HomeMy WebLinkAboutELECTRICAL EMAIL 2 - 23-00435 - Precision Precast - New Commercial BldgShauna,
Can you please attach this email and attachment to the precision precast file?
Thanks,
Alex Owens
Electrical Inspector
Rexburg Building Department
35 North 1st East
Rexburg, Idaho 83440
208-372-2172
From: Quinn Christensen <rivers.edge.elec@gmail.com>
Sent: Thursday, July 20, 2023 12:55 PM
To: Alex Owens <Alex.Owens@rexburg.org>
Subject: Precision Pre cast (Thorton)
Building Permit will be through Steel Vision. Ben Munns @ (208) 313-3949
Planning to install....
1-800amp CT Can 48”x48”x14” 120/208v 3 phase
1-800amp 120/208v 3 phase RT enclosed circuit breaker
Then tapping to 2-200 amp indoor enclosed circuit breakers and 1-200 main breaker 42space qo panel board(shop). The 2 indoor enclosed circuit breakers will be feeding 2-200 amp main
lug 42 space panelboards, 1 for the office space and the other to feed the batch plant area.
-
Identified loads
2-60amp 208v 3 phase overhead cranes
1-100amp 208v 3 phase mini batch plant fed from central location located on batch plant.
Office space
2-3 welder circuits
30-270w LED high bays-looking to deliver around 80-90 foot candles to working plane
Well for water