PLAN REVIEW FOR FIRE SPRINKLER SYSTEMS
PLANS RECEIVED: September 21, 2023 APPROVED: September 27,
2023
REVIEWED BY: Rory Winch, Fire Plans Examiner
PROJECT: Madison Jr. High Addition
STREET ADDRESS: 134 Madison Ave. CITY: Rexburg
AHJ: Madison Fire Department
SPRINKLER CONTRACTOR: Phoenix Fire Protection
4130 Airport Road
Nampa, ID 83687
IDAHO LICENSE: FPSC-108
CONTACT NAME: ASHTON DITTMAR
design@phoenixfp.com
PHONE NO: (208) 468-9115
SYSTEM DESIGNED BY: Boston Orahood
boston@phoenixfp.com
PHONE NO: (208) 468-9115
TYPE OF SYSTEM: NFPA 13 HEAD COUNT: 233
TOTAL SYSTEMS: 1 OCCUPANCY CLASSIFICATION: E
CONSTRUCTION TYPE: VB AREA SQUARE
FOOTAGE: 16,108
SCOPE OF WORK: PHOENIX FIRE TO INSTALL IN AN ADDITION A WET SPRINKLER
SYSTEM PER NFPA 13
PLAN REVIEW COMMENTS: Approved with comments
1. Annular space required. 18.4.1* Clearance shall be provided around all piping
extending through walls, floors, platforms, and foundations, including drains, fire
department connections, and other auxiliary piping.
Approval of shop drawings is not intended to imply waiver or modification of any requirements of the Idaho State Statutes or
Rules, International Fire Code, NFPA Standards or any other applicable criteria.
It is acknowledged that backflow preventer is installed per the demand of the local water purveyor. The State Fire Marshal’s
Office and its personnel does not take any responsibility for the back flow device.