North America: 15K-2P-N
Datasheet Limitless 15K-LV
Input Data (PV)
Max. Allowed PV Power (STC) 19,500W
Nominal Voltage Range 175 - 425V
Startup Voltage 125V
Max. Input Voltage 500V
Max. Input Current per MPPT 26A (self-limiting)
No. of MPP Trackers 3
No. of PV Strings per MPPT 2
Output Data (AC)
Nominal AC Voltage (L-L) 120/240V, 120/208V, 220V
Grid Frequency 50 / 60Hz
Real Power, max continuous 15,000W
Max. Output Current 62.5A
Real Power, max continuous (batteries only, no PV) 12,000W (50A @ 240V)
Peak Apparent Power (10s, off-grid)
Peak Apparent Power (100ms, off-grid)
24,000VA
30,000VA
Max Output Fault Current (5s)
Max Output Fault Current (100ms)
94A with PV, 75A (batteries only, no PV)
120A
Max. Grid Passthrough Current 200A
Power Factor Output Range +/- 0.8 adjustable
Backup Transfer Time 5ms
CEC Efficiency 96.5%
Max Efficiency 97.5%
Design (DC to AC) Transformerless DC
Stackable Up to 12 in parallel
Battery Input Data (DC)
Battery Technologies Lithium / Lead Acid
Nominal DC Voltage 48V
Operating Voltage Range 43 - 63V
Capacity 50 — 9900Ah
Max. Battery Charge / Discharge Current 275A
Charging Controller 3-Stage with Equalization
Grid to Battery Charging Efficiency 96.0%
External Temperature Sensor Included
Current Shunt for Accurate % SOC Integrated
Automatic Generator Start Integrated
Communication to Lithium CANBus & RS485
General Data
Dimensions (H x W x D) 807 x 494 x 306 mm / 31.8 x 19.4 x 12 in
Weight 61.2 Kg / 135 lb.
Enclosure IP65 / NEMA 3R
Ambient Temperature -25~60°C, > 45°C Derating
Noise < 30 dB
Idle consumption - No Load 60W
Wi-Fi & LAN Communication Included
Standard Warranty 10 Years
Protection and Certifications
Electronics Certified Safety by SGS Labs to NEC & UL Specs - NEC 690.4B & NEC 705.4/6 Yes
Grid Sell Back — UL1741-2010/2018, IEEE1547a 2003/2014, FCC 15 Class B, UL1741SB, CA Rule
21, HECO Rule 14H Yes
PV DC Disconnect Switch — NEC 240.15 Integrated
Ground Fault Detection — NEC 690.5 Integrated
PV Rapid Shutdown Control — NEC 690.12 Integrated
PV Arc Fault Detection — NEC 690.11 Integrated
PV Input Lightning Protection Integrated
PV String Input Reverse Polarity Protection Integrated
AC Output Breaker - 200A Integrated
200A x 2 Battery Breaker / Disconnect Integrated
Surge Protection DC Type II / AC Type II