HomeMy WebLinkAboutFA INSPECTION FORM - 22-00795 - Madison Station Apartments - Bldg 1FIRE ALARM AND EMERGENCY COMMUNICATION SYSTEM INSPECTION AND
To be completed by the system impector or tester at the time of the inspection or test
It shall be permitted to modify thisform as needed to provide a more complete and/or clear
Insert N/A in all unused lines.
Attach additional sheets, data, or calculations as necessary to provide a complete reco,
Date of this inspection or test:
1. PROPERTY INFORMATION
Time of inspection or test:
Name of property: Madison Station Apartments Building 1 (tower 1 and 2)
Address: 1460 Elk Creek, Idaho Falls, Id 83404
Description of property: Apartment Complex
Occupancy type:
Name of property representative: Alex Lloyd
Address:
Phone: Fax: E-mail-
Authority having jurisdiction over this property:
Phone: Fax: E-mail:
2. INSTALLATION, SERVICE, AND TESTING CONTRACTOR INFORMATION
Service and/or testing organization for this equipment: 4Sight Security
Address: 6944 Big Bend Drive
Phone: 2084031434 Fax: E-mail: 4sightsecurity@
Service technician or tester: Trevor Blackburn
Qualifications of technician or tester: Idaho Specialty Electrical
A contract for test and inspection in accordance with NFPA standards is in effect as of:
The contract expires: Auto Renew Contract number: Frequency of tests and
Monitoring organization for this equipment: Avant Guard H23160
Address:
Phone: Fax: E-mail:
Entity to which alarms are retransmitted: Phone:
3. TYPE OF SYSTEM OR SERVICE
® Fire alarm system (nonvoice)
❑ Fire alarm with in -building fire emergency voice alarm communication system (EVACS)
❑ Mass notification system (MNS)
❑ Combination system, with the following components:
❑ Fire alarm ❑ EVACS ❑ MNS ❑ Two-way, in -building, emergency
❑ other (specify):
system
FORM
Annual
Copyright ®2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for colpmercial sale or distribution.
3. TYPE OF SYSTEM OR SERVICE (continued)
NFPA 72 edition:
3.1 Control Unit
Manufacturer: Potter
3.2 Mass Notification System
3.2.1 System Type:
❑ In -building MNS—combination
❑ In -building MNS—stand-alone
❑ Other (specify):
Additional description of system(s):
Model number:
❑ This system does not
❑ Wide -area MNS ❑ Distributed recipient MNS
3.2.2 System Features:
❑ Combination fire alarm/MNS ❑ MNS ACU only ❑ Wide -area MNS to regional national t
❑ Local operating console (LOC) ❑ Direct recipient MNS (DRMNS) ❑ Wide -area MNS to DI
❑ Wide -area MNS to high -power speaker array (HPSA) interface ❑ In -building MNS to wide -area MI
❑ Other (specify):
AFC-1000
an MNS.
xting interface
ANS interface
i interface
3.3 System Documentation
❑ An owner's manual, a copy of the manufacturer's instructions, a written sequence of operation, and a -opy of the record
record drawings are stored on site. Location:
3.4 System Software ❑ This system does not have alterable s e-specific software.
Software revision number: SF0815 Software last updated on:
❑ A copy of the site -specific software is stored on site. Location:
4. SYSTEM POWER
4.1 Control Unit
4.1.1 Primary Power
Input voltage of control panel: 120VAC Control panel amps: 20
4.1.2 Engine -Driven Generator ® This system does lot have a generator.
Location of generator:
Location of fuel storage: Type of fuel:
4.1.3 Uninterruptible Power System ® This system es not have a UPS.
Equipment powered by a UPS system:
Location of UPS system:
Calculated capacity of UPS batteries to drive the system components connected to it:
In standby mode (hours): In alarm mode (minutes):
copyright 0 2009 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for w meraal sale or distribution.
4. SYSTEM POWER (continued)
4.1.4 Batteries
Location: In panel Type: LEAD ACID
Nominal voltage; 18VDC X2 Amp/hol
Calculated capacity of batteries to drive the system:
In standby mode (hours): 824
In alarm mode (minutes): 8
® Batteries are marked with date of manufacture.
4.2 In -Building Fire Emergency Voice Alarm Communication System or Mass Notification Systen
® This system does not have an EVACS or MNS.
4.2.1 Primary Power
Input voltage of EVACS or MNS panel:
EVACS or MNS panel amps:
4.2.2 Engine -Driven Generator
® This system does
Location of generator:
Location of fuel storage:
Type of fuel:
-ating: 12
have a generator.
4.2.3 Uni nruptible Power System ® Thissystemd
as not have a UPS.
Equipment powered by UPS system:
Location of UPS system:
Calculated capacity of UPS batteries to drive the system components connected to it:
In standby mode (hours): In alarm mode (minutes):
4.2.4 Batteries
Location: Type: Nominal voltage: Amp/hou
rating:
Calculated capacity of batteries to drive the system:
In standby mode (hours): In alarm mode (minutes):
.flatteries are marked with date of manufacture.
4.3 Notification Appliance Power Extender Panels ❑ This system does not have pov
er extender panels.
4.3.1 Primary Power
Input voltage of power extender panel(s): Power extender nel amps:
4.3.2 Engine -Driven Generator s system does r
or have a generator.
Location of generator:
Location of fuel storage: Type of fuel:
4.3.3 Uninterruptible Power System ❑ This system
s not have a UPS.
Equipment powered by a UPS system:
Location of UPS system:
Calculated capacity of UPS batteries to drive the system components connected to it:
In standby mode (hours): In alarm mode (minutes):
_.
copyright ® 2009 National Fire Protection AssocWtion. This form may be copied for individual use other than for resale. It may not be copied for com
ercial sale or distribution.
4. SYSTEM POWER (continued)
4.3.4 Batteries
Location: Type:
Calculated capacity of batteries to drive the system:
In standby mode (hours):
❑ Batteries are marked with date of manufacture.
5. ANNUNCIATORS
5.1 Location and Description of Annunciators
Annunciator I:
Annunciator 2:
Annunciator 3:
6. NOTIFICATIONS MADE PRIOR TO TESTING
Nominal voltage:
In alarm mode (minutes):
Monitoring organization
Contact: AvantGuard
Building management
Contact: Front Receptionist
Building occupants
Contact:
Authority havingiurisdiction
Contact:
Other, if required
Contact:
7. TESTING RESULTS
7.1 Control Unit and Related Equipment
Visual I Functional
Other (specify)
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
0 This system does not
Time:
Time:
Time:
Time:
Time:
rating:
annunciators.
Copynght ®2008 National Fire Protection Association. TNs form maybe copied for Individual use other than for resale. a may not be copied for c mr nemial sale or distribution.
7. TESTING RESULTS (continued)
7.2 Control Unit Power Supplies
Visual I Functional
condition
OK
NA
OK
OK
OK
OK
—Other (specify) 1 ❑ 1 ❑ 1
7.3 In -Building Fire Emergency Voice Alarm Communications Equipment
Visual Functional
Control unit
❑
❑
NA
Lam s/LEDs/LCDs
®
®
OK
Fuses
®
®
OK
Primary power supply
®
®
OK
Secondary power supply
®
®
OK
Trouble signals
®
®
OK
Disconnect switches
®
®
OK
Ground -fault monitoring
®
®
OK
Panel supervision
®
®
OK
System performance
®
®
OK
Sound pressure levels
Occupied ❑ Yes ❑ No
Ambient dBA
Alarm dBA
®
®
OK
(attach report with locations, values
System intelligibility ❑ I ❑ OK
❑ CSI ❑ STI
(attach report with locations, values,
Other (specify)
Copyright ® 2009 National Fire protection Association. This form may be copied for individual use oNer than for resale. It may not be copied for co,lmercial sale or o stribution.
7. TESTING RESULTS (continued)
7.4 Notification Appliance Power Extender Panels
Visual
Functional
Description
inspection
Test
Lam s/LEDs/LCDs
❑
❑
Fuses
❑
❑
Primary power supply
❑
❑
around -fault monitoring ❑ ❑
Panel supervision Q Q
Other (specify)
7.5 Mass Notification Equipment
NA
NA
NA
NA
NA
NA
NA
Description
Visual
Inspection
Functional
Test
Functional test
❑
❑
N/A
-Reset/power down test
❑
❑
NA
Fuses
❑
❑
NA
-Primary power supply
❑
❑
NA
UPS power test
❑
❑
NA
Trouble signals
❑
❑
NA
Disconnect switches
❑
❑
NA
Ground -fault monitoring
❑
❑
NA
CCU security mechanism
❑
❑
NA
Prerecorded message content
❑
❑
NA
Prerecorded message activation
❑
❑
NA
Software backup performed
❑
❑
NA
Test backup software
❑
❑
NA
Fire alarm to MNS interface
❑
❑
NA
MNS to fire alarm interface
❑
❑
NA
In -building MNS to wide -area
❑
❑
NA
Copyright 020M National Fire Protection Association. This torte maybe copied for Individual use dher than for resale. It may not be copied for comemial sale or distribution.
7. TESTING RESULTS (continued)
7.5 Mass Notification Equipment (continuer)
Visual
Functional
Description
Inspection
Test
MNS to direct recipient MNS
❑
❑
NA
Sound pressure levels
❑
❑
NA
Occupied ❑ Yes ❑ No
Ambient dBA
Alarm dBA
(attach report with locations, values,
and weather conditions)
System intelligibility
❑
❑
NA
❑ CSl ❑ STI
(attach report with locations, values,
and weather conditions
—Other (specify) ❑ ❑
7.6 Two -Way Communications Equipment
Visual
Functional
Description
Inspection
Test
Phone handsets
❑
❑
NA
Phone'acks
❑
❑
NA
—Off-hook indicator
❑
❑
NA
Call -in si nal
❑
❑
NA
—System performance
❑
❑
NA
—System audibility
❑
❑
NA
—System intelligibility
❑
❑
NA
Radio communications
❑
❑
NA
enhancements stem
Area of refuge communication
❑
❑
NA
s stem
Elevator emergency
❑
❑
NA.
communications system
Other (specify)
❑
❑
Comments
Copyright 0 2009 National Fire Protection Association. This forth may be copied for individual use other than for resale. It may not be copied
7. TESTING RESULTS (continued)
7.7 Combination Systems
Visual
Functional
Description
Inspection
Test
Comments
Fire extinguishing monitoring ❑ ❑ NSA
devices/system
Carbon monoxide detector/system ❑ ❑ NA
Combination fire/securi s stem ❑ ❑ NA
Other (specify) ❑ ❑
7.8 Special Hazard Systems
Visual
tion s eci
Ins ection
Comments
nFunctionalDescri
❑❑
7.9 Emergency Communications System
❑ Visual
❑ Functional
❑ Simulated operation
❑ Ensue predischarge notification appliances of special hazard systems are not overridden by the MN
See NFPA 72, 24.4.1.7.1.
.
7.10 Monitored Systems
Visual
Functional
Description s eci
Inspection
Test
Comments
-Engine-driven generator
❑
❑
NA
NA
NA
Fire pump
❑
❑
S ecial suppression systems
❑
❑
Other (specify)
❑
❑
Copyn& ®2009 National Fire Proteotien Association This form may ba coped for individual use other than for resale. It may not be copied for commercial sale or di.s button.
7. TESTING RESULTS (continued)
7.11 Auxiliary Functions
Description
Visual
Inspection
Functional
Test
Comments
—Door-releasing devices
❑
❑
NA
NA
NA
NA
NA
NA
NA
NA
NA
Fan shutdown
❑
❑
Smoke management/smoke control
❑
❑
Smoke damper operation
❑
❑
Smoke shutter release
❑
❑
Door unlocking
❑
❑
Elevator recalll❑
Elevator shunt trip
❑
MNS override of FA si
❑
Other (specify)
❑
7.12 Alarm Initiating Device
® Device test results sheet attached listing all devices tested and the results of the testing
7.13 Supervisory Alarm Initiating Device
® Device test results sheet attached listing all devices tested and the results of the testing
7.14 Alarm Notification Appliances
I@ Appliance test results sheet attached listing all appliances tested and the results of the testing
7.15 Supervisory Station Monitoring
Description
No
Time
Com ents
Alarm signalAlarm
restorationTrouble
si 1Trouble
VIOC:31
restorationSu
rviso si alSu
ervisor restoration
❑
Copyright 0 2009 National Fire Proteelion Association. THIS form may be copied for indvidual use other than for resale. It may not be copied for comlarclat sale or distribution.
8. NOTIFICATIONS THAT TESTING IS COMPLETE
Monitoring organization
Contact: Avantouartl
Time:
Building management
Contact. All Present
Time:
Building occupants
Contact:
Time:
Authority having jurisdiction
Contact:'
Time:
Other, if required
Contact:
Time:
9. SYSTEM RESTORED TO
NORMAL OPERATION
Date:
'lime:
10. CERTIFICATION
10.1 Inspector Certification:
This system, as specified herein, has been inspected and tested according to all NFPA standards cited
Signed: Printed name: Trevor Blackburn
Date:
Organization: 4Sight Security, Title: Manager LLC Phone:
10.2 Acceptance by Owner or Owner's Representative:
The undersigned has a service contract for this system in effect as of the date shown below.
Signed:
Organization:
Printed name:
Title.
Date:
Phone:
Copyright C 2009 National Fire Protection Association. This form may be copied for Individual use other than for resale. It may not be copied for ccm,Ircial sale or distribution.
DEVICE TEST RESULTS
(Attach additional sheets if required)
Pull Statiom
2
FACP?RISER Room
Photo Smoke
3
FACP/RISER room
Flow Imput
4.1
Water Flow
Tamper 1
5.1
Tamper/Sprinkler
Tamper
5.2
Tamper/Sprinkler
Nac MOD
6
unit 1104 ADA room
Carbon
7
ADA Room 11 o4
Photo Smoke
8
ADA Room i i o4
Copyright 0 2009 National Fire Protection Association. This form may be copied for individual use other then for resale. It may not be copied for ,ommi-ial sale or distribution.