Engineering Addendum
Project Name: Harris Architecture Palisades
Apartments (Rexburg) 3110323
Project Location: Pioneer Rd and Mariah Ave
Rexburg, Idaho 83460
Project Number: 3110323
Date: 5/12/2023
The following is in response to an email request from Jared Hill on 05/12/2023:
City correction items have been addressed.
1. Special inspection requirements have been added to the plans on sheet SN2.
2. A note about waterproofing per IBC 1805 has been added to the general structural notes.
3. A note was added to the foundation plan addressing the bar placement in the foundation wall.
744 S. 400 E.
Orem, Utah 84097
Phone 801.229.9020
Fax 801.224.0050
info@acuteengineering.com
3
5
2
) ( 6 6 , 2 1 $ / ( 1 * , 1 ( ( 5 / , & ( 1 6 ( '
6 7 $ 7 ( 2 ) , ' $ + 2
&
+
5
, 6 7 2 3 + ( 5 + , 5 2 6 + , < ( $
7
(
6
06/30/2023
1
Ryan Wilkinson
From:Jared Hill <jared@harris-arc.com>
Sent:Friday, May 12, 2023 10:02 AM
To:Chris Yeates; Todd Payne
Cc:Dave Hansen
Subject:Palisades city comments
Chris and Todd,
Here is the drop box link to the city comments that I got back this morning.
hƩps://www.dropbox.com/scl/fo/kmm91b8pgo9e9zjmy4s0u/h?dl=0&rlkey=ok2m5vhy42zfqzwvhgy831oeq
Dave, I did not see any comments for you, however but can you just look and verify that I did not miss anything.
Thanks everyone.
JARED HILL
Project Manager
O 801.377.6303 ext 110
920 East 800 North #201, Orem, UT 84097 | www.harris-architecture.com
Author Name Author Email Author Phone No.:
Cody Jones Cody.Jones@rexburg.org 208-372-2173
Don Allen Don.Allen@rexburg.org 208-372-2174
Alex Owens Alex.Owens@rexburg.org 208-372-2172
Description : Palisade Apartments
Address : RPRPNRV0020010
Application Type :
Document Filename : ~PALISADES APARTMENT - FULL SET SUBMITAL_1 - 2023-0504.pdf Array
Comment Author Contact Information:
Corrections in the following table need to be applied before a permit can be issued
Review Report
Revisions Required
Page Reference Annotation
Type
Author : Department Status Page Review Comments Applicant Response Comments
G0.1 Free Text Cody Jones : Building Open 2 2018
G0.1 Free Text Cody Jones : Building Open 2 2018
G0.1 Free Text Cody Jones : Building Open 2 Need Envelope COMM check or prescriptive form signed.
Engineered truss plans need to be approved by building
design professional.
Cross slope of landings and sidewalks not to exceed 2%.
Ventilation to comply IBC section 1203.
Dwelling unit sound transmission toto have a class of not less
than 50, unless tested.
Exit signs and Exit lighting to comply with 1008 and 1013.
Emergency Escape openings to comply with 1030.
G07 Free Text Cody Jones : Building Open 8 2% of units to be type A.
G07 Free Text Cody Jones : Building Open 8 Other then type A units the remainder to be type B units.
A5.1 Free Text Cody Jones : Building Open 38 Section 708.4.2, exception #4 requires draft stopping above
every two units or 3,000 square feet whichever is less.
A5.1 Free Text Cody Jones : Building Open 38 2018
SN1 Free Text Cody Jones : Building Open 47 Special Inspector to be identified as per Section 1704.
# 23-00257
New Multi-Family Residence
Please digitally re-submit all pages of the plan set in response to requested revisions
for our next review cycle, with noted items resolved.
Report Date: 05.11.2023
Approval of plans does not constitute approval of variance from code
Page 1 of 2
Page Reference Annotation
Type
Author : Department Status Page Review Comments Applicant Response Comments
SN1 Free Text Cody Jones : Building Open 47 Waterproofing to comply with 1805.
S0-0 Note Cody Jones : Building Open 48 Rebar: 8' Wall-Horizontal & Vertical 24" O.C. with 2 in Top 12"
Rebar: 4' Wall-Horizontal & Vertical 24" O.C. with 1 in Top 6"
E1.0 Callout Alex Owens : Electrical Open 72 All electrical work must comply with 2017 NEC.
E3.0 Callout Alex Owens : Electrical Open 80 For verification: Idaho has exempted afci protection
requirements in kitchens.
E3.0 Callout Alex Owens : Electrical Open 80 For verification: Idaho has exempted gfci protection
requirements for dishwashers/disposals under sink.
E3.0 Callout Alex Owens : Electrical Open 80 For verification: 2017 NEC does not require panels in
residential applications to be main breaker.
E3.1 Free Text Alex Owens : Electrical Open 81 Notes on page 80 apply
E3.2 Callout Alex Owens : Electrical Open 82 Please provide available fault current calculation for service.
E3.2 Free Text Alex Owens : Electrical Open 82 Notes on page 80 apply
Report Date: 05.11.2023
Approval of plans does not constitute approval of variance from code
Page 2 of 2
Powered by TCPDF (www.tcpdf.org)
Author Name Author Email Author Phone No.:
Cody Jones Cody.Jones@rexburg.org 208-372-2173
Description : Juniper Sands Apartments - Bldg #4 - 60 Units
Address : 720 Cornelison Ave (formally Palisades)
Application Type :
Document Filename : ~PALISADES APARTMENT - SUBMITAL_3 - 2023-0608.pdf Array
Comment Author Contact Information:
Corrections in the following table need to be applied before a permit can be issued
Review Report
Revisions Required
Page Reference Annotation
Type
Author : Department Status Page Review Comments Applicant Response Comments
1 Free Text Cody Jones : Building Open 1 Need Envelope COMM check.
49 Free Text Cody Jones : Building Open 49 As per city ordinance walls 8' or taller needs to have two #4
bar in top 6".
# 23-00257
New Multi-Family Residence
Please digitally re-submit all pages of the plan set in response to requested revisions
for our next review cycle, with noted items resolved.
Dampproofing/Waterproofing comply with IBC Section 1805
Report Date: 06.28.2023
Approval of plans does not constitute approval of variance from code
Page 1 of 1