Compressive Strength of Concrete Test Specimens
Project Number:
22-247
Cumulative Test Load Amount:
7.2
Project Name:
U-Haul Moving and Storage
Test Location:
Building A slab approx. A-17
Client:
Bateman-Hall
Admixtures:
MS-AC-534, MP-322
Contractor:
Bryan Landon
Supplier:
Walters Ready Mix
Mix Number:
W-172FI U
Date:
6/1/2023
Cylinder Log #:
227
Field Test Results:
Set #:
1
Entrained Air
(%):
1.5
Concrete
Temperature
(°F):
68
Ambient
Temperature
(°F):
45
Unit Weight
(PCF):
137.3
Tested By:
B. Choffin
Date:
6/1/2023
Picked Up By:
Jense Christensen
Date:
6/2/2023
Time:
11:00 AM
Max, Min Temperature
81,59
Previous Test Results:
Cylinder ID:Break Age:Break Date:Area (in^2):Maximum Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
A 7 6/8/2023 12.57 52335 4163 4,000.00 Type 6
File name:
22247SB06292023JPC
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
984FA1A4-8740-4289-9935-8F696982C955 2
Current Break Testing:
Cylinder
ID:
Break
Age:
Break
Date:
Diameter
(in):
Area
(in^2):
Maximum
Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
B 28 6/29/2023 4.000 12.57 62,525.0 4974 4,000.0 Type 1
C 28 6/29/2023 4.000 12.57 65,880.0 5241 4,000.0 Type 1
D 28 6/29/2023 4.000 12.57 62,385.0 4963 4,000.0 Type 3
Second Break Average:
5059
Date:
07/01/2023
Reviewed By:
Luke Hammar
Signature:
File name:
22247SB06292023LSH
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
6BADBDE5-2377-4C9D-BC80-386104ABC2EA 1
4103 E 605 N Suite 1
Rigby, ID 83442
208.932.4428
Compressive Strength of Concrete Test Specimens
Project Number:
22-247
Cumulative Test Load Amount:
30
Project Name:
U-Haul Moving and Storage
Test Location:
Building A Gridline C:31
Client:
Bateman-Hall
Admixtures:
MS AC 534, MP 322, MA
AE 90
Contractor:
Bryan Landon
Supplier:
Walters Ready Mix, Inc.
Mix Number:
142-3500
Date:
6/1/2023
Cylinder Log #:
228
Field Test Results:
Set #:
2
Entrained Air
(%):
5.0
Concrete
Temperature
(°F):
68
Ambient
Temperature
(°F):
46
Unit Weight
(PCF):
143.4
Tested By:
Michael Hammar
Date:
6/1/2023
Picked Up By:
Jense Christensen
Date:
6/2/2023
Time:
11:00 AM
Max, Min Temperature
81,59
Previous Test Results:
Cylinder ID:Break Age:Break Date:Area (in^2):Maximum Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
A 3 6/4/2023 12.57 45380 3610 3,500.00 Type 1
B 7 6/8/2023 12.57 56145 4467 3,500.00 Type 3
File name:
22247SB06292023LSH
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
6BADBDE5-2377-4C9D-BC80-386104ABC2EA 2
Current Break Testing:
Cylinder
ID:
Break
Age:
Break
Date:
Diameter
(in):
Area
(in^2):
Maximum
Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
C 28 6/29/2023 4.000 12.57 65,325.0 5197 3,500.0 Type 3
D 28 6/29/2023 4.000 12.57 65,055.0 5175 3,500.0 Type 3
E 28 6/29/2023 4.000 12.57 65,390.0 5202 3,500.0 Type 1
Second Break Average:
5191
Date:
07/05/2023
Reviewed By:
Luke Hammar
Signature:
File name:
22247SB07072023JPC
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
E6944D6B-549B-41AF-83B3-D06304636D23 1
4103 E 605 N Suite 1
Rigby, ID 83442
208.932.4428
Compressive Strength of Concrete Test Specimens
Project Number:
22-247
Cumulative Test Load Amount:
10
Project Name:
U-Haul Moving and Storage
Test Location:
Approx. 300 South of Northwest corner of Building B.
Client:
Bateman-Hall
Admixtures:
MS AC 534, MP 322
Contractor:
Bryan Landon Construction
Supplier:
Walters Ready Mix, Inc.
Mix Number:
W172FI 35
Date:
6/9/2023
Cylinder Log #:
244
Field Test Results:
Set #:
1
Entrained Air
(%):
1.5
Concrete
Temperature
(°F):
70
Ambient
Temperature
(°F):
48
Unit Weight
(PCF):
145.1
Tested By:
B. Choffin
Date:
6/9/2023
Picked Up By:
Jense Christensen
Date:
6/10/2023
Time:
1:00 PM
Max, Min Temperature
80, 60
Previous Test Results:
Cylinder ID:Break Age:Break Date:Area (in^2):Maximum Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
A 7 6/16/2023 12.57 50615 4027 4,000.00 Type 6
File name:
22247SB07072023JPC
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
E6944D6B-549B-41AF-83B3-D06304636D23 2
Current Break Testing:
Cylinder
ID:
Break
Age:
Break
Date:
Diameter
(in):
Area
(in^2):
Maximum
Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
B 28 7/7/2023 4.000 12.57 60,865.0 4842 4,000.0 Type 2
C 28 7/7/2023 4.000 12.57 62,830.0 4998 4,000.0 Type 4
D 28 7/7/2023 4.000 12.57 64,175.0 5105 4,000.0 Type 3
Second Break Average:
4982
Date:
07/07/2023
Reviewed By:
Luke Hammar
Signature:
File name:
22247SB07122023JPC
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
1EA35FD2-8B84-4AD8-AF13-29364520E82E 1
4103 E 605 N Suite 1
Rigby, ID 83442
208.932.4428
Compressive Strength of Concrete Test Specimens
Project Number:
22-247
Cumulative Test Load Amount:
10
Project Name:
U-Haul Moving and Storage
Test Location:
Valley gutter, 5 ft. south of building 1.
Client:
Bateman-Hall
Admixtures:
AE200, POLY980
Contractor:
Bryan Landon Construction
Supplier:
Knife River
Mix Number:
C401G456
Date:
6/14/2023
Cylinder Log #:
276
Field Test Results:
Set #:
1
Entrained Air
(%):
6.0
Concrete
Temperature
(°F):
70
Ambient
Temperature
(°F):
65
Unit Weight
(PCF):
141.1
Tested By:
Michael Hammar
Date:
6/14/2023
Picked Up By:
Jense Christensen
Date:
6/15/2023
Time:
1:38 PM
Max, Min Temperature
80,60
Previous Test Results:
Cylinder ID:Break Age:Break Date:Area (in^2):Maximum Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
A 7 6/21/2023 12.57 44360 3529 3,500.00 Type 6
File name:
22247SB07122023JPC
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
1EA35FD2-8B84-4AD8-AF13-29364520E82E 2
Current Break Testing:
Cylinder
ID:
Break
Age:
Break
Date:
Diameter
(in):
Area
(in^2):
Maximum
Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
B 28 7/12/2023 4.000 12.57 57,760.0 4595 3,500.0 Type 1
C 28 7/12/2023 4.000 12.57 57,250.0 4554 3,500.0 Type 1
D 28 7/12/2023 4.000 12.57 59,245.0 4713 3,500.0 Type 1
Second Break Average:
4621
Date:
07/12/2023
Reviewed By:
Luke Hammar
Signature:
File name:
22247SB07142023JPC5
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
EE1F418C-5461-4C58-8E7B-E9745E1BE492 1
4103 E 605 N Suite 1
Rigby, ID 83442
208.932.4428
Compressive Strength of Concrete Test Specimens
Project Number:
22-247
Cumulative Test Load Amount:
150
Project Name:
U-Haul Moving and Storage
Test Location:
Building B slab
Client:
Bateman-Hall
Admixtures:
MS AC 534, Delvo, MP 322
Contractor:
Bryan Landon Construction
Supplier:
Walters Ready Mix, Inc.
Mix Number:
1421 4000
Date:
6/16/2023
Cylinder Log #:
267
Field Test Results:
Set #:
5
Entrained Air
(%):
1.9
Concrete
Temperature
(°F):
65
Ambient
Temperature
(°F):
45
Unit Weight
(PCF):
145.8
Tested By:
B. Choffin
Date:
6/16/2023
Picked Up By:
Jense Christensen
Date:
6/17/2023
Time:
1:00 PM
Max, Min Temperature
80,62
Previous Test Results:
Cylinder ID:Break Age:Break Date:Area (in^2):Maximum Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
A 7 6/23/2023 12.57 56620 4504 4,000.00 Type 3
File name:
22247SB07142023JPC5
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
EE1F418C-5461-4C58-8E7B-E9745E1BE492 2
Current Break Testing:
Cylinder
ID:
Break
Age:
Break
Date:
Diameter
(in):
Area
(in^2):
Maximum
Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
B 28 7/14/2023 4.000 12.57 68,635.0 5460 4,000.0 Type 1
C 28 7/14/2023 4.000 12.57 66,815.0 5315 4,000.0 Type 1
D 28 7/14/2023 4.000 12.57 67,405.0 5362 4,000.0 Type 1
Second Break Average:
5379
Date:
07/14/2023
Reviewed By:
Luke Hammar
Signature:
File name:
22247SB07142023JPC4
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
91662058-6FAC-45D6-8AFD-1B97304B4AA8 1
4103 E 605 N Suite 1
Rigby, ID 83442
208.932.4428
Compressive Strength of Concrete Test Specimens
Project Number:
22-247
Cumulative Test Load Amount:
110
Project Name:
U-Haul Moving and Storage
Test Location:
Building B slab
Client:
Bateman-Hall
Admixtures:
MS AC 534, Delvo, MP 322
Contractor:
Bryan Landon Construction
Supplier:
Walters Ready Mix, Inc.
Mix Number:
1421 4000
Date:
6/16/2023
Cylinder Log #:
266
Field Test Results:
Set #:
4
Entrained Air
(%):
1.9
Concrete
Temperature
(°F):
67
Ambient
Temperature
(°F):
43
Unit Weight
(PCF):
144
Tested By:
B. Choffin
Date:
6/16/2023
Picked Up By:
Jense Christensen
Date:
6/17/2023
Time:
1:00 PM
Max, Min Temperature
80,62
Previous Test Results:
Cylinder ID:Break Age:Break Date:Area (in^2):Maximum Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
A 7 6/23/2023 12.57 58600 4662 4,000.00 Type 6
File name:
22247SB07142023JPC4
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
91662058-6FAC-45D6-8AFD-1B97304B4AA8 2
Current Break Testing:
Cylinder
ID:
Break
Age:
Break
Date:
Diameter
(in):
Area
(in^2):
Maximum
Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
B 28 7/14/2023 4.000 12.57 69,785.0 5552 4,000.0 Type 1
C 28 7/14/2023 4.000 12.57 68,420.0 5443 4,000.0 Type 3
D 28 7/14/2023 4.000 12.57 68,125.0 5420 4,000.0 Type 1
Second Break Average:
5472
Date:
07/14/2023
Reviewed By:
Luke Hammar
Signature:
File Name
22247C07212023CH
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
A089E9C4-866A-44CD-A7AD-CC093A9AF3EE 1
4103 E 605 N Suite 1
Rigby, ID 83442
208.932.4428
Compressive Strength of Concrete Test Specimens
Project Number:
22-247
Cumulative Test Load Amount:
11.0
Ticket #:
06655
Project Name:
U-Haul Moving and Storage
Test Location:
Exterior lab south west corner
of building B
Concrete Member:
Exterior Slab
Client:
Bateman-Hall
Admixtures:
DELVO, ML ASR 30, MP
322, MA AE 90
Required 28 day Strength
(psi):
4,000.0
Contractor
Bryan Landon
Supplier:
Walters Ready Mix
Mix Number:
400-4500
Date:
07/21/2023
Start Time
07:30 AM
Time on Project
4 hours 30 minutes
Tested By:
Caleb Hammar
Testing:
Set #:Cumulative
Test
Load
Amount:
Ticket
Image:
Ticket
#:
Time
Tested:
Test
Location:
Ambient
Temp.
(°F):
Weight
of
Concrete
(lbs):
Unit
Weight
(PCF):
Concrete
Temp.
(°F):
Entrained
Air
(%):
Entrained
Air
Spec.
(%):
Slump
(in):
Slump
Spec.
(in):
2 11.0 06655 09:15
AM
Exterior
lab
south
west
corner
of
building
B
74 34.860 140.0 78 6.1 6 +-
1.5
5 1/2 8 Max
Observations/Remarks:
I arrived on site and began observations on the exterior slab for the south east corner of building B. The first
truck arrived at the same time that I was performing a test for a different pour and by the time I finished the
different pour, the first truck had already finished pouring. I received a sample from the second truck after
approximately 5 yards had been expelled from the truck. The truck stopped pouring and waited for the results of
the test. With the sample, I performed a concrete field test and made test specimens. I observed that the results
File Name
22247C07212023CH
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
A089E9C4-866A-44CD-A7AD-CC093A9AF3EE 2
of the test were within general conformance to project specifications, and I reported my results to the contractor.
I remained on site for the duration of the pour, then left the job-site.
Signature:Reviewed By:
Luke Hammar
Signature:
Date:
07/21/2023
Inspection Images
File Name
22247C07252023LSH
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
3B97E102-5FA5-458F-B2D5-FF45ADFF1D23 1
4103 E 605 N Suite 1
Rigby, ID 83442
208.932.4428
Compressive Strength of Concrete Test Specimens
Project Number:
22-247
Cumulative Test Load Amount:
10.0
Ticket #:
22413593
Project Name:
U-Haul Moving and Storage
Test Location:
Curb along the east entrance
on N Third East
Concrete Member:
Site Elements
Client:
Bateman-Hall
Admixtures:
AE200, POLY980, DELVO
Required 28 day Strength
(psi):
3,500.0
Contractor
Bryant Greene Construction Inc.
Supplier:
Knife River
Mix Number:
C401G456
Date:
07/25/2023
Start Time
01:00 PM
Time on Project
2.5 hours
Tested By:
Bryce Choffin
Testing:
Set #:Cumulative
Test
Load
Amount:
Ticket
Image:
Ticket
#:
Time
Tested:
Test
Location:
Ambient
Temp.
(°F):
Weight
of
Concrete
(lbs):
Unit
Weight
(PCF):
Concrete
Temp.
(°F):
Entrained
Air
(%):
Entrained
Air
Spec.
(%):
Slump
(in):
Slump
Spec.
(in):
1 10.0 2241359302:20
PM
Curb
along
the
east
entrance
on N
Third
East
85 35.500 142.6 78 5 6 +-
1.5
2 3/4 8 Max
Observations/Remarks:
I arrived on site around 1:50 PM. After finding an area to setup my equipment, I proceeded to inspect the forms
where todays pour is and found it to be within project specifications.
The first truck arrived around 2:10-2:15 PM. I grabbed my sample after a yard or two was poured out, and
began performing my tests. The results were satisfactory.
File Name
22247C07252023LSH
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
3B97E102-5FA5-458F-B2D5-FF45ADFF1D23 2
I observed the contractor place the material.
Signature:Reviewed By:
Luke Hammar
Signature:
Date:
07/25/2023
Inspection Images
File Name
22247C07262023MH
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
ED417C21-9B51-4759-98E0-D9E4739A65D9 1
4103 E 605 N Suite 1
Rigby, ID 83442
208.932.4428
Compressive Strength of Concrete Test Specimens
Project Number:
22-247
Cumulative Test Load Amount:
10.0
Ticket #:
22413639
Project Name:
U-Haul Moving and Storage
Test Location:
Site elements, southeast
corner of Building B
Concrete Member:
Site Elements
Client:
Bateman-Hall
Admixtures:
AE200, POLY980, DELVO
Required 28 day Strength
(psi):
3,500.0
Contractor
Bryant Greene Construction Inc.
Supplier:
Knife River
Mix Number:
C401G426
Date:
07/26/2023
Start Time
07:30 AM
Time on Project
2 hours 30 minutes
Tested By:
Michael Hammar
Testing:
Set #:Cumulative
Test
Load
Amount:
Ticket
Image:
Ticket
#:
Time
Tested:
Test
Location:
Ambient
Temp.
(°F):
Weight
of
Concrete
(lbs):
Unit
Weight
(PCF):
Concrete
Temp.
(°F):
Entrained
Air
(%):
Entrained
Air
Spec.
(%):
Slump
(in):
Slump
Spec.
(in):
1 10.0 2241363908:30
AM
Site
elements,
southeast
corner
of
Building
B
65 35.320 141.8 71 5.5 6 +-
1.5
1 1/2 8 Max
Observations/Remarks:
I arrived on site at approximately 7:55 AM and began preparing my equipment for testing. The truck arrived at
approximately 8:25 AM and immediately began preparing to place material.
Once a sufficient amount of material had been placed, I collected a sample for testing. The tests I performed for
this sample were in general conformance of project specifications and the results were reported to the contractor.
File Name
22247C07262023MH
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
ED417C21-9B51-4759-98E0-D9E4739A65D9 2
I then cleaned my equipment and entered my vehicle to begin this report.
Signature:Reviewed By:
Luke Hammar
Signature:
Date:
07/26/2023
Inspection Images
File Name
22247C07262023MH
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
ED417C21-9B51-4759-98E0-D9E4739A65D9 3
File name:
22247FB07282023JPC
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
8E6978EF-AF72-48EB-B715-3E4DF0AB9860 1
4103 E 605 N Suite 1
Rigby, ID 83442
208.932.4428
Compressive Strength of Concrete Test Specimens
Project Number:
22-247
Cumulative Test Load Amount:
11
Project Name:
U-Haul Moving and Storage
Test Location:
Exterior lab south west corner of building B
Client:
Bateman-Hall
Admixtures:
DELVO, ML ASR 30, MP
322, MA AE 90
Ticket Number:
6655
Contractor:
Bryan Landon
Supplier:
Walters Ready Mix
Mix Number:
400-4500
Date:
7/21/2023
Cylinder Log #:
407
Field Test Results:
Set #:
2
Entrained Air
(%):
6.1
Concrete
Temperature
(°F):
78
Ambient
Temperature
(°F):
74
Unit Weight
(PCF):
140
Tested By:
Caleb Hammar
Time Tested:
04:48 PM
Picked Up By:
B.Ferguson
Date:
7/22/2023
Time:
8:55 AM
Max, Min Temperature
80, 60
Initial Break Testing:
Cylinder
ID:
Break
Age:
Break
Date:
Diameter
(in):
Area
(in^2):
Maximum
Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
A 7 7/28/2023 4.000 12.57 60,260.0 4794 4,000.0 Type 2
Date:
07/31/2023
Reviewed By:
Luke Hammar
Signature:
File name:
22247FB07282023JPC
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
7C026760-4EE5-4A59-89B4-0D822A097EAE 1
4103 E 605 N Suite 1
Rigby, ID 83442
208.932.4428
Compressive Strength of Concrete Test Specimens
Project Number:
22-247
Cumulative Test Load Amount:
5
Project Name:
U-Haul Moving and Storage
Test Location:
Curb north of building B
Client:
Bateman-Hall
Admixtures:
AE200, POLY980, DELVO
Ticket Number:
102075
Contractor:
Bryant Greene Construction
Supplier:
Knife River
Mix Number:
C401G426
Date:
7/21/2023
Cylinder Log #:
405
Field Test Results:
Set #:
1
Entrained Air
(%):
6.3
Concrete
Temperature
(°F):
73
Ambient
Temperature
(°F):
74
Unit Weight
(PCF):
140.8
Tested By:
Caleb Hammar
Time Tested:
04:43 PM
Picked Up By:
B.Ferguson
Date:
7/22/2023
Time:
8:46 AM
Max, Min Temperature
80, 60
Initial Break Testing:
Cylinder
ID:
Break
Age:
Break
Date:
Diameter
(in):
Area
(in^2):
Maximum
Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
A 7 7/28/2023 4.000 12.57 53,595.0 4264 4,000.0 Type 2
Date:
07/31/2023
Reviewed By:
Luke Hammar
Signature:
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
613A4840-717B-4326-B4B4-33AEB4A01447 1
4103 E 605 N Suite 1
Rigby, ID 83442
208.932.4428
File name:
22247FB08022023LGS
Compressive Strength of Concrete Test Specimens
Project Number:
22-247
Cumulative Test Load Amount:
10.0
Project Name:
U-Haul Moving and Storage
Test Location:
Site elements, southeast corner of Building B
Client:
Bateman-Hall
Admixtures:
AE200, POLY980
Ticket Number:
22413639
Contractor:
Bryant Greene Construction Inc.
Supplier:
Knife River
Mix Number:
C401G426
Date:
7/26/2023
Cylinder Log #:
420
Set #:
1
Entrained Air (%):
5.5
Concrete Temperature (°F):
71
Ambient Temperature (°F):
65
Unit Weight (PCF):
141.8
Tested By:
Michael Hammar
Time Tested:
08:52 AM
Field Test Results:
Pick Up Date:
7/27/2023
Picked Up By:
E. Vail
Time:
1:00 PM
Max, Min Temperature:
80, 60
Compressive Strength Data
Initial Break Testing:
Cylinder
ID:
Break
Age:
Break
Date:
Diameter
(in):
Area
(in^2):
Maximum
Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
A 7 8/2/2023 4.000 12.57 47,685.0 3794 3,500.0 Type 2
Date:
08/02/2023
Reviewed By:
Luke Hammar
Signature:
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
4C670F70-A4A4-4970-9677-C71EEC900FE0 1
4103 E 605 N Suite 1
Rigby, ID 83442
208.932.4428
File name:
2224708012023LGS
Compressive Strength of Concrete Test Specimens
Project Number:
22-247
Cumulative Test Load Amount:
10.0
Project Name:
U-Haul Moving and Storage
Test Location:
Curb along the east entrance on N Third East
Client:
Bateman-Hall
Admixtures:
AE200, POLY980, DELVO
Ticket Number:
22413593
Contractor:
Bryant Greene Construction Inc.
Supplier:
Knife River
Mix Number:
C401G456
Date:
7/25/2023
Cylinder Log #:
416
Set #:
1
Entrained Air (%):
5.0
Concrete Temperature (°F):
78
Ambient Temperature (°F):
85
Unit Weight (PCF):
142.6
Tested By:
Bryce Choffin
Time Tested:
08:11 AM
Field Test Results:
Date:
7/26/2023
Picked Up By:
B. Choffin
Time:
8:19 AM
Max, Min Temperature
80, 60
Compressive Strength Data
Initial Break Testing:
Cylinder
ID:
Break
Age:
Break
Date:
Diameter
(in):
Area
(in^2):
Maximum
Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
A 7 8/1/2023 4.000 12.57 57,950.0 4610 3,500.0 Type 2
Date:
08/02/2023
Reviewed By:
Luke Hammar
Signature:
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
D0314F04-D661-4971-9283-2CB77AA95887 1
4103 E 605 N Suite 1
Rigby, ID 83442
208.932.4428
File name:
22247FB08032023BC
Compressive Strength of Concrete Test Specimens
Project Number:
22-247
Cumulative Test Load Amount:
10
Project Name:
U-Haul Moving and Storage
Test Location:
Site Elements, southwest side of building B
Client:
Bateman-Hall
Admixtures:
AE200, POLY980, DELVO
Ticket Number:
22413731
Contractor:
Bryant Greene Construction Inc.
Supplier:
Knife River
Mix Number:
C401G426
Date:
7/27/2023
Cylinder Log #:
424
Set #:
1
Entrained Air (%):
5.0
Concrete Temperature (°F):
72
Ambient Temperature (°F):
64
Unit Weight (PCF):
143.1
Tested By:
Michael Hammar
Time Tested:
12:41 PM
Field Test Results:
Pick Up Date:
7/28/2023
Picked Up By:
Michael Hammar
Time:
2:47 PM
Max, Min Temperature:
80, 60
Compressive Strength Data
Initial Break Testing:
Cylinder
ID:
Break
Age:
Break
Date:
Diameter
(in):
Area
(in^2):
Maximum
Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
A 7 8/3/2023 4.000 12.57 56,360.0 4484 3,500.0 Type 6
Date:
08/03/2023
Reviewed By:
Luke Hammar
Signature:
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
2005B7CA-635D-4484-88F0-792CDF74E8E5 1
4103 E 605 N Suite 1
Rigby, ID 83442
208.932.4428
File Name:
22247C08112023EV
Compressive Strength of Concrete Test Specimens
Project Number:
22-247
Project Name:
U-Haul Moving and Storage
Client:
Bateman-Hall
Contractor:
Bryan Landon Construction
Date:
08/11/2023
Start Time:
06:45 AM
Supplier:
Walters Ready Mix
Mix Number:
142I 4000
Concrete Member:
Interior Slab
Required 28 day Strength (psi):
4,000.0
Admixtures:
Super P
Entrained Air Spec. (%):
N/A
Slump Spec. (inches):
6 Max
Testing Results
Testing:
Set #:Cumulative
Test
Load
Amount:
Ticket
Image:
Ticket
#:
Time
Tested:
Test
Location:
Ambient
Temp.
(°F):
Weight
of
Concrete
(lbs):
Unit
Weight
(PCF):
Concrete
Temp.
(°F):
Entrained
Air
(%):
Entrained
Air
Spec.
(%):
Slump
(in):
Slump
Spec.
(in):
1 121.0 7267 08:00
AM
East
half of
Building
A, 2nd
floor.
61 34.760 139.6 72 1.7 N/A 6 6 Max
Field Technician Information
Date:
08/11/2023
Total Trip Mileage:
22.00
Items observed are in general conformance with approved
project documents and jurisdictional requirements.
Items observed are NOT in general conformance with
approved project documents and jurisdictional
requirements. (Explanation to be given in Observations and/
or Remarks.)
Tested By:
Eric Vail
Signature:
Observations and/or Remarks:
I arrived on site and checked in with Mike Massey (Bateman-Hall) and Ryan Murdock (Bryan Landon
Construction) and was able to test the last truck of the day.
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
2005B7CA-635D-4484-88F0-792CDF74E8E5 2
After a yard was displaced, I was able to obtain a sample for testing. I tested for air, slump, and temp. Those
results were within spec and reported back to the appropriate parties.
After making strength cylinders I cleaned up my gear and observed the remainder of the pour.
Reviewed By:
Luke Hammar
Date:
08/11/2023
Signature:
Inspection Images:
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
7706B1FB-428E-4B15-B01A-675968CBD665 1
4103 E 605 N Suite 1
Rigby, ID 83442
208.932.4428
File Name:
22247C08172023LS
Compressive Strength of Concrete Test Specimens
Project Number:
22-247
Project Name:
U-Haul Moving and Storage
Client:
Bateman-Hall
Contractor:
BL Construction
Date:
08/17/2023
Time on Project:
3 hours
Start Time:
03:45 AM
Supplier:
Walter’s Ready Mix
Mix Number:
1421 4000
Concrete Member:
Interior Slab
Required 28 day Strength (psi):
4000.0
Admixtures:
MS WC 534, DELVO, MP 322, SUPER
PLASTISIZER
Entrained Air Spec. (%):
N/A
Slump Spec. (inches):
6 Max
Testing Results
Testing:
Set #:Cumulative
Test
Load
Amount:
Ticket
Image:
Ticket
#:
Time
Tested:
Test
Location:
Ambient
Temp.
(°F):
Weight
of
Concrete
(lbs):
Unit
Weight
(PCF):
Concrete
Temp.
(°F):
Entrained
Air
(%):
Entrained
Air
Spec.
(%):
Slump
(in):
Slump
Spec.
(in):
1 10.0 07417 04:30
AM
Interior
floor,
2nd
level
55 36.400 146.2 75 1.9 N/A 7.5
inches
6 Max
2 50.0 07421 05:15
AM
2nd
floor
interior
slab
55 35.980 144.5 73 2.2 N/A 8
inches
6 Max
3 100.0 07427 06:00
AM
2nd
floor
interior
sub
flooring
53 36.360 146.0 71 1.8 N/A 7.75
inches
6 Max
Field Technician Information
Date:
08/17/2023
Total Trip Mileage:
Tested By:
Leland Stiener
Signature:
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
7706B1FB-428E-4B15-B01A-675968CBD665 2
20.00
Items observed are in general conformance with approved
project documents and jurisdictional requirements.
Items observed are NOT in general conformance with
approved project documents and jurisdictional
requirements. (Explanation to be given in Observations and/
or Remarks.)
Observations and/or Remarks:
I arrived on site at around 3:45am and began setting up for concrete testing. The first trucked arrived at around
4:30am and I began testing. I tested three times, at 10 yards, 50 yards, and 100 yards.
As I completed my tests I was able to report my results to the contractor and supplier.
I made strength specimens for each truck that I tested.
Upon completion of my last test I cleaned my equipment and wrote this report.
Reviewed By:
Luke Hammar
Date:
08/17/2023
Signature:
Inspection Images:
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
0DAB1752-2A44-4C7E-A978-5FBAC8A38735 1
4103 E 605 N Suite 1
Rigby, ID 83442
208.932.4428
File name:
22247FB08182023MDH
Compressive Strength of Concrete Test Specimens
Project Number:
22-247
Cumulative Test Load Amount:
121.0
Project Name:
U-Haul Moving and Storage
Test Location:
East half of Building A, 2nd floor.
Client:
Bateman-Hall
Admixtures:
Super P
Ticket Number:
7267
Contractor:
Bryan Landon Construction
Supplier:
Walters Ready Mix
Mix Number:
142I 4000
Date:
8/11/2023
Cylinder Log #:
452
Set #:
1
Entrained Air (%):
1.7
Concrete Temperature (°F):
72
Ambient Temperature (°F):
61
Unit Weight (PCF):
139.6
Tested By:
Eric Vail
Time Tested:
01:35 PM
Field Test Results:
Pick Up Date:
8/11/2023
Picked Up By:
Jense Christensen
Time:
9:00 AM
Max, Min Temperature:
80,60
Compressive Strength Data
Initial Break Testing:
Cylinder
ID:
Break
Age:
Break
Date:
Diameter
(in):
Area
(in^2):
Maximum
Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
A 7 8/18/2023 4.000 12.57 59,265.0 4715 4,000.0 Type 2
Date:
08/18/2023
Reviewed By:
E. Vail
Signature:
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
BFBA0F0B-4573-401C-9371-1CB698C353B2 1
4103 E 605 N Suite 1
Rigby, ID 83442
208.932.4428
File name:
22247SB08182023MDH
Compressive Strength of Concrete Test Specimens
Project Number:
22-247
Cumulative Test Load Amount:
11.0
Project Name:
U-Haul Moving and Storage
Test Location:
Exterior lab south west corner of building B
Client:
Bateman-Hall
Admixtures:
DELVO, ML ASR 30, MP
322, MA AE 90
Contractor:
Bryan Landon
Supplier:
Walters Ready Mix
Mix Number:
400-4500
Date:
7/21/2023
Cylinder Log #:
407
Set #:
2
Entrained Air (%):
6.1
Concrete Temperature (°F):
78
Ambient Temperature (°F):
74
Unit Weight (PCF):
140.0
Tested By:
Caleb Hammar
Date:
7/21/2023
Field Test Results:
Picked Up By:
B.Ferguson
Pick Up Date:
7/22/2023
Pick Up Time:
8:55 AM
Max, Min Temperature:
80, 60
Compressive Strength Data
Previous Test Results:
Cylinder ID:Break Age:Break Date:Area (in^2):Maximum Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
A 7 7/28/2023 12.57 60260 4794 4,000.00 Type 2
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
BFBA0F0B-4573-401C-9371-1CB698C353B2 2
Current Break Testing:
Cylinder
ID:
Break
Age:
Break
Date:
Diameter
(in):
Area
(in^2):
Maximum
Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
B 28 8/18/2023 4.000 12.57 71,695.0 5704 4,000.0 Type 1
C 28 8/18/2023 4.000 12.57 73,950.0 5883 4,000.0 Type 6
D 28 8/18/2023 4.000 12.57 75,645.0 6018 4,000.0 Type 1
Second Break Average:
5868
Date:
08/18/2023
Reviewed By:
E. Vail
Signature:
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
10758E1C-B064-4DAE-BE4A-F547CB059112 1
4103 E 605 N Suite 1
Rigby, ID 83442
208.932.4428
File name:
22247SB08182023MDH
Compressive Strength of Concrete Test Specimens
Project Number:
22-247
Cumulative Test Load Amount:
5.0
Project Name:
U-Haul Moving and Storage
Test Location:
Curb north of building B
Client:
Bateman-Hall
Admixtures:
AE200, POLY980, DELVO
Contractor:
Bryant Greene Construction
Supplier:
Knife River
Mix Number:
C401G426
Date:
7/21/2023
Cylinder Log #:
405
Set #:
1
Entrained Air (%):
6.3
Concrete Temperature (°F):
73
Ambient Temperature (°F):
74
Unit Weight (PCF):
140.8
Tested By:
Caleb Hammar
Date:
7/21/2023
Field Test Results:
Picked Up By:
B.Ferguson
Pick Up Date:
7/22/2023
Pick Up Time:
8:46 AM
Max, Min Temperature:
80, 60
Compressive Strength Data
Previous Test Results:
Cylinder ID:Break Age:Break Date:Area (in^2):Maximum Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
A 7 7/28/2023 12.57 53595 4264 4,000.00 Type 2
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
10758E1C-B064-4DAE-BE4A-F547CB059112 2
Current Break Testing:
Cylinder
ID:
Break
Age:
Break
Date:
Diameter
(in):
Area
(in^2):
Maximum
Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
B 28 8/18/2023 4.000 12.57 64,695.0 5147 4,000.0 Type 3
C 28 8/18/2023 4.000 12.57 65,135.0 5182 4,000.0 Type 6
D 28 8/18/2023 4.000 12.57 63,925.0 5086 4,000.0 Type 6
Second Break Average:
5138
Date:
08/18/2023
Reviewed By:
E. Vail
Signature:
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
294143FC-18AD-4B2F-AFEC-E3E11EB21D41 1
4103 E 605 N Suite 1
Rigby, ID 83442
208.932.4428
File name:
22247SB08222023MDH
Compressive Strength of Concrete Test Specimens
Project Number:
22-247
Cumulative Test Load Amount:
10.0
Project Name:
U-Haul Moving and Storage
Test Location:
Curb along the east entrance on N Third East
Client:
Bateman-Hall
Admixtures:
AE200, POLY980, DELVO
Contractor:
Bryant Greene Construction Inc.
Supplier:
Knife River
Mix Number:
C401G456
Date:
7/25/2023
Cylinder Log #:
416
Set #:
1
Entrained Air (%):
5.0
Concrete Temperature (°F):
78
Ambient Temperature (°F):
85
Unit Weight (PCF):
142.6
Tested By:
Bryce Choffin
Date:
7/25/2023
Field Test Results:
Picked Up By:
B. Choffin
Pick Up Date:
7/26/2023
Pick Up Time:
8:19 AM
Max, Min Temperature:
80, 60
Compressive Strength Data
Previous Test Results:
Cylinder ID:Break Age:Break Date:Area (in^2):Maximum Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
A 7 8/1/2023 12.57 57950 4610 3,500.00 Type 2
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
294143FC-18AD-4B2F-AFEC-E3E11EB21D41 2
Current Break Testing:
Cylinder
ID:
Break
Age:
Break
Date:
Diameter
(in):
Area
(in^2):
Maximum
Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
B 28 8/22/2023 4.000 12.57 65175.0 5185 3500.0 Type 1
C 28 8/22/2023 4.000 12.57 66120.0 5260 3500.0 Type 1
D 28 8/22/2023 4.000 12.57 68705.0 5466 3500.0 Type 1
Second Break Average:
5304
Date:
08/23/2023
Reviewed By:
Luke Hammar
Signature:
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
66244CC8-DAD7-45F6-B3C9-9F76BD375116 1
4103 E 605 N Suite 1
Rigby, ID 83442
208.932.4428
File name:
22247SB08232023MDH
Compressive Strength of Concrete Test Specimens
Project Number:
22-247
Cumulative Test Load Amount:
10.0
Project Name:
U-Haul Moving and Storage
Test Location:
Site elements, southeast corner of Building B
Client:
Bateman-Hall
Admixtures:
AE200, POLY980
Contractor:
Bryant Greene Construction Inc.
Supplier:
Knife River
Mix Number:
C401G426
Date:
7/26/2023
Cylinder Log #:
420
Set #:
1
Entrained Air (%):
5.5
Concrete Temperature (°F):
71
Ambient Temperature (°F):
65
Unit Weight (PCF):
141.8
Tested By:
Michael Hammar
Date:
7/26/2023
Field Test Results:
Picked Up By:
E. Vail
Pick Up Date:
7/27/2023
Pick Up Time:
1:00 PM
Max, Min Temperature:
80, 60
Compressive Strength Data
Previous Test Results:
Cylinder ID:Break Age:Break Date:Area (in^2):Maximum Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
A 7 8/2/2023 12.57 47685 3794 3,500.00 Type 2
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
66244CC8-DAD7-45F6-B3C9-9F76BD375116 2
Current Break Testing:
Cylinder
ID:
Break
Age:
Break
Date:
Diameter
(in):
Area
(in^2):
Maximum
Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
B 28 8/23/2023 4.000 12.57 62560.0 4977 3500.0 Type 1
C 28 8/23/2023 4.000 12.57 63515.0 5053 3500.0 Type 3
D 28 8/23/2023 4.000 12.57 65330.0 5197 3500.0 Type 3
Second Break Average:
5076
Date:
08/23/2023
Reviewed By:
Luke Hammar
Signature:
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
DBC9D8EF-ACE3-46C9-866D-02E20C287043 1
4103 E 605 N Suite 1
Rigby, ID 83442
208.932.4428
File Name:
22247C08252023LS
Compressive Strength of Concrete Test Specimens
Date:
08/25/2023
Project Number:
22-247
Project Name:
U-Haul Moving and Storage
Client:
Bateman-Hall
Time on Project:
3 hours
Start Time:
04:00 AM
Contractor:
Bryan Landon Construction
Supplier:
Walter’s Ready Mix, Inc
Mix Number:
142I 4000
Concrete Member:
Interior Slab
Required 28 day Strength (psi):
4000.0
Admixtures:
MS AC 534, DELVO, MP 322,
SUPERPLASTISIZER
Entrained Air Spec. (%):
N/A
Slump Spec. (inches):
6 Max
Results
Testing:
Set #:Cumulative
Test
Load
Amount:
Ticket
#:
Time
Tested:
Test Location:Ambient
Temp.
(°F):
Weight
of
Concrete
(lbs):
Unit
Weight
(PCF):
Concrete
Temp.
(°F):
Entrained
Air
(%):
Slump
(in):
1 10.0 07698 04:30
AM
Interior subfloor 2nd story 53 36.060 144.8 70 2.5 8
2 50.0 07702 05:15
AM
2nd level interior subfloor 53 36.640 147.1 73 2.1 7 1/2
3 110.0 07708 06:15
AM
2 level interior subfloor 50 36.710 147.4 69 1.7 8 1/4
Field Technician Information
Truck:
THOR
Total Trip Mileage:
20.00
Tested By:
Leland Steiner
Signature:
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
DBC9D8EF-ACE3-46C9-866D-02E20C287043 2
Items observed are in general conformance with approved project documents and jurisdictional requirements.
Items observed are NOT in general conformance with approved project documents and jurisdictional requirements.
(Explanation to be given in Observations and/or Remarks.)
Observations and/or Remarks:
I arrived on site around 4:00 AM and began my inspections. I then began setting up my equipment for my field
tests. Throughout the pour, I tested the concrete 3 different times, 50 yards apart. After each test I reported my
results to the contractor and made strength specimens. Upon completion I cleaned my gear and observed the
duration of the concrete placement.
Reviewed By:
Luke Hammar
Signature:
Inspection Images:
Testing:
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
DBC9D8EF-ACE3-46C9-866D-02E20C287043 3
Ticket Image:
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
DBC9D8EF-ACE3-46C9-866D-02E20C287043 4
Ticket Image:
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
DBC9D8EF-ACE3-46C9-866D-02E20C287043 5
Ticket Image:
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
1D3F0C75-F8FF-4F23-AA31-BD2F4350466F 1
4103 E 605 N Suite 1
Rigby, ID 83442
208.932.4428
File name:
22247SB08242023MDH
Compressive Strength of Concrete Test Specimens
Project Number:
22-247
Cumulative Test Load Amount:
10.0
Project Name:
U-Haul Moving and Storage
Test Location:
Site Elements, southwest side of building B
Client:
Bateman-Hall
Admixtures:
AE200, POLY980, DELVO
Contractor:
Bryant Greene Construction Inc.
Supplier:
Knife River
Mix Number:
C401G426
Date:
7/27/2023
Cylinder Log #:
424
Set #:
1
Entrained Air (%):
5.0
Concrete Temperature (°F):
72
Ambient Temperature (°F):
64
Unit Weight (PCF):
143.1
Tested By:
Michael Hammar
Date:
7/27/2023
Field Test Results:
Picked Up By:
Michael Hammar
Pick Up Date:
7/28/2023
Pick Up Time:
2:47 PM
Max, Min Temperature:
80, 60
Compressive Strength Data
Previous Test Results:
Cylinder ID:Break Age:Break Date:Area (in^2):Maximum Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
A 7 8/3/2023 12.57 56360 4484 3,500.00 Type 6
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
1D3F0C75-F8FF-4F23-AA31-BD2F4350466F 2
Current Break Testing:
Cylinder
ID:
Break
Age:
Break
Date:
Diameter
(in):
Area
(in^2):
Maximum
Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
B 28 8/24/2023 4.000 12.57 72635.0 5778 3500.0 Type 1
C 28 8/24/2023 4.000 12.57 75045.0 5970 3500.0 Type 1
D 28 8/24/2023 4.000 12.57 72950.0 5804 3500.0 Type 1
Second Break Average:
5851
Date:
08/28/2023
Reviewed By:
Luke Hammar
Signature:
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
3EAD8823-2DC4-4578-A121-9C5B53F4D3AA 1
4103 E 605 N Suite 1
Rigby, ID 83442
208.932.4428
File name:
22247FB08242023MDH
Compressive Strength of Concrete Test Specimens
Project Number:
22-247
Cumulative Test Load Amount:
10.0
Project Name:
U-Haul Moving and Storage
Test Location:
Interior floor, 2nd level
Client:
Bateman-Hall
Admixtures:
MS WC 534, DELVO, MP 322,
SUPER PLASTISIZER
Ticket Number:
7417
Contractor:
BL Construction
Supplier:
Walters Ready Mix
Mix Number:
1421 4000
Date:
8/17/2023
Cylinder Log #:
469
Set #:
1
Entrained Air (%):
1.9
Concrete Temperature (°F):
75
Ambient Temperature (°F):
55
Unit Weight (PCF):
146.2
Tested By:
Leland Stiener
Time Tested:
08:50 AM
Field Test Results:
Pick Up Date:
8/18/2023
Picked Up By:
Matthew Hammar
Time:
10:10 AM
Max, Min Temperature:
80, 60
Compressive Strength Data
Initial Break Testing:
Cylinder
ID:
Break
Age:
Break
Date:
Diameter
(in):
Area
(in^2):
Maximum
Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
A 7 8/24/2023 4.000 12.57 58710.0 4671 4000.0 Type 1
Date:
08/28/2023
Reviewed By:
Luke Hammar
Signature:
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
F7DE7675-585F-408C-8D7A-115F2C57041B 1
4103 E 605 N Suite 1
Rigby, ID 83442
208.932.4428
File name:
22247FB08242023MDH
Compressive Strength of Concrete Test Specimens
Project Number:
22-247
Cumulative Test Load Amount:
100.0
Project Name:
U-Haul Moving and Storage
Test Location:
2nd floor interior sub flooring
Client:
Bateman-Hall
Admixtures:
MS WC 534, DELVO, MP 322,
SUPER PLASTISIZER
Ticket Number:
7427
Contractor:
BL Construction
Supplier:
Walters Ready Mix
Mix Number:
1421 4000
Date:
8/17/2023
Cylinder Log #:
471
Set #:
3
Entrained Air (%):
1.8
Concrete Temperature (°F):
71
Ambient Temperature (°F):
53
Unit Weight (PCF):
146.0
Tested By:
Leland Stiener
Time Tested:
08:45 AM
Field Test Results:
Pick Up Date:
8/18/2023
Picked Up By:
Matthew Hammar
Time:
10:40 AM
Max, Min Temperature:
80, 60
Compressive Strength Data
Initial Break Testing:
Cylinder
ID:
Break
Age:
Break
Date:
Diameter
(in):
Area
(in^2):
Maximum
Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
A 7 8/24/2023 4.000 12.57 59705.0 4750 4000.0 Type 3
Date:
08/28/2023
Reviewed By:
Luke Hammar
Signature:
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
BC630ABC-512D-4FEB-A3A1-2AC0369CA4FF 1
4103 E 605 N Suite 1
Rigby, ID 83442
208.932.4428
File name:
22247FB08242023MDH
Compressive Strength of Concrete Test Specimens
Project Number:
22-247
Cumulative Test Load Amount:
50.0
Project Name:
U-Haul Moving and Storage
Test Location:
2nd floor interior slab
Client:
Bateman-Hall
Admixtures:
MS WC 534, DELVO, MP 322,
SUPER PLASTISIZER
Ticket Number:
7421
Contractor:
BL Construction
Supplier:
Walters Ready Mix
Mix Number:
1421 4000
Date:
8/17/2023
Cylinder Log #:
470
Set #:
2
Entrained Air (%):
2.2
Concrete Temperature (°F):
73
Ambient Temperature (°F):
55
Unit Weight (PCF):
144.5
Tested By:
Leland Stiener
Time Tested:
08:42 AM
Field Test Results:
Pick Up Date:
8/18/2023
Picked Up By:
Matthew Hammar
Time:
10:29 AM
Max, Min Temperature:
80, 60
Compressive Strength Data
Initial Break Testing:
Cylinder
ID:
Break
Age:
Break
Date:
Diameter
(in):
Area
(in^2):
Maximum
Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
A 7 8/24/2023 4.000 12.57 57330.0 4561 4000.0 Type 6
Date:
08/28/2023
Reviewed By:
Luke Hammar
Signature:
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
6FF3DC7E-E9A4-40B9-B2F5-D76C60FBAC9C 1
4103 E 605 N Suite 1
Rigby, ID 83442
208.932.4428
File name:
22247FB0912023MDH
Compressive Strength of Concrete Test Specimens
Project Number:
22-247
Cumulative Test Load Amount:
110.0
Project Name:
U-Haul Moving and Storage
Test Location:
2 level interior subfloor
Client:
Bateman-Hall
Admixtures:
MS AC 534, DELVO, MP 322,
SUPERPLASTISIZER
Ticket Number:
7708
Contractor:
Bryan Landon Construction
Supplier:
Walters Ready Mix, Inc
Mix Number:
142I 4000
Date:
8/25/2023
Cylinder Log #:
501
Set #:
3
Entrained Air (%):
1.7
Concrete Temperature (°F):
69
Ambient Temperature (°F):
50
Unit Weight (PCF):
147.4
Tested By:
Leland Steiner
Time Tested:
08:13 AM
Field Test Results:
Pick Up Date:
8/26/2023
Picked Up By:
L. Steiner
Time:
1:53 PM
Max, Min Temperature:
80,60
Compressive Strength Data
Initial Break Testing:
Cylinder
ID:
Break
Age:
Break
Date:
Diameter
(in):
Area
(in^2):
Maximum
Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
A 7 9/1/2023 4.000 12.57 64890.0 5162 4000.0 Type 1
Date:
09/01/2023
Reviewed By:
Luke Hammar
Signature:
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
900CB26B-0CEB-4122-9899-AB8D69A37368 1
4103 E 605 N Suite 1
Rigby, ID 83442
208.932.4428
File name:
22247FB0912023MDH
Compressive Strength of Concrete Test Specimens
Project Number:
22-247
Cumulative Test Load Amount:
50.0
Project Name:
U-Haul Moving and Storage
Test Location:
2nd level interior subfloor
Client:
Bateman-Hall
Admixtures:
MS AC 534, DELVO, MP 322,
SUPERPLASTISIZER
Ticket Number:
7702
Contractor:
Bryan Landon Construction
Supplier:
Walters Ready Mix, Inc
Mix Number:
142I 4000
Date:
8/25/2023
Cylinder Log #:
500
Set #:
2
Entrained Air (%):
2.1
Concrete Temperature (°F):
73
Ambient Temperature (°F):
53
Unit Weight (PCF):
147.1
Tested By:
Leland Steiner
Time Tested:
08:09 AM
Field Test Results:
Pick Up Date:
8/26/2023
Picked Up By:
L. Steiner
Time:
1:30 PM
Max, Min Temperature:
80,60
Compressive Strength Data
Initial Break Testing:
Cylinder
ID:
Break
Age:
Break
Date:
Diameter
(in):
Area
(in^2):
Maximum
Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
A 7 9/1/2023 4.000 12.57 58845.0 4681 4000.0 Type 3
Date:
09/01/2023
Reviewed By:
Luke Hammar
Signature:
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
D923B3A7-F3D9-4B7A-BC1F-75E955B79968 1
4103 E 605 N Suite 1
Rigby, ID 83442
208.932.4428
File name:
22247FB0912023MDH
Compressive Strength of Concrete Test Specimens
Project Number:
22-247
Cumulative Test Load Amount:
10.0
Project Name:
U-Haul Moving and Storage
Test Location:
Interior subfloor 2nd story
Client:
Bateman-Hall
Admixtures:
MS AC 534, DELVO, MP 322,
SUPERPLASTISIZER
Ticket Number:
7698
Contractor:
Bryan Landon Construction
Supplier:
Walters Ready Mix, Inc
Mix Number:
142I 4000
Date:
8/25/2023
Cylinder Log #:
499
Set #:
1
Entrained Air (%):
2.5
Concrete Temperature (°F):
70
Ambient Temperature (°F):
53
Unit Weight (PCF):
144.8
Tested By:
Leland Steiner
Time Tested:
08:03 AM
Field Test Results:
Pick Up Date:
8/26/2023
Picked Up By:
L. Steiner
Time:
1:20 PM
Max, Min Temperature:
76,60
Compressive Strength Data
Initial Break Testing:
Cylinder
ID:
Break
Age:
Break
Date:
Diameter
(in):
Area
(in^2):
Maximum
Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
A 7 9/1/2023 4.000 12.57 58270.0 4636 4000.0 Type 2
Date:
09/01/2023
Reviewed By:
Luke Hammar
Signature:
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
EF2B11CA-2D47-49F3-8D42-874A97563ABC 1
4103 E 605 N Suite 1
Rigby, ID 83442
208.932.4428
File Name:
23247C09112023BF
Compressive Strength of Concrete Test Specimens
Date:
09/11/2023
Project Number:
22-247
Project Name:
U-Haul Moving and Storage
Client:
Bateman-Hall
Time on Project:
4.5
Start Time:
04:15 AM
Contractor:
Bryan Landon Construction
Supplier:
Walters
Mix Number:
1421 4000
Concrete Member:
Interior Slab
Required 28 day Strength (psi):
4,000.0
Admixtures:
N/A
Entrained Air Spec. (%):
N/A
Slump Spec. (inches):
6 Max
Results
Testing:
Set #:Cumulative
Test
Load
Amount:
Ticket
#:
Time
Tested:
Test Location:Ambient
Temp.
(°F):
Weight
of
Concrete
(lbs):
Unit
Weight
(PCF):
Concrete
Temp.
(°F):
Entrained
Air
(%):
Slump
(in):
1 10.0 08102 05:00
AM
Second floor interior slab 65 36.660 147.2 72 1.5 8
2 60.0 08107 05:30
AM
Second floor interior slab 65 36.560 146.8 70 2 8
3 110.0 08113 06:00
AM
Second floor interior slab 68 36.240 145.5 71 2 8
Field Technician Information
Truck:
GROOT
Total Trip Mileage:
22.00
Tested By:
Bryton Ferguson
Signature:
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
EF2B11CA-2D47-49F3-8D42-874A97563ABC 2
Items observed are in general conformance with approved project documents and jurisdictional requirements.
Items observed are NOT in general conformance with approved project documents and jurisdictional requirements.
(Explanation to be given in Observations and/or Remarks.)
Observations and/or Remarks:
Arrived on site, spoke with Ryan Murdock (Bryan Landon Construction) regarding where would be best for me to
set up my equipment, they pumped 120 yards with a pump truck to the second floor slab. My tests were within
general acceptance of the job specific specifications. Informed Ryan of results.
Reviewed By:
E. Vail
Signature:
Inspection Images:
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
EF2B11CA-2D47-49F3-8D42-874A97563ABC 3
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
EF2B11CA-2D47-49F3-8D42-874A97563ABC 4
Testing:
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
EF2B11CA-2D47-49F3-8D42-874A97563ABC 5
Ticket Image:
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
EF2B11CA-2D47-49F3-8D42-874A97563ABC 6
Ticket Image:
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
EF2B11CA-2D47-49F3-8D42-874A97563ABC 7
Ticket Image:
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
5BA361B7-4104-4DE8-BA79-F8871C312801 1
4103 E 605 N Suite 1
Rigby, ID 83442
208.932.4428
File name:
22247SB09082023MDH
Compressive Strength of Concrete Test Specimens
Project Number:
22-247
Cumulative Test Load Amount:
121.0
Project Name:
U-Haul Moving and Storage
Test Location:
East half of Building A, 2nd floor.
Client:
Bateman-Hall
Admixtures:
Super P
Contractor:
Bryan Landon Construction
Supplier:
Walters Ready Mix
Mix Number:
142I 4000
Date:
8/11/2023
Cylinder Log #:
452
Set #:
1
Entrained Air (%):
1.7
Concrete Temperature (°F):
72
Ambient Temperature (°F):
61
Unit Weight (PCF):
139.6
Tested By:
Eric Vail
Date:
8/11/2023
Field Test Results:
Picked Up By:
Jense Christensen
Pick Up Date:
8/11/2023
Pick Up Time:
9:00 AM
Max, Min Temperature:
80,60
Compressive Strength Data
Previous Test Results:
Cylinder ID:Break Age:Break Date:Area (in^2):Maximum Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
A 7 8/18/2023 12.57 59265 4715 4,000.00 Type 2
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
5BA361B7-4104-4DE8-BA79-F8871C312801 2
Current Break Testing:
Cylinder
ID:
Break
Age:
Break
Date:
Diameter
(in):
Area
(in^2):
Maximum
Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
B 28 9/8/2023 4.000 12.57 71,830.0 5714 4,000.0 Type 3
C 28 9/8/2023 4.000 12.57 74,230.0 5905 4,000.0 Type 3
D 28 9/8/2023 4.000 12.57 73,755.0 5868 4,000.0 Type 3
Second Break Average:
5829
Date:
09/11/2023
Reviewed By:
E. Vail
Signature:
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
832590EE-7763-4424-B87B-F384FEA0060C 1
4103 E 605 N Suite 1
Rigby, ID 83442
208.932.4428
File Name:
22247C09132023BF
Compressive Strength of Concrete Test Specimens
Date:
09/13/2023
Project Number:
22-247
Project Name:
U-Haul Moving and Storage
Client:
Bateman-Hall
Time on Project:
4 Hours
Start Time:
06:46 AM
Contractor:
Bryan Landon Construction
Supplier:
Walters
Mix Number:
1421 4000
Concrete Member:
Interior Slab
Required 28 day Strength (psi):
4000.0
Admixtures:
N/A
Entrained Air Spec. (%):
N/A
Slump Spec. (inches):
6 Max
Results
Testing:
Set #:Cumulative
Test
Load
Amount:
Ticket
#:
Time
Tested:
Test Location:Ambient
Temp.
(°F):
Weight
of
Concrete
(lbs):
Unit
Weight
(PCF):
Concrete
Temp.
(°F):
Entrained
Air
(%):
Slump
(in):
1 10.0 08180 04:10
AM
Gridlines 27-E page S2 of plans 68 36.280 145.7 70 1.25 7.75
2 70.0 08186 05:15
AM
Gridlines 24-D page S2 of plans 68 36.340 145.9 70 1.5 8
3 110.0 08190 05:40
AM
Gridlines 26-B page S2 of plans 70 36.500 146.6 70 2 8
Field Technician Information
Truck:
GROOT
Total Trip Mileage:
22.00
Tested By:
Bryton Ferguson
Signature:
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
832590EE-7763-4424-B87B-F384FEA0060C 2
Items observed are in general conformance with approved project documents and jurisdictional requirements.
Items observed are NOT in general conformance with approved project documents and jurisdictional requirements.
(Explanation to be given in Observations and/or Remarks.)
Observations and/or Remarks:
I arrived on site and located where the concrete placement was to take place.
I set up my equipment and pulled my first sample. I performed a concrete field test and reported my results to
conractor. I then made stregth specimens.
I repeated this process two more time every 50 yards of concrete placed. All results were reported to the
contractor.
Upon completion of my final field test for the day I cleaned my equipment and observed the remainder of the
pour.
Reviewed By:
Luke Hammar
Signature:
Inspection Images:
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
832590EE-7763-4424-B87B-F384FEA0060C 3
Testing:
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
832590EE-7763-4424-B87B-F384FEA0060C 4
Ticket Image:
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
832590EE-7763-4424-B87B-F384FEA0060C 5
Ticket Image:
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
832590EE-7763-4424-B87B-F384FEA0060C 6
Ticket Image:
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
F0794576-A01B-4624-BAE3-C09753602299 1
4103 E 605 N Suite 1
Rigby, ID 83442
208.932.4428
File name:
22w47SB09142023MDH
Compressive Strength of Concrete Test Specimens
Project Number:
22-247
Cumulative Test Load Amount:
100.0
Project Name:
U-Haul Moving and Storage
Test Location:
2nd floor interior sub flooring
Client:
Bateman-Hall
Admixtures:
MS WC 534, DELVO, MP
322, SUPER PLASTISIZER
Contractor:
BL Construction
Supplier:
Walters Ready Mix
Mix Number:
1421 4000
Date:
8/17/2023
Cylinder Log #:
471
Set #:
3
Entrained Air (%):
1.8
Concrete Temperature (°F):
71
Ambient Temperature (°F):
53
Unit Weight (PCF):
146.0
Tested By:
Leland Stiener
Date:
8/17/2023
Field Test Results:
Picked Up By:
Matthew Hammar
Pick Up Date:
8/18/2023
Pick Up Time:
10:40 AM
Max, Min Temperature:
80, 60
Compressive Strength Data
Previous Test Results:
Cylinder ID:Break Age:Break Date:Area (in^2):Maximum Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
A 7 8/24/2023 12.57 59705 4750 4,000.00 Type 3
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
F0794576-A01B-4624-BAE3-C09753602299 2
Current Break Testing:
Cylinder
ID:
Break
Age:
Break
Date:
Diameter
(in):
Area
(in^2):
Maximum
Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
B 28 9/14/2023 4.000 12.57 75570.0 6012 4000.0 Type 6
C 28 9/14/2023 4.000 12.57 74885.0 5957 4000.0 Type 2
D 28 9/14/2023 4.000 12.57 77136.0 6137 4000.0 Type 1
Second Break Average:
6035
Date:
09/18/2023
Reviewed By:
Luke Hammar
Signature:
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
9A4D5FE1-F58F-456B-82AC-8ECC6161C41E 1
4103 E 605 N Suite 1
Rigby, ID 83442
208.932.4428
File name:
22247SB09142023MDH
Compressive Strength of Concrete Test Specimens
Project Number:
22-247
Cumulative Test Load Amount:
10.0
Project Name:
U-Haul Moving and Storage
Test Location:
Interior floor, 2nd level
Client:
Bateman-Hall
Admixtures:
MS WC 534, DELVO, MP
322, SUPER PLASTISIZER
Contractor:
BL Construction
Supplier:
Walters Ready Mix
Mix Number:
1421 4000
Date:
8/17/2023
Cylinder Log #:
469
Set #:
1
Entrained Air (%):
1.9
Concrete Temperature (°F):
75
Ambient Temperature (°F):
55
Unit Weight (PCF):
146.2
Tested By:
Leland Stiener
Date:
8/17/2023
Field Test Results:
Picked Up By:
Matthew Hammar
Pick Up Date:
8/18/2023
Pick Up Time:
10:10 AM
Max, Min Temperature:
80, 60
Compressive Strength Data
Previous Test Results:
Cylinder ID:Break Age:Break Date:Area (in^2):Maximum Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
A 7 8/24/2023 12.57 58710 4671 4,000.00 Type 1
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
9A4D5FE1-F58F-456B-82AC-8ECC6161C41E 2
Current Break Testing:
Cylinder
ID:
Break
Age:
Break
Date:
Diameter
(in):
Area
(in^2):
Maximum
Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
B 28 9/14/2023 4.000 12.57 75430.0 6001 4000.0 Type 1
C 28 9/14/2023 4.000 12.57 72180.0 5742 4000.0 Type 6
D 28 9/14/2023 4.000 12.57 72300.0 5752 4000.0 Type 6
Second Break Average:
5832
Date:
09/18/2023
Reviewed By:
Luke Hammar
Signature:
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
5B47D9E2-2F58-4161-A979-7EB472455835 1
4103 E 605 N Suite 1
Rigby, ID 83442
208.932.4428
File name:
22247SB09142023MDH
Compressive Strength of Concrete Test Specimens
Project Number:
22-247
Cumulative Test Load Amount:
50.0
Project Name:
U-Haul Moving and Storage
Test Location:
2nd floor interior slab
Client:
Bateman-Hall
Admixtures:
MS WC 534, DELVO, MP
322, SUPER PLASTISIZER
Contractor:
BL Construction
Supplier:
Walters Ready Mix
Mix Number:
1421 4000
Date:
8/17/2023
Cylinder Log #:
470
Set #:
2
Entrained Air (%):
2.2
Concrete Temperature (°F):
73
Ambient Temperature (°F):
55
Unit Weight (PCF):
144.5
Tested By:
Leland Stiener
Date:
8/17/2023
Field Test Results:
Picked Up By:
Matthew Hammar
Pick Up Date:
8/18/2023
Pick Up Time:
10:29 AM
Max, Min Temperature:
80, 60
Compressive Strength Data
Previous Test Results:
Cylinder ID:Break Age:Break Date:Area (in^2):Maximum Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
A 7 8/24/2023 12.57 57330 4561 4,000.00 Type 6
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
5B47D9E2-2F58-4161-A979-7EB472455835 2
Current Break Testing:
Cylinder
ID:
Break
Age:
Break
Date:
Diameter
(in):
Area
(in^2):
Maximum
Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
B 28 9/14/2023 4.000 12.57 70175.0 5583 4000.0 Type 1
C 28 9/14/2023 4.000 12.57 68570.0 5455 4000.0 Type 6
D 28 9/14/2023 4.000 12.57 72035.0 5731 4000.0 Type 3
Second Break Average:
5590
Date:
09/18/2023
Reviewed By:
Luke Hammar
Signature:
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
DF3D68A6-7FD9-4B29-8DE2-728ABD60E9CE 1
4103 E 605 N Suite 1
Rigby, ID 83442
208.932.4428
File Name:
22247C09202023EV
Compressive Strength of Concrete Test Specimens
Date:
09/20/2023
Project Number:
22-247
Project Name:
U-Haul Moving and Storage
Client:
Bateman-Hall
Time on Project:
3 hours
Start Time:
09:00 AM
Contractor:
Bryant Greene Construction
Supplier:
Knife River
Mix Number:
C401G456
Concrete Member:
Site Elements
Required 28 day Strength (psi):
3,500.0
Admixtures:
Air entrainment
Entrained Air Spec. (%):
6 +- 1.5
Slump Spec. (inches):
8 Max
Results
Testing:
Set #:Cumulative
Test
Load
Amount:
Ticket
#:
Time
Tested:
Test Location:Ambient
Temp.
(°F):
Weight
of
Concrete
(lbs):
Unit
Weight
(PCF):
Concrete
Temp.
(°F):
Entrained
Air
(%):
Slump
(in):
1 9.0 22416626 11:00
AM
NW most sidewalk. NW corner of
location.
63 34.260 137.6 65 6 7 1/4
Field Technician Information
Truck:
DEADPOOL
Total Trip Mileage:
30.00
Tested By:
Eric Vail
Signature:
Items observed are in general conformance with approved project documents and jurisdictional requirements.
Items observed are NOT in general conformance with approved project documents and jurisdictional requirements.
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
DF3D68A6-7FD9-4B29-8DE2-728ABD60E9CE 2
(Explanation to be given in Observations and/or Remarks.)
Observations and/or Remarks:
I arrived on site and spoke with Mike Massey of Bateman Hall who told me what they planned on pouring today.
He mentioned that concrete was about an hour late so I had time to look over the forms and rebar. The rebar
appeared to be in accordance with the specs and the forms were free of debris and appeared to be structurally
sound.
Eventually the concrete showed up and I was able to test for air, slump, and temp. They were within spec and I
reported that back to the appropriate parties.
After making strength cylinders I cleaned up my gear and left.
Reviewed By:
E. Vail
Signature:
Inspection Images:
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
DF3D68A6-7FD9-4B29-8DE2-728ABD60E9CE 3
Testing:
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
DF3D68A6-7FD9-4B29-8DE2-728ABD60E9CE 4
Ticket Image:
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
CDD64F8F-838B-4CB8-9D42-7837C86B482F 1
4103 E 605 N Suite 1
Rigby, ID 83442
208.932.4428
File name:
22247FB09192023MDH
Compressive Strength of Concrete Test Specimens
Project Number:
22-247
Cumulative Test Load Amount:
60
Project Name:
U-Haul Moving and Storage
Test Location:
Second floor interior slab
Client:
Bateman-Hall
Admixtures:
N/A
Ticket Number:
8107
Contractor:
Bryan Landon Construction
Supplier:
Walters
Mix Number:
1421 4000
Date:
9/11/2023
Cylinder Log #:
543
Set #:
2
Entrained Air (%):
2.0
Concrete Temperature (°F):
70
Ambient Temperature (°F):
69
Unit Weight (PCF):
146.8
Tested By:
Bryton Ferguson
Time Tested:
02:42 PM
Field Test Results:
Pick Up Date:
9/12/2023
Picked Up By:
Matthew Hammar
Time:
2:19 PM
Max, Min Temperature:
80, 60
Compressive Strength Data
Initial Break Testing:
Cylinder
ID:
Break
Age:
Break
Date:
Diameter
(in):
Area
(in^2):
Maximum
Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
A 7 9/18/2023 4.000 12.57 64,645.0 5143 4,000.0 Type 3
Date:
09/22/2023
Reviewed By:
Luke Hammar
Signature:
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
DED0B59B-4F43-4CF3-AE7B-E02D53065A29 1
4103 E 605 N Suite 1
Rigby, ID 83442
208.932.4428
File name:
22247FB09192023MDH
Compressive Strength of Concrete Test Specimens
Project Number:
22-247
Cumulative Test Load Amount:
110
Project Name:
U-Haul Moving and Storage
Test Location:
Second floor interior slab
Client:
Bateman-Hall
Admixtures:
N/A
Ticket Number:
8113
Contractor:
Bryan Landon Construction
Supplier:
Walters
Mix Number:
1421 4000
Date:
9/11/2023
Cylinder Log #:
544
Set #:
3
Entrained Air (%):
2.0
Concrete Temperature (°F):
71
Ambient Temperature (°F):
69
Unit Weight (PCF):
145.5
Tested By:
Bryton Ferguson
Time Tested:
02:39 PM
Field Test Results:
Pick Up Date:
9/12/2023
Picked Up By:
Matthew Hammar
Time:
2:29 PM
Max, Min Temperature:
80, 60
Compressive Strength Data
Initial Break Testing:
Cylinder
ID:
Break
Age:
Break
Date:
Diameter
(in):
Area
(in^2):
Maximum
Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
A 7 9/18/2023 4.000 12.57 64,440.0 5126 4,000.0 Type 3
Date:
09/22/2023
Reviewed By:
Luke Hammar
Signature:
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
50E5F95A-EBDC-489B-B6FB-26DB102F17FD 1
4103 E 605 N Suite 1
Rigby, ID 83442
208.932.4428
File name:
22247FB09192023MDH
Compressive Strength of Concrete Test Specimens
Project Number:
22-247
Cumulative Test Load Amount:
10
Project Name:
U-Haul Moving and Storage
Test Location:
Second floor interior slab
Client:
Bateman-Hall
Admixtures:
N/A
Ticket Number:
8102
Contractor:
Bryan Landon Construction
Supplier:
Walters
Mix Number:
1421 4000
Date:
9/11/2023
Cylinder Log #:
542
Set #:
1
Entrained Air (%):
1.5
Concrete Temperature (°F):
72
Ambient Temperature (°F):
69
Unit Weight (PCF):
147.2
Tested By:
Bryton Ferguson
Time Tested:
02:35 PM
Field Test Results:
Pick Up Date:
9/12/2023
Picked Up By:
Matthew Hammar
Time:
2:08 PM
Max, Min Temperature:
80, 60
Compressive Strength Data
Initial Break Testing:
Cylinder
ID:
Break
Age:
Break
Date:
Diameter
(in):
Area
(in^2):
Maximum
Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
A 7 9/18/2023 4.000 12.57 63,845.0 5079 4,000.0 Type 6
Date:
09/22/2023
Reviewed By:
Luke Hammar
Signature:
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
8E587498-6A67-48E3-8DC0-6EA1CDEFBA03 1
4103 E 605 N Suite 1
Rigby, ID 83442
208.932.4428
File name:
22247FB09202023MDH
Compressive Strength of Concrete Test Specimens
Project Number:
22-247
Cumulative Test Load Amount:
10.0
Project Name:
U-Haul Moving and Storage
Test Location:
Gridlines 27-E page S2 of plans
Client:
Bateman-Hall
Admixtures:
MS AC 534, DELVO, MP 322,
SUPERPLASTISIZER
Ticket Number:
8180
Contractor:
Bryan Landon Construction
Supplier:
Walters
Mix Number:
1421 4000
Date:
9/13/2023
Cylinder Log #:
554
Set #:
1
Entrained Air (%):
1.2
Concrete Temperature (°F):
70
Ambient Temperature (°F):
68
Unit Weight (PCF):
145.7
Tested By:
Bryton Ferguson
Time Tested:
08:29 AM
Field Test Results:
Pick Up Date:
9/14/2023
Picked Up By:
Matthew Hammar
Time:
1:01 PM
Max, Min Temperature:
80, 60
Compressive Strength Data
Initial Break Testing:
Cylinder
ID:
Break
Age:
Break
Date:
Diameter
(in):
Area
(in^2):
Maximum
Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
A 7 9/20/2023 4.000 12.57 49275.0 3920 3500.0 Type 6
Date:
09/22/2023
Reviewed By:
Luke Hammar
Signature:
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
75511E1F-9EDA-4454-AA56-94DCBF0B6A52 1
4103 E 605 N Suite 1
Rigby, ID 83442
208.932.4428
File name:
22247FB09202023MDH
Compressive Strength of Concrete Test Specimens
Project Number:
22-247
Cumulative Test Load Amount:
70.0
Project Name:
U-Haul Moving and Storage
Test Location:
Gridlines 24-D page S2 of plans
Client:
Bateman-Hall
Admixtures:
MS AC 534, DELVO, MP 322,
SUPERPLASTISIZER
Ticket Number:
8186
Contractor:
Bryan Landon Construction
Supplier:
Walters
Mix Number:
1421 4000
Date:
9/13/2023
Cylinder Log #:
555
Set #:
2
Entrained Air (%):
1.5
Concrete Temperature (°F):
70
Ambient Temperature (°F):
68
Unit Weight (PCF):
145.9
Tested By:
Bryton Ferguson
Time Tested:
08:24 AM
Field Test Results:
Pick Up Date:
9/14/2023
Picked Up By:
Matthew Hammar
Time:
1:30 PM
Max, Min Temperature:
80, 60
Compressive Strength Data
Initial Break Testing:
Cylinder
ID:
Break
Age:
Break
Date:
Diameter
(in):
Area
(in^2):
Maximum
Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
A 7 9/20/2023 4.000 12.57 54845.0 4363 3500.0 Type 1
Date:
09/22/2023
Reviewed By:
Luke Hammar
Signature:
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
86B14DB9-E53D-4EE5-8B4D-35E6A80B47C0 1
4103 E 605 N Suite 1
Rigby, ID 83442
208.932.4428
File name:
22247FB09202023MDH
Compressive Strength of Concrete Test Specimens
Project Number:
22-247
Cumulative Test Load Amount:
110.0
Project Name:
U-Haul Moving and Storage
Test Location:
Gridlines 26-B page S2 of plans
Client:
Bateman-Hall
Admixtures:
MS AC 534, DELVO, MP 322,
SUPERPLASTISIZER
Ticket Number:
8190
Contractor:
Bryan Landon Construction
Supplier:
Walters
Mix Number:
1421 4000
Date:
9/13/2023
Cylinder Log #:
556
Set #:
3
Entrained Air (%):
2.0
Concrete Temperature (°F):
70
Ambient Temperature (°F):
70
Unit Weight (PCF):
146.6
Tested By:
Bryton Ferguson
Time Tested:
08:20 AM
Field Test Results:
Pick Up Date:
9/14/2023
Picked Up By:
Matthew Hammar
Time:
1:38 PM
Max, Min Temperature:
80, 60
Compressive Strength Data
Initial Break Testing:
Cylinder
ID:
Break
Age:
Break
Date:
Diameter
(in):
Area
(in^2):
Maximum
Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
A 7 9/20/2023 4.000 12.57 53765.0 4277 3500.0 Type 2
Date:
09/22/2023
Reviewed By:
Luke Hammar
Signature:
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
7BD14591-7F44-4B9B-B528-FB35C1D58A45 1
4103 E 605 N Suite 1
Rigby, ID 83442
208.932.4428
File name:
22247SB09222023MDH
Compressive Strength of Concrete Test Specimens
Project Number:
22-247
Cumulative Test Load Amount:
10.0
Project Name:
U-Haul Moving and Storage
Test Location:
Interior subfloor 2nd story
Client:
Bateman-Hall
Admixtures:
MS AC 534, DELVO, MP
322, SUPERPLASTISIZER
Contractor:
Bryan Landon Construction
Supplier:
Walters Ready Mix, Inc
Mix Number:
142I 4000
Date:
8/25/2023
Cylinder Log #:
499
Set #:
1
Entrained Air (%):
2.5
Concrete Temperature (°F):
70
Ambient Temperature (°F):
53
Unit Weight (PCF):
144.8
Tested By:
Leland Steiner
Date:
8/25/2023
Field Test Results:
Picked Up By:
L. Steiner
Pick Up Date:
8/26/2023
Pick Up Time:
1:20 PM
Max, Min Temperature:
76,60
Compressive Strength Data
Previous Test Results:
Cylinder ID:Break Age:Break Date:Area (in^2):Maximum Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
A 7 9/1/2023 12.57 58270 4636 4000 Type 2
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
7BD14591-7F44-4B9B-B528-FB35C1D58A45 2
Current Break Testing:
Cylinder
ID:
Break
Age:
Break
Date:
Diameter
(in):
Area
(in^2):
Maximum
Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
B 28 9/22/2023 4.000 12.57 71300.0 5672 4000.0 Type 1
C 28 9/22/2023 4.000 12.57 72810.0 5792 4000.0 Type 3
D 28 9/22/2023 4.000 12.57 74910.0 5959 4000.0 Type 1
Second Break Average:
5808
Date:
09/25/2023
Reviewed By:
Luke Hammar
Signature:
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
576FBCAB-7D07-48AD-B6B8-DCF6253433FB 1
4103 E 605 N Suite 1
Rigby, ID 83442
208.932.4428
File name:
22247SB09222023MDH
Compressive Strength of Concrete Test Specimens
Project Number:
22-247
Cumulative Test Load Amount:
50.0
Project Name:
U-Haul Moving and Storage
Test Location:
2nd level interior subfloor
Client:
Bateman-Hall
Admixtures:
MS AC 534, DELVO, MP
322, SUPERPLASTISIZER
Contractor:
Bryan Landon Construction
Supplier:
Walters Ready Mix, Inc
Mix Number:
142I 4000
Date:
8/25/2023
Cylinder Log #:
500
Set #:
2
Entrained Air (%):
2.1
Concrete Temperature (°F):
73
Ambient Temperature (°F):
53
Unit Weight (PCF):
147.1
Tested By:
Leland Steiner
Date:
8/25/2023
Field Test Results:
Picked Up By:
L. Steiner
Pick Up Date:
8/26/2023
Pick Up Time:
1:30 PM
Max, Min Temperature:
80,60
Compressive Strength Data
Previous Test Results:
Cylinder ID:Break Age:Break Date:Area (in^2):Maximum Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
A 7 9/1/2023 12.57 58845 4681 4000 Type 3
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
576FBCAB-7D07-48AD-B6B8-DCF6253433FB 2
Current Break Testing:
Cylinder
ID:
Break
Age:
Break
Date:
Diameter
(in):
Area
(in^2):
Maximum
Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
B 28 9/22/2023 4.000 12.57 75215.0 5984 4000.0 Type 1
C 28 9/22/2023 4.000 12.57 71745.0 5708 4000.0 Type 6
D 28 9/22/2023 4.000 12.57 74740.0 5946 4000.0 Type 3
Second Break Average:
5879
Date:
09/25/2023
Reviewed By:
Luke Hammar
Signature:
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
516CF514-DEA0-4870-9E61-4B0EC99E0183 1
4103 E 605 N Suite 1
Rigby, ID 83442
208.932.4428
File name:
22247SB09222023MDH
Compressive Strength of Concrete Test Specimens
Project Number:
22-247
Cumulative Test Load Amount:
110.0
Project Name:
U-Haul Moving and Storage
Test Location:
2 level interior subfloor
Client:
Bateman-Hall
Admixtures:
MS AC 534, DELVO, MP
322, SUPERPLASTISIZER
Contractor:
Bryan Landon Construction
Supplier:
Walters Ready Mix, Inc
Mix Number:
142I 4000
Date:
8/25/2023
Cylinder Log #:
501
Set #:
3
Entrained Air (%):
1.7
Concrete Temperature (°F):
69
Ambient Temperature (°F):
50
Unit Weight (PCF):
147.4
Tested By:
Leland Steiner
Date:
8/25/2023
Field Test Results:
Picked Up By:
L. Steiner
Pick Up Date:
8/26/2023
Pick Up Time:
1:53 PM
Max, Min Temperature:
80,60
Compressive Strength Data
Previous Test Results:
Cylinder ID:Break Age:Break Date:Area (in^2):Maximum Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
A 7 9/1/2023 12.57 64890 5162 4000 Type 1
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
516CF514-DEA0-4870-9E61-4B0EC99E0183 2
Current Break Testing:
Cylinder
ID:
Break
Age:
Break
Date:
Diameter
(in):
Area
(in^2):
Maximum
Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
B 28 9/22/2023 4.000 12.57 74755.0 5947 4000.0 Type 1
C 28 9/22/2023 4.000 12.57 73700.0 5863 4000.0 Type 6
D 28 9/22/2023 4.000 12.57 73660.0 5860 4000.0 Type 3
Second Break Average:
5890
Date:
09/25/2023
Reviewed By:
Luke Hammar
Signature:
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
993C7787-2DC6-429F-B2CD-97AFED24FB82 1
4103 E 605 N Suite 1
Rigby, ID 83442
208.932.4428
File Name:
22247C09252023BF
Compressive Strength of Concrete Test Specimens
Date:
09/25/2023
Project Number:
22-247
Project Name:
U-Haul Moving and Storage
Client:
Bateman-Hall
Time on Project:
3 hours.
Start Time:
10:15 AM
Contractor:
Bryant Greene Construction
Supplier:
Knife River
Mix Number:
C416426
Concrete Member:
Site Elements
Required 28 day Strength (psi):
3500.0
Admixtures:
No
Entrained Air Spec. (%):
6 +- 1.5
Slump Spec. (inches):
8 Max
Results
Testing:
Set #:Cumulative
Test
Load
Amount:
Ticket
#:
Time
Tested:
Test Location:Ambient
Temp.
(°F):
Weight
of
Concrete
(lbs):
Unit
Weight
(PCF):
Concrete
Temp.
(°F):
Entrained
Air
(%):
Slump
(in):
1 10.0 22416739 11:40
AM
Curb west side of project next to
road
60 34.900 140.2 70 6 2.25
Field Technician Information
Truck:
STARLORD
Total Trip Mileage:
22.00
Tested By:
Bryton Ferguson
Signature:
Items observed are in general conformance with approved project documents and jurisdictional requirements.
Items observed are NOT in general conformance with approved project documents and jurisdictional requirements.
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
993C7787-2DC6-429F-B2CD-97AFED24FB82 2
(Explanation to be given in Observations and/or Remarks.)
Observations and/or Remarks:
I arrived ont site and located where the concrete placement was to take place.
I set up my gear and waited for concrete to arrive.
When the concrete truck arrived I was able to obtain a sample and perform a concrete field test.
I reported my results to the contractor and made strength specimens.
I then cleaned my equipment and observed the duration of the pour.
Reviewed By:
Luke Hammar
Signature:
Inspection Images:
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
993C7787-2DC6-429F-B2CD-97AFED24FB82 3
Testing:
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
993C7787-2DC6-429F-B2CD-97AFED24FB82 4
Ticket Image:
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
A31A0C1D-6476-401E-9BCF-E80C2828B499 1
4103 E 605 N Suite 1
Rigby, ID 83442
208.932.4428
File Name:
22247C09262023BF
Compressive Strength of Concrete Test Specimens
Date:
09/26/2023
Project Number:
22-247
Project Name:
U-Haul Moving and Storage
Client:
Bateman-Hall
Time on Project:
6.5 hours
Start Time:
09:31 AM
Contractor:
Bryan Landon Construction
Supplier:
Walter's Ready Mix
Mix Number:
1421 4000
Concrete Member:
Interior Slab
Required 28 day Strength (psi):
4000.0
Admixtures:
MS AC 534, Delvo, MP 322
Entrained Air Spec. (%):
N/A
Slump Spec. (inches):
6 Max
Results
Testing:
Set #:Cumulative
Test
Load
Amount:
Ticket
#:
Time
Tested:
Test Location:Ambient
Temp.
(°F):
Weight
of
Concrete
(lbs):
Unit
Weight
(PCF):
Concrete
Temp.
(°F):
Entrained
Air
(%):
Slump
(in):
1 10.0 08493 05:10
AM
3rd floor west side 45 36.600 147.0 65 1.25 6
2 60.0 08498 05:40
AM
3rd floor west side 45 36.200 145.4 61 1.5 6
3 110.0 08503 06:20
AM
3rd floor west side 45 36.500 146.6 60 1.5 5.75
Field Technician Information
Truck:
STARLORD
Total Trip Mileage:
22.00
Tested By:
Bryton Ferguson
Signature:
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
A31A0C1D-6476-401E-9BCF-E80C2828B499 2
Items observed are in general conformance with approved project documents and jurisdictional requirements.
Items observed are NOT in general conformance with approved project documents and jurisdictional requirements.
(Explanation to be given in Observations and/or Remarks.)
Observations and/or Remarks:
I arrived on site and located where the pour was to take place.
I set up my gear and awaited for the concrete to arrive.
Upon arrival I sampled from the first truck and performed a concrete field test.
I reported my results to the contractor and made strength specimens.
I repeated this process 2 more time every 50 yards of concrete placed.
Upon completion I cleaned my gear and observed the duration of the pour.
Reviewed By:
Luke Hammar
Signature:
Inspection Images:
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
A31A0C1D-6476-401E-9BCF-E80C2828B499 3
Testing:
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
A31A0C1D-6476-401E-9BCF-E80C2828B499 4
Ticket Image:
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
A31A0C1D-6476-401E-9BCF-E80C2828B499 5
Ticket Image:
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
A31A0C1D-6476-401E-9BCF-E80C2828B499 6
Ticket Image:
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
66ce3319-ae45-4619-8ac5-519e21a6134d 1
4103 E 605 N Suite 1
Rigby, ID 83442
208.932.4428
File Name:
22247C09262023BF 2
Compressive Strength of Concrete Test Specimens
Date:
09/26/2023
Project Number:
22-247
Project Name:
U-Haul Moving and Storage
Client:
Bateman-Hall
Time on Project:
2 hours
Start Time:
09:30 AM
Contractor:
Bryant Green Construction
Supplier:
Knife River
Mix Number:
C401G456
Concrete Member:
Site Elements
Required 28 day Strength (psi):
3500.0
Admixtures:
AE200, POLY980
Entrained Air Spec. (%):
6 +- 1.5
Slump Spec. (inches):
8 Max
Results
Testing:
Set #:Cumulative
Test
Load
Amount:
Ticket
#:
Time
Tested:
Test Location:Ambient
Temp.
(°F):
Weight
of
Concrete
(lbs):
Unit
Weight
(PCF):
Concrete
Temp.
(°F):
Entrained
Air
(%):
Slump
(in):
4 10.0 22416805 10:15
AM
Curb along south side of project 50 35.600 143.0 60 4.5 2 1/2
Field Technician Information
Truck:
STARLORD
Total Trip Mileage:
0.00
Tested By:
Bryton Ferguson
Signature:
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
66ce3319-ae45-4619-8ac5-519e21a6134d 2
Items observed are in general conformance with approved project documents and jurisdictional requirements.
Items observed are NOT in general conformance with approved project documents and jurisdictional requirements.
(Explanation to be given in Observations and/or Remarks.)
Observations and/or Remarks:
I arrived on site for another pour earlier in the morning. Once that pour was completed I located where the curb
pour was to take place and I set up my gear.
I tested the first truck that arrived on site and I reported my results to the contractor.
I then made strength specimens and cleaned my gear.
I observed the duration of the concrete placement.
Reviewed By:
Luke Hammar
Signature:
Inspection Images:
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
66ce3319-ae45-4619-8ac5-519e21a6134d 3
Testing:
Ticket Image:
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
8532ED54-B699-4388-82E6-0130DFDBDF34 1
4103 E 605 N Suite 1
Rigby, ID 83442
208.932.4428
File name:
22247FB10022023MDH
Compressive Strength of Concrete Test Specimens
Project Number:
22-247
Cumulative Test Load Amount:
10
Project Name:
U-Haul Moving and Storage
Test Location:
Curb west side of project next to road
Client:
Bateman-Hall
Admixtures:
N/A
Ticket Number:
22416739
Contractor:
Bryant Greene Construction
Supplier:
Knife River
Mix Number:
C416426
Date:
9/25/2023
Cylinder Log #:
596
Set #:
1
Entrained Air (%):
6.0
Concrete Temperature (°F):
70
Ambient Temperature (°F):
60
Unit Weight (PCF):
140.2
Tested By:
Bryton Ferguson
Time Tested:
04:37 PM
Field Test Results:
Pick Up Date:
9/26/2023
Picked Up By:
Matthew Hammar
Time:
4:55 PM
Max, Min Temperature:
80,60
Compressive Strength Data
Initial Break Testing:
Cylinder
ID:
Break
Age:
Break
Date:
Diameter
(in):
Area
(in^2):
Maximum
Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
A 7 10/2/2023 4.000 12.57 47,955.0 3815 3,500.0 Type 6
Date:
10/04/2023
Reviewed By:
Luke Hammar
Signature:
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
E730BB20-A1F5-416F-BCA9-AE0287698740 1
4103 E 605 N Suite 1
Rigby, ID 83442
208.932.4428
File name:
22247FB10032023MDH
Compressive Strength of Concrete Test Specimens
Project Number:
22-247
Cumulative Test Load Amount:
10
Project Name:
U-Haul Moving and Storage
Test Location:
1421 4000
Client:
Bateman-Hall
Admixtures:
MS AC 534, Delvo, MP 322
Ticket Number:
8493
Contractor:
Bryan Landon Construction
Supplier:
Walter's Ready Mix
Mix Number:
1421 4000
Date:
9/26/2023
Cylinder Log #:
610
Set #:
1
Entrained Air (%):
1.2
Concrete Temperature (°F):
65
Ambient Temperature (°F):
45
Unit Weight (PCF):
147
Tested By:
Bryton Ferguson
Time Tested:
08:40 AM
Field Test Results:
Pick Up Date:
9/27/2023
Picked Up By:
Matthew Hammar
Time:
3:56 PM
Max, Min Temperature:
80, 60
Compressive Strength Data
Initial Break Testing:
Cylinder
ID:
Break
Age:
Break
Date:
Diameter
(in):
Area
(in^2):
Maximum
Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
A 7 10/3/2023 4.000 12.57 54,405.0 4328 4,000.0 Type 1
Date:
10/04/2023
Reviewed By:
Luke Hammar
Signature:
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
F7A91FD5-46E5-4E30-B640-E7E785A19DDF 1
4103 E 605 N Suite 1
Rigby, ID 83442
208.932.4428
File name:
22247FB10032023MDH
Compressive Strength of Concrete Test Specimens
Project Number:
22-247
Cumulative Test Load Amount:
110.0
Project Name:
U-Haul Moving and Storage
Test Location:
1421 4000
Client:
Bateman-Hall
Admixtures:
MS AC 534, Delvo, MP 322
Ticket Number:
8503
Contractor:
Bryan Landon Construction
Supplier:
Walter's Ready Mix
Mix Number:
1421 4000
Date:
9/26/2023
Cylinder Log #:
612
Set #:
3
Entrained Air (%):
1.5
Concrete Temperature (°F):
60
Ambient Temperature (°F):
45
Unit Weight (PCF):
146.6
Tested By:
Bryton Ferguson
Time Tested:
08:57 AM
Field Test Results:
Pick Up Date:
9/27/2023
Picked Up By:
Matthew Hammar
Time:
4:34 PM
Max, Min Temperature:
80, 60
Compressive Strength Data
Initial Break Testing:
Cylinder
ID:
Break
Age:
Break
Date:
Diameter
(in):
Area
(in^2):
Maximum
Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
A 7 10/3/2023 4.000 12.57 55720.0 4433 4000.0 Type 3
Date:
10/05/2023
Reviewed By:
Luke Hammar
Signature:
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
B8999DA5-B2BB-46DC-A354-5639CB2E50E4 1
4103 E 605 N Suite 1
Rigby, ID 83442
208.932.4428
File name:
22247FB10032023MDH
Compressive Strength of Concrete Test Specimens
Project Number:
22-247
Cumulative Test Load Amount:
10.0
Project Name:
U-Haul Moving and Storage
Test Location:
C401G456
Client:
Bateman-Hall
Admixtures:
AE200, POLY980
Ticket Number:
22416805
Contractor:
Bryant Green Construction
Supplier:
Knife River
Mix Number:
C401G456
Date:
9/26/2023
Cylinder Log #:
613
Set #:
4
Entrained Air (%):
4.5
Concrete Temperature (°F):
60
Ambient Temperature (°F):
50
Unit Weight (PCF):
143.0
Tested By:
Bryton Ferguson
Time Tested:
08:54 AM
Field Test Results:
Pick Up Date:
9/27/2023
Picked Up By:
Matthew Hammar
Time:
4:41 PM
Max, Min Temperature:
80, 60
Compressive Strength Data
Initial Break Testing:
Cylinder
ID:
Break
Age:
Break
Date:
Diameter
(in):
Area
(in^2):
Maximum
Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
A 7 10/3/2023 4.000 12.57 58450.0 4650 3500.0 Type 2
Date:
10/05/2023
Reviewed By:
Luke Hammar
Signature:
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
D4E826E3-E37A-4DC3-A88A-DA1A653EEAF6 1
4103 E 605 N Suite 1
Rigby, ID 83442
208.932.4428
File name:
22247FB10032023MDH
Compressive Strength of Concrete Test Specimens
Project Number:
22-247
Cumulative Test Load Amount:
60.0
Project Name:
U-Haul Moving and Storage
Test Location:
1421 4000
Client:
Bateman-Hall
Admixtures:
MS AC 534, Delvo, MP 322
Ticket Number:
8498
Contractor:
Bryan Landon Construction
Supplier:
Walter's Ready Mix
Mix Number:
1421 4000
Date:
9/26/2023
Cylinder Log #:
611
Set #:
2
Entrained Air (%):
1.5
Concrete Temperature (°F):
61
Ambient Temperature (°F):
45
Unit Weight (PCF):
145.4
Tested By:
Bryton Ferguson
Time Tested:
08:43 AM
Field Test Results:
Pick Up Date:
9/27/2023
Picked Up By:
Matthew Hammar
Time:
4:13 PM
Max, Min Temperature:
80, 60
Compressive Strength Data
Initial Break Testing:
Cylinder
ID:
Break
Age:
Break
Date:
Diameter
(in):
Area
(in^2):
Maximum
Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
A 7 10/3/2023 4.000 12.57 54915.0 4369 4000.0 Type 6
Date:
10/05/2023
Reviewed By:
Luke Hammar
Signature:
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
B126E603-E9ED-4548-B702-6DA9367579E7 1
4103 E 605 N Suite 1
Rigby, ID 83442
208.932.4428
File name:
22247SB10112023MDH
Compressive Strength of Concrete Test Specimens
Project Number:
22-247
Cumulative Test Load Amount:
110
Project Name:
U-Haul Moving and Storage
Test Location:
Gridlines 26-B page S2 of plans
Client:
Bateman-Hall
Admixtures:
MS AC 534, DELVO, MP
322, SUPERPLASTISIZER
Contractor:
Bryan Landon Construction
Supplier:
Walters
Mix Number:
1421 4000
Date:
9/13/2023
Cylinder Log #:
556
Set #:
3
Entrained Air (%):
2.0
Concrete Temperature (°F):
70
Ambient Temperature (°F):
70
Unit Weight (PCF):
146.6
Tested By:
Bryton Ferguson
Date:
9/13/2023
Field Test Results:
Picked Up By:
Matthew Hammar
Pick Up Date:
9/14/2023
Pick Up Time:
1:38 PM
Max, Min Temperature:
80, 60
Compressive Strength Data
Previous Test Results:
Cylinder ID:Break Age:Break Date:Area (in^2):Maximum Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
A 7 9/20/2023 12.57 53765 4277 3500 Type 2
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
B126E603-E9ED-4548-B702-6DA9367579E7 2
Current Break Testing:
Cylinder
ID:
Break
Age:
Break
Date:
Diameter
(in):
Area
(in^2):
Maximum
Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
B 28 10/11/2023 4.000 12.57 64,415.0 5125 3,500.0 Type 3
C 28 10/11/2023 4.000 12.57 66,455.0 5287 3,500.0 Type 1
D 28 10/11/2023 4.000 12.57 68,240.0 5429 3,500.0 Type 1
Second Break Average:
5280
Date:
10/13/2023
Reviewed By:
Luke Hammar
Signature:
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
54E76831-B014-488D-9695-EF4526F98ED6 1
4103 E 605 N Suite 1
Rigby, ID 83442
208.932.4428
File name:
22247SB10112023MDH
Compressive Strength of Concrete Test Specimens
Project Number:
22-247
Cumulative Test Load Amount:
70
Project Name:
U-Haul Moving and Storage
Test Location:
Gridlines 24-D page S2 of plans
Client:
Bateman-Hall
Admixtures:
MS AC 534, DELVO, MP
322, SUPERPLASTISIZER
Contractor:
Bryan Landon Construction
Supplier:
Walters
Mix Number:
1421 4000
Date:
9/13/2023
Cylinder Log #:
555
Set #:
2
Entrained Air (%):
1.5
Concrete Temperature (°F):
70
Ambient Temperature (°F):
68
Unit Weight (PCF):
145.9
Tested By:
Bryton Ferguson
Date:
9/13/2023
Field Test Results:
Picked Up By:
Matthew Hammar
Pick Up Date:
9/14/2023
Pick Up Time:
1:30 PM
Max, Min Temperature:
80, 60
Compressive Strength Data
Previous Test Results:
Cylinder ID:Break Age:Break Date:Area (in^2):Maximum Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
A 7 9/20/2023 12.57 54845 4363 3500 Type 1
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
54E76831-B014-488D-9695-EF4526F98ED6 2
Current Break Testing:
Cylinder
ID:
Break
Age:
Break
Date:
Diameter
(in):
Area
(in^2):
Maximum
Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
B 28 10/11/2023 4.000 12.57 70,830.0 5635 3,500.0 Type 1
C 28 10/11/2023 4.000 12.57 71,270.0 5670 3,500.0 Type 3
D 28 10/11/2023 4.000 12.57 69,770.0 5551 3,500.0 Type 1
Second Break Average:
5619
Date:
10/13/2023
Reviewed By:
Luke Hammar
Signature:
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
25E37C65-AC6D-4B3B-8FF3-9D215A2D95BD 1
4103 E 605 N Suite 1
Rigby, ID 83442
208.932.4428
File name:
22247SB10112023MDH
Compressive Strength of Concrete Test Specimens
Project Number:
22-247
Cumulative Test Load Amount:
10.0
Project Name:
U-Haul Moving and Storage
Test Location:
Gridlines 27-E page S2 of plans
Client:
Bateman-Hall
Admixtures:
MS AC 534, DELVO, MP
322, SUPERPLASTISIZER
Contractor:
Bryan Landon Construction
Supplier:
Walters
Mix Number:
1421 4000
Date:
9/13/2023
Cylinder Log #:
554
Set #:
1
Entrained Air (%):
1.2
Concrete Temperature (°F):
70
Ambient Temperature (°F):
68
Unit Weight (PCF):
145.7
Tested By:
Bryton Ferguson
Date:
9/13/2023
Field Test Results:
Picked Up By:
Matthew Hammar
Pick Up Date:
9/14/2023
Pick Up Time:
1:01 PM
Max, Min Temperature:
80, 60
Compressive Strength Data
Previous Test Results:
Cylinder ID:Break Age:Break Date:Area (in^2):Maximum Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
A 7 9/20/2023 12.57 49275 3920 3500 Type 6
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
25E37C65-AC6D-4B3B-8FF3-9D215A2D95BD 2
Current Break Testing:
Cylinder
ID:
Break
Age:
Break
Date:
Diameter
(in):
Area
(in^2):
Maximum
Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
B 28 10/11/2023 4.000 12.57 62,730.0 4990 3,500.0 Type 3
C 28 10/11/2023 4.000 12.57 68,030.0 5412 3,500.0 Type 1
D 28 10/11/2023 4.000 12.57 65,485.0 5210 3,500.0 Type 3
Second Break Average:
5204
Date:
10/13/2023
Reviewed By:
Luke Hammar
Signature:
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
D854923C-3ABF-480E-B47D-AF0ED8B784F1 1
4103 E 605 N Suite 1
Rigby, ID 83442
208.932.4428
File name:
22247SB10092023MDH
Compressive Strength of Concrete Test Specimens
Project Number:
22-247
Cumulative Test Load Amount:
60
Project Name:
U-Haul Moving and Storage
Test Location:
Second floor interior slab
Client:
Bateman-Hall
Admixtures:
N/A
Contractor:
Bryan Landon Construction
Supplier:
Walters
Mix Number:
1421 4000
Date:
9/11/2023
Cylinder Log #:
543
Set #:
2
Entrained Air (%):
2.0
Concrete Temperature (°F):
70
Ambient Temperature (°F):
69
Unit Weight (PCF):
146.8
Tested By:
Bryton Ferguson
Date:
9/11/2023
Field Test Results:
Picked Up By:
Matthew Hammar
Pick Up Date:
9/12/2023
Pick Up Time:
2:19 PM
Max, Min Temperature:
80, 60
Compressive Strength Data
Previous Test Results:
Cylinder ID:Break Age:Break Date:Area (in^2):Maximum Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
A 7 9/18/2023 12.57 64645 5143 4,000.00 Type 3
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
D854923C-3ABF-480E-B47D-AF0ED8B784F1 2
Current Break Testing:
Cylinder
ID:
Break
Age:
Break
Date:
Diameter
(in):
Area
(in^2):
Maximum
Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
B 28 10/9/2023 4.000 12.57 79,755.0 6345 4,000.0 Type 1
C 28 10/9/2023 4.000 12.57 76,415.0 6079 4,000.0 Type 1
D 28 10/9/2023 4.000 12.57 78,375.0 6235 4,000.0 Type 3
Second Break Average:
6220
Date:
10/13/2023
Reviewed By:
Luke Hammar
Signature:
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
5067D2E1-DADB-4F09-A91A-AD0C89310E9D 1
4103 E 605 N Suite 1
Rigby, ID 83442
208.932.4428
File name:
22247SB10092023MDH
Compressive Strength of Concrete Test Specimens
Project Number:
22-247
Cumulative Test Load Amount:
10
Project Name:
U-Haul Moving and Storage
Test Location:
Second floor interior slab
Client:
Bateman-Hall
Admixtures:
N/A
Contractor:
Bryan Landon Construction
Supplier:
Walters
Mix Number:
1421 4000
Date:
9/11/2023
Cylinder Log #:
542
Set #:
1
Entrained Air (%):
1.5
Concrete Temperature (°F):
72
Ambient Temperature (°F):
69
Unit Weight (PCF):
147.2
Tested By:
Bryton Ferguson
Date:
9/11/2023
Field Test Results:
Picked Up By:
Matthew Hammar
Pick Up Date:
9/12/2023
Pick Up Time:
2:08 PM
Max, Min Temperature:
80, 60
Compressive Strength Data
Previous Test Results:
Cylinder ID:Break Age:Break Date:Area (in^2):Maximum Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
A 7 9/18/2023 12.57 63845 5079 4,000.00 Type 6
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
5067D2E1-DADB-4F09-A91A-AD0C89310E9D 2
Current Break Testing:
Cylinder
ID:
Break
Age:
Break
Date:
Diameter
(in):
Area
(in^2):
Maximum
Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
B 28 10/9/2023 4.000 12.57 77,360.0 6154 4,000.0 Type 3
C 28 10/9/2023 4.000 12.57 72,400.0 5760 4,000.0 Type 1
D 28 10/9/2023 4.000 12.57 73,455.0 5844 4,000.0 Type 2
Second Break Average:
5919
Date:
10/13/2023
Reviewed By:
Luke Hammar
Signature:
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
E321AF90-664C-4377-BDBA-87D36FBBF54B 1
4103 E 605 N Suite 1
Rigby, ID 83442
208.932.4428
File name:
22247SB10092023MDH
Compressive Strength of Concrete Test Specimens
Project Number:
22-247
Cumulative Test Load Amount:
110
Project Name:
U-Haul Moving and Storage
Test Location:
Second floor interior slab
Client:
Bateman-Hall
Admixtures:
N/A
Contractor:
Bryan Landon Construction
Supplier:
Walters
Mix Number:
1421 4000
Date:
9/11/2023
Cylinder Log #:
544
Set #:
3
Entrained Air (%):
2.0
Concrete Temperature (°F):
71
Ambient Temperature (°F):
69
Unit Weight (PCF):
145.5
Tested By:
Bryton Ferguson
Date:
9/11/2023
Field Test Results:
Picked Up By:
Matthew Hammar
Pick Up Date:
9/12/2023
Pick Up Time:
2:29 PM
Max, Min Temperature:
80, 60
Compressive Strength Data
Previous Test Results:
Cylinder ID:Break Age:Break Date:Area (in^2):Maximum Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
A 7 9/18/2023 12.57 64440 5126 4,000.00 Type 3
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
E321AF90-664C-4377-BDBA-87D36FBBF54B 2
Current Break Testing:
Cylinder
ID:
Break
Age:
Break
Date:
Diameter
(in):
Area
(in^2):
Maximum
Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
B 28 10/9/2023 4.000 12.57 76,370.0 6076 4,000.0 Type 3
C 28 10/9/2023 4.000 12.57 76,325.0 6072 4,000.0 Type 1
D 28 10/9/2023 4.000 12.57 75,720.0 6024 4,000.0 Type 1
Second Break Average:
6057
Date:
10/13/2023
Reviewed By:
Luke Hammar
Signature:
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
EB8E6276-0330-4F5F-A8B6-69CCAF4F482C 1
4103 E 605 N Suite 1
Rigby, ID 83442
208.932.4428
File name:
22247SB10162023MDH
Compressive Strength of Concrete Test Specimens
Project Number:
22-247
Cumulative Test Load Amount:
10.0
Project Name:
U-Haul Moving and Storage
Test Location:
West side sidewalk
Client:
Bateman-Hall
Admixtures:
AE200, POLY980
Contractor:
BRYANT GREENE CONSTRUCTION INC.
Supplier:
KNIFE RIVER
Mix Number:
C401G456
Date:
9/18/2023
Cylinder Log #:
575
Set #:
1
Entrained Air (%):
7.0
Concrete Temperature (°F):
68
Ambient Temperature (°F):
62
Unit Weight (PCF):
137.3
Tested By:
Matthew Hammar
Date:
9/18/2023
Field Test Results:
Picked Up By:
Matthew Hammar
Pick Up Date:
9/19/2023
Pick Up Time:
1:16 PM
Max, Min Temperature:
80, 60
Compressive Strength Data
Previous Test Results:
Cylinder ID:Break Age:Break Date:Area (in^2):Maximum Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
A 7 9/25/2023 12.57 38140 3034 4000 Type 6
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
EB8E6276-0330-4F5F-A8B6-69CCAF4F482C 2
Current Break Testing:
Cylinder
ID:
Break
Age:
Break
Date:
Diameter
(in):
Area
(in^2):
Maximum
Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
B 28 10/16/2023 4.000 12.57 49,770.0 3959 4,000.0 Type 3
C 28 10/16/2023 4.000 12.57 50,580.0 4024 4,000.0 Type 1
D 28 10/16/2023 4.000 12.57 50,785.0 4040 4,000.0 Type 2
E 28 10/16/2023 4.000 12.57 51,205.0 4074 4,000.0 Type 3
Second Break Average:
4024
Date:
10/18/2023
Reviewed By:
E. Vail
Signature:
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
A13D6BCB-0A23-4805-8FD0-A5728972DE8D 1
4103 E 605 N Suite 1
Rigby, ID 83442
208.932.4428
File name:
22247SB10232023MDH
Compressive Strength of Concrete Test Specimens
Project Number:
22-247
Cumulative Test Load Amount:
10
Project Name:
U-Haul Moving and Storage
Test Location:
Curb west side of project next to road
Client:
Bateman-Hall
Admixtures:
N/A
Contractor:
Bryant Greene Construction
Supplier:
Knife River
Mix Number:
C416426
Date:
9/25/2023
Cylinder Log #:
596
Set #:
1
Entrained Air (%):
6.0
Concrete Temperature (°F):
70
Ambient Temperature (°F):
60
Unit Weight (PCF):
140.2
Tested By:
Bryton Ferguson
Date:
9/25/2023
Field Test Results:
Picked Up By:
Matthew Hammar
Pick Up Date:
9/26/2023
Pick Up Time:
4:55 PM
Max, Min Temperature:
80,60
Compressive Strength Data
Previous Test Results:
Cylinder ID:Break Age:Break Date:Area (in^2):Maximum Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
A 7 10/2/2023 12.57 47955 3815 3500 Type 6
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
A13D6BCB-0A23-4805-8FD0-A5728972DE8D 2
Current Break Testing:
Cylinder
ID:
Break
Age:
Break
Date:
Diameter
(in):
Area
(in^2):
Maximum
Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
B 28 10/23/2023 4.000 12.57 58,560.0 4659 3,500.0 Type 1
C 28 10/23/2023 4.000 12.57 61,675.0 4907 3,500.0 Type 1
D 28 10/23/2023 4.000 12.57 57,940.0 4609 3,500.0 Type 2
Second Break Average:
4725
Date:
10/24/2023
Reviewed By:
Luke Hammar
Signature:
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
57956AAA-192D-47F2-97E3-E51C706C7745 1
4103 E 605 N Suite 1
Rigby, ID 83442
208.932.4428
File name:
22247SB10242023EV
Compressive Strength of Concrete Test Specimens
Project Number:
22-247
Cumulative Test Load Amount:
10.0
Project Name:
U-Haul Moving and Storage
Test Location:
C401G456
Client:
Bateman-Hall
Admixtures:
AE200, POLY980
Contractor:
Bryant Green Construction
Supplier:
Knife River
Mix Number:
C401G456
Date:
9/26/2023
Cylinder Log #:
613
Set #:
4
Entrained Air (%):
4.5
Concrete Temperature (°F):
60
Ambient Temperature (°F):
50
Unit Weight (PCF):
143.0
Tested By:
Bryton Ferguson
Date:
9/26/2023
Field Test Results:
Picked Up By:
Matthew Hammar
Pick Up Date:
9/27/2023
Pick Up Time:
4:41 PM
Max, Min Temperature:
80, 60
Compressive Strength Data
Previous Test Results:
Cylinder ID:Break Age:Break Date:Area (in^2):Maximum Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
A 7 10/3/2023 12.57 58450 4650 3500 Type 2
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
57956AAA-192D-47F2-97E3-E51C706C7745 2
Current Break Testing:
Cylinder
ID:
Break
Age:
Break
Date:
Diameter
(in):
Area
(in^2):
Maximum
Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
B 28 10/24/2023 4.000 12.57 73,960.0 5884 3,500.0 Type 2
C 28 10/24/2023 4.000 12.57 74,875.0 5957 3,500.0 Type 1
D 28 10/24/2023 4.000 12.57 74,700.0 5943 3,500.0 Type 1
Second Break Average:
5928
Date:
10/27/2023
Reviewed By:
E. Vail
Signature:
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
0D76AE86-5A98-45CD-BFC2-F1F8C6187671 1
4103 E 605 N Suite 1
Rigby, ID 83442
208.932.4428
File name:
22247SB10242023EV3
Compressive Strength of Concrete Test Specimens
Project Number:
22-247
Cumulative Test Load Amount:
10.0
Project Name:
U-Haul Moving and Storage
Test Location:
1421 4000
Client:
Bateman-Hall
Admixtures:
MS AC 534, Delvo, MP 322
Contractor:
Bryan Landon Construction
Supplier:
Walter's Ready Mix
Mix Number:
1421 4000
Date:
9/26/2023
Cylinder Log #:
610
Set #:
1
Entrained Air (%):
1.2
Concrete Temperature (°F):
65
Ambient Temperature (°F):
45
Unit Weight (PCF):
147.0
Tested By:
Bryton Ferguson
Date:
9/26/2023
Field Test Results:
Picked Up By:
Matthew Hammar
Pick Up Date:
9/27/2023
Pick Up Time:
3:56 PM
Max, Min Temperature:
80, 60
Compressive Strength Data
Previous Test Results:
Cylinder ID:Break Age:Break Date:Area (in^2):Maximum Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
A 7 10/3/2023 12.57 54405 4328 4000 Type 1
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
0D76AE86-5A98-45CD-BFC2-F1F8C6187671 2
Current Break Testing:
Cylinder
ID:
Break
Age:
Break
Date:
Diameter
(in):
Area
(in^2):
Maximum
Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
B 28 10/24/2023 4.000 12.57 72,845.0 5795 4,000.0 Type 2
C 28 10/24/2023 4.000 12.57 69,120.0 5499 4,000.0 Type 1
D 28 10/24/2023 4.000 12.57 71,425.0 5682 4,000.0 Type 2
Second Break Average:
5658
Date:
10/27/2023
Reviewed By:
E. Vail
Signature:
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
083D0950-9430-469A-8D8D-D213A9037173 1
4103 E 605 N Suite 1
Rigby, ID 83442
208.932.4428
File name:
22247SB10242023EV4
Compressive Strength of Concrete Test Specimens
Project Number:
22-247
Cumulative Test Load Amount:
60.0
Project Name:
U-Haul Moving and Storage
Test Location:
1421 4000
Client:
Bateman-Hall
Admixtures:
MS AC 534, Delvo, MP 322
Contractor:
Bryan Landon Construction
Supplier:
Walter's Ready Mix
Mix Number:
1421 4000
Date:
9/26/2023
Cylinder Log #:
611
Set #:
2
Entrained Air (%):
1.5
Concrete Temperature (°F):
61
Ambient Temperature (°F):
45
Unit Weight (PCF):
145.4
Tested By:
Bryton Ferguson
Date:
9/26/2023
Field Test Results:
Picked Up By:
Matthew Hammar
Pick Up Date:
9/27/2023
Pick Up Time:
4:13 PM
Max, Min Temperature:
80, 60
Compressive Strength Data
Previous Test Results:
Cylinder ID:Break Age:Break Date:Area (in^2):Maximum Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
A 7 10/3/2023 12.57 54915 4369 4000 Type 6
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
083D0950-9430-469A-8D8D-D213A9037173 2
Current Break Testing:
Cylinder
ID:
Break
Age:
Break
Date:
Diameter
(in):
Area
(in^2):
Maximum
Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
B 28 10/24/2023 4.000 12.57 74,460.0 5924 4,000.0 Type 6
C 28 10/24/2023 4.000 12.57 70,770.0 5630 4,000.0 Type 1
D 28 10/24/2023 4.000 12.57 69,930.0 5563 4,000.0 Type 2
Second Break Average:
5704
Date:
10/27/2023
Reviewed By:
E. Vail
Signature:
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
141B8CFC-ADC5-4514-9497-5A1BA153BDAA 1
4103 E 605 N Suite 1
Rigby, ID 83442
208.932.4428
File name:
22247SB12042023MDH
Compressive Strength of Concrete Test Specimens
Project Number:
22-247
Cumulative Test Load Amount:
9.0
Project Name:
U-Haul Moving and Storage
Test Location:
North facing exterior slab on the middle garage
entrance of U-Haul
Client:
Bateman-Hall
Admixtures:
AC534
Contractor:
BRYANT GREENE CONSTRUCTION
Supplier:
KNIFE RIVER
Mix Number:
C401G456
Date:
11/3/2023
Cylinder Log #:
694
Set #:
1
Entrained Air (%):
5.5
Concrete Temperature (°F):
68
Ambient Temperature (°F):
43
Unit Weight (PCF):
139.0
Tested By:
Matthew Hammar
Date:
11/3/2023
Field Test Results:
Picked Up By:
C Hammar
Pick Up Date:
11/4/2023
Pick Up Time:
5:00 PM
Max, Min Temperature:
80, 60
Compressive Strength Data
Previous Test Results:
Cylinder ID:Break Age:Break Date:Area (in^2):Maximum Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
A 7 11/10/2023 12.57 34990 2784 4,000.00 Type 3
PRIVILEGED AND CONFIDENTIAL: This document and the information contained herein are confidential and protected from disclosure. This message and its
content is intended only for the use of the addressee(s) and may contain sensitive, confidential information. If you are not the intended recipient, you are hereby
notified that the use, dissemination, or copying of this information is strictly prohibited, please notify the sender immediately.
141B8CFC-ADC5-4514-9497-5A1BA153BDAA 2
Current Break Testing:
Cylinder
ID:
Break
Age:
Break
Date:
Diameter
(in):
Area
(in^2):
Maximum
Load
(lbs):
Compressive
Strength
(psi):
Required
28 day
Strength
(psi):
Break
Type:
B 28 12/1/2023 4.000 12.57 48,135.0 3829 4,000.0 Type 2
C 28 12/1/2023 4.000 12.57 49,960.0 3975 4,000.0 Type 3
Second Break Average:
3902
Date:
12/04/2023
Reviewed By:
Luke Hammar
Signature: