Description : Starbucks - Interior
Address : 1050 Golden Beauty Dr
Record Type : Commercial - Remodel
Document Filename : Plans_Starbucks_1060 Golden Beauty Dr.pdf
Comment Author Contact Information:
Corrections in the following table need to be applied before a permit can be issued
Review Report
Approved
# 23-00793
Page Reference Annotation
Type
Author : Department Status Page Review Comments Applicant Response Comments
G001 Stamp Cody Jones : Building Open 1 Approved - Building Inspector
G002 Free Text Cody Jones : Building Open 2 Doors to swing in direction of Egress.
G005 Free Text Cody Jones : Building Open 5 Landings at doors and cross slope of sidewalks not to exceed
2%
A101 Note Cody Jones : Building Open 14 Concealed spaces are fireblocked/draftstopped per Section
718
A101 Note Cody Jones : Building Open 14 Insulation materials meet the requirements of Section 720
A602 Note Cody Jones : Building Open 19 Glass and Glazing meets the requirements of IBC Chapter 24
I104 Note Cody Jones : Building Open 31 Exit Lighting and Exit Signs comply with IBC 1008 & 1013
G001 Stamp Alex Owens : Electrical Open 1 Approved - Electrical Inspector
I601 Stamp Alex Owens : Electrical Open 52 Approved - Electrical Inspector
I602 Stamp Alex Owens : Electrical Open 53 Approved - Electrical Inspector
Commercial - Remodel
Approval of plans does not constitute approval of variance from code
Page Reference Annotation
Type
Author : Department Status Page Review Comments Applicant Response Comments
E001 Stamp Alex Owens : Electrical Open 54 Approved - Electrical Inspector
E100 Stamp Alex Owens : Electrical Open 55 Approved - Electrical Inspector
E101 Free Text Alex Owens : Electrical Open 56 All electrical work must comply with 2017 NEC. All kitchen
receptacles must have GFCI protection. All electrical work
connecting fryers of any kind must have shunt trip protection.
E101 Stamp Alex Owens : Electrical Open 56 Approved - Electrical Inspector
E102 Stamp Alex Owens : Electrical Open 57 Approved - Electrical Inspector
E103 Free Text Alex Owens : Electrical Open 58 All emergency and exit lighting must comply with 1008 and
1013 in the 2018 IBC.
E103 Stamp Alex Owens : Electrical Open 58 Approved - Electrical Inspector
E-104 Stamp Alex Owens : Electrical Open 59 Approved - Electrical Inspector
E501 Stamp Alex Owens : Electrical Open 60 Approved - Electrical Inspector
E502 Stamp Alex Owens : Electrical Open 61 Approved - Electrical Inspector
E503 Stamp Alex Owens : Electrical Open 62 Approved - Electrical Inspector
E601 Stamp Alex Owens : Electrical Open 63 Approved - Electrical Inspector
G001 Stamp Don Allen : Mechanical Open 1 Corrections Required
G001 Stamp Don Allen : Mechanical Open 1 Approved - Mechanical Inspector
G001 Stamp Don Allen : Mechanical Open 1 Approved - Plumbing Inspector
G001 Stamp Kyle Baldwin : P&Z Open 1 Approved - Planning and Zoning
Approval of plans does not constitute approval of variance from code