Corrections in the following table need to be applied before a permit can be issued
Review Report
Approved
# 23-00463
Page Reference Annotation
Type
Author : Department Status Page Review Comments Applicant Response Comments
1 Stamp Cody Jones : Building Open 1 Approved - Building Inspector
Commercial - Remodel
Approval of plans does not constitute approval of variance from code
Powered by TCPDF (www.tcpdf.org)
Cody Jones
City of Rexburg
35 North 1st East
Rexburg, ID 83440
Subject: Bodifi – Remodel Permit Review Comments
Dear Cody,
Thank you for taking the time to visit with me regarding the review comments of the
subject project. We offer the following response to the review comments per our
phone discussion:
•ADA shower dimensions – the intended ADA shower to be installed is the
transfer style that is min. 36”x36” to meet ADA requirements
•ADA Shower stalls - Transfer units meet ICC A117.1 requirements
•Tempered Glass - Contractor to provide tempered glass at glass partitions
•Fixture count - Water closet, urinal and lavatory fixture count will remain the
same. Shower count decreases by 2 in men and women toilet rooms.
However, the ICC does not specify a min. shower stall count per occupant load
like it does for other plumbing fixtures.
•Electrical - Electrical work is extremely limited in scope and does not merit a
full electrical drawing. Electrical contractor to contact the electrical inspector
and coordinate inspections to ensure code compliance.
Please don't hesitate to contact studio i with any further questions or comments
regarding this project.