HomeMy WebLinkAboutFIRE ALARM FINAL - 22-00796 - Madison Station Apartments - Bldg 2FIRE ALARM AND EMERGENCY COMMUNICATION SYSTEM RECORD OF COMPLETION To be completed by the system installation contractor at the time ofsystent acceptance and approval. It shall be permitted to modify this form as needed to provide a more complete andllor clear record Insert NIA in all amused lines. Attach additional sheets, data, or calculations as necessary to provide a complete record 1. PROPERTY INFORMATION Name of property: Madison station building 2 Address: 577 trejo Rexburg Idaho Description of property: Apartment Building Occupancytype: GROUP Name of property representative: Aaron Oconner Address: Phone: Fax: E-mail: Authority having jurisdiction over this property: Rexburg FIRE MARSHAL Phone: Fax: E-mail: 2. INSTALLATION, SERVICE, AND TESTING CONTRACTOR INFORMATION Installation contractor tot this equipment: 4Sight Security, L.L.C. Address: 6944 Big Bend, Idaho Falls, ID 83406 License or certificationmmmber: Contractor.#RCE-37051;ID ELE-SC-021298 Phone: 208403-1434 Fax: E-mail: Trevor(a)4siehtsecuritv.ore Service organization for this equipment: 4Sight Security, L.L.C. Address: 6944 Big Bend, Idaho Falls, ID 83406 License or certification number: Contractor: # RCE-37051; ID ELE-SC-021298 Phone: 208-403-1434 Fax: E-mail: A contract for test and inspection in accordance with NFPA standards is in effect as of Contracted testing company: 4Sight Security, L.L.C. Address: 6944 Big Bend, Idaho Falls, ID 83406 Phone: 208-403-1434 Fax: E-mail: Contract expires: AUTO- Contract number: N/A Frequency of routine inspections: ANNUAL RENEW 3. DESCRIPTION OF SYSTEM OR SERVICE Fire alarm system (nonvoice) Fire alarm with in -building fire emergency voice alarm communication system (EVACS) Mass notification system (MNS) Combination system, with the following components: Fire alarm EVACS MNS Two-way, in -building, emergency communication system NFPA 72, Fig. 10.18.2.1.1 (p. 1 of 12) Copyright 0 2009 National Fire Protection Association. This form may be Copied for individual use other than for resale. It may not be copied for commemial sale or distribution. other (specify): 3. DESCRIPTION OF SYSTEM OR SERVICE (continued) NFPA 72 edition: 2017 3.1 Control Unit Manufacturer: Napco 3.2 Mass Notification System MNS 3.2.1 System Type: In -building MNS—combination In -building MNS—stand-alone Other (specify): _. Additional description of system(s): Model number: Firelink This system does not incorporate an Wide -area MNS Distributed recipient MNS 3.2.2 System Features: Combination fire alarm/MNS MNS autonomous control unit Wide -area MNS to regional national alerting interface Local operating. console (LOC) Direct recipient MNS (DRMNS) Wide -area MNS to DRMNS interface Wide -area MNS to high -power speaker array (HPSA) interface In -building MNS to wide -area MNS interface Other (specify): - 3.3System Documentation An owner's manual, a copy of the manufacturer's instructions, a written sequence of operation, and a copy of the numbered record drawings are stored on site. Location: FACP 3.4System Software This system does not have alterable site -specific software. Operating system (executive) software revision level: _ Site -specific software revision date: Revision completed by: Trevor BLACKBURN A copy of the site -specific software is stored on site. Location: 3.5Off-Premises Signal Transmission transmission. Name of organization receiving alarm signals with phone numbers: Alarm: AVANT GUARD MONITORING Supervisory: AVANT GUARD MONITORING Trouble: AVANT GUARD MONITORING Entity to which alarms are re -transmitted: Idaho Falls Fire Method of re- DIGITAL VIA Starlink Radio transmission: This system does not have off -premises Phone: 877-206-9141 Phone: 877-206-9141 Phone: 877-206-9141 Phone: If Chapter 26, specify the means of transmission from the protected premises to the supervising station: If Chapter 27, specify the type of auxiliary alarm system: Local energy Shunt Wired Wheless NFPA 72, Fig. 10.18:2.1.1 (p. 2 of 12) Copyright 0 MG9 National Pile Protection Association. r1s form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution. 4. CIRCUITS AND PATHWAYS 4.1 Signaling Line Pathways 4.1.1 Pathways Class Designations and Survivability Pathways class: N/A Survivability level: _ Quantity: (See NFPA 72, Sections 12.3 and 12.4) 4.1.2 Pathways Utilizing Two or More Media Quantity: 0 Description: N/A 4.1.3 Device Power Pathways No separate power pathways from the signaling line pathway Power pathways are separate but of the same pathway classification as the signaling line pathway Power pathways are separate and different classification from the signaling line pathway 4.1.4 Isolation Modules Quantity: 0 4.2AIarm Initiating Device Pathways 4.2.1 Pathways Class Designations and Survivability Pathways class: C Survivability level: 1 Quantity: 1 (See NFPA 72, Sections 12.3 and 12.4) 4.2.2 Pathways Utilizing Two or More Media Quantity: 1 Description: ALARM INITIATING AND NAGS RUN TOGETHER 4.2.3 Device Power Pathways No separate power pathways from the initiating device pathway Power pathways are separate but of the same pathway classification as the initiating device pathway Power pathways are separate and different classification from the initiating device pathway 4.3 Non -Voice Audible System Pathways 4.3.1 Pathways Class Designations and Survivability Pathways class: B _ Survivability level: 1 Quantity: 8 (See NFPA 72, Sections 12.3 and 12:.4) 43.2 Pathways Utilizing Two or More Media Quantity: 8 Description: ALARM INITIATING AND NAGS RUN TOGETHER 4.3.3 Appliance Power Pathways No separate power pathways from the notification appliance pathway Power pathways are separate but of the same pathway classification as the notification appliance pathway Power pathways are separate and different classification from the notification appliance pathway NFPA 72, Fig. 10.18.2.1.1 (p. 3 of 12) copyright 02009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution. 5. ALARM INITIATING DEVICES 5.1 Manual Initiating Devices 5.1.1 Manual Fire Alarm Boxes Type and number of devices: Addressable: 1 Other (specify): 5.1.2 Other Alarm Boxes Description: _ Type and number of devices: Addressable: Other (specify): _ 5.2 Automatic Initiating Devices This system does not have manual fire alarm boxes. Conventional: Coded: Transmitter: This system does not have other alarm boxes. Conventional: Coded: Transmitter: 5.2.1 Smoke Detectors This system does not have smoke detectors. Type and number of devices: Addressable: 1 Conventional: Other (specify): Type of coverage: Complete area Partial area Nonrequired partial area Other (specify): - - Typeofsmokedetectorsensingtechnology: Ionization Photoelectric Multicriteria Aspirating Beam Other (specify): 5.2.2 Duct Smoke Detectors X This system does not have alarm -causing duct smoke detectors. Type and number of devices: Addressable: Conventional: Other (specify): Type of coverage: Type of smoke detector sensing technology: Ionization Photoelectric Aspirating Beam 5.2.3 Radiant Energy (Flame) Detectors This system does not have radiant energy detectors. Type and number of devices: Addressable: _ Conventional: Other (specify): Type of coverage: 5.2.4 Gas Detectors This system does not have gas detectors. Type of detector(s): Number of devices: Addressable: Conventional: Type of coverage: _.. 5.2.5 Heat Detectors This system does not have heat detectors. Type and number of devices: Addressable: Conventional: Type of coverage: Complete area Partial area Nonrequired partial area Linear Spot Type of heat detector sensing technology: Fixed temperature Rate -of -rise Rate compensated NFPA 72, Fig. 10.18.2.1.1 (p. 4 of 12) Copyright ® 2009 Natlonal Fire Protection Association. The form may be wiped for indvidual use other than for resale. It may not be copied for commercial sale or distribution. 5. ALARM INITIATING DEVICES (continued) 5.2.6 Addressable Monitoring Modules Number of devices: 5.2.7 WaterflowAlarm Devices devices. This system does not have monitoring modules. This system does have waterflow alarm Type and number of devices: Addressable: 1 Conventional: Coded: Transmitter: 6.2.8 Alarm Verification This system does have incorporate alarm verification. Number of devices subject to alarm verification: 1 _ 51.9 Presignal Number of devices subject to presignal: Describe presignal functions: 5.2.10 Positive Alarm Sequence (PAS) Describe PAS: 5.2.11 Other Initiating Devices Describe: 6. SUPERVISORY SIGNAL -INITIATING DEVICES Alarm verification set for seconds This system does not incorporate pre -signal. This system does not incorporate PAS. This system does not have other initiating devices. 6.1 Sprinkler System Supervisory Devices This system does not have sprinkler supervisory devices. Type and number of devices: Addressable: 2 Conventional: Coded: Transmitter: Other (specify): _ fit Fire Pump Description and Supervisory Devices This system does not have a fire pump. Type fire pump: Electric pump Engine Type and number of devices: Addressable: Conventional: Coded: Transmitter: Other (specify): __ ____ 6.2.1 Fire Pump Functions Supervised Power Running Phase reversal Selector switch not in auto Engine or control panel trouble Low fuel Other (specify): 6.3 Duct Smoke Detectors (DSOs) This system does not have DSDs causing supervisory signals. Type and number of devices: Addressable: 0 Conventional: Other (specify): Type of coverage: Type of smoke detector sensing technology: Ionization Photoelectric Aspirating Beam 6A Other Supervisory Devices This system does not have other supervisory devices. Describe: _ NFPA 72, Fig. 10.18.2.1.1 (p. 5 of 12) copyright 0 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distdbufion. 7. MONITORED SYSTEMS 7.1 Engine -Driven Generator This system does not have agenerator. 7.1.1 Generator Functions Supervised Engine or control panel trouble Generator running Selector switch not in auto Low fuel Other (specify): - - 72 Special Hazard Suppression Systems This system does not monitor special hazard systems. Description of special hazard system(s): 73 Other Monitoring Systems This system does not monitor other systems. Description of special hazard system(s): - 8. ANNUNCIATORS &I Location and Description of Annunciators Location 1: Location 2: Location 3: 9. ALARM NOTIFICATION APPLIANCES This system does not have annunciators. 9.1 In -Building Fire Emergency Voice Alarm Communication System This system does not have an EVACS. Number of single voice alarm channels: Number of multiple voice alarm channels: Number of speakers: Number of speaker circuits: Location of amplification and sound -processing equipment: Location of paging microphone stations: Location 1: Location 2: Location 3: 92 Nonvoice Notification Appliances Horns: 36 With visible: 48 Bells: Chimes: With visible: Visible only: Other (describe): 93 Notification Appliance Power Extender Panels Quantity: 1 Locations: Risr room With visible: This system does have power extender panels. NFPA 72, Fig. 10.18.2.1.1 (p. 6 of 12) Copyright ®2009 National Fire Protection Association This form maybe copied for individual use other than for resale. It may not be copied for commercial sale or distribution. 10. MASS NOTIFICATION CONTROLS, APPLIANCES,AND CIRCUITS This system does not have an MNS. 10.1 MNS Local Operating Consoles Location l: Location 2: Location 3: 102 High -Power Speaker Arrays Number of HPSA speaker initiation. zones: Location 1: Location 2: Location 3: 10.3 Mass Notification Devices Combination fire alarm/MNS visible appliances: MNS-only visible appliances: _. Textual signs: _ Other (describe): Supervision class: _ 10.3.1 Special Hazard Notification This system does not have special suppression predischarge notification. MNS systems DO NOT override notification appliances required to provide special suppression predischarge notification. 11. TWO-WAY EMERGENCY COMMUNICATION SYSTEMS 11.1 Telephone System Number of telephone jacks installed: Number of telephone handsets stored on site: Type of telephone system installed: Electrically powered This system does not have a two-way telephone system. Number of warden stations installed: Sound powered 112 Two -Way Radio Communications Enhancement System This system does not have a two-way radio communications enhancement system. Percentage. of area covered by two-way radio service: Criticalarem: % General building areas: Amplification component locations: Inbound signal strength: dBm Outbound signal strength: Donor antenna isolation is: dB above the signal booster gain Radio frequencies covered: Radio system monitor panel location: dBm NFPA 72, Fig. 10.18.2,1.1 (p. 7 of 12) Copyright ®2009 National Fire protection Association. This form maybe copied for Individual use other than for resale. It may not becopiecl for commercial sae or distribution. 11. TWO-WAY EMERGENCY COMMUNICATION SYSTEMS (continued) 113 Area of Refuge (Area of Rescue Assistance) Emergency Communications Systems This system does not have an area of refuge (area of rescue assistance) emergency communications system. Number of stations: Location of central control point: Days and hours when central control point is attended: Location of alternate control point: Days and hours when alternate control point is attended: HA Elevator Emergency Communications Systems This system does not have an elevator emergency communications system. Number of elevators with stations: Location of central control point: Days and hours when central control point is attended: Location of alternate control point: Days and hours when alternate control point is attended: 115 Other Two -Way Communication Systems Describe: 12. CONTROL FUNCTIONS This system activates the following control functions: Hold -open door releasing devices Smoke management HVAC shutdown F/S dampers Door unlocking Elevator recall Fuel source shutdown Extinguishing agent release Elevator shunt trip Mass notification system override of fire alarm notification appliances Other (specify): 12.1 Addressable Control Modules Number of devices: Other (specify): 13. SYSTEM POWER 13.1 Control Unit This system does not have control modules. 13.1.1 Primary Power Input voltage of control panel: 120 VAC Control panel amps: 20 Overcurrent protection: Type: BREAKER Amps: 20 Location (of primary supply panel board): Front riser room Disconnecting means location: ELECTRICAL PANEL, MARKED ON PANELS 13.1.2 Engine -Driven Generator Location of generator: Location of fuel storage: _ Type of fuel: This system does not have agenerator. NFPA 72, Fig. 10.18.2.1.1 (p. 8 of 12) Copyright 0 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution. 13. SYSTEM POWER (continued) 13.1.3 Unintermptible Power System This system does not have a UPS. Equipment powered by a UPS system: Location of UPS system: Calculated capacity of UPS batteries to drive the system components connected to it: In standby mode (hours): _ In alarm mode (minutes): 13.1.4 Batteries Location: IN PANEL Type: LEAD ACID Nominal voltage: 12 Amp/hour rating: 18 VDC X 2 Calculated capacity of batteries to drive the system: In standby mode (hours): 24 _ In alarm mode (minutes): 5 Batteries are marked with date of manufacture Battery calculations are attached 13.2 In -Building Fire Emergency Voice Alarm Communication System or Mass Notification System This system does not have an EVACS or MNS system. 13.2.1 Primary Power Input voltage of EVACS or MNS panel: Overcurrent protection: Type: Location (of primary supply panel board): Disconnecting means location: 13.2.2 Engine -Driven Generator Location of generator: Location of fuel storage: EVACS or MNS panel amps: Amps: Type of fuel: This system does not have agenerator. 13.2.3 Uninterruptible Power System Equipment powered by a UPS system: Location of UPS system.: ._ Calculated capacity of UPS batteries to drive the system components connected to it: In standby mode (hours): _ In alarm mode (minutes): 13.2.4 Batteries Location: _ _. _ Type: Calculated capacity of batteries to drive the system: In standby mode (hours): Batteries are marked with date of manufacture Nominal voltage: In alarm mode (minutes): Battery calculations are attached This system does not have a UPS. Amp/hour rating: NFPA 72, Fig. 10-18.2.1.1 (p. 9 of 12) Copyright 0 2009 National Fire Protector, Association. This form may be copied for individual use other then For resale. It may not be copied for commercial sale or distribution. 13. SYSTEM POWER (continued) 13.3 Notification Appliance Power Extender Panels This system does not have power extender panels. 13.3.1 Primary Power Input voltage of power extender panels): 120 VAC Power extender panel amps: 6 Ovemurrent protection: Type: BREAKER _ Amps: 20 Location (of primary supply panel board): Fire Front Rlsr ROOM Disconnecting means location: ELECTRICAL PANEL, MARKED ON FIRE PANELS 13.3.2 Engine -Driven Generator Location of generator: Location of fuel storage: _ Type of fuel: This system does not have a generator. 13.3.3 Uninterruptible Power System Equipment powered by a UPS system: Location of UPS system: _ Calculated capacity of UPS batteries to drive the system components connected to it: In standby mode (hours): In alarm mode (minutes): This system does not have a UPS. 13.3.4 Batteries Location: IN PANEL Type: LEAD ACID Nominal voltage: 12 Amp/hour rating: 18 VDC X 2 Calculated capacity of batteries to drive the system: In standby mode (hours): 24 _ In alarm mode (minutes): 5 Batteries arc marked with date of manul'actare Battery calculations are attached 14. RECORD OF SYSTEM INSTALLATION Fill out after all installation is complete and wiring has been checkedfor opens, shorts, groundfaults, and improper branching, but before conducting operational acceptance tests. This is a: New system Modification to an existing system Permit number: The system has been installed in accordance with the following requirements: (Note any or all that apply.) _ NFPA 72, Edition: 2019 NFPA 70, National Electrical Code, Artit le 760, Edition: 2017 Manufacturer's published instructions Other (specify): _ System deviations from referenced NFPA standards: NONE Signed: Printed name: Trevor Blackburn Date: 4Sight Security LLG Organization: Tithe: JOURNEYMAN TECHNICIAN Phone: 208-881-3510 NFPA 72, Fig. 10.18.2.1.1 (p. 10 of 12) copyright 0 2009 National Fire. Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution. 15. RECORD OF SYSTEM OPERATIONAL ACCEPTANCE TEST New system All operational features and functions of this system were tested by, or in the presence of, the signer shown below, on the dale shown below, and were found to be operating properly in accordance with the requirements for the following: Modifications to an existing system All newly modified operational features andfunctiotu ofthe system were tested bv, or in the presence of, the signer shown below, on the date shown below, and were found to be operating properly in accordance with the requirements of the following: NFPA 72, Edition: 2017 NFPA 70, National Electrical Code, Attic le 760, Edition: 2017 Manufacturer's published instructions Other (specify): - Individual device testing documentation [Inspection and Testing Form (Figure 14.6.2.4) is attached] Signed: Printed name: .Trevor Blackburn Date: 4Sight Security LLC Organization: 4Sight JOURNEYMAN TECHNICIAN phone: 208-881-3510 16. CERTIFICATIONS AND APPROVALS 16.1 System Installation Contractor: This system, as specified herein, has been installed and tested according to all NFPA standards cited herein. Signed: _ _ Printed name: Trevor Blackburn Date: 4Sight Security LLC Organization: - Title: JOURNEYMAN TECHNICIAN Phone: 208-881-3510 16.2 System Service Contractor: The undersigned has a service contract for this system in effect as of the date shown below. Signed: 4Sight Security LLC Organization: Printed name: Trevor Blackburn Title: JOURNEYMAN TECHNICIAN 16.3 Supervising Station: This system, as specified herein, will be monitored according to all NFPA standards cited herein. Signed: _ _ _ Printed time: JASON PERRON 4Sight Security LLC Organization: Title: JOURNEYMAN TECHNICIAN Date: Phone: 208-881-3510 Date: Phone: 208-881-3510 NFPA 72, Fig. 10.18.2.1.1 (p. 11 of 12) Copyright 0 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution. 16. CERTIFICATIONS AND APPROVALS (continued) 16.4 Property or Owner Representative: I accept this system as having been installed and tested to its specifications and all NFPAstandardscited herein. Ginned- ' Organization: Signed: C7llU't Organization: _GY_ Printed name: Alm Title: 0&4z,4.1 Date: wAlt y Phone: "24-sir — 7It* -) 3 30 NFPA 72, Fig. 10.18.2.1.1 (p. 12 of 12) copyright 0 2009 National Fire Protection Association. This ions may be copied for individual use other than for resets. It may not be copied for commercial sale or distribution.