HomeMy WebLinkAboutAPPROVED DRAWINGS RESPONSE - 23-00173 - Beehive Federal Credit UnionAuthor Name Author Email Author Phone No.:
Cody Jones Cody.Jones@rexburg.org 208-372-2173
Kyle Baldwin Kyle.Baldwin@rexburg.org 208-372-2164
Alex Owens Alex.Owens@rexburg.org 208-372-2172
Description : Beehive Federal Credit Union
Address : 220 E Moody Rd
Record Type : New Commercial Building
Document Filename : DRAWINGS - Beehive FCU North Rexburg Bid Set-Reviewed-Corrections-NBW Response.pdf
Comment Author Contact Information:
Corrections in the following table need to be applied before a permit can be issued
Review Report
Approved
# 23-00173
Page Reference Annotation
Type
Author : Department Status Page Review Comments Applicant Response Comments
G1.0 Stamp Cody Jones : Building Open 3 Approved - Building Inspector
G1.0 Stamp Alex Owens : Electrical Open 3 Approved - Electrical Inspector
E0.0 Free Text Alex Owens : Electrical Open 68 All electrical work to comply with 2017 NEC
E0.0 Stamp Alex Owens : Electrical Open 68 Approved - Electrical Inspector
SP1.1 Stamp Kyle Baldwin : P&Z Open 22 Approved - Planning and Zoning
New Commercial Building
Approval of plans does not constitute approval of variance from code
Powered by TCPDF (www.tcpdf.org)
N
NORTH ARROW
ROOM
.
ROOM NAME
ROOM NAME TAG
ROOM NUMBER
.
.
SECTION NUMBER
BUILDING SECTION TAG
PAGE NUMBER
SYMBOLS LEGEND
BREAK LINE
SCALE:
.
?" = 1'-0"
DETAIL
.
DETAIL NUMBER
DETAIL TITLE TAG
PAGE NUMBER
SCALE:
.
?" = 1'-0"
ELEVATION
.
INT. ELEV. TITLE TAG
SCALE: ?" = 1'-0"
TITLEMAIN TITLE TAG
SCALE:
.
?" = 1'-0"
SECTION
.
DETAIL NUMBER
PAGE NUMBER
DETAIL NUMBER
SECTION TITLE TAG
PAGE NUMBER
FINISHED FLOOR
ELEV. 100'-0"ELEVATION TAG
1 REVISION TAG
WALL TYPE TAG
D-DOOR TYPE TAG
W-WINDOW TYPE TAG
?KEYNOTE TAG
R-ROOF TYPE TAG
ROOM FINISHES
TAG
SCALE:
.
?" = 1'-0"
ELEVATION
.
EXT. ELEV. TITLE TAG
DETAIL NUMBER
PAGE NUMBER
A101
1
DETAIL NUMBER
DETAIL TAG
PAGE NUMBER
N
E F
S
WB
N1
E1
S1
W1
B1 F1
ADDITIONAL FINISH NOTES
PLAN SOUTH WALL FINISH
BASE FINISH
PLAN WEST WALL FINISH PLAN NORTH WALL FINISH
FLOOR FINISH
ADDITIONAL FINISH NOTES
PLAN EAST WALL FINISH
300 STOREFRONT TYPE TAG
9.6A-1
WALL'S FIRE RATING - HR
UNIQUE WALL TYPE
CONFIGURATION
STRUCTURAL MATERIAL
TYPE - CSI DIVISIONS
STRUCTURAL MATERIAL
WIDTH
VICINITY MAP: REXBURG, IDAHO
PROJECT LOCATION
HWY 20
HWY 33
2N
D
E
A
S
T
MOODY ROAD
DESIGN TEAM
OWNER
ARCHITECT
CIVIL ENGINEERS
LANDSCAPE ARCHITECT
STRUCTURAL ENGINEERS
MECHANICAL ENGINEERS
ELECTRICAL ENGINEERS
BEEHIVE FEDERAL CREDIT UNION
CRAIG GUMMOW - CEO
1087 ERIKSON DRIVE
REXBURG, IDAHO 83440
PHONE: (208) 656-1000
NBW ARCHITECTS P.A.
990 JOHN ADAMS PARKWAY
IDAHO FALLS, IDAHO 83401
PHONE: (208) 522-8779
FAX: (208) 522-8785
CONNECT ENGINEERING
2295 N YELLOWSTONE HWY, STE #6
IDAHO FALLS, IDAHO 83401
PHONE: (208) 881-0081
BRECKON LAND DESIGN
6661 N. GLENWOOD ST
GARDEN CITY, IDAHO 83714
PHONE: (208) 376-5153
FROST STRUCTURAL ENGINEERING
1020 E. LINCOLN RD.
IDAHO FALLS, IDAHO 83401
PHONE: (208) 227-8404
ENGINEERED SYSTEMS ASSOCIATES
1355 EAST CENTER ST.
POCATELLO, IDAHO 83201
PHONE: (208) 233-0501
FAX: (208) 233-0529
PAYNE ENGINEERING, INC.
1823 EAST CENTER ST.
POCATELLO, IDAHO 83201
PHONE: (208) 232-4439
FAX: (208) 232-1435
ABBREVIATIONS
# - NUMBER OR POUND
& - AND
A.F.F. - ABOVE FINISH FLOOR
AL - ALUMINUM
ALUM. - ALUMINUM
B.O. - BOTTOM OF
CMU - CONCRETE MASONRY UNIT
CONC. - CONCRETE
CONT. - CONTINUOUS
DEMO. - DEMOLITION OR DEMOLISH
DIA. - DIAMETER
DN - DOWN
EA. - EACH
EIFS - EXTERIOR INSULATION & FINISHING SYSTEM
ELEC. - ELECTRICAL
ELEV. - ELEVATION
EQ. - EQUAL
EQUIP. - EQUIPMENT
EXT. - EXTERIOR
F.F. - FINISH FLOOR
FRP - FIBERGLASS REINFORCED PLASTIC
GA. - GAUGE
GYP. - GYPSUM
H.M. - HOLLOW METAL
HR - HOUR
HVAC - HEATING, VENTILATING, & AIR CONDITION
I.D. - INSIDE DIAMETER
I.M.P. - INSULATED METAL PANEL
INSUL. - INSULATION
INT. - INTERIOR
MAX. - MAXIMUM
MECH. - MECHANICAL
MFR - MANUFACTURER
MIN. - MINIMUM
N.I.C. - NOT IN CONTRACT
NO. - NUMBER
O.C. - ON CENTER
O.D. - OUTSIDE DIAMETER
PLY - PLYWOOD
PLUM. - PLUMBING
PVC - POLYVINYL CHLORIDE
RCP - REFLECTED CEILING PLAN
REQ'D - REQUIRED
SIM. - SIMILAR
SPM - SINGLE PLY MEMBRANE
STOR. - STORAGE
STRUCT. - STRUCTURAL
T.O. - TOP OF
TYP. - TYPICAL
U.N.O. - UNLESS NOTED OTHERWISE
W/ - WITH
W.C. - WATER CLOSET
WD - WOOD
I D A H O
FA
L
L
S
,
O
H
A
D
I
L
E
AR
-
9
8
5
8
9
6
T
A
F
F
T
E
O
F
IN
L
GE
S
O
S
H
L
ADI
T
NO
O
R
E
NCIE
S
A
D
C
I
E
T
H
C
PROJECT NO.
DATE:
DRAWN BY:
CHECKED BY:
DRAWING NO.:
REVISIONS
PR
O
J
E
C
T
:
SH
E
E
T
T
I
T
L
E
:
04
/
0
6
/
2
0
2
3
4/
6
/
2
0
2
3
9
:
1
5
:
3
4
A
M
N
:
\
P
r
o
j
e
c
t
s
\
O
t
h
e
r
\
B
e
e
h
i
v
e
N
o
r
t
h
Re
x
b
u
r
g
B
r
a
n
c
h
-
N
e
w
B
l
d
g
-
2
2
0
2
1
\
C
A
D
\
D
r
a
w
i
n
g
s
\
B
e
e
h
iv
e
F
C
U
N
o
r
t
h
R
e
x
b
u
r
g
v
_
2
3
.
r
v
t
G1.0
22021
BE
E
H
I
V
E
F
C
U
-
N
O
R
T
H
R
E
X
B
U
R
G
CO
R
N
E
R
O
F
2
N
D
E
A
S
T
A
N
D
M
O
O
D
Y
R
D
.
GE
N
E
R
A
L
I
N
F
O
R
M
A
T
I
O
N
APRIL 2023
NE
W
B
U
I
L
D
I
N
G
F
O
R
:
RE
X
B
U
R
G
,
I
D
A
H
O
8
3
4
4
0
NEW BUILDING FOR:
BEEHIVE FCU - NORTH REXBURG
CORNER OF 2ND EAST AND MOODY RD.
REXBURG, IDAHO 83440
CJR
GLN
DRAWING INDEX
GENERAL
G1.0 GENERAL INFORMATION
G1.1 CODE ANALYSIS
G1.2 ANSI STANDARDS
CIVIL
C1.00 COVER
C2.00 NOTES
C3.00 REFERENCE SHEET
C4.00 EXISTING CONDITIONS
C5.00 GENERAL LAYOUT
C6.00 UTILITY LAYOUT
C7.00 GRADING
C8.00 DETAILS
C9.00 DETAILS 2
C10.0 STORMTECH DETAILS
C11.0 EROSION CONTROL
LANDSCAPE
L1.1 LANDSCAPE PLAN
L1.5 LANDSCAPE DETAILS
L2.1 IRRIGATION PLAN
L2.5 IRRIGATION DETAILS
L2.6 IRRIGATION DETAILS
SITE DESIGN
SP1.1 SITE PLAN - HORIZONTAL CONTROL
SP2.1 SITE DETAILS
SP2.2 SITE DETAILS
SP2.3 SITE DETAILS
ARCHITECTURAL
A1.0 WALL AND ROOF TYPES
A1.1 DIMENSION PLAN
A1.2 ANNOTATION PLAN
A1.3 REFLECTED CEILING PLAN
A1.4 SIGNAGE, FLOOR FINISHED, AND DETAILS
A1.5 OWNER FURNISHED PLAN
A2.1 BUILDING ELEVATIONS
A3.1 BUILDING SECTIONS
A3.2 BUILDING SECTIONS
A3.3 3D SECTIONS
A4.1 WALL SECTION
A4.2 WALL SECTIONS
A4.3 WALL SECTIONS
A4.4 ENLARGED SECTIONS AND ELEVATION
A5.1 ENLARGED PLANS AND ELEVATIONS
A5.2 ENLARGED PLANS, ELEVATIONS, AND SECTIONS
A5.3 CASEWORK DETAILS
A5.4 FLOOR PLAN DETAILS
A6.1 DOOR SCHEDULE & ELEVATIONS
A6.2 DOOR AND WINDOW DETAILS
A7.1 ROOF PLAN
A7.2 ROOF DETAILS
PROJECT PERSPECTIVE
DRAWING INDEX
STRUCTURAL
S1.0 GENERAL STRUCTURAL NOTES
S1.1 SPECIAL INSPECTIONS
S1.2 TYPICAL DETAILS
S1.3 TYPICAL DETAILS
S2.0 FOUNDATION PLAN
S2.1 LOWER ROOF FRAMING PLAN
S2.2 UPPER ROOF FRAMING PLAN
S3.0 FOUNDATION DETAILS
S3.1 FOUNDATION DETAILS
S4.0 ROOF FRAMING DETAILS
S4.1 ROOF FRAMING DETAILS
S4.2 ROOF FRAMING DETAILS
S4.3 ROOF FRAMING DETAILS
MECHANICAL
M1.0 MECHANICAL FOUNDATION PLAN
M1.1 MECHANICAL FLOOR PLAN
M2.1 MECHANICAL DETAILS
M3.1 EQUIPMENT SCHEDULE AND DETAILS
PLUMBING
P1.0 PLUMBING FOUNDATION PLAN
P1.1 PIPING FLOOR PLAN
P2.1 PLUMBING DETAILS AND DIAGRAMS
ELECTRICAL
E0.0 ELECTRICAL SYMBOLS AND DETAILS
E0.1 ELECTRICAL SITE PLAN
E1.0 LIGHTING PLAN
E2.0 POWER/DATA PLAN
E3.0 POWER RISER AND SCHEDULE
E3.1 ELECTRICAL SCHEDULES AND DETAILS
20
'
-
0
"
25
'
-
0
"
20
'
-
0
"
46'-6"66'-6"25'-0"20'-0"
(TYP.)
9'-5"
8'
-
7
"
26'-0"26'-0"
67
'
-
5
"
20
'
-
0
"
86'-6"
158'-0"
10
'
-
0
"
10
'
-
1
0
"
10'-0"
10'-7"
6'
-
0
"
5'
-
0
"
8'
-
1
0
"
10'-0"
35
'
-
6
"
36
'
-
0
"
5'
-
0
"
22
'
-
0
"
65
'
-
7
1
/
2
"
12
'
-
4
"
10
'
-
0
"
(T
Y
P
.
)
R
7
.
5
'
R7.5
'
6'
-
0
"
6'-0"
6'
-
6
"
15'-6"
9'-0"2'-0"9'-0"2'-0"9'-0"3'-6"10'-0"
32
'
-
2
"
1'
-
1
1
"
1'
-
1
1
"
4'-0"
(TYP.)
19'-6"
15
'
-
8
"
12'-10"8'-1 1/2"
5'-0"
6'-6"11'-0"
(VAN)
5'-0"
13'-9"
24
"
30
"
30
"
10'-0"4'-0"10'-0"
10'-0"
R
1
0
.
0
'
SI
T
E
P
L
A
N
-
H
O
R
I
Z
O
N
T
A
L
C
O
N
T
R
O
L
DRAWING NO.:
CHECKED BY:
DRAWN BY:
DATE:
PROJECT NO.:
REVISIONS
PR
O
J
E
C
T
:
SH
E
E
T
T
I
T
L
E
:
BE
E
H
I
V
E
F
C
U
-
N
O
R
T
H
R
E
X
B
U
R
G
CO
R
N
E
R
O
F
2
N
D
E
A
S
T
A
N
D
M
O
O
D
Y
R
D
.
RE
X
B
U
R
G
,
I
D
A
H
O
8
3
4
4
0
NE
W
B
U
I
L
D
I
N
G
F
O
R
:
GLN
22021
APRIL 2023
CJR
04
-
0
6
-
2
0
2
3
NSCALE:
SITE PLAN
1" = 10'-0"SP1.1
1 City Plan Review 4/21/23
J
FURN.
FURN.
CR
CR
CR
J
J
CR
J
CR
J
J
6
4
3
1
2
ABDE
5
C
AABBCC
1D-3
IP CAM
1
1D-3
IP CAM
1
1D-3
IP CAM
1
2
6D-5
1D-3
IP CAM
1
1D-3
IP CAM
1
1D-3
IP CAM
1
MANAGER
103
BREAK
107
OFFICE 1
104
MECH.
111
JAN./STOR.
112
DRIVE-THRU
106OFFICE 2
113
MAIN LOBBY
102
OFFICE 3
115
I.T.
116
TOILET
117
TOILET
118
VESTIBULE
101
1D-3
122"
1D-3
122"
1 1
IP CAMIP CAM
1D-3
IP CAM
1D-3
IP CAM
1
1
1D-3
122"
IP CAM
1D-3
IP CAM
1
1D-3
IP CAM
1
1D-3
IP CAM
1
1D-3
IP CAM
1
1
2D-3
IP CAM
1 1D-3
IP CAM
2
2 3
3
2
3
2
3
2
3
2
1D-3
IP CAM
1
1D-3
IP CAM
1
1D-3
156"1
IP CAM
1
13053
STATEOFIDAHOSHAWNA.M E A D ORREGISTEREDRP
OFESSIONALENGIN
EE
R
1823 E. Center
Pocatello, Idaho 83201
tel (208) 232-4439
www.payneengineeringinc.com
Engineering Inc.
Consulting Engineers
PROJECT #:
PROJECT NO.
DATE:
DRAWN BY:
CHECKED BY:
DRAWING NO.:
REVISIONS
PR
O
J
E
C
T
:
SH
E
E
T
T
I
T
L
E
:
SAM
TEP
03/24/23
3/
2
3
/
2
0
2
3
1
1
:
3
0
:
1
4
A
M
\
\
P
A
Y
N
E
F
I
L
E
S
E
R
V
E
R
\
M
a
i
n
F
i
l
e
S
t
or
a
g
e
\
2
0
2
3
\
B
e
e
h
i
v
e
F
C
U
R
e
x
b
u
r
g
-
2
3
2
2
\
1
0
_
W
o
r
k
i
n
g
D
r
aw
i
n
g
s
\
B
e
e
h
i
v
e
F
C
U
R
e
x
b
u
r
g
_
S
A
M
_
P
a
y
n
e
.
r
v
t
E0.0
19035
BE
E
H
I
V
E
F
C
U
-
N
O
R
T
H
R
E
X
B
U
R
G
CO
R
N
E
R
O
F
2
N
D
E
A
S
T
A
N
D
M
O
O
D
Y
R
D
.
EL
E
C
T
R
I
C
A
L
S
Y
M
B
O
L
S
&
D
E
T
A
I
L
S
MARCH 2023
NE
W
B
U
I
L
D
I
N
G
F
O
R
:
RE
X
B
U
R
G
,
I
D
A
H
O
8
3
4
4
0
2322
CIRCUITING & GENERAL SYMBOL SCHEDULE
NOTE: ALL SYMBOLS MAY NOT BE USED
SYMBOL DESCRIPTION
KEYED NOTE REFERENCE1
BRANCH CIRCUIT HOME-RUN TO PANEL INDICATED
A-1,3,5
3/4"C.-6#12,1#12G
QTY & SIZE OF EQUIPMENT GROUND CONDUCTOR
QTY & SIZE OF NEUTRAL AND PHASE CONDUCTOR(S)
SIZE OF CONDUIT
A-1,3,5
3/4"C.-6#12,1#12G
PANEL AND CIRCUIT DESIGNATIONS
EQUIPMENT GROUNDING CONDUCTOR
TICK MARKS
NEUTRAL CONDUCTOR(S)
PHASE AND/OR SWITCH-LEG CONDUCTOR(S)
BRANCH CIRCUIT/FEEDER CONCEALED IN CEILING OR WALL
BRANCH CIRCUIT/FEEDER CONCEALED UNDERGROUND OR FLOOR
NEW EQUIPMENT, DEVICES, ETC.
EXISTING EQUIPMENT, DEVICES, ETC.
DEMOLITION EQUIPMENT, DEVICES, ETC.
DETAIL # / SHEET REFERENCE1 / ES101
*25,000A CALCULATED AVAILABLE FAULT CURRENT AT EQUIPMENT(SEE POWER RISER)
LIGHTING SYMBOL SCHEDULE
NOTE: ALL SYMBOLS MAY NOT BE USED
SYMBOL DESCRIPTION
PARKING AREA POLE LIGHT, SINGLE OR DOUBLE HEAD AS INDICATED ON
DRAWINGS. REFER TO LIGHT POLE DETAIL FOR POLE INFORMATION.
2X4 FLUORESCENT OR LED FIXTURE
2X2 FLUORESCENT OR LED FIXTURE
SURFACE MOUNTED FLUORESCENT OR LED FIXTURE
STRIP FLUORESCENT OR LED FIXTURE
WALL MOUNTED FLUORESCENT OR LED FIXTURE
EXTERIOR WALL MOUNTED FIXTURE
ROUND RECESSED FIXTURE
SURFACE OR PENDANT FIXTURE
LIGHT FIXTURE SUBSCRIPTS
NL NIGHT-LIGHT(CONNECT TO UNSWITCHED LEG OF CIRCUIT)
EXIT SIGN, WALL OR CEILING MOUNTING AS REQUIRED (SINGLE OR DOUBLE FACE)
DIRECTIONAL CHEVRONS AS INDICATED; CONNECT TO UNSWITCHED LEG OF LIGHTING
CIRCUIT THAT IS IN THE SAME AREA AS THE EXIT SIGNS.
SHADED FIXTURE INDICATES AN EMERGENCY FIXTURE. PROVIDE WITH EMERG. BATTERY
PACK OR CONNECT TO EMERGENCY POWER SYSTEM (WHERE APPLICABLE). CONNECT
BATTERY PACK TO UNSWITCHED LEG OF LIGHTING CIRCUIT THAT SERVES THE SAME
AREA AS THE EMERGENCY FIXTURE. PROVIDE WITH TEST LIGHT AND SWITCH.
CEILING MOUNTED OCCUPANCY SENSOR, REFER TO OCCUPANCY SENSOR/SWITCH
SCHEDULE FOR SENSOR TYPE AND ADDITIONAL INFORMATION.
SWITCH MOUNTED OCCUPANCY SENSOR OR LOW VOLTAGE SWITCHPOD, REFER TO
OCCUPANCY SENSOR/SWITCH SCHEDULE FOR TYPE AND ADDITIONAL INFORMATION.
SINGLE-POLE SWITCH
DUAL-LEVEL SWITCH, PROVIDE CONTROL OF FIXTURES TO ALLOW OCCUPANT TO
REDUCE LIGHT LEVEL TO 50%. (SUBSCRIPT APPLIES TO BOTH SWITCHES)
SWITCH SUBSCRIPTS
3 3-WAY SWITCH
4 4-WAY SWITCH
D DIMMER SWITCH (COMPATIBLE W/ LOAD & LTG TYPES)
K KEYED SWITCH
F TIMER SWITCH (INTERMATIC MODEL EI400 SERIES)
P PILOT LIGHTED SWITCH
F1 LIGHT FIXTURE TYPE DESIGNATION
S
###
WALL OR CEILING MOUNTED EMERGENCY LIGHTING UNIT W/BATTERY PACK
CONNECT TO UNSWITCHED LEG OF LIGHTING CIRCUIT THAT IS IN THE SAME AREA AS
THE EMERGENCY LIGHT.
LV LOW-VOLTAGE SWITCH (PER DWG'S)
T THERMAL-OVERLOAD SWITCH
M SWITCH SUPPLIED WITH EQUIPMENT,
INSTALLED BY E.C.
WP WEATHERPROOF
2P DOUBLE POLE, SINGLE THROW SWITCH
GENERAL LIGHTING NOTES:
A. SYMBOLS SHOWN ABOVE MAY NOT REPRESENT ALL LIGHT FIXTURES USED ON PROJECT, REFER TO
LIGHT FIXTURE SCHEDULE FOR ACTUAL FIXTURE INFORMATION INCLUDING FIXTURE TYPE, LAMPING,
MOUNTING AND ETC.
B. JUNCTION BOXES FOR LIGHTING CIRCUITING ARE NOT SHOWN FOR CLARITY. THE E.C. IS RESPONSIBLE
FOR PROVIDING AND INSTALLING ALL JUNCTION BOXES REQUIRED FOR CIRCUITING OF ALL LIGHT
FIXTURES THAT ARE NOT LISTED FOR "THROUGH-BRANCH CIRCUIT WIRING".
C. IN GENERAL ALL SWITCH-LEG CONDUCTORS MAY NOT BE SHOWN ON DRAWINGS; E.C. SHALL PROVIDE
AND INSTALL CONDUCTORS AS REQUIRED TO ACHIEVE CONTROL SCHEMES INDICATED AND
DESCRIBED ON DRAWINGS. INCLUDING ALL 0 - 10V DIMMING CONTROLS BETWEEN SWITCH AND
FIXTURES.
D. ALL BATTERY EXIT SIGNS AND EMERGENCY LIGHTING TO BE CONNECTED TO THE UNSWITCHED LEG OF
THE LIGHTING CIRCUIT IN THE AREA.
###
F
M
POWER SYMBOL SCHEDULE
NOTE: ALL SYMBOLS MAY NOT BE USED
SYMBOL DESCRIPTION
ELECTRICAL SWITCHBOARD EQUIPMENT, (SEE POWER RISER AND PANEL SCHEDULES
FOR ADDITIONAL INFORMATION)
'MSB'
'T##'DRY-TYPE TRANSFORMER, (SEE POWER RISER FOR ADDITIONAL INFORMATION)
'LA'
ELECTRICAL PANELBOARD, (SEE POWER RISER AND PANEL SCHEDULES
FOR ADDITIONAL INFORMATION)
DISCONNECT SWITCH, SIZE/POLES/TYPE AS INDICATED
TYPES: 1=NEMA 1, 3R=NEMA 3R, 4X=NEMA 4X30A/3P/3R
FUSED DISCONNECT SWITCH, SIZE/POLES/TYPE AS INDICATED
TYPES: 1=NEMA 1, 3R=NEMA 3R, 4X=NEMA 4X30A/3P/3R
(30A FUSES)
COMBINATION STARTER & FUSED DISCONNECT SWITCH, SIZE/POLES/TYPE AS INDICATED.
TYPES: 1=NEMA 1, 3R=NEMA 3R, 4X=NEMA 4X
J
JUNCTION BOX
CR = CORD REEL; SEE DRAWINGS FOR INFORMATION
CD = CORD DROP; SEE DRAWINGS FOR INFORMATION
EQUIPMENT CONNECTION; COORDINATE CONNECTION WITH EQUIPMENT
PRIOR TO ROUGH-IN
MOTOR CONNECTION
POWER AND/OR DATA SERVICE POLE
FLOORBOX WITH POWER ONLY (SEE FLOORBOX SCHEDULE FOR ADDITIONAL
INFORMATION)
PUSHBUTTON STATION
FLOORBOX WITH POWER AND DATA(SEE FLOORBOX SCHEDULE FOR ADDITIONAL
INFORMATION)
FB#
FB#
SPECIAL RECEPTACLE (COORDINATE NEMA TYPE WITH EQUIP.)
(REFER TO PANEL SCHEDULES FOR AMPS)
CEILING MOUNTED DUPLEX RECEPTACLE (COORDINATE PLACEMENT WITH
CEILING EQUIPMENT PRIOR TO ROUGH-IN)
DUPLEX RECEPTACLE, UL TAMPER-RESISTANT WHERE MOUNTED BELOW 5FT
GFCI-TYPE DUPLEX RECEPTACLE, UL TAMPER-RESISTANT WHERE MOUNTED BELOW 5FT
DOUBLE-DUPLEX RECEPTACLE, UL TAMPER-RESISTANT WHERE MOUNTED BELOW 5FT
GFCI-TYPE DOUBLE-DUPLEX RECEPTACLE, UL TAMPER-RESISTANT WHERE MOUNTED
BELOW 5FT.
RECEPTACLE AND EQUIPMENT SUBSCRIPTS
AC ABOVE COUNTER
WP WEATHERPROOF (UL LISTED
WEATHER-RESISTANT)
42"MOUNTING HEIGHT AFF OR AFG
IG ISOLATED GROUND
S SURGE-PROTECTION TYPE
REF REFRIGERATOR
W WASHING MACHINE
D DRYER (30A-240V RATED RECPT.)
M MICROWAVE
HVAC THERMOSTAT OR SENSOR; PROVIDE & INSTALL BACKBOX,3/4" CONDUIT AND
CONDUCTORS TO ASSOCIATED HVAC UNIT. COORDINATE EXACT LOCATION & SIZE AND
NUMBER OF CONDUCTORS WITH M.C.
T SOR
30A/3P/3R
SIZE 1
(30A FUSES)
SMALL EXHAUST FAN CONNECTION
TV 120V RECEPT. FOR TV; VERIFY HEIGHT WITH ARCH.
DRAWINGS & ELEVATIONS
USB 120V RECPT. WITH USB CHARGING PORTS
EWC ELECTRIC WATER COOLER; (SEE DETAIL. RECPT. SHALL
BE ACCESSIBLE, DO NOT MOUNT BEHIND HOUSING.)
DISP GARBAGE DISP. (UNDER SINK)
DW DISHWASHER (COORDINATE W/ MILLWORK, INSTALL PER
NEC 422.16(B)(2)).
M/R MICROWAVE/RANGE HOOD (COORDINATE W/ MILLWORK)
R ELECTRIC RANGE (50A-240V RATED RECPT.)
GENERAL SPECIAL SYSTEM NOTES:
A. ALL DEVICES SHOWN AT OR NEAR MILLWORK/CASEWORK SHALL BE COORDINATED WITH THE
ARCHITECTURAL ELEVATION DRAWINGS AND MILLWORK INSTALLER TO INSURE PROPER MOUNTING
HEIGHTS. CONTRACTOR SHALL ADJUST DEVICES AS NECESSARY IN ORDER TO POSITION DEVICES SUCH
THAT THEY WILL NOT FALL BEHIND MILLWORK, CABINETS OR BE DIRECTLY ABOVE SINKS OR MIDWAY
BETWEEN TILEWORK/WALL OR WAINSCOATING, ETC.
B. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO INSTALL A GFCI TYPE RECEPTACLE FOR ALL
RECPTACLES SHOWN IN TOILET RMS, BATHROOMS, KITCHENS/SERVING AREAS, ROOFTOP, OUTDOORS
OR WITHIN 6FT OF ANY SINK, BASIN, TUB OR FLOOR SINK AND ALL OTHER AREAS DEFINED BY THE NEC.
SPECIAL SYSTEMS SYMBOL SCHEDULE
NOTE: ALL SYMBOLS MAY NOT BE USED
SYMBOL DESCRIPTION
DATA OUTLET; _= # OF DATA CABLES, X=CONDUIT SIZE (SEE NOTES 1,2,3 BELOW)_D-X
TELEPHONE OUTLET; _= # OF TELEPHONE CABLES, X=CONDUIT SIZE
(SEE NOTES 1,2,3 BELOW)
_T-X
TELEPHONE/DATA OUTLET; _= # OF TELEPHONE/DATA CABLES, X=CONDUIT SIZE
(SEE NOTES 1,2,3 BELOW)
_T/_D-X
CEILING MOUNTED DATA OUTLET; _= # OF DATA CABLES, X=CONDUIT SIZE
(SEE NOTES 1,2,3 BELOW)
_D-X
A. COMMUNICATIONS CABLES SHALL HAVE BENDS NO GREATER THAN 90 DEG.
B. CONDUITS FOR COMMUNICATIONS CABLING SHALL HAVE A MAXIMUM BEND RADIUS NOT MORE THAN 10X
THE DIAMETER OF THE CONDUIT.
C. ALL COMMUNICATIONS CONDUITS SHALL BE TERMINATED WITH AN INSULATED NON-METALLIC BUSHING
AT BOTH ENDS.
D. COMMUNICATIONS CONDUITS SHALL HAVE NO MORE THAN (2) 90'S WITHOUT A PULLBOX. PULL BOXES
SHALL BE LOCATED IN ACCESSIBLE LOCATIONS AND SHALL BE SIZED AT LEASED 12X THE LARGEST
CONDUIT DIAMETER IN LENGTH AND MIN, 4" DEEP AND 8" WIDE.
E. IT SHALL BE THE RESPONSIBILITY OF THE E.C. TO INSURE THAT THE PATHWAY FOR THE DATA CABLING
DOES NOT CREATE CABLE LENGTHS TO EXCEEDS THE LENGTH OF 295FT FROM OUTLET TO PATCH
PANEL, THIS INCLUDES SERVICE LOOPS AND PATCH CORDS.
F. WHERE CABLE TRAY IS UTILIZED IN THE PROJECT. COMMUNICATION CONDUITS ENDING AT THE CABLE
TRAY SHALL EXTEND 1" OVER THE SIDE INTO THE TRAY.
GENERAL SPECIAL SYSTEM NOTES:
RECESSED WALL MOUNTED AV/TV ENCLOSURE, (SEE NOTE 2 BELOW)
HUBBELL ENCLOSURE# NSAV62M W/ COVER# NSAV6C, (1) POWERKIT HBL#NSOKPS,
(1) DATA PLATE W. TERMINATIONS. MOUNT 5'-0" AFF; FIELD COORDINATE WITH TV
LOCATION. E.C. SHALL INSTALL 1 1/4"C FROM DATA COMPARTMENT TO NEAREST
ACCESSIBLE CEILING SPACE. INSTALL DATA CABLING AND TERMINATIONS AS INDICATED
ON DRAWINGS.
LARGE CAPACITY 2-GANG AV BOX, (SEE NOTE 2 BELOW)
HUBBELL# HBL260 WITH 2-GANG MUDRING; PROVIDE 2-GANG DECORA COVER PLATE W/
(1) DATA INSERT (LEVITON P/N: 4164*-*)
(1) BRUSH PASSTHROUGH INSERT (LEVITON P/N: 41075-DB*).
INSTALL 1 1/2" CONDUIT FROM BOX TO ABOVE ACCESSIBLE CEILING.
INSTALL DATA CABLING AND TERMINATIONS AS INDICATED ON DRAWINGS.
TV
AV
_D-X
_D-X
SPECIAL SYSTEMS NOTES:
1. UTILIZE 4 11/16" DEEP BOX WITH REQUIRED MUDRING AND CONDUIT TO ABOVE NEAREST ACCESSIBLE
CEILING OR DATA RACK, TERMINATE WITH INSULATED THROAT BUSHING. PROVIDE QTY OF CABLES
INDICATED FROM OUTLET TO NEAREST TELE/DATA ROOM. SEE DWGS FOR ADDITIONAL INFORMATION.
UTILIZE J-HOOKS 3FT ON CENTER FOR SUPPORT OF CABLING WHERE CABLE TRAY IS NOT
INSTALLED/SPECIFIED.
2. CONDUIT SIZE ('X' FROM ABOVE); 2=1/2", 3=3/4", 4=1", 5=1-1/4", 6=1-1/2"
3. BLANK (NO LABEL) = 4-11/16" DEEP BOX WITH REQUIRED MUDRING AND 1" CONDUIT TO ABOVE NEAREST
ACCESSIBLE CEILING OR TO DATA RACK, TERMINATE WITH INSULATED THROAT BUSHING, PROVIDE PULL
STRING. (UNLESS OTHERWISE NOTED)
WALL PATHWAY SYSTEM; STI FIRESTOP EZ-PATH SERIES
INSTALL THROUGH WALL ABOVE ACCESSIBLE CEILING, FIELD VERIFY EXACT LOCATION TO
AVOID CONFLICT WITH OTHER TRADES AND UTILITIES. PROVIDE ALL REQUIRE MOUNTING
HARDWARE AND ETC. FOR COMPLETE INSTALLATION.
EPF2 = FIRE RATED, EZ-PATH SERIES 22
EPF3 = FIRE RATED, EZ-PATH SERIES 33
EPF4 = FIRE RATED, EZ-PATH SERIES 44
EP3 = NON-FIRE RATED, EZ-PATH 33NEZ SERIES
###
FB#
_D-X MULTI-SERVICE FLOORBOX; SEE FLOORBOX SCHEDULE FOR ADDITIONAL INFORMATION.
_= # OF DATA CABLES, X=CONDUIT SIZE (SEE NOTES 1,2,3 BELOW)
P
1PH
2/C
3/C
3P
3PH
3W
4W
AC
ADA
AFF
AFG
AIC
AL
A or
AMP
ANN
AP
ATS
AV
AWG
BFG
C
CATV
CB
CCTV
CKT
C
CP
CT
CU
DS
EA
E.C.
EM
EMT
ENT
EPO
EQUIP
EX
FA
FACP
FLA
FMC
GND
G.C.
GEN
GFI
GFP
HD
HID
HOA
HP
HPS
HV
HZ
IG
IMC
J-BOX
ABBREVIATIONS
SINGLE POLE
SINGLE-PHASE
TWO-CONDUCTOR
THREE-CONDUCTOR
THREE POLE
THREE-PHASE
THREE-WIRE
FOUR-WIRE
ABOVE COUNTER
AMERICANS WITH DISABILITIES ACT
ABOVE FINISHED FLOOR
ABOVE FINISHED GRADE
AMPERE INTERRUPTING CAPACITY
ALUMINUM
AMPERE
ANNUNCIATOR
ACCESS POINT
(WIRELESS DATA)
AUTOMATIC TRANSFER SWITCH
AUDIO VISUAL
AMERICAN WIRE GAGE
BELOW FINISHED GRADE
CEILING MOUNTED
CABLE TELEVISION
CIRCUIT BREAKER
CLOSED CIRCUIT TELEVISION
CIRCUIT
CONDUIT
CONTROL PANEL
CURRENT TRANSFORMER
COPPER
DISCONNECT SWITCH
EACH
ELECTRICAL CONTRACTOR
EMERGENCY
ELECTRICAL METALLIC TUBING
ELECTRICAL NONMETALLIC TUBING
EMERGENCY POWER OFF
EQUIPMENT
EXISTING
FIRE ALARM
FIRE ALARM CONTROL PANEL
FULL LOAD AMPS
FLEXIBLE METAL CONDUIT
GROUND
GENERAL CONTRACTOR
GENERATOR
GROUND FAULT CIRCUIT INTERRUPTER
GROUND FAULT PROTECTION
HEAVY DUTY
HIGH INTENSITY DISCHARGE
HAND-OFF-AUTOMATIC
HORSE POWER
HIGH PRESSURE SODIUM
HIGH VOLTAGE
HERTZ
ISOLATED GROUND
INTERMEDIATE METAL CONDUIT
JUNCTION BOX
V
KVA
kW
kWh
LED
LFMC
LFNC
LTG
LV
MAX
M.C.
MCA
MCB
MCC
MDP
MH
MIN
MLO
MOCP
NA
NC
NEC
NEMA
NFPA
NIC
NL
NO
NTS
OC
OH DR
OL
PB
P
PNL
PT
PTZ
QTY
RCP
RMC
RNC
SCA
SCBA
SF
SPD
SPEC
SWBD
SWGR
TL
TP
TTB
TV
TYP
UG
UPS
V
VA
V.I.F.
VFD
W/
W/O
WP
XFMR
KILOVOLT
KILOVOLT AMPERE
KILOWATT
KILOWATT HOUR
LIGHT EMITTING DIODE
LIQUID TIGHT FLEXIBLE METAL CONDUIT
LIQUID TIGHT FLEXIBLE NONMETALLIC
CONDUIT
LIGHTING
LOW VOLTAGE
MAXIMUM
MECH. CONTRACTOR
MINIMUM CIRCUIT AMPS
MAIN CIRCUIT BREAKER
MOTOR CONTROL CENTER
MAIN DISTRIBUTION PANEL
MANHOLE
MINIMUM
MAIN LUGS ONLY
MAXIMUM OVERCURRENT PROTECTION
NOT APPLICABLE
NORMALLY CLOSED
NATIONAL ELECTRICAL CODE
NATIONAL ELECTRICAL
MANUFACTURERS ASSOCIATION
NATIONAL FIRE PROTECTION
ASSOCIATION
NOT IN CONTRACT
NIGHT LIGHT
NORMALLY OPEN
NOT TO SCALE
ON CENTER
OVERHEAD DOOR
OVERLOAD
PUSHBUTTON
PHASE
PANEL
POTENTIAL TRANSFORMER
PAN/TILT/ZOOM
QUANTITY
REFLECTED CEILING PLAN
RIGID METAL CONDUIT
RIGID NONMETALLIC CONDUIT
SHORT CIRCUIT AMPS
STANDARD COLOR BY ARCHITECT
SQUARE FOOT (FEET)
SURGE PROTECTION DEVICE
SPECIFICATION
SWITCHBOARD
SWITCHGEAR
TWIST LOCK
TWISTED PAIR
TELEPHONE TERMINAL BOARD
TELEVISION
TYPICAL
UNDERGROUND
UNINTERRUPTIBLE POWER SUPPLY
VOLTS
VOLT AMPERE
VERIFY IN FIELD
VARIABLE FREQUENCY DRIVE
WITH
WITHOUT
WEATHERPROOF
TRANSFORMER
• ELECTRICAL CONTRACTOR SHALL REFER TO THE MECHANICAL DRAWINGS FOR EXACT LOCATIONS
OF ALL MECHANICAL EQUIPMENT AND ELECTRICAL CONNECTIONS.
• ELECTRICAL CONTRACTOR SHALL PROVIDE MINIMUM WORKING CLEARANCE AS PER NEC BEFORE
INSTALLING ANY ELECTRICAL PANELS OR CABINETS. SEE ELECTRICAL EQUIPMENT CLEARANCE
DETAIL.
• INSTALL ALL LIGHT FIXTURES IN MECHANICAL ROOM AFTER THE MECHANICAL EQUIPMENT IS IN
PLACE. ADJUST AS NECESSARY. PROVIDE CHAIN SUSPENSION KITS AS REQUIRED.
• REFER TO ARCHITECTURAL REFLECTED CEILING PLAN(S) FOR EXACT FIXTURE LOCATIONS, CEILING
TYPES, ETC.
• ELECTRICAL CONTRACTOR SHALL PROVIDE ALL CONCRETE PADS AS REQUIRED FOR ALL
ELECTRICAL EQUIPMENT.
• CONFIRM EXACT LOCATIONS OF ALL TELEPHONE/DATA OUTLETS WITH OWNER PRIOR TO ROUGH-IN.
• LOCATE SWITCHES, OUTLETS, ETC., SHOWN AT ROOM ENTRY DOORWAYS, AS CLOSE TO DOOR
FRAME AS POSSIBLE, SO AS NOT RO INTERFERE WITH ROOM CABINETS, ETC.
PROJECT GENERAL NOTES:
• SUPPORT ALL LIGHT FIXTURES INDEPENDENT OF CEILING.
• ELECTRICAL CONTRACTOR SHALL OBTAIN ALL APPLICABLE PERMITS FOR WORK AND PAY ASSOCIATED FEES.
• MAINTAIN 24" MIN. CLEARANCE FROM ALL COMMUNICATIONS CABLING AND ELECTRONIC BALLASTS.
• UNLESS SPECIFICALLY INDICATED OTHERWISE, ELECTRICAL CONTRACTOR SHALL COORDINATE WITH ANY
SPECIAL SYSTEMS SUPPLIER/CONTRACTOR; DENTAL, MEDICAL, KITCHEN, SPECIALIZED EQUIPMENT, ETC. FOR
THE EXACT ROUGH-IN REQUIREMENTS FOR THEIR EQUIPMENT. ALSO UNLESS INDICATED OTHERWISE, THE
ELECTRICAL CONTRACTOR TO BE RESPONSIBLE FOR FINAL ELECTRICAL CONNECTIONS TO ALL SPECIAL
EQUIPMENT.
• ALL CONDUIT/RACEWAY/CABLES TO BE CONCEALED IN WALLS OR ABOVE CEILINGS. IF ANY SURFACE WORK IS
NECESSARY, IT SHALL BE APPROVED BY THE ARCHITECT/ENGINEER PRIOR TO INSTALLATION.
• ELECTRICAL CONTRACTOR SHALL VISIT THE SITE PRIOR TO BID AND THOROUGHLY INVESTIGATE THE
EXISTING CONDITIONS, AS THEY RELATE TO THE SCOPE OF WORK DESCRIBED. MAKE NECESSARY
PROVISIONS IN THE BASE BID TO ADEQUATELY ACCOMMODATE THESE CONDITIONS.
TYPICAL DEVICE MOUNTING HEIGHTS:
GENERAL COORDINATION NOTE:
GENERAL DETAIL NOTES:
FINISH FLOOR
1' - 6''
THERMOSTAT OR SENSORVERIFY WITH M.C. PRIOR TO
LIGHT SW.
(OR AS NOTED)
* 4' - 0''
* 3' - 6''
(OR AS NOTED)
RECEPTACLE
@ MILLWORK
BACKSPLASH
CA
B
.
D
I
M
E
N
S
I
O
N
S
PE
R
A
R
C
H
.
D
E
T
A
I
L
6"
CABINET
*E.C. SHALL COORDINATE ALL DEVICE
MOUNTING HGTS. AND EXACT LOCATION
WITH ARCHITECTURAL INTERIOR
ELEVATIONS REPORT CONFLICTS TO
ARCHITECT **PRIOR TO ROUGH-IN**
ROUGH-IN.
TYPICAL FOR ALL DEVICES
MOUNTED ABOVE COUNTER
(ie C.O.'S, DATA, PHONE etc.)
A.
B.
C.
D.
ALL MOUNTING HEIGHTS TYPICAL UNLESS
NOTED OTHERWISE.
COORDINATE OUTLET HEIGHTS WITH
ARCHITECTS MILLWORK DWGS. TO INSURE
THAT OUTLETS WILL NOT FALL BEHIND
CABINETS, BACKSPLASHES, OR INTERFERE
WITH WAINSCOTING, ETC.
ALL SWITCHES AND THERMOSTATS TO BE
MOUNTED AS CLOSE TO DOOR JAMS AS
POSSIBLE. COORDINATE ALL DEVICES WITH
ARCHITECTURAL PLANS AND DETAILS.
COORDINATE LIGHT SWITCH & OUTLET
HEIGHTS WITH ARCHITECTURAL
WAINSCOTING AND OR TILE WORK SO AS
NOT TO FALL MIDWAY IN THESE FINISHES.
FIRE
6' - 8''
FIRE ALARM NOTIFICATION
DEVICE
FIRE
MANUAL PULL STATION
HANDLE SHALL BE
BETWEEN 42" & 48" AFF CABINET
RECEPT.
TELE/DATA
OUTLET
TV
OUTLET
SECURITY & ACCESS CONTROL SYMBOL SCHEDULE
NOTE: ALL SYMBOLS MAY NOT BE USED
SYMBOL DESCRIPTION
PROVIDE ROUGH-IN FOR CARD REAADER WITH A 3/4" CONDUIT & PULL CORD FROM
WIRING CHASE IN DOOR FRAME TO ABOVE NEAREST ACCESSIBLE CEILING SPACE. E.C.
SHALL COORDINATE WITH ACCESS CONTROL CONTRACTOR.
CR
PROVIDE AND INSTALL A 3/4" CONDUIT & PULL CORD FROM WIRING CHASE IN DOOR
FRAME TO ABOVE NEAREST ACCESSIBLE CEILING SPACE. E.C. SHALL ARRANGE A PRE-
INSTALLATION MEETING WITH G.C. AND DOOR HARDWARE SUPPLIER TO COORDINATE
EXACT PALCEMENT PRIOR TO ROUGH-IN.
• PRIOR TO ROUGH IN E.C. SHALL HAVE A COORDINATION MEETING WITH SECURITY CONTRACTOR FOR
REQUIRED ROUGH-IN FOR ALL SECURITY/ACCESS CONTROL EQUIPMENT.
GENERAL SECURITY & ACCESS CONTROL NOTES:
IDAHO POWER CO. ROCKY MOUNTAIN POWER CO.
WWW.IDAHOPOWER.COM WWW.ROCKYMOUNTAINPOWER.NET
CONTACT: CONTACT:
SHELLEY MARTIN (208) 388-5872 DAN KUHL (503) 308-0233
OR DAN KUHL (503) 308-0233 dan.kuhl@evergreen-efficiency.com
dan.kuhl@evergreen-efficiency.com
UTILITY LIGHTING REBATES & INCENTIVES:
IT SHALL BE THE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR TO PREPARE ALL REQUIRED
APPLICATIONS AND INFORMATION REQUIRED TO PROVIDE THE OWNER WITH THE MAXIMUM AMOUNT OF
REBATE DOLLARS FROM THE LOCAL UTILITY COMPANY. THE ELECTRICAL CONTRACTOR SHALL SUBMIT
VERIFICATION OF THE UTILITY COMPANY PRE-APPLICATION APPROVAL PRIOR TO ORDERING ANY MATERIALS.
VISIT THE FOLLOWING UTILITY CO. WEBSITES FOR INFORMATION:
SCALE: 1/8" = 1'-0"1 SECURITY/ACCESS CONTROL & SOUND SYSTEM ROUGH-IN PLAN
1 E.C. SHALL PROVIDE REQUIRED ROUGH-IN AND CABLING FOR IP CAMERAS; PRIOR
TO ROUGH-IN E.C. SHALL COORDINATE EXACT LOCATIONS WITH OWNER; SEE
GENERAL NOTES FOR OWNER CONTACT INFORMATION. ALL IP CAMERA CABLING
SHALL TERMINATE IN DEDICATED PATCH PANEL(S) IN DATA RACK.
2 E.C. SHALL PROVIDE REQUIRED ROUGH-IN INCLUDING BOX AND CONDUIT TO
SECURITY SYSTEM HEAD-END EQUIPMENT AS DIRECTED BY SECURITY
CONTRACTOR. E.C. SHALL COORDINATE SECURITY ROUGH-IN REQUIREMENTS
WITH SECURITY CONTRACTOR PRIOR TO WORK; SEE GENERAL NOTES.
3 PROVIDE AND INSTALL A 120V CIRCUIT IN J-BOX ABOVE ACCESSIBLE CEILING.
LABEL "ACCESS CONTROL POWER SUPPLY" FOR USE BY ACCESS CONTROL
CONTRACTOR. UTILIZE NEAREST 120V RECEPTACLE CIRCUIT IN AREA.
SOUND SYSTEM SYMBOL SCHEDULE
NOTE: ALL SYMBOLS MAY NOT BE USED
SYMBOL DESCRIPTION
VOLUME CONTROLLER
E.C SHALL PROVIDE ROUGH-IN; BOX, MUDRING AND 1/2" C. WITH PULL STRING TO
ACCESSIBLE CEILING OR SPEAKER; COORDINATE WITH SOUND SYSTEM CONTRACTOR.
ZACH McCLEERY W/ ACS 208-571-7007.
KEY NOTES:#
16'8'0"
All electrical work to comply with 2017 NEC