HomeMy WebLinkAboutRESPONSE LETTER - 23-00793 - Starbucks - Interior
November 30, 2023
Cody Jones
Community Development Department
35 North 1st East
Rexburg, ID 83440
(208) 372-2166
Re: University & Yellowstone
1060 Golden Beauty Drive
Rexburg, ID 83440
NG Project Number: 96972-001
Review #: 23-00793
Dear Cody Jones,
We received the following building department comments dated 11/13/2023 for the above project. We
respond as follows:
1. Comment 1:
RESPONSE: The exterior door swings have been reversed- refer to sheet G002.
2. Comment 2:
RESPONSE: Sheet A001 has been revised to include note “L” which states “Landings at
doors and cross slopes of sidewalks not to exceed 2%.”
3. Comment 3:
RESPONSE: Sheet A101 has been revised to include note “N” which states “Provide fire
blocking per IBC section 718 in all concealed wall spaces (double stud, furred, or cated
walls, ETC.). Fire blocking shall be provided vertically at each floor/ceiling assemblies and
horizontally at 10’-0” O.C. Max.”
4. Comment 4:
RESPONSE: Sheet A101 has been revised to include note “O” which states “Insulation to
meet code requirements per section 720, 2018 IBC.”
5. Comment 5:
RESPONSE: The glass and glazing will be existing and installed by the landlord. The door
schedule on sheet A602 has been revised to exclude exterior doors with glazing, as these will
be provided by the LL under a separate permit for the building shell.
6. Comment 6:
RESPONSE: Sheet I104 has been revised to include emergency lighting above the restroom
doors. Note “K” has been added to sheet I104 to indicate that emergency exit lighting and
signs are compliant with 2018 IBC sections 1008 and 1013.
For items on E101, E103, and the Plumbing comment, please refer to the response letter from
Schnackel Engineers.
We have responded to all questions to the best of our ability at this time. Please feel free to call me if you
have any questions.
Sincerely,
Richard Avery
Director of Studio One25
Schnackel Project No.: 230929
General Review
Item: E101
All electrical work must comply with 2017 NEC. All kitchen receptacles must have GFCI
protection. All electrical work connecting fryers of any kind must have shunt trip
protection.
Item: E103
All emergency and exit lighting must comply with 1008 and 1013 in the 2018 IBC.
Item: 3
Drainage and Venting needs to be sized to the 2017 Idaho State Plumbing Code.
If you have any questions, please let me know.
11/20/2023