Description : U-Haul - New Commercial Bldg A
Address : 328 N 2nd E
Application Type :
Document Filename : PLANS - 22-00610 - U-Haul - New Commercial.pdf Array
Comment Author Contact Information:
Corrections in the following table need to be applied before a permit can be issued
Review Report
Revisions Required
Page Reference Annotation
Type
Author : Department Status Page Review Comments Applicant Response Comments
C4 Free text Todd Smith : Broadband Open 15 As per Resolution 2022-07, adopted April 6, 2022, new
development is required to follow standards for the
installation of fiber conduit and distribution boxes. Location
of conduit and distribution boxes need to be identified and
shown on plans.
T1.1 Free text Cody Jones : Building Open 1 Discrepancy in occupant load.
T1.1 Free text Cody Jones : Building Open 1 Landings at doors and cross slope of sidewalks not to exceed
2%.
S0 Free text Cody Jones : Building Open 61 36"
S0.1 Free text Cody Jones : Building Open 62 Special inspector to be identified as per Section 1704.2.1
# 22-00610
New Commercial Building
Please digitally re-submit all pages of the plan set in response to requested revisions
for our next review cycle, with noted items resolved.
Report Date: 09.22.2022
Approval of plans does not constitute approval of variance from code
Page 1 of 2
Page Reference Annotation
Type
Author : Department Status Page Review Comments Applicant Response Comments
E5.1 Callout Alex Owens : Electrical Open 111 Main bonding jumper will be inspected in accordance with
table 250.66 2017 NEC
E5.1 Callout Alex Owens : Electrical Open 111 Transformer system bonding jumper will be inspected in
accordance with table 250.102C1 2017 NEC
C4 Callout Stan Crittenden : Fire Open 15 Need to verify location of FDC on building. FDC must be
located with in 150 ft. of a fire hydrant.
C4 Callout Stan Crittenden : Fire Open 15 Need to verify locations of the FDC. FDC must be located with
in 150 ft. of the fire hydrant.
C4 Free text Stan Crittenden : Fire Open 15 Both building A & B will be required to
have (2) knox boxes installed. One at
main entrance and the second at a side
door.
C4 Callout Kyle Baldwin : P&Z Open 15 Retain and Protect existing sidewalk
C4 Free text Kyle Baldwin : P&Z Open 15 Please show proposed locations for snow storage. Include
square footage in notes. (Landscaping may double as snow
storage area)
C4 Callout Kyle Baldwin : P&Z Open 15 Sidewalks shall be provided along the full length of the
building along any facade featuring a customer entrance, and
along any facade abutting public parking areas. See section
6.00.090,A,2
C4 Callout Kyle Baldwin : P&Z Open 15 Please provide sidewalk connectivity fron internal sidewalks to
sidewalks in right-of-way. see section 6.00.090,B
L1 Free text Kyle Baldwin : P&Z Open 23 Please provide total area of landscaping
C4 Callout Joel Gray : PW Open 15 Existing low back curbing replaced with high back curbing. Typ
4 places
C4 Callout Joel Gray : PW Open 15 Where is existing service tying into? Also concerned about
depth
C4 Callout Joel Gray : PW Open 15 must be 8" sewer line.
C4 Callout Joel Gray : PW Open 15 Install new fire hydrant closer to road and place sidewalk 7 ft
behind curb
C6 Callout Joel Gray : PW Open 17 Could one of the existing water meters on 2nd E be used for
irrigation?
C8 Callout Joel Gray : PW Open 19 Approximate location of existing head manhole
C8 Callout Joel Gray : PW Open 19 Existing 8" sewer line
Report Date: 09.22.2022
Approval of plans does not constitute approval of variance from code
Page 2 of 2