUT REMODEL
EXISTING FIRE SPRINKLERS AND PIPING OUTSIDE OF REMODEL AREA TO REMAIN.
9
ZONE 3 - RECEPTION/EXHIBIT 55
ZONE 2 - ARCHIVE 57
ZONE 1 - VAULT 56
PANEL AND EXTINGUISHING AGENT (EACH ZONE DISCHARGES INDEPENDENTLY):
SYSTEMS/ZONES AS INDICATED BELOW. ZONES MAY SHARE COMMON CONTROL
PRESENT. PROVIDE 3 SEPARATE AND COMPLETELY DISTINCT FIRE SUPPRESSION
SUSPENDED CEILING AND FLOOR INCLUDING VOLUME BELOW RAISED FLOOR WHERE
SYSTEM SHALL BE TOTAL FLOODING TYPE PROTECTING ENTIRE VOLUME BETWEEN
MANUFACTURER’S REQUIREMENTS AND PROJECT SPECIFICATIONS. CLEAN AGENT
ACCORDANCE WITH ALL APPLICABLE PROVISIONS OF NFPA 72, NFPA 2001,
SYSTEM. DESIGN, INSTALL AND TEST CLEAN AGENT FIRE SUPPRESSION SYSTEM IN
HATCHED AREA TO BE PROTECTED BY CLEAN AGENT (FM-200) FIRE SUPPRESSION
10
18
FIRE SUPPRESSION SYSTEM.
DETECTION/WARNING ONLY AND SHALL NOT BE USED TO RELEASE CLEAN AGENT
BUILDING FIRE ALARM SYSTEM. VESDA SYSTEM IS FOR EARLY SMOKE
NORMALLY OCCUPIED AREA. PROGRAM HIGH THRESHOLD ALARM TO ACTIVATE
PROGRAM LOW THRESHOLD ALARM (EARLY) TO SOUND SUPERVISORY ALARM IN
THROUGHOUT ARE PROTECTED BY CLEAN AGENT FIRE SUPPRESSION SYSTEM.
INSTALL AIR SAMPLING TYPE, EARLY WARNING SMOKE DETECTION SYSTEM (VESDA)
19
AREAS FOR WATER SUPPLY.
HAZARD GROUP 1. CONNECT TO EXISTING FIRE SPRINKLER PIPING IN ADJACENT
DESIGN FIRE SPRINKLERS TO PROTECT A HAZARD CLASSIFICATION OF ORDINARY
EXTEND FIRE SPRINKLER PROTECT INTO EXISTING BASEMENT ELECTRICAL ROOM.
7 7
7
7 7
7 7 7
7 7
7 7 7
7
7 7
7
8
8
8
8
3
4
KEY PLAN
A
B
SCALE: 1/8" = 1’-0"
1
0510 10 20
FP101b
FP101b
Plan
Level 01 Area
LEVEL 01 AREA B FIRE PROTECTION PLAN
Protection
B Fire
STORAGESTUDYSTUDY
CLASSROOMCLASSROOM
ADJUNCT
OFFICE
OFFICEOFFICEOFFICEOFFICEOFFICEOFFICE
CONFERENCE
ROOM
CONFERENCE
COLLABORATIVE
SPACE
CLASSROOM CLASSROOM
DANA’S OFFICEDON’S OFFICE
TRAINING AREA
OFFICE
SMALL MEETING
OFFICE JOSH’S OFFICE
TUTORING
ADMIN OPEN
AREA
OFFICEPRACTICE
WORKSPACE
STORAGE
DROP IN MATH
LAB
WORKSTATIONS/
FLEX SPACE
CLASSROOM
STUDENT PREP
STUDY STUDY
MATH LAB
RECEPTIONIST
I.T. HELP DESK
KEVIN’S OFFICE
STORAGE
STORAGE
PRACTICE
PRACTICE
PRACTICE
RECEPTION
VESTIBULE
ELEC
VESTIBULE
MECH
ELEV EQUIP
ELEV
MEN’S
RESTROOM
WOMEN’S
RESTROOM
16
16
15
15
14
14
13
13
12
12
11
11
10
10
9
9
8
87
K
H
F
D
B
A
L
21.0780
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
10/27/2022
Bid Set
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # :12242
10/27/2022
1
2
3
4
5
FIRE PROTECTION KEY NOTES
RE: SHEETS FP100a - FP103a
ZONE.
INDEPENDENTLY). SIZE AGENT STORAGE TO SUPPLY AGENT TO THE LARGEST
SYSTEM ZONE MAY SHARE AGENT STORAGE CYLINDERS (ZONE DISCHARGE
NFPA 2001 AND FIRE SUPPRESSION SYSTEM MANUFACTURER. FIRE SUPPRESSION
CALCULATED TO PROVIDE THE MINIMUM DESIGN CONCENTRATION REQUIRED BY
SHALL BE DETERMINED BY FACTORY TRAINED SYSTEM DESIGNER AND SHALL BE
WHERE INDICATED ON PLANS. SIZE/CAPACITY AND FILL LEVEL OF CYLINDERS
CLEAN AGENT STORAGE CYLINDERS. INSTALL IN OR NEAR PROTECTED AREA
11
CONTROL PANEL TO BUILDING FIRE ALARM SYSTEM.
REQUIREMENTS. CONNECT FIRE ALARM, SUPERVISORY AND TROUBLE RELAYS OF
APPLICABLE REQUIREMENTS OF NFPA 72, 2001 AND MANUFACTURER’S
SYSTEM SHALL BE DESIGNED, INSTALLED AND TESTED IN ACCORDANCE WITH ALL
RELEASE OF CLEAN AGENT FIRE SUPPRESSION SYSTEM. CONTROL/RELEASING
CONTROL PANEL (UL LISTED AND FM APPROVED FOR RELEASING SERVICE) FOR
12
REQUIREMENTS.
APPLICABLE PROVISIONS OF NFPA 72, NFPA 2001 AND MANUFACTURER’S
INSTALL AND TEST SMOKE DETECTION SYSTEM IN ACCORDANCE WITH ALL
CONNECTED TO DIFFERENT INITIATING DEVICE ZONES (ZONE A OR B). DESIGN,
WHERE PRESENT (NOT SHOWN ON PLANS). ADJACENT DETECTORS SHALL BE
DETECTORS IN EACH ROOM/SPACE INCLUDING AREAS UNDER RAISED FLOORS
EACH DETECTOR SHALL BE 225 SQ FT (15’ X 15’). PROVIDE AT LEAST 2
ACTUATION OF CLEAN AGENT FIRE SUPPRESSION SYSTEMS. MAXIMUM SPACING FOR
INSTALL CROSS ZONED SMOKE DETECTION SYSTEM TO PROVIDE AUTOMATIC
13
SYSTEM" OR "ABORT FIRE SUPPRESSION SYSTEM RELEASE" AS APPROPRIATE.
DESCRIBE SWITCH FUNCTION. SIGN SHALL STATE "RELEASE FIRE SUPPRESSION
FROM PROTECTED SPACE. INSTALL SIGNS ADJACENT TO EACH SWITCH TO
COUNTDOWN WHEN RELEASED. INSTALL SWITCHES ADJACENT TO EACH EXIT DOOR
ABORT SWITCH SHALL RESET DISCHARGE TIME DELAY COUNTER AND RESTART
PROVIDE MANUAL CONTROL OF EACH CLEAN AGENT FIRE SUPPRESSION SYSTEM.
INSTALL MANUAL RELEASE AND "CONSTANT PRESSURE" TYPE ABORT SWITCHES TO
14
SHALL TRANSMIT A SUPERVISORY ALARM TO CONTROL/RELEASING PANEL.
OF EACH FIRE SUPPRESSION SYSTEM WHEN ACTIVATED. ACTIVATION OF SWITCH
CONTROL/RELEASING PANEL. CONFIGURE SWITCH TO DISABLE RELEASING RELAYS
SUPPRESSION SYSTEM. INSTALL SYSTEM LOCKOUT ADJACENT TO
INSTALL KEY OPERATED, MANUAL LOCK OUT SWITCH FOR CLEAN AGENT FIRE
15
SYSTEMS TO BE DETERMINED BY INSTALLING CONTRACTOR.
SYSTEM. REQUIRED NUMBER AND LOCATION OF RELAYS AS WELL AS INTERFACED
OFF, ETC.) REQUIRED FOR PROPER FUNCTION OF CLEAN AGENT FIRE SUPPRESSION
AUXILIARY FUNCTIONS (I.E. DAMPER CLOSURE, FAN SHUTDOWN, EMERGENCY POWER
INSTALL RELAYS FROM CONTROL/RELEASING PANEL TO INITIATE ALL REQUIRED
16
SUPPRESSION SYSTEM PRE -DISCHARGE ALARM".
PROTECTED AREA. INSTALL SIGN ADJACENT TO EACH ALARM STATING "FIRE
SOUND UPON ACTIVATION OF ANY SINGLE SMOKE DETECTION ZONE FOR
PROTECTED SPACE ABOVE EACH EXIT DOOR. CONFIGURE ALARM TO FLASH AND
BUILDING FIRE ALARM) FOR CLEAN AGENT FIRE SUPPRESSION SYSTEM INSIDE
INSTALL PRE -DISCHARGE ALARM (AUDIBLE AND VISIBLE SIGNALS DISTINCT FROM
17
SYSTEM RELEASED WHEN FLASHING".
RELEASE. INSTALL SIGN ADJACENT TO EACH STROBE STATING "FIRE SUPPRESSION
ABOVE EACH EXIT DOOR AND CONFIGURE STROBES TO FLASH UPON AGENT
THE INTERIOR AND EXTERIOR OF PROTECTED SPACE. INSTALL DISCHARGE STROBES
INSTALL DISCHARGE STROBES FOR CLEAN AGENT FIRE SUPPRESSION SYSTEM IN
TEST BY: GREG JONES - PCI
TEST LOCATION: SIDEWALK AREA NORTHWEST OF BUILDING
TEST DATE: 8/10/22
FLOW: 1,321 GPM
RESIDUAL PRESSURE: 72 PSI
STATIC PRESSURE: 81 PSI
SYSTEM SUPPLIES THE FOLLOWING PRESSURES/FLOW FOR FIRE PROTECTION:
EXISTING 6" FIRE PROTECTION WATER SUPPLY TO BUILDING TO REMAIN. WATER
CONNECT TO RISER DOWNSTREAM OF ALARM VALVE.
SUPPLY FROM EXTERIOR, FREE STANDING FIRE DEPARTMENT CONNECTION
VALVE ASSEMBLY (RETROFIT), 4" OS&Y VALVE AND ALARM VALVE WITH TRIM. 4"
EXISTING FIRE SPRINKLER RISER TO REMAIN. RISER INCLUDES 4" DOUBLE CHECK
EXISTING 4" VERTICAL FEED MAIN INSTALLED IN MECHANICAL SHAFT TO REMAIN.
EACH FLOOR LEVEL TO REMAIN.
EXISTING FIRE SPRINKLER CONTROL VALVE TO ISOLATE FIRE SPRINKLERS ON
B (1ST AND 2ND LEVELS) TO REMAIN.
EXISTING 3" HORIZONTAL FEED MAIN TO SUPPLY FIRE SPRINKLER ZONES IN AREA
6
7
TO ARCHITECTURAL PLANS TO DETERMINE SCOPE AND EXTENT OF REMODEL.
REUSED WHERE COMPLETELY FUNCTIONAL AND COMPLIANT WITH NFPA 13. REFER
OF REMODEL AREA. EXISTING PIPING SUPPORTS AND BRACES MAY REMAIN TO BE
PIPING, COUPLINGS, FITTINGS AND FIRE SPRINKLERS. REMOVE PIPING BACK TO EDGE
SHOULD BE REPLACED WITH NEW PIPING/SPRINKLERS REMOVE ALL EXISTING
INSTALLED IN 1979, ARE NEAR THE END OF THEIR ANTICIPATED SERVICE LIFE AND
TO UNDERGO REMODEL WITH NEW. PIPING/SPRINKLERS IN BASEMENT WERE
REPLACE EXISTING FIRE SPRINKLERS, AND PIPING THROUGHOUT BASEMENT AREAS
REMODEL. COORDINATE WITH MECHANICAL AND ELECTRICAL SYSTEMS.
REFER TO ARCHITECTURAL PLANS TO DETERMINE SCOPE AND EXTENT OF
SPRINKLER PROTECTION THROUGHOUT BUILDING IN ACCORDANCE WITH NFPA 13.
AND PIPING AS REQUIRED TO ACCOMMODATE REMODEL AND ENSURE FIRE
PROPOSED BUILDING REMODEL. MODIFY, ADJUST AND/OR ADD FIRE SPRINKLERS
PORTIONS OF THE BUILDING TO REMAIN AND TO BE MODIFIED TO ACCOMMODATE
SIGNIFICANT SERVICE LIFE REMAINING. EXISTING FIRE SPRINKLER SYSTEM IN THESE
FIRE SPRINKLERS AND PIPING ON LEVELS 1-3 WERE INSTALLED IN 1999 AND HAVE
8
AREAS TO MAINTAIN WATER SUPPLY.
RECONNECT PIPING TO NEW FIRE SPRINKLER PIPING THROUGHOUT REMODEL
EXISTING FIRE SPRINKLERS AND PIPING OUTSIDE OF REMODEL AREA TO REMAIN.
9
ZONE 3 - RECEPTION/EXHIBIT 55
ZONE 2 - ARCHIVE 57
ZONE 1 - VAULT 56
PANEL AND EXTINGUISHING AGENT (EACH ZONE DISCHARGES INDEPENDENTLY):
SYSTEMS/ZONES AS INDICATED BELOW. ZONES MAY SHARE COMMON CONTROL
PRESENT. PROVIDE 3 SEPARATE AND COMPLETELY DISTINCT FIRE SUPPRESSION
SUSPENDED CEILING AND FLOOR INCLUDING VOLUME BELOW RAISED FLOOR WHERE
SYSTEM SHALL BE TOTAL FLOODING TYPE PROTECTING ENTIRE VOLUME BETWEEN
MANUFACTURER’S REQUIREMENTS AND PROJECT SPECIFICATIONS. CLEAN AGENT
ACCORDANCE WITH ALL APPLICABLE PROVISIONS OF NFPA 72, NFPA 2001,
SYSTEM. DESIGN, INSTALL AND TEST CLEAN AGENT FIRE SUPPRESSION SYSTEM IN
HATCHED AREA TO BE PROTECTED BY CLEAN AGENT (FM-200) FIRE SUPPRESSION
10
18
FIRE SUPPRESSION SYSTEM.
DETECTION/WARNING ONLY AND SHALL NOT BE USED TO RELEASE CLEAN AGENT
BUILDING FIRE ALARM SYSTEM. VESDA SYSTEM IS FOR EARLY SMOKE
NORMALLY OCCUPIED AREA. PROGRAM HIGH THRESHOLD ALARM TO ACTIVATE
PROGRAM LOW THRESHOLD ALARM (EARLY) TO SOUND SUPERVISORY ALARM IN
THROUGHOUT ARE PROTECTED BY CLEAN AGENT FIRE SUPPRESSION SYSTEM.
INSTALL AIR SAMPLING TYPE, EARLY WARNING SMOKE DETECTION SYSTEM (VESDA)
19
AREAS FOR WATER SUPPLY.
HAZARD GROUP 1. CONNECT TO EXISTING FIRE SPRINKLER PIPING IN ADJACENT
DESIGN FIRE SPRINKLERS TO PROTECT A HAZARD CLASSIFICATION OF ORDINARY
EXTEND FIRE SPRINKLER PROTECT INTO EXISTING BASEMENT ELECTRICAL ROOM.
88
8
8
8
7 7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7 7
4
KEY PLAN
A
B
SCALE: 1/8" = 1’-0"
1
0510 10 20
FP102a FP102a
Plan
Level 02 Area
LEVEL 02 AREA A FIRE PROTECTION PLAN
A Fire
Protection
ELECTRICAL
ROOM
ELEC ROOM
EVYLYN’S OPEN
OFFICE
JOLENE’S OPEN
OFFICE
TECH SERVICES
SHEET MUSIC LARGE
COMPUTER
CLASSROOM
OPEN
COMPUTERS
MOTHERS FAMILY RR
OPEN STUDY
PRESS ROOM
RECEPTION
/EXHIBIT
VAULT
ARCHIVE
INSTRUCTION 2INSTRUCTION 1
DCAM HANNA OFFICE
SCANNER
ADAM OFFICE
STUDY (MED)STUDY (MED)STUDY (MED)
STUDY (SM)
JANITOR
OFFICE
JULIE’S OFFICE
STUDY (SM)STUDY (SM)STUDY (SM)
INA’S OFFICE
STUDY (MED)
RECEP
OPEN STUDY
MECHANICAL
I.T.
MEN’S
RESTROOM
WOMEN’S
RESTROOM
STAIR
ELEV ELEV EQUIP
STAIR
STAIR
OPEN STUDY
FSRP
L R
A
A
A
A
DIL RACHELS
VESDA
21.0780
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
10/27/2022
Bid Set
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # :12242
10/27/2022
1
2
3
4
5
FIRE PROTECTION KEY NOTES
RE: SHEETS FP100a - FP103a
ZONE.
INDEPENDENTLY). SIZE AGENT STORAGE TO SUPPLY AGENT TO THE LARGEST
SYSTEM ZONE MAY SHARE AGENT STORAGE CYLINDERS (ZONE DISCHARGE
NFPA 2001 AND FIRE SUPPRESSION SYSTEM MANUFACTURER. FIRE SUPPRESSION
CALCULATED TO PROVIDE THE MINIMUM DESIGN CONCENTRATION REQUIRED BY
SHALL BE DETERMINED BY FACTORY TRAINED SYSTEM DESIGNER AND SHALL BE
WHERE INDICATED ON PLANS. SIZE/CAPACITY AND FILL LEVEL OF CYLINDERS
CLEAN AGENT STORAGE CYLINDERS. INSTALL IN OR NEAR PROTECTED AREA
11
CONTROL PANEL TO BUILDING FIRE ALARM SYSTEM.
REQUIREMENTS. CONNECT FIRE ALARM, SUPERVISORY AND TROUBLE RELAYS OF
APPLICABLE REQUIREMENTS OF NFPA 72, 2001 AND MANUFACTURER’S
SYSTEM SHALL BE DESIGNED, INSTALLED AND TESTED IN ACCORDANCE WITH ALL
RELEASE OF CLEAN AGENT FIRE SUPPRESSION SYSTEM. CONTROL/RELEASING
CONTROL PANEL (UL LISTED AND FM APPROVED FOR RELEASING SERVICE) FOR
12
REQUIREMENTS.
APPLICABLE PROVISIONS OF NFPA 72, NFPA 2001 AND MANUFACTURER’S
INSTALL AND TEST SMOKE DETECTION SYSTEM IN ACCORDANCE WITH ALL
CONNECTED TO DIFFERENT INITIATING DEVICE ZONES (ZONE A OR B). DESIGN,
WHERE PRESENT (NOT SHOWN ON PLANS). ADJACENT DETECTORS SHALL BE
DETECTORS IN EACH ROOM/SPACE INCLUDING AREAS UNDER RAISED FLOORS
EACH DETECTOR SHALL BE 225 SQ FT (15’ X 15’). PROVIDE AT LEAST 2
ACTUATION OF CLEAN AGENT FIRE SUPPRESSION SYSTEMS. MAXIMUM SPACING FOR
INSTALL CROSS ZONED SMOKE DETECTION SYSTEM TO PROVIDE AUTOMATIC
13
SYSTEM" OR "ABORT FIRE SUPPRESSION SYSTEM RELEASE" AS APPROPRIATE.
DESCRIBE SWITCH FUNCTION. SIGN SHALL STATE "RELEASE FIRE SUPPRESSION
FROM PROTECTED SPACE. INSTALL SIGNS ADJACENT TO EACH SWITCH TO
COUNTDOWN WHEN RELEASED. INSTALL SWITCHES ADJACENT TO EACH EXIT DOOR
ABORT SWITCH SHALL RESET DISCHARGE TIME DELAY COUNTER AND RESTART
PROVIDE MANUAL CONTROL OF EACH CLEAN AGENT FIRE SUPPRESSION SYSTEM.
INSTALL MANUAL RELEASE AND "CONSTANT PRESSURE" TYPE ABORT SWITCHES TO
14
SHALL TRANSMIT A SUPERVISORY ALARM TO CONTROL/RELEASING PANEL.
OF EACH FIRE SUPPRESSION SYSTEM WHEN ACTIVATED. ACTIVATION OF SWITCH
CONTROL/RELEASING PANEL. CONFIGURE SWITCH TO DISABLE RELEASING RELAYS
SUPPRESSION SYSTEM. INSTALL SYSTEM LOCKOUT ADJACENT TO
INSTALL KEY OPERATED, MANUAL LOCK OUT SWITCH FOR CLEAN AGENT FIRE
15
SYSTEMS TO BE DETERMINED BY INSTALLING CONTRACTOR.
SYSTEM. REQUIRED NUMBER AND LOCATION OF RELAYS AS WELL AS INTERFACED
OFF, ETC.) REQUIRED FOR PROPER FUNCTION OF CLEAN AGENT FIRE SUPPRESSION
AUXILIARY FUNCTIONS (I.E. DAMPER CLOSURE, FAN SHUTDOWN, EMERGENCY POWER
INSTALL RELAYS FROM CONTROL/RELEASING PANEL TO INITIATE ALL REQUIRED
16
SUPPRESSION SYSTEM PRE -DISCHARGE ALARM".
PROTECTED AREA. INSTALL SIGN ADJACENT TO EACH ALARM STATING "FIRE
SOUND UPON ACTIVATION OF ANY SINGLE SMOKE DETECTION ZONE FOR
PROTECTED SPACE ABOVE EACH EXIT DOOR. CONFIGURE ALARM TO FLASH AND
BUILDING FIRE ALARM) FOR CLEAN AGENT FIRE SUPPRESSION SYSTEM INSIDE
INSTALL PRE -DISCHARGE ALARM (AUDIBLE AND VISIBLE SIGNALS DISTINCT FROM
17
SYSTEM RELEASED WHEN FLASHING".
RELEASE. INSTALL SIGN ADJACENT TO EACH STROBE STATING "FIRE SUPPRESSION
ABOVE EACH EXIT DOOR AND CONFIGURE STROBES TO FLASH UPON AGENT
THE INTERIOR AND EXTERIOR OF PROTECTED SPACE. INSTALL DISCHARGE STROBES
INSTALL DISCHARGE STROBES FOR CLEAN AGENT FIRE SUPPRESSION SYSTEM IN
TEST BY: GREG JONES - PCI
TEST LOCATION: SIDEWALK AREA NORTHWEST OF BUILDING
TEST DATE: 8/10/22
FLOW: 1,321 GPM
RESIDUAL PRESSURE: 72 PSI
STATIC PRESSURE: 81 PSI
SYSTEM SUPPLIES THE FOLLOWING PRESSURES/FLOW FOR FIRE PROTECTION:
EXISTING 6" FIRE PROTECTION WATER SUPPLY TO BUILDING TO REMAIN. WATER
CONNECT TO RISER DOWNSTREAM OF ALARM VALVE.
SUPPLY FROM EXTERIOR, FREE STANDING FIRE DEPARTMENT CONNECTION
VALVE ASSEMBLY (RETROFIT), 4" OS&Y VALVE AND ALARM VALVE WITH TRIM. 4"
EXISTING FIRE SPRINKLER RISER TO REMAIN. RISER INCLUDES 4" DOUBLE CHECK
EXISTING 4" VERTICAL FEED MAIN INSTALLED IN MECHANICAL SHAFT TO REMAIN.
EACH FLOOR LEVEL TO REMAIN.
EXISTING FIRE SPRINKLER CONTROL VALVE TO ISOLATE FIRE SPRINKLERS ON
B (1ST AND 2ND LEVELS) TO REMAIN.
EXISTING 3" HORIZONTAL FEED MAIN TO SUPPLY FIRE SPRINKLER ZONES IN AREA
6
7
TO ARCHITECTURAL PLANS TO DETERMINE SCOPE AND EXTENT OF REMODEL.
REUSED WHERE COMPLETELY FUNCTIONAL AND COMPLIANT WITH NFPA 13. REFER
OF REMODEL AREA. EXISTING PIPING SUPPORTS AND BRACES MAY REMAIN TO BE
PIPING, COUPLINGS, FITTINGS AND FIRE SPRINKLERS. REMOVE PIPING BACK TO EDGE
SHOULD BE REPLACED WITH NEW PIPING/SPRINKLERS REMOVE ALL EXISTING
INSTALLED IN 1979, ARE NEAR THE END OF THEIR ANTICIPATED SERVICE LIFE AND
TO UNDERGO REMODEL WITH NEW. PIPING/SPRINKLERS IN BASEMENT WERE
REPLACE EXISTING FIRE SPRINKLERS, AND PIPING THROUGHOUT BASEMENT AREAS
REMODEL. COORDINATE WITH MECHANICAL AND ELECTRICAL SYSTEMS.
REFER TO ARCHITECTURAL PLANS TO DETERMINE SCOPE AND EXTENT OF
SPRINKLER PROTECTION THROUGHOUT BUILDING IN ACCORDANCE WITH NFPA 13.
AND PIPING AS REQUIRED TO ACCOMMODATE REMODEL AND ENSURE FIRE
PROPOSED BUILDING REMODEL. MODIFY, ADJUST AND/OR ADD FIRE SPRINKLERS
PORTIONS OF THE BUILDING TO REMAIN AND TO BE MODIFIED TO ACCOMMODATE
SIGNIFICANT SERVICE LIFE REMAINING. EXISTING FIRE SPRINKLER SYSTEM IN THESE
FIRE SPRINKLERS AND PIPING ON LEVELS 1-3 WERE INSTALLED IN 1999 AND HAVE
8
AREAS TO MAINTAIN WATER SUPPLY.
RECONNECT PIPING TO NEW FIRE SPRINKLER PIPING THROUGHOUT REMODEL
EXISTING FIRE SPRINKLERS AND PIPING OUTSIDE OF REMODEL AREA TO REMAIN.
9
ZONE 3 - RECEPTION/EXHIBIT 55
ZONE 2 - ARCHIVE 57
ZONE 1 - VAULT 56
PANEL AND EXTINGUISHING AGENT (EACH ZONE DISCHARGES INDEPENDENTLY):
SYSTEMS/ZONES AS INDICATED BELOW. ZONES MAY SHARE COMMON CONTROL
PRESENT. PROVIDE 3 SEPARATE AND COMPLETELY DISTINCT FIRE SUPPRESSION
SUSPENDED CEILING AND FLOOR INCLUDING VOLUME BELOW RAISED FLOOR WHERE
SYSTEM SHALL BE TOTAL FLOODING TYPE PROTECTING ENTIRE VOLUME BETWEEN
MANUFACTURER’S REQUIREMENTS AND PROJECT SPECIFICATIONS. CLEAN AGENT
ACCORDANCE WITH ALL APPLICABLE PROVISIONS OF NFPA 72, NFPA 2001,
SYSTEM. DESIGN, INSTALL AND TEST CLEAN AGENT FIRE SUPPRESSION SYSTEM IN
HATCHED AREA TO BE PROTECTED BY CLEAN AGENT (FM-200) FIRE SUPPRESSION
10
18
FIRE SUPPRESSION SYSTEM.
DETECTION/WARNING ONLY AND SHALL NOT BE USED TO RELEASE CLEAN AGENT
BUILDING FIRE ALARM SYSTEM. VESDA SYSTEM IS FOR EARLY SMOKE
NORMALLY OCCUPIED AREA. PROGRAM HIGH THRESHOLD ALARM TO ACTIVATE
PROGRAM LOW THRESHOLD ALARM (EARLY) TO SOUND SUPERVISORY ALARM IN
THROUGHOUT ARE PROTECTED BY CLEAN AGENT FIRE SUPPRESSION SYSTEM.
INSTALL AIR SAMPLING TYPE, EARLY WARNING SMOKE DETECTION SYSTEM (VESDA)
19
AREAS FOR WATER SUPPLY.
HAZARD GROUP 1. CONNECT TO EXISTING FIRE SPRINKLER PIPING IN ADJACENT
DESIGN FIRE SPRINKLERS TO PROTECT A HAZARD CLASSIFICATION OF ORDINARY
EXTEND FIRE SPRINKLER PROTECT INTO EXISTING BASEMENT ELECTRICAL ROOM.
11
8
8
8
8
8
8
87
7
7
7
7
7
7
7
7 7
7
77
7 7 7
13
13
13
13
A B
A B A B
A B
A B
A B
A
B
A B
9
9
9
9
9
9
10
14
15
16
17
17
16
17
16
17
16
3
4
5
5
5
5
5
12
12
12
12
12
12
18
18
18
18
18
18
18
18
18
18
KEY PLAN
A
B
SCALE: 1/8" = 1’-0"
1
0510 10 20
FP102b
FP102b
Plan
Level 02 Area
LEVEL 02 AREA B FIRE PROTECTION PLAN
Protection
B Fire
READING
CENTER
SETH’S OFFICE
OFFICE
STUDY
ENGLISH
TRANSITION
CENTER
OPEN TUTORING
STUDY SKILLS /
READING
WRITING
CENTER OPEN
TUTORING
STUDYSTUDYSTUDYSTUDYOFFICEOFFICE
STUDY
STUDY
PREP /
STORAGE
CLASSROOM
CLASSROOM
TUTOR PREP DJ’S OFFICE MICHAEL’S
OFFICE
OPEN TUTORING
CENTER
ADJUNCT
OFFICE
TR / COMM.
CLASSROOM
PRE-FUNCTION PRE-FUNCTION PRE-FUNCTION
RECEPTION
PREFUNCTION
STORAGE
PAULETTE’S
OFFICE
BREAK
DJ’S OFFICE
STORAGE
STUDY
STUDY
STUDY
STORAGE
ELEV
16
15
15
14
14
13
13
12
12
11
11
10
10
9
9
8
8
7
7
K
H
F
D
B
A
L
21.0780
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
10/27/2022
Bid Set
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # :12242
10/27/2022
1
2
3
4
5
FIRE PROTECTION KEY NOTES
RE: SHEETS FP100a - FP103a
ZONE.
INDEPENDENTLY). SIZE AGENT STORAGE TO SUPPLY AGENT TO THE LARGEST
SYSTEM ZONE MAY SHARE AGENT STORAGE CYLINDERS (ZONE DISCHARGE
NFPA 2001 AND FIRE SUPPRESSION SYSTEM MANUFACTURER. FIRE SUPPRESSION
CALCULATED TO PROVIDE THE MINIMUM DESIGN CONCENTRATION REQUIRED BY
SHALL BE DETERMINED BY FACTORY TRAINED SYSTEM DESIGNER AND SHALL BE
WHERE INDICATED ON PLANS. SIZE/CAPACITY AND FILL LEVEL OF CYLINDERS
CLEAN AGENT STORAGE CYLINDERS. INSTALL IN OR NEAR PROTECTED AREA
11
CONTROL PANEL TO BUILDING FIRE ALARM SYSTEM.
REQUIREMENTS. CONNECT FIRE ALARM, SUPERVISORY AND TROUBLE RELAYS OF
APPLICABLE REQUIREMENTS OF NFPA 72, 2001 AND MANUFACTURER’S
SYSTEM SHALL BE DESIGNED, INSTALLED AND TESTED IN ACCORDANCE WITH ALL
RELEASE OF CLEAN AGENT FIRE SUPPRESSION SYSTEM. CONTROL/RELEASING
CONTROL PANEL (UL LISTED AND FM APPROVED FOR RELEASING SERVICE) FOR
12
REQUIREMENTS.
APPLICABLE PROVISIONS OF NFPA 72, NFPA 2001 AND MANUFACTURER’S
INSTALL AND TEST SMOKE DETECTION SYSTEM IN ACCORDANCE WITH ALL
CONNECTED TO DIFFERENT INITIATING DEVICE ZONES (ZONE A OR B). DESIGN,
WHERE PRESENT (NOT SHOWN ON PLANS). ADJACENT DETECTORS SHALL BE
DETECTORS IN EACH ROOM/SPACE INCLUDING AREAS UNDER RAISED FLOORS
EACH DETECTOR SHALL BE 225 SQ FT (15’ X 15’). PROVIDE AT LEAST 2
ACTUATION OF CLEAN AGENT FIRE SUPPRESSION SYSTEMS. MAXIMUM SPACING FOR
INSTALL CROSS ZONED SMOKE DETECTION SYSTEM TO PROVIDE AUTOMATIC
13
SYSTEM" OR "ABORT FIRE SUPPRESSION SYSTEM RELEASE" AS APPROPRIATE.
DESCRIBE SWITCH FUNCTION. SIGN SHALL STATE "RELEASE FIRE SUPPRESSION
FROM PROTECTED SPACE. INSTALL SIGNS ADJACENT TO EACH SWITCH TO
COUNTDOWN WHEN RELEASED. INSTALL SWITCHES ADJACENT TO EACH EXIT DOOR
ABORT SWITCH SHALL RESET DISCHARGE TIME DELAY COUNTER AND RESTART
PROVIDE MANUAL CONTROL OF EACH CLEAN AGENT FIRE SUPPRESSION SYSTEM.
INSTALL MANUAL RELEASE AND "CONSTANT PRESSURE" TYPE ABORT SWITCHES TO
14
SHALL TRANSMIT A SUPERVISORY ALARM TO CONTROL/RELEASING PANEL.
OF EACH FIRE SUPPRESSION SYSTEM WHEN ACTIVATED. ACTIVATION OF SWITCH
CONTROL/RELEASING PANEL. CONFIGURE SWITCH TO DISABLE RELEASING RELAYS
SUPPRESSION SYSTEM. INSTALL SYSTEM LOCKOUT ADJACENT TO
INSTALL KEY OPERATED, MANUAL LOCK OUT SWITCH FOR CLEAN AGENT FIRE
15
SYSTEMS TO BE DETERMINED BY INSTALLING CONTRACTOR.
SYSTEM. REQUIRED NUMBER AND LOCATION OF RELAYS AS WELL AS INTERFACED
OFF, ETC.) REQUIRED FOR PROPER FUNCTION OF CLEAN AGENT FIRE SUPPRESSION
AUXILIARY FUNCTIONS (I.E. DAMPER CLOSURE, FAN SHUTDOWN, EMERGENCY POWER
INSTALL RELAYS FROM CONTROL/RELEASING PANEL TO INITIATE ALL REQUIRED
16
SUPPRESSION SYSTEM PRE -DISCHARGE ALARM".
PROTECTED AREA. INSTALL SIGN ADJACENT TO EACH ALARM STATING "FIRE
SOUND UPON ACTIVATION OF ANY SINGLE SMOKE DETECTION ZONE FOR
PROTECTED SPACE ABOVE EACH EXIT DOOR. CONFIGURE ALARM TO FLASH AND
BUILDING FIRE ALARM) FOR CLEAN AGENT FIRE SUPPRESSION SYSTEM INSIDE
INSTALL PRE -DISCHARGE ALARM (AUDIBLE AND VISIBLE SIGNALS DISTINCT FROM
17
SYSTEM RELEASED WHEN FLASHING".
RELEASE. INSTALL SIGN ADJACENT TO EACH STROBE STATING "FIRE SUPPRESSION
ABOVE EACH EXIT DOOR AND CONFIGURE STROBES TO FLASH UPON AGENT
THE INTERIOR AND EXTERIOR OF PROTECTED SPACE. INSTALL DISCHARGE STROBES
INSTALL DISCHARGE STROBES FOR CLEAN AGENT FIRE SUPPRESSION SYSTEM IN
TEST BY: GREG JONES - PCI
TEST LOCATION: SIDEWALK AREA NORTHWEST OF BUILDING
TEST DATE: 8/10/22
FLOW: 1,321 GPM
RESIDUAL PRESSURE: 72 PSI
STATIC PRESSURE: 81 PSI
SYSTEM SUPPLIES THE FOLLOWING PRESSURES/FLOW FOR FIRE PROTECTION:
EXISTING 6" FIRE PROTECTION WATER SUPPLY TO BUILDING TO REMAIN. WATER
CONNECT TO RISER DOWNSTREAM OF ALARM VALVE.
SUPPLY FROM EXTERIOR, FREE STANDING FIRE DEPARTMENT CONNECTION
VALVE ASSEMBLY (RETROFIT), 4" OS&Y VALVE AND ALARM VALVE WITH TRIM. 4"
EXISTING FIRE SPRINKLER RISER TO REMAIN. RISER INCLUDES 4" DOUBLE CHECK
EXISTING 4" VERTICAL FEED MAIN INSTALLED IN MECHANICAL SHAFT TO REMAIN.
EACH FLOOR LEVEL TO REMAIN.
EXISTING FIRE SPRINKLER CONTROL VALVE TO ISOLATE FIRE SPRINKLERS ON
B (1ST AND 2ND LEVELS) TO REMAIN.
EXISTING 3" HORIZONTAL FEED MAIN TO SUPPLY FIRE SPRINKLER ZONES IN AREA
6
7
TO ARCHITECTURAL PLANS TO DETERMINE SCOPE AND EXTENT OF REMODEL.
REUSED WHERE COMPLETELY FUNCTIONAL AND COMPLIANT WITH NFPA 13. REFER
OF REMODEL AREA. EXISTING PIPING SUPPORTS AND BRACES MAY REMAIN TO BE
PIPING, COUPLINGS, FITTINGS AND FIRE SPRINKLERS. REMOVE PIPING BACK TO EDGE
SHOULD BE REPLACED WITH NEW PIPING/SPRINKLERS REMOVE ALL EXISTING
INSTALLED IN 1979, ARE NEAR THE END OF THEIR ANTICIPATED SERVICE LIFE AND
TO UNDERGO REMODEL WITH NEW. PIPING/SPRINKLERS IN BASEMENT WERE
REPLACE EXISTING FIRE SPRINKLERS, AND PIPING THROUGHOUT BASEMENT AREAS
REMODEL. COORDINATE WITH MECHANICAL AND ELECTRICAL SYSTEMS.
REFER TO ARCHITECTURAL PLANS TO DETERMINE SCOPE AND EXTENT OF
SPRINKLER PROTECTION THROUGHOUT BUILDING IN ACCORDANCE WITH NFPA 13.
AND PIPING AS REQUIRED TO ACCOMMODATE REMODEL AND ENSURE FIRE
PROPOSED BUILDING REMODEL. MODIFY, ADJUST AND/OR ADD FIRE SPRINKLERS
PORTIONS OF THE BUILDING TO REMAIN AND TO BE MODIFIED TO ACCOMMODATE
SIGNIFICANT SERVICE LIFE REMAINING. EXISTING FIRE SPRINKLER SYSTEM IN THESE
FIRE SPRINKLERS AND PIPING ON LEVELS 1-3 WERE INSTALLED IN 1999 AND HAVE
8
AREAS TO MAINTAIN WATER SUPPLY.
RECONNECT PIPING TO NEW FIRE SPRINKLER PIPING THROUGHOUT REMODEL
EXISTING FIRE SPRINKLERS AND PIPING OUTSIDE OF REMODEL AREA TO REMAIN.
9
ZONE 3 - RECEPTION/EXHIBIT 55
ZONE 2 - ARCHIVE 57
ZONE 1 - VAULT 56
PANEL AND EXTINGUISHING AGENT (EACH ZONE DISCHARGES INDEPENDENTLY):
SYSTEMS/ZONES AS INDICATED BELOW. ZONES MAY SHARE COMMON CONTROL
PRESENT. PROVIDE 3 SEPARATE AND COMPLETELY DISTINCT FIRE SUPPRESSION
SUSPENDED CEILING AND FLOOR INCLUDING VOLUME BELOW RAISED FLOOR WHERE
SYSTEM SHALL BE TOTAL FLOODING TYPE PROTECTING ENTIRE VOLUME BETWEEN
MANUFACTURER’S REQUIREMENTS AND PROJECT SPECIFICATIONS. CLEAN AGENT
ACCORDANCE WITH ALL APPLICABLE PROVISIONS OF NFPA 72, NFPA 2001,
SYSTEM. DESIGN, INSTALL AND TEST CLEAN AGENT FIRE SUPPRESSION SYSTEM IN
HATCHED AREA TO BE PROTECTED BY CLEAN AGENT (FM-200) FIRE SUPPRESSION
10
18
FIRE SUPPRESSION SYSTEM.
DETECTION/WARNING ONLY AND SHALL NOT BE USED TO RELEASE CLEAN AGENT
BUILDING FIRE ALARM SYSTEM. VESDA SYSTEM IS FOR EARLY SMOKE
NORMALLY OCCUPIED AREA. PROGRAM HIGH THRESHOLD ALARM TO ACTIVATE
PROGRAM LOW THRESHOLD ALARM (EARLY) TO SOUND SUPERVISORY ALARM IN
THROUGHOUT ARE PROTECTED BY CLEAN AGENT FIRE SUPPRESSION SYSTEM.
INSTALL AIR SAMPLING TYPE, EARLY WARNING SMOKE DETECTION SYSTEM (VESDA)
19
AREAS FOR WATER SUPPLY.
HAZARD GROUP 1. CONNECT TO EXISTING FIRE SPRINKLER PIPING IN ADJACENT
DESIGN FIRE SPRINKLERS TO PROTECT A HAZARD CLASSIFICATION OF ORDINARY
EXTEND FIRE SPRINKLER PROTECT INTO EXISTING BASEMENT ELECTRICAL ROOM.
7
7
7
7
7
7
7
7
77
7
7
7
7
7
7
7
7
7
8
8
4
5
KEY PLAN
A
B
SCALE: 1/8" = 1’-0"
1
0510 10 20
FP103a FP103a
Plan
Level 03 Area
LEVEL 03 AREA A FIRE PROTECTION PLAN
Protection
A Fire
TLC LIBRARIAN
HOLLY
STUDENT
ENGAGEMENT
LIBRARIAN
VERONICA
TLC
WORKSPACE
TEACHER
LEARNING
CENTER
JUVENILLE
STORAGE STUDY (MED)
STUDY (MED)
CIRC/SEC
KIDS PLAYMOTHERS
ROOM
RESTROOM
FAMILY STUDY
OPEN STUDY
OPEN STUDY
Bridge
Connection
BRIDGE
CONNECTION
STAIR 1
MENS
WOMENS
SINGLE TEST
RM
WENDY /
CUSTODIAL
OFFICE
Janitors Closet
MAC
SUPERVISOR
REBEKAH
MAC EQUIP STUDY (LG)
STUDY (LG)MAC LAB
STUDY (SM)
STUDY (SM)
STUDY (SM)
SINGLE TEST
RM
STUDY (SM)
STUDY (SM)
123 SF
STUDY (SM)
ELECTRICAL
ELEC
STUDY (SM)
STUDY (SM)
STUDY (SM)
( QUIET )
OPEN STUDY
ELECTRICAL
STORAGE
SINGLE TEST
RM
Room
Room
SINGLE TEST
RM
SINGLE TEST
RM
SINGLE TEST
RM
SINGLE TEST
RM
SINGLE TEST
RM
SINGLE TEST
RM
SINGLE TEST
RM
SINGLE TEST
RM
SINGLE TEST
RM
SINGLE TEST
RM
SINGLE TEST
RM
SINGLE TEST
RM
1
G
J
L
M
N
P
Q
E
C
2 3 4 51.5 6
21.0780
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
10/27/2022
Bid Set
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
b y u i d a h o p r o j e c t # :12242
10/27/2022
1
2
3
4
5
FIRE PROTECTION KEY NOTES
RE: SHEETS FP100a - FP103a
ZONE.
INDEPENDENTLY). SIZE AGENT STORAGE TO SUPPLY AGENT TO THE LARGEST
SYSTEM ZONE MAY SHARE AGENT STORAGE CYLINDERS (ZONE DISCHARGE
NFPA 2001 AND FIRE SUPPRESSION SYSTEM MANUFACTURER. FIRE SUPPRESSION
CALCULATED TO PROVIDE THE MINIMUM DESIGN CONCENTRATION REQUIRED BY
SHALL BE DETERMINED BY FACTORY TRAINED SYSTEM DESIGNER AND SHALL BE
WHERE INDICATED ON PLANS. SIZE/CAPACITY AND FILL LEVEL OF CYLINDERS
CLEAN AGENT STORAGE CYLINDERS. INSTALL IN OR NEAR PROTECTED AREA
11
CONTROL PANEL TO BUILDING FIRE ALARM SYSTEM.
REQUIREMENTS. CONNECT FIRE ALARM, SUPERVISORY AND TROUBLE RELAYS OF
APPLICABLE REQUIREMENTS OF NFPA 72, 2001 AND MANUFACTURER’S
SYSTEM SHALL BE DESIGNED, INSTALLED AND TESTED IN ACCORDANCE WITH ALL
RELEASE OF CLEAN AGENT FIRE SUPPRESSION SYSTEM. CONTROL/RELEASING
CONTROL PANEL (UL LISTED AND FM APPROVED FOR RELEASING SERVICE) FOR
12
REQUIREMENTS.
APPLICABLE PROVISIONS OF NFPA 72, NFPA 2001 AND MANUFACTURER’S
INSTALL AND TEST SMOKE DETECTION SYSTEM IN ACCORDANCE WITH ALL
CONNECTED TO DIFFERENT INITIATING DEVICE ZONES (ZONE A OR B). DESIGN,
WHERE PRESENT (NOT SHOWN ON PLANS). ADJACENT DETECTORS SHALL BE
DETECTORS IN EACH ROOM/SPACE INCLUDING AREAS UNDER RAISED FLOORS
EACH DETECTOR SHALL BE 225 SQ FT (15’ X 15’). PROVIDE AT LEAST 2
ACTUATION OF CLEAN AGENT FIRE SUPPRESSION SYSTEMS. MAXIMUM SPACING FOR
INSTALL CROSS ZONED SMOKE DETECTION SYSTEM TO PROVIDE AUTOMATIC
13
SYSTEM" OR "ABORT FIRE SUPPRESSION SYSTEM RELEASE" AS APPROPRIATE.
DESCRIBE SWITCH FUNCTION. SIGN SHALL STATE "RELEASE FIRE SUPPRESSION
FROM PROTECTED SPACE. INSTALL SIGNS ADJACENT TO EACH SWITCH TO
COUNTDOWN WHEN RELEASED. INSTALL SWITCHES ADJACENT TO EACH EXIT DOOR
ABORT SWITCH SHALL RESET DISCHARGE TIME DELAY COUNTER AND RESTART
PROVIDE MANUAL CONTROL OF EACH CLEAN AGENT FIRE SUPPRESSION SYSTEM.
INSTALL MANUAL RELEASE AND "CONSTANT PRESSURE" TYPE ABORT SWITCHES TO
14
SHALL TRANSMIT A SUPERVISORY ALARM TO CONTROL/RELEASING PANEL.
OF EACH FIRE SUPPRESSION SYSTEM WHEN ACTIVATED. ACTIVATION OF SWITCH
CONTROL/RELEASING PANEL. CONFIGURE SWITCH TO DISABLE RELEASING RELAYS
SUPPRESSION SYSTEM. INSTALL SYSTEM LOCKOUT ADJACENT TO
INSTALL KEY OPERATED, MANUAL LOCK OUT SWITCH FOR CLEAN AGENT FIRE
15
SYSTEMS TO BE DETERMINED BY INSTALLING CONTRACTOR.
SYSTEM. REQUIRED NUMBER AND LOCATION OF RELAYS AS WELL AS INTERFACED
OFF, ETC.) REQUIRED FOR PROPER FUNCTION OF CLEAN AGENT FIRE SUPPRESSION
AUXILIARY FUNCTIONS (I.E. DAMPER CLOSURE, FAN SHUTDOWN, EMERGENCY POWER
INSTALL RELAYS FROM CONTROL/RELEASING PANEL TO INITIATE ALL REQUIRED
16
SUPPRESSION SYSTEM PRE -DISCHARGE ALARM".
PROTECTED AREA. INSTALL SIGN ADJACENT TO EACH ALARM STATING "FIRE
SOUND UPON ACTIVATION OF ANY SINGLE SMOKE DETECTION ZONE FOR
PROTECTED SPACE ABOVE EACH EXIT DOOR. CONFIGURE ALARM TO FLASH AND
BUILDING FIRE ALARM) FOR CLEAN AGENT FIRE SUPPRESSION SYSTEM INSIDE
INSTALL PRE -DISCHARGE ALARM (AUDIBLE AND VISIBLE SIGNALS DISTINCT FROM
17
SYSTEM RELEASED WHEN FLASHING".
RELEASE. INSTALL SIGN ADJACENT TO EACH STROBE STATING "FIRE SUPPRESSION
ABOVE EACH EXIT DOOR AND CONFIGURE STROBES TO FLASH UPON AGENT
THE INTERIOR AND EXTERIOR OF PROTECTED SPACE. INSTALL DISCHARGE STROBES
INSTALL DISCHARGE STROBES FOR CLEAN AGENT FIRE SUPPRESSION SYSTEM IN
TEST BY: GREG JONES - PCI
TEST LOCATION: SIDEWALK AREA NORTHWEST OF BUILDING
TEST DATE: 8/10/22
FLOW: 1,321 GPM
RESIDUAL PRESSURE: 72 PSI
STATIC PRESSURE: 81 PSI
SYSTEM SUPPLIES THE FOLLOWING PRESSURES/FLOW FOR FIRE PROTECTION:
EXISTING 6" FIRE PROTECTION WATER SUPPLY TO BUILDING TO REMAIN. WATER
CONNECT TO RISER DOWNSTREAM OF ALARM VALVE.
SUPPLY FROM EXTERIOR, FREE STANDING FIRE DEPARTMENT CONNECTION
VALVE ASSEMBLY (RETROFIT), 4" OS&Y VALVE AND ALARM VALVE WITH TRIM. 4"
EXISTING FIRE SPRINKLER RISER TO REMAIN. RISER INCLUDES 4" DOUBLE CHECK
EXISTING 4" VERTICAL FEED MAIN INSTALLED IN MECHANICAL SHAFT TO REMAIN.
EACH FLOOR LEVEL TO REMAIN.
EXISTING FIRE SPRINKLER CONTROL VALVE TO ISOLATE FIRE SPRINKLERS ON
B (1ST AND 2ND LEVELS) TO REMAIN.
EXISTING 3" HORIZONTAL FEED MAIN TO SUPPLY FIRE SPRINKLER ZONES IN AREA
6
7
TO ARCHITECTURAL PLANS TO DETERMINE SCOPE AND EXTENT OF REMODEL.
REUSED WHERE COMPLETELY FUNCTIONAL AND COMPLIANT WITH NFPA 13. REFER
OF REMODEL AREA. EXISTING PIPING SUPPORTS AND BRACES MAY REMAIN TO BE
PIPING, COUPLINGS, FITTINGS AND FIRE SPRINKLERS. REMOVE PIPING BACK TO EDGE
SHOULD BE REPLACED WITH NEW PIPING/SPRINKLERS REMOVE ALL EXISTING
INSTALLED IN 1979, ARE NEAR THE END OF THEIR ANTICIPATED SERVICE LIFE AND
TO UNDERGO REMODEL WITH NEW. PIPING/SPRINKLERS IN BASEMENT WERE
REPLACE EXISTING FIRE SPRINKLERS, AND PIPING THROUGHOUT BASEMENT AREAS
REMODEL. COORDINATE WITH MECHANICAL AND ELECTRICAL SYSTEMS.
REFER TO ARCHITECTURAL PLANS TO DETERMINE SCOPE AND EXTENT OF
SPRINKLER PROTECTION THROUGHOUT BUILDING IN ACCORDANCE WITH NFPA 13.
AND PIPING AS REQUIRED TO ACCOMMODATE REMODEL AND ENSURE FIRE
PROPOSED BUILDING REMODEL. MODIFY, ADJUST AND/OR ADD FIRE SPRINKLERS
PORTIONS OF THE BUILDING TO REMAIN AND TO BE MODIFIED TO ACCOMMODATE
SIGNIFICANT SERVICE LIFE REMAINING. EXISTING FIRE SPRINKLER SYSTEM IN THESE
FIRE SPRINKLERS AND PIPING ON LEVELS 1-3 WERE INSTALLED IN 1999 AND HAVE
8
AREAS TO MAINTAIN WATER SUPPLY.
RECONNECT PIPING TO NEW FIRE SPRINKLER PIPING THROUGHOUT REMODEL
EXISTING FIRE SPRINKLERS AND PIPING OUTSIDE OF REMODEL AREA TO REMAIN.
9
ZONE 3 - RECEPTION/EXHIBIT 55
ZONE 2 - ARCHIVE 57
ZONE 1 - VAULT 56
PANEL AND EXTINGUISHING AGENT (EACH ZONE DISCHARGES INDEPENDENTLY):
SYSTEMS/ZONES AS INDICATED BELOW. ZONES MAY SHARE COMMON CONTROL
PRESENT. PROVIDE 3 SEPARATE AND COMPLETELY DISTINCT FIRE SUPPRESSION
SUSPENDED CEILING AND FLOOR INCLUDING VOLUME BELOW RAISED FLOOR WHERE
SYSTEM SHALL BE TOTAL FLOODING TYPE PROTECTING ENTIRE VOLUME BETWEEN
MANUFACTURER’S REQUIREMENTS AND PROJECT SPECIFICATIONS. CLEAN AGENT
ACCORDANCE WITH ALL APPLICABLE PROVISIONS OF NFPA 72, NFPA 2001,
SYSTEM. DESIGN, INSTALL AND TEST CLEAN AGENT FIRE SUPPRESSION SYSTEM IN
HATCHED AREA TO BE PROTECTED BY CLEAN AGENT (FM-200) FIRE SUPPRESSION
10
18
FIRE SUPPRESSION SYSTEM.
DETECTION/WARNING ONLY AND SHALL NOT BE USED TO RELEASE CLEAN AGENT
BUILDING FIRE ALARM SYSTEM. VESDA SYSTEM IS FOR EARLY SMOKE
NORMALLY OCCUPIED AREA. PROGRAM HIGH THRESHOLD ALARM TO ACTIVATE
PROGRAM LOW THRESHOLD ALARM (EARLY) TO SOUND SUPERVISORY ALARM IN
THROUGHOUT ARE PROTECTED BY CLEAN AGENT FIRE SUPPRESSION SYSTEM.
INSTALL AIR SAMPLING TYPE, EARLY WARNING SMOKE DETECTION SYSTEM (VESDA)
19
AREAS FOR WATER SUPPLY.
HAZARD GROUP 1. CONNECT TO EXISTING FIRE SPRINKLER PIPING IN ADJACENT
DESIGN FIRE SPRINKLERS TO PROTECT A HAZARD CLASSIFICATION OF ORDINARY
EXTEND FIRE SPRINKLER PROTECT INTO EXISTING BASEMENT ELECTRICAL ROOM.
7
7
7
7
7
7
7
7
7 7
77
77
77
7
7
7
7
8
8
8
8
8
3
4
CIRCUITING & GENERAL SYMBOL SCHEDULE
NOTE: ALL SYMBOLS MAY NOT BE USED
SYMBOL DESCRIPTION
KEYED NOTE REFERENCE1
BRANCH CIRCUIT HOME-RUN TO PANEL INDICATED
A-1,3,5
3/4"C.-6#12,1#12G
QTY & SIZE OF EQUIPMENT GROUND CONDUCTOR
QTY & SIZE OF NEUTRAL AND PHASE CONDUCTOR(S)
SIZE OF CONDUIT
A-1,3,5
3/4"C.-6#12,1#12G
PANEL AND CIRCUIT DESIGNATIONS
EQUIPMENT GROUNDING CONDUCTOR
TICK MARKS
NEUTRAL CONDUCTOR(S)
PHASE AND/OR SWITCH-LEG CONDUCTOR(S)
BRANCH CIRCUIT/FEEDER CONCEALED IN CEILING OR WALL
BRANCH CIRCUIT/FEEDER CONCEALED UNDERGROUND OR FLOOR
NEW EQUIPMENT, DEVICES, ETC.
EXISTING EQUIPMENT, DEVICES, ETC.
DEMOLITION EQUIPMENT, DEVICES, ETC.
DETAIL # / SHEET REFERENCE1 / ES101
*25,000A CALCULATED AVAILABLE FAULT CURRENT AT EQUIPMENT(SEE POWER RISER)
FIRE ALARM SYMBOL SCHEDULE
NOTE: ALL SYMBOLS MAY NOT BE USED
SYMBOL DESCRIPTION
DETECTOR SUBSCRIPTS
P PHOTOELECTRIC SMOKE DETECTOR D DUCT SMOKE DETECTOR
ID IN-DUCT SMOKE DETECTOR H HEAT DETECTOR
M MULTI-STATION SMOKE DETECTOR
(120V W/BATTERY BACKUP)
FIRE ALARM CONTROL & VOICE EVAC. PANEL (WALL MOUNTED, TOP AT 6'-0' AFF)
F
FACP
NOTIFICATION DEVICE EXTENDER PANEL. PROVIDE QTY AS REQUIRED BASED ON DEVICE
VOLTAGE DROP CALC'S PER NFPA 72 REQUIREMENTS. (WALL MOUNTED, TOP AT 5'-0' AFF)
REMOTE ANNUCIATOR PANEL (FLUSH MOUNTED IN WALL AT 5'-0' AFF)
NAC
RA
MANUAL PULL STATION (MOUNTING HEIGHT PER ADA & NFPA 72)
MAGNETIC DOOR HOLD OPEN
ADDRESSABLE CONTROL/RELAY MODULE
MM
CM
ADDRESSABLE MONITORING MODULE
FIRE ALARM FLOW SWITCH
FIRE ALARM TAMPER SWITCH
FS
TS
WALL MOUNTED FIRE SPEAKER ONLY
WALL MOUNTED FIRE ALARM STROBE ONLY
(CANDELA RATING AS REQUIRED)
#
ADDRESSABLE DETECTOR WITH BASE
CEILING MOUNTED FIRE ALARM STROBE ONLY
(CANDELA RATING AS REQUIRED)
WALL MOUNTED FIRE ALARM SPEAKER STROBE
(CANDELA RATING AS REQUIRED)
CEILING MOUNTED FIRE ALARM SPEAKER STROBE
(CANDELA RATING AS REQUIRED)
EXTERIOR 120V FIRE BELL, INSTALL NEXT TO FDC.
FIRE/SMOKE DAMPER; COORDINATE LOCATIONS WITH MECH. DRAWINGSSD
A. DO NOT INSTALL MORE THAN (10) NOTIFICATION APPLIANCES ON ANY SINGLE CLASS "A" SIGNAL CIRCUIT.
DO NOT EXCEED 400 FT. OF NO. 14 WIRE IN THE TOTAL LOOP.
B. NFPA ALLOWS NOTIFICATION APPLIANCES TO BE MOUNTED AT A HEIGHT RANGE BETWEEN 80" TO 96"
ABOVE FINISH FLOOR. THE PREFERRED HEIGHT IS 80". IF THIS CONFLICTS WITH OTHER TRADES OR ROOM
FURNISHINGS, LOCATE AS CLOSE TO 80" AS POSSIBLE, NOT EXCEEDING 96". ALL NOTIFICATION
APPLIANCES IN A COMMON ROOM OR LINE OF SIGHT SHALL BE LOCATED AT A COMMON HEIGHT.
C. MOUNT PULL STATIONS AT 46-48" A.F.F. TO THE OPERATING HANDLE TO MEET ADA REQUIREMENTS.
D. DO NOT CONNECT THE FIRE ALARM SYSTEM TO ANY DEVICE WHICH HAS A POWER HELD
CONTACTS.(FLOW, TAMPER, HOOD SYSTEM, DUCT DETECTOR, ETC..FALSE ALARM WILL OCCUR.
E. ELECTRICAL CONTRACTOR SHALL SUPPLY AND INSTALL CONDUCTOR QUANTITIES PER FIRE ALARM
SYSTEM SUPPLIER, AND AS PER NFPA AND NEC REQUIREMENTS.
F. DO NOT INSTALL ANY SMOKE OR HEAT DETECTORS WITHIN 3 FEET OF ANY AIR DIFFUSER.
G. DO NOT EXCEED 2500 FEET ON ANY ADDRESSABLE DEVICE RUN. DO NOT EXCEED 120 DEVICES ON ANY
ONE ADDRESSABLE DEVICE RUN.
H. ALL AIR HANDLING EQUIPMENT 2000 CFM OR MORE MUST BE SHUT DOWN UPON FIRE ALARM AS PER LIFE
SAFETY CODES.
I. ALL CLASS "B" INITIATING CIRCUITS WITH ADDRESSABLE DEVICES NEED EOLR. (END OF LINE RESISTORS).
J. IN CORRIDORS, NOTIFICATION APPLIANCES MUST BE LOCATED WITHIN 15' FROM ENDS OF CORRIDORS
AND A MAXIMUM OF 100' SPACING.
K. NOTIFICATION APPLIANCES TO BE SYNCHRONIZED TO PROVIDE A 3-3-3 TEMPORAL PATTERN.
L. ALL WIRING AND CONDUIT ROUTING TO BE AS DESCRIBED ON SUPPLIED SHOP DRAWINGS. FIRE ALARM
PLAN IS SHOWN FOR GENERAL LOCATION AND LAYOUT ONLY.
M. THE FIRE ALARM SYSTEM TO BE IN COMPLIANCE WITH ALL APPLICABLE LOCAL, STATE AND ADA
REQUIREMENTS.
N. ELECT. CONTR. TO CONNECT SPRINKLER SYSTEM TAMPER SWITCHES AND FLOW VALVES TO FIRE ALARM
SYSTEM AS REQUIRED. SEE FIRE SPRINKLER SYSTEM DRAWINGS FOR EXACT LOCATIONS AND
QUANTITIES.
GENERAL FIRE ALARM SYSTEM NOTES
CEILING MOUNTED FIRE ALARM SPEAKER ONLY
FIRE ALARM SMOKE DAMPERSD
LIGHTING SYMBOL SCHEDULE
NOTE: ALL SYMBOLS MAY NOT BE USED
SYMBOL DESCRIPTION
PARKING AREA POLE LIGHT, SINGLE OR DOUBLE HEAD AS INDICATED ON
DRAWINGS. REFER TO LIGHT POLE DETAIL FOR POLE INFORMATION.
2X4 FLUORESCENT OR LED FIXTURE
2X2 FLUORESCENT OR LED FIXTURE
SURFACE MOUNTED FLUORESCENT OR LED FIXTURE
STRIP FLUORESCENT OR LED FIXTURE
WALL MOUNTED FLUORESCENT OR LED FIXTURE
EXTERIOR WALL MOUNTED FIXTURE
ROUND RECESSED FIXTURE
SURFACE OR PENDANT FIXTURE
LIGHT FIXTURE SUBSCRIPTS
NL NIGHT-LIGHT(CONNECT TO UNSWITCHED LEG OF CIRCUIT)
EXIT SIGN, WALL OR CEILING MOUNTING AS REQUIRED (SINGLE OR DOUBLE FACE)
DIRECTIONAL CHEVRONS AS INDICATED; CONNECT TO UNSWITCHED LEG OF LIGHTING
CIRCUIT THAT IS IN THE SAME AREA AS THE EXIT SIGNS.
SHADED FIXTURE INDICATES AN EMERGENCY FIXTURE. PROVIDE WITH EMERG. BATTERY
PACK OR CONNECT TO EMERGENCY POWER SYSTEM (WHERE APPLICABLE). CONNECT
BATTERY PACK TO UNSWITCHED LEG OF LIGHTING CIRCUIT THAT SERVES THE SAME
AREA AS THE EMERGENCY FIXTURE. PROVIDE WITH TEST LIGHT AND SWITCH.
CEILING MOUNTED OCCUPANCY SENSOR, REFER TO OCCUPANCY SENSOR/SWITCH
SCHEDULE FOR SENSOR TYPE AND ADDITIONAL INFORMATION.
SWITCH MOUNTED OCCUPANCY SENSOR, LOW VOLTAGE SWITCHPOD OR DIMMER
SWITCH, REFER TO OCCUPANCY SENSOR/SWITCH SCHEDULE FOR TYPE AND
ADDITIONAL INFORMATION.
SINGLE-POLE SWITCH (SEE SUB-SCRIPTS BELOW FOR ADDITIONAL INFORMATION)
SWITCH SUBSCRIPTS
3 3-WAY SWITCH
4 4-WAY SWITCH
D DIMMER SWITCH (COMPATIBLE W/ LOAD & LTG TYPES)
F 7-DAY PROGRAMMABLE TIMER SWITCH
(INTERMATIC MODEL EI500WC SERIES)
P PILOT LIGHTED SWITCH
F1 LIGHT FIXTURE TYPE DESIGNATION
S
###
WALL OR CEILING MOUNTED EMERGENCY LIGHTING UNIT W/BATTERY PACK
CONNECT TO UNSWITCHED LEG OF LIGHTING CIRCUIT THAT IS IN THE SAME AREA AS
THE EMERGENCY LIGHT.
LV LOW-VOLTAGE SWITCH (PER DWG'S)
T THERMAL-OVERLOAD SWITCH
M MOMENTARY SWITCH CENTER OFF
WP WEATHERPROOF
2P DOUBLE POLE, SINGLE THROW SWITCH
GENERAL LIGHTING NOTES:
A. SYMBOLS SHOWN ABOVE MAY NOT REPRESENT ALL LIGHT FIXTURES USED ON PROJECT, REFER TO
LIGHT FIXTURE SCHEDULE FOR ACTUAL FIXTURE INFORMATION INCLUDING FIXTURE TYPE, LAMPING,
MOUNTING AND ETC.
B. JUNCTION BOXES FOR LIGHTING CIRCUITING ARE NOT SHOWN FOR CLARITY. THE E.C. IS RESPONSIBLE
FOR PROVIDING AND INSTALLING ALL JUNCTION BOXES REQUIRED FOR CIRCUITING OF ALL LIGHT
FIXTURES THAT ARE NOT LISTED FOR "THROUGH-BRANCH CIRCUIT WIRING".
C. IN GENERAL ALL SWITCH-LEG CONDUCTORS MAY NOT BE SHOWN ON DRAWINGS; E.C. SHALL PROVIDE
AND INSTALL CONDUCTORS AS REQUIRED TO ACHIEVE CONTROL SCHEMES INDICATED AND
DESCRIBED ON DRAWINGS. INCLUDING ALL 0 -10V DIMMING CONTROLS BETWEEN SWITCH AND
FIXTURES.
D. ALL BATTERY EXIT SIGNS AND EMERGENCY LIGHTING TO BE CONNECTED TO THE UNSWITCHED LEG OF
THE LIGHTING CIRCUIT IN THE AREA.
###
F
M
POW ER SYMBOL SCHEDULE
NOTE: ALL SYMBOLS MAY NOT BE USED
SYMBOL DESCRIPTION
ELECTRICAL SWITCHBOARD EQUIPMENT, (SEE POWER RISER AND PANEL SCHEDULES
FOR ADDITIONAL INFORMATION)
'MSB'
'T##'DRY-TYPE TRANSFORMER, (SEE POWER RISER FOR ADDITIONAL INFORMATION)
'LA'
ELECTRICAL PANELBOARD, (SEE POWER RISER AND PANEL SCHEDULES
FOR ADDITIONAL INFORMATION)
DISCONNECT SWITCH, SIZE/POLES/TYPE AS INDICATED
TYPES: 1=NEMA 1, 3R=NEMA 3R, 4X=NEMA 4X30A/3P/3R
FUSED DISCONNECT SWITCH, SIZE/POLES/TYPE AS INDICATED
TYPES: 1=NEMA 1, 3R=NEMA 3R, 4X=NEMA 4X30A/3P/3R
(30A FUSES)
COMBINATION STARTER & FUSED DISCONNECT SWITCH, SIZE/POLES/TYPE AS INDICATED.
TYPES: 1=NEMA 1, 3R=NEMA 3R, 4X=NEMA 4X
J
JUNCTION BOX
CR = CORD REEL; SEE DRAWINGS FOR INFORMATION
CD = CORD DROP; SEE DRAWINGS FOR INFORMATION
EQUIPMENT CONNECTION; COORDINATE CONNECTION WITH EQUIPMENT
PRIOR TO ROUGH-IN
MOTOR CONNECTION
POWER AND/OR DATA SERVICE POLE
FLOORBOX (SEE FLOORBOX SCHEDULE FOR ADDITIONAL INFORMATION)
PUSHBUTTON STATION
FB#
SPECIAL RECEPTACLE (COORDINATE NEMA TYPE WITH EQUIP.)
(REFER TO PANEL SCHEDULES FOR AMPS)
CEILING MOUNTED DUPLEX RECEPTACLE (COORDINATE PLACEMENT WITH
CEILING EQUIPMENT PRIOR TO ROUGH-IN)
DUPLEX RECEPTACLE, UL TAMPER-RESISTANT WHERE MOUNTED BELOW 5FT
GFCI-TYPE DUPLEX RECEPTACLE, UL TAMPER-RESISTANT WHERE MOUNTED BELOW 5FT
DOUBLE-DUPLEX RECEPTACLE, UL TAMPER-RESISTANT WHERE MOUNTED BELOW 5FT
GFCI-TYPE DOUBLE-DUPLEX RECEPTACLE, UL TAMPER-RESISTANT WHERE MOUNTED
BELOW 5FT.
RECEPTACLE AND EQUIPMENT SUBSCRIPTS
AC ABOVE COUNTER
W P W EATHERPROOF (UL LISTED
W EATHER-RESISTANT)
42"MOUNTING HEIGHT AFF OR AFG
IG ISOLATED GROUND
S SURGE-PROTECTION TYPE
REF REFRIGERATOR
W W ASHING MACHINE
D DRYER (30A-240V RATED RECPT.)
M MICROW AVE
HVAC THERMOSTAT OR SENSOR; PROVIDE & INSTALL BACKBOX,3/4" CONDUIT AND
CONDUCTORS TO ASSOCIATED HVAC UNIT. COORDINATE EXACT LOCATION & SIZE AND
NUMBER OF CONDUCTORS WITH M.C.
T SOR
30A/3P/3R
SIZE 1
(30A FUSES)
SMALL EXHAUST FAN CONNECTION
TV 120V RECEPT. FOR TV; VERIFY HEIGHT W ITH ARCH.
DRAW INGS & ELEVATIONS
USB 120V RECPT. W ITH USB CHARGING PORTS
EW C ELECTRIC W ATER COOLER; (SEE DETAIL. RECPT. SHALL
BE ACCESSIBLE, DO NOT MOUNT BEHIND HOUSING.)
DISP GARBAGE DISP. (UNDER SINK)
DW DISHW ASHER (COORDINATE W / MILLW ORK, INSTALL PER
NEC 422.16(B)(2)).
M/R MICROW AVE/RANGE HOOD (COORDINATE W / MILLWORK)
R ELECTRIC RANGE (50A-240V RATED RECPT.)
GENERAL SPECIAL SYSTEM NOTES:
A. ALL DEVICES SHOWN AT OR NEAR MILLWORK/CASEWORK SHALL BE COORDINATED WITH THE
ARCHITECTURAL ELEVATION DRAWINGS AND MILLWORK INSTALLER TO INSURE PROPER MOUNTING
HEIGHTS. CONTRACTOR SHALL ADJUST DEVICES AS NECESSARY IN ORDER TO POSITION DEVICES SUCH
THAT THEY WILL NOT FALL BEHIND MILLWORK, CABINETS OR BE DIRECTLY ABOVE SINKS OR MIDWAY
BETWEEN TILEWORK/WALL OR WAINSCOATING, ETC.
B. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO INSTALL A GFCI TYPE RECEPTACLE FOR ALL
RECPTACLES SHOWN IN TOILET RMS, BATHROOMS, KITCHENS/SERVING AREAS, ROOFTOP, OUTDOORS
OR WITHIN 6FT OF ANY SINK, BASIN, TUB OR FLOOR SINK AND ALL OTHER AREAS DEFINED BY THE NEC.
SPECIAL SYSTEMS SYMBOL SCHEDULE
NOTE: ALL SYMBOLS MAY NOT BE USED
SYMBOL DESCRIPTION
DATA OUTLET; _= # OF DATA CABLES, X=CONDUIT SIZE (SEE NOTES 1,2,3 BELOW)_D-X
TELEPHONE OUTLET; _= # OF TELEPHONE CABLES, X=CONDUIT SIZE
(SEE NOTES 1,2,3 BELOW)
_T-X
TELEPHONE/DATA OUTLET; _= # OF TELEPHONE/DATA CABLES, X=CONDUIT SIZE
(SEE NOTES 1,2,3 BELOW)
_T/_D-X
CEILING MOUNTED DATA OUTLET; _= # OF DATA CABLES, X=CONDUIT SIZE
(SEE NOTES 1,2,3,4 BELOW)
_D-X
A. COMMUNICATIONS CABLES SHALL HAVE BENDS NO GREATER THAN 90 DEG.
B. CONDUITS FOR COMMUNICATIONS CABLING SHALL HAVE A MAXIMUM BEND RADIUS NOT MORE THAN 10X
THE DIAMETER OF THE CONDUIT.
C. ALL COMMUNICATIONS CONDUITS SHALL BE TERMINATED WITH AN INSULATED NON-METALLIC BUSHING
AT BOTH ENDS.
D. COMMUNICATIONS CONDUITS SHALL HAVE NO MORE THAN (2) 90'S WITHOUT A PULLBOX. PULL BOXES
SHALL BE LOCATED IN ACCESSIBLE LOCATIONS AND SHALL BE SIZED AT LEASED 12X THE LARGEST
CONDUIT DIAMETER IN LENGTH AND MIN, 4" DEEP AND 8" WIDE.
E. IT SHALL BE THE RESPONSIBILITY OF THE E.C. TO INSURE THAT THE PATHWAY FOR THE DATA CABLING
DOES NOT CREATE CABLE LENGTHS TO EXCEEDS THE LENGTH OF 295FT FROM OUTLET TO PATCH
PANEL, THIS INCLUDES SERVICE LOOPS AND PATCH CORDS.
F. WHERE CABLE TRAY IS UTILIZED IN THE PROJECT. COMMUNICATION CONDUITS ENDING AT THE CABLE
TRAY SHALL EXTEND 1" OVER THE SIDE INTO THE TRAY.
GENERAL SPECIAL SYSTEM NOTES:
###
_D-X
SPECIAL SYSTEMS NOTES:
1. UTILIZE 4 11/16" DEEP BOX WITH REQUIRED MUDRING AND CONDUIT TO ABOVE NEAREST ACCESSIBLE
CEILING OR DATA RACK, TERMINATE WITH INSULATED THROAT BUSHING. PROVIDE QTY OF CABLES
INDICATED FROM OUTLET TO NEAREST TELE/DATA ROOM. SEE DWGS FOR ADDITIONAL INFORMATION.
UTILIZE J-HOOKS 3FT ON CENTER FOR SUPPORT OF CABLING WHERE CABLE TRAY IS NOT
INSTALLED/SPECIFIED.
2. CONDUIT SIZE ('X' FROM ABOVE); 2=1/2", 3=3/4", 4=1", 5=1-1/4", 6=1-1/2"
3. BLANK (NO LABEL) = 4-11/16" DEEP BOX WITH REQUIRED MUDRING AND 1" CONDUIT TO ABOVE NEAREST
ACCESSIBLE CEILING/CABLE TRAY, TERMINATE WITH INSULATED THROAT BUSHING, PROVIDE PULL
STRING. (UNLESS OTHERWISE NOTED).
4. IN LOCATIONS W/ DROP TILE CEILINGS DATA JACKS SHALL BE MOUNTED ABOVE TILE CEILING. IN
LOCATIONS W/ HARD CEILING DATA JACKS SHALL BE CUT INTO THE CEILING.
WALL/FLOOR ELECTRICAL PATHWAY SLEEVE;
INSTALL THROUGH WALL OR FLOOR AS INDICATED. SLEEVES SHALL BE ABOVE
ACCESSIBLE CEILINGS IN ACCESSIBLE LOCATION, FIELD VERIFY EXACT LOCATION TO
AVOID CONFLICT WITH OTHER TRADES AND UTILITIES. IF WALL/FLOOR IS NOT FIRE RATED
E.C. MAY UTILIZED EMT CONDUIT SLEEVES OF EQUAL SIZE. REFER TO ARCHITECTURAL
DRAWINGS FOR FIRE RATINGS.
(qty) = QUANTITY OF SLEEVES AT LOCATION
EP2 = 2" HILTI SPEED SLEEVE CP-653-BA
EP4 = 4" HILTI SPEED SLEEVE CP-653-BA
###
FB#
_D-X
ELECTRICAL FLOORBOX
REFER TO "ELECTRICAL FLOORBOX SCHEDULE" FOR INFORMATION.
_= # OF DATA CABLES, X=CONDUIT SIZE (SEE NOTES 1,2,3 BELOW)
TV AND/OR AV BOX; WITH POWER, DATA AND/OR AV CONNECTIVITY
### = BOX ID: REFER TO "ELECTRICAL AV/TV BOX SCHEDULE" FOR INFORMATION.
_= # OF DATA CABLES, X=CONDUIT SIZE (SEE NOTE #2 BELOW)
INSTALL CONDUIT (SIZE AS INDICATED) FROM BOX TO NEAREST ACCESSIBLE CEILING
SPACE W/ DATA CABLING/TERMINATIONS AS INDICATED ON DRAWINGS.
WALL
###
FLOOR
(qty)
(qty)
CRESTRON SCHEDULING TOUCH SCREEN AND ANGLED WALL MOUNT:
7in ROOM SCHEDULING TOUCH SCRREN, BLACK SMOOTH: TSW-770-LB-B-S 6511329
MULTISUFACE ANGLED WALL MOUNT KIT: TSW-770/1070-MSMK-ANG-B-S-6511786
PROVIDE AND INSTALL (1) CAT 6A CABLE FROM DEVICE TO NEAREST COMMUNICATIONS
ROOM.
INSTALL 1" CONDUIT FROM DEVICE TO NEAREST ACCESSIBLE CEILING.
SS
P
1PH
2/C
3/C
3P
3PH
3W
4W
AC
ADA
AFF
AFG
AIC
AL
A or
AMP
ANN
AP
ATS
AV
AWG
BFG
C
CATV
CB
CCTV
CKT
C
CP
CT
CU
DS
EA
E.C.
EM
EMT
ENT
EPO
EQUIP
EX
FA
FACP
FLA
FMC
GND
G.C.
GEN
GFI
GFP
HD
HID
HOA
HP
HPS
HV
HZ
IG
IMC
J-BOX
ABBREVIATIONS
SINGLE POLE
SINGLE-PHASE
TWO-CONDUCTOR
THREE-CONDUCTOR
THREE POLE
THREE-PHASE
THREE-WIRE
FOUR-WIRE
ABOVE COUNTER
AMERICANS WITH DISABILITIES ACT
ABOVE FINISHED FLOOR
ABOVE FINISHED GRADE
AMPERE INTERRUPTING CAPACITY
ALUMINUM
AMPERE
ANNUNCIATOR
ACCESS POINT
(WIRELESS DATA)
AUTOMATIC TRANSFER SWITCH
AUDIO VISUAL
AMERICAN WIRE GAGE
BELOW FINISHED GRADE
CEILING MOUNTED
CABLE TELEVISION
CIRCUIT BREAKER
CLOSED CIRCUIT TELEVISION
CIRCUIT
CONDUIT
CONTROL PANEL
CURRENT TRANSFORMER
COPPER
DISCONNECT SWITCH
EACH
ELECTRICAL CONTRACTOR
EMERGENCY
ELECTRICAL METALLIC TUBING
ELECTRICAL NONMETALLIC TUBING
EMERGENCY POWER OFF
EQUIPMENT
EXISTING
FIRE ALARM
FIRE ALARM CONTROL PANEL
FULL LOAD AMPS
FLEXIBLE METAL CONDUIT
GROUND
GENERAL CONTRACTOR
GENERATOR
GROUND FAULT CIRCUIT INTERRUPTER
GROUND FAULT PROTECTION
HEAVY DUTY
HIGH INTENSITY DISCHARGE
HAND-OFF-AUTOMATIC
HORSE POWER
HIGH PRESSURE SODIUM
HIGH VOLTAGE
HERTZ
ISOLATED GROUND
INTERMEDIATE METAL CONDUIT
JUNCTION BOX
V
KVA
kW
kWh
LED
LFMC
LFNC
LTG
LV
MAX
M.C.
MCA
MCB
MCC
MDP
MH
MIN
MLO
MOCP
NA
NC
NEC
NEMA
NFPA
NIC
NL
NO
NTS
OC
OH DR
OL
PB
P
PNL
PT
PTZ
QTY
RCP
RMC
RNC
SCA
SCBA
SF
SPD
SPEC
SWBD
SWGR
TL
TP
TTB
TV
TYP
UG
UPS
V
VA
V.I.F.
VFD
WAP
W/
W/O
WP
XFMR
KILOVOLT
KILOVOLT AMPERE
KILOWATT
KILOWATT HOUR
LIGHT EMITTING DIODE
LIQUID TIGHT FLEXIBLE METAL CONDUIT
LIQUID TIGHT FLEXIBLE NONMETALLIC
CONDUIT
LIGHTING
LOW VOLTAGE
MAXIMUM
MECH. CONTRACTOR
MINIMUM CIRCUIT AMPS
MAIN CIRCUIT BREAKER
MOTOR CONTROL CENTER
MAIN DISTRIBUTION PANEL
MANHOLE
MINIMUM
MAIN LUGS ONLY
MAXIMUM OVERCURRENT PROTECTION
NOT APPLICABLE
NORMALLY CLOSED
NATIONAL ELECTRICAL CODE
NATIONAL ELECTRICAL
MANUFACTURERS ASSOCIATION
NATIONAL FIRE PROTECTION
ASSOCIATION
NOT IN CONTRACT
NIGHT LIGHT
NORMALLY OPEN
NOT TO SCALE
ON CENTER
OVERHEAD DOOR
OVERLOAD
PUSHBUTTON
PHASE
PANEL
POTENTIAL TRANSFORMER
PAN/TILT/ZOOM
QUANTITY
REFLECTED CEILING PLAN
RIGID METAL CONDUIT
RIGID NONMETALLIC CONDUIT
SHORT CIRCUIT AMPS
STANDARD COLOR BY ARCHITECT
SQUARE FOOT (FEET)
SURGE PROTECTION DEVICE
SPECIFICATION
SWITCHBOARD
SWITCHGEAR
TWIST LOCK
TWISTED PAIR
TELEPHONE TERMINAL BOARD
TELEVISION
TYPICAL
UNDERGROUND
UNINTERRUPTIBLE POWER SUPPLY
VOLTS
VOLT AMPERE
VERIFY IN FIELD
VARIABLE FREQUENCY DRIVE
WIRELESS ACCESS POINT
WITH
WITHOUT
WEATHERPROOF
TRANSFORMER
A. E.C. SHALL REFER TO THE MECHANICAL DRAWINGS FOR EXACT LOCATIONS OF ALL MECHANICAL
EQUIPMENT AND ELECTRICAL CONNECTIONS.
B. E.C. SHALL PROVIDE MINIMUM WORKING CLEARANCE AS PER NEC BEFORE INSTALLING ANY ELECTRICAL
PANELS OR CABINETS. SEE ELECTRICAL EQUIPMENT CLEARANCE DETAIL.
C. INSTALL ALL LIGHT FIXTURES IN MECHANICAL ROOM AFTER THE MECHANICAL EQUIPMENT IS IN PLACE.
ADJUST AS NECESSARY. PROVIDE CHAIN SUSPENSION KITS AS REQUIRED.
D. REFER TO ARCHITECTURAL REFLECTED CEILING PLAN(S) FOR EXACT FIXTURE LOCATIONS, CEILING
TYPES, ETC.
E. E.C. SHALL PROVIDE ALL CONCRETE PADS AS REQUIRED FOR ALL ELECTRICAL EQUIPMENT.
F. CONFIRM EXACT LOCATIONS OF ALL TELEPHONE/DATA OUTLETS WITH OWNER PRIOR TO ROUGH-IN.
G. LOCATE SWITCHES, OUTLETS, ETC., SHOWN AT ROOM ENTRY DOORWAYS, AS CLOSE TO DOOR FRAME AS
POSSIBLE, SO AS NOT RO INTERFERE WITH ROOM CABINETS, ETC.
H. SUPPORT ALL LIGHT FIXTURES INDEPENDENT OF CEILING.
I. ELECTRICAL CONTRACTOR SHALL OBTAIN ALL APPLICABLE PERMITS FOR WORK AND PAY ASSOCIATED
FEES.
J. MAINTAIN 24" MIN. CLEARANCE FROM ALL COMMUNICATIONS CABLING AND ELECTRONIC BALLASTS.
K. UNLESS SPECIFICALLY INDICATED OTHERWISE, E.C. SHALL COORDINATE WITH ANY SPECIAL SYSTEMS
SUPPLIER/SHOP DRAWINGS; DENTAL, MEDICAL, KITCHEN, SPECIALIZED EQUIPMENT, ETC. FOR THE EXACT
ROUGH-IN REQUIREMENTS FOR THEIR EQUIPMENT. ALSO UNLESS INDICATED OTHERWISE, THE E.C. TO
BE RESPONSIBLE FOR FINAL ELECTRICAL CONNECTIONS TO ALL SPECIAL EQUIPMENT.
L. ALL CONDUIT/RACEWAY/CABLES TO BE CONCEALED IN WALLS OR ABOVE CEILINGS. IF ANY SURFACE
WORK IS NECESSARY, IT SHALL BE APPROVED BY THE ARCHITECT/ENGINEER PRIOR TO INSTALLATION.
M. ELECTRICAL CONTRACTOR SHALL VISIT THE SITE PRIOR TO BID AND THOROUGHLY INVESTIGATE THE
EXISTING CONDITIONS, AS THEY RELATE TO THE SCOPE OF WORK DESCRIBED. MAKE NECESSARY
PROVISIONS IN THE BASE BID TO ADEQUATELY ACCOMMODATE THESE CONDITIONS.
N. DATA CABLING SYSTEM PRE-INSTALLATION CONFERENCE:
1. E.C. SHALL SCHEDULE A MEETING A MINIMUM OF FIVE CALENDAR DAYS PRIOR TO BEGINNING DATA
CABLING INSTALLATION . ATTENDEES SHOULD INCLUDE OWNER’S REP., ENGINEER, GC, EC AND
CABLING SUB. REFER TO SECTION 26 6210(1.4)(E)FOR ADDITIONAL INFORMATION.
PROJECT GENERAL NOTES:
CONTACT:Jarom Taylor Nexant
(801) 746-1623
For Assistance
UTILITY LIGHTING REBATES & INCENTIVES:
IT SHALL BE THE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR TO PREPARE ALL REQUIRED
APPLICATIONS AND INFORMATION REQUIRED TO PROVIDE THE OWNER WITH THE MAXIMUM AMOUNT OF
REBATE DOLLARS FROM THE LOCAL UTILITY COMPANY. THE ELECTRICAL CONTRACTOR SHALL SUBMIT
VERIFICATION OF THE UTILITY COMPANY PRE-APPLICATION APPROVAL PRIOR TO ORDERING ANY MATERIALS.
TYPICAL DEVICE MOUNTING HEIGHTS:
GENERAL COORDINATION NOTE:
GENERAL DETAIL NOTES:
FINISH FLOOR
1' -6''
THERMOSTAT OR SENSOR
VERIFY WITH M.C. PRIOR TO
LIGHT SW.
(OR AS NOTED)
* 4' -0''
* 3' -6''
(OR AS NOTED)
RECEPTACLE
@ MILLWORK
BACKSPLASH
CAB. DIMENSIONS
PER ARCH. DETAIL
6"
CABINET
*E.C. SHALL COORDINATE ALL DEVICE
MOUNTING HGTS. AND EXACT LOCATION
WITH ARCHITECTURAL INTERIOR
ELEVATIONS REPORT CONFLICTS TO
ARCHITECT **PRIOR TO ROUGH-IN**
ROUGH-IN.
TYPICAL FOR ALL DEVICES
MOUNTED ABOVE COUNTER
(ie C.O.'S, DATA, PHONE etc.)
A.
B.
C.
D.
ALL MOUNTING HEIGHTS TYPICAL UNLESS
NOTED OTHERWISE.
COORDINATE OUTLET HEIGHTS WITH
ARCHITECTS MILLWORK DWGS. TO INSURE
THAT OUTLETS WILL NOT FALL BEHIND
CABINETS, BACKSPLASHES, OR INTERFERE
WITH WAINSCOTING, ETC.
ALL SWITCHES AND THERMOSTATS TO BE
MOUNTED AS CLOSE TO DOOR JAMS AS
POSSIBLE. COORDINATE ALL DEVICES WITH
ARCHITECTURAL PLANS AND DETAILS.
COORDINATE LIGHT SWITCH & OUTLET
HEIGHTS WITH ARCHITECTURAL
WAINSCOTING AND OR TILE WORK SO AS
NOT TO FALL MIDWAY IN THESE FINISHES.
FIRE
6' -8''
FIRE ALARM NOTIFICATION
DEVICE
FIRE
MANUAL PULL STATION
HANDLE SHALL BE
BETWEEN 42" & 48" AFF CABINET
RECEPT.
TELE/DATA
OUTLET
TV
OUTLET
ELECTRICAL EQUIP. CLEARANCE
ELECTRICAL
EQUIPMENT
NOTE #1
N O T E #4
NOTE#3
NOTE#2
NOTES:
1. THE MINIMUM HEADROOM OF WORKING SPACE SHALL BE 6 1/2FT.
2. THE WIDTH OF THE WORKING SPACE SHALL BE THE WIDTH OF THE EQUIPMENT OR 30", WHICHEVER IS
GREATER. THE PANEL DOOR SHALL OPEN AT LEAST 90 DEGREES.
3. ALL CIRCUIT BREAKERS, WHEN IN THIER HIGHEST POSITION, SHALL NOT BE MORE THAN 6FT 7 IN. ABOVE
THE FINISHED FLOOR.
4. 3FT CLEARANCE IF 0-150V TO GROUND, 3.5FT CLEARANCE IF 151-600V TO GROUND. 4FT IF EXPOSED LIVE
PARTS ON BOTH SIDES OF THE WORKING SPACE.
GENERAL NOTES:
A. ALL WORKING SPACE CLEARANCES ARE FROM THE FACE OF THE EQUIPMENT.
8270
STATEOFIDAHO
T
ODD P A Y N EREGISTER
EDRP
OFESSIONALEN
G
I
NE
E
R
1823 E. Center
Pocatello, Idaho 83201
tel (208) 232-4439
www.payneengineeringinc.com
Engineering Inc.
Consulting Engineers
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
P.E. #:2259
10-28-2022 EG000
ELECTRICAL
SYMBOLS &
DETAILS
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
BID SET
SECURITY & ACCESS CONTROL SYMBOL SCHEDULE
NOTE: ALL SYMBOLS MAY NOT BE USED
SYMBOL DESCRIPTION
CARD READER/KEYPAD LOCATION; UTILIZE 4SQ. BOX W/1-GANG MUDRING AND 1"C. W/
PULL STRING TO NEAREST ACCESSIBLE CEILING SPACE. CR
CONNECTION TO DOOR FRAME FOR ACCESS CONTROL. PROVIDE (1)1"C W/PULLSTRING
FROM DOOR TO NEAREST ACCESSSIBLE CEILING SPACE.
• E.C. IS RESPONSIBLE FOR ROUGH-IN FOR ACCESS CONTROL SYSTEM; E.C. SHALL COORDINATE ROUGH-
IN OF ACCESS CONTROL SYSTEM WITH OWNER PRIOR TO ROUGH-IN.
GENERAL SECURITY & ACCESS CONTROL NOTES:
F
REQUEST TO EXIT; UTILIZE 4SQ. BOX W/1-GANG MUDRING AND 1"C. W/ PULL STRING TO
NEAREST ACCESSIBLE CEILING SPACE. RX
SECURITY CAMERA: PROVIDE AND INSTALL A 4SQ. BOX W/ A 1" CHASE NIPPLE OR 1" C.,
TO NEAREST ACCESSIBLE CEILING SPACE. WITH (1) DATA DROP MOUNTED ABOVE
ACCESSIBLE CEILING BUT WITHIN 10FT OF CAMERA LOCATION, FOR CAMERA PATCH
CORD. CAMERA TO BE PROVIDED AND INSTALLED BY OWNER OVER BOX; COORDINATE
ROUGH-IN W/ OWNER CAMERA SPEC PRIOR TO ROUGH-IN.
CS
CALL STATIONS & SIGNAGE: AXIS A8004-VE; LOCATE (1) AT EACH ELEVATOR LANDING OR
AS REQUIRED BY LOCAL AHJ ON ALL FLOORS W/ CAT6A CABLE TO NEAREST IT ROOM
12" SQUARE, SEMI-RECESSED 60HZ. SYNCHRONOUS, 4-WIRE CLOCK WITH ALUMINUM
FRAME AND WHITE FACE.
SIMPLEX #2310-9271 W/ SIMPLEX #2975-9038 RECESSED BACKBOX. (UNO)
CLOCK (AMERICAN TIME & STANDARD #ASQMSTR-002XE)
PROVIDE AND INSTALL A 3/4"C., 4#12 THHN (BLK,WHT,RED,GRN) FROM EACH CLOCK BACK
TO NEAREST MASTER CLOCK OR SYSTEM J-BOX. PROVIDE ALL REQUIRED CONNECTIONS
BETWEEN MASTER CLOCK AND CLOCKS FOR A COMPLETE AND FUNCTIONAL SYSTEM.
PATRON COUNTING SYSTEM SCHEDULE
SYMBOL DESCRIPTION
PROVIDE ALL EQUIPMENT, MATERIALS, AND CABLE NECESSARY FOR INSTALLATION,
COMMISSIONING AND PROGRAMMING OF A COMPLETE AND OPERABLE P.O.E. BASED, 3D
VIDEO PATRON COUNTING SYSTEM AS MANUFACTURED BY SENSOURCE.
EACH VIDEO SENSOR SHALL BE CONNECT TO NEAREST CEILING P.O.E. DATA PORT.
VIDEO SENSORS SHALL BE INSTALLED AND COMMISSIONED BY SENSOURCE CERTIFIED
TECHNICIAN.
PROVIDE FACTORY 5 YEAR WARRANTY AND 1 YEAR CLOUD DATA HOSTING.
PROVIDE ON SITE FACTORY SUPPORTED TRAINING FOR OWNER.
FOR ADDITIONAL INFORMATION AND QUOTATION CONTACT:
SENSOURCE
CHRIS LISTORTI
CLISTORTI@SENSOURCEINC.COM
PC
nPP16-D
NHN
CAT5e
BLK/ORN
WHT
BLU
BLU
VIO
GRY
GRN
0-10V
LED DRIVER
IN FIXTURE
TO ADDITIONAL
LIGHT FIXTURES
S
R
120V PW R
0-10V DIMMING
CAT5e CABLE
nLIGHT CEILING
SENSOR, TYPE
& QTY PER
DRAWINGS
120V CIRUIT
SEE DW G'S
RELAY/PWR
PACK, SEE DETAIL
LIGHT FIXTURE
QTY & TYPE
PER DW G'S
DETAIL GENERAL NOTES:
A. THIS DIAGRAM IS SCHEMATIC IN NATURE; REFER TO LTG DRAWINGS nLIGHT LIGHTING
CONTROL SCHEDULE FOR ADDITIONAL INFORMATION, QTY AND LOCATION OF SENSORS,
SWITCHES, FIXTURES, ETC.
B. E.C. SHALL MEET WITH OW NERS REP. AND PROGRAM DEVICE OPERATION AND CONTROL
ZONES OF LIGHTING TO OW NER'S SATISFACTION PRIOR TO FINAL PUNCHOUT OF
PROJECT.
AV
ROOMS WITH A/V CABINETS,
PROVIDE nLIGHT nIO-X KIT,
LOCATED IN CABINET & SUPPLY
DB9F ADAPTERS AS REQUIRED.
REFER TO DWG'S
(D/EG100)
ON/OFF
ON/OFF
GRAY DEVICE
W/ STAINLESS STEEL
COVERPLATE
nLIGHT
SW ITCH(ES)
TYPE & QTY PER
DWG'S
ON
OFF
GRAY DEVICE
W/ STAINLESS STEEL
COVERPLATE
n###
n###
nLIGHT
SWITCH(ES)
TYPE & QTY PER
DWG'S
n###
S
120V PW R
CAT5e CABLE
LIGHT FIXTURE
QTY & TYPE
PER DWG'S
120V CIRUIT
SEE DWG'S
ON
OFF
GRAY DEVICE
W/ STAINLESS STEEL
COVERPLATE
AV
ROOMS WITH A/V CABINETS,
PROVIDE nLIGHT nIO-X KIT,
LOCATED IN CABINET & SUPPLY
DB9F ADAPTERS AS REQUIRED.
REFER TO DWG'S
nLIGHT
SWITCH(ES)
TYPE & QTY PER
DWG'S
ON/OFF
ON/OFF
GRAY DEVICE
W/ STAINLESS STEEL
COVERPLATE
n###
n###
DETAIL GENERAL NOTES:
A. THIS DIAGRAM IS SCHEMATIC IN NATURE; REFER TO LTG DRAWINGS nLIGHT LIGHTING
CONTROL SCHEDULE FOR ADDITIONAL INFORMATION, QTY AND LOCATION OF SENSORS,
SWITCHES, FIXTURES, ETC.
B. E.C. SHALL MEET WITH OWNERS REP. AND PROGRAM DEVICE OPERATION AND CONTROL
ZONES OF LIGHTING TO OW NER'S SATISFACTION PRIOR TO FINAL PUNCHOUT OF
PROJECT.
nLIGHT
SWITCH(ES)
TYPE & QTY PER
DWG'S
nLIGHT CEILING
SENSOR, TYPE
& QTY PER
DRAW INGS
n###FIRE ALARM SYSTEM NOTES:
• FIRE ALARM SYSTEM CONDUIT ROUTING SHALL BE
DETERMINED BY THE ELECTRICAL CONTRACTOR AND
FIRE ALARM CONTRACTOR TO MEET THE SPECIFIED
DESIGN CRITERIA.
• ALL FIRE ALARM SYSTEM CABLING SHALL BE RUN IN
CONDUIT OR WIREMOLD WHERE SURFACE MOUNTED
RACEWAY MUST BE INSTALLED IN EXISTING FINISHED
SPACES.
• CONTRACTOR SHALL PROVIDE ADDITIONAL POWER
SUPPLY AND AMPLIFIER PANELS WHERE REQUIRED TO
MEET THE SPECIFIED DESIGN CRITERIA.
• CONTRACTOR SHALL SUBMIT SHOP DRAWINGS AND
REQUIRED CALCULATIONS TO THE AUTHORITY HAVING
JURISDICTION AND OBTAIN A WRITTEN LETTER OF
ACCEPTANCE OF THE PROPOSED SYSTEM. INCLUDE
LETTER WITH SHOP DRAWING SUBMITTAL TO ENGINEER.
• E.C. SHALL PROVIDE AND INSTALL CELLULAR ALARM
COMMUNICATOR FOR FIRE ALARM SYSTEM MONITORING,
TELGUARD TG-7FS LTE OR EQUAL. SYSTEM SHALL BE UL
LISTED AND COMPLIANT WITH NFPA 72 REQUIREMENTS.
NEW
FIRE ALARM &
VOICE EVAC.
PANEL(S)
TYPICAL NOTIFICATION
APPLIANCE CIRCUIT
(STROBES)
TYPICAL INITIATING
DEVICE CIRCUIT
(SLC LOOP)
CLASS B
H P FSTSD MM
CMRM
TYPICAL NOTIFICATION
APPLIANCE CIRCUIT
(SPEAKERS)
RA REMOTE ANNUNCIATOR(S) WITH
MICROPHONE
(VERIFY LOCATION WITH LOCAL AHJ)
D
CM
120V CIRCUIT
DOOR HOLDER
CIRCUIT
MECH. EQUIP.
FAN SHUT DOWN
ADDITIONAL NAC &
AMPLIFIER PANELS
AS NEEDED, INSTALL
IN ELEC. ROOMS
UL 864
CELLULAR
ALARM
COMM.
TO ADDITIONAL
ADDRESSABLE
DEVICES
LOAD
ADDITIONAL 1-POLE
LINE VOLTAGE OCC.
SENSOR(S)
AS PER DRAWINGS
1-POLE LINE
VOLTAGE
OCC. SENSOR PER
DRAWINGS
SWITCH PER
DRAWINGS
ROOM LTG
120/277V
CIRCUIT
PER
DRAWINGS
BLACK
BLUE
WHITE
BLACK
BLUE
WHITE
TEE BAR
GRID
POW ER SUPPLY CONDUIT FOR
CEILING OR WALL "J" BOX.
SUPPORT WIRE BY ELECTRICAL
CONTRACTOR INDEPENDENT OF CEILING
SYSTEM. (TYPICAL)
ACOUSTIC
CEILING
TILE
SUPPORT
CLIPS
ALL SIDES
8270
STATEOFIDAHO
T
ODD P A Y N EREGISTER
EDRP
OFESSIONALEN
G
I
NE
E
R
1823 E. Center
Pocatello, Idaho 83201
tel (208) 232-4439
www.payneengineeringinc.com
Engineering Inc.
Consulting Engineers
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
P.E. #:2259
10-28-2022 EG100
ELECTRICAL
DETAILS
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
BID SET
SCALE: NONEDnLIGHT POWER/RELAY PACK DETAIL
SCALE: NONECnLIGHT CONTROL DIAGRAM W/NON-nLIGHT FIXTURES
SCALE: NONEBnLIGHT CONTROL DIAGRAM W/ nLIGHT FIXTURES
SCALE: NONEAFIRE ALARM RISER DIAGRAM (VOICE EVAC.)
SCALE: 1/8" = 1'-0"E LINE-VOLTAGE, 1-POLE CEILING OCC. SENSORS W/ OVERRIDE SWITCH
SCALE: 1/8" = 1'-0"F RECESSED LIGHT FIXTURE DETAIL
F16
?
?
1
1LB-16
4'-0 MIN.
6"
25'-0±
UNDISTURBED OR
COMPACTED EARTH
POLE BASE WITH 4 #5 RE-BARS
AND #3 TIES @ 12" O.C. 3000 PSI
MIN.
CONDUIT (PVC) 24" MIN.
DEPTH. REFER TO PLAN.
ANCHOR BOLTS TO SUIT
POLE
FINISHED GRADE
POLE BASE COVER
POLE LIGHT-SEE SCHEDULE
24" DIA.
GFI, WP RECEPTACLE
(WHERE INDICATED ON DWG'S)
HAND
HOLE
TOP EDGE OF POLE BASE
SHALL BE CHAMFERED
8270
STATEOFIDAHO
T
ODD P A Y N EREGISTER
EDRP
OFESSIONALEN
G
I
NE
E
R
1823 E. Center
Pocatello, Idaho 83201
tel (208) 232-4439
www.payneengineeringinc.com
Engineering Inc.
Consulting Engineers
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
P.E. #:2259
10-28-2022 ES100
ELECTRICAL
SITE PLAN -
WEST
ENTRANCE
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
BID SET
KEY NOTES:#
1 CIRCUIT NEW POLE LIGHT TO EXITING POLE LIGHT
CIRCUIT . UTILIZE EXISTING CONTROLS.
SCALE: 1" = 10'-0"1 ELECTRICAL SITE PLAN
NORTH
20'10'0"SCALE: NONEAPOLE LIGHT DETAIL
J
G
J
E
C
2 3 4 5 6
1
8270
STATEOFIDAHO
T
ODD P A Y N EREGISTER
EDRP
OFESSIONALEN
G
I
NE
E
R
1823 E. Center
Pocatello, Idaho 83201
tel (208) 232-4439
www.payneengineeringinc.com
Engineering Inc.
Consulting Engineers
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
P.E. #:2259
10-28-2022 ED100
EXISTING
LIGHTING
PLAN LEVEL
0
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
BID SET
1. ALL CIRCUIT BREAKERS FROM DEMOLITIONED PANELS
SHALL BE BOXED UP AND DELIVERED TO THE OWNER, TO AN
ON CAMPUS LOCATION AS DIRECTED BY OWNER.
2. ALL CONDUCTORS BEING REMOVED THAT ARE RATED 100
AMPS AND ABOVE SHALL BE DELIVERED TO THE CAMPUS
RECYCLING CENTER.
3. ALL TRANSFORMERS BEING REMOVED SHALL BE DELIVERED
TO THE OWNER, TO AN ON CAMPUS LOCATION AS DIRECTED
BY OWNER.
4. UNLESS INDICATED ABOVE, ALL OTHER MATERIAL SHALL BE
DISPOSED OF LEGALLY BY THE CONTRACTOR.
5. CAREFULLY REMOVE ALL EXISTING FIRE ALARM DEVICES IN
CONFLICT WITH REMODEL, TO BE UTILIZED WHERE
POSSIBLE IN NEW SYSTEM. SEE NEW FIRE ALARM PLANS.
6. E.C. SHALL REMOVE ALL EXISTING DATA CABLING IN THE
BUILDING. PROTECT AND MAINTAIN EXISTING FIBER OPTIC
BACKBONE CABLING AND RACEWAY WHEREVER POSSIBLE.
PROVIDE AND INSTALL A COMPLETE AND NEW HORIZONTAL
CABLING PLANT TO ACCOMMODATED REMODEL.
SPECIAL DEMOLITION NOTES:
A. IN GENERAL, UNLESS SPECIFICALLY INDICATED OTHERWISE,
ALL EXISTING ELECTRICAL EQUIPMENT SHOWN SHALL BE
REMOVED. WHEN EXISTING SWITCH AND OR OUTLET BOXES
FALL WITHIN OR NEAR NEW OUTLETS/SWITCHES SHOWN IN
NEW DESIGN, THE E.C. MAY UTILIZE THE EXISTING ROUGH-IN,
ETC. IN LIEU OF INSTALLING NEW. CONTRACTOR MUST
HOWEVER MAINTAIN ELECTRICAL CONTINUITY TO
DOWNSTREAM EQUIPMENT TO REMAIN. ELECTRICAL
CONTRACTOR MAY UTILIZE ANY EXISTING RACEWAYS
WHERE THEY ARE COMPATIBLE WITH NEW DESIGN/SYSTEMS.
PROVIDE ALL NEW DEVICES AND COVERS.
B. ALL EXISTING ELECTRICAL MAY NOT APPEAR ON THESE
PLANS, HOWEVER THE ABOVE INFORMATION APPLIES.
C. PROVIDE AND INSTALL BLANK COVERS ON ALL UNUSED
SWITCH/OUTLET/J-BOXES WHERE REQUIRED.
D. ALL WALL DEVICES THAT ARE EXISTING TO REMAIN, SHALL
BE ADAPTED TO NEW WALL COVERINGS, REFER TO
ARCHITECTURAL DRAWINGS FOR EXACT WALL LOCATIONS,
THICKNESS, ETC.
E. PRIOR TO THE START OF ANY DEMOLITION WORK,
DISCONNECTING ANY POWER AND OR TELE/DATA SYSTEMS,
THE CONTRACTOR SHALL COORDINATE DOWN-TIME WITH
THE OWNER.
F. REFER TO ARCHITECTURAL PLANS FOR EXTENT OF
DEMOLITION, DETAILS, ETC.
G. REMOVE OR RELOCATE ELECTRICAL AS NECESSARY FOR
NEW WORK.
H. WHERE EXISTING CIRCUITS ARE TO BE RE-USED, EXTEND AS
NECESSARY. MAINTAIN ELECTRICAL CONTINUITY TO
DOWNSTREAM EQUIPMENT TO REMAIN.
I. EXISTING SHOWN TO REMAIN, MAY NEED TO BE REMOVED
AND RE-INSTALLED ONLY AS NECESSARY FOR EXTENDING
OR MODIFICATION OF EXISTING CIRCUITS OR WIRING.
J. REFER TO MECHANICAL PLANS FOR EXTENT OF MECHANICAL
EQUIPMENT TO BE REMOVED OR RELOCATED.
K. REMOVE ALL UNUSED EQUIPMENT WIRING, CONDUIT AND
BOXES IN ALL AREAS. ABANDON ONLY IN CONCEALED
AREAS.
L. CONTRACTOR MY UTILIZE ANY EXISTING CONDUIT WHERE
COMPATIBLE WITH NEW DESIGN, AND IF IN GOOD CONDITION
AND COMPLIES WITH SPECIFICATIONS.
M. WHEN ANY MODIFICATIONS ARE MADE TO ANY EXISTING
ELECTRICAL PANEL TO REMAIN, CONTRACTOR TO PROVIDE
NEW TYPE WRITTEN INDEX TO REFLECT ALL NEW AND
EXISTING LOADS.
N. REMOVE ALL EQUIPMENT, RACEWAYS, CABLES,ETC. NOT
USED IN FINISHED AREAS.
O. UNLESS OTHERWISE NOTED DISCONNECT AND REMOVE ALL
EXISTING LIGHTING. REMOVE ALL ASSOCIATED CIRCUITING
AND CONTROLS.
GENERAL NOTES:
KEY NOTES:#
1 EXISTING PHOTO-CELL FOR OUTSIDE LIGHTING CONTROL TO
REMAIN. EXACT LOCATION TO BE FIELD VERIFIED. PROTECT
AND MAINTAIN EXISTING WIRE AND CABLE TO DEVICE.
NORTH
16'8'0"SCALE: 1/8" = 1'-0"1 LEVEL 0 EXISTING LIGHITNG PLAN
1
G
J
L
M
N
P
Q
E
C
2 3 4 5 61.5
EE201
2
1
1
1
2 2 2 2 2 8270
STATEOFIDAHO
T
ODD P A Y N EREGISTER
EDRP
OFESSIONALEN
G
I
NE
E
R
1823 E. Center
Pocatello, Idaho 83201
tel (208) 232-4439
www.payneengineeringinc.com
Engineering Inc.
Consulting Engineers
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
P.E. #:2259
10-28-2022 ED101
EXISTING
LIGHTING
PLAN LEVEL
1 AREA A
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
BID SET
1. ALL CIRCUIT BREAKERS FROM DEMOLITIONED PANELS
SHALL BE BOXED UP AND DELIVERED TO THE OWNER, TO AN
ON CAMPUS LOCATION AS DIRECTED BY OWNER.
2. ALL CONDUCTORS BEING REMOVED THAT ARE RATED 100
AMPS AND ABOVE SHALL BE DELIVERED TO THE CAMPUS
RECYCLING CENTER.
3. ALL TRANSFORMERS BEING REMOVED SHALL BE DELIVERED
TO THE OWNER, TO AN ON CAMPUS LOCATION AS DIRECTED
BY OWNER.
4. UNLESS INDICATED ABOVE, ALL OTHER MATERIAL SHALL BE
DISPOSED OF LEGALLY BY THE CONTRACTOR.
5. CAREFULLY REMOVE ALL EXISTING FIRE ALARM DEVICES IN
CONFLICT WITH REMODEL, TO BE UTILIZED WHERE
POSSIBLE IN NEW SYSTEM. SEE NEW FIRE ALARM PLANS.
6. E.C. SHALL REMOVE ALL EXISTING DATA CABLING IN THE
BUILDING. PROTECT AND MAINTAIN EXISTING FIBER OPTIC
BACKBONE CABLING AND RACEWAY WHEREVER POSSIBLE.
PROVIDE AND INSTALL A COMPLETE AND NEW HORIZONTAL
CABLING PLANT TO ACCOMMODATED REMODEL.
SPECIAL DEMOLITION NOTES:
A. IN GENERAL, UNLESS SPECIFICALLY INDICATED OTHERWISE,
ALL EXISTING ELECTRICAL EQUIPMENT SHOWN SHALL BE
REMOVED. WHEN EXISTING SWITCH AND OR OUTLET BOXES
FALL WITHIN OR NEAR NEW OUTLETS/SWITCHES SHOWN IN
NEW DESIGN, THE E.C. MAY UTILIZE THE EXISTING ROUGH-IN,
ETC. IN LIEU OF INSTALLING NEW. CONTRACTOR MUST
HOWEVER MAINTAIN ELECTRICAL CONTINUITY TO
DOWNSTREAM EQUIPMENT TO REMAIN. ELECTRICAL
CONTRACTOR MAY UTILIZE ANY EXISTING RACEWAYS
WHERE THEY ARE COMPATIBLE WITH NEW DESIGN/SYSTEMS.
PROVIDE ALL NEW DEVICES AND COVERS.
B. ALL EXISTING ELECTRICAL MAY NOT APPEAR ON THESE
PLANS, HOWEVER THE ABOVE INFORMATION APPLIES.
C. PROVIDE AND INSTALL BLANK COVERS ON ALL UNUSED
SWITCH/OUTLET/J-BOXES WHERE REQUIRED.
D. ALL WALL DEVICES THAT ARE EXISTING TO REMAIN, SHALL
BE ADAPTED TO NEW WALL COVERINGS, REFER TO
ARCHITECTURAL DRAWINGS FOR EXACT WALL LOCATIONS,
THICKNESS, ETC.
E. PRIOR TO THE START OF ANY DEMOLITION WORK,
DISCONNECTING ANY POWER AND OR TELE/DATA SYSTEMS,
THE CONTRACTOR SHALL COORDINATE DOWN-TIME WITH
THE OWNER.
F. REFER TO ARCHITECTURAL PLANS FOR EXTENT OF
DEMOLITION, DETAILS, ETC.
G. REMOVE OR RELOCATE ELECTRICAL AS NECESSARY FOR
NEW WORK.
H. WHERE EXISTING CIRCUITS ARE TO BE RE-USED, EXTEND AS
NECESSARY. MAINTAIN ELECTRICAL CONTINUITY TO
DOWNSTREAM EQUIPMENT TO REMAIN.
I. EXISTING SHOWN TO REMAIN, MAY NEED TO BE REMOVED
AND RE-INSTALLED ONLY AS NECESSARY FOR EXTENDING
OR MODIFICATION OF EXISTING CIRCUITS OR WIRING.
J. REFER TO MECHANICAL PLANS FOR EXTENT OF MECHANICAL
EQUIPMENT TO BE REMOVED OR RELOCATED.
K. REMOVE ALL UNUSED EQUIPMENT WIRING, CONDUIT AND
BOXES IN ALL AREAS. ABANDON ONLY IN CONCEALED
AREAS.
L. CONTRACTOR MY UTILIZE ANY EXISTING CONDUIT WHERE
COMPATIBLE WITH NEW DESIGN, AND IF IN GOOD CONDITION
AND COMPLIES WITH SPECIFICATIONS.
M. WHEN ANY MODIFICATIONS ARE MADE TO ANY EXISTING
ELECTRICAL PANEL TO REMAIN, CONTRACTOR TO PROVIDE
NEW TYPE WRITTEN INDEX TO REFLECT ALL NEW AND
EXISTING LOADS.
N. REMOVE ALL EQUIPMENT, RACEWAYS, CABLES,ETC. NOT
USED IN FINISHED AREAS.
O. UNLESS OTHERWISE NOTED DISCONNECT AND REMOVE ALL
EXISTING LIGHTING. REMOVE ALL ASSOCIATED CIRCUITING
AND CONTROLS.
GENERAL NOTES:
KEY NOTES:#
1 EXISTING EXIT LIGHT TO REMAIN. PROTECT AND/OR
RE-ESTABLISH ELECTRICAL SERVICE.
2 EXISTING LIGHT TO REMAIN. PROTECT DURING
CONSTRUCTION, CIRCUIT AND CONTROL AS SHOWN IN NEW
DESIGN.
NORTH
16'8'0"SCALE: 1/8" = 1'-0"1 LEVEL 1 EXISTING LIGHITNG PLAN AREA A
KEY PLAN
A
B
16151413121110987
K
H
F
D
B
A
'EE''1P''MCC1'
'M'
1
2
2
3
8270
STATEOFIDAHO
T
ODD P A Y N EREGISTER
EDRP
OFESSIONALEN
G
I
NE
E
R
1823 E. Center
Pocatello, Idaho 83201
tel (208) 232-4439
www.payneengineeringinc.com
Engineering Inc.
Consulting Engineers
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
P.E. #:2259
10-28-2022 ED102
EXISTING
LIGHTING
PLAN LEVEL
1 AREA B
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
BID SET
1. ALL CIRCUIT BREAKERS FROM DEMOLITIONED PANELS
SHALL BE BOXED UP AND DELIVERED TO THE OWNER, TO AN
ON CAMPUS LOCATION AS DIRECTED BY OWNER.
2. ALL CONDUCTORS BEING REMOVED THAT ARE RATED 100
AMPS AND ABOVE SHALL BE DELIVERED TO THE CAMPUS
RECYCLING CENTER.
3. ALL TRANSFORMERS BEING REMOVED SHALL BE DELIVERED
TO THE OWNER, TO AN ON CAMPUS LOCATION AS DIRECTED
BY OWNER.
4. UNLESS INDICATED ABOVE, ALL OTHER MATERIAL SHALL BE
DISPOSED OF LEGALLY BY THE CONTRACTOR.
5. CAREFULLY REMOVE ALL EXISTING FIRE ALARM DEVICES IN
CONFLICT WITH REMODEL, TO BE UTILIZED WHERE
POSSIBLE IN NEW SYSTEM. SEE NEW FIRE ALARM PLANS.
6. E.C. SHALL REMOVE ALL EXISTING DATA CABLING IN THE
BUILDING. PROTECT AND MAINTAIN EXISTING FIBER OPTIC
BACKBONE CABLING AND RACEWAY WHEREVER POSSIBLE.
PROVIDE AND INSTALL A COMPLETE AND NEW HORIZONTAL
CABLING PLANT TO ACCOMMODATED REMODEL.
SPECIAL DEMOLITION NOTES:
A. IN GENERAL, UNLESS SPECIFICALLY INDICATED OTHERWISE,
ALL EXISTING ELECTRICAL EQUIPMENT SHOWN SHALL BE
REMOVED. WHEN EXISTING SWITCH AND OR OUTLET BOXES
FALL WITHIN OR NEAR NEW OUTLETS/SWITCHES SHOWN IN
NEW DESIGN, THE E.C. MAY UTILIZE THE EXISTING ROUGH-IN,
ETC. IN LIEU OF INSTALLING NEW. CONTRACTOR MUST
HOWEVER MAINTAIN ELECTRICAL CONTINUITY TO
DOWNSTREAM EQUIPMENT TO REMAIN. ELECTRICAL
CONTRACTOR MAY UTILIZE ANY EXISTING RACEWAYS
WHERE THEY ARE COMPATIBLE WITH NEW DESIGN/SYSTEMS.
PROVIDE ALL NEW DEVICES AND COVERS.
B. ALL EXISTING ELECTRICAL MAY NOT APPEAR ON THESE
PLANS, HOWEVER THE ABOVE INFORMATION APPLIES.
C. PROVIDE AND INSTALL BLANK COVERS ON ALL UNUSED
SWITCH/OUTLET/J-BOXES WHERE REQUIRED.
D. ALL WALL DEVICES THAT ARE EXISTING TO REMAIN, SHALL
BE ADAPTED TO NEW WALL COVERINGS, REFER TO
ARCHITECTURAL DRAWINGS FOR EXACT WALL LOCATIONS,
THICKNESS, ETC.
E. PRIOR TO THE START OF ANY DEMOLITION WORK,
DISCONNECTING ANY POWER AND OR TELE/DATA SYSTEMS,
THE CONTRACTOR SHALL COORDINATE DOWN-TIME WITH
THE OWNER.
F. REFER TO ARCHITECTURAL PLANS FOR EXTENT OF
DEMOLITION, DETAILS, ETC.
G. REMOVE OR RELOCATE ELECTRICAL AS NECESSARY FOR
NEW WORK.
H. WHERE EXISTING CIRCUITS ARE TO BE RE-USED, EXTEND AS
NECESSARY. MAINTAIN ELECTRICAL CONTINUITY TO
DOWNSTREAM EQUIPMENT TO REMAIN.
I. EXISTING SHOWN TO REMAIN, MAY NEED TO BE REMOVED
AND RE-INSTALLED ONLY AS NECESSARY FOR EXTENDING
OR MODIFICATION OF EXISTING CIRCUITS OR WIRING.
J. REFER TO MECHANICAL PLANS FOR EXTENT OF MECHANICAL
EQUIPMENT TO BE REMOVED OR RELOCATED.
K. REMOVE ALL UNUSED EQUIPMENT WIRING, CONDUIT AND
BOXES IN ALL AREAS. ABANDON ONLY IN CONCEALED
AREAS.
L. CONTRACTOR MY UTILIZE ANY EXISTING CONDUIT WHERE
COMPATIBLE WITH NEW DESIGN, AND IF IN GOOD CONDITION
AND COMPLIES WITH SPECIFICATIONS.
M. WHEN ANY MODIFICATIONS ARE MADE TO ANY EXISTING
ELECTRICAL PANEL TO REMAIN, CONTRACTOR TO PROVIDE
NEW TYPE WRITTEN INDEX TO REFLECT ALL NEW AND
EXISTING LOADS.
N. REMOVE ALL EQUIPMENT, RACEWAYS, CABLES,ETC. NOT
USED IN FINISHED AREAS.
O. UNLESS OTHERWISE NOTED DISCONNECT AND REMOVE ALL
EXISTING LIGHTING. REMOVE ALL ASSOCIATED CIRCUITING
AND CONTROLS.
GENERAL NOTES:
KEY NOTES:#
1 EXISTING LIGHTING IN ROOM TO REMAIN. MAINTAIN AND/OR
RE-ESTABLISH EXISTING FEEDER AND CONTROLS.
2 EXISTING EXIT LIGHT TO REMAIN. PROTECT AND/OR
RE-ESTABLISH ELECTRICAL SERVICE.
3 EXISTING LIGHT TO REMAIN. PROTECT DURING
CONSTRUCTION, CIRCUIT AND CONTROL AS SHOWN IN NEW
DESIGN.
NORTH
16'8'0"SCALE: 1/8" = 1'-0"1 LEVEL 1 EXISTING LIGHITNG PLAN AREA B
KEY PLAN
A
B
1
G
J
L
M
N
P
Q
E
C
2 3 4 5 61.5
1
8270
STATEOFIDAHO
T
ODD P A Y N EREGISTER
EDRP
OFESSIONALEN
G
I
NE
E
R
1823 E. Center
Pocatello, Idaho 83201
tel (208) 232-4439
www.payneengineeringinc.com
Engineering Inc.
Consulting Engineers
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
P.E. #:2259
10-28-2022 ED103
EXISTING
LIGHTING
PLAN LEVEL
2 AREA A
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
BID SET
1. ALL CIRCUIT BREAKERS FROM DEMOLITIONED PANELS
SHALL BE BOXED UP AND DELIVERED TO THE OWNER, TO AN
ON CAMPUS LOCATION AS DIRECTED BY OWNER.
2. ALL CONDUCTORS BEING REMOVED THAT ARE RATED 100
AMPS AND ABOVE SHALL BE DELIVERED TO THE CAMPUS
RECYCLING CENTER.
3. ALL TRANSFORMERS BEING REMOVED SHALL BE DELIVERED
TO THE OWNER, TO AN ON CAMPUS LOCATION AS DIRECTED
BY OWNER.
4. UNLESS INDICATED ABOVE, ALL OTHER MATERIAL SHALL BE
DISPOSED OF LEGALLY BY THE CONTRACTOR.
5. CAREFULLY REMOVE ALL EXISTING FIRE ALARM DEVICES IN
CONFLICT WITH REMODEL, TO BE UTILIZED WHERE
POSSIBLE IN NEW SYSTEM. SEE NEW FIRE ALARM PLANS.
6. E.C. SHALL REMOVE ALL EXISTING DATA CABLING IN THE
BUILDING. PROTECT AND MAINTAIN EXISTING FIBER OPTIC
BACKBONE CABLING AND RACEWAY WHEREVER POSSIBLE.
PROVIDE AND INSTALL A COMPLETE AND NEW HORIZONTAL
CABLING PLANT TO ACCOMMODATED REMODEL.
SPECIAL DEMOLITION NOTES:
A. IN GENERAL, UNLESS SPECIFICALLY INDICATED OTHERWISE,
ALL EXISTING ELECTRICAL EQUIPMENT SHOWN SHALL BE
REMOVED. WHEN EXISTING SWITCH AND OR OUTLET BOXES
FALL WITHIN OR NEAR NEW OUTLETS/SWITCHES SHOWN IN
NEW DESIGN, THE E.C. MAY UTILIZE THE EXISTING ROUGH-IN,
ETC. IN LIEU OF INSTALLING NEW. CONTRACTOR MUST
HOWEVER MAINTAIN ELECTRICAL CONTINUITY TO
DOWNSTREAM EQUIPMENT TO REMAIN. ELECTRICAL
CONTRACTOR MAY UTILIZE ANY EXISTING RACEWAYS
WHERE THEY ARE COMPATIBLE WITH NEW DESIGN/SYSTEMS.
PROVIDE ALL NEW DEVICES AND COVERS.
B. ALL EXISTING ELECTRICAL MAY NOT APPEAR ON THESE
PLANS, HOWEVER THE ABOVE INFORMATION APPLIES.
C. PROVIDE AND INSTALL BLANK COVERS ON ALL UNUSED
SWITCH/OUTLET/J-BOXES WHERE REQUIRED.
D. ALL WALL DEVICES THAT ARE EXISTING TO REMAIN, SHALL
BE ADAPTED TO NEW WALL COVERINGS, REFER TO
ARCHITECTURAL DRAWINGS FOR EXACT WALL LOCATIONS,
THICKNESS, ETC.
E. PRIOR TO THE START OF ANY DEMOLITION WORK,
DISCONNECTING ANY POWER AND OR TELE/DATA SYSTEMS,
THE CONTRACTOR SHALL COORDINATE DOWN-TIME WITH
THE OWNER.
F. REFER TO ARCHITECTURAL PLANS FOR EXTENT OF
DEMOLITION, DETAILS, ETC.
G. REMOVE OR RELOCATE ELECTRICAL AS NECESSARY FOR
NEW WORK.
H. WHERE EXISTING CIRCUITS ARE TO BE RE-USED, EXTEND AS
NECESSARY. MAINTAIN ELECTRICAL CONTINUITY TO
DOWNSTREAM EQUIPMENT TO REMAIN.
I. EXISTING SHOWN TO REMAIN, MAY NEED TO BE REMOVED
AND RE-INSTALLED ONLY AS NECESSARY FOR EXTENDING
OR MODIFICATION OF EXISTING CIRCUITS OR WIRING.
J. REFER TO MECHANICAL PLANS FOR EXTENT OF MECHANICAL
EQUIPMENT TO BE REMOVED OR RELOCATED.
K. REMOVE ALL UNUSED EQUIPMENT WIRING, CONDUIT AND
BOXES IN ALL AREAS. ABANDON ONLY IN CONCEALED
AREAS.
L. CONTRACTOR MY UTILIZE ANY EXISTING CONDUIT WHERE
COMPATIBLE WITH NEW DESIGN, AND IF IN GOOD CONDITION
AND COMPLIES WITH SPECIFICATIONS.
M. WHEN ANY MODIFICATIONS ARE MADE TO ANY EXISTING
ELECTRICAL PANEL TO REMAIN, CONTRACTOR TO PROVIDE
NEW TYPE WRITTEN INDEX TO REFLECT ALL NEW AND
EXISTING LOADS.
N. REMOVE ALL EQUIPMENT, RACEWAYS, CABLES,ETC. NOT
USED IN FINISHED AREAS.
O. UNLESS OTHERWISE NOTED DISCONNECT AND REMOVE ALL
EXISTING LIGHTING. REMOVE ALL ASSOCIATED CIRCUITING
AND CONTROLS.
GENERAL NOTES:
KEY NOTES:#
1 EXISTING EXIT LIGHT TO REMAIN. PROTECT AND/OR
RE-ESTABLISH ELECTRICAL SERVICE.
NORTH
16'8'0"SCALE: 1/8" = 1'-0"1 LEVEL 2 EXISTING LIGHITNG PLAN AREA A
KEY PLAN
A
B
16151413121110987
K
H
F
D
B
A
1
8270
STATEOFIDAHO
T
ODD P A Y N EREGISTER
EDRP
OFESSIONALEN
G
I
NE
E
R
1823 E. Center
Pocatello, Idaho 83201
tel (208) 232-4439
www.payneengineeringinc.com
Engineering Inc.
Consulting Engineers
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
P.E. #:2259
10-28-2022 ED104
EXISTING
LIGHTING
PLAN LEVEL
2 AREA B
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
BID SET
1. ALL CIRCUIT BREAKERS FROM DEMOLITIONED PANELS
SHALL BE BOXED UP AND DELIVERED TO THE OWNER, TO AN
ON CAMPUS LOCATION AS DIRECTED BY OWNER.
2. ALL CONDUCTORS BEING REMOVED THAT ARE RATED 100
AMPS AND ABOVE SHALL BE DELIVERED TO THE CAMPUS
RECYCLING CENTER.
3. ALL TRANSFORMERS BEING REMOVED SHALL BE DELIVERED
TO THE OWNER, TO AN ON CAMPUS LOCATION AS DIRECTED
BY OWNER.
4. UNLESS INDICATED ABOVE, ALL OTHER MATERIAL SHALL BE
DISPOSED OF LEGALLY BY THE CONTRACTOR.
5. CAREFULLY REMOVE ALL EXISTING FIRE ALARM DEVICES IN
CONFLICT WITH REMODEL, TO BE UTILIZED WHERE
POSSIBLE IN NEW SYSTEM. SEE NEW FIRE ALARM PLANS.
6. E.C. SHALL REMOVE ALL EXISTING DATA CABLING IN THE
BUILDING. PROTECT AND MAINTAIN EXISTING FIBER OPTIC
BACKBONE CABLING AND RACEWAY WHEREVER POSSIBLE.
PROVIDE AND INSTALL A COMPLETE AND NEW HORIZONTAL
CABLING PLANT TO ACCOMMODATED REMODEL.
SPECIAL DEMOLITION NOTES:
A. IN GENERAL, UNLESS SPECIFICALLY INDICATED OTHERWISE,
ALL EXISTING ELECTRICAL EQUIPMENT SHOWN SHALL BE
REMOVED. WHEN EXISTING SWITCH AND OR OUTLET BOXES
FALL WITHIN OR NEAR NEW OUTLETS/SWITCHES SHOWN IN
NEW DESIGN, THE E.C. MAY UTILIZE THE EXISTING ROUGH-IN,
ETC. IN LIEU OF INSTALLING NEW. CONTRACTOR MUST
HOWEVER MAINTAIN ELECTRICAL CONTINUITY TO
DOWNSTREAM EQUIPMENT TO REMAIN. ELECTRICAL
CONTRACTOR MAY UTILIZE ANY EXISTING RACEWAYS
WHERE THEY ARE COMPATIBLE WITH NEW DESIGN/SYSTEMS.
PROVIDE ALL NEW DEVICES AND COVERS.
B. ALL EXISTING ELECTRICAL MAY NOT APPEAR ON THESE
PLANS, HOWEVER THE ABOVE INFORMATION APPLIES.
C. PROVIDE AND INSTALL BLANK COVERS ON ALL UNUSED
SWITCH/OUTLET/J-BOXES WHERE REQUIRED.
D. ALL WALL DEVICES THAT ARE EXISTING TO REMAIN, SHALL
BE ADAPTED TO NEW WALL COVERINGS, REFER TO
ARCHITECTURAL DRAWINGS FOR EXACT WALL LOCATIONS,
THICKNESS, ETC.
E. PRIOR TO THE START OF ANY DEMOLITION WORK,
DISCONNECTING ANY POWER AND OR TELE/DATA SYSTEMS,
THE CONTRACTOR SHALL COORDINATE DOWN-TIME WITH
THE OWNER.
F. REFER TO ARCHITECTURAL PLANS FOR EXTENT OF
DEMOLITION, DETAILS, ETC.
G. REMOVE OR RELOCATE ELECTRICAL AS NECESSARY FOR
NEW WORK.
H. WHERE EXISTING CIRCUITS ARE TO BE RE-USED, EXTEND AS
NECESSARY. MAINTAIN ELECTRICAL CONTINUITY TO
DOWNSTREAM EQUIPMENT TO REMAIN.
I. EXISTING SHOWN TO REMAIN, MAY NEED TO BE REMOVED
AND RE-INSTALLED ONLY AS NECESSARY FOR EXTENDING
OR MODIFICATION OF EXISTING CIRCUITS OR WIRING.
J. REFER TO MECHANICAL PLANS FOR EXTENT OF MECHANICAL
EQUIPMENT TO BE REMOVED OR RELOCATED.
K. REMOVE ALL UNUSED EQUIPMENT WIRING, CONDUIT AND
BOXES IN ALL AREAS. ABANDON ONLY IN CONCEALED
AREAS.
L. CONTRACTOR MY UTILIZE ANY EXISTING CONDUIT WHERE
COMPATIBLE WITH NEW DESIGN, AND IF IN GOOD CONDITION
AND COMPLIES WITH SPECIFICATIONS.
M. WHEN ANY MODIFICATIONS ARE MADE TO ANY EXISTING
ELECTRICAL PANEL TO REMAIN, CONTRACTOR TO PROVIDE
NEW TYPE WRITTEN INDEX TO REFLECT ALL NEW AND
EXISTING LOADS.
N. REMOVE ALL EQUIPMENT, RACEWAYS, CABLES,ETC. NOT
USED IN FINISHED AREAS.
O. UNLESS OTHERWISE NOTED DISCONNECT AND REMOVE ALL
EXISTING LIGHTING. REMOVE ALL ASSOCIATED CIRCUITING
AND CONTROLS.
GENERAL NOTES:
KEY NOTES:#
1 EXISTING EXIT LIGHT TO REMAIN. PROTECT AND/OR
RE-ESTABLISH ELECTRICAL SERVICE.
NORTH
16'8'0"SCALE: 1/8" = 1'-0"1 LEVEL 2 EXISTING LIGHITNG PLAN AREA B
KEY PLAN
A
B
1
G
J
L
M
N
P
Q
E
C
2 3 4 5 61.5
1
8270
STATEOFIDAHO
T
ODD P A Y N EREGISTER
EDRP
OFESSIONALEN
G
I
NE
E
R
1823 E. Center
Pocatello, Idaho 83201
tel (208) 232-4439
www.payneengineeringinc.com
Engineering Inc.
Consulting Engineers
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
P.E. #:2259
10-28-2022 ED105
EXISTING
LIGHTING
PLAN LEVEL
3
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
BID SET
1. ALL CIRCUIT BREAKERS FROM DEMOLITIONED PANELS
SHALL BE BOXED UP AND DELIVERED TO THE OWNER, TO AN
ON CAMPUS LOCATION AS DIRECTED BY OWNER.
2. ALL CONDUCTORS BEING REMOVED THAT ARE RATED 100
AMPS AND ABOVE SHALL BE DELIVERED TO THE CAMPUS
RECYCLING CENTER.
3. ALL TRANSFORMERS BEING REMOVED SHALL BE DELIVERED
TO THE OWNER, TO AN ON CAMPUS LOCATION AS DIRECTED
BY OWNER.
4. UNLESS INDICATED ABOVE, ALL OTHER MATERIAL SHALL BE
DISPOSED OF LEGALLY BY THE CONTRACTOR.
5. CAREFULLY REMOVE ALL EXISTING FIRE ALARM DEVICES IN
CONFLICT WITH REMODEL, TO BE UTILIZED WHERE
POSSIBLE IN NEW SYSTEM. SEE NEW FIRE ALARM PLANS.
6. E.C. SHALL REMOVE ALL EXISTING DATA CABLING IN THE
BUILDING. PROTECT AND MAINTAIN EXISTING FIBER OPTIC
BACKBONE CABLING AND RACEWAY WHEREVER POSSIBLE.
PROVIDE AND INSTALL A COMPLETE AND NEW HORIZONTAL
CABLING PLANT TO ACCOMMODATED REMODEL.
SPECIAL DEMOLITION NOTES:
A. IN GENERAL, UNLESS SPECIFICALLY INDICATED OTHERWISE,
ALL EXISTING ELECTRICAL EQUIPMENT SHOWN SHALL BE
REMOVED. WHEN EXISTING SWITCH AND OR OUTLET BOXES
FALL WITHIN OR NEAR NEW OUTLETS/SWITCHES SHOWN IN
NEW DESIGN, THE E.C. MAY UTILIZE THE EXISTING ROUGH-IN,
ETC. IN LIEU OF INSTALLING NEW. CONTRACTOR MUST
HOWEVER MAINTAIN ELECTRICAL CONTINUITY TO
DOWNSTREAM EQUIPMENT TO REMAIN. ELECTRICAL
CONTRACTOR MAY UTILIZE ANY EXISTING RACEWAYS
WHERE THEY ARE COMPATIBLE WITH NEW DESIGN/SYSTEMS.
PROVIDE ALL NEW DEVICES AND COVERS.
B. ALL EXISTING ELECTRICAL MAY NOT APPEAR ON THESE
PLANS, HOWEVER THE ABOVE INFORMATION APPLIES.
C. PROVIDE AND INSTALL BLANK COVERS ON ALL UNUSED
SWITCH/OUTLET/J-BOXES WHERE REQUIRED.
D. ALL WALL DEVICES THAT ARE EXISTING TO REMAIN, SHALL
BE ADAPTED TO NEW WALL COVERINGS, REFER TO
ARCHITECTURAL DRAWINGS FOR EXACT WALL LOCATIONS,
THICKNESS, ETC.
E. PRIOR TO THE START OF ANY DEMOLITION WORK,
DISCONNECTING ANY POWER AND OR TELE/DATA SYSTEMS,
THE CONTRACTOR SHALL COORDINATE DOWN-TIME WITH
THE OWNER.
F. REFER TO ARCHITECTURAL PLANS FOR EXTENT OF
DEMOLITION, DETAILS, ETC.
G. REMOVE OR RELOCATE ELECTRICAL AS NECESSARY FOR
NEW WORK.
H. WHERE EXISTING CIRCUITS ARE TO BE RE-USED, EXTEND AS
NECESSARY. MAINTAIN ELECTRICAL CONTINUITY TO
DOWNSTREAM EQUIPMENT TO REMAIN.
I. EXISTING SHOWN TO REMAIN, MAY NEED TO BE REMOVED
AND RE-INSTALLED ONLY AS NECESSARY FOR EXTENDING
OR MODIFICATION OF EXISTING CIRCUITS OR WIRING.
J. REFER TO MECHANICAL PLANS FOR EXTENT OF MECHANICAL
EQUIPMENT TO BE REMOVED OR RELOCATED.
K. REMOVE ALL UNUSED EQUIPMENT WIRING, CONDUIT AND
BOXES IN ALL AREAS. ABANDON ONLY IN CONCEALED
AREAS.
L. CONTRACTOR MY UTILIZE ANY EXISTING CONDUIT WHERE
COMPATIBLE WITH NEW DESIGN, AND IF IN GOOD CONDITION
AND COMPLIES WITH SPECIFICATIONS.
M. WHEN ANY MODIFICATIONS ARE MADE TO ANY EXISTING
ELECTRICAL PANEL TO REMAIN, CONTRACTOR TO PROVIDE
NEW TYPE WRITTEN INDEX TO REFLECT ALL NEW AND
EXISTING LOADS.
N. REMOVE ALL EQUIPMENT, RACEWAYS, CABLES,ETC. NOT
USED IN FINISHED AREAS.
O. UNLESS OTHERWISE NOTED DISCONNECT AND REMOVE ALL
EXISTING LIGHTING. REMOVE ALL ASSOCIATED CIRCUITING
AND CONTROLS.
GENERAL NOTES:
KEY NOTES:#
1 EXISTING EXIT LIGHT TO REMAIN. PROTECT AND/OR
RE-ESTABLISH ELECTRICAL SERVICE.
NORTH
16'8'0"SCALE: 1/8" = 1'-0"1 LEVEL 3 EXISTING LIGHTING PLAN
KEY PLAN
A
B
P
P
PP
P
P
FF
P
D D D
D D D
PP
PP
P F
F
P
PP
P
RM RM RM
RM RM RM
M
M
M
M
G
J
E
C
2 3 4 5 6
'O'
'M
C
'
'A
T
S
W
E
S
T
'
'E
M
W
'
'A
T
S
E
A
S
T
'
'E
M
E
'
EXISTING SWITCH GEAR
'E'
'UPS'
1
PROTECT AND
MAINTAIN ALL
EXISTING
ELECTRICAL
EQUIPMENT IN
THIS ROOM
2
2
2
2
2
2
2
'CP7'
3
2
22
2 2 2
'R'
'U
P
S
-W
'
'DB1''P'
4
5
MASTER
CLOCK
3
2
2
2
2
22
2
2
2
2
2
6
7
8
9
8270
STATEOFIDAHO
T
ODD P A Y N EREGISTER
EDRP
OFESSIONALEN
G
I
NE
E
R
1823 E. Center
Pocatello, Idaho 83201
tel (208) 232-4439
www.payneengineeringinc.com
Engineering Inc.
Consulting Engineers
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
P.E. #:2259
10-28-2022 ED200
EXISTING
ELECTRICAL
PLAN LEVEL
0
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
BID SET
SCALE: 1/8" = 1'-0"1 LEVEL 0 EXISTING ELECTRICAL PLAN
1. ALL CIRCUIT BREAKERS FROM DEMOLITIONED PANELS
SHALL BE BOXED UP AND DELIVERED TO THE OWNER, TO AN
ON CAMPUS LOCATION AS DIRECTED BY OWNER.
2. ALL CONDUCTORS BEING REMOVED THAT ARE RATED 100
AMPS AND ABOVE SHALL BE DELIVERED TO THE CAMPUS
RECYCLING CENTER.
3. ALL TRANSFORMERS BEING REMOVED SHALL BE DELIVERED
TO THE OWNER, TO AN ON CAMPUS LOCATION AS DIRECTED
BY OWNER.
4. UNLESS INDICATED ABOVE, ALL OTHER MATERIAL SHALL BE
DISPOSED OF LEGALLY BY THE CONTRACTOR.
5. CAREFULLY REMOVE ALL EXISTING FIRE ALARM DEVICES IN
CONFLICT WITH REMODEL, TO BE UTILIZED WHERE
POSSIBLE IN NEW SYSTEM. SEE NEW FIRE ALARM PLANS.
6. E.C. SHALL REMOVE ALL EXISTING DATA CABLING IN THE
BUILDING. PROTECT AND MAINTAIN EXISTING FIBER OPTIC
BACKBONE CABLING AND RACEWAY WHEREVER POSSIBLE.
PROVIDE AND INSTALL A COMPLETE AND NEW HORIZONTAL
CABLING PLANT TO ACCOMMODATED REMODEL.
SPECIAL DEMOLITION NOTES:
A. IN GENERAL, UNLESS SPECIFICALLY INDICATED OTHERWISE,
ALL EXISTING ELECTRICAL EQUIPMENT SHOWN SHALL BE
REMOVED. WHEN EXISTING SWITCH AND OR OUTLET BOXES
FALL WITHIN OR NEAR NEW OUTLETS/SWITCHES SHOWN IN
NEW DESIGN, THE E.C. MAY UTILIZE THE EXISTING ROUGH-IN,
ETC. IN LIEU OF INSTALLING NEW. CONTRACTOR MUST
HOWEVER MAINTAIN ELECTRICAL CONTINUITY TO
DOWNSTREAM EQUIPMENT TO REMAIN. ELECTRICAL
CONTRACTOR MAY UTILIZE ANY EXISTING RACEWAYS
WHERE THEY ARE COMPATIBLE WITH NEW DESIGN/SYSTEMS.
PROVIDE ALL NEW DEVICES AND COVERS.
B. ALL EXISTING ELECTRICAL MAY NOT APPEAR ON THESE
PLANS, HOWEVER THE ABOVE INFORMATION APPLIES.
C. PROVIDE AND INSTALL BLANK COVERS ON ALL UNUSED
SWITCH/OUTLET/J-BOXES WHERE REQUIRED.
D. ALL WALL DEVICES THAT ARE EXISTING TO REMAIN, SHALL
BE ADAPTED TO NEW WALL COVERINGS, REFER TO
ARCHITECTURAL DRAWINGS FOR EXACT WALL LOCATIONS,
THICKNESS, ETC.
E. PRIOR TO THE START OF ANY DEMOLITION WORK,
DISCONNECTING ANY POWER AND OR TELE/DATA SYSTEMS,
THE CONTRACTOR SHALL COORDINATE DOWN-TIME WITH
THE OWNER.
F. REFER TO ARCHITECTURAL PLANS FOR EXTENT OF
DEMOLITION, DETAILS, ETC.
G. REMOVE OR RELOCATE ELECTRICAL AS NECESSARY FOR
NEW WORK.
H. WHERE EXISTING CIRCUITS ARE TO BE RE-USED, EXTEND AS
NECESSARY. MAINTAIN ELECTRICAL CONTINUITY TO
DOWNSTREAM EQUIPMENT TO REMAIN.
I. EXISTING SHOWN TO REMAIN, MAY NEED TO BE REMOVED
AND RE-INSTALLED ONLY AS NECESSARY FOR EXTENDING
OR MODIFICATION OF EXISTING CIRCUITS OR WIRING.
J. REFER TO MECHANICAL PLANS FOR EXTENT OF MECHANICAL
EQUIPMENT TO BE REMOVED OR RELOCATED.
K. REMOVE ALL UNUSED EQUIPMENT WIRING, CONDUIT AND
BOXES IN ALL AREAS. ABANDON ONLY IN CONCEALED
AREAS.
L. CONTRACTOR MY UTILIZE ANY EXISTING CONDUIT WHERE
COMPATIBLE WITH NEW DESIGN, AND IF IN GOOD CONDITION
AND COMPLIES WITH SPECIFICATIONS.
M. WHEN ANY MODIFICATIONS ARE MADE TO ANY EXISTING
ELECTRICAL PANEL TO REMAIN, CONTRACTOR TO PROVIDE
NEW TYPE WRITTEN INDEX TO REFLECT ALL NEW AND
EXISTING LOADS.
N. REMOVE ALL EQUIPMENT, RACEWAYS, CABLES,ETC. NOT
USED IN FINISHED AREAS.
O. UNLESS OTHERWISE NOTED DISCONNECT AND REMOVE ALL
EXISTING LIGHTING. REMOVE ALL ASSOCIATED CIRCUITING
AND CONTROLS.
GENERAL NOTES:
KEY NOTES:#
1 DISCONNECT AND REMOVE EXISTING MCC. REMOVE ALL
ASSOCIATED CONDUIT AND WIRE FEEDERS BACK TO
SOURCE AND LABEL BREAKER AS SPARE. REMOVE
ASSOCIATED WIRE AND CONDUIT TO EXISTING LOADS.
2 EXISTING DEVICE LOCATION TO REMAIN. REPLACE DEVICE
AND FACEPLATE. PROVIDE NEW CIRCUIT AS SHOWN.
3 EXISTING ELECTRICAL PANEL TO REMAIN. PROTECT,
MAINTAIN OR RE-ESTABLISH ELECTRICAL SERVICE TO THIS
PANEL.
4 EXISTING VFD'S PROTECT, MAINTAIN, AND/OR RE-ESTABLISH
ELECTRICAL SERVICE TO DEVICES.
5 EXISTING PANEL TO REMAIN. PROTECT, MAINTAIN, AND/OR
RE-ESTABLISH ELECTRICAL SERVICE. MAINTAIN EXISTING
BRANCH CIRCUITS FROM PANEL, AND NEW AS SHOWN.
PROVIDE NEW PANEL INDEX AND PANEL LABEL.
6 EXISTING DEVICE TO REMAIN. PROTECT DEVICE DURING
CONSTRUCTION, MAINTAIN AND/OR RE-ESTABLISH SERVICE
TO DEVICE.
7 CAREFULLY DISCONNECT, REMOVE, CLEAN, AND STORE
EXISTING CLOCK TO BE USED IN REMODEL.
8 EXISTING MASTER CLOCK CIRCUIT. E.C. SHALL FIELD VERIFY
EXACT LOCATION. PROTECT AND MAINTAIN CIRCUIT TO BE
USED IN REMODEL.
9 EXISTING PANEL LOCATION TO REMAIN. DISCONNECT AND
REMOVE EXISTING POWERLINK 'AS' INTERIOR. REPLACE
WITH COMPATIBLE 'NQ' STYLE INTERIOR AND BREAKERS.
PROVIDE NEW DOOR AND PANEL INDEX SHOWING NEW
CIRCUITING.
NORTH
16'8'0"
DEMO: FIRE ALARM SYSTEM
• E.C. SHALL DISCONNECT AND REMOVE ALL EXISTING FIRE
ALARM DEVICES. DISCONNECT AND REMOVE ALL
ASSOCIATED CONDUIT AND WIRE.
• DISCONNECT, REMOVE, AND RETURN ALL FIRE ALARM
CONTROL PANELS, NAC PANELS, AND ANNUNCIATOR PANEL
TO OWNER.
P
F
F
P
PP
P
P
P
P
P
P
P
P
P
P
P
P
PP
P
P
P
P P
P
P
P
P
P
P
P
P
P
P
P
PP
P
P
F
P
1
G
J
L
M
N
P
Q
E
C
2 3 4 5 61.5
'EW3'
'1LB'
'CP11'
'CP9''CP10'
1
1
2
2
2
2
2
2
2
2
3
1
2
2
2
2
'B'
3
4
5
5
5
5
5
5
'C'
6
7
7
7
7
7
77
7
7
7
5
5
5
7
2
5
5
5 5
5
5
5 5
5
5
5 5
8
5
5
8
5
5
9
10 10
10
10
10
1010
10
10
10
9
11 11
8270
STATEOFIDAHO
T
ODD P A Y N EREGISTER
EDRP
OFESSIONALEN
G
I
NE
E
R
1823 E. Center
Pocatello, Idaho 83201
tel (208) 232-4439
www.payneengineeringinc.com
Engineering Inc.
Consulting Engineers
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
P.E. #:2259
10-28-2022 ED201
EXISTING
ELECTRICAL
PLAN LEVEL
1 AREA A
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
BID SET
1. ALL CIRCUIT BREAKERS FROM DEMOLITIONED PANELS
SHALL BE BOXED UP AND DELIVERED TO THE OWNER, TO AN
ON CAMPUS LOCATION AS DIRECTED BY OWNER.
2. ALL CONDUCTORS BEING REMOVED THAT ARE RATED 100
AMPS AND ABOVE SHALL BE DELIVERED TO THE CAMPUS
RECYCLING CENTER.
3. ALL TRANSFORMERS BEING REMOVED SHALL BE DELIVERED
TO THE OWNER, TO AN ON CAMPUS LOCATION AS DIRECTED
BY OWNER.
4. UNLESS INDICATED ABOVE, ALL OTHER MATERIAL SHALL BE
DISPOSED OF LEGALLY BY THE CONTRACTOR.
5. CAREFULLY REMOVE ALL EXISTING FIRE ALARM DEVICES IN
CONFLICT WITH REMODEL, TO BE UTILIZED WHERE
POSSIBLE IN NEW SYSTEM. SEE NEW FIRE ALARM PLANS.
6. E.C. SHALL REMOVE ALL EXISTING DATA CABLING IN THE
BUILDING. PROTECT AND MAINTAIN EXISTING FIBER OPTIC
BACKBONE CABLING AND RACEWAY WHEREVER POSSIBLE.
PROVIDE AND INSTALL A COMPLETE AND NEW HORIZONTAL
CABLING PLANT TO ACCOMMODATED REMODEL.
SPECIAL DEMOLITION NOTES:
A. IN GENERAL, UNLESS SPECIFICALLY INDICATED OTHERWISE,
ALL EXISTING ELECTRICAL EQUIPMENT SHOWN SHALL BE
REMOVED. WHEN EXISTING SWITCH AND OR OUTLET BOXES
FALL WITHIN OR NEAR NEW OUTLETS/SWITCHES SHOWN IN
NEW DESIGN, THE E.C. MAY UTILIZE THE EXISTING ROUGH-IN,
ETC. IN LIEU OF INSTALLING NEW. CONTRACTOR MUST
HOWEVER MAINTAIN ELECTRICAL CONTINUITY TO
DOWNSTREAM EQUIPMENT TO REMAIN. ELECTRICAL
CONTRACTOR MAY UTILIZE ANY EXISTING RACEWAYS
WHERE THEY ARE COMPATIBLE WITH NEW DESIGN/SYSTEMS.
PROVIDE ALL NEW DEVICES AND COVERS.
B. ALL EXISTING ELECTRICAL MAY NOT APPEAR ON THESE
PLANS, HOWEVER THE ABOVE INFORMATION APPLIES.
C. PROVIDE AND INSTALL BLANK COVERS ON ALL UNUSED
SWITCH/OUTLET/J-BOXES WHERE REQUIRED.
D. ALL WALL DEVICES THAT ARE EXISTING TO REMAIN, SHALL
BE ADAPTED TO NEW WALL COVERINGS, REFER TO
ARCHITECTURAL DRAWINGS FOR EXACT WALL LOCATIONS,
THICKNESS, ETC.
E. PRIOR TO THE START OF ANY DEMOLITION WORK,
DISCONNECTING ANY POWER AND OR TELE/DATA SYSTEMS,
THE CONTRACTOR SHALL COORDINATE DOWN-TIME WITH
THE OWNER.
F. REFER TO ARCHITECTURAL PLANS FOR EXTENT OF
DEMOLITION, DETAILS, ETC.
G. REMOVE OR RELOCATE ELECTRICAL AS NECESSARY FOR
NEW WORK.
H. WHERE EXISTING CIRCUITS ARE TO BE RE-USED, EXTEND AS
NECESSARY. MAINTAIN ELECTRICAL CONTINUITY TO
DOWNSTREAM EQUIPMENT TO REMAIN.
I. EXISTING SHOWN TO REMAIN, MAY NEED TO BE REMOVED
AND RE-INSTALLED ONLY AS NECESSARY FOR EXTENDING
OR MODIFICATION OF EXISTING CIRCUITS OR WIRING.
J. REFER TO MECHANICAL PLANS FOR EXTENT OF MECHANICAL
EQUIPMENT TO BE REMOVED OR RELOCATED.
K. REMOVE ALL UNUSED EQUIPMENT WIRING, CONDUIT AND
BOXES IN ALL AREAS. ABANDON ONLY IN CONCEALED
AREAS.
L. CONTRACTOR MY UTILIZE ANY EXISTING CONDUIT WHERE
COMPATIBLE WITH NEW DESIGN, AND IF IN GOOD CONDITION
AND COMPLIES WITH SPECIFICATIONS.
M. WHEN ANY MODIFICATIONS ARE MADE TO ANY EXISTING
ELECTRICAL PANEL TO REMAIN, CONTRACTOR TO PROVIDE
NEW TYPE WRITTEN INDEX TO REFLECT ALL NEW AND
EXISTING LOADS.
N. REMOVE ALL EQUIPMENT, RACEWAYS, CABLES,ETC. NOT
USED IN FINISHED AREAS.
O. UNLESS OTHERWISE NOTED DISCONNECT AND REMOVE ALL
EXISTING LIGHTING. REMOVE ALL ASSOCIATED CIRCUITING
AND CONTROLS.
GENERAL NOTES:
KEY NOTES:#
1 DISCONNECT AND REMOVE EXISTING PANEL. REMOVE ALL
ASSOCIATED CONDUIT AND WIRE FROM FEEDER AND
BRANCH CIRCUITS.
2 DISCONNECT AND REMOVE ALL POWER/DATA POLES IN
CONFLICT WITH REMODEL. REMOVE ALL ASSOCIATED
CONDUIT AND WIRE BACK TO SOURCE OR NEXT ACTIVE
J-BOX. MARK ANY UNUSED BREAKERS AS "SPARE".
3 EXISTING ELECTRICAL PANEL TO REMAIN. PROTECT,
MAINTAIN OR RE-ESTABLISH ELECTRICAL SERVICE TO THIS
PANEL.
4 CAREFULLY DISCONNECT AND REMOVE EXISTING
POWERLINK PANEL. INTERIOR OF PANEL TO BE REUSED IN
NEW DESIGN, PROVIDE NEW CAN, FRAME, AND DOOR FOR
EXISTING PANEL INTERIOR. REMOVE ALL ASSOCIATED
CONDUIT AND WIRE FROM FEEDER AND BRANCH CIRCUITS.
SEE NEW ELECTRICAL DESIGN FOR REINSTALLATION
LOCATION.
5 EXISTING DEVICE LOCATION TO REMAIN. REPLACE DEVICE
AND FACEPLATE. PROVIDE NEW CIRCUIT AS SHOWN.
6 EXISTING PANEL TO BE REMOVED, REMOVE ALL ASSOCIATED
CONDUIT, WIRE, AND CABLING.
7 CAREFULLY DISCONNECT, REMOVE, AND CLEAN EXISTING
SECURITY CAMERA. REMOVE ALL ASSOCIATED CONDUIT AND
CABLE. RETURN CAMERA TO OWNER.
8 CAREFULLY DISCONNECT, REMOVE, CLEAN, AND STORE
EXISTING CLOCK TO BE USED IN REMODEL.
9 REMOVE EXISTING SECTION OF CABLE TRAY IN CONFLICT
WITH REMODEL.
10 EXISTING CABLE TRAY TO REMAIN, PROTECT DURING
CONSTRUCTION.
11 EXISTING ADA DOOR OPENING DEVICES. PROTECT DEVICES,
MAINTAIN AND/OR RE-ESTABLISH FUNCTIONALITY OF
SYSTEM. PROVIDE NEW CIRCUITING AS SHOWN IN NEW
DESIGN.
SCALE: 1/8" = 1'-0"1 LEVEL 1 EXISTING ELECTRICAL PLAN AREA A
NORTH
16'8'0"
KEY PLAN
A
B
DEMO: FIRE ALARM SYSTEM
• E.C. SHALL DISCONNECT AND REMOVE ALL EXISTING FIRE
ALARM DEVICES. DISCONNECT AND REMOVE ALL
ASSOCIATED CONDUIT AND WIRE.
• DISCONNECT, REMOVE, AND RETURN ALL FIRE ALARM
CONTROL PANELS, NAC PANELS, AND ANNUNCIATOR PANEL
TO OWNER.
J J
J
J
J
F
TS FS
DD
D D
RM
CM
P
P
F
F
F
P P
P
P
P
P
P
P P
P
P
P
P
P
P
P P
P P
P P
M M M M
CR
16151413121110987
K
H
F
D
B
A
'M'
'1P''EE'
'1A'
'1LA'
'CP1'
'CP2'
'CP3'
'CP4'
'CC''MCC1'
1
1
1
1
1
1
1
2
2 3
4
2 5 2
6
7
8
8 8 8 8 8
8
8
8
8
8
8
8
8888888
8
8
8
8
8
8
8
8
8 8
8
8
8
88
8
8
8
8
8
8
8
8
8
8
88
88
8
8888
8
8
8
8
8
8
8
8
8 8
8
8 8 8 8
8
1 1
8
9
10
8 8 8
11
10
1
11210
1
13
13
13
13
13
13
13
13
13
13
14
14
14
8270
STATEOFIDAHO
T
ODD P A Y N EREGISTER
EDRP
OFESSIONALEN
G
I
NE
E
R
1823 E. Center
Pocatello, Idaho 83201
tel (208) 232-4439
www.payneengineeringinc.com
Engineering Inc.
Consulting Engineers
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
P.E. #:2259
10-28-2022 ED202
EXISTING
ELECTRICAL
PLAN LEVEL
1 AREA B
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
BID SET
1. ALL CIRCUIT BREAKERS FROM DEMOLITIONED PANELS
SHALL BE BOXED UP AND DELIVERED TO THE OWNER, TO AN
ON CAMPUS LOCATION AS DIRECTED BY OWNER.
2. ALL CONDUCTORS BEING REMOVED THAT ARE RATED 100
AMPS AND ABOVE SHALL BE DELIVERED TO THE CAMPUS
RECYCLING CENTER.
3. ALL TRANSFORMERS BEING REMOVED SHALL BE DELIVERED
TO THE OWNER, TO AN ON CAMPUS LOCATION AS DIRECTED
BY OWNER.
4. UNLESS INDICATED ABOVE, ALL OTHER MATERIAL SHALL BE
DISPOSED OF LEGALLY BY THE CONTRACTOR.
5. CAREFULLY REMOVE ALL EXISTING FIRE ALARM DEVICES IN
CONFLICT WITH REMODEL, TO BE UTILIZED WHERE
POSSIBLE IN NEW SYSTEM. SEE NEW FIRE ALARM PLANS.
6. E.C. SHALL REMOVE ALL EXISTING DATA CABLING IN THE
BUILDING. PROTECT AND MAINTAIN EXISTING FIBER OPTIC
BACKBONE CABLING AND RACEWAY WHEREVER POSSIBLE.
PROVIDE AND INSTALL A COMPLETE AND NEW HORIZONTAL
CABLING PLANT TO ACCOMMODATED REMODEL.
SPECIAL DEMOLITION NOTES:
A. IN GENERAL, UNLESS SPECIFICALLY INDICATED OTHERWISE,
ALL EXISTING ELECTRICAL EQUIPMENT SHOWN SHALL BE
REMOVED. WHEN EXISTING SWITCH AND OR OUTLET BOXES
FALL WITHIN OR NEAR NEW OUTLETS/SWITCHES SHOWN IN
NEW DESIGN, THE E.C. MAY UTILIZE THE EXISTING ROUGH-IN,
ETC. IN LIEU OF INSTALLING NEW. CONTRACTOR MUST
HOWEVER MAINTAIN ELECTRICAL CONTINUITY TO
DOWNSTREAM EQUIPMENT TO REMAIN. ELECTRICAL
CONTRACTOR MAY UTILIZE ANY EXISTING RACEWAYS
WHERE THEY ARE COMPATIBLE WITH NEW DESIGN/SYSTEMS.
PROVIDE ALL NEW DEVICES AND COVERS.
B. ALL EXISTING ELECTRICAL MAY NOT APPEAR ON THESE
PLANS, HOWEVER THE ABOVE INFORMATION APPLIES.
C. PROVIDE AND INSTALL BLANK COVERS ON ALL UNUSED
SWITCH/OUTLET/J-BOXES WHERE REQUIRED.
D. ALL WALL DEVICES THAT ARE EXISTING TO REMAIN, SHALL
BE ADAPTED TO NEW WALL COVERINGS, REFER TO
ARCHITECTURAL DRAWINGS FOR EXACT WALL LOCATIONS,
THICKNESS, ETC.
E. PRIOR TO THE START OF ANY DEMOLITION WORK,
DISCONNECTING ANY POWER AND OR TELE/DATA SYSTEMS,
THE CONTRACTOR SHALL COORDINATE DOWN-TIME WITH
THE OWNER.
F. REFER TO ARCHITECTURAL PLANS FOR EXTENT OF
DEMOLITION, DETAILS, ETC.
G. REMOVE OR RELOCATE ELECTRICAL AS NECESSARY FOR
NEW WORK.
H. WHERE EXISTING CIRCUITS ARE TO BE RE-USED, EXTEND AS
NECESSARY. MAINTAIN ELECTRICAL CONTINUITY TO
DOWNSTREAM EQUIPMENT TO REMAIN.
I. EXISTING SHOWN TO REMAIN, MAY NEED TO BE REMOVED
AND RE-INSTALLED ONLY AS NECESSARY FOR EXTENDING
OR MODIFICATION OF EXISTING CIRCUITS OR WIRING.
J. REFER TO MECHANICAL PLANS FOR EXTENT OF MECHANICAL
EQUIPMENT TO BE REMOVED OR RELOCATED.
K. REMOVE ALL UNUSED EQUIPMENT WIRING, CONDUIT AND
BOXES IN ALL AREAS. ABANDON ONLY IN CONCEALED
AREAS.
L. CONTRACTOR MY UTILIZE ANY EXISTING CONDUIT WHERE
COMPATIBLE WITH NEW DESIGN, AND IF IN GOOD CONDITION
AND COMPLIES WITH SPECIFICATIONS.
M. WHEN ANY MODIFICATIONS ARE MADE TO ANY EXISTING
ELECTRICAL PANEL TO REMAIN, CONTRACTOR TO PROVIDE
NEW TYPE WRITTEN INDEX TO REFLECT ALL NEW AND
EXISTING LOADS.
N. REMOVE ALL EQUIPMENT, RACEWAYS, CABLES,ETC. NOT
USED IN FINISHED AREAS.
O. UNLESS OTHERWISE NOTED DISCONNECT AND REMOVE ALL
EXISTING LIGHTING. REMOVE ALL ASSOCIATED CIRCUITING
AND CONTROLS.
GENERAL NOTES:
KEY NOTES:#
1 DISCONNECT AND REMOVE ALL POWER/DATA POLES IN
CONFLICT WITH REMODEL. REMOVE ALL ASSOCIATED
CONDUIT AND WIRE BACK TO SOURCE OR NEXT ACTIVE
J-BOX. MARK ANY UNUSED BREAKERS AS "SPARE".
2 EXISTING ELECTRICAL PANEL TO REMAIN. PROTECT,
MAINTAIN OR RE-ESTABLISH ELECTRICAL SERVICE TO
THIS PANEL.
3 DISCONNECT AND REMOVE EXISTING MCC. REMOVE ALL
ASSOCIATED CONDUIT AND WIRE FEEDERS BACK TO
SOURCE AND LABEL BREAKER AS SPARE. REMOVE
ASSOCIATED WIRE AND CONDUIT TO EXISTING LOADS.
4 REPLACE EXISTING MAIN SWITCHBOARD WITH NEW.
RECONNECT ALL EXISTING AND NEW FEEDERS.
5 EXISTING PANEL LOCATION TO REMAIN. DISCONNECT
AND REMOVE EXISTING POWERLINK 'AS' INTERIOR.
REPLACE WITH COMPATIBLE 'NQ' STYLE INTERIOR AND
BREAKERS. PROVIDE NEW PANEL INDEX SHOWING NEW
CIRCUITING.
6 EXISTING 100A 3 POLE BREAKER AND ENCLOSURE, W/
SHUNT TRIP CONTROL, TO REMAIN. PROTECT, MAINTAIN
AND/OR RE-ESTABLISH ELECTRICAL SERVICE TO
DISCONNECT.
7 CAREFULLY DISCONNECT AND REMOVE EXISTING
POWERLINK PANEL. INTERIOR OF PANEL TO BE REUSED
IN NEW DESIGN, PROVIDE NEW CAN, FRAME, AND DOOR
FOR EXISTING PANEL INTERIOR. REMOVE ALL
ASSOCIATED CONDUIT AND WIRE FROM FEEDER AND
BRANCH CIRCUITS. SEE NEW ELECTRICAL DESIGN FOR
REINSTALLATION LOCATION.
8 EXISTING DEVICE LOCATION TO REMAIN. REPLACE
DEVICE AND FACEPLATE. PROVIDE NEW CIRCUIT AS
SHOWN.
9 EXISTING RACEWAY TO BE REMOVED, REMOVED ALL
ASSOCIATED CONDUIT, WIRE, AND CABLE.
10 CAREFULLY DISCONNECT, REMOVE, AND CLEAN
EXISTING SECURITY CAMERA. REMOVE ALL ASSOCIATED
CONDUIT AND CABLE. RETURN CAMERA TO OWNER.
11 EXISTING ADA DOOR OPENING DEVICES. PROTECT
DEVICES, MAINTAIN AND/OR RE-ESTABLISH
FUNCTIONALITY OF SYSTEM. PROVIDE NEW CIRCUITING
AS SHOWN IN NEW DESIGN.
12 CAREFULLY DISCONNECT, REMOVE, CLEAN, AND STORE
EXISTING CLOCK TO BE USED IN REMODEL.
13 EXISTING CABLE TRAY TO REMAIN, PROTECT DURING
CONSTRUCTION.
14 REMOVE EXISTING SECTION OF CABLE TRAY IN
CONFLICT WITH REMODEL.
SCALE: 1/8" = 1'-0"1 LEVEL 1 EXISTING ELECTRICAL PLAN AREA B
NORTH
16'8'0"
KEY PLAN
A
B
DEMO: FIRE ALARM SYSTEM
• E.C. SHALL DISCONNECT AND REMOVE ALL EXISTING FIRE
ALARM DEVICES. DISCONNECT AND REMOVE ALL
ASSOCIATED CONDUIT AND WIRE.
• DISCONNECT, REMOVE, AND RETURN ALL FIRE ALARM
CONTROL PANELS, NAC PANELS, AND ANNUNCIATOR PANEL
TO OWNER.
P
P P
PPP
P P P P
P
P P
P P
P
PPPPP
P P
PP
PPP
P P
P
P P
PP
P
P
P
P
F
P P
P
PP
P
P
P
P
J
1
G
J
L
M
N
P
Q
E
C
2 3 4 5 61.5
'2
L
B
'
'2
W
A
'
'C
P
1
3
'
'C
P
1
4
'
'U
P
S
'
'E
W
2
'
'D'
'G'
'F1'
'F'
'CP12'
1
2
3
4
5
5
5
6
5
5
5 5
55
5
57
8
1
5
8
7
7
3
3
8
8
8
7
5
5
9
9
9
9
9
9
9
9
9
9
9
9
9
10
5 10
5
8270
STATEOFIDAHO
T
ODD P A Y N EREGISTER
EDRP
OFESSIONALEN
G
I
NE
E
R
1823 E. Center
Pocatello, Idaho 83201
tel (208) 232-4439
www.payneengineeringinc.com
Engineering Inc.
Consulting Engineers
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
P.E. #:2259
10-28-2022 ED203
EXISTING
ELECTRICAL
PLAN LEVEL
2 AREA A
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
BID SET
1. ALL CIRCUIT BREAKERS FROM DEMOLITIONED PANELS
SHALL BE BOXED UP AND DELIVERED TO THE OWNER, TO AN
ON CAMPUS LOCATION AS DIRECTED BY OWNER.
2. ALL CONDUCTORS BEING REMOVED THAT ARE RATED 100
AMPS AND ABOVE SHALL BE DELIVERED TO THE CAMPUS
RECYCLING CENTER.
3. ALL TRANSFORMERS BEING REMOVED SHALL BE DELIVERED
TO THE OWNER, TO AN ON CAMPUS LOCATION AS DIRECTED
BY OWNER.
4. UNLESS INDICATED ABOVE, ALL OTHER MATERIAL SHALL BE
DISPOSED OF LEGALLY BY THE CONTRACTOR.
5. CAREFULLY REMOVE ALL EXISTING FIRE ALARM DEVICES IN
CONFLICT WITH REMODEL, TO BE UTILIZED WHERE
POSSIBLE IN NEW SYSTEM. SEE NEW FIRE ALARM PLANS.
6. E.C. SHALL REMOVE ALL EXISTING DATA CABLING IN THE
BUILDING. PROTECT AND MAINTAIN EXISTING FIBER OPTIC
BACKBONE CABLING AND RACEWAY WHEREVER POSSIBLE.
PROVIDE AND INSTALL A COMPLETE AND NEW HORIZONTAL
CABLING PLANT TO ACCOMMODATED REMODEL.
SPECIAL DEMOLITION NOTES:
A. IN GENERAL, UNLESS SPECIFICALLY INDICATED OTHERWISE,
ALL EXISTING ELECTRICAL EQUIPMENT SHOWN SHALL BE
REMOVED. WHEN EXISTING SWITCH AND OR OUTLET BOXES
FALL WITHIN OR NEAR NEW OUTLETS/SWITCHES SHOWN IN
NEW DESIGN, THE E.C. MAY UTILIZE THE EXISTING ROUGH-IN,
ETC. IN LIEU OF INSTALLING NEW. CONTRACTOR MUST
HOWEVER MAINTAIN ELECTRICAL CONTINUITY TO
DOWNSTREAM EQUIPMENT TO REMAIN. ELECTRICAL
CONTRACTOR MAY UTILIZE ANY EXISTING RACEWAYS
WHERE THEY ARE COMPATIBLE WITH NEW DESIGN/SYSTEMS.
PROVIDE ALL NEW DEVICES AND COVERS.
B. ALL EXISTING ELECTRICAL MAY NOT APPEAR ON THESE
PLANS, HOWEVER THE ABOVE INFORMATION APPLIES.
C. PROVIDE AND INSTALL BLANK COVERS ON ALL UNUSED
SWITCH/OUTLET/J-BOXES WHERE REQUIRED.
D. ALL WALL DEVICES THAT ARE EXISTING TO REMAIN, SHALL
BE ADAPTED TO NEW WALL COVERINGS, REFER TO
ARCHITECTURAL DRAWINGS FOR EXACT WALL LOCATIONS,
THICKNESS, ETC.
E. PRIOR TO THE START OF ANY DEMOLITION WORK,
DISCONNECTING ANY POWER AND OR TELE/DATA SYSTEMS,
THE CONTRACTOR SHALL COORDINATE DOWN-TIME WITH
THE OWNER.
F. REFER TO ARCHITECTURAL PLANS FOR EXTENT OF
DEMOLITION, DETAILS, ETC.
G. REMOVE OR RELOCATE ELECTRICAL AS NECESSARY FOR
NEW WORK.
H. WHERE EXISTING CIRCUITS ARE TO BE RE-USED, EXTEND AS
NECESSARY. MAINTAIN ELECTRICAL CONTINUITY TO
DOWNSTREAM EQUIPMENT TO REMAIN.
I. EXISTING SHOWN TO REMAIN, MAY NEED TO BE REMOVED
AND RE-INSTALLED ONLY AS NECESSARY FOR EXTENDING
OR MODIFICATION OF EXISTING CIRCUITS OR WIRING.
J. REFER TO MECHANICAL PLANS FOR EXTENT OF MECHANICAL
EQUIPMENT TO BE REMOVED OR RELOCATED.
K. REMOVE ALL UNUSED EQUIPMENT WIRING, CONDUIT AND
BOXES IN ALL AREAS. ABANDON ONLY IN CONCEALED
AREAS.
L. CONTRACTOR MY UTILIZE ANY EXISTING CONDUIT WHERE
COMPATIBLE WITH NEW DESIGN, AND IF IN GOOD CONDITION
AND COMPLIES WITH SPECIFICATIONS.
M. WHEN ANY MODIFICATIONS ARE MADE TO ANY EXISTING
ELECTRICAL PANEL TO REMAIN, CONTRACTOR TO PROVIDE
NEW TYPE WRITTEN INDEX TO REFLECT ALL NEW AND
EXISTING LOADS.
N. REMOVE ALL EQUIPMENT, RACEWAYS, CABLES,ETC. NOT
USED IN FINISHED AREAS.
O. UNLESS OTHERWISE NOTED DISCONNECT AND REMOVE ALL
EXISTING LIGHTING. REMOVE ALL ASSOCIATED CIRCUITING
AND CONTROLS.
GENERAL NOTES:
KEY NOTES:#
1 DISCONNECT AND REMOVE EXISTING PANEL. REMOVE
ALL ASSOCIATED CONDUIT AND WIRE FROM FEEDER AND
BRANCH CIRCUITS.
2 EXISTING ELECTRICAL PANEL TO REMAIN. PROTECT,
MAINTAIN OR RE-ESTABLISH ELECTRICAL SERVICE TO
THIS PANEL.
3 DISCONNECT AND REMOVE ALL POWER/DATA POLES IN
CONFLICT WITH REMODEL. REMOVE ALL ASSOCIATED
CONDUIT AND WIRE BACK TO SOURCE OR NEXT ACTIVE
J-BOX. MARK ANY UNUSED BREAKERS AS "SPARE".
4 CAREFULLY DISCONNECT AND REMOVE EXISTING
POWERLINK PANEL. INTERIOR OF PANEL TO BE REUSED
IN NEW DESIGN, PROVIDE NEW CAN, FRAME, AND DOOR
FOR EXISTING PANEL INTERIOR. REMOVE ALL
ASSOCIATED CONDUIT AND WIRE FROM FEEDER AND
BRANCH CIRCUITS. SEE NEW ELECTRICAL DESIGN FOR
REINSTALLATION LOCATION.
5 EXISTING DEVICE LOCATION TO REMAIN. REPLACE
DEVICE AND FACEPLATE. PROVIDE NEW CIRCUIT AS
SHOWN.
6 EXISTING WIREMOLD TO BE REMOVED. REMOVE ALL
ASSOCIATED DEVICES, WIRE, CABLE, AND CONDUIT.
7 CAREFULLY DISCONNECT, REMOVE, CLEAN, AND STORE
EXISTING CLOCK TO BE USED IN REMODEL.
8 CAREFULLY DISCONNECT, REMOVE, AND CLEAN
EXISTING SECURITY CAMERA. REMOVE ALL ASSOCIATED
CONDUIT AND CABLE. RETURN CAMERA TO OWNER.
9 EXISTING CABLE TRAY TO REMAIN, PROTECT DURING
CONSTRUCTION.
10 EXISTING PANEL LOCATION TO REMAIN. DISCONNECT
AND REMOVE EXISTING POWERLINK 'AS' INTERIOR.
REPLACE WITH COMPATIBLE 'NQ' STYLE INTERIOR AND
BREAKERS. PROVIDE NEW DOOR AND PANEL INDEX
SHOWING NEW CIRCUITING.
SCALE: 1/8" = 1'-0"1 LEVEL 2 EXISTING ELECTRICAL PLAN AREA A
NORTH
16'8'0"
KEY PLAN
A
B
DEMO: FIRE ALARM SYSTEM
• E.C. SHALL DISCONNECT AND REMOVE ALL EXISTING FIRE
ALARM DEVICES. DISCONNECT AND REMOVE ALL
ASSOCIATED CONDUIT AND WIRE.
• DISCONNECT, REMOVE, AND RETURN ALL FIRE ALARM
CONTROL PANELS, NAC PANELS, AND ANNUNCIATOR PANEL
TO OWNER.
J
JJ
J
F
P
PP
P
P P
P P P P
P
P
P
PP
P
PP
P
P PP
P
P
P
P
P
H
16151413121110987
K
H
F
D
B
A
'CP8''CP5''2B''EE2'
'UPS1''2A''2LA''CP6'
1
1
1
2 34
5
5
5
5 5 5 5 5
5
5
5 5
5
5
5
5
5
5 5
5
5 5 5 5 5 5
5
5 5 5
5
5
5
5
5
5
5
5
5
555555
5
5
5
5
5
5
5
5
5
5
55
5
5
5
5
5
5
5
5
5
5
5
5
6
7
8
5
6
6
6
6
9
9
9
9
9
9
9
9
9
9
9
9
9
8270
STATEOFIDAHO
T
ODD P A Y N EREGISTER
EDRP
OFESSIONALEN
G
I
NE
E
R
1823 E. Center
Pocatello, Idaho 83201
tel (208) 232-4439
www.payneengineeringinc.com
Engineering Inc.
Consulting Engineers
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
P.E. #:2259
10-28-2022 ED204
EXISTING
ELECTRICAL
PLAN LEVEL
2 AREA B
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
BID SET
1. ALL CIRCUIT BREAKERS FROM DEMOLITIONED PANELS
SHALL BE BOXED UP AND DELIVERED TO THE OWNER, TO AN
ON CAMPUS LOCATION AS DIRECTED BY OWNER.
2. ALL CONDUCTORS BEING REMOVED THAT ARE RATED 100
AMPS AND ABOVE SHALL BE DELIVERED TO THE CAMPUS
RECYCLING CENTER.
3. ALL TRANSFORMERS BEING REMOVED SHALL BE DELIVERED
TO THE OWNER, TO AN ON CAMPUS LOCATION AS DIRECTED
BY OWNER.
4. UNLESS INDICATED ABOVE, ALL OTHER MATERIAL SHALL BE
DISPOSED OF LEGALLY BY THE CONTRACTOR.
5. CAREFULLY REMOVE ALL EXISTING FIRE ALARM DEVICES IN
CONFLICT WITH REMODEL, TO BE UTILIZED WHERE
POSSIBLE IN NEW SYSTEM. SEE NEW FIRE ALARM PLANS.
6. E.C. SHALL REMOVE ALL EXISTING DATA CABLING IN THE
BUILDING. PROTECT AND MAINTAIN EXISTING FIBER OPTIC
BACKBONE CABLING AND RACEWAY WHEREVER POSSIBLE.
PROVIDE AND INSTALL A COMPLETE AND NEW HORIZONTAL
CABLING PLANT TO ACCOMMODATED REMODEL.
SPECIAL DEMOLITION NOTES:
A. IN GENERAL, UNLESS SPECIFICALLY INDICATED OTHERWISE,
ALL EXISTING ELECTRICAL EQUIPMENT SHOWN SHALL BE
REMOVED. WHEN EXISTING SWITCH AND OR OUTLET BOXES
FALL WITHIN OR NEAR NEW OUTLETS/SWITCHES SHOWN IN
NEW DESIGN, THE E.C. MAY UTILIZE THE EXISTING ROUGH-IN,
ETC. IN LIEU OF INSTALLING NEW. CONTRACTOR MUST
HOWEVER MAINTAIN ELECTRICAL CONTINUITY TO
DOWNSTREAM EQUIPMENT TO REMAIN. ELECTRICAL
CONTRACTOR MAY UTILIZE ANY EXISTING RACEWAYS
WHERE THEY ARE COMPATIBLE WITH NEW DESIGN/SYSTEMS.
PROVIDE ALL NEW DEVICES AND COVERS.
B. ALL EXISTING ELECTRICAL MAY NOT APPEAR ON THESE
PLANS, HOWEVER THE ABOVE INFORMATION APPLIES.
C. PROVIDE AND INSTALL BLANK COVERS ON ALL UNUSED
SWITCH/OUTLET/J-BOXES WHERE REQUIRED.
D. ALL WALL DEVICES THAT ARE EXISTING TO REMAIN, SHALL
BE ADAPTED TO NEW WALL COVERINGS, REFER TO
ARCHITECTURAL DRAWINGS FOR EXACT WALL LOCATIONS,
THICKNESS, ETC.
E. PRIOR TO THE START OF ANY DEMOLITION WORK,
DISCONNECTING ANY POWER AND OR TELE/DATA SYSTEMS,
THE CONTRACTOR SHALL COORDINATE DOWN-TIME WITH
THE OWNER.
F. REFER TO ARCHITECTURAL PLANS FOR EXTENT OF
DEMOLITION, DETAILS, ETC.
G. REMOVE OR RELOCATE ELECTRICAL AS NECESSARY FOR
NEW WORK.
H. WHERE EXISTING CIRCUITS ARE TO BE RE-USED, EXTEND AS
NECESSARY. MAINTAIN ELECTRICAL CONTINUITY TO
DOWNSTREAM EQUIPMENT TO REMAIN.
I. EXISTING SHOWN TO REMAIN, MAY NEED TO BE REMOVED
AND RE-INSTALLED ONLY AS NECESSARY FOR EXTENDING
OR MODIFICATION OF EXISTING CIRCUITS OR WIRING.
J. REFER TO MECHANICAL PLANS FOR EXTENT OF MECHANICAL
EQUIPMENT TO BE REMOVED OR RELOCATED.
K. REMOVE ALL UNUSED EQUIPMENT WIRING, CONDUIT AND
BOXES IN ALL AREAS. ABANDON ONLY IN CONCEALED
AREAS.
L. CONTRACTOR MY UTILIZE ANY EXISTING CONDUIT WHERE
COMPATIBLE WITH NEW DESIGN, AND IF IN GOOD CONDITION
AND COMPLIES WITH SPECIFICATIONS.
M. WHEN ANY MODIFICATIONS ARE MADE TO ANY EXISTING
ELECTRICAL PANEL TO REMAIN, CONTRACTOR TO PROVIDE
NEW TYPE WRITTEN INDEX TO REFLECT ALL NEW AND
EXISTING LOADS.
N. REMOVE ALL EQUIPMENT, RACEWAYS, CABLES,ETC. NOT
USED IN FINISHED AREAS.
O. UNLESS OTHERWISE NOTED DISCONNECT AND REMOVE ALL
EXISTING LIGHTING. REMOVE ALL ASSOCIATED CIRCUITING
AND CONTROLS.
GENERAL NOTES:
KEY NOTES:#
1 DISCONNECT AND REMOVE ALL POWER/DATA POLES IN
CONFLICT WITH REMODEL. REMOVE ALL ASSOCIATED
CONDUIT AND WIRE BACK TO SOURCE OR NEXT ACTIVE
J-BOX. MARK ANY UNUSED BREAKERS AS "SPARE".
2 EXISTING ELECTRICAL PANEL TO REMAIN. PROTECT,
MAINTAIN OR RE-ESTABLISH ELECTRICAL SERVICE TO
THIS PANEL.
3 EXISTING PANEL LOCATION TO REMAIN. DISCONNECT
AND REMOVE EXISTING POWERLINK 'AS' INTERIOR.
REPLACE WITH COMPATIBLE 'NQ' STYLE INTERIOR AND
BREAKERS. PROVIDE NEW PANEL INDEX SHOWING NEW
CIRCUITING.
4 CAREFULLY DISCONNECT AND REMOVE EXISTING
POWERLINK PANEL. INTERIOR OF PANEL TO BE REUSED
IN NEW DESIGN, PROVIDE NEW CAN, FRAME, AND DOOR
FOR EXISTING PANEL INTERIOR. REMOVE ALL
ASSOCIATED CONDUIT AND WIRE FROM FEEDER AND
BRANCH CIRCUITS. SEE NEW ELECTRICAL DESIGN FOR
REINSTALLATION LOCATION.
5 EXISTING DEVICE LOCATION TO REMAIN. REPLACE
DEVICE AND FACEPLATE. PROVIDE NEW CIRCUIT AS
SHOWN.
6 CAREFULLY DISCONNECT, REMOVE, CLEAN, AND STORE
EXISTING CLOCK TO BE USED IN REMODEL.
7 EXISTING WIREMOLD TO BE REMOVED. REMOVE ALL
ASSOCIATED DEVICES, WIRE, CABLE, AND CONDUIT.
8 CAREFULLY DISCONNECT, REMOVE, AND CLEAN
EXISTING SECURITY CAMERA. REMOVE ALL ASSOCIATED
CONDUIT AND CABLE. RETURN CAMERA TO OWNER.
9 EXISTING CABLE TRAY TO REMAIN, PROTECT DURING
CONSTRUCTION.
SCALE: 1/8" = 1'-0"1 LEVEL 2 EXISTING ELECTRICAL PLAN AREA B
NORTH
16'8'0"KEY PLAN
A
B
DEMO: FIRE ALARM SYSTEM
• E.C. SHALL DISCONNECT AND REMOVE ALL EXISTING FIRE
ALARM DEVICES. DISCONNECT AND REMOVE ALL
ASSOCIATED CONDUIT AND WIRE.
• DISCONNECT, REMOVE, AND RETURN ALL FIRE ALARM
CONTROL PANELS, NAC PANELS, AND ANNUNCIATOR PANEL
TO OWNER.
P
P
P H
P
PP
P
P
1
G
J
L
M
N
P
Q
E
C
2 3 4 5 61.5
'H'
'K'
'N'
'3
L
A
'
'3
W
A
'
'C
P
1
8
'
'C
P
1
7
'
'3WB'
'CP15'
'CP16'
1
1
1
2
2
2
2
2
2
2
2
2
1
3
4
4
4
'J'
5
6
7
7
7
8
8
5
8
5
5
5
2
5
4
4
4
4
444
4
4
4
4
4 4
4
4
9 9 9
9
9
9
9
9
9
9
9
10
10
10
9
9
9
9
9
9
8270
STATEOFIDAHO
T
ODD P A Y N EREGISTER
EDRP
OFESSIONALEN
G
I
NE
E
R
1823 E. Center
Pocatello, Idaho 83201
tel (208) 232-4439
www.payneengineeringinc.com
Engineering Inc.
Consulting Engineers
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
P.E. #:2259
10-28-2022 ED205
EXISTING
ELECTRICAL
PLAN LEVEL
3
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
BID SET
1. ALL CIRCUIT BREAKERS FROM DEMOLITIONED PANELS
SHALL BE BOXED UP AND DELIVERED TO THE OWNER, TO AN
ON CAMPUS LOCATION AS DIRECTED BY OWNER.
2. ALL CONDUCTORS BEING REMOVED THAT ARE RATED 100
AMPS AND ABOVE SHALL BE DELIVERED TO THE CAMPUS
RECYCLING CENTER.
3. ALL TRANSFORMERS BEING REMOVED SHALL BE DELIVERED
TO THE OWNER, TO AN ON CAMPUS LOCATION AS DIRECTED
BY OWNER.
4. UNLESS INDICATED ABOVE, ALL OTHER MATERIAL SHALL BE
DISPOSED OF LEGALLY BY THE CONTRACTOR.
5. CAREFULLY REMOVE ALL EXISTING FIRE ALARM DEVICES IN
CONFLICT WITH REMODEL, TO BE UTILIZED WHERE
POSSIBLE IN NEW SYSTEM. SEE NEW FIRE ALARM PLANS.
6. E.C. SHALL REMOVE ALL EXISTING DATA CABLING IN THE
BUILDING. PROTECT AND MAINTAIN EXISTING FIBER OPTIC
BACKBONE CABLING AND RACEWAY WHEREVER POSSIBLE.
PROVIDE AND INSTALL A COMPLETE AND NEW HORIZONTAL
CABLING PLANT TO ACCOMMODATED REMODEL.
SPECIAL DEMOLITION NOTES:
A. IN GENERAL, UNLESS SPECIFICALLY INDICATED OTHERWISE,
ALL EXISTING ELECTRICAL EQUIPMENT SHOWN SHALL BE
REMOVED. WHEN EXISTING SWITCH AND OR OUTLET BOXES
FALL WITHIN OR NEAR NEW OUTLETS/SWITCHES SHOWN IN
NEW DESIGN, THE E.C. MAY UTILIZE THE EXISTING ROUGH-IN,
ETC. IN LIEU OF INSTALLING NEW. CONTRACTOR MUST
HOWEVER MAINTAIN ELECTRICAL CONTINUITY TO
DOWNSTREAM EQUIPMENT TO REMAIN. ELECTRICAL
CONTRACTOR MAY UTILIZE ANY EXISTING RACEWAYS
WHERE THEY ARE COMPATIBLE WITH NEW DESIGN/SYSTEMS.
PROVIDE ALL NEW DEVICES AND COVERS.
B. ALL EXISTING ELECTRICAL MAY NOT APPEAR ON THESE
PLANS, HOWEVER THE ABOVE INFORMATION APPLIES.
C. PROVIDE AND INSTALL BLANK COVERS ON ALL UNUSED
SWITCH/OUTLET/J-BOXES WHERE REQUIRED.
D. ALL WALL DEVICES THAT ARE EXISTING TO REMAIN, SHALL
BE ADAPTED TO NEW WALL COVERINGS, REFER TO
ARCHITECTURAL DRAWINGS FOR EXACT WALL LOCATIONS,
THICKNESS, ETC.
E. PRIOR TO THE START OF ANY DEMOLITION WORK,
DISCONNECTING ANY POWER AND OR TELE/DATA SYSTEMS,
THE CONTRACTOR SHALL COORDINATE DOWN-TIME WITH
THE OWNER.
F. REFER TO ARCHITECTURAL PLANS FOR EXTENT OF
DEMOLITION, DETAILS, ETC.
G. REMOVE OR RELOCATE ELECTRICAL AS NECESSARY FOR
NEW WORK.
H. WHERE EXISTING CIRCUITS ARE TO BE RE-USED, EXTEND AS
NECESSARY. MAINTAIN ELECTRICAL CONTINUITY TO
DOWNSTREAM EQUIPMENT TO REMAIN.
I. EXISTING SHOWN TO REMAIN, MAY NEED TO BE REMOVED
AND RE-INSTALLED ONLY AS NECESSARY FOR EXTENDING
OR MODIFICATION OF EXISTING CIRCUITS OR WIRING.
J. REFER TO MECHANICAL PLANS FOR EXTENT OF MECHANICAL
EQUIPMENT TO BE REMOVED OR RELOCATED.
K. REMOVE ALL UNUSED EQUIPMENT WIRING, CONDUIT AND
BOXES IN ALL AREAS. ABANDON ONLY IN CONCEALED
AREAS.
L. CONTRACTOR MY UTILIZE ANY EXISTING CONDUIT WHERE
COMPATIBLE WITH NEW DESIGN, AND IF IN GOOD CONDITION
AND COMPLIES WITH SPECIFICATIONS.
M. WHEN ANY MODIFICATIONS ARE MADE TO ANY EXISTING
ELECTRICAL PANEL TO REMAIN, CONTRACTOR TO PROVIDE
NEW TYPE WRITTEN INDEX TO REFLECT ALL NEW AND
EXISTING LOADS.
N. REMOVE ALL EQUIPMENT, RACEWAYS, CABLES,ETC. NOT
USED IN FINISHED AREAS.
O. UNLESS OTHERWISE NOTED DISCONNECT AND REMOVE ALL
EXISTING LIGHTING. REMOVE ALL ASSOCIATED CIRCUITING
AND CONTROLS.
GENERAL NOTES:
KEY NOTES:#
1 DISCONNECT AND REMOVE EXISTING PANEL. REMOVE ALL
ASSOCIATED CONDUIT AND WIRE FROM FEEDER AND
BRANCH CIRCUITS.
2 DISCONNECT AND REMOVE ALL POWER/DATA POLES IN
CONFLICT WITH REMODEL. REMOVE ALL ASSOCIATED
CONDUIT AND WIRE BACK TO SOURCE OR NEXT ACTIVE
J-BOX. MARK ANY UNUSED BREAKERS AS "SPARE".
3 CAREFULLY DISCONNECT AND REMOVE EXISTING
POWERLINK PANEL. INTERIOR OF PANEL TO BE REUSED IN
NEW DESIGN, PROVIDE NEW CAN, FRAME, AND DOOR FOR
EXISTING PANEL INTERIOR. REMOVE ALL ASSOCIATED
CONDUIT AND WIRE FROM FEEDER AND BRANCH CIRCUITS.
SEE NEW ELECTRICAL DESIGN FOR REINSTALLATION
LOCATION.
4 EXISTING DEVICE LOCATION TO REMAIN. REPLACE DEVICE
AND FACEPLATE. PROVIDE NEW CIRCUIT AS SHOWN.
5 CAREFULLY DISCONNECT, REMOVE, AND CLEAN EXISTING
SECURITY CAMERA. REMOVE ALL ASSOCIATED CONDUIT AND
CABLE. RETURN CAMERA TO OWNER.
6 EXISTING ELECTRICAL PANEL TO REMAIN. PROTECT,
MAINTAIN OR RE-ESTABLISH ELECTRICAL SERVICE TO THIS
PANEL.
7 EXISTING WIREMOLD TO BE REMOVED. REMOVE ALL
ASSOCIATED DEVICES, WIRE, CABLE, AND CONDUIT.
8 CAREFULLY DISCONNECT, REMOVE, CLEAN, AND STORE
EXISTING CLOCK TO BE USED IN REMODEL.
9 EXISTING CABLE TRAY TO REMAIN, PROTECT DURING
CONSTRUCTION.
1
0
REMOVE EXISTING SECTION OF CABLE TRAY IN CONFLICT
WITH REMODEL.
SCALE: 1/8" = 1'-0"1 LEVEL 3 EXISTING PLAN
NORTH
16'8'0"
DEMO: FIRE ALARM SYSTEM
• E.C. SHALL DISCONNECT AND REMOVE ALL EXISTING FIRE
ALARM DEVICES. DISCONNECT AND REMOVE ALL
ASSOCIATED CONDUIT AND WIRE.
• DISCONNECT, REMOVE, AND RETURN ALL FIRE ALARM
CONTROL PANELS, NAC PANELS, AND ANNUNCIATOR PANEL
TO OWNER.
REF.REF.
S
nD1
R
nPS80
nD
C
S
nD1
R
nPS80
S
nD1
R
nPS80
SnD1
R
nPS80
nD
C
nD
C
nD
C
nD
C
R
nPS80
SnD1
S
nD1
R
nPS80
nD
C
nD
C
nD
S
nD
1
SnD1
nD
nD
C
SnD1
R
nPS80
SnD1
nD
nO
S
nD1
nD
nDC nDC nDC nDC
SnD1S
nD1
SnD1SnD1
R
nPS80
R
nPS80
R
nPS80R
nPS80
nD
C
SCD2 S
CD2
nO
nO
SnD1
S
nD1
S
nD1
nD
nD
nD
SnD1
M
M
M
nD
nD
J
1 7
G
J
L
E
C
2 3 4 5 61.5
TIER 2
[016]
OFFICE
[010]
OFFICE
[026A]
OFFICE
[011]
BREAK
ROOM
[013]
OFFICE
[018]
STORAGE
[032]
OFFICE
[012]
OFFICE
[026C]
STUDENTS
[026F]
TECH
ROOM
[024]
SHORT
TERM
STORAGE
[028]
QA
[022A]
OFFICE
[020]
OPS
[022]
STORAGE
[044]
CUSTODIAL
STORAGE
[042]BDF
[040]MEN'S RR
[015]WOMEN'S
RR
[014]
ELECTRICAL
[038]
CUSTODIAL
[036]
MECH
CHASE
[034]
ELEV
[0-J]
STAIR
[0-E]
MECH
CHASE
[O-F]
STAIR
[0-E]
MECH
ROOM
[030]
CHEMICALS
ROOM
[O-D]
IMAGING
AND
STORAGE
[009]
OFFICE
[026B]OFFICE
[026D]
OFFICE
[026E]
'O'
'EME'
'EMW'
'MC'
'ATS WEST''ATS EAST'
'E'
F11
F8
F8
(TYP)
F3
(TYP)
F3
(TYP)
F2
(TYP)
F3
(TYP)
F2
(TYP)
F2
(TYP)
F2
(TYP)
F2 (TYP)
F2
(TYP)
F2
F3
F3
(TYP)
F3
(TYP)
F3
(TYP)
F3
(TYP)
F3
F8
F8
F8
F8
F8
F8
F11 F11
F11F11
F3
F5F5F3
F3
F11
F1
F1
F1
F1
F3
F1
F1
F1
F1
(TYP)
F3
F3E
F3NL
F3NL
F3E
F3NL
F3E
(TYP)
F3
(TYP)
F3
(TYP)
F3
F3E F3E
F3NL
F3E
F3NL
F3E
F3E
F3E
F11E
F11E
(TYP)
F3
F3NL
(TYP)
F2
F23 F23 F23
(TYP)
F11
O-2
O-4
O-6
O-3
F11E
F11E
F11E
F11E
F8NL
(TYP)
F3
1
2
(TYP)
F2
(TYP)
F2
O-1
O-5
O-2
3
3
O-7
8270
STATEOFIDAHO
T
ODD P A Y N EREGISTER
EDRP
OFESSIONALEN
G
I
NE
E
R
1823 E. Center
Pocatello, Idaho 83201
tel (208) 232-4439
www.payneengineeringinc.com
Engineering Inc.
Consulting Engineers
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
P.E. #:2259
10-28-2022 EE100
LIGHITNG
PLAN LEVEL
0
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
BID SET
A. REFER TO SYMBOL SCHEDULE SHEET FOR PROJECT
GENERAL NOTES AND GENERAL NOTES ASSOCIATED WITH
THE INSTALLATION OF EACH SYSTEM, INCLUDINB BUT NOT
LIMITED TO; LIGHTING, POWER, FIRE ALARM, SPECIAL
SYSTEMS, ETC.
GENERAL NOTES:
KEY NOTES:#
1 LIGHTING SHOWN FOR QUANTITY, E.C. SHALL MATCH
EXISTING LAYOUT. UTILIZE EXISTING LIGHITNG CIRCUIT
IN AREA.
2 AIR HANDLER LIGHTING TO REMAIN. MAINTAIN AND/OR
RE-ESTABLISH ELECTRICAL FEEDER AND CONTROLS.
3 EXISTING LIGHT TO REMAIN. PROTECT DURING
CONSTRUCTION, CIRCUIT AND CONTROL AS SHOWN IN
NEW DESIGN.
SCALE: 1/8" = 1'-0"1 LEVEL 0 LIGHITNG PLAN
16'8'0"
NORTH
RE
F
.
nDC
nD
C
S
nD1
SnD1
R
nPS80
R
nPS80
S
nD1
R
nPS80
S
nD1
R
nPS80
S
nD1
R
nPS80
SnD1
R
nPS80
SnD1
R
nPS80
S
nD1
R
nPS80
SnD1
SnD1
SnD1
SnD1
SnD1
SnD1
SnD1
SnD1
SnD1
SnD1
nD
C
nD
C
nD
C
nD
C
nD
C
nDC
nD
nD
nD
nD
nD
nD
nD
n1
n1
S
nD1
SCD2
S
CD2
S
nD1
n1
n1 S
nD1
S
nD1
R
nPS80
nDC
nD
nO
M M M
M
M
S
PS
S
PS
M
1
G
J
L
M
N
P
Q
E
C
2 3 4 5 61.5
CHECK-IN
[112]
OFFICE
[129]
OFFICE
[130]OFFICE
[131]
STUDY
(MED)
[132]
OFFICE
[136]
RECEPTION
[134]
OFFICE
[138]
CONFERENCE
ROOM
[140]
BREAKROOM
[142]STUDY (SM)
[128]
STUDY
(MED)
[124]
STUDY
(MED)
[125]
STUDY (SM)
[126]
STUDY (SM)
[127]
OPEN
STUDY
[120A]
VESTIBULE
[1-F]
CIRCULATION
RECEPTION
[110]
OFFICE
[108]
INTER
LIBRARY
LOAN
WORKSPACE
[114]
FAMILY RR
[144]
OPEN
STUDY
[122C]
OPEN
STUDY
[122B]
MENS
[146]
WOMENS
[148]
JANITORS
OFFICE
[147]
OFFICE
[106]
OFFICE
[104]
OFFICE
[114A]
STAIR
[1-H]
STAIR
[1-B]
VESTIBULE
[1-A]
STAIR
[1-D]
HALLWAY
[1-C]
MECH
CHASE
[1-K]
'EW3'
RESERVE
MEDIA
[116]
(TYP)
F3
(TYP)
F3
(TYP)
F2
(TYP)
F4
(TYP)
F4
(TYP)
F4
(TYP)
F4
(TYP)
F3
(TYP)
F3
(TYP)
F3
(TYP)
F3
(TYP)
F3
(TYP)
F2
(TYP)
F2
(TYP)
F2
(TYP)
F2
F8
F8
(TYP)
F3
(TYP)
F3(TYP)
F4
(TYP)
F2
(TYP)
F2
(TYP)
F2
F11
F3
F3E F3E F3E
F3E
F3E
F3E
F3NL
F3E
F3NL
F3E
F3E F3NL
F3E
F3E
F3NL
F3E F3E
F3E
F3NL
F8E
F4E
F4E
F4E
F4EF4EF4E
F4E
F4E
F4EF4E
F4E
F3E
F3NL
(TYP)
F3
F3E F3NL
F3E
F3E
(TYP)
F2
F22
F22
F22
F8NL
F4 F4 F4
F3F3
(TYP)
F3
F7E
F3R
F3R
F3R
F3R
F3R
F3R
F3R
F3R
F11
F12
F13
F6
F6
F6
F6
F6
F6
?
?
(TYP)
F3
(TYP)
F3
F3NLF3NL
F3E F3E F3E
F3NLF3EF3NL
F3E F3E F3E
F3NLF3EF3NL
F3NL
F3E
F3NL
F3NL
F3NL
F3E
F18F18F18F18F18
F6
F6
F6
F6
F6
F6
F6
(TYP)
F3
(TYP)
F3
(TYP)
F3
(TYP)
F3
F13F13
(TYP)
F4
F4
(TYP)
F4
F8 F8 F8 F8
F8
F8
F3 F3
(TYP)
F8
(TYP)
F8
F5
F5
F5
F5
F8
F3 F3
F3 F3 F3
(TYP)
F3
F9 F9 F9
(TYP)
F9(TYP)
F9
(TYP)
F9
F14 F14
EE101
A
F15
F20 F20
F20
(TYP)
F3
F22F22F22F22
F22
F22
F22
F22
F22
F22 F22 F22 F22 F22
1LB-18
1LB-11LB-2
1LB-51LB-5
1LB-4
1LB-6
1LB-7
1LB-9
1LB-8 1LB-11
1LB-15
1LB-14
1LB-16
F3NL
F3NL
F3E
F3E
F3NL
1LB-10
1LB-12
O-1
1LB-3
1LB-13
LIGHTING AREA 'a'
LIGHTING AREA 'b'
LIGHTING AREA 'c'
a b c
LIGHTING AREA 'd'
d
F17
F17
F17
F17
F17
F17
COORDIANTE
EXACT FIXTURE
LOCATION W/
ARCHETECT PRIOR
TO ROUGH IN
8270
STATEOFIDAHO
T
ODD P A Y N EREGISTER
EDRP
OFESSIONALEN
G
I
NE
E
R
1823 E. Center
Pocatello, Idaho 83201
tel (208) 232-4439
www.payneengineeringinc.com
Engineering Inc.
Consulting Engineers
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
P.E. #:2259
10-28-2022 EE101
LIGHITNG
PLAN LEVEL1
AREA A
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
BID SET
A. REFER TO SYMBOL SCHEDULE SHEET FOR PROJECT
GENERAL NOTES AND GENERAL NOTES ASSOCIATED WITH
THE INSTALLATION OF EACH SYSTEM, INCLUDINB BUT NOT
LIMITED TO; LIGHTING, POWER, FIRE ALARM, SPECIAL
SYSTEMS, ETC.
GENERAL NOTES:
SCALE: 1/8" = 1'-0"1 LEVEL 1 LIGHITNG PLAN AREA A
NORTH16'8'0"
KEY PLAN
A
B
SCALE: 1/4" = 1'-0"A CIRCULATION DESK BACK WALL
RE
F
.
nD nD nD nD
S
nD1 S
nD1
S
nD1
S
nD1
S
nD1
S
nD1S
nD1
nD
nD
nD
nD
S
nD1
S
nD1
SnD1 S
nD1nD
nD
n1
SnD1
S
nD1
nD
C
R
nPS80
R
nPS80R
nPS80
S
nD1
SnD1
nDCnDC
R
nPS80
S
nD1
nDC
R
nPS80
S
nD1
nDC
R
nPS80
SnD1
nDC
R
nPS80
SnD1
nD
C
R
nPS80
SnD1
nD
C
R
nPS80
S
nD1
nD
C
R
nPS80
SnD1
nD
C
nD
S
nD1
SnD1 nD
n1
S
nD1
S
nD1
nD
nD
nD
nO
SnD1
SnD1
SnD1
nD
C
R
nPS80
R
nPS80
SnD1
nD
C
R
nPS80
S
nD1
nD
C
S
nD1
nD
nDCnD
S
nD1
S
nD1
R
nPS80nO
nD
SnD1
SnD1 nD
nD
SnD1
S
nD1
S
nD1
nO
M
S
CD
2
SCD2
M
16151413121110987
K
H
F
D
B
A
STORAGE
[170C]
STUDY
[170B]
STUDY
[170A]
CLASSROOM
[168]
CLASSROOM
[166]
ADJUNCT
OFFICE
[180]
OFFICE
[181]OFFICE
[182]
OFFICE
[183]
OFFICE
[184]
OFFICE
[185]OFFICE
[186]
CONFERENCE
ROOM
[158]
CONFERENCE
[188B]
COLLABORATIVE
SPACE
[188]
CLASSROOM
[162]
CLASSROOM
[164]
OFFICE
[190B]
OFFICE
[190A]
TRAINING
AREA
[190]
OFFICE
[192B]
SMALL
MEETING
[192A]
OFFICE
[160A]
OFFICE
[160B]
TUTORING
ADMIN
OPEN AREA
[160]
OFFICE
[156F]
PRACTICE
[156E]
WORKSPACE
[156]
STORAGE
[156D]
DROP IN
MATH LAB
[170]
WORKSTATIONS/
FLEX
SPACE
[192]
CLASSROOM
[172]
STUDENT
PREP
[174]
STUDY
[178]
STUDY
[179]
MATH LAB
RECEPTION
[175]
I.T. HELP
DESK
[176]
OFFICE
[188A]
STORAGE
[190C]
STORAGE
[192C]
PRACTICE
[156C]
PRACTICE
[156B]
PRACTICE
[156A]
VESTIBULE
[1-U]
ELECTRICAL
[173]
VESTIBULE
[1-Z]
MECH
[08]
ELEV
EQUIP
[08A]
ELEV
[1-T]
MEN'S
RESTROOM
[154]
WOMEN'S
RESTROOM
[152]
STAIRS
[1-N]
F1
F1
F1
F1
F1
(TYP)
F4
(TYP)
F2
(TYP)
F2
(TYP)
F3
(TYP)
F3
(TYP)
F3
(TYP)
F3
(TYP)
F2
(TYP)
F2(TYP)
F2
(TYP)
F2
(TYP)
F2
(TYP)
F3R
F3
F3
F3
F3
(TYP)
F3
(TYP)
F3
(TYP)
F3
(TYP)
F3
(TYP)
F3
(TYP)
F3
(TYP)
F3
(TYP)
F3
(TYP)
F2
(TYP)
F2
(TYP)
F2(TYP)
F2
(TYP)
F2(TYP)
F2
(TYP)
F3
(TYP)
F3
(TYP)
F2
F4F4
(TYP)
F3
(TYP)
F2
(TYP)
F2
(TYP)
F3
(TYP)
F3
(TYP)
F2
F3F3
(TYP)
F11
F8
F8
F5
F5
F10
F5
F5
F10
(TYP)
F8
F4
(TYP)
F3
F3E
(TYP)
F3R
F3RNL
F3RNL
F3E F3NL
F3EF3NL
F3NL
F3RE
F3RNL F3RE
F3RNL
F3RE
F3E
F3E
(TYP)
F3
F3E F3NL F3E
F3NL F3E
F3NL
F3E
F3NL
(TYP)
F3
F3E
F3E
F3E
F3E
F3RNL
F3E F3NL F3NL
F3E
F3E
F3E
F3E
F3E
F3E
F3E
F4E F4E
F4EF4E
(TYP)
F8
F8E
F8E
F3E
F3E
F3E
F3E
F4E F4E
F3E
F3
F3
F3E
F4 F4 F4
F11E
F11E
F1
F11F11F7E
F3
F3
F3
F3
F3E
(TYP)
F4
(TYP)
F4
(TYP)
F4
F13
(TYP)
F4
(TYP)
F4
(TYP)
F3R
(TYP)
F3
F3NLF3E
F18
F18
F18
F18
F18
F18
(TYP)
F2
F4E F4E
F4E
F4E
F4E
F4E
F4E
F4E
F4E
F4E
F4E
F4E
F4E F4E
1LA-1
1LA-3
1LA-2
1LA-5
1LA-6
1LA-9
1LA-9
1LA-11
1P-5
1LA-8
1LA-10
EE202
A
F11E
F11E1P-2
F11
F11
F11
1LA-13
8270
STATEOFIDAHO
T
ODD P A Y N EREGISTER
EDRP
OFESSIONALEN
G
I
NE
E
R
1823 E. Center
Pocatello, Idaho 83201
tel (208) 232-4439
www.payneengineeringinc.com
Engineering Inc.
Consulting Engineers
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
P.E. #:2259
10-28-2022 EE102
LIGHITNG
PLAN LEVEL1
AREA B
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
BID SET
A. REFER TO SYMBOL SCHEDULE SHEET FOR PROJECT
GENERAL NOTES AND GENERAL NOTES ASSOCIATED WITH
THE INSTALLATION OF EACH SYSTEM, INCLUDINB BUT NOT
LIMITED TO; LIGHTING, POWER, FIRE ALARM, SPECIAL
SYSTEMS, ETC.
GENERAL NOTES:
SCALE: 1/8" = 1'-0"1 LEVEL 1 LIGHITNG PLAN AREA B
NORTH
16'8'0"
KEY PLAN
A
B
S
nD1
S
nD1S
nD1
n2Dn2D
n2
D
nD
C
nD
C
SnD1
R
nPS80
S
nD1
R
nPS80
nD
C
nDCnDC
S
nD1
R
nPS80
SnD1
SnD1
nD
nD
SnD1
SnD1
nD
nD
S
nD1
S
nD1
S
nD1
n1
nD
SnD1
S
nD1
S
nD1
S
nD1
S
nD1
SnD1
SnD1
S
nD1
S
nD1
S
nD1
S
nD1SnD1
R
nPS80
R
nPS80
nD
C
nD
C
nD
nD
nDnD
nD
nDnDnD
nO
nO
nOnO
n2
D
n1
nO
nD
C
S
nD1
nO nO
S
nD1
R
nPS80
S
nD1
n1
SCD2 S
CD2
S
nD1
S
nD1
SnD1
SnD1
nD
SnD1SnD1
SnD1
SnD1
SnD1
nD
R
nPS80
R
nPS80
R
nPS80
R
nPS80
R
nPS80
R
nPS80
M
nD
M M
1
G
J
L
M
N
P
Q
E
C
2 3 4 5 61.5
ELECTRICAL
ROOM
[242]
TECH SERV
STORAGE
[2-E]
SHEET
MUSIC
[236]
LARGE
COMPUTER
CLASSROOM
[234]
OPEN
COMPUTERS
[240]
MOTHERS
[243]
OPEN
STUDY
[53]
PRESS
ROOM
[226]
SPECIAL
COLLECTIONS
[228]
VAULT
[228E]
ARCHIVE
[228D]
INSTRUCTION
2
[224]
INSTRUCTION
1
[222]
DCAM
[228B]
OFFICE
[228A]
SCANNER
[228C]
OFFICE
[232]
STUDY
(MED)
[216]
STUDY
(MED)
[214]
STUDY
(MED)
[218]
STUDY (SM)
[204]
JANITOR'S
OFFICE
[241]
OFFICE
[230]
OFFICE
[202]
STUDY (SM)
[212]STUDY (SM)
[210]
STUDY (SM)
[208]
OFFICE
[200]
MECHANICAL
[2-D]
I.T.
[245]
MEN'S
RESTROOM
[247]
WOMEN'S
RESTROOM
[248]
STAIR
[2-G]
ELEV
[2-H]
MECH
CHASE
[2-J]
STAIR
[2-A]
STAIR
[2-B]
TECH
SERVICES
[238]
F5
F5
F5
F5
F5 F5
F5
F5
F5
F5 F8
F8
F8
F8
F11
F11
F11
F11
F8
FAMILY RR
[244]
(TYP)
F3
(TYP)
F3
(TYP)
F3
(TYP)
F3
(TYP)
F3
(TYP)
F3
(TYP)
F3
(TYP)
F3
(TYP)
F3
F12
F10 F10
(TYP)
F2
(TYP)
F2
(TYP)
F3
(TYP)
F3
(TYP)
F3
(TYP)
F3
(TYP)
F3
(TYP)
F3
(TYP)
F3
F8
(TYP)
F3
(TYP)
F3
(TYP)
F3
(TYP)
F3
(TYP)
F3
(TYP)
F2
(TYP)
F2
(TYP)
F3
(TYP)
F3
(TYP)
F3
(TYP)
F3
F3
F3
F8
F8E F8NL
F3NL
F3E
F3NL
F3E
(TYP)
F3
F3E
F3E F3E
F3E
F3E
F3E
F3E
F3NL
F3E
F3E
F3NL
F3E
F3E
F3E
F3E
F3E F3E
F3E F3NL
F3EF3E
(TYP)
F3
F3E
F3E
F3E F3E
F3E
F3EF3NL
F3E
(TYP)
F3
F3E F3E
F3E F3NL
F3E F3E
F3NL F3E F3NL
F8E
F8NL
(TYP)
F3
(TYP)
F3
F3NL F3E F3NL
F3E F3E F3E
F3E F3E
F3E F3E
F3E F3NL F3E
F3NL
F3E
F3NL
F3E
F3E
F3NL
F3NL F3E
F3NLF3E
F3R
F3R
F3R
STUDY
(MED)
[206]
(TYP)
F3
F22
F22
F22
F22
F22
F4
F4
F4
F4
F4
F3
F2
F2
F8
F4 F4 F4
F12
F12F12F12F12F12
(TYP)
F2
F7E
OPEN
STUDY
[220]
(TYP)
F3
(TYP)
F3
(TYP)
F3
(TYP)
F3
(TYP)
F3
(TYP)
F3
F3EF3NLF3EF3NL
F3E F3E
F3E
F3E
F3NL
F3E
F3E
F3E
F3NL
F3E F3E
F3E
F3E
F3NLF3E
F3NL
(TYP)
F3
(TYP)
F9
(TYP)
F9
(TYP)
F9
F8 F8 F8 F8
F8 F8
F8 F8
F8
F8
F8
F8
F3
a
a
a
a
a
a
a
a
a
a
a
a
a
a
a
a
a
a
a
a
a
a
a
a
a
a
a a a
a a a
a
a a
b b b b b
b
a
b
b
2LB-13
2LB-1
2LB-1
2LB-3
2LB-7
2LB-7
2LB-12
F12
F12
2LB-9
2LB-14
2LB-6
2LB-6
2LB-8
2LB-10
F3NL
O-1
1LB-18
2LB-5
F3EF3E
a
b
ab
8270
STATEOFIDAHO
T
ODD P A Y N EREGISTER
EDRP
OFESSIONALEN
G
I
NE
E
R
1823 E. Center
Pocatello, Idaho 83201
tel (208) 232-4439
www.payneengineeringinc.com
Engineering Inc.
Consulting Engineers
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
P.E. #:2259
10-28-2022 EE103
LIGHITNG
PLAN LEVEL2
AREA A
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
BID SET
A. REFER TO SYMBOL SCHEDULE SHEET FOR PROJECT
GENERAL NOTES AND GENERAL NOTES ASSOCIATED WITH
THE INSTALLATION OF EACH SYSTEM, INCLUDINB BUT NOT
LIMITED TO; LIGHTING, POWER, FIRE ALARM, SPECIAL
SYSTEMS, ETC.
GENERAL NOTES:
SCALE: 1/8" = 1'-0"1 LEVEL 2 LIGHITNG PLAN AREA A
NORTH
16'8'0"
KEY PLAN
A
B
REF.
REF.
S
nD1
R
nPS80
nDC
n1
S
nD1
nO
nDC
S
nD1
R
nPS80
S
nD1
nD
nD
S
nD1
nD
S nD1
S
nD1 S
nD1 SnD1
nD nD
nD
nD
SnD1
SnD1
R
nPS80
nDC
nD
nD
nO
SnD1
SnD1
S
nD1
SnD1
R
nPS80
R
nPS80
nDCnDC
nD
nD
nD
nD
S
nD1
SnD1SnD1SnD1
S
nD1S
nD1
SnD1
R
nPS80
R
nPS80
nDCnDC
nD
nD
S
nD1
S
nD1
S
nD1
nD
n1
S
nD1
SnD1
nD
nDCnDC
S
nD1
S
nD1
R
nPS80
R
nPS80nO
nD
nD
SnD1 SnD1
S
nD1
SnD1
SCD2SCD2
M
M
16151413121110987
K
H
F
D
B
A
CLASSROOM
[272]
OFFICE
[288B]
ENGLISH
TRANSITION
CENTER
[288]
OPEN
TUTORING
[254]
STUDY
SKILLS
[252]
WRITING
CENTER
OPEN
TUTORING
[256]
STUDY
[269]
STUDY
[268]STUDY
[267]
STUDY
[266]
OFFICE
[265]
OFFICE
[264]
STORAGE
[270J]
STUDY
[270H]
PREP /
STORAGE
[270B]
CLASSROOM
[258]
CLASSROOM
[260]
PREP /
STORAGE
[256A]
OFFICE
[256B]
OFFICE
[256C]
OPEN
TUTORING
CENTER
[270]
ADJUNCT
OFFICE
[286]
TR / COMM.
[280]
CLASSROOM
[278]
PRE-FUNCTION
[270C]PRE-FUNCTION
[270D]
PRE-FUNCTION
[270E]
RECEPTION
[270A]
PREFUNCTION
[270F]
STUDY
[252B]
PREP /
STORAGE
[252G]
OFFICE
[252E]
STORAGE
[252F]
OFFICE
[252D]
STUDY
[252A]
STUDY
[252C]
STUDY
[270G]
ELEV
[2-R]
WOMEN'S
RESTROOM
[284]
MEN'S
RESTROOM
[282]
STAIR
[2-P]
STOR
[299]
OFFICE
[288C]
STUDY
[288D]
STUDY
[288E]STUDY
[288F]
STUDY
[288G]STORAGE
[288H]
STUDY
[288A]F8
F8
F8
F8 F8
F8
F8
F8
F8
F3R F3R
F11
F3 F3 F3 F3
(TYP)
F3
(TYP)
F2
(TYP)
F2
(TYP)
F3
(TYP)
F3
(TYP)
F2
(TYP)
F3
(TYP)
F3
(TYP)
F3
(TYP)
F3
(TYP)
F3
(TYP)
F3
(TYP)
F3
(TYP)
F4
(TYP)
F4
(TYP)
F4
(TYP)
F4
(TYP)
F3
(TYP)
F3
(TYP)
F3
(TYP)
F3(TYP)
F3
(TYP)
F3
(TYP)
F3
(TYP)
F2
(TYP)
F2
(TYP)
F3
(TYP)
F3
(TYP)
F3
(TYP)
F3
(TYP)
F2
(TYP)
F2
(TYP)
F3
(TYP)
F2
(TYP)
F3
(TYP)
F2
(TYP)
F3
(TYP)
F3
(TYP)
F3
(TYP)
F3
(TYP)
F3
F3
F5 F5
F11
F11
F3RE F3RE
F3E
F3E
F4E
F8E F8E
F8E
F3E
F3E
F3E
F3E
F3E
F3E
F3NLF3EF3E
F3NL F3E F3E
F3EF3EF3E
F3E
F3E
F3NL
F3E F3E F3E
F3EF3EF3E
F3E F3E F3E
F3E
F3E
(TYP)
F3
F3E
F3E
F3NL F3E F3NL F3E
F3E
F3E F3E
F3E F3E
F3E F3E
F3E
(TYP)
F3
(TYP)
F3
F7E
F3RNL
F3RE
F3RNL
F3RE
(TYP)
F3R
(TYP)
F3R(TYP)
F3R
(TYP)
F4
(TYP)
F3R
F4F4F4F4F4F4F4
F3R
F3NLF3E
F3EF3E
F3E F3E F3NL F3E
F3EF3EF3NL
F3E
F3E
(TYP)
F3
(TYP)
F3
(TYP)
F3
F3RE
2LA-1
2LA-62LA-7 2LA-7
2LA-4
2LA-5
2LA-2
2LA-9
2LA-8
2LA-3
2LA-10
2LA-12
F3RNL
F3RE
F3RNL
F3R
F3R
8270
STATEOFIDAHO
T
ODD P A Y N EREGISTER
EDRP
OFESSIONALEN
G
I
NE
E
R
1823 E. Center
Pocatello, Idaho 83201
tel (208) 232-4439
www.payneengineeringinc.com
Engineering Inc.
Consulting Engineers
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
P.E. #:2259
10-28-2022 EE104
LIGHITNG
PLAN LEVEL2
AREA B
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
BID SET
A. REFER TO SYMBOL SCHEDULE SHEET FOR PROJECT
GENERAL NOTES AND GENERAL NOTES ASSOCIATED WITH
THE INSTALLATION OF EACH SYSTEM, INCLUDINB BUT NOT
LIMITED TO; LIGHTING, POWER, FIRE ALARM, SPECIAL
SYSTEMS, ETC.
GENERAL NOTES:
SCALE: 1/8" = 1'-0"1 LEVEL 2 LIGHITNG PLAN AREA B
NORTH
16'8'0"
KEY PLAN
A
B
nO
nD
nO
nD nD nD
SnD1 SnD1
SnD1
nO
nDnDnD
S
nD1
SnD1SnD1SnD1
nD
nD
S
nD1
S
nD1
S
nD1
S
nD1
S
nD1
nD
nD
nD
nD
nD
nD
SnD1SnD1S
nD1
nO
nD
C
SnD1
R
nPS80
R
nPS80
SnD1
nD
C
nD
S
nD1
S
nD1
S
nD1
nD
nD
SnD1
SnD1
R
nPS80
nD
C
nO
nO
SnD1
R
nPS80
nDC
nD
S
nD1
S
nD1
nD
nD
S
nD1
S
nD1
nD
nD
S
nD1
S
nD1
nD
S
CD2
S
CD2
nD
nD
nD
S
nD1
S
nD1
SnD1
SnD1
SnD1
SnD1
nD
SnD1
SnD1
S
CD2
MM
1
K
H
F
D
G
J
L
M
N
P
Q
E
C
2 3 4 5 61.5
STUDY (SM)
[332]
STUDY (SM)
[336]
STUDY (SM)
[314]
STUDY (SM)
[316]
ELEC
[364]
STUDY (SM)
[320]
STUDY (SM)
[338]
STUDY (SM)
[318]
ELECTRICAL
[324B]
STUDY (SM)
[334]
OFFICE
[310]
OFFICE
[312]
JUVENILE
[300]
STORAGE
[306]
STUDY
(MED)
[304]
STUDY
(MED)
[302]
KIDS PLAY
[344C]
MOTHERS
ROOM
[344A]RESTROOM
[344B]
FAMILY
STUDY
[344]
OPEN
STUDY
[362]
Bridge
Connection
[-]
BRIDGE
CONNECTION
[3-A]
STAIR 1
[3-B]
MENS
[368]WOMENS
[366]
TEST RM
[378]
STUDY (SM)
[330]
Janitors
Closet
[376]
OFFICE
[322]
MAC EQUIP
[324A]
STUDY (LG)
[328]
STUDY (LG)
[326]
MAC LAB
[324]
TEST RM
[374]
STUDY (SM)
[340]
ELECTRICAL
[308]
STORAGE
[352]
TEST RM
[382]
TEST RM
[380]
TEST RM
[372]
TEST RM
[370]
TEST RM
[360]
TEST RM
[358]
TEST RM
[356]
TEST RM
[350]
TEST RM
[348]
TEST RM
[346]
MECH
CHASE
[3-E]
MECH
[3-D]
STAIRS
[3-C]
STAIR
[3-F]ELEV
[3-G]
MECH
CHASE
[3-H]
(TYP)
F4
F8
F3 F3 F3
F3
F11
F3
F3F3
F8
F3
F3
F3
F8 F8 F8
F3
F3
F3
F11
F11
(TYP)
F3
(TYP)
F3
(TYP)
F3
(TYP)
F3
(TYP)
F3
(TYP)
F3
(TYP)
F3
(TYP)
F3
(TYP)
F3
(TYP)
F3
(TYP)
F3
(TYP)
F3(TYP)
F3
(TYP)
F3
F8
F8
(TYP)
F2
(TYP)
F2
(TYP)
F3
(TYP)
F3
(TYP)
F3
(TYP)
F3
(TYP)
F2
(TYP)
F3
(TYP)
F2
(TYP)
F3
(TYP)
F3
(TYP)
F3
(TYP)
F3
(TYP)
F3
(TYP)
F3
F3NLF3EF3NLF3EF3NL
(TYP)
F3
F3E
F3E
F3E
F3E
F3NL
F3E
F3E
F3E
F3NLF3E
F4E F4E
F8E
F8E
F8E
F8
F8
F8
F8
F8
F8
F8E
F3E F3E
F3E F3E
F3E F3E
F3E
F3E
(TYP)
F3
(TYP)
F3
F3E
F3E F3NLF3EF3NLF3NL
F3E
F3EF3NL
F3E F3E F3E F3E F3E
F3E F3E
F8E F8E
F8E F8E
F8NL
F8E
F8E
(TYP)
F3
F3E F3E
F3E F3E
F3E
F3E
F3E
F3E
F3E
F3E
F3E
F3E
F3E
F3
F3
F3NL
OPEN
STUDY
[383]
F3E
F11E
F7E
F3E
(TYP)
F9
F3NL
(TYP)
F3
F3E
(TYP)
F4
F22F22F22F22F22
F22
F22
F22
(TYP)
F3
F3NL
F3EF3E
F8
F7E
(TYP)
F3
(TYP)
F3
(TYP)
F9
(TYP)
F9
(TYP)
F9
F4 F4 F4
(TYP)
F9
(TYP)
F9
(TYP)
F9
(TYP)
F9
(TYP)
F9
(TYP)
F9
(TYP)
F9
(TYP)
F9
(TYP)
F9
(TYP)
F3
(TYP)
F3 F19F19F19
F19 F19 F19
3LA-7 3LA-6
3LA-4
3LA-9
1LB-9
3LA-9
3LA-11
3LA-5
3LA-8
3LA-3
3LA-13
3LA-12
F3EF3E
F3EF3E
(TYP)
F3
(TYP)
F3
O-1
1LB-18
(TYP)
F3
3LA-10
a b
a
b
8270
STATEOFIDAHO
T
ODD P A Y N EREGISTER
EDRP
OFESSIONALEN
G
I
NE
E
R
1823 E. Center
Pocatello, Idaho 83201
tel (208) 232-4439
www.payneengineeringinc.com
Engineering Inc.
Consulting Engineers
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
P.E. #:2259
10-28-2022 EE105
LIGHITNG
PLAN LEVEL
3
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
BID SET
A. REFER TO SYMBOL SCHEDULE SHEET FOR PROJECT
GENERAL NOTES AND GENERAL NOTES ASSOCIATED WITH
THE INSTALLATION OF EACH SYSTEM, INCLUDINB BUT NOT
LIMITED TO; LIGHTING, POWER, FIRE ALARM, SPECIAL
SYSTEMS, ETC.
GENERAL NOTES:
SCALE: 1/8" = 1'-0"1 LEVEL 3 LIGHTING PLAN
NORTH
16'8'0"
REF.REF.
M
J
M
M
M
M
M
M
M
FBT
G
J
E
C
2 3 4 5 6
TIER 2
[016]
OFFICE
[010]
OFFICE
[026A]
OFFICE
[011]
BREAK
ROOM
[013]
'O'
'EMW''EME'
'ATS WEST''ATS EAST'
'MC'
SHORT
TERM
STORAGE
[028]
OFFICE
[012]
TECH
ROOM
[024]
STUDENTS
[026F]
OFFICE
[026C]
OPS
[022]
MECH
ROOM
[030]
STAIR
[0-E]
STORAGE
[032]
MECH
CHASE
[O-F]
STAIR
[0-E]ELEV
[0-J]
ELECTRICAL
[038]
CUSTODIAL
[036]
MECH
CHASE
[034]
BDF
[040]
CUSTODIAL
STORAGE
[042]
STORAGE
[044]
OFFICE
[018]
OFFICE
[020]
QA
[022A]
MEN'S RR
[015]
WOMEN'S
RR
[014]
IMAGING
AND
STORAGE
[009]
OFFICE
[026B]
OFFICE
[026D]
OFFICE
[026E]
AC
'E''UPS'
2D-4
AC
4D-4
AC
AC
4D-4
AC2D-4
ACAC
4D-4
ACAC
4D-4
ACAC
4D-4
AC
'CP7'
2D-4
3D-4
1D-4 1D-4 1D-4
1D-4
1D-4
2D-42D-42D-4AC AC AC
2D-4
1
AC
2D-4
ACAC
3D-4
ACAC
AC
2D-4
AC
1D-4
1D-4
EE200
A
CP7-34
CP7-9
CP7-112
CP7-13
CP7-17
CP7-12
CP7-10
CP7-8CP7-14
CP7-16CP7-18
CP7-19
CP7-21
CP7-23
CP7-27
CP7-25CP7-24
CP7-29
CP7-22
CP7-30
CP7-31
CP7-28
CP7-26
2D-4
2D-4
2D-4
3D-4 2D-4
1D-4
3D-E
3D-E
3D-E
R-3
R-1
R-5
1D-E
R-2
1D-4
1D-4
2D-4
2D-4
'R'
2D-4
2D-4
2D-4
1D-E
R-4
2D-4
CP7-20
1D-4
1D-4
'DB1''P'
1D-4
CP7-33 CP7-35
CP7-32
PROVIDE AND
ISNTALL (4) NEW
BREAKERS (NEED TO
DETERMINE SIZE)
FOR THE TWO
CHILLER PUMPS AND
THE TWO CW PUMPS
INSTALL NEW
CIRCUIT TO VFD
THEN TO PUMP AND
MAKE ALL
CONNECTIONS
INSTALL VFD'S ON
NEW RACK
ADJACENT TO THE
EXISTING VFD'S
SCU-040
SAC-040
(E)CHWP-8
(E)CHWP-7
HWP-10
HWP-9
(E)CHWP-6
(E)CHWP-5
R-6
R-7
FCP-1
'(E) VFD
CHWP-5'
'(E) VFD
CHWP-6'
'VFD CHWP-7'
'VFD CHWP-8'
'V
F
D
H
W
P
-9'
'V
F
D
H
W
P
-10
'
R-9
'ACCESS
CONTROL
HEAD END'
34
5
5
5
5
5
5
6
R-11
CP7-6
CP7-7
CP7-4
CP7-4 CP7-4
8270
STATEOFIDAHO
T
ODD P A Y N EREGISTER
EDRP
OFESSIONALEN
G
I
NE
E
R
1823 E. Center
Pocatello, Idaho 83201
tel (208) 232-4439
www.payneengineeringinc.com
Engineering Inc.
Consulting Engineers
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
P.E. #:2259
10-28-2022 EE200
POWER
PLAN LEVEL
0
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
BID SET
A. REFER TO SYMBOL SCHEDULE SHEET FOR PROJECT
GENERAL NOTES AND GENERAL NOTES ASSOCIATED WITH
THE INSTALLATION OF EACH SYSTEM, INCLUDINB BUT NOT
LIMITED TO; LIGHTING, POWER, FIRE ALARM, SPECIAL
SYSTEMS, ETC.
GENERAL NOTES:
KEY NOTES:#
1 MOUNT BEHIND TV, COORDINATE MOUNTING W/ TV
MOUNTING BRACKET PRIOR TO ROUGH IN. PROVIDE
EXTRA DEEP BOX SUCH AS, HUBBELL HBL260, W/ SINGLE
GANG MUD RING W/ 1 1/4" C., TO ABOVE ACCESSIBLE
CEILING. COORDINATE W/ KENDEN JENSEN (CAMPUS AV)
PRIOR TO ROUGH IN.
2 LOCATE RECEPTACLE BEHIND DRINKING FOUNTAIN
HOUSING.
3 PROVIDE AND INSTALL NEW (2) 200A 3P CIRCUIT
BREAKER IN PANEL DB1 FOR CHWP - 7 AND CHWP - 8.
4 PROVIDE AND INSTALL NEW 50A 3P CIRCUIT BREAKER
AND NEW 20A 3P CIRCUIT BREAKER IN PANEL P FOR
HWP-9 AND HWP-10.
5 ROUTE NEW MOTOR/PUMP CIRCUIT THROUGH VFD. MAKE
ALL REQUIRED CONNECTIONS.
6 FLOOR BOX TO BE INSTALLED IN EXISTING CONCRETE
SLAB. EXISTING SLAB TO BE CUT AND PATCHED TO
ACCOMMODATE FLOOR BOX AND CONDUIT
INSTALLATION.
SCALE: 1/8" = 1'-0"1 LEVEL 0 POWER PLAN
NORTH
16'8'0"
SCALE: 1/2" = 1'-0"A BREAK ROOM 013
ELECTRICAL FLOORBOX SCHEDULE
ID DESCRIPTION MFGR. FLOORBOX p/n COVERPLATE p/n
POWER
DEVICES
DATA
DEVICES NOTES
FB2S FIRE RATED POKE-THRU FLOORBOX, HUBBELL S1PTFIT S1CFCXX (1) DUPLEX
RECPT.
(2) RJ45 1,2,3
FBCP FIRE RATED POKE-THRU FLOORBOX, W/ 1
1/4" KNOCK OUT
HUBBELL S1R6PTFIT S1CFCXX (1) DUPLEX
RECPT.
BRUSH
PLATE
1,2,3
FBFF FIRE RATED POKE-THRU FLOORBOX,
FURNITURE FEED
HUBBELL S1PTFIT S1SPFFA2 1,2,3
FBGC ON GRADE FLOOR BOX LEGRAND EFB6S-OG-1-1/
4KO
(1) DUPLEX
RECPT.
BRUSH
PLATE
1,2,3
FBP FIRE RATED POKE-THRU FLOORBOX, HUBBELL S1PTFIT S1CFCXX (2) DUPLEX
RECPT.
1,2,3
FBT 2-GANG, MULTI-SERVICE CONCRETE
FLOORBOX, 3" MIN. POUR
HUBBELL CFB2G30CR 24GCCVRXXX (2) DUPLEX
RECPT.
1,2,3
1. PROVIDE REQUIRED SUB-PLATES FOR INSTALLATION OF POWER, DATA AND AV DEVICES.
2. E.C. SHALL FIELD LOCATE EXACT PLACEMENT OF FLOORBOX WITH ARCHITECT/OWNER PRIOR TO INSTALLATION.
3. PROVIDE CONDUIT (SIZE AS INDICATED ON DRAWINGS) TO ACCESSIBLE CEILING SPACE FOR ROUTING OF DATA AND/OR
LOW VOLTAGE CABLING.
FLOORBOX SCHEDULE NOTES:
SYMBOL LOCATIONS FOR FLOOR BOXES ARE APPROXIMATE. THE EXACT LOCATION OF EACH FLOOR BOX WITHIN EACH PAN
OF THE WAFFLE SLAB SHALL BE COORDINATED WITH THE ARCHITECT AND OWNER PRIOR TO ROUGH-IN. CONTRACTOR TO
VISUALLY LAY OUT THE LOCATIONS OF THE FURNITURE AND THE WAFFLE SLAB PATTERN ON EACH FLOOR THEN MARK THE
PROPOSED LOCATION OF EACH FLOOR BOX FOR REVIEW BY THE ARCHITECT AND OWNER. AFTER OWNER APPROVAL OF THE
LAYOUT, CORE DRILLING AND ROUGH IN CAN PROCEED.
GENERAL NOTES:
PUBLIC ADDRESS SYSTEM:
FOR BIDDING PURPOSE:
• E.C. SHALL INCLUDE A CASH ALLOWANCE FOR $250,000.00 TO
COVER ALL MATERIALS, LABOR, PROGRAMMING & TRAINING
REQUIRED TO INSTALL A COMPLETE AND OPERABLE PUBLIC
ADDRESS SYSTEM IN THIS FACILITY. PA SYSTEM DESIGN
WILL BE PROVIDED TO THE CONTRACTOR PRIOR TO
COMMENCEMENT OF CONSTRUCTION.
• E.C. SHALL CAREFULLY DISCONNECT AND REMOVE ALL
EXISTING PUBLIC ADDRESS SYSTEM SPEAKERS, CONTROLS,
HEAD END, ETC. REMOVE ALL ASSOCIATED CABLE, WIRE,
AND CONDUIT. CLEAN, BOX, AND DELIVER ALL SPEAKERS
AND HEAD END EQUIPMENT TO OWNER SPECIFIED
LOCATION.
RE
F
.
FBP
FBP
FBP
FBP
FBT
FBT
FBT
FBT
FBT
J
FBT
J
J
J
J
J
J
FBP FBP FBP
FBT
FBT
SS
SS
SS
SS
SS
SS
FBP
FBP
FBPFBPFBP
FBCP
PC
PCPC
1
G
J
L
M
N
P
Q
E
C
2 3 4 5 61.5
CHECK-IN
[112]
OFFICE
[129]
OFFICE
[130]
OFFICE
[131]
STUDY
(MED)
[132]
OFFICE
[136]
RECEPTION
[134]
OFFICE
[138]
CONFERENCE
ROOM
[140]
BREAKROOM
[142]STUDY (SM)
[128]
STUDY
(MED)
[124]
STUDY
(MED)
[125]
STUDY (SM)
[126]
STUDY (SM)
[127]
OPEN
STUDY
[122A]
HD BOOK
COLLECTION
[122]
OPEN
STUDY
[120A]
VESTIBULE
[1-F]
CIRCULATION
RECEPTION
[110]
OFFICE
[108]
INTER
LIBRARY
LOAN
WORKSPACE
[114]
FAMILY RR
[144]
OPEN
STUDY
[122C]
OPEN
STUDY
[122B]
OPEN
STUDY
[118]
MENS
[146]
WOMENS
[148]
JANITORS
OFFICE
[147]
'EW3'
OFFICE
[106]
'C
P
9
'
'C
P
1
0
'
'1
L
B
'
'C
P
1
1
'
OFFICE
[104]
OFFICE
[114A]
STAIR
[1-H]
STAIR
[1-B]
VESTIBULE
[1-A]
STAIR
[1-D]
HALLWAY
[1-C]
MECH
CHASE
[1-K]
1D-4
1D-4
1D-4
1D-4
1D-4
1D-4
1D-4
RESERVE
MEDIA
[116]
1D-4 1D-4
2D-4
2D-4
1D-4
2D-4
2D-4
1D-4
1D-4
2D-4
2D-4
2D-4
2D-4
2D-4
2D-4
2D-4
ELEC
ROOM
[102]
ACAC
1D-4
2D-42D-4
2D-4
1
3D-4
2D-4
AC
ACAC
2D-4
1D-4
AC
2
2
2
2
2
2
'B'
4D-4
4D-4
4D-4
AC AC
AC
AC
1D-4
3 3
CP9-3
CP9-1
CP9-5
CP9-2
CP9-11
CP9-9
CP9-7
CP9-4
CP9-8
CP9-10
CP9-12
CP9-13
CP9-17
CP9-15
EW3-1
EW3-1
CP9-14
CP9-18
B-3
CP11-1
CP11-3
CP11-2
CP11-4
CP11-6 CP11-7
CP11-9
CP11-11
CP11-8
CP11-10
CP11-12
CP11-15 CP11-17CP11-13
CP11-14 CP11-16
EE201
2
CP10-1
CP10-5
ACAC
CP10-4
CP10-7
CP10-9
CP10-11
CP10-13
CP10-2
CP10-6
FCU-1
CH-3
CH-2
CH-1
B-1
CP11-5
2D-4
2D-4
2D-4
2D-4
2D-4
2D-4
CP9-19
AC
AC
AC
AC
AC
1D-4
4
5
5
5
5
5
5
5
5
6
6
6
CP10-8
CP10-15
CP9-214
CP11-18
EW3-7
2D-4
CP9-6
7
AC
2D-4
CP10-8 CP10-10
CP10-12
CP10-8
8270
STATEOFIDAHO
T
ODD P A Y N EREGISTER
EDRP
OFESSIONALEN
G
I
NE
E
R
1823 E. Center
Pocatello, Idaho 83201
tel (208) 232-4439
www.payneengineeringinc.com
Engineering Inc.
Consulting Engineers
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
P.E. #:2259
10-28-2022 EE201
POWER
PLAN LEVEL
1 AREA A
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
BID SET
A. REFER TO SYMBOL SCHEDULE SHEET FOR PROJECT
GENERAL NOTES AND GENERAL NOTES ASSOCIATED WITH
THE INSTALLATION OF EACH SYSTEM, INCLUDINB BUT NOT
LIMITED TO; LIGHTING, POWER, FIRE ALARM, SPECIAL
SYSTEMS, ETC.
GENERAL NOTES:
KEY NOTES:#
1 MOUNT BEHIND TV, COORDINATE MOUNTING W/ TV
MOUNTING BRACKET PRIOR TO ROUGH IN. PROVIDE
EXTRA DEEP BOX, SUCH AS HUBBELL HBL260 BOX, W/
SINGLE GANG MUD RING W/ 1 1/4" C., TO ABOVE
ACCESSIBLE CEILING, AND A 1 1/4" C., TO UNDER
CONFERENCE TABLE. COORDINATE W/ KENDEN JENSEN
(CAMPUS AV) PRIOR TO ROUGH IN.
2 MOUNT BEHIND TV, COORDINATE MOUNTING W/ TV
MOUNTING BRACKET PRIOR TO ROUGH IN. PROVIDE
EXTRA DEEP BOX SUCH AS, HUBBELL HBL260, W/ SINGLE
GANG MUD RING W/ 1 1/4" C., TO ABOVE ACCESSIBLE
CEILING. COORDINATE W/ KENDEN JENSEN (CAMPUS AV)
PRIOR TO ROUGH IN.
3 MOUNT RECEPTACLES HORIZONTALLY.
4 LOCATE RECEPTACLE BEHIND DRINKING FOUNTAIN
HOUSING.
5 FLOOR BOX TO BE INSTALLED IN EXISTING CONCRETE
SLAB. EXISTING SLAB TO BE CUT AND PATCHED TO
ACCOMMODATE FLOOR BOX AND CONDUIT
INSTALLATION.
6 CONNECTION TO AUTOMATIC ADA DOORS; FIELD VERIFY
CONNECTION LOCATION AND REQUIREMENTS WITH
EQUIPMENT INSTALLERS. PROVIDE ALL REQUIRED
ROUGH-IN AND CONNECTIONS TO PUSH-BUTTONS.
7 PROVIDE AND INSTALL SECURITY PANIC BUTTON,
INSTALL 1" C., TO ABOVE ACCESSIBLE CEILING. CONNECT
BUTTON TO CAMPUS SECURITY.
SCALE: 1/8" = 1'-0"1 LEVEL 1 POWER PLAN AREA A
NORTH
16'8'0"
KEY PLAN
A
B
SCALE: 1/2" = 1'-0"2 BREAK ROOM 142
PUBLIC ADDRESS SYSTEM:
FOR BIDDING PURPOSE:
• E.C. SHALL INCLUDE A CASH ALLOWANCE FOR $250,000.00 TO
COVER ALL MATERIALS, LABOR, PROGRAMMING & TRAINING
REQUIRED TO INSTALL A COMPLETE AND OPERABLE PUBLIC
ADDRESS SYSTEM IN THIS FACILITY. PA SYSTEM DESIGN
WILL BE PROVIDED TO THE CONTRACTOR PRIOR TO
COMMENCEMENT OF CONSTRUCTION.
• E.C. SHALL CAREFULLY DISCONNECT AND REMOVE ALL
EXISTING PUBLIC ADDRESS SYSTEM SPEAKERS, CONTROLS,
HEAD END, ETC. REMOVE ALL ASSOCIATED CABLE, WIRE,
AND CONDUIT. CLEAN, BOX, AND DELIVER ALL SPEAKERS
AND HEAD END EQUIPMENT TO OWNER SPECIFIED
LOCATION.
RE
F
.
J
J
FBT FBT FBT
FBT FBT FBT
FBT
FBT
FBT
FBT FBT FBT
FBT FBT FBT
J
J
J
J
J
J
J
J
J
FBGC
PC
M M M M
MM
J
16151413121110987
K
H
F
D
B
A
STORAGE
[170C]
STUDY
[170B]
STUDY
[170A]
CLASSROOM
[168]
CLASSROOM
[166]
ADJUNCT
OFFICE
[180]
OFFICE
[181]
OFFICE
[182]
OFFICE
[183]OFFICE
[184]
OFFICE
[185]
OFFICE
[186]
CONFERENCE
ROOM
[158]
CONFERENCE
[188B]
COLLABORATIVE
SPACE
[188]
CLASSROOM
[162]CLASSROOM
[164]
OFFICE
[190B]
OFFICE
[190A]
TRAINING
AREA
[190]
OFFICE
[192B]
SMALL
MEETING
[192A]
OFFICE
[160A]
OFFICE
[160B]
TUTORING
ADMIN
OPEN AREA
[160]
OFFICE
[156F]PRACTICE
[156E]
WORKSPACE
[156]
STORAGE
[156D]
DROP IN
MATH LAB
[170]
WORKSTATIONS/
FLEX
SPACE
[192]
CLASSROOM
[172]
STUDENT
PREP
[174]
STUDY
[178]
STUDY
[179]
MATH LAB
RECEPTION
[175]
I.T. HELP
DESK
[176]
OFFICE
[188A]
'1
A
'
'1
L
A
'
'C
P
1
'
'C
P
2
'
'C
P
3
'
'C
P
4
'
'C
C
'
'EE''1P'
STORAGE
[190C]
STORAGE
[192C]
PRACTICE
[156C]
PRACTICE
[156B]
PRACTICE
[156A]
VESTIBULE
[1-U]
ELECTRICAL
[173]
VESTIBULE
[1-Z]
MECH
[08]
ELEV
EQUIP
[08A]
ELEV
[1-T]
MEN'S
RESTROOM
[154]
WOMEN'S
RESTROOM
[152]
1D-4
1D-4 1D-4
1D-4
1D-4
1D-4
1D-4
2D-4
6D-5 6D-5
6D-5
6D-5
1D-4
1D-4
1D-4
1D-4
1D-4
2D-4
2D-4
6D-5
3D-4
3D-4
2D-4
3D-4
3D-43D-4
3D-43D-4
1D-4
AC
AC
AC
AC
AC
AC
1D-4
1D-4
1D-4
1D-4
1D-4
3D-4
2D-4
2D-4
2D-4
1D-4
1D-4
1D-4
4D-4
2D-42D-42D-4
2D-4
2D-4
2D-4
2D-4
1D-4
1D-4
2D-4
2D-4
2D-4
2D-4
2D-4
1D-4
'M (EAST)'
1
1
1
1
1
2
3
1
3
3
3
2D-4
2D-4
1
1D-4
1D-4
1D-4
1D-4 1D-4 1D-4 1D-4
3
6D-5
3
AC
'ELEVATOR'
2D-4
2D-4
6D-5
3
AC
2D-4
4 1A-1
1A-5
1A-3
1A-2 1A-4
1A-6
1A-9
1A-7
1A-11
1A-30
1A-10
1A-12
1A-151A-13
1A-17
1A-14
1A-16
1A-18
1A-23
1A-221A-24
5
CP4-7
1A-261A-29
CP1-5
CP1-3CP1-1
CP1-4
CP1-6
CP1-2
CP1-7
CP1-11
CP1-9 CP1-12CP1-10
CP1-8
1D-E
1D-E
1D-E
CP1-13
CP1-15
CP1-16
CP1-18
CP1-14
CP1-17
CP1-19
CP1-24
CP1-21 CP2-6
CP2-1
CP2-3
CP2-5
CP2-2
CP2-4
CP2-7
CP2-9
CP2-11
CP2-8
CP2-10CP2-12
CP2-13
CP2-15
CP2-14
CP2-17CP2-16
CP2-18
4
CP2-23
CP2-19CP2-21
EE-1
CP3-5
CP3-1CP3-3
CP3-2
CP3-6
CP3-7
CP3-9
CP3-11
1P-11P-3
CH-5CH-4
CH-6
CH-7
CP2-20
CP4-2
CP4-5
CP4-3
6
2D-4
2D-4
2D-4
M/42"
1A-28
2D-4
1A-8
1A-19
EE202
A
CP4-4
1A-21
1A-25
1A-20
1D-4
M/44"CP4-9
2D-4
AC
2D-4
7
CP1-20
8
9
9 9
9 9
9
9
10 10 10
10
10 10
1010
10
10
10
1010
10
10
9
9
1P-4
4
11
11
CP3-4
(E) HWP-1
(E) HWP-2
(E) P-3
(E) P-4
'(E) VFD P-3'
'(E) VFD P-4'
'(E) VFD SNOW
MELT'
'V
F
D
H
W
P
-1'
'V
F
D
H
W
P
-2'
CP1-22
CP3-8
(E) SHWP-2(E) SHWP-1
12
EE-9
13
'MM'1D-4
14
14
AC AC
AC
1D-4
5
CP4-6
CP4-4
CP4-4
8270
STATEOFIDAHO
T
ODD P A Y N EREGISTER
EDRP
OFESSIONALEN
G
I
NE
E
R
1823 E. Center
Pocatello, Idaho 83201
tel (208) 232-4439
www.payneengineeringinc.com
Engineering Inc.
Consulting Engineers
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
P.E. #:2259
10-28-2022 EE202
POWER
PLAN LEVEL
1 AREA B
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
BID SET
A. REFER TO SYMBOL SCHEDULE SHEET FOR PROJECT
GENERAL NOTES AND GENERAL NOTES ASSOCIATED WITH
THE INSTALLATION OF EACH SYSTEM, INCLUDINB BUT NOT
LIMITED TO; LIGHTING, POWER, FIRE ALARM, SPECIAL
SYSTEMS, ETC.
GENERAL NOTES:
KEY NOTES:#
1 MOUNT BEHIND TV, COORDINATE MOUNTING W/ TV
MOUNTING BRACKET PRIOR TO ROUGH IN. PROVIDE
EXTRA DEEP BOX SUCH AS, HUBBELL HBL260, W/ SINGLE
GANG MUD RING W/ 1 1/4" C., TO ABOVE ACCESSIBLE
CEILING. COORDINATE W/ KENDEN JENSEN (CAMPUS AV)
PRIOR TO ROUGH IN.
2 MOUNT BEHIND TV, COORDINATE MOUNTING W/ TV
MOUNTING BRACKET PRIOR TO ROUGH IN. PROVIDE
EXTRA DEEP BOX, SUCH AS HUBBELL HBL260 BOX, W/
SINGLE GANG MUD RING W/ 1 1/4" C., TO ABOVE
ACCESSIBLE CEILING, AND A 1 1/4" C., TO UNDER
CONFERENCE TABLE. COORDINATE W/ KENDEN JENSEN
(CAMPUS AV) PRIOR TO ROUGH IN.
3 SLIM LINE AV SYSTEM CABINET. PROVIDE (2) DUPLEX
OUTLETS IN CABINET, EXTRA-DEEP BOX WITH 1 1/2"
CONDUIT TO ABOVE ACCESSIBLE CEILING FOR DATA/AV
CABLING. COORDINATE EXACT PLACEMENT OF BOXES
WITH CABINET AND KENDEN JENSEN (CAMPUS AV) PRIOR
TO ROUGH IN. PROVIDE A #10 GREEN INSULATED
GROUND CONDUCTOR FROM CABINET TO NEAREST
ELECTRICAL ROOM GROUND BAR. FIELD VERIFY FINAL
LOCATION PRIOR TO ROUGH-IN.
4 LOCATE RECEPTACLE BEHIND DRINKING FOUNTAIN
HOUSING.
5 MOUNT BEHIND TV, COORDINATE MOUNTING W/ TV
MOUNTING BRACKET PRIOR TO ROUGH IN. PROVIDE AN
EXTRA DEEP BOX, SUCH AS HUBBELL HBL260 BOX, W/
SINGLE GANG MUD RING W/ 1 1/4" C., TO ABOVE
ACCESSIBLE CEILING. COORDINATE W/ KENDEN JENSEN
(CAMPUS AV) PRIOR TO ROUGH IN.
6 PROVIDE HEAT TRACING FOR SCUPPER/DRAIN. WHERE
DRAIN PIPES EXTEND INTO UNCONDITIONED SPACE,
HEAT TRACE SHALL EXTEND DOWN PIPE AND OUT END
OF DOWNSPOUT APPROX. 6". EXACT TAPE LENGTH TO BE
DETERMINED IN FIELD. UTILIZE RAYCHEM 120V, GM-1XT
CABLE. PROVIDE ALL COMPONENTS FOR A COMPLETE
INSTALLATION INCLUDING BUT NOT LIMITED TO: POWER
CONNECTORS, JUNCTION BOX, CABLE END SEALS,
CABLE SUPPORT CLIPS, ETC. UTILIZE GFEPD TYPE
CIRCUIT BREAKERS FOR ALL HEAT TRACE CIRCUITS.
7 PROVIDE AND INSTALL SECURITY PANIC BUTTON,
INSTALL 1" C., TO ABOVE ACCESSIBLE CEILING. CONNECT
BUTTON TO CAMPUS SECURITY.
8 HEAT TRACE CONTACT. POWER HEAT TRACE FROM
GFEPD BREAKER THROUGH CONTACT; CONTROL WITH
POWER LINK CIRCUIT.
9 RECEPTACLE MOUNTED FLUSH IN CEILING FOR
OVERHEAD PROJECTOR, VERIFY EXACT LOCATION WITH
OWNER PRIOR TO ROUGH-IN. INSTALL J-BOX ABOVE
CEILING MOUNTED TO STRUCTURE WITH A 10FT MC
CABLE WHIP TO RECEPTACLE.
10 FLOOR BOX TO BE INSTALLED IN EXISTING CONCRETE
SLAB. EXISTING SLAB TO BE CUT AND PATCHED TO
ACCOMMODATE FLOOR BOX AND CONDUIT
INSTALLATION.
11 CONNECTION TO AUTOMATIC ADA DOORS; FIELD VERIFY
CONNECTION LOCATION AND REQUIREMENTS WITH
EQUIPMENT INSTALLERS. PROVIDE ALL REQUIRED
ROUGH-IN AND CONNECTIONS TO PUSH-BUTTONS.
12 PROVIDE AND INSTALL DATA CABLE FOR POWER LOGIC
METERING. COORDINATE EXACT TERMINATION
LOCATION WITH NEW SWITCHGEAR.
13 E.C. SHALL ORIENT PANEL AND VFD'S AS NECESSARY TO
FIT THE SPACE, PROVIDE RACK MOUNTING EQUIPMENT
IF NEEDED.
14 ROUTE NEW MOTOR/PUMP CIRCUIT THROUGH VFD. MAKE
ALL REQUIRED CONNECTIONS.
SCALE: 1/8" = 1'-0"1 LEVEL 1 POWER PLAN AREA B
NORTH
16'8'0"
KEY PLAN
A
B
SCALE: 1/2" = 1'-0"A FLEX SPACE 192
PUBLIC ADDRESS SYSTEM:
FOR BIDDING PURPOSE:
• E.C. SHALL INCLUDE A CASH ALLOWANCE FOR $250,000.00 TO
COVER ALL MATERIALS, LABOR, PROGRAMMING & TRAINING
REQUIRED TO INSTALL A COMPLETE AND OPERABLE PUBLIC
ADDRESS SYSTEM IN THIS FACILITY. PA SYSTEM DESIGN
WILL BE PROVIDED TO THE CONTRACTOR PRIOR TO
COMMENCEMENT OF CONSTRUCTION.
• E.C. SHALL CAREFULLY DISCONNECT AND REMOVE ALL
EXISTING PUBLIC ADDRESS SYSTEM SPEAKERS, CONTROLS,
HEAD END, ETC. REMOVE ALL ASSOCIATED CABLE, WIRE,
AND CONDUIT. CLEAN, BOX, AND DELIVER ALL SPEAKERS
AND HEAD END EQUIPMENT TO OWNER SPECIFIED
LOCATION.
FBP FBP
FBP FBP
FBP FBP
FBP FBP
FB2S
FB2S
FB2S
FB2S
FBP
FBP
FBP
FBP
FBP
FBP
FBP
FBP
FBP FBP
FBFF
FBFF
FBFF FBFF
FBFF
FBP FBP
FBP
FBP
FBP FBP
J J J J J J J
J
M M
FBP
FBP
CR CR
FF
SS
SSSSSSSSSSSS
FBP
FB2S
FBP
FBP
FBP
FBP
FBP
FBP
FBP
FBP
FBP
FBP
CS
SS
J
J
J
J
M
S H
PC
PC
J
1
G
J
L
M
N
P
Q
E
C
2 3 4 5 61.5
ELECTRICAL
ROOM
[242]
TECH
SERVICES
[238]
SHEET
MUSIC
[236]
LARGE
COMPUTER
CLASSROOM
[234]
OPEN
COMPUTERS
[240]
MOTHERS
[243]
OPEN
STUDY
[53]
PRESS
ROOM
[226]
SPECIAL
COLLECTIONS
[228]
VAULT
[228E]
ARCHIVE
[228D]
INSTRUCTION
2
[224]
INSTRUCTION
1
[222]
DCAM
[228B]
OFFICE
[228A]
SCANNER
[228C]
OFFICE
[232]
STUDY
(MED)
[216]
STUDY
(MED)
[214]
STUDY
(MED)
[218]
OFFICE
[230]
OFFICE
[202]
STUDY (SM)
[212]
STUDY (SM)
[210]
STUDY (SM)
[208]
OFFICE
[200]
OPEN
STUDY
[220]
'CP12'
'G'
'F1'
'F'
'U
P
S
'
'E
W
2
'
'C
P
1
4
'
'2
L
B
'
'2
W
A
'
'C
P
1
3
'
'D
'
TECH SERV
STORAGE
[2-E]
STUDY (SM)
[204]
JANITOR'S
OFFICE
[241]
MECHANICAL
[2-D]
I.T.
[245]
MEN'S
RESTROOM
[247]
WOMEN'S
RESTROOM
[248]
STAIR
[2-G]
ELEV
[2-H]
MECH
CHASE
[2-J]
STAIR
[2-A]
STAIR
[2-B]
6D-5 6D-5
1D-4
1D-4
2D-4
3D-4
3D-4
2D-4
2D-4
6D-5
3D-4
1D-4 1D-4
1D-4
1D-4
1D-4 1D-4
1D-4 1D-4
1D-4 1D-4
3D-4 3D-4
1D-4
2D-4
2D-42D-42D-4
1D-4
1D-4
2D-4
2D-42D-4
2D-42D-4
2D-4
2D-4
1
1
2 2 2
2 2 2 2
1D-4
2
AC
3 3
2D-4
2D-4
2D-4
2D-4
4D-4
1
2D-4
2D-4
2D-4
2D-4
2D-4
2D-4
2D-4
2D-4
STUDY
(MED)
[206]
1D-4
2D-4
FAMILY RR
[244]
2D-4
1D-42D-42D-4
2D-4
2D-4
2D-4
2D-4
1D-4
2D-4
2D-4
AC
AC
AC
AC
AC
AC
AC
AC
AC
AC
AC
AC
AC
ACACACACAC
4D-4
4D-4
4D-4
2D-4
4D-4
CP12-2
CP12-4
CP12-6
CP12-7
CP12-8
CP12-11
CP12-10
CP12-12
CP12-13 CP12-15
CP12-17
CP12-14
CP12-16
6D-5 6D-5 6D-5
4D-4 4D-4 4D-4
2D-4
CP14-1
CP14-5
CP14-3
CP14-6
CP14-7 CP14-2
CP14-4
CP14-9
CP14-11
CP14-13
1D-41D-4
1D-4 1D-4
1D-4 1D-4
1D-4 1D-4
1D-41D-4
1D-4
1D-41D-4
1D-4
1D-4 1D-4
1D-4 1D-4
1D-4
1D-41D-41D-4
1D-4
1D-4
1D-4
1D-4
1D-4 1D-4
1D-4
1D-4
1D-41D-41D-4
44
4
4
4
5
CP14-10
CP14-8
CP14-12
CP14-15
CP14-17
CP14-14 CP14-16
CP14-19
CP14-18
AC
AC
AC
6
CP13-3
CP13-5
AC
AC
AC
CP13-6
CP13-4
CP13-2
CP13-7
CP13-9
CP13-10
CP13-8
CP13-11
CP13-12
3D-43D-4
1D-4
6
CP13-13
CP13-15
CP13-17
CP13-14CP13-16
CP13-18
CP13-19
CP13-21CP13-23
CP14-21
CP13-20
D-1
D-3
D-5
D-4
D-6
D-7
D-11 D-9
D-8
D-10
D-13
D-12
D-15
D-17
D-14
D-16
D-18
D-21
D-19
D-23
D-20 D-22
D-24
D-25
D-27,29,31D-26,28,30
H-1
DXFCU-1(FC)
FCU-2
DXFCU-1 H-1
7
8
2D-4
CP12-1
EW2-5 EW2-3
EW2-1
CP13-28
EE203
2
CP13-30
D-33
D-2
D-35
9
1D-4CP12-9
CP12-18
10
L
5 6
7
CP13-29
CP13-24,26,25,27
UPS-7
UPS-2,4,6,8
CP13-22
NEMA 6L-20
RECEPTS.
I.T.
[245]
SAC-245A SAC-245B
8270
STATEOFIDAHO
T
ODD P A Y N EREGISTER
EDRP
OFESSIONALEN
G
I
NE
E
R
1823 E. Center
Pocatello, Idaho 83201
tel (208) 232-4439
www.payneengineeringinc.com
Engineering Inc.
Consulting Engineers
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
P.E. #:2259
10-28-2022 EE203
POWER
PLAN LEVEL
2 AREA A
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
BID SET
A. REFER TO SYMBOL SCHEDULE SHEET FOR PROJECT
GENERAL NOTES AND GENERAL NOTES ASSOCIATED WITH
THE INSTALLATION OF EACH SYSTEM, INCLUDINB BUT NOT
LIMITED TO; LIGHTING, POWER, FIRE ALARM, SPECIAL
SYSTEMS, ETC.
GENERAL NOTES:
KEY NOTES:#
1 SLIM LINE AV SYSTEM CABINET. PROVIDE (2) DUPLEX
OUTLETS IN CABINET, EXTRA-DEEP BOX WITH 1 1/2"
CONDUIT TO ABOVE ACCESSIBLE CEILING FOR DATA/AV
CABLING. COORDINATE EXACT PLACEMENT OF BOXES
WITH CABINET AND KENDEN JENSEN (CAMPUS AV) PRIOR
TO ROUGH IN. PROVIDE A #10 GREEN INSULATED
GROUND CONDUCTOR FROM CABINET TO NEAREST
ELECTRICAL ROOM GROUND BAR. FIELD VERIFY FINAL
LOCATION PRIOR TO ROUGH-IN.
2 MOUNT BEHIND TV, COORDINATE MOUNTING W/ TV
MOUNTING BRACKET PRIOR TO ROUGH IN. PROVIDE
EXTRA DEEP BOX SUCH AS, HUBBELL HBL260, W/ SINGLE
GANG MUD RING W/ 1 1/4" C., TO ABOVE ACCESSIBLE
CEILING. COORDINATE W/ KENDEN JENSEN (CAMPUS AV)
PRIOR TO ROUGH IN.
3 PROVIDE AND INSTALL ALL POWER AND CONTROL
CONDUIT AND CABLING PER FOLDING WALL
MANUFACTURER. COORDINATE ROUGH-IN
REQUIREMENTS WITH WALL INSTALL. MAKE ALL
REQUIRED CONNECTION.
4 FLOOR BOX FOR POWER/DATA SERVICE TO FURNITURE.
COORDINATE EXACT FURNITURE FEED ROUGH IN
LOCATION PRIOR TO CORE DRILLING FLOOR.
COORDINATE WITH G.C. AND FURNITURE SHOP
DRAWINGS. MAKE ALL REQUIRED CONNECTION TO
DEVICES SHOWN.
5 ROUTE WIRES THROUGH FURNITURE, PROVIDE AND
INSTALL ALL NECESSARY BRACKETS, COVERS,
CONNECTORS, ETC. REQUIRED FOR INSTALLATION.
6 LOCATE RECEPTACLE BEHIND DRINKING FOUNTAIN
HOUSING.
7 PROVIDE AND INSTALL (2) 4" C., FROM TR ROOM TO
ABOVE ACCESSIBLE CEILING IN FLOOR BELOW, AND (2) 4"
C., FROM TR ROOM TO ABOVE ACCESSIBLE CEILING IN
FLOOR ABOVE.
8 PROVIDE AND INSTALL 3/4" PLYWOOD ON WALLS AS
SHOWN FOR ACCESS CONTROL HEADEND. MOUNT
PLYWOOD AT 36" AFF. PROVIDE AND INSTALL (2) 4" C., TO
FLOOR BELOW AND (2) 4" C., TO FLOOR ABOVE.
9 PROVIDE AND INSTALL SECURITY PANIC BUTTON,
INSTALL 1" C., TO ABOVE ACCESSIBLE CEILING. CONNECT
BUTTON TO CAMPUS SECURITY.
10 MOUNT BEHIND TV, COORDINATE MOUNTING W/ TV
MOUNTING BRACKET PRIOR TO ROUGH IN. PROVIDE AN
EXTRA DEEP BOX, SUCH AS HUBBELL HBL260 BOX, W/
SINGLE GANG MUD RING W/ 1 1/4" C., TO ABOVE
ACCESSIBLE CEILING. COORDINATE W/ KENDEN JENSEN
(CAMPUS AV) PRIOR TO ROUGH IN.
SCALE: 1/8" = 1'-0"1 LEVEL 2 POWER PLAN AREA A
NORTH
16'8'0"
KEY PLAN
A
B
SCALE: 1/4" = 1'-0"2 COMM ROOM 245
PUBLIC ADDRESS SYSTEM:
FOR BIDDING PURPOSE:
• E.C. SHALL INCLUDE A CASH ALLOWANCE FOR $250,000.00 TO
COVER ALL MATERIALS, LABOR, PROGRAMMING & TRAINING
REQUIRED TO INSTALL A COMPLETE AND OPERABLE PUBLIC
ADDRESS SYSTEM IN THIS FACILITY. PA SYSTEM DESIGN
WILL BE PROVIDED TO THE CONTRACTOR PRIOR TO
COMMENCEMENT OF CONSTRUCTION.
• E.C. SHALL CAREFULLY DISCONNECT AND REMOVE ALL
EXISTING PUBLIC ADDRESS SYSTEM SPEAKERS, CONTROLS,
HEAD END, ETC. REMOVE ALL ASSOCIATED CABLE, WIRE,
AND CONDUIT. CLEAN, BOX, AND DELIVER ALL SPEAKERS
AND HEAD END EQUIPMENT TO OWNER SPECIFIED
LOCATION.
REF.
REF.
FBP FBP
FBP
FBT FBT
FBP FBP
FBP FBP
FBP
FBP
FBP
FBP FBP FBP
FBP
FBP
FBP
M
M
M
FBP
CS
M
F
F
J
J
J
16151413121110987
K
H
F
D
B
A
CLASSROOM
[272]
OFFICE
[288B]
ENGLISH
TRANSITION
CENTER
[288]
OPEN
TUTORING
[254]
STUDY
SKILLS
[252]
WRITING
CENTER
OPEN
TUTORING
[256]
STUDY
[269]
STUDY
[268]
STUDY
[267]
STUDY
[266]
OFFICE
[265]
OFFICE
[264]
STORAGE
[270J]
STUDY
[270H]
PREP /
STORAGE
[270B]
CLASSROOM
[258]
CLASSROOM
[260]
PREP /
STORAGE
[256A]
OFFICE
[256B]
OFFICE
[256C]
OPEN
TUTORING
CENTER
[270]
ADJUNCT
OFFICE
[286]TR / COMM.
[280]
CLASSROOM
[278]
PRE-FUNCTION
[270C]
PRE-FUNCTION
[270D]
PRE-FUNCTION
[270E]
RECEPTION
[270A]
PREFUNCTION
[270F]
'C
P
8
'
'C
P
6
'
'C
P
5
'
'2
L
A
'
'2
B
'
'2
A
'
'E
E
2
'
'U
P
S
1
'
STUDY
[270G]
STORAGE
[252F]
PREP /
STORAGE
[252G]
STUDY
[252B]
STUDY
[252A]
ELEV
[2-R]
STUDY
[252C]
OFFICE
[252D]
1D-4
1D-4
6D
-5
3D-4
3D-4
6D
-5
1D-4
1D-4
OFFICE
[288C]
STUDY
[288D]
STUDY
[288E]
STUDY
[288F]
STUDY
[288G]
STORAGE
[288H]
2D-4
STUDY
[288A]
1D-4
1D-4
1D-4
1D-4
1D-4
1D-4AC
1D-4
1D-4
AC
1D-4
AC
1D-4
1D-4
AC
1D-4
AC
1D-4
AC
AC
1D-4
3D-4
2D-4
1D-4
1D-4
1D-4
1D-4
AC
AC
AC
AC
3D-4
6D-5
2D-4
2D-4
3D-4
1D-41D-4
6D
-5
1D-4
1D-4
1D-4
1 1
1
3D-4
1
6D
-5
1
2
2
2
6D-5
1
2D-4 1D-4
AC
2A-1
2A-3
2A-5
2A-6
2A-4
2A-2
3
2A-8
2A-13
2A-12
1D-E
2A-11
2A-7
2A-15
2A-17
2A-14
2A-19
2A-18
2A-21
2A-23
2B-1
2B-3
2B-5
2B-6
2B-4
2B-2
2B-11
2B-9
2B-7 2B-8
2B-10
2B-12
2B-13
2B-15
2B-17
2B-14
2B-18AC
2B-20
2B-23
2B-21
2B-19
2B-242B-22
2B-29
2B-27
2B-25
2B-26 2B-28
2B-31
2B-30
CP5-3
CP5-1
3
CP5-5
CP5-2
CP5-4CP5-6
3
CP5-7
CP5-9
CP5-8
1D-E
CP5-10
CP5-12
CP5-17 CP5-15 CP5-13
CP5-14CP5-16
CP5-18
CP6-1,3,5
CP6-2,4,6
CP6-7,9,11
CP6-10
CP6-8
4D-4
2D-4
CP6-12
CP6-13 CP6-15CP6-17
CP6-14
4
2A-9
2B-16
EE204
2
CP6-16
(ON ROOF)
REF-4
5
5
2A-25
2A-25
6
6
SCU-280BSCU-280A
CP5-11
2D-4
7
1D-4
2A-20
8
8
1D-4
8
11
SAC-280B
'UPS (280)'
CP5-20,22,23,25
CP5-21
UPS (280)-1
UPS (280)-2,4,3,5
CP5-19
4
SAC-280A
8270
STATEOFIDAHO
T
ODD P A Y N EREGISTER
EDRP
OFESSIONALEN
G
I
NE
E
R
1823 E. Center
Pocatello, Idaho 83201
tel (208) 232-4439
www.payneengineeringinc.com
Engineering Inc.
Consulting Engineers
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
P.E. #:2259
10-28-2022 EE204
POWER
PLAN LEVEL
2 AREA B
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
BID SET
A. REFER TO SYMBOL SCHEDULE SHEET FOR PROJECT
GENERAL NOTES AND GENERAL NOTES ASSOCIATED WITH
THE INSTALLATION OF EACH SYSTEM, INCLUDINB BUT NOT
LIMITED TO; LIGHTING, POWER, FIRE ALARM, SPECIAL
SYSTEMS, ETC.
GENERAL NOTES:
KEY NOTES:#
1 SLIM LINE AV SYSTEM CABINET. PROVIDE (2) DUPLEX
OUTLETS IN CABINET, EXTRA-DEEP BOX WITH 1 1/2"
CONDUIT TO ABOVE ACCESSIBLE CEILING FOR DATA/AV
CABLING. COORDINATE EXACT PLACEMENT OF BOXES
WITH CABINET AND KENDEN JENSEN (CAMPUS AV) PRIOR
TO ROUGH IN. PROVIDE A #10 GREEN INSULATED
GROUND CONDUCTOR FROM CABINET TO NEAREST
ELECTRICAL ROOM GROUND BAR. FIELD VERIFY FINAL
LOCATION PRIOR TO ROUGH-IN.
2 PROVIDE AND INSTALL ALL POWER AND CONTROL
CONDUIT AND CABLING PER FOLDING WALL
MANUFACTURER. COORDINATE ROUGH-IN
REQUIREMENTS WITH WALL INSTALL. MAKE ALL
REQUIRED CONNECTION.
3 LOCATE RECEPTACLE BEHIND DRINKING FOUNTAIN
HOUSING.
4 PROVIDE AND INSTALL (2) 4" C., FROM TR ROOM TO
ABOVE ACCESSIBLE CEILING IN FLOOR BELOW.
5 EXISTING ROOF TOP EXHAUST FAN TO REMAIN, MAINTAIN
AND/OR RE-ESTABLISH ELECTRICAL FEEDER TO DEVICE.
6 RECEPTACLE MOUNTED TO HVAC UNIT, COORDINATE
MOUNTING WITH M.C. PRIOR TO ROUGH-IN.
7 RECEPTACLE MOUNTED FLUSH IN CEILING FOR
OVERHEAD PROJECTOR, VERIFY EXACT LOCATION WITH
OWNER PRIOR TO ROUGH-IN. INSTALL J-BOX ABOVE
CEILING MOUNTED TO STRUCTURE WITH A 10FT MC
CABLE WHIP TO RECEPTACLE.
8 MOUNT BEHIND TV, COORDINATE MOUNTING W/ TV
MOUNTING BRACKET PRIOR TO ROUGH IN. PROVIDE AN
EXTRA DEEP BOX, SUCH AS HUBBELL HBL260 BOX, W/
SINGLE GANG MUD RING W/ 1 1/4" C., TO ABOVE
ACCESSIBLE CEILING. COORDINATE W/ KENDEN JENSEN
(CAMPUS AV) PRIOR TO ROUGH IN.
SCALE: 1/8" = 1'-0"1 LEVEL 2 POWER PLAN AREA B
NORTH
16'8'0"
KEY PLAN
A
B
SCALE: 1/4" = 1'-0"2 COMM ROOM 280
PUBLIC ADDRESS SYSTEM:
FOR BIDDING PURPOSE:
• E.C. SHALL INCLUDE A CASH ALLOWANCE FOR $250,000.00 TO
COVER ALL MATERIALS, LABOR, PROGRAMMING & TRAINING
REQUIRED TO INSTALL A COMPLETE AND OPERABLE PUBLIC
ADDRESS SYSTEM IN THIS FACILITY. PA SYSTEM DESIGN
WILL BE PROVIDED TO THE CONTRACTOR PRIOR TO
COMMENCEMENT OF CONSTRUCTION.
• E.C. SHALL CAREFULLY DISCONNECT AND REMOVE ALL
EXISTING PUBLIC ADDRESS SYSTEM SPEAKERS, CONTROLS,
HEAD END, ETC. REMOVE ALL ASSOCIATED CABLE, WIRE,
AND CONDUIT. CLEAN, BOX, AND DELIVER ALL SPEAKERS
AND HEAD END EQUIPMENT TO OWNER SPECIFIED
LOCATION.
FBP FBP
FBP FBP FBPFBP FBP
FBP FBP
FBP
FBP
FBP
FBP FBP
FBPFBP
FBP FBP FBP
FBP
FBP
FBP
FBP FBP
J
J
J
J
J
J
FBP FBP FBP FBP
FBP FBP FBP FBP
FBP
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS
SS SS
SS
SS
SS
SS
SS
SS
FBP
FB2S
CS
SS SS SS
SSSSSS
J
J
J
J
J
J
J
J
M
M
M
PC
M
1
G
J
L
M
N
P
Q
E
C
2 3 4 5 61.5
STUDY (SM)
[332]
STUDY (SM)
[336]
STUDY (SM)
[314]
STUDY (SM)
[316]
ELEC
[364]
STUDY (SM)
[320]
STUDY (SM)
[338]
STUDY (SM)
[318]
ELECTRICAL
[324B]
STUDY (SM)
[334]
OFFICE
[310]
OFFICE
[312]
JUVENILE
[300]
STORAGE
[306]
STUDY
(MED)
[304]STUDY
(MED)
[302]
KIDS PLAY
[344C]
MOTHERS
ROOM
[344A]
RESTROOM
[344B]
FAMILY
STUDY
[344]
( QUIET )
OPEN
STUDY
[342]
OPEN
STUDY
[362]
Bridge
Connection
[-]
BRIDGE
CONNECTION
[3-A]
STAIR 1
[3-B]
MENS
[368]
WOMENS
[366]
TEST RM
[378]
STUDY (SM)
[330]
Janitors
Closet
[376]
OFFICE
[322]
MAC EQUIP
[324A]
STUDY (LG)
[328]
STUDY (LG)
[326]
MAC LAB
[324]
TEST RM
[374]
STUDY (SM)
[340]
'CP16'
'CP15'
'3WB'
'K'
'3
L
A
'
'3
W
A
'
'CP17'
'CP18''N'
'H'
ELECTRICAL
[308]
STORAGE
[352]
TEST RM
[382]
TEST RM
[380]
TEST RM
[372]
TEST RM
[370]
TEST RM
[360]
TEST RM
[358]
TEST RM
[356]
TEST RM
[350]
TEST RM
[348]TEST RM
[346]
MECH
CHASE
[3-E]
MECH
[3-D]
2D-4
2D-4
2D-4
2D-4
2D-4
2D-4
2D-4
2D-4
2D-4
2D-4
2D-4
3D-4 2D-4
2D-4
6D
-5
2D-4
2D-4
2D-4
1D-4
1D-4
2D-4
2D-4
2D-4
2D-4
1D-4
3D-4
1D-4
2D-4
2D-4
11
1
1
2
ACAC
1
1
2D-4
1D-4
2D-4
1D-4
2D-4
4D-4
4D-4
4D-4
1D-4 1D-4 1D-4
AC
2D-4
4D-4
4D-4
4D-4
ELEV
[3-G]
MECH
CHASE
[3-H]
STAIR
[3-F]
AC
AC
ACAC
1
1
1
1
1
1
ACACAC
AC
AC
N-5
N-3
N-1
N-8
N-2
N-4
N-6
N-7
N-9
N-11
N-10
N-12
N-13
1
1
N-17
N-15
N-14
N-16
FCU-3
(ON ROOF)
REF-3
(ON ROOF)
REF-2
(ON ROOF)
REF-1
K-1
K-3
K-5
K-11
K-9
K-7
K-6
K-4
K-2
K-8 K-10
K-12
K-13
CP15-1
CP15-4
CP15-2
CP15-6
CP15-3
CP15-5
CP15-11
CP15-9
CP15-7
K-14
K-15
K-17
K-16
K-18
K-19
K-21
H-5 H-3
H-1
H-2H-4H-6
H-7
3
H-9
3
CP17-1
CP17-5
CP17-4
CP17-2
CP17-9
'J'
3
CP17-15
CP17-10
CP17-12
CP17-8
CP17-11
2D-4
K-20
K-22
K-24
K-25
K-27
K-26
2D-4
2D-4
4D-4 4D-4
2D-4
K-29
CP17-3
CP17-6
CP17-7
(ON ROOF)
DXFCU-1(CU)
K-30
K-30
K-30
K-30
4
4
4
4
CP17-14
CP15-8
(ON ROOF)
SCU-245B
(ON ROOF)
SCU-245A4K-30
5
8270
STATEOFIDAHO
T
ODD P A Y N EREGISTER
EDRP
OFESSIONALEN
G
I
NE
E
R
1823 E. Center
Pocatello, Idaho 83201
tel (208) 232-4439
www.payneengineeringinc.com
Engineering Inc.
Consulting Engineers
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
P.E. #:2259
10-28-2022 EE205
POWER
PLAN LEVEL
3
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
BID SET
A. REFER TO SYMBOL SCHEDULE SHEET FOR PROJECT
GENERAL NOTES AND GENERAL NOTES ASSOCIATED WITH
THE INSTALLATION OF EACH SYSTEM, INCLUDINB BUT NOT
LIMITED TO; LIGHTING, POWER, FIRE ALARM, SPECIAL
SYSTEMS, ETC.
GENERAL NOTES:
KEY NOTES:#
1 MOUNT BEHIND TV, COORDINATE MOUNTING W/ TV
MOUNTING BRACKET PRIOR TO ROUGH IN. PROVIDE EXTRA
DEEP BOX SUCH AS, HUBBELL HBL260, W/ SINGLE GANG
MUD RING W/ 1 1/4" C., TO ABOVE ACCESSIBLE CEILING.
COORDINATE W/ KENDEN JENSEN (CAMPUS AV) PRIOR TO
ROUGH IN.
2 SLIM LINE AV SYSTEM CABINET. PROVIDE (2) DUPLEX
OUTLETS IN CABINET, EXTRA-DEEP BOX WITH 1 1/2"
CONDUIT TO ABOVE ACCESSIBLE CEILING FOR DATA/AV
CABLING. COORDINATE EXACT PLACEMENT OF BOXES WITH
CABINET AND KENDEN JENSEN (CAMPUS AV) PRIOR TO
ROUGH IN. PROVIDE A #10 GREEN INSULATED GROUND
CONDUCTOR FROM CABINET TO NEAREST ELECTRICAL
ROOM GROUND BAR. FIELD VERIFY FINAL LOCATION PRIOR
TO ROUGH-IN.
3 LOCATE RECEPTACLE BEHIND DRINKING FOUNTAIN
HOUSING.
4 RECEPTACLE MOUNTED TO HVAC UNIT, COORDINATE
MOUNTING WITH M.C. PRIOR TO ROUGH-IN.
5 PROVIDE AND INSTALL SECURITY PANIC BUTTON, INSTALL 1"
C., TO ABOVE ACCESSIBLE CEILING. CONNECT BUTTON TO
CAMPUS SECURITY.
SCALE: 1/8" = 1'-0"1 LEVEL 3 POWER PLAN
NORTH
16'8'0"
KEY PLAN
A
B
PUBLIC ADDRESS SYSTEM:
FOR BIDDING PURPOSE:
• E.C. SHALL INCLUDE A CASH ALLOWANCE FOR $250,000.00 TO
COVER ALL MATERIALS, LABOR, PROGRAMMING & TRAINING
REQUIRED TO INSTALL A COMPLETE AND OPERABLE PUBLIC
ADDRESS SYSTEM IN THIS FACILITY. PA SYSTEM DESIGN
WILL BE PROVIDED TO THE CONTRACTOR PRIOR TO
COMMENCEMENT OF CONSTRUCTION.
• E.C. SHALL CAREFULLY DISCONNECT AND REMOVE ALL
EXISTING PUBLIC ADDRESS SYSTEM SPEAKERS, CONTROLS,
HEAD END, ETC. REMOVE ALL ASSOCIATED CABLE, WIRE,
AND CONDUIT. CLEAN, BOX, AND DELIVER ALL SPEAKERS
AND HEAD END EQUIPMENT TO OWNER SPECIFIED
LOCATION.
REF.REF.
M
F
F
F
F
C1
C1
C1
C1
C1
C1
G
J
E
C
2 3 4 5 6
TIER 2
[016]
OFFICE
[010]
OFFICE
[026A]
OFFICE
[011]
BREAK
ROOM
[013]
'O'
'EMW''EME'
'ATS WEST''ATS EAST'
'MC'
SHORT
TERM
STORAGE
[028]
OFFICE
[012]
TECH
ROOM
[024]
STUDENTS
[026F]
OFFICE
[026C]
OPS
[022]
MECH
ROOM
[030]
STAIR
[0-E]
STORAGE
[032]
MECH
CHASE
[O-F]
STAIR
[0-E]ELEV
[0-J]
ELECTRICAL
[038]
CUSTODIAL
[036]
MECH
CHASE
[034]
BDF
[040]
CUSTODIAL
STORAGE
[042]
STORAGE
[044]
OFFICE
[018]
OFFICE
[020]
QA
[022A]
MEN'S RR
[015]
WOMEN'S
RR
[014]
IMAGING
AND
STORAGE
[009]
OFFICE
[026B]
OFFICE
[026D]
OFFICE
[026E]
'E''UPS'
'CP7''R''DB1''P'
RUN ALL ACCESS CONTROL CABLES
IN THIS AREA TO HEAD END
LOCATED IN ELECTRICAL ROOM 038
ACCESS CONTROL CABLE SCHEDULE
C1
LABEL CABLE DESCRIPTION CABLE TYPE
16/4 PLENUM/SHIELDED/STRANDED (RED, BLACK, GREEN, W HITE)CAROL
C2 16/2 PLENUM/STRANDED CAROL
C3 20/7 PLENUM/SHIELDED/STRANDED BELDEN 6405FE
• ACCESS CONTROL SYSTEM DETAILS ARE FOR REFERENCE ONLY; E.C. SHALL INSTALL AND CONNECT SYSTEM AS DIRECTED BY THE EQUIPMENT
SUPPLIER AND ACTUAL FIELD CONDITIONS.
• ALL ACCESS CONTROL CABLING SHALL BE WHITE IN COLOR.
• E.C. SHALL COIL AND LABEL 20FT OF CABLING AT EACH INDICATED LOCATION ABOVE ACCESSIBLE CEILING, AND COIL AND LABEL 20FT OF
CABLING AT THE INDICATED ACCESS CONTROL HEADEND.
ACCESS CONTROL CABLING NOTES:
8270
STATEOFIDAHO
T
ODD P A Y N EREGISTER
EDRP
OFESSIONALEN
G
I
NE
E
R
1823 E. Center
Pocatello, Idaho 83201
tel (208) 232-4439
www.payneengineeringinc.com
Engineering Inc.
Consulting Engineers
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
P.E. #:2259
10-28-2022 EE300
ACCESS
CONTROL
PLAN LEVEL
0
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
BID SET
A. REFER TO SYMBOL SCHEDULE SHEET FOR PROJECT
GENERAL NOTES AND GENERAL NOTES ASSOCIATED WITH
THE INSTALLATION OF EACH SYSTEM, INCLUDINB BUT NOT
LIMITED TO; LIGHTING, POWER, FIRE ALARM, SPECIAL
SYSTEMS, ETC.
GENERAL NOTES:
NORTH
16'8'0"
KEY PLAN
A
B
SCALE: 1/8" = 1'-0"1 LEVEL 0 ACCESS CONTROL PLAN
RE
F
.
RE
F
.
F
F F
FF
F
F
CR
F
F
CR
F
F
CR
F
F
F
F
F
CR
FFF
F
C1
C1
C1C3
C3
C1
C1
C3
C1
C1
C1
C1 C1 C3
C1
C1
C1
C1
C1 C1
C1
CR
C3
1
1615141312111098
B
A
G
J
L
M
N
P
Q
E
C
2 3 4 5 61.5
CHECK-IN
[112]
OFFICE
[129]
OFFICE
[130]
OFFICE
[131]
STUDY
(MED)
[132]
OFFICE
[136]
RECEPTION
[134]
OFFICE
[138]
CONFERENCE
ROOM
[140]
BREAKROOM
[142]
STORAGE
[170C]STUDY
[170B]
STUDY
[170A]CLASSROOM
[168]
CLASSROOM
[166]
ADJUNCT
OFFICE
[180]
OFFICE
[181]
OFFICE
[182]
OFFICE
[183]
OFFICE
[184]
OFFICE
[185]
OFFICE
[186]
CONFERENCE
ROOM
[158]
CONFERENCE
[188B]
COLLABORATIVE
SPACE
[188]
STUDY (SM)
[128]
STUDY
(MED)
[124]
STUDY
(MED)
[125]
STUDY (SM)
[126]
STUDY (SM)
[127]
OPEN
STUDY
[122A]
HD BOOK
COLLECTION
[122]
OPEN
STUDY
[120A]
VESTIBULE
[1-F]
CIRCULATION
RECEPTION
[110]
OFFICE
[108]INTER
LIBRARY
LOAN
WORKSPACE
[114]
FAMILY RR
[144]
OPEN
STUDY
[122C]
OPEN
STUDY
[122B]
CLASSROOM
[162]
CLASSROOM
[164]
OFFICE
[190B]
OFFICE
[190A]
TRAINING
AREA
[190]
OFFICE
[192B]
SMALL
MEETING
[192A]
OFFICE
[160A]OFFICE
[160B]
TUTORING
ADMIN
OPEN AREA
[160]
OFFICE
[156F]PRACTICE
[156E]
WORKSPACE
[156]
STORAGE
[156D]
DROP IN
MATH LAB
[170]
WORKSTATIONS/
FLEX
SPACE
[192]
CLASSROOM
[172]
STUDENT
PREP
[174]
STUDY
[178]
STUDY
[179]
MATH LAB
RECEPTION
[175]
I.T. HELP
DESK
[176]
OPEN
STUDY
[118]
MENS
[146]
WOMENS
[148]
JANITORS
OFFICE
[147]
OFFICE
[188A]
'EW3'
OFFICE
[106]
OFFICE
[104]
OFFICE
[114A]
STAIR
[1-H]
STAIR
[1-B]
VESTIBULE
[1-A]
STAIR
[1-D]
HALLWAY
[1-C]
MECH
CHASE
[1-K]
RESERVE
MEDIA
[116]
ELEC
ROOM
[102]
'B'
'ACCESS
CONTROL
HEAD END'
RUN ACCESS
CONTROL
CABLES IN AREA
TO IT ROOM 241
RUN ACCESS
CONTROL
CABLES IN AREA
TO ELECTRICAL
ROOM 2-I
ACCESS CONTROL CABLE SCHEDULE
C1
LABEL CABLE DESCRIPTION CABLE TYPE
16/4 PLENUM/SHIELDED/STRANDED (RED, BLACK, GREEN, W HITE)CAROL
C2 16/2 PLENUM/STRANDED CAROL
C3 20/7 PLENUM/SHIELDED/STRANDED BELDEN 6405FE
• ACCESS CONTROL SYSTEM DETAILS ARE FOR REFERENCE ONLY; E.C. SHALL INSTALL AND CONNECT SYSTEM AS DIRECTED BY THE EQUIPMENT
SUPPLIER AND ACTUAL FIELD CONDITIONS.
• ALL ACCESS CONTROL CABLING SHALL BE WHITE IN COLOR.
• E.C. SHALL COIL AND LABEL 20FT OF CABLING AT EACH INDICATED LOCATION ABOVE ACCESSIBLE CEILING, AND COIL AND LABEL 20FT OF
CABLING AT THE INDICATED ACCESS CONTROL HEADEND.
ACCESS CONTROL CABLING NOTES:
8270
STATEOFIDAHO
T
ODD P A Y N EREGISTER
EDRP
OFESSIONALEN
G
I
NE
E
R
1823 E. Center
Pocatello, Idaho 83201
tel (208) 232-4439
www.payneengineeringinc.com
Engineering Inc.
Consulting Engineers
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
P.E. #:2259
10-28-2022 EE301
ACCESS
CONTROL
PLAN LEVEL
1
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
BID SET
A. REFER TO SYMBOL SCHEDULE SHEET FOR PROJECT
GENERAL NOTES AND GENERAL NOTES ASSOCIATED WITH
THE INSTALLATION OF EACH SYSTEM, INCLUDINB BUT NOT
LIMITED TO; LIGHTING, POWER, FIRE ALARM, SPECIAL
SYSTEMS, ETC.
GENERAL NOTES:
NORTH
32'16'0"
KEY PLAN
A
B
SCALE: 1/16" = 1'-0"1 LEVEL 1 ACCESS CONTROL PLAN
REF.
REF.
F
F
F
F
F
CR
F
CR
CRCR
CR
F
F
F
F
F
CR
F F
C1
C1
C1
C3
C3
C3
C1
C1
C1
C1
C1
C1
C1
C1
C1
C1
C1
C1
C1
C1
C3
C3
C3
C1 C1 C1
C1
C1
C1C1
C1
1
16151413121110987
B
A
G
J
L
M
N
P
Q
E
C
2 3 4 5 61.5
ELECTRICAL
ROOM
[242]
TECH
SERVICES
[238]
SHEET
MUSIC
[236]
LARGE
COMPUTER
CLASSROOM
[234]
OPEN
COMPUTERS
[240]
OPEN
STUDY
[53]
PRESS
ROOM
[226]
SPECIAL
COLLECTIONS
[228]
VAULT
[228E]
ARCHIVE
[228D]
INSTRUCTION
2
[224]
INSTRUCTION
1
[222]
DCAM
[228B]
OFFICE
[228A]
SCANNER
[228C]
OFFICE
[232]
STUDY
(MED)
[216]
STUDY
(MED)
[214]
STUDY
(MED)
[218]
CLASSROOM
[272]
OFFICE
[288B]
OFFICE
[288C]
ENGLISH
TRANSITION
CENTER
[288]
OPEN
TUTORING
[254]
STUDY
SKILLS
[252]
WRITING
CENTER
OPEN
TUTORING
[256]STUDY
[269]
STUDY
[268]
STUDY
[267]
STUDY
[266]OFFICE
[265]
OFFICE
[264]
STORAGE
[270J]
STUDY
[270H]
PREP /
STORAGE
[270B]
CLASSROOM
[258]
CLASSROOM
[260]
PREP /
STORAGE
[256A]
OFFICE
[256B]
OFFICE
[256C]
OPEN
TUTORING
CENTER
[270]
OFFICE
[230]
OFFICE
[202]
STUDY (SM)
[212]
STUDY (SM)
[210]
STUDY (SM)
[208]
OFFICE
[200]
OPEN
STUDY
[220]
ADJUNCT
OFFICE
[286]
TR / COMM.
[280]
CLASSROOM
[278]
PRE-FUNCTION
[270C]
PRE-FUNCTION
[270D]
PRE-FUNCTION
[270E]
RECEPTION
[270A]
PREFUNCTION
[270F]
TECH SERV
STORAGE
[2-E]
STUDY (SM)
[204]
JANITOR'S
OFFICE
[241]
MECHANICAL
[2-D]
I.T.
[245]
MEN'S
RESTROOM
[247]
WOMEN'S
RESTROOM
[248]
STAIR
[2-G]
ELEV
[2-H]
MECH
CHASE
[2-J]
STAIR
[2-A]
STAIR
[2-B]
MOTHERS
[243]
FAMILY RR
[244]
STUDY
(MED)
[206]
'ACCESS
CONTROL
HEAD END'
ELECTRICAL
[2-I]
IT
[241A]
RUN ACCESS
CONTROL
CABLES IN AREA
TO IT ROOM 241
RUN ACCESS
CONTROL
CABLES IN AREA
TO ELECTRICAL
ROOM 2-I
ACCESS CONTROL CABLE SCHEDULE
C1
LABEL CABLE DESCRIPTION CABLE TYPE
16/4 PLENUM/SHIELDED/STRANDED (RED, BLACK, GREEN, W HITE)CAROL
C2 16/2 PLENUM/STRANDED CAROL
C3 20/7 PLENUM/SHIELDED/STRANDED BELDEN 6405FE
• ACCESS CONTROL SYSTEM DETAILS ARE FOR REFERENCE ONLY; E.C. SHALL INSTALL AND CONNECT SYSTEM AS DIRECTED BY THE EQUIPMENT
SUPPLIER AND ACTUAL FIELD CONDITIONS.
• ALL ACCESS CONTROL CABLING SHALL BE WHITE IN COLOR.
• E.C. SHALL COIL AND LABEL 20FT OF CABLING AT EACH INDICATED LOCATION ABOVE ACCESSIBLE CEILING, AND COIL AND LABEL 20FT OF
CABLING AT THE INDICATED ACCESS CONTROL HEADEND.
ACCESS CONTROL CABLING NOTES:
8270
STATEOFIDAHO
T
ODD P A Y N EREGISTER
EDRP
OFESSIONALEN
G
I
NE
E
R
1823 E. Center
Pocatello, Idaho 83201
tel (208) 232-4439
www.payneengineeringinc.com
Engineering Inc.
Consulting Engineers
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
P.E. #:2259
10-28-2022 EE302
ACCESS
CONTROL
PLAN LEVEL
2
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
BID SET
A. REFER TO SYMBOL SCHEDULE SHEET FOR PROJECT
GENERAL NOTES AND GENERAL NOTES ASSOCIATED WITH
THE INSTALLATION OF EACH SYSTEM, INCLUDINB BUT NOT
LIMITED TO; LIGHTING, POWER, FIRE ALARM, SPECIAL
SYSTEMS, ETC.
GENERAL NOTES:
NORTH
32'16'0"
KEY PLAN
A
B
SCALE: 1/16" = 1'-0"1 LEVEL 2 ACCESS CONTROL PLAN
F
F
F
F
F
CR
F
F
F
F F FF
C1
C1
C1
C1
C1
C1
C1
C1
C3
C1
C1
C1
1
G
J
L
M
N
P
Q
E
C
2 3 4 5 61.5
STUDY (SM)
[332]
STUDY (SM)
[336]
STUDY (SM)
[314]
STUDY (SM)
[316]
ELEC
[364]
STUDY (SM)
[320]
STUDY (SM)
[338]
STUDY (SM)
[318]
ELECTRICAL
[324B]
STUDY (SM)
[334]
OFFICE
[310]
OFFICE
[312]
JUVENILE
[300]
STORAGE
[306]
STUDY
(MED)
[304]STUDY
(MED)
[302]
KIDS PLAY
[344C]
MOTHERS
ROOM
[344A]
RESTROOM
[344B]
FAMILY
STUDY
[344]
( QUIET )
OPEN
STUDY
[342]
OPEN
STUDY
[362]
Bridge
Connection
[-]
BRIDGE
CONNECTION
[3-A]
STAIR 1
[3-B]
MENS
[368]
WOMENS
[366]
TEST RM
[378]
STUDY (SM)
[330]
Janitors
Closet
[376]
OFFICE
[322]
MAC EQUIP
[324A]
STUDY (LG)
[328]
STUDY (LG)
[326]
MAC LAB
[324]
TEST RM
[374]
STUDY (SM)
[340]
'CP16'
'CP15'
'3WB'
'K'
'3
L
A
'
'3
W
A
'
'CP17'
'CP18''N'
'H'
ELECTRICAL
[308]
STORAGE
[352]
TEST RM
[382]
TEST RM
[380]
TEST RM
[372]
TEST RM
[370]
TEST RM
[360]
TEST RM
[358]
TEST RM
[356]
TEST RM
[350]
TEST RM
[348]TEST RM
[346]
MECH
CHASE
[3-E]
MECH
[3-D]
ELEV
[3-G]
MECH
CHASE
[3-H]
STAIR
[3-F]
RUN ACCESS
CONTROL
CABLES IN AREA
TO IT ROOM 241
ACCESS CONTROL CABLE SCHEDULE
C1
LABEL CABLE DESCRIPTION CABLE TYPE
16/4 PLENUM/SHIELDED/STRANDED (RED, BLACK, GREEN, W HITE)CAROL
C2 16/2 PLENUM/STRANDED CAROL
C3 20/7 PLENUM/SHIELDED/STRANDED BELDEN 6405FE
• ACCESS CONTROL SYSTEM DETAILS ARE FOR REFERENCE ONLY; E.C. SHALL INSTALL AND CONNECT SYSTEM AS DIRECTED BY THE EQUIPMENT
SUPPLIER AND ACTUAL FIELD CONDITIONS.
• ALL ACCESS CONTROL CABLING SHALL BE WHITE IN COLOR.
• E.C. SHALL COIL AND LABEL 20FT OF CABLING AT EACH INDICATED LOCATION ABOVE ACCESSIBLE CEILING, AND COIL AND LABEL 20FT OF
CABLING AT THE INDICATED ACCESS CONTROL HEADEND.
ACCESS CONTROL CABLING NOTES:
8270
STATEOFIDAHO
T
ODD P A Y N EREGISTER
EDRP
OFESSIONALEN
G
I
NE
E
R
1823 E. Center
Pocatello, Idaho 83201
tel (208) 232-4439
www.payneengineeringinc.com
Engineering Inc.
Consulting Engineers
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
P.E. #:2259
10-28-2022 EE303
ACCESS
CONTROL
PLAN LEVEL
3
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
BID SET
A. REFER TO SYMBOL SCHEDULE SHEET FOR PROJECT
GENERAL NOTES AND GENERAL NOTES ASSOCIATED WITH
THE INSTALLATION OF EACH SYSTEM, INCLUDINB BUT NOT
LIMITED TO; LIGHTING, POWER, FIRE ALARM, SPECIAL
SYSTEMS, ETC.
GENERAL NOTES:
NORTH
16'8'0"
KEY PLAN
A
B
SCALE: 1/8" = 1'-0"1 LEVEL 3 ACCESS CONTROL PLAN
PANEL
1P
PANEL
EE
100A 3 POLE BREAKER
AND ENCLOSURE WITH
SHUNT TRIP FOR
ELEVATOR
PANEL
CC
PANEL
1A
PANEL
1LA
PANEL
CP1
PANEL
CP2
PANEL
CP3
PANEL
CP4
PROVIDE W/
POWER
LOGIC
METERING
PANEL
2A
PANEL
2B
PANEL
2LA
PANEL
CP5
PANEL
CP6
PANEL
CP8
FIRST FLOOR
SECOND FLOOR
MAIN SWITCHBOARD (EAST)
1600A MBR, 208/120, 3PH 4W
XX AIC 2" C., 4#1/0
+ 1#6G
2" C., 4#1/0
+ 1#6G
1 1/2" C., 4#2
+ 1#8G
2" C., 4#1/0
+ 1#6G
2" C., 4#1/0
+ 1#6G
2" C., 4#1/0
+ 1#6G2" C., 4#1/0
+ 1#6G
1 1/2" C., 4#2
+ 1#8G2" C., 4#3/0
+ 1#6G
2" C., 4#1/0
+ 1#6G
2" C., 4#1/0
+ 1#6G
2" C., 4#3/0
+ 1#6G
2" C., 4#1/0
+ 1#6G
2" C., 4#1/0
+ 1#6G
2" C., 4#1/0
+ 1#6G
SPLICE AND EXTEND
EXISTING FEEDERS AS
NECESSARY TO
ACCOMMODATE NEW
SWITCHGEAR
BASEMENT
FIRST FLOOR
SECOND FLOOR
THIRD FLOOR
PANEL
O
PANEL
E
PANEL
1LB
PANEL
B
PANEL
CP9
PANEL
CP10
PANEL
CP15
PANEL
CP16
PANEL
3WB
PANEL
J
PANEL
K
PANEL
N
PANEL
3LA
PANEL
3WA
PANEL
CP18
PANEL
H
PANEL
CP17
PANEL
F1
PANEL
F
PANEL
G
PANEL
D
PANEL
CP13
PANEL
2LB
PANEL
2WA
PANEL
CP14
PANEL
CP12
PANEL
CP11
SWITCHBOARD -MC
PANEL
CP7
2" C., 4#1/0 + 1#6G
2" C., 4#1/0 + 1#6G 1 1/2" C., 4#2 + 1#8G
1 1/4" C., 4#3 + 1#8G
1 1/2" C., 4#2 + 1#8G
2" C., 4#1/0 + 1#6G
SWITCHBOARD -M
(WEST)
SEE EMERGENCY
POWER RISER FOR
E - POWER
DISTRIBUTION
2" C., 4#1/0 + 1#6G2" C., 4#1/0 + 1#6G
2" C., 4#1/0 + 1#6G
2" C., 4#
3/0 + 1#6G
2" C., 4#
1/0 + 1#
6G
2" C., 4#
1/0 + 1#6G
2" C., 4#1/0 + 1#6G 1 1/2" C., 4#2 + 1#8G
2" C., 4#
1/0 + 1#6G 1 1/2" C., 4#2 + 1#8G
PANEL
P
1 1/2" C., 4#2 + 1#8G
PANEL
R
8270
STATEOFIDAHO
T
ODD P A Y N EREGISTER
EDRP
OFESSIONALEN
G
I
NE
E
R
1823 E. Center
Pocatello, Idaho 83201
tel (208) 232-4439
www.payneengineeringinc.com
Engineering Inc.
Consulting Engineers
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
P.E. #:2259
10-28-2022 EE400
RISER
DIAGRAM
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
BID SET
SCALE: NONEAPOWER RISER DIAGRAM - EAST WING
SCALE: NONEBPOWER RISER DIAGRAM - WEST WING
N E
L
N E
L
UPS WEST WING UPS EAST WING
PANEL
EWM
PANEL
EEM
PANEL
E
WEST WING EAST WING
PANEL
EW2
PANEL
UPS
PANEL
UPS1
PANEL
EE2
PANEL
EEMAIN PANEL M
BASEMENT
FIRST FLOOR
SECOND FLOOR
NEW 60A PANEL IN
NEW DATA ROOM FEED
FROM UPS PANEL
GENERATOR LOCATED
AT SMITH BUILDING
1 1
MAIN PANEL M
WEST WING
PANEL
EW3
1 1/2" C., 4#2 + 1#8G
8270
STATEOFIDAHO
T
ODD P A Y N EREGISTER
EDRP
OFESSIONALEN
G
I
NE
E
R
1823 E. Center
Pocatello, Idaho 83201
tel (208) 232-4439
www.payneengineeringinc.com
Engineering Inc.
Consulting Engineers
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
P.E. #:2259
10-28-2022 EE401
EMERGENCY
POWER
RISER
DIAGRAM
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
BID SET
SCALE: NONEAPOWER RISER DIAGRAM - EMERGENCY POWER
KEY NOTES:#
1 EXISTING PANEL TO GET RELOCATED,
RE-ESTABLISH/REFEED PANEL. SEE PLANS FOR NEW
LOCATION.
8270
STATEOFIDAHO
T
ODD P A Y N EREGISTER
EDRP
OFESSIONALEN
G
I
NE
E
R
1823 E. Center
Pocatello, Idaho 83201
tel (208) 232-4439
www.payneengineeringinc.com
Engineering Inc.
Consulting Engineers
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
P.E. #:2259
10-28-2022 EE500
PANEL
SCHEDULES
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
BID SET
S = SHUNT-TRIP BREAKER G = GFCI BREAKER R = RED HANDLED, LOCK-OUT TYPE
A = ARC-FAULT BREAKER GP = GFEPD BREAKER LCP = CRKT TO BE ROUTED THROUGH LTG CONTROL PANEL
BRK NOTES:
TOTAL ESTIMATED DEMAND AMPS:41 A
TOTAL AMPS:60 A 58 A 50 A
TOTAL LOAD:7.0 kVA 6.8 kVA 5.9 kVA
41 42
39 40
37 38
35 Receptacle 20 A 1 720 36
33 Receptacle 20 A 1 720 720 1 20 A Receptacle 34
31 Receptacle 20 A 1 720 900 1 20 A Receptacle 32
29 Receptacle 20 A 1 720 540 1 20 A Receptacle 30
27 Receptacle 20 A 1 720 540 1 20 A Receptacle 28
25 Receptacle 20 A 1 540 720 1 20 A Receptacle 26
23 Receptacle 20 A 1 540 720 1 20 A Receptacle 24
21 Receptacle 20 A 1 540 720 1 20 A Receptacle 22
19 Receptacle 20 A 1 720 720 1 20 A Receptacle 20
17 Receptacle 20 A 1 540 900 1 20 A Receptacle 18
15 Receptacle 20 A 1 360 720 1 20 A Receptacle 16
13 Receptacle 20 A 1 900 720 1 20 A Receptacle 14
11 Drinking Fountain G 20 A 1 180 900 1 20 A Receptacle 12
9 Receptacle 20 A 1 540 720 1 20 A Receptacle 10
7 Receptacle 20 A 1 180 900 1 20 A Receptacle 8
5 180 1 20 A Receptacle 6
3 540 1 20 A Receptacle 4
1 2
CKT CIRCUIT DESCRIPTION NOTE AMPS P A B C P AMPS NOTE CIRCUIT DESCRIPTION CKT
NOTES:
MFG & MODEL:SQ. D/NQ SERIES DIMENSIONS:20"W x 5.8"D x *"H FEED:
ENCLOSURE: BUSSING:SEE SPEC'S MBR AMPS:N/A
MOUNTING:WIRES:4 PANEL AMPS:225 A
FED FROM: PHASES:3 PANEL TYPE:MLO MCK Library Remodel
LOCATION: VOLTAGE:120/208 Wye A.I.C. RATING:0 PROJECT:
PANEL: CP7
PAYNE ENGINEERING
S = SHUNT-TRIP BREAKER G = GFCI BREAKER R = RED HANDLED, LOCK-OUT TYPE
A = ARC-FAULT BREAKER GP = GFEPD BREAKER LCP = CRKT TO BE ROUTED THROUGH LTG CONTROL PANEL
BRK NOTES:
TOTAL ESTIMATED DEMAND AMPS:11 A
TOTAL AMPS:22 A 6 A 5 A
TOTAL LOAD:2.6 kVA 0.7 kVA 0.6 kVA
41 42
39 40
37 38
35 36
33 34
31 32
29 30
27 28
25 26
23 24
21 22
19 20
17 18
15 16
13 14
11 12
9 10
7 ADA Door Opener 20 A 1 1000 8
5 CH-2 20 A 1 83 500 1 20 A Power 6
3 CH-1 20 A 1 173 500 1 20 A Other 4
1 Power 20 A 1 1500 83 1 20 A CH-3 2
CKT CIRCUIT DESCRIPTION NOTE AMPS P A B C P AMPS NOTE CIRCUIT DESCRIPTION CKT
NOTES:
MFG & MODEL:SQ. D/NQ SERIES DIMENSIONS:20"W x 5.8"D x *"H FEED:
ENCLOSURE: BUSSING:SEE SPEC'S MBR AMPS:N/A
MOUNTING:WIRES:4 PANEL AMPS:225 A
FED FROM: PHASES:3 PANEL TYPE:MLO MCK Library Remodel
LOCATION:Room 1-M VOLTAGE:120/208 Wye A.I.C. RATING:0 PROJECT:
PANEL: EW3
PAYNE ENGINEERING
S = SHUNT-TRIP BREAKER G = GFCI BREAKER R = RED HANDLED, LOCK-OUT TYPE
A = ARC-FAULT BREAKER GP = GFEPD BREAKER LCP = CRKT TO BE ROUTED THROUGH LTG CONTROL PANEL
BRK NOTES:
TOTAL ESTIMATED DEMAND AMPS:34 A
TOTAL AMPS:46 A 38 A 33 A
TOTAL LOAD:5.4 kVA 4.5 kVA 4.0 kVA
41 42
39 40
37 38
35 36
33 34
31 32
29 30
27 28
25 26
23 24
21 Power 20 A 1 500 22
19 Receptacle 20 A 1 360 0 1 20 A -- Smoke Dampers 20
17 Receptacle 20 A 1 360 180 1 20 A G Drinking Fountain 18
15 Receptacle 20 A 1 360 720 1 20 A Receptacle 16
13 Receptacle 20 A 1 720 1080 1 20 A Receptacle 14
11 Receptacle 20 A 1 540 900 1 20 A Receptacle 12
9 Receptacle 20 A 1 900 360 1 20 A Receptacle 10
7 Receptacle 20 A 1 1080 360 1 20 A Receptacle 8
5 Receptacle 20 A 1 900 1080 1 20 A Receptacle 6
3 Receptacle 20 A 1 900 720 1 20 A Receptacle 4
1 Receptacle 20 A 1 720 1080 1 20 A Receptacle 2
CKT CIRCUIT DESCRIPTION NOTE AMPS P A B C P AMPS NOTE CIRCUIT DESCRIPTION CKT
NOTES:
MFG & MODEL:SQ. D/NQ SERIES DIMENSIONS:20"W x 5.8"D x *"H FEED:
ENCLOSURE: BUSSING:SEE SPEC'S MBR AMPS:N/A
MOUNTING:WIRES:4 PANEL AMPS:225 A
FED FROM: PHASES:3 PANEL TYPE:MLO MCK Library Remodel
LOCATION:ELEC ROOM 102 VOLTAGE:120/208 Wye A.I.C. RATING:0 PROJECT:
PANEL: CP9
PAYNE ENGINEERING
S = SHUNT-TRIP BREAKER G = GFCI BREAKER R = RED HANDLED, LOCK-OUT TYPE
A = ARC-FAULT BREAKER GP = GFEPD BREAKER LCP = CRKT TO BE ROUTED THROUGH LTG CONTROL PANEL
BRK NOTES:
TOTAL ESTIMATED DEMAND AMPS:23 A
TOTAL AMPS:34 A 28 A 12 A
TOTAL LOAD:3.8 kVA 3.1 kVA 1.4 kVA
41 42
39 40
37 38
35 36
33 34
31 32
29 30
27 28
25 26
23 24
21 22
19 20
17 18
15 Receptacle 20 A 1 360 16
13 Receptacle 20 A 1 900 14
11 Receptacle 20 A 1 540 180 1 20 A Receptacle 12
9 Receptacle 20 A 1 900 180 1 20 A Receptacle 10
7 Receptacle 20 A 1 900 540 1 20 A Receptacle 8
5 Receptacle 20 A 1 540 180 1 20 A Receptacle 6
3 Receptacle 20 A 1 720 900 1 20 A Receptacle 4
1 Receptacle 20 A 1 720 720 1 20 A Receptacle 2
CKT CIRCUIT DESCRIPTION NOTE AMPS P A B C P AMPS NOTE CIRCUIT DESCRIPTION CKT
NOTES:
MFG & MODEL:SQ. D/NQ SERIES DIMENSIONS:20"W x 5.8"D x *"H FEED:
ENCLOSURE: BUSSING:SEE SPEC'S MBR AMPS:N/A
MOUNTING:WIRES:4 PANEL AMPS:225 A
FED FROM: PHASES:3 PANEL TYPE:MLO MCK Library Remodel
LOCATION:ELEC ROOM 102 VOLTAGE:120/208 Wye A.I.C. RATING:0 PROJECT:
PANEL: CP10
PAYNE ENGINEERING
S = SHUNT-TRIP BREAKER G = GFCI BREAKER R = RED HANDLED, LOCK-OUT TYPE
A = ARC-FAULT BREAKER GP = GFEPD BREAKER LCP = CRKT TO BE ROUTED THROUGH LTG CONTROL PANEL
BRK NOTES:
TOTAL ESTIMATED DEMAND AMPS:55 A
TOTAL AMPS:53 A 61 A 51 A
TOTAL LOAD:6.4 kVA 7.3 kVA 6.1 kVA
41 42
39 40
37 38
35 36
33 34
31 32
29 30
27 28
25 26
23 24
21 22
19 20
17 Lighting 20 A 1 1640 472 1 20 A Lighting 18
15 Lighting 20 A 1 1593 528 1 20 A Exterior Lighting 16
13 Lighting 20 A 1 583 1400 1 20 A Lighting 14
11 Lighting 20 A 1 866 1220 1 20 A Lighting 12
9 Lighting 20 A 1 2378 1664 1 20 A Lighting 10
7 Lighting 20 A 1 780 1430 1 20 A Lighting 8
5 Lighting 20 A 1 1014 959 1 20 A Lighting 6
3 Lighting 20 A 1 735 435 1 20 A Lighting 4
1 Lighting 20 A 1 1005 1195 1 20 A Lighting 2
CKT CIRCUIT DESCRIPTION NOTE AMPS P A B C P AMPS NOTE CIRCUIT DESCRIPTION CKT
NOTES:
MFG & MODEL:SQ. D/NQ SERIES DIMENSIONS:20"W x 5.8"D x *"H FEED:
ENCLOSURE: BUSSING:SEE SPEC'S MBR AMPS:N/A
MOUNTING:WIRES:4 PANEL AMPS:225 A
FED FROM: PHASES:3 PANEL TYPE:MLO MCK Library Remodel
LOCATION:ELEC ROOM 102 VOLTAGE:120/208 Wye A.I.C. RATING:0 PROJECT:
PANEL: 1LB
PAYNE ENGINEERING
S = SHUNT-TRIP BREAKER G = GFCI BREAKER R = RED HANDLED, LOCK-OUT TYPE
A = ARC-FAULT BREAKER GP = GFEPD BREAKER LCP = CRKT TO BE ROUTED THROUGH LTG CONTROL PANEL
BRK NOTES:
TOTAL ESTIMATED DEMAND AMPS:33 A
TOTAL AMPS:38 A 36 A 33 A
TOTAL LOAD:4.5 kVA 4.3 kVA 4.0 kVA
41 42
39 40
37 38
35 36
33 34
31 32
29 30
27 28
25 26
23 FCU-1 15 A 1 586 24
21 22
19 20
17 Receptacle 20 A 1 540 500 1 20 A Power 18
15 Receptacle 20 A 1 720 540 1 20 A Receptacle 16
13 Receptacle 20 A 1 540 540 1 20 A Receptacle 14
11 Drinking Fountain 20 A 1 180 540 1 20 A Receptacle 12
9 Receptacle 20 A 1 900 540 1 20 A Receptacle 10
7 Receptacle 20 A 1 720 1080 1 20 A Receptacle 8
5 Receptacle 20 A 1 900 720 1 20 A Receptacle 6
3 Receptacle 20 A 1 720 900 1 20 A Receptacle 4
1 Receptacle 20 A 1 900 720 1 20 A Receptacle 2
CKT CIRCUIT DESCRIPTION NOTE AMPS P A B C P AMPS NOTE CIRCUIT DESCRIPTION CKT
NOTES:
MFG & MODEL:SQ. D/NQ SERIES DIMENSIONS:20"W x 5.8"D x *"H FEED:
ENCLOSURE: BUSSING:SEE SPEC'S MBR AMPS:N/A
MOUNTING:WIRES:4 PANEL AMPS:225 A
FED FROM: PHASES:3 PANEL TYPE:MLO MCK Library Remodel
LOCATION:ELEC ROOM 102 VOLTAGE:120/208 Wye A.I.C. RATING:0 PROJECT:
PANEL: CP11
PAYNE ENGINEERING
S = SHUNT-TRIP BREAKER G = GFCI BREAKER R = RED HANDLED, LOCK-OUT TYPE
A = ARC-FAULT BREAKER GP = GFEPD BREAKER LCP = CRKT TO BE ROUTED THROUGH LTG CONTROL PANEL
BRK NOTES:
TOTAL ESTIMATED DEMAND AMPS:4 A
TOTAL AMPS:5 A 10 A 0 A
TOTAL LOAD:0.5 kVA 1.1 kVA 0.0 kVA
41 42
39 40
37 38
35 36
33 34
31 32
29 30
27 28
25 26
23 24
21 22
19 20
17 18
15 16
13 14
11 12
9 10
7 8
5 6
3 Receptacle 20 A 1 1080 4
1 Receptacle 20 A 1 540 2
CKT CIRCUIT DESCRIPTION NOTE AMPS P A B C P AMPS NOTE CIRCUIT DESCRIPTION CKT
NOTES:
MFG & MODEL:SQ. D/NQ SERIES DIMENSIONS:20"W x 5.8"D x *"H FEED:
ENCLOSURE: BUSSING:SEE SPEC'S MBR AMPS:N/A
MOUNTING:WIRES:4 PANEL AMPS:225 A
FED FROM: PHASES:3 PANEL TYPE:MLO MCK Library Remodel
LOCATION: VOLTAGE:120/208 Wye A.I.C. RATING:0 PROJECT:
PANEL: B
PAYNE ENGINEERING
S = SHUNT-TRIP BREAKER G = GFCI BREAKER R = RED HANDLED, LOCK-OUT TYPE
A = ARC-FAULT BREAKER GP = GFEPD BREAKER LCP = CRKT TO BE ROUTED THROUGH LTG CONTROL PANEL
BRK NOTES:
TOTAL ESTIMATED DEMAND AMPS:15 A
TOTAL AMPS:21 A 8 A 20 A
TOTAL LOAD:2.3 kVA 0.9 kVA 2.2 kVA
41 42
39 40
37 38
35 36
33 34
31 32
29 30
27 28
25 26
23 24
21 22
19 20
17 18
15 16
13 14
11 12
9 10
7 Lighting 20 A 1 300 8
5 Lighting 20 A 1 1145 1095 1 20 A Lighting 6
3 Lighting 20 A 1 60 860 1 20 A Lighting 4
1 Stair Lighting 20 A 1 520 1490 1 20 A Lighting 2
CKT CIRCUIT DESCRIPTION NOTE AMPS P A B C P AMPS NOTE CIRCUIT DESCRIPTION CKT
NOTES:
MFG & MODEL:SQ. D/NQ SERIES DIMENSIONS:20"W x 5.8"D x *"H FEED:
ENCLOSURE: BUSSING:SEE SPEC'S MBR AMPS:N/A
MOUNTING:WIRES:4 PANEL AMPS:225 A
FED FROM: PHASES:3 PANEL TYPE:MLO MCK Library Remodel
LOCATION:ELECTRICAL 038 VOLTAGE:120/208 Wye A.I.C. RATING:0 PROJECT:
PANEL: O
PAYNE ENGINEERING
S = SHUNT-TRIP BREAKER G = GFCI BREAKER R = RED HANDLED, LOCK-OUT TYPE
A = ARC-FAULT BREAKER GP = GFEPD BREAKER LCP = CRKT TO BE ROUTED THROUGH LTG CONTROL PANEL
BRK NOTES:
TOTAL ESTIMATED DEMAND AMPS:15 A
TOTAL AMPS:19 A 17 A 11 A
TOTAL LOAD:2.2 kVA 1.9 kVA 1.3 kVA
41 42
39 40
37 38
35 36
33 34
31 32
29 30
27 28
25 26
23 24
21 22
19 20
17 18
15 16
13 14
11 Receptacle 20 A 1 180 12
9 Power 20 A 1 500 10
7 Receptacle 20 A 1 540 8
5 Receptacle 20 A 1 540 540 1 20 A Receptacle 6
3 Receptacle 20 A 1 720 720 1 20 A Receptacle 4
1 Receptacle 20 A 1 540 1080 1 20 A Receptacle 2
CKT CIRCUIT DESCRIPTION NOTE AMPS P A B C P AMPS NOTE CIRCUIT DESCRIPTION CKT
NOTES:
MFG & MODEL:SQ. D/NQ SERIES DIMENSIONS:20"W x 5.8"D x *"H FEED:
ENCLOSURE: BUSSING:SEE SPEC'S MBR AMPS:N/A
MOUNTING:WIRES:4 PANEL AMPS:225 A
FED FROM: PHASES:3 PANEL TYPE:MLO MCK Library Remodel
LOCATION: VOLTAGE:120/208 Wye A.I.C. RATING:0 PROJECT:
PANEL: R
PAYNE ENGINEERING
8270
STATEOFIDAHO
T
ODD P A Y N EREGISTER
EDRP
OFESSIONALEN
G
I
NE
E
R
1823 E. Center
Pocatello, Idaho 83201
tel (208) 232-4439
www.payneengineeringinc.com
Engineering Inc.
Consulting Engineers
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
P.E. #:2259
10-28-2022 EE501
PANEL
SCHEDULES
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
BID SET
S = SHUNT-TRIP BREAKER G = GFCI BREAKER R = RED HANDLED, LOCK-OUT TYPE
A = ARC-FAULT BREAKER GP = GFEPD BREAKER LCP = CRKT TO BE ROUTED THROUGH LTG CONTROL PANEL
BRK NOTES:
TOTAL ESTIMATED DEMAND AMPS:47 A
TOTAL AMPS:68 A 62 A 70 A
TOTAL LOAD:8.0 kVA 7.5 kVA 8.3 kVA
41 42
39 40
37 38
35 36
33 34
31 32
29 Receptacle 20 A 1 540 900 1 20 A Receptacle 30
27 Receptacle 20 A 1 900 1000 1 20 A Receptacle 28
25 Receptacle 20 A 1 720 540 1 20 A Receptacle 26
23 Receptacle 20 A 1 360 360 1 20 A Receptacle 24
21 Receptacle 20 A 1 720 720 1 20 A Receptacle 22
19 Receptacle 20 A 1 1080 540 1 20 A Receptacle 20
17 Receptacle 20 A 1 720 720 1 20 A Receptacle 18
15 Receptacle 20 A 1 720 720 1 20 A Receptacle 16
13 Receptacle 20 A 1 720 720 1 20 A Receptacle 14
11 Receptacle 20 A 1 900 1080 1 20 A Receptacle 12
9 Receptacle 20 A 1 180 540 1 20 A Receptacle 10
7 Receptacle 20 A 1 720 1720 1 20 A Receptacle 8
5 Receptacle 20 A 1 1800 900 1 20 A Receptacle 6
3 Receptacle 20 A 1 1260 720 1 20 A Receptacle 4
1 Drinking Fountain G 20 A 1 180 1080 1 20 A Receptacle 2
CKT CIRCUIT DESCRIPTION NOTE AMPS P A B C P AMPS NOTE CIRCUIT DESCRIPTION CKT
NOTES:
MFG & MODEL:SQ. D/NQ SERIES DIMENSIONS:20"W x 5.8"D x *"H FEED:
ENCLOSURE: BUSSING:SEE SPEC'S MBR AMPS:N/A
MOUNTING:WIRES:4 PANEL AMPS:225 A
FED FROM:M (EAST)PHASES:3 PANEL TYPE:MLO MCK Library Remodel
LOCATION:ELECTRICAL 173 VOLTAGE:120/208 Wye A.I.C. RATING:0 PROJECT:
PANEL: 1A
PAYNE ENGINEERING
S = SHUNT-TRIP BREAKER G = GFCI BREAKER R = RED HANDLED, LOCK-OUT TYPE
A = ARC-FAULT BREAKER GP = GFEPD BREAKER LCP = CRKT TO BE ROUTED THROUGH LTG CONTROL PANEL
BRK NOTES:
TOTAL ESTIMATED DEMAND AMPS:44 A
TOTAL AMPS:52 A 54 A 32 A
TOTAL LOAD:6.0 kVA 6.2 kVA 3.9 kVA
41 42
39 40
37 38
35 36
33 34
31 32
29 30
27 28
25 26
23 24
21 22
19 20
17 18
15 16
13 Lighting 20 A 1 114 14
11 Lighting 20 A 1 1650 0 1 20 A -- HEAT TAPE CONTROL 12
9 Lighting 20 A 1 1765 1692 1 20 A Lighting 10
7 Lighting 20 A 1 1200 1410 1 20 A Lighting 8
5 Lighting 20 A 1 1392 835 1 20 A Lighting 6
3 Lighting 20 A 1 1166 1560 1 20 A Lighting 4
1 Lighting 20 A 1 1591 1660 1 20 A Lighting 2
CKT CIRCUIT DESCRIPTION NOTE AMPS P A B C P AMPS NOTE CIRCUIT DESCRIPTION CKT
NOTES:
MFG & MODEL:SQ. D/NQ SERIES DIMENSIONS:20"W x 5.8"D x *"H FEED:
ENCLOSURE: BUSSING:SEE SPEC'S MBR AMPS:N/A
MOUNTING:WIRES:4 PANEL AMPS:225 A
FED FROM:M (EAST)PHASES:3 PANEL TYPE:MLO MCK Library Remodel
LOCATION:ELECTRICAL 173 VOLTAGE:120/208 Wye A.I.C. RATING:0 PROJECT:
PANEL: 1LA
PAYNE ENGINEERING
S = SHUNT-TRIP BREAKER G = GFCI BREAKER R = RED HANDLED, LOCK-OUT TYPE
A = ARC-FAULT BREAKER GP = GFEPD BREAKER LCP = CRKT TO BE ROUTED THROUGH LTG CONTROL PANEL
BRK NOTES:
TOTAL ESTIMATED DEMAND AMPS:43 A
TOTAL AMPS:58 A 55 A 54 A
TOTAL LOAD:7.0 kVA 6.6 kVA 6.5 kVA
41 42
39 40
37 38
35 36
33 34
31 32
29 30
27 28
25 26
23 Receptacle 20 A 1 720 720 1 20 A Receptacle 24
21 Receptacle 20 A 1 1080 500 1 20 A Power 22
19 Receptacle 20 A 1 1080 500 1 20 A GP HEAT TRACE 20
17 Receptacle 20 A 1 720 900 1 20 A Receptacle 18
15 Receptacle 20 A 1 720 360 1 20 A Receptacle 16
13 Receptacle 20 A 1 900 1080 1 20 A Receptacle 14
11 Receptacle 20 A 1 1260 1080 1 20 A Receptacle 12
9 Receptacle 20 A 1 1080 1260 1 20 A Receptacle 10
7 Receptacle 20 A 1 720 1080 1 20 A Receptacle 8
5 Receptacle 20 A 1 900 180 1 20 A G Drinking Fountain 6
3 Receptacle 20 A 1 720 900 1 20 A Receptacle 4
1 Receptacle 20 A 1 900 720 1 20 A Receptacle 2
CKT CIRCUIT DESCRIPTION NOTE AMPS P A B C P AMPS NOTE CIRCUIT DESCRIPTION CKT
NOTES:
MFG & MODEL:SQ. D/NQ SERIES DIMENSIONS:20"W x 5.8"D x *"H FEED:
ENCLOSURE: BUSSING:SEE SPEC'S MBR AMPS:N/A
MOUNTING:WIRES:4 PANEL AMPS:225 A
FED FROM:M (EAST)PHASES:3 PANEL TYPE:MLO MCK Library Remodel
LOCATION:ELECTRICAL 173 VOLTAGE:120/208 Wye A.I.C. RATING:0 PROJECT:
PANEL: CP1
PAYNE ENGINEERING
S = SHUNT-TRIP BREAKER G = GFCI BREAKER R = RED HANDLED, LOCK-OUT TYPE
A = ARC-FAULT BREAKER GP = GFEPD BREAKER LCP = CRKT TO BE ROUTED THROUGH LTG CONTROL PANEL
BRK NOTES:
TOTAL ESTIMATED DEMAND AMPS:36 A
TOTAL AMPS:53 A 48 A 35 A
TOTAL LOAD:6.1 kVA 5.6 kVA 4.1 kVA
41 42
39 40
37 38
35 36
33 34
31 32
29 30
27 28
25 26
23 Drinking Fountain G 20 A 1 180 24
21 Receptacle 20 A 1 1080 22
19 Receptacle 20 A 1 1080 180 1 20 A Receptacle 20
17 Receptacle 20 A 1 720 360 1 20 A Receptacle 18
15 Receptacle 20 A 1 360 1080 1 20 A Receptacle 16
13 Receptacle 20 A 1 900 900 1 20 A Receptacle 14
11 Receptacle 20 A 1 900 720 1 20 A Receptacle 12
9 Receptacle 20 A 1 1080 720 1 20 A Receptacle 10
7 Receptacle 20 A 1 1080 900 1 20 A Receptacle 8
5 Receptacle 20 A 1 360 900 1 20 A Receptacle 6
3 Receptacle 20 A 1 540 720 1 20 A Receptacle 4
1 Receptacle 20 A 1 540 540 1 20 A Receptacle 2
CKT CIRCUIT DESCRIPTION NOTE AMPS P A B C P AMPS NOTE CIRCUIT DESCRIPTION CKT
NOTES:
MFG & MODEL:SQ. D/NQ SERIES DIMENSIONS:20"W x 5.8"D x *"H FEED:
ENCLOSURE: BUSSING:SEE SPEC'S MBR AMPS:N/A
MOUNTING:WIRES:4 PANEL AMPS:225 A
FED FROM:M (EAST)PHASES:3 PANEL TYPE:MLO MCK Library Remodel
LOCATION:ELECTRICAL 173 VOLTAGE:120/208 Wye A.I.C. RATING:0 PROJECT:
PANEL: CP2
PAYNE ENGINEERING
S = SHUNT-TRIP BREAKER G = GFCI BREAKER R = RED HANDLED, LOCK-OUT TYPE
A = ARC-FAULT BREAKER GP = GFEPD BREAKER LCP = CRKT TO BE ROUTED THROUGH LTG CONTROL PANEL
BRK NOTES:
TOTAL ESTIMATED DEMAND AMPS:22 A
TOTAL AMPS:23 A 30 A 15 A
TOTAL LOAD:2.7 kVA 3.4 kVA 1.8 kVA
41 42
39 40
37 38
35 36
33 34
31 32
29 30
27 28
25 26
23 24
21 22
19 20
17 18
15 16
13 14
11 Receptacle 20 A 1 540 12
9 Receptacle 20 A 1 720 10
7 Receptacle 20 A 1 900 500 1 20 A Power 8
5 Receptacle 20 A 1 900 360 1 20 A Receptacle 6
3 Receptacle 20 A 1 1440 1260 1 20 A Receptacle 4
1 Receptacle 20 A 1 360 900 1 20 A Receptacle 2
CKT CIRCUIT DESCRIPTION NOTE AMPS P A B C P AMPS NOTE CIRCUIT DESCRIPTION CKT
NOTES:
MFG & MODEL:SQ. D/NQ SERIES DIMENSIONS:20"W x 5.8"D x *"H FEED:
ENCLOSURE: BUSSING:SEE SPEC'S MBR AMPS:N/A
MOUNTING:WIRES:4 PANEL AMPS:225 A
FED FROM:M (EAST)PHASES:3 PANEL TYPE:MLO MCK Library Remodel
LOCATION:ELECTRICAL 173 VOLTAGE:120/208 Wye A.I.C. RATING:0 PROJECT:
PANEL: CP3
PAYNE ENGINEERING
S = SHUNT-TRIP BREAKER G = GFCI BREAKER R = RED HANDLED, LOCK-OUT TYPE
A = ARC-FAULT BREAKER GP = GFEPD BREAKER LCP = CRKT TO BE ROUTED THROUGH LTG CONTROL PANEL
BRK NOTES:
TOTAL ESTIMATED DEMAND AMPS:15 A
TOTAL AMPS:12 A 19 A 15 A
TOTAL LOAD:1.4 kVA 2.3 kVA 1.7 kVA
41 42
39 40
37 38
35 36
33 34
31 32
29 30
27 28
25 26
23 24
21 22
19 20
17 18
15 16
13 14
11 12
9 Receptacle 20 A 1 1000 10
7 Receptacle 20 A 1 720 8
5 Receptacle 20 A 1 720 1000 1 20 A Receptacle 6
3 Receptacle 20 A 1 720 540 1 20 A Receptacle 4
1 720 1 20 A Receptacle 2
CKT CIRCUIT DESCRIPTION NOTE AMPS P A B C P AMPS NOTE CIRCUIT DESCRIPTION CKT
NOTES:
MFG & MODEL:SQ. D/NQ SERIES DIMENSIONS:20"W x 5.8"D x *"H FEED:
ENCLOSURE: BUSSING:SEE SPEC'S MBR AMPS:N/A
MOUNTING:WIRES:4 PANEL AMPS:225 A
FED FROM:M (EAST)PHASES:3 PANEL TYPE:MLO MCK Library Remodel
LOCATION:ELECTRICAL 173 VOLTAGE:120/208 Wye A.I.C. RATING:0 PROJECT:
PANEL: CP4
PAYNE ENGINEERING
POWER-MISC.10000 VA 100.00% 10000 VA
Power 2000 VA 100.00% 2000 VA TOTAL EST. DEMAND...343 A
Receptacle 135400 VA 53.69% 72700 VA TOTAL CONN. AMPS:516 A
Other 0 VA 0.00% 0 VA TOTAL EST. DEMAND:123 kW
Motor 5500 VA 107.53% 5914 VA TOTAL CONN. LOAD:186 kW
Lighting 32843 VA 100.00% 32843 VA
LOAD CLASSIFICATION CONNECTED... DEMAND FACTOR EST. DEMAND PANEL TOTALS
PANEL LOAD SUMMARY
TOTAL AMPS:516 A
TOTAL CONN....186 kW
15 ELEVATOR BREAKER 3 400 A 100 A 0 kW
14 PANEL CP8 3 400 A 150 A 0 kW
13 PANEL CP6 3 400 A 150 A 7 kW
12 PANEL CP5 3 400 A 150 A 25 kW
11 PANEL 2LA 3 400 A 200 A 16 kW
10 PANEL 2B 3 400 A 150 A 26 kW
9 PANEL 2A 3 400 A 150 A 20 kW
8 PANEL 1P 3 400 A 200 A 2 kW
7 PANEL CC 3 400 A 150 A 0 kW
6 PANEL CP4 3 400 A 150 A 5 kW
5 PANEL CP3 3 400 A 150 A 8 kW
4 PANEL CP2 3 400 A 150 A 16 kW
3 PANEL CP1 3 400 A 100 A 20 kW
2 PANEL 1LA 3 400 A 150 A 16 kW
1 PANEL 1A 3 400 A 150 A 24 kW
CKT CIRCUIT DESCRIPTION POLES
FRAME
AMPS
TRIP
AMPS LOAD REMARKS
NETWORK AND PROGRAM POWER LOGIC METERING PER BYU-I STANDARD
NOTES:
MFG/MODEL:SQ. D/QED SERIES DIMENSIONS: FEED:
ENCLOSURE: BUSSING:SEE SPEC'S MBR AMPS:1600 A
MOUNTING: WIRES:4 PANEL AMPS:1600 A
FED FROM: PHASES:3 PANEL TYPE:MBR MCK Library Remodel
LOCATION:MECH 08 VOLTAGE:120/208 Wye A.I.C. RATING:0 PROJECT:
PANEL: M (EAST)
PAYNE ENGINEERING
8270
STATEOFIDAHO
T
ODD P A Y N EREGISTER
EDRP
OFESSIONALEN
G
I
NE
E
R
1823 E. Center
Pocatello, Idaho 83201
tel (208) 232-4439
www.payneengineeringinc.com
Engineering Inc.
Consulting Engineers
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
P.E. #:2259
10-28-2022 EE502
PANEL
SCHEDULES
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
BID SET
S = SHUNT-TRIP BREAKER G = GFCI BREAKER R = RED HANDLED, LOCK-OUT TYPE
A = ARC-FAULT BREAKER GP = GFEPD BREAKER LCP = CRKT TO BE ROUTED THROUGH LTG CONTROL PANEL
BRK NOTES:
TOTAL ESTIMATED DEMAND AMPS:50 A
TOTAL AMPS:46 A 60 A 41 A
TOTAL LOAD:5.4 kVA 7.1 kVA 4.9 kVA
41 42
39 40
37 38
35 36
33 34
31 32
29 30
27 28
25 26
23 24
21 2222 22
19 Split System 245B 40 A 2
2222 20
17 Other 20 A 1 500 2222 18
15 Other 20 A 1 500 2222 2 40 A Split System 245A
16
13 Power 20 A 1 500 500 1 20 A Other 14
11 288 990 12
9 288 990 10
7
DXFCU-1(CONDENSING UNIT) 20 A 3
288 990
3 15 A H-1
8
5 Receptacle 20 A 1 360 552 6
3 Receptacle 20 A 1 360 552 4
1 Receptacle 20 A 1 360 552
3 15 A DXFCU-1(FAN COIL)
2
CKT CIRCUIT DESCRIPTION NOTE AMPS P A B C P AMPS NOTE CIRCUIT DESCRIPTION CKT
NOTES:
MFG & MODEL:SQ. D/NQ SERIES DIMENSIONS:20"W x 5.8"D x *"H FEED:
ENCLOSURE: BUSSING:SEE SPEC'S MBR AMPS:N/A
MOUNTING:WIRES:4 PANEL AMPS:225 A
FED FROM: PHASES:3 PANEL TYPE:MLO MCK Library Remodel
LOCATION:ELECTRICAL ROOM 242 VOLTAGE:120/208 Wye A.I.C. RATING:0 PROJECT:
PANEL: EW2
PAYNE ENGINEERING
S = SHUNT-TRIP BREAKER G = GFCI BREAKER R = RED HANDLED, LOCK-OUT TYPE
A = ARC-FAULT BREAKER GP = GFEPD BREAKER LCP = CRKT TO BE ROUTED THROUGH LTG CONTROL PANEL
BRK NOTES:
TOTAL ESTIMATED DEMAND AMPS:28 A
TOTAL AMPS:43 A 21 A 21 A
TOTAL LOAD:5.2 kVA 2.5 kVA 2.5 kVA
41 42
39 40
37 38
35 36
33 34
31 32
29 30
27 28
25 26
23 24
21 22
19 20
17 18
15 16
13 14
11 12
9 10
7 Receptacle 20 A 1 180 2500 8
5 2500 2 20 A 6l-20 Receptacle
6
3 2500 4
1 2500 2 20 A 6L-20 Receptacle
2
CKT CIRCUIT DESCRIPTION NOTE AMPS P A B C P AMPS NOTE CIRCUIT DESCRIPTION CKT
NOTES:
MFG & MODEL:SQ. D/NQ SERIES DIMENSIONS:20"W x 5.8"D x *"H FEED:
ENCLOSURE: BUSSING:SEE SPEC'S MBR AMPS:N/A
MOUNTING:WIRES:4 PANEL AMPS:225 A
FED FROM: PHASES:3 PANEL TYPE:MLO MCK Library Remodel
LOCATION:I.T. 245 VOLTAGE:120/208 Wye A.I.C. RATING:0 PROJECT:
PANEL: UPS
PAYNE ENGINEERING
S = SHUNT-TRIP BREAKER G = GFCI BREAKER R = RED HANDLED, LOCK-OUT TYPE
A = ARC-FAULT BREAKER GP = GFEPD BREAKER LCP = CRKT TO BE ROUTED THROUGH LTG CONTROL PANEL
BRK NOTES:
TOTAL ESTIMATED DEMAND AMPS:53 A
TOTAL AMPS:67 A 61 A 68 A
TOTAL LOAD:7.9 kVA 7.4 kVA 8.1 kVA
41 42
39 40
37 38
35 Receptacle 20 A 1 540 36
33 Power 20 A 1 500 34
31 552 32
29 552 552 30
27
Partition Wall 20 A 3
552 552 28
25 Receptacle 20 A 1 720 552
3 20 A Partition Wall
26
23 Receptacle 20 A 1 720 720 1 20 A Receptacle 24
21 Receptacle 20 A 1 720 360 1 20 A Receptacle 22
19 Receptacle 20 A 1 720 360 1 20 A Receptacle 20
17 Receptacle 20 A 1 1080 720 1 20 A Receptacle 18
15 Receptacle 20 A 1 900 900 1 20 A Receptacle 16
13 Receptacle 20 A 1 720 1080 1 20 A Receptacle 14
11 Receptacle 20 A 1 720 900 1 20 A Receptacle 12
9 Receptacle 20 A 1 540 720 1 20 A Receptacle 10
7 Receptacle 20 A 1 720 900 1 20 A Receptacle 8
5 Receptacle 20 A 1 720 900 1 20 A Receptacle 6
3 Receptacle 20 A 1 900 720 1 20 A Receptacle 4
1 Receptacle 20 A 1 900 720 1 20 A Receptacle 2
CKT CIRCUIT DESCRIPTION NOTE AMPS P A B C P AMPS NOTE CIRCUIT DESCRIPTION CKT
NOTES:
MFG & MODEL:SQ. D/NQ SERIES DIMENSIONS:20"W x 5.8"D x *"H FEED:
ENCLOSURE: BUSSING:SEE SPEC'S MBR AMPS:N/A
MOUNTING:WIRES:4 PANEL AMPS:225 A
FED FROM: PHASES:3 PANEL TYPE:MLO MCK Library Remodel
LOCATION:ELECTRICAL ROOM 242 VOLTAGE:120/208 Wye A.I.C. RATING:0 PROJECT:
PANEL: D
PAYNE ENGINEERING
S = SHUNT-TRIP BREAKER G = GFCI BREAKER R = RED HANDLED, LOCK-OUT TYPE
A = ARC-FAULT BREAKER GP = GFEPD BREAKER LCP = CRKT TO BE ROUTED THROUGH LTG CONTROL PANEL
BRK NOTES:
TOTAL ESTIMATED DEMAND AMPS:66 A
TOTAL AMPS:82 A 78 A 67 A
TOTAL LOAD:9.7 kVA 9.2 kVA 8.0 kVA
41 42
39 40
37 38
35 36
33 34
31 32
29 Receptacle 20 A 1 180 500 1 20 A Power 30
27 2500 720 1 20 A Receptacle 28
25 Electric Clothes Dryer 20 A 2
2500 2500 26
23 Receptacle 20 A 1 720 2500 2 20 A Electric Clothes Dryer
24
21 Receptacle 20 A 1 720 360 1 20 A Receptacle 22
19 Receptacle 20 A 1 1080 360 1 20 A Receptacle 20
17 Receptacle 20 A 1 720 900 1 20 A Receptacle 18
15 Receptacle 20 A 1 720 900 1 20 A Receptacle 16
13 Receptacle 20 A 1 180 720 1 20 A Receptacle 14
11 Receptacle 20 A 1 720 720 1 20 A Receptacle 12
9 Receptacle 20 A 1 900 900 1 20 A Receptacle 10
7 Receptacle 20 A 1 540 720 1 20 A Receptacle 8
5 Drinking Fountain G 20 A 1 180 900 1 20 A Receptacle 6
3 Receptacle 20 A 1 720 720 1 20 A Receptacle 4
1 Receptacle 20 A 1 540 540 1 20 A Receptacle 2
CKT CIRCUIT DESCRIPTION NOTE AMPS P A B C P AMPS NOTE CIRCUIT DESCRIPTION CKT
NOTES:
MFG & MODEL:SQ. D/NQ SERIES DIMENSIONS:20"W x 5.8"D x *"H FEED:
ENCLOSURE: BUSSING:SEE SPEC'S MBR AMPS:N/A
MOUNTING:WIRES:4 PANEL AMPS:225 A
FED FROM: PHASES:3 PANEL TYPE:MLO MCK Library Remodel
LOCATION:ELECTRICAL ROOM 242 VOLTAGE:120/208 Wye A.I.C. RATING:0 PROJECT:
PANEL: CP13
PAYNE ENGINEERING
S = SHUNT-TRIP BREAKER G = GFCI BREAKER R = RED HANDLED, LOCK-OUT TYPE
A = ARC-FAULT BREAKER GP = GFEPD BREAKER LCP = CRKT TO BE ROUTED THROUGH LTG CONTROL PANEL
BRK NOTES:
TOTAL ESTIMATED DEMAND AMPS:40 A
TOTAL AMPS:46 A 48 A 47 A
TOTAL LOAD:5.5 kVA 5.7 kVA 5.6 kVA
41 42
39 40
37 38
35 36
33 34
31 32
29 30
27 28
25 26
23 FCU-2 15 A 1 586 24
21 Receptacle 20 A 1 180 22
19 Receptacle 20 A 1 720 0 1 20 A -- Smoke Dampers 20
17 Receptacle 20 A 1 1080 540 1 20 A Receptacle 18
15 Receptacle 20 A 1 1080 1220 1 20 A Receptacle 16
13 Receptacle 20 A 1 720 1040 1 20 A Power 14
11 Receptacle 20 A 1 720 1440 1 20 A Receptacle 12
9 Receptacle 20 A 1 720 1440 1 20 A Receptacle 10
7 Receptacle 20 A 1 540 1440 1 20 A Receptacle 8
5 Receptacle 20 A 1 720 540 1 20 A Receptacle 6
3 Receptacle 20 A 1 540 540 1 20 A Receptacle 4
1 Receptacle 20 A 1 540 540 1 20 A Receptacle 2
CKT CIRCUIT DESCRIPTION NOTE AMPS P A B C P AMPS NOTE CIRCUIT DESCRIPTION CKT
NOTES:
MFG & MODEL:SQ. D/NQ SERIES DIMENSIONS:20"W x 5.8"D x *"H FEED:
ENCLOSURE: BUSSING:SEE SPEC'S MBR AMPS:N/A
MOUNTING:WIRES:4 PANEL AMPS:225 A
FED FROM: PHASES:3 PANEL TYPE:MLO MCK Library Remodel
LOCATION:ELECTRICAL ROOM 242 VOLTAGE:120/208 Wye A.I.C. RATING:0 PROJECT:
PANEL: CP14
PAYNE ENGINEERING
S = SHUNT-TRIP BREAKER G = GFCI BREAKER R = RED HANDLED, LOCK-OUT TYPE
A = ARC-FAULT BREAKER GP = GFEPD BREAKER LCP = CRKT TO BE ROUTED THROUGH LTG CONTROL PANEL
BRK NOTES:
TOTAL ESTIMATED DEMAND AMPS:89 A
TOTAL AMPS:122 A 117 A 48 A
TOTAL LOAD:13.5 kVA 12.9 kVA 5.8 kVA
41 42
39 40
37 38
35 36
33 34
31 32
29 30
27 28
25 26
23 24
21 22
19 20
17 18
15 Lighting 20 A 1 1239 6150 1 20 A Lighting 16
13 Lighting 20 A 1 1360 6750 1 20 A Lighting 14
11 Lighting 20 A 1 1416 1465 1 20 A Lighting 12
9 Lighting 20 A 1 1245 1240 1 20 A Lighting 10
7 Lighting 20 A 1 1284 1700 1 20 A Lighting 8
5 Lighting 20 A 1 1245 1650 1 20 A Lighting 6
3 Lighting 20 A 1 1660 1374 1 20 A Lighting 4
1 Lighting 20 A 1 1514 942 1 20 A Lighting 2
CKT CIRCUIT DESCRIPTION NOTE AMPS P A B C P AMPS NOTE CIRCUIT DESCRIPTION CKT
NOTES:
MFG & MODEL:SQ. D/NQ SERIES DIMENSIONS:20"W x 5.8"D x *"H FEED:
ENCLOSURE: BUSSING:SEE SPEC'S MBR AMPS:N/A
MOUNTING:WIRES:4 PANEL AMPS:225 A
FED FROM: PHASES:3 PANEL TYPE:MLO MCK Library Remodel
LOCATION:ELECTRICAL ROOM 242 VOLTAGE:120/208 Wye A.I.C. RATING:0 PROJECT:
PANEL: 2LB
PAYNE ENGINEERING
S = SHUNT-TRIP BREAKER G = GFCI BREAKER R = RED HANDLED, LOCK-OUT TYPE
A = ARC-FAULT BREAKER GP = GFEPD BREAKER LCP = CRKT TO BE ROUTED THROUGH LTG CONTROL PANEL
BRK NOTES:
TOTAL ESTIMATED DEMAND AMPS:0 A
TOTAL AMPS:0 A 0 A 0 A
TOTAL LOAD:0.0 kVA 0.0 kVA 0.0 kVA
41 42
39 40
37 38
35 36
33 34
31 32
29 30
27 28
25 26
23 24
21 22
19 20
17 18
15 16
13 14
11 12
9 10
7 8
5 6
3 4
1 2
CKT CIRCUIT DESCRIPTION NOTE AMPS P A B C P AMPS NOTE CIRCUIT DESCRIPTION CKT
NOTES:
MFG & MODEL:SQ. D/NQ SERIES DIMENSIONS:20"W x 5.8"D x *"H FEED:
ENCLOSURE: BUSSING:SEE SPEC'S MBR AMPS:N/A
MOUNTING:WIRES:4 PANEL AMPS:225 A
FED FROM: PHASES:3 PANEL TYPE:MLO MCK Library Remodel
LOCATION:ELECTRICAL ROOM 242 VOLTAGE:120/208 Wye A.I.C. RATING:0 PROJECT:
PANEL: 2WA
PAYNE ENGINEERING
S = SHUNT-TRIP BREAKER G = GFCI BREAKER R = RED HANDLED, LOCK-OUT TYPE
A = ARC-FAULT BREAKER GP = GFEPD BREAKER LCP = CRKT TO BE ROUTED THROUGH LTG CONTROL PANEL
BRK NOTES:
TOTAL ESTIMATED DEMAND AMPS:32 A
TOTAL AMPS:41 A 33 A 38 A
TOTAL LOAD:4.9 kVA 4.0 kVA 4.5 kVA
41 42
39 40
37 38
35 36
33 34
31 32
29 30
27 28
25 26
23 24
21 22
19 20
17 Receptacle 20 A 1 1080 540 1 20 A Receptacle 18
15 Receptacle 20 A 1 720 360 1 20 A Receptacle 16
13 Receptacle 20 A 1 900 720 1 20 A Receptacle 14
11 Receptacle 20 A 1 720 720 1 20 A Receptacle 12
9 Receptacle 20 A 1 720 720 1 20 A Receptacle 10
7 Receptacle 20 A 1 720 720 1 20 A Receptacle 8
5 Receptacle 20 A 1 720 720 1 20 A Receptacle 6
3 Receptacle 20 A 1 720 720 1 20 A Receptacle 4
1 Receptacle 20 A 1 720 1080 1 20 A Receptacle 2
CKT CIRCUIT DESCRIPTION NOTE AMPS P A B C P AMPS NOTE CIRCUIT DESCRIPTION CKT
NOTES:
MFG & MODEL:SQ. D/NQ SERIES DIMENSIONS:20"W x 5.8"D x *"H FEED:
ENCLOSURE: BUSSING:SEE SPEC'S MBR AMPS:N/A
MOUNTING:WIRES:4 PANEL AMPS:225 A
FED FROM: PHASES:3 PANEL TYPE:MLO MCK Library Remodel
LOCATION: VOLTAGE:120/208 Wye A.I.C. RATING:0 PROJECT:
PANEL: CP12
PAYNE ENGINEERING
8270
STATEOFIDAHO
T
ODD P A Y N EREGISTER
EDRP
OFESSIONALEN
G
I
NE
E
R
1823 E. Center
Pocatello, Idaho 83201
tel (208) 232-4439
www.payneengineeringinc.com
Engineering Inc.
Consulting Engineers
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
P.E. #:2259
10-28-2022 EE503
PANEL
SCHEDULES
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
BID SET
S = SHUNT-TRIP BREAKER G = GFCI BREAKER R = RED HANDLED, LOCK-OUT TYPE
A = ARC-FAULT BREAKER GP = GFEPD BREAKER LCP = CRKT TO BE ROUTED THROUGH LTG CONTROL PANEL
BRK NOTES:
TOTAL ESTIMATED DEMAND AMPS:28 A
TOTAL AMPS:23 A 42 A 21 A
TOTAL LOAD:2.7 kVA 5.0 kVA 2.5 kVA
41 42
39 40
37 38
35 36
33 34
31 32
29 30
27 28
25 26
23 24
21 22
19 20
17 18
15 16
13 14
11 12
9 10
7 8
5 2500 6
3 5000 4
1
UPS (280) 60 A 3
2680 2
CKT CIRCUIT DESCRIPTION NOTE AMPS P A B C P AMPS NOTE CIRCUIT DESCRIPTION CKT
NOTES:
MFG & MODEL:SQ. D/NQ SERIES DIMENSIONS:20"W x 5.8"D x *"H FEED:
ENCLOSURE: BUSSING:SEE SPEC'S MBR AMPS:N/A
MOUNTING:WIRES:4 PANEL AMPS:225 A
FED FROM: PHASES:3 PANEL TYPE:MLO MCK Library Remodel
LOCATION:ELECTRICAL 2-I VOLTAGE:120/208 Wye A.I.C. RATING:0 PROJECT:
PANEL: UPS1
PAYNE ENGINEERING
S = SHUNT-TRIP BREAKER G = GFCI BREAKER R = RED HANDLED, LOCK-OUT TYPE
A = ARC-FAULT BREAKER GP = GFEPD BREAKER LCP = CRKT TO BE ROUTED THROUGH LTG CONTROL PANEL
BRK NOTES:
TOTAL ESTIMATED DEMAND AMPS:29 A
TOTAL AMPS:41 A 23 A 23 A
TOTAL LOAD:4.9 kVA 2.7 kVA 2.7 kVA
41 42
39 40
37 38
35 36
33 34
31 32
29 30
27 28
25 26
23 24
21 22
19 20
17 18
15 16
13 14
11 12
9 10
7 2222 8
5 Other 20 A 1 500 2222 2 40 A Split System 280B
6
3 Other 20 A 1 500 2222 4
1 Other 20 A 1 500 2222 2 40 A Split System 280A
2
CKT CIRCUIT DESCRIPTION NOTE AMPS P A B C P AMPS NOTE CIRCUIT DESCRIPTION CKT
NOTES:
MFG & MODEL:SQ. D/NQ SERIES DIMENSIONS:20"W x 5.8"D x *"H FEED:
ENCLOSURE: BUSSING:SEE SPEC'S MBR AMPS:N/A
MOUNTING:WIRES:4 PANEL AMPS:225 A
FED FROM: PHASES:3 PANEL TYPE:MLO MCK Library Remodel
LOCATION:ELECTRICAL 2-I VOLTAGE:120/208 Wye A.I.C. RATING:0 PROJECT:
PANEL: EE2
PAYNE ENGINEERING
S = SHUNT-TRIP BREAKER G = GFCI BREAKER R = RED HANDLED, LOCK-OUT TYPE
A = ARC-FAULT BREAKER GP = GFEPD BREAKER LCP = CRKT TO BE ROUTED THROUGH LTG CONTROL PANEL
BRK NOTES:
TOTAL ESTIMATED DEMAND AMPS:43 A
TOTAL AMPS:47 A 65 A 62 A
TOTAL LOAD:5.6 kVA 7.5 kVA 7.2 kVA
41 42
39 40
37 38
35 36
33 34
31 32
29 30
27 REF-4 20 A 1 528 28
25 Receptacle 20 A 1 360 26
23 Receptacle 20 A 1 900 360 1 20 A Receptacle 24
21 Receptacle 20 A 1 900 360 1 20 A Receptacle 22
19 Receptacle 20 A 1 540 720 1 20 A Receptacle 20
17 Receptacle 20 A 1 1800 900 1 20 A Receptacle 18
15 Receptacle 20 A 1 720 1620 1 20 A Receptacle 16
13 Receptacle 20 A 1 900 360 1 20 A Receptacle 14
11 Receptacle 20 A 1 900 1080 1 20 A Receptacle 12
9 Receptacle 20 A 1 900 1080 1 20 A Receptacle 10
7 Drinking Fountain G 20 A 1 180 900 1 20 A Receptacle 8
5 Receptacle 20 A 1 900 360 1 20 A Receptacle 6
3 Receptacle 20 A 1 900 540 1 20 A Receptacle 4
1 Receptacle 20 A 1 900 720 1 20 A Receptacle 2
CKT CIRCUIT DESCRIPTION NOTE AMPS P A B C P AMPS NOTE CIRCUIT DESCRIPTION CKT
NOTES:
MFG & MODEL:SQ. D/NQ SERIES DIMENSIONS:20"W x 5.8"D x *"H FEED:
ENCLOSURE: BUSSING:SEE SPEC'S MBR AMPS:N/A
MOUNTING:WIRES:4 PANEL AMPS:225 A
FED FROM:M (EAST)PHASES:3 PANEL TYPE:MLO MCK Library Remodel
LOCATION:ELECTRICAL 2-I VOLTAGE:120/208 Wye A.I.C. RATING:0 PROJECT:
PANEL: 2A
PAYNE ENGINEERING
S = SHUNT-TRIP BREAKER G = GFCI BREAKER R = RED HANDLED, LOCK-OUT TYPE
A = ARC-FAULT BREAKER GP = GFEPD BREAKER LCP = CRKT TO BE ROUTED THROUGH LTG CONTROL PANEL
BRK NOTES:
TOTAL ESTIMATED DEMAND AMPS:46 A
TOTAL AMPS:41 A 54 A 42 A
TOTAL LOAD:4.9 kVA 6.4 kVA 5.1 kVA
41 42
39 40
37 38
35 36
33 34
31 32
29 30
27 28
25 26
23 24
21 22
19 20
17 18
15 16
13 14
11 Lighting 20 A 1 1270 1070 1 20 A Lighting 12
9 Lighting 20 A 1 1561 1615 1 20 A Lighting 10
7 Lighting 20 A 1 1031 940 1 20 A Lighting 8
5 Lighting 20 A 1 1580 1150 1 20 A Lighting 6
3 Lighting 20 A 1 1599 1673 1 20 A Lighting 4
1 Lighting 20 A 1 1549 1370 1 20 A Lighting 2
CKT CIRCUIT DESCRIPTION NOTE AMPS P A B C P AMPS NOTE CIRCUIT DESCRIPTION CKT
NOTES:
MFG & MODEL:SQ. D/NQ SERIES DIMENSIONS:20"W x 5.8"D x *"H FEED:
ENCLOSURE: BUSSING:SEE SPEC'S MBR AMPS:N/A
MOUNTING:WIRES:4 PANEL AMPS:225 A
FED FROM:M (EAST)PHASES:3 PANEL TYPE:MLO MCK Library Remodel
LOCATION:ELECTRICAL 2-I VOLTAGE:120/208 Wye A.I.C. RATING:0 PROJECT:
PANEL: 2LA
PAYNE ENGINEERING
S = SHUNT-TRIP BREAKER G = GFCI BREAKER R = RED HANDLED, LOCK-OUT TYPE
A = ARC-FAULT BREAKER GP = GFEPD BREAKER LCP = CRKT TO BE ROUTED THROUGH LTG CONTROL PANEL
BRK NOTES:
TOTAL ESTIMATED DEMAND AMPS:63 A
TOTAL AMPS:89 A 65 A 57 A
TOTAL LOAD:10.6 kVA 7.7 kVA 6.8 kVA
41 42
39 40
37 38
35 36
33 34
31 32
29 30
27 28
25 2500 26
23 6L-20 Receptacle (COMM ROOM) 20 A 2
2500 24
21 Receptacle 20 A 1 180 2500 22
19 Receptacle 20 A 1 360 2500 2 20 A 6L-20 Receptacle (COMM ROOM)
20
17 Receptacle 20 A 1 1440 900 1 20 A Receptacle 18
15 Receptacle 20 A 1 1080 720 1 20 A Receptacle 16
13 Receptacle 20 A 1 1440 720 1 20 A Receptacle 14
11 Receptacle 20 A 1 360 1260 1 20 A Receptacle 12
9 Receptacle 20 A 1 900 1080 1 20 A Receptacle 10
7 Receptacle 20 A 1 720 900 1 20 A Receptacle 8
5 Receptacle 20 A 1 180 180 1 20 A Receptacle 6
3 Receptacle 20 A 1 720 540 1 20 A Receptacle 4
1 Receptacle 20 A 1 720 720 1 20 A Receptacle 2
CKT CIRCUIT DESCRIPTION NOTE AMPS P A B C P AMPS NOTE CIRCUIT DESCRIPTION CKT
NOTES:
MFG & MODEL:SQ. D/NQ SERIES DIMENSIONS:20"W x 5.8"D x *"H FEED:
ENCLOSURE: BUSSING:SEE SPEC'S MBR AMPS:N/A
MOUNTING:WIRES:4 PANEL AMPS:225 A
FED FROM:M (EAST)PHASES:3 PANEL TYPE:MLO MCK Library Remodel
LOCATION:ELECTRICAL 2-I VOLTAGE:120/208 Wye A.I.C. RATING:0 PROJECT:
PANEL: CP5
PAYNE ENGINEERING
S = SHUNT-TRIP BREAKER G = GFCI BREAKER R = RED HANDLED, LOCK-OUT TYPE
A = ARC-FAULT BREAKER GP = GFEPD BREAKER LCP = CRKT TO BE ROUTED THROUGH LTG CONTROL PANEL
BRK NOTES:
TOTAL ESTIMATED DEMAND AMPS:21 A
TOTAL AMPS:22 A 23 A 17 A
TOTAL LOAD:2.6 kVA 2.7 kVA 2.0 kVA
41 42
39 40
37 38
35 36
33 34
31 32
29 30
27 28
25 26
23 24
21 22
19 20
17 Receptacle 20 A 1 180 18
15 Receptacle 20 A 1 180 500 1 20 A Power 16
13 Receptacle 20 A 1 180 180 1 20 A Receptacle 14
11 552 180 1 20 A Receptacle 12
9 552 360 1 20 A Receptacle 10
7
Motor 20 A 3
552 540 1 20 A Receptacle 8
5 552 552 6
3 552 552 4
1
Motor 20 A 3
552 552
3 20 A Motor
2
CKT CIRCUIT DESCRIPTION NOTE AMPS P A B C P AMPS NOTE CIRCUIT DESCRIPTION CKT
NOTES:
MFG & MODEL:SQ. D/NQ SERIES DIMENSIONS:20"W x 5.8"D x *"H FEED:
ENCLOSURE: BUSSING:SEE SPEC'S MBR AMPS:N/A
MOUNTING:WIRES:4 PANEL AMPS:225 A
FED FROM:M (EAST)PHASES:3 PANEL TYPE:MLO MCK Library Remodel
LOCATION:ELECTRICAL 2-I VOLTAGE:120/208 Wye A.I.C. RATING:0 PROJECT:
PANEL: CP6
PAYNE ENGINEERING
S = SHUNT-TRIP BREAKER G = GFCI BREAKER R = RED HANDLED, LOCK-OUT TYPE
A = ARC-FAULT BREAKER GP = GFEPD BREAKER LCP = CRKT TO BE ROUTED THROUGH LTG CONTROL PANEL
BRK NOTES:
TOTAL ESTIMATED DEMAND AMPS:0 A
TOTAL AMPS:0 A 0 A 0 A
TOTAL LOAD:0.0 kVA 0.0 kVA 0.0 kVA
41 42
39 40
37 38
35 36
33 34
31 32
29 30
27 28
25 26
23 24
21 22
19 20
17 18
15 16
13 14
11 12
9 10
7 8
5 6
3 4
1 2
CKT CIRCUIT DESCRIPTION NOTE AMPS P A B C P AMPS NOTE CIRCUIT DESCRIPTION CKT
NOTES:
MFG & MODEL:SQ. D/NQ SERIES DIMENSIONS:20"W x 5.8"D x *"H FEED:
ENCLOSURE: BUSSING:SEE SPEC'S MBR AMPS:N/A
MOUNTING:WIRES:4 PANEL AMPS:225 A
FED FROM:M (EAST)PHASES:3 PANEL TYPE:MLO MCK Library Remodel
LOCATION:ELECTRICAL 2-I VOLTAGE:120/208 Wye A.I.C. RATING:0 PROJECT:
PANEL: CP8
PAYNE ENGINEERING
S = SHUNT-TRIP BREAKER G = GFCI BREAKER R = RED HANDLED, LOCK-OUT TYPE
A = ARC-FAULT BREAKER GP = GFEPD BREAKER LCP = CRKT TO BE ROUTED THROUGH LTG CONTROL PANEL
BRK NOTES:
TOTAL ESTIMATED DEMAND AMPS:28 A
TOTAL AMPS:23 A 42 A 21 A
TOTAL LOAD:2.7 kVA 5.0 kVA 2.5 kVA
29 30
27 28
25 26
23 24
21 22
19 20
17 18
15 16
13 14
11 12
9 10
7 8
5 2500 6
3 6L-20 Receptacle 20 A 2
2500 2500 4
1 Receptacle 20 A 1 180 2500 2 20 A 6L-20 Receptacle
2
CKT CIRCUIT DESCRIPTION NOTE AMPS P A B C P AMPS NOTE CIRCUIT DESCRIPTION CKT
NOTES:
MFG & MODEL:SQ. D/NQ SERIES DIMENSIONS:20"W x 5.8"D x *"H FEED:
ENCLOSURE: BUSSING:SEE SPEC'S MBR AMPS:N/A
MOUNTING:WIRES:4 PANEL AMPS:100 A
FED FROM:UPS1 PHASES:3 PANEL TYPE:MLO MCK Library Remodel
LOCATION:TR / COMM. 280 VOLTAGE:120/208 Wye A.I.C. RATING:0 PROJECT:
PANEL: UPS (280)
PAYNE ENGINEERING
8270
STATEOFIDAHO
T
ODD P A Y N EREGISTER
EDRP
OFESSIONALEN
G
I
NE
E
R
1823 E. Center
Pocatello, Idaho 83201
tel (208) 232-4439
www.payneengineeringinc.com
Engineering Inc.
Consulting Engineers
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
P.E. #:2259
10-28-2022 EE504
PANEL
SCHEDULES
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
BID SET
S = SHUNT-TRIP BREAKER G = GFCI BREAKER R = RED HANDLED, LOCK-OUT TYPE
A = ARC-FAULT BREAKER GP = GFEPD BREAKER LCP = CRKT TO BE ROUTED THROUGH LTG CONTROL PANEL
BRK NOTES:
TOTAL ESTIMATED DEMAND AMPS:0 A
TOTAL AMPS:0 A 0 A 0 A
TOTAL LOAD:0.0 kVA 0.0 kVA 0.0 kVA
41 42
39 40
37 38
35 36
33 34
31 32
29 30
27 28
25 26
23 24
21 22
19 20
17 18
15 16
13 14
11 12
9 10
7 8
5 6
3 4
1 2
CKT CIRCUIT DESCRIPTION NOTE AMPS P A B C P AMPS NOTE CIRCUIT DESCRIPTION CKT
NOTES:
MFG & MODEL:SQ. D/NQ SERIES DIMENSIONS:20"W x 5.8"D x *"H FEED:
ENCLOSURE: BUSSING:SEE SPEC'S MBR AMPS:N/A
MOUNTING:WIRES:4 PANEL AMPS:225 A
FED FROM: PHASES:3 PANEL TYPE:MLO MCK Library Remodel
LOCATION:ELECTRICAL 308 VOLTAGE:120/208 Wye A.I.C. RATING:0 PROJECT:
PANEL: 3WB
PAYNE ENGINEERING
S = SHUNT-TRIP BREAKER G = GFCI BREAKER R = RED HANDLED, LOCK-OUT TYPE
A = ARC-FAULT BREAKER GP = GFEPD BREAKER LCP = CRKT TO BE ROUTED THROUGH LTG CONTROL PANEL
BRK NOTES:
TOTAL ESTIMATED DEMAND AMPS:17 A
TOTAL AMPS:23 A 19 A 12 A
TOTAL LOAD:2.7 kVA 2.2 kVA 1.4 kVA
41 42
39 40
37 38
35 36
33 34
31 32
29 30
27 28
25 26
23 24
21 22
19 20
17 18
15 16
13 14
11 Receptacle 20 A 1 360 12
9 Receptacle 20 A 1 720 10
7 Receptacle 20 A 1 720 500 1 20 A Power 8
5 Receptacle 20 A 1 360 720 1 20 A Receptacle 6
3 Receptacle 20 A 1 900 540 1 20 A Receptacle 4
1 Receptacle 20 A 1 720 720 1 20 A Receptacle 2
CKT CIRCUIT DESCRIPTION NOTE AMPS P A B C P AMPS NOTE CIRCUIT DESCRIPTION CKT
NOTES:
MFG & MODEL:SQ. D/NQ SERIES DIMENSIONS:20"W x 5.8"D x *"H FEED:
ENCLOSURE: BUSSING:SEE SPEC'S MBR AMPS:N/A
MOUNTING:WIRES:4 PANEL AMPS:225 A
FED FROM: PHASES:3 PANEL TYPE:MLO MCK Library Remodel
LOCATION:ELECTRICAL 308 VOLTAGE:120/208 Wye A.I.C. RATING:0 PROJECT:
PANEL: CP15
PAYNE ENGINEERING
S = SHUNT-TRIP BREAKER G = GFCI BREAKER R = RED HANDLED, LOCK-OUT TYPE
A = ARC-FAULT BREAKER GP = GFEPD BREAKER LCP = CRKT TO BE ROUTED THROUGH LTG CONTROL PANEL
BRK NOTES:
TOTAL ESTIMATED DEMAND AMPS:0 A
TOTAL AMPS:0 A 0 A 0 A
TOTAL LOAD:0.0 kVA 0.0 kVA 0.0 kVA
41 42
39 40
37 38
35 36
33 34
31 32
29 30
27 28
25 26
23 24
21 22
19 20
17 18
15 16
13 14
11 12
9 10
7 8
5 6
3 4
1 2
CKT CIRCUIT DESCRIPTION NOTE AMPS P A B C P AMPS NOTE CIRCUIT DESCRIPTION CKT
NOTES:
MFG & MODEL:SQ. D/NQ SERIES DIMENSIONS:20"W x 5.8"D x *"H FEED:
ENCLOSURE: BUSSING:SEE SPEC'S MBR AMPS:N/A
MOUNTING:WIRES:4 PANEL AMPS:225 A
FED FROM: PHASES:3 PANEL TYPE:MLO MCK Library Remodel
LOCATION:ELECTRICAL 324B VOLTAGE:120/208 Wye A.I.C. RATING:0 PROJECT:
PANEL: CP18
PAYNE ENGINEERING
S = SHUNT-TRIP BREAKER G = GFCI BREAKER R = RED HANDLED, LOCK-OUT TYPE
A = ARC-FAULT BREAKER GP = GFEPD BREAKER LCP = CRKT TO BE ROUTED THROUGH LTG CONTROL PANEL
BRK NOTES:
TOTAL ESTIMATED DEMAND AMPS:41 A
TOTAL AMPS:49 A 46 A 39 A
TOTAL LOAD:5.8 kVA 5.4 kVA 4.7 kVA
41 42
39 40
37 38
35 36
33 34
31 32
29 30
27 28
25 26
23 24
21 901 22
19 901 20
17 Receptacle 20 A 1 720 901
3 20 A REF-1
18
15 Receptacle 20 A 1 720 900 1 20 A Receptacle 16
13 Receptacle 20 A 1 720 900 1 20 A Receptacle 14
11 Receptacle 20 A 1 720 720 1 20 A Receptacle 12
9 Receptacle 20 A 1 720 720 1 20 A Receptacle 10
7 Receptacle 20 A 1 720 900 1 20 A Receptacle 8
5 Receptacle 20 A 1 900 720 1 20 A Receptacle 6
3 Receptacle 20 A 1 720 720 1 20 A Receptacle 4
1 Receptacle 20 A 1 900 720 1 20 A Receptacle 2
CKT CIRCUIT DESCRIPTION NOTE AMPS P A B C P AMPS NOTE CIRCUIT DESCRIPTION CKT
NOTES:
MFG & MODEL:SQ. D/NQ SERIES DIMENSIONS:20"W x 5.8"D x *"H FEED:
ENCLOSURE: BUSSING:SEE SPEC'S MBR AMPS:N/A
MOUNTING:WIRES:4 PANEL AMPS:225 A
FED FROM: PHASES:3 PANEL TYPE:MLO MCK Library Remodel
LOCATION:ELECTRICAL 324B VOLTAGE:120/208 Wye A.I.C. RATING:0 PROJECT:
PANEL: N
PAYNE ENGINEERING
S = SHUNT-TRIP BREAKER G = GFCI BREAKER R = RED HANDLED, LOCK-OUT TYPE
A = ARC-FAULT BREAKER GP = GFEPD BREAKER LCP = CRKT TO BE ROUTED THROUGH LTG CONTROL PANEL
BRK NOTES:
TOTAL ESTIMATED DEMAND AMPS:37 A
TOTAL AMPS:42 A 44 A 48 A
TOTAL LOAD:5.0 kVA 5.2 kVA 5.8 kVA
41 42
39 40
37 38
35 36
33 34
31 32
29 Receptacle 20 A 1 900 900 1 20 A Roof Receptacle 30
27 Receptacle 20 A 1 360 528 1 20 A REF-3 28
25 Receptacle 20 A 1 720 540 1 20 A Receptacle 26
23 Receptacle 20 A 1 180 720 1 20 A Receptacle 24
21 Receptacle 20 A 1 540 720 1 20 A Receptacle 22
19 Receptacle 20 A 1 720 540 1 20 A Receptacle 20
17 Receptacle 20 A 1 720 720 1 20 A Receptacle 18
15 Receptacle 20 A 1 540 540 1 20 A Receptacle 16
13 Receptacle 20 A 1 360 720 1 20 A Receptacle 14
11 Receptacle 20 A 1 360 540 1 20 A Receptacle 12
9 Receptacle 20 A 1 540 360 1 20 A Receptacle 10
7 Receptacle 20 A 1 360 360 1 20 A Receptacle 8
5 Receptacle 20 A 1 360 360 1 20 A Receptacle 6
3 Receptacle 20 A 1 540 540 1 20 A Receptacle 4
1 Receptacle 20 A 1 360 360 1 20 A Receptacle 2
CKT CIRCUIT DESCRIPTION NOTE AMPS P A B C P AMPS NOTE CIRCUIT DESCRIPTION CKT
NOTES:
MFG & MODEL:SQ. D/NQ SERIES DIMENSIONS:20"W x 5.8"D x *"H FEED:
ENCLOSURE: BUSSING:SEE SPEC'S MBR AMPS:N/A
MOUNTING:WIRES:4 PANEL AMPS:225 A
FED FROM: PHASES:3 PANEL TYPE:MLO MCK Library Remodel
LOCATION:ELECTRICAL 324B VOLTAGE:120/208 Wye A.I.C. RATING:0 PROJECT:
PANEL: K
PAYNE ENGINEERING
S = SHUNT-TRIP BREAKER G = GFCI BREAKER R = RED HANDLED, LOCK-OUT TYPE
A = ARC-FAULT BREAKER GP = GFEPD BREAKER LCP = CRKT TO BE ROUTED THROUGH LTG CONTROL PANEL
BRK NOTES:
TOTAL ESTIMATED DEMAND AMPS:18 A
TOTAL AMPS:24 A 16 A 14 A
TOTAL LOAD:2.8 kVA 1.9 kVA 1.7 kVA
41 42
39 40
37 38
35 36
33 34
31 32
29 30
27 28
25 26
23 24
21 22
19 20
17 18
15 288 16
13 288 14
11
REF-2 20 A 3
288 12
9 Drinking Fountain G 20 A 1 180 10
7 Receptacle 20 A 1 1080 8
5 Receptacle 20 A 1 720 720 1 20 A Receptacle 6
3 Receptacle 20 A 1 720 720 1 20 A Receptacle 4
1 Receptacle 20 A 1 720 720 1 20 A Receptacle 2
CKT CIRCUIT DESCRIPTION NOTE AMPS P A B C P AMPS NOTE CIRCUIT DESCRIPTION CKT
NOTES:
MFG & MODEL:SQ. D/NQ SERIES DIMENSIONS:20"W x 5.8"D x *"H FEED:
ENCLOSURE: BUSSING:SEE SPEC'S MBR AMPS:N/A
MOUNTING:WIRES:4 PANEL AMPS:225 A
FED FROM: PHASES:3 PANEL TYPE:MLO MCK Library Remodel
LOCATION:ELEC 364 VOLTAGE:120/208 Wye A.I.C. RATING:0 PROJECT:
PANEL: H
PAYNE ENGINEERING
S = SHUNT-TRIP BREAKER G = GFCI BREAKER R = RED HANDLED, LOCK-OUT TYPE
A = ARC-FAULT BREAKER GP = GFEPD BREAKER LCP = CRKT TO BE ROUTED THROUGH LTG CONTROL PANEL
BRK NOTES:
TOTAL ESTIMATED DEMAND AMPS:49 A
TOTAL AMPS:58 A 44 A 46 A
TOTAL LOAD:6.9 kVA 5.3 kVA 5.5 kVA
41 42
39 40
37 38
35 36
33 34
31 32
29 30
27 28
25 26
23 24
21 22
19 20
17 18
15 16
13 Lighting 20 A 1 1148 14
11 Lighting 20 A 1 1250 1012 1 20 A Lighting 12
9 Lighting 20 A 1 1610 535 1 20 A Lighting 10
7 Lighting 20 A 1 1295 1720 1 20 A Lighting 8
5 Lighting 20 A 1 1607 1665 1 20 A Lighting 6
3 Lighting 20 A 1 1517 1650 1 20 A Lighting 4
1 Lighting 20 A 1 1330 1429 1 20 A Lighting 2
CKT CIRCUIT DESCRIPTION NOTE AMPS P A B C P AMPS NOTE CIRCUIT DESCRIPTION CKT
NOTES:
MFG & MODEL:SQ. D/NQ SERIES DIMENSIONS:20"W x 5.8"D x *"H FEED:
ENCLOSURE: BUSSING:SEE SPEC'S MBR AMPS:N/A
MOUNTING:WIRES:4 PANEL AMPS:225 A
FED FROM: PHASES:3 PANEL TYPE:MLO MCK Library Remodel
LOCATION:ELEC 364 VOLTAGE:120/208 Wye A.I.C. RATING:0 PROJECT:
PANEL: 3LA
PAYNE ENGINEERING
S = SHUNT-TRIP BREAKER G = GFCI BREAKER R = RED HANDLED, LOCK-OUT TYPE
A = ARC-FAULT BREAKER GP = GFEPD BREAKER LCP = CRKT TO BE ROUTED THROUGH LTG CONTROL PANEL
BRK NOTES:
TOTAL ESTIMATED DEMAND AMPS:29 A
TOTAL AMPS:35 A 26 A 29 A
TOTAL LOAD:4.1 kVA 3.1 kVA 3.5 kVA
41 42
39 40
37 38
35 36
33 34
31 32
29 30
27 28
25 26
23 24
21 22
19 20
17 FCU-3 15 A 1 586 18
15 Receptacle 20 A 1 900 16
13 Receptacle 20 A 1 720 500 1 20 A Power 14
11 Receptacle 20 A 1 900 180 1 20 A Receptacle 12
9 Receptacle 20 A 1 900 720 1 20 A Receptacle 10
7 Receptacle 20 A 1 900 720 1 20 A Receptacle 8
5 Receptacle 20 A 1 900 900 1 20 A Receptacle 6
3 Receptacle 20 A 1 360 180 1 20 A Receptacle 4
1 Receptacle 20 A 1 360 900 1 20 A Receptacle 2
CKT CIRCUIT DESCRIPTION NOTE AMPS P A B C P AMPS NOTE CIRCUIT DESCRIPTION CKT
NOTES:
MFG & MODEL:SQ. D/NQ SERIES DIMENSIONS:20"W x 5.8"D x *"H FEED:
ENCLOSURE: BUSSING:SEE SPEC'S MBR AMPS:N/A
MOUNTING:WIRES:4 PANEL AMPS:225 A
FED FROM: PHASES:3 PANEL TYPE:MLO MCK Library Remodel
LOCATION:ELEC 364 VOLTAGE:120/208 Wye A.I.C. RATING:0 PROJECT:
PANEL: CP17
PAYNE ENGINEERING
8270
STATEOFIDAHO
T
ODD P A Y N EREGISTER
EDRP
OFESSIONALEN
G
I
NE
E
R
1823 E. Center
Pocatello, Idaho 83201
tel (208) 232-4439
www.payneengineeringinc.com
Engineering Inc.
Consulting Engineers
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
P.E. #:2259
10-28-2022 EE600
SCHEDULES
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
BID SET
MECHANICAL - CABINET HEATER
EQUIP. ID VOLTS PH.WATTS CIRCUIT FEEDER NOTES
CH-1 120 V 1 173 W EW3-3 3/4" C., 3#12+1#12 GND
CH-2 120 V 1 83 W EW3-5 3/4" C., 3#12+1#12 GND
CH-3 120 V 1 83 W EW3-2 3/4" C., 3#12+1#12 GND
CH-4 120 V 1 83 W EE-4 3/4" C., 3#12+1#12 GND
CH-5 120 V 1 83 W EE-3 3/4" C., 3#12+1#12 GND
CH-6 120 V 1 83 W EE-5 3/4" C., 3#12+1#12 GND
CH-7 120 V 1 83 W EE-2 3/4" C., 3#12+1#12 GND
MECHANICAL - FAN COIL UNITS (CHW)
EQUIP. ID VOLTS PH.MOCP CIRCUIT FEEDER NOTES
FCU-1 120 V 1 15 A CP11-23 3/4" C., 3#12+1#12 GND
FCU-2 120 V 1 15 A CP14-23 3/4" C., 3#12+1#12 GND
FCU-3 120 V 1 15 A CP17-17 3/4" C., 3#12+1#12 GND
MECHANICAL - FAN COIL UNITS (DX)
EQUIP. ID VOLTS PH.MOCP MCA CIRCUIT FEEDER DISCONNECT SIZE DISCONNECT TYPE NOTES
DXFCU-1(CU)208 V 3 15 A 3 A EW2-7,9,11 3/4"C.,3#12+1#12G 15 A 3R
DXFCU-1(FC)208 V 3 15 A 6 A EW2-2,4,6 3/4"C.,3#12+1#12G 15 A 1R
MECHANICAL - ROOFTOP EXHAUST FAN SCHEDULE
EQUIP. ID VOLTS PH.HP CIRCUIT FEEDER NOTES
REF-1 208 V 3 2 N-18,20,22 3/4"C.,3#12+1#12G
REF-2 208 V 3 1/2 H-11,13,15 3/4"C.,3#12+1#12G
REF-3 120 V 1 1/6 K-28 3/4"C.,2#12+1#12G
REF-4 120 V 1 1/6 2A-27 3/4"C.,2#12+1#12G
MECHANICAL - SPLIT SYSTEM AIR CONDITIONING UNIT (INDOOR)
EQUIP. ID VOLTS PH.FLA CIRCUIT FEEDER NOTES
SAC-040 208 V 1 1 A E-1,3 PER MANUFACTURER 5
SAC-245A 208 V 1 1 A EW2-16,18 PER MANUFACTURER 5
SAC-245B 208 V 1 1 A EW2-19,21 PER MANUFACTURER 5
SAC-280A 208 V 1 1 A EE2-2,4 PER MANUFACTURER 5
SAC-280B 208 V 1 1 A EE2-6,8 PER MANUFACTURER 5
MECHANICAL - WALL HUNG HUMIDIFIER
EQUIP. ID VOLTS PH.MOCP MCA CIRCUIT FEEDER NOTES
H-1 208 V 3 15 A 10 A EW2-8,10,12 3/4" C., 3#12+1#12 GND
LIGHTING FIXTURE SCHEDULE
TYPE DESCRIPTION MOUNTING VOLTAGE LUMENS
COLOR
TEMP.(K)MFGR.CATALOG #NOTES
F1 EXIT SIGN WALL OR
CEILING
120-277 N/A N/A LITHONIA LQM-S-W-3-G-20/277-EL N
F2 2X2 LAY-IN LED TROFFER RECESSED 120-277 4000 4000 LITHONIA 2BLT2-TUWH-PROP-40L-ADSM-MVOLT-N100
F3 2X2 LAY-IN LED FLAT PANEL RECESSED 120-277 4000 4000 LITHONIA EPANL-2X2-4000LM-80CRI-40K-MIN1-NLIGHT-MVOLT
F3R 2X2 LED FLAT PANEL W/ GYP. CEILING
RECESSED KIT
RECESSED 120-277 4000 4000 LITHONIA EPANL-2X2-4000LM-80CRI-40K-MIN1-NLIGHT-MVOLT / DGA
22
F4 6" ROUND RECESSED LED CAN, 0-10V
DIMMING
RECESSED 120-277 1500 4000 LITHONIA LDN6-40/15-LO6AR-LSS-MVOLT-NPP16D
F5 4FT LINEAR WALL FIXTURE WALL 120-277 4000 LITHONIA WL4-30L-MVOLT-EZ1-LP840-N100
F6 HOOP PENDANT 36" DIAMETER SUSPENDED 120 4000 CERCHIO KUZ2213830
F8 1X4 SURFACE FIXTURE SURFACE 120-277 4000 4000 LITHONIA BLWP4-40L-ADP-EZ1-LP840-N100
F9 6" ROUND PENDANT LED DOWNLIGHT,
DIMMABLE
SURFACE/
SUSPENDED
120 4000 LITHONIA LDN8CYL 40/20 LO6 AR LSS MVOLT EZ10 ACC CBA
NPS80EZ
F10 2FT LINEAR WALL FIXTURE WALL ABOVE
MIRROR
120-277 4000 LITHONIA WL2-22L-EZ1-LP840-N100
F11 4FT LED STRIP, 0-10V DIMMING SURFACE/
SUSPENDED
120-277 4000 4000 LITHONIA CLX-L48-4000LM-SEF-RDL-MVOLT-GZ10-40K-80CRI-N100
F12 LED TRACK LIGHT SURFACE 120 1500 4000 LSI TRACK: TRK-SC-XX1-120-CBA HEAD: SEE NOTE 8 9
F13 LED PUCK LIGHT SURFACE 120 1000 4000 JUNO JSF-7IN-10LM-40K-90CRI-MVOLT ZT-WH
F14 ARCHITECTUAL PENDANT FOSCARINI FOS570261
F15 LED RECESSED LINEAR FIXTURE RECESSED 120-277 5000 4000 FOCAL POINT FSM2L-FL-625LF-40K-1C-UNV-TF-8FT
F16 AREA POLE LIGHT, SINGLE-HEAD,POLE (SEE
DETAIL)
OWNER FURNISHED CONTRACTOR INSTALLED
F17 LED TAPE LIGHT IN CHANNEL 120 4000 NOVA FLEX STRIP: NF-COB-1-480-24V -4000K/
CHANNEL:NF-CH-1806-2M
F18 HOOP PENDANT 72" DIAMETER SUSPENDED 120 4000 CERCHIO KUZ2213831
F19 6" ROUND RECESSED LED CAN, 0-10V
DIMMING
RECESSED 120-277 1500 4000 LITHONIA LDN6-40/10-LO6AR-LSS-MVOLT-NPP16D
F20 LED RECESSED LINEAR FIXTURE RECESSED 120-277 5000 4000 FOCAL POINT FSM2L-FL-625LF-40K-1C-UNV-TF-12FT
F22 LED RECESSED LINEAR FIXTURE RECESSED 120-277 FOCAL POINT FSM2L-FL-625LF-40K-1C-UNV-TF-2FT
F23 SURFACE MOUNTED LOADING DOCK LIGHT SURFACE 3000 4000 KENALL MS15FL-PP-CBA-25L-40K-DV
LIGHTING CONTROL (nLIGHT) SYSTEM SCHEDULE
TYPE DESCRIPTION MFGR.CATALOG #NOTES
CEILING SENSORS
nD1 DUAL-TECHNOLOGY, SMALL MOTION, CEILING OCCUPANCY SENSOR W/ AUTO DIMMING
CONTROL PHOTOCELL
SENSOR SWITCH nCM-PDT-9-RJB-ADCX
RELAY PACKS/POWER SUPPLIES & INTERFACE DEVICES
nPS80 RELAY POWER PACK SENSOR SWITCH nPS80 2
WALL SWITCHES
n1 nLIGHT ON/OFF PUSHBUTTON SENSOR SWITCH nPODM 3
n2D nLIGHT ON/OFF PUSHBUTTON W/DIMMING, 2-CHANNEL SENSOR SWITCH nPODM-2PDX-X 3
nD nLIGHT ON/OFF PUSHBUTTON W/DIMMING SENSOR SWITCH nPODM-DX 3
nDC nLIGHT ON/OFF PUSHBUTTON W/DIMMING, COLOR CORRECTION SENSOR SWITCH nPODM-DX-CCT 3
nO nLIGHT DUAL-TECH OCCUPANCY SENSOR, ON/OFF PUSHBUTTON W/DIMMING SENSOR SWITCH nWSX PDT LV NL 3
LIGHTING CONTROL/OCCUPANCY SENSOR SCHEDULE
TYPE DESCRIPTION MFGR.CATALOG #NOTES
APPROVED
EQUALS
OCC. SENSORS - CEILING (LINE VOLTAGE)
CD2 DUAL-TECHNOLOGY, LINE VOLTAGE, SMALL MOTION 800W MAX
LOAD
SENSOR SWITCH CMR PDT 9 COOPER,
WATTSOPPER,
HUBBELL
POWER SUPPLY
PS POWER SUPPLY NOVA FLEX NF-PS-UNV-96W-24 8
1. REFER TO DRAWINGS FOR FIXTURES REQUIRED TO HAVE 0-10V OR STEP-LEVEL DIMMING CONTROL. PROVIDE FIXTURE(S) WITH LED DRIVER(S)
AND REQUIRED DIMMING/SWITCH-LEG CONDUCTORS BETWEEN SWITCH(ES) AND FIXTURE(S) TO PROVIDE CONTROL AS INDICATED ON
DRAWINGS.
2. FIXTURE TO BE CONTINUOUS ROW MOUNTED, LENGTH AS INDICATED ON DRAWINGS. PROVIDE REQUIRED ACCESSORIES/CONNECTORS FOR
CONTINUOUS ROW MOUNTING.
3. SCBA -STANDARD COLOR BY ARCHITECT/OWNER (COORDINATE COLOR WITH ARCHITECT/OWNER PRIOR TO ORDERING.)
4. FIELD ADJUST PENDANT LENGTH AS REQUIRED, VERIFY LENGTH WITH COUNTER AS DIRECTED BY ARCHITECT.
5. REFER TO ARCHITECTURAL ELEVATION DRAWINGS FOR PLACEMENT AND MOUNTING HEIGHT OF FIXTURES.
6. PROVIDE AND INSTALL 120V FACTORY APPROVED DIMMER SWITCH FOR TRACK: ACUITY P/N: SYNERGY ISD 400 ELV 120.
7. PROVIDE ALL COMPONENTS FOR COMPLETE INSTALLATION, INCLUDING BUT NOT LIMITED TO: END FEEDS, CONNECTORS AND ETC.
8. E.C. SHALL PROVIDE AND INSTALL (50) LZ-15-90-40-ZM-CT2-10-120-CBA. LOCATE, AIM, AND FOCUS TO SATISFACTION OF OWNER.
9. REFER TO PLANS FOR TRACK LENGTH AND CONFIGURATION. E.C. SHALL PROVIDE AND INSTALL ALL REQUIRED POWER FEEDS, CORNERS,
CONNECTORS ETC. FOR A COMPLETE TRACK SYSTEM.
LIGHT FIXTURE SCHEDULE NOTES:
• LIGHTING FIXTURES INDICATED IN SCHEDULE ARE BASIS OF DESIGN, ALTERNATE MANUFACTURERS SHALL BE PRE-APPROVED BY ADDENDUM.
ALTERNATE MANUFACTURERS SHALL SUBMIT PER-APPROVALS TO ENGINEER A MINIMUM OF 10 DAYS PRIOR TO PROJECT BID DATE.
• THE SUFFIX 'E' DENOTES A FIXTURE SUPPLIED WITH AN EMERGENCY TRANSFER DEVICE. PROVIDE A NORMAL POWER SENSING CIRCUIT.
CONTROL FIXTURE WITH SURROUNDING FIXTURES. CONNECT TO EXISTING EMERGENCY LIGHTING CIRCUIT IN AREA. CONNECT SUCH THAT
FIXTURE WILL ILLUMINATE UPON NORMAL POWER FAILURE.
• THE SUFFIX 'NL' DENOTES A FIXTURE TO BE CONNECT TO EMERGENCY CIRCUIT IN AREA. LIGHT TO BE UNCONTROLLED AND ON CONTINUALLY
GENERAL LIGHTING SCHEDULE NOTES:
1. PROVIDE 0-10V DIMMING CONDUCTORS (GREY & VIOLET) BETWEEN DEVICE AND LIGHT FIXTURE(S) FOR DIMMING AS INDICATED ON DWGS.
2. ROUTE ASSOCIATED ROOM LTG CIRCUIT THROUGH RELAY FOR CONTROL, PROVDE 0-10V DIMMING AND LOW VOLTAGE CONNECTIONS AS
INDICATED ON DRAWINGS AND DETAILS.
3. DEVICE COLOR SHALL MATCH WIRING DEVICES; REFER TO SPECIFICATIONS.
4. MOUNT DEVICE TO BOTTOM OF STRUCTURE.
nLIGHT LIGHTING CONTROL SCHEDULE NOTES:
nLIGHT LIGHTING CONTROL SCHEDULE GENERAL NOTES:
• E.C. SHALL BE RESPONSIBLE FOR PROVIDING ALL LIGHTING CONTROL COMMISSIONING/PROGRAMMING OF ALL nLIGHT COMPONENTS. THE
COMMISSIONING/PROGRAMMING SHALL BE DONE BY A nLIGHT CERTIFIED TECHNICIAN.
• E.C. SHALL NOTIFY OWNER 1-WEEK PRIOR TO COMMISSIONING/PROGRAMMING OF THE SYSTEM SO THAT THE OWNER CAN PROVIDE
REPRESENTATIVES DURING THE COMMISSIONING/PROGRAMMING PERIOD.
1. PROVIDE ADDITIONAL POWER PACKS; SENSOR SWITCH PP20 AS NEED FOR QTY OF OCCUPANCY SENSORS/SWITCHES.
2. DEVICE COLOR SHALL MATCH WIRING DEVICES; REFER TO SPECIFICATIONS.
3. REFER TO MANUFACTURER DOCUMENTATION FOR QTY AND SIZE OF CONDUCTORS BETWEEN LOW VOLTAGE SWITCH, SENSOR(S) AND
POWER/RELAY PACKS.
4. PROVIDE SECONDARY RELAY PACK; SENSOR SWITCH SP20 AS NEEDED TO PROVIDE DUAL-LEVEL SWITCHING OF FIXTURES.
5. PROVIDE 0-10V DIMMING CONDUCTORS (GRAY & VIOLET) BETWEEN SWITCH AND LIGHT FIXTURES FOR DIMMING CONTROL.
6. PROGRAM ON/OFF TIMES OF RELAY'S AS DIRECTED BY OWNER. PROVIDE COMMISSIONING AS INDICATED IN GENERAL NOTES BELOW.
7. CUSTOM WALL STATION ENGRAVINGS IS REQUIRED FOR WALL STATION(S) AND SHALL BE SPECIFIED/COORDINATED WITH OWNER AFTER
PROGRAMING OF SYSTEM.
8. PROVIDE WITH ALL REQUIRED ACCESSORIES AND COMPONENTS FOR A COMPLETE AND OPERABLE SYSTEM
CONTROL & OCCUPANCY SENSOR SCHEDULE NOTES:
• E.C. SHALL BE RESPONSIBLE FOR THE PROGRAMMING/COMMISSIONING OF THE LIGHTING CONTROL SYSTEMS TO FUNCTION AS INDICATED ON
THE DRAWINGS AND SHALL INCLUDE ALL REQUIRED COST IN THE BASE BID. FOR AREAS WITH DAYLIGHTING CONTROL, THE DAYLIGHTING SET-
POINTS SHALL BE COORDINATED WITH THE OWNER FOR EACH AREA PRIOR TO FINAL PROGRAMMING OF THE DAYLIGHTING SENSOR(S). ALL
PROGRAMMING/COMMISSIONING SHALL BE DONE BY A FACTORY CERTIFIED OR TRAINED PERSON.
• LIGHTING IS SPACES WITH WIRELESS CONTROLS SHALL BE FIELD TUNED TO FOOTCANDLE LEVELS THAT ARE SATISFACTORY TO THE OWNER
DURING PROGRAMMING AND COMMISSIONING OF THE WIRELESS CONTROL SYSTEM.
GENERAL LIGHTING CONTROL NOTES:
1. CIRCUIT AND CONTROL EXHAUST FAN WITH ROOM LIGHTING CIRCUIT.
2. E.C. SHALL PROVIDE LOCAL DISCONNECT RATED, THERMAL-OVERLOAD SWITCH FOR EQUIPMENT; SWITCH RATING SHALL NOT BE LESS THEN
CIRCUIT BREAKER SUPPLYING EQUIPMENT.
3. E.C. SHALL PROVIDE LOCAL DISCONNECT SWITCH FOR EQUIPMENT; SIZE AND TYPE AS INDICATED IN SCHEDULE. IF FUSED DISCONNECT IS
SPECIFIED FOR EQUIPMENT, FUSE PER EQUIPMENT NAMEPLATE RATING.
4. EQUIPMENT IS FACTORY SUPPLYED WITH DISCONNECT AND CONVIENENCE OUTLET; E.C. SHALL PROVIDE ALL NECESSARY CONNECTIONS.
5. INDOOR UNIT IS POWERED FROM OUTDOOR UNIT; COORDINATE EXACT NUMBER OF CONDUCTORS BETWEEN UNITS WITH M.C. PRIOR TO
ROUGH-IN.
6. PROVIDE 1/2" CONDUIT AND CONDUCTORS BETWEEN FURNACE AND CORRESPONDING OUTDOOR CONDENSING UNIT. COORDINATE SIZE AND
NUMBER OF CONDUCTORS WITH M.C. PRIOR TO ROUGH-IN. PROVIDE CONNECTION BETWEEN FURNACE AND ASSOCIATED OUTSIDE AIR
MOTORIZED DAMPER, COORDINATE WITH M.C.
7. E.C. SHALL PROVIDE COMBINATION STARTER/DISCONNECT SWITCH FOR EQUIPMENT; SIZE AND TYPE AS INDICATED IN SCHEDULE. PROVIDE
WITH CONTROL XFMR (2) SETS OF NO/NC CONTACTS, CONTROLS WITH M.C. PRIOR TO ROUGH-IN. FUSE DISCONNECT PER EQUIPMENT
NAMEPLATE RATING.
MECHANICAL SCHEDULE NOTES:
MECHANICAL - SPLIT SYSTEM AIR CONDITIONING UNIT (OUTDOOR)
EQUIP. ID VOLTS PH.MOCP MCA CIRCUIT FEEDER NOTES
SCU-040 208 V 1 42 A 26 A E-1,3 3/4" c., 3#8+1#10 GND
SCU-245A 208 V 1 42 A 26 A EW2-16,18 3/4" c., 3#8+1#10 GND
SCU-245B 208 V 1 42 A 26 A EW2-19,21 3/4" c., 3#8+1#10 GND
SCU-280A 208 V 1 42 A 26 A EE2-2,4 3/4" c., 3#8+1#10 GND
SCU-280B 208 V 1 42 A 26 A EE2-6,8 3/4" c., 3#8+1#10 GND
MECHANICAL - FAN COIL CIRCULATING PUMP
EQUIP. ID VOLTS PH.HP Panel FEEDER NOTES
FCP-1 120 V 1 1/2 P 3/4"C.,2#12+1#12G
REF.REF.
DDD
D D D
G
J
E
C
2 3 4 5 6
TIER 2
[016]
OFFICE
[010]
OFFICE
[026A]
OFFICE
[011]
BREAK
ROOM
[013]
'O'
'EMW''EME'
'ATS W EST''ATS EAST'
'MC'
SHORT
TERM
STORAGE
[028]
OFFICE
[012]
TECH
ROOM
[024]
STUDENTS
[026F]
OFFICE
[026C]
OPS
[022]
MECH
ROOM
[030]
STAIR
[0-E]
STORAGE
[032]
MECH
CHASE
[O-F]
STAIR
[0-E]ELEV
[0-J]
ELECTRICAL
[038]
CUSTODIAL
[036]
MECH
CHASE
[034]
BDF
[040]
CUSTODIAL
STORAGE
[042]
STORAGE
[044]
OFFICE
[018]
OFFICE
[020]
QA
[022A]
MEN'S RR
[015]
WOMEN'S
RR
[014]
IMAGING
AND
STORAGE
[009]
OFFICE
[026B]
OFFICE
[026D]OFFICE
[026E]
'E'
'RA'
'NAC'
E-5
E-2
8270
STATEOFIDAHO
T
ODD P A Y N EREGISTER
EDRP
OFESSIONALEN
G
I
NE
E
R
1823 E. Center
Pocatello, Idaho 83201
tel (208) 232-4439
www.payneengineeringinc.com
Engineering Inc.
Consulting Engineers
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
P.E. #:2259
10-28-2022 EF100
FIRE ALARM
PLAN LEVEL
0
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
BID SET
A. REFER TO SYMBOL SCHEDULE SHEET FOR PROJECT
GENERAL NOTES AND GENERAL NOTES ASSOCIATED WITH
THE INSTALLATION OF EACH SYSTEM, INCLUDINB BUT NOT
LIMITED TO; LIGHTING, POWER, FIRE ALARM, SPECIAL
SYSTEMS, ETC.
GENERAL NOTES:
SCALE: 1/8" = 1'-0"1 LEVEL 0 FIRE ALARM PLAN
16'8'0"
NORTH
REF.
P
SD
SD
SD
SD
SD
SD
1
G
J
L
M
N
P
Q
E
C
2 3 4 5 61.5
CHECK-IN
[112]
OFFICE
[129]
OFFICE
[130]
OFFICE
[131]
STUDY
(MED)
[132]
OFFICE
[136]
RECEPTION
[134]
OFFICE
[138]
CONFERENCE
ROOM
[140]
BREAKROOM
[142]
STUDY (SM)
[128]
STUDY
(MED)
[124]
STUDY
(MED)
[125]
STUDY (SM)
[126]
STUDY (SM)
[127]
OPEN
STUDY
[122A]
HD BOOK
COLLECTION
[122]
OPEN
STUDY
[120A]
VESTIBULE
[1-F]
CIRCULATION
RECEPTION
[110]
OFFICE
[108]
INTER
LIBRARY
LOAN
WORKSPACE
[114]
FAMILY RR
[144]
OPEN
STUDY
[122C]
OPEN
STUDY
[122B]
OPEN
STUDY
[118]
MENS
[146]
WOMENS
[148]
JANITORS
OFFICE
[147]
'EW 3'
OFFICE
[106]
'CP9'
'CP10'
'1LB'
'CP11'
OFFICE
[104]
OFFICE
[114A]
STAIR
[1-H]
STAIR
[1-B]
VESTIBULE
[1-A]
STAIR
[1-D]
HALLWAY
[1-C]
MECH
CHASE
[1-K]
RESERVE
MEDIA
[116]
ELEC
ROOM
[102]
'LLC'
'RA'
'NAC'
EW3-6EW3-4
1
1
CP14-20
CP9-20
8270
STATEOFIDAHO
T
ODD P A Y N EREGISTER
EDRP
OFESSIONALEN
G
I
NE
E
R
1823 E. Center
Pocatello, Idaho 83201
tel (208) 232-4439
www.payneengineeringinc.com
Engineering Inc.
Consulting Engineers
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
P.E. #:2259
10-28-2022 EF101
FIRE ALARM
PLAN LEVEL
1 AREA A
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
BID SET
A. REFER TO SYMBOL SCHEDULE SHEET FOR PROJECT
GENERAL NOTES AND GENERAL NOTES ASSOCIATED WITH
THE INSTALLATION OF EACH SYSTEM, INCLUDINB BUT NOT
LIMITED TO; LIGHTING, POWER, FIRE ALARM, SPECIAL
SYSTEMS, ETC.
GENERAL NOTES:
KEY NOTES:#
1 E.C. SHALL PROVIDE AND INSTALL 120V., ALL REQUIRED
MONITOR RELAY MODULES AND ALL CONTROL
CONNECTIONS TO INTERFACE SMOKE DAMPERS WITH
FIRE ALARM SYSTEM. REFER TO MECH DRAWINGS FOR
EXACT LOCATION. CIRCUIT AS INDICATED.
16'8'0"
NORTH
SCALE: 1/8" = 1'-0"1 LEVEL 1 FIRE ALARM PLAN AREA A
KEY PLAN
A
B
REF.
ID ID
IDID
PCM
RMTSFS
P P
16151413121110987
K
H
F
D
B
A
STORAGE
[170C]
STUDY
[170B]
STUDY
[170A]
CLASSROOM
[168]CLASSROOM
[166]
ADJUNCT
OFFICE
[180]
OFFICE
[181]OFFICE
[182]
OFFICE
[183]
OFFICE
[184]
OFFICE
[185]
OFFICE
[186]
CONFERENCE
ROOM
[158]
CONFERENCE
[188B]
COLLABORATIVE
SPACE
[188]
CLASSROOM
[162]
CLASSROOM
[164]
OFFICE
[190B]
OFFICE
[190A]
TRAINING
AREA
[190]
OFFICE
[192B]
SMALL
MEETING
[192A]
OFFICE
[160A]
OFFICE
[160B]
TUTORING
ADMIN
OPEN AREA
[160]
OFFICE
[156F]
PRACTICE
[156E]
WORKSPACE
[156]
STORAGE
[156D]
DROP IN
MATH LAB
[170]
WORKSTATIONS/
FLEX
SPACE
[192]
CLASSROOM
[172]
STUDENT
PREP
[174]
STUDY
[178]
STUDY
[179]
MATH LAB
RECEPTION
[175]
I.T. HELP
DESK
[176]
OFFICE
[188A]
'1A'
'1LA'
'CP1'
'CP2'
'CP3'
'CP4'
'CC'
'EE''1P'
STORAGE
[190C]
STORAGE
[192C]
PRACTICE
[156C]
PRACTICE
[156B]
PRACTICE
[156A]
VESTIBULE
[1-U]
ELECTRICAL
[173]
VESTIBULE
[1-Z]
MECH
[08]
ELEV
EQUIP
[08A]
ELEV
[1-T]
MEN'S
RESTROOM
[154]
WOMEN'S
RESTROOM
[152]
'M (EAST)'
1
2
EE-6 EE-7
'NAC''RA'
8270
STATEOFIDAHO
T
ODD P A Y N EREGISTER
EDRP
OFESSIONALEN
G
I
NE
E
R
1823 E. Center
Pocatello, Idaho 83201
tel (208) 232-4439
www.payneengineeringinc.com
Engineering Inc.
Consulting Engineers
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
P.E. #:2259
10-28-2022 EF102
FIRE ALARM
PLAN LEVEL
1 AREA B
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
BID SET
A. REFER TO SYMBOL SCHEDULE SHEET FOR PROJECT
GENERAL NOTES AND GENERAL NOTES ASSOCIATED WITH
THE INSTALLATION OF EACH SYSTEM, INCLUDINB BUT NOT
LIMITED TO; LIGHTING, POWER, FIRE ALARM, SPECIAL
SYSTEMS, ETC.
GENERAL NOTES:
KEY NOTES:#
1 DUCT-SMOKE DETECTOR PROVIDED AND CONNECT BY
ELECTRICAL CONTRACTOR, INSTALLED BY MECHANICAL
CONTRACTOR. DETECTOR SHALL BE CONNECTED TO
FIRE ALARM SYSTEM AND SHALL SHUT-DOWN
ASSOCIATED HVAC UNIT UPON ACTIVATION. ELECT.
CONTRACTOR SHALL ALSO PROVIDE AND INSTALL
REMOTE TEST SWITCH, INSTALL FLUSH IN CEILING NEAR
LOCATION OF DUCT-SMOKE DETECTOR.
2 PROVIDE MONITORING OF FLOW AND TAMPER
SWITCHES; VERIFY EXACT NUMBER OF SWITCHES WITH
FIRE SPRINKLER CONTRACTOR.
16'8'0"
NORTH
SCALE: 1/8" = 1'-0"1 LEVEL 1 FIRE ALARM PLAN AREA B KEY PLAN
A
B
P
SD
SD
SD
SD
SD
SD
1
G
J
L
M
N
P
Q
E
C
2 3 4 5 61.5
ELECTRICAL
ROOM
[242]
TECH
SERVICES
[238]
SHEET
MUSIC
[236]
LARGE
COMPUTER
CLASSROOM
[234]
OPEN
COMPUTERS
[240]
OPEN
STUDY
[53]
PRESS
ROOM
[226]
SPECIAL
COLLECTIONS
[228]
VAULT
[228E]
ARCHIVE
[228D]
INSTRUCTION
2
[224]
INSTRUCTION
1
[222]
DCAM
[228B]
OFFICE
[228A]
SCANNER
[228C]
OFFICE
[232]
STUDY
(MED)
[216]
STUDY
(MED)
[214]
STUDY
(MED)
[218]
OFFICE
[230]
OFFICE
[202]
STUDY (SM)
[212]
STUDY (SM)
[210]STUDY (SM)
[208]
OFFICE
[200]
OPEN
STUDY
[220]
'CP12'
'G'
'F1'
'F'
'UPS'
'EW2'
'CP14'
'2LB'
'2W
A'
'CP13'
'D'
TECH SERV
STORAGE
[2-E]
STUDY (SM)
[204]
JANITOR'S
OFFICE
[241]
MECHANICAL
[2-D]
I.T.
[245]
MEN'S
RESTROOM
[247]
WOMEN'S
RESTROOM
[248]
STAIR
[2-G]
ELEV
[2-H]
MECH
CHASE
[2-J]
STAIR
[2-A]
STAIR
[2-B]
MOTHERS
[243]
FAMILY RR
[244]
STUDY
(MED)
[206]
EW2-13 EW2-15
'RA''NAC'
1
1
CP14-20
CP9-20
8270
STATEOFIDAHO
T
ODD P A Y N EREGISTER
EDRP
OFESSIONALEN
G
I
NE
E
R
1823 E. Center
Pocatello, Idaho 83201
tel (208) 232-4439
www.payneengineeringinc.com
Engineering Inc.
Consulting Engineers
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
P.E. #:2259
10-28-2022 EF103
FIRE ALARM
PLAN LEVEL
2 AREA A
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
BID SET
A. REFER TO SYMBOL SCHEDULE SHEET FOR PROJECT
GENERAL NOTES AND GENERAL NOTES ASSOCIATED WITH
THE INSTALLATION OF EACH SYSTEM, INCLUDINB BUT NOT
LIMITED TO; LIGHTING, POWER, FIRE ALARM, SPECIAL
SYSTEMS, ETC.
GENERAL NOTES:
KEY NOTES:#
1 E.C. SHALL PROVIDE AND INSTALL 120V., ALL REQUIRED
MONITOR RELAY MODULES AND ALL CONTROL
CONNECTIONS TO INTERFACE SMOKE DAMPERS WITH
FIRE ALARM SYSTEM. REFER TO MECH DRAWINGS FOR
EXACT LOCATION. CIRCUIT AS INDICATED.
16'8'0"
NORTH
SCALE: 1/8" = 1'-0"1 LEVEL 2 FIRE ALARM PLAN AREA A
KEY PLAN
A
B
REF.
REF.
P
H
P
16151413121110987
K
H
F
D
B
A
CLASSROOM
[272]
OFFICE
[288B]
ENGLISH
TRANSITION
CENTER
[288]
OPEN
TUTORING
[254]
STUDY
SKILLS
[252]
WRITING
CENTER
OPEN
TUTORING
[256]
STUDY
[269]
STUDY
[268]
STUDY
[267]
STUDY
[266]
OFFICE
[265]
OFFICE
[264]
STORAGE
[270J]
STUDY
[270H]
PREP /
STORAGE
[270B]
CLASSROOM
[258]
CLASSROOM
[260]
PREP /
STORAGE
[256A]
OFFICE
[256B]
OFFICE
[256C]
OPEN
TUTORING
CENTER
[270]
ADJUNCT
OFFICE
[286]TR / COMM.
[280]
CLASSROOM
[278]
PRE-FUNCTION
[270C]
PRE-FUNCTION
[270D]
PRE-FUNCTION
[270E]
RECEPTION
[270A]
PREFUNCTION
[270F]
'CP8'
'CP6'
'CP5'
'2LA'
'2B'
'2A'
'EE2'
'UPS1'
STUDY
[270G]
STORAGE
[252F]
PREP /
STORAGE
[252G]
STUDY
[252B]
STUDY
[252A]
ELEV
[2-R]
STUDY
[252C]
OFFICE
[252D]
OFFICE
[288C]
STUDY
[288D]
STUDY
[288E]
STUDY
[288F]STUDY
[288G]
STORAGE
[288H]
STUDY
[288A]
'FACP'
'RA''NAC'
EE2-3
EE2-5
EE2-1
1
8270
STATEOFIDAHO
T
ODD P A Y N EREGISTER
EDRP
OFESSIONALEN
G
I
NE
E
R
1823 E. Center
Pocatello, Idaho 83201
tel (208) 232-4439
www.payneengineeringinc.com
Engineering Inc.
Consulting Engineers
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
P.E. #:2259
10-28-2022 EF104
FIRE ALARM
PLAN LEVEL
2 AREA B
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
BID SET
A. REFER TO SYMBOL SCHEDULE SHEET FOR PROJECT
GENERAL NOTES AND GENERAL NOTES ASSOCIATED WITH
THE INSTALLATION OF EACH SYSTEM, INCLUDINB BUT NOT
LIMITED TO; LIGHTING, POWER, FIRE ALARM, SPECIAL
SYSTEMS, ETC.
GENERAL NOTES:
KEY NOTES:#
1 E.C. SHALL PROVIDE AND INSTALL 4-STRAND
SINGLE-MODE FIBER FROM 'FACP' IT ROOM AND
PROVIDE ALL REQUIRED TERMINATIONS. INSTALL FIBER
IN INNER-DUCT AND CONDUIT. FIELD COORDINATE
ROUTING.
16'8'0"
NORTH
SCALE: 1/8" = 1'-0"1 LEVEL 2 FIRE ALARM PLAN AREA B KEY PLAN
A
B
H
P
P
P
SD
SD
SD
SD
SD
SD
1
G
J
L
M
N
P
Q
E
C
2 3 4 5 61.5
STUDY (SM)
[332]
STUDY (SM)
[336]
STUDY (SM)
[314]
STUDY (SM)
[316]
ELEC
[364]
STUDY (SM)
[320]
STUDY (SM)
[338]
STUDY (SM)
[318]
ELECTRICAL
[324B]
STUDY (SM)
[334]
OFFICE
[310]
OFFICE
[312]
JUVENILE
[300]
STORAGE
[306]
STUDY
(MED)
[304]
STUDY
(MED)
[302]
KIDS PLAY
[344C]
MOTHERS
ROOM
[344A]
RESTROOM
[344B]
FAMILY
STUDY
[344]
( QUIET )
OPEN
STUDY
[342]
OPEN
STUDY
[362]
Bridge
Connection
[-]
BRIDGE
CONNECTION
[3-A]
STAIR 1
[3-B]
MENS
[368]
WOMENS
[366]
TEST RM
[378]
STUDY (SM)
[330]
Janitors
Closet
[376]
OFFICE
[322]
MAC EQUIP
[324A]
STUDY (LG)
[328]
STUDY (LG)
[326]
MAC LAB
[324]
TEST RM
[374]
STUDY (SM)
[340]
'CP16'
'CP15'
'3W B'
'K'
'3LA'
'3W
A'
'CP17'
'CP18''N'
'H'
ELECTRICAL
[308]
STORAGE
[352]
TEST RM
[382]
TEST RM
[380]
TEST RM
[372]
TEST RM
[370]
TEST RM
[360]TEST RM
[358]TEST RM
[356]
TEST RM
[350]
TEST RM
[348]TEST RM
[346]
MECH
CHASE
[3-E]
MECH
[3-D]
'NAC''RA'EW2-17
EW2-14
1
1
CP14-20
CP9-20
8270
STATEOFIDAHO
T
ODD P A Y N EREGISTER
EDRP
OFESSIONALEN
G
I
NE
E
R
1823 E. Center
Pocatello, Idaho 83201
tel (208) 232-4439
www.payneengineeringinc.com
Engineering Inc.
Consulting Engineers
3 6 0 w e s t a s p e n a v e n u e
s a l t l a k e c i t y , u t a h 8 4 1 0 1
8 0 1 5 3 2 4 4 2 2
sheet:
title:
revisions :
p r o j e c t # :
d a t e :
UNLESS A PROFESSIONAL SEAL WITH SIGNATURE AND
DATE IS AFFIXED, THIS DOCUMENT IS PRELIMINARY AND IS
NOT INTENDED FOR CONSTRUCTION, RECORDING
PURPOSES, OR IMPLEMENTATION
THE DESIGNS SHOWN AND DESCRIBED HEREIN INCLUDING
ALL TECHNICAL DRAWINGS, GRAPHIC REPRESENTATIONS &
MODELS THEREOF, ARE PROPRIETARY & CAN NOT BE
COPIED, DUPLICATED, OR COMMERCIALLY EXPLOITED IN
WHOLE OR IN PART WITHOUT THE SOLE AND EXPRESS
WRITTEN PERMISSION FROM METHOD STUDIO INC.
project:
E
D
C
B
A
E
D
C
B
A
1 2 3 4 5 6
1 2 3 4 5 6
P.E. #:2259
10-28-2022 EF105
FIRE ALARM
PLAN LEVEL
3
21.0780
10/28/2022
BRIGHAM YOUNG UNIVERSITY -
IDAHO
294 S 1st E, Rexburg, ID 83460
MCK Library
Remodel
BID SET
A. REFER TO SYMBOL SCHEDULE SHEET FOR PROJECT
GENERAL NOTES AND GENERAL NOTES ASSOCIATED WITH
THE INSTALLATION OF EACH SYSTEM, INCLUDINB BUT NOT
LIMITED TO; LIGHTING, POWER, FIRE ALARM, SPECIAL
SYSTEMS, ETC.
GENERAL NOTES:
KEY NOTES:#
1 E.C. SHALL PROVIDE AND INSTALL 120V., ALL REQUIRED
MONITOR RELAY MODULES AND ALL CONTROL
CONNECTIONS TO INTERFACE SMOKE DAMPERS WITH
FIRE ALARM SYSTEM. REFER TO MECH DRAWINGS FOR
EXACT LOCATION. CIRCUIT AS INDICATED.
SCALE: 1/8" = 1'-0"1 LEVEL 3 FIRE ALARM PLAN
NORTH
16'8'0"