HomeMy WebLinkAboutAPPROVED PLANS - 23-00829 - 784 Park St - Solar PanelsAuthor Name Author Email Author Phone No.:
Alex Owens Alex.Owens@rexburg.org 208-372-2172
Description : 784 Park St - Solar Panels
Address : 784 Park St
Record Type : Solar Panels
Document Filename : Dick, Deb Site Plan (2).pdf
Comment Author Contact Information:
Corrections in the following table need to be applied before a permit can be issued
Review Report
Approved
# 23-00826
Page Reference Annotation
Type
Author : Department Status Page Review Comments Applicant Response Comments
Pg 1 Stamp Alex Owens : Electrical Open 1 Approved - Electrical Inspector
Pg 3 Stamp Alex Owens : Electrical Open 3 Approved - Electrical Inspector
Pg 3 Free Text Alex Owens : Electrical Open 3 Call for rough inspection once panels are on site and prior to
installation on roof.
Solar Panels
Approval of plans does not constitute approval of variance from code
Powered by TCPDF (www.tcpdf.org)
UtahEnergySavers.com
ESSolar.net
Layton, UT 801-614-0606
DICK RESIDENCE
784 PARK ST
REXBURG, IDAHO 83440
Sheet 1 of 7
PLANT LOCATION
Scale
NTS
PLANT LOCATION:
DICK RESIDENCE
784 PARK ST
REXBURG, IDAHO 83440
SOLAR EDGE SE7600H-US INVERTER
25 HANWHA Q.PEAK BLK-G4.1 295
PV PANELS
SOLAR EDGE SE7600HUB-US INVERTER
31 SOLARIA POWERXT-400R-PM PANELS
SOLAR EDGE SE5000H-US INVERTER
17 LG LG335N1C-A5 335 PV PANELS
(2) SOLAR EDGE SE7600H-US INVERTER
47 HANWHA Q.PEAK DUO BLK-G5 310
PV PANELS
SOLAR EDGE SE7600H-US INVERTER
25 JA JAM60S03-310/PR PV PANELS
SOLAR EDGE SE3800H-US INVERTER
14 PANASONIC VBHN320KA03 320
PV PANELS
SOLAR EDGE SE7600HUB-US INVERTER
25 S ENERGY SL40-60MBI-360V PANELS
REVISION 1:
ADDITION TO EXISTING SOLAR SYSTEM
PLAN BY: BRYCE PETERSON
SOLAR EDGE SE7600H-US INVERTER
25 VIKRAM SOMERA VSMHBB.60.365
TEXT
2 REC400AA PURE-R
UtahEnergySavers.com
ESSolar.net
Layton, UT 801-614-0606
INSTALL SITE
Scale
NTSLIMITS OF CONSTRUCTION
SOLADECK
JUNCTION
BOX (S)
EXISTING SOLAR EDGE SE3000H-US
INVERTER (LOCATED NEXT TO
SERVICE)
EXISTING 200A SERVICE
ENTRANCE PANELBOARD
Sheet 2 of 7
GENERAL NOTES:
ALL CONSTRUCTION / INSTALLATION SHALL COMPLY WITH:
2017 NATIONAL ELECTRICAL CODE (NEC)
2018 INTERNATIONAL FIRE CODE (IFC)
2018 INTERNATIONAL BUILDING CODE (IBC)
2018 INTERNATIONAL RESIDENTIAL CODE (IRC)
ALL DIMENSIONS SHOWN ARE APPROXIMATE
UTILITY HAS 24-HR UNRESTRICTED ACCESS TO ALL PV SYSTEM
COMPONENTS LOCATED AT SERVICE ENTRANCE
ALL CONDUITS ON ROOF SHALL BE A MINIMUM OF ½” OFF ROOF
CONSTRUCTION LIMITS: ALL IMPROVEMENTS AND ACCESS
SHALL OCCUR WITHIN PLANT PROPERTY LINES
PHOTOVOLTAIC SYSTEM
COMBINER PANEL 100A, 120/240
VAC LOAD CENTER
DEDICATED PHOTOVOLTAIC SYSTEM AC DISCONNECT
ESS BATTERY
(LOCATED INSIDE GARAGE ON SIDEWALL)
DEDICATED BATTERY SYSTEM AC
DISCONNECT
(LOCATED IN SIGHT OF BATTERY)
EXISTING DEDICATED
BATTERY SYSTEM UTILITY
STOP DISCONNECT
(LOCATED NEXT TO SERVICE)
NEW 125A SUBPANEL
(LOCATED IN SIGHT OF BATTERY)
Portrait = 4 panels per 14’ rail
Landscape = 2 panels per 14” rail
Portrait = 1 rail to 2 panels (360W/400W = 2 rails to 3 panels)
Landscape = 1 rail to 1 panel
Splices = 2 for every consecutive 4 panels portrait (3 panels for
360W/400W)/ 2 panels landscape
End Clamps = 2 on every end
Mid Clamps = 2 on every joint between panel
EXISTING 200A INTERIOR
LOADS PANEL LOCATED IN
BASEMENT
DEDICATED PHOTOVOLTAIC
SYSTEM AC DISCONNECT
(LOCATED NEXT TO SERVICE)
SOLADECK JUNCTION BOX (S)
ONE PER ARRAY
APPROX. 40' DC RUN
(IN ATTIC WHERE
AVAILABLE)
SOLADECK JUNCTION BOX
(S) ONE PER ARRAY
B
DEDICATED PHOTOVOLTAIC
SYSTEM AC DISCONNECT
(LOCATED NEXT TO SERVICE)
PV METER SOCKET
(LOCATED NEXT TO SERVICE)
ESS BATTERY
(LOCATED INSIDE GARAGE ON SIDEWALL IN
THE FRONT 10 FEET OF GARAGE)
TRENCH
TRENCH
EXISTING SOLAR ARRAY
(SHOWN IN BLUE)
DICK RESIDENCE
784 PARK ST
REXBURG, IDAHO 83440
NEW SOLAR MODULES
(SHOWN IN BLACK)
0.8 KW DC
PHOTOVOLTAIC SYSTEM
SOLAR BOM
NEW SOLADECK JUNCTION BOX (SOLTECTION RJ-1) _1_ QTY
NEW JUNCTION BOX (SOLTECTION RU-2LP) _1_ QTY
RAIL (SNAPNRACK SERIES 100)= _2_ (14 FT LENGTH) QTY
SPLICES (SNAPNRACK SERIES 100)= _0_ QTY
MID CLAMP (SNAPNRACK SERIES 100) = 2 QTY
END CLAMP (SNAPNRACK SERIES 100) = 4 QTY
STANDOFFS FEET AND LAGS (SNAPNRACK SERIES 100) = 4 QTY EACH
2 REC400AA PURE-R
UtahEnergySavers.com
ESSolar.net
Layton, UT 801-614-0606
Scale
NTS Sheet 3 of 7
4 #10 THWN-2 CU PV WIRE1 #10 THWN-2 CU GND3/4" EMT CONDUITSOLADECK JUNCTION BOX TRANSITION BOX
AC ONE LINE
DIAGRAM
20A/2P
EXISTNG 3.0KW
SOLAR INVERTER
40A/2P
NEW 125A BACKUP LOADS
SUPPANEL (LOCATED IN INTERIOR)
NO SINGLE LOAD LARGER THAN 36A
OR 8.64KVA (NEC 710.15)
(2)#8 AWG CU
(1)#8 AWG NEUTRAL CU
(1)#8 AWG EGC CU
¾” EMT MIN. W/ THWN-2 OUTDOOR / NM
CABLE INDOOR
125A SUBPANEL
CT
ETHERNET LINE TO HOME
NETWORK
A*
D*
E*
A*-EXISTING MAIN SERVICE (METER HEAD ONLY)
B*-EXISTING 30A/2P DISCONNECT (EATON DG221URB)
C*-SONNEN CORE (SONNENCORE10KWH)
D*-NEW SUBPANEL (EATON BR816L125RP)
E*-NEW SUBPANEL (EATON BR816L125RP)
F*-60A/2P DISCONNECT (EATON DG222URB)
G*-SOLAREDGE 3000W HD WAVE INVERTER (SE3000H-US)
H*-HEAT/SMOKE DETECTOR (BRK SA520B) LOCATED IN CEILING ABOVE ESS
I*-EXISTING SUBPANEL (SQUARE D 200A)
G*
EXISTING INTERIOR SUB PANEL
(LOCATED IN INTERIOR)
40A/2P
EXISTING
LOADS
200A SUBPANEL
I*
60A/2P VISIBLY OPEN
DISCONNECT (LOCATED
WITHIN 3’ OF SERVICE)
F*
(2)#10 AWG CU
(1)#10 AWG NEUTRAL CU
(1)#10 AWG EGC CU
¾” EMT MIN. W/ THWN-2 OUTDOOR / NM
CABLE INDOOR
DC CIRCUITS CONTINUE
TO EXISTING ARRAY
(2)#8 AWG CU
(1)#8 AWG NEUTRAL CU
(1)#8 AWG EGC CU
¾” EMT MIN. W/ THWN-2 OUTDOOR / NM
CABLE INDOOR
(6)#14 AWG CU
¾” EMT MIN. W/ THWN-2 OUTDOOR / NM
CABLE INDOOR
(2)#10 AWG CU
(1)#10 AWG NEUTRAL CU
(1)#10 AWG EGC CU
¾” EMT MIN. W/ THWN-2 OUTDOOR / NM
CABLE INDOOR
(2)#8 AWG CU
(1)#8 AWG NEUTRAL CU
(1)#8 AWG EGC CU
¾” EMT MIN. W/ THWN-2 OUTDOOR / NM
CABLE INDOOR
NEW
INTERCONNECTED
HEAT OR SMOKE
DETECTOR
H*
(2)3/0 AWG CU / 4/0 AWG AL
(1)3/0 AWG NEUTRAL CU / 4/0 AWG AL
(1)#6 AWG EGC CU / #4 AWG AL
2” EMT MIN. W/ THWN-2 /SER CABLE
EXTERIOR LOCATED
LESS THAN 3 FT FROM
MAIN
10 KWH BATTERY
SONNEN CORE ESS
4.8 KW
INVERTER
40A AUTOMATIC
TRANSFER SWITCH
LOCKABLE
DISCONNECT
C*
EXISTING
LOCKABLE 30A/2P
VISIBLY OPEN
DISCONNECT B*
C*-200A SUB PANEL (EATON BRP08B200RF)
C*-200A SUB PANEL (EATON BRP12L200R)
EXTERIOR SUBPANEL SIZES:
BRP08B200RF = 8 BREAKER SLOTS
BRP12L200R = 12 BREAKER SLOTS
B*-NEW 125A SUBPANEL (EATON BR816L125RP)
*WE WILL BE ADDING ONE 125A BREAKER TO THE MAIN SERVICE PANEL TO PROTECT THE EXISTING HOUSE FEEDER WIRES IN COMPLIANCE WITH NEC 705.12(B)(2)(1)(B)PV METERB*- PV METER BOX
E*-30A/2P DISCONNECT (EATON DG221URB)
200A/2P
40A/2P
OTHER
LOADS
(2)#6 AWG CU
(1)#6 AWG NEUTRAL CU
(1)#6 AWG EGC CU
¾” EMT MIN. W/ THWN-2 OUTDOOR / NM
CABLE INDOOR
(2)#8 AWG CU
(1)#8 AWG NEUTRAL CU
(1)#8 AWG EGC CU
¾” EMT MIN. W/ THWN-2 OUTDOOR / NM
CABLE INDOOR
(2)#10 AWG CU
(1)#10 AWG NEUTRAL CU
(1)#10 AWG EGC CU
¾” EMT MIN. W/ THWN-2 OUTDOOR / NM
CABLE INDOOR
*WE WILL BE ADDING ONE 125A BREAKER
TO THE MAIN SERVICE PANEL TO PROTECT
THE EXISTING HOUSE FEEDER WIRES IN
COMPLIANCE WITH NEC 705.12(B)(2)(1)(B)
IN GARAGE
(UNLESS OTHERWISE SPECIFIED)
(2)#14 AWG CU (24V EMERGENCY STOP
CONTACT)
¾” EMT MIN. W/ THWN-2 OUTDOOR / NM
CABLE INDOOR
(2)3/0 AWG CU / 4/0 AWG AL
(1)3/0 AWG NEUTRAL CU / 4/0 AWG AL
(1)#6 AWG EGC CU / #4 AWG AL
2” EMT MIN. W/ THWN-2 /SER CABLE
(2)1/0 AWG CU / 2/0 AWG AL
(1)1/0 AWG NEUTRAL CU / 2/0 AWG AL
(1)#6 AWG EGC CU / # 4 AWG AL
1 ½ ” EMT MIN. W/ THWN-2 OUTDOOR /
SER CABLE INDOOR
(2)#1 AWG CU / 1/0 AWG AL
(1)#1 AWG NEUTRAL CU / 1/0 AWG AL
(1)#6 AWG EGC CU / #4 AWG AL
1 ½ ” EMT MIN. W/ THWN-2 OUTDOOR /
SER CABLE INDOOR
(2)#2 AWG CU / #2 AWG AL
(1)#2 AWG NEUTRAL CU / #2 AWG AL
(1)#8 AWG EGC CU / #6 AWG AL
1 ½ ” EMT MIN. W/ THWN-2 OUTDOOR /
SER CABLE INDOOR
OGDEN WIRE SIZES NEED TO BE
CHANGED TO:
(2)#8 AWG CU
(1)#8 AWG NEUTRAL CU
(1)#10 AWG EGC CU
¾” EMT MIN. W/ THWN-2 OUTDOOR / NM
CABLE INDOOR
(2)#14 AWG CU (24V EMERGENCY STOP
CONTACT)
¾” EMT MIN. W/ THWN-2 OUTDOOR / NM
CABLE INDOOR OR SPEAKER WIRE OR
SPRINKLER WIRE
200A MAIN
DICK RESIDENCE
784 PARK ST
REXBURG, IDAHO 83440
0.8 KW DC
PHOTOVOLTAIC SYSTEM
2 REC400AA PURE-R
Call for rough inspection once
panels are on site and prior to
installation on roof.
UtahEnergySavers.com
ESSolar.net
Layton, UT 801-614-0606
SIGNAGE
Scale
NTS
1 DUAL INPUT SOURCE
SECOND SOURCE IS SOLAR PV SYSTEM
ALL SIGNAGE MUST BE PERMANENTLY ATTACHED AND NOT HAND-WRITTEN. NEC 110.21(B)
SIGN LOCATED AT POINT OF INTERCONNECTION.
NEC 690.56(B) AND 705.10 AND 712.10
2 WARNING:SOLAR POWER SOURCE
OUTPUT CONNECTION,
DO NOT RELOCATE
THIS OVERCURRENT DEVICE
SIGN LOCATED NEXT TO SOLAR BACKFEED BREAKERS AT SERVICE PANEL.
IF BREAKER FEED AND UTILIZING THE 120% RULE NEC 705.12(B)(2)(3)(b)
3 RAPID SHUTDOWN SWITCH
FOR SOLAR PV SYSTEM
SIGN LOCATED NEXT TO THE SOLAR AC OR DC DISCONNECT THAT
ACTIVATES RAPID SHUTDOWN. NEC 690.56 (C) (3) OR NEXT TO MAIN
SERVICE DISCONNECT OR NEXT TO A RSD RELAY SIGNAL BUTTON
THE MARKINGS SHALL BE REFLECTIVE WHITE ON RED BACKGROUND
5 PHOTOVOLTAIC POWER SOURCE
THIS SIGN IS LOCATED ON THE OUTSIDE OF ANY CONDUITS, ENCLOSURES, OR MC CABLE THAT CONTAINS DC CIRCUITS.
The markings shall be reflective and be provided at every enclosure, every 10’ along conduit or MC cable, and at each side of where the
conduit or cable passes through a wall, floor, or any other partition. NEC 690.31(G)(3-4) and IFC 605.11.1.2
8
4 PHOTOVOLTAIC ARRAY
DC DISCONNECT SWITCH
MAX SYSTEM VOLTAGE= 480 VDC
MAX CIRCUIT CURRENT= 15 ADC
MAX CURRENT FOR POWER
OPTIMISERS= 15 ADC
THIS SIGN IS LOCATED ON THE OUTSIDE OF EACH DC DISCONNECT.
NEC 690.53 and 690.13(B)
7
PV SYSTEM BACKFEEDING
THROUGH THIS PANEL
AC OUTPUT CURRENT= 32 AAC
AC VOLTAGE=240 VAC
THIS SIGN IS LOCATED AT THE BACKFEED PANEL BOARD
NEC 690.54
Sheet 4 of 7
11PHOTOVOLTAIC SYSTEM
DEDICATED KWH METER
THIS SIGN IS LOCATED AT THE DEDICATED
KWH METER
6
NOTICE:
PV SYSTEM COMBINER PANEL
DO NOT ADD LOADS TO THIS PANEL
THIS SIGN IS LOCATED AT THE COMBINER PANEL
PHOTOVOLTAIC SYSTEM
AC DISCONNECT
THIS SIGN IS LOCATED AT THE AC PV SYSTEM DISCONNECT
690.13 (B)
THIS SIGN IS LOCATED ON OR WITHIN 3’ FEET OF THE
SERVICE METER PANELBOARD AND ON ANY AC DISCONNECT
SWITCH ON THE OUTSIDE OF THE BUILDINGS NEC
690.56(C)(1) / IFC 1204.5.1
9
SE3000H-US 12.5
SE3800H-US 16
SE5000H-US 21
SE6000H-US 25
SE7600H-US 32
SE10000H-US 42
SE11400A-US 47.5
Ansi z535.4 color
specific
ENERGY STORAGE SYSTEM
DISCONNECT
NOMINAL ESS AC VOLTAGE=_240_VAC
MAXIMUM ESS DC VOLTAGE=_204_VDC
SIGN LOCATED AT ENERGY STORAGE SYSTEM DISCONNECTS
NEC 706.15(C)
10
9
CAUTION: MULTIPLE SOURCES OF POWER
POWER TO THIS SERVICE IS ALSO SUPPLIED FROM A PV SYSTEM
CONNECTED TO THE AC SERVICE PANEL.
LITHIUM BATTERY IS LOCATED IN GARAGE (SIDEWALL)
INVERTER IS LOCATED NEXT TO SERVICE
BATTERY LIGHTS WILL BE OFF WHEN EMERGENCY STOP ACTIVE
THIS DIRECTORY LOCATED AT POINTS OF INTERCONNECTION.
NEC 690.56(B) AND 705.10 AND 706.21 AND 710.10 AND 712.10
ALSO PER UTILITY REQUIREMENTS
DICK RESIDENCE
784 PARK ST
REXBURG, IDAHO 83440
0.8 KW DC
PHOTOVOLTAIC SYSTEM
2 REC400AA PURE-R
UtahEnergySavers.com
ESSolar.net
Layton, UT 801-614-0606
PLACARDS
Scale
NTS
ALL SIGNAGE MUST BE PERMANENTLY ATTACHED AND NOT HAND-WRITTEN. NEC 110.21(B)
Sheet 5 of 7
11
PARALLEL
GENERATION ON
SITE
THIS PLACARD IS LOCATED NEXT TO METER SOCKET. 2”X4”
ENGRAVED METAL OR RED AND WHITE HARD PLASTIC ⅜” OR LARGER
LETTERS
MANUAL
DISCONNECT
FOR BATTERY
THIS PLACARD IS LOCATED AT THE AC ESS SYSTEM
DISCONNECT. 2”X4” ENGRAVED METAL OR RED AND WHITE
HARD PLASTIC ⅜” OR LARGER LETTERS
12
N
MANUAL
DISCONNECT
FOR PARALLEL
GENERATION
THIS PLACARD IS LOCATED AT THE AC PV SYSTEM
DISCONNECT. 2”X4” ENGRAVED METAL OR RED AND WHITE
HARD PLASTIC ⅜” OR LARGER LETTERS
13
MANUAL
DISCONNECT
FOR PARALLEL
GENERATION
AND BATTERY
THIS PLACARD IS LOCATED AT THE AC ESS SYSTEM
DISCONNECT. 2”X4” ENGRAVED METAL OR RED AND WHITE
HARD PLASTIC ⅜” OR LARGER LETTERS
12
WARNING:
MULTIPLE SOURCES OF POWER. A
PV SYSTEM IS PRESENT.
DISCONNECT ALL POWER SOURCES
BEFORE SERVICING.
FOR ST GEORGE POWER
DICK RESIDENCE
784 PARK ST
REXBURG, IDAHO 83440
0.8 KW DC
PHOTOVOLTAIC SYSTEM
2 REC400AA PURE-R
ARRAY SELF WEIGHT
2 REC 400W PANELS 20.5 kg = 45 LBS/PANEL + SNAP-N-RACK
RACKING MOUNTING HARDWARE:2 X 41.888 = 84
A = L x W (PANEL): 71.7” X 40 = 19.91 SQ FT X 2 = 40
TOTAL SQ FT OF PLANE VIEW ROOF AREA = 2225
PERCENTAGE OF ROOF AREA COVERED IN SOLAR PANELS = 1.8%
(IFC 1204.2.1.2)
ARRAY: 84 LBS / 40 SQ FT = 2.3 PSF
MAX WEIGHT PER ANCHOR = 44.6 LBS (FOR 4’0” SPANS)
PULL OUT STRENGTH
CONNECTOR 5/16 LAG BOLT 4 STANDOFFS (4 LAGS) 4 x 3” EMBED x
210 LBS = 2520 LBS
WEATHER LOADING
GROUND SNOW: 50PSF
WIND SPEED: 160MPH
EXPOSURE CATEGORY: B
LIMITS OF CONSTRUCTION
UtahEnergySavers.com
ESSolar.net
Layton, UT 801-614-0606
MOUNTING AND
WEIGHT LOAD
Scale
NTS
MEETS OR EXCEEDS 2021 IBC IRC CONSTRUCTION STANDARDS
CASE 1 Load Calculations 2X4 construction, 24" on center trusses
ROOF LOAD BEARING
______ LBS / ___ STANDOFFS = _____LBS
TOTAL WEIGHT = PANELS + HARDWARE
1412.5 LBS
1412.5 LBS / 460.75 SQ FT=
3.065 PSF
DEDICATED PHOTOVOLTAIC
SYSTEM AC DISCONNECT
Sheet 6 of 7
TIMES
PANELS
BY 630
ALL ROOF
PENETRATIONS MUST
BE PROPERLY
FLASHED. IRC
M2302.2.2.
THIS INSTALLATION SHALL COMPLY WITH THE REQUIREMENTS
SPECIFIED IN SECTION 1205 OF THE 2021 INTERNATIONAL FIRE CODE.
ROOF RACKING SUPPORT SPACING NOT TO EXCEED 4’ SPACING. ALL
SUPPORTS MUST BE STAGGERED FROM ONE ROW OF RACKING TO
THE NEXT SO NOT ALL SUPPORTS ARE BEARING ON THE SAME
TRUSSES
ALL WIRING MUST BE SUPPORTED BY DEVICES OR MECHANICAL MEANS
DESIGNED AND LISTED FOR SUCH USE AND WIRING MUST BE
PERMANENTLY AND COMPLETELY HELD OFF THE ROOF SURFACE.
36 INCH FIRE
DEPARTMENT
SETBACK 36” PATHWAYS TO RIDGE
(SHOWN IN PURPLE)
WE WILL BE OBSERVING IFC 1204.2 EXCEPTION 1TO BE USED WHEN USING A BARN OR NON INHABITED SPACE FOR ROOF TOP INSTALL
THIS INSTALLATION SHALL COMPLY WITH THE REQUIREMENTS
SPECIFIED IN THE UTAH AMENDED SECTIONS OF THE 2021 IRC THAT PERTAIN
TO ENERGY STORAGE SYSTEMS INCLUDING SHEET ROCK AND AN
INTERCONNECTED FIRE ALARM IN THE ROOM OF THE ENERGY STORAGE
SYSTEM
FOR GRANTSVILLE:
WEATHER LOADING
GROUND SNOW: 30PSF
WIND SPEED: 115MPH
EXPOSURE CATEGORY: C
FOR BINGHAM COUNTY
IDAHO:
WEATHER LOADING
GROUND SNOW: 42PSF
WIND SPEED: 115MPH
EXPOSURE CATEGORY: C
0.8 KW DC
PHOTOVOLTAIC SYSTEM
2 REC400AA PURE-R
UtahEnergySavers.com
ESSolar.net
Layton, UT 801-614-0606
Scale
NTS
SIGNAGE LOCATION
Sheet 7 of 7
*5
*5
*5
*5
*5
*5
*5
*4
*1,*9
EXISTING 200A
MAIN SERVICE PANEL
EXISTING SOLAREDGE
SE3000H-US
INVERTER
TRANSITION BOX SOLADECK
JUNCTION BOXES
IN ATTIC
(EXTERIOR *7)
(NEXT TO
BREAKER
*2,*6)
*3
*11,
*1,*8,*13
* NOT REFLECTIVE OF
ACTUAL EQUIPMENT
LOCATION
NEW
SUBPANEL
AC
DISCONNECT SONNEN ESS
IN GARAGE
*3,*8, *13
TO EXISTING INTERIOR LOADS PANEL
*10
*1, *2, *6,
*3, *10, *12
EXISTING
LOCKABLE
VISIBLY OPEN
DISCONNECT
* FOR SIGNAGE AND
PLACARDS SEE PAGES 7 AND
8
*ONLY APPLICABLE STICKER
WILL BE SHOWN ON PAGES 7
AND 8 AND INSTALLED ON
SITE.
*2, *6,
DICK RESIDENCE
784 PARK ST
REXBURG, IDAHO 83440
0.8 KW DC
PHOTOVOLTAIC SYSTEM
2 REC400AA PURE-R