HomeMy WebLinkAboutINFRASTRUCTURE PLAN Rev 3 3.23.23 - 22-00795 - Madison Station Apartments - Trejo St-Reviewed-ApprovedAuthor Name Author Email Author Phone No.: Stan Crittenden Stan.Crittenden@rexburg.org 208-372-2314 Joel Gray Joel.Gray@rexburg.org 208-372-2331 Kyle Baldwin Kyle.Baldwin@rexburg.org 208-372-2164 Todd Smith Todd.Smith@rexburg.org 208-372-2181 Katie Saurey Katie.Saurey@rexburg.org 208-372-2167 Description : Madison Station Apartments - Bldg 1Address : 577 Trejo StRecord Type : New Multi-Family ResidenceDocument Filename : INFRASTRUCTURE PLAN Rev 3 3.23.23 - 22-00795 - Madison Station Apartments - Trejo St.pdf Comment Author Contact Information: Corrections in the following table need to be applied before a permit can be issued Review Report Approved # 22-00795 Page Reference AnnotationType Author : Department Status Page Review Comments Applicant Response Comments 1 COVER Stamp Todd Smith : Broadband Open 3 Approved - Broadband Inspector 1 COVER Stamp Stan Crittenden : Fire Open 3 Approved - Fire Dept Report Stamp Katie Saurey : P&Z Open 1 Plan Received 1 COVER Stamp Katie Saurey : P&Z Open 3 Plan Received C-2 Stamp Kyle Baldwin : P&Z Open 6 Approved - Planning and Zoning C-3 Stamp Kyle Baldwin : P&Z Open 7 Approved - Planning and Zoning 1 COVER Stamp Joel Gray : PW Open 3 Approved - Public Works New Multi-Family Residence Approval of plans does not constitute approval of variance from code Powered by TCPDF (www.tcpdf.org) See Attached, Item #1 See Attached, Item #2 See Attached, Item #3 Attachment 1. Fire Department approved previous location of fire hydrant, but as requested the hydrant location has been changed. See sheet C-2. 2. Through presubmittal meetings with the City Engineering Dept., the probability of connectivity to the south is unknown. The Owner has agreed to provide a ROW when/if the need arises. A note has been added to the drawings acknowledging the future ROW and that modifications to the site will be needed once the scope of the ROW is identified. See sheets C-2 & SD1.1. 3. A dedicated left turn lane has been shown from west bound Trejo to the project access. See sheet C-2 & SD1.1. Fi l e L o c a t i o n : z: \ p r o j e c t s \ 2 0 2 2 \ 2 2 1 2 5 m a d i s o n s t a t i o n a p a r t m e n t s \ 3 . 0 d e s i g n \ 3 . 1 c a d \ 3 . 1 3 f i n a l \ 2 2 1 2 5 c o v e r . d w g Pl o t t e d B y : ru s s e l l Da t e P l o t t e d : We d n e s d a y , M a r c h 2 2 2 0 2 3 a t 0 3 : 2 7 P M 1 -- - - CO V E R CIVIL SITEWORK FOR: PART OF THE SOUTHEAST QUARTER OF SECTION 25, TOWNSHIP 6 NORTH, RANGE 39 EAST, BOISE MERIDIAN, CITY OF REXBURG, MADISON COUNTY, IDAHO APPROVED BY: CITY OF REXBURG ENGINEERING DEPARTMENT APPROVED BY: ROCKY MOUNTAIN POWER APPROVED BY: MADISON FIRE DEPARTMENT APPROVED BY: LUMEN APPROVED BY: INTERMOUNTAIN GAS MADISON STATION APARTMENTS March 2023 AG L E R O C K N G I N E E R I N G SU R V E Y E D B Y : DR A W N B Y : PR O J E C T N O . AP P R O V E D B Y : DE S C R I P T I O N DA T E RE V I S I O N S 1 2 3 4 5 6 AT T E N T I O N Th i s d o c u m e n t o r a n y p a r t t h e r e o f i n d e t a i l o r d e s i g n c o n c e p t is t h e p r o p e r t y o f E a g l e R o c k E n g i n e e r i n g a n d s h a l l n o t b e co p i e d i n a n y f o r m w i t h o u t t h e w r i t t e n a u t h o r i z a t i o n o f E a g l e Ro c k E n g i n e e r i n g . E SH E E T N O . SH E E T N A M E CI V I L P L A N N I N G S U R V E Y I N G ID A H O F A L L S ( 2 0 8 ) 5 4 2 - 2 6 6 5 RE X B U R G ( 2 0 8 ) 3 5 9 - 2 6 6 5 PR E P A R E D F O R : RY A N N E L S O N MA D I S O N S T A T I O N A P A R T M E N T S A. S N A R R R. J O R D A N P. S N A R R 22 1 2 5 P R E L I M I N A R Y N O T A P P R O V E D F O R C O N S T R U C T I O N 16 4 1 0 Designed By: AGLE ROCK NGINEERING CIVIL PLANNING SURVEYING IDAHO FALLS (208) 542-2665 E REXBURG (208) 359-2665 IDAHO FALLS REXBURG BLACKFOOT CHUBBUCK TWIN FALLS SUN VALLEY CASCADE McCALL BOISE MOSCOW COUER d' ALENE RUPERT SALMON AMMON ST.ANTHONY ISLAND PARK POCATELLO MOUNTAINHOME RIGBYIONA SHELLEY VO L M O S S R D . PROJ E C T LOCA T I O N TREJO ST. MA R L I N A V E . S. 1 0 0 0 S t W W. 5TH S. W. 6TH S. St TU R I N W A Y W E S N HANDCART Ln SHEET INDEX SHEET No.SHEET NAME SHEET TITLE 1 COVER 2 G-1 NOTES 3 C-1 EXISTING CONDITIONS & DEMOLITION PLAN 4 C-2 OVERALL SITE PLAN 5 C-3 GRADING & STORM PLAN 6 C-4 STORM AREA TABLES 7 PP-1 ALIGNMENT D, G, & E 8 PP-2 ALIGNMENT F 9 PP-3 ALIGNMENT C & H 10 PP-4 ALIGNMENT A 11 PP-5 ALIGN B 12 PP-6 ALIGNMENT I & J 13 PP-7 ALIGNMENT K 14 PP-8 SOUTHWEST SERVICE CONNECTIONS 14 SWPPP STORM WATER POLLUTION PREVENTION PLAN 15 D-1 DETAILS 16 D-2 DETAILS Fi l e L o c a t i o n : z: \ p r o j e c t s \ 2 0 2 2 \ 2 2 1 2 5 m a d i s o n s t a t i o n a p a r t m e n t s \ 3 . 0 d e s i g n \ 3 . 1 c a d \ 3 . 1 3 f i n a l \ 2 2 1 2 5 n o t e s . d w g Pl o t t e d B y : ru s s e l l Da t e P l o t t e d : We d n e s d a y , M a r c h 2 2 2 0 2 3 a t 0 3 : 2 7 P M 2 G- 1 NO T E S AG L E R O C K N G I N E E R I N G SU R V E Y E D B Y : DR A W N B Y : PR O J E C T N O . AP P R O V E D B Y : DE S C R I P T I O N DA T E RE V I S I O N S 1 2 3 4 5 6 AT T E N T I O N Th i s d o c u m e n t o r a n y p a r t t h e r e o f i n d e t a i l o r d e s i g n c o n c e p t is t h e p r o p e r t y o f E a g l e R o c k E n g i n e e r i n g a n d s h a l l n o t b e co p i e d i n a n y f o r m w i t h o u t t h e w r i t t e n a u t h o r i z a t i o n o f E a g l e Ro c k E n g i n e e r i n g . E SH E E T N O . SH E E T N A M E CI V I L P L A N N I N G S U R V E Y I N G ID A H O F A L L S ( 2 0 8 ) 5 4 2 - 2 6 6 5 RE X B U R G ( 2 0 8 ) 3 5 9 - 2 6 6 5 PR E P A R E D F O R : RY A N N E L S O N MA D I S O N S T A T I O N A P A R T M E N T S A. S N A R R R. J O R D A N P. S N A R R 22 1 2 5 P R E L I M I N A R Y N O T A P P R O V E D F O R C O N S T R U C T I O N 16 4 1 0 GIDUOYEROFEBLLA C DIG LINE 1-800-342-1585 ELECTRICAL NOTES: 1.ALL TRAFFIC SIGNAGE SHALL BE DESIGNED, CONSTRUCTED AND PLACED IN ACCORDANCE WITH THE CURRENT MANUAL OF UNIFORM TRAFFIC CONTROL DEVICES (MUTCD) WITH THE FOLLOWING EXCEPTIONS: 2.ALL STOP AND YIELD SIGNS USED IN ANY SUBDIVISION SHALL BE A MINIMUM 30”X 30”. ENGINEER GRADE SHEETING SHALL NOT BE ALLOWED. 3.ALL ROAD NAME AND STREET SIGNS SHALL HAVE A MINIMUM 4” LEGEND. BOTH BACKGROUND AND LEGEND SHALL BE REFLECTIVE STANDARD COLORS WITH WHITE LEGEND AND GREEN BACKGROUND EXCEPT PRIVATE ROADS, WHICH WILL HAVE A BLUE BACKGROUND. 4.SUBSTRATE MATERIAL SHALL BE ALUMINUM; NO FIBERGLASS OR PLASTIC WILL BE ACCEPTED. 5.THE MINIMUM SIZE FOR SPEED LIMIT SIGNS SHALL BE 24”W X 30”L WITH BLACK LEGEND ON WHITE BACKGROUND. 6.POSTS SHALL BE METAL AND SHALL BE ANCHORED WITH A “SOIL TYPE” ANCHOR. NO CONCRETE SHALL BE USED AS AN ANCHOR. POSTS SHALL BE 2”X 2” SQUARE AND SHALL MEET BREAK-A-WAY STANDARDS OF THE STATE OF IDAHO. NO U-CHANNEL SHALL BE USED. 7.THE MINIMUM HEIGHT OF SIGNS SHALL BE 6' FROM THE ROAD SURFACE TO THE BOTTOM OF THE SIGN. 8.MAINTENANCE OF ALL STREET AND TRAFFIC SIGNS WILL BE THE RESPONSIBILITY OF THE DEVELOPER UNTIL THE STREETS ARE OFFICIALLY ACCEPTED FOR MAINTENANCE BY THE CITY OF REXBURG. SIGNAGE NOTES: GENERAL NOTES: 1.ALL NEW ELECTRICAL FACILITIES SHALL BE CONSTRUCTED IN ACCORDANCE WITH THE CURRENT ROCKY MOUNTAIN POWER SERVICE POLICY. 2.DEVELOPER SHALL BEAR ALL COSTS TO RELOCATE OR REMOVE EXISTING POWER POLES, LIGHT POLES, ANCHOR GUYS AND MISCELLANEOUS ELECTRICAL FACILITIES. 3.ALL PVC ELECTRIC CONDUITS SHALL BE PVC SCHEDULE 40. ALL FIBERGLASS CONDUITS SHALL MEET ROCKY MOUNTAIN POWER'S MARKING AND STRENGTH RATING REQUIREMENTS. CONDUIT DIAMETERS SHALL MEET ROCKY MOUNTAIN POWER'S DESIGN. ALL ELBOWS SWEEP RADII SHALL BE 36”, 48” OR 60” DEPENDING ON ROCKY MOUNTAIN POWER'S DESIGN. 4.ALL PRIMARY AND SECONDARY CONDUITS SHALL BE PROVIDED AND INSTALLED BY THE DEVELOPER. 5.TRENCH EXCAVATION AND CONDUIT PLACEMENT SHALL BE IN ACCORDANCE WITH ROCKY MOUNTAIN POWER SERVICE POLICY SPECIFICATIONS AND IN ACCORDANCE WITH OSHA STANDARDS. CONDUIT TRENCH DEPTHS SHALL BE BETWEEN 36” AND 48” (NOT TO EXCEED 60”) AND INCLUDE THE REQUIRED SAND PLACEMENT BELOW AND ABOVE THE PLACED CONDUIT. 6.THE ENGINEER SHALL PROVIDE ALL STAKING AND LAYOUT OF NEW ELECTRICAL FACILITIES INCLUDING POWER POLES. 7.THE CONTACTOR SHALL RETAIN AND PROTECT ALL EXISTING POWER POLES AND ELECTRICAL FACILITIES DURING CONSTRUCTION. 8.THE DEVELOPER SHALL COORDINATE ALL ELECTRICAL CONSTRUCTION WITH ROCKY MOUNTAIN POWER. 9.CLEARANCE BETWEEN OVERHEAD POWER AND NEW BUILDING STRUCTURES SHALL BE MAINTAINED MEETING THE CURRENT ROCKY MOUNTAIN POWER SERVICE POLICY. 10.SEE ROCKY MOUNTAIN POWER ELECTRICAL SITE PLAN FOR OFF-SITE AND ON-SITE ELECTRICAL LAYOUT AND INSTALLATION DETAILS. IN THE EVENT THE FIBER OPTIC UTILITY ELECTS TO USE THE SAME TRENCH, THEY MUST MEET NESC UNDERGROUND UTILITY CLEARANCES. 11.A 15 FOOT WIDE PUBLIC UTILITY EASEMENT IS PERPETUALLY RESERVED WITHIN EACH LOT ALONG ALL ROAD FRONTAGES FOR THE USE OF PUBLIC UTILITIES WITHIN THIS SUBDIVISION. NO PERMANENT STRUCTURES, SIDEWALKS, AND DRIVEWAYS SHALL BE CONSTRUCTED OVER SAID EASEMENT (OTHER THAN CROSSINGS) IN ORDER FOR THE UTILITY COMPANIES TO MAINTAIN. FIRE DEPARTMENT NOTES: 1.TURNING RADIUS (CUL-DE-SACS/HAMMERHEADS) SHALL MEET IFC D103.4. DEAD ENDS SHALL REQUIRE A 96' DIAMETER CUL-DE-SAC FOR TURNING EMERGENCY VEHICLES. THE CUL-DE-SAC DESIGN FOR THIS SUBDIVISION IS DESIGNED WITH A 98' DIAMETER TURNAROUND FROM BACK OF CURBS (96' TURNING WIDTH). 2.FIRE CODE SIGNAGE SHALL BE DETERMINED BY THE FIRE CODE OFFICIAL. WHEN REQUIRED, SIGNS MEETING IFC D103.6 SHALL BE INSTALLED (REQUIRED UPON OFFICIAL OR WHEN STREETS COMING INTO DEAD ENDS ARE LESS THAN 26' IN WIDTH AND THE TURNING RADIUS DOES NOT MEET 96' DIAMETER). 1.UNLESS OTHERWISE SHOWN ON THESE PLANS ALL WORK IS TO BE PERFORMED IN ACCORDANCE TO CURRENT CITY OF REXBURG STANDARD DRAWINGS AND SPECIFICATIONS. THE CONTRACTOR IS REQUIRED TO MAINTAIN A COMPLETE COPY ON SITE AT ALL TIMES (RESOLUTION 2016-15). 2.ALL DISTANCES AND DATA SHALL BE CHECKED BY THE CONTRACTOR PRIOR TO THE START OF CONSTRUCTION. IN CASE OF CONFLICT THE ENGINEER SHALL BE NOTIFIED IMMEDIATELY SO THAT CLARIFICATION MAY BE MADE PRIOR TO THE START OF WORK. 3.BASIS OF BEARINGS CITY OF REXBURG CONTROL. 4.ELEVATIONS SHOWN ARE NAVD 88 DATUM TO FINISHED SURFACE OR PIPE INVERT UNLESS OTHERWISE NOTED. 5.GENERAL LOCATIONS AND SIZES OF UTILITIES ARE SHOWN ON THE PLANS. THEY ARE TO BE USED FOR GENERAL INFORMATION ONLY. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO NOTIFY THE APPROPRIATE UTILITY COMPANIES WHEN CONSTRUCTION MIGHT INTERFERE WITH NORMAL OPERATIONS OF ANY UTILITIES. IT SHALL ALSO BE THE CONTRACTORS RESPONSIBILITY TO HAVE THE APPROPRIATE UTILITY COMPANY FIELD-LOCATE ANY UTILITY INSTALLATIONS WHICH MIGHT BE AFFECTED BY CONSTRUCTION PRIOR TO BEGINNING WORK IN THAT AREA. THE CONTRACTOR SHALL BE RESPONSIBLE FOR MAINTAINING SERVICE OF EXISTING UTILITIES AND FOR RESTORING ANY UTILITIES DAMAGED DUE TO CONSTRUCTION AT NO ADDITIONAL COST TO THE OWNER. 6.THE CONTRACTOR SHALL BE RESPONSIBLE FOR SECURING SOURCES FOR GRANULAR MATERIAL, DISPOSAL SITES, AND ANY ADDITIONAL MATERIAL THAT MAY BE NECESSARY FOR PROPER CONSTRUCTION OF THIS PROJECT. 7.IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO MAKE ARRANGEMENTS FOR WATER REQUIRED FOR TESTING, COMPACTION AND DUST CONTROL MEASURES. 8.ROCK EXCAVATION MAY BE ENCOUNTERED DURING UTILITY CONSTRUCTION. EVERY EFFORT WAS MADE TO REDUCE UTILITY DEPTH WHILE STILL MEETING REGULATORY REQUIREMENTS. FOR BIDDING PURPOSES CONTACT OWNER FOR TEST HOLE DEPTH OF ROCK. 9.DEMOLITION IS REQUIRED ON THIS PROJECT PRIOR TO JOB START. CONTRACTOR/BIDDER TO WALK JOB AND IDENTIFY DEMOLITION WORK PRIOR TO BIDDING. 10.ALL UTILITY MAIN LINES (WATER, SANITARY SEWER AND STORM DRAINAGE) WITHIN PUBLIC STREETS WILL BE OWNED AND MAINTAINED BY THE CITY AND CONSTRUCTED TO CURRENT CITY OF REXBURG STANDARD DRAWINGS AND SPECIFICATIONS; INSPECTED AND CERTIFIED BY AN ENGINEER, LICENSED IN THE STATE OF IDAHO; AND HAVE “AS-BUILT” DRAWINGS PROVIDED TO THE CITY ENGINEER. FAILURE TO COMPLY WITH THE REQUIREMENTS OF THIS PLAN MAY RESULT IN THE CITY'S WITHHOLDING OF BUILDING PERMITS, CERTIFICATE OF OCCUPANCY, AND WATER OR ELECTRICAL SERVICE. 11.LANDSCAPING SIGNS NOT TO EXCEED 3 FEET IN HEIGHT IN THE CLEAR SIGHT TRIANGLE. 12.THERE SHALL BE A 15-FOOT WIDE PUBLIC UTILITY EASEMENT WITHIN EACH LOT ALONG ALL ROAD/STREET FRONTAGES FOR POWER, PHONE, CABLE, GAS, ETC. (GAS REQUIRES SEPARATE TRENCH). THE EXACT LOCATION OF TRANSFORMERS AND PHONE BOXES WILL BE FIELD DETERMINED BY EACH UTILITY COMPANY AFTER ROADS/STREETS HAVE BEEN CONSTRUCTED TO SUBGRADE AND SIDE SLOPES HAVE BEEN COMPLETED. 13.ALL FRONTAGE PUBLIC UTILITY EASEMENTS (PUE) SHALL BE 15 FEET FROM BACK OF SIDEWALK UNLESS NOTED OTHERWISE. 14.LUMEN/CENTURY LINK/SPARKLIGHT USES THE SAME TRENCH AS ROCKY MOUNTAIN POWER AND REQUIRES CONDUITS (CONTRACTOR SHALL NOTIFY ALL FOR SCHEDULING). POWER DESIGN SHOWN IS PRELIMINARY AND ANY CONSTRUCTION STAKING OF POWER SHALL BE CONFIRMED WITH ROCKY MOUNTAIN POWER FOR FINAL LAYOUT. VERIFY CONDUIT SIZE MEETING ROCKY MOUNTAIN POWER DESIGN PRIOR TO CONSTRUCTION. 15.ALL UTILITIES INCLUDING POWER, PHONE, CABLE, ETC. EXCEPT NATURAL GAS MAY BE IN THE SAME TRENCH. NATURAL GAS MUST BE IN A SEPARATE TRENCH. 16.A 12” SPACING SHALL BE REQUIRED BETWEEN DIFFERENT UTILITIES IN THE SAME TRENCH. 17.CONTRACTOR SHALL CONTACT DIG-LINE AT 811, (800) 342-1585 OR (208) 342-1585 PRIOR TO ANY UTILITY CONSTRUCTION. WATER NOTES: 1.ALL WATER MAINS, SERVICES, AND ALL APPURTENANCES SHALL MEET CURRENT CITY OF REXBURG STANDARD DRAWINGS AND SPECIFICATIONS. THIS SHALL INCLUDE ALL MATERIALS, LABOR, AND INSTALLATION INCLUDING VERTICAL AND HORIZONTAL SEPARATION DISTANCES AND SLOPE REQUIREMENTS. 2.ALL WATER MAIN LINE SHALL BE CLASS 50 DUCTILE IRON MEETING AWWA C-151. 3.MINIMUM COVER OVER ALL WATER LINES SHALL BE 6 FEET. 4.WATER LINE SHALL HAVE A MINIMUM SEPARATION DISTANCE OF TEN (10) FEET FROM ANY SANITARY SEWER OR STORM SEWER MEASURED FROM THE OUTSIDE OF EACH PIPE AS OUTLINED IN THE ISPWC 2020 STANDARD DRAWING SD-407. CROSS AT APPROXIMATELY RIGHT ANGLES WITH FULL PIPE SECTIONS AND MINIMUM OF 1.5 FEET OF VERTICAL SEPARATION. 5.THRUST BLOCKS SHALL BE PLACED AT ALL DIRECTION CHANGES FOR PRESSURE PIPE. 6.FIRE HYDRANTS SHALL HAVE TWO 2-1/2” DIAMETER HOSE NOZZLES AND ONE 4-1/2” DIAMETER HOSE NOZZLE PER CITY STANDARDS. 7.WATER AND SEWER SERVICE LINES ARE SHOWN AT APPROXIMATE LOCATIONS. CONTRACTOR TO CONTACT DIG LINE PRIOR TO ALL EXCAVATION AND FIELD VERIFY LOCATION AND WITH ARCHITECTURAL DRAWINGS (IF APPLICABLE) FOR ANY ADDITIONAL SERVICES REQUIRED. 8.WATER METERS AND PRESSURE REDUCING VALVES - SEE PLUMBING DRAWINGS FOR DETAILS. ALL PLUMBING SHALL MEET THE STATE OF IDAHO PLUMBING CODE. COMMERCIAL BUILDINGS SHALL REQUIRE THE WATER METERS TO BE INSTALLED ON THE INTERIOR AND MOUNTED IN A HORIZONTAL POSITION WITHIN A HEATED MECHANICAL ROOM. 9.CONTRACTOR SHALL INSTALL FIRE LINES/SPRINKLERS MEETING THE CURRENT VERSION OF THE INTERNATIONAL FIRE CODE AND SHALL INCLUDE ALL APPURTENANCES (IF APPLICABLE). 10.IT IS THE RESPONSIBILITY OF THE OWNER TO PROVIDE AND INSTALL ALL REQUIRED BACKFLOW PREVENTION DEVICES ON WATER SERVICES. 11.ALL WATER MAINS AND APPURTENANCES SHALL BE TESTED FOR PRESSURE, LEAKAGE, AND BACTERIA MEETING CITY AND AWWA STANDARDS AND SHALL BE CLEANED AND DISINFECTED PRIOR TO ACCEPTANCE BY THE CITY FOR DOMESTIC USE. TESTING AND DISINFECTION OF WATER MAINS AND APPURTENANCES SHALL BE IN ACCORDANCE WITH AWWA C651 STANDARDS. AWWA STANDARDS REQUIRE EACH STREET TO BE TESTED INDIVIDUALLY FOR PRESSURE, LEAKAGE, AND BACTERIA. STORM SEWER NOTES: 1.ALL STORM SEWER SHALL MEET CURRENT CITY OF REXBURG STANDARD DRAWINGS AND SPECIFICATIONS. THIS SHALL INCLUDE ALL MATERIALS, LABOR, AND INSTALLATION INCLUDING VERTICAL AND HORIZONTAL SEPARATION DISTANCES AND SLOPE REQUIREMENTS. 2.SEPARATION REQUIREMENTS: WATER LINE SHALL HAVE A MINIMUM SEPARATION DISTANCE OF TEN (10) FEET FROM ANY SANITARY SEWER OR STORM SEWER MEASURED FROM THE OUTSIDE OF EACH PIPE AS OUTLINED IN THE ISPWC 2020 STANDARD DRAWING SD-407, CROSS AT APPROXIMATELY RIGHT ANGLES WITH FULL PIPE SECTIONS, AND MINIMUM OF 1.5 FEET OF VERTICAL SEPARATION. 3.STORM DRAIN PIPE SHALL MEET ONE OF THE FOLLOWING: PVC SDR 35 MEETING THE REQUIREMENTS OF ASTM D 3034 FOR DIAMETERS 18” OR LESS, ASTM F 679 FOR DIAMETERS 18” OR GREATER, PVC RIBBED PIPE MEETING THE REQUIREMENTS OF ASTM F 794 MEETING THE CURRENT CITY OF REXBURG STANDARD SPECIFICATIONS AND DRAWINGS. 4.CONTRACTOR SHALL PERFORM TESTING AND CLEANING OF SEWER MAINS MEETING CITY STANDARDS. SANITARY SEWER NOTES: 1.ALL SEWER MAIN SHALL BE PVC SDR 35 IN ACCORDANCE WITH ASTMD3034 WATER MAIN AND SERVICE SHALL MEET CURRENT CITY OF REXBURG STANDARD DRAWINGS AND SPECIFICATIONS. THIS SHALL INCLUDE ALL MATERIALS, LABOR, AND INSTALLATION INCLUDING VERTICAL AND HORIZONTAL SEPARATION DISTANCES AND SLOPE REQUIREMENTS. 2.SEPARATION REQUIREMENTS: WATER LINE SHALL HAVE A MINIMUM SEPARATION DISTANCE OF TEN (10) FEET FROM ANY SANITARY SEWER OR STORM SEWER MEASURED FROM THE OUTSIDE OF EACH PIPE AS OUTLINED IN THE ISPWC 2020 STANDARD DRAWING SD-407, CROSS AT APPROXIMATELY RIGHT ANGLES WITH FULL PIPE SECTIONS, AND MINIMUM OF 1.5 FEET OF VERTICAL SEPARATION. 3.CONTRACTOR SHALL PERFORM TESTING AND CLEANING OF SEWER MAINS MEETING CITY STANDARDS. BTM BOTTOM BLDG BUILDING CB CATCH BASIN CL CENTERLINE CONC CONCRETE DIA DIAMETER ELEV ELEVATION EO EDGE OF OIL EX EXISTING FH FIRE HYDRANT FL FLOW LINE FW FACE OF WALK HORZ HORIZONTAL HP HIGH POINT IFS CITY OF IDAHO FALLS STANDARDS INV INVERT LF LINEAR FEET LP LOW POINT MAX MAXIMUM MH MANHOLE MIN MINIMUM MX MATCH EXISTING OSHA OCCUPATIONAL SAFETY & HEALTH ADMINISTRATION PC POINT OF CURVATURE PT POINT OF TANGENT P.U.E.PUBLIC UTILITY EASEMENT PVC POLYVINYL CHLORIDE REQ'D REQUIRED MH MANHOLE SD STORM DRAIN SSMH SANITARY SEWER MANHOLE STA STATIONING TBC TOP BACK OF CURB TBRC TOP BACK RIBBON CURB TYP TYPICAL VERT VERTICAL VG VALLEY GUTTER EX EXISTING XG EXISTING GROUND ABBREVIATIONS: DESCRIPTION PRESSURE LINE (WATER LINE) SANITARY SEWER MAIN LINETYPE GAS LINE FENCE LINE GAS UGP OHP UNDERGROUND POWER LINE OVERHEAD POWER LINE TELEPHONE LINE FIBER OPTICFO PROPOSED/EXISTING ELEVATION PROPOSED/EXISTING FIRE HYDRANT PROPOSED/EXISTING VALVE PROPOSED/EXISTING CURB AND GUTTER PROPOSED/EXISTING STREET LIGHT PROPOSED/EXISTING POWER POLE EXIST.PRO.DESCRIPTION PROPOSED/EXISTING MANHOLE PROPOSED/EXISTING STORM DRAIN INLET PROPOSED ASPHALT DRAINAGE FLOW ARROW LEGEND 0.75% BOUNDARY LINE CENTERLINE SECTION LINE CONCRETE EXISTING GROUND CONTOUR4727 8" W ( 8" SS TBC 72.1 0 XG = 7 2 . 1 0 PROJECT MANAGER..............................................................................KURT ROLAND...................................................(208) 542-2665 OFFICE PROJECT ENGINEER...............................................................................PAUL SNARR......................................................(208) 542-2665 CITY ENGINEER......................................................................................KEITH DAVIDSON...............................................(208) 359-3020 PROJECT CONTACTS: PUBLIC UTILITY EASEMENT STORM DRAIN MAIN ( 12" SD IDAHO DEPARTMENT OF ENVIRONMENTAL QUALITY (DEQ) ...............CARLIN FEISTHAMEL, PE ...................................(208) 582-2650 RIP-RAP DIGLINE (CALL BEFORE YOU DIG).....................................................................................................................................(800) 342-1585 MADISON FIRE DEPARTMENT................................................................STAN CRITTENDEN............................................(208) 359-3010 PROPOSED LIP DOWN 18" CURB & GUTTER GRADE BREAKGBGB PROPOSED WATER METER BOX EG EG EG EG EG EG EG EG EO EOEOEOEO EO EO EO EO EO EO EO EO EO EO EO EO FL FL FL FL FL FL FL FL FL FLFLFLFLFLFLFLFLFLFLFL FL FL FL FL FL FL FL FL FL FL FL FL FL FL FL FL FL TO E TO E TO E TO E TO E TO E TO E TO E TO E TOE TO E TO E TO E TO E TO E TO E TO E TO E TO E TO E TO E TO E TO E TO E TO E TO E TO E TO E TO E TO E UGP UGP UGP UGP UGP UGP UGP UG P UG P UG P OH P O H P OH P OH P OH P OH P OH P OH P OH P OH P OH P OH P OH P OH P OHP OHP OHP OHP OHP OHP OHP OHP OHP OHP OHP OHP OHP TOE TOE TOE TOP TOP TOP TOP TOP TOP (8''SS (8''SS (8''SS (8''SS (8''SS (8''SS 8''W 8''W 8''W 8''W 8''W 8''W 8''W 8''W 8''W 8''W 8''W 8''W W6' ' P S 6' ' P S 6' ' P S 6' ' P S 6' ' P S 6' ' P S 6' ' P S 6' ' P S 6' ' P S 6' ' P S 6' ' P S 6' ' P S 6' ' P S 6' ' P S 6' ' P S EG EG EG EG EG EG EG EG EO EOEOEOEO EO EO EO EO EO EO EO EO EO EO EO EO FL FL FL FL FL FL FL FL FL FLFLFLFLFLFLFLFLFLFLFL FL FL FL FL FL FL FL FL FL FL FL FL FL FL FL FL FL TO E TO E TO E TO E TO E TO E TO E TO E TO E TOE TO E TO E TO E TO E TO E TO E TO E TO E TO E TO E TO E TO E TO E TO E TO E TO E TO E TO E TO E TO E UGP UGP UGP UGP UGP UGP UGP UG P UG P UG P OH P O H P OH P OH P OH P OH P OH P OH P OH P OH P OH P OH P OH P OH P OHP OHP OHP OHP OHP OHP OHP OHP OHP OHP OHP OHP OHP TOE TOE TOE TOP TOP TOP TOP TOP TOP (8''SS (8''SS (8''SS (8''SS (8''SS (8''SS 8''W 8''W 8''W 8''W 8''W 8''W 8''W 8''W 8''W 8''W 8''W 8''W W6' ' P S 6' ' P S 6' ' P S 6' ' P S 6' ' P S 6' ' P S 6' ' P S 6' ' P S 6' ' P S 6' ' P S 6' ' P S 6' ' P S 6' ' P S 6' ' P S 6' ' P S EA S T E R N I D A H O R A I L R O A D TREJO STREET SO U T H Y E L L O W S T O N E H I G H W A Y 50. 2 8 ' T O C L O F R A I L 100 ' R A I L R O A D R I G H T - O F - W A Y 70 ' RO W 11' PU B L I C W A L K E A S E M E N T 58 9 . 8 4 ' 15.02' L1 L2 OVERHEAD POWER TO BE RELOCATED. COORDINATE RELOCATION WITH ROCKY MOUNTAIN POWER. OVERHEAD POWER TO BE RELOCATED. COORDINATE RELOCATION WITH ROCKY MOUNTAIN POWER. OVERHEAD POWER TO BE RELOCATED. COORDINATE RELOCATION WITH ROCKY MOUNTAIN POWER. ABANDON WELL REMOVE ALL ASPHALT AND CONCRETE REMOVE CONCRETE AND FRENCH DRAIN SYSTEM ABANDON AND BACKFILL IRRIGATION DITCH ABANDON AND BACKFILL IRRIGATION DITCH ABANDON AND BACKFILL IRRIGATION DITCH ABANDON AND BACKFILL IRRIGATION DITCH ABANDON AND BACKFILL IRRIGATION DITCH REMOVE DIRT MOUND REMOVE/RELOCATE GRAVEL DRIVE TO ADJACENT PROPERTY 485 9 4858 4859 4859 4859 4859 4859 4860 48 6 0 4860 4 8 5 9 4 8 6 0 4 8 6 1 4861 4862 4863 4864 485 9 4860 TREJO S T R E E T Fi l e L o c a t i o n : z: \ p r o j e c t s \ 2 0 2 2 \ 2 2 1 2 5 m a d i s o n s t a t i o n a p a r t m e n t s \ 3 . 0 d e s i g n \ 3 . 1 c a d \ 3 . 1 3 f i n a l \ 2 2 1 2 5 d e m o p l a n . d w g Pl o t t e d B y : ru s s e l l Da t e P l o t t e d : We d n e s d a y , M a r c h 2 2 2 0 2 3 a t 0 3 : 2 7 P M 3 C- 1 EX I S T I N G C O N D I T I O N S & D E M O L I T I O N P L A N AG L E R O C K N G I N E E R I N G SU R V E Y E D B Y : DR A W N B Y : PR O J E C T N O . AP P R O V E D B Y : DE S C R I P T I O N DA T E RE V I S I O N S 1 2 3 4 5 6 AT T E N T I O N Th i s d o c u m e n t o r a n y p a r t t h e r e o f i n d e t a i l o r d e s i g n c o n c e p t is t h e p r o p e r t y o f E a g l e R o c k E n g i n e e r i n g a n d s h a l l n o t b e co p i e d i n a n y f o r m w i t h o u t t h e w r i t t e n a u t h o r i z a t i o n o f E a g l e Ro c k E n g i n e e r i n g . E SH E E T N O . SH E E T N A M E CI V I L P L A N N I N G S U R V E Y I N G ID A H O F A L L S ( 2 0 8 ) 5 4 2 - 2 6 6 5 RE X B U R G ( 2 0 8 ) 3 5 9 - 2 6 6 5 PR E P A R E D F O R : RY A N N E L S O N MA D I S O N S T A T I O N A P A R T M E N T S A. S N A R R R. J O R D A N P. S N A R R 22 1 2 5 P R E L I M I N A R Y N O T A P P R O V E D F O R C O N S T R U C T I O N 16 4 1 0 W E S N 040'40'20' SCALE: 1" = 40' 1.INSERT SHEET NOTES HERE. SHEET NOTES: 1.INSERT KEYNOTES HERE. KEYNOTES: EA S T E R N I D A H O R A I L R O A D EA S T E R N I D A H O R A I L R O A D TO E TO E TO E TO E TO E TO E TO E TO E TO E TOE TO E TO E TO E TO E TO E TO E TO E TO E TO E TO E TO E TO E TO E TO E TO E TO E TO E TO E TO E TO E UGP UGP UGP UGP UGP UGP UGP UG P UG P UG P (8''SS (8''SS (8''SS (8''SS (8''SS (8''SS 8''W 8''W 8''W 8''W 8''W 8''W 8''W 8''W 8''W 8''W 8''W 8''W W6' ' P S 6' ' P S 6' ' P S 6' ' P S 6' ' P S 6' ' P S 6' ' P S 6' ' P S 6' ' P S 6' ' P S 6' ' P S 6' ' P S 6' ' P S 6' ' P S 6' ' P S N0 0 ° 1 5 ' 5 5 " W 1 5 1 . 6 8 ' C1 C2 62.05' C 3 S30 ° 0 8 ' 1 8 " W 9 5 9 . 9 1 ' ( M ) 9 6 0 . 1 4 ' ( R ) S89°47'35"W 590.00' (M) 591.00' (R) EA S T E R N I D A H O R A I L R O A D TREJO STREET SO U T H Y E L L O W S T O N E H I G H W A Y N0 0 ° 1 6 ' 0 5 " W 6 0 4 . 8 6 ' ( M ) 6 0 5 . 0 0 ' ( R ) N89°47'52"E 599.99' TO E TO E TO E TO E TO E TO E TO E TO E TO E TOE TO E TO E TO E TO E TO E TO E TO E TO E TO E TO E TO E TO E TO E TO E TO E TO E TO E TO E TO E TO E UGP UGP UGP UGP UGP UGP UGP UG P UG P UG P (8''SS (8''SS (8''SS (8''SS (8''SS (8''SS 8''W 8''W 8''W 8''W 8''W 8''W 8''W 8''W 8''W 8''W 8''W 8''W W6' ' P S 6' ' P S 6' ' P S 6' ' P S 6' ' P S 6' ' P S 6' ' P S 6' ' P S 6' ' P S 6' ' P S 6' ' P S 6' ' P S 6' ' P S 6' ' P S 6' ' P S (1 2 ' ' S D (1 2 ' ' S D (1 2 ' ' S D (1 2 ' ' S D 8' ' W 8' ' W 8' ' W 8' ' W 8' ' W 8' ' W 8' ' W 8' ' W 8''W 8''W 8''W 8''W 8''W 8''W 8''W 8''W (12''SD (12''SD (12''SD 8''W 8''W 8''W 8''W 8''W 8''W 8''W 8''W 8''W (8' ' S S (8' ' S S (8' ' S S (8' ' S S (8' ' S S (8' ' S S (8' ' S S 8''W 8''W 8''W 8''W 8''W 8''W 8''W 8''W 8''W 8''W 8''W 8''W 8' ' W 8 ' ' W 8' ' W 8' ' W 8''W 8''W 8''W 8''W 8''W 8''W 8''W 8''W 8''W 8''W 12''SD) 8''W 8'' W 8'' W 8' ' W (8''SS (8''SS (8 ' ' S S (8''SS 12 ' ' S D ) 6' ' S S 6' ' S S 2' ' W S 6' ' F S 6' ' F S 4''SS 4''S S 2''W S 2''W S 2''FS 2''FS GB GB G B GB GB GB GB GB GB GB GB GB GB GB GB GB GB GB GB 12 ' ' S D ) GB GB GB GB GB GB GB GB GB G B 8' ' S S ) 8' ' S S ) 8' ' S S ) 8' ' S S ) (8''SS (8''SS (8''SS (8''SS 6' ' F S 6' ' F S 2' ' W S 2' ' W S G B G B GB GB 6''S S 6''S S 6''F S2'' W S 6''S S 6''S S 6''FS 6''F S 2''W S 2''W S6''S S 6' ' S S 6' ' S S 2' ' W S 6' ' F S 6' ' F S 2' ' W S 2' ' W S 6' ' F S 6' ' F S 6''FS2''WS 6''SS 6''SS 6''SS 6''SS 6' ' F S 2' ' W S FO FO FO FOFO FO FO FO FO 12' ' S D ) 6''F S2'' W S 6''F S 6''F S 2'' W S 2'' W S 1 2 ' ' S D ) 8''W 8' ' S S ) 8' ' S S ) 8' ' S S ) 8' ' S S ) 8''SS ) (8''SS (8''SS (8''SS (8''SS (8''SS (8''SS 6' ' S S 6' ' S S 6' ' S S STORM POND 1 FOUND ALUMINUM CAP EAST QUARTER CORNER SECTION 25, TOWNSHIP 6 NORTH, RANGE 39 EAST, BOISE MERIDIAN CPF NO. 429712 FOUND ALUMINUM CAP SOUTH QUARTER CORNER SECTION 25, TOWNSHIP 6 NORTH, RANGE 39 EAST, BOISE MERIDIAN CPF NO. 408707 1 1 1 1 1 2 3 4 7 BLDG FF: 61.70 BLDG FF: 62.10 BLDG FF: 62.80 BLDG FF: 61.70 BLDG FF: 62.40 BLDG FF: 61.30 BLDG FF: 62.20 BLDG FF: 62.70 BLDG FF: 63.00 CLUBHOUSE BLDG FF: 62.75 BLDG FF: 61.00 2 3 5 5 5 2 11 3 3 2 2 7 2 2 2 7 5 6 65 49 9 7 1 1 1 1 1 1 1 1 1 1 1 2 2 2 1 1 1 1 1 3 2 4 4 9 8 9 9 STORM POND 2 2 3 2 8 10' 10' 8 DEVELOPMENT SIGN 3 2 7 10 6 5 9 7 4 4 10 6 5 8 8 9 4 6 6 5 5 6 5 5 2 2 2 2 3 2 3 4 5610105 6 5 9 8 2 19 ' 24 . 7 5 ' 19 ' 19'19'26' 19 ' 24 ' 18 . 5 ' 18 . 5 ' 19 ' 24 ' 19 ' 24 . 7 5 ' 19 ' 19' 19' 26' 20 ' 24 ' 20 ' 93. 6 ' 91 . 3 8 ' 91 . 7 9 ' 6 5 10 9 3 4 7 7 9 10 3 2 9 3 5 7 2 9 10 3 9 10 3 9 10 3 5 5 5 2 2 3 3 3 2 11' P A T H W A Y E A S E M E N T 11' P A T H W A Y E A S E M E N T 3 11 2 11 3 2 2 11 3 3 5 2 7 2 7 9 10 3 3 2 2 5 9 10 3 5 3 2 5 2 7 3 4 11 7 4 2 8"x6" REDUCER 9 10 3 6 5 11 2 4 7 3 2 2 5 5 5 7 7 5 2 2 3 9 10 3 9 10 3 9 1 5 2 CONNECT NEW 8" WATER MAIN AND NEW 8" SANITARY SEWER TO EXISTING SERVICES (SEE PP-8 FOR CONNECTION) 1 2 5 7 1 25 ' 25 ' 1 1 1 5 5 4 4 4 1 1 1 4 8 4 5 9 8 9 9 8 9 8 9 9 8 9 9 9 4 2 PLUG AND THRUST BLOCK 8" WATERLINE AT PROPERTY LINE (SEE GENERAL NOTE 1 THIS SHEET FOR CONNECTIVITY TO SOUTH) CAP 8" SANITARY SEWER STUB AT PROPERTY LINE SEE GENERAL NOTE 2 THIS SHEET 5 Fi l e L o c a t i o n : z: \ p r o j e c t s \ 2 0 2 2 \ 2 2 1 2 5 m a d i s o n s t a t i o n a p a r t m e n t s \ 3 . 0 d e s i g n \ 3 . 1 c a d \ 3 . 1 3 f i n a l \ 2 2 1 2 5 o v e r a l l s i t e p l a n . d w g Pl o t t e d B y : ru s s e l l Da t e P l o t t e d : We d n e s d a y , M a r c h 2 2 2 0 2 3 a t 0 3 : 2 8 P M W E S N 040'40'20' SCALE: 1" = 40' 4 C- 2 OV E R A L L S I T E P L A N AG L E R O C K N G I N E E R I N G SU R V E Y E D B Y : DR A W N B Y : PR O J E C T N O . AP P R O V E D B Y : DE S C R I P T I O N DA T E RE V I S I O N S 1 2 3 4 5 6 AT T E N T I O N Th i s d o c u m e n t o r a n y p a r t t h e r e o f i n d e t a i l o r d e s i g n c o n c e p t is t h e p r o p e r t y o f E a g l e R o c k E n g i n e e r i n g a n d s h a l l n o t b e co p i e d i n a n y f o r m w i t h o u t t h e w r i t t e n a u t h o r i z a t i o n o f E a g l e Ro c k E n g i n e e r i n g . E SH E E T N O . SH E E T N A M E CI V I L P L A N N I N G S U R V E Y I N G ID A H O F A L L S ( 2 0 8 ) 5 4 2 - 2 6 6 5 RE X B U R G ( 2 0 8 ) 3 5 9 - 2 6 6 5 PR E P A R E D F O R : RY A N N E L S O N MA D I S O N S T A T I O N A P A R T M E N T S A. S N A R R R. J O R D A N P. S N A R R 22 1 2 5 P R E L I M I N A R Y N O T A P P R O V E D F O R C O N S T R U C T I O N 16 4 1 0 ASPHALT PAVING PER DETAIL 9 ON SHEET D-1. SEWER MANHOLE TYPE A PER LATEST REVISION OF CITY OF REXBURGSTANDARDS. SEE DETAIL X ON SHEET D-X. 4" SANITARY SEWER SERVICE PER LATEST REVISION OF CITY OF REXBURG STANDARDS.SEE PLAN & PROFILE SHEETS FOR LOCATIONS. (CLUBHOUSE) WATER MAIN VALVE AND VALVE BOX MEETING WATER MAIN SIZE PER LATEST REVISION OF CITY OF REXBURG STANDARDS. FIRE HYDRANT ASSEMBLY PER CITY OF REXBURG STANDARDS. SEE DETAIL 5 ON SHEET D-1. 1.5' LIP UP CURB PER DETAIL 7 ON SHEET D-1. INSTALL STORM DRAIN MANHOLE PER CITY OF REXBURG STANDARDS. 8"x8" TEE WITH THRUST BLOCK. SEE PLAN & PROFILE SHEETS FOR LOCATIONS. PAVING AND DRAINAGE CONSTRUCTION ITEMS SEWER CONSTRUCTION ITEMS 1 2 4 6 INSTALL ADA RAMP AND TRUNCATED DOMES PER CITY OF REXBURG STADARDS. 1 2 WATER CONSTRUCTION ITEMS 5 CATCH BASIN PER DETAIL 1 ON SHEET D-2. 1 2 3 4 5 7 8"x6" TEE WITH THRUST BLOCK. SEE PLAN & PROFILE SHEETS FOR LOCATIONS. 8 3 9 6' SIDEWALK PER CITY OF REXBURG STANDARDS. 6 7 BEND (ANGLE PER PLAN) WITH THRUST BLOCK. SEE PLAN & PROFILE SHEETS FOR LOCATIONS. 8 8"x4" TEE WITH THRUST BLOCK. SEE PLAN & PROFILE SHEETS FOR LOCATIONS. 10 9 10 PLUG AND THRUST BLOCK. SEE PLAN & PROFILE SHEETS FOR LOCATIONS. 1.5' LIP DOWN CURB PER DETAIL 8 ON SHEET D-1. 5' SIDEWALK PER CITY OF REXBURG STANDARDS. TRASH ENCLOSURE PER CITY OF REXBURG STANDARDS. INSTALL SC-740 INFILTRATION SYSTEM. SEE STORM TABLES ON SHEET C-4 FOR SYSTEM SPECIFICATIONS. SEE DETAIL 6 ON SHEET D-2. 6" SANITARY SEWER SERVICE PER LATEST REVISION OF CITY OF REXBURG STANDARDS.TYPICAL ON ALL APARTMENT BUILDINGS. SEE PLAN & PROFILE SHEETS FOR LOCATIONS.3 2" WATER SERVICE PER CITY OF REXBURG STANDARDS. WATER METER TO BEINSTALLED IN ACCORDANCE WITH STANDARD DRAWING 16. 6" FIRE SERVICE LINE PER CITY OF REXBURG STANDARDS TO MECHANICAL ROOM PERJRW ARCHITECTURAL PLANS. 8' ASPHALT WALKING PATH 10' ASPHALT WALKING PATH (SEE SHEET D-1 DETAIL 6) SAW-CUT EXISTING CURB & GUTTER FOR COMMERCIAL APPROACH PER CITY OF REXBURG STANDARDS CONNECT NEW 8" SS LINE TO EXISTING SSMH (SEE PP-1 FOR CONNECTION) CITY UTILITY MAP SHOWS A SERVICE STUBBED TO LOT. SERVICE SIZE IS NOT KNOWN AT THE TIME OF THIS DESIGN. IF EXISTING STUB IS NOT 8" IT SHALL BE REQ'D TO TIE NEW LINE BACK TO THE EXISTING WATER MAIN. TREJO S T R E E T GENERAL NOTES: 1.68' RIGHT-OF-WAY STREET CONNECTIVITY TO THE SOUTH SHALL BE CONSTRUCTED BY THE DEVELOPER PER THE DEVELOPMENT AGREEMENT. 2.AT THE TIME OF STREET CONNECTIVITY TO THE SOUTH OCCURS 3 PARKING STALLS SHALL BE ADDED IN THE SOUTH EAST CORNER AT THE LOCATION OF THE EMERGENCY ACCESS TO MEET THE REQUIRED PARKING FOR APARTMENTS. (SEE DEVELOPMENT AGREEMENT) APARTMENT COUNT 1 BEDROOM UNITS: 24 UNITS PER BUILDING (240 TOTAL) 2 BEDROOM UNITS: 12 UNITS PER BUILDING (120 TOTAL) BUILDING TOTALS: 36 UNITS PER BUILDING (360 TOTAL) PROPOSED USE: RESIDENTIAL APARTMENTS PROJECT AREA: 12.756 ACRES ZONE: HDR1 PARKING STALLS REQUIRED: 600 PARKING STALLS PROVIDED: 605 HANDICAP PARKING STALLS: 16 COMPACT STALLS: 116 (25%) LANDSCAPE AREA: 4.226 ACRES ASPHALT AREA: 4.250 ACRES (ASPHALT WALKWAY: 0.220 ACRES) INSTALL FIBER CONDUIT PER CITY OF REXBURG STANDARDS. COORDINATE DISTRIBUITION BOX LOCATION WITH CITY OF REXBURG BREAK AWAY BOLLARD 11 TRANSITION CURB LIP UP TO LIP DOWN. 2" FIRE SERVICE LINE (CLUBHOUSE) PER CITY OF REXBURG STANDARDS TOMECHANICAL ROOM WITH REMOTE READOUT PER JRW ARCHITECTURAL PLANS. PIONEE R V I L L A G E LOT 1 B L O C K 1 WESTA T E S S U B D I V I S I O N N O . 1 LOT 4 B L O C K 2 WESTA T E S S U B D I V I S I O N N O . 1 LOT 3 B L O C K 2 TRANSITION FROM 8' WALKING PATH TO 10' ASPHALT WALKING PATH (SEE SHEET D-1 DETAIL 6) 120' DE C E L & S T O R A G E L E N G T H 63' SHIFTIN G T A P E R SEE TABLE 1 FOR TURNING LENGTHS AND NOTE 3 REGARDING THE ACCESS THROAT LENGTH FUTURE R.O.W., WIDTH TO BE DETERMINED AT TIME ACCESS IS NEEDED TO E TO E TO E TO E TO E TO E TO E TO E TO E TOE TO E TO E TO E TO E TO E TO E TO E TO E TO E TO E TO E TO E TO E TO E TO E TO E TO E TO E TO E TO E UGP UGP UGP UGP UGP UGP UGP UG P UG P UG P (8''SS (8''SS (8''SS (8''SS (8''SS (8''SS 8''W 8''W 8''W 8''W 8''W 8''W 8''W 8''W 8''W 8''W 8''W 8''W W N0 0 ° 1 5 ' 5 5 " W 1 5 1 . 6 8 ' C1 C2 62.05' C 3 S30 ° 0 8 ' 1 8 " W 9 5 9 . 9 1 ' ( M ) 9 6 0 . 1 4 ' ( R ) S89°47'35"W 590.00' (M) 591.00' (R) EA S T E R N I D A H O R A I L R O A D TREJO STREET SO U T H Y E L L O W S T O N E H I G H W A Y N0 0 ° 1 6 ' 0 5 " W 6 0 4 . 8 6 ' ( M ) 6 0 5 . 0 0 ' ( R ) N89°47'52"E 599.99' TO E TO E TO E TO E TO E TO E TO E TO E TO E TOE TO E TO E TO E TO E TO E TO E TO E TO E TO E TO E TO E TO E TO E TO E TO E TO E TO E TO E TO E TO E UGP UGP UGP UGP UGP UGP UGP UG P UG P UG P (8''SS (8''SS (8''SS (8''SS (8''SS (8''SS 8''W 8''W 8''W 8''W 8''W 8''W 8''W 8''W 8''W 8''W 8''W 8''W W (1 2 ' ' S D (1 2 ' ' S D (1 2 ' ' S D (1 2 ' ' S D (12''SD (12''SD (12''SD 12''SD) 12 ' ' S D ) GB GB G B GB GB GB GB GB GB GB GB GB GB GB GB GB GB GB GB 12 ' ' S D ) GB GB GB GB GB GB GB GB GB G B G B G B GB GB FO FO FO FOFO FO FO FO FO 12' ' S D ) 1 2 ' ' S D ) 1 2 3 4 56 STORM POND 1 (SNOW STORAGE AREA) TOP: 4857.80 (16923 SQFT) CAPACITY TOP: 4857.20 (14408 SQFT) BTM: 4853.60 (2686 SQFT) TBC: 59.57 TBC: 59.52 TBC: 59.30 TBC: 60.20 TBC: 60.53 TBC: 61.20 TBC: 60.53 TBC: 60.20 TBC: 59.30 TBC: 59.68 TBC: 59.74 TBC/LP: 58.75 TBC: 59.15 TBC: 59.27 TBC: 60.46 TBC: 61.00 TBC: 59.22 TBC: 59.26 TBC: 59.55 TBC: 59.90 TBC: 60.70 TBC: 61.75TBC: 61.75 TBC: 61.40 TBC: 61.45 TBC: 60.40 STORM POND 2 (SNOW STORAGE AREA) TOP: 4858.75 (4540 SQFT) CAPACITY TOP: 4858.15 (3844 SQFT) BTM: 4855.15 (568 SQFT) TBC: 60.00 TBC: 59.85 TBC: 61.40 TBC/LP: 59.30 TBC: 60.00 TBC: 60.36 TBC: 60.36 TBC: 60.00 TBC/LP: 58.20 TBC: 59.80TBC: 59.80 TBC: 61.20 TBC: 60.50 TBC: 60.00 TBC: 58.80 TBC: 59.50 TBC: 59.70 TBC: 60.00TBC: 60.00 TBC: 60.00 TBC: 61.60 TBC: 61.60 TBC: 61.60 TBC: 61.00 WALK: 62.25 TBC: 61.00 TBC: 61.00 TBC: 60.64 TBC: 61.00 TBC: 61.00 TBC/LP: 58.74 TBC: 59.34 TBC: 59.61TBC: 59.70 TBC: 59.90 TBC: 60.70 TBC: 61.10TBC: 60.48TBC: 60.45 TBC: 59.14 TBC: 58.90 TBC: 58.20 TBC/LP: 57.80 TBC: 58.76 TBC: 58.80 TBC: 59.50 TBC: 58.50 TBC: 58.10 TBC: 58.90 TBC: 58.90 TBC: 57.80 TBC: 60.10 TBC: 61.30TBC: 58.90 TBC: 59.50 TBC: 58.90 TBC: 57.90 TBC: 57.65 TBC/LP: 57.20 TBC: 58.00 TBC: 59.10 TBC: 59.70 TBC: 59.30 TBC: 59.80 TBC: 59.20 TBC: 57.85 TBC: 57.75 TBC/LP: 57.50 TBC: 57.80 TBC/LP: 57.70 TBC: 58.10 TBC: 58.10 TBC: 59.35 TBC: 59.75 SDMH #1F CB #1F SDMH #1E SDMH #3 CB #1D CB # 1G CB #3 CB #1H CB #2 CB #1E SDMH #1B SDMH #4 SMDH #5 SDMH #1A CB #4 CB #5 SDMH #6 SDMH #1D CB #6A CB #6B SDMH #1C CB #1A CB #1C CB #1B TBC/LP: 59.40 TBC: 59.62 TBC: 59.66 TBC: 60.35 TBC: 60.35 TBC: 60.35 TBC: 58.30 OIL: 60.90OIL: 60.20 TBC: 60.70 TBC: 58.90 TBC/LP: 58.70 TBC: 58.81 TBC: 58.86 TBC: 59.60TBC: 58.70 TBC: 59.00 TBC: 59.10 TBC: 59.88 TBC: 60.00 TBC/LP: 59.60 TBC: 58.40 TBC: 58.48 TBC/LP: 57.80 TBC: 59.35 TBC: 59.75 TBC: 60.53 TBC: 60.56 TBC: 60.65 TBC: 59.10 TBC/LP: 58.20 TBC: 58.60 TBC: 60.00 TBC: 58.60 TBC: 58.50 TBC: 58.20 SDMH #3A CB #3A TBC: 59.60 TBC: 61.85 TBC: 61.20 TBC: 61.36 TBC: 61.26 TBC: 60.90 TBC: 60.93 TBC: 60.77 TBC: 61.04 TBC: 59.85 TBC: 59.80 TBC: 60.10 TBC: 60.20 TBC: 58.20 CB #1I TBC/HP: 4858.15 TBC: 61.55 TBC/HP: 4860.51 TBC: 60.46 TBC: 59.14 TBC: 61.45 TBC: 59.74 BLDG FF: 61.70 BLDG FF: 62.10 BLDG FF: 62.80 BLDG FF: 61.70 BLDG FF: 62.40 BLDG FF: 61.30 BLDG FF: 62.20 BLDG FF: 62.70 BLDG FF: 63.00 CLUBHOUSE BLDG FF: 62.75 BLDG FF: 61.00 Fi l e L o c a t i o n : z: \ p r o j e c t s \ 2 0 2 2 \ 2 2 1 2 5 m a d i s o n s t a t i o n a p a r t m e n t s \ 3 . 0 d e s i g n \ 3 . 1 c a d \ 3 . 1 3 f i n a l \ 2 2 1 2 5 g r a d i n g & s t o r m p l a n . d w g Pl o t t e d B y : ru s s e l l Da t e P l o t t e d : We d n e s d a y , M a r c h 2 2 2 0 2 3 a t 0 3 : 2 8 P M W E S N 040'40'20' SCALE: 1" = 40' 273934 SQFT STORM AREA: 5 C- 3 GR A D I N G & S T O R M P L A N AG L E R O C K N G I N E E R I N G SU R V E Y E D B Y : DR A W N B Y : PR O J E C T N O . AP P R O V E D B Y : DE S C R I P T I O N DA T E RE V I S I O N S 1 2 3 4 5 6 AT T E N T I O N Th i s d o c u m e n t o r a n y p a r t t h e r e o f i n d e t a i l o r d e s i g n c o n c e p t is t h e p r o p e r t y o f E a g l e R o c k E n g i n e e r i n g a n d s h a l l n o t b e co p i e d i n a n y f o r m w i t h o u t t h e w r i t t e n a u t h o r i z a t i o n o f E a g l e Ro c k E n g i n e e r i n g . E SH E E T N O . SH E E T N A M E CI V I L P L A N N I N G S U R V E Y I N G ID A H O F A L L S ( 2 0 8 ) 5 4 2 - 2 6 6 5 RE X B U R G ( 2 0 8 ) 3 5 9 - 2 6 6 5 PR E P A R E D F O R : RY A N N E L S O N MA D I S O N S T A T I O N A P A R T M E N T S A. S N A R R R. J O R D A N P. S N A R R 22 1 2 5 P R E L I M I N A R Y N O T A P P R O V E D F O R C O N S T R U C T I O N 16 4 1 0 1 70953 SQFT2 49033 SQFT3 39701 SQFT4 28911 SQFT5 44306SQFT6 LEGEND: DRAINAGE FLOW RIP-RAP 1.THE ADS STORM INFILTRATION SYSTEM SHOWN IS SIZED USING ADS TECH SC-740 CHAMBER SYSTEM. THE CHAMBER AREAS ARE SET FOR DESIGN OF EACH STORM AREA; HOWEVER THE LENGTHS AND WIDTHS MAY VARY TO MEET SEPARATION FROM OTHER UTILITIES OR CONSTRUCTION OBSTACLES. 2.CONTRACTOR TO SUPPLY AND SUBMIT FINAL ADS STORM TECH DRAWINGS AND SPECIFICATIONS (OR EQUAL SYSTEM) TO ENGINEER FOR APPROVAL PRIOR TO INSTALLATION. 3.CONTRACTOR TO INSTALL THE ADS STORM TECH SC-740 SYSTEM (OR EQUAL) WITH PRECAST 48" CONCRETE MANHOLE INLET AND OUTLET PER CITY OF REXBURG STANDARD DRAWINGS AND SPECIFICATIONS. ADS STORM INFILTRATION NOTES: 1.SEE STORM TABLES ON SHEET 6/C-4. NOTES: ADS SYSTEM 93'x16' (SEE TABLE 4) ADS SYSTEM 86'x16' (SEE TABLE 4) ADS SYSTEM 93'x11' (SEE TABLE 4) ADS SYSTEM 93'x16' (SEE TABLE 4) PROPOSED LIP DOWN 18" CURB & GUTTER PROPOSED LIP UP 18" CURB & GUTTER Fi l e L o c a t i o n : z: \ p r o j e c t s \ 2 0 2 2 \ 2 2 1 2 5 m a d i s o n s t a t i o n a p a r t m e n t s \ 3 . 0 d e s i g n \ 3 . 1 c a d \ 3 . 1 3 f i n a l \ 2 2 1 2 5 g r a d i n g & s t o r m p l a n . d w g Pl o t t e d B y : ru s s e l l Da t e P l o t t e d : We d n e s d a y , M a r c h 2 2 2 0 2 3 a t 0 3 : 2 8 P M 6 C- 4 ST O R M A R E A T A B L E S AG L E R O C K N G I N E E R I N G SU R V E Y E D B Y : DR A W N B Y : PR O J E C T N O . AP P R O V E D B Y : DE S C R I P T I O N DA T E RE V I S I O N S 1 2 3 4 5 6 AT T E N T I O N Th i s d o c u m e n t o r a n y p a r t t h e r e o f i n d e t a i l o r d e s i g n c o n c e p t is t h e p r o p e r t y o f E a g l e R o c k E n g i n e e r i n g a n d s h a l l n o t b e co p i e d i n a n y f o r m w i t h o u t t h e w r i t t e n a u t h o r i z a t i o n o f E a g l e Ro c k E n g i n e e r i n g . E SH E E T N O . SH E E T N A M E CI V I L P L A N N I N G S U R V E Y I N G ID A H O F A L L S ( 2 0 8 ) 5 4 2 - 2 6 6 5 RE X B U R G ( 2 0 8 ) 3 5 9 - 2 6 6 5 PR E P A R E D F O R : RY A N N E L S O N MA D I S O N S T A T I O N A P A R T M E N T S A. S N A R R R. J O R D A N P. S N A R R 22 1 2 5 P R E L I M I N A R Y N O T A P P R O V E D F O R C O N S T R U C T I O N 16 4 1 0 Madison Station Apartments Storm Volume - Average Coefficient Calculations Table 1 Rev 12/9/2022 Description Area Storm Runoff Storm (ft2)(in)Coefficient (ft3) Storm Area 1 273,934 1 1.0 22,828 Storm Area 2 70,953 1 1.0 5,913 Storm Area 3 49,033 1 1.0 4,086 Storm Area 4 39,701 1 1.0 3,308 Storm Area 5 28,911 1 1.0 2,409 Storm Area 6 44,306 1 1.0 3,692 Madison Station Apartments Storage Volume - Storm Ponds & Infiltration System Calculations ADS Storm Tech System SC-740 Storm Areas #3 Thru #6 Table 2 REV 12/9/2022 Description Req'd Storm Volume (ft³) Drainage Bed Length (ft) Storage Provided (ft³) Notes Storm Area 1 22,828 NA 25,796 Storm Pond Storm Area 2 5,913 NA 6,449 Storm Pond Storm Area 3 4,086 ADS 4,109 ADS Infiltration Storm Area 4 3,308 ADS 3,517 ADS Infiltration Storm Area 5 2,409 ADS 2,610 ADS Infiltration Storm Area 6 3,692 ADS 3,824 ADS Infiltration NOTES: 1. The storage provided are minimum system lengths to be installed and are calculated to contain storm water within the project site. Madison Station Storm Pond Calculations Table 3 Rev 1/11/23 Required Storm Volume: Area 1 Unit Quantity Total Site Area (15.782 Acres)ft²273,934 Storm Depth (1")ft 0.0833 Net Required Storm Pond Volume ft³22,828 Required Storm Volume: Area 2 Unit Quantity Total Site Area (15.782 Acres)ft²70,953 Storm Depth (1")ft 0.0833 Net Required Storm Pond Volume ft³5,913 Designed Storm Volume Area 1 Elev (ft) Area (ft²)Volume (ft³) Top Pond 4857.80 (CB Grate 4856.60 Low Point)4856.60 14,408 25,641Bottom Pond 4853.60 2,686 Mid Point Pond 4855.10 8,547 Designed Storm Volume Area 2 Elev (ft) Area (ft²)Volume (ft³) Top Pond 4858.75 (CB Grate 4858.15 Low Point)4858.15 3,844 6,618Bottom Pond 4855.15 568 Mid Point Pond 4856.65 2,206 NOTES: 1. Storm ponds to be excavated to free draining gravel and brought up to grade with drainage gravel to within approximately 1' prior to installing landscape dirt (landscape mix with minimal clay) and sod/grass seed or landscape rock. 2. Storm ponds to be maintained by the property owner or representative(s). Madison Station Apartments Madison Station Apartments Madison Station Apartments Madison Station Apartments Storm Area No 3 Storm Area No 4 Storm Area No 5 Storm Area No 6 Table 4 10/19/2022 Table 4 10/19/2022 Table 4 10/19/2022 Table 4 10/19/2022 System Inputs System Inputs System Inputs System Inputs Chamber Model (or equal)SC-740 Chamber Model (or equal)SC-740 Chamber Model (or equal)SC-740 Chamber Model (or equal)SC-740 Required Storage Volume 3905 CF Required Storage Volume 3308 CF Required Storage Volume 2409 CF Required Storage Volume 3692 CF Stone Porosity 40%Stone Porosity 40%Stone Porosity 40%Stone Porosity 40% Stone Foundation Depth 18"Stone Foundation Depth 18"Stone Foundation Depth 18"Stone Foundation Depth 18" Stone Above Chamber 18"Stone Above Chamber 12"Stone Above Chamber 12"Stone Above Chamber 12" Average Cover Over Chambers 18"Average Cover Over Chambers 18"Average Cover Over Chambers 18"Average Cover Over Chambers 18" System Volume and Bed Sizing System Volume and Bed Sizing System Volume and Bed Sizing System Volume and Bed Sizing Installed Storage Volume 4109 CF Installed Storage Volume 3517 CF Installed Storage Volume 2610 CF Installed Storage Volume 3824 CF Storage Volume/Chamber 45.90 CF Storage Volume/Chamber 45.90 CF Storage Volume/Chamber 45.90 CF Storage Volume/Chamber 45.90 CF Number of Chambers Required 35 ea Number of Chambers Required 32 ea Number of Chambers Required 23 ea Number of Chambers Required 35 ea Number of End Caps Required 6 ea Number of End Caps Required 6 ea Number of End Caps Required 4 ea Number of End Caps Required 6 ea Chamber Rows 3 Rows Chamber Rows 3 Chamber Rows 2 Chamber Rows 3 Maximum Length 93 ft Maximum Length 86 ft Maximum Length 93 ft Maximum Length 93 ft Maximum Width 16 ft Maximum Width 16 ft Maximum Width 11 ft Maximum Width 16 ft Approximate Bed Size 1430 SF Approximate Bed Size 1318 SF Approximate Bed Size 989 SF Approximate Bed Size 1430 SF System Components System Components System Components System Components Stone Required 232 CY Stone Required 190 CY Stone Required 144 CY Stone Required 206 CY Volume of Excavation (not including fill)292 CY Volume of Excavation (not including fill)245 CY Volume of Excavation (not including fill)184 CY Volume of Excavation (not including fill)265 CY Total Non-Woven Geotextile Required 541 SY Total Non-Woven Geotextile Required 487 SY Total Non-Woven Geotextile Required 403 SY Total Non-Woven Geotextile Required 527 SY Woven Geotextile Required (excluding Isolator Row)16 SY Woven Geotextile Required (excluding Isolator Row)16 SY Woven Geotextile Required (excluding Isolator Row)8 SY Woven Geotextile Required (excluding Isolator Row)16 SY Woven Geotextile Required (Isolator Row)58 SY Woven Geotextile Required (Isolator Row)54 SY Woven Geotextile Required (Isolator Row)58 SY Woven Geotextile Required (Isolator Row)58 SY Total Woven Geotextile Required 74 SY Total Woven Geotextile Required 70 SY Total Woven Geotextile Required 66 SY Total Woven Geotextile Required 74 SY Notes: 1. StormTech SC740 injection molded polypropylene chambers or equivalent per manufacturer’s drawings and specifications to be approved by Eagle Rock Engineering prior to construction that provides jet vacuum access for cleaning of the water quality BMP area of the system and a NJCAT verified TSS removal efficiency of 95% for OK-110 (or equivalent as approved by Engineer) 2. The sizing shown above are calculated using the SC-740 ADS System and can be modified to meet other chamber systems provided they meet the specifications approved by the Engineer. Contractor to submit final plans for each system to be reviewed and approved prior to installation UG P (8 ' ' S S 8' ' W 8' ' W 8' ' W W (8''SS UG P (8 ' ' S S 8' ' W 8' ' W 8' ' W W (8''SS 8''W 8''W (8''SS 8' ' W (8 ' ' S S (8 ' ' S S FO FO FO FO FO TBC: 59.57 TBC: 59.52 TBC: 59.30 TBC: 60.20TBC: 60.53 TBC: 61.20 TBC: 60.53 TBC: 60.20 TBC: 59.30 TBC: 59.68TBC: 59.74 SSMH #1EX. SSMH #1 CURB CUT FOR NEW ENTRY 1+500+00 1+00 1 2 3 2 4 2 1 78 9 98 CONNECT TO EX. SS STUB (FIELD VERIFY INV.) CONNECT TO EX. WATER MAIN STUB (FIELD VERIFY INV.) 4846 4848 4850 4852 4854 4856 4858 4860 4862 4864 4846 4848 4850 4852 4854 4856 4858 4860 4862 4864 0+00 1+00 1+50 38-LF OF 8" WATERLINE EX. 28-LF OF 8" PVC @ 0.40% 8" E INV IN=4851.65 8" N INV OUT=4851.55 SSMH #1 STA=1+11.06, 37.98' R RIM=4859.10 8" S INV IN=4851.24 8" W INV OUT=4851.14 EX. SSMH #1 STA=0+32.53, 33.92' R RIM=4858.72 EXISTING GROUND GRADE AT ALIGNMENT CL ST A = 0 + 6 1 . 4 1 EL = 4 8 5 9 . 2 3 LIP @ CL STA=1+37.30 EL=4860.57 TBC @ CL STA=1+38.79 EL=4861.15 5' MIN. BURY @ SS CROSSING W/ 2" THICK INSULATION BLUE BOARD OVER WATER MAIN (2' EACH SIDE OF PIPE OUTER WALLS) FULL LENGTH OF 5' BURY TO MEET 6' BURY DEPTH 22-LF OF 8" WATERLINE 18 " M I N . SE P A R A T I O N 51-LF OF 8" PVC @ 0.40% CONNECT TO EXISTING 8" SS STUB AT PROPERTY LINE INV: 4851.35± (FIELD VERIFY) CONNECT TO EXISTING WATER MAIN INV: 4852.26± (FIELD VERIFY) UGP UGP UGP (8''SS W W (8 ' ' S S C1 UGP UGP UGP (8''SS W W (8 ' ' S S 8' ' W 8'' W (8 ' ' S S 8''W 8 ' ' W (8''SS (8''SS ( 8 ' ' S S (1 2 ' ' S D 12 ' ' S D ) FO FO FO FO FO FO FO TBC: 59.14 TBC: 59.30 TBC: 58.74 TBC: 60.46 TBC: 60.20 TBC: 61.20 TBC: 60.20 TBC: 60.46 TBC/LP: 58.75 TBC: 59.30 TBC: 59.68 TBC: 59.74TBC: 59.52 TBC: 59.57 1 2 2 SSMH #2SSMH #1 3 51 4 77 2 2+10 0+00 1+00 2+00 CB #2 CB #1H STORM POND 2 4858.754858.15 4857.15 4856.154855.15 TBC: 59.27 TBC: 59.07 4846 4848 4850 4852 4854 4856 4858 4860 4862 4846 4848 4850 4852 4854 4856 4858 4860 4862 0+00 1+00 2+00 2+10 8" E INV IN=4851.65 8" N INV OUT=4851.55 SSMH #1 STA=0+64.32, 0.00' RIM=4859.10 8" SE INV IN=4852.19 8" W INV OUT=4852.09 SSMH #2 STA=1+74.47, 0.00' RIM=4858.60 110-LF OF 8" PVC @ 0.40% 38-LF OF 8" WATERLINE 79-LF OF 8 " W A T E R L I N E 5-LF OF 8" WATERLINE 5-LF OF 8" WATERLINE EXISTING GROUND GRADE AT ALIGNMENT CL 6' M I N . B U R Y 5' MIN. BURY @ SS CROSSING W/ 2" THICK INSULATION BLUE BOARD OVER WATER MAIN (2' EACH SIDE OF PIPE OUTER WALLS) FULL LENGTH OF 5' BURY TO MEET 6' BURY DEPTH N INV OUT=4855.15 CB #2 STA=1+99.80, 7.03' L RIM=4858.15 S INV OUT=4855.14 CB #1H STA=0+04.21, 0.40' L RIM=4858.14 T O E T O E T O E T O E T O E T O E T O E UG P UG P U G P W T O E T O E T O E T O E T O E T O E T O E UG P UG P U G P W ( 8 ' ' S S ( 8 ' ' S S 8 ' ' W 8 ' ' W 8''W 8''W 8''W 8''W 8''W 8''W (8 ' ' S S (8 ' ' S S (8''SS (8''SS (8''SS (8''SS 4' ' S S 4' ' S S 4' ' S S 2' ' W S 2' ' W S 2' ' F S 2' ' F S 2' ' F S (12''S D GB GB GB 6' ' F S 6' ' F S 6' ' F S 2' ' W S 2' ' W S 6' ' S S 6' ' S S FO FO FO 12 ' ' S D ) 1 2 ' ' S D ) 1+0 0 SSMH #2 SSMH #3 3 2 0+00 1+00 2+00 TBC/LP: 58.75 TBC: 59.15 TBC: 59.27 TBC: 60.46 TBC: 61.00 TBC: 59.20 TBC: 59.28 10 9 1 2 7 7 TBC: 60.20 TBC: 59.55 TBC: 59.85 TBC: 60.70 5 4 3 TBC: 61.75TBC: 61.75 TBC: 61.40 TBC: 61.45 TBC: 60.20 TBC: 60.10 CB #3A TBC: 59.90 TBC: 59.85 TBC/LP: 59.60 TBC: 60.40 2+40 TBC: 61.45 TBC: 61.40 5 5 STORM POND 2 4858.754858.15 4857.15 4856.154855.15 4846 4848 4850 4852 4854 4856 4858 4860 4862 4846 4848 4850 4852 4854 4856 4858 4860 4862 0+00 1+00 2+00 2+40 8" SE INV IN=4852.19 8" W INV OUT=4852.09 SSMH #2 STA=0+13.52, 5.50' L RIM=4858.60 196-LF OF 8" PVC @ 0.40% 8" SW INV IN=4853.07 8" NW INV OUT=4852.97 SSMH #3 STA=2+09.26, 5.50' L RIM=4859.40 N INV OUT=4855.15 CB #2 STA=0+17.35, 31.51' L GRATE=4858.15 22-LF OF 12" PVC @ 0.22% TO POND INV @ POND= 4855.10 179-LF OF 8" WATERLINE EXISTING GROUND GRADE AT ALIGNMENT CL 1 CY RIP-RAP PIPE TO FLOW LINE OF POND 6' M I N . B U R Y SW INV OUT=4856.10 CB #3A STA=2+33.51, 15.51' L GRATE=4859.10 INSTALL FH STA=1+85.76 W E S N 030'30'15' SCALE: 1" = 30' 7 PP - 1 AL I G N M E N T D , G , & E Fi l e L o c a t i o n : z: \ p r o j e c t s \ 2 0 2 2 \ 2 2 1 2 5 m a d i s o n s t a t i o n a p a r t m e n t s \ 3 . 0 d e s i g n \ 3 . 1 c a d \ 3 . 1 3 f i n a l \ 2 2 1 2 5 p p 1 a l i g n d _ g _ e . d w g Pl o t t e d B y : ru s s e l l Da t e P l o t t e d : We d n e s d a y , M a r c h 2 2 2 0 2 3 a t 0 3 : 2 8 P M KEY MAP W E S N ALIGNMENT "D" AG L E R O C K N G I N E E R I N G SU R V E Y E D B Y : DR A W N B Y : PR O J E C T N O . AP P R O V E D B Y : DE S C R I P T I O N DA T E RE V I S I O N S 1 2 3 4 5 6 AT T E N T I O N Th i s d o c u m e n t o r a n y p a r t t h e r e o f i n d e t a i l o r d e s i g n c o n c e p t is t h e p r o p e r t y o f E a g l e R o c k E n g i n e e r i n g a n d s h a l l n o t b e co p i e d i n a n y f o r m w i t h o u t t h e w r i t t e n a u t h o r i z a t i o n o f E a g l e Ro c k E n g i n e e r i n g . E SH E E T N O . SH E E T N A M E CI V I L P L A N N I N G S U R V E Y I N G ID A H O F A L L S ( 2 0 8 ) 5 4 2 - 2 6 6 5 RE X B U R G ( 2 0 8 ) 3 5 9 - 2 6 6 5 PR E P A R E D F O R : RY A N N E L S O N MA D I S O N S T A T I O N A P A R T M E N T S A. S N A R R R. J O R D A N P. S N A R R 22 1 2 5 P R E L I M I N A R Y N O T A P P R O V E D F O R C O N S T R U C T I O N 16 4 1 0 W E S N 030'30'15' SCALE: 1" = 30' ALIGNMENT "G" W E S N 030'30'15' SCALE: 1" = 30' ALIGNMENT "E" TR E J O S T . 7 A B C D F H I J K E G CONSTRUCTION ITEMS: THE FOLLOWING CONSTRUCTION ITEMS ARE FOR THE PURPOSE OF DISPLAY IN THE PLAN AND PROFILE VIEW ONLY AND DO NOT SHOW EACH AND EVERY CONSTRUCTION COMPONENT IN THE DESIGN. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO REVIEW THE PLANS AND UNDERSTAND THAT ALL ELBOWS, TEES, ADA ACCESSES, FIRE HYDRANTS, ETC.... MAY NOT BE LABELED BUT ARE REQUIRED FOR A COMPLETE PROJECT. ASPHALT PAVING PER DETAIL 9 ON SHEET D-1.SEWER MANHOLE TYPE A PER LATEST REVISION OF CITY OF REXBURG STANDARDS. SEE DETAIL X ON SHEET D-X. WATER MAIN VALVE AND VALVE BOX MEETING WATER MAIN SIZE PER CITY OF REXBURGSTANDARDS. FIRE HYDRANT ASSEMBLY PER CITY OF REXBURG STANDARDS. SEE DETAIL 5 ON SHEET D-1. 2" FIRE SERVICE LINE (CLUBHOUSE) PER CITY OF REXBURG STANDARDS TO MECHANICAL ROOM WITH REMOTE READOUT PER JRW ARCHITECTURAL PLANS. 1.5' LIP UP CURB PER DETAIL 7 ON SHEET D-1. INSTALL STORM DRAIN MANHOLE PER CITY OF REXBURG STANDARDS. 8"x8" TEE WITH THRUST BLOCK. SEE DETAIL 3 ON SHEET D-2. PAVING AND DRAINAGE CONSTRUCTION ITEMS SEWER CONSTRUCTION ITEMS 1 2 4 6 INSTALL ADA RAMP AND TRUNCATED DOMES PER CITY OF REXBURG STADARDS. 1 2 WATER CONSTRUCTION ITEMS 5 CATCH BASIN PER DETAIL 1 ON SHEET D-2. 1 2 3 4 5 7 8"x6" TEE WITH THRUST BLOCK. SEE DETAIL 3 ON SHEET D-2. 8 3 9 6' SIDEWALK PER CITY OF REXBURG STANDARDS. 6 7 BEND (ANGLE PER PLAN) WITH THRUST BLOCK. SEE DETAIL 3 ON SHEET D-2. 8 8"x8" CROSS WITH THRUST BLOCK. SEE DETAIL 3 ON SHEET D-2. 10 11 12 9 10 PLUG AND THRUST BLOCK. 11 1.5' LIP DOWN CURB PER DETAIL 8 ON SHEET D-1. 5' SIDEWALK PER CITY OF REXBURG STANDARDS. TRASH ENCLOSURE PER CITY OF REXBURG STANDARDS. INSTALL SC-740 INFILTRATION SYSTEM. SEE STORM TABLES ON SHEET C-4 FOR SYSTEM SPECIFICATIONS. PER DETAIL 6 ON SHEET D-1. TRANSITION CURB LIP UP TO LIP DOWN. NOT USED 6" SANITARY SEWER SERVICE PER LATEST REVISION OF CITY OF REXBURG STANDARDS. SEE DETAIL 2 ON SHEET D-1. (APARTMENT BUILDINGS)3 NOT USED NOT USED NOT USED 4 5 6 11 2" WATER SERVICE PER CITY OF REXBURG STANDARDS. WATER METER TO BEINSTALLED IN MECHANICAL ROOM W/ REMOTE READOUT PER JRW ARCHITECTURAL PLANS. NOT USED NOT USED 4" FIRE SERVICE PER CITY OF REXBURG STANDARDS TO MECHANICAL ROOM PER JRW ARCHITECTURAL PLANS. 4" SANITARY SEWER SERVICE PER LATEST REVISION OF CITY OF REXBURG STANDARDS. SEE DETAIL 2 ON SHEET D-1. (CLUBHOUSE) NEW FIBER CONDUIT. COORDINATE WITH CITY OF REXBURG. DEVELOPMENT SIGN 2 9 3 DEVELOPMENT SIGN TOETOETOETOETOE UGP S30°08'18"W 959.91' (M) 960.14' (R) TOETOETOETOETOE UGP 8 ' ' W 8 ' ' W 8 ' ' W (8''SS (8''SS (8''SS (8''SS (8''SS (8''SS (8''SS (8''SS (8''SS (8''SS 8''W 8''W 8''W 8''W 8''W 8''W 8''W 8''W 8''W 8''W 8''W 8''W 8''W 8''W 8''W 8''W 8'' W 8'' W 8'' W (8 ' ' S S (8 ' ' S S (8 ' ' S S 4''SS 4''SS 4''SS 2''WS 2''WS 2''FS 2''FS 2''FS GB GBGB GB GB GB GB GB 6' ' S S 6' ' S S 6' ' S S 6' ' F S 6' ' F S 2' ' W S 2' ' W S 6' ' S S 6' ' S S 6''FS 6''FS 6''FS 2''WS 2''WS 6''SS 6''SS 12''SD)12''SD) 6' ' F S 6' ' F S 2' ' W S 2' ' W S 6' ' F S 6' ' F S 6' ' F S 2' ' W S 2' ' W S ( 8 ' ' S S 6''SS 6''SS 6''SS 6''SS 0+00 1+00 2+00 3+00 4+00 5+00 6+00 7+007+00SSMH #5SSMH #4SSMH #3 TBC: 60.40 TBC: 60.00 TBC: 59.85 TBC: 59.55 TBC: 61.40 TBC: 61.40 TBC: 61.75TBC: 61.75 TBC/LP: 59.30 TBC: 60.00 TBC: 60.36 TBC: 60.36 TBC: 60.00 TBC/LP: 58.20 TBC: 59.80 TBC: 59.80 TBC: 61.20 TBC: 60.50 TBC: 60.00 TBC: 58.80 TBC: 59.50 TBC: 59.70 TBC: 60.00TBC: 60.00TBC: 60.00 TBC: 61.54 TBC: 61.60 TBC: 61.60TBC: 61.00 WALK: 62.25 BLDG FF: 63.00 BLDG FF: 62.70 BLDG FF: 62.20 1 102 3 5 10 5 6 6 SDMH #3 CB #3 SDMH #4 SMDH #5 CB #4 CB #5 7 7 7 1 1 1 2 7 7 10 9 10 9 10 9 5 5 5 1 3 3 3 4 4 9 9 10 ' 8 TBC: 60.30 TBC: 60.20 TBC: 60.10 TBC: 59.80TBC/LP: 59.60 TBC: 59.85TBC: 59.90 CB #3A SDMH #3A TBC: 61.04 TBC: 61.20 TBC: 61.36 TBC: 61.85 TBC: 61.20 TBC: 60.93 TBC: 60.77 TBC: 60.90 TBC: 61.45 TBC: 61.45 TBC/HP: 4860.51 3 3 3 2 11 3 3 2 2 2 2 3 11 2 3 3 5 5 5 8 2 4848 4850 4852 4854 4856 4858 4860 4862 4864 4848 4850 4852 4854 4856 4858 4860 4862 4864 0+00 1+00 2+00 3+00 4+00 5+00 6+00 7+007+00 8" SW INV IN=4853.07 8" NW INV OUT=4852.97 SSMH #3 STA=0+09.62, 5.50' L RIM=4859.40 220-LF OF 8" PVC @ 0.40% 8" NE INV OUT=4854.93 SSMH #5 STA=4+50.07, 5.50' L RIM=4860.00 273-LF OF 8" WATERLINE 5-LF OF 8" WATERLINE 319-LF OF 8" WATERLINE 12" S INV IN=4855.68 24" NE INV OUT=4854.08 SDMH #3 STA=2+03.45, 24.27' L RIM=4858.90 N INV OUT=4855.70 CB #3 STA=2+10.44, 31.51' L GRATE=4858.70 10-LF OF 12" PVC @ 0.22% 5-LF OF 24" PVC @ 0.22% 5-LF OF 24" PVC @ 0.22% 10-LF OF 12" PVC @ 0.22% 12" S INV IN=4854.58 24" NE INV OUT=4852.98 SDMH #4 STA=5+89.46, 24.01' L RIM=4857.70 N INV OUT=4854.60 CB #4 STA=5+96.45, 31.51' L GRATE=4857.608" SW INV IN=4854.05 8" NE INV OUT=4853.95 SSMH #4 STA=2+29.85, 5.50' L RIM=4859.20 220-LF OF 8" PVC @ 0.40% EXISTING GROUND GRADE AT ALIGNMENT CL INSTALL STORM INFILTRATION SYSTEM 93'L x 16'W SC-740 ADS STORM TECH CHAMBER SYSTEM (SEE TABLE 4 SHEET C-4) STA=0+41.04 EL=4860.45 ST A = 2 + 1 4 . 6 7 EL = 4 8 5 9 . 7 1 STA=4+00 EL=4860.33 STA=6+00.24 EL=4858.77 STA=6+76.99 EL=4859.25 INSTALL STORM INFILTRATION SYSTEM 86'L x 16'W SC-740 ADS STORM TECH CHAMBER SYSTEM (SEE TABLE 4 SHEET C-4) 6" M I N . B U R Y SW INV OUT=4856.10 CB #3A STA=0+06.18, 31.51' L GRATE=4859.10 95-LF OF 12" PVC @ 0.22% 12" NE INV IN=4855.89 24" SW INV OUT=4854.09 SDMH #3A STA=1+00.44, 24.27' L RIM=4859.60 5-LF OF 24" PVC @ 0.22% IN S T A L L F H ST A = 6 + 7 2 . 5 5 INSTALL FH STA=3+36.67INSTALL FH STA=0+27.32 W E S N 030'30'15' SCALE: 1" = 30' 8 PP - 2 AL I G N M E N T F Fi l e L o c a t i o n : z: \ p r o j e c t s \ 2 0 2 2 \ 2 2 1 2 5 m a d i s o n s t a t i o n a p a r t m e n t s \ 3 . 0 d e s i g n \ 3 . 1 c a d \ 3 . 1 3 f i n a l \ 2 2 1 2 5 p p 2 a l i g n f . d w g Pl o t t e d B y : ru s s e l l Da t e P l o t t e d : We d n e s d a y , M a r c h 2 2 2 0 2 3 a t 0 3 : 2 9 P M ALIGNMENT "F" AG L E R O C K N G I N E E R I N G SU R V E Y E D B Y : DR A W N B Y : PR O J E C T N O . AP P R O V E D B Y : DE S C R I P T I O N DA T E RE V I S I O N S 1 2 3 4 5 6 AT T E N T I O N Th i s d o c u m e n t o r a n y p a r t t h e r e o f i n d e t a i l o r d e s i g n c o n c e p t is t h e p r o p e r t y o f E a g l e R o c k E n g i n e e r i n g a n d s h a l l n o t b e co p i e d i n a n y f o r m w i t h o u t t h e w r i t t e n a u t h o r i z a t i o n o f E a g l e Ro c k E n g i n e e r i n g . E SH E E T N O . SH E E T N A M E CI V I L P L A N N I N G S U R V E Y I N G ID A H O F A L L S ( 2 0 8 ) 5 4 2 - 2 6 6 5 RE X B U R G ( 2 0 8 ) 3 5 9 - 2 6 6 5 PR E P A R E D F O R : RY A N N E L S O N MA D I S O N S T A T I O N A P A R T M E N T S A. S N A R R R. J O R D A N P. S N A R R 22 1 2 5 P R E L I M I N A R Y N O T A P P R O V E D F O R C O N S T R U C T I O N 16 4 1 0 KEY MAP W E S N A B C D F H I J K E G CONSTRUCTION ITEMS: THE FOLLOWING CONSTRUCTION ITEMS ARE FOR THE PURPOSE OF DISPLAY IN THE PLAN AND PROFILE VIEW ONLY AND DO NOT SHOW EACH AND EVERY CONSTRUCTION COMPONENT IN THE DESIGN. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO REVIEW THE PLANS AND UNDERSTAND THAT ALL ELBOWS, TEES, ADA ACCESSES, FIRE HYDRANTS, ETC.... MAY NOT BE LABELED BUT ARE REQUIRED FOR A COMPLETE PROJECT. ASPHALT PAVING PER DETAIL 9 ON SHEET D-1.SEWER MANHOLE TYPE A PER LATEST REVISION OF CITY OF REXBURG STANDARDS. SEE DETAIL X ON SHEET D-X. WATER MAIN VALVE AND VALVE BOX MEETING WATER MAIN SIZE PER CITY OF REXBURGSTANDARDS. FIRE HYDRANT ASSEMBLY PER CITY OF REXBURG STANDARDS. SEE DETAIL 5 ON SHEET D-1. 2" FIRE SERVICE LINE (CLUBHOUSE) PER CITY OF REXBURG STANDARDS TO MECHANICAL ROOM WITH REMOTE READOUT PER JRW ARCHITECTURAL PLANS. 1.5' LIP UP CURB PER DETAIL 7 ON SHEET D-1. INSTALL STORM DRAIN MANHOLE PER CITY OF REXBURG STANDARDS. 8"x8" TEE WITH THRUST BLOCK. SEE DETAIL 3 ON SHEET D-2. PAVING AND DRAINAGE CONSTRUCTION ITEMS SEWER CONSTRUCTION ITEMS 1 2 4 6 INSTALL ADA RAMP AND TRUNCATED DOMES PER CITY OF REXBURG STADARDS. 1 2 WATER CONSTRUCTION ITEMS 5 CATCH BASIN PER DETAIL 1 ON SHEET D-2. 1 2 3 4 5 7 8"x6" TEE WITH THRUST BLOCK. SEE DETAIL 3 ON SHEET D-2. 8 3 9 6' SIDEWALK PER CITY OF REXBURG STANDARDS. 6 7 BEND (ANGLE PER PLAN) WITH THRUST BLOCK. SEE DETAIL 3 ON SHEET D-2. 8 8"x8" CROSS WITH THRUST BLOCK. SEE DETAIL 3 ON SHEET D-2. 10 11 12 9 10 PLUG AND THRUST BLOCK. 11 1.5' LIP DOWN CURB PER DETAIL 8 ON SHEET D-1. 5' SIDEWALK PER CITY OF REXBURG STANDARDS. TRASH ENCLOSURE PER CITY OF REXBURG STANDARDS. INSTALL SC-740 INFILTRATION SYSTEM. SEE STORM TABLES ON SHEET C-4 FOR SYSTEM SPECIFICATIONS. PER DETAIL 6 ON SHEET D-1. TRANSITION CURB LIP UP TO LIP DOWN. NOT USED 6" SANITARY SEWER SERVICE PER LATEST REVISION OF CITY OF REXBURG STANDARDS. SEE DETAIL 2 ON SHEET D-1. (APARTMENT BUILDINGS)3 NOT USED NOT USED NOT USED 4 5 6 11 2" WATER SERVICE PER CITY OF REXBURG STANDARDS. WATER METER TO BEINSTALLED IN MECHANICAL ROOM W/ REMOTE READOUT PER JRW ARCHITECTURAL PLANS. NOT USED NOT USED 4" FIRE SERVICE PER CITY OF REXBURG STANDARDS TO MECHANICAL ROOM PER JRW ARCHITECTURAL PLANS. 4" SANITARY SEWER SERVICE PER LATEST REVISION OF CITY OF REXBURG STANDARDS. SEE DETAIL 2 ON SHEET D-1. (CLUBHOUSE) 11 ' P A T H W A Y E A S E M E N T 8' A S P H A L T P A T H W A Y 10 ' A S P H A L T P A T H W A Y 8''W 8''W 8''W 8 ' ' W 8' ' W ( 8 ' ' S S GB GB GB 12''SD) 0+00 1+00 2+00 TBC: 61.00TBC: 60.20 TBC: 60.46 TBC: 61.00 TBC: 60.64 TBC: 61.00TBC: 61.00 TBC/LP: 58.74 TBC: 59.34 TBC: 59.61 TBC: 60.70 TBC: 59.90 SSMH #1 CB # 1GCB #1H 1 2 3 4 5 58 9 8 9 8 8 9 7 7 1 5 87-LF OF 12" S.D @ 0.22% 30-LF OF 12" S.D @ 0.22% TO STORM POND 7 4 4 4857.80 4856.80 4855.80 STORM POND 1 TBC: 59.14 2 3 4846 4848 4850 4852 4854 4856 4858 4860 4862 4846 4848 4850 4852 4854 4856 4858 4860 4862 0+00 1+00 2+00 164-LF OF 8" WATERLINE 25-LF OF 8" WATERLINE 23-LF OF 8" WATERLINE 30-LF OF 12" PVC @ 0.22% TO POND INV @ POND= 4854.78 1CY RIP-RAP PIPE TO FLOW LINE OF POND N INV IN=4854.95 SW INV OUT=4854.85 CB # 1G STA=1+04.65, 31.88' R GRATE=4858.50 87-LF OF 12" PVC @ 0.22% S INV OUT=4855.14 CB #1H STA=0+17.79, 31.88' R GRATE=4858.14 EXISTING GROUND GRADE AT ALIGNMENT CL LIP @ CL STA=1+91.11 EL=4860.02 TBC @ CL STA=1+93.43 EL=4860.61 6" M I N . B U R Y INSTALL FH STA=1+79.25 6' ' P S 6' ' P S 6' ' P S 6' ' P S N89°47'52"E 599.99' 6' ' P S 6' ' P S 6' ' P S 6' ' P S (1 2 ' ' S D (1 2 ' ' S D 8' ' W 8' ' W 8' ' W 8''W 8''W 8''W 8''W 8''W 8''W 8''W 8''W 8''W 8''W 8''W 8''W 8''W 8''W 12''SD) 6' ' S S 6' ' S S 2' ' W S 2' ' W S 6' ' F S 6' ' F S 12' ' S D ) GB GB GB G B G B 8' ' S S ) 8' ' S S ) (8''SS (8''SS (8''SS (8''SS (8''SS (8''SS 6' ' S S 6' ' S S 2' ' W S 2' ' W S 6' ' F S 6' ' F S 2' ' W S 2' ' W S 2' ' W S 6' ' F S 6' ' F S 6' ' F S 1 2 ' ' S D ) 6+500+00 1+00 2+00 3+00 4+00 5+00 6+00 SSMH #14SSMH #13 CB # 1G SDMH #1B SDMH #1A SDMH #1C CB #1A CB #1B STORM POND 1 (SNOW STORAGE) TOP=4857.80 (16923 SQFT) CAPACITY TOP: 4857.60 (14408 SQFT) BTM=4853.60 (2686 SQFT) TBC: 59.70 TBC: 59.90 TBC: 60.70 TBC: 61.10TBC: 60.51 TBC: 60.43 TBC: 59.14 TBC: 58.90 TBC: 58.90 TBC: 58.20 TBC/LP: 57.80 TBC: 58.74 TBC: 58.83 TBC: 59.34 TBC: 59.75 TBC: 59.50 TBC: 58.50 TBC: 57.90 TBC: 58.10 TBC: 58.48 TBC: 58.84 TBC: 57.80 TBC: 60.10 TBC: 61.30 TBC: 58.90 1 1 2 2 3 3 4 4 5 6 7 9 89 23 7 BLDG FF: 61.70 BLDG FF: 62.10 BLDG FF: 62.80 BLDG FF: 63.00 4857.804857.60 3 9 3 3 1 7 1 2 10 9 10 9 7 1 55 310 9 TBC: 58.20 CB #1I 5 5 5 4856.604855.604854.60 2 2 3 11 3 3 2 2 3 1 5 4853.60 4857.804857.604856.604855.604854.604853.60 9 8 4846 4848 4850 4852 4854 4856 4858 4860 4862 4846 4848 4850 4852 4854 4856 4858 4860 4862 0+00 1+00 2+00 3+00 4+00 5+00 6+00 6+50 12" S INV IN=4853.05 12" NW INV IN=4854.56 12" E INV OUT=4852.95 SDMH #1B STA=0+35.53, 9.00' L RIM=4858.00 76-LF OF 12" PVC @ 0.22% 12" W INV IN=4852.78 12" N INV OUT=4852.68 SDMH #1A STA=1+11.80, 9.00' L RIM=4857.70 S INV IN=4852.63 NE INV OUT=4852.54 CB #1A STA=1+11.80, 30.88' L GRATE=4857.20 27-LF OF 12" PVC @ 0.22% TO POND INV @ POND= 4852.48 1 CY RIP-RAP PIPE TO FLOW LINE OF POND 8" E INV IN=4854.54 8" S INV OUT=4854.44 SSMH #13 STA=2+48.10, 3.00' L RIM=4858.50 25-LF OF 8" WATERLINE 23-LF OF 8" WATERLINE193-LF OF 8" WATERLINE 18 " M I N . 8" W INV OUT=4855.58 SSMH #14 STA=5+08.46, 3.00' L RIM=4859.50 STA=0+65.92 EL=4858.51 ST A = 1 + 0 9 . 5 3 EL = 4 8 5 8 . 1 3 ST A = 5 + 7 1 . 1 4 EL = 4 8 5 9 . 9 4 LIP @ CL STA=6+36.24 EL=4860.06 TBC @ CL STA=6+38.59 EL=4860.63 EXISTING GROUND GRADE AT ALIGNMENT CL 6" M I N . B U R Y INSTALL FH STA=6+19.42 IN S T A L L F H ST A = 0 + 7 0 . 1 7 SE INV OUT=4854.70 CB #1I STA=0+03.70, 61.82' L RIM=4857.70 62-LF OF 12" PVC @ 0.22% 149-LF OF 8" WATERLINE 199-LF OF 8" WATERLINE INSTALL FH STA=4+12.29 260-LF OF 8" PVC @ 0.40% W E SN 030'30'15' SCALE: 1" = 30' 9 PP - 3 AL I G N M E N T C & H Fi l e L o c a t i o n : z: \ p r o j e c t s \ 2 0 2 2 \ 2 2 1 2 5 m a d i s o n s t a t i o n a p a r t m e n t s \ 3 . 0 d e s i g n \ 3 . 1 c a d \ 3 . 1 3 f i n a l \ 2 2 1 2 5 p p 3 a l i g n c _ h . d w g Pl o t t e d B y : ru s s e l l Da t e P l o t t e d : We d n e s d a y , M a r c h 2 2 2 0 2 3 a t 0 3 : 2 9 P M ALIGNMENT "C" AG L E R O C K N G I N E E R I N G SU R V E Y E D B Y : DR A W N B Y : PR O J E C T N O . AP P R O V E D B Y : DE S C R I P T I O N DA T E RE V I S I O N S 1 2 3 4 5 6 AT T E N T I O N Th i s d o c u m e n t o r a n y p a r t t h e r e o f i n d e t a i l o r d e s i g n c o n c e p t is t h e p r o p e r t y o f E a g l e R o c k E n g i n e e r i n g a n d s h a l l n o t b e co p i e d i n a n y f o r m w i t h o u t t h e w r i t t e n a u t h o r i z a t i o n o f E a g l e Ro c k E n g i n e e r i n g . E SH E E T N O . SH E E T N A M E CI V I L P L A N N I N G S U R V E Y I N G ID A H O F A L L S ( 2 0 8 ) 5 4 2 - 2 6 6 5 RE X B U R G ( 2 0 8 ) 3 5 9 - 2 6 6 5 PR E P A R E D F O R : RY A N N E L S O N MA D I S O N S T A T I O N A P A R T M E N T S A. S N A R R R. J O R D A N P. S N A R R 22 1 2 5 P R E L I M I N A R Y N O T A P P R O V E D F O R C O N S T R U C T I O N 16 4 1 0 KEY MAP W E S N A B C D F H I J K E G W E S N 030'30'15' SCALE: 1" = 30' ALIGNMENT "H" CONSTRUCTION ITEMS: THE FOLLOWING CONSTRUCTION ITEMS ARE FOR THE PURPOSE OF DISPLAY IN THE PLAN AND PROFILE VIEW ONLY AND DO NOT SHOW EACH AND EVERY CONSTRUCTION COMPONENT IN THE DESIGN. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO REVIEW THE PLANS AND UNDERSTAND THAT ALL ELBOWS, TEES, ADA ACCESSES, FIRE HYDRANTS, ETC.... MAY NOT BE LABELED BUT ARE REQUIRED FOR A COMPLETE PROJECT. ASPHALT PAVING PER DETAIL 9 ON SHEET D-1.SEWER MANHOLE TYPE A PER LATEST REVISION OF CITY OF REXBURG STANDARDS. SEE DETAIL X ON SHEET D-X. WATER MAIN VALVE AND VALVE BOX MEETING WATER MAIN SIZE PER CITY OF REXBURGSTANDARDS. FIRE HYDRANT ASSEMBLY PER CITY OF REXBURG STANDARDS. SEE DETAIL 5 ON SHEET D-1. 2" FIRE SERVICE LINE (CLUBHOUSE) PER CITY OF REXBURG STANDARDS TO MECHANICAL ROOM WITH REMOTE READOUT PER JRW ARCHITECTURAL PLANS. 1.5' LIP UP CURB PER DETAIL 7 ON SHEET D-1. INSTALL STORM DRAIN MANHOLE PER CITY OF REXBURG STANDARDS. 8"x8" TEE WITH THRUST BLOCK. SEE DETAIL 3 ON SHEET D-2. PAVING AND DRAINAGE CONSTRUCTION ITEMS SEWER CONSTRUCTION ITEMS 1 2 4 6 INSTALL ADA RAMP AND TRUNCATED DOMES PER CITY OF REXBURG STADARDS. 1 2 WATER CONSTRUCTION ITEMS 5 CATCH BASIN PER DETAIL 1 ON SHEET D-2. 1 2 3 4 5 7 8"x6" TEE WITH THRUST BLOCK. SEE DETAIL 3 ON SHEET D-2. 8 3 9 6' SIDEWALK PER CITY OF REXBURG STANDARDS. 6 7 BEND (ANGLE PER PLAN) WITH THRUST BLOCK. SEE DETAIL 3 ON SHEET D-2. 8 8"x8" CROSS WITH THRUST BLOCK. SEE DETAIL 3 ON SHEET D-2. 10 11 12 9 10 PLUG AND THRUST BLOCK. 11 1.5' LIP DOWN CURB PER DETAIL 8 ON SHEET D-1. 5' SIDEWALK PER CITY OF REXBURG STANDARDS. TRASH ENCLOSURE PER CITY OF REXBURG STANDARDS. INSTALL SC-740 INFILTRATION SYSTEM. SEE STORM TABLES ON SHEET C-4 FOR SYSTEM SPECIFICATIONS. PER DETAIL 6 ON SHEET D-1. TRANSITION CURB LIP UP TO LIP DOWN. NOT USED 6" SANITARY SEWER SERVICE PER LATEST REVISION OF CITY OF REXBURG STANDARDS. SEE DETAIL 2 ON SHEET D-1. (APARTMENT BUILDINGS)3 NOT USED NOT USED NOT USED 4 5 6 11 2" WATER SERVICE PER CITY OF REXBURG STANDARDS. WATER METER TO BEINSTALLED IN MECHANICAL ROOM W/ REMOTE READOUT PER JRW ARCHITECTURAL PLANS. NOT USED NOT USED 4" FIRE SERVICE PER CITY OF REXBURG STANDARDS TO MECHANICAL ROOM PER JRW ARCHITECTURAL PLANS. 4" SANITARY SEWER SERVICE PER LATEST REVISION OF CITY OF REXBURG STANDARDS. SEE DETAIL 2 ON SHEET D-1. (CLUBHOUSE) 6''PS 6''PS 6''PS 6''PS 6''PS 6''PS 6''PS 6''PS 6''PS 6''PS 6''PS 6''PS 6''PS 6''PS 6''PS 6''PS48 5 8 . 4 8 LI PN00°16'05"W 604.86' (M) 605.00' (R)6''PS 6''PS 6''PS 6''PS 6''PS 6''PS 6''PS 6''PS 6''PS 6''PS 6''PS 6''PS 6''PS 6''PS 6''PS 6''PS48 5 8 . 4 8 LI P (12''SD (12''SD (12''SD (12''SD (12''SD 8''W 8''W 8''W 8''W 8''W 8''W 8''W 8''W 8''W 8''W 8''W 8' ' W 8' ' W 8' ' W 8' ' W (1 2 ' ' S D 8' ' W 8' ' W 8' ' W 8' ' W 12 ' ' S D ) (12''S D 12''SD) 12''S D ) GB GB GB GB GB GB GB GB GB GB 12' ' S D ) (1 2 ' ' S D GB GB GB GB GB GB 12''SD ) 8' ' W 8' ' S S ) (8 ' ' S S (8 ' ' S S TBC: 59.50 TBC: 59.50 TBC: 58.90 TBC: 58.10TBC: 58.90 TBC: 58.90 TBC: 57.90 TBC: 57.80 TBC: 57.65 TBC/LP: 57.20 TBC: 58.00 TBC: 58.30 TBC: 59.14 TBC: 58.90 TBC: 59.10 TBC: 59.70 TBC: 60.35 TBC: 59.30 TBC: 59.80 TBC: 59.20 TBC: 59.00 TBC: 58.70 TBC: 57.85 TBC: 57.75 TBC/LP: 57.50 TBC: 58.20 TBC/HP: 58.60 TBC: 58.48TBC: 58.40 TBC: 57.80 TBC/LP: 57.70 TBC: 58.10 TBC: 58.10 TBC/LP: 57.80 TBC: 59.35 TBC: 59.35TBC: 59.75 TBC: 58.90 SDMH #1ECB #1D CB #1E SDMH #1B SDMH #1A SDMH #6 SDMH #1D CB #6A CB #6B SDMH #1C CB #1A CB #1CCB #1B BLDG FF: 61.70 BLDG FF: 61.30 1+000+00 TBC: 58.20CB #1I TBC/HP: 58.15 0+00 1+00 2+00 3+00 4+00 5+00 5+30 1 2 3 2 56 7 7 7 9 91 7 2 4 45 1 5 102 11 3 3 2 2 3 3 2 3 3 7 4 9 1 4848 4850 4852 4854 4856 4858 4860 4862 4848 4850 4852 4854 4856 4858 4860 4862 0+00 1+00 2+00 3+00 4+00 5+00 5+30 E INV IN=4853.84 W INV IN=4853.84 N INV OUT=4853.74 SDMH #1D STA=2+74.30, 9.00' R RIM=4857.30 E INV OUT=4853.89 CB #1C STA=2+83.03, 31.02' R GRATE=4856.90 24-LF OF 12" PVC @ 0.22% 205-LF OF 12" PVC @ 0.22% 63-LF OF 12" PVC @ 0.22% S INV IN=4853.29 W INV IN=4853.55 N INV OUT=4853.19 SDMH #1C STA=0+69.78, 9.00' R RIM=4857.10 E INV OUT=4853.60 CB #1B STA=0+69.78, 31.52' R RIM=4856.60 5-LF OF 8" WATERLINE 190-LF OF 8" WATERLINE 5-LF OF 8" WATERLINE 31-LF OF 8" WATERLINE 36-LF OF 8" WATERLINE 5-LF OF 8" WATERLINE 191-LF OF 8" WATERLINE EXISTING GRADE GRADE @ ALIGNMENT CL 12" S INV IN=4853.05 12" NW INV IN=4854.56 12" E INV OUT=4852.95 SDMH #1B STA=0+07.17, 9.00' R RIM=4858.00 6" M I N . B U R Y IN S T A L L F H ST A = 0 + 3 6 . 8 1 IN S T A L L F H ST A = 2 + 5 5 . 6 1 IN S T A L L F H ST A = 4 + 7 4 . 6 3 SE INV OUT=4854.10 CB #6B STA=5+03.61, 31.52' R GRATE=4857.10 33-LF OF 12" PVC @ 0.22% 12" NW INV IN=4854.03 12" SW INV IN=4854.18 24" E INV OUT=4852.41 SDMH #6 STA=5+17.92, 1.28' R RIM=4857.40 12" E INV IN=4854.05 12" SE INV IN=4854.99 12" N INV IN=4855.62 12" W INV OUT=4853.95 SDMH #1E STA=2+74.30, 40.26' L RIM=4859.00 80-LF OF 12" PVC @ 0.22% S INV OUT=4855.80 CB #1D STA=1+94.27, 40.26' L RIM=4858.80 NE INV OUT=4854.20 CB #6A STA=5+25.31, 8.37' R GRATE=4857.20 INSTALL STORM INFILTRATION SYSTEM 93'L x 16'W SC-740 ADS STORM TECH CHAMBER SYSTEM (SEE TABLE 4 SHEET C-4) 8"x8" TEE STA=4+87.41, 8.00' L 4850 4852 4854 4856 4858 4860 4850 4852 4854 4856 4858 4860 0+00 1+00 SE INV OUT=4854.70 CB #1I STA=0+21.50, 10.75' R GRATE=4857.70 62-LF OF 12" PVC @ 0.22% 12" S INV IN=4853.05 12" NW INV IN=4854.56 12" E INV OUT=4852.95 SDMH #1B STA=0+74.32, 21.08' L RIM=4858.00 63-LF OF 12" PVC @ 0.22% EXISTING GRADE GRADE @ ALIGNMENT CL 6''PS 6''PS 6''PS6''PS 6''PS 6''PS (12''SD 8''W 8' ' W 12 ' ' S D ) GB GB 12''SD ) SDMH #1B 1+000+00 CB #1I 2 6 7 1 2 TBC: 58.90 TBC: 58.10TBC: 58.90 TBC: 58.90 TBC: 57.90 TBC: 57.80 TBC: 59.14 TBC: 58.90 TBC: 58.20 2 11 3 3 2 0+00 7 W E SN 030'30'15' SCALE: 1" = 30' 10 PP - 4 AL I G N M E N T A Fi l e L o c a t i o n : z: \ p r o j e c t s \ 2 0 2 2 \ 2 2 1 2 5 m a d i s o n s t a t i o n a p a r t m e n t s \ 3 . 0 d e s i g n \ 3 . 1 c a d \ 3 . 1 3 f i n a l \ 2 2 1 2 5 p p 4 a l i g n a . d w g Pl o t t e d B y : ru s s e l l Da t e P l o t t e d : We d n e s d a y , M a r c h 2 2 2 0 2 3 a t 0 3 : 2 9 P M ALIGNMENT "A" AG L E R O C K N G I N E E R I N G SU R V E Y E D B Y : DR A W N B Y : PR O J E C T N O . AP P R O V E D B Y : DE S C R I P T I O N DA T E RE V I S I O N S 1 2 3 4 5 6 AT T E N T I O N Th i s d o c u m e n t o r a n y p a r t t h e r e o f i n d e t a i l o r d e s i g n c o n c e p t is t h e p r o p e r t y o f E a g l e R o c k E n g i n e e r i n g a n d s h a l l n o t b e co p i e d i n a n y f o r m w i t h o u t t h e w r i t t e n a u t h o r i z a t i o n o f E a g l e Ro c k E n g i n e e r i n g . E SH E E T N O . SH E E T N A M E CI V I L P L A N N I N G S U R V E Y I N G ID A H O F A L L S ( 2 0 8 ) 5 4 2 - 2 6 6 5 RE X B U R G ( 2 0 8 ) 3 5 9 - 2 6 6 5 PR E P A R E D F O R : RY A N N E L S O N MA D I S O N S T A T I O N A P A R T M E N T S A. S N A R R R. J O R D A N P. S N A R R 22 1 2 5 P R E L I M I N A R Y N O T A P P R O V E D F O R C O N S T R U C T I O N 16 4 1 0 KEY MAP W E S N A B C D F H I J K E G ALIGNMENT "1A" CONSTRUCTION ITEMS: THE FOLLOWING CONSTRUCTION ITEMS ARE FOR THE PURPOSE OF DISPLAY IN THE PLAN AND PROFILE VIEW ONLY AND DO NOT SHOW EACH AND EVERY CONSTRUCTION COMPONENT IN THE DESIGN. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO REVIEW THE PLANS AND UNDERSTAND THAT ALL ELBOWS, TEES, ADA ACCESSES, FIRE HYDRANTS, ETC.... MAY NOT BE LABELED BUT ARE REQUIRED FOR A COMPLETE PROJECT. ASPHALT PAVING PER DETAIL 9 ON SHEET D-1.SEWER MANHOLE TYPE A PER LATEST REVISION OF CITY OF REXBURG STANDARDS. SEE DETAIL X ON SHEET D-X. WATER MAIN VALVE AND VALVE BOX MEETING WATER MAIN SIZE PER CITY OF REXBURGSTANDARDS. FIRE HYDRANT ASSEMBLY PER CITY OF REXBURG STANDARDS. SEE DETAIL 5 ON SHEET D-1. 2" FIRE SERVICE LINE (CLUBHOUSE) PER CITY OF REXBURG STANDARDS TO MECHANICAL ROOM WITH REMOTE READOUT PER JRW ARCHITECTURAL PLANS. 1.5' LIP UP CURB PER DETAIL 7 ON SHEET D-1. INSTALL STORM DRAIN MANHOLE PER CITY OF REXBURG STANDARDS. 8"x8" TEE WITH THRUST BLOCK. SEE DETAIL 3 ON SHEET D-2. PAVING AND DRAINAGE CONSTRUCTION ITEMS SEWER CONSTRUCTION ITEMS 1 2 4 6 INSTALL ADA RAMP AND TRUNCATED DOMES PER CITY OF REXBURG STADARDS. 1 2 WATER CONSTRUCTION ITEMS 5 CATCH BASIN PER DETAIL 1 ON SHEET D-2. 1 2 3 4 5 7 8"x6" TEE WITH THRUST BLOCK. SEE DETAIL 3 ON SHEET D-2. 8 3 9 6' SIDEWALK PER CITY OF REXBURG STANDARDS. 6 7 BEND (ANGLE PER PLAN) WITH THRUST BLOCK. SEE DETAIL 3 ON SHEET D-2. 8 8"x8" CROSS WITH THRUST BLOCK. SEE DETAIL 3 ON SHEET D-2. 10 11 12 9 10 PLUG AND THRUST BLOCK. 11 1.5' LIP DOWN CURB PER DETAIL 8 ON SHEET D-1. 5' SIDEWALK PER CITY OF REXBURG STANDARDS. TRASH ENCLOSURE PER CITY OF REXBURG STANDARDS. INSTALL SC-740 INFILTRATION SYSTEM. SEE STORM TABLES ON SHEET C-4 FOR SYSTEM SPECIFICATIONS. PER DETAIL 6 ON SHEET D-1. TRANSITION CURB LIP UP TO LIP DOWN. NOT USED 6" SANITARY SEWER SERVICE PER LATEST REVISION OF CITY OF REXBURG STANDARDS. SEE DETAIL 2 ON SHEET D-1. (APARTMENT BUILDINGS)3 NOT USED NOT USED NOT USED 4 5 6 11 2" WATER SERVICE PER CITY OF REXBURG STANDARDS. WATER METER TO BEINSTALLED IN MECHANICAL ROOM W/ REMOTE READOUT PER JRW ARCHITECTURAL PLANS. NOT USED NOT USED 4" FIRE SERVICE PER CITY OF REXBURG STANDARDS TO MECHANICAL ROOM PER JRW ARCHITECTURAL PLANS. 4" SANITARY SEWER SERVICE PER LATEST REVISION OF CITY OF REXBURG STANDARDS. SEE DETAIL 2 ON SHEET D-1. (CLUBHOUSE) W E SN 030'30'15' SCALE: 1" = 30' EG EG EG EG EG EG 8' ' W 8' ' W 8' ' W 8' ' W 8' ' W 8' ' W (1 2 ' ' S D (1 2 ' ' S D 8' ' W 8' ' W 8''W 8' ' W 8' ' W 8' ' W GB GB GB GB GB GB GB GB GB GB G B G B 8''SS)8''SS)8''SS)8''SS)8''SS) (8 ' ' S S (8 ' ' S S 6' ' S S 6' ' S S 6' ' S S 6' ' S S 6' ' S S 8''SS)8''SS)8''SS)8''SS)8''SS) (8 ' ' S S (8 ' ' S S (8 ' ' S S 6' ' S S 6' ' S S (8''SS 8''W BLDG FF: 61.70 15 ' 15 ' TBC: 60.12 TBC: 58.37 TBC: 60.07 OIL: 60.90 SSMH #12 SSMH #13 SDMH #1F 2+ 0 0 2+ 0 0 3+ 0 0 5+600+00 1+00 2+00 3+00 4+00 5+00 2 9 STORM POND 1 1 3 1 1 3 39 30 ' TBC: 59.32 TBC: 60.32 BLDG FF: 62.10 BLDG FF: 62.40 BLDG FF: 61.30 2 SSMH #10 9 3 2 4846 4848 4850 4852 4854 4856 4858 4860 4862 4846 4848 4850 4852 4854 4856 4858 4860 4862 0+00 1+00 2+00 3+00 4+00 5+00 5+60 8" N INV IN=4853.47 8" S INV OUT=4853.37 SSMH #12 STA=2+75.51, 0.00' RIM=4860.208" E INV IN=4854.54 8" S INV OUT=4854.44 SSMH #13 STA=0+32.38, 0.00' RIM=4858.50 8" WATER CROSSING (SEE ALIGNMENT J FOR CROSSING INFO SHEET PP-6) 12" STORM CROSSING 18 " M I N . 18 " M I N . 8" WATER CROSSING (SEE ALIGNMENT I FOR CROSSING INFO SHEET PP-6) TBC @ CL STA=0+03.50 EL=4858.37 LIP @ CL STA=0+05 EL=4857.95 ST A = 2 + 5 6 . 9 8 EL = 4 8 6 0 . 5 6 TBC @ CL STA=0+67.27 EL=4860.12 TBC @ CL STA=2+12.48 EL=4860.07 LIP @ CL STA=0+65.73 EL=4859.54 LIP @ CL STA=2+13.98 EL=4859.66 EXISTING GRADE GRADE @ ALIGNMENT CL 18 " M I N . 8" N INV IN=4852.40 8" E INV IN=4852.40 8" S INV IN=4852.40 8" W INV OUT=4852.30 SSMH #10 STA=5+18.63, 0.00' RIM=4858.70 243-LF OF 8" PVC @ 0.40% 243-LF OF 8" PVC @ 0.40% TBC @ CL STA=3+36.53 EL=4859.32 TBC @ CL STA=4+81.73 EL=4860.32 TBC @ CL STA=5+45.52 EL=4858.69 LIP @ CL STA=3+35.03 EL=4858.92 LIP @ CL STA=4+83.23 EL=4859.74 LIP @ CL STA=5+44.02 EL=4858.28 8" WATER CROSSING (SEE ALIGNMENT K FOR CROSSING INFO SHEET PP-7) 18 " M I N . 37-LF OF 8" PVC @ 0.40% CAP AT PROPERTY LINE INV= 4852.55 5-LF OF 8" WATERLINE 17-LF OF 8" WATERLINE 5-LF OF 8" WATERLINE 22-LF OF 8" WATERLINE PLUG AND THRUST BLOCK AT PROPERTY LINE INV= 4851.59 18 " M I N . 8"x8" TEE W/ 45° ELBOW (SEE ALIGNMENT "K" FOR LOCATION) 030'30'15' SCALE: 1" = 30' 11 PP - 5 AL I G N B Fi l e L o c a t i o n : z: \ p r o j e c t s \ 2 0 2 2 \ 2 2 1 2 5 m a d i s o n s t a t i o n a p a r t m e n t s \ 3 . 0 d e s i g n \ 3 . 1 c a d \ 3 . 1 3 f i n a l \ 2 2 1 2 5 p p 5 a l i g n b . d w g Pl o t t e d B y : ru s s e l l Da t e P l o t t e d : We d n e s d a y , M a r c h 2 2 2 0 2 3 a t 0 3 : 3 0 P M AG L E R O C K N G I N E E R I N G SU R V E Y E D B Y : DR A W N B Y : PR O J E C T N O . AP P R O V E D B Y : DE S C R I P T I O N DA T E RE V I S I O N S 1 2 3 4 5 6 AT T E N T I O N Th i s d o c u m e n t o r a n y p a r t t h e r e o f i n d e t a i l o r d e s i g n c o n c e p t is t h e p r o p e r t y o f E a g l e R o c k E n g i n e e r i n g a n d s h a l l n o t b e co p i e d i n a n y f o r m w i t h o u t t h e w r i t t e n a u t h o r i z a t i o n o f E a g l e Ro c k E n g i n e e r i n g . E SH E E T N O . SH E E T N A M E CI V I L P L A N N I N G S U R V E Y I N G ID A H O F A L L S ( 2 0 8 ) 5 4 2 - 2 6 6 5 RE X B U R G ( 2 0 8 ) 3 5 9 - 2 6 6 5 PR E P A R E D F O R : RY A N N E L S O N MA D I S O N S T A T I O N A P A R T M E N T S A. S N A R R R. J O R D A N P. S N A R R 22 1 2 5 P R E L I M I N A R Y N O T A P P R O V E D F O R C O N S T R U C T I O N 16 4 1 0 KEY MAP W E S N A B C D F H I J K E G W E SN ALIGNMENT "B" CONSTRUCTION ITEMS: THE FOLLOWING CONSTRUCTION ITEMS ARE FOR THE PURPOSE OF DISPLAY IN THE PLAN AND PROFILE VIEW ONLY AND DO NOT SHOW EACH AND EVERY CONSTRUCTION COMPONENT IN THE DESIGN. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO REVIEW THE PLANS AND UNDERSTAND THAT ALL ELBOWS, TEES, ADA ACCESSES, FIRE HYDRANTS, ETC.... MAY NOT BE LABELED BUT ARE REQUIRED FOR A COMPLETE PROJECT. ASPHALT PAVING PER DETAIL 9 ON SHEET D-1.SEWER MANHOLE TYPE A PER LATEST REVISION OF CITY OF REXBURG STANDARDS. SEE DETAIL X ON SHEET D-X. WATER MAIN VALVE AND VALVE BOX MEETING WATER MAIN SIZE PER CITY OF REXBURGSTANDARDS. FIRE HYDRANT ASSEMBLY PER CITY OF REXBURG STANDARDS. SEE DETAIL 5 ON SHEET D-1. 2" FIRE SERVICE LINE (CLUBHOUSE) PER CITY OF REXBURG STANDARDS TO MECHANICAL ROOM WITH REMOTE READOUT PER JRW ARCHITECTURAL PLANS. 1.5' LIP UP CURB PER DETAIL 7 ON SHEET D-1. INSTALL STORM DRAIN MANHOLE PER CITY OF REXBURG STANDARDS. 8"x8" TEE WITH THRUST BLOCK. SEE DETAIL 3 ON SHEET D-2. PAVING AND DRAINAGE CONSTRUCTION ITEMS SEWER CONSTRUCTION ITEMS 1 2 4 6 INSTALL ADA RAMP AND TRUNCATED DOMES PER CITY OF REXBURG STADARDS. 1 2 WATER CONSTRUCTION ITEMS 5 CATCH BASIN PER DETAIL 1 ON SHEET D-2. 1 2 3 4 5 7 8"x6" TEE WITH THRUST BLOCK. SEE DETAIL 3 ON SHEET D-2. 8 3 9 6' SIDEWALK PER CITY OF REXBURG STANDARDS. 6 7 BEND (ANGLE PER PLAN) WITH THRUST BLOCK. SEE DETAIL 3 ON SHEET D-2. 8 8"x8" CROSS WITH THRUST BLOCK. SEE DETAIL 3 ON SHEET D-2. 10 11 12 9 10 PLUG AND THRUST BLOCK. 11 1.5' LIP DOWN CURB PER DETAIL 8 ON SHEET D-1. 5' SIDEWALK PER CITY OF REXBURG STANDARDS. TRASH ENCLOSURE PER CITY OF REXBURG STANDARDS. INSTALL SC-740 INFILTRATION SYSTEM. SEE STORM TABLES ON SHEET C-4 FOR SYSTEM SPECIFICATIONS. PER DETAIL 6 ON SHEET D-1. TRANSITION CURB LIP UP TO LIP DOWN. NOT USED 6" SANITARY SEWER SERVICE PER LATEST REVISION OF CITY OF REXBURG STANDARDS. SEE DETAIL 2 ON SHEET D-1. (APARTMENT BUILDINGS)3 NOT USED NOT USED NOT USED 4 5 6 11 2" WATER SERVICE PER CITY OF REXBURG STANDARDS. WATER METER TO BEINSTALLED IN MECHANICAL ROOM W/ REMOTE READOUT PER JRW ARCHITECTURAL PLANS. NOT USED NOT USED 4" FIRE SERVICE PER CITY OF REXBURG STANDARDS TO MECHANICAL ROOM PER JRW ARCHITECTURAL PLANS. 4" SANITARY SEWER SERVICE PER LATEST REVISION OF CITY OF REXBURG STANDARDS. SEE DETAIL 2 ON SHEET D-1. (CLUBHOUSE) PLUG AND THRUST BLOCK 8" WATERLINE AT PROPERTY LINE CAP 8" SANITARY SEWER STUB AT PROPERTY LINE 4850 4852 4854 4856 4858 4860 4862 4850 4852 4854 4856 4858 4860 4862 0+00 1+00 2+00 3+00 3+40 E INV OUT=4853.89 CB #1C STA=0+09.01, 2.77' L GRATE=4856.90 E INV IN=4853.84 W INV IN=4853.84 N INV OUT=4853.74 SDMH #1D STA=0+31.03, 11.50' L RIM=4857.30 24-LF OF 12" PVC @ 0.22%49-LF OF 12" PVC @ 0.22% 49-LF OF 12" PVC @ 0.22% 213-LF OF 12" PVC @ 0.22% NW INV OUT=4855.10 CB #1E STA=1+06.17, 30.52' R RIM=4858.10 SE INV IN=4855.90 W INV OUT=4854.52 SDMH #1F STA=2+93.50, 11.50' L RIM=4860.00 48-LF OF 12" PVC @ 0.22% NW INV OUT=4856.00 CB #1F STA=3+36.51, 8.90' R GRATE=4859.00 12" E INV IN=4854.05 12" SE INV IN=4854.99 12" N INV IN=4855.62 12" W INV OUT=4853.95 SDMH #1E STA=0+80.29, 11.50' L RIM=4859.00 176-LF OF 8" WATERLINE 5-LF OF 8" WATERLINE EXISTING GRADE GRADE @ ALIGNMENT CL GB/STA=0+71.57 EL=4858.93LIP @ CL STA=0+09.01 EL=4857.12 12" S INV OUT=4855.80 CB #1D STA=0+80.29, 91.53' L RIM=4858.80 8" N INV IN=4853.47 8" S INV OUT=4853.37 SSMH #12 STA=2+43.61, 29.51' L RIM=4860.20 6' M I N . B U R Y INSTALL FH STA=0+58.53 18 " M I N . 5-LF OF 8" WATERLINE 20-LF OF 8" WATERLINE 5-LF OF 8" WATERLINE 50-LF OF 8" WATERLINE 4850 4852 4854 4856 4858 4860 4850 4852 4854 4856 4858 4860 0+00 1+00 2+00 3+003+00 S INV OUT=4855.80 CB #1D STA=0+62.29, 30.51' L RIM=4858.80 5-LF OF 8" WATERLINE 38-LF OF 8" WATERLINE 12-LF OF 8" WATERLINE 8" SS CROSSING 5-LF OF 8" WATERLINE 20-LF OF 8" WATERLINE 5-LF OF 8" WATERLINE MAINTAIN 18" VERTICAL SEPARATION POTABLE & NON-POTABLE WATER. 10' EACH SIDE OF NON-POTABLE WATER LINE. (4) 45° ELBOWS 18 " M I N . EXISTING GRADE GRADE @ ALIGNMENT CLGB/STA=0+53.54 EL=4859.46 GB/STA=2+84.22 EL=4860.56 6" M I N . B U R Y INSTALL FH STA=0+40.53 INSTALL FH STA=2+90.50 6' ' P S 6' ' P S 6' ' P S 6' ' P S 6' ' P S 6' ' P S 6' ' P S 6' ' P S 6' ' P S 6' ' P S 6' ' P S 6' ' P S (1 2 ' ' S D (1 2 ' ' S D 8' ' W 8' ' W 8' ' W 8' ' W 8' ' W 8''W 8''W 8''W 8''W 8''W 8''W 8''W 8''W 8''W 8''W 8''W 8''W (12''SD (12''SD (12''SD (12''SD 8' ' W ( 1 2 ' ' S D 12 ' ' S D ) (12'' S D GB GB GB GB GB GB GB GB GB GB GB GB GB GB GB GB GB GB GB GB GB (12''SD GB GBGB GB G B G B 8' ' S S ) 8' ' S S ) 6''FS 6''FS2''FS 2''FS 6''SS 6''SS 6''SS 6''SS 6''SS 6''SS 8' ' S S ) 8' ' S S ) BLDG FF: 60.30 TBC/LP: 59.40 TBC: 59.70 TBC: 59.60 TBC: 59.68 TBC: 60.35 TBC: 60.35 TBC: 60.35 TBC: 58.00 TBC: 58.30 TBC: 57.85 TBC: 57.75 TBC/LP: 57.50 TBC: 59.30 TBC: 59.80 OIL: 60.90OIL: 60.20 TBC: 60.70 CB #1F SDMH #1E CB #1D SDMH #1D CB #1C SDMH #1F SSMH #12 TBC: 58.90 TBC: 59.20 TBC/LP: 58.70 TBC: 58.79 TBC: 58.88 TBC: 59.60 TBC: 58.70 TBC: 59.00 3+000+00 1+00 2+00 3+00 3+40 0+00 1+00 2+00 3+00 TBC: 59.10 TBC: 59.88 TBC: 60.00 TBC/LP: 59.60 ALIGNMENT "I" ALIGNMENT "J" 1 22 2 2 2 3 4 6 9 9 9 BLDG FF: 62.40 BLDG FF: 61.70 BLDG FF: 62.10BLDG FF: 61.70 4 4 3 1 4 2 5 15 4 7 7 9 10 113 11 2 TBC: 60.24 TBC: 60.04 ALIGNMENT "J" W E S N 12 PP - 6 AL I G N M E N T I & J Fi l e L o c a t i o n : z: \ p r o j e c t s \ 2 0 2 2 \ 2 2 1 2 5 m a d i s o n s t a t i o n a p a r t m e n t s \ 3 . 0 d e s i g n \ 3 . 1 c a d \ 3 . 1 3 f i n a l \ 2 2 1 2 5 p p 6 a l i g n i _ j . d w g Pl o t t e d B y : ru s s e l l Da t e P l o t t e d : We d n e s d a y , M a r c h 2 2 2 0 2 3 a t 0 3 : 3 0 P M ALIGNMENT "I" AG L E R O C K N G I N E E R I N G SU R V E Y E D B Y : DR A W N B Y : PR O J E C T N O . AP P R O V E D B Y : DE S C R I P T I O N DA T E RE V I S I O N S 1 2 3 4 5 6 AT T E N T I O N Th i s d o c u m e n t o r a n y p a r t t h e r e o f i n d e t a i l o r d e s i g n c o n c e p t is t h e p r o p e r t y o f E a g l e R o c k E n g i n e e r i n g a n d s h a l l n o t b e co p i e d i n a n y f o r m w i t h o u t t h e w r i t t e n a u t h o r i z a t i o n o f E a g l e Ro c k E n g i n e e r i n g . E SH E E T N O . SH E E T N A M E CI V I L P L A N N I N G S U R V E Y I N G ID A H O F A L L S ( 2 0 8 ) 5 4 2 - 2 6 6 5 RE X B U R G ( 2 0 8 ) 3 5 9 - 2 6 6 5 PR E P A R E D F O R : RY A N N E L S O N MA D I S O N S T A T I O N A P A R T M E N T S A. S N A R R R. J O R D A N P. S N A R R 22 1 2 5 P R E L I M I N A R Y N O T A P P R O V E D F O R C O N S T R U C T I O N 16 4 1 0 KEY MAP W E S N A B C D F H I J K E G 030'30'15' SCALE: 1" = 30' CONSTRUCTION ITEMS: THE FOLLOWING CONSTRUCTION ITEMS ARE FOR THE PURPOSE OF DISPLAY IN THE PLAN AND PROFILE VIEW ONLY AND DO NOT SHOW EACH AND EVERY CONSTRUCTION COMPONENT IN THE DESIGN. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO REVIEW THE PLANS AND UNDERSTAND THAT ALL ELBOWS, TEES, ADA ACCESSES, FIRE HYDRANTS, ETC.... MAY NOT BE LABELED BUT ARE REQUIRED FOR A COMPLETE PROJECT. ASPHALT PAVING PER DETAIL 9 ON SHEET D-1.SEWER MANHOLE TYPE A PER LATEST REVISION OF CITY OF REXBURG STANDARDS. SEE DETAIL X ON SHEET D-X. WATER MAIN VALVE AND VALVE BOX MEETING WATER MAIN SIZE PER CITY OF REXBURGSTANDARDS. FIRE HYDRANT ASSEMBLY PER CITY OF REXBURG STANDARDS. SEE DETAIL 5 ON SHEET D-1. 2" FIRE SERVICE LINE (CLUBHOUSE) PER CITY OF REXBURG STANDARDS TO MECHANICAL ROOM WITH REMOTE READOUT PER JRW ARCHITECTURAL PLANS. 1.5' LIP UP CURB PER DETAIL 7 ON SHEET D-1. INSTALL STORM DRAIN MANHOLE PER CITY OF REXBURG STANDARDS. 8"x8" TEE WITH THRUST BLOCK. SEE DETAIL 3 ON SHEET D-2. PAVING AND DRAINAGE CONSTRUCTION ITEMS SEWER CONSTRUCTION ITEMS 1 2 4 6 INSTALL ADA RAMP AND TRUNCATED DOMES PER CITY OF REXBURG STADARDS. 1 2 WATER CONSTRUCTION ITEMS 5 CATCH BASIN PER DETAIL 1 ON SHEET D-2. 1 2 3 4 5 7 8"x6" TEE WITH THRUST BLOCK. SEE DETAIL 3 ON SHEET D-2. 8 3 9 6' SIDEWALK PER CITY OF REXBURG STANDARDS. 6 7 BEND (ANGLE PER PLAN) WITH THRUST BLOCK. SEE DETAIL 3 ON SHEET D-2. 8 8"x8" CROSS WITH THRUST BLOCK. SEE DETAIL 3 ON SHEET D-2. 10 11 12 9 10 PLUG AND THRUST BLOCK. 11 1.5' LIP DOWN CURB PER DETAIL 8 ON SHEET D-1. 5' SIDEWALK PER CITY OF REXBURG STANDARDS. TRASH ENCLOSURE PER CITY OF REXBURG STANDARDS. INSTALL SC-740 INFILTRATION SYSTEM. SEE STORM TABLES ON SHEET C-4 FOR SYSTEM SPECIFICATIONS. PER DETAIL 6 ON SHEET D-1. TRANSITION CURB LIP UP TO LIP DOWN. NOT USED 6" SANITARY SEWER SERVICE PER LATEST REVISION OF CITY OF REXBURG STANDARDS. SEE DETAIL 2 ON SHEET D-1. (APARTMENT BUILDINGS)3 NOT USED NOT USED NOT USED 4 5 6 11 2" WATER SERVICE PER CITY OF REXBURG STANDARDS. WATER METER TO BEINSTALLED IN MECHANICAL ROOM W/ REMOTE READOUT PER JRW ARCHITECTURAL PLANS. NOT USED NOT USED 4" FIRE SERVICE PER CITY OF REXBURG STANDARDS TO MECHANICAL ROOM PER JRW ARCHITECTURAL PLANS. 4" SANITARY SEWER SERVICE PER LATEST REVISION OF CITY OF REXBURG STANDARDS. SEE DETAIL 2 ON SHEET D-1. (CLUBHOUSE) 6' ' P S 6' ' P S 6' ' P S 6' ' P S S89°47'35"W 590.00' (M) 591.00' (R) 6' ' P S 6' ' P S 6' ' P S 6' ' P S 8' ' W 8' ' W 8' ' W 8''W 8''W 8''W 8''W 8''W 8''W 8''W 8''W 8''W 8''W 8''W 8''W 8''W 8''W 12''S D ) GB GB GB GB GB GB GB G B G B 6' ' F S 6' ' F S 2' ' W S 2' ' W S 6' ' F S 6' ' F S 2' ' W S 2' ' W S 6''F S 6''F S 6''F S 2'' W S 2'' W S 8''W 8' ' S S ) 8' ' S S ) 8' ' S S ) 8''SS ) (8''SS (8''SS (8''SS (8''SS (8''SS (8''SS (8''SS (8''SS (8''SS 6''SS 6''SS 6' ' S S 6' ' S S 6' ' S S 6' ' S S (8 ' ' S S 8' ' W SSMH #11 5+700+00 1+00 2+00 3+00 4+00 5+00 BLDG FF: 60.30 BLDG FF: 62.40 BLDG FF: 62.20 TBC: 57.80 TBC: 58.40 TBC: 58.48 TBC/LP: 57.70 TBC: 58.10 TBC: 58.10 TBC/LP: 57.80 TBC: 59.35 TBC: 59.75 TBC: 59.35 TBC: 60.51 TBC: 60.58 TBC: 60.65 TBC: 59.10 TBC/LP: 58.20 TBC: 58.60 TBC: 58.80 TBC: 60.00 TBC: 60.50 TBC: 61.20 TBC: 59.80 TBC: 59.80 TBC: 59.70 TBC: 59.50 TBC: 60.00TBC: 60.00TBC: 58.60 TBC: 58.50 TBC: 58.20 25 ' MI N . SMDH #5 CB #5 SDMH #6 CB #6A CB #6B 1 2 32 10 10 6 7 1 2 5 10 9 7 5 25 ' MI N . 24 . 7 5 ' 26' 26' 7 7 9 4 5 6 3 2 2 3 3 2 32 10 9 TBC/HP: 58.15 2 33 11 2 3 5 7 SSMH #9 SSMH #10 3 3 3 1 5 2 1 1 1 9 4 2 CAP 8" SANITARY SEWER STUB AT PROPERTY LINE 4848 4850 4852 4854 4856 4858 4860 4862 4848 4850 4852 4854 4856 4858 4860 4862 0+00 1+00 2+00 3+00 4+00 5+00 5+70 5-LF OF 8" WATERLINE 13-LF OF 8" WATERLINE 53-LF OF 8" WATERLINE NW INV OUT=4854.60 CB #5 STA=5+04.05, 30.89' R RIM=4857.60 12" SE INV IN=4854.58 24" W INV OUT=4852.98 SMDH #5 STA=4+96.91, 23.50' R RIM=4857.70 SE INV OUT=4854.10 CB #6B STA=0+02.98, 9.19' R GRATE=4857.10 NE INV OUT=4854.20 CB #6A STA=0+26.13, 30.89' R GRATE=4857.20 10-LF OF 12" PVC @ 0.22% 12" NW INV IN=4854.03 12" SW INV IN=4854.18 24" E INV OUT=4852.41 SDMH #6 STA=0+33.22, 23.50' R RIM=4857.40 5-LF OF 24" PVC @ 0.22%165-LF OF 8" WATERLINE EXISTING GRADE GRADE @ ALIGNMENT CL INSTALL STORM INFILTRATION SYSTEM 93'L x 16'W SC-740 ADS STORM TECH CHAMBER SYSTEM (SEE TABLE 4 SHEET C-4) INSTALL STORM INFILTRATION SYSTEM 93'L x 11'W SC-740 ADS STORM TECH CHAMBER SYSTEM (SEE TABLE 4 SHEET C-4) 6' M I N . B U R Y 5-LF OF 24" PVC @ 0.22% 10-LF OF 12" PVC @ 0.22% INSTALL FH STA=0+60.25 INSTALL FH STA=5+47.67 INSTALL FH STA=2+23.01 5-LF OF 8" WATERLINE 13-LF OF 8" WATERLINE 33-LF OF 12" PVC @ 0.22% 5-LF OF 8" WATERLINE 26-LF OF 8" WATERLINE 18 " MI N . 8" E INV IN=4851.48 8" SW INV OUT=4851.38 SSMH #9 STA=0+33.35, 5.00' R RIM=4857.80 8" N INV IN=4852.40 8" E INV IN=4852.40 8" S INV IN=4852.40 8" W INV OUT=4852.30 SSMH #10 STA=2+38.08, 5.00' R RIM=4858.70 8" W INV OUT=4853.27 SSMH #11 STA=4+56.59, 5.00' R RIM=4858.50 6-LF OF 8" WATERLINE 70-LF OF 8" PVC @ 0.40% 205-LF OF 8" PVC @ 0.40% 219-LF OF 8" PVC @ 0.40%18 " M I N . MAINTAIN 18" VERTICAL SEPARATION POTABLE & NON-POTABLE WATER. 10' EACH SIDE OF NON-POTABLE WATER LINE. (4) 45° ELBOWS 163-LF OF 8" WATERLINE 5-LF OF 8" WATERLINE 20-LF OF 8" WATERLINE 5-LF OF 8" WATERLINE 68-LF OF 8" WATERLINE 8"x8"x6" TEE W/ 45° ELBOW 8"x8" TEE W/ 45° ELBOW 14-LF OF 8" WATERLINE W E S N 030'30'15' SCALE: 1" = 30' 13 PP - 7 AL I G N M E N T K Fi l e L o c a t i o n : z: \ p r o j e c t s \ 2 0 2 2 \ 2 2 1 2 5 m a d i s o n s t a t i o n a p a r t m e n t s \ 3 . 0 d e s i g n \ 3 . 1 c a d \ 3 . 1 3 f i n a l \ 2 2 1 2 5 p p 7 a l i g n k . d w g Pl o t t e d B y : ru s s e l l Da t e P l o t t e d : We d n e s d a y , M a r c h 2 2 2 0 2 3 a t 0 3 : 3 0 P M ALIGNMENT "K" AG L E R O C K N G I N E E R I N G SU R V E Y E D B Y : DR A W N B Y : PR O J E C T N O . AP P R O V E D B Y : DE S C R I P T I O N DA T E RE V I S I O N S 1 2 3 4 5 6 AT T E N T I O N Th i s d o c u m e n t o r a n y p a r t t h e r e o f i n d e t a i l o r d e s i g n c o n c e p t is t h e p r o p e r t y o f E a g l e R o c k E n g i n e e r i n g a n d s h a l l n o t b e co p i e d i n a n y f o r m w i t h o u t t h e w r i t t e n a u t h o r i z a t i o n o f E a g l e Ro c k E n g i n e e r i n g . E SH E E T N O . SH E E T N A M E CI V I L P L A N N I N G S U R V E Y I N G ID A H O F A L L S ( 2 0 8 ) 5 4 2 - 2 6 6 5 RE X B U R G ( 2 0 8 ) 3 5 9 - 2 6 6 5 PR E P A R E D F O R : RY A N N E L S O N MA D I S O N S T A T I O N A P A R T M E N T S A. S N A R R R. J O R D A N P. S N A R R 22 1 2 5 P R E L I M I N A R Y N O T A P P R O V E D F O R C O N S T R U C T I O N 16 4 1 0 KEY MAP W E S N A B C D F H I J K E G 10 9 CONSTRUCTION ITEMS: THE FOLLOWING CONSTRUCTION ITEMS ARE FOR THE PURPOSE OF DISPLAY IN THE PLAN AND PROFILE VIEW ONLY AND DO NOT SHOW EACH AND EVERY CONSTRUCTION COMPONENT IN THE DESIGN. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO REVIEW THE PLANS AND UNDERSTAND THAT ALL ELBOWS, TEES, ADA ACCESSES, FIRE HYDRANTS, ETC.... MAY NOT BE LABELED BUT ARE REQUIRED FOR A COMPLETE PROJECT. ASPHALT PAVING PER DETAIL 9 ON SHEET D-1.SEWER MANHOLE TYPE A PER LATEST REVISION OF CITY OF REXBURG STANDARDS. SEE DETAIL X ON SHEET D-X. WATER MAIN VALVE AND VALVE BOX MEETING WATER MAIN SIZE PER CITY OF REXBURGSTANDARDS. FIRE HYDRANT ASSEMBLY PER CITY OF REXBURG STANDARDS. SEE DETAIL 5 ON SHEET D-1. 2" FIRE SERVICE LINE (CLUBHOUSE) PER CITY OF REXBURG STANDARDS TO MECHANICAL ROOM WITH REMOTE READOUT PER JRW ARCHITECTURAL PLANS. 1.5' LIP UP CURB PER DETAIL 7 ON SHEET D-1. INSTALL STORM DRAIN MANHOLE PER CITY OF REXBURG STANDARDS. 8"x8" TEE WITH THRUST BLOCK. SEE DETAIL 3 ON SHEET D-2. PAVING AND DRAINAGE CONSTRUCTION ITEMS SEWER CONSTRUCTION ITEMS 1 2 4 6 INSTALL ADA RAMP AND TRUNCATED DOMES PER CITY OF REXBURG STADARDS. 1 2 WATER CONSTRUCTION ITEMS 5 CATCH BASIN PER DETAIL 1 ON SHEET D-2. 1 2 3 4 5 7 8"x6" TEE WITH THRUST BLOCK. SEE DETAIL 3 ON SHEET D-2. 8 3 9 6' SIDEWALK PER CITY OF REXBURG STANDARDS. 6 7 BEND (ANGLE PER PLAN) WITH THRUST BLOCK. SEE DETAIL 3 ON SHEET D-2. 8 8"x8" CROSS WITH THRUST BLOCK. SEE DETAIL 3 ON SHEET D-2. 10 11 12 9 10 PLUG AND THRUST BLOCK. 11 1.5' LIP DOWN CURB PER DETAIL 8 ON SHEET D-1. 5' SIDEWALK PER CITY OF REXBURG STANDARDS. TRASH ENCLOSURE PER CITY OF REXBURG STANDARDS. INSTALL SC-740 INFILTRATION SYSTEM. SEE STORM TABLES ON SHEET C-4 FOR SYSTEM SPECIFICATIONS. PER DETAIL 6 ON SHEET D-1. TRANSITION CURB LIP UP TO LIP DOWN. NOT USED 6" SANITARY SEWER SERVICE PER LATEST REVISION OF CITY OF REXBURG STANDARDS. SEE DETAIL 2 ON SHEET D-1. (APARTMENT BUILDINGS)3 NOT USED NOT USED NOT USED 4 5 6 11 2" WATER SERVICE PER CITY OF REXBURG STANDARDS. WATER METER TO BEINSTALLED IN MECHANICAL ROOM W/ REMOTE READOUT PER JRW ARCHITECTURAL PLANS. NOT USED NOT USED 4" FIRE SERVICE PER CITY OF REXBURG STANDARDS TO MECHANICAL ROOM PER JRW ARCHITECTURAL PLANS. 4" SANITARY SEWER SERVICE PER LATEST REVISION OF CITY OF REXBURG STANDARDS. SEE DETAIL 2 ON SHEET D-1. (CLUBHOUSE) SEE SOUTHWEST SERVICE CONNECTION PLAN & PROFILE (SHEET PP-8) PLUG AND THRUST BLOCK 8" WATERLINE AT PROPERTY LINE (SEE GENERAL NOTE 1 ON SHEET 4/C-2 FOR CONNECTIVITY TO SOUTH) 6' ' P S 6' ' P S 6' ' P S W W W W SS SS SS SS SD SD SD SD SD SD 6' ' P S 6' ' P S 6' ' P S W W W W SS SS SS SS SD SD SD SD SD SD SS 8' ' S S ) (8''SS (8''SS 0+00 1+00 1+20 SSMH #7 SSMH #6 (DOGHOUSE MH) 1 1 EX. SSMH EX. SSMH 6''PS 6''PS 6''PS 6''PS 6''PS 6''PS W W S D S D S D 6''PS 6''PS 6''PS 6''PS 6''PS 6''PS 6''PS W W S D S D S D 12' ' S D ) 8' ' W 8''W 8''W 8' ' S S ) 8''SS)8''SS)8''SS) (8 ' ' S S (8 ' ' S S 2+000+00 1+00 7 7 7 1 1 SSMH #9 SSMH #8 SSMH #7 10 ' 5' 15' 19 . 5 ' ± 11 . 6 ± 4848 4850 4852 4854 4856 4858 4860 4848 4850 4852 4854 4856 4858 4860 0+00 1+00 2+00 18 " M I N . EX. 12" S.D. CROSSING SW INV OUT=4853.84 EX CB #1 STA=1+07.93, 10.95' L RIM=4857.29 10-LF OF 8" WATERLINE 18-LF OF 8" WATERLINE CONNECT NEW 8" WATER MAIN TO EXISTING 8" WATER MAIN BEFORE HYDRANT VALVE. (FIELD VERIFY DEPTH AND CONNECTION LOCATION) 6' M I N . B U R Y EX. 6" PRESSURE SEWER EXISTING FH STA=1+43.98 8" N INV IN=4850.34 8" W INV OUT=4850.24 SSMH #7 STA=1+79.55, 5.00' L RIM=4858.85± (MATCH EXISTING ASPHALT) 8" NE INV IN=4851.10 8" S INV OUT=4851.00 SSMH #8 STA=0+15.85, 5.00' L RIM=4858.46± (MATCH EXISTING ASPHALT) 164-LF OF 8" PVC @ 0.40% 111-LF OF 8" WATERLINE 12-LF OF 8" WATERLINE 70-LF OF 8" PVC @ 0.40% 6''P S 6''P S 6''P S 6''P S 6''P S 6''P S 6''P S 6''P S 8''W 8''W 8'' W 8'' W 1 2 ' ' S D ) G B G B 8''W 8''W 8''SS) (8' ' S S (8' ' S S 8''S S ) 8''S S ) TBC: 57.80 TBC: 58.40 TBC: 58.48 TBC/LP: 57.70 TBC: 58.10 TBC: 58.10 TBC/LP: 57.80 TBC: 59.35 TBC: 59.35 SDMH #6 CB #6A CB #6B TBC/HP: 58.15 7' 1+20 0+00 1+00 WATERLINE ENCASEMENT (12" C900 PRESSURE PIPE) 10 ' 10 ' 2 3 5 5 7 9 10 1 1 1 2 4 7 7 SSMH #9 SSMH #8 4846 4848 4850 4852 4854 4856 4858 4860 4862 4846 4848 4850 4852 4854 4856 4858 4860 4862 0+00 1+00 1+20 EX. 6" PRESSURE SEWER CROSSING (FIELD VERIFY DEPTH & LOCATION) 18 " M I N . 18 " M I N . (S T O R M C R O S S I N G ) 33-LF OF 12" PVC @ 0.22% SE INV OUT=4854.10 CB #6B STA=0+45.96, 11.68' R GRATE=4857.10 12" NW INV IN=4854.03 12" SW INV IN=4854.18 24" E INV OUT=4852.41 SDMH #6 STA=0+32.43, 18.92' L RIM=4857.40 5-LF OF 8" WATERLINE 13-LF OF 8" WATERLINE 5-LF OF 8" WATERLINE 26-LF OF 8" WATERLINE 20' TO BE ENCASED WITH 12" C-900 PRESSURE PIPE 5-LF OF 8" WATERLINE 20-LF OF 8" WATERLINE 5-LF OF 8" WATERLINE NOTE: SEWER LINE NOT SHOWN FOR CLARITY OF WATER CROSSING 7-LF OF 8" WATERLINE 111-LF OF 8" WATERLINE 4846 4848 4850 4852 4854 4856 4858 4860 4846 4848 4850 4852 4854 4856 4858 4860 0+00 1+00 1+20 8" N INV IN=4849.76 8" E INV IN=4849.86 8" S INV OUT=4849.76 SSMH #6 (DOGHOUSE MH) STA=0+11.28, 0.00' L RIM=4857.80± (MATCH EXISTING ASPHALT) 8" N INV IN=4850.34 8" W INV OUT=4850.24 SSMH #7 STA=1+05.57, 0.00' RIM=4858.85± (MATCH EXISTING ASPHALT) (EX.) (EX.) 94-LF OF 8" PVC @ 0.40% EXISTING 6" PRESSURE SEWER EXISTING GRADE W E S N 030'30'15' SCALE: 1" = 30' 14 PP - 8 SO U T H W E S T S E R V I C E C O N N E C T I O N S Fi l e L o c a t i o n : z: \ p r o j e c t s \ 2 0 2 2 \ 2 2 1 2 5 m a d i s o n s t a t i o n a p a r t m e n t s \ 3 . 0 d e s i g n \ 3 . 1 c a d \ 3 . 1 3 f i n a l \ 2 2 1 2 5 p p 8 s w s e r v i c e c o n n e c t i o n s . d w g Pl o t t e d B y : ru s s e l l Da t e P l o t t e d : We d n e s d a y , M a r c h 2 2 2 0 2 3 a t 0 3 : 3 1 P M AG L E R O C K N G I N E E R I N G SU R V E Y E D B Y : DR A W N B Y : PR O J E C T N O . AP P R O V E D B Y : DE S C R I P T I O N DA T E RE V I S I O N S 1 2 3 4 5 6 AT T E N T I O N Th i s d o c u m e n t o r a n y p a r t t h e r e o f i n d e t a i l o r d e s i g n c o n c e p t is t h e p r o p e r t y o f E a g l e R o c k E n g i n e e r i n g a n d s h a l l n o t b e co p i e d i n a n y f o r m w i t h o u t t h e w r i t t e n a u t h o r i z a t i o n o f E a g l e Ro c k E n g i n e e r i n g . E SH E E T N O . SH E E T N A M E CI V I L P L A N N I N G S U R V E Y I N G ID A H O F A L L S ( 2 0 8 ) 5 4 2 - 2 6 6 5 RE X B U R G ( 2 0 8 ) 3 5 9 - 2 6 6 5 PR E P A R E D F O R : RY A N N E L S O N MA D I S O N S T A T I O N A P A R T M E N T S A. S N A R R R. J O R D A N P. S N A R R 22 1 2 5 P R E L I M I N A R Y N O T A P P R O V E D F O R C O N S T R U C T I O N 16 4 1 0 KEY MAP W E S N A B C D F H I J K E G CONSTRUCTION ITEMS: THE FOLLOWING CONSTRUCTION ITEMS ARE FOR THE PURPOSE OF DISPLAY IN THE PLAN AND PROFILE VIEW ONLY AND DO NOT SHOW EACH AND EVERY CONSTRUCTION COMPONENT IN THE DESIGN. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO REVIEW THE PLANS AND UNDERSTAND THAT ALL ELBOWS, TEES, ADA ACCESSES, FIRE HYDRANTS, ETC.... MAY NOT BE LABELED BUT ARE REQUIRED FOR A COMPLETE PROJECT. ASPHALT PAVING PER DETAIL 9 ON SHEET D-1.SEWER MANHOLE TYPE A PER LATEST REVISION OF CITY OF REXBURG STANDARDS. SEE DETAIL X ON SHEET D-X. WATER MAIN VALVE AND VALVE BOX MEETING WATER MAIN SIZE PER CITY OF REXBURGSTANDARDS. FIRE HYDRANT ASSEMBLY PER CITY OF REXBURG STANDARDS. SEE DETAIL 5 ON SHEET D-1. 2" FIRE SERVICE LINE (CLUBHOUSE) PER CITY OF REXBURG STANDARDS TO MECHANICAL ROOM WITH REMOTE READOUT PER JRW ARCHITECTURAL PLANS. 1.5' LIP UP CURB PER DETAIL 7 ON SHEET D-1. INSTALL STORM DRAIN MANHOLE PER CITY OF REXBURG STANDARDS. 8"x8" TEE WITH THRUST BLOCK. SEE DETAIL 3 ON SHEET D-2. PAVING AND DRAINAGE CONSTRUCTION ITEMS SEWER CONSTRUCTION ITEMS 1 2 4 6 INSTALL ADA RAMP AND TRUNCATED DOMES PER CITY OF REXBURG STADARDS. 1 2 WATER CONSTRUCTION ITEMS 5 CATCH BASIN PER DETAIL 1 ON SHEET D-2. 1 2 3 4 5 7 8"x6" TEE WITH THRUST BLOCK. SEE DETAIL 3 ON SHEET D-2. 8 3 9 6' SIDEWALK PER CITY OF REXBURG STANDARDS. 6 7 BEND (ANGLE PER PLAN) WITH THRUST BLOCK. SEE DETAIL 3 ON SHEET D-2. 8 8"x8" CROSS WITH THRUST BLOCK. SEE DETAIL 3 ON SHEET D-2. 10 11 12 9 10 PLUG AND THRUST BLOCK. 11 1.5' LIP DOWN CURB PER DETAIL 8 ON SHEET D-1. 5' SIDEWALK PER CITY OF REXBURG STANDARDS. TRASH ENCLOSURE PER CITY OF REXBURG STANDARDS. INSTALL SC-740 INFILTRATION SYSTEM. SEE STORM TABLES ON SHEET C-4 FOR SYSTEM SPECIFICATIONS. PER DETAIL 6 ON SHEET D-1. TRANSITION CURB LIP UP TO LIP DOWN. NOT USED 6" SANITARY SEWER SERVICE PER LATEST REVISION OF CITY OF REXBURG STANDARDS. SEE DETAIL 2 ON SHEET D-1. (APARTMENT BUILDINGS)3 NOT USED NOT USED NOT USED 4 5 6 11 2" WATER SERVICE PER CITY OF REXBURG STANDARDS. WATER METER TO BEINSTALLED IN MECHANICAL ROOM W/ REMOTE READOUT PER JRW ARCHITECTURAL PLANS. NOT USED NOT USED 4" FIRE SERVICE PER CITY OF REXBURG STANDARDS TO MECHANICAL ROOM PER JRW ARCHITECTURAL PLANS. 4" SANITARY SEWER SERVICE PER LATEST REVISION OF CITY OF REXBURG STANDARDS. SEE DETAIL 2 ON SHEET D-1. (CLUBHOUSE) W E SN 030'30'15' SCALE: 1" = 30' ALIGNMENT "SOUTHWEST SERVICE CONNECTION (2)" SAW-CUT EX. ASPHALT FOR WATERLINE CONNECTION TO EX. WATERMAIN & REPAIR PER REXBURG STANDARDSPRESERVE & PROTECT EX. CURB & GUTTER PRESERVE & PROTECT EX. CURB & GUTTER EXISTING BUILDING CONNECT TO EXISTING 8" WATER MAIN & THRUST BLOCK PER REXBURG STANDARDS (FIELD VERIFY CONNECTION LOCATION & DEPTH) 18-LF OF 8" WATERLINE PRESERVE & PROTECT EX. VALVE & HYDRANT W E S N 030'30'15' SCALE: 1" = 30' 70-LF OF 8" PVC @ 0.40% SAW-CUT EX. ASPHALT FOR SERVICE CONNECTIONS TO EX. WATERMAIN & SEWER. REPAIR ASPHALT PER REXBURG STANDARDS SAW-CUT EX. ASPHALT FOR SERVICE CONNECTIONS TO EX. WATERMAIN & SEWER. REPAIR ASPHALT PER REXBURG STANDARDS PRESERVE & PROTECT EX. CURB & GUTTER PRESERVE & PROTECT EX. VALVE & HYDRANT CONNECT TO EXISTING 8" SEWER LINE WITH DOGHOUSE MH (FIELD VERIFY CONNECTION POINT & DEPTH) PRESERVE & PROTECT EX. CURB & GUTTER 70-LF OF 8" PVC @ 0.40% 15 ' P . U . E . ALIGNMENT "SOUTHWEST SERVICE CONNECTION (1)"ALIGNMENT "SOUTHWEST SERVICE CONNECTION (3)" SAW-CUT EX. ASPHALT FOR SERVICE CONNECTIONS TO EX. WATERMAIN & SEWER. REPAIR ASPHALT PER REXBURG STANDARDS 50' P.U.E. P.U.E. P.U.E. TO E TO E TO E TO E TO E TO E TO E TO E TO E TOE TO E TO E TO E TO E TO E TO E TO E TO E TO E TO E TO E TO E TO E TO E TO E TO E TO E TO E TO E UGP UGP UGP UGP UGP UGP UGP UG P UG P UG P (8''SS (8''SS (8''SS (8''SS (8''SS (8''SS 8''W 8''W 8''W 8''W 8''W 8''W 8''W 8''W 8''W 8''W 8''W 8''W W6' ' P S 6' ' P S 6' ' P S 6' ' P S 6' ' P S 6' ' P S 6' ' P S 6' ' P S 6' ' P S 6' ' P S 6' ' P S 6' ' P S 6' ' P S 6' ' P S 6' ' P S LOT 1 BLOCK 1 555657 SF 12.756AC. N0 0 ° 1 5 ' 5 5 " W 1 5 1 . 6 8 ' C1 C2 62.05' C 3 S30 ° 0 8 ' 1 8 " W 9 5 9 . 9 1 ' ( M ) 9 6 0 . 1 4 ' ( R ) S89°47'35"W 590.00' (M) 591.00' (R) EA S T E R N I D A H O R A I L R O A D TREJO STREET SO U T H Y E L L O W S T O N E H I G H W A Y 70 ' RO W N0 0 ° 1 6 ' 0 5 " W 6 0 4 . 8 6 ' ( M ) 6 0 5 . 0 0 ' ( R ) N89°47'52"E 599.99' TO E TO E TO E TO E TO E TO E TO E TO E TO E TOE TO E TO E TO E TO E TO E TO E TO E TO E TO E TO E TO E TO E TO E TO E TO E TO E TO E TO E TO E UGP UGP UGP UGP UGP UGP UGP UG P UG P UG P (8''SS (8''SS (8''SS (8''SS (8''SS (8''SS 8''W 8''W 8''W 8''W 8''W 8''W 8''W 8''W 8''W 8''W 8''W 8''W W6' ' P S 6' ' P S 6' ' P S 6' ' P S 6' ' P S 6' ' P S 6' ' P S 6' ' P S 6' ' P S 6' ' P S 6' ' P S 6' ' P S 6' ' P S 6' ' P S 6' ' P S (1 2 ' ' S D (1 2 ' ' S D (1 2 ' ' S D (1 2 ' ' S D (12''SD (12''SD (12''SD 12''SD) 12 ' ' S D ) GB GB G B G B GB GB GB GB GB GB GB GB GB GB GB GB GB GB GB 12 ' ' S D ) GB GB GB GB GB GB GB GB GB G B G B G B GB GB FO FO FO FOFO FO FO FO FO 12' ' S D ) 1 2 ' ' S D ) Fi l e L o c a t i o n : z: \ p r o j e c t s \ 2 0 2 2 \ 2 2 1 2 5 m a d i s o n s t a t i o n a p a r t m e n t s \ 3 . 0 d e s i g n \ 3 . 1 c a d \ 3 . 1 3 f i n a l \ 2 2 1 2 5 s w p p p . d w g Pl o t t e d B y : ru s s e l l Da t e P l o t t e d : We d n e s d a y , M a r c h 2 2 2 0 2 3 a t 0 3 : 3 1 P M W E S N 040'40'20' SCALE: 1" = 40' 14 SW P P P ST O R M W A T E R P O L L U T I O N P R E V E N T I O N P L A N AG L E R O C K N G I N E E R I N G SU R V E Y E D B Y : DR A W N B Y : PR O J E C T N O . AP P R O V E D B Y : DE S C R I P T I O N DA T E RE V I S I O N S 1 2 3 4 5 6 AT T E N T I O N Th i s d o c u m e n t o r a n y p a r t t h e r e o f i n d e t a i l o r d e s i g n c o n c e p t is t h e p r o p e r t y o f E a g l e R o c k E n g i n e e r i n g a n d s h a l l n o t b e co p i e d i n a n y f o r m w i t h o u t t h e w r i t t e n a u t h o r i z a t i o n o f E a g l e Ro c k E n g i n e e r i n g . E SH E E T N O . SH E E T N A M E CI V I L P L A N N I N G S U R V E Y I N G ID A H O F A L L S ( 2 0 8 ) 5 4 2 - 2 6 6 5 RE X B U R G ( 2 0 8 ) 3 5 9 - 2 6 6 5 PR E P A R E D F O R : RY A N N E L S O N MA D I S O N S T A T I O N A P A R T M E N T S A. S N A R R R. J O R D A N P. S N A R R 22 1 2 5 P R E L I M I N A R Y N O T A P P R O V E D F O R C O N S T R U C T I O N 16 4 1 0 1. CONTRACTOR IS RESPONSIBLE FOR THE OFFICIAL WRITTEN SWPPP AND NOI MEETING EPA REGULATIONS. 2.CONTRACTOR SHALL INSTALL A DIRT BERM OR SILT FENCE AROUND THE PERIMETER OF THE SITE(S) WHERE EARTHWORK IS TAKING PLACE TO LIMIT POLLUTANT DISCHARGE LEAVING THIS SITE AND ENTERING ADJACENT PROPERTIES. THIS CAN BE INDIVIDUAL BUILDING SITES OR ENTIRE PERIMETER. CONTRACTOR TO MAINTAIN BERM OR SILT FENCE REGULARLY TO ENSURE SEDIMENT AND OTHER CONTAMINANTS FROM MIGRATING OFF PROJECT SITE. 3. CONTRACTOR TO ESTABLISH A STAGING AREA FOR FUELING AND ENSURE COMPLIANCE WITH SPILL PREVENTION AND CONTAINMENT BEFORE THE START OF ON SITE CONSTRUCTION ACTIVITIES. 4.CONTRACTOR SHALL ENSURE TRUCKS EXITING THE PROJECT SITE ARE NOT TRACKING MATERIAL OFF SITE. IN THE CASE TRACKING MATERIAL OFF SITE OCCURS, THE CONTRACTOR SHALL HAVE A PICK-UP BROOM (OR OTHER EQUIPMENT) ON SITE TO ENSURE THE OFFSITE ROADWAYS REMAIN CLEAN. THIS WILL BE SCHEDULED ON AN AS NEEDED BASIS. 5.IF THE CONTRACTOR DOESN'T CONTROL THE TRACKING OF MATERIAL ONTO THE CITY/COUNTY ROADWAYS TO THE SATISFACTION OF THE CITY, THE CITY MAY SHUT DOWN THE PROJECT UNTIL THE CONTRACTOR INSTALLS ANTI TRACKING PADS (STONE OR CORRUGATED STEEL PANELS) AT A DESIGNATED EXIT POINT PRIOR TO EXITING THE SITE. 6. CONTRACTOR TO INSPECT EQUIPMENT/VEHICLE STORAGE AREA AND FUEL TANK WEEKLY AND AFTER STORM EVENTS. LEAKS TO BE REPAIRED IMMEDIATELY. SPILL CLEANUP MATERIALS SHALL BE AVAILABLE ON SITE AND PROPER DISPOSAL OF CONTAMINATED MATERIAL SHALL BE DISPOSED OF PER EPA GUIDELINES. 7. INSTALL CONSTRUCTION RACK/MAT, SHAKER PLATE, RUMBLE RACK OR EQUAL TO MITIGATE TRACKING OFF SITE. CONTRACTOR TO SUBMIT SPECIFICATIONS TO ENGINEER FOR APPROVAL. BERM ALONG PERIMETER CONCRETE WASH-OUT STABALIZE CONSTRUCTION ENTRANCE (SEE NOTE 7) INLET PROTECTION CONCRETE WASHOUT STABILIZED CONSTRUCTION ENTRANCE SEE BALLAST DETAILROADWAY UNDER CONSTRUCTION EXISTING PAVED ROADWAY SHOULDER TO SHOULDER WIDTH 100' M I N E X C E P T 5 0 ' M I N F O R P R O J E C T SITE S O F L E S S T H A N 1 A C R E GEO-TEXTILE FILTER FABRIC BALLAST DETAIL 12" MIN. COMPACTED FRACTURED STONE LEGEND: NO SCALE NO SCALE BERM AROUND PERIMETER 12" WIDE MINIMUM 10 mil PLASTIC LINING 2 FEET DEEP MINIMUM8' MIN. LATH AND FLAGGING ON 3 SIDES 8' MIN. A A NOTES: 1.ACTUAL LAYOUT DETERMINED IN THE FIELD 2.THE CONCRETE WASHOUT SIGN SHALL BE INSTALLED WITHIN 32 FEET OF THE TEMPORARY CONCRETE WASHOUT FACILITY 3.WASH OUT CONCRETE TRUCKS IN DESIGNATED AREAS ONLY 4.AVOID MIXING EXCESS CONCRETE 5.WASHOUT AREA CAN ALSO BE USED FOR SHEET ROCK MUD, STUCCO, MASONRY, ETC. 6.COLLECT LIQUID WASTE IN A TEMPORARY LINED PIT AND ALLOW IT TO DRY 7.THE PIT SHOULD BE LARGE ENOUGH TO CONTAIN ALL WASTE FROM WASHOUT 8.LOCATE WASHOUT FACILITIES A MINIMUM OF 50 FEET FROM STORM DRAIN OR RECEIVING WATERS 9.KEEP THE WASHOUT AREAS AWAY FROM ARES OF CONSTRUCTION TRAFFIC 10.INSPECT DAILY WHEN IN USE 11.ALLOW WASTE TO DRY AND THEN DISPOSE OF AS SOLID WASTE 12.MAINTAIN WASHOUTS TO PROVIDE A MINIMUM 1 FOOT FREE-BOARD FOR BELOW GRADE FACILITIES 13.CLEAN LEAN EXISTING FACILITIES OR CONSTRUCT ADDITIONAL FACILITES WHEN THE WASHOUT IS 50% FULL CONCRETE WASHOUT SIGN DETAIL (OR EQUIVALENT) CONCRETE WASHOUT BERM SECTION A-A NATURAL GROUND LATH AND FLAGGING ON 3 SIDES BERM AROUND PERIMETER 12" WIDE MINIMUM 10 mil PLASTIC LINING 2' MIN. SWPPP PLAN NOTES DETAIL A-A Fi l e L o c a t i o n : z: \ p r o j e c t s \ 2 0 2 2 \ 2 2 1 2 5 m a d i s o n s t a t i o n a p a r t m e n t s \ 3 . 0 d e s i g n \ 3 . 1 c a d \ 3 . 1 3 f i n a l \ 2 2 1 2 5 d e t a i l s . d w g Pl o t t e d B y : ru s s e l l Da t e P l o t t e d : We d n e s d a y , M a r c h 2 2 2 0 2 3 a t 0 3 : 3 1 P M 15 D- 1 DE T A I L S AG L E R O C K N G I N E E R I N G SU R V E Y E D B Y : DR A W N B Y : PR O J E C T N O . AP P R O V E D B Y : DE S C R I P T I O N DA T E RE V I S I O N S 1 2 3 4 5 6 AT T E N T I O N Th i s d o c u m e n t o r a n y p a r t t h e r e o f i n d e t a i l o r d e s i g n c o n c e p t is t h e p r o p e r t y o f E a g l e R o c k E n g i n e e r i n g a n d s h a l l n o t b e co p i e d i n a n y f o r m w i t h o u t t h e w r i t t e n a u t h o r i z a t i o n o f E a g l e Ro c k E n g i n e e r i n g . E SH E E T N O . SH E E T N A M E CI V I L P L A N N I N G S U R V E Y I N G ID A H O F A L L S ( 2 0 8 ) 5 4 2 - 2 6 6 5 RE X B U R G ( 2 0 8 ) 3 5 9 - 2 6 6 5 PR E P A R E D F O R : RY A N N E L S O N MA D I S O N S T A T I O N A P A R T M E N T S A. S N A R R R. J O R D A N P. S N A R R 22 1 2 5 P R E L I M I N A R Y N O T A P P R O V E D F O R C O N S T R U C T I O N 16 4 1 0 MIN. GRADE 1/4"/FT.(2%) "E" "D" CAP OR PLUG AND INSTALL SERVICE LINE MARKER PER SD-512 (TYP.) ABSOLUTE MIN. GRADE 1/8"/FT.(1%) 4"-1/8 OR 1/16 BEND AS NEEDED MIN. GRADE 1/4"/FT.(2%) "C" "B" "A" TYPE C TEE OR APPROVED CONNECTION NOTES: TYPE E 45° TYPE A & D TEE OR APPROVED CONNECTION LP 45 ° M A X . 1/8 LONG RADIUS BEND TYPE B 45 ° M A X . GASKET ALL JOINTS CONCRETE COLLAR FINISHED GRADEFRAME & COVER 45° FL O W SHE L F SHE L F SH E L F MANHOLE NOTES: 5" FLEXIBLE RUBBER GASKET PRECAST MONOLITHIC CONCENTRIC CONE SECTION PRECAST CONCRETE MANHOLE-BARREL SECTIONS AS REQ'D PREFABRICATED BASE. UNDISTURBED EARTH A 4 A P P R O V E D BE D D I N G 6" MIN31 " 48" DIA 9 M I N RUBBER BOOT .7 5 X D i P I P E 1.PLACE VERTICAL WALL ON UPSTREAM SIDE OF MANHOLE, ROTATED 45 DEGREES. 2.WHERE PVC PIPE IS UTILIZED, INSTALL A RUBBER RING OR GASKET COLLAR WHERE THE PIPE IS IN CONTACT WITH MANHOLE BASE AND/OR MANHOLE CHANNEL, IN ORDER TO INSURE A WATERTIGHT SEAL. 3.UNLESS OTHERWISE SHOWN, MANHOLES SHALL HAVE 0.1 FALL FROM UPSTREAM INVERT TO DOWNSTREAM INVERT. FOR PIPE SLOPES GREATER THAN 2.5% SLOPE, SEE PLAN & PROFILE. PLAN DETAIL NOT TO SCALE SEWER MANHOLE SECTION1 NOT TO SCALE 6" SANITARY SEWER SERVICE LINES DETAIL2 NOT TO SCALE TYPICAL SEWER TRENCH DETAIL3 4" M I N 6" M I N TYPICAL STREET/OPEN FIELD 6' - 0 " M I N . B U R Y ( T Y P . ) NATIVE MATERIAL COMPACTED AS PER CITY REQUIREMENTS AND ISPWC PIPE BEDDING 4" M I N 6" M I N TYPICAL STREET 6' - 0 " M I N . B U R Y ( T Y P . ) FLOWABLE FILL AS PER CITY OF REXBURG SPECIFICATIONS PIPE BEDDING 12" (MIN.) UNDISTURBED EARTH (TYP.) EXISTING BASE FOUNDATION STABILIZATION TYPE I BEDDING MATERIAL PIPE TRENCH BACK SLOPE PER O.S.H.A. OR SUITABLE SHORING. UPPER & LOWER BACKFILL ZONE MATERIAL & COMPACTION TO MATCH REQUIREMENTS OF STORM DRAIN TRENCH SECTION (DETAIL 1/SD-1). LOWER BACKFILL ZONE. MATERIAL & COMPACTION TO MATCH REQUIREMENTS OF LOWER BACKFILL ZONE OF STORM DRAIN PIPE SECTION. DETAIL (1/SD-1). FINISH GRADE SURFACE REPAIR WIDTH OR LOCAL CUT BACK REQUIREMENTS TYPICAL BOTH SIDES. EXISTING SURFACENEW PAVEMENT SECTION Do+24" SE E N O T E 2 VA R I E S P E R PI P E S I Z E 2' - 6 " VA R I E S 0. 3 5 ' M I N 0. 5 4 ' M I N Do NOT TO SCALE TYPICAL MISC TRENCH DETAIL4 SUBGRADE OR NATURAL GROUND 90°90° 90°90° NOT TO SCALE PIPE BEDDING DETAILS10NOT TO SCALE MULTI-USE ASPHALT PATHWAY SECTION6 NOT TO SCALE FIRE HYDRANT DETAIL5 1.ALL SERVICE LINES TO BE 4" INSIDE DIAMETER UNLESS OTHERWISE NOTED. 2.TYPE "C" SERVICE WILL ONLY BE ALLOWED IF SPECIFICALLY APPROVED BY THE ENGINEER. 3.TYPE "E" ALLOWABLE FOR TRENCHES 15 FT. DEEP OR GREATER WITH PRE-APPROVAL BY THE ENGINEER. 4.USE 6" OF TYPE I BEDDING ALL AROUND EACH SERVICE. FINISH GRADE FINISH GRADE MIN. GRADE 1/4"/FT.(2%) 2-45° BENDS STANDARD TRENCH DETAIL ON PRIVATE PROPERTY STANDARD TRENCH DETAIL ON PUBLIC ROAD 6" M I N 6" M I N 6' - 0 " M I N TYPE 1 AGGREGATE BEDDING (2"x8"x12") CONCRETE BLOCK THRUST BLOCK DO NOT COVER DRAIN HOLES WITH CONCRETE PLACE SAFETY FLANGE OR FLANGE WITH BREAK AWAY BOLTS 2" MIN. 8" MAX ABOVE GRADE HYDRANT SHALL BE FACTORY PAINTED RED STORZ CONNECTION MJ JOINT FLANGED JOINT TEE DI LINE TO CITY MAINLINE THRUST BLOCK VALVE VALVE NUT EXTENSION TO WITHIN 6" OF SURFACE CONCRETE COLLAR FINISHED GRADE VALVE BOX SET TO FINISHED GRADE PIPE BEDDING FOR RIGID PIPE PIPE BEDDING DETAIL FOR FLEXIBLE PIPE SHAPED SUBGRADE GRANULAR FOUNDATION SHAPED SUBGRADE GRANULAR FOUNDATION COMPACT 1" MAX. BACKFILL IN 6" LAYERS TO 95% OR ASTM D-698 COMPACT 1" MAX. BACKFILL IN 6" LAYERS TO 95% OR ASTM D-698 COMPACT APPROVED BEDDING MATERIAL TO 95% OF ASTM D-698 COMPACT APPROVED BEDDING MATERIAL TO 95% OF ASTM D-698 6" M I N 12" MAX3" 6" M I N 12" MAX SHAPED UNDISTURBED SOIL. EXCAVATED FOR BELL HOLES. SHAPED UNDISTURBED SOIL. EXCAVATED FOR BELL HOLES. 6" M I N 12" MAX3" 6" M I N 12" MAX 2" OF PLANT MIX PAVEMENT UNDISTURBED EARTH 9" OF GRANULAR BORROW/PITRUN 3" OF 3/4" GRAVEL ROADBASE 6" 1' 6" AGGREGATE BASE 1'-0" 1'-6" 6" 4"6" 6" 1' 6" AGGREGATE BASE 1'-0" 1'-6" 6" 4" 6" NOT TO SCALE TYPICAL PARKING LOT/ DRIVEWAY SECTION9 NOT TO SCALE LIP DOWN CURB8 NOT TO SCALE LIP UP CURB7 2" THICK ASPHALT PAVING TOP COURSE HAND TAMP EDGES STRAIGHT CONTINUE BASE COURSES 6" BEYOND EDGE OF ASPHALT 4" THICK - 3/4" MINUS GRAVEL, TYPE B BASE COURSE 8' TO 10' Fi l e L o c a t i o n : z: \ p r o j e c t s \ 2 0 2 2 \ 2 2 1 2 5 m a d i s o n s t a t i o n a p a r t m e n t s \ 3 . 0 d e s i g n \ 3 . 1 c a d \ 3 . 1 3 f i n a l \ 2 2 1 2 5 d e t a i l s . d w g Pl o t t e d B y : ru s s e l l Da t e P l o t t e d : We d n e s d a y , M a r c h 2 2 2 0 2 3 a t 0 3 : 3 1 P M 16 D- 2 DE T A I L S AG L E R O C K N G I N E E R I N G SU R V E Y E D B Y : DR A W N B Y : PR O J E C T N O . AP P R O V E D B Y : DE S C R I P T I O N DA T E RE V I S I O N S 1 2 3 4 5 6 AT T E N T I O N Th i s d o c u m e n t o r a n y p a r t t h e r e o f i n d e t a i l o r d e s i g n c o n c e p t is t h e p r o p e r t y o f E a g l e R o c k E n g i n e e r i n g a n d s h a l l n o t b e co p i e d i n a n y f o r m w i t h o u t t h e w r i t t e n a u t h o r i z a t i o n o f E a g l e Ro c k E n g i n e e r i n g . E SH E E T N O . SH E E T N A M E CI V I L P L A N N I N G S U R V E Y I N G ID A H O F A L L S ( 2 0 8 ) 5 4 2 - 2 6 6 5 RE X B U R G ( 2 0 8 ) 3 5 9 - 2 6 6 5 PR E P A R E D F O R : RY A N N E L S O N MA D I S O N S T A T I O N A P A R T M E N T S A. S N A R R R. J O R D A N P. S N A R R 22 1 2 5 P R E L I M I N A R Y N O T A P P R O V E D F O R C O N S T R U C T I O N 16 4 1 0 7" 1.73' 2' - 6 " 0.2' TYP. 0. 2 ' BR O K E N ST O N E 1-1/2"-2" WASHED BROKEN STONE ASPHALT CULTEC 410 FILTER FABRIC TO SEPARATE TOPSOIL FROM WASHED STONE CURB & GUTTER STORM TECH SC-740 CHAMBER INFILTRATOR PRECAST SOLID FLOOR AND LOWER MH SECTION 1. 2 ' 12"Ø PVC TO INFILTRATOR INFILTRATOR 12" TO 24" 12"Ø INLET FROM CATCH BASIN. EXTEND INTO INNER SEPARATOR RING STANDARD MH RING & COVER FLUSH WITH GROUND SURFACE (GRATE NOT RING IN COURTYARD) STANDARD MH CONE SECTION STD 4'Ø MANHOLE SECURE PIPE TO WALL W/ SS STRAP AND HARDWARE. TYP. 12" OPENING WITH FLEXIBLE SEAL,TYP. CROSS SECTION INFILTRATOR DRAIN CROSS SECTION VIEW DRAIN . .. ... ............... ...... .... .. . ... .. .... .. .. . .. .. .... .. ... .. . .. . . ... . .. ..... . .. ........ ......... ....... . ................. .. .. .... . . . . ... .. ... . . ..... . .. .. . .. .. . ..... ..... .... .... . .... . .. ... ... .. .... . ... .... .. . .. . . . ... . ... .. . . ... .... ..... .. . . . .. . .... .. ...... . .. ... .... .... ... . . 10'-0" 30" DIA. PRECAST INLET BOX, SEE TYPE 1 FOR DIMENSIONS AS PER THE CITY OF REXBURG SPECIFICATIONS AND STANDARD DRAWINGS 3/4" CRUSHED GRAVEL 6"3" 1'-0" 6" 6" ASPHALT GRATE1 1 / 4 " #4 REBAR 10'-0" 10 ' - 0 " - D 3' - 3 " 3'-3" ASPHALT CONCRETE 1' .. ..... .. ..... .. .. ..... .. ..... .. .... .... ... ... ..... ..... NOT TO SCALE CATCH BASIN1 12 " M I N . D I A . GASKET FOR PLASTIC PIPE KNOCKOUTS TYPICAL (4) SIDES 18" DIA. TO RECEIVE UP TO 15" DIA. PIPE 3' - 0 " M I N . 3 1 / 2 " 2" 3 1/2"30" INSIDE DIA. BARREL SECTION 39" 20"3'-0"x6"x3/8" STEEL PLATE 6" C1 SIDEWALK TBC C3 #4 REBAR BY MANUFACTURER ADJUSTING BOLTS C1 CL CL 10"GRATE 9" INLET BOX 12 " 18" LIP UP CURB & GUTTER PLASTIC PIPE REBAR SCHEDULE MARK LOCATION SIZE LENGTH QUANTITY C3 CURB AND BOX 4 2'-0"4 NOT TO SCALE STORM DRAIN SECTION4 NOT TO SCALE CROSS SECTIONS OF DRAIN 5NOT TO SCALE THRUST BLOCKING DETAILS3 NOT TO SCALE NOT USED2 ADS STORM TECH SYSTEM NOTES: 1.SC-740 CHAMBERS SHALL CONFORM TO THE REQUIREMENTS OF ASTM F2418 "STANDARD SPECIFICATION FOR POLYPROPYLENE (PP) CORRUGATED WALL STORMWATER COLLECTION CHAMBERS".^J 2.SC-740 CHAMBERS SHALL BE DESIGNED IN ACCORDANCE WITH ASTM F2787 "STANDARD PRACTICE FOR STRUCTURAL DESIGN OF THERMOPLASTIC CORRUGATED WALL STORMWATER COLLECTION CHAMBERS".^J 3."ACCEPTABLE FILL MATERIALS" TABLE ABOVE PROVIDES MATERIAL LOCATIONS, DESCRIPTIONS, GRADATIONS, AND COMPACTION REQUIREMENTS FOR FOUNDATION, EMBEDMENT, AND FILL MATERIALS.^J 4.THE "SITE DESIGN ENGINEER" REFERS TO THE ENGINEER RESPONSIBLE FOR THE DESIGN AND LAYOUT OF THE STORMTECH CHAMBERS FOR THIS PROJECT.^J 5.THE SITE DESIGN ENGINEER IS RESPONSIBLE FOR ASSESSING THE BEARING RESISTANCE (ALLOWABLE BEARING CAPACITY) OF THE SUBGRADE SOILS AND THE DEPTH OF FOUNDATION STONE WITH CONSIDERATION FOR THE RANGE OF EXPECTED SOIL MOISTURE CONDITIONS.^J 6.PERIMETER STONE MUST BE EXTENDED HORIZONTALLY TO THE EXCAVATION WALL FOR BOTH VERTICAL AND SLOPED EXCAVATION WALLS. 7.ONCE LAYER 'C' IS PLACED, ANY SOIL/MATERIAL CAN BE PLACED IN LAYER 'D' UP TO THE FINISHED GRADE. MOST PAVEMENT SUBBASE SOILS CAN BE USED TO REPLACE THE MATERIAL REQUIREMENTS OF LAYER 'C' OR 'D' AT THE SITE DESIGN ENGINEER'S DISCRETION. 30" (762 mm) 18" (450 mm) MIN* 8' (2.4 m) MAX SUBGRADE SOILS (SEE NOTE 5) PAVEMENT LAYER (DESIGNED BY SITE DESIGN ENGINEER) SC-740 END CAP 6" (150 mm) MIN DEPTH OF STONE TO BE DETERMINED BY SITE DESIGN ENGINEER 6" (150 mm) MIN D C B A PERIMETER STONE (SEE NOTE 6) EXCAVATION WALL (CAN BE SLOPED OR VERTICAL) *TO BOTTOM OF FLEXIBLE PAVEMENT. FOR UNPAVED INSTALLATIONS WHERE RUTTING FROM VEHICLES MAY OCCUR, INCREASE COVER TO 30" (750 mm). 12" (300 mm) MIN ADS GEOSYNTHETICS 601T NON-WOVEN GEOTEXTILE ALL AROUND CLEAN, CRUSHED, ANGULAR STONE IN A & B LAYERS 12" (300 mm) MIN51" (1295 mm)6" (150 mm) MIN SUMP DEPTH TBD BY SITE DESIGN ENGINEER (24" [600 mm] MIN RECOMMENDED)24" (600 mm) HDPE ACCESS PIPE REQUIRED USE FACTORY PRE-FABRICATED END CAP PART #: MC3500IEPP24BC TWO LAYERS OF ADS GEOSYNTHETICS 315WTK WOVEN GEOTEXTILE BETWEEN FOUNDATION STONE AND CHAMBERS 8.25' (2.51 m) MIN WIDE CONTINUOUS FABRIC WITHOUT SEAMS MANHOLE COVER PIPE CONNECTION TO END CAP WITH ADS GEOSYNTHETICS 601T NON-WOVEN GEOTEXTILE SC-740 CHAMBER SC-740 END CAP SC-740 ISOLATOR ROW DETAIL NTS OPTIONAL INSPECTION PORT STORMTECH HIGHLY RECOMMENDS FLEXSTORM PURE INSERTS IN ANY UPSTREAM STRUCTURES WITH OPEN GRATES ADS STORM INFILTRATION NOTES 1.THE ADS STORM INFILTRATION SYSTEM SHOWN IS SIZED USING ADS STORM TECH SC-740 CHAMBER SYSTEM. THE CHAMBER AREAS ARE SET FOR DESIGN FOR EACH AREA; HOWEVER THE LENGTHS AND WIDTHS MAY VARY TO MEET SEPARATION FROM OTHER UTILITIES OR CONSTRUCTION OBSTACLES. 2.CONTRACTOR TO SUPPLY AND SUBMIT FINAL ADS STORM TECH DRAWINGS AND SPECIFICATIONS (OR EQUAL SYSTEM) TO ENGINEER FOR APPROVAL PRIOR TO INSTALLATION. 3. CONTRACTOR TO INSTALL THE ADS STORM TECH SC-740 SYSTEM (OR EQUAL) WITH NYLOPLAST INLET AND OUTLET (OR PRECAST CONCRETE) PER MANUFACTURERS DRAWINGS AND SPECIFICATIONS. NOT TO SCALE STORM TECH SC-740 ADS CHANBER SYSTEM6 B B/3 MI N . A TEE BEND/ELBOW REDUCER 22а BEND REDUCERS & 1'-9" 2'-5" 3'-2" 4'-0" 4'-8" 6'-6" DIMENSION FOR THRUST BLOCKING 14" 6" 10" 12" 8" FITTING SIZES 4" 1'-11" 2'-6" 3'-3" 3'-10" 3'-10"5'-5" 2'-0" 3'-4" 4'-0" 2'-8" TEES & PLUGS 1'-2" A 1'-7" B 1'-8" 1'-10" 45° BEND & WYES 2'-5" 3'-0" 4'-9" 3'-8" 2'-2" 3'-10" 4'-11" 4'-8" 3'-0" B 1'-6" 90° BEND A A 1'-7" 2'-1" 2'-9" 3'-5" 3'-3" 3'-5" 1'-9" 1'-9" 2'-2" 2'-7" 0'-10" B A 1'-7" 2'-5" 0'-10" 1'-11" 2'-3" 1'-6" 0'-6" B NOTES: 1.WRAP ALL FITTINGS W/ 8 MIL POLYETHYLENE ENCASEMENT TO PREVENT CONCRETE FROM ADHERING TO THE FITTINGS. 2.THRUST BLOCKING CONCRETE TO BE MINIMUM 3000 PSI MIX. 3.ALL THRUST BLOCKS ARE TO BE FORMED ON THE VERTICAL PLANES. 4.PLACE THRUST BLOCKS ON ALL WATERLINE BENDS AND TEES.