HomeMy WebLinkAboutAPPROVED PLANS - 23-00600 - Cafe Sabor - RemodelAuthor Name Author Email Author Phone No.: Don Allen Don.Allen@rexburg.org 208-372-2174 Alex Owens Alex.Owens@rexburg.org 208-372-2172 Description : Cafe Sabor - Remodel Address : 160 W 2nd S Record Type : Commercial - Remodel Document Filename : 20230601 ESA Dwg-Cafe Sabor-Final Review.pdf Comment Author Contact Information: Corrections in the following table need to be applied before a permit can be issued Review Report Approved # 23-00600 Page Reference Annotation Type Author : Department Status Page Review Comments Applicant Response Comments M1.1 Stamp Alex Owens : Electrical Open 1 Corrections Required M1.1 Free Text Alex Owens : Electrical Open 1 No electrical plans provided. Please provide electrical plans or have electrician call 208-372-2172 to explain electrical work to be completed. All electrical work must comply with 2017 NEC. M1.1 Stamp Don Allen : Mechanical Open 1 Approved - Mechanical Inspector M1.1 Stamp Don Allen : Mechanical Open 1 Approved - Plumbing Inspector Commercial - Remodel Approval of plans does not constitute approval of variance from code Powered by TCPDF (www.tcpdf.org) MECHANICAL FLOOR PLAN NorthSCALE: 1/4" = 1'-0" M1.1 ME C H A N I C A L F L O O R P L A N S 2OF: SHEET: JOB NO. 21050 M JENSEN DATE: APRIL '23 D HANSEN DRWN. BY:CKD. BY: HE M M I N G V I L L A G E R E X B U R G , I D A H O CA F E S A B O R RE M O D E L O F : PR O J E C T : SH E E T T I T L E : S: \ 2 0 0 0 - 2 0 \ 2 3 \ 2 3 0 5 0 C a f e S a b o r \ C A D \ 2 3 0 5 0 - M 1 . 1 . d w g J u n 0 1 , 2 0 2 3 - 1 0 : 0 9 a m En g i n e e r e d S y s t e m s A s s o c i a t e s Me c h a n i c a l E n g i n e e r s Dw a y n e S u d w e e k s P . E . , D a v e H a n s e n P . E . , T a n n e r D a v i s P . E . 13 5 5 E a s t C e n t e r - P o c a t e l l o , I d a h o 8 3 2 0 1 Ph o n e : ( 2 0 8 ) 2 3 3 - 0 5 0 1 e m a i l : e s a @ e n g s y s t e m s . c o m CON S T R U C T I O N DRA W I N G PRE L I M I N A R Y NOT F O R MECHANICAL DEMO PLAN NorthSCALE: 1/8" = 1'-0" PLAN NOTES: 1 EXISTING ELECTRIC HEATERS TO REMAIN. PROTECT DURING CONSTRUCTION. EXISTING DUCTWORK TO REMAIN UNLESS NOTED OTHERWISE. FIELD VERIFY EXACT LOCATIONS AND SIZES. PROTECT DURING CONSTRUCTION. EXISTING SUPPLY DIFFUSER AND ASSOCIATED BRANCH DUCT TO REMAIN. PROTECT DURING CONSTRUCTION. RE-BALANCE EXISTING DIFFUSER AFTER NEW FURNACE HAS BEEN INSTALLED TO CFM AS INDICATED. EXISTING CEILING DIFFUSER OR RETURN AIR GRILLE TO BE RELOCATED. DISCONNECT FROM EXISTING BRANCH DUCT. REMOVE EXISTING BRANCH DUCT AS SHOWN. PROVIDE NEW ROUND FLEXIBLE DUCT TO CONNECT RELOCATED GRILLE TO EXISTING DUCTWORK. DISCONNECT AND REMOVE EXISTING GRILLES AND DUCTWORK AS SHOWN. REFER TO MECHANICAL FLOOR PLAN FOR NEW DUCTWORK TO BE CONNECTED TO EXISTING. CAP ALL DUCT TAKE-OFFS NOT BEING REUSED. EXISTING RETURN AIR GRILLE IN WALL ABOVE TOILET ROOMS TO REMAIN. DISCONNECT EXISTING RETURN DUCT TO MECHANICAL EQUIPMENT. DISCONNECT AND REMOVE EXISTING VFR EQUIPMENT FROM ABOVE CEILING. CAP REFRIGERANT PIPING AND ABANDON IN PLACE. REMOVE EXISTING HEAT PUMP UNIT AND DELIVER TO BUILDING OWNER. RELOCATE EXISTING WALL MOUNTED THERMOSTAT TO NEW DINING ROOM WALL AS SHOWN. MODIFY CONTROL WIRING AS REQUIRED TO CONNECT TO NEW FURNACE #1. EXISTING WALL MOUNTED THERMOSTAT TO REMAIN. PROTECT DURING CONSTRUCTION. MODIFY EXISTING CONTROL WIRING AS REQUIRED TO CONNECT TO NEW FURNACE #2. INSTALL NEW HORIZONTAL FURNACE WITH MATCHING DX COOLING COIL ABOVE TOILET ROOMS. PROVIDE DRAIN PAN BELOW UNIT. COORDINATE UNIT WITH BUILDING STRUCTURE AND EXISTING DUCTWORK. KEEP UNIT AS HIGH AS POSSIBLE. MAINTAIN GREATEST DISTANCE BETWEEN UNIT AS POSSIBLE. PROVIDE NEW 12" WIDE BY 20" DEEP RETURN AIR PLENUM. CONNECT TO EXISTING WALL MOUNTED RETURN AIR GRILLE AND TO (2) NEW FURNACE SYSTEMS. CONNECT NEW DUCT AS CALLED OUT TO EXISTING DUCT. CONTRACTOR TO FIELD VERIFY EXACT LOCATIONS AND SIZES OF EXISTING DUCTWORK. PROVIDE DUCT TRANSITIONS AS REQUIRED FOR CONNECTION. KITCHEN HOOD SUPPLIED AND INSTALLED BY KITCHEN EQUIPMENT CONTRACTOR. COORDINATE ALL DUCTWORK ABOVE HOOD WITH BUILDING STRUCTURE AND WITH NEW HOOD. ROUGH-IN AND CONNECT 24" x 10" EXHAUST DUCT TO NEW KITCHEN HOOD. REFER TO KITCHEN EQUIPMENT DRAWINGS FOR HOOD LOCATION AND DUCT CONNECTIONS. COORDINATE NEW DUCTWORK WITH BUILDING STRUCTURE AND NEW HOOD. EXHAUST DUCT TO HAVE FIRE PROTECTION HEADS AND PIPING FROM HOOD ANSUL SYSTEM AS REQUIRED BY CODE. PROVIDE 12x10 FIRE RATED DUCT ACCESS DOORS IN EXHAUST DUCT. LOCATE ACCESS PANEL IN ACCESSIBLE LOCATION. ROUGH-IN AND CONNECT 28x12 MAKE-UP DUCT TO KITCHEN HOOD. PROVIDE BALANCING DAMPER IN DUCT AND BALANCE EACH DUCT TO 673 CFM. REFER TO KITCHEN EQUIPMENT DRAWINGS FOR HOOD LOCATION AND DUCT CONNECTIONS. (TYPICAL OF 6 CONNECTIONS.) COORDINATE LOCATION OF MAKE-UP AIR DUCT WITH OTHER DUCTWORK, KITCHEN HOOD, PIPING, AND BUILDING STRUCTURE. RISE 18x18 MAKE-UP AIR DUCT UP IN DUCT CHASE ON LEVEL ABOVE. COORDINATE DUCT WITH FLOOR JOISTS AND BEAMS. SEE PARTIAL UPPER LEVEL PLAN FOR CONTINUATION. TRANSITION KITCHEN HOOD EXHAUST DUCT TO 16"Ø AND RISE UP IN NEW DUCT CHASE ON LEVEL ABOVE. COORDINATE DUCT WITH FLOOR JOISTS AND BEAMS. SEE PARTIAL UPPER LEVEL PLAN FOR CONTINUATION. RISE 18x18 UP IN DUCT CHASE. CONNECT TO MAKE-UP AIR UNIT ON ROOF. REFER TO KITCHEN EQUIPMENT PLANS FOR LOCATION AND DUCT CONNECTION TO MAKE-UP AIR UNIT. RISE 16"Ø EXHAUST DUCT TO IN DUCT CHASE. CONNECT TO EXHAUST FAN ON ROOF. REFER TO KITCHEN EQUIPMENT PLANS FOR LOCATION AND DUCT CONNECTION TO EXHAUST FAN. EXTEND EXISTING 12"Ø OUTSIDE AIR DUCT AS REQUIRED TO CONNECT TO NEW RETURN AIR PLENUM. PROVIDE MANUAL BALANCING DAMPER AND BALANCE TO 400 CFM MAXIMUM. INSTALL NEW CONDENSING UNITS ON FLAT SECTION OF ROOF. DROP REFRIGERANT LINES DOWN THRU ROOF AND ROM TO CORRESPONDING FURNACE SYSTEMS. REFER TO SCHEDULE FOR REFRIGERANT LINE SIZES. COORDINATE UNIT LOCATION ON ROOF WITH KITCHEN HOOD EQUIPMENT TO MAINTAIN MAXIMUM CLEARANCES AROUND ALL EQUIPMENT. RUN (2) 3"Ø FURNACE VENTS FROM EACH FURNACE THRU EXTERIOR WALL. TERMINATE WITH FLAT CONCENTRIC TYPE FITTINGS. REFER TO DETAIL E/M2.1 FOR TYPICAL INSTALLATION. DINING AREA 106 RESTROOM 105 RESTROOM 104 SERVING 107 KITCHEN 108 FOYER 100 ENTRY 103 ELEVATOR 101 STAIRWAY 102 DINING AREA 106 RESTROOM 105 RESTROOM 104 SERVING 107 KITCHEN 108 FOYER 101 ENTRY 103 ELEVATOR 101 STAIRWAY 102 PREPARATION 111 DISHWASH 110 EXIST. FREEZER (E ) 1 6 x 1 2 R A (E) 14x14 OA (E) 14x14 EA (E) 12"Ø OA (E) 10"Ø EA (E) 10"Ø SA(E ) 1 0 " Ø S A (E ) 1 0 " Ø S A (E) 8 " Ø S A (E) 1 0 " Ø S A 7 5 4 4 4 3 3 5 2 HD HD HD HD HD HD HD (E ) 8 " Ø O A HD HD (E ) 1 4 " Ø S A (E ) 1 0 " Ø S A (E) 10"Ø SA (E) 10"Ø SA (E ) 8 " Ø S A T T (E) 10"Ø SA 33333 3 3 3 3 3 3 3 3 7 6 3 (E ) 8 " Ø S A 5 8 3 (E) 12"Ø EA FIRE 103 FIRE 103 (E) 14x14 OA (E) 14x14 EA (E) 12"Ø OA (E) 10"Ø EA 3 3 3 3 3 3 HD HD HD (E ) 1 4 " Ø S A (E ) 1 0 " Ø S A (E) 10"Ø SA (E) 10"Ø SA (E ) 8 " Ø S A T T (E) 10"Ø SA 3 33 3 3 3 6 3 1 (E ) 8 " Ø S A 3 9 3 (E) 12"Ø EA 1 1 1 3 2 2 2 2 2 2 HD 12 RG-1 400 200 CFM 200 CFM 200 CFM 200 CFM 200 CFM 200 CFM 200 CFM 200 CFM 180 CFM 180 CFM 180 CFM 200 CFM 1 F10 2 F10 12x20 RA EXIST 200 3 EXIST 200 200 CFM PARTIAL UPPER LEVEL PLAN NorthSCALE: 1/8" = 1'-0" EXISTING W21x44 BEAMS BELOW FLOOR. FIELD VERIFY EXACT LOCATIONS. HD HD HD HD HD 2 22 2 22 2 5 5 2 2 2 2 5 5 9 5 5 2 11 12 2 2 18"Ø SA CD-1 2004 CD-1 2004 15 15 15 14"Ø SA 12 CAP 2 12 8"Ø SA 8 1 FTO 14"Ø RA CAP CAP 12 2 FTO 18 17 18 14 20 x 1 2 E A 20 x 1 2 E A 13 16 18 " x 1 8 M A 18 " x 1 8 " R A 12 " x 1 8 " R A 14 13 13 13 14 16 2 2 2 12 2 2 12 18"Ø SA 14"Ø SA 14"Ø SA 12 8"Ø SA 2 3 4 5 6 7 8 9 10 11 12 22 x 1 2 E A 14 13 14 15 16 17 18 19 20 19 20 20 MAKE-UP AIR UNIT ON ROOF BY KITCHEN EQUIPMENT CONTRACTOR. EXHAUST FAN ON ROOF BY KITCHEN EQUIPMENT CONTRACTOR. EXHAUST FAN ON ROOF BY KITCHEN EQUIPMENT CONTRACTOR. 21 21 HD 1 CU 2 CU 22 22 22 100 CFM 100 CFM 23 23 AFÑWBWUhI>USBÑGBSEJÑGIFM>VWV•Ñ CBWSJWÑGIFM>VWÑWBWUhI>USBÑGBSEJÑFIÑ ZSMWÑWBWUhI>U>SEÑUSBBÑ ½Ž)#ÃÁ½#½¤Á½ÑhFÑWPGBS>EÑWBWUhI>USB OFI@ÑhFÑTWÑUFCGBWhWV•Ñ2BBÑ M2.1 ME C H A N I C A L S C H E D U L E S A N D D E T A I L S 2OF: SHEET: JOB NO. 21050 M JENSEN DATE: APRIL '23 D HANSEN DRWN. BY:CKD. BY: HE M M I N G V I L L A G E R E X B U R G , I D A H O CA F E S A B O R RE M O D E L O F : PR O J E C T : SH E E T T I T L E : S: \ 2 0 0 0 - 2 0 \ 2 3 \ 2 3 0 5 0 C a f e S a b o r \ C A D \ 2 3 0 5 0 - M 2 . 1 . d w g J u n 0 1 , 2 0 2 3 - 1 0 : 0 8 a m En g i n e e r e d S y s t e m s A s s o c i a t e s Me c h a n i c a l E n g i n e e r s Dw a y n e S u d w e e k s P . E . , D a v e H a n s e n P . E . , T a n n e r D a v i s P . E . 13 5 5 E a s t C e n t e r - P o c a t e l l o , I d a h o 8 3 2 0 1 Ph o n e : ( 2 0 8 ) 2 3 3 - 0 5 0 1 e m a i l : e s a @ e n g s y s t e m s . c o m CON S T R U C T I O N DRA W I N G PRE L I M I N A R Y NOT F O R SUCTION REFRIGERANT PIPING LIQUID LENNOX MODEL 13ACX-060 WITH LOW AMBIENT 'HARD-START' KIT. REMARKSMCAEATBTUSYM.CHAR. 34.695°FCU 1 56,000 208/60/1 CONDENSING UNIT SCHEDULE 250# WEIGHT O.A. CFM HORIZONTAL1 F SYM.TYPE 1940 200 DESIGN CFM REMARKS FURNACE SCHEDULE CHAR.H.P. 1.5" SPE 120/60/1 A.G.A. 110,000 INPUT 106,000 OUTPUT VENTLAT 65°F 107°F EAT 1/2" SUP (2) 3"Ø NAT. GAS TYPE LENNOX MODEL ML195UH-110XP60C WITH MATCHING HORIZONTAL DX COOLING COIL. THROW CD-1 SYM. 12 x 12 SIZE GRILLE AND REGISTER SCHEDULE BRANCHCONSTR. 200-400 CFM STEEL FINISH WHITE 10" Ø DUCT NO F.D. NO O.B.REMARKS PRICE MODEL SMD WITH BEVELED FRAME CEILING JOIST ROOF OR PIPING TO SUPPORTS SECURE REFRIGERANT CLAMP ASSEMBLY SUCTION LINE THRU RUN INSULATION OF CLAMP OR EQUAL WITH "UNISTRUT" SUCTION LINES TYPICAL REFRIGERANT PIPE IN MECH. ROOM HANGER RODS OR EQUAL (TYPICAL) "UNISTRUT" CHANNEL 1-5/8" P-1001 INSULATION ON ALL PIPING SUPPORTS OF JOISTS. NO PIPING SUPPORTS ARE TO BE PRIOR TO FIREPROOFING FIREPROOFING HAS BEEN DONE. ARE TO BE INSTALLED ATTACHED AFTER NOTE: 1" CHANNEL (UNISTRUT OR FEE & MASON) WELD TO JOISTS EXISTING EXPANSION VALVE SEAL WATERTIGHT ROOF PENETRATION SIGHT GLASS FILTER DRYER PIPE SUPPORT AT RISE EXISTING 3/4" CD EXISTING FURNACE EXISTING DX COIL ROUTE PIPING UP THRU EXISTING ROOF MOUNT UNIT ON PYRAMID SUPPORTS RELOCATE EXISTING CONDENSING UNIT TO ROOF CAULK NON-HARDENING COLLAR STORM FLASHING 4" MIN. 2' - 0 " AND SEAL WATERTIGHT FLASH ONTO ROOF REFRIGERANT PIPING TO DX COOLING COIL REFRIGERANT PIPING TO CONDENSING UNIT GALVANIZED METAL VENT THRU ROOF WITH GOOSENECK. REINFORCING MENDED GAGE 24 26 DRIVE RECOM- SLIP 19 - 30 13 - 18 UP THRU 12 LONGEST INCHES SIDE, DIMENSION NONE REQUIRED26 NONE REQUIRED 1"x1"x1/8" @ 60 IN24 24 (ALL FOUR SIDES) OF GAGE METAL SHEET BETWEEN INTERMEDIATE REINFORCING JOINTS &/OR TRANSVERSE ANGLE SIZE SPACING LONGITUDINAL AND MAXIMUM 2"2" 26 MAX. 12" OC 24 24- S SLIP RECOM- MENDED GAGE HEMMED 1" TRANSVERSE REINFORCING (1) MINIMUM AT JOINTS (1) TRANSVERSE REINFORCING SIZE IS DETERMINED BY DIMENSION OF SIDE TO WHICH ANGLE IS APPLIED. GRIP NAILS SHALL BE INSTALLED BY GRIPNAIL AIR HAMMER OR BY AUTOMATIC FASTENER EQUIP. METAL FASTENERS - OMARK INSULPINS, DURO DYNE FASTENERS OR GRIPNAILS. STRAPS TO BE TIGHT AGAINST DUCTWORK HANG DUCTS UP TO 30" WIDTH WITH 1" x 18 GAGE STRAPS AT 10'-0" MAXIMUM SPACING. SELF-TAPPING CADMIUM PLATED HEX HEAD SHEET METAL SCREW NO POP RIVETS ALLOWED HANGER STRAPS SHEET METAL DUCT NOT MORE THAN 2" FROM EDGE OF LINER ALL ENDS OF LINER TO BE COATED WITH ADHESIVE. SEE SPECIFICATIONS. 1" THICK DUCT LINER TOP AND BOTTOM SECTION OF LINER SHALL OVERLAP THE SIDES ENDS OF LINER SHALL BE BUTTED FIRMLY TOGETHER LINER TO BE ADHERED TO DUCT W/100% ADHESIVE SEE SPECIFICATIONS. REFRIGERANT PIPE SUPPORT DETAIL NO SCALEBDUCT CONSTRUCTION AND HANGER DETAILS NO SCALEA NO SCALEC CONENCTRIC VENT TERMINATION THRU WALL DETAIL NO SCALEE REFERGERANT PIPING THRU ROOF DETAIL REFRIGERANT PIPING DIAGRAM NO SCALED HORIZONTAL2 F 1600 200 1/2.5"120/60/1 90,000 85,000 65°F 106°F 1/2"(2) 3"Ø NAT.LENNOX MODEL ML195UH-090XP48C WITH MATCHING HORIZONTAL DX COOLING COIL. MCOP 60 3/8"1-1/8" LENNOX MODEL 13ACX-048 WITH LOW AMBIENT 'HARD-START' KIT.28.995°FCU 2 48,000 208/60/1 230#50 3/8"78" SUPPLY AIR ELECTRONIC THERMOSTAT EQUIPMENT SYMBOL PLAN NOTE ABOVE FINISHED FLOOR REFRIGERANT OUTSIDE AIR RETURN AIR F 1 T AFF 1 SA REFR OA RA INSULATED FLEXIBLE DUCT ROUND SPIRAL DUCTWORK ROUND CEILING DIFFUSER ROUND BRANCH DUCT WITH HAND DAMPER RECTANGULAR SUPPLY AND RETURN AIR DUCT TAKE-OFF TURNING VANES DUCT TRANSITION HAND DAMPER HD MECHANICAL LEGEND DESCRIPTIONDESCRIPTIONSYMBOLSYMBOL SYMBOL DESCRIPTION HORIZONTAL FURNACE (RETURN AIR) SIDEWALL GRILLE CONDENSING UNIT RETURN AIR GRILLE EXHAUST AIR GRILLE RG-1 18 x 18 300-800 STEEL WHITE 14" Ø NO NO PRICE MODEL 535 WITH NARROW FRAME HAND DAMPERHD EXHAUST AIREA SQUARE CEILING DIFFUSER SINGLE LINE DUCTWORK = EXISTING DOUBLE LINE DUCTWORK = NEW DUCT VENT PLATECOMBUSTION AIR VENT FURNACE FLUE 12" MINIMUM TO OVERHANG MAINTAIN 12" MINIMUM CLEARANCE ABOVE HIGHEST ANTICIPATED SNOW LEVEL OR GRADE WHICHEVER IS GREATER SECURE TO WALL WITH 2" SCREWS VENT PLATE CONNECT FURNACE VENTS TO WALL SLEEVES. UTILIZE REDUCING COUPLER IF REQ'D. SEAL ALL WALL CAVITIES WATER TIGHT BUILDING WALL MAKE-UP AIRMA MAIN LEVEL PLUMBING FLOOR PLAN NorthSCALE: 1/4" = 1'-0" P1.1 PL U M B I N G F L O O R P L A N S 2OF: SHEET: JOB NO. 21050 M JENSEN DATE: APRIL '23 D HANSEN DRWN. BY:CKD. BY: HE M M I N G V I L L A G E R E X B U R G , I D A H O CA F E S A B O R RE M O D E L O F : PR O J E C T : SH E E T T I T L E : S: \ 2 0 0 0 - 2 0 \ 2 3 \ 2 3 0 5 0 C a f e S a b o r \ C A D \ 2 3 0 5 0 - P 1 . 1 . d w g J u n 0 1 , 2 0 2 3 - 1 0 : 0 8 a m En g i n e e r e d S y s t e m s A s s o c i a t e s Me c h a n i c a l E n g i n e e r s Dw a y n e S u d w e e k s P . E . , D a v e H a n s e n P . E . , T a n n e r D a v i s P . E . 13 5 5 E a s t C e n t e r - P o c a t e l l o , I d a h o 8 3 2 0 1 Ph o n e : ( 2 0 8 ) 2 3 3 - 0 5 0 1 e m a i l : e s a @ e n g s y s t e m s . c o m CON S T R U C T I O N DRA W I N G PRE L I M I N A R Y NOT F O R MAIN LEVEL PLUMBING DEMO PLAN NorthSCALE: 1/8" = 1'-0" PLAN NOTES: 1 EXISTING PLUMBING FIXTURE TO REMAIN. PROTECT DURING CONSTRUCTION. MAINTAIN EXISTING WASTE, WASTE AND VENT LINE CONNECTIONS TO FIXTURE. EXISTING FLOOR DRAIN OR FLOOR SINK TO REMAIN. COVER DURING CONSTRUCTION TO KEEP CLEAN. CLEAN OUT P-TRAP AFTER WORK HAS BEEN COMPLETED. EXISTING BEVERAGE DISPENSER TO BE REMOVED. CAP EXISTING COLD WATER LINE INSIDE EXISTING WALL. PATCH EXISTING WALL TO MATCH ADJACENT SURFACES. DISCONNECT AND REMOVE EXISTING PLUMBING FIXTURE. REMOVE EXISTING WASTE, WATER AND VENT PIPING FROM WALL BEING DEMOLISHED. CAP WASTE AND WATER PIPING IN BASEMENT. CAP VENT PIPING ABOVE CEILING. CONTRACTOR TO FIELD VERIFY EXACT SIZES AND LOCATIONS OF EXISTING PIPING. FURNACE BY MECHANICAL CONTRACTOR. CONNECT 3/4" CONDENSATE DRAIN LINE TO FURNACE AND COOLING COIL. CONNECT 3/4" DRAIN LINE TO DRAIN PAN BELOW EQUIPMENT. RUN (2) SEPARATE HORIZONTAL 3/4" DRAIN LINES TO WALL. DROP SINGLE 1" DRAIN LINE DOWN IN WALL. EXTEND OUT BELOW FIXTURE OR COUNTERTOP AND CONNECT TO UPSTREAM SIDE OF P-TRAP WITH DISHWASHER TYPE FITTING. SEE DETAIL F/P2.1. EXISTING ELECTRIC WATER HEATER TO BE REPLACED WITH (2) NEW GAS FIRED WATER HEATERS AS SCHEDULED. EXISTING PIPING IN WALL TO REMAIN. DISCONNECT FROM EXISTING EQUIPMENT AND RECONNECT TO NEW HEATERS WITH NEW FLEXIBLE PIPES. MODIFY PIPING AS REQUIRED FOR NEW CONNECTIONS. PROVIDE NEW RECIRC. PUMP, THERMAL EXPANSION TANK, AND HEAT TRAP NIPPLES. REFER TO DETAIL D/P2.1 FOR TYPICAL PIPING CONNECTIONS. CONNECT 3/4" GAS LINE TO EACH WATER HEATER WITH PRESSURE REGULATOR, SHUT-OFF VALVE AND FLEXIBLE HOSE. RISE VENTS FROM WATER HEATER UP THRU CHASE ON UPPER LEVEL AND EXTEND THRU ROOF WITH WEATHER CAP AS RECOMMENDED BY MANUFACTURER. INSTALL NEW WATER SOFTENER AND BRINE TANK AS SCHEDULED. COORDINATE NEW EQUIPMENT WITH EXISTING FLOOR SINK. CONNECT NEW SOFTENER TO 1" COLD WATER LINE. RUN NEW 1" SOFT WATER LINE TO NEW WATER HEATER. REFER TO DETAIL H/P2.1 FOR TYPICAL PIPING CONNECTIONS TO WATER SOFTENER SYSTEM. INSTALL NEW FLOOR SINK AS SCHEDULED. MOUNT FLUSH WITH FLOOR. CUT EXISTING CONCRETE FLOOR AS REQUIRED TO INSTALL FIXTURE AND PIPING. PATCH AROUND NEW FIXTURE TO MATCH ADJACENT SURFACES. CONNECT NEW 4" WASTE LINE TO EXISTING 4" (OR LARGER) WASTE PIPING AS SHOWN IN BASEMENT LEVEL PLUMBING PLAN. NEW GAS METER FOR REMODELED SUITE PROVIDED AND INSTALLED BY LOCAL GAS COMPANY. LOCATE NEW METER NEAR EXISTING METER. REFER TO GAS LOAD CALCULATIONS FOR SIZING. METER TO HAVE 1,600,000 BTU CAPACITY WITH 2.0 PSI DISCHARGE PRESSURE. RUN 1-1/2" (2 PSI) GAS PIPING IN BASEMENT. COORDINATE WITH OTHER EXISTING PIPING, DUCTWORK AND BUILDING STRUCTURE. RISE 1-1/2" (1/2 PSI) GAS LINE UP THRU FLOOR NEAR KITCHEN HOOD AND RUN ALONG WALL BEHIND EQUIPMENT. CONNECT TO KITCHEN EQUIPMENT WITH SHUT-OFF VALVE AND FLEXIBLE HOSE. REFER TO DETAIL K/P2.1 FOR TYPICAL GAS LINE CONNECTION TO KITCHEN EQUIPMENT. RISE 3/4" (1/2 PSI) GAS LINE UP THRU FLOOR INSIDE EXISTING CLOSET. RISE UP TO ABOVE TOILET ROOMS AND CONNECT TO (2) NEW FURNACES. REFER TO DETAIL M/P2.1 FOR TYPICAL GAS LINE CONNECTION TO FURNACES. RISE 3/4" (2 PSI) GAS LINE UP THRU FLOOR BEHIND WATER HEATERS. CONNECT 3/4" LINE TO (2) WATER HEATERS WITH REGULATOR, SHUT-OFF VALVE AND FLEXIBLE HOSE. EXTEND 3/4" (2 PSI) PIPING UP THRU ROOF AND CONNECT TO MAKE-UP AIR UNIT FOR KITCHEN HOOD. CONNECT TO EQUIPMENT WITH PRESSURE REGULATOR, SHUT-OFF VALVE AND FLEXIBLE HOSE. REFER TO DETAIL L/P2.1 FOR TYPICAL GAS LINE CONNECTION TO ROOF MOUNTED EQUIPMENT. CONNECT HOT WATER, COLD WATER AND/OR WASTE PIPING TO EXISTING CORRESPONDING PIPING IN BASEMENT. CONTRACTOR FOR FIELD VERIFY EXACT SIZES AND LOCATIONS OF EXISTING PIPING. NEW PIPING TO MATCH ELEVATIONS EXISTING PIPING AND CONNECT TO EQUAL OR LARGER PIPE SIZES. RISE 1/2" COLD WATER LINE UP IN WALL ABOVE. CONNECT TO WATER FILTRATION SYSTEM ABOVE. REFER TO KITCHEN EQUIPMENT DRAWINGS. DINING AREA 106 RESTROOM 105 RESTROOM 104 SERVING 107 KITCHEN 108 FOYER 100 ENTRY 103 ELEVATOR 101 STAIRWAY 102 DINING AREA 106 RESTROOM 105 RESTROOM 104 SERVING 107 KITCHEN 108 FOYER 101 ENTRY 103 ELEVATOR 101 STAIRWAY 102 PREPARATION 111 DISHWASH 110 EXIST. FREEZER 1 FIRE 103 FIRE 103 1 F5 2 F5 BASEMENT LEVEL PLUMBING PLAN NorthSCALE: 1/8" = 1'-0" 2 1 3 2 1 1 6 4 4 2 2 4 1 4 1 2 1 1 2 1 EXISTING COTG EXISTING COTG (E) 4" GREASE WASTE (E) 4" SANITARY WASTE (E) 4" SANITARY WASTE (E) 4" GREASE WASTE (E) 2-1/2" COLD WATER(E) 2-1/2" COLD WATER (E) 1" COLD WATER LINE AND SHUT-OFF VALVE 2 4 3 5 6 7 8 9 10 11 EXISTING ELECTRICAL PANEL STAIRWAY 102 ELEVATOR 101 FOYER 001 ELECT. 002 BASEMENT 003 WH-1 WS-1 7 BRINE TANK 6 K-3 FS-1 K-13 K-2 FS-1K-21K-18 & 8 8 K-22 FS-1 8 K-24K-23 & K-51 K-50 11 1-1/2" G 11 11 1-1/2" G 1-1/2" G K-34 K-35 K-36 K-37 K-38 K- 4 8 K- 4 7 K- 4 6 K-39 K-41 K-42 K-44 K-45 K-72 FS-18 FS-18 K-61 K-60 FS-1 8 K-62 FS-1 8 K-68 K-69 K-66 GAS LOAD CALCULATIONS: K-34 80,000 BTU K-35 80,000 BTU K-36 40,000 BTU K-37 122,000 BTU K-38 122,000 BTU K-41 120,000 BTU K-42 192,000 BTU K-44 66,000 BTU TOTAL GAS LOAD 1,506,000 BTU K-39 66,000 BTU TOTAL CFH LOAD (1000/BTU)1506 CFH TOTAL DESIGN LOAD 1,600,000 BTU PIPE LENGTH 200 FT. DISCHARGE PRESSURE 2.0 PSI GAS PIPE SIZE 1-1/2" K- 4 9 1" CD 3/4" CD 2 1 1 1 1 4 14 15 K-72 K-45 FS-1 1/2" HW & CW 1-1/2" W 4" W 2" V 4" W (GREASE) 14 2" V 1/2" CW 4" W FS-1 K-62 2" V 4" W FS-1 15 K-69K-68 &1/2" CW 4" W 2" V FS-1 14 (E) 4" GREASE WASTE (E) 4" GREASE WASTE K-23 K-22 K-18 FS-1 2" V FS-1 2" V 4" W 4" W 3/4" CW (E) 3/4" HW (E) 3/4" HW K-50K-51 & 1-1/2" W 14 14 12 13 9 RISE 1-1/2" GAS LINE UP THRU FLOOR. PLACE REGULATOR IN BASEMENT. APPROXIMATELY 125' 88,000 BTU 110,000 BTU 2 F 1 F 1-1/2" G IN BASEMENT 1-1/2" (2 PSI) GAS LINE FROM METER. SEE MAIN FLOOR PLAN ABOVE FOR METER LOCATION. 1" G RISE GAS LINE UP THRU FLOOR. 1-1/2" G IN BASEMENT SEE BASEMENT PLAN BELOW FOR CONTINUATION OF 1-1/2" GAS LINE. PRESSURE REG. (2# TO 1/2#) 3/4" G 3/4" G MAU 380,000 BTU 14 15 133/4" (2 PSI) GAS 1-1/2" (1/2 PSI) GAS 3/4" GAS 3/4" GAS 12 WH-2 40000 BTU WH-1 40,000 BTU WH-2 6 K-41 1 FS-1 EXISTING FLOOR SINK TO REMAIN 2 CONNECT NEW 2" VENT TO EXISTING 2" (OR LARGER) VENT PIPING. CONTRACTOR TO FIELD VERIFY. CONNECT NEW 2" VENT TO EXISTING 2" (OR LARGER) VENT PIPING. CONTRACTOR TO FIELD VERIFY. 2" V 2" V 2" V 2" V 2" VENT IN WALL 2" V 2" V 2" V 2" V 2" V 2" V 2" V CONNECT NEW 2" VENT TO EXISTING 2" (OR LARGER) VENT PIPING. CONTRACTOR TO FIELD VERIFY. 2" V FILED VERIFY ACTUAL ROUTING OF GAS LINE FOR EXISTING BUILDING STRUCTURE. GAS LINE UP THRU FLOOR TO WATER HEATERS AND MAKE-UP AIR UNIT ON ROOF. PRESSURE REG. (2# TO 1/2#) 12 FS-1 2" V K-13FS-1 2" V K-2 K-4 P2.1 PL U M B I N G S C H E D U L E A N D D E T A I L S 2OF: SHEET: JOB NO. 21050 M JENSEN DATE: APRIL '23 D HANSEN DRWN. BY:CKD. BY: HE M M I N G V I L L A G E R E X B U R G , I D A H O CA F E S A B O R RE M O D E L O F : PR O J E C T : SH E E T T I T L E : S: \ 2 0 0 0 - 2 0 \ 2 3 \ 2 3 0 5 0 C a f e S a b o r \ C A D \ 2 3 0 5 0 - P 2 . 1 . d w g J u n 0 1 , 2 0 2 3 - 1 0 : 0 9 a m En g i n e e r e d S y s t e m s A s s o c i a t e s Me c h a n i c a l E n g i n e e r s Dw a y n e S u d w e e k s P . E . , D a v e H a n s e n P . E . , T a n n e r D a v i s P . E . 13 5 5 E a s t C e n t e r - P o c a t e l l o , I d a h o 8 3 2 0 1 Ph o n e : ( 2 0 8 ) 2 3 3 - 0 5 0 1 e m a i l : e s a @ e n g s y s t e m s . c o m CON S T R U C T I O N DRA W I N G PRE L I M I N A R Y NOT F O R 3" PVC VENTS TYPICAL TRAP RETURN AIR DUCT (REC . ) 36" M I N 30" M I N (REC . ) 18"MI N (REC . ) VERT I C A L HORI Z O N T A L WALL BRACKET TYPICAL KITCHEN EQUIPMENT (SEE FLOOR PLANS) SHUT-OFF VALVE SWIVEL QUICK DISCONNECT FITTINGS AND FLEXIBLE HOSE RESTRAINING CABLE BY OTHERS EQUIPMENT REGULATOR IN OUT AIR GAP FUNNEL DRAIN 1" DRAIN LINE TO NEAREST FLOOR DRAIN OR SERVICE SINK WATTS 009 SERIES REDUCED PRESSURE BACKFLOW PREVENTER SIZE TO MATCH LINE SIZE AS SHOWN ON PLANS.TYPICAL TEST COCK SHUT-OFF VALVE SHUT-OFF VALVE UNIONUNION COLD WATER SOFT WATER BYPASS VALVE BRINE TANK MINERAL TANK FLOOR DRAIN SHUT OFF VALVE SHUT OFF VALVE FLOOR 1/2" BRINE LINE TOP MOUNT CONTROL VALVE (2) 1" DRAIN LINES TO NEAREST FLOOR DRAIN OR FLOOR SINK MULTI-RESIN SOFTENER SYSTEM WATER HEATER PIPING DETAIL NO SCALED 1'-0" 1/8 BEND IF CLEANOUT OCCURS AT END OF LINE. WASTE LINE WASTE LINE. LENGTH TO SUIT. 1/8 BEND CHROME WALL COVER AND SCREW FLOOR LINE WALL MAY EXTEND AS A WASTE OR VENT PLUGGED TEE WITH CLEANOUT POLYMER, COPPER, BRONZE OR BRASS FITTING PEX PIPING AS SHOWN ON PLANS REINFORCED RING THIS TYPE (COLD EXPANSION) OF FITTING REQUIRES THAT THE PEX PIPING, WITH REINFORCING PEX RING PLACED OVER THE END OF THE END OF THE PIPE, IS EXPANDED BEFORE THE FITTING IS INSERTED INTO THE PIPE END. THE EXPANDED PIPE END IS ALLOWED TO RETRACT ONTO THE FITTING TO FORM THE SEAL. THE MEMORY OF THE PIPE ALLOWS IT TO TIGHTEN OVER THE FITTING. AN EXPANDER TOOL IS REQUIRED TO EXPAND THE PIPE AND THE PEX RING TOGETHER. NOTE: STAINLESS STEEL CAMP BANDS ARE ALSO PERMITTED FOR REINFORCING RING. ALL JOINTS (TEES. ELBOWS, COUPLINGS, ETC.) ARE JOINTED SIMILARLY. 12" 6"HEAT SOURCE PEX PIPING MIN. CLEARANCES KEEP TUBING A MINIMUM OF 12" VERTICALLY OR 6" HORIZONTALLY FROM SOURCES OF HIGH HEAT SUCH AS LIGHT FIXTURES, FLUES OR HEATING EQUIPMENT. NOTE: USE ONLY CONTINUOUS LENGTH TUBING (NO FITTINGS) WHEN INSTALLING PEX UNDER OR WITHIN A SLAB. PROTECT PEX TUBING WITH NONMETALLIC SLEEVES WHERE IT PENETRATES A SLAB OR FOUNDATION WALL. DO NOT CRUSH OR KINK TUBING DO NOTE DRAG TUBING OVER ROUGH TERRAIN, ROCKS, OR ANY SURFACE THAT CAN CUT, PUNCTURE OR DAMAGE TUBING WALL. 3/8"4" 1/2"5" 3/4"7" 1"9" TUBING SIZE MIN. RADIUS BENDING TUBING AND FITTINGS SHALL BE STORED UNDERCOVER FOR CLEANLINESS AND TO AVOID EXPOSURE TO SUNLIGHT. CONSULT MANUFACTURER FOR RECOMMENDED LIMITS TO OUTSIDE STORAGE. NAIL PLATE WALL STUD (WOOD OR METAL SIMILAR) PEX PIPING WALL INSTALLATION DO NOT USE IN ANY APPLICATION WHERE TUBING WILL BE EXPOSED TO DIRECT SUNLIGHT. PIPE SUPPORTS PIPE SUPPORTS: PLASTIC HANGERS AND STRAPS ARE RECOMMENDED, BUT METAL SUPPORTS WHICH ARE DESIGNED FOR USE WITH PLASTIC TUBING CAN BE USED. DO NOT USE SUPPORTS THAT PINCH OR CUT THE TUBING. SUPPORT SHOULD ALLOW FREE TUBING MOVEMENT. INSPECT ALL SUPPORTS PRIOR TO INSTALLATION TO ENSURE THAT SHARP EDGES DO NOT EXIST THAT CAN DAMAGE THE TUBING. VERTICAL TUBING TO BE SUPPORTED EVERY 8'-0" WHEN PENETRATING METAL STUDS, UTILIZE A BUSING DESIGNED FOR PLASTIC TUBING. SUPPORTS S.9HALL BE INSTALLED AT CHANGES IN DIRECTION TO RELIEVE STRESS AS SHOWN. APPROVED BUSHING CLAMP WOOD STUD METAL STUD CLAMP AT TURN VENTWASTEHOTCOLDSYM.DESCRIPTIONVENTWASTEHOTCOLDSYM.DESCRIPTION GASGAS WATER SOFTENER PIPING DIAGRAM NO SCALEHBACKFLOW PREVENTER DETAIL NO SCALEG PEX PIPE HANDLING DETAILS NO SCALECPEX PIPE INSTALLATION DETAILS NO SCALEB CONDENSATE DRAIN CONNECTION DETAIL NO SCALEF PEX PIPE FITTING DETAILS NO SCALEA WALL CLEAN OUT DETAIL NO SCALEE GAS LINE CONNECTION DETAIL NO SCALEJ ROOF EQUIPMENT GAS LINE CONNECTION NO SCALEL HORIZONTAL FURNACE PIPING DIAGRAM NO SCALEM SWIVEL GAS HOSE CONNECTOR DETAIL NO SCALEK FURNACE PER SCHEDULE. SUPPORT ON 12 GA. 1-5/8"x1-3/8" UNISTRUT. KINDORF OR APPROVED. FLEX DUCT CONNECTION TYP. SUPPLY AND RETURN 22 GA. SECONDARY DRAIN PAN WITH 1-1/2" LIP. EXTEND UNDER COIL. HANG FROM UNISTRUT CHANNEL. 3/4" DRAIN LINE TO NEAREST FLOOR DRAIN (SEPARATE FROM FURNACE DRAIN LINE) 3/4" PVC FURNACE CONDENSATE TO FLOOR DRAIN 3/4" CONDENSATE DRAIN TO NEAREST FLOOR DRAIN FLEX GAS CONNECTION 3/4" COND. DRAIN REFRIGERANT LINES PER MANUFACTURER SUPPLY AIR DUCT FS-1 WH-1 WS-1 K-50 K-60 K-48 K-3 K-2 K-23 K-22 K-34 K-44 K-46 K-45 K-36 K-37 K-39 K-41 K-42 FLOOR SINK - ZURN Z-1900-2 WITH 1/2 GRATE, DEEP SEAL P-TRAP AND 1/2" TRAP PRIMER CONNECTION. LOCATE BELOW EQUIPMENT. 2"4"--------- BEVERAGE RACK - BY KITCHEN EQUIPMENT CONTRACTOR. PLUMBING CONTRACTOR TO RUN DRAIN LINES TO FLOOR SINK. COORDINATE WITH EQUIPMENT PROVIDED. ------------TO FLOOR SINK EXISTING FIXTURE - EXISTING FIXTURE TO REMAIN. EXISTING WASTE, WATER AND VENT PIPING TO REMAIN. PROTECT FIXTURE AND PIPING DURING CONSTRUCTION. EXISTINGEXISTINGEXISTING ---EXISTING DISHWASHER - BY KITCHEN EQUIPMENT CONTRACTOR. PLUMBING CONTRACTOR TO ROUGH-IN AND CONNECT 1/2" HOT WATER LINE WITH SHUT-OFF VALVES. RUN DRAIN LINE TO FLOOR SINK. ------1/2"---TO FLOOR SINK DISH TABLE WITH PRE-RINSE FAUCET - BY KITCHEN EQUIPMENT CONTRACTOR. PLUMBING CONTRACTOR TO ROUGH-IN AND CONNECT 1/2" HOT AND COLD WATER LINES WITH SHUT-OFF VALVES. RUN DRAIN LINE TO FLOOR SINK. ---1/2"1/2"---TO FLOOR SINK GAS RANGE - BY KITCHEN EQUIPMENT CONTRACTOR. PLUMBING CONTRACTOR TO ROUGH-IN AND CONNECT 3/4" GAS LINE WITH SHUT-OFF VALVE AND SWIVEL CONNECTION. SEE DETAIL K/P2.1. (80,000 BTU) ---------3/4" K-24 --- GAS CONVECTION OVEN - BY KITCHEN EQUIPMENT CONTRACTOR. PLUMBING CONTRACTOR TO ROUGH-IN AND CONNECT 3/4" GAS LINE WITH SHUT-OFF VALVE AND SWIVEL CONNECTION. SEE DETAIL K/P2.1. (40,000 BTU) ---------3/4"--- GAS FRYER - BY KITCHEN EQUIPMENT CONTRACTOR. PLUMBING CONTRACTOR TO ROUGH-IN AND CONNECT 3/4" GAS LINE WITH SHUT-OFF VALVE AND SWIVEL CONNECTION. SEE DETAIL K/P2.1. (122,000 BTU) ---------3/4"--- GAS GRIDDLE - BY KITCHEN EQUIPMENT CONTRACTOR. PLUMBING CONTRACTOR TO ROUGH-IN AND CONNECT 3/4" GAS LINE WITH SHUT-OFF VALVE AND SWIVEL CONNECTION. SEE DETAIL K/P2.1. (66,000 BTU) ---------3/4"--- K-35 K-38 GAS CHARBROILER - BY KITCHEN EQUIPMENT CONTRACTOR. PLUMBING CONTRACTOR TO ROUGH-IN AND CONNECT 3/4" GAS LINE WITH SHUT-OFF VALVE AND SWIVEL CONNECTION. SEE DETAIL K/P2.1. (120,000 BTU) ---------3/4"--- GAS HOT PLATE - BY KITCHEN EQUIPMENT CONTRACTOR. PLUMBING CONTRACTOR TO ROUGH-IN AND CONNECT 3/4" GAS LINE WITH SHUT-OFF VALVE AND SWIVEL CONNECTION. SEE DETAIL K/P2.1. (192,000 BTU) ---------3/4"--- GAS GRIDDLE - BY KITCHEN EQUIPMENT CONTRACTOR. PLUMBING CONTRACTOR TO ROUGH-IN AND CONNECT 3/4" GAS LINE WITH SHUT-OFF VALVE AND SWIVEL CONNECTION. SEE DETAIL K/P2.1. (66,000 BTU) ---------3/4"--- WORK TABLE WITH PREP SINK - BY KITCHEN EQUIPMENT CONTRACTOR. PLUMBING CONTRACTOR TO ROUGH-IN AND CONNECT 1/2" HOT AND COLD WATER LINES WITH SHUT-OFF VALVES. RUN DRAIN LINE TO FLOOR SINK. ---1/2"1/2"---TO FLOOR SINK HOT FOOD TABLE - BY KITCHEN EQUIPMENT CONTRACTOR. PLUMBING CONTRACTOR TO RUN DRAIN LINE TO FLOOR SINK. ------------TO FLOOR SINK REFRIGERATED FOOD TABLE - BY KITCHEN EQUIPMENT CONTRACTOR. PLUMBING CONTRACTOR TO RUN DRAIN LINE TO FLOOR SINK. ------------TO FLOOR SINK K-49 K-47 K-51 HAND WASH SINK - BY KITCHEN EQUIPMENT CONTRACTOR. PLUMBING CONTRACTOR TO ROUGH-IN AND CONNECT 1/2" HOT AND COLD WATER LINES WITH SHUT-OFF VALVES, AND 1- 1/2" P-TRAP. 1-1/2"1-1/2"1/2"1/2"--- ICE MAKER WITH STORAGE BIN AND WATER FILTER - BY KITCHEN EQUIPMENT CONTRACTOR. PLUMBING CONTRACTOR TO ROUGH-IN AND CONNECT 1/2" COLD WATER LINE, THRU WALL MOUNTED BACK-FLOW PREVENTION DEVICE AND FILTER, TO ICE MAKER. RUN DRAIN LINE TO FLOOR SINK. ---1/2"1/2"--- K-61 K-62 TO FLOOR SINK K-66 BEVERAGE DISPENSER - BY KITCHEN EQUIPMENT CONTRACTOR. PLUMBING CONTRACTOR TO ROUGH-IN AND CONNECT 1/2" COLD WATER LINES THRU WALL MOUNTED BACK-FLOW PREVENTION DEVICE AND FILTER. RUN DRAIN LINES TO FLOOR SINK. ---1/2"------TO FLOOR SINK K-68 COFFEE & ICE TEA BREWERS - BY KITCHEN EQUIPMENT CONTRACTOR. PLUMBING CONTRACTOR TO ROUGH-IN AND CONNECT 1/2" COLD WATER LINES THRU WALL MOUNTED BACK-FLOW PREVENTION DEVICE AND FILTER. RUN DRAIN LINES TO FLOOR SINK. ---1/2"------TO FLOOR SINK K-69 K-72 HAND WASH SINK - BY KITCHEN EQUIPMENT CONTRACTOR. PLUMBING CONTRACTOR TO ROUGH-IN AND CONNECT 1/2" HOT AND COLD WATER LINES WITH SHUT-OFF VALVES, AND 1- 1/2" P-TRAP. 1-1/2"1-1/2"1/2"1/2"--- WATER SOFTENER -SENTY II SERIES A960-70 WITH BY-PASS VALVE AND SINGLE BRINE TANK, 23 GPM PEAK FLOW, 70,000 GRAIN CAPACITY WITH METERING VALVE, AND 3/4" COLD WATER LINE. REFER TO DETAIL H/P2.1 FOR TYPICAL PIPING CONNECTIONS. RUN DRAIN LINE TO EXISTING FLOOR SINK. ------3/4"------ GAS FIRED WATER HEATER - SIMILAR TO A.O.SMITH MODEL GPD50 WITH 50 GALLON CAPACITY, 3/4" T&P RELIEF VALVE, THERMAL EXPANSION TANK, HEAT TRAP NIPPLES, AND SYMMONS 2-700 MIXING VALVE. (40,000 BTU) REFER TO DETAIL D/P2.1 FOR TYPICAL PIPING CONNECTIONS. ------3/4"3/4"3/4" FLOOR WALL SANITARY TEE TRAP EXTEND CONDESATE DRAIN LINE OUT OF WALL BELOW CABINET TYPICAL COUNTERTOP SINK DISHWASHER CONNECTION NOTE: CONDENSATE CONNECTION TO WALL MOUNTED LAVATORY SIMILAR 2" VENT TO ATMOSPHERE CONDENSATE DRAIN LINE DOWN IN WALL K-18 DISH TABLE WITH POT SINK AND FAUCET - BY KITCHEN EQUIPMENT CONTRACTOR. PLUMBING CONTRACTOR TO ROUGH-IN AND CONNECT 1/2" HOT AND COLD WATER LINES WITH SHUT-OFF VALVES. RUN DRAIN LINE TO FLOOR SINK. ---1/2"1/2"---TO FLOOR SINK K-21 6" V E R T I C A L EQUIPMENT ROOF GROUND JOINT UNION GAS PRESSURE REGULATOR 2# TO 1/2# PROVIDE ESCHUCEON PLATE AROUND PIPING FLEXIBLE GAS CONNECTOR. 18" MAX. DRIP LEG SAME SIZE AS PIPE MANUAL MAIN SHUT-OFF VALVE 'PYRAMID' TYPE SUPPORTS 6" V E R T I C A L 3/4" DROP FROM MAIN. SEE PLAN FOR SIZE MANUAL MAIN SHUT-OFF VALVEGROUND JOINT UNION EQUIPMENT CASING FLEXIBLE GAS CONNECTOR. 18" MAX. DRIP LEG SAME SIZE AS DROP WH-2 G R 3/4" WATER HEATER ANCHOR BALL VALVE (TYP.) RECIRCULATING PUMP OPERATING THERMOSTAT AQUASTAT HOT WATER RECIRC COLD WATER LINE HOT WATER LINE DIELECTRIC UNION (TYP) REGULATOR UNION HEAT TRAP FITTING MTHERMOMETER DRAIN VALVE W/ THREADED HOSE CONNECTION PIPE FULL SIZE TO FLOOR DRAIN AMTROL ST-5 EXPANSION TANK T&P RELIEF VALVE SIZED TO MATCH WATER HEATER MIXING VALVE FOR TEMPERED WATER GAS SUPPLY GAS COCK DIRT LEG RISE FLUES UP THRU ROOF K-4