HomeMy WebLinkAboutCOMCHECK 7-6-23 - 23-00257 - Juniper Sands Apartments - Bldg #4 - 60 UnitsCOMcheck Software Version COMcheckWeb
Envelope Compliance Certificate
Project Title:
2018 IECC
Project Type:New Construction
Vertical Glazing / Wall Area:10%
Location:Rexburg, Idaho
Climate Zone:6b
Construction Site:
720 Cornelison Ave
rexburg, Idaho 83440
Owner/Agent:
scott page
VENTURE BUIDLERS LLC
2535 Little Town Drive
rexburg, Idaho 83440
2088215592
scott@venturebuilders-id.com
Designer/Contractor:
scott page
VENTURE BUIDLERS LLC
2535 Little Town Drive
rexburg, Idaho 83440
2088215592
scott@venturebuilders-id.com
Project Information
Energy Code:
Juniper Sands
Credits: 1.0 Required 1.0 Proposed
High Performance HVAC, 1.0 credit
Additional Efficiency Package(s)
Building Area Floor Area
1-Apartments (Multifamily) : Nonresidential 30618
Envelope Assemblies
Assembly Cavity
R-Value
Cont.
R-Value
Proposed
U-Factor
Budget U-
Factor(a)
Gross Area
or
Perimeter
Floor: Wood-Framed, [Bldg. Use 1 - Apartments]10206 30.0 0.0 0.033 0.033
Floor: Wood-Framed, [Bldg. Use 1 - Apartments]10206 30.0 0.0 0.033 0.033
Floor: Wood-Framed, [Bldg. Use 1 - Apartments]10206 30.0 0.0 0.033 0.033
Floor: Wood-Framed, [Bldg. Use 1 - Apartments]10206 30.0 0.0 0.033 0.033
Roof: Attic Roof, Wood Joists, [Bldg. Use 1 - Apartments]11343 50.0 0.0 0.021 0.021
NORTH
Basement: Solid Concrete, 8in. Thickness, Normal Density,
Furring: Wood, Wall Ht 10.0, Depth B.G. 0.0, [Bldg. Use 1 -
Apartments]
2300 30.0 0.0 0.047 0.119
Door: Insulated Metal, Swinging, [Bldg. Use 1 - Apartments]25 ------0.510 0.370
Window: Other Window: Operable, Perf. Specs.: Product ID
EWG-K-82-00005-00001, SHGC 0.34, [Bldg. Use 1 -
Apartments] (c)
2240 ------0.300 0.430
Ext. Wall: Wood-Framed, 16in. o.c., [Bldg. Use 1 - Apartments]6888 22.0 0.0 0.061 0.051
EAST
Basement: Solid Concrete, 8in. Thickness, Normal Density,
Furring: Wood, Wall Ht 10.0, Depth B.G. 0.0, [Bldg. Use 1 -
Apartments]
860 30.0 0.0 0.047 0.119
Ext. Wall: Wood-Framed, 16in. o.c., [Bldg. Use 1 - Apartments]1439 22.0 0.0 0.061 0.051
SOUTH
Basement: Solid Concrete, 8in. Thickness, Normal Density,
Furring: Wood, Wall Ht 10.0, Depth B.G. 0.0, [Bldg. Use 1 -
Apartments]
1550 30.0 0.0 0.047 0.119
Project Title:
Data filename:
Juniper Sands 07/06/23Report date:
181 ofPage
Assembly Cavity
R-Value
Cont.
R-Value
Proposed
U-Factor
Budget U-
Factor(a)
Gross Area
or
Perimeter
Ext. Wall: Wood-Framed, 16in. o.c., [Bldg. Use 1 - Apartments]6071 22.0 0.0 0.061 0.051
WEST
Basement: Solid Concrete, 8in. Thickness, Normal Density,
Furring: Wood, Wall Ht 10.0, Depth B.G. 0.0, [Bldg. Use 1 -
Apartments]
860 30.0 0.0 0.047 0.119
Ext. Wall: Wood-Framed, 16in. o.c., [Bldg. Use 1 - Apartments]1439 22.0 0.0 0.061 0.051
(a)Budget U-factors are used for software baseline calculations ONLY, and are not code requirements.
(b)'Other' components require supporting documentation for proposed U-factors.
(c)Fenestration product performance must be certified in accordance with NFRC and requires supporting documentation.
Envelope Compliance Statement
Compliance Statement: The proposed envelope design represented in this document is consistent with the building plans,
specifications, and other calculations submitted with this permit application. The proposed envelope systems have been
designed to meet the 2018 IECC requirements in COMcheck Version COMcheckWeb and to comply with any applicable
mandatory requirements listed in the Inspection Checklist.
Name - Title Signature Date
Envelope PASSES: Design 10% better than code
Project Title:
Data filename:
Juniper Sands 07/06/23Report date:
182 ofPage
COMcheck Software Version COMcheckWeb
Interior Lighting Compliance Certificate
Project Title:
2018 IECC
Project Type:New Construction
Construction Site:
720 Cornelison Ave
rexburg, Idaho 83440
Owner/Agent:
scott page
VENTURE BUIDLERS LLC
2535 Little Town Drive
rexburg, Idaho 83440
2088215592
scott@venturebuilders-id.com
Designer/Contractor:
scott page
VENTURE BUIDLERS LLC
2535 Little Town Drive
rexburg, Idaho 83440
2088215592
scott@venturebuilders-id.com
Project Information
Energy Code:
Juniper Sands
Credits: 1.0 Required 1.0 Proposed
High Performance HVAC, 1.0 credit
Additional Efficiency Package(s)
Allowed Interior Lighting Power
A
Area Category
B
Floor Area
(ft2)
C
Allowed
Watts / ft2
D
Allowed Watts
1-Apartments (Multifamily)30618 0.68 20820
20820Total Allowed Watts =
Proposed Interior Lighting Power
E
(C X D)
D
Fixture
Watt.
A
Fixture ID : Description / Lamp / Wattage Per Lamp / Ballast
B
Lamps/
Fixture
C
# of
Fixture
1-Apartments (Multifamily)
LED: LED Other Fixture Unit 28W:3 120 28 3360
3360Total Proposed Watts =
Interior Lighting Compliance
Statement
Compliance Statement: The proposed interior lighting design represented in this document is consistent with the building plans,
specifications, and other calculations submitted with this permit application. The proposed interior lighting systems have been
designed to meet the 2018 IECC requirements in COMcheck Version COMcheckWeb and to comply with any applicable
mandatory requirements listed in the Inspection Checklist.
Name - Title Signature Date
Interior Lighting PASSES: Design 84% better than code
Project Title:
Data filename:
Juniper Sands 07/06/23Report date:
183 ofPage
COMcheck Software Version COMcheckWeb
Exterior Lighting Compliance Certificate
Project Title:
2018 IECC
Project Type:New Construction
Construction Site:
720 Cornelison Ave
rexburg, Idaho 83440
Owner/Agent:
scott page
VENTURE BUIDLERS LLC
2535 Little Town Drive
rexburg, Idaho 83440
2088215592
scott@venturebuilders-id.com
Designer/Contractor:
scott page
VENTURE BUIDLERS LLC
2535 Little Town Drive
rexburg, Idaho 83440
2088215592
scott@venturebuilders-id.com
Project Information
Energy Code:
Juniper Sands
2 (Residential mixed use area (LZ2))Exterior Lighting Zone
Allowed Exterior Lighting Power
A
Area/Surface Category
B
Quantity
C
Allowed
Watts /
D
Tradable
Wattage
E
Allowed Watts
(B X C)
Front/Rear entrance (Entry canopy)2 ft2 0.25 Yes 0
Total Tradable Watts (a) =
Total Allowed Watts =
Total Allowed Supplemental Watts (b) =
0
0
400
(a)Wattage tradeoffs are only allowed between tradable areas/surfaces.
(b)A supplemental allowance equal to 400 watts may be applied toward compliance of both non-tradable and tradable
areas/surfaces.
Proposed Exterior Lighting Power
E
(C X D)
D
Fixture
Watt.
A
Fixture ID : Description / Lamp / Wattage Per Lamp / Ballast
B
Lamps/
Fixture
C
# of
Fixture
Front/Rear entrance (Entry canopy, 2 ft2): Tradable Wattage
LED: LED A Lamp 25W:1 12 28 336
336Total Tradable Proposed Watts =
Exterior Lighting Compliance
Statement
Compliance Statement: The proposed exterior lighting design represented in this document is consistent with the building plans,
specifications, and other calculations submitted with this permit application. The proposed exterior lighting systems have been
designed to meet the 2018 IECC requirements in COMcheck Version COMcheckWeb and to comply with any applicable
mandatory requirements listed in the Inspection Checklist.
Name - Title Signature Date
Exterior Lighting PASSES: Design 16% better than code
Project Title:
Data filename:
Juniper Sands 07/06/23Report date:
184 ofPage
COMcheck Software Version COMcheckWeb
Mechanical Compliance Certificate
Project Title:
2018 IECC
Project Type:New Construction
Location:Rexburg, Idaho
Climate Zone:6b
Construction Site:
720 Cornelison Ave
rexburg, Idaho 83440
Owner/Agent:
scott page
VENTURE BUIDLERS LLC
2535 Little Town Drive
rexburg, Idaho 83440
2088215592
scott@venturebuilders-id.com
Designer/Contractor:
scott page
VENTURE BUIDLERS LLC
2535 Little Town Drive
rexburg, Idaho 83440
2088215592
scott@venturebuilders-id.com
Project Information
Energy Code:
Juniper Sands
Credits: 1.0 Required 1.0 Proposed
High Performance HVAC, 1.0 credit
Additional Efficiency Package(s)
Mechanical Systems List
Quantity System Type & Description
Cooling: 1 each - Single Package Vertical AC Unit, Capacity = 60000 kBtu/h, Evaporatively Cooled Condenser, Air
Economizer
Proposed Efficiency = 0.00 EER, Required Efficiency = 9.46 EER
Proposed Part Load Efficiency = 0.00 , Required Part Load Efficiency = 0.00
SYSTEM COMPLIANCE FAILS: PROPOSED EFFICIENCY FAILS TO MEET CODE REQUIREMENTS.
1 HVAC System (Unknown):
Project Title:
Data filename:
Juniper Sands 07/06/23Report date:
185 ofPage
Inspection Checklist
Requirements: 0.0% were addressed directly in the COMcheck software
COMcheck Software Version COMcheckWeb
Text in the "Comments/Assumptions" column is provided by the user in the COMcheck Requirements screen. For each
requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception
is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided.
Energy Code: 2018 IECC
Section
#
& Req.ID
Plan Review Complies?Comments/Assumptions
C103.2
[PR1]1
Plans and/or specifications provide all
information with which compliance
can be determined for the building
envelope and document where
exceptions to the standard are
claimed.
Complies
Does Not
Not Observable
Not Applicable
C103.2
[PR2]1
Plans, specifications, and/or
calculations provide all information
with which compliance can be
determined for the mechanical
systems and equipment and
document where exceptions to the
standard are claimed. Load
calculations per acceptable
engineering standards and
handbooks.
Complies
Does Not
Not Observable
Not Applicable
C103.2
[PR4]1
Plans, specifications, and/or
calculations provide all information
with which compliance can be
determined for the interior lighting
and electrical systems and equipment
and document where exceptions to
the standard are claimed. Information
provided should include interior
lighting power calculations, wattage of
bulbs and ballasts, transformers and
control devices.
Complies
Does Not
Not Observable
Not Applicable
C103.2
[PR8]1
Plans, specifications, and/or
calculations provide all information
with which compliance can be
determined for the exterior lighting
and electrical systems and equipment
and document where exceptions to
the standard are claimed. Information
provided should include exterior
lighting power calculations, wattage of
bulbs and ballasts, transformers and
control devices.
Complies
Does Not
Not Observable
Not Applicable
C402.4.1
[PR10]1
The vertical fenestration area <= 30
percent of the gross above-grade wall
area.
Complies
Does Not
Not Observable
Not Applicable
C402.4.1
[PR11]1
The skylight area <= 3 percent of the
gross roof area.
Complies
Does Not
Not Observable
Not Applicable
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Juniper Sands 07/06/23Report date:
186 ofPage
Section
#
& Req.ID
Plan Review Complies?Comments/Assumptions
C406
[PR9]1
Plans, specifications, and/or
calculations provide all information
with which compliance can be
determined for the additional energy
efficiency package options.
Complies
Does Not
Not Observable
Not Applicable
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Juniper Sands 07/06/23Report date:
187 ofPage
Section
#
& Req.ID
Footing / Foundation Inspection Complies?Comments/Assumptions
C303.2
[FO2]2
Below-grade wall insulation installed
per manufacturer’s instructions.
Complies
Does Not
Not Observable
Not Applicable
C303.2.1
[FO6]1
Exterior insulation protected against
damage, sunlight, moisture, wind,
landscaping and equipment
maintenance activities.
Complies
Does Not
Not Observable
Not Applicable
C402.1.4
[FO1]2
Installed below-grade wall insulation
type and R-value consistent with
insulation specifications reported in
plans and COMcheck reports.
Complies
Does Not
Not Observable
Not Applicable
See the Envelope Assemblies table for values.
C403.12.2
,
C403.12.3
[FO9]3
Snow/ice melting system and freeze
protection systems have sensors and
controls configured to limit service for
pavement temperature and outdoor
temperature. future connection to
controls.
Complies
Does Not
Not Observable
Not Applicable
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Juniper Sands 07/06/23Report date:
188 ofPage
Section
#
& Req.ID
Framing / Rough-In Inspection Complies?Comments/Assumptions
C303.1.3
[FR12]2
Fenestration products rated in
accordance with NFRC.
Complies
Does Not
Not Observable
Not Applicable
C303.1.3
[FR13]1
Fenestration products are certified as
to performance labels or certificates
provided.
Complies
Does Not
Not Observable
Not Applicable
C402.4.3
[FR10]1
Vertical fenestration SHGC value.Complies
Does Not
Not Observable
Not Applicable
See the Envelope Assemblies table for values.
C402.4.3,
C402.4.3.
4
[FR8]1
Installed vertical fenestration U-factor
and SHGC consistent with label
specifications and as reported in plans
and COMcheck reports.
Complies
Does Not
Not Observable
Not Applicable
See the Envelope Assemblies table for values.
C402.5.1.
2.2
[FR20]1
The building envelope contains a
continuous air barrier that is sealed in
an approved manner and average
assembly air leakage <= 0.04 cfm/ft2.
Air barrier penetrations are sealed in
an approved manner.
Complies
Does Not
Not Observable
Not Applicable
C402.5.2,
C402.5.4
[FR18]3
Factory-built fenestration and doors
are labeled as meeting air leakage
requirements.
Complies
Does Not
Not Observable
Not Applicable
C402.5.7
[FR17]3
Vestibules are installed on all building
entrances. Doors have self-closing
devices.
Complies
Does Not
Not Observable
Not Applicable
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Juniper Sands 07/06/23Report date:
189 ofPage
Section
#
& Req.ID
Plumbing Rough-In Inspection Complies?Comments/Assumptions
C404.5,
C404.5.1,
C404.5.2
[PL6]3
Heated water supply piping conforms
to pipe length and volume
requirements. Refer to section details.
Complies
Does Not
Not Observable
Not Applicable
C404.6.3
[PL7]3
Pumps that circulate water between a
heater and storage tank have controls
that limit operation from startup to
<= 5 minutes after end of heating
cycle.
Complies
Does Not
Not Observable
Not Applicable
C404.7
[PL8]3
Demand recirculation water systems
have controls that start the pump
upon receiving a signal from the
action of a user of a fixture or
appliance and limits the temperature
of the water entering the cold-water
piping to 104°F.
Complies
Does Not
Not Observable
Not Applicable
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Juniper Sands 07/06/23Report date:
1810 ofPage
Section
#
& Req.ID
Mechanical Rough-In Inspection Complies?Comments/Assumptions
C402.2.6
[ME41]3
Thermally ineffective panel surfaces of
sensible heating panels have
insulation >= R-3.5.
Complies
Does Not
Not Observable
Not Applicable
C402.5.5,
C403.2.4.
3
[ME3]3
Stair and elevator shaft vents have
motorized dampers that automatically
close. Refernece section C403.7.7 for
operational details.
Complies
Does Not
Not Observable
Not Applicable
C403.7.7
[ME58]3
Outdoor air and exhaust systems have
motorized dampers that automatically
shut when not in use and meet
maximum leakage rates. Check
gravity dampers where allowed.
Reference section language for
operational details.
Complies
Does Not
Not Observable
Not Applicable
C403.8.1
[ME65]3
HVAC fan systems at design
conditions do not exceed allowable
fan system motor nameplate hp or fan
system bhp.
Complies
Does Not
Not Observable
Not Applicable
See the Mechanical Systems list for values.
C403.8.3
[ME117]2
Fans have efficiency grade (FEG) >=
67. The total efficiency of the fan at
the design point of operation <= 15%
of maximum total efficiency of the
fan.
Complies
Does Not
Not Observable
Not Applicable
C403.12.1
[ME71]2
Systems that heat outside the building
envelope are radiant heat systems
controlled by an occupancy sensing
device or timer switch.
Complies
Does Not
Not Observable
Not Applicable
C403.5.5
[ME113]2
Fault detection and diagnostics
installed with air-cooled unitary DX
units having economizers.
Complies
Does Not
Not Observable
Not Applicable
C403.2.2
[ME59]1
Natural or mechanical ventilation is
provided in accordance with
International Mechanical Code
Chapter 4. Mechanical ventilation has
capability to reduce outdoor air supply
to minimum per IMC Chapter 4.
Complies
Does Not
Not Observable
Not Applicable
C403.7.1
[ME59]1
Demand control ventilation provided
for spaces >500 ft2 and >25
people/1000 ft2 occupant density and
served by systems with air side
economizer, auto modulating outside
air damper control, or design airflow
>3,000 cfm.
Complies
Does Not
Not Observable
Not Applicable
C403.7.2
[ME115]3
Enclosed parking garage ventilation
has automatic contaminant detection
and capacity to stage or modulate
fans to 50% or less of design capacity.
Complies
Does Not
Not Observable
Not Applicable
C403.7.6
[ME141]3
HVAC systems serving guestrooms in
Group R-1 buildings with > 50
guestrooms: Each guestroom is
provided with controls that
automatically manage temperature
setpoint and ventilation (see sections
C403.7.6.1 and C403.7.6.2).
Complies
Does Not
Not Observable
Not Applicable
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Juniper Sands 07/06/23Report date:
1811 ofPage
Section
#
& Req.ID
Mechanical Rough-In Inspection Complies?Comments/Assumptions
C403.7.4
[ME57]1
Exhaust air energy recovery on
systems meeting Table C403.7.4(1)
and C403.7.4(2).
Complies
Does Not
Not Observable
Not Applicable
C403.7.5
[ME116]3
Kitchen exhaust systems comply with
replacement air and conditioned
supply air limitations, and satisfy hood
rating requirements and maximum
exhaust rate criteria.
Complies
Does Not
Not Observable
Not Applicable
C403.11.1
,
C403.11.2
[ME60]2
HVAC ducts and plenums insulated in
accordance with C403.11.1 and
constructed in accordance with
C403.11.2, verification may need to
occur during Foundation Inspection.
Complies
Does Not
Not Observable
Not Applicable
C403.5,
C403.5.1,
C403.5.2
[ME62]1
Air economizers provided where
required, meet the requirements for
design capacity, control signal,
ventilation controls, high-limit shut-off,
integrated economizer control, and
provide a means to relieve excess
outside air during operation.
Complies
Does Not
Not Observable
Not Applicable
C403.5.3.
3
[ME124]1
Air economizers automatically reduce
outdoor air intake to the design
minimum outdoor air quantity when
outdoor air intake will not reduce
cooling energy usage. See Table
C403.5.3.3 for applicable device types
and climate zones.
Complies
Does Not
Not Observable
Not Applicable
C403.5.3.
4
[ME125]1
System capable of relieving excess
outdoor air during air economizer
operation to prevent overpressurizing
the building. The relief air outlet
located to avoid recirculation into the
building.
Complies
Does Not
Not Observable
Not Applicable
C403.5.3.
5
[ME126]1
Return, exhaust/relief and outdoor air
dampers used in economizers have
motorized dampers that automatically
shut when not in use and meet
maximum leakage rates. Reference
section C403.7.7 for details.
Complies
Does Not
Not Observable
Not Applicable
C403.4.1.
4
[ME63]2
Heating for vestibules and air curtains
with integral heating include
automatic controls that shut off the
heating system when outdoor air
temperatures > 45F. Vestibule
heating and cooling systems
controlled by a thermostat in the
vestibule with heating setpoint <=
60F and cooling setpoint >= 80F.
Complies
Does Not
Not Observable
Not Applicable
C408.2.2.
1
[ME53]3
Air outlets and zone terminal devices
have means for air balancing.
Complies
Does Not
Not Observable
Not Applicable
C403.5,
C403.5.1,
C403.5.2
[ME123]3
Refrigerated display cases, walk-in
coolers or walk-in freezers served by
remote compressors and remote
condensers not located in a
condensing unit, have fan-powered
condensers that comply with Sections
C403.5.1 and refrigeration compressor
systems that comply with C403.5.2..
Complies
Does Not
Not Observable
Not Applicable
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Juniper Sands 07/06/23Report date:
1812 ofPage
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Juniper Sands 07/06/23Report date:
1813 ofPage
Section
#
& Req.ID
Rough-In Electrical Inspection Complies?Comments/Assumptions
C405.2.2.
2
[EL22]1
Spaces required to have light-
reduction controls have a manual
control that allows the occupant to
reduce the connected lighting load in
a reasonably uniform illumination
pattern >= 50 percent.
Complies
Does Not
Not Observable
Not Applicable
C405.2.1,
C405.2.1.
1
[EL18]1
Occupancy sensors installed in
classrooms/lecture/training rooms,
conference/meeting/multipurpose
rooms, copy/print rooms,
lounges/breakrooms, enclosed offices,
open plan office areas, restrooms,
storage rooms, locker rooms,
warehouse storage areas, and other
spaces <= 300 sqft that are enclosed
by floor-to-ceiling height partitions.
Reference section language
C405.2.1.2 for control function in
warehouses and section C405.2.1.3
for open plan office spaces.
Complies
Does Not
Not Observable
Not Applicable
C405.2.1.
2
[EL19]1
Occupancy sensors control function in
warehouses: In warehouses, the
lighting in aisleways and open areas is
controlled with occupant sensors that
automatically reduce lighting power
by 50% or more when the areas are
unoccupied. The occupant sensors
control lighting in each aisleway
independently and do not control
lighting beyond the aisleway being
controlled by the sensor.
Complies
Does Not
Not Observable
Not Applicable
C405.2.1.
3
[EL20]1
Occupant sensor control function in
open plan office areas: Occupant
sensor controls in open office spaces
>= 300 sq.ft. have controls 1)
configured so that general lighting can
be controlled separately in control
zones with floor areas <= 600 sq.ft.
within the space, 2) automatically turn
off general lighting in all control zones
within 20 minutes after all occupants
have left the space, 3) are configured
so that general lighting power in each
control zone is reduced by >= 80% of
the full zone general lighting power
within 20 minutes of all occupants
leaving that control zone, and 4) are
configured such that any daylight
responsive control will activate space
general lighting or control zone
general lighting only when occupancy
for the same area is detected.
Complies
Does Not
Not Observable
Not Applicable
C405.2.2,
C405.2.2.
1,
C405.2.2.
2
[EL21]2
Each area not served by occupancy
sensors (per C405.2.1) have time-
switch controls and functions detailed
in sections C405.2.2.1 and C405.2.2.2.
Complies
Does Not
Not Observable
Not Applicable
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Juniper Sands 07/06/23Report date:
1814 ofPage
Section
#
& Req.ID
Rough-In Electrical Inspection Complies?Comments/Assumptions
C405.2.3,
C405.2.3.
1,
C405.2.3.
2
[EL23]2
Daylight zones provided with
individual controls that control the
lights independent of general area
lighting. See code section C405.2.3
Daylight-responsive controls for
applicable spaces, C405.2.3.1 Daylight
responsive control function and
section C405.2.3.2 Sidelit zone.
Complies
Does Not
Not Observable
Not Applicable
C405.2.4
[EL26]1
Separate lighting control devices for
specific uses installed per approved
lighting plans.
Complies
Does Not
Not Observable
Not Applicable
C405.2.4
[EL27]1
Additional interior lighting power
allowed for special functions per the
approved lighting plans and is
automatically controlled and
separated from general lighting.
Complies
Does Not
Not Observable
Not Applicable
C405.2.5
[EL28]null
Manual controls required by the
energy code are in a location with
ready access to occupants and
located where the controlled lights are
visible, or identify the area served and
their status.
Complies
Does Not
Not Observable
Not Applicable
C405.2.6
[EL30]null
Automatic lighting controls for exterior
lighting installed. Controls will be
daylight controlled, set based on
business operation time-of-day, or
reduce connected lighting > 30%.
Complies
Does Not
Not Observable
Not Applicable
C405.3
[EL6]1
Exit signs do not exceed 5 watts per
face.
Complies
Does Not
Not Observable
Not Applicable
C405.6
[EL26]2
Low-voltage dry-type distribution
electric transformers meet the
minimum efficiency requirements of
Table C405.6.
Complies
Does Not
Not Observable
Not Applicable
C405.7
[EL27]2
Electric motors meet the minimum
efficiency requirements of Tables
C405.7(1) through C405.7(4).
Efficiency verified through certification
under an approved certification
program or the equipment efficiency
ratings shall be provided by motor
manufacturer (where certification
programs do not exist).
Complies
Does Not
Not Observable
Not Applicable
C405.8.2,
C405.8.2.
1
[EL28]2
Escalators and moving walks comply
with ASME A17.1/CSA B44 and have
automatic controls configured to
reduce speed to the minimum
permitted speed in accordance with
ASME A17.1/CSA B44 or applicable
local code when not conveying
passengers.
Complies
Does Not
Not Observable
Not Applicable
C405.9
[EL29]2
Total voltage drop across the
combination of feeders and branch
circuits <= 5%.
Complies
Does Not
Not Observable
Not Applicable
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Juniper Sands 07/06/23Report date:
1815 ofPage
Section
#
& Req.ID
Insulation Inspection Complies?Comments/Assumptions
C303.1
[IN3]1
Roof insulation installed per
manufacturer’s instructions. Blown or
poured loose-fill insulation is installed
only where the roof slope is <=3 in
12.
Complies
Does Not
Not Observable
Not Applicable
C402.2.1
[IN20]1
Insulation installed on a suspended
ceiling having ceiling tiles is not being
specified for roor/ceiling assemblies.
Continuous insulation board installed
in 2 or more layers with edge joints
offset between layers.
Complies
Does Not
Not Observable
Not Applicable
C303.1
[IN10]2
Building envelope insulation is labeled
with R-value or insulation certificate
providing R-value and other relevant
data.
Complies
Does Not
Not Observable
Not Applicable
C303.2
[IN7]1
Above-grade wall insulation installed
per manufacturer’s instructions.
Complies
Does Not
Not Observable
Not Applicable
C303.2,
C402.2.4
[IN9]2
Floor insulation installed per
manufacturer’s instructions. Cavity or
structural slab insulation installed in
permanent contact with underside of
decking or structural slabs.
Complies
Does Not
Not Observable
Not Applicable
C105
[IN6]1
Installed above-grade wall insulation
type and R-value consistent with
insulation specifications reported in
plans and COMcheck reports.
Complies
Does Not
Not Observable
Not Applicable
See the Envelope Assemblies table for values.
C402.2.3
[IN8]2
Installed floor insulation type and R-
value consistent with insulation
specifications reported in plans and
COMcheck reports.
Complies
Does Not
Not Observable
Not Applicable
See the Envelope Assemblies table for values.
C402.2.6
[IN18]3
Radiant panels and associated
components, designed for heat
transfer from the panel surfaces to the
occupants or indoor space are
insulated with a minimum of R-3.5.
Complies
Does Not
Not Observable
Not Applicable
C105
[IN2]1
Installed roof insulation type and R-
value consistent with insulation
specifications reported in plans and
COMcheck reports. For some ceiling
systems, verification may need to
occur during Framing Inspection.
Complies
Does Not
Not Observable
Not Applicable
See the Envelope Assemblies table for values.
C402.5.1.
1
[IN1]1
All sources of air leakage in the
building thermal envelope are sealed,
caulked, gasketed, weather stripped
or wrapped with moisture vapor-
permeable wrapping material to
minimize air leakage.
Complies
Does Not
Not Observable
Not Applicable
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Juniper Sands 07/06/23Report date:
1816 ofPage
Section
#
& Req.ID
Final Inspection Complies?Comments/Assumptions
C303.3,
C408.2.5.
2
[FI17]3
Furnished O&M instructions for
systems and equipment to the
building owner or designated
representative.
Complies
Does Not
Not Observable
Not Applicable
C303.3,
C408.2.5.
3
[FI8]3
Furnished O&M manuals for HVAC
systems within 90 days of system
acceptance.
Complies
Does Not
Not Observable
Not Applicable
C402.5.6
[FI37]1
Weatherseals installed on all loading
dock cargo door openings and provide
direct contact along the top and sides
of vehicles parked in the doorway.
Complies
Does Not
Not Observable
Not Applicable
C402.5.8
[FI26]3
Recessed luminaires in thermal
envelope to limit infiltration and be IC
rated and labeled. Seal between
interior finish and luminaire housing.
Complies
Does Not
Not Observable
Not Applicable
C403.2.2
[FI27]3
HVAC systems and equipment
capacity does not exceed calculated
loads.
Complies
Does Not
Not Observable
Not Applicable
C403.2.4.
1
[FI47]3
Heating and cooling to each zone is
controlled by a thermostat control.
Minimum one humidity control device
per installed
humidification/dehumidification
system.
Complies
Does Not
Not Observable
Not Applicable
C403.4.1.
2
[FI38]3
Thermostatic controls have a 5 °F
deadband.
Complies
Does Not
Not Observable
Not Applicable
C403.2.4.
1.3
[FI20]3
Temperature controls have setpoint
overlap restrictions.
Complies
Does Not
Not Observable
Not Applicable
C403.2.4.
2
[FI39]3
Each zone equipped with setback
controls using automatic time clock or
programmable control system.
Complies
Does Not
Not Observable
Not Applicable
C403.2.4.
2.1,
C403.2.4.
2.2
[FI40]3
Automatic Controls: Setback to 55°F
(heat) and 85°F (cool); 7-day clock, 2-
hour occupant override, 10-hour
backup
Complies
Does Not
Not Observable
Not Applicable
C405.4.1
[FI18]1
Interior installed lamp and fixture
lighting power is consistent with what
is shown on the approved lighting
plans, demonstrating proposed watts
are less than or equal to allowed
watts.
Complies
Does Not
Not Observable
Not Applicable
See the Interior Lighting fixture schedule for values.
C405.5.1
[FI19]1
Exterior lighting power is consistent
with what is shown on the approved
lighting plans, demonstrating
proposed watts are less than or equal
to allowed watts.
Complies
Does Not
Not Observable
Not Applicable
See the Exterior Lighting fixture schedule for values.
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Juniper Sands 07/06/23Report date:
1817 ofPage
Section
#
& Req.ID
Final Inspection Complies?Comments/Assumptions
C408.1.1
[FI57]1
Building operations and maintenance
documents will be provided to the
owner. Documents will cover
manufacturers' information,
specifications, programming
procedures and means of illustrating
to owner how building, equipment and
systems are intended to be installed,
maintained, and operated.
Complies
Does Not
Not Observable
Not Applicable
C408.2.1
[FI28]1
Commissioning plan developed by
registered design professional or
approved agency.
Complies
Does Not
Not Observable
Not Applicable
C408.2.3.
1
[FI31]1
HVAC equipment has been tested to
ensure proper operation.
Complies
Does Not
Not Observable
Not Applicable
C408.2.3.
2
[FI10]1
HVAC control systems have been
tested to ensure proper operation,
calibration and adjustment of controls.
Complies
Does Not
Not Observable
Not Applicable
C408.2.3.
3
[FI32]1
Economizers have been tested to
ensure proper operation.
Complies
Does Not
Not Observable
Not Applicable
C408.2.4
[FI29]1
Preliminary commissioning report
completed and certified by registered
design professional or approved
agency.
Complies
Does Not
Not Observable
Not Applicable
C408.2.5.
1
[FI7]3
Furnished HVAC as-built drawings
submitted within 90 days of system
acceptance.
Complies
Does Not
Not Observable
Not Applicable
C408.2.5.
1
[FI16]3
Furnished as-built drawings for
electric power systems within 90 days
of system acceptance.
Complies
Does Not
Not Observable
Not Applicable
C408.2.5.
3
[FI43]1
An air and/or hydronic system
balancing report is provided for HVAC
systems.
Complies
Does Not
Not Observable
Not Applicable
C408.2.5.
4
[FI30]1
Final commissioning report due to
building owner within 90 days of
receipt of certificate of occupancy.
Complies
Does Not
Not Observable
Not Applicable
C408.3
[FI33]1
Lighting systems have been tested to
ensure proper calibration, adjustment,
programming, and operation.
Complies
Does Not
Not Observable
Not Applicable
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title:
Data filename:
Juniper Sands 07/06/23Report date:
1818 ofPage